Multilin DGCS Switch Controller

GE Digital Energy Multilin DGCS Switch Controller Instruction Manual Multilin DGCS Switch Controller Firmware Revision: 1.40 GE Publication Code: 16...
Author: Alice Morrison
7 downloads 2 Views 3MB Size
GE Digital Energy

Multilin DGCS Switch Controller

Instruction Manual Multilin DGCS Switch Controller Firmware Revision: 1.40 GE Publication Code: 1601-0260-B5 (GEK-119533D)

*1601-0260-B5*

Copyright © 2015 GE Multilin Inc. All rights reserved. The Multilin DGCS Switch Controller™ Instruction Manual for revision 1.40. Multilin DGCS Switch Controller, EnerVista™, EnerVista Launchpad™, and EnerVista DGCS Setup™ are trademarks or registered trademarks of GE Multilin Inc. The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. This manual is for informational use only and is subject to change without notice. Part number: 1601-0260-B5 (July 2015) FCC/Industry Canada This device complies with Part 15 of the FCC and Industry Canada Rules. Operation is subject to the following two conditions (1) This device may not cause harmful interference, and (2) this device must accept any interference that may cause undesired operation. L’appareil conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisé aux deux conditions suivantes: 1.

L'appareil ne doit pas produire de brouillage

2.

L'utilisateur de l'appareil doit accepter tout brouillage radiolectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.

BATTERY DISPOSAL

EN Battery Disposal This product contains a battery that cannot be disposed of as unsorted municipal waste in the European Union. See the product documentation for specific battery information. The battery is marked with this symbol, which may include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg). For proper recycling return the battery to your supplier or to a designated collection point. For more information see: www.recyclethis.info. CS Nakládání s bateriemi Tento produkt obsahuje baterie, které nemohou být zneškodněny v Evropské unii jako netříděný komunální odpadu. Viz dokumentace k produktu pro informace pro konkrétní baterie. Baterie je označena tímto symbolem, který může zahrnovat i uvedena písmena, kadmium (Cd), olovo (Pb), nebo rtuť (Hg). Pro správnou recyklaci baterií vraťte svémudodavateli nebo na určeném sběrném místě. Pro více informací viz: www.recyclethis.info DA Batteri affald Dette produkt indeholder et batteri som ikke kan bortskaffes sammen med almindeligt husholdningsaffald i Europa. Se produktinformation for specifikke informationer om batteriet. Batteriet er forsynet med indgraveret symboler for hvad batteriet indeholder: kadmium (Cd), bly (Pb) og kviksølv (Hg). Europæiske brugere af elektrisk udstyr skal aflevere kasserede produkter til genbrug eller til leverandøren. Yderligere oplysninger findes på webstedet www.recyclethis.info. DE Entsorgung von Batterien Dieses Produkt beinhaltet eine Batterie, die nicht als unsortierter städtischer Abfall in der europäischen Union entsorgt werden darf. Beachten Sie die spezifischen Batterie-informationen in der Produktdokumentation. Die Batterie ist mit diesem Symbol gekennzeichnet, welches auch Hinweise auf möglicherweise enthaltene Stoffe wie Kadmium (Cd), Blei (Pb) oder Quecksilber (Hektogramm) darstellt. Für die korrekte Wiederverwertung bringen Sie diese Batterie zu Ihrem lokalen Lieferanten zurück oder entsorgen Sie das Produkt an den gekennzeichneten Sammelstellen. Weitere Informationen hierzu finden Sie auf der folgenden Website: www.recyclethis.info. EL Απόρριψη μπαταριών Αυτό το προϊόν περιέχει μια μπαταρία που δεν πρέπει να απορρίπτεται σε δημόσια συστήματα απόρριψης στην Ευρωπαϊκή Κοινότητα. ∆είτε την τεκμηρίωση του προϊόντος για συγκεκριμένες πληροφορίες που αφορούν τη μπαταρία. Η μπαταρία είναι φέρει σήμανση με αυτό το σύμβολο, το οποίο μπορεί να περιλαμβάνει γράμματα για να δηλώσουν το κάδμιο (Cd), τον μόλυβδο (Pb), ή τον υδράργυρο (Hg). Για την κατάλληλη ανακύκλωση επιστρέψτε την μπαταρία στον προμηθευτή σας ή σε καθορισμένο σημείο συλλογής. Για περισσότερες πληροφορίες δείτε: www.recyclethis.info. ES Eliminacion de baterias Este producto contiene una batería que no se pueda eliminar como basura normal sin clasificar en la Unión Europea. Examine la documentación del producto para la información específica de la

batería. La batería se marca con este símbolo, que puede incluir siglas para indicar el cadmio (Cd), el plomo (Pb), o el mercurio (Hg ). Para el reciclaje apropiado, devuelva este producto a su distribuidor ó deshágase de él en los puntos de reciclaje designados. Para mas información: wwwrecyclethis.info. ET Patareide kõrvaldamine Käesolev toode sisaldab patareisid, mida Euroopa Liidus ei tohi kõrvaldada sorteerimata olmejäätmetena. Andmeid patareide kohta vaadake toote dokumentatsioonist. Patareid on märgistatud käesoleva sümboliga, millel võib olla kaadmiumi (Cd), pliid (Pb) või elavhõbedat (Hg) tähistavad tähed. Nõuetekohaseks ringlusse võtmiseks tagastage patarei tarnijale või kindlaksmääratud vastuvõtupunkti. Lisainformatsiooni saab Internetist aadressil: www.recyclethis.info. FI Paristoje ja akkujen hävittäminen Tuote sisältää pariston, jota ei saa hävittää Euroopan Unionin alueella talousjätteen mukana. Tarkista tuoteselosteesta tuotteen tiedot. Paristo on merkitty tällä symbolilla ja saattaa sisältää cadmiumia (Cd), lyijyä (Pb) tai elohopeaa (Hg). Oikean kierrätystavan varmistamiseksi palauta tuote paikalliselle jälleenmyyjälle tai palauta se paristojen keräyspisteeseen. Lisätietoja sivuilla www.recyclethis.info. FR Élimination des piles Ce produit contient une batterie qui ne peuvent être éliminés comme déchets municipaux non triés dans l'Union européenne. Voir la documentation du produit au niveau des renseignements sur la pile. La batterie est marqué de ce symbole, qui comprennent les indications cadmium (Cd), plomb (Pb), ou mercure (Hg). Pour le recyclage, retourner la batterie à votre fournisseur ou à un point de collecte. Pour plus d'informations, voir: www.recyclethis.info. HU Akkumulátor hulladék kezelése Ezen termék akkumulátort tartalmaz, amely az Európai Unión belül csak a kijelölt módon és helyen dobható ki. A terméken illetve a mellékelt ismertetőn olvasható a kadmium (Cd), ólom (Pb) vagy higany (Hg) tartalomra utaló betűjelzés. A hulladék akkumulátor leadható a termék forgalmazójánál új akkumulátor vásárlásakor, vagy a kijelölt elektronikai hulladékudvarokban. További információ a www.recyclethis.info oldalon. IT Smaltimento batterie Questo prodotto contiene una batteria che non può essere smaltita nei comuni contenitori per lo smaltimento rifiuti, nell' Unione Europea. Controllate la documentazione del prodotto per le informazioni specifiche sulla batteria. La batteria è contrassegnata con questo simbolo e può includere alcuni caratteri ad indicare la presenza di cadmio (Cd), piombo (Pb) oppure mercurio (Hg). Per il corretto smaltimento, potete restituirli al vostro fornitore locale, oppure rivolgervi e consegnarli presso i centri di raccolta preposti. Per maggiori informazioni vedere: ww.recyclethis.info.

LT Baterijų šalinimas

RU Утилизация батарей

Šios įrangos sudėtyje yra baterijų, kurias draudžiama šalinti Europos Sąjungos viešose nerūšiuotų atliekų šalinimo sistemose. Informaciją apie baterijas galite rasti įrangos techninėje dokumentacijoje. Baterijos žymimos šiuo simboliu, papildomai gali būti nurodoma kad baterijų sudėtyje yra kadmio (Cd), švino (Pb) ar gyvsidabrio (Hg). Eksploatavimui nebetinkamas baterijas pristatykite į tam skirtas surinkimo vietas arba grąžinkite jas tiesioginiam tiekėjui, kad jos būtų tinkamai utilizuotos. Daugiau informacijos rasite šioje interneto svetainėje: www.recyclethis.info.

Согласно европейской директиве об отходах электрического и электронного оборудования, продукты, содержащие батареи, нельзя утилизировать как обычные отходы на территории ЕС. Более подробную информацию вы найдете в документации к продукту. На этом символе могут присутствовать буквы, которые означают, что батарея собержит кадмий (Cd), свинец (Pb) или ртуть (Hg). Для надлежащей утилизации по окончании срока эксплуатации пользователь должен возвратить батареи локальному поставщику или сдать в специальный пункт приема. Подробности можно найти на веб-сайте: www.recyclethis.info.

LV Bateriju likvidēšana Šis produkts satur bateriju vai akumulatoru, kuru nedrīkst izmest Eiropas Savienībā esošajās sadzīves atkritumu sistēmās. Sk. produkta dokumentācijā, kur ir norādīta konkrēta informācija par bateriju vai akumulatoru. Baterijas vai akumulatora marķējumā ir šis simbols, kas var ietvert burtus, kuri norāda kadmiju (Cd), svinu (Pb) vai dzīvsudrabu (Hg). Pēc ekspluatācijas laika beigām baterijas vai akumulatori jānodod piegādātājam vai specializētā bateriju savākšanas vietā. Sīkāku informāciju var iegūt vietnē: www.recyclethis.info. NL Verwijderen van baterijen Dit product bevat een batterij welke niet kan verwijdert worden via de gemeentelijke huisvuilscheiding in de Europese Gemeenschap. Gelieve de product documentatie te controleren voor specifieke batterij informatie. De batterijen met deze label kunnen volgende indictaies bevatten cadium (Cd), lood (Pb) of kwik (Hg). Voor correcte vorm van kringloop, geef je de producten terug aan jou locale leverancier of geef het af aan een gespecialiseerde verzamelpunt. Meer informatie vindt u op de volgende website: www.recyclethis.info.

SK Zaobchádzanie s batériami Tento produkt obsahuje batériu, s ktorou sa v Európskej únii nesmie nakladať ako s netriedeným komunálnym odpadom. Dokumentácia k produktu obsahuje špecifické informácie o batérii. Batéria je označená týmto symbolom, ktorý môže obsahovať písmená na označenie kadmia (Cd), olova (Pb), alebo ortuti (Hg). Na správnu recykláciu vráťte batériu vášmu lokálnemu dodávateľovi alebo na určené zberné miesto. Pre viac informácii pozrite: www.recyclethis.info. SL Odlaganje baterij Ta izdelek vsebuje baterijo, ki je v Evropski uniji ni dovoljeno odstranjevati kot nesortiran komunalni odpadek. Za posebne informacije o bateriji glejte dokumentacijo izdelka. Baterija je označena s tem simbolom, ki lahko vključuje napise, ki označujejo kadmij (Cd), svinec (Pb) ali živo srebro (Hg). Za ustrezno recikliranje baterijo vrnite dobavitelju ali jo odstranite na določenem zbirališču. Za več informacij obiščite spletno stran: www.recyclethis.info.

NO Retur av batteri

SV Kassering av batteri

Dette produkt inneholder et batteri som ikke kan kastes med usortert kommunalt søppel i den Europeiske Unionen. Se produktdokumentasjonen for spesifikk batteriinformasjon. Batteriet er merket med dette symbolet som kan inkludere symboler for å indikere at kadmium (Cd), bly (Pb), eller kvikksølv (Hg) forekommer. Returner batteriet til leverandøren din eller til et dedikert oppsamlingspunkt for korrekt gjenvinning. For mer informasjon se: www.recyclethis.info.

Denna produkt innehåller ett batteri som inte får kastas i allmänna sophanteringssytem inom den europeiska unionen. Se produktdokumentationen för specifik batteriinformation. Batteriet är märkt med denna symbol, vilket kan innebära att det innehåller kadmium (Cd), bly (Pb) eller kvicksilver (Hg). För korrekt återvinning skall batteriet returneras till leverantören eller till en därför avsedd deponering. För mer information, se: www.recyclethis.info. TR Pil Geri Dönüşümü Bu ürün Avrupa Birliği genel atık sistemlerine atılmaması gereken pil içermektedir. Daha detaylı pil bilgisi için ürünün kataloğunu inceleyiniz. Bu sembolle işaretlenmiş piller Kadmiyum(Cd), Kurşun(Pb) ya da Civa(Hg) içerebilir. Doğru geri dönüşüm için ürünü yerel tedarikçinize geri veriniz ya da özel işaretlenmiş toplama noktlarına atınız. Daha fazla bilgi için: www.recyclethis.info.

PL Pozbywanie się zużytych baterii Ten produkt zawiera baterie, które w Unii Europejskiej mogą być usuwane tylko jako posegregowane odpady komunalne. Dokładne informacje dotyczące użytych baterii znajdują się w dokumentacji produktu. Baterie oznaczone tym symbolem mogą zawierać dodatkowe oznaczenia literowe wskazujące na zawartość kadmu (Cd), ołowiu (Pb) lub rtęci (Hg). Dla zapewnienia właściwej utylizacji, należy zwrócić baterie do dostawcy albo do wyznaczonego punktu zbiórki. Więcej informacji można znaleźć na stronie internetowej www.recyclethis.info. PT Eliminação de Baterias Este produto contêm uma bateria que não pode ser considerado lixo municipal na União Europeia. Consulte a documentação do produto para obter informação específica da bateria. A bateria é identificada por meio de este símbolo, que pode incluir a rotulação para indicar o cádmio (Cd), chumbo (Pb), ou o mercúrio (hg). Para uma reciclagem apropriada envie a bateria para o seu fornecedor ou para um ponto de recolha designado. Para mais informação veja: www.recyclethis.info.

TR Pil Geri Dönüşümü Bu ürün Avrupa Birliği genel atık sistemlerine atılmaması gereken pil içermektedir. Daha detaylı pil bilgisi için ürünün kataloğunu inceleyiniz. Bu sembolle işaretlenmiş piller Kadmiyum(Cd), Kurşun(Pb) ya da Civa(Hg) içerebilir. Doğru geri dönüşüm için ürünü yerel tedarikçinize geri veriniz ya da özel işaretlenmiş toplama noktlarına atınız. Daha fazla bilgi için: www.recyclethis.info.

Global Contacts Worldwide telephone: +1 905 927 7070 Europe, Middle East, Africa telephone: +34 94 485 88 54 North America toll free: 1 800 547 8629

Table of Contents 1. INTRODUCTION

Overview ........................................................................................................................................... 1 - 1 Cautions and Warnings............................................................................................................. 1 - 1 Safety words and definitions ...........................................................................................................1 - 1 General Cautions and Warnings ....................................................................................................1 - 2

For Further Assistance ............................................................................................................... 1 - 3

2. OVERVIEW

Description of the DGCS Controllers.................................................................................... 2 - 1 DGCS Order Codes ....................................................................................................................... 2 - 7 Specifications ................................................................................................................................. 2 - 7 Inputs ..........................................................................................................................................................2 - 7 Outputs.......................................................................................................................................................2 - 8 Configuration...........................................................................................................................................2 - 8 Power supply ........................................................................................................................................ 2 - 10 Fuses......................................................................................................................................................... 2 - 10 Battery ..................................................................................................................................................... 2 - 10 Communications................................................................................................................................. 2 - 10 Testing and Certification ................................................................................................................. 2 - 11 Environmental...................................................................................................................................... 2 - 11

3. INSTALLATION

Mechanical installation.............................................................................................................. 3 - 2 Electrical installation ................................................................................................................... 3 - 4

4. INTERFACES

Front Control Panel Interface.................................................................................................. 4 - 1 Working with the Keypad ..................................................................................................................4 - 3 LED Status Indicators...........................................................................................................................4 - 5

Software Setup .............................................................................................................................. 4 - 6 EnerVista DGCS Setup Software.....................................................................................................4 - 6 Connecting EnerVista DGCS Setup to the Device................................................................ 4 - 10 Working with Settings and Settings Files ................................................................................ 4 - 13 Upgrading DGCS firmware............................................................................................................. 4 - 20 Advanced EnerVista DGCS Setup features............................................................................. 4 - 21

5. ACTUAL VALUES

A1 Status........................................................................................................................................... 5 - 1 Clock ............................................................................................................................................................5 - 1 Contact inputs.........................................................................................................................................5 - 2 Output relays ...........................................................................................................................................5 - 2 Virtual inputs............................................................................................................................................5 - 3 Virtual outputs ........................................................................................................................................5 - 4 Contact inputs summary ...................................................................................................................5 - 4 Output relays summary......................................................................................................................5 - 5 Flexlogic summary................................................................................................................................5 - 5 RTDs .............................................................................................................................................................5 - 5

A2 Metering ..................................................................................................................................... 5 - 5 Current........................................................................................................................................................5 - 6 Voltage .......................................................................................................................................................5 - 7 Sequences.................................................................................................................................................5 - 7 Power ..........................................................................................................................................................5 - 8 Frequency .................................................................................................................................................5 - 9

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

TOC–I

Total Harmonic Distortion (THD)..................................................................................................... 5 - 9 Harmonics ..............................................................................................................................................5 - 10 Energy.......................................................................................................................................................5 - 11

A3 Records .................................................................................................................................... 5 - 12 Event records ........................................................................................................................................5 - 12 Data logger ............................................................................................................................................5 - 13

A4 Messages................................................................................................................................. 5 - 14 Target Messages .................................................................................................................................5 - 14 Self-Test Errors .....................................................................................................................................5 - 15 Flash Messages....................................................................................................................................5 - 15

6. SETTINGS

S1 Product Setup...........................................................................................................................6 - 1 Clock............................................................................................................................................................ 6 - 1 Password security................................................................................................................................. 6 - 3 Communications ................................................................................................................................... 6 - 4 Event recorder ........................................................................................................................................ 6 - 9 Datalogger .............................................................................................................................................6 - 10 Front panel .............................................................................................................................................6 - 11 Installation..............................................................................................................................................6 - 12

S2 System setup ......................................................................................................................... 6 - 12 Current sensing....................................................................................................................................6 - 13 CT corrections.......................................................................................................................................6 - 13 Voltage sensing....................................................................................................................................6 - 14 VT Corrections.......................................................................................................................................6 - 15 Power system........................................................................................................................................6 - 16 Open/Close Setup ...............................................................................................................................6 - 16 Circuit breaker setup .........................................................................................................................6 - 19 Battery backup.....................................................................................................................................6 - 20

S3 Configuration......................................................................................................................... 6 - 27 Phase IOC................................................................................................................................................6 - 27 Phase TOC...............................................................................................................................................6 - 29 Neutral overcurrent ...........................................................................................................................6 - 40 Phase overvoltage..............................................................................................................................6 - 42 Phase undervoltage...........................................................................................................................6 - 44 Voltage unbalance .............................................................................................................................6 - 47 Power loss...............................................................................................................................................6 - 50 Auto sectionalizing .............................................................................................................................6 - 52 Wearing monitor .................................................................................................................................6 - 57

S4 Controls .................................................................................................................................... 6 - 62 Remote control.....................................................................................................................................6 - 62 Open/Close control ............................................................................................................................6 - 63 Change setpoint group.....................................................................................................................6 - 67 Virtual inputs .........................................................................................................................................6 - 69 Cold load pickup ..................................................................................................................................6 - 70 FlexLogic™ .............................................................................................................................................6 - 74

S5 Inputs/Outputs...................................................................................................................... 6 - 78 Contact inputs ......................................................................................................................................6 - 78 Output relays.........................................................................................................................................6 - 79 Virtual inputs .........................................................................................................................................6 - 82

TOC–II

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

7. TROUBLESHOOTING 8. COMMANDS 9. MAINTENANCE

M1 Product information ............................................................................................................ 9 - 1 M2 Product maintenance ......................................................................................................... 9 - 2 M3 Statistics.................................................................................................................................... 9 - 2 Counters ....................................................................................................................................................9 - 3 Reset counters ........................................................................................................................................9 - 3 Preset counters ......................................................................................................................................9 - 3

A. APPENDIX A

Warranty........................................................................................................................................... A - 1 Revision History ............................................................................................................................. A - 1 Change Notes..........................................................................................................................................A - 1 Changes to the DGCS manual.........................................................................................................A - 2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

TOC–III

TOC–IV

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

GE Digital Energy

Multilin DGCS Switch Controller Chapter 1: Introduction

Introduction

Overview The DGCS is a microprocessor-based unit that belongs to the Distribution Grid Controller family, and it is designed as a switch controller. This device is intended to control and monitor different types of medium voltage switches, primarily load and no-load breaking switches (LBS/NLS) used on distribution feeders. Fault-current-breaking units like circuit breakers or reclosers cannot be controlled by the DGCS (DGC switch controller).

Cautions and Warnings Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment damage, or downtime.

Safety words and definitions The following symbols used in this document indicate the following conditions DANGER:

IMPORTANT:

CAUTION:

FASTPATH:

Indicates a hazardous situation which, if not avoided, will result in death or serious injury. Indicates a hazardous situation which, if not avoided, could result in death or serious injury. Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Indicates practices not related to personal injury.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

1–1

CAUTIONS AND WARNINGS

CHAPTER 1: INTRODUCTION

General Cautions and Warnings The following general safety precautions and warnings apply. CAUTION:

Ensure that all connections to the product are correct so as to avoid accidental risk of shock and/or fire, for example such as can arise from high voltage connected to low voltage terminals. Thoroughly and carefully read this instruction sheet and the product manual before programming, operating, or maintaining the DGC Controller. Familiarize yourself with “SAFETY INFORMATION” on this page. The equipment covered by this publication must be installed, operated, and maintained by qualified personal who are knowledgeable in the installation, operation, and maintenance of overhead electric power distribution equipment along with the associated hazards. The user shall be responsible for ensuring the integrity of any Protective conductor connections before carrying out other actions. It is the responsibility of the user to check the equipment ratings and operating Instructions / installation Instructions prior to commissioning, service. Prior to servicing / commissioning ensure the Protective earth (PE) conductor is connected to Earth Ground prior to conducting any work. This product requires an external disconnect to isolate the mains voltage supply. Ensure that the protective earth (PE) terminal is suited with a recommended wire size of 14 awg minimum. The (PE) terminal lug must be fastened with a #8 stud with a required torque of 18-20 in/lb. Prior to commencing work on CTs’ ccts these shall be short circuited. Ensure to contact the remote user prior to approaching the DGCS to conduct local work. Use a lift system with side rails/bucket to reduce a fall hazard as opposed to other means when installing or servicing. Do not disconnect power connectors on the DGCS when the system is on LIVE. Ensure the DGCS outer cabinet is re-locked after local service is completed. This product is rated to Class A emissions levels and is to be used exclusively in Utility or Substation environments. Not to be used near electronic devices rated for Class B levels. Integrating an untested radio into the OEM module may result in functional performance deterioration due to unknown RF immunity effects. At a minimum the Radio must comply with the R&TTE directive and FCC and Industry Canada registered respecting the local RF regulations For Europe and North America. The radios maximum primary rating cannot exceed 13.8 Vdc 12W continuous operation and @2A max transmitting current. The antenna provided must not be replaced with a different type. Attaching a different antenna will void the FCC and IC approval and the FCC /IC ID can no longer be considered.

1–2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 1: INTRODUCTION

FOR FURTHER ASSISTANCE

When Equipped with a Radio rated for North America: For MDS iNETII, radio contains transmitter with FCC ID: E5MDS-INETII/CAN 3738A-INETII.For MDS TransNet, radio contains transmitter with FCC ID: E5MDS-EL805/IC: 3738A 12122.For MDS SD4, radio contains transmitter with FCC ID: E5MDS-SD4/IC: 101D-SD4. CAUTION:

BATTERY: The onboard battery can be replaced only by the same model type. Any other batteries used may not provide the safety nor performance required.

For Further Assistance For product support, contact the information and call center as follows: GE Digital Energy 650 Markland Street Markham, Ontario Canada L6C 0M1 Worldwide telephone: +1 905 927 7070 Europe/Middle East/Africa telephone: +34 94 485 88 54 North America toll-free: 1 800 547 8629 Fax: +1 905 927 5098 Worldwide e-mail: [email protected] Europe e-mail: [email protected] Website: http://www.gedigitalenergy.com/multilin

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

1–3

FOR FURTHER ASSISTANCE

1–4

CHAPTER 1: INTRODUCTION

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

GE Digital Energy

Multilin DGCS Switch Controller Chapter 2: Overview

Overview

Description of the DGCS Controllers The distribution feeders are equipped with feeder DGC Switch Controllers (pole-top, padmount) that are typically installed at the source end of the feeder. Distribution circuits called “laterals” are connected between two consecutive feeder switches. They are protected by over-current fuses and they are not automated. A typical distribution feeder layout is depicted in Figure below.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

2–1

DESCRIPTION OF THE DGCS CONTROLLERS

CHAPTER 2: OVERVIEW

Figure 2-1: Typical distribution feeders layout

The switches are grouped into three main groups: •

Reclosers: These switches are capable of interrupting fault currents. They are similar to breakers.



Load Breaking Switches: These switches are not capable of interrupting fault currents, but can interrupt load currents. They can open only during a normal load condition, or when the circuit breaker in the substation is opened.



No-load switches: These switches are not capable of interrupting neither during fault, nor during normal load conditions. They can only open or close when the circuit breaker in the substation is opened.

As mentioned before, the DGC Switch Controller is intended to control load and no-load breaking switches. The switches are usually located on the trunk of the distribution feeder. The controller is equipped with 6 voltage and 3 current inputs that can be connected to voltage and current transformers respectively, or to any other voltage and current sensors with AC outputs within the specified voltage and current ranges. The controller uses two auxiliary contacts (52a and 52b) to detect open/close switch position, and produce an alarm flag in case of the contacts discrepancy. This is implemented in a hardcoded logic producing output flags that can be used to build user defined logic. The DGCS is equipped with a set of standard function elements available for the user through inputting related setting values. Additional functions that are not part of the standard DGCS element set can be easily configured and implemented using FlexLogic™ functionality. The controller is equipped with MDS radio that securely transmits data to the subscribed distribution automation devices, relays, SCADA, etc. The transmission uses DNP 3.0 protocol. The figure below depicts the section of a distribution feeder, where a DGC Switch Controller is used:

2–2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 2: OVERVIEW

DESCRIPTION OF THE DGCS CONTROLLERS

Figure 2-2: DGCS used as a feeder switch controller

The controller is equipped with the following AC inputs: •

6 PT inputs (Ph-Ph / Ph-N configurations)



3 CT inputs (Phase currents)

The main purpose of the DGC Switch Controller is to provide voltage and power measurements, voltage- and current-based computations, as well as several other digital parameters at the local point. In addition, this information can be transmitted to the remote user. MAIN FUNCTIONS OF THE DGC SWITCH CONTROLLER

The DGCS provides two modes of operation: •

Remote mode



Local mode

The mode can be selected only by using the faceplate pushbutton. When in Remote mode, the DGCS accepts remote commands to operate the switch. When in Local mode, remote commands are blocked and only local commands can be executed. The local commands are available only at the DGCS faceplate (pushbuttons, keypad and LED). The DGCS provides two types of the open/close command execution: •

Manual



Auto

In Manual, the user is directly issuing an open or a close command to the controller. In Auto, the commands are executed by programmable function elements that are running on the controller. Both (open and close) commands are interlocked with various detection functions in order to avoid the switch to be operated at certain current and voltage levels (depending on the switch type). The DGC Switch Controller is capable of measuring three phase voltages and currents from the electric distribution line. Based on the measured quantities, it can perform the following: AC Parameters Level Detections •

Power Loss



Phase Instantaneous Overcurrent



Phase Timed Overcurrent



Neutral Instantaneous Overcurrent



Phase Overvoltage



Phase Undervoltage

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

2–3

DESCRIPTION OF THE DGCS CONTROLLERS



CHAPTER 2: OVERVIEW

Phase Voltage Unbalance

Automatic Logic Functions •

Auto Sectionalizing



CLP (Cold Load Pickup)

AC PARAMETERS LEVEL DETECTIONS

Each level detection function generates a flag that is logged as an event. Power Loss: The controller provides a technique of specifying minimum load current (xCT) threshold and minimum voltage (xVT) threshold. When both quantities are below the threshold (pickup) level, the DGCS will generate a flag representing power loss. Phase Instantaneous Overcurrent:: The controller provides a technique of specifying the instantaneous overcurrent condition for the switch, and generates a flag during overload conditions. The flag may be used to block the opening of the switch, if the overload level is above the switch rating. The flags are generated and reported to the master host via the radio communications. Phase Timed Overcurrent: The controller provides a technique of specifying the timed overcurrent condition for the switch. The user can select different overload curves as a part of the setup procedure for the actual application. During the overload condition the controller generates a flag. The flag may be used to block the opening of the switch, if the overload level is above the switch rating. The flags are generated and reported to the master host via the radio communications. Neutral Instantaneous Overcurrent: The controller provides a technique of specifying the maximum allowed neutral current level above which the controller generates a flag to indicate abnormal ground fault condition. Overvoltage: The controller provides a technique of setting the maximum phase voltage level, above which the controller generates a flag to indicate abnormal overvoltage condition. Phase undervoltage: The controller provides a technique of setting the minimum phase voltage level, below which the controller generates a flag to indicate loss of potential condition. Voltage unbalance and phase loss: The controller provides a technique of setting the maximum negative sequence voltage level, above which the controller generates a flag to indicate voltage unbalance condition. Another (higher) maximum negative sequence voltage level can be set above which a phase loss flag will be generated. AUTOMATIC LOGIC FUNCTIONS

Auto Sectionalizing: The Auto sectionalizing element provides a good mechanism to localize a fault by coordinating this function with the reclosing operations of the feeder breaker within a timing schedule. The logic implemented in this element provides a way to detect several reclosing actions from the main circuit breaker and accordingly open the local switch, in periods when the voltage is absent. The logic uses the information of the overcurrent condition followed by a loss of voltage, loss of current, power flow direction and voltage detection functions to execute the transition into internal states. CLP Cold load pickup: The CLP function is used to avoid fault detections under energizing or inrush conditions. The Cold Load pickup provides two different working ways: Time Block and Multiplier factor. When the CLP is programmed, the energizing process is detected by the transition from a ‘no voltage and no current’ state to a ‘voltage and current present’ condition. Time Block selected: After a CLP condition is detected, the time overcurrent functions are blocked during the period of time programmed in CLP function. Multiplier factor selected: Each Overcurrent element is provided by a setting to indicate the factor at which the pickup threshold of the function shall be increased under inrush conditions. If the current magnitude measured is higher this setting, the element will operate. COMMUNICATION CAPABILITIES

2–4

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 2: OVERVIEW

DESCRIPTION OF THE DGCS CONTROLLERS

The DGC Switch Controller can measure/compute electrical quantities, detect the status of the grid equipment and produce various alarms and events. This information can be sent to the distribution center by means of the Distributed Network Protocol (DNP) communications. In addition, the DGCS can receive different status information and commands through the DNP. MEASUREMENTS

The measurements provided by DGCS are as follows: On the Source side

UNITS

-Ph-N and Ph-Ph Voltages. -Neutral Current -Phase Current -Positive Sequence Voltage -Negative Sequence Voltage -Zero Sequence Voltage -Positive Sequence Current -Negative Sequence Current -Zero Sequence Current -3Ph active Power -3Ph Reactive Power -3Ph Apparent Power -Power Factor -Frequency -THD Currents (up to 8th harmonic) -THD Voltage (up to 8th harmonic)

[V or kV]. (Secondary or primary) [A] [A] [V] [V] [V] [A] [A] [A] [kW] [kVAr] [kVA] [Hz] % %

On the Load side -Ph-N and Ph-Ph Voltages. -Positive Sequence Voltage -Negative Sequence Voltage -Zero Sequence Voltage -THD Voltages (up to 8th harmonic)

[V or kV]. (Secondary or primary)-[V]-[V]-[V]-%

The DGCS calculates the 3ph power based on currents from Wye connected CTs , and either voltage inputs from Wye connected PTs, or Delta connected PTs. In addition, two PTs or either only one PT can be used. The controller has to be configured for different PT connections in order to compute the 3ph power properly. The DGC Switch Controller provides DFT and RMS measurements. The internal metering process is executed at the internal frequency rate of 1 /4 of a full cycle. MONITORING AND CONTROL FUNCTIONS

The DGC Switch Controller is able to monitor the switch state based on auxiliary input 52a /52b provided by the feeder switch. Several external inputs for monitoring possible errors are also mounted on the switch: - Low charge limit switch (LCL) - Spring Charge limit (SCL) - Disconnect Closed & Latched (DCL) - Open visual disconnect contact These inputs can be used to inhibit any possible local and remote closing and opening commands to the feeder switch. The controller is able to monitor other external states as low battery conditions, high and low ambient temperature (if the order code included an RTD input card), etc. Maintenance Elements The maintenance elements provide alarms to the system based on: •

Maximum number of closing/opening executed commands per period of time



I2t measurements per feeder.

