SELF-CONTAINED HEAT PUMP PACKAGE UNITS FORM NO. P11-751 REV. 1 Supersedes Form No. P11-751

RQKA- STANDARD EFFICIENCY 10-SEER SERIES NOMINAL SIZES 1.5-4 TONS [5-14.1 kW]

RQMA- HIGH EFFICIENCY 12-SEER SERIES NOMINAL SIZES 1.5-3 TONS [5-10.6 kW]

RQMA- MODELS ONLY (PRIOR TO JAN. 1 2004)

TABLE OF CONTENTS

Unit Features & Benefits ................................................................................3-4 Model Identification Options............................................................................5-6 General Data RQKA- Series ............................................................................................7-9 RQMA- Series ........................................................................................10-11 General Data Notes ........................................................................................12 Performance Data RQKA- Series ........................................................................................13-15 RQMA- Series ........................................................................................16-17 Airflow Performance RQKA- Series ........................................................................................18-19 RQMA- Series ............................................................................................20 Electrical Data RQKA- Series ............................................................................................21 RQMA- Series ............................................................................................22 Electric Heater Kits ....................................................................................23-26 Dimensional Data ..........................................................................................27 Typical Installations ........................................................................................28 Accessories ..............................................................................................29-36 Typical Wiring ............................................................................................37-38 Limited Warranty ............................................................................................40

2

UNIT FEATURES & BENEFITS—RQKA/RQMA-

These quality features are included in the Rheem Outdoor Package Heat Pumps 5

4

3

UNIT FEATURES & BENEFITS—RQKA/RQMA- SERIES

Features Below Correspond to Photos on Page 3 1. All models feature Copeland® Scroll® compressors for maximum efficiency and quiet operation.

8. Refrigerant connections are conveniently located for easy service diagnostics.

2. Louvered condenser compartment for protecting the coil against yard hazards and/or weather extremes.

9. Condenser and evaporator coils feature enhanced fins for better heat transfer and rifled copper tubing for greater efficiency.

3. One-piece top with a deep flange to help keep water out of the unit.

10. Supplemental electric heat strips up to 15 kW are available (field or factory installed) for periods of extreme cold temperatures. Single point wiring makes installation even easier.

4. Supply and return air openings feature a one-inch tall flange to prevent water migration into the ductwork.

11. All units feature an internal trap on the condensate line eliminating the need for installing an on-site external trap.

5. Access panels have “weep holes” and channels to further help manage water run-off. 6. Side and down discharge options available on all models. (Shipped Downflow Standard).

12. Integral gasketing on the base rails is standard on those units shipped from the factory in the down-flow configuration.

7. Easily accessible blower section complete with slideout blower. All units feature a system matched MultiFlex® coil with low static pressure drop and excellent cooling capacities.

13. Easily accessible control box.

4

MODEL IDENTIFICATION—RQKA/RQMA- SERIES

R Q K A — A 036 J K 010 X X X Future Option Factory Installed Options (See Next Page) Heating Capacity (Factory Installed) 000 = No Resistance Heat 005 = 05 KW Resistance Heat (018-030) 006 = 06 KW Resistance Heat (036-048) 010 = 10 KW Resistance Heat (024-048) 011 = 10 KW Resistance Heat (Canada) (024-048) 015 = 15 KW Resistance Heat (036-048) 016 = 15 KW Resistance Heat (Canada) (036-048) Drive Package K = Direct Drive Electrical Designation J = 208-230V—1PH—60 Hz C = 208-230V—3PH—60 Hz Cooling Capacity (BTUH) [kW] 018 = 18,000 [5.28] 024 = 24,000 [7.03] 030 = 30,000 [8.79] 036 = 36,000 [10.55] 042 = 42,000 [12.31] 048 = 48,000 [14.07] 060 = 60,000 [17.59] Future Technical Variations Design Series A = 1st Design Efficiency Designation K = 10 SEER Standard Efficiency M = 12 SEER High Efficiency Product Classification Q = Package Heat Pump Tradebrand R = Rheem

[ ] Designates Metric Conversions

5

OPTIONS—RQKA/RQMA- SERIES Instructions for Factory Installed Option(s) Selection Note: Two characters following the model number will be utilized to designate a factory-installed option or combination of options. If no factory option(s) is required, nothing follows the model number. Step 1. After a basic rooftop model is selected, choose a two-character option code from the FACTORY INSTALLED OPTION SELECTION TABLE.

FACTORY INSTALLED OPTION CODES Option Code AA AKA

Side Flow No Option x

Example: RQKA-A036JK000XX (where XX is factory installed option) Example: No Options RQKA-A036JK000 Example: Options with Sideflow RQKA-A036JK000AKA Note: Factory installed economizer is not available on these models.

6

GENERAL DATA—RQKA- SERIES NOMINAL SIZES 1.5-4 TONS [5-14.1 kW] Model RQKA- Series Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2

A018JK

A024JK

A030JK

A036CK

18,600 [5.4] 10.15/10

24,000 [7] 9.5/10

31,200 [9.1] 9.1/10

CONTINUED 37,200 [10.9] 9.5/10

600/600 [283/283] 18,000 [5.3]

800/800 [378/378] 23,200 [6.8]

1000/1000 [472/472] 30,000 [8.8]

1200/1200 [566/566] 36,000 [10.5]

13,200 [3.9]

17,200 [5]

21,400 [6.3]

25,200 [7.4]

4800 [1.4]

6000 [1.8]

8600 [2.5]

10,800 [3.2]

1.8

2.4

3.3

3.8

18,000 [5.3] 1.7/3.18 9400 [2.8]

23,600 [6.9] 2.1/3.24 12,600 [3.7]

29,600 [8.7] 2.8/3.08 16,400 [4.8]

36,000 [10.5] 3.4/3.12 21,600 [6.3]

1.5/1.8

1.9/1.9

2.5/1.9

3.2/2

6.8

6.8

6.8

6.8

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 76

Louvered

Louvered

Louvered

Louvered

Smooth 0.375 [9.5] 12.75 [1.18] 1 / 18 [7]

Smooth 0.375 [9.5] 12.75 [1.18] 1 / 20 [8]

Smooth 0.375 [9.5] 12.75 [1.18] 1 / 18 [7]

Smooth 0.375 [9.5] 12.42 [1.15] 2 / 18 [7]

Refrigerant Control

TX Valves

TX Valves

TX Valves

TX Valves

Indoor Coil—Fin Type Tube Type Tube Size in. [mm]

Louvered Rifled 0.3125 [7.9]

Louvered Rifled 0.3125 [7.9]

Louvered Rifled 0.3125 [7.9]

Louvered Rifled 0.3125 [7.9]

7.6 [0.71]

7.6 [0.71]

10.13 [0.94]

10.13 [0.94]

1 / 18 [7] Orifices 1/0.75 [19.05] Propeller

1 / 18 [7] Orifices 1/0.75 [19.05] Propeller

1 / 18 [7] Orifices 1/0.75 [19.05] Propeller

1 / 18 [7] TX Valves 1/0.75 [19.05] Propeller

1/22 [559]

1/22 [559]

1/22 [559]

1/22 [559]

Direct/1

Direct/1

Direct/1

Direct/1

1800 [849] 1 at 1/15 HP

1800 [849] 1 at 1/15 HP

2730 [1288] 1 at 1/5 HP

2600 [1227] 1 at 1/5 HP

Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW Heating Performance (Heat Pumps) Heating Input Btu [kW] Rating System Power KW/COP Low Temp. Btuh [kW] Rating System Power KW/COP HSPF (Btu/Watts-hr) Compressor No./Type Outdoor Sound Rating (dB)3 Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm]

Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm] Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM Motor Frame Size Filter—Type Furnished

1075

1075

1075

1075

FC Centrifugal 1/9x7 [228.6x177.8] Direct/2

FC Centrifugal 1/9x7 [228.6x177.8] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/1

1

1

1

1

1/4

1/4

1/2

1/3

1075

1075

1075

1075

48 Field Supplied

48 Field Supplied

48 Field Supplied

48 Field Supplied

No

No

No

No

(1)1x20x16 [25x508x406]

(1)1x20x20 [25x508x508]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

65 [1843]

62 [1758]

70 [1984]

103 [2920]

Net Weight lbs. [kg]

360 [163]

362 [164]

389 [176]

405 [184]

Ship Weight lbs. [kg]

400 [181]

402 [182]

429 [195]

445 [202]

(No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g] Weights

[ ] Designates Metric Conversions

See Page 12 for Notes.

7

GENERAL DATA—RQKA- SERIES NOMINAL SIZES 1.5-4 TONS [5-14.1 kW] Model RQKA- Series Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2

A036JK

A042CK

A042JK

A048CK

37,200 [10.9] 9.5/10

42,000 [12.3] 9.1/10

48,500 [14.2] 9.1/10

CONTINUED 48,500 [14.2] 9/10

1200/1200 [566/566] 36,000 [10.5]

1400/1400 [661/661] 40,500 [11.9]

1400/1400 [661/661] 40,500 [11.9]

1600/1500 [755/708] 46,500 [13.6]

Net Sensible Capacity Btu [kW]

25,200 [7.4]

29,000 [8.5]

29,000 [8.5]

32,100 [9.4]

Net Latent Capacity Btu [kW]

10,800 [3.2]

11,500 [3.4]

11,500 [3.4]

14,400 [4.2]

3.8

4.5

4.5

5.2

36,000 [10.5] 3.4/3.12 21,600 [6.3]

41,000 [12] 3.9/3.1 22,600 [6.6]

41,000 [12] 3.9/3.1 22,600 [6.6]

48,000 [14.1] 4.6/3.08 28,000 [8.2]

3.2/2

3.4/1.96

3.4/1.96

4/2.06

6.8

6.8

6.8

6.8

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 78

Louvered

Louvered

Louvered

Louvered

Smooth 0.375 [9.5] 12.42 [1.15] 2 / 18 [7]

Smooth 0.375 [9.5] 12.42 [1.15] 2 / 18 [7]

Smooth 0.375 [9.5] 12.42 [1.15] 2 / 18 [7]

Smooth 0.375 [9.5] 12.42 [1.15] 2 / 18 [7]

Refrigerant Control

TX Valves

TX Valves

TX Valves

TX Valves

Indoor Coil—Fin Type Tube Type Tube Size in. [mm]

Louvered Rifled 0.3125 [7.9]

Louvered Rifled 0.3125 [7.9]

Louvered Rifled 0.3125 [7.9]

Louvered Rifled 0.3125 [7.9]

10.13 [0.94]

10.13 [0.94]

10.13 [0.94]

10.13 [0.94]

1 / 18 [7] TX Valves 1/0.75 [19.05] Propeller

1 / 18 [7] TX Valves 1/0.75 [19.05] Propeller

1 / 18 [7] TX Valves 1/0.75 [19.05] Propeller

1 / 18 [7] TX Valves 1/0.75 [19.05] Propeller

1/22 [559]

1/22 [559]

1/22 [559]

1/22 [559]

Direct/1

Direct/1

Direct/1

Direct/1

2600 [1227] 1 at 1/5 HP

2600 [1227] 1 at 1/5 HP

2600 [1227] 1 at 1/5 HP

3000 [1416] 1 at 1/3 HP

Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW]

Net System Power kW Heating Performance (Heat Pumps) Heating Input Btu [kW] Rating System Power KW/COP Low Temp. Btuh [kW] Rating System Power KW/COP HSPF (Btu/Watts-hr) Compressor No./Type Outdoor Sound Rating (dB)3 Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm]

Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm] Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM Motor Frame Size Filter—Type Furnished

1075

1075

1075

1075

FC Centrifugal 1/10x9 [254x228.6] Direct/1

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/3

1

1

1

1

1/3

1/2

1/2

3/4

1075

1075

1075

1075

48 Field Supplied

48 Field Supplied

48 Field Supplied

56 Field Supplied

No

No

No

No

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

103 [2920]

139 [3941]

139 [3941]

138 [3912]

Net Weight lbs. [kg]

409 [186]

416 [189]

420 [191]

441 [200]

Ship Weight lbs. [kg]

449 [204]

456 [207]

460 [209]

481 [218]

(No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g] Weights

[ ] Designates Metric Conversions

See Page 12 for Notes.

8

GENERAL DATA—RQKA- SERIES NOMINAL SIZES 1.5-4 TONS [5-14.1 kW] Model RQKA- Series Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW]

A048JK 48,500 [14.2] 9/10 1600/1500 [755/708] 46,500 [13.6]

Net Sensible Capacity Btu [kW]

32,100 [9.4]

Net Latent Capacity Btu [kW]

14,400 [4.2]

Net System Power kW Heating Performance (Heat Pumps) Heating Input Btu [kW] Rating System Power KW/COP Low Temp. Btuh [kW] Rating System Power KW/COP HSPF (Btu/Watts-hr)

5.2 48,000 [14.1] 4.6/3.08 28,000 [8.2] 4/2.06 6.8

Compressor No./Type Outdoor Sound Rating (dB)3 Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm]

1/Copeland Scroll 78 Louvered Smooth 0.375 [9.5] 12.42 [1.15] 2 / 18 [7]

Refrigerant Control

TX Valves

Indoor Coil—Fin Type Tube Type Tube Size in. [mm]

Louvered Rifled 0.3125 [7.9]

Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm] Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM Motor Frame Size Filter—Type Furnished (No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g]

10.13 [0.94] 1 / 18 [7] TX Valves 1/0.75 [19.05] Propeller 1/22 [559] Direct/1 3000 [1416] 1 at 1/3 HP 1075 FC Centrifugal 1/10x9 [254x228.6] Direct/1+B34 1 3/4 1075 48 Field Supplied No (1)1x24x24 [25x610x610] 138 [3912]

Weights Net Weight lbs. [kg]

450 [204]

Ship Weight lbs. [kg]

490 [222] [ ] Designates Metric Conversions

See Page 12 for Notes.

