1SDH000556R0001

B0431

Modbus System Interface

Modbus system Interface for Protection relays PR122/P and PR123/P + communication module PR120/D-M, mounted on CB New Emax Protection relays PR332/P and PR333/P + communication module PR330/D-M, mounted on CB Emax X1, Tmax T7 and Tmax T8

Power and productivity for a better worldTM



Index 1. INTRODUCTION....................................................................................................................................................................................... 4 1.1 SCOPE ....................................................................................................................................................................................................... 4 1.2 APPLICABILITY .......................................................................................................................................................................................... 4 1.3 ACRONYM AND DEFINITION .................................................................................................................................................................... 4 1.3.1. Acronym ........................................................................................................................................................................................... 4 1.3.2. Definitions ........................................................................................................................................................................................ 5 1.4 BIBLIOGRAPY ............................................................................................................................................................................................ 5 2. MODBUS PROTOCOL ............................................................................................................................................................................... 6 2.1 Communication Parameters .................................................................................................................................................................... 6 2.2 Device RTU Framing ................................................................................................................................................................................. 6 2.2.1. Silent interval < 4 char between two characters inside the message .............................................................................................. 6 2.2.2. Silent interval  4 char between two characters inside the message .............................................................................................. 7 2.2.3. New frame before 4 character silent interval at the end of a frame................................................................................................ 7 2.3 Unit identification .................................................................................................................................................................................... 7 2.4 Available Modbus functions ..................................................................................................................................................................... 7 2.4.1. Function 03 (03h) Read Holding Registers ....................................................................................................................................... 8 2.4.2. Function 04 (04h) Read Input Registers ........................................................................................................................................... 8 2.4.3. Function 06 (06h) Write Single Register ........................................................................................................................................... 8 2.4.4. Function 08 (08h) Diagnostic ............................................................................................................................................................ 8 2.4.5. Function 16 (10h) Write Multiple Registers ..................................................................................................................................... 8 2.4.6. Function 17 (11h) Report slave ID .................................................................................................................................................... 9 2.4.7. Function 70 (46h) Read Extended Registers ..................................................................................................................................... 9 2.5 Exception responses ................................................................................................................................................................................ 9 2.5.1. Exception occurrences ................................................................................................................................................................... 10 3. MODBUS MAP ...................................................................................................................................................................................... 11 3.1 Unit configuration .................................................................................................................................................................................. 12 3.1.1. Protection....................................................................................................................................................................................... 12 3.1.2. MEASURES ...................................................................................................................................................................................... 13 3.2 REGISTERS MAP ..................................................................................................................................................................................... 14 3.3 LOGGER MAP (extended registers) ........................................................................................................................................................ 15 4. DESCRIPTION OF REGISTERS .................................................................................................................................................................. 17 4.1 COMMANDS ........................................................................................................................................................................................... 17 4.2 STATISTICAL DATA .................................................................................................................................................................................. 18 4.3 PROGR FAIL ERROR CODE ...................................................................................................................................................................... 18 4.4 STATE ..................................................................................................................................................................................................... 20 4.5 TIME ....................................................................................................................................................................................................... 23 4.6 RUN-TIME MEASURES ............................................................................................................................................................................ 23 4.7 HARMONIC MEASURES .......................................................................................................................................................................... 24 4.8 INFORMATION ....................................................................................................................................................................................... 24 4.9 LOCAL BUS DATA AREA .......................................................................................................................................................................... 24 4.10 CONFIGURATION1.................................................................................................................................................................................. 25 4.11 PARAMETERS CONFIGURATION2 ........................................................................................................................................................... 25 4.12 PARAMETERS CONFIGURATION3 ........................................................................................................................................................... 26 4.13 PARAMETERS PROTECTION SET1 / SET2 (only for PR123/P - PR333/P) ................................................................................................. 28 4.14 TRIP HISTORY ......................................................................................................................................................................................... 31 4.15 MEASURE HISTORY ................................................................................................................................................................................ 32 4.16 LOG EVENTS ........................................................................................................................................................................................... 32 4.17 WAVEFORMS ......................................................................................................................................................................................... 32 5. TABLES .................................................................................................................................................................................................. 33 6. APPENDIX ............................................................................................................................................................................................. 37 6.1 PARAMETER PROGRAMMING ................................................................................................................................................................ 37 6.2 RELAYS AND DATA LOGGER “CUSTOM” SETTING .................................................................................................................................. 38 6.3 MEASURE HISTORY DATA STRUCTURE ................................................................................................................................................... 38 6.4 WAVEFORM AND HARMONICS .............................................................................................................................................................. 39 6.5 CB STATE INFORMATION ....................................................................................................................................................................... 40 6.6 STATISTICAL DATA .................................................................................................................................................................................. 41 6.7 COMMANDS EXECUTION CONDITIONS .................................................................................................................................................. 42 6.8 MEASURE LIMITS AND REPRESENTATION .............................................................................................................................................. 43 6.9 CONTACT WEAR ..................................................................................................................................................................................... 43 7. REVISION HISTORY ................................................................................................................................................................................ 44 7.1 B0431 (16/12/2015) ............................................................................................................................................................................... 44

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

2/45

Index of Tables TABLE 1 ALARMS TYPE ..................................................................................................................................................................................................... 5 TABLE 2 AND 3 AVAILABLE AND DEFAULT COMMUNICATION PARAMETERS .................................................................................................................................... 6 TABLE 4 UNIT IDENTIFICATION ........................................................................................................................................................................................... 7 TABLE 5 AVAILABLE MODBUS FUNCTIONS ............................................................................................................................................................................. 7 TABLE 6 AND 7 FUNCTION 3 QUERY AND RESPONSE ................................................................................................................................................................ 8 TABLE 8 AND 9 FUNCTION 4 QUERY AND RESPONSE ................................................................................................................................................................ 8 TABLE 10 AND 11 FUNCTION 6 QUERY AND RESPONSE ............................................................................................................................................................ 8 TABLE 12 AND 13 FUNCTION 8 QUERY AND RESPONSE ............................................................................................................................................................ 8 TABLE 14 AND 15 FUNCTION 16 QUERY AND RESPONSE .......................................................................................................................................................... 8 TABLE 16 AND 17 FUNCTION 17 QUERY AND RESPONSE .......................................................................................................................................................... 9 TABLE 18 AND 19 FUNCTION 70 QUERY AND RESPONSE .......................................................................................................................................................... 9 TABLE 20, 21, 22, 23 AND 24 EXCEPTION RESPONSES ........................................................................................................................................................... 9 TABLE 25 EXCEPTION RESPONSES ..................................................................................................................................................................................... 10 TABLE 26 CODE MEANING .............................................................................................................................................................................................. 11 TABLE 26 PROTECTIONS ................................................................................................................................................................................................. 12 TABLE 27 ACTIVE MEASURES ........................................................................................................................................................................................... 13 TABLE 28 REGISTERS MAP ............................................................................................................................................................................................... 14 TABLE 29 LOGGER MAP .................................................................................................................................................................................................. 15 TABLE 30 TAB_INPUT_OUTPUT ................................................................................................................................................................................. 16 TABLE 31 TAB_TRIP .................................................................................................................................................................................................... 16 TABLE 32 TAB_ALARM_1 ........................................................................................................................................................................................... 16 TABLE 33 TAB_ALARM_2 ........................................................................................................................................................................................... 16 TABLE 34 COMMANDS ................................................................................................................................................................................................... 17 TABLE 35 TAB_COMMANDS ...................................................................................................................................................................................... 17 TABLE 36 TAB_WAV ................................................................................................................................................................................................... 17 TABLE 37 STATISTICAL DATA ........................................................................................................................................................................................... 18 TABLE 38 PROGRAM FAIL ERROR ..................................................................................................................................................................................... 18 TABLE 39 TAB_PAR_ERR_CODE ................................................................................................................................................................................. 19 TABLE 40 STATE ........................................................................................................................................................................................................... 22 TABLE 41 TIME ............................................................................................................................................................................................................ 23 TABLE 42 RUN-TIME MEASURES....................................................................................................................................................................................... 24 TABLE 43 HARMONIC MEASURES ...................................................................................................................................................................................... 24 TABLE 44 INFORMATION ................................................................................................................................................................................................ 24 TABLE 45 LOCAL BUS DATA AREA ...................................................................................................................................................................................... 24 TABLE 46 CONFIGURATION 1........................................................................................................................................................................................... 25 TABLE 47 CONFIGURATION 2........................................................................................................................................................................................... 25 TABLE 48 CONFIGURATION 3........................................................................................................................................................................................... 27 TABLE 49 SET 1/ SET 2 .................................................................................................................................................................................................. 30 TABLE 50 TAB_TH_RC ................................................................................................................................................................................................. 30 TABLE 51 TAB_TIME_RC .............................................................................................................................................................................................. 30 TABLE 52 TRIP HISTORY ................................................................................................................................................................................................. 31 TABLE 53 TAB_TRIP_TYPE .......................................................................................................................................................................................... 31 TABLE 54 MEASURE HISTORY .......................................................................................................................................................................................... 32 TABLE 55 LOG EVENTS ................................................................................................................................................................................................... 32 TABLE 56 WAVEFORMS.................................................................................................................................................................................................. 32 TABLE 57 TAB_UN ...................................................................................................................................................................................................... 33 TABLE 58 TAB_RELAYS_FUNCTION ............................................................................................................................................................................ 33 TABLE 59 TAB_RELAYS_K51_CONFIG......................................................................................................................................................................... 33 TABLE 60 TAB_P_RELE_CONFIG ................................................................................................................................................................................. 33 TABLE 61 TAB_CB_TYPE ............................................................................................................................................................................................. 34 TABLE 62 TAB_CB_TYPE_33X ..................................................................................................................................................................................... 35 TABLE 63 TAB_LOG_EVENTS ...................................................................................................................................................................................... 36 TABLE 64 RELAY AND DATALOGGER CUSTOM SETTING ........................................................................................................................................................... 38 TABLE 65 WAVEFORM AND HARMONICS ............................................................................................................................................................................. 39 TABLE 66 CB STATE INFORMATION ................................................................................................................................................................................... 40 TABLE 67 COMMANDS ACCEPTANCE CONDITIONS ................................................................................................................................................................. 42 TABLE 68 MEASURE LIMITS AND REPRESENTATION................................................................................................................................................................ 43

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

3/45

1.

INTRODUCTION

The documents refer to the system bus Modbus interface of relays PR122/P and PR123/P mounted on New Emax power circuit breaker, and PR332/P and PR333/P mounted on Emax X1, Tmax T7 and Tmax T8 power circuit breaker.

1.1

SCOPE

The aim of this document is to indicate the addresses of all measures, parameters and information available in PR122/3 and PR332/3 relays. Moreover it explains the procedure to read information and to program the parameters of the above mentioned protection units.

1.2

APPLICABILITY

This document applies to the device PR122/P - PR123/P equipped with the communication module PR120/D-M, and PR332/P PR333/P equipped with the communication module PR330/D-M. This version of the document refer to relays SW version 2.0 or major.

1.3 1.3.1.

ACRONYM AND DEFINITION Acronym

CB PR12x PR33x

Circuit Breaker Both protection relays PR122/P and PR123/P Both protection relays PR332/P and PR333/P

AI AO LSb LSB MSb MSB

Analog Input Analog Output Least Significant Bit Least Significant Byte Most Significant Bit Most Significant Byte

BOOL BYTE WORD DWORD LWORD SINT USINT INT UINT DINT UDINT LINT ULINT STRING UNICODE

Bit or Boolean (IEC 61131-3) Byte (IEC 61131-3) Word (IEC 61131-3) Double word (IEC 61131-3) Long Word (IEC 61131-3) Short Integer (IEC 61131-3) Unsigned Short Integer (IEC 61131-3) Single Integer (IEC 61131-3) Unsigned Integer (IEC 61131-3) Double Integer (IEC 61131-3) Unsigned Double Integer (IEC 61131-3) Long Integer (IEC 61131-3) Unsigned Long Integer (IEC 61131-3) Text String (IEC 61131-3) Unicode (IEC 61131-3)

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

4/45

1.3.2.

Definitions

ALARM:

there are two types of alarm:

Alarm Type

Definition

Alarm

It’s similar to a status. A Trip Reset is NOT necessary to reset it. Ex. L Pre-Alarm, S Alarm, ...

Trip

Only a command can reset it, i.e. a new alarm won’t be signalled until the reset. Ex. L Tripped, S Tripped, ... Table 1 Alarms type

BUFFER: CB RESET: DEVICE: EVENT: PARAMETER: PROTECTION TRIPS: PROTECTION UNIT: REGISTER: REMOTE SYSTEM: STATUS: TRIP COMMAND FAIL:

TRIP RESET:

1.4

meaningful part of a Modbus Map section. It’s defined by the Modbus Map of the device. event (Any Trip) /alarm reset of any information related to the (last) trip. Protection Unit information that signals a normal (foreseen) device behaviour. Typically, the producer of an event is the device, while the consumer is the system. information that allows configuration of device functionality (e.g. a protection algorithm). sum of real protection trips ( LSIG trips). ‘Real’ means ‘not caused by the Test Unit. PR122/3 and PR332/3 electronic device that implements protection algorithms the least analogue information container (one word = 2 bytes) a device (SCADA) which behaves as Modbus Master on the external bus. It polls the information provided by the device and sends to it commands and parameters. information that represents the dynamics of a functionality (e.g. the CB or a protection algorithm). It can be managed (i.e. set/reset) only by the device itself. after a protection trip, with relevant opening command to the release, CB stays in CLOSED state. In this case, the device tries to open the CB by starting a back-up procedure. Meanwhile, the device tries also to open the CB using the YO (through the I/O). command equal to CB Reset

BIBLIOGRAPY

Schneider Automation Inc., ‘Modicon MODBUS Protocol Reference Guide’

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

5/45

2.