Data Logger

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

2–5

DESCRIPTION OF THE DGCS CONTROLLERS

CHAPTER 2: OVERVIEW

The DGCS provides data logger capabilities. The data logger stores the current and voltage measurements of three phases per feeder at every minute (the interval is configurable). It can also store the 3 Ph active and reactive power. A minimum of 72 hours should be stored for statistical features. There are two more buffers containing information over the largest current values reached. •

The largest value per hour is also stored in the ‘peak hourly register’. A minimum of 72 values should be stored for statistical features.



The largest value per 72 hour is also stored in the ‘peak 72 hour register’ buffer.

Event Recorder The DGCS can store up to 1024 consecutive events. Operate and dropout events of fault detection functions can be enabled or disabled by settings. A snapshot of the phase voltage/current and power metering can also be included and stored at each Event. Some of events and alarms include the following: •

Remote mode



Local mode



Remote/Manual Close command



Remote/Manual Open Command



switch opened/ closed / failed



Overload events



Overvoltage events



Loss of voltage events



Loss of current events



High neutral current events



Max number of closing reached.



Battery Low



Communications loss



Internal error

Statistics and Counters

2–6



Max / Min Values of current & voltage per hour.



Max / Min Values of current & voltage per 72 hour.



Daily close/open operation



Total Close/open operation

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 2: OVERVIEW

DGCS ORDER CODES

DGCS Order Codes Figure 2-3: Order Codes

DGC Application

S S

Language Power Supply

1

2

3

4

5

6

E I

L I

S I

S I

A I

* I

* I

E I

* I

X I

* I

* X X X Description I Switch Controller

E

I L

I I

I I

I I

I I

I I

I I

I I

I I

I I

I I

English (Standard) Low (20 to 60 V DC)

S

I S

I I

I I

I I

I I

I I

I I

I I

I I

A

I

I

I

I

I

I

I

B

B

I

I

I

I

I

J

J

I

I

I

I

I

E

E

E

I

I

I

D

I

I

I

G

I

I

I

X

X

I

I

2

I

3

I

RS485 Modbus RTU / DNP3.0 (Standard) Standard Current Input Card (1A/5A) - should be compatible with Lindsey Line current sensors o/p of 1A/5A) Voltage Input Card (110 ~ 300VAC) - should be compatible with Lindsey Line voltage sensors o/p of 120VAC Voltage Sensor Input Card (12V Lindsey Sensor) Two (2) 10 A Form-A relays and six (6) 20 to 60V DC digital Inputs (2xIO_E Standard), Max 3xIO_E) Four (4) 10A form-C relays (Optional, Max 1 IO_D) 3 RTD (Only one used for DGC application (optional, Max 1 IO_G) None Controller + Front Display Panel in an Enclosure for G&W Switch type ORA21-386-20RP Controller + Front Display Panel in an Enclosure for S&C Switch None MDS TransNet (North American customers only) MDS iNet-II (North American customers only) Prewired for future radio with 12 VDC Power Supply installed Prewired for future radio with 24 VDC Power Supply installed

Communication Options I/O

Controller Packaging

Wireless Radio Option

X 1 2 4 5

Specifications

Inputs PHASE CURRENT INPUTS Range: ...................................................................... 0.2 to 40 A (8 x CT) Input Type:.............................................................. Combined 1A/5A Frequency:.............................................................. 50 or 60 Hz Accuracy: ................................................................ ±1.5% of reading or ±1.5% rated current (whichever is greater) Withstand (at 5 A nominal):............................ 0.2 s at 100x 2.0 s at 40x continuous at 3x rated current

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

2–7

SPECIFICATIONS

CHAPTER 2: OVERVIEW

PHASE VOLTAGE INPUTS Input Range:.......................................................... Input Range:.......................................................... Nominal Frequency: .......................................... Accuracy (IO_B card) for Voltage range 60 to 380 V: ...................................................... Accuracy (IO_J card): ........................................

60 to 440 V (IO_B card) 0.5 to 10 V (IO_J card) 50 or 60 Hz ±1% of reading or ±1V (whichever is greater) ±1% of reading or ±0.2V (whichever is greater)

PHASE OC, OV, AND UV TIME DELAYS Range:...................................................................... 0.0 to 600.0 s in steps of 0.1 s Accuracy:................................................................ up to ±0.3%

REVERSE POWER DELAY Range:...................................................................... 0.0 to 3600.0 s in steps of 0.1 s Accuracy:................................................................ up to ±0.2%

CONTACT INPUTS Fixed Pickup: ......................................................... 65 V AC Recognition Time:............................................... 2 cycles Current Draw @ Rated Voltage:................... 75 mA @ 120 V AC for 200 μs each cycle 60 mA @ 240 V AC for 800 μs each cycle Input Impedance: ............................................... 1.7 KOhms Nominal Frequency: .......................................... 50 or 60 Hz Type: ......................................................................... opto-isolated External Switch:................................................... wet contact Maximum Input Voltage:................................. 300 V AC

Outputs OUTPUT RELAYS Configuration: ...................................................... Contact Material: ................................................ Operate Time: ...................................................... Minimum Contact Load:.................................. Continuous Current: .......................................... Make and Carry for 0.2 s:................................ Mechanical Life: ..................................................

electromechanical form A (IO_C) and form C (IO_D) silver alloy 10 ms 10 mA @ 5 V DC 10 A 30 A per ANSI C37.90 10 000 000 operations

FORM C OUTPUT CONTACTS AC Resistive, 120 V AC: ..................................... AC Resistive, 240 V AC: ..................................... AC Inductive, PF = 0.4 pilot duty: ................. DC Resistive, 30 V DC:.......................................

10 A normally open, 5 A normally closed 10 A normally open, 8 A normally closed 2.5 A 10 A

Configuration PHASE INSTANTANEOUS OVERCURRENT Current:.................................................................... Pickup Level: ......................................................... Dropout Level:...................................................... Time Delay:............................................................ Operate Time: ...................................................... Level Accuracy:.................................................... Timing Accuracy:................................................

2–8

Fundamental 0.05 - 8.00 x CT in steps of 0.01 x CT 95 to 98% of Pickup or ±0.02 x CT (whichever is greater) 0.00 to 600.00 s in steps of 0.01 1.5 x Pickup level) ±1% at rated current±3% for current higher than 0.1x CT ±3% of trip time or ±20ms (whichever is greater)

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 2: OVERVIEW

SPECIFICATIONS

PHASE TIMED OVERCURRENT Current:.................................................................... Fundamental Pickup Level:.......................................................... 0.05 to 8.00 x CT in steps of 0.01 x CT Dropout Level: ...................................................... 95 to 98% of Pickup or ±0.02 x CT (whichever is greater) Time Delay: ............................................................ 0.00 to 600.00 s in steps of 0.01 Operate Time:....................................................... 1.5 x Pickup level) Level Accuracy:.................................................... ±1% at rated current±3% for current higher than 0.1x CT Timing Accuracy: ................................................ ±3% of trip time or ±20ms (whichever is greater)

NEUTRAL OVERCURRENT Neutral Current:................................................... Fundamental Pickup Level:.......................................................... 0.05 - 8.00 x CT in steps of 0.01 x CT (phase CT) Dropout Level: ...................................................... 95 to 98% of Pickup or ±0.02 x CT (whichever is greater) Time Delay: ............................................................ 0.00 to 600.00 s in steps of 0.01 Operate Time:....................................................... 1.5 x Pickup level, no time delay) Level Accuracy:.................................................... ±1% at rated current±3% for current higher than 0.1x CT Timing Accuracy: ................................................ +0.25cycle (0 s time delay)±3% of trip time or 0.25cycle whichever is greater (intentional delay)

PHASE OVERVOLTAGE Pickup Level:.......................................................... 0.05 to 1.25 x VT in steps of 0.01 Dropout Level: ...................................................... 95% to 99% of pickup (V > 0.1 x VT)85% to 99% of pickup (V < 0.1 x VT) Time Delay: ............................................................ 0.0 to 600.0 s in steps of 0.1 Operate Time:....................................................... time delay + up to 35 ms.@ 60Hz (V > 1.1 x PKP)time delay + up to 40 ms.@ 50Hz (V > 1.1 x PKP) Level Accuracy:.................................................... per voltage input

PHASE UNDERVOLTAGE Minimum Voltage:............................................... programmable from 0.00 to 1.25 x VT in steps of 0.01 Pickup Level:.......................................................... 0.05 to 1.25 x VT in steps of 0.01 Dropout Level: ...................................................... 101% to 104% of pickup (V > 0.1 x VT)101% to 115% of pickup (V < 0.1 x VT) OperateTime:........................................................ Time Delay ± 30 ms @ 60Hz (V < 0.85 x PKP) Time Delay: ............................................................ ± 40 ms @50Hz (V < 0.85 x PKP) Time Delay Accuracy: ....................................... ±3% of expected inverse time or 1 cycle, whichever is greater Level Accuracy:.................................................... per voltage input

VOLTAGE UNBALANCE Pickup Level:.......................................................... 4 to 40% in steps of 1% Time Delay: ............................................................ 1.00 to 60.00 s in steps of 0.01 s Dropout Level: ...................................................... (pickup – 0.2 to 2 units)% Pickup Accuracy:................................................. ±2% Timing Accuracy: ................................................ ±0.5 s or ± 0.5% of total time

POWER LOSS Operate Time:....................................................... time delay + up to 35 ms @ 60Hz (V > 1.1 x PKPtime delay + up to 40 ms @ 50Hz (V > 1.1 x PKP) Time Delay Accuracy: ....................................... 0 to 1 cycle Level Accuracy:.................................................... per voltage input Voltage:.................................................................... Fundamental Pickup Level:.......................................................... 0.01 to 0.40 x VT in steps of 0.01 Dropout Level: ...................................................... 101% to 104% of pickup (V > 0.1 xVT)101% to 115% of pickup (V < 0.1 xVT) Current:.................................................................... Fundamental Pickup Level:.......................................................... 0.01 to 0.40 x CT in steps of 0.01 x CT Dropout Level: ...................................................... 102 to 105% of Pickup or ±0.02xCT (whichever is greater)

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

2–9

SPECIFICATIONS

CHAPTER 2: OVERVIEW

AUTO SECTIONALIZING IOC Dropout Time Delay: ................................ Trip Count Limit: .................................................. Auto Sectionalizing Delay:.............................. Reverse Power Pickup: ..................................... Reverse Power Delay: ....................................... Auto Sectionalizing Timeout: ........................

0.05 to 5.00 s in steps of 0.01s 1 to 5 in steps of 1 0.1 to 60.0 s in steps of 0.1s 0 to –50000 in steps of 1 kW 0 to 60.0 s in steps of 0.1s 6 to 600 s in steps of 1s

SWITCH WEARING MONITOR Open Counter Limit: .......................................... Close Counter Limit: .......................................... KI2t Maximum Limit: ......................................... KI2t Integral Time:..............................................

0 to 9999 in steps of 1 0 to 9999 in steps of 1 0 to 9999.99 (KA)2s in steps of 0.01 (KA)2s 0.03 to 0.25 s in steps of 0.01 s

Power supply POWER SUPPLY Nominal:.................................................................. 120 to 240 V AC 125 to 250 V DC Range:...................................................................... 60 to 300 V AC (50 and 60 Hz) 84 to 250 V DC Ride Through: ....................................................... 35 ms Overvoltage Withstand: .................................. 2 x highest nominal voltage for 10 ms Power Consumption:......................................... 16 W typical, 45 W maximum

Fuses FUSES USED Internal Voltage Source:.................................. FUSE 3A/250V 1/4" X 1-1/4" CARTRIDGE GE P/N: 0901-0015, COPPER BUSHMANN P/N: AGC-3 Switch Mechanism:............................................ FUSE FAST ACTING 6.3MMX32.0MM 250V 6A GE P/N: 0901-0086, COPPER BUSHMANN P/N: AGC-6-R

Battery BATTERY Manufacturer: ...................................................... Odyssey Manufacturer’s P/N: .......................................... PC310 Description: ........................................................... BATTERY DRY CELL 101X86X138MM 12V 8AH HIGH_TEMP M4_RECEPTACLE

BATTERY BACKUP Voltage: ................................................................... Capacity:................................................................. Charging: ................................................................ Alarms:..................................................................... Battery Test: .......................................................... CAUTION:

24 VDC (two 12 V batteries) 8 hours Constantly connected to a smart charging unit LED and alarm messages Programmable through system setup menu

Replace battery with the same model and type . When replacing ensure the metal cover is reused to harness the batteries. Ensure that the rubber battery terminal covers are reused to prevent accidental short circuits.

Communications COMMUNICATIONS Data Transfer Rate: ........................................... 9600, 19200, 38400, 57600, or 115200 bits per second Communication Protocols:............................. DNP 3, Modbus

2–10

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 2: OVERVIEW

SPECIFICATIONS

Testing and Certification APPROVALS Applicable Council Directive CE compliance

ISO

According to

Low voltage directive

EN60255-5 / EN60255-27

EMC Directive

EN61000-6-2 / 6-4 / 6-5 (AREA G)

Manufactured under a registered quality program

ISO9001

TYPE TESTS Test

Reference Standard

Test Level

Dielectric Voltage Withstand

EN60255-5

2.3KV

Impulse Voltage Withstand

EN60255-5

5KV

Insulation Resistance Test

EN60255-5

500 VDC

Damped Oscillatory

IEC61000-4-18IEC60255-22-1

2.5KV CM, 1KV DM

Electrostatic Discharge

EN61000-4-2/IEC60255-22-2

Level 4

RF Immunity

EN61000-4-3/IEC60255-22-3

Level 3

Fast Transient Disturbance

EN61000-4-4/IEC60255-22-4

Class A and B

Surge Immunity

EN61000-4-5/IEC60255-22-5

Level 3 & 4

Conducted RF Immunity

EN61000-4-6/IEC60255-22-6

Level 3

Radiated & Conducted Emissions

CISPR11 /CISPR22/ IEC60255-25

Class A

Sinusoidal Vibration

IEC60255-21-1

Class 1

Shock & Bump

IEC60255-21-2

Class 1

Siesmic

IEC60255-21-3

Class 2

Power Magnetic Immunity

IEC61000-4-8

Level 5

Voltage Dip & interruption

IEC61000-4-11

0, 40, 70, 80% dips, 250/300 cycle interrupts

Environmental (Cold)

IEC60068-2-1

-20C 16 hrs

Environmental (Cold Storage)

IEC60068-2-1

-40C 16 hrs

Environmental (Dry heat)

IEC60068-2-2

85C 16hrs

Relative Humidity Cyclic

IEC60068-2-30

6day variant 2

RF Immunity

IEEE/ANSIC37.90.2

20V/m 80-1Ghz

Environmental ENVIRONMENTAL SPECIFICATIONS Ambient temperatures: Storage/shipping:

- 40oC to 90oC *

Operating:

-40oC to 60oC *

* Internal temperature cannot exceed 60oC. This product is capable of operating in a maximum ambient of 40oC including solar loading.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

2–11

SPECIFICATIONS

CHAPTER 2: OVERVIEW

ENVIRONMENTAL SPECIFICATIONS

Humidity:

Operating up to 95% (non condensing) @ 55oC (As per IEC60068-2-30 Variant 2, 6days)

Altitude:

2000m (max)

Insulation Category:

I

Overvoltage Category:

II

Ingress Protection:

IP54

Environmental rating:

60oC surrounding air

Pollution Degree:

II Type 1 (panel mount versions only)

2–12

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

GE Digital Energy

Multilin DGCS Switch Controller Chapter 3: Installation

Installation

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

3–1

MECHANICAL INSTALLATION

CHAPTER 3: INSTALLATION

Mechanical installation Figure 3-1: DGCS dimensions LEGEND INCHES [mm]

Option 1 shows the connection available for the S & C switch.

3–2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 3: INSTALLATION

MECHANICAL INSTALLATION

Figure 3-2: Bottom view for S & C switch OPTION 1

Option 2 shows the connections available for the G & W switch. Figure 3-3: Bottom view for G & W switch OPTION 2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

3–3

SOURCE SIDE

C

B

USB

Step-down Transformer

FRONT PORT

RJ45

FACEPLATE

RTD

FUSE 3A

CB CONTROLS

RJ45

CIRCUIT BREAKER

F3

FRONT PORT

RJ45

OPTIONAL

120V, 60Hz

G13 G14

G12

G11

RS232

+

SURGE ARRESTOR

MDS INET II RADIO

COM

-

+

RS232 RS485 CONVERTER

-

RS485

-

+

-

+

L N G

AC INPUT

-

AC/DC Convertor + 24V

DC/DC Convertor

BATTERY BACKUP SYSTEM

IO_E2

POWER SUPPLY GND

+

-

F14

F13

F12

F11

F9 F10

F8

G10

DGC - SWITCH CONTROLLER

G9

G8 (optional)

F5

F4 F6 F7

COM

F1 F2

G6 G7

IO_E1

IO_B (optional) or IO_J (optional)

IO_B or IO_J

IO_A

IO_G

E1 E2 E3 E4 E5 E6 E7 E8

D1 D2 D3 D4 D5 D6 D7 D8

WYE PTs

C1 C2 C3 C4 C5 C6 C7 C8

WYE PTs

FEEDER SWITCH (SW)

G5

G4

G3

G2

G1

WYE CTs

POWER

3–4 POWER

A

891801.cdr

SW 52a contact SW 52b contact

SW input OPEN

SW input CLOSE

SWITCH CONTROLS

LOAD SIDE

ELECTRICAL INSTALLATION CHAPTER 3: INSTALLATION

Electrical installation Figure 3-4: S & C Switch Controller wiring diagram - 3 CT Wye / 3 PTs Wye

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

SOURCE SIDE

C

B

USB

Step-down Transformer

FRONT PORT

RJ45

FACEPLATE

RTD

FUSE 3A

CB CONTROLS

RJ45

CIRCUIT BREAKER

FRONT PORT

RJ45

OPTIONAL

120V, 60Hz

G13 G14

G12

G11

G10

G9

+

RS232

+

SURGE ARRESTOR

MDS INET II RADIO

COM

-

-

RS485

RS232 RS485 CONVERTER

COM

-

+

-

+

-

L N G

AC INPUT

AC/DC Convertor + 24V

DC/DC Convertor

BATTERY BACKUP SYSTEM

IO_E2

DGC - SWITCH CONTROLLER

GND

+

-

POWER SUPPLY

IO_E1

IO_B (optional) or IO_J (optional)

IO_B or IO_J

IO_A

IO_G

E1 E2 E3 E4 E5 E6 E7 E8

OpDelta PTs

D1 D2 D3 D4 D5 D6 D7 D8

OpDelta PTs

FEEDER SWITCH (SW)

C1 C2 C3 C4 C5 C6 C7 C8

G8 (optional)

G6 G7

G5

G4

G3

G2

G1

WYE CTs

POWER

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL POWER

A

F1

F14

F13

F12

F11

F10

F9

F8

F6 F7

F5

F4

F3

F2

891802.cdr

SW 52a contact SW 52b contact

SW input OPEN

SW input CLOSE

SWITCH CONTROLS

LOAD SIDE

CHAPTER 3: INSTALLATION ELECTRICAL INSTALLATION

Figure 3-5: S & C Switch Controller wiring diagram - 3 CT Wye / 3 PTs OpDelta

3–5

SOURCE SIDE

C

B

USB

Step-down Transformer

FRONT PORT

RJ45

FACEPLATE

RTD

FUSE 3A

CB CONTROLS

RJ45

CIRCUIT BREAKER

FRONT PORT

RJ45

OPTIONAL

120V, 60Hz

G13 G14

G12

G11

RS232

+

SURGE ARRESTOR

MDS INET II RADIO

COM

-

+

RS232 RS485 CONVERTER

-

RS485

POWER SUPPLY

-

+

-

+

L N G

AC INPUT

-

AC/DC Convertor + 24V

DC/DC Convertor

BATTERY BACKUP SYSTEM

IO_E2

GND

+

-

F14

F13

F12

F11

F9 F10

G10

F8

G9

G8

DGC - SWITCH CONTROLLER

F6 F7 IO_E1

F4

F3

F2

F1

G6 G7

IO_B (optional) or IO_J (optional)

E1 E2 E3 E4 E5 E6 E7 E8

WYE PTs

F5

COM

IO_B or IO_J

IO_A

IO_G (optional)

D1 D2 D3 D4 D5 D6 D7 D8

C1 C2 C3 C4 C5 C6 C7 C8

WYE PTs

FEEDER SWITCH (SW)

G5

G4

G3

G2

G1

WYE CTs

POWER

3–6 POWER

A

SW 52a contact SW 52b contaFW

input

input

input

input

891804.cdr

SWITCH output LO GAS

SWITCH CLOSE SWITCH CLOSE SWITCH OPEN SWITCH OPEN

SWITCH CONTROLS

LOAD SIDE

ELECTRICAL INSTALLATION CHAPTER 3: INSTALLATION

Figure 3-6: G & W Switch Controller wiring diagram - 3 CT Wye / 3 PTs Wye

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

SOURCE SIDE

C

B

USB

Step-down Transformer

FRONT PORT

RJ45

FACEPLATE

RTD

FUSE 3A

CB CONTROLS

RJ45

CIRCUIT BREAKER

OPTIONAL

FRONT PORT

RJ45

+

RS232

+

SURGE ARRESTOR

MDS INET II RADIO

COM

-

-

RS485

RS232 RS485 CONVERTER

COM

-

+

-

+

-

L N G

AC INPUT

AC/DC Convertor + 24V

DC/DC Convertor

BATTERY BACKUP SYSTEM

IO_E2

DGC - SWITCH CONTROLLER

GND

+

-

POWER SUPPLY

IO_E1

IO_B (optional) or IO_J (optional)

IO_B or IO_J

IO_A

IO_G (optional)

E1 E2 E3 E4 E5 E6 E7 E8

Open Delta PTs

D1 D2 D3 D4 D5 D6 D7 D8

Open Delta PTs

FEEDER SWITCH (SW)

C1 C2 C3 C4 C5 C6 C7 C8

120V, 60Hz

G13 G14

G12

G11

G10

G9

G8

G6 G7

G5

G4

G3

G2

G1

WYE CTs

POWER

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL POWER

A

F14

F13

F12

F11

F10

F9

F8

F6 F7

F5

F4

F3

F2

F1

SW 52a contact SW 52b contact

input

input

input

input

891805.cdr

SWITCH output LO GAS

SWITCH CLOSE SWITCH CLOSE SWITCH OPEN SWITCH OPEN

SWITCH CONTROLS

LOAD SIDE

CHAPTER 3: INSTALLATION ELECTRICAL INSTALLATION

Figure 3-7: S & C Switch Controller wiring diagram - 3 CT Wye / 3 PTs Open Delta

3–7

ELECTRICAL INSTALLATION

3–8

CHAPTER 3: INSTALLATION

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

GE Digital Energy

Multilin DGCS Switch Controller Chapter 4: Interfaces

Interfaces

Front Control Panel Interface The DGC Switch Controller front panel provides easy navigation using full keypad pushbuttons, conveniently located open/close control pushbuttons, quick access to settings, regulation transparency using LED indicators, and a 4 x 20 character Liquid Crystal Display. The front panel includes the following components:

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–1

FRONT CONTROL PANEL INTERFACE

CHAPTER 4: INTERFACES

Figure 4-1: DGCS Front Panel

DGCS STATUS LEDs: Three LEDs indicating the DGCS status: “In-Service”, “Alarm”, and (communications) “Comms OK” are placed in the upper left corner of the DGCS front panel.

4–2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

FRONT CONTROL PANEL INTERFACE

IN SERVICE:

The DGCS is operational and functioning properly when the “In-Service” LED shows green. The LED turns off upon detection of an internal firmware or hardware error. The product is not programmed when shipped, and the “In-Service” LED will not light upon power up. The LED will turn on green upon selecting the “Ready” setting under the S1 INSTALLATION/PRODUCT STATUS menu.

ALARM:

The “Alarm” LED turns orange upon detection of either an internal firmware error, a hardware error, or upon ALARM conditions driven by the control of the configuration elements such as “phase IOC” or “phase TOC”.

COMMS OK:

The communications LED, is a bi-color LED, meaning that it will show green when the transmit/receive channels are set and the DGCS is communicating with another smart device or SCADA. This LED will turn orange if the communication channels – communication card failure, or communication channels - are not working properly.

4 X 20 CHARACTER LCD The DGCS has an LCD with 4 lines of 20 characters, that allows visibility under varied lighting conditions. When the keypad and the display are not being used, system information is displayed after a user-defined period of inactivity. Pressing the keypad when the screen shows the default display returns the display to the last available message before the default screen activated. Any DGCS control actions, as well as element operations, are displayed automatically, overriding any target message displayed at that time. The display and the navigation keypad are conveniently located to provide the user easy access to any settings, actual values, status, monitoring tools, or statistics. NOTE:

NOTE

Pressing any of the Quick Settings pushbuttons, invokes only the settings programmed in the active Settings Group. Accessing and editing of settings from the other Settings Groups can be done using the navigation keypad pushbuttons. SWITCH CONTROLLER CONTROL PANEL The Switch Controller control panel includes the following pushbuttons: Figure 4-2: Switch Controller Control Panel

Working with the Keypad The display messages are organized into a Main Menu, pages, and sub-pages. There are four main menus labeled Actual Values, Quick Setup, Settings, and Maintenance. Pressing the MENU key followed by the MESSAGE key scrolls through the four Main Menu headers, which appear in sequence as follows:

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–3

FRONT CONTROL PANEL INTERFACE

CHAPTER 4: INTERFACES

Figure 4-3: The four Main Menu headers

█ ACTUAL VALUES QUICK SETUP SETPOINTS MAINTENANCE Pressing the MESSAGE ► key or the ENTER key from these Main Menu pages will display the corresponding menu Page. Use the MESSAGE ▲ and MESSAGE ▼ keys to scroll through the Page headers. Figure 4-4: Typical paging operation from Main Menu selection

△ Back



ACTUAL VALUES █ A1 STATUS A2 METERING A3 RECORDS

▶ ▽

1 click

A1 STATUS █ CLOCK CONTACT INPUTS OUTPUT RELAYS Back

▼ ◁

▷ ▼

2 clicks

A1 STATUS CLOCK CONTACT INPUTS █ OUTPUT RELAYS Back





▷ ▼

Click to end

A1 STATUS

.. .

█ ACTIVE GROUP

When the display shows SETTINGS, pressing the MESSAGE ► key or the ENTER key will display the page headers of programmable parameters (referred to as settings in the manual). When the display shows ACTUAL VALUES, pressing the MESSAGE ► key or the ENTER key displays the page headers of measured parameters (referred to as actual values in the manual). Each page is broken down further into logical sub-pages of messages. The MESSAGE ▲ and MESSAGE ▼ keys are used to navigate through the sub-pages. A summary of the settings and actual values pages can be found in the Chapters : Settings and Actual Values, respectively. The ENTER key is dual purpose. It is used to enter the sub-pages and to store altered setting values into memory to complete the change. The MESSAGE ► key can also be used to enter sub-pages but not to store altered settings.

4–4

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

FRONT CONTROL PANEL INTERFACE

The ESCAPE key is also dual purpose. It is used to exit the sub-pages and to cancel a setting change. The MESSAGE ◄ key can also be used to exit sub-pages and to cancel setting changes. The VALUE keys are used to scroll through the possible choices of an enumerated setting. They also decrement and increment numerical settings. The RESET key resets any latched conditions that are not currently active. This includes resetting latched output relays, latched Trip LEDs, breaker operation failure, and trip / close coil failures. The Autoreclose Scheme is also reset with the shot counter being returned to zero and the lockout condition being cleared. The MESSAGE ▲ and MESSAGE ▼ keys scroll through any active conditions in the relay. Diagnostic messages are displayed indicating the state of protection and monitoring elements that are picked up, operating, or latched.

LED Status Indicators The DGC Switch Controller faceplate provides easy navigation through a set of keypad pushbuttons, conveniently located switch control pushbuttons, regulation transparency through LED indicators, and a 4 by 20 character Liquid Crystal Display. The faceplate includes the following LED components: •

IN SERVICE: Green The DGCS is operational and functions properly when the “In Service” LED is lit green. The LED turns off upon detection of an internal firmware or hardware error. The product is not programmed when shipped, and the “In-Service” LED will not light upon power-up. The LED will turn green upon selecting the setting “Ready” under the S1 INSTALLATION > PRODUCT STATUS menu.



