MONUMENT CHEMICAL BRANDENBURG, KENTUCKY May, 2013
Infrared Inspection Report©
Monument Chemical Company Contact James Cherry Project: 03070513 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227 PHONE: 800-737-1787 & 501-228-5001 FAX: 501-228-5001 EMAIL:
[email protected]
ORDER OF REPORT CONTENTS 1: Data To Facilitate Understanding & Utilizing Scan Report 2: Scan Results Overview & Action Taken Form 3: Identified Faulting Conditions, Information & Photographs 4: List Of Facility Equipment Identified By The Customer Representative & Notations Of Faulting Conditions Found
DISCLAIMER This report and the recommendations contained in it are based upon conditions and practices observed and information made available to United Spectrographics personnel. This report does not purport to list all hazards or faulty conditions. It is not intended to indicate that other hazards or faulty conditions do not exist. Severity ratings in the report are based on the criteria shown in this report and are intended as guidelines only. No responsibility is assumed for the control of the facility’s condition, maintenance practices or correction of conditions indicated herein. By issuing this report, neither United Spectrographics nor any of its employees makes any warranty, expressed or implied, concerning the contents of this report. Furthermore, neither United Spectrographics nor any of its employees shall be liable in any manner (other than liability that may be expressed in any policy of insurance that may be issued by United Spectrographics) for personal injury or property damage or loss of any kind arising from or connected with this inspection or failure to inspect.
Utilizing Report Contents Included in this report are Photographs and Thermographs of problem areas found during our recent Infrared Inspection of your facility.
Each problem area picture is accompanied by: Date Location Information Temperature Calculations Color-coded Temperature Intensity and/or Condition Significance Data A Brief Comment Relating The Item In The Photograph To Its Corresponding Thermograph Suggested Corrective Recommendations. In most cases, problems (faults) found will be listed according to the date and order that they were located, rather then by significance or priority, as we feel that you and/or your personnel can best judge this, keeping in mind circuit importance and thermograph intensity.
Thermal intensity is indicated by use of a color-coded data inserts that locate a fault‘s position on the standard electrical failure curve. The color of the insert represents the temperature range of the hottest item, or a portion of the item's circuitry, pointed out in the thermograph. The temperature ranges which the colored inserts represent are grouped as follows: INSERT
Temperature Range
Red
70ºC/126ºF and higher above Ambient Operating Temp.
Orange
40ºC/72ºF to 69ºC/124ºF above Ambient Operating Temp.
Yellow
25ºC/45ºF to 39ºC/70ºF above Ambient Operating Temp.
Green
*10ºC/18ºF to 24ºC/43ºF above Ambient Operating Temp. ( * See page 4)
Determining Cost Effective Responses Electrical equipment failures generally follow a standard mechanical/electrical failure curve. Dividing the failure curve into temp. ranges and locating a problems position on the curve allows us to indicate the probable time to its failure. Knowing a problems probable time to failure allows you to make a cost effective response to the problem areas that we locate. Below is a depiction of the electrical fault failure curve with the thermal intensity ranges and the colors that we assign to faults detailed in our reports.
STANDARD ELECTRICAL FAULT FAILURE CURVE (Does Not Include Area In Blue)
MINOR
10ºC * 18ºF
YEARS
INTERMEDIATE
25ºC 45ºF
SERIOUS
40°C 72ºF
MONTHS
MONTHS TO WEEKS
CRITICAL
70°C 126ºF
WEEKS TO NOW
DEVICE TEMP IS AMBIENT, BUT DEVICE IS EITHER FAULTY OR UNSAFE.
AMBIENT TEMP
FAULTY EQUIP
Built In Trend Monitoring When yearly scans are accomplished, report results allow you to trend monitor your electrical equipment without having to cross reference previous report findings. If a previous years problem is not repaired it will show up again in the current scan report and its current intensity range indicates a current effective response.
Defining Total Temperature and Ambient Operating Temperature And Explanation For Their Use Total Temperature: Total Temperature = Ambient Operating Temperature + Fault temperature Allows you, the customer, to evaluate possible damage to equipment. Leads fail between 90ºC/194ºF and 110ºC/230º Phenolic fails around 200ºC/392ºF Transformers and Motor Insulation failure temperature depends on insulation class rating. Contacts start to fail around 130ºC/266ºF
Ambient Operating Temperature (AOT*) for Infrared Scanning Purposes: Temperature within a device container (Box or Cabinet) that is not directly affected by faulting component = Normal Equipment Operating Temperature Contained By Box or Cabinet. If there is no container (Example: Device mounted to a wall) it is the temperature adjacent to the device not affected by the fault. Allows you, the customer, to determine if device will operate at intended amperage. Most switchgear is rated to operate at approximately 40ºC/104ºF (Industrial) to 50ºC/122ºF (Marine) If AOT is enough above normal rated temperature, either of the following conditions can cause an unanticipated trip. 1. An intermittent high load. 2. A minor (Green) or intermediate (Yellow) fault. Report pages with photographs: PH stands for Visible Light Photograph TH stands for Infrared Light Thermograph * AOT stands for Ambient Operating Temperature Both black & white and color infrared thermographs are presented to better depict the fault condition.
In addition to the corrective response time frame suggested below and the failure curve located on the previous page, you may want to consider using the military standard responses presented below. Military Standard For Evaluating Faults Located In Electrical Equipment Utilizing Temperature Data Obtained With Infrared Imaging Equipment: Temperatures rise above Ambient Operating Temperature: *10ºC/18ºF to 24ºC/43ºF component failure unlikely, but corrective measures required at next scheduled routine maintenance period or as scheduling permits. (Green Label) 25ºC/45ºF to 39ºC/70ºF component failure probable, unless corrected. (Yellow Label) 40ºC/72ºF to 69ºC/124ºF component failure almost certain, unless corrected. (Orange Label) 70ºC/126ºF and above component failure imminent. Immediately inform the person responsi ble for continued operation of equipment. (Red Label) Note: United Spectrographics uses a Blue Label to indicate faults that require attention due to either ambient temperature (Ex: Phase Not Operating), faulty equipment elements or unsafe conditions. * Note: Temperature conditions below 10ºC/18ºF rise above AOT are not considered significant enough to record and are usually not included in the reports.
