Permit and Inspection Requirements for Single Family Residential Construction

Permit and Inspection Requirements for Single Family Residential Construction Building Inspection Office (817) 503-1030 City of Colleyville 100 Main...
Author: Ralph Simpson
1 downloads 4 Views 736KB Size
Permit and Inspection Requirements for Single Family Residential Construction

Building Inspection Office (817) 503-1030

City of Colleyville 100 Main St. Colleyville, TX 76034 www.colleyville.com

Building Inspection Line (817) 503-1172 Building Inspection Fax (817) 503-1039

CV-605 (2-18-2014)

City of Colleyville

A. INTRODUCTION This information booklet has been prepared by the Colleyville Building Inspection Department to provide homeowners and building contractors a brief summary of the procedures used to obtain a building permit and receive periodic inspections of construction work. Typically, many residential construction projects have similar characteristics and the procedures described in this booklet will generally apply in those situations. However, since construction practices vary, it may become necessary for the building inspector to change or modify these procedures to accommodate the wide range of building and construction techniques found in the construction industry. For questions regarding construction practices not described in this booklet contact the staff of the Colleyville Building Inspection Department who are available to provide assistance with permit applications or to answer questions regarding specific inspection procedures. This information packet is intended to be a helpful reference and does not replace any requirements specified in the codes and ordinances adopted by the City Council. B. BUILDING PERMIT AND INSPECTION DEPARTMENT OFFICE HOURS Building permit applications may be submitted during regular office hours from 8:00 a.m. to 5:00 p.m., Monday through Friday. Inspectors are generally available in the office between the hours of 8:00 a.m. to 9:00 a.m. and 4:00 p.m. to 5:00 p.m. each day. Technical questions must be directed to the inspectors during the above listed office hours. General questions and permit information may be obtained by calling the Building Inspection Department. C. BUILDING PERMIT REQUIREMENTS A building permit is required for new residential construction or for any renovation or addition to an existing residential structure. Building permits may be obtained from the Building Inspection Department.

No construction, grading or dirt movement (including the setting of forms for the future pouring of foundations) of any kind may begin on any lot until an erosion control plan AND an engineered lot grading plan has been submitted and approved by the City. To apply for a building permit, a complete submittal must include ALL OF the following items: 1. Application Form – one (1) copy of the completed permit application indicating the names of the general, concrete, plumbing, electrical and mechanical contractors. The permit application form may be downloaded from the City of Colleyville website www.colleyville.com or is available in the Building Inspection department. 2. Sidewalk Permit Application - The Sidewalk Permit Application form may be downloaded from the City of Colleyville website (www.colleyville.com) or is available in the Building Inspection department. 3. Plot Plan – one (1) copy of a plot plan showing all structures, existing and proposed, and where these structures are or are to be placed in relation to property lines and each other.

City of Colleyville

4. Erosion Control Plan – one (1) copy of a plan showing the location of all erosion control measures. This information may be shown on the plot plan. (An example of an erosion control plan is shown in Section P of this brochure). 5. Engineered Grading Plan – one (1) copy of a site specific, engineered grading plan. 6. Energy Compliance Documentation – The International Energy Conservation Code adopted by the City of Colleyville requires the submittal of documentation at time of building permit application that the proposed structure complies with the minimum energy conservation requirements. Builders can download the necessary computer software at www.energycodes.gov to perform their own energy calculations. Additions to residential buildings that will be heated and/or cooled must comply with the International Energy Conservation Code. For example, all new ductwork to an addition from an existing heating system must be insulated and sealed in accordance with the code. Additions that are not heated and/or cooled, such as an unconditioned garage, need not comply. Contractors must contract with a third-party inspection company for the required Energy Code inspections. A certificate of compliance must be forwarded to the Building Inspection Department prior to Building Final inspection. 7. Construction Plans – two (2) sets of construction plans, 11X17 is acceptable. The construction plans shall include the following items: a. b. c. d. e.

A floor plan of all structures. Window and door sizes. Elevation drawings showing exterior wall construction. Foundation drawings stamped by a professional engineer licensed by the State of Texas. Original letter from the same engineer that designed and sealed the foundation plans stating that the foundation was designed for the soil conditions on that particular lot. The letter must also state that the foundation design criteria comply with the minimum standards required by the 2003 International Residential Code.