ALARM: Orange The “Alarm” LED turns orange upon detection of either an internal firmware error, a hardware error, or upon alarm conditions driven by configuration elements such as “Phase IOC” or “Phase TOC”.



COMMS OK: Green/Orange The communications LED is a bi-color LED; it will light green when the transmit/ receive channels are set and the DGCS is communicating with another smart device or SCADA. The LED will turn red if the communication channels – because of communication card failure or communication channels not working properly – are no longer functioning.



AUTO SECTIONALIZING LOCKOUT: Red The "Auto Sectionalizing Lockout” LED turns red when the Auto Sectionalizing element is in a lockout state.



BLOCK OPEN SWITCH: Orange This LED is not labeled, but it is located next to the “Block Open Switch” pushbutton. It is lit when the OPEN SWITCH command is blocked.



BLOCK CLOSE SWITCH: Orange This LED is not labeled, but it is located next to the “Block Close Switch” pushbutton. It is lit when the CLOSE SWITCH command is blocked.



PHASE OVERCURRENT: Orange The “Phase Overcurrent” LED operation is connected with the Phase Time Overcurrent and Phase Instantaneous Overcurrent elements. The LED is lit when either or both of these elements are operating.



NEUTRAL OVERCURRENT: Orange The “Neutral Overcurrent” LED is lit when the Neutral Overcurrent element is operating.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–5

SOFTWARE SETUP

CHAPTER 4: INTERFACES



OVERVOLTAGE: Orange The “Overvoltage” LED is lit when the Overvoltage element is operating.



UNDERVOLTAGE: Orange The “Undervoltage” LED is lit when the Undervoltage element is operating.



REVERSE POWER: Orange The “Reverse Power” LED is lit when there is a reverse power condition detected in the monitored power grid.



SWITCH OPEN: Green/Red/Orange The “Switch Open” LED is lit when the controlled switch is open. The color of the LED is configurable and can be set to Green, Red or Orange. Factory default is Red.



SWITCH CLOSED: Green/Red/Orange The “Switch Closed” LED is lit when the controlled switch is closed. The color of the LED is configurable and can be set to Green, Red or Orange. Factory default is Green.



SWITCH ALARM: Orange This LED lights up orange when any of the following three events occur: The switch is not detected closed after the expected time, the switch is not detected open after the expected time, or the system cannot determine the state of the switch.



AC POWER LOSS: Orange This LED lights up orange when the system detects a power loss condition on the source side of the switch.



BATTERY ALARM: Orange This LED is lit steadily if the battery fuse is blown or the battery needs to be replaced. It flashes while the battery test is in progress.



AUTO: Green The DGCS is in Auto mode when the “Auto” LED is lit green. The outputs are controlled by automatic functions running on the controller. The LED blinks while the Auto mode is blocked by a remote (SCADA) user.



MANUAL: Green The DGCS is in Manual mode when the “Manual” LED is lit green. The DGCS outputs are controlled by MANUAL commands.



REMOTE: Green The DGCS is in Remote mode when the “Remote” LED is lit green. The DGCS is then being controlled from a remote location.



LOCAL: Red The DGCS is in Local mode when the “Local” LED is lit red. The DGCS can then only be controlled by a user who has access to the faceplate commands.

Software Setup

EnerVista DGCS Setup Software Although settings can be entered manually using the control panel keys, a PC can be used to download settings through the communications port. The software is available from GE Digital Energy to make this as convenient as possible. With running, it is possible to: •

4–6

Program and modify settings

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

SOFTWARE SETUP



Load and save setting files to and from a disk



Read actual values



Monitor status



Read pre-trip data and event records



Get help on any topic



Upgrade the firmware

The software allows immediate access to all features with easy to use pull down menus in the familiar Windows environment. This section provides the necessary information to install , upgrade the relay firmware, and write and edit setting files. The software can run even if the DGCS is not connected to the computer. In this case, settings may be saved to a file for future use. If the DGCS is connected to a PC and communications are enabled, the DGCS can be programmed from the setting screens. In addition, measured values, status and trip messages can be displayed on the actual value screens.

Hardware and Software Requirements

The following requirements must be met for the software. •

Microsoft Windows™ 7 / XP is installed and running properly.



At least 100 MB of hard disk space is available.



At least 256 MB of RAM is available.

The software can be installed from either the GE EnerVista CD or the GE Digital Energy website at http://www.gedigitalenergy.com.

Installing the EnerVista DGCS Setup Software

After ensuring the minimum requirements indicated earlier, use the following procedure to install the EnerVista DGCS Setup software from the enclosed GE EnerVista CD. 1.

Insert the GE EnerVista CD into your CD-ROM drive.

2.

Click the Install Now button and follow the installation instructions to install the nocharge EnerVista software on the local PC.

3.

When installation is complete, start the EnerVista Launchpad application.

4.

Click the IED Setup section of the LaunchPad toolbar.

5.

In the EnerVista Launchpad window, click the Add Product button and select the DGC Recloser Controller as shown below. Select the Web option to ensure the most recent software release, or select CD if you do not have a web connection, then click the Add Now button to list software items for the DGCS.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–7

SOFTWARE SETUP

4–8

CHAPTER 4: INTERFACES

6.

EnerVista Launchpad will obtain the latest installation software from the Web or CD and automatically start the installation process. A status window with a progress bar will be shown during the downloading process.

7.

Select the complete path, including the new directory name, where the EnerVista DGCS Setup software will be installed.

8.

Click on Next to begin the installation. The files will be installed in the directory indicated, the USB driver will be loaded into the computer, and the installation program will automatically create icons and add EnerVista DGCS Setup software to the Windows start menu.

9.

The DGCS device (DA Setup) will be added to the list of installed IEDs in the EnerVista Launchpad window, as shown below.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

SOFTWARE SETUP

If you are going to communicate from your computer to the Relay using the USB port: 10. Plug the USB cable into the USB port on the Relay then into the USB port on your computer. 11. Launch Enervista DA Setup from LaunchPad by double-clicking the DA Setup icon. 12. In EnerVista > Device Setup:

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–9

SOFTWARE SETUP

CHAPTER 4: INTERFACES

13. Select USB as the Interface type. 14. Select DGCS as the USB device.

Connecting EnerVista DGCS Setup to the Device Configuring Serial Communications

4–10

Before starting, verify that the cable is properly connected to either the USB port on the front panel of the device (for USB communications) or to the RS485 terminals on the back of the device (for RS485 communications). This example demonstrates a USB connection. For RS485 communications, the Multilin F485 converter will be required. Refer to the F485 manual for additional details. 1.

Install and start the latest version of the software (available from the GE Digital Energy web site). See the previous section for the installation procedure.

2.

Click on the Device Setup button to open the Device Setup window and click the Add Site button to define a new site.

3.

Enter the desired site name in the "Site Name" field. If desired, a short description of the site can also be entered. In this example, we will use “Substation 1” as the site name.

4.

The new site will appear in the upper-left list in the window.

5.

Click the Add Device button to define the new device.

6.

Enter the desired name in the "Device Name" field and a description (optional) of the device.

7.

Select “Serial” from the Interface drop-down list.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

SOFTWARE SETUP

8.

Click the Read Order Code button to connect to the device and upload the order code.

9.

Click OK when the relay order code has been received. The new device will be added to the Site List window (or Online window) located in the top left corner of the main window. The Site Device has now been configured for USB communications. Proceed to Connecting to the DGCS below, to begin communications.

Using the Quick Connect Feature

The Quick Connect button can be used to establish a fast connection through the front panel USB port of a DGC device. The following window will appear when the QuickConnect button is pressed:

As indicated by the window, the "Quick Connect" feature can quickly connect the software to a front port if a USB is selected in the interface drop-down list. Select a device and press the Connect button. When connected, a new Site called “Quick Connect” will appear in the Site List window.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–11

SOFTWARE SETUP

CHAPTER 4: INTERFACES

The DGC Device has now been configured via the Quick Connect feature for USB communications. Proceed to Connecting to the DGCS, below, to begin communications.

Connecting to the DGCS

4–12

Now that the communications parameters have been properly configured, the user can easily communicate with the device. 1.

Expand the Site list by double clicking on the site name or clicking on the «+» box to list the available devices for the given site.

2.

Desired device trees can be expanded by clicking the «+» box. The following list of headers is shown for each device: Device Definition Actual Values Quick Setup Settings Maintenance.

3.

Expand the SETTINGS > PRODUCT SETUP list item and double click on Front Panel to open the "Front Panel" settings window as shown below:

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

SOFTWARE SETUP

4.

The "Front Panel" settings window will open with a corresponding status indicator on the lower left of the EnerVista DGCS Setup window.

5.

If the status indicator is red, verify that the serial or USB cable is properly connected to the relay, and that the device has been properly configured for communications (steps described earlier). The "Front Panel" settings can now be edited, printed, or changed. Other settings and command windows can be displayed and edited in a similar manner. "Actual Values" windows are also available for display. These windows can be arranged, and resized at will.

Working with Settings and Settings Files Engaging a Device

Entering Settings

The EnerVista DGCS Setup software may be used in on-line mode (relay connected) to directly communicate with a DGC device. Communicating devices are organized and grouped by communication interfaces and into sites. Sites may contain any number of devices selected from the product series. The System Setup page will be used as an example to illustrate the entering of settings. In this example, we will be changing the voltage sensing settings. 1.

Establish communications with the DGC device.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–13

SOFTWARE SETUP

4–14

CHAPTER 4: INTERFACES

2.

Select the Settings > System Setup > Source Side VTs menu item.

3.

Select the Settings > System Setup > Load Side VTs menu item.

4.

Select the Source or Load VT Ratio or Secondary settings by clicking anywhere in the parameter box. This will display three arrows: two to increment/decrement the value and another to launch the numerical keypad.

5.

Clicking the arrow at the end of the box displays a numerical keypad interface that allows the user to enter a value within the setting range displayed near the top of the keypad: Click = to exit from the keypad and keep the new value. Click on X to exit from the keypad and retain the old value.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

File Support

Using Settings Files

SOFTWARE SETUP

6.

For settings requiring non-numerical pre-set values (e.g. Load VT Connection below), clicking anywhere within the Load VT parameter box displays a drop-down selection menu arrow. Select the desired value from this list.

7.

For settings requiring an alphanumeric text string (e.g. "product name"), the value may be entered directly within the settings Parameter box.

8.

In the above Settings > System Setup > Load Side VTs dialog box, click on Save to save the values into the relay. Click YES to accept any changes and exit the window. Click Restore to retain previous values. Click Default to restore Default values.

Opening any file will automatically launch the application or provide focus to the already opened application. If the file is a settings file (has a ‘DGC’ extension) which had been removed from the Settings List tree menu, it will be added back to the Settings List tree. New files will be automatically added to the tree. The software interface supports three ways of handling changes to DGCS settings: •

In off-line mode (DGC disconnected) to create or edit DGC settings files for later download to communicating DGC devices.



Directly modifying DGC settings while connected to a communicating DGC device, then saving the settings when complete.



Creating/editing settings files while connected to a communicating DGC device, then saving them to the device when complete.

Settings files are organized on the basis of file names assigned by the user. A settings file contains data pertaining to the following types of DGC settings: •

Device Definition



DGC Setup



System Setup



Control



Inputs/Outputs

Factory default values are supplied and can be restored after any changes. The displays DGC settings with the same hierarchy as the front panel display.

Downloading and Saving Settings Files

Settings must be saved to a file on the local PC before performing any firmware upgrades. Saving settings is also highly recommended before making any settings changes or creating new settings files. The settings files in the window are accessed in the Files Window. Use the following procedure to download and save settings files to a local PC. 1.

Ensure that the site and corresponding device(s) have been properly defined and configured as shown in Connecting to the DGCS, above.

2.

Select the desired device from the site list.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–15

SOFTWARE SETUP

Adding Settings Files to the Environment

Creating a New Settings File

4–16

CHAPTER 4: INTERFACES

3.

Select the Online > Read Device Settings from Device menu item, or right-click on the device and select Read Device Settings to obtain settings information from the device.

4.

After a few seconds of data retrieval, the software will request the name and destination path of the settings file. The corresponding file extension will be automatically assigned. Press Receive to complete the process. A new entry will be added to the tree, in the File pane, showing path and file name for the setting file.

The software provides the capability to review and manage a large group of settings files. Use the following procedure to add an existing file to the list. 1.

In the files pane, right-click on Files and select the Add Existing Setting File item as shown:

2.

The Open dialog box will appear, prompting the user to select a previously saved settings file. As for any other MS Windows® application, browse for the file to be added then click Open. The new file and complete path will be added to the file list.

The software allows the user to create new settings files independent of a connected device. These can be uploaded to a device at a later date. The following procedure illustrates how to create new settings files.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

Upgrading Settings Files to a New Revision

SOFTWARE SETUP

1.

In the File pane, right click on File and select the New Settings File item. The following box will appear, allowing for the configuration of the settings file for the correct firmware version. It is important to define the correct firmware version to ensure that settings not available in a particular version are not downloaded into the device.

2.

Select the Firmware Version, and Order Code options for the new settings file.

3.

For future reference, enter some useful information in the Description box to facilitate the identification of the device and the purpose of the file.

4.

To select a file name and path for the new file, click the button beside the File Name box.

5.

Select the file name and path to store the file, or select any displayed file name to replace an existing file. All settings files should have the extension ‘DGC’ (for example, ‘feeder1.DGC’).

6.

Click OK to complete the process. Once this step is completed, the new file, with a complete path, will be added to the EnerVista DGCS Setup software environment.

It is often necessary to upgrade the revision for a previously saved settings file after the firmware has been upgraded. This is illustrated in the following procedure: 1.

Establish communications with the relay.

2.

Select the Maintenance > M1 Relay Info menu item and record the Firmware Revision.

3.

Load the settings file to be upgraded into the EnerVista DGCS Setup environment as described in the section, Adding Settings Files to the Environment.

4.

In the File pane, select the saved settings file.

5.

From the main window menu bar, select the Offline > Edit Settings File Properties menu item and note the File Version of the settings file. If this version is different from the Firmware Revision noted in step 2, select a New File Version that matches the Firmware Revision from the pull-down menu.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–17

SOFTWARE SETUP

CHAPTER 4: INTERFACES

6.

Printing Settings and Actual Values

4–18

For example, if the firmware revision is 1.20) and the current settings file revision is 1.10, change the settings file revision to “1.2x”.

7.

Enter any special comments about the settings file in the "Description" field.

8.

Select the desired firmware version from the "New File Version" field.

9.

When complete, click OK to convert the settings file to the desired revision. See Loading Settings from a File below, for instructions on loading this settings file into the DGCS device.

The EnerVista DGCS Setup software allows the user to print partial or complete lists of settings and Actual Values. Use the following procedure to print a list of settings: 1.

Select a previously saved settings file in the File pane or establish communications with a device.

2.

From the main window, select the Offline > Export Settings File menu item.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

Printing Actual Values from a Connected Device

SOFTWARE SETUP

3.

The Print/Export Options dialog box will appear. Select Settings in the upper section and select either Include All Features (for a complete list) or Include Only Enabled Features (for a list of only those features which are currently used) in the filtering section and click OK.

4.

The process for Offline > Print Preview Settings File is identical to the steps above.

5.

Settings lists can be printed in the same manner by right clicking on the desired file (in the file list) or device (in the device list) and selecting the Print Device Information or Print Settings File options.

A complete list of actual values can also be printed from a connected device with the following procedure: 1.

Establish communications with the desired device.

2.

From the main window, select the Online > Print Device Information menu item

3.

The Print/Export Options dialog box will appear. Select Actual Values in the upper section and select either Include All Features (for a complete list) or Include Only Enabled Features (for a list of only those features which are currently used) in the filtering section and click OK. Actual Values lists can be printed in the same manner by right clicking on the desired device (in the device list) and selecting the Print Device Information option.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–19

SOFTWARE SETUP

CHAPTER 4: INTERFACES

Loading Settings from a File The following procedure illustrates how to load settings from a file. Before loading a settings file, it must first be added to the environment as described in the section, Adding Settings Files to the Environment.

FASTPATH:

1.

Select the previously saved settings file from the File pane of the EnerVista DGCS Setup software main window.

2.

Select the Offline > Edit Settings File Properties menu item and verify that the corresponding file is fully compatible with the hardware and firmware version of the target device. If the versions are not identical, see Upgrading Settings Files to a New Revision for details on changing the settings file version.

3.

Right-click on the selected file and select the Write Settings File to Device item.

4.

Select the target device from the list of devices shown and click Send. If there is an incompatibility, an "Incompatible device..." error message will be shown. An error message will occur when attempting to download a settings file with a revision number that does not match the relay firmware. If the firmware has been upgraded since saving the settings file, see for instructions on changing the revision number of a settings file. If there are no incompatibilities between the target device and the settings file, the data will be transferred to the device. An indication of the percentage completed will be shown in the bottom of the main window.

Upgrading DGCS firmware To upgrade the DGCS firmware, follow the procedures listed in this section. Upon successful completion of this procedure, the device will have new firmware installed with the factory default settings.The latest firmware files are available from the GE Digital Energy website at http://www.digitalenergy.com. EnerVista DGCS Setup software prevents incompatible firmware from being loaded into a DGC device.

NOTE:

NOTE

Before upgrading firmware, it is very important to save the current DGCS settings to a file on your PC. After the firmware has been upgraded, it will be necessary to load this file back into the device. Refer to Downloading and Saving Settings Files for details on saving settings to a file.

FASTPATH:

Loading new DGC firmware

Loading new firmware into the flash memory is accomplished as follows: 1.

Connect the device to the local PC and save the settings to a file as shown in Downloading and Saving Settings Files.

2.

Select the Maintenance > Update Firmware menu item.

3.

The software will request the new firmware file. Locate the folder that contains the firmware files to load into the relay. The firmware filename has the following format:

MJ M03 M A 100 . 000 Modification Number (000 = none) Firmware Rev # Board Assembly Rev # Code Type in Memory Device PCB Code Number Product Reference Code (MJ = DGC)

4–20

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

SOFTWARE SETUP

4.

EnerVista DGCS Setup software now prepares the to receive the new firmware file. The front panel will momentarily display "DGC BOOT PROGRAM Waiting for Message,” indicating that it is in upload mode.

5.

While the file is being loaded into the device, a status box appears showing how much of the new firmware file has been transferred, and the upgrade status. The entire transfer process takes approximately 10 minutes.

6.

The software will notify the user when the EnerVista DGCS Setup program has finished loading the file. Carefully read any displayed messages and click OK to return the main screen. Cycling power to the relay is recommended after a firmware upgrade. After successfully updating the firmware, the device will not be in service and will require settings programming. To communicate with the relay, the communication settings may have to be manually reprogrammed. When communications are established, the saved settings must be reloaded back into the device. See Loading Settings from a File for details. Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (i.e. default values, min/max values, data type, and item size) may change slightly from version to version of the firmware. Addresses are rearranged when new features are added or existing features are enhanced or modified.

Advanced EnerVista DGCS Setup features Event records

The EnerVista DGCS Setup software can be used to capture events from the device at the instance of a pickup, trip, alarm, or other condition. •

With EnerVista DGCS Setup software running and communications established, select the Actual Values > A3 Records > Event Records menu item to open the Event Records Viewer window.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–21

SOFTWARE SETUP

CHAPTER 4: INTERFACES



Data logger

The data logger feature is used to sample and record up to ten actual values at a selectable interval. The datalogger can be run with Continuous mode Enabled, which will continuously record samples until stopped by the user; or with Continuous mode Disabled, which will trigger the datalog once without overwriting previous data. Viewing and saving of the Datalogger is performed as follows: 1.

4–22

Click on the Save Events button to save the selected events to the local PC.

With running and communications established, select the A3 Records > Data Logger menu item to open the datalog setup window:

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

SOFTWARE SETUP

2.

If Continuous mode is enabled, click on Stop to stop the datalog

3.

Click on the Save to File button to save the datalog to the local PC. A new window will appear requesting for file name and path.

4.

One file is saved as a COMTRADE file, with the extension ‘CFG’. The other file is a DAT file, required by the COMTRADE file for proper display of data.

5.

To view a previously saved COMTRADE file, click the Open button and select the corresponding COMTRADE file.

6.

To view the datalog, click the Launch Viewer button. A detailed Datalog window will appear as shown below.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–23

SOFTWARE SETUP

CHAPTER 4: INTERFACES

TRIGGER TIME & DATE Display the time & date of the Trigger

Display graph values at the corresponding cursor line. Cursor lines are identified by their colors.

7.

Password security

FILE NAME Indicates the file name and complete path (if saved)

CURSOR LINE POSITION Indicate the cursor line position in time with respect to the trigger time DELTA Indicates time difference between the two cursor lines

CURSOR LINES To move lines locate the mouse pointer over the cursor line then click and drag the cursor to the new location.

TRIGGER LINE Indicates the point in time for the trigger

The datalog can be set to capture another buffer by clicking on Run (when Continuous mode is enabled), or by clicking on Release (when Continuous mode is disabled).

Password security is an optional feature of the DGCS which can be setup using the EnerVista DGCS Setup software. The password system has been designed to facilitate a hierarchy for centralized management. This is accomplished through a Master level access password which can be used for resetting lower level access passwords and higher level privileged operations. In cases where operational security is required as well as a central administrative authority then the use of the password system is highly encouraged. The feature robustness of this system requires it to be managed exclusively through the EnerVista setup software. This section describes how to perform the initial setup. For more details on the password security feature, refer to Chapter 6 - Password Security. 1.

4–24

VECTOR DISPLAY SELECT Click here to open a new graph to display vectors

DGCS devices shipped from the factory are initially set with security disabled. If the password security feature is to be used, the user must first change the Master Reset Password from the initial Null setting. This can be done only over communications, not from the front panel keypad. The new Master Reset Password must be 8 to 10

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 4: INTERFACES

SOFTWARE SETUP

characters in length, and must have minimum 2 letters and 2 numbers. The letters are case sensitive. After entering a valid Master Reset Password, enter the new Master Reset Password again to confirm, then select Change Password.

2.

Now that the Master Reset Password has been programmed, enter it again to log in to the Master Access level. The Master Level permits setup of the Remote and Local Passwords. If the Master Reset Password has been lost, record the Encrypted Key and contact the factory to have it decrypted.

3.

With Master Level access, the user may disable password security altogether, or change the Master Reset Password.

4.

The Master Access level allows programming of the Remote Settings and Remote Control passwords. These passwords are initially set to a Null value, and can only be set or changed from a remote user over RS485 communications. Remote Passwords must be 3 to 10 characters in length.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

4–25

SOFTWARE SETUP

4–26

CHAPTER 4: INTERFACES

5.

Initial setup of the Local Settings and Local Control passwords requires the Master Access level. If Overwrite Local Passwords is set to YES, Local passwords can be changed remotely only (over RS485). If Overwrite Local Passwords is set to NO, Local Passwords can be changed locally only (over USB or keypad). If changing Local Passwords is permitted locally, the keypad user can only change the Local Passwords if they have been changed from the initial NULL value to a valid one. Local Passwords must be 3 to 10 characters in length.

6.

If any Remote Password has never been set, that level will not be attainable except when logged in as the Master Level. The same logic applies to the Local Passwords.

7.

When passwords have been set, the user will be prompted to enter the appropriate password depending on the interface being used (remote or local), and the nature of the change being made (settings or control). If the correct password is entered, the user is now logged into that access level over that interface only. The access level turns off after a period of 5 minutes of inactivity, if control power is cycled, or if the user enters an incorrect password.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

GE Digital Energy

Multilin DGCS Switch Controller Chapter 5: Actual values

Actual values

A1 Status The main Status Menu is shown below:

Clock

PATH: ACTUAL VALUES > A1 STATUS > CLOCK CURRENT DATE Feb 12 2009 Range: Date in format shown Indicates today’s date.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

5–1

A1 STATUS

CHAPTER 5: ACTUAL VALUES

CURRENT TIME 09:17:12 Range: Time in format shown Indicates the current time of day.

Contact inputs

PATH: ACTUAL VALUES > A1 STATUS > CONTACT INPUTS CONTACT INPUT 1 to 12 OFF Range: Off, On Message displays the state of the contact input. The message “ON” indicates that the contact input is energized, and message “OFF” indicates a de-energized contact.

Output relays

PATH: ACTUAL VALUES > A1 STATUS > OUTPUT RELAYS RLY 1 SW OPEN (Output Relay #1) OFF Range: Off, On The “ON” state of Output Relay #1 (OPEN) shows that an OPEN command has been sent to the breaker. RLY 2 SW CLOSE (Output Relay #2) OFF Range: Off, On The “ON” state of Output Relay #2 (CLOSE) shows that a close command has been sent to the breaker. OUTPUT RELAY 3 to X (Auxiliary Output Relays) OFF Range: Off, On

5–2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 5: ACTUAL VALUES

A1 STATUS

Virtual inputs

The state of all active virtual inputs is displayed here. PATH: ACTUAL VALUES > A1 STATUS > VIRTUAL INPUTS VIRTUAL INPUTS 1 to 32 OFF Range: Off, On

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

5–3

A1 STATUS

CHAPTER 5: ACTUAL VALUES

Virtual outputs

The state of all active virtual outputs is displayed here. PATH: ACTUAL VALUES > A1 STATUS > VIRTUAL OUTPUTS VIRTUAL OUTPUTS 1 to 32 OFF Range: Off, On

Contact inputs summary PATH: ACTUAL VALUES > A1 STATUS > C. INPUTS SUMMARY CI#1

OFF

CI#7

OFF

CI#2

OFF

CI#8

OFF

CI#3

OFF

CI#9

OFF

CI#4

OFF

CI#10

OFF

CI#5

OFF

CI#11

OFF

CI#6

OFF

CI#12

OFF

The display shows a summary of the states of all contact inputs.

5–4

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 5: ACTUAL VALUES

A2 METERING

Output relays summary PATH: ACTUAL VALUES > A1 STATUS > OUT RELAYS SUMMARY RLY#1

OFF

RLY#5

OFF

RLY#2

OFF

RLY#6

OFF

RLY#3

OFF

RLY#7

OFF

RLY#4

OFF

RLY#8

OFF

This display shows a summary of the states of all output relays. Output Relays #1 and #2 are the Open and Close relays respectively.

NOTE:

NOTE

Flexlogic summary

PATH: ACTUAL VALUES > A1 STATUS > FLEXLOGIC SUMMARY FLEXLOGIC STATUS FLEX LINES USED

RTDs PATH: ACTUAL VALUES > A1 STATUS > RTDs RTDs This status display is available only if an optional IO_G card is used.

NOTE:

NOTE

A2 Metering Line currents and line voltages are filtered values used for the control algorithm. The integration is based on an IIR filter over the last 10 measurements. For abrupt changes in metering, higher than twice of the pickup value, a quick update over these registers are made. Displayed metered quantities are updated approximately three (3) times a second for readability. The DGC Switch Controller measures and computes the following electrical quantities: Source Side AC inputs configuration

Load Side AC inputs configuration

Voltage Inputs: 3Φ V

Current Inputs: 3Φ I Voltage Inputs: 3Φ V

Wye VTs: Ph-n and ph-ph voltages (V)

Ph A, B, C currents (A)

Delta VTs: ph-ph voltages (V)

Neutral current (A)

Wye VTs: Ph-n and ph-ph voltages (V) Delta VTs: ph-ph voltages (V)

Frequency

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

5–5

A2 METERING

CHAPTER 5: ACTUAL VALUES

Source Side AC inputs configuration

Load Side AC inputs configuration

Negative sequence voltage Negative sequence (V) current (A) Positive sequence voltage (V)

Positive sequence current (A)

Zero sequence voltage (V)

Zero sequence current (A)

Voltage 2nd to 8th harmonic (%)

Current 2nd to 8th harmonic (%)

Voltage THD (%)

Current THD (%)

3Φ Real power (kVA) 3Φ Reactive power (kVAr) 3Φ Apparent power (kVA) Power factor (lag or lead) 3Φ Positive real energy (kWh) 3Φ Negative real energy (kWh) 3Φ Positive reactive energy (kVAr*h) 3Φ Negative reactive energy (kVAr*h)

By scrolling the Up/Down keys, the unit shows one-by-one, all metered values as follows:

Current

PH A CURRENT 0.0 A 0° lag Range: 0.0 to 100000.0 A, 0 to 359° lag PH B CURRENT 0.0 A 0° lag Range: 0.0 to 100000.0 A, 0 to 359° lag PH C CURRENT 0.0 A 0° lag Range: 0.0 to 100000.0 A, 0 to 359° lag

5–6

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 5: ACTUAL VALUES

A2 METERING

NTRL CURRENT 0.0 A 0° lag Range: 0.0 to 100000.0 A, 0 to 359° lag

Voltage

PH A VOLTAGE 0.0 V 0° lag Range: 0.0 to 700000.0 V PH B VOLTAGE 0.0 V 0° lag Range: 0.0 to 700000.0 V PH C VOLTAGE 0.0 V 0° lag Range: 0.0 to 700000.0 V

Sequences

POS. SEQ. CURRENT 0.0 A 0° lag Range: 0.0 to 100000.0 A, 0 to 359° lag NEG. SEQ. CURRENT 0.0 A 0° lag Range: 0.0 to 100000.0 A, 0 to 359° lag ZERO SEQ. CURRENT 0.0 A 0° lag Range: 0.0 to 100000.0 A, 0 to 359° lag

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

5–7

A2 METERING

CHAPTER 5: ACTUAL VALUES

POS. SEQ. VOLTAGE 0.0 V 0° lag Range: 0.0 to 700000.0 V NEG. SEQ. VOLTAGE 0.0 V 0° lag Range: 0.0 to 700000.0 V ZERO SEQ. VOLTAGE 0.0 V 0° lag Range: 0.0 to 700000.0 V

Power

3-PH ACTIVE POWER 0.0 kW Range: -50000.0 to 50000.0 kW 3-PH REACTIVE POWER 0.0 kVAR Range: -50000.0 to 50000.0 kVAR 3-PH APPARENT POWER 0.0 kVA Range: -50000.0 to 50000.0 kVA POWER FACTOR 0.00 Range: -0.99 to 1.00

Power calculation

5–8

The DGCS is calculating real, reactive and apparent power (labeled P, Q and S respectively) using measured currents and voltages on the source side of the recloser. When VTs are connected in Wye, the following formulae are used:

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 5: ACTUAL VALUES

A2 METERING

When VTs are connected in Open Delta, the following formulae are used:

Frequency

FREQUENCY 0.00 Hz Range: 40.00 to 70.00 Hz

Total Harmonic Distortion (THD)

THD CURRENTS THD PH A CURRENT 0.0% Range: 0.20% to 100% THD PH B CURRENT 0.0% Range: 0.20% to 100% THD PH C CURRENT 0.0% Range: 0.20% to 100% THD VOLTAGES THD PH A VOLTAGE 0.0% Range: 0.20% to 100% THD PH B VOLTAGE 0.0% Range: 0.20% to 100% THD PH C VOLTAGE 0.0% Range: 0.20% to 100%

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

5–9

A2 METERING

CHAPTER 5: ACTUAL VALUES

Harmonics

CURRENTS 2nd HARM PH A CRNT 0.00% Range: 0.20 to 100.00% 2nd HARM PH B CRNT 0.00% Range: 0.20 to 100.00% 2nd HARM PH C CRNT 0.00% Range: 0.20 to 100.00% . .

