NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

X841

I.S. 241 - BRONX, 3333 HENRY HUDSON PKWY W, BRONX, NY, 10463

School: InspectionId

Inspection Type

11074 ELECTRICAL

Time In

Last Edited

2015-01-21 08:35AM

2015-02-05 11:17AM

Asset Data Question

Answer

Have any Systems/Major Building Components been upgraded?

Systems:

Intrusion Alarm System

Years: Systems:

Years: Systems:

1995 Interior Fluorescent Lighting, Partial Molded Case Circuit Breaker Panel Board, Public Address System Amplifier, Partial Lighting - Security Lights 2000 LAN

Years: Systems:

2005 Intrusion Alarm System Siren/Strobe

Years: Systems:

2006 Telephone System

Years: 2009 Below Ground

Type of Service Does Interactive Whiteboard (IWB) Exist?

Yes

DEDICATED INTERCOMS IN FIRE RESCUE AREAS Question Are there any Life Rescue Assistance Areas, Fire Rescue Areas, and/or Holding Rooms in your building?

Response No

Priority Condition Priority Condition Exist Last Year?

Priority Category

Condition Description

Component Affected

Location Description

Person(s) Notified

Yes

Electrical Room Used as Storage

Electrical Room Used as Storage

Electrical Equipment

Room 11

Jose Ocasio

Person(s) Title

Fireman

PhotoImage

No Photo Tak

Inspection Question

Response

Electrical ATHLETIC FIELD

Does not exist

AUDITORIUM

Does not exist

AUXILIARY SIGNAL/BELL SYSTEM

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded

CAFETERIA

Instance on 1st Floor

Inspected

Instance on 1st Floor

Inspected

Lighting Lighting Fixture - Fluorescent

Inspected

Instance on 1st Floor Pendant Mounted

Does not exist

Instance on 1st Floor Recessed Mounted

Does not exist

Instance on 1st Floor Surface Mounted

Instance on 1st Floor

Inspected

Instance Condition

3- Fair

Deficiency

No deficiencies recorded

Lighting Fixture - HID

Does not exist

Instance on 1st Floor Lighting Fixture - Incandescent

Does not exist

Instance on 1st Floor Mobile Validity Version 2.0 (P)

Page 1 of 7

Print Date: 6/18/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

X841

Question

Response

CAFETERIA Lighting Lighting Fixture - LED

Does not exist

Instance on 1st Floor Local Sound System

Does not exist

Instance on 1st Floor Projection System

Does not exist

Instance on 1st Floor Theater Lighting System

Does not exist

Instance on 1st Floor CITY FIRE ALARM SYSTEM

Does not exist

CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE

Inspected Inspected

Lighting Does a Chandelier Exist?

No Inspected

Lighting Fixture - Fluorescent

Inspected

Pendant Mounted

3- Fair

Condition Deficiency

No deficiencies recorded

Recessed Mounted

Does not exist

Surface Mounted

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded

Lighting Fixture - HID

Does not exist

Lighting Fixture - Incandescent

Does not exist

Lighting Fixture - LED

Does not exist

COMPUTER LAB

Instance on Room 8

Inspected

Has LAN/Modem access

Yes

Power Panel?

No

Instance on Room 8

Inspected

Lighting Lighting Fixture - Fluorescent

Inspected

Instance on Room 8 Pendant Mounted

Does not exist

Instance on Room 8 Recessed Mounted

Does not exist

Instance on Room 8 Surface Mounted

Instance on Room 8

Inspected

Instance Condition

3- Fair

Deficiency Deficiency Quantity

LIGHTING FIXTURE BALLAST DEFECTIVE 1 EACH REPLACE BALLAST PRIORITY 3 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Lighting Fixture - HID

Does not exist

Instance on Room 8 Lighting Fixture - Incandescent

Does not exist

Instance on Room 8 Lighting Fixture - LED

Does not exist

Instance on Room 8 Raceway With Receptacles

Inspected

Instance on Room 8 Mobile Validity Version 2.0 (P)