8. CD with Documents in PDF Format – One (1) disk with items 1-7 in PDF format.

Permit Application Checklist Permit

Application

Erosion  Control Plan

 Foundation Letter (5e)



Sidewalk Permit Application

Energy  Compliance

Engineered Grading Plan



Plot Plan

Form

All submitted

Construction documents in Plans PDF on CD

City of Colleyville

D. PLAN REVIEW PROCEDURES Permit applications and all accompanying documents should be submitted to the Building Inspection Department for processing. City staff will review the permit application submittal and provide written comments on the proposed construction plans, which will be returned to the applicant for correction and re-submittal. Where the construction plans do not require major corrections, city staff will complete the plan review process, calculate all applicable fees and notify the applicant that the permit is ready to be issued upon payment of the applicable fees. Most plan reviews can be completed within five working days after submittal of the application. E. PERMIT FEES The City of Colleyville has adopted the permit fee schedules contained in the 1997 Uniform Administrative Code and calculates permit fees based on the estimated construction value of the proposed building. In some instances, the City of Colleyville has established flat rate permit fees for certain types of construction. The City of Colleyville Building Code states that the estimated construction value used for calculating permit fees shall not be less than the square footage construction cost listed in the most recent Building Valuation Data published by the International Conference of Building Officials. Permit fees shall be adjusted on an annual basis for permit applications received on or after the 1st day of June using the most recent edition of the Building Valuation Data. The City of Colleyville Building Code also requires payment of a plan review fee. The plan review fee is a separate fee and is in addition to the permit fee. The current plan review fee for a new single-family residence is $350. No additional plan review fee shall be charged where plans are incomplete or for reviewing a construction plan that has been previously reviewed and re-submitted with corrections. Where construction plans are changed to a new proposal or where a third plan review is necessary, an additional plan review fee is required. F. APPLICABLE CODES AND ORDINANCES The City of Colleyville has adopted and enforces the following codes that are applicable to building construction activities within the corporate limits of the community. 1. 2. 3 4 5. 6. 7.

National Electrical Code – 2002 edition International Building Code – 2003 edition International Plumbing Code – 2003 edition International Mechanical Code – 2003 edition International Fire Code – 2003 edition International Energy Conservation Code – 2009 edition (Effective January 1, 2012) International Residential Code – 2003 edition

Local amendments to the above codes can be viewed on the Colleyville web site or can be obtained from the Building Inspection Department. G. GENERAL INSPECTION REQUIREMENTS

City of Colleyville

1. Building permit packet must be displayed in a conspicuous place that can be seen by the inspector. 2. Address numbers must be posted at all times on the job site and on temporary electrical poles with 4 inch numbers in a location that is visible from the street on each lot. 3. Instruct subcontractors and their employees to park in such a manner that emergency vehicular traffic will not be obstructed, i.e., fire trucks and ambulances. 4. An eight-foot by eight-foot by four-foot high (8’x 8’ x 4’) trash container (bin) is required on the job site prior to beginning of any work. Openings in the walls of the trash container cannot be large enough to allow a two- inch (2”) diameter sphere to pass through. 5. Toilet facilities will be required on the job site. 6. Silt fence is required at plumbing rough-in inspection. 7. Construction working hours are 7:00 A.M. to 6:00 P.M. Monday through Saturday. No working is allowed on Sunday. 8. Lawn sprinkler systems require a separate permit and back flow certification before final inspection. 9. A separate fence permit is required prior to any fence construction.

H. MATERIALS LOCATED IN RIGHT-OF-WAY All dirt, sand or any type of construction material must be located in such a way as to comply with the following requirements. 1. If no city sidewalk has been constructed on the property, all construction material must be located at least four feet (4’) from back of curb to allow for pedestrian passage through the property. 2. If a sidewalk does exist, construction materials can be placed behind the sidewalk. No construction material will be allowed on the sidewalk. 3. When the plumber installs the water meter, the builder must erect a wooden pole or metal stake adjacent to the meter that extends at least four feet above the ground. The stake must be painted blue. No construction material can be placed within three feet (3’) of the pole or stake. 4. At all times during construction, the water meter box must be installed around the water meter. I.