5–10

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 5: ACTUAL VALUES

A2 METERING

8th HARM PH A CRNT 0.00% Range: 0.20 to 100.00% 8th HARM PH B CRNT 0.00% Range: 0.20 to 100.00% 8th HARM PH C CRNT 0.00% Range: 0.20 to 100.00% VOLTAGES 2nd HARM PH A VOLT 0.00% Range: 0.20 to 100.00% 2nd HARM PH B VOLT 0.00% Range: 0.20 to 100.00% 2nd HARM PH C VOLT 0.00% Range: 0.20 to 100.00% . . 8th HARM PH A VOLT 0.00% Range: 0.20 to 100.00% 8th HARM PH B VOLT 0.00% Range: 0.20 to 100.00% 8th HARM PH C VOLT 0.00% Range: 0.20 to 100.00%

Energy

3-PH POSITIVE REAL ENERGY 0.0 kWh Range: 0 to 999999.999 kWh 3-PH NEGATIVE REAL ENERGY 0.0 kWh Range: 0 to 999999.999 kWh 3-PH POSITIVE REACTIVE ENERGY 0.0 kVAr*h Range: 0 to 999999.999 kVAr*h

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

5–11

A3 RECORDS

CHAPTER 5: ACTUAL VALUES

3-PH NEGATIVE REACTIVE ENERGY 0.0 kVAr*h Range: 0 to 999999.999 kVAr*h

A3 Records

Event records Event Records include events generated by operation of the following functions: •

Control functions



Open and Close commands



Alarms, Blocks



Change of inputs.

The events are stored in memory, which can store up to 256 events. Each event is stored with an event number, date, time, and analog data of interest.

The following list shows the analog data viewable for each recorded event:

5–12

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 5: ACTUAL VALUES

A3 RECORDS

Phase A Current Phase B Current Phase C Current Neutral Current Van Voltage Source (Wye,Va,Vb,Vc VT input)* Vbn Voltage Source (Wye,Va,Vb,Vc VT input)* Vcn Voltage Source (Wye,Va,Vb,Vc VT input)* Vab Voltage Source (Delta,Vab,Vbc,Vca VT input)* Vbc Voltage Source (Delta,Vab,Vbc,Vca VT input)* Vca Voltage Source (Delta,Vab,Vbc,Vca VT input)* Van Voltage Load (Wye,Va,Vb,Vc VT input)* Vbn Voltage Load (Wye,Va,Vb,Vc VT input)* Vcn Voltage Load (Wye,Va,Vb,Vc VT input)* Vab Voltage Load (Delta,Vab,Vbc,Vca VT input)* Vbc Voltage Load (Delta,Vab,Vbc,Vca VT input)* Vca Voltage Load (Delta,Vab,Vbc,Vca VT input)* Voltage Unbalance Power Factor 3Ph Real Power 3Ph Reactive Power 3Ph Apparent Power Frequency THD Current Phase A THD Current Phase B THD Current Phase C THD Voltage Phase A THD Voltage Phase B THD Voltage Phase C *Dependent on VT Input selection.

Data logger

The data logger is used to sample and record actual values at a selectable time interval. The stored actual values are chosen according to the user’s criteria. For a list of available settings, refer to Chapter 5: Settings / S1 Product Setup / Data Logger.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

5–13

A4 MESSAGES

CHAPTER 5: ACTUAL VALUES

A4 Messages

Target Messages

Target messages are automatically displayed for any active condition on the relay such as pickups, trips, or alarms. The relay displays the most recent event first, and after 5 seconds will start rolling up the other target messages until the conditions clear and/or the RESET command is initiated. The Target Messages can be reviewed by pressing either the MESSAGE UP or MESSAGE DOWN key. If a RESET command is not performed but any of the other faceplate pushbuttons is pressed, the display will not show the target messages unless the user navigates to ACTUAL VALUES > A4 TARGET MESSAGES, where they can be reviewed. If the target messages have not been cleared before the user presses a pushbutton different from “RESET”, they will reappear on the screen after the time specified under the SETPOINTS > S1 PRODUCT SETUP > FRONT PANEL > MESSAGE TIMEOUT setting, that will start timing out from the last pressed pushbutton. The following shows the format of a typical Target Message: Figure 5-1: Typical target message

A4 TARGET MESSAGES Cause State: Operate ▼ Phase: Example of a Phase IOC1 operation - phase A: Phase IOC1 function: Trip

A4 TARGET MESSAGES Ph IOC1 Trip State: Operate ▼ Phase:A Cause The first line contains information of the cause of operation (the name of the operated element), and the element function. State: Operate This line from the display shows the state of the element: Pickup, Operated, Alarm.

5–14

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 5: ACTUAL VALUES

A4 MESSAGES

Phase: A The last line from the display shows the phase that picked up or operated.

Self-Test Errors The relay performs self diagnostics at initialization (after power up), and continuously as a background task to ensure that the hardware and software are functioning correctly. There are two types of self-test warnings indicating either a minor or major problem. Minor problems indicate a problem with the relay that does not compromise protection of the power system. Major errors indicate a problem with the relay which takes it out of service. CAUTION:

Self-Test Warnings may indicate a serious problem with the relay hardware! Upon detection of a minor problem, the relay will: •

Display the error on the relay display.



Record the minor self-test error in the Event Recorder.

Upon detection of a major problem, the relay will: •

De-energize auxiliary relays programmed for “Failsafe” operation.



Inhibit operation of all other output relays.



Turn off the "IN SERVICE" LED.



Flash the "ALARM" LED.



Display the cause of major self-test failure.



Record the major self-test failure in the Event Recorder.

Figure 5-2: Typical Self-test warning

A4 TARGET MESSAGES UNIT FAILURE: Contact Factory: Error code:1

Flash Messages Flash messages are warning, error, or general information messages displayed in response to pressing certain keys. The factory default flash message time is 4 seconds. Figure 5-3: Typical Flash message

SETPOINT STORED This flash message is displayed in response to the ENTER key while on any setpoint message (see example above). The edited value was stored as entered. COMMAND EXECUTED This flash message is displayed in response to executing a command: ON, OFF, YES, NO, etc.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

5–15

A4 MESSAGES

CHAPTER 5: ACTUAL VALUES

INVALID PASSWORD This flash message appears upon an attempt to enter an incorrect password, as part of password security. AR IN PROGRESS This flash message appears when the Autoreclosure is in progress performing the configured sequence.

5–16

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

GE Digital Energy

Multilin DGCS Switch Controller Chapter 6: Settings

Settings

S1 Product Setup The main Product Setup menu is shown below:

Clock The DGCS has an internal real time clock that performs time stamping for various features such as the event and transient recorders. Time synchronization priority uses Modbus or DNP commands as follows: Synchronization commands are all eventually translated into a MODBUS function, and as such are blocked from the MODBUS layer as required. There is no prioritization amongst synchronization commands. A synchronization command issued from DNP for example, can be directly followed by another from MODBUS, for example.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–1

S1 PRODUCT SETUP

CHAPTER 6: SETTINGS

PATH: SETTINGS > S1 PRODUCT SETUP > CLOCK SETUP DATE: (MM/DD/YYYY) Range: Month: Jan, Feb, Mar, Apr, May, Jun, Jul, Aug, Sep, Oct, Nov, Dec Day: 1 to 31 Year: 2009 to 2099 Default: Jan 15 2009 This setting sets the date in the specified format. TIME: (HH:MM:SS) Range: 0 to 23: 0 to 59: 0 to59 Default: 03:15:50 This setting sets the time in the specified format. DLS ENABLE Range: Disabled, Enabled Default: Disabled With DLS Enabled, the main CPU has to maintain the information regarding AV.m_DaylightSavingsActive, because it is necessary in the communications CPU to translate from local time to UTC in 61850 protocol. In addition, if SNTP is enabled, the main CPU will receive UTC time from the communications CPU and it needs to apply this in order to pass it to local time. Without any other synchronization, DLS correction is applied only at 0200 hours on daylight saving months. PATH: SETTINGS > S1 PRODUCT SETUP > CLOCK > DAYLIGHT SAVINGS [ENABLED] DLS START MONTH: Range: Not Set, January, February, March, April, May, June, July, August, September, October, November, December Default: Not Set This setting sets the month for the DLS start time. DLS START WEEK: Range: Not Set, 1st, 2nd, 3rd, 4th, Last Default: Not Set This setting sets the week of the month for the DLS start time.

6–2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S1 PRODUCT SETUP

DLS START WEEKDAY: Range: Not Set, Mon, Tue, Wed, Thu, Fri, Sat, Sun Default: Not Set This setting sets the weekday for the DLS start time. DLS END MONTH: Range: Not Set, January, February, March, April, May, June, July, August, September, October, November, December Default: Not Set This setting sets the month for the end of the DLS time. DLS END WEEK: Range: Not Set, 1st, 2nd, 3rd, 4th, Last Default: Not Set This setting sets the week of the month for the end of the DLS time. DLS END WEEKDAY: Range: Not Set, Mon, Tue, Wed, Thu, Fri, Sat, Sun Default: Not Set This setting sets the weekday for the end of the DLS time.

Password security Password security features are designed into the relay to provide protection against unauthorized setting changes and control. The relay has programmable passwords for both Local and Remote access, which can be used to allow settings changes and command execution from both the front panel and the communications ports. These passwords consist of 3 to 10 alphanumeric characters. The Local and the Remote passwords are initially set after entering in a Master Reset Password (MRP). The Master Reset Password (MRP) is set to “NULL” when the relay is shipped from the factory. When the MRP is programmed to “NULL” all password security is disabled.. The remote user may choose to allow the local user to change the local passwords. Each interface (RS485, USB, and front panel keypad) is independent of one another, meaning that enabling settings access on one interface does not enable access for any of the other interfaces (i.e., the password must be explicitly entered via the interface from which access is desired). The EnerVista DGCS Setup software incorporates a facility for programming the relay’s passwords as well as enabling/disabling settings access. For example, when an attempt is made to modify a settings but access is restricted, the program will prompt the user to enter the password and send it to the relay before the settings can actually be written to the relay. If a SCADA system is used for relay programming, it is up to the programmer to incorporate appropriate security for the application. Aside from being logged out of security, which allows the user to read settings and actual values only, three levels of security access are provided: settings Level, Control Level, and Master Level. The settings and Control Levels can be attained either locally using the Local passwords (USB port and keypad), or remotely using the Remote passwords (RS485 port). The user can have either settings or Control Level active, but not both simultaneously from the same interface. The Master Level is used for setting and resetting of passwords, and includes all settings and Control Level access rights. The Master Level cannot be attained from the keypad. The Master Reset Password must be 8 to 10 characters in length, and must contain at least 2 letters and 2 numbers. The Master Level can define whether the local user is permitted to change Local Passwords without having to enter the Master Level. The Master Reset Password is encrypted, and is not viewable from the keypad. If the Master Reset Password is lost, the user should contact the factory to decrypt the Master Reset Password.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–3

S1 PRODUCT SETUP

CHAPTER 6: SETTINGS

After password entry, the access level is maintained until a period of 5 minutes of inactivity has elapsed, after which the password must be re-entered. A power-loss or entering in the wrong password will log the user out of security. Further definition of the access levels is described as follows: SETTINGS LEVEL •

Changing settings under QUICK SETUP menu



Changing settings under the SETTINGS menu except the features requiring control access listed below



Changing any setting under MAINTENANCE such as trip and close coil monitoring and breaker maintenance settings, except the features requiring control access listed below



Changing the Local or Remote settings Password, depending on the interface being accessed

CONTROL LEVEL •

Reset command



Open and Close Breaker commands



Virtual Input commands



Clearing of event records, transient records, and other data



Uploading new firmware



Changing the Local or Remote Control Password, depending on the interface being accessed

MASTER LEVEL •

Setting and changing of all passwords including the Master Reset Password



Disabling password security



All settings and Control Level access rights

For details on Password Security setup and handling using the EnerVista DGCS Setup software, refer to Chapter 3.

Communications

RS485 interface

6–4

The DGCS is equipped with one serial RS485 communication port. The RS485 port has settings for baud rate and parity. It is important that these parameters agree with the settings used on the computer or other equipment that is connected to these ports. This port may be connected to a computer running the EnerVista DGCS Setup software. This software can download and upload setting files, view measured parameters, and upgrade the device firmware. A maximum of 32 -series devices can be daisy-chained and connected to a DCS, PLC, or PC using the RS485 port. Select the Settings > Communications > Serial Ports menu item in the program, or the SETTINGS > S1 PRODUCT SETUP > COMMUNICATIONS > RS485 path on the display, to configure the serial port.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S1 PRODUCT SETUP

The following settings are available to configure the RS485 port. BAUD RATE Range: 9600, 19200, 38400, 57600, 115200 Default: 115200 This setting specifies the baud rate (bits per second) for the RS485 port. PARITY Range: None, Odd, Even Default: None This setting specifies the parity for the RS485 port.

Modbus

The Modicon Modbus protocol is supported by the DGCS. Modbus is available via the RS485 serial link (Modbus RTU). The DGCS always acts as a slave device, meaning that it never initiates communications; it only listens and responds to requests issued by a master device. A subset of the Modbus protocol format is supported that allows extensive monitoring, programming, and control functions using read and write register commands. Refer to the DGCS Communications Guide for additional details on the Modbus protocol and the Modbus memory map. The Modbus server can simultaneously support two clients over serial RS485. The server is capable of reporting any indication or measurement and operating any output present in the device. A user-configurable input and output map is also implemented. The DGCS operates as a Modbus slave device only Select the Settings > Communications > Modbus > Protocol menu item in software, or the SETTINGS > S1 PRODUCT SETUP > COMMUNICATIONS > MODBUS path to set up the modbus protocol as shown below.

The following Modbus settings are available: MODBUS SLAVE ADDRESS Range: 1 to 254 in steps of 1 Default: 254 This setting specifies the Modbus slave address . Each device must have a unique address from 1 to 254. Address 0 is the broadcast address to which all Modbus slave devices listen. Addresses do not have to be sequential, but no two devices can have the same address or conflicts resulting in errors will occur. Generally, each device added to the link should use the next higher address starting at 1. Please refer to the DGCS Communications Guide for details on how to set up the Modbus communications protocol.

DNP communication

The menu structure for the DNP (distributed network protocol) is shown below. PATH: SETTINGS > S1 PRODUCT SETUP > COMMUNICATIONS > DNP Figure 6-1: DNP communication settings menu

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–5

S1 PRODUCT SETUP

CHAPTER 6: SETTINGS

Figure 6-2: DNP general settings menu

Figure 6-3: DNP default variation settings menu

Figure 6-4: DNP points list menus

6–6

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

S1 PRODUCT SETUP

6–7

S1 PRODUCT SETUP

CHAPTER 6: SETTINGS

Please refer to the DGCS Communications Guide for more details on communications.

6–8

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S1 PRODUCT SETUP

Event recorder The Event Recorder runs continuously, capturing and storing the last 50 events. All events are stored in non-volatile memory on power-down, where the information is maintained for up to 3 days in case of lost DGCS control power. NOTE:

NOTE

The relay requires a minimum time of 15 seconds from power-on in order to be able to save the 50 events on power-down. If power is lost before the first 15 seconds have elapsed, the controller will not be able to save the events.

PATH: SETTINGS > S1 PRODUCT SETUP > EVENT RECORDER PICKUP EVENTS Range: Disabled, Enabled Default: Disabled When set to “Enabled”, the event recorder records the events that occur when a monitoring element picks up. DROPOUT EVENTS Range: Disabled, Enabled Default: Disabled When set to “Enabled” the event recorder records the dropout state of a monitoring element. TRIP EVENTS Range: Disabled, Enabled Default: Enabled When set to “Enabled”, the event recorder records trip events. ALARM EVENTS Range: Disabled, Enabled Default: Enabled These events include the elements programmed as an “ALARM” or “LATCHED ALARM” function. CONTROL EVENTS Range: Disabled, Enabled Default: Enabled If set to “Enabled”, the event recorder records events caused by the performance of the programmed control elements. CONTACT INPUTS Range: Disabled, Enabled Default: Enabled When set to “Enabled”, the event recorder will record the event when a contact input changes its state.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–9

S1 PRODUCT SETUP

CHAPTER 6: SETTINGS

VIRTUAL INPUTS Range: Disabled, Enabled Default: Enabled When set to “Enabled”, the event recorder records the events which occur upon state changes of any virtual input. VIRTUAL OUTPUTS Range: Disabled, Enabled Default: Enabled When set to “Enabled”, the event recorder records the events which occur upon state changes of any virtual outputs. SETTING DATE/TIME Range: Disabled, Enabled Default: Enabled When set to “Enabled”, the event recorder records the events which occur upon changes to Date/Time.

Datalogger

PATH: SETTINGS > S1 PRODUCT SETUP > DATA LOGGER The following settings are available: SAMPLE RATE Range: 1 min, 5 min, 10 min, 15 min, 30 min, 60 min, Disable Default: 1 min Determines how often data is stored in the data log. CONTINUOUS MODE Range: Disabled, Enabled Default: Disabled Determines whether or not the trigger data is overwritten with new data. Enabled will overwrite the previous trigger data with new trigger data. When Disabled, the data log will run until filled with 256 samples. Continuous Mode should be used when the data is stored externally by a polling system. The sample rate should be chosen to match the poll rate of the external program. TRIGGER POSITION Range: 0 to 100% steps of 1% Default: 25% Percentage of the sample buffer used for pretrigger samples.

6–10

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S1 PRODUCT SETUP

DATA LOG TRGR SRC Range: Command, VO1 to VO32, Any Trip Pickup, Any Trip, Any Trip Dropout, Any Alarm Pickup, Any Alarm, Any Alarm Dropout Default: Command Selects a trigger source. Command is always active. Logic Elements can be used to create combinations of trigger sources. CHANNEL 1 Disabled, Ph A Current, Ph B Current, Ph C Current, System Frequency, Power Factor, 3ph Real Power, 3ph Reactive Power, 3ph Apperent Power, External Temp, THD Curr PhA, THD Curr PhB, THD Curr PhC, 2nd….8th Harm Curr PhA, 2nd….8th Harm Curr PhB, 2nd….8th Harm Curr PhC, THD Volt PhA, THD Volt PhB, THD Volt PhC, THD Volt PhA, THD Volt PhB, THD Volt PhC, 2nd….8th Harm Volt PhA, 2nd….8th Harm Volt PhB, 2nd….8th Harm Volt PhC, THD Line Volt, THD Line Curr, 2nd….8th Harm Curr, 2nd….8th Harm Volt, (Van, Vbn, Vcn, Vab, Vbc, Vca - Source and Load), Positive Seq Curr, Negative Seq Curr, Zero Seq Curr, Positive Seq Volt, Negative Seq Volt, Zero Seq Volt, Open Count, Close Count, AS Trip Cnt, KI2t Cnt PhaseA, KI2t Cnt PhaseB, KI2t Cnt PhaseC Refer to DGCS Communications guide for the complete list of analog variables available for data logger channel selection.

NOTE:

NOTE

Default: Disabled Sources and Defaults for Channels 2 to 10 are the same as those for Channel 1.

NOTE:

NOTE

Front panel The user can send a message to the display, that will override any normal message by sending text through Modbus.

PATH: SETTINGS > S1 PRODUCT SETUP > FRONT PANEL FLASH MESSAGE TIME Range: 1 s to 65535 s Default: 5 s Flash messages are status, warning, error, or information messages displayed for several seconds in response to certain key presses during setting programming. These messages override any normal messages. The duration of a flash message on the display can be changed to accommodate different reading rates. MESSAGE TIMEOUT Range: 1 s to 65535 s Default: 30 s If the keypad is inactive for a period of time, the relay automatically reverts to a default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough during programming or reading of actual values.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–11

S2 SYSTEM SETUP

CHAPTER 6: SETTINGS

SCREEN SAVER Range: Off, 1 min to 10000 min Default: Off The life of the LCD backlight can be prolonged by enabling the Screen Saver mode. If the keypad is inactive for the selected period of time, the DGCS automatically shuts off the LCD screen. Any activity (keypress, alarm, trip, or target message) will restore screen messages. LED OPEN COLOR Range: Red, Green, Orange Default: Red This setting defines the color of the LED “SWITCH OPEN”. LED CLOSE COLOR Range: Red, Green, Orange Default: Green This setting defines the color of the LED “SWITCH CLOSED”.

Installation

PATH: SETTINGS > S1 PRODUCT SETUP > INSTALLATION PRODUCT NAME Range: Name, Alpha-numeric (20 characters) Default: DA Name The PRODUCT NAME setting allows the user to uniquely identify a DGCS unit. This name will appear on generated reports. This name is also used to identify specific devices which are engaged in automatically sending/receiving data over the communications channel. PRODUCT STATUS Range: Not Ready, Ready Default: Not Ready Allows the user to activate/deactivate the DGCS. The DGCS is not operational when set to "Not Ready."

S2 System setup One three-phase current input and two three-phase voltage inputs are available on the DGCS for connection to the external measuring transformers. These are programmable through the Current and Voltage Sensing menus. During normal loading conditions the three-phase currents and voltages are well balanced. The controller uses currents and voltages measured on the source side of the switch to compute the electrical power (apparent, active, and reactive). The table in the main ACTUAL VALUES/A2 METERING section shows all electrical quantities measured and calculated by the controller. The DGCS displays the electrical quantities shown in the ACTUAL VALUES/A2 METERING subsections, for the Source and Load sides separately.

6–12

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S2 SYSTEM SETUP

Current sensing

PATH: SETTINGS > S2 SYSTEM SETUP > CURRENT SENSING PHASE CT PRIMARY Range: 1 to 6000 A in steps of 1 A Default: 1 A This setting defines the rated primary current of the connected current transformer. PHASE CT SECONDARY Range: 1 A, 5 A Default: 5 A This setting defines the rated secondary current of the connected current transformer.

CT corrections

PATH: SETTINGS > S2 SYSTEM SETUP > CT CORRECTIONS CT 1/2/3 MAGNITUDE Range: 0.700 to 1.120 in steps of 0.001 Default: 1.000 This setting specifies the correction magnitude for the measurement taken from CT 1/2/ 3 input. The magnitude correction factor equals: Calculated CT 1/2/3 Current = CT 1/2/3 Magnitude x Measured CT 1/2/3 Voltage PCT 1/2/3 PHASE SHIFT Range: 0.0 to 359.9 in steps of 0.1º Default: 0.0º Lag This setting provides the leading phase shift correction that should be applied to the phasor calculations to compensate the angle error provided by the CT.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–13

S2 SYSTEM SETUP

CHAPTER 6: SETTINGS

Voltage sensing

Available settings depend on the IO card selection. PATH: SETTINGS > S2 SYSTEM SETUP > SOURCE SIDE VTs SOURCE VT INPUTS Range: Wye, Delta Default: Wye This setting defines the type of VT connection wired to the source side terminals of the controller (labeled ‘D’). SOURCE VT RATIO Range: 1:1 to 1:10000 in steps of 1 Default: 1:1 This setting specifies the voltage sensing ratio between the primary and the secondary voltage transformer sides. It applies to the source side VT terminals of the controller (labeled ‘D’). SRC VT SECONDARY Range (IO_B card): 60.0 to 440.0 V in steps of 0.1 V Default: 120.0 V Range (IO_J card): 0.5 to 10.0 V in steps of 0.1 V Default: 10.0 V This setting specifies the nominal voltage of the secondary of the voltage transformer connected to the source side VT terminals of the controller (labeled ‘D’).

PATH: SETTINGS > S2 SYSTEM SETUP > LOAD SIDE VTs LOAD VT INPUTS Range: Wye, Delta Default: Wye This setting defines the type of VT connection wired to the source side terminals of the controller (labeled ‘E’). LOAD VT RATIO Range: 1:1 to 1:10000 in steps of 1 Default: 1:1 This setting specifies the voltage sensing ratio between the primary and the secondary voltage transformer sides. It applies to the source side VT terminals of the controller (labeled ‘E’).

6–14

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S2 SYSTEM SETUP

LOAD VT SECONDARY Range (IO-B card): 60.0 to 440.0 V in steps of 0.1 V Default: 120.0 V Range (IO-J card): 0.5 to 10.0 V in steps of 0.1 V Default: 10.0 V This setting specifies the nominal voltage of the secondary of the voltage transformer connected to the source side VT terminals of the controller (labeled ‘E’).

VT Corrections

PATH: SETPOINTS > S2 SYSTEM SETUP > VT CORRECTIONS > SRC VOLTAGES VT1/2/3 MAGNITUDE Range: 0.500 to 1.500 in steps of 0.001 Default: 1.000 The DGC uses magnitude and phase correction factors to correct for manufacturing tolerances in the line-sensing equipment.This setting specifies the correction magnitude that must be applied for the measurement taken from VT1/2/3 input. The magnitude correction factor equals: Calculated VT1/2/3 Voltage = VT1/2/3 Magnitude x Measured VT1/2/3 Voltage VT1/2/3 PHASE SHIFT Range: 0.0 to 359.9 in steps of 0.1º Default: 0.0º Lag This setting provides the leading phase shift correction that should be applied to the phasor calculations to compensate the angle error provided by the VT sensor.

PATH: SETPOINTS > S2 SYSTEM SETUP > VT CORRECTIONS > LOAD VOLTAGES

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–15

S2 SYSTEM SETUP

CHAPTER 6: SETTINGS

VT1/2/3 MAGNITUDE Range: 0.500 to 1.500 in steps of 0.001 Default: 1.000 The DGC uses magnitude and phase correction factors to correct for manufacturing tolerances in the line-sensing equipment.This setting specifies the correction magnitude that must be applied for the measurement taken from VT1/2/3 input. The magnitude correction factor equals: Calculated VT1/2/3 Voltage = VT1/2/3 Magnitude x Measured VT1/2/3 Voltage VT1/2/3 PHASE SHIFT Range: 0.0 to 359.9 in steps of 0.1º Default: 0.0º Lag This setting provides the leading phase shift correction that should be applied to the phasor calculations to compensate the angle error provided by the VT sensor. These settings are also available for the conventional load and source side VTs.

Power system

PATH: SETPOINTS > S2 SYSTEM SETUP > POWER SYSTEM NOMINAL FREQUENCY Range: 50 Hz, 60 Hz Default: 60 Hz This setting defines the frequency of the power system. SYSTEM ROTATION Range: ABC, ACB Default: ABC This setting defines the phase rotation of the power system.

Open/Close Setup The recloser Control feature has a programmable menu where the user can set the criteria for open and close commands to the installed load or no load break recloser. DGCS has one dedicated output relay for the “Open” command and another one for the “Close” command. Depending on ordered controller, the DGCS may have a number of other auxiliary output relays that can be programmed to close/open logic as well. The logic diagrams below show how the open and close commands are individually generated. recloser control outputs will energize when the respective close/open request is generated, unless any blocking condition exists. De-energizing of the outputs is controlled by the state of the recloser as monitored by its 52a and/or 52b contact and delayed by a settable period of time. Details are shown in the table below, “recloser Auxiliary Contacts and recloser Operation”.

6–16

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S2 SYSTEM SETUP

Table 6-1: recloser Auxiliary Contacts and recloser Operation 52a Contact Configured

52b Contact Configured

recloser Operation

Yes

Yes

The Open output relay remains operating until both the 52a and the 52b recloser contacts read open and close respectively. These aux. contacts state define opened recloser. The Close output relay remains operating until both the 52a, and the 52b contacts read close and open respectively. These aux. contacts state define closed recloser.

Yes

No

The Open output relay remains operating until 52a contact changes its state from closed to open. This indicates open recloser. The Close output relay remains operating until 52a contact changes its state from open to close. This indicates closed recloser.

No

Yes

The Open output relay remains operating until 52b contact changes its state from open to closed. This indicates open recloser. The Close output relay remains operating until 52b contact changes its state from closed to open. This indicates closed recloser.

No

No

The recloser state is not monitored.

If the controller fails to detect the recloser operational state, an alarm will be generated. Details about the alarm function are shown in the table below, “recloser monitoring logic with both 52a and 52b contacts configured”. Table 6-2: recloser Monitoring logic with both 52a and 52b contacts configured Auxiliary Contact 52a

Auxiliary Contact 52b recloser Position

Alarm

On

Off

CLOSED

No

Off

On

OPEN

No

Off

Off

recloser State Failed After Time Delay until acknowledged

On

On

The duration of the output energized state depends on different conditions but it is limited to the adjustable time. More details are available in the recloser Control logic diagram below. MODES OF OPERATION Remote/Local Mode The REMOTE/LOCAL pushbutton toggles between REMOTE and LOCAL mode of operation. Each of the two modes is associated with a LED to show the selection. This selection has absolute priority and it can be made only by operating the REMOTE/LOCAL pushbutton. Automatic, Manual, or OFF Mode The AUTO/OFF/MANUAL pushbutton toggles between either AUTO, OFF, or MANUAL mode of operation. The Auto and Manual modes are associated with a corresponding LED, which turns on upon mode selection. When OFF position is selected, both LEDs are off. The controller mode can be selected from the faceplate pushbuttons or from the remote location. SCADA user has a read only access at all times, regardless of the mode selected. However, issuing commands and selecting AUTO/OFF/MANUAL modes via SCADA is restricted and it depends on the selection as shown in the “Controller Modes” tables below.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–17

S2 SYSTEM SETUP

CHAPTER 6: SETTINGS

Table 6-3: Controller Modes Pushbutton

Auto

Manual

Remote Control Enabled

- Automatic Operation enabled - SCADA Remote Open/ Close recloser control and Auto override enabled - Remote Inputs Open/Close recloser control and Auto override enabled - Manual (faceplate) pushbutton Open/Close recloser control disabled

- Automatic Operation disabled - SCADA Remote Open/Close recloser control enabled - Remote Inputs Open/Close recloser control enabled - Manual (faceplate) pushbutton Open/Close recloser control disabled

Local Control Enabled

- Automatic Operation enabled - SCADA Remote Open/ Close recloser control disabled - Remote Inputs Open/Close recloser control disabled - Manual (faceplate) pushbutton Open/Close recloser control disabled

- Automatic Operation disabled - SCADA Remote Open/Close recloser control disabled - Remote Inputs Open/Close recloser control disabled - Manual (faceplate) pushbutton Open/Close recloser control enabled

In Manual mode, the DGCS controls the recloser by responding to manually performed commands from the faceplate pushbuttons OPEN and CLOSE. In Automatic mode, the decision to send a Recloser Open command will made by Control elements, if it is enabled. In both modes the DGCS controller sends either Open or Close command to the recloser using two digital outputs: RLY 1 RCR OPEN and RLY 2 RCR CLOSE. With Remote mode selected when in AUTO mode, the recloser can be also controlled by either the OPEN/CLOSE commands sent via communications, or via asserting inputs configured in the Remote Inputs menu: REMOTE OPEN CMND and REMOTE CLOSE CMND. The remote control overrides the automatic control. After the remote regulation is performed, the controller will revert back to automatic mode. Block Auto mode from Communications (COMM BLOCK AUTO) The Auto mode can be blocked remotely by asserting the command COMM BLOCK AUTO via communications. This can be done only by using the EnerVista DGCS Setup program while in Remote control. In this case the recloser can be controlled only remotely. This command is not visible on the HMI. Save Block Auto from Communications (SAVE COMM BLK AUTO) While in Remote mode, the user can select to keep the Auto mode blocked during loss of communication or loss of power to the DGCS, by setting the command SAVE COMM BLK AUTO, to “Enabled”. This will keep the Auto mode blocked after the communication or the power to the DGCS has been restored. Unblock Auto mode from Communications (COMM UNBLOCK AUTO) Both the COMM BLOCK AUTO and the SAVE COMM BLK AUTO selections will reset upon issuing COMM UNBLOCK AUTO command. This command is not visible on the HMI. The recloser setup settings for DGCS are as follows:

PATH: SETTINGS > S2 SYSTEM SETUP > OPEN/CLOSE SETUP

6–18

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S2 SYSTEM SETUP

****RECLOSER TYPE Range: Load, No Load Default: Load This setting selects the type of recloser. If the recloser is designed to interrupt the load current, the selection should be ‘Load’. If the recloser is designed to open only when there is no load, the selection should be ‘No Load’. When the recloser type has been designated as Load, the recloser rated current and recloser voltage level is used to block the opening and closing commands. See SW RATED CURRENT and SW RATED VOLTAGE for more information. SW RATED CURRENT and SW RATED VOLTAGE Setting will not be used when recloser type is selected as ‘No Load’.