MODBUS PROTOCOL

2.1

Communication Parameters Baud rate 9600/19200

Address 1  247

Addressing type Standard / ABB

Physical protocol E, 8, 1 / O, 8, 1 / N, 8, 2 / N, 8, 1

The default unit configuration is: Baud rate Address 19200 247

Addressing type Standard

Physical protocol E, 8, 1

Table 2 and 3 Available and default communication parameters

2.2

Device RTU Framing

The allowed inter-character silent interval has been relaxed from ‘at least 2 characters’ to ‘at least 4 characters’ (the same silent interval to recognize the end of a message). This means:

2.2.1.

Silent interval < 4 char between two characters inside the message

In this case the receiver filters the silent interval and the following characters will be appended to those already received. The difference from the protocol specification is: 1.

Silent interval < 2 char between two characters inside the message Transmitter

Silent interval

4 char 1

2

4 char 1

2

...

3

n 4 char

Receiver 3

n 4 char

...

The behaviour is exactly as specified by the protocol. 2.

Silent interval  2 char and < 4 char between two characters inside the message The received characters are NOT flushed and the following ones will be appended. Silent interval

Transmitter 4 char 1

2

4 char 1

2

3

...

n 4 char

Receiver

3

n 4 char

...

Note that after flushing, the standard protocol specification allows:  reception of the remaining characters of a partially received message  reception of a completely new message

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

6/45

The device behaviour doesn’t cover the second case because it always appends new incoming characters to the previous ones, leading to a CRC error. So the behaviour is exactly the same if and only if the incoming characters are NOT a new message. In this case the received packet will lead to a CRC error and the CRC error counter will be incremented.

2.2.2.

Silent interval  4 char between two characters inside the message

If the message transmission is NOT ended, all the previously received characters are managed as a message because this is exactly the protocol specification regarding the end of a message.

2.2.3.

New frame before 4 character silent interval at the end of a frame

In this case the receiver filters the silent interval and the following characters (of the new frame) will be appended to those already received. This will lead to a CRC error. Silent interval

Transmitter 4 char 1

2

n

...

3

1

2

3

...

m 4 char

Receiver 4 char 1

2

n

...

3

1

2

3

...

m 4 char

So the CRC error counter will count both the ‘real’ CRC errors and the inter-character errors.

2.3

Unit identification Unit PR122/P PR123/P PR332/P PR333/P PR332/P MM

Slave ID 0x51 0x52 0x55 0x56 0x25

Table 4 Unit identification

2.4

Available Modbus functions Function Code 03 (03h) 04 (04h) 06 (06h) Funct. Code Subf. Code 08 (08h) 00 (00H) Function Code 16 (10h) 17 (11h) 70 (46h)

Name Read Holding Registers Read Input Registers Write Single Register Name Diagnostic Loop back Name Write Multiple Registers Report Slave ID Read Extended Registers

Applicable to AO AI AO Applicable to --Applicable to AO --Extended Reg.

Table 5 Available Modbus functions Note: all queries must respect the limitation of maximum modbus message length of 256 byte Legend: AA = slave address (1 247) cl = byte low of CRC ch = byte high of CRC Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

7/45

2.4.1.

Function 03 (03h) Read Holding Registers

Query Addr Function Starting address AA 03h High Low Note: number of registers ≤ 125 Response Addr AA

Function 03h

Byte count nn

Number of registers High Low

Register value High Low

… …

Crc ch

cl

Register value High Low

Crc ch

cl

Table 6 and 7 Function 3 query and response

2.4.2.

Function 04 (04h) Read Input Registers

Query Addr Function Starting address AA 04h High Low Note: number of registers ≤ 125 Response Addr AA

Function 04h

Byte count nn

Nr of input registers High Low

Input register High Low

… …

Crc ch

cl

Input register High Low

Crc ch

cl

Table 8 and 9 Function 4 query and response

2.4.3.

Function 06 (06h) Write Single Register

Query Addr AA

Function 06h

Register address High Low

Register value High Low

ch

Crc

Response (echo of query) Addr Function Register address AA 06h High Low

Register value High Low

ch

cl Crc cl

Table 10 and 11 Function 6 query and response

2.4.4.

Function 08 (08h) Diagnostic

Query Addr Function Sub function AA 08h 00h 00h Note: 0 ≤ Number of data bytes ≤ 250, any value Response (echo of query) Addr Function AA 08h

Sub function 00h 00h

Data yy

… …

ch

Crc

Data yy

… …

ch

cl

Crc cl

Table 12 and 13 Function 8 query and response

2.4.5.

Function 16 (10h) Write Multiple Registers

Query Addr Funct Starting addr AA 10h High Low Note: number of registers ≤ 123 Response Addr AA

Function 10h

Num of registers High Low

Starting address High Low

Byte count Nn

Number of register High Low

Reg value High Low

… …

Reg value High Low

Crc ch

cl

Crc ch

cl

Table 14 and 15 Function 16 query and response Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

8/45

2.4.6.

Function 17 (11h) Report slave ID

Query Addr AA

Function 11h

Response Addr Function AA 11h

Crc ch

Cl

Byte count 16h

Slave ID ID

Run indicator 0FFh

Sw Version High Low

Events addr High Low

Device Ser Nr 16 byte (ASCII)

Crc ch cl

Table 16 and 17 Function 17 query and response

2.4.7.

Function 70 (46h) Read Extended Registers

Query Addr Function Byte count AA 46h 07h Notes: 1. File number ≤ 3 2. Starting address ≤ 65535 3. Number of registers ≤ 125 Response Addr AA

Funct 46h

Byte count Nn

Ref type 06h

Ref type 06h

File number High Low

Reg value High Low

… …

Starting address High Low

Reg value High Low

Number of registers High Low

Crc ch

cl

Crc ch

cl

Table 18 and 19 Function 70 query and response

2.5

Exception responses

Illegal function: Addr AA

Function Function + 80h

Exception code 01h

ch

Crc

Addr AA

Function Function + 80h

Exception code 02h

ch

Addr AA

Function Function + 80h

Exception code 03h

ch

Addr AA

Function Function + 80h

Exception code 04h

Addr AA

Function Function + 80h

Exception code 06h

cl

Illegal data address: Crc cl

Illegal data value: Crc cl

Slave device failure: Crc ch

cl

Slave device busy: Crc ch

cl

Table 20, 21, 22, 23 and 24 Exception responses

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

9/45

2.5.1.

Exception occurrences Exception 01 Illegal function

02 Illegal data address Starting address not valid

03

Starting address not valid

04

04 Slave device failure

03 Illegal data value - Invalid query length - Requested number of register too large - Address out of modbus map - Invalid query length

Reading attempt of busy non-volatile memory at present

- Requested number of register too large - Address out of modbus map

- Starting address not valid - Write of TIME information not allowed with this function

QUERY FUNCTION

06

06 Slave device busy

- Local state - Programming session already open

Invalid query length

- Programming session not open - Sub function ≠ 00 00

08

- Invalid query length - Invalid query length - Number of register too large Starting address not valid

16

- Address out of modbus map - Command not available - Command parameter filed not valid - Wrong Time

17

Parameters error check after a stop programming session command

- Local state - Programming session already open - Programming session not open - Command acceptance conditions not verified

Invalid query length - Invalid query length Starting address not valid

70

- Requested number of register too large - Address out of modbus map - Field Ref Type not correct

Reading attempt of busy data logger

- Field Byte count not correct Other

Function not available

Table 25 Exception responses

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

10/45

3.

MODBUS MAP

Data format LINT (Acronym 1.3.1) (4 byte = 2 word = 2 register) is transferred with low significant part at lower modbus address (LOW-HIGH) Register i LS word Register i + 1 MS word Instead within WORD data the most significant byte is transferred first (as in MODBUS RTU standard) MS byte LS byte Since the PR122/P and PR332/P information set is a subset of PR123/P and PR333/P set, it was decided to represent them in only one general map from which is possible to deduce information of each device. PR123/P PR333/P

PR122/P PR332/P

For this purpose in each table it was foreseen a column named PR12x/PR33x in which, row by row, are shown the device and the product execution where the information has mean. The explanation of how to read column PR12x/PR33x follows: PR12x Meaning PR33x 3 Information available for PR123/P and PR333/P LSI/LSIG and NOT available for other units 3 Information available for PR123/P and PR333/P LSIG and NOT available for other units G 2/3 Information available for PR122/P and PR332/P LSI/LSIG, PR123/P and PR333/P LSI/LSIG and NOT available for S other units 2/3 Information available for PR122/P and PR332/P LSIG, PR123/P and PR333/P LSIG and NOT available for other units G 2/3 Information available for PR122/P and PR332/P LI/LSI/LSIG, PR123/P and PR333/P LSI/LSIG 2/3 The contained information in the line is worth for PR122/P, PR332/P and PR123/P,PR333/P Rc versions and is NOT Rc AVAILABLE for the other units The contained information in the line is worth for PR332/P and PR333/P versions and is NOT AVAILABLE for the 233x/333x PR122/P and PR123/P units The contained information in the line is worth for PR122/P and PR123/P versions and is NOT AVAILABLE for the 233x/333x PR332/P and PR333/P units MM The contained information in the line is worth for PR332/P MM unit and is NOT AVAILABLE for all the others units MM Not available for PR332/P MM unit Table 26 Code meaning WARNING: Parameters declared NOT AVALAIBLE for a unit are treated in the same way than the others, they are saved and checked in validity range but they are not used by the protections. Reading parameters declared NOT AVAILABLE could return not consistent data in respect to the ones previously programmed. Example: Program on PR122 the directional protection (NOT AVAILABLE for PR122) with the following data:  Prot D configuration = 0x0001 (Prot enable = ON)  Prot D Prot threshold Forward = 1 In Programming will be accepted because data is valid but D protection will remain disabled, therefore reading the parameters just programmed will return:  Prot D configuration = 0x0000 (Prot enable = OFF)  Prot D Prot threshold Forward = 1 In

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

11/45

3.1

Unit configuration

3.1.1.

Protection

The following table shows the available protections for each type of device and possible necessary conditions:

PR122/P - PR332/P L

PR123/P - PR333/P

LI

LSI

LSIG

LSIRc

LSIG MM(5)

LSI

LSIG



























S S2





D

MEAS(1)

MEAS(1)





I





( )

( )

G







NOSGR 4

MCR

4

( ) 4



( ) 4

( ) 4

 ( )

(4)

4



MM Gext

SGR

Gext (Idn)

SGR

RCM

RCM(1) 

RCM(1)

U











UV

MEAS

MEAS

MEAS

MEAS(1)

MEAS(1)

OV

MEAS

MEAS

MEAS

MEAS(1)

MEAS(1)

RV

MEAS QP

MEAS QP

MEAS QP

MEAS(1) QP

MEAS(1) QP

RP

MEAS

MEAS

MEAS

MEAS(1)

MEAS(1)

UF

MEAS

MEAS

MEAS

MEAS(1)

MEAS(1)

OF

MEAS

MEAS

MEAS

MEAS(1)

MEAS(1)

T















LC

(2)

(2)

(2)

(2)

(2)

(2)

(2)















Hw prot.



Phase rotation(3)

MEAS(1)

3

1

CosΦ module( ) Frequency Error(3)

MEAS

MEAS

MEAS

Harm distortion(3)











MEAS(1)

MEAS( )

MEAS(1)

MEAS(1)

MEAS(1)





Table 27 Protections Legend: : NOSGR: SGR: RCM: MEAS: QP: (1): (2): (3): (4): (5):

Model

Available without condition External Toroid absent (Ext Toroid Type (addr 1032) = 0) External Toroid = Source Ground Return (Ext Toroid Type (addr 1032) = 1) External Toroid = Residual Current (Ext Toroid Type (addr 1032) = 2) + Measuring Module present Measuring Module present “CB 4 pole” otherwise neutral voltage present (Unit configuration (addr 1020) bit 5 = 1) Measuring Module always present on PR122 LSIRc, PR332 LSIRc and PR123, PR333 Load control always enabled on state bits but feasible only if present signaling module or output unit on local bus (ex: Flex Interface) Warning functions. Activable in alternative to I protection. LSIG MM version available only with PR332/P MM

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

12/45

3.1.2.

MEASURES

The following table shows the available measures for each type of device and possible necessary conditions:

PR122/P - PR332/P

PR123/P - PR333/P

LI

LSI

LSIG

LSIRc

LSIG MM

LSI

LSIG

Line currents















Neutral current

Ne

Ne

Ne

Ne

Ne

Ne

Ne





MEAS QP

MEAS(1) QP

SGR or RCM(1) MEAS(1) QP

MEAS

MEAS(1)

MEAS(1)

Ground current

NOSGR

Line to neutral voltages

MEAS QP

MEAS QP

SGR or RCM MEAS QP

Line to line voltages

MEAS

MEAS

MEAS

External toroid ground current

RCM(1)

Line to neutral power

MEAS QP

MEAS QP

MEAS QP

MEAS QP

MEAS(1) QP

MEAS(1) QP

Total power

MEAS

MEAS

MEAS

MEAS

MEAS(1)

MEAS(1)

Power factor

MEAS

MEAS

MEAS

MEAS

MEAS(1)

MEAS(1)

Net frequency

MEAS

MEAS

MEAS

MEAS

1

MEAS( )

MEAS(1)

Peak factor















Neutral crest factor

Ne

Ne

Ne

Ne

Ne

Ne

Ne

MEAS

MEAS

MEAS

MEAS(1)

MEAS(1)

Trip history















Log event history















Measures history















Contact wear















Energy

Current waveform





Neutral current waveform

Ne

Ne

MEAS(1)

MEAS(1)





Line to line voltage waveform Current harmonics Neutral current harmonics Line to line voltage harmonics 

Data logger









Ne

Ne

MEAS(1)

MEAS(1)





Table 28 Active measures Legend: : QP: MEAS: (1): Ne: NOSGR: SGR: RCM:

Model

Available without condition “CB 4 pole” otherwise neutral voltage present (Unit configuration (addr 1020) bit 5 = 1) Module Measuring present Measuring Module always present on PR122 LSIRc, PR332 LSIRc and PR123, PR333 Neutral connection present (CB 4 pole o 3 pole + neutral) External Toroid absent (Ext Toroid Type (addr 1032) = 0) External Toroid = Source Ground Return (Ext Toroid Type (addr 1032) = 1) External Toroid = Residual Current (Ext Toroid Type (addr 1032) = 2) + Measuring Module present.

