Modbus System Interface
Modbus system Interface for Protection relays PR122/P and PR123/P + communication module PR120/D-M, mounted on CB New Emax Protection relays PR332/P and PR333/P + communication module PR330/D-M, mounted on CB Emax X1, Tmax T7 and Tmax T8
Power and productivity for a better worldTM
Index 1. INTRODUCTION....................................................................................................................................................................................... 4 1.1 SCOPE ....................................................................................................................................................................................................... 4 1.2 APPLICABILITY .......................................................................................................................................................................................... 4 1.3 ACRONYM AND DEFINITION .................................................................................................................................................................... 4 1.3.1. Acronym ........................................................................................................................................................................................... 4 1.3.2. Definitions ........................................................................................................................................................................................ 5 1.4 BIBLIOGRAPY ............................................................................................................................................................................................ 5 2. MODBUS PROTOCOL ............................................................................................................................................................................... 6 2.1 Communication Parameters .................................................................................................................................................................... 6 2.2 Device RTU Framing ................................................................................................................................................................................. 6 2.2.1. Silent interval < 4 char between two characters inside the message .............................................................................................. 6 2.2.2. Silent interval 4 char between two characters inside the message .............................................................................................. 7 2.2.3. New frame before 4 character silent interval at the end of a frame................................................................................................ 7 2.3 Unit identification .................................................................................................................................................................................... 7 2.4 Available Modbus functions ..................................................................................................................................................................... 7 2.4.1. Function 03 (03h) Read Holding Registers ....................................................................................................................................... 8 2.4.2. Function 04 (04h) Read Input Registers ........................................................................................................................................... 8 2.4.3. Function 06 (06h) Write Single Register ........................................................................................................................................... 8 2.4.4. Function 08 (08h) Diagnostic ............................................................................................................................................................ 8 2.4.5. Function 16 (10h) Write Multiple Registers ..................................................................................................................................... 8 2.4.6. Function 17 (11h) Report slave ID .................................................................................................................................................... 9 2.4.7. Function 70 (46h) Read Extended Registers ..................................................................................................................................... 9 2.5 Exception responses ................................................................................................................................................................................ 9 2.5.1. Exception occurrences ................................................................................................................................................................... 10 3. MODBUS MAP ...................................................................................................................................................................................... 11 3.1 Unit configuration .................................................................................................................................................................................. 12 3.1.1. Protection....................................................................................................................................................................................... 12 3.1.2. MEASURES ...................................................................................................................................................................................... 13 3.2 REGISTERS MAP ..................................................................................................................................................................................... 14 3.3 LOGGER MAP (extended registers) ........................................................................................................................................................ 15 4. DESCRIPTION OF REGISTERS .................................................................................................................................................................. 17 4.1 COMMANDS ........................................................................................................................................................................................... 17 4.2 STATISTICAL DATA .................................................................................................................................................................................. 18 4.3 PROGR FAIL ERROR CODE ...................................................................................................................................................................... 18 4.4 STATE ..................................................................................................................................................................................................... 20 4.5 TIME ....................................................................................................................................................................................................... 23 4.6 RUN-TIME MEASURES ............................................................................................................................................................................ 23 4.7 HARMONIC MEASURES .......................................................................................................................................................................... 24 4.8 INFORMATION ....................................................................................................................................................................................... 24 4.9 LOCAL BUS DATA AREA .......................................................................................................................................................................... 24 4.10 CONFIGURATION1.................................................................................................................................................................................. 25 4.11 PARAMETERS CONFIGURATION2 ........................................................................................................................................................... 25 4.12 PARAMETERS CONFIGURATION3 ........................................................................................................................................................... 26 4.13 PARAMETERS PROTECTION SET1 / SET2 (only for PR123/P - PR333/P) ................................................................................................. 28 4.14 TRIP HISTORY ......................................................................................................................................................................................... 31 4.15 MEASURE HISTORY ................................................................................................................................................................................ 32 4.16 LOG EVENTS ........................................................................................................................................................................................... 32 4.17 WAVEFORMS ......................................................................................................................................................................................... 32 5. TABLES .................................................................................................................................................................................................. 33 6. APPENDIX ............................................................................................................................................................................................. 37 6.1 PARAMETER PROGRAMMING ................................................................................................................................................................ 37 6.2 RELAYS AND DATA LOGGER “CUSTOM” SETTING .................................................................................................................................. 38 6.3 MEASURE HISTORY DATA STRUCTURE ................................................................................................................................................... 38 6.4 WAVEFORM AND HARMONICS .............................................................................................................................................................. 39 6.5 CB STATE INFORMATION ....................................................................................................................................................................... 40 6.6 STATISTICAL DATA .................................................................................................................................................................................. 41 6.7 COMMANDS EXECUTION CONDITIONS .................................................................................................................................................. 42 6.8 MEASURE LIMITS AND REPRESENTATION .............................................................................................................................................. 43 6.9 CONTACT WEAR ..................................................................................................................................................................................... 43 7. REVISION HISTORY ................................................................................................................................................................................ 44 7.1 B0431 (16/12/2015) ............................................................................................................................................................................... 44
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
2/45
Index of Tables TABLE 1 ALARMS TYPE ..................................................................................................................................................................................................... 5 TABLE 2 AND 3 AVAILABLE AND DEFAULT COMMUNICATION PARAMETERS .................................................................................................................................... 6 TABLE 4 UNIT IDENTIFICATION ........................................................................................................................................................................................... 7 TABLE 5 AVAILABLE MODBUS FUNCTIONS ............................................................................................................................................................................. 7 TABLE 6 AND 7 FUNCTION 3 QUERY AND RESPONSE ................................................................................................................................................................ 8 TABLE 8 AND 9 FUNCTION 4 QUERY AND RESPONSE ................................................................................................................................................................ 8 TABLE 10 AND 11 FUNCTION 6 QUERY AND RESPONSE ............................................................................................................................................................ 8 TABLE 12 AND 13 FUNCTION 8 QUERY AND RESPONSE ............................................................................................................................................................ 8 TABLE 14 AND 15 FUNCTION 16 QUERY AND RESPONSE .......................................................................................................................................................... 8 TABLE 16 AND 17 FUNCTION 17 QUERY AND RESPONSE .......................................................................................................................................................... 9 TABLE 18 AND 19 FUNCTION 70 QUERY AND RESPONSE .......................................................................................................................................................... 9 TABLE 20, 21, 22, 23 AND 24 EXCEPTION RESPONSES ........................................................................................................................................................... 9 TABLE 25 EXCEPTION RESPONSES ..................................................................................................................................................................................... 10 TABLE 26 CODE MEANING .............................................................................................................................................................................................. 11 TABLE 26 PROTECTIONS ................................................................................................................................................................................................. 12 TABLE 27 ACTIVE MEASURES ........................................................................................................................................................................................... 13 TABLE 28 REGISTERS MAP ............................................................................................................................................................................................... 14 TABLE 29 LOGGER MAP .................................................................................................................................................................................................. 15 TABLE 30 TAB_INPUT_OUTPUT ................................................................................................................................................................................. 16 TABLE 31 TAB_TRIP .................................................................................................................................................................................................... 16 TABLE 32 TAB_ALARM_1 ........................................................................................................................................................................................... 16 TABLE 33 TAB_ALARM_2 ........................................................................................................................................................................................... 16 TABLE 34 COMMANDS ................................................................................................................................................................................................... 17 TABLE 35 TAB_COMMANDS ...................................................................................................................................................................................... 17 TABLE 36 TAB_WAV ................................................................................................................................................................................................... 17 TABLE 37 STATISTICAL DATA ........................................................................................................................................................................................... 18 TABLE 38 PROGRAM FAIL ERROR ..................................................................................................................................................................................... 18 TABLE 39 TAB_PAR_ERR_CODE ................................................................................................................................................................................. 19 TABLE 40 STATE ........................................................................................................................................................................................................... 22 TABLE 41 TIME ............................................................................................................................................................................................................ 23 TABLE 42 RUN-TIME MEASURES....................................................................................................................................................................................... 24 TABLE 43 HARMONIC MEASURES ...................................................................................................................................................................................... 24 TABLE 44 INFORMATION ................................................................................................................................................................................................ 24 TABLE 45 LOCAL BUS DATA AREA ...................................................................................................................................................................................... 24 TABLE 46 CONFIGURATION 1........................................................................................................................................................................................... 25 TABLE 47 CONFIGURATION 2........................................................................................................................................................................................... 25 TABLE 48 CONFIGURATION 3........................................................................................................................................................................................... 27 TABLE 49 SET 1/ SET 2 .................................................................................................................................................................................................. 30 TABLE 50 TAB_TH_RC ................................................................................................................................................................................................. 30 TABLE 51 TAB_TIME_RC .............................................................................................................................................................................................. 30 TABLE 52 TRIP HISTORY ................................................................................................................................................................................................. 31 TABLE 53 TAB_TRIP_TYPE .......................................................................................................................................................................................... 31 TABLE 54 MEASURE HISTORY .......................................................................................................................................................................................... 32 TABLE 55 LOG EVENTS ................................................................................................................................................................................................... 32 TABLE 56 WAVEFORMS.................................................................................................................................................................................................. 32 TABLE 57 TAB_UN ...................................................................................................................................................................................................... 33 TABLE 58 TAB_RELAYS_FUNCTION ............................................................................................................................................................................ 33 TABLE 59 TAB_RELAYS_K51_CONFIG......................................................................................................................................................................... 33 TABLE 60 TAB_P_RELE_CONFIG ................................................................................................................................................................................. 33 TABLE 61 TAB_CB_TYPE ............................................................................................................................................................................................. 34 TABLE 62 TAB_CB_TYPE_33X ..................................................................................................................................................................................... 35 TABLE 63 TAB_LOG_EVENTS ...................................................................................................................................................................................... 36 TABLE 64 RELAY AND DATALOGGER CUSTOM SETTING ........................................................................................................................................................... 38 TABLE 65 WAVEFORM AND HARMONICS ............................................................................................................................................................................. 39 TABLE 66 CB STATE INFORMATION ................................................................................................................................................................................... 40 TABLE 67 COMMANDS ACCEPTANCE CONDITIONS ................................................................................................................................................................. 42 TABLE 68 MEASURE LIMITS AND REPRESENTATION................................................................................................................................................................ 43
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
3/45
1.
INTRODUCTION
The documents refer to the system bus Modbus interface of relays PR122/P and PR123/P mounted on New Emax power circuit breaker, and PR332/P and PR333/P mounted on Emax X1, Tmax T7 and Tmax T8 power circuit breaker.
1.1
SCOPE
The aim of this document is to indicate the addresses of all measures, parameters and information available in PR122/3 and PR332/3 relays. Moreover it explains the procedure to read information and to program the parameters of the above mentioned protection units.
1.2
APPLICABILITY
This document applies to the device PR122/P - PR123/P equipped with the communication module PR120/D-M, and PR332/P PR333/P equipped with the communication module PR330/D-M. This version of the document refer to relays SW version 2.0 or major.
1.3 1.3.1.
ACRONYM AND DEFINITION Acronym
CB PR12x PR33x
Circuit Breaker Both protection relays PR122/P and PR123/P Both protection relays PR332/P and PR333/P
AI AO LSb LSB MSb MSB
Analog Input Analog Output Least Significant Bit Least Significant Byte Most Significant Bit Most Significant Byte
BOOL BYTE WORD DWORD LWORD SINT USINT INT UINT DINT UDINT LINT ULINT STRING UNICODE
Bit or Boolean (IEC 61131-3) Byte (IEC 61131-3) Word (IEC 61131-3) Double word (IEC 61131-3) Long Word (IEC 61131-3) Short Integer (IEC 61131-3) Unsigned Short Integer (IEC 61131-3) Single Integer (IEC 61131-3) Unsigned Integer (IEC 61131-3) Double Integer (IEC 61131-3) Unsigned Double Integer (IEC 61131-3) Long Integer (IEC 61131-3) Unsigned Long Integer (IEC 61131-3) Text String (IEC 61131-3) Unicode (IEC 61131-3)
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
4/45
1.3.2.
Definitions
ALARM:
there are two types of alarm:
Alarm Type
Definition
Alarm
It’s similar to a status. A Trip Reset is NOT necessary to reset it. Ex. L Pre-Alarm, S Alarm, ...
Trip
Only a command can reset it, i.e. a new alarm won’t be signalled until the reset. Ex. L Tripped, S Tripped, ... Table 1 Alarms type
BUFFER: CB RESET: DEVICE: EVENT: PARAMETER: PROTECTION TRIPS: PROTECTION UNIT: REGISTER: REMOTE SYSTEM: STATUS: TRIP COMMAND FAIL:
TRIP RESET:
1.4
meaningful part of a Modbus Map section. It’s defined by the Modbus Map of the device. event (Any Trip) /alarm reset of any information related to the (last) trip. Protection Unit information that signals a normal (foreseen) device behaviour. Typically, the producer of an event is the device, while the consumer is the system. information that allows configuration of device functionality (e.g. a protection algorithm). sum of real protection trips ( LSIG trips). ‘Real’ means ‘not caused by the Test Unit. PR122/3 and PR332/3 electronic device that implements protection algorithms the least analogue information container (one word = 2 bytes) a device (SCADA) which behaves as Modbus Master on the external bus. It polls the information provided by the device and sends to it commands and parameters. information that represents the dynamics of a functionality (e.g. the CB or a protection algorithm). It can be managed (i.e. set/reset) only by the device itself. after a protection trip, with relevant opening command to the release, CB stays in CLOSED state. In this case, the device tries to open the CB by starting a back-up procedure. Meanwhile, the device tries also to open the CB using the YO (through the I/O). command equal to CB Reset
BIBLIOGRAPY
Schneider Automation Inc., ‘Modicon MODBUS Protocol Reference Guide’
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
5/45
2.
