NHP Medium Voltage Switchgear

NHP Medium Voltage Switchgear Customised switchgear solutions built to last MEDIUM VOLTAGE POWER MV MV SOLUTIONS NHP Electrical Engineering Produc...
Author: Ursula Lindsey
79 downloads 0 Views 10MB Size
NHP Medium Voltage Switchgear Customised switchgear solutions built to last MEDIUM VOLTAGE POWER

MV

MV

SOLUTIONS

NHP Electrical Engineering Products Pty Ltd

Sales 1300 NHP NHP Sales 0800 NHP NHP

nhp.com.au nhp-nz.com

easy to do business with

2

Why NHP? We’re easy to do business with. At NHP we’re solely committed to serving the needs of our customers in the industrial electrical industry. From concept design through to installation and after sales service, we are confident we have the experience and expertise to exceed your expectations and ensure you get the best result for your project. How? Well, put simply, we’re easy to do business with. Combining Partnerships, Agility, Knowledge and Scalability, NHP offer the Australasian market quality, around-theclock service that forms the ultimate choice in our industry.

Partnerships:

Knowledge:

When you choose NHP you gain a valuable industry partner. You gain access to an exclusive network of quality global suppliers who together with NHP’s 50+ branch and regional locations across Australia and New Zealand, can achieve an engineered solution for your medium voltage application.

If your Medium Voltage application demands a specialist team of trained project management, design and engineering professionals, then NHP is the ultimate choice. Bringing together over 40 years of electrical industry experience, NHP’s dedicated Medium Voltage project team promises to deliver customiseable solutions from concept design through to installation and project management.

Providing the perfect balance of knowledge and experience, a partnership with NHP promises to last the life of current and future projects, working together with you to offer complete trust, assurance and peace of mind.

We know that you have a range needs and that these needs can change but calling on our vast industry experience we know how to meet them. When it comes to Medium Voltage, look no further than NHP.

If it’s Medium Voltage, partner with NHP.

Agility:

Scalability:

At NHP we understand your Medium Voltage application needs and know that these needs can often change throughout the life of a project. But with a seamless combination of local and technical support and a network of global suppliers, NHP have the agility to provide real-time solutions that are backed by around the clock service and support for not only the life of a project but any future needs as well.

With all the scale of a large multi-national company, NHP maintain a premium level of customer service and attention to detail no matter how big or small your Medium Voltage project.

Don’t be caught waiting. Choose NHP and get the very best in Medium Voltage solutions – day in, day out, right where you need them.

Be it our 1000+ expert staff, our 50+ branch and regional locations, or our extensive network of global suppliers, when you deal with NHP you will receive all of this combined knowledge and expertise in an ‘easy to do business with’ solutions with a local focus!

TABLE OF CONTENTS NHP Medium Voltage Switchgear Overview....................................................... 5 Application............................................................................................................................. 6 Air Insulated Switchgear (AIS) with visual earthing - DF-2.......................... 9 Ring Main Units (RMUs) - DR-6/DT-6......................................................................28 Withdrawable Switchgear - DW-2...........................................................................34 Gas Insulated Swithgear (GIS) - DI-2......................................................................44 Compact Air Insulated Switchgear - DF-3..........................................................50

4

NHP MEDIUM VOLTAGE SWITCHGEAR OVERVIEW Suitable for 3.3kV, 6.6kV, 11kV, 22kV.

Air Insulated Switchgear (AIS) with visual earthing - DF-2

PAGE 9

AIS up to 24kV and 25kA 1 sec DF-2’s modular air insulated switchgear design allows you to create rational, economical and custom-made combinations of medium-voltage cubicles with visible earth contact.

Ring Main Units (RMUs) - DR-6/DT-6

PAGE 28

RMU up to 24kV and 25kA 1 sec Compact and/or extensible gas insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker.

Withdrawable Switchgear - DW-2

PAGE 34

AIS metalclad fully withdrawable up to 12kV and 31.5kA 4 sec

A family of air-insulated medium voltage switchgear solutions for indoor installations.

Gas Insulated Switchgear (GIS) - DI-2

PAGE 44

GIS up to 36kV and 20kA 3 sec A modular concept combining all medium voltage functions. Suitable for 11kV, 22kV, 33kV.

Compact Air Insulated Switchgear - DF-3

PAGE 50

AIS compact up to 24kV and 20kA 1 sec Our new modular and extendible switchgear. 5

Applications Power stations generate electrical power, with voltages up to 500,000V, which is transmitted to transformer stations and dispersion stations. These substations distribute medium voltage above 1kV to 36kV and it is here that a number of NHP Medium Voltage Switchgear cubicles can be used. A medium-voltage grid starts from every substation and supplies a large area with medium-voltage. Wherever medium-voltage enters residential areas, industrial production companies, mining sites, data centres, rail, hospitals and more, there is a medium voltage cubicle fulfilling four essential functions.

1. POWER SUPPLY: the network distributor’s grid is branched off to allow switching 2. SECURITY: the installation is secured with a load break switch with HRC fuses, or by a load break switch with a safety relay 3. MEASUREMENT: the energy consumption is measured on the high-voltage, or low-voltage side 4. TRANSFORMATION: medium-voltage is transformed into low-voltage (1,000V-400V-230V)

The Power Grid CO-GENERATION MARKET GARDENING

CATERING INDUSTRY / SHOPPING CENTRE

PRODUCTION

DISPERSION

MEDIUM VOLTAGE SWITCHGEAR

INFRASTRUCTURE

INDUSTRY

RESIDENTIAL AREAS

Commercial Buildings including Hospitals and Data Centres

6

NHP Medium Voltage Switchgear OVERVIEW DESIGN PHILOSOPHY AND APPLICATIONS User-friendliness, safety and care for the environment were the main motivators in the selection of NHP Medium Voltage Switchgear. NHP can provide “made-to-measure” solutions for all your medium-voltage needs. NHP Medium Voltage Switchgear offers a wide range of applications that can be used worldwide in many industries. Cubicles can be used with distribution and dispersion switchgear, electrical sub-stations and medium-voltage engines, wind generators, cogeneration, and much more. The NHP Medium Voltage Switchgear range provides a solution for all your needs and demands as it can replace obsolete installations, extend existing installations, and it is also perfectly suited for brand new installations.

The NHP Medium Voltage Switchgear cubicles are a modular concept based on the “building blocks” principle, which means that cubicles are produced in series. As a result these products meet the highest technical standards in a rational and economically sound way. The combination of cubicles is unlimited. Very complex diagrams of distribution and transformer switchgear can be compiled through this extensive spectrum of possibilities. Cubicles contain standard functional interlocks which allows for effortless application and installation in most consumer work spaces. As a result, capacity loss will be minimal. Additionally, the cubicles have been fitted with a system for pressure release which shields the user from the consequences of an internal arc.

7

INTERNAL ARC MITIGATION

OPTION WITH BUILT-IN ARC-KILLER

A short-circuit or another malfunction can create an internal arc. An internal arc in a Medium Voltage cubicle could severely damage the installation and possibly injure the operator.

Protect your cubicles, infrastructure and your staff against the consequences of an internal arc. The built-in Arc-Killer extinguishes an arc in less than 50ms.

NHP Medium Voltage Switchgear cubicles are designed to mitigate the creation of internal arcs and therefore protect both the operator and the installation. Through a strategic pressure release system, the internal arc is restricted to the compartment where it originated and it does not spread towards the operator or to other compartments. The cubicles are specifically designed to minimize the consequences of an internal arc. All provided cubicles are fitted on the rear side with overpressure valves pointing downward as a standard. NHP Medium Voltage Switchgear cubicles have been tested with these specifications at independent, and accredited testing solutions (for example: IPH, Kema). The load break switches have been tested according to IEC standards and consequently, all NHP Medium Voltage cubicles are internal arc resistant.

Without Arc-Killer

The NHP Medium Voltage Switchgear range includes the Arc-Killer SV-25 and SV-53, a system for detecting and extinguishing an internal arc. The Arc-Killer extinguishes the arc by directing it to a metal earthed short circuit. The arc is extinguished in less than 50ms. Our modules are metal enclosed cubicles combined with a shaft at the rear end. The shaft absorbs any gasses (in case of an internal arc) that escape through the overpressure valves. As a result, the expansion of hot gasses in a room can be reduced to an absolute minimum. NHP Medium Voltage Switchgear cubicles offer protection against an internal arc classification IAC category B, FLR 20 kA 1 s. (F=frontal, L=lateral, R=rear). As a result, the operator is protected against the consequences of an arc whether they stand in front of the switchboard, next to it or behind it.

With Arc-Killer

The patented SV-25 and SV-53 Arc-Killer takes safety to a new level. Not just the operator and the environment are shielded from harm, but the super-swift arc extinguishing system allows cubicles to be back in operation very quickly in case of an internal fault. What’s more, the Arc-Killer’s improved security features place less strict demands on the installation room. As such, the Arc-Killer couples security and operational safety with flexible room demands.

