Plug Fans with EC motor

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd 19.05.2011 11:32 Seite 1 Plug Fans with EC motor The engineer’s choice version 05/2011 Plug_Fans...
Author: Jessie Eaton
6 downloads 0 Views 18MB Size
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 1

Plug Fans with EC motor

The engineer’s choice

version 05/2011

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 2

New Plug fans with EC motor

The plug fans of the centrifugal series with GreenTech EC technology, already established in the market, are now even better! Firstly, all fans above a 500-watt drive output can now be controlled by MODBUS and 0-10V. Secondly, gaps existing in the product range have been filled and the series has been expanded to greater diameters. The sizes 630, 710, 800 and 900 are new. These have been equipped with a stable base frame that enables the entire unit to be decoupled from vibrations in the environment. This makes it possible to achieve additional applications, not just in the heating and ventilation industry. The plug fans are principally intended for operation without a scroll housing. All plug fans shown in the catalogue exceed the minimum efficiency requirements of the ErP Directive for fans, which take effect in 2013 and 2015. Now there are 12 sizes available, with their outer diameters ranging from 250 to 900 mm, which are driven by energy-saving EC external rotor motors with drive capacities between 400 W and 6 kW. The welded impellers with their 7 backward curved blades are made of aluminium as this minimises the bearing load of the motors and maximises durability with high rotational velocity. The position of the impellers on the EC external-rotor motors has been optimised too in terms of aerodynamics and installation requirements. The complete plug fan series is available in the new release of the "Product selector" design program. This tool can be used to select, compare and document fans according to the required operating points. Via a DLL file the plug fans can be integrated into your fan selection programme.

2

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 3

Table of contents

New Plug Fans with EC motor

2

GreenTech: The Green Company

4

Overview

6

Text for tenders

8

Size 250 - 900

10

Accessories (air intake guard grilles, inlet rings)

60

Electrical connections

62

Technical parameters & scope

66

ebm-papst representatives & subsidiaries

70

3

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 4

Sustainability is at the centre of our thoughts and actions. Out of conviction!

Eco-friendliness and sustainability have always been at the core of our thoughts and actions. For decades, we have worked according to the simple but strict creed of our co-founder Gerhard Sturm: “Each new product we develop has to be better than the last one in terms of economy and ecology.” GreenTech is the ultimate expression of our corporate philosophy.

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 5

GreenTech is pro-active development.

GreenTech is acknowledged and certified.

Even in the design phase, the materials and processes we use are optimi-

Every step in our chain of production meets the stringent standards of

sed for the greatest possible eco-friendliness, energy balance and –

environmental specialists and the public. The 2008 Environmental Prize

wherever possible – recyclability. We continually improve the material

of Baden-Wuerttemberg, the Green Award 2009, the Energy Efficiency

and performance of our products, as well as the flow and noise charac-

Award 2009 of the dena – to give just a few examples – testify to this.

teristics. At the same time, we significantly reduce energy consumption.

The environmental advantage gained in the performance of the products

Close co-operation with universities and scientific institutes and the pro-

developed from our GreenTech philosophy can also be measured in the

fessorship we endow in the area of power engineering and regenerative

fulfilment of the most stringent energy and environmental standards.

energies allows us to profit from the latest research findings in these

In many instances, our products are already well below the thresholds

fields – and at the same time ensure highly qualified young academics.

energy legislation will impose a few years from now – several times over.

GreenTech is eco-friendly production.

Our customers profit from this every day.

GreenTech also stands for maximum energy efficiency in our production

The heart of GreenTech is future-oriented EC technology from ebm-

processes. There, the intelligent use of industrial waste heat and ground-

papst. The EC technology at the core of our most efficient motors and

water cooling, photovoltaics and, of course, our own cooling and venti -

fans allows efficiency of up to 90%, saves energy at a very high level,

lation technology are of the utmost importance. Our most modern plant,

significantly extends service life and makes our products maintenance-

for instance, consumes 91% less energy than currently specified and

free. These values pay off not only for the environment, but every cent al-

required. In this way, our products contribute to protecting the environ-

so pays off for the user! All ebm-papst products – even those for which

ment, from their origin to their recyclable packaging.

GreenTech EC technology does not (yet) make sense from an application viewpoint – feature the greatest possible connection of economy and ecology.

5

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

23.05.2011

08:47

Seite 6

New Plug Fans with EC motor Overview of curves

Pa

R3G 250 / M3G 084 R3G 280 / M3G 084 R3G 310 / M3G 112

R3G 355 / M3G 112 R3G 400 / M3G 150 R3G 450 / M3G 150

R3G 500 / M3G 150 R3G 560 / M3G 150 R3G 630 / M3G 200

R3G 710 / M3G 200 R3G 800 / M3G 200 R3G 900 / M3G 200

2000

1000 900 800 700 600 500 400 300

psf

200

100 1000

2000

3000

4000

5000

10000

20000

30000

qV

m3/h

F5 Type Hygiene devices (2) K-Box

Vibration-absorb. elem. D x H / Shore A

K3G250-AT39-74

K3G250-AT39-56

---

K3G250-AV29-B4

K3G250-AV29-B6

---

K3G280-AT04-74

K3G280-AT04-56

---

K3G280-AU06-B2

K3G280-AU06-B4

K3G280-AU06-B6

---

R3G280-AU11-C1

K3G280-AU11-C2

K3G280-AU11-C4

K3G280-AU11-C6

---

1000

R3G310-AX52-90

K3G310-AX52-90

K3G310-AX52-91

K3G310-AX52-35

---

1~ 200-277

1270

R3G310-AX54-21

K3G310-AX54-22

K3G310-AX54-52

---

---

M3G 112-GA

3~ 380-480

1650

R3G310-BB49-01

K3G310-BB49-02

K3G310-BB49-32

---

---

M3G 112-IA

3~ 380-480

2915

R3G310-AZ88-01

K3G310-AZ88-02

K3G310-AZ88-32

K3G310-AZ88-35

---

M3G 112-EA

3~ 380-480

1000

R3G355-AX56-90

K3G355-AX56-90

K3G355-AX56-91

---

---

M3G 112-GA

1~ 200-277

1400

R3G355-AY43-21

K3G355-AY43-22

K3G355-AY43-52

---

---

M3G 112-GA

3~ 380-480

1700

R3G355-AY40-01

K3G355-AY40-02

K3G355-AY40-32

K3G355-AY40-35

---

M3G 112-IA

3~ 380-480

1850

R3G400-AY87-01

K3G400-AY87-02

K3G400-AY87-32

---

---

M3G 150-FF

3~ 380-480

3000

R3G400-AQ23-01

K3G400-AQ23-01

K3G400-AQ23-31

K3G400-AQ23-35

---

M3G 112-IA

3~ 380-480

1650

R3G450-AY86-01

K3G450-AY86-02

K3G450-AY86-32

---

---

M3G 150-FF

3~ 380-480

2730

R3G450-AQ24-01

K3G450-AQ24-01

K3G450-AQ24-31

K3G450-AQ24-35

---

M3G 150-IF

3~ 380-480

5370

R3G450-AZ30-01

K3G450-AZ30-01

K3G450-AZ30-31

K3G450-AZ30-35

---

M3G 150-FF

3~ 380-480

2825

R3G500-AP25-01

K3G500-AP25-01

K3G500-AP25-31

---

---

M3G 150-IF

3~ 380-480

5500

R3G500-AQ33-01

K3G500-AQ33-01

K3G500-AQ33-31

K3G500-AQ33-35

---

M3G 150-IF

3~ 380-480

3000

R3G560-AP23-01

K3G560-AP23-01

K3G560-AP23-31

---

---

M3G 150-NA

3~ 380-480

4700

R3G560-AQ04-01

K3G560-AQ04-01

K3G560-AQ04-31

K3G560-AQ04-35

---

630

M3G 200-HF

3~ 380-480

6140

R3G630-AQ01-01

K3G630-AQ01-01

---

---

50 x 45 / 40

710

M3G 200-LA

3~ 380-480

6240

R3G710-AQ01-01

K3G710-AQ01-01

---

---

50 x 45 / 40

800

M3G 200-QA

3~ 380-480

5800

R3G800-AQ03-01

K3G800-AQ03-01

---

---

50 x 45 / 40

900

M3G 200-QA

3~ 380-480

5950

R3G900-AQ01-01

K3G900-AQ01-01

---

---

50 x 45 / 40

Baugröße Size 250

280

310

355

400

450

500 560

Standard Type Centrifugal fan K-Box

Motor

Supply VAC

Pe W

M3G 084-DF

1~ 200-277

450

R3G250-AT39-71

K3G250-AT39-72

M3G 084-FA

1~ 200-277

700

R3G250-AV29-B1

K3G250-AV29-B2

M3G 084-FA

1~ 200-277

415

R3G280-AT04-71

K3G280-AT04-72

M3G 084-GF

1~ 200-277

715

R3G280-AU06-B1

M3G 084-GF

3~ 380-480

1000

M3G 112-EA

3~ 380-480

M3G 112-EA

(1) Increased

corrosion protection: The support bracket, mounting plate and impeller are coated in black, and the motor also features a black coating.

6

40000

F4-2 Type (1) K-Box

(2) Design

of the hygiene devices: The support bracket, mounting plate and impeller are coated in white, the motor is coated in black, the fastening elements are made of stainless steel.

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 7

Product Selector 2011

Additionaly, and for selecting the correct fan, you can take advan-

Additionally, the life cycle costs for the selected fans can be calculated.

tage of the ebm-papst software "Product Selector" with integrated

You can make your selection based on the operating point or on the type

“Black-Box" module for integration in system configuration pro-

designation.

grammes on the customer side. The data sheets, which can be created in PDF format, show not only the The new selection program gives you the ability to select plug fans based

nominal data of the fan, but also the performance data in the specified

on the operating point. If multiple fans are in the specified power range,

operating point with the inlet and outlet side sound power levels across

the aerodynamic and acoustic data displayed can be used to select and

the octave band.

document the most suitable fan. For more detailed information, simply ask your ebm-papst contact!

7

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 8

EC Centrifugal fan modules K3G 250 to K3G 900

Text for tenders

ebm-papst high performance centrifugal fan modules

Protective features

Single inlet; direct drive; 2D centrifugal impeller with circumferential

- Alarm relay with zero-potential change-over contacts

diffuser mounted on an electronically commutated external-rotor motor

(250 V AC/2 A, cos ϕ = 1)

with integrated electronics; backward curved impeller blades; inlet

- Locked-rotor protection

nozzle made of galvanised sheet steel with pressure relief; complete

- Phase failure detection

unit statically and dynamically balanced in two planes according to

- Soft start of motors

DIN / ISO 1940 and to balancing quality G 6.3; EC external-rotor motor

- Mains under-voltage detection

with maintenance-free ball bearings and permanent lubrication; wide

- Over-temperature protection of electronics and motor

voltage input 1~200-277V, 50/60 Hz respectively 3~380-480V,

- Short-circuit protection

50/60Hz; unit can be operated on all standard Electricity Board networks at identical air performance; optimised motor technology; soft

Technical data

start; integrated current limitation; connection via brought-out variable

- Air flow

qV

cable connector (motor size 084) or via easy-to-mount and robust inte-

- Static pressure

psf = __________Pa

grated terminal box made of aluminium with spring loaded terminals

- Nominal voltage range

U

=

V

(motor sizes 112, 150 and 200); extremely compact electronics; with

- Frequency

f

=

Hz

adjustable PID controller (motor sizes 112, 150 and 200); meets all

- Fan speed

n

= __________rpm

necessary EMC directives and all requirements as to current reverse

- Input power

Pe

= __________kW

transfer; no complicated installation with shielded cables required; very

- Current draw

I

= __________A

low-noise commutation logic; 100% controllability. Motors with an

- Noise level

Lp

= __________dBA

output of 750 W or higher have the RS485/MODBUS RTU interface. If

- Perm. ambient temperature

T

=

structure-borne noise needs to be decoupled, any such action has to

- Fan mass

= __________kg

be taken by the customer.

- Approvals

=

Optionally: Modules with higher protection against corrosion.

Fan type

= __________m3/h

_______________________________

For technical details, dimensions and connection see data sheet

8

°C

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 9

EC centrifugal fans R3G 250 to R3G 900

Text for tenders

ebm-papst high performance centrifugal fans

Protective features

Single inlet; direct drive; 2D centrifugal impeller with circumferential

- Alarm relay with zero-potential change-over contacts

diffuser mounted on an electronically commutated external-rotor motor

(250 V AC/2 A, cos ϕ = 1)

with integrated electronics; backward curved impeller blades; inlet

- Locked-rotor protection

nozzle made of galvanised sheet steel; complete unit statically and

- Phase failure detection

dynamically balanced in two planes according to DIN / ISO 1940 and to

- Soft start of motors

balancing quality G 6.3; EC external-rotor motor with maintenance-free

- Mains under-voltage detection

ball bearings and permanent lubrication; wide voltage input

- Over-temperature protection of electronics and motor

1~200-277V, 50/60 Hz respectively 3~380-480V, 50/60Hz; unit can be

- Short-circuit protection

operated on all standard Electricity Board networks at identical air performance; optimised motor technology; soft start; integrated current

Technical data

limitation; connection via brought-out variable cable connector (motor

- Air flow

qV

= __________m3/h

size 084) or via easy-to-mount and robust integrated terminal box

- Static pressure

psf = __________Pa

made of aluminium with spring loaded terminals (motor sizes 112, 150

- Nominal voltage range

U

=

V

and 200); extremely compact electronics; with adjustable PID controller

- Frequency

f

=

Hz

(motor sizes 112, 150 and 200); meets all necessary EMC directives

- Fan speed

n

= __________rpm

and all requirements as to current reverse transfer; no complicated

- Input power

Pe

= __________kW

installation with shielded cables required; very low-noise commutation

- Current draw

I

= __________A

logic; 100% controllability. Motors with an output of 750 W or higher

- Noise level

Lp

= __________dBA

have the RS485/MODBUS RTU interface.

- Perm. ambient temperature

T

=

°C

- Fan mass

= __________kg

For technical details, dimensions and connection -

- Direction of rotation

= rechts

see data sheet

- Approvals

=

Fan type _______________________________

9

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 10

EC centrifugal fan and modules backward curved, Ø 250

Perm. amb. temp.

