SED2 Variable Frequency Drives With Bypass Options

Submittal Sheet Document No. 154-044 October 13, 2003 SED2 Variable Frequency Drives With Bypass Options Description Bypass Control Features The By...
Author: Harold Sullivan
0 downloads 1 Views 405KB Size
Submittal Sheet Document No. 154-044 October 13, 2003

SED2 Variable Frequency Drives With Bypass Options Description

Bypass Control Features

The Bypass Options are companion packages for the family of SED2 Variable Frequency Drives.



For information on the family of SED2 VFDs, see the SED2 Variable Frequency Drives Submittal Sheet, Document Number 154-042.











Overload protection in bypass mode.



Step-down transformer with fused primary and secondary.



Contactors electrically and mechanically interlocked.



3-Contactor (optional): Input, Output, & Bypass In addition to the 2-contactor features, 3-contactor features provide: −

Drive test function



Complete electrical isolation of drive Disconnect



Fused disconnect (optional)



Circuit breaker (optional)



All doors are interlocked and padlockable



The drive’s programmable relay, typically set to fault, can be set up for applications that run full speed for an extended period of time.

Enable Input



Input Device

Common Remote Start/Stop

Motor

2 Contactor Bypass

Common remote start/stop can be used in both drive and bypass mode.

Essential Services Mode −

Typically used for smoke purge; the motor goes to bypass regardless of the selected mode.



No call to stop will have an effect, including open safety or stop commands.



Only turning the power off or opening this contact will stop the motor.

2-Contactor Units −

Drive-Off-Bypass selector



Bypass pilot light

Input Device

• Drive

Generally used for safety tie-ins; the motor will not operate the drive or bypass when open.

Bypass – Door Mounted Control Devices

Input Device −

Relay logic allows user to send the motor to bypass mode based on the drive’s programmable relay.



2-Contactor: Output & Bypass

VF0302R1







Bypass Power Features •

Auto Bypass

Drive

3-Contactor Units −

Drive-Off-Bypass selector



Bypass pilot light



Drive Test on/off selector

Motor

3 Contactor Bypass

Reactor Options −

Line reactor mounted in bypass option enclosure.



Line reactor (in NEMA 1 enclosure) supplied separately.



Load reactor mounted in bypass option enclosure.



Load reactor (in NEMA 1 enclosure) supplied separately.

http://www.sbt.siemens.com/hvp/drives

Siemens Building Technologies, Inc.

Submittal Sheet Document No. 154-044 October 13, 2003

SED2 Variable Frequency Drives With Bypass Options

Product Numbers

Dimensions

Example shown: VBA340.F120X = VFD with bypass, 480V, 40 hp, fused disconnect, NEMA 1, 2 contactors, and no reactors. Your Product Number: V B

18.0 (457)

= Protective Shield 12.0 (305)

X

Example Product Number: V B A 3 4 0 . F 1 2 0 X Model: VB - VFD with Bypass Series A - Conventional Bypass (Standard) Voltage: 1 = 208V 2 = 230 to 240V 3 = 380 to 480V 4 = 500 to 600V HP Rating: 0.5, 0.7, 1.0, 1.5, 2.0, 3.0, 4.0, 5.0, 7.5, 10., 15., 20., 25., 30., 40., 50., 60., 75., 100, 125 Disconnect: D = Disconnect F = Fused Disconnect NEMA: 1 = NEMA Type 1 Contactors 2 = 2 Contactors 3 = 3 Contactors Reactor 0 = None 3 = Line Reactor * L = Load Reactor * Filter X (Factory Required Designator) Options HA1 = High Amp rating

Depth 11.3 (287)

Depth 9.7 (244) 12.0 (305)

12.0 (305) 36.0 (914)

12.0 (305) 12.0 (305)

Depth 8.3 (211) 36.0 (914)

24.0 (610)

12.0 (305)

49.0 (1245)

36.0 (914)

12.0 (305)

57.5 (1461)

12.0 (305)

12.0 (305)

12.0 (305)

11.0 (279) Frame Size C

11.0 (279) Frame Size A and B

5.5 (140)

18.0 (457)

5.5 (140)

17.0 (432) Frame Size D

45.5 (116)

Depth 11.3 (287) 12.0 (305) 12.0 (305)

48.0 (1219)

66.5 (1689)

57.5 (146)

12.0 (305)

12.0 (305)

VFD0007R3

9.5 (241)

17.0 (432) Frame Size E

Frame Size F

Figure 1. Dimensions in Inches (Cm).