8

DF-2 AIR INSULATED SWITCHGEAR (AIS) WITH VISUAL EARTHING DF-2

A MODULAR CONCEPT COMBINING ALL MEDIUMVOLTAGE FUNCTIONS. DF-2’s modular design allows you to create rational, economical and custom-made combinations of mediumvoltage cubicles with a rated voltage of up to 24kV.

9

DF-2 COMPARTMENTS SWITCHGEAR COMPARTMENT In this compartment, the gas filled (RV44) load break switch is double sealed, which acts as the physical separation between the busbar set and the cable compartment. The switch has two functions: it connects or interrupts the electrical current between the high voltage cables and the busbar. BUSBAR COMPARTMENT The busbar compartment is located in the upper part of the cubicle and behind the low-voltage compartment. The modular busbar set is manufactured from specially provided electrolyte F25 copper of 60 x 10mm with n = 5mm (800A). Standard as well as 1250A option is available. Several cubicles are connected through the bar set compartments. Hexagonal bolts connect the busbars to the upper contact surfaces of the RV44 load break switch.

CABLE COMPARTMENT The cable compartment is located behind the interlocked, removable door of the DF-2 cubicle. This part of the field receives the cable(s) and contains the necessary equipment to connect the cable(s). The earthing switch is installed below the load break switch on the right side, ensuring a “visible earthing” when the earthing switch is closed. In a DF-A cubicle, the cables are connected to the contact points below the RV 44 load break switch. The cables of the DF-P cubicles are connected to the lower fuse base side. This type of cubicle also has an additional auxiliary earthing switch to divert any residual current. DF-D type cubicle have the earthing switches located in the cable compartment below. The removable door, the sectional floor panels which house the necessary conductive rubber for the cables, and the cable supports all simplify the cable connection.

LOW-VOLTAGE COMPARTMENT

CABLE COMPARTMENT

BUSBAR COMPARTMENT

SWITCHGEAR COMPARTMENT

LOW-VOLTAGE COMPARTMENT The drive mechanism that controls the RV44 load break switch and the earthing switch EM20 is fitted with the synoptic diagram and is located behind the front panel. Several accessories, such as the auxiliary contacts, switch-on or switch-off coils, and minimum voltage relays are also located in this compartment. Any control with the necessary electrical switchgear, a control and clamp strip are also installed in this compartment. The compartment is easily accessible by removing the front panel.

9

10

DF-2 DF-2 MODULE RANGE TECHNICAL SPECIFICATIONS OF MODULES Rated Voltage

kV

12

12*

24

- To earth and between phases

kV

75

95

125

- Over the insulated distance

kV

85

110

145

kV

28

38

50

Impulse withstand voltage 1.2 / 50 μs

Power frequency withstand voltage: - To earth and between phases

kV

32

45

60

Rated frequency

- Over the insulated distance

Hz

50/60

50/60

50/60

Rated current

A

800/1250**

800/1250**

630

Rated short-time current 1s.

kA

25

25

20

Rated peak value of the current

kA

63

63

50

- Mainly active load

A

800/1250**

800/1250**

630

- Closed loop

A

800

800

630

- Load cable charging

A

18

18

18

- Making current



63

63

50

- Earth fault

A

100

100

100

- Earth fault cable charging

A

30

30

30

kA

16

16

16

Breaking capacity RV44 (Class E3)

Internal arc 1s. Degree of protection

IP4X

Mechanical durability c/o

1000

Standards

IEC 62271-100, IEC 62271-1, 62271-102, -103, -105, 62271-200 and IEC 61243-5

Certificates

KEMA/IPH

Notes: * Utilities Specifications ** According to IEC 62271-103, Class E1

11

DF-2 MODULE SPECIFICATIONS AND DIMENSIONS

12

Load break switch with interlocked earth switch - DF-A/DF-A+

PAGE 13

Protection cubicle with vacuum circuit breaker - DF-AAD/ DF-AAD+

PAGE 20

Load break switchfuse with interlocked earth switch - DF-P

PAGE 14

Protection cubicle with double interruption - DF-AADT

PAGE 21

Auxiliary voltage cubicle with interlocked earthing switch - df-av

PAGE 15

Busbar coupling cubicle - DF-LK

PAGE 22

Vacuum circuit breaker with integrated protection relay - DF-D/DF-D+

PAGE 16

Transformer housing - DF-T

PAGE 23

Protection cubicle with vacuum circuit breaker - DF-D/EDN/ DF-D+/EDN

PAGE 17

Metering cubicle DF-C-750/DF-C-500

PAGE 25

Protection cubicle with remountable vacuum circuit breaker with integrated protection relay - DF-D-500

PAGE 18

Busbar link panel - DF-LKB

PAGE 26

Protection cubicle with vacuum circuit breaker (magnetic driven) and integrated protection relay.

PAGE 19

Cable connection panel or bus riser - DF-K

PAGE 27

DF-2 LOAD BREAK SWITCH WITH INTERLOCKED EARTH SWITCH DF-A

DF-A+ (with arc killer)

Application: Incomer or feeder-load break switch with interlocked earthing switch. Standard Equipment • Three phase load break switch RV44, class E3 according to IEC 62271-103, gas insulated • Cable support • Door interlock 940 • Sockets for capacitive voltage detector with parallel testing possibility • Low-voltage compartment Options • Auxiliary contacts on load break switch and or earthing switch • Key interlock on load break switch and/or earthing switch • Motor operation local or remote control: 24-48-110V-AC/DC or 220VAC • Short-circuit indicator 10 • Voltage indicators • Plinth 200mm to 400mm height Ø79 • Gland plate AL/BRASS

I

I

0

1700

0

180

775

570

365

205

150

24

Rated current

A

800-1250

630

Short-term current

kA

25

20

s

1

1

55

60

400

100

**

500

900mm

1050

1700

1700

Height between ground and end socket

mm

945

835

Height between ground and cable support

mm

445

445

Weight

kg

180

180

Weight with Arc Killer

kg

240

240

210

210 500

DF-A 10 Ø79

400

100

900 1050

55

60

900

995

775

570

500 1050

205

mm mm

150

Width Depth

365

1090

995

12 *

860

1700

L3

900

kV

Height

HR

DEBA

L2

*

Rated Voltage

duration of current

HR

DEBA

L1

500

Specifications & Dimensions

Time of the short

HR

DEBA

210 500

DF-A+ (Arc Killer Option)

Notes: * Arc Killer Option

13

DF-2 load break switchFUSE with interlocked earth switch DF-P Application: Transformer protection and Medium Voltage 970 equipment protection.

*

60

900

400

100

210 500

995

Options • Set of auxiliary contacts on load break switch and/or earthing switch • Key interlock on load break switch and/or earthing switch • Shunt trip ** • Under voltage release ** • Closing release ** • Motor operation ** • Contact “fuse blown” • Automatic recloser • Set of 2 or 3 voltage transformers • Voltage indicators • Plinth: 200mm - 400mm Specifications & Dimensions Rated Voltage

kV

12

24

Rated current

A

800-1250

630

Short-term current

kA

25

20

Time of the short duration of current

s

1

1

Width

mm

500

500

Depth

mm

1050

1050

Height

mm

1700

1700

Height between ground and end socket

mm

460

415

Fuse size

mm

292 (DIN)

442 (DIN)/ UTE

kg

210

210

Weight

14

205 570 995

**

775

Ø79

365

10

150

9 10

9 10 1

1700

1700

30 31 1 2 3 2829

2 3

2 3 4

500

12 1

9 7

7 8 9 10 11 5 6

210

11

210

4

A

7 8

0

24 212223 25 26 27

0

0

Standard Equipment • Three-phase load break switch RV44, class E3 according to IEC 62271-105, gas insulation • Double earthing switch with mutual interlock • Socket for HRC fuses: - 292mm DIN 10 at 17.5kV - 442mm DIN 20 at 24kV - UTE • Three-pole fuse trip • Door interlock • Sockets for capacitive voltage detector 500 900 • Low-voltage compartment 8

I

I

20

L3

5 6 7

HR

DEBA

L2

4 5 6

HR

DEBA

L1

15 1617 18 13 14 19 12

HR

DEBA

DF-2 AUXILIARY VOLTAGE CUBICLE with INTERLOCKED EARTHING SWITCH DF-AV Application: For supply of auxiliary voltage with cubicle interlocked earthing switch. Standard Equipment • Three-phase load break switch RV44, class E3 according to IEC 62271-103, gas insulation • Double interlocked earthing switch • HRC fuse-holders: - 292 mm DIN 10 at 17.5 kV - 442 mm DIN 20 at 24 kV - UTE 970 • Door interlock • Sockets for capacitive voltage detector • Low-voltage compartment • Assembly plate for auxiliary transformer(s)

HR

HR

HR

DEBA

DEBA

DEBA

L1

L2

L3

I

I

0

1700

0

210

Options • Set of auxiliary contacts on load break switch and/or earthing switch • Key interlock on load break switch and/or earthing switch • Motor operation * • Contact “fuse blown” • Set of 1, 2 or 3 voltage transformers • Voltage indicator(s) • Plinth: 200mm - 400mm • VT: xx kV/x V x VA CL.XX

60

Specifications & Dimensions Rated Voltage

kV

12

24

Rated current

A

800-1250

630

Short-term current

kA

Time of the short duration of current

25 900

20

s

1

1

Width

mm

500

500

Depth

mm

1050

1050

Height

mm

1700

1700

Height between ground and end socket

mm

460

415

Fuse size

mm

292 (DIN)

442 (DIN)/ UTE

kg

210

210

Weight

400

100

55

900

995

**

1700

150

10

205

500

500

15

DF-2 vacuum circuit breaker with integrated protection relay DF-D

DF-D+ (with arc killer)

Application: Protection of descending feeders with circuit breaker, transformer and Medium Voltage 980 equipment protection.