9

GENERAL DATA—RQMA- SERIES NOMINAL SIZES 1.5-3 TONS [5-10.6 kW] Model RQMA- Series Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2

A018JK

A024JK

A030JK

A036CK

19,600 [5.7] 10.5/12

25,000 [7.3] 10.6/12

30,200 [8.8] 10.2/12

CONTINUED 36,600 [10.7] 10.5/12

600/700 [283/330] 18,800 [5.5]

800/800 [378/378] 24,000 [7]

1000/1050 [472/495] 29,000 [8.5]

1200/1200 [566/566] 35,400 [10.4]

14,000 [4.1]

17,000 [5]

21,400 [6.3]

25,300 [7.4]

4800 [1.4]

7000 [2.1]

7600 [2.2]

10,100 [3]

1.8

2.3

2.8

3.4

18,800 [5.5] 1.7/3.1 10,400 [3]

24,000 [7] 2.2/3.2 13,500 [4]

29,000 [8.5] 2.7/3.1 16,000 [4.7]

35,800 [10.5] 3.2/3.3 20,200 [5.9]

1.6/1.96

2/2

2.3/2

2.9/2.08

7.2

7.2

7.2

7.2

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 76

Louvered

Louvered

Louvered

Louvered

Smooth 0.375 [9.5] 12.42 [1.15] 2 / 18 [7]

Smooth 0.375 [9.5] 12.42 [1.15] 2 / 18 [7]

Smooth 0.375 [9.5] 12.42 [1.15] 2 / 18 [7]

Smooth 0.375 [9.5] 12.42 [1.15] 2 / 18 [7]

Refrigerant Control

TX Valves

TX Valves

TX Valves

TX Valves

Indoor Coil—Fin Type Tube Type Tube Size in. [mm]

Louvered Rifled 0.3125 [7.9]

Louvered Rifled 0.3125 [7.9]

Louvered Rifled 0.3125 [7.9]

Louvered Rifled 0.3125 [7.9]

10.13 [0.94]

10.13 [0.94]

10.13 [0.94]

10.13 [0.94]

1 / 18 [7] TX Valves 1/0.75 [19.05] Propeller

1 / 18 [7] TX Valves 1/0.75 [19.05] Propeller

1 / 18 [7] TX Valves 1/0.75 [19.05] Propeller

1 / 18 [7] TX Valves 1/0.75 [19.05] Propeller

1/22 [559]

1/22 [559]

1/22 [559]

1/22 [559]

Direct/1

Direct/1

Direct/1

Direct/1

2600 [1227] 1 at 1/5 HP

2600 [1227] 1 at 1/5 HP

2600 [1227] 1 at 1/5 HP

2600 [1227] 1 at 1/5 HP

Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW Heating Performance (Heat Pumps) Heating Input Btu [kW] Rating System Power KW/COP Low Temp. Btuh [kW] Rating System Power KW/COP HSPF (Btu/Watts-hr) Compressor No./Type Outdoor Sound Rating (dB)3 Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm]

Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm] Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM Motor Frame Size Filter—Type Furnished

1075

1075

1075

1075

FC Centrifugal 1/9x7 [228.6x177.8] Direct/2

FC Centrifugal 1/9x7 [228.6x177.8] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2+D33

FC Centrifugal 1/10x9 [254x228.6] Direct/1

1

1

1

1

1/4

1/4

1/2

1/3

1075

1075

1075

1075

48 Field Supplied

48 Field Supplied

48 Field Supplied

48 Field Supplied

No

No

No

No

(1)1x20x16 [25x508x406]

(1)1x20x20 [25x508x508]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

112 [3175]

112 [3175]

119 [3374]

106 [3005]

Net Weight lbs. [kg]

383 [174]

395 [179]

405 [184]

405 [184]

Ship Weight lbs. [kg]

423 [192]

435 [197]

445 [202]

445 [202]

(No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g] Weights

[ ] Designates Metric Conversions

See Page 12 for Notes.

10

GENERAL DATA—RQMA- SERIES NOMINAL SIZES 1.5-3 TONS [5-10.6 kW] Model RQMA- Series Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW Heating Performance (Heat Pumps) Heating Input Btu [kW] Rating System Power KW/COP Low Temp. Btuh [kW] Rating System Power KW/COP HSPF (Btu/Watts-hr)

A036JK 36,600 [10.7] 10.5/12 1200/1200 [566/566] 35,400 [10.4] 25,300 [7.4] 10,100 [3] 3.4 35,800 [10.5] 3.2/3.3 20,200 [5.9] 2.9/2.08 7.2

Compressor No./Type Outdoor Sound Rating (dB)3 Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm]

1/Copeland Scroll 76 Louvered Smooth 0.375 [9.5] 12.42 [1.15] 2 / 18 [7]

Refrigerant Control

TX Valves

Indoor Coil—Fin Type Tube Type Tube Size in. [mm]

Louvered Rifled 0.3125 [7.9]

Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm] Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM Motor Frame Size Filter—Type Furnished (No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g]

10.13 [0.94] 1 / 18 [7] TX Valves 1/0.75 [19.05] Propeller 1/22 [559] Direct/1 2600 [1227] 1 at 1/5 HP 1075 FC Centrifugal 1/10x9 [254x228.6] Direct/1 1 1/3 1075 48 Field Supplied No (1)1x24x24 [25x610x610] 106 [3005]

Weights Net Weight lbs. [kg]

405 [184]

Ship Weight lbs. [kg]

445 [202] [ ] Designates Metric Conversions

See Page 12 for Notes.

11

GENERAL DATA—RQKA/RQMA- SERIES NOTES: 1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. [ ] Designates Metric Conversions

12

SYSTEMS PERFORMANCE—RQKA- SERIES GROSS SYSTEMS PERFORMANCE DATA—RQKA-A018 ENTERING INDOOR AIR @ 80°F [26.7°C] wbE CFM [L/s] DR ➀

660 [311] .27

71°F [21.7°C] 600 [283] .26

510 [241] .24

660 [311] .27

67°F [19.4°C] 600 [283] .26

510 [241] .24

660 [311] .27

63°F [17.2°C] 600 [283] .26

510 [241] .24

Total BTUH [kW] 75 Sens BTUH [kW] [23.9] Power

21.9 [6.42] 12.0 [3.52] 1.3

21.6 [6.33] 11.4 [3.34] 1.3

21.1 [6.18] 10.5 [3.08] 1.3

20.0 [5.86] 14.0 [4.10] 1.3

19.7 [5.77] 13.4 [3.93] 1.3

19.2 [5.63] 12.5 [3.66] 1.3

18.6 [5.45] 15.6 [4.57] 1.3

18.3 [5.36] 15.0 [4.40] 1.3

17.8 [5.22] 14.1 [4.13] 1.3

Total BTUH [kW] 80 Sens BTUH [kW] [26.7] Power

21.2 [6.21] 11.7 [3.43] 1.4

20.9 [6.13] 11.2 [3.28] 1.4

20.4 [5.98] 10.3 [3.02] 1.4

19.3 [5.66] 13.7 [4.02] 1.4

19.0 [5.57] 13.1 [3.84] 1.4

18.5 [5.42] 12.3 [3.60] 1.4

17.9 [5.25] 15.3 [4.48] 1.4

17.6 [5.16] 14.7 [4.31] 1.4

17.1 [5.01] 13.9 [4.07] 1.4

Total BTUH [kW] 85 Sens BTUH [kW] [29.4] Power

20.7 [6.07] 11.6 [3.40] 1.5

20.3 [5.95] 11.0 [3.22] 1.4

19.9 [5.83] 10.1 [2.96] 1.4

18.8 [5.51] 13.5 [3.96] 1.5

18.5 [5.42] 13.0 [3.81] 1.5

18.0 [5.28] 12.1 [3.55] 1.4

17.4 [5.10] 15.1 [4.43] 1.4

17.0 [4.98] 14.5 [4.25] 1.4

16.6 [4.86] 13.7 [4.02] 1.4

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

20.2 [5.92] 11.4 [3.34] 1.5 19.8 [5.80] 11.2 [3.28] 1.6 19.3 [5.66] 11.0 [3.22] 1.7

19.9 [5.83] 10.8 [3.17] 1.5 19.5 [5.71] 10.6 [3.11] 1.6 19.0 [5.57] 10.4 [3.05] 1.7

19.4 [5.69] 9.9 [2.90] 1.5 19.0 [5.57] 9.7 [2.84] 1.6 18.5 [5.42] 9.5 [2.78] 1.7

18.3 [5.36] 13.4 [3.93] 1.6 17.9 [5.25] 13.2 [3.87] 1.6 17.5 [5.13] 13.0 [3.81] 1.7

18.0 [5.28] 12.8 [3.75] 1.5 17.6 [5.16] 12.6 [3.69] 1.6 17.1 [5.01] 12.4 [3.63] 1.7

17.5 [5.13] 11.9 [3.49] 1.5 17.1 [5.01] 11.7 [3.43] 1.6 16.7 [4.89] 11.5 [3.37] 1.7

16.9 [4.95] 15.0 [4.40] 1.5 16.5 [4.84] 14.8 [4.34] 1.6 16.1 [4.72] 14.5 [4.25] 1.7

16.6 [4.86] 14.4 [4.22] 1.5 16.2 [4.75] 14.2 [4.16] 1.6 15.7 [4.60] 14.0 [4.10] 1.7

16.1 [4.72] 13.5 [3.96] 1.5 15.7 [4.60] 13.3 [3.90] 1.6 15.3 [4.48] 13.1 [3.84] 1.6

Total BTUH [kW] 105 Sens BTUH [kW] [40.6] Power

18.8 [5.51] 10.7 [3.14] 1.8

18.5 [5.42] 10.1 [2.96] 1.7

18.0 [5.28] 9.2 [2.70] 1.7

16.9 [4.95] 12.7 [3.72] 1.8

16.6 [4.86] 12.1 [3.55] 1.8

16.1 [4.72] 11.2 [3.28] 1.7

15.5 [4.54] 14.3 [4.19] 1.7

15.2 [4.45] 13.7 [4.02] 1.7

14.7 [4.31] 12.8 [3.75] 1.7

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

18.1 [5.30] 10.3 [3.02] 1.8 17.2 [5.04] 9.9 [2.90] 1.9

17.8 [5.22] 9.7 [2.84] 1.8 16.9 [4.95] 9.3 [2.73] 1.9

17.3 [5.07] 8.9 [2.61] 1.8 16.4 [4.81] 8.4 [2.46] 1.9

16.2 [4.75] 12.3 [3.60] 1.9 15.3 [4.48] 11.9 [3.49] 1.9

15.9 [4.66] 11.7 [3.43] 1.8 15.0 [4.40] 11.3 [3.31] 1.9

15.4 [4.51] 10.9 [3.19] 1.8 14.5 [4.25] 10.4 [3.05] 1.9

14.8 [4.34] 13.9 [4.07] 1.8 13.9 [4.07] 13.4 [3.93] 1.9

14.5 [4.25] 13.3 [3.90] 1.8 13.6 [3.99] 12.9 [3.78] 1.9

14.0 [4.10] 12.4 [3.63] 1.8 13.1 [3.84] 12.0 [3.52] 1.9

O U T D O O R D R Y B U L B T E M P E R A T U R E

GROSS SYSTEMS PERFORMANCE DATA—RQKA-A024 ENTERING INDOOR AIR @ 80°F [26.7°C] wbE CFM [L/s] DR ➀

880 [415] .25

71°F [21.7°C] 800 [378] .24

680 [321] .22

880 [415] .25

67°F [19.4°C] 800 [378] .24

680 [321] .22

880 [415] .25

63°F [17.2°C] 800 [378] .24

680 [321] .22

Total BTUH [kW] 75 Sens BTUH [kW] [23.9] Power

28.8 [8.44] 15.8 [4.63] 2.0

28.4 [8.32] 14.9 [4.37] 2.0

27.7 [8.12] 13.7 [4.02] 2.0

27.2 [7.97] 18.9 [5.54] 2.0

26.8 [7.85] 18.1 [5.30] 2.0

26.1 [7.65] 16.9 [4.95] 2.0

25.0 [7.33] 21.4 [6.27] 2.0

24.5 [7.18] 20.6 [6.04] 1.9

23.9 [7.00] 19.3 [5.66] 1.9

Total BTUH [kW] 80 Sens BTUH [kW] [26.7] Power

28.8 [8.44] 15.7 [4.60] 2.1

28.4 [8.32] 14.9 [4.37] 2.1

27.7 [8.12] 13.7 [4.02] 2.1

27.2 [7.97] 18.9 [5.54] 2.1

26.7 [7.82] 18.1 [5.30] 2.1

26.1 [7.65] 16.9 [4.95] 2.1

25.0 [7.33] 21.4 [6.27] 2.1

24.5 [7.18] 20.5 [6.01] 2.1

23.8 [6.98] 19.3 [5.66] 2.0

Total BTUH [kW] 85 Sens BTUH [kW] [29.4] Power

28.4 [8.32] 15.6 [4.57] 2.2

28.0 [8.21] 14.8 [4.34] 2.2

27.3 [8.00] 13.6 [3.99] 2.2

26.8 [7.85] 18.8 [5.51] 2.2

26.3 [7.71] 18.0 [5.28] 2.2

25.7 [7.53] 16.8 [4.92] 2.2

24.6 [7.21] 21.2 [6.21] 2.2

24.1 [7.06] 20.4 [5.98] 2.2

23.4 [6.86] 19.2 [5.63] 2.1

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

27.8 [8.15] 15.4 [4.51] 2.3 26.9 [7.88] 15.2 [4.45] 2.5 25.9 [7.59] 14.8 [4.34] 2.6

27.3 [8.00] 14.6 [4.28] 2.3 26.4 [7.74] 14.3 [4.19] 2.4 25.5 [7.47] 14.0 [4.10] 2.6

26.6 [7.80] 13.4 [3.93] 2.3 25.8 [7.56] 13.1 [3.84] 2.4 24.8 [7.27] 12.8 [3.75] 2.5

26.1 [7.65] 18.6 [5.45] 2.3 25.3 [7.41] 18.3 [5.36] 2.5 24.3 [7.12] 18.0 [5.28] 2.6

25.7 [7.53] 17.8 [5.22] 2.3 24.8 [7.27] 17.5 [5.13] 2.4 23.9 [7.00] 17.2 [5.04] 2.6

25.0 [7.33] 16.6 [4.86] 2.3 24.1 [7.06] 16.3 [4.78] 2.4 23.2 [6.80] 15.9 [4.66] 2.5

23.9 [7.00] 21.0 [6.15] 2.3 23.0 [6.74] 20.8 [6.10] 2.4 22.1 [6.48] 20.4 [5.98] 2.5

23.4 [6.86] 20.2 [5.92] 2.3 22.6 [6.62] 20.0 [5.86] 2.4 21.6 [6.33] 19.6 [5.74] 2.5

22.8 [6.68] 19.0 [5.57] 2.2 21.9 [6.42] 18.7 [5.48] 2.4 21.0 [6.15] 18.4 [5.39] 2.5