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

13/45

3.2

REGISTERS MAP AI [30001]

AO [40001]

Relative Address

Function 4 (2.4.2)

0

STATISTICAL DATA (4.2)

50

PROGR. FAIL ERROR CODE (4.3)

100

STATE(4.4)

200

RUN TIME MEASURES (4.5)

600

HARMONICS MEASURES (4.7)

700

INFORMATION (4.8)

800

LOCAL BUS DATA AREA (4.9)

1000

PAR. CONFIG1 ACTUAL (4.10)

1020

PAR. CONFIG2 ACTUAL (4.11)

1050

PAR. CONFIG3 ACTUAL (4.12)

PAR. CONFIG3 NEW (*)

1100

PAR. PROT. SET1 ACTUAL (4.13)

PAR. PROT SET1 NEW (*)

1200

PAR. PROT. SET2 ACTUAL (4.13)

PAR. PROT SET2 NEW (*)

2000

TRIP HISTORY (4.14)

2500

MEASURES HISTORY (4.15)

3300

LOG EVENTS (4.16)

4000

WAVEFORMS (4.17)

Function:

16 (2.4.5)

3 (2.4.1)

6 (2.4.3)

COMMANDS (4.1)

TIME (*)

Table 29 Registers map WARNING: *NON-VOLATILE memory : could be busy (busy exception response) (*) Parameters that can be written only during an open programming session Example of table reading: RUN-TIME MEASURES analog input absolute address: 30001+ offset (200) = 30201 The relative address is offset (200) = 200

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

14/45

3.3

LOGGER MAP (extended registers) WARNING: Addressing type “ABB” cannot be used for these registers, therefore the address field will be always included between 1 and 65536 for all addressing methods Extended Reg. (60000)

File Number

Sample Number

Function 70 Description

Rel. address 0

Samples 0 (Old) File 0 (Old)

Samples 1

Notes

PR12x PR33x

L1 current sample

(1)

2/3

1

L2 current sample

(1)

2/3

2

L3 current sample

(1)

2/3

3

Ne current sample

(1)

2/3

4

External Ground (SGR/Rc sensor) current sample

(4)

2/3 G

5

L1 MSP current sample

(2)

2/3

6

L2 MSP current sample

(2)

2/3

7

L3 MSP current sample

(2)

2/3

8

Ne MSP current sample

(2)

2/3

9

V1 voltage sample

(3)

2/3

10

V2 voltage sample

(3)

2/3

11

V3 voltage sample

(3)

2/3

12

Input/Output status

13

Alarms 1 status

14

Alarm 2 status

15

Trip 1 status

See Table 31 TAB_INPUT_OUTPUT See Table 33 TAB_ALARM_1 See Table 34 TAB_ALARM_2

2/3 2/3 2/3

See Table 32 TAB_TRIP

2/3

16 ÷ 31





2/3









2/3

Samples 4095 (New)

65519 ÷ 65535





2/3

File 1

Samples 0 ÷ Samples 4095

0 ÷ 65535





2/3

File 2

Samples 0 ÷ Samples 4095

0 ÷ 65535





2/3

File 3 (New)

Samples 0 ÷ Samples 4095

0 ÷ 65535





2/3

Table 30 Logger map Notes: (1) Signal derivative samples (538 rms means 1In rms @ 50Hz) (2) Signal derivative samples For PR12x and PR33x with DSP version before of 2.05: If net frequency = 50Hz 1 means 72,6 Arms @ 50Hz If net frequency = 60Hz 1 means 72,6 Arms @ 60Hz For PR33x with DSP version 2.05: If net frequency = 50Hz 1 means 52,3 Arms @ 50Hz If net frequency = 60Hz 1 means 52,3 Arms @ 60Hz (3) Signal samples (750 rms means 71,04Vrms) (4) If SGR connected Signal derivate samples (552 rms means 46,84 Arms @ 50Hz for Toroid of 100/250A) Signal derivate samples (552 rms means 160 Arms @ 50Hz for Toroid of 400/800A) If Rc connected Signal samples (371 rms means 1 Arms)

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

15/45

Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Bit

Description

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Local bus Relay 1 contact Local bus Relay 2 contact Local bus Relay 3 contact Local bus Relay 4 contact --Local bus Relay 6 contact Local bus Relay 7 contact Local bus Relay 8 contact Relay P1 contact Relay P2 contact Relay P3 contact Relay P4 contact S zone selectivity input S zone selectivity output G zone selectivity input G zone selectivity output

Table 33 TAB_ALARM_1

Table 31 TAB_INPUT_OUTPUT

Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Description L tripped S tripped S2 tripped I tripped Iinst tripped G tripped G ext tripped T tripped D tripped U tripped UV tripped OV tripped RV tripped RP tripped UF tripped OF tripped

Bit

Description

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

U Alarm (Blocked Trip) UV Timing UV Alarm (Blocked Trip) OV Timing OV Alarm (Blocked Trip) RV Timing RV Alarm (Blocked Trip) RP Timing RP Alarm (Blocked Trip) UF Timing UF Alarm (Blocked Trip) OF Timing OF Alarm (Blocked Trip) Frequency Error Iw Warning LC1 Alarm

Table 34 TAB_ALARM_2

Table 32 TAB_TRIP

Model

Description Harmonic distortion > 2.1 Contact Wear Pre-alarm Contact Wear Alarm L Pre-alarm L Timing S Timing S2 Timing G Timing G Alarm (Blocked Trip) G Ext Timing G Ext Alarm (Blocked Trip) T Pre-alarm T Alarm T Alarm (Blocked Trip) D Timing U Timing

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

16/45

4.

DESCRIPTION OF REGISTERS

4.1

COMMANDS Rel addr

# of item

Name

Notes

0 1

1 1

COMMAND TYPE COMMAND PARAMETER

Table 36 TAB_COMMANDS Table 36 TAB_COMMANDS

PR12x PR33x 2/3 2/3

Table 35 Commands To execute a command it is requested to write together to COMMAND TYPE field the number desired and to COMMAND PARAMETER field the optional parameter value (0 if not needed) with 17odbus function 16 also if the parameters value is not necessary. Example 1: to send “Trip reset” command, write “01” at COMMAND TYPE address and “00” at COMMAND PARAMETER address (parameter not necessary for this command). Example 2: to send “Waveform + harmonics acquisition start” Command on L2 phase, write “16” at COMMAND TYPE address and “02” at COMMAND PARAMETER address.

Following the command list table with pertinent command parameters. Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Command type

Parameter

Dummy command Trip reset Signaling reset Communication statistics reset Log events reset Start programming session Abort programming session Stop programming session CB Open CB Close CB reset Wink toggle command History measure reset Energy counters reset Data logger trigger restart Data logger stop Waveform + harmonics acquisition start Waveform + harmonics acquisition stop

don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care Table 37 TAB_WAV don’t care

PR12x PR33x 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 3 3

Table 36 TAB_COMMANDS Value 0 1 2 3 4 5 6 7

Channel --L1 L2 L3 NE V12 V23 V31

Table 37 TAB_WAV

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

17/45

4.2 Rel addr

STATISTICAL DATA # of item

Description

Representation

Notes

PR12x PR33x

0

1

Received message number

0 ÷ 65535

NOT updated in self-supply Received msg n° = Received msg n° with crc error + Sent msg n° + Received broadcast msg n°.

1

1

Received message number with crc error

0 ÷ 65535

NOT updated in self-supply

2/3

2

1

Sent message number

0 ÷ 65535

NOT updated in self-supply Total exception response number included

2/3

3

1

Slave Busy exception number responses

0 ÷ 65535

NOT updated in self-supply

2/3

4

1

Total exception response number

0 ÷ 65535

NOT updated in self-supply Slave Busy exception number response included

2/3

5

1

Contact wear

0 ÷ 65000 (100% = 65000) CW > 100%  65000

Updated in self-supply too

2/3

6

1

Total trip protection number

0 ÷ 65535

7

1

Total operation number

0 ÷ 65535

8

1

Manual operation number

0 ÷ 65535

9

1

Total trip protection number

0 ÷ 65535

10 11

1 1

Trip protection fail number Trip test number

0 ÷ 65535 0 ÷ 65535

Updated in self-supply too Protection trip fail number included NOT updated in self-supply Total operation n° = Manual operation n° + protection trip n° + protection trip fail n° + trip test n°. NOT updated in self-supply NOT updated in self-supply Protection trip fail number NOT included NOT updated in self-supply NOT updated in self-supply

2/3

2/3

2/3

2/3 2/3 2/3 2/3

Table 38 Statistical Data WARNING: Registers from address 0 to 4 compose the communication statistics, registers from address 6 to 11 compose CB operation statistics

4.3 Rel addr

PROGR FAIL ERROR CODE # of item

Description

PR12x PR33x

Note 0: No error 1 ÷ 999: See Table 40 TAB_PAR_ERR_CODE

50

1

Programming Fail Error Code

Fail Error refer to SET 1 (1xxx) and SET 2 (2xxxx) x001: L Th ≥ S Th x002: S Th ≥ I Th x003: L Th ≥ S2 Th x004: S2 Th ≥ I Th x005: L Th ≥ D Th x006: D Th ≥ I Th x007: (Only with CB UL) G Th > 1200A x008: (Only with CB UL) Startup G Th > 1200A x009: Selettivita di zona D attiva contemp. A sel zona S o S2 o G o Gext x010: (Only with CB UL) Tempo S > 400 ms x011: (Only with CB UL) Tempo S2 > 400 ms x012: (Only with CB UL) Tempo G > 400 ms x013: (Only with CB UL) Tempo Gext > 400 ms x014: (Only with CB UL) Curva L diversa da I2t=k

2/3

Common: 3001: Error during language exchange 3002: Error on Rc Sense 3003: Error on internal neutral configuration

Table 39 Program Fail Error

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

18/45

Par error code min max Step 0 1 2 3 4 5 6 7 8 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194

Parameters address Not used 1020 1050 1021 1022 1023 1024 1025 1026 1051 1083 1028 1029 Reserved Reserved 1095 1096 1084 1085 1086 1087 1088 1089 1090 1091 1092 1093 1027 1094 1032 1097 1098 1052 1067 1053 1054 1055 1056 1057 1058 1059 1060 1061 1062 1063 1064 1065 1066 1068 1069 1070 1071 1072 1073 1074 1075

Par error code min max Step 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389

Parameters address 1076 1077 1078 1079 1080 1081 1082 1100 1101 1102 1104 1103 1105 1106 1107 1108 1110 1112 1109 1111 1113 1114 1115 1116 1118 1117 1119 1120 1121 1122 1125 1123 1124 1126 1127 1128 1129 1130 1131 1132 1133 1134 1136 1138 1135 1137 1139 1140 1141 1142 1143 1145 1147 1144 1146 1148 1149

Par error code min max Step 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560

Parameters address 1176 1177 1178 1150 1151 1152 1153 1154 1155 1156 1157 1158 1159 1160 1161 1162 1163 1164 1165 1166 1167 1168 1169 1170 1171 1172 1173 1174 1175 1179 1180 1181 1200 1201 1202 1204 1203 1205 1206 1207 1208 1210 1212 1209 1211 1213 1214 1215 1216 1218 1217 1219 1220 1221 1222 1225 1223

Par error code min max Step 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 631 632 633 634 635 636 637 638 639 640 641 642 643 644 645 646 647 648 649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666 667 668 669 670 671 672 673 674 675 676 677 678 679 680 681 682 683 684 685 686 687 688 689 690 691 692 693 694 695 696 697 698 699 700 701 702 703 704 705 706 707 708 709 710 711 712 713 714 715 716 717 718 719 720 721 722 723 724 725 726 727 728 729 730 731

Parameters address 1224 1226 1227 1228 1229 1230 1231 1232 1233 1234 1236 1238 1235 1237 1239 1240 1241 1242 1243 1245 1247 1244 1246 1248 1249 1276 1277 1278 1250 1251 1252 1253 1254 1255 1256 1257 1258 1259 1260 1261 1262 1263 1264 1265 1266 1267 1268 1269 1270 1271 1272 1273 1274 1275 1279 1280 1281

Table 40 TAB_PAR_ERR_CODE Legend: min: max: step:

Model

the code inserted is lower than the minimum available (ex: Par Err Code=252  inserted at address 1103 a value< 300) the code inserted is higher than the maximum available (ex: Par Err Code=253  inserted at address 1103 a value > 14400) the code inserted has not the requested step (ex: Par Err Code=254  inserted at address 1103 a value = 302)

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

19/45

4.4

STATE

Symbols (↑) and (↕) marks state bits whose variation are traced in the events log; (↑) means that variation from 0 to 1 is traced, instead (↕) means that variation from 1 to 0 is traced too. Rel addr

# of item

100

101

102

1

1

1

Name

STATE 1 GLITCH Note 4

STATE 2 FLAGS

STATE 3 FLAGS

Bit

Description

Notes

PR12x PR33x 2/3 2/3 3 2/3 2/3 2/3 2/3 2/3 3 ---------------

BIT 0 (↑) BIT 1 BIT 2 BIT 3 (↑) BIT 4 BIT 5 BIT 6 BIT 7 BIT 8 BIT 9 BIT 10 BIT 11 BIT 12 BIT 13 BIT 14 BIT 15

Parameter changed Historical Measure Update Waveform available Signaling Reset Trip Reset CB Reset Dummy Command Energy Reset Dual Set Change ---------------

1 = Parameter(s) changed 1 = History measures updated 1 = Waveform available 1 = Signaling reset 1 = Trip Reset Command executed 1 = CB Reset Command executed 1 = Dummy Command executed 1 =Energy Reset Command executed 1 = Dual Set Changed ---------------

BIT 0

Any Alarm / Timing / Warning

OR of alarms

2/3

BIT 1

Any Trip

OR of Trips (latched)

2/3

BIT 2

CB tripped

1 = CB tripped

2/3

BIT 3 (↕) BIT 4 (↕)

CB connected / isolated CB open/closed

0 = Isolated, 1 = Connected 0 = Open, 1 = Closed

2/3 2/3

BIT 5 (↕)

CB undefined

1 = Undefined

2/3

BIT 6 (↕)

No communication on Local Bus

1 = No communication on LB

2/3

BIT 7 BIT 8 (↑) BIT 9 (↕)

Springs charged/discharged Trip command fail Local / Remote Operating Mode

0 = Discharged, 1 = Charged 1 = Trip command failed 0 = Local, 1 = Remote

2/3 2/3 2/3

BIT 10

Programming OK

1 = Programming OK

2/3

BIT 11

Programming Fail

1 = Programming Failed

2/3

BIT 12

Internal Bus programming session

1 = Bus SSI session open

2/3

BIT 13

Test Bus programming session

1 = Bus Test session open

2/3

BIT 14 BIT 15

Local Bus programming session System Bus programming session

1 = Bus Local session open 1 = Bus Ext session open

2/3 2/3

BIT 0 (↕) BIT 1 (↕) BIT 2 BIT 3 BIT 4 BIT 5 BIT 6 BIT 7 BIT 8 BIT 9 BIT 10 (↕) BIT 11 BIT 12 BIT 13 BIT 14 BIT 15

Test Session Test Unit connected BT unit present Signaling module present Dialog unit present Measuring unit present Display Off for high temp Waiting Trigger Data logger Triggered Data logger stopped Active Dual Set Wink ON Signaling Module Input Status KK function Waveform session status Local Bus Digital Input

1 = Test session open 1 = Test unit connected 1 = BT unit present 1 = Signaling module present 1 = Dialog unit present 1 = Measuring unit present 1 = Display Off 1 =Waiting trigger 1 = Triggered 1 = Stopped 0 = SET1, 1 = SET2 0 = OFF, 1 = ON 0 = Not active, 1 = Active 0 = OFF, 1 = ON 1 = Busy 0 = OFF, 1 = ON

2/3 2/3 233x/333x 2/3 2/3 2/3 2/3 2/3 2/3 2/3 3 2/3 233x/333x 2/3 3 2/3

Custom Byte N°

1

2

3

4

5

6

(continues)

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

20/45

Rel addr

103

104

105

# of item

Name

STATE 4 ALARM

1

STATE 5 ALARM

1

STATE 6 ALARM

1

Bit

Description

Notes

PR12x PR33x

BIT 0 (↕)

Harmonic distortion > 2.1

2/3

BIT 1 (↕)

Contact Wear Pre-alarm

2/3

BIT 2 (↕)

Contact Wear Alarm

2/3

BIT 3 (↕)

L Pre-alarm

2/3

BIT 4 (↕)

L Timing

BIT 5 (↕)

S Timing

BIT 6 (↕)

S2 Timing

BIT 7 (↕)

G Timing

BIT 8 (↕)

G Alarm (Blocked Trip)

BIT 9 (↕)

G Ext Timing

BIT 10 (↕)

G Ext Alarm (Blocked Trip)

BIT 11 (↕)

T Pre-alarm

2/3 2/3 S 3 S 2/3 G 2/3 G 2/3 G MM 2/3 G MM 2/3

BIT 12 (↕)

T Alarm

2/3

BIT 13 (↕) BIT 14 (↕)

T Alarm (Blocked Trip) D Timing

2/3 3

BIT 15 (↕)

U Timing

2/3

BIT 0 (↕) BIT 1 (↕) BIT 2 (↕) BIT 3 (↕) BIT 4 (↕) BIT 5 (↕) BIT 6 (↕) BIT 7 (↕) BIT 8 (↕) BIT 9 (↕) BIT 10 (↕) BIT 11 (↕) BIT 12 (↕) BIT 13 (↕) BIT 14 (↕) BIT 15 (↕) BIT 0 (↕) BIT 1 (↕) BIT 2 (↕) BIT 3 (↕) BIT 4 (↕)

U Alarm (Blocked Trip) UV Timing UV Alarm (Blocked Trip) OV Timing OV Alarm (Blocked Trip) RV Timing RV Alarm (Blocked Trip) RP Timing RP Alarm (Blocked Trip) UF Timing UF Alarm (Blocked Trip) OF Timing OF Alarm (Blocked Trip) Frequency Error Iw Warning LC1 Alarm LC2 Alarm L1 Sensor Error L2 Sensor Error L3 Sensor Error Ne Sensor Error

BIT 5 (↕)

Gext Sensor Error

BIT 6 (↕) BIT 7 (↕) BIT 8 (↕) BIT 9 BIT 10 (↕) BIT 11 (↕) BIT 12

SA Error Rating Plug Error Installation Error Internal Error Power Factor Error Phase Cycle Error Invalid Date

BIT 13 (↕)

Configuration Error

BIT 14 (↕)

CB Status Error

BIT 15

Local Bus Analog Value

Custom Byte N°

7

8

9 2/3 MM

10 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 G MM 2/3 2/3 2/3 2/3 3 3 2/3 (neutral setting, parameters incongruecy,…) 1 = Error 0 = under/equal threshold 1 = over threshold

11

12

2/3 2/3 2/3

(continues)

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

21/45

Rel addr

106

# of item

1

Name

STATE 7 INPUTS / OUTPUTS

Bit

107

108

1

1

STATE 9 LATCHED Note 5

Notes

BIT 0 BIT 1 BIT 2 BIT 3 BIT 4 BIT 5 BIT 6 BIT 7

Local bus Relay 1 contact Local bus Relay 2 contact Local bus Relay 3 contact Local bus Relay 4 contact --Local bus Relay 6 contact Local bus Relay 7 contact Local bus Relay 8 contact

0 = open, 1 = closed 0 = open, 1 = closed 0 = open, 1 = closed 0 = open, 1 = closed --0 = open, 1 = closed 0 = open, 1 = closed 0 = open, 1 = closed

BIT 8

Relay P1 contact

0 = open, 1 = closed

BIT 9 BIT 10 BIT 11 BIT 12

Relay P2 contact Relay P3 contact Relay P4 contact S zone selectivity input

0 = open, 1 = closed 0 = open, 1 = closed 0 = open, 1 = closed 1 = input active

BIT 13

S zone selectivity output

1 = output active

BIT 14

G zone selectivity input

1 = input active

BIT 15

G zone selectivity output

1 = output active

BIT 0 (↑)

L tripped

1 = L trip

BIT 1 (↑)

S tripped

1 = S trip

BIT 2 (↑)

S2 tripped

1 = S2 trip

BIT 4 (↑)

I tripped MCR tripped Iinst tripped

1 = I trip 1 = MCR trip 1 = Iinst trip

BIT 5 (↑)

G tripped

1 = G trip

BIT 6 (↑)

G ext tripped

1 = G ext trip

BIT 7 (↑) BIT 8 (↑) BIT 9 (↑) BIT 10 (↑) BIT 11 (↑) BIT 12 (↑) BIT 13 (↑) BIT 14 (↑) BIT 15 (↑) BIT 0 (↑) BIT 1 (↑) BIT 2 (↑) BIT 3 (↑) BIT 4 BIT 5 BIT 6 BIT 7 BIT 8 BIT 9 BIT 10 BIT 11 BIT 12 BIT 13 BIT 14 BIT 15

T tripped D tripped UN tripped UV tripped OV tripped RV tripped RP tripped UF tripped OF tripped Electronic Trip Test Simulated Trip from Test Unit External Input Trip Hardware Error Trip ----------------------TRIP command Fail

1 = T trip 1 = D trip 1 = UN trip 1 = UV trip 1 = OV trip 1 = RV trip 1 = RP trip 1 = UF trip 1 = OF trip 1 = electronic trip test 1 = simulated trip 1 = trip from external input 1 = trip of Hardware error ----------------------1= TRIP command Failed

BIT 3 (↑)

STATE 8 LATCHED Note 5

Description

PR12x PR33x

Custom Byte N°

2/3 MM ---

13

2/3 MM 2/3 MM 233x/333x 2/3 S MM 2/3 G MM 2/3 2/3 S 3 S 2/3 2/3 2/3 2/3 G 2/3 G MM 2/3 3

14

2/3 MM

16

2/3 2/3 233x/333x 2/3 ----------------------2/3

15

17

18

Table 41 State Notes: GLITCH registers are automatically cleared after reading. LATCHED registers are set when the associated event happens; they are reset only by “CB RESET” or “TRIP RESET” commands

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

22/45

4.5

TIME

Rel addr 100 101 102 103

# of item 1 1 1 1

Description

PR12x PR33x

Number of days from 31/12/1999 MSB = Hour, LSB = minute 0 - 59 0 - 999

2/3

Name Day Hour & minute Second Millisecond

Table 42 Time WARNING: Has shown in REGISTERS MAP(3.2), the TIME update could be done only using 23odbus function 16. In order to modify the Time it is necessary to open the programming session, the data come immediately modified and not at the and of the programming session as it happens for the normal parameters, therefore the abandonment (abort) of the programming session do not cancel the carried out modification It’s recommended to update simultaneously all four TIME registers

4.6

RUN-TIME MEASURES

The measure limits shown in column “Notes” are depicted in MEASURE LIMITS AND REPRESENTATION (6.8). Rel addr

# of item

200

2

Name

Description

Notes

PR12x PR33x

Maximum current (rms)

[A]

Not available  232-1 I < IMIN  0 I > IMAX  IMAX

2/3

0 Not available, 1L1, 2L2, 3L3, 4Ne

Not available  0

2/3

Not available  232-1 I < IMIN  0 I > IMAX  IMAX

2/3

Not available  232-1 I < IMIN  0 Not available  232-1 I < IMIN  0 I > IMAX  IMAX

2/3 G 2/3 G MM

202

1

Maximum current phase

203 205 207 209

2 2 2 2

L1 phase Current (rms) L2 phase Current (rms) L3 phase Current (rms) Ne phase Current (rms)

211

2

Internal Ground current (rms)

213

2

External Ground current (rms)

[A *10-2]

215 216 217 218 219 220 221 222 224 226 228 230 232 234 236 238 240 242 244 246

1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 1

V1 line to neutral voltage (rms) V2 line to neutral voltage (rms) V3 line to neutral voltage (rms) V0 residual voltage (rms) V12 line to line voltage (rms) V23 line to line voltage (rms) V31 line to line voltage (rms) L1 phase active power L2 phase active power L3 phase active power Total active power L1 phase reactive power L2 phase reactive power L3 phase reactive power Total reactive power L1 phase apparent power L2 phase apparent power L3 phase apparent power Total apparent power Total power factor

[V *10-1] [V *10-1] [V *10-1] [V *10-1] [V *10-1] [V *10-1] [V *10-1] [kW *10-1] (signed) [kW *10-1] (signed) [kW *10-1] (signed) [kW *10-1] (signed) [kVAR *10-1] (signed) [kVAR *10-1] (signed) [kVAR *10-1] (signed) [kVAR *10-1] (signed) [kVA *10-1] (signed) [kVA *10-1] (signed) [kVA *10-1] (signed) [kVA *10-1] (signed) [10-2] (signed)

247

1

Frequency

[Hz *10-1]

[A]

Not available  216-1 V < VMIN  0 V > VMAX  VMAX

Not available  231-1 | P | < PMIN  0 P > PMAX  PMAX P < -PMAX  -PMAX

2/3

Not available  215-1 Not available  216-1 F < FMIN  FMIN F > FMAX  FMAX

(continues)

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

23/45

Rel addr 248 249 250 251 252 254 256 258 260 262 264

# of item 1 1 1 1 2 2 2 2 2 2 2

Name

Description

L1 phase peak factor L2 phase peak factor L3 phase peak factor Ne phase peak factor Positive Active Energy Negative Active Energy Total Active Energy Positive Reactive Energy Negative Reactive Energy Total Reactive Energy Total Apparent Energy

[10-2] [10-2] [10-2] [10-2] [KWh] (signed) [KWh] (signed) [KWh] (signed) [KVARh] (signed) [KVARh] (signed) [KVARh] (signed) [KVAh] (signed)

PR12x PR33x

Notes

Not available  216-1

2/3

E < -231  -231 E > 231-1  231-1

2/3

Table 43 Run-Time measures

4.7

HARMONIC MEASURES

Rel addr 600 601 602 …. 640

# of item 1 1 1 …. 1

Name

PR12x PR33x

Description

Total Harmonic Distortion (THD) 1th Harmonic ratio = 1000 ‰ 2th Harmonic ratio …. 40th Harmonic ratio

[‰] [‰] [‰] [‰] [‰]

3

Table 44 Harmonic measures

4.8

INFORMATION

Rel addr 700 701

# of item 1 1

Name

Range

702

1

703

1

704

1

3/4 pole CB 3/4/2 pole CB In (nominal current)

705

1

CB type

706 714 715

8 1 1

CB Serial Number Data logger max file Data logger max address

Major + minor 0÷1 0÷2 0÷1 0÷2 100 ÷ 6300 See Table 62 TAB_CB_TYPE See Table 63 TAB_CB_TYPE_33x ASCII format characters 0÷3 0 ÷ 65535

