Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 1
Plug Fans with EC motor
The engineer’s choice
version 05/2011
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 2
New Plug fans with EC motor
The plug fans of the centrifugal series with GreenTech EC technology, already established in the market, are now even better! Firstly, all fans above a 500-watt drive output can now be controlled by MODBUS and 0-10V. Secondly, gaps existing in the product range have been filled and the series has been expanded to greater diameters. The sizes 630, 710, 800 and 900 are new. These have been equipped with a stable base frame that enables the entire unit to be decoupled from vibrations in the environment. This makes it possible to achieve additional applications, not just in the heating and ventilation industry. The plug fans are principally intended for operation without a scroll housing. All plug fans shown in the catalogue exceed the minimum efficiency requirements of the ErP Directive for fans, which take effect in 2013 and 2015. Now there are 12 sizes available, with their outer diameters ranging from 250 to 900 mm, which are driven by energy-saving EC external rotor motors with drive capacities between 400 W and 6 kW. The welded impellers with their 7 backward curved blades are made of aluminium as this minimises the bearing load of the motors and maximises durability with high rotational velocity. The position of the impellers on the EC external-rotor motors has been optimised too in terms of aerodynamics and installation requirements. The complete plug fan series is available in the new release of the "Product selector" design program. This tool can be used to select, compare and document fans according to the required operating points. Via a DLL file the plug fans can be integrated into your fan selection programme.
2
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 3
Table of contents
New Plug Fans with EC motor
2
GreenTech: The Green Company
4
Overview
6
Text for tenders
8
Size 250 - 900
10
Accessories (air intake guard grilles, inlet rings)
60
Electrical connections
62
Technical parameters & scope
66
ebm-papst representatives & subsidiaries
70
3
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 4
Sustainability is at the centre of our thoughts and actions. Out of conviction!
Eco-friendliness and sustainability have always been at the core of our thoughts and actions. For decades, we have worked according to the simple but strict creed of our co-founder Gerhard Sturm: “Each new product we develop has to be better than the last one in terms of economy and ecology.” GreenTech is the ultimate expression of our corporate philosophy.
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 5
GreenTech is pro-active development.
GreenTech is acknowledged and certified.
Even in the design phase, the materials and processes we use are optimi-
Every step in our chain of production meets the stringent standards of
sed for the greatest possible eco-friendliness, energy balance and –
environmental specialists and the public. The 2008 Environmental Prize
wherever possible – recyclability. We continually improve the material
of Baden-Wuerttemberg, the Green Award 2009, the Energy Efficiency
and performance of our products, as well as the flow and noise charac-
Award 2009 of the dena – to give just a few examples – testify to this.
teristics. At the same time, we significantly reduce energy consumption.
The environmental advantage gained in the performance of the products
Close co-operation with universities and scientific institutes and the pro-
developed from our GreenTech philosophy can also be measured in the
fessorship we endow in the area of power engineering and regenerative
fulfilment of the most stringent energy and environmental standards.
energies allows us to profit from the latest research findings in these
In many instances, our products are already well below the thresholds
fields – and at the same time ensure highly qualified young academics.
energy legislation will impose a few years from now – several times over.
GreenTech is eco-friendly production.
Our customers profit from this every day.
GreenTech also stands for maximum energy efficiency in our production
The heart of GreenTech is future-oriented EC technology from ebm-
processes. There, the intelligent use of industrial waste heat and ground-
papst. The EC technology at the core of our most efficient motors and
water cooling, photovoltaics and, of course, our own cooling and venti -
fans allows efficiency of up to 90%, saves energy at a very high level,
lation technology are of the utmost importance. Our most modern plant,
significantly extends service life and makes our products maintenance-
for instance, consumes 91% less energy than currently specified and
free. These values pay off not only for the environment, but every cent al-
required. In this way, our products contribute to protecting the environ-
so pays off for the user! All ebm-papst products – even those for which
ment, from their origin to their recyclable packaging.
GreenTech EC technology does not (yet) make sense from an application viewpoint – feature the greatest possible connection of economy and ecology.
5
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
23.05.2011
08:47
Seite 6
New Plug Fans with EC motor Overview of curves
Pa
R3G 250 / M3G 084 R3G 280 / M3G 084 R3G 310 / M3G 112
R3G 355 / M3G 112 R3G 400 / M3G 150 R3G 450 / M3G 150
R3G 500 / M3G 150 R3G 560 / M3G 150 R3G 630 / M3G 200
R3G 710 / M3G 200 R3G 800 / M3G 200 R3G 900 / M3G 200
2000
1000 900 800 700 600 500 400 300
psf
200
100 1000
2000
3000
4000
5000
10000
20000
30000
qV
m3/h
F5 Type Hygiene devices (2) K-Box
Vibration-absorb. elem. D x H / Shore A
K3G250-AT39-74
K3G250-AT39-56
---
K3G250-AV29-B4
K3G250-AV29-B6
---
K3G280-AT04-74
K3G280-AT04-56
---
K3G280-AU06-B2
K3G280-AU06-B4
K3G280-AU06-B6
---
R3G280-AU11-C1
K3G280-AU11-C2
K3G280-AU11-C4
K3G280-AU11-C6
---
1000
R3G310-AX52-90
K3G310-AX52-90
K3G310-AX52-91
K3G310-AX52-35
---
1~ 200-277
1270
R3G310-AX54-21
K3G310-AX54-22
K3G310-AX54-52
---
---
M3G 112-GA
3~ 380-480
1650
R3G310-BB49-01
K3G310-BB49-02
K3G310-BB49-32
---
---
M3G 112-IA
3~ 380-480
2915
R3G310-AZ88-01
K3G310-AZ88-02
K3G310-AZ88-32
K3G310-AZ88-35
---
M3G 112-EA
3~ 380-480
1000
R3G355-AX56-90
K3G355-AX56-90
K3G355-AX56-91
---
---
M3G 112-GA
1~ 200-277
1400
R3G355-AY43-21
K3G355-AY43-22
K3G355-AY43-52
---
---
M3G 112-GA
3~ 380-480
1700
R3G355-AY40-01
K3G355-AY40-02
K3G355-AY40-32
K3G355-AY40-35
---
M3G 112-IA
3~ 380-480
1850
R3G400-AY87-01
K3G400-AY87-02
K3G400-AY87-32
---
---
M3G 150-FF
3~ 380-480
3000
R3G400-AQ23-01
K3G400-AQ23-01
K3G400-AQ23-31
K3G400-AQ23-35
---
M3G 112-IA
3~ 380-480
1650
R3G450-AY86-01
K3G450-AY86-02
K3G450-AY86-32
---
---
M3G 150-FF
3~ 380-480
2730
R3G450-AQ24-01
K3G450-AQ24-01
K3G450-AQ24-31
K3G450-AQ24-35
---
M3G 150-IF
3~ 380-480
5370
R3G450-AZ30-01
K3G450-AZ30-01
K3G450-AZ30-31
K3G450-AZ30-35
---
M3G 150-FF
3~ 380-480
2825
R3G500-AP25-01
K3G500-AP25-01
K3G500-AP25-31
---
---
M3G 150-IF
3~ 380-480
5500
R3G500-AQ33-01
K3G500-AQ33-01
K3G500-AQ33-31
K3G500-AQ33-35
---
M3G 150-IF
3~ 380-480
3000
R3G560-AP23-01
K3G560-AP23-01
K3G560-AP23-31
---
---
M3G 150-NA
3~ 380-480
4700
R3G560-AQ04-01
K3G560-AQ04-01
K3G560-AQ04-31
K3G560-AQ04-35
---
630
M3G 200-HF
3~ 380-480
6140
R3G630-AQ01-01
K3G630-AQ01-01
---
---
50 x 45 / 40
710
M3G 200-LA
3~ 380-480
6240
R3G710-AQ01-01
K3G710-AQ01-01
---
---
50 x 45 / 40
800
M3G 200-QA
3~ 380-480
5800
R3G800-AQ03-01
K3G800-AQ03-01
---
---
50 x 45 / 40
900
M3G 200-QA
3~ 380-480
5950
R3G900-AQ01-01
K3G900-AQ01-01
---
---
50 x 45 / 40
Baugröße Size 250
280
310
355
400
450
500 560
Standard Type Centrifugal fan K-Box
Motor
Supply VAC
Pe W
M3G 084-DF
1~ 200-277
450
R3G250-AT39-71
K3G250-AT39-72
M3G 084-FA
1~ 200-277
700
R3G250-AV29-B1
K3G250-AV29-B2
M3G 084-FA
1~ 200-277
415
R3G280-AT04-71
K3G280-AT04-72
M3G 084-GF
1~ 200-277
715
R3G280-AU06-B1
M3G 084-GF
3~ 380-480
1000
M3G 112-EA
3~ 380-480
M3G 112-EA
(1) Increased
corrosion protection: The support bracket, mounting plate and impeller are coated in black, and the motor also features a black coating.
6
40000
F4-2 Type (1) K-Box
(2) Design
of the hygiene devices: The support bracket, mounting plate and impeller are coated in white, the motor is coated in black, the fastening elements are made of stainless steel.
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 7
Product Selector 2011
Additionaly, and for selecting the correct fan, you can take advan-
Additionally, the life cycle costs for the selected fans can be calculated.
tage of the ebm-papst software "Product Selector" with integrated
You can make your selection based on the operating point or on the type
“Black-Box" module for integration in system configuration pro-
designation.
grammes on the customer side. The data sheets, which can be created in PDF format, show not only the The new selection program gives you the ability to select plug fans based
nominal data of the fan, but also the performance data in the specified
on the operating point. If multiple fans are in the specified power range,
operating point with the inlet and outlet side sound power levels across
the aerodynamic and acoustic data displayed can be used to select and
the octave band.
document the most suitable fan. For more detailed information, simply ask your ebm-papst contact!
7
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 8
EC Centrifugal fan modules K3G 250 to K3G 900
Text for tenders
ebm-papst high performance centrifugal fan modules
Protective features
Single inlet; direct drive; 2D centrifugal impeller with circumferential
- Alarm relay with zero-potential change-over contacts
diffuser mounted on an electronically commutated external-rotor motor
(250 V AC/2 A, cos ϕ = 1)
with integrated electronics; backward curved impeller blades; inlet
- Locked-rotor protection
nozzle made of galvanised sheet steel with pressure relief; complete
- Phase failure detection
unit statically and dynamically balanced in two planes according to
- Soft start of motors
DIN / ISO 1940 and to balancing quality G 6.3; EC external-rotor motor
- Mains under-voltage detection
with maintenance-free ball bearings and permanent lubrication; wide
- Over-temperature protection of electronics and motor
voltage input 1~200-277V, 50/60 Hz respectively 3~380-480V,
- Short-circuit protection
50/60Hz; unit can be operated on all standard Electricity Board networks at identical air performance; optimised motor technology; soft
Technical data
start; integrated current limitation; connection via brought-out variable
- Air flow
qV
cable connector (motor size 084) or via easy-to-mount and robust inte-
- Static pressure
psf = __________Pa
grated terminal box made of aluminium with spring loaded terminals
- Nominal voltage range
U
=
V
(motor sizes 112, 150 and 200); extremely compact electronics; with
- Frequency
f
=
Hz
adjustable PID controller (motor sizes 112, 150 and 200); meets all
- Fan speed
n
= __________rpm
necessary EMC directives and all requirements as to current reverse
- Input power
Pe
= __________kW
transfer; no complicated installation with shielded cables required; very
- Current draw
I
= __________A
low-noise commutation logic; 100% controllability. Motors with an
- Noise level
Lp
= __________dBA
output of 750 W or higher have the RS485/MODBUS RTU interface. If
- Perm. ambient temperature
T
=
structure-borne noise needs to be decoupled, any such action has to
- Fan mass
= __________kg
be taken by the customer.
- Approvals
=
Optionally: Modules with higher protection against corrosion.
Fan type
= __________m3/h
_______________________________
For technical details, dimensions and connection see data sheet
8
°C
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 9
EC centrifugal fans R3G 250 to R3G 900
Text for tenders
ebm-papst high performance centrifugal fans
Protective features
Single inlet; direct drive; 2D centrifugal impeller with circumferential
- Alarm relay with zero-potential change-over contacts
diffuser mounted on an electronically commutated external-rotor motor
(250 V AC/2 A, cos ϕ = 1)
with integrated electronics; backward curved impeller blades; inlet
- Locked-rotor protection
nozzle made of galvanised sheet steel; complete unit statically and
- Phase failure detection
dynamically balanced in two planes according to DIN / ISO 1940 and to
- Soft start of motors
balancing quality G 6.3; EC external-rotor motor with maintenance-free
- Mains under-voltage detection
ball bearings and permanent lubrication; wide voltage input
- Over-temperature protection of electronics and motor
1~200-277V, 50/60 Hz respectively 3~380-480V, 50/60Hz; unit can be
- Short-circuit protection
operated on all standard Electricity Board networks at identical air performance; optimised motor technology; soft start; integrated current
Technical data
limitation; connection via brought-out variable cable connector (motor
- Air flow
qV
= __________m3/h
size 084) or via easy-to-mount and robust integrated terminal box
- Static pressure
psf = __________Pa
made of aluminium with spring loaded terminals (motor sizes 112, 150
- Nominal voltage range
U
=
V
and 200); extremely compact electronics; with adjustable PID controller
- Frequency
f
=
Hz
(motor sizes 112, 150 and 200); meets all necessary EMC directives
- Fan speed
n
= __________rpm
and all requirements as to current reverse transfer; no complicated
- Input power
Pe
= __________kW
installation with shielded cables required; very low-noise commutation
- Current draw
I
= __________A
logic; 100% controllability. Motors with an output of 750 W or higher
- Noise level
Lp
= __________dBA
have the RS485/MODBUS RTU interface.
- Perm. ambient temperature
T
=
°C
- Fan mass
= __________kg
For technical details, dimensions and connection -
- Direction of rotation
= rechts
see data sheet
- Approvals
=
Fan type _______________________________
9
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 10
EC centrifugal fan and modules backward curved, Ø 250
Perm. amb. temp.
Electr. connection
M3G 084-DF
Max. current draw(1)
*3G 250
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet aluminium Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 62
50/60
3000
450
2,80
-25..+40
1~ 200-277
A
K1)
(1) Nominal data in operating point with maximum load and 230 VAC
subject to alterations
Pa
in H2O
Curves A
Air performance measured
3175
380
2,48
84
2
3045
436
2,72
80
A
3
3000
450
2,80
76
A
4
3020
436
2,72
80
A
5
2575
201
1,34
79
Suction-side noise levels:
A
6
2510
228
1,50
75
LWA as per ISO 13347,
A
7
2470
235
1,57
73
LpA measured at 1 m distance
A
8
2495
224
1,51
76
A
9
2000
92
0,66
74
A
10
2000
112
0,78
71
A
11
1990
125
0,88
68
A
12
2015
118
0,84
71
4,0
accidental contact
3,2
LWA dB(A)
1
without protection against
4
I A
A
with ebm-papst inlet nozzle
800
Pe W
A
as per: ISO 5801, Installation category A,
1000
n rpm
600
2,4
to fan axis The acoustic values given are
3
only valid under the measur-
8
ment conditions listed and 1,6
may vary depending on the
400
installation situation.
