Light Oil Burners
ALM Series
30 - 2064 kW
High Technology
Wide Model Range and Full Series
Light oil burners are designed as a result of long term tests and by professionals experienced in case of liquid fuel. High technology production burners have the same operating efficiency with diesel fuel and light oil. Alarko diesel fuel and light oil burners comply with the European Norms (EN 267).
2.5 - 174 kg/h capacity range, square and volute body, single and double stage, totally 13 models are available. Wide range of capacity enables the most suitable and economic selection.
Maximum Safety and Reliability
Alarko light oil burners are featured to burn the oils which have viscosities up to 1.5°E-6 cSt (at 20°C). Single or double stage burners are factory-equipped with standard operating components, factory-adjusted and completely mounted and delivered in full with the fuel hoses and nozzles.
Burners are designed complying with the regulations of European standards. Special care is taken for safety during production and each burner is factory tested.
High Efficiency - Low Fuel Consumption Perfect air-fuel mixture and proper combustion is obtained with high efficiency by the special design combustion head and air diffuser. The same amount of energy is maintained with less fuel supply. By this means maximum economy for fuel consumption is provided.
Environment Friendly Operates silently with highly efficient fan and perfect combustion is provided even for the boilers with high back pressures. Particular designs of combustion head and air diffuser assure operating with low CO and NOx emissions contributing to the environmental protection.
Order Notation ALM
.../
_ 2
- : Single stage 2 : Double stage Maximum fuel consumption (kg/h) Alarko light oil burners
Full Delivery
Boiler-Burner Conformity Correct burner selection for the boiler, burner flame length and diameter conformity with combustion chamber are the most important factors affecting the combustion quality. Alarko burners operate properly and silently with the boilers having either low or high back pressures. The best matching of boiler and burner is determined and certificated after prolonged tests.
Square Body Burners
Models ALM 30, 30/2, 40/2 have black rear covers.
Dimensions (mm) TYPES
A
ALM 5 ALM 7 ALM 14 ALM 22 ALM 30 ALM 30/2 ALM 40/2
B
280 280 309 359 420 420 420
D
C 379 450 576 671 765 765 782
247 247 282 349 423 423 430
ØF
E Max. 89 137 220 200 290 290 310
Min. 40 85 60 70 70 120
195 195 217 275 350 350 350
ØG
80 90 130 120 133 133 147
ØH Min. 136 140 140 160 174 174 172
85 95 110 135 145 145 160
J Max. 161 200 200 225 226 226 225
M8 M8 M8 M10 M10 M10 M10
Technical Specifications ALM 5
ALM 7
ALM 14
ALM 22
ALM 30
ALM 30/2
ALM 40/2
min.
kg/h
2,5
4,7
6,8
11
18
13
20
max.
kg/h
5
7
14
22
30
30
40
min.
kW
29,7
55,8
80,8
130,2
213,4
154,1
237,2
max.
kW
59,3
83,1
166,3
261
355,8
355,8
474,4
min.
kcal/h
25.500
48.000
69.500
112.000
183.500
132.500
204.000
max.
kcal/h
408.000
TYPES
Capacity
Heating Power
51.000
71.500
143.000
224.500
306.000
306.000
Motor 2800 d/d
W
100
100
150
250
370
370
370
Net Weight
kg
9,7
10,4
13,2
19
27,3
28,8
27,5
Package Dimensions mm Power Supply
640x395x335
515x375x315
740x435x400
850x495x475
1~220V, 50Hz
Fuel
3~220/380V, 50Hz
Light Oil - max. Viscosity 1,5°E=6 cSt, 20°C. Lower calorific value of the fuel: 10.200 kcal/kg. ALM 5, 7, 14, 22, 30, 30/2, 40/2 models not compatible with CE standards. mbar
mbar
Capacity - Pressure Curves 4,5
5,5 5
4
4,5
3,5
4
3
3,5
2,5
3
2
2,5 2
1,5
1,5
1
3
5
7
20 40 60 80
9
160
200
240
280
ALM 40/2
0,5
11 13 15 17 19 21 23 25 27 29 31 kg/h 120
ALM 30/2
1
ALM 30
ALM 22
ALM 14
ALM 7
0,5 0,2 0 -0,2 -0,4
ALM 5
1
320
360 kW
0 -0,2 -0,4 12 13 15 17 150
190
19 21 23 25 230
270
27 29 31 33 35
310
350
390
37 39 41 kg/h
430
470
kW
Volute Body Burners
L
G
A K
B
H
C
J
F
ØS
øD
ØP
Z
E
Z
X
ØT
M
M1
Y1 Y
Dimensions (mm) TYPES
A
C
ØD
E
F
G
H
J
K
L
M
M1
N
ØP
ØS
ØT
Y
211
159
318
434
560
295
265
712
-
-
663
115
186
162
M10
-
R561 164
45
181
203
159
318
434
560
295
265
712
794
745
663
115
186
162
M10 R638 R561 164
45
193
213
181
318
440
560
295
265
712
-
-
663
115
208
184
M10
R561 164
45
181
211
181
318
440
564
295
269
712
794
745
663
115
208
184
M10 R638 R561 164
45
1.023 726
260
297
204
375
525
746
348
398
926 1.007 895
976
152
300
230
M12 R824 R756 230
45
1.033 734
262
299
226
375
525
746
348
398
926 1.007 895
976
152
300
230
M12 R824 R756 230
45
B Min.
