NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

K406

MIDWOOD AF (MAIN) - BROOKLYN, 1124 EAST 17TH STREET, BROOKLYN, NY, 11210

School: InspectionId

Inspection Type

700 ELECTRICAL

Time In

Last Edited

2014-11-12 08:25AM

2015-02-20 05:23PM

Asset Data Question

Answer

Have any Systems/Major Building Components been upgraded?

Systems:

Scoreboard

Years: Systems:

2009 Security Lights

Years: Systems:

2000, 2009, 2013 Panel Boards - Molded Case Circuit Breaker Type

Years: 1976 Below Ground

Type of Service Does Interactive Whiteboard (IWB) Exist?

No

DEDICATED INTERCOMS IN FIRE RESCUE AREAS Question Are there any Life Rescue Assistance Areas, Fire Rescue Areas, and/or Holding Rooms in your building?

Response No

Priority Condition Priority Condition Exist Last Year?

Priority Category

Condition Description

Component Affected

Location Description

Person(s) Notified

Person(s) Title

PhotoImage

No condition recorded

Inspection Question

Response

Electrical ATHLETIC FIELD

Inspected

Exterior Lighting

Inspected

Condition

5- Poor

Replacement Quantity Replacement Uom

8 EACH

Deficiency Deficiency Quantity

LIGHTING FIXTURE NOT OPERATIONAL 8 EACH REPLACE PRIORITY 3 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Local Sound System

Does not exist

Scoreboard

Inspected

Instance

Athletic Field - North 1- Good

Instance Condition Instance Quantity Instance Quantity Uom

1 EACH

Deficiency

No deficiencies recorded

AUDITORIUM

Does not exist

AUXILIARY SIGNAL/BELL SYSTEM

Does not exist

CAFETERIA

Does not exist

CITY FIRE ALARM SYSTEM

Does not exist

CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE

Inspected Inspected

Lighting Does a Chandelier Exist?

No Inspected

Lighting Fixture - Fluorescent

Inspected

Pendant Mounted

3- Fair

Condition Deficiency Deficiency Quantity Mobile Validity Version 2.0 (P)

LIGHTING FIXTURE BEYOND USEFUL LIFE 25 Page 1 of 9

Print Date: 6/16/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

K406

Question

Response

CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE Lighting Lighting Fixture - Fluorescent Pendant Mounted

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations

EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded Inspected

Recessed Mounted

3- Fair

Condition Deficiency Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE 2 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations

Does not exist

Surface Mounted Lighting Fixture - HID

Does not exist

Lighting Fixture - Incandescent

Inspected Inspected

Pendant Mounted

3- Fair

Condition Deficiency Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE 16 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Recessed Mounted

Does not exist

Surface Mounted

Inspected 3- Fair

Condition Deficiency Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE 8 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations

Does not exist

Lighting Fixture - LED COMPUTER LAB

Does not exist

EMERGENCY DC STANDBY BATTERY POWER

Does not exist

EMERGENCY GENERATOR SET

Does not exist

EMERGENCY LIGHT/EXIT LIGHT PANEL

Does not exist

EMERGENCY LIGHTING

Does not exist

EXIT LIGHT

Does not exist

EXIT/EMERGENCY LIGHT

Does not exist

FIRE ALARM SYSTEM

Inspected

Area Smoke Detector

Does not exist

Bell/Horn

Does not exist

Duct Smoke Detector

Does not exist

Elevator Recall

Does not exist

Fan Shutdown Control

Does not exist

Fire Alarm Digital Communicator

Does not exist

Mobile Validity Version 2.0 (P)

Page 2 of 9

Print Date: 6/16/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

K406

Question

Response

FIRE ALARM SYSTEM

Inspected

Fused Cutout Panel

3- Fair

Condition Deficiency

No deficiencies recorded

Heat Detector

Does not exist

Magnetic Door Holder/Contactor

Does not exist

Main Panel

Inspected Inspected

Bell At Panel

Condition

3- Fair

Deficiency

No deficiencies recorded

Fire Alarm Control Panel (Electronic)

Does not exist

Fire Alarm Control Panel (Standard)

Inspected

Instance

Storage Building 3- Fair

Instance Condition Instance Quantity Instance Quantity Uom

1 EACH

Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year

ACME Sprinkler Control Panel 2 Circuits Inspector Estimate 1976 Documented

Deficiency Deficiency Location/Instance Deficiency Quantity

BEYOND USEFUL LIFE Storage Building 12,000 S.F. REPLACE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Manual Pull Station

Does not exist

Remote Annunciator

Does not exist

Sprinkler Flow/Air Pressure Switch

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded

Strobe

Does not exist

Sub-Panel

Does not exist

Tamper Flow Switch/Chain

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded Inspected

GROUNDING SYSTEM

3- Fair

Condition Deficiency

No deficiencies recorded

GYMNASIUM

Does not exist

INTERCOM SYSTEM

Does not exist

KITCHEN/WARMING PANTRY

Does not exist

LAN

Does not exist

LIBRARY

Does not exist

LIGHTNING PROTECTION

Does not exist

LOCKER ROOM

Instance on 1st Floor - Boys

Inspected

Alternative Use

No

Instance on 1st Floor - Boys - Visitor

Inspected

Alternative Use

No

Mobile Validity Version 2.0 (P)