7 12
With any deviation to the stan-
2 11
dard setup, the specific values
0,8
200
have to be checked and re-
6
viewed once installed or fitted! 10
For detailed information
psf
9 0
qV
10
400
400
800
800
1200
1 1600
5 1200
1600
2000
2400
see page 66 ff. cfm
2800 m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 11
Mass of centrifugal module with support bracket
Masse centrifugal fan
Mass of centrifugal module with support bracket
– Technical features: • Output 10 VDC max. 1,1 mA • PFC (passive) • Alarm relay • Control input 0-10 VDC / PWM • Over-temperature protected electronics / motor – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Cable exit: Variable – Protection class: I – Product conforming to standards: EN 61800-5-1, CE – Approvals: UL, CSA; VDE, CCC, GOST are applied for
Centrifugal fan
kg
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
R3G 250-AT39 -71
4,4
25075-2-4013
K3G 250-AT39 -72
8,7
K3G 250-AT39 -74
8,7
(2) Centrifugal module with higher protection against corrosion
4x90˚
4xØ4.5
201,5±3 153,5 ±2
48 130±1
30˚
43
45˚
Depth of screw 8-10 mm
R3G 250-AT39 -71 Ø6.5
4x90˚ 600+20 85
Ø260 Ø290
Ø166.2
Ø176 Ø284
Ø102
(Ø251)
Ø178 Ø150±0.25 Ø100
M6
80 112
6
Ø164±0.35
Connection line AWG 22, 3x crimped core-end sleeves
Core-end sleeves K3G 250-AT39 -72 / -74 2
o400±1.2 o298
Connection line AWG 18, 5x crimped core-end sleeves
Observe the correct mounting position ! Install the support struts only vertically as shown in the view !
4xØ11
85
±1
0
60
0+
20
237±3 187±1
o350
Pressure tap
11 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 62
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 12
EC centrifugal fan and modules backward curved, Ø 250
subject to alterations
Perm. amb. temp.
Electr. connection
M3G 084-FA
Max. current draw(1)
*3G 250
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet aluminium Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 63
50/60
3450
700
3,00
-25..+40
1~ 200-277
A
L7)
(1) Nominal data in operating point with maximum load and 230 VAC
Pa
in H2O
Curves A
Air performance measured
3450
469
2,07
85
2
3450
591
2,64
82
A
3
3450
700
3,00
78
A
4
3450
661
2,95
81
A
5
2890
268
1,18
81
Suction-side noise levels:
A
6
2890
337
1,51
78
LWA as per ISO 13347,
A
7
2890
401
1,79
74
LpA measured at 1 m distance
A
8
2890
378
1,69
77
A
9
2300
135
0,60
76
A
10
2300
170
0,76
73
A
11
2300
202
0,90
69
A
12
2300
190
0,85
72
4,0
without protection against
3,2
3 8
to fan axis
2,4
600
The acoustic values given are only valid under the measur7
ment conditions listed and may vary depending on the
12
installation situation.
1,6
400
11
2
With any deviation to the standard setup, the specific values
6
0,8
200
have to be checked and reviewed once installed or fitted!
10
psf
For detailed information 0
qV
12
400
400
9 1200
800
800
LWA dB(A)
1
accidental contact
800
I A
A
with ebm-papst inlet nozzle
4
Pe W
A
as per: ISO 5801, Installation category A,
1000
n rpm
1200
1600
2000
1600
2400
see page 66 ff.
1
5
2800
cfm m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 13
Masse centrifugal fan
Line undervoltage detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start
Mass of centrifugal module with support bracket
• • • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (active) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: EN 61800-5-1, CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal fan
kg
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
R3G 250-AV29 -B1
5,6
25075-2-4013
K3G 250-AV29 -B2
10,1
K3G 250-AV29 -B4
10,1
(2) Centrifugal module with higher protection against corrosion
Depth of screw 12-16 mm
223.9±3 167.4±2
4x Ø4.5
56.5
156±1
5x
72
43
˚
R3G 250-AV29 -B1
Ø260 Ø290
Ø166.2
Ø176 Ø284
Ø102
Ø197 Ø165±0.25 Ø130
Ø5.5
Tightening torque 3.5±0.5 Nm Ø186±0,5 80 112
Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm
6
257.5±3 201±1
2
o400-1 o298
Observe the correct mounting position ! Install the support struts only vertically as shown in the view !
4xØ11
K3G 250-AV29 -B2 / -B4
M16x1.5(3x)
Pressure tap
o350
13 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 63
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 14
EC centrifugal fan and modules backward curved, Ø 280
Perm. amb. temp.
Electr. connection
M3G 084-FA
Max. current draw(1)
*3G 280
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet aluminium Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 62
50/60
2400
415
2,70
-25..+40
1~ 200-277
A
K1)
(1) Nominal data in operating point with maximum load and 230 VAC
subject to alterations
Pa
A
Air performance measured
2530
335
2,19
80
2415
392
2,57
75
A
3
2400
415
2,70
71
A
4
2405
405
2,66
75
A
5
2040
171
1,17
74
Suction-side noise levels:
A
6
1990
216
1,45
69
LWA as per ISO 13347,
A
7
1965
237
1,58
67
LpA measured at 1 m distance
A
8
2010
215
1,45
70
A
9
1570
85
0,63
67
A
10
1575
111
0,79
63
A
11
1560
122
0,86
62
A
12
1580
106
0,76
64
2,8
accidental contact
2,4
to fan axis
2,0
500
The acoustic values given are
3
only valid under the measur-
8
1,6
400
ment conditions listed and may vary depending on the installation situation.
7
1,2
300
12
2
0,8
200
With any deviation to the standard setup, the specific values
11 6
have to be checked and reviewed once installed or fitted!
10
0,4
100
For detailed information
psf
9 0
qV
14
LWA dB(A)
2
without protection against
600
I A
1
Installation category A,
4
Pe W
A
with ebm-papst inlet nozzle
700
n rpm A
as per: ISO 5801,
3,2
800
in H2O
Curves
500
500
1000
1000
1500
2000
5 1500
2500
see page 66 ff.
1 cfm
3000
m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 15
Mass of centrifugal module with support bracket
Masse centrifugal fan
Mass of centrifugal module with support bracket
– Technical features: • Output 10 VDC max. 1,1 mA • PFC (passive) • Alarm relay • Control input 0-10 VDC / PWM • Over-temperature protected electronics / motor – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Cable exit: Variable – Protection class: I – Product conforming to standards: EN 61800-5-1, CE – Approvals: UL, CSA; VDE, CCC, GOST are applied for
Centrifugal fan
kg
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
R3G 280-AT04 -71
5,4
28075-2-4013
K3G 280-AT04 -72
9,8
K3G 280-AT04 -74
9,8
(2) Centrifugal module with higher protection against corrosion
4x90˚
4xØ4.5
227±3 179±2
48 145±1
30˚
53
45˚
Depth of screw 8-10 mm
R3G 280-AT04 -71 Ø6.5
4x90˚ 600+20 85
Ø280 Ø325
Ø187.2
Ø197.4 Ø319
Ø102
(Ø282)
Ø178 Ø150±0.25 Ø100
M6
90 132
10
Ø164±0.35
Connection line AWG 22, 3x crimped core-end sleeves
Core-end sleeves K3G 280-AT04 -72 / -74 2
o400±1.2 o298
Connection line AWG 18, 5x crimped core-end sleeves
Observe the correct mounting position ! Install the support struts only vertically as shown in the view !
4xØ11
85
±1
0
60
0+
20
Ø319±2
268±3 218±1
o350
Pressure tap
15 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 62
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 16
EC centrifugal fan and modules backward curved, Ø 280
subject to alterations
Perm. amb. temp.
Electr. connection
M3G 084-GF
Max. current draw(1)
*3G 280
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet aluminium Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 63
50/60
2800
715
3,10
-25..+40
1~ 200-277
A
L7)
(1) Nominal data in operating point with maximum load and 230 VAC
Pa
in H2O
Curves A
2800
479
2,11
83
2
2800
655
2,88
79
A
3
2800
715
3,10
76
A
4
2800
650
2,85
82
A
5
2400
294
1,30
79
Suction-side noise levels:
A
6
2400
410
1,80
75
LWA as per ISO 13347,
A
7
2400
471
2,06
73
LpA measured at 1 m distance
A
8
2400
401
1,76
78
A
9
1900
146
0,65
74
A
10
1900
203
0,89
70
A
11
1900
234
1,02
68
A
12
1900
199
0,87
73
3,2
Installation category A,
2,8
accidental contact
to fan axis
2,0
500
2,4
3 8
7
The acoustic values given are only valid under the measur-
1,6
400
ment conditions listed and
12
1,2
2
300
may vary depending on the installation situation.
11 6
0,8
With any deviation to the stan-
200
dard setup, the specific values 10
have to be checked and reviewed once installed or fitted!
0,4
100
For detailed information
psf
9 0
qV
16
LWA dB(A)
1
without protection against
600
I A
A
with ebm-papst inlet nozzle
700
Pe W
A
as per: ISO 5801, 4
800
Air performance measured
n rpm
500
500
1000
1000
1500
1500
2000
2500
2000
3000
see page 66 ff.
1
5
3500
cfm m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 17
Masse centrifugal fan
Line undervoltage detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start
Mass of centrifugal module with support bracket
• • • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (active) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: EN 61800-5-1, CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal fan
kg
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
R3G 280-AU06 -B1
6,8
28075-2-4013
K3G 280-AU06 -B2
11,4
K3G 280-AU06 -B4
11,4
(2) Centrifugal module with higher protection against corrosion
Depth of screw 12-16 mm
252.4±3 196±2 171.4±1
4x Ø4.5
56.5
5x
72
53
˚
R3G 280-AU06 -B1
Ø280 Ø325
Ø187.2
Ø197.4 Ø319
Ø102
Ø197 Ø165±0.25 Ø130
Ø5.5
Tightening torque 3.5±0.5 Nm Ø186±0,5 90 132
Cable gland: M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm
291.5±3 235±1
o400-1 o298
2
Observe the correct mounting position ! Install the support struts only vertically as shown in the view !
4xØ11
Ø319±2
K3G 280-AU06 -B2 / -B4
10
M16x1.5(3x)
o350
Pressure tap
17 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 63
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:32
Seite 18
EC centrifugal fan and modules backward curved, Ø 280
subject to alterations
Perm. amb. temp.
Electr. connection
M3G 084-GF
Max. current draw(1)
*3G 280
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet aluminium Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 63
50/60
3100
1000
1,60
-25..+60
3~ 380-480
A
L6)
(1) Nominal data in operating point with maximum load and 400 VAC
Pa
in H2O
Curves A
Air performance measured
3100
645
1,04
86
2
3100
852
1,35
83
A
3
3100
1000
1,60
80
A
4
3100
921
1,46
83
A
5
2575
358
0,58
82
Suction-side noise levels:
A
6
2575
482
0,76
79
LWA as per ISO 13347,
A
7
2575
562
0,89
76
LpA measured at 1 m distance
A
8
2575
514
0,82
79
A
9
2045
180
0,29
77
A
10
2045
242
0,38
74
A
11
2045
282
0,45
71
A
12
2045
257
0,41
74
4,0
without protection against
3,2
3
to fan axis
2,4
8
600
The acoustic values given are only valid under the measur-
7
ment conditions listed and may vary depending on the
1,6
12
400
installation situation.
2 11
With any deviation to the stan6
dard setup, the specific values have to be checked and re-
0,8
200
viewed once installed or fitted!
10
psf
For detailed information 0
qV
18
500
500
1000
9 1500
1000
1500
LWA dB(A)
1
accidental contact
800
I A
A
with ebm-papst inlet nozzle
4
Pe W
A
as per: ISO 5801, Installation category A,
1000
n rpm
2000
2500
5 2000
3000
3500
1 cfm m3/h
see page 66 ff.
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 19
Masse centrifugal fan
Line undervoltage / phase failure detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start
Mass of centrifugal module with support bracket
• • • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: EN 61800-5-1, CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal fan
kg
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
R3G 280-AU11 -C1
7,1
28075-2-4013
K3G 280-AU11 -C2
11,7
K3G 280-AU11 -C4
11,7
(2) Centrifugal module with higher protection against corrosion
Depth of screw 12-16 mm
252.4±3 196±2 171.4±1
4x Ø4.5
56.5
5x
72
53
˚
R3G 280-AU11 -C1
Ø280 Ø325
Ø187.2
Ø197.4 Ø319
Ø102
Ø197 Ø165±0.25 Ø130
Ø5.5
Tightening torque 3.5±0.5 Nm Ø186±0,5 90 132
Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm
291.5±3 235±1
o400-1 o298
2
Observe the correct mounting position ! Install the support struts only vertically as shown in the view !
4xØ11
Ø319±2
K3G 280-AU11 -C2 / -C4
10
M16x1.5(3x)
o350
Pressure tap
19 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 63
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 20
EC centrifugal fan and modules backward curved, Ø 310
Perm. amb. temp.
Electr. connection
M3G 112-EA
Max. current draw(1)
*3G 310
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 63
50/60
2580
1000
1,60
-25..+55
3~ 380-480
A
L6)
(1) Nominal data in operating point with maximum load and 400 VAC
subject to alterations
Pa
A
Air performance measured
2580
669
1,17
88
2580
862
1,46
81
A
3
2580
1000
1,60
77
A
4
2580
907
1,53
79
A
5
1930
288
0,57
80
Suction-side noise levels:
A
6
1910
348
0,69
74
LWA as per ISO 13347,
A
7
1900
396
0,77
500
3,2 2,8 2,4
600
70
LpA measured at 1 m distance
A
8
1905
360
0,72
71
A
9
1305
123
0,28
72
A
10
1305
144
0,33
67
A
11
1305
151
0,34
62
A
12
1300
151
0,34
62
accidental contact
3
to fan axis The acoustic values given are
8
only valid under the measurment conditions listed and
1,6
400
2
may vary depending on the
7
1,2
installation situation.
300
With any deviation to the stan12
0,8
200
dard setup, the specific values
6
have to be checked and re-
11
0,4
viewed once installed or fitted!
100
10
For detailed information
psf
9 0
qV
20
LWA dB(A)
2
without protection against
2,0
700
I A
1
with ebm-papst inlet nozzle
800
Pe W
A
Installation category A,
4
n rpm A
as per: ISO 5801,
3,6
900
in H2O
Curves
500
1000
1000
5 2000
1500
2000
3000
see page 66 ff.