Electr. connection

M3G 084-DF

Max. current draw(1)

*3G 250

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet aluminium Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 62

50/60

3000

450

2,80

-25..+40

1~ 200-277

A

K1)

(1) Nominal data in operating point with maximum load and 230 VAC

subject to alterations

Pa

in H2O

Curves A

Air performance measured

3175

380

2,48

84

2

3045

436

2,72

80

A

3

3000

450

2,80

76

A

4

3020

436

2,72

80

A

5

2575

201

1,34

79

Suction-side noise levels:

A

6

2510

228

1,50

75

LWA as per ISO 13347,

A

7

2470

235

1,57

73

LpA measured at 1 m distance

A

8

2495

224

1,51

76

A

9

2000

92

0,66

74

A

10

2000

112

0,78

71

A

11

1990

125

0,88

68

A

12

2015

118

0,84

71

4,0

accidental contact

3,2

LWA dB(A)

1

without protection against

4

I A

A

with ebm-papst inlet nozzle

800

Pe W

A

as per: ISO 5801, Installation category A,

1000

n rpm

600

2,4

to fan axis The acoustic values given are

3

only valid under the measur-

8

ment conditions listed and 1,6

may vary depending on the

400

installation situation.

7 12

With any deviation to the stan-

2 11

dard setup, the specific values

0,8

200

have to be checked and re-

6

viewed once installed or fitted! 10

For detailed information

psf

9 0

qV

10

400

400

800

800

1200

1 1600

5 1200

1600

2000

2400

see page 66 ff. cfm

2800 m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 11

Mass of centrifugal module with support bracket

Masse centrifugal fan

Mass of centrifugal module with support bracket

– Technical features: • Output 10 VDC max. 1,1 mA • PFC (passive) • Alarm relay • Control input 0-10 VDC / PWM • Over-temperature protected electronics / motor – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Cable exit: Variable – Protection class: I – Product conforming to standards: EN 61800-5-1, CE – Approvals: UL, CSA; VDE, CCC, GOST are applied for

Centrifugal fan

kg

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

R3G 250-AT39 -71

4,4

25075-2-4013

K3G 250-AT39 -72

8,7

K3G 250-AT39 -74

8,7

(2) Centrifugal module with higher protection against corrosion

4x90˚

4xØ4.5

201,5±3 153,5 ±2

48 130±1

30˚

43

45˚

Depth of screw 8-10 mm

R3G 250-AT39 -71 Ø6.5

4x90˚ 600+20 85

Ø260 Ø290

Ø166.2

Ø176 Ø284

Ø102

(Ø251)

Ø178 Ø150±0.25 Ø100

M6

80 112

6

Ø164±0.35

Connection line AWG 22, 3x crimped core-end sleeves

Core-end sleeves K3G 250-AT39 -72 / -74 2

o400±1.2 o298

Connection line AWG 18, 5x crimped core-end sleeves

Observe the correct mounting position ! Install the support struts only vertically as shown in the view !

4xØ11

85

±1

0

60

0+

20

237±3 187±1

o350

Pressure tap

11 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 62

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 12

EC centrifugal fan and modules backward curved, Ø 250

subject to alterations

Perm. amb. temp.

Electr. connection

M3G 084-FA

Max. current draw(1)

*3G 250

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet aluminium Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 63

50/60

3450

700

3,00

-25..+40

1~ 200-277

A

L7)

(1) Nominal data in operating point with maximum load and 230 VAC

Pa

in H2O

Curves A

Air performance measured

3450

469

2,07

85

2

3450

591

2,64

82

A

3

3450

700

3,00

78

A

4

3450

661

2,95

81

A

5

2890

268

1,18

81

Suction-side noise levels:

A

6

2890

337

1,51

78

LWA as per ISO 13347,

A

7

2890

401

1,79

74

LpA measured at 1 m distance

A

8

2890

378

1,69

77

A

9

2300

135

0,60

76

A

10

2300

170

0,76

73

A

11

2300

202

0,90

69

A

12

2300

190

0,85

72

4,0

without protection against

3,2

3 8

to fan axis

2,4

600

The acoustic values given are only valid under the measur7

ment conditions listed and may vary depending on the

12

installation situation.

1,6

400

11

2

With any deviation to the standard setup, the specific values

6

0,8

200

have to be checked and reviewed once installed or fitted!

10

psf

For detailed information 0

qV

12

400

400

9 1200

800

800

LWA dB(A)

1

accidental contact

800

I A

A

with ebm-papst inlet nozzle

4

Pe W

A

as per: ISO 5801, Installation category A,

1000

n rpm

1200

1600

2000

1600

2400

see page 66 ff.

1

5

2800

cfm m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 13

Masse centrifugal fan

Line undervoltage detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start

Mass of centrifugal module with support bracket

• • • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (active) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: EN 61800-5-1, CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Centrifugal fan

kg

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

R3G 250-AV29 -B1

5,6

25075-2-4013

K3G 250-AV29 -B2

10,1

K3G 250-AV29 -B4

10,1

(2) Centrifugal module with higher protection against corrosion

Depth of screw 12-16 mm

223.9±3 167.4±2

4x Ø4.5

56.5

156±1

5x

72

43

˚

R3G 250-AV29 -B1

Ø260 Ø290

Ø166.2

Ø176 Ø284

Ø102

Ø197 Ø165±0.25 Ø130

Ø5.5

Tightening torque 3.5±0.5 Nm Ø186±0,5 80 112

Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm

6

257.5±3 201±1

2

o400-1 o298

Observe the correct mounting position ! Install the support struts only vertically as shown in the view !

4xØ11

K3G 250-AV29 -B2 / -B4

M16x1.5(3x)

Pressure tap

o350

13 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 63

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 14

EC centrifugal fan and modules backward curved, Ø 280

Perm. amb. temp.

Electr. connection

M3G 084-FA

Max. current draw(1)

*3G 280

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet aluminium Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 62

50/60

2400

415

2,70

-25..+40

1~ 200-277

A

K1)

(1) Nominal data in operating point with maximum load and 230 VAC

subject to alterations

Pa

A

Air performance measured

2530

335

2,19

80

2415

392

2,57

75

A

3

2400

415

2,70

71

A

4

2405

405

2,66

75

A

5

2040

171

1,17

74

Suction-side noise levels:

A

6

1990

216

1,45

69

LWA as per ISO 13347,

A

7

1965

237

1,58

67

LpA measured at 1 m distance

A

8

2010

215

1,45

70

A

9

1570

85

0,63

67

A

10

1575

111

0,79

63

A

11

1560

122

0,86

62

A

12

1580

106

0,76

64

2,8

accidental contact

2,4

to fan axis

2,0

500

The acoustic values given are

3

only valid under the measur-

8

1,6

400

ment conditions listed and may vary depending on the installation situation.

7

1,2

300

12

2

0,8

200

With any deviation to the standard setup, the specific values

11 6

have to be checked and reviewed once installed or fitted!

10

0,4

100

For detailed information

psf

9 0

qV

14

LWA dB(A)

2

without protection against

600

I A

1

Installation category A,

4

Pe W

A

with ebm-papst inlet nozzle

700

n rpm A

as per: ISO 5801,

3,2

800

in H2O

Curves

500

500

1000

1000

1500

2000

5 1500

2500

see page 66 ff.

1 cfm

3000

m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 15

Mass of centrifugal module with support bracket

Masse centrifugal fan

Mass of centrifugal module with support bracket

– Technical features: • Output 10 VDC max. 1,1 mA • PFC (passive) • Alarm relay • Control input 0-10 VDC / PWM • Over-temperature protected electronics / motor – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Cable exit: Variable – Protection class: I – Product conforming to standards: EN 61800-5-1, CE – Approvals: UL, CSA; VDE, CCC, GOST are applied for

Centrifugal fan

kg

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

R3G 280-AT04 -71

5,4

28075-2-4013

K3G 280-AT04 -72

9,8

K3G 280-AT04 -74

9,8

(2) Centrifugal module with higher protection against corrosion

4x90˚

4xØ4.5

227±3 179±2

48 145±1

30˚

53

45˚

Depth of screw 8-10 mm

R3G 280-AT04 -71 Ø6.5

4x90˚ 600+20 85

Ø280 Ø325

Ø187.2

Ø197.4 Ø319

Ø102

(Ø282)

Ø178 Ø150±0.25 Ø100

M6

90 132

10

Ø164±0.35

Connection line AWG 22, 3x crimped core-end sleeves

Core-end sleeves K3G 280-AT04 -72 / -74 2

o400±1.2 o298

Connection line AWG 18, 5x crimped core-end sleeves

Observe the correct mounting position ! Install the support struts only vertically as shown in the view !

4xØ11

85

±1

0

60

0+

20

Ø319±2

268±3 218±1

o350

Pressure tap

15 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 62

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 16

EC centrifugal fan and modules backward curved, Ø 280

subject to alterations

Perm. amb. temp.

Electr. connection

M3G 084-GF

Max. current draw(1)

*3G 280

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet aluminium Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 63

50/60

2800

715

3,10

-25..+40

1~ 200-277

A

L7)

(1) Nominal data in operating point with maximum load and 230 VAC

Pa

in H2O

Curves A

2800

479

2,11

83

2

2800

655

2,88

79

A

3

2800

715

3,10

76

A

4

2800

650

2,85

82

A

5

2400

294

1,30

79

Suction-side noise levels:

A

6

2400

410

1,80

75

LWA as per ISO 13347,

A

7

2400

471

2,06

73

LpA measured at 1 m distance

A

8

2400

401

1,76

78

A

9

1900

146

0,65

74

A

10

1900

203

0,89

70

A

11

1900

234

1,02

68

A

12

1900

199

0,87

73

3,2

Installation category A,

2,8

accidental contact

to fan axis

2,0

500

2,4

3 8

7

The acoustic values given are only valid under the measur-

1,6

400

ment conditions listed and

12

1,2

2

300

may vary depending on the installation situation.

11 6

0,8

With any deviation to the stan-

200

dard setup, the specific values 10

have to be checked and reviewed once installed or fitted!

0,4

100

For detailed information

psf

9 0

qV

16

LWA dB(A)

1

without protection against

600

I A

A

with ebm-papst inlet nozzle

700

Pe W

A

as per: ISO 5801, 4

800

Air performance measured

n rpm

500

500

1000

1000

1500

1500

2000

2500

2000

3000

see page 66 ff.

1

5

3500

cfm m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 17

Masse centrifugal fan

Line undervoltage detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start

Mass of centrifugal module with support bracket

• • • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (active) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: EN 61800-5-1, CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Centrifugal fan

kg

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

R3G 280-AU06 -B1

6,8

28075-2-4013

K3G 280-AU06 -B2

11,4

K3G 280-AU06 -B4

11,4

(2) Centrifugal module with higher protection against corrosion

Depth of screw 12-16 mm

252.4±3 196±2 171.4±1

4x Ø4.5

56.5

5x

72

53

˚

R3G 280-AU06 -B1

Ø280 Ø325

Ø187.2

Ø197.4 Ø319

Ø102

Ø197 Ø165±0.25 Ø130

Ø5.5

Tightening torque 3.5±0.5 Nm Ø186±0,5 90 132

Cable gland: M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm

291.5±3 235±1

o400-1 o298

2

Observe the correct mounting position ! Install the support struts only vertically as shown in the view !

4xØ11

Ø319±2

K3G 280-AU06 -B2 / -B4

10

M16x1.5(3x)

o350

Pressure tap

17 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 63

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:32

Seite 18

EC centrifugal fan and modules backward curved, Ø 280

subject to alterations

Perm. amb. temp.

Electr. connection

M3G 084-GF

Max. current draw(1)

*3G 280

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet aluminium Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 63

50/60

3100

1000

1,60

-25..+60

3~ 380-480

A

L6)

(1) Nominal data in operating point with maximum load and 400 VAC

Pa

in H2O

Curves A

Air performance measured

3100

645

1,04

86

2

3100

852

1,35

83

A

3

3100

1000

1,60

80

A

4

3100

921

1,46

83

A

5

2575

358

0,58

82

Suction-side noise levels:

A

6

2575

482

0,76

79

LWA as per ISO 13347,

A

7

2575

562

0,89

76

LpA measured at 1 m distance

A

8

2575

514

0,82

79

A

9

2045

180

0,29

77

A

10

2045

242

0,38

74

A

11

2045

282

0,45

71

A

12

2045

257

0,41

74

4,0

without protection against

3,2

3

to fan axis

2,4

8

600

The acoustic values given are only valid under the measur-

7

ment conditions listed and may vary depending on the

1,6

12

400

installation situation.

2 11

With any deviation to the stan6

dard setup, the specific values have to be checked and re-

0,8

200

viewed once installed or fitted!

10

psf

For detailed information 0

qV

18

500

500

1000

9 1500

1000

1500

LWA dB(A)

1

accidental contact

800

I A

A

with ebm-papst inlet nozzle

4

Pe W

A

as per: ISO 5801, Installation category A,

1000

n rpm

2000

2500

5 2000

3000

3500

1 cfm m3/h

see page 66 ff.

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 19

Masse centrifugal fan

Line undervoltage / phase failure detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start

Mass of centrifugal module with support bracket

• • • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: EN 61800-5-1, CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Centrifugal fan

kg

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

R3G 280-AU11 -C1

7,1

28075-2-4013

K3G 280-AU11 -C2

11,7

K3G 280-AU11 -C4

11,7

(2) Centrifugal module with higher protection against corrosion

Depth of screw 12-16 mm

252.4±3 196±2 171.4±1

4x Ø4.5

56.5

5x

72

53

˚

R3G 280-AU11 -C1

Ø280 Ø325

Ø187.2

Ø197.4 Ø319

Ø102

Ø197 Ø165±0.25 Ø130

Ø5.5

Tightening torque 3.5±0.5 Nm Ø186±0,5 90 132

Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm

291.5±3 235±1

o400-1 o298

2

Observe the correct mounting position ! Install the support struts only vertically as shown in the view !

4xØ11

Ø319±2

K3G 280-AU11 -C2 / -C4

10

M16x1.5(3x)

o350

Pressure tap

19 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 63

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 20

EC centrifugal fan and modules backward curved, Ø 310

Perm. amb. temp.

Electr. connection

M3G 112-EA

Max. current draw(1)

*3G 310

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 63

50/60

2580

1000

1,60

-25..+55

3~ 380-480

A

L6)

(1) Nominal data in operating point with maximum load and 400 VAC

subject to alterations

Pa

A

Air performance measured

2580

669

1,17

88

2580

862

1,46

81

A

3

2580

1000

1,60

77

A

4

2580

907

1,53

79

A

5

1930

288

0,57

80

Suction-side noise levels:

A

6

1910

348

0,69

74

LWA as per ISO 13347,

A

7

1900

396

0,77

500

3,2 2,8 2,4

600

70

LpA measured at 1 m distance

A

8

1905

360

0,72

71

A

9

1305

123

0,28

72

A

10

1305

144

0,33

67

A

11

1305

151

0,34

62

A

12

1300

151

0,34

62

accidental contact

3

to fan axis The acoustic values given are

8

only valid under the measurment conditions listed and

1,6

400

2

may vary depending on the

7

1,2

installation situation.

