Miniature Circuit Breakers (MCB) Earth Leakage Circuit Breaker (ELCB)

Miniature Circuit Breakers (MCB) Earth Leakage Circuit Breaker (ELCB) Miniature Circuit Breaker The Miniature Circuit Breakers (MCB) are current-li...
66 downloads 2 Views 4MB Size
Miniature Circuit Breakers (MCB) Earth Leakage Circuit Breaker (ELCB)

Miniature Circuit Breaker

The Miniature Circuit Breakers (MCB) are current-limiting devices. These MCB’s force a fast and efficient extinguishing of the arc, which results in a limiting of the short circuit current before it can go up to its peak. The time tE (tripping response time between the short circuit occurrence and the separation of the contacts) is extremely short, due to the use of the electromagnetic principle in the magnetic trip mechanism. The oscilloscope reading shows time tE = 0.7 msec. The fast and wide contact separation causes the rapid elongation of the arc, which establishes a sharply rising arc voltage across the contacts. Parallel to that, the arc is guided between special plastic plates to the arc chamber by the “arc guide”. In the arc chamber, the electrodynamic and thermodynamic forces continue the established movement of the arc to the plates of the miniature de-ion grid, which extinguishes it. The full burning voltage UB = 340 V is reached after 1.4 msec. The strong rising arc voltage works as an additional impedance, which limits the short circuit current (I = 4.5 kA) and extinguishes it far before (4.3 msec) the natural waveform zero crossover. The selectivity diagram shows the let-through-∫i2 dt (Joule/Energy Integral) of a full sine half wave (1) and MCB’s (2, 3, 4). All the shown values of the Joule-Integral (let-through-∫i2 dt) are maximum values of the MCB’s switch-off time, which only occur when the short circuit current develops at a moment of the sine half wave where the angle is between 600 and 900. In addition, the diagram shows the melting curve (let-through-∫i2 dt) of fuses according to DIN VDE 0636. The crossing of the MCB – and fuse – trip characteristics show the short circuit current up to which selectivity is still maintained. The melting curve of the fuses represents the minimum value. For example, the crossing of the curves of a B 16 A MCB and a 35 A fuse is 1.5 kA. The value for a 100 A fuse is about RA. That means, that the MCB will trip up to these short circuit currents and the fuse stays intact. The MCB’s, due to their strong current and energy limiting capabilities, meet all the requirements for the highest current and energy limiting Class 3 according to DIN VDE 0641 Part 11 / EN 60898 / IEC 60898. As a matter of fact, the real let-through values are much lower.

Selectivity between MCB’s and fuses to VDE 0636

2

Oscillogram showing the operation of a B 25 A MCB at 10 kA, cos ϕ = 0,45 – 0,50

Miniature Circuit Breakers (MCB) 10 kA and 6 kA Technical Data

Tripping Characteristic

B

C

D

K

Z

Application

Wiring protection

Wiring Protection Device Protection

Wiring Protection Power Circuit Transformers Motors

Power Circuit Transformers Motors

Semiconductor Protection for Circuits with high Impedance

1 – 4; 1 + N; 3 + N

1–3

Number of Poles 10 kA

1 – 4; 1 + N; 3 + N

Number of Poles 6 kA Breaking Capacity Current Limiting Class

10/15 kA to IEC 60947-2, EN 60947-2, DIN VDE 0660 T101 6/10 kA to IEC 60898, EN 60898, DIN VDE 0641 T11 3

3

Max. Fuse for 10 kA

Fuse according to DIN VDE 0636 125 A operating class gL

Max. Fuse for 6 kA

Fuse according to DIN VDE 0636 operating class gL (0,3 – 20 A; 80 A / 25 – 31 A; 100 A / 40 – 63 A; 125 A)

Rated Voltage AC

6 kA – 230/400 V; 10 kA – 240/415 V

Rated Voltage DC L/R = 4 ms

1 pole 60 V 2 pole 125 V in serial connection of both poles

Rated Current Range

Test Currents

1 – 3; 1 + N; 3 + N

6 – 63 A

0,3 – 63 A

0,3 – 63 A

0,3 – 63 A

0,3 – 32 A

Thermal not tripping I1 (A) > 1 h

1,13 x In

1,13 x In

1,13 x In

1,05 x In

1,05 x In

Thermal tripping I2 (A) < 1 h

1,45 x In

1,45 x In

1,45 x In

1,20 x In

1,35 x In

Electromagnetic not tripping I4 (A) > 0,1 s

3 x In

5 x In

8 x In

2 x In

Electromagnetic tripping I5 (A) < 0,1 s

5 x In

10 x In

12 x In

3 x In

Reverence Calibration Temperature

≤ 32 A 12 x In > 32 A 10 x In < 32 A 16 x In ≥ 32 A 13 x In

30 °C + 5 °C

20 °C + 5 °C

Influence of the ambient temperature on the thermal release: decrease of the current values with higher ambient temperature and increase with lower temperatures of approximately 5 % per 10 °C difference in temperature. Frequency Range

162⁄3 to 60 Hz With higher frequencies the electromagnetic tripping values increase by approximately of factor 1,1 at 100 Hz; 1,2 at 200 Hz; 1,4 at 400 Hz; DC at 1,5

