Data sheet
DST0-QHEA-GB0 SPLIT / 05.09.2016 - V 1.1
Q heat split heat meter MID-conform split heat meter with different ultrasonic and Woltman flow sensors. Available in numerous sizes from qp 0.6 m³/h to qp 60 m³/h, Fitted with an optical interface for retrofitting to external add-on modules. Thanks to integrated modules, the calculator unit can be equipped with the required communication technology ex factory. For use in the Q opto and Q basic systems or optionally through an integrated communication module in the Q M-Bus system. Can be retrofitted with external modules for use in the systems Q M-Bus, Q walk-by and Q AMR. As series G 13 / G 14 with combined heat and cold metering, and as series G 18 / G 19 with solar metering.
www.qundis.com
Application Split heat meters G 03 / G 04 are used for measuring heat energy. The G 13 / G 14 allows combined measurement of heat and cold energy, the G 18 / G 19 makes the measurement of solar energy possible. Split heat meters are used wherever compact heat meters cannot be installed. This applies particularly to unfavourable installation positions, high temperature loads or large volume flows.
Typical users are: ❱❱ Metering service companies ❱❱ Housing associations ❱❱ Property management companies ❱❱ Specialist companies for sanitary, heating and air-conditioning technology
General description The split heat meters G 03 - G 19 are made up of the calculator unit R 20 / R 21 / R 28, a pair of precise temperature sensors and a flow sensor which is installed in a hot water or cooling circuit. The electronic calculator unit calculates the difference in temperature between the supply and return flow and multiplies the value by the flow rate. The result of this (current heating or cooling capacity) is cumulated, displayed or forwarded to a data-processing system wirelessly or by cable. The calculator unit of the split heat meter can be extended using different internal and external modules. Internal modules are installed in the device during production in the factory. The calculator unit R 20 / R 21 / R 28 has two communication interfaces. The optical interface Q opto (1107) which is accessible from the outside. This allows programming and retrofitting work on the R 20 / R 21 / R 28 on-site at all times. The calculator unit can be retrofitted for wireless or other communication methods. The respective modules are mounted on the calculator unit. The internal module interface for internal impulse output or M-Bus modules. In the case of integrated modules, the information is forwarded via a permanently mounted, threaded and sealed cable connection (impulse output and M-Bus).
Storing the consumption values Using the measured difference in temperature between supply and return flow, the flow rate and the calculated thermal coefficient, the heat quantity is shown on the LC display in physical units (kWh, MWh, MJ, GJ) following an internal calculation process. To increase measuring accuracy, the density and enthalpy values are determined for every measurement and integrated into the calculation.
2 DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
05.09.2016 - V 1.1
Storing the consumption values The heat consumption values are continually cumulated. The current status is stored at 24.00 h on the due date. The due date can be set with the aid of a programming key; December 31 is the default setting. When the annual consumption is stored, the heat meter calculates a plausibility figure. This can be read out together with the due date value and checked in the billing program. This allows incorrect display readouts (e.g. “switched digits”) to be detected. The stored due date value remains in place for one year.
Calculator unit ❱❱ MID-conform calculator unit (only for measuring heat) ❱❱ Temperature sensor connection using 2- and 4-conductor technology ❱❱ Optical interface for external communication modules ❱❱ Internal communication modules for M-Bus and impulse available ex factory ❱❱ Mains-independent, for local use, 6 or 10-year lithium battery ❱❱ High resolution thanks to 7-digit LC display that indicates current value, old value, check number and many service and operating parameters ❱❱ Additional display of 18 monthly values with date ❱❱ Programming of a due date can be carried out on-site via the optical interface ❱❱ Add-on modules for M-Bus communication as well as impulse output modules can be retrofitted at any time on-site via the optical interface ❱❱ The readout processes are made easier and optimised in terms of error detection and secure data transmission ❱❱ Very high measuring accuracy ❱❱ Clear pictograms and large numbers allow meter reading to be carried out quickly and easily
3 DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
05.09.2016 - V 1.1
Flow sensors ❱ Variants from 0.6 to 250 m3/h ❱ Ultrasonic sensors for installation in any position ❱ Dynamic ratio 1:100 ❱ Safety and precise measurement ❱ Permissible operating temperature 120 °C ❱ Numerous measuring ranges available for ultrasonic measurement ❱ For flanged or threaded connection ❱ Different impulse values ❱ MID-confirm
Temperature sensor ❱ 2-conductor technology ❱ Short response time ❱ Silicone cable resistant to high temperatures available in different lengths ❱ Measuring range from 0 to 120 °C ❱ Deviations smaller than 0.05 °C ❱ MID-confirm
Split heat meter installation example Calculator unit
Temperature sensor
Ultrasonic or Woltman flow meter
Temperature sensor Example illustration
4 DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
05.09.2016 - V 1.1
Display Device states, display units and consumption values are shown via the LC display on several levels (up to 4 levels). The heat meter is equipped with a key that can be used to switch between the individual display steps and levels. The meter display is switched off and is only activated after a key has been pressed.
The display includes the following values ❱ Current heat quantity / G 13 / G 14 cold quantity
❱ Temperature difference
❱ Display test
❱ Current energy flow
❱ Old value heat quantity / G 13 / G 14 cold quantity
❱ Operating hours
❱ Check sum heat quantity / G 13 / G 14 cold quantity
❱ High-resolution heat quantity
❱ Due date
❱ Volume per input impulse
❱ Cumulated volume
❱ Software status
❱ Current flow
❱ Any module installed
❱ Supply flow temperature
❱ Save date and consumption values for the last 18 months for heat quantity / G 13 / G 14 cold quantity
❱ Return flow temperature
Operating scheme Changing between levels 0 to 4: Keep blue key pressed (approx. 3 sec.)
Changing the display on the level: Press blue key briefly
E0
E1 3
E4
. . . .
3
3
- - - - -
. . . .
. . . .
