REGULATOR SIZING

- 107 -

DEFINITIONS RELATING TO REGULATOR CAPACITY The capacities contained in this bulletin are based on a specific level of performance by the regulator. The measure of performance is accuracy of regulation, also known as offset or deviation. Each table is appended with a footnote indicating the accuracy of regulation obtainable at the rated capacities listed. Pertinent terms involved in the determination of accuracy of regulation and rated capacity are defined as follows: * REGULATED VARIABLE is the controlled condition of the fluid either (1) flowing through a regulator or (2) in a process served by a regulator. Reduced pressure, back pressure and differential pressure are the typical regulated variables to be dealt with in this instance. Other cases, such as vapor pressure produced by a steam-heated vapor generator, will be found. * MINIMUM CONTROLLED FLOW is the lowest flow at which a steady condition of fluid pressure can be maintained. Any further reduction of flow produces a noticeable deviation of the regulated pressure toward dead-end shut off. For convenience,

minimum controlled flow is often considered as being at 5% of rated capacity. * SET POINT is the value of the regulated pressure at minimum controlled flow. * RATED CAPACITY of a pressure regulator pertains to specified inlet and outlet conditions and is the rate of flow through the regulator, guaranteed by the manufacturer, when the regulated pressure deviates no more than a specified number of psi from the set pressure at minimum controlled flow. * ACCURACY OF REGULATION is the amount by which the regulated pressure deviates from set point at minimum controlled flow as the flow through the regulator is gradually increased from minimum to rated capacity. * LOCK-UP is the increase from set value due to dead end shut-off. * Adapted from “Definitions of Regulator Capacities”, Standard No. FCI 58-1, published by Fluid Controls Institute, Inc.

REDUCED PRESSURE - psi

50

TYPICAL REGULATION CURVE SPENCE TYPE ED INLET PRESSURE 100 psi

40

30

20

10

0 0

10

20

30

40

50

70

60

80

90

100

110

FLOW - PERCENT

TYPICAL REGULATION CURVE The performance characteristic of a Spence Pressure Regulator is shown above. Using this curve to illustrate several terms of reference, the following facts are evident: REGULATED VARIABLE

REDUCED PRESSURE

Minimum Controlled Flow…………………………4% Set Point …………………………………………25.0 Reduced Pressure at Rated (100%) Flow …22.5 psi Accuracy of Regulation, psi …………………2.5 psi Accuracy of Regulation, % of set pressure ……10%

The slight slope of the curve establishes a definite relationship between flow and regulated pressure. Note that 1 psi accuracy of regulation is obtainable at 95% of rated flow. For back pressure regulation, or differential where the regulator opens on increasing differential, the characteristic curve would lie opposite to that shown. It would slope upward with flow increase because a positive deviation is required to cancel valve opening.

NOTES

ON

USE

OF

TABLES

The lowest reduced pressures are approximate critical pressures. No appreciable increase in flow can be obtained at lower pressures. Downstream pipe size should be enlarged at regulator outlet to approximately equalize pipe velocities before and after the reduction. The Steam Capacity Tables are useful for determining steam pipe sizes and regulator size at any desired lower velocity level. Reduced Seats—Spence Regulators are available with a choice of seat sizes called Full and Normal Ports. There is a capacity table for each port with standard plugs. The Cv Valve Coefficients shown on the back page, indicate where 75% and 50% parabolic plugs are available. For a given pressure drop, rated flows with various ports and plugs in the same size body may be compared. Thus, valve and port size may be selected to limit velocities entering and leaving the regulator. Lower velocities mean a greater proportion of the pressure drop occurs at the valve seat, where it belongs, rather than in the body outlet and connected piping. Capacity ratings apply to Spence Regulators with Type D, N and Q Pilots which are spring loaded and have 31/2 inch diaphragms. Other pilots having greater or lesser sensitivity will provide proportionally greater or less accuracy of regulation.

PLANNING MAIN VALVE INSTALLATION A. PLANNING THE INSTALLATION 1. Locate the valve in a straight run of horizontal pipe. See Fig. 1. 2. Allow headroom above the valve for access through the blind flange. Provide clearance for stem withdrawal underneath. 3. Prevent water hammer and erratic operation by installing traps to provide proper drainage before and after the valve, and before secondary PRV or control valve. 4. Avoid damaging affects of scale and dirt in pipe lines by using a strainer as shown in Fig. 1 . 5. Provide a 3-valve by-pass to facilitate inspection without interrupting service. 6. To eliminate excessive noise and erratic regulation with steam and other compressible fluids enlarge the delivery pipe size to effect a reasonable flow velocity at the reduced pressure. A tapered transition is recommended. If possible, avoid a sharp turn close to the regulator outlet and a bullheaded tee connection to the low pressure main. 7. Install initial and delivery pressure gauges to indicate performance. If the pressure rating of the delivery system or connected equipment is less than the initial steam pressure, provide a safety valve. B. CONTROL PIPE 1. Use 1/4” pipe for this line which connects the pilot diaphragm chamber to the desired point of pressure control. See Fig. 1. 2. Take the control at a point of minimum turbulence. Avoid control immediately at the valve outlet or after a turn. When the delivery pipe expands in size select a spot at least 4 pipe diameters beyond the point of enlargement. 3. Pitch away from pilot to avoid erratic operation and fouling. Eliminate water pockets. 4. Locate delivery pressure gauge in control pipe to show pressure actually reaching pilot diaphragm.

1. 2. 3. 4. 5. 6.

Inlet Pipe Isolation Valve Strainer PRV Type Bypass Pipe Bypass Valve

C. DESIGN GUIDELINES TO MINIMIZE NOISE 1. Size the regulator to provide a maximum inlet velocity of about 10,000 FPM. 2. Determine the regulator outlet velocity. if it would exceed 30,000 FPM, use a Spence muffling orifice or a second stage regulator. 3 Expand regulator outlet piping to limit discharge line velocity to about 10,000 FPM. 4. Avoid abrupt changes in pipe size. Limit pipe diameter changes to two pipe sizes per stage of expansion. Do not use eccentric reducers. 5. Directional changes in downstream piping should be made only after the line size has been increased. Use long radius fittings; avoid bull-head tee connection. 6. Provide as much straight run of pipe on both sides of regulator as possible: a - 10 pipe diameters minimum to the inlet. b - 20 pipe diameters minimum of expanded line size from the outlet. 7. Size all piping components, including strainer and stop valves for a maximum flow velocity of about 10,000 FPM (Exception: An outlet stop valve mounted at the regulator outlet should be equal in size to the regulator). In areas where low sound levels are specified, reduce this limit by 25% to 50%. 8. To limit noise transmission through the building’s structure. keep the regulator and piping at least 3 feet away from solid surfaces. Use sound-isolating piping supports. 9. Apply high density insulation to the regulator body, piping and system components. Insulation reduces heat loss significantly and can provide moderate (3-6 dB) local noise attenuation. 10. Use a Spence noise suppressor to reduce the propagation of noise via the downstream piping.

7. Delivery Pipe 8. SRV Type 9. Drip Pan Elbow 10. Vent Stack 11. Low Pressure Trap 12. High Pressure Trap 10

Provide as much straight run of pipe on both sides of regulator as possible: ● 10 pipe diameters minimum to the inlet. ● 20 pipe diameters minimum of expanded line size from the outlet.

8

9 1 6

5

10 d1

2

4

2 7

20 d2

d1

d2

3

Min. 4 d2

11 12

RULES FOR MAIN VALVE SELECTION When you select a Main Valve, your sizing can be based on one of three methods. They are:

ECONOMICAL MAIN VALVE Economical Main Valve Selection is choosing a regulator that has the line size and rough capacity to handle the load. No consideration is given to velocities or noise. If you are interested in an economical selection, select a regulator type for your application, then go to the Capacity Tables and select the size that will provide you with the capacity needed.

ENGINEERED MAIN VALVE Engineered Main Valve Selection takes into consideration the inlet and outlet velocities of the regulator, It will limit these velocities to acceptable standards. See Pressure Reducing Station Design Guidelines on the following pages for details. If you are interested in an engineered selection, select a regulator

RULES

FOR

type for your application, and then to the Capacity Tables and select the size that will provide you with the capacity needed. Verify that the velocities fall within the guidelines by consulting the Velocity Charts in this Section.

ENGINEERED MAIN VALVE WITH NOISE SUPPRESSION Engineered Main Valve Selection with Noise Suppression considers both velocity and noise suppression in the selection of the regulator. For this selection, it is recommended that you contact your local Spence Technical Sales Representative who can provide you with a computer generated solution.

SELECTING A REGULATOR TYPE The following rules should be used to help you to determine the type of regulator that you should use. You should consult the Product Pages, Velocity Tables and Capacity Tables for additional information on your selection.

MAIN VALVE SELECTION–STEAM SERVICE

Together with the following rules, reference should be made to the Main Valve Specification Table or individual Product Pages for maximum initial pressures and temperatures and “minimum differentials”for the several types of Main Valve. For pressure reduction where fast response time is important, but capacity and accuracy are not critical, select D50 DIRECT OPERATED REGULATOR.

EITHER DEAD-END OR CONTINUOUS FLOW SERVICE RULE 1. For Initial Pressures exceeding 15 psi: (a) TYPE E – Select when the Delivery Pressure is less than 75% of Initial Pressure. For Differential Pressures of 15-50 psi, specify optional LP Spring (10 psi minimum Differential Pressure is attainable by adding optional fittings).

RULES

FOR

(b) TYPE E5 – Select when the Delivery Pressure is 75% to 96%of Initial Pressure. RULE 2. For Initial Pressures less than 15 psi: (a) TYPE E2 – Select when Initial Pressure is less than 15 psi.

MAIN VALVE SELECTION–AIR SERVICE

Together with the following rules, reference should be made to the Main Valve Specification Table or individual Product Pages for maximum initial pressures and temperatures and “minimum differentials”for the several types of Main Valve.For pressure reduction where fast response time is important, but capacity and accuracy are not critical, select D50 DIRECT OPERATED REGULATOR.

EITHER DEAD-END OR CONTINUOUS FLOW SERVICE RULE 1. For Initial Pressures exceeding 15 psi: (a) TYPE E – Select when the Delivery Pressure is less than 75% of Initial Pressure. For Differential Pressures of 15-50 psi, specify optional LP Spring (10 psi minimum Differential Pressure is attainable by adding optional fittings).

RULES

FOR

(b) TYPE E6 – Select when the Delivery Pressure is 75% to 93%of Initial Pressure. (c) TYPE E5 – Select when the Delivery Pressure is 93% to 96%of Initial Pressure. RULE 2. For Initial Pressures less than 15 psi: (a) TYPE E2 – Select when Initial Pressure is less than 15 psi.

MAIN VALVE SELECTION–WATER SERVICE

Pilot Operated Regulators are not uniformly successful in liquid pressure reducing service unless the delivery system has unusual cushioning such as afforded by an elevated tank or large air chamber.

WATER PRESSURE REDUCING VALVES The TYPE D34 DIRECT OPERATED VALVE was developed for application on rapidly changing and intermittent flow to an inflexible system. RULE 1. Select TYPE D34 DIRECT OPERATED VALVE for pressure reducing service.

FOR PILOT OPERATED WATER REGULATORS When a pilot operated regulator is required the following rules for the selection of a main valve govern: RULE 2. When pressure drop across valve exceeds 10 psi: (a) TYPE C34 -Select for all normal requirements.

(b) TYPE E6 with Dashpot-Select where high lift is desired or special flow requirements encountered. RULE 3. When pressure drop across valve is between 5 and 10 psi: (a) TYPE E5 - Select for pressure drops not less than 5 psi. (b) TYPE E6 with Dashpot-Select if auxiliary operation is possible. Together with the above rules, reference should be made to the Main Valve Specification Table for maximum initial pressures and temperatures and “minimum differentials” for the several types of Main Valves.

