Lighting Efficiency. input wattage guide

Information Sheet Lighting Efficiency input wattage guide Please use these wattages when calculating estimated wattage savings for Lighting Efficienc...
Author: Gerald Dorsey
126 downloads 0 Views 642KB Size
Information Sheet

Lighting Efficiency input wattage guide Please use these wattages when calculating estimated wattage savings for Lighting Efficiency rebates. These estimates figure electricity drawn by the system in an enclosed fixture and are taken from existing test data or calculated for similar lamp/ballast combinations. • This wattage guide is provided to estimate energy savings. Energy savings calculations are estimates and may vary from actual results. • Fixture wattages may vary slightly between different model numbers and manufacturers. The type of fixture and method of installation will affect the actual system wattage. • Lighting projects evaluated under the Custom Efficiency program may use the information contained in the Input Wattage Guide as a starting point; however, current policies or program rules that are in effect can cause adjustment to any of these values. Contents Page T12 Fluorescent Lamps

2

T12 U-bend Fluorescent Lamps

3

T10 Fluorescent Lamps

3

T8 Fluorescent Lamps

3

Super T8 System Input Wattage

3

T8 Fluorescent Parking Garage Lamps – High Efficiency Ballast

3

T5 Fluorescent Lamps

4

Compact Fluorescent Lightbulb (CFL)

5

Pin Based CFL Lamps

5

High Pressure Sodium Lamp

6

Canopy/Soffit High Pressure Sodium Lamp

6

High Pressure Sodium Lamp Wall Packs

6

Mercury Vapor Lamp

6

Canopy/Soffit Mercury Vapor Lamp

6

Mercury Vapor Lamp Wall Packs

6

Metal Halide Lamp

6

Canopy/Soffit Metal Halide Lamp

6

Metal Halide Wall Packs

6

Ceramic Metal Halide Lamp

7

Pulse Start Metal Halide Lamp

7

Canopy/Soffit Pulse Start Metal Halide Lamp

7

Pulse Start Metal Halide Wall Packs

7

Exit Signs

8

Low-Watt T8 Lamps

8

Page 1 of 8

13-11-407 | 11/2013 | CR# 0293

Input wattage guide

Lighting efficiency

T12 Fluorescent Lamps

Fluorescent Lamp Description F15T12 1.5' 15W F15T12 1.5' 15W F15T12 1.5' 15W F20T12 2' 20W F20T12 2' 20W F20T12 2' 20W F20T12 2' 20W F24T12 2' 35W HO F24T12 2' 35W HO F24T12 2' 35W HO F24T12 2' 35W HO F30T12 2.5' 42W HO F30T12 2.5' 42W HO F21T12 3' 21W F21T12 3' 21W F24T12 3' 24W F24T12 3' 24W F25T12 3' 25W F25T12 3' 25W F25T12 3' 25W F25T12 3' 25W F30T12 3' 25W F30T12 3' 25W F30T12 3' 25W F30T12 3' 25W F30T12 3' 30W F30T12 3' 30W F30T12 3' 30W F30T12 3' 30W F36T12 3' 30W SLIM F36T12 3' 30W SLIM F36T12 3' 50W HO F36T12 3' 50W HO F36T12 3' 50W HO F36T12 3' 50W HO F42T12 3.5' 35W SLIM F42T12 3.5' 35W SLIM F42T12 3.5' 50W HO F42T12 3.5' 50W HO F48T12 4' 30W F48T12 4' 30W F40T12 4' 34W F40T12 4' 34W F40T12 4' 34W F40T12 4' 34W F40T12 4' 40W F40T12 4' 40W F40T12 4' 40W F40T12 4' 40W F48T12 4' 40W F48T12 4' 40W F48T12 4' 60W HO F48T12 4' 60W HO F48T12 4' 60W HO F48T12 4' 60W HO Page 2 of 8

Number of Lamps 1 2 3 1 2 3 4 1 2 3 4 1 2 1 2 1 2 1 2 3 4 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 1 2 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4