Max.
595
181
798
595
808
595
806
595
986 996
Min.
Max.
ALM 50
776
806
ALM 60/2
776
ALM 59
788
ALM 76/2
776
ALM 125/2 ALM 174/2
-
Y1
X
Z
Technical Specifications ALM 50
ALM 60/2
ALM 59
ALM 76/2
ALM 125/2
ALM 174/2
min.
kg/h
19,8
19,1
32
32
53,4
60,5
max.
kg/h
50
60
59,5
76,6
123,4
174
min.
kW
235
227
380
380
632,8
717
max.
kW
593
712
706
909
1.464
2.064
min.
kcal/h
201.960
194.820
326.400
326.400
544.680
617.100
max.
kcal/h
510.000
612.000
606.900
781.320
1.258.680
1.774.800
TYPES
Capacity
Heating Power
Motor 2800 d/d
W
2.780
2.780
2.800
2.800
2.850
2.850
Net Weight
kg
32,1
34
33,6
35,5
66
66
Package Dimensions
mm
680x1.000x640
Power Supply
3~380/400V, 50Hz Light Oil - max. Viscosity 1,5°E=6 cSt, 20°C.
Fuel
Lower calorific value of the fuel: 10.200 kcal/kg.
Capacity - Pressure Curves
ALM 60/2 7 6
ALM 174/2
ALM 125/2
8
ALM 76/2
mbar
9
ALM 50
5 4 3 2
ALM 59
1 0 -1 10
20
30
40
50
60
70
80
90
100
110 120
130
140
150 160
170 180 kg/saat
200 300 400 500 600 700 800 900 100 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100
kW
Outstanding Features Combustion Head and Air Diffuser Adjustment Combustion head adjustment of square body burners can be done while the burner is in operation. For volute body burners, combustion head and air diffuser adjustments are accomplished by opening the burner by the means of hinged flange, optimum combustion is provided.
Silent Burners operate more silently comparing to similar ones of other brands. Square body burners have special air suction and noise reducing protective cover system. Volute body burners operate silently with their special aluminium alloy bodies having aerodynamic structures.
Air Adjustment Air damper of double stage burner is operated with servomotor and proper fuel-air mixture is obtained. Thus stable combustion with high efficiency is provided.
Automatic Air Shutting Maintains the temperature variations in the boiler within limits, retards the cooling of the boiler, and reduces oil consumption.
Ease of Assembly Sliding flange for square body, special hinged flange system for volute body burners utilize easy and correct burner-boiler assembly and provide fast maintenance conditions.
Service and Maintenance Ease Burner construction is designed allowing each component can be reached easily. Combustion head can be reached, adjustment and maintenance of the combustion and ionization electrodes can be carried out without separating square type burner from main fuel supply and boiler. By removing the protective cover all main components can be reached.
Easy Electrical Connections All cautions are taken for utilizing the electrical connection operations easy, correct and fast. To prevent possible connection failures electrical connections are designed to be made via sockets and clemences.
Main Components Square Body Burners 13 4
1
5
6 11
14
10
20
2 3 12
7
17 15
9 19
8
18
16
1. Body 2. Inner Cover 3. Fan 4. Air Diffuser 5. Ignition Electrodes 6. Check Cover 7. Photocell 8. Burner Motor 9. Fuel Pump 10. Electronic Control Unit
11. Ignition Transformer 12. Air Flap Adjustment Assembly 13. Combustion Head 14. Boiler Connection Flange 15. Front Cover 16. Rear Exterior Cover 17. Air Damper Motor (40/2) 18. Contactor (ALM 40/2) 19. Connector (ALM 30) 20. Selenoid Valve (ALM 40/2)
Volute Body Burners 6
13
17
1
16
12
18
11
10
2
20 7 8
15
19
9
3
4
5
14
1. Body 2. Top Cover 3. Boiler Connection Flange 4. Boiler Connection Gasket 5. Hinge 6. Burner Motor 7. Fuel Pump 8. 1st. Nozzle Button 9. Photocell 10. Operation Failure/Reset
11. Electronic Control Unit 12. Fuse 13. Cable Gland 14. Combustion Head 15. 1st. Selenoid Valve* 16. Damper Motor* 17. Inspection Hole 18. Air Flap Adjustment Key 19. 2nd. Nozzle Button* 20. 2nd. Selenoid Valve
* ALM 60/2, 76/2, 125/2, 174/2 models.
ALARKO CARRIER SANAY‹ VE T‹CARET A.fi.
GOSB-Gebze Organize Sanayi Bölgesi fiahabettin Bilgisu Cad. 41480 Gebze-Kocaeli/TURKEY Phone : (90)(262) 648 60 00 PBX Telefax : (90)(262) 648 61 01 web : www.alarko-carrier.com.tr e-mail :
[email protected]
A.5.1.3i 220108 MiNERAL
The company reserves its right to alter its products due to technological developments.