VALVE SIZING BY COMPUTATION FORMULA KEY A Cv EDR F ft G ∆P P1 P2 Pc

= = = = = = = = = =

∆PS =

Area of Pipe in (inches)2 Valve Coefficient Equivalent Direct Radiation (Sq. Ft.) Pipe Area Factor (see Pipe Factors Table) Feet Specific Gravity Pressure Drop,P1 – P2 psi Inlet Pressure, psia (psi + 14.7) Reduced Pressure, psia (psi + 14.7) Pressure at Thermodynamic Critical Point, psia (water = 3206 psia)

P1 – Pv when P2 > Pv

P ) P when P < P √ P q = Liquid Flow Rate, U.S. gpm

∆PS = P1 – (.96 – .28

v

C

v

2

v

Q = Flow Rate, SCFH T = Absolute T (T + 460)°R TSH = Steam Superheat (°F) = Total Steam Temp. – Saturated Steam Temp. v V W Ws

Pv = Vapor Pressure, psia

= = = =

Specific Volume FT3/# Velocity, FPM Steam Flow, #/Hr. Flow, #/Hr. Superheated Steam

To avoid interpolation or solve problems beyond the scope of the table, valve sizes may be determined by calculation as follows:

Cv

LOADS

SUBCRITICAL SATURATED STEAM:

CRITICAL

P2 > .58 P1 W Cv= 2.1 √∆P (P1 + P2)

P2 < .58 P1 W 1.71 P1

Cv=

P2 > .55 P1 SUPERHEATED STEAM: Cv= W (1 + .0007TSH) P2 > .5 P1 Q Cv= 963

√∆P (PGT P ) 1+

2

Cv=

q

ABSORPTION W = 16-20 #/Hr./Ton-Hr. STM. ATOM

Cv=

.93q

W = 0.1 #/Hr./#Oil

VELOCITY

P2 < P1 – .85 ∆PS

√∆PG

RADIATION

Q √GT 834 P1

Cv=

P2 > P1 – .85 ∆PS

LIQUID:

AIR

P2 < .5 P1

GPM X Temp. Rise (°F) 2 GPM W= X Temp. Rise (°F) 4 W = CFM X Temp. Rise (°F) 900 2 f EDR W= 4 W=

FUEL OIL

P2 < .55 P1 W (1 + .0007TSH) Cv= 1.75 P1

2.1 √∆P (P1 + P2)

GAS:

WATER

√∆PG

STEAM

V = 2.4

Wv A

S

PIPE FACTORS FOR STANDARD (SCHEDULE 40) PIPE SIZE

FLOW STEAM

1

W = .0433 x V x F

v

AIR & GASES Q = .0259 x V x F x P1 T LIQUIDS

q = .0054 x V x F

/8 / 3/8 1 /2 3/4 1 11/4 11/2 2 21/2 3 14

FACTOR

SIZE

FACTOR

.55 1.0 1.8 2.9 5.1 8.3 14 20 32 46 71

1

95 122 192 278 481 758 1076 1301 1699 2151 2673

3 /2 4 5 6 8 10 12 14 16 18 20

PRESSURE REDUCING STATION DESIGN GUIDELINES I. SINGLE STAGE PRESSURE REGULATOR

A. When intermediate steam pressure is required.

1. When to use single stage regulator:

B. When concerned with PRV generated noise, use two stage station when specific volume ratio, outlet to inlet, is greater than 3 to 1, unless manufacturer offers assurance or other means of meeting noise specification.

A. When load turndown requirement is generally no greater than 10:1. B. When ratio of specific volume of steam, outlet to inlet, is no greater than 3 to 1. C. When only one reduced steam pressure level is required.

II. PARALLEL PRESSURE REGULATORS 1. When to use parallel pressure regulator stations: A. When maximum specified capacity requires selection of a pressure regulator greater than 12 inch pipe size. (It may be more economical to install two smaller valves than one very large one.) B. When normal conditions require operation at 10% or less of specified maximum capacity for sustained periods.

C. When complying with Power Piping Code ANSI B31.11986, which reads, in part, “in district heating and steam distribution systems where the steam pressure does not exceed 400 psi (2758 kPa) and where the use of relief valves and vent piping are not feasible, two or more pressure reducing valves may be installed in series, each set at or below the safe working pressure of equipment served and no relief valve is required.”

IV. TWO STAGE PARALLEL PRESSURE REGULATORS† 1. Whenever any condition from II and any condition from III applies.

SPACE CONSIDERATIONS FOR REDUCING STATIONS

C. When there are two distinct load requirements; i.e., summer/winter operation.

1. Following are rules of thumb for approximating space requirements for installing reducing stations:

2. When to use a pneumatically operated parallel pressure regulator station:

A. Single stage (with or without noise suppressors)

A. When the combined accuracy of regulation of mechanically operated controls is unacceptable. For Spence mechanically operated regulators normal sizing/selection results in accuracy of regulation of approximately 5% of set pressure. Combined accuracy of regulation of mechanically operated parallel installed regulators is approximately 10% of set pressure. Pneumatically operated regulators equipped with reset maintain set point within 1% for all sustained flows.

Inlet side: ten (10) diameters of PRV pipe size Outlet side: twenty (20) diameters of final pipe size, where final pipe size is determined on the basis of 10,000 fpm line velocity. B. Two stage Inlet side of primary: ten (10) diameters of PRV pipe size. Intermediate: twenty (20) diameters of secondary PRV pipe size.

III. TWO STAGE PRESSURE REGULATORS†

Outlet side: twenty (20) diameters of final pipe size, where final pipe size is determined on the basis of 10,000 fpm line velocity.

1. When to use two stage pressure regulator stations:

C. Two stage with muffling orifice; same as A above.

† Primary PRV requires optional base bypass and 1/8" bleedport.

PRESSURE REDUCING STATION GENERAL SPECIFICATION A.Pressure Reducing Station shall consist of: -

pressure regulator inlet strainer inlet and outlet stop valves (gate type) by-pass valve (globe type) trap at inlet to pressure regulator pressure gauges on inlet and outlet of station pressure relief valve downstream of regulator

B.Stop valves and strainer shall be at least pressure regulator size C.Expand pressure regulator outlet pipe size to obtain discharge line velocity which will not exceed: Up to and including 2” 2 1/2” up to 8” Above 8”

15,000 FPM 10,000 FPM 8,000 FPM

Regulator outlet velocity shall be limited to: Up to and including 2” 2 1/ 2” up to 8” Above 8”

45,000 FPM 30,000 FPM 24,000 FPM

D.Unions shall be used on either side of screwed end bypass valve and pressure regulator to facilitate removal. E. Pressure regulators 2-1/2” and larger shall have flanged ends and be suitable for pressure and temperature specified. F. Limit pressure regulator inlet velocity to: Up to and including 2” 2 1/2” thru 8” Above 8”

15,000 FPM 10,000 FPM 8,000 FPM

G.Regulator sound pressure level while operating at specified maximum capacity shall not exceed 90 dbA as measured at a point three feet downstream and three feet from uninsulated pipe surface. H.Pressure regulator capacity shall not be greater than 120 of specified maximum capacity. I. For details of safety valve sizing and installation, please refer to the latest National Board Inspection Code and ANSI B31.1 Code.















12

22

39

58

76

125

189

316

38

12

3

/4

1

11/4

11/2

2

21/2

3

4

5

6

8

10

12

474

283

187

114

87

59

33

18

















631

377

249

151

115

78

43

24

17.6

14.6

10.4

7.5

4.8

1.5

.65



557

353

222

124

85

55

37

22

15.5

9.9

7.0

4.4

2.7

1.4



— —



835

530

333

186

127

82

56

33

23.3

14.8

10.6

6.6

4.0

2.1

1113

706

444

248

169

109

74

44

31

19.8

14.1

8.8

5.4

2.8

1.5



Full

1118

748

465

255

202

143

96

68

44

27.4

18.9

11.7

7.6







E2

952

525

366

228

176

120

59

35

25

19.8

13.4

10.0

5.7







1611

1018

665

350

258

159

95

67

43

27.4

18.9

11.7

7.6







Normal Full

E5,E6







196

139

86

53

36

24

17.3

12.5

5.5









C34



























.32

.32

.25

D

The Parabolic Discs given in the above table are designed to: a) Improve performance at minimum flows by improving stability over wide flow ranges. b) Provide easy field conversion to obtain a substantial increase or decrease in regulator Cv to meet system load requirements. c) Facilitate selection of smaller size safety relief valves. d) Size more precisely to the required Cv, thereby eliminating one of the most frequent causes of poor performance.

75% AND 50% REDUCED TRIM (Parabolic)

/

/



/4

1

E Valve Size Normal Normal Normal Full Full 50% 75% 50% 75%

REGULATOR CV DATA







118

84

52

32

21.6

14.4

10.4

7.5

3.3









60%

D34

















10.8

10.1

5.0

4.9

3.3

2.2





D50















60

37.5

20.8

14.3

9.2

5.3







50%

N6

















17.2

15.1

14.3

9.15

6.85

.4-5.22





Series 2000

SATURATED STEAM FLOW TABLE (LB/HR) Based on Schedule 40 Pipe SIZES 1/4" THROUGH 2" VEL., FPM PRESS. (PSIG) -10 -5 0 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150 175 200 250 300

45000

45000

45000

45000

45000

45000

45000

45000

REGULATOR or PIPE SIZE (inches) 1 /4 23 51 73 97 120 142 164 186 208 251 293 336 377 420 461 503 607 710 813 916 1121 1336

3/8 43 93 134 178 220 260 301 341 381 460 538 616 692 770 846 922 1113 1302 1491 1680 2057 2452

1/2 68 148 213 284 350 415 479 543 607 732 857 981 1102 1225 1347 1468 1771 2072 2374 2675 3274 3902

3/4 120 260 373 498 613 728 841 953 1065 1285 1504 1721 1934 2150 2364 2577 3108 3636 4166 4694 5746 6848

1 195 422 605 807 994 1179 1363 1545 1726 2083 2437 2789 3134 3485 3831 4176 5037 5893 6752 7608 9313 11099

11/4 337 730 1046 1396 1720 2041 2359 2673 2987 3605 4217 4827 5424 6031 6630 7228 8718 10198 11685 13166 16118 19209

11/2 458 994 1424 1900 2342 2778 3210 3639 4065 4906 5740 6570 7383 8209 9024 9838 11866 13881 15905 17921 21938 26145

2 755 1638 2348 3132 3860 4579 5292 5998 6700 8087 9461 10829 12170 13531 14874 16216 19558 22879 26216 29539 36160 43094

30000

30000

30000

30000

24000

24000

10 9466 20524 29424 39256 48374 57390 66320 75171 83977 101355 118578 135722 152523 169579 186417 203233 245117 286743 328560 370208 453186 540098

12 13437 29134 41767 55723 68666 81464 94139 106703 119203 143871 168318 192653 216502 240713 264614 288484 347938 407024 466382 525501 643286 766655

SIZES 21/2" THROUGH 12" VEL., FPM PRESS. (PSIG) -10 -5 0 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150 175 200 250 300

30000

30000

REGULATOR or PIPE SIZE (inches)

21/2 718 1558 2233 2979 3671 4356 5033 5705 6373 7692 9000 10301 11576 12870 14148 15424 18603 21763 24936 28097 34395 40991

3 1109 2405 3448 4600 5669 6725 7772 8809 9841 11878 13896 15905 17874 19873 21846 23817 28725 33603 38503 43384 53108 63293

4 1910 4142 5938 7922 9762 11581 13383 15170 16947 20454 23929 27389 30779 34221 37619 41012 49465 57865 66303 74708 91453 108992

5 3002 6509 9331 12449 15341 18200 21032 23839 26632 32143 37605 43042 48370 53779 59119 64452 77735 90936 104197 117405 143720 171283

6 4335 9399 13475 17978 22154 26283 30372 34426 38459 46418 54305 62156 69851 77662 85373 93074 112256 131319 150470 169544 207545 247348

8 7507 16276 23334 31131 38362 45512 52594 59613 66596 80378 94036 107631 120955 134481 147834 161169 194385 227395 260557 293586 359389 428313

SATURATED STEAM FLOW TABLE (LB/HR) Based on Schedule 40 Pipe SIZES 3/8" THROUGH 4" VEL., FPM PRESS. (PSIG) -10 -5 0 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150 175 200 250 300 400 500 600

15000

15000

15000

15000

15000

15000

15000

10000

10000

10000

REGULATOR or PIPE SIZE (inches) 3/8 14 31 45 59 73 87 100 114 127 153 179 205 231 257 282 307 371 434 497 560 686 817 1065 1326 1591

1/2 23 49 71 95 117 138 160 181 202 244 286 327 367 408 449 489 590 691 791 892 1091 1301 1696 2110 2532

3/4 40 87 124 166 204 243 280 318 355 428 501 574 645 717 788 859 1036 1212 1389 1565 1915 2283 2976 3703 4444

1 65 141 202 269 331 393 454 515 575 694 812 930 1045 1162 1277 1392 1679 1964 2251 2536 3104 3700 4823 6002 7202