300

With any deviation to the stan12

0,8

200

dard setup, the specific values

6

have to be checked and re-

11

0,4

viewed once installed or fitted!

100

10

For detailed information

psf

9 0

qV

20

LWA dB(A)

2

without protection against

2,0

700

I A

1

with ebm-papst inlet nozzle

800

Pe W

A

Installation category A,

4

n rpm A

as per: ISO 5801,

3,6

900

in H2O

Curves

500

1000

1000

5 2000

1500

2000

3000

see page 66 ff.

1 2500

4000

cfm m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 21

Masse centrifugal fan

Line undervoltage / phase failure detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start

Mass of centrifugal module with support bracket

• • • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Centrifugal fan

kg

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

R3G 310-AX52 -90

8,8

31575-2-4013

K3G 310-AX52 -90

16,7

K3G 310-AX52 -91

16,7

(2) Centrifugal module with higher protection against corrosion

253,7±3 197,2±2

Depth of screw 12-16 mm 4xØ4,5

56,5

R3G 310-AX52 -90

5xM6

55

160,5±1

˚

72

Ø325 Ø350

Ø211,7

Ø222 Ø360

Ø138

5x

Ø168 Ø186±0,5

Tightening torque 3.5±0.5 Nm Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm

100 147

10

294±3 237.5±2.5

o500-1 o372

15

Observe the correct mounting position ! Install the support struts only vertically as shown in the view !

4xØ11

K3G 310-AX52 -90 / -91

M16x1.5(3x) o450

Pressure tap

21 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 63

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 22

EC centrifugal fan and modules backward curved, Ø 310

subject to alterations

Electr. connection

A

Perm. amb. temp.

M3G 112-EA

Max. current draw(1)

*3G 310

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 65

50/60

2850

1270

5,60

-25..+60

1~ 200-277

L9)

(1) Nominal data in operating point with maximum load and 230 VAC

n rpm

Pa

1200

4,8 in H2O

Curves A

Air performance measured

1

2930

946

4,14

88

2

2895

1147

5,01

83

A

3

2850

1270

5,60

79

A

4

2850

1237

5,41

83

A

5

2430

529

2,34

84

Suction-side noise levels:

A

6

2430

663

2,91

78

LWA as per ISO 13347,

A

7

2430

743

3,26

77

LpA measured at 1 m distance

A

8

2430

751

3,29

78

A

9

1955

299

1,36

78

A

10

1955

360

1,61

73

A

11

1955

398

1,77

72

A

12

1955

400

1,78

73

without protection against

4,0

accidental contact

3,2

800

8

to fan axis

3

2,4

The acoustic values given are

600

only valid under the measur7

ment conditions listed and

12

may vary depending on the installation situation.

2

1,6

400

11

With any deviation to the stan6

dard setup, the specific values have to be checked and re-

0,8

200

10

viewed once installed or fitted!

psf

For detailed information 0

qV

22

500

1000

1000

9 2000

1500

2000

3000

LWA dB(A)

A

Installation category A,

4

I A

A

as per: ISO 5801, with ebm-papst inlet nozzle

1000

Pe W

5 2500

4000

see page 66 ff.

1 cfm

5000

m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 23

kg

R3G 310-AX54 -21

11,0

Line undervoltage detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start

Mass of centrifugal module with support bracket

Masse centrifugal fan Centrifugal fan

• • • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (active) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

31575-2-4013

K3G 310-AX54 -22

19,4

K3G 310-AX54 -52

19,4

(2) Centrifugal module with higher protection against corrosion

72

269.2 ±3 197.2 ±2

4xØ4.5

R3G 310-AX54 -21

Depth of screw 12-16 mm

55

6xM10

Ø325 Ø350

Ø211.7

Ø 222 Ø 360

Ø 138



6x6

Ø 232±0.3

Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

100 147

Ø 252±0.5

10

309.5±3 273.5±2

o500-1 o375

15

Tightening torque 3.5±0.5 Nm

Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)

K3G 310-AX54 -22 / -52

5

. 0x1 M2 3x) (

o450

Pressure tap

23 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 65

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 24

EC centrifugal fan and modules backward curved, Ø 310

subject to alterations

Perm. amb. temp.

Electr. connection

M3G 112-GA

Max. current draw(1)

*3G 310

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

3140

1650

2,50

-25..+60

3~ 380-480

A

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

Pa

1400

in H2O

Curves A

Air performance measured

3140

1158

1,79

90

2

3140

1440

2,21

86

A

3

3140

1650

2,50

83

A

4

3140

1559

2,39

87

A

5

2620

658

1,02

85

Suction-side noise levels:

A

6

2620

824

1,26

82

LWA as per ISO 13347,

A

7

2620

942

1,44

79

LpA measured at 1 m distance

A

8

2620

889

1,36

83

A

9

2100

339

0,52

81

A

10

2100

425

0,65

77

A

11

2100

485

0,74

74

A

12

2100

458

0,70

78

4,8

without protection against accidental contact

3 8

LWA dB(A)

1

Installation category A,

4,0

1000

I A

A

with ebm-papst inlet nozzle

1200

Pe W

A

as per: ISO 5801, 4

n rpm

800

3,2

to fan axis The acoustic values given are 7

ment conditions listed and

2,4

600

only valid under the measur-

12

may vary depending on the installation situation.

2 1,6

11

400

With any deviation to the stan6

dard setup, the specific values have to be checked and re-

0,8

200

10

viewed once installed or fitted!

psf

For detailed information 0

qV

24

500

1000

1000

9 2000

1500

2000

3000

5 2500

4000

see page 66 ff.

1 3000

5000

cfm m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 25

kg

R3G 310-BB49 -01

12,6

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Masse centrifugal fan Centrifugal fan

• • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC bzw. 4-20 mA • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

31575-2-4013

K3G 310-BB49 -02

21,0

K3G 310-BB49 -32

21,0

(2) Centrifugal module with higher protection against corrosion

60

277.2 ±3 217.2 ±2

4xØ4.5

R3G 310-BB49 -01

Depth of screw 12-16 mm

55

6xM10

Ø325 Ø350

Ø211.7

Ø 222 Ø 360

Ø 138



6x6

Ø 232±0.3

Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

100 147

Ø 252±0.5

10

318.5±3 258.5±2

o500-1 o375

15

Tightening torque 3.5±0.5 Nm

Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)

K3G 310-BB49 -02 / -32

5

. 0x1 M2 3x) (

o450

Pressure tap

25 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 26

EC centrifugal fan and modules backward curved, Ø 310

subject to alterations

Perm. amb. temp.

Electr. connection

M3G 112-IA

Max. current draw(1)

*3G 310

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

4100

2915

4,50

-25..+40

3~ 380-480

A

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

Pa

in H2O

Curves A

Air performance measured

4100

1976

3,03

97

2

4100

2488

3,77

91

A

3

4100

2915

4,50

89

A

4

4100

2750

4,19

93

A

5

3400

1127

1,73

93

Suction-side noise levels:

A

6

3400

1428

2,17

87

LWA as per ISO 13347,

A

7

3400

1659

2,53

85

LpA measured at 1 m distance

A

8

3400

1566

2,39

89

A

9

2700

564

0,87

88

A

10

2700

715

1,08

82

A

11

2700

831

1,27

80

A

12

2700

784

1,19

84

8,0

accidental contact

3

LWA dB(A)

1

without protection against

6,4

1600

I A

A

with ebm-papst inlet nozzle 4

Pe W

A

as per: ISO 5801, Installation category A,

2000

n rpm

to fan axis 4,8

8

1200

The acoustic values given are only valid under the measur7

ment conditions listed and may vary depending on the installation situation.

12

3,2

800

2 11

With any deviation to the stan6

dard setup, the specific values have to be checked and re-

1,6

400

10

viewed once installed or fitted! For detailed information

psf

9 0

qV

26

500

1000

1000

1500

2000

2000

3000

5 2500

4000

3000

5000

1 cfm m3/h

see page 66 ff.

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 27

kg

R3G 310-AZ88 -01

15,0

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Masse centrifugal fan Centrifugal fan

• • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC bzw. 4-20 mA • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

31575-1-4013

K3G 310-AZ88 -02

24,2

K3G 310-AZ88 -32

24,2

(2) Centrifugal module with higher protection against corrosion

69.5

287±3 217.5 ±2

4xØ4.5

R3G 310-AZ88 -01

Depth of screw 12-16 mm

55

6xM10

Ø325 Ø350

Ø211.7

Ø 222 Ø 360

Ø 138



6x6

Ø 232±0.3

Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

80 127

Ø 252±0.5

10

328±3 258.5±2

o500-1 o375

15

Tightening torque 3.5±0.5 Nm

Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)

K3G 310-AZ88 -02 / -32

5

. 0x1 M2 3x) (

o450

Pressure tap

27 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 28

EC centrifugal fan and modules backward curved, Ø 355

Perm. amb. temp.

Electr. connection

M3G 112-EA

Max. current draw(1)

*3G 355

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 63

50/60

2140

1000

1,70

-25..+60

3~ 380-480

A

L6)

(1) Nominal data in operating point with maximum load and 400 VAC

subject to alterations

Pa

A

Air performance measured

2140

656

1,14

87

2140

893

1,50

77

A

3

2140

1000

1,70

75

A

4

2140

918

1,54

78

A

5

1610

286

0,57

79

Suction-side noise levels:

A

6

1595

350

0,68

70

LWA as per ISO 13347,

A

7

1580

387

0,74

69

LpA measured at 1 m distance

A

8

1585

366

0,70

70

A

9

1080

113

0,28

71

A

10

1065

133

0,31

64

A

11

1065

143

0,33

60

A

12

1060

135

0,32

61

with ebm-papst inlet nozzle

2,8

accidental contact

2,4

to fan axis

2,0

500

The acoustic values given are 8

1,6

400

only valid under the measur-

2

ment conditions listed and

1,2

200

0,8

7

300

may vary depending on the installation situation. With any deviation to the stan6

dard setup, the specific values

12

have to be checked and re-

11

viewed once installed or fitted!

0,4

100

10

psf

For detailed information 0

qV

28

LWA dB(A)

2

3

600

I A

1

without protection against

700

Pe W

A

Installation category A,

4

n rpm A

as per: ISO 5801,

3,2

800

in H2O

Curves

500

1000

9 1500

1000

2000

2000

3000

see page 66 ff.

1

5 2500

4000

3000

5000

cfm m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 29

Masse centrifugal fan

Line undervoltage / phase failure detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start

Mass of centrifugal module with support bracket

• • • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Centrifugal fan

kg

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

R3G 355-AX56 -90

9,4

35675-2-4013

K3G 355-AX56 -90

17,4

K3G 355-AX56 -91

17,4

(2) Centrifugal module with higher protection against corrosion

270,7±3 214,2±2

56,5

Depth of screw 12-16 mm 4xØ4,5

R3G 355-AX56 -90

5xM6

64,5

160,5±1

˚

72

Ø345 Ø370

Ø239

Ø250,3 Ø404

Ø138

Ø405

5x

Ø168 Ø186±0,5

Tightening torque 3.5±0.5 Nm 112

Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm

164

12

319.5±3 263±2.5

o500-1 o372

15

Observe the correct mounting position ! Install the support struts only vertically as shown in the view !

4xØ11

K3G 355-AX56 -90 / -91

M16x1.5(3x) o450

Pressure tap

29 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 63

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 30

EC centrifugal fan and modules backward curved, Ø 355

subject to alterations

Electr. connection

A

Perm. amb. temp.

M3G 112-GA

Max. current draw(1)

*3G 355

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 65

50/60

2450

1400

6,00

-25..+50

1~ 200-277

L9)

(1) Nominal data in operating point with maximum load and 230 VAC

n rpm

Pa

in H2O

Curves A

Air performance measured

1

2450

998

4,33

86

2

2440

1232

5,35

82

A

3

2450

1400

6,00

79

A

4

2410

1344

5,84

82

A

5

2035

562

2,44

82

Suction-side noise levels:

A

6

2035

715

3,11

78

LWA as per ISO 13347,

A

7

2035

855

3,72

76

LpA measured at 1 m distance

A

8

2035

810

3,52

78

A

9

1630

289

1,25

77

A

10

1630

368

1,60

73

A

11

1630

440

1,91

71

A

12

1630

416

1,81

73

4,0

without protection against

3,2

accidental contact

800

3 8

to fan axis

2,4

600

The acoustic values given are only valid under the measur-

7

ment conditions listed and may vary depending on the

12

installation situation.

1,6

400

2 11

With any deviation to the standard setup, the specific values

6

have to be checked and re-

0,8

200

10

viewed once installed or fitted!

psf

For detailed information 0

qV

30

500

1000

1000

2000

LWA dB(A)

A

with ebm-papst inlet nozzle 4

I A

A

as per: ISO 5801, Installation category A,

1000

Pe W

1500

2000

3000

9 2500

4000

5 3000

5000

see page 66 ff.

1 3500

6000

cfm m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 31

kg

R3G 355-AY43 -21

14,0

Line undervoltage detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start

Mass of centrifugal module with support bracket

Masse centrifugal fan Centrifugal fan

• • • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (active) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

35675-2-4013

K3G 355-AY43 -22

22,4

K3G 355-AY43 -52

22,4

(2) Centrifugal module with higher protection against corrosion

72

306.2 ±3 234.2 ±2

4xØ4.5

R3G 355-AY43 -21

Depth of screw 12-16 mm

64.4

6xM10

Ø345 Ø370

Ø239

Ø 250.3 Ø 404

Ø 405

Ø 138



6x6

Ø 232±0.3

112 164

Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

354.5±3 282.5±2

o500-1 o375

15

Tightening torque 3.5±0.5 Nm

Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)

Ø405

K3G 355-AY43 -22 / -52

Ø 252±0.5

12

5

. 0x1 M2 3x) (

o450

Pressure tap

31 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 65

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 32

EC centrifugal fan and modules backward curved, Ø 355

Perm. amb. temp.

