RL
with
Merchandisers
INNOVATOR Doors Technical Data Sheet
P/N 0425644_P NSF ® Certified
M K
November 2009
E I H
L J Warning: Terminal block NOT for case-to-case wire connection!
A D
B
F G
We reserve the right to change or revise specifications and product design in connection with any feature of our products. Such changes do not entitle the buyer to corresponding changes, improvements, additions or replacements for equipment previously sold or shipped.
C Item Part #
Description
Wiring Item #
FAN ASSEMBLIES, AND THERMOSTATS A. 12W Standard Fan Assembly (1) 0047000 Fan Motor, Evaporator (MO.4410103) 0461805 Fan Blade (FB.4780446) 12W Optional Energy Efficient Fan Assembly (1) 0477655 Fan Motor, Evaporator (MO.4410546) 0461805 Fan Blade (FB.4780446) B. 0474033 C. D. 0344662 E. 0461814
RELAYS F. 0342598 G. 0342599
Standard Non-adjustable Defrost Thermostat (CT.4440726) Optional Adjustable Refrigeration Thermostat Defrost Limit Thermostat (CT.4440261) Relay Control Thermostat or Fan and Anti-sweat Heater Thermostat (CT.4481296)
(2)
Anti-Sweat Control Relay (120V) (RL.4480238) Fan Control Relay (208V) (RL.4480237)
(6)
(3) (4) (5)
(7)
HEATERS H. Electric Defrost Heaters – Front (208V) (8) 0484312 (1) 1 Door Models (HE.4850632) 0441755 (1) 2 Door Models (HE.4850346) 0441756 (1) 3 Door Models (HE.4850337) 0441757 (1) 4 Door Models (HE.4850347) 0441758 (1) 5 Door Models (HE.4850323)
Item Part #
(Qty)
Description
Wiring Item #
HEATERS (CONTINUED) H. Electric Defrost Heaters — Rear (208V) (8) 0484313 (1) 1 Door Models (HE.4850634) 0463891 (1) 2 Door Models (HE.4850358) 0463892 (1) 3 Door Models (HE.4850359) 0463893 (1) 4 Door Models (HE.4850360) 0463894 (1) 5 Door Models (HE.4850361) I. Drain Pan Heater — (9) Electric & KoolGas (120V) 0489708 (1) 1 Door Models (HE.4850643) 0387036 (1) 2 Door Models (HE.4850239) 0387037 (1) 3 Door Models (HE.4850240) 0387038 (1) 4 Door Models (HE.4850241) 0387039 (1) 5 Door Models (HE.4850242) LAMPS, BALLASTS, LED FIXTURES AND POWER SUPPLY J. 0489698 2 Lamp Ballast (BA.4481596) 0489699 3 Lamp Ballast (BA.4481739) 0424649 Export Ballast (BA.0424649) K. Standard Fluorescent Lamp Replace with like fixtures L. 0499399 M.
LED Power Supply (EP.4481668) LED Fixture Replace with like fixtures
NOTE: For LED lighting parts contact your Hussmann service representative at 1-800-922-1919. Please have your model and serial number available. Refer to I NNOVATOR R EACH -I N G LASS D OOR I NSTALLATION AND S ERVICE manual, P/N 0425683, for Innovator and Innovator II door and frame replacement parts.
NOTE: Revision P updated electrical data, page 4. ©2009 HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-522-1900 • WWW.HUSSMANN.COM
P/N0425644P
Engineering
PHYSICAL DATA
Plan Views
RL - RM - RMF Plan View
Reach-In 1, 2, 3, 4 & 5 Door
1 1/4 3/8 7/8
Merchandiser Drip Pipe (in.) Merchandiser Liquid Line (in.) Merchandiser Suction Line (in.)
06-2009
Dimensions shown as in. & (mm).
A B
41 7
5/8
(1057)
32
Skid/ External Base
6 Bottom Front Support
(152)
48
(178)
(813)
(1219)
5 5/8
34 5/8
(143)
(879)
Waste Outlet Refrig. Outlet
4 (102)
(44)
(1111)
Relay & Terminal Block Location
Front 5-Door Shown
1 3/4
43 3/4
Splashguard
Electrical Wireway
4 1 3/4
(102)
70 1/4 (1784)
(44)
26 1/2 (673)
Clearance for Door Swing
General (A) Case Length (without ends or partitions)
1 Dr
2 Dr
3 Dr
4 Dr
5 Dr
31 1/2 (800)
62 (1575)
92 1/2 (2350)
122 7/8 (3121)
153 3/8 (3896)
(Each end adds 2 in. (51 mm) to length of lineup; each insulated partition adds 1 1/2 in. (38 mm).
