PACKAGE HEAT PUMPS RQNA- HIGH EFFICIENCY 13-SEER SERIES. NOMINAL SIZES 2-4 TONS [ kw]

PACKAGE HEAT PUMPS FORM NO. P22-764 REV. 4 Supersedes Form No. P22-764 Rev. 3 RQNA- HIGH EFFICIENCY 13-SEER SERIES NOMINAL SIZES 2-4 TONS [7.03-14.07...
Author: Andra Fields
1 downloads 0 Views 2MB Size
PACKAGE HEAT PUMPS FORM NO. P22-764 REV. 4 Supersedes Form No. P22-764 Rev. 3

RQNA- HIGH EFFICIENCY 13-SEER SERIES NOMINAL SIZES 2-4 TONS [7.03-14.07 kW]

TABLE OF CONTENTS

Unit Features & Benefits ..............................................................................3-4 Model Identification Options ..........................................................................5-6 General Data RQNA- Series ..........................................................................................7-8 General Data Notes ........................................................................................9 Performance Data RQNA- Series ......................................................................................10-14 Airflow Performance RQNA- Series ......................................................................................15-16 Electrical Data RQNA- Series............................................................................................17 Electric Heater Kits ..................................................................................18-19 Dimensional Data ....................................................................................20-21 Typical Installations ......................................................................................22 Accessories ............................................................................................23-31 Typical Wiring ..........................................................................................32-35 Limited Warranty ..........................................................................................36

2

UNIT FEATURES & BENEFITS—RQNA-

These quality features are included in the Ruud Outdoor Package Heat Pumps 5

4

3

UNIT FEATURES & BENEFITS—RQNA- SERIES

Features Below Correspond to Photos on Page 3 1. All models feature Scroll® compressors for maximum efficiency and quiet operation.

8. Refrigerant connections are conveniently located for easy service diagnostics.

2. Louvered condenser compartment for protecting the coil against yard hazards and/or weather extremes.

9. Condenser and evaporator coils feature enhanced fins for better heat transfer and rifled copper tubing for greater efficiency.

3. One-piece top with a deep flange to help keep water out of the unit.

10. Supplemental electric heat strips up to 15 kW are available (field or factory installed) for periods of extreme cold temperatures. Single point wiring makes installation even easier.

4. Supply and return air openings feature a one-inch tall flange to prevent water migration into the ductwork. 5. Access panels have “weep holes” and channels to further help manage water run-off.

11. All units feature an internal trap on the condensate line eliminating the need for installing an on-site external trap.

6. Side and down discharge options available on all models. (Shipped Downflow Standard).

12. Easily accessible control box.

7. Easily accessible blower section complete with slideout blower. All units feature a system matched indoor coil with low static pressure drop and excellent cooling capacities.

4

MODEL IDENTIFICATION—RQNA- SERIES

R Q N A — 036 J K 000 XXX Factory Installed Options (See Next Page) Heating Capacity (Factory Installed) 000 = No Resistance Heat 005 = 05 KW Resistance Heat (018-030) 010 = 10 KW Resistance Heat (024-048) 015 = 15 KW Resistance Heat (036-048) Drive Package K = Direct Drive Electrical Designation J = 208-230V—1PH—60 Hz C = 208-230V—3PH—60 Hz Cooling Capacity (BTUH) [kW] 024 = 24,000 [7.03] 030 = 30,000 [8.79] 036 = 36,000 [10.55] 042 = 42,000 [12.31] 048 = 48,000 [14.07] Design Series A = 1st Design Efficiency Designation N = 13 SEER High Efficiency Product Classification Q = Package Heat Pump Tradebrand R = Ruud

[ ] Designates Metric Conversions

5

OPTIONS—RQNA- SERIES Instructions for Factory Installed Option(s) Selection Note: Two characters following the model number will be utilized to designate a factory-installed option or combination of options. If no factory option(s) is required, nothing follows the model number. Step 1. After a basic rooftop model is selected, choose a two-character option code from the FACTORY INSTALLED OPTION SELECTION TABLE.

FACTORY INSTALLED OPTION CODES Option Code AA AKA

Side Flow No Option x

Example: RQNA-036JK000XX (where XX is factory installed option) Example: No Options RQNA-036JK000 Example: Options with Sideflow RQNA-036JK000AKA Note: Factory installed economizer is not available on these models.

6

GENERAL DATA—RQNA- SERIES NOMINAL SIZES 2-4 TONS [7.03-14.07 kW] Model RQNA- Series Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2

B024JK

B030JK

B036CK

B036JK

24,400 [7.15] 11/13

31,400 [9.2] 11/13

36,600 [10.72] 11/13

CONTINUED 36,600 [10.72] 11/13

800/800 [378/378] 23,600 [6.91]

1000/1050 [472/495] 30,200 [8.85]

1200/1200 [566/566] 35,400 [10.37]

1200/1200 [566/566] 35,400 [10.37]

Net Sensible Capacity Btu [kW]

17,900 [5.24]

22,100 [6.48]

26,300 [7.71]

26,300 [7.71]

Net Latent Capacity Btu [kW]

5,700 [1.67]

8,100 [2.37]

9,100 [2.67]

9,100 [2.67]

2.14

2.74

3.22

3.22

23,000 [6.74] 1.95/3.4 12,900 [3.78]

29,000 [8.5] 2.44/3.4 16,100 [4.72]

34,200 [10.02] 2.91/3.4 19,500 [5.71]

34,200 [10.02] 2.91/3.4 19,500 [5.71]

1.89/2

2.29/2

2.72/2.1

2.72/2.1

7.7

7.7

7.7

7.7

1/Scroll 76

1/Scroll 76

1/Scroll 76

1/Scroll 76

Louvered

Louvered

Louvered

Louvered

Rifled 0.375 [9.5] 14.51 [1.35] 1 / 22 [9]

Rifled 0.375 [9.5] 16.32 [1.52] 1 / 22 [9]

Rifled 0.375 [9.5] 11.2 [1.04] 2 / 22 [9]

Rifled 0.375 [9.5] 11.2 [1.04] 2 / 22 [9]

Refrigerant Control

TX Valves

TX Valves

TX Valves

TX Valves

Indoor Coil—Fin Type Tube Type Tube Size in. [mm]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

5.54 [0.51]

7.39 [0.69]

7.39 [0.69]

7.39 [0.69]

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

Direct/1

Direct/1

Direct/1

Direct/1

2700 [1274] 1 at 1/5 HP

2700 [1274] 1 at 1/5 HP

2700 [1274] 1 at 1/5 HP

2700 [1274] 1 at 1/5 HP

Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW]

Net System Power kW Heating Performance (Heat Pumps) Heating Input Btu [kW] Rating System Power KW/COP Low Temp. Btuh [kW] Rating System Power KW/COP HSPF (Btu/Watts-hr) Compressor No./Type Outdoor Sound Rating (dB)3 Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm]

Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm] Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM Motor Frame Size Filter—Type Furnished

1075

1075

1075

1075

FC Centrifugal 1/9x7 [228.6x177.8] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/3

FC Centrifugal 1/10x9 [254x228.6] Direct/1

FC Centrifugal 1/10x9 [254x228.6] Direct/1

1

1

1

1

1/4

1/2

1/3

1/3

1075

1075

1075

1075

48 Field Supplied

48 Field Supplied

48 Field Supplied

48 Field Supplied

No

No

No

No

(1)1x20x20 [25x508x508]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

86 [2438]

93 [2637]

122 [3459]

122 [3459]

Net Weight lbs. [kg]

391 [177]

444 [201]

471 [214]

468 [212]

Ship Weight lbs. [kg]

401 [182]

455 [206]

482 [219]

479 [217]

(No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g] Weights

[ ] Designates Metric Conversions

See Page 9 for Notes.

7

GENERAL DATA—RQNA- SERIES NOMINAL SIZES 2-4 TONS [7.03-14.07 kW] Model RQNA- Series

B042CK

B042JK

B048CK

B048JK

44,500 [13.04] 11/13

44,500 [13.04] 11/13

50,000 [14.65] 11/13

50,000 [14.65] 11/13

1400/1400 [661/661] 43,500 [12.75]

1400/1400 [661/661] 43,500 [12.75]

1600/1600 [755/755] 48,500 [14.21]

1600/1600 [755/755] 48,500 [14.21]

Net Sensible Capacity Btu [kW]

31,800 [9.32]

31,800 [9.32]

36,000 [10.55]

36,000 [10.55]

Net Latent Capacity Btu [kW]

11,700 [3.43]

11,700 [3.43]

12,500 [3.66]

12,500 [3.66]

3.96

3.96

4.41

4.41

39,500 [11.57] 3.34/3.4 22,800 [6.68]

39,500 [11.57] 3.34/3.4 22,800 [6.68]

46,000 [13.48] 4.11/3.28 27,400 [8.03]

46,000 [13.48] 4.11/3.28 28,000 [8.2]

3.18/2.1

3.18/2.1

3.86/2.08

3.86/2.08

7.7

7.7

7.7

7.7

1/Scroll 76

1/Scroll 76

1/Scroll 78

1/Scroll 78

Louvered

Louvered

Louvered

Louvered

Rifled 0.375 [9.5] 16.32 [1.52] 2 / 22 [9]

Rifled 0.375 [9.5] 16.32 [1.52] 2 / 22 [9]

Rifled 0.375 [9.5] 16.32 [1.52] 2 / 22 [9]

Rifled 0.375 [9.5] 16.32 [1.52] 2 / 22 [9]

Refrigerant Control

TX Valves

TX Valves

TX Valves

TX Valves

Indoor Coil—Fin Type Tube Type Tube Size in. [mm]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

7.39 [0.69]

7.39 [0.69]

7.39 [0.69]

7.39 [0.69]

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

Direct/1

Direct/1

Direct/1

Direct/1

3300 [1557] 1 at 1/3 HP

3300 [1557] 1 at 1/3 HP

3000 [1416] 1 at 1/3 HP

3000 [1416] 1 at 1/3 HP

Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW]

Net System Power kW Heating Performance (Heat Pumps) Heating Input Btu [kW] Rating System Power KW/COP Low Temp. Btuh [kW] Rating System Power KW/COP HSPF (Btu/Watts-hr) Compressor No./Type Outdoor Sound Rating (dB)3 Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm]

Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm] Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM Motor Frame Size Filter—Type Furnished

1075

1075

1075

1075

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

1

1

1

1

3/4

3/4

3/4

3/4

1075

1075

1725

1075

48 Field Supplied

48 Field Supplied

48 Field Supplied

48 Field Supplied

No

No

No

No

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

158 [4479]

158 [4479]

150 [4252]

150 [4252]

Net Weight lbs. [kg]

508 [230]

505 [229]

500 [227]

510 [231]

Ship Weight lbs. [kg]

519 [235]

516 [234]

511 [232]

521 [236]

(No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g] Weights

[ ] Designates Metric Conversions

See Page 9 for Notes.

8

GENERAL DATA—RQNA- SERIES NOTES: 1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation in CFM range shown in airflow tables. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.