Total BTUH [kW] 105 Sens BTUH [kW] [40.6] Power

25.0 [7.33] 14.4 [4.22] 2.7

24.5 [7.18] 13.6 [3.99] 2.7

23.8 [6.98] 12.4 [3.63] 2.6

23.3 [6.83] 17.6 [5.16] 2.7

22.9 [6.71] 16.8 [4.92] 2.7

22.2 [6.51] 15.5 [4.54] 2.6

21.1 [6.18] 20.0 [5.86] 2.6

20.7 [6.07] 19.2 [5.63] 2.6

20.0 [5.86] 18.0 [5.28] 2.6

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

24.1 [7.06] 13.9 [4.07] 2.8 23.3 [6.83] 13.4 [3.93] 2.9

23.6 [6.92] 13.1 [3.84] 2.8 22.9 [6.71] 12.6 [3.69] 2.9

22.9 [6.71] 11.9 [3.49] 2.8 22.2 [6.51] 11.4 [3.34] 2.9

22.4 [6.56] 17.1 [5.01] 2.8 21.7 [6.36] 16.6 [4.86] 2.9

22.0 [6.45] 16.3 [4.78] 2.8 21.3 [6.24] 15.8 [4.63] 2.9

21.3 [6.24] 15.1 [4.43] 2.7 20.6 [6.04] 14.6 [4.28] 2.9

20.2 [5.92] 19.6 [5.74] 2.7 19.5 [5.71] 19.0 [5.57] 2.9

19.8 [5.80] 18.7 [5.48] 2.7 19.0 [5.57] 18.2 [5.33] 2.8

19.1 [5.60] 17.5 [5.13] 2.7 18.4 [5.39] 17.0 [4.98] 2.8

O U T D O O R D R Y B U L B T E M P E R A T U R E

DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

13

SYSTEMS PERFORMANCE—RQKA- SERIES GROSS SYSTEMS PERFORMANCE DATA—RQKA-A030 ENTERING INDOOR AIR @ 80°F [26.7°C] wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1000 [472] .25

850 [401] .23

1100 [519] .26

67°F [19.4°C] 1000 [472] .25

850 [401] .23

1100 [519] .26

63°F [17.2°C] 1000 [472] .25

850 [401] .23

Total BTUH [kW] 36.2 [10.61] 75 Sens BTUH [kW] 21.2 [6.21] [23.9] Power 2.4

35.6 [10.43] 20.2 [5.92] 2.4

34.8 [10.20] 18.7 [5.48] 2.4

34.7 [10.17] 24.7 [7.24] 2.5

34.2 [10.02] 23.6 [6.92] 2.5

33.3 [9.76] 22.1 [6.48] 2.4

33.4 [9.79] 28.8 [8.44] 2.4

32.8 [9.61] 27.8 [8.15] 2.4

32.0 [9.38] 26.2 [7.68] 2.3

Total BTUH [kW] 36.0 [10.55] 80 Sens BTUH [kW] 20.6 [6.04] [26.7] Power 2.6

35.4 [10.37] 19.6 [5.74] 2.6

34.6 [10.14] 18.1 [5.30] 2.5

34.5 [10.11] 24.0 [7.03] 2.6

33.9 [9.94] 23.0 [6.74] 2.6

33.1 [9.70] 21.5 [6.30] 2.6

33.2 [9.73] 28.2 [8.26] 2.5

32.6 [9.55] 27.2 [7.97] 2.5

31.7 [9.29] 25.6 [7.50] 2.5

Total BTUH [kW] 35.3 [10.35] 85 Sens BTUH [kW] 20.1 [5.89] [29.4] Power 2.7

34.8 [10.20] 19.1 [5.60] 2.7

33.9 [9.94] 17.6 [5.16] 2.7

33.9 [9.94] 23.6 [6.92] 2.8

33.3 [9.76] 22.6 [6.62] 2.8

32.5 [9.52] 21.0 [6.15] 2.7

32.5 [9.52] 27.7 [8.12] 2.7

31.9 [9.35] 26.7 [7.82] 2.7

31.1 [9.11] 25.2 [7.39] 2.6

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

34.4 [10.08] 19.8 [5.80] 2.9 33.2 [9.73] 19.4 [5.69] 3.0 31.9 [9.35] 19.0 [5.57] 3.2

33.8 [9.91] 18.7 [5.48] 2.8 32.6 [9.55] 18.4 [5.39] 3.0 31.3 [9.17] 18.0 [5.28] 3.1

32.9 [9.64] 17.2 [5.04] 2.8 31.8 [9.32] 16.9 [4.95] 3.0 30.5 [8.94] 16.5 [4.84] 3.1

32.9 [9.64] 23.2 [6.80] 2.9 31.7 [9.29] 22.9 [6.71] 3.1 30.4 [8.91] 22.5 [6.59] 3.2

32.3 [9.47] 22.2 [6.51] 2.9 31.2 [9.14] 21.8 [6.39] 3.1 29.9 [8.76] 21.5 [6.30] 3.2

31.5 [9.23] 20.7 [6.07] 2.9 30.3 [8.88] 20.3 [5.95] 3.0 29.0 [8.50] 19.9 [5.83] 3.2

31.5 [9.23] 27.3 [8.00] 2.8 30.4 [8.91] 27.0 [7.91] 3.0 29.1 [8.53] 26.6 [7.80] 3.1

31.0 [9.09] 26.3 [7.71] 2.8 29.8 [8.73] 26.0 [7.62] 2.9 28.5 [8.35] 25.6 [7.50] 3.1

30.1 [8.82] 24.8 [7.27] 2.8 29.0 [8.50] 24.4 [7.15] 2.9 27.6 [8.09] 24.1 [7.06] 3.1

Total BTUH [kW] 30.6 [8.97] 105 Sens BTUH [kW] 18.6 [5.45] [40.6] Power 3.3

30.0 [8.79] 17.6 [5.16] 3.3

29.1 [8.53] 16.0 [4.69] 3.2

29.1 [8.53] 22.0 [6.45] 3.4

28.5 [8.35] 21.0 [6.15] 3.3

27.7 [8.12] 19.5 [5.71] 3.3

27.7 [8.12] 26.2 [7.68] 3.3

27.2 [7.97] 25.1 [7.36] 3.2

26.3 [7.71] 23.6 [6.92] 3.2

28.7 [8.41] 17.0 [4.98] 3.4 27.7 [8.12] 16.2 [4.75] 3.6

27.9 [8.18] 15.4 [4.51] 3.4 26.8 [7.85] 14.7 [4.31] 3.5

27.9 [8.18] 21.4 [6.27] 3.5 26.8 [7.85] 20.6 [6.04] 3.7

27.3 [8.00] 20.4 [5.98] 3.5 26.2 [7.68] 19.6 [5.74] 3.6

26.4 [7.74] 18.9 [5.54] 3.5 25.4 [7.44] 18.1 [5.30] 3.6

26.5 [7.77] 25.6 [7.50] 3.4 25.4 [7.44] 24.8 [7.27] 3.6

25.9 [7.59] 24.5 [7.18] 3.4 24.9 [7.30] 23.8 [6.98] 3.5

25.1 [7.36] 23.0 [6.74] 3.3 24.0 [7.03] 22.2 [6.51] 3.5

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

1100 [519] .26

29.3 [8.59] 18.0 [5.28] 3.5 28.2 [8.26] 17.2 [5.04] 3.6

GROSS SYSTEMS PERFORMANCE DATA—RQKA-A036 ENTERING INDOOR AIR @ 80°F [26.7°C] wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1200 [566] .26

1020 [481] .24

1320 [623] .27

67°F [19.4°C] 1200 [566] .26

1020 [481] .24

1320 [623] .27

63°F [17.2°C] 1200 [566] .26

1020 [481] .24

Total BTUH [kW] 42.9 [12.57] 75 Sens BTUH [kW] 23.4 [6.86] [23.9] Power 2.9

42.2 [12.37] 22.2 [6.51] 2.9

41.2 [12.07] 20.4 [5.98] 2.8

41.4 [12.13] 28.2 [8.26] 3.0

40.7 [11.93] 27.0 [7.91] 2.9

39.7 [11.63] 25.2 [7.39] 2.9

39.7 [11.63] 32.8 [9.61] 2.9

39.0 [11.43] 31.6 [9.26] 2.9

38.0 [11.14] 29.7 [8.70] 2.8

Total BTUH [kW] 41.8 [12.25] 80 Sens BTUH [kW] 23.3 [6.83] [26.7] Power 3.1

41.1 [12.05] 22.1 [6.48] 3.1

40.1 [11.75] 20.3 [5.95] 3.0

40.3 [11.81] 28.1 [8.24] 3.2

39.7 [11.63] 26.9 [7.88] 3.1

38.6 [11.31] 25.1 [7.36] 3.1

38.6 [11.31] 32.7 [9.58] 3.1

37.9 [11.11] 31.5 [9.23] 3.0

36.9 [10.81] 29.7 [8.70] 3.0

Total BTUH [kW] 41.0 [12.02] 85 Sens BTUH [kW] 23.1 [6.77] [29.4] Power 3.3

40.3 [11.81] 21.9 [6.42] 3.3

39.3 [11.52] 20.1 [5.89] 3.2

39.5 [11.58] 27.9 [8.18] 3.3

38.8 [11.37] 26.7 [7.82] 3.3

37.8 [11.08] 24.9 [7.30] 3.3

37.8 [11.08] 32.5 [9.52] 3.3

37.1 [10.87] 31.3 [9.17] 3.2

36.1 [10.58] 29.5 [8.65] 3.2

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

40.2 [11.78] 22.9 [6.71] 3.5 39.5 [11.58] 22.5 [6.59] 3.7 38.7 [11.34] 22.0 [6.45] 3.9

39.5 [11.58] 21.6 [6.33] 3.5 38.8 [11.37] 21.3 [6.24] 3.6 38.0 [11.14] 20.8 [6.10] 3.8

38.5 [11.28] 19.8 [5.80] 3.4 37.8 [11.08] 19.4 [5.69] 3.6 37.0 [10.84] 19.0 [5.57] 3.8

38.8 [11.37] 27.7 [8.12] 3.5 38.0 [11.14] 27.3 [8.00] 3.7 37.2 [10.90] 26.8 [7.85] 3.9

38.1 [11.17] 26.4 [7.74] 3.5 37.3 [10.93] 26.1 [7.65] 3.7 36.5 [10.70] 25.6 [7.50] 3.9

37.1 [10.87] 24.6 [7.21] 3.5 36.3 [10.64] 24.2 [7.09] 3.6 35.5 [10.40] 23.8 [6.98] 3.8

37.0 [10.84] 32.2 [9.44] 3.4 36.3 [10.64] 31.9 [9.35] 3.6 35.5 [10.40] 31.4 [9.20] 3.8

36.4 [10.67] 31.0 [9.09] 3.4 35.6 [10.43] 30.6 [8.97] 3.6 34.8 [10.20] 30.2 [8.85] 3.8

35.3 [10.35] 29.2 [8.56] 3.4 34.6 [10.14] 28.8 [8.44] 3.6 33.8 [9.91] 28.4 [8.32] 3.7

Total BTUH [kW] 37.7 [11.05] 105 Sens BTUH [kW] 21.5 [6.30] [40.6] Power 4.0

37.0 [10.84] 20.2 [5.92] 4.0

36.0 [10.55] 18.4 [5.39] 4.0

36.2 [10.61] 26.3 [7.71] 4.1

35.5 [10.40] 25.0 [7.33] 4.1

34.5 [10.11] 23.2 [6.80] 4.0

34.5 [10.11] 30.8 [9.03] 4.0

33.8 [9.91] 29.6 [8.67] 4.0

32.8 [9.61] 27.8 [8.15] 3.9

35.7 [10.46] 19.6 [5.74] 4.2 34.0 [9.96] 18.9 [5.54] 4.4

34.7 [10.17] 17.8 [5.22] 4.2 33.0 [9.67] 17.1 [5.01] 4.3

34.9 [10.23] 25.6 [7.50] 4.3 33.3 [9.76] 24.9 [7.30] 4.5

34.2 [10.02] 24.4 [7.15] 4.2 32.6 [9.55] 23.7 [6.95] 4.4

33.2 [9.73] 22.6 [6.62] 4.2 31.6 [9.26] 21.9 [6.42] 4.4

33.2 [9.73] 30.2 [8.85] 4.2 31.5 [9.23] 29.5 [8.65] 4.4

32.5 [9.52] 29.0 [8.50] 4.2 30.9 [9.06] 28.3 [8.29] 4.3

31.5 [9.23] 27.2 [7.97] 4.1 29.8 [8.73] 26.4 [7.74] 4.3

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1320 [623] .27

36.4 [10.67] 20.8 [6.10] 4.2 34.7 [10.17] 20.1 [5.89] 4.4

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

14

SYSTEMS PERFORMANCE—RQKA- SERIES GROSS SYSTEMS PERFORMANCE DATA—RQKA-A042 ENTERING INDOOR AIR @ 80°F [26.7°C] wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1400 [661] .27

1190 [562] .25

1540 [727] .28

67°F [19.4°C] 1400 [661] .27

1190 [562] .25

1540 [727] .28

63°F [17.2°C] 1400 [661] .27

1190 [562] .25

Total BTUH [kW] 48.6 [14.24] 75 Sens BTUH [kW] 27.1 [7.94] [23.9] Power 3.2

47.9 [14.04] 25.7 [7.53] 3.1

46.7 [13.69] 23.6 [6.92] 3.1

46.1 [13.51] 32.0 [9.38] 3.1

45.4 [13.31] 30.6 [8.97] 3.1

44.2 [12.95] 28.5 [8.35] 3.1

44.3 [12.98] 38.3 [11.22] 3.1

43.6 [12.78] 36.9 [10.81] 3.1

42.4 [12.43] 34.9 [10.23] 3.0

Total BTUH [kW] 48.0 [14.07] 80 Sens BTUH [kW] 26.6 [7.80] [26.7] Power 3.4

47.2 [13.83] 25.2 [7.39] 3.3

46.1 [13.51] 23.1 [6.77] 3.3

45.5 [13.33] 31.5 [9.23] 3.3

44.7 [13.10] 30.1 [8.82] 3.3

43.6 [12.78] 28.1 [8.24] 3.3

43.7 [12.81] 37.8 [11.08] 3.3

42.9 [12.57] 36.4 [10.67] 3.3

41.8 [12.25] 34.4 [10.08] 3.2

Total BTUH [kW] 47.3 [13.86] 85 Sens BTUH [kW] 26.3 [7.71] [29.4] Power 3.6

46.5 [13.63] 24.9 [7.30] 3.5

45.3 [13.28] 22.9 [6.71] 3.5

44.8 [13.13] 31.2 [9.14] 3.5

44.0 [12.90] 29.9 [8.76] 3.5

42.9 [12.57] 27.8 [8.15] 3.5

43.0 [12.60] 37.6 [11.02] 3.5

42.2 [12.37] 36.2 [10.61] 3.5

41.1 [12.05] 34.1 [9.99] 3.4

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

46.4 [13.60] 26.2 [7.68] 3.8 45.4 [13.31] 26.0 [7.62] 4.0 44.3 [12.98] 25.8 [7.56] 4.2