205

940 1050

110

750

490 DF-D

900 1050

365

570

775

750

Cubicle Options • Set of auxiliary contacts on the load break switch and/or earthing switch • Key interlock on load break switch and/or earthing switch • Motor operation on load break switch: 24-48-110VAC/DC and 220VAC • Short-circuit indicator • Earthing connection above circuit breaker • Circuit breaker gas insulated • Voltage indicators • Plinth: 200mm - 400mm Options on the circuit breaker • Motor operation ** • Closing release • Shunt trip ** • Under voltage release ** • Set of auxiliary contacts • Error contact • Supply for test protective relay (battery block) • Cycle counter • Automatic recloser • Key interlock Specifications & Dimensions

DF-D+ (Arc Killer Option)

16

940 1050

995

940 1155

750

55

60

*

O

460

150

1700

1700

I

I

O

110

9 10 1

2 3

2 3 4

9 10

30 31 1 2 3 2829

7 8

12 1

9 7

7 8 9 10 11 5 6

11

4

A

24 212223 25 26 27

460 Standard Equipment • Three-phase load break switch RV44, class E3 according to IEC 62271-103, gas insulation • Vacuum circuit breaker with integrated protection relay, current transformers and release 10 • Interlocked earthing switch with rated making capacity up to 63kA downstream of the Ø79 capacity switch • Cable support • Door interlock • Sockets for capacitive voltage detector 460 • Voltage indicators 100 • LV compartment 8

I

0

20

L3

5 6 7

HR

DEBA

L2

4 5 6

HR

DEBA

L1

15 1617 18 13 14 19 12

HR

DEBA

I

0

Rated Voltage

kV

12

24

Rated current

A

800/1250

630

Short-term current

kA

25

20

Time of the short duration of current

s

1

1

Width

mm

750

750

Depth

mm

1050

1050

Height

mm

1700

1700

Height between ground and socket

mm

445

445

Weight

kg

460

460

Weight with Arc Killer

kg

490

490

DF-2 Protection cubicle with vacuum circuit breaker DF-D/EDN

DF-D+/EDN (with arc killer)

Application Protection of descending feeders with circuit breaker, transformer and Medium Voltage equipment protection.

A I

1700

0

I

O

460 150

205 365 570

900 1050

995 460 55

60

775

Ø79

100

570

365

205

10

12

24

Rated current

A

800/1250

630

s

25

20

9001

1

1265

900 1050

460 55

kV kA

DF-D/EDN

Ø79

995

Rated Voltage

Time of the short duration of current

150

750

Specifications & Dimensions

Short-term current

490

775

7 8

15 1617 18 13 14 19 12

1700

Options on the circuit breaker • Motor operation ** 940 • Closing release 1155 • Shunt trip ** • Under voltage release ** • Set of auxiliary contacts • Switch counter • Automatic recloser • Button press control on circuit breaker • Remote control on circuit breaker • Key interlock

60

4 5 6

20

2 3

7 8 9 10 11 5 6

9 10 1

L1 L2 L3

I

0

750

Cubicle Options • Protection relay (to be specified by the customer) 10 • Current transformer (to be specified by the customer) • Set of auxiliary contacts on the load break switch and/or earthing switch • Key interlock on load break switch and/or earthing switch • Motor operation on load break switch: 24-48-110VAC/DC and 220VAC • Short-circuit indicator (to be specified by the customer) • Earthing connections upwards from the circuit breaker • Circuit breaker gas insulated 1228 • Plinth: 200 - 400mm

1700

30 31 1 2 3 2829

4

24 212223 25 26 27

Standard Equipment • Three-phase load break switch RV44, class E3 according to IEC 62271-103, gas insulation • Vacuum circuit breaker • Interlocked earthing switch with rated making capacity up to 63kA downstream of the capacity switch • Cable support 1120 • Door interlock • Sockets for capacitive voltage detector • Voltage indicators • LV compartment

100

750

Width

mm

750

750

Depth

mm

1050

1050

Height

mm

1700

1700

Height between ground and socket

mm

445

445

Weight

kg

460

460

Weight with Arc Killer

kg

490

490

DF-D+/EDN (Arc Killer Option)

17

DF-2 Protection cubicle with remountable vacuum circuit breaker 970 with integrated protection relay I

400

DF-D-500

0

I

30 31 1 2 3 2829

7 8

212223

9 10 1

2 3

2 3 4

2425 26

27

12 1

9 7

995 940 1050 55

500

357 60

O

400

602

205

I

O

Ø79

Standard Equipment • Three-phase load break switch RV44, class E3 according to IEC 62271-103, gas insulation • Vacuum circuit breaker with integrated protection relay, current transformers and release • Interlocked earthing switch with rated making capacity up to 63kA downstream of the 375 100 capacity switch 500 • Cable support 940 500 1155 • Door interlock • Sockets for capacitive voltage detector • Low voltage compartment • Draw-out circuit breaker 847

I

1700

1700

110

7 8 9 10 11 5 6

11

4

A

9 10

Application 10 Feature breaker allowing fast exchange of the circuit breaker (minimum downtime). 8

0

20

L3

5 6 7

HR

DEBA

L2

4 5 6

HR

DEBA

L1

15 1617 18 13 14 19 12

HR

DEBA

Cubicle Options • Set of auxiliary contacts on the load break switch and/or earthing switch • Key interlock on load break switch and/or earthing switch • Motor operation on load break switch: 24-48-110VAC/DC and 220VAC • Short-circuit indicator (to be specified by the customer) • Voltage indicators • Plinth: 200 - 400mm Options on the circuit breaker • Motor operation ** • Closing release • Shunt trip ** • Under voltage release ** • Set of auxiliary contacts • Error contact • Supply for test protective relay (battery block) • Switch counter • Automatic recloser • Button press control on circuit breaker • Remote control on circuit breaker • Key interlock Specifications & Dimensions Rated Voltage

kV

12

Rated current

A

630

Short-term current

kA

25

Time of the short duration of current

s

1

mm

500

Width Depth

mm

1050

Height

mm

1700

Height between ground and socket

mm

450

kg

400

Weight

18

DF-2 Protection cubicle WITH vacuum circuit breaker (magnetic driven) AND integrated protection relay DF-DT

Standard Equipment • Three-phase load break switch RV44 - class E3 according to IEC 62271-103, gas insulation • Vacuum circuit breaker with magnetic drive and 6NO / NC auxiliary contacts • Interlocked earthing switch with a rated making capacity up to 63kA downstream of the circuit breaker • Cable support structure • Door interlock • Sockets for capacitive voltage detectors Ø10 • Voltage presence indicators • LV compartment

360

1700

Application Protection of feeders with circuit breaker, voltage and current transformer and Medium Voltage protection (max 1250A).

570

750

60

1050

775

Cubicle Options • Current transformer (to be specified by the customer) • Voltage transformer (to be specified by the customer) • Set of auxiliary contacts on the load break switch and/or earthing switch • Key interlock on load break switch and/or earthing switch • Choice of auxiliary voltage 24-48-110VDC or 110-220VAC • Short circuit indicator (to be specified by the customer) • Earthing connection upstream from the circuit breaker 100 • Voltage indication • Plinth: 200mm - 400mm

750

940

Options on the circuit breaker • Under-voltage release (electronic) • Supplementary auxiliary contacts • Operation counter • Reclosing function (standard) • Remote control • Interlock Specifications & Dimensions Rated Voltage

kV

12

24

Rated current

A

800-1250

630-1250

Short-term current

kA

16/20/25

16/20

Time of the short duration of current

s

1/02/03

1/02/03

Width

mm

750

750

Depth

mm

940

940

Height

mm

1700

1700

Height between ground and socket

mm

450

450

kg

360

360

Weight

19

DF-2 Protection cubicle with vacuum circuit breaker DF-AAD

Standard Equipment • Three-phase load break switch RV44, class E3 according toØ10IEC 62271-103, gas insulation • Vacuum circuit breaker with/without integrated protection relay • Door interlock • Low voltage compartment • Holder for capacitive voltage indicators load break switch 1 and/or 2 12 1

30 31 1 2 3 2829

9 10 1

2 3

2 3 4

9 7

O

100 Cubicle Options • Set of auxiliary contacts on load break switch 1 and/or 2 940 750 1155 • Key 750 interlock on load break switch 1 and/or 2, and/or earthing switch • Mechanical interlock between the load break switches • Motor operation on load break switch 1 and/or 2: 24-48-110VAC/DC and 220VAC • Earthing-switch • Earthing connections on load break switch 1 and/or 2 • Earthing connections outside of cubicle • Capacitive voltage indicators load break switch 1 and/or 2 • Plinth: 200mm - 400mm • Current transformers 60