716

1

Data logger Trigger

0÷4

717 718 719 720 723

1 1 1 1 6

Day of Data logger trigger Hours & minutes of Dlog trigger Second of Dlog trigger Millisecond of Dlog trigger CB name

Number of days from 31/12/1999 Hours & minutes Seconds Milliseconds ASCII format characters

Slave ID SW version Product Standard reference

Description

0IEC, 1UL1066 0IEC, 1UL1066, 1UL489 0  3 Pole, 1  4 Pole 0  3 Pole, 1  4 Pole, 2  2 Pole [A] See Table 62 TAB_CB_TYPE See Table 63 TAB_CB_TYPE_33x ASCII format characters 0÷3 0 ÷ 65535 0 = None (free running) 1 = Any Alarm 2 = L Timing 3= Any Trip 4 = Custom MSB = Hours, LSB = minutes

PR12x PR33x 2/3 2/3 233x/333x 233x/333x 233x/333x 233x/333x 2/3 233x/333x 233x/333x 2/3 2/3 2/3

2/3

2/3 2/3 2/3 2/3 2/3

Table 45 Information

4.9

LOCAL BUS DATA AREA

Rel addr

# of item

Name

Range

Description Bit = 0 Bit = 1 0 Bus Warning OFF Bus Warning ON 1 Bus Alarm OFF Bus Alarm ON 2(1) Digital Input OFF Digital Input ON 0 ÷ 65535 Used by Accessory unit

PR12x PR33x

Bit

800

1

Accessory Bus status

0x0000 ÷ 0x0003

801 802

1 25

Analog Value Local Bus Data Area

0 ÷ 65535 0 ÷ 65535

2/3 2/3 2/3

Table 46 Local bus data area Note: digital input value (Addr.800, bit 2) is reported in STATE relay. Local bus data area is an exchange buffer between system bus and devices connected to the accessory bus (e.g. PR035/MM). Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

24/45

4.10

CONFIGURATION1

Rel addr

# of item

1000

1

Product execution

0÷3

1001

8

Relay Serial Number

ASCII format characters

Name

Range

Description 0LI, 1LSI, 2LSIG, 3LSIRc ---

PR12x PR33x 2/3 2/3

Table 47 Configuration 1

4.11 Rel addr

PARAMETERS CONFIGURATION2 # of item

Name

Range

0x0000 ÷ 0x003F

1020

1

Unit configuration

1021

1

Language

0÷4

1022

1

Neutral selection

0÷3

1023

1

Ext. ground toroid

0÷3

1024

1

Nominal voltage Un

See Table 58 TAB_UN

1025

1

VT secondary voltage

0÷5

1026

1

Net Frequency

0÷1

1027

1

Plant Configuration

0÷1

1028

1

1029

1

1030

1

1031

1

Protocol Type (external bus only)

0÷3

1032

1

Ext Toroid Type

0÷2

Slave Address (external bus only) Addressing Type (external bus only) Baud rate (external bus only)

1 ÷ 247 0÷1 0÷1

Description Bit Bit = 0 0 Not Used 1 Local Bus Unit = absent 2 VT = absent 3 Neutral Protection = OFF 4 Power Direction = Bottom  Top 5 Neutral Voltage = absent 6 Operating mode = Local 0 = ENG 1 = ITA 2 = FRA 3 = GER 4 = SPA 0 = 50 % 1 = 100 % 2 = 150 % 3 = 200 % 0 = 100 A 1 = 250 A 2 = 400 A 3 = 800 A

Bit = 1 Not Used Local Bus Unit = present VT = present Neutral Protection = ON Power Direction = Top  Bottom Neutral Voltage = present Operating mode = Remote

PR12x PR33x 2/3 2/3 2/3 2/3 2/3 2/3 2/3

2/3

2/3

2/3 G MM

See Table 58 TAB_UN

2/3

0 = 100 V 1 = 110 V 2 = 115 V 3 = 120 V 4 = 200 V 5 = 230 V 0 = 50 Hz 1 = 60 Hz 0 = 3P 1 = 3P+N

2/3

2/3 2/3

1 ÷ 247

2/3

0 = standard 1 = ABB 0 = 9600 1 = 19200 0 = “E,8,1” 1 = “O,8,1” 2 = “N,8,2” 3 = “N,8,1” 0 = None 1 = Source Ground Return 2 = Rc

2/3 2/3

2/3

2/3 G

Table 48 Configuration 2

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

25/45

4.12

PARAMETERS CONFIGURATION3

Rel addr

# of item

Name

Range Bit

Bit = 0

Bit = 1

0

Par set = set A

Par set = set B

3

1

Dual Setting = OFF Harm Dist Warn = OFF Phase Rotation Warn = OFF Phase Rotation Cycle = 123

Dual Setting = ON Harm Dist Warn = ON Phase Rotation Warn = ON Phase Rotation Cycle = 321

3

CosFi Module Warning = OFF

CosFi Module Warning = ON

3

Set B on CB close

3

Set B on Vaux OFF

3

Set B on Local Bus Digital Input ON

3

2 3 1050

1

Configuration

4

0x0000 ÷ 0x007F

5

Dual set CB close disable Dual set Vaux 7 disable Dual Set Local Bus 8 disable 5 ÷ 120 min 6

1051

1

1052

1

1053 1054 1055 1056 1057 1058 1059 1060 1061 1062 1063 1064 1065 1066

1 1 1 1 1 1 1 1 1 1 1 1 1 1

1067

1

1068 1069 1070 1071 1072 1073 1074 1075

1 1 1 1 1 1 1 1

1076

1

PR12x PR33x

Description

Measurement store time Loc Bus Relays Unit Contact configuration Loc Bus Relay 1 Function Loc Bus Relay 1 Delay Loc Bus Relay 2 Function Loc Bus Relay 2 Delay Loc Bus Relay 3 Function Loc Bus Relay 3 Delay Loc Bus Relay 4 Function Loc Bus Relay 4 Delay Loc Bus Relay 6 Function Loc Bus Relay 6 Delay Loc Bus Relay 7 Function Loc Bus Relay 7 Delay Loc Bus Relay 8 Function Loc Bus Relay 8 Delay P Relays Contact configuration P1 Function P1 Delay P2 Function P2 Delay P3 Function P3 Delay P4 Function P4 Delay

5 ÷ 120 step 5 [min] See Table 60 TAB_RELAYS_K51_CONFIG 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] See Table 61 TAB_P_RELE_CONFIG 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s]

Programmable Input configuration

0x0000 ÷ 0x0001

1

Programmable Input Function

0÷5

1078

1

Programmable Input Delay

0.00 ÷ 100.00 step 0.01 [s]

3 3

2/3

See Table 60 TAB_RELAYS_K51_CONFIG See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 61 TAB_P_RELE_CONFIG See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] 0 = Active low 1 = Active high

1077

2/3

0 = Generic 1 = External TRIP 2 = Trip reset 3 = Set B (PR123/P only) 4 = Dial Local 5 = Reset Signaling Module 6 = Energy reset 0 ÷ 10000 [s*10-2]

2/3

2/3 MM

233x/333x

(continues)

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

26/45

Rel addr

# of item

1079

1

1080

1

Name

Range

Description

PR12x PR33x

0 = Data Logger = OFF 1 = Data Logger = ON

Data Logger Configuration

0x0000 ÷ 0x0001

Data Logger Trigger Type

Standard: 0 ÷ 3 Custom 256 ÷ 65535 (see RELAYS AND DATA LOGGER “CUSTOM” SETTING)

1081

1

Data Logger Stop Delay

0.00 ÷ 10.00 step 0.01 [s]

1082

1

Data Logger Frequency

0÷3

1083 1084 1089 1094 1095 1096 1097

1 5 5 1 1 1 1

0.50 ÷ 0.95 step 0.01 ASCII format characters ASCII format characters 0.20 ÷ 50.00 step 0.10 [s] Number of days from 31/12/1999 Number of days from 31/12/1999 0 ÷ 65535

1098

1

CosFi Module Threshold CB TAG name User data Dual set CB close time Date of installation CB Date of last maintenance CB Local Bus Analog Value Threshold Startup current activation threshold

0.10 ÷ 10.00 step 0.10 [In]

Standard: 0 = None (free running) 1 = Any Alarm 2 = L Timing 3 = Any Trip 0 ÷ 1000 [s*10-2] 0 = 600 Hz 1 = 1200 Hz 2 = 2400 Hz 3 = 4800 Hz 50 ÷ 95 [10-2]

2/3

0 ÷ 65535

3 2/3 2/3 3 2/3 2/3 2/3

10 ÷ 1000 [In*10-2]

2/3

20 ÷ 5000 [s*10-2]

Table 49 Configuration 3

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

27/45

4.13

PARAMETERS PROTECTION SET1 / SET2 (only for PR123/P - PR333/P)

The following table shows parameters included in protection SET1 and SET2 areas. Column “Rel addr” reports SET1 addresses (1100 ÷ 1178); SET2 addresses (1200 ÷ 1278) can be obtained adding 100 to SET1 addresses. Rel addr

# of item

Name

Range Bit 0 1 2 3 4

1100

1

Prot L configuration

1101

1

Prot L curve type

0÷3

1102 1103 1104 1105

1 1 1 1

Prot L threshold Prot L time Prot L threshold IEC255 Prot L time IEC255

0.40 ÷ 1.00 step 0.01 [In] 3 ÷ 144 step 3 [s] 0.40 ÷ 1.00 step 0.01 [In] 3 ÷ 144 step 3 [s] Bit

1106

1

Prot S configuration

1107 1108 1109 1110 1111 1112 1113 1114

1 1 1 1 1 1 1 1

Prot S curve type Prot S threshold T=k/I2 Prot S time T=k/I2 Prot S threshold T=k Prot S time T=k Prot S start up threshold Prot S start up time Prot S zone selectivity time

1115

1

Prot S2 configuration

1116 1117 1118 1119 1120

1 1 1 1 1

Prot S2 threshold T=k Prot S2 time T=k Prot S2 start up threshold Prot S2 start up time Prot S2 zone selectivity time

1121

1

Prot D configuration

1122 1123 1124 1125 1126 1127

1 1 1 1 1 1

Prot D threshold Prot D time Forward Prot D time Backward Prot D start up threshold Prot D start up time Prot D zone selectivity time

1128

1

Prot I configuration

1129 1130 1131

1 1 1

Prot I threshold Prot I start up threshold Prot I start up time

0 T=k, 1 I2t = k 0.6 ÷ 10.0 step 0.1 [In] 0.05 ÷ 0.8 step 0.01[s] 0.6 ÷ 10.0 step 0.1 [In] 0.05 ÷ 0.8 step 0.01[s] 0.6 ÷ 10.0 step 0,1 [In] 0.10 ÷ 30.00 step 0.01 [s] 0.04 ÷ 0.20 step 0.01 [s]

0.6 ÷ 10.0 step 0.1 [In] 0.05 ÷ 0.8 step 0.01[s] 0.6 ÷ 10.0 step 0,1 [In] 0.10 ÷ 30.00 step 0.01 [s] 0.04 ÷ 0.20 step 0.01 [s]

1,5 ÷ 15 step 0.1 [In] 1,5 ÷ 15 step 0.1 [In] 0.10 ÷ 30.00 step 0.01[s]

Bit = 0 Bit = 1 ----------------Thermal memory = OFF Thermal memory = ON 0: I2t = k 2: 13,5*b/(i-1) 1: 0,14/(i0.02-1) 3: 80*b/(i2-1) 40 ÷ 100 [In*10-2] 300 ÷ 14400 [s*10-2] 40 ÷ 100 [In*10-2] 300 ÷ 14400 [s*10-2]

Bit = 0 Prot disable --Start Up Th= OFF Zone selectivity= OFF Thermal memory= OFF 0÷1 60 ÷ 1000 [In*10-2] 5 ÷ 80 [s*10-2] 60 ÷ 1000 [In*10-2] 5 ÷ 80 [s*10-2] 60 ÷ 1000 [In*10-2] 10 ÷ 3000 [s*10-2] 4 ÷ 20 [s*10-2] Bit Bit = 0 0 Prot disable 1 --2 Start Up Th= OFF 3 Zone selectivity= OFF 4 --60 ÷ 1000 [In*10-2] 5 ÷ 80 [s*10-2] 60 ÷ 1000 [In*10-2] 10 ÷ 3000 [s*10-2] 4 ÷ 20 [s*10-2] Bit Bit = 0 0 Prot disable 1 --2 Start Up Th= OFF 3 Zone selectivity= OFF 4 --60 ÷ 1000 [In*10-2] 20 ÷ 80 [s*10-2] 20 ÷ 80 [s*10-2] 60 ÷ 1000 [In*10-2] 10 ÷ 3000 [s*10-2] 13 ÷ 50 [s*10-2] Bit Bit = 0 0 Prot disable 1 --2 Start Up Th= OFF 3 --4 --150 ÷ 1500 [In*10-2] 150 ÷ 1500 [In*10-2] 10 ÷ 3000 [s*10-2] 0 1 2 3 4

0.6 ÷ 10.0 step 0.1 [In] 0.2 ÷ 0.8 step 0.01 [s] 0.2 ÷ 0.8 step 0.01 [s] 0.6 ÷ 10.0 step 0.1 [In] 0.10 ÷ 30.00 step 0.01[s] 0.13 ÷ 0.50 step 0.01 [s]

PR12x PR33x

Description

Bit = 1 Prot enable --Start Up Th= ON Zone selectivity= ON Thermal memory= ON

--------2/3 2/3 2/3 2/3

2/3 S --2/3 S 2/3 S 2/3 S 2/3 S

2/3 S Bit = 1 Prot enable --Start Up Th= ON Zone selectivity= ON ---

3 S

Bit = 1 Prot enable --Start Up Th= ON Zone selectivity= ON --3

Bit = 1 Prot enable --Start Up Th= ON -----

2/3 --2/3 ----2/3 2/3 MM

(continues)