45.6 [13.36] 24.8 [7.27] 3.7 44.7 [13.10] 24.6 [7.21] 3.9 43.5 [12.75] 24.4 [7.15] 4.1

44.5 [13.04] 22.7 [6.65] 3.7 43.5 [12.75] 22.6 [6.62] 3.9 42.3 [12.40] 22.4 [6.56] 4.1

43.9 [12.87] 31.1 [9.11] 3.7 42.9 [12.57] 30.9 [9.06] 3.9 41.8 [12.25] 30.7 [9.00] 4.1

43.2 [12.66] 29.7 [8.70] 3.7 42.2 [12.37] 29.6 [8.67] 3.9 41.0 [12.02] 29.3 [8.59] 4.1

42.0 [12.31] 27.6 [8.09] 3.7 41.0 [12.02] 27.5 [8.06] 3.9 39.9 [11.69] 27.3 [8.00] 4.1

42.1 [12.34] 37.4 [10.96] 3.7 41.1 [12.05] 37.2 [10.90] 3.9 40.0 [11.72] 37.0 [10.84] 4.1

41.4 [12.13] 36.0 [10.55] 3.7 40.4 [11.84] 35.9 [10.52] 3.9 39.2 [11.49] 35.7 [10.46] 4.1

40.2 [11.78] 33.9 [9.94] 3.6 39.2 [11.49] 33.8 [9.91] 3.8 38.1 [11.17] 33.6 [9.85] 4.0

Total BTUH [kW] 42.9 [12.57] 105 Sens BTUH [kW] 25.4 [7.44] [40.6] Power 4.4

42.1 [12.34] 24.0 [7.03] 4.3

41.0 [12.02] 22.0 [6.45] 4.3

40.4 [11.84] 30.3 [8.88] 4.3

39.7 [11.63] 29.0 [8.50] 4.3

38.5 [11.28] 26.9 [7.88] 4.2

38.6 [11.31] 36.7 [10.76] 4.3

37.9 [11.11] 35.3 [10.35] 4.3

36.7 [10.76] 33.2 [9.73] 4.2

40.6 [11.90] 23.4 [6.86] 4.5 38.7 [11.34] 22.4 [6.56] 4.7

39.4 [11.55] 21.3 [6.24] 4.5 37.6 [11.02] 20.3 [5.95] 4.7

38.8 [11.37] 29.7 [8.70] 4.5 37.0 [10.84] 28.7 [8.41] 4.7

38.1 [11.17] 28.3 [8.29] 4.5 36.3 [10.64] 27.3 [8.00] 4.7

36.9 [10.81] 26.3 [7.71] 4.4 35.1 [10.29] 25.3 [7.41] 4.6

37.0 [10.84] 36.0 [10.55] 4.5 35.2 [10.32] 35.0 [10.26] 4.7

36.3 [10.64] 34.6 [10.14] 4.5 34.5 [10.11] 33.6 [9.85] 4.6

35.1 [10.29] 32.6 [9.55] 4.4 33.3 [9.76] 31.6 [9.26] 4.6

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

1540 [727] .28

41.3 [12.10] 24.8 [7.27] 4.6 39.5 [11.58] 23.8 [6.98] 4.8

GROSS SYSTEMS PERFORMANCE DATA—RQKA-A048 ENTERING INDOOR AIR @ 80°F [26.7°C] wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1500 [708] .21

1280 [604] .19

1650 [779] .22

67°F [19.4°C] 1500 [708] .21

1280 [604] .19

1650 [779] .22

63°F [17.2°C] 1500 [708] .21

1280 [604] .19

Total BTUH [kW] 57.0 [16.71] 75 Sens BTUH [kW] 29.5 [8.65] [23.9] Power 4.2

56.1 [16.44] 27.9 [8.18] 4.1

54.8 [16.06] 25.5 [7.47] 4.1

54.5 [15.97] 35.2 [10.32] 4.1

53.6 [15.71] 33.6 [9.85] 4.1

52.3 [15.33] 31.2 [9.14] 4.0

51.4 [15.06] 40.4 [11.84] 4.0

50.5 [14.80] 38.8 [11.37] 4.0

49.2 [14.42] 36.4 [10.67] 3.9

Total BTUH [kW] 55.7 [16.32] 80 Sens BTUH [kW] 31.7 [9.29] [26.7] Power 4.4

54.8 [16.06] 30.1 [8.82] 4.3

53.5 [15.68] 27.7 [8.12] 4.3

53.2 [15.59] 37.5 [10.99] 4.3

52.3 [15.33] 35.9 [10.52] 4.2

51.0 [14.95] 33.5 [9.82] 4.2

50.1 [14.68] 42.7 [12.51] 4.2

49.2 [14.42] 41.1 [12.05] 4.2

47.9 [14.04] 38.7 [11.34] 4.1

Total BTUH [kW] 54.4 [15.94] 85 Sens BTUH [kW] 32.2 [9.44] [29.4] Power 4.5

53.5 [15.68] 30.6 [8.97] 4.5

52.2 [15.30] 28.2 [8.26] 4.4

51.9 [15.21] 38.0 [11.14] 4.5

51.0 [14.95] 36.4 [10.67] 4.4

49.7 [14.57] 34.0 [9.96] 4.4

48.8 [14.30] 43.2 [12.66] 4.4

47.9 [14.04] 41.6 [12.19] 4.4

46.6 [13.66] 39.2 [11.49] 4.3

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

53.2 [15.59] 31.5 [9.23] 4.7 51.8 [15.18] 30.1 [8.82] 4.9 50.4 [14.77] 28.3 [8.29] 5.1

52.3 [15.33] 29.9 [8.76] 4.7 50.9 [14.92] 28.5 [8.35] 4.9 49.5 [14.51] 26.7 [7.82] 5.1

51.0 [14.95] 27.5 [8.06] 4.6 49.6 [14.54] 26.1 [7.65] 4.8 48.2 [14.13] 24.3 [7.12] 5.0

50.6 [14.83] 37.3 [10.93] 4.7 49.3 [14.45] 35.8 [10.49] 4.8 47.9 [14.04] 34.1 [9.99] 5.0

49.7 [14.57] 35.7 [10.46] 4.6 48.4 [14.18] 34.3 [10.05] 4.8 47.0 [13.77] 32.5 [9.52] 5.0

48.4 [14.18] 33.3 [9.76] 4.6 47.1 [13.80] 31.9 [9.35] 4.7 45.7 [13.39] 30.1 [8.82] 4.9

47.5 [13.92] 42.5 [12.46] 4.6 46.2 [13.54] 41.0 [12.02] 4.8 44.8 [13.13] 39.2 [11.49] 5.0

46.7 [13.69] 40.9 [11.99] 4.5 45.3 [13.28] 39.4 [11.55] 4.7 43.9 [12.87] 37.6 [11.02] 4.9

45.3 [13.28] 38.5 [11.28] 4.5 44.0 [12.90] 37.0 [10.84] 4.7 42.6 [12.48] 35.2 [10.32] 4.9

Total BTUH [kW] 48.8 [14.30] 105 Sens BTUH [kW] 26.7 [7.82] [40.6] Power 5.3

48.0 [14.07] 25.1 [7.36] 5.2

46.6 [13.66] 22.7 [6.65] 5.2

46.3 [13.57] 32.4 [9.50] 5.2

45.4 [13.31] 30.9 [9.06] 5.2

44.1 [12.92] 28.5 [8.35] 5.1

43.2 [12.66] 37.6 [11.02] 5.1

42.3 [12.40] 36.0 [10.55] 5.1

41.0 [12.02] 33.6 [9.85] 5.0

46.2 [13.54] 24.1 [7.06] 5.4 44.2 [12.95] 24.2 [7.09] 5.6

44.9 [13.16] 21.7 [6.36] 5.4 42.9 [12.57] 21.8 [6.39] 5.6

44.5 [13.04] 31.5 [9.23] 5.4 42.5 [12.46] 31.6 [9.26] 5.6

43.6 [12.78] 29.9 [8.76] 5.4 41.6 [12.19] 30.0 [8.79] 5.5

42.3 [12.40] 27.5 [8.06] 5.3 40.3 [11.81] 27.6 [8.09] 5.5

41.5 [12.16] 36.6 [10.73] 5.3 39.5 [11.58] 36.7 [10.76] 5.5

40.6 [11.90] 35.0 [10.26] 5.3 38.6 [11.31] 35.1 [10.29] 5.5

39.3 [11.52] 32.6 [9.55] 5.2 37.3 [10.93] 32.7 [9.58] 5.4

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1650 [779] .22

47.1 [13.80] 25.7 [7.53] 5.5 45.1 [13.22] 25.8 [7.56] 5.7

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

15

SYSTEMS PERFORMANCE—RQMA- SERIES GROSS SYSTEMS PERFORMANCE DATA—RQMA-A018 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

770 [363] .23

71°F [21.7°C] 700 [330 .22

600 [283] .19

770 [363] .23

67°F [19.4°C] 700 [330] .22

600 [283] .19

770 [363] .23

63°F [17.2°C] 700 [330] .22

600 [283] .19

Total BTUH [kW] 75 Sens BTUH [kW] [23.9] Power

24.6 [7.21] 14.3 [4.19] 1.3

24.3 [7.12] 13.6 [3.99] 1.3

23.8 [6.98] 12.6 [3.69] 1.3

22.8 [6.68] 16.8 [4.92] 1.3

22.4 [6.56] 16.1 [4.72] 1.3

21.9 [6.42] 15.0 [4.40] 1.3

21.5 [6.30] 19.4 [5.69] 1.3

21.1 [6.18] 18.7 [5.48] 1.3

20.6 [6.04] 17.7 [5.19] 1.3

Total BTUH [kW] 80 Sens BTUH [kW] [26.7] Power

24.2 [7.09] 14.2 [4.16] 1.4

23.8 [6.98] 13.5 [3.96] 1.4

23.3 [6.83] 12.4 [3.63] 1.3

22.3 [6.54] 16.6 [4.86] 1.4

21.9 [6.42] 15.9 [4.66] 1.4

21.4 [6.27] 14.9 [4.37] 1.4

21.0 [6.15] 19.2 [5.63] 1.4

20.6 [6.04] 18.5 [5.42] 1.4

20.1 [5.89] 17.5 [5.13] 1.3

Total BTUH [kW] 85 Sens BTUH [kW] [29.4] Power

23.5 [6.89] 13.9 [4.07] 1.4

23.1 [6.77] 13.2 [3.87] 1.4

22.6 [6.62] 12.1 [3.55] 1.4

21.6 [6.33] 16.3 [4.78] 1.5

21.2 [6.21] 15.6 [4.57] 1.4

20.7 [6.07] 14.6 [4.28] 1.4

20.3 [5.95] 18.9 [5.54] 1.4

20.0 [5.86] 18.2 [5.33] 1.4

19.4 [5.69] 17.2 [5.04] 1.4

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

22.7 [6.65] 13.5 [3.96] 1.5

22.3 [6.54] 12.8 [3.75] 1.5

21.8 [6.39] 11.7 [3.43] 1.5

20.8 [6.10] 15.9 [4.66] 1.5

20.4 [5.98] 15.2 [4.45] 1.5

19.9 [5.83] 14.2 [4.16] 1.5

19.5 [5.71] 18.5 [5.42] 1.5

19.1 [5.60] 17.8 [5.22] 1.5

18.6 [5.45] 16.8 [4.92] 1.5

21.8 [6.39] 13.0 [3.81] 1.6

21.4 [6.27] 12.3 [3.60] 1.6

20.9 [6.13] 11.3 [3.31] 1.5

19.9 [5.83] 15.5 [4.54] 1.6

19.6 [5.74] 14.8 [4.34] 1.6

19.0 [5.57] 13.7 [4.02] 1.5

18.6 [5.45] 18.2 [5.33] 1.6

18.3 [5.36] 17.4 [5.10] 1.5

17.8 [5.22] 16.4 [4.81] 1.5

21.0 [6.15] 12.6 [3.69] 1.6

20.6 [6.04] 11.9 [3.49] 1.6

20.1 [5.89] 10.9 [3.19] 1.6

19.1 [5.60] 15.0 [4.40] 1.6

18.7 [5.48] 14.4 [4.22] 1.6

18.2 [5.33] 13.3 [3.90] 1.6

17.8 [5.22] 17.6 [5.16] 1.6

17.4 [5.10] 17.0 [4.98] 1.6

16.9 [4.95] 16.0 [4.69] 1.6

Total BTUH [kW] 105 Sens BTUH [kW] [40.6] Power

20.2 [5.92] 12.3 [3.60] 1.7

19.8 [5.80] 11.6 [3.40] 1.7

19.3 [5.66] 10.6 [3.11] 1.7

18.3 [5.36] 14.7 [4.31] 1.7

18.0 [5.28] 14.0 [4.10] 1.7

17.4 [5.10] 13.0 [3.81] 1.7

17.0 [4.98] 17.0 [4.98] 1.7

16.7 [4.89] 16.7 [4.89] 1.7

16.2 [4.75] 15.6 [4.57] 1.7

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

19.6 [5.74] 12.1 [3.55] 1.8 19.2 [5.63] 12.0 [3.52] 1.8

19.2 [5.63] 11.4 [3.34] 1.7 18.9 [5.54] 11.3 [3.31] 1.8

18.7 [5.48] 10.3 [3.02] 1.7 18.3 [5.36] 10.3 [3.02] 1.8

17.7 [5.19] 14.5 [4.25] 3.5 17.4 [5.10] 14.5 [4.25] 1.8

17.4 [5.10] 13.8 [4.04] 1.8 17.0 [4.98] 13.8 [4.04] 1.8

16.8 [4.92] 12.8 [3.75] 1.7 16.5 [4.84] 12.7 [3.72] 1.8

16.4 [4.81] 16.4 [4.81] 1.7 16.1 [4.72] 16.1 [4.72] 1.8

16.1 [4.72] 16.1 [4.72] 1.7 15.7 [4.60] 15.7 [4.60] 1.8

15.6 [4.57] 15.4 [4.51] 1.7 15.2 [4.45] 15.2 [4.45] 1.8

O U T D O O R D R Y B U L B T E M P E R A T U R E

GROSS SYSTEMS PERFORMANCE DATA—RQMA-A024 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 800 [378] .20