940 1050

110

750

540 150

DF-AAD

Options on the circuit breaker • Motor operation/closing release/shunt trip ** • Current transformer shunt trip • Delay/direct under voltage release ** • Set of auxiliary contacts • Error contact • Supply for test protective relay (battery block) • Switch counter • Automatic recloser • Button press control on circuit breaker • Remote control on circuit breaker • Key interlock

900 1050

Specifications & Dimensions

DF-AAD+ (Arc Killer Option)

20

110

I

995

510 I

O

1700

1700

205

7 8 9 10 11 5 6

11

4

A

940 1050

I

0

9 10

I

0

7 8

L3

24 212223 25 26 27

HR

DEBA

L2

8

HR

DEBA

L1

20

HR

DEBA

L3

5 6 7

HR

DEBA

L2

4 5 6

HR

DEBA

L1

Application 1010 Protection of descending feeders with transformer and Medium Voltage equipment provided with circuit breaker and double Separation of busbar upstream and downstream. 510 15 1617 18 13 14 19 12

HR

DEBA

DF-AAD+ (with arc killer)

Rated Voltage

kV

12

24

Rated current

A

800-1250

630

Short-term current

kA

25

20

Time of the short duration of current

s

1

1

Width

mm

750

750

Depth

mm

1050

1050

Height

mm

1700

1700

Weight

kg

510

510

Weight

kg

510

510

DF-2 Protection cubicle with double interruption Standard Equipment • Double, three-phase load break switch RV44 - class E3 according to IEC 62271-103, gas insulation • Vacuum circuit breaker with magnetic drive and 6NO / NC auxiliary contacts • Cable support structure • Door interlock • Sockets for capacitive voltage detectors • Voltage presence indicators • LV compartment

150

750

940 Specifications & Dimensions

Rated Voltage

940 1050

995 100

60

Options on the circuit breaker • Under-voltage release (electronic) • Supplementary auxiliary contacts • Operation counter • Reclosing function (standard) • Remote control • Interlock

360 750

205

Cubicle Options • Auxiliary contacts on load break switch 1 and/or 2 up to 3NO/NC • Auxiliary contacts on the earthing switch up to 2NO/NC • Key interlock on the load break switch and/or earthing switch • Choice of auxiliary voltage 24-60-110VDC or 110-220VAC Ø10 • Short circuit indicator (to be specified by the customer) • Current transformers (to be specified by the customer) • Earthing connection upstream from the circuit breaker • Voltage indication • Plinth: 200mm - 400mm

1700

DF-AADT

kV

12

24

Rated current

A

800-1250

630-1250

Short-term current

kA

16/20/25

16/20

Time of the short duration of current

s

1/02/03

1/02/03

Width

mm

750

750

Depth

mm

940

940

Height

mm

1700

1700

Weight

kg

360

360

21

DF-2 Busbar coupling cubicle DF-LK 940 Application Coupling between two parts of the Medium Voltage panel.

150 995

1700

Specifications & Dimensions

60

150

Options • Holder for capacitive voltage indicators load break switch 1 and/or 2 100 • Set of auxiliary contacts on load break switch 1 and/or 2 • Key interlock on load break switch 1 and/or 2, and/or earthing switch 750 750 900 • Mechanical interlock between the load break switches • Motor operation on load break switch 1 and/or 2: 24-48-110VAC/DC and 220VAC • Earthing-switch • Earthing connections on load break switch 1 and/or 2 • Earthing connections outside of cubicle • Capacitive voltage indicators load break switch 1 and/or 2 • Plinth: 200mm - 400mm • Current transformers

900 1050

900 1050

Ø10

205

27

2425 26

9 10

9 10 1

7 8

212223

8

30 31 1 2 3 2829

20

5 6 7

9 10

7 8

15 1617 18 13 14 19 12

8

4 5 6

20

12 1

9 7

2 3

1700

11

2 3 4

A

7 8 9 10 11 5 6

2 3

2 3 4

9 10 1

5 6 7

30 31 1 2 3 2829

245

4

12 1

9 7

7 8 9 10 11 5 6

245

11

4

A

24 212223 25 26 27

Standard Equipment • 2 three-phase load break switch RV 44, class E3 according to IEC 62271-103, gas insulation • Door interlock • Low-voltage compartment 4 5 6

I

0

15 1617 18 13 14 19 12

I

0

750

22

Rated Voltage

kV

12

24

Rated current

A

800-1250

630

Short-term current

kA

25

20

Time of the short duration of current

s

1

1

Width

mm

750

750

Depth

mm

1050

1050

Height

mm

1700

1700

Weight

kg

245

245

DF-2 Transformer housing DF-T Application The DF-T cubicle has been designed from the long-term practical experience of installing and connecting distribution transformers.

B

B

B

A

Cubicle Options • Key interlock with LV protection • Shaft with rail set on top of the transformer housing • LV compartment • Oil receptacle • Forced ventilation • With closed back • With closed roof • Extra ventilation • Opening for LV switch of LV equipment • Opening for the thermometer • Opening for digital measuring set • Holder for capacitive voltage indicators • Capacitive voltage indicators B • IP2X / IP4X / IP315 • Interlockable doors • Interlock possibilities

*

C

Standard Equipment • Windows • Ventilation openings • Hinge door(s) in function of the cubicle width

A

If a built-in LV switch is required in the DF-T, the size needs to be specified. The DF-T was designed specifically with ventilation problems in mind. The ventilation openings in the cubicle ensure that the transformer will constantly be ventilated. The specific concept allows the transformer to be driven in and out smoothly at all times.

C

C

Width

Height

Depth

100-160 kVA

1200

1900

1050

250-630 kVA

1400

2100

1150

800-1000 kVA

1800

2100

1150

1250-1600 kVA

2000

2100

1400

2000-2500 kVA

2400

2400

1500

B

A

A

Dimensions Oil Filled Transformers

Dimensions Cast Resin Transformers Width

Height

Depth

1500

1900

1050

1800

2100

1150

2000

2100

1200

1250-1600 kVA

2200

2200

1300

2000-2500 kVA

2400

2400

1400

100-160 kVA 250-630 kVA 800-1000 kVA

B

C

23

DF-2 DF-C-750 | Metering cubicle

DF-P | Protection cubicle

DF-A | Load break switch with interlock earth switch (outgoing)

DF-A | Load break switch with interlock earth switch (incoming)

Transformer

29

24

DF-2 Metering cubicle DF-C-500

DF-C-750

Standard Equipment • 3 Ti’s xA => 5A • 3 Tp’s xV => 110V, V3 Cubicle Options • Additional current transformers • Additional voltage transformer with or without Medium Voltage and LV protection • Support for the positioning of measuring transformers • Measuring system with 3 CTs and 3 VTs • Measuring system with KWH metering and Kvarh metering (requirements to be specified by the customer) • Current measurement system • Voltage measurement system • Plinth: 200mm - 400mm • Low voltage compartment safety box to secure voltage circuits

240

1700

p

330

750

p

720

The following voltage transformer VT specifications need to be specified by the customer: 940 • Primary voltage, secondary voltage, capacity and precision class, 205 insulation class

A

720 760 Time of the short

up to 1250

kA

25

20

s

1

1

Width

mm

500

500

Depth

mm

720

720

Height

mm

1700

1700

kg

240

240

up to 630

100

300 500

duration of current

570

365

205

10 Ø79

Ø79

900

995 190

55

60

280

100

900

DF-C-500

775

Weight **

55

1050

Rated current

195

24

150

12

79

kV

55

Rated Voltage

165

Specifications & Dimensions

Short-term current

165

The following current transformer CT specifications need to be specified by the customer: • Primary current, secondary current, capacity and precision class, insulation class, rated 10 short time current 100

750 DF-C-750

25

DF-2 Busbar link panel DF-LKB Application Panel above switchgear, required for connection of two non-adjacent panels. Available for connecting panels of different dimensions. Standard Equipment • 1 three-phase load break switch RV 44, class E3 according to IEC 62271-103, gas insulation • Low-voltage compartment • Holder for capacitive voltage indicators load break switch left/right • In case of coupling between two cubicles of 750mm, a final piece of 250mm will be provided Cubicle Options • Set of auxiliary contacts on the load break switch • Key interlock on load break switch • Motor operation on load break switch: 24-48-110VAC/DC and 220VAC • Earthing ball clamps on load break switch left/right • Earthing ball clamps outside of cubicle • Capacitive voltage indicators on load break switch left/right • Plinth: 200-400mm Specifications & Dimensions

26

Rated Voltage

kV

12

24

Rated current

A

800-1250

630

Short-term current

kA

25

20

Time of the short duration of current

s

1

1

Width

mm

1000/1250

1000/1250

Depth

mm

975

975

Height

mm

500

500

Weight

kg

162

176

DF-2 Cable connection panel or bus riser DF-K Application Cubical for a separate cable connection zone. These panels can also be used as busbar zones or busbar risers.