Key for changing between the display levels and moving within the levels 5 DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
05.09.2016 - V 1.1
Overview of display levels EbenenPlatzhalter übersicht
Textzeile Display level 0
Current information 3
Display level 1
Current values Display level 2
Parameter Display level 3
Monthly values heat measurement Display level 4
Monthly values cold measurement
Standardelemente 0 Standard displayEbene elements Standardelemente Ebene Standardelemente Ebene 0 0 0 0 0
0 0 0
3 3 3
Standardelemente 0 Alle Alle Segmente Segmente an an Alle Segmente an
3
0 Standardelemente -12 -12 0 Standardelemente -12 Alle Segmente an Alle Alle Segmente Segmente aus aus0 0 Alle Segmente aus -12 Standardelemente -24 0 Alle Segmente an -24 -24 Alle Segmente aus0 Impulse (animiert) 3
3 33 3
-12 0 -24 -36 -36 -12 -36 -24 -12 -36 -48 -48 -24 -48 -36 -24 -48 -60 -60 -36 -60 -48 -36 -60 -72 -72 -48 -72 -60 -48 -72 -84 -84 -60 -84 -72 -60 -84 -96 -96 -72 -96
Impulse (animiert) Alle Segmente an Impulse (animiert)
Alle Segmente aus Alle Segmente an Impulse (animiert) Warten Warten Alle Segmente aus Warten
Impulse (animiert) Alle Segmente aus Warten Temperatur Temperatur Impulse (animiert) Temperatur
Warten Impulse (animiert) Temperatur Keine Keine Energie Energie Warten Keine Energie
Temperatur Warten Keine Energie Display-Geräte Display-Geräte Ebenen Ebenen Temperatur Display-Geräte Ebenen
Keine Energie Temperatur Display-Geräte Ebenen Blinkende Elemente Blinkende Elemente Keine Energie Blinkende Elemente
3 3 3 3 3
3 3 3 33 3
3 3 3 3 33 3
3 3 3 3 33 3
3 3 3 3 33 3
3 3 3 3
Display-Geräte Ebenen Keine Energie Blinkende Elemente Display-Geräte Ebenen
-84 -72 -96 Blinkende Elemente -108 -108 -84 -108 Display-Geräte Ebenen -96 -84 -108 -120 -120 -96 -120 Blinkende Elemente ST1 ST2 ST2 ST2
-108 -96 -120 -132 -132 -108 -132 ST1 ST2 ST3 ST3 ST1 ST3
3
3
Ebene 1 Ebene Ebene 1 1 -54 -54 -54
All segments on Ebene 0 are displayed Ebene 1 All segments – display test
Ebene 3 Ebene Ebene 3 3 -108 -108 -108
Ebene 4 Ebene Ebene 4 4 -135 -135 -135
Alternierend Alternierend Alternierend -162 -162 -162
3
-27
-54
Aktuelle Aktuelle Wärmemenge Wärmemenge Aktuelle Wärmemenge
Kumuliertes Kumuliertes Volumen Volumen Kumuliertes Volumen
3 3 3
3 3 3 3
Aktuelle Wärmemenge Alle Segmente Alle Segmente an an Alle Segmente an
-27
Kumuliertes Volumen Momentaner Durchfluss Momentaner Durchfluss Momentaner Durchfluss
-54
3
Ebene 2 -81
Hochaufgelöste Hochaufgelöste Wärmemenge Wärmemenge Hochaufgelöste Wärmemenge
All segments Ebene 0 off Ebene 1 -27 -54 heat Normal silent the Ebene 0 operation of Ebene 1 meter
Ebene 2 -81 2 Ebene
Hochaufgelöste Wärmemenge Volumen Volumen pro pro Energieimpuls Energieimpuls Volumen pro Energieimpuls
-81
Impulses (animated) Ebene 2 Ebene 0 are Kumuliertes 1 by the Aktuelle Wärmemenge Volumen Hochaufgelöste Wärmemenge Flow impulses beingEbene received hydraulic sensor. 3
3
Ebene 3 -108
Speicherdatum Speicherdatum neuester neuester Monat Monat Speicherdatum neuester Monat
Ebene 3 -108 3 Ebene
Speicherdatum neuester Monat zugehöriger zugehöriger Monatswert Monatswert zugehöriger Monatswert
Ebene 4 -135
Speicherdatum Speicherdatum neuester neuester Monat Monat Speicherdatum neuester Monat
Ebene 4 -135 4 Ebene
-108
Speicherdatum neuester Monat zugehöriger zugehöriger Monatswert Monatswert zugehöriger Monatswert
Speicherdatum neuester Monat zugehöriger MonatswertMonat Speicherdatum Speicherdatum ältester ältester Monat Speicherdatum neuester Monat Speicherdatum ältester Monat
Ebene 3 -108
Alternierend -162
Batterielaufzeit Batterielaufzeit überschritten überschritten Batterielaufzeit überschritten
Alternierend -162 Alternierend
-135
Batterielaufzeit überschritten Blinkendes Blinkendes Thermometer Thermometer Blinkendes Thermometer
Speicherdatum neuester Monat
Ebene 4 -135
Batterielaufzeit überschritten
zugehöriger MonatswertMonat Speicherdatum Speicherdatum ältester ältester Monat Speicherdatum neuester Monat Speicherdatum ältester Monat
Blinkendes Thermometer Interner (RAM-Zelle Interner Speicherf. Speicherf. (RAM-Zelle de de Batterielaufzeit überschritten Interner Speicherf. (RAM-Zelle de
zugehöriger Monatswert Speicherdatum neuester Monat Speicherdatum ältester Monat zugehöriger Monatswert zugehöriger Monatswert Monatswert zugehöriger zugehöriger Monatswert
Blinkendes Thermometer Batterielaufzeit überschritten Interner Speicherf. (RAM-Zelle de Temperaturf. im Temperaturf.Thermometer im Warms. Warms. unterbro unterbro Blinkendes Temperaturf. im Warms. unterbro
Speicherdatum ältester Monat zugehöriger Monatswert zugehöriger Monatswert Speicherdatum ältester Monat
Interner Speicherf. (RAM-Zelle de Blinkendes Thermometer Temperaturf. im Warms. unterbro Temperaturf. im kurzgesc Temperaturf. im Warms. Warms. kurzgesc Interner Speicherf. (RAM-Zelle de Temperaturf. im Warms. kurzgesc
-162
3
-27
Alle Segmente an Alle Segmente aus Alle Segmente aus Aktuelle Wärmemenge Alle Segmente aus
3
-54
Momentaner Durchfluss Temperatur Temperatur Warmstrang Warmstrang Kumuliertes Volumen Temperatur Warmstrang
3 3
-81
Volumen pro Energieimpuls Softwarestand Softwarestand Wärmemenge Hochaufgelöste Softwarestand