11/4 112 243 349 465 573 680 786 891 996 1202 1406 1609 1808 2010 2210 2409 2906 3399 3895 4389 5373 6403 8347 10387 12464

11/2 153 331 475 633 781 926 1070 1213 1355 1635 1913 2190 2461 2736 3008 3279 3955 4627 5302 5974 7313 8715 11361 14138 16965

2 252 546 783 1044 1287 1526 1764 1999 2233 2696 3154 3610 4057 4510 4958 5405 6519 7626 8739 9846 12053 14365 18725 23303 27963

21/2 239 519 744 993 1224 1452 1678 1902 2124 2564 3000 3434 3859 4290 4716 5141 6201 7254 8312 9366 11465 13664 17812 22166 26599

3 370 802 1149 1533 1890 2242 2591 2936 3280 3959 4632 5302 5958 6624 7282 7939 9575 11201 12834 14461 17703 21098 27502 34225 41070

4 637 1381 1979 2641 3254 3860 4461 5057 5649 6818 7976 9130 10260 11407 12540 13671 16488 19288 22101 24903 30484 36331 47360 58936 70724

10000

8000

8000

8000

8000

8000

8000

8000

16 7071 15332 21980 29325 36136 42871 49542 56153 62731 75713 88579 101385 113936 126677 139255 151817 183105 214199 245437 276549 338534 404358 525936 654498 785398

18 8951 19407 27822 37119 45740 54265 62708 71078 79404 95836 112121 128331 144217 160345 176265 192166 231770 271128 310668 350048 428507 510687 665717 828448 994137

20 11122 24115 34572 46124 56836 67430 77921 88321 98667 119086 139321 159464 179204 199244 219027 238785 287997 336904 386036 434970 532463 634579 827219 1029428 1235314

24 16087 34878 50002 66710 82204 97526 112700 127741 142706 172238 201505 230638 259189 288174 316787 345363 416540 487276 558337 629112 770120 917814 1196436 1488898 1786677

SIZES 5" THROUGH 24" VEL., FPM PRESS. (PSIG) -10 -5 0 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150 175 200 250 300 400 500 600

10000

10000

REGULATOR or PIPE SIZE (inches)

5 1001 2170 3110 4150 5114 6067 7011 7946 8877 10714 12535 14347 16123 17926 19706 21484 25912 30312 34732 39135 47907 57094 74426 92620 111143

6 1445 3133 4492 5993 7385 8761 10124 11475 12820 15473 18102 20719 23284 25887 28458 31025 37419 43773 50157 56151 69182 82449 107479 133751 160501

8 2502 5425 7778 10377 12787 15171 17531 19871 22199 26793 31345 35877 40318 44827 49278 53723 64795 75798 86852 97862 119796 142771 186112 231607 277928

10 3155 6841 9808 13085 16125 19130 22107 25057 27992 33785 39526 45241 50841 56526 62139 67744 81706 95581 109520 123403 151062 180033 234685 292053 350464

12 4479 9711 13922 18574 22889 27155 31380 35568 39734 47957 56106 64218 72167 80238 88205 96161 115979 135675 155461 175167 214429 255552 333130 414562 497474

14 5413 11737 16826 22448 27662 32818 37924 42986 48021 57959 67808 77611 87219 96972 106601 116217 140168 163972 187884 211700 259150 308850 402609 501024 601229

SELECTING PRESSURE PILOTS Any of the Main Valves described in the Main Valve Section can be combined with any of the Pilots listed below to produce the SPENCE Pressure Regulator. This Regulator will reduce and regulate a steady or varying initial pressure, within the range

specified, so as to maintain a constant, adjustable, predetermined delivery pressure. The table below lists the principal Pressure Pilots.

PRESSURE REGULATOR PILOTS Type

Service Conditions Cast Iron

Cast Bronze

a

Diaphragm

Cast Steel

250

450

300

500

600

750

3

150

D2

250

450

300

500

600

750

100

300

D5

250

450

300

500





1

25

5

150

Diameter inches

Material

1 psi

31/2

St. Stl.

Spring

E or C Series

2 psi

1

3 /2

St. Stl.

Spring

E or C Series

12

/ psi

53/4

St. Stl.

Spring

E or C Series

1 psi

1

4 /2

St. Stl.

Spring

E or C Series

31/2-71/4b

St. Stl.

Air

E or C Series

3 /2-5 /

St. Stl.

Air

E or C Series

31/2

St. Stl.

Air

E or C Series

D120

250

450

300

500

600

750

A73

250

450

300

500

600

750

1

/2 psi

A53

250

450

300

500

600

750

1

A

250

450

300

500

600

750

1

/2 psi

A35

250

450

300

500





A54

250

450

300

500

600

750

curves on

250

450

300

500

600

750

A86

250

450

300

500

600

750

A87

250

450

300

500

600

750

A85

250

450

300

500

600

750

1

/2 psi

See response

A70

Main Valve

Delivery Pressure

Maximum Maximum Maximum Maximum Maximum Maximum Normal Initial TemperInitial TemperInitial TemperAccuracy Pressure ature Pressure ature Pressure ature Minimum Maximum psi °F psi °F psi °F psi psi ± D

Loading

A Pilot

1

/8 psi

1 b 2

5 /4-3 /

St. Stl.

Air

E or C Series

1 psi

41/2-53/4b

St. Stl.

Air

E or C Series

2 psi

1

7 /4

St. Stl.

Air

E or C Series

1

41/2

St. Stl.

Air

E or C Series

14

7/

St. Stl.

Air

E or C Series

31/2-53/4b

St. Stl.

Air

E or C Series

/2 psi

Product Page

12

/ psi

1

/2 psi

50

3 b 4

A84

250

450

300

500

600

750

12

A83

250

450

300

500

600

750

12

3

12

3/

St. Stl.

Air

E or C Series

31/2

St. Stl.

Air

E or C Series

/8 psi

3

5 /4

St. Stl.

Air

E or C Series

/ psi / psi

1

A82

250

450

300

500





Safety Pilot





300

500

600

750

5

175



31/2

St. Stl.

Spring

E or C Series

P125

250

450





600

750

5

175

1 psi

41/2

St. Stl.

Spring

E or C Series

Bronze Body Pilots are recommended for water service. These Pilots have dual diaphragms, the first size being the control diaphragm and the second, the air loading diaphragm.

a

b

NOTES

ON

SELECTION

OF

PILOTS

D SERIES PILOTS meet the requirements of the majority of all pressure regulator problems. They are spring-loaded. Other Pilots are modifications of the D Series for specific purposes. A SERIES PILOTS are air-loaded. These Pilots are recommended where frequent changes in setting must be made and the Regulator is not easily accessible. In any one Series of Pilots a larger Diaphragm will produce closer accuracy of control but with less range in delivery pressure.

Water Service Pilot operated Regulators are not uniformly satisfactory as water reducing valves unless the delivery system has the ample cushioning afforded by an elevated tank or air chamber. When the flow is intermittent to an inflexible system, the SPENCE Type D34 Direct Operated Pressure Reducing Valve is recommended.

SIZING PRESSURE REGULATORS DATA REQUIRED

FOR

EXAMPLE

ORDERING

(a) Maximum/Minimum.

Select size and type Regulator to pass 14,600 lb. steam per hour reducing from 175/150 psi saturated to 40/20 psi. Ends to be flanged, pilot spring loaded and pressure controlled within 2 psi.

(b) Superheat, Gravity, etc.

1. Steam

1. SERVICE Fluid flowing though Regulator. 2. INITIAL (INLET) PRESSURE

(1) Steam Service–Total Temperature or Degrees Superheat, if any. (2) Air, Gases, Water and Liquids–Temperature and Specific Gravity. 3. DELIVERY (OUTLET) PRESSURE Maximum/Minimum. 4. CAPACITY Maximum required flow through Regulator.

2. (a) 175/150 psi (b) None (saturated, 378°F total temperature) 3. 40/20 psi 4. 14,600 lb. per hour 5. Flanged, if 21/2" size or larger

5. END CONNECTIONS Screwed or Flanged. (If flanged, state drilling.)

SELECTION

OF

TYPE

AND

SIZE

MAIN VALVE A. TYPE —See Selection Criteria for Steam, Air, Gases or Water and Liquids in beginning of this Section.

OF

REGULATOR

PILOT See Selection Criteria and Selection Charts opposite.

B. SIZE—See applicable Valve Capacity Tables in this Section.

C. MATERIAL— See Main Valve Selection Chart in Technical Reference Section or individual Product Pages.

SELECTION

OF

TYPE

AND

MAIN VALVE A. Since maximum Delivery Pressure is less than 75% of minimum Initial Pressure and the least pressure drop exceeds required “minimal differential”. SELECT TYPE E

SIZE

OF

REGULATOR

PILOT Since maximum Initial Pressure 175 psi, Total Temperature 378°F maximum Delivery Pressure 40 psi, Pilot spring loaded and required accuracy 2 psi: SELECT TYPE D

B. For 14,600 lb. per hour and 150 psi minimum Initial Pressure Economical: SELECT 3" FULL PORT Engineered: SELECT 4" NORMAL PORT See Pilot Selection Chart opposite or individual Product Pages.

D. ACCESSORIES—See Accessories in Other Products Section.

C. For 175 psi, 378°F: SELECT CAST IRON, FLANGED 250 LB.

For 175 psi, 378°F: SELECT CAST IRON

D. None required in this case.

None required in this case.

ECONOMICAL SOLUTION: 3" FULL PORT SPENCE TYPE ED, CAST IRON BODY, 250 LB. FLANGED ENDS ENGINEERED SOLUTION: 4" NORMAL PORT SPENCE TYPE ED, CAST IRON BODY, 250 LB. FLANGED ENDS. NOTE:Pressure Regulators should always be protected by properly designed Strainers.

SELECTING TEMPERATURE PILOTS Any of the Main Valves described in the Main Valve Section can be combined with any of the Pilots listed below, to produce the SPENCE Temperature Regulator. This Regulator is designed to control the flow of fluid to a heating or cooling element so as to maintain a constant, adjustable, precise predetermined temperature. Pilots fully stroke valve within 5°F. The table below lists the principal Temperature Pilots. The Thermostats of these SPENCE Pilots are of the Vapor Tension Type. They are ruggedly constructed and will not be injured by overheating.

These SPENCE Temperature Pilots can be furnished with 150°F range of temperature adjustment on special order. It should be noted that since heavier Adjusting Springs are required for this greater range the regulation will not be quite so accurate. TEMPERATURE RANGES 20°F to 120°F 150°F to 300°F 50°F to 150°F 170°F to 270°F 70°F to 170°F 250°F to 350°F 120°F to 220°F

Thermostats can be furnished for temperatures higher than 350°F on special order.

TEMPERATURE REGULATOR PILOTS Type

Service Conditions Cast Iron Cast Bronzea Cast Steel Delivery Maximum Maximum Maximum Maximum Maximum Maximum Pressure Initial TemperInitial TemperInitial TemperPressure ature Pressure ature Pressure ature Maximum psi °F psi °F psi °F psi

Operating Characteristics

Main Valve

Cascade Control–Closes on rise in temperature–controls delivery pressure–decreases delivery pressure as temperature increases & vice versa–spring loaded pressure control.

E or C Series

Closes on rise in temperature.

E or C Series

Closes on rise in temperature–controls delivery pressure at predetermined setting– spring loaded pressure control

E or C Series

T134

250

450

300

500

600

750

20

T124

250

450

300

500





125

T14

250

450

300

500

600

750



T14D

250

450

300

500

600

750

150

T14D2

250

450

300

500

600

750

300

T52

250

450

300

500







Opens on rise in temperature.

E or C Series

Safety Pilot





300

500







Prevents excessive temperature rise.