Fault Correction Recommendation When Our Source Assessment Is Inaccurate: When a fault is indicated in a connection or component and examination by your electrician does not turn up a loose connection or faulty component where we have indicated, a fault does exist. The electrician should continue to investigate the next connection or component to be found in the direction that the heat is coming from until a source is located. Example: If a molded case breaker line side lead connection lug is indicated as a fault source and is found to be secure, but not frozen in place, look for a loose connection or sign of over temp. in the lead holder lug.
SCAN RESULTS OVERVIEW
PROMPT ATTENTION ITEMS: Because of: 1. The intensity or heat level indicated at the time of the scan. 2. Deterioration caused by excessive temperature not present at the time of the scan. 3. Physical condition irregularities observed at the time of the scan. We recommend that the following faults be given prompt attention: Faults: None Noted
Items With Asterisks Have High Total or Ambient Operating Temperatures.
United Spectrographics May, 2013
SUMMARY OF FINDINGS FAULTS BY CATEGORY
NUMBER OF FAULTS
FAULT NO./ITEM NO.
MINOR
1
2/70
INTERMEDIATE
4
1/115 3/168 4/311 5/656
SERIOUS
0
0
CRITICAL
0
0
SERIOUS
0
0
Number of items located at facility: Number of faults:
764 5
ACTION TAKEN Monument Chemical Brandenburg, Kentucky May, 2013
Fault #
Item #
Category
1
115
Intermediate
2
70
Minor
3
168
Intermediate
4
311
Intermediate
5
656
Intermediate
Repaired
Monitor
Date
Name
PROJECT:
03070513
CUST REP: Travis SCAN REP: Chris Wright May 7th, 2013
DATE:
LOCATION: Waste Water Treatment #1 MCC 5B Box Labeled: G-202B Sec. 3E Combination Starter
PH # 1 >
ITEM:
Aø of Motor Control Overload Relay
SOURCE:
Load side lead connection lug.
TEMP:
Temp. of connection and lug is: 63ºC / 145ºF Total Temp - 26ºC / 78ºF AOT = 37ºC / 67ºF above AOT.
TH # 1 >
COMMENTS
TH # 1 >
Abnormal heat is being generated in motor control connection. See yellow arrows in PH#1 and TH#1. Loose and/or corroded contact area. Clean, inspect and re-secure.
TEMPERATURE ABOVE AOT 37°C / 67°F
PROJECT:
03070513
CUST REP: Travis SCAN REP: Chris Wright May 7th, 2013
DATE:
LOCATION: Waste Water Treatment #2 MCC West #1 Box Labeled: G-309A Combination Starter
< PH # 2
ITEM:
Aø of Main Molded Case Breaker
SOURCE:
Line side buss connection lug.
TEMP:
Temp. of connection and lug is: 47ºC / 116ºF Total Temp. - 28ºC / 82ºF AOT = 19ºC / 34ºF above AOT.
< TH # 2
< TH # 2
COMMENTS
Abnormal heat is being generated in case breaker connection. See green arrows in PH#2 and TH#2. Loose and/or corroded contact area. Clean, inspect and re-secure.
TEMPERATURE ABOVE AOT 19°C / 34°F
PROJECT:
03070513
CUST REP: Travis SCAN REP: Chris Wright May 7th, 2013
DATE:
LOCATION: West Tank Farm MCC Room MCC #1 Box Labeled: Filter Tank Hold Tank Pump 15P-98P Combination Starter PH # 3 >
ITEM:
Aø of Motor Lead Terminal Block
SOURCE:
Line side lead connection lug.
TEMP:
Temp. of connection and lug is: 58ºC / 136ºF Total Temp. - 29ºC / 84ºF AOT = 29ºC / 52ºF above AOT.
TH # 3 >
COMMENTS
TH # 3 >
Abnormal heat is being generated in terminal block connection. See yellow arrows in PH#3 and TH#3. Loose and/or corroded contact area. Clean, inspect and re-secure.
TEMPERATURE ABOVE AOT 29°C / 52°F
PROJECT:
03070513
CUST REP: Travis SCAN REP: Chris Wright May 7th, 2013
DATE:
LOCATION: POP Area MCC #2 South Box Labeled; Incoming Main Circuit Breaker Molded Case Breaker
< PH # 4
ITEM:
Bø of Case Breaker
SOURCE:
Line side lead connection lugs.
TEMP:
Temp. of connections and lugs range to: 52ºC / 125ºF Total Temp. - 25ºC / 77ºF AOT = 27ºC / 48ºF above AOT.
< TH # 4
< TH # 4
COMMENTS
Abnormal heat is being generated in case breaker connections. See yellow arrows in PH#4 and TH#4. Loose and/or corroded contact areas. Clean, inspect and re-secure.
TEMPERATURE ABOVE AOT 27°C / 48°F
PROJECT:
03070513
CUST REP: Travis SCAN REP: Chris Wright May 8th, 2013
DATE:
Visible Light Image Was Not Possible. Image Viewed Though IRSS Window.
LOCATION: Outside Glycol Substation Box For: 4160 Incoming Power Fuse Disconnect
PH # 5 >
ITEM:
Aø Fuse Block
SOURCE:
Line side bushing connection.
TEMP:
Temp. of connection is: 56ºC / 132ºF Total Temp. - 29ºC / 84ºF AOT = 27ºC / 48ºF above AOT.
TH # 5 >
COMMENTS
TH # 5 >
Abnormal heat is being generated in fuse block connection. See yellow arrows TH#5. Loose and/or corroded contact area. Clean, inspect and re-secure serviceable components.