Maximum O/S dimension of case back to front
43 3/4 (1111)
43 3/4 (1111)
43 3/4 (1111)
43 3/4 (1111)
43 3/4 (1111)
39 7/8 (1013) 3 3/4 (95) 6 (152) 3 1/8 (79)
39 7/8 (1013) 3 3/4 (95) 6 (152) 3 1/8 (79)
39 7/8 (1013) 3 3/4 (95) 6 (152) 3 1/8 (79)
39 7/8 (1013) 3 3/4 (95) 6 (152) 3 1/8 (79)
39 7/8 (1013) 3 3/4 (95) 6 (152) 3 1/8 (79)
4 (102) 27 1/2 (698) 41 5/8 (1058)
4 (102) 58 (1473) 41 5/8 (1058)
4 (102) 88 1/2 (2248) 41 5/8 (1058)
4 (102) 118 7/8 (3019) 41 5/8 (1058)
4 (102) 149 3/8 (3794) 41 5/8 (1058)
Waste Outlet (B) Right end of case to center of waste outlet Back O/S of case to center of waste outlet
15 3/4 (400) 34 5/8 (879)
23 7/8 (606) 34 5/8 (879)
54 1/4 (1378) 34 5/8 (879)
46 1/4 (1175) 34 5/8 (879)
76 5/8 (1946) 34 5/8 (879)
Water Seal Edge of water seal to center of waste outlet Schedule 40 PVC drip pipe
13 (330) 1 1/4 (32)
13 (330) 1 1/4 (32)
13 (330) 1 1/4 (32)
13 (330) 1 1/4 (32)
13 (330) 1 1/4 (32)
5 3/8 (137) 32 (813) 6 3/4 (170) 24 (610)
5 3/8 (137) 32 (813) 6 3/4 (170) 24 (610)
5 3/8 (137) 32 (813) 6 3/4 (170) 24 (610)
5 3/8 (137) 32 (813) 6 3/4 (170) 24 (610)
(Includes bumper. Add 26 1/2 in. (673 mm) for door swing.)
Back of case to rear of splashguard Width of Skidrail Width of Bottom Front Support Stub-up area between front support and splashguard Electrical Service RH end of case to the center of nearest knockout RH end of case to the center of LH knockout Back O/S of case to center of knockout * NOTE: Electrical Field Wiring Connection Point is at terminal.
** NOTE: Field installed water seal outlets, tees, and connectors are shipped with case
Refrigeration Outlet RH end of case to center of RH refrigeration outlet Back O/S of case to center of refrigeration outlet Outside bottom front supports from end of case Center bottom front support from Centerline
5 3/8 (137) 32 (813) 6 3/4 (170) NA
Distance between Center and Outside supports will vary
2 of 7
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
RL with Innovator Doors Technical Data Sheet
Reach-in 2, 3, 4 and 5 Door Models
RL
Impact With INNOVATOR Doors Frozen Food & Ice Cream
Dimensions shown as in. & (mm).
REFRIGERATION DATA Note: This data is based on store temperature and humidity that does not exceed 75°F and 55% R.H. 41 (1041)
2 1/8
2 5/8
(54)
(67)
83 (2108)
82 1/4 (2089)
2, 3, 4, 5 Door 1 Door FF IC FF IC Discharge Air (°F) –5 –12 2 –5 Evaporator (°F) –11 –19 –11 –19 Unit Sizing (°F) –14 –22 –14 –22 Btu/hr/Door* Parallel 1300 1370 1390 1470 Conventional 1325 1400 1420 1590 *Optional LED lighting reduces refrigeration load by 100 Btu/hr/Door. Optional Energy Efficient Fan motors reduce refrigeration load by 109 Btu/hr/Door.
62 1/2
67
(1588)
(1702) Frame
DEFROST DATA ALL FF IC Frequency (hr) 24 24 Defrost Water (lb/Dr/day) 1.2 1.2 (± 15% based on case configuration and product loading.)