Wait Momentaner Durchfluss Volumen pro Energieimpuls zugehöriger Monatswert Displayed during increased access to the optical interface Speicherdatum Kumuliertes Volumen Hochaufgelöste Wärmemenge neuester Monat Temperatur Warmstrang Speicherdatum ältester Monat Softwarestand Temperatur Kaltstrang Kaltstrang Prüfsumme Software Software metr. metr. Bereich Bereich zugehöriger Monatswert Monatswert Temperatur Prüfsumme zugehöriger Momentaner Durchfluss Volumen pro Energieimpuls zugehöriger Monatswert Kaltstrang Prüfsumme Software metr. Bereich zugehöriger Monatswert • Battery under tooTemperatur much load! Further communication not possible until after date changeSpeicherdatum ältester Monat Temperatur Warmstrang Alle Segmente aus Softwarestand Alle Segmente an Aktuelle Wärmemenge Alle Segmente aus Altwert Wärmemenge Altwert Wärmemenge Alle Segmente an Altwert Wärmemenge
Alle Segmente an Altwert Wärmemenge Checkzahl Wärmemenge Checkzahl Wärmemenge Alle Segmente aus Checkzahl Wärmemenge
3
3
Momentaner Durchfluss Temperatur Kaltstrang Temperatur Differenz Temperatur Warmstrang Differenz Temperatur Temperatur Differenz
Volumen pro Energieimpuls Prüfsumme vorhanden Software metr. Bereich Kein Kein Modul Modul vorhanden Softwarestand Kein Modul vorhanden
Temperature Thermometer indicates information Temperaturtemperature Kaltstrang Prüfsumme Software metr. Bereich Altwert Wärmemenge Temperatur Warmstrang Alle Segmente aus Softwarestand Checkzahl Wärmemenge Temperatur Kein Modul • High column - hot pipeDifferenz • Low column - vorhanden cold pipe Momentaner Energiefluss Funkmodul, nicht Stichtag MomentanerKaltstrang Energiefluss Funkmodul, Software nicht im im Betrieb Betrieb StichtagWärmemenge Temperatur Prüfsumme metr. Bereich Altwert Momentaner Energiefluss Funkmodul, nicht im Betrieb Stichtag • Flashing column - temperature difference Checkzahl Wärmemenge Altwert Wärmemenge Stichtag Aktuelle Kältemenge Aktuelle Kältemenge Checkzahl Wärmemenge Aktuelle Kältemenge
Temperatur Differenz Temperatur Kaltstrang Momentaner Energiefluss Betriebsstunden Betriebsstunden Temperatur Differenz Betriebsstunden
Kein Modul vorhanden Prüfsumme Software metr. Bereich Funkmodul, im nicht im Betrieb Funkmodul, Funkmodul, im Betrieb Betrieb Kein Modul vorhanden Funkmodul, im Betrieb
No energy No energy is being recorded Momentaner Energiefluss Funkmodul, nicht im Betrieb Stichtag (No flow and/or now temperature difference) Checkzahl Wärmemenge Temperatur Differenz Kein Modul vorhanden Aktuelle Kältemenge Altwert Altwert Kältemenge Kältemenge Stichtag Altwert Kältemenge
Betriebsstunden Momentaner Energiefluss
Funkmodul, im Betrieb Funkmodul, nicht im Betrieb
Display or device level indicator Betriebsstunden Aktuelle Kältemenge • Level 0 = no barsMomentaner • Level 1 =Funkmodul, 1 barim Betrieb Energiefluss Funkmodul, nicht im Betrieb Stichtag Altwert Kältemenge M-Bus-Modul Checkzahl Kältemenge M-Bus-Moduliminstalliert Checkzahl Kältemenge Betriebsstunden • Level 3 =Funkmodul, Aktuelle Kältemenge Betrieb • Level 2 = 2 bars 3 barsinstalliert M-Bus-Modul installiert Checkzahl Kältemenge • Level 4 = top and bottom bars shown, centre empty Altwert Kältemenge Aktuelle Kältemenge Checkzahl Kältemenge Schleife OBEN Schleife OBEN Altwert Kältemenge Schleife OBEN
zugehöriger Monatswert zugehöriger Monatswert Speicherdatum ältester Monat
3 3 3
zugehöriger Monatswert Speicherdatum ältester Monat
zugehöriger Monatswert Speicherdatum ältester Monat
zugehöriger Monatswert
zugehöriger Monatswert 3 3 3
Betriebsstunden M1 M1
Funkmodul, Betrieb M-Bus-Moduliminstalliert
M2
Schleife OBEN Checkzahl Kältemenge Schleife UNTEN Schleife MITTE Schleife OBEN MITTE Schleife Schleife MITTE
M1
Schleife OBEN Schleife MITTE Schleife UNTEN
M1 M3 M4 M4 M2 M4
M2 M3 M3 M1 M3
M-Bus-Modul installiert
E0 - E4 E0 - E4
M-Bus-Modul installiert
E0 - E4
Temperaturf. im Warms. unterbro Interner Speicherf. (RAM-Zelle de Temperaturf. im Warms. kurzgesc Temperaturf. im Kalts. Temperaturf. im im Warms. Kalts. unterbroch unterbroch Temperaturf. unterbro Temperaturf. im Kalts. unterbroch
3
zugehöriger Monatswert
zugehöriger Monatswert 3 3
Temperaturf. im Warms. kurzgesc Temperaturf. im Warms. unterbro Temperaturf. im Kalts. unterbroch Temperaturf. Temperaturf. im im Kalts. Kalts. kurzgesch kurzgesch Temperaturf. im Warms. kurzgesc Temperaturf. im Kalts. kurzgesch
3
M1 M1 M1
3 3
Temperaturf. im Kalts. unterbroch Temperaturf. im Warms. kurzgesc Temperaturf. im Kalts. kurzgesch Interner Interner Prüfsummenfehler Prüfsummenfehler Temperaturf. im Kalts. unterbroch Interner Prüfsummenfehler 3 3
3
M1 M2 M2 M2
M1 M1 M1
3
3
Temperaturf. im Kalts. kurzgesch Temperaturf. im Kalts. unterbroch Interner Prüfsummenfehler Display-Geräte-Ebene 0 Display-Geräte-Ebene 0 Temperaturf. im Kalts. kurzgesch Display-Geräte-Ebene 0 3 3 3 3
M1
M1 Flashing elements Flashing of the fine lines: ProgrammingM-Bus-Modul mode installiert Checkzahl Kältemenge Altwert Kältemenge Press blue key: Program / edit Schleife OBEN M1 Schleife UNTEN M2 Schleife UNTEN M2 Checkzahl Kältemenge Schleife UNTEN
Alternierend -162
3
3
-120 DST0-QHEA-GB0 SPLIT Q heat split – Data sheet -108 -132 -144 Schleife UNTEN M2 -144 -120 -144 ST2 ST1 ST3 ST4 ST4 ST2 ST4
3 3
Ebene 2 Ebene Ebene 2 2 -81 -81 -81
.. .. .. .. . . . . . . . . .. . . . . .