Page 2 of 7

Print Date: 6/18/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

X841

Question

Response

COMPUTER LAB Raceway With Receptacles Instance Condition

3- Fair

Deficiency

No deficiencies recorded

EMERGENCY DC STANDBY BATTERY POWER

Does not exist

EMERGENCY GENERATOR SET

Does not exist

EMERGENCY LIGHT/EXIT LIGHT PANEL

Does not exist

EMERGENCY LIGHTING

Inspected Inspected

Battery Pack

3- Fair

Condition Deficiency

No deficiencies recorded Does not exist

Non Battery Pack

Inspected

EXIT LIGHT

Inspected

Battery Pack

3- Fair

Condition Deficiency

No deficiencies recorded Does not exist

Non Battery Pack EXIT/EMERGENCY LIGHT

Does not exist

FIRE ALARM SYSTEM

Inspected

Area Smoke Detector

Does not exist

Bell/Horn

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded

Duct Smoke Detector

Does not exist

Elevator Recall

Does not exist

Fan Shutdown Control

Does not exist

Fire Alarm Digital Communicator

Does not exist

Fused Cutout Panel

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded

Heat Detector

Does not exist

Magnetic Door Holder/Contactor

Does not exist

Main Panel

Inspected Inspected

Bell At Panel

Condition

3- Fair

Deficiency

No deficiencies recorded

Fire Alarm Control Panel (Electronic)

Does not exist

Fire Alarm Control Panel (Standard)

Inspected

Instance

Room 11 3- Fair

Instance Condition Instance Quantity Instance Quantity Uom

1 EACH

Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year

ACME Fire Alarm Control Board 3 Circuits Diagram 1970 Documented

Deficiency Deficiency Location/Instance Deficiency Quantity

BEYOND USEFUL LIFE Room 11 12,000 S.F. REPLACE PRIORITY 1

Quantity Uom Potential Action Urgency of Action Mobile Validity Version 2.0 (P)

Page 3 of 7

Print Date: 6/18/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

X841

Question

Response

FIRE ALARM SYSTEM Main Panel Fire Alarm Control Panel (Standard)

Purpose of Action Violations

LEVEL 2 No violations recorded Inspected

Manual Pull Station

3- Fair

Condition Deficiency

No deficiencies recorded

Remote Annunciator

Does not exist

Sprinkler Flow/Air Pressure Switch

Does not exist

Strobe

Does not exist

Sub-Panel

Does not exist

Tamper Flow Switch/Chain

Does not exist

GROUNDING SYSTEM

Does not exist

GYMNASIUM

Does not exist

INTERCOM SYSTEM

Does not exist

KITCHEN/WARMING PANTRY

Does not exist

LAN

Inspected

Local Distribution Frame (I/LDF)

Does not exist

Main Equipment Rack (MDF)

Inspected 2- Between Good and Fair

Condition Deficiency

No deficiencies recorded

LIBRARY

Does not exist

LIGHTNING PROTECTION

Does not exist

LOCKER ROOM

Does not exist

MOTOR CONTROL CENTER

Does not exist

MOTOR STARTER/CONTACTOR

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded

MULTIPURPOSE ROOM

Does not exist

PANEL BOARD

Inspected

Fused Disconnect Switch Type

Does not exist

Fused Knife Switch Type

Does not exist

Fused Toggle Switch Type

Does not exist

Molded Case Circuit Breaker Type

Inspected 3- Fair

Condition Deficiency Deficiency Location/Instance Deficiency Quantity

PANEL BOARD BEYOND USEFUL LIFE Room11, Custodian Room 2 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations

Inspected

PUBLIC ADDRESS SYSTEM

Instance

General Office 3- Fair

Instance Condition Instance Quantity

1 EACH

Instance Quantity Uom Model Installation Year Source of Installation Year

Radio Shack - MPA 250A 1970 Documented

Deficiency Deficiency Location/Instance

BEYOND USEFUL LIFE General Office

Mobile Validity Version 2.0 (P)