Fixture Input Watts (for normal power ballasts) *Standard Energy Saving Magnetic Magnetic Electronic Ballast Ballast Ballast – 21 – – 41 – – 63 – – 21 – – 53 – – 64 – – 91 – – 64 – – 95 – – 148 – – 183 – – 67 – – 95 – – – 25 – – 49 – 45 – 65 – – 35 – – 71 – – 70 – – 88 – 40 28 – 64 50 – 103 80 – 125 – 40 30 – 75 60 – 113 90 – 138 – – 57 – – 83 – – 72 – – 110 – – 166 – – 212 – – 57 48 – 87 73 – 72 – – 126 – – 49 39 – 80 64 45 42 31 84 67 60 127 104 91 156 144 119 51 41 38 97 87 71 135 141 107 175 172 134 – 62 53 – 98 82 – 82 62 – 133 125 – 204 – – 263 –

Fluorescent Lamp Description F48T12 4' 116W HO F48T12 4' 116W HO F48T12 4' 116W HO F60T12 5' 138W HO F60T12 5' 138W HO F60T12 5' 50W F60T12 5' 50W F60T12 5' 75W HO F60T12 5' 75W HO F60T12 5' 75W HO F60T12 5' 75W HO F64T12 64" 80W HO F64T12 64" 80W HO F64T12 64" 80W HO F64T12 64" 80W HO F72T12 6' 168W HO F72T12 6' 168W HO F72T12 6' 168W HO F72T12 6' 57W F72T12 6' 57W F72T12 6' 85W HO F72T12 6' 85W HO F72T12 6' 85W HO F72T12 6' 85W HO F84T12 7' 65W F84T12 7' 65W F84T12 7' 100W HO F84T12 7' 100W HO F84T12 7' 100W HO F96T12 8' 60W F96T12 8' 60W F96T12 8' 60W F96T12 8' 75W F96T12 8' 75W F96T12 8' 95W HO F96T12 8' 95W HO F96T12 8' 110W HO F96T12 8' 110W HO F95T12 8' 185W HO F95T12 8' 185W HO F95T12 8' 185W HO F95T12 8' 215W HO F95T12 8' 215W HO F95T12 8' 215W HO F96T12 8' 110W HO F96T12 8' 110W HO F95T12 8' 185W HO F95T12 8' 185W HO F95T12 8' 185W HO F95T12 8' 215W HO F95T12 8' 215W HO F95T12 8' 215W HO

Number of Lamps 1 2 3 1 2 1 2 1 2 3 4 1 2 3 4 1 2 3 1 2 1 2 3 4 1 2 1 2 3 1 2 4 1 2 1 2 1 2 1 2 3 1 2 3 1 2 1 2 3 1 2 3

Fixture Input Watts (for normal power ballasts) *Standard Energy Saving Magnetic Magnetic Electronic Ballast Ballast Ballast – 130 – – 230 – – 329 – – 140 – – 241 – – 72 64 – 111 103 – 98 – – 163 145 – 223 – – 278 243 – 104 – – 178 141 – 246 – – 312 – – 169 – – 314 – – 424 – – 80 67 – 122 106 – 106 – – 190 164 – 291 225 – 323 – – 89 75 – 143 120 – 113 – – 209 190 – 278 – – 74 67 – 113 105 – 246 – – 94 84 145 145 133 125 120 – 216 203 170 140 121 119 258 238 205 – 198 – – 398 – – 550 – – 213 – – 320 – – 518 – 140 121 119 258 238 205 – 198 – – 398 – – 550 – – 213 – – 320 – – 519 –

*Standard Magnetic ballasts that don't comply with Public Law 100-357 of 1988. These ballasts were no longer manufactured after January 1, 1990. In a custom analysis utilizing T12’s, a T8 baseline will be assumed. 13-11-407 | 11/2013 | CR# 0293

Input wattage guide

Lighting efficiency

T12 U-bend Fluorescent Lamps

T8 Fluorescent Lamps

Fixture Input Watts (for normal power ballasts) Standard Standard Efficiency, Efficiency, Standard Energy Energy Fluorescent Number Efficiency, Saving Saving Lamp of Electronic Magnetic Magnetic Description Lamps Ballast Ballast Ballast

