Refrigerant Dryers Refrigerant Compressed Air Dryer with integrated DF Filters

Refrigerant Dryers Refrigerant Compressed Air Dryer with integrated DF Filters BURAN DC 0020 AB - DC 0850 AB MAIN FEATURES & BENEFITS Sterile P-BE ...
Author: Muriel Quinn
10 downloads 0 Views 1MB Size
Refrigerant Dryers Refrigerant Compressed Air Dryer with integrated DF Filters BURAN DC 0020 AB - DC 0850 AB MAIN FEATURES & BENEFITS

Sterile

P-BE

● Purification package incl. refrigerant dryer with integrated pre- and afterfilters and condensate drains. ● Integrated pre filter, type V, for protection of the compressed air dryer against contaminations; Integrated afterfilter UltraPleat® M for the removal of oil aerosols and particles with high retention effiency and very low differential pressure; Safe compliance with the compressed air quality at low energy costs. ● Extremely compact design with robust steel housing. No additional pipings for installation of pre-and afterfilter required. ● Electronic level-controlled condensate drain incl. function monitoring and alarm messages for discharging of the Process Filtration compressed air condensate at the heat exchanger. Optional with pre-and afterfilter upgradeable. ● Electronic controller with dewpoint indicator, operating time counter, alarm display, service display and operating display for compressed air dryer and fan. ● 17 sizes for nominal flow rates up to 850 m³/h enable accurate selection of the suitable refrigerated compressed air dryer on the respective actual flow rate.

Condensate

UFM-D

Steam

Gases

P-EG

P-EG

PG-EG

P-EG

UFM-P

UFS-SP N

P-BE

PG-EG

(P)-SRF N

(P)-SRF N

PF-EG

P-KG

(P)-SM N

P-EGS

(P)-BE

PG-EG

Liquid

PP-TF

(P)-PP (P)-PP 100

PP 100 C

(P)-PF-PT

UFA-AC

(P)-PF-PP

(P)-GS N

(P)-PF-PES „W“

(P)-PF-PT

(P)-BE

(P)-GSL N

UFTD

R-EG P-SLF

INDUSTRIES

(P)-GSL N

(P)-PF-PP

PP-FC PP-FC 100

PF-PES „B“ PF-PES „X“

(P)-GSL N

● Chemical and electrical industry ● Machine building industry and plant engineering / construction ● Automotive industry Donaldson Filtration Deutschland GmbH Büssingstr. 1 D-42781 Haan Tel.: +49 (0) 2129 569 0 Fax: +49 (0) 2129 569 100 E-Mail: [email protected] Web: www.donaldson.com

BURAN DC 0020 AB - DC 0850 AB

Refrigerant Dryers

BURAN DC 0020 AB - DC 0850 AB

PRODUCT DESCRIPTION The compressed air is being fed into the dryer and being pre-cooled in the air-to-air heat exchanger by the outgoing cold compressed air.The pre-cooled air then passes through the refrigerant-to-air heat exchanger where it is being further cooled down to the required pressure dew point. The moisture in the compressed air condenses out and gathers and discharges automatically. Finally, the cold discharged air is being reheated by the incoming compressed air. This saves energy and prevents any moisture forming beyond the dryer in the compressed air system. The cooling capacity of the refrigeration cycle is being controlled by a hot gas bypass which assures the dryer functionabilty for partial loads, too.

Technical Data Sheet

2/5

Typical applications for the fridge dryers DC 0020 AB - DC 0850 AB are: ● Central compressed air purification Generation of dry, oil-free and particulate-free compressed air

● Automotive industry Purification of compressed air for painting applications

Refrigerant Dryers

BURAN DC 0020 AB - DC 0850 AB

PRODUCT SPECIFICATIONS Features:

Benefits:

Intelligent over-all concept

Type range, filter performance data, integrated monitoring functions as well as automatic condensate drain adapted for the use in central compressed air applications

Integrated pre-and afterfilter with condensate drain

Pre filter, type V, for protection of the compressed air dryer against contaminations; Afterfilter UltraPleat® M for the removal of oil aerosols and particles with high retention effiency and very low differential pressure; Safe compliance with the compressed air quality at low energy costs.