ST1 ST1 Blinkende Elemente ST1
3 3
-27 -27 -27
M2 M3 M3 M1 M3
M1 M2 M2 M2
Interner Prüfsummenfehler Temperaturf. im Kalts. kurzgesch Display-Geräte-Ebene 0 3 Display-Geräte-Ebene 1 Display-Geräte-Ebene 1 Interner Prüfsummenfehler Display-Geräte-Ebene 1 3 3 33 3
M2 M1 M3 M4 M4 M2 M4
M1 M2 M3 M3 M1 M3
Display-Geräte-Ebene 0 Interner Prüfsummenfehler Display-Geräte-Ebene 1 Display-Geräte-Ebene Display-Geräte-Ebene 2 2 Display-Geräte-Ebene 0 Display-Geräte-Ebene 2
M3 M2 M4 M5 M5 M3 M5
M2 M1 M3 M4 M4 M2 M4
Display-Geräte-Ebene 1 Display-Geräte-Ebene 0 Display-Geräte-Ebene 2 Display-Geräte-Ebene 3 Display-Geräte-Ebene 1 3 Display-Geräte-Ebene Display-Geräte-Ebene 3
M4 M3 M5 M6 M6 M4 M6
M3 M2 M4 M5 M5 M3 M5
6
05.09.2016 - V 1.1 Display-Geräte-Ebene 2 Display-Geräte-Ebene 1 Display-Geräte-Ebene 3 Display-Geräte-Ebene Display-Geräte-Ebene 4 4 Display-Geräte-Ebene 2 Display-Geräte-Ebene 4
3 3 3 3 33 3
3 3 3 3 33 3
3 3 3
Ebene 0 -27
Ebene 3 -108
Ebene 4 -135
Alternierend -162
3
Aktuelle Wärmemenge
Kumuliertes Volumen
Hochaufgelöste Wärmemenge
Speicherdatum neuester Monat
Speicherdatum neuester Monat
Batterielaufzeit überschritten
Volumen pro Energieimpuls
zugehöriger Monatswert
zugehöriger Monatswert
Blinkendes Thermometer
3
3
Momentaner Durchfluss
Alle Segmente an
Display function control Standardelemente Ebene 0 Temperatur Warmstrang
Alle Segmente aus
0 Standardelemente 0 3
0
Altwert Wärmemenge
0
3
Ebene 1 Speicherdatum ältester Monat -27 -54 1 Ebene 0 Ebene Display -27test (all segments -54on)
Softwarestand
Ebene 3 -108 3 Ebene
Ebene 4 -135 4 Ebene
Alternierend -162 Alternierend
-108
-135
-162
Interner Speicherf. (RAM-Zelle defekt)
-81
Check whether all the segments in the zugehöriger adjacent display light up. zugehöriger Monatswert Monatswert Temperaturf. im Warms. unterbrochen 3
Temperatur Kaltstrang Alle Segmente an
Prüfsumme Software metr. Bereich Aktuelle Wärmemenge
Alle Segmente an
Aktuelle Wärmemenge
Temperatur Differenz Alle Segmente aus
Display test (all segments off) Kein Modul vorhanden Momentaner Durchfluss Volumen pro Energieimpuls Alle Segmente an Check whether all the segments are off.
-12 -12
Ebene 2 -81 2 Ebene
Speicherdatum ältester Monat
3
Kumuliertes Volumen
Hochaufgelöste Wärmemenge
Speicherdatum neuester Monat
Speicherdatum neuester Monat
Batterielaufzeit überschritten
Hochaufgelöste Wärmemenge
Speicherdatum neuester Monat
Speicherdatum neuester Monat
Batterielaufzeit überschritten
Temperaturf. im Warms. kurzgeschl. zugehöriger Monatswert
3
3
Checkzahl Wärmemenge
Stichtag
Ebene 2 -81
Ebene 1 -54
Kumuliertes Volumen 3
3
zugehöriger Monatswert
Blinkendes Thermometer
Alle Segmente an
Momentaner Durchfluss
Volumen pro Energieimpuls
zugehöriger Monatswert
zugehöriger Monatswert
Blinkendes Thermometer
Ebene 2 Funkmodul, nicht im Betrieb -81 Alle Segmente aus
Ebene 3 -108 Temperatur Warmstrang
Ebene 4 Softwarestand -135
Alternierend Temperaturf. im Kalts. unterbrochen Speicherdatum-162 ältester Monat
Speicherdatum ältester Monat
3
3
Alle Segmente aus
Ebene 0 -24 -27 -24 Ebene 0 -36 -27
Aktuelle Kältemenge Aktuelle Wärmemenge
Ebene 0 -27
Aktuelle Wärmemenge Altwert Kältemenge Alle Segmente an
-36
Ebene 1 Momentaner Energiefluss -54 Impulse (animiert) Ebene 1 -54 Betriebsstunden
Kumuliertes Volumen Warten Warten
3
-48
3 3
Ebene 1 -54
Kumuliertes Volumen Momentaner Durchfluss Temperatur
3 3 3 3
Aktuelle Wärmemenge 3
-60
-81
-60
-108
-135
-162
Temperatur Kaltstrang
Prüfsumme Software metr. Bereich
zugehöriger Monatswert
3 3
Hochaufgelöste Wärmemenge
Speicherdatum neuester Monat
3
Volumen pro Energieimpuls Checkzahl Wärmemenge
Speicherdatum neuester Monat M1 zugehöriger Monatswert Temperatur Differenz
Batterielaufzeit überschritten Interner Prüfsummenfehler Blinkendes Thermometer
Temperatur Kumuliertes Volumen Momentaner Durchfluss
3
Altwert Wärmemenge
3
Alle Segmente an Checkzahl Kältemenge Alle Segmente aus
Operating hours TemperaturEbene Warmstrang 3 ältester Monat Softwarestand 2 hour Ebene 4 with Speicherdatum If theEbene operating display approximately correlates the Alternierend service life of theSpeicherdatum deviceältester Monat -81 -108 -135 -162 Funkmodul, im Betriebof manufacture), the device voltage supply is OK.Temperaturf. im Kalts. kurzgeschl. (see year Hochaufgelöste Wärmemenge Speicherdatum neuester Monat Speicherdatum neuester Monat Batterielaufzeit überschritten Temperatur Kaltstrang Prüfsumme Software metr. Bereich zugehöriger Monatswert zugehöriger Monatswert Altwert Wärmemenge Ebene Ebene Ebenethe 4 battery isAlternierend NOTE: The 2hours counter runs 3from the moment installed in the factory.