Electr. connection

M3G 112-GA

Max. current draw(1)

*3G 355

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

2600

1700

2,60

-25..+40

3~ 380-480

A

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

subject to alterations

Pa

1200

4,8 in H2O

Curves A

Air performance measured

2600

1140

1,74

92

2

2600

1510

2,30

83

A

3

2600

1700

2,60

79

A

4

2600

1594

2,42

83

A

5

1940

436

0,73

84

Suction-side noise levels:

A

6

1910

541

0,88

76

LWA as per ISO 13347,

A

7

1885

533

0,95

73

LpA measured at 1 m distance

A

8

1905

558

0,91

76

A

9

1330

194

0,40

76

A

10

1315

226

0,45

70

A

11

1305

239

0,47

66

A

12

1305

236

0,46

66

with ebm-papst inlet nozzle

4,0

accidental contact

3,2

800

LWA dB(A)

1

Installation category A,

3

I A

A

without protection against

1000

Pe W

A

as per: ISO 5801, 4

n rpm

to fan axis

600

2,4

The acoustic values given are 8

only valid under the measurment conditions listed and 2

may vary depending on the

7

1,6

400

installation situation. With any deviation to the stan-

12

0,8

200

dard setup, the specific values

6

have to be checked and re-

11

viewed once installed or fitted! 10

psf

For detailed information 0

qV

32

500

1000

1000

2000

1500

9 2000

3000

2500

4000

see page 66 ff.

1

5 3000

5000

3500

6000

cfm m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 33

kg

R3G 355-AY40 -01

13,1

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Masse centrifugal fan Centrifugal fan

• • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC bzw. 4-20 mA • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

35675-2-4013

K3G 355-AY40 -02

23,4

K3G 355-AY40 -32

23,4

(2) Centrifugal module with higher protection against corrosion

294.2±3 234.2±2

60

4xØ4.5

R3G 355-AY40 -01

Depth of screw 12-16 mm

64.4

6xM10

182±1

Ø345 Ø370

Ø239

Ø 250.3 Ø 404

Ø 405

Ø 138



6x6

Ø 232±0.3

112 163.7

Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

342.5±3 282.5±2

o500-1 o375

15

Tightening torque 3.5±0.5 Nm

Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)

Ø405

K3G 355-AY40 -02 / -32

Ø 252±0.5

12

5

. 0x1 M2 3x) (

o450

Pressure tap

33 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 34

EC centrifugal fan and modules backward curved, Ø 400

subject to alterations

Electr. connection

A

Perm. amb. temp.

M3G 112-IA

Max. current draw(1)

*3G 400

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

2180

1850

2,90

-25..+50

3~ 380-480

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

Pa

in H2O

Curves A

Air performance measured

2180

1178

1,81

89

2

2180

1748

2,66

82

A

3

2180

1850

2,90

81

A

4

2180

1638

2,49

84

A

5

1850

720

1,10

85

Suction-side noise levels:

A

6

1850

1063

1,62

78

LWA as per ISO 13347,

A

7

1850

1132

1,72

77

LpA measured at 1 m distance

A

8

1850

1001

1,52

80

A

9

1470

361

0,55

80

A

10

1470

533

0,81

73

A

11

1470

568

0,86

72

A

12

1470

502

0,76

75

4,0

accidental contact

3,2

800

8

to fan axis 7

2,4

600

The acoustic values given are

2

only valid under the measurment conditions listed and 1,6

12

400

may vary depending on the

6

installation situation.

11

With any deviation to the stan10

dard setup, the specific values have to be checked and re-

0,8

200

viewed once installed or fitted!

psf

For detailed information 0

qV

34

1000

1000

2000

LWA dB(A)

1

without protection against

3

I A

A

with ebm-papst inlet nozzle 4

Pe W

A

as per: ISO 5801, Installation category A,

1000

n rpm

9 3000

2000

3000

4000

5000

5 4000

6000

7000

1 cfm m3/h

see page 66 ff.

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 35

kg

R3G 400-AY87 -01

15,6

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Masse centrifugal fan Centrifugal fan

• • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC bzw. 4-20 mA • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

40075-2-4013

K3G 400-AY87 -02

26,0

K3G 400-AY87 -32

26,0

(2) Centrifugal module with higher protection against corrosion

330.5±3 273 ±2

57.5

6xØ9

R3G 400-AY87 -01

Depth of screw 12-16 mm

68

6xM10

202±1

Ø390 Ø413

Ø270.9

Ø 282 Ø 455

Ø 138



6x6

Ø 232±0.3

125 182

Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

384±3 327±2

o500-1 o375

15

Tightening torque 3.5±0.5 Nm

Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)

Ø455

K3G 400-AY87 -02 / -32

Ø 252±0.5

9

5

. 0x1 M2 3x) (

o450

Pressure tap

35 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 36

EC centrifugal fan and modules backward curved, Ø 400

Perm. amb. temp.

Electr. connection

M3G 150-FF

Max. current draw(1)

*3G 400

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

2550

3000

4,60

-25..+60

3~ 380-480

A

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

subject to alterations

Pa

1400

in H2O

Curves A

Air performance measured

2550

1989

3,03

93

2

2550

2578

3,92

87

A

3

2550

3000

4,60

85

A

4

2550

2890

4,41

87

A

5

2115

1135

1,73

89

Suction-side noise levels:

A

6

2115

1471

2,24

83

LWA as per ISO 13347,

A

7

2115

1709

2,61

81

LpA measured at 1 m distance

A

8

2115

1649

2,52

83

A

9

1680

569

0,87

84

A

10

1680

737

1,12

78

A

11

1680

857

1,31

76

A

12

1680

826

1,26

78

with ebm-papst inlet nozzle

4,8

without protection against accidental contact

4,0

8

LWA dB(A)

1

3

1000

I A

A

Installation category A,

1200

Pe W

A

as per: ISO 5801, 4

n rpm

800

3,2

to fan axis 7

The acoustic values given are only valid under the measurment conditions listed and

2,4

600

2

12

may vary depending on the installation situation.

1,6

11

400

6

With any deviation to the standard setup, the specific values have to be checked and re-

200

0,8

10

viewed once installed or fitted! For detailed information

psf

9 0

qV

36

1000

2000

2000

3000

4000

1 cfm

5 4000

6000

8000

m3/h

see page 66 ff.

19.05.2011

Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay

Masse centrifugal fan Centrifugal fan

kg

R3G 400-AQ23 -01

21,7

Seite 37

• • • •

Mass of centrifugal module with support bracket

– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST

11:33

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

40075-2-4013

K3G 400-AQ23 -01

32,3

K3G 400-AQ23 -31

32,3

(2) Centrifugal module with higher protection against corrosion

68

6xØ9

335.6 ±3 265.6 ±2

70

R3G 400-AQ23 -01

Depth of screw max. 25 mm 14xM10 45

8x

220.5±1

6x6 0˚

Ø390 Ø413

Ø455

Ø270.9

Ø282

22.5˚

Ø188

˚

Ø232-2

Ø252±0,3 Ø275

9

125 182

Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

K3G 400-AQ23 -01 / -31 390±3 320±2

15

Tightening torque 3.5±0.5 Nm

o500-1 o375

Ø11 (4x)

M 2 (3 0x1 x) .5

Ø566

Observe the correct mounting position ! Install the support struts only vertically as shown in the view !

o450

Pressure tap

37 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 38

EC centrifugal fan and modules backward curved, Ø 450

subject to alterations

Electr. connection

A

Perm. amb. temp.

M3G 112-IA

Max. current draw(1)

*3G 450

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

1750

1615

2,50

-25..+50

3~ 380-480

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

Pa

A

Air performance measured

1750

1036

1,61

87

1750

1457

2,25

80

A

3

1750

1615

2,50

77

A

4

1750

1524

2,33

80

A

5

1450

571

0,92

82

Suction-side noise levels:

A

6

1450

812

1,28

75

LWA as per ISO 13347,

A

7

1450

906

1,42

73

LpA measured at 1 m distance

A

8

1450

810

1,27

76

A

9

1155

306

0,56

76

A

10

1155

427

0,73

69

A

11

1155

462

0,77

67

A

12

1155

411

0,70

69

2,8

accidental contact

2,4

8

to fan axis

2,0

500

The acoustic values given are

7

2

1,6

400

only valid under the measurment conditions listed and may vary depending on the

1,2

12

300

installation situation.

6

11

0,8

With any deviation to the stan-

200

dard setup, the specific values

10

have to be checked and reviewed once installed or fitted!

0,4

100

For detailed information

psf

9 0

qV

38

1000

2000

LWA dB(A)

2

with ebm-papst inlet nozzle

3

600

I A

1

without protection against

700

Pe W

A

Installation category A, 4

n rpm A

as per: ISO 5801,

3,2

800

in H2O

Curves

2000

3000

4000

4000

6000

see page 66 ff.

1

5 5000

8000

cfm m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 39

kg

R3G 450-AY86 -01

16,4

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Masse centrifugal fan Centrifugal fan

• • • •

Mass of centrifugal module with support bracket

– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC bzw. 4-20 mA • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

45075-2-4013

K3G 450-AY86 -02

31,9

K3G 450-AY86 -32

31,9

(2) Centrifugal module with higher protection against corrosion

355 ±3 295 ±2

60

6xØ9

R3G 450-AY86 -01

Depth of screw 12-16 mm

76

6xM10

202±1

Ø430 Ø480

Ø303.4

Ø 317 Ø 505

Ø 138



6x6

Ø 232±0.3

140 204

Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

417±3 357±2

o630-1 o551

15

Tightening torque 3.5±0.5 Nm

Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)

Ø505

K3G 450-AY86 -02 / -32

Ø 252±0.5

9

5

. 0x1 M2 3x) (

o580

Pressure tap

39 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 40

EC centrifugal fan and modules backward curved, Ø 450

Perm. amb. temp.

Electr. connection

M3G 150-FF

Max. current draw(1)

*3G 450

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

2040

2730

4,20

-25..+60

3~ 380-480

A

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

subject to alterations

Pa

1200

4,8 in H2O

Curves A

Air performance measured

2040

1773

2,71

92

2

2040

2500

3,80

83

A

3

2040

2730

4,20

81

A

4

2040

2587

3,96

83

A

5

1695

991

1,52

88

Suction-side noise levels:

A

6

1695

1428

2,17

79

LWA as per ISO 13347,

A

7

1695

1548

2,35

77

LpA measured at 1 m distance

A

8

1695

1450

2,22

79

A

9

1345

495

0,76

83

A

10

1345

713

1,09

74

A

11

1345

774

1,18

72

A

12

1345

725

1,11

74

without protection against

4,0

accidental contact

3,2

800

to fan axis

8

The acoustic values given are 2

7

2,4

600

only valid under the measurment conditions listed and may vary depending on the

12

installation situation.

6

1,6

400

11

With any deviation to the standard setup, the specific values

10

have to be checked and re-

0,8

200

viewed once installed or fitted!

psf

For detailed information 0

qV

40

1000

2000

2000

9 4000

3000

4000

LWA dB(A)

1

Installation category A,

3

I A

A

with ebm-papst inlet nozzle

1000

Pe W

A

as per: ISO 5801,

4

n rpm

6000

5 5000

8000

see page 66 ff.

1 6000

cfm

10000

m3/h

19.05.2011

Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay

Masse centrifugal fan Centrifugal fan

kg

R3G 450-AQ24 -01

22,5

Seite 41

• • • •

Mass of centrifugal module with support bracket

– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST

11:33

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

45075-2-4013

K3G 450-AQ24 -01

38,2

K3G 450-AQ24 -31

38,2

(2) Centrifugal module with higher protection against corrosion

76

6xØ9

357 ±3 287.2 ±2

70

R3G 450-AQ24 -01

Depth of screw max. 25 mm 14xM10

6x6



Ø430 Ø480

Ø303.4

Ø505

Ø317

22.5˚

Ø188

˚

45

8x

220.5±1

Ø232-2

Ø252±0,3 Ø275

9

140 204

Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

K3G 450-AQ24 -01 / -31 419±3 349±2

15

Tightening torque 3.5±0.5 Nm

o630-1 o551

Ø11 (8x)

M 2 (3 0x1 x) .5

Ø566

Observe the correct mounting position ! Install the support struts only vertically as shown in the view !

o580

Pressure tap

41 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 42

EC centrifugal fan and modules backward curved, Ø 450

Electr. connection

VAC

Hz

rpm

W

A

°C

p. 64

50/60

2750

5370

8,30

-25..+40

3~ 380-480

A

subject to alterations

Perm. amb. temp.

M3G 150-IF

Max. current draw(1)

*3G 450

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

Pa

2000

8,0 in H2O

Curves A

Air performance measured

2750

3105

4,79

100

2

2750

4841

7,47

90

A

3

2750

5370

8,30

89

A

4

2750

5060

7,80

93

A

5

2280

1769

2,73

96

Suction-side noise levels:

A

6

2280

2759

4,26

86

LWA as per ISO 13347,

A

7

2280

3058

4,70

85

LpA measured at 1 m distance

A

8

2280

2884

4,44

89

A

9

1815

893

1,38

91

A

10

1815

1392

2,15

81

A

11

1815

1543

2,37

80

A

12

1815

1455

2,24

84

without protection against

6,4

accidental contact

to fan axis

8

4,8

1200

The acoustic values given are

7

2

only valid under the measurment conditions listed and may vary depending on the

3,2

800

12

installation situation.

6 11

With any deviation to the standard setup, the specific values

1,6

10

400

have to be checked and reviewed once installed or fitted! For detailed information

psf

9 0

qV

42

1000

2000

2000

4000

LWA dB(A)

1

Installation category A,

3

I A

A

with ebm-papst inlet nozzle

1600

Pe W

A

as per: ISO 5801,

4

n rpm

3000

4000

6000

5000

8000

5 6000

10000

see page 66 ff.

1 7000

cfm

12000

m3/h

19.05.2011

Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay

Masse centrifugal fan Centrifugal fan

kg

R3G 450-AZ30 -01

31,1

Seite 43

• • • •

Mass of centrifugal module with support bracket

– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST

11:33

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

45075-1-4013

K3G 450-AZ30 -01

52,7

K3G 450-AZ30 -31

52,7

(2) Centrifugal module with higher protection against corrosion

113

406.5±3 293.5±2

Depth of screw max. 20 mm

6xØ9

R3G 450-AZ30 -01

76 6xM10

6x6

Ø430 Ø480

Ø303.4

Ø317 Ø505

Ø188



Tightening torque 3.5±0.5 Nm

Ø280-2

Cable gland M20x1,5(2x)

112 176

9

Ø304±0.5

Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

Cable gland M25x1,5(1x) 469 ±3 355.5 ±2

Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm

o630-1 o520.5

15

Ø11(8x)

K3G 450-AZ30 -01 / -31

o580

Pressure tap

43 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:33

Seite 44

EC centrifugal fan and modules backward curved, Ø 500

subject to alterations

Perm. amb. temp.