9

SYSTEMS PERFORMANCE—RQNA- SERIES COOLING PERFORMANCE DATA—RQNA-024 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

900 [425] .19

71°F [21.7°C] 800 [378] .16

700 [330] .11

900 [425] .19

67°F [19.4°C] 800 [378] .16

700 [330] .11

900 [425] .19

63°F [17.2°C] 800 [378] .16

700 [330] .11

Total BTUH [kW] 75 Sens BTUH [kW] [23.9] Power

31.4 [9.20] 18.2 [5.33] 1.6

30.7 [9.00] 17.2 [5.04] 1.5

30.0 [8.79] 16.2 [4.75] 1.5

29.1 [8.53] 21.6 [6.33] 1.6

28.4 [8.32] 20.4 [5.98] 1.5

27.8 [8.15] 19.2 [5.63] 1.5

28.6 [8.38] 23.3 [6.83] 1.5

28.0 [8.21] 22.0 [6.45] 1.5

27.4 [8.03] 20.7 [6.07] 1.5

Total BTUH [kW] 80 Sens BTUH [kW] [26.7] Power

30.5 [8.94] 18.0 [5.28] 1.6

29.8 [8.73] 17.0 [4.98] 1.6

29.2 [8.56] 16.0 [4.69] 1.6

28.2 [8.26] 21.4 [6.27] 1.6

27.6 [8.09] 20.2 [5.92] 1.6

27.0 [7.91] 19.0 [5.57] 1.6

27.8 [8.15] 23.1 [6.77] 1.6

27.2 [7.97] 21.8 [6.39] 1.6

26.5 [7.77] 20.5 [6.01] 1.6

Total BTUH [kW] 85 Sens BTUH [kW] [29.4] Power

29.5 [8.65] 17.6 [5.16] 1.7

28.8 [8.44] 16.6 [4.86] 1.7

28.2 [8.26] 15.7 [4.60] 1.7

27.2 [7.97] 21.0 [6.15] 1.7

26.6 [7.80] 19.8 [5.80] 1.7

26.0 [7.62] 18.7 [5.48] 1.7

26.8 [7.85] 22.7 [6.65] 1.7

26.2 [7.68] 21.4 [6.27] 1.7

25.6 [7.50] 20.2 [5.92] 1.7

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

28.4 [8.32] 17.1 [5.01] 1.8

27.8 [8.15] 16.1 [4.72] 1.8

27.1 [7.94] 15.2 [4.45] 1.8

26.1 [7.65] 20.4 [5.98] 1.8

25.5 [7.47] 19.3 [5.66] 1.8

25.0 [7.33] 18.2 [5.33] 1.8

25.7 [7.53] 22.1 [6.48] 1.8

25.1 [7.36] 20.9 [6.13] 1.8

24.5 [7.18] 19.7 [5.77] 1.8

27.3 [8.00] 16.5 [4.84] 1.9

26.7 [7.83] 15.6 [4.57] 1.9

26.1 [7.65] 14.7 [4.31] 1.9

25.0 [7.33] 19.9 [5.83] 1.9

24.5 [7.18] 18.8 [5.51] 1.9

23.9 [7.00] 17.7 [5.19] 1.9

24.6 [7.21] 21.6 [6.33] 1.9

24.0 [7.03] 20.4 [5.98] 1.9

23.5 [6.89] 19.2 [5.63] 1.9

26.3 [7.71] 15.9 [4.66] 2.0

25.7 [7.53] 15.0 [4.40] 2.0

25.1 [7.36] 14.1 [4.13] 2.0

24.0 [7.03] 19.2 [5.63] 2.0

23.5 [6.89] 18.2 [5.33] 2.0

22.9 [6.71] 17.1 [5.01] 2.0

23.5 [6.89] 20.9 [6.13] 2.0

23.0 [6.74] 19.8 [5.80] 2.0

22.5 [6.59] 18.6 [5.45] 2.0

Total BTUH [kW] 105 Sens BTUH [kW] [40.6] Power

25.4 [7.44] 15.3 [4.48] 2.1

24.9 [7.30] 14.5 [4.25] 2.1

24.3 [7.12] 13.6 [3.99] 2.0

23.1 [6.77] 18.7 [5.48] 2.1

22.6 [6.62] 17.6 [5.16] 2.1

22.1 [6.48] 16.6 [4.86] 2.0

22.7 [6.65] 20.4 [5.98] 2.1

22.2 [6.51] 19.2 [5.63] 2.1

21.7 [6.36] 18.1 [5.30] 2.0

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

24.8 [7.27] 14.8 [4.34] 2.2 24.5 [7.18] 14.4 [4.22] 2.3

24.3 [7.12] 14.0 [4.10] 2.2 24.0 [7.03] 13.6 [3.99] 2.2

23.7 [6.95] 13.2 [3.87] 2.1 23.4 [6.86] 12.8 [3.75] 2.2

22.5 [6.59] 18.1 [5.30] 2.2 22.2 [6.51] 17.8 [5.22] 2.3

22.0 [6.45] 17.1 [5.01] 2.2 21.7 [6.36] 16.8 [4.92] 2.2

21.5 [6.30] 16.1 [4.72] 2.1 21.3 [6.24] 15.8 [4.63] 2.2

22.1 [6.48] 19.8 [5.80] 2.2 21.8 [6.39] 19.5 [5.71] 2.3

21.6 [6.33] 18.7 [5.48] 2.1 21.3 [6.24] 18.4 [5.39] 2.2

21.1 [6.18] 17.7 [5.19] 2.1 20.8 [6.10] 17.3 [5.07] 2.2

O U T D O O R D R Y B U L B T E M P E R A T U R E

DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQNA-024 IDB CFM [L/s] O U T D O O R D R Y B U L B T E M P E R A T U R E °F [°C]

0 [-17.8] 5 [-15] 10 [-12.2] 15 [-9.4] 20 [-6.7] 25 [-3.9] 30 [-1.1] 35 [1.7] 40 [4.4] 45 [7.2] 50 [10]

Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power

900 [425]

60°F [15.5°C] 800 [378]

700 [330]

900 [425]

70°F [21.1°C] 800 [378]

700 [330]

900 [425]

80°F [26.7°C] 800 [378]

700 [330]

7.8 [2.29] 1.2 9.4 [2.75] 1.3 10.9 [3.19] 1.3 12.4 [3.63] 1.3 13.9 [4.07] 1.3 15.4 [4.51] 1.4 17.0 [4.98] 1.4 18.6 [5.45] 1.4 20.3 [5.95] 1.4 22.2 [6.51] 1.5 24.3 [7.12] 1.5

7.7 [2.26] 1.2 9.3 [2.73] 1.3 10.8 [3.17] 1.3 12.3 [3.60] 1.3 13.8 [4.04] 1.4 15.3 [4.48] 1.4 16.8 [4.92] 1.4 18.4 [5.39] 1.4 20.2 [5.92] 1.5 22.0 [6.45] 1.5 24.1 [7.06] 1.5

7.6 [2.23] 1.3 9.2 [2.70] 1.3 10.7 [3.14] 1.3 12.2 [3.58] 1.4 13.6 [3.99] 1.4 15.1 [4.43] 1.4 16.7 [4.89] 1.4 18.3 [5.36] 1.5 20.0 [5.86] 1.5 21.8 [6.39] 1.5 23.9 [7.00] 1.5

7.1 [2.08] 1.4 8.7 [2.55] 1.4 10.2 [2.99] 1.5 11.7 [3.43] 1.5 13.2 [3.87] 1.5 14.7 [4.31] 1.6 16.3 [4.78] 1.6 17.9 [5.25] 1.6 19.7 [5.77] 1.6 21.5 [6.30] 1.7 23.6 [6.92] 1.7

7.0 [2.05] 1.4 8.6 [2.52] 1.5 10.1 [2.96] 1.5 11.6 [3.40] 1.5 13.1 [3.84] 1.6 14.6 [4.28] 1.6 16.1 [4.72] 1.6 17.7 [5.19] 1.6 19.5 [5.71] 1.7 21.3 [6.24] 1.7 23.4 [6.86] 1.7

7.0 [2.05] 1.5 8.5 [2.49] 1.5 10.0 [2.93] 1.5 11.5 [3.37] 1.5 13.0 [3.81] 1.6 14.4 [4.22] 1.6 16.0 [4.69] 1.6 17.6 [5.16] 1.7 19.3 [5.66] 1.7 21.2 [6.21] 1.7 23.2 [6.80] 1.7

5.8 [1.70] 1.5 7.4 [2.17] 1.6 8.9 [2.61] 1.6 10.4 [3.05] 1.6 11.9 [3.49] 1.7 13.4 [3.93] 1.7 15.0 [4.40] 1.7 16.6 [4.86] 1.7 18.4 [5.39] 1.8 20.3 [5.95] 1.8 22.3 [6.54] 1.8

5.8 [1.70] 1.6 7.3 [2.14] 1.6 8.9 [2.61] 1.6 10.3 [3.02] 1.7 11.8 [3.46] 1.7 13.3 [3.90] 1.7 14.9 [4.37] 1.7 16.5 [4.84] 1.8 18.2 [5.33] 1.8 20.1 [5.89] 1.8 22.1 [6.48] 1.8

5.7 [1.67] 1.6 7.3 [2.14] 1.6 8.8 [2.58] 1.6 10.2 [2.99] 1.7 11.7 [3.43] 1.7 13.2 [3.87] 1.7 14.7 [4.31] 1.8 16.3 [4.78] 1.8 18.1 [5.30] 1.8 19.9 [5.83] 1.8 21.9 [6.42] 1.9

IDB—Indoor air dry bulb

[ ] Designates Metric Conversions

10

SYSTEMS PERFORMANCE—RQNAINTRODUCTION SERIES COOLING PERFORMANCE DATA—RQNA-030 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1050 [496] .16

