REFRIGERATION THERMOSTATS

REFRIGERATION THERMOSTATS DANFOSS REFRIGERATION THERMOSTATS INTRODUCTION KP thermostats are temperature-controlled electrical switches. All KP thermos...
Author: Anissa Holmes
28 downloads 3 Views 677KB Size
REFRIGERATION THERMOSTATS DANFOSS REFRIGERATION THERMOSTATS INTRODUCTION KP thermostats are temperature-controlled electrical switches. All KP thermostats have a single pole double throw (SPDT) changeover switch. The position of the switch depends on the thermostat setting and the bulb temperature. A KP thermostat can be directly connected to single-phase a.c. motors of up to about 2.7 hp, or installed in the control current circuit of d.c. motors and large a.c. motors.

FEATURES • • • • • • • • • • •

Wide regulating range. Can be used for deep freeze, refrigeration and air conditioning systems. Welded bellows elements mean increased reliability. Small dimensions — Easy to install in refrigerated counters or cold rooms. Ultra-short bounce times. Long operating life. Unnecessary cut-in and cut-out of control equipment is avoided. Standard versions with changeover switch. Possible to obtain opposite switch function or to connect a signal. Electrical connection at the front of the unit facilitates rack mounting. Saves space. Suitable for alternating and direct current. No spade or lug terminals required. Integral 1/2 NPSM swivel cable connector. Allows direct attachment of 1/2 in. male pipe thread connector. Extensive and wide range.

P636

P636C

APPROVALS UL listed, file E31024. CSA certified, LR 27339.

933

REFRIGERATION THERMOSTATS DANFOSS REFRIGERATION THERMOSTATS ORDERING

CHARGE

TYPE

Vapour

KP 61 KP 62 KP 63 KP 69 KP 71

Adsorption

KP 73 KP 98

BULB TYPE*

REGULATION RANGE

B C A B E2 E2 D E1 E2 E2

–20 to 55 –20 to 60 –60 to 15 25 to 95 20 to 70 25 to 70 –15 to 60 0 to 80 Oil: 30 to 90 HT: 210 to 350

DIFFERENTIAL ∆t At Lowest At Highest Temperature Temperature Setting °F Setting °F 8 to 40 2.2 to 13 10 to 40 2.7 to 13 18 to 125 4.9 to 15 8 to 45 3.2 to 13 4.5 to 18 4 to 18 Fixed 5.4 Fixed 5.4 8 to 36 6.3 to 36 10 to 35 10 to 35 Oil: Fixed 22 Oil: Fixed 22 HT: Fixed 45 HT: Fixed 45

*Bulb Types: A B C D E1 E2

— — — — — —

Straight Capillary Tube 3/8-in. dia. x 2-3/4-in. Remote Air Coil Integrated Air Coil Double Contact Remote Bulb 1/4-in. dia. x 3-3/8-in. Remote Bulb 3/8-in. dia. x 4-in. Remote Bulb

THEMOSTAT BULB TYPES A Straight capillary tube Sensing Length: 15 in. of 80 in.

B Dia. 3/8 in. x 2-3/4 in. remote air coil C Dia. 1-9/16 in. x 1 in. air coil (integral with thermostat)

D Dia. 3/8 in. x 2-3/4 in. double contact remote bulb NOTE: Cannot be used in sensor (bulb) pocket. E E1: Dia. 1/4 in. x 3-3/8 in. remote bulb E2: Dia. 3/8 in. x 4 in. remote bulb

934

RESET

CAP. TUBE LENGTH (ft)

Auto. Auto. Auto. Auto. Auto. Man. Min. Auto. Auto. Man. Max.

6.5 — 6.5 6.5 6.5 6.5 6.5 6.5 3.2 6.5

P/N 60L2002 60L2015 60L2007 60L2009 60L2010 60L2011 60L2017 60L2029 60L2025

PRESSURE CONTROLS DANFOSS OIL DIFFERENTIAL PRESSURE CONTROLS INTRODUCTION MP 54 and MP 55 oil differential pressure controls are used as safety switches to protect refrigeration compressors against low lubricating oil pressure. If the oil pressure fails, the control will stop the compressor after a predetermined time period has elapsed. MP 54 and 55 are used in refrigerating systems using CFC, HCFC, HFC MP 54 has a fixed differential pressure setting. It also incorporates a thermal time relay with a fixed release time setting. MP 55 have adjustable differential pressure and are available with thermal time relay.

P639

FEATURES • Fixed and adjustable differentials available. • 240 or 120 V a.c. or d.c. control voltage. • Simple manual trip, electrical test function eliminates need of tools and test "jumper" wires. • Extremely narrow switch differential accuracy. • Reliable, long life stainless steel bellows. • Sturdy metal cover and universal mounting hole patterns. • Integral 1/2 NPSM swivel cable connector allows direct attachment of 1/2 in. male pipe thread connector. • Standard four-wire hook-up. • Refrigerants: CFC, HCFC, HFC. APPROVALS • UL listed, file E31024. • CSA certified, LRA 56093.

P639B

MATERIALS IN CONTACT WITH THE MEDIUM UNIT TYPE MP 54 MP 55 MP with capillary tube

MATERIAL Stainless steel 19/11, no. 1.4306 to DIN 17440 Deep-drawn steel plate, no. 1.0338 to DIN 1624 Free cutting steel, no. 1.0718 to DIN 1651 Copper SF-Cu, no. 2.0090 to DIN 1787

TECHNICAL DATA Maximum bellows temperature: 212° F. Temperature compensation: The time relay is temperature-compensated in the range - 40 to 140° F. Switch differential: Maximum 2.8 psi. Maximum working pressure: MWP = 245 psig. Maximum test pressure: p′ = 320 psig. Control voltage: 240 V or 120 V a.c. or d.c. Permissible voltage variation: +10 to −15%. Contact load of time relay output contacts M-S:

240 V a.c.: 2 FLA 240 V a.c.*: 0.2 FLA *Not approved for DC application.

Cable entry: Integral 1/2 in. female NPSM swivel cable connector allows direct attachment of 1/2 in. male pipe thread connector. Enclosure: NEMA 1; IP 20 to IEC 529.

935

PRESSURE CONTROLS DANFOSS OIL DIFFERENTIAL PRESSURE CONTROLS

TYPE

P639C

MP 54 MP 54 MP 54 MP 54 MP 54 MP 54 MP 54 MP 54 MP 54 MP 54 MP 54 MP 55 MP 55 MP 55 MP 55 MP 55 MP 55 MP 55 MP 54

PRESSURE CONNECTION CONTROL REGULATION TIME RELAY DIFFERENTIAL RANGE 36 in. 88 in. DELAY TIME 1/4 in. ∆P LP SIDE Capillary Capillary S Flare PSI (IN. HG TO PSIG) Tube Tube fixed 6.0 29 in. to 170 45 + fixed 6.0 29 in. to 170 45 + fixed 6.0 29 in. to 170 45 + fixed 13.0 29 in. to 170 45 + fixed 6.0 29 in. to 170 60 + fixed 9.0 29 in. to 170 60 + fixed 9.0 29 in. to 170 60 + fixed 9.0 29 in. to 170 90 + fixed 9.0 29 in. to 170 90 + fixed 9.0 29 in. to 170 120 + fixed 9.0 29 in. to 170 120 + 4.3 to 64 29 in. to 170 45 + 4.3 to 64 29 in. to 170 60 + 4.3 to 64 29 in. to 170 60 + 4.3 to 64 29 in. to 170 90 + 4.3 to 64 29 in. to 170 90 + 4.3 to 64 29 in. to 170 120 + 4.3 to 64 29 in. to 170 120 + fixed 6.0 29 in. to 170 120 +

P/N 60B2008 60B2050 60B2058 60B2061† 60B2059 60B2001 60B2051 60B2002 60B2052 60B2003** 60B2053** 60B2054 60B2012†† 60B2055 60B2006 60B2056 60B2007 60B2057 60B2008*

*Corresponds to CARRIER/CARLYLE specifications. †With 60B1203 bracket. **Correspond to COPELAND specifications. Three-wire hook-up. ††With operational light that remains on during normal operation of compressor. NOTE: When time delay is energized which also means that min. permissible oil pressure (differential ∆p) is reached, light goes out.

DIMENSIONS AND WEIGHTS

P639D

MP 54, 55 — Weight: Approx 1.8 lbs

936

PRESSURE CONTROLS DANFOSS PRESSURE CONTROLS INTRODUCTION KP pressure controls can be used as safety switches against too low a suction pressure and/or too high a discharge pressure in refrigeration and air conditioning systems. They can also be used to start/stop compressors and fans for air-cooled condensers. They are available in both single and dual versions and include a single pole double throw (SPDT) switch. FEATURES • "Snap Action" electrical contact. Minimizes chatter, bounce and wear, insuring long-term reliability. • Available with gold-plated contacts. • SPDT switch design. Offers open or close switching action on pressure rise or fall. • Computer-designed integrated bellows/spring assembly. For maximum accuracy and control repeatability. • Fail safe double bellows. Prevent refrigerant loss and system contamination — standard on KP 7 and KP 17 pressure controls. • Convenient manual trip feature — To test electrical contact function — no tools needed. • Vibration and shock resistant. • Repeatability less than 0.1 psi drift. Even after 400,000 cycles. • Pressure wire connectors for easy electrical wiring. • No spade or lug terminals required. • Integral 1/2 NPSM swivel cable connector allows direct attachment of 1/2 in. male pipe thread connector. • Lockplate prevents tampering with range and differential settings. • Universal mounting hole patterns. APPROVALS • UL listed, file E31024. • CSA certified, LR 27339.

P641

P641A

Metric Conversions 1 psi = 0.07 bar 5/9 (t1° F – 32) = t2° C 1 ton = 3.5 kW 1 in. = 25.4 mm 1 ft = 0.3 m 1 lb = 0.454 kg 1 oz = 28.35 g US gal/min = 0.86 m3/h

937

PRESSURE CONTROLS DANFOSS PRESSURE CONTROLS

P641B

Refrigerants: CFC, HCFC, HFC

LOW PRESSURE (LP) HIGH PRESSURE (HP) RESET PART NO. Pressure Connection Regulating CONTACT Differential Regulating Differential Low High PRESSURE TYPE Range Cap. Tube w/1/4 in. ∆p Range ∆p Pressure Pressure SYSTEM (in. Hg 1/4 in. Flare Flare Nut psi psig psi LP HP to psig) 36 in. Low KP 1 6 to 108 10 to 58 auto. 60-2001 Low KP 1 6 to 108 10 to 58 auto. 60-2051 Low KP 1 27 to 100 fixed 10 manual 60-2052* SPDT Low KP 1 6 to 108 10 to 58 auto. 60-2076 Low KP 2 6 to 50 6 to 32 auto. 60-2013 Low KP 2 6 to 72 6 to 32 auto. 60-2063 High KP 5 115 to 465 25 to 85 auto. 60-2014 High KP 5 115 to 465 25 to 85 auto. 60-2064 High KP 7W† 115 to 465 58 to 140 auto. 60-2003 SPDT High KP 7W† 115 to 465 58 to 140 auto. 60-2053 High KP7B† 115 to 465 fixed 58 manual 60-2004 High KP7B† 115 to 465 fixed 58 manual 60-2054 Dual KP 15 6 to 108 10 to 58 115 to 465 fixed 58 auto. auto. 60-2008 Dual KP 15 6 to 108 10 to 58 115 to 465 fixed 58 auto. auto. 60-2058 SPDT/w. LP signal Dual KP 15 6 to 108 10 to 58 115 to 465 fixed 58 auto. manual 60-2059 Dual KP 15 6 to 108 10 to 58 115 to 465 fixed 58 manual manual 60-2060 Dual KP 15 6 to 108 10 to 58 115 to 465 fixed 58 auto. auto. 60-2031 SPDT/w. Dual KP 15 6 to 108 10 to 58 115 to 465 fixed 58 auto. manual LP + HP 60-2026 signal Dual KP 17W† 6 to 108 10 to 58 115 to 465 fixed 58 auto. auto. 60-2029 SPDT/w. 60-2055 Dual KP 17W† 6 to 108 10 to 58 115 to 465 fixed 58 auto. auto. LP signal *With dial knob. †With fail safe double bellows.

938

Metric Conversions 1 psi = 0.07 bar 5/9 (t1° F – 32) = t2° C

PRESSURE CONTROLS DANFOSS PRESSURE CONTROLS DIMENSIONS AND WEIGHTS Flare Connection

P641C

Capillary Tube Connection

P641D

Metric Conversions:1 in. = 25.5 mm 1 lb = 0.454 kg

939

940

Applications

AKV

TRE

Supermarket Cases Walk-In Coolers Ice-Machines

Supermarket Cases Walk-In-Coolers Residential A/C T(E)2 Ice-Machines Heat Pump Transport Refrigeration Food Dispensers Supermarket Cases Walk-In-Coolers Residential A/C TUA(E) Ice-Machines Heat Pump Transport Refrigeration Food Dispensers Mobile Refrigeration Equip Air Conditioning Units Heat Pump TC Refrigeration Appliances Liquid Coolers Ice-Machines Traditional Refrig. Systems Air Conditioning Systems Heat Pump Water Chillers Refrigerated Containers Traditional Refrig. Systems

Valve

Electronic expansion valves (PWM)

Adjustable Superheat, Bi flow, Stainless Steel cap tubed/bulb, Available with or w/o MOP

Available with Interchangeable or Fixed Orifice, Available with Adjustable or Fixed Superheat, Available with or w/o MOP

Interchangeable orifice, Bi flow, Stainless Steel body/cap tube/bulb, Adjustable Superheat

Interchangeable orifice, available with or w/o Maximum Operating Pressure (MOP), Adjustable Superheat

Features

0.30-5.70

40.0-70.0

TRE80

AKV10

20.0-40.0

10.0-20.0

TRE20

TRE40

8.00-10.0

5.00-7.50

0.17-4.50

0.15-4.50

0.20-3.90

0.20-3.00

0.20-4.40

28.0-56.0

14.0-28.0

7.00-14.0

5.00-7.00

3.50-5.20

0.13-3.50

0.11-3.00

0.20-4.80

40.0-70.0

20.0-40.0

8.00-16.0

8.00

3.80-5.70

0.13-3.50

0.11-2.60

0.30-5.70

40.0-70.0

20.0-40.0

10.0-20.0

8.00-10.0

5.40-8.10

0.18-4.80

55.0-100

25.0-55.0

15.0-25.0

8.00-15.0

6.50-9.80

Nominal Capacity Ranges in TR for Range N -40 to 50° F R-22 R-502 R-134a R-404A/507 R-407C R-410A

TRE10

Models

Angelway

Straightway

Straightway

Straightway

Angleway

Body Type

Internal

External

External

Internal/External

Internal/External

Pressure Equalization

3/8 x 1/2 1/2 x 5/8

3/8 x 1/2

3/8 x 1/2

3/8 x 1/2 1/2 x 5/8

5/8 x 7/8 7/8 x 7/8 7/8 x 1-1/8 5/8 x 7/8 7/8 x 7/8 7/8 x 1-1/8 7/8 x 1-3/8 1-1/8 x 1-1/8 7/8 x 1-1/8 7/8 x 1-3/8 1-1/8 x 1-3/8 1-1/8 x 1-1/8 1-1/8 x 1-3/8 1-1/8 x 1-5/8 1-3/8 x 1-3/8 1-1/8 x 1-5/8 1-3/8 x 1-5/8

3/8 x 5/8 1/2 x 5/8

1/4 x 3/8 1/4 x 1/2 3/8 x 3/8 3/8 x 1/2 1/2 x 5/8

1/4 x 1/2 3/8 x 1/2

Connections SAE x SAE SAE x ODF ODF x ODF

THERMOSTATIC EXPANSION VALVES

DANFOSS TYPE T(E)2, TUA(E), TC, TRE, AKV

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE TC Introduction, type TC

The TC thermostatic expansion valve has been developed and designed for soldering into hermetic refrigeration systems. It is manufactured in stainless steel and is therefore very suitable for installation in refrigeration systems for the food industry. C can be used in many different forms of refrigeration system, in particular: - Mobile refrigeration equipment - Air conditioning units - Heat pump systems - Refrigeration appliances - Liquid coolers - Ice cube machines - Traditional refrigeration systems All variants are available in both single pack and industrial packs as required by the customer. TCAE with interchangeable orifice assembly and adjustable superheat TCBE with fixed orifice assembly and adjustable superheat TCCE with fixed superheat, otherwise it is identical with TCBE. All types are straightway versions.

Features, TC





• • • • •

Bimetal connections - straightforward and fast soldering (no wet cloth or cooling pliers required) Refrigerants R-22, R-134a, R-404A, R-507, R-407C, R-410A and future refrigerants Capacities from 5.0 to 7.5 TR (17.5 to 26.5 kW) for R-22 Stable regulation Biflow function (orifice 1 and 2) Compact design - small dimensions and low weight Stainless steel, hermetically tight solder version - high connection strength - high corrosion resistance - capillary tube joints of high strength and vibration resistance.







• • • •

Laser-welded, stainless steel thermostatic diaphragm element - optimum function - long diaphragm life - high pressure resistance Stainless steel double contact bulb - straightforward and fast installation - good heat transfer from bulb to pipe Adjustable superheat type (TCAE/TCBE) - accurate setting - adjustable in operation Fixed superheat type (TCCE) Filter with high dirt retention capacity Available with self-cleaning bleed Available with MOP (Max. Operating Pressure)

Static superheat (SS) for R-22, R-134a, R-404A, R-407C, R-410A Valves without MOP: 9° F Valves with MOP: 7° F Static superheat (SS) for R-507 Valves without MOP: 11° F Valves with MOP: 9.5° F Capillary tube length 59.0 in. Connections: Inlet 3/8 in. 1/2 in. Outlet 5/8 in.

Standard range, TCAE

Versions available in the standard range. Ranges for R-22, R-134a, R-404A, R-507, R-407C and R-410A: N –40 → +50° F without MOP N –40 → +50° F MOP + 60°F NM –40 → +25° F MOP + 32°F Ranges for R-404A og R-507 B –75 → –15° F without MOP B –75 → –15° F MOP -4°F

Standard range, TCBE

Versions available in the standard range: Ranges N -40 → +50° F without MOP N -40 → +50° F MOP + 60° F Static superheat (SS) for R-22, R-134a, R-404A, R-407C, R-410A Valves without MOP: 9°F Valves with MOP: 7°F

Variant range TCBE/TCCE

In addition to the standard range, TCBE and TCCE valves are also available in these variants and variant combinations: Ranges NM -40 → +25° F MOP +32° F B -75 → -15° F without MOP B -75 → -15° F MOP -4° F Static superheat (SS) The static superheat setting is to be determined before ordering. Contact Danfoss for the appropriate setting

Static superheat (SS) for R-507 Valves without MOP: 11¨° F Valves with MOP: 9.5° F Capillary tube length: 36.0 in Connections: Inlet Orifice 1 3/8 in. Orifice 1-3 1/2 in. Outlet 5/8 in.

Capillary tube length: 59.0 in Bleed: 15% Connections: Inlet Orifice 2-3 3/8 in. Outlet Orifice 1-3 1/2 in.

941

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE TC Ordering TCAE, Straightway — Thermostat element without orifice and with bulb strap R-22, R-134a, R-404A, R-507, R-407C, R-410A

REFRIGERANT

VALVE TYPE

PRESSURE EQUALIZATION 1)

CONNECTION Inlet x Outlet (In.)

ext. 1/4 in.

3/8 x 5/8 1/2 x 5/8 3/8 x 5/8 1/2 x 5/8 3/8 x 5/8 1/2 x 5/8 3/8 x 5/8 1/2 x 5/8 3/8 x 5/8 1/2 x 5/8

R-22 R-134a R-404A/ R-507

TCAE

R-12 R-502

Range N –40/+50° F Without MOP MOP +60° F 068U4280 068U4282 068U4281 068U4283 068U4292 068U4294 068U4293 068U4295 068U4304 068U4306 068U4305 068U4307 068U4324 068U4326 068U4325 068U4327 068U4336 068U4338 068U4337 068U4339

CODE NO. Range NM –40/–25° F MOP +32° F 068U4288 068U4289 068U4300 068U4301 068U4312 068U4313 068U4332 068U4333 068U4344 068U4345

Range B –75/–15° F Without MOP MOP –4° F

068U4316 068U4317

068U4318 068U4319

Capillary tube length 59.0 in.

Ordering TCAE Orifice Assembly with filter and gasket ORIFICE1)

BLEED % 0 15 0 15 0 15

1 1 2 2 3 3

1)

TC with orifice no. 3, cannot be used for biflow operation.

Spare Parts: Filter (24 pcs): Gaskets (24 pcs):

CODE NO. 068U4100 068U4097 068U4101 068U4098 068U4102 068U4099

068U0016 068U0015

NOTE: To secure tightness, the orifice gasket must be changed each time the orifice is disassembled.

Ordering TCBE, Straightway — Thermostatic expansion valve with bulb strap

R-22, R-134a, R-404A, R-507, R-407C, R-410A REFRIGERANT

TYPE

R-22

R-134a

R-404A/ R-507

TCBE

R-407C

R-410A

RATED CAPACITY 2) kW 17.5 17.5 21.0 26.5 12.0 12.0 14.5 18.0 13.5 13.5 16.0 20.0 19.0 19.0 23.0 28.5 23.0 23.0 27.5 34.0

TR 5 5 6 7.5 3.5 3.5 4.1 5.2 3.8 3.8 4.5 5.7 5.4 5.4 6.5 8.1 6.5 6.5 7.8 9.8

Capillary tube length 36.0 in. 1) 2

TC with orifice no. 3, cannot be used for biflow operation.

) The rated capacity is based on ARI 750-97.

942

ORIFICE No. 1)

PRESSURE EQUALIZATION

1 1 2 3 1 1 2 3 1 1 2 3 1 1 2 3 1 1 2 3

ext. 1/4 in.

CONNECTION Inlet x Outlet (in. x in.) 3/8 x 5/8 1/2 x 5/8 1/2 x 5/8 1/2 x 5/8 3/8 x 5/8 1/2 x 5/8 1/2 x 5/8 1/2 x 5/8 3/8 x 5/8 1/2 x 5/8 1/2 x 5/8 1/2 x 5/8 3/8 x 5/8 1/2 x 5/8 1/2 x 5/8 1/2 x 5/8 3/8 x 5/8 1/2 x 5/8 1/2 x 5/8 1/2 x 5/8

CODE NO. Range N: –40/+10° C Without MOP MOP +60° F 068U4200 068U4204 068U4201 068U4205 068U4202 068U4206 068U4203 068U4207 068U4216 068U4220 068U4217 068U4221 068U4218 068U4222 068U4219 068U4223 068U4232 068U4236 068U4233 068U4237 068U4234 068U4238 068U4235 068U4239 068U4248 068U4252 068U4249 068U4253 068U4250 058U4254 068U4251 068U4255 068U4264 068U4268 068U4265 068U4269 068U4266 068U4270 068U4267 068U4271

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE T2 & TE2 Introduction

Thermostatic expansion valves, type T 2 and TE 2 regulate the flow of refrigerant liquid into evaporators. Injection is controlled by the refrigerant superheat. T 2 valves are especially suitable for liquid injection into “dry” evaporators where the superheat at the evaporator outlet is proportional to the evaporator load. The valves are available in rated capacities up to 4.5 TR (R 22) and can be used in a wide range of applications: • Conventional refrigeration systems

P332B

• Heat pump systems • Air conditioning systems • Specialty refrigeration appliances • Liquid chillers • Ice machines • Transport refrigeration This leaflet contains data and code numbers for our standard product program.