Electr. connection

M3G 150-FF

Max. current draw(1)

*3G 500

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

1780

2825

4,30

-25..+60

3~ 380-480

A

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

Pa

in H2O

Curves A

Air performance measured

1780

1985

3,09

94

2

1780

2530

3,90

89

A

3

1780

2825

4,30

83

A

4

1780

2692

4,14

85

A

5

1475

1094

1,70

90

Suction-side noise levels:

A

6

1475

1411

2,18

84

LWA as per ISO 13347,

A

7

1475

1602

2,47

79

LpA measured at 1 m distance

A

8

1475

1484

2,28

80

A

9

1175

553

0,86

85

A

10

1175

714

1,10

80

A

11

1175

810

1,25

74

A

12

1175

750

1,15

75

Installation category A,

4,0

without protection against

3,2

3

8

to fan axis

2,4

600

The acoustic values given are 7

only valid under the measurment conditions listed and may vary depending on the

12

2

1,6

400

installation situation.

11

With any deviation to the stan-

6

dard setup, the specific values have to be checked and re-

0,8

200

10

viewed once installed or fitted!

psf

For detailed information 0

qV

44

1000

2000

2000

4000

LWA dB(A)

1

accidental contact

800

I A

A

with ebm-papst inlet nozzle

1000

Pe W

A

as per: ISO 5801, 4

n rpm

3000

4000

6000

9 5000

8000

5 6000

10000

see page 66 ff.

1 7000

12000

cfm m3/h

19.05.2011

Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay

Masse centrifugal fan Centrifugal fan

kg

R3G 500-AP25 -01

24,6

Seite 45

• • • •

Mass of centrifugal module with support bracket

– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST

11:34

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

64025-2-4013

K3G 500-AP25 -01

40,2

K3G 500-AP25 -31

40,2

(2) Centrifugal module with higher protection against corrosion

75

6xØ9

373.5 ±3 303.5 ±2

70

R3G 500-AP25 -01

Depth of screw max. 25 mm 14xM10

6x6



Ø445 Ø470

Ø566

Ø337.2

Ø352.5

22.5˚

Ø188

˚

45

8x

220.5±1

Ø232-2

Ø252±0,3 Ø275

12

150 220

Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

K3G 500-AP25 -01 / -31 431.5±3 361.5±2

15

Tightening torque 3.5±0.5 Nm

o630-1 o551

Ø11 (8x)

M 2 (3 0x1 x) .5

Ø566

Observe the correct mounting position ! Install the support struts only vertically as shown in the view !

o580

Pressure tap

45 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 46

EC centrifugal fan and modules backward curved, Ø 500

Electr. connection

A

Perm. amb. temp.

M3G 150-IF

Max. current draw(1)

*3G 500

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

2200

5500

8,40

-25..+45

3~ 380-480

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

subject to alterations

Pa

A

Air performance measured

2200

3725

5,82

100

2200

4944

7,64

94

A

3

2200

5500

8,40

89

A

4

2200

5148

7,95

90

A

5

1825

2039

3,19

95

Suction-side noise levels:

A

6

1825

2736

4,23

90

LWA as per ISO 13347,

A

7

1825

3052

4,70

84

LpA measured at 1 m distance

A

8

1825

2830

4,37

86

A

9

1465

1055

1,65

91

A

10

1465

1416

2,19

85

A

11

1465

1578

2,43

80

A

12

1465

1464

2,26

81

5,6

accidental contact

4,8

1200

8

to fan axis

4,0

1000

The acoustic values given are

7

only valid under the measur-

3,2

800

ment conditions listed and

2 12

may vary depending on the installation situation.

2,4

600

11 6

1,6

With any deviation to the stan-

400

dard setup, the specific values 10

have to be checked and reviewed once installed or fitted!

0,8

200

psf

For detailed information 0

qV

46

2000

2000

4000

LWA dB(A)

2

without protection against

3

I A

1

with ebm-papst inlet nozzle

1400

Pe W

A

Installation category A,

4

n rpm A

as per: ISO 5801,

6,4

1600

in H2O

Curves

4000

6000

8000

9 6000

5

10000

12000

see page 66 ff.

1 8000

14000

cfm m3/h

19.05.2011

Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay

Masse centrifugal fan Centrifugal fan

kg

R3G 500-AQ33 -01

33,2

Seite 47

• • • •

Mass of centrifugal module with support bracket

– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST

11:34

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

64025-2-4013

K3G 500-AQ33 -01

55,9

K3G 500-AQ33 -31

55,9

(2) Centrifugal module with higher protection against corrosion

450.5±3 337.5±2

113

Depth of screw max. 20 mm

6xØ9

R3G 500-AQ33 -01

75 6xM10

298.5±1

Ø445 Ø470

Ø337

Ø352.5 Ø566

Ø188



6x6

Ø280-2

Cable gland M20x1,5(2x)

150 220.5

12

Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm

Ø304±0.5

Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

Cable gland M25x1,5(1x) 510 ±3 396.5 ±2

Tightening torque 3.5±0.5 Nm

o630-1 o520.5

15

Ø11(8x)

K3G 500-AQ33 -01 / -31

o580

Pressure tap

47 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 48

EC centrifugal fan and modules backward curved, Ø 560

subject to alterations

Electr. connection

A

Perm. amb. temp.

M3G 150-IF

Max. current draw(1)

*3G 560

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

1500

3000

4,60

-25..+50

3~ 380-480

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

Pa

in H2O

Curves A

Air performance measured

1500

1952

2,98

90

2

1500

2481

3,77

86

A

3

1500

3000

4,60

80

A

4

1500

2754

4,18

83

A

5

1250

1101

1,68

86

Suction-side noise levels:

A

6

1250

1420

2,16

82

LWA as per ISO 13347,

A

7

1250

1712

2,60

76

LpA measured at 1 m distance

A

8

1250

1560

2,37

78

A

9

1000

564

0,86

81

A

10

1000

727

1,10

77

A

11

1000

876

1,33

71

A

12

1000

799

1,21

74

4,0

accidental contact

3

to fan axis

2,4

8

600

The acoustic values given are only valid under the measurment conditions listed and

7

may vary depending on the 12

1,6

400

installation situation. 2 11

With any deviation to the standard setup, the specific values

6

have to be checked and re-

0,8

200

viewed once installed or fitted!

10

For detailed information

psf

9 0

qV

48

2000

2000

4000

4000

6000

10000

8000

12000

see page 66 ff.

1

5 6000

8000

LWA dB(A)

1

without protection against

3,2

800

I A

A

with ebm-papst inlet nozzle 4

Pe W

A

as per: ISO 5801, Installation category A,

1000

n rpm

14000

cfm m3/h

19.05.2011

Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay

Masse centrifugal fan Centrifugal fan

kg

R3G 560-AP23 -01

30,5

Seite 49

• • • •

Mass of centrifugal module with support bracket

– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST

11:34

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

64030-2-4013

K3G 560-AP23 -01

56,1

K3G 560-AP23 -31

56,1

(2) Centrifugal module with higher protection against corrosion

82

6xØ9

422 ±3 352 ±2

70

R3G 560-AP23 -01

Depth of screw max. 25 mm 14xM10

6x6



Ø490 Ø515

Ø385

Ø636

Ø395

22.5˚

Ø188

˚

45

8x

250.5±1

Ø232-2

Ø252±0,3 Ø275

16

160 239

Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

K3G 560-AP23 -01 / -31 483±3 413±2

15

Tightening torque 3.5±0.5 Nm

o800-1 o555

Ø11 (8x)

M 2 (3 0x1 x) .5

Ø566

Observe the correct mounting position ! Install the support struts only vertically as shown in the view !

o750

Pressure tap

49 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 50

EC centrifugal fan and modules backward curved, Ø 560

Perm. amb. temp.

Electr. connection

M3G 150-NA

Max. current draw(1)

*3G 560

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

1750

4700

7,30

-25..+40

3~ 380-480

A

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

subject to alterations

Pa

1400

in H2O

Curves A

Air performance measured

1750

3032

4,77

97

2

1750

3929

6,10

91

A

3

1750

4700

7,30

84

A

4

1750

4366

6,71

86

A

5

1450

1675

2,64

93

Suction-side noise levels:

A

6

1450

2171

3,37

87

LWA as per ISO 13347,

A

7

1450

2602

4,01

80

LpA measured at 1 m distance

A

8

1450

2432

3,74

82

A

9

1150

836

1,32

88

A

10

1150

1083

1,68

82

A

11

1150

1298

2,00

75

A

12

1150

1213

1,87

76

4,8

without protection against

4,0

accidental contact

3

to fan axis

3,2

8

800

The acoustic values given are only valid under the measur-

7

ment conditions listed and

2,4

600

may vary depending on the 12

installation situation.

2 11

1,6

400

With any deviation to the stan6

dard setup, the specific values have to be checked and re-

10

0,8

200

viewed once installed or fitted! For detailed information

psf

9 0

qV

50

2000

4000

LWA dB(A)

1

with ebm-papst inlet nozzle

1000

I A

A

Installation category A,

1200

Pe W

A

as per: ISO 5801,

4

n rpm

4000

6000

8000

cfm

8000

12000

see page 66 ff.

1

5

16000

m3/h

19.05.2011

Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay

Masse centrifugal fan Centrifugal fan

kg

R3G 560-AQ04 -01

40,0

Seite 51

• • • •

Mass of centrifugal module with support bracket

– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST

11:34

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with support bracket

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

Inlet nozzle with one pressure tap

Centrifugal module w. support bracket

kg

Centrifugal module w. supp. bracket (2)

kg

64030-2-4013

K3G 560-AQ04 -01

69,7

K3G 560-AQ04 -31

69,7

(2) Centrifugal module with higher protection against corrosion

505±3 392±2

113

Depth of screw max. 20 mm

6xØ9

R3G 560-AQ04 -01

82 6xM10

333±1

Ø490 Ø515

Ø385

Ø395 Ø636

Ø188



6x6

Ø280-2

Cable gland M20x1,5(2x)

160 239

16

Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm

Ø304±0.5

Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

Cable gland M25x1,5(1x) 566 ±3 453 ±2

Tightening torque 3.5±0.5 Nm

o800-1 o570

15

Ø11(8x)

K3G 560-AQ04 -01 / -31

o750

Pressure tap

51 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 52

EC centrifugal fan and modules backward curved, Ø 630

subject to alterations

Perm. amb. temp.

Electr. connection

M3G 200-HF

Max. current draw(1)

*3G 630

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support structure: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

1450

6140

9,90

-25..+40

3~ 380-480

A

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

Pa

1200

4,8 in H2O

Curves A

Air performance measured

1450

4116

6,75

95

2

1450

5426

8,70

88

A

3

1450

6140

9,90

84

A

4

1450

4956

7,95

87

A

5

1200

2314

3,79

90

Suction-side noise levels:

A

6

1200

3050

4,89

84

LWA as per ISO 13347,

A

7

1200

3450

5,54

80

LpA measured at 1 m distance

A

8

1200

2792

4,48

83

A

9

960

1185

1,94

86

A

10

960

1562

2,50

79

A

11

960

1766

2,83

75

A

12

960

1429

2,29

78

with ebm-papst inlet nozzle

4,0

accidental contact 3

8

LWA dB(A)

1

Installation category A,

3,2

800

I A

A

without protection against

1000

Pe W

A

as per: ISO 5801, 4

n rpm

to fan axis 7

600

2,4

The acoustic values given are only valid under the measurment conditions listed and 12

installation situation.

11

1,6

400

may vary depending on the

2

6

With any deviation to the standard setup, the specific values have to be checked and re-

10

0,8

200

viewed once installed or fitted! For detailed information

psf

9 0

qV

52

2000

4000

4000

8000

6000

8000

12000

10000

16000

see page 66 ff.

1

5 12000

cfm

20000

m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

11:34

Seite 53

Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay

Masse centrifugal fan kg

R3G 630-AQ01 -01

61,0

Inlet nozzle with one pressure tap

Centrifugal module with support structure

64040-2-4013

K3G 630-AQ01 -01

533±3 420±2

113

R3G 630-AQ01 -01

6xØ10.5

Centrifugal fan

• • • •

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

Mass of centrifugal module with supporting construction

– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST applied for

19.05.2011

kg 105,0

Depth of screw max. 20 mm 98.5

Tightening torque 3.5±0.5 Nm Ø600 Ø634

Ø436.8 (Ø427)

Ø325

Ø444 Ø716

8xM10

8x45˚

Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm

224 318

Ø280-2 304 ±0.5

12

Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

Cable gland M20x1,5(2x) Cable gland M25x1,5(1x)

o760 -10

B-B

400±3

40

433 ±2

30

K3G 630-AQ01 -01

15

20

Observe the correct mounting position ! Install only as shown in the view !

813 ±2

Ø11(8x)

o660 ±1

B

B

10.5 710 ±2 760 ±2

540 630 ±2 670 ±5

80 ±2

53 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 54

EC centrifugal fan and modules backward curved, Ø 710

subject to alterations

Perm. amb. temp.

Electr. connection

M3G 200-LA

Max. current draw(1)

*3G 710

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support structure: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

1200

6240

10,00

-25..+40

3~ 380-480

A

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

Pa

in H2O

Curves A

Air performance measured

1200

4060

6,70

96

2

1200

5561

8,94

89

A

3

1200

6240

10,00

83

A

4

1200

4999

8,12

85

A

5

1000

2332

3,85

92

Suction-side noise levels:

A

6

1000

3202

5,15

85

LWA as per ISO 13347,

A

7

1000

3590

5,73

79

LpA measured at 1 m distance

A

8

1000

2872

4,67

81

A

9

790

1150

1,90

87

A

10

790

1579

2,54

80

A

11

790

1770

2,83

74

A

12

790

1416

2,30

76

4,0

without protection against

3,2

3

8

to fan axis

2,4

600

The acoustic values given are

7

only valid under the measurment conditions listed and may vary depending on the

2

12

installation situation.

1,6

400

11 6

With any deviation to the stan-

0,8

dard setup, the specific values

200

have to be checked and re-

10

viewed once installed or fitted!

psf

For detailed information 0

qV

54

2000

4000

4000

8000

LWA dB(A)

1

accidental contact

800

I A

A

with ebm-papst inlet nozzle

4

Pe W

A

as per: ISO 5801, Installation category A,

1000

n rpm

6000

8000

12000

9 10000

16000

12000

20000

see page 66 ff.

1

5 14000

24000

cfm m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

11:34

Seite 55

Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay

Masse centrifugal fan Centrifugal fan

kg

R3G 710-AQ01 -01

73,0

Inlet nozzle with one pressure tap

Centrifugal module with support structure

71075-2-4013

K3G 710-AQ01 -01

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

kg 130,0

594±3 481±2

113

Depth of screw max. 20 mm 6xØ9

R3G 710-AQ01 -01

• • • •

Mass of centrifugal module with supporting construction

– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST applied for

19.05.2011

117

Tightening torque 3.5±0.5 Nm Ø700 Ø720

Ø492.6 (Ø470.3)

Ø325

Ø501 Ø808

8xM10

8x45˚

Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm

250 354

Ø280-2 304 ±0.5

15

Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

Cable gland M20x1,5(2x) Cable gland M25x1,5(1x)

o960 -10

B-B

450±3

40

543 ±2

30

K3G 710-AQ01 -01

15

25

Observe the correct mounting position ! Install only as shown in the view !