920 [434] .11

1180 [557] .19

67°F [19.4°C] 1050 [496] .16

920 [434] .11

1180 [557] .19

63°F [17.2°C] 1050 [496] .16

920 [434] .11

Total BTUH [kW] 37.6 [11.02] 75 Sens BTUH [kW] 22.4 [6.56] [23.9] 1.9 Power

36.8 [10.79] 21.2 [6.21] 1.9

35.9 [10.52] 19.9 [5.83] 1.9

35.2 [10.32] 26.5 [7.77] 1.9

34.4 [10.08] 25.0 [7.33] 1.9

33.6 [9.85] 23.6 [6.92] 1.9

34.1 [9.99] 28.8 [8.44] 1.9

33.3 [9.76] 27.2 [7.97] 1.9

32.5 [9.52] 25.6 [7.50] 1.9

Total BTUH [kW] 37.4 [10.96] 80 Sens BTUH [kW] 22.4 [6.56] [26.7] 2.1 Power

36.6 [10.73] 21.2 [6.21] 2.0

35.7 [10.46] 19.9 [5.83] 2.0

35.0 [10.26] 26.5 [7.77] 2.1

34.2 [10.02] 25.0 [7.33] 2.0

33.5 [9.82] 23.6 [6.92] 2.0

33.9 [9.94] 28.8 [8.44] 2.1

33.1 [9.70] 27.2 [7.97] 2.0

32.4 [9.50] 25.6 [7.50] 2.0

Total BTUH [kW] 36.7 [10.76] 85 Sens BTUH [kW] 22.0 [6.45] [29.4] 2.2 Power

35.9 [10.52] 20.8 [6.10] 2.2

35.1 [10.29] 19.6 [5.74] 2.1

34.4 [10.08] 26.1 [7.65] 2.2

33.6 [9.85] 24.7 [7.24] 2.2

32.8 [9.61] 23.2 [6.80] 2.1

33.2 [9.73] 28.4 [8.32] 2.2

32.5 [9.52] 26.9 [7.88] 2.1

31.7 [9.29] 25.3 [7.41] 2.1

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

35.7 [10.46] 21.4 [6.27] 2.3

34.9 [10.23] 20.2 [5.92] 2.3

34.2 [10.02] 19.0 [5.57] 2.3

33.3 [9.76] 25.5 [7.47] 2.3

32.6 [9.55] 24.1 [7.06] 2.3

31.9 [9.35] 22.7 [6.65] 2.3

32.2 [9.44] 27.8 [8.15] 2.3

31.5 [9.23] 26.3 [7.71] 2.3

30.8 [9.03] 24.7 [7.24] 2.2

34.5 [10.11] 20.6 [6.04] 2.4

33.7 [9.88] 19.5 [5.71] 2.4

33.0 [9.67] 18.3 [5.36] 2.4

32.1 [9.41] 24.7 [7.24] 2.4

31.4 [9.20] 23.3 [6.83] 2.4

30.7 [9.00] 21.9 [6.42] 2.4

31.0 [9.09] 27.0 [7.91] 2.4

30.3 [8.88] 25.5 [7.47] 2.4

29.6 [8.67] 24.0 [7.03] 2.4

33.2 [9.73] 19.7 [5.77] 2.5

32.4 [9.50] 18.6 [5.45] 2.5

31.7 [9.29] 17.6 [5.16] 2.5

30.8 [9.03] 23.8 [6.98] 2.5

30.1 [8.82] 22.5 [6.59] 2.5

29.4 [8.62] 21.2 [6.21] 2.5

29.6 [8.67] 26.1 [7.65] 2.5

29.0 [8.50] 24.7 [7.24] 2.5

28.3 [8.29] 23.3 [6.83] 2.5

Total BTUH [kW] 31.8 [9.32] 105 Sens BTUH [kW] 18.9 [5.54] [40.6] 2.7 Power

31.1 [9.11] 17.9 [5.25] 2.6

30.4 [8.91] 16.8 [4.92] 2.6

29.4 [8.62] 23.0 [6.74] 2.7

28.8 [8.44] 21.7 [6.36] 2.6

28.1 [8.24] 20.5 [6.01] 2.6

28.3 [8.29] 25.3 [7.41] 2.6

27.7 [8.12] 23.9 [7.00] 2.6

27.0 [7.91] 22.5 [6.59] 2.6

29.9 [8.76] 17.3 [5.07] 2.8 29.0 [8.50] 16.9 [4.95] 2.9

29.2 [8.56] 16.3 [4.78] 2.7 28.3 [8.29] 15.9 [4.66] 2.8

28.2 [8.26] 22.3 [6.54] 2.8 27.2 [7.97] 21.9 [6.42] 2.9

27.6 [8.09] 21.1 [6.18] 2.7 26.6 [7.80] 20.7 [6.07] 2.9

26.9 [7.88] 19.9 [5.83] 2.7 26.0 [7.62] 19.5 [5.71] 2.8

27.1 [7.94] 24.7 [7.24] 2.8 26.1 [7.65] 24.3 [7.12] 2.9

26.5 [7.77] 23.3 [6.83] 2.7 25.5 [7.47] 22.9 [6.71] 2.9

25.9 [7.59] 21.9 [6.42] 2.7 24.9 [7.30] 21.6 [6.33] 2.8

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1180 [557] .19

30.6 [8.97] 18.3 [5.36] 2.8 29.6 [8.67] 17.9 [5.25] 2.9

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQNA-030 IDB CFM [L/s] O U T D O O R D R Y B U L B T E M P E R A T U R E °F [°C]

0 [-17.8] 5 [-15] 10 [-12.2] 15 [-9.4] 20 [-6.7] 25 [-3.9] 30 [-1.1] 35 [1.7] 40 [4.4] 45 [7.2] 50 [10]

Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power

1180 [557]

60°F [15.5°C] 1050 [496]

920 [434]

1180 [557]

70°F [21.1°C] 1050 [496]

920 [434]

1180 [557]

80°F [26.7°C] 1050 [496]

920 [434]

9.7 [2.84] 1.5 11.8 [3.46] 1.5 13.8 [4.04] 1.5 15.7 [4.60] 1.6 17.6 [5.16] 1.6 19.5 [5.71] 1.7 21.5 [6.30] 1.7 23.6 [6.92] 1.7 25.8 [7.56] 1.8 28.1 [8.24] 1.8 30.7 [9.00] 1.8

9.7 [2.84] 1.5 11.7 [3.43] 1.5 13.7 [4.02] 1.6 15.6 [4.57] 1.6 17.5 [5.13] 1.6 19.4 [5.69] 1.7 21.3 [6.24] 1.7 23.4 [6.86] 1.8 25.5 [7.47] 1.8 27.9 [8.18] 1.8 30.4 [8.91] 1.9

9.6 [2.81] 1.5 11.6 [3.40] 1.6 13.6 [3.99] 1.6 15.4 [4.51] 1.6 17.3 [5.07] 1.7 19.2 [5.63] 1.7 21.1 [6.18] 1.7 23.2 [6.80] 1.8 25.3 [7.41] 1.8 27.6 [8.09] 1.9 30.2 [8.85] 1.9

8.7 [2.55] 1.7 10.7 [3.14] 1.7 12.7 [3.72] 1.8 14.7 [4.31] 1.8 16.6 [4.86] 1.9 18.5 [5.42] 1.9 20.4 [5.98] 1.9 22.5 [6.59] 2.0 24.7 [7.24] 2.0 27.1 [7.94] 2.0 29.6 [8.67] 2.1

8.6 [2.52] 1.7 10.7 [3.14] 1.8 12.6 [3.69] 1.8 14.5 [4.25] 1.8 16.4 [4.81] 1.9 18.3 [5.36] 1.9 20.3 [5.95] 2.0 22.3 [6.54] 2.0 24.5 [7.18] 2.0 26.8 [7.85] 2.1 29.4 [8.62] 2.1

8.5 [2.49] 1.8 10.6 [3.11] 1.8 12.5 [3.66] 1.8 14.4 [4.22] 1.9 16.3 [4.78] 1.9 18.1 [5.30] 2.0 20.1 [5.89] 2.0 22.1 [6.48] 2.0 24.3 [7.12] 2.1 26.6 [7.80] 2.1 29.1 [8.53] 2.1

8.0 [2.34] 1.9 10.1 [2.96] 1.9 12.0 [3.52] 2.0 14.0 [4.10] 2.0 15.9 [4.66] 2.0 17.8 [5.22] 2.1 19.8 [5.80] 2.1 21.8 [6.39] 2.1 24.0 [7.03] 2.2 26.4 [7.74] 2.2 28.9 [8.47] 2.3

7.9 [2.32] 1.9 10.0 [2.93] 1.9 11.9 [3.49] 2.0 13.8 [4.04] 2.0 15.7 [4.60] 2.1 17.6 [5.16] 2.1 19.6 [5.74] 2.1 21.6 [6.33] 2.2 23.8 [6.98] 2.2 26.1 [7.65] 2.3 28.7 [8.41] 2.3

7.8 [2.29] 1.9 9.9 [2.90] 2.0 11.8 [3.46] 2.0 13.7 [4.02] 2.1 15.6 [4.57] 2.1 17.5 [5.13] 2.1 19.4 [5.69] 2.2 21.4 [6.27] 2.2 23.6 [6.92] 2.2 25.9 [7.59] 2.3 28.4 [8.32] 2.3

IDB—Indoor air dry bulb

[ ] Designates Metric Conversions

11

SYSTEMS PERFORMANCE—RQNA- SERIES COOLING PERFORMANCE DATA—RQNA-036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1200 [566] .16