1 2500
4000
cfm m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 21
Masse centrifugal fan
Line undervoltage / phase failure detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start
Mass of centrifugal module with support bracket
• • • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal fan
kg
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
R3G 310-AX52 -90
8,8
31575-2-4013
K3G 310-AX52 -90
16,7
K3G 310-AX52 -91
16,7
(2) Centrifugal module with higher protection against corrosion
253,7±3 197,2±2
Depth of screw 12-16 mm 4xØ4,5
56,5
R3G 310-AX52 -90
5xM6
55
160,5±1
˚
72
Ø325 Ø350
Ø211,7
Ø222 Ø360
Ø138
5x
Ø168 Ø186±0,5
Tightening torque 3.5±0.5 Nm Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm
100 147
10
294±3 237.5±2.5
o500-1 o372
15
Observe the correct mounting position ! Install the support struts only vertically as shown in the view !
4xØ11
K3G 310-AX52 -90 / -91
M16x1.5(3x) o450
Pressure tap
21 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 63
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 22
EC centrifugal fan and modules backward curved, Ø 310
subject to alterations
Electr. connection
A
Perm. amb. temp.
M3G 112-EA
Max. current draw(1)
*3G 310
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 65
50/60
2850
1270
5,60
-25..+60
1~ 200-277
L9)
(1) Nominal data in operating point with maximum load and 230 VAC
n rpm
Pa
1200
4,8 in H2O
Curves A
Air performance measured
1
2930
946
4,14
88
2
2895
1147
5,01
83
A
3
2850
1270
5,60
79
A
4
2850
1237
5,41
83
A
5
2430
529
2,34
84
Suction-side noise levels:
A
6
2430
663
2,91
78
LWA as per ISO 13347,
A
7
2430
743
3,26
77
LpA measured at 1 m distance
A
8
2430
751
3,29
78
A
9
1955
299
1,36
78
A
10
1955
360
1,61
73
A
11
1955
398
1,77
72
A
12
1955
400
1,78
73
without protection against
4,0
accidental contact
3,2
800
8
to fan axis
3
2,4
The acoustic values given are
600
only valid under the measur7
ment conditions listed and
12
may vary depending on the installation situation.
2
1,6
400
11
With any deviation to the stan6
dard setup, the specific values have to be checked and re-
0,8
200
10
viewed once installed or fitted!
psf
For detailed information 0
qV
22
500
1000
1000
9 2000
1500
2000
3000
LWA dB(A)
A
Installation category A,
4
I A
A
as per: ISO 5801, with ebm-papst inlet nozzle
1000
Pe W
5 2500
4000
see page 66 ff.
1 cfm
5000
m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 23
kg
R3G 310-AX54 -21
11,0
Line undervoltage detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start
Mass of centrifugal module with support bracket
Masse centrifugal fan Centrifugal fan
• • • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (active) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
31575-2-4013
K3G 310-AX54 -22
19,4
K3G 310-AX54 -52
19,4
(2) Centrifugal module with higher protection against corrosion
72
269.2 ±3 197.2 ±2
4xØ4.5
R3G 310-AX54 -21
Depth of screw 12-16 mm
55
6xM10
Ø325 Ø350
Ø211.7
Ø 222 Ø 360
Ø 138
0˚
6x6
Ø 232±0.3
Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
100 147
Ø 252±0.5
10
309.5±3 273.5±2
o500-1 o375
15
Tightening torque 3.5±0.5 Nm
Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)
K3G 310-AX54 -22 / -52
5
. 0x1 M2 3x) (
o450
Pressure tap
23 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 65
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 24
EC centrifugal fan and modules backward curved, Ø 310
subject to alterations
Perm. amb. temp.
Electr. connection
M3G 112-GA
Max. current draw(1)
*3G 310
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
3140
1650
2,50
-25..+60
3~ 380-480
A
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
Pa
1400
in H2O
Curves A
Air performance measured
3140
1158
1,79
90
2
3140
1440
2,21
86
A
3
3140
1650
2,50
83
A
4
3140
1559
2,39
87
A
5
2620
658
1,02
85
Suction-side noise levels:
A
6
2620
824
1,26
82
LWA as per ISO 13347,
A
7
2620
942
1,44
79
LpA measured at 1 m distance
A
8
2620
889
1,36
83
A
9
2100
339
0,52
81
A
10
2100
425
0,65
77
A
11
2100
485
0,74
74
A
12
2100
458
0,70
78
4,8
without protection against accidental contact
3 8
LWA dB(A)
1
Installation category A,
4,0
1000
I A
A
with ebm-papst inlet nozzle
1200
Pe W
A
as per: ISO 5801, 4
n rpm
800
3,2
to fan axis The acoustic values given are 7
ment conditions listed and
2,4
600
only valid under the measur-
12
may vary depending on the installation situation.
2 1,6
11
400
With any deviation to the stan6
dard setup, the specific values have to be checked and re-
0,8
200
10
viewed once installed or fitted!
psf
For detailed information 0
qV
24
500
1000
1000
9 2000
1500
2000
3000
5 2500
4000
see page 66 ff.
1 3000
5000
cfm m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 25
kg
R3G 310-BB49 -01
12,6
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Masse centrifugal fan Centrifugal fan
• • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC bzw. 4-20 mA • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
31575-2-4013
K3G 310-BB49 -02
21,0
K3G 310-BB49 -32
21,0
(2) Centrifugal module with higher protection against corrosion
60
277.2 ±3 217.2 ±2
4xØ4.5
R3G 310-BB49 -01
Depth of screw 12-16 mm
55
6xM10
Ø325 Ø350
Ø211.7
Ø 222 Ø 360
Ø 138
0˚
6x6
Ø 232±0.3
Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
100 147
Ø 252±0.5
10
318.5±3 258.5±2
o500-1 o375
15
Tightening torque 3.5±0.5 Nm
Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)
K3G 310-BB49 -02 / -32
5
. 0x1 M2 3x) (
o450
Pressure tap
25 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 26
EC centrifugal fan and modules backward curved, Ø 310
subject to alterations
Perm. amb. temp.
Electr. connection
M3G 112-IA
Max. current draw(1)
*3G 310
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
4100
2915
4,50
-25..+40
3~ 380-480
A
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
Pa
in H2O
Curves A
Air performance measured
4100
1976
3,03
97
2
4100
2488
3,77
91
A
3
4100
2915
4,50
89
A
4
4100
2750
4,19
93
A
5
3400
1127
1,73
93
Suction-side noise levels:
A
6
3400
1428
2,17
87
LWA as per ISO 13347,
A
7
3400
1659
2,53
85
LpA measured at 1 m distance
A
8
3400
1566
2,39
89
A
9
2700
564
0,87
88
A
10
2700
715
1,08
82
A
11
2700
831
1,27
80
A
12
2700
784
1,19
84
8,0
accidental contact
3
LWA dB(A)
1
without protection against
6,4
1600
I A
A
with ebm-papst inlet nozzle 4
Pe W
A
as per: ISO 5801, Installation category A,
2000
n rpm
to fan axis 4,8
8
1200
The acoustic values given are only valid under the measur7
ment conditions listed and may vary depending on the installation situation.
12
3,2
800
2 11
With any deviation to the stan6
dard setup, the specific values have to be checked and re-
1,6
400
10
viewed once installed or fitted! For detailed information
psf
9 0
qV
26
500
1000
1000
1500
2000
2000
3000
5 2500
4000
3000
5000
1 cfm m3/h
see page 66 ff.
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 27
kg
R3G 310-AZ88 -01
15,0
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Masse centrifugal fan Centrifugal fan
• • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC bzw. 4-20 mA • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
31575-1-4013
K3G 310-AZ88 -02
24,2
K3G 310-AZ88 -32
24,2
(2) Centrifugal module with higher protection against corrosion
69.5
287±3 217.5 ±2
4xØ4.5
R3G 310-AZ88 -01
Depth of screw 12-16 mm
55
6xM10
Ø325 Ø350
Ø211.7
Ø 222 Ø 360
Ø 138
0˚
6x6
Ø 232±0.3
Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
80 127
Ø 252±0.5
10
328±3 258.5±2
o500-1 o375
15
Tightening torque 3.5±0.5 Nm
Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)
K3G 310-AZ88 -02 / -32
5
. 0x1 M2 3x) (
o450
Pressure tap
27 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 28
EC centrifugal fan and modules backward curved, Ø 355
Perm. amb. temp.
Electr. connection
M3G 112-EA
Max. current draw(1)
*3G 355
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 63
50/60
2140
1000
1,70
-25..+60
3~ 380-480
A
L6)
(1) Nominal data in operating point with maximum load and 400 VAC
subject to alterations
Pa
A
Air performance measured
2140
656
1,14
87
2140
893
1,50
77
A
3
2140
1000
1,70
75
A
4
2140
918
1,54
78
A
5
1610
286
0,57
79
Suction-side noise levels:
A
6
1595
350
0,68
70
LWA as per ISO 13347,
A
7
1580
387
0,74
69
LpA measured at 1 m distance
A
8
1585
366
0,70
70
A
9
1080
113
0,28
71
A
10
1065
133
0,31
64
A
11
1065
143
0,33
60
A
12
1060
135
0,32
61
with ebm-papst inlet nozzle
2,8
accidental contact
2,4
to fan axis
2,0
500
The acoustic values given are 8
1,6
400
only valid under the measur-
2
ment conditions listed and
1,2
200
0,8
7
300
may vary depending on the installation situation. With any deviation to the stan6
dard setup, the specific values
12
have to be checked and re-
11
viewed once installed or fitted!
0,4
100
10
psf
For detailed information 0
qV
28
LWA dB(A)
2
3
600
I A
1
without protection against
700
Pe W
A
Installation category A,
4
n rpm A
as per: ISO 5801,
3,2
800
in H2O
Curves
500
1000
9 1500
1000
2000
2000
3000
see page 66 ff.
1
5 2500
4000
3000
5000
cfm m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 29
Masse centrifugal fan
Line undervoltage / phase failure detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start
Mass of centrifugal module with support bracket
• • • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal fan
kg
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
R3G 355-AX56 -90
9,4
35675-2-4013
K3G 355-AX56 -90
17,4
K3G 355-AX56 -91
17,4
(2) Centrifugal module with higher protection against corrosion
270,7±3 214,2±2
56,5
Depth of screw 12-16 mm 4xØ4,5
R3G 355-AX56 -90
5xM6
64,5
160,5±1
˚
72
Ø345 Ø370
Ø239
Ø250,3 Ø404
Ø138
Ø405
5x
Ø168 Ø186±0,5
Tightening torque 3.5±0.5 Nm 112
Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm
164
12
319.5±3 263±2.5
o500-1 o372
15
Observe the correct mounting position ! Install the support struts only vertically as shown in the view !
4xØ11
K3G 355-AX56 -90 / -91
M16x1.5(3x) o450
Pressure tap
29 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 63
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 30
EC centrifugal fan and modules backward curved, Ø 355
subject to alterations
Electr. connection
A
Perm. amb. temp.
M3G 112-GA
Max. current draw(1)
*3G 355
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 65
50/60
2450
1400
6,00
-25..+50
1~ 200-277
L9)
(1) Nominal data in operating point with maximum load and 230 VAC
n rpm
Pa
in H2O
Curves A
Air performance measured
1
2450
998
4,33
86
2
2440
1232
5,35
82
A
3
2450
1400
6,00
79
A
4
2410
1344
5,84
82
A
5
2035
562
2,44
82
Suction-side noise levels:
A
6
2035
715
3,11
78
LWA as per ISO 13347,
A
7
2035
855
3,72
76
LpA measured at 1 m distance
A
8
2035
810
3,52
78
A
9
1630
289
1,25
77
A
10
1630
368
1,60
73
A
11
1630
440
1,91
71
A
12
1630
416
1,81
73
4,0
without protection against
3,2
accidental contact
800
3 8
to fan axis
2,4
600
The acoustic values given are only valid under the measur-
7
ment conditions listed and may vary depending on the
12
installation situation.
1,6
400
2 11
With any deviation to the standard setup, the specific values
6
have to be checked and re-
0,8
200
10
viewed once installed or fitted!
psf
For detailed information 0
qV
30
500
1000
1000
2000
LWA dB(A)
A
with ebm-papst inlet nozzle 4
I A
A
as per: ISO 5801, Installation category A,
1000
Pe W
1500
2000
3000
9 2500
4000
5 3000
5000
see page 66 ff.
1 3500
6000
cfm m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 31
kg
R3G 355-AY43 -21
14,0
Line undervoltage detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start
Mass of centrifugal module with support bracket
Masse centrifugal fan Centrifugal fan
• • • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (active) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC / PWM • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
35675-2-4013
K3G 355-AY43 -22
22,4
K3G 355-AY43 -52
22,4
(2) Centrifugal module with higher protection against corrosion
72
306.2 ±3 234.2 ±2
4xØ4.5
R3G 355-AY43 -21
Depth of screw 12-16 mm
64.4
6xM10
Ø345 Ø370
Ø239
Ø 250.3 Ø 404
Ø 405
Ø 138
0˚
6x6
Ø 232±0.3
112 164
Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
354.5±3 282.5±2
o500-1 o375
15
Tightening torque 3.5±0.5 Nm
Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)
Ø405
K3G 355-AY43 -22 / -52
Ø 252±0.5
12
5
. 0x1 M2 3x) (
o450
Pressure tap
31 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 65
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 32
EC centrifugal fan and modules backward curved, Ø 355
Perm. amb. temp.
Electr. connection
M3G 112-GA
Max. current draw(1)
*3G 355
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
2600
1700
2,60
-25..+40
3~ 380-480
A
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
subject to alterations
Pa
1200
4,8 in H2O
Curves A
Air performance measured
2600
1140
1,74
92
2
2600
1510
2,30
83
A
3
2600
1700
2,60
79
A
4
2600
1594
2,42
83
A
5
1940
436
0,73
84
Suction-side noise levels:
A
6
1910
541
0,88
76
LWA as per ISO 13347,
A
7
1885
533
0,95
73
LpA measured at 1 m distance
A
8
1905
558
0,91
76
A
9
1330
194
0,40
76
A
10
1315
226
0,45
70
A
11
1305
239
0,47
66
A
12
1305
236
0,46
66
with ebm-papst inlet nozzle
4,0
accidental contact
3,2
800
LWA dB(A)
1
Installation category A,
3
I A
A
without protection against
1000
Pe W
A
as per: ISO 5801, 4
n rpm
to fan axis
600
2,4
The acoustic values given are 8
only valid under the measurment conditions listed and 2
may vary depending on the
7
1,6
400
installation situation. With any deviation to the stan-
12
0,8
200
dard setup, the specific values
6
have to be checked and re-
11
viewed once installed or fitted! 10
psf
For detailed information 0
qV
32
500
1000
1000
2000
1500
9 2000
3000
2500
4000
see page 66 ff.