Features

• Applicable for deep freezing, refrigeration and air conditioning.

• Available with Maximum Operating Pressure (MOP) Used to protect the compressor motor against excessive evaporator pressure.

• Interchangeable orifice assembly Easier stocking, capacity matching, and service.

• Stainless steel double-contact bulb For easy self-aligning during installation and efficient heat transfer from pipe to bulb.

• Broad temperature range from –75 to 50° F:

• Rated capacities from 0.15 to 4.5 TR (R-22)

Thermostatic charge options

Danfoss offers the following standard range of thermostatic charges: Range N –40 to +50° F without MOP Range N –40 to +50° F, MOP ~ 60° F Range NM –40 to +25° F, MOP ~ 32° F

Range NL –40 to +5° F, MOP ~ 15°F Range B1) –75 to +15° F without MOP Range B1) –75 to +15° F, MOP ~ –4°F 1

Regular valve options

Static superheat (SS) (R-12, R-22, R-502, R-134a, and R-404A): Valves without MOP: 9° F Valves with MOP: 7° F Static superheat (SS) for R-507: Valves without MOP: 11° F Valves with MOP: 9° F Capillary tube length 5 ft

) T 2/TE 2 valves for range B are not available for R-12 and R-134a

Connection sizes Inlet x outlet: 3/8 in. flare x 1/2 in. flare 3/8 in. flare x 1/2 in. ODF 3/8 in. ODF*) x 1/2 in. flare 3/8 in. ODF*) x 1/2 in. ODF 1/4 in. ODF*) x 1/2 in. flare 1/4 in. ODF*) x 1/2 in. ODF *) Requires a solder adapter

External equalization: 1/4 in. flare (for all flare outlet bodies) 1/4 in. ODF (for all ODF outlet bodies)

943

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE T2 & TE2 Ordering

Components with Flare x Flare Connections Thermostatic element and valve body with bulb strap (without orifice and filter)

Refrigerant

R-22 R-134a R-404A/ R-507 R-12 R-502 1)

Valve Type

Pressure Equalization1)

Capillary Tube (ft)

Connection Inlet x Outlet (in. x in.)

P/N Range NM Range NL –40 to +25° F –40 to +5° F With With MOP MOP

Range N –40 to +50° F Without With MOP MOP

Range B –75 to –15° F Without With MOP MOP

TX 2

Int.

5

3/8 x 1/2

068Z3206

068Z3208

068Z3224

068Z3226

068Z3207

068Z3228

TEX 2

Ext.

5

3/8 x 1/2

068Z3209

068Z3211

068Z3225

068Z3227

068Z3210

068Z3229

068Z3369

TN 2

Int.

5

3/8 x 1/2

068Z3346

068Z3347

068Z3393

TEN 2

Ext.

5

3/8 x 1/2

068Z3348

068Z3349

068Z3392

068Z3370

TS 2

Int.

5

3/8 x 1/2

068Z3400

068Z3402

068Z3406

068Z3408

068Z3401

068Z3410

TES 2

Ext.

5

3/8 x 1/2

068Z3403

068Z3405

068Z3407

068Z3409

068Z3404

068Z3411

TF 2

Int.

5

3/8 x 1/2

068Z3202

068Z3236

068Z3220

068Z3222

TEF 2

Ext.

5

3/8 x 1/2

068Z3204

068Z3237

068Z3221

068Z3223

TY 2

Int.

5

3/8 x 1/2

068Z3212

068Z3214

068Z3230

068Z3232

068Z3213

068Z3234

TEY 2

Ext.

5

3/8 x 1/2

068Z3215

068Z3217

068Z3231

068Z3233

068Z3216

068Z3235

Externally equalized connections are 1/4 in. flare.

Orifice Assembly with Filter

Rated capacity in tons (TR) Orifice No. 0X 00 01 02 03 04 05 06

R-22 0.15 0.3 0.7 1.0 1.5 2.3 3.0 4.5

Range N: –40 to +50° F R-134a R-404A/R-507 R-12 0.11 0.11 0.25 0.21 0.2 0.5 0.45 0.3 0.8 0.6 0.5 1.3 1.2 1.0 1.9 1.7 1.5 2.5 2.2 2.0 3.0 2.6 3.0

R-502 0.2 0.3 0.5 1.0 1.5 2.0 3.0

Rated capacity is based on: Evaporating temperature te = +40° F for range N and te = –20° F for range B Condensing temperature tc = +90° F Refrigerant liquid temperature ahead of valve tl = +80° F

Flare Connection Accessories Connection for Copper Tube w OD (in.) 1/4 3/8 1/2

Reducer for copper Tube w OD (in.)

1/4

Metric conversions 1 psi = 0.07 bar 5/9 (t1° F – 32) = t2° C 1 ton = 3.5 kW 1 in. = 25.4 mm 1 ft = 0.3 m

944

P/N 011L1101 011L1135 011L1103 011L1107

Range B: –75 to –15° F R-22 R-404A/R-507 R-502 0.15 0.11 0.2 0.21 0.2 0.3 0.45 0.3 0.6 0.6 0.5 0.8 1.0 0.8 1.2 1.4 1.2 1.5 1.7 1.5 2.0 1.9 2.0

P/N 068-2002 068-2003 068-2010 068-2015 068-2006 068-2007 068-2008 068-2009

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE T2 & TE2 Ordering (continued) Components with Flare x Solder Connections Thermostatic element and valve body with bulb strap (without orifice and filter) CONNECTION Refrigerant

R-22 R-134a R-404A/ R-507 R-12 R-502 1)

Valve Type

Equalization1)

Capillary Tube (ft)

Pressure

Inlet Flare (in.)

Outlet ODF Solder (in.)

CODE NO. Range NL –40 to +5° F With MOP

Range N –40 to +50° F Without With MOP MOP

Range B –75 to –15° F Without With MOP MOP

TX 2

Int.

5

3/8

1/2

68Z3281

68Z3287

68Z3357

68Z3319

TEX 2

Ext.

5

3/8

1/2

68Z3284

68Z3290

68Z3359

68Z3320

TN 2

Int.

5

3/8

1/2

68Z3383

68Z3387

TEN 2

Ext.

5

3/8

1/2

68Z3385

68Z3389

TS 2

Int.

5

3/8

1/2

68Z3414

68Z3416

68Z3429

68Z3418

68Z3420

TES 2

Ext.

5

3/8

1/2

68Z3415

68Z3417

68Z3430

68Z3419

68Z3421

TF 2

Int.

5

3/8

1/2

68Z3280

68Z3286

TEF 2

Ext.

5

3/8

1/2

68Z3283

68Z3289

TY 2

Int.

5

3/8

1/2

68Z3282

68Z3288

68Z3292

68Z3294

TEY 2

Ext.

5

3/8

1/2

68Z3285

68Z3291

68Z3293

68Z3295

Externally equalized connections are 1/4 in. ODF solder.

Orifice Assembly with Filter

Rated capacity in tons (TR) Orifice

Metric conversions 1 psi = 0.07 bar 5/9 (t1° F – 32) = t2° C 1 ton = 3.5 kW 1 in. = 25.4 mm 1 ft = 0.3 m

No.1) 0X 00 01 02 03 04 05 06 1)

R-22 0.15 0.3 0.7 1.0 1.5 2.3 3.0 4.5

Range N: –40 to +50° F R-134a R-404A/R-507 R-12 0.11 0.11 0.25 0.21 0.2 0.5 0.45 0.3 0.8 0.6 0.5 1.3 1.2 1.0 1.9 1.7 1.5 2.5 2.2 2.0 3.0 2.6 3.0

Range B: –75 to –15° F R-22 R-404A/R-507 R-502 0.15 0.11 0.2 0.21 0.2 0.3 0.45 0.3 0.6 0.6 0.5 0.8 1.0 0.8 1.2 1.4 1.2 1.5 1.7 1.5 2.0 1.9 2.0

R-502 0.2 0.3 0.5 1.0 1.5 2.0 3.0

Code No. 68-2002 68-2003 68-2010 68-2015 68-2006 68-2007 68-2008 68-2009

These orifice assemblies cannot be used together with solder adapters. Please see adapter information

below. Rated capacity is based on: Evaporating temperature te = +40° F for range N and te = –20° F for range B Condensing temperature tc = +90° F

Solder Adapter

Filter for solder adapter

The adapter is for use with thermostatic expansion valves type T2 and TE2 with flare x solder connections. When the adapter is correctly fitted it meets DIN 8964 sealing requirements. The adapter offers the following advantages without unsoldering the valve from the system: The orifice assembly can be replaced. The filter can be cleaned or replaced. When using the solder adapter, a special orifice assembly is required. Please use the following tables to select both the appropriate adapter and orifice assembly. Solder adapter without orifice assembly and filter Connection ODF Solder 1/4 in. 3/8 in.

Code No. 68-2062 68-2060

Description Filter excl. orifice assembly

Code No. 68-0015

Orifice assembly and filter for use with solder adapter Orifice No. 0X 00 01 02 03 04 05 06

Code No. 68-2089 68-2090 68-2091 68-2092 68-2093 68-2094 68-2095 68-2096

945

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE T2 & TE2 Design

T 2 and TE 2 valves consist of four main components: 1. Thermostatic element 2. Orifice assembly 3. Valve body with connections 4. Superheat setting spindle For a given valve type and refrigerant, the associated orifice is suitable for all versions of the valve body and in all evaporating temperature ranges.

1. 2. 3. 4.

946

Thermostatic element Interchangeable orifice assembly Valve body Superheat adjustment spindle

The valves are equipped with internal or external pressure equalization. Where a liquid distributor is used, always use a valve with external equalization. The double-contact bulb give fast and precise reaction of temperature changes in the evaporator. The bulb design makes mounting quick and easy. The valves are able to withstand the effects that normally occur with hot gas defrosting. To insure long operating life, the valve cone and valve seat are made of steel alloy with particularly good wear qualities.

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE TUA/TUAE

P4200

Features

P4200A

Refrigerants • R-22, R-134a, R-404A, R-407C, R-507 (for other refrigerants, contact Danfoss) Interchangeable orifice assembly • For easier stocking, capacity matching, and service Bi-flow function Stainless steel • High body strength • High corrosion resistance • Highly vibration-resistant, flexible capillary tube

Metric conversions 1 ton = 3.5 kW

Stainless steel capillary tube • Tolerates more bending for easier installation and longer life. • Greater resistance to vibration during operation. Stainless steel double-contact bulb • Self-aligning for fast and easy installation; secures with a single strap or quick clip. • More contact surface for better heat transfer. Removable strainer • 100 mesh removable strainer for easy servicing. Suitable for use with new POE oils.

Compact design Bi-metal connections • Small dimensions and light weight for com• Fast and easy soldering without the need for pact installation. a wet cloth. Laser engraving Precision Port design • Durable positive valve identification; no Four major features contributing to superior labels to peel off over time. repeatable performance over an extended Patented superheat adjustment device: valve life: • Adjust with 5/32-in. Allen wrench. • Laser-welded power element insures diaphragm´s structural integrity and lengthens Optional quick clip bulb fastener life. • For fast and easy installation. • Precision-machined cone and bushing avoid the need for a packing gland. • Free-floating push-rod is self-aligning and eliminates binding. • Precision-machined cone and orifice accurately meters refrigerant under all operating conditions.

947

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE TUE/TUAE Ordering

Thermostatic element and valve body with bulb strap (without orifice and filter) R-22, R-134a, R-404A, R-407C, R-507 PRESSURE CAPILLARY VALVE REFRIGERANT TYPE EQUALIZATION1) TUBE (in.)

R-22

R-134a

R-404A/ R-507

R-407C

TUA TUA TUAE TUAE TUA TUA TUAE TUAE TUA TUA TUAE TUAE TUA TUA TUAE TUAE

Int. Int. Ext. 1/4 in. Ext. 1/4 in. Int. Int. Ext. 1/4 in. Ext. 1/4 in. Int. Int. Ext. 1/4 in. Ext. 1/4 in. Int. Int. Ext. 1/4 in. Ext. 1/4 in.

CONNECTIONS ODF x ODF (in.)

59 59 59 69 59 59 59 59 59 59 59 59 59 59 59 59

1/4 x 1/2 3/8 x 1/2 1/4 x 1/2 3/8 x 1/2 1/4 x 1/2 3/8 x 1/2 1/4 x 1/2 3/8 x 1/2 1/4 x 1/2 3/8 x 1/2 1/4 x 1/2 3/8 x 1/2 1/4 x 1/2 3/8 x 1/2 1/4 x 1/2 3/8 x 1/2

CODE NO. Range N Range NM –40 → 50° F –40 → 25° F w/o MOP MOP 60° F MOP 32° F 068U2234 068U2242 068U2250 068U2235 068U2243 068U2251 068U2236 068U2244 068U2252 068U2237 068U2245 068U2253 068U2204 068U2212 068U2220 068U2205 068U2213 068U2221 068U2206 068U2214 068U2222 068U2207 068U2215 068U2223 068U2284 068U2292 068U2300 068U2285 068U2293 068U2301 068U2286 068U2294 068U2302 068U2287 068U2295 068U2303 068U2324 068U2332 068U2340 068U2325 068U2333 068U2341 068U2326 068U2334 068U2342 068U2327 068U2335 068U2343

Range B –60 → –15° F w/o MOP MOP –15° F 068U2258 068U2266 068U2259 068U2267 068U2260 068U2268 068U2261 068U2269

068U2308 068U2309 068U2310 068U2311 068U2348 068U2349 068U2350 068U2351

068U2316 068U2317 068U2318 068U2319 068U2356 068U2357 068U2358 068U2359

Orifice assembly with filter and gasket Rated capacity in tons (TR)1) ORIFICE NO. 0 1 2 3 4 5 6 7 8 9

R-22 0.17 0.25 0.36 0.50 0.75 1.00 1.5 2.0 3.0 4.5

RANGE N: –40 → 50° F R-134a R-404A R-407C 0.13 0.13 0.18 0.19 0.19 0.26 0.28 0.28 0.38 0.39 0.39 0.53 0.59 0.60 0.80 0.78 0.79 1.1 1.2 1.2 1.6 1.6 1.6 2.1 2.3 2.4 3.2 3.5 3.5 4.8

R-507 0.13 0.19 0.27 0.38 0.57 0.76 1.1 1.5 2.3 3.4

R-22 0.15 0.19 0.24 0.34 0.50 0.66 1.0 1.3 2.0 2.9

RANGE B: –60 → –15° F R-404A R-407C 0.10 0.13 0.14 0.16 0.18 0.20 0.25 0.28 0.37 0.41 0.50 0.55 0.75 0.82 1.0 1.1 1.5 1.6 2.2 2.4

R-507 0.11 0.15 0.20 0.28 0.41 0.55 0.82 1.1 1.7 2.4

CODE NO. 068U1030 068U1031 068U1032 068U1033 068U1034 068U1035 068U1036 068U1037 068U1038 068U1039

1) According to ARI 750-94. Rated capacities for range N are based on: Liquid temperature ahead of expansion valve tl = 100° F Evaporating temperature te = 40° F Pressure drop across valve ∆p = 60 psi for R-134a Pressure drop across valve ∆p = 100 psi for R-22, R-404A, R-407C and R-507.

Rated capacities for range B are based on: Liquid temperature ahead of expansion valve tl = 100° F Evaporating temperature te = –40° F Pressure drop across valve ∆p = 100 psi for R-134a Pressure drop across valve ∆p = 150 psi for R-22, R-404A, R-507C and R-507.

Spare Parts Filter (24 pcs): 068U0016 Gasket (24 pcs): 068U0015 NOTE: To secure tightness, the orifice gasket must be changed each time the orifice is disassembled.

948

Metric conversions 1 psi = 0.07 bar 5/9 (t1° F – 32) = t2° C 1 ton = 3.5 kW 1 in. = 25.4 mm

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE TRE10, TRE20, TRE40, AND TRE80

P4201

• Bimetal connections - waterless soldering - quicker installation times - higher productivity

Features

• Two-way balanced port/biflow function - superheat unaffected by condensing pressure independent of flow direction - One valve for heat pump service

• Stainless steel double contact bulb • Developed for R-410A - R-22, R-407C, R-134a, R-404A, R-507 and - straightforward and fast installation - good thermal contact and heat transfer other fluorinated refrigerants • Laser-welded power element: - longer diaphragm life - high pressure tolerance and working pressure

• Adjustable/non-adjustable version - setting spindle assembly can be retrofitted to non-adjustable version

• Stainless steel power element, capillary tube and bulb - high corrosion resistance - high strength and vibration resistance - fast installation: self-aligning bulb secures with one strap - good thermal contact and transmission

Overview of product range CAPACITY TR 8-70 8-70 8-85 8-85 8-70 8-70 5-56 5-56

kW 28-245 28-245 28-350 28-350 28-246 28-246 18-196 18-196

REFRIGERANT Type Code R-22 X R-22 X R-410A L R-410A L R-407C Z R-407C Z R-134a N R-134a N

RANGE

MOP

K N K N K N K N

60°F/15°C 60°F/15°C 60°F/15°C 60°F/15°C

K: –15 → +50°F / –25 → +10°C N: –40 → +50°F / –40 → +10°C To avoid charge migration when MOP valves are used, the bulb temperature must be lower than the thermostatic element temperature.

MOP points

REFRIGERANT

R-22 R-410A R-407C R-134a R-404A/R-507 1)

RANGE K –15 → 50°F / –25 → +10°C MOP Point for Evaporating Temperature te and Evaporating Pressure Pe 1) t0 = +60°F / +15°C Pe = 100 psig / 6.9 bar Pe = 165 psig / 11.5 bar Pe = 95 psig / 6.6 bar Pe = 55 psig / 3.9 bar Pe = 120 psig / 8.4 bar

Pe in bar gauge

949

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE TRE10, TRE20, TRE40, AND TRE80 Valve options

In addition to the standard program, TRE valves are also available with the following options:

Refrigerants - Range - MOP: Contact Danfoss for information regarding different refrigerants and evaporator ranges. Static superheat, adjustable: 3.6°F → 10.8°F

P4201

Static superheat, fixed: 3.6°F → 10.8°F Internal bleed:

Capillary tube length:: TYPE TRE10 TRE20 TRE40 TRE80

CAPILLARY TUBE LENGTH 0.9 or 1.5 m 3 or 5 ft 0.9; 1.5 or 3.0 m 3; 5 or 10 ft 1.5 or 3.0 m 5 or 10 ft 1.5 or 3.0 m 5 or 10 ft

Connections: TYPE TRE10 TRE20

15% TRE40 TRE80

INLET ODF SOLDER 1/2 - 5/8 - 7/8 in. 12 - 16 - 22 mm 5/8 - 7/8 - 1-1/8 in. 16 - 22 - 28 mm 7/8 - 1-1/8 in. 22 - 28 mm 1-1/8 - 1-3/8 in. 28 - 35 mm

OUTLET ODF SOLDER 1/2 - 5/8 - 7/8 - 1-1/8 in. 12 - 16 - 22 - 28 mm 5/8 - 7/8 - 1-1/8 - 1-3/8 in. 16 - 22 - 28 - 35 mm 7/8 - 1-1/8 - 1-3/8 in. 22 - 28 - 35 mm 1-1/8 - 1-3/8 - 1-5/8 in. 28 - 35 - 42 mm

Equalizing connection 1/4 in. or 6 mm ODF on all types. Sizes in bold type are standard sizes.

Maximum operating temperature - Thermostatic Element: N

charge

K

charge

210°F/100°C (R-410A max. 115°F/70°C) 302°F/150°C

Biflow operation TRE valves are designed for biflow operation. During flow in the reverse direction, the rated capacity is reduced by as much as 10%.

- Valve body: 230°F/110°C

Maximum working pressure PB = 609 psig/42 bar Maximum test pressure p' = 670 psig/46.5 bar MOP function

To avoid charge migration when MOP valves are used, the bulb temperature must be lower than the thermostatic element temperature.

MOP points:

REFRIGERANT

1)

950

RANGE K –25 → +10°C/–15 → +50°F MOP Point for Evaporating Temperature te and Evaporating Pressure pe1) te = +60°F/+15°C

R-22

pe = 100 psig/6.9 bar

R-410A

pe = 165 psig/11.5 bar

R-407C

pe = 95 psig/6.6 bar

R-134a

pe = 55 psig/3.9 bar

R-404A/R-507

pe = 120 psig/8.4 bar

pe in bar gauge

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE TRE10, TRE20, TRE40, AND TRE80 Ordering Standard program

R-22, R-410A REFRIGERANT

R-22

Pressure equalization = 1/4 in. ODF 1)

The rated capacity is based on: ARI Standard 750-97 2) Number of valves in industrial and multipacks: (see page 6)

R-410A

CONNECTION ODF SOLDER

TYPE RATED CAPACITY Qnom1) TR

RATED CAPACITY Qnom1) TR

Inlet in.

Outlet in.