MODBUS PROTOCOL
2.1
Communication Parameters Baud rate 9600/19200
Address 1 247
Addressing type Standard / ABB
Physical protocol E, 8, 1 / O, 8, 1 / N, 8, 2 / N, 8, 1
The default unit configuration is: Baud rate Address 19200 247
Addressing type Standard
Physical protocol E, 8, 1
Table 2 and 3 Available and default communication parameters
2.2
Device RTU Framing
The allowed inter-character silent interval has been relaxed from ‘at least 2 characters’ to ‘at least 4 characters’ (the same silent interval to recognize the end of a message). This means:
2.2.1.
Silent interval < 4 char between two characters inside the message
In this case the receiver filters the silent interval and the following characters will be appended to those already received. The difference from the protocol specification is: 1.
Silent interval < 2 char between two characters inside the message Transmitter
Silent interval
4 char 1
2
4 char 1
2
...
3
n 4 char
Receiver 3
n 4 char
...
The behaviour is exactly as specified by the protocol. 2.
Silent interval 2 char and < 4 char between two characters inside the message The received characters are NOT flushed and the following ones will be appended. Silent interval
Transmitter 4 char 1
2
4 char 1
2
3
...
n 4 char
Receiver
3
n 4 char
...
Note that after flushing, the standard protocol specification allows: reception of the remaining characters of a partially received message reception of a completely new message
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
6/45
The device behaviour doesn’t cover the second case because it always appends new incoming characters to the previous ones, leading to a CRC error. So the behaviour is exactly the same if and only if the incoming characters are NOT a new message. In this case the received packet will lead to a CRC error and the CRC error counter will be incremented.
2.2.2.
Silent interval 4 char between two characters inside the message
If the message transmission is NOT ended, all the previously received characters are managed as a message because this is exactly the protocol specification regarding the end of a message.
2.2.3.
New frame before 4 character silent interval at the end of a frame
In this case the receiver filters the silent interval and the following characters (of the new frame) will be appended to those already received. This will lead to a CRC error. Silent interval
Transmitter 4 char 1
2
n
...
3
1
2
3
...
m 4 char
Receiver 4 char 1
2
n
...
3
1
2
3
...
m 4 char
So the CRC error counter will count both the ‘real’ CRC errors and the inter-character errors.
2.3
Unit identification Unit PR122/P PR123/P PR332/P PR333/P PR332/P MM
Slave ID 0x51 0x52 0x55 0x56 0x25
Table 4 Unit identification
2.4
Available Modbus functions Function Code 03 (03h) 04 (04h) 06 (06h) Funct. Code Subf. Code 08 (08h) 00 (00H) Function Code 16 (10h) 17 (11h) 70 (46h)
Name Read Holding Registers Read Input Registers Write Single Register Name Diagnostic Loop back Name Write Multiple Registers Report Slave ID Read Extended Registers
Applicable to AO AI AO Applicable to --Applicable to AO --Extended Reg.
Table 5 Available Modbus functions Note: all queries must respect the limitation of maximum modbus message length of 256 byte Legend: AA = slave address (1 247) cl = byte low of CRC ch = byte high of CRC Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
7/45
2.4.1.
Function 03 (03h) Read Holding Registers
Query Addr Function Starting address AA 03h High Low Note: number of registers ≤ 125 Response Addr AA
Function 03h
Byte count nn
Number of registers High Low
Register value High Low
… …
Crc ch
cl
Register value High Low
Crc ch
cl
Table 6 and 7 Function 3 query and response
2.4.2.
Function 04 (04h) Read Input Registers
Query Addr Function Starting address AA 04h High Low Note: number of registers ≤ 125 Response Addr AA
Function 04h
Byte count nn
Nr of input registers High Low
Input register High Low
… …
Crc ch
cl
Input register High Low
Crc ch
cl
Table 8 and 9 Function 4 query and response
2.4.3.
Function 06 (06h) Write Single Register
Query Addr AA
Function 06h
Register address High Low
Register value High Low
ch
Crc
Response (echo of query) Addr Function Register address AA 06h High Low
Register value High Low
ch
cl Crc cl
Table 10 and 11 Function 6 query and response
2.4.4.
Function 08 (08h) Diagnostic
Query Addr Function Sub function AA 08h 00h 00h Note: 0 ≤ Number of data bytes ≤ 250, any value Response (echo of query) Addr Function AA 08h
Sub function 00h 00h
Data yy
… …
ch
Crc
Data yy
… …
ch
cl
Crc cl
Table 12 and 13 Function 8 query and response
2.4.5.
Function 16 (10h) Write Multiple Registers
Query Addr Funct Starting addr AA 10h High Low Note: number of registers ≤ 123 Response Addr AA
Function 10h
Num of registers High Low
Starting address High Low
Byte count Nn
Number of register High Low
Reg value High Low
… …
Reg value High Low
Crc ch
cl
Crc ch
cl
Table 14 and 15 Function 16 query and response Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
8/45
2.4.6.
Function 17 (11h) Report slave ID
Query Addr AA
Function 11h
Response Addr Function AA 11h
Crc ch
Cl
Byte count 16h
Slave ID ID
Run indicator 0FFh
Sw Version High Low
Events addr High Low
Device Ser Nr 16 byte (ASCII)
Crc ch cl
Table 16 and 17 Function 17 query and response
2.4.7.
Function 70 (46h) Read Extended Registers
Query Addr Function Byte count AA 46h 07h Notes: 1. File number ≤ 3 2. Starting address ≤ 65535 3. Number of registers ≤ 125 Response Addr AA
Funct 46h
Byte count Nn
Ref type 06h
Ref type 06h
File number High Low
Reg value High Low
… …
Starting address High Low
Reg value High Low
Number of registers High Low
Crc ch
cl
Crc ch
cl
Table 18 and 19 Function 70 query and response
2.5
Exception responses
Illegal function: Addr AA
Function Function + 80h
Exception code 01h
ch
Crc
Addr AA
Function Function + 80h
Exception code 02h
ch
Addr AA
Function Function + 80h
Exception code 03h
ch
Addr AA
Function Function + 80h
Exception code 04h
Addr AA
Function Function + 80h
Exception code 06h
cl
Illegal data address: Crc cl
Illegal data value: Crc cl
Slave device failure: Crc ch
cl
Slave device busy: Crc ch
cl
Table 20, 21, 22, 23 and 24 Exception responses
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
9/45
2.5.1.
Exception occurrences Exception 01 Illegal function
02 Illegal data address Starting address not valid
03
Starting address not valid
04
04 Slave device failure
03 Illegal data value - Invalid query length - Requested number of register too large - Address out of modbus map - Invalid query length
Reading attempt of busy non-volatile memory at present
- Requested number of register too large - Address out of modbus map
- Starting address not valid - Write of TIME information not allowed with this function
QUERY FUNCTION
06
06 Slave device busy
- Local state - Programming session already open
Invalid query length
- Programming session not open - Sub function ≠ 00 00
08
- Invalid query length - Invalid query length - Number of register too large Starting address not valid
16
- Address out of modbus map - Command not available - Command parameter filed not valid - Wrong Time
17
Parameters error check after a stop programming session command
- Local state - Programming session already open - Programming session not open - Command acceptance conditions not verified
Invalid query length - Invalid query length Starting address not valid
70
- Requested number of register too large - Address out of modbus map - Field Ref Type not correct
Reading attempt of busy data logger
- Field Byte count not correct Other
Function not available
Table 25 Exception responses
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
10/45
3.
MODBUS MAP
Data format LINT (Acronym 1.3.1) (4 byte = 2 word = 2 register) is transferred with low significant part at lower modbus address (LOW-HIGH) Register i LS word Register i + 1 MS word Instead within WORD data the most significant byte is transferred first (as in MODBUS RTU standard) MS byte LS byte Since the PR122/P and PR332/P information set is a subset of PR123/P and PR333/P set, it was decided to represent them in only one general map from which is possible to deduce information of each device. PR123/P PR333/P
PR122/P PR332/P
For this purpose in each table it was foreseen a column named PR12x/PR33x in which, row by row, are shown the device and the product execution where the information has mean. The explanation of how to read column PR12x/PR33x follows: PR12x Meaning PR33x 3 Information available for PR123/P and PR333/P LSI/LSIG and NOT available for other units 3 Information available for PR123/P and PR333/P LSIG and NOT available for other units G 2/3 Information available for PR122/P and PR332/P LSI/LSIG, PR123/P and PR333/P LSI/LSIG and NOT available for S other units 2/3 Information available for PR122/P and PR332/P LSIG, PR123/P and PR333/P LSIG and NOT available for other units G 2/3 Information available for PR122/P and PR332/P LI/LSI/LSIG, PR123/P and PR333/P LSI/LSIG 2/3 The contained information in the line is worth for PR122/P, PR332/P and PR123/P,PR333/P Rc versions and is NOT Rc AVAILABLE for the other units The contained information in the line is worth for PR332/P and PR333/P versions and is NOT AVAILABLE for the 233x/333x PR122/P and PR123/P units The contained information in the line is worth for PR122/P and PR123/P versions and is NOT AVAILABLE for the 233x/333x PR332/P and PR333/P units MM The contained information in the line is worth for PR332/P MM unit and is NOT AVAILABLE for all the others units MM Not available for PR332/P MM unit Table 26 Code meaning WARNING: Parameters declared NOT AVALAIBLE for a unit are treated in the same way than the others, they are saved and checked in validity range but they are not used by the protections. Reading parameters declared NOT AVAILABLE could return not consistent data in respect to the ones previously programmed. Example: Program on PR122 the directional protection (NOT AVAILABLE for PR122) with the following data: Prot D configuration = 0x0001 (Prot enable = ON) Prot D Prot threshold Forward = 1 In Programming will be accepted because data is valid but D protection will remain disabled, therefore reading the parameters just programmed will return: Prot D configuration = 0x0000 (Prot enable = OFF) Prot D Prot threshold Forward = 1 In
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
11/45
3.1
Unit configuration
3.1.1.
Protection
The following table shows the available protections for each type of device and possible necessary conditions:
PR122/P - PR332/P L
PR123/P - PR333/P
LI
LSI
LSIG
LSIRc
LSIG MM(5)
LSI
LSIG
S S2
D
MEAS(1)
MEAS(1)
I
( )
( )
G
NOSGR 4
MCR
4
( ) 4
( ) 4
( ) 4
( )
(4)
4
MM Gext
SGR
Gext (Idn)
SGR
RCM
RCM(1)
RCM(1)
U
UV
MEAS
MEAS
MEAS
MEAS(1)
MEAS(1)
OV
MEAS
MEAS
MEAS
MEAS(1)
MEAS(1)
RV
MEAS QP
MEAS QP
MEAS QP
MEAS(1) QP
MEAS(1) QP
RP
MEAS
MEAS
MEAS
MEAS(1)
MEAS(1)
UF
MEAS
MEAS
MEAS
MEAS(1)
MEAS(1)
OF
MEAS
MEAS
MEAS
MEAS(1)
MEAS(1)
T
LC
(2)
(2)
(2)
(2)
(2)
(2)
(2)
Hw prot.
Phase rotation(3)
MEAS(1)
3
1
CosΦ module( ) Frequency Error(3)
MEAS
MEAS
MEAS
Harm distortion(3)
MEAS(1)
MEAS( )
MEAS(1)
MEAS(1)
MEAS(1)
Table 27 Protections Legend: : NOSGR: SGR: RCM: MEAS: QP: (1): (2): (3): (4): (5):
Model
Available without condition External Toroid absent (Ext Toroid Type (addr 1032) = 0) External Toroid = Source Ground Return (Ext Toroid Type (addr 1032) = 1) External Toroid = Residual Current (Ext Toroid Type (addr 1032) = 2) + Measuring Module present Measuring Module present “CB 4 pole” otherwise neutral voltage present (Unit configuration (addr 1020) bit 5 = 1) Measuring Module always present on PR122 LSIRc, PR332 LSIRc and PR123, PR333 Load control always enabled on state bits but feasible only if present signaling module or output unit on local bus (ex: Flex Interface) Warning functions. Activable in alternative to I protection. LSIG MM version available only with PR332/P MM
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
12/45
3.1.2.
MEASURES
The following table shows the available measures for each type of device and possible necessary conditions:
PR122/P - PR332/P
PR123/P - PR333/P
LI
LSI
LSIG
LSIRc
LSIG MM
LSI
LSIG
Line currents
Neutral current
Ne
Ne
Ne
Ne
Ne
Ne
Ne
MEAS QP
MEAS(1) QP
SGR or RCM(1) MEAS(1) QP
MEAS
MEAS(1)
MEAS(1)
Ground current
NOSGR
Line to neutral voltages
MEAS QP
MEAS QP
SGR or RCM MEAS QP
Line to line voltages
MEAS
MEAS
MEAS
External toroid ground current
RCM(1)
Line to neutral power
MEAS QP
MEAS QP
MEAS QP
MEAS QP
MEAS(1) QP
MEAS(1) QP
Total power
MEAS
MEAS
MEAS
MEAS
MEAS(1)
MEAS(1)
Power factor
MEAS
MEAS
MEAS
MEAS
MEAS(1)
MEAS(1)
Net frequency
MEAS
MEAS
MEAS
MEAS
1
MEAS( )
MEAS(1)
Peak factor
Neutral crest factor
Ne
Ne
Ne
Ne
Ne
Ne
Ne
MEAS
MEAS
MEAS
MEAS(1)
MEAS(1)
Trip history
Log event history
Measures history
Contact wear
Energy
Current waveform
Neutral current waveform
Ne
Ne
MEAS(1)
MEAS(1)
Line to line voltage waveform Current harmonics Neutral current harmonics Line to line voltage harmonics
Data logger
Ne
Ne
MEAS(1)
MEAS(1)
Table 28 Active measures Legend: : QP: MEAS: (1): Ne: NOSGR: SGR: RCM:
Model
Available without condition “CB 4 pole” otherwise neutral voltage present (Unit configuration (addr 1020) bit 5 = 1) Module Measuring present Measuring Module always present on PR122 LSIRc, PR332 LSIRc and PR123, PR333 Neutral connection present (CB 4 pole o 3 pole + neutral) External Toroid absent (Ext Toroid Type (addr 1032) = 0) External Toroid = Source Ground Return (Ext Toroid Type (addr 1032) = 1) External Toroid = Residual Current (Ext Toroid Type (addr 1032) = 2) + Measuring Module present.