Validated performance data acc. to ISO 12500-1 and ISO 12500-3 for the integrated pre-and afterfilter

Reliable achievement of the compressed air quality according to ISO 8573-1

Compact and space-saving design with robust steel housing

Little space required at the installation site, no additional piping for the installation of pre-and afterfilter required, low storage space requirements and low transport costs

Electronic level-controlled condensate drain UFM-D at the heat exchanger

No expensive pressure drops, condensate discharge depending on the amount of condensate

Electronic controller with dewpoint indicator, operating time counter, alarm display, service display and operating display for compressed air dryer and fan; potential-free error message

Reliable monitoring of the operating condition and timely display of necessary maintenance work; Remote monitoring via potential-free error message possible

High load capacity up to pressure dew point of + 20°C

In case of overload the refrigerant compressed air dryer switches off only at a pressure dewpoint upper than +20°C

Aluminium heat exchanger

No corrosion within the heat exchanger by contact with moist compressed air; good heat transfer properties combined with low weight

Technical Data Operating pressure:

DC 0020 AB - DC 0125 AB: min. 2 bar (g) / max. 16 bar (g) DC 0150 AB - DC 0850 AB: min. 2 bar (g) / max. 14 bar (g)

Ambient temperature:

min. +2°C / max. +50°C

Medium temperature:

max. +70°C

Medium:

Compressed air

Refrigerant:

DC 0020 AB - DC 0150 AB: R134a DC 0180 AB - DC 0850 AB: R407C

Noise pressure level:

< 70 dB (A)

Power supply:

DC 0020 AB - DC 0105 AB: 230V / 1~ / 50-60 Hz DC 0180 AB - DC 0850 AB: 230V / 1~ / 50 Hz or 60 Hz

Protection class:

IP 22

Declaration of Conformity Types DC 0020 AB - DC 0850 AB:

Technical Data Sheet

acc. to directive 2006/42/EG appendix IIA

3/5

BURAN DC 0020 AB - DC 0850 AB

Refrigerant Dryers

PRODUCT SPECIFICATIONS Type

Volume flow*

Volume flow*

Pressure drop**

Cooling air requirement

Power supply

DC 0020 AB DC 0035 AB DC 0050 AB DC 0065 AB DC 0085 AB DC 0105 AB DC 0125 AB DC 0150 AB DC 0180 AB DC 0225 AB DC 0300 AB DC 0360 AB DC 0450 AB DC 0550 AB DC 0650 AB DC 0750 AB DC 0850 AB

m3/h 20 35 50 65 85 105 125 150 180 225 300 360 450 550 650 750 850

m3/min. 0,33 0,58 0,83 1,08 1,42 1,75 2,08 2,50 3,00 3,75 5,00 6,00 7,50 9,17 10,83 12,50 14,17

bar 0,04 0,04 0,10 0,13 0,14 0,28 0,39 0,15 0,12 0,18 0,36 0,49 0,11 0,15 0,32 0,25 0,33

m3/h 200 200 300 300 300 300 300 300 380 380 450 450 450 1900 1900 2500 3300

kW 0,14 0,17 0,19 0,24 0,28 0,28 0,45 0,47 0,68 0,76 0,71 0,89 0,91 1,11 1,40 1,34 1,70

* acc. to ISO 7183 ** incl. pre-and afterfilter

SIZING Operating pressure (bar)

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Correction factor fp

0,60

0,70

0,80

0,88

0,94

1,00

1,04

1,06

1,09

1,10

1,12

1,14

1,15

1,16

1,17

Compressed air inlet temperature (°C)

30

35

40

45

50

55

60

65

70

Correction factor fte

1,28

1,00

0,88

0,75

0,58

0,48

0,44

0,42

0,40

Temperature of cooling media (°C)

25

30

35

40

45

50

Pressure dewpoint °C

3

5

7

10

Correction factor ftu

1,00

0,97

0,97

0,87

0,75

0,62

Correction factor ftpd

1,00

1,12

1,24

1,36

Example:

.

Vnom = 100 m3/h (intake volume of the compressor), compressed air inlet temperature = 40°C, cooling air temperature = 35°C, operating pressure = 9 bar, pressure dewpoint = +3°C

.

Vkorr =

.

Vnom f

=

100 m3/h 0,88 x 1,06 x 0,94 x 1,00

Technical Data Sheet

= 114 m3/h

4/5

Calculated dryer size: DC 0125 AB

Refrigerant Dryers

BURAN DC 0020 AB - DC 0850 AB

DIMENSIONS

Type

A

B

C

Compressed air connections

Weight

DC 0020 AB DC 0035 AB DC 0050 AB DC 0065 AB DC 0085 AB DC 0105 AB DC 0125 AB DC 0150 AB DC 0180 AB DC 0225 AB DC 0300 AB DC 0360 AB DC 0450 AB DC 0550 AB DC 0650 AB DC 0750 AB DC 0850 AB

mm 455 455 455 455 455 455 455 600 600 600 600 600 800 800 800 800 800

mm 410 410 410 410 410 410 410 590 590 590 590 590 920 920 920 920 920

mm 645 645 645 645 645 645 645 870 870 870 870 870 1055 1055 1055 1055 1055

BSP 3/4“ 3/4“ 3/4“ 3/4“ 3/4“ 3/4“ 3/4“ 1 1/2“ 1 1/2“ 1 1/2“ 1 1/2“ 1 1/2“ 2“ 2“ 2“ 2“ 2“

kg 30 31 33 36 37 37 38 63 65 76 76 76 143 152 159 175 192

Technical Data Sheet

Subject to technical change without prior notice R01/2016/01/26