* Only one can be installed in bypass option enclosure. If both are required, a separate enclosed reactor is required.

NOTE:

HA1 option is a bypass package rated to 178 amps at 480 Vac. Though it does not meet NEC for 150 hp of 180 amps, the package will be able to control a high percentage of 150 horsepower motors.

Typical Specifications SED2 Bypass Options shall send the motor to bypass mode based on an easily accessible door-mounted selector or based on the drive’s programmable relay. A bypass pilot light shall provide indication of the bypass mode. The bypass mode shall provide overload protection. Contactors shall be electrically and mechanically interlocked. An essential services mode shall send the motor to bypass regardless of the selected mode.

Page 2

Table 1. Approximate Weights. Frame

Wt. lb (kg)*

A B C D E F

55 (25) 65 (29) 100 (45) 170 (77) 200 (91) 500 (227)

Siemens Building Technologies, Inc.http://www.sbt.siemens.com/hvp/drives

9.5 (241)

Depth 17.4 (44)

SED2 Variable Frequency Drives With E-Bypass Options

Submittal Sheet Document No. 154-051 October 13, 2003

Table 2. SED2 Frame Sizes and Power Ranges.

HP kW 208/230V 480V .5 .75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 HA1

.37 .55 .75 1.1 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 –

A

575V

A

B

C

B C C D E F

N/A

D

D

E

E F

F

N/A

Table 3. Bypass Output Current Ratings (Amps) — Per NEC Motor Tables. HP

.75

1

1.5

7.5

10

15

20

25

30

208V 2.3 230V 2.2

3.0

3.9

5.5

7.4 10.4 16.7

22

28

42

54

68

80

104 130 154

3.0

3.9

5.5

6.8

9.6 15.2

22

28

42

54

68

80

104 130 154



460V 1.1 575V .9

1.6

2.1

3.0

3.4

4.8

7.6

11

14

21

27

34

40

52

65

77

96

124 156 178

1.3

1.4

2.1

2.7

3.9

6.1

9

11

17

22

27

32

41

52

62

77

99

NOTE:

.5

2

3

5

40

50

60

75

100





125 HA1











125



Drives are current rated devices. Verify that the listed ratings are ≥ the motor full load current rating.

Siemens Building Technologies, Inc.

http://www.sbt.siemens.com/hvp/drives

Page 3

Submittal Sheet Document No. 154-044 October 13, 2003

SED2 Variable Frequency Drives With Bypass Options

Wiring Diagrams High Voltage

116

1L1

1L2

FU2

116

T1 TRANSFORMER [H1]

[H2]

[H3]

[H4]

120vac

OL1

5 (96)

4

(95)

4

CUSTOMER SUPPLIED SAFETIES

FU3

1

3

X2

[XF]

[X1]

[X2]

2 13

ESSENTIAL SERVICE 14 ACTIVE

3

ESR

JUMPER

5

1

CUSTOMER REMOTE START

ESR

6

2

ESSENTIAL SERVICE RELAY

(12)

ESSENTIAL SERVICE 12 ENABLED

(8)

11

RR

RUN RELAY

DR

DRIVE RELAY

M1

BYPASS CONTACTOR

VFD1 (CONTROL TERMINALS) 21

5

22

7

OFF DRIVE

BYPASS

5

8 xoo

9

INSTALL JUMPER FOR AUTO 10 BYPASS OPERATION

9

DR

10

INSTALL JUMPER

5 FOR REMOTE 6

10

7

15

RR

12

M2

13

BYPASS OPERATION

oox

ESR

11

DR

16

INSTALL JUMPER FOR LOCAL 8 BYPASS OPERATION

12

A

M1

17

xoo 18

VF0304R1

xoo

BYPASS LIGHT

VFD OUTPUT CONTACTOR M2

M3

VFD INPUT CONTACTOR

DRIVE TEST ON OFF

xo

ONLY SUPPLIED WITH OPTIONAL THREE CONTACTOR BYPASS. (ADDITION OF DRIVE INPUT CONTACTOR)

Figure 2. Bypass 120 Vac Control Circuit.