Page 3 of 9

Print Date: 6/16/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

K406

Question

Response

LOCKER ROOM Instance on 1st Floor - Girls

Inspected

Alternative Use

No

Instance on 1st Floor - Girls - Visitor

Inspected

Alternative Use

No

Instance on 1st Floor - Boys

Inspected

Instance on 1st Floor - Boys - Visitor

Inspected

Instance on 1st Floor - Girls

Inspected

Instance on 1st Floor - Girls - Visitor

Inspected

Lighting

Lighting Fixture - Fluorescent

Instance on 1st Floor - Boys

Does not exist

Instance on 1st Floor - Boys - Visitor

Does not exist

Instance on 1st Floor - Girls

Does not exist

Instance on 1st Floor - Girls - Visitor

Does not exist

Lighting Fixture - HID

Instance on 1st Floor - Boys

Does not exist

Instance on 1st Floor - Boys - Visitor

Does not exist

Instance on 1st Floor - Girls

Does not exist

Instance on 1st Floor - Girls - Visitor

Does not exist

Lighting Fixture - Incandescent

Instance on 1st Floor - Boys

Inspected

Instance on 1st Floor - Boys - Visitor

Inspected

Instance on 1st Floor - Girls

Inspected

Instance on 1st Floor - Girls - Visitor

Inspected

Pendant Mounted

Instance on 1st Floor - Boys

Inspected

Instance Condition

3- Fair

Deficiency Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE 9 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Instance on 1st Floor - Boys - Visitor

Inspected

Instance Condition

3- Fair

Deficiency Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE 9 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Instance on 1st Floor - Girls

Does not exist

Instance on 1st Floor - Girls - Visitor

Does not exist

Recessed Mounted

Instance on 1st Floor - Boys

Does not exist

Instance on 1st Floor - Boys - Visitor

Does not exist

Instance on 1st Floor - Girls

Does not exist

Instance on 1st Floor - Girls - Visitor

Does not exist

Surface Mounted

Instance on 1st Floor - Boys

Inspected

Instance Condition

3- Fair

Deficiency

LIGHTING FIXTURE BEYOND USEFUL LIFE

Mobile Validity Version 2.0 (P)

Page 4 of 9

Print Date: 6/16/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

K406

Question

Response

LOCKER ROOM Lighting Lighting Fixture - Incandescent Surface Mounted Deficiency Quantity

1 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Instance on 1st Floor - Boys - Visitor

Inspected

Instance Condition

3- Fair

Deficiency Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE 1 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Instance on 1st Floor - Girls

Inspected

Instance Condition

3- Fair

Deficiency Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE 5 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Deficiency Deficiency Quantity

LIGHTING FIXTURE NOT OPERATIONAL 2 EACH REPLACE PRIORITY 3 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Instance on 1st Floor - Girls - Visitor

Inspected

Instance Condition

3- Fair

Deficiency Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE 10 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Lighting Fixture - LED

Instance on 1st Floor - Boys

Does not exist

Instance on 1st Floor - Boys - Visitor

Does not exist

Instance on 1st Floor - Girls

Does not exist

Instance on 1st Floor - Girls - Visitor

Does not exist

MOTOR CONTROL CENTER

Does not exist

MOTOR STARTER/CONTACTOR

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded

MULTIPURPOSE ROOM

Does not exist

PANEL BOARD

Inspected Inspected

Fused Disconnect Switch Type

Mobile Validity Version 2.0 (P)

Page 5 of 9

Print Date: 6/16/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

K406

Question

Response

PANEL BOARD Fused Disconnect Switch Type Condition

3- Fair

Deficiency Deficiency Location/Instance Deficiency Quantity

PANEL BOARD BEYOND USEFUL LIFE Storage Building 1 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Fused Knife Switch Type

Does not exist

Fused Toggle Switch Type

Does not exist

Molded Case Circuit Breaker Type

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded Inspected

PUBLIC ADDRESS SYSTEM

Instance

Coachs Office 3- Fair

Instance Condition Instance Quantity

1 EACH

Instance Quantity Uom Model

Rauland DX125C 1980 Inspector estimated

Installation Year Source of Installation Year Deficiency Deficiency Location/Instance Deficiency Quantity

BEYOND USEFUL LIFE Coachs Office 12,000 S.F. REPLACE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations SCIENCE DEMO ROOM