E or C Series

Bronze Body Pilots are recommended for water service.

a

AIR CONTROLLED TEMPERATURE PILOTS SPENCE Air Control Pilots, listed below, have been developed to meet special conditions when used in conjunction with A Series Pressure Pilots. The fast bi-metal thermostats have a 200°F adjustable range and protection against damage from Bulb Style

Bulb Material

No.736

Bronze

No. 737

St. Stl.1

T64

No. 738

St. Stl.1

T60

No.745

St. Stl.2

Type T61

Bulb Mounting

over-heating. By cascading an air signal onto a pressure regulator, the EAT Series temperature control reduces steam pressure to an adjustable limit as well as regulating output temperature. Range °F

Maximum Bulb Temperature °F

Control Mode

Action

1

50-250

350

Proportional

Reverse*

1

50-250

350

Proportional

Reverse*

50-250

350

Proportional

Reverse*

180 350

Proportional Proportional

Reverse* Reverse*

/2 NPT

/2 NPT Sanitary Thermometer Bushing 1 /2 NPT Union Mounted

30-150 100-300***

* Rising output pressure on falling temperature. This action applied to an EA Series Regulator increases steam flow with decreasing temperature. Direct action available for cooling control. 1 2 Type 304 Type 347 or optional Type 316 **Rate or reset available on application ***Other ranges on application

NOTES

ON

SELECTION

OF

PILOTS

HEATING CONTROL Single Pilot Types T134 and Combination Pilot Type T14D2 reduce the steam pressure as well as regulate the output temperature. A choice should be made according to the maximum required delivery pressure, i.e., the pressure needed in the heater to carry the peak load. Pilot Types T14D and T14D2 in cast steel are designed for initial steam pressures in excess of 500°F. Of the Air Control Pilots, the Type T61 is the general choice. The Type T60 is used for temperature indication or for remote adjustment. The required heater pressure will determine the choice of the A Series Pilot. See Product Pages.

COOLING CONTROL Pilot Type T52 is employed With Type E or C Series Main Valves to control temperature by regulating the flow of a cooling medium. This Pilot opens the Main Valve on rising temperature and exercises no control over the delivery pressure. The Air Control Pilots can be furnished with increasing air signal on temperature rise for use in cooling control. TEMPERATURE RANGES Selection of the following ranges of temperature adjustment is recommended for the services noted: 50°F to 150°F Room or air duct control 120°F to 220°F Domestic or laundry hot water service. 70°F to 170°F Fuel oil preheating. 170°F to 270°F Fuel oil heating.

SIZING TEMPERATURE REGULATORS DATA REQUIRED

FOR

EXAMPLE

ORDERING

Select size and type Regulator for heating 120 gpm water from 50°F entering temperature to 170°F final temperature in an instantaneous heater. Steam supply at 125 psi pressure to be reduced to 30 psi maximum in heater.

1. SERVICE (a) Fluid flowing though Regulator. (b) Type heater to be controlled.

1. (a) Steam

2. INITIAL (INLET) PRESSURE

(b) Instantaneous

(a) Maximum/Minimum.

2. (a) 125 psi

(b) Superheat, Gravity, etc. (1) Steam Service–Total Temperature or Degrees Superheat, if any. (2) Air, Gases, Water and Liquids–Temperature and Specific Gravity. 3. DELIVERY (OUTLET) PRESSURE Maximum required on heater. 4. CAPACITY Maximum required flow through Regulator or the following data leading to same: (a) Quantity and type of fluid to be heated or cooled. (b) Temperature rise or drop, °F.

(b) None (saturated, 353°F total temperature) 3. 30 psi 4. See Capacity Tables in this Section. (a) 120 gpm water. (b) 170-50 = 120°F Rise 120 x 120 = 7200#/Hr. 2 5. (a) 170°F–Select standard Temperature Range from facing page to include this final temperature. (b) Close on temperature rise.

5. THERMOSTAT CHARACTERISTICS:

(c) Style No. 700 bronze. (See Options Section)

(a) Controlled Temperature, °F–Maximum/Minimum. (b) Operation–Open or Close on temperature rise.

(d) Ten (10) feet, brass–furnished unless otherwise specified. 6. Flanged, if 21/2" size or larger.

(c) Thermostat Bulb–Style Number and Material. (d) Flexible Tubing–Length and Material. 6. END CONNECTIONS Screwed or Flanged. (If flanged, state drilling)

SELECTION

OF

TYPE

AND

SIZE

MAIN VALVE A. TYPE —See Selection Criteria for Steam, Air, Gases or Water and Liquids in beginning of this Section.

OF

REGULATOR

PILOT See Selection Criteria and Selection Charts opposite.

OF

TYPE

AND

SIZE

MAIN VALVE A. Since maximum Delivery Pressure is less than 75% of minimum Initial Pressure and the least pressure drop exceeds required “minimal differential”. SELECT TYPE E

OF

REGULATOR

PILOT Since maximum Initial Pressure 125 psi, Total Temperature 353°F maximum Delivery Pressure 30 psi SELECT TYPE T124

B. Using Capacity Tables in this Section, for 7200#/Hr and 125 psi initial pressure SELECT 2" FULL PORT

B. SIZE—See applicable Valve Capacity Tables in this Section.

C. MATERIAL— See Main Valve Selection Chart in Technical Reference Section or individual Product Pages.

SELECTION

See Pilot Selection Chart opposite or individual Product Pages.

D. ACCESSORIES—See Accessories in Other Products Section.

C. For 125 psi, 353°F: SELECT CAST IRON, NPT 250

For 125 psi, 353°F: SELECT CAST IRON

D. None required in this case.

None required in this case.

ECONOMICAL SOLUTION: 3" SPENCE TYPE ET124, CAST IRON BODY, NPT 250 ENDS TEMPERATURE RANGE 120-220°F EQUIPPED WITH 10 FEET OF BRASS FLEXIBLE TUBING AND STYLE NO. 700 BRONZE THERMOSTAT BULB. Temperature Regulators should always be protected by properly designed Strainers.

SELECTING DIFFERENTIAL PRESSURE PILOTS SPENCE Differential Pressure Regulators may usually be classified in one or the other of the following groups:

sure on a steam atomizing oil burner at a constant differential above the oil pressure at the nozzle.

1. Control of the delivery pressure at a constant, adjustable, predetermined differential above another source of fluid pressure. This case is illustrated by the use of the SPENCE Type EN Differential Pressure Regulator on a boiler feedwater make-up line to control the delivery pressure of the feedwater at a constant differential above the boiler steam pressure. Another example is the use of the Type EN to control the steam pres-

2. Control of the differential pressure or pressure drop across the Pressure Regulator itself. This case is illustrated by the use of the SPENCE Type EN24 Differential Pressure Regulator installed in parallel with a heat exchanger to maintain a constant differential across it, thereby limiting the flow rate of fluid through the heater. The table below lists the principal Differential Pilots.

DIFFERENTIAL PRESSURE REGULATOR PILOTS Type

Service Conditions Cast Iron

Cast Bronzea

Diaphragm Differential Pressure Max.

Operating Characteristics

Cast Steel

Max. Max. Max. Max. Max. Max. Max. Max. Initial Temper- Diaph. Initial Temper- Diaph. Initial Temper- Diaph. Pressure ature Pressure Pressure ature Pressure Pressure ature Pressure psi °F psi psi °F psi psi °F psi

Normal Accuracy

Min. psi

Max. psi

±

Main Valve

Loading Diameter Material inches

N

250

450

240

300

500

290

600

750

300

3

150

1 psi

31/2 St. Stl. Spring

N33

250

450

240

300

500

290

600

750

300

3

150

1 psi

31/2 St. Stl. Spring

N20

250

366

250

300

366

300

300

366

300

3

150

1 psi

31/2 St. Stl. Spring

Closes on increase in differential Delivery pressure controlled at set differential above loading pressure Loading Pressure may be any fluid Opens on increase in differential Initial pressure controlled at set differential above loading pressure Loading pressure may be any fluid

E or C Series E or C Series E or C Series

Bronze Body Pilots are recommended for water service.

a

NOTES

ON

SELECTION

OF

PILOTS

TYPE N AND N33 PILOTS require that the delivery pressure (pressure of fluid discharged from the Regulator) be controlled at a given differential above some separate source of loading pressure. TYPE N meets the requirements of most boiler feedwater make-up and steam atomizing oil burner differential control problems as described in the first group in the above table.

TYPE N33 is a version of the Type N in which two separated diaphragms are employed to preclude the possibility of contact between the two fluids applied to the pilot. TYPE N20 is a differential relief pilot which causes the Main Valve to open when its initial pressure exceeds the loading pressure by a set differential.

SIZING DIFFERENTIAL PRESSURE REGULATORS DATA REQUIRED

EXAMPLE

ORDERING

FOR

Select size and type Regulator to control the flow of water from a Motor-Driven Centrifugal Boiler Feed Pump maintaining an Excess or Differential pressure of 50 psi between the boiler feedwater and the boiler steam pressure. The feedwater temperature is 240°F. The boiler steam pressure is 150 psi. Flow 90 gpm at 220 psi pump discharge pressure.

1. SERVICE Fluid flowing though Regulator. 2. INITIAL (INLET) PRESSURE (a) Maximum/Minimum. (b) Superheat, Gravity, etc. (1) Steam Service–Total Temperature or Degrees Superheat, if any.

1. Water 2. (a) 220 psi

(2) Air, Gases, Water and Liquids–Temperature and Specific Gravity.

(b) 240°F 3. (a) 150 psi Boiler Pressure

3. LOADING PRESSURE

(b) Steam

(a) Maximum/Minimum.

4. (a) 200 psi (Loading plus Excess Pressure)

(b) Fluid

(b) Water

4. CONTROLLED PRESSURE (a) Maximum/Minimum.

5. Identical with Controlled Pressure, Item 4

(b) Fluid

6. 90 gpm 7. Flanged, if 21/2" size or larger

5. DELIVERY PRESSURE Maximum/Minimum. 6. CAPACITY Maximum required flow through Regulator. 7. END CONNECTIONS Screwed or Flanged. (If flanged, state drilling.)

SELECTION

OF

TYPE

AND

SIZE

MAIN VALVE

OF

REGULATOR

SELECTION

PILOT

TYPE

AND

SIZE

MAIN VALVE

See Selection Criteria and Selection Charts opposite.

A. TYPE —See Selection Criteria for Steam, Air, Gases or Water and Liquids in beginning of this Section.

OF

REGULATOR

PILOT

A. Since pressure drop across valve (Initial Pressure minus Delivery Pressure) is greater than 10 psi: SELECT TYPE E

B. SIZE—See applicable Valve Capacity Tables in this Section.

OF

Since Initial Pressure 220 psi, 240°F, Differential (Excess) Pressure 50 psi and the Delivery and Controlled Pressures are the same: SELECT TYPE N

B. For 90 gpm: SELECT 3" See Pilot Selection Chart opposite or individual Product Pages.

C. MATERIAL— See Main Valve Selection Chart in Technical Reference Section or individual Product Pages.

D. ACCESSORIES—See Accessories in Other Products Section.

C. For 220 psi, 240°F: SELECT CAST IRON, FLANGED 250 LB.

For 220 psi, 240°F: SELECT BRONZE

D. For Water Service: Dashpot required.

None required in this case.

ANSWER: 3" SPENCE TYPE EN, CAST IRON BODY, 250 LB FLANGED ENDS, EQUIPPED WITH BRONZE DASHPOT AND BRONZE PILOT BODY. NOTE: Differential Regulators should always be protected by properly designed Strainers.

WATER CAPACITY TABLE–FLOW

IN

GALLONS

PER

MINUTE

These flow rates provide a simple method for sizing regulators or water pipes with inlet velocities in the range of 240 to 600 fpm. Spence Regulators have variable seat sizes. The factory will select the proper seat for particular flow and pressure drop. Additional capacity data is available on request. 14

/

3

/8

1

/2

3

/4

1

11/4

11/2

VALVE OR PIPE SIZE 2 21/2 3 Velocity, fpm fpm Velocity,

4

5

6

8

10

12

247

251

255

262

270

277

285

300

315

330

360

390

420

480

540

600

1.3

2.5

4.0

7.3

12

22

30

52

78

127

238

405

630

1250

2210

3490

SELECTING BACK PRESSURE PILOTS Any of the Main Valves described in the Main Valve Section can be combined with any of the Pilots listed below to produce the SPENCE Back Pressure Regulator. Provided the delivery (discharge) pressure is sufficiently below the desired back pressure to operate the Regulator, it will maintain a steady back pressure regardless of fluctuations in the load. The Pilot is guaranteed to shut tight when the back pressure falls below a predetermined

setting. The table below lists the principal Back Pressure Pilots. THE SPENCE BACK PRESSURE REGULATOR IS NOT A SAFETY VALVE AND SHOULD NEVER BE USED AS SUCH. The discharge pressure must always be low enough in relation to the back pressure to provide the required minimum differential listed in the Main Valve Selection Chart in the Technical Reference Section.