1050 [496] .11

1350 [637] .19

67°F [19.4°C] 1200 [566] .16

1050 [496] .11

1350 [637] .19

63°F [17.2°C] 1200 [566] .16

1050 [496] .11

Total BTUH [kW] 46.3 [13.57] 75 Sens BTUH [kW] 26.6 [7.80] [23.9] 2.4 Power

45.3 [13.28] 25.1 [7.36] 2.4

44.3 [12.98] 23.7 [6.95] 2.4

43.0 [12.60] 31.7 [9.29] 2.4

42.1 [12.34] 29.9 [8.76] 2.4

41.1 [12.05] 28.2 [8.26] 2.3

41.4 [12.13] 33.4 [9.79] 2.4

40.4 [11.84] 31.5 [9.23] 2.4

39.5 [11.58] 29.7 [8.70] 2.4

Total BTUH [kW] 45.2 [13.25] 80 Sens BTUH [kW] 25.8 [7.56] [26.7] 2.6 Power

44.2 [12.95] 24.4 [7.15] 2.5

43.2 [12.66] 22.9 [6.71] 2.5

41.9 [12.28] 30.9 [9.06] 2.5

41.0 [12.02] 29.2 [8.56] 2.5

40.1 [11.75] 27.5 [8.06] 2.5

40.3 [11.81] 32.6 [9.55] 2.5

39.4 [11.55] 30.8 [9.03] 2.5

38.5 [11.28] 29.0 [8.50] 2.5

Total BTUH [kW] 43.9 [12.87] 85 Sens BTUH [kW] 25.1 [7.36] [29.4] 2.7 Power

42.9 [12.57] 23.8 [6.98] 2.6

41.9 [12.28] 22.4 [6.56] 2.6

40.6 [11.90] 30.2 [8.85] 2.6

39.7 [11.63] 28.5 [8.35] 2.6

38.8 [11.37] 26.9 [7.88] 2.6

38.9 [11.40] 31.9 [9.35] 2.7

38.0 [11.14] 30.2 [8.85] 2.6

37.2 [10.90] 28.4 [8.32] 2.6

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

42.4 [12.43] 24.6 [7.21] 2.8

41.4 [12.13] 23.3 [6.83] 2.8

40.5 [11.87] 21.9 [6.42] 2.7

39.1 [11.46] 29.7 [8.70] 2.8

38.2 [11.20] 28.0 [8.21] 2.7

37.3 [10.93] 26.4 [7.74] 2.7

37.4 [10.96] 31.4 [9.20] 2.8

36.6 [10.73] 29.7 [8.70] 2.7

35.7 [10.46] 27.9 [8.18] 2.7

40.8 [11.96] 24.1 [7.06] 2.9

39.9 [11.69] 22.8 [6.68] 2.9

39.0 [11.43] 21.5 [6.30] 2.9

37.5 [10.99] 29.2 [8.56] 2.9

36.7 [10.76] 27.6 [8.09] 2.8

35.8 [10.49] 26.0 [7.62] 2.8

35.8 [10.49] 30.9 [9.06] 2.9

35.0 [10.26] 29.2 [8.56] 2.9

34.2 [10.02] 27.5 [8.06] 2.8

39.3 [11.52] 23.6 [6.92] 3.0

38.4 [11.25] 22.3 [6.54] 3.0

37.5 [10.99] 21.0 [6.15] 3.0

36.0 [10.55] 28.7 [8.41] 3.0

35.2 [10.32] 27.1 [7.94] 3.0

34.4 [10.08] 25.5 [7.47] 2.9

34.3 [10.05] 30.4 [8.91] 3.0

33.5 [9.82] 28.7 [8.41] 3.0

32.8 [9.61] 27.0 [7.91] 2.9

Total BTUH [kW] 37.8 [11.08] 105 Sens BTUH [kW] 23.0 [6.74] [40.6] 3.2 Power

37.0 [10.84] 21.7 [6.36] 3.1

36.2 [10.61] 20.5 [6.01] 3.1

34.5 [10.11] 28.1 [8.24] 3.1

33.8 [9.91] 26.5 [7.77] 3.1

33.0 [9.67] 25.0 [7.33] 3.0

32.9 [9.64] 29.8 [8.73] 3.1

32.1 [9.41] 28.1 [8.24] 3.1

31.4 [9.20] 26.5 [7.77] 3.1

35.8 [10.49] 21.0 [6.15] 3.2 34.9 [10.23] 20.1 [5.89] 3.4

35.0 [10.26] 19.8 [5.80] 3.2 34.1 [9.99] 18.9 [5.54] 3.3

33.3 [9.76] 27.3 [8.00] 3.2 32.4 [9.50] 26.3 [7.71] 3.4

32.6 [9.55] 25.8 [7.56] 3.2 31.7 [9.29] 24.9 [7.30] 3.3

31.8 [9.32] 24.3 [7.12] 3.2 30.9 [9.06] 23.4 [6.86] 3.3

31.6 [9.26] 29.0 [8.50] 3.3 30.7 [9.00] 28.0 [8.21] 3.4

30.9 [9.06] 27.4 [8.03] 3.2 30.0 [8.79] 26.5 [7.77] 3.3

30.2 [8.85] 25.8 [7.56] 3.2 29.3 [8.59] 25.0 [7.33] 3.3

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1350 [637] .19

36.6 [10.73] 22.2 [6.51] 3.3 35.7 [10.46] 21.3 [6.24] 3.4

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQNA-036 IDB CFM [L/s] O U T D O O R D R Y B U L B T E M P E R A T U R E °F [°C]

0 [-17.8] 5 [-15] 10 [-12.2] 15 [-9.4] 20 [-6.7] 25 [-3.9] 30 [-1.1] 35 [1.7] 40 [4.4] 45 [7.2] 50 [10]

Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power

1350 [637]

60°F [15.5°C] 1200 [566]

1050 [496]

1350 [637]

70°F [21.1°C] 1200 [566]

1050 [496]

1350 [637]

80°F [26.7°C] 1200 [566]

1050 [496]

13.9 [4.07] 1.8 15.8 [4.63] 1.8 17.6 [5.16] 1.9 19.4 [5.69] 1.9 21.2 [6.21] 2.0 23.0 [6.74] 2.0 25.1 [7.36] 2.1 27.3 [8.00] 2.1 29.9 [8.76] 2.2 32.8 [9.61] 2.2 36.3 [10.64] 2.3

13.8 [4.04] 1.8 15.7 [4.60] 1.9 17.5 [5.13] 1.9 19.2 [5.63] 2.0 21.0 [6.15] 2.0 22.8 [6.68] 2.1 24.8 [7.27] 2.1 27.1 [7.94] 2.2 29.6 [8.67] 2.2 32.6 [9.55] 2.3 35.9 [10.52] 2.3

13.6 [3.99] 1.8 15.5 [4.54] 1.9 17.3 [5.07] 1.9 19.1 [5.60] 2.0 20.8 [6.10] 2.0 22.6 [6.62] 2.1 24.6 [7.21] 2.1 26.8 [7.85] 2.2 29.4 [8.62] 2.2 32.3 [9.47] 2.3 35.6 [10.43] 2.3

13.0 [3.81] 2.0 14.9 [4.37] 2.1 16.7 [4.89] 2.1 18.5 [5.42] 2.2 20.3 [5.95] 2.2 22.1 [6.48] 2.3 24.1 [7.06] 2.3 26.4 [7.74] 2.4 29.0 [8.50] 2.4 31.9 [9.35] 2.5 35.4 [10.37] 2.5

12.9 [3.78] 2.1 14.8 [4.34] 2.1 16.6 [4.86] 2.2 18.3 [5.36] 2.2 20.1 [5.89] 2.3 21.9 [6.42] 2.3 23.9 [7.00] 2.4 26.2 [7.68] 2.4 28.7 [8.41] 2.5 31.7 [9.29] 2.5 35.0 [10.26] 2.6

12.7 [3.72] 2.1 14.7 [4.31] 2.2 16.4 [4.81] 2.2 18.2 [5.33] 2.3 19.9 [5.83] 2.3 21.7 [6.36] 2.4 23.7 [6.95] 2.4 25.9 [7.59] 2.5 28.5 [8.35] 2.5 31.4 [9.20] 2.6 34.7 [10.17] 2.6

12.1 [3.55] 2.3 14.1 [4.13] 2.4 15.9 [4.66] 2.4 17.7 [5.19] 2.5 19.4 [5.69] 2.5 21.3 [6.24] 2.6 23.3 [6.83] 2.6 25.6 [7.50] 2.7 28.1 [8.24] 2.7 31.1 [9.11] 2.8 34.5 [10.11] 2.8

12.0 [3.52] 2.4 14.0 [4.10] 2.4 15.8 [4.63] 2.5 17.5 [5.13] 2.5 19.3 [5.66] 2.6 21.1 [6.18] 2.6 23.1 [6.77] 2.6 25.3 [7.41] 2.7 27.9 [8.18] 2.7 30.8 [9.03] 2.8 34.2 [10.02] 2.8

11.9 [3.49] 2.4 13.8 [4.04] 2.4 15.6 [4.57] 2.5 17.3 [5.07] 2.5 19.1 [5.60] 2.6 20.9 [6.13] 2.6 22.9 [6.71] 2.7 25.1 [7.36] 2.7 27.6 [8.09] 2.8 30.6 [8.97] 2.8 33.9 [9.94] 2.9

IDB—Indoor air dry bulb

[ ] Designates Metric Conversions

12

SYSTEMS PERFORMANCE—RQNA- SERIES COOLING PERFORMANCE DATA—RQNA-042 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1400 [661] .16

1220 [576] .11

1580 [746] .19

67°F [19.4°C] 1400 [661] .16

1220 [576] .11

1580 [746] .19

63°F [17.2°C] 1400 [661] .16

1220 [576] .11

Total BTUH [kW] 57.5 [16.85] 75 Sens BTUH [kW] 33.3 [9.76] [23.9] 3.1 Power

56.2 [16.47] 31.4 [9.20] 3.1

54.9 [16.09] 29.6 [8.67] 3.1

53.3 [15.62] 38.9 [11.40] 3.1

52.1 [15.27] 36.8 [10.79] 3.1

51.0 [14.95] 34.6 [10.14] 3.0

51.4 [15.06] 41.3 [12.10] 3.1

50.3 [14.74] 39.0 [11.43] 3.1

49.2 [14.42] 36.7 [10.76] 3.0

Total BTUH [kW] 54.2 [15.88] 80 Sens BTUH [kW] 31.6 [9.26] [26.7] 3.3 Power

53.0 [15.53] 29.8 [8.73] 3.2

51.8 [15.18] 28.1 [8.24] 3.2

50.0 [14.65] 37.2 [10.90] 3.2

48.9 [14.33] 35.2 [10.32] 3.2

47.8 [14.01] 33.1 [9.70] 3.2

48.2 [14.13] 39.6 [11.61] 3.2

47.1 [13.80] 37.4 [10.96] 3.2

46.0 [13.48] 35.2 [10.32] 3.2

Total BTUH [kW] 52.0 [15.24] 85 Sens BTUH [kW] 30.4 [8.91] [29.4] 3.4 Power

50.8 [14.89] 28.7 [8.41] 3.4

49.7 [14.57] 27.0 [7.91] 3.4

47.8 [14.01] 36.1 [10.58] 3.4

46.7 [13.69] 34.1 [9.99] 3.4

45.7 [13.39] 32.1 [9.41] 3.3

45.9 [13.45] 38.4 [11.25] 3.4

44.9 [13.16] 36.3 [10.64] 3.4

43.9 [12.87] 34.2 [10.02] 3.3

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

50.5 [14.80] 29.6 [8.67] 3.6

49.4 [14.48] 27.9 [8.18] 3.6

48.3 [14.16] 26.3 [7.71] 3.5

46.4 [13.60] 35.2 [10.32] 3.6

45.3 [13.28] 33.3 [9.76] 3.5

44.3 [12.98] 31.3 [9.17] 3.5

44.5 [13.04] 37.6 [11.02] 3.6

43.5 [12.75] 35.5 [10.40] 3.5

42.5 [12.46] 33.4 [9.79] 3.5

49.6 [14.54] 29.0 [8.50] 3.7

48.5 [14.21] 27.4 [8.03] 3.7

47.4 [13.89] 25.8 [7.56] 3.7

45.5 [13.33] 34.7 [10.17] 3.7

44.5 [13.04] 32.8 [9.61] 3.7

43.5 [12.75] 30.9 [9.06] 3.6

43.6 [12.78] 37.0 [10.84] 3.7

42.6 [12.48] 35.0 [10.26] 3.7

41.7 [12.22] 32.9 [9.64] 3.6

49.0 [14.36] 28.6 [8.38] 3.9

47.9 [14.04] 27.0 [7.91] 3.9

46.8 [13.72] 25.5 [7.47] 3.8

44.8 [13.13] 34.3 [10.05] 3.9

43.8 [12.84] 32.4 [9.50] 3.8

42.8 [12.54] 30.5 [8.94] 3.8

42.9 [12.57] 36.6 [10.73] 3.9

42.0 [12.31] 34.6 [10.14] 3.8

41.0 [12.02] 32.6 [9.55] 3.8

Total BTUH [kW] 48.3 [14.16] 105 Sens BTUH [kW] 28.3 [8.29] [40.6] 4.1 Power

47.2 [13.83] 26.7 [7.83] 4.0

46.1 [13.51] 25.1 [7.36] 4.0

44.1 [12.92] 33.9 [9.94] 4.0

43.2 [12.66] 32.0 [9.38] 4.0

42.2 [12.37] 30.2 [8.85] 3.9

42.3 [12.40] 36.3 [10.64] 4.0

41.3 [12.10] 34.3 [10.05] 4.0

40.4 [11.84] 32.3 [9.47] 3.9

46.3 [13.57] 26.3 [7.71] 4.2 44.8 [13.13] 25.7 [7.53] 4.3

45.2 [13.25] 24.8 [7.27] 4.1 43.7 [12.81] 24.2 [7.09] 4.3

43.2 [12.66] 33.5 [9.82] 4.2 41.6 [12.19] 32.9 [9.64] 4.3

42.2 [12.37] 31.7 [9.29] 4.1 40.7 [11.93] 31.1 [9.11] 4.3

41.2 [12.07] 29.8 [8.73] 4.1 39.8 [11.66] 29.3 [8.59] 4.2

41.3 [12.10] 35.8 [10.49] 4.2 39.7 [11.63] 35.3 [10.35] 4.3

40.4 [11.84] 33.9 [9.94] 4.1 38.9 [11.40] 33.3 [9.76] 4.3

39.5 [11.58] 31.9 [9.35] 4.1 38.0 [11.14] 31.4 [9.20] 4.2

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1580 [746] .19

47.3 [13.86] 27.8 [8.15] 4.2 45.8 [13.42] 27.2 [7.97] 4.4

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQNA-042 IDB CFM [L/s] O U T D O O R D R Y B U L B T E M P E R A T U R E °F [°C]