Ambient air Temperature Storage and Transport Conditions

-25 °C to +55 °C -40 °C to +70 °C

Dimensions

Compare page 4

Mechanical Endurance

20.000 switching cycles (20.000 switch ons and 20.000 switch offs)

Touch Protection

Safe for fingers and back of hand according to DIN VDE 0106 T 100, BGV A2 (VBG 4)

Isolation Group According to DIN VDE 0110

C at 250 V AC B at 400 V AC

Protection type EN 60529 / IEC 60529

IP 20

Installation Position

any

Mounting

Din-rail according to DIN EN 60715 35 mm

3

Miniature Circuit Breakers (MCB) 10 kA and 6 kA Technical Data

Lead Sealability

In the on and off position of the handle. May be secured against manual switching, by a lead seal.

Climatic Resistance

Humid heat constant according to DIN IEC 60068-2 – 3 Humid heat cyclic according to DIN EN 60068-2 – 30

Vibration Resistance

> 15 g according to DIN EN 60068-2 – 59 during a load with I1

Resistance to Thermal Shocks

25 g 11 ms Connectable Conductor Cross Sections Self-adjusting clamp bottom

Type of Conductor

Maximum

Minimum

Maximum

Minimum

Single Wire

35 mm2

0,5 mm2

35 mm2

0,5 mm2

Multiple Wire

35 mm2

(16 mm2)

25 mm2

(16 mm2)

Fine Wire

25 mm2

0,5 mm2

16 mm2

0,5 mm2

Fine Wire with Ferrule

16 mm2

0,5 mm2

16 mm2

0,5 mm2

Bus Bar Cable Lug

Up to 3 mm thickness

Up to 1,5 mm thickness

Combined, Connector and Bus Bar or Cable Lug

Up to 35 mm2 and 2 mm thickness

Not possible

Torque

4

Self-adjusting clamp top

Maximum 2,5 Nm

Miniature Circuit Breakers (MCB) 10 kA and 6 kA Technical Data

Internal Resistance (mΩ) and Power Loss (Watt) per Pole (by In) Rated Current In (A) 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 12,5 13 16 20 25 32 40 50 63

B-Characteristic Internal Power Resistance Loss mΩ Watt

52,9

1,9

13,4

1,3

11,3 8,0 7,1 5,0 3,6 2,2 2,0 1,8

1,9 2,1 2,8 3,1 3,7 3,5 4,9 7,0

C-Characteristic Internal Power Resistance Loss mΩ Watt 16.600 1,5 6.850 1,7 3.050 1,7 1.750 1,8 590 1,5 420 1,7 295 1,8 200 1,8 125 1,5 109 1,7 61,6 1,5 49,1 1,8 24 1,5 13,4 1,3 8,0 8,0 7,5 5,0 3,6 2,2 1,9 1,8

D-Characteristic Internal Power Resistance Loss mΩ Watt 16.600 1,5 6.850 1,7 3.050 1,7 1.750 1,8 590 1,5 420 1,7 295 1,8 173 1,6 125 1,5 105 1,7 61,6 1,5 45,9 1,7 20,7 1,3 20,4 2,0

1,4 2,1 3,0 3,1 3,7 3,5 4,8 7,0

8,1 8,1 6,4 4,1 2,7 2,2 1,8 1,7

K-Characteristic Internal Power Resistance Loss mΩ Watt 16.860 1,5 6.850 1,7 3.050 1,7 1.750 1,8 590 1,5 420 1,7 295 1,8 200 1,8 125 1,5 109 1,7 65,4 1,6 49,1 1,8 44 2,8 31,5 3,1 8,8 1,4

1,4 2,1 2,5 2,5 2,8 3,5 4,6 6,8

7,5 6,3 4,7 2,8 2,2 2,0 1,8

Z-Characteristic Internal Power Resistance Loss mΩ Watt 31.500 2,8 10.250 2,6 5.150 2,9 2.690 2,7 940 2,4 690 2,8 430 2,7 345 3,1 225 2,8 225 3,6 105 2,6 82,3 3,0 37,1 2,4 27,8 2,8 15,1 2,4

1,9 2,5 2,9 2,9 3,5 4,9 7,0

11,3 7,4 5,8 3,6

2,9 3,0 3,7 3,7

Short Circuit Selectivity between MCB and Fuse in kA Rated Current In (A) B 6 10 Tripping C 6/8 10 Characteristics D/K 6/8 10 0,85 0,8 In (A) 25 0,7 0,7 0,7 0,6 1,6 1,6 35 1,3 1,3 1,2 1,15 2,4 2,35 Fuse 50 2,1 2,1 operating 1,9 1,8 3,5 3,3 Class gL 63 2,9 2,8 DIN VDE 2,5 2,4 5,0 4,8 0636 and 80 4,1 4,0 IEC 60269 3,5 3,4 7,6 7,3 100 6,3 6,1 5,2 4,9 10 10 125 10 10 8,8 8,0

13

16 13

20 16

13 0,8

16 0,75 0,65

0,7 0,6 1,5

20

1,1

2,2

1,7 3,2

4,6 3,9

7,1 5,9

5,7 4,8

10

5,0

10 10

10 10

7,7

1.) Above line 1 no selectivity; 2.) Below line 2 values are only for 10 kA

2,8

5,4

2,3 4,9

4,3 3,8

1.)