TRE10-8X TRE10-10X TRE20-10X TRE20-12.5X TRE20-15X TRE20-20X TRE20-20X TRE40-20X TRE40-20X TRE40-25X TRE40-25X TRE40-30X TRE40-40X TRE80-40X TRE80-55X TRE80-70X TRE10-8L TRE10-8L TRE10-10L TRE10-10L TRE10-12.5L TRE10-12.5L TRE10-15L TRE10-15L TRE20-15L TRE20-15L TRE20-20L TRE20-20L TRE20-25L TRE20-25L TRE40-25L TRE40-25L TRE40-30L TRE40-30L TRE40-40L TRE40-40L TRE40-55L TRE40-55L TRE80-55L TRE80-55L TRE80-80L TRE80-80L TRE80-80L TRE80-100L TRE80-100L

8 10 10 12.5 15 20 20 20 20 25 25 30 40 40 55 70 8 8 10 10 12.5 12.5 15 15 15 15 20 20 25 25 25 25 30 30 40 40 55 55 55 55 80 80 80 100 100

5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8

7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 5/8 7/8 5/8 7/8 5/8 7/8 7/8 1-1/8 7/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8

RANGE K –15°/+50°F MOP 60°F –25°/+10°C MOP 15°C Code no. Code no. Industrial Multi2) pack2) pack 067L1021 067L2021 067L1024 067L2024 067L1075 067L2075 067L1079 067L2079 067L1084 067L2084 067L1087 067L2087 067L1088 067L2088 067L3001 067L4001 067L3002 067L4002 067L3005 067L4005 067L3006 067L4006 067L3009 067L4009 067L3012 067L4012 067L3060 067L4060 067L3063 067L4063 067L3066 067L4066 067L1028 067L2028 067L1029 067L2029 067L1030 067L2030 067L1031 067L2031 067L1034 067L2034 067L1035 067L2035 067L1038 067L2038 067L1039 067L2039 067L1091 067L2091 067L1092 067L2092 067L1093 067L2093 067L1094 067L2094 067L1097 067L2097 067L1099 067L2099 067L3015 067L4015 067L3016 067L4016 067L3019 067L4019 067L3020 067L4020 067L3023 067L4023 067L3024 067L4024 067L3027 067L4027 067L3028 067L4028 067L3069 067L4069 067L3070 067L4070 067L3073 067L4073 067L3074 067L4074 067L3075 067L4075 067L3078 067L4078 067L3079 067L4079

RANGE N –40°/+50°F –40°/+10°C Code no. Code no. MultiIndustrial 2) pack pack2) 067L1121 067L2121 067L1124 067L2124 067L1175 067L2175 067L1179 067L2179 067L1184 067L2184 067L1187 067L2187 067L1188 067L2188 067L3101 067L4101 067L3102 067L4102 067L3105 067L4105 067L3106 067L4106 067L3109 067L4109 067L3112 067L4112 067L3160 067L4160 067L3163 067L4163 067L3166 067L4166 067L1128 067L2128 067L1129 067L2129 067L1130 067L2130 067L1131 067L2131 067L1134 067L2134 067L1135 067L2135 067L1138 067L2138 067L1139 067L2139 067L1191 067L2191 067L1192 067L2192 067L1193 067L2193 067L1194 067L2194 067L1197 067L2197 067L1199 067L2199 067L3115 067L4115 067L3116 067L4116 067L3119 067L4119 067L3120 067L4120 067L3123 067L4123 067L3124 067L4124 067L3127 067L4127 067L3128 067L4128 067L3169 067L4169 067L3170 067L4170 067L3173 067L4173 067L3174 067L4174 067L3175 067L4175 067L3178 067L4178 067L3179 067L4179

951

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE TRE10, TRE20, TRE40, AND TRE80 Ordering Standard program

R-407C, R-134a REFRIGERANT

R-407C

Pressure equalization = 1/4 in. ODF 1)

TYPE RATED CAPACITY Qnom1) TR TRE10-8Z TRE10-10Z TRE20-10Z TRE20-12.5Z TRE20-15Z TRE20-20Z TRE20-20Z TRE40-20Z TRE40-20Z TRE40-25Z TRE40-25Z TRE40-30Z TRE40-40Z TRE80-40Z TRE80-55Z TRE80-70Z TRE10-5N TRE10-7N TRE20-7N TRE20-9N TRE20-11N TRE20-14N TRE20-14N TRE40-14N TRE40-14N TRE40-16N TRE40-16N TRE40-20N TRE40-25N TRE80-25N TRE80-35N TRE80-45N

RATED CAPACITY Qnom1) TR 8 10 10 12.5 15 20 20 20 20 25 25 30 40 40 55 70 5 7 7 9 11 14 14 14 14 16 16 20 25 25 35 45

CONNECTION ODF SOLDER Inlet in.

Outlet in.

5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8

7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-5/8

RANGE K –15°/+50°F MOP 60°F –25°/+10°C MOP 15°C Code no. Code no. Industrial Multi2) pack2) pack 067L1012 067L2012 067L1015 067L2015 067L1058 067L2058 067L1062 067L2062 067L1067 067L2067 067L1070 067L2070 067L1071 067L2071 067L3030 067L4030 067L3031 067L4031 067L3034 067L4034 067L3035 067L4035 067L3038 067L4038 067L3040 067L4040 067L3082 067L4082 067L3085 067L4085 067L3088 067L4088 067L1003 067L2003 067L1006 067L2006 067L1041 067L2041 067L1045 067L2045 067L1050 067L2050 067L1053 067L2053 067L1054 067L2054 067L3043 067L4043 067L3044 067L4044 067L3047 067L4047 067L3048 067L4048 067L3051 067L4051 067L3054 067L4054 067L3091 067L4091 067L3094 067L4094 067L3097 067L4097

RANGE N –40°/+50°F –40°/+10°C Code no. Code no. MultiIndustrial 2) pack pack2) 067L1112 067L2112 067L1115 067L2115 067L1158 067L2158 067L1162 067L2162 067L1167 067L2167 067L1170 067L2170 067L1171 067L2171 067L3130 067L4130 067L3131 067L4131 067L3134 067L4134 067L3135 067L4135 067L3138 067L4138 067L3140 067L4140 067L3182 067L4182 067L3185 067L4185 067L3188 067L4188 067L1103 067L2103 067L1106 067L2106 067L1141 067L2141 067L1145 067L2145 067L1150 067L2150 067L1153 067L2153 067L1154 067L2154 067L3143 067L4143 067L3144 067L4144 067L3147 067L4147 067L3148 067L4148 067L3151 067L4151 067L3154 067L4154 067L3191 067L4191 067L3194 067L4194 0673197 067L4197

According to ARI 750 Rated capacities for Range N are based on: R-134a Liquid temperature ahead of expansion valve t1 = 100°F Evaporating temperature te = 40°F Pressure drop across valve ∆p = 60 psi for R-134a Pressure drop across valve ∆p = 100 psi for R-22, R-404A, R-407C and R-507 Pressure drop across valve ∆p = 160 psi for R-410A. 2) Number of valves in industrial and For connections, refrigerants, capillary tube lengths, etc. outside the standard program, see Valve options. multipacks: (see page 6)

Accessories

Filter: For mounting in the inlet connection. Setting spindle assembly: For installation on valves with fixed setting. NOTE: Spring not included.

DIMENSION 1/2 in. 5/8 in. 7/8 in. 1-1/8 in.

TYPE TRE10 TRE20 TRE40 TRE80

952

TIGHTENING TORQUE 30 Nm (22 ft lbf) 46 Nm (34 ft lbf) 66 Nm (49 ft lbf) 90 Nm (66 ft lbf)

CODE NO. 067L1281 067L1282 067L1283 067L1284

CODE NO. 067L1295 067L1296 067L1297 067L1298

THERMOSTATIC EXPANSION VALVES DANFOSS TYPE TRE10, TRE20, TRE40, AND TRE80 Dimensions and Weights

P4202

Type

TRE10

TRE20

TRE40

TRE80

1)Fixed

Connection, ODF Solder Inlet x Outlet Inlet x Outlet in. mm 1/2 x 1/2 12 x 12 1/2 x 5/8 12 x 16 5/8 x 1/2 16 x 12 5/8 x 5/8 16 x 16 5/8 x 7/8 16 x 22 7/8 x 7/8 22 x 22 7/8 x 1-1/8 22 x 28 5/8 x 5/8 16 x 16 5/8 x 7/8 16 x 22 7/8 x 7/8 22 x 22 7/8 x 1-1/8 22 x 28 7/8 x -3/8 22 x 35 1-1/8 x 7/8 28 x 22 1-1/8 x 1-1/8 28 x 28 1-1/8 x 1-3/8 28 x 35 7/8 x 7/8 22 x 22 7/8 x 1-1/8 22 x 28 7/8 x 1-3/8 22 x 35 1-1/8 x 1-1/8 28 x 28 1-1/8 x 1-3/8 28 x 35 1-1/8 x 1-5/8 28 x 42 1-1/8 x 1-1/8 28 x 28 1-1/8 x 1-3/8 28 x 35 1-1/8 x 1-5/8 28 x 42 1-3/8 x 1-3/8 35 x 35 1-3/8 x 1-5/8 35 x 42

Capillary Tube Length (ft)

H1 (in.)

H2 (in.)

H3 (in.)

H4 (in.)

L1 (in.) 1.59

4.09 4.92

1.26

0.30

0.20

1.79 3.231)

2.03 1.89

4.80 4.92

1.46

0.35

2.13

0.31 3.941)

5.71 11.76

11.76

1.65

1.85

0.51

0.67

2.40

2.26

0.43 5.04

2.54

6.50

2.64

0.51 5.83

3.03

L2 (in.) 1.59 1.79 1.59 1.79 2.03 2.03 2.31 1.89 2.13 2.13 2.40 2.80 2.13 2.40 2.80 2.26 2.54 2.93 2.54 2.93 3.25 2.64 3.03 3.35 3.03 3.35

L3 (in.)

L4 (in.)

øD1 (in.)

øD2 (in.)

Weight (lbs)

0.86 1.36

2.76

1.77

0.59 0.771)

1.32 1.50

4.69

2.09

0.65 1.231)

1.74 1.61

4.37

2.36

0.80 2.051)

2.95 1.73

5.83

2.83

0.80 2.871)

setting.

953

ELECTRONIC EXPANSION VALVE - PWM DANFOSS AKV 1O Introduction

The Danfoss AKV 10 is an electronic expansion valve designed for commercial refrigeration systems using all types of HFC and HCFC refrigerants. Danfoss can also supply an AKVA 10 version for use with ammonia. The refrigerants for which the AKV 10 is approved are given in the Technical Data section. The AKV 10 functions as an expansion valve and as a solenoid valve.

The AKV 10 valves cover a nominal capacity range from 0.3 to 5.7 tons (R-22). An individual valve is effective over a part of that range depending on which of 8 available orifices is specified. The complete type designation of the valve includes the orifice number, so that a valve with orifice 3 would be designated AKV 10-3.

Availability

AKV 10 valves are supplied complete or as components, as follows: • Complete valve (shipped with coil dismounted from valve)

• Valve without coil • Coil with conduit boss • Spare parts: coil; armature; orifice; filter

Applications

For all evaporators up to a maximum refrigeration capacity of 7 Tons (R-22). Designed for optimal control by Danfoss ADAP-KOOL® system controllers, the AKV 10’s selection of coils make it suitable for use with practically any control system.

Advantages

• Life tested to 50,000,000 cycles

• Wide range of capacities

• Hydraulic damping function minimizes liquid line pulsation

• Easily disassembled

• Normally closed fail-safe design • Use with any fluorinated refrigerant (contact Danfoss for information on AKVA 10 valves for ammonia)

Nominal Capacities

• Orifice and screen are replaceable • When you change refrigerants, simply change the orifice (if necessary).

Te = 40° F

AKV 10-1 AKV 10-2 AKV 10-3

R-22 Tr 0.3 0.5 0.7

R-502 Tr 0.2 0.3 0.5

R-134a Tr 0.2 0.4 0.6

R-404A Tr 0.2 0.3 0.6

R-507 Tr 0.2 0.3 0.6

Tc = 90° F

AKV 10-4

1.1

0.8

0.9

0.9

0.9

Tl = 82° F

AKV 10-5 AKV 10-6 AKV 10-7 AKV 10-8

1.8 2.8 4.5 5.7

1.3 2.0 3.2 3.9

1.4 2.2 3.6 4.4

1.4 2.2 3.5 4.3

1.5 2.4 3.8 4.8

AKV 10-n

Nominal capacities of AKV 10. It is important to size valves using the method found in the AKV Sizing section.

954

ELECTRONIC EXPANSION VALVE - PWM DANFOSS Pressure 30 Drop (psig) R-22 Capacities in tons Capacity, AKV10-1

60

90

115

145

175

200

Pressure 30 60 Drop (psig) R-404A Capacities in tons

235

Range: -40° F to 50° F

90

115

145

175

200

235

Range: -40° F to 50° F

Capacity, AKV10-1

Capacity, AKV10-2

0.21 0.26 0.29 0.31 0.34 0.34 0.34 0.35 0.32 0.41 0.47 0.51 0.51 0.54 0.53 0.58

Capacity, AKV10-2

0.16 0.23 0.23 0.25 0.25 0.25 0.25 0.22 0.26 0.32 0.36 0.37 0.37 0.38 0.37 0.38

Capacity, AKV10-3

0.53 0.68 0.76 0.79 0.82 0.86 0.84 0.86

Capacity, AKV10-3

0.42 0.52 0.58 0.59 0.59 0.60 0.58 0.60

Capacity, AKV10-4

0.82 1.06 1.20 1.24 1.31 1.34 1.34 1.41

Capacity, AKV10-4

0.68 0.84 0.94 0.93 0.97 0.97 0.92 0.95

Capacity, AKV10-5

1.29 1.67 1.88 1.97 2.04 2.14 2.13 2.22

Capacity, AKV10-5

1.03 1.33 1.45 1.46 1.50 1.51 1.48 1.49

Capacity, AKV10-6

2.06 2.64 3.00 3.10 3.27 3.37 3.39 3.51

Capacity, AKV10-6

1.65 2.10 2.29 2.32 2.41 2.42 2.34 2.34

Capacity, AKV10-7

3.29 4.23 4.79 4.96 5.23 5.43 5.40 5.61

Capacity, AKV10-7

2.65 3.36 3.68 3.72 3.84 3.86 3.76 3.77

Capacity, AKV10-8

4.11 5.29 5.99 6.19 6.52 6.76 6.74 7.00

Capacity, AKV10-8

3.31 4.19 4.60 4.63 4.80 4.83 4.68 4.68

R-134a Capacities in tons Capacity, AKV10-1

Range: -40° F to 50° F

R-507 Capacities in tons

Range: -40° F to 50° F

Capacity, AKV10-1

Capacity, AKV10-2

0.18 0.24 0.26 0.25 0.26 0.26 0.25 0.26 0.26 0.35 0.41 0.39 0.43 0.43 0.42 0.43

Capacity, AKV10-2

0.17 0.24 0.24 0.26 0.26 0.26 0.26 0.23 0.27 0.34 0.37 0.39 0.39 0.39 0.39 0.40

Capacity, AKV10-3

0.44 0.56 0.62 0.65 0.65 0.69 0.67 0.66

Capacity, AKV10-3

0.44 0.54 0.61 0.62 0.62 0.62 0.61 0.63

Capacity, AKV10-4

0.71 0.88 1.00 1.01 1.05 1.09 1.06 1.06

Capacity, AKV10-4

0.71 0.88 0.98 0.97 1.01 1.02 0.97 0.99

Capacity, AKV10-5

1.09 1.41 1.56 1.60 1.68 1.69 1.65 1.70

Capacity, AKV10-5

1.08 1.39 1.52 1.52 1.57 1.58 1.54 1.55

Capacity, AKV10-6

1.73 2.23 2.50 2.53 2.64 2.69 2.63 2.68

Capacity, AKV10-6

1.72 2.20 2.40 2.43 2.51 2.53 2.45 2.45

Capacity, AKV10-7

2.76 3.56 3.97 4.05 4.23 4.28 4.20 4.29

Capacity, AKV10-7

2.77 3.51 3.85 3.89 4.02 4.04 3.93 3.94

Capacity, AKV10-8

3.48 4.47 4.98 5.07 5.27 5.37 5.26 5.34

Capacity, AKV10-8

3.46 4.38 4.81 4.84 5.02 5.05 4.89 4.90

R-502 Capacities in tons Capacity, AKV10-1

Range: -40° F to 50° F

Capacity, AKV10-2

0.15 0.21 0.21 0.23 0.23 0.23 0.22 0.20 0.24 0.29 0.32 0.34 0.34 0.34 0.34 0.35

Capacity, AKV10-3

0.38 0.47 0.53 0.53 0.54 0.54 0.53 0.55

Capacity, AKV10-4

0.62 0.76 0.85 0.84 0.88 0.89 0.84 0.86

Capacity, AKV10-5

0.94 1.20 1.32 1.32 1.36 1.37 1.34 1.35

Capacity, AKV10-6

1.50 1.91 2.09 2.11 2.19 2.20 2.13 2.13

Capacity, AKV10-7

2.41 3.06 3.35 3.38 3.49 3.51 3.41 3.42

Capacity, AKV10-8

3.01 3.81 4.18 4.21 4.36 4.39 4.25 4.26

Correction for Subcooling

Factor for R-502

0 1.10 1.10

7.2 1.00 1.00

18 0.91 0.91

27 0.87 0.87

36 0.83 0.80

45 0.80 0.77

54 0.77 0.71

63 0.74 0.69

72 0.71 0.67

Factor for R-134a

1.10

1.00

0.91

0.87

0.83

0.80

0.77

0.71

0.67

Factor for R-404A

1.10

1.00

0.93

0.87

0.82

0.77

0.73

0.70

0.66

Factor for R-507

1.10

1.00

0.93

0.87

0.81

0.77

0.72

0.69

0.65

Subcooling (°F) Factor for R-22

Contact Danfoss for information on other refrigerants.

955

MOISTURE LIQUID INDICATORS DANFOSS SIGHT GLASSES INTRODUCTION Danfoss sight glasses are designed to accurately indicate the presence of moisture in refrigeration and air-conditioning systems. When system moisture content rises above permissible levels, the “dry/green” indicator will change to yellow indicating a “wet” system. The indication of dangerous moisture levels is essential in helping prevent the formation of harmful acids which are detrimental to the system. Danfoss offers two types of sight glasses: inline and vessel mount. Inline sight glass types SGI and SGN are used in the systems liquid line to indicate both the condition and moisture content of the refrigerant. They incorporate an indicator which changes color dependent on the moisture content. Type SGI is optimized for use with all CFC refrigerants while type SGN is recommended for all HCFC and HFC refrigerants. Vessel sight glass types SGR, SGRI and SGRN are specially designed to be mounted directly on either a receiver or the compressor crankcase to indicate liquid level. Types SGRI and SGRN are available with a refrigerant moisture indicator which can be used with all fluorinated refrigerants. Refrigerant recommendations for the indicator type (I and N) are similar to the inline versions.

P990

FEATURES • Provides fast and easy indication of: - High system moisture content. - Lack of subcooling or low system charge. - Liquid level (vessel mount versions only). • Two indicator types: - Type “I” provides optimal moisture indication for all CFC refrigerants. - Type “N” provides optimal moisture indication for all HCFC and HFC refrigerants. • All indicators are dirt resistant. • Available in both inline and vessel mount versions. • Hermetically sealed, tempered glass for easy viewing. • Available in both flare and solder versions.

APPROVALS UL listed, file SA 652. CSA Certified, LR 55874.

TECHNICAL DATA Refrigerants: SGI/SGRI: CFC SGN/SGRN: HFC and HCFC Ambient Temperature: -60° F → 175° F Maximum Working Pressure: SGI/SGN: 6 → 12: MWP = 500 psig SGI/SGN: 16s (solder): MWP = 500 psig SGI/SGN: 16 (flare): MWP = 400 psig SGI/SGN 19 → 22: MWP = 400 psig SGR/SGRI/SGRN: MWP = 500 psig

956

P990D

MOISTURE LIQUID INDICATORS DANFOSS SIGHT GLASSES SELECTION Prior to selecting a sightglass with moisture indicator, the following should be considered: • Type of refrigerant. • Water solubility of refrigerant. • The level at which a danger signal is required to prevent the formation of harmful acids. The following tables indicate moisture content levels at which the sightglass indicator will register a dry or wet system for various refrigerants. The values under “green /dry” are to be taken as the maximum permissible moisture content for the system. When the green color begins to fade indicating an increase in moisture levels, the sightglass should be checked more frequently. If the moisture levels increase enough to change the indicator to “yellow” indicating a wet system, the filter drier must be changed immediately.

CFC Refrigerants

Green/ Dry 140 230 50 90

*The values refer to liquid temperature. NOTE: For moisture values of other refrigerants, please contact Danfoss.

HCFC Refrigerants MOISTURE CONTENT PPM = PARTS PER MILLION SGN (Recommended) 110° F* 77° F* 110° F* Green/ Intermed. Yellow/ Green/ Intermed. Yellow/ Green/ Intermed. Dry Color Wet Dry Color Wet Dry Color 500 120 200

*The values refer to liquid temperature. NOTE: For moisture values of other refrigerants, please contact Danfoss.

HFC Refrigerants MOISTURE CONTENT PPM = PARTS PER MILLION SGN (Recommended) 110° F* 77° F* 110° F* Green/ Intermed. Yellow/ Green/ Intermed. Yellow/ Green/ Intermed. Dry Color Wet Dry Color Wet Dry Color 430 100 100 >225 >110

*The values refer to liquid temperature.

957

MOISTURE LIQUID INDICATORS DANFOSS SIGHT GLASSES Ordering SGI, SGR AND SGRI TYPE

P990B

SGI 6 SGI 10 SGI 12 SGI 16 SGI 6 SGI 10 SGI 12 SGI 16 SGI 6s SGI 10s SGI 12s SGI 16s SGI 22s SGI 6s SGI 10s SGI 12s SGI 16s SGI 22s SGR 1/2 SGR 3/4 SGRI 1/2

VERSION Flare ext. x ext.

Flare* int. x ext.

ODF x ODF solder

ODF x ODM solder NPT NPT NPT

SGN AND SGRN CONNECTION (in.) 1/4 x 1/4 3/8 x 3/8 1/2 x 1/2 5/8 x 5/8 1/4 x 1/4 3/8 x 3/8 1/2 x 1/2 5/8 x 5/8 1/4 x 1/4 3/8 x 3/8 1/2 x 1/2 5/8 x 5/8 7/8 x 7/8 1/4 x 1/4 3/8 x 3/8 1/2 x 1/2 5/8 x 5/8 7/8 x 7/8 1/2 3/4 1/2

P/N

TYPE

14-0060 14-0061 14-0062 14-0157 14-0063 14-0064 14-0065 14-0072 14-0066 14-0067 14-0068 14-0069 14-0070 14-0118 14-0119 14-0120 14-0121 14-0123 14-0013 14-0071 14-0131

SGN 6 SGN 10 SGN 12 SGN 16 SGN 6 SGN 10 SGN 12 SGN 16 SGN 6s SGN 10s SGN 12s SGN 16s SGN 22s SGN 6s SGN 10s SGN 12s SGN 16s SGN 22s SGRN

VERSION Flare ext. x ext.

Flare* int. x ext.

ODF x ODF solder

ODF x ODM solder NPT

CONNECTION (in.) 1/4 x 1/4 3/8 x 3/8 1/2 x 1/2 5/8 x 5/8 1/4 x 1/4 3/8 x 3/8 1/2 x 1/2 5/8 x 5/8 1/4 x 1/4 3/8 x 3/8 1/2 x 1/2 5/8 x 5/8 7/8 x 7/8 1/4 x 1/4 3/8 x 3/8 1/2 x 1/2 5/8 x 5/8 7/8 x 7/8 1/2

P/N 14-0132 14-0133 14-0134 14-0135 14-0137 14-0138 14-0139 14-0140 14-0142 14-0143 14-0144 14-0145 14-0147 14-0151 14-0152 14-0153 14-0154 14-0156 14-0006

*Can be screwed directly onto the Danfoss filter drier.

*Can be screwed directly onto the Danfoss filter drier.