NOTE:

NOTE

****SW RATED CURRENT Range: 0.00 to 5000.00 A Default: 600.00 A This setting defines the recloser rated current. Select the rated current level above which the opening command to the recloser will be blocked. ****SW RATED VOLTAGE Range: 0.00 to 50.00 kV Default: 15.00 Kv This setting defines the recloser rated voltage. Select the rated voltage level above which the closing or the opening command to the recloser will be blocked. 52a CONTACT Range: Enabled, Disabled Default: Enabled Select ‘Enable’ if Contact Input 1 (terminal F5) is connected to the recloser state Aux contact (52a). The contact is ON (energized) when the recloser is closed and it is OFF (deenergized) when the recloser is opened. 52b CONTACT Range: Enabled, Disabled Default: Enabled Select ‘Enable’ if Contact Input 2 (terminal F6) is connected to the recloser reversed state Aux contact (52b). The contact is ON (energized) when the recloser is opened and it is OFF (de-energized) when the recloser is closed.

Circuit breaker setup

PATH: SETTINGS > S2 SYSTEM SETUP > CIRC BRK SETUP

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–19

S2 SYSTEM SETUP

CHAPTER 6: SETTINGS

CB STATE INFO Range: Local, Remote Default: Local This setting selects the means of getting the information about the circuit breaker state (opened or closed). Local: Comparing currents and voltages with the minimum threshold. Remote: Reading selected Contact Input (1 to x), Virtual Input (1 to 32), or Virtual Output (1 to 32). In addition, currents and voltages are compared with the minimum threshold to decide about the state of the circuit breaker. CB TYPE Range: 1 Unit (3 Pole), 3 Units (1 Pole) Default: 1 Unit (3 Pole) This setting has to match the type of the circuit breaker installed on the source side of the feeder. CB (3 POLE) CLOSED Range: Off, Contact Inputs 1 to x, Virtual Input 1 to 32, Virtual Output 1 to 32 Default: Off This setting configures the input to receive the state of the main breaker. The breaker will be in the closed state when this input is activated. CB a CLOSED Range: Off, Contact Inputs 1 to x, Virtual Input 1 to 32, Virtual Output 1 to 32 Default: Off This setting selects the input to receive the state of the pole of the phase a of the main breaker. The pole will be in the closed state when this input is activated. CB b CLOSED Range: Off, Contact Inputs 1 to x, Virtual Input 1 to 32, Virtual Output 1 to 32 Default: Off This setting selects the input to receive the state of the pole of the phase b of the main breaker. The pole will be in the closed state when this input is activated. CB c CLOSED Range: Off, Contact Inputs 1 to x, Virtual Input 1 to 32, Virtual Output 1 to 32 Default: Off This setting selects the input to receive the state of the pole of the phase c of the main breaker. The pole will be in the closed state when this input is activated.

Battery backup The DGCS is capable of controlling the feeder switch in different conditions including power loss. The power loss can occur if the feeder circuit breaker opens up or there is a distribution grid blackout. During all power loss conditions, the DGCS is supplied from a backup battery. It is sized to keep the DGCS running for 8 hours. During normal running conditions, the battery is connected to the charger. Switching to different modes of operation is controlled by a standard IO-E module. This module is inserted in the second slot of the two DGCS racks, reserved for IO-E modules. The hardware described above is referred to as DGCS Battery Backup System (BBS). The battery is a Sealed Valve Regulated Lead Acid (SVRLA) battery. A slow “3 step charging cycle” is recommended for optimal charging of SVRLA batteries. Improper charging is among the most common problems of premature failure of Lead Acid batteries. The preferred three step charging procedure is common for SVRLA batteries and consists of a constant current step followed by two steps of constant voltage. In the first step, BULK

6–20

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S2 SYSTEM SETUP

step, a constant current is applied to the battery until the battery voltage reaches a level of 80% State of Charge (SOC). The next step of charging is referred to as the TOP OFF or ABSORPTION step, and holds the 80% SOC voltage constant until the battery is not accepting any more charge (or until a pre-set timer in the controller has expired). At this point, the voltage is dropped to a new level and held constant in what is called the FLOAT step, so that the battery remains fully charged. This profile is optimal for most lead acid batteries. For 24 V battery systems, the voltage (at 25°C) should be within the range of 28.4 to 30 V. The battery backup is not like a traditional standard battery and charger. The system implemented is in fact simpler as it splits the charger into two parts: a power supply and a charger controller. The main reason a traditional method cannot be implemented is because no off the shelf charger exists that meets the wide temperature range of –40° to 60° and can withstand GE type test requirements. It is also important to capture the minimum and maximum voltages that the load can withstand. The minimum turn ON voltage for the load Switch Controller is 20VDC. The battery should therefore supply power down to 20VDC and then cut the load off to prevent deep discharge. A Battery Management System (BMS) board is implemented to the BBS to optimize battery life and provide useful feedback to the DGC. The BMS board will output the following to the DGC: 1.

Battery Low warning (19.6 V)

2. Battery fuse blown. Main function The connections of the BBS components are shown in the following BBS wiring diagram. Under normal running conditions, the main power supply feeds the DGCS and the battery charger. When a power loss condition occurs, the battery supplies power to the DGCS. Occasionally, the system checks the battery condition. MODES OF OPERATION Run In normal running condition, the power is fed from the unit labeled ‘POWER SUPPLY’, contact output 1 is closed, and contact output 2 is open. So, the battery is connected to the charger (unit labeled ‘CHARGER’) and its capacity is constantly being maintained at optimum level. In addition, the DGCS CPU power input is constantly energized. Once the unit is completely shut-off it cannot be powered by Battery only. An AC source must be applied to turn the unit on. Backup The BBS switches to this mode, when the power is down. In Backup mode, terminals labeled ‘BATTERY’ connect to terminals ‘DC LOAD’ inside the charger (unit labeled ‘ROGUE’) allowing the battery to feed the DGCS. Contact output 1 is closed, and contact output 2 is open. Test Battery test In test mode, the battery is disconnected from the charger and connected to an 8 ohm resistor for a certain time period that can be programmed in the BBS menu. During the test, Contact output 1 is open and Contact output 2 is closed. The duration of the test can be programmed. If the voltage stays above the contact input threshold (19.4 V) during the test, the battery will be considered healthy. Otherwise, the test aborts, and an alarm flag is set. The sequence is initiated periodically. The time between two tests can be set. In addition, pushing the button labeled ‘BATTERY TEST’ on the front panel, initiates the testing sequence.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–21

S2 SYSTEM SETUP

CHAPTER 6: SETTINGS

NOTE:

NOTE

If a power loss occurs during battery test, the DGCS power is supplied from the battery through the diode D3. In addition, after the power loss (detected by low “AC power OK” input), the battery test will abort within the output relay operate time. Fuse test The Battery fuse test is performed simultaneously with the battery test by checking the state of Contact inputs 1 and 2. If both are detected high, the fuse is considered healthy. If Contact input 2 is high but Contact input 1 is low, the fuse blown alarm will be set. Battery alarm LED This is a red LED located on the front panel. The LED light is off during normal operation. The LED turns on in three cases as follows. •

The battery test fails for a programmable number of times. Test failures have to be consecutive in order to turn the LED on. (Steady)



The battery fuse test fails. (Steady)



The battery test is in progress (Flashing).

Reset A manual or system reset command clears all battery related alarms and LED signals if the alarm condition does not exist anymore.

6–22



The battery test mode is not affected by the reset command.



An additional reset command is provided. The path is: COMMANDS/BAT TEST CONT RST. It has to be executed after the DEFECTIVE battery has been replaced with a new one.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S2 SYSTEM SETUP

Figure 6-5: Battery Backup System wiring diagram

IO_E 24V DC

+

+

POWER SUPPLY

-

-

D1 SURGE

~14 ~13

VT INPUT ~12

-

+

INPUT D2

DC LOAD

CHARGER

COMMON

~11

CONTACT INPUT 6 +

~10

CONTACT INPUT 5 +

~9

CONTACT INPUT 4 +

~8

CONTACT INPUT 3 +

~7

CONTACT INPUT 2 +

~6

CONTACT INPUT 1 +

~5 ~4

BATTERY TESTING

+

~3

-

~2 BATTERY CHARGING

Load for battery status check

~1

BATTERY

+

-

FUSE

D3

+

-

12V BATTERY

+

-

12V BATTERY 891873.cdr

PATH: SETTINGS > S2 SYSTEM SETUP > BATTERY BACKUP BATT TEST CYC TIME Range: 48 to 9000 hrs in steps of 1 hr Default: 168 min This setting defines the battery test cycle time, which is how often the battery test will be performed. The initial value of 168 hours is equal to one week. BATT TEST DURATION Range: 1 to 30 min in steps of 1 min Default: 15 hrs This setting defines the battery test duration time.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–23

Message: Message: BATTERY BATTERY TO FUSE REPLACE BLOWN

6–24

BATTERY TEST

Battery test passed

YES = 1

891753.cdr

0

COUNTER

RESET

RESET

INCREMENT

BATT TEST COUNTER

RESET

BATT TEST COUNT >= 1

BATT TEST LIMIT

SETTING

RESET

BATT TEST COUNT >= BATT TEST LIMIT

BATT TEST LIMIT

SETTING

R

LATCH

S

Battery test passed

Battery test in progress

15 min

R

LATCH

S

R

LATCH

S

Flashing

Message: BATTERY TEST IN PROGRESS

Event recorder

Message: CHECK BATTERY

Event recorder

Message: BATTERY TO REPLACE

LED:: BATTERY ALARM

Message:: BATTERY FUSE BLOWN

Event recorder

Batt Testing

IO_E MODULE OUT 2

Batt Charging

IO_E MODULE OUT 1

Steady

NO = 0

SETTING BATT TEST DURATION

BATT TEST COUNT

RESET DOMINANT

R

LATCH

S

AND

BATT TEST CONT RST

Battery Plus

IO_E MODULE IN 2

Battery Fuse

IO_E MODULE IN 1

One shot

Steady

COMMANDS

IN SERVICE

RELAY STATUS

0

OR

Battery test passed

AC Power OK

IO_E MODULE IN 6

AND

PUSH BUTTON

168 hr

BATT TEST CYC TIME

SETTING

S2 SYSTEM SETUP CHAPTER 6: SETTINGS

BATT TEST LIMIT Range: 1 to 20 in steps of 1 Default: 2 This setting defines the limit of the number of battery tests. When the number of consecutive unsuccessful battery tests reaches this limit, the BATTERY TO REPLACE alarm is raised.

Figure 6-6: Battery backup logic diagram

AND

OR

OR

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

Charger controller

S2 SYSTEM SETUP

The Charger Controller has the following features: •

10 Amp Capacity: The charger can facilitate a total of 10 amps to charge the battery and power the load.



Temperature Compensation: The charger has an internal temperature sensor and varies charging voltages accordingly.



3-stage Operation: The charger uses a 3 stage system to optimize lead acid battery charging. (Refer to graph for typical charging pattern).

The controller terminals are listed below:

Charger controller operation



-BATTERY - Negative Battery terminal



+BATTERY - Positive Battery terminal



+LOAD - Positive Load terminal



-LOAD - Negative Load terminal



LVALERT - Low Voltage Disconnect Signal, Active Low



-SOLAR - Negative Input terminal



+SOLAR - Positive Input terminal

A microcontroller reads the battery and power input voltages, along with a set of internal timers and other logic, and determines what the state of the switches (FETs) should be. The two switches are controlled and activated independently, such that either one, both, or neither switch can be activated at any given time. Figure 6-7: BMS Charge Graph

The graph above shows an ideal charging cycle typically found after a lead acid battery has discharged overnight. The red line (upper) indicates the battery terminal voltage and the green line (lower) indicates the charging current supplied to the battery.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–25

S2 SYSTEM SETUP

CHAPTER 6: SETTINGS

When the charger is first connected, or when the battery voltage drops below approximately 2.15V per cell, the charger enters bulk (fast) mode, where it attempts to bring the voltage to approximately 2.45V per cell. At this point, top-off mode is entered. When the charger senses that the battery is no longer taking a charge, float mode is entered where the voltage is lowered and maintained at approximately 2.3V per cell. The current for the load will come from the solar/power input when available, and the battery in that case will provide power filtering and smoothing to the load, while at the same time maintaining a float/trickle charge from the power source. The battery effectively acts as a large capacitor when connected in this manner

Battery safety information

To prevent fire or chemical burns: •

Do not attempt to recharge batteries after removal from the unit.



Do not disassemble, crush, or puncture the batteries.



Do not short the external contacts of the batteries.



Do not immerse the batteries in water.



Do not expose to temperatures higher than 80°C (176°F).



The batteries are recyclable. They contain lead and pose a hazard to the environment and human health if not disposed of properly. Return the battery to a factory authorized service center or refer to local codes for proper disposal requirements.



Do not open or mutilate batteries. They contain an electrolyte which is toxic and harmful to the skin and eyes.



Replace batteries with the same number and type of batteries as originally installed.

To prevent personal injury from hazardous energy: •

Remove watches, rings, or other metal objects.



Use tools with insulated handles.



Do not place tools or metal parts on top of batteries.



When removing and installing the new batteries, extreme care must be used not to short metal chassis parts across the battery terminals and not to short the batteries to each other. A battery can present a risk of electrical shock and high short circuit current.

To prevent personal injury, prepare the area and observe all materials-handling procedures when transporting a battery module. Battery modules weigh 5.7 kg (12.6 lb) each.

CAUTION:

Replacement procedure for batteries Replace all battery modules at the same time.

NOTE:

NOTE

6–26

1.

Servicing of batteries should be performed or supervised by Qualified Service Technician and the required precautions. Keep unauthorized personnel away from batteries.

2.

Remove the battery fuse (if present) prior to replacement.

3.

Disconnect the negative cable (wire label BATT- ROG-B) from the right battery black terminal.

4.

Disconnect the positive cable from the right battery red terminal.

5.

Disconnect the negative cable from the left battery black terminal.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

6.

Disconnect the positive cable (wire label BATT+ BATT-FS) from the left battery red terminal.

7.

Remove the battery securing strap.

8.

Remove both batteries.

9.

Secure two new same type of batteries back to back.

10. Reconnect the positive cable (wire label BATT+ BATT-FS) to the left battery red terminal. 11. Reconnect the negative cable to the left battery black terminal. 12. Reconnect the positive cable to the right battery red terminal. 13. Reconnect the negative cable (wire label BATT- ROG-B) to the right battery black terminal. 14. Secure the battery securing strap. 15. Replace the battery fuse.

S3 Configuration

Phase IOC The relay has one Instantaneous Overcurrent detection function Phase IOC. It consists of three separate Instantaneous Overcurrent blocks; one per phase, with identical settings.

PATH: SETTINGS > S3 CONFIGURATION > SETPOINT GROUP 1/2/3 > PHASE IOC PH IOC FUNCTION Range: Disabled, Enabled Default: Disabled The selection of the Enabled setting enables the Phase IOC function. The “ALARM” LED will flash upon Phase IOC operation, and the IOC function is selected as Enabled, and will self-reset when the operating condition clears.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–27

S3 CONFIGURATION

CHAPTER 6: SETTINGS

PH IOC PKP Range: 0.05 to 8.00 in steps of 0.01 x CT Default: 1.00 x CT This setting sets the Instantaneous Overcurrent pickup level in per times CT. For example, a PKP setting of 0.9 x CT with 300:5 CT translates into 270A primary current. PH IOC PKP DELAY Range: 0.00 to 600.00 s in steps of 0.01 s Default: 0.00 s This setting provides a selection for the time delay used to delay the operation of the protection function. PH IOC BLOCK Range: Off, Contact Input 1 to 8, Virtual Input Default: Off There is one blocking input provided in the Phase IOC menu. The selection of the block can include Contact inputs, Virtual Inputs and Virtual Outputs.

6–28

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

891830.cdr

Phase IOC B OP

Phase IOC C OP

Phase IOC OP

Phase IOC A OP

IB > PICKUP

IC > PICKUP

tPKP

0

0 tPKP

PH IOC PKP DELAY

tPKP

RUN

RUN

IA > PICKUP

RUN

Phase B Current (IB)

Phase C Current (IC)

Phase A Current (IA)

Phase Currents

Cold Load PKP

Block Inputs

Off = 0

SETTING PH IOC BLOCK

Enabled = 1

Disabled = 0

SETTING PH IOC FUNCTION

OR

AND

SETTING

PH IOC PICKUP:

SETTING

0

OR

AND

Message

Event Recorder

- LED: Alarm

Figure 6-8: PH IOC - logic diagram

Phase TOC The settings of this function are applied to each of the three phases to produce pickup and alarm condition per phase. The TOC pickup flag is asserted, when the current on any phase is above the PKP value. The TOC alarm flag is asserted if the element stays picked up for the time defined by the selected inverse curve and the magnitude of the current. The element drops from pickup without operation, if the measured current drops below 97-

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–29

S3 CONFIGURATION

CHAPTER 6: SETTINGS

98% of the pickup value, before the time for operation is reached. The selection of Definite Time with the base time delay of 0.1 s is multiplied by the selected TD multiplier. For example the operating time for TOC set to Definite Time and a TDM set to 5 will result in 5*0.1 = 0.5 s. SETTINGS

PATH: SETTINGS > S3 CONFIGURATION > SETPOINT GROUP 1/2/3 > PHASE TOC PH TOC FUNCTION Range: Disabled, Enabled Default: Disabled This setting enables the TOC detection function. The “ALARM” LED will flash upon Phase TOC operation and will self-reset when the operation clears. PH TOC PKP Range: 0.05 to 8.00 x CT in steps of 0.01 x CT Default: 1.00 x CT This setting sets the Time Overcurrent pickup level. For example, a PKP setting of 0.9 x CT with 300:5 CT translates into a 270 A primary current. PH TOC CURVE Range: ANSI Extremely/Very/Moderately/Normally Inverse, Definite Time, IEC Curve A/B/C and Short Inverse, IAC Extremely/Very/Inverse/Short, User Curve, FlexCurve A, FlexCurve B Default: Extremely Inverse This setting sets the shape of the selected TOC inverse curve. If none of the standard curve shapes is appropriate, a custom User curve, or FlexCurve can be created. Refer to the User curve and the FlexCurve setup for more detail on their configurations and usages. PH TOC TDM Range: 0.05 to 20.00 in steps of 0.01 Default: 1.00 This setting provides a selection for the Time Dial Multiplier by which the times from the inverse curve are modified. For example if an ANSI Extremely Inverse curve is selected with TDM = 2, and the fault current was 5 times greater than the PKP level, the operation of the element will not occur before an elapsed time from pickup, of 495 ms. PH TOC RESET TIME Range: Instantaneous, Linear Default: Instantaneous The “instantaneous” reset method is intended for applications with other relays, such as most static relays, which set the energy capacity directly to zero when the current falls below the Reset threshold. The “linear” reset method can be used where the relay must coordinate with electromechanical relays.

6–30

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

PH TOC BLOCK Range: Off, Contact Input 1 to 10[8], Virtual Input 1 to 32, Remote Input 1 to 32, Logic Elements 1 to 16 Default: Off One blocking input is provided in the Phase TOC menu. When the selected blocking input - Contact input, Virtual Input, Remote Input, or Logic Element - turns on, the Phase TOC function will be blocked.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–31

TOC curves

6–32

SETTING

Cold Load PKP

Adjust Phase TOC PKP

Phase C current (IC)

Phase B current (IB)

SETPOINTS

IB > PICKUP

IA > PICKUP

IC > PICKUP

Adjust PKP

RUN

Adjust PKP

RUN

Adjust PKP

RUN

PH TOC RESET TIME:

PH TOC TDM:

PH TOC CURVE:

PH TOC PICKUP:

OR

Phase A current (IA)

Phase Currents

Off = 0

PHTOC BLOCK

SETTING

Enabled = 0

PH TOC FUNCTION:

Phase IOC OP

LED: ALARM

PH TOC PH C PKP

PH TOC PH B PKP

PH TOC PH A PKP

PH TOC PKP

PH TOC OP

PH TOC PH C OP

PH TOC PH B OP

Message : PH TOC PH A OP

(From IOC Element)

891866.cdr

LED: PHASE OVERCURRENT

Event Recorder

Event Recorder

S3 CONFIGURATION CHAPTER 6: SETTINGS

Figure 6-9: Phase Time Overcurrent logic diagram

OR

OR

AND

DESCRIPTION

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

The relay has a total of two phase, two neutral, and two ground/sensitive ground time overcurrent elements. The programming of the time-current characteristics of these elements is identical in all cases and will only be covered in this section. The required curve is established by programming a Pickup Current, Curve Shape, Curve Multiplier, and Reset Time. The Curve Shape can be either a standard shape or a user-defined shape programmed with the FlexCurve™ feature. Accurate coordination may require changing the time overcurrent characteristics of particular elements under different conditions. For picking up a cold load, a different timecurrent characteristic can be produced by increasing the pickup current value. The following setpoints are used to program the time-current characteristics. •

PICKUP: The pickup current is the threshold current at which the time overcurrent element starts timing. There is no intentional ‘dead band’ when the current is above the pickup level. However, accuracy is only guaranteed above a 1.5 per unit pickup level. The dropout threshold is 98% of the pickup threshold. Enter the pickup current corresponding to 1 per unit on the time overcurrent curves as a multiple of the source CT. For example, if 100: 5 CTs are used and a pickup of 90 amps is required for the time overcurrent element, enter “0.9 x CT”.



CURVE: Select the desired curve shape. If none of the standard curve shapes is appropriate, a custom FlexCurve™ can be created by entering the trip times at 80 different current values; see S2 SYSTEM SETUP > FLEXCURVE A. Curve formulas are given for use with computer based coordination programs. Calculated trip time values are only valid for I / Ipu > 1. Select the appropriate curve shape and multiplier, thus matching the appropriate curve with the protection requirements. The available curves are shown in the table below.

ANSI

GE TYPE IAC

IEC

OTHER

Extremely Inverse

Extremely Inverse

Curve A (BS142)

Definite Time

Very Inverse

Very Inverse

Curve B (BS142)

Flexcurve ATM

Normally Inverse

Inverse

Curve C (BS142)

Flexcurve BTM

Moderately Inverse

Short Inverse

IEC Short Inverse

User Curve



MULTIPLIER: A multiplier setpoint allows shifting of the selected base curve in the vertical time direction. Unlike the electromechanical time dial equivalent, trip times are directly proportional to the value of the time multiplier setpoint. For example, all trip times for a multiplier of 10 are 10 times the multiplier 1 or base curve values. When Timed Over-Current is programmed with Definite time, the operating time is obtained after multiplication of the selected Multiplier (TDM) by a 0.1 s base line. For example, selection of TDM = 5 would lead to a 0.5 s operating time.



RESET: Time overcurrent tripping time calculations are made with an internal ‘energy capacity’ memory variable. When this variable indicates that the energy capacity has reached 100%, a time overcurrent trip is generated. If less than 100% is accumulated in this variable and the current falls below the dropout threshold of 97 to 99% of the pickup value, the variable must be reduced. Two methods of this resetting operation are available, Instantaneous and Linear. The Instantaneous selection is intended for applications with other relays, such as most static units, which set the energy capacity directly to zero when the current falls below the reset threshold. The Linear selection can be used where the relay must coordinate with electromechanical units. With this setpoint, the energy capacity variable is decremented according to the following equation.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–33

S3 CONFIGURATION

CHAPTER 6: SETTINGS

where: TRESET = reset time in seconds; E = energy capacity reached (per unit); M = curve multiplier; CR = characteristic constant (5 for ANSI, IAC, Definite Time, and FlexCurves™; 8 for IEC) TOC CURVE CHARACTERISTICS ANSI Curves The ANSI time overcurrent curve shapes conform to industry standards and the ANSI C37.90 curve classifications for extremely, very, normally, and moderately inverse. The ANSI curves are derived from the following formula:

where:T = trip time (seconds); M = multiplier value; I = input current; Ipu = pickup current setpoint; A, B, C, D, E = constants Table 6-4: ANSI Curve Constants ANSI Curve Shape

A

B

C

D

ANSI Extremely Inverse

0.0399

0.2294

0.5000

3.0094

E 0.7222

ANSI Very Inverse

0.0615

0.7989

0.3400

–0.2840

4.0505

ANSI Normally Inverse

0.0274

2.2614

0.3000

–4.1899

9.1272

ANSI Moderately Inverse

0.1735

0.6791

0.8000

–0.0800

0.1271

Table 6-5: ANSI Curve Trip Times (in seconds) Multiplier (TDM)

Current (I/Ipickup) 1.5

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

ANSI Extremely Inverse 0.5

2.000

0.872

0.330

0.184

0.124

0.093

0.075

0.063

0.055

0.049

1.0

4.001

1.744

0.659

0.368

0.247

0.185

0.149

0.126

0.110

0.098

2.0

8.002

3.489

1.319

0.736

0.495

0.371

0.298

0.251

0.219

0.196

4.0

16.004 6.977

2.638

1.472

0.990

0.742

0.596

0.503

0.439

0.393

6.0

24.005 10.466 3.956

2.208

1.484

1.113

0.894

0.754

0.658

0.589

8.0

32.007 13.955 5.275

2.944

1.979

1.483

1.192

1.006

0.878

0.786

10.0

40.009 17.443 6.594

3.680

2.474

1.854

1.491

1.257

1.097

0.982

0.5

1.567

0.663

0.268

0.171

0.130

0.108

0.094

0.085

0.078

0.073

1.0

3.134

1.325

0.537

0.341

0.260

0.216

0.189

0.170

0.156

0.146

2.0

6.268

2.650

1.074

0.682

0.520

0.432

0.378

0.340

0.312

0.291

4.0

12.537 5.301

2.148

1.365

1.040

0.864

0.755

0.680

0.625

0.583

6.0

18.805 7.951

3.221

2.047

1.559

1.297

1.133

1.020

0.937

0.874

8.0

25.073 10.602 4.295

2.730

2.079

1.729

1.510

1.360

1.250

1.165

10.0

31.341 13.252 5.369

3.412

2.599

2.161

1.888

1.700

1.562

1.457

ANSI Very Inverse

ANSI Normally Inverse 0.5

2.142

0.883

0.377

0.256

0.203

0.172

0.151

0.135

0.123

0.113

1.0

4.284

1.766

0.754

0.513

0.407

0.344

0.302

0.270

0.246

0.226

2.0

8.568

3.531

1.508

1.025

0.814

0.689

0.604

0.541

0.492

0.452

4.0

17.137 7.062

3.016

2.051

1.627

1.378

1.208

1.082

0.983

0.904

6.0

25.705 10.594 4.524

3.076

2.441

2.067

1.812

1.622

1.475

1.356

8.0

34.274 14.125 6.031

4.102

3.254

2.756

2.415

2.163

1.967

1.808

10.0

42.842 17.656 7.539

5.127

4.068

3.445

3.019

2.704

2.458

2.260

ANSI Moderately Inverse

6–34

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

Multiplier (TDM)

Current (I/Ipickup) 1.5

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

0.5

0.675

0.379

0.239

0.191

0.166

0.151

0.141

0.133

0.128

0.123

1.0

1.351

0.757

0.478

0.382

0.332

0.302

0.281

0.267

0.255

0.247

2.0

2.702

1.515

0.955

0.764

0.665

0.604

0.563

0.533

0.511

0.493

4.0

5.404

3.030

1.910

1.527

1.329

1.208

1.126

1.066

1.021

0.986

6.0

8.106

4.544

2.866

2.291

1.994

1.812

1.689

1.600

1.532

1.479

8.0

10.807 6.059

3.821

3.054

2.659

2.416

2.252

2.133

2.043

1.972

10.0

13.509 7.574

4.776

3.818

3.324

3.020

2.815

2.666

2.554

2.465

IEC Curves For European applications, the relay offers the four standard curves defined in IEC 255-4 and British standard BS142. These are defined as IEC Curve A, IEC Curve B, IEC Curve C, and Short Inverse. The formulae for these curves are:

where: T = trip time (seconds), M = multiplier setpoint, I = input current, Ipu = pickup current setpoint, K, E = constants. Table 6-6: IEC (BS) Inverse Time Curve Constants IEC (BS) Curve Shape

K

E

IEC Curve A (BS142)

0.140

0.020

IEC Curve B (BS142)

13.500

1.000

IEC Curve C (BS142)

80.000

2.000

IEC Short Inverse

0.050

0.040

Table 6-7: IEC Curve Trip Times (in seconds) Multiplier (TDM)