2,6 2,4

5,1 4,5

5,6

1,7 3,1

2,5

6,8 5,7

1,9 1,8

2,9

8,5 6,9

7,1

2,0 3,3

3,4

1,2 2,3

1,9

3,9

8,8 8,7

7,6

2,1 3,5

3,5

1,4 1,3

2,4

2,4

4,0 4,4

1,4

2,8 5,0

1,6 1,5

2,5

2,5 5,0

4,7

1,8

2,8

1,0 1,7

1,6

3,3

3,1 6,5

1,8

1,8

3,6

1,1 1,1

2,0

3,4

3,2 7,0

2,4

2,3

1,2 1,2

1,2

2,1

4,3

3,3

1,3

2,6

0,5 1,3

1,4

2,5

2,3

3,9

1,5

3,0

2,4

63

0,7 0,8

1,5

1,6

2,7

4,7

1,6

1,7

2,7

63 50

0,8 1,0

0,9

1,9

3,2

1,1 1,1

1,0

2,0

40

0,5 1,2

1,1

2,0

32

63 50

0,55

1,2

2,3

50 40

0,6

1,4 1,2

40 32

25

0,6 0,55

0,6

1,25

32 25

0,7

1,5

2,3

25 20

4,1 3,6

3,5

2.)

5

Miniature Circuit Breakers (MCB) 10 kA 

B, C and D to IEC 60898, EN 60898, DIN VDE 0641 B, C, D, K and Z to IEC 60974-2, EN 60974-2, DIN VDE 0660 Tripping Characteristics D K

Rated Current

B

C

In A

Article No.

Article No.

Article No.

Article No.

Article No.

1C030 1C050 1C075 1C1.0 1C1.6 1C2.0 1C2.5 1C3.0 1C3.5 1C4.0 1C5.0 1C6.0 1C8.0 1C.10

1D030 1D050 1D075 1D1.0 1D1.6 1D2.0 1D2.5 1D3.0 1D3.5 1D4.0 1D5.0 1D6.0 1D8.0 1D.10

1K030 1K050 1K075 1K1.0 1K1.6 1K2.0 1K2.5 1K3.0 1K3.5 1K4.0 1K5.0 1K6.0 1K8.0 1K.10

1Z030 1Z050 1Z075 1Z1.0 1Z1.6 1Z2.0 1Z2.5 1Z3.0 1Z3.5 1Z4.0 1Z5.0 1Z6.0 1Z8.0 1Z.10

1K.12

1Z.12

1C.13 1C.16 1C.20 1C.25 1C.32 1C.40 1C.50 1C.63

1D.13 1D.16 1D.20 1D.25 1D.32 1D.40 1D.50 1D.63

1K.16 1K.20 1K.25 1K.32 1K.40 1K.50 1K.63

1Z.16 1Z.20 1Z.25 1Z.32

Z

Weight g/each

Packing unit

150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300

5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5

Single-Pole 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 10 12,5 13 16 20 25 32 40 50 63

1B6.0 1B.10 1B.10rot 1B.13 1B.16 1B.20 1B.25 1B.32 1B.40 1B.50 1B.63

Single-Pole with Switched Neutral 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 12,5 13 16 20 25 32 40 50 63

6

8B.10

8C030 8C050 8C075 8C1.0 8C1.6 8C2.0 8C2.5 8C3.0 8C3.5 8C4.0 8C5.0 8C6.0 8C8.0 8C.10

8D030 8D050 8D075 8D1.0 8D1.6 8D2.0 8D2.5 8D3.0 8D3.5 8D4.0 8D5.0 8D6.0 8D8.0 8D.10

8B.13 8B.16 8B.20 8B.25 8B.32 8B.40 8B.50 8B.63

8C.13 8C.16 8C.20 8C.25 8C.32 8C.40 8C.50 8C.63

8D.13 8D.16 8D.20 8D.25 8D.32 8D.40 8D.50 8D.63

8B6.0

8K030 8K050 8K075 8K1.0 8K1.6 8K2.0 8K2.5 8K3.0 8K3.5 8K4.0 8K5.0 8K6.0 8K8.0 8K.10 8K.12 8K.16 8K.20 8K.25 8K.32 8K.40 8K.50 8K.63

Miniature Circuit Breakers (MCB) 10 kA 

B, C and D to IEC 60898, EN 60898, DIN VDE 0641 B, C, D, K and Z to IEC 60974-2, EN 60974-2, DIN VDE 0660 Tripping Characteristics D K

Rated Current

B

C

In A

Article No.

Article No.

Article No.

Article No.

Article No.