1023 ±2

Ø11(8x)

o750 ±1

B

B

10.5 910 ±2 960 ±2

560 630 ±2 680 ±5

95 ±2

55 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 56

EC centrifugal fan and modules backward curved, Ø 800

subject to alterations

Perm. amb. temp.

Electr. connection

M3G 200-QA

Max. current draw(1)

*3G 800

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support structure: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

960

5800

9,40

-25..+40

3~ 380-480

A

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

n rpm

Pa

A

Air performance measured

960

3763

6,21

91

2

960

5067

8,20

85

A

3

960

5800

9,40

79

A

4

960

5306

8,53

81

A

5

800

2193

3,62

87

Suction-side noise levels:

A

6

800

2994

4,84

81

LWA as per ISO 13347,

A

7

800

3413

5,50

75

LpA measured at 1 m distance

A

8

800

3107

4,99

77

A

9

630

1071

1,77

82

A

10

630

1462

2,36

76

A

11

630

1667

2,69

70

A

12

630

1517

2,44

72

without protection against 2,8

accidental contact

2,4

3

600

8

to fan axis

2,0

500

7

The acoustic values given are only valid under the measur-

1,6

400

ment conditions listed and 2

12

may vary depending on the installation situation.

1,2

300

11 6

With any deviation to the stan-

0,8

200

dard setup, the specific values have to be checked and re-

10

viewed once installed or fitted!

0,4

100

For detailed information

psf

9 0

qV

56

LWA dB(A)

1

with ebm-papst inlet nozzle

700

I A

A

Installation category A,

4

Pe W

A

as per: ISO 5801,

3,2

800

in H2O

Curves

4000

5000

8000

10000

15000

12000

20000

25000

see page 66 ff.

1

5 16000

cfm

30000

m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

11:34

Seite 57

Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay

Masse centrifugal fan Centrifugal fan

kg

R3G 800-AQ03 -01

97,0

Inlet nozzle with one pressure tap

Centrifugal module with support structure

80075-2-4013

K3G 800-AQ03 -01

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

kg 158,0

656±3 543±2

113

Depth of screw max. 20 mm 6xØ9

R3G 800-AQ03 -01

• • • •

Mass of centrifugal module with supporting construction

– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST applied for

19.05.2011

131

Tightening torque 3.5±0.5 Nm Ø700 Ø720

Ø555.3 (Ø529.7)

Ø325

Ø565 Ø909

8xM10

8x45˚

Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm

280 396

Ø280-2 304 ±0.5

20

Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

Cable gland M20x1,5(2x) Cable gland M25x1,5(1x)

o960 -10

B-B

502±3

40

543 ±2

30

K3G 800-AQ03 -01

15

25

Observe the correct mounting position ! Install only as shown in the view !

1023 ±2

Ø11(8x)

o750 ±1

B

B

10.5 910 ±2 960 ±2

700 840 ±2 890 ±5

87±2

57 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 58

EC centrifugal fan and modules backward curved, Ø 900

subject to alterations

Electr. connection

A

Perm. amb. temp.

M3G 200-QA

Max. current draw(1)

*3G 900

Max. input power(1)

Motor

Speed/rpm(1)

Type

Frequency

Nominal data

Nominal voltage range

Curve

– Material: Support structure: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings

VAC

Hz

rpm

W

A

°C

p. 64

50/60

800

5950

9,50

-25..+40

3~ 380-480

L5)

(1) Nominal data in operating point with maximum load and 400 VAC

n rpm

Pa

A

Air performance measured

800

3732

6,14

91

2

800

5512

8,86

83

A

3

800

5950

9,50

78

A

4

800

4991

8,02

79

A

5

665

2129

3,50

87

Suction-side noise levels:

A

6

665

3144

5,05

79

LWA as per ISO 13347,

A

7

665

3397

5,42

74

LpA measured at 1 m distance

A

8

665

2847

4,58

75

A

9

530

1078

1,77

82

A

10

530

1591

2,56

74

A

11

530

1720

2,74

69

A

12

530

1441

2,32

70

with ebm-papst inlet nozzle

2,4

accidental contact

2,0

3

500

8

LWA dB(A)

1

without protection against

600

I A

A

Installation category A,

4

Pe W

A

as per: ISO 5801,

2,8

700

in H2O

Curves

400

1,6

to fan axis The acoustic values given are

7

only valid under the measur2 1,2

300

ment conditions listed and

12

may vary depending on the installation situation. 11

6

With any deviation to the stan-

0,8

200

dard setup, the specific values 10

have to be checked and reviewed once installed or fitted!

0,4

100

psf

For detailed information 0

qV

58

5000

5000

10000

10000

15000

20000

9 15000

5

25000

30000

see page 66 ff.

1 20000

35000

cfm m3/h

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

Seite 59

Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay

Masse centrifugal fan Centrifugal fan

kg 107,0

R3G 900-AQ01 -01

113

Inlet nozzle with one pressure tap

Centrifugal module with support structure

90075-2-4013

K3G 900-AQ01 -01

Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating

kg 194,0

596±3 483±2

Depth of screw max. 20 mm 6xØ9

R3G 900-AQ01 -01

• • • •

Mass of centrifugal module with supporting construction

– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST applied for

11:34

148

Tightening torque 3.5±0.5 Nm Ø850 Ø900

Ø624.7 (Ø595.9)

Ø325

Ø635 Ø1010

8xM10

8x45˚

Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm 15

Cable gland M20x1,5(2x) Cable gland M25x1,5(1x) Ø11(12x)

o950 ±1 o400 ±1

565 ±3

o1180 -10

B-B

Ø280-2 304 ±0.5

Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

40

660 ±2

30

K3G 900-AQ01 -01

15

30

Observe the correct mounting position ! Install only as shown in the view !

1250 ±2

310 439

B

B

10.5 1130 ±2 1180 ±2

640 840 ±2 900 ±5

97±2

59 Guard grille p. 60

Inlet nozzle p. 60

Electr. connection p. 64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 60

Accessories Vers. 1

- Material: sheet steel, plastic coated, silver-metallic gloss

Vers. 2

a

Ød

Ød

a

e

b

e

b

Air intake guard grilles for backward curved centrifugal fans (according to EN 294) Part no.

Size

Vers.

a

b

d

e

Strut pitch

78129-2-4039

250

1

260

4,5

191

2,8

4 x 90°

78130-2-4039

280

1

280

4,5

229

2,8

4 x 90°

78131-2-4039

310

1

325

4,5

248

2,8

4 x 90°

78132-2-4039

355

1

345

4,5

305

2,8

4 x 90°

78133-2-4039

400

2

390

8,5

343

3,8

3 x 120°

78134-2-4039

450

2

430

8,5

381

3,8

3 x 120°

78139-2-4039

500

2

445

8,5

410

3,8

3 x 120°

78137-2-4039

560

2

490

8,5

430

3,8

3 x 120°

subject to alterations

Vers. 1

- Material: galvanised sheet steel

Vers. 2

6x6



˚

90

4x

Inlet nozzles without measuring device for backward curved centrifugal fans Part no.

Size

Vers.

25070-2-4013

250

1

page 11

28070-2-4013

280

1

page 15

31570-2-4013

310

1

page 21

35670-2-4013

355

1

page 29

40070-2-4013

400

2

page 35

45070-2-4013

450

2

page 39

63072-2-4013

500

2

page 45

63071-2-4013

560

2

page 49

63070-2-4013

630

2

page 53

71070-2-4013

710

2

page 55

80070-2-4013

800

2

page 57

90070-2-4013

900

2

page 59

subject to alterations

60

For dimensions, see

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 61

Accessories Effects of installation space

Curve

When mounting our product in a rectangular box, air performance might be reduced.

1,00

B

Formula: dh = 2 x B x H / (B + H) B = Width of box

0,93

0,94

0,95

0,96

dh = Hydraulic diameter

0,92

Correction factor for air flow

D

H

0,5xD

D

0,97

0,98

0,99

D

1,4

1,6

1,8

2,0

2,2

2,4

2,6

2,8

Hydraulic diameter dh/D

H = Height of box D = Outer diameter of the fan

Air flow determination:

The differential pressure approach compares the static pressure before the inlet nozzle with the static pressure inside the inlet nozzle. Air flow can be calculated on the basis of the differential pressure (difference in pressure of the static pressures) in keeping with the following equation: qV = k . ∆p

0,5xD

qV in [m3/h] and ∆p in [Pa]

D

If constant air flow is to be controlled to, then the nozzle pressure has to be kept constant: ∆p = qV2 : k2

∆p

k takes into account the specific nozzle characteristics. Differences in static pressure are measured in 1/4 measuring point(s) along the circumference of the inlet nozzle. Connection on the customer side is acomplished via a pre-mounted T tube connector. This tube connector is suited for pneumatic hoses with an internal diameter of 4 mm.

Inlet nozzles with measuring device to determine air flow for backward curved centrifugal fans Part no.

Part no.

Size

k-value

For dimensions, see

25075-2-4013(1) / 25080-2-4013(2)

250

70

page 11

28075-2-4013(1) / 28080-2-4013(2)

280

93

page 15

(2)

310

116

page 21

35675-2-4013(1) / 35680-2-4013(2)

355

148

page 29

40075-2-4013(1) / 40080-2-4013(2)

400

188

page 35

(2)

450

240

page 39

64025-2-4013(1) / 64002-2-4013(2)

500

281

page 45

64030-2-4013(1) / 64001-2-4013(2)

560

348

page 49

(2)

630

438

page 53

71075-2-4013(1) / 71080-2-4013(2)

710

545

page 55

80075-2-4013(1) / 80080-2-4013(2)

800

695

page 57

900

page 59

(1)

31575-2-4013

(1)

45075-2-4013

(1)

64040-2-4013

(1)

90075-2-4013

/ 31580-2-4013

/ 45080-2-4013

/ 64000-2-4013

(2)

/ 90080-2-4013

subject to alterations

900 (1)

with one pressure tap

(2)

with piezometer ring (4 pressure taps connected by tubing)

61

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 62

Electrical connections EC

K1) Notes on various control possibilities and their applications Umin = 15 V Imax = 10 mA

Mains 50/60 Hz

L black N blue PE green/yellow

+ -

NC white1

+ white2 Voltage output red +10 V max. 1.1 mA

U

PWM

-

10 K 12 V

Alarm relay: Break for failure (2 A, 250 VAC, AC1)

Lin/PWM control input yellow 0-10 VDC / PWM 1 µF

GND blue Speed setting PWM 1 - 10 kHz

Speed setting with variable resistance

Full speed

Speed setting 1 V - 10 V

100% PWM -> n=max approx. 10% PWM -> n=min < 10% PWM -> n=0

10 V -> n=max approx. 1 V -> n=min < 1 V -> n=0

start up at > 14 %

start up at > 1.4 V

Customer circuit

Connection

+10 V

0-10 V PWM

GND

green/yellow white1

COM

blue

Line 2 NC

N

black

PE

L

Line 1

Fan

white2

red

yellow

blue

Line

Connection Colour Assignment / function

Line

1

L

black

Mains 50/60 Hz, phase

2

N

blue

Mains 50/60 Hz, neutral

0-10 V / PWM yellow

Control input (Impedance 100 kΩ)

PE

green/yel

Protective earth

GND

GND

NC

white1

Alarm relay, break for failure

COM

white2

Alarm relay, COMMON

62

Connection Colour Assignment / function +10 V

red blue

Voltage output +10 V max. 1.1 mA

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 63

L6)

PE

L2

L1

L3

KL1 NC

COM

NO

OUT

GND

+10 V

0-10 V PWM

+20 V

KL2 4-20 mA

GND

0-10 V PWM

RS B

RS A

RS B

RS A

KL3

Connector Connection Assignment / function

Connector Connection Assignment / function

PE

PE

Protective earth

KL3

OUT

Master output 0-10 V max. 3 mA

KL1

L3

Mains; L3

GND

GND

L2

Mains; L2

0-10 V / PWM Control / Actual value input (Impedance 100 kΩ)

L1

Mains; L1

+10 V

NC

Alarm relay, break for failure

COM

Alarm relay, COMMON (2A, 250 VAC, AC1)

NO

Alarm relay, make for failure

KL2

Supply for external potentiometer, 10 VDC (+10 %) max. 10 mA

+20 V

Supply for external sensor, 20 VDC (±20 %) max. 50 mA

4-20 mA

Control / Actual value input

0-10 V / PWM Control / Actual value input GND

GND

RSB

RS485 interface for MODBUS RTU; RS B

RSA

RS485 interface for MODBUS RTU; RS A

RSB

RS485 interface for MODBUS RTU; RS B

RSA

RS485 interface for MODBUS RTU; RS A

L7)

PE

L

N

KL1 NC

COM

NO

OUT

GND

+10 V

0-10 V PWM

+20 V

KL2 4-20 mA

GND

0-10 V PWM

RS B

RS A

RS B

RS A

KL3

Connector Connection Assignment / function

Connector Connection Assignment / function

PE

PE

Protective earth

KL3

OUT

Master output 0-10 V max. 3 mA

KL1

N

Mains 50/60 Hz. neutral

GND

GND

L

Mains 50/60 Hz, phase

0-10 V / PWM Control / Actual value input (Impedance 100 kΩ)

NC

Alarm relay, break for failure

+10 V

COM

Alarm relay, COMMON (2A, 250 VAC, AC1)

NO

Alarm relay, make for failure

KL2

Supply for external potentiometer, 10 VDC (+10 %) max. 10 mA

+20 V

Supply for external sensor, 20 VDC (±20 %) max. 50 mA

4-20 mA

Control / Actual value input

0-10 V / PWM Control / Actual value input GND

GND

RSB

RS485 interface for MODBUS RTU; RS B

RSA

RS485 interface for MODBUS RTU; RS A

RSB

RS485 interface for MODBUS RTU; RS B

RSA

RS485 interface for MODBUS RTU; RS A

63

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 64

Electrical connections EC

L5)

L3

Aout Din1

L2

Ain2 I Ain1 I

L1

+20 V +10 V

PE

Ain2 U Ain1 U

KL1

NC

GND GND

COM

Din3 RS B

NO

Din2

KL2

RS A

KL3

Connector Connection Assignment / function

Connector Connection Assignment / function

KL1

KL3

L3

Mains; L3

L2

Mains; L2

L1

Mains; L1

PE

PE

Protective earth

KL2

NC

Alarm relay, break for failure

COM

Alarm relay, COMMON (2A, 250 VAC, AC1)

