Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan IGM Reference Document Including Modbus and BACnet object Listings

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

This referenceReference document is based on the assumption that the connecting module is of exec. 6 or exec. B firmware type unless otherwise noted.

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Revision Level Updates: Revision

Date

B.5 B.6 B.7 B.8 B.9 B.10 B.11 B.12

11/8/00 2/19/01 4/4/02 5/3/02 10/1/02 1/22/03 7/23/03 4/19/04

B.13

5/24/04

B.14

B.16

8/19/20 04 11/22/2 004 5/18/05

B.17

7/1/05

B.18

7/21/05

B.19 B.20

11/30/05 12/14/05

B.21

8/9/06

B.22

8/10/06

B.23

3/16/07

B.24 B.25 B.26 B.27

4/16/07 4/30/07 5/2/07 11/14/07

B.15

Description Added: revision level update chart, HiPulse support, and NPower support Revised NPower definition Added support for HiMod LNA Revised Modbus explanation (Hi Byte / Lo Byte) Corrected NPower table (typing error) Added support for DataMate Added support for STS-2 Corrected ModBus register addressing for STS-2 alarms. PM2 – removed duplicate Output Voltage THD Alarm. Added XDP Unit. Added LDS5000 Unit. Added Universal Monitor. Added BACNet/IP for: WDU, MM4, SC4, PM2 & LAM. Added Run Hours for MM2 Removed non-existent alarms for MM2. Added BacNet/IP Point addresses for MM2. Track issue 3576 – Make BacNet points consistent with Modbus Points. Added ESP-2 based UPS Units that use OC485 card. Includes Nx, HiNet, PSI, and GXT Added “High Water Humidifier Pan” alarm to L00. Corrected alarm points for BacnetBACNet and Modbus addressing on STS-2. Added Remote shutdown alarm to LAM. Added Note about Alarms “BacnetBACNet auto discovery” to CCM, L00, LAM, MMS, PM2, PMP, SCC. Added note to STS2 that it is for units with or without PDU. Changed breaker status register for STS2 from bits1-8 to 0-7. Added XDC Unit. Added control point note for units with on/off control as follows: Bit 0 on=unit off Bit 1 on=unit on. Removed cables 3 & 4 on LDS5000 and marked these registers as spares. Corrected revision level and date in header on this document. SMS – Added Scale factor for kVA & kW. Revised note on page 1 to state module type rather than “SS2000 Hardware”. Series 610 UPS – added note that Series 610 is the same as series 600. SC4-SM4 changed “Bypass Breaker Closed” alarm from “Bypass Breaker Open”. Added note to LAM that iCOM w/native IGM also applies. Nfinity UPS (pnf), Nx (pnx), STS-2 (st2) – deleted status and setpoint points that are not displayed in SiteScan. XDC, XDP added scale factor notes for Ref, Fluid and CW temps. PMP – Local Alarm #1 was Load Alarm, Added Local Alarm #2, Corrected Modbus addressing from 40290:04 to 40290:07 AC8 – Added Unit tables to reference library MM2 – Corrected entire table due to MS Word problems. Corrected major MS Word formatting problems throughout document. Added iCOM DS unit for 2mb modules (small version)

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Table of Contents Click on the desired page number for instant navigation. Use the “back” arrow on your toolbar to return to the table of contents. REVISION LEVEL UPDATES:........................................................................................................................................3 TABLE OF CONTENTS..................................................................................................................................................4

OPEN COMMUNICATIONS..............................................8 DEFAULT MAPPING FOR MODBUS & BACNET OBJECTS ............................................................................................8 MODBUS COMMUNICATIONS ....................................................................................................................................10 Connectivity to SiteLink modules using Modbus .................................................................................................10 Implementation Basics.........................................................................................................................................10 Transmission Format...........................................................................................................................................10 Modbus Packet Format........................................................................................................................................11 RTU Framing.......................................................................................................................................................12 BACNET COMMUNICATIONS ....................................................................................................................................13 BACnet Protocol Implementation Conformance Statement Rev. 2.1 ..............................................................13

LIEBERT ENVIRONMENTAL UNITS .............................17 AIR UNIT - LEVEL 0 – L00........................................................................................................................................18 AIR UNIT – LEVEL 10 – L10 .....................................................................................................................................20 AIR UNIT – STANDARD MICROPROCESSOR – LSM ...................................................................................................22 AIR UNIT – ADVANCED MICROPROCESSOR – LAM..................................................................................................24 AIR UNIT – SMALL SYSTEMS – L0B .........................................................................................................................27 AIR UNIT – MINI-MATE 2 – MM2, DATAMATE .......................................................................................................29 AIR UNIT – 8 TON MINIMATE – L8T........................................................................................................................31 ATLAS AIR UNIT – C10 ............................................................................................................................................34 CHILLER UNIT – CSU3000 – CSU............................................................................................................................37 CHILLER UNIT – CSU 3000 W/ECONO – CSE ...........................................................................................................39 AIR UNIT - HIROSS MICROFACE ...............................................................................................................................41 AIR UNIT – X-TREME DENSITY COOLANT DISTRIBUTION UNIT– CDU....................................................................44 AIR UNIT – X-TREME DENSITY COOLANT PUMPING UNIT– XDP ............................................................................46 AIR UNIT – X-TREME DENSITY CHILLER UNIT– XDC .............................................................................................48 AIR UNIT – ICOM DS & RETROFIT (2MB VERSION SITELINK) .................................................................................51

LIEBERT POWER UNITS...............................................54 POWER UNIT – VOLTAGE- CURRENT MONITORING PANEL – VCM ..........................................................................55 POWER UNIT – POWER MONITORING PANEL – PMP ................................................................................................57 POWER UNIT – VOLTAGE-CURRENT-FREQ. MONITOR PANEL – VCF.......................................................................60 POWER UNIT – POWER MONITORING PANEL (EXT. PROTOCOL– PM2......................................................................64 POWER UNIT – STATIC TRANSFER SWITCH PDU – EDS...........................................................................................68 POWER UNIT – STATIC TRANSFER SWITCH PDU DUAL OUTPUT – STS ...................................................................71 POWER UNIT – STATIC TRANSFER SWITCH PDU DUAL OUTPUT – STS-2 ................................................................74

LIEBERT UPS UNITS .....................................................77 UPS UNIT – MULTI MODULE UPS – S600/610 EXTENDED PROT. – MM4 ...............................................................81 UPS UNIT – MULTI MODULE SERIES – MMS...........................................................................................................84 UPS UNIT – SYSTEM CONTROL CABINET – S600/610 EXT. PROT. – SC4.................................................................89 UPS UNIT – SYSTEM CONTROL CABINET – SCC......................................................................................................92 UPS UNIT – SINGLE MODULE SERIES – SMS ...........................................................................................................94 UPS UNIT – SINGLE MODULE UPS – S600/610 EXT. PROT. – SM4 .........................................................................96

Revision B.27 11/14/2007 Liebert Monitoring Group - Development UPS UNIT – MULTI-MODULE SICE 7200 & HIPULSE UPS – SMM .......................................................................100 UPS UNIT – SYSTEMS CABINET SICE 7200 UPS – SSC.........................................................................................105 UPS UNIT – SINGLE MODULE SICE 7200 & HIPULSE UPS – SSM ........................................................................108 UPS UNIT – UPSTATION S – DCU .........................................................................................................................113 UPS UNIT – UPSTATION S3 – US3.........................................................................................................................116 UPS UNIT – SINGLE MODULE SERIES AP301/302 – SM3 ......................................................................................119 UPS UNIT – SINGLE MODULE UPS – NPOWER—IMP ...........................................................................................122 UPS UNIT – SINGLE MODULE UPS – NX—PNX ...................................................................................................127 UPS UNIT – HINET – PHN .....................................................................................................................................131 UPS UNIT – NFINITY – PNF...................................................................................................................................133 UPS UNIT – GXT – PGX........................................................................................................................................136 UPS UNIT – PSI – PPS ...........................................................................................................................................140

LIEBERT MONITORING MODULES ............................143 CONTACT CLOSURE MODULE – CCM ....................................................................................................................144 WATER/LIQUID DETECTION UNIT – WDU .............................................................................................................147 REMOTE AUTOCHANGEOVER – RAC......................................................................................................................148 TEMPERATURE/HUMIDITY MODULE – THM ..........................................................................................................150 WATER/LIQUID DETECTION UNIT LDS5000 – WD5 ..............................................................................................153 UNIVERSAL MONITOR – UVM ...............................................................................................................................154 AUTOCHANGEOVER CONTROLLER – AC8 ..............................................................................................................157

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

How to use the Reference Library Charts This document contains a dedicated sheet for each Liebert Unit and associated controller. The title of each chart contains the name of the Liebert Controller used such as L00 for a Level-0 Air unit or PMP for a Power Monitoring Panel for Power Center. The first section, Compatible Hardware, indicates the equipment associated with this particular controller as follows: Liebert Units Indicates the Environmental, Power, UPS or Monitoring Module by model name that uses this controller. SiteScan Interface Indicates which SiteScan Hardware Modules can be used with the controller. Take Modules Special note of this box when adding new units to an existing SiteScan system, as some new controllers are only compatible with the new hardware (SiteLink). BMS interface Modules Indicates which SiteScan Hardware Modules can be used with the controller for interfacing with a third part using BACnet or Modbus protocol. The next section, Available Points, contains six categories providing the following information: Status Points (View) Status Information for the listed points that will be presented in SiteScan Alarm Points Alarms that are available to SiteScan Setpoints (View) Current settings of controllable Setpoints available to SiteScan Control Points (Set) Setpoints that can be changed with SiteScan Trendable Points (Set) Points that can be graphically trended within the SiteScan software Reports Reports that can be triggered within the SiteScan software

Page 6 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

3-Letter ID L00

Liebert Unit ID Chart Environmental Products 3-Letter ID Level 00, Level 1 SMS

L10

Level 2, Level 3, and Level 10

SM3

LAM

Level 15 and Level AM/AG, HiMod (LNA), iCOM control w/ native IGM Level SM and Level 0 w/ On/Off Control Small Systems Controller

SM4

LSM L0B MM2

UPStation S3 UPS

MMS

SSC

Multi Module Series 500-600 UPS (Prior to 1/98) Multi Module Series 600600/610 UPS - Extended Protocol (1/98 or later) System Control Cabinet Series 500600 (Prior to 1/98) System Control Cabinet Series 600/610- Extended Protocol (1/98 or later) Single Module Series UPS - SICE 7200 & HiPulse Multi Module Series UPS - SICE 7200 & HiPulse System Control Cabinet - SICE 7200

IMP PNX

NPower (S300 Replacement) NX UPS – ESP2 Protocol

PHN

HiNet UPS – ESP2 Protocol

PNF PGX

Nfinity UPS – ESP2 Protocol GXT UPS – ESP2 Protocol

PPS

PSI UPS – ESP2 Protocol

MM4

CSE

CSU

Chiller

SSM

XDP

SMM

THM WDU

Xtreme Density Unit Environmental Control Xtreme Density Coolant DistibutionDistribution Unit DS Unit with iCOM control or Deluxe System 3 with iCOM control retrofit. Static Switch PDU Static Switch PDU (Single Output Breaker, Prior to 1/99) Static Switch PDU (Dual Output Breaker Option, 1/99 or later) Miscellaneous All IGM Contact Modules CM200 / RCM8 / VSM Remote Autochangeover Module RAC2-8 Temperature / Humidity Module Liquid Detection LDS750 or LDS1000

WD5

Liquid Detection LDS5000

VCF

UVM

Universal Monitor

VCM

AC8

Autochangeover Controller

PM2

CDU iCOM

EDS STS

CCM RAC

Page 7 of 158

Single Module Series UPS - S300, S500, S600 (Prior to 1/98) Single Module Series 30x (latest version) Single Module Series 600/610 Extended Protocol (1/98 or later)

US3

Small Systems Controller - Mini Mate II, DataMate Atlas Air Environmental Control (LECS15) Chiller w/ Econocoil

C10

UPS Products

SCC SC4

PMP

Power Products PDU Precision Power & DatawavesDatawave w/ PMP (latest LCD display) All Voltage-Current-Frequency Panels (Old Red LED Display) All Voltage-Current Monitoring Panels (Old Red LED Display) Precision Power & DatawavesDatawave w/ PMP (latest LCD display and extended protocol EPROM version 3.290.0, manufactured and shipped after 4/99)

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Open Communications Default Mapping for Modbus & BACnet Objects This model represents the standard configuration for a Liebert Sitelink-12 module. Consecutive register / object mapping is utilized, regardless of the SiteLink-12 population. All ports that do not have a Liebert IGM attached will be assigned “null values” (or zero’s) for their corresponding registers. The default “slave ID” or “Device ID” follows the CMnetCMNet address of the unit. The address can be visually checked by looking at the address dip-switch or rotary switch settings. However, the address can be changed in software to suit specific needs. How to use this table: The unit or model specific reference sheets assumessheets assume that the desired unit is attached to port 1 of the SiteLink module. If the desired unit is attached to a different port, the table below indicates the starting register or object number for the unit. For example: The register for “temperature” for a L00 type unit attached to port 1 is identified as 40001. If an additional L00 type unit were attached to port 2, the “temperature” value would be located in register 40025. The same type unit attached to port 3 = 40049…etc. Modbus Notes: •

Modbus Registers start at 40001.



All registers are unsigned integers.

BACnet Notes: •

BACnet Objects start at 1.



All “Status” and “Alarm” objects are “AI’s” (analog inputs).



The “Control” objects are “AO’s” (analog outputs)

Page 8 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Register Offset 1-24 25-48 49-72 73-96 97-120 121-144 145-168 169-192 193-216 217-240 241-264 265-288

Object Type Status Status Status Status Status Status Status Status Status Status Status Status

Port Assignment 1 2 3 4 5 6 7 8 9 10 11 12

289-293 294-298 299-303 304-308 309-313 314-318 319-323 324-328 329-333 334-338 339-343 344-348

Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms

1 2 3 4 5 6 7 8 9 10 11 12

349-351 Control 352-354 Control 355-357 Control 358-360 Control 361-363 Control 364-366 Control 367-369 Control 370-372 Control 373-375 Control 376-378 Control 379-381 Control 382-384 Control ** See reference libraries for unit specific objects.

Page 9 of 158

1 2 3 4 5 6 7 8 9 10 11 12

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Modbus Communications Connectivity to SiteLink modules using Modbus This design specification describes the Modbus communications protocol as supported by the SiteLink module. It includes information on how to pass information to and from the SiteLink module via Modbus. It is also intended to help facilitate answering questions regarding supported types, frame format, function code support etc.

Implementation Basics Protocol controls the language structure or message format between devices in other words, the rules for communication. The rules for communication include how master and slave devices initiate communications, as well as unit identification, message handling and error checking. Modbus protocol simply refers to the control of the query and response cycles between master and slave devices. The SiteLink module is configured to act as a slave device on a common network. The common network can be point-to-point over EIA-232, where one master communicates to one slave device or in a multi-drop configuration over EIA-485, where multiple slaves reside on a common wire or loop.

Transmission Format The SiteLink module supports both Modbus RTU (Remote Terminal Unit) and ASCII (American Standard Code for Information Interchange) transmission modes. The SiteLink module has a choice of transmission medium, baud rate, character parity and number of stop bits. See chart below. Physical Port EIA-232 – DB9 DCE EIA-232 – DB9 DCE

Transmission Mode RTU

Baud Rate

Data Bits

Parity Bits

Stop Bits

Default

9600

8

None

1

Yes

ASCII

Configurable

Configurable

Configurable

No

EIA-485 – 2 or 4 wire

RTU or ASCII

1200 – 38.4kbd (19.2kbd omit) 1200 – 38.4kbd (19.2kbd omit)

Configurable

Configurable

Configurable

No

Page 10 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Modbus Packet Format Each Modbus packet consists of the following fields: • • • •

Device Address Function Code Data Field(s) Error Check Field

Device Address: The address field immediately follows the beginning of the frame and consists of 8-bits (RTU) or 2 characters (ASCII). These bits indicate the user assigned address of the slave device that is to receive the message sent by the attached master device. Each slave must be assigned a unique address and only the addressed slave will respond to a query that contains its address. Function Code: The function code field tells the addressed slaves what function to perform. Function codes are specifically designed invoke a specific action by the slave device. The function code range is from 1 to 127. However, the SiteLink module primarily uses Function Code 3 (Read Holding Registers), Function Code 6 (Preset Single Register) and Function Code 16 (Preset Multiple Registers). Data Field(s): The data field varies in length depending on whether the message is a request or a response to a packet. This field typically contains information required by the slave device to perform the command specified or to pass back data to the master device. Error Check Field: The Error Check Field consists of a 16-bit (2 byte) Cyclical Redundancy Check (CRC16). It allows the receiving device to detect a packet that has been corrupted with transmission errors.