Alle Segmente aus
Impulse (animiert)
3
-48
3
3 3
Temperatur Warmstrang Keine Energie
zugehöriger Monatswert Kein Modul vorhanden
zugehöriger Monatswert
Temperature in the hotDifferenz pipe Checkzahl Wärmemenge Temperatur Kein Modul vorhanden Hochaufgelöste Wärmemenge Speicherdatum neuester Monat Speicherdatum neuester Monat Batterielaufzeit überschritten Use a thermometer to determine the actual in the heating system Volumen pro Energieimpuls zugehöriger Monatswert zugehörigercurrent Monatswert temperature Blinkendes Thermometer M-Bus-Modul installiert Display-Geräte-Ebene 0 M2 M1 Speicherdatum ältester Monat Speicherdatum ältester Monat Interner Speicherf. (RAM-Zelle defekt) Softwarestand and compare the result with the display. Momentaner Energiefluss Funkmodul, nicht im Betrieb Stichtag
Alle Segmente aus Schleife OBEN Altwert Wärmemenge
Temperatur Warmstrang M1 Temperatur Kaltstrang Display-Geräte Ebenen
Ebene 0 -72 -27 -72
Ebene 1 -54
3
33
Alle Segmente aus
-84
Altwert Wärmemenge Schleife UNTEN Checkzahl Wärmemenge Aktuelle Wärmemenge
-84
Display-Geräte Ebenen Temperatur Warmstrang Temperatur Kaltstrang M2 Temperatur Differenz Kumuliertes Volumen Blinkende Elemente
-96
Checkzahl Wärmemenge Schleife MITTE Stichtag Alle Segmente an
Ebene 0 -96 -27
Checkzahl Wärmemenge
Altwert Wärmemenge Kältemenge Altwert
Funkmodul, nicht im Betrieb Volumen pro Energieimpuls Checkzahl Kältemenge
-120
Temperatur Kaltstrang ST2
Alle Segmente an
Momentaner Durchfluss
Aktuelle Kältemenge
ST2 Betriebsstunden
Altwert Kältemenge
Checkzahl Checkzahl Kältemenge Wärmemenge
-132
Hochaufgelöste Wärmemenge 3
M-Bus-Modul installiert Kein Modul vorhanden Schleife MITTE
Temperaturf. imüberschritten Warms. kurzgeschl. Batterielaufzeit M1
Interner Prüfsummenfehler
M1 Temperaturf. im Warms. unterbrochen
Interner Prüfsummenfehler
3
zugehöriger Monatswert
zugehöriger Monatswert
3
3
3
3
M6 Speicherdatum ältester Monat M1
M5 Speicherdatum ältester Monat3
Speicherdatum neuester Monat
Speicherdatum neuester Monat
Temperaturf. im Kalts. unterbrochen Display-Geräte-Ebene 4 Temperaturf. im Kalts. kurzgeschl. Interner Speicherf. (RAM-Zelle defekt) M3
M1
3
Display-Geräte-Ebene 0 3
M2
Display-Geräte-Ebene 1
M2
Display-Geräte-Ebene 1
M3
Display-Geräte-Ebene 2
M3
Display-Geräte-Ebene 2
M4
Display-Geräte-Ebene 3
M4
Display-Geräte-Ebene 3
M5
Display-Geräte-Ebene 4
M5
Display-Geräte-Ebene 4
3
3
3
M2 M3
M1
Temperaturf. im Kalts. kurzgeschl.
E0 - E4 E0 - E4
3
Interner Prüfsummenfehler
3
Display-Geräte-Ebene 3 Temperaturf. im Warms.0 kurzgeschl. M5 3
3
3
3
3
M1 Momentaner Energiefluss ST4
3
.... .... ....
Altwert Wärmemenge
Temperatur Kaltstrang
Prüfsumme Software metr. Bereich
zugehöriger Monatswert
zugehöriger Monatswert
Checkzahl Kältemenge
ST4
M-Bus-Modul installiert
M4 M2
M1
M6 Display-Geräte-Ebene 0
Schleife OBEN
M1
M3
M2
Display-Geräte-Ebene 1
Schleife Aktuelle UNTEN Kältemenge
M2 Betriebsstunden
Funkmodul, im Betrieb
M4
M3
Display-Geräte-Ebene 2 3 Temperaturf. im Kalts. kurzgeschl.
Checkzahl Wärmemenge
Temperatur Differenz
Kein Modul vorhanden
Schleife OBEN
M1
M3
M2
Schleife UNTEN
M2
M4
M3
Display-Geräte-Ebene 2
3
Schleife MITTE Altwert Kältemenge
M3
M5 M1
M4
Display-Geräte-Ebene 3 Interner Prüfsummenfehler
3
M4
M3
M5
M4
Display-Geräte-Ebene 3
3
M6 M2
M5 M1
Display-Geräte-Ebene Display-Geräte-Ebene 4 0
3
E0 - E4 E0 - E4
3
3 Temperaturf. im Warms. unterbrochen
3
3 Temperaturf. im Warms. kurzgeschl. 3
Funkmodul, nicht im Betrieb
Display-Geräte-Ebene 1
Stichtag
Momentaner Energiefluss
Schleife UNTEN
M2
Schleife MITTE
M3
Checkzahl Kältemenge
M4
M-Bus-Modul installiert
Aktuelle Kältemenge
Betriebsstunden
Funkmodul, im Betrieb
Schleife MITTE
M3
M5
M4
Display-Geräte-Ebene 3
M4
M6
M5
Display-Geräte-Ebene 4
M1
M3
M2
Display-Geräte-Ebene 1 Interner Prüfsummenfehler
3
M6
M5
Display-Geräte-Ebene 4
3
M4
M3
Display-Geräte-Ebene 2
M2
M1
Display-Geräte-Ebene 0
E0 - E4
....