NO

Alarm relay, make for failure

Din1

Digital input 1 (enabling / disabling of electronics),, Enabling: Pin open or applied voltage 5...50 VDC Disabling: Bridge to GND or applied voltage < 1 VDC

Ain1 I

Analogue set value input, 4-20 mA (impedance 100 Ω),

+10 V

Supply for external potentiometer,

only to be used as alternative to terminal Ain1 U 10 VDC (±3 %) max. 10 mA Ain1U

Analogue set value input, 0-10 V (impedance 100 kΩ),

GND

GND

RSB

RS485 interface for MODBUS RTU; RS B

RSA

RS485 interface for MODBUS RTU; RS A

Aout

Analogue output 0-10 V max. 5 mA, reading of current

only to be used as alternative to terminal Ain1 I

motor speed / current motor control factor Ain2 I

Analog. actual value input, 4-20mA (impedance 100Ω),

+20 V

Supply for external sensor,

only to be used as alternative to terminal Ain2 U 20 VDC (+25 % / -10%) max. 40 mA Ain2 U

Analog. actual value input, 0-10 V (impedance 100 kΩ),

GND

GND

Din3

Digital input 3 (switch Normal / Inverse),

only to be used as alternative to terminal Ain2 I

The preset effective direction of the integrated controller can be selected via BUS or via digital input Normal/Inverse. Normal: Pin open or applied voltage 5...50 VDC Inverse: Bridge to GND or applied voltage < 1 VDC Din2

Digital input 2 (switch Day / Night), The preset set of parameters can be selected via BUS or via digital input Day/Night. Day: Pin open or applied voltage 5...50 VDC Night: Bridge to GND or applied voltage < 1 VDC

64

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 65

L9) Aout Din1

N

Ain2 I Ain1 I

L1

+20 V +10 V

PE

Ain2 U Ain1 U

KL1

NC

GND GND

COM

Din3 RS B

NO

Din2

KL2

RS A

KL3

Connector Connection Assignment / function

Connector Connection Assignment / function

KL1

KL3

N

Mains; neutral

L1

Mains; L1

PE

PE

Protective earth

KL2

NC

Alarm relay, break for failure

COM

Alarm relay, COMMON (2A, 250 VAC, AC1)

NO

Alarm relay, make for failure

Din1

Digital input 1 (enabling / disabling of electronics),, Enabling: Pin open or applied voltage 5...50 VDC Disabling: Bridge to GND or applied voltage < 1 VDC

Ain1 I

Analogue set value input, 4-20 mA (impedance 100 Ω),

+10 V

Supply for external potentiometer,

only to be used as alternative to terminal Ain1 U 10 VDC (±3 %) max. 10 mA Ain1U

Analogue set value input, 0-10 V (impedance 100 kΩ),

GND

GND

RSB

RS485 interface for MODBUS RTU; RS B

RSA

RS485 interface for MODBUS RTU; RS A

Aout

Analogue output 0-10 V max. 5 mA, reading of current

only to be used as alternative to terminal Ain1 I

motor speed / current motor control factor Ain2 I

Analog. actual value input, 4-20mA (impedance 100Ω),

+20 V

Supply for external sensor,

only to be used as alternative to terminal Ain2 U 20 VDC (+25 % / -10%) max. 40 mA Ain2 U

Analog. actual value input, 0-10 V (impedance 100 kΩ),

GND

GND

Din3

Digital input 3 (switch Normal / Inverse),

only to be used as alternative to terminal Ain2 I

The preset effective direction of the integrated controller can be selected via BUS or via digital input Normal/Inverse. Normal: Pin open or applied voltage 5...50 VDC Inverse: Bridge to GND or applied voltage < 1 VDC Din2

Digital input 2 (switch Day / Night), The preset set of parameters can be selected via BUS or via digital input Day/Night. Day: Pin open or applied voltage 5...50 VDC Night: Bridge to GND or applied voltage < 1 VDC

65

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 66

Technical parameters & scope

High standards for all ebm-papst products Here at ebm-papst, we constantly strive to further improve our products in order to be able to offer you the best possible product for your application. Careful monitoring of the market ensures that technical innovations are reflected in the improvements of our products. Based on the technical parameters listed below and the ambience you want our product to operate in, we here at ebm-papst can always work out the best solution for your specific application.

General performance parameters

Service life

Any deviations from the technical data and parameters described here

The service life of ebm-papst products depends on two major factors:

are listed on the product-specific data sheet.

– The service life of the insulation system – The service life of the bearing system

Type of protection

The service life of the insulation system mainly depends on voltage level,

The type of protection is specified in the product-specific data sheets.

temperature and ambient conditions, such as humidity and condensation. The service life of the bearing system depends mainly on the thermal load

Insulation class

on the bearing.

The insulation class is specified in the product-specific data sheets.

The majority of our products use maintenance-free ball bearings for any mounting position possible. As an option, sleeve bearings can be

Mounting position

used, which is indicated on the product-specific data sheet wherever

The mounting position is specified in the product-specific data sheets.

applicable. The service life L10 of the ball bearings can be taken as approx. 40,000

Condensate discharge holes

operating hours at an ambient temperature of 40 °C, yet this estimate

Information on the condensate discharge holes is provided in the

can vary according to the actual ambient conditions.

product-specific data sheets.

We will gladly provide you with a lifetime calculation taking into account your specific operating conditions.

Mode of operation The mode of operation is specified in the product-specific data sheets.

Motor protection / thermal protection Information on motor protection and thermal protection is provided in the

Protection class

product-specific data sheets.

The protection class is specified in the product-specific data sheets.

Depending on motor type and field of application, the following protective features are realised: – Thermal overload protection (TOP), either in-circuit or external – PTC with electronic diagnostics – Impedance protection – Thermal overload protection (TOP) with electronic diagnostics – Current limitation via electronics If an external TOP is connected, the customer has to make sure to connect a conventional trigger device for switching it off. Products without fitted TOP and without protection against improper use, a motor protection complying with the valid standards has to be installed.

66

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 67

Left: Endurance test room Middle: Shock test Right: Chamber test rig

Mechanical strain / performance parameters

Legal and normative directives

All ebm-papst products are subjected to comprehensive tests complying

The products described in this catalogue are designed, developed and

with the normative specifications. In addition to this, the tests also reflect

produced in keeping with the standards in place for the relevant product

the vast experience and expertise of ebm-papst.

and, if known, the conditions governing the relevant fields of application.

Vibration test

Standards

Vibration tests are carried out in compliance with

Information on standards is provided in the product-specific data sheets.

– Vibration test in operation according to DIN IEC 68, parts 2-6 – Vibration test at standstill according to DIN IEC 68, parts 2-6

EMC Information on EMC standards is provided in the product-specific data

Shock load

sheets.

Shock load tests are carried out in compliance with

Complying with the EMC standards has to be established on the final

– Shock load according to DIN IEC 68, parts 2-27

appliance, as different mounting situations can result in changed EMC properties.

Balancing quality Testing the balancing quality is carried out in compliance with

Leakage current

– Residual imbalance according to DIN ISO 1940

Information on the leakage current is provided in the product-specific

– Standard balancing quality level G 6.3

data sheets.

Should you require a higher balancing quality level for your specific

Measuring is according to IEC 60990.

application, please let us know and specify this when ordering your product.

Approvals In case you require a specific approval for your ebm-papst product

Chemo-physical strain / performance parameters

(VDE, UL, GOST, CCC, CSA, etc.) please let us know.

Should you have questions about chemo-physical strain, please direct

Most of our products can be supplied with the relevant approval.

them to your ebm-papst contact.

Information on existing approvals is provided in the product-specific data sheets.

Fields of application, industries and applications Our products are used in various industries and applications:

Air performance measurements

Ventilation, air-conditioning and refrigeration technology, clean room

All air performance measurements are carried out on suction side and on

technology, automotive and rail technology, medical and laboratory tech-

chamber test beds conforming to the specifications as per ISO 5801 and

nology, electronics, computer and office technology, telecommunications,

DIN 24163. The fans under test are installed in the measuring chamber at

household appliances, heating, machines and plants, drive engineering.

free air intake and exhaust (installation category A) and are operated at

Our products are not designed for use in the aviation and aerospace

nominal voltage, with AC also at nominal frequency, and without any

industry!

additional components such as guard grilles. As required by the standard, the air performance curves correspond to an air density of 1.2 kg/m3.

67

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 68

Room for precision noise measuring

Measurement conditions for air and noise measurement ebm-papst products are measured under the following conditions: – Axial and diagonal fans in direction of rotation “V” in full nozzle and without guard grille – Backward curved centrifugal fans, free-running and with inlet nozzle – Forward curved single and dual inlet centrifugal fans with housing Noise measurements All noise measurements are carried out in low-reflective test rooms with reverberant floor. Thus the ebm-papst acoustic test chambers meet the requirements of precision class 1 according to DIN EN ISO 3745. For noise measurement, the fans being tested are placed in a reverberant wall and operated at nominal voltage (for AC, also at nominal frequency) without additional attachments such as the guard grille. Sound pressure level and sound level All acoustic values are established according to ISO 13347, DIN 45635 and ISO 3744/3745 to accuracy class 2 and given in A-rated form. When the sound pressure level (Lp) is measured, the microphone is on the intake side of the fan being tested, usually at a distance of 1 m on the fan axis. To measure the sound power level (Lw), 10 microphones are distributed over an enveloping surface on the intake side of the fan being tested (see graphic). The sound power level measured can be roughly calculated

1,5d

from the sound pressure level by adding 7 dB.

D

Measuring configuration as per ISO 13347-3 respectively DIN 45635-38: 10 measuring points d≥D h = 1,5d ... 4,5d

h

3d

Measurement area S = 6d2 + 7d (h + 1,5d)

2d

68

11:34

Seite 69

Adding multiple noise sources with the same level

15

19.05.2011

dB

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

pressure level of a fan is approximately 75 dB(A). The level increase measured from the diagram is 9 dB. Thus the overall sound level of the installation can be expected to be 84 dB(A).

10 9

Example: 8 A3G800 axial fans are on a condenser. According to the data sheet, the sound

5

the noise values specified in the data sheet. This is shown in the diagram opposite.

0

The noise characteristics of multiple identical fans can be determined in advance based on

Increase in sound pressure / sound power level

Adding 2 noise sources with the same volume results in a level increase of approx. 3 dB.

1

2

3

4

5

6 7 8 9 10

15

20 25

dB

Adding two noise sources with different levels

3

Number of sources of sound with identical level

4 dB. The level increase can now be read in the diagram as approx. 1.5 dB. This means that the overall sound level of the unit can be expected to be 76.5 dB(A).

2 1,5

ating point and an axial fan A3G710 with 71 dB(A) in a ventilation unit. The level difference is

1

Example: There is an axial fan A3G800 with a sound pressure level of 75 dB(A) at the oper-

0

levels given in the data sheet. This is shown in the diagram opposite.

Increase in sound pressure / sound power level

The acoustic performance of two different fans can be predetermined based on the sound

0

4

8

12

16

20

24

Difference in level with two sources of sound 0 dB

Distance laws

dB

Sound power level is independent of distance to the sound source. In contrast to this, sound -10

pressure level decreases the further away the noise source is. The adjacent diagram shows the decrease in level under far sound field conditions. Far sound field conditions apply when-

decreases by 6 dB. In the near field of the fan, other correlations apply and the decrease in levels can be considerably smaller. The following example only applies to far sound field conditions and can vary strongly depending on the installation effects: With an axial fan A3G300, a sound pressure level of 65 dB(A) was measured at a distance of 1 m. According to the adjacent diagram, at a distance of 20 m we would get a reduction by

-20 -26 -30

vant literature on this complex topic. Per doubling of distance, the level in the far sound field

-40

wavelength to be considered. For more information on far sound field, please consult the rele-

Decrease in sound pressure level

ever the distance between microphone and fan is big when compared to fan diameter and

1

Distance

2

5

10

20

50

100 m

26 dB, i.e. a sound pressure level of 39 dB(A).

69

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

fan agent compact fan agent

19.05.2011

11:34

Seite 70

ebm-papst in Germany

motor specialist motor agent

Germany ebm-papst Mulfingen GmbH & Co. KG

ebm-papst St. Georgen GmbH & Co. KG

ebm-papst Landshut GmbH

Bachmühle 2 D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110 [email protected]

Hermann-Papst-Straße 1 D-78112 St. Georgen Phone +49 7724 81-0 Fax +49 7724 81-1309 [email protected]

Hofmark-Aich-Straße 25 D-84030 Landshut Phone +49 871 707-0 Fax +49 871 707-465 [email protected]

www.ebmpapst.com

www.ebmpapst.com

www.ebmpapst.com

70

Berlin Dipl.-Ing. (TH) Jens Duchow Händelstraße 7 D-16341 Panketal Phone +49 30 944149-62 Fax +49 30 944149-63 [email protected]

Heilbronn / Heidelberg Dipl.-Ing. Mark Gartner Gehrweg 12 D-74199 Unterheinriet Phone +49 7130 404569-1 Fax +49 7130 404569-2 [email protected]

Bielefeld Dipl.-Ing. (FH) Wolf-Jürgen Weber Niehausweg 13 D-33739 Bielefeld Phone +49 5206 91732-31 Fax +49 5206 91732-35 [email protected]

Kassel Dipl.-Ing. (FH) Ralph Brück Hoherainstraße 3 b D-35075 Gladenbach Phone +49 6462 4071-10 Fax +49 6462 4071-11 [email protected]

Dortmund Dipl.-Ing. (FH) Hans-Joachim Pundt Auf den Steinern 3 D-59519 Möhnesee-Völlinghausen Phone +49 2925 800-407 Fax +49 2925 800-408 [email protected]

Koblenz Winfried Schaefer Hinter der Kirch 10 D-56767 Uersfeld Phone +49 2657 16-96 Fax +49 2657 16-76 [email protected]

Frankfurt Dipl.-Ing. Christian Kleffmann Dr.-Hermann-Krause-Straße 23 D-63452 Hanau Phone +49 6181 1898-12 Fax +49 6181 1898-13 [email protected]

Munich Dipl.-Wirt.-Ing. (FH) Jens Peter Uhlandstraße 6 D-74427 Fichtenberg Phone +49 7971 260-180 Fax +49 7971 260-221 [email protected]

Halle Dipl.-Ing. (TU) Michael Hanning Lercheneck 4 D-06198 Salzatal / OT Lieskau Phone +49 345 55124-56 Fax +49 345 55124-57 [email protected]

Nuremberg Dipl.-Wirt.-Ing. (FH) Axel Resch Steinsfeldstraße 80 D-74626 Bretzfeld Phone +49 7946 94401-02 Fax +49 7946 94401-03 [email protected]