Fixture Input Watts Standard Ballast Type High Efficiency Ballast High Normal Low High Normal Low Number Energy Ballast Ballast Ballast Ballast Ballast Ballast Fluorescent of Factor Factor Factor Factor Factor Factor Saving Lamp Description Lamps Magnetic Electronic Electronic Electronic Electronic Electronic Electronic F13T8 1' 13W 1 17 – – – – – – F13T8 1' 13W 2 36 – – – – – – F15T8 1.5' 15W 1 20 – – – – – – F15T8 1.5' 15W 2 41 – – – – – – F17T8 2' 17W 1 24 – 18 – 13 15 20 F17T8 2' 17W 2 45 – 31 – 27 30 39 F17T8 2' 17W 3 64 – 45 – 40 45 59 F17T8 2' 17W 4 83 – 57 – 53 60 78 F25T8 3' 25W 1 30 – 24 – 20 22 29 F25T8 3' 25W 2 62 – 43 – 39 44 58 F25T8 3' 25W 3 87 – 63 – 63 72 86 F25T8 3' 25W 4 116 – 85 – 85 74 111 F25T8 4' 25W 1 – – 26 – 20 22 29 F25T8 4' 25W 2 – – 43 – 39 44 58 F25T8 4' 25W 3 – – 63 – 59 66 94 F25T8 4' 25W 4 – – 85 – 78 88 115 F28T8 4' 28W 1 – – 25 – 22 25 32 F28T8 4' 28W 2 – – 48 – 44 49 64 F28T8 4' 28W 3 – – 72 – 66 74 97 F28T8 4' 28W 4 – – 97 – 87 99 129 F30T8 4' 30W ES 1 40 – 31 – – – – F30T8 4' 30W ES 2 82 – 54 – – – – F30T8 4' 30W ES 3 – – 77 – – – – F30T8 4' 30W ES 4 – – 104 – – – – F32T8 4' 32W 1 35 – 32 – 25 28 37 F32T8 4' 32W 2 68 52 59 77 50 56 74 F32T8 4' 32W 3 100 78 88 115 75 84 110 F32T8 4' 32W 4 131 104 117 153 100 113 147 F32T8 4' 32W 6 – – – – 150 169 221 F32T8 4' 32W 8 – – – – 200 225 294 F32T8 4' 32W 12 – – – – 300 338 442 F32T8 4' 32W 14 – – – – 349 394 515 F32T8 4' 32W 16 – – – – 399 451 589 F32T8 4' 32W 18 – – – – 449 507 662 F32T8 4' 32W 20 – – – – 499 563 736 F32T8 4' 32W VHLO 3 – – – – – 279 – F32T8 4' 32W VHLO 5 – – – – – 465 – F32T8 4' 32W VHLO 6 – – – – – 555 – F32T8 4' 32W VHLO 8 – – – – 793 – F36T8 4' 36W 2 – – 74 – – – – F48T8 HO 4' 44W 1 – – 59 – – – – F48T8 HO 4' 44W 2 120 – 98 – – – – F40T8 5' 40W 1 50 – 39 – – – – F40T8 5' 40W 2 86 – 75 – – – – F40T8 5' 40W 3 131 – 107 – – – – F40T8 5' 40W 4 171 – 116 – – – – F60T8 HO 5' 55W 1 – – 70 – – – – F60T8 HO 5' 55W 2 126 – 118 – – – – F72T8 6' 46W 1 52 – 50 – – – – F72T8 6' 46W 2 97 – 88 – – – – F96T8 8' 59W ES 1 – – 64 – 47 52 68 F96T8 8' 59W ES 2 – – 104 – 94 104 136 F72T8 6' 66W HO 1 – – 81 – – – – F72T8 6' 66W HO 2 150 – 135 – – – – F96T8 8' 86W HO 1 – – 100 – – – – F96T8 8' 86W HO 2 – – 160 – – – – F96T8 8' 96W 1 – – – – 47 52 68 F96T8 8' 96W 2 – – – – 94 104 136

FT12 4' 34W

2

60

67

84

FT12 4' 40W

2

71

87

97

T10 Fluorescent Lamps

Fluorescent Lamp Description

Fixture Input Watts (for normal power ballasts) Energy Saving Number of Magnetic Electronic Lamps Ballast Ballast

F40T10 4' 40W

1

54

41

F40T10 4' 40W

2

88

72

F40T10 4' 40W

3

141

112

Super T8 System Input Wattage Instant Start Ballast

Rapid Start Ballast

Low Ballast factor (0.77)

Normal Ballast factor (0.87)

High Ballast factor (1.15)

Low Ballast factor (0.71)

Low Ballast factor (0.77)

Normal Ballast factor (0.88)