2B.10

2C030 2C050 2C075 2C1.0 2C1.6 2C2.0 2C2.5 2C3.0 2C3.5 2C4.0 2C5.0 2C6.0 2C8.0 2C.10

2D030 2D050 2D075 2D1.0 2D1.6 2D2.0 2D2.5 2D3.0 2D3.5 2D4.0 2D5.0 2D6.0 2D8.0 2D.10

2K030 2K050 2K075 2K1.0 2K1.6 2K2.0 2K2.5 2K3.0 2K3.5 2K4.0 2K5.0 2K6.0 2K8.0 2K.10 2K.12

2Z030 2Z050 2Z075 2Z1.0 2Z1.6 2Z2.0 2Z2.5 2Z3.0 2Z3.5 2Z4.0 2Z5.0 2Z6.0 2Z8.0 2Z.10 2Z.12

2B.13 2B.16 2B.20 2B.25 2B.32 2B.40 2B.50 2B.63

2C.13 2C.16 2C.20 2C.25 2C.32 2C.40 2C.50 2C.63

2D.13 2D.16 2D.20 2D.25 2D.32 2D.40 2D.50 2D.63

2K.16 2K.20 2K.25 2K.32 2K.40 2K.50 2K.63

2Z.16 2Z.20 2Z.25 2Z.32

3B.10

3C030 3C050 3C075 3C1.0 3C1.6 3C2.0 3C2.5 3C3.0 3C3.5 3C4.0 3C5.0 3C6.0 3C8.0 3C.10

3D030 3D050 3D075 3D1.0 3D1.6 3D2.0 3D2.5 3D3.0 3D3.5 3D4.0 3D5.0 3D6.0 3D8.0 3D.10

3K030 3K050 3K075 3K1.0 3K1.6 3K2.0 3K2.5 3K3.0 3K3.5 3K4.0 3K5.0 3K6.0 3K8.0 3K.10 3K.12

3Z030 3Z050 3Z075 3Z1.0 3Z1.6 3Z2.0 3Z2.5 3Z3.0 3Z3.5 3Z4.0 3Z5.0 3Z6.0 3Z8.0 3Z.10 3Z.12

3B.13 3B.16 3B.20 3B.25 3B.32 3B.40 3B.50 3B.63

3C.13 3C.16 3C.20 3C.25 3C.32 3C.40 3C.50 3C.63

3D.13 3D.16 3D.20 3D.25 3D.32 3D.40 3D.50 3D.63

3K.16 3K.20 3K.25 3K.32 3K.40 3K.50 3K.63

3Z.16 3Z.20 3Z.25 3Z.32

Z

Weight g/each

Packing unit

300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450

4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

Double-Pole 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 12,5 13 16 20 25 32 40 50 63

2B6.0

Triple-Pole 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 12,5 13 16 20 25 32 40 50 63

3B6.0

7

Miniature Circuit Breakers (MCB) 10 kA 

B, C and D to IEC 60898, EN 60898, DIN VDE 0641 B, C, D, K and Z to IEC 60974-2, EN 60974-2, DIN VDE 0660 Tripping Characteristics D K

Rated Current

B

C

In A

Article No.

Article No.

Article No.

Article No.

Z

Weight g/each

Packing unit

600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Article No.

Triple-Pole with Switched Neutral 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 12,5 13 16 20 25 32 40 50 63

9B.10

9C030 9C050 9C075 9C1.0 9C1.6 9C2.0 9C2.5 9C3.0 9C3.5 9C4.0 9C5.0 9C6.0 9C8.0 9C.10

9D030 9D050 9D075 9D1.0 9D1.6 9D2.0 9D2.5 9D3.0 9D3.5 9D4.0 9D5.0 9D6.0 9D8.0 9D.10

9B.13 9B.16 9B.20 9B.25 9B.32 9B.40 9B.50 9B.63

9C.13 9C.16 9C.20 9C.25 9C.32 9C.40 9C.50 9C.63

9D.13 9D.16 9D.20 9D.25 9D.32 9D.40 9D.50 9D.63

4B.10

4C030 4C050 4C075 4C1.0 4C1.6 4C2.0 4C2.5 4C3.0 4C3.5 4C4.0 4C5.0 4C6.0 4C8.0 4C.10

4D030 4D050 4D075 4D1.0 4D1.6 4D2.0 4D2.5 4D3.0 4D3.5 4D4.0 4D5.0 4D6.0 4D8.0 4D.10

4B.13 4B.16 4B.20 4B.25 4B.32 4B.40 4B.50 4B.63

4C.13 4C.16 4C.20 4C.25 4C.32 4C.40 4C.50 4C.63

4D.13 4D.16 4D.20 4D.25 4D.32 4D.40 4D.50 4D.63

9B6.0

9K030 9K050 9K075 9K1.0 9K1.6 9K2.0 9K2.5 9K3.0 9K3.5 9K4.0 9K5.0 9K6.0 9K8.0 9K.10 9K.12 9K.16 9K.20 9K.25 9K.32 9K.40 9K.50 9K.63

Four-Pole 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 12,5 13 16 20 25 32 40 50 63

8

4B6.0

4K030 4K050 4K075 4K1.0 4K1.6 4K2.0 4K2.5 4K3.0 4K3.5 4K4.0 4K5.0 4K6.0 4K8.0 4K.10 4K.12 4K.16 4K.20 4K.25 4K.32 4K.40 4K.50 4K.63

Miniature Circuit Breakers (MCB) 6 kA B and C to IEC 60898, EN 60898, DIN VDE 0641 IEC 60974-2, EN 60974-2, DIN VDE 0660 Rated Current

Tripping Characteristics

In A

Article No. Article No.