680 [321] .18

880 [415] .22

67°F [19.4°C] 800 [378] .20

680 [321] .18

880 [415] .22

63°F [17.2°C] 800 [378] .20

680 [321] .18

Total BTUH [kW] 30.5 [8.94] 75 Sens BTUH [kW] 17.9 [5.25] [23.9] 1.8 Power

30.1 [8.82] 17.0 [4.98] 1.7

29.4 [8.62] 15.8 [4.63] 1.7

28.6 [8.38] 20.6 [6.04] 1.7

28.2 [8.26] 19.8 [5.80] 1.7

27.5 [8.06] 18.5 [5.42] 1.7

26.0 [7.62] 23.4 [6.86] 1.7

26.8 [7.85] 22.6 [6.62] 1.7

25.7 [7.53] 21.3 [6.24] 1.6

Total BTUH [kW] 29.6 [8.67] 80 Sens BTUH [kW] 17.5 [5.13] [26.7] 1.9 Power

29.2 [8.56] 16.6 [4.86] 1.8

28.5 [8.35] 15.4 [4.51] 1.8

27.7 [8.12] 20.2 [5.92] 1.8

27.2 [7.97] 19.4 [5.69] 1.8

26.6 [7.80] 18.1 [5.30] 1.8

25.9 [7.59] 23.0 [6.74] 1.8

25.4 [7.44] 22.2 [6.51] 1.8

24.8 [7.27] 20.9 [6.13] 1.7

Total BTUH [kW] 28.8 [8.44] 85 Sens BTUH [kW] 17.0 [4.98] [29.4] 2.0 Power

28.3 [8.29] 16.2 [4.75] 1.9

27.7 [8.12] 14.9 [4.37] 1.9

26.9 [7.88] 19.8 [5.80] 1.9

26.4 [7.74] 18.9 [5.54] 1.9

25.7 [7.53] 17.7 [5.19] 1.9

25.1 [7.36] 22.6 [6.62] 1.9

24.6 [7.21] 21.7 [6.36] 1.9

23.9 [7.00] 20.5 [6.01] 1.8

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

28.0 [8.21] 16.5 [4.84] 2.1

27.6 [8.09] 15.7 [4.60] 2.0

26.9 [7.88] 14.4 [4.22] 2.0

26.1 [7.65] 19.3 [5.66] 2.0

25.6 [7.50] 18.5 [5.42] 2.0

25.0 [7.33] 17.2 [5.04] 2.0

24.3 [7.12] 22.1 [6.48] 2.0

23.8 [6.98] 21.3 [6.24] 2.0

23.1 [6.77] 20.0 [5.86] 1.9

27.2 [7.97] 16.0 [4.69] 2.1

26.8 [7.85] 15.2 [4.45] 2.1

26.1 [7.65] 13.9 [4.07] 2.1

25.3 [7.41] 18.8 [5.51] 2.1

24.9 [7.30] 18.0 [5.28] 2.1

24.2 [7.09] 16.7 [4.89] 2.1

23.5 [6.89] 21.6 [6.33] 2.1

23.1 [6.77] 20.8 [6.10] 2.1

22.4 [6.56] 19.5 [5.71] 2.0

26.4 [7.74] 15.5 [4.54] 2.2

26.0 [7.62] 14.7 [4.31] 2.2

25.3 [7.41] 13.4 [3.93] 2.2

24.5 [7.18] 18.3 [5.36] 2.2

24.1 [7.06] 17.5 [5.13] 2.2

23.4 [6.86] 16.2 [4.75] 2.2

22.7 [6.65] 21.1 [6.18] 2.2

22.3 [6.54] 20.3 [5.95] 2.2

21.6 [6.33] 19.0 [5.57] 2.1

Total BTUH [kW] 25.6 [7.50] 105 Sens BTUH [kW] 15.1 [4.43] [40.6] 2.3 Power

25.2 [7.39] 14.2 [4.16] 2.3

24.5 [7.18] 13.0 [3.81] 2.3

23.7 [6.95] 17.8 [5.22] 2.3

23.2 [6.80] 17.0 [4.98] 2.3

22.6 [6.62] 15.7 [4.60] 2.3

21.9 [6.42] 20.6 [6.04] 2.3

21.4 [6.27] 19.8 [5.80] 2.3

20.8 [6.10] 18.5 [5.42] 2.2

24.3 [7.12] 13.8 [4.04] 2.4 23.2 [6.80] 13.4 [3.93] 2.5

23.6 [6.92] 12.5 [3.66] 2.4 22.6 [6.62] 12.1 [3.55] 2.5

22.8 [6.68] 17.4 [5.10] 2.4 21.8 [6.39] 17.0 [4.98] 2.5

22.3 [6.54] 16.5 [4.84] 2.4 21.3 [6.24] 16.1 [4.72] 2.5

21.7 [6.36] 15.3 [4.48] 2.4 20.6 [6.04] 14.9 [4.37] 2.5

21.0 [6.15] 20.2 [5.92] 2.4 20.0 [5.86] 19.7 [5.77] 2.5

20.5 [6.01] 19.3 [5.66] 2.4 19.5 [5.71] 18.9 [5.54] 2.5

19.8 [5.80] 18.1 [5.30] 2.3 18.8 [5.51] 17.7 [5.19] 2.4

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

880 [415] .22

24.7 [7.24] 14.6 [4.28] 2.4 23.7 [6.95] 14.2 [4.16] 2.5

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

16

SYSTEMS PERFORMANCE—RQMA- SERIES GROSS SYSTEMS PERFORMANCE DATA—RQMA-A030 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1000 [472] .24

850 [401] .21

1100 [519] .25

67°F [19.4°C] 1000 [472] .24

850 [401] .21

1100 [519] .25

63°F [17.2°C] 1000 [472] .24

850 [401] .21

Total BTUH [kW] 37.7 [11.05] 75 Sens BTUH [kW] 20.5 [6.01] [23.9] Power 2.1

37.2 [10.90] 19.5 [5.71] 2.0

36.4 [10.67] 18.0 [5.28] 2.0

34.7 [10.17] 24.2 [7.09] 2.0

34.2 [10.02] 23.2 [6.80] 2.0

33.4 [9.79] 21.7 [6.36] 2.0

33.0 [9.67] 27.1 [7.94] 2.0

32.5 [9.52] 26.1 [7.65] 2.0

31.7 [9.29] 24.5 [7.18] 2.0

Total BTUH [kW] 36.8 [10.79] 80 Sens BTUH [kW] 19.8 [5.80] [26.7] Power 2.2

36.3 [10.64] 18.8 [5.51] 2.1

35.4 [10.37] 17.3 [5.07] 2.1

33.8 [9.91] 23.6 [6.92] 2.1

33.3 [9.76] 22.6 [6.62] 2.1

32.4 [9.50] 21.1 [6.18] 2.1

32.1 [9.41] 26.4 [7.74] 2.1

31.5 [9.23] 25.4 [7.44] 2.1

30.7 [9.00] 23.9 [7.00] 2.1

Total BTUH [kW] 35.7 [10.46] 85 Sens BTUH [kW] 19.4 [5.69] [29.4] 2.3 Power

35.2 [10.32] 18.4 [5.39] 2.3

34.4 [10.08] 16.9 [4.95] 2.2

32.7 [9.58] 23.1 [6.77] 2.2

32.2 [9.44] 22.1 [6.48] 2.2

31.3 [9.17] 20.6 [6.04] 2.2

31.0 [9.09] 25.9 [7.59] 2.3

30.5 [8.94] 24.9 [7.30] 2.2

29.6 [8.67] 23.4 [6.86] 2.2

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

34.5 [10.11] 19.0 [5.57] 2.4

34.0 [9.96] 18.0 [5.28] 2.4

33.2 [9.73] 16.5 [4.84] 2.3

31.5 [9.23] 22.8 [6.68] 2.4

31.0 [9.09] 21.8 [6.39] 2.3

30.2 [8.85] 20.3 [5.95] 2.3

29.8 [8.73] 25.6 [7.50] 2.4

29.3 [8.59] 24.6 [7.21] 2.3

28.4 [8.32] 23.1 [6.77] 2.3

33.3 [9.76] 18.7 [5.48] 2.5

32.8 [9.61] 17.7 [5.19] 2.5

32.0 [9.38] 16.2 [4.75] 2.5

30.3 [8.88] 22.5 [6.59] 2.5

29.8 [8.73] 21.5 [6.30] 2.5

28.9 [8.47] 20.0 [5.86] 2.4

28.6 [8.38] 25.3 [7.41] 2.5

28.1 [8.24] 24.3 [7.12] 2.5

27.2 [7.97] 22.8 [6.68] 2.4

32.2 [9.44] 18.3 [5.36] 2.6

31.6 [9.26] 17.3 [5.07] 2.6

30.8 [9.03] 15.8 [4.63] 2.6

29.1 [8.53] 22.1 [6.48] 2.6

28.6 [8.38] 21.1 [6.18] 2.6

27.8 [8.15] 19.6 [5.74] 2.5

27.4 [8.03] 24.9 [7.30] 2.6

26.9 [7.88] 23.9 [7.00] 2.6

26.1 [7.65] 22.4 [6.56] 2.5

Total BTUH [kW] 31.1 [9.11] 105 Sens BTUH [kW] 17.8 [5.22] [40.6] 2.7 Power

30.6 [8.97] 16.8 [4.92] 2.7

29.8 [8.73] 15.3 [4.48] 2.7

28.1 [8.24] 21.5 [6.30] 2.7

27.6 [8.09] 20.5 [6.01] 2.7

26.8 [7.85] 19.0 [5.57] 2.7

26.4 [7.74] 24.3 [7.12] 2.7

25.9 [7.59] 23.3 [6.83] 2.7

25.1 [7.36] 21.8 [6.39] 2.7

29.8 [8.73] 16.0 [4.69] 2.8 29.2 [8.56] 14.8 [4.34] 2.9

29.0 [8.50] 14.5 [4.25] 2.8 28.4 [8.32] 13.3 [3.90] 2.9

27.3 [8.00] 20.7 [6.07] 2.8 26.8 [7.85] 19.5 [5.71] 2.9

26.8 [7.85] 19.7 [5.77] 2.8 26.2 [7.68] 18.5 [5.42] 2.9

26.0 [7.62] 18.2 [5.33] 2.8 25.4 [7.44] 17.0 [4.98] 2.9

25.6 [7.50] 23.5 [6.89] 2.8 25.1 [7.36] 22.4 [6.56] 2.9

25.1 [7.36] 22.5 [6.59] 2.8 24.5 [7.18] 21.4 [6.27] 2.9

24.2 [7.09] 21.0 [6.15] 2.8 23.7 [6.95] 19.9 [5.83] 2.9

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

1100 [519] .25

30.3 [8.88] 17.0 [4.98] 2.8 29.8 [8.73] 15.8 [4.63] 3.0

GROSS SYSTEMS PERFORMANCE DATA—RQMA-A036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

1320 [623] .30

71°F [21.7°C] 1200 [566] .29

1020 [481] .27

1320 [623] .30

67°F [19.4°C] 1200 [566] .29

1020 [481] .27

1320 [623] .30

63°F [17.2°C] 1200 [566] .29

1020 [481] .27

Total BTUH [kW] 40.0 [11.72] 75 Sens BTUH [kW] 22.7 [6.65] [23.9] 2.4 Power

39.3 [11.52] 38.3 [11.22] 21.5 [6.30] 19.7 [5.77] 2.4 2.4

39.9 [11.69] 28.1 [8.24] 2.4

39.2 [11.49] 26.9 [7.88] 2.4

38.2 [11.20] 25.1 [7.36] 2.3

36.9 [10.81] 30.9 [9.06] 2.4

36.3 [10.64] 29.7 [8.70] 2.3

35.3 [10.35] 28.0 [8.21] 2.3

Total BTUH [kW] 40.6 [11.90] 80 Sens BTUH [kW] 22.7 [6.65] [26.7] 2.6 Power

39.9 [11.69] 21.5 [6.30] 2.5

38.9 [11.40] 19.7 [5.77] 2.5

40.5 [11.87] 28.1 [8.24] 2.5

39.8 [11.66] 27.0 [7.91] 2.5

38.8 [11.37] 25.2 [7.39] 2.5

37.5 [10.99] 31.0 [9.09] 2.5

36.9 [10.81] 29.8 [8.73] 2.5

35.9 [10.52] 28.0 [8.21] 2.4

Total BTUH [kW] 40.3 [11.81] 85 Sens BTUH [kW] 22.4 [6.56] [29.4] 2.7 Power

39.6 [11.61] 21.3 [6.24] 2.7

38.6 [11.31] 19.5 [5.71] 2.7

40.2 [11.78] 27.9 [8.18] 2.7

39.5 [11.58] 26.7 [7.82] 2.7

38.5 [11.28] 24.9 [7.30] 2.6

37.3 [10.93] 30.7 [9.00] 2.7

36.6 [10.73] 29.5 [8.65] 2.6

35.6 [10.43] 27.7 [8.12] 2.6

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

39.4 [11.55] 21.9 [6.42] 2.9

38.7 [11.34] 20.8 [6.10] 2.9

37.7 [11.05] 19.0 [5.57] 2.8

39.3 [11.52] 27.4 [8.03] 2.9

38.6 [11.31] 26.2 [7.68] 2.8

37.6 [11.02] 24.4 [7.15] 2.8

36.4 [10.67] 30.2 [8.85] 2.8

35.7 [10.46] 29.0 [8.50] 2.8

34.7 [10.17] 27.2 [7.97] 2.8

38.0 [11.14] 21.3 [6.24] 3.0

37.3 [10.93] 20.1 [5.89] 3.0

36.3 [10.64] 18.3 [5.36] 3.0

37.9 [11.11] 26.7 [7.82] 3.0

37.2 [10.90] 25.5 [7.47] 3.0

36.2 [10.61] 23.7 [6.95] 2.9

35.0 [10.26] 29.5 [8.65] 3.0

34.3 [10.05] 28.3 [8.29] 2.9

33.3 [9.76] 26.6 [7.80] 2.9

36.4 [10.67] 20.5 [6.01] 3.2

35.7 [10.46] 19.3 [5.66] 3.2

34.7 [10.17] 17.5 [5.13] 3.1

36.2 [10.61] 25.9 [7.59] 3.2

35.6 [10.43] 24.7 [7.24] 3.1

34.6 [10.14] 23.0 [6.74] 3.1

33.3 [9.76] 28.8 [8.44] 3.1

32.7 [9.58] 27.6 [8.09] 3.1

31.6 [9.26] 25.8 [7.56] 3.1

Total BTUH [kW] 34.7 [10.17] 105 Sens BTUH [kW] 19.7 [5.77] [40.6] 3.3 Power

34.0 [9.96] 18.5 [5.42] 3.3

33.0 [9.67] 16.7 [4.89] 3.3

34.5 [10.11] 25.1 [7.36] 3.3

33.9 [9.94] 23.9 [7.00] 3.3

32.9 [9.64] 22.1 [6.48] 3.3

31.6 [9.26] 27.9 [8.18] 3.3

31.0 [9.09] 26.7 [7.82] 3.3

29.9 [8.76] 25.0 [7.33] 3.2

32.4 [9.50] 17.7 [5.19] 3.5 31.2 [9.14] 17.0 [4.98] 3.6

31.4 [9.20] 15.9 [4.66] 3.4 30.2 [8.85] 15.2 [4.45] 3.6

33.0 [9.67] 24.3 [7.12] 3.5 31.8 [9.32] 23.6 [6.92] 3.6

32.3 [9.47] 23.1 [6.77] 3.4 31.1 [9.11] 22.4 [6.56] 3.6

31.3 [9.17] 21.3 [6.24] 3.4 30.1 [8.82] 20.6 [6.04] 3.6

30.1 [8.82] 27.1 [7.94] 3.4 28.8 [8.44] 26.4 [7.74] 3.6

29.4 [8.62] 25.9 [7.59] 3.4 28.2 [8.26] 25.2 [7.39] 3.6

28.4 [8.32] 24.1 [7.06] 3.4 27.2 [7.97] 23.4 [6.86] 3.5

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

33.1 [9.70] 18.9 [5.54] 3.5 31.9 [9.35] 18.1 [5.30] 3.6

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

17

AIRFLOW PERFORMANCE—RQKA- SERIES INDOOR AIRFLOW PERFORMANCE—230 VOLTS Nominal Cooling Capacity Tons [kW]

