PORT COMMISSIONERS: CONSTANCE T. BACON DON MEYER DONALD C. JOHNSON RICHARD P. MARZANO CLARE PETRICH
DRAWING LIST
PORT STAFF:
SHEET #
SHEET TITLE
1
COVER SHEET
A1.1
2
SHED FLOOR PLAN
A1.2
3
SHED ELEVATION
M1.3
4
MECHANICAL SHED PLAN
EO.2
5
E4.1
6
ELECTRICAL LEGEND AND POWER RISER DIAGRAM SHED ELECTRICAL PLAN
JOHN WOLFE Chief Executive Officer DAKOTA CHAMBERLAIN Director of Facilities Development
SPECIAL INSPECTION 2215 North 30th Street,
Tacoma, WA 98403
SEATTLE 801SECONDAVENUES , TE700S , EATTLEW , A99104 TEL(2 :06)269-0104 wwwc.ardnoc.om
253.383.2422 TEL 253.383.2572 FAX
OF 6
Suite 300,
SH 1
STANLEY RYTER, PE Project Manager
CONSULTANTS:
G1.1
JANE VANDENBERG, PE Director of Engineering
REVISION
COVER SHEET
SHEET DESIGNATION G1.1
MAINTENANCE SHED HEATING
PROJECT LOCATION
6582
PORT OF TACOMA FILE: C:\Users\vecto\OneDrive\Vector\Clients\04-Cardno\Maintenance Mezzanine\CAD\Sheet Files\MID 101140.01 COVER_SHED
PROJECT NO. 101140.01 CONTRACT NO. 070735
THIS DRAWING IS THE PROPERTY OF THE PORT OF TACOMA AND SHALL NOT BE USED ON OTHER WORK, DISCLOSED, COPIED, IN WHOLE OR IN PART, WITHOUT WRITTEN PERMISSION
P.O. BOX 1837 TACOMA, WA 98401 (253)383-5841
BINDING EDGE
MAINTENANCE SHED HEATING
SH 2
OF 6
A1.1
6582
BINDING EDGE
P.O. BOX 1837 TACOMA, WA 98401 (253)383-5841
THIS DRAWING IS THE PROPERTY OF THE PORT OF TACOMA AND SHALL NOT BE USED ON OTHER WORK, DISCLOSED, COPIED, IN WHOLE OR IN PART, WITHOUT WRITTEN PERMISSION
SHED FLOOR PLAN
MAINTENANCE SHED HEATING
PORT OF TACOMA FILE: C:\Users\vecto\OneDrive\Vector\Clients\04-Cardno\Maintenance Mezzanine\CAD\Sheet Files\MID 101140.01 A1.1-A1.2_SHED
SH 3
OF 6
A1.2
6582
BINDING EDGE
P.O. BOX 1837 TACOMA, WA 98401 (253)383-5841
THIS DRAWING IS THE PROPERTY OF THE PORT OF TACOMA AND SHALL NOT BE USED ON OTHER WORK, DISCLOSED, COPIED, IN WHOLE OR IN PART, WITHOUT WRITTEN PERMISSION
SHED ELEVATION
MAINTENANCE SHED HEATING
PORT OF TACOMA FILE: C:\Users\vecto\OneDrive\Vector\Clients\04-Cardno\Maintenance Mezzanine\CAD\Sheet Files\MID 101140.01 A1.1-A1.2_SHED
P.O. BOX 1837 TACOMA, WA 98401 (253)383-5841
BINDING EDGE
CONSTRUCTION NOTES
UH 2
INSTALL UNIT HEATER PER MANUFACTURER RECOMMENDATIONS. INSTALL 8' ABOVE FINISHED FLOOR WHILE MAINTAINING REQUIRED CLEARANCES. SEE INSTALLATION DETAIL 2 ON THIS SHEET.
1
ELECTRIC UNIT HEATER SCHEDULE ELECTRICAL WATTS VOLTS Ø
UNIT NO
MANUFACTURER
MODEL
UH-1
INDEECO
UHIR
SHED
T'STAT
7500
480
UH-2
INDEECO
UHIR
SHED
T'STAT
7500
480
LOCATION INTERLOCK
STARTER FURN. BY
DISCONNECT FURN. BY
3
MFR
EC
1
2
3
4
3
MFR
EC
1
2
3
4
REMARKS
NOTES FOR UNIT HEATER SCHEDULE: 1 UNIT TO BE CONTROLLED WITH INTEGRAL 2-STAGE FACTORY-INSTALLED THERMOSTAT. SET POINT TO BE 55°F. 2 INSTALL PER MANUFACTURER INSTALLATION INSTRUCTIONS. PROVIDE WITH FACTORY DIRECTIONAL DIFFUSERS.
2017
3 INSTALL WITH ENGRAVED PLASTIC LAMINATE IDENTIFICATION NAMEPLATE PER 23 05 53.
WALL BRACKET
12/19/17
PROVIDE BASIS OF DESIGN MODEL OR APPROVED EQUAL. 12/19/17
4
12/15/
ONE SITCUM PLAZA TACOMA, WA 98401-1837
CC
DS
HEATER BRACKET
MOUNTING LOCATION TO BE COORDINATED WITH G.C.
2 M1.3
SCALE : NOT TO SCALE
3E 34 MLLW 19.18' @ Tide 22 1933 AS NOTED
MECHANICAL SHED PLAN SCALE : 1/8" = 1'-0"
0'
4'
8'
16'
32'
OF 6 SH # 4
SCALE: 1/8" = 1'-0"
M1.3
1 M1.3
ELECTRIC HEATER INSTALLATION DETAIL
21N WA83-SF 27
1
MECHANICAL SHED PLAN
UH 1
6582
PORT OF TACOMA FILE: R:\dwgs\217\217-054\_Drawings\Mechanical\217054_M1-3
MOUNTING HEIGHT 8' AFF TO BOTTOM OF UNIT
MAINTENANCE SHED HEATING
UNIT HEATER
THIS DRAWING IS THE PROPERTY OF THE PORT OF TACOMA AND SHALL NOT BE USED ON OTHER WORK, DISCLOSED, COPIED, IN WHOLE OR IN PART, WITHOUT WRITTEN PERMISSION
1
DEMAND CALCULATION EXISTING FUSED SWITCHBOARD #5 NEC 220-87 AND WAC 296-46B-010(16)(J) Phase to Phase Voltage(volts): Phases(1 = Single Phase, 3 = Three Phase):
480 3
Peak Demand 30-Day Meter Reading
=
Demand Adjustment Factor Per NEC 220-87(2)
x
Adjusted Peak Demand Added New Load Added load from the Bridge Crane Project New Added load from Shed Heater
220.78 kW 1.25
(
275.98 kVA 332.10 A)
+ +
30.75 kVA 15.00 kVA
Calculated Demand Load Calculated Demand Current Existing Switchboard Size
321.73 kVA 387 Amps 800 Amps
DEMAND CALCULATION EXISTING PANEL "A" NEC 220-87 AND WAC 296-46B-010(16)(J) 480 Phase to Phase Voltage(volts): 3 Phases(1 = Single Phase, 3 = Three Phase): = 91.88 kW Peak Demand 30-Day Meter Reading Demand Adjustment Factor Per NEC 220-87(2)
x (
1.25 114.85 kVA 138.21 A)
+ +
30.75 kVA 15.00 kVA
Adjusted Peak Demand Added New Load Added load from the Bridge Crane Project New Added load from Shed Heater
Calculated Demand Load Calculated Demand Current Existing Switchboard Size
160.60 kVA 193 Amps 400 Amps