Current (I/Ipickup) 1.5

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

0.05

0.860

0.501

0.315

0.249

0.214

0.192

0.176

0.165

0.156

0.149

0.10

1.719

1.003

0.630

0.498

0.428

0.384

0.353

0.330

0.312

0.297

0.20

3.439

2.006

1.260

0.996

0.856

0.767

0.706

0.659

0.623

0.594

0.40

6.878

4.012

2.521

1.992

1.712

1.535

1.411

1.319

1.247

1.188

0.60

10.317 6.017

3.781

2.988

2.568

2.302

2.117

1.978

1.870

1.782

0.80

13.755 8.023

5.042

3.984

3.424

3.070

2.822

2.637

2.493

2.376

1.00

17.194 10.029 6.302

4.980

4.280

3.837

3.528

3.297

3.116

2.971

0.05

1.350

0.675

0.338

0.225

0.169

0.135

0.113

0.096

0.084

0.075

0.10

2.700

1.350

0.675

0.450

0.338

0.270

0.225

0.193

0.169

0.150

0.20

5.400

2.700

1.350

0.900

0.675

0.540

0.450

0.386

0.338

0.300

0.40

10.800 5.400

2.700

1.800

1.350

1.080

0.900

0.771

0.675

0.600

0.60

16.200 8.100

4.050

2.700

2.025

1.620

1.350

1.157

1.013

0.900

0.80

21.600 10.800 5.400

3.600

2.700

2.160

1.800

1.543

1.350

1.200

1.00

27.000 13.500 6.750

4.500

3.375

2.700

2.250

1.929

1.688

1.500

0.05

3.200

1.333

0.500

0.267

0.167

0.114

0.083

0.063

0.050

0.040

0.10

6.400

2.667

1.000

0.533

0.333

0.229

0.167

0.127

0.100

0.081

IEC Curve A

IEC Curve B

IEC Curve C

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–35

S3 CONFIGURATION

CHAPTER 6: SETTINGS

Multiplier (TDM)

Current (I/Ipickup) 1.5

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

2.000

1.067

0.667

0.457

0.333

0.254

0.200

0.162

0.40

25.600 10.667 4.000

2.133

1.333

0.914

0.667

0.508

0.400

0.323

0.60

38.400 16.000 6.000

3.200

2.000

1.371

1.000

0.762

0.600

0.485

0.80

51.200 21.333 8.000

4.267

2.667

1.829

1.333

1.016

0.800

0.646

1.00

64.000 26.667 10.000 5.333

3.333

2.286

1.667

1.270

1.000

0.808

0.05

0.153

0.089

0.056

0.044

0.038

0.034

0.031

0.029

0.027

0.026

0.10

0.306

0.178

0.111

0.088

0.075

0.067

0.062

0.058

0.054

0.052

0.20

0.612

0.356

0.223

0.175

0.150

0.135

0.124

0.115

0.109

0.104

0.40

1.223

0.711

0.445

0.351

0.301

0.269

0.247

0.231

0.218

0.207

0.60

1.835

1.067

0.668

0.526

0.451

0.404

0.371

0.346

0.327

0.311

0.80

2.446

1.423

0.890

0.702

0.602

0.538

0.494

0.461

0.435

0.415

1.00

3.058

1.778

1.113

0.877

0.752

0.673

0.618

0.576

0.544

0.518

0.20

12.800 5.333

IEC Short Time

IAC Curves The curves for the General Electric type IAC relay family are derived from the formulae:

where: T = trip time (seconds), M = multiplier setpoint, I = input current, Ipu = pickup current setpoint, A to E = constants. Table 6-8: GE Type IAC Inverse Curve Constants IAC Curve Shape

A

B

C

D

E

IAC Extreme Inverse

0.0040

0.6379

0.6200

1.7872

0.2461

IAC Very Inverse

0.0900

0.7955

0.1000

–1.2885

7.9586

IAC Inverse

0.2078

0.8630

0.8000

–0.4180

0.1947

IAC Short Inverse

0.0428

0.0609

0.6200

–0.0010

0.0221

Table 6-9: IAC Curve Trip Times Multiplier (TDM) 1.5

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

IAC Extremely Inverse 0.5

1.699

0.749

0.303

0.178

0.123

0.093

0.074

0.062

0.053

0.046

1.0

3.398

1.498

0.606

0.356

0.246

0.186

0.149

0.124

0.106

0.093

2.0

6.796

2.997

1.212

0.711

0.491

0.372

0.298

0.248

0.212

0.185

4.0

13.591 5.993

2.423

1.422

0.983

0.744

0.595

0.495

0.424

0.370

6.0

20.387 8.990

3.635

2.133

1.474

1.115

0.893

0.743

0.636

0.556

8.0

27.183 11.987 4.846

2.844

1.966

1.487

1.191

0.991

0.848

0.741

10.0

33.979 14.983 6.058

3.555

2.457

1.859

1.488

1.239

1.060

0.926

0.5

1.451

0.656

0.269

0.172

0.133

0.113

0.101

0.093

0.087

0.083

1.0

2.901

1.312

0.537

0.343

0.266

0.227

0.202

0.186

0.174

0.165

2.0

5.802

2.624

1.075

0.687

0.533

0.453

0.405

0.372

0.349

0.331

4.0

11.605 5.248

2.150

1.374

1.065

0.906

0.810

0.745

0.698

0.662

6.0

17.407 7.872

3.225

2.061

1.598

1.359

1.215

1.117

1.046

0.992

8.0

23.209 10.497 4.299

2.747

2.131

1.813

1.620

1.490

1.395

1.323

IAC Very Inverse

6–36

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

Multiplier (TDM) 1.5

4.0

5.0

6.0

7.0

8.0

9.0

10.0

29.012 13.121 5.374

3.434

2.663

2.266

2.025

1.862

1.744

1.654

0.5

0.578

0.375

0.266

0.221

0.196

0.180

0.168

0.160

0.154

0.148

1.0

1.155

0.749

0.532

0.443

0.392

0.360

0.337

0.320

0.307

0.297

2.0

2.310

1.499

1.064

0.885

0.784

0.719

0.674

0.640

0.614

0.594

4.0

4.621

2.997

2.128

1.770

1.569

1.439

1.348

1.280

1.229

1.188

6.0

6.931

4.496

3.192

2.656

2.353

2.158

2.022

1.921

1.843

1.781

8.0

9.242

5.995

4.256

3.541

3.138

2.878

2.695

2.561

2.457

2.375

10.0

11.552 7.494

5.320

4.426

3.922

3.597

3.369

3.201

3.072

2.969

0.5

0.072

0.047

0.035

0.031

0.028

0.027

0.026

0.026

0.025

0.025

1.0

0.143

0.095

0.070

0.061

0.057

0.054

0.052

0.051

0.050

0.049

2.0

0.286

0.190

0.140

0.123

0.114

0.108

0.105

0.102

0.100

0.099

4.0

0.573

0.379

0.279

0.245

0.228

0.217

0.210

0.204

0.200

0.197

6.0

0.859

0.569

0.419

0.368

0.341

0.325

0.314

0.307

0.301

0.296

8.0

1.145

0.759

0.559

0.490

0.455

0.434

0.419

0.409

0.401

0.394

10.0

1.431

0.948

0.699

0.613

0.569

0.542

0.524

0.511

0.501

0.493

10.0

2.0

3.0

IAC Inverse

IAC Short Inverse

USER Curves The relay provides a selection of user definable curve shapes used by the time overcurrent protection. The User curve is programmed by selecting the proper parameters in the formula:

A, P, Q, B, K - selectable curve parameters within the ranges from the table: D is the Time Dial Multiplier. User Curve can be used on multiple elements only if the time dial multiplier is the same for each element. V = I/IPICKUP (TOC setting) is the ratio between the measured current and the pickup setting. The maximum trip time for the User Curve is limited to 65.535 seconds. The User Curve can be used for one protection situation only.

NOTE:

NOTE

Parameters

A

B

P

Q

K

Range

0 to 125

0 to 3

0 to 3

0 to 2

0 to 1.999

Step

0.0001

0.0001

0.0001

0.0001

0.001

Unit

sec

sec

NA

NA

sec

Default Value

0.05

0

0.04

1.0

0

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–37

S3 CONFIGURATION

CHAPTER 6: SETTINGS

Figure 6-10: USER curve configuration settings

Flexcurves Prospective FlexCurves™ can be configured from a selection of standard curves to provide the best approximate fit, then specific data points can be edited afterwards. Click the Initialize button to populate the pickup values with the points from the curve specified by the "Select Curve" setting and the "Multiply" value. These values can then be edited to create a custom curve. Click on the Clear FlexCurve Data button to reset all pickup values to zero. Curve data can be imported from CSV (comma-separated values) files by clicking on the Open button. Likewise, curve data can be saved in CSV format by clicking the Save button. CSV is a delimited data format with fields separated by the comma character and records separated by new lines. Refer to IETF RFC 4180 for additional details. The curve shapes for the two FlexCurves are derived from the following equations.

In the above equations, Toperate represents the operate time in seconds, TDM represents the multiplier setting, I represents the input current, Ipickup represents the value of the pickup current setting, Tflex represents the FlexCurve™ time in seconds.

6–38

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

Figure 6-11: Flexcurve™ configuration settings

The following settings are available for each custom Flexcurve™. Select Curve Range: ANSI Moderately Inverse, ANSI Very Inverse, ANSI Extremely Inverse, IEEE Normally Inverse, IEC Curve A, IEC Curve B, IEC Curve C, IEC Short Inverse, IAC Extreme Inv, IAC Very Inverse, IAC Inverse, IAC Short Inverse, User Curve, FlexCurve B (Note: For FlexCurve A, you can select FlexCurve B as the setpoint, and vice versa for FlexCurve B.) Default: Extremely Inverse This setting specifies a curve to use as a base for a custom FlexCurve™. Must be used before Initialization is implemented (see Initialization below). Multiply Range: 0.01 to 30.00 in steps of 0.01 Default: 1.00 This setting provides selection for Time Dial Multiplier by which the times from the inverse curve are modified. For example if an ANSI Extremely Inverse curve is selected with TDM = 2, and the fault current was 5 times bigger than the PKP level, the operation of the element will not occur before a time elapse of 495 ms from pickup. Initialization Used after specifying a curve to use as a base for a custom FlexCurve™ (see Select Curve and Multiply above). When the Initialize FlexCurve button is clicked, the pickup settings will be populated with values specified by the curve selected in this setting.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–39

S3 CONFIGURATION

CHAPTER 6: SETTINGS

1.03 × Pickup, ..., 20.00 × Pickup Range: 0 to 65535 ms in steps of 1 Default: 0 ms These settings specify the time to operate at the following pickup levels 1.03 to 20.00. This data is converted into a continuous curve by linear interpolation between data points. To enter a custom FlexCurve™, enter the operate time for each selected pickup point. NOTE:

NOTE

Each FlexCurve can be configured to provide inverse time characteristic to more than one Time Overcurrent Element. However, for computation of the curve operating times, one must take into account the setting of the Time Delay Multiplier from the FlexCurve menu, and the Time Delay Multiplier setting from TOC menu. The true TDM applied to the TOC element when FlexCurve is selected is the result from the multiplication of both TDM settings. For example, for FlexCurve Multiplier = 5, and Phase TOC Multiplier = 2, the total Time Dial Multiplier will be equal to 10. To avoid confusion, it is suggested to keep the multiplier from the TOC menu equal to 1, and change only the multiplier from the selected FlexCurve. This way, one can see from the FlexCurve setup, the curve operating times as related to the multiples of pickup.

Neutral overcurrent The relay has one Neutral Instantaneous Overcurrent detection function. The settings of this function are applied to the calculated neutral current as a pickup flag. The Neutral IOC pickup flag is asserted when the neutral current is above the PKP value. The Neutral IOC operate flag is asserted if the element stays picked up for the time defined by the Neutral IOC Delay setting. If the pickup time delay is set to 0.00 seconds, the pickup and operate flags will be asserted at the same time. The element drops from pickup without operation if the neutral current drops below 97 to 98% of the pickup value.

PATH: SETTINGS > S3 CONFIGURATION > SETPOINT GROUP 1/2/3 > NEUTRAL OVERCURRENT NTRL IOC FUNCTION Range: Disabled, Enabled Default: Disabled The selection of the Enabled setting enables the Neutral IOC function. The “ALARM” LED will flash upon Neutral IOC operation, with the IOC function selected as Enabled, and will self-reset when the operating condition clears. NTRL IOC PKP Range: 0.05 to 8 x CT in steps of 0.01 x CT Default: 1.00 x CT This setting sets the Neutral Instantaneous Overcurrent pickup level specified per times CT. NTRL IOC DELAY Range: 0.00 to 600.00 s in steps of 0.01 Default: 0.00 s This setting provides a selection for pickup time delay used to delay the operation of this function.

6–40

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

NTRL IOC BLOCK Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Virtual Output 1 to 32 Default: Off There is one blocking input provided in the Neutral IOC menu. The selection of the block can include Contact Input, Virtual Input, and Virtual Output.

Message: Neutral IOC OP

LED: ALARM

891831.cdr

LED: NEUTRAL OVERCURRENT

Event Recorder

Figure 6-12: Neutral IOC - logic diagram

0 tPKP IN > PICKUP

SETTING

RUN

SETTING

NTRL IOC PICKUP

NTRL IOC PKP DLY

Message: Neutral IOC PKP

AND

AND

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

Block Inputs

Computed by the relay Neutral current (IN)

Cold Load PKP

SETTING NTRL IOC BLOCK Off = 0

SETTING NTRL IOC FUNCTION: Disabled = 0 Enabled

OR

6–41

S3 CONFIGURATION

CHAPTER 6: SETTINGS

Phase overvoltage The Phase OV protection can be used to protect voltage sensitive feeder loads and circuits against sustained overvoltage conditions. The protection element can be used to generate an alarm when the voltage exceeds the selected voltage level for the specified time delay.

PATH: SETTINGS > S3 CONFIGURATION > SETPOINT GROUP 1/2/3 > OVERVOLTAGE PH OV FUNCTION Range: Disabled, Enabled Default: Disabled The selection of the Enabled setting enables the Phase OV function. The ALARM LED will flash upon OV operation with the phase OV selected as Enabled, and will self-reset, when the operating condition clears. PH OV PKP Range: 0.05 to 1.25 x VT in steps of 0.01 Default: 1.25 x VT This setting defines the phase OV pickup level, and is usually set to a level above which some voltage sensitive loads and feeder components may experience over-excitation and dangerous overheating conditions. PH OV DELAY Range: 0.0 to 600.0 s in steps of 0.1 Default: 1.0 s This setting specifies the time delay before OV operation. PH OV PHASES Range: Any One, Any Two, All Three Default: Any One This setting selects the combination of overvoltage conditions with respect to the number of the phase voltages to the overvoltage pickup setting. PH OV BLOCK Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Virtual Output 1 to 32 Default: Off There is one blocking input provided in the Phase Overvoltage menu. The selection of the block can include Contact Inputs, Virtual Inputs, and Virtual Outputs.

6–42

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

SETTING

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL Delta Vab Vbc Vca

Wye

Van

Vbn

Vcn

None

Phase Voltage Inputs (associated setpoints)

Off = 0

PH OV BLOCK

SETTING

Enabled

Disabled = 0

PH OV FUNCTION:

SETTINGS

RUN

RUN

RUN

Vc > PICKUP

Vb > PICKUP

Va > PICKUP

PH OV PICKUP:

SETTING

Operate for programmed combination

All Three

Any Two

Any One

PH OV PHASES:

SETTING

tPKP

PHASE OV DELAY:

AND

OV PKP Event Recorder 891867.cdr

LED: OVERVOLTAGE

Phase Overvoltage Messages

LED: ALARM

CHAPTER 6: SETTINGS S3 CONFIGURATION

Figure 6-13: Phase Overvoltage logic diagram

OR

AND

6–43

S3 CONFIGURATION

CHAPTER 6: SETTINGS

Phase undervoltage For voltage sensitive loads, such as induction motors, a drop in voltage will result in an increase in the drawn current, which may cause dangerous overheating in the motor. The undervoltage protection feature can be used to generate an alarm when the voltage drops below a specified voltage setting for a specified time delay.

PATH: SETTINGS > S3 CONFIGURATION > SETPOINT GROUP 1/2/3 > UNDERVOLTAGE PH UV FUNCTION Range: Disabled, Enabled Default: Disabled The selection of Enabled setting enables Phase UV function. The LED “ALARM” will flash upon UV operating condition, with the phase UV selected as Alarm, and will self-reset, when the operating condition clears. PH UV PKP Range: 0.05 to 1.25 x VT in steps of 0.01 Default: 0.75 x VT This setting defines the phase UV pickup level, and it is usually set to a level, below which the drawn current from voltage sensitive loads, such as induction motors may cause dangerous motor overheating conditions. PH UV CURVE Range: Definite Time, Inverse Time Default: Inverse Time This setting selects the type of inverse time curve, to define the time of undervoltage operation based on selected UV time delay, and the actual undervoltage condition with respect to selected UV pickup. PH UV DELAY Range: 0.0 to 600.0 s in steps of 0.1 Default: 1.0 s This setting specifies a time delay, used by the selected PHASE UV CURVE type of timing to calculate time before UV operation. PH UV PHASES Range: Any One, Any Two, All Three Default: Any One This setting selects the combination of undervoltage conditions with respect to the number of phase voltages under the undervoltage pickup setting. Selection of the “Any Two”, or “All Three” setting would effectively rule out the case of a single VT fuse failure. PH UV MIN VOLTAGE Range: 0.00 to 1.25 x VT in steps of 0.01 Default: 0.30 X VT The minimum operating voltage level is programmable to prevent undesired UV operation before voltage becomes available.

6–44

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

PH UV BLOCK Range: Off, Contact Input 1 to 8, Virtual Input1 to 32, Virtual Output 1 to 32 Default: Off There is one blocking input provided in the Phase OverVoltage menu. The selection of the block can include Contact Input, Virtual Input and Virtual Outputs.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–45

6–46

SETPOINT

Delta

Vab

Vbc

Vca

Wye

Van

Vbn

Vcn

None

Phase Voltage Inputs (associated setpoints)

Off = 0

PH UV BLOCK

SETPOINTS

Enabled = 1

Disabled = 0

PH UV FUNCTION

AND SETPOINT

Vcn or Vca > Minimum

RUN

AND

Van or Vab > Minimum

RUN

AND

Vbn or Vbc > Minimum

RUN

PICKUP

PICKUP

PICKUP

PH UV DELAY:

PH UV CURVE:

AND

PH UV MIN VOLTAGE:

SETPOINTS PH UV PICKUP:

UV PKP Event Recorder

SETPOINT

Operate for programmed combination

All Three

Any Two

Any One

PH UV PHASES:

LED: UNDERVOLTAGE

891836.cdr

UV OP/DPO Event Recorder

Phase Undervoltage Messages

LED: ALARM

S3 CONFIGURATION CHAPTER 6: SETTINGS

Figure 6-14: Phase Undervoltage - logic diagram

AND

OR

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

Phase undervoltage curves

The undervoltage elements can be programmed to have an inverse time delay characteristic. The undervoltage delay setpoint defines a family of curves as shown below. The operating time is given by:

T=

D 1- V/Vpu

Eq. 1

Where: T = Operating Time D = Undervoltage Delay setpoint V = Voltage as a fraction of the nominal VT Secondary Voltage Vpu = Pickup Level At 0% of pickup, the operating time equals the Undervoltage Delay setpoint.

NOTE:

NOTE

Figure 6-15: Inverse time undervoltage curves D=5.0

20.0

2.0 1.0

18.0

Time (seconds)

16.0 14.0 12.0 10.0 8.0 6.0 4.0 2.0 0.0 0

10

20 30

40

50

60

70

80 90 100 110

% of V pickup

The following path is available using the keypad. For instructions on how to use the keypad, please refer to Chapter 3 - Working with the Keypad.

Voltage unbalance For the DGC, unbalance is defined as the ratio of negative-sequence to positive-sequence voltage, (V2/V1) X 100%. If enabled, an alarm occurs once the unbalance level equals and exceeds the set pickup for the set period of time.

PATH: SETPOINTS > S3 CONFIGURATION > SETPOINT GROUP 1/2/3 > VOLTAGE UNBALANCE VOLTAGE UNBAL FUNC Range: Disabled, Enabled Default: Disabled This setting enables the Voltage Unbalance functionality.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–47

S3 CONFIGURATION

CHAPTER 6: SETTINGS

VOLTAGE UNBAL PKP Range: 4% to 40% in steps of 1% Default: 15% This setting specifies a pickup threshold for the Voltage Unbalance condition. VOLTAGE UNBL DELAY Range: 1.00 to 60.00 s in steps of 0.01 s Default: 1.00 s This setting specifies a time delay for the Voltage Unbalance condition. VOLTAGE UNBL BLOCK Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Virtual Output 1 to 32 Default: Off There is one blocking input provided for the Voltage Unbalance feature. When the selected blocking input is ON, the Voltage Unbalance function is blocked.

6–48

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

SETTING

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

ACTUAL VALUE Source side negative sequence voltage (V2) Source side positive sequence voltage (V1)

Off = 0

VOLTAGE UNBL BLOCK

SETTING

Enabled = 1

Disabled = 0

VOLTAGE UNBAL FUNC:

(V2/V1) x100%

SETTING

UNBAL >= PICKUP

RUN

VOLTAGE UNBL PKP:

SETTING

tPKP

VOLTAGE UNBL DELAY:

891868.cdr

Event Recorder

Message

Voltage Unbalance

LED: ALARM

CHAPTER 6: SETTINGS S3 CONFIGURATION

Figure 6-16: Voltage Unbalance - logic diagram

AND

AND

6–49

S3 CONFIGURATION

CHAPTER 6: SETTINGS

Power loss The Power Loss detection function is used to detect a power loss condition in each phase of the power distribution line. After opening the upstream breaker, the DGC has to confirm that the voltage and current levels of the line are below a minimum threshold.When the switch type is selected as ’no-load,’ the opening or closing commands of the switch are interlocked with this function. Any OPEN or CLOSE command will be blocked unless the currents and voltages of each phase fall below minimum set values. This function is also used by the auto-sectionalizing function to detect the power loss condition after a previous IOC fault detection. When the switch is closed, the power loss detection of the source side is used to control the opening commands execution. However, for DGC devices provided with voltage on both sides of the line, the power loss condition has to be established in both sides before closing a no-load switch into the power line.

PATH: SETTINGS > S3 CONFIGURATION > SETPOINT GROUP 1/2/3 > POWER LOSS MIN PH CURR PICKUP Range: 0.01 to 0.40xCT in steps of 0.01xCT Default: 0.03xCT This setting is used to detect the circuit breaker open condition. When a phase current falls below this threshold and at the same time the voltage of the same phase falls below its minimum value, the power loss condition of this phase is declared after the power loss delay expires. MIN PH VOLT PICKUP Range: 0.01 to 0.40xVT in steps of 0.01xVT Default: 0.05xVT This setting is used to detect the circuit breaker open condition. When a phase voltage falls below this threshold and at the same time the current of the same phase falls below its minimum value, the power loss condition of this phase is declared after the power loss delay expires. POWER LOSS DELAY Range: 0.00 to 10.00 s in steps of 0.01 s Default: 0.05 s This setting specifies the time delay before a power loss condition.

6–50

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

SETTING

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL RUN

Phase B Current (Ib)

Vab

Vbc

Vca

Van

Vbn

Vcn

Source [load] Voltage Delta Wye

Wye = 0 Delta = 1

SETTING VT INPUT

MAX

MAX

V < PICKUP

V < PICKUP

V < PICKUP

MIN PH VOLT PICKUP

SETTING

Ic < PICKUP

Ib < PICKUP

Ia < PICKUP

MAX

RUN

Phase A Current (Ia)

Phase C Current (Ic)

RUN

RELAY STATUS In Service

MIN PH CURR PICKUP

2 Vin > Vab > 1.5 Vin

RUN

2 Vin > Vca > 1.5 Vin

RUN

2 Vin > Vbc > 1.5 Vin

RUN

AND

AND

OR

OR

OR

AND

AND

AND

AND

AND OR

OR

OR

tPKP

POWER LOSS DELAY

SETTING

tPKP

POWER LOSS DELAY

SETTING

tPKP

POWER LOSS DELAY

SETTING

OR

AND

- LED: ALARM

FlexLogic Operands & Event Recorder

PWR LOSS SRC (LOAD)

- LED: AC POWER LOSS

PWR LOSS SRC (LOAD) PH A PWR LOSS SRC (LOAD) PH B PWR LOSS SRC (LOAD) PH C

FlexLogic Operands & Event Recorder

CHAPTER 6: SETTINGS S3 CONFIGURATION

Figure 6-17: Power Loss - logic diagram

6–51

S3 CONFIGURATION

CHAPTER 6: SETTINGS

Auto sectionalizing The Auto Sectionalizing function of the DGCS is designed to control a switch separating the sections of a feeder. Normally there are several switches within one feeder, each controlled by a separate DGCS. The feeder is protected by a circuit breaker installed on the source side. When there is a fault on the feeder, Auto Sectionalizing functions in all feeder DGCS units coordinate the actions of the breaker using feeder switches. At the end of the switching sequence, the switch at the entry point of the faulty section remains open, allowing the upstream sections to resume normal operation. As indicated above, the distribution feeders are equipped with feeder switches (pole-top, pad-mount) that can segment the feeder into electrically isolated sections. Distribution circuits called “laterals” (labeled as ‘Loads’) are connected between two consecutive switches. These are protected by over-current fuses and are not automated. An example of the circuit is depicted in the figure below. Figure 6-18: Typical Distribution Circuit

For the topology shown above, the assumption is that there is a fault (F2) on Feeder 1. Circuit breaker 1 will start with the trip-reclose operating profile shown below.

6–52

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

Figure 6-19: Circuit Breaker Operating Profile - F2 fault condition

The circuit breaker operating steps on the profile are numbered from 1 to 12. The height of the profile step is scaled to the current and the length of the profile step is scaled to the duration of the state. The duration of steps and the number of re-closing attempts can be set on the circuit breaker controller. Usually the entire CB fault operating profile completes within 60 seconds. The number of re-closing attempts must be set to the number of feeder switches, incremented by 1. Usually, the maximum number of re-closing attempts is 4, which limits the number of sectionalizing switches to 3. In this example, there are 3 reclosing attempts (events 3, 7 and 11). Each DGCS is equipped with a CT set that is installed at the source side of the corresponding switch. Using the current readout, DGCs will detect the fault current if the fault occurred downstream of the switch. Both DGCs are in counting mode. They are counting events ‘Overcurrent followed by power supply loss’. For the last switch on the feeder (furthermost from the circuit breaker) the count limit must be set to 2 and it should increment by 1 for each switch positioned closer to the circuit breaker. In this case the DGCS_11 count limit is 3 and the DGCS_12 count limit is 2. When a DGCS unit count reaches its limit, the switch will open. Two cases will be considered: F1. The fault occurred between the Tie breaker / switch and DGCS_12. After the Auto Sectionalizing sequence is complete, the DGCS_12 will open during CB event 6. After CB step 7 is complete, the nominal current will flow through the feeder and the faulty feeder segment will be sectionalized. F2. The fault occurred between the DGCS_11 and DGCS_12. After the Auto Sectionalizing sequence is complete, the DGCS_11 will open during CB event 10. After CB step 11 is complete, the nominal current will flow through the feeder and the faulty feeder segment will be sectionalized. NOTE:

NOTE

Each DGCS is set to detect a reverse power condition. If such a condition has been detected, the Auto Sectionalizing sequence will operate, but the “Open Switch” command will not be executed. FLEXLOGIC Auto Sectionalizing function of the DGCS controls 7 Flexlogic operands: OC FOL BY PWR LOSS TRIP COUNT = 0 TRIP COUNT = 1 TRIP COUNT = 2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–53

S3 CONFIGURATION

CHAPTER 6: SETTINGS

TRIP COUNT = 3 TRIP COUNT = 4 TRIP COUNT = 5 The Auto Sectionalizing function of the DGCS uses 4 Flexlogic operands that are controlled by other elements: Phase IOC A OP (from Phase IOC element) Phase IOC B OP (from Phase IOC element) Phase IOC C OP (from Phase IOC element) NTRL IOC OP (from NTRL IOC element)

PATH: SETTINGS > S3 CONFIGURATION > AUTO SECTIONALIZING AUTO SECT FUNCTION Range: Enabled, Disabled Default: Disabled This setting enables the Auto Sectionalizing function. IOC DPO TIME DELAY Range: 0.05 to 5.00 s in steps of 0.01 s Default: 0.20 s When the overcurrent condition is detected, the IOC STATE alarm will be asserted. When the overcurrent condition clears, the IOC STATE alarm will stay active for the time selected in this setup. Within this time the condition ‘Overcurrent followed by power supply loss’ will be detected. CB STATE INFO Range: Local, Remote Default: Local This setting selects the means of getting information on the circuit breaker state (opened or closed). Local: Comparing currents and voltages with the minimum threshold. Remote: Reading selected Contact Input (1 to x), Virtual Input (1 to 32), or Virtual Output (1 to 32). In addition, currents and voltages are compared with the minimum threshold to decide on the state of the circuit breaker. CB TYPE Range: 1 Unit (3-Pole), 3 Units (1-Pole) Default: 1 Unit (3-Pole) This setting has to match the type of circuit breaker installed on the source side of the feeder.