1
5 3000
5000
3500
6000
cfm m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 33
kg
R3G 355-AY40 -01
13,1
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Masse centrifugal fan Centrifugal fan
• • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC bzw. 4-20 mA • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
35675-2-4013
K3G 355-AY40 -02
23,4
K3G 355-AY40 -32
23,4
(2) Centrifugal module with higher protection against corrosion
294.2±3 234.2±2
60
4xØ4.5
R3G 355-AY40 -01
Depth of screw 12-16 mm
64.4
6xM10
182±1
Ø345 Ø370
Ø239
Ø 250.3 Ø 404
Ø 405
Ø 138
0˚
6x6
Ø 232±0.3
112 163.7
Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
342.5±3 282.5±2
o500-1 o375
15
Tightening torque 3.5±0.5 Nm
Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)
Ø405
K3G 355-AY40 -02 / -32
Ø 252±0.5
12
5
. 0x1 M2 3x) (
o450
Pressure tap
33 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 34
EC centrifugal fan and modules backward curved, Ø 400
subject to alterations
Electr. connection
A
Perm. amb. temp.
M3G 112-IA
Max. current draw(1)
*3G 400
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
2180
1850
2,90
-25..+50
3~ 380-480
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
Pa
in H2O
Curves A
Air performance measured
2180
1178
1,81
89
2
2180
1748
2,66
82
A
3
2180
1850
2,90
81
A
4
2180
1638
2,49
84
A
5
1850
720
1,10
85
Suction-side noise levels:
A
6
1850
1063
1,62
78
LWA as per ISO 13347,
A
7
1850
1132
1,72
77
LpA measured at 1 m distance
A
8
1850
1001
1,52
80
A
9
1470
361
0,55
80
A
10
1470
533
0,81
73
A
11
1470
568
0,86
72
A
12
1470
502
0,76
75
4,0
accidental contact
3,2
800
8
to fan axis 7
2,4
600
The acoustic values given are
2
only valid under the measurment conditions listed and 1,6
12
400
may vary depending on the
6
installation situation.
11
With any deviation to the stan10
dard setup, the specific values have to be checked and re-
0,8
200
viewed once installed or fitted!
psf
For detailed information 0
qV
34
1000
1000
2000
LWA dB(A)
1
without protection against
3
I A
A
with ebm-papst inlet nozzle 4
Pe W
A
as per: ISO 5801, Installation category A,
1000
n rpm
9 3000
2000
3000
4000
5000
5 4000
6000
7000
1 cfm m3/h
see page 66 ff.
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 35
kg
R3G 400-AY87 -01
15,6
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Masse centrifugal fan Centrifugal fan
• • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC bzw. 4-20 mA • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
40075-2-4013
K3G 400-AY87 -02
26,0
K3G 400-AY87 -32
26,0
(2) Centrifugal module with higher protection against corrosion
330.5±3 273 ±2
57.5
6xØ9
R3G 400-AY87 -01
Depth of screw 12-16 mm
68
6xM10
202±1
Ø390 Ø413
Ø270.9
Ø 282 Ø 455
Ø 138
0˚
6x6
Ø 232±0.3
125 182
Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
384±3 327±2
o500-1 o375
15
Tightening torque 3.5±0.5 Nm
Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)
Ø455
K3G 400-AY87 -02 / -32
Ø 252±0.5
9
5
. 0x1 M2 3x) (
o450
Pressure tap
35 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 36
EC centrifugal fan and modules backward curved, Ø 400
Perm. amb. temp.
Electr. connection
M3G 150-FF
Max. current draw(1)
*3G 400
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
2550
3000
4,60
-25..+60
3~ 380-480
A
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
subject to alterations
Pa
1400
in H2O
Curves A
Air performance measured
2550
1989
3,03
93
2
2550
2578
3,92
87
A
3
2550
3000
4,60
85
A
4
2550
2890
4,41
87
A
5
2115
1135
1,73
89
Suction-side noise levels:
A
6
2115
1471
2,24
83
LWA as per ISO 13347,
A
7
2115
1709
2,61
81
LpA measured at 1 m distance
A
8
2115
1649
2,52
83
A
9
1680
569
0,87
84
A
10
1680
737
1,12
78
A
11
1680
857
1,31
76
A
12
1680
826
1,26
78
with ebm-papst inlet nozzle
4,8
without protection against accidental contact
4,0
8
LWA dB(A)
1
3
1000
I A
A
Installation category A,
1200
Pe W
A
as per: ISO 5801, 4
n rpm
800
3,2
to fan axis 7
The acoustic values given are only valid under the measurment conditions listed and
2,4
600
2
12
may vary depending on the installation situation.
1,6
11
400
6
With any deviation to the standard setup, the specific values have to be checked and re-
200
0,8
10
viewed once installed or fitted! For detailed information
psf
9 0
qV
36
1000
2000
2000
3000
4000
1 cfm
5 4000
6000
8000
m3/h
see page 66 ff.
19.05.2011
Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay
Masse centrifugal fan Centrifugal fan
kg
R3G 400-AQ23 -01
21,7
Seite 37
• • • •
Mass of centrifugal module with support bracket
– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST
11:33
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
40075-2-4013
K3G 400-AQ23 -01
32,3
K3G 400-AQ23 -31
32,3
(2) Centrifugal module with higher protection against corrosion
68
6xØ9
335.6 ±3 265.6 ±2
70
R3G 400-AQ23 -01
Depth of screw max. 25 mm 14xM10 45
8x
220.5±1
6x6 0˚
Ø390 Ø413
Ø455
Ø270.9
Ø282
22.5˚
Ø188
˚
Ø232-2
Ø252±0,3 Ø275
9
125 182
Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
K3G 400-AQ23 -01 / -31 390±3 320±2
15
Tightening torque 3.5±0.5 Nm
o500-1 o375
Ø11 (4x)
M 2 (3 0x1 x) .5
Ø566
Observe the correct mounting position ! Install the support struts only vertically as shown in the view !
o450
Pressure tap
37 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 38
EC centrifugal fan and modules backward curved, Ø 450
subject to alterations
Electr. connection
A
Perm. amb. temp.
M3G 112-IA
Max. current draw(1)
*3G 450
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
1750
1615
2,50
-25..+50
3~ 380-480
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
Pa
A
Air performance measured
1750
1036
1,61
87
1750
1457
2,25
80
A
3
1750
1615
2,50
77
A
4
1750
1524
2,33
80
A
5
1450
571
0,92
82
Suction-side noise levels:
A
6
1450
812
1,28
75
LWA as per ISO 13347,
A
7
1450
906
1,42
73
LpA measured at 1 m distance
A
8
1450
810
1,27
76
A
9
1155
306
0,56
76
A
10
1155
427
0,73
69
A
11
1155
462
0,77
67
A
12
1155
411
0,70
69
2,8
accidental contact
2,4
8
to fan axis
2,0
500
The acoustic values given are
7
2
1,6
400
only valid under the measurment conditions listed and may vary depending on the
1,2
12
300
installation situation.
6
11
0,8
With any deviation to the stan-
200
dard setup, the specific values
10
have to be checked and reviewed once installed or fitted!
0,4
100
For detailed information
psf
9 0
qV
38
1000
2000
LWA dB(A)
2
with ebm-papst inlet nozzle
3
600
I A
1
without protection against
700
Pe W
A
Installation category A, 4
n rpm A
as per: ISO 5801,
3,2
800
in H2O
Curves
2000
3000
4000
4000
6000
see page 66 ff.
1
5 5000
8000
cfm m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 39
kg
R3G 450-AY86 -01
16,4
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Masse centrifugal fan Centrifugal fan
• • • •
Mass of centrifugal module with support bracket
– Technical features: • Slave output 0-10 V max. 3 mA • PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Control input 0-10 VDC bzw. 4-20 mA • RS485 MODBUS • Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
45075-2-4013
K3G 450-AY86 -02
31,9
K3G 450-AY86 -32
31,9
(2) Centrifugal module with higher protection against corrosion
355 ±3 295 ±2
60
6xØ9
R3G 450-AY86 -01
Depth of screw 12-16 mm
76
6xM10
202±1
Ø430 Ø480
Ø303.4
Ø 317 Ø 505
Ø 138
0˚
6x6
Ø 232±0.3
140 204
Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
417±3 357±2
o630-1 o551
15
Tightening torque 3.5±0.5 Nm
Observe the correct mounting position ! Install the support struts only vertically as shown in the view ! Ø11 (4x)
Ø505
K3G 450-AY86 -02 / -32
Ø 252±0.5
9
5
. 0x1 M2 3x) (
o580
Pressure tap
39 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 40
EC centrifugal fan and modules backward curved, Ø 450
Perm. amb. temp.
Electr. connection
M3G 150-FF
Max. current draw(1)
*3G 450
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
2040
2730
4,20
-25..+60
3~ 380-480
A
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
subject to alterations
Pa
1200
4,8 in H2O
Curves A
Air performance measured
2040
1773
2,71
92
2
2040
2500
3,80
83
A
3
2040
2730
4,20
81
A
4
2040
2587
3,96
83
A
5
1695
991
1,52
88
Suction-side noise levels:
A
6
1695
1428
2,17
79
LWA as per ISO 13347,
A
7
1695
1548
2,35
77
LpA measured at 1 m distance
A
8
1695
1450
2,22
79
A
9
1345
495
0,76
83
A
10
1345
713
1,09
74
A
11
1345
774
1,18
72
A
12
1345
725
1,11
74
without protection against
4,0
accidental contact
3,2
800
to fan axis
8
The acoustic values given are 2
7
2,4
600
only valid under the measurment conditions listed and may vary depending on the
12
installation situation.
6
1,6
400
11
With any deviation to the standard setup, the specific values
10
have to be checked and re-
0,8
200
viewed once installed or fitted!
psf
For detailed information 0
qV
40
1000
2000
2000
9 4000
3000
4000
LWA dB(A)
1
Installation category A,
3
I A
A
with ebm-papst inlet nozzle
1000
Pe W
A
as per: ISO 5801,
4
n rpm
6000
5 5000
8000
see page 66 ff.
1 6000
cfm
10000
m3/h
19.05.2011
Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay
Masse centrifugal fan Centrifugal fan
kg
R3G 450-AQ24 -01
22,5
Seite 41
• • • •
Mass of centrifugal module with support bracket
– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST
11:33
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
45075-2-4013
K3G 450-AQ24 -01
38,2
K3G 450-AQ24 -31
38,2
(2) Centrifugal module with higher protection against corrosion
76
6xØ9
357 ±3 287.2 ±2
70
R3G 450-AQ24 -01
Depth of screw max. 25 mm 14xM10
6x6
0˚
Ø430 Ø480
Ø303.4
Ø505
Ø317
22.5˚
Ø188
˚
45
8x
220.5±1
Ø232-2
Ø252±0,3 Ø275
9
140 204
Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
K3G 450-AQ24 -01 / -31 419±3 349±2
15
Tightening torque 3.5±0.5 Nm
o630-1 o551
Ø11 (8x)
M 2 (3 0x1 x) .5
Ø566
Observe the correct mounting position ! Install the support struts only vertically as shown in the view !
o580
Pressure tap
41 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 42
EC centrifugal fan and modules backward curved, Ø 450
Electr. connection
VAC
Hz
rpm
W
A
°C
p. 64
50/60
2750
5370
8,30
-25..+40
3~ 380-480
A
subject to alterations
Perm. amb. temp.
M3G 150-IF
Max. current draw(1)
*3G 450
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
Pa
2000
8,0 in H2O
Curves A
Air performance measured
2750
3105
4,79
100
2
2750
4841
7,47
90
A
3
2750
5370
8,30
89
A
4
2750
5060
7,80
93
A
5
2280
1769
2,73
96
Suction-side noise levels:
A
6
2280
2759
4,26
86
LWA as per ISO 13347,
A
7
2280
3058
4,70
85
LpA measured at 1 m distance
A
8
2280
2884
4,44
89
A
9
1815
893
1,38
91
A
10
1815
1392
2,15
81
A
11
1815
1543
2,37
80
A
12
1815
1455
2,24
84
without protection against
6,4
accidental contact
to fan axis
8
4,8
1200
The acoustic values given are
7
2
only valid under the measurment conditions listed and may vary depending on the
3,2
800
12
installation situation.
6 11
With any deviation to the standard setup, the specific values
1,6
10
400
have to be checked and reviewed once installed or fitted! For detailed information
psf
9 0
qV
42
1000
2000
2000
4000
LWA dB(A)
1
Installation category A,
3
I A
A
with ebm-papst inlet nozzle
1600
Pe W
A
as per: ISO 5801,
4
n rpm
3000
4000
6000
5000
8000
5 6000
10000
see page 66 ff.
1 7000
cfm
12000
m3/h
19.05.2011
Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay
Masse centrifugal fan Centrifugal fan
kg
R3G 450-AZ30 -01
31,1
Seite 43
• • • •
Mass of centrifugal module with support bracket
– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST
11:33
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
45075-1-4013
K3G 450-AZ30 -01
52,7
K3G 450-AZ30 -31
52,7
(2) Centrifugal module with higher protection against corrosion
113
406.5±3 293.5±2
Depth of screw max. 20 mm
6xØ9
R3G 450-AZ30 -01
76 6xM10
6x6
Ø430 Ø480
Ø303.4
Ø317 Ø505
Ø188
0˚
Tightening torque 3.5±0.5 Nm
Ø280-2
Cable gland M20x1,5(2x)
112 176
9
Ø304±0.5
Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
Cable gland M25x1,5(1x) 469 ±3 355.5 ±2
Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm
o630-1 o520.5
15
Ø11(8x)
K3G 450-AZ30 -01 / -31
o580
Pressure tap
43 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:33
Seite 44
EC centrifugal fan and modules backward curved, Ø 500
subject to alterations
Perm. amb. temp.
Electr. connection
M3G 150-FF
Max. current draw(1)
*3G 500
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
1780
2825
4,30
-25..+60
3~ 380-480
A
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
Pa
in H2O
Curves A
Air performance measured
1780
1985
3,09
94
2
1780
2530
3,90
89
A
3
1780
2825
4,30
83
A
4
1780
2692
4,14
85
A
5
1475
1094
1,70
90
Suction-side noise levels:
A
6
1475
1411
2,18
84
LWA as per ISO 13347,
A
7
1475
1602
2,47
79
LpA measured at 1 m distance
A
8
1475
1484
2,28
80
A
9
1175
553
0,86
85
A
10
1175
714
1,10
80
A
11
1175
810
1,25
74
A
12
1175
750
1,15
75
Installation category A,
4,0
without protection against
3,2
3
8
to fan axis
2,4
600
The acoustic values given are 7
only valid under the measurment conditions listed and may vary depending on the
12
2
1,6
400
installation situation.