1700

Options • Holder for capacitive voltage indicators • Capacitive voltage indicators • Short-circuit detectors (to be specified by the customer when ordering) 940 • Earthing switch • Set of auxiliary contacts on earthing switch • Key interlock on earthing switch • Earthing ball clamps • Current transformers in the busbar • Voltage transformers with of without protection in the busbar • Plinth: 200mm - 400mm • Door interlock

55

775 990

Rated Voltage

kV

12

24

Rated current

A

up to 1200

up to 630

Short-term current

kA

up to 25

up to 20

Time of the short duration of current

s

1

1

900

400 100 60

Specifications & Dimensions

210 500

Width

mm

M

M

Depth

mm

1050

1050

Height

mm

M

M

kg

55

55

Weight **

570

Ø79

365

Possible Connections • Bottom in - top out • Bottom in - top left out • Bottom in - top right out 900

1700

150

Ø10

210

500

27

DR-6/DT-6 RING MAIN UNITS (RMUs) DR-6/DT-6

A compact and extensible gas insulated ring main unit with load break switch or integrated vacuum circuit breaker. Safe, reliable, compact and insensible to the environment in the field of electricity distribution up to 24kv.

28

DR-6/DT-6 DESCRIPTIONS DR-6/DT-6

LBS operating axle Position indicator Release rotary button Earthing switch operating axel Synoptic diagram Voltage indicator Cable compartment Acces door

Circuit breaker tripping axle Operation button circuit breaker Pressure indicator Protection relay LBS operating axle Position indicator Earthing switch operating axle Voltage indicators (VDS) Access door to cable compartment

29

DR-6/DT-6 DEVELOPMENT & MANUFACTURING PHILOSOPHY The DR-6/DT-6 range offers a compact, safe, reliable and economical design which is free of any possible environmental aggression. Extensions on site is possible without any special tooling nor particular surrounding conditions. THE COMPONENTS

Load break switch The three position load break switch (ON/OFF/Earth) is in accordance with the IEC requirements. The concept insures a natural interlock of the primary functions of the cubicle. The arc extinction is insured by gas, which reduces arcing time. The load break switch RV44 of the DF-2 range is of the class E3/M1 (100 CO and 1000 mechanical operations) following IEC 62271-103 and is therefore a perfect application.

Circuit breaker The SGC ISM-086 vacuum circuit breaker (VCB) of the magnetic actuator type uses the latest vacuum interrupter technology. The VCB can only be closed electrically and therefore mechanical closing is not possible*. The VCB can be opened only electrically. The circuit breaker operates through a control module and a self powered digital protection relay RP600, this together with the three CT’s allows the detection of over-current and earth faults failures. (*) In absence of auxiliary voltage, a hand operated generator can be used.

The fuse holders The fuse holders are made for HRC fuses of the DIN and UTE type for voltages of 12, 12 (Utilities Specification) and 24kV. A simple intelligent artifice allows the change without any particular tooling. Fuse holders are made from epoxy with a non-losable cover, and a fuse supporting structure firmly fixed to the cover. Earthing on both sides of the fuses is clearly marked on the synoptic diagram. The fuse holder is water tight and tested in accordance with the IEC standards. Access to the fuse holders is facilitated by a simple and logic interlock system allowing the opening of the door only after earthing of the cubicle. The mechanical drives Deba Components mechanical drives have already been subject to intensive tests and usage in the DF-2 range of products. The same design has been implemented in the DR-6/DT-6. The steel used for the drives has been chosen because of their high tensile force, toughness and resistance to bending. The mechanical drive accommodates both the operates axles (LBS and earth) and the interlocks. The spring type drive operates independently of the operator and does not allow any function violation. The switch position indicator shows at any time the real status of the switch. The forces needed to control the mechanism are low which results in a high user-friendliness. The drive can be motorized and can receive a number of options and allows remote control, remote position indication and integration into a SCADA operated network.

30

DR-6/DT-6 Cable connection The cables are connected to the cubicles by means of bushings with M16 screwed contacts and for connectors according to EN 50 181 / DIN 50 standards. They may be of the type A/B or C (200, 400 630A) and they are defined in function of their applications. The cable compartment size allows one connector per bushing with a maximum of 400mm2 per cable (on request, lightning arrestors can also be accommodated in the cable box as well as two cables per bushing). The extensibility concept Extensibility of the ring main unit is ensured by top placed bushings of the C- type. An insulated and screened extension device connects the two sets to be extended. Extension requires no special tooling nor special on site condition. The bushings are directly moulded on a stainless steel plate avoiding any risk of leakage caused by mechanical assembly.

The synoptic diagram and the accessories A clear, logic and well understandable synoptic diagram is placed in front of each of the functions. This diagram also supports the voltage indicator of the type HR-3, showing the presence of the voltage on the cables and allowing the use of phase concordance units. Short circuit indicators can find their place in the LV compartment and the associated ring type CT’s in the cable box. Complementary accessories can be accommodated in a well designed LV box to be placed on the top of the concerned function(s).

IEC 62271-102 HV AC disconnectors and earthing switches IEC 62271-105 HV AC Fuse switch combination IEC 62271-100 HV AC circuit breakers IEC 62271-1 Common specifications for HV switchgear and controlgear

1 2 3 4 5 6 7 8

1

2

3

4

5

6

7

8

9



1 2 3 4 5 6 7 8



IEC 62271-200 AC metal enclosed switchgear and controlgear above 1kV up to 52 kV

Protection relay The self powered digital protection relay has a wide range of protection functions, is equipped with four outgoing contact points and two free programmable outgoing points. The relay functions are easy accessible and programmable with the help of a laptop or with the support of the menu oriented interface.

+

Applicable standards

0 RP600

The enclosure The stainless steel enclosure is manufactured on brand new, up to date machines associating laser cutting, robotised bending and 3-D laser welding. The welded tank is sealed for life and tested under vacuum, in strict conditions with experienced equipment. The enclosure accommodates the life components and is foreseen of a rupture disk avoiding any problem in the improbable case of an internal overpressure.

IEC 61243-5 Voltage detection systems (VDS)

31

DR-6/DT-6 ELECTRICAL CHARACTERISTICS

Rated voltage General specifications Impulse withstand voltage 1.2 / 50 µsec. To earth and between phases Over the insulation distance Power frequency voltage test 1 min. To earth and between phases Over the insulation distance Rated frequency Rated current Rated short time current 1 sec. Rated peak value of the current Breaking capacity (IEC 62271-103) Rated current Closed loop No load cable Earth leakage fault Internal arc 1 sec. IEC 62271-200 (5 criteria) Degree of protection HV-compartment LV- and cable compartment Rated gas pressure at 20°C Line Feeder Rated current Rated short time current 1 sec. Rated peak value of the current Transformer feeder Rated current   Fuse switch Short circuit breaking capacity (limited by the fuse) Making capacity Circuit breaker Short circuit breaking capacity 1 sec. Making capacity Number of makings

kV

12

12 Utilities Specifications

24

kV kV

75 85

95 110

125 145

kV kV Hz A kA kÂ

28 32

38 45 50/60

50 60

A A A A kA

630 630 30 100 20

630 25 63

400/630 12.5/16/20 40/50

20 50 Class E3 630 630 30 100 20

400/630 400/630 30 100 20

IP6X IP4X 0.3 bar overpressure

Bar A kA kÂ

630 25 63

630 20 50

630 12.5/16/20 31.5/40/50

A

200

200

200

kA kÂ

25 63

25 63

16/20 40/50

kA kA

20 63

20 50 5

16 50

FUSE SELECTION TABLE Standard UTE

DIN 10 DIN 20

32

kV 10 15 20 10 11 13.8 15 20 22

Power of the distribution transformer (kVA) 100 125 160 200 250 16 16 31.5 31.5 31.5 16 16 16 16 16 16 16 16 16 16 16 20 25 25 31.5 16 20 20 25 25 10 16 16 20 25 10 10 16 20 25 10 10 16 16 20 10 10 10 16 16

315 63 43 16 40 40 31.5 31.5 25 20

400 63 43 43 50 40 40 31.5 25 25

500 63 43 43 50 50 40 40 31.5 31.5

630 63 43 43 63 50 50 50 40 40

800

1000

1250

43 43 80 63 50 50 40 40

63 43 100 80 63 63 63 50

63 125 100 100 80 63 63

1600

2000

125 100 80 80

100 100

DR-6/DT-6 DIMENSIONS AND DESCRIPTIONS

DR-6C 2KT DR-6E-2KT

DR-6C 2K

DR-6C 2K2T

I>I>>

I>I>>

DR-6C 3KT

DR-6C 3KD

DR-6C 2KD DR-6E-2KD

DR-6E EXTENSIBLE FUNCTIONAL UNITS

FUNCTION DESCRIPTION K - Incoming/ outgoing cubicle T - Fuse protection cubicles (combined D - Circuit breaker cubicle C - Metering cubicle gas insulated

I>I>>

DR-6 2E K

DR-6 2E T

DR-6 2E D

DR-6 2E C

DR-6E EXTENSIBLE FUNCTIONAL UNITS

DR-6C/DR-6E COMPACT - NON EXTENSIBLE/EXTENSIBLE RING MAIN UNITS Type

Height

Width

Depth

Weight

Type

Height

Width

Depth

Weight

DR-6C 2K

1410 mm

600 mm

720 mm

280 kg

DR-6E K

1460 mm

300 mm

720 mm

140 kg

DR-6C 2KT

1410 mm

950 mm

720 mm

450 kg

DR-6E T

1460 mm

350 mm

720 mm

180 kg

DR-6E 2KT

1460 mm

950 mm

720 mm

470 kg

DR-6E D

1460 mm

350 mm

720 mm

210 kg

DR-6C 2K2T

1410 mm

1300 mm

720 mm

640 kg

DR-6E C

1460 mm

500 mm

720 mm

240 kg

DR-6C 3KT

1410 mm

1250 mm

720 mm

600 kg

­DT-6C 2KD

1420 mm

950 mm

838 mm

530 kg

DT-6E 2KD

1460 mm

950 mm

838 mm

550 kg

DT-6C 3KD

1460 mm

1250 mm

838 mm

660 kg

The functional units are always extendable to the left or the right of the multifunctional unit.