6–54

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

TRIP COUNT LIMIT Range: 1 to 5 in steps of 1 Default: 2 This setting sets the number of CB trip cycles before the switch open command is initiated. For the last switch on the feeder (furthermost from the circuit breaker) the limit should be set to 2. The limit for the second last switch should be set to 3. The limit for the third last switch should be set to 4. AUTO SECT MODE Range: Timing mode, Counting mode Default: Counting mode This setting selects the mode of Auto Sectionalizing. In Timing mode, ‘Auto Sect Delay’ time should be set to the lowest value for the last switch on the feeder (furthermost from the circuit breaker). For the second last switch, the time should be longer, continuing in the same way to the first switch on the feeder. AUTO SECT DELAY Range: 0.1 to 60.0 s in steps of 0.1s Default: 0.2 s This setting selects the time delay between issuing and executing the Auto Sectionalizing command. REVERSE PWR DETECT Range: Enabled, Disabled Default: Disabled This setting selects the detection of the reverse power. When enabled, a reverse power condition triggers the message “REVERSE POWER.” REVERSE PWR PKP Range: 0 to -50000 kW in steps of 1kW Default: -50 kW This setting selects the pickup level for the reverse power detection. It is recommended to avoid setting zero for the pickup level since in that case the ‘no load’ condition will be interpreted as a ‘reverse power’ condition. REVERSE PWR DELAY Range: 0.0 to 60.0 s in steps of 0.1 s Default: 0.5 s This setting delays the reverse power detection. Reverse power has to be lower than the pickup value for more than the time in this setting, before the REVERSE POWER message is asserted. AUTO SECT TIMEOUT Range: 6 to 600 in steps of 1s Default: 60 s The Auto Sectionalizing sequence must be complete before this time elapses. If the time expires before the completion of the sequence, the sequence will reset. This time should be equal to the duration of the breaker switching sequence.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–55

S3 CONFIGURATION

CHAPTER 6: SETTINGS

Figure 6-20: Auto Sectionalizing logic diagram - 1 of 2 SETTING

AS enabled

AUTO SECT FUNCTION

To page 2

ENABLED = 1

Phase IOC A OP (from Phase IOC element) IOC DPO TIME DELAY

FLEXLOGIC OPERAND

AND

AND

Phase IOC C OP(from Phase IOC element)

SETTING

OR

Phase IOC B OP(from Phase IOC element)

0 200 ms

OC FOL BY PWR LOSS

NTRL IOC OP(from Neutral IOC element)

Event recorder FLEXLOGIC OPERAND Pwr Loss Src OP

Alarm: IOC STATE

FLEXLOGIC OPERAND Pwr Loss Src Ph A OP

OR

Pwr Loss Src Ph B OP

OR

FLEXLOGIC OPERAND

FLEXLOGIC OPERAND Pwr Loss Src Ph C OP

AND

Power loss

SETTING (SYSTEM SETUP) SWITCH TYPE NO LOAD = 0 LOAD = 1

AND

SETTING (SYSTEM SETUP) CB STATE INFO REMOTE = 0 LOCAL = 1

AND

AND

(from SYSTEM SETUP) Status: CBa CLOSED(selected source) Status: CBb CLOSED (selected source)

OR

AND

OR

SETTING (SYSTEM SETUP) CB TYPE

OR

Status: CBc CLOSED (selected source)

3 UNITS(1 POLE) = 0 1 UNIT (3POLE) = 1

6–56

AND

(from SYSTEM SETUP) Status: CB(3pole) CLOSED (selected source)

891869.cdr

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL Remote reset(from comms)

Manual reset

AS enabled

RESET SHOT COUNTER

TRIP COUNT = 1 TRIP COUNT = 0

1 0

SETTING REVERSE PWR PKP

OR

Alarm: AS LOCKOUT

R

LATCH

S

REVERSE PWR DETECT ENABLE = 1

SETTING

REAL POWER=< REVERSE POWER PKP

RUN

Power loss

100 ms

0

AUTO SECT TIMEOUT

6.0 s

AS switch open command (to Switch control logic element)

Message: REVERSE POWER

Event recorder

0

LED: ALARM

891870.cdr

Message: AUTO SECT TIMEOUT

Event recorder

Alarm: FIRST AS TRIP

SETTING

0

SETTING REVERSE PWR DELAY

500 ms

SETTING AUTO SECT DELAY

LED: AUTOSECTIONALIZING LOCKOUT

AND

From page1

TRIP COUNT = 4 TRIP COUNT = 3 TRIP COUNT = 2

4 3 2

INCREMENT SHOT COUNTER

SHOT COUNTER

FLEXLOGIC OPERANDS TRIP COUNT = 5

REAL POWER

From page 1

AND

ACTUAL VALUE

TRIP COUNT >= 1

OR

COUNT 5

RUN

AND

ACTUAL VALUE TRIP COUNT

TIMING MODE = 0 COUNTING MODE = 1

SETTING AUTO SECT MODE

TRIP COUNT >= TRIP COUNT LIMIT

RUN

SETTING TRIP COUNT LIMIT

AND

FLEXLOGIC OPERAND OC FOL BY PWR LOSS

From page1

AS enabled

CHAPTER 6: SETTINGS S3 CONFIGURATION

Figure 6-21: Auto Sectionalizing logic diagram - 2 of 2

OR

Wearing monitor

The DGCS provides counters for counting the switch OPEN and CLOSE actions. Every new OPEN action increments the content of the Flexlogic variable SWITCH OPEN COUNT. Equally, every new CLOSE action increments the content of the Flexlogic variable SWITCH CLOSE COUNT. Both variables are located in MAINTENANCE / M3 COUNTERS. The user can select the limit for each action separately. When a limit has been reached, a corresponding message is produced.

6–57

S3 CONFIGURATION

CHAPTER 6: SETTINGS

The DGCS is provided with an Arcing Current Counter that calculates the energy of the arc created for every switch open action. The calculation is performed for each phase and it is based on the instantaneous value of the KI2t being integrated for the duration of the switch open action. Furthermore, the controller adds up the arc energy of every new switch open action, creating an accumulated count of this quantity for a long period of time. The accumulated arcing energy of phase A is saved in the Flexlogic variable KI2t SW COUNT PH A, as is the accumulated arcing energy of phases B and C. The controller provides for setting the limit for arcing energy and if any of the phases’ arcing energy value exceeds this limit, the alarm message is triggered. Usually, the switch manufacturer provides the maximum KI2t value and when this value is reached, the switch has to be repaired. This makes the Arcing Current function a very useful maintenance tool. The logic diagrams for the Switch Action Counter and the Arcing Current Counter are shown below.

PATH: SETTINGS > S3 CONFIGURATION > WEARING MONITOR ACT CNTR FUNCT Default: Disabled Range: Enabled, Disabled This setting enables the functionality of the Switch Action Counter. It has two separate parts: one for counting open actions, and another for counting close actions of the switch. When enabled, every open or close action of the switch results in incrementing of the open or close count respectively. OPEN CNTER LIMIT Default: 9999 Range: 1 to 9999 Steps 1 This is the maximum number of openings allowed for the controlled switch. When this value is exceeded, the message OP CNT LIM REACHED appears to signal this issue. Once the message is activated, it can be removed by resetting the open counter. The path of the reset command is: MAINTENANCE / M3 STATISTICS/ RESET COUNTERS / RESET OPEN COUNT. When the limit of 9999 is reached the Open Counter starts from zero. CLOSE CNTER LIMIT Default: 9999 Range: 1 to 9999 Steps 1 This is the maximum number of closings allowed for the controlled switch. When this value is exceeded, the message CL CNT LIM REACHED appears to signal this issue. Once the message is activated, it can be removed by resetting the open counter. The path to the reset command is: MAINTENANCE / M3 STATISTICS / RESET COUNTERS / RESET CLOSE COUNT. When the limit of 9999 is reached the Close Counter starts from zero. ARC CURRENT FUNCT Default: Disabled Range: Enabled, Disabled This setting enables the functionality of the Arcing Current Counter.

6–58

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S3 CONFIGURATION

ARC CURRENT BLOCK Default: Disabled Range: Off, Contact Inputs 1 to x, Virtual Input 1 to 32, Virtual Output 1 to 32 This setting blocks the functionality of the Arcing Current Counter. KI2t MAXIMUM LIMIT Default: 9999.99 Range: 0 to 9999.99 Steps: 0.01(KA)2s This setting is programmed with the maximum I2t accumulated value. If the KI2t counter of one phase exceeds this level, a message KI2T LIMIT REACHED will appear to signal this issue. Once the message is activated, it can be removed by resetting the KI2t counter. The path to the reset command is: MAINTENANCE / M3 RESET COUNTERS / RESET SW KI2t COUNT. KI2t INTEGRAL TIME Default: 0.03s Range: 0.03 to 0.25s Steps: 0.01s. This is the integration time taken as the base (fixed opening time) for the calculation of KI2t. It should be set to the estimated duration of the arcing event.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–59

6–60 SETPOINT

SETPOINT

Yes

No = 0

RESET CLOSE COUNT

COMMAND (M3 RESET COUNTERS)

SWITCH CLOSED

FLEXLOGIC OPERAND

INI CLOSE COUNT

Yes

No = 0

RESET OPEN COUNT

COMMAND (M3 RESET COUNTERS)

SWITCH OPENED

FLEXLOGIC OPERAND

INI OPEN COUNT

SETPOINT

Enabled = 1

ACT CNTR FUNCT

ACTUAL VALUES

Counter = Initial count + new count

Counter= Initial count + new count

Set to Zero

Increment Counter

Initial Count

CLOSE COUNT

ACTUAL VALUES

Set to Zero

Increment Counter

Initial Count

OPEN COUNT

SETPOINT

SETPOINT

TOTAL = LIMIT

RUN

TOTAL = LIMIT

CLOSE CNTER LIMIT

RUN

OPEN CNTER LIMIT

891871.cdr

Event Recorder

CL CNT LIM REACHED

Message

Event Recorder

OP CNT LIM REACHED

Message

S3 CONFIGURATION CHAPTER 6: SETTINGS

Figure 6-22: Switch Action Counter logic diagram

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

SETTING

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

Disabled= 0

RESET SW KI2t COUNT

COMMAND(M4 RESET)

Phase A Current(Ic)

Phase A Current(Ib)

Phase A Current (Ia)

SWITCH OPEN

FLEXLOGIC

Disabled= 0

SW ARC CURR BLOCK :

SETTING

Enabled= 1

Disabled= 0

SW ARC CURR FUNC :

Freeze currents

Ph C

Ph B

Ph A

LATCH LATCH

AND

AND

OR

SETTING

↑ T, sec

KI2t INTEGRAL TIME :

AND

AND

AND



RUN

RUN

RUN

100 ms

KI2t Integrate

KI2t Integrate

KI2t Integrate

Set All To Zero

IC2 t

2

2

IB t

IA t

Add to Accumulator

KI2t SW COUNT PH C

KI2t SW COUNT PH B

KI2t SW COUNT PH A

COUNTERS

Select Highest Value

2

S(KA) t > Limit

LATCH KI2t MAX LIMIT

891872.cdr

FlexLogic Operands & Event recorder

KI2t LIMIT REACHED

LED: ALARM

CHAPTER 6: SETTINGS S3 CONFIGURATION

Figure 6-23: Arcing Current Counter logic diagram

6–61

S4 CONTROLS

CHAPTER 6: SETTINGS

S4 Controls

Remote control

PATH: SETTINGS > S4 CONTROLS > REMOTE CONTROL REMOTE OPEN Range: Off, Contact Input, Virtual Input, Virtual Output Default: Off This setting defines the input to trigger the open command to the switch. This input can be selected from the list of inputs including contact inputs, virtual inputs, protection or control operand, as well as input flags received from SCADA, or IEDs. REMOTE CLOSE Range: Off, Contact Input, Virtual Input, Virtual Output Default: Disabled This setting defines the input to trigger the close command to the switch. This input can be selected from the list of inputs including contact inputs, virtual inputs, protection or control operand, as well as input flags received from SCADA, or IEDs. REMOTE RESET Range: Off, Contact Input, Virtual Input, Virtual Output Default: Off This setting is used to reset the LEDs, alarms and target messages generated during some abnormal condition of the switch. The setting provides the selection of an input from a list of inputs that performs the reset action upon activation. COMM BLOCK AUTO Range: No, Yes Default: No The Auto mode can be blocked remotely by asserting the command COMM BLOCK AUTO via communications. This can be done only by using the DGC PC program while in Remote control. In this case the switch can be controlled only remotely. This command is not visible on the HMI.

6–62

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S4 CONTROLS

SAVE COMM BLK AUTO Range: Disabled, Enabled Default: Disabled While in Remote mode, the user can select to keep the Auto mode blocked during loss of communication or loss of power to the DGC-S, by setting the command SAVE COMM BLK AUTO, to “Enabled”. This will keep the Auto mode blocked after the communication or the power to the DGC-S has been restored. COMM UNBLOCK AUTO Range: No, Yes Default: Yes Both the COMM BLOCK AUTO and the SAVE COMM BLK AUTO selections will reset upon issuing COMM UNBLOCK AUTO command. This command is not visible on the HMI.

Open/Close control

PATH: SETTINGS > S4 CONTROLS > OPEN/CLOSE CONTROL OPEN RESET TIME Range: 0.00 to 600.00s in steps of 0.01 Default: 3.00 s Upon issuing an OPEN command, the output relay “RLY 1 SW OPEN” will energize. Then, after a period of time that depends on the switch design (switch open reaction time), the switch will open. When the switch is detected as opened, a timer starts, and after the time set in S5 / RLY 1 CONTROL / SEAL-IN TIME has elapsed, the output relay “RLY 1 SW OPEN” will de-energize. However, “RLY 1 SW OPEN” will de-energize after the time set in OPEN SW RESET TIME if this time is shorter than the total of, OPEN REACTION TIME + SEAL-IN TIME. BLOCK OPEN CMND Range: Off, Any input from the list of inputs Default: Off This setting defines a block to the Open Switch command. When the selected input is asserted, the output relay “OPEN SWITCH” will be blocked. CLOSE RESET TIME Range: 0.00 to 600.00s in steps of 0.01 Default: 3.00 s Upon issuing a CLOSE command, the output relay “RLY 2 SW CLOSE” will energize. Then, after a period of time that depends on the switch design (switch close reaction time), the switch will close. When the switch is detected as closed, a timer starts, and after the time set in S5 / RLY 2 CONTROL / SEAL-IN TIME has elapsed, the output relay “RLY 2 SW CLOSE” will de-energize. However, “RLY 2 SW CLOSE” will de-energize after the time set in CLOSE SW RESET TIME, if this time is shorter than the total of, CLOSE REACTION TIME + SEAL-IN TIME.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–63

S4 CONTROLS

CHAPTER 6: SETTINGS

BLOCK CLOSE CMND Range: Off, Any input from the list of inputs Default: Off This setting defines a block to the Close Switch command. When the selected input is asserted, the output relay “CLOSE” will be blocked. ALARM FUNCTION Range: Enabled, Disabled Default: Disabled This setting enables the Switch Alarm function. It will allow triggering of the alarm ‘Switch state failed’ according to the ‘Close Switch’ and ‘Switch Monitoring Logic’ tables in the logic diagrams below. ALARM DELAY Range: 0.00 to 600.00s in steps of 0.01 Default: 4.00 s Delays ‘Switch State Failed’ alarm. Output relay 1 has been fixed and is not programmable to operate when the OPEN SWITCH output command is true.

NOTE:

NOTE

6–64

Output relay 2 has been fixed and is not programmable to operate when the CLOSE SWITCH output command is true.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

Pushbutton

SCADA Commands Open Close

Remote Inputs (S4) Remote Control Remote Open Remote Close

Faceplate Pushbuttons or MENU Commands Open Close

Remote Commands Manual Auto Off

From SCADA

Local Remote

PB / USB Commands Manual Auto Off

S

R

>

S

R

>

Q

Q

Q

Q

OR

OR

AND

AND

AND

AND

To Sheets 2&3

LED: REMOTE

CLR

SET

CLR

SET

LED: LOCAL

AND

AND

OR

OR

OR

OR

OR

OR

CLR

SET

CLR

SET

CLR

SET

Q

Q

Q

Q

Q

Q

POWER LOSS

State COMM FAIL ALARM

SETTINGS SAVE COMM BLK Enabled = 1

Remote Commands COMM BLK AUTO COMM UNBLOCK AUTO

AND

Off Mode

OR

LED: MANUAL

OR

AND

Auto Remote

Set Auto LED in blinking mode

STATUS

LED: AUTO

PC Program and SCADA

R

>

S

R

>

S

R

>

S

STATUS Manual Mode

AND

AND

AND

AND

AND

AND

AND

Always Off

OR

OR

R

>

S

CLR

SET

Q

Q

State (EEPROM) COMM BLK AUTO STATE

STATUS Auto Mode

SPARE

AS Switch Open Command

From Auto Sectionalizing Element

AND

AND

OR

OR

891833.cdr (”Sheet 1”)

Close Switch Request To Sheet 3

Open Switch Request To Sheet 2

CHAPTER 6: SETTINGS S4 CONTROLS

Figure 6-24: Switch Control Logic - Sheet 1 of 3

6–65

6–66

SETTING

SETTING

Pwr Loss Src OP

Load = 0

No Load = 1

AND

FLEXLOGIC OPERAND

POSITIVE EDGE DETECTOR

Cmd Open Switch

SETPOINT

0.5 s

SEAL-IN TIME

tRST

SETPOINT

3.0 s tRST

OPEN SW RESET TIME

R

LATCH

S

To Sheet 3

Switch Open Failed

891834.cdr

OR

SWITCH TYPE

SETTING

SETTING Measured Voltages, SW RATED VOLTAGE source side (Va, Vb, Vc, Vab, Vbc, Vca) V > Vrated, KV

I > Irated, A

SW RATED CURRENT

AND

Measured Currents (Ia, Ib, Ic)

FAULT (Spare)

AND

(Selected Input, ON = 1)

LED: BLOCK OPEN SWITCH

AND

Disabled = 0

BLOCK OPEN CMND

SETTING

Enabled = 1

Disabled = 0

BLOCK OPEN SWITCH

PUSHBUTTON

From Sheet 1

AND

Local

To Sheet 3

OR

Open Switch Request

At least one switch contact enabled

Switch Open

LED: SW OPEN

AND

From Sheet 3

Contact Input 1 (F5) State

AND

Enabled

52a CONTACT

SETTING

Contact Input 2 (F6) State

Enabled

52b CONTACT

Open Switch Flag

OPEN SWITCH Operate Form C Output (RLY1 SW OPEN)

S4 CONTROLS CHAPTER 6: SETTINGS

Figure 6-25: Switch Control Logic - Sheet 2 of 3

AND

AND

OR

AND

OR

OR

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

SETTING 52a CONTACT

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL Local

V > Vrated, kV

No Load = 1

Load = 0

SETTING SWITCH TYPE

FLEXLOGIC OPERAND Pwr Loss Load OP

FLEXLOGIC OPERAND Pwr Loss Src OP

XOR

AND

AND

AND

AND

AND

LED: BLOCK CLOSE SWITCH

Measured Voltages, SW RATED VOLTAGE source and Load side (Va, Vb, Vc, Vab, Vbc, Vca)

SETTING

FAULT (AS lockout, OV, UV)

(Selected Input, ON=1)

Disabled = 0

SETTING BLOCK CLOSE CMND

Enabled = 1

Disabled = 0

AND

Close Switch Request

PUSHBUTTON BLOCK CLOSE SWITCH

From Sheet 1

From Sheet 1

Contact Input 2 (F6) State

Enabled

SETTING 52b CONTACT

Contact Input 1 (F5) State

Enabled

From Sheet 2

AND

OR

Enabled = 1

AND

SETTING SW ALARM FUNCTION

4s

SW ALARM DELAY

SETPOINT

AND

AND

OR

Cmd Close Switch

AND

Switch Closed

LED: SWITCH CLOSED

POSITIVE EDGE DETECTOR

0.5 s

SETPOINT SEAL-IN TIME (S5 RLY 2 CONTROL)

At least one switch contact enabled

3.0 s

CLOSE SW RESET TIME

SETPOINT

AND

AND

SW Open Failed From Sheet 2

R

LATCH

S

SW State Failed

LED: SWITCH ALARM

SW Close Failed

891835.cdr

Close Switch Flag

CLOSE SWITCH Operate Form C Output (RLY2 SW CLOSE)

CHAPTER 6: SETTINGS S4 CONTROLS

Figure 6-26: Switch Control Logic - Sheet 3 of 3

Change setpoint group

The DGCS has three identical settings groups - Groups 1, 2, and 3 - for all DGCS monitoring elements. Switching between these three groups is available either automatically by assigning an input (contact, virtual, remote, flexlogic element), or manually through communications. Group 1 is the default setting group. The device can automatically switch from Group 1 DGCS elements to the other group elements, and vice versa, by setting up the switching conditions under “Change Setpoint Group”. Under some application conditions, it may be

6–67

S4 CONTROLS

CHAPTER 6: SETTINGS

undesirable to change settings groups. In such cases, the user can set a condition under “BLK GROUP CHANGE”, where if asserted, the active settings group will stay active, even if the input configured to switch to the other settings group is asserted. For example if the active group was group 1 at any given time, and the input configured under “BLK GROUP CHANGE” is asserted, the relay will maintain settings group 1, even if the input “SET GROUP 2 (3) ACTIVE” is asserted. Visa versa, if the “BLK GROUP CHANGE” input is asserted, the relay will not switch from group 2/3 to group 1, even if the input under “SET GROUP 2 (3) ACTIVE” is de-asserted. The device will default to settings group 1, if both the input “SET GROUP 2 (3) ACTIVE” and the blocking input “BLK GROUP CHANGE” are de-asserted. Table group 3 of settings has a higher priority than the rest of settings groups. That means, if both “SET GROUP 2 ACTIVE” and “SET GROUP 3 ACTIVE” signals are maintained asserted at the same time, the DGCS will change to the table 3 of settings. The logic functionality takes into account this feature.

PATH: SETTINGS > S4 CONTROLS > CHANGE SETPOINT GROUP SET GROUP 2 ACTIVE Range: Off, Contact Input 1 to 12 (Order Code dependent), Virtual Input 1 to 32, Virtual Output 1 to 32 Default: Off This setting selects an input, used to change to Settings Group 2, when asserted. If no group change supervision is selected, the Settings Group 2 will stay active as long as the “SET GROUP 2 ACTIVE” input is asserted, and will revert to group 1 when this input is deasserted. SET GROUP 3 ACTIVE Range: Off, Contact Input 1 to 12 (Order Code dependent), Virtual Input 1 to 32, Virtual Output 1 to 32 Default: Off This setting selects an input, used to change to Settings Group 3, when asserted. If no group change supervision is selected, the Settings Group 3 will stay active as long as the “SET GROUP 3 ACTIVE” input is asserted, and will revert to the default group, when this input is de-asserted. BLK GROUP CHANGE Range: Off, Contact Input 1 to 12 (Order Code dependent), Virtual Input 1 to 32, Virtual Output 1 to 32 Default: Off This setting defines an input that can be used to block changing settings groups. When the assigned input is asserted, changing from one settings group to the other one is blocked.

6–68

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S4 CONTROLS

891991.cdr

Use Setpoint Group 2

(Default Group)

Use Setpoint Group 1

Use Setpoint Group 3

Figure 6-27: Changing Settings groups - logic diagram

OR

OR

OR

AND AND

AND

Off

SETPOINT

SET GROUP 3 ACTIVE

Off

SETPOINT

BLK GROUP CHANGE

Off

SETPOINT

SET GROUP 2 ACTIVE

AND

Virtual inputs There are 32 Virtual Inputs that can be individually programmed to respond to Input commands entered via the relay keypad, or by using communication protocols.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–69

S4 CONTROLS

CHAPTER 6: SETTINGS

SETTINGS > S4 CONTROLS > VIRTUAL INPUT COMMANDS

VIRTUAL INPUT 1 to 32 Range: Off, On Default: Off The state of each virtual input can be controlled under SETTINGS > S4 CONTROL > VIRTUAL INPUT COMMANDS menu. Entering OFF or On in the selected menu window will change the input’s state. See also the Virtual inputs section under S5 Inputs/Outputs.

NOTE:

NOTE

Cold load pickup The DGCS can be programmed to block the instantaneous over-current elements, and raise the pickup level of the time over-current elements, when a cold load condition is detected. The cold load condition is detected during closing of the breaker on a feeder that has been de-energized for a long time. The feeder inrush current and the motor accelerating current during breaker closing may be above some over-current protection settings. The diagram shows the slow decaying of the cold load current starting at about 500% of the nominal current at the time of breaker closing, decaying down to 300% after 1 second, 200% after 2 seconds, and 150% after 3 seconds. Figure 6-28: Cold load pickup

Current (% of nominal)

500

400

300

NORMAL TRIP SETTING 200

X PICKUP

PICKUP

100

OUTAGE 0 -1

0

1

2

3

4

5

6

Time (seconds) LOAD ENERGIZED

6–70

898750.CDR

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S4 CONTROLS

The relay detects Cold Load condition (Cold Load Pickup armed), if the currents on all three phases drop below 3% of the CT nominal rating for the period of time greater, than the Outage Time Before Cold Load setting. The Cold Load condition can be immediately initiated (Outage Time Before Cold Load timer bypassed), by asserting a contact input selected for External CLP Initiate. The second timer Cold Load Pickup Block is used to specify the time of blocking the instantaneous over-current elements, and the time of raised pickup levels of the time overcurrent elements, after breaker closing. The timer starts when at least one of the three phase currents is above 10% of CT nominal. Upon timer expiration, the settings return to normal. The following path is available using the keypad. For instructions on how to use the keypad, please refer to Chapter 3 - Working with the Keypad.

PATH: SETTINGS > S4 CONTROLS > COLD LOAD PICKUP CLP FUNCTION Range: Disabled, Enabled Default: Disabled This setting enables the Cold Load Pickup function. OUTAGE TIME Range: 1 to 1000 min in steps of 1 min Default: 20 min This timer starts when the feeder is de-energized (currents drop below 3% of CT nominal). The Cold Load Pickup is armed after the time expires. CLP BLOCKING TIME Range: 1 to 1000 s in steps of 1 s Default: 5 s This setting sets the blocking time for the selected Instantaneous Overcurrent elements, and the raised pickup level time for the Time Overcurrent elements. This timer starts when currents greater than 10% of CT nominal are detected. CLP EXT INITIATE Range: Off, Contact Input 1 to 8, Virtual Input 1 to 32, Virtual Output 1 to 32 Default: Off This setting allows the user to select Contact Input, Virtual Input/Output and force the CLP element into the Cold Load Pickup armed state, bypassing the timer Outage Time. BLOCK PH IOC/BLOCK NTRL IOC/BLOCK OV/BLOCK UV Range: No, Yes Default: No Each element on the list can be selected for block or not, upon a Cold Load Pickup condition.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–71

S4 CONTROLS

CHAPTER 6: SETTINGS

SELECT SP GROUP Range: Active Group, Group 1, Group 2, Group 3 Default: Active Group The CLP blocking function will block the IOC and adjust the TOC pickup levels for the Overcurrent elements from whichever Setting Group is active, if the Active Group for that setting is selected. RAISE PH TOC PKP Range: 0 to 100% in steps of 1% Default: 0% The pickup level of the TOC element can be raised by 0 to 100% upon a Cold Load Pickup condition.

6–72

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

Ia < 3% CT

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

Enabled

Disabled

CLP FUNCTION:

SETTING

RUN SELECTED PERCENTAGE

RESET

Cold Load Pickup armed

SETPOINT SETTING

Block

Block

AND AND AND AND

To Phase Time Overcurrent Element

Yes = 1, No = 0

BLOCK UV

SETTING

Yes = 1, No = 0

Block

891832.cdr

Raise by Percent

RAISE PH TOC PKP

SETTING

Group No.

Select Setp Group

SETTING

Cold Load PKP

Message

Record Event

Operate output relays upon selection

Select Group

Select Group

AND

BLOCK OV

Block

LED: ALARM

AND

SETTING

Yes = 1, No = 0

BLOCK NTRL IOC

SETTING

Yes = 1, No = 0

BLOCK PH IOC

SETTING

RUN

ENABLE

CLP BLOCKING TIME

AND

RAISE PH TOC PKP

Ic < 10% CT

Ib < 10% CT

Ia < 10% CT

RUN

ENABLE

OR

SETTING

CLP INITIATE

SETTING

(External Input)

Ic < 3% CT

Ib < 3% CT

SETTING OUTAGE TIME

CHAPTER 6: SETTINGS S4 CONTROLS

Figure 6-29: Cold Load Pickup - logic diagram

OR

AND

AND

6–73

S4 CONTROLS

CHAPTER 6: SETTINGS

FlexLogic™ The DGCS FlexLogic™ system, defines operators, and lists of operands. In essence, all the necessary information for custom built logic. The FlexLogic tool is accessible from the EnerVista DGCS Setup program under the SETTINGS > FLEXLOGIC menu All DGCS digital signal states are represented by FlexLogic™ operands. Each operand is in one of two states: on (asserted, logic 1, or set), or off (de-asserted, logic 0, or reset). There is a FlexLogic™ operand for each contact input, contact output, communications command, control panel command, element trip, and element alarm, as well as many others. A list of FlexLogic™ operands and operators are sequentially processed once every 4.17 ms or 5 ms, depending on the power system frequency (60 Hz or 50 Hz). When list processing encounters an operand, the value of that operand is placed in a first in - first out stack. When list processing encounters a calculation operator, the number of values required for the calculation are removed from the stack, and the result of the operation is placed back on the stack. The operators are logic gates (for example, AND, OR, NOT), timers, latches, one-shots, and assignments. Assignment operators assign the value calculated by the preceding operators to a special class of operands called virtual outputs. Like any other operand, a virtual output can be used as an input to any operator – feedback to achieve seal-in is allowed. When list processing encounters an end operator, processing is stopped until the next processing cycle, at which time it restarts at the top of the list. Each contact output has a setting to specify the operand that drives the output. Any operand may be selected – selection of a virtual output is the means by which FlexLogic™ directly controls external equipment such as the motor contactors. The operators used in FlexLogic™ conform to the following rules: •

512 lines for bulding logic are available in the FlexLogic tool. All lines are executed every 1 / 4 power system cycle (4.17 ms. or 5 ms).



A virtual output may only be assigned once within the FlexLogic environment. An unassigned virtual output will have a value of off.



A maximum of thirty (32) general purpose timers (timers 1 through 32) are available for configuration. Each timer may only be used once within the FlexLogic environment.



A maximum of thirty (30) one-shots is allowed.



A maximum of 16 latches is supported.

The operators available in FlexLogic™ are shown below:

6–74

Operator

Inputs

Description



none

The output value is the value of the named .

NOT

1

The output value is “on” if and only if any of the input values are “off”.

OR

2 to 16 The output value is “on” if and only if any of the input values are “on”.

AND

2 to 16 The output value is “on” if and only if all of the input values are “on”.

NOR

2 to 16 The output value is “on” if and only if all of the input values are “off”.

NAND

2 to 16 The output value is “on” if and only if any of the input values are “off”.

XOR

2

The output value is “on” if and only if one input value is “on” and the other input value is “off”.

TIMER

1

The output value is “on” if the input value has been “on” for the set pickup time. Once the output value is “on”, it remains “on” until the input value has been “off” for the set dropout time.

LATCH

2

The output value is the state of a reset-dominant volatile bi-stable latch, where the first input value is the set input, and the second input value is the reset input.

Positive-one-shot

1

The output value is “on” for one processing cycle following an off-toon transition of the input value.

Negative-one-shot 1

The output value is “on” for one processing cycle following an on-tooff transition of the input value.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

FlexLogic™ operands

S4 CONTROLS

Operator

Inputs

Description

Dual-one-shot

1

The output value is “on” for one processing cycle following either an on-to-off or off-to-on transition of the input value.

ASSIGN 1

The input value is assigned to the named operand. There is otherwise no output value.

