OMX-AV Control Interface

OMX-AV GRAFIK Systems Control Interfaces omxav-1 06.14.04 OMX-AV Control Interface Description • Integrates GRAFIK 5000/6000/7000 Systems with equi...
Author: Hilda Cummings
61 downloads 1 Views 111KB Size
OMX-AV

GRAFIK Systems

Control Interfaces omxav-1 06.14.04

OMX-AV Control Interface Description • Integrates GRAFIK 5000/6000/7000 Systems with equipment that has contact-closure I/O, including: – Motion and occupant sensors. – Timeclocks and push buttons. – Motorized projection screens, skylights, window shades, and movable walls. – AV equipment. – Security systems. • Use the GRAFIK Systems Processor Panel to setup the OMX-AV Interface for different modes, functions, and momentary/maintained inputs and outputs. Inputs/Outputs • Provides five inputs and five outputs. • Using the inputs, contact closures in other equipment can operate controls to: – Select scenes. – Run sequences (loop through scenes). – Lock lighting controls to prevent changes. – Activate panic mode (lights go full on). – Adjust control logic to reflect status of movable walls. – Turn lights on or off based on room occupancy. • Using the outputs, scene changes in lighting controls can: – Trigger outputs to control other equipment. – Provide status feedback to other equipment.

R

S P E C I F I C AT I O N S U B M I T TA L

Job Name: Job Number:

Model Numbers:

Page 1

OMX-AV

GRAFIK Systems

Control Interfaces omxav-2 06.14.04

Specifications Power • Low-voltage Class 2 (PELV). Operating Voltage: 32 V Direct Current. • Provides 2-way interface between lighting controls and dry contact closure devices. • Provides 5 inputs and 5 outputs. Outputs can control other manufacturers’ equipment. Operating Modes • • • •

Scene selection Special functions Partitioning Occupant sensor Five Input Terminals

• • • • • •

Accept maintained inputs and momentary inputs with 40msec minimum pulse times. Inputs must be dry contact closure or open collector (NPN). On-state saturation voltage must be less than 2.0VDC. Off-state leakage current must be less than 10µA. Open circuit voltage: 36V maximum. Short circuit current: 4.0µA maximum. Five Output Terminals

• Provide solid-state maintained or momentary (1-second) outputs. • Outputs require an external relay and power supply (30VDC max., Class 2/PELV) by others for contact closure devices. • Maximum voltage: 38V • Maximum current: 200mA • Open collector (NPN) output: On-state saturation voltage 1.0V maximum, off state leakage current 0.1µA maximum. Status LEDs Five Status LEDs light when associated output is active (on). System Communications and Capacity Low-voltage type Class 2 (PELV) wiring connects OMX-AV Interface to Processor Panel. Environment 32-104°F (0-40°C). Relative humidity less than 90% non-condensing.

R

S P E C I F I C AT I O N S U B M I T TA L

Job Name: Job Number:

Model Numbers:

Page 2

OMX-AV

GRAFIK Systems

Control Interfaces omxav-3 06.14.04

Dimensions Front

Side

7 3/4” (197mm)

DIP Switches

4

5

6

2 34 MUX LINK

1

2

MUX

+V

1

2

3

4

5 1

2

INPUTS

34 MUX

8

C

MUX LINK COM

7

C

1

2

3

3

C 4

5

OUTPUTS

4

INPUTS

5 1

2

3

C 4

OUTPUTS

Class 2 (PELV) Wiring

5 COM

1

3

PROGRAM SWITCH

MUX Link to Processor Panel

2

COM

1

2 1/2” (84mm)

6” (127mm)

Mounting • Mount on a 4" (10.2mm) square junction box. • May also mount directly to the wall. • Ensure that the metal casing is grounded. Connect a ground wire to the ground screw. • Note that wires do not feed through the back of the unit. 4”x4” Junction Box OMX-AV

OMX-AV

Wall Wall Insert Wires Through Punch-Outs

R

S P E C I F I C AT I O N S U B M I T TA L

Job Name: Job Number:

Model Numbers:

Page 3

OMX-AV

GRAFIK Systems

Control Interfaces omxav-4 06.14.04

Low-Voltage Class 2 (PELV) Wiring • Daisy-chain the OMX-AV Interface to the Class 2 (PELV) Wallstation Link that connects to the Processor Panel. • Make daisy-chain connections to the low-voltage Class 2 (PELV) MUX Link terminals on front of OMX-AV Interface. • Do not use T-taps. Run all wires in and out of the terminal block. • Each terminal accepts up to two #18 AWG (1.0mm2) wires. • Consult Processor Panel Specification Submittal for more details.

2 1

3

Power Supply

Output 5

+ V –

4 5

C 1 2 3 4 5 1 2 3 4 5 C Program Switch

MUX

MUX

+V

COM

1 2 3 4 MUX Link

Output 4

Output 3

Output 2

Output 1

Input 5

Input 4

Input 3

To Processor Panel

Input 2

Input 1

User-Supplied Equipment

Inputs

Outputs

OMX-AV To up to 31 additional Control Interfaces, Control Units, or Wallstations

R

S P E C I F I C AT I O N S U B M I T TA L

Job Name: Job Number:

Model Numbers:

Page 4

OMX-AV

GRAFIK Systems

Control Interfaces omxav-5 06.14.04

Class 2 (PELV) Terminal Connections • Two #12 AWG (2.5mm2) conductors for common (terminal 1) and 32VDC (terminal 2). These will not fit in terminals. Connect as shown. • One shielded, twisted pair #18 AWG (1.0mm2) for data link (terminals 3 and 4). • Connect Drain/Shield as shown. Do not connect to Ground (Earth) or Wallstation/Control Interfaces. Connect the bare drain wires and cut off the outside shield.

Data Link - (1) twisted, shielded pair #18 AWG (1.0mm2) 3: MUX D: Drain/Shield 4: MUX

(2) #12 AWG (2.5mm2)

2

3

6

7

8

C

1

2

3

4

5 1

2

INPUTS

4 MUX

+V

MUX

COM

5

2 3 4 MUX LINK

MUX LINK

(1) #18 AWG (1.0mm2)

C

1

2

3

INPUTS

3

4

5

C

OUTPUTS

4

5 1

2

3

4

OUTPUTS

5

C

OMX-AV

(2) #12 AWG (2.5mm2)

R

4

COM

1

3

PROGRAM SWITCH

1

2

COM

1

(1) #18 AWG (1.0mm2)

Class 2/PELV Control wiring 1: Common 2: 32VDC

S P E C I F I C AT I O N S U B M I T TA L

Job Name: Job Number:

Model Numbers:

Page 5