11
With any deviation to the stan-
6
dard setup, the specific values have to be checked and re-
0,8
200
10
viewed once installed or fitted!
psf
For detailed information 0
qV
44
1000
2000
2000
4000
LWA dB(A)
1
accidental contact
800
I A
A
with ebm-papst inlet nozzle
1000
Pe W
A
as per: ISO 5801, 4
n rpm
3000
4000
6000
9 5000
8000
5 6000
10000
see page 66 ff.
1 7000
12000
cfm m3/h
19.05.2011
Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay
Masse centrifugal fan Centrifugal fan
kg
R3G 500-AP25 -01
24,6
Seite 45
• • • •
Mass of centrifugal module with support bracket
– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST
11:34
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
64025-2-4013
K3G 500-AP25 -01
40,2
K3G 500-AP25 -31
40,2
(2) Centrifugal module with higher protection against corrosion
75
6xØ9
373.5 ±3 303.5 ±2
70
R3G 500-AP25 -01
Depth of screw max. 25 mm 14xM10
6x6
0˚
Ø445 Ø470
Ø566
Ø337.2
Ø352.5
22.5˚
Ø188
˚
45
8x
220.5±1
Ø232-2
Ø252±0,3 Ø275
12
150 220
Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
K3G 500-AP25 -01 / -31 431.5±3 361.5±2
15
Tightening torque 3.5±0.5 Nm
o630-1 o551
Ø11 (8x)
M 2 (3 0x1 x) .5
Ø566
Observe the correct mounting position ! Install the support struts only vertically as shown in the view !
o580
Pressure tap
45 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 46
EC centrifugal fan and modules backward curved, Ø 500
Electr. connection
A
Perm. amb. temp.
M3G 150-IF
Max. current draw(1)
*3G 500
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
2200
5500
8,40
-25..+45
3~ 380-480
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
subject to alterations
Pa
A
Air performance measured
2200
3725
5,82
100
2200
4944
7,64
94
A
3
2200
5500
8,40
89
A
4
2200
5148
7,95
90
A
5
1825
2039
3,19
95
Suction-side noise levels:
A
6
1825
2736
4,23
90
LWA as per ISO 13347,
A
7
1825
3052
4,70
84
LpA measured at 1 m distance
A
8
1825
2830
4,37
86
A
9
1465
1055
1,65
91
A
10
1465
1416
2,19
85
A
11
1465
1578
2,43
80
A
12
1465
1464
2,26
81
5,6
accidental contact
4,8
1200
8
to fan axis
4,0
1000
The acoustic values given are
7
only valid under the measur-
3,2
800
ment conditions listed and
2 12
may vary depending on the installation situation.
2,4
600
11 6
1,6
With any deviation to the stan-
400
dard setup, the specific values 10
have to be checked and reviewed once installed or fitted!
0,8
200
psf
For detailed information 0
qV
46
2000
2000
4000
LWA dB(A)
2
without protection against
3
I A
1
with ebm-papst inlet nozzle
1400
Pe W
A
Installation category A,
4
n rpm A
as per: ISO 5801,
6,4
1600
in H2O
Curves
4000
6000
8000
9 6000
5
10000
12000
see page 66 ff.
1 8000
14000
cfm m3/h
19.05.2011
Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay
Masse centrifugal fan Centrifugal fan
kg
R3G 500-AQ33 -01
33,2
Seite 47
• • • •
Mass of centrifugal module with support bracket
– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST
11:34
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
64025-2-4013
K3G 500-AQ33 -01
55,9
K3G 500-AQ33 -31
55,9
(2) Centrifugal module with higher protection against corrosion
450.5±3 337.5±2
113
Depth of screw max. 20 mm
6xØ9
R3G 500-AQ33 -01
75 6xM10
298.5±1
Ø445 Ø470
Ø337
Ø352.5 Ø566
Ø188
0˚
6x6
Ø280-2
Cable gland M20x1,5(2x)
150 220.5
12
Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm
Ø304±0.5
Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
Cable gland M25x1,5(1x) 510 ±3 396.5 ±2
Tightening torque 3.5±0.5 Nm
o630-1 o520.5
15
Ø11(8x)
K3G 500-AQ33 -01 / -31
o580
Pressure tap
47 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 48
EC centrifugal fan and modules backward curved, Ø 560
subject to alterations
Electr. connection
A
Perm. amb. temp.
M3G 150-IF
Max. current draw(1)
*3G 560
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
1500
3000
4,60
-25..+50
3~ 380-480
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
Pa
in H2O
Curves A
Air performance measured
1500
1952
2,98
90
2
1500
2481
3,77
86
A
3
1500
3000
4,60
80
A
4
1500
2754
4,18
83
A
5
1250
1101
1,68
86
Suction-side noise levels:
A
6
1250
1420
2,16
82
LWA as per ISO 13347,
A
7
1250
1712
2,60
76
LpA measured at 1 m distance
A
8
1250
1560
2,37
78
A
9
1000
564
0,86
81
A
10
1000
727
1,10
77
A
11
1000
876
1,33
71
A
12
1000
799
1,21
74
4,0
accidental contact
3
to fan axis
2,4
8
600
The acoustic values given are only valid under the measurment conditions listed and
7
may vary depending on the 12
1,6
400
installation situation. 2 11
With any deviation to the standard setup, the specific values
6
have to be checked and re-
0,8
200
viewed once installed or fitted!
10
For detailed information
psf
9 0
qV
48
2000
2000
4000
4000
6000
10000
8000
12000
see page 66 ff.
1
5 6000
8000
LWA dB(A)
1
without protection against
3,2
800
I A
A
with ebm-papst inlet nozzle 4
Pe W
A
as per: ISO 5801, Installation category A,
1000
n rpm
14000
cfm m3/h
19.05.2011
Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay
Masse centrifugal fan Centrifugal fan
kg
R3G 560-AP23 -01
30,5
Seite 49
• • • •
Mass of centrifugal module with support bracket
– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST
11:34
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
64030-2-4013
K3G 560-AP23 -01
56,1
K3G 560-AP23 -31
56,1
(2) Centrifugal module with higher protection against corrosion
82
6xØ9
422 ±3 352 ±2
70
R3G 560-AP23 -01
Depth of screw max. 25 mm 14xM10
6x6
0˚
Ø490 Ø515
Ø385
Ø636
Ø395
22.5˚
Ø188
˚
45
8x
250.5±1
Ø232-2
Ø252±0,3 Ø275
16
160 239
Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
K3G 560-AP23 -01 / -31 483±3 413±2
15
Tightening torque 3.5±0.5 Nm
o800-1 o555
Ø11 (8x)
M 2 (3 0x1 x) .5
Ø566
Observe the correct mounting position ! Install the support struts only vertically as shown in the view !
o750
Pressure tap
49 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 50
EC centrifugal fan and modules backward curved, Ø 560
Perm. amb. temp.
Electr. connection
M3G 150-NA
Max. current draw(1)
*3G 560
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support bracket: Steel, coated in black Support plate: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
1750
4700
7,30
-25..+40
3~ 380-480
A
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
subject to alterations
Pa
1400
in H2O
Curves A
Air performance measured
1750
3032
4,77
97
2
1750
3929
6,10
91
A
3
1750
4700
7,30
84
A
4
1750
4366
6,71
86
A
5
1450
1675
2,64
93
Suction-side noise levels:
A
6
1450
2171
3,37
87
LWA as per ISO 13347,
A
7
1450
2602
4,01
80
LpA measured at 1 m distance
A
8
1450
2432
3,74
82
A
9
1150
836
1,32
88
A
10
1150
1083
1,68
82
A
11
1150
1298
2,00
75
A
12
1150
1213
1,87
76
4,8
without protection against
4,0
accidental contact
3
to fan axis
3,2
8
800
The acoustic values given are only valid under the measur-
7
ment conditions listed and
2,4
600
may vary depending on the 12
installation situation.
2 11
1,6
400
With any deviation to the stan6
dard setup, the specific values have to be checked and re-
10
0,8
200
viewed once installed or fitted! For detailed information
psf
9 0
qV
50
2000
4000
LWA dB(A)
1
with ebm-papst inlet nozzle
1000
I A
A
Installation category A,
1200
Pe W
A
as per: ISO 5801,
4
n rpm
4000
6000
8000
cfm
8000
12000
see page 66 ff.
1
5
16000
m3/h
19.05.2011
Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay
Masse centrifugal fan Centrifugal fan
kg
R3G 560-AQ04 -01
40,0
Seite 51
• • • •
Mass of centrifugal module with support bracket
– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST
11:34
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with support bracket
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
Inlet nozzle with one pressure tap
Centrifugal module w. support bracket
kg
Centrifugal module w. supp. bracket (2)
kg
64030-2-4013
K3G 560-AQ04 -01
69,7
K3G 560-AQ04 -31
69,7
(2) Centrifugal module with higher protection against corrosion
505±3 392±2
113
Depth of screw max. 20 mm
6xØ9
R3G 560-AQ04 -01
82 6xM10
333±1
Ø490 Ø515
Ø385
Ø395 Ø636
Ø188
0˚
6x6
Ø280-2
Cable gland M20x1,5(2x)
160 239
16
Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm
Ø304±0.5
Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
Cable gland M25x1,5(1x) 566 ±3 453 ±2
Tightening torque 3.5±0.5 Nm
o800-1 o570
15
Ø11(8x)
K3G 560-AQ04 -01 / -31
o750
Pressure tap
51 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 52
EC centrifugal fan and modules backward curved, Ø 630
subject to alterations
Perm. amb. temp.
Electr. connection
M3G 200-HF
Max. current draw(1)
*3G 630
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support structure: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
1450
6140
9,90
-25..+40
3~ 380-480
A
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
Pa
1200
4,8 in H2O
Curves A
Air performance measured
1450
4116
6,75
95
2
1450
5426
8,70
88
A
3
1450
6140
9,90
84
A
4
1450
4956
7,95
87
A
5
1200
2314
3,79
90
Suction-side noise levels:
A
6
1200
3050
4,89
84
LWA as per ISO 13347,
A
7
1200
3450
5,54
80
LpA measured at 1 m distance
A
8
1200
2792
4,48
83
A
9
960
1185
1,94
86
A
10
960
1562
2,50
79
A
11
960
1766
2,83
75
A
12
960
1429
2,29
78
with ebm-papst inlet nozzle
4,0
accidental contact 3
8
LWA dB(A)
1
Installation category A,
3,2
800
I A
A
without protection against
1000
Pe W
A
as per: ISO 5801, 4
n rpm
to fan axis 7
600
2,4
The acoustic values given are only valid under the measurment conditions listed and 12
installation situation.
11
1,6
400
may vary depending on the
2
6
With any deviation to the standard setup, the specific values have to be checked and re-
10
0,8
200
viewed once installed or fitted! For detailed information
psf
9 0
qV
52
2000
4000
4000
8000
6000
8000
12000
10000
16000
see page 66 ff.
1
5 12000
cfm
20000
m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
11:34
Seite 53
Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay
Masse centrifugal fan kg
R3G 630-AQ01 -01
61,0
Inlet nozzle with one pressure tap
Centrifugal module with support structure
64040-2-4013
K3G 630-AQ01 -01
533±3 420±2
113
R3G 630-AQ01 -01
6xØ10.5
Centrifugal fan
• • • •
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
Mass of centrifugal module with supporting construction
– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST applied for
19.05.2011
kg 105,0
Depth of screw max. 20 mm 98.5
Tightening torque 3.5±0.5 Nm Ø600 Ø634
Ø436.8 (Ø427)
Ø325
Ø444 Ø716
8xM10
8x45˚
Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm
224 318
Ø280-2 304 ±0.5
12
Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
Cable gland M20x1,5(2x) Cable gland M25x1,5(1x)
o760 -10
B-B
400±3
40
433 ±2
30
K3G 630-AQ01 -01
15
20
Observe the correct mounting position ! Install only as shown in the view !
813 ±2
Ø11(8x)
o660 ±1
B
B
10.5 710 ±2 760 ±2
540 630 ±2 670 ±5
80 ±2
53 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 54
EC centrifugal fan and modules backward curved, Ø 710
subject to alterations
Perm. amb. temp.
Electr. connection
M3G 200-LA
Max. current draw(1)
*3G 710
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support structure: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
1200
6240
10,00
-25..+40
3~ 380-480
A
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
Pa
in H2O
Curves A
Air performance measured
1200
4060
6,70
96
2
1200
5561
8,94
89
A
3
1200
6240
10,00
83
A
4
1200
4999
8,12
85
A
5
1000
2332
3,85
92
Suction-side noise levels:
A
6
1000
3202
5,15
85
LWA as per ISO 13347,
A
7
1000
3590
5,73
79
LpA measured at 1 m distance
A
8
1000
2872
4,67
81
A
9
790
1150
1,90
87
A
10
790
1579
2,54
80
A
11
790
1770
2,83
74
A
12
790
1416
2,30
76
4,0
without protection against
3,2
3
8
to fan axis
2,4
600
The acoustic values given are
7
only valid under the measurment conditions listed and may vary depending on the
2
12
installation situation.
1,6
400
11 6
With any deviation to the stan-
0,8
dard setup, the specific values
200
have to be checked and re-
10
viewed once installed or fitted!
psf
For detailed information 0
qV
54
2000
4000
4000
8000
LWA dB(A)
1
accidental contact
800
I A
A
with ebm-papst inlet nozzle
4
Pe W
A
as per: ISO 5801, Installation category A,
1000
n rpm
6000
8000
12000
9 10000
16000
12000
20000
see page 66 ff.
1
5 14000
24000
cfm m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
11:34
Seite 55
Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay
Masse centrifugal fan Centrifugal fan
kg
R3G 710-AQ01 -01
73,0
Inlet nozzle with one pressure tap
Centrifugal module with support structure
71075-2-4013
K3G 710-AQ01 -01
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
kg 130,0
594±3 481±2
113
Depth of screw max. 20 mm 6xØ9
R3G 710-AQ01 -01
• • • •
Mass of centrifugal module with supporting construction
– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST applied for
19.05.2011
117
Tightening torque 3.5±0.5 Nm Ø700 Ø720
Ø492.6 (Ø470.3)
Ø325
Ø501 Ø808
8xM10
8x45˚
Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm
250 354
Ø280-2 304 ±0.5
15
Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
Cable gland M20x1,5(2x) Cable gland M25x1,5(1x)
o960 -10
B-B
450±3
40
543 ±2
30
K3G 710-AQ01 -01
15
25
Observe the correct mounting position ! Install only as shown in the view !
1023 ±2
Ø11(8x)
o750 ±1
B
B
10.5 910 ±2 960 ±2
560 630 ±2 680 ±5
95 ±2
55 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 56
EC centrifugal fan and modules backward curved, Ø 800
subject to alterations
Perm. amb. temp.
