63249-420-352A1 04/2011
Installation Bulletin
Lighting Control Relay Panels LPS Standalone Lighting Control Relay Panel LPB Lighting Control Relay Panel with Native BACnet Protocol LPL Lighting Control Relay Panel with the LonWorks® Protocol INTRODUCTION This bulletin contains instructions for mounting the LPS Standalone Lighting Control Relay Panel, the LPB Lighting Control Relay Panel with the native BACnet protocol, and the LPL Lighting Control Relay Panel with the LonWorks® protocol.
SAFETY PRECAUTIONS This section contains important safety precautions that must be followed before attempting to install or maintain electrical equipment. Carefully read and follow the safety precautions below.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
This equipment must be installed and serviced by qualified electrical personnel.
Turn off all electrical power supplying this equipment before working on or inside the equipment.
Always use a properly rated voltage sensing device to confirm that power is off.
Replace all devices, doors, and covers before turning on power to this equipment. Failure to follow these instructions will result in death or serious injury.
© 2011 Schneider Electric. All Rights Reserved.
Lighting Control Relay Panels Installation Bulletin
63249-420-352A1 04/2011
DESCRIPTION All relay panels include the following: Enclosure Cover Interior assembly The interior assembly can include the following depending on the options selected: Figure 1: Relay Panel Description KEY: A. B. C. D. E. F. G.
TOP VIEW
Class 1 wiring section with cover plate Control relays (one or two poles) Low voltage (Class 2) section Control transformer Electronic control card and devices Mounting holes Knockouts
G
NOTE: Keep Class 1 and Class 2 wiring separated.
SIDE VIEW
FRONT VIEW WITHOUT DOOR
F
A
W I R I N G
B
D U C T
C D
G
1
W I R I N G
9
2
10
3
11
4
12
5
13
6
14
7
1
15
8
16
4
RUN
RUN
PROGRAM
ON
OFF
OPTIONS
ON ONLY
PGM
OFF ONLY
GROUP SELECT
KC-411
2 5
3 6
7
8
9
CLEAR
0
ENTER
E
24 Vac L
N
Ry Sw Sw Sw
1
2
3
4
COM
D U C T 1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16
RUN
PROGRAM
ON
OFF
OPTIONS
ON ONLY
OFF ONLY
GROUP SELECT
24 Vac L
F
N
Ry Sw Sw Sw
1
2
3
4
COM
BOTTOM VIEW
G
2
© 2011 Schneider Electric. All Rights Reserved.
63249-420-352A1 04/2011
Lighting Control Relay Panels Installation Bulletin
DIMENSIONS Figure 2: 8 Relays SIDE VIEW
FRONT VIEW WITHOUT DOOR
TOP VIEW 149 (5.9)
42 (1.7)
90 (3.5)
149 (5.9) 46 (1.8)
101 (4)
1
W I R I N G
2 3 4
101 (4)
1
9
2
10
3
11
4
12
5
13
6
381 (15)
14
7
15
8
D U C T
345 (13.6)
16
RUN
PROGRAM
ON
OFF
OPTIONS
ON ONLY
OFF ONLY
mm (in.)
GROUP SELECT
24 Vac L
N
1
Ry Sw Sw Sw
2
3
4
COM
90 (3.5) 330 (13)
46 (1.8) 101 (4)
381 (15)
Figure 3: 16 Relays SIDE VIEW
FRONT VIEW WITHOUT DOOR
TOP VIEW 42 (1.7)
94 (3.7)
149 (5.9)
149 (5.9) 46 (1.8)
101 (4) 1
kameleon
K4
2 KC-411
3
1
4
101 (4)
6 7 8
101 (4)
RUN
D U C T
9 10 11
6
8
9
0
ENTER
556 (21.9)
1
3 4
9
12 13 14
7
15
8
15
mm (in.)
11
KC - 401
6
13
592 (23.3)
10
Kameleon
5
14
94 (3.7)
3
5
7 CLEAR
PGM
2
12
101 (4)
2
4
W I R I N G
5
16
RUN
PROGRAM
ON
OFF
OPTIONS
ON ONLY
OFF ONLY
GROUP SELECT
24 Vac L
N
Ry Sw Sw Sw
1
2
3
4
COM
16
46 (1.8)
330 (13) 101 (4)
381 (15)
© 2011 Schneider Electric. All Rights Reserved.