PERMIT PACKETS AND INSPECTION TAGS

Permit packets must be on the construction site at the location specified below. Inspection tags will be placed inside the permit packet by the inspector once the inspection is complete. The inspection tag must remain on the construction site with the permit packet at all times. 1. T-Pole, Plumbing-Rough and Foundation: The permit packet must be located on the side of the trash bin that is facing the street. The trash bin must be located within the front yard of the lot. 2. Frame and Building Final: The permit packet must be taped to the inside of the window closest to the front door facing the street. J.

ENGINEERING LETTERS AND OTHER REQUIRED DOCUMENTS

Whenever an engineering letter or other document is required, an original signature is required on the plans or on a letter specifically referring to the plans by address. K. INCLEMENT WEATHER PROCEDURES

City of Colleyville

No concrete or plumbing rough inspections will be made if it has been determined that it is too wet by the Building Inspection Department. All rained out inspections must be recalled. Plumbing rough inspections may be conducted in wet weather provided that a five (5) p.s.i. air test is placed on the sewer lines and a (50) p.s.i. air test is placed on the water lines. When the inspection is requested, it must be stated that there is an air test on the rough. No concrete inspection will be made unless the temperature is at least 38 degrees Fahrenheit and rising. All inspections cancelled due to cold weather must be recalled. L. RE-INSPECTION FEES The City of Colleyville Building Code authorizes the assessment of a re-inspection fee when an inspector is unable to perform or complete a requested inspection due to the fault of the contractor. If a reinspection fee is assessed, no further inspections will be performed on the construction site until the reinspection fee has been paid. The first re-inspection fee shall be $75.00; (2) the second, and any subsequent, re-inspection fee shall be $125.00 to include any of the following reasons: 1. 2. 3. 4. 5. 6. 4. 5. 6. 7. 8. 9. 10. 11.

The requested inspection is not ready. The temporary electrical pole does not have the address posted. No building address posted. Copies of the approved construction plans and permits are not on the job site. Trash on lot. The structure is locked or work to be inspected is not otherwise accessible. An inspection is disapproved twice for the same item. The previous red tag has been removed from place left by the inspector. Trash bin not on site. A safety fence is not installed around sewer tap excavation that is four feet deep or more. No form board survey is on file in the office when a plumbing rough inspection is requested. Construction materials are located within the right-of-way. Water or sewer tap is not connected when the plumbing rough is inspected. Silt screening not installed in accordance with the soil erosion plan.

M. REQUESTING AN INSPECTION When the particular stage of construction work has been completed and ready for an inspection from the Building Inspection Department, call the Inspection Request Line at (817) 503-1172 or visit http://permitsonline.colleyville.com/etrakit/ to request an inspection or check results. Inspection requests placed before 6:00 a.m. on Monday through Friday will be performed that day. N. REQUIRED RESIDENTIAL INSPECTIONS This section identifies the inspections required for a typical residential structure and outlines the construction elements usually inspected by the inspector. Inspection requests are generally made in the sequence listed below unless there are unusual circumstances. No inspection will be performed if an inspection is requested out of sequence, unless special arrangements with the inspector have been made. 1. Temporary power pole inspection (can be done at any time)

City of Colleyville

2. Plumbing rough inspection 3. Foundation inspection (form board survey is required to be submitted, to our office, prior to this inspection) 4. Seconds inspection (framing, plumbing top-out, electrical rough, and mechanical rough) 5. Temporary Electric and/or Temporary Gas 6. Flat work inspection (can be done any time) 7. Irrigation system (see Irrigation Systems Procedures on our website for inspection requirements) 8. Building final inspection Temporary power pole inspection The following items are generally required and inspected during the temporary power pole inspection: 1. 2. 3. 4. 5. 6.