1 Lamp

25

28

38

25



31

2 Lamps

48

55

74

47

48

60

3 Lamps

71

82

110

73

74

88

4 Lamps

95

108

144

93

98

118

T8 Fluorescent Parking Garage Lamps — High Efficiency Ballast T8 Fluorescent Parking Low Normal High Garage Number Ballast Ballast Ballast Lamps of Factor Factor Factor Description Lamps Electronic Electronic Electronic FT8 4' 32W

2

50

56

74

FT8 4' 32W

3

48

84

110

Page 3 of 8

13-11-407 | 11/2013 | CR# 0293

Input wattage guide

Lighting efficiency

T5 Fluorescent Lamps Fixture Input Watts (for normal power ballasts)

Fixture Input Watts (for normal power ballasts)

Fluorescent Lamp Description

Number of Lamps

Energy Saving Magnetic Ballast

Electronic Ballast

Fluorescent Lamp Description

Number of Lamps

Energy Saving Magnetic Ballast

Electronic Ballast

F4T5 6'' 4W

1

9



F28T5 4' 28W

1



32

F4T5 6'' 4W

2

20



F28T5 4' 28W

2



63

F6T5 9'' 6W

1

10



F28T5 4' 28W

3



95

F6T5 9'' 6W

2

21



F28T5 4' 28W

4



126

F8T5 1' 8W

1

14

10

F35T5 5' 35W

1



40

F8T5 1' 8W

2

23

21

535T5 5' 35W

2



77

F13T5 2' 13W

1

13

14

F54T5HO 4' 54W

1



62

F13T5 2' 13W

2

26

27

F54T5HO 4' 54W

2



117

F14T5 2' 14W

1



14

F54T5H0 4' 54W

3



179

F14T5 2' 14W

2



28

F54T5HO 4' 54W

4



234

F24T5 HO 2' 24W

1



27

F54T5H0 4' 54W

5



295

F24T5 HO 2' 24W

2



54

F54T5H0 4' 54W

6



358

F21T5 3' 21W

1



25

F54T5H0 4' 54W

8



468

F21T5 3' 21W

2



49

F54T5H0 4' 54W

10



468

F39T5HO 3' 39W

1



42

F39T5HO 3' 39W

1



40

F39T5HO 3' 39W

2



85

F39T5HO 3' 39W

2



77

F80T5HO 5' 80W

1



89

Page 4 of 8

13-11-407 | 11/2013 | CR# 0293

Input wattage guide

Lighting efficiency

COMPACT FLUORESCENT LIGHT BULB Fixture Input Watts (for normal power ballasts) Compact Fluorescent Number of Energy Saving Electronic Wattage Lamps Magnetic Ballast Ballast

Fixture Input Watts (for normal power ballasts) Compact Fluorescent Number of Energy Saving Electronic Wattage Lamps Magnetic Ballast Ballast

Fixture Input Watts (for normal power ballasts) Compact Fluorescent Number of Energy Saving Electronic Wattage Lamps Magnetic Ballast Ballast