Page 11 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

RTU Framing The example below shows a typical Q/R from a SiteLink module. In common terms, the master device initiates a query asking slave device 2 for holding registers starting at holding register 40051 (decimal 50) and including next 2 Registers (3 total).

Query Sample Slave Address

Function Code

02

03

Starting Register “Hi Byte”

Starting Register “Lo Byte”

Number of Registers “Hi Byte”

Number of Registers “Lo Byte”

CRC16

CRC16

“Hi Byte”

“Lo Byte”

00

32

00

03

E5

FA

Count: Bytes of Data

Register 40051 Data Hi Lo

Register 40052 Data Hi Lo

Register 40053 Data Hi Lo

CRC16

CRC16

“Hi Byte

“Lo Byte”

1B

0D

Response Sample Slave Address

Function Code

02

03

6

01

58

00

FA

00

54

Slave address 2 responds to Function Code 3 with 6 bytes of hexadecimal data and ends with CRC16 checksum. Register values: 40051 = 158(hex) = 344(decimal) 40052 = FA (hex) = 250 (decimal) 40053 = 54 (hex) = 84 (decimal)

ASCII Framing: Framing in ASCII transmission mode is accomplished by the use of the unique colon (:) to indicate the beginning of the frame and a carriage return (CR) line feed (LF) to delineate the end of the frame. The line feed also serves as a synchronizing character which indicates that the transmitting station is ready to receive an immediate reply.

ASCII Example Frame Start

Slave Address

Function Code

Data

Error Check

End of Frame CR

Ready for Data LF

:

2 Char

2 Char

N x 4 Char

B3

0D

0A

16-bits

16-bits

N x 16-bits

Char = Character: 1 Character = 7 data bits, 1 start bit, 1 or 2 stop bits and 1 parity bit (optional)

Page 12 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

BACnet Communications BACnet Protocol Implementation Conformance Statement Vendor Name:

Liebert Corporation

Product Name:

SiteLink Module

Rev. 2.1

Product Model Number: SiteLink-DC12i, SiteLink-DC4i, SiteLink-12, and SiteLink-4

Product Description:

The SiteLink module provides a BACnet Point-to-Point communication exchange between proprietary Liebert Environmental, Power, UPS units to other BACnet compliant devices. The connection to the SiteLink module is via EIA-232, 9600 baud, no parity, 8 data bits, 1 stop bit (9600,N,8,1 default.) The SiteLink modules are available in 12 port and 4 port configurations (configurations (i.e. 1 port per/ Liebert Unit, 12 Liebert units per/ SiteLink module maximum.) Class 1 Class 2 Class 3

BACnet Conformance Class Supported: Class 4 Class 5 x Class 6 BACnet Functional Groups Supported:

Clock HHWS PCWS Event Initialization Event Response COV Event Initiation COV Event Response

Files Reinitialize Virtual Operator Interface Virtual Terminal Device Communications Time Master

Page 13 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development BACnet Standard Application Services Supported: Application Service Initiate Execute Requests Requests AcknowledgeAlarm ConfirmedCOVNotification ConfirmedEventNotification GetAlarmSummary GetEnrollmentSummary SubscribeCOV UnconfirmedCOVNotification UnconfirmedEventNotification AtomicReadFile AtomicWriteFile AddListElement RemoveListElement CreateObject DeleteObject ReadProperty ReadPropertyConditional ReadPropertyMultiple WriteProperty WritePropertyMultiple DeviceCommunicationControl ConfirmedPrivateTransfer UnconfirmedPrivateTransfer ReinitializeDevice ConfirmedTextMessage TimeSynchronization Who-Has I-Have Who-Is I-Am

X

X

X

X X X

X X X X

VT-Open VT-Closed VT-Data Authenticate Request Key

Page 14 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development BACnet Standard Application Services Supported (continued): Supported Dynamically Dynamically Optional Creatable Deleteable Properties X Analog Input X Analog Output Analog Value Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Loop Multi-State Input Multi-State Output Notification Class Program Schedule Object Type

Data Link Layer:

Point-to-Point, EIA-232, baud rates: 9600 & 38,400 Character Set Supported:

ANSI X3.4 Segmented Requests Supported Segmented Responses Supported Router

Special Functionality: No No No

Page 15 of 158

Writable Properties None Present Value

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Page 16 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Liebert Environmental Units

Page 17 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit - Level 0 – L00 Hardware Compatibility Liebert Units: Challenger 3, Logicool, Modular Plus, LS400, Mini-Tower, System 4 SiteScan Interface Modules: DC-1; DC4; DC12; SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Temperature Humidity Cooling Heating Humidification Dehumidification Econ-o-Cycle Stages % Capacity

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009

1 2 3 4 5 6 7 8 9

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x

Alarm Points Communications High Head Pressure 1 High Head Pressure 2 Loss of Airflow Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Local Alarm High Water Humidifier Pan

Notes:

1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff

Discrete BACnet alarm objects available – use auto-discover for this unit 40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40289:11

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 289:11

Page 18 of 158

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance

40010 40011 40012 40013

10 11 12 13

BS10_x BS11_x BS12_x BS13_x

Control Points (Set) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance

40350 40350 40351 40351

350 350 351 351

BC02_x BC02_x BC03_x BC03_x

Trendable points (Set) Temperature Humidity Reports Trend Status

Page 19 of 158

Notes:

Multiply desired value by 1000 Multiply desired value by 1000

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit – Level 10 – L10 Hardware Compatibility Liebert Units: Modular Plus, Deluxe System/3, Industrial Cooling Series SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Temperature Humidity Cooling Heating Humidification Dehumidification Econ-o-Cycle Stages % Capacity Alarm Points Communications High Head Pressure 1 High Head Pressure 2 Loss of Airflow Standby Glycol Unit On Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem No Water in Humidifier Pan Compressor 1 Overload Compressor 2 Overload Main Fan Overload

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009

1 2 3 4 5 6 7 8 9

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3 40290:4

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 290:4

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04

Page 20 of 158

Notes:

1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Manual Override Smoke Detected Loss of Water Standby Unit On Low Suction Short Cycle Loss of Power Inverter Bypass Standby Fan On Loss of Emergency Power Local Alarm 1 Local Alarm 2 Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance High Temperature Setpoint Low Temperature Setpoint High Humidity Setpoint Low Humidity Setpoint Auto-Restart Delay Control Points (Set) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40290:5 40290:6 40290:7 40290:8 40290:9 40290:10 40291:0 40291:1 40291:2 40291:3 40291:4 40291:5

290:5 290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2 291:3 291:4 291:5

BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA04_x:05

40010 40011 40012 40013 40014 40015 40016 40017

10 11 12 13 14 15 16 17

BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x

40350 40350 40351 40351

350 350 351 351

BC02_x BC02_x BC03_x BC03_x

Trendable Points (Set) Temperature Humidity Reports Trend Status

Page 21 of 158

Notes:

Multiply desired value by 1000 Multiply desired value by 1000

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit – Standard Microprocessor – LSM Hardware Compatibility Liebert Units: Challenger 3000. Deluxe System / 3, ICS , System 4 (Replaces L0A control) SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Status Points (View) Temperature Humidity Cooling Heating Humidification De-humidification Econ-O-Cycle Stages % Capacity Unit Status (On / Off)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40014

1 2 3 4 5 6 7 8 9 14

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS14_x

Alarm Points Communications Local Off Remote Off High Head Pressure 1 High Head Pressure 2 Loss of Airflow Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Local Alarm

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01

Page 22 of 158

Notes:

1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off

1=on / 0=off

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance

40010 40011 40012 40013

10 11 12 13

BS10_x BS11_x BS12_x BS13_x

Control Points (Set) Unit On / Off Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance

40349 40350 40350 40351 40351

349 350 350 351 351

BC01_x BC02_x BC02_x BC03_x BC03_x

Trendable Points (Set) Temperature Humidity Reports Trend Status

Page 23 of 158

Notes:

Bit 0 on=unit off Bit 1 on=unit on Multiply desired value by 1000 Multiply desired value by 1000

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit – Advanced Microprocessor – LAM Hardware Compatibility Liebert Units: Challenger 3000. Deluxe System / 3, ICS, System 4 (Replaces L15 & L1A) HiMod (LNA version) – iCOM control (Native IGM port) SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability

Status Points (View) Temperature Humidity Cooling Heating Humidification De-humidification Econ-O-Cycle Stages % Capacity Unit Status (On / Off)

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40018

1 2 3 4 5 6 7 8 9 18

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS18_x

Alarm Points Communications Local Off Remote Off High Head Pressure 1 High Head Pressure 2 Loss of Airflow Standby Glycol Unit On Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem No Water in Humidifier Pan

Notes:

1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off

1=on / 0=off Discrete BACnet alarm objects available – use auto-discover for this unit

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3

Page 24 of 158

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

Compressor 1 Overload Compressor 2 Overload Main Fan Overload Manual Override Smoke Detected Loss of Water Standby Unit On Low Suction Short Cycle Loss of Power Inverter on Bypass Standby Fan On Loss of Emergency Power Local Alarm 1 Local Alarm 2 Off by Remote Shutdown RunTimesRuntimes (View) Compressor 1 Run Hours Compressor 2 Run Hours Glycol Run Hours Fan Motor Run Hours Humidifier Run Hours Reheat 1 Run Hours Reheat 2 Run Hours Reheat 3 Run Hours Chilled Water Valve Run Hours

40290:4 40290:5 40290:6 40290:7 40290:8 40290:9 40290:10 40291:0 40291:1 40291:2 40291:3 40291:4 40291:5 40291:6 40291:7 40291:8

Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance High Temp Alarm Setpoint Low Temp Alarm Setpoint High Humd Alarm Setpoint Low Humidity Alarm Setpoint

BACnet Instance (Exec. 6 Modules) 290:4 290:5 290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2 291:3 291:4 291:5 291:6 291:7 291:9

BACnet Instance (Exec. B Modules) BA02:04_x BA02:05_x BA02:06_x BA02:07_x BA02:08_x BA02:09_x BA02:10_x BA03:00_x BA03:01_x BA03:02_x BA03:03_x BA03:04_x BA03:05_x BA03:06_x BA03:07_x BA03:08_x

Notes:

Runtimes not available on iCOM control 40019 40020

19 20

BS19_x BS20_x

40021 40022

21 22

BS21_x BS22_x

40010 40011 40012 40013 40014 40015 40016 40017

10 11 12 13 14 15 16 17

BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x

Page 25 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Control Points (Set) Unit On / Off Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance Reheat Lockout Humidifier Lockout

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40349 40350 40350 40351 40351 40349 40349

349 350 350 351 351 349 349

BC01_x BC02_x BC02_x BC03_x BC03_x BC01_x BC01_x

Trendable Points (Set) Temperature Humidity Reports Trend Status

Page 26 of 158

Notes:

Bit 0 on=unit off Bit 1 on=unit on Multiply desired value by 1000 Multiply desired value by 1000 Bit 2 on=RH off Bit 3 on=RH on Bit 4 on=HL off Bit 5 on=HL on

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit – Small Systems – L0B Hardware Compatibility Liebert Units: DatamateDataMate, Mini-Mate, Mini-Mate Plus SiteScan Interface Modules: DC-1; DC4; DC12; SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Temperature Humidity Cooling Heating Humidification Dehumidification Econ-o-Cycle Stages % Capacity Unit On/Off Alarm Points Communications Local Off Remote Off High Temperature Low Temperature High Humidity Low Humidity

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40011

1 2 3 4 5 6 7 8 9 11

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS11_x

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6

289:0 289:1 289:2 289:3 289:4 289:5 289:6

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06

40349

349

BC01_x

Notes:

1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff

1=on / 0=0ff

Setpoints (View) None Control Points (Set) Remote On/Off

Page 27 of 158

Bit 0 on=unit off Bit 1 on=unit on

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Trendable Points (Set) Temperature Humidity Reports Trend Status

Page 28 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit – Mini-Mate 2 – MM2, DataMate Hardware Compatibility Liebert Units: Mini-Mate 2, DataMate SiteScan Interface Modules: SiteLink BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Temperature Humidity Cooling Heating Humidification Dehumidification Econ-o-Cycle Stages % Capacity Unit On/Off Alarm Points Communications Local Off Remote Off High Head Pressure 1 Loss of Airflow Standby Glycol Unit On Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem Smoke Detected Loss of Water Flow Standby Unit On

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40018

1 2 3 4 5 6 7 8 9 18

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS18_x

40289:0 40289:1 40289:2 40289:3 40289:5 40289:6 40289:7 40289:8 40289:9 40290:0 40290:1 40290:2 40290:8 40290:9 40290:10

289:0 289:1 289:2 289:3 289:5 289:6 289:7 289:8 289:9

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:08 BA02_x:09 BA02_x:10

290:0 290:1 290:2 290:8 290:9 290:10

Page 29 of 158

Notes:

1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off

1=on / 0=off

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40291:1 40291:2 40291:6

291:1 291:2 291:6

BA03:01 BA03:02 BA03:06

40019 40020 40021

19 20 21

BS19_x BS20_x BS21_x

Setpoints (View) Temperature Temp Tolerance Humidity Humidity Tolerance High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm

40010 40011 40012 40013 40014 40015 40016 40017

10 11 12 13 14 15 16 17

BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x

Control Points (Set) Remote On/Off Temperature Setpoint Temperature Tolerance

40349 40350 40350

349 350 350

BC01_x BC02_x BC02_x

Humidity Setpoint Humidity Tolerance

40351 40351

351 351

BC03_x BC03_x

Alarm Points Short Cycle Loss of Power Local Alarm 1

Run Hours (View) Compressor 1 Fan Motor Humidifier Reheat 1 Reheat 2 Reheat 3 Chilled Water Valve

Trendable Points (Set) Temperature Humidity Reports Trend Status

Page 30 of 158

Notes:

Bit 0 on=unit off Bit 1 on=unit on Multiply desired value by 1000 (ModBus & BACNet 2.6 only) 0=No Change Multiply desired value by 1000 (ModBus & BACNet 2.6 only) 0=No Change

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit – 8 Ton MiniMate – L8T Hardware Compatibility Liebert Units: MinimateMiniMate - 8 Ton only SiteScan Interface Modules: DC-1; DC4-422; SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Temperature Humidity Cooling Heating Humidification De-humidification Econ-O-Cycle Stages % Capacity Unit Status (On / Off) Alarm Points Communications Local Off Remote Off High Head Pressure 1 High Head Pressure 2 Loss of Airflow Standby Glycol Unit On Not Used Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem Not Used

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40018

1 2 3 4 5 6 7 8 9 18

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS18_x

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x00 BA02_x01 BA02_x02 BA02_x03

Page 31 of 158

Notes:

1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off

1=on / 0=off

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Not Used Not Used Not Used Not Used Smoke Detected Loss of Water Standby Unit On Not Used Short Cycle Loss of Power Not Used Not Used Not Used Local Alarm 1 Local Alarm 2 Run Times (View) Compressor 1 Run Hours Compressor 2 Run Hours Glycol Run Hours Fan Motor Run Hours Humidifier Run Hours Reheat 1 Run Hours Reheat 2 Run Hours Reheat 3 Run Hours Chilled H2O Valve Run Hours Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance High Temperature Alarm Setpoint Low Temp Alarm Setpoint High Humidity Alarm Setpoint Low Humidity Alarm Setpoint

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40290:4 40290:5 40290:6 40290:7 40290:8 40290:9 40290:10 40291:0 40291:1 40291:2 40291:3 40291:4 40291:5 40291:6 40291:7

290:4 290:5 290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2 291:3 291:4 291:5 291:6 291:7

BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07

40019 40020

19 20

BS19_x BS20_x

40021 40022

21 22

BS21_x BS22_x

40010 40011 40012 40013 40014

10 11 12 13 14

BS10_x BS11_x BS12_x BS13_x BS14_x

40015 40016 40017

15 16 17

BS15_x BS16_x BS17_x

Page 32 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Control Points (Set) Unit On / Off Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance Reheat Lockout Humidifier Lockout

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40349 40350 40350 40351 40351 40349 40349

349 350 350 351 351 349 349

BC01_x BC02_x BC02_x BC03_x BC03_x BC01_x BC01_x

Trendable Points (Set) Temperature Humidity Reports Trend Status

Page 33 of 158

Notes:

Bit 0 on=unit off Bit 1 on=unit on Multiply desired value by 1000 Multiply desired value by 1000 Bit 2 on=RH off Bit 3 on=RH on Bit 4 on=HL off Bit 5 on=HL on

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Atlas Air Unit – C10 Hardware Compatibility Liebert Units: Atlas Air; LECS 15 SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Unit Number Average Return Air Temp. Average Return Air Humidity Average Supply Air Temp. Average Supply Air Humidity Activation Mode Fan Status Cool 1 Status Cool 2 Status Heat 1 Status Heat 2 Status Humidifier Status De-humidifier Status Cooling Capacity Heating Capacity Active Operation (Days) Active Operation (Hours) Cool Mode (Days) Cool Mode (Hours) Heat Mode (Days) Heat Mode (Hours) Humidifier Mode (Days) Humidifier Mode (Hours) De-humidifier Mode (Days) De-humidifier Mode (Hours) Cool 1 Operating Mode (Days) Cool 1 Operating Mode (Hours)

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x

Page 34 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Cool 2 Operating Mode (Days) Cool 2 Operating Mode (Hours) Fan Operation (Days) Fan Operation (Hours) Heat 1Operating Mode (Days) Heat 1Operating Mode (Hours) Heat 2 Operating Mode (Days) Heat 2 Operating Mode (Hours) Humidify Operating Mode (Days) Humidity Operating Mode (Hours) Cool Service (Days) Cool Service (Hours) Filter Service (Days) Filter Service (Hours) Humidifier Service (Days) Humidifier Service (Hours) Temperature Control Status Battery Voltage Level Remote Shutdown Status General Alarm Status Audible Alarm Status Temperature Control Select Alarm Points Communications Faulty Sensor High Temperature Low Temperature High Humidity Low Humidity Loss of Airflow Water Under Floor Cool 1 Low Pressure Alarm Cool 2 Low Pressure Alarm Cool 1 High Pressure Alarm Cool 2 High Pressure Alarm Cool Service Humidifier Service

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40019 40020 40021 40022 40023 40024

19 20 21 22 23 24

BS19_x BS20_x BS21_x BS22_x BS23_x BS24_x

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02

Page 35 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Filter Service Humidity Low Level Battery Level Low Loss of Power Spare 1 Spare 2 Setpoints (View) Unit Status (On / Off) Return Air Temperature Return Air Humidity Supply Air Temperature High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm Start up Delay Control Points (Set) Unit Status (On / Off) Return Air Temperature Return Air Humidity Supply Air Temperature High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm Start up Delay Trendable Points (Set) Average Return Air Temp. Average Return Air Humidity Average Supply Air Temp. Average Supply Air Humidity Reports Trend Status

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40290:3 40290:4 40290:5 40290:6 40290:7 40290:8

290:3 290:4 290:5 290:6 290:7 290:8

BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08

40016 40017 40018

16 17 18

BS16_x BS17_x BS18_x

40349 40350 40351

349 350 351

BC01_x BC02_x BC03_x

Page 36 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Chiller Unit – CSU3000 – CSU Hardware Compatibility Liebert Units: Chiller CSU-3000 SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Number of Modules Module 1 Start Module 1 Pump Module 1 Cool Module 2 Start Module 2 Pump Module 2 Cool Module 3 Start Module 3 Pump Module 3 Cool Alarm Points Communications Mod 1 High Head Pressure Mod 2 High Head Pressure Mod 3 High Head Pressure Module 1 No Water Flow Module 2 No Water Flow Module 3 No Water Flow Module 1 High Water Temp. Module 2 High Water Temp. Module 3 High Water Temp. Module 1 Low Water Temp. Module 2 Low Water Temp. Module 3 Low Water Temp. Module 1 No Power Module 2 No Power

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010

1 2 3 4 5 6 7 8 9 10

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03

Page 37 of 158

Notes:

1=START / 0=STOP 1=ON / 0=OFF 1=ON / 0=OFF 1=ON / 0=OFF 1=ON / 0=OFF 1=START / 0=STOP 1=ON / 0=OFF 1=ON / 0=OFF

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Module 3 No Power Module 1 Liquid Detected Module 2 Liquid Detected Module 3 Liquid Detected Local Alarm 1 Local Alarm 2

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40290:4 40290:5 40290:6 40290:7 40290:8 40290:9

290:4 290:5 290:6 290:7 290:8 290:9

BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09

Setpoints (View) None Control Points (Set) None Trendable Points (Set) None Reports Status

Page 38 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Chiller Unit – CSU 3000 w/Econo – CSE Hardware Compatibility Liebert Units: Chiller CSU-3000 SiteScan Interface Modules: DC-1; DC4-422; SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) System Econ-o-Cycle Number of Modules Module 1 Start Module 1 Pump Module 1 Cool Module 2 Start Module 2 Pump Module 2 Cool Module 3 Start Module 3 Pump Module 3 Cool Module 1 Econ-o-Cycle Module 2 Econ-o-Cycle Module 3 Econ-o-Cycle Alarm Points Communications Mod 1 High Head Pressure Mod 2 High Head Pressure Mod 3 High Head Pressure Module 1 No Water Flow Module 2 No Water Flow Module 3 No Water Flow Module 1 High Water Temp. Module 2 High Water Temp. Module 3 High Water Temp. Module 1 Low Water Temp.

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014

1 2 3 4 5 6 7 8 9 10 11 12 13 14

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10

Page 39 of 158

Notes:

1=ON / 0=OFF 1=START / 0=STOP 1=ON / 0=OFF 1=ON / 0=OFF 1=START / 0=STOP 1=ON / 0=OFF 1=ON / 0=OFF 1=START / 0=STOP 1=ON / 0=OFF 1=ON / 0=OFF 1=ON / 0=OFF 1=ON / 0=OFF 1=ON / 0=OFF

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Module 2 Low Water Temp. Module 3 Low Water Temp. Module 1 No Power Module 2 No Power Module 3 No Power

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40290:0 40290:1 40290:2 40290:3 40290:4

290:0 290:1 290:2 290:3 290:4

BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04

Setpoints (Set) None Control Points (Set) None Trendable Points (Set) None Reports Status

Page 40 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit -Unit - Hiross Microface Hardware Compatibility Liebert Units: Liebert Hiross Microface SiteScan Interface Modules: SiteLink (All) BMS interface Modules: Liebert Hiross Hirolink

Available Points SiteScan Availability

Modbus Register

Status Points (View) Unit On Off Heater Working Hours Humidifier Working Hours Compressor 1 Working Hours Conditioner Working Hours Low Humidity Warning High Humidity Warning Low Temperature Warning High Temperature Warning Humidity Proportional Band Temperature Proportional Band Room Humidity Setpoint Room Temperature Setpoint 1 Compressor 2 Working Hours Free-cooling Working Hours Cooling Ramp Status Dehumidification Status Electrical Heater 2 Status Electrical Heater 1 Status Compressor 1 Humidifier Current Room Humidity Room Temperature Status Compressor 2 Free-cooling Status

Page 41 of 158

BACnet Instance

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability Alarm Points Smoke Alarm No Power (User Input) Power On (User Input) User Input 2 Triggered User Input 2 Triggered No Connection To Unit 1 Compressor 1 Motor Protection Compressor 2 Motor Protection Fire Alarm Out Of Memory Condenser 1 Fan Failure Condenser 2 Fan Failure Network Ping Subgroup-Id Not Unique Subgroup-Unit 1 Not Connected Subgroup-Unit 2 Not Connected Share Rm. Sensor Failure Warn Share Rm. Sensor Failure Alarm Share Outdoor Temp Sensor Share Glycol Temp Sensor Unit Synch (Short Reset) Humidifier High Temperature Humidifier Overflow

Modbus Register

Setpoints (View) Room Temperature Setpoint 1 Temperature Proportional Band Room Humidity Setpoint Humidity Proportional Band High Temperature Alarm Setpoint Low Temp Alarm Setpoint High Humidity Alarm Setpoint Low Humidity Alarm Setpoint

Page 42 of 158

BACnet Instance

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability Control Points (Set) Unit On/Off Humidity Proportional Band Temperature Proportional Band Room Humidity Setpoint Room Temperature Setpoint

Modbus Register

Trendable Points (Set) Temperature Humidity Reports Trend Status

Page 43 of 158

BACnet Instance

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit – X-Treme Density Coolant Distribution Unit– CDU Hardware Compatibility Liebert Units: X-Treme Density Coolant DitributionDistribution Unit SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Valve % Open Pump 1 Status Pump 2 Status Fluid Level Fluid Temperature Stop Valve Purge Valve FMS Disable Rate Of Change Local Temp Local Humidity Local Dewpoint Remote Temp Remote Humidity Remote Dewpoint Unit Status

Alarm Points Communications Local Off Remote Off Loss Of Flow P1 Loss Of Flow P2 Pump Short Cycle Spare 5 Leak Detected Valve Failure Customer Alarm 1 Fan Fail High Fluid Temp Low Fluid Temp

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01

Page 44 of 158

Notes:

1=On / 0=Off 1=On / 0=Off

1=On / 0=Off 43=C / 46=F

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Fluid Sensor Problem High Remote Temp Low Remote Temp Remote Sensor Problem High Local Temp Low Local Temp Local Sensor Problem Low Pressure High Fluid Level Low Fluid Level Low Low Level Fluid Level ROC System Purge P1 Emergency Purge FMS Power Loss Loss Of Power

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06

290:2 290:3 290:4 290:5 290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2 291:3 291:4 291:5 291:6

BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06

Setpoints (View) Temperature Setpoint High Fluid Temp Setpoint Temp Scale High Air Temp Low Air Temp Dewpoint Margin Restart Delay

40017 40018

17 18

BS17_x BS18_x

40019 40020 40021 40022

19 20 21 22

BS19_x BS20_x BS21_x BS22_x

Control Points (Set) Unit On / Off Temperature Setpoint Dewpoint Margin

40349 40350 40351

49 50 51

BC01_x BC02_x BC03_x

Trendable Points (Set) Temperature Humidity Dewpoint Reports Trend Status

Page 45 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit – X-Treme Density Coolant Pumping Unit– XDP Hardware Compatibility Liebert Units: X-Treme Density Coolant Pumping Unit SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Status Points (View) Valve % Open Pump 1 Status Pump 2 Status Fluid Temperature Chilled Water Temperature Unit Status Scale F or C Local Temperature Local Humidity Local Dewpoint Remote Temperature Remote Humidity Remote Dewpoint

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013

1 2 3 4 5 6 7 8 9 10 11 12 13

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x

Alarm Points Communications Local Off Remote Off Loss Of Flow P1 Loss Of Flow P2 Pump Short Cycle Condensation Refrigerant Leak Valve Failure Customer Alarm 1 Fan Failure Alarm High Chilled Water Temp Low Chilled Water Temp Failed Chilled Water Sensor High Remote Temp Low Remote Temp Remote Sensor Problem

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 290:4 290:5

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05

Page 46 of 158

Notes:

1=On / 0=Off 1=On / 0=Off Divide by 10 for correct value Divide by 10 for correct value 1=On / 0=Off 43=C / 46=F

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02

290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2

BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02

Alarm Points High Local Temp Low Local Temp Local Sensor Problem Low Pressure High Refrigerant Temp Low Refrigerant Temp Failed Refrigerant Sensor Loss Of Power Setpoints (View) Temperature Setpoint Temperature Scale High Chilled Water Temp High Air Temp Low Air Temp Dewpoint Margin Restart Delay

40014

14

BS14_x

40015 40016 40017 40018 40019

15 16 17 18 19

BS15_x BS16_x BS17_x BS18_x BS19_x

Control Points (Set) Unit On / Off Temperature Setpoint Dewpoint Margin

40349 40350 40351

49 50 51

BC01_x BC02_x BC03_x

Trendable Points (Set) Temperature Humidity Dewpoint Reports Trend Status

Page 47 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit – X-Treme Density Chiller Unit– XDC Hardware Compatibility Liebert Units: X-Treme Density Chiller Unit SiteScan Interface Modules: SiteLink-12, SiteLink-4 BMS interface Modules: SiteLink-12, SiteLink-4

Available Points SiteScan Availability

Status Points (View) Pump 1 Status Pump 2 Status Cooling % Compressor 1A status Compressor 1B status HG Valve1 % Compressor 2A status Compressor 2B status HG Valve2 % Refer Temp 1 Refer Temp 2 CW Temp Unit Status Scale F or C Local Temp Local Humidity Local Dew Point Remote Temp Remote Humidity Remote Dew Point

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Notes:

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020

N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x

1=On / 0=Off 1=On / 0=Off

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08

N/A N/A N/A N/A N/A N/A N/A N/A N/A

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08

Alarm Points Communications Local Off Remote Off Loss Of Flow Pump 1 Loss Of Flow Pump 2 Pump Short Cycle Customer Alarm 1 Condensation Fan Failure Alarm

Page 48 of 158

1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off Divide by 10 for correct value Divide by 10 for correct value Divide by 10 for correct value 1=On / 0=Off 43=C / 46=F

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01 40292:02 40292:03

N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03

40021 40022 40023

N/A N/A N/A

BS21_x BS22_x BS23_x

Alarm Points High Local Temperature Low Local Temperature Local Sensor Problem High Remote Temperature Low Remote Temperature Remote Sensor Problem High Dewpoint High Head Compressor 1a High Head Compressor 1b High Head Compressor 2a High Head Compressor 2b Low Suction P Tandem 1 Low Suction P Tandem 2 Short Cycle Compressor 1a Short Cycle Compressor 1b Short Cycle Compressor 2a Short Cycle Compressor 2b High Refrigerant Temp 1 Low Refrigerant Temp 1 Failed Refrigerant Sensor 1 High Refrigerant Temp 2 Low Refrigerant Temp 2 Failed Refrigerant Sensor 2 High Chilled Water Temp Low Chilled Water Temp Failed Chilled Water Sensor Valve Failure Loss Of Power Setpoints (View) Temp Setpoint High Temp Setpoint Low Temp Setpoint

Page 49 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Control Points (Set) Unit On / Off Temperature Setpoint Dewpoint Margin

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40349 40350 -

N/A N/A N/A

BC01_x BC02_x -

Trendable Points Temperature Humidity Dewpoint Reports Trend

Page 50 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Air Unit – iCOM DS & Retrofit (2mb version SiteLink) Hardware Compatibility Liebert Units: iCOM DS controls and retrofit SiteScan Interface Modules: SiteLink-12, SiteLink-4, SiteLink-E BMS interface Modules: SiteLink-12, SiteLink-4, SiteLink-E

Available Points SiteScan Availability

Status Points (View) Unit On/Off Status Unit Standy Status Control Mode (Auto, Manual) Control Reason Fan Status Cooling Status Freecooling Status Hot Water State Electric Heater State Humidifier State De-humidifier State Audible Alarm State Cooling Ramp Heating Ramp Return Temp Return Humidity Run Hours (View) Conditioner Run Hrs. Comp 1 Run Hrs. Comp 2 Run Hrs. Humidifier Run Hrs. Reheat 1 Run Hrs. Reheat 2 Run Hrs. Reheat 3 Run Hrs. Setpoints (View) Front Display Temp Scale Humidifier Lockout Status Reheat Lockout Status Temperature Setpoint Temp Proportional Band Temp Deadband