Hamburg Ingenieurbüro Breuell GmbH Ing. Dirk Kahl Elektroingenieur Grützmühlenweg 40 D-22339 Hamburg Phone +49 40 538092-19 Fax +49 40 538092-84 [email protected]

Offenburg Dipl.-Ing. (FH) Ralf Braun Hubeneck 21 D-77704 Oberkirch Phone +49 7802 9822-52 Fax +49 7802 9822-53 [email protected] Stuttgart Dipl.-Ing. (FH) Rudi Weinmann Hindenburgstraße 100/1 D-73207 Plochingen Phone +49 7153 9289-80 Fax +49 7153 9289-81 [email protected]

Ulm M.Sc. Reinhard Sommerreißer Am Silbermannpark 10 D-86161 Augsburg Phone +49 821 6610-7023 Fax +49 821 6610-7024 [email protected]

Distributors Frankfurt R.E.D. Handelsgesellschaft mbH Gutenbergstraße 3 D-63110 Rodgau - Jügesheim Phone +49 6106 841-0 Fax +49 6106 841-111 [email protected] www.red-elektromechanik.de Hamburg Breuell + Hilgenfeldt GmbH Grützmühlenweg 40 D-22339 Hamburg Phone +49 40 538092-20 Fax +49 40 538092-84 [email protected] Munich A. Schweiger GmbH Ohmstraße 1 D-82054 Sauerlach Phone +49 8104 897-0 Fax +49 8104 897-90 [email protected] www.schweiger-gmbh.com (1 to 5 pieces) North Breuell + Hilgenfeldt GmbH Grützmühlenweg 40 D-22339 Hamburg Phone +49 40 538092-20 Fax +49 40 538092-84 [email protected] South HDS Ventilatoren Vertriebs GmbH Glaswiesenstraße 1 D-74677 Dörzbach Phone +49 7937 8033520 Fax +49 7937 8033525 [email protected]

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 71

ebm-papst in Europe

Europe Austria ebm-papst Motoren & Ventilatoren GmbH Straubingstraße 17 A-4030 Linz Phone +43 732 321150-0 Fax +43 732 321150-20 [email protected] www.ebmpapst.at Belarus ebm-papst Bel AgmbH P.O. Box 117 BY-220138 Minsk Phone +375 17 3851556 Fax +375 17 3851556 [email protected] www.ebmpapst.by Belgium ebm-papst Benelux B.V. Sales office Belgium-Luxemburg Romeinsestraat 6/0101 Research Park Haasrode B-3001 Heverlee-Leuven Phone +32 16 396-200 Fax +32 16 396-220 [email protected] www.ebmpapst.be Bulgaria ebm-papst Romania S.R.L. Str. Tarnavei Nr. 20 RO-500327 Brasov Phone +40 268 312-805 Fax +40 268 312-805 [email protected] Croatia ebm-papst Industries Kft. Ezred u. 2. H-1044 Budapest Phone +36 1 8722-190 Fax +36 1 8722-194 [email protected]

Czech Republic / Slovakia ebm-papst CZ s.r.o. Kaštanová 34a CZ-620 00 Brno Phone +420 544 502-411 Fax +420 547 232-622 [email protected] www.ebmpapst.cz Denmark ebm-papst Denmark ApS Vallensbækvej 21 DK-2605 Brøndby Phone +45 43 631111 Fax +45 43 630505 [email protected] www.ebmpapst.dk Estonia ebm-papst Oy, Eesti Filiaal Kesk tee 13 Aaviku küla, Jüri Tehnopark EST-75301 Rae Vald, Harjumaa Phone +372 65569-78 Fax +372 65569-79 www.ebmpapst.ee Finland ebm-papst Oy Puistotie 1 FIN-02760 Espoo Phone +358 9 887022-0 Fax +358 9 887022-13 [email protected] www.ebmpapst.fi France ebm-papst sarl ZI Nord - rue A. Mohler BP 62 F-67212 Obernai Cedex Phone +33 820 326266 Fax +33 3 88673883 [email protected] www.ebmpapst.fr Greece Helcoma Th. Rotas & Co OE Davaki 65 GR-17672 Kallithea-Attiki Phone +30 210 9513-705 Fax +30 210 9513-490 [email protected] www.helcoma.gr

Hungary ebm-papst Industries Kft. Ezred u. 2. H-1044 Budapest Phone +36 1 8722-190 Fax +36 1 8722-194 [email protected] Iceland RJ Engineers Stangarhyl 1a IS-110 Reykjavik Phone +354 567 8030 Fax +354 567 8015 [email protected] www.rj.is Ireland ebm-papst UK Ltd. Chelmsford Business Park GB-Chelmsford Essex CM2 5EZ Phone +44 1245 468555 Fax +44 1245 466336 [email protected] www.ebmpapst.co.uk AuBren Limited Portlaoise Business & Technology Park Mountrath Road IRL-Portlaoise, Co. Laois Phone +353 57 8664343 Fax +353 57 8664346 [email protected] www.aubren.com Italy ebm-papst Srl Via Cornaggia 108 I-22076 Mozzate (Co) Phone +39 0331 836201 Fax +39 0331 821510 [email protected] www.ebmpapst.it Macedonia ebm-papst Industries Kft. Ezred u. 2. H-1044 Budapest Phone +36 1 8722-190 Fax +36 1 8722-194 [email protected]

71

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

fan agent compact fan agent

19.05.2011

11:34

Seite 72

ebm-papst in Europe

motor specialist motor agent

Netherlands ebm-papst Benelux B.V. Engelseweg 127 NL-5705 AC Helmond Phone +31 492 502-900 Fax +31 492 502-950 [email protected] www.ebmpapst.nl

Russia ebm-papst Ural GmbH Posadskaja-Strasse, 23(E), 3 RU-620102 Ekaterinburg Phone +7 343 2338000 Fax +7 343 2337788 [email protected] www.ebmpapst.ur.ru

Switzerland ebm-papst AG Rütisbergstrasse 1 CH-8156 Oberhasli Phone +41 44 73220-70 Fax +41 44 73220-77 [email protected] www.ebmpapst.ch

Norway ebm-papst AS P.B. 173 Holmlia N-1203 Oslo Phone +47 22 763340 Fax +47 22 619173 [email protected] www.ebmpapst.no

ebm-papst Rus GmbH proezd 4529, vladenie 5, stroenie 1 RU-141000 Mytistschi, Oblast Moskau Phone +7 495 9807524 Fax +7 495 5140924 [email protected] www.ebmpapst.ru

Turkey Akantel Elektronik San. Tic. LTD. Sti. Atatürk Organize Sanayi Bölgesi 10007 SK. No.:6 TR-35620 Cigli-Izmir Phone +90 232 3282090 Fax +90 232 3280270 [email protected] www.ebmpapst.com.tr

Poland ebm-papst Polska Sp. z o.o. ul. Annopol 4A PL-03236 Warszawa Phone +48 22 6757819 Fax +48 22 6769587 [email protected] www.ebmpapst.pl Portugal ebm-papst (Portugal), Lda. Centro Empresarial de Alverca Rua de Adarse, Vale D’Ervas Corpo D / Fracção 3 P-2615-178 Alverca do Ribatejo Phone +351 218 394 880 Fax +351 218 394 759 [email protected] www.ebmpapst.pt Romania ebm-papst Romania S.R.L. Str. Tarnavei Nr. 20 RO-500327 Brasov Phone +40 268 312-805 Fax +40 268 312-805 [email protected]

72

Serbia & Montenegro ebm-papst Industries Kft. Ezred u. 2. H-1044 Budapest Phone +36 1 8722-190 Fax +36 1 8722-194 [email protected] Spain ebm-papst Ibérica S.L. Avda. del Sistema Solar, 29 E-28830 San Fernando de Henares (Madrid) Phone +34 91 6780894 Fax +34 91 6781530 [email protected] Sweden ebm-papst AB Äggelundavägen 2 S-17562 Järfälla Phone +46 8 7619400 Fax +46 8 362306 [email protected] www.ebmpapst.se

Ukraine ebm-papst Ukraine LLC Lepse Boulevard, 4, Building 47 UA-03067 Kiev Phone +38 044 2063091 Fax +38 044 2063091 [email protected] www.ebmpapst.ua United Kingdom ebm-papst UK Ltd. Chelmsford Business Park GB-Chelmsford Essex CM2 5EZ Phone +44 1245 468555 Fax +44 1245 466336 [email protected] www.ebmpapst.co.uk ebm-papst Automotive & Drives (UK) Ltd. The Smithy Fidlers Lane GB-East Ilsley, Berkshire RG20 7LG Phone +44 1635 2811-11 Fax +44 1635 2811-61 [email protected] www.ebmpapst-ad.com

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 73

ebm-papst in America and Africa

America Argentina ebm-papst de Argentina S.A. Hernandarias 148 Lomas del Mirador Pcia. de Buenos Aires (1752) Phone +54 11 46576135 Fax +54 11 46572092 [email protected] www.ebmpapst.com.ar Brasil ebm-papst Motores Ventiladores Ltda. Av. José Giorgi, 301 Galpões B6+B7 Condominio Logical Center BR-06707-100 Cotia - São Paulo Phone +55 11 4613-8700 Fax +55 11 3164-8924 [email protected] www.ebmpapst.com.br

USA ebm-papst Inc. P.O. Box 4009 100 Hyde Road USA-Farmington, CT 06034 Phone +1 860 674-1515 Fax +1 860 674-8536 [email protected] www.ebmpapst.us ebm-papst Automotive & Drives, Inc. 3200 Greenfield, Suite 255 USA-Dearborn, MI 48120 Phone +1 313 406-8080 Fax +1 313 406-8081 [email protected] www.ebmpapst-automotive.us

Africa South Africa ebm-papst South Africa (Pty) Ltd. P.O. Box 3124 1119 Yacht Avenue ZA-2040 Honeydew Phone +27 11 794-3434 Fax +27 11 794-5020 [email protected] www.ebmpapst.co.za

Canada ebm-papst Canada Inc. 1800 Ironstone Manor, Unit 2 CDN-Pickering, Ontario, L1W3J9 Phone +1 905 420-3533 Fax +1 905 420-3772 [email protected] www.ebmpapst.ca Mexico ebm Industrial S.de R.L. de C.V. Paseo de Tamarindos 400-A-5to Piso Col. Bosques de las Lomas MEX-Mexico 05120, D.F. Phone +52 55 3300-5144 Fax +52 55 3300-5243 [email protected] www.ebmpapst.com.mx

73

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

fan agent compact fan agent

19.05.2011

11:34

Seite 74

ebm-papst in Asia and Australia

motor specialist motor agent

Asia China ebm-papst Ventilator (Shanghai) Co., Ltd. No. 418, Huajing Road WaiGaoQiao Free Trade Zone No. 2001, Yang Gao (N) Road VRC-200131 Shanghai, P.R. of China Phone +86 21 5046-0183 Fax +86 21 5046-1119 [email protected] www.ebmpapst.com.cn Hong Kong ebm-papst Hong Kong Ltd. Unit No. 13,9 / F Technology Park, 18 On Lai Street Siu Lek Yuen, Shatin N.T. Hong Kong - P.R. of China Phone +852 2145-8678 Fax +852 2145-7678 [email protected] India ebm-papst India Pvt. Ltd. 26/3, G.N.T. Road, Erukkencherry IND-Chennai-600118 Phone +91 44 25372556 Fax +91 44 25371149 [email protected] www.ebmpapst.in Indonesia ebm-papst Indonesia Representative Office German Centre, 4th Floor, Suite 4470 Jl. Kapt. Subijono Dj. Bumi Serpong Damai RI-15321 Tangerang Phone +62 21 5376250 Fax +62 21 5388305 [email protected] Israel Polak Bros. Import Agencies Ltd. 9 Hamefalsim Street IL-Kiryat Arie, Petach-Tikva 49514 Phone +972 3 9100300 Fax +972 3 5796679 [email protected] www.polak.co.il

74

Japan ebm-papst Industries Japan K.K. 12 Floor, Benex S-3 Bldg. 3-20-8 Shinyokohama, Kohoku-ku J-222-0033 Yokohama Phone +81 45 47057-51 Fax +81 45 47057-52 [email protected] www.ebmpapst.jp Korea ebm-papst Korea Co. Ltd. 6F, Trutec Bldg. B 6-2, Digital Media City (DMC) Sangam-Dong, Mapo-Gu ROK-Seoul 121-270 Phone +82 2 366213-24 Fax +82 2 366213-26 [email protected] www.ebmpapst.co.kr Malaysia ebm-papst Malaysia Representative Office Unit 12-2, Jalan USJ Sentral 3 Persiaran Subang, Selangor Darul Ehsan MAL-47600 Subang Jaya Phone +60 3 8024-1680 Fax +60 3 8024-8718 [email protected] Singapore ebm-papst SEA Pte. Ltd. No. 23 Ubi Road 4 #06-00 Olympia Industrial Building SGP-Singapore 408620 Phone +65 65513789 Fax +65 68428439 [email protected] Taiwan ETECO Engineering & Trading Corp. 10F-I, No. 92, Teh-Wei Str. RC-Tsow-Inn District, Kaohsiung Phone +886 7 557-4268 Fax +886 7 557-2788 [email protected] www.ebmpapst.com.tw

Thailand ebm-papst Thailand Co., Ltd. 99/349 Na-Nakorn Bldg., 4th Floor Chaeng Wattana Road, Thungsonghong, THA-10210 Laksi, BKK Phone +66 2 57615-24 Fax +66 2 57615-42 [email protected] United Arab Emirates ebm-papst Middle East FZE PO Box 17755 Jebel Ali Free Zone / FZS1 / AP05 UAE-Dubai Phone +971 4 88608-26 Fax +971 4 88608-27 [email protected] www.ebmpapst.ae Vietnam ebm-papst Vietnam Representative Office Room #102, 25 Nguyen Van Thu Street District 1 VN-Ho Chi Minh City Phone +84 8 39104099 Fax +84 8 39103970 [email protected]

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 75

Australia Australia ebm-papst A&NZ Pty Ltd. 10 Oxford Road AUS-Laverton North, Victoria, 3026 Phone +61 3 9360-6400 Fax +61 3 9360-6464 [email protected] www.ebmpapst.com.au New Zealand ebm-papst A&NZ Pty Ltd. 102 Henderson Valley Road NZ-Henderson, Auckland 1230 Phone +64 9 837-1884 Fax +64 9 837-1899 [email protected] www.ebmpapst.com.au

75

Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd

19.05.2011

11:34

Seite 76

37797-7-8811 · KD-11/05-3’ Printed in Germany

ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110 [email protected]

www.ebmpapst.com

Suggest Documents