1.5 [5.28]

Motor Speed from Factory

Blower Size/ Motor HP [W] & # of Speeds

Low

0.1 [.02]

Low 9x7 1/4 HP [186] 2 Speed Motor

2.0 [7.03]

High

2.5 [8.79]

Low

High

Low 10 x 9 1/2 HP [373] 2 Speed Motor 3.5 [12.31]

Med

High High

3.0 [10.55]

High

10 x 9 1/3 HP [249] 1 Speed Motor

High

Low

4.0 [14.07]

Med

10 x 9 3/4 HP [559] 3 Speed Motor

CFM [L/s] Air Delivery/RPM/Watts—230 Volts Side Discharge—Wet Coil External Static Pressure—Inches W.C. [kPa]

Motor Speed

Med

High

CFM 771 [364] RPM 825 Watts 253 CFM 946 [446] RPM 990 315 Watts CFM 1206 [569] RPM 760 Watts 419 CFM 1411 [666] RPM 865 Watts 498 CFM 1641 [774] RPM 980 Watts 589 CFM 1391 [666] RPM 835 Watts 428 CFM 1390 [656] RPM 781 Watts 431 CFM 1875 [885] RPM 1024 Watts 736 CFM 2024 [955] RPM 1089 Watts 809

0.2 [.05]

0.3 [.07]

751 [354] 870 242 922 [435] 1015 303 1182 [558] 815 406 1368 [646] 900 481 1577 [744] 1000 565 1357 [646] 875 419 1387 [655] 839 459

725 [342] 910 230 882 [416] 1035 288 1157 [546] 870 394 1327 [626] 935 464 1515 [715] 1020 543 1312 [626] 915 406 1375 [649] 896 486

0.4 [.10]

691 [326] 950 217 830 [392] 1055 273 1128 [532] 910 381 1285 [606] 970 447 1455 [687] 1035 523 1258 [606] 940 392 1353 [639] 935 512 1806 [852] 1739 [821] 1672 [789] 1042 1059 1073 690 653 620

0.5 [.12]

645 [304] 985 204 769 [363] 1070 257 1091 [515] 950 368 1238 [584] 1000 430 1393 [657] 1050 503 1201 [584] 965 378 1319 [622] 974 536 1602 [756] 1087 590 1960 [925] 1882 [888] 1793 [846] 1698 [801] 1099 1108 1116 1124 776 739 700 661

0.6 [.15]

0.7 [.17]

584 [276] 1010 189 701 [331] 1085 241 1044 [493] 975 353 1183 [558] 1020 411 1329 [627] 1065 481 1145 [558] 985 365 1272 [600] 1003 558 1528 [721] 1098 559 1602 [756] 1130 622

546 [258] 1030 181 630 [298] 1100 226 983 [464] 1000 334 1116 [527] 1035 391 1262 [596] 1080 456 1093 [527] 1000 355 1210 [571] 1032 579 1447 [683] 1109 523 1509 [712] 1136 587

NOTES: Data reflects airflow with electric strip heat installed.  WARNING: Do not operate unit in regions shown in bold (CFM greater than 1700 on 4 ton models) due to possibility of water blow-off. [ ] Designates Metric Conversions

18

AIRFLOW PERFORMANCE—RQKA- SERIES INDOOR AIRFLOW PERFORMANCE—208 VOLTS Nominal Cooling Capacity Tons [kW]

1.5 [5.28]

Motor Speed from Factory

Blower Size/ Motor HP [W] & # of Speeds

Low

0.1 [.02]

Low 9x7 1/4 HP [186] 2 Speed Motor

2.0 [7.03]

High

2.5 [8.79]

Low

High

Low 10 x 9 1/2 HP [373] 2 Speed Motor 3.5 [12.31]

Med

High High

3.0 [10.55]

High

10 x 9 1/3 HP [249] 1 Speed Motor

High

Low

4.0 [14.07]

Med

10 x 9 3/4 HP [559] 3 Speed Motor

CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—Wet Coil External Static Pressure—Inches W.C. [kPa]

Motor Speed

Med

High

CFM 675 [319] RPM 695 Watts 221 CFM 898 [424] RPM 940 Watts 292 CFM 1076 [508] RPM 730 Watts 356 CFM 1222 [577] RPM 765 Watts 423 CFM 1514 [715] RPM 895 538 Watts CFM 1222 [577] RPM 785 Watts 355 CFM 1179 [556] RPM 684 Watts 490 CFM 1719 [811] RPM 943 Watts 681 CFM 1954 [922] RPM 1060 Watts 769

0.2 [.05]

0.3 [.07]

0.4 [.10]

657 [310] 785 214 861 [406] 965 278 1059 [500] 775 349 1197 [565] 810 415 1461 [670] 930 514 1201 [565] 805 352 1180 [557] 755 477 1681 [793] 977 645

634 [299] 870 203 822 [388] 995 266 1032 [490] 820 341 1179 [556] 855 407 1415 [668] 965 493 1173 [556] 830 346 1183 [558] 825 464 1634 [771] 1011 611

602 [284] 905 191 777 [367] 1020 253 996 [470] 865 331 1162 [548] 890 397 1370 [647] 985 473 1137 [548] 870 340 1181 [557] 873 448 1579 [745] 1032 579

0.5 [.12]

560 [264] 940 171 721 [340] 1045 239 950 [448] 905 320 1137 [537] 920 386 1322 [624] 1005 454 1090 [537] 905 331 1169 [552] 921 430 1516 [715] 1052 548 1888 [891] 1816 [857] 1737 [820] 1655 [781] 1075 1089 1098 1106 731 692 654 617

0.6 [.15]

0.7 [.17]

505 [238] 980 163 651 [307] 1070 221 896 [423] 940 305 1097 [518] 960 370 1266 [597] 1025 434 1030 [518] 950 320 1139 [538] 960 409 1448 [683] 1067 516 1570 [741] 1115 583

435 [205] 1020 149 562 [265] 1090 199 832 [393] 975 287 1033 [488] 995 351 1197 [565] 1045 412 954 [488] 990 306 1087 [513] 999 384 1373 [648] 1082 484 1483 [700] 1123 551

NOTES: Data reflects airflow with electric strip heat installed.  WARNING: Do not operate unit in regions shown in bold (CFM greater than 1700 on 4 ton models) due to possibility of water blow-off.

DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE) CFM [L/s] 600 [283] 800 [378] Pressure Drop—Inches W.C. [kPa] .00 .01 [.002] [ ] Designates Metric Conversions

19

1000 [472] .02 [.005]

1200 [566] .03 [.007]

1400 [661] .05 [.012]

1600 [775] .07 [.017]

AIRFLOW PERFORMANCE—RQMA- SERIES INDOOR AIRFLOW PERFORMANCE—230 VOLTS Nominal Motor Cooling Speed Capacity from Tons [kW] Factory

Manufacturer Recommended Airflow Range (Min/Max)

1.5 Ton [5.28]

Low

525 CFM/675 CFM [271/319 L/s]

2.0 Ton [7.03]

High

700 CFM/900 CFM [330/425 L/s]

Blower Size Motor HP & # of Speeds

9 x 7 Blower 1/4 HP 2 Speed Motor

Motor Speed

Low

High

Low 2.5 Ton [8.79]

Low

875 CFM/1125 CFM [413/531 L/s]

10 x 9 Blower 1/2 HP 2 Speed Motor

Med

High 3.0 Ton [10.55]

High

10 x 9 Blower 1050 CFM/1350 CFM 1/3 HP 1 Speed [496/637 L/s] Motor

High

CFM [L/s] RPM (Watts) CFM [L/s] RPM (Watts) CFM [L/s] RPM (Watts) CFM [L/s] RPM (Watts) CFM [L/s] RPM (Watts) CFM [L/s] RPM (Watts)

0.1 [.02] 771 [364] 825 (253) 946 [446] 990 (315) 1206 [569] 760 (419) 1411 [666] 865 (498) 1641 [774] 980 (589) 1391 [656] 835 (428)

CFM Air Delivery/RPM/Watts–230 Volts Side Discharge–Wet Coil External Static Pressure (In. W.C.) 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 751 [354] 725 [342] 691 [326] 645 [304] 584 [276] 870 910 950 985 1010 (242) (230) (217) (204) (189) 922 [435] 882 [416] 830 [392] 769 [363] 701 [331] 1015 1035 1055 1070 1085 (303) (288) (273) (257) (241) 1182 [558] 1157 [546] 1128 [532] 1091 [515] 1044 [493] 815 870 910 950 975 (406) (394) (381) (368) (353) 1368 [646] 1327 [626] 1285 [606] 1238 [584] 1183 [558] 900 935 970 1000 1020 (481) (464) (447) (430) (411) 1577 [744] 1515 [715] 1455 [687] 1393 [657] 1329 [627] 1000 1020 1035 1050 1065 (565) (543) (523) (503) (481) 1357 [640] 1312 [619] 1258 [594] 1201 [567] 1145 [540] 875 915 940 965 985 (419) (406) (392) (378) (365)

0.7 [.17] 546 [258] 1030 (181) 630 [297] 1100 (226) 983 [464] 1000 (334) 1116 [527] 1035 (391) 1262 [596] 1080 (456) 1093 [516] 1000 (355)

INDOOR AIRFLOW PERFORMANCE—208 VOLTS 1.5 Ton [5.28]

Low

525 CFM/675 CFM [248/319 L/s]

2.0 Ton [7.03]

High

700 CFM/900 CFM [330/425 L/s]

9 x 7 Blower 1/4 HP 2 Speed Motor

Low

High

Low 2.5 Ton [8.79]

Low

875 CFM/1125 CFM [413/531 L/s]

10 x 9 Blower 1/2 HP 2 Speed Motor

Med

High 3.0 Ton [10.55]

High

10 x 9 Blower 1050 CFM/1350 CFM 1/3 HP 1 Speed [496/637 L/s] Motor

High

CFM [L/s] RPM (Watts) CFM [L/s] RPM (Watts) CFM [L/s] RPM (Watts) CFM [L/s] RPM (Watts) CFM [L/s] RPM (Watts) CFM [L/s] RPM (Watts)

675 [319] 695 (221) 898 [424] 940 (292) 1076 [508] 730 (356) 1222 [577] 765 (423) 1514 [715] 895 (538) 1222 [577] 785 (355)

657 [310] 785 (214) 861 [406] 965 (278) 1059 [500] 775 (349) 1197 [565] 810 (415) 1461 [690] 930 (514) 1201 [567] 805 (352)

634 [299] 870 (203) 822 [388] 995 (266) 1032 [487] 820 (341) 1179 [556] 855 (407) 1415 [668] 965 (493) 1173 [554] 830 (346)

602 [284] 905 (191) 777 [367] 1020 (253) 996 [470] 865 (331) 1162 [548] 890 (397) 1370 [647] 985 (473) 1137 [537] 870 (340)

560 [264] 940 (171) 721 [340] 1045 (239) 950 [448] 905 (320) 1137 [537] 920 (386) 1322 [624] 1005 (454) 1090 [514] 905 (331)

505 [238] 980 (163) 651 [307] 1070 (221) 896 [423] 940 (305) 1097 [518] 960 (370) 1266 [597] 1025 (434) 1030 [486] 950 (320)

435 [205] 1020 (149) 562 [265] 1090 (199) 832 [393] 975 (287) 1033 [488] 995 (351) 1197 [565] 1045 (412) 954 [450] 990 (306)

NOTE: Effect of electric strip heat on airflow performance is negligible.

DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE) CFM [L/s] 600 [283] 800 [378] Pressure Drop—Inches W.C. [kPa] .00 .01 [.002]

[ ] Designates Metric Conversions

20

1000 [472] .01 [.002]

1200 [566] .02 [.005]

1400 [661] .04 [.010]

ELECTRICAL DATA—RQKA- SERIES Model No. RQKAA018JK A024JK A030JK A036CK A036JK A042CK A042JK A048CK A048JK

Unit Information Unit Operating Voltage Range 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253

Minimum Circuit Ampacity 14/14 18/18 23/23 21/21 30/30 20/20 30/30 30/30 45/45

Evaporator Fan

Minimum Overcurrent Protection Device Size 20/20 25/25 30/30 25/25 40/40 25/25 35/35 35/35 60/60

Maximum Overcurrent Protection Device Size 20/20 25/25 35/35 35/35 50/50 30/30 50/50 45/45 70/70

No.

Volts

Phase

HP

1 1 1 1

208/230 208/230 208/230 208/230

1 1 1 1

1/4 1/4 1/2 1/3

1

208/230

1

1/3

1 1 1

208/230 208/230 208/230

1 1 1

1/2 1/2 3/4

1

208/230

1

3/4

Compressor Motor

Model No. RQKA-

No.