Double pole/single throw breaker installed for 240 volt 20A outlet. Single pole breaker installed for 120-volt outlet with 20A GFCI protection on all 120-volt receptacles. Box is to be secured to the pole. Pole is to be braced, secure and stable. A ground rod must be installed with a ground wire that is a minimum size of #6 AWG. The licensed electrician can test house circuits provided that power is disconnected when the electrician leaves the site. Anyone other than the electrician connecting power to the house circuits may be subject to a citation for creating a potential electrical hazard to the public. Exception: An electrical utility company may connect power after approval of the utility final. 7. All power connections from T-Pole must have proper connectors on each end of the cord. 8. Legible address numbers must be posted on the T-Pole. Numbers must be at least four inches (4”) in height. 9. No holes are allowed in the panel (front cover sides, top or bottom must be rain tight). 10. Outlets outside the panel box must be weatherproof. 11. All breakers and receptacles must be clearly marked with amperage/voltage. 12. Neutral conductor shall be identified for its entire exposed length by a distinctive white marking at all terminations. Plumbing rough inspection 1. Form board survey – Prior to requesting a plumbing rough inspection, the contractor shall submit a form board survey to the Building Inspection Department. The form board survey must be stamped by a licensed surveyor and show the location of the proposed foundation in relation to the property boundary. The information shown on the form board survey must indicate that the location of the structure will conform to the set-back requirements of the applicable zoning regulations for the property. The form board survey must include top of form. 2. Water lines – The following items are required and inspected when the plumbing rough inspection is performed by the inspector. a. One hose connection with non-removable vacuum breaker must be installed in the water line to check the pressure on the copper. b. All hose connections must have non-removable vacuum breakers installed at all times. c. A one-inch (1”) minimum service line will be required.

City of Colleyville

d. Copper lines will not be allowed to touch each other. Copper lines must be sleeved where penetrating concrete. e. The water meter should be in place with all valves open to allow for water testing of the lines at city water pressure. If city water is not available, a 50 p.s.i. air test can be substituted for the water test. 3. Sanitary Sewer – The following items are required and inspected when the plumbing rough inspection is performed by the inspector. a. Five-foot (5’) head of water measured at the last stack in the house. b. A 5 p.s.i. air test can be substituted for the water test required on the sewer line. c. The sewer tap must be exposed two feet (2’) from either side of sewer connection. (This means that two feet (2’) of the city green lateral line adjacent to the tie-in must be exposed at the time of inspection). d. Holes dug for sewer taps that are deeper than six feet (6’) must be protected by temporary construction fence. e. Sewer must be connected to the City’s sanitary sewer system. Foundation inspection No foundation inspections will be made if it has been determined that it is too wet. All rained out inspections must be recalled. No foundation inspections will be approved unless the outside temperature is 38 degrees Fahrenheit and rising or suitable provisions have been taken to assure proper curing of the concrete. 1. The following requirements must be met in order to pass a foundation inspection: a. Everything must conform with the engineered plans with no changes to the approved plans. b. All copper water pipes that will be exposed to concrete must be sleeved or taped. c. The post tension drawing must be on the job with detail sheet and the plot plan (both must be City stamped.) d. Cables that must be re-routed to miss plumbing fixtures must be done with long sweeping curves of the cables. e. Electrical conduit located in the foundation must be installed (kitchen island, floor outlet, etc.). f. Jenn-Air ducts must be installed (P.V.C. or metal ducts.) g. All gas line sleeves must be installed. h. Form board surveys and, when required, finished floor elevation surveys must be submitted prior to requesting the inspection. i. No changes can be made to the foundation after inspection approval without requesting another foundation inspection. j. Poly must cover all pad areas only. Poly is to be cut away from bottom of beams. k. A water test with city pressure or a minimum air test of 50 p.s.i. must be maintained on the water supply lines. l. All water must be removed from beams before scheduling an inspection. Seconds inspection (Framing, electrical rough, plumbing top-out, mechanical rough-in)