B

C

Weight g/each

Packing unit

C

Weight g/each

Packing unit

Single-Pole with Switched Neutral

1B6.06 1B106 1B136 1B166 1B206 1B256 1B326 1B406 1B506 1B636

1C0.306 1C0.506 1C0.756 1C1.06 1C1.66 1C2.06 1C2.56 1C3.06 1C3.56 1C4.06 1C5.06 1C6.06 1C8.06 1C106 1C136 1C166 1C206 1C256 1C326 1C406 1C506 1C636

150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

Double-Pole 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 13 16 20 25 32 40 50 63

B

Article No. Article No.

Single-Pole 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 13 16 20 25 32 40 50 63

Tripping Characteristics

2B6.06 2B106 2B136 2B166 2B206 2B256 2B326 2B406 2B506 2B636

8B6.06 8B106 8B136 8B166 8B206 8B256 8B326 8B406 8B506 8B636

8C0.306 8C0.506 8C0.756 8C1.06 8C1.66 8C2.06 8C2.56 8C3.06 8C3.56 8C4.06 8C5.06 8C6.06 8C8.06 8C106 8C136 8C166 8C206 8C256 8C326 8C406 8C506 8C636

300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300

5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5

450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450

4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

Triple-Pole 2C0.306 2C0.506 2C0.756 2C1.06 2C1.66 2C2.06 2C2.56 2C3.06 2C3.56 2C4.06 2C5.06 2C6.06 2C8.06 2C106 2C136 2C166 2C206 2C256 2C326 2C406 2C506 2C636

300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300

5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5

3B6.06 3B106 3B136 3B166 3B206 3B256 3B326 3B406 3B506 3B636

3C0.306 3C0.506 3C0.756 3C1.06 3C1.66 3C2.06 3C2.56 3C3.06 3C3.56 3C4.06 3C5.06 3C6.06 3C8.06 3C106 3C136 3C166 3C206 3C256 3C326 3C406 3C506 3C636

9

Miniature Circuit Breakers (MCB) 6 kA B and C to IEC 60898, EN 60898, DIN VDE 0641 IEC 60974-2, EN 60974-2, DIN VDE 0660 Rated Current

Tripping Characteristics

In A

Article No. Article No.

B

C

Weight g/each

Packing unit

Triple-Pole with Switched Neutral 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 13 16 20 25 32 40 50 63

10

9B6.06 9B106 9B136 9B166 9B206 9B256 9B326 9B406 9B506 9B636

9C0.306 9C0.506 9C0.756 9C1.06 9C1.66 9C2.06 9C2.56 9C3.06 9C3.56 9C4.06 9C5.06 9C6.06 9C8.06 9C106 9C136 9C166 9C206 9C256 9C326 9C406 9C506 9C636

600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Accessories for Miniature Circuit Breakers (MCB)

Shunt Trip Module

Operating Voltage

Max. Operating Current at Rated Voltage (t 1h Thermal tripping I2 (A) < 1h Electromagnetic not tripping I4 (A) > 0,1h Elecreomagnetic tripping I5 (A) < 0,1h Reference Calibration Temperature

B

1,13 x In

1,13 x In

1,45 x In

1,45 x In

3 x In

5 x In

5 x In

5 x In 30 °C + 5 °C

Connectable Conductor Cross Sections Type of Conductors Single Wire Fine Wire Fine Wire with Ferrule Torque

Minimum 0,5 mm2 0,5 mm2 0,5 mm2

Maximum 10 mm2 6 mm2 6 mm2 max. 1,2 Nm

15



Miniature Circuit Breakers (MCB) UL and CSA 5/10 kA

Tripping Characteristic

B

C

Application

Wiring Protection

Wiring Protection Device Protection

D

E

G

Z

Wiring Protection Wiring Protection Semiconductor Power Circuit Power Circuit Wiring Protection Protection for Transformers Transformers Device Protection Circuits with high Motors Motors Impedance

Number of Poles

1 – 3; 1 + N; 3 + N

Breaking Capacity

Please consult for application in USA, Canada and Europe the data sheet on page 18

Current Limiting Class

Test Currents

Technical Data

3

3

Maximum Fuse

Please consult for application in USA, Canada and Europe the data sheet on page 18

Rated Voltage AC

277 / 480 V

Rated Voltage DC L/R = 4 ms

1 pole 60 V 2 pole 125 V in serial connection of both poles

Rated Current Range

6 – 60 A

0,3 – 60 A

0,3 – 60 A

0,3 – 60 A

0,3 – 60 A

0,3 – 32 A

Thermal not tripping I1 (A) > 1 h

1,13 x In

1,13 x In

1,13 x In

1,05 x In

1,05 x In

1,05 x In

Thermal tripping I2 (A) < 1 h

1,45 x In

1,45 x In

1,45 x In

1,35 x In

1,35 x In

1,35 x In

Electromagnetic not tripping I4 (A) > 0,1 s

3 x In

5 x In

10 x In

11 x In

8 x In

2 x In

Electromagnetic tripping I5 (A) < 0,1 s

5 x In

10 x In

16 x In

18 x In

10 x In

3 x In

Reverence Calibration Temperature

30 °C + 5 °C

20 °C + 5 °C

Influence of the surrounding temperature on the thermal release: decrease of the current values with higher ambient temperature and increase with lower temperatures of approximately 5 % per 10 °C difference in temperature. Frequency Range

162⁄3 to 60 Hz With higher frequencies the electromagnetic tripping values increase by approximately of factor 1,1 at 100 Hz; 1,2 at 200 Hz; 1,4 at 400 Hz; DC at 1,5

16

Ambient air Temperature Storage and Transport Conditions

-25 °C to +55 °C -40 °C to +70 °C

Dimensions

Compare page 17

Mechanical Endurance

20.000 switching cycles (20.000 switch ons and 20.000 switch offs)

Touch Protection

Safe for fingers and back of hand according to DIN VDE 0106 T 100, BGV A2 (VBG 4)

Isolation Group According to DIN VDE 0110

C at 250 V AC B at 400 V AC

Protection Type EN 60529 / IEC 60529

IP 20

Installation Position

any

Mounting

Din-rail according to DIN EN 60715 35 mm



Miniature Circuit Breakers (MCB) UL and CSA 5/10 kA Technical Data

Lead Sealability

In the on and off postiton of the handle. May be secured against manual switching, by a lead seal.

Climatic Resistance

Humid heat constant according to DIN IEC 60068-2 – 3 Humid heat cyclic according to DIN EN 60068-2 – 30

Vibration Resistance

> 15 g according to DIN EN 60068-2 – 59 during a load with I1

Resistance to Thermal Shocks

25 g 11 ms Connectable Conductor Cross Sections Self-adjusting clamp bottom

Self-adjusting clamp top

Type of Conductor

Maximum

Minimum

Maximum

Minimum

Single Wire

35 mm2

0,5 mm2

35 mm2

0,5 mm2

Multiple Wire

35 mm2

(16 mm2)

25 mm2

(16 mm2)

Fine Wire

25 mm2

0,5 mm2

16 mm2

0,5 mm2

Fine Wire with Ferrule

16 mm2

0,5 mm2

16 mm2

0,5 mm2

Bus Bar Cable Lug

Up to 3 mm thickness

Up to 1,5 mm thickness

Combined, Connector and Bus Bar or Cable Lug

Up to 35 mm2 and 2 mm thickness

Not possible

Torque

Maximum 2,5 Nm

17



Miniature Circuit Breakers (MCB) UL and CSA Technical Data

For Applications in USA and Canada Tripping Characteristic

B, C, D, E, G and Z

Regulations

UL 508 and CSA-22.2 Nr.14

Breaking Capacity

Maximum Fuse for Group Installations

Number of Poles

Maximum Rated Voltage V

Rated Current Range A

Breaking Capacity kA

Fuse

1/2/1+N

277

0,3 – 10

10

no

1/2/1+N

277

12 – 60

5

no

1/2/1+N

277

12 – 60

10

4 x In

2/3/3+N

480

0,3 – 10

10

no

2 / 3 / 3 +N

480

12 – 60

5

no

2/3/3+N

480

12 – 60

10

4 x In

2/3/3+N

480

40 – 60 E

5

4 x In

1/1+N

277

0,3 – 10

10

1/1+N

277

12 – 60

5

2/3/3+N

480

0,3 – 10

10

2/3/3+N

480

12 – 60

5

1.)

800 A

1.)

Characteristic E

For Applications in Europe Tripping Characteristic

B, C, D, E, G and Z

Regulations

DIN VDE 0660 T 101, IEC 60947-2, EN 60947-2, UL 508 and CSA-22.2 Nr.14 Characteristic B, C and D according to DIN VDE 0641 T11, IEC 60898 and EN 60898 Number of Poles

Maximum Rated Voltage V

Rated Current Range A

Breaking Capacity kA

Maximum Fuse

1/2/1+N

277

0,3 – 60

10

160

2/3/3+N

480

0,3 – 60

10

160

Breaking Capacity

18



Miniature Circuit Breakers (MCB)

to UL 508 and CSA-22.2 Nr.14  B, C and D according to IEC 60898, EN 60898 and DIN VDE 0641 T11 Rated Current In A

B

C

Tripping Characteristic D G

E

Z

 Weight g/each

Packing units

Article No. Article No. Article No. Article No. Article No. Article No.