1

1

1

1

35

1

46

37

69

1

90

73

2

1

3

2

36

1

47

38

70

1

91

74

3

1

4

3

37

1

48

39

71

1

93

75

4

1

5

4

38

1

50

40

72

1

94

76

5

1

7

5

39

1

51

41

73

1

95

77

6

1

8

6

40

1

52

42

74

1

97

78

7

1

9

7

41

1

54

43

75

1

98

79

8

1

10

8

42

1

55

44

76

1

99

80

9

1

12

10

43

1

56

45

77

1

101

81

10

1

13

11

44

1

57

47

78

1

102

83

11

1

14

12

45

1

59

48

79

1

103

84

12

1

16

13

46

1

60

49

80

1

104

85

13

1

17

14

47

1

61

50

81

1

106

86

14

1

18

15

48

1

63

51

82

1

107

87

15

1

20

16

49

1

64

52

83

1

108

88

16

1

21

17

50

1

65

53

84

1

110

89

17

1

22

18

51

1

67

54

85

1

111

90

18

1

24

19

52

1

68

55

86

1

112

91

19

1

25

20

53

1

69

56

87

1

114

92

20

1

26

21

54

1

71

57

88

1

115

93

21

1

27

22

55

1

72

58

89

1

116

94

22

1

29

23

56

1

73

59

90

1

118

95

23

1

30

24

57

1

74

60

91

1

119

96

24

1

31

25

58

1

76

61

92

1

120

97

25

1

33

26

59

1

77

62

93

1

121

98

26

1

34

28

60

1

78

63

94

1

123

99

27

1

35

29

61

1

80

65

95

1

124

101

28

1

37

30

62

1

81

66

96

1

125

102

29

1

38

31

63

1

82

67

97

1

127

103

30

1

39

32

64

1

84

68

98

1

128

104

31

1

40

33

65

1

85

69

99

1

129

105

100

1

131

106

32

1

42

34

66

1

86

70

33

1

43

35

67

1

88

71

34

1

44

36

68

1

89

72

Pin Based CFL Lamps Number of Lamps

Standard Efficiency, Magnetic Ballast

High Efficiency, Electronic Ballast

32

2

68

68

38

2

74

74

42

2

93

93

Compact Fluorescent Wattage

Page 5 of 8

13-11-407 | 11/2013 | CR# 0293

Input wattage guide

Lighting efficiency

High Pressure Sodium Lamp

Mercury Vapor Lamp

Metal Halide Lamp

Compact Fluorescent Wattage

Number of Lamps

High Efficiency, Electronic Ballast

35W Med. Base

1

43

75W Med. Base

1

75

35W/39W Med. Base

1

48

50W Med. Base

1

64

100W Med. Base

1

122

50W Med. Base

1

62

70W Med. Base

1

86

175W Med. Base

1

205

70W Med. Base

1

93

1

205

70W Double Ended

1

94

Mercury Vapor Lamp Description

Number of Lamps

Magnetic Ballast

Metal Halide Lamp Description

Number of Lamps

Magnetic Ballast

50W Med. Base

1

75

32W Med. Base

1

38

70W Med. Base

1

126

175W Mogul Base

100W Mogul Base

1

130

250W Mogul Base

1

285

100W Med. Base

1

125

150W Med. Base

1

188

400W Mogul Base

1

454

100W Double Ended

1

130

150W Mogul Base

1

188

400W Mogul Base

1

880

175W Mogul Base

1

210

1,000W Mogul Base

1

1,080

150W Med. Base

1

173

150W Double Ended

1

185

250W Mogul Base

1

295

400W Mogul Base

1

456

400W Mogul Base

1

890

200W Mogul Base

1

240

250W Mogul Base

1

295

310W Mogul Base

1

365

400W Mogul Base

1

457

Canopy/Soffit Mercury Vapor Lamp

600W Mogul Base

1

665

Canopy/Soffit Mercury Vapor Lamp Description

750W Mogul Base

1

840

100 Watt

1

122

1000W Mogul Base

1

1,080

1000W Mogul Base

1

1,100

175 Watt

1

205

1500W Mogul Base

1

1,610

250 Watt

1

285

1650W Mogul Base

1

1,765

454

2000W Mogul Base

1

2,140

Canopy/Soffit High Pressure Sodium Lamp Canopy/Soffit High Pressure Sodium Lamp Description

Number of Lamps

Magnetic Ballast

100 Watt

1

130

150 Watt

1

188

200 Watt

1

240

250 Watt

1

295

310 Watt

1

365

400 Watt

1

457

High Pressure Sodium Lamp Wall Packs

400 Watt

Number of Lamps

Magnetic Ballast

1

Mercury Vapor Lamp Wall Packs

Canopy/Soffit Metal Halide Lamp Canopy/Soffit Metal Halide Lamp Description

Number of Lamps

Magnetic Ballast

75

100 Watt

1

125

1

185

Mercury Vapor Lamp Wall Packs Description

Number of Lamps

Magnetic Ballast

50 Watt

1

75 Watt

1

95

150 Watt

100 Watt

1

120

175 Watt

1

210

175 Watt

1

205

250 Watt

1

295

250 Watt

1

285

400 Watt

1

454

400 Watt

1

454

Metal Halide Wall Packs Metal Halide Wall Packs Description

Number of Lamps

Magnetic Ballast

High Pressure Sodium Lamp Wall Packs Description

Number of Lamps

Magnetic Ballast

35 Watt

1

48

50 Watt

1

62

35 Watt

1

43

70 Watt

1

93

50 Watt

1

64

100 Watt

1

125

70 Watt

1

86

150 Watt

1

173

100 Watt

1

126

175 Watt

1

210

150 Watt

1

188

250 Watt

1

295

200 Watt

1

240

400 Watt

1

454

250 Watt

1

295

310 Watt

1

365

400 Watt

1

457

Page 6 of 8

13-11-407 | 11/2013 | CR# 0293

Input wattage guide

Lighting efficiency

Ceramic Metal Halide Lamp

Pulse-Start Metal Halide Lamp Energy Number Saving Pulse Start Metal Halide of Magnetic Magnetic Lamp Description Lamps Ballast Ballast

