Chilled Water Distribution Systems

APPA Institute for Facilities Management February 6, 2014

1

Purpose of Today’s Presentation  To provide a broad understanding of chilled water distribution systems  Explore in some detail various distribution system configurations  Provide some useful observations and solutions

2

Agenda  System Concepts – Definitions – Basic Formulae  ∆T

– Hydraulic Profile

 System Components  System Configurations

3

APPA Institute - Dallas, TX Feb 2014

1

WORDS OF WISDOM It’s not how much you’ve got; it’s whether you can use it.

Production

Distribution

Load

4

Definitions 

 

System (Static/Fill) Pressure: The non-flowing pressure to which the system must be filled to assure flooding of the highest device. – Static pressure is created by the weight of water in the system. Static pressure has no effect on pump capacity. If you consider a water piping system as being an upright loop of water confined in a pipe, the static pressure in one of the vertical pipes is caused by the weight of the water column in the pipe. – Static Pressure is equal to .434 pounds per sq. inch per foot of water above the measurement gauge. For example, if the highest device is 20 feet above the gauge, the static pressure at the gauge will be: 20 x .434 which equals 8.6 psig. At various elevations above the gauge, the static pressure becomes correspondingly less. At 10 feet, it is 4.3 pounds per sq. in., and at the top, located 20 feet above the gauge, there is no pressure. System pressure is usually set so that there is at least 5 psig measured at the highest device in the system. QUESTION: What pressure must there be in the system if the highest device is located 120 feet above the chilled water makeup water inlet?

5

Fill Pressure, Makeup, and Expansion

∆H= ∆H120’ ∆H= 120’ Makeup/Fill Water

Makeup/Fill Water

System Pressure = .434 psi/ft X 120’ + 5 = 57 psig 6

APPA Institute - Dallas, TX Feb 2014

2

Definitions (cont.) 

Dynamic Pressure: – The flowing pressure the system pumps must develop to overcome the friction due to piping, coils, valves, fittings, and other devices in the system at a given flow rate. – Head loss, measured in feet of head = 2.31 ft. W.C./psi (1/.434 psi/ft)



Design Pressure – The dynamic pressure the system pumps must develop at the maximum flow in the system. – The differential pressure between the supply and return piping at the pump, i.e. the total head



QUESTION: What will the supply and return pressures be in our 57 psig system if the design head loss at maximum flow is 100’ W.C.?

Supply Pressure = 100’ W.C. X .434 psig/ft + 57 psig = 100 psig Return Pressure = 57 psig 7

System Hydraulic Profile

Pressure

Total Head = 100’

100 psig

Typical Bldg Load Plant Pumps Supply Piping

57 psig

Return Piping

Relative Distance from Plant

8

Basic Formulae The heating and cooling capacity of water when it flows through a coil (heating or cooling) can be calculated as follows:

Basic equation: Q = mcp∆T = ρcpV∆T for water: Q = 60min/hr ·V · 8.33 lb/gal · 1.0 BTU/lb-oF · ∆T = 500 x GPM x ∆T Q = heat rate (Btu/hr, kJ/hr) m = mass flow (lbm//hr, kg/hr) Converting to refrigeration tons: cp = specific heat @ const. press. QTons = 500 x GPM x ∆T ρ = density (lb/cu. ft.) 12,000 BTU/Ton-hr ∆T = temperature difference

Qtons =

GPM × ∆T 24

between supply and return

9

APPA Institute - Dallas, TX Feb 2014

3

Chilled Water System Component Interactions  Pumps/ Piping – Parallel Pumping – Series Pumping – Variable Speed Pumping

 Effect of ∆T on Pump Energy  Effect of ∆T on Pump Flow  Effect of ∆T on Dynamic Pressure 10

Pumping Arrangements

2 Pumps

1 Pump

2 Pumps

1 Pump

11

Varying Pump Speed Qtons

GPM × ∆T = 24

12

APPA Institute - Dallas, TX Feb 2014

4

Delta T vs. Req’d System HP Qtons =

GPM × ∆T 24

∆T vs. System HP For Fixed Load

400 300 200

2. 3

1. 8

4

3

7. 8

5. 5

18 .5

11 .7

62 .5 32

100 0

HP

14 8

Horsepower

40 0

500

0

4

6

8 10 12 14 16 18 20 22 24 26 Temperature Difference 13

Specific Flow vs. ∆T

System Pump HP ~ Q3

14

Dynamic Pressure vs ∆T Qtons =

GPM × ∆T 24

• Increasing supply-to-return differential temperature requires less flow for same heat transferred • Less flow in a given pipe system results in lower velocity • Lower velocity equals lower friction and lower pressure loss • Lower pressure and flow equals lower energy Three Rules for Chilled Water System Optimization Reduce Flow Reduce Flow Reduce Flow 15

APPA Institute - Dallas, TX Feb 2014

5

Chilled Water Distribution System Configurations – Constant/Variable Flow Combinations  Primary  Primary/Secondary  Primary/Secondary/Tertiary

– Variable Direct Primary

16

Constant Primary Only (One unit on) Pump 1000 gpm

Control Valve

Chiller 500 Tons

Bldg Coils

Load equals 1 chiller = 1000 gpm @ 12oF ∆T = 500 Tons 17

CV

Constant Primary Only (Two units on) Pump 1000 gpm

Control Valves bypass excess water into return

Chiller 500 Tons

Bldg Coils Pump 1000 gpm

Chiller 500 Tons

Load equals 1.2 chillers = 600 Tons = 2000 gpm @ 7.2oF ∆T 18

APPA Institute - Dallas, TX Feb 2014

6

Constant Primary / Secondary Pump 1000 gpm

Chiller 500 Tons

Building Secondary Pumps

Bldg Coils

“Bridge” Pump 1000 gpm

Chiller 500 Tons

19

Constant Primary / Secondary / Tertiary Pump 1000 gpm

Chiller 500 Tons

Building Secondary Pumps Secondary Pump

“Bridge”

Bldg Coils

Pump 1000 gpm

Chiller 500 Tons

20

Constant Primary / Variable Secondary (primary and secondary pumps in central plant ) Chiller Pump 1000 gpm

Chiller 500 Tons

Variable Secondary Pump 3000 gpm max.

Bypass (Bridge)

Control Valve

Bldg Coils

Chiller Pump 1000 gpm

Chiller 500 Tons

less than System flow more thanchiller chillerflow flow

Chiller staging indicated by flow direction in the bridge 21

APPA Institute - Dallas, TX Feb 2014

7

Variable Primary Only (One unit on) VF Pump 1000 gpm

Control Valve

Chiller 500 Tons

Bldg Coils

Load equals 1 chiller = 1000 gpm @ 12oF ∆T = 500 Tons 22

Variable Primary Only (Two units on) QUESTION: How can we improve this scheme? VF Pump 600 gpm

Control Valves close against increased pressure

Chiller 500 Tons

Bldg Coils

VF Pump 600 gpm Chiller 500 Tons

Chiller and flow staging accomplished by measurement of ∆P between supply and return at selected location

Load equals 1.2 chillers = 600 Tons = 1200 gpm @ 12oF ∆T 23

Questions & Answers Thank You!

24

APPA Institute - Dallas, TX Feb 2014

8