Volts

Phase

HP2

RPM

A018JK A024JK

1 1

208/230 208/230

1 1

1 1/2 2

3450 3450

A030JK

1

208/230

1

2 2/3

3450

A036CK A036JK A042CK A042JK

1 1 1 1

200/230 208/230 200/230 208/230

3 1 3 1

3 1/3 3 1/3 3 1/2 3 1/2

3450 3450 3450 3450

A048CK A048JK

1 1

200/230 208/230

3 1

4 4

3450 3450

Amps (FLA) 1.3 1.3 2.4 1.7 1.7 2.4 2.4 4.4 4.4

Amps (LRA) 2.3 2.3 4.8 2.2 2.2 4.8 4.8 9.5 9.5

Condenser Motor Amps1 (RLA) 9.6/9.6 15.4/15.4 14.8/14.8 14.4/14.4 21.4/21.4 12.4/12.4 20.8/20.8 18.8/18.8 31/31

Amps1 (LRA) 47/47 63/63 83/83 88/88 103/103 88/88 127/127 115/115 132/132

1. Horsepower Per Compressor. 2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.

21

No.

Volts

Phase

HP2

1 1

208/230 208/230

1 1

1/15 1/15

1

208/230

1

1/5

1 1 1 1

208/230 208/230 208/230 208/230

1 1 1 1

1/5 1/5 1/5 1/5

1 1

208/230 208/230

1 1

1/3 1/3

Amps1 (FLA) 0.5 0.5 1.3 1.3 1.3 1.3 1.3 1.7 1.7

Amps1 (LRA) 0.63 0.63 2.23 2.23 2.23 2.23 2.23 3 3

ELECTRICAL DATA—RQMA- SERIES Model No. RQMAA018JK A024JK A030JK A036CK A036JK

Unit Information Unit Operating Voltage Range 187-253 187-253 187-253 187-253 187-253

Minimum Circuit Ampacity 15/15 19/19 26/26 18/18 25/25

Evaporator Fan

Minimum Overcurrent Protection Device Size 20/20 25/25 30/30 20/20 30/30

Maximum Overcurrent Protection Device Size 20/20 30/30 40/40 25/25 40/40

No.

Volts

Phase

HP

1 1 1 1

208/230 208/230 208/230 208/230

1 1 1 1

1/4 1/4 1/2 1/3

1

208/230

1

1/3

Compressor Motor

Model No. RQMA-

No.

Volts

Phase

HP2

RPM

A018JK A024JK

1 1

208/230 208/230

1 1

1 1/2 2

3450 3450

A030JK

1

208/230

1

2 1/2

3450

A036CK A036JK

1 1

200/230 208/230

3 1

3 3

3450 3450

Amps (FLA) 1.3 1.3 2.4 1.7 1.7

Amps (LRA) 2.3 2.3 4.8 2.2 2.2

Condenser Motor Amps1 (RLA) 9.6/9.6 13.1/13.1 17.3/17.3 11.3/11.3 17.5/17.5

Amps1 (LRA) 50/50 63/63 72.5/72.5 77/77 95/95

1. Horsepower Per Compressor. 2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.

22

No.

Volts

Phase

HP2

1 1

208/230 208/230

1 1

1/5 1/5

1

208/230

1

1/5

1 1

208/230 208/230

1 1

1/5 1/5

Amps1 (FLA) 1.3 1.3 1.3 1.3 1.3

Amps1 (LRA) 2.23 2.23 2.23 2.23 2.23

ELECTRIC HEATER KITS—RQKA- SERIES Unit Model Application

RQKA-A018JK

RQKA-A024JK

RQKA-A030JK

RQKA-A036JK

RQKA-A042JK

RQKA-A048JK

RQKA-A036CK

RQKA-A042CK

RQKA-A048CK

Electric Heater Kit Models RXQJ-A03J (208-240 volt, 1-ph, 3kW) RXQJ-A05J (208-240 volt, 1-ph, 5kW)

Country USA & Canada USA & Canada

RXQJ-A06J (208-240 volt, 1-ph, 6kW) RXQJ-A08J (208-240 volt, 1-ph, 8kW)

USA & Canada USA & Canada

RXQJ-A03J (208-240 volt, 1-ph, 3kW)

USA & Canada

RXQJ-A05J (208-240 volt, 1-ph, 5kW) RXQJ-A06J (208-240 volt, 1-ph, 6kW) RXQJ-A08J (208-240 volt, 1-ph, 8kW) RXQJ-A10J (208-240 volt, 1-ph, 10kW)

USA & Canada USA & Canada USA & Canada USA Only

RXQJ-A11J (208-240 volt, 1-ph, 10kW-Canadian)

USA & Canada

RXQJ-A03J (208-240 volt, 1-ph, 3kW) RXQJ-A05J (208-240 volt, 1-ph, 5kW)

USA & Canada USA & Canada

RXQJ-A06J (208-240 volt, 1-ph, 6kW)

USA & Canada

RXQJ-A08J (208-240 volt, 1-ph, 8kW) RXQJ-A10J (208-240 volt, 1-ph, 10kW)

USA & Canada USA Only

RXQJ-A11J (208-240 volt, 1-ph, 10kW-Canadian)

USA & Canada

RXQJ-A06J (208-240 volt, 1-ph, 6kW) RXQJ-A10J (208-240 volt, 1-ph, 10kW)

USA & Canada USA Only

RXQJ-A11J (208-240 volt, 1-ph, 10kW-Canadian) RXQJ-A15J (208-240 volt, 1-ph, 15kW)

USA & Canada USA Only

RXQJ-A16J (208-240 volt, 1-ph, 15kW-Canadian)

USA & Canada

RXQJ-B06J (208-240 volt, 1-ph, 6kW)

USA Only

RXQJ-B10J (208-240 volt, 1-ph, 10kW)

USA Only

RXQJ-B11J (208-240 volt, 1-ph, 10kW-Canadian) RXQJ-B15J (208-240 volt, 1-ph, 15kW) RXQJ-B16J (208-240 volt, 1-ph, 15kW-Canadian)

USA & Canada USA Only USA & Canada

RXQJ-B06J (208-240 volt, 1-ph, 6kW)

USA Only

RXQJ-B10J (208-240 volt, 1-ph, 10kW) RXQJ-B11J (208-240 volt, 1-ph, 10kW-Canadian) RXQJ-B15J (208-240 volt, 1-ph, 15kW) RXQJ-B16J (208-240 volt, 1-ph, 15kW-Canadian)

USA Only USA & Canada USA Only USA & Canada

RXQJ-A10C (208-240 volt, 3-ph, 10kW) RXQJ-A12C (208-240 volt, 3-ph, 12kW)

USA & Canada USA Only

RXQJ-A15C (208-240 volt, 3-ph, 15kW)

USA Only

RXQJ-A16C (208-240 volt, 3-ph, 15kW-Canadian) RXQJ-A10C (208-240 volt, 3-ph, 10kW)

USA & Canada USA & Canada

RXQJ-A12C (208-240 volt, 3-ph, 12kW) RXQJ-A15C (208-240 volt, 3-ph, 15kW) RXQJ-A16C (208-240 volt, 3-ph, 15kW-Canadian)

USA Only USA Only USA & Canada

RXQJ-A10C (208-240 volt, 3-ph, 10kW) RXQJ-A12C (208-240 volt, 3-ph, 12kW)

USA & Canada USA Only

RXQJ-A15C (208-240 volt, 3-ph, 15kW) RXQJ-A16C (208-240 volt, 3-ph, 15kW-Canadian)

USA Only USA & Canada

WARNING ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

23

ELECTRIC HEATER KITS—RQMA- SERIES Unit Model Application

RQMA-A018JK

RQMA-A024JK

RQMA-A030JK

RQMA-A036JK

RQMA-A036CK

Electric Heater Kit Models RXQJ-A03J (208/240 volt, 1-ph, 3kW)

Country USA & Canada

RXQJ-A05J (208/240 volt, 1-ph, 5kW)

USA & Canada

RXQJ-A06J (208/240 volt, 1-ph, 6kW) RXQJ-A08J (208/240 volt, 1-ph, 8kW)

USA & Canada USA & Canada

RXQJ-A03J (208/240 volt, 1-ph, 3kW)

USA & Canada

RXQJ-A05J (208/240 volt, 1-ph, 5kW)

USA & Canada

RXQJ-A06J (208/240 volt, 1-ph, 6kW) RXQJ-A08J (208/240 volt, 1-ph, 8kW) RXQJ-A10J (208/240 volt, 1-ph, 10kW)

USA & Canada USA & Canada USA Only

RXQJ-A11J (208/240 volt, 1-ph, 10kW-Canadian)

USA & Canada

RXQJ-A03J (208/240 volt, 1-ph, 3kW) RXQJ-A05J (208/240 volt, 1-ph, 5kW) RXQJ-A06J (208/240 volt, 1-ph, 6kW)

USA & Canada USA & Canada USA & Canada

RXQJ-A08J (208/240 volt, 1-ph, 8kW)

USA & Canada

RXQJ-A10J (208/240 volt, 1-ph, 10kW)

USA Only

RXQJ-A11J (208/240 volt, 1-ph, 10kW-Canadian) RXQJ-A06J (208/240 volt, 1-ph, 6kW) RXQJ-A10J (208/240 volt, 1-ph, 10kW)

USA & Canada USA & Canada USA Only

RXQJ-A11J (208/240 volt, 1-ph, 10kW-Canadian)

USA & Canada

RXQJ-A15J (208/240 volt, 1-ph, 15kW)

USA Only

RXQJ-A16J (208/240 volt, 1-ph, 15kW-Canadian)

USA & Canada

RXQJ-A10C (208/240 volt, 3-ph, 10kW)

USA & Canada

RXQJ-A12C (208/240 volt, 3-ph, 12kW) RXQJ-A15C (208/240 volt, 3-ph, 15kW) RXQJ-A16C (208/240 volt, 3-ph, 15kW-Canadian)

USA Only USA Only USA & Canada

WARNING ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

24

ELECTRIC HEATER KITS—RQKA- SERIES AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION 208-240 Volt, Single Phase and Three Phase, 60 HZ Model No. RQKA-

Heater Kit Nominal kW

No. of Elements

No. of Sequence Steps

Rated Heater kW @ 208-240 V

Heater KBTU/Hr @ 208-240 V

Heater Amps. @ 208-240 V

Unit Min. Ckt. Ampacity @ 208-240 V

No Heat 03 05 06 08 No Heat 03 05 06 08 10 No Heat 03 05 06 08 10 No Heat 06 10 15 No Heat 10 12 15 No Heat 06 10 15 No Heat 10 12 15 No Heat 06 10 15 No Heat 10 12 15

— 1 1 2 2 — 1 1 2 2 2 — 1 1 2 2 2 — 2 2 3 — 3 3 3 — 2 2 3 — 3 3 3 — 2 2 3 — 3 3 3

— 1 1 1 1 — 1 1 1 1 1 — 1 1 1 1 1 — 1 1 1 — 1 1 1 — 1 1 1 — 1 1 1 — 1 1 1 — 1 1 1

— 2.1/2.8 3.6/4.8 4.2/5.6 5.7/7.6 — 2.1/2.8 3.6/4.8 4.2/5.6 5.7/7.6 7.2/9.6 — 2.1/2.8 3.6/4.8 4.2/5.6 5.7/7.6 7.2/9.6 — 4.2/5.6 7.2/9.6 10.8/14.4 — 7.2/9.6 8.6/11.4 10.8/14.4 — 4.2/5.6 7.2/9.6 10.8/14.4 — 7.2/9.6 8.6/11.4 10.8/14.4 — 4.2/5.6 7.2/9.6 10.8/14.4 — 7.2/9.6 8.6/11.4 10.8/14.4

— 7.17/9.55 12.28/16.38 14.33/19.11 19.45/25.93 — 7.17/9.55 12.28/16.38 14.33/19.11 19.45/25.93 24.57/32.76 — 7.17/9.55 12.28/16.38 14.33/19.11 19.45/25.93 24.57/32.76 — 14.33/19.11 24.57/32.76 36.85/49.13 — 24.57/32.76 29.34/38.90 36.85/49.13 — 14.33/19.11 24.57/32.76 36.85/49.13 — 24.57/32.76 29.34/38.90 36.85/49.13 — 14.33/19.11 24.57/32.76 36.85/49.13 — 24.57/32.76 29.34/38.90 36.85/49.13

— 10.1/11.7 17.3/20.0 20.2/23.3 27.4/31.6 — 10.1/11.7 17.3/20.0 20.2/23.3 27.4/31.6 34.6/40.0 — 10.1/11.7 17.3/20.0 20.2/23.3 27.4/31.6 34.6/40.0 — 20.2/23.3 34.6/40.0 51.9/60.0 — 20.0/23.1 23.8/27.4 30.1/34.7 — 20.2/23.3 34.6/40.0 51.9/60.0 — 20.0/23.1 23.8/27.4 30.1/34.7 — 20.2/23.3 34.6/40.0 51.9/60.0 — 20.0/23.1 23.8/27.4 30.1/34.7

14/14 27/29 36/39 39/43 48/54 18/18 30/32 39/43 43/47 52/57 61/68 23/23 35/37 44/48 48/52 57/62 66/73 30/30 55/59 73/80 95/105 21/21 46/50 51/56 59/65 30/30 55/59 73/80 95/105 20/20 45/49 49/54 57/63 45/45 71/74 89/95 110/120 30/30 55/59 60/64 68/73

A018J

A024J

A030J

A036J

A036C

A042J

A042C

A048J

A048C

SUPPLY WIRE LENGTH-FEET

Copper Wire Size—AWG 300 250 200 150 100 50

Overcurrent Protective Device Size Min./Max. @ 208 V 20/20 30/30 40/40 40/40 50/50 25/25 35/35 40/45 45/45 60/60 70/70 30/35 40/45 45/50 50/50 60/60 70/70 40/50 60/70 80/80 100/100 25/35 50/50 60/60 60/60 35/50 60/70 80/80 100/100 25/30 45/50 50/50 60/60 60/70 80/90 90/110 110/125 35/45 60/60 60/70 70/70

Min./Max. @ 240 V 20/20 30/30 40/40 45/45 60/60 25/25 35/40 45/45 50/50 60/60 70/70 30/35 40/45 50/50 60/60 70/70 80/80 40/50 60/70 80/90 100/110 25/35 50/50 60/60 70/70 35/50 60/70 80/90 100/110 25/30 50/50 60/60 70/70 60/70 80/90 100/110 125/125 35/45 60/70 70/70 80/80

(1% Voltage Drop)

4 4 6 8 10 14

3 4 4 6 8 12

2 3 4 6 8 10

2 3 4 4 6 10

1 2 3 4 6 8

1/0 1 2 4 6 8

1/0 1 2 3 4 6

2/0 1/0 1 3 4 6

2/0 1/0 1 2 4 6

3/0 2/0 1/0 2 3 4

3/0 2/0 1/0 1 3 4

3/0 2/0 1/0 1 2 4

4/0 3/0 2/0 1/0 2 3

4/0 3/0 2/0 1/0 2 3

4/0 3/0 2/0 1/0 1 3

4/0 4/0 3/0 1/0 1 2

250 4/0 3/0 2/0 1 2

250 4/0 3/0 2/0 1 2

250 4/0 3/0 2/0 1 2

250 4/0 3/0 2/0 1/0 2

300 250 4/0 2/0 1/0 1

300 250 4/0 3/0 1/0 1

300 250 4/0 3/0 1/0 1

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

105

110

115

120

125

CIRCUIT AMPACITY Notes: 1. Wire size based on 60°C. type copper conductors below 100 ampacity. 2. Wire size based on 75°C. type copper conductors for 100 ampacity and above.