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

28/45

Rel addr

# of item

1130

1

Prot MM configuration

1131

1

Prot MM threshold

Name

Range Bit

1132

1

Prot G configuration

1133

1

Prot G curve type

1134

1

Prot G threshold T=k/I2

1135

1

Prot G time T=k/I2

1136

1

Prot G threshold T=k

1137 1138 1139 1140

1 1 1 1

Prot G time T=k Prot G start up threshold Prot G start up time Prot G zone selectivity time

1141

1

1142 1143 1144 1145 1146 1147 1148

1 1 1 1 1 1 1

1149

1

1150

1151 1152

1

1 1

Prot U threshold Prot U time

1

Prot UV configuration

1154 1155

1 1

Prot UV threshold Prot UV time

1156

1

Prot OV configuration

1159 1160 1161

1 1 1 1 1

1,5 ÷ 4 step 0.1 [In]

0 T=k, 1 I2t = k

Prot OV threshold Prot OV time

Bit = 1 Prot enable Trip enable Start Up Th= ON Zone selectivity= ON ---

MM

2/3 G 2/3 G --2/3 G

10 ÷ 100 [In*10-2]

233x/333x G

0.20 ÷ 1.00 step 0.02 [In]

20 ÷ 100 [In*10-2]

233x/333 G

0.10 ÷ 1.00 step 0.05 [s]

10 ÷ 100 [s*10-2]

2/3 G

0.10 ÷ 1.00 step 0.02 [In]

10 ÷ 100 [In*10-2]

233x/333x G

0.20 ÷ 1.00 step 0.02 [In]

20 ÷ 100 [In*10-2]

233x/333 G

10 ÷ 100 [s*10-2] 20 ÷ 100 [In*10-2] 10 ÷ 3000 [s*10-2] 4 ÷ 20 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 Start Up Th = OFF

Bit = 1 Prot enable Trip enable Start Up Th = ON

3

Zone selectivity= OFF

Zone selectivity = ON

4

0.10 ÷ 30.00 step 0.01 [s]

--0÷1 20 ÷ 100 [InGext *10-2] 10 ÷ 100 [s*10-2] 20 ÷ 100 [InGext *10-2] 10 ÷ 100 [s*10-2] 20 ÷ 100 [InGext *10-2] 10 ÷ 3000 [s*10-2]

0.04 ÷ 0.20 step 0.01 [s]

4 ÷ 20 [s*10-2]

0.10 ÷ 1.00 step 0.05 [s] 0.20 ÷ 1.00 step 0.02 [In] 0.10 ÷ 30.00 step 0.01[s] 0.04 ÷ 0.20 step 0.01 [s]

0 T=k, 1 I2t = k 0.10 ÷ 1.00 step 0.02 [InGext]

0.10 ÷ 1.00 step 0.05 [s] 0.10 ÷ 1.00 step 0.02 [InGext]

0.10 ÷ 1.00 step 0.05 [s] 0.10 ÷ 1.00 step 0.02 [InGext]

Bit 0 1 2 3 4 5 2 ÷ 90 step 1 [%] 0.5 ÷ 60 step 0.5 [s]

0.50 ÷ 0.95 step 0.01 [Un] 0.1 ÷ 5.0 step 0.1 [s]

1.05 ÷ 1.20 step 0.01 [Un] 0.1 ÷ 5.0 step 0.1 [s]

Prot RV configuration Prot RV threshold Prot RV time

Bit = 1 Prot enable --

0.10 ÷ 1.00 step 0.02 [In]

Prot U configuration

1153

1157 1158

Bit = 0 Prot disable -150 ÷ 400 [In*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 Start Up Th= OFF 3 Zone selectivity= OFF 4 --0÷1 0 1

Prot Ext G configuration

Prot Ext G curve type Prot Ext G threshold T=k/I2 Prot Ext G time T=k/I2 Prot Ext G threshold T=k Prot Ext G time T=k Prot Ext G start up threshold Prot Ext G start up time Prot Ext G zone selectivity time

PR12x PR33x

Description

0.10 ÷ 0.40 step 0.05 [Un] 0.5 ÷ 30.0 step 0.5 [s]

Bit = 0 Prot disable Trip disable ------Current selection 2 ÷ 90 [%] 50 ÷ 6000 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 --50 ÷ 95 [Un*10-2] 10 ÷ 500 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 --105 ÷ 120 [Un*10-2] 10 ÷ 500 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 --10 ÷ 40 [Un*10-2] 50 ÷ 3000 [s*10-2]

2/3 G 2/3 G

--2/3 G MM

Bit = 1 Prot enable Trip enable ------Voltage selection

2/3

Bit = 1 Prot enable Trip enable ---

Bit = 1 Prot enable Trip enable ---

Bit = 1 Prot enable Trip enable ---

2/3 MM

2/3 MM

2/3 MM

(continues) Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

29/45

Rel addr

1162

1163 1164

1165

1166 1167

1168

1169 1170

1171

# of item

1

1 1

1

1 1

1

1 1

1

Name

Range Bit 0 1 2 3 4

Prot RP configuration

Prot RP threshold Prot RP time

-0.10 ÷ -0.30 step 0.02 [Pnt] 0.5 ÷ 25.0 step 0.1 [s]

Prot UF configuration

Prot UF threshold Prot UF time

0,90 ÷ 0.99 step 0.01 [Fn] 0.5 ÷ 3.0 step 0.1 [s]

Prot OF configuration

Prot OF threshold Prot OF time

1,01 ÷ 1.10 step 0.01 [Fn] 0.5 ÷ 3.0 step 0.1 [s]

Prot T configuration

1172

1

Load control configuration

0x0000 ÷ 0x0007

1173 1174 1175

1 1 1

Warning current Iw LC1 threshold LC2 threshold

0.30 ÷ 10.00 step 0.05 [In] 50 ÷ 100 step 1 [%I1] 50 ÷ 100 step 1 [%I1]

1176

1

Prot Rc configuration

Not Used

1177 1178

1 1

Prot Rc threshold Prot Rc time

See Table 51 TAB_TH_Rc See Table 52 TAB_Time_Rc

1179

1

MCR Config

1180 1181

1 1

MCR Threshold MCR Time

6 ÷ 15 step 0.1[In] 0.04 ÷ 0.5 step 0.01 [s]

PR12x PR33x

Description Bit = 0 Prot disable Trip disable ------10 ÷ 30 [-Pnt *10-2] 50 ÷ 2500 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 --3 --4 --90 ÷ 99 [Fn *10-2] 50 ÷ 300 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 --3 --4 --101 ÷ 110 [Fn*10-2] 50 ÷ 300 [s*10-2] Bit Bit = 0 0 ---

Bit = 1 Prot enable Trip enable -------

2/3 MM

Bit = 1 Prot enable Trip enable -------

2/3 MM

Bit = 1 Prot enable Trip enable -------

2/3 MM

Bit = 1 ---

1

Trip disable

Trip enable

2 3 4 Bit 0 1 2

-------

-------

Bit = 0 Bit = 1 Iw Th disabled Iw Th enabled LC1 Th disabled LC1 Th enabled LC2 Th disabled LC2 Th enabled 30 ÷ 1000 [In*10-2] 50 ÷ 100 [%I1] 50 ÷ 100 [%I1] Bit Bit = 0 Bit = 1 0 ----1 ----2 ----3 ----4 ----See Table 51 TAB_TH_Rc See Table 52 TAB_Time_Rc Bit Bit = 0 Bit = 1 0 MCR disable MCR enable 600 ÷ 1500 [In*10-2] 4 ÷ 50 [s*10-2]

2/3

2/3

2/3 Rc MM

2/3

Table 50 Set 1/ Set 2

Value 0 1 2 3 4 5

Threshold 3A 5A 7A 10 A 20 A 30 A

Value 0 1 2 3 4 5 6

Table 51 TAB_TH_Rc

Time 0.06 [s] 0.10 [s] 0.20 [s] 0.30 [s] 0.40 [s] 0.50 [s] 0.80 [s]

Table 52 TAB_Time_Rc

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

30/45

4.14

TRIP HISTORY

Rel addr

# of item

2000

2019 … … … … … … … 2361

Name

19

Trip history N° 1 (new)

19 19 19 19 19 19 19 … 19

PR12x PR33x

Description 0 1 2 3 4 5 6 7÷8 9÷10 11÷12 13÷14 15 16 17 18

MARKER (0 = valid) See Table 54 TAB_TRIP_TYPE Trip Number Date (Number of days from 31/12/1999) Date (MSB = ore, LSB = min) Date (seconds) Date (ms) Current phase L1 Current phase L2 Current phase L3 Current phase Ne Contact wear See Table 54 TAB_TRIP_TYPE See Table 54 TAB_TRIP_TYPE See Table 54 TAB_TRIP_TYPE “ “ “ “ “ “ “ “ “

Trip history N° 2 Trip history N° 3 Trip history N° 4 Trip history N° 5 Trip history N° 6 Trip history N° 7 Trip history N° 8 …. Trip history N° 20 (old)

2/3

Table 53 Trip History Trip type L S S2 D D FW D BW I / MM MCR G

word 1 1 2 3 4 5 6

8

word 16 In Active threshold = value / 512 In Active threshold = value / 512 In Active threshold = value / 512 In Active threshold = value / 512 In Active threshold = value / 512 In Active threshold = value / 512 0x0000 0xABCD Internal Ground Current (rms) Low

word 17 see address 1100 mS selected time mS selected time see address 1121 see address 1121 see address 1121 In Active threshold = value / 512 In Active threshold = value / 512 Internal Ground Current (rms) High

G_EXT

9

External Ground Current (rms) Low

External Ground Current (rms) High

T UV OV RV RP UF OF UN Current UN Voltage EXT Rc Rc TEST Hw Trip Iinst

10 11 12 13 14 15 16

°C temperature = value * 0.073855 V12 line to line voltage (rms) V12 line to line voltage (rms) V0 residual voltage (rms) Total Active Power Low Frequency Frequency 0xABCD V12 line to line voltage (rms) see address 1078 Rc Current (rms) Low Rc Current (rms) Low see address 105 see address 704

see address 705 V23 line to line voltage (rms) V23 line to line voltage (rms) --Total Active Power High Hz Active threshold = value / 100 Hz Active threshold = value / 100 % Active threshold = value / 10 V23 line to line voltage (rms) see address 1076 Rc Current (rms) High Rc Current (rms) High --see address 705

7

17 18 19 20 21 22

word 18 see address 1101 see address 1106 see address 1115 see address 1020 see address 1020 see address 1020 see address 1128 mS selected time In Active threshold = value / 512 InExt Active threshold = value / 1085 (100A) InExt Active threshold = value / 2720 (250A) InExt Active threshold = value / 1270 (400A) InExt Active threshold = value / 2540 (800A) see address 704 V31 line to line voltage (rms) V31 line to line voltage (rms) ----mS selected time mS selected time mS selected time V31 line to line voltage (rms) see address 1077 Amp. Active threshold = value / 166.7 Amp. Active threshold = value / 166.7 --see address 105

Table 54 TAB_TRIP_TYPE

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

31/45

4.15 Rel addr

MEASURE HISTORY # of item

Name 0 1

2500

2524 2548 … 3052 3076

24

24 24 24 24 24

PR12x PR33x

Description

Measure history n° 1 (new)

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

Measure history n° 2 Measure history n° 3 … Measure history n° 24 Measure history n° 25 (old)

MARKER (0 = valid) History code: 0 = NORMAL_HISTORY 1 = POWER_UP 2 = NEW_PERIOD Period from last save (minutes) Number of days from 31/12/1999 MSB = Hour, LSB = minute Total mean active power (LSW) Total mean active power (MSW) Total maximum active power (LSW) Total maximum active power (MSW) Maximum current phase (0=L1, 1=L2, 2=L3, 3=Ne) Maximum current (LSW) Maximum current (MSW) Maximum line to line voltage phase (0=V12, 1=V23, 2=V31) Maximum line to line voltage Minimum line to line voltage phase (0=V12, 1=V23, 2=V31) Minimum line to line voltage Total mean reactive power (LSW) Total mean reactive power (MSW) Total maximum reactive power (LSW) Total maximum reactive power (MSW) Total mean apparent power (LSW) Total mean apparent power (MSW) Total maximum apparent power (LSW) Total maximum apparent power (MSW) “ “ “ “ “

2/3

Table 55 Measure History

4.16 Rel addr

LOG EVENTS # of item

Name

Description

3300

6

Log event n° 1 (new)

3306 3312 … 3768 3774

6 6 6 6 6

Log event n° 2 Log event n° 3 … Log event n° 79 Log event n° 80 (old)

PR12x PR33x

MARKER (0 = valid) See Table 64 TAB_LOG_EVENTS Number of days from 31/12/1999 MSB = Hour, LSB = minute Seconds Milliseconds “ “ “ “ “

2/3

Table 56 Log events

4.17 Rel addr 4000 4128 4256 4384

WAVEFORMS # of item 128 128 128 128

Name Buffer waveform channel: L1 or U12 Buffer waveform channel: L2 or U23 Buffer waveform channel: L3 or U31 Buffer waveform channel: NE

Description

PR12x PR33x

[A], [V *10-1] [A], [V *10-1] [A], [V *10-1] [A]

3

Table 57 Waveforms

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

32/45

5.