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
13/45
3.2
REGISTERS MAP AI [30001]
AO [40001]
Relative Address
Function 4 (2.4.2)
0
STATISTICAL DATA (4.2)
50
PROGR. FAIL ERROR CODE (4.3)
100
STATE(4.4)
200
RUN TIME MEASURES (4.5)
600
HARMONICS MEASURES (4.7)
700
INFORMATION (4.8)
800
LOCAL BUS DATA AREA (4.9)
1000
PAR. CONFIG1 ACTUAL (4.10)
1020
PAR. CONFIG2 ACTUAL (4.11)
1050
PAR. CONFIG3 ACTUAL (4.12)
PAR. CONFIG3 NEW (*)
1100
PAR. PROT. SET1 ACTUAL (4.13)
PAR. PROT SET1 NEW (*)
1200
PAR. PROT. SET2 ACTUAL (4.13)
PAR. PROT SET2 NEW (*)
2000
TRIP HISTORY (4.14)
2500
MEASURES HISTORY (4.15)
3300
LOG EVENTS (4.16)
4000
WAVEFORMS (4.17)
Function:
16 (2.4.5)
3 (2.4.1)
6 (2.4.3)
COMMANDS (4.1)
TIME (*)
Table 29 Registers map WARNING: *NON-VOLATILE memory : could be busy (busy exception response) (*) Parameters that can be written only during an open programming session Example of table reading: RUN-TIME MEASURES analog input absolute address: 30001+ offset (200) = 30201 The relative address is offset (200) = 200
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
14/45
3.3
LOGGER MAP (extended registers) WARNING: Addressing type “ABB” cannot be used for these registers, therefore the address field will be always included between 1 and 65536 for all addressing methods Extended Reg. (60000)
File Number
Sample Number
Function 70 Description
Rel. address 0
Samples 0 (Old) File 0 (Old)
Samples 1
Notes
PR12x PR33x
L1 current sample
(1)
2/3
1
L2 current sample
(1)
2/3
2
L3 current sample
(1)
2/3
3
Ne current sample
(1)
2/3
4
External Ground (SGR/Rc sensor) current sample
(4)
2/3 G
5
L1 MSP current sample
(2)
2/3
6
L2 MSP current sample
(2)
2/3
7
L3 MSP current sample
(2)
2/3
8
Ne MSP current sample
(2)
2/3
9
V1 voltage sample
(3)
2/3
10
V2 voltage sample
(3)
2/3
11
V3 voltage sample
(3)
2/3
12
Input/Output status
13
Alarms 1 status
14
Alarm 2 status
15
Trip 1 status
See Table 31 TAB_INPUT_OUTPUT See Table 33 TAB_ALARM_1 See Table 34 TAB_ALARM_2
2/3 2/3 2/3
See Table 32 TAB_TRIP
2/3
16 ÷ 31
“
“
2/3
…
…
“
“
2/3
Samples 4095 (New)
65519 ÷ 65535
“
“
2/3
File 1
Samples 0 ÷ Samples 4095
0 ÷ 65535
“
“
2/3
File 2
Samples 0 ÷ Samples 4095
0 ÷ 65535
“
“
2/3
File 3 (New)
Samples 0 ÷ Samples 4095
0 ÷ 65535
“
“
2/3
Table 30 Logger map Notes: (1) Signal derivative samples (538 rms means 1In rms @ 50Hz) (2) Signal derivative samples For PR12x and PR33x with DSP version before of 2.05: If net frequency = 50Hz 1 means 72,6 Arms @ 50Hz If net frequency = 60Hz 1 means 72,6 Arms @ 60Hz For PR33x with DSP version 2.05: If net frequency = 50Hz 1 means 52,3 Arms @ 50Hz If net frequency = 60Hz 1 means 52,3 Arms @ 60Hz (3) Signal samples (750 rms means 71,04Vrms) (4) If SGR connected Signal derivate samples (552 rms means 46,84 Arms @ 50Hz for Toroid of 100/250A) Signal derivate samples (552 rms means 160 Arms @ 50Hz for Toroid of 400/800A) If Rc connected Signal samples (371 rms means 1 Arms)
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
15/45
Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Bit
Description
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Local bus Relay 1 contact Local bus Relay 2 contact Local bus Relay 3 contact Local bus Relay 4 contact --Local bus Relay 6 contact Local bus Relay 7 contact Local bus Relay 8 contact Relay P1 contact Relay P2 contact Relay P3 contact Relay P4 contact S zone selectivity input S zone selectivity output G zone selectivity input G zone selectivity output
Table 33 TAB_ALARM_1
Table 31 TAB_INPUT_OUTPUT
Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Description L tripped S tripped S2 tripped I tripped Iinst tripped G tripped G ext tripped T tripped D tripped U tripped UV tripped OV tripped RV tripped RP tripped UF tripped OF tripped
Bit
Description
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
U Alarm (Blocked Trip) UV Timing UV Alarm (Blocked Trip) OV Timing OV Alarm (Blocked Trip) RV Timing RV Alarm (Blocked Trip) RP Timing RP Alarm (Blocked Trip) UF Timing UF Alarm (Blocked Trip) OF Timing OF Alarm (Blocked Trip) Frequency Error Iw Warning LC1 Alarm
Table 34 TAB_ALARM_2
Table 32 TAB_TRIP
Model
Description Harmonic distortion > 2.1 Contact Wear Pre-alarm Contact Wear Alarm L Pre-alarm L Timing S Timing S2 Timing G Timing G Alarm (Blocked Trip) G Ext Timing G Ext Alarm (Blocked Trip) T Pre-alarm T Alarm T Alarm (Blocked Trip) D Timing U Timing
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
16/45
4.
DESCRIPTION OF REGISTERS
4.1
COMMANDS Rel addr
# of item
Name
Notes
0 1
1 1
COMMAND TYPE COMMAND PARAMETER
Table 36 TAB_COMMANDS Table 36 TAB_COMMANDS
PR12x PR33x 2/3 2/3
Table 35 Commands To execute a command it is requested to write together to COMMAND TYPE field the number desired and to COMMAND PARAMETER field the optional parameter value (0 if not needed) with 17odbus function 16 also if the parameters value is not necessary. Example 1: to send “Trip reset” command, write “01” at COMMAND TYPE address and “00” at COMMAND PARAMETER address (parameter not necessary for this command). Example 2: to send “Waveform + harmonics acquisition start” Command on L2 phase, write “16” at COMMAND TYPE address and “02” at COMMAND PARAMETER address.
Following the command list table with pertinent command parameters. Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Command type
Parameter
Dummy command Trip reset Signaling reset Communication statistics reset Log events reset Start programming session Abort programming session Stop programming session CB Open CB Close CB reset Wink toggle command History measure reset Energy counters reset Data logger trigger restart Data logger stop Waveform + harmonics acquisition start Waveform + harmonics acquisition stop
don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care don’t care Table 37 TAB_WAV don’t care
PR12x PR33x 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 3 3
Table 36 TAB_COMMANDS Value 0 1 2 3 4 5 6 7
Channel --L1 L2 L3 NE V12 V23 V31
Table 37 TAB_WAV
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
17/45
4.2 Rel addr
STATISTICAL DATA # of item
Description
Representation
Notes
PR12x PR33x
0
1
Received message number
0 ÷ 65535
NOT updated in self-supply Received msg n° = Received msg n° with crc error + Sent msg n° + Received broadcast msg n°.
1
1
Received message number with crc error
0 ÷ 65535
NOT updated in self-supply
2/3
2
1
Sent message number
0 ÷ 65535
NOT updated in self-supply Total exception response number included
2/3
3
1
Slave Busy exception number responses
0 ÷ 65535
NOT updated in self-supply
2/3
4
1
Total exception response number
0 ÷ 65535
NOT updated in self-supply Slave Busy exception number response included
2/3
5
1
Contact wear
0 ÷ 65000 (100% = 65000) CW > 100% 65000
Updated in self-supply too
2/3
6
1
Total trip protection number
0 ÷ 65535
7
1
Total operation number
0 ÷ 65535
8
1
Manual operation number
0 ÷ 65535
9
1
Total trip protection number
0 ÷ 65535
10 11
1 1
Trip protection fail number Trip test number
0 ÷ 65535 0 ÷ 65535
Updated in self-supply too Protection trip fail number included NOT updated in self-supply Total operation n° = Manual operation n° + protection trip n° + protection trip fail n° + trip test n°. NOT updated in self-supply NOT updated in self-supply Protection trip fail number NOT included NOT updated in self-supply NOT updated in self-supply
2/3
2/3
2/3
2/3 2/3 2/3 2/3
Table 38 Statistical Data WARNING: Registers from address 0 to 4 compose the communication statistics, registers from address 6 to 11 compose CB operation statistics
4.3 Rel addr
PROGR FAIL ERROR CODE # of item
Description
PR12x PR33x
Note 0: No error 1 ÷ 999: See Table 40 TAB_PAR_ERR_CODE
50
1
Programming Fail Error Code
Fail Error refer to SET 1 (1xxx) and SET 2 (2xxxx) x001: L Th ≥ S Th x002: S Th ≥ I Th x003: L Th ≥ S2 Th x004: S2 Th ≥ I Th x005: L Th ≥ D Th x006: D Th ≥ I Th x007: (Only with CB UL) G Th > 1200A x008: (Only with CB UL) Startup G Th > 1200A x009: Selettivita di zona D attiva contemp. A sel zona S o S2 o G o Gext x010: (Only with CB UL) Tempo S > 400 ms x011: (Only with CB UL) Tempo S2 > 400 ms x012: (Only with CB UL) Tempo G > 400 ms x013: (Only with CB UL) Tempo Gext > 400 ms x014: (Only with CB UL) Curva L diversa da I2t=k
2/3
Common: 3001: Error during language exchange 3002: Error on Rc Sense 3003: Error on internal neutral configuration
Table 39 Program Fail Error
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
18/45
Par error code min max Step 0 1 2 3 4 5 6 7 8 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194
Parameters address Not used 1020 1050 1021 1022 1023 1024 1025 1026 1051 1083 1028 1029 Reserved Reserved 1095 1096 1084 1085 1086 1087 1088 1089 1090 1091 1092 1093 1027 1094 1032 1097 1098 1052 1067 1053 1054 1055 1056 1057 1058 1059 1060 1061 1062 1063 1064 1065 1066 1068 1069 1070 1071 1072 1073 1074 1075
Par error code min max Step 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389
Parameters address 1076 1077 1078 1079 1080 1081 1082 1100 1101 1102 1104 1103 1105 1106 1107 1108 1110 1112 1109 1111 1113 1114 1115 1116 1118 1117 1119 1120 1121 1122 1125 1123 1124 1126 1127 1128 1129 1130 1131 1132 1133 1134 1136 1138 1135 1137 1139 1140 1141 1142 1143 1145 1147 1144 1146 1148 1149
Par error code min max Step 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560
Parameters address 1176 1177 1178 1150 1151 1152 1153 1154 1155 1156 1157 1158 1159 1160 1161 1162 1163 1164 1165 1166 1167 1168 1169 1170 1171 1172 1173 1174 1175 1179 1180 1181 1200 1201 1202 1204 1203 1205 1206 1207 1208 1210 1212 1209 1211 1213 1214 1215 1216 1218 1217 1219 1220 1221 1222 1225 1223
Par error code min max Step 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 631 632 633 634 635 636 637 638 639 640 641 642 643 644 645 646 647 648 649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666 667 668 669 670 671 672 673 674 675 676 677 678 679 680 681 682 683 684 685 686 687 688 689 690 691 692 693 694 695 696 697 698 699 700 701 702 703 704 705 706 707 708 709 710 711 712 713 714 715 716 717 718 719 720 721 722 723 724 725 726 727 728 729 730 731