Single-Pole 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 13 16 20 25 32 40 50 60

1BU6 1BU10 1BU13 1BU16 1BU20 1BU25 1BU32 1BU40 1BU50 1BU60

1CU03 1CU05 1CU075 1CU1 1CU1.6 1CU2 1CU2.5 1CU3 1CU3.5 1CU4 1CU5 1CU6 1CU8 1CU10 1CU13 1CU16 1CU20 1CU25 1CU32 1CU40 1CU50 1CU60

1DU03 1DU05 1DU075 1DU1 1DU1.6 1DU2 1DU2.5 1DU3 1DU3.5 1DU4 1DU5 1DU6 1DU8 1DU10 1DU13 1DU16 1DU20 1DU25 1DU32 1DU40 1DU50 1DU60

1GU03 1GU05 1GU075 1GU1 1GU1.6 1GU2 1GU2.5 1GU3 1GU3.5 1GU4 1GU5 1GU6 1GU8 1GU10 1GU13 1GU16 1GU20 1GU25 1GU32 1GU40 1GU50 1GU60

1EU03 1EU05 1EU075 1EU1 1EU1.6 1EU2 1EU2.5 1EU3 1EU3.5 1EU4 1EU5 1EU6 1EU8 1EU10 1EU13 1EU16 1EU20 1EU25 1EU32 1EU40 1EU50 1EU60

1ZU03 1ZU05 1ZU075 1ZU1 1ZU1.6 1ZU2 1ZU2.5 1ZU3 1ZU3.5 1ZU4 1ZU5 1ZU6 1ZU8 1ZU10 1ZU13 1ZU16 1ZU20 1ZU25 1ZU32

150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

2GNU03 2GNU05 2GNU075 2GNU1 2GNU1.6 2GNU2 2GNU2.5 2GNU3 2GNU3.5 2GNU4 2GNU5 2GNU6 2GNU8 2GNU10 2GNU13 2GNU16 2GNU20 2GNU25 2GNU32 2GNU40 2GNU50 2GNU60

2ENU03 2ENU05 2ENU075 2ENU1 2ENU1.6 2ENU2 2ENU2.5 2ENU3 2ENU3.5 2ENU4 2ENU5 2ENU6 2ENU8 2ENU10 2ENU13 2ENU16 2ENU20 2ENU25 2ENU32 2ENU40 2ENU50 2ENU60

2ZNU03 2ZNU05 2ZNU075 2ZNU1 2ZNU1.6 2ZNU2 2ZNU2.5 2ZNU3 2ZNU3.5 2ZNU4 2ZNU5 2ZNU6 2ZNU8 2ZNU10 2ZNU13 2ZNU16 2ZNU20 2ZNU25 2ZNU32

300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300

5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5

Singel-Pole with Switched Neutral 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 13 16 20 25 32 40 50 60

2BNU6 2BNU10 2BNU13 2BNU16 2BNU20 2BNU25 2BNU32 2BNU40 2BNU50 2BNU60

2CNU03 2CNU05 2CNU075 2CNU1 2CNU1.6 2CNU2 2CNU2.5 2CNU3 2CNU3.5 2CNU4 2CNU5 2CNU6 2CNU8 2CNU10 2CNU13 2CNU16 2CNU20 2CNU25 2CNU32 2CNU40 2CNU50 2CNU60

2DNU03 2DNU05 2DNU075 2DNU1 2DNU1.6 2DNU2 2DNU2.5 2DNU3 2DNU3.5 2DNU4 2DNU5 2DNU6 2DNU8 2DNU10 2DNU13 2DNU16 2DNU20 2DNU25 2DNU32 2DNU40 2DNU50 2DNU60

19



Miniature Circuit Breakers (MCB)

to UL 508 and CSA-22.2 Nr.14  B, C and D according to IEC 60898, EN 60898 and DIN VDE 0641 T11 Rated Current In A

B

C

Tripping Characteristic D G

E

Z

 Weight g/each

Packing units

Article No. Article No. Article No. Article No. Article No. Article No.

Double-Pole 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 13 16 20 25 32 40 50 60

2BU6 2BU10 2BU13 2BU16 2BU20 2BU25 2BU32 2BU40 2BU50 2BU60

2CU03 2CU05 2CU075 2CU1 2CU1.6 2CU2 2CU2.5 2CU3 2CU3.5 2CU4 2CU5 2CU6 2CU8 2CU10 2CU13 2CU16 2CU20 2CU25 2CU32 2CU40 2CU50 2CU60

2DU03 2DU05 2DU075 2DU1 2DU1.6 2DU2 2DU2.5 2DU3 2DU3.5 2DU4 2DU5 2DU6 2DU8 2DU10 2DU13 2DU16 2DU20 2DU25 2DU32 2DU40 2DU50 2DU60

2GU03 2GU05 2GU075 2GU1 2GU1.6 2GU2 2GU2.5 2GU3 2GU3.5 2GU4 2GU5 2GU6 2GU8 2GU10 2GU13 2GU16 2GU20 2GU25 2GU32 2GU40 2GU50 2GU60

2EU03 2EU05 2EU075 2EU1 2EU1.6 2EU2 2EU2.5 2EU3 2EU3.5 2EU4 2EU5 2EU6 2EU8 2EU10 2EU13 2EU16 2EU20 2EU25 2EU32 2EU40 2EU50 2EU60