3
Lighting Control Relay Panels Installation Bulletin
63249-420-352A1 04/2011
Figure 4: 32 Relays SIDE VIEW
FRONT VIEW WITHOUT DOOR
TOP VIEW 194 (7.6)
60 (2.4)
55 (2.2)
60 (2.4)
27.87 (1.10)
W I R I N G
190 (7.5)
194 (7.6)
55 (2.2)
D U C T
mm (in.) 850 (33.5)
360 (14) W I R I N G
RUN
D U C T
1
2
4
5
7
8
9
CLEAR
0
ENTER
PGM
3 6
1
9
2
10
3
11
12
4
12
13
5
13
6
14
6
14
7
15
7
15
16
RUN
PROGRAM
ON
OFF
OPTIONS
ON ONLY
N
8
OFF ONLY
GROUP SELECT
24 Vac L
9
10 11
4 5
8
190 (7.5)
1
2 3
16
RUN
PROGRAM
ON
OFF
OPTIONS
ON ONLY
OFF ONLY
GROUP SELECT
24 Vac Ry Sw Sw Sw
1
2
3
4
COM
L
N
Ry Sw Sw Sw
1
2
3
4
COM
27.05 (1.08) 55 (2.2) 55 (2.2)
406.8 (16) 101.6 (4)
4
508 (20)
© 2011 Schneider Electric. All Rights Reserved.
63249-420-352A1 04/2011
Lighting Control Relay Panels Installation Bulletin
Figure 5: 64 Relays SIDE VIEW
FRONT VIEW WITHOUT DOOR
TOP VIEW 194 (7.6)
60 (2.4)
55 (2.2) 27.87 (1.10)
194 (7.6)
60 (2.4)
55 (2.2)
380 (15)
mm (in.)
1250 (49.2)
380 (15)
1 2 3 4
Kameleon
5
KC - 401
6
9
1
10
2
11
3
12
4
13
5
14
7
PROGRAM
ON
OFF
OPTIONS
ON ONLY
N
380 (15)
1
2
3
4
ON
OFF
COM
L
N
ON ONLY
OFF ONLY
GROUP SELECT
1
Ry Sw Sw Sw
2
3
4
COM
K4
11 12
KC-411
13
KC - 401
6
14
7
15
8
16
RUN
ON
16
OPTIONS
kameleon
9 10
Kameleon
5
RUN
15
PROGRAM
24 Vac Ry Sw Sw Sw
2
4
14
8
RUN
GROUP SELECT
1
3
13
7
16
OFF ONLY
24 Vac L
11 12
KC - 401
6
15
8
RUN
9 10
Kameleon
PROGRAM
OPTIONS
OFF
ON ONLY
OFF ONLY
PGM
1
2
4
5
7
8
9
CLEAR
0
ENTER
3 6
GROUP SELECT
24 Vac L
N
Ry Sw Sw Sw
1
2
3
4
COM
27.05 (1.08) 55 (2.2) 406.8 (16)
55 (2.2) 101 (4)
© 2011 Schneider Electric. All Rights Reserved.
508 (20)
5
Lighting Control Relay Panels Installation Bulletin
63249-420-352A1 04/2011
INSTALLATION Remove the Interior Assembly It is recommended that the interior assembly be removed from the relay panel before mounting the relay panel. To remove the interior assembly, do the following: 1. Unscrew the screws securing the Class 1 wiring cover plate(s) to the relay panel. 2. Remove the Class 1 wiring cover plate(s) to reveal the screws securing the interior assembly to the relay panel. 3. Unscrew the screws securing the interior assembly to the relay panel. 4. Remove the interior assembly from the relay panel. 5. Proceed to the mounting instructions for the relay panel.