Electr. connection
M3G 200-QA
Max. current draw(1)
*3G 800
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support structure: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
960
5800
9,40
-25..+40
3~ 380-480
A
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
n rpm
Pa
A
Air performance measured
960
3763
6,21
91
2
960
5067
8,20
85
A
3
960
5800
9,40
79
A
4
960
5306
8,53
81
A
5
800
2193
3,62
87
Suction-side noise levels:
A
6
800
2994
4,84
81
LWA as per ISO 13347,
A
7
800
3413
5,50
75
LpA measured at 1 m distance
A
8
800
3107
4,99
77
A
9
630
1071
1,77
82
A
10
630
1462
2,36
76
A
11
630
1667
2,69
70
A
12
630
1517
2,44
72
without protection against 2,8
accidental contact
2,4
3
600
8
to fan axis
2,0
500
7
The acoustic values given are only valid under the measur-
1,6
400
ment conditions listed and 2
12
may vary depending on the installation situation.
1,2
300
11 6
With any deviation to the stan-
0,8
200
dard setup, the specific values have to be checked and re-
10
viewed once installed or fitted!
0,4
100
For detailed information
psf
9 0
qV
56
LWA dB(A)
1
with ebm-papst inlet nozzle
700
I A
A
Installation category A,
4
Pe W
A
as per: ISO 5801,
3,2
800
in H2O
Curves
4000
5000
8000
10000
15000
12000
20000
25000
see page 66 ff.
1
5 16000
cfm
30000
m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
11:34
Seite 57
Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay
Masse centrifugal fan Centrifugal fan
kg
R3G 800-AQ03 -01
97,0
Inlet nozzle with one pressure tap
Centrifugal module with support structure
80075-2-4013
K3G 800-AQ03 -01
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
kg 158,0
656±3 543±2
113
Depth of screw max. 20 mm 6xØ9
R3G 800-AQ03 -01
• • • •
Mass of centrifugal module with supporting construction
– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST applied for
19.05.2011
131
Tightening torque 3.5±0.5 Nm Ø700 Ø720
Ø555.3 (Ø529.7)
Ø325
Ø565 Ø909
8xM10
8x45˚
Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm
280 396
Ø280-2 304 ±0.5
20
Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
Cable gland M20x1,5(2x) Cable gland M25x1,5(1x)
o960 -10
B-B
502±3
40
543 ±2
30
K3G 800-AQ03 -01
15
25
Observe the correct mounting position ! Install only as shown in the view !
1023 ±2
Ø11(8x)
o750 ±1
B
B
10.5 910 ±2 960 ±2
700 840 ±2 890 ±5
87±2
57 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 58
EC centrifugal fan and modules backward curved, Ø 900
subject to alterations
Electr. connection
A
Perm. amb. temp.
M3G 200-QA
Max. current draw(1)
*3G 900
Max. input power(1)
Motor
Speed/rpm(1)
Type
Frequency
Nominal data
Nominal voltage range
Curve
– Material: Support structure: Sheet steel, hot-galvanised Impeller: Sheet aluminium, welded Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings
VAC
Hz
rpm
W
A
°C
p. 64
50/60
800
5950
9,50
-25..+40
3~ 380-480
L5)
(1) Nominal data in operating point with maximum load and 400 VAC
n rpm
Pa
A
Air performance measured
800
3732
6,14
91
2
800
5512
8,86
83
A
3
800
5950
9,50
78
A
4
800
4991
8,02
79
A
5
665
2129
3,50
87
Suction-side noise levels:
A
6
665
3144
5,05
79
LWA as per ISO 13347,
A
7
665
3397
5,42
74
LpA measured at 1 m distance
A
8
665
2847
4,58
75
A
9
530
1078
1,77
82
A
10
530
1591
2,56
74
A
11
530
1720
2,74
69
A
12
530
1441
2,32
70
with ebm-papst inlet nozzle
2,4
accidental contact
2,0
3
500
8
LWA dB(A)
1
without protection against
600
I A
A
Installation category A,
4
Pe W
A
as per: ISO 5801,
2,8
700
in H2O
Curves
400
1,6
to fan axis The acoustic values given are
7
only valid under the measur2 1,2
300
ment conditions listed and
12
may vary depending on the installation situation. 11
6
With any deviation to the stan-
0,8
200
dard setup, the specific values 10
have to be checked and reviewed once installed or fitted!
0,4
100
psf
For detailed information 0
qV
58
5000
5000
10000
10000
15000
20000
9 15000
5
25000
30000
see page 66 ff.
1 20000
35000
cfm m3/h
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
Seite 59
Slave output 0-10 V max. 3 mA Output 20 VDC (±20 %) max. 50 mA Output 10 VDC (+10 %) max. 10 mA RS485 MODBUS Motor current limitation, Alarm relay
Masse centrifugal fan Centrifugal fan
kg 107,0
R3G 900-AQ01 -01
113
Inlet nozzle with one pressure tap
Centrifugal module with support structure
90075-2-4013
K3G 900-AQ01 -01
Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Digital inputs for day/night switch, enabling, cooling / heating
kg 194,0
596±3 483±2
Depth of screw max. 20 mm 6xØ9
R3G 900-AQ01 -01
• • • •
Mass of centrifugal module with supporting construction
– Technical features: • • PFC (passive) • • Integrated PID controller • • Control input 0-10 VDC bzw. 4-20 mA • • Input for sensor 0-10 V or 4-20 mA • – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Leakage current: < 3,5 mA acc. to EN 61800-5-1 – Connection leads: Via terminal strip – Protection class: I (acc. to EN 61800-5-1) – Product conforming to standards: CE – Approvals: UL, CSA, GOST applied for
11:34
148
Tightening torque 3.5±0.5 Nm Ø850 Ø900
Ø624.7 (Ø595.9)
Ø325
Ø635 Ø1010
8xM10
8x45˚
Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm 15
Cable gland M20x1,5(2x) Cable gland M25x1,5(1x) Ø11(12x)
o950 ±1 o400 ±1
565 ±3
o1180 -10
B-B
Ø280-2 304 ±0.5
Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm
40
660 ±2
30
K3G 900-AQ01 -01
15
30
Observe the correct mounting position ! Install only as shown in the view !
1250 ±2
310 439
B
B
10.5 1130 ±2 1180 ±2
640 840 ±2 900 ±5
97±2
59 Guard grille p. 60
Inlet nozzle p. 60
Electr. connection p. 64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 60
Accessories Vers. 1
- Material: sheet steel, plastic coated, silver-metallic gloss
Vers. 2
a
Ød
Ød
a
e
b
e
b
Air intake guard grilles for backward curved centrifugal fans (according to EN 294) Part no.
Size
Vers.
a
b
d
e
Strut pitch
78129-2-4039
250
1
260
4,5
191
2,8
4 x 90°
78130-2-4039
280
1
280
4,5
229
2,8
4 x 90°
78131-2-4039
310
1
325
4,5
248
2,8
4 x 90°
78132-2-4039
355
1
345
4,5
305
2,8
4 x 90°
78133-2-4039
400
2
390
8,5
343
3,8
3 x 120°
78134-2-4039
450
2
430
8,5
381
3,8
3 x 120°
78139-2-4039
500
2
445
8,5
410
3,8
3 x 120°
78137-2-4039
560
2
490
8,5
430
3,8
3 x 120°
subject to alterations
Vers. 1
- Material: galvanised sheet steel
Vers. 2
6x6
0˚
˚
90
4x
Inlet nozzles without measuring device for backward curved centrifugal fans Part no.
Size
Vers.
25070-2-4013
250
1
page 11
28070-2-4013
280
1
page 15
31570-2-4013
310
1
page 21
35670-2-4013
355
1
page 29
40070-2-4013
400
2
page 35
45070-2-4013
450
2
page 39
63072-2-4013
500
2
page 45
63071-2-4013
560
2
page 49
63070-2-4013
630
2
page 53
71070-2-4013
710
2
page 55
80070-2-4013
800
2
page 57
90070-2-4013
900
2
page 59
subject to alterations
60
For dimensions, see
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 61
Accessories Effects of installation space
Curve
When mounting our product in a rectangular box, air performance might be reduced.
1,00
B
Formula: dh = 2 x B x H / (B + H) B = Width of box
0,93
0,94
0,95
0,96
dh = Hydraulic diameter
0,92
Correction factor for air flow
D
H
0,5xD
D
0,97
0,98
0,99
D
1,4
1,6
1,8
2,0
2,2
2,4
2,6
2,8
Hydraulic diameter dh/D
H = Height of box D = Outer diameter of the fan
Air flow determination:
The differential pressure approach compares the static pressure before the inlet nozzle with the static pressure inside the inlet nozzle. Air flow can be calculated on the basis of the differential pressure (difference in pressure of the static pressures) in keeping with the following equation: qV = k . ∆p
0,5xD
qV in [m3/h] and ∆p in [Pa]
D
If constant air flow is to be controlled to, then the nozzle pressure has to be kept constant: ∆p = qV2 : k2
∆p
k takes into account the specific nozzle characteristics. Differences in static pressure are measured in 1/4 measuring point(s) along the circumference of the inlet nozzle. Connection on the customer side is acomplished via a pre-mounted T tube connector. This tube connector is suited for pneumatic hoses with an internal diameter of 4 mm.
Inlet nozzles with measuring device to determine air flow for backward curved centrifugal fans Part no.
Part no.
Size
k-value
For dimensions, see
25075-2-4013(1) / 25080-2-4013(2)
250
70
page 11
28075-2-4013(1) / 28080-2-4013(2)
280
93
page 15
(2)
310
116
page 21
35675-2-4013(1) / 35680-2-4013(2)
355
148
page 29
40075-2-4013(1) / 40080-2-4013(2)
400
188
page 35
(2)
450
240
page 39
64025-2-4013(1) / 64002-2-4013(2)
500
281
page 45
64030-2-4013(1) / 64001-2-4013(2)
560
348
page 49
(2)
630
438
page 53
71075-2-4013(1) / 71080-2-4013(2)
710
545
page 55
80075-2-4013(1) / 80080-2-4013(2)
800
695
page 57
900
page 59
(1)
31575-2-4013
(1)
45075-2-4013
(1)
64040-2-4013
(1)
90075-2-4013
/ 31580-2-4013
/ 45080-2-4013
/ 64000-2-4013
(2)
/ 90080-2-4013
subject to alterations
900 (1)
with one pressure tap
(2)
with piezometer ring (4 pressure taps connected by tubing)
61
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 62
Electrical connections EC
K1) Notes on various control possibilities and their applications Umin = 15 V Imax = 10 mA
Mains 50/60 Hz
L black N blue PE green/yellow
+ -
NC white1
+ white2 Voltage output red +10 V max. 1.1 mA
U
PWM
-
10 K 12 V
Alarm relay: Break for failure (2 A, 250 VAC, AC1)
Lin/PWM control input yellow 0-10 VDC / PWM 1 µF
GND blue Speed setting PWM 1 - 10 kHz
Speed setting with variable resistance
Full speed
Speed setting 1 V - 10 V
100% PWM -> n=max approx. 10% PWM -> n=min < 10% PWM -> n=0
10 V -> n=max approx. 1 V -> n=min < 1 V -> n=0
start up at > 14 %
start up at > 1.4 V
Customer circuit
Connection
+10 V
0-10 V PWM
GND
green/yellow white1
COM
blue
Line 2 NC
N
black
PE
L
Line 1
Fan
white2
red
yellow
blue
Line
Connection Colour Assignment / function
Line
1
L
black
Mains 50/60 Hz, phase
2
N
blue
Mains 50/60 Hz, neutral
0-10 V / PWM yellow
Control input (Impedance 100 kΩ)
PE
green/yel
Protective earth
GND
GND
NC
white1
Alarm relay, break for failure
COM
white2
Alarm relay, COMMON
62
Connection Colour Assignment / function +10 V
red blue
Voltage output +10 V max. 1.1 mA
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 63
L6)
PE
L2
L1
L3
KL1 NC
COM
NO
OUT
GND
+10 V
0-10 V PWM
+20 V
KL2 4-20 mA
GND
0-10 V PWM
RS B
RS A
RS B
RS A
KL3
Connector Connection Assignment / function
Connector Connection Assignment / function
PE
PE
Protective earth
KL3
OUT
Master output 0-10 V max. 3 mA
KL1
L3
Mains; L3
GND
GND
L2
Mains; L2
0-10 V / PWM Control / Actual value input (Impedance 100 kΩ)
L1
Mains; L1
+10 V
NC
Alarm relay, break for failure
COM
Alarm relay, COMMON (2A, 250 VAC, AC1)
NO
Alarm relay, make for failure
KL2
Supply for external potentiometer, 10 VDC (+10 %) max. 10 mA
+20 V
Supply for external sensor, 20 VDC (±20 %) max. 50 mA
4-20 mA
Control / Actual value input
0-10 V / PWM Control / Actual value input GND
GND
RSB
RS485 interface for MODBUS RTU; RS B
RSA
RS485 interface for MODBUS RTU; RS A
RSB
RS485 interface for MODBUS RTU; RS B
RSA
RS485 interface for MODBUS RTU; RS A
L7)
PE
L
N
KL1 NC
COM
NO
OUT
GND
+10 V
0-10 V PWM
+20 V
KL2 4-20 mA
GND
0-10 V PWM
RS B
RS A
RS B
RS A
KL3
Connector Connection Assignment / function
Connector Connection Assignment / function
PE
PE
Protective earth
KL3
OUT
Master output 0-10 V max. 3 mA
KL1
N
Mains 50/60 Hz. neutral
GND
GND
L
Mains 50/60 Hz, phase
0-10 V / PWM Control / Actual value input (Impedance 100 kΩ)
NC
Alarm relay, break for failure
+10 V
COM
Alarm relay, COMMON (2A, 250 VAC, AC1)
NO
Alarm relay, make for failure
KL2
Supply for external potentiometer, 10 VDC (+10 %) max. 10 mA
+20 V
Supply for external sensor, 20 VDC (±20 %) max. 50 mA
4-20 mA
Control / Actual value input
0-10 V / PWM Control / Actual value input GND
GND
RSB
RS485 interface for MODBUS RTU; RS B
RSA
RS485 interface for MODBUS RTU; RS A
RSB
RS485 interface for MODBUS RTU; RS B
RSA
RS485 interface for MODBUS RTU; RS A
63
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 64
Electrical connections EC
L5)
L3
Aout Din1
L2
Ain2 I Ain1 I
L1
+20 V +10 V
PE
Ain2 U Ain1 U
KL1
NC
GND GND
COM
Din3 RS B
NO
Din2
KL2
RS A
KL3
Connector Connection Assignment / function
Connector Connection Assignment / function
KL1
KL3
L3
Mains; L3
L2
Mains; L2
L1
Mains; L1
PE
PE
Protective earth
KL2
NC
Alarm relay, break for failure
COM
Alarm relay, COMMON (2A, 250 VAC, AC1)
NO
Alarm relay, make for failure
Din1
Digital input 1 (enabling / disabling of electronics),, Enabling: Pin open or applied voltage 5...50 VDC Disabling: Bridge to GND or applied voltage < 1 VDC
Ain1 I
Analogue set value input, 4-20 mA (impedance 100 Ω),
+10 V
Supply for external potentiometer,
only to be used as alternative to terminal Ain1 U 10 VDC (±3 %) max. 10 mA Ain1U
Analogue set value input, 0-10 V (impedance 100 kΩ),
GND
GND
RSB
RS485 interface for MODBUS RTU; RS B
RSA
RS485 interface for MODBUS RTU; RS A
Aout
Analogue output 0-10 V max. 5 mA, reading of current
only to be used as alternative to terminal Ain1 I
motor speed / current motor control factor Ain2 I
Analog. actual value input, 4-20mA (impedance 100Ω),
+20 V
Supply for external sensor,
only to be used as alternative to terminal Ain2 U 20 VDC (+25 % / -10%) max. 40 mA Ain2 U
Analog. actual value input, 0-10 V (impedance 100 kΩ),
GND
GND
Din3
Digital input 3 (switch Normal / Inverse),
only to be used as alternative to terminal Ain2 I
The preset effective direction of the integrated controller can be selected via BUS or via digital input Normal/Inverse. Normal: Pin open or applied voltage 5...50 VDC Inverse: Bridge to GND or applied voltage < 1 VDC Din2
Digital input 2 (switch Day / Night), The preset set of parameters can be selected via BUS or via digital input Day/Night. Day: Pin open or applied voltage 5...50 VDC Night: Bridge to GND or applied voltage < 1 VDC
64
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 65
L9) Aout Din1
N
Ain2 I Ain1 I
L1
+20 V +10 V
PE
Ain2 U Ain1 U
KL1
NC
GND GND
COM
Din3 RS B
NO
Din2
KL2
RS A
KL3
Connector Connection Assignment / function
Connector Connection Assignment / function
KL1
KL3
N
Mains; neutral
L1
Mains; L1
PE
PE
Protective earth
KL2
NC
Alarm relay, break for failure
COM
Alarm relay, COMMON (2A, 250 VAC, AC1)
NO
Alarm relay, make for failure
Din1
Digital input 1 (enabling / disabling of electronics),, Enabling: Pin open or applied voltage 5...50 VDC Disabling: Bridge to GND or applied voltage < 1 VDC
Ain1 I
Analogue set value input, 4-20 mA (impedance 100 Ω),
+10 V
Supply for external potentiometer,
only to be used as alternative to terminal Ain1 U 10 VDC (±3 %) max. 10 mA Ain1U
Analogue set value input, 0-10 V (impedance 100 kΩ),
GND
GND
RSB
RS485 interface for MODBUS RTU; RS B
RSA
RS485 interface for MODBUS RTU; RS A
Aout
Analogue output 0-10 V max. 5 mA, reading of current
only to be used as alternative to terminal Ain1 I
motor speed / current motor control factor Ain2 I
Analog. actual value input, 4-20mA (impedance 100Ω),
+20 V
Supply for external sensor,
only to be used as alternative to terminal Ain2 U 20 VDC (+25 % / -10%) max. 40 mA Ain2 U
Analog. actual value input, 0-10 V (impedance 100 kΩ),
GND
GND
Din3
Digital input 3 (switch Normal / Inverse),
only to be used as alternative to terminal Ain2 I
The preset effective direction of the integrated controller can be selected via BUS or via digital input Normal/Inverse. Normal: Pin open or applied voltage 5...50 VDC Inverse: Bridge to GND or applied voltage < 1 VDC Din2
Digital input 2 (switch Day / Night), The preset set of parameters can be selected via BUS or via digital input Day/Night. Day: Pin open or applied voltage 5...50 VDC Night: Bridge to GND or applied voltage < 1 VDC
65
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 66
Technical parameters & scope
High standards for all ebm-papst products Here at ebm-papst, we constantly strive to further improve our products in order to be able to offer you the best possible product for your application. Careful monitoring of the market ensures that technical innovations are reflected in the improvements of our products. Based on the technical parameters listed below and the ambience you want our product to operate in, we here at ebm-papst can always work out the best solution for your specific application.