65 1/2 (1664) Door
ELECTRIC 22
Shelf
Temp Term (°F) Failsafe (minutes)
(559)
FF 48° 45
IC 48° 45
20
20
GAS Duration (minutes)
27 7/8 (708) Refrigeration Outlet
OFFTIME
Fan
13 1/8
Coil
CONVENTIONAL CONTROLS
(333) Frame
6 1/4
4 3/4
(159)
(121)
3
1/2
(89)
32 (813) 34 5/8 (879) 41 7/8 (1064) 43 3/4 (1111)
Not Recommended
Low Pressure Backup Control FF CI/CO (Temp °F)** –18°/ –34°
Indoor Unit Only, Pressure Defrost Termination (Temp °F)** Not Recommended **Use a Temperature Pressure Chart to determine PSIG conversions. Estimated Charge (lb)*** 1Dr 0.9 4Dr 2Dr 1.8 5Dr 3Dr 2.7
NSF Certification This merchandiser model is manufactured to meet ANSI/NSF (National Sanitation Foundation) Standard #7 requirements for construction, materials & cleanability.
P/N 0425644_P
IC – 26°/ –45°
3.6 4.6
***This is an average for all refrigerant types. Actual refrigerant charge may vary by approximately half a pound.
Length Added to Lineup by each Standard End (in.) Optional End with Window (in.) Optional Partition (in.)
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM
2 1 1/2 1 1/2
3 of 7
RL
Hussmann recommends against frame heater cycling with Innovator doors to prevent door seals from freezing to the frames and tearing.
Impact With INNOVATOR Doors Frozen Food & Ice Cream
Electrical Data Number of Fans—12W
1
2
3
4
5
Merchandiser
1Dr
2Dr
Amperes 3Dr
4Dr
5Dr
1Dr
2Dr
Watts 3Dr
4Dr
5Dr
Evaporator Fan 120V 60Hz Standard 120V 50Hz Standard 220V 60Hz Export 220V 50Hz Export 120V 60Hz Energy Efficient 220V 60Hz Energy Efficient
0.65 0.75 NA NA 0.30 NA
1.30 1.50 0.66 0.76 0.60 0.30
1.95 2.25 0.99 1.14 0.90 0.45
2.60 3.00 1.32 1.52 1.20 0.60
3.25 3.75 1.65 1.90 1.50 0.75
50 57 NA NA 18 NA
100 114 100 114 36 36
150 171 150 171 54 54
200 228 200 228 72 72
250 285 250 285 90 90
Door Anti-sweat Heaters (on fan circuit) 120V 50/60Hz Standard 220V 50/60Hz Export
0.77 NA
1.54 0.84
2.31 1.26
3.08 1.68
3.86 2.10
92 NA
185 185
278 278
370 370
463 463
Frame Anti-sweat Heaters (on fan circuit) 120V 50/60Hz Standard 220V 50/60Hz Export
0.39 NA
0.78 0.43
1.18 0.64
1.57 0.85
1.97 1.07
47 NA
94 94
141 141
188 188
236 236
Minimum Circuit Ampacity 120V 60Hz Standard 120V 50Hz Standard 220V 60Hz Export 220V 50Hz Export 120V 60Hz Energy Efficient 220V 60Hz Energy Efficient
3.01 3.01 NA NA NA NA
3.82 4.02 2.13 2.23 3.12 1.77
5.64 5.94 3.09 3.24 4.59 2.55
7.45 7.85 4.05 4.25 6.05 3.33
9.28 9.78 5.02 5.27 7.53 4.12
20 15
20 15
20 15
20 15
20 15
1.67 NA
0.63 0.34
1.25 0.76
2.00 1.22
2.57 1.53
200 NA
75 84
150 168
240 269
300 336
2.88 NA
6.72 7.11
10.08 10.66
13.46 14.24
16.82 17.79
600 NA
1400 1564
2100 2345
2800 3133
3500 3914