City of Colleyville

1. Water – The following items are required and inspected when the seconds inspection is performed by the inspector. a. Frost proof hose-connections with integral vacuum breakers must be installed. b. All water lines in unheated areas must be insulated with a minimum of ¾” pipe insulation. 2. Sewer – The following items are required and inspected when the seconds inspection is performed by the inspector. a. All vents must extend through the roof with flashings installed at the roof and at least 18-inches from any wall, at least 6-inches above the roof and at least 10 feet from or 2 feet above any opening such as a window. b. A top-out water test is required for all plumbing located above the first floor. c. A water test is required for all tubs and shower pans. d. Water heaters installed in a location where leakage could cause damage must have a drip pan. The pan must have a drain pipe extending to the exterior of the building. 3. Gas Line – The following items are required and inspected when the seconds inspection is performed by the inspector. a. Gas appliance vents must be at least four feet (4’) away from or two feet (2’) above windows that can be opened. b. Black pipe gas lines: An air test of at least one and one-half times the operating pressure is required. The gauge must be located outside of the house at the gas meter connection. c. CSST Gas Lines: An air test of at least sixty pounds per square inch (60 p.s.i.) on a one-hundred (100) pound gauge is required for all lines prior to the regulator (piping designed to operate at 2 p.s.i. working pressure) the gauge for the 60 p.s.i. test should be located outside of the house at the gas meter connection. All lines after the regulator must have an air test of at least ten pounds per square inch (10 p.s.i.). The test must be performed on a thirty (30) pound gauge. The gauge should be located at the fireplace. d. Holes cut in studs or plates for gas lines may only be large enough for the line to penetrate (all holes cut in top plate must be sealed). e. Gas lines must be properly supported. f. Gas lines located between bricks and masonry must be factory mill wrapped. g. All gas outlets must have approved gas stops installed with caps. h. No water, soil or waste pipe can be installed or located outside of a building in an unheated area or in an exterior wall unless, adequate provisions are made to protect such line from freezing. i. Gas vent must terminate at least 2 feet higher than any portion of the structure within 10 feet of the vent. 4. Electrical rough – The following items are required and inspected when the seconds inspection is performed by the inspector. Non-metallic - sheathed cable will be referred to as Romex: a. Romex extending through masonry must be protected by sleeving with plastic (P.V.C.) or liquid tight flex conduit (with approved fittings). b. A ground must be connected to the cold water piping. A supplemental grounding rod must also be supplied. Clamps for grounding electrode must be accessible.

City of Colleyville

c. All 240-volt appliances must be wired with a four (4) wire system that includes a neutral and a separate ground. d. Electrical conductors in notched or bored studs that are less than 1-1/4 inches from the edge of the stud must be protected by a nail plate. 5. Mechanical rough – The following items are required and inspected when the seconds inspection is performed by the inspector. a. Metal ducts shall be screwed and taped and inspected before insulation. b. Flexible ducts shall be supported with material at least one and one-half inches (1-1/2") wide. Maximum spacing for support is four feet (4'). Some manufacturers require supports every two feet (2'). Turns must be made in such a way that the airflow is not deterred. c. A minimum one-inch (1") clearance must be maintained around gas appliance vents from combustible materials. d. Air conditioning condensate drains must be tied into a wet trap. e. Where air-conditioning condensate drain pans are located in an attic, a secondary drain must be installed with the condensate line discharging over a window, door, patio or other approved location. f. Condensate drain lines must be a minimum of three-fourth (3/4") inch in diameter. g. Horizontal runs on gravity type water heater and furnace flue vents must not exceed seventyfive percent (75%) of the height of the vent. h. Bath exhaust fan ducts must extend to the exterior of the building or immediately inside the structure at a vent or grill. i. Dryer vents are limited to a maximum length of twenty-five feet (25'). The twenty-five foot (25') length includes two (2) ninety-degree fittings. Additional fittings over and above the two (2) allowed will reduce the maximum length of the vent by two (2') for every ninety degree (90) fitting (or combination of fittings that total 90 degrees). Dryer vent connections must be taped and not screwed. j. Dryer vents extending through a roof must include a tight fitting collar to keep lint from falling back into the attic. 6. Framing – The following items are required and inspected when the seconds inspection is performed by the inspector. a. Exterior bottom plates must be secured to the foundation by j-bolts, which shall not be less than 1/2-inch nominal diameter steel bolts embedded at least 7-inches into the concrete. Washer and nuts must be tightened. ICBO approved powder actuated fasteners such as “ramsets” are acceptable. These fasteners must be shot not more than every twenty-four inches (24") on center and within twelve inches (12") of every end of exterior plates. These fasteners must be used with proper metal washers. b. Top plate splices must be offset a minimum of forty-eight inches (48"). c. Rafters must be framed directly opposite each other at the ridge. The size of the ridge must not be less in depth than the cut end of the rafter. Hurricane fasteners must be used on all rafters. d. Valleys and hip rafters must not be less than two inches (2") nominal thickness and not less in depth than the cut end of the rafter. e. Purlins must be the same size as the rafter it supports. Braces must be installed every six feet (6') from the purlin to the wall or beam.