BACK PRESSURE REGULATOR PILOTS Type

Service Conditions Cast Iron

Cast Bronzea

Diaphragm

Cast Steel

Main Valve

Delivery Pressure

Maximum Maximum Maximum Maximum Maximum Maximum Initial TemperInitial TemperInitial TemperPressure ature Pressure ature Pressure ature Minimum Maximum psi °F psi °F psi °F psi psi

Normal Accuracy Diameter inches

Material

±

Q

150

366

150

366

150

366

3

150

1 psi

31/2

St. Stl.

E or C Series

Q2

250

450

300

500

600

750

100

400

2 psi

31/2

St. Stl.

E or C Series

Q73b

150

366

150

366

150

366

3

150

12

/ psi

31/2-71/4c

St. Stl.

E or C Series

F14

250

450

300

500

600

750

3

150

1 psi

41⁄2

St. Stl.

E or C Series

F13

250

450

300

500

600

750

100

300

2 psi

31⁄2

St. Stl.

E or C Series

F15

250

450

300

500

600

750

2

25

1/2 psi

53⁄4

St. Stl.

E or C Series

F32

250

450

300

500

600

750

200

2000

10 psi

⁄8 piston

St. Stl.

E or C Series

7

Bronze Body Pilots are recommended for water service. Type Q73 is air adjusted, all others are spring loaded. These Pilots have dual diaphragms, the first size being the control diaphragm and the second, the air loading diaphragm.

a

b

c

NOTES

ON

SELECTION

OF

PILOTS

TYPE Q SERIES meet the requirements of the majority of all back pressure problems. They are packless and spring or air loaded. The Type Q Pilot can be furnished for service on refrigerants on special order. TYPE F SERIES have bellows stem seals and separate diaphragm chambers. They are designed for applications where a regulator is required to open on rise in pressure of a fluid other

than that flowing through the regulator. Type F Series Pilots are also recommended for usual back pressure service in the event that long control pipes are unavoidable. In either series of back pressure pilots, a larger Diaphragm will produce closer accuracy of control but with less range in back pressure.

SIZING BACK PRESSURE REGULATORS DATA REQUIRED

FOR

EXAMPLE

ORDERING

(a) Maximum/Minimum.

Select size and type Regulator to pass 9000 lb steam per hour retaining a back pressure of 5 psi and exhausting into a condenser at 6" Hg vacuum. Pilot to be packless, spring loaded and to control the pressure within ±1/2 psi.

(b) Superheat, Gravity, etc.

1. Steam

1. SERVICE Fluid flowing though Regulator. 2. INITIAL (INLET) PRESSURE

(1) Steam Service–Total Temperature or Degrees Superheat, if any.

2. (a) 5 psi

(2) Air, Gases, Water and Liquids–Temperature and Specific Gravity.

3. 6" Hg vacuum

3. DISCHARGE (OUTLET) PRESSURE Maximum/Minimum. 4. CAPACITY Maximum required flow through Regulator.

(b) None (saturated, 228°F total temperature) 4. 9000lb. per hour 5. Flanged, if 21/2" size or larger

5. END CONNECTIONS Screwed or Flanged. (If flanged, state drilling.)

SELECTION

OF

TYPE

AND

SIZE

MAIN VALVE A. TYPE —See Selection Criteria for Steam, Air, Gases or Water and Liquids in beginning of this Section.

OF

REGULATOR

PILOT See Selection Criteria and Selection Charts opposite.

OF

TYPE

AND

MAIN VALVE A. Since Initial Pressure is less than 15 psi and the least pressure drop exceeds “minimum differential”: SELECT TYPE E2

SIZE

OF

REGULATOR

PILOT Since maximum Initial Pressure 5 psi, Total Temperature 228°F, accuracy of control ±1⁄2 psi and Pilot spring loaded: SELECT TYPE F15

B. For 9000 lb. per hour and 5 psi Initial Pressure: SELECT 8" SIZE.

B. SIZE—See applicable Valve Capacity Tables in this Section. C. MATERIAL— See Main Valve Selection Chart in Technical Reference Section or individual Product Pages.

SELECTION

See Pilot Selection Chart opposite or individual Product Pages.

D. ACCESSORIES—See Accessories in Other Products Section.

C. For 5 psi, 228°F: SELECT CAST IRON, FLANGED 125 LB.

For 5 psi, 228°F: SELECT CAST IRON

D. For discharge into vacuum: Condensation Chamber required.

None required in this case.

ANSWER: 8" SPENCE TYPE E2F15, CAST IRON BODY, 125 LB. FLANGED ENDS, EQUIPPED WITH CONDENSATION CHAMBER. NOTE: Back Pressure Regulators should always be protected by properly designed Strainers.

SELECTING PUMP GOVERNOR PILOTS SPENCE Pump Governors are classified in four groups as follows: 1. Constant Pressure Pump Governor which is illustrated by the SPENCE Type EP14 Pump Governor. This Regulator governs the steam supply to a pump, either reciprocating or turbine-driven, and maintains a constant, adjustable pump discharge pressure. 2. Excess Pressure Pump Governor which is illustrated by the SPENCE Type EN Differential Pressure Regulator. Although this Regulator is not a Pump Governor, it is recommended to govern the steam supply to boiler feed pump where it is desired to maintain the pump discharge pressure at a constant, adjustable differential pressure in excess of the boiler steam pressure.

3. Vacuum Pump Governor which is illustrated by the SPENCE Type EF46 Pump Governor. This Regulator governs the steam supply to a vacuum pump and maintains a constant, adjustable vacuum on the pump suction. 4.Differential Control for electric motor-driven centrifugal pumps which is illustrated by the SPENCE Type EN Differential Pressure Regulator. Although this Regulator is not a Pump Governor, it is recommended to maintain a constant, adjustable differential between the feedwater pressure and the boiler steam pressure; i.e., a constant pressure drop across the feedwater regulator. The table below lists the principal Pump Governor Pilots.

PUMP GOVERNOR PILOTS Type

Service Conditions Cast Iron

Cast Bronzea

Diaphragm

Main Valve

Type of Control

Cast Steel

Pump Discharge Pressure Maximum Maximum Maximum Maximum Maximum Maximum Initial TemperInitial TemperInitial TemperPressure ature Pressure ature Pressure ature Minimum Maximum psi °F psi °F psi °F psi psi

Diameter inches

Material

P13

250

450

300

500

600

750

100

300

31/2

St. Stl.

E or C Series Constant Pressure

P14

250

450

300

500

600

750

5

150

41/2

St. Stl.

E or C Series Constant Pressure

P15

250

450

300

500

600

750

3

25

53/4

St. Stl.

E or C Series Constant Pressure

P32

250

450

300

500

600

750

200

2000

7 /8 Piston

St. Stl.

E or C Series Constant Pressure

F46

250

450

300

500

600

750

0

30” Hg vac

41/2

St. Stl.

E or C Series

Vacuum

N

250

450

300

500

600

500

3b

300b

31/2

St. Stl.

E or C Series

Differentialc

b Bronze Body Pilots are recommended for water service. Regulator discharge pressure For electric motor driven centrifugal pump applications only, differential pressure range 3 to 150 psi

a c

NOTES

ON

SELECTION

OF

PILOTS

P SERIES PILOTS are used for constant pressure control. In this Series a larger Diaphragm will produce closer accuracy of control but with less range in pump discharge pressure. TYPE F46 is a vacuum pump governor Pilot. TYPE N is a differential pressure Pilot which is applied to the discharge of a constant speed centrifugal pump to effect

excess pressure control. The design of the Pilot requires that the delivery pressure (pressure of fluid discharged from Regulator) be controlled at a given differential above some separate source of loading pressure. In typical service, boiler feedwater flows through the Regulator and is delivered at constant excess pressure above the boiler steam pressure.

RATED STEAM CAPACITY TABLE TYPE E MAIN VALVE—FULL PORT VALVE INFO

Pounds of Saturated Steam per Hour PRESSURE-psig INLET REDUCED 20 25

VALVE SIZE (inches) 3

/8

12

/

34

/

1

1

1 /2

2

21/2

3

4

5

6

8

10

12

1 /4

1

5-0

90

165

370

520

835

1175

1840

2610

4390

6470

10030

14715

26345

41890

66040

10

100

185

350

575

920

1290

2025

2870

4830

7115

11030

16185

28980

46080

72645

5-0

100

190

365

595

955

1345

2105

2985

5025

7400

11475

16835

30140

47930

75560

30

15 10-0

105 115

195 215

380 415

615 675

990 1080

1390 1515

2175 2370

3085 3365

5190 5655

7645 8330

11855 12920

17400 18955

31150 33940

49530 53965

78080 85075

40

25 20 15-0

120 135 140

220 250 260

425 480 505

695 780 825

1115 1250 1320

1565 1760 1850

2450 2755 2900

3475 3905 4115

5850 6570 6920

8615 9680 10195

13355 15005 15805

19600 22020 23195

35085 39425 41530

55790 87950 62690 98830 66035 104105

50

35 30 25 20-0

130 150 160 165

245 275 300 310

470 530 580 600

765 865 945 975

1225 1385 1515 1560

1720 1945 2125 2190

2695 3045 3325 3430

3830 4320 4720 4870

6435 7270 7940 8185

9480 10705 11695 12060

14700 16600 18130 18700

21575 24360 26605 27440

38625 43615 47635 49125

61415 96820 69350 109330 75745 119410 78110 123140

60

45 40 35 30-0

140 160 175 190

265 300 330 350

510 575 630 680

830 940 1030 1105

1330 1505 1650 1770

1865 2115 2320 2490

2925 3310 3630 3895

4150 4700 5155 5530

6975 7905 8665 9300

10280 11645 12765 13700

15935 18055 19790 21240

23385 26495 29045 31170

41865 47435 51995 55805

66570 75425 82680 88735

104945 118905 130345 139885

75

55 50 45 40-0

180 195 210 225

330 365 395 420

640 705 760 805

1045 1150 1235 1315

1670 1840 1980 2105

2350 2585 2785 2955

3675 4045 4360 4630

5215 5740 6185 6570

8775 9655 10405 11050

12925 14220 15325 16275

20040 22050 23760 25230

29405 32355 34865 37025

52645 83710 57930 92110 62420 99255 66285 105400

131970 145215 156475 166160

100

75 60 50-0

225 275 295

420 510 550

810 985 1060

1320 1610 1725

2115 2575 2765

2970 3620 3885

4655 5665 6080

6605 8045 8630

11110 13525 14515

16365 19925 21380

25370 30890 33145

37230 45330 48640

66650 105985 167080 81155 129045 203440 87085 138475 218300

125

100 75 65-0

250 335 360

470 630 670

905 1215 1290

1475 1980 2100

2360 3170 3370

3315 4455 4730

5190 6970 7405

7370 9895 10510

12395 16645 17680

18255 24515 26040

28305 38010 40370

41535 74360 118235 186400 55775 99860 158785 250320 59245 106065 168655 265880

150

125 100 80-0

275 370 425

515 695 790

990 1340 1520

1610 2185 2480

2585 3500 3970

3625 4915 5575

5680 7695 8730

8060 10920 12390

13555 18370 20840

19970 27055 30700

30960 41945 47595

45430 81340 129335 203895 61555 110205 175235 276255 69845 125045 198835 313460

175

150 125 100 95-0

295 405 475 485

555 755 890 910

1065 1455 1715 1750

1740 2370 2790 2855

2785 3800 4475 4575

3915 5335 6285 6425

6130 8355 9835 10055

8695 11860 13960 14275

14625 19945 23480 24005

21545 29375 34585 35360

33405 45545 53625 54820

49020 87765 139555 220005 66835 119660 190270 299960 78690 140880 224015 353155 80450 144030 229015 361045

200

150 125 110-0

435 515 550

810 960 1030

1560 1850 1980

2545 3015 3230

4080 4825 5175

5725 6780 7265

8965 10615 11380

12725 15065 16150

21405 25335 27160

31525 37320 40005

48880 57860 62025

71730 128420 204200 321920 84910 152015 241715 381060 91020 162960 259120 408500

225

175 150 125-0

460 550 615

860 1025 1145

1660 1975 2210

2710 3220 3600

4340 5155 5765

6095 7240 8100

9540 11335 12680

13540 16090 18000

22770 27065 30270

33540 39865 44585

52000 76310 136620 217240 342475 61810 90700 162380 258200 407055 69130 101440 181615 288785 455265

250

200 175 150 140-0

490 580 655 675

910 1085 1220 1265

1755 2095 2350 2435

2860 3410 3830 3970

4585 5465 6135 6360

6440 7675 8615 8930

10080 14305 12020 170601 13490 19145 13985 19845

24060 28690 32200 33380

35440 42255 47435 49165

54945 80630 144355 65515 96145 172130 73540 107920 193210 76230 111860 200270

Based on 10% (2 psi minimum) accuracy of regulation.