Page 4

http://www.sbt.siemens.com/hvp/drives

Siemens Building Technologies, Inc.

Bypass Options for SED2 Variable Frequency Drives

Submittal Sheet Document No. 154-044 October 13, 2003

Wiring Diagrams continued

OPTIONAL SUPPLEMENTARY POWER FUSES - MAIN SHORT CIRCUIT PROTECTION BY OTHERS (SEE NOTE 1) DISC1 FU1 1L1 L1 (T1) (L1)

POWER SUPPLY L2 3 PHASE (T2) 60 Hz L3 (T3) GND

M1

2L1

1L2 (L2)

2L2

1L3 (L3)

2L3 OPTIONAL OPTIONAL DRIVE INPUT INPUT LINE CONTACTOR REACTOR M3 3L1 R (2) (1) A1 A2 3L2 S (4) (3) B1 B2

GND GND LUG

3L3 (6) (5)

T C1

OPTIONAL OUTPUT LOAD REACTOR

VFD

L1

U

L2

V

L3

W

U1

U A1

A2

V1

(6)

(3)

(4)

(1)

(2)

M2

B1

B2

C1

C2

OL1

(1) (2)

1T1 (T1)

(3) (4)

1T2 (T2)

(5) (6)

1T3 (T3)

V W

W1

C2

(5)

M

AC MOTOR (CUSTOMER SUPPLIED)

GND 1L1

GND LUG

1L2

VFD0160R1

TO STEP-DOWN CONTROL TRANSFORMER

NOTES:

1. Branch circuit protection to be provided by installer, per UL508A, if not provided with drive. 2. For bypass operation, modify these drive parameters: P0704[0] and P0704[1] = 3, P0748 = Digital Out 1 Reverse ( 3. Control and communication wiring should be 300V UL minimum. 4. Communication wiring should be run with maximum separation possible from all other wiring. 5. Essential service mode operates the motor full speed (bypass) with no protection for the motor or system. 6. Ensure that automatic bypass will not damage the system before activating. 7. Refer to Siemens Publication No. 125-3208 for proper fuse and wire sizes. 8. Refer to Siemens Publication No. 125-3201 for SED2 input/output control signal wiring details. Figure 3. Bypass Power Circuit.

Siemens Building Technologies, Inc.

http://www.sbt.siemens.com/hvp/drives

Page 5

).

Submittal Sheet Document No. 154-044 October 13, 2003

SED2 Variable Frequency Drives With Bypass Options

Wiring Diagrams, continued DRIVE CONTROL TERMINATIONS

ANALOG INPUT EXAMPLES Analog input connection examples

21

23

RL2 NO

22

RL2 COM

RL2 NC

20

RL1 COM

RL1 NO

RL1 NC

Control terminations located on drive I/O module

24

2

3

26

27

28

3

+

4

+

29

-

SPEED POTENTIOMETER

N-

17

P+

DIN6

16

ISO 0VDC

DIN5

15

AO2-

PTC B

14

AO2+

PTC A

AO1+

AO113

2

25

-

12

EXTERNAL 0/4-20mA

EXTERNAL 0-

1

2

3

30

1

2

3

4

5

6

7

8

9

VFD 24VDC POWERED 0/4-20mA DEVICE (POWER CONSUMPTION CANNOT EXCEED 100mA)

AIN2-

AIN2+

DIN4

ISO 24VDC

DIN3

DIN2

DIN1

AIN1-

AIN1+

+0VDC

+10VDC

4.7k Ohm

10

2

3

4

28

11 POWER

108

109

mA

105

9

M2

RR

Control inter-connection between bypass panel

BYPASS CONTROL TERMINATIONS Control terminations located in bypass enclosure CBT-1