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002

BS01 BS02

40003

BS03

40004 40005 40006

BS04 BS05 BS06

40007 40008 40009 40010

BS07 BS08 BS09 BS10

40011 40012 40013 40014

BS11 BS12 BS13 BS14

40015 40016 40017 40018

BS15 BS16 BS17 BS18

Page 51 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Setpoints (View) Humidity Setpoint Humd Proportional Band Humd Deadband Autorestart Delay IR Humidifier Flush Rate High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm Setpoints (Set) Temperature Setpoint Temp Proportional Band Temp Deadband Humidity Setpoint Humd Proportional Band Humd Deadband Autorestart Delay IR Humidifier Flush Rate High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm Commands (Set) Unit On/Off Humidifier Lockout Reheat Lockout Alarms Loss Of Comm Main Fan Overload Loss of Airflow Loss of Water Flow Compressor 1 High Pressure Compressor 1 Overload Compressor 2 High Pressure Compressor 2 Overload Smoke Detected Water Detected

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Notes:

40019 40020

BS19 BS20

40021 40022 40023 40024

BS21 BS22 BS23 BS24

40350 40350

BC02_1 BC02_2

Scale by 1000 (e.g. 2=2000 Modbus Only)

40351 40351

BC03_1 BC03_2

Scale by 1000 (e.g. 5=5000 Modbus Only)

40349:0,1 40349:2,3 40349:4,5

BC01_1 BC01_2 BC01_3

Bit pair 0,1;1=off, 2=on (Modbus Only) Bit pair 2,3; 1=normal, 2=lckout (Modbus Only) Bit pair 4,5; 1=normal, 2=lckout (Modbus Only) Discrete BACnet alarm objects available –use autodiscover for this unit

40289:0 40289:1 40289:2

BA01_x:0 BA01_x:1 BA01_x:2 BA01_x:3 BA01_x:4 BA01_x:5 BA01_x:6 BA01_x:7 BA01_x:8 BA01_x:9

40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9

Page 52 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarms Humidifier Problem Standby Unit On High Room Temp Low Room Temp High Room Humidity Low Room Humidity User Alarm #1 User Alarm #2 Unit On Unit Off Trends Return Temperature Return Humidity

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules) BA01_x:10 BA02_X:0 BA02_X:1 BA02_X:2 BA02_X:3 BA02_X:4 BA02_X:5 BA02_X:6 BA02_X:7 BA02_X:8

40289:10 40290:0 40290:1 40290:2 40290:3 40290:4 40290:5 40290:6 40290:7 40290:8

Page 53 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Liebert Power Units

Page 54 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Power Unit – Voltage- Current Monitoring Panel – VCM Hardware Compatibility Liebert Units: Datawave, Precision Power Center SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Voltage Out X-Y Voltage Out Y-Z Voltage Out Z-X Voltage Out X-N Voltage Out Y-N Voltage Out Z-N Current Out A Current Out B Current Out C Ground Current Neutral Current KVA Alarm Points Communications Output Undervoltage Output Overvoltage Transformer Overtemp Local Alarm #1 Local Alarm #2

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012

1 2 3 4 5 6 7 8 9 10 11 12

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5

289:0 289:1 289:2 289:3 289:4 289:5

BA01_x:00 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09

Setpoints (View) None Control Points (Set) None

Page 55 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Trendable Points (Set) Voltage Out X-Y Voltage Out Y-Z Voltage Out Z-X Voltage Out X-N Voltage Out Y-N Voltage Out Z-N Current Out A Current Out B Current Out C Ground Current Neutral Current kVA Reports Trend Status

Page 56 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Power Unit – Power Monitoring Panel – PMP Hardware Compatibility Liebert Units: Datawave, Precision Power Center SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C Ground Current Neutral Current KVA KW Frequency % Capacity A % Capacity B % Capacity C

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x

Alarm Points Communications Output Undervoltage Output Overvoltage Output Overcurrent Frequency Deviation

Notes:

Divide by 10 for correct value

Divide by 10 for correct value

Discrete BACnet alarm objects available –use auto-discover for this unit 40289:00 40289:01 40289:02 40289:03 40289:04

289:00 289:01 289:02 289:03 289:04

Page 57 of 158

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Ground Overcurrent Transformer Overtemp Ground Fault Ground Failure Liquid Detected Security Alarm Phase Rotation/Loss Datawave Overtemperature Emergency Shutdown Load On Bypass Local Alarm #1 Local Alarm #2 Custom Alarm #1 Custom Alarm #2

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07

289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07

BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07

Setpoints (View) None Control Points (Set) None Trendable Points (Set) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage In A-N Voltage In B-N Voltage In C-N

Page 58 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Trendable Points (Set) Current Out A Current Out B Current Out C % Capacity A % Capacity B % Capacity C Ground Current Neutral Current KW KVA Reports Trend Status

Page 59 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Power Unit – Voltage-Current-Freq. Monitor Panel – VCF Hardware Compatibility Liebert Units: MPU4000, Datawave, Precision Power Center SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Voltage Out X-Y Voltage Out Y-Z Voltage Out Z-X Voltage Out X-N Voltage Out Y-N Voltage Out Z-N Current Out A Current Out B Current Out C Ground Current Neutral Current KVA Frequency Alarm Points Communications Output Undervoltage Output Overvoltage Transformer Overtemp Local Alarm #1 Local Alarm #2

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013

1 2 3 4 5 6 7 8 9 10 11 12 13

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5

289:0 289:1 289:2 289:3 289:4 289:5

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05

Setpoints (View) None Control Points (Set) None

Page 60 of 158

Notes:

Divide by 10 for correct value

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Trendable Points (Set) Voltage Out X-Y Voltage Out Y-Z Voltage Out Z-X Voltage Out X-N Voltage Out Y-N Voltage Out Z-N Current Out A Current Out B Current Out C Ground Current Neutral Current kVA Reports Trend Status

Page 61 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Power Unit – Power Monitoring Panel (Ext. Protocol) – PM2 Hardware Compatibility Liebert Units: Datawave, Precision Power Center SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability Status Points (View) Voltage In X-Y Voltage In Y-Z Voltage In Z-X Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C Ground Current Neutral Current KVA KW Frequency % Capacity A % Capacity B % Capacity C Power Factor Kilowatt Hours THD Voltage X THD Voltage Y THD Voltage Z THD Current X THD Current Y

Modbus Register

BACnet Instance

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

Page 62 of 158

Notes:

Divide by 10 for correct value

Divide by 10 for correct value

Divide by 100 for correct value

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability Status Points (View) THD Current Z K Factor Current X K Factor Current Y K Factor Current Z CREST Factor Current X CREST Factor Current Y CREST Factor Current Z Alarm Points Communications Output Undervoltage Output Overvoltage Output Overcurrent Frequency Deviation Ground Overcurrent Transformer Overtemperature Ground Fault Ground Failure Liquid Detected Security Alarm Phase Rotation/Loss Datawave Overtemperature Emergency Shutdown Load On Bypass Local Alarm #1 Local Alarm #2 Output Voltage THD Custom Alarm #1 Custom Alarm #2 Output Voltage THD Setpoints (View) None

Modbus Register

BACnet Instance

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3 40290:4 40290:5 40290:6 40290:7 40290:8 40290:9

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 290:4 290:5 290:6 290:7 290:8 290:9

Control Points (Set) None

Page 63 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability Trendable Points (Set) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage In A-N Voltage In B-N Voltage In C-N Current Out A Current Out B Current Out C % Capacity A % Capacity B % Capacity C Ground Current Neutral Current KW KVA Power Factor THD Voltage X THD Voltage Y THD Voltage Z THD Current X THD Current Y THD Current Z K Factor Current X K Factor Current Y K Factor Current Z CREST Factor Current X CREST Factor Current Y CREST Factor Current Z Reports Trend Status

Modbus Register

BACnet Instance

Notes:

Power Unit – Power Monitoring Panel (Ext. Protocol) – PM2 Hardware Compatibility Liebert Units: Datawave, Precision Power Center SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All)

Page 64 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development Available Points SiteScan Availability

Status Points (View) Voltage In X-Y Voltage In Y-Z Voltage In Z-X Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A

Current Out B Current Out C Ground Current Neutral Current KVA KW Frequency % Capacity A % Capacity B % Capacity C Power Factor Kilowatt Hours THD Voltage X THD Voltage Y THD Voltage Z THD Current X THD Current Y

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_X BS18_x BS19_x BS20_x BS21_x

Page 65 of 158

Notes:

Divide by 10 for correct value

Divide by 10 for correct value

Divide by 100 for correct value

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Notes:

Status Points (View) THD Current Z K Factor Current X K Factor Current Y K Factor Current Z CREST Factor Current X CREST Factor Current Y CREST Factor Current Z Alarm Points Communications Output Undervoltage Output Overvoltage Output Overcurrent Frequency Deviation Ground Overcurrent Transformer Overtemp Ground Fault Ground Failure Liquid Detected Security Alarm Phase Rotation/Loss Datawave Overtemperature Emergency Shutdown Load On Bypass Local Alarm #1 Local Alarm #2 Output Voltage THD Custom Alarm #1 Custom Alarm #2

Discrete BACnet alarm objects available –use auto-discover for this unit 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08

Setpoints (View) None Control Points (Set) None

Page 66 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Trendable Points (Set) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage In A-N Voltage In B-N Voltage In C-N Current Out A Current Out B Current Out C % Capacity A % Capacity B % Capacity C Ground Current Neutral Current KW KVA Power Factor THD Voltage X THD Voltage Y THD Voltage Z THD Current X THD Current Y THD Current Z K Factor Current X K Factor Current Y K Factor Current Z CREST Factor Current X CREST Factor Current Y CREST Factor Current Z Reports Trend Status

Page 67 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Power Unit – Static Transfer Switch PDU – EDS Hardware Compatibility Liebert Units: Static Transfer Switch SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Transfer Count Preferred Source Load On Source 1or 2 Source 1 Voltage A-B Source 1 Voltage B-C Source 1 Voltage C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 1 Frequency Source 2 Voltage A-B Source 2 Voltage B-C Source 2 Voltage C-A Source 2 Current A Source 2 Current B Source 2 Current C Source 2 Frequency KW KVA Auto Transfer Timer Nominal Voltage Deviation Phase Differential Limit Frequency Deviation Auto Transfer Enabled

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 40024

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x BS21_x BS22_x BS23_x BS24_x

Page 68 of 158

Notes:

1=Source 1 / 0=Source 2 1=Source 1 / 2=Source 2

Divide by 10 for correct value

Divide by 10 for correct value

Divide by 10 for correct value 1=Enabled / 0=Disabled

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Communications Logic Failure Equipment Overtemp Power Supply 1 Fault Source 1 Overvoltage Source 1 Undervoltage Source 2 Overvoltage Source 2 Undervoltage Source 1 Overload Shorted SCR1 Shorted SCR2 Open SCR1 Open SCR2 Fan Failure Source 2 Overload Power Supply 2 Fault Frequency Deviation Transfer Inhibit Auto Retransfer Primed Out of Synchronization Source 1 Failure Source 2 Failure Auto Retransfer Failed Overload Control Fuse 1 Blown Control Fuse 2 Blown Source 1 CB1 Open Source 2 CB2 Open Output CB3 Open Custom Alarm 1 Custom Alarm 2 Bypass CB4 Closed Bypass CB5 Closed Custom Alarm 3 Custom Alarm 4

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 291:08 291:09 291:10 292:00 292:01

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01

Page 69 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Custom Alarm 5 Custom Alarm 6 Custom Alarm 7 Custom Alarm 8

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40292:2 40292:3 40292:4 40292:5

292:2 292:3 292:4 292:5

BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05

Setpoints (View) None Control Points (Set) None Trendable Points (Set) Source 1 Voltage A-B Source 1 Voltage B-C Source 1 Voltage C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 2 Voltage A-B Source 2 Voltage B-C Source 2 Voltage C-A Source 2 Current A Source 2 Current B Source 2 Current C KW KVA Reports Trend Status

Page 70 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Power Unit – Static Transfer Switch PDU Dual Output – STS Hardware Compatibility Liebert Units: Static Transfer Switch with w/ & w/o PDU SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Transfer Count Preferred Source Load On Source 1 or 2 Source 1 Voltage A-B Source 1 Voltage B-C Source 1 Voltage C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 1 Frequency Source 2 Voltage A-B Source 2 Voltage B-C Source 2 Voltage C-A Source 2 Current A Source 2 Current B Source 2 Current C Source 2 Frequency KW KVA Auto Transfer Timer Nominal Voltage Deviation Phase Differential Limit Frequency Deviation Auto Transfer Enabled Dual Output Breaker Status

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 40024

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x BS21_x BS22_x BS23_x BS24_x

Page 71 of 158

Notes:

1=Source 1 / 0=Source 2 1=Source 1 / 2=Source 2

Divide by 10 for correct value

Divide by 10 for correct value

Divide by 10 for correct value 1=Enabled / 0=Disabled 1=Enabled / 0=Disabled

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Communications Logic Failure Equipment Overtemp Power Supply 1 Fault Source 1 Overvoltage Source 1 Undervoltage Source 2 Overvoltage Source 2 Undervoltage Source 1 Overload Shorted SCR1 Shorted SCR2 Open SCR1 Open SCR2 Fan Failure Source 2 Overload Power Supply 2 Fault Frequency Deviation Transfer Inhibit Auto Retransfer Primed Out of Synchronization Source 1 Failure Source 2 Failure Auto Retransfer Failed Overload Control Fuse 1 Blown Control Fuse 2 Blown Source 1 CB1 Open Source 2 CB2 Open Output CB3 Open Custom Alarm 1 Custom Alarm 2 Bypass CB4 Closed Bypass CB5 Closed Output CB 3B Open Custom Alarm 4 Custom Alarm 5 Custom Alarm 6

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01 40292:02 40292:03

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 291:08 291:09 291:10 292:00 292:01 292:02 292:03

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 BA01_x:02 BA01_x:03

Page 72 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Custom Alarm 7 Custom Alarm 8

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40292:4 40292:5

292:4 292:5

BA01_x:04 BA01_x:05

Setpoints (View) Auto Transfer Timer Nominal Voltage Deviation Phase Differential Limit Frequency Deviation Auto Transfer Enabled Control Points (Set) None Trendable Points (Set) Source 1 Voltage A-B Source 1 Voltage B-C Source 1 Voltage C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 2 Voltage A-B Source 2 Voltage B-C Source 2 Voltage C-A Source 2 Current A Source 2 Current B Source 2 Current C KW KVA Reports Trend Status

Page 73 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Power Unit – Static Transfer Switch PDU Dual Output – STS-2 Hardware Compatibility Liebert Units: Static Transfer Switch Extended Protocol w/ & w/o PDU SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Total Transfer Count Preferred Source Active Source Source 1 Volts A-B Source 1 Volts B-C Source 1 Volts C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 1 Frequency Source 2 Volts A-B Source 2 Volts B-C Source 2 Volts C-A Source 2 Current A Source 2 Current B Source 2 Current C Source 2 Frequency Output KW Output KVA Sync Phase Angle Total Operating Hours CB1 Status CB2 Status CB3 Status CB3A Status CB4 Status CB5 Status CB7 Status CB8 Status SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x

40024:0 40024:1 40024:2 40024:3 40024:4 40024:5 40024:6 40024:7

24:0 24:1 24:2 24:3 24:4 24:5 24:6 24:7

BS24_x:00 BS24_x:01 BS24_x:02 BS24_x:03 BS24_x:04 BS24_x:05 BS24_x:06 BS24_x:07

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Page 74 of 158

Notes:

0=Source 1, 255=Source 2 1=Source 1, 2=Source 2

Divide by 10 for correct value

Divide by 10 for correct value

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development Setpoints (View) Retransefer Delay STS2 Voltage Rating Max Xfer Phase Angle Freq. Deviation Trip Point

40020 40021 40022 40023

BS20_x BS21_x BS22_x BS23_x

20 21 22 23

Discrete BACnet alarm objects available – use autodiscover for this unit

Alarm Points Communications Lost S1 SCR Short S2 SCR Short S1 SCR Open S2 SCR Open Primary Fan Fail Control Module Fail PWR Supply DC A Fail PWR Supply DC B Fail PWR Supply SRC 1 AC Fail PWR Supply SRC 2 AC Fail PWR Supply Logic Fail Output Voltage Sense Fail S1 Voltage Sense Fail S2 Voltage Sense Fail S1 SCR Sense Fail S2 SCR Sense Fail S1 Current Sense Fail S2 Current Sense Fail S1 Gate Drive Fail S2 Gate Drive Fail Internal Comm Fail External Comm Fail CB1 Shunt Trip Fail CB2 Shunt Trip Fail CB6 Neutral Open Contactor Neutral Fail Heatsink Overtemp Equipment Overtemp Ambient Overtemp S1 Undervolts S1 Undervolts (RMS) S1 Overvolts S1 Over/Under Freq S1 Fail S2 Undervolts S2 Undervolts (RMS) S2 Overvolts

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40290:11 40290:12 40290:13 40290:14 40290:15 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05

289:00 289:01 289:02 289:03 289:041 289:052 289:063 289:074 289:085 289:096 289:107 289:11 289:12 289:13 289:14 289:15 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 290:11 290:12 290:13 290:14 290:15 291:00 291:01 291:02 291:03 291:04 291:05

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA02_x:11 BA02_x:12 BA02_x:13 BA02_x:14 BA02_x:15 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05

Page 75 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points (Cont’d) S2 Over/Under Frequency S2 Fail S1 Overcurrent S2 Overcurrent S1 I-Peak S2 I-Peak Sources Out of Sync Load On Alternate Source Auto Retransfer Inhibit CB1 (S1) Open CB2 (S2) Open CB4 (S1 BYP) Closed CB5 (S2 BYP) Closed CB3 Output Bkr Open CB3A Output Bkr Open S1 Phase Rotation Error S2 Phase Rotation Error Transfer Inhibited Output Undervoltage History Logs Full Input Contact #1 Input Contact #2 Input Contact #3 Input Contact #4 Input Contact #5 Input Contact #6 Input Contact #7 Input Contact #8

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40291:06 40291:07 40291:08 40291:09 40291:10 40291:11 40291:12 40291:13 40291:14 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 40292:06 40292:07 40292:08 40292:09 40292:10 40292:11 40292:12 40292:13 40292:14 40293:00 40293:01 40293:02 40293:03

291:06 291:07 291:08 291:09 291:10 291:11 291:12 291:13 291:14 292:00 292:01 292:02 292:03 292:04 292:05 292:06 292:07 292:08 292:09 292:10 292:11 292:12 292:13 292:14 293:00 293:01 293:02 293:03

BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA03_x:11 BA03_x:12 BA03_x:13 BA03_x:14 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 BA04_x:06 BA04_x:07 BA04_x:08 BA04_x:09 BA04_x:10 BA04_x:11 BA04_x:12 BA04_x:13 BA04_x:14 BA05_x:00 BA05_x:01 BA05_x:02 BA05_x:03

Trendable Points (Set) S1 Amps A S1 Amps B S1 Amps C S2 Amps A S2 Amps B S2 Amps C kVA kW

Page 76 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Liebert UPS Units

Page 77 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – Multi Module UPS – S600 Extended Prot. – MM4 Hardware Compatibility Liebert Units: Series 600MMS SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability Status Points (View) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C DC Bus Voltage Battery Current KVA KW Critical Bus Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C Input Amps Phase A Input Amps Phase B Input Amps Phase C Total Operating Hours Module Number Total # Battery Discharge Accumulated Battery Time

Modbus Register

BACnet Instance

40001 40002 40003 40004 40005 40006

1 2 3 4 5 6

40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020

7 8 9 10 11 12 13 14 15 16 17 18 19 20

Page 78 of 158

Notes:

Divide by 10 fro correct value

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability Status Points (View) Accumulated Battery Amp/Hr Accumulated Battery kw/Hr Battery Charge Percent Battery Time Remaining Battery Temperature Alarm Points Communications Battery Discharge Input Failure Hardware Shutdown DC Ground Fault Input CB Open Output CB Open DC Cap Fuse Blown Low Battery Reserve Output Overload Rectifier Fuse Blown Emergency Power Off Ambient Overtemperature Battery Disconnected Control Power Failure Overload Shutdown Inverter Fault Input Current Unbalanced Inverter Out of Sync Reverse Power Low Battery Shutdown DC Overvoltage Shutdown Battery Cycle Buffer Full Equipment Overtemperature Blower/Fan Failure Overtemperature Shutdown Battery Room Overtemp Battery Test Running

Modbus Register

BACnet Instance

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3 40290:4 40290:5 40290:6 40290:7 40290:8 40290:9 40290:10 40291:0 40291:1 40291:2 40291:3 40291:4 40291:5

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 290:4 290:5 290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2 291:3 291:4 291:5

Page 79 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability Setpoints (View) Overload Alarm DC Overvoltage Alarm Battery Discharging Alarm Low Battery Alarm Battery Shutdown 1 Alarm Battery Shutdown 2 Alarm

Modbus Register

Control Points (Set) None Trendable Pionts (Set) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C DC Bus Voltage KVA KW % Capacity Phase A % Capacity Phase B % Capacity Phase C Input Amps Phase A Input Amps Phase B Input Amps Phase C Reports Trend Status

Page 80 of 158

BACnet Instance

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – Multi Module UPS – S600/610 Extended Prot. – MM4 Hardware Compatibility Liebert Units: Series 600/610 MMS SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability

Status Points (View) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A

Output Amps Phase B Output Amps Phase C

DC Bus Voltage Battery Current KVA KW Critical Bus Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C Input Amps Phase A Input Amps Phase B Input Amps Phase C Total Operating Hours Module Number Total # Battery Discharge Accumulated Battery Time

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006

1 2 3 4 5 6

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x

40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020

7 8 9 10 11 12 13 14 15 16 17 18 19 20

BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x

Page 81 of 158

Notes:

Divide by 10 for correct value

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05

Status Points (View) Accumulated Battery Amp/Hr Accumulated Battery kw/Hr Battery Charge Percent Battery Time Remaining Battery Temperature Alarm Points Communications Battery Discharge Input Failure Hardware Shutdown DC Ground Fault Input CB Open Output CB Open DC Cap Fuse Blown Low Battery Reserve Output Overload Rectifier Fuse Blown Emergency Power Off Ambient Overtemperature Battery Disconnected Control Power Failure Overload Shutdown Inverter Fault Input Current Unbalanced Inverter Out of Sync Reverse Power Low Battery Shutdown DC Overvoltage Shutdown Battery Cycle Buffer Full Equipment Overtemp Blower/Fan Failure Overtemperature Shutdown Battery Room Overtemp Battery Test Running

Page 82 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Setpoints (View) Overload Alarm DC Overvoltage Alarm Battery Discharging Alarm Low Battery Alarm Battery Shutdown 1 Alarm Battery Shutdown 2 Alarm Control Points (Set) None Trendable Points (Set) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A

Output Amps Phase B Output Amps Phase C

DC Bus Voltage KVA KW % Capacity Phase A % Capacity Phase B % Capacity Phase C Input Amps Phase A Input Amps Phase B Input Amps Phase C Reports Trend Status

Page 83 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – Multi Module Series – MMS Hardware Compatibility Liebert Units: Series 600600/610MMS, Series 600T MS SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink

Available Points SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Status Points (View) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C DC Bus Voltage Battery Current KVA KW Frequency % Capacity A % Capacity B % Capacity C Alarm Points

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x

Communications Battery Discharge Low Battery Reserve Output Overload Fuse Cleared Ambient Overtemperature

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05

Notes:

Divide by 10 for correct value

Discrete BACnet alarm objects available – use auto-discover for this unit 289:00 289:01 289:02 289:03 289:04 289:05

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05

Page 84 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Battery Grounded Battery Disconnected Module Cooling Failure Control Power Failure Overload Shutdown

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40289:06 40289:07 40289:08 40289:09 40289:10

289:06 289:07 289:08 289:09 289:10

BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10

Setpoints (View) None Control Points (Set) None Trendable Points (Set) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C % Capacity A % Capacity B % Capacity C DC Bus Voltage DC Bus Current kW kVA Reports Trend

Page 85 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – System Control Cabinet – S600 Ext. Prot. – SC4 Hardware Compatibility Liebert Units: Series 600 SCC SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability Status Points (View) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C KVA KW Critical Bus Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Output Frequency Bypass Frequency Total Operating Hours Number of Modules in System System Number

Modbus Register

BACnet Instance

40001 40002 40003 40004 40005 40006

1 2 3 4 5 6

40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020

7 8 9 10 11 12 13 14 15 16 17 18 19 20

Page 86 of 158

Notes:

Divide by 10 for correct value

Divide by 10 for correct value Divide by 10 for correct value

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability Alarm Points Communications Output Undervoltage Output Overvoltage Frequency Deviation Bypass CB Open Output CB Open Static Switch Disconnected Output Overload Emergency Power Off Load On Bypass Static Switch Disabled Control Power Failure Module #1 Summary Alarm Module #2 Summary Alarm Module #3 Summary Alarm Module #4 Summary Alarm Module #5 Summary Alarm Module #6 Summary Alarm Bypass Not Available Not OK to Transfer Bypass Phase Rotation Error Manual Reset/Transfer Auto Re-Transfer Primed Overload Transfer Module #1 Offline Module #2 Offline Module #3 Offline Module #4 Offline Module #5 Offline Module #6 Offline Custom Alarm #1 Custom Alarm #2 Custom Alarm #3 Custom Alarm #4 Custom Alarm #5

Modbus Register

BACnet Instance

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3 40290:4 40290:5 40290:6 40290:7 40290:8 40290:9 40290:10 40291:0 40291:1 40291:2 40291:3 40291:4 40291:5 40291:6 40291:7 40291:8 40291:9 40291:10 40292:0 40292:1

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 290:4 290:5 290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2 291:3 291:4 291:5 291:6 291:7 291:8 291:9 291:10 292:0 292:1

Page 87 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability Alarm Points Custom Alarm #6 Custom Alarm #7 Custom Alarm #8

Modbus Register

BACnet Instance

40292:2 40292:3 40292:4

292:2 292:3 292:4

Setpoints (View) Overload Alarm Control Points (Set) None Trendable Points (Set) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C kVA kW % Capacity Phase A % Capacity Phase B % Capacity Phase C Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Reports Trend Status

Page 88 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – System Control Cabinet – S600600/610 Ext. Prot. – SC4 Hardware Compatibility Liebert Units: Series 600600/610 SCC SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability

Status Points (View) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C KVA KW Critical Bus Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Output Frequency Bypass Frequency Total Operating Hours Number of Modules in System System Number

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006

1 2 3 4 5 6

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x

40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020

7 8 9 10 11 12 13 14 15 16 17 18 19 20

BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x

Page 89 of 158

Notes:

Divide by 10 for correct value

Divide by 10 for correct value Divide by 10 for correct value

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Communications Output Undervoltage Output Overvoltage Frequency Deviation Bypass CB ClosedOpen Output CB Open Static Switch Disconnected Output Overload Emergency Power Off Load On Bypass Static Switch Disabled Control Power Failure Module #1 Summary Alarm Module #2 Summary Alarm Module #3 Summary Alarm Module #4 Summary Alarm Module #5 Summary Alarm Module #6 Summary Alarm Bypass Not Available Not OK to Transfer Bypass Ph Rotation Error Manual Reset/Transfer Auto Re-Transfer Primed Overload Transfer Module #1 Offline Module #2 Offline Module #3 Offline Module #4 Offline Module #5 Offline Module #6 Offline Custom Alarm #1 Custom Alarm #2 Custom Alarm #3 Custom Alarm #4 Custom Alarm #5

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 291:08 291:09 291:10 292:00 292:01

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01

Page 90 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Custom Alarm #6 Custom Alarm #7 Custom Alarm #8

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40292:02 40292:03 40292:04

292:02 292:03 292:04

BA04_x:02 BA04_x:03 BA04_x:04

Setpoints (View) Overload Alarm Control Points (Set) None Trendable Points (Set) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C kVA KW % Capacity Phase A % Capacity Phase B % Capacity Phase C Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Reports Trend Status

Page 91 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – System Control Cabinet – SCC Hardware Compatibility Liebert Units: Series 600600/610 SCC SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage In A-N Voltage In B-N Voltage In C-N Current Out A Current Out B Current Out C KVA KW Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x

Divide by 10 for correct value

Discrete BACnet alarm objects available – use auto-discover for this unit

Alarm Points Communications Output Overload Emergency Power Off Load On Bypass Static Switch Disabled Output Out of Limits Module #1 Summary

Notes:

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06

289:00 289:01 289:02 289:03 289:04 289:05 289:06

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06

Page 92 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Module #2 Summary Module #3 Summary Module #4 Summary Module #5 Summary Module #6 Summary

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40289:07 40289:08 40289:09 40289:10 40290:00

289:07 289:08 289:09 289:10 290:00

BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00

Setpoints (View) None Control Points (Set) None Trendable Points (Set) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage In A-N Voltage In B-N Voltage In C-N Current Out A Current Out B Current Out C % Capacity Phase A % Capacity Phase B % Capacity Phase C KW KVA Reports Trend Status

Page 93 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – Single Module Series – SMS Hardware Compatibility Liebert Units: Series 300/500/600 Single Module UPS SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C DC Bus Voltage DC Bus Current KVA KW Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C Alarm Points Communications Battery Discharge Low Battery Reserve Output Overload Fuse Cleared Emergency Power Off Ambient Overtemperature Load On Bypass Static Switch Disabled Battery Disconnected Module Cooling Failure

Modbus Register

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020

BACnet Instance (Exec. 6 Modules) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10

BACnet Notes: Instance (Exec. B Modules) BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x Divide by 10 for correct value Modbus Only BS16_x Divide by 10 for correct value Modbus Only BS17_x Divide by 10 for correct value Modbus Only BS18_x BS19_x BS20_x

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10

Page 94 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Control Power Failure Overload Shutdown Setpoints (View) None Control Points (Set) None Trendable Points (Set) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C % Capacity Phase A % Capacity Phase B % Capacity Phase C DC Bus Voltage DC Bus Current KW KVA Reports Trend Status

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40290:00 40290:01

290:00 290:01

BA02_x:00 BA02_x:01

Page 95 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – Single Module UPS – S600600/610 Ext. Prot. – SM4 Hardware Compatibility Liebert Units: Series 600600/610 SMS SiteScan Interface Modules: DC1,DC4, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C DC Bus Voltage Battery Current KVA KW Critical Bus Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Input Amps Phase A Input Amps Phase B Input Amps Phase C Bypass Frequency

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006

1 2 3 4 5 6

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x

40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 40024

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x BS21_x BS22_x BS23_x BS24_x

Page 96 of 158

Notes:

Divide by 10 for correct value

Divide by 10 for correct value

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Status Points (View) Bypass Frequency Total Operating Hours Module Number Total # Battery Discharge Accumulated Battery Time Accumulated Battery Amp/Hr Accumulated Battery kW/Hr Battery Charge Percent Battery Time Remaining Battery Temperature Alarm Points Communications Output Undervoltage Output Overvoltage Battery Discharge Frequency Deviation Input Failure Hardware Shutdown DC Ground Fault Input CB Open Bypass CB OpenClosed Output CB Open Static Switch Disconnected DC Cap Fuse Blown Low Battery Reserve Output Overload Rectifier Fuse Blown Emergency Power Off Ambient Overtemperature Load On Bypass Static Switch Disabled Battery Disconnected Control Power Failure Inverter Fault Input Current Unbalanced

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:01 BA03_x:02

Page 97 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Bypass Not Available Not OK to Transfer Bypass Ph Rotation Error Manual Reset/Transfer Auto Re-Transfer Primed Overload Transfer Reserve Power Low Battery Shutdown DC Overvoltage Shutdown Battery Cycle Buffer Full Equipment Overtemp Blower/Fan Failure Overtemperature Shutdown Custom Alarm #1 Custom Alarm #2 Custom Alarm #3 Custom Alarm #4 Custom Alarm #5 Custom Alarm #6 Custom Alarm #7 Custom Alarm #8 Battery Room Overtemp Battery Test Running Auto-restart Initiated Auto-restart Failed Setpoints (View) Overload Alarm DC Overvoltage Alarm Battery Discharging Alarm Low Battery Alarm Battery Shutdown 1 Alarm Battery Shutdown 2 Alarm Control Points (Set) None

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 40292:06 40292:07 40292:08 40292:09 40292:10 40292:00 40293:01 40293:02 40293:03 40293:04

291:02 291:03 291:04 291:05 291:06 291:07 291:08 291:09 291:10 292:00 292:01 292:02 292:03 292:04 292:05 292:06 292:07 292:08 292:09 292:10 292:00 293:01 293:02 293:03 293:04

BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 BA04_x:06 BA04_x:07 BA04_x:08 BA04_x:09 BA04_x:10 BA05_x:00 BA05_x:01 BA05_x:02 BA05_x:03 BA05_x:04

Page 98 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Trendable Points (Set) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C DC Bus Voltage Battery Current KVA KW % Capacity Phase A % Capacity Phase B % Capacity Phase C Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Input Amps Phase A Input Amps Phase B Input Amps Phase C Reports Trend Status

Page 99 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – Multi-Module SICE 7200 & HiPulse UPS – SMM Hardware Compatibility Liebert Units: SICE 7200 SiteScan Interface Modules: DC1, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Voltage L1-N Output Voltage L2-N Output Voltage L3-N Output Amps L1 Output Amps L2 Output Amps L3 Output Amps Neutral Power L1 Power L2 Power L3 Bypass Frequency Inverter Frequency Input Voltage L1-L2 Input Voltage L2-L3 Input Voltage L3-L1 Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 Module Number

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003

1 2 3

BS01_x BS02_x BS03_x

40004 40005 40006

4 5 6

BS04_x BS05_x BS06_x

40007 40008 40009 40010 40011

7 8 9 10 11

BS07_x BS08_x BS09_x BS10_x BS11_x

40012 40013 40014 40015 40016 40017 40018 40019

12 13 14 15 16 17 18 19

BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x

Page 100 of 158

Notes:

Divide by 10 for correct value Divide by 10 for correct value

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Status Points (View) % Battery Charge Battery Temperature Battery Time Remaining Alarm Points Communications Bypass Switch Open Output Switch Open Rectifier Switch Open Battery CB Open Manual Bypass Closed Bypass Absent Bypass Overvoltage Bypass Undervoltage Bypass Frequency Error Byp Phase Rotation Error Bypass SCR Failure Bypass Off Bypass Off Via Display Load On Bypass Bypass Overtemperature Rectifier Off Rectifier Off Via Display Rectifier Block Rectifier Current Limit Rectifier Overtemperature Rectifier Fuse Failure Inverter Off Inverter Off Via Display Inverter Block Inverter Current Limit Inverter Overtemperature Inverter Non Sync Inverter Overvoltage Inverter Undervoltage

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40020 40021 40022

20 21 22

BS20_x BS21_x BS22_x

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07

Page 101 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Inverter Fuse Failure Output Overvoltage Output Undervoltage Output No Voltage Output Waveform Error Inverter Frequency Error Inverter Parallel Error Contactor Failure Battery Test Battery Test Failed Battery On Load Battery End of Discharge Boost Time Expired DC Slow Overvoltage DC Undervoltage Battery Fuse Failure DC Fast Overvoltage Transfer Count Block Overload Shutdown Overtemperature SD Emergency Stop Overload Present Overload Shutdown TO Bad EEPROM Error LRC Par P1 Error LRC Par P2 Error LRC Par P3 Error LRC Alarm History Error LRC Event History Internal Battery Low Error LRC Table Error LRC Panel Can Bus No Response Battery Ground Fault BackFeedBack Feed Fault

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40291:08 40291:09 40291:10 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 40292:06 40292:07 40292:08 40292:09 40292:10 40293:00 40293:01 40293:02 40293:03 40293:04 40293:05 40293:06 40293:07 40293:08 40293:09 40293:10

291:08 291:09 291:10 292:00 292:01 292:02 292:03 292:04 292:05 292:06 292:07 292:08 292:09 292:10 293:00 293:01 293:02 293:03 293:04 293:05 293:06 293:07 293:08 293:09 293:10

BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 BA04_x:06 BA04_x:07 BA04_x:08 BA04_x:09 BA04_x:10 BA05_x:00 BA05_x:01 BA05_x:02 BA05_x:03 BA05_x:04 BA05_x:05 BA05_x:06 BA05_x:07 BA05_x:08 BA05_x:09 BA05_x:10

Page 102 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Alarm Points Synchronization Inhibited ECO – Mode On

Setpoints (View) Power Rating Configuration Nominal Voltage Low Level Input Voltage Upper Level Input Voltage Low Level Output Voltage Upper Level Output Voltage Nominal Frequency Frequency Tolerance Slew Rate # of Battery Cells Rated Capacity Pre-End Discharge End of Discharge per Cell Maximum Voltage per Cell Year Month Day Hour Minute Second Control Points (Set) Date & Time Sync

Trendable Points (Set) Output Voltage L1-L2 Output Voltage L2-L3 Output voltage L3-L1

Page 103 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Trendable Points (Set) Output Amps L1 Output Amps L2 Output Amps L3 Power L1 Power L2 Power L3 Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 Reports Status Trend

Page 104 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – Systems Cabinet SICE 7200 UPS – SSC Hardware Compatibility Liebert Units: SICE 7200 SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Voltage L1-N Output Voltage L2-N Output Voltage L3-N Output Amps L1 Output Amps L2 Output Amps L3 Output Amps Neutral Power L1 Power L2 Power L3 Bypass Frequency Input Voltage L1-L2 Input Voltage L2-L3 Input Voltage L3-L1 Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 Number of Modules in Sys %Battery Charge Battery Temperature Battery Time Remaining

Modbus Register

40001 40002 40003

BACnet Instance (Exec. 6 Modules) 1 2 3

BACnet Instance (Exec. B Modules) BS01_x BS02_x BS03_x

40004 40005 40006

4 5 6

BS04_x BS05_x BS06_x

40007 40008 40009 40010

7 8 9 10

BS07_x BS08_x BS09_x BS10_x

40012 40013 40014 40015 40016 40017 40018 40019

12 13 14 15 16 17 18 19

BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x

40020 40021 40022

20 21 22

BS20_x BS21_x BS22_x

Page 105 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

Communications Bypass Switch Open Output Switch Open Battery CB Open Manual Bypass Closed Bypass Absent Bypass Overvoltage Bypass Undervoltage Bypass Frequency Error Bypass Ph Rotation Error Bypass SCR Failure Bypass Off Bypass Off Via Display Load On Bypass Bypass Overtemperature Inverter Non Sync Output Overvoltage Output Undervoltage Output No Voltage Output Waveform Error Transfer Count Block Overload Shutdown Overtemperature Shutdown Emergency Stop Overload Present Overload Shutdown TO Bad EEPROM Error LRC Par P1 Error LRC Par P2 Error LRC Par P3 Error LRC Alarm History Error LRC Event History Internal Battery Low Error LRC Table Error LRC Panel Can Bus No Response

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:05 40291:05 40291:05 40291:05 40291:05 40291:05 40291:05 40291:05

BACnet Instance (Exec. 6 Modules) 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:05 291:05 291:05 291:05 291:05 291:05 291:05 291:05

BACnet Instance (Exec. B Modules) BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05

Page 106 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Setpoints ( View) Power Rating Configuration Nominal Voltage Low Level Input Voltage Upper Level Input Voltage Low Level Output Voltage Upper Level Output Voltage Nominal Frequency Frequency Tolerance Year Month Day Hour Minute Second Trendable Points (Set) Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Amps L1 Output Amps L2 Output Amps L3 Power L1 Power L2 Power L3 Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 Reports Status Trend

Page 107 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – Single Module SICE 7200 & HiPulse UPS – SSM Hardware Compatibility Liebert Units: SICE 7200 SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Voltage L1-N Output Voltage L2-N Output Voltage L3-N Output Amps L1 Output Amps L2 Output Amps L3 Output Amps Neutral Power L1 Power L2 Power L3 Bypass Frequency Inverter Frequency Input Voltage L1-L2 Input Voltage L2-L3 Input Voltage L3-L1 Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 %Battery Charge

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003

1 2 3

BS01_x BS02_x BS03_x

40004 40005 40006

4 5 6

BS04_x BS05_x BS06_x

40007 40008 40009 40010 40011

7 8 9 10 11

BS07_x BS08_x BS09_x BS10_x BS11_x

40012 40013 40014 40015 40016 40017 40018 40019 40020

12 13 14 15 16 17 18 19 20

BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x

Page 108 of 158

Notes:

Divide by 10 for correct value Divide by 10 for correct value

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Status Points (View) Battery Temperature Battery Time Remaining

40021 40022

21 22

BS21_x BS22_x

Alarm Points Communications Bypass Switch Open Output Switch Open Rectifier Switch Open Battery CB Open Manual Bypass Closed Bypass Absent Bypass Overvoltage Bypass Undervoltage Bypass Frequency Error Bypass Ph Rotation Error Bypass SCR Failure Bypass Off Bypass Off Via Display Load On Bypass Bypass Overtemperature Rectifier Off Rectifier Off Via Display Rectifier Block Rectifier Current Limit Rectifier Overtemperature Rectifier Fuse Failure Inverter Off Inverter Off Via Display Inverter Block Inverter Current Limit Inverter Overtemperature Inverter Non Sync Inverter Overvoltage Inverter Undervoltage Inverter Fuse Failure

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 291:08

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08

Page 109 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Alarm Points Output Overvoltage Output Undervoltage Output No Voltage Output Waveform Error Inverter Frequency Error Inverter Parallel Error Contactor Failure Battery Test Battery Test Failed Battery On Load Battery End of Discharge Boost Time Expired DC Slow Overvoltage DC Undervoltage Battery Fuse Failure DC Fast Overvoltage Transfer Count Block Overload Shutdown Overtemperature Shutdown Emergency Stop Overload Present Overload Shutdown TO Bad EEPROM Error LRC Par P1 Error LRC Par P2 Error LRC Par P3 Error LRC Alarm History Error LRC Event History Internal Battery Low Error LRC Table Error LRC Panel Can Bus No Response

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40291:09 40291:10 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 40292:06 40292:07 40292:08 40292:09 40292:10 40293:00 40293:01 40293:02 40293:03 40293:04 40293:05 40293:06 40293:07 40293:08 40293:09 40293:10 40293:10 40293:10 40293:10 40293:10 40293:10 40293:10 40293:10 40293:10

291:09 291:10 292:00 292:01 292:02 292:03 292:04 292:05 292:06 292:07 292:08 292:09 292:10 293:00 293:01 293:02 293:03 293:04 293:05 293:06 293:07 293:08 293:09 293:10 293:10 293:10 293:10 293:10 293:10 293:10 293:10 293:10

BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 BA04_x:06 BA04_x:07 BA04_x:08 BA04_x:09 BA04_x:10 BA05_x:00 BA05_x:01 BA05_x:02 BA05_x:03 BA05_x:04 BA05_x:05 BA05_x:06 BA05_x:07 BA05_x:08 BA05_x:09 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10

Page 110 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Alarm Points Setpoints (View) Power Rating Configuration Nominal Voltage Low Level Input Voltage Upper Level Input Voltage Low Level Output Voltage Upper Level Output Voltage Nominal Frequency Frequency Tolerance Slew Rate # of Battery Cells Rated Capacity Pre-End Discharge End of Discharge per Cell Maximum Voltage per Cell Year Month Day Hour Minute Second Control Points (Set) Date & Time Sync Trendable Points (Set) Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Amps L1 Output Amps L2 Output Amps L3 Power L1 Power L2 Power L3 Battery Voltage

Page 111 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Trendable Points (Set) Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 Reports Status Trend

Page 112 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – UPStation S – DCU Hardware Compatibility Liebert Units: UPStation S SiteScan Interface Modules: DCU BMS interface Modules:

Available Points SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Status Points (View) Battery Time Remaining Last Battery Test Passed Last Self Test Passed Voltage In Phase A Voltage In Phase B Voltage In Phase C Current In Phase A Current In Phase B Current In Phase C Voltage Out Phase A Voltage Out Phase B Current Out Phase A Current Out Phase B Voltage Bypass Phase A Voltage Bypass Phase B Current Bypass Phase A Current Bypass Phase B VA Inverter Load Percentage Load Inverter Temperature PFC Temperature Battery Temperature Battery Voltage Battery Current Input Frequency Output Frequency

Page 113 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Status Points (View) Bypass Frequency Alarm Points Communications Inverter Utility Failure Ambient Overtemperature Battery Test In Progress Input Overvoltage UPS On Bypass Receptacle 1 Off Receptacle 2 Off Receptacle 3 Off Receptacle 4 Off Receptacle 5 Off Receptacle 6 Off Receptacle 7 Off Receptacle 8 Off Outlet Overload Input Frequency Charger Failure Low Battery Inverter Undervoltage Inverter Overvoltage Bypass Power UPS Status Setpoints (View) None Control Points (Set) None

Page 114 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Trendable Points (Set) Voltage In Phase A Voltage In Phase B Voltage In Phase C Current In Phase A Current In Phase B Current In Phase C Voltage Out Phase A Voltage Out Phase B Current Out Phase A Current Out Phase B Voltage Bypass Phase A Voltage Bypass Phase B Current Bypass Phase A Current Bypass Phase B VA Inverter Load Percentage Load Inverter Temperature PFC Temperature Battery Temperature Battery Voltage Battery Current Input Frequency Output Frequency Bypass Frequency Reports Trend Status

Page 115 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – UPStation S3 – US3 Hardware Compatibility Liebert Units: UPStation S3 SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Bypass Voltage A-N Bypass Voltage B-N Bypass Voltage C-N Voltage In A-N Voltage In B-N Voltage In C-N Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C DC Bus Voltage DC Bus Current KVA KW Inverter Temperature PFC Temperature Battery Temperature Battery Test Status Input Frequency Bypass Frequency Output Frequency Current In A Current In B Current In C % Capacity

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40016 40017 40018 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40021 40022 40023

16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 21 22 23

BS16_x BS17_x BS18_x BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS21_x BS22_x BS23_x

40024 40014

24 14

BS24_x BS14_x

40015

15

BS15_x

Page 116 of 158

Notes:

Divide by 10 for correct value Modbus Only

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Status Points (View) Inverter Status Utility Status Bypass Status Battery Test in Progress Battery Time Remaining KVA Size Alarm Points Communications Bypass Failure Input Failure Battery Discharging Low Battery Reserve Output Overload Ambient Overtemperature Output Undervoltage Output Overvoltage Input Overvoltage Charge Failure UPS Off Load On Bypass Utility Failed

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40020 40019

20 19

BS20_x BS19_x

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02

Setpoints (View) None Control Points (Set) None Trendable Points (Set) Bypass Voltage A-N Bypass Voltage B-N Bypass Voltage C-N Voltage In A-N Voltage In B-N

Page 117 of 158

Notes:

Countdown starts at 254

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Trendable Points (Set) Voltage In C-N Voltage Out A-N Voltage Out B-N Voltage Out C-N Current In A Current In B Current In C Current Out A Current Out B Current Out C % Capacity DC Bus Voltage DC Bus Current KW KVA Battery Time

Reports Trend Status

Page 118 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – Single Module Series AP301/302 – SM3 Hardware Compatibility Liebert Units: Single Module UPS AP301/302 SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Bypass Voltage A-N Bypass Voltage B-N Bypass Voltage C-N Voltage in A-N Voltage in B-N Voltage in C-N Voltage Out A-N Voltage Out B-N Voltage Out C-N Current In A Current In B Current In C Current Out A Current Out B Current Out C % Capacity DC Bus Voltage DC Bus Current KW KVA Input Frequency Bypass Frequency Output Frequency Last Battery Test Status Inverter Status Model Number KVA Size

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40016 40017 40018 40001 40002 40003 40004 40005 40006

16 17 18 1 2 3 4 5 6

BS16_x BS17_x BS18_x BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x

40007 40008 40009 40015 40010 40011 40012 40013

7 8 9 15 10 11 12 13

BS07_x BS08_x BS09_x BS15_x BS10_x BS11_x BS12_x BS13_x

40014 40022 40023 40020 40019

14 22 23 20 19

Page 119 of 158

BS14_x BS22_x BS23_x BS20_x BS19_x

Notes:

Divide by 10 for correct value Divide by 10 for correct value Divide by 10 for correct value Modbus Only 0=failed / 1= passed 0=off / 1=on

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Notes:

Status Points (View) Utility Status Bypass Status Battery Test In Progress Battery Time Remaining

40024

24

BS24_x

0=not present / 1=present

40021

21

BS21_x

Countdown timer starts at 254

Alarm Points Communications Bypass Failure Input Failure Battery Discharging Low Battery Reserve Output Overload Ambient Overtemperature Output Undervoltage Output Overvoltage Charger Failure Load On Bypass Utility Failed