Mounting the 8 or 16 Relay Capacity Panels 1. Turn off all power supplying this equipment before working inside the relay panel 2. Use a properly rated voltage sensing device to confirm that power is off, and follow all lockout/tagout procedures. 3. Remove the appropriate knockouts for the wiring. 4. Position the relay panel in the location it will be mounted. 5. Screw the mounting bolts through the mounting holes and into the wall. 6. Attach the interior assembly to the inside of the relay panel using the screws and washers removed in Remove the Interior Assembly on page 6. 7. Attach the supply line voltage to the relay panel.
SUPPLY LINE VOLTAGE MUST MATCH POWER SUPPLY The relay panel power supply has several options allowing it to operate with 115 VAC, 240 VAC, 277 VAC, or 347 VAC line voltage. Wire only to one of these terminals. Failure to follow these instructions can damage the power supply and relay panel and void the product warranty.
NOTE: The Class 2 control transformers with either 50 or 60 Hz have internal over-current protection. 8. Replace the Class 1 wiring cover plate(s) to the interior assembly.
6
© 2011 Schneider Electric. All Rights Reserved.
63249-420-352A1 04/2011
Lighting Control Relay Panels Installation Bulletin
Mounting the 32 or 64 Relay Capacity Panels 1. Turn off all power supplying this equipment before working inside the relay panel 2. Use a properly rated voltage sensing device to confirm that power is off, and follow all lockout/tagout procedures. 3. Remove the appropriate knockouts for the wiring. 4. Use the relay panel dimensions drawing as a reference for measuring the correct distance between the two keyhole mounting slots. 5. Screw the mounting bolts into the wall based on your measurements in step 3. 6. Align the keyhole mounting slots on the back of the relay panel to the bolts in the wall. 7. Slide the relay panel down to secure it to the mounting bolts. 8. Attach the interior assembly onto the inside of the relay panel using the screws and washers removed in Remove the Interior Assembly on page 6. 9. Attach the supply line voltage to the relay panel.
SUPPLY LINE VOLTAGE MUST MATCH POWER SUPPLY The relay panel power supply has several options allowing it to operate with 115 VAC, 240 VAC, 277 VAC, or 347 VAC line voltage. Wire only to one of these terminals. Failure to follow these instructions can damage the power supply and relay panel and void the product warranty.
NOTE: The Class 2 control transformers with either 50 or 60 Hz have internal over-current protection. 10. Replace the Class 1 wiring cover plate(s) to the interior assembly.
© 2011 Schneider Electric. All Rights Reserved.
7
Lighting Control Relay Panels Installation Bulletin
63249-420-352A1 04/2011
Wiring Connect Load and Line Voltage to Relays Before making any connections to the relays, perform continuity tests to verify load circuits are not shorted. 1. Wire the conductors from the circuit breaker through each relay's output terminals and then from the relay terminals to the loads. 2. Torque each relay load terminal to the value specified on the relay. Figure 6: HID Relay Description Manual ON/OFF Switch and ON/OFF Indicator
Low Voltage Terminal (Blue Screw)
Load Terminals
Low Voltage Terminal (Red Screw)
Manual ON/OFF Switch and ON/OFF Indicator
Low Voltage Terminal (Blue Screw)
Load Terminals
Low Voltage Terminal (Red Screw) Low Voltage Terminal (Blue Screw)
Load Terminals
Low Voltage Terminal (Red Screw)
Figure 7: Relay Wiring
H Circuit Breaker
H Tr 24V
White Circuit Breaker
Blue
Relays
Tr 24V
White Blue
Relays Switches
Switches Red
Red Lights Lights
Limit of six (6) switches per relay
8
Limit of four (4) per switch.
© 2011 Schneider Electric. All Rights Reserved.
63249-420-352A1 04/2011
Lighting Control Relay Panels Installation Bulletin
Low Voltage (Class 2) Wiring The low voltage (Class 2) wiring section of the relay panel provides terminal connections for a variety of optional switches and other devices. Individual relays can be controlled from a switch or sensor that is hardwired to the corresponding connector on the relay controller card. More than one relay can be grouped into a group channel on the relay controller card and controlled from a single switch or sensor. Up to eight groups are supported with a single relay controller card.