Dimensions and Weights

P990C TYPE SGI/SGN 6 SGI/SGN 10 SGI/SGN 12 SGI/SGN 16 SGI/SGN 6 SGI/SGN 10 SGI/SGN 12 SGI/SGN 16 SGI/SGN 6s SGI/SGN 10s SGI/SGN 12s SGI/SGN 16s SGI/SGN 22s SGI/SGN 6s SGI/SGN 10s SGI/SGN 12s SGI/SGN 16s SGI/SGN 22s SGR 1/2 SGR 3/4 SGRI/SGRN 1/2

958

VERSION Flare ext. x ext.

Flare int. x ext.

ODF x ODF solder

ODF x ODM solder NPT NPT NPT

L (in.) 2.638 3.228 3.465 4.094 1.811 2.244 2.323 2.795 3.976 4.685 5.748 5.748 6.811 3.976 4.685 5.748 5.748 6.811

L1 (in.)

0.276 0.354 0.394 0.472 0.699 0.276 0.354 0.394 0.472 0.699

H (in.) 0.945 1.102 1.181 1.457 0.945 1.181 1.181 1.457 0.945 0.945 1.102 1.181 1.457 0.945 0.945 1.102 1.181 1.457 1.181 1.220 1.181

H1 (in.) 0.551 0.630 0.709 0.827 0.551 0.709 0.709 0.827 0.551 0.551 0.630 0.709 0.827 0.551 0.551 0.630 0.709 0.827 0.709 0.709 0.709

B1 (in.) 0.551 0.748 0.866 1.063 0.630 0.866 0.945 1.063 0.551 0.551 0.748 0.866 1.063 0.551 0.551 0.748 0.866 1.063 1.063 1.260 1.063

DIM D (in.) 1.063 1.260 1.260 1.457 1.063 1.260 1.260 1.457 1.063 1.063 1.260 1.260 1.457 1.063 1.063 1.260 1.260 1.457

WEIGHT (lb) 0.22 0.44 0.66 0.88 0.22 0.44 0.66 0.88 0.22 0.22 0.44 0.44 0.44 0.22 0.22 0.44 0.44 0.44 0.22 0.22 0.22

PURON DRIERS CARRIER PURON APPROVED LIQUID LINE FILTER DRIERS CARRIER PART NUMBER APPLICATION KH43LG072 Heat Pump KH43LG073 AC KH43LG074 AC KH43LG075 AC NOTE: Capacity based on 1 PSI Delta P at ARI Standards

CAPACITY 5 Tons 4 Tons 5 Tons 6 Tons

SIZE 16.5 cu. in. 8 cu. in. 16 cu. in. 30 cu. in.

CARRIER PURON APPROVED SUCTION LINE FILTER DRIERS CARRIER PART NUMBER KH45LG140 KH45LG141

SIZE 8 cu. in. 13 cu. in.

CONNECTION SIZE ID IN. 3/4″ 7.8″

959

PRESSURE REGULATORS DANFOSS HOT-GAS BYPASS REGULATORS, TYPE CPCE LIQUID-GAS MIXERS, TYPE LG A liquid-gas mixer type LG should be used for hot-gas injection. The object of the LG is to create a monogeneous mixture of the hot-gas from the CPCE regulator and the liquid from the thermostatic expansion valve so that the function of the liquid distributor (next in the system) remains unimpaired.

TYPE LG 12/16 LG 12/22 LG 16/28 LG 22/35

CONNECTION FOR EXPANSION LIQUID HOT-GAS VALVE DISTRIBUTOR (in.) ODM (in.) ODM (in.) ODF 5/8 1/2 5/8 7/8 1/2 7/8 1-1/8 5/8 1-1/8 1-3/8 7/8 1-3/8

P/N 472-4001 472-4002 472-4003 472-4004

The liquid-gas mixer type LG can also be used in connection with hot-gas defrosting or with reverse cycle systems.

DANFOSS HEAT RECOVERY REGULATORS, HEAD PRESSURE REGULATORS, TYPE KVR, DIFFERENTIAL PRESSURE VALVES, TYPE NRD Consequently, the condenser is partially filled with liquid, so that the effective condensing surface is reduced. In this way the required condensing pressure is restored. Since the real regulation task during winter operation is to keep the receiver pressure at a suitably high value, KVR is combined with a differential pressure valve type NRD, which is sitted in the bypass line shown. NRD begins to open at a differential pressure of 20 psi. When the condensing pressure falls, KVR will begin to throttle. This increases the total pressure drop across the condenser + KVR. When this pressure drop reaches 20 psi, NRD will begin to open thus ensuring that the receiver pressure is maintained. As a rule of thumb, it can be assumed that the pressure in the receiver is equal to the set pressure of the KVR less 14 psi.

P278 P392

Regulator systems KVR + NRD are used to maintain a constant and sufficiently high condensing and receiver pressure in systems with heat recovery or in refrigeration and air conditioning systems with air-cooled condensers.

During summer operation, when the KVR is fully open, the total pressure drop across the condenser and KVR is less than 20 psi. The NRD is therefore closed. To avoid inadvertent opening of the NRD the pressure drop across the condenser at max. load must not exceed 10 psi. If this pressure is exceeded, two NRD units can be used in series instead of one.

During winter operation the ambient temperature falls and with During summer operation the charge can accumulate in the it the condensing pressure of the air-cooled condenser falls. receiver. Therefore the system must be equipped with a sufficiently KVR-regulation is dependent on the inlet pressure. It begins to large receiver to store the excess refrigerant. throttle when the pressure falls below the pressure setting.

TECHNICAL DATA TYPE

REFRIGERANTS

KVR 12, 15, 22 KVR 28, 35 NRD

R-12, R-22, R-502* R-12, R-22, R-502* R-12, R-22, R-502*

REGULATION RANGE (BEGINNING TO OPEN) (psig) 70 to 285 70 to 250 —

OPENING DIFFERENTIAL PRESSURE ∆P PSI BEGINNING COMPLETELY OPEN OPEN — — — — 20 43

MAX. TEMPERATURE (°F) +265** +265** +275

MAX. OPERATING PRESSURE (SWIP) (psig) 305 275 350

MAX. TEST PRESSURE (psig) 400 355 455

*Other fluorinated refrigerants, for example R-500, can be used at the stated temperatures and pressures. **Provided that the Schraeder valve is removed and the connector is sealed with seal cap and nut — otherwise +200° F.

ORDERING TYPE KVR 12 KVR 15 KVR 22 KVR 28 KVR 35 NRD

NOMINAL LIQUID CAPACITY (TONS) R-12 R-22 R-502 11.0 14.5 9.0 11.0 14.5 9.0 11.0 14.5 9.0 28.0 36.5 24.0 28.0 36.5 24.0 — — —

NOMINAL HOT-GAS CAPACITY (TONS)* R-12 R-22 R-502 3.0 4.0 3.0 3.0 4.0 3.0 3.0 4.0 3.0 7.5 10.0 8.0 7.5 10.0 8.0 — — —

FLARE CONNECTION SOLDER CONNECTION (in.) SAE P/N (in.) ODF P/N 1/2 481-0091 1/2 481-0093 5/8 481-0092 5/8 481-0097 — — 7/8 481-0094 — — 1-1/8 481-0095 — — 1-3/8 481-0100 — — 1/2 482-1132

*The rated capacity is the regulator capacity at evaporating temperature to = +40° F concerning liquid and 0° F concerning hot-gas, condensing temperature tk = +100° F and pressure drop across the valve ∆p = 3 p.

960

EVAPORATOR PRESSURE REGULATORS DANFOSS EVAPORATOR PRESSURE REGULATORS INTRODUCTION KVP evaporator pressure regulators are mounted in the suction line of refrigeration and air conditioning systems. They are used to maintain a constant pressure corresponding to a constant temperature on the evaporator. They also protect against too low an evaporating pressure by throttling down when pressure falls below the set value. They are also used to differentiate the evaporating pressures in two or more evaporators in systems with one compressor.

FEATURES • • • • • • • • •

Accurate, adjustable pressure regulation. Wide capacity and operating range. Pulsation damping design. Stainless steel bellows. Compact angle design for easy installation in any position. “Hermetic" brazed construction. 1/4 in. Schrader valve for pressure testing. Available with flare and ODF solder connections. For use with CFC, HCFC and HFC refrigerants.

P4311

APPROVALS UL listed, file SA7200. CSA approved.

TECHNICAL DATA Refrigerants: CFC, HCFC, HFC Regulation range: 0 to 80 psig Factory setting = 29 psig

P4311A

Maximum working pressure: MWP = 200 psig Maximum test pressure: KVP 12 to 22: p′ = 410 psig KVP 28 to 35: p′ = 370 psig Maximum temperature of medium: 212° F* Minimum temperature of medium: – 40° F* P band (full valve stroke): KVP 12 to 22 = 26 psi KVP 28 to 35 = 40 psi *If the Schrader valve cone is removed and the connector is sealed with cap and nut, the maximum temperature is 300° F and the minimum temperature is – 330° F.

961

EVAPORATOR PRESSURE REGULATORS DANFOSS EVAPORATOR PRESSURE REGULATORS ORDERING TYPE KVP 12 KVP 15 KVP 22 KVP 28 KVP 35

R-22 1.3 1.3 1.3 2.8 2.8

RATED CAPACITY* (Tons) R-134a R-404A/R-507 0.9 1.2 0.9 1.2 0.9 1.2 1.9 2.4 1.9 2.4

FLARE CONNECTION† in. Code No 1/2 034L0021 5/8 034L0022

R-407C 1.2 1.2 1.2 2.6 2.6

SOLDER CONNECTION in. ODF Code No. 1/2 034L0023 5/8 034L0029 7/8 034L0025 1-1/8 034L0026 1-3/8 034L0032

*Rated capacity is based on: Evaporating temperature te = 40° F Condensing temperature tc = 100° F Pressure drop across regulator ∆p = 2 psi Offset (design evaporating pressure minus minimum allowable evaporator pressure) = 9 psi. †KVP supplied without flare nuts. Separate flare nuts can be supplied: 1/2 in., code no. 011L1103 5/8 in., code no. 011L1167 NOTE: The connection dimensions chosen must not be too small, as gas velocities in excess of 130 ft/s at the inlet of the regulator can result in flow noise.

CAPACITY Maximum Regulator Capacity Qe* TYPE KVP 12 KVP 15 KVP 22

KVP 28 KVP 35

PRESSURE DROP ACROSS REGULATOR ∆p psi 2 4 6 10 20 2 4 6 10 20

R-22 CAPACITY Qe IN TONS AT EVAPORATING TEMPERATURE te °F –20

–10

0

10

20

30

40

50

60

70

0.6 0.9 1.0 1.1 1.1 1.4 1.9 2.1 2.4 2.4

0.7 1.0 1.2 1.4 1.4 1.6 2.2 2.5 2.9 3.0

0.8 1.1 1.3 1.6 1.8 1.8 2.5 2.9 3.5 3.8

0.9 1.3 1.5 1.9 2.2 2.0 2.8 3.3 4.0 4.7

1.0 1.4 1.7 2.1 2.6 2.3 3.1 3.8 4.6 5.6

1.2 1.6 1.9 2.4 3.0 2.5 3.5 4.2 5.2 6.6

1.3 1.8 2.2 2.7 3.5 2.8 3.9 4.7 5.8 7.5

1.4 2.0 2.4 3.0 3.9 3.1 4.3 5.2 6.5 8.5

1.5 2.2 2.6 3.3 4.4 3.4 4.7 5.7 7.2 9.6

1.7 2.4 2.9 3.6 4.9 3.7 5.2 6.3 7.9 10.6

R-134a

Maximum Regulator Capacity Qe* TYPE KVP 12 KVP 15 KVP 22

KVP 28 KVP 35

PRESSURE DROP ACROSS REGULATOR ∆p psi 2 4 6 10 20 2 4 6 10 20

CAPACITY Qe IN TONS AT EVAPORATING TEMPERATURE te °F 10

20

30

40

50

60

70

0.6 0.8 0.9 1.0 1.0 1.3 1.7 2.0 2.2 2.2

0.7 0.9 1.0 1.2 1.3 1.5 2.0 2.3 2.7 2.8

0.8 1.0 1.2 1.5 1.6 1.7 2.3 2.7 3.2 3.5

0.9 1.2 1.4 1.7 2.0 1.9 2.6 3.1 3.7 4.4

1.0 1.3 1.6 2.0 2.4 2.1 2.9 3.5 4.3 5.2

1.1 1.5 1.8 2.2 2.8 2.4 3.3 3.9 4.9 6.1

1.2 1.7 2.0 2.5 3.3 2.6 3.6 4.4 5.5 7.1

*The capacities are based on: Liquid temperature ahead of expansion valve Regulator offset

962

tl = 100° F ∆p = 9 psi

EVAPORATOR PRESSURE REGULATORS DANFOSS EVAPORATOR PRESSURE REGULATORS CAPACITY (cont)

R-404A and R-507

Maximum Regulator Capacity Qe* TYPE KVP 12 KVP 15 KVP 22

KVP 28 KVP 35

PRESSURE DROP ACROSS REGULATOR ∆p psi 2 4 6 10 20 2 4 6 10 20

CAPACITY Qe IN TONS AT EVAPORATING TEMPERATURE te °F –30

–20

–10

0

10

20

30

40

50

60

70

0.5 0.6 0.7 0.8 0.8 1.0 1.3 1.5 1.7 1.7

0.5 0.7 0.8 1.0 1.0 1.1 1.5 1.8 2.1 2.1

0.6 0.8 1.0 1.2 1.3 1.3 1.8 2.1 2.5 2.7

0.7 0.9 1.1 1.3 1.6 1.5 2.0 2.4 2.9 3.4

0.8 1.1 1.3 1.6 1.9 1.8 2.4 2.9 3.5 4.3

0.9 1.3 1.5 1.9 2.3 2.0 2.7 3.2 4.1 5.2

1.1 1.4 1.7 2.0 2.7 2.2 3.1 3.7 4.6 5.9

1.2 1.6 1.9 2.4 3.2 2.4 3.4 4.1 5.2 6.8

1.3 1.8 2.1 2.8 3.6 2.8 3.9 4.7 5.9 7.8

1.4 1.9 2.4 3.0 4.1 3.0 4.3 5.1 6.5 8.8

1.5 2.2 2.6 3.4 4.5 3.4 4.8 5.7 7.2 9.8

Maximum Regulator Capacity Qe* TYPE KVP 12 KVP 15 KVP 22

KVP 28 KVP 35

*The

R-407C

PRESSURE DROP ACROSS REGULATOR ∆p psi 2 4 6 10 20 2 4 6 10 20

CAPACITY Qe IN TONS AT EVAPORATING TEMPERATURE te °F –20

–10

0

10

20

30

40

50

60

70

0.5 0.7 0.8 0.9 0.9 1.1 1.5 1.7 1.9 1.9

0.6 0.9 1.0 1.1 1.1 1.3 1.8 2.1 2.4 2.5

0.7 0.9 1.1 1.4 1.5 1.5 2.1 2.5 3.0 3.2

0.8 1.1 1.3 1.6 1.9 1.7 2.4 2.8 3.4 4.0

0.9 1.2 1.5 1.9 2.3 2.0 2.7 3.3 4.0 4.9

1.0 1.4 1.7 2.2 2.7 2.3 3.2 3.8 4.7 5.9

1.2 1.7 2.0 2.5 3.2 2.6 3.6 4.3 5.3 6.9

1.3 1.9 2.3 2.8 3.7 2.9 4.0 4.9 6.1 8.0

1.4 2.1 2.5 3.1 4.2 3.2 4.5 5.4 6.8 9.1

1.7 2.3 2.8 3.5 4.8 3.6 5.0 6.1 7.7 10.3

capacities are based on:

Liquid temperature ahead of expansion valve tl = 100° F Regulator offset ∆p = 9 psi

Correction factors for liquid temperature tl tl °F R-22 R-134a R-404A/R-507 R-407C

50 0.82 0.79 0.71 0.78

60 0.85 0.82 0.75 0.81

70 0.88 0.86 0.80 0.85

80 0.92 0.90 0.85 0.89

90 0.96 0.95 0.92 0.94

100 1.0 1.0 1.0 1.0

110 1.05 1.06 1.10 1.07

21

120 1.10 1.13 1.24 1.15

Correction factors for offset OFFSET PSI KVP 12 KVP 15 KVP 22 KVP 28 KVP 35

3

6

9

12

15

18

2.5

1.4

1

0.77

0.67

0.59

1.4

1

0.77

0.67

0.59

0.53

963

EVAPORATOR PRESSURE REGULATORS DANFOSS EVAPORATOR PRESSURE REGULATORS Dimensions and Weights

P4311B

TYPE KVP 12 KVP 15 KVP 22 KVP 28 KVP 35

964

CONNECTION Flare Solder ODF (in.) (in.) 1/2 1/2 5/8 5/8 7/8 1-1/8 1-3/8

NV1 (in.)

NV2 (in.)

H1 (in.)

H2 (in.)

H3 (in.)

B1 (in.)

B2 (in.)

C (in.)

DIA. D (in.)

WEIGHT (lbs)

0.748 0.748 0.945 0.945

0.945 0.945 0.945 0.945

7.047 7.047 7.047 10.197 10.197

3.898 3.898 3.898 5.945 5.945

2.598 2.598 2.598 4.055 4.055

2.520 2.520 2.520 4.134 4.134

1.614 1.614 1.614 1.890 1.890

0.394 0.472 0.669 0.787 0.984

1.181 1.181 1.181 1.693 1.693

0.9 0.9 0.9 2.0 2.0

CONDENSER PRESSURE REGULATORS DANFOSS CONDENSER PRESSURE REGULATORS INTRODUCTION KVR condenser regulators can be mounted in either the gas or liquid side of the condenser in refrigeration and air conditioning systems. They are used to maintain a constant and sufficiently high condensing pressure with systems using air-cooled condensers. They can also be used with valve types NRD or KVD to assure that adequate pressure is maintained on the receiver.

FEATURES • Accurate, adjustable pressure regulation • Wide capacity and operating range • Pulsation damping design • Stainless steel bellows • Compact angle design for easy installation in any position

P4312

• "Hermetic" brazed construction • 1/4-in. Schrader valve for pressure testing • Available with flare and ODF solder connections • For use with CFC, HCFC and HFC refrigerants • Can be used as a relief valve from high pressure to suction side

APPROVALS UL listed, file SA7200. CSA approved.

TECHNICAL DATA Refrigerants: CFC, HCFC, HFC Regulation range: 70 to 250 psig P4312A

Factory setting = 145 psig Maximum working pressure: Maximum test pressure:

KVR: MWP = 400 psig NRD: MWP = 400 psig KVR: p' = 450 psig NRD: p' = 530 psig

Maximum temperature of medium: KVR: 212° F* NRD: 275° F Minimum temperature of medium: – 40° F P band (full valve stroke): KVR 12 to 22: 90 psi KVR 28 to 35: 72.5 psi Opening differential pressure for NRD: Fully open: ∆p = 43 psi *If the Schrader valve cone is removed and the connector is sealed with cap and nut, the maximum temperature is 265° F.

965

CONDENSER PRESSURE REGULATORS DANFOSS CONDENSER PRESSURE REGULATORS CAPACITY Maximum regulator capacity Qe* TYPE

CONDENSING TEMPERATURE tc (°F)

LIQUID CAPACITY IN TONS (Evaporator Capacity) Offset 45 psi Pressure Drop ∆ psi 1.5 3 6 10 25

HOT GAS CAPACITY IN TONS (Evaporator Capacity) Offset 45 psi Pressure Drop ∆p psi 1.5 3 6 10 25

R-22 KVR 12 KVR 15 KVR 22

KVR 28 KVR 35

50 70 90 110 130 50 70 90 110 130

13.1 11.9 10.6 9.2 7.8 33.5 30.4 27.1 23.6 20.0

17.6 16.0 14.4 12.7 11.0 45.0 41.1 37.0 32.6 28.0

25.2 23.0 20.8 18.4 16.0 64.4 58.9 53.2 47.2 40.9

32.9 30.0 27.0 23.9 20.7 84.2 76.8 69.2 61.3 53.0

52.6 48.0 43.2 38.2 33.1 134.6 122.8 110.6 97.8 84.6

R-22 1.81 1.92 2.04 2.13 2.20 4.77 5.11 5.42 5.67 5.79

2.47 2.62 2.76 2.89 2.98 6.50 6.93 7.34 7.65 7.83

3.52 3.75 3.96 4.13 4.27 9.31 9.92 10.48 10.93 11.23

4.51 4.83 5.12 5.36 5.54 11.95 12.79 13.54 14.16 14.60

6.86 7.44 7.94 8.34 8.64 18.15 19.66 20.98 22.06 22.85

Maximum regulator capacity Qe* TYPE

CONDENSING TEMPERATURE tc (°F)

LIQUID CAPACITY IN TONS (Evaporator Capacity) Offset 45 psi Pressure Drop ∆ psi 1.5 3 6 10 25

HOT GAS CAPACITY IN TONS (Evaporator Capacity) Offset 45 psi Pressure Drop ∆p psi 1.5 3 6 10 25

R-134a KVR 12 KVR 15 KVR 22

KVR 28 KVR 35

50 70 90 110 130 50 70 90 110 130

12.0 11.9 9.6 8.4 7.1 30.7 27.6 24.5 21.4 18.1

16.9 16.0 13.6 11.8 10.0 43.4 39.1 34.7 30.2 25.6

24.0 23.0 19.2 16.7 14.2 61.3 55.3 49.1 42.8 36.3

31.0 30.0 24.8 21.6 18.3 79.2 71.4 63.4 55.3 46.9

50 70 90 110 130 50 70 90 110 130

9.2 8.1 7.0 5.9 4.8 23.6 20.8 17.9 15.1 12.3

12.4 10.9 9.6 8.2 6.8 31.7 27.9 24.5 20.9 17.4

17.6 15.7 13.8 11.8 10.0 45.2 40.1 35.2 30.3 25.7

23.0 20.4 17.9 15.4 13.0 59.0 52.2 45.9 39.3 33.1

50 70 90 110 130 50 70 90 110 130

4.2 12.9 11.5 10.0 8.6 36.2 32.8 29.3 25.7 22.0

19.0 17.3 15.6 13.8 12.1 48.6 44.4 40.0 35.5 30.8

27.2 24.8 22.5 20.1 17.6 69.6 63.6 57.5 51.5 45.0

35.5 32.4 29.2 26.1 22.8 90.9 82.9 74.7 66.8 58.3

49.1 48.0 39.3 34.2 29.0 126.0 113.0 100.0 87.5 74.2

R-134a 1.40 1.92 1.50 1.53 1.52 3.72 3.87 3.99 4.06 4.03

1.97 2.62 2.12 2.15 2.14 5.24 5.44 5.62 5.71 5.68

2.75 3.75 2.97 3.03 3.01 7.31 7.63 7.89 8.04 8.00

3.50 4.83 3.80 3.87 3.86 9.26 9.71 10.07 10.28 10.25

1.63 1.60 1.65 1.68 1.69 4.06 4.24 4.41 4.88 4.49

2.09 2.17 2.25 2.28 2.31 5.52 5.74 5.96 6.06 6.12

2.99 3.10 3.21 3.27 3.34 7.89 8.20 8.50 8.66 8.82

3.84 4.00 4.15 4.24 4.34 10.15 10.58 10.99 11.22 11.45

1.96 2.07 2.20 2.32 2.42 5.15 5.52 5.85 6.18 6.37

2.67 2.83 2.98 3.15 3.28 7.02 7.48 7.93 8.34 8.61

3.80 4.05 4.28 4.50 4.70 10.06 10.71 11.32 11.91 12.35

4.87 5.22 5.53 5.84 6.09 12.91 13.81 16.62 15.43 16.06

R-404A/R-507 KVR 12 KVR 15 KVR 22

KVR 28 KVR 35

37.0 32.7 28.7 24.5 20.6 94.5 83.6 73.4 62.7 52.7

R-404A/R-507

R-407C KVR 12 KVR 15 KVR 22

KVR 28 KVR 35

*The capacities are based on: Evaporating temperature te = 40° F For other evaporating temperatures, see correction table.