Parameters address 1224 1226 1227 1228 1229 1230 1231 1232 1233 1234 1236 1238 1235 1237 1239 1240 1241 1242 1243 1245 1247 1244 1246 1248 1249 1276 1277 1278 1250 1251 1252 1253 1254 1255 1256 1257 1258 1259 1260 1261 1262 1263 1264 1265 1266 1267 1268 1269 1270 1271 1272 1273 1274 1275 1279 1280 1281
Table 40 TAB_PAR_ERR_CODE Legend: min: max: step:
Model
the code inserted is lower than the minimum available (ex: Par Err Code=252 inserted at address 1103 a value< 300) the code inserted is higher than the maximum available (ex: Par Err Code=253 inserted at address 1103 a value > 14400) the code inserted has not the requested step (ex: Par Err Code=254 inserted at address 1103 a value = 302)
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
19/45
4.4
STATE
Symbols (↑) and (↕) marks state bits whose variation are traced in the events log; (↑) means that variation from 0 to 1 is traced, instead (↕) means that variation from 1 to 0 is traced too. Rel addr
# of item
100
101
102
1
1
1
Name
STATE 1 GLITCH Note 4
STATE 2 FLAGS
STATE 3 FLAGS
Bit
Description
Notes
PR12x PR33x 2/3 2/3 3 2/3 2/3 2/3 2/3 2/3 3 ---------------
BIT 0 (↑) BIT 1 BIT 2 BIT 3 (↑) BIT 4 BIT 5 BIT 6 BIT 7 BIT 8 BIT 9 BIT 10 BIT 11 BIT 12 BIT 13 BIT 14 BIT 15
Parameter changed Historical Measure Update Waveform available Signaling Reset Trip Reset CB Reset Dummy Command Energy Reset Dual Set Change ---------------
1 = Parameter(s) changed 1 = History measures updated 1 = Waveform available 1 = Signaling reset 1 = Trip Reset Command executed 1 = CB Reset Command executed 1 = Dummy Command executed 1 =Energy Reset Command executed 1 = Dual Set Changed ---------------
BIT 0
Any Alarm / Timing / Warning
OR of alarms
2/3
BIT 1
Any Trip
OR of Trips (latched)
2/3
BIT 2
CB tripped
1 = CB tripped
2/3
BIT 3 (↕) BIT 4 (↕)
CB connected / isolated CB open/closed
0 = Isolated, 1 = Connected 0 = Open, 1 = Closed
2/3 2/3
BIT 5 (↕)
CB undefined
1 = Undefined
2/3
BIT 6 (↕)
No communication on Local Bus
1 = No communication on LB
2/3
BIT 7 BIT 8 (↑) BIT 9 (↕)
Springs charged/discharged Trip command fail Local / Remote Operating Mode
0 = Discharged, 1 = Charged 1 = Trip command failed 0 = Local, 1 = Remote
2/3 2/3 2/3
BIT 10
Programming OK
1 = Programming OK
2/3
BIT 11
Programming Fail
1 = Programming Failed
2/3
BIT 12
Internal Bus programming session
1 = Bus SSI session open
2/3
BIT 13
Test Bus programming session
1 = Bus Test session open
2/3
BIT 14 BIT 15
Local Bus programming session System Bus programming session
1 = Bus Local session open 1 = Bus Ext session open
2/3 2/3
BIT 0 (↕) BIT 1 (↕) BIT 2 BIT 3 BIT 4 BIT 5 BIT 6 BIT 7 BIT 8 BIT 9 BIT 10 (↕) BIT 11 BIT 12 BIT 13 BIT 14 BIT 15
Test Session Test Unit connected BT unit present Signaling module present Dialog unit present Measuring unit present Display Off for high temp Waiting Trigger Data logger Triggered Data logger stopped Active Dual Set Wink ON Signaling Module Input Status KK function Waveform session status Local Bus Digital Input
1 = Test session open 1 = Test unit connected 1 = BT unit present 1 = Signaling module present 1 = Dialog unit present 1 = Measuring unit present 1 = Display Off 1 =Waiting trigger 1 = Triggered 1 = Stopped 0 = SET1, 1 = SET2 0 = OFF, 1 = ON 0 = Not active, 1 = Active 0 = OFF, 1 = ON 1 = Busy 0 = OFF, 1 = ON
2/3 2/3 233x/333x 2/3 2/3 2/3 2/3 2/3 2/3 2/3 3 2/3 233x/333x 2/3 3 2/3
Custom Byte N°
1
2
3
4
5
6
(continues)
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
20/45
Rel addr
103
104
105
# of item
Name
STATE 4 ALARM
1
STATE 5 ALARM
1
STATE 6 ALARM
1
Bit
Description
Notes
PR12x PR33x
BIT 0 (↕)
Harmonic distortion > 2.1
2/3
BIT 1 (↕)
Contact Wear Pre-alarm
2/3
BIT 2 (↕)
Contact Wear Alarm
2/3
BIT 3 (↕)
L Pre-alarm
2/3
BIT 4 (↕)
L Timing
BIT 5 (↕)
S Timing
BIT 6 (↕)
S2 Timing
BIT 7 (↕)
G Timing
BIT 8 (↕)
G Alarm (Blocked Trip)
BIT 9 (↕)
G Ext Timing
BIT 10 (↕)
G Ext Alarm (Blocked Trip)
BIT 11 (↕)
T Pre-alarm
2/3 2/3 S 3 S 2/3 G 2/3 G 2/3 G MM 2/3 G MM 2/3
BIT 12 (↕)
T Alarm
2/3
BIT 13 (↕) BIT 14 (↕)
T Alarm (Blocked Trip) D Timing
2/3 3
BIT 15 (↕)
U Timing
2/3
BIT 0 (↕) BIT 1 (↕) BIT 2 (↕) BIT 3 (↕) BIT 4 (↕) BIT 5 (↕) BIT 6 (↕) BIT 7 (↕) BIT 8 (↕) BIT 9 (↕) BIT 10 (↕) BIT 11 (↕) BIT 12 (↕) BIT 13 (↕) BIT 14 (↕) BIT 15 (↕) BIT 0 (↕) BIT 1 (↕) BIT 2 (↕) BIT 3 (↕) BIT 4 (↕)
U Alarm (Blocked Trip) UV Timing UV Alarm (Blocked Trip) OV Timing OV Alarm (Blocked Trip) RV Timing RV Alarm (Blocked Trip) RP Timing RP Alarm (Blocked Trip) UF Timing UF Alarm (Blocked Trip) OF Timing OF Alarm (Blocked Trip) Frequency Error Iw Warning LC1 Alarm LC2 Alarm L1 Sensor Error L2 Sensor Error L3 Sensor Error Ne Sensor Error
BIT 5 (↕)
Gext Sensor Error
BIT 6 (↕) BIT 7 (↕) BIT 8 (↕) BIT 9 BIT 10 (↕) BIT 11 (↕) BIT 12
SA Error Rating Plug Error Installation Error Internal Error Power Factor Error Phase Cycle Error Invalid Date
BIT 13 (↕)
Configuration Error
BIT 14 (↕)
CB Status Error
BIT 15
Local Bus Analog Value
Custom Byte N°
7
8
9 2/3 MM
10 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 2/3 G MM 2/3 2/3 2/3 2/3 3 3 2/3 (neutral setting, parameters incongruecy,…) 1 = Error 0 = under/equal threshold 1 = over threshold
11
12
2/3 2/3 2/3
(continues)
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
21/45
Rel addr
106
# of item
1
Name
STATE 7 INPUTS / OUTPUTS
Bit
107
108
1
1
STATE 9 LATCHED Note 5
Notes
BIT 0 BIT 1 BIT 2 BIT 3 BIT 4 BIT 5 BIT 6 BIT 7
Local bus Relay 1 contact Local bus Relay 2 contact Local bus Relay 3 contact Local bus Relay 4 contact --Local bus Relay 6 contact Local bus Relay 7 contact Local bus Relay 8 contact
0 = open, 1 = closed 0 = open, 1 = closed 0 = open, 1 = closed 0 = open, 1 = closed --0 = open, 1 = closed 0 = open, 1 = closed 0 = open, 1 = closed
BIT 8
Relay P1 contact
0 = open, 1 = closed
BIT 9 BIT 10 BIT 11 BIT 12
Relay P2 contact Relay P3 contact Relay P4 contact S zone selectivity input
0 = open, 1 = closed 0 = open, 1 = closed 0 = open, 1 = closed 1 = input active
BIT 13
S zone selectivity output
1 = output active
BIT 14
G zone selectivity input
1 = input active
BIT 15
G zone selectivity output
1 = output active
BIT 0 (↑)
L tripped
1 = L trip
BIT 1 (↑)
S tripped
1 = S trip
BIT 2 (↑)
S2 tripped
1 = S2 trip
BIT 4 (↑)
I tripped MCR tripped Iinst tripped
1 = I trip 1 = MCR trip 1 = Iinst trip
BIT 5 (↑)
G tripped
1 = G trip
BIT 6 (↑)
G ext tripped
1 = G ext trip
BIT 7 (↑) BIT 8 (↑) BIT 9 (↑) BIT 10 (↑) BIT 11 (↑) BIT 12 (↑) BIT 13 (↑) BIT 14 (↑) BIT 15 (↑) BIT 0 (↑) BIT 1 (↑) BIT 2 (↑) BIT 3 (↑) BIT 4 BIT 5 BIT 6 BIT 7 BIT 8 BIT 9 BIT 10 BIT 11 BIT 12 BIT 13 BIT 14 BIT 15
T tripped D tripped UN tripped UV tripped OV tripped RV tripped RP tripped UF tripped OF tripped Electronic Trip Test Simulated Trip from Test Unit External Input Trip Hardware Error Trip ----------------------TRIP command Fail
1 = T trip 1 = D trip 1 = UN trip 1 = UV trip 1 = OV trip 1 = RV trip 1 = RP trip 1 = UF trip 1 = OF trip 1 = electronic trip test 1 = simulated trip 1 = trip from external input 1 = trip of Hardware error ----------------------1= TRIP command Failed
BIT 3 (↑)
STATE 8 LATCHED Note 5
Description
PR12x PR33x
Custom Byte N°
2/3 MM ---
13
2/3 MM 2/3 MM 233x/333x 2/3 S MM 2/3 G MM 2/3 2/3 S 3 S 2/3 2/3 2/3 2/3 G 2/3 G MM 2/3 3
14
2/3 MM
16
2/3 2/3 233x/333x 2/3 ----------------------2/3
15
17
18
Table 41 State Notes: GLITCH registers are automatically cleared after reading. LATCHED registers are set when the associated event happens; they are reset only by “CB RESET” or “TRIP RESET” commands
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
22/45
4.5
TIME
Rel addr 100 101 102 103
# of item 1 1 1 1
Description
PR12x PR33x
Number of days from 31/12/1999 MSB = Hour, LSB = minute 0 - 59 0 - 999
2/3
Name Day Hour & minute Second Millisecond
Table 42 Time WARNING: Has shown in REGISTERS MAP(3.2), the TIME update could be done only using 23odbus function 16. In order to modify the Time it is necessary to open the programming session, the data come immediately modified and not at the and of the programming session as it happens for the normal parameters, therefore the abandonment (abort) of the programming session do not cancel the carried out modification It’s recommended to update simultaneously all four TIME registers
4.6
RUN-TIME MEASURES
The measure limits shown in column “Notes” are depicted in MEASURE LIMITS AND REPRESENTATION (6.8). Rel addr
# of item
200
2
Name
Description
Notes
PR12x PR33x
Maximum current (rms)
[A]
Not available 232-1 I < IMIN 0 I > IMAX IMAX
2/3
0 Not available, 1L1, 2L2, 3L3, 4Ne
Not available 0
2/3
Not available 232-1 I < IMIN 0 I > IMAX IMAX
2/3
Not available 232-1 I < IMIN 0 Not available 232-1 I < IMIN 0 I > IMAX IMAX
2/3 G 2/3 G MM
202
1
Maximum current phase
203 205 207 209
2 2 2 2
L1 phase Current (rms) L2 phase Current (rms) L3 phase Current (rms) Ne phase Current (rms)
211
2
Internal Ground current (rms)
213
2
External Ground current (rms)
[A *10-2]
215 216 217 218 219 220 221 222 224 226 228 230 232 234 236 238 240 242 244 246
1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 1
V1 line to neutral voltage (rms) V2 line to neutral voltage (rms) V3 line to neutral voltage (rms) V0 residual voltage (rms) V12 line to line voltage (rms) V23 line to line voltage (rms) V31 line to line voltage (rms) L1 phase active power L2 phase active power L3 phase active power Total active power L1 phase reactive power L2 phase reactive power L3 phase reactive power Total reactive power L1 phase apparent power L2 phase apparent power L3 phase apparent power Total apparent power Total power factor
[V *10-1] [V *10-1] [V *10-1] [V *10-1] [V *10-1] [V *10-1] [V *10-1] [kW *10-1] (signed) [kW *10-1] (signed) [kW *10-1] (signed) [kW *10-1] (signed) [kVAR *10-1] (signed) [kVAR *10-1] (signed) [kVAR *10-1] (signed) [kVAR *10-1] (signed) [kVA *10-1] (signed) [kVA *10-1] (signed) [kVA *10-1] (signed) [kVA *10-1] (signed) [10-2] (signed)
247
1
Frequency
[Hz *10-1]
[A]
Not available 216-1 V < VMIN 0 V > VMAX VMAX
Not available 231-1 | P | < PMIN 0 P > PMAX PMAX P < -PMAX -PMAX
2/3
Not available 215-1 Not available 216-1 F < FMIN FMIN F > FMAX FMAX
(continues)
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
23/45
Rel addr 248 249 250 251 252 254 256 258 260 262 264
# of item 1 1 1 1 2 2 2 2 2 2 2
Name