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00

Setpoints (View) None Control Points (Set) None Trendable Points (Set) Bypass Voltage A-N Bypass Voltage B-N Bypass Voltage C-N Voltage In A-N Voltage In B-N Voltage In C-N Voltage Out A-N Voltage Out B-N Voltage Out C-N Current In A Current In B Current In C Current Out A Current Out B

Page 120 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Current Out C % Capacity DC Bus Voltage DC Bus Current KW KVA Input Frequency Bypass Frequency Output Frequency Battery Time Reports Trend Status

Page 121 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – Single Module UPS – NPower—IMP Hardware Compatibility Liebert Units: NPower SMS SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Input Voltage A-B Input Voltage B-C Input Voltage C-A Input Frequency Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Bypass Frequency Battery Voltage Battery Current Battery Temperature Battery Time Remaining Battery Charge Percentage Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Current A Output Current B Output Current C Output kVA A Output kVA B Output kVA C Output kW A Output kW B

BACnet Modbus Instance Register (2.6)BACne t Instance

BACnet SSWEB

40001 40002 40003

1 2 3

BS01_x BS02_x BS03_x

40004 40005 40006

4 5 6

BS04_x BS05_x BS06_x

40007 40008 40009

7 8 9

BS07_x BS08_x BS09_x

40010 40011 40012

10 11 12

BS10_x BS11_x BS12_x

40013 40014 40015 40016 40017 40018 40019 40020

13 14 15 16 17 18 19 20

BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x

Page 122 of 158

Notes:

Scale by 10

Scale by 10 Scale by 10 Scale by 10

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability Status Points (View) Output kW C Output Frequency Rated kVA Percentage Rated kW Percentage SBS Line Contact On/Off SBS Load Contact On/Off Input Delta Contact On/Off Input Wye Contact On/Off Output Contact On/Off Battery Breaker On/Off Trap Filter Contact On/Off Int. Mbypass Sw. On/Off Ext. Mbypass Sw. On/Off Year Alarm Points Communications Battery Fuse Fail Rectifier Fuse Fail Trap Fuse Fail Battery Overcharged Bypass Overload Shutdown Inverter Overload Inverter Fuse Failure Overvoltage Transfer Undervoltage Transfer Inverter Curr.Lim. Transfer EPO Shutdown Rectifier Fail Inverter Fail Hardware Shutdown On Battery Input Current Limit Battery CB Open Battery Discharging

BACnet Modbus Instance Register (2.6)BACne t Instance

BACnet SSWEB

40021 40022 40023 40024

21 22 23 24

BS21_x BS22_x BS23_x BS24_x

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02

289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 289:11 289:12 289:13 289:14 289:15 290:00 290:01 290:02

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02

Page 123 of 158

Notes:

Scale by 10

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability Alarms Points SBS Overload Phase A SBS Overload Phase B SBS Overload Phase C Inverter Current Limit Inverter Overload Phase A Inverter Overload Phase B Inverter Overload Phase C

BACnet Instance Modbus Register (2.6)BACne t Instance

BACnet SSWEB

Notes:

40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09

290:03 290:04 290:05 290:06 290:07 290:08 290:09

BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09

Low PF Warning Battery Ground Fault EPO Latched SBS Unable Inverter Off By User Battery Low Warning Battery Test Fail User Shutdown Battery Not Charged Load On Bypass Input Contact #1 Input Contact #2 Input Contact #3 Input Contact #4 Input Contact #5 Input Contact #6 Input Contact #7 Input Contact #8 Common Alarm Inverter Overload Phase A

40290:10 40290:11 40290:12 40290:13 40290:14 40290:15 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40291:11 40291:12

290:10 290:11 290:12 290:13 290:14 290:15 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 291:08 291:09 291:10 291:11 291:12

BA02_x:10 BA02_x:11 BA02_x:12 BA02_x:13 BA02_x:14 BA02_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA02_x:11 BA02_x:12 Common alarm includes

Inverter Overload Phase B Inverter Overload Phase C Excessive Auto reTransfers Aux. Overtemp Warning Battery Overtemp Warning

40291:03 40291:03 40291:04 40291:05 40291:05

40291:03

Page 124 of 158

All other alarms not listed Supported as “Output Overload” Supported as “Output Overload” Supported as “Output Overload” Supported as “OverTemp Warning” Supported as “OverTemp Warning” Supported as “OverTemp Warning”

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability Alarms Points Heatsink Overtemp Warning Inlet Air Overtemp Warning Outlet Air Overtemp Wrning Powerpole Fan 1 Failure Powerpole Fan 2 Failure Powerpole Fan 3 Failure Primary Fan 1 Failure Primary Fan 2 Failure Primary Fan 3 Failure System Fan Failure SBS Unable Inverter Off by User Low Battery Warning Battery Test Failed User Shutdown Load on Bypass Input Contact #1 Input Contact #2 Input Contact #3 Input Contact #4 Input Contact #5 Input Contact #6 Input Contact #7 Input Contact #8

Modbus Register 40291:05 40291:05 40291:05 40291:06 40291:06 40291:06 40291:06 40291:06 40291:06 40291:06 40291:07 40291:08 40291:09 40291:10 40291:11 40291:12 40291:13 40291:13 40291:13 40291:13 40291:13 40291:13 40291:13 40291:13

Setpoints (view) Module Number # System Modules

Page 125 of 158

BACnet Instance

Notes: Supported as “OverTemp Warning” Supported as “OverTemp Warning” Supported as “OverTemp Warning” Supported as “Fan Failure” Supported as “Fan Failure” Supported as “Fan Failure” Supported as “Fan Failure” Supported as “Fan Failure” Supported as “Fan Failure” Supported as “Fan Failure”

Supported as “Customer Alarm” Supported as “Customer Alarm” Supported as “Customer Alarm” Supported as “Customer Alarm” Supported as “Customer Alarm” Supported as “Customer Alarm” Supported as “Customer Alarm” Supported as “Customer Alarm” Supported as “Customer Alarm” Supported as “Customer Alarm” Supported as “Customer Alarm”

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Trendable Points Battery Current Output Current A Output Current B Output Current C Ouptut kVA A Ouptut kVA B Ouptut kVA C Ouptut kW A Ouptut kW B Ouptut kW C % Rated kVA % Rated kW Reports Trend & Status

Page 126 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – Single Module UPS – NX—PNX Hardware Compatibility Liebert Units: NX SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Input Frequency Output Frequency Bypass Frequency Battery Voltage Battery Current Battery Charge Percentage Battery Time Remaining Battery Temperature Input Voltage Vab Input Voltage Vbc Input Voltage Vca Bypass Volts A Bypass Volts B Bypass Volts C Output Volts A Output Volts B Output Volts C Output Current A Output Current B Output Current C Output % A Output % B Output % C Output Va A Output Va B Output Va C Output Watts A

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Notes:

40001

BS01_x

Scale By 10

40002 40003

BS02_x BS03_x

Scale by 10

40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016

BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x

40017

BS17_x

40018 40019 40020 40021

BS18_x BS19_x BS20_x BS21_x

Page 127 of 158

Scale by 10

Scale by 10 Scale by 10 Scale by 10 Average of A,B,C

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Available Points SiteScan Availability

Status Points (View) Output Watts B Output Watts C System Output Va A System Output Va B System Output Va C Alarm Points Loss Of Communications Input Switch Open Generator Input Disconnected Main AC Neutral Lost Load On Battery Reserved Load On Joint Mode Load On Bypass No Power Supplied

Overload Bypass Max Xfer Bypass False Operation UPS Overload Battery Shutdown Imminent Inverter Not Sync DC Under Voltage Shutdown Inverter FaultOutput Var A Inverter DC Offset Overrun Inverter Contactor Fail Inverter Over Current Inverter Communication Fail Rectifier Input Fuse Blown Rectifier Startup Fail Rectifier Fault Rectifier Over Current Rectifier Communication Fail Control Power Fail Fan Fail Battery Overtemperature Ambient Overtemperature Rectifier Overtemperature Rectifier Inductor Overtemp

Modbus Register

BACnet BACnet Instance Instance (Exec. B (Exec. 6 Modules) Modules)

40022 40023

BS22_x BS23_x

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40290:11 40290:12 40290:13 40290:14 40290:15

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA02_x:11 BA02_x:12 BA02_x:13 BA02_x:14 BA02_x:15

Page 128 of 158

Notes:

Scale by 10 Scale by 10 Scale by 10

Average of A,B,C

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Available Points SiteScan Availability

Modbus Register

BACnet BACnet Instance (Exec. Instance (Exec. 6 Modules) B Modules)

Alarm Points Inverter Overtemperature Inverter Inductor Overtemp Battery Converter Overtemp Battery Balancer Overtemp Input Power Failure Input Brown Out Input Frequency Deviation Input Phase Rotation Bypass SBS Unable Bypass Input Fault Output Over Voltage Charger Failure Battery Fault Battery Contactor Fail Battery Converter Fail Battery Converter Overcurrent Battery Balancer Fault Battery Balancer Over Current Parallel System Low Batt Warn Parallel Load Share Fault Parallel System Fault Parallel Connection Error Parallel System Over Load Parallel Transfer To Bypass Parallel Communication Fail

40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40291:11 40291:12 40291:13 40291:14 40291:15 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 40292:06 40292:07 40292:08

Control Points (Set) None Trend Points Output Current Phase A Output Current Phase B Output Current Phase C Output % (Avg 3 Phases)

Page 129 of 158

BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA03_x:11 BA03_x:12 BA03_x:13 BA03_x:14 BA03_x:15 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 BA04_x:06 BA04_x:07 BA04_x:08

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Alarm Points

Parallel Transfer To Bypass Parallel Communication Fail

40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40291:11 40291:12 40291:13 40291:14 40291:15 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 40292:06 40292:07 40292:08

BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA03_x:11 BA03_x:12 BA03_x:13 BA03_x:14 BA03_x:15 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 BA04_x:06 BA04_x:07 BA04_x:08

Setpoints (View) Nominal VA

40024

BS24

Battery Converter Over Temp Battery Balancer Over Temp Input Power Failure Alarm Input Brown Out Alarm Input Frequency Deviation Alarm Input Phase Rotation Alarm Bypass SBS Unable Bypass Input Fault Output Over Voltage Alarm Charger Failure Battery Fault Battery Contactor Fail Battery Converter Fail Battery Converter Over Current Battery Balancer Fault Battery Balancer Over Current Parallel System Low Batt Warn Parallel Load Share Fault Parallel System Fault Parallel Connection Error Parallel System Over Load

Trends Battery Current Current Phase A Current Phase B Current Phase C Avg. Output %

Page 130 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – HiNet – PHN Hardware Compatibility Liebert Units: HiNet SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) UPS Load VA UPS Load Watt Input Frequency Output Frequency Load On Inverter UPS Load On Bypass UPS DC-DC Status Battery Voltage Battery Current Battery Charge Percentage Ambient Temperature Input Va Input Vb Input Vc Input Current Ia Input Current Ib Input Current Ic Output Va Output Vb Output Vc Output Current Ia Output Current Ib Output Current Ic

Modbus Register

BACnet Instance (Exec. 6 Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023

BACnet Instance (Exec. B Modules) BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x BS21_x BS22_x BS23_x

Page 131 of 158

Notes:

Scale By 10 Scale By 10

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Available Points SiteScan Availability

Alarm Points Loss Of Communications Load On Battery Reserved Load On Bypass – Permanent UPS Overload Battery Shutdown imminent Inverter Not Sync Input Power Failure Bypass SBS SCR Open fault Bypass Input Fault

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09

40024

BS24_x

Setpoints (View) Device Type UPS Sub Module Number UPS Battery Count UPS Outlet Circuitry Supported UPS Type Is Offline UPS Type Is Interactive UPS Has Dual Inputs

Setpoints (Set) None Trend Points Load VA Load Watts Input Current A Input Current B Input Current C Output Current A Output Current B Output Current C

Page 132 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – NFinity – PNF Hardware Compatibility Liebert Units: Nfinity SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) UPS Load VA UPS Load Watt UPS Load Percent Input Frequency Output Frequency Bypass Frequency UPS Load On Bypass Power Factor Correction Stat Battery Voltage Battery Charge Percentage Battery Time Remaining Battery Temperature Transformer Temperature Input Voltage Input Current Bypass Voltage Bypass Current Output Voltage Output Current Battery Discharge Count Battery Discharge Time Setpoints (View) Maximum System Capacity Auto Restart Delay Auto Battery Test Enable

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x BS21_x

40022 40023 40024

BS22_x BS23_x BS24_x

Page 133 of 158

Notes:

Scale By 10 Scale By 10 Scale By 10

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Available Points SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Setpoints (Set) None Alarm Points Loss Of Communications Load On Battery Load On Bypass Overload Bypass Fault Bypass Manual Bypass Manual Xfer Prohibited UPS Overload Shutdown Pending Battery Shutdown imminent Fan Fail Air Filter Bad Transformer Overtemperature Internal Comm Failure New Event Logged Input Power Failure Red Power Module Low Device Active Alarm Main Control Module Alarm Redundant Module Alarm Power Module Alarm Battery Module Alarm Main Control Module Fail Red. Control Module Fail User Interface Module Fail Power Module Failure Battery Module Failure Overtemp Shutdown Overload Shutdown Output Short Shutdown Low Battery Shutdown Remote Shutdown EPO Shutdown

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40290:11 40290:12 40290:13 40290:14 40290:15 40291:00

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA02_x:11 BA02_x:12 BA02_x:13 BA02_x:14 BA02_x:15 BA03_x:00

Page 134 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Available Points SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Trend Points vA Watts Input Current Bypass Current Output Current

Page 135 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – GXT – PGX Hardware Compatibility Liebert Units: GXT SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) UPS Load VA UPS Load Watt UPS Load Percent Input Frequency Output Frequency Bypass Frequency Load On Inverter UPS Load On Bypass Battery Test Result DC-DC Status Inverter Ready Status Power Factor Correction Stat Battery Charge Comp Status Replace Battery Status Battery Test In Progress Battery Charge Status Battery Voltage Battery Charge Percentage Battery Deplete Time Ambient Temperature Input Voltage Vab Input Voltage Van Bypass Voltage Vab Bypass Voltage Van Output Voltage Vab Output Voltage Van Output Current Ia Output Load % Phase A

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x

40007 40008 40009

BS07_x BS08_x BS09_x

40010 40011 40012 40013 40014 40015 40016 40017

BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x

Page 136 of 158

Notes:

Scale By 10 Scale By 10 Scale By 10

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Available Points SiteScan Availability

Status Points (View) Output VA Phase A Output Var Phase A Output Watt Phase A Input Voltage Vbn Bypass Voltage Vbn Output Voltage Vbn Output Current Ib Output Load % Phase B Output VA Phase B Output Watt Phase B UPS Black Out Count UPS Brown Out Count PhaseA Maximum Input Va PhaseA Minimum Input Va PhaseA Maximum Output Va PhaseA Minimum Output Va Load Circuit Output State Setpoints (View) Device Type UPS Sub Module Number

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40018 40019 40020

BS18_x BS19_x BS20_x

40021 40022 40023

BS21_x BS22_x BS23_x

40024

BS24_x

Outlet Circuitry Supported Nominal VA Nominal Input Voltage Nominal Output Voltage Nominal Bypass Voltage Nominal Input Current Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal Battery Voltage Auto Restart Delay Battery Low Alarm time Auto Restart Enable Audible Alarm Enable Auto Battery Test Enable

Page 137 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Available Points SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Setpoints (View) UPS Type Is Offline UPS Type Is Interactive UPS Has Dual Inputs Setpoints (View) None Control Points (Set) Delayed Output Off Delayed Output Off/Reboot Delayed Output On Battery Test Command Alarm Silence Abort Command Alarm Points Loss Of Comm Load On Battery Reserved UPS Overload UPS Shutdown Pending Battery Shutdown IminentImminent Overtemperature Input Current Unbalance Input Power Failure Input Over Voltage Input Under Voltage Input Frequency Deviation Bypass Input Fault Output Undervoltage Output Overvoltage Shutdown – Overtemp Shutdown – Overload Shutdown – DC Bus OV Shutdown - Output Short Shutdown - L-N Swapped