[ ] Designates Metric Conversions

25

ELECTRIC HEATER KITS—RQMA- SERIES AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION 208/240 Volt, Single Phase, 60 HZ Nominal Size Tons [kW]

1.5 [5.28] 1-PHASE

2.0 [7.03] 1-PHASE

2.5 [8.79] 1-PHASE

3.0 [10.55] 1-PHASE

3.0 [10.55] 3-PHASE

Unit Kit Nominal kW

No. of Elements

No. of Sequence Steps

Rated Heater kW @ 208-240 V

Heater KBTU/Hr @ 208-240 V

Heater Amps. @ 208-240 V

Unit Min. Ckt. Ampacity @ 208-240 V

No Heat 03 05* 06 08 No Heat 03 05* 06 08 10* No Heat 03 05* 06 08 10* No Heat 06* 10* 15* No Heat 10* 12 15*

— 1 1 2 2 — 1 1 2 2 2 — 1 1 2 2 2 — 2 2 3 — 3 3 3

— 1 1 1 1 — 1 1 1 1 1 — 1 1 1 1 1 — 1 1 1 — 1 1 1

— 2.1/2.8 3.6/4.8 4.2/5.6 5.7/7.6 — 2.1/2.8 3.6/4.8 4.2/5.6 5.7/7.6 7.2/9.6 — 2.1/2.8 3.6/4.8 4.2/5.6 5.7/7.6 7.2/9.6 — 4.2/5.6 7.2/9.6 10.8/14.4 — 7.2/9.6 8.6/11.4 10.8/14.4

— 7.17/9.55 12.28/16.38 14.33/19.11 19.45/25.93 — 7.17/9.55 12.28/16.38 14.33/19.11 19.45/25.93 24.57/32.76 — 7.17/9.55 12.28/16.38 14.33/19.11 19.45/25.93 24.57/32.76 — 14.33/19.11 24.57/32.76 36.85/49.13 — 24.57/32.76 29.34/38.90 36.85/49.13

— 10.1/11.7 17.3/20.0 20.2/23.3 27.4/31.6 — 10.1/11.7 17.3/20.0 20.2/23.3 27.4/31.6 34.6/40.0 — 10.1/11.7 17.3/20.0 20.2/23.3 27.4/31.6 34.6/40.0 — 20.2/23.3 34.6/40.0 51.9/60.0 — 20.0/23.1 23.8/27.4 30.1/34.7

15/15 28/30 37/40 40/44 49/54 19/19 32/34 41/44 45/49 54/59 63/69 26/26 38/40 47/51 51/55 60/65 69/76 25/25 51/54 69/75 90/100 18/18 43/46 47/52 55/61

Overcurrent Protective Device Size Min./Max. @ 208 V

Min./Max. @ 240 V

20/20 30/30 40/40 40/40 50/50 25/30 35/40 45/45 45/50 60/60 70/70 30/40 40/50 50/50 60/60 60/70 70/70 30/40 60/60 70/70 90/90 20/25 45/45 50/50 60/60

20/20 30/35 40/40 45/45 60/60 25/30 35/40 45/50 50/50 60/60 70/70 30/40 45/50 60/60 60/60 70/70 80/80 30/40 60/60 80/80 100/100 20/25 50/50 60/60 70/70

*Indicates heater series that may be factory installed by ordering appropriate model number. (See Model Identification, page 5)

SUPPLY WIRE LENGTH-FEET

Copper Wire Size—AWG 300 250 200 150 100 50

(1% Voltage Drop)

4 4 6 8 10 14

3 4 4 6 8 12

2 3 4 6 8 10

2 3 4 4 6 10

1 2 3 4 6 8

1/0 1 2 4 6 8

1/0 1 2 3 4 6

2/0 1/0 1 3 4 6

2/0 1/0 1 2 4 6

3/0 2/0 1/0 2 3 4

3/0 2/0 1/0 1 3 4

3/0 2/0 1/0 1 2 4

4/0 3/0 2/0 1/0 2 3

4/0 3/0 2/0 1/0 2 3

4/0 3/0 2/0 1/0 1 3

4/0 4/0 3/0 1/0 1 2

250 4/0 3/0 2/0 1 2

250 4/0 3/0 2/0 1 2

250 4/0 3/0 2/0 1 2

250 4/0 3/0 2/0 1/0 2

300 250 4/0 2/0 1/0 1

300 250 4/0 3/0 1/0 1

300 250 4/0 3/0 1/0 1

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

105

110

115

120

125

CIRCUIT AMPACITY Notes: 1. Wire size based on 60°C. type copper conductors below 100 ampacity. 2. Wire size based on 75°C. type copper conductors for 100 ampacity and above.

[ ] Designates Metric Conversions

26

UNIT DIMENSIONS—RQKA/RQMA- SERIES UNIT DIMENSIONS SELF-CONTAINED AIR CONDITIONERS

RQKA/RQMA1.5-4 [5-14.1 kW] TON MODELS

[ ] Designates Metric Conversions

27

TYPICAL INSTALLATIONS

[ ] Designates Metric Conversions

28

ACCESSORIES ACCESSORY EQUIPMENT Accessory Description

Model Application

Accessory Model No. RXQG-AAA14 (14" [356 mm] Height) RXQG-AAA24 (24" [610 mm] Height)

Roofcurbs

RQKA/RQMA

Supply & Return Diffusers

RQKA/RQMA

Economizers (Downflow Only)

RQKA/RQMA

Fresh Air Damper

RQKA/RQMA

Rectangular to Round Transition (Downflow)

RQKA/RQMA

Filter Kit

RQKA/RQMA

RXMC-CA02 (16" [406 mm] Ducts) RXMC-CA03 (18" [457 mm] Ducts) RXRY-B01

High Pressure Control

RQKA/RQMA

RXAB-A04

Outdoor Thermostat Monitor

RQKA/RQMA RQKA/RQMA

RXPT-A01 RXPM-B01

Low Ambient Control Duct Adapter Sideflow Square to Round Transition

RQKA/RQMA RQKA/RQMA

RXPZ-C01 or RXPZ-F01 RXMC-BA01

RXRN-BD15 RXRE-CAA30 (3 Position) RXRD-CAM10 (Fully Modulating) RXRF-FAB1 (Motorized-35%) RXRF-FAA1 (Fixed-35%)

[ ] Designates Metric Conversions

COMMON SUPPLY/RETURN CONCENTRIC AIR DIFFUSER

SUPPLY/RETURN DIFFUSER

NOTE: The location of the combination supply and return diffuser should not exceed 10 feet [3.05 m] above the floor level for units @ 1000 CFM [472 L/s] or less and 12 [3.66 m] to 14 feet [4.27 m] above the floor level for units with CFM greater than 1000 [472 L/s]. If the diffuser is installed with a greater distance than recommended above, the supply air may become stratified above the required comfort area causing uncomfortable conditions.

AIRFLOW/PRESSURE DROP INFORMATION (INCHES W.C. [kPa]) Designed to convert a side by side or an over and under arrangement into a concentric distribution of air. The diffuser is flush mounted, completely insulated, assembled, and internally baffled to provide four way supply air distribution with a center return. To make the assembly complete and ready to fit into a 2' [0.61 m] x 4' [1.22 m] suspended ceiling grid, the diffuser includes adjustable supply louvers, hanging rings, anti-sweat gasket, and round flanges for use with flexible ducts.

Approximate CFM [L/s]-Supply Air 1300 [614] 1575 [743] 1800 [850] 2200 [1038] Plenum & Supply/Return Duct .07 [.017] .10 [.024] .12 [.030] .17 [.042] Diffuser .09 [.022] .13 [.032] .16 [.040] .24 [.060] Economizer .06 [.015] .09 [.022] .11 [.027] .17 [.042] Accessory

SUPPLY AIR/PERFORMANCE Model No. RXRNBD15

Diameter Inches [mm] 16 [406]

Shipping Wt. Lbs. [kg] 90 [40.82]

Diffuser Airflow CFM [L/s] 800 [378]-1200 [566] 1600 [755]-2000 [944]

Dimension A Inches [mm] 201/2 [521]

29

Range of Throw Ft. [m] 14 [4.27]-16 [4.88] 18 [5.49]-28 [8.53]

ACCESSORIES DUCT ADAPTERS RECTANGULAR TO ROUND TRANSITIONS (DOWNFLOW)

RXMC-CA02

RXMC-CA03

[ ] Designates Metric Conversions

30

ACCESSORIES FRESH AIR DAMPER FOR USE ON RQKA-/RQMA- SERIES RXRF-FAA1 (Fixed - 0-35%) The 0-35% manual outside Air Damper is designed to replace the unit return air duct cover. No drilling or damper assembly is required. The amount of outside air (0-35%) is controlled by simply adjusting the side damper. RXRF-FAB1 (Motorized - 0-35%) The 0-35% motorized outside Air Damper is designed to replace the unit return air duct cover. No drilling or damper assembly is required. The control motor opens the adjustable slide damper when the unit blower motor is energized.

ECONOMIZERS RXRE-CAA30 (3 Position) and RXRD-CAM10 (Fully Modulating) for RQKA-/RQMA- Series RXRE-CAA30 (3 Position) Provided with enthalpy control, and mixed air sensor. Settings include fully open, fully closed and adjustable mid point. RXRD-CAM10 (Fully Modulating) Provided with enthalpy control, mixed air sensor and minimum position potentiometer for proportioning (modulating) the amount of fresh air.

[ ] Designates Metric Conversions

31

ACCESSORIES FILTER KIT INSTALLATION RXRY-B01 For use in either vertical or horizontal discharge.

Model No. RQKA-/RQMARQKA-/RQMARQKA-/RQMARQKA-/RQMARQKA-/RQMARQKA-/RQMARQKA-

CFM [L/s] Minimum Nominal Airflow Airflow 510 [241] 600 [283] 680 [321] 800 [378] 850 [401] 1000 [472] 1020 [481] 1200 [566] 1190 [562] 1400 [661] 1275 [602] 1500 [708] 1700 [802] 2000 [944]

Airflow Pressure Drop, Inches W.C. [kPa] CFM [L/s] 1" Filter 2" Filter 500 [236] .02 [.0050] .03 [.0075] 600 [283] .02 [.0050] .03 [.0075] 700 [330] .03 [.0075] .04 [.0010] 800 [378] .04 [.0010] .05 [.0124] 900 [425] .05 [.0124] .06 [.0149] 1000 [472] .07 [.0174] .08 [.0199] 1100 [519] .08 [.0199] .09 [.0224] 1200 [566] .10 [.0249] .12 [.0299] 1300 [614] .13 [.0324] .15 [.0373] 1400 [661] .16 [.0398] .19 [.0473] 1500 [708] .19 [.0473] .21 [.0523] 1600 [755] .20 [.0498] .23 [.0572] 1700 [802] .21 [.0523] .24 [.0598] 1800 [850] .22 [.0548] .25 [.0623] 1900 [897] .24 [.0598] .27 [.0672] 2000 [944] .26 [.0647] .29 [.0722]

Maximum Airflow 660 [311] 880 [415] 1100 [519] 1320 [623] 1540 [727] 1650 [779] 2200 [1039]

[ ] Designates Metric Conversions

32

ACCESSORIES DUCT ADAPTER SIDEFLOW SQUARE TO ROUND TRANSITION RXMC-BA01 Adapts the side rectangular supply and return openings to 14" [356 mm] diameter round openings. Adapters provided with same finish as unit and also provided with thermal insulation.

33

ACCESSORIES RXQG-AAA14 (14" [356 mm] High)

Roofcurb (Sloped) RXQG-AAA14 & RXQG-AAA24 for RQKA- & RQMA- Series Heat pump models must use sloped curbs. Hinged corners make for fast, easy set-up.

RXQG-AAA24 (24" [610 mm] High)

[ ] Designates Metric Conversions

Packaged Heat Pump Roofcurb Installation (Sloped)

34

ACCESSORIES ROOFCURB ADAPTERS Fabricated from galvanized steel to adapt the New cabinet to the old style curb. All are furnished with a New gasket. OLD MODEL PACKAGE HEAT PUMP

OLD CURB MODEL

SMALL CABINET (11/2-2 TON) [5.28-7.03 kW] RPNCRPND-

20 SERIES

RXPA-CA20

MEDIUM CABINET (21/2-3 TON) [8.79-10.55 kW] RPNCRPND-

21 SERIES

RXPA-CA21

EXTRA LARGE CABINET (31/2-5 TON) [12.31-17.58 kW] RPNCRPND-

23 SERIES

RXPA-CA23

NEW MODEL TO OLD MODEL ROOFCURB ADAPTER

NEW MODEL PACKAGE HEAT PUMP

ONLY 1 CABINET SIZE— ALL MODELS RXPX-BACCA20 RXPX-BACCA21 RXPX-BACCA23

(1) SLOPE TYPE (2) FULL PERIMETER TYPE [ ] Designates Metric Conversions

35

RQKARQMA-

ACCESSORIES LIFT KIT—MODEL NO. RXML-A01 The lift kit is intended for temporary installation while the unit is being lifted into position. Kit includes 4 lift brackets.

36

WIRING SCHEMATICS—RQKA/RQMA- SERIES

37

WIRING SCHEMATICS—RQKA/RQMA- SERIES

38

NOTES

39

BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM YOUR RETAILER.

GENERAL TERMS OF LIMITED WARRANTY Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty. For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or Contact the Manufacturer for a Copy.

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

*Condenser Coil and Evaporator Coil leaks caused by factory defects ...........................Five (5) Years *Compressor (1 Phase, 12-SEER models) .......Ten (10) Years *Compressor (3 Phase models) .......................Five (5) Years *Any Other Part ...............................................One (1) Year *All other parts and components carry a limited warranty of five years, provided they are single-phase products installed in a residential application.

RHEEM AIR CONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72908

“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.” PRINTED IN U.S.A.

7-04 DC

FORM NO. P11-751 REV. 1 Supersedes Form No. P11-751