Description
L1 phase peak factor L2 phase peak factor L3 phase peak factor Ne phase peak factor Positive Active Energy Negative Active Energy Total Active Energy Positive Reactive Energy Negative Reactive Energy Total Reactive Energy Total Apparent Energy
[10-2] [10-2] [10-2] [10-2] [KWh] (signed) [KWh] (signed) [KWh] (signed) [KVARh] (signed) [KVARh] (signed) [KVARh] (signed) [KVAh] (signed)
PR12x PR33x
Notes
Not available 216-1
2/3
E < -231 -231 E > 231-1 231-1
2/3
Table 43 Run-Time measures
4.7
HARMONIC MEASURES
Rel addr 600 601 602 …. 640
# of item 1 1 1 …. 1
Name
PR12x PR33x
Description
Total Harmonic Distortion (THD) 1th Harmonic ratio = 1000 ‰ 2th Harmonic ratio …. 40th Harmonic ratio
[‰] [‰] [‰] [‰] [‰]
3
Table 44 Harmonic measures
4.8
INFORMATION
Rel addr 700 701
# of item 1 1
Name
Range
702
1
703
1
704
1
3/4 pole CB 3/4/2 pole CB In (nominal current)
705
1
CB type
706 714 715
8 1 1
CB Serial Number Data logger max file Data logger max address
Major + minor 0÷1 0÷2 0÷1 0÷2 100 ÷ 6300 See Table 62 TAB_CB_TYPE See Table 63 TAB_CB_TYPE_33x ASCII format characters 0÷3 0 ÷ 65535
716
1
Data logger Trigger
0÷4
717 718 719 720 723
1 1 1 1 6
Day of Data logger trigger Hours & minutes of Dlog trigger Second of Dlog trigger Millisecond of Dlog trigger CB name
Number of days from 31/12/1999 Hours & minutes Seconds Milliseconds ASCII format characters
Slave ID SW version Product Standard reference
Description
0IEC, 1UL1066 0IEC, 1UL1066, 1UL489 0 3 Pole, 1 4 Pole 0 3 Pole, 1 4 Pole, 2 2 Pole [A] See Table 62 TAB_CB_TYPE See Table 63 TAB_CB_TYPE_33x ASCII format characters 0÷3 0 ÷ 65535 0 = None (free running) 1 = Any Alarm 2 = L Timing 3= Any Trip 4 = Custom MSB = Hours, LSB = minutes
PR12x PR33x 2/3 2/3 233x/333x 233x/333x 233x/333x 233x/333x 2/3 233x/333x 233x/333x 2/3 2/3 2/3
2/3
2/3 2/3 2/3 2/3 2/3
Table 45 Information
4.9
LOCAL BUS DATA AREA
Rel addr
# of item
Name
Range
Description Bit = 0 Bit = 1 0 Bus Warning OFF Bus Warning ON 1 Bus Alarm OFF Bus Alarm ON 2(1) Digital Input OFF Digital Input ON 0 ÷ 65535 Used by Accessory unit
PR12x PR33x
Bit
800
1
Accessory Bus status
0x0000 ÷ 0x0003
801 802
1 25
Analog Value Local Bus Data Area
0 ÷ 65535 0 ÷ 65535
2/3 2/3 2/3
Table 46 Local bus data area Note: digital input value (Addr.800, bit 2) is reported in STATE relay. Local bus data area is an exchange buffer between system bus and devices connected to the accessory bus (e.g. PR035/MM). Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
24/45
4.10
CONFIGURATION1
Rel addr
# of item
1000
1
Product execution
0÷3
1001
8
Relay Serial Number
ASCII format characters
Name
Range
Description 0LI, 1LSI, 2LSIG, 3LSIRc ---
PR12x PR33x 2/3 2/3
Table 47 Configuration 1
4.11 Rel addr
PARAMETERS CONFIGURATION2 # of item
Name
Range
0x0000 ÷ 0x003F
1020
1
Unit configuration
1021
1
Language
0÷4
1022
1
Neutral selection
0÷3
1023
1
Ext. ground toroid
0÷3
1024
1
Nominal voltage Un
See Table 58 TAB_UN
1025
1
VT secondary voltage
0÷5
1026
1
Net Frequency
0÷1
1027
1
Plant Configuration
0÷1
1028
1
1029
1
1030
1
1031
1
Protocol Type (external bus only)
0÷3
1032
1
Ext Toroid Type
0÷2
Slave Address (external bus only) Addressing Type (external bus only) Baud rate (external bus only)
1 ÷ 247 0÷1 0÷1
Description Bit Bit = 0 0 Not Used 1 Local Bus Unit = absent 2 VT = absent 3 Neutral Protection = OFF 4 Power Direction = Bottom Top 5 Neutral Voltage = absent 6 Operating mode = Local 0 = ENG 1 = ITA 2 = FRA 3 = GER 4 = SPA 0 = 50 % 1 = 100 % 2 = 150 % 3 = 200 % 0 = 100 A 1 = 250 A 2 = 400 A 3 = 800 A
Bit = 1 Not Used Local Bus Unit = present VT = present Neutral Protection = ON Power Direction = Top Bottom Neutral Voltage = present Operating mode = Remote
PR12x PR33x 2/3 2/3 2/3 2/3 2/3 2/3 2/3
2/3
2/3
2/3 G MM
See Table 58 TAB_UN
2/3
0 = 100 V 1 = 110 V 2 = 115 V 3 = 120 V 4 = 200 V 5 = 230 V 0 = 50 Hz 1 = 60 Hz 0 = 3P 1 = 3P+N
2/3
2/3 2/3
1 ÷ 247
2/3
0 = standard 1 = ABB 0 = 9600 1 = 19200 0 = “E,8,1” 1 = “O,8,1” 2 = “N,8,2” 3 = “N,8,1” 0 = None 1 = Source Ground Return 2 = Rc
2/3 2/3
2/3
2/3 G
Table 48 Configuration 2
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
25/45
4.12
PARAMETERS CONFIGURATION3
Rel addr
# of item
Name
Range Bit
Bit = 0
Bit = 1
0
Par set = set A
Par set = set B
3
1
Dual Setting = OFF Harm Dist Warn = OFF Phase Rotation Warn = OFF Phase Rotation Cycle = 123
Dual Setting = ON Harm Dist Warn = ON Phase Rotation Warn = ON Phase Rotation Cycle = 321
3
CosFi Module Warning = OFF
CosFi Module Warning = ON
3
Set B on CB close
3
Set B on Vaux OFF
3
Set B on Local Bus Digital Input ON
3
2 3 1050
1
Configuration
4
0x0000 ÷ 0x007F
5
Dual set CB close disable Dual set Vaux 7 disable Dual Set Local Bus 8 disable 5 ÷ 120 min 6
1051
1
1052
1
1053 1054 1055 1056 1057 1058 1059 1060 1061 1062 1063 1064 1065 1066
1 1 1 1 1 1 1 1 1 1 1 1 1 1
1067
1
1068 1069 1070 1071 1072 1073 1074 1075
1 1 1 1 1 1 1 1
1076
1
PR12x PR33x
Description
Measurement store time Loc Bus Relays Unit Contact configuration Loc Bus Relay 1 Function Loc Bus Relay 1 Delay Loc Bus Relay 2 Function Loc Bus Relay 2 Delay Loc Bus Relay 3 Function Loc Bus Relay 3 Delay Loc Bus Relay 4 Function Loc Bus Relay 4 Delay Loc Bus Relay 6 Function Loc Bus Relay 6 Delay Loc Bus Relay 7 Function Loc Bus Relay 7 Delay Loc Bus Relay 8 Function Loc Bus Relay 8 Delay P Relays Contact configuration P1 Function P1 Delay P2 Function P2 Delay P3 Function P3 Delay P4 Function P4 Delay
5 ÷ 120 step 5 [min] See Table 60 TAB_RELAYS_K51_CONFIG 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] See Table 61 TAB_P_RELE_CONFIG 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s] 0 ÷ 65535 0.00 ÷ 100.00 step 0.01 [s]
Programmable Input configuration
0x0000 ÷ 0x0001
1
Programmable Input Function
0÷5
1078
1
Programmable Input Delay
0.00 ÷ 100.00 step 0.01 [s]
3 3
2/3
See Table 60 TAB_RELAYS_K51_CONFIG See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 61 TAB_P_RELE_CONFIG See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] See Table 59 TAB_RELAYS_FUNCTION 0 ÷ 10000 [s*10-2] 0 = Active low 1 = Active high
1077
2/3
0 = Generic 1 = External TRIP 2 = Trip reset 3 = Set B (PR123/P only) 4 = Dial Local 5 = Reset Signaling Module 6 = Energy reset 0 ÷ 10000 [s*10-2]
2/3
2/3 MM
233x/333x
(continues)
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
26/45
Rel addr
# of item
1079
1
1080
1
Name
Range
Description
PR12x PR33x
0 = Data Logger = OFF 1 = Data Logger = ON
Data Logger Configuration
0x0000 ÷ 0x0001
Data Logger Trigger Type
Standard: 0 ÷ 3 Custom 256 ÷ 65535 (see RELAYS AND DATA LOGGER “CUSTOM” SETTING)
1081
1
Data Logger Stop Delay
0.00 ÷ 10.00 step 0.01 [s]
1082
1
Data Logger Frequency
0÷3
1083 1084 1089 1094 1095 1096 1097
1 5 5 1 1 1 1
0.50 ÷ 0.95 step 0.01 ASCII format characters ASCII format characters 0.20 ÷ 50.00 step 0.10 [s] Number of days from 31/12/1999 Number of days from 31/12/1999 0 ÷ 65535
1098
1
CosFi Module Threshold CB TAG name User data Dual set CB close time Date of installation CB Date of last maintenance CB Local Bus Analog Value Threshold Startup current activation threshold
0.10 ÷ 10.00 step 0.10 [In]
Standard: 0 = None (free running) 1 = Any Alarm 2 = L Timing 3 = Any Trip 0 ÷ 1000 [s*10-2] 0 = 600 Hz 1 = 1200 Hz 2 = 2400 Hz 3 = 4800 Hz 50 ÷ 95 [10-2]
2/3
0 ÷ 65535
3 2/3 2/3 3 2/3 2/3 2/3
10 ÷ 1000 [In*10-2]
2/3
20 ÷ 5000 [s*10-2]
Table 49 Configuration 3
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
27/45
4.13
PARAMETERS PROTECTION SET1 / SET2 (only for PR123/P - PR333/P)
The following table shows parameters included in protection SET1 and SET2 areas. Column “Rel addr” reports SET1 addresses (1100 ÷ 1178); SET2 addresses (1200 ÷ 1278) can be obtained adding 100 to SET1 addresses. Rel addr
# of item
Name
Range Bit 0 1 2 3 4
1100
1
Prot L configuration
1101
1
Prot L curve type
0÷3
1102 1103 1104 1105
1 1 1 1
Prot L threshold Prot L time Prot L threshold IEC255 Prot L time IEC255
0.40 ÷ 1.00 step 0.01 [In] 3 ÷ 144 step 3 [s] 0.40 ÷ 1.00 step 0.01 [In] 3 ÷ 144 step 3 [s] Bit
1106
1
Prot S configuration
1107 1108 1109 1110 1111 1112 1113 1114
1 1 1 1 1 1 1 1
Prot S curve type Prot S threshold T=k/I2 Prot S time T=k/I2 Prot S threshold T=k Prot S time T=k Prot S start up threshold Prot S start up time Prot S zone selectivity time
1115
1
Prot S2 configuration
1116 1117 1118 1119 1120
1 1 1 1 1
Prot S2 threshold T=k Prot S2 time T=k Prot S2 start up threshold Prot S2 start up time Prot S2 zone selectivity time
1121
1
Prot D configuration
1122 1123 1124 1125 1126 1127
1 1 1 1 1 1
Prot D threshold Prot D time Forward Prot D time Backward Prot D start up threshold Prot D start up time Prot D zone selectivity time
1128
1
Prot I configuration
1129 1130 1131
1 1 1
Prot I threshold Prot I start up threshold Prot I start up time
0 T=k, 1 I2t = k 0.6 ÷ 10.0 step 0.1 [In] 0.05 ÷ 0.8 step 0.01[s] 0.6 ÷ 10.0 step 0.1 [In] 0.05 ÷ 0.8 step 0.01[s] 0.6 ÷ 10.0 step 0,1 [In] 0.10 ÷ 30.00 step 0.01 [s] 0.04 ÷ 0.20 step 0.01 [s]
0.6 ÷ 10.0 step 0.1 [In] 0.05 ÷ 0.8 step 0.01[s] 0.6 ÷ 10.0 step 0,1 [In] 0.10 ÷ 30.00 step 0.01 [s] 0.04 ÷ 0.20 step 0.01 [s]
1,5 ÷ 15 step 0.1 [In] 1,5 ÷ 15 step 0.1 [In] 0.10 ÷ 30.00 step 0.01[s]
Bit = 0 Bit = 1 ----------------Thermal memory = OFF Thermal memory = ON 0: I2t = k 2: 13,5*b/(i-1) 1: 0,14/(i0.02-1) 3: 80*b/(i2-1) 40 ÷ 100 [In*10-2] 300 ÷ 14400 [s*10-2] 40 ÷ 100 [In*10-2] 300 ÷ 14400 [s*10-2]
Bit = 0 Prot disable --Start Up Th= OFF Zone selectivity= OFF Thermal memory= OFF 0÷1 60 ÷ 1000 [In*10-2] 5 ÷ 80 [s*10-2] 60 ÷ 1000 [In*10-2] 5 ÷ 80 [s*10-2] 60 ÷ 1000 [In*10-2] 10 ÷ 3000 [s*10-2] 4 ÷ 20 [s*10-2] Bit Bit = 0 0 Prot disable 1 --2 Start Up Th= OFF 3 Zone selectivity= OFF 4 --60 ÷ 1000 [In*10-2] 5 ÷ 80 [s*10-2] 60 ÷ 1000 [In*10-2] 10 ÷ 3000 [s*10-2] 4 ÷ 20 [s*10-2] Bit Bit = 0 0 Prot disable 1 --2 Start Up Th= OFF 3 Zone selectivity= OFF 4 --60 ÷ 1000 [In*10-2] 20 ÷ 80 [s*10-2] 20 ÷ 80 [s*10-2] 60 ÷ 1000 [In*10-2] 10 ÷ 3000 [s*10-2] 13 ÷ 50 [s*10-2] Bit Bit = 0 0 Prot disable 1 --2 Start Up Th= OFF 3 --4 --150 ÷ 1500 [In*10-2] 150 ÷ 1500 [In*10-2] 10 ÷ 3000 [s*10-2] 0 1 2 3 4
0.6 ÷ 10.0 step 0.1 [In] 0.2 ÷ 0.8 step 0.01 [s] 0.2 ÷ 0.8 step 0.01 [s] 0.6 ÷ 10.0 step 0.1 [In] 0.10 ÷ 30.00 step 0.01[s] 0.13 ÷ 0.50 step 0.01 [s]