TABLES Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

VT nominal 100 115 120 190 208 220 230 240 277 347 380 400 415 440 480 500 550 600 660 690 910 950 1000 1150

Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13

256 ÷ 65535

Bit = 1 Relay K51/1 latched Relay K51/2 latched Relay K51/3 latched Relay K51/4 latched Relay K51/6 latched Relay K51/7 latched Relay K51/8 latched Contact K51/1 NC Contact K51/2 NC Contact K51/3 NC Contact K51/4 NC Contact K51/6 NC Contact K51/7 NC Contact K51/8 NC

Table 60 TAB_RELAYS_K51_CONFIG

Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7

Table 58 TAB_UN Value 0 1 2 3 4 5 6 7 8 9 10 11

Bit = 0 Relay K51/1 not latched Relay K51/2 not latched Relay K51/3 not latched Relay K51/4 not latched Relay K51/6 not latched Relay K51/7 not latched Relay K51/8 not latched Contact K51/1 NO Contact K51/2 NO Contact K51/3 NO Contact K51/4 NO Contact K51/6 NO Contact K51/7 NO Contact K51/8 NO

Bit = 0 Relay P1 not latched Relay P2 not latched Relay P3 not latched Relay P4 not latched Contact P1 NO Contact P2 NO Contact P3 NO Contact P4 NO

Bit = 1 Relay P1 Latched Relay P2 Latched Relay P3 Latched Relay P4 Latched Contact P1 NC Contact P2 NC Contact P3 NC Contact P4 NC

Table 61 TAB_P_RELE_CONFIG

Description None L pre-alarm L timing S timing L trip S trip I trip G trip Any trip Any Alarm LC1 LC2 Custom (see RELAYS AND DATA LOGGER “CUSTOM” SETTING)

Table 59 TAB_RELAYS_FUNCTION

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

33/45

Value 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126

CB type E1B800/3P E1B1000/3P E1B1250/3P E1B1600/3P E1N800/3P E1N1000/3P E1N1250/3P E1N1600/3P E2B1600/3P E2B2000/3P E2N1000/3P E2N1250/3P E2N1600/3P E2N2000/3P E2S800/3P E2S1000/3P E2S1250/3P E2S1600/3P E2S2000/3P E2L1250/3P E2L1600/3P E3N2500/3P E3N3200/3P E3S1000/3P E3S1250/3P E3S1600/3P E3S2000/3P E3S2500/3P E3S3200/3P E3H800/3P E3H1000/3P E3H1250/3P E3H1600/3P E3H2000/3P E3H2500/3P E3H3200/3P E3V800/3P E3V1250/3P E3V1600/3P E3V2000/3P E3V2500/3P E3V3200/3P E3L2000/3P E3L2500/3P E4S4000/3P --E4H3200/3P --E4H4000/3P --E4V3200/3P E4V4000/3P E6H4000/3P E6H5000/3P --E6H6300/3P --E6V-A6000/3P E6V4000/3P E6V5000/3P E6V6300/3P E1B-A800/3P E1B-A1200/3P E2B-A1600/3P

Value 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99 101 103 105 107 109 111 113 115 117 119 121 123 125 127

CB type E1B800/4P E1B1000/4P E1B1250/4P E1B1600/4P E1N800/4P E1N1000/4P E1N1250/4P E1N1600/4P E2B1600/4P E2B2000/4P E2N1000/4P E2N1250/4P E2N1600/4P E2N2000/4P E2S800/4P E2S1000/4P E2S1250/4P E2S1600/4P E2S2000/4P E2L1250/4P E2L1600/4P E3N2500/4P E3N3200/4P E3S1000/4P E3S1250/4P E3S1600/4P E3S2000/4P E3S2500/4P E3S3200/4P E3H800/4P E3H1000/4P E3H1250/4P E3H1600/4P E3H2000/4P E3H2500/4P E3H3200/4P E3V800/4P E3V1250/4P E3V1600/4P E3V2000/4P E3V2500/4P E3V3200/4P E3L2000/4P E3L2500/4P E4S4000/4P E4S/f4000/4P E4H3200/4P E4H/f3200/4P E4H4000/4P E4H/f4000/4P E4V3200/4P E4V4000/4P E6H4000/4P E6H5000/4P E6H/f5000/4P E6H6300/4P E6H/f6300/4P E6V-A6000/4P E6V4000/4P E6V5000/4P E6V6300/4P E1B-A800/4P E1B-A1200/4P E2B-A1600/4P

Standard IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC UL IEC IEC IEC UL UL UL

Value 128 130 132 134 136 138 140 142 144 146 148 150 152 154 156 158 160 162 164 166 168 170 172 174 176 178 180 182 184 186 188 190 192 194 196 198 200 202 204 206 208 210 212 214 216 218 220 222 224 226 228 230 232 234 236 238 240 242 244 246 248 250 252 254

CB type E2N-A1200/3P E2N-A1600/3P E2S-A1200/3P E2S-A1600/3P E3N-A2000/3P E3N-A2500/3P E3S-A1200/3P E3S-A1600/3P E3S-A2000/3P E3S-A2500/3P E3H-A1200/3P E3H-A1600/3P E3H-A2000/3P E3H-A2500/3P E3V-A1200/3P E3V-A1600/3P E3V-A2000/3P E3V-A2500/3P E4S-A3200/3P E4S-A3600/3P E4H-A3200/3P E4H-A3600/3P E4V-A3200/3P E4V-A3600/3P E6H-A4000/3P E6H-A5000/3P E6V-A4000/3P E6V-A5000/3P --E1N-A800/3P E1N-A1200/3P E2N-A800/3P E2S-A800/3P E2H-A800/3P E2H-A1200/3P E2H-A1600/3P E3S-A800/3P E3S-A3200/3P E3H-A800/3P E3H-A3200/3P E3V-A800/3P E3V-A3200/3P ----E4L-A3200/3P E4L-A3600/3P ----E6L-A4000/3P E6L-A5000/3P E3X-A800/3P E3X-A1200/3P E3X-A1600/3P E3X-A2000/3P E6X-A4000/3P E6X-A5000/3P ----E1B-A250/3P E1N-A250/3P E2S-A250/3P E2H-A250/3P E1N250/3P E2S250/3P

Value 129 131 133 135 137 139 141 143 145 147 149 151 153 155 157 159 161 163 165 167 169 171 173 175 177 179 181 183 185 187 189 191 193 195 197 199 201 203 205 207 209 211 213 215 217 219 221 223 225 227 229 231 233 235 237 239 241 243 245 247 249 251 253 255

CB type E2N-A1200/4P E2N-A1600/4P E2S-A1200/4P E2S-A1600/4P E3N-A2000/4P E3N-A2500/4P E3S-A1200/4P E3S-A1600/4P E3S-A2000/4P E3S-A2500/4P E3H-A1200/4P E3H-A1600/4P E3H-A2000/4P E3H-A2500/4P E3V-A1200/4P E3V-A1600/4P E3V-A2000/4P E3V-A2500/4P E4S-A3200/4P E4S-A3600/4P E4H-A3200/4P E4H-A3600/4P E4V-A3200/4P E4V-A3600/4P E6H-A4000/4P E6H-A5000/4P E6V-A4000/4P E6V-A5000/4P E6H/f4000/4P E1N-A800/4P E1N-A1200/4P E2N-A800/4P E2S-A800/4P E2H-A800/4P E2H-A1200/4P E2H-A1600/4P E3S-A800/4P E3S-A3200/4P E3H-A800/4P E3H-A3200/4P E3V-A800/4P E3V-A3200/4P E4H-A/f3200/4P E4H-A/f3600/4P E4L-A3200/4P E4L-A3600/4P E6H-A/f4000/4P E6H-A/f5000/4P E6L-A4000/4P E6L-A5000/4P E3X-A800/4P E3X-A1200/4P E3X-A1600/4P E3X-A2000/4P E6X-A4000/4P E6X-A5000/4P E6X-A/f4000/4P E6X-A/f5000/4P E1B-A250/4P E1N-A250/4P E2S-A250/4P E2H-A250/4P E1N250/4P E2S250/4P

Standard UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL IEC UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL IEC IEC

Modbus system Interface for relays PR122-3 and PR332-3

Scale

Table 62 TAB_CB_TYPE Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

1SDH000556R0001

Page NO.

34/45

Value 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122

CB type T7S800 /3P T7S1000/3P T7S1250/3P T7S1600/3P T7H800 /3P T7H1000/3P T7H1250/3P T7H1600/3P T7L800 /3P T7L1000/3P T7L1250/3P T7L1600/3P T7V800 /3P T7V1000/3P T7V1250/3P T7S1200/3P T7H1200/3P T7L1200/3P X1B630/3P X1B800/3P X1B1000/3P X1B1250/3P X1B1600/3P X1N630/3P X1N800/3P X1N1000/3P X1N1250/3P X1N1600/3P X1L630/3P X1L800/3P X1L1000/3P X1L1250/3P X1B800/3P X1B1200/3P X1N800/3P X1N1200/3P X1L800/3P X1L1200/3P X1B800/3P X1B1200/3P X1B1600/3P X1N800/3P X1N1200/3P X1N1600/3P X1L800/3P X1L1200/3P X1V800/3P X1V1200/3P T8L2000/3P T8L2500/3P T8L3200/3P T8V2000/3P T8V2500/3P T8V3200/3P T8V1600/3P T8V2000/3P T8V2500/3P T8V3000/3P T7S1000/3P T7H1000/3P T7L1000/3P T7X800/3P

Value 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99 101 103 105 107 109 111 113 115 117 119 121 123

CB type T7S800 /4P T7S1000/4P T7S1250/4P T7S1600/4P T7H800 /4P T7H1000/4P T7H1250/4P T7H1600/4P T7L800 /4P T7L1000/4P T7L1250/4P T7L1600/4P T7V800 /4P T7V1000/4P T7V1250/4P T7S1200/4P T7H1200/4P T7L1200/4P X1B630/4P X1B800/4P X1B1000/4P X1B1250/4P X1B1600/4P X1N630/4P X1N800/4P X1N1000/4P X1N1250/4P X1N1600/4P X1L630/4P X1L800/4P X1L1000/4P X1L1250/4P X1B800/4P X1B1200/4P X1N800/4P X1N1200/4P X1L800/4P X1L1200/4P X1B800/4P X1B1200/4P X1B1600/4P X1N800/4P X1N1200/4P X1N1600/4P X1L800/4P X1L1200/4P X1V800/4P X1V1200/4P T8L2000/3P T8L2500/3P T8L3200/3P T8V2000/3P T8V2500/3P T8V3200/3P T8V1600/3P T8V2000/3P T8V2500/3P T8V3000/3P T7S1000/3P T7H1000/3P T7L1000/3P T7X800/3P

Standard IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC UL489 UL489 UL489 IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC UL1066 UL1066 UL1066 UL1066 UL1066 UL1066 UL489 UL489 UL489 UL489 UL489 UL489 UL489 UL489 UL489 UL489 IEC IEC IEC IEC IEC IEC UL489 UL489 UL489 UL489 UL489 UL489 UL489 IEC

Table 63 TAB_CB_TYPE_33x

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

35/45

Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46

Event type Parameters changed Signaling reset CB isolated CB connected CB open CB closed CB status defined CB status undefined Internal bus OK Internal bus fault Trip command fail Local mode operating mode Remote mode operating mode Test session closed Test session opene Test unit not connected Test unit connected Set B OFF Set B ON Harmonic distortion OFF Harmonic distortion ON Cw Pre-alarm OFF Cw Pre-alarm ON Cw Alarm OFF Cw Alarm ON L Pre-alarm OFF L Pre-alarm ON L Timing OFF L Timing ON S Timing OFF S Timing ON S2 Timing OFF S2 Timing ON G Timing OFF G Timing ON G Alarm OFF G Alarm ON Gext Timing OFF Gext Timing ON Gext Alarm OFF Gext Alarm ON T Warning OFF T Warning ON T Alarm OFF T Alarm ON T Alarm Block OFF T Alarm Block ON

Value 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93

Event type D Timing OFF D Timing ON U Timing OFF U Timing ON U Alarm OFF U Alarm ON Uv Timing OFF Uv Timing ON Uv Alarm OFF Uv Alarm ON Ov Timing OFF Ov Timing ON Ov Alarm OFF Ov Alarm ON Rv Timing OFF Rv Timing ON Rv Alarm OFF Rv Alarm ON Rp Timing OFF Rp Timing ON Rp Alarm OFF Rp Alarm ON Uf Timing OFF Uf Timing ON Uf Alarm OFF Uf Alarm ON Of Timing OFF Of Timing ON Of Alarm OFF Of Alarm ON Freq Alarm OFF Freq Alarm ON I-warning Alarm OFF I-warning Alarm ON Load control threshold nr.1 OFF Load control threshold nr.1 ON Load control threshold nr.2 OFF Load control threshold nr.2 ON Sensor continuity check 1 Alarm OFF Sensor continuity check 1 Alarm ON Sensor continuity check 2 Alarm OFF Sensor continuity check 2 Alarm ON Sensor continuity check 3 Alarm OFF Sensor continuity check 3 Alarm ON Sensor continuity check Ne Alarm OFF Sensor continuity check Ne Alarm ON Sensor continuity check Gext Alarm OFF

Value 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135

Event type Sensor continuity check Gext Alarm ON Trip coil continuity check Alarm OFF Trip coil continuity check Alarm ON Rating Plug Alarm OFF Rating Plug Alarm ON Installation error OFF Installation error ON Power factor error OFF Power factor error ON Phase cycle error OFF Phase cycle error ON Configuration error ON Configuration error OFF CB status error OFF CB status error ON L tripped S tripped S2 tripped I tripped Iinst tripped G tripped Gext tripped T tripped D tripped U tripped UV tripped OV tripped RV tripped RP tripped UF tripped OF tripped Electronic trip test Simulated trip from test unit External input trip Hardware Error Trip 24dc auxiliary supply On Trip Reset History Trip Reset History Measure Reset Energy Reset PR120/V supply On Test connector supply On

Table 64 TAB_LOG_EVENTS

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

36/45

6.