END

The first END encountered terminates the current processing cycle.

none

The FlexLogic™ operands available in the DGCS are listed below. Control operands: Group 1 Active OP......................................Activates when Setting Group 1 is applied. Group 1 Active DPO ..................................Activates when the DGCS is switched to a Setting Group different from Group 1. Group 2 Active OP......................................Activates when Setting Group 2 is applied. Group 2 Active DPO ..................................Activates when the DGCS is switched to a Setting Group different from Group 2. Group 3 Active OP......................................Activates when Setting Group 3 is applied. Group 3 Active DPO ..................................Activates when the DGCS is switched to a Setting Group different from Group 3. Auto Ctrl .........................................................Activates when the DGCS is switched to Auto control mode. Remote Ctrl...................................................Activates when the DGCS is switched to Remote control mode. Manual Ctrl ...................................................Activates when the DGCS is switched to Manual control mode. Local Ctrl........................................................Activates when the DGCS is switched to Local control mode. OFF Ctrl...........................................................Activates when the DGCS is switched to OFF control mode. AS Switch Open OP ...................................Activates when the Switch Open command is issued by the AS function. AS Switch Open DPO................................Activates when the Switch Open command drops out. Auto Switch Open......................................Activates when the Switch Open command operates in Auto mode. Manual Switch Open................................Activates when the Switch Open command operates in Manual mode. Auto Switch Close......................................Activates when the Switch Close command operates in Auto mode. Manual Switch Close................................Activates when the Switch Close command operates in Manual mode. Reverse Power OP .....................................Activates when the Reverse Power element operates. Reverse Power DPO..................................Activates when the Reverse Power level drops below the pickup level. Reset Open Count......................................Activates when an Open Count Reset is issued. Reset Close Count......................................Activates when an Close Count Reset is issued. Reset SW I2t .................................................Activates when an Close Count Reset is issued. CBa Closed....................................................Activated when PhA of circuit breaker is in the Closed state. CBa Opened .................................................Activated when PhA of circuit breaker is in the Open state. CBb Closed....................................................Activated when PhB of circuit breaker is in the Closed state. CBb Opened .................................................Activated when PhB of circuit breaker is in the Open state. CBc Closed ....................................................Activated when PhC of circuit breaker is in the Closed state. CBc Opened..................................................Activated when PhC of circuit breaker is in the Open state. CB 3 Closed...................................................Activated when CB 3 Poll is in the Closed state. CB 3 Opened ................................................Activated when CB 3 Poll is in the Open state. Check Battery..............................................Activated when the battery test has failed.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–75

S4 CONTROLS

CHAPTER 6: SETTINGS

Battery to Replace ....................................Activated when the maximum number of consecutive unsuccessful battery tests is reached. Battery Fuse Blown...................................Activated when during a battery test, the blown fuse is detected. Battery Test in Progress..........................Activated during a battery test. Device Shutdown Pickup .......................Activated when device shutdown on AC power loss is enabled, and AC power is lost. Device Shutdown....................................... Input/Output Operands: Contact Input 1 (2 to X) On....................Asserted when the respective Contact Input is activated. Contact Input 1 (2 to X) Off....................Asserted when the respective Contact Input is deactivated. Contact Output 1 (2 to X) On ................Asserted when the respective Contact Output is activated. Contact Output 1 (2 to X) Off................Asserted when the respective Contact Output is deactivated. VI1 (VI1 to VO32) On .................................Asserted when the respective Virtual Input is activated. VI1 (VI2 to VI32) Off ...................................Asserted when the respective Virtual Input is deactivated. VO1 (VO2 to VO32) On .............................Asserted when the respective Virtual Output is activated. VO1Off to VO32 Off...................................Asserted when the respective Virtual Output is deactivated. Alarm Operands: Any Alarm OP...............................................Activates when any Alarm Operand is asserted (logic 1). Not Configured...........................................Activates when the DGC status is “Not Configured” under INSTALLATION/PRODUCT STATUS. Self-test Alarm OP.....................................Activates when the CB detects a Self-Test error. Comm Fail Alarm OP................................Activates when the communication channel fails. IOC State Alarm OP...................................Activates when the IOC State Alarm operates. IOC State Alarm DPO ...............................Activates when the IOC State Alarm drops out. OC FOL BY PWR LOSS OP.......................Activates when OC FO BY PWR LOSS operates. OC FOL BY PWR LOSS DPO....................Activates when OC FO BY PWR LOSS drops out. First AS Trip Alarm OP..............................Activates when the First AS Trip Alarm operates. First AS Trip Alarm DPO ..........................Activates when the First AS Trip Alarm drops out. AS Lockout Alarm OP...............................Activates when AS Lockout Alarm operates. AS Lockout Alarm DPO............................Activates when AS Lockout Alarm drops out. Auto Sect Timeout OP .............................Activates when Auto Sect Timeout operates. Auto Sect Timeout DPO..........................Activates when Auto Sect Timeout drops out. Ph A IOC Alarm OP ....................................Activates when Phase A IOC operates. Ph B IOC Alarm OP ....................................Activates when Phase B IOC operates. Ph C IOC Alarm OP ....................................Activates when Phase C IOC operates. Ph IOC Alarm DPO .....................................Activates when Phase IOC drops out. Ph A TOC Alarm OP ...................................Activates when Phase A TOC operates. Ph B TOC Alarm OP ...................................Activates when Phase B TOC operates. Ph C TOC Alarm OP ...................................Activates when Phase C TOC operates. Ph TOC Alarm DPO....................................Activates when Phase TOC drops out. NTRL IOC Alarm OP...................................Activates when NTRL IOC operates. NTRL IOC Alarm DPO................................Activates when NTRL IOC drops out. Ph OV Alarm OP..........................................Activates when Phase OV operates. Ph OV Alarm DPO.......................................Activates when Phase OV drops out. Ph UV Alarm OP..........................................Activates when Phase UV operates. Ph UV Alarm DPO.......................................Activates when Phase UV drops out. Volt UNBAL Alarm OP...............................Activates when Voltage UNBAL operates.

6–76

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S4 CONTROLS

Volt UNBAL Alarm DPO ...........................Activates when Voltage UNBAL drops out. CLP Alarm PKP.............................................Activates when CLP picks up. CLP Alarm OP...............................................Activates when CLP operates. CLP Alarm DPO............................................Activates when CLP drops out. Pwr Loss Src A, B, C OP............................Activates when Power Loss on phase A, B, C of source voltage side operates. Vol Loss Src PKP..........................................Activates when Voltage Loss on source voltage side picks up. Vol Loss Src Ph A, B, C OP.......................Activates when Voltage Loss on phase A, B, C operates. Pwr Loss Load A, B, C OP........................Activates when Power Loss on phase A, B, C of load voltage side operates. Vol Loss Load PKP......................................Activates when Voltage Loss on load voltage side picks up. Vol Loss Load Ph A, B, C OP...................Activates when Voltage Loss on phase A, B, C of load voltage side operates. Switch Open.................................................Activates when Switch is in Open state. Switch Closed ..............................................Activates when Switch is in Closed state. Switch Open Failed OP ............................Activates when Switch Open Failed operates. Switch Close Failed OP............................Activates when Switch Close Failed operates. Switch State Failed OP ............................Activates when Switch State Failed operates. OP Cnt Lim Reached OP..........................Activates when the total open operations limit has been reached. CL Cnt Lim Reached OP ..........................Activates when the total close operations limit has been reached. KI2t Limit Reached OP.............................Activates when the total KI2t value limit has been reached.. Block and Inhibit Operands: Group Change Block OP .........................Activates when the input programmed to block group change is energized. Group Change Block DPO......................Activates when the input programmed to block group change is de-energized. CLP PhIOC1 Blk OP ....................................Activated when the CLP Ph IOC block operates. CLP PhIOC1 Blk DPO.................................Activated when the CLP Ph IOC block drops out. CLP NeIOC1 Blk OP....................................Activated when the CLP Neutral IOC block operates. CLP NeIOC1 Blk DPO.................................Activated when the CLP Neutral IOC block drops out. CLP OV Blk OP..............................................Activated when the CLP OV block operates. CLP OV Blk DPO...........................................Activated when the CLP OV block drops out. CLP UV Blk OP..............................................Activated when the CLP UV block operates. CLP UV Blk DPO...........................................Activated when the CLP UV block drops out. Ph IOC Block OP..........................................Activated when the Phase IOC block operates. Ph IOC Block DPO.......................................Activated when the Phase IOC block drops out. Ph TOC Block OP.........................................Activated when the Phase TOC block operates. Ph TOC Block DPO......................................Activated when the Phase TOC block drops out. Ntrl IOC Block OP........................................Activated when the Neutral IOC block operates. Ntrl IOC Block DPO ....................................Activated when the Neutral IOC block drops out. Sw Arc Curr Block OP ...............................Activated when the Sw Arcing Current function is blocked. Sw Arc Curr Block DPO............................Activated when the Sw Arcing Current function drops out. Ph OV Block OP ...........................................Activated when the Phase OV block operates. Ph OV Block DPO........................................Activated when the Phase OV block drops out. Ph UV Block OP ...........................................Activated when the Phase UV block operates. Ph UV Block DPO........................................Activated when the Phase UV block drops out. Volt UNBAL Blk OP .....................................Activated when the Voltage Unbalance block operates.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–77

S5 INPUTS/OUTPUTS

CHAPTER 6: SETTINGS

Volt UNBAL Blk DPO..................................Activated when the Voltage Unbalance block drops out. Block Open Switch OP.............................Activated when the DGCS Block Open Switch operates. Block Open Switch DPO..........................Activated when the DGCS Block Open Switch drops out. Block Close Switch OP.............................Activated when the DGCS Block Close Switch operates. Block Close Switch DPO..........................Activated when the DGCS Block Close Switch drops out.

S5 Inputs/Outputs

Contact inputs The relay is equipped with six (6) contact inputs, which can be used to provide a variety of functions such as for circuit breaker control, external trips, blocking of protection elements, etc. A further twelve (12) contact inputs can be added with the purchase of another IO_C board (see the Order Codes section). All contact inputs are wet type contacts (refer to the typical wiring diagram) that require an external voltage source.

PATH: SETTINGS > S5 INPUTS/OUTPUTS > CONTACT INPUTS CONTACT INPUT 1 Range: Fourteen Characters Default: 52a Contact CONTACT INPUT 2 Range: Fourteen Characters Default: 52b Contact CONTACT INPUT X [3 to 18] Range: Fourteen Characters Default: Input X (Exceptions: 7=Battery Fuse, 8=Battery Plus) Each of the contact inputs can be named to reflect the function it represents within the application. Up to 14 alpha-numeric characters are available for names.

6–78

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S5 INPUTS/OUTPUTS

Output relays The DGCS is equipped with fourteen electromechanical output relays: 2 form A control relays (Relay 1 — Switch Open, and Relay 2 — Switch Close), and up to 12 Auxiliary relays depending on the ordered configuration (see the Order Codes section).

PATH: SETTINGS > S5 INPUTS/OUTPUTS > OUTPUT RELAYS Control Relay "RLY 1 SW OPEN" Range: Any alpha-numeric combination, 14 characters long Default: RLY 1 SW OPEN This relay is dedicated to the switch open output function and that cannot be changed. SEAL-IN TIME Range: 0.00 to 9.99 s, Step 0.01 s Default: 0.5 s Refer to the “Switch control” section and Figure 24. Control Relay "RLY 2 SW CLOSE" Range: Any alpha-numeric combination, 14 characters long Default: RLY 2 SW CLOSE This relay is dedicated to the switch close output function and that cannot be changed. SEAL-IN TIME Range: 0.00 to 9.99 s, Step 0.01 s Default: 0.5 s Refer to the “Switch control” section and Figure 25. Auxiliary Relay 3 “BATT CHARGING” Range: Any alpha-numeric combination, 14 characters long Default: BATT CHARGING This relay is dedicated to the battery charging output function and that cannot be changed. Refer to the “Battery backup” section and Figure 7. Auxiliary Relay 4 “BATT TESTING” Range: Any alpha-numeric combination, 14 characters long Default: BATT TESTING This relay is dedicated to the battery testing output function and that cannot be changed. Refer to the “Battery backup” section and Figure 7. Auxiliary Relay 5 to 14 Range: Any alpha-numeric combination, 14 characters long Default: Relay 5 (to 14) FUNCTION Range: Off, Contact Input 1 to 12 On, Contact Input 1 to 12 Off, Contact Output 1 to 8 On, Contact Output 1 to 8 Off, Virtual Input 1 to 32 On, Virtual Input 1 to 32 Off, Virtual Output 1 to 32 On, Virtual Output 1 to 32 Off, Any Alarm OP, Any monitoring function output OP or DPO, Any power loss condition OP or DPO, Any counter limit reached, Any block command OP or DPO, Any Switch and breaker state, Any Mode selected, Any group active.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–79

S5 INPUTS/OUTPUTS

CHAPTER 6: SETTINGS

Refer to DGCS Communications guide for the complete list of functions available for selection.

NOTE:

NOTE

Default: Off The auxiliary relay state is equal to the value of the selected function variable. TYPE Range: Self-Reset, Latched Default: Self-Reset Each auxiliary relay can be selected as either Self-Reset, or Latched. If the Self-Reset type is selected, the output relay is energized as long as the element is in operating mode and will reset when the element drops out. If the Latched type is selected, the output relay stays energized, after the element dropout, and will be de-energized upon the reset command. If an auxiliary output is only required while the activating condition is present, select Self-Reset. Once an activating condition disappears, the auxiliary relay returns to the non-active state and the associated message automatically clears. To ensure all auxiliary function conditions are acknowledged, select Latched. OPERATION Range: Failsafe, Non-Failsafe Default: Non-Failsafe The auxiliary relay state is equal to the value of the selected function variable.When Failsafe operation is selected, the auxiliary relay is energized or de-energized (state change) depending on the following conditions: 1. The auxiliary relay is de-energized, if the relay is not IN SERVICE or the control power is not applied to the relay. 2. The auxiliary relay is energized when the control power is applied to the relay and the relay is IN SERVICE mode. 3. The auxiliary relay stays de-energized, when the control power is applied, upon major self-test failure during relay boot up. 4. The auxiliary relay changes state from energized to de-energized if the DGCS experiences any major self-test failure.

Output Relay "RLY 1 SW OPEN"

This relay is dedicated to the switch open output function and that cannot be changed. PATH: SETTINGS > S5 INPUTS/OUTPUTS > OUTPUT RELAYS NAME Range: Any alpha-numeric combination, 14 characters long Default: RLY 1 SW OPEN The name setting is used to change the name of this relay from “RLY 1 SW OPEN” to a different one, for example “RELAY 1”. SEAL-IN TIME Range: 0.00 to 9.99 s, Step 0.01 s Default: 0.5 s Refer to the “Switch control” section and Figure 24.

Output Relay "RLY 2 SW CLOSE"

6–80

This relay is dedicated to the switch close output function and that cannot be changed. PATH: SETTINGS > S5 INPUTS/OUTPUTS > OUTPUT RELAYS

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S5 INPUTS/OUTPUTS

NAME Range: Any alpha-numeric combination, 14 characters long Default: RLY 2 SW CLOSE The name setting is used to change the name of this relay from “RLY 2 SW CLOSE” to a different one, for example “RELAY 2”. SEAL-IN TIME Range: 0.00 to 9.99 s, Step 0.01 s Default: 0.5 s Refer to the “Switch control” section and Figure 25.

Auxiliary Relay 3 "BATT CHARGING"

This relay is dedicated to the battery charging output function and that cannot be changed. PATH: SETTINGS > S5 INPUTS/OUTPUTS > OUTPUT RELAYS NAME Range: Any alpha-numeric combination, 14 characters long Default: BATT CHARGING The name setting is used to change the name of this relay from “BATT CHARGING” to a different one, for example “BATTERY”. Refer to the “Battery backup” section and Figure 7.

Auxiliary Relay 4 “BATT TESTING”

This relay is dedicated to the battery testing output function and that cannot be changed. Refer to the “Battery backup” section and Figure 7. PATH: SETTINGS > S5 INPUTS/OUTPUTS > OUTPUT RELAYS NAME Range: Any alpha-numeric combination, 14 characters long Default: BATT TESTING The name setting is used to change the name of this relay from “BATT TESTING” to a different one, for example “TESTING”.

Auxiliary Relay 5 to 14

PATH: SETTINGS > S5 INPUTS/OUTPUTS > OUTPUT RELAYS NAME Range: Any alpha-numeric combination, 14 characters long Default: Relay 5 (to 14) The name setting is used to change the name of this relay from “Relay 5 (to 14)” to a different one, for example “RLY FIVE”. FUNCTION Range: Off, Contact Input 1 to 12 On, Contact Input 1 to 12 Off, Contact Output 1 to 8 On, Contact Output 1 to 8 Off, Virtual Input 1 to 32 On, Virtual Input 1 to 32 Off, Virtual Output 1 to 32 On, Virtual Output 1 to 32 Off, Any Alarm OP, Any monitoring function output OP or DPO, Any power loss condition OP or DPO, Any counter limit reached, Any block command OP or DPO, Any Switch and breaker state, Any Mode selected, Any group active. Refer to DGCS Communications guide for the complete list of functions available for selection.

NOTE:

NOTE

Default: Off The auxiliary relay state is equal to the value of the selected function variable.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

6–81

S5 INPUTS/OUTPUTS

CHAPTER 6: SETTINGS

TYPE Range: Self-Reset, Latched Default: Self-Reset Each auxiliary relay can be selected as either Self-Reset, or Latched. If the Self-Reset type is selected, the output relay is energized as long as the element is in operating mode and will reset when the element drops out. If the Latched type is selected, the output relay stays energized, after the element dropout, and will be de-energized upon the reset command. If an auxiliary output is only required while the activating condition is present, select Self-Reset. Once an activating condition disappears, the auxiliary relay returns to the non-active state and the associated message automatically clears. To ensure all auxiliary function conditions are acknowledged, select Latched. OPERATION Range: Failsafe, Non-Failsafe Default: Non-Failsafe The auxiliary relay state is equal to the value of the selected function variable.When Failsafe operation is selected, the auxiliary relay is energized or de-energized (state change) depending on the following conditions: 1. The auxiliary relay is de-energized, if the relay is not IN SERVICE or the control power is not applied to the relay. 2. The auxiliary relay is energized when the control power is applied to the relay and the relay is IN SERVICE mode. 3. The auxiliary relay stays de-energized, when the control power is applied, upon major self-test failure during relay boot up. 4. The auxiliary relay changes state from energized to de-energized if the DGCS experiences any major self-test failure.

Virtual inputs There are 32 Virtual Inputs that can be individually programmed to respond to Input commands entered via the relay keypad, or by using communication protocols. Virtual Input programming begins with enabling the Virtual Input function and selecting the Virtual Input Type - Self-Reset or Latched - under SETTINGS > S5 INPUTS/OUTPUTS. Next, under SETTINGS > S4 CONTROLS > VIRTUAL INPUTS, the user assigns either an On or an Off command to the Virtual Input enabled earlier. Referring to the Virtual Inputs logic diagram below, a Virtual Input type can be selected to be either Self-Reset, or Latched. When Self-Reset is selected, and the command On is executed, the virtual input is evaluated as a pulse at rate of one protection pass. When the Latched type is selected, the On state of the Virtual Input will be latched.

PATH: SETTINGS > S5 INPUTS/OUTPUTS > VIRTUAL INPUTS

6–82

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 6: SETTINGS

S5 INPUTS/OUTPUTS

VI x NAME Range: 18 Characters Default: Virtual IN x This setting defines a programmable name for the Virtual Input. VI x FUNCTION Range: Disabled/Enabled Default: Disabled The Virtual Input is enabled and ready to be triggered when set to Enabled. VI x TYPE Range: Self-Reset, Latched Default: Self-reset When the Self-Reset type is selected, the Virtual Input will be evaluated for one protection pass only, upon “On” initiation and it will reset. When the Latched type is selected, the virtual input will keep the state “On” until reset command “Off” is initiated. See also the Virtual Inputs section under S4 CONTROLS, on how to trigger a virtual input signal state.

NOTE:

NOTE

Figure 6-30: Virtual Inputs Scheme - logic diagram SETTING V INPUT FUNCTION Disabled = 0 Enabled = 1 “Virtual Input 1 to ON = 1”

AND

S SETTING V INPUT1 NAME: (Operand)

LATCH “Virtual Input 1 to OFF = 1”

AND

R OR

V Input1 Status

SETTING V INPUT1 TYPE Latched Self-Reset

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

AND

> 891924.cdr

6–83

S5 INPUTS/OUTPUTS

6–84

CHAPTER 6: SETTINGS

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

GE Digital Energy

Multilin DGCS Switch Controller Chapter 7: Troubleshooting

Troubleshooting

SELF-TEST WARNINGS The DGC Controller performs self diagnostics at initialization (after power up), and continuously as a background task to ensure that every testable unit of the hardware and software is alive and functioning correctly. FASTPATH:

Self-Test Warnings indicate a serious problem with the relay hardware may exist! Follow the table below which contains recommended remedies for fixing errors. If errors persist call the factory.

ERROR CODE

ERROR CODE MEANING

ERROR DESCRIPTION

Error code 1

Ordercode error

This warning occurs Verify all modules on the unit when the DGC Controller are screwed in properly. If fails to match the issue persists call factory installed modules to the ordercode set from factory.

Error code 2

Clock error

This warning occurs Program the DGC when the controller’s Controller’s clock. clock is not programmed.

Error code 4

Calibration error

This warning occurs when the relay has not been factory calibrated.

Send the unit back to the factory for repair.

Error code 8

EEPROM error

EEPROM Hardware failure.

Send the unit back to the factory for repair.

Error code 16

Sys. Health error

Error code 32

IO Comms Fail error

This warning occurs when CPU fails to read serial numbers from installed modules.

Verify all modules on the unit are screwed in properly. If issue still persist call factory.

Error code 64

IO Zero Cross error

This warning occurs when the controller’s Vaux input fails to read valid control power.

Verify the control power wiring to the Vaux inputs is secure, if issue persists call factory.

Error code 128

Frequency error

This warning occurs This is normally caused from when the controller external signals, If issue still measures high frequency persist call factory. fluctuations.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

POSSIBLE REMEDY

7–1

CHAPTER 7: TROUBLESHOOTING

7–2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

GE Digital Energy

Multilin DGCS Switch Controller Chapter 8: Commands

Commands

The DGCS OPEN/CLOSE commands can be used in three different ways: •

OPEN and CLOSE commands from the DGC faceplate pushbuttons or the DGC menu. This method of control is active in Local / Manual mode, providing that the DGCS control is not set to OFF and no other blocks or switching inhibits are applied.



Remote OPEN and CLOSE control upon energizing of assigned inputs under SETTINGS/ CONTROLS/REMOTE CONTROL. This method of control will be active, in Remote / Manual and Remote / Auto mode, providing the DGC–S control is not set to OFF and no other blocks or switching inhibits are applied.



OPEN and CLOSE commands over DNP addresses using radio and the EnerVista DGCS Setup menu. This method of control will be active in Remote / Auto mode, providing the DGCS control is not set to OFF and no other blocks or switching inhibits are applied.

The DGCS RESET command is available on the faceplate keypad button, shown below, and in the Commands menu. Figure 8-1: DGC faceplate OPEN/CLOSE commands

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

8–1

CHAPTER 8: COMMANDS

PATH: MAIN MENU > COMMANDS OPEN Range: No, Yes Default: No This setting is used to open the Switch from the DGC menu. Selecting “Yes” and pressing the ENTER pushbutton from the keypad initiates an OPEN pulse command. The “Yes” command pulse is set to 50ms. CLOSE Range: No, Yes Default: No This setting is used to close the Switch from the DGC menu. Selecting “Yes” and pressing the ENTER pushbutton from the keypad initiates a CLOSE pulse command. The “Yes” command pulse is set to 50ms. RESET Range: No, Yes Default: Disabled This setting is used to reset activated LEDs and any alarms or target messages. Selecting “Yes” and pressing the ENTER pushbutton from the keypad initiates a RESET command. The “Yes” command pulse is set to 50ms. BATT TEST CONT RST Range: No, Yes Default: Disabled It is necessary to execute this command after a defective battery has been replaced with a new one. Selecting ‘Yes’ will set the value of the BATT TEST COUNT to zero. Remote OPEN and CLOSE (upon energizing of inputs selected under SETTINGS/ CONTROLS/REMOTE CONTROL)

8–2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 8: COMMANDS

The Switch OPEN and CLOSE commands received via the selected inputs, are executed if the DGCS control is enabled and the selected control mode is Remote (the Remote LED is lit). The remote OPEN and CLOSE commands are blocked if the “Local” control mode is selected (the “Local” LED is lit) or the corresponding BLOCK command is active. The Remote Reset command can be executed by asserting the selected input when the controller is in Remote mode. PATH: S4 SETPOINTS > CONTROLS > REMOTE CONTROL REMOTE OPEN Range: Off, Contact Input, Virtual Input, Virtual Output Default: Off This setting defines the Input to trigger the OPEN command to the switch. This Input can be selected from the list of Inputs including Contact Inputs, Virtual Inputs, Protection or Control Operand, as well as Input Flags received from SCADA, or IEDs. REMOTE CLOSE Range: Off, Contact Input, Virtual Input, Virtual Output Default: Disabled This setting defines the Input to trigger the CLOSE command to the switch. This Input can be selected from the list of Inputs including Contact Inputs, Virtual Inputs, Protection or Control Operand, as well as Input Flags received from SCADA, or IEDs. REMOTE RESET Range: No, Off, Contact Input, Virtual Input, Virtual Output Default: Off This setting is used to reset the LEDs, alarms, and target messages generated during some abnormal Switch condition. The setting provides for the selection of an Input from a list of Inputs, that performs the RESET action upon activation. OPEN and CLOSE commands over DNP addressing, using radio The OPEN or CLOSE command can be initiated from a SCADA or an IED using radio communication. The controlling device maps an OPEN or CLOSE command to its binary outputs and transmits them via radio communication to the controller. Upon receipt the DGCS controller executes the appropriate action. The DGCS controller executes the received commands, if the controller is not in OFF mode and the selected control mode is set to “Remote” (the Remote LED is lit). The remote OPEN and CLOSE commands via radio, are blocked if the “Local” control mode is selected (the “Local” LED is lit).

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

8–3

CHAPTER 8: COMMANDS

8–4

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

GE Digital Energy

Multilin DGCS Switch Controller Chapter 9: Maintenance

Maintenance

The DGCS allows you to monitor the device for detailed product informations, it’s operating temperature, and collected operational data.

M1 Product information The product information table provides information such as the DGCS name, order code, firmware revision, boot code, serial number, etc. This is the place where one verifies whether updates have been performed correctly on the device.

PATH: MAINTENANCE > M1 PRODUCT INFO PRODUCT NAME Range: alpha-numeric name of up to 18 characters Default: Motor Name ORDER CODE DGC-VEHSSABCDG This screen shows a DGCS Order Code.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

9–1

M2 PRODUCT MAINTENANCE

CHAPTER 9: MAINTENANCE

MAIN FIRMWARE REVISION 1.10 This screen shows the relay Main Firmware Revision. MAIN BUILD DATE Aug 16 2010 This screen shows the relay Main Firmware Build Date. MAIN BUILD TIME 16:32:38 This screen shows the relay Main Firmware Build Time. MAIN BOOT REVISION 1.20 This screen shows the relay Main Boot Code Revision. MAIN BOOT DATE Dec 11 2009 This screen shows the relay Main Boot Code Build Date. MAIN BOOT TIME 10:44:54 This screen shows the relay Main Boot Code Build Time. SERIAL NUMBER ML0A08M00133 Each relay has a unique serial number.

M2 Product maintenance

PATH: MAINTENANCE > M2 PRODUCT MAINTENANCE INTERNAL TEMP 57.0°C 134.6°F This screen displays the actual temperature inside the DGCS.

M3 Statistics

9–2

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

CHAPTER 9: MAINTENANCE

M3 STATISTICS

Counters

PATH: MAINTENANCE > M3 STATISTICS > COUNTERS TRIP CNT Displays the actual trip count from the Auto sectionalizing element. OPEN COUNT Displays the actual count of Switch open actions. CLOSE COUNT Displays the KI2t value for phase A. KI2t COUNT PHA Displays the KI2t value for phase A. KI2t COUNT PHB Displays the KI2t value for phase B. KI2t COUNT PHC Displays the KI2t value for phase C. BATTERY TEST COUNT: Displays the count of unsuccessful battery tests.

Reset counters PATH: MAINTENANCE > M3 STATISTICS > RESET COUNTERS Entering “Yes” into the selected counter menu resets the actual count value.

Preset counters

PATH: MAINTENANCE > M3 STATISTICS > PRESET COUNTERS INI OPEN COUNT Default: 9999 Range: 1 to 9999 Steps 1 This setting is the initial count for the Open Counter. The actual count is added to this number to get the total count. When the SAVE command is sent to the relay, the value is updated into the internal OPEN COUNTER. After power-up the relay keeps the previous counter value, saved in EEPROM, regardless of the stored value of this setting. After a command reset, the counter clears regardless of the value stored in the INI SW OPEN COUNT.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

9–3

M3 STATISTICS

CHAPTER 9: MAINTENANCE

INI CLOSE COUNT Default: 9999 Range: 1 to 9999 Steps 1 This setting is the initial count for the Close Counter. The actual count is added to this number to get the total count. When the SAVE command is sent to the relay, the value is updated into the internal CLOSE COUNTER. After power-up the relay keeps the previous counter value, saved in EEPROM, regardless of the stored value of this setting. After a command reset, the counter will be cleared regardless of the value stored in the INI SW CLOSE COUNT.

9–4

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

GE Digital Energy

Multilin DGCS Switch Controller Appendix A

Appendix A

Appendix A includes the warranty and revision history.

Warranty For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Digital Energy Terms and Conditions at https:// www.gedigitalenergy.com/multilin/warranty.htm For products shipped before 1 October 2013, the standard 24-month warranty applies.

Revision History Change Notes Table 1: Revision History Manual P/N

Revision

Release Date

1601-0260-B1

1.4x

February 2013

1601-0260-B2

1.4x

September 2013

1601-0260-B3

1.4x

January 2014

1601-0260-B5

1.4x

July 2015

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL

A–1

REVISION HISTORY

APPENDIX A

Changes to the DGCS manual Table 2: B5 Updates for the DGCS Manual Section/Page

Description

Chapter 6

Current Sensing section updated.

n/a

Added Chapter 1, renumbered chapters.

n/a

Minor corrections throughout

Table 3: B3 Updates for the DGCS Manual Section/Page

Description

Chapter 5, Battery Backup/ Operating Modes/Run

Added sentence indicating unit cannot be powered by battery only if unit is completely shut-off.

Table 4: B2 Updates for the DGCS Manual

A–2

Section/Page

Description

Chapter 5, Battery Backup

Battery test resistor value corrected to 8 ohm.

MULTILIN DGCS SWITCH CONTROLLER – INSTRUCTION MANUAL