The multifunctional units are always extendable in both directions.

33

DW-2 WITHDRAWABLE SWITCHGEAR DW-2

A family of air-insulated fully withdrawable medium voltage switchgear solutions for indoor installations. DW-2’s modular design allows you to create rational, economical and custom-made combinations of medium voltage cubicles (up to 12kV).

34

DW-2 Type tests DW-2 switchgear solutions are all fully type tested according to IEC 62271-200: • • • • • • •

Short time and peak withstand current Temperature rise and main circuit impedance Dielectric test on main and auxiliary circuits Making and breaking capacity of the circuit breaker within the panel Earthing switch making capacity Mechanical operations Internal arc fault (IAC classified: AFLR, 31.5A/1s)

Availability and partition DW-2 switchgears are designed in compliance to availability classes LSC2B and partition class PM according to IEC 62271-200. The switchgear compartments do not need any tools for opening. Interlocks allow access only when the corresponding high voltage parts are dead and earthed. Metallic shutters and partitions segregate the compartments from each other. When a compartment is opened all other panels in the installation and all cable termination compartments (including that in the panel concerned) remain in operation.

Internal arc fault test, 31.5kA/1s 35

DW-2 COMPARTMENTS

36

LOW-VOLTAGE COMPARTMENT The protection relays that controls the circuit breaker and accessories, such as the auxiliary contacts, and minimum voltage relays, are also located in this compartment. The compartment can be accessed very easily by opening the compartment door.

LOW-VOLTAGE COMPARTMENT

BUSBAR COMPARTMENT

SWITCHGEAR COMPARTMENT

BUSBAR COMPARTMENT The busbar compartment is located in the back side of the cubicle and behind the low-voltage compartment. The modular busbar set is manufactured from specially provided electrolyte F25 copper. Several cubicles are connected through the bar set compartments. Hexagonal bolts connect the busbars to the upper contact surfaces of the fixed contacts in the insulators.

CABLE COMPARTMENT The cable compartment is located behind the interlocked, removable door of the DW-2 cubicle. This part accepts the cable(s) and contains the necessary equipment to connect the cable(s). The earthing switch is installed below the circuit breaker switch on the back side, ensuring a “visible earthing” when the earthing switch is closed. The door and the sectional floor panels, which house the necessary conductive rubber for the cables, and the cable supports, all simplify the cable connection.

CABLE COMPARTMENT

SWITCHGEAR COMPARTMENT In this compartment, the withdrawable magnetic driven vacuum circuit breaker switch, acts as the physical separation between the busbar set and the cable compartment. The switch has two functions: it connects or interrupts the electrical current between the high voltage cables and the busbar.

DW-2 TECHNICAL SPECIFICATIONS

Rated Data Rated Voltage

12kV

12 Utilities Specifications

Rated power frequency withstand voltage (Ud)

28kV

42kV on request

Rated lightning impulse withstand voltage (peak)

75kV

95kV on request

Rated short-circuit breaking current (Isc)

to 31.5kA

to 31.5kA

Rated peak withstand current (Ip)

to 82kA

to 82kA

Rated short-time withstand current (Ik)

to 31.5kA

to 31.5kA

Rated duration of short circuit current (tk)

4s

4s

Internal arc withstand current, 1s

31.5kA

31.5kA

Rated frequency

50/60Hz

50/60Hz

Rated busbar current

2500A

2500A

Rated feeder current

630A, 1250A, 1600A, 2000A

630A, 1250A, 1600A, 2000A

IEC 62271-200

IEC 62271-200

Degree of protection (RC 630A, 1250A)

IP4X

IP4X

Degree of protection (RC 1600A, 2000A)

IP3X

IP3X

-25…+40 °C

-25…+40 °C

95%

95%

1000m a.s.l.*

1000m a.s.l.*

Standards

Temperature range Maximum relative humidity Maximum altitude Notes:

* For installations at altitudes higher than 1000m, the insulation withstand level of external insulation at the service location has to be determined by multiplying the rated insulation levels by a factor Ka in accordance to IEC 62271-1.

37

DW-2 DW-2 MODULES

38

Withdrawable circuit breaker panel with optional earthing switch - DW-2-IF

PAGE 39

Busbar riser with optional VT - DW-2-BR

PAGE 40

Bustie with optional CT and earthing switch - DW-2-BT

PAGE 41

VT panel with optional earthing switch - DW-2-M

PAGE 42

Incoming feeder connection panel - DW-2-DIF

PAGE 43

DW-2 WITHDRAWABLE CIRCUIT BREAKER WITH Optional EARTHING SWITCH DW-2-IF Application Incoming/outgoing feeder with optional earthing switch. Specifications & Dimensions Rated current

A

630 - 1250

1600-2000

Height

mm

2200

2200

Height with arc venting shields

mm

2500

2600

Height with gas exhaust duct

mm

2600

2600

Width

mm

650/800

800

Depth

mm

1260

1260

Possible Configurations

39

DW-2 Bus riser WITH OPTIONAL VT DW-2-BR Application Cubical for rising bus from bottom to top/or top to bottom with optional VT for metering or auxiliary voltage supply. Specifications & Dimensions Rated current

A

630 - 1250

1600-2000

Height

mm

2200

2200

Height with arc venting shields

mm

2500

2600

Height with gas exhaust duct

mm

2600

2600

Width

mm

650/800

800

Depth

mm

1260

1260

Possible Configurations

40

DW-2 Bus TIE with optional ct and earthing switch DW-2-BT Application Bus tie with optional earthing switch for earthing one side of bus tie. Optional CT for metering requirements. Specifications & Dimensions Rated current

A

630 - 2000

Height

mm

2200

Height with arc venting shields

mm

2500

Height with gas exhaust duct

mm

2600

Width

mm

650/800

Depth

mm

1260

Possible Configurations

41

DW-2 VT PANEL with optional earth switch DW-2-M Application Voltage Source or metering voltage tap with optional earthing switch. Specifications & Dimensions Rated current

A

630 - 2000

Height

mm

2200

Height with arc venting shields

mm

2500

Height with gas exhaust duct

mm

2600

Width

mm

650/800

Depth

mm

1260

Possible Configurations

42

DW-2 incoming feeder connection panel DW-2-DIF Application Incoming cable connecting metering with optional earth switch, CT’s and VT’s. Specifications & Dimensions Rated current

A

630 - 1250

1600-2000

Height

mm

2200

2200

Height with arc venting shields

mm

2500

2600

Height with gas exhaust duct

mm

2600

2600

Width

mm

650/800

800

Depth

mm

1260

1260

Possible Configurations

43

DI-2 GAS INSULATED SWITCHGEAR DI-2

A modular concept combining all medium-voltage functions. DI-2’s modular design allows you to create rational, economical and custom-made combinations of medium-voltage cubicles (with a rated voltage of up to 36kV)

44

DI-2 TECHNICAL SPECIFICATIONS

Rated Voltage

kV

Up to 36

- To earth and between phases

kV

170

- Over the insulated distance

kV

195

- To earth and between phases

kV

70

- Over the insulated distance

kV

80

Rated frequency

Hz

48/62

Rated current

A

400/630

Rated short-time current 3s.

kA

20

Rated peak value of the current



50

- Mainly active load current (I1 / Iloop)

A

400/630

- Closed loop current (I2A / Iloop)

A

630

- Cable charging current (I4A/ICC)

A

25

A

2

- Short circuit making current (Ina)



50

- Earth fault current (I6a/Ief1)

A

50

- Cable and line charging current under earth faults (I6b / Ief2)

A

16

Impulse withstand voltage 1.2 / 50 μs

Power frequency withstand voltage:

Breaking capacity RV36 (Class E3)

(I4B)

Degree of protection Mechanical durability c/o

IP2X 1000 (=M1)