TEMPERATURE ABOVE AOT 27°C / 48°F
AREA/EQUIPMENT LIST Following is a list of the electrical equipment located at the Monument Chemical, Brandenburg, Kentucky, facility and data relating to its operating condition at the time the scan was performed.
NOTE: Items noted as visually inspected were not operational or show no visible load at the time of the inspection. No.
Equipment
Oper.
Visually Inspected
EQUIPMENT LIST
POWER HOUSE-BOILER HOUSE 1
Breakers #1-#10 Rear View of Breakers
X
2
Breakers #11-#24 Rear View of Breakers
X
3
MCC #1 Transformer 4160/480 Volt #12313
X
4
Battery Racks
X
5
Rear of Main Switchgear #12134
X
6
Utility Pole Outside of Building
X
MCC #1 7
39DC-14A FD Fan Motor
X
8
P-1 Condensate Pump Drive
X
9
39P-5A BFW Pump Drive
X
10
UPS Breaker
X
11
New Lighting Panel
X
12
39P-5C BFW Pump Drive
13
Atlas Copco Closed Loop Cooling
X
14
DP-5B
X
15
#4 Boiler Feed Water Pump
X
X
MCC #2 16
Spare
X
17
Raw H2O Pump
X
18
A/C Provox Room
X
19
Aux/UPS Breaker
X
20
P-2 Condensate Pump Drive
21
New Light Panel East of CR Door
X X
Fault #
No.
Equipment
Oper.
Visually Inspected
22
Incoming Main Lugs
X
23
Boiler Fan
LOTO
24
39P-5B BFW Pump Drive
LOTO
MAIN SUBSTATION 25
Transformers
X
26
Air Switches
X
27
Lightning Arrestors
X
28
Units 100-111
Did Not Scan
29
Units 116-119
Did Not Scan
30
Units 112-115
Did Not Scan
POLYTERGENT SUBSTATION 31
East Transformer
X
32
West Transformer
X
WASTE WATER TREATMENT #2 33
Panel PP
X
34
Panel LP
X
35
Panel LT PNL
X
36
Outside Transformer
X
MCC East #2 37
Spray Cooler #2 X-305B O.O.S. Sec: 1H
LOTO
38
O.O.S. Sec: 1M
39
G-309E North Basin North Middle Aerator Sec: 2M
40
G-309D Sec: 3M
X
41
G-309C North Basin South West Aerator S/E Sec: 4M
X
42
Receptacle Sec: 5B
X
43
O.O.S. Sec: 5F
Not In Service
44
O.O.S. Sec: 5H
Not In Service
45
G-316A Sec: 5M
X X
X
Fault #
No.
Equipment
Oper.
Visually Inspected
46
P-342B Sec: 6B
47
O.O.S. Sec: 6D
48
HV-1 Sec: 6F
49
G-303B Sec: 6H
LOTO
50
P-319B Sec: 6M
Not In Service
51
P-51 Sec: 7B
X
52
P-319C Sec: 7D
X
53
P-320C Sec: 7M
X
54
O.O.S. Sec: 8B
X
55
UH-2 Sec: 8D
X
56
UH-5 Sec: 8F
X
57
UH-7 Sec: 8H
X
58
UH-9 Sec: 8K
X
59
Spare Sec: 8M
X
60
Tie Breaker Sec: 9E
61
15 KVA Transformer Sec: 9G
62
P-302B Sec: 9M
Fault #
X X X
LOTO X X
MCC West #1 63
Incoming
X
64
P-351 Sec: 1D
65
Flare Fan
Not In Service
66
X-305C Sec: 1M
Not In Service
67
Tie Feeder
LOTO
68
G-309B Sec: 3M
LOTO
69
G-309F Sec: 3M
X
70
G-309A North Basin South East Aerator S/E
X
71
X-500-1/2 Sec: 5B
X
72
O.O.S. Sec: 5F
X
73
O.O.S. Sec: 5H
X
74
G-314A Sec: 5K
X
X
2
No.
Equipment
Oper.
Visually Inspected
75
P-342A Sec: 6D
X
76
P-302A Sec: 6F
X
77
G-303 Sec: 6H
X
78
O.O.S. Sec: 6K
Not In Service
79
Spare Sec: 7B
X
80
P-319A Sec: 7H
81
P-320B Sec: 7K
X
82
P-320A Sec: 7M
X
83
LT PNL Sec: 8B
X
84
Air Comp Sec: 8D
X
85
Recept Sec: 8F
X
86
UH-1 Sec: 8H
X
87
UH-3 Sec: 8K
X
88
UH-4 Sec: 8M
X
89
Lighting Sec: 9F
X
90
DC-2 Sec: 9H
X
91
UH-6 Sec: 9K
X
92
UH-8 Sec: 9M
X
X
WASTE WATER TREATMENT #1 93
Outside Transformer
X
ELECTRICAL ROOM 94
Panel PP-20A
X
95
Panel LP-20C
X
96
Panel HT-20D
X
MCC 5B 97
P-300 Sec: 7A
X
98
Spare
X
99
P-210B Sec: 7C
X
Fault #
No.
Equipment
Oper.
Visually Inspected
100
UH-2 Sec: 6AL
101
SUPR. OFFICE Sec: 6AR
102
P-324C Sec: 6B
X
103
G-201C Sec: 6C S.W. Aerator
X
104
LP-20C Sec: 5AL
X
105
HT-20D Sec: 5AR
X
106
P-202 Sec: 5B
X
107
G-201B Sec: 5C
X
108
EF-3 Sec: 4A
109
P-369 Sec: 4B
110
G-201A Sec: 4C
111
EF-4 Sec: 3A
112
EF-2 Sec: 3B
X
113
P-119A Sec: 3C
X
114
12th St. Shack Sec: 3D
X
115
G-202B Sec: 3E
116
G-202A Sec: 3F
117
AC-1 Sec: 2A
X
118
AR-1 Sec: 2BL
X
119
EHC-1 Sec: 2BR
X
120
IP-20B Sec: 2C
X
121
PP-20A Sec: 2D
X
122
P-206B Sec: 2E
123
P-208B Sec: 2F
X
124
P-208A Sec: 2G
X
125
O.O.S. Sec: 1A
Not in Service
126
F-205B Sec: 1B
X
127
F-201B Sec: 1C
128
FLD Lights/12th St Sec: 1D
Fault #
X X
X LOTO X X
X
1 LOTO
X
X X
No.