Field Programmable Control Cards Field programmable relay panels have the SERPTC411 controller card installed. The figures below show typical wiring configurations for the SERPTC411. Figure 8: Typical Wiring for the Time Controller
R4 R3 R2 R1
OFF OFF OFF OFF
Green Yellow
OFF
R5
Blue
Orange
OFF
R6
Purple
Red
OFF
R7
Gray
Brown
OFF
R8
04:58:25
1 2
30 Sep 2011 1 2 3 4 5 6 7 8
TRANSFORMER T1 277, 120/24V Local Switch If Used IRDA
RUN
24 VacGND L
N
PGM
2
3
4
5
6
7
8
9
CLEAR
0
ENTER
PHOTOCELL SUPPLY
INPUT RY SW 1
1
2
+
+
+
-
+
-
COM
Black White White Dashed line to be used by authorized electrical personnel.
3-wire 2-wire Device Device Low Voltage Switch If Used
© 2011 Schneider Electric. All Rights Reserved.
9
Lighting Control Relay Panels Installation Bulletin
63249-420-352A1 04/2011
Figure 9: Typical Wiring for the Time Controller with a Relay Controller
Orange
White + Orange
Red
White + Yellow
Brown
White + Green
1
9
2
10
3
11
OFF OFF
4
TRANSFORMER T1 277, 120/24V Local Switch If Used
12
SERPTC411
5
SERPRC401
13
8 CHANNEL TIME CLOCK/RELAY CONTROLLER
6
16 RELAY CONTROLLER
14
7
15
8
16
IRDA
RUN
RUN
PROGRAM
ON
OFF
OPTIONS
ON ONLY
OFF ONLY
GROUP SELECT 24 VacGND
24 Vac GND L
N
Ry Sw Sw Sw
PGM
1
2
3
4
COM
L
N
2
3
4
5
6
7
8
9
CLEAR
0
ENTER
R11 R12 R13 R14 R15 R16 R17 R18
PHOTOCELL SUPPLY
INPUT RY SW 1
1
OFF
White + Red
OFF
Yellow
OFF
White + Brown
OFF
Green
R10
OFF
White + Black
OFF
Blue
R9
OFF
Black
OFF
Purple
OFF
R1
White
OFF
R2
Gray
OFF
R3
OFF
R4
OFF
R5
OFF
R6
OFF
R7
OFF
White
R8
2
+
+
+
-
+
-
COM
Black Black White White White Dashed line to be used by authorized electrical personnel. Low Voltage Switch If Used
10
Low Voltage Switch If Used
© 2011 Schneider Electric. All Rights Reserved.
63249-420-352A1 04/2011
Lighting Control Relay Panels Installation Bulletin
Power and Test Relays HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
Do NOT apply power to the controlled circuit loads while testing the relays.
This equipment must be installed and serviced by qualified electrical personnel. Failure to follow these instructions will result in death or serious injury.
Do NOT apply power to the controlled circuit loads while testing the relays. 1. Apply power to the lighting control panel's control transformer only (see Description on page 2). 2. Locate the manual relay control devices on the relay. Activate the manual relay control devices by switching the relay switch ON and OFF. The relay will click and change state. The activator device will change from yellow to red. 3. Confirm the operation of each relay. 4. If all relays work as intended, apply main power to the lighting control panel. 5. Manually activate each relay ON and OFF again, then confirm that each relay controls the appropriate load.
© 2011 Schneider Electric. All Rights Reserved.
11
Lighting Control Relay Panels Instruction Bulletin
Contact the Customer Information Center for technical support by phone at 1-888-778-2733 or e-mail at
[email protected]. Contact your local Schneider Electric service representative for repairs or service to your network. You may also find helpful information on our web site at www.Schneider-Electric.us.
Schneider Electric, USA 320 Tech Park Drive, Suite 100 La Vergne, TN, 37086 1-888-778-2733 www.schneider-electric.us
Schneider Electric and logo are trademarks or registered trademarks of Schneider Electric and/or its affiliates in the United States and/or other countries. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. © 2011 Schneider Electric. All Rights Reserved.
63249-420-352A1
04/2011