1

2

VFD0004R2

CUSTOMER REMOTE START

3

4

CUSTOMER SUPPLIED SAFETIES

5

6

INSTALL JUMPER FOR REMOTE BYPASS OPERATION

7

8

9

INSTALL JUMPER FOR LOCAL BYPASS OPERATION

10

INSTALL JUMPER FOR AUTO BYPASS OPERATION

11

9

ESSENTIAL SERVICE ENABLED

PROVIDE DRY CONTACT

10

11

ESSENTIAL SERVICE ACTIVE PROVIDE DRY CONTACT

Figure 4. Terminations. Table 4. Conventional Bypass Specifications. Specifications

Description 208V, 3AC±10%

Input Voltage (3 phase)

230V, 3AC±10% 460V, 3AC ±10% 575V, 3 AC ±10%

Temperature Humidity

Page 6

Operating: 32°F to 104°F (0°C to 40°C) Storage: –40°F to 158°F (–40°C to 70°C) 0 to 95% rh, non-condensing

Siemens Building Technologies, Inc.http://www.sbt.siemens.com/hvp/drives

Bypass Options for SED2 Variable Frequency Drives

Submittal Sheet Document No. 154-044 October 13, 2003

Table 5. Drive Specifications. Drive Specifications Input voltage and power ranges (3 phase)

Description 200V to 240V, 3AC±10%. 1/2 hp to 60 hp 380V to 480V, 3AC ±10% 1/2 hp to 125 hp 500V to 600V, 3 AC ±10% 1 hp to 125 hp

Input frequency

47 Hz to 63 Hz

Output frequency

0 Hz to 150 Hz

Power factor

≥0.9

VFD degree of efficiency

96% to 97%

Switch-on current

Less than nominal input current

Auxiliary supply 24V

Glavanically separated, unregulated auxiliary supply (18V to 32V) 100 mA

Overload capacity

110% for 60 seconds, 150% for 3 seconds

Control method

Linear, parabolic and programmable V/f; and flux current control low-power mode

PWM frequency

2k Hz to 16k Hz (adjustable in 2k Hz increments)

Fixed frequencies

15 programmable

Skip frequency bands

4 programmable 0.01 Hz digital

Setpoint resolution

0.01 Hz serial 10 bit analog

Digital inputs (sink/source)

6: fully programmable and scalable isolated digital inputs, switchable

Analog inputs

2: 0 to 10 Vdc, 0/4 to 20 mA, can also be configured as digital inputs or Ni 1000 input

Relay outputs

2: configurable 30 Vdc /5A (resistive), 250 Vac 2A (inductive)

Analog outputs

2: programmable (0/4 to 20 mA or 0 Vdc to 10 Vdc)

Serial interface

RS-485; Protocols: USS, P1 and N2; Transmission rate: Up to 38.4k Baud

Protection level Temperature ranges Humidity Operational altitudes

IP20: NEMA Type 1 with protective shield and gland plate installed IP54: NEMA Type 12 Operating: 14°F to 104°F (–10°C to 40°C) Storage: –40°F to 158°F (–40°C to 70°C) 95% rh, non-condensing Up to 3280 ft (1000m) above sea level without derating • Under-voltage • Over-voltage • Overload • Ground fault

Protection features

• Short circuit • Stall prevention • Locked motor • Motor over temperature l2 t, PTC • Over-temperature • Parameter PIN protection

Standards

UL, cUL, CE, C-tick

CE conformity

Conformity with EC Low Voltage Directive 73/23/EEC

Siemens Building Technologies, Inc.

http://www.sbt.siemens.com/hvp/drives

Page 7

Submittal Sheet Document No. 154-044 October 13, 2003

SED2 Variable Frequency Drives With Bypass Options

Table 6. Order Worksheet. Item

Qty.

Designation

Part Number

Description

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners. © 2003 Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. Your feedback is important to us. If you have comments about this Document No. 154-044 1000 Deerfield Parkway document, please send them to [email protected] Printed in the U.S.A Buffalo Grove, IL 60089-4513 Page 8 U.S.A.