PR12x PR33x
Description
Bit = 1 Prot enable --Start Up Th= ON Zone selectivity= ON Thermal memory= ON
--------2/3 2/3 2/3 2/3
2/3 S --2/3 S 2/3 S 2/3 S 2/3 S
2/3 S Bit = 1 Prot enable --Start Up Th= ON Zone selectivity= ON ---
3 S
Bit = 1 Prot enable --Start Up Th= ON Zone selectivity= ON --3
Bit = 1 Prot enable --Start Up Th= ON -----
2/3 --2/3 ----2/3 2/3 MM
(continues)
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
28/45
Rel addr
# of item
1130
1
Prot MM configuration
1131
1
Prot MM threshold
Name
Range Bit
1132
1
Prot G configuration
1133
1
Prot G curve type
1134
1
Prot G threshold T=k/I2
1135
1
Prot G time T=k/I2
1136
1
Prot G threshold T=k
1137 1138 1139 1140
1 1 1 1
Prot G time T=k Prot G start up threshold Prot G start up time Prot G zone selectivity time
1141
1
1142 1143 1144 1145 1146 1147 1148
1 1 1 1 1 1 1
1149
1
1150
1151 1152
1
1 1
Prot U threshold Prot U time
1
Prot UV configuration
1154 1155
1 1
Prot UV threshold Prot UV time
1156
1
Prot OV configuration
1159 1160 1161
1 1 1 1 1
1,5 ÷ 4 step 0.1 [In]
0 T=k, 1 I2t = k
Prot OV threshold Prot OV time
Bit = 1 Prot enable Trip enable Start Up Th= ON Zone selectivity= ON ---
MM
2/3 G 2/3 G --2/3 G
10 ÷ 100 [In*10-2]
233x/333x G
0.20 ÷ 1.00 step 0.02 [In]
20 ÷ 100 [In*10-2]
233x/333 G
0.10 ÷ 1.00 step 0.05 [s]
10 ÷ 100 [s*10-2]
2/3 G
0.10 ÷ 1.00 step 0.02 [In]
10 ÷ 100 [In*10-2]
233x/333x G
0.20 ÷ 1.00 step 0.02 [In]
20 ÷ 100 [In*10-2]
233x/333 G
10 ÷ 100 [s*10-2] 20 ÷ 100 [In*10-2] 10 ÷ 3000 [s*10-2] 4 ÷ 20 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 Start Up Th = OFF
Bit = 1 Prot enable Trip enable Start Up Th = ON
3
Zone selectivity= OFF
Zone selectivity = ON
4
0.10 ÷ 30.00 step 0.01 [s]
--0÷1 20 ÷ 100 [InGext *10-2] 10 ÷ 100 [s*10-2] 20 ÷ 100 [InGext *10-2] 10 ÷ 100 [s*10-2] 20 ÷ 100 [InGext *10-2] 10 ÷ 3000 [s*10-2]
0.04 ÷ 0.20 step 0.01 [s]
4 ÷ 20 [s*10-2]
0.10 ÷ 1.00 step 0.05 [s] 0.20 ÷ 1.00 step 0.02 [In] 0.10 ÷ 30.00 step 0.01[s] 0.04 ÷ 0.20 step 0.01 [s]
0 T=k, 1 I2t = k 0.10 ÷ 1.00 step 0.02 [InGext]
0.10 ÷ 1.00 step 0.05 [s] 0.10 ÷ 1.00 step 0.02 [InGext]
0.10 ÷ 1.00 step 0.05 [s] 0.10 ÷ 1.00 step 0.02 [InGext]
Bit 0 1 2 3 4 5 2 ÷ 90 step 1 [%] 0.5 ÷ 60 step 0.5 [s]
0.50 ÷ 0.95 step 0.01 [Un] 0.1 ÷ 5.0 step 0.1 [s]
1.05 ÷ 1.20 step 0.01 [Un] 0.1 ÷ 5.0 step 0.1 [s]
Prot RV configuration Prot RV threshold Prot RV time
Bit = 1 Prot enable --
0.10 ÷ 1.00 step 0.02 [In]
Prot U configuration
1153
1157 1158
Bit = 0 Prot disable -150 ÷ 400 [In*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 Start Up Th= OFF 3 Zone selectivity= OFF 4 --0÷1 0 1
Prot Ext G configuration
Prot Ext G curve type Prot Ext G threshold T=k/I2 Prot Ext G time T=k/I2 Prot Ext G threshold T=k Prot Ext G time T=k Prot Ext G start up threshold Prot Ext G start up time Prot Ext G zone selectivity time
PR12x PR33x
Description
0.10 ÷ 0.40 step 0.05 [Un] 0.5 ÷ 30.0 step 0.5 [s]
Bit = 0 Prot disable Trip disable ------Current selection 2 ÷ 90 [%] 50 ÷ 6000 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 --50 ÷ 95 [Un*10-2] 10 ÷ 500 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 --105 ÷ 120 [Un*10-2] 10 ÷ 500 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 --10 ÷ 40 [Un*10-2] 50 ÷ 3000 [s*10-2]
2/3 G 2/3 G
--2/3 G MM
Bit = 1 Prot enable Trip enable ------Voltage selection
2/3
Bit = 1 Prot enable Trip enable ---
Bit = 1 Prot enable Trip enable ---
Bit = 1 Prot enable Trip enable ---
2/3 MM
2/3 MM
2/3 MM
(continues) Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
29/45
Rel addr
1162
1163 1164
1165
1166 1167
1168
1169 1170
1171
# of item
1
1 1
1
1 1
1
1 1
1
Name
Range Bit 0 1 2 3 4
Prot RP configuration
Prot RP threshold Prot RP time
-0.10 ÷ -0.30 step 0.02 [Pnt] 0.5 ÷ 25.0 step 0.1 [s]
Prot UF configuration
Prot UF threshold Prot UF time
0,90 ÷ 0.99 step 0.01 [Fn] 0.5 ÷ 3.0 step 0.1 [s]
Prot OF configuration
Prot OF threshold Prot OF time
1,01 ÷ 1.10 step 0.01 [Fn] 0.5 ÷ 3.0 step 0.1 [s]
Prot T configuration
1172
1
Load control configuration
0x0000 ÷ 0x0007
1173 1174 1175
1 1 1
Warning current Iw LC1 threshold LC2 threshold
0.30 ÷ 10.00 step 0.05 [In] 50 ÷ 100 step 1 [%I1] 50 ÷ 100 step 1 [%I1]
1176
1
Prot Rc configuration
Not Used
1177 1178
1 1
Prot Rc threshold Prot Rc time
See Table 51 TAB_TH_Rc See Table 52 TAB_Time_Rc
1179
1
MCR Config
1180 1181
1 1
MCR Threshold MCR Time
6 ÷ 15 step 0.1[In] 0.04 ÷ 0.5 step 0.01 [s]
PR12x PR33x
Description Bit = 0 Prot disable Trip disable ------10 ÷ 30 [-Pnt *10-2] 50 ÷ 2500 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 --3 --4 --90 ÷ 99 [Fn *10-2] 50 ÷ 300 [s*10-2] Bit Bit = 0 0 Prot disable 1 Trip disable 2 --3 --4 --101 ÷ 110 [Fn*10-2] 50 ÷ 300 [s*10-2] Bit Bit = 0 0 ---
Bit = 1 Prot enable Trip enable -------
2/3 MM
Bit = 1 Prot enable Trip enable -------
2/3 MM
Bit = 1 Prot enable Trip enable -------
2/3 MM
Bit = 1 ---
1
Trip disable
Trip enable
2 3 4 Bit 0 1 2
-------
-------
Bit = 0 Bit = 1 Iw Th disabled Iw Th enabled LC1 Th disabled LC1 Th enabled LC2 Th disabled LC2 Th enabled 30 ÷ 1000 [In*10-2] 50 ÷ 100 [%I1] 50 ÷ 100 [%I1] Bit Bit = 0 Bit = 1 0 ----1 ----2 ----3 ----4 ----See Table 51 TAB_TH_Rc See Table 52 TAB_Time_Rc Bit Bit = 0 Bit = 1 0 MCR disable MCR enable 600 ÷ 1500 [In*10-2] 4 ÷ 50 [s*10-2]
2/3
2/3
2/3 Rc MM
2/3
Table 50 Set 1/ Set 2
Value 0 1 2 3 4 5
Threshold 3A 5A 7A 10 A 20 A 30 A
Value 0 1 2 3 4 5 6
Table 51 TAB_TH_Rc
Time 0.06 [s] 0.10 [s] 0.20 [s] 0.30 [s] 0.40 [s] 0.50 [s] 0.80 [s]
Table 52 TAB_Time_Rc
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
30/45
4.14
TRIP HISTORY
Rel addr
# of item
2000
2019 … … … … … … … 2361
Name
19
Trip history N° 1 (new)
19 19 19 19 19 19 19 … 19
PR12x PR33x
Description 0 1 2 3 4 5 6 7÷8 9÷10 11÷12 13÷14 15 16 17 18
MARKER (0 = valid) See Table 54 TAB_TRIP_TYPE Trip Number Date (Number of days from 31/12/1999) Date (MSB = ore, LSB = min) Date (seconds) Date (ms) Current phase L1 Current phase L2 Current phase L3 Current phase Ne Contact wear See Table 54 TAB_TRIP_TYPE See Table 54 TAB_TRIP_TYPE See Table 54 TAB_TRIP_TYPE “ “ “ “ “ “ “ “ “
Trip history N° 2 Trip history N° 3 Trip history N° 4 Trip history N° 5 Trip history N° 6 Trip history N° 7 Trip history N° 8 …. Trip history N° 20 (old)
2/3
Table 53 Trip History Trip type L S S2 D D FW D BW I / MM MCR G
word 1 1 2 3 4 5 6
8
word 16 In Active threshold = value / 512 In Active threshold = value / 512 In Active threshold = value / 512 In Active threshold = value / 512 In Active threshold = value / 512 In Active threshold = value / 512 0x0000 0xABCD Internal Ground Current (rms) Low
word 17 see address 1100 mS selected time mS selected time see address 1121 see address 1121 see address 1121 In Active threshold = value / 512 In Active threshold = value / 512 Internal Ground Current (rms) High
G_EXT
9
External Ground Current (rms) Low
External Ground Current (rms) High
T UV OV RV RP UF OF UN Current UN Voltage EXT Rc Rc TEST Hw Trip Iinst
10 11 12 13 14 15 16
°C temperature = value * 0.073855 V12 line to line voltage (rms) V12 line to line voltage (rms) V0 residual voltage (rms) Total Active Power Low Frequency Frequency 0xABCD V12 line to line voltage (rms) see address 1078 Rc Current (rms) Low Rc Current (rms) Low see address 105 see address 704
see address 705 V23 line to line voltage (rms) V23 line to line voltage (rms) --Total Active Power High Hz Active threshold = value / 100 Hz Active threshold = value / 100 % Active threshold = value / 10 V23 line to line voltage (rms) see address 1076 Rc Current (rms) High Rc Current (rms) High --see address 705
7
17 18 19 20 21 22
word 18 see address 1101 see address 1106 see address 1115 see address 1020 see address 1020 see address 1020 see address 1128 mS selected time In Active threshold = value / 512 InExt Active threshold = value / 1085 (100A) InExt Active threshold = value / 2720 (250A) InExt Active threshold = value / 1270 (400A) InExt Active threshold = value / 2540 (800A) see address 704 V31 line to line voltage (rms) V31 line to line voltage (rms) ----mS selected time mS selected time mS selected time V31 line to line voltage (rms) see address 1077 Amp. Active threshold = value / 166.7 Amp. Active threshold = value / 166.7 --see address 105
Table 54 TAB_TRIP_TYPE
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
31/45
4.15 Rel addr
MEASURE HISTORY # of item
Name 0 1
2500
2524 2548 … 3052 3076
24
24 24 24 24 24
PR12x PR33x
Description
Measure history n° 1 (new)
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Measure history n° 2 Measure history n° 3 … Measure history n° 24 Measure history n° 25 (old)
MARKER (0 = valid) History code: 0 = NORMAL_HISTORY 1 = POWER_UP 2 = NEW_PERIOD Period from last save (minutes) Number of days from 31/12/1999 MSB = Hour, LSB = minute Total mean active power (LSW) Total mean active power (MSW) Total maximum active power (LSW) Total maximum active power (MSW) Maximum current phase (0=L1, 1=L2, 2=L3, 3=Ne) Maximum current (LSW) Maximum current (MSW) Maximum line to line voltage phase (0=V12, 1=V23, 2=V31) Maximum line to line voltage Minimum line to line voltage phase (0=V12, 1=V23, 2=V31) Minimum line to line voltage Total mean reactive power (LSW) Total mean reactive power (MSW) Total maximum reactive power (LSW) Total maximum reactive power (MSW) Total mean apparent power (LSW) Total mean apparent power (MSW) Total maximum apparent power (LSW) Total maximum apparent power (MSW) “ “ “ “ “
2/3
Table 55 Measure History
4.16 Rel addr
LOG EVENTS # of item
Name
Description
3300
6
Log event n° 1 (new)
3306 3312 … 3768 3774
6 6 6 6 6
Log event n° 2 Log event n° 3 … Log event n° 79 Log event n° 80 (old)
PR12x PR33x
MARKER (0 = valid) See Table 64 TAB_LOG_EVENTS Number of days from 31/12/1999 MSB = Hour, LSB = minute Seconds Milliseconds “ “ “ “ “
2/3
Table 56 Log events
4.17 Rel addr 4000 4128 4256 4384
WAVEFORMS # of item 128 128 128 128
Name Buffer waveform channel: L1 or U12 Buffer waveform channel: L2 or U23 Buffer waveform channel: L3 or U31 Buffer waveform channel: NE
Description
PR12x PR33x
[A], [V *10-1] [A], [V *10-1] [A], [V *10-1] [A]
3
Table 57 Waveforms
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
32/45
5.