56.8 51.8 46.7 41.6 36.4 145.4 132.6 119.5 106.6 93.1

5.87 6.17 6.45 6.60 6.78 15.48 16.32 17.06 17.49 17.92

R-407C 7.41 8.04 8.58 9.09 9.50 19.60 21.23 22.66 24.05 25.14

Correction Factors (Evaporating Temperature) te °F R-22 R-134a R-404A R-407C R-507

-40 0.89 0.82 0.76 0.83 0.74

-20 0.92 0.86 0.82 0.87 0.81

0 0.95 0.91 0.88 0.92 0.88

20 0.97 0.96 0.94 0.96 0.94

System capacity x correction factor = table capacity.

966

5.15 7.44 5.75 5.92 5.95 13.60 14.49 15.22 15.69 15.77

40 1.0 1.0 1.0 1.0 1.0

50 1.02 1.04 1.05 1.04 1.06

CONDENSER PRESSURE REGULATORS DANFOSS CONDENSER PRESSURE REGULATORS DIMENSIONS AND WEIGHTS

P4312B

TYPE

CONNECTIONS (in.) Flare Solder ODF

NV1 (in.)

NV2 (in.)

H1 (in.)

H2 (in.)

H3 (in.)

L (in.)

L1 (in.)

B1 (in.)

B2 (in.)

C (in.)

DIA. D (in.)

WEIGHT (lbs)

KVR 12

1/2

1/2

0.748

0.945

7.045

3.898

2.598

2.520

1.614

0.394

1.181

0.88

KVR 15

5/8

5/8

0.945

0.945

7.045

3.898

2.598

2.520

1.614

0.472

1.181

0.88

KVR 22

7/8

7.045

3.898

2.598

2.520

1.614

0.669

1.181

0.88

KVR 28

1-1/8

10.197

5.945

4.055

4.134

1.890

0.787

1.693

2.20

KVR 35

1-3/8

10.197

5.945

4.055

4.134

1.890

0.984

1.693

2.20

NRD

1/2

0.866

0.22

5.157

0.394

967

HOT GAS BYPASS CAPACITY REGULATORS DANFOSS HOT GAS BYPASS CAPACITY REGULATORS INTRODUCTION KVC capacity regulators are used to adapt compressor capacity to actual evaporator load by supplying a replacement capacity in form of hot/cool gas. It is installed in a bypass line between the high and low pressure sides of the refrigeration system and is designed for direct gas injection into the suction line.

FEATURES • Accurate, adjustable pressure regulation. • Wide capacity and operating range. • Pulsation, damping design. • Stainless steel bellows. • Compact angle design for easy installation.

P4313

• “Hermetic” brazed construction. • Available with flare and ODF solder connections. • For CFC, HCFC and HFC refrigerants.

APPROVALS UL listed, file SA7200. CSA approved.

TECHNICAL DATA Refrigerants: CFC, HCFC, HFC Regulation range:

3 to 85 psig Factory setting = 29 psig

P4313A

Maximum working pressure: MWP = 400 psig Maximum test pressure: p' = 450 psig Maximum temperature of medium: 300° F Minimum temperature of medium: – 40° F Maximum P-band: 29 psi

ORDERING TYPE KVC 12 KVC 15 KVC 22

R-22 2.14 4.17 5.35

RATED CAPACITY* (Tons) R-134a R-404A/R-507 1.36 2.02 2.65 3.93 3.41 5.04

R-407C 2.31 4.50 5.78

FLARE CONNECTION† in. Code No. 1/2 034L0141 5/8 034L0142

SOLDER CONNECTION in. ODF Code No. 1/2 034L0143 5/8 034L0147 7/8 034L0144

*Rated capacity is based on: Suction gas temperature ts = 10° F Liquid temperature tl = 100° F Offset ∆p = 10 psi †KVC are delivered without flare nuts. Separate flare nuts can be supplied: 1/2 in. code no. 011L1103; 5/8 in. code no. 011L1167. NOTE: The connection dimensions chosen must not be too small, as gas velocities in excess of 130 ft/s at the inlet of the regulator can result in flow noise. If the temperature in the discharge gas line is too high according to the compressor specifications, it is recommended to install a liquid injection valve in a bypass from the liquid line to the suction line.

968

P4313B

HOT GAS BYPASS CAPACITY REGULATORS DANFOSS HOT GAS BYPASS CAPACITY REGULATORS REPLACEMENT CAPACITY Maximum Regulator Capacity Qe* OFFSET ∆p psi

TYPE

REGULATOR CAPACITY Q TONS SUCTION GAS TEMPERATURE ts AFTER PRESSURE/TEMPERATURE REDUCTION °F –50 –40 –25 –10 10 30 50

R-22 KVC 12

1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0 1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0 1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0

KVC 15

KVC 22

0.68 0.93 1.33 1.75 1.93 2.00 2.19 2.62 1.01 1.20 1.73 2.64 3.39 3.90 4.76 5.05 1.09 1.38 1.89 2.88 4.02 4.98 6.35 7.10

0.70 0.95 1.36 1.79 1.97 2.04 2.24 2.67 1.03 1.23 1.77 2.69 3.46 3.98 4.66 5.16 1.12 1.41 1.93 2.94 4.11 5.09 6.49 7.25

0.71 0.97 1.39 1.83 2.01 2.08 2.28 2.72 1.06 1.25 1.80 2.75 3.54 4.06 4.75 5.27 1.14 1.44 1.97 3.00 4.19 5.20 6.63 7.40

0.73 1.00 1.43 1.88 2.07 2.14 2.35 2.80 1.09 1.29 1.85 2.83 3.63 4.17 4.88 5.42 1.17 1.48 2.02 3.08 4.31 5.35 6.82 7.60

0.75 1.03 1.47 1.93 2.12 2.20 2.41 2.87 1.12 1.32 1.90 2.90 3.73 4.28 5.01 5.57 1.21 1.52 2.07 3.16 4.43 5.50 7.01 7.79

0.41 0.58 0.83 1.09 1.20 1.25 1.36 1.62 0.62 0.74 1.08 1.64 2.12 2.45 2.87 3.13 0.67 0.86 1.18 1.80 2.52 3.13 4.00 4.43

0.43 0.60 0.86 1.14 1.25 1.30 1.42 1.69 0.65 0.78 1.13 1.72 2.21 2.54 2.96 3.26 0.70 0.90 1.22 1.86 2.62 3.25 4.15 4.61

0.46 0.62 0.91 1.20 1.31 1.36 1.49 1.78 0.68 0.82 1.18 1.79 2.30 2.65 3.11 3.44 0.73 0.94 1.28 1.96 2.74 3.41 4.34 4.82

0.48 0.66 0.95 1.25 1.37 1.42 1.56 1.86 0.72 0.86 1.24 1.87 2.41 2.77 3.25 3.61 0.78 0.97 1.33 2.04 2.87 3.55 4.54 5.05

0.77 1.05 1.51 1.98 2.18 2.26 2.48 2.94 1.15 1.35 1.95 2.98 3.83 4.39 5.14 5.72 1.24 1.56 2.12 3.24 4.54 5.64 7.20 7.99

R-134a KVC 12

1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0 1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0 1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0

KVC15

KVC 22

0.50 0.70 1.00 1.31 1.44 1.49 1.63 1.94 0.76 0.90 1.28 1.96 2.51 2.88 3.40 3.79 0.82 1.02 1.39 2.12 2.99 3.71 4.74 5.28

*The capacities are based on: Liquid temperature ahead of the expansion valve tl = 100 °F.

Correction factors for liquid temperature tl When liquid temperature tl ahead of the evaporator is other than 100° F, adjust the table capacities by multiplying them by the appropriate correction factor found in the following table. tl °F

60

70

80

90

100

110

120

R-22 R-134a

0.60 0.60

0.71 0.70

0.80 0.80

0.90 0.90

1.0 1.0

1.11 1.10

1.22 1.21

System capacity x correction factor = table capacity.

969

HOT GAS BYPASS CAPACITY REGULATORS DANFOSS HOT GAS BYPASS REGULATORS REPLACEMENT CAPACITY Maximum Regulator Capacity Qe* TYPE

OFFSET ∆p psi

REGULATOR CAPACITY Q TONS SUCTION GAS TEMPERATURE ts AFTER PRESSURE/TEMPERATURE REDUCTION °F –50 –40 –25 –10 10 30 50

R-404A/R-507 KVC 12

KVC 15

KVC 22

1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0 1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0 1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0

0.57 0.79 1.16 1.54 1.68 1.74 1.89 2.27 0.86 1.05 1.51 2.29 2.94 3.38 3.95 4.36 0.92 1.19 1.71 2.63 3.58 4.33 5.49 6.31

0.58 0.81 1.19 1.58 1.73 1.78 1.94 2.33 0.89 1.07 1.55 2.34 3.01 3.47 4.06 4.48 0.96 1.22 1.75 2.71 3.67 4.46 5.64 6.49

0.62 0.85 1.23 1.64 1.79 1.85 2.01 2.42 0.92 1.11 1.61 2.44 3.14 3.61 4.22 4.66 0.99 1.27 1.83 2.81 3.82 4.63 5.86 6.74

0.64 0.88 1.28 1.69 1.86 1.93 2.10 2.51 0.96 1.16 1.66 2.53 3.26 3.75 4.39 4.85 1.02 1.31 1.89 2.92 3.96 4.81 6.08 7.01

0.67 0.92 1.34 1.77 1.96 2.02 2.20 2.62 1.01 1.21 1.74 2.65 3.42 3.93 4.61 5.09 1.08 1.38 1.98 3.06 4.17 5.04 6.39 7.35

0.70 0.97 1.40 1.85 2.05 2.11 2.31 2.74 1.06 1.27 1.82 2.77 3.58 4.11 4.82 5.34 1.12 1.44 2.08 3.20 4.35 5.28 6.69 7.70

0.73 1.00 1.44 1.89 2.08 2.16 2.37 2.83 1.09 1.30 1.87 2.85 3.66 4.21 4.92 5.45 1.18 1.49 2.04 3.11 4.34 5.38 6.86 7.67

0.76 1.03 1.47 1.93 2.13 2.20 2.42 2.88 1.11 1.33 1.91 2.91 3.74 4.30 5.03 5.57 1.21 1.52 2.08 3.18 4.44 5.50 7.01 7.83

0.77 1.05 1.50 1.98 2.17 2.25 2.46 2.94 1.14 1.35 1.94 2.97 3.82 4.38 5.13 5.69 1.23 1.56 2.13 3.24 4.53 5.62 7.16 7.99

0.79 1.08 1.54 2.03 2.24 2.31 2.54 3.02 1.18 1.39 2.00 3.06 3.92 4.50 5.27 5.85 1.26 1.60 2.18 3.33 4.65 5.78 7.37 8.21

0.81 1.11 1.59 2.08 2.29 2.38 2.60 3.10 1.21 1.43 2.05 3.13 4.03 4.62 5.41 6.02 1.31 1.64 2.24 3.41 4.78 5.94 7.57 8.41

0.74 1.01 1.46 1.93 2.13 2.21 2.41 2.85 1.10 1.32 1.90 2.89 3.74 4.30 5.04 5.58 1.18 1.51 2.17 3.34 4.54 5.51 6.99 8.04

R-407C KVC 12

KVC15

KVC 22

1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0 1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0 1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0

*The capacities are based on: Liquid temperature ahead of the expansion valve tl = 100 °F.

0.83 1.13 1.63 2.14 2.35 2.44 2.68 3.18 1.24 1.46 2.11 3.22 4.14 4.74 5.55 6.18 1.34 1.68 2.29 3.50 4.90 6.09 7.78 8.63

the following table.

Correction factors for liquid temperature tl When liquid temperature tl ahead of the evaporator is other than 100° F, adjust the table capacities by multiplying them by the appropriate correction factor found in

tl °F

60

70

80

90

100

110

120

R-404A/R-507 R-407C

0.69 0.66

0.79 0.74

0.87 0.82

0.94 0.91

1.0 1.0

1.05 1.09

1.09 1.17

SIZING For optimum performance, it is important to select a KVC valve according to system conditions and application. The following data must be used when sizing a KVC valve: • Refrigerant: CFC, HCFC or HFC. • Suction temperature at maximum compressor/evaporator load ts in °F/psig.

970

• • • • • •

Minimum suction temperature ts in °F/psig. Compressor capacity in tons. Evaporating load in tons. Liquid temperature ahead of expansion valve tl in °F. Connection type flare or solder. Connection size in inches.

CRANKCASE PRESSURE REGULATORS DANFOSS CRANKCASE PRESSURE REGULATORS INTRODUCTION KVL crankcase pressure regulators are used to protect the compressor motor against overload experienced during startup after long off periods or just after defrost periods. They are installed in the suction line of refrigeration systems.

FEATURES • Accurate, adjustable pressure regulation. • Wide capacity and operating range. • Pulsation damping design. • Stainless steel bellows. • Compact angle design for easy installation in any position. • “Hermetic” brazed construction.

P4314

• Available with flare and ODF solder connections. • For use with CFC, HCFC and HFC refrigerants.

APPROVALS UL listed, file SA7200. CSA approved.

TECHNICAL DATA Refrigerants: CFC, HCFC, HFC Regulation range:

3 to 85 psig Factory setting = 29 psig

Maximum working pressure: KVL 12 to 22: MWP = 200 psig KVL 28 to 35: MWP = 200 psig Maximum test pressure:

KVL 12 to 22: p' = 405 psig KVL 28 to 35: p' = 370 psig

P4314A

Maximum temperature of medium: 300° F Minimum temperature of medium: – 325° F Maximum P-band: KVL 12 to 22: 29 psi KVL 28 to 35: 22 psi

971

CRANKCASE PRESSURE REGULATORS DANFOSS CRANKCASE PRESSURE REGULATORS CAPACITIES

R-22 Maximum regulator capacity Qe* at condensing temperature tc = 100° F TYPE

PRESSURE DROP ACROSS REGULATOR ∆p psi

2

KVL 12 KVL 15 KVL 22

3

4

2

KVL 28 KVL 35

3

4

CAPACITY Qe TONS AT SUCTION TEMPERATURE ts AFTER THE REGULATOR, °F

MAXIMUM SUCTION PRESSURE ps psig

–30

10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50

0.3 0.7 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.4 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.5 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.1 0.8 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 0.9 2.4 3.1 3.1 3.1 3.1 3.1 3.1 3.1 1.1 2.8 3.6 3.6 3.6

60 70 80 90

3.6 3.6 3.6 3.6

*The capacities are based on: liquid temperature tl = 100° F.

–20

–10

0

10

20

30

40

50

0.6 0.9 0.9 0.9 0.9 0.9 0.9 0.9

0.3 0.9 1.0 1.0 1.0 1.0 1.0 1.0

0.5 1.0 1.1 1.1 1.1 1.1 1.1

0.7 1.2 1.2 1.2 1.2 1.2

0.8 1.3 1.4 1.4 1.4

0.6 1.4 1.5 1.5

0.2 1.3 1.6

0.9

0.8 1.1 1.1 1.1 1.1 1.1 1.1 1.1

0.4 1.0 1.2 1.2 1.2 1.2 1.2 1.2

0.7 1.3 1.3 1.3 1.3 1.3 1.3

0.9 1.5 1.5 1.5 1.5 1.5

0.9 1.6 1.7 1.7 1.7

0.8 1.7 1.8 1.8

0.3 1.6 2.0

1.1

0.9 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.6 2.7 2.9 2.9 2.9 2.9 2.9 2.9 2.9

0.4 1.2 1.4 1.4 1.4 1.4 1.4 1.4

0.8 1.5 1.6 1.6 1.6 1.6 1.6

1.0 1.7 1.7 1.7 1.7 1.7

1.1 1.9 1.9 1.9 1.9

0.9 2.0 2.1 2.1

0.3 1.9 2.3

1.3

0.7 2.3 3.2 3.2 3.2 3.2 3.2 3.2

1.2 3.0 3.6 3.6 3.6 3.6 3.6

1.6 3.5 4.1 4.1 4.1 4.1

1.8 3.8 4.5 4.5 4.5

1.4 3.9 5.0 5.0

0.4 3.4 5.5

2.0

1.9 3.4 3.5 3.5 3.5 3.5 3.5 3.5

0.8 2.8 4.0 4.0 4.0 4.0 4.0 4.0

1.5 3.6 4.5 4.5 4.5 4.5 4.5

2.0 4.3 5.0 5.0 5.0 5.0

2.2 4.7 5.5 5.5 5.5

1.8 4.7 6.1 6.1

0.5 4.2 6.7

2.5

2.2 3.9 4.1 4.1

0.9 3.3 4.6 4.6

1.8 4.2 5.2

2.3 4.9

2.5

4.1 4.1 4.1 4.1

4.6 4.6 4.6 4.6

5.2 5.2 5.2 5.2

5.8 5.8 5.8 5.8

5.4 6.4 4.5 4.5

2.0 5.5 7.1 7.1

0.6 4.8 7.7

2.9

70

Correction Factors for Liquid Temperature tl tl °F R-22

50 0.82

60 0.85

70 0.88

80 0.92

90 0.96

System capacity x correction factor = table capacity.

972

60

100 1.0

110 1.05

120 1.10

CRANKCASE PRESSURE REGULATORS DANFOSS CRANKCASE PRESSURE REGULATORS CAPACITIES

R-134a Maximum regulator capacity Qe at condensing temperature tc = 100° F TYPE

PRESSURE DROP ACROSS REGULATOR ∆p psi

MAXIMUM SUCTION PRESSURE ps psig 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50

2

KVL 12 KVL 15 KVL 22

3

4

2

KVL 28 KVL 35

3

4

60 70 80 90

CAPACITY Qe TONS AT SUCTION TEMPERATURE ts AFTER THE REGULATOR, °F –30

–20

–10

0

0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.5 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 1.3 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.6 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.5 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.8 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.5

0.4 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.6 0.8 0.9 0.9 0.9 0.9 0.9 0.9 0.9 1.1 1.7 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.4 2.1 2.5 2.5 2.5 2.5 2.5 2.5 2.5 1.6 2.4 2.9 2.9 2.9 2.9 2.9 2.9 2.9

0.3 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.4 0.7 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.5 0.8 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.7 1.5 2.2 2.3 2.3 2.3 2.3 2.3 2.3 0.9 1.8 2.7 2.8 2.8 2.8 2.8 2.8 2.8 1.0 2.1 3.1 3.3 3.3 3.3 3.3 3.3 3.3

10

20

30

40

50

60

70

0.4 0.7 0.8 0.8 0.8 0.8 0.8 0.8

0.6 0.9 0.9 0.9 0.9 0.9 0.9

0.7 1.0 1.0 1.0 1.0 1.0

0.8 1.1 1.1 1.1 1.1

1.0 1.3 1.3 1.3

1.2 1.4 1.4

1.5 1.5

0.5 0.9 1.0 1.0 1.0 1.0 1.0 1.0

0.7 1.0 1.1 1.1 1.1 1.1 1.1

0.8 1.2 1.2 1.2 1.2 1.2

1.0 1.4 1.4 1.4 1.4

1.3 1.5 1.5 1.5

1.5 1.7 1.7

1.8 1.9

0.6 1.0 1.1 1.1 1.1 1.1 1.1 1.1

0.8 1.2 1.3 1.3 1.3 1.3 1.3

1.0 1.4 1.4 1.4 1.4 1.4

1.2 1.6 1.6 1.6 1.6

1.5 1.8 1.8 1.8

1.8 2.0 2.0

2.1 2.2

1.0 1.9 2.6 2.6 2.6 2.6 2.6 2.6

1.3 2.5 3.0 3.0 3.0 3.0 3.0

1.7 3.1 3.3 3.3 3.3 3.3

2.1 3.7 3.7 3.7 3.7

2.7 4.2 4.2 4.2

3.4 4.7 4.7

4.1 5.2

1.2 2.4 3.2 3.2 3.2 3.2 3.2 3.2

1.6 3.1 3.6 3.6 3.6 3.6 3.6

2.1 3.8 4.1 4.1 4.1 4.1

2.6 4.6 4.6 4.6 4.6

3.3 5.1 5.1 5.1

4.1 5.7 5.7

5.1 6.3

1.4 2.8 3.7 3.7 3.7 3.7 3.7 3.7

1.8 3.5 4.2 4.2 4.2 4.2 4.2

2.4 4.4 4.7 4.7 4.7 4.7

3.0 5.3 5.3 5.3 5.3

3.8 5.9 5.9 5.9

4.8 6.6 6.6

5.9 7.3

Correction Factors for Liquid Temperature tl tl °F R-134a

50 0.79

60 0.82

70 0.86

80 0.90

90 0.95

100 1.0

110 1.06

120 1.13

System capacity x correction factor = table capacity.

973

CRANKCASE PRESSURE REGULATORS DANFOSS CRANKCASE PRESSURE REGULATORS CAPACITIES

R-404A/R-507 Maximum regulator capacity Qe* at condensing temperature tc = 100° F TYPE

PRESSURE DROP ACROSS REGULATOR ∆p psi

2

KVL 12 KVL 15 KVL 22

3

4

2

KVL 28 KVL 35

3

4

MAXIMUM SUCTION PRESSURE ps psig 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50

60 70 80 90 *The capacities are based on: liquid temperature tl = 100° F.

CAPACITY Qe TONS AT SUCTION TEMPERATURE ts AFTER THE REGULATOR, °F –30

–20

–10

0

10

20

30

40

0.5 0.6 0.6 0.6 0.6 0.6 0.6 0.6

0.3 0.6 0.7 0.7 0.7 0.7 0.7 0.7

0.5 0.8 0.8 0.8 0.8 0.8 0.8

0.6 0.9 0.9 0.9 0.9 0.9

0.7 1.0 1.0 1.0 1.1

0.7 1.1 1.1 1.2

0.5 1.1 1.3

1.1

0.6 0.8 0.8 0.8 0.8 0.8 0.8 0.8

0.3 0.8 0.9 0.9 0.9 0.9 0.9 0.9

0.6 0.9 1.0 1.0 1.0 1.0 1.1

0.7 1.1 1.1 1.1 1.1 1.2

0.8 1.2 1.3 1.3 1.3

0.8 1.4 1.5 1.5

0.6 1.5 1.6

1.3

0.7 0.9 0.9 0.9 0.9 0.9 0.9 0.9

0.4 0.9 1.0 1.0 1.0 1.0 1.0 1.1

0.7 1.1 1.1 1.1 1.1 1.1 1.2

0.9 1.3 1.3 1.4 1.4 1.4

1.0 1.4 1.5 1.5 1.5

1.0 1.7 1.7 1.7

0.7 1.7 1.9

1.5

1.2 2.0 2.0 2.0 2.1 2.1 2.1 2.1 0.1 1.4 2.5 2.6 2.6 2.6 2.6 2.6 2.6 0.1 1.7 2.8 3.0 3.0 3.0 3.0 3.0 3.1

0.6 1.7 2.3 2.4 2.4 2.4 2.4 2.4

1.1 2.2 2.7 2.7 2.7 2.7 2.7

1.5 2.8 3.1 3.1 3.1 3.1

1.7 3.2 3.4 3.4 3.5

1.6 3.3 3.9 3.9

1.1 3.2 4.3

2.6

0.7 2.1 3.0 3.0 3.0 3.0 3.0 3.1

1.3 2.9 3.2 3.2 3.2 3.2 3.3

1.9 3.4 3.8 3.9 3.9 3.9

2.1 3.9 4.3 4.3 4.3

2.1 4.2 4.8 4.8

1.3 4.0 5.4

3.3

0.8 2.5 3.4 3.4 3.4 3.4 3.4 3.5

1.5 3.3 3.9 3.9 4.0 4.0 4.0

2.1 4.0 4.3 4.4 4.4 4.4

2.4 4.4 4.9 4.9 4.9

2.4 4.8 5.5 5.6

1.7 4.6 6.2

3.7

60

70

110 1.10

120 1.24

Correction Factors for Liquid Temperature tl tl °F 50 R-404A/R-507 0.71

60 0.75

70 0.80

80 0.85

90 0.92

System capacity x correction factor = table capacity.

974

50

100 1.0

CRANKCASE PRESSURE REGULATORS DANFOSS CRANKCASE PRESSURE REGULATORS CAPACITIES

R-407C Maximum regulator capacity Qe at condensing temperature tc = 100° F TYPE

PRESSURE DROP ACROSS REGULATOR ∆p psi

MAXIMUM SUCTION PRESSURE ps psig 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50 60 70 80 90 10 20 30 40 50

2

KVL 12 KVL 15 KVL 22

3

4

2

KVL 28 KVL 35

3

4

CAPACITY Qe TONS AT SUCTION TEMPERATURE ts AFTER THE REGULATOR, °F –30

–20

–10

0

10

20

30

40

50

0.5 0.8 0.8 0.8 0.8 0.8 0.8 0.9

0.3 0.8 0.9 0.9 0.9 0.9 0.9 0.9

0.4 0.9 1.0 1.0 1.0 1.0 1.0

0.6 1.1 1.1 1.1 1.1 1.1

0.7 1.2 1.3 1.3 1.3

0.6 1.3 1.4 1.4

0.2 1.2 1.5

0.9

0.7 1.0 1.0 1.0 1.0 1.0 1.0 1.0

0.3 0.9 1.1 1.1 1.1 1.1 1.1 1.1

0.6 1.2 1.2 1.2 1.2 1.2 1.2

0.8 1.4 1.4 1.4 1.4 1.4

0.8 1.5 1.6 1.6 1.6

0.7 1.6 1.7 1.7

0.3 1.5 1.9

1.0

0.8 1.0 1.1 1.1 1.1 1.1 1.1 1.1

0.3 1.0 1.3 1.3 1.3 1.3 1.3 1.3

0.7 1.4 1.4 1.5 1.5 1.5 1.5

0.9 1.5 1.6 1.6 1.6 1.6

1.0 1.7 1.8 1.8 1.8

0.8 1.8 2.0 2.0

0.3 1.8 2.2

1.2

2.3 2.5 2.6 2.6 2.6 2.7 2.7 2.7

0.6 2.0 2.9 2.9 2.9 2.9 3.0 3.0

1.0 2.7 3.2 3.3 3.3 3.4 3.4

1.4 3.2 3.7 3.8 3.8 3.9

1.6 3.5 4.1 4.2 4.2

1.3 3.6 4.7 4.7

0.4 3.2 5.2

1.9

1.6 3.0 3.1 3.2 3.2 3.2 3.3 3.3

0.7 2.4 3.6 3.6 3.6 3.7 3.7 3.8

1.3 3.2 4.1 4.1 4.1 4.2 4.2

1.8 3.9 4.6 4.6 4.7 4.7

2.0 4.3 5.1 5.1 5.2

1.6 4.3 5.7 5.7

0.5 3.9 6.3

2.4

1.9 3.4 3.7 3.7 3.7 3.8 3.8 3.9

0.8 2.9 4.1 4.1 4.2 4.2 4.3 4.3

1.6 3.7 4.7 4.7 4.8 4.8 4.9

2.1 4.4 5.3 5.3 5.4 5.5

2.3 4.9 5.9 6.0 6.0

1.8 2.1 6.6 6.7

0.6 4.5 7.2

2.7

0.2 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.8 0.3 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.9 0.4 0.9 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.7 1.7 2.2 2.2 2.3 2.3 2.3 2.3 2.4 0.7 2.0 2.7 2.8 2.8 2.8 2.9 2.9 2.9 0.9 2.4 3.1 3.2 3.2 3.3 3.3 3.4 3.4

60 70 80 90

60

70

Correction Factors for Liquid Temperature tl tl °F R-407C

50 0.78

60 0.81

70 0.85

80 0.89

90 0.94

100 1.0

110 1.07

120 1.15

System capacity x correction factor = table capacity.

975

CRANKCASE PRESSURE REGULATORS DANFOSS CRANKCASE PRESSURE REGULATORS DIMENSIONS AND WEIGHTS

P4314B

TYPE KVL 12 KVL 15 KVL 22 KVL 28 KVL 35

976

Flare 1/2 5/8

CONNECTION (in.) Solder ODF 1/2 5/8 7/8 1-1/8 1-3/8

H1 (in.) 7.047 7.047 7.047 10.197 10.197

H2 (in.) 3.898 3.898 3.898 5.945 5.945

B1 (in.) 2.520 2.520 2.520 4.134 4.134

C (in.) 0.375 0.5 0.625 0.875 1.0

DIA. D (in.) 1.181 1.181 1.181 1.693 1.693

WEIGHT (lbs) 0.9 0.9 0.9 2.0 2.0

CHECK VALVES DANFOSS CHECK VALVES, TYPE NRV

P393

P394 P397

P279

The NRV check valve can be fitted in liquid, suction and hot-gas lines in refrigeration, freezing and air conditioning systems with fluorinated refrigerants (R-12, R-22, R-502, etc.).

The NRV is fitted with a special damping piston that ensures silent operation and makes the valve suitable for installation in piping systems where pulsation may occur, for example in the discharge line from the compressor and in reverse cycle heat pump systems.

TECHNICAL DATA & ORDERING. TYPE

VERSION

CONNECTION (in.)

REFRIGERANTS: R-12, R-22, R-500, etc. NRV 6 NRV 10 Flare SAE NRV 12 NRV 15 NRV 6s StraightNRV 10s way 3) NRV 10S NRV 12S NRV 12S3) NRV 15s NRV 15S3) NRV 22s NRV 28s NRV 35s

Solder ODF

1/4 3/8 1/2 5/8 1/4 3/8

∆P 1) (PSI)

TEMP. OF MEDIUM (°F)

MAX. OPERATING PRESSURE (SWP) (PSIG)

MAX. TEST PRESSURE (PSIG)

0.7 1.6 2.3 4.2 0.7

1 0.7 1 350 4.3

1/2

0.7

-

4.3

5/8

0.7

455

-60 to +285

Angleway

NOTES: 1) ∆p = the minimum pressure at which the valve is completely open. The NRV with a stronger spring (∆p = 4.3 psi) is used in the discharge line from compressors connected in parallel. For still greater pressure drop, refer to differential pressure valve type NRD with ∆p = 2 psi when the valve begins to open and ∆p = 20 psi when the valve is completely open. 2) The C factor is the water flow in gal/min v at a pressure drop across the valve of 1 psi, = 10 lb/gal. 3) For pressure lines. 4 ) Type NRV with ∆po 4.3 psi can be supplied to special order. 5) Indicated at to = +15° F, t = +75° F and v ∆p = 1 psi. 6 ) Indicated at to = +15° F, tv = +75° F, ∆p = 1 psi for NRV 6-10; ∆p = 0.7 psi for NRV 12-35. 7 ) Indicated at tk = +75° F, hot-gas = +140° F and ∆p = 1 psi.

0.6 0.6 0.6

TYPE

NRV 6 NRV 10 NRV 12 NRV 15 NRV 22 NRV 28 NRV 35

NOMINAL LIQUID CAPACITY 5 ) (TONS) R-12 R-22 R-502 1.7 2.2 1.5 4.1 5.3 3.6 5.8 7.6 5.3 10.6 13.9 9.6 25.0 32.8 22.7 55.9 73.5 50.6 85.4 113 77.5

1.6 2.3 4.2

4.3 7/8 1-1/8 1-3/8

Cv FACTOR GAL/MIN 2 )

305

400

NOMINAL SUCTION VAPOR CAPACITY 6 ) (TONS) R-12 R-22 R-502 0.2 0.2 0.2 0.4 0.5 0.5 0.5 0.7 0.6 0.8 1.2 1.0 1.9 2.9 2.4 4.4 6.5 5.5 6.6 9.9 8.3

10 22 34

P/N

482-1040 482-1041 482-1042 482-1043 482-1010 482-1011 4) 482-1012 4) 482-1013 4 ) 482-1020 482-1021 482-1022

NOMINAL HOT-GAS CAPACITY 7 ) (TONS) R-12 R-22 R-502 0.2 0.4 0.3 0.6 1.0 0.8 1.0 1.4 1.1 1.7 2.5 2.0 4.2 6.3 5.0 8.4 12.6 10.0 13.6 20.4 16.2

977

CHECK VALVES DANFOSS CHECK VALVES INTRODUCTION NRV check valves can be used in liquid, suction and hot gas lines in refrigeration and air conditioning systems using fluorinated refrigerants. They allow flow in only one direction and have a built-in damping piston that makes the valve suitable for installation in lines where pulsation can occur. They are available in both angleway and straightway versions. NRVH check valves can be used in liquid and hot gas lines in refrigeration and air conditioning systems using fluorinated refrigerants. They are supplied with a stronger spring than type NRV (DP = 4.3 psi) and are especially suitable for installation in the discharge line of systems with compressors connected in parallel. PNRV-1

FEATURES • Two Versions available. Type NRV: Requires a minimum ∆p of 0.6 to 1 psi for 100% flow. Type NRVH: Includes a stronger spring that requires a minimum ∆p of 4.3 psi for 100% flow. • Both straightway and angleway versions. • Prevents refrigerant migration from a warm evaporator to a cold evaporator. • Built-in damping piston. Suitable for installation in lines where pulsation can occur, e.g. in the discharge line from the compressor. • Oversize connections provide flexibility in use.

TECHNICAL DATA Refrigerants: CFC, HCFC and HFC Temperature of medium: -60 → +285° F Maximum working pressure: MWP = 400 psig Maximum test pressure: p′ = 520 psig

978

DIMENSIONING AND SELECTION When dimensioning and selecting check valves to be mounted into the compressor discharge line, it is important to be aware of the following: The differential pressure across the check valve must always be higher than the given minimum pressure drop at which the valve is completely open. This also applies to lowest capacity for compressors with capacity regulation, and refrigeration systems that operate at partial load conditions. In refrigeration systems with compressors connected in parallel, it is advantageous to use NRVH equipped with a stronger spring than NRV. With check valve, type NRVH, resonance problems can be avoided at partial load in the refrigeration systems.

CHECK VALVES DANFOSS CHECK VALVES CAPACITY Liquid Capacity CAPACITY IN TONS AT PRESSURE DROP ACROSS VALVE ∆p PSI 1 2 3 4 5 6 7

TYPE

R-22 NRV/H 6 NRV/H 10 NRV/H 12 NRV/H 16 NRV/H 19 NRV/H 22 NRV/H 28 NRV/H 35

1.88 4.80 6.90 12.11 16.82 28.59 63.90 97.54

2.88 7.34 10.55 18.51 25.72 43.73 97.72 149.16

3.53 8.99 12.92 22.67 31.50 53.55 119.68 182.68

4.05 10.33 14.84 26.04 36.18 61.51 137.47 209.84

4.55 11.60 16.66 29.24 40.63 69.08 154.38 235.65

4.99 12.72 18.27 32.07 44.56 75.76 169.31 258.34

5.38 13.73 19.72 34.61 48.09 81.75 182.71 278.89

1.90 4.83 6.94 12.19 16.94 28.79 64.34 98.21

2.68 6.83 9.81 17.22 23.93 40.68 90.91 138.77

3.29 8.38 12.04 21.13 29.36 49.92 111.56 170.28

3.80 9.69 13.91 24.42 33.93 57.68 128.91 196.76

4.24 10.82 15.55 27.29 37.92 64.46 144.06 219.89

4.65 11.85 17.02 29.87 41.50 70.55 157.67 240.67

5.02 12.80 18.39 32.28 44.85 76.25 170.41 260.12

1.40 3.56 5.12 8.99 12.48 21.22 47.43 72.40

1.98 5.05 7.25 12.73 17.69 30.07 67.20 102.57

2.43 6.19 8.89 15.60 21.68 36.85 82.35 125.70

2.80 7.14 10.26 18.01 25.03 42.55 95.09 145.14

3.13 7.99 11.47 20.13 27.98 47.56 106.29 162.24

3.43 8.75 12.56 22.05 30.63 52.08 116.39 177.66

3.71 9.47 13.60 23.88 33.18 56.40 126.05 192.40

1.85 4.72 6.78 11.90 16.53 28.10 62.81 95.87

2.62 6.68 9.60 16.85 23.41 39.80 88.94 135.76

3.21 8.18 11.76 20.63 28.67 48.74 108.92 166.26

3.71 9.45 13.58 23.84 33.12 55.30 125.83 192.97

4.14 10.56 15.17 26.82 36.99 62.89 140.54 214.53

4.54 11.58 16.64 29.20 40.58 68.98 154.16 235.31

4.90 12.51 17.96 31.53 43.81 74.48 166.46 254.08

R-134a NRV/H 6 NRV/H 10 NRV/H 12 NRV/H 16 NRV/H 19 NRV/H 22 NRV/H 28 NRV/H 35

R-404A/R-507 NRV/H 6 NRV/H 10 NRV/H 12 NRV/H 16 NRV/H 19 NRV/H 22 NRV/H 28 NRV/H 35

R-407C NRV/H 6 NRV/H 10 NRV/H 12 NRV/H 16 NRV/H 19 NRV/H 22 NRV/H 28 NRV/H 35

The capacities are based on: Evaporating temperature te = 40° F Liquid temperature tl = 100° F Superheat temperature ts = (te +10° F) = 50° F

Correction Factors for Liquid Temperature tl When liquid temperature tl ahead of the evaporator is other than 100° F, adjust the table capacities by multiplying them by the appropriate correction factor found in the following table. tl °F R-22 R-134a R-404A/R-507 R-407C

50 0.82 0.79 0.71 0.78

60 0.85 0.82 0.75 0.81

70 0.88 0.86 0.80 0.85

80 0.92 0.90 0.85 0.89

90 0.96 0.95 0.92 0.94

100 1.0 1.0 1.0 1.0

110 1.05 1.06 1.10 1.07

120 1.10 1.13 1.24 1.15

979

CHECK VALVES DANFOSS CHECK VALVES CAPACITY Suction Vapor Capacity TYPE

PRESSURE DROP ACROSS VALVE ∆p psi

SUCTION VAPOR CAPACITY IN TONS AT EVAPORATING TEMPERATURE te °F –40

–20

0

10

20

30

40

50

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

0.11 0.15 0.17 0.29 0.38 0.45 0.41 0.55 0.64 0.72 0.96 1.12 0.99 1.33 1.56 1.69 2.27 2.66 3.78 5.07 5.93 5.76 7.74 9.06

0.15 0.20 0.24 0.39 0.52 0.62 0.55 0.74 0.88 0.97 1.30 1.54 1.35 1.80 2.14 2.29 3.07 3.65 5.13 6.85 8.15 7.82 10.46 12.43

0.19 0.26 0.31 0.49 0.67 0.80 0.70 0.95 1.15 1.23 1.68 2.01 1.70 2.33 2.80 2.90 3.96 4.76 6.47 8.85 10.63 9.88 13.51 16.22

0.21 0.30 0.35 0.55 0.78 0.91 0.79 1.11 1.30 1.38 1.95 2.28 1.92 2.71 3.17 3.26 4.61 5.38 7.28 10.30 12.03 11.12 15.73 18.36

0.24 0.34 0.40 0.61 0.86 1.02 0.87 1.23 1.46 1.53 2.17 2.57 2.13 3.01 3.56 3.62 5.12 6.06 8.09 11.44 13.54 12.35 17.46 20.67

0.26 0.37 0.46 0.68 0.96 1.17 0.97 1.37 1.68 1.70 2.40 2.94 2.36 3.34 4.09 4.01 5.67 6.95 8.96 12.68 15.54 13.67 19.35 23.72

0.29 0.41 0.51 0.75 1.06 1.30 1.07 1.51 1.85 1.88 2.66 3.25 2.61 3.69 4.52 4.44 6.28 7.68 9.93 14.03 17.16 15.15 21.41 26.19

0.32 0.45 0.56 0.82 1.17 1.43 1.18 1.67 2.04 2.06 2.92 3.58 2.87 4.06 4.97 4.88 6.90 8.45 10.90 15.43 18.88 16.63 23.55 28.82

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

0.07 0.09 0.10 0.17 0.22 0.24 0.25 0.32 0.35 0.44 0.56 0.61 0.61 0.78 0.85 1.04 1.33 1.45 2.32 2.97 3.24 3.54 4.53 4.94

0.10 0.13 0.15 0.25 0.33 0.38 0.36 0.48 0.55 0.62 0.84 0.96 0.87 1.16 1.33 1.47 1.98 2.27 3.29 4.42 5.07 5.02 6.75 7.74

0.14 0.18 0.21 0.35 0.46 0.55 0.50 0.66 0.79 0.88 1.17 1.38 1.22 1.62 1.92 2.08 2.75 3.26 4.64 6.15 7.28 7.08 9.39 11.12

0.16 0.21 0.25 0.40 0.54 0.64 0.57 0.77 0.92 1.00 1.35 1.61 1.39 1.87 2.24 2.37 3.19 3.81 5.29 7.12 8.52 8.07 10.87 13.01

0.18 0.24 0.29 0.45 0.61 0.73 0.65 0.88 1.05 1.13 1.54 1.85 1.58 2.14 2.57 2.68 3.65 4.37 5.99 8.15 9.76 9.14 12.43 14.91

0.20 0.28 0.33 0.51 0.72 0.84 0.73 1.04 1.21 1.29 1.82 2.13 1.79 2.53 2.95 3.04 4.30 5.02 6.80 9.60 11.22 10.38 14.66 17.13

0.22 0.32 0.38 0.57 0.81 0.96 0.82 1.16 1.37 1.44 2.04 2.41 2.00 2.84 3.35 3.40 4.83 5.70 7.61 10.79 12.73 11.61 16.47 19.43

0.25 0.36 0.44 0.64 0.91 1.11 0.92 1.30 1.60 1.61 2.29 2.80 2.24 3.18 3.89 3.81 5.41 6.61 8.52 12.08 14.78 13.01 18.45 22.56

R-22 NRV 6

NRV 10

NRV 12

NRV 16

NRV 19

NRV 22

NRV 28

NRV 35

R-134a NRV 6

NRV 10

NRV 12

NRV 16

NRV 19

NRV 22

NRV 28

NRV 35

The capacities are based on: Liquid temperature tl = 100° F Superheat temperature ts = (te +7° F)

Correction Factors for Liquid Temperature tl When liquid temperature tl ahead of the evaporator is other than 100° F, adjust the table capacities by multiplying them by the appropriate correction factor found in the following table. For each additional 10° F of superheat above 7° F, the table capacities must be reduced by 2%. tl °F R-22 R-134a

980

50 0.82 0.79

60 0.85 0.82

70 0.88 0.86

80 0.92 0.90

90 0.96 0.95

100 1.0 1.0

110 1.05 1.06

120 1.10 1.13

CHECK VALVES DANFOSS CHECK VALVES CAPACITY Suction Vapor Capacity (cont) TYPE

PRESSURE DROP ACROSS VALVE ∆p psi

SUCTION VAPOR CAPACITY IN TONS AT EVAPORATRING TEMPERATURE te °F –40

–20

0

10

20

30

40

50

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

0.09 0.12 0.14 0.22 0.31 0.36 0.32 0.44 0.51 0.56 0.77 0.90 0.78 1.07 1.25 1.33 1.81 2.12 2.97 4.05 4.75 4.53 6.18 7.25

0.12 0.16 0.20 0.31 0.42 0.50 0.44 0.60 0.72 0.78 1.05 1.26 1.08 1.46 1.75 1.83 2.49 2.97 4.10 5.56 6.64 6.26 8.48 10.13

0.16 0.23 0.27 0.41 0.58 0.68 0.58 0.83 0.97 1.02 1.46 1.71 1.42 2.03 2.37 2.41 3.45 4.03 5.40 7.71 9.01 8.24 11.78 13.75

0.18 0.26 0.31 0.47 0.66 0.78 0.68 0.94 1.12 1.19 1.66 1.96 1.65 2.30 2.73 2.80 3.91 4.63 6.26 8.74 10.36 9.55 13.34 15.81

0.21 0.29 0.35 0.53 0.74 0.91 0.75 1.06 1.30 1.32 1.86 2.28 1.83 2.58 3.17 3.11 4.39 5.38 6.96 9.82 12.03 10.62 14.99 18.36

0.23 0.33 0.40 0.59 0.84 1.03 0.84 1.20 1.47 1.48 2.11 2.58 2.06 2.93 3.58 3.50 4.97 6.08 7.82 11.11 13.60 11.94 16.96 20.75

0.26 0.36 0.45 0.66 0.93 1.15 0.94 1.33 1.64 1.66 2.34 2.87 2.30 3.25 3.99 3.91 5.53 6.78 8.74 12.35 15.16 13.34 18.86 23.14

0.29 0.41 0.50 0.74 1.04 1.28 1.05 1.49 1.83 1.85 2.62 3.21 2.57 3.64 4.46 4.37 6.18 7.58 9.76 13.81 16.94 14.91 21.08 25.86

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

0.09 0.12 0.14 0.23 0.30 0.35 0.33 0.43 0.50 0.57 0.75 0.88 0.80 1.04 1.22 1.35 1.76 2.08 3.02 3.94 4.64 4.61 6.01 7.08

0.13 0.17 0.20 0.32 0.43 0.51 0.46 0.61 0.72 0.81 1.07 1.27 1.12 1.49 1.76 1.91 2.53 2.99 4.26 5.66 6.69 6.51 8.65 10.21

0.17 0.22 0.27 0.42 0.58 0.69 0.61 0.82 0.98 1.06 1.44 1.73 1.48 2.00 2.40 2.51 3.40 4.08 5.61 7.61 9.12 8.56 11.61 13.92

0.19 0.27 0.31 0.49 0.69 0.80 0.69 0.98 1.14 1.22 1.72 2.00 1.69 2.39 2.78 2.87 4.06 4.73 6.42 9.06 10.57 9.80 13.83 16.14

0.21 0.30 0.35 0.55 0.78 0.91 0.79 1.11 1.30 1.38 1.95 2.28 1.92 2.71 3.17 3.26 4.61 5.38 7.28 10.30 12.03 11.12 15.73 18.36

0.24 0.34 0.44 0.62 0.87 1.14 0.88 1.25 1.62 1.54 2.19 2.85 2.14 3.04 3.96 3.65 5.17 6.74 8.15 11.55 15.05 12.43 17.62 22.98

0.27 0.38 0.47 0.70 0.99 1.21 1.00 1.41 1.72 1.75 2.47 3.03 2.43 3.44 4.20 4.13 5.84 7.15 9.23 13.06 15.97 14.08 19.93 24.38

0.30 0.43 0.52 0.77 1.10 1.34 1.11 1.57 1.92 1.94 2.75 3.36 2.70 3.82 4.67 4.59 6.49 7.94 10.25 14.51 17.75 15.65 22.15 27.09

R-404A/R-507 NRV 6

NRV 10

NRV 12

NRV 16

NRV 19

NRV 22

NRV 28

NRV 35

R-407C NRV 6

NRV 10

NRV 12

NRV 16

NRV 19

NRV 22

NRV 28

NRV 35

The capacities are based on: Liquid temperature tl = 100° F Superheat temperature ts = (te +7° F)

Correction Factors for Liquid Temperature tl When liquid temperature tl ahead of the evaporator is other than 100° F, adjust the table capacities by multiplying them by the appropriate correction factor found in the following table. For each additional 10° F of superheat above 7° F, the table capacities must be reduced by 2%. tl °F R-404A/R-507 R-407C

50 0.71 0.78

60 0.75 0.81

70 0.80 0.85

80 0.85 0.89

90 0.92 0.94

100 1.0 1.0

110 1.10 1.07

120 1.24 1.15

981

CHECK VALVES DANFOSS CHECK VALVES CAPACITY Hot Gas Capacity TYPE

HOT GAS TEMPERATURE CAPACITY IN TONS AT PRESSURE DROP ACROSS VALVE ∆p psi tc °F 2 5 10 15 20 25

R-22 NRV/H 6

NRV/H 10

NRV/H 12

NRV/H 16

NRV/H 19

NRV/H 22

NRV/H 28

NRV/H 35

70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140

0.59 0.65 0.70 1.52 1.68 1.80 2.17 2.40 2.57 3.81 4.21 4.52 5.30 5.85 6.28 9.00 9.95 10.67 20.12 22.23 23.85 30.72 33.93 36.40

0.95 1.04 1.12 2.43 2.68 2.87 3.48 3.83 4.09 6.10 6.71 7.18 8.48 9.33 9.98 14.41 15.86 16.97 32.21 35.45 37.93 49.16 54.10 57.89

1.31 1.50 1.59 3.36 3.84 4.09 4.79 5.48 5.84 8.41 9.63 10.25 11.69 13.38 14.24 19.87 22.74 24.21 44.40 50.82 54.11 67.77 77.57 82.60

1.59 1.77 1.97 4.08 4.53 5.06 5.83 6.47 7.23 10.23 11.35 12.68 14.21 15.78 17.62 24.16 26.82 29.96 54.00 59.94 66.95 82.43 91.49 102.20

1.83 2.04 2.20 4.69 5.22 5.64 6.70 7.46 8.06 11.75 13.09 14.14 16.33 18.19 19.65 27.76 30.92 33.41 62.04 69.11 74.67 94.70 105.49 113.97

2.04 2.27 2.46 5.23 5.83 6.30 7.46 8.32 9.00 13.10 14.60 15.80 18.20 20.29 21.95 30.95 34.50 37.32 69.16 77.09 83.41 105.57 117.68 127.31

70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140

0.48 0.53 0.56 1.24 1.37 1.44 1.78 1.96 2.05 3.12 3.43 3.60 4.33 4.77 5.00 7.36 8.11 8.50 16.45 18.13 18.99 25.12 27.67 28.99

0.78 0.86 0.89 2.01 2.19 2.29 2.86 3.13 3.27 5.03 5.50 5.73 6.99 7.64 7.97 11.88 12.99 13.54 26.54 29.03 30.27 40.52 44.30 46.20

1.07 1.19 1.28 2.74 3.05 3.27 3.92 4.35 4.68 6.88 7.63 8.21 9.56 10.61 11.40 16.25 18.03 19.38 36.31 40.30 43.32 55.42 61.52 66.13

1.31 1.46 1.58 3.36 3.74 4.07 4.80 5.34 5.81 8.43 9.37 10.19 11.72 13.02 14.16 19.92 22.14 24.07 44.51 49.47 53.79 67.94 75.52 82.10

1.52 1.69 1.78 3.90 4.33 4.57 5.57 6.18 6.53 9.77 10.85 11.46 13.58 15.08 15.92 23.08 25.64 27.06 51.58 57.30 60.48 78.73 87.46 92.31

1.71 1.89 2.00 4.38 4.86 5.13 6.25 6.94 7.32 10.98 12.18 12.86 15.25 16.93 17.86 25.93 28.77 30.37 57.94 64.31 67.87 88.44 98.16 103.60

R-134a NRV/H 6

NRV/H 10

NRV/H 12

NRV/H 16

NRV/H 19

NRV/H 22

NRV/H 28

NRV/H 35

The capacities are based on: Evaporating temperature te = 40° F Subcooling tsub = (tc – 10° F) Hot gas superheat ts = (tc +40° F) For each additional 10° F of superheat above 40° F, the table capacities must be reduced by 1%.

982

CHECK VALVES DANFOSS CHECK VALVES CAPACITY Hot Gas Capacity TYPE

HOT GAS TEMPERATURE tc °F

CAPACITY IN TONS AT PRESSURE DROP ACROSS VALVE ∆p psi 2 5 10 15 20 25

R- 404A/R-507 NRV/H 6

NRV/H 10

NRV/H 12

NRV/H 16

NRV/H 19

NRV/H 22

NRV/H 28

NRV/H 35

70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140

0.50 0.53 0.51 1.29 1.35 1.31 1.85 1.93 1.86 3.24 3.38 3.27 4.50 4.70 4.54 7.65 7.99 7.72 17.10 17.86 17.26 26.11 27.26 26.35

0.81 0.84 0.81 2.07 2.15 2.08 2.95 3.07 2.96 5.18 5.40 5.20 7.20 7.50 7.23 12.24 12.75 12.29 27.35 28.49 27.46 41.75 43.48 41.92

1.11 1.20 1.16 2.84 3.09 2.96 4.06 4.41 4.23 7.12 7.75 7.43 9.90 10.76 10.32 16.83 18.30 17.55 37.60 40.89 39.22 57.40 62.42 59.87

1.36 1.42 1.43 3.50 3.65 3.67 4.99 5.21 5.23 8.76 9.14 9.19 12.17 12.69 12.77 20.69 21.58 21.70 46.24 48.23 48.50 70.57 73.62 74.03

1.57 1.64 1.59 4.02 4.20 4.09 5.74 5.99 5.84 10.08 10.52 10.25 14.00 14.61 14.24 23.80 24.84 24.21 53.19 55.51 54.11 81.20 84.74 82.60

1.76 1.84 1.78 4.51 4.72 4.56 6.45 6.74 6.52 11.31 11.83 11.44 15.72 16.44 15.89 26.72 27.95 27.01 59.72 62.47 60.37 91.16 95.36 92.15

70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140 70 100 140

0.65 0.72 0.72 1.67 1.85 1.86 2.39 2.64 2.65 4.19 4.63 4.65 5.82 6.43 6.46 9.90 10.94 10.98 22.12 24.44 24.55 33.76 37.30 37.47

1.04 1.15 1.15 2.68 2.95 2.95 3.83 4.21 4.22 6.71 7.39 7.40 9.33 10.27 10.28 15.86 17.45 17.48 35.45 39.01 39.06 54.10 59.54 59.62

1.44 1.65 1.64 3.69 4.23 4.21 5.27 6.03 6.01 9.25 10.59 10.56 12.85 14.71 14.67 21.85 25.01 24.94 48.82 55.89 55.73 74.53 85.31 85.07

1.75 1.94 2.03 4.49 4.98 5.21 6.41 7.12 7.44 11.25 12.49 13.06 15.63 17.35 18.15 26.58 29.50 30.85 59.40 65.93 68.95 90.67 100.63 105.24

2.01 2.24 2.27 5.16 5.75 5.82 7.37 8.20 8.30 12.93 14.40 14.57 17.96 20.01 20.25 30.54 34.01 34.42 68.25 76.02 76.93 104.17 116.03 117.43

2.24 2.50 2.53 5.75 6.41 6.49 8.21 9.15 9.27 14.41 16.07 16.27 20.02 22.32 22.61 34.04 37.95 38.43 76.07 84.81 85.89 116.11 129.45 131.10

R-407C NRV/H 6

NRV/H 10

NRV/H 12

NRV/H 16

NRV/H 19

NRV/H 22

NRV/H 28

NRV/H 35

The capacities are based on: Evaporating temperature te = 40° F Subcooling tsub = (tc – 10° F) Hot gas superheat ts = (tc +40° F) For each additional 10° F of superheat above 40° F, the table capacities must be reduced by 1%.

983

CHECK VALVES DANFOSS CHECK VALVES

NRV/VRVH 6-19

NRV/NRVH 6s-19s NRV/NRVH 22s-42s VERSION

Flare Straightway

Solder Straightway

Solder Angleway

TYPE NRV 6 NRV 10 NRV 12 NRV 16 NRV 19 NRV/H 6s NRV/H 6s* NRV/H 10s NRV/H 10s* NRV/H 12s NRV/H 12s* NRV/H 16s NRV/H 16s* NRV/H 19s NRV/H 19s* NRV/H 22s NRV/H 22s* NRV/H 28s NRV/H 28s* NRV/H 35s NRV/H 35s*

*Oversize connections.

984

SIZE (in.) 1/4 3/8 1/2 5/8 3/4 1/4 3/8 3/8 1/2 1/2 5/8 5/8 3/4 3/4 7/8 7/8 1-1/8 1-1/8 1-3/8 1-3/8 1-5/8

H1 (in.)

3.701 3.701 5.551 5.551 5.551 5.551

H2 (in.)

1.850 1.850 2.559 2.559 2.559 2.559

L (in.) 2.205 2.362 2.717 3.150 3.470 3.622 3.622 4.291 4.291 5.157 5.157 5.433 5.433 6.496 6.496

L1 (in.)

0.276 0.354 0.354 0.394 0.394 0.472 0.472 0.551 0.551 0.669 0.669 0.866 0.866 0.984 0.984 1.142

L2 (in.)

DIA. D (in.)

3.465 3.465 4.843 4.843 4.843 4.843

0.709 0.709 0.787 0.787 0.866 0.866 1.102 1.102 1.339 1.339 1.417 1.417 1.890 1.890 1.890 1.890

PNRV-2

SPANNER FLATS S (in.) 0.748 0.787 0.945 1.102 1.339

WEIGHT (lbs) 0.2 0.4 0.4 0.7 0.9 0.2 0.4 0.4 0.4 0.4 0.4 0.7 0.7 0.9 0.9 1.1 1.1 2.4 2.4 2.4 2.4

SOLENOID VALVES DANFOSS SOLENOID VALVES INTRODUCTION This leaflet presents a newly extended program of Danfoss solenoid valves, type EVR. The program includes a new coil design, type GP, with quick and easy DanlokTM snap down mounting. EVR is a direct or servo operated solenoid valve for liquid, suction, and hot gas lines using fluorinated refrigerants. EVR valves are supplied as separate components; valve body and coil, if required, can be ordered separately.

FEATURES • A complete range of solenoid valves for refrigeration, freezing and air conditioning systems. • Normally closed (NC) and normally open (NO) versions available. • AC and DC coils are interchangeable on all valve body versions. • Use with any fluorinated refrigerant. • Designed for media temperatures up to 220° F. • Flare connections up to 5/8 in. • Solder connections up to 2-1/8 in. • Solder versions have extended connections; there is no need to dismantle the valve when soldering.

P4315

APPROVALS NOTE: These approvals are only recognized when one of the EVR series of solenoid valves found in this leaflet is combined with a GP general purpose coil. • UL listed, file MH 7648. • CSA certified, LR 52727. P4315A

TECHNICAL DATA Refrigerant: R-22, R-134a, R-404A, R-507, etc. Temperature of medium:

–40 to 220° F Maximum 265° F during defrosting

Maximum working pressure: EVR 2 to 10: EVR 15 to 22: EVR 25 to 40:

MWP = 500 psig MWP = 460 psig MWP = 400 psig

Enclosure of coil: NEMA 2 or NEMA 4

985

SOLENOID VALVES DANFOSS SOLENOID VALVES TECHNICAL DATA (cont) VALVE TYPE

Minimum

EVR 2 EVR 3 EVR 4 EVR 6 EVR 8 EVR 10 EVR 15 EVR 18 EVR 20 EVR 22 EVR 25 EVR 32 EVR 40

0.0 0.0 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 1.0 1.0 1.0

OPENING DIFFERENTIAL PRESSURE ∆p psi Maximum (= MOPD) liquid† AC DC 350 260 350 260 350 260 350 260‡ 350 260 350 260‡ 350 260‡ 350 260 350** 230** †† 350** 230** †† 350 205 350 205 350 205

MEDIUM TEMPERATURE (°F)

MAXIMUM WORKING PRESSURE MWP (psig)

Cv VALUE* (gal/min)

–40 to 220 –40 to 220 –40 to 220 –40 to 220 –40 to 220 –40 to 220 –40 to 220 –40 to 220 –40 to 220 –40 to 220 –40 to 220 –40 to 220 –40 to 220

500 500 500 500 500 500 500 500 500 500 400 400 400

0.19 0.32 0.66 0.93 1.3 2.2 3.0 3.9 5.8 6.9 12.0 18.0 29.0

*Cv value is the water flow in gal/min at a pressure drop across valve ∆p = 1 psi, ρ = 10 lbs/gal. †MOPD for media in gas form is approximately 14 psi greater. ‡EVR (NO): 300 psig. **EVR (NO): 275 psig. ††DC coils for EVR 20 and EVR 22: 190 psig.

VALVE TYPE

Liquid R-134a 0.89

R-404A/R-507 0.80

RATED CAPACITY* (Tons) Suction Vapor R-22 R-134a R-404A/R-507 0.10 0.07 0.09

R-22 0.22

Hot Gas R-134a R-404A/R-507

EVR 2

R-22 1.17

0.18

0.17

EVR 3

2.03

1.55

1.40

0.17

0.13

0.15

0.38

0.31

0.30

EVR 4

4.15

3.16

2.86

0.34

0.26

0.30

0.77

0.63

0.62

EVR 6

5.83

4.43

4.01

0.48

0.37

0.43

1.08

0.88

0.87

EVR 8

8.01

6.09

5.52

0.66

0.51

0.58

1.49

1.21

1.19

9.53

1.15

0.88

1.01

2.57

2.10

2.06

EVR 10

13.8

10.5

EVR 15

18.9

14.4

13.0

1.57

1.20

1.38

3.52

2.87

2.82

EVR 18

24.6

18.7

17.0

2.04

1.56

1.80

4.57

3.73

3.67

EVR 20

36.4

27.7

25.1

3.02

2.31

2.66

6.76

5.51

5.43

EVR 22

43.7

33.3

30.1

3.62

2.78

3.19

8.11

6.62

EVR 25

72.8

55.4

50.2

6.04

4.63

5.32

EVR 32

116.5

88.7

80.3

EVR 40

182.0

138.5

125.4

*Rated liquid and suction vapor capacity are based on: Evaporating temperature te = 40° F Liquid temperature ahead of valve tl = 100° F Pressure drop ∆p across valve - with liquid - with suction vapor Rated hot gas capacity is based on: Condensing temperature tc = 100° F Hot gas temperature th = 140° F Pressure drop across valve ∆p = 2 psi

986

9.66 16.1

7.40 11.6

8.51 13.3

∆p = 2 psi for R-134a ∆p = 3 psi for R-22, R-404A and R-507 ∆p = 1 psi

6.52

13.5

11.0

10.9

21.6

17.7

17.4

33.8

27.6

27.2

SOLENOID VALVES DANFOSS SOLENOID VALVES CROSS REFERENCE Separate valve bodies for EVR, normally closed (NC).

TYPE EVR 2 EVR 3 EVR 3 EVR 4 EVR 4 EVR 6 EVR 6 EVR 6 EVR 8 EVR 8 EVR 8 EVR 10 EVR 10 EVR 10 EVR 15 EVR 15 EVR 18 EVR 18 EVR 20 EVR 20 EVR 22 EVR 22 EVR 25 EVR 25 EVR 32 EVR 32 EVR 32 EVR 40 EVR 40

With Manual Stem (in.)

32F1185

CODE NUMBERS (Valve Body Excl. Coil) Flare Totaline Without Totaline Part No. Manual Stem Part No. (formerly) (in.) (formerly) 32F7101 32F1155 P510-A02F02SD 32F1154 P510-A02F03SD 32F7112 32F7113 P510-B04F03MD 32F1160 P510-B04F03MD 32F1159 P510-B04F04SD

32F7123

32F1187

P510-B06F04MD

32F1165 32F1167

P510-B06F04SD P510-B06F05SD

Solder ODF With Without Manual Stem Manual Stem (in.) (in.) 32F7100 32F7105 32F1157 32F7110 32F7111 32F7116 32F7115 32F1162 32F7117 32F7120 32F7121 32F7122 32F7125 32F1188 32F1166 32F1168 32F1172 32F1171 32F7130 32F7135 32F7136 32F1177 32F1176 32F1178 32F7145 32F7146 32F1190 32F1189 32F1194 32F1193 42H1177 42H1176 42H1179 42H1178 42H1181 42H1180 42H1186 42H1185 42H1188 42H1187

987

SOLENOID VALVES DANFOSS SOLENOID VALVES CAPACITY — LIQUID NOTE: Bold figures refer to rated capacity. TYPE

LIQUID CAPACITY Q0 TONS AT PRESSURE DROP ACROSS VALVE ∆p psi 1

2

3

4

5

6

7

EVR 2 EVR 3 EVR 4 EVR 6 EVR 8 EVR 10 EVR 15 EVR 18 EVR 20 EVR 22 EVR 25 EVR 32 EVR 40

0.67 1.18 2.40 3.37 4.62 7.99 10.9 14.2 21.0 25.2 42.1 67.3 105.0

0.95 1.66 3.39 4.76 6.54 11.3 15.5 20.1 29.7 35.7 59.5 95.1 148.6

1.17 2.03 4.15 5.83 8.01 13.8 18.9 24.6 36.4 43.7 72.8 116.5 182.0

1.35 2.35 4.79 6.73 9.24 16.0 21.9 28.4 42.0 50.4 84.1 134.0 210.0

1.50 2.63 5.36 7.52 10.3 17.9 24.4 31.8 47.0 56.4 94.0 150.0 235.0

1.65 2.88 5.87 8.24 11.3 19.6 26.8 34.8 51.5 61.8 103.0 164.8 257.0

1.78 3.11 6.34 8.90 12.2 21.1 28.9 37.6 55.6 66.7 111.0 177.0 278.0

EVR 2 EVR 3 EVR 4 EVR 6 EVR 8 EVR 10 EVR 15 EVR 18 EVR 20 EVR 22 EVR 25 EVR 32 EVR 40

0.63 1.10 2.23 3.14 4.31 7.45 10.2 13.3 19.6 23.5 39.2 62.7 98.0

0.89 1.55 3.16 4.43 6.09 10.5 14.4 18.7 27.7 33.3 55.4 88.7 138.5

1.09 1.90 3.87 5.43 7.46 12.9 17.7 23.0 33.9 40.7 67.9 108.0 169.0

1.25 2.19 4.47 6.27 8.62 14.9 20.4 26.5 39.2 47.0 78.4 125.0 195.0

1.40 2.45 5.00 7.01 9.63 16.7 22.8 29.6 43.8 52.6 87.6 140.0 219.0

1.54 2.68 5.47 7.68 10.6 18.2 25.0 32.4 48.0 57.6 96.0 153.0 239.0

EVR EVR 3 EVR 4 EVR 6 EVR 8 EVR 10 EVR 15 EVR 18 EVR 20 EVR 22 EVR 25 EVR 32 EVR 40

0.46 0.81 1.65 2.32 3.18 5.50 7.53 9.79 14.5 17.4 29.0 46.3 72.4

0.66 1.14 2.33 3.28 4.50 7.78 10.6 13.8 20.5 24.6 40.9 65.5 102.0

0.80 1.40 2.86 4.01 5.52 9.53 13.0 17.0 25.1 30.1 50.2 80.3 125.0

0.93 1.62 3.30 4.63 6.37 11.0 15.1 19.6 29.0 34.7 57.9 92.6 144.0

1.04 1.81 3.69 5.18 7.12 12.3 16.8 21.9 32.4 38.8 64.7 103.6 162.0

R-22

R-134a 1.66 2.90 5.91 8.30 11.4 19.7 27.0 35.0 51.8 62.2 103.0 165.0 259.0

R-404A and R-507 1.13 1.98 4.04 5.67 7.80 13.5 18.4 24.0 35.5 42.5 70.9 113.0 177.0

1.23 2.14 4.37 6.13 8.42 14.6 19.9 25.9 38.3 46.0 76.6 121.0 191.0

Capacities are based on: Liquid temperature tl = 100° F Evaporating temperature te = 40° F Superheat temperature (te + 10° F) = 50° F Correction factors for liquid temperature tl When liquid temperature tl ahead of the expansion valve is other than 100° F, adjust the table capacities by multiplying them by the appropriate correction factor found in the following table. tl °F Factor

988

80 1.10

90 1.05

100 1.00

110 0.95

120 0.90

SOLENOID VALVES DANFOSS SOLENOID VALVES CAPACITY — SUCTION VAPOR NOTE: Bold figures refer to rated capacity. TYPE

PRESSURE DROP ACROSS VALVE ∆p psi

SUCTION VAPOR CAPACITY Q0 TONS AT EVAPORATING TEMPERATURE te °F –40

–20

0

+10

+20

+30

+40

+50

R-22 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

EVR 2

EVR 3

EVR 4

EVR 6

EVR 8

EVR 10

EVR 15

EVR 18

EVR 20

EVR 22

EVR 25

EVR 32

EVR 40

0.04 0.05 0.06 0.06 0.09 0.10 0.13 0.18 0.21 0.18 0.25 0.29 0.25 0.34 0.40 0.44 0.59 0.69 0.60 0.80 0.94 0.78 1.04 1.22 1.15 1.54 1.81 1.38 1.85 2.17 2.30 3.09 3.61 3.68 4.94 5.78 5.74 7.71 9.03

0.05 0.07 0.08 0.09 0.12 0.14 0.18 0.24 0.28 0.25 0.33 0.40 0.34 0.46 0.55 0.59 0.79 0.94 0.81 1.08 1.29 1.05 1.41 1.68 1.56 2.08 2.48 1.87 2.50 2.97 3.12 4.17 4.96 4.99 6.67 7.93 7.80 10.4 12.4

0.06 0.09 0.10 0.11 0.15 0.18 0.22 0.31 0.37 0.32 0.43 0.52 0.43 0.59 0.71 0.75 1.02 1.23 1.02 1.40 1.68 1.33 1.82 2.19 1.97 2.69 3.23 2.36 3.23 3.88 3.94 5.38 6.47 6.30 8.61 10.4 9.85 13.5 16.2

0.07 0.10 0.12 0.12 0.18 0.20 0.25 0.36 0.42 0.35 0.50 0.59 0.49 0.69 0.80 0.84 1.19 1.39 1.15 1.63 1.90 1.50 2.12 2.47 2.22 3.13 3.66 2.66 3.76 4.39 4.43 6.27 7.32 7.09 10.0 11.7 11.1 15.7 18.3

0.08 0.11 0.13 0.14 0.19 0.23 0.28 0.40 0.47 0.39 0.56 0.66 0.54 0.77 0.91 0.94 1.32 1.57 1.28 1.81 2.14 1.66 2.35 2.79 2.46 3.48 4.12 2.95 4.18 4.94 4.92 6.96 8.24 7.88 11.1 13.2 12.3 17.4 20.6

0.09 0.12 0.15 0.15 0.22 0.26 0.31 0.44 0.54 0.44 0.62 0.76 0.60 0.85 1.04 1.04 1.47 1.80 1.42 2.01 2.46 1.84 2.61 3.20 2.72 3.86 4.73 3.27 4.63 5.67 5.45 7.71 9.45 8.72 12.3 15.1 13.6 19.3 23.6

0.10 0.14 0.17 0.17 0.24 0.29 0.34 0.49 0.60 0.48 0.68 0.84 0.66 0.94 1.15 1.15 1.62 1.98 1.57 2.22 2.71 2.04 2.88 3.53 3.02 4.27 5.22 3.62 5.12 6.26 6.04 8.53 10.4 9.66 13.6 16.7 16.1 21.3 26.1

0.11 0.15 0.18 0.19 0.26 0.32 0.38 0.54 0.66 0.53 0.75 0.92 0.73 1.03 1.26 1.26 1.78 2.18 1.72 2.44 2.99 2.24 3.17 3.88 3.32 4.69 5.74 3.98 5.63 6.89 6.63 9.39 11.5 10.6 15.0 18.4 16.6 23.5 28.7

The table values refer to evaporator capacity and are given as a function of evaporating temperature te and pressure drop ∆p across the valve. Capacities are based on: Liquid temperature tl = 100° F ahead of the expansion valve and superheat ts = 7° F. For each additional 10° F of superheat, the table capacities must be reduced by 2%. Correction factors for liquid temperature tl When liquid temperature tl ahead of the expansion valve is other than 100° F, adjust the table capacities by multiplying them by the appropriate correction factor found in the following table. tl °F Factor

80 1.10

90 1.05

100 1.00

110 0.95

120 0.90

989

SOLENOID VALVES DANFOSS SOLENOID VALVES CAPACITY — SUCTION VAPOR NOTE: Bold figures refer to rated capacity. TYPE

PRESSURE DROP ACROSS VALVE ∆p psi

SUCTION VAPOR CAPACITY Q0 TONS AT EVAPORATING TEMPERATURE te °F –40

–20

0

+10

+20

+30

+40

+50

R-134a 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

EVR 2

EVR 3

EVR 4

EVR 6

EVR 8

EVR 10

EVR 15

EVR 18

EVR 20

EVR 22

EVR 25

EVR 32

EVR 40

0.02 0.03 0.03 0.04 0.05 0.06 0.08 0.10 0.11 0.11 0.14 0.16 0.16 0.20 0.22 0.27 0.34 0.37 0.37 0.47 0.51 0.48 0.61 0.67 0.71 0.90 0.98 0.85 1.08 1.18 1.41 1.81 1.97 2.26 2.89 3.15 3.53 4.51 4.92

0.03 0.04 0.05 0.06 0.08 0.09 0.11 0.15 0.18 0.16 0.22 0.25 0.22 0.30 0.34 0.38 0.51 0.59 0.52 0.70 0.80 0.68 0.91 1.04 1.00 1.35 1.54 1.20 1.62 1.85 2.00 2.69 3.09 3.20 4.31 4.94 5.01 6.73 7.71

0.05 0.06 0.07 0.08 0.10 0.12 0.16 0.21 0.25 0.23 0.30 0.35 0.31 0.41 0.49 0.54 0.71 0.84 0.73 0.97 1.15 0.95 1.26 1.50 1.41 1.87 2.22 1.69 2.25 2.66 2.82 3.74 4.43 4.52 5.99 7.09 7.06 9.35 11.1

0.05 0.07 0.08 0.09 0.12 0.14 0.18 0.25 0.30 0.26 0.35 0.42 0.35 0.48 0.57 0.61 0.82 0.99 0.84 1.13 1.35 1.09 1.46 1.75 1.61 2.17 2.59 1.93 2.60 3.11 3.22 4.33 5.19 5.15 6.93 8.30 8.04 10.8 13.0

0.06 0.08 0.10 0.10 0.14 0.17 0.21 0.28 0.34 0.29 0.40 0.48 0.40 0.55 0.65 0.69 0.94 1.13 0.95 1.29 1.54 1.23 1.68 2.01 1.82 2.48 2.97 2.19 2.97 3.56 3.64 4.96 5.94 5.83 7.93 9.51 9.11 12.4 14.9

0.07 0.09 0.11 0.12 0.16 0.19 0.24 0.33 0.39 0.33 0.47 0.55 0.45 0.64 0.75 0.79 1.11 1.30 1.08 1.52 1.78 1.40 1.98 2.31 2.07 2.92 3.41 2.48 3.51 4.10 4.14 5.84 6.83 6.62 9.35 10.9 10.3 14.6 17.1

0.07 0.11 0.12 0.13 0.18 0.22 0.26 0.37 0.44 0.37 0.53 0.62 0.51 0.72 0.85 0.88 1.25 1.47 1.20 1.71 2.01 1.56 2.22 2.62 2.31 3.28 3.87 2.78 3.94 4.65 4.63 6.56 7.75 7.40 10.5 12.4 11.6 16.4 19.4

0.08 0.12 0.14 0.14 0.21 0.25 0.30 0.42 0.51 0.42 0.59 0.72 0.57 0.81 0.99 0.99 1.40 1.71 1.35 1.91 2.34 1.75 2.49 3.04 2.59 3.68 4.50 3.11 4.41 5.40 5.19 7.35 8.99 8.30 11.8 14.4 13.0 18.4 22.5

The table values refer to evaporator capacity and are given as a function of evaporating temperature te and pressure drop ∆p across the valve. Capacities are based on: Liquid temperature tl = 100° F ahead of the expansion valve and superheat ts = 7° F. For each additional 10° F of superheat, the table capacities must be reduced by 2%. Correction factors for liquid temperature tl When liquid temperature tl ahead of the expansion valve is other than 100° F, adjust the table capacities by multiplying them by the appropriate correction factor found in the following table. tl °F Factor

990

80 1.10

90 1.05

100 1.00

110 0.95

120 0.90

SOLENOID VALVES DANFOSS SOLENOID VALVES CAPACITY — SUCTION VAPOR NOTE: Bold figures refer to rated capacity. TYPE

PRESSURE DROP ACROSS VALVE ∆p psi

SUCTION VAPOR CAPACITY Q0 TONS AT EVAPORATING TEMPERATURE te °F –40

–20

0

+10

+20

+30

+40

+50

R-404A and R-507 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

EVR 2

EVR 3

EVR 4

EVR 6

EVR 8

EVR 10

EVR 15

EVR 18

EVR 20

EVR 22

EVR 25

EVR 32

EVR 40

0.03 0.04 0.05 0.05 0.07 0.08 0.10 0.14 0.16 0.14 0.20 0.23 0.20 0.27 0.32 0.34 0.47 0.55 0.47 0.64 0.75 0.61 0.83 0.98 0.90 1.23 1.44 1.08 1.48 1.73 1.81 2.46 2.89 2.89 3.94 4.62 4.51 6.15 7.22

0.04 0.05 0.06 0.07 0.09 0.11 0.14 0.19 0.23 0.20 0.27 0.32 0.27 0.37 0.44 0.47 0.64 0.77 0.65 0.88 1.05 0.84 1.14 1.36 1.25 1.69 2.02 1.50 2.03 2.42 2.49 3.38 4.04 3.99 5.41 6.46 6.24 8.45 10.1

0.05 0.08 0.09 0.09 0.13 0.15 0.19 0.27 0.31 0.26 0.38 0.44 0.36 0.52 0.60 0.62 0.89 1.04 0.85 1.22 1.43 1.11 1.59 1.85 1.64 2.35 2.74 1.97 2.82 3.29 3.28 4.69 5.48 5.25 7.51 8.77 8.21 11.7 13.7

0.06 0.09 0.10 0.11 0.15 0.18 0.22 0.30 0.36 0.30 0.43 0.50 0.42 0.58 0.69 0.72 1.01 1.20 0.99 1.38 1.64 1.29 1.80 2.13 1.90 2.66 3.15 2.28 3.19 3.78 3.81 5.32 6.30 6.09 8.51 10.1 9.5 13.3 15.8

0.07 0.10 0.12 0.12 0.17 0.20 0.24 0.34 0.42 0.34 0.48 0.59 0.47 0.66 0.80 0.80 1.14 1.39 1.10 1.55 1.90 1.43 2.02 2.47 2.12 2.99 3.66 2.54 3.58 4.39 4.23 5.97 7.32 6.77 9.56 11.7 10.6 14.9 18.3

0.08 0.11 0.13 0.13 0.19 0.23 0.27 0.39 0.47 0.38 0.54 0.66 0.52 0.74 0.91 0.90 1.28 1.57 1.24 1.76 2.15 1.61 2.29 2.80 2.38 3.38 4.14 2.86 4.06 4.96 4.76 6.76 8.27 7.62 10.8 13.2 11.9 16.9 20.7

0.09 0.12 0.15 0.15 0.21 0.26 0.30 0.43 0.53 0.43 0.60 0.74 0.58 0.83 1.01 1.01 1.43 1.75 1.38 1.95 2.40 1.80 2.54 3.12 2.66 3.76 4.61 3.19 4.51 5.53 5.32 7.52 9.22 8.51 12.0 14.8 13.3 18.8 23.1

0.10 0.13 0.16 0.17 0.23 0.29 0.34 0.48 0.59 0.48 0.67 0.82 0.65 0.92 1.13 1.13 1.60 1.96 1.54 2.18 2.68 2.01 2.84 3.48 2.97 4.20 5.15 3.56 5.04 6.18 5.94 8.40 10.31 9.51 13.4 16.5 14.9 21.0 25.8

The table values refer to evaporator capacity and are given as a function of evaporating temperature te and pressure drop ∆p across the valve. Capacities are based on: Liquid temperature tl = 100° F ahead of the expansion valve and superheat ts = 7° F. For each additional 10° F of superheat, the table capacities must be reduced by 2%. Correction factors for liquid temperature tl When liquid temperature tl ahead of the expansion valve is other than 100° F, adjust the table capacities by multiplying them by the appropriate correction factor found in the following table. tl °F Factor

80 1.10

90 1.05

100 1.00

110 0.95

120 0.90

991

SOLENOID VALVES DANFOSS SOLENOID VALVES CAPACITY — HOT GAS NOTE: Bold figures refer to rated capacity.

EVR 2 to EVR 18

TYPE

EVR 2

EVR 3

EVR 4

EVR 6

EVR 8

EVR 10

EVR 15

EVR 18

PRESSURE DROP ACROSS VALVE ∆p psi 2 5 10 15 20 25 2 5 10 15 20 25 2 5 10 15 20 25 2 5 10 15 20 25 2 5 10 15 20 25 2 5 10 15 20 25 2 5 10 15 20 25 2 5 10 15 20 25

HOT GAS CAPACITY Qh TONS EVAPORATING TEMP te = +40° F, HOT GAS TEMP. th = tc + 40° F, SUBCOOLING ∆tu = 10° F R-22 R-134a R-404A/R-507 Condensing Temp. tc °F Condensing Temp. tc °F Condensing Temp. tc °F +70 +100 +140 +70 +100 +140 +70 +100 +140 0.20 0.22 0.23 0.16 0.18 0.18 0.17 0.17 0.17 0.31 0.35 0.37 0.26 0.28 0.29 0.27 0.28 0.27 0.43 0.49 0.53 0.35 0.39 0.42 0.37 0.40 0.38 0.53 0.58 0.65 0.43 0.48 0.52 0.45 0.47 0.47 0.60 0.67 0.73 0.50 0.56 0.59 0.52 0.54 0.53 0.67 0.75 0.81 0.56 0.63 0.66 0.58 0.61 0.59 0.34 0.38 0.41 0.28 0.31 0.32 0.29 0.30 0.29 0.55 0.60 0.64 0.45 0.49 0.51 0.47 0.48 0.47 0.75 0.86 0.92 0.62 0.69 0.74 0.64 0.70 0.67 0.92 1.02 1.14 0.76 0.84 0.91 0.79 0.82 0.82 1.05 1.18 1.27 0.88 0.97 1.03 0.90 0.94 0.92 1.18 1.31 1.42 0.99 1.09 1.15 1.02 1.06 1.03 0.70 0.77 0.83 0.57 0.63 0.66 0.59 0.62 0.60 1.12 1.23 1.32 0.92 1.01 1.05 0.95 0.99 0.95 1.54 1.76 1.88 1.26 1.40 1.50 1.30 1.42 1.36 1.87 2.08 2.32 1.54 1.72 1.87 1.60 1.67 1.68 2.15 2.40 2.59 1.79 1.99 2.10 1.85 1.93 1.88 2.40 2.67 2.89 2.01 2.23 2.35 2.07 2.17 2.09 0.98 1.08 1.16 0.80 0.88 0.92 0.83 0.87 0.84 1.57 1.73 1.85 1.29 1.41 1.47 1.33 1.39 1.34 2.16 2.47 2.63 1.77 1.96 2.11 1.83 1.99 1.91 2.63 2.92 3.26 2.17 2.41 2.62 2.25 2.35 2.36 3.02 3.37 3.64 2.51 2.79 2.94 2.59 2.70 2.63 3.37 3.75 4.06 2.82 3.13 3.30 2.91 3.04 2.94 1.35 1.49 1.60 1.10 1.21 1.27 1.14 1.19 1.16 2.15 2.37 2.54 1.78 1.94 2.03 1.83 1.91 1.84 2.97 3.40 3.62 2.43 2.70 2.90 2.52 2.74 2.62 3.61 4.01 4.48 2.98 3.31 3.60 3.09 3.23 3.25 4.15 4.62 5.00 3.45 3.83 4.05 3.56 3.71 3.62 4.63 5.16 5.58 3.88 4.30 4.54 4.00 4.18 4.04 2.33 2.57 2.76 1.90 2.10 2.20 1.98 2.06 2.00 3.72 4.10 4.38 3.07 3.36 3.50 3.16 3.29 3.17 5.13 5.87 6.26 4.20 4.66 5.01 4.35 4.73 4.53 6.24 6.93 7.74 5.15 5.72 6.22 5.34 5.58 5.61 7.17 7.99 8.63 5.96 6.62 6.99 6.15 6.42 6.26 8.00 8.91 9.64 6.70 7.43 7.85 6.90 7.22 6.98 3.18 3.52 3.77 2.60 2.87 3.00 2.71 2.82 2.73 5.09 5.61 6.00 4.20 4.59 4.79 4.33 4.51 4.34 7.02 8.04 8.56 5.74 6.38 6.85 5.95 6.47 6.20 8.54 9.48 10.6 7.04 7.83 8.51 7.31 7.63 7.67 9.81 10.9 11.8 8.16 9.06 9.57 8.41 8.78 8.56 10.9 12.2 13.2 9.2 10.2 10.7 9.45 9.88 9.55 4.14 4.57 4.90 3.38 3.73 3.91 3.52 3.67 3.55 6.62 7.29 7.80 5.46 5.97 6.22 5.63 5.86 5.65 9.13 10.5 11.1 7.47 8.29 8.91 7.73 8.41 8.07 11.1 12.3 13.8 9.15 10.2 11.1 9.51 9.92 9.98 12.8 14.2 15.4 10.6 11.8 12.4 10.9 11.4 11.1 14.2 15.9 17.2 11.9 13.2 14.0 12.3 12.9 12.4

Correction Factors for th and te The table values refer to hot gas capacity and are given as a function of condensing temperature tc and pressure drop ∆p across the valve. Capacities are based on a hot gas temperature superheated 40° F above condensing temperature (th = tc + 40° F). For each additional 10° F of superheat above 40° F, the table capacities must be reduced by 1%.

992

When the valve is used in a hot gas defrost circuit, evaporator temperature affects the capacity. When the evaporator temperature differs from +40° F, adjust the table capacities by multiplying them by the appropriate correction factor found in the following table. te °F Factor

-40 1.18

-20 1.14

0 1.09

20 1.04

40 1

50 0.97

SOLENOID VALVES DANFOSS SOLENOID VALVES CAPACITY — HOT GAS NOTE: Bold figures refer to rated capacity.

EVR 20 to EVR 40

TYPE

EVR 20

EVR 22

EVR 25

EVR 32

EVR 40

PRESSURE DROP ACROSS VALVE ∆p psi 2 5 10 15 20 25 2 5 10 15 20 25 2 5 10 15 20 25 2 5 10 15 20 25 2 5 10 15 20 25

HOT GAS CAPACITY Qh TONS EVAPORATING TEMP te = +40° F, HOT GAS TEMP. th = tc + 40° F, SUBCOOLING ∆tu = 10° F R-22 R-134a R-404A/R-507 Condensing Temp. tc °F Condensing Temp. tc °F Condensing Temp. tc °F +70 +100 +140 +70 +100 +140 +70 +100 +140 6.12 6.76 7.25 5.01 5.51 5.78 5.20 5.43 5.25 9.80 10.8 11.5 8.07 8.83 9.21 8.32 8.67 8.35 13.5 15.5 16.5 11.1 12.3 13.2 11.4 12.4 11.9 16.4 18.2 20.4 13.5 15.1 16.4 14.1 14.7 14.8 18.9 21.0 22.7 15.7 17.4 18.4 16.2 16.9 16.5 21.0 23.5 25.4 17.6 19.6 20.7 18.2 19.0 18.4 7.35 8.11 8.71 6.01 6.62 6.93 6.24 6.52 6.30 11.8 12.9 13.9 9.69 10.6 11.1 9.99 10.4 10.0 16.2 18.6 19.8 13.3 14.7 15.8 13.7 14.9 14.3 19.7 21.9 24.4 16.3 18.1 19.6 16.9 17.6 17.7 22.7 25.2 27.3 18.8 20.9 22.1 19.4 20.3 19.8 25.3 28.1 30.5 21.2 23.5 24.8 21.8 22.8 22.0 12.2 13.5 14.5 10.0 11.0 11.6 10.4 10.9 10.5 19.6 21.6 23.1 16.2 17.7 18.4 16.6 17.3 16.7 27.0 30.9 32.9 22.1 24.5 26.4 22.9 24.9 23.9 32.9 36.5 40.7 27.1 30.1 32.7 28.1 29.4 29.5 37.8 42.1 45.4 31.4 34.9 36.8 32.4 33.8 32.9 42.1 46.9 50.8 35.3 39.1 41.3 36.3 38.0 36.7 19.6 21.6 23.2 16.0 17.7 18.5 16.7 17.4 16.8 31.4 34.5 36.9 25.8 28.3 29.5 26.6 27.7 26.7 43.2 49.5 52.7 35.3 39.2 42.2 36.6 39.8 28.2 52.6 58.4 65.2 43.3 48.2 52.4 45.0 47.0 47.2 60.4 67.3 72.7 50.2 55.8 58.9 51.8 54.0 52.7 67.3 75.1 81.2 56.4 62.6 66.1 58.1 60.3 58.8 30.6 33.8 36.3 25.0 27.6 28.9 26.0 27.2 26.3 49.0 53.9 57.7 40.4 44.2 46.0 41.6 43.3 41.8 67.5 77.3 82.3 55.2 61.3 65.9 57.2 62.2 59.7 82.1 91.1 101.0 67.7 75.3 81.8 70.3 73.4 73.8 94.4 105.0 113.0 78.5 87.2 92.0 80.9 84.4 82.3 105.0 117.0 126.0 88.1 97.8 103.0 90.8 95.0 91.8

Correction Factors for th and te The table values refer to hot gas capacity and are given as a function of condensing temperature tc and pressure drop ∆p across the valve. Capacities are based on a hot gas temperature superheated 40° F above condensing temperature (th = tc + 40° F). For each additional 10° F of superheat above 40° F, the table capacities must be reduced by 1%. When the valve is used in a hot gas defrost circuit, evaporator temperature affects the capacity. When the evaporator temperature differs from +40° F, adjust the table capacities by multiplying them by the appropriate correction factor found in the following table. te °F Factor

-40 1.18

-20 1.14

0 1.09

20 1.04

40 1

50 0.97

993

SOLENOID VALVES DANFOSS SOLENOID VALVES — GENERAL PURPOSE COIL, TYPE GP INTRODUCTION The GP is a general purpose solenoid valve coil with Danlok™ snap-on mounting to make installation faster, easier and more secure.

FEATURES • • • • •

Mount and dismount without tools. No loose parts during mounting or operation. Suitable for all standard Danfoss solenoid valves. Available with terminal box or conduit boss connection. Dual voltage models available.

APPROVALS

P1013

• UL listed, file MH 7648. • CSA certified, LR 52727. NOTE: These approvals are only recognized when one of the EVR series of solenoid valves is combined with a GP general purpose coil.

TECHNICAL DATA Enclosure:

With junction box, NEMA 2. With conduit boss, NEMA 4.

Ambient temperature: -40 to +120° F.

994