Page 4 of 7

Print Date: 6/18/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

X841

Question

Response

PUBLIC ADDRESS SYSTEM Deficiency Quantity

12,000 S.F. REPLACE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations SCIENCE DEMO ROOM

Does not exist

SCIENCE LAB

Does not exist

SCIENCE PREP ROOM

Does not exist

SECURITY

Inspected

Intrusion Alarm System

Inspected

Central Control Panel

Inspected

Instance

Custodian Room 3- Fair

Instance Condition Instance Quantity

1 EACH

Instance Quantity Uom Model Installation Year Source of Installation Year

Vista - 50P 1995 Documented

Deficiency

No deficiencies recorded Inspected

Infrared Sensor

Condition

3- Fair

Deficiency

No deficiencies recorded Inspected

Panic Switch

Condition

3- Fair

Deficiency

No deficiencies recorded Inspected

Remote Annunciator

Condition

3- Fair

Deficiency

No deficiencies recorded Inspected

Siren/Strobe

Condition

2- Between Good and Fair

Deficiency

No deficiencies recorded

Ultrasonic Sensor

Does not exist

IPDVS/CCTV System

Does not exist

Lighting - Security

Inspected

Condition

3- Fair

Replacement Quantity Replacement Uom

3 EACH

Deficiency Deficiency Location/Instance Deficiency Quantity

LIGHTING FIXTURE BEYOND USEFUL LIFE Main Entrance and Back Exit 2 EACH REPLACE-UPGRADE PRIORITY 1 LEVEL 3 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations

Inspected

SERVICE SWITCH

Instance

Room 11 3- Fair

Instance Condition Instance Quantity Instance Quantity Uom

1 EACH

Manufacturer EquipmentId Capacity/Size Quantity

General Electric N/A 200

Mobile Validity Version 2.0 (P)

Page 5 of 7

Print Date: 6/18/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

X841

Question

Response

SERVICE SWITCH Capacity/Size UOM Source of Capacity/Size

Amps Nameplate 1970 Documented

Installation Year Source of Installation Year Deficiency Deficiency Quantity

SWITCH ID IS MISSING 1 EACH MAINTENANCE PRIORITY 2 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Deficiency Deficiency Location/Instance Deficiency Quantity

BEYOND USEFUL LIFE Room 11 1 EACH REPLACE PRIORITY 1 LEVEL 2 No violations recorded

Quantity Uom Potential Action Urgency of Action Purpose of Action Violations SWIMMING POOL

Does not exist

SWITCHBOARD

Does not exist

TELEPHONE SYSTEM

Inspected Inspected

PBX/Intercom

1- Good

Condition Deficiency

No deficiencies recorded Inspected

Standard

1- Good

Condition Deficiency

No deficiencies recorded Inspected

TOILET ROOM - STAFF

Inspected

Lighting

Inspected

Lighting Fixture - Fluorescent Pendant Mounted

Does not exist

Recessed Mounted

Does not exist

Surface Mounted

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded

Lighting Fixture - HID

Does not exist

Lighting Fixture - Incandescent

Does not exist

Lighting Fixture - LED

Does not exist Inspected

TOILET ROOM - STUDENT

Inspected

Lighting

Inspected

Lighting Fixture - Fluorescent Pendant Mounted

Does not exist

Recessed Mounted

Does not exist

Surface Mounted

Inspected 3- Fair

Condition Deficiency

No deficiencies recorded

Lighting Fixture - HID

Does not exist

Lighting Fixture - Incandescent

Does not exist

Lighting Fixture - LED

Does not exist

TRANSFORMER

Does not exist

TV SYSTEM Cable System Exist? Operational?

Inspected

Mobile Validity Version 2.0 (P)

Yes No Page 6 of 7

Print Date: 6/18/2015

NYC Department of Education Building Condition Assessment Survey 2014-2015

Electrical Inspection

X841

Question

Response

TV SYSTEM

Does not exist

Main Equipment Rack

Mobile Validity Version 2.0 (P)

Page 7 of 7

Print Date: 6/18/2015