229540 273700 307225 318445

361865 431485 484355 502025

RATED STEAM CAPACITY TABLE TYPE E MAIN VALVE—NORMAL PORT VALVE INFO

Pounds of Saturated Steam per Hour PRESSURE-psig INLET REDUCED 20 25

VALVE SIZE (inches) 3

/8

12

/

34

/

1

1

1 /4

1

1 /2

2

21/2

3

4

5

6

8

10

12

8960

14775

22370

37440

5-0

40

90

285

445

615

865

1045

1425

2550

4630

6825

10

40

100

315

490

680

955

1150

1565

2805

5090

7505

9855

16250

24605

41185

5-0

45

100

325

510

705

990

1195

1630

2920

5295

7805

10250

16905

25595

42835

30

15 10-0

45 50

105 115

335 365

525 575

730 795

1025 1115

1235 1345

1685 1835

3015 3285

5470 5960

8070 8790

10595 11540

17470 19035

26450 28815

44265 48230

40

25 20 15-0

50 60 60

120 135 140

380 425 450

595 665 700

820 925 975

1155 1295 1365

1390 1565 1645

1895 2130 2245

3400 3820 4020

6165 6925 7295

9090 10210 10755

11930 13410 14125

19675 22110 23290

29790 33475 35265

49865 56030 59020

50

35 30 25 20-0

55 65 70 70

130 145 160 165

420 470 515 530

650 735 805 830

905 1020 1115 1150

1270 1435 1565 1615

1530 1730 1890 1945

2090 2360 2575 2655

3740 4225 4615 4755

6785 7660 8370 8630

10005 11295 12340 12725

13135 14835 16200 16705

21660 24460 26715 27550

32795 37035 40445 41710

54890 61985 67695 69810

60

45 40 35 30-0

60 70 75 80

140 160 175 190

455 515 560 605

705 800 880 945

980 111 1220 1305

1375 1560 1710 1835

1660 1880 2060 2210

2265 2565 2810 3015

4055 4595 5035 5405

7355 8335 9135 9805

10845 12285 13470 14455

14240 16130 17685 18980

23480 26600 29160 31295

35545 40275 44150 47385

59495 67410 73895 79305

75

55 50 45 40-0

75 85 90 95

180 195 210 225

570 625 675 715

890 980 1055 1120

1235 1355 1460 1555

1730 1905 2055 2180

2085 2295 2475 2630

2845 3130 3375 3585

5100 5610 6045 6420

9250 10175 10965 11645

13635 15005 16170 17170

17905 19700 21230 22545

29525 32485 35005 37175

44700 49185 53005 56285

74820 82325 88710 94205

100

75 60 50-0

100 120 125

225 275 295

720 875 940

1125 1370 1470

1560 1900 2040

2190 2670 2865

2640 3215 3450

3605 4385 4705

6455 7860 8435

11710 14255 15300

17265 21020 22555

22670 27600 29615

37380 45515 48840

56595 94725 68910 115335 73945 123760

125

100 75 65-0

110 145 155

250 335 360

805 1080 1145

1255 1685 1790

1740 2340 2485

2445 3285 3490

2950 3960 4205

4020 5400 5735

7200 9670 10270

13065 17545 18635

19260 25865 27470

25290 33960 36070

41700 56000 59485

63140 105675 84790 141915 90060 150740

150

125 100 80-0

120 160 185

275 370 420

880 1190 1350

1375 1860 2110

1905 2580 2930

2675 3625 4110

3225 4370 4955

4395 5955 6760

7875 10675 12110

14290 19360 21970

21065 28545 32390

27660 37480 42525

45615 69065 115595 61805 93575 156620 70130 106175 177715

175

150 125 100 95-0

130 175 205 210

295 405 475 485

950 1295 1525 1555

1485 2020 2380 2435

2055 2805 3300 3375

2885 3935 4635 4735

3480 4745 5585 5710

4745 6470 7615 7785

8500 11590 13645 13950

15420 21020 24750 25300

22730 30995 36490 37305

29850 40695 47915 48980

49220 74520 124730 67105 101605 170055 79010 119625 200215 80770 22295 204690

200

150 125 110-0

190 225 240

435 515 550

1390 1645 1760

2170 2570 2755

3010 3560 3815

4225 5000 5360

5090 6025 6460

6940 8215 8810

12435 14720 15780

25560 26708 28630

33260 39375 42210

43675 51700 55420

72020 109040 182510 85250 129075 216035 91390 138370 231595

225

175 150 125-0

200 240 265

460 550 615

1475 1755 1965

2310 2745 3070

3200 3805 4255

4495 5340 5970

5415 6435 7200

7385 8775 9815

13230 15725 17590

24000 28525 31905

35385 42060 47040

46465 76620 116005 194160 55225 91065 137880 230775 61765 101850 154210 258105

250

200 175 150 140-0

210 250 285 295

490 580 655 675

1560 1860 2090 2165

2440 2910 3265 3385

3380 4030 4525 4690

4745 5660 6355 6585

5720 6825 7660 7940

7805 9305 10445 10825

13980 16670 18710 19395

25360 30240 33945 35180

37390 44585 50045 51870

49095 80955 122575 58540 96530 146155 65710 108355 164055 68110 112315 170050

Based on 10% (2 psi minimum) accuracy of regulation.

205155 244625 274585 284615

RATED STEAM CAPACITY TABLE TYPE E2 MAIN VALVE VALVE INFO

Pounds of Saturated Steam per Hour PRESSURE-psig INLET REDUCED

VALVE SIZE (inches) 3

1

1 /2

2

21/2

3

4

5

6

8

10

12

/4

1

12 10 8 5

150 245 295 345

230 375 455 530

375 605 735 860

545 880 1070 1245

875 1415 1715 2000

1350 2185 2650 3085

1905 3085 3740 4360

2840 4595 5570 6495

4010 6490 7870 9170

5060 8195 9935 11580

9230 14945 18120 21110

14850 24040 29145 33960

22195 35930 43560 50760

2.5

375

575

930

1345

2160

3340

4715

7025

9925

12530

22850

36755

54935

12

9 7 5 2

145 230 280 325

220 355 430 495

355 570 690 805

515 830 1005 1165

825 1330 1610 1870

1275 2060 2490 2890

1800 2910 3515 4080

2680 4330 5235 6075

3785 6115 7395 8585

4780 7720 9340 10835

8715 14080 17030 19760

14020 22650 27390 31785

20955 33855 40940 47510

10

7 5 2 1 “ HG VAC

135 220 280 310

210 340 435 480

340 550 705 775

490 795 1020 1125

790 1275 1635 1805

1220 1970 2525 2795

1725 2780 3565 3945

2570 4145 5315 5875

3630 5855 7505 8295

4580 7390 9475 10475

8355 13475 17280 19095

13440 21670 27795 30720

20090 32395 41545 45915

9

6 4 2 2” HG VAC

135 215 260 300

205 330 400 460

330 535 645 745

480 775 935 1080

775 1245 1500 1730

1195 1925 2320 2675

1685 2715 3275 3780

2510 4045 4880 5625

3550 5715 6890 7950

4480 7215 8700 10035

8170 13160 15865 18300

13140 21165 25515 29435

19645 31640 38140 43995

8

5 3 3.1“ HG VAC

130 210

200 325

325 520

470 755

755 1215

1165 1875

1645 2650

2455 3950

3465 5575

4375 7040

7980 12835

12835 20650

19185 30865

285

440

710

1035

1660

2565

3620

5390

7615

9610

17530

28195

42145

7

4 2 4.3’” HG VAC

125 205 275

195 315 420

315 510 680

460 735 985

735 1185 1585

1140 1830 2450

1605 2580 3460

2395 3845 5150

3380 5435 7275

4270 6860 9185

7785 12505 16750

12520 20120 26945

18715 30070 40275

6

3 1 5.5” HG VAC

125 200 260

190 305 405

310 495 650

445 715 945

720 1150 1515

1110 1780 2340

1565 2510 3305

2330 3740 4925

3295 5285 6955

4160 6675 8780

7585 12170 16010

12200 19575 25755

18235 29255 38495

5

2 0 6.7” HG VAC

120 195 250

185 295 380

300 480 615

435 695 895

700 1120 1435

1080 1730 2215

1525 2440 3130

2270 3635 4660

3205 5135 6485

4045 6480 8310

7380 11820 15155

11870 19010 24380

17740 28415 36440

15

1 /4

1

Based on 1 psi accuracy of regulation. K-Factor is included in the above tabulations.

Size 3

/4

1 11/4 11/2 2 21/2 3 4 5 6 8 10 12

E2 Cv Valve Coefficient

∆P Nominal

K Factor

7.6 11.7 18.9 27.4 44 68 96 143 202 255 465 748 1118

3 4 5 6 7 8 9 10 11 12 15

0.635 0.785 0.855 0.895 0.915 0.928 0.935 0.937 0.938 0.940 0.940

TYPE E2 MAIN VALVE ONLY Used at such low pressure drops, a 1 psi deviation of reduced pressure at rated capacity is a significant portion of the total drop. It must be accounted for in calculations dealing with a subcritical flow condition. Also, because E2 valve opening, for 1 psi accuracy of regulation, varies with the pressure drop, a regulation factor K is inserted in the formula. Cv=

W 2.1 K

Where

√ ∆P’(P1 +P’2)

K = Factor from accompanying table Cv = Valve coefficient W = Flow, #/Hr. (saturated steam) ∆P’ = ∆P nominal plus 1 psi P1 = Inlet pressure, psia (psi + 14.7) P2 = Reduced pressure, psia (psi + 14.7) P’2 = P2 nominal (set point value) minus 1 psi ∆P = Pressure drop, psi

NOTE: When computing W for safety valve sizing, use K = 1.0

RATED STEAM CAPACITY TABLE TYPE E5 MAIN VALVE—FULL PORT VALVE INFO

Pounds of Saturated Steam per Hour PRESSURE-psig INLET REDUCED

VALVE SIZE (inches) 3

/4

1

11/4

11/2

2

21/2

3

4

5

6

8

10

12 60708 82453 95592

20

15 10 5.4

286 389 451

441 599 694

712 967 1121

1033 1402 1626

1620 2201 2551

2525 3429 3976

3580 4862 5637

5992 8138 9435

9722 13205 15309

13189 17914 20768

25059 34036 39459

38361 52103 60405

25

20 15 10 8.3

308 420 496 516

474 647 764 794

766 1046 1234 1283

1110 1516 1788 1860

1742 2379 2807 2919

2714 3707 4373 4548

3848 5256 6201 6449

6440 8796 10378 10794

10450 14273 16839 17515

14176 19363 22844 23760

26935 36789 43404 45145

41232 65251 56318 89124 66444 105149 69109 109366

30

25 20 15 11.2

328 450 533 581

505 692 821 894

815 1118 1326 1445

1182 1621 1922 2094

1855 2544 3017 3287

2890 3965 4700 5121

4098 5622 6665 7262

6859 9409 11154 12153

11130 15267 18100 19721

15099 20711 24554 26753

28688 39351 46652 50831

43916 69498 60239 95329 71417 113018 77813 123140

40

35 30 25 17

365 503 601 711

561 775 925 1094

907 1251 1494 1768

1315 1814 2165 2563

2063 2847 3398 4022

3215 4436 5295 6267

4558 6290 7507 8886

7629 10527 12565 14872

12379 17082 20388 24133

16793 23173 27658 32738

31906 44029 52550 62202

48843 77295 67400 106662 80445 127305 95221 150688

50

45 40 35 22.8

398 551 661 841

613 849 1018 1294

990 1371 1644 2091

1435 1988 2384 3031

2252 3120 3741 4757

3509 4862 5828 7413

4976 6894 8264 10511

8327 11538 13832 17591

13512 18722 22444 28544

18331 25397 30447 38723

34829 53317 84374 48255 73870 116901 57849 88558 140144 73574 112628 178236

75

70 65 60 37.3

471 657 793 1166

726 1011 1220 1795

1172 1634 1971 2899

1699 2368 2857 4203

2667 3717 4484 6596

4155 5791 6987 10277

5891 8211 9907 14572

9860 13743 16581 24389

15999 22300 26905 39574

21704 41238 63128 99902 30251 57477 87988 139242 36499 69349 106161 168001 53685 102002 156148 247106