General performance parameters
Service life
Any deviations from the technical data and parameters described here
The service life of ebm-papst products depends on two major factors:
are listed on the product-specific data sheet.
– The service life of the insulation system – The service life of the bearing system
Type of protection
The service life of the insulation system mainly depends on voltage level,
The type of protection is specified in the product-specific data sheets.
temperature and ambient conditions, such as humidity and condensation. The service life of the bearing system depends mainly on the thermal load
Insulation class
on the bearing.
The insulation class is specified in the product-specific data sheets.
The majority of our products use maintenance-free ball bearings for any mounting position possible. As an option, sleeve bearings can be
Mounting position
used, which is indicated on the product-specific data sheet wherever
The mounting position is specified in the product-specific data sheets.
applicable. The service life L10 of the ball bearings can be taken as approx. 40,000
Condensate discharge holes
operating hours at an ambient temperature of 40 °C, yet this estimate
Information on the condensate discharge holes is provided in the
can vary according to the actual ambient conditions.
product-specific data sheets.
We will gladly provide you with a lifetime calculation taking into account your specific operating conditions.
Mode of operation The mode of operation is specified in the product-specific data sheets.
Motor protection / thermal protection Information on motor protection and thermal protection is provided in the
Protection class
product-specific data sheets.
The protection class is specified in the product-specific data sheets.
Depending on motor type and field of application, the following protective features are realised: – Thermal overload protection (TOP), either in-circuit or external – PTC with electronic diagnostics – Impedance protection – Thermal overload protection (TOP) with electronic diagnostics – Current limitation via electronics If an external TOP is connected, the customer has to make sure to connect a conventional trigger device for switching it off. Products without fitted TOP and without protection against improper use, a motor protection complying with the valid standards has to be installed.
66
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 67
Left: Endurance test room Middle: Shock test Right: Chamber test rig
Mechanical strain / performance parameters
Legal and normative directives
All ebm-papst products are subjected to comprehensive tests complying
The products described in this catalogue are designed, developed and
with the normative specifications. In addition to this, the tests also reflect
produced in keeping with the standards in place for the relevant product
the vast experience and expertise of ebm-papst.
and, if known, the conditions governing the relevant fields of application.
Vibration test
Standards
Vibration tests are carried out in compliance with
Information on standards is provided in the product-specific data sheets.
– Vibration test in operation according to DIN IEC 68, parts 2-6 – Vibration test at standstill according to DIN IEC 68, parts 2-6
EMC Information on EMC standards is provided in the product-specific data
Shock load
sheets.
Shock load tests are carried out in compliance with
Complying with the EMC standards has to be established on the final
– Shock load according to DIN IEC 68, parts 2-27
appliance, as different mounting situations can result in changed EMC properties.
Balancing quality Testing the balancing quality is carried out in compliance with
Leakage current
– Residual imbalance according to DIN ISO 1940
Information on the leakage current is provided in the product-specific
– Standard balancing quality level G 6.3
data sheets.
Should you require a higher balancing quality level for your specific
Measuring is according to IEC 60990.
application, please let us know and specify this when ordering your product.
Approvals In case you require a specific approval for your ebm-papst product
Chemo-physical strain / performance parameters
(VDE, UL, GOST, CCC, CSA, etc.) please let us know.
Should you have questions about chemo-physical strain, please direct
Most of our products can be supplied with the relevant approval.
them to your ebm-papst contact.
Information on existing approvals is provided in the product-specific data sheets.
Fields of application, industries and applications Our products are used in various industries and applications:
Air performance measurements
Ventilation, air-conditioning and refrigeration technology, clean room
All air performance measurements are carried out on suction side and on
technology, automotive and rail technology, medical and laboratory tech-
chamber test beds conforming to the specifications as per ISO 5801 and
nology, electronics, computer and office technology, telecommunications,
DIN 24163. The fans under test are installed in the measuring chamber at
household appliances, heating, machines and plants, drive engineering.
free air intake and exhaust (installation category A) and are operated at
Our products are not designed for use in the aviation and aerospace
nominal voltage, with AC also at nominal frequency, and without any
industry!
additional components such as guard grilles. As required by the standard, the air performance curves correspond to an air density of 1.2 kg/m3.
67
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 68
Room for precision noise measuring
Measurement conditions for air and noise measurement ebm-papst products are measured under the following conditions: – Axial and diagonal fans in direction of rotation “V” in full nozzle and without guard grille – Backward curved centrifugal fans, free-running and with inlet nozzle – Forward curved single and dual inlet centrifugal fans with housing Noise measurements All noise measurements are carried out in low-reflective test rooms with reverberant floor. Thus the ebm-papst acoustic test chambers meet the requirements of precision class 1 according to DIN EN ISO 3745. For noise measurement, the fans being tested are placed in a reverberant wall and operated at nominal voltage (for AC, also at nominal frequency) without additional attachments such as the guard grille. Sound pressure level and sound level All acoustic values are established according to ISO 13347, DIN 45635 and ISO 3744/3745 to accuracy class 2 and given in A-rated form. When the sound pressure level (Lp) is measured, the microphone is on the intake side of the fan being tested, usually at a distance of 1 m on the fan axis. To measure the sound power level (Lw), 10 microphones are distributed over an enveloping surface on the intake side of the fan being tested (see graphic). The sound power level measured can be roughly calculated
1,5d
from the sound pressure level by adding 7 dB.
D
Measuring configuration as per ISO 13347-3 respectively DIN 45635-38: 10 measuring points d≥D h = 1,5d ... 4,5d
h
3d
Measurement area S = 6d2 + 7d (h + 1,5d)
2d
68
11:34
Seite 69
Adding multiple noise sources with the same level
15
19.05.2011
dB
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
pressure level of a fan is approximately 75 dB(A). The level increase measured from the diagram is 9 dB. Thus the overall sound level of the installation can be expected to be 84 dB(A).
10 9
Example: 8 A3G800 axial fans are on a condenser. According to the data sheet, the sound
5
the noise values specified in the data sheet. This is shown in the diagram opposite.
0
The noise characteristics of multiple identical fans can be determined in advance based on
Increase in sound pressure / sound power level
Adding 2 noise sources with the same volume results in a level increase of approx. 3 dB.
1
2
3
4
5
6 7 8 9 10
15
20 25
dB
Adding two noise sources with different levels
3
Number of sources of sound with identical level
4 dB. The level increase can now be read in the diagram as approx. 1.5 dB. This means that the overall sound level of the unit can be expected to be 76.5 dB(A).
2 1,5
ating point and an axial fan A3G710 with 71 dB(A) in a ventilation unit. The level difference is
1
Example: There is an axial fan A3G800 with a sound pressure level of 75 dB(A) at the oper-
0
levels given in the data sheet. This is shown in the diagram opposite.
Increase in sound pressure / sound power level
The acoustic performance of two different fans can be predetermined based on the sound
0
4
8
12
16
20
24
Difference in level with two sources of sound 0 dB
Distance laws
dB
Sound power level is independent of distance to the sound source. In contrast to this, sound -10
pressure level decreases the further away the noise source is. The adjacent diagram shows the decrease in level under far sound field conditions. Far sound field conditions apply when-
decreases by 6 dB. In the near field of the fan, other correlations apply and the decrease in levels can be considerably smaller. The following example only applies to far sound field conditions and can vary strongly depending on the installation effects: With an axial fan A3G300, a sound pressure level of 65 dB(A) was measured at a distance of 1 m. According to the adjacent diagram, at a distance of 20 m we would get a reduction by
-20 -26 -30
vant literature on this complex topic. Per doubling of distance, the level in the far sound field
-40
wavelength to be considered. For more information on far sound field, please consult the rele-
Decrease in sound pressure level
ever the distance between microphone and fan is big when compared to fan diameter and
1
Distance
2
5
10
20
50
100 m
26 dB, i.e. a sound pressure level of 39 dB(A).