City of Colleyville

f. g. h. i. j. k. l. m.

n. o. p. q. r. s.

Joists over four feet (4') in length, that are not bearing on 1-1/2” of wood or 3” of masonry, must be pressure blocked on one side or a joist hanger must be used (with nails in all openings). Furr-downs, chimneys, ceilings of different heights, and vertical wall spaces over ten feet (10') must be fire blocked. Poly sealing small holes and gaps in fire blocks will be acceptable. Load bearing studs must be sixteen inches (16") on center. Studs with masonry veneer wall ties attached cannot exceed spacing of sixteen inches (16") on center. Load bearing beams must be supported with two (2) wall studs on each end. All lumber must be grade stamped. Unstamped lumber is unacceptable as a framing structural member. Ceiling joist must be doubled when supporting a water heater. There will be a two-inch (2) gap between fireplace material and wood studs or any other combustible material as required by the International Building Code. All stairs treads must have a maximum rise of 7 ¾ inches and a minimum run of 10 inches. The stair treads on a winding stairway shall not be less than six (6) inches on the inside of each winder and at a point twelve inches out from the inside winder, a 10” tread is required. Masonry fireplaces must be complete to a point one foot (1') above the damper. Any brick supported on wood must comply with the City's brick on wood policy or the design must be certified by a professional engineer. All penetrations in top plates must be sealed. Small penetrations may be poly sealed. Holes in exterior sheathing must be sealed. Covered porches and patios must be inspected to verify proper structural framing prior to installing soffit material. Cutting, notching or boring of engineered beams is not allowed without engineer’s letter.

Utility Inspection for gas and electricity connection a. b. c. d. e. g. h. i.

All wires must be capped or fixtures installed and electrical outlets and switches installed. Cover must be off the breaker panel. Both grounds installed, cold water and ground rod clamps are to be tight. Neutral and grounding conductors must be properly coded and identified. The meter base must be bonded to the main panel box. Gas piping must be under pressure as required for a gas test. Gas stops and caps must be installed on all gas lines. Gas stops at each appliance must be properly secured for all types of piping, including CSST systems.

Building final inspection (building, electrical, plumbing, mechanical finals) 1. General – The following items are required and inspected when the building final inspection is performed by the inspector. a. All work is to be complete other than non-code regulated items such as wall paper or carpeting. b. All required permits have been obtained and all required fees have been paid. 2. Plumbing – The following items are required and inspected when the building final inspection is performed by the inspector.

City of Colleyville

a. All gas appliances must be connected or have gas stops and caps installed. Gas connectors must not exceed three feet (3’), except for clothes dryers and ranges, which must not exceed 6 feet. b. All plumbing fixtures must be installed. Any drain or water line that is installed for future use or expansion must have permanent caps. c. Sewer cleanouts must be cut to grade and P.V.C. caps installed. d. Hot water must correspond to left side of fittings on plumbing fixtures. e. PVC vent stacks must be painted to provide protection from ultra-violet light exposure. f. All toilets must be caulked at the floor. g. Air gap fittings must be installed on all dishwashers. h. Shower door must have a minimum opening clearance of twenty-two inches (22"). 3. Electrical – The following items are required and inspected when the building final inspection is performed by the inspector. a. All receptacles must be wired properly. All light fixtures must be installed. b. All GFCI's must be installed and working properly. c. A permanent electrical outlet and light fixture controlled by a switch located at the required attic opening must be provided at or near air-conditioning and water heater equipment. d. All areas requiring illumination must be switched. e. The whirlpool tub access panel must be removed for inspection. f. Electrical outlets located in garages that are not GFCI protected must be single receptacles and labeled. g. Floor outlet receptacles must be accessible and require U. L. listed type floor boxes. 4. Mechanical – The following items are required and inspected when the building final inspection is performed by the inspector. a. Combustion air vents must be installed in the upper twelve inches (12") and lower twelve inches (12") of closets enclosing gas appliances. Each vent must total 100 square inches. b. A mechanical heating system must be operational that is capable of maintaining a temperature of 70 degree Fahrenheit at a point that is two feet above floor level. c. Vent fans must be operational in bath and utility rooms. 5. Building – The following items are required and inspected when the building final inspection is performed by the inspector. a. A permanent address must be installed with numbers of contrasting color to background and visible from the street. Address may be posted on the building or on the mailbox if located on the same lot. b. Street, alley and all flatwork must be clean and clear of mud and debris. c. Silt fencing, sod or other approved erosion control must be in place. Yard must be clear of debris and final grade completed. d. A solid walkway at least twenty-four inches (24") wide must be installed from attic opening to furnaces and water heaters. The distance from the opening to the equipment cannot exceed twenty feet (20'). A thirty-inch (30") working platform is also required directly in front of the equipment. e. Chimneys must extend at least two feet (2') above any point within ten feet (10') of the roof. f. A solid-core door must be installed between the garage and living area.