Standards

IEC 62271-100, IEC 62271-1, 62271-102, -103, -105, 62271-200 and IEC 61243-5

Certificates

KEMA/IPH

45

DI-2 DI-2 MODULES

46

Load break switch and interlocked earthing switch - DI-A

PAGE 62

Load break switchfuse combination - DI-P

PAGE 63

Protection cubicle with load break switch and vacuum circuit breaker - DI-D

PAGE 64

DI-2 LOADBREAK SWITCH AND INTERLOCKED EARTHING SWITCH DI-A Application Incomer or feeder cable connection cubicle. Standard Equipment • Three-phase load break switch RV36, class E3 according to IEC 62271-103, gas insulation • Integrated interlocked earthing switch with making capacity up to 50kA • Cable support • Door interlock • Sockets for capacitive voltage detector with parallel testing possibility • Low-voltage compartment Options • Set of auxiliary contacts on load break switch • Set of auxiliary contacts on earthing switch • Key interlock on load break switch and/or earthing switch • Motor operation: 24-48-110V-DC of 110-220VAC • Short-circuit indicator (to be specified by the customer when the order is placed) • Voltage indicators • Plinth: 200mm - 400mm Specifications & Dimensions Rated Voltage

kV

36

Rated current

A

630

Short-term current

kA

20

s

3

Width

mm

418

Depth

mm

760

Height

mm

1790

Height between ground and end socket

mm

790

Height between ground and cable support

mm

310

kg

225

Time of the short duration of current

Weight IAC AFL

16kA - 1s

47

DI-2 load break switchfuse combination DI-P Application Transformer protection and Medium Voltage equipment protection. Standard Equipment • Three-phase load break switch RV36, class E3 according to IEC 62271-105, gas insulation • Double earthing switch with mutual interlock • Socket for HRC fuses: • Door interlock • Sockets for capacitive voltage detector • Low-voltage compartment • Three phase tripping in case of fuse trip Options • Set of auxiliary contacts on load break switch and/or earthing switch • Key interlock on load break switch and/or earthing switch • Shunt trip * • Under voltage release * • Closing release * • Motor operation * • HRC fuses and/or spare fuses • Contact “fuse blown” • Automatic recloser • Set of 2 or 3 voltage transformers • Voltage indicators • Plinth: 200mm - 400mm Specifications & Dimensions Rated Voltage

kV

36

Rated current

A

630

Short-term current

kA

20

s

3

mm

524

Time of the short duration of current Width Depth

mm

950

Height

mm

1790

Height between ground and end socket

mm

790

Height between ground and cable support

mm

310

kg

250

Weight IAC AFL

48

16kA - 1s

DI-2 Protection cubicle with LOAD BREAK SWITCH AND VACUUM CIRCUIT BREAKER DI-D Application Protection of descending feeders with circuit breaker, transformer and Medium Voltage equipment protection. Standard Equipment • Three-phase load break switch RV36, class E3 according to IEC 62271-103, gas insulation • Vacuum circuit breaker with integrated protection relay, current transformers and release • Interlocked earthing switch with rated making capacity up to 50kA downstream of the capacity switch • Cable support • Door interlock • Sockets for capacitive voltage detector • Voltage indicators • LV compartment Options • Set of auxiliary contacts on the load break switch and/or earthing switch • Key interlock on load break switch and/or earthing switch • Motor operation on load break switch: 24-48-110VAC/DC and 220VAC • Short-circuit indicator (to be specified by the customer) • Earthing connections upwards from the circuit breaker • Voltage indicators • Plinth: 200mm - 400mm Specifications & Dimensions Rated Voltage

kV

36

Rated current

A

630

Short-term current

kA

20

s

3

Width

mm

600

Depth

mm

1047

Height

mm

1790

Height between ground and end socket

mm

790

Height between ground and cable support

mm

310

kg

352

Time of the short duration of current

Weight IAC AFL

16kA - 1s

49

DF-3 COMPACT AIR INSULATED SWITCHGEAR DF-3

The safe, compact and environmentally concious Medium Voltage Switchgear cubicle. The DF-3 has extendable switchgear with three functional gas insulated load break switch and associated mechcanical drives.

50

DF-3 The new modular and extendable switchgear DF-3 THE CONCEPT DF-3

• • • • •

Gas insulated three-functional (ON/OFF/EARTH) load break switch and associated mechanical drives Up to 24kV insulation voltage level - 800/630A Air insulated cable and busbar compartment PI/LSC2A/IAC AFL 16 KA (AFLR - optional)/E3/M1 according to IEC 62271 (100/102/103/105/200) Integrated voltage presence indicators with phase comparison possibility (IEC 61243-5) Clear and visible single line diagram with functional integrated interlocking

HR

DEBA COMPONENTS

1400



THE ADVANTAGES • • • • • • • • •

Developed and manufactured in line with the ISO 9001 standards Reduced sizes (hxlxp - 1400 (1700)mm x 375 (500)mm x 900mm) very near of the compact full gas insulated designs factory tested Mechanical spring operated drives with numbers of options for Scada applications and remote control Galvanised steel construction Reduced on site installation time and possibility of extension at any time Conventional cable connections Exceptional accessibility to all components of the cable compartment Easy op operate, reliable and safe for the operator Maintenance free

375/500

DF-3 A DF-D-500 DF-3 P

51

DF-3 COMPARTMENTS

52

LOW-VOLTAGE COMPARTMENT The drive mechanism that controls the RV53 load break switch and the integrated earthing switch is fitted with the synoptic diagram and is located behind the front panel. Several accessories such as the auxiliary contacts, switch-on or switch-off coils, and minimum voltage relays, are also located in this compartment. An optional motorized drive mechanism with all the necessary control elements could also be installed in this compartment. The compartment can be accessed very easily by disassembling the front panel. Optional padlocks prevent unauthorised access.

LOW-VOLTAGE COMPARTMENT

BUSBAR COMPARTMENT

SWITCHGEAR COMPARTMENT

BUSBAR COMPARTMENT The busbar compartment is located in the upper part of the cubicle and behind the low-voltage compartment. The modular busbar set is manufactured from specially provided electrolyte F25 copper Ø27mm (IrBB=630A). Various cubicles are connected through busbar compartments. Hexagonal bolts connect the busbars to the upper contact surfaces of the RV53 load break switch.

CABLE COMPARTMENT The cable compartment is located behind the interlocked, removable door of the DF-3 cubicle. This part of the cubicle accommodates the cable(s) and contains the necessary equipment to connect the cable(s). In a DF-A cubicle, the cables are connected to the contact points below the RV53 load break switch. The cables of the DF-P cubicles are connected to the lower fuse base side. This type of cubicle also has an additional auxiliary earthing switch to divert any residual current. DF-D types have the earthing located in the cable compartment below the circuit breaker. The removable door, the sectional floor panels, which house the necessary conductive rubber for the cables, and the cable supports, all simplify the cable connection.

CABLE COMPARTMENT

SWITCHGEAR COMPARTMENT In this compartment, the gas filled RV53 three position load break switch acts as the physical separation between the busbar set and the cable compartment. The switch has three functions: it connects or interrupts the electrical current between the high voltage cables and the busbar. Additionally, the earthing switch is integrated.

DF-3 TECHNICAL SPECIFICATIONS

Rated Voltage

kV

12

12 *

24

- To earth and between phases

kV

75

95

125

- Over the insulated distance

kV

85

110

145

- To earth and between phases

kV

28

38

50

- Over the insulated distance

kV

32

45

60

Rated frequency

Hz

50/60

50/60

50/60

Rated current

A

630

630

630

Rated short-time current 1s.

kA

20

20

20

Rated peak value of the current



50

50

50

- Mainly active load current (I1 / Iloop)

A

630

630

630

- Closed loop current (I2A / Iloop)

A

630

630

630

- Cable charging current (I4A/ICC)

A

16

16

16

(0,2-0,4 I4A / 0,1-0,4 ICC)

A

5

5

5

- Short circuit making current (Ina)

kA

50

50

50

- Earth fault current (I6a/Ief1)

A

100

100

100

- Cable and line charging current under earth faults (I6b / Ief2)

A

30

30

30

Impulse withstand voltage 1.2 / 50 μs

Power frequency withstand voltage:

Breaking capacity RV53 (Class E3)

Degree of protection

IP4X

Mechanical durability c/o

1000

Standards

IEC 62271-100, IEC 62271-1, 62271-102, -103, -105, 62271-200 and IEC 61243-5

Certificates

KEMA/IPH

* Utilities Specifications

53

DF-3 DF-3 MODULES

54

Load break switch and interlocked earthing switch - DF-A/DF-A+

PAGE 55

Load break switchfuse combination - DF-P

PAGE 56

Protection cubicle with vacuum circuitbreaker and integrated protection relay -DF-D

PAGE 57

Metering cubicle - DF-C-750

PAGE 58

Cable cubicle and/or bus zone - DF-K

PAGE 59

DF-3 LOAD BREAK SWITCH AND AIR INTERLOCKED EARTHING SWITCH DF-A

DF-A+ (12 kV Only)