Standard Vertical Lighting 1Dr Innovator* Doors (120V) 1.00 (Export: 220V 50 hz) NA Optional LED Lighting Hussmann EcoShine™ [27 W] (120V) 0.23 Hussmann EcoShine™ [27 W] [220V Export)] 0.12 Hussmann EcoShine™ EP [16 W] (120V) 0.13 Hussmann EcoShine™ EP [16 W] [220V Exp)]0.07 Hussmann EcoShine™ [20 W] (120V) 0.17 Hussmann EcoShine™ [20 W] [220V Export)] 0.08 0.24 Gelcore (120V) 0.13 Gelcore (120V) [220V (Export)]
2Dr 1.50 0.84
3Dr 2.00 1.12
4Dr 2.50 1.40
5Dr 3.00 1.68
1Dr 120 NA
2Dr 180 185
3Dr 240 246
4Dr 300 308
5Dr 360 370
0.45 0.25 0.27 0.15 0.33 0.17 0.48 0.26
0.68 0.37 0.40 0.22 0.50 0.25 0.73 0.40
0.90 0.49 0.53 0.29 0.67 0.33 0.97 0.53
1.13 0.61 0.67 0.36 0.83 0.42 1.21 0.66
27 27 16 16 20 20 29 29
54 54 32 32 40 40 58 58
81 81 48 48 60 60 87 87
108 108 64 64 80 80 116 116
135 135 80 80 100 100 145 145
Maximum Over Current Protection 120V Maximum Over Current Protection 220V Defrost Drain Heaters (120V) (Export: 220V 50 hz) 208V Electric Defrost (Export: 220V 50 hz)
* Innovator or Innovator II
4 of 7
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
RL with Innovator Doors Technical Data Sheet
RL
Impact With INNOVATOR Doors Frozen Food & Ice Cream
Product Data Recommended Usable Cube 1 (Cu Ft/Dr) ARI Total Display Area 2 (Sq Ft/Dr) Shelf Area 3 (Sq Ft/Dr) 1
23.46 ft3 /Dr (0.66 m3 /Dr) 13.31 ft2 /Dr (1.24 m2 /Dr) 29.32 ft2 /Dr (2.72 m2 /Dr)
ARI Refrigerated Volume less shelving and other unusable space: Refrigerated Volume/Unit of Length, ft3/ft [m3/m] Computed using ARI 1200 standard methodology: Total Display Area, ft2 [m2]/Unit of Length, ft [m] Shelf surface area is composed of bottom deck plus standard shelf complement, as shown in the Hussmann Product Reference Guide. The standard shelf complement for this model is (5) rows of 22-inch shelves.
2 3
ESTIMATED SHIPPING WEIGHT 4 Case lb (kg) 4
Solid End 1 Dr
2 Dr
3 Dr
4 Dr
5 Dr
(each)
617 (280)
997 (453)
1295 (589)
1595 (725)
1874 (852)
55 (25)
Actual weights will vary according to optional kits included.
P/N 0425644_P
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM
5 of 7
Low Temperature CIRCLED NUMBERS = PARTS LIST ITEM NUMBERS R = Red P = Purple 2P = Purple (2 Bands) DB = Dark Blue BL = Black LB = Light Blue BR =Brown Y =Yellow OR = Orange W = White THESE ARE MARKER COLORS (WIRE MAY VARY.)
208V
208V
Evaporator Fan 7 Relay Coil
1
R
2
R
1 Rear Defrost Heater
4
R
8
8
R
Front Defrost Heater
3
3
C
circuit load, then additional supplemental overcurrent protection may be required per NEC Articles 210 and 240.
8
7
R
R
Defrost Limit 4
6
BK
14
BK
Fan Relay 7 F N.C. Fan Relay 7 F N.O.
Rod Heater (Drain)
A.S. Relay Coil
5
3 C.O.R. COM
BK
N.C.
25
c
W
24
6
1
10
BK
Frame A.S. Heaters
11
P
Switch
P
22
2P
21
Door A.S. Heaters
OR
OR
DB
Y
Defrost Termination Thermostat
Refer to Innovator Reach-In Glass Door, Installation and Service manual, P/N 0425683, for Innovator door and frame replacement parts.
6
NEUTRAL
FIELD WIRED
26
9
Y
BK
120V POWER
17
BR
COM
A.S. Relay A.S.
13
NEUTRAL
1
Evaporator Fans
Relay Control
16
5
BK O.O.R.
N.C.