Equipment
Oper.
Visually Inspected
MCC 5A 129
P-205A Sec: 1A
X
130
P-201A Sec: 1B
X
131
G-202 Sec: 1C
X
132
MCC-5A Sec: 2A
133
P-205C Sec: 2B
X
134
P-206A Sec: 2C
X
135
P-300E Sec: 2D
X
136
P-324A Sec: 2E
X
137
OH Door #3 Sec: 3AL
X
138
OH Door #4 Sec: 3AR
X
139
OH Door #5 Sec: 3BL
X
140
Press Inst Air Sec: 3BR
X
141
O.O.S. Sec: 3C
X
142
P-324B Sec: 3D
X
143
G-202C Sec: 3E
144
G-202D Sec: 3
X
145
Spare Sec: 4A
X
146
N.W. -S. Basin Aerator G-201F Sec: 4B
147
F-300 Sec: 5A
148
G-201E Sec: 5B
149
Receptacle Motor Room Sec: 6AL
X
150
Receptacle Mechanical Room Sec: 6AR
X
151
UH-1 Sec: 6BL
X
152
UH-3 Sec: 6BR
X
153
G-201D Sec: 6C
LOTO
154
F-202B Sec: 7A
X
155
PM-20-209 Sampling Pump
X
X
X
LOTO X LOTO
Fault #
No.
Equipment
Oper.
156
Pole Lights Sec: 7C
157
P-210A East Lift Station Sec: 7D
Visually Inspected
Fault #
X X
CONTROL ROOM 158
Panel PP-20E
X
159
Panel IP-20B
X
WEST TANK FARM MCC ROOM 160
LP-A
X
161
Feed to UPS Panel
X
162
UPS Fuse Panel
X
MCC #1 163
Incoming Feeder Cables
X
164
G-66E-B Agitator B Class II Polyol Tank Agitator
X
165
375-D Product Transfer Pump 15P-671
X
166
H&V Unit AHU-1
X
167
Class II Polyol Transfer Pump 15P-66B
168
Filter Hold Tank Pump 15P-98P
X
169
X-423 Product Tank Agitator 15G-67B
X
170
X-423 Product Tank Agitator 15G-67C
X
171
X-423 Product Tank Pump 15P-67B
X
172
Filter Circulation Tank Pump 15P-97P
X
173
Evaporator Bottoms Pump 15P-84A
X
174
Evaporator Receiver Tank Agitator 15G-83A
175
Welding Receptacle WR-1-A,B,C
X
176
Feeder Breaker Filter Building LP-F
X
177
Evaporator Receiver Tank Pump 15P-83A
X
178
Evaporator Receiver Tank Pump 15P-83B
X
179
Evaporator Receiver Tank Agitator 15G-83B
X
180
Evaporator Feed Tank Agitator 15G-82B
181
Tank Farm Hoist 15W-64
X
182
Tank Farm Hoist 15W-65
X
X 3
X
X
No.
Equipment
Oper.
Visually Inspected
183
Evaporator Feed Tank Agitator 15G-82A
X
184
Evaporator Feed Pump 15P-82A
X
185
Evaporator Feed Pump 15P-82B
X
186
G-97T AGIT
X
187
98T-Bottom Pump
X
188
Tank Farm Hoist 15W-66
189
Tank Farm Hoist 15W-67
X
190
Filter Hold Tank Agitator 15G-98P
X
191
G-133 Agitator
192
Freon Pump 15P-9
193
Effluent Sump Pump 15P-11B
194
15P-M84
195
Feeder Breaker 45 KVA Transformer #1 LP-A
X
196
Feeder Breaker 15 KVA Transformer LP-D
X
197
Tempered Water Pumps 15P-3D
X
198
G-66E-A Agitator A
X
199
O-TDA Polyol Tank Agitator 15G-66EB
LOTO
200
P-133 Transfer Pump
LOTO
201
15G-M84
X
202
Feeder Breaker Drum Bldg. MCC #3
X
203
Electric Heat AHU#1
X
204
Filter Circ. Tank Agitator 15G-97P
X
205
1320 Product Tank Agitator 15G-67DA
X
206
Condensate Pump 15P-6A
X
X LOTO X X
LOTO
MCC #2 207
Incoming Main Lugs
X
208
P-174 Pump
X
209
98TA-Vacuum Pump
X
Fault #
No.
Equipment
Oper.
Visually Inspected
210
P-97T Transfer Pump
211
Heat Tape M-75
LOTO
212
Heat Tape M-76
X
213
75 Pump
214
76
215
15P-69A Pump
X
216
15G-69A
X
217
G-98T
X
218
807 Product Tank Agitator 15G-66HA
X
219
807 Product Tank Agitator 15G-66HB
X
220
P-66D Transfer Pump
X
221
1320 Product Tank Pump 15P-67D
X
222
X-419 Product Tank Pump 15P-67G
X
223
X-419 Product Tank Agitator 15G-67GA
X
224
Spare
225
W-68 Building Hoist
226
X-419 Product Tank Agitator 15G-67GB
227
807 Product Tank Pump 15P-66H
X
228
375-D Product Tank Agitator 15G-67J
X
229
RF-230 Transfer Pump 15P-66A
230
G-66D-A Agitator A
231
G-66D-B Agitator B
232
X-423 Product Tank Pump 15P-67C
233
1320 Product Tank Agitator 15G-67DB
234
X-419 Product Tank Pump 15P-67F
235
X-419 Product Tank Agitator 15G-67FA
236
Spare
237
804 Product Tank Pump 15P-66J
238
804 Product Tank Agitator 15G-66JA
239
804 Product Tank Agitator 15G-66JB
X
X X
Not In Service X LOTO
X X LOTO X LOTO X X Not In Service LOTO X LOTO
Fault #
No.
Equipment
Oper.
Visually Inspected
240
O-TDA Tank Agitator 15G-66CA
241
O-TDA Tank Agitator 15G-66CB
242
P-66E Transfer Pump
X
243
801 Product Tank Pump 15P-66F
X
244
807 Product Tank Agitator 15G-66FB
245
807 Product Tank Agitator 15G-66FA
X
246
Incoming Feeder Cables
X
247
F-166 Hydraulic Pump
X
248
O-TDA Transfer Pump 15P-66C
X
249
RF-230 Tank Agitator 15G-66A
X
X LOTO
LOTO
MCC #3 250
Incoming Line
X
251
G70
252
P70
253
G131
X
254
P131
X
255
P-134 Transfer Pump
256
P/C West Filter N2 Compressor C-213
X
257
Blank
X
258
Blank
X
259
Blank
X
260
Blank
X
261
G-134 Agitator
X
262
G-102P Agitator
X
263
P-102P Transfer Pump
X
264
15-66K West Agitator
X
265
66K West Agitator
X
266
15G-66KB
X
X X
LOTO
Fault #
No.
Equipment
Oper.
267
15P-66K East Agitator
Visually Inspected X
POP AREA 268
UPS Panel
X
269
240 Volt Panel
X
270
Fuse Cabinet
X
MCC-1 NORTH 271
Incoming Main Circuit Breaker
X
272
Crude BDPO Pump P-206
273
Crude ADPO Agitator AG-206
X
274
BDPO Pump P-205
X
275
Blank
X
276
Crude ADPO Pump P-204
X
277
Crude BDPO Agitator AG-204
X
278
Recycle DPO B Pump P-207
279
Recycle DPO B Agitator P-207
X
280
Recycle DPO A Pump P-208
X
281
Recycle DPO A Agitator AG-208
X
282
Chain Hoist
X
283
Filter Building Transformer
X
284
Wiped Film Evaporator Drive M-251
X
285
New East Pop Sump Pump
286
Spare
X
287
Reactor 101 Mat Transfer Pump P-101
X
288
R-101 Decant to WFE
X
289
DPO Recycle Pump P-106
X
290
2A1 Pump P-203
X
291
Vessel 102 Mat Transfer Pump P-102A
X
292
ADPO Pump P-209
X
293
ADPO Agitator AG-209
X
LOTO
LOTO
X
Fault #
No.
Equipment
Oper.
Visually Inspected
294
Main C/B Distr. Panel
295
Drum Building Distr. Panel
X
296
Sump P-253 S.
X
297
Sump P-252 N.
298
Spare
299
Chiller Transformer
300
LUWA Bottom Pump P-105
X
301
Flood Lights Outside West of 2P1 Fence Line
X
302
Scrubber Bottom Pump M-254P
LOTO
303
Chiller P-109
LOTO
304
Nitrogen Booster Pump N2
X
305
Agitator AG-100
X
306
2A1 P-100
X
307
2A1 P-103
X
308
M-104 P255
X
309
Sump P-257
X
310
Nitrogen Heater N2
X
Fault #
X
X X X
MCC #2 SOUTH 311
Incoming Circuit Breaker
X
4
312
2A1-L Pump P-214
X
313
2A1-L Agitator AG-214
X
314
2A1-L Pump P-215
X
315
2A1-L Agitator AG-215
X
316
2A1-L Acid Pump P-216
X
317
2A1-L Acid Agitator AG-216
X
318
2A1 Acid Pump P-217
X
319
2A1 Acid Agitator AG-217
X
No.
Equipment
Oper.
Visually Inspected
320
2A1 Pump P-218
X
321
2A1 Agitator AG-218
X
322
P-225 NH3 Recovery Pump
323
West Welding Receptacle
324
2A1 Pump P-224B
X
325
H2O Booster Pump
X
326
2A1 Pump P-219
X
327
T-15 Ammonia Heater
X
328
Propylene Tet. Pump P-226
X
329
Dodecene Pump P-227
330
DPO Pump P-228
X
331
DPO Agitator A-228
X
332
50 Percent Caustic Pump P-229
LOTO
333
50 Percent Caustic Agitator AG-229
LOTO
334
Welding Recpt.
X
335
Welding Recpt.
X
336
Tempered H2O Pump P-107
337
Cooling H2O Pump P-108
X
338
P-15
X
339
Dodecene Agitator AG-227
X
340
Propyl Tet AG-226
X
341
CSA Mat Transfer P-225A
LOTO
342
Naoh Mat Transfer P-229A
Not In Service
343
Oil Seal Pump A South
X
344
Oil Seal Pump B North
X
345
2A1 Pump P-223
346
2A1 Pump P-224
X
347
2A1 Pump P-224A
X
348
R-101 Agitator
X
X X
X
LOTO
X
Fault #
No.
Equipment
Oper.
Visually Inspected
349
2A1 Pump P-223A
X
350
Blank
X CONTROL ROOM
351
Panel LP1
X
352
Panel EP1
X
353
Panel CP1
X
2A1 AREA 354
Emergency System Panel
X
355
Relay Cabinet
X
356
DP Panel
X
SOUTH MCC 357
Dryer
X
358
LP-1 Normal Lighting
X
359
Spare
X
360
Flood Lighting Contactor
X
361
DP-1 Feeder Normal Source
X
362
P-25A R-1 Cooling H2O (Hot Oil Pump)
X
363
P-22A R-2 Cooling H2O
X
364
Spare
X
365
P-18B
Not In Service
366
Spare
Not In Service
367
P-40
X
368
G-2 R-2 Agitator
X
369
Styrene/ACN E-Stop Power Supply
X
370
Spare
X
371
P-10 M-10 Pump
X
372
Spare
X
373
P-2 R-2 to R-4
LOTO
Fault #
No.
Equipment
Oper.
Visually Inspected
374
West Pit Pump
X
375
Spare
X
376
Spare
X
377
P-3 R3&4 Stripper Pump
X
378
Spare
X
379
Spare
X
380
South MCC Main Circuit Breaker (Could Not Open)
381
X-56-7 Condensate Return Pump
382
G-3 R-3 Agitator
383
A-56-6 Reactor Product Letdown Drum Agitator
X LOTO X
NORTH MCC 384
Main Circuit Breaker
X
385
Spare
X
386
Spare
X
387
G-4 R-4 Agitator
388
P56-10A R56-I Pump Out
389
C-1A Oil Pump
390
P42 R-1 Seal Fluid Pump
X
391
P-8
X
392
P-20 BFW Pump
LOTO
393
C-1 Compressor
X
394
Spare
X
395
UPS
X
396
P-14
X
397
Spare
398
P-13 IPA
399
Spare
400
P-25B R-1 Cooling H2O Pump
X
401
R-2 Cooling H2O Pump
X
402
G1A
LOTO Not In Service X
Not In Service LOTO X
X
Fault #
No.
Equipment
Oper.
Visually Inspected
403
P1A
X
404
Power Receptacles (Future)
X
405
Welding Receptacles TDA Area
X
406
Spare
X
407
R-1 G-1 Agitator
408
Tank Farm Feeder
X X
L&N AREA 409
Seal Fluid Systems Power Panel
X
410
Distribution Panel LP2-M1-1L
X
411
Substation 21A-LNR
X
21-A-2C-MCC #3 412
Spare
X
413
DP-94R
414
Spare
X
415
Spare
X
416
Spare
X
417
DP-111BA M-111B Agitator “A”
X
418
DP-111BA M-111B Agitator “B”
X
419
DP-111BA M-111B Transfer Pump
X
420
Spare
X
421
Spare
X
422
Spare
X
423
DG-111AA M-111A Agitator “A”
424
DG-111AB M-111A Agitator “B”
425
DP-111A M-111A Transfer Pump
426
Spare
Not In Service
427
Spare
Not In Service
428
Spare
Not In Service
X
LOTO X X
Fault #
No.
Equipment
Oper.
Visually Inspected
429
Incoming Lug Section
430
Spare
431
Sump Pump
432
DP-62N M-62N Transfer Pump
433
Spare
X
434
Spare
X
435
WR1-M3-5GL
X
436
WR2-M3-5GR
X
437
DP-64N M-64N Transfer Pump
X
438
DP-92NA (Spare)
X
439
Hoist 115-DH-1
X
440
Hoist 115-DH 2
X
441
DG-92N
X
442
DG-93N
X X Not In Service X
X
21A-2B-MCC#2 443
Incoming Lug Section
X
444
Spare
445
DP-93N M-93N Transfer Pump
446
DP-61 NA
447
DG-62 NA
X
448
DG-63 NA
X
449
DG-64 NA
450
DP-61N
X
451
DP-63N
X
452
DG-61NB
X
453
Spare
Not In Service
454
Spare
Not In Service
455
Spare
Not In Service
456
Spare
Not In Service
457
Spare
Not In Service
X X LOTO
LOTO
Fault #
No.
Equipment
Oper.
Visually Inspected
21A-1B-MCC #1 458
Incoming Lug Section
X
459
DP-92-L
X
460
DP-93L
X
461
LP2-M1-1L
X
462
DG-92L
X
463
DG-93L
X
464
DP-130A
X
465
DP-130B
X
466
Blank
467
Seal Fluid Systems Transformer
X
468
DG-130B
X
469
DG-130A
X
470
Spare
Not In Service
471
Spare
Not In Service
472
Spare
Not In Service
473
EF1-M1-4A
474
Blank
Not In Service
475
Blank
Not In Service
476
Blank
Not In Service
477
Blank
Not In Service
478
WR3-M1-4k
Not In Service
X
X
OUTSIDE L&N AREA 21A-2D-MCC #7A (SECTION 6) 479
DH3-M7A-6A
X
21A-2D-MCC #7A (SECTION 5) 480
Spare
X
481
DH-1 Dehumidifier Panel
X
Fault #
No.
Equipment
Oper.
Visually Inspected
482
Spare
483
M-204
484
Blank
X
485
Blank
X
X X
21A-2D-MCC #7A (SECTION 4) 486
Blank
X
487
DV-205
X
488
DC-106
X
489
DCD-112
X
490
Spare
X
491
Spare
X
21A-2D-MCC #7A (SECTION 3) 492
DG-93R
X
493
DP-93R
X
494
LP1-M7A-4GL
X
495
PP1-M7A-3GR
X
496
DG-63NB
X
497
DG-62NB
LOTO
21A-2D-MCC #7A (SECTION 2) 498
DG-92R
X
499
DP-92R
500
DG-90R
X
501
DP-90R
X
502
DG-64NB
X
X
21A-2D-MCC #7A (SECTION 1) 503
600 Amp Main Breaker
504
Metering
505
DC101
X X X
Fault #
No.
Equipment
Oper.
Visually Inspected
POLYOL DRUM BUILDING USF COATINGS AREA 506
LP-E Panel
X
507
Allen Bradley MCC
X
MEZZANINE 508
Lighting Panel 1
X
509
Lighting Panel 2
X
510
Unlabeled 120/240 Volt Distribution Panel
X
511
Air Cond. Panel
X
MEZZANINE MCC’S (Select Buckets Only) MCC #1 512
Metering
X
513
A5 Agit (Loc. In 6th Section)
X
MCC #2 514
Metering
X
515
Air Cond. Unit Outside
516
Transformer Loading Recept.
X
517
Lighting XFORMER
X
518
Ints. Transformer
X
X
MCC #3 519
Metering
X
520
West Fan
X
521
East Fan
X
MICRO AREA CENTRAL ELECTRICAL ROOM 522
Light Panel LPB
523
Reactor Agitator Drive (Did Not Open)
X
Fault #
No.
Equipment
Oper.
Visually Inspected
WESTINGHOUSE MCC 524
G-100 Reactor Agitator
X
525
P-100 A R-100 BTMS Pump
X
526
Exhaust Fan Above Centrifuge
X
527
Spare
528
G-201 ADG (Rubber Reactor & Light Panel)
X
529
Light Panel Transformer
X
530
C-110 East Roof Vent Blower
X
531
C-210 Vacuum Pump
X
532
Spare
533
P-201B Rubber Reactor Jacket Circulation Pump
534
“A”
535
P-201D
X
536
700C-2
X
537
T-110B Cold Storage Stanley Refrig. Unit
X
538
C210 New Lower Stage
539
G-200 Rubber Dissolver Activator
540
Main Circuit Breaker
X
541
Metering
X
542
D-2 Tempered Water
X
Not In Service
Not In Service X LOTO
Not In Service X
EAST END ELECTRICAL ROOM 543
240/120 Volt Distribution Panel
X
544
MCC-1
545
Heat Trace Panel XFMR
546
M-306 12 kW Heater
X
547
Spare
X
548
Air Handler Dryer Building
X
549
Roof Vent Fan
X
550
740-P-306 Novalak Filter
X
LOTO
Fault #
No.
Equipment
Oper.
551
740-G-306 Novalak Stg. Tank Agitator
552
P-305-A
X
553
New Hot Oil System
X
554
Spare
X
555
G-302 Agitator
X
556
Out of Service
Not In Service
557
740-G-302D Scrubber Fan
X
558
740P-302D Scrubber Circ. Pump
X
559
740C-303D Exhaust Fan
560
740C-304 1st Floor Ventilation Fan
X
561
740C-304A 2nd Floor Ventilation Fan
X
562
740C-302B East End Spare Vac. Pump (Spare)
X
563
740P-305 Isopar Transf. Pump
564
740-P300 Jacket Circ. Pump
565
740G-301 Agitator
566
740-P301 Jacket Circ. Pump
567
Spare Size 1, 30A
Not In Service
568
Lighting Panel #21
X
569
740P-302B East End Spare Vac. Pump
X
570
600A Main Breaker
571
R-302 Jacket Heat Cool Unit
X
572
Weld. Recept.
X
573
Metering Section
574
Office Trailer
575
15 KVA Transformer
576
740G-300 Agitator
X
X
Not In Service X X X
X
X X X X
MICRO AREA CONTROL ROOM 577
LP-2
Visually Inspected
X
Fault #
No.
Equipment
Oper.
578
LP-1
X
579
Unlabeled 240 Volt Distribution Panel
X
Visually Inspected
MCC 580
Main Breaker
X
581
Lunchroom Shower Change Room
X
582
Lighting Panel LP-A
X
583
R-101 Agitator
X
584
#3 Firewater Pump
X
585
C-110C West Roof Vent Blower
X
586
Inst. Panel IPA
X
587
Spare
Not In Service
588
Spare
Not In Service
589
P-201A Rubber Reactor
X
590
P-110A Scrubber Pump
X
591
T-110A Cold Storage Refrig. Unit
X
592
Cold Storage Door
X
593
C-102B Dryer Building Fan
X
594
Spare
X
595
P-100E 32% HCLO Drum Pump
X
596
P-10A Column Feed Pump
X
597
P-100 Bottoms Pump
X
598
P-108 Reflux Pump
X
599
Spare
X
600
P-1A M-1A Clean Acetone Tk. XFER Pump
X
601
Spare
X
602
P-2A M-2A Clean Xylene Transfer Pump
X
603
P-28 M-28 Dirty Xylene Transfer Pump
604
Center Fan
605
710-P-20-A Xylene Btting Pump
Not In Service X LOTO
Fault #
No.
Equipment
Oper.
606
710-P-20-A Xylene Reflux Pump
Visually Inspected LOTO
MCC 2 607
Incoming Main Cables
X
608
7CA 15 Amp Bkr. Spare
X
609
7CB 100 Amp Bkr. Spare
X
610
Dryer Room Air Lock Fan
X
611
D-303G Vacuum Pump
X
612
C-110 E Vent Blower
X
613
8AA 40 Amp Bkr Ltg Transformer
X
614
8AB 150 Amp Bkr. For Drum Building
X
615
DI-Tank 700P-G
X
616
Cont. Rm. Airlock
X
617
M-3A Heating Pump
X
618
E-1 Fan (R-101)
X
619
E-1 Fan
X
620
Portable Pump
X
621
Formaldehyde Pump P-3A
622
F-5 North Wall
623
F-4 South Wall Centrifuge
624
P-6A
X X LOTO X
WEST END 625
240 Volt Distribution Panel
X
ALLEN BRADLEY MCC 626
Elev. 897 Building
X
627
30 KVA Lighting Transformer
X
628
Drum Fan
X
629
C 3031 Scrubber Fan
X
Fault #
No.
Equipment
Oper.
Visually Inspected
630
C-303H Chilled Glycol Pump
631
P-303D Scrubber Pump
632
D-3031 Scrubber Pump
633
Spare
634
G-303 Agitator
635
Spare
636
D-303C Tempered Glycol Pump
637
G-303C Chiller Package Unit
X
638
DG-303A 1st FL. Conv. #1
X
639
Glycol 40 kW Htr.