2ZU03 2ZU05 2ZU075 2ZU1 2ZU1.6 2ZU2 2ZU2.5 2ZU3 2ZU3.5 2ZU4 2ZU5 2ZU6 2ZU8 2ZU10 2ZU13 2ZU16 2ZU20 2ZU25 2ZU32

300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300

5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5

3CU03 3CU05 3CU075 3CU1 3CU1.6 3CU2 3CU2.5 3CU3 3CU3.5 3CU4 3CU5 3CU6 3CU8 3CU10 3CU13 3CU16 3CU20 3CU25 3CU32 3CU40 3CU50 3CU60

3DU03 3DU05 3DU075 3DU1 3DU1.6 3DU2 3DU2.5 3DU3 3DU3.5 3DU4 3DU5 3DU6 3DU8 3DU10 3DU13 3DU16 3DU20 3DU25 3DU32 3DU40 3DU50 3DU60

3GU03 3GU05 3GU075 3GU1 3GU1.6 3GU2 3GU2.5 3GU3 3GU3.5 3GU4 3GU5 3GU6 3GU8 3GU10 3GU13 3GU16 3GU20 3GU25 3GU32 3GU40 3GU50 3GU60

3EU03 3EU05 3EU075 3EU1 3EU1.6 3EU2 3EU2.5 3EU3 3EU3.5 3EU4 3EU5 3EU6 3EU8 3EU10 3EU13 3EU16 3EU20 3EU25 3EU32 3EU40 3EU50 3EU60

3ZU03 3ZU05 3ZU075 3ZU1 3ZU1.6 3ZU2 3ZU2.5 3ZU3 3ZU3.5 3ZU4 3ZU5 3ZU6 3ZU8 3ZU10 3ZU13 3ZU16 3ZU20 3ZU25 3ZU32

450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450

4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

Triple-Pole 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 13 16 20 25 32 40 50 60

20

3BU6 3BU10 3BU13 3BU16 3BU20 3BU25 3BU32 3BU40 3BU50 3BU60



Miniature Circuit Breakers (MCB)

to UL 508 and CSA-22.2 Nr.14  B, C and D according to IEC 60898, EN 60898 and DIN VDE 0641 T11 Rated Current In A

B

C

Tripping Characteristic D G

E

Z

 Weight g/each

Packing units

600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Article No. Article No. Article No. Article No. Article No. Article No.

Triple-Pole with Switched Neutral 0,3 0,5 0,75 1 1,6 2 2,5 3 3,5 4 5 6 8 10 13 16 20 25 32 40 50 60

4BNU6 4BNU10 4BNU13 4BNU16 4BNU20 4BNU25 4BNU32 4BNU40 4BNU50 4BNU60

4CNU03 4CNU05 4CNU075 4CNU1 4CNU1.6 4CNU2 4CNU2.5 4CNU3 4CNU3.5 4CNU4 4CNU5 4CNU6 4CNU8 4CNU10 4CNU13 4CNU16 4CNU20 4CNU25 4CNU32 4CNU40 4CNU50 4CNU60

4DNU03 4DNU05 4DNU075 4DNU1 4DNU1.6 4DNU2 4DNU2.5 4DNU3 4DNU3.5 4DNU4 4DNU5 4DNU6 4DNU8 4DNU10 4DNU13 4DNU16 4DNU20 4DNU25 4DNU32 4DNU40 4DNU50 4DNU60

4GNU03 4GNU05 4GNU075 4GNU1 4GNU1.6 4GNU2 4GNU2.5 4GNU3 4GNU3.5 4GNU4 4GNU5 4GNU6 4GNU8 4GNU10 4GNU13 4GNU16 4GNU20 4GNU25 4GNU32 4GNU40 4GNU50 4GNU60

4ENU03 4ENU05 4ENU075 4ENU1 4ENU1.6 4ENU2 4ENU2.5 4ENU3 4ENU3.5 4ENU4 4ENU5 4ENU6 4ENU8 4ENU10 4ENU13 4ENU16 4ENU20 4ENU25 4ENU32 4ENU40 4ENU50 4ENU60

4ZNU03 4ZNU05 4ZNU075 4ZNU1 4ZNU1.6 4ZNU2 4ZNU2.5 4ZNU3 4ZNU3.5 4ZNU4 4ZNU5 4ZNU6 4ZNU8 4ZNU10 4ZNU13 4ZNU16 4ZNU20 4ZNU25 4ZNU32

21



Accessories 

for Miniature Circuit Breakers (MCB)

Auxiliary Contact Module Module

Type of Contact

Contacts

Article No.

Weight g/each

Packing units

1⁄ 2

2 auxiliary contact

1NC + 1NO

H11U

40

10

Technical Data H11U Regulations

Minimum Contact Load

To IEC 60947-5-1, EN 60947-5-1, DIN VDE 0600 T 200, UL 508 10 A / 230 V AC 3 A / 125 V DC 1 A / 250 V DC 1 mA at 24 V DC

Type of Conductors Single Wire Fine Wire Fine Wire with Ferrule Torque

Connectable Conductor Cross Sections min. max. 0,5 mm2 2,5 mm2 0,5 mm2 1,5 mm2 2 0,5 mm 1,5 mm2 Maximum 0,7 Nm

Contact Load H11U

Shunt Trip Module

Rated Operational Voltage

Max. Current Input at Rated Voltage (t