0 [-17.8] 5 [-15] 10 [-12.2] 15 [-9.4] 20 [-6.7] 25 [-3.9] 30 [-1.1] 35 [1.7] 40 [4.4] 45 [7.2] 50 [10]

Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power

1580 [746]

60°F [15.5°C] 1400 [661]

16.0 [4.69] 2.2 18.0 [5.28] 2.3 20.3 [5.95] 2.3 22.9 [6.71] 2.4 25.6 [7.50] 2.4 28.5 [8.35] 2.5 31.4 [9.20] 2.5 34.2 [10.02] 2.6 37.0 [10.84] 2.6 39.5 [11.58] 2.7 41.8 [12.25] 2.7

15.8 [4.63] 2.2 17.8 [5.22] 2.3 20.1 [5.89] 2.4 22.7 [6.65] 2.4 25.4 [7.44] 2.5 28.2 [8.26] 2.5 31.1 [9.11] 2.6 33.9 [9.94] 2.6 36.6 [10.73] 2.7 39.2 [11.49] 2.7 41.5 [12.16] 2.8

1220 [576]

1580 [746]

15.7 [4.60] 14.4 [4.22] 2.3 2.5 17.7 [5.19] 16.4 [4.81] 2.3 2.6 20.0 [5.86] 18.7 [5.48] 2.4 2.6 22.5 [6.59] 21.3 [6.24] 2.4 2.7 25.2 [7.39] 24.1 [7.06] 2.5 2.7 28.0 [8.21] 26.9 [7.88] 2.6 2.8 30.8 [9.03] 29.8 [8.73] 2.6 2.8 33.6 [9.85] 32.6 [9.55] 2.7 2.9 36.3 [10.64] 35.4 [10.37] 2.7 2.9 38.8 [11.37] 38.0 [11.14] 2.8 3.0 41.1 [12.05] 40.3 [11.81] 2.8 3.0

IDB—Indoor air dry bulb

70°F [21.1°C] 1400 [661]

1220 [576]

1580 [746]

80°F [26.7°C] 1400 [661]

1220 [576]

14.3 [4.19] 2.6 16.3 [4.78] 2.6 18.6 [5.45] 2.7 21.1 [6.18] 2.7 23.8 [6.98] 2.8 26.7 [7.83] 2.8 29.5 [8.65] 2.9 32.4 [9.50] 2.9 35.1 [10.29] 3.0 37.6 [11.02] 3.0 39.9 [11.69] 3.1

14.2 [4.16] 2.6 16.1 [4.72] 2.7 18.4 [5.39] 2.7 20.9 [6.13] 2.8 23.6 [6.92] 2.8 26.4 [7.74] 2.9 29.3 [8.59] 2.9 32.1 [9.41] 3.0 34.8 [10.20] 3.0 37.3 [10.93] 3.1 39.6 [11.61] 3.1

13.4 [3.93] 2.8 15.4 [4.51] 2.9 17.7 [5.19] 2.9 20.3 [5.95] 3.0 23.0 [6.74] 3.0 25.9 [7.59] 3.1 28.8 [8.44] 3.1 31.6 [9.26] 3.2 34.4 [10.08] 3.3 36.9 [10.81] 3.3 39.2 [11.49] 3.4

13.3 [3.90] 2.9 15.2 [4.45] 2.9 17.6 [5.16] 3.0 20.1 [5.89] 3.0 22.8 [6.68] 3.1 25.7 [7.53] 3.1 28.5 [8.35] 3.2 31.3 [9.17] 3.3 34.1 [9.99] 3.3 36.6 [10.73] 3.4 38.9 [11.40] 3.4

13.1 [3.84] 2.9 15.1 [4.43] 3.0 17.4 [5.10] 3.0 19.9 [5.83] 3.1 22.6 [6.62] 3.1 25.4 [7.44] 3.2 28.3 [8.29] 3.2 31.1 [9.11] 3.3 33.8 [9.91] 3.4 36.3 [10.64] 3.4 38.5 [11.28] 3.5

[ ] Designates Metric Conversions

13

SYSTEMS PERFORMANCE—RQNA- SERIES COOLING PERFORMANCE DATA—RQNA-048 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1600 [755] .16

1400 [661] .11

1800 [850] .19

67°F [19.4°C] 1600 [755] .16

1400 [661] .11

1800 [850] .19

63°F [17.2°C] 1600 [755] .16

1400 [661] .11

Total BTUH [kW] 61.3 [17.97] 75 Sens BTUH [kW] 36.1 [10.58] [23.9] 3.4 Power

60.0 [17.58] 34.1 [9.99] 3.3

58.6 [17.17] 32.1 [9.41] 3.3

57.1 [16.73] 42.7 [12.51] 3.3

55.9 [16.38] 40.3 [11.81] 3.3

54.6 [16.00] 38.0 [11.14] 3.2

54.2 [15.88] 44.8 [13.13] 3.3

53.0 [15.53] 42.3 [12.40] 3.2

51.8 [15.18] 39.9 [11.69] 3.2

Total BTUH [kW] 60.0 [17.58] 80 Sens BTUH [kW] 35.7 [10.46] [26.7] 3.5 Power

58.7 [17.20] 33.7 [9.88] 3.5

57.3 [16.79] 31.7 [9.29] 3.5

55.8 [16.35] 42.2 [12.37] 3.5

54.6 [16.00] 39.9 [11.69] 3.4

53.3 [15.62] 37.6 [11.02] 3.4

52.9 [15.50] 44.4 [13.01] 3.5

51.7 [15.15] 41.9 [12.28] 3.4

50.5 [14.80] 39.5 [11.58] 3.4

Total BTUH [kW] 58.5 [17.14] 85 Sens BTUH [kW] 35.0 [10.26] [29.4] 3.7 Power

57.2 [16.76] 33.0 [9.67] 3.7

55.9 [16.38] 31.1 [9.11] 3.6

54.3 [15.91] 41.5 [12.16] 3.7

53.1 [15.56] 39.3 [11.52] 3.6

51.9 [15.21] 37.0 [10.84] 3.6

51.4 [15.06] 43.7 [12.81] 3.6

50.3 [14.74] 41.2 [12.07] 3.6

49.1 [14.39] 38.8 [11.37] 3.6

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

56.9 [16.68] 34.1 [9.99] 3.9

55.7 [16.32] 32.2 [9.44] 3.9

54.4 [15.94] 30.3 [8.88] 3.8

52.7 [15.44] 40.7 [11.93] 3.8

51.6 [15.12] 38.4 [11.25] 3.8

50.4 [14.77] 36.2 [10.61] 3.7

49.8 [14.59] 42.8 [12.54] 3.8

48.7 [14.27] 40.4 [11.84] 3.8

47.6 [13.95] 38.1 [11.17] 3.7

55.4 [16.24] 33.2 [9.73] 4.1

54.1 [15.86] 31.3 [9.17] 4.0

52.9 [15.50] 29.5 [8.65] 4.0

51.2 [15.01] 39.7 [11.63] 4.0

50.0 [14.65] 37.5 [10.99] 4.0

48.9 [14.33] 35.3 [10.35] 3.9

48.3 [14.16] 41.8 [12.25] 4.0

47.2 [13.83] 39.5 [11.58] 3.9

46.1 [13.51] 37.2 [10.90] 3.9

53.9 [15.80] 32.2 [9.44] 4.2

52.7 [15.44] 30.4 [8.91] 4.2

51.5 [15.09] 28.7 [8.41] 4.2

49.7 [14.57] 38.8 [11.37] 4.2

48.6 [14.24] 36.6 [10.73] 4.1

47.5 [13.92] 34.5 [10.11] 4.1

46.8 [13.72] 40.9 [11.99] 4.2

45.7 [13.39] 38.6 [11.31] 4.1

44.7 [13.10] 36.4 [10.67] 4.1

Total BTUH [kW] 52.5 [15.39] 105 Sens BTUH [kW] 31.4 [9.20] [40.6] 4.4 Power

51.3 [15.03] 29.6 [8.67] 4.4

50.2 [14.71] 27.9 [8.18] 4.3

48.3 [14.16] 37.9 [11.11] 4.4

47.2 [13.83] 35.8 [10.49] 4.3

46.2 [13.54] 33.7 [9.88] 4.3

45.4 [13.31] 40.0 [11.72] 4.3

44.4 [13.01] 37.8 [11.08] 4.3

43.4 [12.72] 35.6 [10.43] 4.2

50.2 [14.71] 29.0 [8.50] 4.5 49.3 [14.45] 28.7 [8.41] 4.7

49.1 [14.39] 27.3 [8.00] 4.5 48.2 [14.13] 27.0 [7.91] 4.7

47.2 [13.83] 37.3 [10.93] 4.5 46.3 [13.57] 36.9 [10.81] 4.7

46.1 [13.51] 35.2 [10.32] 4.5 45.2 [13.25] 34.9 [10.23] 4.7

45.1 [13.22] 33.2 [9.73] 4.4 44.2 [12.95] 32.8 [9.61] 4.6

44.3 [12.98] 39.4 [11.55] 4.5 43.4 [12.72] 39.0 [11.43] 4.7

43.3 [12.69] 37.2 [10.90] 4.5 42.4 [12.43] 36.9 [10.81] 4.6

42.3 [12.40] 35.0 [10.26] 4.4 41.4 [12.13] 34.7 [10.17] 4.6

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1800 [850] .19

51.3 [15.03] 30.7 [9.00] 4.6 50.5 [14.80] 30.3 [8.88] 4.8

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQNA-048 IDB CFM [L/s] O U T D O O R D R Y B U L B T E M P E R A T U R E °F [°C]

0 [-17.8] 5 [-15] 10 [-12.2] 15 [-9.4] 20 [-6.7] 25 [-3.9] 30 [-1.1] 35 [1.7] 40 [4.4] 45 [7.2] 50 [10]

Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power Total BTUH [kW] Power

1800 [850]

60°F [15.5°C] 1600 [755]

1400 [661]

1800 [850]

70°F [21.1°C] 1600 [755]

1400 [661]

1800 [850]

80°F [26.7°C] 1600 [755]

1400 [661]

15.1 [4.43] 2.6 18.3 [5.36] 2.6 21.8 [6.39] 2.7 25.5 [7.47] 2.7 29.3 [8.59] 2.8 33.0 [9.67] 2.9 36.6 [10.73] 2.9 39.8 [11.66] 3.0 42.7 [12.51] 3.0 45.0 [13.19] 3.1 46.5 [13.63] 3.2

14.9 [4.37] 2.6 18.1 [5.30] 2.7 21.6 [6.33] 2.7 25.3 [7.41] 2.8 29.0 [8.50] 2.8 32.7 [9.58] 2.9 36.3 [10.64] 3.0 39.5 [11.58] 3.0 42.3 [12.40] 3.1 44.6 [13.07] 3.2 46.1 [13.51] 3.2

14.8 [4.34] 2.6 17.9 [5.25] 2.7 21.4 [6.27] 2.8 25.0 [7.33] 2.8 28.8 [8.44] 2.9 32.4 [9.50] 3.0 35.9 [10.52] 3.0 39.1 [11.46] 3.1 41.9 [12.28] 3.1 44.2 [12.95] 3.2 45.7 [13.39] 3.3

14.3 [4.19] 3.0 17.5 [5.13] 3.1 21.0 [6.15] 3.1 24.7 [7.24] 3.2 28.5 [8.35] 3.3 32.3 [9.47] 3.3 35.8 [10.49] 3.4 39.1 [11.46] 3.5 41.9 [12.28] 3.5 44.2 [12.95] 3.6 45.8 [13.42] 3.6

14.2 [4.16] 3.1 17.3 [5.07] 3.1 20.8 [6.10] 3.2 24.5 [7.18] 3.3 28.3 [8.29] 3.3 32.0 [9.38] 3.4 35.5 [10.40] 3.4 38.7 [11.34] 3.5 41.5 [12.16] 3.6 43.8 [12.84] 3.6 45.4 [13.31] 3.7

14.1 [4.13] 3.1 17.2 [5.04] 3.2 20.6 [6.04] 3.2 24.3 [7.12] 3.3 28.0 [8.21] 3.4 31.7 [9.29] 3.4 35.2 [10.32] 3.5 38.4 [11.25] 3.6 41.2 [12.07] 3.6 43.4 [12.72] 3.7 45.0 [13.19] 3.8

13.4 [3.93] 3.4 16.6 [4.86] 3.4 20.1 [5.89] 3.5 23.9 [7.00] 3.5 27.6 [8.09] 3.6 31.4 [9.20] 3.7 34.9 [10.23] 3.7 38.2 [11.20] 3.8 41.0 [12.02] 3.9 43.3 [12.69] 3.9 44.9 [13.16] 4.0

13.3 [3.90] 3.4 16.5 [4.84] 3.5 20.0 [5.86] 3.5 23.6 [6.92] 3.6 27.4 [8.03] 3.7 31.1 [9.11] 3.7 34.6 [10.14] 3.8 37.9 [11.11] 3.9 40.7 [11.93] 3.9 42.9 [12.57] 4.0 44.5 [13.04] 4.0

13.2 [3.87] 3.5 16.3 [4.78] 3.5 19.8 [5.80] 3.6 23.4 [6.86] 3.7 27.2 [7.97] 3.7 30.8 [9.03] 3.8 34.3 [10.05] 3.8 37.5 [10.99] 3.9 40.3 [11.81] 4.0 42.5 [12.46] 4.0 44.1 [12.92] 4.1

IDB—Indoor air dry bulb

[ ] Designates Metric Conversions

14

15

1350 CFM/1700 CFM [496/802 L/s]

1225 CFM/1575 CFM [578/743 L/s]

1050 CFM/1350 CFM [496/637 L/s]

875 CFM/1125 CFM [413/531 L/s]

700 CFM/900 CFM [271/319 L/s]

Manufacturer Recommended Air-Flow Range (Min/Max) CFM

10x9 3/4 HP [559] 2 Speed Motor

10x9 3/4 HP [559] 2 Speed Motor

10x9 1/3 HP [248] 1 Speed Motor

10x9 1/2 HP [372] 2 Speed Motor

9x7 1/4 HP [186] 2 Speed Motor

Blower Size/ Motor HP [W] & # of Speeds

[ ] Designates Metric Conversions

NOTE: Effect of electric heat strip on airflow performance is negligible.

Low

Low

3.0 [10.55]

4.0 [14.07]

Low

2.5 [8.79]

Low

High

2.0 [7.03]

3.5 [12.31]

Motor Speed from Factory

Nominal Cooling Capacity Tons [kW]

High

Low

High

Low

High

High

Medium

Low

High

Low

Motor Speed

292 1076 [508]

CFM

1514 [715] 895 538

CFM RPM Watts

966 454

RPM Watts

1770 [835]

1675 [791]

CFM

CFM

321

390

870

RPM Watts 923

1559 [736]

CFM

RPM

268

Watts

824

RPM

1455 [687]

CFM Watts

352

355

466

989

1751 [826]

401

944

1658 [782]

327

893

1530 [722]

280

856

1431 [675]

805

785

RPM

1201 [567]

514

930

1461 [690]

415

810

1197 [565]

349

775

1059 [500]

278

965

861 [406]

214

785

657 [310]

0.2 [.05]

473

1018

1706 [805]

412

979

1610 [760]

338

932

1488 [702]

288

889

1396 [659]

346

830

1173 [554]

493

965

1415 [668]

407

855

1179 [556]

341

820

1032 [487]

266

995

822 [388]

203

870

634 [299]

0.3 [.07]

486

1050

1672 [789]

425

1013

1580 [746]

351

968

1454 [686]

303

931

1360 [642]

340

870

1137 [537]

473

985

1370 [647]

397

890

1162 [548]

331

865

996 [470]

253

1020

777 [367]

191

905

602 [284]

0.4 [.10]

490

1078

1624 [766]

433

1045

1535 [724]

364

1007

1417 [669]

311

968

1315 [621]

331

905

1090 [514]

454

1005

1322 [624]

386

920

1137 [537]

320

905

950 [448]

239

1045

721 [340]

171

940

560 [264]

0.5 [.12]

External Static Pressure—Inches W.C. [kPa]

481

1100

1555 [734]

440

1077

1491 [704]

371

1036

1375 [649]

325

1009

1285 [606]

320

950

1030 [486]

434

1025

1266 [597]

370

960

1097 [518]

305

940

896 [423]

221

1070

651 [307]

163

980

505 [238]

0.6 [.15]

CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—Wet Coil

Watts

1222 [577]

423

CFM

765

RPM

1222 [577]

Watts

CFM

356

940

RPM Watts 730

898 [424]

CFM

RPM

221

Watts

695

RPM

675 [319]

0.1 [.02]

Watts

CFM

INDOOR AIRFLOW PERFORMANCE—208 VOLTS 0.7 [.17]

460

1115

1463 [690]

432

1098

1422 [671]

381

1072

1336 [631]

331

1041

1241 [586]

306

990

954 [450]

412

1045

1197 [565]

351

995

1033 [488]

287

975

832 [393]

199

1090

562 [265]

149

1020

435 [205]

AIRFLOW PERFORMANCE—RQNA- SERIES

16

1350 CFM/1700 CFM [496/802 L/s]

1225 CFM/1575 CFM [578/743 L/s]

1050 CFM/1350 CFM [496/637 L/s]

875 CFM/1125 CFM [413/531 L/s]

700 CFM/900 CFM [271/319 L/s]

Manufacturer Recommended Air-Flow Range (Min/Max) CFM

10x9 3/4 HP [559] 2 Speed Motor

10x9 3/4 HP [559] 2 Speed Motor

10x9 1/3 HP [249] 1 Speed Motor

10x9 1/2 HP [373] 2 Speed Motor

9x7 1/4 HP [186] 2 Speed Motor

Blower Size/ Motor HP [W] & # of Speeds

High

Low

High

Low

High

High

Medium

Low

High

Low

Motor Speed

[ ] Designates Metric Conversions

DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE) CFM [L/s] 600 [283] 800 [378] Pressure Drop—Inches W.C. [kPa] .00 .01 [.002]

NOTE: Effect of electric heat strip on airflow performance is negligible.

Low

High

3.0 [10.55]

4.0 [14.07]

Low

2.5 [8.79]

Low

High

2.0 [7.03]

3.5 [12.31]

Motor Speed from Factory

Nominal Cooling Capacity Tons [kW]

315 1206 [569]

CFM

1641 [774] 980 589

CFM RPM Watts

440

1000 [472] .02 [.005]

955

RPM Watts

1748 [825]

1692 [799]

CFM

CFM

317

404

867

RPM Watts 931

1550 [732]

CFM

RPM

276

Watts

831

RPM

1467 [692]

CFM Watts

419

428

1200 [566] .03 [.007]

446

978

1718 [811]

409

950

1661 [784]

323

890

1520 [717]

282

854

1439 [679]

875

835

RPM

1357 [640]

565

1000

1577 [744]

498

900

1368 [646]

406

815

1182 [558]

303

1015

922 [435]

242

870

751 [354]

0.2 [.05]

1400 [661] .05 [.012]

462

1010

1686 [796]

424

982

1633 [771]

339

930

1486 [701]

297

894

1408 [665]

406

915

1312 [619]

543

1020

1515 [715]

481

935

1327 [626]

394

870

1157 [546]

288

1035

882 [416]

230

910

725 [342]

0.3 [.07]

1600 [775] .07 [.017]

475

1043

1647 [777]

434

1018

1589 [750]

355

974

1449 [684]

307

932

1360 [642]

392

940

1258 [594]

523

1035

1455 [687]

464

970

1285 [606]

381

910

1128 [532]

273

1055

830 [392]

217

950

691 [326]

0.4 [.10]

484

1073

1616 [763]

450

1054

1560 [736]

362

1003

1407 [664]

319

972

1331 [628]

378

965

1201 [567]

503

1050

1393 [657]

447

1000

1238 [584]

368

950

1091 [515]

257

1070

769 [363]

204

985

645 [304]

0.5 [.12]

External Static Pressure—Inches W.C. [kPa]

473

1096

1543 [728]

453

1082

1512 [714]

377

1039

1382 [652]

326

1005

1287 [607]

365

985

1145 [540]

481

1065

1329 [627]

431

1020

1183 [558]

353

975

1044 [493]

241

1085

701 [331]

189

1010

584 [276]

0.6 [.15]

CFM [L/s] Air Delivery/RPM/Watts—230 Volts Side Discharge—Wet Coil

Watts

1391 [656]

498

CFM

865

RPM

1411 [666]

Watts

CFM

419

990

RPM Watts 760

946 [446]

CFM

RPM

253

Watts

825

RPM

771 [364]

0.1 [.02]