Ceramic Metal Halide Lamp Description

Number of Lamps

Magnetic Ballast

Energy Saving Magnetic Ballast

Electronic Ballast

20W Integrated

1





20

25W Integrated

1





25

50W Med. Base

1

39W

1





45

70W Med/Mogul Base

1

90

85

50W Lamp with a Med Base

1

72

62

50

100W Med/Mogul Base

1

128

118

70W Lamp with a Med/Mog Base

1

90

85

70

125W Med/Mogul Base

1

150

141

100W Lamp with a Med/Mog Base

1

128

118



150W Med/Mogul Base

1

189

173

125W Lamp with a Med/Mog Base

1

150

141



175W Med/Mogul Base

1

208

189

150W Lamp

1

189

167

168

200W Med/Mogul Base

1

232

218

175W Lamp

1

191

189

250W Med/Mogul Base

1

290

272

200W Lamp

1

232





320W Med/Mogul Base

1

370

342

200W Lamp with a Med/Mog Base

1

218





350W Med/Mogul Base

1

410

375

250W Lamp

1

272



275

400W Med/Mogul Base

1

465

425

320W Lamp

1

342

367

349

450W Med/Mogul Base

1

506

480

350W Lamp

1

410

375

380

750W Med/Mogul Base

1

812



360W Lamp

1

418





1000W Med/Mogul Base

1

1080



400W Lamp with a Med/Mog Base

1



425

435

450W Lamp with a Med/Mog Base

1

506

480



750W Lamp

1



814



1000W Lamp

1



1080



Canopy/Soffit Pulse Start Metal Halide Lamp Canopy/ Soffit Pulse Start Metal Halide Lamp Description

Energy Saving Number of Magnetic Magnetic Lamps Ballast Ballast

100 Watt

1

118

128

125 Watt

1

141

150

150 Watt

1

173

189

175 Watt

1

189

208

200 Watt

1

218

232

250 Watt

1

272

290

320 Watt

1

342

370

350 Watt

1

375

410

400 Watt

1

425

465

450 Watt

1

480

506

Page 7 of 8

72

62

Pulse-Start Metal Halide Wall Packs Fixture Input Watts (for normal power ballasts) Pulse Start Metal Halide Energy Saving Wall Packs Number Magnetic Magnetic Description of Lamps Ballast Ballast

Pulse Start Metal Halide Energy Saving Wall Packs Number Magnetic Magnetic Description of Lamps Ballast Ballast

50 Watt

1

62

72

200 Watt

1

218

232

70 Watt

1

85

90

250 Watt

1

272

290

100 Watt

1

118

128

320 Watt

1

342

370

125 Watt

1

141

150

350 Watt

1

375

410

150 Watt

1

173

189

400 Watt

1

425

465

175 Watt

1

189

208

450 Watt

1

480

506

13-11-407 | 11/2013 | CR# 0293

Input wattage guide

Lighting efficiency

Exit Signs

Low-Watt T8 Lamps

Exit Sign Description

Watts

30W Incandescent Exit Sign

30

40W Incandescent Exit Sign

40

LEC Exit Sign

0.25

LED Exit Sign

2

Low-Watt Lamp Descriptor

Low Ballast Normal Ballast High Ballast Factor Electronic Factor Electronic Factor Electronic

F32T8 25W Lamp

20

22

29

F32T8 28W Lamp

22

25

32

F32T8 32W Lamp

25

28

37

xcelenergy.com | © 2013 Xcel Energy Inc. | Xcel Energy is a registered trademark of Xcel Energy Inc. | Northern States Power Company-Minnesota, Public Service Company of Colorado and Southwestern Public Service Company, Xcel Energy Companies. 13-11-407 | 11/13 | CRS# 0293