X
640
AC Cond. Unit
X
641
G-303 E AHU-1 Fan
X
642
Spare
643
DG-303B 1st FL Com. #2
X
644
DG-303B 1st FL Com. #3
X
645
Incoming Main Cables
X
646
Meter
X
647
Spare
648
G-303B Hot Oil System
649
Spare
Fault #
X X X Not In Service X Not In Service X
Not In Service
X X X
SUBSTATIONS 650
Storage Substation
X
651
3 Cell Cooling Tower Substations (14B & 12C)
X
652
EDC Substation
X
653
Raw Materials Substation (Fins Only)
X
654
Spray Polyol Substation
X
655
Micro East & West Substation
X
656
Glycol Substation
X
657
Admin. Building Substation (Fins Only)
X
5
No.
Equipment
Oper.
658
Maintenance Building Substation (Fins Only)
X
659
Nitrogen Plant Substation
X
660
EO Substation North & South
661
USF Substation
X
662
PPG Tank Farm Substation
X
663
Cooling Tower Substation
X
664
Glycerin Substation
X
Visually Inspected
Not In Service
PPG UPS ROOM 665
Unlabeled 240/120 Volt Distribution Panel
X
666
Battery Racks
X
WATER TREATMENT WATER TREATMENT MCC 667
Main Breaker
X
668
Micro Pump
X
669
LR Pump
X
670
CIP Heater
X
671
Metering Compartment
X
672
D1 Water Pump
673
East “A” Domestic Water Pump No. 1
Not In Service
674
West “B” Domestic Water Pump No. 2
X
675
Cent Pump
Not In Service
676
CIP Pump
X
677
Cent Pump No. 1
X
678
Cent Pump No. 2
X
679
Cent Pump No. 3
Not In Service
680
Spare
X
681
Spare
X
682
Spare
X
LOTO
Fault #
No.
Equipment
Oper.
Visually Inspected
683
Main Breaker From 10 KVA Lighting Transformer
684
Welding Receptacle
685
Spare
Not In Service
686
Spare
Not In Service
X X
WATER TREATMENT PLANT MCC 687
Blank
X
688
Lighting Panel
X
689
15 KVA Transformer
X
690
Ventilation Fan
691
De-Gas Blower Ion Units (Could Not Open, Broken Release)
692
Caustic Unloading Pump
693
Transformer Circuit Breaker
694
Portable Heater
X
695
Spare
X
696
Spare
X
697
North West Corner Roll Up Door
X
698
Sulfuric Acid Pump
699
Sulfuric Acid Pump
700
Ion Water Booster Pump
701
Main Breaker
X
702
A Transfer
X
703
B Transfer
704
Spare
X Could Not Open X X
X LOTO Not In Service
X Not In Service
WELLS AREA 705
Interceptor Well #1 Riser Pole w/ (3) Fuse Disconnects
X
706
Interceptor Well #2 Riser Pole w/ (3) Fuse Disconnects
X
707
Interceptor Well #3 Riser Pole w/ (3) Fuse Disconnects
708
Interceptor Well #4 Riser Pole w/ (3) Fuse Disconnects
X
709
Interceptor Well #5 Riser Pole w/ (3) Fuse Disconnects
X
Not In Service
Fault #
No.
Equipment
Oper.
710
Interceptor Well #6 Riser Pole w/ (3) Fuse Disconnects
X
711
Interceptor Well #7 Riser Pole w/ (3) Fuse Disconnects
X
712
Interceptor Well #8 Riser Pole w/ (3) Fuse Disconnects
X
713
Domestic Well #1 Riser Pole w/ (3) Fuse Disconnects
X
714
Domestic Well #2 Riser Pole w/ (3) Fuse Disconnects
X
715
Lake Moe Pump Riser Pole w/ (3) Fuse Disconnects & 3ø Transformer Bank
716
Both Water Wells
X
717
Barge Landing Riser Pole w/ (3) Fuse Disconnect
X
718
Switch 1
X
719
Switch 2
X
720
Switch 3
X
721
Switch 4A
X
722
Switch 4B
X
723
Switch 5A
X
724
Switch 5B
X
725
Switch 6A
X
726
Switch 6B
X
Visually Inspected
Not In Service
AMMONIA CHILLER AREA 727
CH-120A Motor & Disconnect
X
728
CH-120B Motor & Disconnect
X
MCC B 729
T-105 Tank Heater
Not In Service
730
T121B 80kW Heater
731
Spare
732
Welding Receptacle
733
P-121 B Heater Supply Pump
X
734
P-121 C Heater Supply Pump
X
X Not In Service X
Fault #
No.
Equipment
Oper.
735
G1000C Agitator For M-1000 VFD
X
736
P-120 Chiller Supply Pump
X
737
Spare
X
738
CH-120-B2 Aux Oil Pump Chiller “B”
X
739
CH-120-B1 Main Drive Chiller “B”
X
740
P-111 Scrubber Pump
741
Spare
Not In Service
742
P-111 Hypochlorite Pump P-111A
Not In Service
743
DP-6GA M-66 Transfer Pump
X
744
P-120A Chiller Supply Pump P-120A
X
745
Spare
X
746
CH-120-A2 Aux Oil Pump Chiller “A”
X
747
CH-120-A1 Main Drive Chiller Motor Chiller “A”
X
748
T-121-A 20 kW Heater T-121A
X
749
T-121-C 60 kW Heater T-121C
X
750
Spare
X
751
Lighting Transformer 45 kVA
X
752
P-121A Heater Supply Pump
X
753
Centrifuge Vent Fan
754
P-112-2 Dry Vacuum Pump P-112A
X
755
P-112-1 Dry Vacuum Pump P-112
X
X
X
POWER HOUSE 756
Cameron Air Compressor Motor
X
NITROGEN PLANT 757
Nitrogen Compressor Combination Starter
Visually Inspected
X
NITROGEN SHED 758
Sylvania 480 Volt Distribution Panel
X
759
CP-53 Combination Starter
X
760
Unlabeled 208/120 Volt Distribution Panel
X
Fault #
No.
Equipment
Oper.
MAINTENANCE AREA 761
Distribution Panel A
X
762
Distribution Panel B
X
763
Distribution Panel C
X
764
Distribution Panel D
X
Visually Inspected
Fault #