Watts

CFM

INDOOR AIRFLOW PERFORMANCE—230 VOLTS 0.7 [.17]

459

1111

1472 [695]

443

1103

1442 [681]

385

1073

1337 [631]

341

1042

1259 [594]

355

1000

1093 [516]

456

1080

1262 [596]

391

1035

1116 [527]

334

1000

983 [464]

226

1100

630 [297]

181

1030

546 [258]

AIRFLOW PERFORMANCE—RQNA- SERIES

ELECTRICAL DATA—RQNA- SERIES

Evaporator Fan

Condenser Motor

Compressor Motor

Unit Information

ELECTRICAL DATA – RQNA- SERIES -024JK

-030JK

-036CK

-036JK

-042CK

-042JK

-048CK

-048JK

Unit Operating Voltage Range

187-253

187-253

187-253

187-253

187-253

187-253

187-253

187-253

Minimum Circuit Ampacity

17/17

21/21

16/16

24/24

25/25

32/32

25/25

37/37

20/20

25/25

20/20

30/30

30/30

40/40

30/30

45/45

25/25

30/30

25/25

35/35

35/35

45/45

35/35

50/50

1 208/230 1 2 3450 10.9/10.9 54/54 1 208/230 1 1/5 1.3 2.2 1 208/230 1 1/4 1.5 2.4

1 208/230 1 2 1/2 3450 13.5/13.5 72.5/72.5 1 208/230 1 1/5 1.3 2.2 1 208/230 1 1/2 2.4 5.1

1 200/230 3 3 3450 10.3/10.3 77/77 1 208/230 1 1/5 1.3 2.2 1 208/230 1 1/3 1.7 2.5

1 208/230 1 3 3450 16/16 88/88 1 208/230 1 1/5 1.3 2.2 1 208/230 1 1/3 1.7 2.5

1 200/230 3 3 1/2 3450 12.4/12.4 88/88 1 208/230 1 1/3 2 3.9 1 208/230 1 3/4 6.8 0

1 208/230 1 3 1/2 3450 17.9/17.9 95/95 1 208/230 1 1/3 2 3.9 1 208/230 1 3/4 6.8 0

1 200/230 3 4 3450 12.4/12.4 88/88 1 208/230 1 1/3 2 3.9 1 208/230 1 3/4 6.8 0

1 208/230 1 4 3450 22/22 137/137 1 208/230 1 1/3 2 3.9 1 208/230 1 3/4 6.8 0

Minimum Overcurrent Protection Device Size Maximum Overcurrent Protection Device Size No. Volts Phase HP RPM Amps (RLA) Amps (LRA) No. Volts Phase HP Amps (FLA) Amps (LRA) No. Volts Phase HP Amps (FLA) Amps (LRA)

1. Horsepower Per Compressor. 2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.

17

ELECTRIC HEATER KITS—RQNA- SERIES Unit Model Application

Electric Heater Kit Models RXQJ-A05J (208-240 volt, 1-ph, 5kW) RXQJ-A10J (208-240 volt, 1-ph, 10kW)

RQNA-024JK

RXQJ-A05J (208-240 volt, 1-ph, 5kW) RXQJ-A10J (208-240 volt, 1-ph, 10kW) RXQJ-A10J (208-240 volt, 1-ph, 10kW) RXQJ-A15J (208-240 volt, 1-ph, 15kW)

RQNA-030JK RQNA-036JK

RXQJ-B10J (208-240 volt, 1-ph, 10kW)

RQNA-042JK

RXQJ-B15J (208-240 volt, 1-ph, 15kW) RXQJ-B10J (208-240 volt, 1-ph, 10kW) RXQJ-B15J (208-240 volt, 1-ph, 15kW) RXQJ-A10C (208-240 volt, 3-ph, 10kW) RXQJ-A15C (208-240 volt, 3-ph, 15kW)

RQNA-048JK

RQNA-036CK

RXQJ-A10C (208-240 volt, 3-ph, 10kW)

RQNA-042CK

RXQJ-A15C (208-240 volt, 3-ph, 15kW) RXQJ-A10C (208-240 volt, 3-ph, 10kW) RXQJ-A15C (208-240 volt, 3-ph, 15kW)

RQNA-048CK

WARNING ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

18

19

048CK

042CK

036CK

Unit Model No. RQNA-

048JK

042JK

036JK

030JK

024JK

Unit Model No. RQNA-

No Heat A10C A15C No Heat A10C A15C No Heat A10C A15C

— 1 2 — 1 2 — 2 2 — 2 2 — 2 2

No. of Sequence Steps — 3.6/4.8 7.2/9.6 — 3.6/4.8 7.2/9.6 — 7.2/9.6 10.8/14.4 — 7.2/9.6 10.8/14.4 — 7.2/9.6 10.8/14.4 24.56/32.75 36.84/49.13

24.56/32.75 36.84/49.13

24.56/32.75 36.84/49.13

12.28/16.38 24.56/32.75

— 12.28/16.38 24.56/32.75

— 17.3/20.0 34.6/40.0 — 17.3/20.0 34.6/40.0 — 34.6/40.0 51.9/60.0 — 34.6/40.0 51.9/60.0 — 34.6/40.0 51.9/60.0

Rated Heater Heater Heater kW KBTU/Hr Amp. @ 208-240 V @ 208-240 V @ 208-240 V 17/17 39/42 60/67 21/21 43/46 64/71 24/24 67/74 88/99 31/31 74/81 96/106 36/36 79/86 101/111

Unit Min. Ckt. Ampacity @ 208-240 V Min./Max. @ 208 V 20/25 40/40 60/60 25/30 45/50 70/70 30/35 70/70 90/90 35/45 80/80 100/100 45/50 80/90 110/110

Min./Max. @ 240 V 20/25 45/45 70/70 25/30 50/50 80/80 30/35 80/80 100/100 35/45 90/90 110/110 45/50 90/90 125/125

Over Current Protective Device Size

Heat Pump

— 22/25 44/50 — 22/25 44/50 — 44/50 65/75 — 44/50 65/75 — 44/50 65/75

Min. Ckt. Ampacity 208/240V — 25/25 45/50 — 25/25 45/50 — 45/50 70/80 — 45/50 70/80 — 45/50 70/80

Max. Fuse Size 208/240V

Heater Kit

17/17 — — 21/21 — — 24/24 — — 31/31 — — 36/36 — —

Min. Circuit Ampacity 208-240 V Min./Max. @ 208 V 20/25 — — 25/30 — — 30/35 — — 35/45 — — 45/50 — —

— 3 3 — 3 3 — 3 3

— 3 3 — 3 3 — 3 3

No. of Sequence Steps — 7.2/9.6 10.8/14.4 — 7.2/9.6 10.8/14.4 — 7.2/9.6 10.8/14.4 24.56/32.75 36.84/49.13

24.56/32.75 36.84/49.13

24.56/32.75 36.84/49.13

— 20.0/23.1 30.1/34.7 — 20.0/23.1 30.1/34.7 — 20.0/23.1 30.1/34.7

Heater Heater Rated KBTU/Hr Amp. Heater kW @ 208-240 V @ 208-240 V @ 208-240 V

Heater Kit

16/16 41/45 54/60 24/24 49/53 62/67 26/26 51/55 63/69

Unit Min. Ckt. Ampacity @ 208-240 V

Single Power Supply For Both Unit and Heater Kit

Min./Max. @ 208 V 20/25 45/45 60/60 30/35 50/50 70/70 30/35 60/60 70/70

Min./Max. @ 240 V 20/25 45/45 60/60 30/35 60/60 70/70 30/35 60/60 70/70

Over Current Protective Device Size

Heat Pump

— 25/29 38/44 — 25/29 38/44 — 25/29 38/44

Min. Ckt. Ampacity 208/240V

— 25/30 40/45 — 25/30 40/45 — 25/30 40/45

Max. Fuse Size 208/240V

Heater Kit

16/16 — — 24/24 — — 26/26 — —

Min. Circuit Ampacity 208-240 V

Min./Max. @ 208 V 20/25 — — 30/35 — — 30/35 — —

Min./Max. @ 240 V 20/25 — — 30/35 — — 30/35 — —

Over Current Protective Device Size

Heat Pump

Separate Power Supply For Both Unit and Heater Kit

Min./Max. @ 240 V 20/25 — — 25/30 — — 30/35 — — 35/45 — — 45/50 — —

Over Current Protective Device Size

Heat Pump

Separate Power Supply For Both Unit and Heater Kit

208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION

— 1 2 — 1 2 — 2 3 — 2 3 — 2 3

RXQJNo. of Heater Kit Elements Nominal kW

No Heat A05J A10J No Heat A05J A10J No Heat A10J A15J No Heat B10J B15J No Heat B10J B15J

RXQJNo. of Heater Kit Elements Nominal kW

Heater Kit

Single Power Supply For Both Unit and Heater Kit

208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION

ELECTRIC HEATER KITS—RQNA- SERIES

UNIT DIMENSIONS—RQNA- SERIES UNIT DIMENSIONS SELF-CONTAINED AIR CONDITIONERS

OUTDOOR FAN GRILLE AND COMPRESSOR ACCESS

CONTROL ACCESS PANEL

FILTER ACCESS PANEL (FOR UNIT MOUNTED FILTER ACCESSORY)

LIQUID PRESSURE SERVICE PORT

OUTDOOR COIL PROTECTIVE GRILLE

30% 2%

SUCTION PRESSURE SERVICE PORT

21% 2%

THREADED PVC CONDENSATE DRAIN CONNECTION (3/4" [19.05 mm] N.P.T.) THERMOSTAT WIRING ENTRANCE

29% 2%

ELECTRICAL POWER ENTRANCE

CORNER WEIGHTS % OF TOTAL UNIT WEIGHT

20% 2%

SIDE RETURN DUCT OPENING BLOWER/ EVAPORATOR ACCESS PANEL

TOP VIEW

SIDE SUPPLY DUCT OPENING

BOTTOM VIEW 451/16" [1145 mm] INSIDE

4719/32" [1209 mm]

13/16" [30 mm] TYP.

11/2" [38 mm] TYP.

BOTTOM RETURN DUCT OPENING 5013/16" [1290 mm]

497/16" [1256 mm] INSIDE

BOTTOM SUPPLY DUCT OPENING

141/4" [362 mm] TYP.

199/16" [497 mm]

OUTDOOR FAN GRILLE & COMPRESSOR ACCESS

313/16" [97 mm]

[ ] Designates Metric Conversions

20

45/16" [95 mm]

153/8" [391 mm]

33/16" [97 mm]

UNIT DIMENSIONS—RQNA- SERIES SIDE VIEW

SIDE VIEW OUTDOOR COIL PROTECTIVE GRILLE

FILTER ACCESS PANEL (FOR UNIT MOUNTED FILTER ACCESSORY)

THERMOSTAT WIRE ENTRANCE

11/8" [28.6 mm]

255/16" [643 mm]

103/16" [259 mm] 51/16" [129 mm]

43/4" [121 mm]

ELECTRICAL POWER ENTRANCE

527/16" [1332 mm]

BLOWER/ EVAPORATOR ACCESS PANEL

BACK VIEW

FRONT VIEW

CONTROL ACCESS PANEL 47/8" [124 mm]

SIDE SUPPLY DUCT OPENING

LIQUID PRESSURE SERVICE PORT

133/4" [349 mm]

75/16" [186 mm]

57/16" [138 mm] 81/2" [216 mm] TYP.