City of Colleyville

g. Test on irrigation backflow device must be on file in the office. h. Permits for all fences and irrigation systems must be issued prior to inspection. 9. The Colleyville Engineering Department must be contacted to inspect and obtain information regarding work to be performed in the right-of-way such as driveway approaches, sidewalks and culvert pipes that are required when a driveway extends over a drainage-ditch. Lot drainage is also regulated by the Engineering Department. O. FINAL LOT DRAINAGE SURVEY A final lot drainage lot drainage survey, performed by a State of Texas Licensed Engineer or State of Texas Licensed Surveyor, confirming compliance with the city approved drainage plan must be submitted to the Building Inspection Department prior to building final approvals. P. EROSION CONTROL MEASURES The City of Colleyville Land Development Code requires all residential construction sites to provide erosion control measures until the site is vegetated. The erosion control measures require the installation of silt screening to prevent soil erosion at construction sites from becoming a public nuisance. Applicants seeking a building permit, to construct a new building or to make an addition to an existing building, are required to submit an "Erosion Control Plan" with their building permit application. The building inspector will review the Erosion Control Plan for conformance with the regulations prior to approving the building permit application. The silt screening shall be installed and maintained by the contractor in accordance with these requirements prior to approval of any inspection. An Erosion Control Plan shall at a minimum contain the following items: 1. A site plan drawn to scale of the property where earthwork is proposed showing the property boundary, any street right-of-way and any drainage easement. 2. The existing drainage flow by using arrows to indicate the direction of slope. 3. The location of any existing or proposed building footprint, if applicable. 4. The location and type of erosion control method proposed. 5. The location where access is gained to the property. The following is an excerpt from Ordinance Number O-99-

City of Colleyville

1174, which describes the minimum criteria for an erosion control screen. "Where required by these regulations, there shall be an erosion control barrier constructed according to these standards. The erosion control barrier shall be installed to a minimum height of twelve inches (12”) with the base buried to protect from washout. Said erosion control barrier shall be placed behind any curb and extend across a minimum of 66% of the street frontage of the lot. Additional erosion control barriers may be required to provide erosion control for the entire width of the lot where required by the City Inspector, except at the access point. There shall be a four foot (4') transition section at each end of the barrier. The erosion control barrier shall provide for a minimum of one point of access, which shall be a minimum width of ten feet (10') and a maximum width of twenty feet (20'). The access point shall have a minimum of four inch (4") thick gravel base and extend a minimum of ten feet (10') from the curb. In the absence of any curb, the City Inspector shall determine the proper location of the erosion control barrier."

Q. TREE PROTECTION REQUIREMENTS The City of Colleyville Land Development Code requires all residential construction sites to provide tree protection for trees located on the lot, but outside the building pad site. Trees within the buildable area of a lot may be removed as a part of the normal construction process. All other trees on the lot having a trunk diameter of 3” or more must remain on the lot and be protected from construction activities. The following regulations are applicable to tree protection during residential construction activities: 1. Protective Fencing – All trees shall have protective fencing located at the tree's drip line. The protective fencing may be comprised of snow fencing, orange vinyl construction fencing, chain link fence or other similar fencing with a four-foot (4’) approximate height. The protective fencing may be located within the drip line of the specimen tree for approved construction only. The fencing shall follow the delineation of the approved construction. 2. Bark Protection – In situations where a tree remains in the immediate area of intended construction, the tree shall be protected by enclosing the entire circumference of the tree's trunk with lumber encircled with wire or other means that does not damage the tree. 3. Construction Pruning – In a case where a low hanging limb may be broken during the course of construction, the obtrusive limb may be cut. The limb shall be cut either flush to the trunk on or at the next joint of the limb. The wound shall then be sealed with pruning paint. In no instance shall pruning involve a portion of the trunk or thirty percent (30%) of the entire canopy without the prior approval of the building inspector. 4. Improvements within the Critical Root Zone of a Tree – Design constraints often dictate that trees slated for preservation have some encroachment on their critical root zone. The following is the minimum design criteria that are allowed within the critical root zone of a tree. Development exceeding the criteria would put the tree at risk and therefore no longer be considered a preserved tree. In such a case replacement trees shall also be required.