69
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
fan agent compact fan agent
19.05.2011
11:34
Seite 70
ebm-papst in Germany
motor specialist motor agent
Germany ebm-papst Mulfingen GmbH & Co. KG
ebm-papst St. Georgen GmbH & Co. KG
ebm-papst Landshut GmbH
Bachmühle 2 D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110
[email protected]
Hermann-Papst-Straße 1 D-78112 St. Georgen Phone +49 7724 81-0 Fax +49 7724 81-1309
[email protected]
Hofmark-Aich-Straße 25 D-84030 Landshut Phone +49 871 707-0 Fax +49 871 707-465
[email protected]
www.ebmpapst.com
www.ebmpapst.com
www.ebmpapst.com
70
Berlin Dipl.-Ing. (TH) Jens Duchow Händelstraße 7 D-16341 Panketal Phone +49 30 944149-62 Fax +49 30 944149-63
[email protected]
Heilbronn / Heidelberg Dipl.-Ing. Mark Gartner Gehrweg 12 D-74199 Unterheinriet Phone +49 7130 404569-1 Fax +49 7130 404569-2
[email protected]
Bielefeld Dipl.-Ing. (FH) Wolf-Jürgen Weber Niehausweg 13 D-33739 Bielefeld Phone +49 5206 91732-31 Fax +49 5206 91732-35
[email protected]
Kassel Dipl.-Ing. (FH) Ralph Brück Hoherainstraße 3 b D-35075 Gladenbach Phone +49 6462 4071-10 Fax +49 6462 4071-11
[email protected]
Dortmund Dipl.-Ing. (FH) Hans-Joachim Pundt Auf den Steinern 3 D-59519 Möhnesee-Völlinghausen Phone +49 2925 800-407 Fax +49 2925 800-408
[email protected]
Koblenz Winfried Schaefer Hinter der Kirch 10 D-56767 Uersfeld Phone +49 2657 16-96 Fax +49 2657 16-76
[email protected]
Frankfurt Dipl.-Ing. Christian Kleffmann Dr.-Hermann-Krause-Straße 23 D-63452 Hanau Phone +49 6181 1898-12 Fax +49 6181 1898-13
[email protected]
Munich Dipl.-Wirt.-Ing. (FH) Jens Peter Uhlandstraße 6 D-74427 Fichtenberg Phone +49 7971 260-180 Fax +49 7971 260-221
[email protected]
Halle Dipl.-Ing. (TU) Michael Hanning Lercheneck 4 D-06198 Salzatal / OT Lieskau Phone +49 345 55124-56 Fax +49 345 55124-57
[email protected]
Nuremberg Dipl.-Wirt.-Ing. (FH) Axel Resch Steinsfeldstraße 80 D-74626 Bretzfeld Phone +49 7946 94401-02 Fax +49 7946 94401-03
[email protected]
Hamburg Ingenieurbüro Breuell GmbH Ing. Dirk Kahl Elektroingenieur Grützmühlenweg 40 D-22339 Hamburg Phone +49 40 538092-19 Fax +49 40 538092-84
[email protected]
Offenburg Dipl.-Ing. (FH) Ralf Braun Hubeneck 21 D-77704 Oberkirch Phone +49 7802 9822-52 Fax +49 7802 9822-53
[email protected] Stuttgart Dipl.-Ing. (FH) Rudi Weinmann Hindenburgstraße 100/1 D-73207 Plochingen Phone +49 7153 9289-80 Fax +49 7153 9289-81
[email protected]
Ulm M.Sc. Reinhard Sommerreißer Am Silbermannpark 10 D-86161 Augsburg Phone +49 821 6610-7023 Fax +49 821 6610-7024
[email protected]
Distributors Frankfurt R.E.D. Handelsgesellschaft mbH Gutenbergstraße 3 D-63110 Rodgau - Jügesheim Phone +49 6106 841-0 Fax +49 6106 841-111
[email protected] www.red-elektromechanik.de Hamburg Breuell + Hilgenfeldt GmbH Grützmühlenweg 40 D-22339 Hamburg Phone +49 40 538092-20 Fax +49 40 538092-84
[email protected] Munich A. Schweiger GmbH Ohmstraße 1 D-82054 Sauerlach Phone +49 8104 897-0 Fax +49 8104 897-90
[email protected] www.schweiger-gmbh.com (1 to 5 pieces) North Breuell + Hilgenfeldt GmbH Grützmühlenweg 40 D-22339 Hamburg Phone +49 40 538092-20 Fax +49 40 538092-84
[email protected] South HDS Ventilatoren Vertriebs GmbH Glaswiesenstraße 1 D-74677 Dörzbach Phone +49 7937 8033520 Fax +49 7937 8033525
[email protected]
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 71
ebm-papst in Europe
Europe Austria ebm-papst Motoren & Ventilatoren GmbH Straubingstraße 17 A-4030 Linz Phone +43 732 321150-0 Fax +43 732 321150-20
[email protected] www.ebmpapst.at Belarus ebm-papst Bel AgmbH P.O. Box 117 BY-220138 Minsk Phone +375 17 3851556 Fax +375 17 3851556
[email protected] www.ebmpapst.by Belgium ebm-papst Benelux B.V. Sales office Belgium-Luxemburg Romeinsestraat 6/0101 Research Park Haasrode B-3001 Heverlee-Leuven Phone +32 16 396-200 Fax +32 16 396-220
[email protected] www.ebmpapst.be Bulgaria ebm-papst Romania S.R.L. Str. Tarnavei Nr. 20 RO-500327 Brasov Phone +40 268 312-805 Fax +40 268 312-805
[email protected] Croatia ebm-papst Industries Kft. Ezred u. 2. H-1044 Budapest Phone +36 1 8722-190 Fax +36 1 8722-194
[email protected]
Czech Republic / Slovakia ebm-papst CZ s.r.o. Kaštanová 34a CZ-620 00 Brno Phone +420 544 502-411 Fax +420 547 232-622
[email protected] www.ebmpapst.cz Denmark ebm-papst Denmark ApS Vallensbækvej 21 DK-2605 Brøndby Phone +45 43 631111 Fax +45 43 630505
[email protected] www.ebmpapst.dk Estonia ebm-papst Oy, Eesti Filiaal Kesk tee 13 Aaviku küla, Jüri Tehnopark EST-75301 Rae Vald, Harjumaa Phone +372 65569-78 Fax +372 65569-79 www.ebmpapst.ee Finland ebm-papst Oy Puistotie 1 FIN-02760 Espoo Phone +358 9 887022-0 Fax +358 9 887022-13
[email protected] www.ebmpapst.fi France ebm-papst sarl ZI Nord - rue A. Mohler BP 62 F-67212 Obernai Cedex Phone +33 820 326266 Fax +33 3 88673883
[email protected] www.ebmpapst.fr Greece Helcoma Th. Rotas & Co OE Davaki 65 GR-17672 Kallithea-Attiki Phone +30 210 9513-705 Fax +30 210 9513-490
[email protected] www.helcoma.gr
Hungary ebm-papst Industries Kft. Ezred u. 2. H-1044 Budapest Phone +36 1 8722-190 Fax +36 1 8722-194
[email protected] Iceland RJ Engineers Stangarhyl 1a IS-110 Reykjavik Phone +354 567 8030 Fax +354 567 8015
[email protected] www.rj.is Ireland ebm-papst UK Ltd. Chelmsford Business Park GB-Chelmsford Essex CM2 5EZ Phone +44 1245 468555 Fax +44 1245 466336
[email protected] www.ebmpapst.co.uk AuBren Limited Portlaoise Business & Technology Park Mountrath Road IRL-Portlaoise, Co. Laois Phone +353 57 8664343 Fax +353 57 8664346
[email protected] www.aubren.com Italy ebm-papst Srl Via Cornaggia 108 I-22076 Mozzate (Co) Phone +39 0331 836201 Fax +39 0331 821510
[email protected] www.ebmpapst.it Macedonia ebm-papst Industries Kft. Ezred u. 2. H-1044 Budapest Phone +36 1 8722-190 Fax +36 1 8722-194
[email protected]
71
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
fan agent compact fan agent
19.05.2011
11:34
Seite 72
ebm-papst in Europe
motor specialist motor agent
Netherlands ebm-papst Benelux B.V. Engelseweg 127 NL-5705 AC Helmond Phone +31 492 502-900 Fax +31 492 502-950
[email protected] www.ebmpapst.nl
Russia ebm-papst Ural GmbH Posadskaja-Strasse, 23(E), 3 RU-620102 Ekaterinburg Phone +7 343 2338000 Fax +7 343 2337788
[email protected] www.ebmpapst.ur.ru
Switzerland ebm-papst AG Rütisbergstrasse 1 CH-8156 Oberhasli Phone +41 44 73220-70 Fax +41 44 73220-77
[email protected] www.ebmpapst.ch
Norway ebm-papst AS P.B. 173 Holmlia N-1203 Oslo Phone +47 22 763340 Fax +47 22 619173
[email protected] www.ebmpapst.no
ebm-papst Rus GmbH proezd 4529, vladenie 5, stroenie 1 RU-141000 Mytistschi, Oblast Moskau Phone +7 495 9807524 Fax +7 495 5140924
[email protected] www.ebmpapst.ru
Turkey Akantel Elektronik San. Tic. LTD. Sti. Atatürk Organize Sanayi Bölgesi 10007 SK. No.:6 TR-35620 Cigli-Izmir Phone +90 232 3282090 Fax +90 232 3280270
[email protected] www.ebmpapst.com.tr
Poland ebm-papst Polska Sp. z o.o. ul. Annopol 4A PL-03236 Warszawa Phone +48 22 6757819 Fax +48 22 6769587
[email protected] www.ebmpapst.pl Portugal ebm-papst (Portugal), Lda. Centro Empresarial de Alverca Rua de Adarse, Vale D’Ervas Corpo D / Fracção 3 P-2615-178 Alverca do Ribatejo Phone +351 218 394 880 Fax +351 218 394 759
[email protected] www.ebmpapst.pt Romania ebm-papst Romania S.R.L. Str. Tarnavei Nr. 20 RO-500327 Brasov Phone +40 268 312-805 Fax +40 268 312-805
[email protected]
72
Serbia & Montenegro ebm-papst Industries Kft. Ezred u. 2. H-1044 Budapest Phone +36 1 8722-190 Fax +36 1 8722-194
[email protected] Spain ebm-papst Ibérica S.L. Avda. del Sistema Solar, 29 E-28830 San Fernando de Henares (Madrid) Phone +34 91 6780894 Fax +34 91 6781530
[email protected] Sweden ebm-papst AB Äggelundavägen 2 S-17562 Järfälla Phone +46 8 7619400 Fax +46 8 362306
[email protected] www.ebmpapst.se
Ukraine ebm-papst Ukraine LLC Lepse Boulevard, 4, Building 47 UA-03067 Kiev Phone +38 044 2063091 Fax +38 044 2063091
[email protected] www.ebmpapst.ua United Kingdom ebm-papst UK Ltd. Chelmsford Business Park GB-Chelmsford Essex CM2 5EZ Phone +44 1245 468555 Fax +44 1245 466336
[email protected] www.ebmpapst.co.uk ebm-papst Automotive & Drives (UK) Ltd. The Smithy Fidlers Lane GB-East Ilsley, Berkshire RG20 7LG Phone +44 1635 2811-11 Fax +44 1635 2811-61
[email protected] www.ebmpapst-ad.com
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 73
ebm-papst in America and Africa
America Argentina ebm-papst de Argentina S.A. Hernandarias 148 Lomas del Mirador Pcia. de Buenos Aires (1752) Phone +54 11 46576135 Fax +54 11 46572092
[email protected] www.ebmpapst.com.ar Brasil ebm-papst Motores Ventiladores Ltda. Av. José Giorgi, 301 Galpões B6+B7 Condominio Logical Center BR-06707-100 Cotia - São Paulo Phone +55 11 4613-8700 Fax +55 11 3164-8924
[email protected] www.ebmpapst.com.br
USA ebm-papst Inc. P.O. Box 4009 100 Hyde Road USA-Farmington, CT 06034 Phone +1 860 674-1515 Fax +1 860 674-8536
[email protected] www.ebmpapst.us ebm-papst Automotive & Drives, Inc. 3200 Greenfield, Suite 255 USA-Dearborn, MI 48120 Phone +1 313 406-8080 Fax +1 313 406-8081
[email protected] www.ebmpapst-automotive.us
Africa South Africa ebm-papst South Africa (Pty) Ltd. P.O. Box 3124 1119 Yacht Avenue ZA-2040 Honeydew Phone +27 11 794-3434 Fax +27 11 794-5020
[email protected] www.ebmpapst.co.za
Canada ebm-papst Canada Inc. 1800 Ironstone Manor, Unit 2 CDN-Pickering, Ontario, L1W3J9 Phone +1 905 420-3533 Fax +1 905 420-3772
[email protected] www.ebmpapst.ca Mexico ebm Industrial S.de R.L. de C.V. Paseo de Tamarindos 400-A-5to Piso Col. Bosques de las Lomas MEX-Mexico 05120, D.F. Phone +52 55 3300-5144 Fax +52 55 3300-5243
[email protected] www.ebmpapst.com.mx
73
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
fan agent compact fan agent
19.05.2011
11:34
Seite 74
ebm-papst in Asia and Australia
motor specialist motor agent
Asia China ebm-papst Ventilator (Shanghai) Co., Ltd. No. 418, Huajing Road WaiGaoQiao Free Trade Zone No. 2001, Yang Gao (N) Road VRC-200131 Shanghai, P.R. of China Phone +86 21 5046-0183 Fax +86 21 5046-1119
[email protected] www.ebmpapst.com.cn Hong Kong ebm-papst Hong Kong Ltd. Unit No. 13,9 / F Technology Park, 18 On Lai Street Siu Lek Yuen, Shatin N.T. Hong Kong - P.R. of China Phone +852 2145-8678 Fax +852 2145-7678
[email protected] India ebm-papst India Pvt. Ltd. 26/3, G.N.T. Road, Erukkencherry IND-Chennai-600118 Phone +91 44 25372556 Fax +91 44 25371149
[email protected] www.ebmpapst.in Indonesia ebm-papst Indonesia Representative Office German Centre, 4th Floor, Suite 4470 Jl. Kapt. Subijono Dj. Bumi Serpong Damai RI-15321 Tangerang Phone +62 21 5376250 Fax +62 21 5388305
[email protected] Israel Polak Bros. Import Agencies Ltd. 9 Hamefalsim Street IL-Kiryat Arie, Petach-Tikva 49514 Phone +972 3 9100300 Fax +972 3 5796679
[email protected] www.polak.co.il
74
Japan ebm-papst Industries Japan K.K. 12 Floor, Benex S-3 Bldg. 3-20-8 Shinyokohama, Kohoku-ku J-222-0033 Yokohama Phone +81 45 47057-51 Fax +81 45 47057-52
[email protected] www.ebmpapst.jp Korea ebm-papst Korea Co. Ltd. 6F, Trutec Bldg. B 6-2, Digital Media City (DMC) Sangam-Dong, Mapo-Gu ROK-Seoul 121-270 Phone +82 2 366213-24 Fax +82 2 366213-26
[email protected] www.ebmpapst.co.kr Malaysia ebm-papst Malaysia Representative Office Unit 12-2, Jalan USJ Sentral 3 Persiaran Subang, Selangor Darul Ehsan MAL-47600 Subang Jaya Phone +60 3 8024-1680 Fax +60 3 8024-8718
[email protected] Singapore ebm-papst SEA Pte. Ltd. No. 23 Ubi Road 4 #06-00 Olympia Industrial Building SGP-Singapore 408620 Phone +65 65513789 Fax +65 68428439
[email protected] Taiwan ETECO Engineering & Trading Corp. 10F-I, No. 92, Teh-Wei Str. RC-Tsow-Inn District, Kaohsiung Phone +886 7 557-4268 Fax +886 7 557-2788
[email protected] www.ebmpapst.com.tw
Thailand ebm-papst Thailand Co., Ltd. 99/349 Na-Nakorn Bldg., 4th Floor Chaeng Wattana Road, Thungsonghong, THA-10210 Laksi, BKK Phone +66 2 57615-24 Fax +66 2 57615-42
[email protected] United Arab Emirates ebm-papst Middle East FZE PO Box 17755 Jebel Ali Free Zone / FZS1 / AP05 UAE-Dubai Phone +971 4 88608-26 Fax +971 4 88608-27
[email protected] www.ebmpapst.ae Vietnam ebm-papst Vietnam Representative Office Room #102, 25 Nguyen Van Thu Street District 1 VN-Ho Chi Minh City Phone +84 8 39104099 Fax +84 8 39103970
[email protected]
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 75
Australia Australia ebm-papst A&NZ Pty Ltd. 10 Oxford Road AUS-Laverton North, Victoria, 3026 Phone +61 3 9360-6400 Fax +61 3 9360-6464
[email protected] www.ebmpapst.com.au New Zealand ebm-papst A&NZ Pty Ltd. 102 Henderson Valley Road NZ-Henderson, Auckland 1230 Phone +64 9 837-1884 Fax +64 9 837-1899
[email protected] www.ebmpapst.com.au
75
Plug_Fans_19_05_2011_EN_:G1G_170_deutsch_.qxd
19.05.2011
11:34
Seite 76
37797-7-8811 · KD-11/05-3’ Printed in Germany
ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110
[email protected]
www.ebmpapst.com