100

95 90 85 51.8

535 748 905 1491

823 1151 1393 2295

1329 1859 2251 3707

1927 2695 3263 5374

3025 4230 5121 8434

4713 6590 7979 13141

6683 9345 11314 18633

11184 15640 18935 31186

18148 25378 30725 50603

24620 46778 71608 113321 34428 65412 100135 158465 41682 79195 121234 191855 68648 130431 199667 315977

125

120 115 110 90 66.3

591 828 1005 1476 1816

910 1275 1547 2272 1751

1470 2060 2500 3671 191

2131 2987 3624 5322 7874

3345 4687 5687 8352 12019

5212 7303 8861 13013 19297

7390 10355 12564 18451 27890

12368 17331 21028 30882 43660

20069 28121 34120 50110 67921

27225 51727 79185 38149 72484 110960 46287 87946 134630 67979 129159 197720 96226 160923 261002

125312 175596 213055 312896 354004

150

145 140 135 110 80.8

643 902 1096 1717 2140

990 1389 1687 2644 2075

1598 2243 2726 4270 191

2317 3252 3951 6191 8545

3637 5103 6201 9716 13051

5667 7952 9662 15138 20965

8035 11275 13700 21465 30308

13448 18871 22930 35925 47454

21820 29601 56243 86098 30620 41539 78924 120819 37207 50475 95902 146809 58293 79080 150252 230010 73834 104610 174955 283770

136251 191198 232328 363994 384891

175

170 165 160 125 95.3

691 970 1180 2048 2465

1063 1493 1817 3153 2400

1717 2412 2934 5094 191

2490 3497 4254 7384 9165

3907 5488 6676 11589 14007

6088 8552 10402 18057 22508

8632 12125 14750 25603 32545

14447 20294 24686 42851 50966

23442 31801 60422 92495 146375 32930 44672 84877 129932 205619 40057 54340 103247 158053 250121 69532 94327 179221 274356 434172 79306 112368 187941 304841 413476

200

195 185 150 109.8

735 1258 2198 2790

1132 1937 3384 4296

1828 3129 5467 6939

2651 4537 7925 10060

4160 7119 12437 15787

6481 11093 19379 24598

9190 15729 27477 34878

15381 26325 45989 58375

24958 33858 64330 98478 155843 42716 57949 110102 168548 266729 74623 101233 192342 294443 465960 94721 128498 244146 373745 591458

250

245 235 200 138.8

817 1402 2471 3440

1258 2158 3804 5296

2032 3486 6145 8555

2946 5054 8908 12402

4624 7932 13980 19463

7205 12359 21784 30327

10215 17524 30887 43001

17098 27743 37636 71508 29330 47592 64563 122670 51695 83883 113795 216210 71969 116780 158423 301004

Based on 10% (2 psi minimum) accuracy of regulation.

109467 187786 330979 460784

173233 297174 523780 729198

RATED STEAM CAPACITY TABLE TYPE E5 MAIN VALVE—NORMAL PORT VALVE INFO

Pounds of Saturated Steam per Hour PRESSURE-psig INLET REDUCED

VALVE SIZE (inches) 3

/4

1

11/4

11/2

2

21/2

3

4

5

6

8

10

12

20

15 10 5.4

215 292 338

377 512 593

505 686 795

746 1013 1175

942 1280 1483

1319 1791 2077

2223 3020 3501

4522 6142 7120

6632 9008 10443

8592 11669 13529

12662 17197 19937

19784 26870 31152

35874 48725 56489

25

20 15 10 8.3

231 315 372 387

405 553 653 679

543 741 875 910

802 1095 1292 1344

1013 1383 1632 1697

1418 1936 2284 2376

2390 3264 3851 4005

4860 6639 7832 8146

7129 9737 11487 11948

9235 12613 14881 15478

13609 18588 21930 22810

21264 29044 34266 35641

38559 52667 62136 64628

30

25 20 15 11.2

246 337 400 436

431 592 702 764

578 793 940 1024

854 1172 1389 1513

1078 1479 1754 1911

1510 2071 2455 2675

2545 3491 4139 4510

5177 7101 8418 9172

7593 10415 12347 13453

9836 13492 15995 17428

14495 19882 23572 25683

22648 31066 36831 40129

41069 56333 66786 72768

40

35 30 25 17

273 377 450 533

480 662 790 935

643 887 1059 1253

950 1311 1565 1852

1199 1655 1976 2338

1679 2317 2766 3274

2831 3906 4662 5519

5758 7945 9483 11224

8444 11653 13908 16463

10939 15095 18017 21326

16121 22246 26552 31428

25189 34759 41487 49107

45676 63030 75229 89047

50

45 40 35 22.8

299 414 496 631

524 726 870 1106

702 972 1166 1483

1037 1437 1722 2191

1309 1814 2175 2766

1833 2540 3045 3872

3090 4281 5133 6528

6285 8708 10439 13276

9218 12771 15311 19472

11941 16545 19834 25225

17598 24382 29229 37174

27496 49860 38096 69081 45671 82816 58084 105326

75

70 65 60 37.3

353 493 594 874

620 864 1043 1534

831 1158 1397 2055

1228 1711 2065 3037

1550 2161 2607 3835

2170 3025 3650 5369

3659 5100 6153 9050

7441 10372 12514 18406

10914 15212 18354 26996

14139 19707 23777 34972

20836 29041 35039 51538

32556 59036 45377 82284 54749 99278 80528 146024

100

95 90 85 51.8

401 561 679 1118

703 984 1191 1961

943 1318 1596 2628

1393 1948 2358 3884

1759 2459 2977 4903

2462 3443 4168 6865

4150 5803 7026 11572

8441 11804 14291 23536

12380 17312 20960 34520

16038 22427 27153 44719

23635 36930 66966 33050 51641 93643 40014 62523 113374 65902 102972 186722

125

120 115 110 90 66.3

443 621 754 1107 1362

778 1090 1322 1942 1313

1042 1461 1772 2603 143

1540 2158 2619 3846 4465

1945 2725 3306 4856 7725

2722 3815 4629 6798 10303

4589 6431 7803 11459 15155

9334 13080 15870 23307 19098

13690 19184 23276 34184 26679

17735 24852 30153 44283 44875

26136 40837 74051 36623 57224 103766 44436 69431 125902 65259 101968 184902 91124 133581 173006

150

145 140 135 110 80.8

482 676 822 1288 1605

846 1187 1442 2259 1557

1133 1590 1932 3028 143

1675 2350 2855 4474 4842

2114 2967 3605 5649 8387

2960 4154 5047 7908 11190

4990 7002 8509 13331 16466

10149 14242 17306 27113 20752

14885 20888 25382 39766 28996

19283 27060 32881 51515 48780

28417 44402 80516 39877 62308 112986 48456 75712 137291 75917 118620 215098 99066 145230 188097

175

170 165 160 125 95.3

518 728 885 1536 1849

909 1276 1553 2695 1800

1218 1710 2080 3611 143

1799 2527 3074 5336 5191

2271 3191 3881 6738 8999

3180 4467 5434 9433 12010

5361 7530 9160 15901 17678

10903 15316 18631 32341 22284

15991 22464 27325 47433 31140

20716 30529 47701 86499 29101 42885 67008 121508 35399 52167 81510 147806 61447 90554 141490 256568 52394 106417 156011 202063

200

195 185 150 109.8

551 944 1649 2093

967 1656 2892 3671

1296 2219 3876 4920

1915 3278 5727 7269

2418 4139 7231 9178

3386 5795 10123 12850

5707 9768 17065 21661

11608 19868 34708 44056

17026 29140 50906 64616

22056 32504 50787 92093 37749 55631 86923 157620 65946 97183 151849 275353 83707 123358 192747 349514

250

245 235 200 138.8

613 1051 1853 2580

1075 1845 3251 4526

1441 2472 4357 6065

2129 3652 6438 8962

2688 4612 8128 11316

3764 6456 11379 15842

6344 10883 19183 26706

12904 22136 39015 54316

18926 24517 36131 56454 32466 42058 61980 96844 57222 74129 109243 170692 79664 103201 152086 237634

Based on 10% (2 psi minimum) accuracy of regulation.

102370 175611 309521 430910

RATED STEAM CAPACITY TABLE TYPE C20 MAIN VALVE AVAILABLE ON SPECIAL ORDER ONLY – CONSULT FACTORY

Pounds of Saturated Steam per Hour PRESSURE-psig INLET REDUCED

VALVE SIZE (inches) 1

11/4

11/2

2

21/2

3

4

5

6

8

10

12

25

5-0

510

950

1360

2035

3190

4685

7805

12625

16970

29600

47520

73520

30

10-0

575

1070

1530

2295

3595

5275

8790

14215

19110

33325

53505

82780

40

20 15-0

665 700

1245 1310

1775 1870

2665 2805

4175 4395

6125 6455

10210 10755

16515 17400

22200 23385

38715 40780

62160 96170 65475 101300

50

30 25 20-0

735 805 830

1375 1500 1550

1965 2145 2215

2945 3220 3320

4615 5040 5200

6780 7405 7635

11295 12340 12725

18270 19955 20580

24555 26820 27660

42830 46775 48240

68760 106385 75100 116190 77445 119820

60

40 35 30-0

800 880 945

1495 1640 1760

2135 2340 2515

3205 3515 3770

5020 5505 5905

7370 8080 8670

12285 13470 14455

19870 21785 23375

26710 29280 31420

46580 51060 54800

74780 115700 81980 126830 87980 136115

75

55 50 45 40-0

890 980 1055 1120

1660 1825 1970 2090

2370 2610 2810 2985

3555 3915 4220 4480

5575 6130 6610 7015

8180 9000 9700 10300

13635 15005 16170 17170

22055 24270 26150 27770

29645 32620 35150 37325

51695 83000 56885 91330 61295 98415 65090 104505

100

75 60 50-0

1125 1370 1470

2100 2560 2745

3000 3655 3925

4505 5485 5885

7055 8590 9220

10360 12610 13535

17265 21020 22555

27920 34000 36480

37530 45695 49035

65450 105080 162575 79695 127950 197955 85515 137295 212415

125

100 75 65-0

1255 1685 1790

2345 3150 3345

3350 4500 4780

5025 6745 7165

7870 10570 11230

1555 15520 16485

19260 25865 27470

31150 41835 44435

41870 73020 117230 181375 56225 98060 157435 243575 59720 104155 167220 258715

150

125 100 80-0

1375 1860 2110

2565 3475 3945

3665 4965 5635

5495 7445 8450

8610 11665 13235

12640 17125 19435

21065 28545 32390

34075 46165 52385

45800 79875 128235 198400 62050 108220 173745 268810 70410 122795 197145 305015

175

150 125 100 95-0

1485 2020 2380 2435

2765 3775 4440 4540

3955 5390 6345 6490

5930 8085 9520 9730

9290 12665 14915 15245

13640 18595 21895 22385

22730 30995 36490 37305

36765 50130 59020 60335

49415 86185 138310 214075 67375 117505 188655 291875 79325 138345 222110 343640 81095 141435 227070 351310

200

150 125 110-0

2170 2570 2755

4050 4795 5140

5785 6845 7340

8675 10270 11010

13595 16090 17250

19955 23625 25325

33260 39375 42210

53800 63680 68265

72310 126105 202465 313245 85595 149275 239660 370790 91755 160025 256920 397490

225

175 150 125-0

2310 2745 3070

4310 5120 5725

6155 7315 8180

9230 10970 12270

14460 17190 19225

21230 25235 28225

35385 42060 47040

57235 76925 134160 215395 333245 68025 91430 159455 256010 396080 76080 102260 178340 286330 442995

250

200 175 150 140-0

2440 2910 3265 3385

4550 5425 6090 6315

6505 7755 8705 9020

9755 11630 13055 13530

15280 18220 20455 21200

22435 26750 30025 31125

37390 44585 50045 51870

60475 81280 141755 72110 96920 169025 80940 108790 189730 83895 112765 196660

Based on 10% (2 psi minimum) accuracy of regulation.