Altwert Kältemenge M4
M2 M-Bus-Modul installiert
Checkzahl Kältemenge
3 Temperaturf. im Kalts. unterbrochen 3 3
Display-Geräte-Ebene 2
Temperaturf. im Kalts. kurzgeschl. 3
M1
E0 - E4 M3
M5
M4
Display-Geräte-Ebene 3
Schleife OBEN
M1
M3
M2
Display-Geräte-Ebene 1
M4 M2
Q heat split – Data sheet
....
DST0-QHEA-GB0 SPLIT
3
3 3
Schleife MITTE
Schleife UNTEN
3
Display-Geräte-Ebene 0
Batterielaufzeit überschritten M3
Speicherdatum ältester Monat Speicherdatum ältester Monat Interner Speicherf. (RAM-Zelle defekt) Current energy flow calculation M3 M5 M1 Interner Prüfsummenfehler Current flow [m3/h]M2x Temperature difference [K] x 1.2 M-Bus-Modul installiert Display-Geräte-Ebene 0 M1 Display-Geräte-Ebene 1 M3 M2 Funkmodul, nicht im Betrieb Temperaturf. im Kalts. unterbrochen M4 should correlate approximately with the M6 The value calculated display.
Softwarestand
Schleife UNTEN
Temperaturf. im Kalts. kurzgesch
3
Schleife MITTE
Schleife OBEN
Temperaturf. im Kalts. kurzgesch
3
Funkmodul, im Betrieb
Temperatur Warmstrang
-144
3
3
Temperaturf. im Kalts. unterbrochen Current flow Temperaturf. im Kalts. kurzgeschl. Funkmodul, im Betrieb In order to evaluate the current functional ability of the heat meter, M1 Interner Prüfsummenfehler Prüfsumme Software metr. Bereich zugehöriger Monatswert zugehöriger Monatswert Temperaturf. im Warms. unterbrochen Schleife UNTEN M2 M4 Volumen pro Energieimpuls zugehöriger Monatswert zugehöriger Monatswert Blinkendes Thermometer open the display showing the current device flow. Schleife UNTEN M2 M4 Schleife OBEN Funkmodul, nicht im Betrieb
ST3
-144
Speicherdatum neuester Monat
Funkmodul, nicht im Betrieb Funkmodul, im Betrieb Softwarestand Schleife OBEN
Altwert Kältemenge
Checkzahl Kältemenge
Speicherdatum neuester Monat
M1
Temperatur Differenz -132 ST3
Temperaturf. im Kalts. unterbroch
Alternierend -162
Interner Speicherf. (RAM-Zelle defekt) Display-Geräte-Ebene 1 Temperaturf. im Warms. unterbrochen
Temperaturf. im Warms. kurzgeschl. Temperature Display-Geräte-Ebene 3 M5 M4 Temperaturf. im Kalts. unterbrochen Ebene 2 difference 4 Alternierend zugehörigerEbene Monatswert 3 zugehörigerEbene Monatswert Blinkendes Thermometer M-Bus-Modul installiert M2 M1 Calculate the difference in temperature between the temperature measured in the hot and cold -81 -108 -135 -162 M-Bus-Modul installiert M1 Checkzahl Temperaturf. im Warms. kurzgeschl. Kein ModulKältemenge vorhanden pipes and compare the result once again with the display. M2
Alle Segmente aus
Schleife Stichtag OBEN
Ebene 4 -135
Speicherdatum ältester Monat M2 zugehöriger Monatswert Funkmodul, im Betrieb
3
3
Kumuliertes Volumen
-120 Betriebsstunden
Temperaturf. im Kalts. unterbroch
Blinkendes Thermometer
Kein Modul vorhanden
Ebene 1 -54
ST1 Momentaner Energiefluss
Funkmodul, im Betrieb zugehöriger nicht Monatswert
. . . .. . . .
Aktuelle Kältemenge
E0 - E4
Temperatur Differenz M3 Momentaner Durchfluss Energiefluss Momentaner
M4
3
Temperaturf. im Warms. kurzgesc 3
UseKältemenge a thermometerBetriebsstunden to determine current temperature in the heating Aktuelle Funkmodul, im Betrieb Speicherdatum ältester Monatthe actual Speicherdatum ältester Monat Interner Speicherf. (RAM-Zelle defekt) system Softwarestand Prüfsumme Software metr. Bereich zugehöriger Monatswert zugehöriger Monatswert Temperaturf. im Warms. unterbrochen and compare the result with the display. Display-Geräte-Ebene 2 M4 M3 Kein Modul vorhanden Hochaufgelöste Wärmemenge Altwert Kältemenge
Betriebsstunden Temperatur Warmstrang -108 ST1
Aktuelle Wärmemenge
Stichtag
Speicherdatum ältester Monat Ebene 2 Ebene 3 M3 Prüfsumme Software metr. Bereich zugehöriger Monatswert -81 Betriebsstunden Aktuelle Kältemenge Temperature in the cold-108 pipe
Altwert Kältemenge Prüfsumme Software metr. Bereich
-108 Momentaner Energiefluss
Stichtag
Aktuelle Kältemenge Alle Segmente aus
Momentaner Energiefluss zugehöriger Monatswert
Softwarestand
Blinkende TemperaturElemente Kaltstrang
Temperatur Differenz
Temperaturf. im Warms. kurzgesc
3
3
3
Altwert Wärmemenge
3
Temperaturf. im Warms. unterbro
3
3
Stichtag Volumen pro Energieimpuls
....