APPENDIX

6.1

PARAMETER PROGRAMMING WARNING: Through the system bus it is allowed to open a programming session only in REMOTE functioning mode. There is a validity programming session timeout of 5minutes once expired the session is aborted; to extend it of 5 more minutes more it is sufficient to re-send an open programming session command

Programming session correctly handled: Open session Send parameters

Stop session

Check parameters OK Save in device nonError code = 0 volatile memory Progr. ok = 1 Progr. fail = 1 Session = 1

Progr. ok = 1 Progr. fail = 0 Session = 0 Par. changed = 1

Programming session open (system bus programming session = 1)

Programming failed: Open session Send parameters

Stop session

Check parameters Reload device internal error: set Error code parameters

Progr. ok = 1 Progr. fail = 1 Session = 1

Progr. ok = 0 Progr. fail = 1 Session = 0

Programming session open (system bus programming session = 1)

Programming aborted: Open session Send parameters

Abort session

Reload device internal parameters

Progr. ok = 1 Progr. fail = 1 Session = 1

Model

Programming session open (system bus programming session = 1)

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Progr. ok = 0 Progr. fail = 0 Session = 0

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

37/45

6.2

RELAYS AND DATA LOGGER “CUSTOM” SETTING

Through the system bus it is possible to configure data logger trigger and programmable relays function in a more sophisticated mode, in the following way: Writing in “Data logger Trigger Type” or “Loc Bus Relay X Function” or “PX Function” registers (a value greater than list values) is possible to configure custom functionality as described in the following table. 15 OR AND

WORD (bits) 14 13 12 11 10 9 8 7 Byte placement (offset from 0x100 address) in the STATE; numeration start from 1.

6

5

4

3

2

1

0

Bits mask to be monitored in the byte

Table 65 relay and Datalogger custom setting Bit 7 ÷ 0: bit mask used bye trigger or function. Bit 14 ÷ 8: byte offset in the device STATE. Bit 15: if 0 means OR function among selected bits (mask), if 1 means AND function. Example 1: to configure data logger trigger type to stop when at least one of the listed conditions occur ( L tripped, S tripped, I tripped and G tripped) the value to write is: Bit 7 ÷ 0 = 00101011 (1 in correspondence of desired bits). Bit 14 ÷ 8 = 00001111 = 15 ( byte containing conditions is the 15th of STATE). Bit 15 = 0 (OR function). Therefore Data logger Trigger Type = 0x0F2B Example 2: to configure data logger trigger type to stop when all the listed conditions occur (UV Timing, RV Timing and RP timing) the value to write is: Bit 7 ÷ 0 = 10100010 (1 in correspondence of desired bits). Bit 14 ÷ 8 = 0001001 = 9 ( byte containing conditions is the 15th of STATE). Bit 15 = 1 (AND function). Therefore Data logger Trigger Type = 0x19A2

6.3

MEASURE HISTORY DATA STRUCTURE

The measure history log (0) contains the following information:  Marker  History code  Saving period  Day  Hour + minute  Total mean active power  Total maximum active power  Maximum current and relative phase  Maximum line voltage and relative phase  Minimum line voltage and relative phase The Marker (word length) is a general code for all non-volatile memory structure used to distinguish valid data (marker = 0x0000) from not valid data (marker = 0x5555) The history code has 3 types of recorded data: Nr. 0 = Normal record. Nr. 1 = First record after a supply power-up. Nr. 2 = First record after a saving period change.

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

38/45

Saving period mean, in the case nr.0 and nr.2, the elapsed time in minutes from previous record. In case nr.1 an almost empty structure is recorded only to show power supply returns; only Marker and History code have mean. Day, hour and minutes are the time-stamp of structure recording time. Could take place the following situations with e.g. saving period = 1hour. 1. Normal situation (history code 0): 1h

2.

1h

For e.g. after 27minutes from last recording time the Saving period is changed to 10minutes (history code 2): 1h

3.

1h

27m

10m

For e.g. after 14minutes from last recording time there is an auxiliary power supply failure and then a new power-up (history code 1): 1h

14m



Power-up

Time gap considered NULL

6.4

1h

WAVEFORM AND HARMONICS

Sending a “start acquisition waveform + harmonics” command the acquisition of waveform samples (4.17) and the relative harmonics calculation can be obtained. There are two available commands: 1. Start acquisition: the waveform device resource is allocated to system bus, samples are acquired simultaneously from several channel and the harmonic calculation starts on selected channel. When calculation finish the glitch STATE bit “waveform available” is set. 2. Stop acquisition: the waveform device resource is released and become available for other requests (e.g. from HMI device); an eventual harmonic calculation in progress will be concluded before releasing the resource. Start acquisition command need a parameter field defining on which channel the harmonic calculation takes place; following table explains parameter and result link. Parameter value (L1) (L2) (L3) (Ne) (V12) (V23) (V31)

Table 57 Waveforms

Table 44 Harmonic measures L1 harmonic calc L2 harmonic calc L3 harmonic calc Ne harmonic calc V12 harmonic calc V23 harmonic calc V31 harmonic calc

Samples from L1, L2, L3 and Ne currents acquired simultaneously. Samples from V12, V23, and V31 line voltages acquired simultaneously.

Table 66 waveform and harmonics WARNING: All currents or all line voltages are acquired simultaneously but only for the selected channel there will be the harmonic calculation. Therefore sending a start command on a different channel ( in the same current or voltage block) allows to don’t start a new acquisition but only to calculate harmonics; sending command on the same channel it will generate a refresh of all samples before harmonic calculation.

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

39/45

Sequence example: start L1 : L1, L2, L3, Ne samples acquisition and L1 harmonic calc start L2 : only L2 harmonics calc; no new sample acquisition start L2 : new samples acquisition (refresh functionality) and L2 harmonic calc start V23 : line voltages samples acquisition and V23 harmonic calc Resource allocation diagram: Start command

Waveform available

Start command

Waveform available

Stop command

Allocated resource WARNING: While the resource is allocated none could use it (an exception busy response will be returned); the STATE flag “waveform session status” show the allocation There is a 5minutes allocation timeout of resource once expired the resource is released. To continue the resource allocation 5minutes more it is sufficient to send a new start acquisition command before timeout ending

6.5

CB STATE INFORMATION

The device using the following dedicated input reports CB state:  CB open  CB close  CB connected / withdrawn  Springs charged The device filters and checks CB state producing the following information:  CB open / close  CB state undefined  CB state error  CB connected / withdrawn  Springs charged / discharged State CB open/close State CB undefined State CB error

Value 0 = Open Input CB open = 1 + Input CB close = 0 + NO flowing current Value 0 = Open Input CB open = 1 + Input CB close = 0 + NO flowing current OR Input CB open = 0 + Input CB close = 1 Value 0 = Open Other cases

State Springs

Input CB open = 0 + Input CB close = 1

Filtered by 30 ms Notes

1 = Close Input CB open = Input CB close

Filtered by 30 ms Notes

1 = Close

Input CB open = 1 + Input CB close = 0 + Current flowing

Filtered by 30 ms

Value

State CB connected

Notes

1 = Close

0 = Open

Notes

1 = Close

Input CB connected = 0

Input CB connected = 1

Filtered by 1000 ms

Value 0 = Open Input charged springs = 0

1 = Close Input charged springs = 1

Notes Filtered by 200 ms

Table 67 CB state information

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

40/45

6.6

STATISTICAL DATA

Device produces same statistical data relevant to system bus communication and to CB operations: 1.

communication statistical data a. received messages nr. b. received messages nr. With crc error c. set messages nr. d. Slave Busy exception responses nr. e. Total exception responses nr. Must be: a = b + c + nr. Broadcast messages Data described above is NOT updated in self-supply device mode.

2.

CB operation statistical data a. Contact wear b. Total Protection Trip number

3.

CB operation statistical data NOT updated in self-supply device mode c. total operation nr. d. manual operation nr. e. protection trip nr. f. protection trip fail nr. g. trip test nr.

The relationship between them: c = d + e + f + g , b ≥ e + f. The following diagram shows the CB statistical data calculation method:

No

New OPEN?

No

No

No

Auxiliary supply present?

Trip open?

(c)Total operation += 1 Protection open?

Protection open?

(b)Total protection trip nr. += 1

(d)Manual operation +=1

(e)Protection trip += 1

No

Trip Failed?

No

(g)Trip test + =1

(f)Trip fail + =1

Save statistical data in non-volatile memory

END

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

41/45

6.7

COMMANDS EXECUTION CONDITIONS

To the condition below reported must be appended: 1. commands are accepted only in REMOTE operation device mode. 2. with TEST unit connected only “CB OPEN” command is accepted Command type Dummy command Trip reset Signaling reset Communication statistics reset Log events reset Start programming session Abort programming session Stop programming session

Action No action Reset trip STATE bits Reset signaling module and local bus unit STATE bits Reset statistical data Reset events data Open programming session Abort programming session End programming session

CB Open

Activate YO

CB Close

Activate YC

CB reset Wink toggle command History measure reset Energy counters reset Data logger trigger restart

Reset trip STATE bits LCD backlight wink ON or OFF Reset measure data Reset Energy data Waiting trigger status

Data logger stop

Trigger immediately

Waveform + harmonics acquisition start

Open waveform acquisition session

Waveform + harmonics acquisition stop

End waveform acquisition session

Acceptance conditions NO protection timings Programming session opened Programming session opened, NO consistency check errors, NO protection timings CB connected, CB open command NOT executing, CB close command NOT executing CB connected, CB OPEN, CB NOT undefined, NO trip executing, CB open command NOT executing, CB close command NOT executing NO trip execution, Data logger enabled, Triggered acquisition completed. NO trip execution, Data logger enabled, Triggered acquisition completed. PR123 unit, I max current ≤ 2 In, Imin. Current ≥ 0.1 In, NE sensor present for NE, L1, L2, L3 sensor connected, PR120/V module present for V12, V23, V31 PR123 unit, Waveform session opened.

Table 68 Commands acceptance conditions

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

42/45

6.8

MEASURE LIMITS AND REPRESENTATION Measure

Special value Not available Too low Saturation

Description

Active, reactive and phase power (P1, P2, P3, Q1, Q2, Q3, S1, S2, S3)

Not available Too low Positive saturation Negative saturation

Sensor disconnected I < Imin I > Imax Sensor disconnected, IG > Igmax IG < Igmin External toroid absent, Sensor disconnected IGEXT < IGEXTmin IGEXT > IGEXTmax Rc toroid absent, Toroid disconnected IRC < IRC min. IRC > IRC max. All sensors disconnected, All current values < Imin PR120/V module absent V < Vmin V > Vmax PR120/V module absent, Sensor disconnected, I < Imin, V < Vmin | P | < Pmin P > Pmax P < - Pmax

Total power (P,Q, S)

Not available

All phase power not available

Currents

Internal ground current

Not available Too low Not available

External ground current

Too low Saturation Not available

Rc current

Too low Saturation

Maximum current phase

Not available

Voltages

Not available Too low Saturation

Active, reactive and apparent energy

Positive saturation Negative saturation

Total cos

Not available

Peak factor

Not available Not available

Frequency (see note)

Harmonic amplitude Contact wear

Too low Too high Not available Saturation Saturation

231-1

E> E < -231 S or P not available | S | or | P | < Pmin S or P > Pmax S or P < -Pmax Sensor disconnected, I < Imin Peak PR120/V module absent or V maximum frequency Amplitude < Harm min Amplitude > Harm max CW > 100%

Modbus data

Local HMI value

0xFFFFFFFF 0 Imax

  I > xxx A

0xFFFFFFFF



0



0xFFFFFFFF



0 Imax

 I > xxx A

0xFFFFFFFF



0 Imax

 I > xxx A

0



0xFFFF 0 Vmax

  V > xxx V

0x7FFFFFFF



0 Pmax - Pmax

 P > xxx kW P < xxx kW

0x7FFFFFFF



0x7FFFFFFF 0x80000000

E > xxx kWh E < xxx kWh

0x7FFF



0xFFFF



0xFFFF



Minimum frequency Maximum frequency 0 Harm max 65000

Freq < Freq min Freq > Freq max  > Harm max 100%

Table 69 Measure limits and representation Legend: Imin Imin Peak Imax Igmin Igmax IGEXTmin IGEXTmax IRCmin IRCmax

= 0,05 In = 0,2 In = 16 In = 0,1 In = 16 In = 0,1 In = 4 In = 2 InRc = 32,5 InRc

Vmin Vmax Pmin Pmax Fmin Fmax Harm min Harm max

= 5,7 V = 922V = 0,5 In * 5,7 V = 16 In * 922V = 29,5 Hz (with hysteresis up to 31 Hz) = 80,5 Hz (with hysteresis up to 79 Hz) =2% = 500 %

Note: the measure of frequency is subject hysteresis in the intervals 29,5 Hz ÷ 31 Hz and 79 Hz ÷ 80,5 Hz, therefore it is valid in the range 31 Hz ≤ freq ≤ 79 Hz.

6.9

CONTACT WEAR

The contact wear is calculated as the usury sum owed at every single CB open and it’s explicit in % (0 ÷ 100[%]): It’s available in format 0 ÷ 65000 (0=0%, 65000=100%), therefore to obtain the percentage is necessary to divide the value for 650. Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

43/45

7.

REVISION HISTORY

7.1

B0431 (16/12/2015)

Added 1 2 3 5 1 2 6

Par.2.3: added Slave ID for PR332/P MM Par.3: inserted codes for PR332/P MM on the table Par.3.1: inserted references and notes to PR332/P MM Par.4.4, 4.6, 4.11, 4.12, 4.13, 4.14: completed compatibility column with references to PR332/P MM Par.4.13: added 1130 and 1131 alternative to startup threshold I Par.4.14: inserted trip MM as alternative to I Added Revision History section

Modified 1 Deleted 1

Model

L2572

L4612

L3987

B0341

Apparatus



Doc.No

Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001

Scale Page NO.

44/45

Power and productivity for a better worldTM