227590 271375 304615 315740

128410 141300 152260 161685

352115 419855 471280 488495

RATED WATER CAPACITY CHART TYPE C34 PILOT OPERATED MAIN VALVE (Specific Gravity of 1)

VALVE INFO

200

PRESSURE DROP – PSI

90 80 70 60 50 40

30

20

10

20

30

40

50

60

80

100

200

300

400

600

800

1000

1500

FLOW IN GALLONS PER MINUTE

VALVE SIZE SELECTION

EXAMPLE

Prior to selecting valve size, the maximum required flow and the pressure drop across the valve must be determined. Enter the Capacity Chart at the maximum required flow GPM and follow vertically to the intersection of the horizontal pressure drop line. The valve size nearest to, but to the right of this intersection is the smallest valve that will satisfy the flow requirements. The vertical portion of the curves indicate the flow at which approximately 15 feet per second velocity is reached. By selecting the next larger size valve, a lower velocity may be maintained. For general service, 8 to 10 feet per second is recommended.

Required maximum flow is 100 GPM, Inlet Pressure is 60 psi, Delivery Pressure is 35 psi (Pressure drop is 25 psi). Enter the Capacity Chart at the 100 GPM line and follow up to 25 psi pressure drop. It falls to the right of the 11/2" valve size line, therefore 2" is the minimum valve size required.

RATED WATER CAPACITY CHART TYPE N6 DIFFERENTIAL PRESSURE VALVE VALVE INFO

(Specific Gravity of 1) 34

/"

11/4"

1"

11/2"

2"

100 90 80 21/2"

70 60

PRESSURE DROP – PSI

50

40

30

20

10 15

20

30

40

50

60

70

80

90

100

150

200

250

300

400

FLOW IN GALLONS PER MINUTE

RATED WATER CAPACITY TABLE TYPE D34 VALVE Water in GPM PRESSURE

VALVE INFO

VALVE SIZE (inches) 14

12

DROP–psig

1

1/

1/

2

21/2

3

4

5

6

5 10 15 20 30 50 75 100 125 150 175

7.4 10 13 15 18 23 29 33 37 40 44

17 24 29 33 41 53 65 75 84 92 100

23 33 40 47 51 74 90 104 116 127 138

32 45 55 64 79 102 125 144 161 176 190

48 68 84 97 118 153 187 216 241 265 285

71 101 124 143 175 226 277 320 358 392 423

116 164 201 233 285 368 450 520 581 637 688

188 266 325 376 460 594 727 840 939 1029 1111

263 373 457 528 646 834 1022 1180 1320 1445 1560

500

SIZING D36 WATER PRESSURE REDUCING VALVE GENERAL CONSIDERATIONS

EXAMPLE

When sizing a water valve, the following points should be considered:

SPECIFIED CONDITIONS Initial Pressure Reduced No Flow Pressure Capacity Required Allowable Droop

(a) The recommended velocity in the pipe (8-10 ft./sec.) (b) The droop which is the fall-off pressure below the no flow pressure setting.

100 PSIG 50 PSIG (lock-up pressure) 30 GPM 10-15 PSIG

1. Enter Capacities vs. Droop Chart, below, at 30 GPM. Move up until you intersect a curve line (possibly more than one curve). e.g. points (a), (b)…etc.

FLOW VS. VELOCITY CHART (Specific Gravity of 1)

The lowest point indicates the minimum size valve required (3/4") at a droop of approximately 16 psi.

500 400

2" 200

11/2"

FLOW IN GALLONS PER MINUTE

= = = =

11/4" 100 80

1"

60

3

/4"

40

1

/2"

20

2. Enter Flow vs. Velocity Chart (left) at 30 GPM and move up until you reach the 3/4" pipe size curve. Move downward and note that the velocity is approximately 18.5 ft./sec., which is unacceptably high. At the point of intersection of 30 GPM with the next valve curve (1"), the velocity will be approximately 11 ft./sec., which is closer to the recommended value. Referring back to the Capacities vs. Droop Chart, you will find that the droop for a 1" valve is only 11 psig, which is also more acceptable. SELECT A 1" TYPE D36

10 8

NOTE: The capacities shown in the Capacities vs. Droop Chart are based on a difference of 50 psig or more between the initial pressure and the regulator lock-up pressure. Where this difference is less than 50 psig, deduct 20% from the capacity obtained.

SCHEDULE 40 PIPE SIZE

6 4

2

0 5

10

15

20

25

VELOCITY FT./SEC. VALVE INFO

CAPACITIES VS. DROOP CHART 0

DROOP PSIG

5 10

b

15

a

20

/"

/"

1 2

10

20

3 4

30

40

11/4"

1"

50

60

70 80 90 100 GALLONS PER MINUTE

11/2"

110

120

130

2"

140

150

160

170

RATED STEAM, AIR AND WATER CAPACITY TABLE TYPE D50 DIRECT ACTING PRESSURE REGULATOR VALVE SIZE CV PSI

1

IN 10 20 30 40 50 75 100 125 150 175 200 250 60 75 85 100 125 150 175 200 250 85 100 125 150 175 200 225 250 110 125 150 200 225 250 135 150 175 200 225 250 160 175 200 225 250

A 14 23 35 29 43 72 98 105 145 170 195 240 38 63 77 96 125 155 180 205 260 44 72 110 140 170 200 225 250 65 105 155 235 275 310 70 115 165 210 255 295 105 145 195 240 280

OUT S 5 41 10 68 10 100 87 130 200 255 30 315 370 425 480 595 115 190 230 280 50 340 405 465 525 650 130 215 325 75 405 465 525 585 650 190 310 460 100 675 755 830 210 340 500 125 635 755 830 315 425 140 580 710 835

/2" 2.2

S — Steam (#/hr.) A — Air (SCFM) W — Water (GPM)

3 " /4 3.3

W 3 4.2 5.9 4.2 5.9 8.8 11 13 15 16 17 20 4.6 7.2 8.5 10 12 14 16 18 20 4.6 7.2 10 12 14 16 18 19 6 9 13 19 21 23 5.9 9.3 13 16 19 21 8.3 11 14 17 19

S 59 97 145 125 185 290 370 450 530 615 695 855 165 275 335 410 500 590 675 765 945 190 315 470 590 675 765 855 945 310 500 745 1095 1220 1350 340 550 810 1030 1230 1350 510 690 940 1150 1350

A 20 33 50 42 63 105 140 175 210 245 280 350 55 92 110 140 185 225 265 305 380 64 105 160 205 245 290 330 370 105 170 250 385 445 505 115 185 270 345 410 475 170 230 315 385 455

W 4.2 6.0 8.5 6.0 8.5 13 16 19 21 23 25 28 6.6 10 12 15 18 21 23 26 30 6.6 10 15 18 21 23 26 28 9 15 21 30 34 37 9.5 15 21 26 30 34 13 18 23 28 31

S 80 130 195 170 250 390 495 605 715 825 930 1150 250 420 510 625 760 895 1030 1170 1440 290 480 720 895 1030 1170 1300 1440 380 620 920 1350 1510 1670 420 680 995 1270 1510 1670 630 855 1160 1420 1670

1"

11/4"

4.9

5.0

A 27 44 67 57 84 140 190 240 285 330 375 470 85 140 170 215 280 340 400 460 580 98 160 240 310 375 440 500 560 125 210 310 475 550 620 140 225 335 425 505 585 210 285 390 475 560

W 5.7 3.1 11 8.1 11 17 21 25 28 31 33 38 10 16 19 23 28 32 36 39 45 10 16 23 28 32 36 39 42 12 19 26 37 41 45 12 19 26 32 37 41 17 22 29 34 39

S 91 150 220 190 285 440 565 690 810 935 1060 1305 260 430 525 645 785 925 1065 1205 1485 300 495 740 925 1065 1205 1345 1485 400 655 970 1430 1590 1760 440 715 1050 1340 1500 1760 665 900 1220 1500 1760

A 30 50 76 64 95 160 215 270 325 375 430 535 87 145 175 220 290 350 415 475 595 100 165 250 320 390 455 515 580 135 220 325 500 580 655 150 240 350 450 535 615 225 300 410 505 590

11/2" 10.1 W 6.5 9.2 13 9 13 19 24 28 32 35 38 43 10 17 20 23 29 33 37 40 47 10 17 23 29 33 37 40 44 12 20 28 39 44 48 12 20 28 34 39 44 17 23 30 36 41

S 105 170 250 250 375 580 740 900 1065 1230 1390 1710 355 585 715 875 1070 1260 1450 1640 2020 410 675 1010 1260 1450 1640 1830 2020 465 755 1120 1650 1840 2030

A 35 57 87 85 125 210 285 355 425 495 560 700 120 195 240 300 390 480 565 650 815 140 225 340 440 530 620 705 790 155 255 375 575 665 760

VALVE INFO

2” 10.8 W 7.4 10 15 12 17 25 32 37 42 46 50 56 14 23 27 32 39 45 50 55 65 14 23 32 39 45 50 55 60 14 23 32 45 50 55

S 120 230 290 265 395 610 780 950 1120 1290 1460 1800 395 655 800 1000 1190 1400 1620 1830 2260 455 750 1130 1400 1620 1830 2040 2250 515 840 1250 1830 2040 2250

A 40 77 100 89 130 220 295 375 445 520 590 735 130 220 270 335 435 535 630 720 905 155 250 380 485 590 685 785 880 170 280 415 640 740 840

W 8.5 14 17 13 18 27 33 39 44 48 52 60 16 25 30 35 43 50 56 61 71 16 25 35 43 50 56 61 66 16 25 35 50 56 61

SIZING D50 DIRECT ACTING PRESSURE REGULATOR EXAMPLE 1 FOR CONDITIONS

WITHIN

EXAMPLE 2 FOR CONDITIONS

CAPACITY TABLE

Given an initial steam pressure of 100 PSIG and a required flow of 500 #/hr. at a reduced pressure of 30 PSIG, determine droop, minimum controllable flow pressure and valve size. In the Capacity Table opposite, the droop has been fixed at 25% of the maximum range of the adjusting spring. Therefore, for a 30 PSIG delivery pressure, a 25-80 adjusting spring would be selected. Thus, the droop is (25% x 80 = 20) 20 PSI. Minimum controllable flow pressure = Reduced Pressure + Droop = 30 + 20 = 50 PSIG Entering the Capacity Table at a minimum controllable flow pressure (OUT) of 50 PSIG, an initial pressure (IN) of 100 PSIG, the smallest valve size capable of delivering 500 #/hr. is the 1" size.

Given an initial steam pressure of 150 psig and a required flow of 900 #/hr. at a reduced pressure of 25 PSIG, determine the valve size, droop and minimum controllable flow pressure. P2 = (25 + 14.7) = 39.7 = .24 thus P = .24P < .58P 2 1 1 P1 (150 + 14.7) 164.7 Therefore, use Critical Flow Cv formula: W = 900 900 Cv = = = 3.2 1.71P1 1.71 (150 + 14.7) 1.71 (164.7) Referring to the Cv line of the Capacity Table opposite, the 3/4" valve size (Cv = 3.3) is the smallest valve with the required capacity. Droop is a function of valve size (3/4"), regulator capacity in percent [(3.2 ÷ 3.3) x 100 = 97%] and adjusting spring range (10-30). Enter the 3/4" Valve Droop Chart (below) at 97% and draw a line upward until you intersect the 10-30 curve. From there , draw a line left to the vertical axis. Droop in this case is 11 PSIG. Minimum Controllable Flow Pressure = Reduced Pressure + Droop = 25 + 11 = 36 PSIG Repeating the above procedure substituting a 1" valve size with a maximum Cv of 4.9, droop would be 8 PSIG and minimum controllable flow pressure would be 33 PSIG.

12

34

/ " VALVE DROOP CHART

/ " VALVE DROOP CHART

0

0

5

3-15

10

DROOP, PSIG

DROOP, PSIG

CAPACITY TABLE

OUTSIDE

10-30

15 25-80

25

3-15

5

10-30

10 15 25-80

25

75-140 35 10

20

30

40

50

60

70

80

90

100

0

10

20

30

40

50

60

70

80

90

REGULATOR CAPACITY IN PERCENT

REGULATOR CAPACITY IN PERCENT

1" & 11/4" VALVE DROOP CHART

11/2" & 2" VALVE DROOP CHART

0

100

0

5

3-15

10

DROOP, PSIG

DROOP, PSIG

75-140

35 0

10-30

15 25-80

25

0

10

20

30

40

50

3-15 10 10-40

15 25

75-140

35

5

30-100

35 60

70

80

REGULATOR CAPACITY IN PERCENT

90

100

0

10

20

30

40

50

60

70

80

REGULATOR CAPACITY IN PERCENT

90

100