2211/16" [576 mm]

47/16" [113 mm]

471/2" [1207 mm]

THREADED PVC CONDENSATED DRAIN CONNECTION (3/4 N.P.T.)

15" [381 mm]

143/16" [360 mm] TYP. 191/8" [486 mm]

SHOWN WITH DUCT COVERS REMOVED. SUCTION PRESSURE SERVICE PORT

IMPORTANT: INSTALLATION MUST NOT INTERFERE WITH DRAINAGE OPENINGS IN BOTTOM OF UNIT UNDER OUTDOOR COIL.

Model Number

Height “A”

024

3515/16

030, 036, 042, 048

41

[ ] Designates Metric Conversions

21

IMPORTANT: UNIT MUST BE LEVEL TO PREVENT WATER MIGRATION.

SIDE RETURN DUCT OPENING

TYPICAL INSTALLATIONS

[ ] Designates Metric Conversions

22

ACCESSORIES ACCESSORY EQUIPMENT Accessory Description

Model Application RQNA-

Thermostats

Accessory Model No. See Thermostat Specification Sheet (T22-001) RXQG-AAA14 (14" [356 mm] Height) RXQG-AAA24 (24" [610 mm] Height) RXRN-D15 RXRE-CAA30 (3 Position) RXRD-CAM10 (Fully Modulating)

Roofcurbs

RQNA-

Supply & Return Diffusers

RQNA-

Economizers (Downflow Only)

RQNA-

Economizers (Sideflow Only)

RQNA-

RXRD-CCM10 (Fully Modulating) RXRE-CAA30 (3 Position)

Fresh Air Damper

RQNA-

RXRF-FAB1 (Motorized-35%) RXRF-FAA1 (Fixed-35%)

Rectangular to Round Transition (Downflow)

RQNA-

Filter Kit High Pressure Control

RQNARQNA-

RXMC-CA02 (16" [406 mm] Ducts) RXMC-CA03 (18" [457 mm] Ducts) RXRY-01 RXAB-A04

Outdoor Thermostat

RQNA-

RXPT-A01

Low Ambient Control Duct Adapter Sideflow Square to Round Transition

RQNARQNA-

RXPZ-C01 or RXPZ-F01 RXMC-A01

COMMON SUPPLY/RETURN CONCENTRIC AIR DIFFUSER

SUPPLY/RETURN DIFFUSER

NOTE: The location of the combination supply and return diffuser should not exceed 10 feet [3.05 m] above the floor level for units @ 1000 CFM [472 L/s] or less and 12 [3.66 m] to 14 feet [4.27 m] above the floor level for units with CFM greater than 1000 [472 L/s]. If the diffuser is installed with a greater distance than recommended above, the supply air may become stratified above the required comfort area causing uncomfortable conditions.

AIRFLOW/PRESSURE DROP INFORMATION (INCHES W.C. [kPa]) Designed to convert a side by side or an over and under arrangement into a concentric distribution of air. The diffuser is flush mounted, completely insulated, assembled, and internally baffled to provide four way supply air distribution with a center return. To make the assembly complete and ready to fit into a 2' [0.61 m] x 4' [1.22 m] suspended ceiling grid, the diffuser includes adjustable supply louvers, hanging rings, anti-sweat gasket, and round flanges for use with flexible ducts.

Approximate CFM [L/s]-Supply Air 1300 [614] 1575 [743] 1800 [850] 2200 [1038] Plenum & Supply/Return Duct .07 [.017] .10 [.024] .12 [.030] .17 [.042] Diffuser .09 [.022] .13 [.032] .16 [.040] .24 [.060] Economizer .06 [.015] .09 [.022] .11 [.027] .17 [.042] Accessory

SUPPLY AIR/PERFORMANCE Model No. RXRNBD15

Diameter Inches [mm] 16 [406]

Shipping Wt. Lbs. [kg] 90 [40.82]

Diffuser Airflow CFM [L/s] 800 [378]-1200 [566] 1600 [755]-2000 [944]

Dimension A Inches [mm] 201/2 [521]

Range of Throw Ft. [m] 14 [4.27]-16 [4.88] 18 [5.49]-28 [8.53] [ ] Designates Metric Conversions

23

ACCESSORIES

24

ACCESSORIES DUCT ADAPTERS RECTANGULAR TO ROUND TRANSITIONS (DOWNFLOW)

RXMC-CA02

RXMC-CA03

[ ] Designates Metric Conversions

25

ACCESSORIES FRESH AIR DAMPER FOR USE ON RQNA- SERIES RXRF-FAA1 (Fixed - 0-35%) The 0-35% manual outside Air Damper is designed to replace the unit return air duct cover. No drilling or damper assembly is required. The amount of outside air (0-35%) is controlled by simply adjusting the side damper. RXRF-FAB1 (Motorized - 0-35%) The 0-35% motorized outside Air Damper is designed to replace the unit return air duct cover. No drilling or damper assembly is required. The control motor opens the adjustable slide damper when the unit blower motor is energized.

ECONOMIZERS RXRE-CAA30 (3 Position) and RXRD-CAM10 (Fully Modulating) for RQNA- Series RXRE-CAA30 (3 Position) Provided with enthalpy control, and mixed air sensor. Settings include fully open, fully closed and adjustable mid point. RXRD-CAM10 (Fully Modulating) Provided with enthalpy control, mixed air sensor and minimum position potentiometer for proportioning (modulating) the amount of fresh air.

[ ] Designates Metric Conversions

26

ACCESSORIES ECONOMIZERS RXRD-CCM10 (Fully Modulating) and RXRE-CCA30 (3 Position) Horizontal Application RXRD-CCM10 (Fully Modulating) Provided with enthalpy control, mixed air sensor and minimum position potentiometer for proportioning (modulating) the amount of fresh air. RXRE-CCA30 (3 Position) Has outdoor air sensor, minimum position potentiometer and mixed air sensor to provide three damper positions. [ ] Designates Metric Conversions

27

ACCESSORIES FILTER KIT INSTALLATION RXRY-01 For use in either vertical or horizontal discharge.

Minimum Airflow 510 [241] 680 [321] 850 [401] 1020 [481] 1190 [562] 1275 [602] 1700 [802]

CFM [L/s] Nominal Airflow 600 [283] 800 [378] 1000 [472] 1200 [566] 1400 [661] 1500 [708] 2000 [944]

Airflow Pressure Drop, Inches W.C. [kPa] CFM [L/s] 1" Filter 2" Filter 500 [236] .02 [.0050] .03 [.0075] 600 [283] .02 [.0050] .03 [.0075] 700 [330] .03 [.0075] .04 [.0010] 800 [378] .04 [.0010] .05 [.0124] 900 [425] .05 [.0124] .06 [.0149] 1000 [472] .07 [.0174] .08 [.0199] 1100 [519] .08 [.0199] .09 [.0224] 1200 [566] .10 [.0249] .12 [.0299] 1300 [614] .13 [.0324] .15 [.0373] 1400 [661] .16 [.0398] .19 [.0473] 1500 [708] .19 [.0473] .21 [.0523] 1600 [755] .20 [.0498] .23 [.0572] 1700 [802] .21 [.0523] .24 [.0598] 1800 [850] .22 [.0548] .25 [.0623] 1900 [897] .24 [.0598] .27 [.0672] 2000 [944] .26 [.0647] .29 [.0722]

Maximum Airflow 660 [311] 880 [415] 1100 [519] 1320 [623] 1540 [727] 1650 [779] 2200 [1039]

[ ] Designates Metric Conversions

28

ACCESSORIES DUCT ADAPTER SIDEFLOW SQUARE TO ROUND TRANSITION RXMC-BA01 Adapts the side rectangular supply and return openings to 14" [356 mm] diameter round openings. Adapters provided with same finish as unit and also provided with thermal insulation.

29

ACCESSORIES Roofcurb (Sloped)

RXQG-AAA14 (14" [356 mm] High)

RXQG-AAA14 & RXQG-AAA24 for RQNA- Series Heat pump models must use sloped curbs. Hinged corners make for fast, easy set-up.

RXQG-AAA24 (24" [610 mm] High)

Packaged Heat Pump Roofcurb Installation (Sloped) OUTDOOR FAN GRILLE AND COMPRESSOR ACCESS

OUTDOOR COIL PROTECTIVE GRILLE

5" [127 mm]

IMPORTANT: UNIT MUST BE LEVEL TO PREVENT WATER MIGRATION

LIQUID PRESSURE SERVICE PORT SUCTION PRESSURE SERVICE PORT

207/8" [530.2 mm]

THREADED PVC CONDENSATE DRAIN CONNECTION (3/4" [19.05 mm] N.P.T.)

CONTROL ACCESS PANEL

[ ] Designates Metric Conversions

30

ACCESSORIES ROOFCURB ADAPTERS Fabricated from galvanized steel to adapt the New cabinet to the old style curb. All are furnished with a New gasket. OLD MODEL PACKAGE HEAT PUMP

OLD CURB MODEL

SMALL CABINET (11/2-2 TON) [5.28-7.03 kW] RPNCRPND-

20 SERIES

RXPA-CA20

MEDIUM CABINET (21/2-3 TON) [8.79-10.55 kW] RPNCRPND-

21 SERIES

RXPA-CA21

EXTRA LARGE CABINET (31/2-5 TON) [12.31-17.58 kW] RPNCRPND-

23 SERIES

RXPA-CA23

NEW MODEL TO OLD MODEL ROOFCURB ADAPTER

NEW MODEL PACKAGE HEAT PUMP

ONLY 1 CABINET SIZE— ALL MODELS RXPX-BACCA20 RXPX-BACCA21 RXPX-BCCCA23

(1) SLOPE TYPE (2) FULL PERIMETER TYPE [ ] Designates Metric Conversions

31

RQNA-

WIRING SCHEMATICS—RQNA- SERIES

32

WIRING SCHEMATICS—RQNA- SERIES

33

WIRING SCHEMATICS—RQNA- SERIES

34

WIRING SCHEMATICS—RQNA- SERIES

35

BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM YOUR RETAILER.

GENERAL TERMS OF LIMITED WARRANTY Ruud will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty. For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or Contact the Manufacturer for a Copy.

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

*Electric Heating Elements for Optional Electric Heating Kits ..................................Five (5) Years *Compressor.................................................Five (5) Years Any Other Part 1-Phase Models ............................................Five (5) Years 3-Phase Models ..............................................One (1) Year

RUUD AIR CONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72908

“In keeping with its policy of continuous progress and product improvement, Ruud reserves the right to make changes without notice.” PRINTED IN U.S.A.

10-07 DC

FORM NO. P22-764 REV. 4 Supersedes Form N o . P 2 2 - 7 6 4 R e v. 3