Application Supply cable connection Standard Equipment • Three phase load break switch RV53, class E3 according to IEC 62271-103, gas insulation • Integrated interlocked earthing switch with making capacity up to 50kA • Cable support • Door interlock • Sockets for capacitive voltage detector with parallel testing possibility • Low-voltage compartment Options • Set of auxiliary contacts on load break switch and\or earthing switch • Key interlock on load break switch and\or earthing switch • Motor operation: 24-48-110V-DC of 110-220VAC • Short-circuit indicator (to be specified by the customer when the order is placed) • Voltage indicators • Plinth: 200mm - 400mm Specifications & Dimensions Rated Voltage

kV

12

12*

24

Rated current

A

630

630

630

Short-term current

kA

20

20

20

s

1

1

1

Width

mm

375/500

375/500

500

Depth

mm

950

950

950

Height

mm

1400

1400

1400

Height between ground and end socket

mm

790

790

790

Height between ground and cable support

mm

310

310

310

kg

115/140

115/140

140

Time of the short Duration of current

Weight IAC AFL

DF-C-500

14 kA - 1s

DF-C-750

55

DF-3 load break switchfuse combination DF-P Application Transformer protection and Medium Voltage equipment protection. Standard Equipment • Three phase load break switch RV53, class E3 according to IEC 62271-105, gas insulation • Double earthing switch with mutual interlock • Socket for HRC fuses: - e = 292mm DIN 10 at 17.5kV - UTE • Door interlock • Sockets for capacitive voltage detector • Low-voltage compartment • Three phase tripping in case of fuse trip Options • Set of auxiliary contacts on load break switch and\or earthing switch • Key interlock on load break switch and\or earthing switch • Shunt trip ** • Under voltage release ** • Closing release ** • Motor operation ** • HRC fuses and/or spare fuses • Contact “fuse blown” • Automatic recloser • Set of 2 or 3 voltage transformers • Voltage indicators • Plinth: 200mm - 400mm Specifications & Dimensions Rated Voltage

kV

12

12*

24

Rated current

A

630

630

630

Short-term current

kA

20

20

20

Time of the short duration of current

s

1

1

1

Width

mm

375

375

375

Depth

mm

950

950

950

Height

mm

1400

1400

1400

Height between ground and end socket

mm

330

330

330

Fuse size

mm

292 (DIN)

292 (DIN)

292 (DIN)

kg

134

134

134

Weight

56

DF-3 Protection cubicle with vacuum circuit breaker and integrated protection relay DF-D Application Protection of descending feeders with circuit breaker, transformer and Medium Voltage equipment protection. Standard Equipment • Three-phase load break switch RV53, class E3 according to IEC 62271-103, gas insulation • Vacuum circuit breaker with integrated protection relay, current transformers and release • Interlocked earthing switch with rated making capacity up to 63kA • Cable support • Door interlock • Sockets for capacitive voltage detector • Voltage indicators • LV compartment Cubicle Options • Set of auxiliary contacts on load break switch and\or earthing switch • Key interlock on load break switch and\or earthing switch • Motor operation on load break switch: 24-48-110VAC/DC and 220VAC • Short-circuit indicator (to be specified by the customer) • Earthing connections upwards from the circuit breaker • Circuit breaker gas insulated • Voltage indicators • Plinth: 200mm - 400mm Options on the circuit breaker • Motor operation ** • Closing release • Shunt trip ** • Under voltage release ** • Set of auxiliary contacts • Error contact • Supply for test protective relay (battery block) • Switch counter • Automatic recloser • Button press control on circuit breaker • Remote control on circuit breaker • Key interlock Specifications & Dimensions Rated Voltage

kV

12

12*

24

Rated current

A

630

630

630

Short-term current

kA

20

20

20

Time of the short duration of current

s

1

1

1

Width

mm

675

675

675

Depth

mm

950

950

950

Height

mm

1500

1500

1500

Height between ground and socket

mm

360

360

360

kg

460

460

460

Weight

57

DF-3 Metering cubicle DF-C-750 Application The DF-C-750 cubicle has been designed for positioning current and voltage transformers to measure energy consumption. Standard Equipment • 3 Ti’s xA => 5A • 3 Tp’s xV => 110V, V3 Options • Additional current transformers • Additional voltage transformer with or without Medium Voltage and LV protection • Support for the positioning of measuring transformers • Measuring system with 3 CTs and 3 VTs • Measuring system with kWh metering and Kvarh metering (requirements to be specified by the customer) • Current measurement system • Voltage measurement system • Plinth: 200mm - 400mm • Low voltage compartment safety box to secure voltage circuits Possible connections: • Bottom left in - bottom right out • Bottom right in - bottom left out • Bottom left in - top right out • Bottom right in - top left out • Top right in - top left out • Top left in - top right out Specifications & Dimensions Rated Voltage

kV

12

24

Rated current

A

up to 630

up to 630

Short-term current

kA

20

20

Time of the short duration of current

s

1

1

Width

mm

750

750

Depth

mm

950

950

Height

mm

1400

1400

kg

55

55

Weight** ** Without equipment

58

DF-3 Cable cubicle and/or Bus zone DF-K Application Cubicles of the DF-3 type are equipped to bring in a supply cable, however a DF-K cubicle can also contain a busbar and can be used as rising cubicle of the rail set. Standard Equipment • Three-phase load break switch RV53, class E3 according to IEC 62271-103, gas insulation • Vacuum circuit breaker with integrated protection relay, current transformers and release • Interlocked earthing switch with rated making capacity up to 63kA • Cable support • Door interlock • Sockets for capacitive voltage detector • Voltage indicators • LV compartment Options • Holder for capacitive voltage indicators • Capacitive voltage indicators • Short-circuit detectors (to be specified by the customer when ordering) • Earthing switch • Set of auxiliary contacts on earthing switch • Key interlock on earthing switch • Earthing ball clamps • Current transformers in the busbar • Voltage transformers with of without protection in the busbar • Plinth: 200mm - 400mm Possible connections: • Bottom in - top out • Bottom in - top left out • Bottom in - top right out Specifications & Dimensions Rated Voltage

kV

12

12*

24

Rated current

A

up to 630

up to 630

up to 630

Short-term current

kA

up to 20

up to 20

up to 20

Time of the short duration of current

s

1

1

1

Width

mm

M

M

M

Depth

mm

950

950

950

Height

mm

1400

1400

1400

kg

55

55

55

Weight (**)

59

Scan the QR code to download the eCatalogues App

AUSTRALIA

New South Wales

Queensland

Sydney 30-34 Day Street North Silverwater NSW 2128 Tel +61 2 9748 3444

Brisbane 16 Riverview Place Murarrie QLD 4172 Tel +61 7 3909 4999

Melbourne 43-67 River Street Richmond VIC 3121 Tel +61 3 9429 2999

Newcastle 575 Maitland Road Mayfield West NSW 2304 Tel +61 2 4960 2220 Fax +61 2 4960 2203

Townsville 5 Leyland Street Garbutt QLD 4814 Tel +61 7 4779 0700 Fax +61 7 4775 1457

Laverton 104-106 William Angliss Drive Laverton North VIC 3026 Tel +61 3 9368 2901

Wollongong 34 Industrial Road Unanderra NSW 2526 Tel +61 2 4272 5763 Fax +61 2 4272 5957

Rockhampton 1 Lawson Street Parkhurst QLD 4702 Tel +61 7 4927 2277 Fax +61 7 4922 2947

nhp.com.au

SALES 1300 NHP NHP FAX 1300 NHP FAX Victoria

Albury / Wodonga 847 Ramsden Drive Albury NSW 2640 Tel +61 2 6049 0600 Fax +61 3 6025 0592 Dandenong 40-42 Cyber Loop Dandenong South VIC 3175 Tel +61 3 8773 6400 Fax +61 3 8768 8522 Tasmania Hobart 29B Lampton Ave Derwent Park TAS 7009 Tel +61 3 6228 9575 Fax +61 3 6228 9757 Launceston Unit 3 13-17 Merino Street Kings Meadows TAS 7249 Tel +61 3 6345 2600 Fax +61 3 6344 6324

ACT Canberra Unit1 187 Gladstone Street Fyshwick ACT 2609 Tel +61 2 6280 9888 Fax +61 2 6280 9588 Western Australia Perth 38 Belmont Ave Rivervale WA 6103 Tel +61 8 9277 1777 Northern Territory Darwin 3 Steele Street Winnellie NT 0820 Tel +61 8 8947 2666 Fax +61 8 8947 2049

NHP Electrical Engineering Products Pty Ltd A.B.N. 84 004 304 812

NMVSWITCHGEARC 0713 © Copyright NHP 2013

Toowoomba Cnr Carroll Street and Struan Court QLD 4350 Tel +61 7 4634 4799 Fax +61 7 4633 1796 Cairns Unit 2 1 Bramp Close Portsmith QLD 4870 Tel +61 7 4035 6888 Fax +61 7 4035 6999 South Australia Adelaide 36-38 Croydon Road Keswick SA 5035 Tel +61 8 8297 9055

NEW ZEALAND nhp-nz.com

SALES 0800 NHP NHP FAX 0800 FAX NHP PO Box 62-009 Sylvia Park Auckland 1644 New Zealand Auckland 118a Carbine Road Mt Wellington 1060 Hamilton 78 Rostrevor Street Hamilton 3204 Napier 126 Taradale Road Onekawa 4110 New Plymouth 2 Dean Place Waiwhakaiho 4312 Wellington 52 Victoria Street Lower Hutt 5010 Christchurch 27 Iversen Terrace Waltham 8011 Dunedin 30 Fox Street South Dunedin 9012