Keine EnergieDurchfluss Momentaner
Interner Speicherf. (RAM-Zelle de
Temperaturf. im Warms. unterbro
3
3
Alle Segmente an
Interner Speicherf. (RAM-Zelle de
7 3 3
M6
M5
Display-Geräte-Ebene 4
M4
M3
Display-Geräte-Ebene 2
05.09.2016 - V 1.1
Ultrasonic series 473 (threaded connection)
Illustration similar
Technical data Series Nominal width Nominal flow Approval Design length Design length with screw fitting Maximum flow Minimum flow (DR 1:250) Minimum flow (DR 1:100) Minimum flow for upside down installation Pressure loss at qp Start-up value Connection thread Meter Connection thread Screw fitting Height Length of electronics Width of electronics Weight Length of impulse cable
473 DN qp
mm m3/h
15 0.6
20 0.6
20 0.6
15 1.5
20 1.5
L L2 qs qi qi
mm mm m3/h l/h l/h
110 190 1.2 6 6
130 230 1.2 6 6
190 1.2 6 6
110 190 3 6 15
130 230 3 6 15
qi
l/h
6
6
6
6
6
6
10
10
Δp
mbar l/h Inches Inches mm mm mm mm kg cm
85 1
85 1
85 1
75 2.5
75 2.5
75 2.5
100 4
100 4
G1B G¾B G1B
G1B
G1B
H H1 L1 B
G¾B G1B
20 20 20 25 1.5 2.5 2.5 3.5 Approval according to MID 190 130 190 135 230 255 3 5 5 7 6 10 10 15 25 25 35
25 3.5
32 3.5
25 3.5
32 3.5
150 270 7 35
150 270 7 35
260 380 7 35
260 380 7 35
35
35
35
35
35
44 7
44 7
44 7
44 7
44 7
G1B
G1¼B
G1¼B
G1½B
G1¼B
G1½B
R1
R1
R1¼
R1
R1¼
23 61 90 65.5 0.88
23 61 90 65.5 0.93
23 61 90 65.5 1.08
23 61 90 65.5 1.35
23 61 90 65.5 1.35
R½
R¾
R¾
R½
R¾
R¾
R¾
R¾
14.5 54.5 90 65.5 0.6
18 56.5 90 65.5 0.61
18 56.5 90 65.5 0.63
14.5 54.5 90 65.5 0.60
18 56.5 90 65.5 0.61
18 56.5 90 65.5 0.63
18 56.5 90 65.5 0.61
18 56.5 90 65.5 0.63 250
Minor changes can occur as a result of technical development.
See the next page for further nominal sizes of the 473 series with threaded connection:
8 DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
05.09.2016 - V 1.1
Ultrasonic series 473 (threaded connection)
Pressure loss (mbar)
Pressure loss curve
Flow (l/h)
Series Nominal width Nominal flow Approval Design length Design length with screw fitting Maximum flow Minimum flow (DR 1:250) Minimum flow (DR 1:100) Minimum flow for upside down installation Pressure loss at qp Start-up value Connection thread Meter Connection thread Screw fitting Height Length of electronics Width of electronics Weight Length of impulse cable (2)
473 DN qp
mm m3/h
25 6
25 6
32 6
25 6
L L2 qs qi qi
mm mm m3/h l/h l/h
135 225 12 24 60
150 270 12 24 60
150 270 12 24 60
260 380 12 24 60
qi
l/h
24
24
24
24
24
100
Δp
mbar l/h Inches Inches mm mm mm mm kg cm
128 7
128 7
128 7
128 7
128 7
95 20
G1¼B
G1¼B
G1½B
G1¼B
G1½B
R1
R1
R1¼
R1
23 61 90 65.5 0.88
23 61 90 65.5 0.93
23 61 90 65.5 1.08
23 61 90 65.5 1.35
H H1 L1 B
32 40 40 6 10 10 Approval according to MID 260 200 300 380 340 440 12 20 20 24 40(2) 40(2) 60 100 100
50 15
65 25
80 40
100 60
270 30 60(2) 150
300 50 100(2) 250
300 80 160(2) 400
360 120 240(2) 600
100
150
250
160
1200
95 20
80 40
75 50
80 80
75 120
G2B
G2B
-
-
-
-
R1¼
R1½
R1½
-
-
-
-
23 61 90 65.5 1.35
33 66.5 90 65.5 2.4 250
33 66.5 90 65.5 2.6
-
-
-
-
Only in horizontal installation position
See the previous page for further nominal sizes of the 473 series with threaded connection:
9 DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
05.09.2016 - V 1.1
Ultrasonic series 473 (flanged connection)
Illustration similar
Technical data Series Nominal width Nominal flow Approval Design length Height Flange dimensions Flange diameter Diameter of hole circle Diameter
DN qp
mm m3/h
20 0.6
20 1.5
20 2.5
25 3.5
L H H1 F D K D1
mm mm mm mm mm mm mm quantity mm mm kg kg cm
190 47.5 56.5 95 105 75 14
190 47.5 56.5 95 105 75 14
190 47.5 56.5 95 105 75 14
260 50 61 100 114 85 14
4
4
4
4
4
4
4
4
90 65.5 2.7 -
90 65.5 2.7 -
90 65.5 2.7 -
90 65.5 3.35 -
90 65.5 4.65 -
90 65.5 3.35 -
90 65.5 4.65 250
90 65.5 6.6 -
Number of flange bore holes Length of electronics Width of electronics Weight of brass housing(2) Weight of cast iron housing(2) Length of impulse cable
L1 B
32 3.5
25 32 40 50 6 6 10 15 Approval according to MID 260 260 260 300 270 62.5 50 62.5 69 73.5 61 61 61 66.5 71.5 125 100 125 138 147 139 114 139 148 163 100 85 100 110 125 18 14 18 18 18
65 25
80 40
100 60
300 85 79 170 184 145 18
300 92.5 86.5 185 200 160 19
360 108 96.5 216 235 180(1)/190 19(1)/22
4
8
8
8
90 65.5 7.45 6.31
90 65.5 9.45 8.08
90 65.5 11.1 10.01
90 65.5 16.9 15.76
Minor changes can occur as a result of technical development. (1) Values for PN 16 housing (2) Meter with battery and impulse cable 2.4 m long
Pressure loss (mbar)
Pressure loss curve
Flow (l/h)
DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
10 05.09.2016 - V 1.1
Woltman WS - series 453
Illustration similar
Technical data Series
453
Design Nominal width Nominal flow Approval Impulse value Flow at 0.1 bar pressure loss Maximum flow (briefly) Lower measuring range limit Start-up values
WS-XKA DN Qn
Qmax Qmin
Flange connection dimensions acc. to DIN 2501/PN 16
Outer dia. Hole circle dia. Number of screws
Height
without increase due to calculator unit with increase due to calculator unit
Length acc. to DIN 19626 Length acc. to DIN ISO 4064 Weight Installation position: - horizontal
D K quantity H H h L L
mm m3/h
50 15
l/imp. m3/h m3/h m3/h l/h mm mm
100 19 50 0.2 60 165 125 4 155 195 84 270 300 14.2
mm mm mm mm mm kg
65 80 25 40 Approval according to MID 100 100 21 42 50 110 0.2 0.3 60 90 185 200 145 160 4 8 155 190 195 230 97 102 300 300 300 350 18 24
100 60 100 70 140 0.4 90 220 180 8 200 240 113 360 350 28
Minor changes can occur as a result of technical development.