City of Colleyville

a. Grade Changes – In the event that grade changes must be made around a tree or group of trees, the following should be implemented in order to maintain oxygen and water exchange within the tree's critical root zone. i.

A minimum of seventy-five percent (75%) of the critical root zone must be preserved at natural grade with natural ground cover or landscaping for the tree to be considered a preserved tree.

ii. No cut or fill greater than two inches (2”) shall be located closer to the tree trunk than one half (1/2) of the radius of the critical root zone radius distance. iii. Increase Grade: Provide an aeration system just outside the tree's drip line. A dry well located a minimum of one-half (1/2) of the radius of the critical root zone. iv. Decrease Grade: Provide retaining walls outside the drip line to mitigate cuts. 5. Prohibited Activities – The following activities shall be prohibited with the limits of the drip line of any tree that is subject to the requirements of this Chapter. a. Material Storage – No materials intended for use in construction or waste materials accumulated due to excavation or demolition shall be placed within the limits of the drip line of any tree. b. Equipment Cleaning / Liquid Disposal – No equipment may be cleaned or other liquids deposited within the limits of the drip line of a tree. This would include but not be limited to, paint, oil, solvents, asphalt, concrete, mortar or other materials. c. Tree Attachments – No signs, wires or other attachments, other than those of a protective nature shall be attached to any tree. d. Vehicular Traffic – No vehicular and construction equipment traffic or parking is allowed within the limits of the drip line of trees. R. MASONRY ON WOOD POLICY The International Building Code specifically prohibits supporting masonry with wooden members. The City of Colleyville does not allow masonry to be supported by wood, unless one of the following conditions is met: 1. The masonry load has been calculated by a professional engineer, licensed in the State of Texas, and the engineer has determined that the wood members will support the weight of the masonry. An original design letter must be submitted by the engineer and contain the engineer’s stamp and signature on the letter. 2. The brick on wood rafters policy prepared by the Society of Professional Building Designers in concurrence with the North Texas Chapter of the International Conference of Building Officials is followed.

City of Colleyville

S. SANITARY FACILITIES DURING CONSTRUCTION The Colleyville ordinances require each contractor to provide adequate sanitary facilities for the convenience of all construction personnel during any construction of a new building. For the purpose of this requirement, a temporary facility that is portable, enclosed, chemically treated and tank-tight may be used, provided that these facilities shall be kept in a clean and sanitary condition throughout the duration of the construction work. T. ADDRESS SIGN The Colleyville Building Codes requires each contractor to post the address at all construction sites as follows: 1. Temporary address sign. All construction sites shall have posted a temporary address sign in a conspicuous place on the premises. The permit holder shall maintain the address sign until the permanent address sign is installed. U. CONSTRUCTION REFUSE The Colleyville Building Codes requires each contractor to provide a covered container for the collection of construction debris and trash. Such container shall of adequate size to contain any debris generated in the construction process. (Typically, 8 ft. by 8 ft. and 4 ft. tall) The contractor shall regularly retrieve any and all debris and trash generated at the construction site which has blown, dropped, floated, dumped or carried onto any adjacent property or city right-of-way and place such into the container. The contractor shall be responsible for the removal of any dirt or mud, which has been introduced onto a city street caused by such construction.

City of Colleyville

Building Permit Application Submittal Checklist  Building Permit Application (B1)  Sidewalk Permit Application  Plot Plan  Erosion Control Plan  Energy Compliance  Construction Plans  Engineered Foundation Letter  Engineered Grading Plan (site specific)  All documents submitted for review in PDF format on CD