Does not exist

SCIENCE LAB

Does not exist

SCIENCE PREP ROOM

Does not exist

SECURITY

Inspected

Intrusion Alarm System

Inspected

Central Control Panel

Inspected

Instance

Storage Building 5- Poor

Instance Condition Instance Quantity

1 EACH

Instance Quantity Uom Model

Varitech Model 380 1985 Inspector estimated

Installation Year Source of Installation Year Deficiency Deficiency Location/Instance Deficiency Quantity

PANEL NOT OPERATIONAL Storage Building 1 EACH REPLACE SYSTEM PRIORITY 4 LEVEL 3 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Instance Instance Condition

Closet Inside Firemans Office 5- Poor

Instance Quantity

1

Mobile Validity Version 2.0 (P)

Page 6 of 9

Print Date: 6/16/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

K406

Question

Response

SECURITY Intrusion Alarm System Central Control Panel

EACH

Instance Quantity Uom Model

Varitech Model 380 1985 Inspector estimated

Installation Year Source of Installation Year Deficiency Deficiency Location/Instance Deficiency Quantity

PANEL NOT OPERATIONAL Closet Inside Firemans Office 1 EACH REPLACE SYSTEM PRIORITY 4 LEVEL 3 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Infrared Sensor

Does not exist

Panic Switch

Does not exist

Remote Annunciator

Does not exist

Siren/Strobe

Inspected

Condition

3- Fair

Deficiency

No deficiencies recorded Inspected

Ultrasonic Sensor

Condition

3- Fair

Deficiency

No deficiencies recorded

IPDVS/CCTV System

Does not exist

Lighting - Security

Inspected

Condition

2- Between Good and Fair

Replacement Quantity Replacement Uom

29 EACH

Deficiency Deficiency Location/Instance Deficiency Quantity

LIGHTING FIXTURE NOT OPERATIONAL Building Exterior 5 EACH REPAIR PRIORITY 4 LEVEL 3 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations

Inspected

SERVICE SWITCH

Instance

Boiler Room 3- Fair

Instance Condition Instance Quantity Instance Quantity Uom

1 EACH

Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year

Electric Switchboard Distribution PNL 1 SW 100 LPN 100 100 Amps Nameplate 1970 Inspector estimated

Deficiency Deficiency Location/Instance Deficiency Quantity

BEYOND USEFUL LIFE Boiler Room 1 EACH REPLACE PRIORITY 1 LEVEL 2

Quantity Uom Potential Action Urgency of Action Purpose of Action Mobile Validity Version 2.0 (P)

Page 7 of 9

Print Date: 6/16/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

K406

Question

Response

SERVICE SWITCH

Violations

No violations recorded

Instance

Boiler Room 3- Fair

Instance Condition Instance Quantity Instance Quantity Uom

1 EACH

Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year

Electric Switchboard Boiler RM PW PNL SW 100 LPN 100 100 Amps Nameplate 1970 Inspector estimated

Deficiency Deficiency Location/Instance Deficiency Quantity

BEYOND USEFUL LIFE Boiler Room 1 EACH REPLACE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Instance

Boiler Room 3- Fair

Instance Condition Instance Quantity Instance Quantity Uom

1 EACH

Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year

Electric Switchboard Distribution PNL 2 SW 100 LPN 100 100 Amps Nameplate 1970 Inspector estimated

Deficiency Deficiency Location/Instance Deficiency Quantity

BEYOND USEFUL LIFE Boiler Room 1 EACH REPLACE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations SWIMMING POOL

Does not exist

SWITCHBOARD

Does not exist

TELEPHONE SYSTEM

Inspected

PBX/Intercom

Does not exist

Standard

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded Inspected

TOILET ROOM - STAFF

Inspected

Lighting

Inspected

Lighting Fixture - Fluorescent Pendant Mounted

Does not exist

Recessed Mounted

Does not exist

Surface Mounted

Inspected 3- Fair

Condition Deficiency Deficiency Quantity Mobile Validity Version 2.0 (P)

LIGHTING FIXTURE BEYOND USEFUL LIFE 2 Page 8 of 9

Print Date: 6/16/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

K406

Question

Response

TOILET ROOM - STAFF Lighting Lighting Fixture - Fluorescent Surface Mounted

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations

EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Lighting Fixture - HID

Does not exist

Lighting Fixture - Incandescent

Inspected

Pendant Mounted

Does not exist

Recessed Mounted

Does not exist

Surface Mounted

Inspected 3- Fair

Condition Deficiency Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE 6 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations

Does not exist

Lighting Fixture - LED

Inspected

TOILET ROOM - STUDENT

Inspected

Lighting Lighting Fixture - Fluorescent

Does not exist

Lighting Fixture - HID

Does not exist

Lighting Fixture - Incandescent

Inspected Inspected

Pendant Mounted

3- Fair

Condition Deficiency Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE 4 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Recessed Mounted

Does not exist

Surface Mounted

Inspected 3- Fair

Condition Deficiency Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE 7 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations

Does not exist

Lighting Fixture - LED TRANSFORMER

Does not exist

TV SYSTEM

Does not exist