Pressure loss (bar)
Pressure loss curve
Flow (m3/h)
DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
11 05.09.2016 - V 1.1
Woltman WP - series 457
Illustration similar
Technical data Series
457
Design Nominal width Nominal flow Approval Impulse value Maximum flow (briefly+factory specifications) Lower measuring range limit Start-up values Outer dia. Flange connection dimensions Hole circle dia. acc. to DIN 2501/PN 16 Number of screws Height Length acc. to DIN 19626 Weight Installation positions: - horizontal - vertical
DN Qn
Qmax Qmin
mm m3/h
50 15
l/imp. m3/h m3/h l/h mm mm
100 30 0.55 130 165 125 4 141 75 200 11.1
D K quantity H mm h mm L mm kg
WP-XKA PH-XKA 65 80 150 25 32 150 Approval according to MID 100 100 100 30 45 300 0.55 2.5 4.5 130 400 1700 185 200 285 145 160 240 4 8 8 141 141 244 82.5 94 135 200 200/225 300 11.6 12.5 39
200 250 100 500 8 200 340 295 8/12 244 163 350 47
Minor changes can occur as a result of technical development.
Pressure loss (bar)
Pressure loss curve
Flow (m3/h)
DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
12 05.09.2016 - V 1.1
Woltman WP - series 456
Illustration similar
Technical data Series
456
Design Nominal width Nominal flow Approval Impulse value Maximum flow (briefly+factory specifications) Flow at 1 bar pressure loss Lower measuring range limit Start-up values Outer dia. Flange connection dimensions Hole circle dia. acc. to DIN 2501/PN 16 Number of screws Height Length acc. to DIN 19626 Weight Installation positions: - horizontal - vertical
WP-XKA PH-XKA DN Qn
mm m3/h
100 60
l/imp. m3/h m3/h m3/h l/h mm mm
100 180 95 2 500 220 180 8 200 110 250 19.8
125 100 Approval according to MID
Qmax Qmin
D K quantity H mm h mm L mm kg
100 250 200 3 800 250 210 8 200 125 250 22.4
Minor changes can occur as a result of technical development.
Pressure loss (bar)
Pressure loss curve
Flow (m3/h)
DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
13 05.09.2016 - V 1.1
Technical data of calculator unit R 20 (heat) 5 - 120 °C 3 - 150 K
Device type
Permissible temperature range Permissible temperature difference
Lithium battery > 6 (opt. 10) years IP 65 5 - 55 °C C (industrial)
Power supply
Battery service life Protection rating Operating temperature Environment class acc. to EN 1434-4
< 1 l/imp. =/> 1 l/imp.
Display
Optional energy display
2.5 m3/h 2.5 m3/h
Registering range
7-digit LCD 4/5 MWh MWh kWh, MJ, GJ GJ -30 °C - +190 °C
Lithium battery > 6 (opt. 10) years IP 65 5 - 55 °C C (industrial)
7-digit LCD 4/5 MWh MWh kWh, MJ, GJ GJ -30 °C - +190 °C
7-digit LCD 4/5 MWh MWh kWh, MJ, GJ GJ -30 °C - +190 °C
Impact-resistant polymer Installation on DIN rail (top hat rail EN 50022 / 35 x 7.5 mm)
Housing
Installation
Max. measuring error
Lithium battery > 6 (opt. 10) years IP 65 5 - 55 °C C (industrial)
Suitable for open collector and Reed contact 10 m 10 m 10 m 0.1 ml - 999,999.9 ml per impulse 166 Hz 166 Hz 166 Hz 20 Hz 20 Hz 20 Hz
Connection flow impulse generator
Display levels Standard energy display
R 28 (solar 2) 5 - 120 °C 3 - 150 K
Type/connection type Type/connection type Type/connection type PT 1000 PT 1000 PT 1000 2-conductor technology 2-conductor technology 2-conductor technology PT 100 / PT 500 PT 100 / PT 500 PT 100 / PT 500 4-conductor technology 4-conductor technology 4-conductor technology 1 K (3) 1 K (3) 1 K (3) -.0.2 K (3) -.10 m 10 m 10 m
Type of temperature sensor
Standard temperature sensor Connection type Optional temperature sensor Connection type Temperature difference heat metering Temperature difference cold metering Max. cable length, unshielded
Max. cable length Impulse value Max. impulse frequency Max. impulse frequency
R 21 (heat + cold 1) 5 - 120 °C 3 - 150 K
± 1.5 % ±1%
at 3 K < ∆t > 20 K at 20 K < ∆t > 150 K
1) approved only for heat, no approval for cold 2) no approval 3) can be selected using article number
14 DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
05.09.2016 - V 1.1
Dimensional drawings Calculator unit
Flow sensors The dimensions and sizes of the flow sensors in this data sheet are the specifications of the different manufacturers.
15 DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
05.09.2016 - V 1.1
Temperature sensor Measuring resistance (standard)
PT1000 EN 60751
Temperature range
0 - 180 °C
Connection wire cable sensor
3 m (standard) 10 m (option)
Dimensions
L1
L2
D
short short
45 mm 45 mm
3000 mm 10000 mm
5.2 mm 5.2 mm
medium medium
105 mm 105 mm
3000 mm 10000 mm
6.0 mm 6.0 mm
long long
140 mm 140 mm
3000 mm 10000 mm
6.0 mm 6.0 mm
Immersion sleeves
Versions
Material Temperature range
Dimensions
short medium long
short
medium
long
Brass Stainless steel Stainless steel 0 - 130 °C 0 - 180 °C 0 - 180 °C
L1
27 mm 40 mm 40 mm
L2
L3
35 mm 47 mm 85 mm 99 mm 120 mm 134 mm
L4
D1
D2
8.0 mm 15 mm 15 mm
6.6 mm 7.5 mm 7.5 mm
6.6 mm 12 mm 12 mm
Note: Head-type sensors are available on request. All sensors are paired and calibrated. In agreement with the MID, immersion sleeves are only approved from qp 6.0 m³/h. DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
D3
G
SW
30 mm 30 mm
¼" ½" ½"
17 mm 22 mm 22 mm
16 05.09.2016 - V 1.1
QUNDIS GmbH Sonnentor 2 D-99098 Erfurt +49 (0) 361 26 280-0 +49 (0) 361 26 280-175
[email protected] www.qundis.com The information in this data sheet only contains general descriptions or product characteristics, which may not always apply in particular application cases and/or may be subject to change through further development of the product. Required product characteristics are then binding if they are expressly agreed when the contract is drawn up. ©2016 QUNDIS GmbH. Subject to change 17
DST0-QHEA-GB0 SPLIT
Q heat split – Data sheet
05.09.2016 - V 1.1