TABLES Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
VT nominal 100 115 120 190 208 220 230 240 277 347 380 400 415 440 480 500 550 600 660 690 910 950 1000 1150
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13
256 ÷ 65535
Bit = 1 Relay K51/1 latched Relay K51/2 latched Relay K51/3 latched Relay K51/4 latched Relay K51/6 latched Relay K51/7 latched Relay K51/8 latched Contact K51/1 NC Contact K51/2 NC Contact K51/3 NC Contact K51/4 NC Contact K51/6 NC Contact K51/7 NC Contact K51/8 NC
Table 60 TAB_RELAYS_K51_CONFIG
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
Table 58 TAB_UN Value 0 1 2 3 4 5 6 7 8 9 10 11
Bit = 0 Relay K51/1 not latched Relay K51/2 not latched Relay K51/3 not latched Relay K51/4 not latched Relay K51/6 not latched Relay K51/7 not latched Relay K51/8 not latched Contact K51/1 NO Contact K51/2 NO Contact K51/3 NO Contact K51/4 NO Contact K51/6 NO Contact K51/7 NO Contact K51/8 NO
Bit = 0 Relay P1 not latched Relay P2 not latched Relay P3 not latched Relay P4 not latched Contact P1 NO Contact P2 NO Contact P3 NO Contact P4 NO
Bit = 1 Relay P1 Latched Relay P2 Latched Relay P3 Latched Relay P4 Latched Contact P1 NC Contact P2 NC Contact P3 NC Contact P4 NC
Table 61 TAB_P_RELE_CONFIG
Description None L pre-alarm L timing S timing L trip S trip I trip G trip Any trip Any Alarm LC1 LC2 Custom (see RELAYS AND DATA LOGGER “CUSTOM” SETTING)
Table 59 TAB_RELAYS_FUNCTION
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
33/45
Value 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126
CB type E1B800/3P E1B1000/3P E1B1250/3P E1B1600/3P E1N800/3P E1N1000/3P E1N1250/3P E1N1600/3P E2B1600/3P E2B2000/3P E2N1000/3P E2N1250/3P E2N1600/3P E2N2000/3P E2S800/3P E2S1000/3P E2S1250/3P E2S1600/3P E2S2000/3P E2L1250/3P E2L1600/3P E3N2500/3P E3N3200/3P E3S1000/3P E3S1250/3P E3S1600/3P E3S2000/3P E3S2500/3P E3S3200/3P E3H800/3P E3H1000/3P E3H1250/3P E3H1600/3P E3H2000/3P E3H2500/3P E3H3200/3P E3V800/3P E3V1250/3P E3V1600/3P E3V2000/3P E3V2500/3P E3V3200/3P E3L2000/3P E3L2500/3P E4S4000/3P --E4H3200/3P --E4H4000/3P --E4V3200/3P E4V4000/3P E6H4000/3P E6H5000/3P --E6H6300/3P --E6V-A6000/3P E6V4000/3P E6V5000/3P E6V6300/3P E1B-A800/3P E1B-A1200/3P E2B-A1600/3P
Value 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99 101 103 105 107 109 111 113 115 117 119 121 123 125 127
CB type E1B800/4P E1B1000/4P E1B1250/4P E1B1600/4P E1N800/4P E1N1000/4P E1N1250/4P E1N1600/4P E2B1600/4P E2B2000/4P E2N1000/4P E2N1250/4P E2N1600/4P E2N2000/4P E2S800/4P E2S1000/4P E2S1250/4P E2S1600/4P E2S2000/4P E2L1250/4P E2L1600/4P E3N2500/4P E3N3200/4P E3S1000/4P E3S1250/4P E3S1600/4P E3S2000/4P E3S2500/4P E3S3200/4P E3H800/4P E3H1000/4P E3H1250/4P E3H1600/4P E3H2000/4P E3H2500/4P E3H3200/4P E3V800/4P E3V1250/4P E3V1600/4P E3V2000/4P E3V2500/4P E3V3200/4P E3L2000/4P E3L2500/4P E4S4000/4P E4S/f4000/4P E4H3200/4P E4H/f3200/4P E4H4000/4P E4H/f4000/4P E4V3200/4P E4V4000/4P E6H4000/4P E6H5000/4P E6H/f5000/4P E6H6300/4P E6H/f6300/4P E6V-A6000/4P E6V4000/4P E6V5000/4P E6V6300/4P E1B-A800/4P E1B-A1200/4P E2B-A1600/4P
Standard IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC UL IEC IEC IEC UL UL UL
Value 128 130 132 134 136 138 140 142 144 146 148 150 152 154 156 158 160 162 164 166 168 170 172 174 176 178 180 182 184 186 188 190 192 194 196 198 200 202 204 206 208 210 212 214 216 218 220 222 224 226 228 230 232 234 236 238 240 242 244 246 248 250 252 254
CB type E2N-A1200/3P E2N-A1600/3P E2S-A1200/3P E2S-A1600/3P E3N-A2000/3P E3N-A2500/3P E3S-A1200/3P E3S-A1600/3P E3S-A2000/3P E3S-A2500/3P E3H-A1200/3P E3H-A1600/3P E3H-A2000/3P E3H-A2500/3P E3V-A1200/3P E3V-A1600/3P E3V-A2000/3P E3V-A2500/3P E4S-A3200/3P E4S-A3600/3P E4H-A3200/3P E4H-A3600/3P E4V-A3200/3P E4V-A3600/3P E6H-A4000/3P E6H-A5000/3P E6V-A4000/3P E6V-A5000/3P --E1N-A800/3P E1N-A1200/3P E2N-A800/3P E2S-A800/3P E2H-A800/3P E2H-A1200/3P E2H-A1600/3P E3S-A800/3P E3S-A3200/3P E3H-A800/3P E3H-A3200/3P E3V-A800/3P E3V-A3200/3P ----E4L-A3200/3P E4L-A3600/3P ----E6L-A4000/3P E6L-A5000/3P E3X-A800/3P E3X-A1200/3P E3X-A1600/3P E3X-A2000/3P E6X-A4000/3P E6X-A5000/3P ----E1B-A250/3P E1N-A250/3P E2S-A250/3P E2H-A250/3P E1N250/3P E2S250/3P
Value 129 131 133 135 137 139 141 143 145 147 149 151 153 155 157 159 161 163 165 167 169 171 173 175 177 179 181 183 185 187 189 191 193 195 197 199 201 203 205 207 209 211 213 215 217 219 221 223 225 227 229 231 233 235 237 239 241 243 245 247 249 251 253 255
CB type E2N-A1200/4P E2N-A1600/4P E2S-A1200/4P E2S-A1600/4P E3N-A2000/4P E3N-A2500/4P E3S-A1200/4P E3S-A1600/4P E3S-A2000/4P E3S-A2500/4P E3H-A1200/4P E3H-A1600/4P E3H-A2000/4P E3H-A2500/4P E3V-A1200/4P E3V-A1600/4P E3V-A2000/4P E3V-A2500/4P E4S-A3200/4P E4S-A3600/4P E4H-A3200/4P E4H-A3600/4P E4V-A3200/4P E4V-A3600/4P E6H-A4000/4P E6H-A5000/4P E6V-A4000/4P E6V-A5000/4P E6H/f4000/4P E1N-A800/4P E1N-A1200/4P E2N-A800/4P E2S-A800/4P E2H-A800/4P E2H-A1200/4P E2H-A1600/4P E3S-A800/4P E3S-A3200/4P E3H-A800/4P E3H-A3200/4P E3V-A800/4P E3V-A3200/4P E4H-A/f3200/4P E4H-A/f3600/4P E4L-A3200/4P E4L-A3600/4P E6H-A/f4000/4P E6H-A/f5000/4P E6L-A4000/4P E6L-A5000/4P E3X-A800/4P E3X-A1200/4P E3X-A1600/4P E3X-A2000/4P E6X-A4000/4P E6X-A5000/4P E6X-A/f4000/4P E6X-A/f5000/4P E1B-A250/4P E1N-A250/4P E2S-A250/4P E2H-A250/4P E1N250/4P E2S250/4P
Standard UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL IEC UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL IEC IEC
Modbus system Interface for relays PR122-3 and PR332-3
Scale
Table 62 TAB_CB_TYPE Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
1SDH000556R0001
Page NO.
34/45
Value 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122
CB type T7S800 /3P T7S1000/3P T7S1250/3P T7S1600/3P T7H800 /3P T7H1000/3P T7H1250/3P T7H1600/3P T7L800 /3P T7L1000/3P T7L1250/3P T7L1600/3P T7V800 /3P T7V1000/3P T7V1250/3P T7S1200/3P T7H1200/3P T7L1200/3P X1B630/3P X1B800/3P X1B1000/3P X1B1250/3P X1B1600/3P X1N630/3P X1N800/3P X1N1000/3P X1N1250/3P X1N1600/3P X1L630/3P X1L800/3P X1L1000/3P X1L1250/3P X1B800/3P X1B1200/3P X1N800/3P X1N1200/3P X1L800/3P X1L1200/3P X1B800/3P X1B1200/3P X1B1600/3P X1N800/3P X1N1200/3P X1N1600/3P X1L800/3P X1L1200/3P X1V800/3P X1V1200/3P T8L2000/3P T8L2500/3P T8L3200/3P T8V2000/3P T8V2500/3P T8V3200/3P T8V1600/3P T8V2000/3P T8V2500/3P T8V3000/3P T7S1000/3P T7H1000/3P T7L1000/3P T7X800/3P
Value 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99 101 103 105 107 109 111 113 115 117 119 121 123
CB type T7S800 /4P T7S1000/4P T7S1250/4P T7S1600/4P T7H800 /4P T7H1000/4P T7H1250/4P T7H1600/4P T7L800 /4P T7L1000/4P T7L1250/4P T7L1600/4P T7V800 /4P T7V1000/4P T7V1250/4P T7S1200/4P T7H1200/4P T7L1200/4P X1B630/4P X1B800/4P X1B1000/4P X1B1250/4P X1B1600/4P X1N630/4P X1N800/4P X1N1000/4P X1N1250/4P X1N1600/4P X1L630/4P X1L800/4P X1L1000/4P X1L1250/4P X1B800/4P X1B1200/4P X1N800/4P X1N1200/4P X1L800/4P X1L1200/4P X1B800/4P X1B1200/4P X1B1600/4P X1N800/4P X1N1200/4P X1N1600/4P X1L800/4P X1L1200/4P X1V800/4P X1V1200/4P T8L2000/3P T8L2500/3P T8L3200/3P T8V2000/3P T8V2500/3P T8V3200/3P T8V1600/3P T8V2000/3P T8V2500/3P T8V3000/3P T7S1000/3P T7H1000/3P T7L1000/3P T7X800/3P
Standard IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC UL489 UL489 UL489 IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC UL1066 UL1066 UL1066 UL1066 UL1066 UL1066 UL489 UL489 UL489 UL489 UL489 UL489 UL489 UL489 UL489 UL489 IEC IEC IEC IEC IEC IEC UL489 UL489 UL489 UL489 UL489 UL489 UL489 IEC
Table 63 TAB_CB_TYPE_33x
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
35/45
Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Event type Parameters changed Signaling reset CB isolated CB connected CB open CB closed CB status defined CB status undefined Internal bus OK Internal bus fault Trip command fail Local mode operating mode Remote mode operating mode Test session closed Test session opene Test unit not connected Test unit connected Set B OFF Set B ON Harmonic distortion OFF Harmonic distortion ON Cw Pre-alarm OFF Cw Pre-alarm ON Cw Alarm OFF Cw Alarm ON L Pre-alarm OFF L Pre-alarm ON L Timing OFF L Timing ON S Timing OFF S Timing ON S2 Timing OFF S2 Timing ON G Timing OFF G Timing ON G Alarm OFF G Alarm ON Gext Timing OFF Gext Timing ON Gext Alarm OFF Gext Alarm ON T Warning OFF T Warning ON T Alarm OFF T Alarm ON T Alarm Block OFF T Alarm Block ON
Value 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93
Event type D Timing OFF D Timing ON U Timing OFF U Timing ON U Alarm OFF U Alarm ON Uv Timing OFF Uv Timing ON Uv Alarm OFF Uv Alarm ON Ov Timing OFF Ov Timing ON Ov Alarm OFF Ov Alarm ON Rv Timing OFF Rv Timing ON Rv Alarm OFF Rv Alarm ON Rp Timing OFF Rp Timing ON Rp Alarm OFF Rp Alarm ON Uf Timing OFF Uf Timing ON Uf Alarm OFF Uf Alarm ON Of Timing OFF Of Timing ON Of Alarm OFF Of Alarm ON Freq Alarm OFF Freq Alarm ON I-warning Alarm OFF I-warning Alarm ON Load control threshold nr.1 OFF Load control threshold nr.1 ON Load control threshold nr.2 OFF Load control threshold nr.2 ON Sensor continuity check 1 Alarm OFF Sensor continuity check 1 Alarm ON Sensor continuity check 2 Alarm OFF Sensor continuity check 2 Alarm ON Sensor continuity check 3 Alarm OFF Sensor continuity check 3 Alarm ON Sensor continuity check Ne Alarm OFF Sensor continuity check Ne Alarm ON Sensor continuity check Gext Alarm OFF
Value 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135
Event type Sensor continuity check Gext Alarm ON Trip coil continuity check Alarm OFF Trip coil continuity check Alarm ON Rating Plug Alarm OFF Rating Plug Alarm ON Installation error OFF Installation error ON Power factor error OFF Power factor error ON Phase cycle error OFF Phase cycle error ON Configuration error ON Configuration error OFF CB status error OFF CB status error ON L tripped S tripped S2 tripped I tripped Iinst tripped G tripped Gext tripped T tripped D tripped U tripped UV tripped OV tripped RV tripped RP tripped UF tripped OF tripped Electronic trip test Simulated trip from test unit External input trip Hardware Error Trip 24dc auxiliary supply On Trip Reset History Trip Reset History Measure Reset Energy Reset PR120/V supply On Test connector supply On
Table 64 TAB_LOG_EVENTS
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
36/45
6.
APPENDIX
6.1
PARAMETER PROGRAMMING WARNING: Through the system bus it is allowed to open a programming session only in REMOTE functioning mode. There is a validity programming session timeout of 5minutes once expired the session is aborted; to extend it of 5 more minutes more it is sufficient to re-send an open programming session command
Programming session correctly handled: Open session Send parameters
Stop session
Check parameters OK Save in device nonError code = 0 volatile memory Progr. ok = 1 Progr. fail = 1 Session = 1
Progr. ok = 1 Progr. fail = 0 Session = 0 Par. changed = 1
Programming session open (system bus programming session = 1)
Programming failed: Open session Send parameters
Stop session
Check parameters Reload device internal error: set Error code parameters
Progr. ok = 1 Progr. fail = 1 Session = 1
Progr. ok = 0 Progr. fail = 1 Session = 0
Programming session open (system bus programming session = 1)
Programming aborted: Open session Send parameters
Abort session
Reload device internal parameters
Progr. ok = 1 Progr. fail = 1 Session = 1
Model
Programming session open (system bus programming session = 1)
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Progr. ok = 0 Progr. fail = 0 Session = 0
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
37/45
6.2
RELAYS AND DATA LOGGER “CUSTOM” SETTING
Through the system bus it is possible to configure data logger trigger and programmable relays function in a more sophisticated mode, in the following way: Writing in “Data logger Trigger Type” or “Loc Bus Relay X Function” or “PX Function” registers (a value greater than list values) is possible to configure custom functionality as described in the following table. 15 OR AND
WORD (bits) 14 13 12 11 10 9 8 7 Byte placement (offset from 0x100 address) in the STATE; numeration start from 1.
6
5
4
3
2
1
0
Bits mask to be monitored in the byte
Table 65 relay and Datalogger custom setting Bit 7 ÷ 0: bit mask used bye trigger or function. Bit 14 ÷ 8: byte offset in the device STATE. Bit 15: if 0 means OR function among selected bits (mask), if 1 means AND function. Example 1: to configure data logger trigger type to stop when at least one of the listed conditions occur ( L tripped, S tripped, I tripped and G tripped) the value to write is: Bit 7 ÷ 0 = 00101011 (1 in correspondence of desired bits). Bit 14 ÷ 8 = 00001111 = 15 ( byte containing conditions is the 15th of STATE). Bit 15 = 0 (OR function). Therefore Data logger Trigger Type = 0x0F2B Example 2: to configure data logger trigger type to stop when all the listed conditions occur (UV Timing, RV Timing and RP timing) the value to write is: Bit 7 ÷ 0 = 10100010 (1 in correspondence of desired bits). Bit 14 ÷ 8 = 0001001 = 9 ( byte containing conditions is the 15th of STATE). Bit 15 = 1 (AND function). Therefore Data logger Trigger Type = 0x19A2
6.3
MEASURE HISTORY DATA STRUCTURE
The measure history log (0) contains the following information: Marker History code Saving period Day Hour + minute Total mean active power Total maximum active power Maximum current and relative phase Maximum line voltage and relative phase Minimum line voltage and relative phase The Marker (word length) is a general code for all non-volatile memory structure used to distinguish valid data (marker = 0x0000) from not valid data (marker = 0x5555) The history code has 3 types of recorded data: Nr. 0 = Normal record. Nr. 1 = First record after a supply power-up. Nr. 2 = First record after a saving period change.
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
38/45
Saving period mean, in the case nr.0 and nr.2, the elapsed time in minutes from previous record. In case nr.1 an almost empty structure is recorded only to show power supply returns; only Marker and History code have mean. Day, hour and minutes are the time-stamp of structure recording time. Could take place the following situations with e.g. saving period = 1hour. 1. Normal situation (history code 0): 1h
2.
1h
For e.g. after 27minutes from last recording time the Saving period is changed to 10minutes (history code 2): 1h
3.
1h
27m
10m
For e.g. after 14minutes from last recording time there is an auxiliary power supply failure and then a new power-up (history code 1): 1h
14m
…
Power-up
Time gap considered NULL
6.4
1h
WAVEFORM AND HARMONICS
Sending a “start acquisition waveform + harmonics” command the acquisition of waveform samples (4.17) and the relative harmonics calculation can be obtained. There are two available commands: 1. Start acquisition: the waveform device resource is allocated to system bus, samples are acquired simultaneously from several channel and the harmonic calculation starts on selected channel. When calculation finish the glitch STATE bit “waveform available” is set. 2. Stop acquisition: the waveform device resource is released and become available for other requests (e.g. from HMI device); an eventual harmonic calculation in progress will be concluded before releasing the resource. Start acquisition command need a parameter field defining on which channel the harmonic calculation takes place; following table explains parameter and result link. Parameter value (L1) (L2) (L3) (Ne) (V12) (V23) (V31)
Table 57 Waveforms
Table 44 Harmonic measures L1 harmonic calc L2 harmonic calc L3 harmonic calc Ne harmonic calc V12 harmonic calc V23 harmonic calc V31 harmonic calc
Samples from L1, L2, L3 and Ne currents acquired simultaneously. Samples from V12, V23, and V31 line voltages acquired simultaneously.
Table 66 waveform and harmonics WARNING: All currents or all line voltages are acquired simultaneously but only for the selected channel there will be the harmonic calculation. Therefore sending a start command on a different channel ( in the same current or voltage block) allows to don’t start a new acquisition but only to calculate harmonics; sending command on the same channel it will generate a refresh of all samples before harmonic calculation.
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
39/45
Sequence example: start L1 : L1, L2, L3, Ne samples acquisition and L1 harmonic calc start L2 : only L2 harmonics calc; no new sample acquisition start L2 : new samples acquisition (refresh functionality) and L2 harmonic calc start V23 : line voltages samples acquisition and V23 harmonic calc Resource allocation diagram: Start command
Waveform available
Start command
Waveform available
Stop command
Allocated resource WARNING: While the resource is allocated none could use it (an exception busy response will be returned); the STATE flag “waveform session status” show the allocation There is a 5minutes allocation timeout of resource once expired the resource is released. To continue the resource allocation 5minutes more it is sufficient to send a new start acquisition command before timeout ending
6.5
CB STATE INFORMATION
The device using the following dedicated input reports CB state: CB open CB close CB connected / withdrawn Springs charged The device filters and checks CB state producing the following information: CB open / close CB state undefined CB state error CB connected / withdrawn Springs charged / discharged State CB open/close State CB undefined State CB error
Value 0 = Open Input CB open = 1 + Input CB close = 0 + NO flowing current Value 0 = Open Input CB open = 1 + Input CB close = 0 + NO flowing current OR Input CB open = 0 + Input CB close = 1 Value 0 = Open Other cases
State Springs
Input CB open = 0 + Input CB close = 1
Filtered by 30 ms Notes
1 = Close Input CB open = Input CB close
Filtered by 30 ms Notes
1 = Close
Input CB open = 1 + Input CB close = 0 + Current flowing
Filtered by 30 ms
Value
State CB connected
Notes
1 = Close
0 = Open
Notes
1 = Close
Input CB connected = 0
Input CB connected = 1
Filtered by 1000 ms
Value 0 = Open Input charged springs = 0
1 = Close Input charged springs = 1
Notes Filtered by 200 ms
Table 67 CB state information
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
40/45
6.6
STATISTICAL DATA
Device produces same statistical data relevant to system bus communication and to CB operations: 1.
communication statistical data a. received messages nr. b. received messages nr. With crc error c. set messages nr. d. Slave Busy exception responses nr. e. Total exception responses nr. Must be: a = b + c + nr. Broadcast messages Data described above is NOT updated in self-supply device mode.
2.
CB operation statistical data a. Contact wear b. Total Protection Trip number
3.
CB operation statistical data NOT updated in self-supply device mode c. total operation nr. d. manual operation nr. e. protection trip nr. f. protection trip fail nr. g. trip test nr.
The relationship between them: c = d + e + f + g , b ≥ e + f. The following diagram shows the CB statistical data calculation method:
No
New OPEN?
No
No
No
Auxiliary supply present?
Trip open?
(c)Total operation += 1 Protection open?
Protection open?
(b)Total protection trip nr. += 1
(d)Manual operation +=1
(e)Protection trip += 1
No
Trip Failed?
No
(g)Trip test + =1
(f)Trip fail + =1
Save statistical data in non-volatile memory
END
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
41/45
6.7
COMMANDS EXECUTION CONDITIONS
To the condition below reported must be appended: 1. commands are accepted only in REMOTE operation device mode. 2. with TEST unit connected only “CB OPEN” command is accepted Command type Dummy command Trip reset Signaling reset Communication statistics reset Log events reset Start programming session Abort programming session Stop programming session
Action No action Reset trip STATE bits Reset signaling module and local bus unit STATE bits Reset statistical data Reset events data Open programming session Abort programming session End programming session
CB Open
Activate YO
CB Close
Activate YC
CB reset Wink toggle command History measure reset Energy counters reset Data logger trigger restart
Reset trip STATE bits LCD backlight wink ON or OFF Reset measure data Reset Energy data Waiting trigger status
Data logger stop
Trigger immediately
Waveform + harmonics acquisition start
Open waveform acquisition session
Waveform + harmonics acquisition stop
End waveform acquisition session
Acceptance conditions NO protection timings Programming session opened Programming session opened, NO consistency check errors, NO protection timings CB connected, CB open command NOT executing, CB close command NOT executing CB connected, CB OPEN, CB NOT undefined, NO trip executing, CB open command NOT executing, CB close command NOT executing NO trip execution, Data logger enabled, Triggered acquisition completed. NO trip execution, Data logger enabled, Triggered acquisition completed. PR123 unit, I max current ≤ 2 In, Imin. Current ≥ 0.1 In, NE sensor present for NE, L1, L2, L3 sensor connected, PR120/V module present for V12, V23, V31 PR123 unit, Waveform session opened.
Table 68 Commands acceptance conditions
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
42/45
6.8
MEASURE LIMITS AND REPRESENTATION Measure
Special value Not available Too low Saturation
Description
Active, reactive and phase power (P1, P2, P3, Q1, Q2, Q3, S1, S2, S3)
Not available Too low Positive saturation Negative saturation
Sensor disconnected I < Imin I > Imax Sensor disconnected, IG > Igmax IG < Igmin External toroid absent, Sensor disconnected IGEXT < IGEXTmin IGEXT > IGEXTmax Rc toroid absent, Toroid disconnected IRC < IRC min. IRC > IRC max. All sensors disconnected, All current values < Imin PR120/V module absent V < Vmin V > Vmax PR120/V module absent, Sensor disconnected, I < Imin, V < Vmin | P | < Pmin P > Pmax P < - Pmax
Total power (P,Q, S)
Not available
All phase power not available
Currents
Internal ground current
Not available Too low Not available
External ground current
Too low Saturation Not available
Rc current
Too low Saturation
Maximum current phase
Not available
Voltages
Not available Too low Saturation
Active, reactive and apparent energy
Positive saturation Negative saturation
Total cos
Not available
Peak factor
Not available Not available
Frequency (see note)
Harmonic amplitude Contact wear
Too low Too high Not available Saturation Saturation
231-1
E> E < -231 S or P not available | S | or | P | < Pmin S or P > Pmax S or P < -Pmax Sensor disconnected, I < Imin Peak PR120/V module absent or V maximum frequency Amplitude < Harm min Amplitude > Harm max CW > 100%
Modbus data
Local HMI value
0xFFFFFFFF 0 Imax
I > xxx A
0xFFFFFFFF
0
0xFFFFFFFF
0 Imax
I > xxx A
0xFFFFFFFF
0 Imax
I > xxx A
0
0xFFFF 0 Vmax
V > xxx V
0x7FFFFFFF
0 Pmax - Pmax
P > xxx kW P < xxx kW
0x7FFFFFFF
0x7FFFFFFF 0x80000000
E > xxx kWh E < xxx kWh
0x7FFF
0xFFFF
0xFFFF
Minimum frequency Maximum frequency 0 Harm max 65000
Freq < Freq min Freq > Freq max > Harm max 100%
Table 69 Measure limits and representation Legend: Imin Imin Peak Imax Igmin Igmax IGEXTmin IGEXTmax IRCmin IRCmax
= 0,05 In = 0,2 In = 16 In = 0,1 In = 16 In = 0,1 In = 4 In = 2 InRc = 32,5 InRc
Vmin Vmax Pmin Pmax Fmin Fmax Harm min Harm max
= 5,7 V = 922V = 0,5 In * 5,7 V = 16 In * 922V = 29,5 Hz (with hysteresis up to 31 Hz) = 80,5 Hz (with hysteresis up to 79 Hz) =2% = 500 %
Note: the measure of frequency is subject hysteresis in the intervals 29,5 Hz ÷ 31 Hz and 79 Hz ÷ 80,5 Hz, therefore it is valid in the range 31 Hz ≤ freq ≤ 79 Hz.
6.9
CONTACT WEAR
The contact wear is calculated as the usury sum owed at every single CB open and it’s explicit in % (0 ÷ 100[%]): It’s available in format 0 ÷ 65000 (0=0%, 65000=100%), therefore to obtain the percentage is necessary to divide the value for 650. Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
43/45
7.
REVISION HISTORY
7.1
B0431 (16/12/2015)
Added 1 2 3 5 1 2 6
Par.2.3: added Slave ID for PR332/P MM Par.3: inserted codes for PR332/P MM on the table Par.3.1: inserted references and notes to PR332/P MM Par.4.4, 4.6, 4.11, 4.12, 4.13, 4.14: completed compatibility column with references to PR332/P MM Par.4.13: added 1130 and 1131 alternative to startup threshold I Par.4.14: inserted trip MM as alternative to I Added Revision History section
Modified 1 Deleted 1
Model
L2572
L4612
L3987
B0341
Apparatus
Doc.No
Modbus system Interface for relays PR122-3 and PR332-3 1SDH000556R0001
Scale Page NO.
44/45
Power and productivity for a better worldTM