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02 40290:03

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03

Page 138 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Available Points SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Alarm Points Shutdown Shutdown Shutdown Shutdown Shutdown

- Low Battery - By Remote - UV Startup - PFC Startup - External Signal

40290:04 40290:05 40290:06 40290:07 40290:08

BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08

Trend Points Load VA Load Watts OuputOutput Current A Output VA A Output VAR A Output Watts A Output Current B Output VA B Output Watts B

Page 139 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

UPS Unit – PSI – PPS Hardware Compatibility Liebert Units: PSI SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) UPS Load VA UPS Load Watt UPS Load Percent Input Frequency Output Frequency Load On Inverter Battery Test Result UPS Booster On Status UPS Buck On Status UPS DC-DC Status UPS Battery Charger State Replace Battery Battery Test In Progress UPS Battery Charge Status Battery Voltage Battery Charge Percentage Battery Time Remaining Ambient Temperature Input Va Input Current Ia Output Va Output Current Ia UPS Black Out Count UPS Brown Out Count PhaseA Maximum Input Va PhaseA Minimum Input Va PhaseA Maximum Output Va PhaseA Minimum Output Va Load Circuit Output State

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x

40007

BS07_x

40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023

BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x BS21_x BS22_x BS23_x

Page 140 of 158

Notes:

Scale By 10 Scale By 10

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Available Points SiteScan Availability

Set Points (View) Device Type Sub Module Number Outlet Circuitry Supported Nominal VA Nominal Input Voltage Nominal Output Voltage Nominal Input Current Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal Battery Voltage Battery Last Min Rated Load Battery Float Voltage Auto Restart Delay Ambient Overtemp Alarm Overtemp Failure Threshold Auto Restart Enable Audible Alarm Enable Auto Battery Test Enable UPS Type Is Offline UPS Type Is Interactive UPS Has Dual Inputs

Modbus Register

BACnet Instance (Exec. 6 Modules)

40024

BACnet Instance (Exec. B Modules)

BS24_x

Setpoints (Set) None Control Points (Set) Turn Output Off with Delay Delayed OuputOutput Off/Reboot Delayed Output On Battery Test Command Alarm Silent command Abort previous Command Reset Battery Stats Cmd Reset Stat Counters Cmd

Page 141 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Available Points SiteScan Availability

Alarm Points Loss Of Comm Load On Battery Reserved UPS Overload UPS Shutdown Pending Battery Shutdown Iminent Overtemperature Input Current Unbalance Input Power Failure Input Over Voltage Input Under Voltage Input Frequency Deviation Bypass Input Fault Output Undervoltage Output Overvoltage Shutdown – Overtemp Shutdown – Overload Shutdown – DC Bus OV Shutdown - Output Short Shutdown - L-N Swapped Shutdown - Low Battery Shutdown - By Remote Shutdown - UV Startup Shutdown - PFC Startup Shutdown - External Signal

Modbus Register

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules) BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08

Trend Points Load VA Load Watts OuputOutput Current A Output VA A Output VAR A Output Watts A Output Current B Output VA B Output Watts B

Page 142 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Liebert Monitoring Modules

Page 143 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Contact Closure Module – CCM Hardware Compatibility Liebert Units: CCM200, RCM8, VSM100 SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Contact 1 Contact 2 Contact 3 Contact 4 Contact 5 Contact 6 Contact 7 Contact 8 Contact 9 Contact 10 Contact 11 Contact 12 Contact 13 Contact 14 Contact 15 Contact 16 Contact 17 Contact 18 Contact 19 Contact 20 Contact 21 Contact 22 Contact 23 Contact 24 Contact 25 Contact 26 Contact 27

Page 144 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Notes:

Status Points (View) Contact 28 Contact 29 Contact 30 Contact 31 Contact 32 Discrete BACnet alarm objects available – use auto-discover for this unit

Alarm Points (See Note) Communications

40001:0

1:0

BS01_x:00

Contact 1 Contact 2 Contact 3 Contact 4 Contact 5 Contact 6 Contact 7 Contact 8 Contact 9 Contact 10 Contact 11 Contact 12 Contact 13 Contact 14 Contact 15 Contact 16 Contact 17 Contact 18 Contact 19 Contact 20 Contact 21 Contact 22 Contact 23 Contact 24 Contact 25 Contact 26 Contact 27

40001:1 40001:2 40001:3 40001:4 40001:5 40001:6 40001:7 40001:8 40001:9 40001:10 40002:0 40002:1 40002:2 40002:3 40002:4 40002:5 40002:6 40002:7 40002:8 40002:9 40002:10 40003:0 40003:1 40003:2 40003:3 40003:4 40003:5

1:1 1:2 1:3 1:4 1:5 1:6 1:7 1:8 1:9 1:10 2:0 2:1 2:2 2:3 2:4 2:5 2:6 2:7 2:8 2:9 2:10 3:0 3:1 3:2 3:3 3:4 3:5

BS01_x:01 BS01_x:02 BS01_x:03 BS01_x:04 BS01_x:05 BS01_x:06 BS01_x:07 BS01_x:08 BS01_x:09 BS01_x:10 BS02_x:00 BS02_x:01 BS02_x:02 BS02_x:03 BS02_x:04 BS02_x:05 BS02_x:06 BS02_x:07 BS02_x:08 BS02_x:09 BS02_x:10 BS03_x:00 BS03_x:01 BS03_x:02 BS03_x:03 BS03_x:04 BS03_x:05

Page 145 of 158

Note: The first three status registers are used to report Alarm Points.

Revision B.27 11/14/2007 Liebert Monitoring Group - Development SiteScan Availability

Contact 28 Contact 29 Contact 30 Contact 31 Contact 32

Modbus Register

40003:6 40003:7 40003:8 40003:9 40003:10

BACnet Instance (Exec. 6 Modules) 3:6 3:7 3:8 3:9 3:10

BACnet Instance (Exec. B Modules) BS03_x:06 BS03_x:07 BS03_x:08 BS03_x:09 BS03_x:10

Setpoints (View) None Control Points (Set) None Trendable Points (Set) None Reports Status

Page 146 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Water/Liquid Detection Unit – WDU Hardware Compatibility Liebert Units: LDS1000, LDS750 SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability Status Points (View) Distance Feet or Meters Alarm Points Communications Cable Fault Liquid Detected

Modbus Register

BACnet Instance

40001 40002

1 2

40289:0 40289:1 40289:2

289:0 289:1 289:2

Setpoints (View) None Control Points (Set) None Trendable Points (Set) None Reports Status

Page 147 of 158

Notes:

1=feet / 0=meters

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Remote Autochangeover – RAC Hardware Compatibility Liebert Units: RAC2-8 SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Unit 6 Unit 7 Unit 8 Alarm Points Communications Common Alarm 1 Common Alarm 2 Common Alarm 3 Common Alarm 4 Common Alarm 5 Common Alarm 6 Common Alarm 7 Common Alarm 8 Emergency Power Operation EPO All Units High Temperature Low Temperature High Humidity Low Humidity Manual Override

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Notes:

40001 40002 40003 40004 40005 40006 40007 40008

1 2 3 4 5 6 7 8

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x

1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff

40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3 40290:4

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 290:4

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04

Page 148 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Setpoints (View) None Control Points (Set) None Trendable Points (Set) None Reports Status

Page 149 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Temperature/Humidity Module – THM Hardware Compatibility Liebert Units: THM100 SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Temperature Sensor 1 Humidity Sensor 1 Temperature Sensor 2 Humidity Sensor 2 Temperature Sensor 3 Humidity Sensor 3 Temperature Sensor 4 Humidity Sensor 4 Temperature Sensor 5 Humidity Sensor 5 Temperature Sensor 6 Humidity Sensor 6 Temperature Sensor 7 Humidity Sensor 7 Temperature Sensor 8 Humidity Sensor 8 Alarm Points Communications High/Low Temp Sensor 1 High/Low Humidity Sensor 1 High/Low Temp Sensor 2 High/Low Humidity Sensor 2 High/Low Temp Sensor 3 High/Low Humidity Sensor 3 High/Low Temp Sensor 4 High/Low Humidity Sensor 4

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x

40289:0

289:0

BA01_x:00

Notes:

Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others

Page 150 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

High/Low Temp Sensor 5 High/Low Humidity Sensor 5 High/Low Temp Sensor 6 High/Low Humidity Sensor 6 High/Low Temp Sensor 7 High/Low Humidity Sensor 7 High/Low Temp Sensor 8 High/Low Humidity Sensor 8 Setpoints (View) High/Low Temp Sensor 1 High/Low Humidity Sensor 1 High/Low Temp Sensor 2 High/Low Humidity Sensor 2 High/Low Temp Sensor 3 High/Low Humidity Sensor 3 High/Low Temp Sensor 4 High/Low Humidity Sensor 4 High/Low Temp Sensor 5 High/Low Humidity Sensor 5 High/Low Temp Sensor 6 High/Low Humidity Sensor 6 High/Low Temp Sensor 7 High/Low Humidity Sensor 7 High/Low Temp Sensor 8 High/Low Humidity Sensor 8 Control Points (Set) High/Low Temp Sensor 1 High/Low Humidity Sensor 1 High/Low Temp Sensor 2 High/Low Humidity Sensor 2 High/Low Temp Sensor 3 High/Low Humidity Sensor 3 High/Low Temp Sensor 4 High/Low Humidity Sensor 4 High/Low Temp Sensor 5

Page 151 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

Trend Points Temp Sensor 1 Humidity Sensor 1 Temp Sensor 2 Humidity Sensor 2 Temp Sensor 3 Humidity Sensor 4 Temp Sensor 4 Humidity Sensor 4 Temp Sensor 5 Humidity Sensor 5 Temp Sensor 6 Humidity Sensor 6 Temp Sensor 7 Humidity Sensor 7 Temp Sensor 8 Humidity Sensor 8

Page 152 of 158

BACnet Instance (Exec. B Modules)

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Water/Liquid Detection Unit LDS5000 – WD5 Hardware Compatibility Liebert Units: LDS5000 SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) Installed Cable Footage 1 Installed Cable Footage 2 Not Used - Spare Not Used - Spare Leak Det Footage Cable 1 Leak Det Footage Cable 2 Not Used - Spare Not Used - Spare Leakage Current Cable 1 Leakage Current Cable 2 Not Used - Spare Not Used - Spare Feet / Meters Alarm Points Communications Leak Detected Cable 1 Cable Fault Cable 1 Leak Detected Cable 2 Cable Fault Cable 2 Not Used - Spare Not Used - Spare Not Used - Spare Not Used - Spare Setpoints (View) None

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013

1 2 3 4 5 6 7 8 9 10 11 12 13

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08

289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08

Control Points (Set) Alarm Silence Alarm Reset Trendable Points (Set) None

Page 153 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Universal Monitor – UVM Hardware Compatibility Liebert Units: Universal Monitor – UVM SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All)

Available Points SiteScan Availability

Status Points (View) I/O Extender Card Status Input Contact #1 Status Input Contact #2 Status Input Contact #3 Status Input Contact #4 Status Input Contact #5 Status Input Contact #6 Status Input Contact #7 Status Input Contact #8 Status Input Contact #9 Status Input Contact #10 Status Input Contact #11 Status Input Contact #12 Status Input Contact #13 Status Input Contact #14 Status Input Contact #15 Status Input Contact #16 Status Input Contact #17 Status Input Contact #18 Status Input Contact #19 Status Input Contact #20 Status Input Contact #21 Status Input Contact #22 Status Input Contact #23 Status Input Contact #24 Status Output Contact #1 Status Output Contact #2 Status Output Contact #3 Status Output Contact #4 Status Output Contact #5 Status Output Contact #6 Status Output Contact #7 Status

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules) BS01_x

40001

Page 154 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Status Points (View) Output Contact #8 Status Output Contact #9 Status Output Contact #10 Status Output Contact #11 Status Output Contact #12 Status Output Contact #13 Status Output Contact #14 Status Output Contact #15 Status Output Contact #16 Status Sensor #1 High Status Sensor #1 Low Status Sensor #2 High Status Sensor #2 Low Status Sensor #3 High Status Sensor #3 Low Status Sensor #4 High Status Sensor #4 Low Status Sensor #1 Reading Sensor #2 Reading Sensor #3 Reading Sensor #4 Reading Alarm Points Input #1 Alarm Input #2 Alarm Input #3 Alarm Input #4 Alarm Input #5 Alarm Input #6 Alarm Input #7 Alarm Input #8 Alarm Input #9 Alarm Input #10 Alarm Input #11 Alarm Input #12 Alarm Input #13 Alarm Input #14 Alarm

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40002 40003 40004 40005

BS02_x BS03_x BS04_x BS05_x

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02

Page 155 of 158

Notes:

Revision B.27 11/14/2007 Liebert Monitoring Group - Development SiteScan Availability

Alarm Points Input #15 Alarm Input #16 Alarm Input #17 Alarm Input #18 Alarm Input #19 Alarm Input #20 Alarm Input #21 Alarm Input #22 Alarm Input #23 Alarm Input #24 Alarm Sensor #1 High Alarm Sensor #1 Low Alarm Sensor #2 High Alarm Sensor #2 Low Alarm Sensor #3 High Alarm Sensor #3 Low Alarm Sensor #4 High Alarm Sensor #4 Low Alarm Loss of Power Low Battery Alarm Battery Unplugged Check Battery Exp board loss of comm Configuration Changed Loss of Comm Setpoints (View) Sensor #1 High Threshold SP Sensor #1 Low Threshold SP Sensor #2 High Threshold SP Sensor #2 Low Threshold SP Sensor #3 High Threshold SP Sensor #3 Low Threshold SP Sensor #4 High Threshold SP Sensor #4 Low Threshold SP Control Points (Set) Sensor High Threshold Sensor Low Threshold Alarm Silence Alarm Reset Trendable Points (Set) Sensor Readings

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05

BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05

40006 40007 40008 40009 40010 40011 40012 40013

BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x

Notes:

Sensors 1-4 Sensors 1-4

Sensors 1-4

Page 156 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

Autochangeover Controller – AC8 Hardware Compatibility Liebert Units: Autochangeover Controller – AC8 SiteScan Interface Modules: SiteLink-4, SiteLink-12, SiteLink-E series BMS interface Modules: SiteLink-4, SiteLink-12, SiteLink-E series

Available Points SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Notes:

Status Points (View) Output #1 Status Output #2 Status Output #3 Status Output #4 Status Output #5 Status Output #6 Status Output #7 Status Output #8 Status Device #1 Status Device #2 Status Device #3 Status Device #4 Status Device #5 Status Device #6 Status Device #7 Status Device #8 Status Temp. Sensor #1 Reading Temp. Sensor #2 Reading Temp. Sensor #3 Reading Temp. Sensor #4 Reading

BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x

40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020

Control Points (Set) Enable Date & Time Sync Output #1 Output #2 Output #3 Output #4 Output #5 Output #6 Output #7 Output #8

0=Off, 1=On, 2=Forced Off, 3=Forced On, 4=Hardware On

30=Not Used, 31=Operating, 32=Standby, 33=Pending, 34=Forced On, 35=Forced Off, 36=Hardware On, 37=Alarm, 38=Event

Modbus Format – Signed Integer

Force On, Force Off, Return to Normal

Page 157 of 158

Revision B.27 11/14/2007 Liebert Monitoring Group - Development

SiteScan Availability

Modbus Register

BACnet Instance (Exec. 6 Modules)

BACnet Instance (Exec. B Modules)

Notes:

Alarm Points Loss Of Comm. Input #1 Alarm Input #2 Alarm Input #3 Alarm Input #4 Alarm Input #5 Alarm Input #6 Alarm Input #7 Alarm Input #8 Alarm Sensor #1 High Alarm Sensor #2 High Alarm Sensor #2 Low Alarm Sensor #3 High Alarm Sensor #3 Low Alarm Sensor #4 High Alarm Sensor #4 Low Alarm Loss of Power Low Battery Alarm Battery Unplugged Check Battery Emergency Power Op Configuration Changed Common Alarm

40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06

BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 Note: Discrete BACnet objects available BA01_x:11 using auto-discover BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06

Trendable points (Set) Sensor #1 Sensor #2 Sensor #3 Sensor #4

Page 158 of 158