120V POWER
CAUTION: When multiplexing merchandisers equipped with defrost heaters, if branch circuit overcurrent protection is larger than the
12
20
2P
Defrost Termination Thermostat
Refrigeration Thermostat (Optional)
2 DB
C.O.R.
Terminal Blocks in Raceway
Low Temperature with Electric Defrost R
R
R
R
1
2
3
4
BK BK 5
6
2
R
R
BK P
7
8
10
2P
11 12
Permanent Internal Removable External Jumpers DEFROST HEATERS Jumpers (208V)
BK BK BK OR OR 2P 13
14 16
FANS & A.S. (120V)
17
20
21
3
Pink P
W
Y BR
22
24
25
LIGHTS
LIGHTS
(120V)
(Neutral)
26
}
To Condensing Unit
Dark Blue
FANS & A.S. (Neutral)
Electric Defrost Sequence - Low Temperature 1.
Power from the defrost contactor energizes Defrost Heaters and 208V Evaporator Fan Relay Coil (7). Relay Contacts open the fan circuit and energizes the Drain Pan Heater.
2.
If the Defrost Heater raises internal air temperature above 90°F, the Defrost Limit Thermostat (4) will open.
3.
Temperature rise of the evaporator closes the Relay Control Thermostat (5) at about 35°F, energizing 120V A.S. Relay Coil (6). This relay’s contacts open the Frame and Door Heater Circuits.
4.
When Defrost Termination Thermostat ends defrost period, the defrost contactor opens the Defrost Heater and Evaporator Fan Relay Coil Circuits. The Drain Pan Heater goes off and fans are on.
5.
Temperature fall of the evaporator opens the Relay Control Thermostat (5) at about 20°F, de-energizing 120V A.S. Relay Coil (6). A.S. Relay Contacts close the Frame and Door Heater Circuits.
6 of 7
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
RL with Innovator Doors Technical Data Sheet
Low Temperature CIRCLED NUMBERS = PARTS LIST ITEM NUMBERS R = Red P = Purple 2P = Purple (2 Bands) DB = Dark Blue BL = Black LB = Light Blue BR =Brown Y =Yellow OR = Orange W = White THESE ARE MARKER COLORS (WIRE MAY VARY.)
NEUTRAL 120V POWER
14
BK
Fan Relay 7 F N.C. COM
Fan Relay 7 F N.O.
Defrost Limit Y
4
O.O.R.
BK
BK
A.S. Relay Coil
5
c c
C.O.R.
6
A.S. Relay A.S.
13
9
Rod Heater (Drain)
3
COM
26
BR
Relay Control
16
1
Evaporator Fans
N.C.
BK
Y
25
W
24
Refer to Innovator Reach-In Glass Door, Installation and Service manual, P/N 0425683, for Innovator door and frame replacement parts.
6
1
Fan Relay 7 Coil
10
Frame A.S. Heaters
11
P
12
2P
P
22
2P
21
Door A.S. Heaters
NEUTRAL
120V POWER Switch
17
OR
20
OR
Refrigeration Thermostat (Optional)
Terminal Blocks in Raceway
Low Temperature with Gas Defrost BK 10
Removable External Jumpers
P
2P BK BK BK OR OR 2P
11 12
13
14
FANS & A.S. (120V)
16
17
20
21
P
W
Y BR
22
24
25
LIGHTS
LIGHTS
(120V)
(Neutral)
3
}
Pink
To Condensing Unit
26
FANS & A.S. (Neutral)
Permanent Internal Jumpers
Gas Defrost Sequence - Low Temperature 1.
Defrost vapor enters evaporator causing a rise in temperature. At about 35°F the Control Relay Thermostat (5) closes the Fan Relay Coil (7) and Control Relay Coil (6) circuit. The Coil opens the Fan, Door Heater, and Frame Heater circuits, while energizing the Drain Pan Heater (9).
2.
If the Drain Pan Heater (9) raises internal air temperature above 90°F, the Heater Limit Thermostat (4) will open.
3.
When the defrost timer ends a defrost period, the evaporator temperature will start to fall. At about 20°F, the Control Relay Thermostat will open, de-energizing the Control Relay Coil and Fan Relay Coil (7). Control and Fan Relay’s will open the Drain Pan Heater circuits, and will close the Fan, Door Heater, and Frame Heater circuits.
P/N 0425644_P
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM