Lateral Design of Wood Frame Structures
This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.
Lateral Failure Shear Walls and Braced Walls
Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written permission of the speaker is prohibited. © USP Structural Connectors
Photos Courtesy National Information Service for Earthquake Engineering, University of California, Berkeley.
Lateral Failure
Earth Home
Shear Walls and Braced Walls
Shear Walls and Braced Walls
Photos Courtesy National Information Service for Earthquake Engineering, University of California, Berkeley. Photos Courtesy National Information Service for Earthquake Engineering, University of California, Berkeley.
Lateral Forces !
WIND - Wind forces are calculated from the velocity of the wind in that region and the load is stated in pounds per square foot.
Lateral Forces !
SEISMIC - Each region (Seismic Design Category, SDC) applies a multiplier to the structure’s mass in order to determine the lateral design load. ! The higher the SDC, the higher the multiplier.
– Racking – Sliding
– Overturning – Racking
Lateral Bracing
Lateral Bracing Shear Walls and Braced Walls
Shear Walls and Braced Walls
All buildings must have some type of lateral resisting system for lateral forces (wind, seismic).
Both Braced Walls and Shear Walls behave as a cantilevered beam.
1. 2. 3. 5.
Braced Walls Shear walls Prefabricated shear panel X-Bracing
Shear Wall/Braced Wall fixed at one end (at foundation)
Cantilever Beam fixed at one end
Shear Walls & Braced Walls
Shear Wall Analysis Methods
Shear Walls
Shear Walls
Shear Walls ! An Engineered Solution !
Pre-Fabricated or Field Fabricated
Braced Walls ! A prescriptive equivalent to engineered shear wall ! Braced Wall Lines ! Braced Wall Panels
Each Method requires: • Holdowns for uplift or overturning/ racking resistance • Anchor bolts for shear or translation
Shear Walls
Pre-Fabricated Shear Walls Shear Walls
Shear Walls
! Manufacturer
provides allowable loads for a particular panel and installation ! Should compare cost differences to site built ! Install per manufacturer’s recommendation.
Site-Built Shear Walls ! Nailing
patterns and hardware attachment information provided by engineer. ! IBC Table 2306.4.1 Provides Nailing Information Courtesy of APA-The Engineered Wood Association!
Complete Exterior Sheathing CUREE’s 7 Steps to better Shearwalls
Building Better Shear walls CUREE came out with 7 Tips to building better shear walls as a result of their research.
Symmetrical Edge Nailing Pattern CUREE’s 7 Steps to better Shearwalls
! Non-symmetrical ! Reduced
! Damage
pattern shifts center of rotation of the panel
Capacity
concentrated at edges having single row of nails
Use Sill Plate Washers
Increase Nailing Edge Distance
CUREE’s 7 Steps to better Shearwalls
! Plate
washers called for in the code as a result of sill plate splitting in cyclic testing performed at Virginia Tech ! Building code now requires 3” x 3” x ¼” Plate washers
CUREE’s 7 Steps to better Shearwalls
! More
distance from edge equals better shear wall performance. ! Maintain ¾” at top and bottom of wall 5/8” on side framing member attachment
Avoid Over-Driving Nails into Sheathing
Use Larger Vertical Members CUREE’s 7 Steps to better Shearwalls
CUREE’s 7 Steps to better Shearwalls
! Increase
vertical members or studs at holdowns and on sheathing joints ! Use
4x at holdowns ! Use 3x at vertical framing joints ! When
using a pneumatic nailer, avoid over-driving nails into sheathing ! Nail head should be recessed into sheathing a maximum of 1/32 inch
! If
using built-up post, studs must be nailed together (stitch nailing) to ensure piece acts as single unit
Shear Walls & Braced Walls
Exceptions for Braced Wall Panel Length
Braced Walls
Shear Walls ! An Engineered Solution !
Pre-Fabricated or Field Fabricated
Braced Walls ! A prescriptive equivalent to engineered shear wall ! Braced Wall Lines ! Braced Wall Panels
Braced Walls
!
Section R602.10.4 give exceptions if building contains: ! !
Continuous wood structural panel sheathing (R602.10.5) Alternate braced wall panels (R602.10.6.1 or R602.10.2)
PRESCRIPTIVE VS. ENGINEERED !
PRESCRIPTIVE ! 3 Stories Max. ! Wind < 110 mph (< 100 mph in hurricane-prone regions) ! SDC A-D ! Other limitations stated in IRC Chapter 3
!
ENGINEERED ! Any size/shape within IBC limits ! Wind – no limit ! Seismic – no limit ! Governed by engineer’s calculations
“Cookbook Engineering” !
! Recipes
! ! ! ! !
BRACED WALL REQUIREMENTS HAVE BEEN COMPLETELY REWRITTEN
! 2006 IRC © = 6 pages ! 2009 IRC © and 2012 IRC © = 28 pages ! ICC / APA Guide to the 2009 IRC© Bracing Provisions = 255 pages !
! !
based on: Historical Performance Typical Materials Conservative Analysis Nationwide Application No Design Professional Required
Braced Walls in the 2012 IRC ©
2012 IRC & 2009 IRC vs. 2006 IRC !
Ad Hoc Wall Bracing Committee
ALL PLANS DESIGNED UNDER 2006 IRC © SHOULD BE REVIEWED Most smaller houses will likely be OK Larger houses may need additional bracing.
! Continuous improvement to the organization of BW requirements ! Reorganized to consolidate BWL length, spacing and orientation into ! ! ! ! ! !
one section BWP now allowed to be up to 10ft from end of BWL instead of 12.5ft Wind adjustment footnotes have now been consolidated into a table Bracing methods consolidated into one section Minimum BWP lengths consolidated into one table All ABW now consolidated into one section Simplified BW section added for low wind and low seismic areas.
BRACED WALL TERMINOLOGY ! ! ! !
BRACED WALL LINE SPACING
Braced Wall Line Braced Wall Line Spacing Braced Wall Panel Braced Wall Panel Spacing
– The braced wall line spacing in IRC Table R602.10.1.3 Seismic>Do is limited to 25 feet or less, however: – For townhouses in SDC C - No adjustment required for spacing up to 35 feet, bracing length Table R602.10.1.3. Note that IRC Section R301.2.2 exempts all residential buildings in SDC A and B from seismic provisions of the code. – For all structures in SDC D0, D1, D2, - No adjustment required for spacing up to 35 feet to accommodate a single room not to exceed 900 square feet in each dwelling unit, otherwise braced wall line lengths should be adjusted in accordance with IRC Table R602.10.1.3, with certain limitations. Braced wall line spacing greater than 35 feet is not permitted.
BRACED WALLS OFFSET
TABLE R602.10.1.3 BRACED WALL LINE SPACING
BRACED WALL LINE SPACING CRITERIA APPLICATION
CONDITION
BUILDING TYPE Maximum Spacing
Wind Bracing
Seismic Bracing
Exception to Maximum Spacing
85 mph to < 110 mph
Detached, Townhouse
SDC A - C
Detached
Use Wind Bracing
SDC A - B
Townhouse
Use Wind Bracing
SDC C
Townhouse
35 feet
Up to 50 feet when length of required bracing per Table R602.10.3(3) is adjusted in accordance with Table R602.10.3(4).
SDC D0, D1, and D2
Detached, Townhouses, One- and Two-Story Only
25 feet
Up to 35 feet to allow for a single room not to exceed 900 square feet. Spacing of all other braced wall lines shall not exceed 25 feet.
SDC D0, D1, and D2
Detached, Townhouse
25 feet
Up to 35 feet when length of required bracing per Table R602.10.3(3) is adjusted in accordance with Table R602.10.3(4).
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 mile per hour = 0.447 m/s.
60 feet
None
• BRACED
WALL PANELS are allowed to be offset up to 8’-0” and still be considered in the same BRACED WALL LINE so long as all of the BRACED WALL PANELS are within 4’-0” of the designated BRACED WALL LINE.
BRACED WALL LINE SPACING ! !
LENGTH OF BRACED WALL LINES
IRC Section R602.10.1 The length of the braced wall line spacing shall be measured as the maximum distance to adjacent braced wall lines.
! !
LENGTH OF BRACED WALL LINES
!
LENGTH OF BRACED WALL LINES
R602.010.1 BRACED WALL LINES:
The end of a braced wall line shall be considered to be either: ! The intersection with perpendicular exterior walls ! The intersection with perpendicular – 1 braced wall lines ! The end of the braced wall line shall be chosen such that the – 2 maximum length results
!
– 3
IRC Section R602.10.1 The length of a braced wall line shall be measured as the distance between the ends of the wall line.
!
R602.010.1 BRACED WALL LINES:
!
The end of a braced wall line shall be considered to be either: The intersection with perpendicular exterior walls The intersection with perpendicular braced wall lines The end of the braced wall line shall be chosen such that the maximum length results
!
– 1 ! !
– 2
– 3
IMAGINARY (EFFECTIVE) BRACED WALL LINES !
BRACED WALL LINE LENGTH EXAMPLE
If wall line is less than 4 feet from braced wall line there is no need for a bracing panel on that line. – The braced wall line spacing in IRC Table R602.10.1.2 (2) is limited to 25 feet or less, however: – For townhouses in SDC C - No adjustment required for spacing up to 35 feet, bracing length Table R602.10.1.2 (3). Note that IRC Section R301.2.2 exempts all residential buildings in SDC A and B from seismic provisions of the code. – For all structures in SDC D0, D1,, D2, - No adjustment required for spacing up to 35 feet to accommodate a single room not to exceed 900 square feet in each dwelling unit, otherwise braced wall line lengths should be adjusted in accordance with IRC Table R602.10.1.5, with certain limitations. Braced wall line spacing greater than 35 feet is not permitted.
BRACED WALL PANEL SPACING !
BRACED WALL PANEL (PRESCRIBED)
IRC Section R602.10.1.4 !
Not Farther Than 25 Feet on Center !
Measured From Centerline of Panel to Centerline of Panel
!
If Bracing Sections are Wider Than 4 Feet it is Acceptable to be Spaced 21 Feet Apart
!
Seismic and Wind Requirements Slightly Different
!
A full-height section of wall constructed to resist in-plane shear loads through interaction of framing members sheathing material and anchors.
!
The panel’s length meets the requirements of its particular bracing method and contributes toward the total amount of bracing required along its braced wall line in accordance with Section R602.10.1.
INTERMITTENT BRACING !
LIB – LET-IN-BRACING
!
DWB – DIAGONAL WOOD BOARDS
!
WSP – WOOD STRUCTURAL PANEL
!
SFB – STRUCTURAL FIBERBOARD SHEATHING
!
GB – GYPSUM BOARD
!
PBS – PARTICLEBOARD SHEATHING
!
PCP – PORTLAND CEMENT PLASTER
!
HPS – HARDBOARD PANEL SIDING
!
ABW – ALTERNATE BRACED WALL
!
PFH – PORTAL FRAME WITH HOLDOWNS
!
PFG – PORTAL FRAME AT GARAGE.
LIB – LET-IN-BRACING Method
Material
Minimum Thickness
LIB
Let-In Bracing
1x4 wood or approved metal straps at 45 to 60 angles for maximum 16” stud spacing
DWB – DIAGONAL WOOD BOARDS Method
Material
Minimum Thickness
DWB
Diagonal Wood Boards
3/4” (1” nominal) for maximum 24” stud spacing
Figure
Figure
Connection Criteria
Wood: 2-8d nails per stud including top & bottom plate Metal: per manufacturer
WSP – WOOD STRUCTURAL PANEL
Connection Criteria
Method
Material
Minimum Thickness
2-8d (2 1/2” x 0.113”) nails or 2 staples, 1-3/4” per stud
WSP
Wood Structural Panel (See Section R604)
3/8”
Figure
Connection Criteria
Exterior Sheathing: see IRC Table R602.3(3) Interior Sheathing: see IRC Table R602.3(1)
SFB – STRUCTURAL FIBERBOARD SHEATHING Method
Material
Minimum Thickness
SFB
Structural Fiberboard Sheathing
1/2” or 25/32” for Maximum 16” Stud spacing
Figure
Connection Criteria
1-1/2” galvanized roofing nails or 8d common (2-1/2” x 0.131”) nails at 3” spacing (panel edges) at 6” spacing (intermediate supports).
GB – GYPSUM BOARD Method
GB
Material
Gypsum Board
Material
Minimum Thickness
PBS
Particleboard Sheathing (See Section R605)
3/8” or 1/2” for maximum 16” stud spacing
Figure
Figure
Connection Criteria
Nails and screws at 7” spacing at panel edges including top and bottom plates for all braced wall panel locations. For exterior sheathing nail or screw size, see IRC Table R602.3(1). For interior gypsum board nail or screw size, see IRC Table R702.3.5.
1/2”
PCP – PORTLAND CEMENT PLASTER
PBS – PARTICLEBOARD SHEATHING Method
Minimum Thickness
Connection Criteria
Method
Material
Minimum Thickness
1-1/2” galvanized roofing nails or 8d common (2-1/2” x 0.131”) nails at 3” spacing (panel edges) at 6” spacing (intermediate supports).
PCP
Portland Cement Plaster
See Section R703.6 for maximum 16” stud spacing
Figure
Connection Criteria
1-1/2”, 11 gage 7/16” head nails or 7/8”, 16 gage staples at 6” spacing
CONTINUOUS SHEATHING
HPS – HARDBOARD PANEL SIDING
Method
Material
Minimum Thickness
HPS
Hardboard Panel Siding
7/16” for maximum 16” stud spacing
Figure
Connection Criteria
!
0.092” dia., 0.225 head nails with length to accommodate 1-1/2” penetration into studs at 4” spacing (panel edges), at 8” spacing (intermediate supports).
CONTINUOUS SHEATHING BRACING MATERIALS ! ! ! !
CS-WSP CS-G CS-PF CS-SFB
CS-WSP CONTINUOUSLY SHEATHED WOOD STRUCTURAL PANEL
Method
CS-WSP
Method
Material
Minimum Thickness
CS-WSP
Wood Structural Panel
3/8”
6d common (2” x 0.113”) nails at 6” spacing (panel edges) and at 12” spacing (intermediate supports) or 16 ga. x 1-3/4 staples: at 3” spacing (panel edges) and 6” spacing (intermediate supports)
CS-G
Wood Structural Panel Adjacent to Garage Openings and Supporting Roof Load Only ab
3/8”
See Method CS-WSP
CS-PF
Continuous Portal Frame
See Section R602.10.4.1.1
See Section R602.10.4.1.1
a. Applies to one wall of a garage only. b. Roof covering dead loads shall be 3 psf or less.
Structural Sheathing Applied to all Sheathable Surfaces Including the Areas Above and Below Openings
Figure
Connection Criteria
Material
Wood Structural Panel
Minimum Thickness
3/8”
Figure
Connection Criteria
6d common (2” x 0.113”) nails at 6” spacing (panel edges) and at 12” spacing (intermediate supports) or 16 ga. x 1-3/4 staples: at 3” spacing (panel edges) and 6” spacing (intermediate supports)
CS-G
CS-PF
CONTINUOUSLY SHEATHED WOOD STRUCTURAL PANEL ADJACENT TO GARAGE
CONTINUOUSLY SHEATHED PORTAL FRAME
Method
Material
Minimum Thickness
CS-G
Wood Structural Panel Adjacent to Garage Openings and Supporting Roof Load Only ab
3/8”
Figure
Connection Criteria
See Method CS-WSP
Method
Material
Minimum Thickness
CS-PF
Continuous Portal Frame
See Section R602.10.4.1.1
Figure
Connection Criteria
See Section R602.10.4.1.1
a. Applies to one wall of a garage only. b. Roof covering dead loads shall be 3 psf or less.
CS-SFB
MIXED BRACING METHODS
CONTINUOUSLY SHEATHED STRUCTURAL FIBERBOARD SHEATHING
Method
CS-SFB
! !
Material
Continuous Structural Fiberboard Sheathing
Minimum Thickness
1/2” or 25/32” for 16” Stud Spacing Only
New to the 2009 IRC Restrictions apply, see R602.10.5
Figure
Connection Criteria
1-1/2” galvanized roofing nails or 8d common (2-1/2” x 0.131”) nails at 3” spacing (panel edges) at 6” spacing (intermediate supports).
! ! !
!
R602.10.1.1 BRACED WALL PANELS. ! Mixing of bracing methods shall be permitted as follows: 1. Mixing bracing methods from story to story is permitted. 2. Mixing bracing methods from braced wall line to braced wall line within a story is permitted, except CS shall conform to R602.10.4 and R602.10.5. 3. Mixing bracing methods within a braced wall line is permitted only in SDC A, B and detached dwellings of C.
Table R602.10.4.1.1
ABW – ALTERNATE BRACED WALL Method
ABW
Material
Minimum Thickness
Wood Structural Panel
Figure
Tension Strap Capacity Required For Resisting Wind Pressures Perpendicular to 6:1 Aspect Ratio Walls
Connection Criteria MINIMUM WALL STUD FRAMING SIZE AND GRADE
3/8”
BASIC WIND SPEED (mph)
MAXIMUM PONY WALL HEIGHT (feet)
MAXIMUM TOTAL WALL HEIGHT (feet)
MAXIMUM OPENING WIDTH (feet)
85
0
10
18
1000
1000
1000
1000
1000
9
1000
1000
1000
1000
1000
10
16
1000
1000
1750
1800
2325
3500
18
1000
1200
2100
2175
2725
Engineering Req’d
– 8d common or gal. box nails@ 6" o.c. at panel edges for the first two stories
– Studs under header as required
1
2X4 No. 2 Grade
– 8d common or gal. box nails @ 12" o.c. at interior supports
– Hold-down or strap-type anchor per Table R602.10.3.2 (Both shown for clarity.) Strap-type anchors shall be permitted to be attached over the wood structural panel.
– Minimum reinforcing of foundation, one #4 bar top and bottom of footing. Reinforcing shall be lapped 15 inches.
2
2
– (2) 1/2" Diameter anchor bolts per Figure R403.1.1, located between 6 and 12 inches of each end of the segment
– Minimum footing size under opening is 12" x 12" A turneddown slab shall be permitted at door openings. Reinforcing shall be as shown above.
4
2
10
12
12
12
2x6 Stud Grade 4
Table R602.10.3.2 Minimum Length Requirements and Hold-Down Forces For ABW Braced Wall Panels
85
90
100
Exposure C
Tension strap capacity required (lbf)
– For panel splice (if needed) adjoining panel edges shall meet over and be fastened to common framing
– Minimum 2X4 framing, minimum double studs required
100
Exposure B
See Section R602.10.3.2
– Min. 3/8" (10) wood structural panel sheathing on one face
90
12
1000 1275
9
1000
1000
1025
1075
1550
2500
16
1525
2025
3125
3200
3900
Engineering Req’d
18
1875
2400
3575
3700
Engineering Req’d
Engineering Req’d
9
1000
1200
2075
2125
2750
4000
16
2600
3200
Engineering Req’d
Engineering Req’d
Engineering Req’d
Engineering Req’d
18
3175
3850
Engineering Req’d
Engineering Req’d
Engineering Req’d
Engineering Req’d
9
1775
2350
3500
3550
Engineering Req’d
Engineering Req’d
16
4175
Engineering Req’d
Engineering Req’d
Engineering Req’d
Engineering Req’d
Engineering Req’d
9
1000
1000
1325
1375
1750
2550
16
1650
2050
2925
3000
3550
Engineering Req’d
18
2025
2450
3425
3500
4100
Engineering Req’d
9
1125
1500
2225
2275
2775
3800
16
2650
3150
Engineering Req’d
Engineering Req’d
Engineering Req’d
Engineering Req’d
18
3125
3675
Engineering Req’d
Engineering Req’d
Engineering Req’d
Engineering Req’d
Bracing Around Garage Doors Braced Walls
Lateral Failure SEISMIC DESIGN CATEGORY AND WIND SPEED
HEIGHT OF BRACED WALL PANEL
Minimum sheathed length
SDC A, B and C Wind speed < 110 mph
R602.10.3.2, item 1 hold-down force (lb) R602.10.3.2, item 1 hold-down force (lb) Minimum sheathed length R602.10.3.2, item 1 hold-down force (lb)
SDC D0, D1 and D2 Wind speed < 110 mph
R602.10.3.2, item 1 hold-down force (lb)
8 ft
9 ft
10 ft
11 ft
12 ft
2’-4”
2’-8”
2’-10”
3’-2”
3’-6”
1800
1800
1800
2000
2200
3000
3000
3000
3300
3600
2’-8”
2’-8”
2’-10”
Not Permitted
Not Permitted
1800
1800
1800
Not Permitted
Not Permitted
3000
3000
3000
Not Permitted
Not Permitted
Photo Courtesy National Information Service for Earthquake Engineering, University of California, Berkeley.
PFH – PORTAL FRAME WITH HOLDOWNS
PFG – PORTAL FRAME AT GARAGE EIGHT SPECIFIC PFG PROVISIONS R602.10.3.4
Method
Material
Minimum Thickness
PFG
Wood Structural Panel
7/16”
Figure
Connection Criteria
Method
Material
Minimum Thickness
See Section R602.10.3.4
PFH
Wood Structural Panel
3/8”
– Fasten sheathing to header with 8d common or galvanized box nails in 3 in. grid pattern as shown and 3 in. o.c. in all framing (studs, blocking, and sills) typ.
– 1
– For a panel splice (if needed), panel edges shall occur over and be nailed to common blocking, and occur within middle 24 in. of wall height. One row of 3 in. o.c. nailing is required in each panel edge.
– 2
– Minimum length based on 4:1 height-to-length ratio. For example: 24 in. min. for 8 ft. height.
– 3
See Section R602.10.3.3
– Fasten sheathing to header with 8d common or galvanized box nails in 3 in. grid pattern as shown and 3 in. o.c. in all framing (studs, blocking, and sills) typ.
– 2
– 3
– Min. length = 16 in. for one story, min. length = 24 in. for use in the first two story structures.
– 4
– Min. 4200 lb tie-down device (embedded into concrete and nailed into framing). – For a panel splice (if needed), panel edges shall occur over and be nailed to common blocking, and occur within middle 24 in. of wall height. One row of 3 in. o.c. nailing is required in each panel edge.
CONTINUOUSLY SHEATHED BRACED WALL LINE A braced wall line with structural sheathing applied to all sheathable surfaces including the areas above and below openings.
Connection Criteria
– Fasten top plate to header with two rows of 16d sinker. Nails at 3 in. o.c. typ.
– 1
– 5
!
Figure
CONTINUOUSLY SHEATHED BRACED WALL WITH OPENINGS !
R602.10.4.2 OPENINGS IN BRACED WALL LINE
CONTINUOUSLY SHEATHED BRACED WALL WITH OPENINGS !
R602.10.4.2 OPENINGS IN BRACED WALL LINE
– TABLE R602.10.5
!
CS - MINIMUM LENGTH OF BRACED WALL PANELS
WALL HEIGHT Method
Adjacent Clear Opening Height
8’
9’
10’
11’
12’
64”
24”
27”
30”
33”
36”
68”
26”
27”
30”
33”
36”
72”
27”
27”
30”
33”
36”
76”
30”
29’
30”
33”
36”
80”
32”
30”
30”
33”
36”
84”
35”
32”
32”
33”
36”
88”
38”
35”
33”
33”
36”
92”
43”
37”
35”
35”
36”
96”
48”
41”
38”
36”
36”
100”
-
44”
40”
38”
38”
104”
-
49”
43”
40”
39”
108”
-
54”
46”
43”
41”
112”
-
-
50”
45”
43”
116”
-
-
55”
48”
45”
120”
-
-
60”
52”
48”
124”
-
-
-
56”
51”
128”
-
-
-
61”
54”
132”
-
-
-
66”
58”
136”
-
-
-
-
62”
140”
-
-
-
-
66”
144”
-
-
-
-
72”
CS-G
See Note B
24”
27”
30”
-
-
CS-PF
< 120”
16”
18”
20”
-
-
CS-WSP, CS-SFB
a. Interpolation shall be permitted. b. Garage openings adjacent to a method CS-G panel shall be provided with a header in accordance with IRC Table R502.5(1). A full-height clear opening shall not be permitted adjacent to a method CS-G c. Maximum opening height shall be in accordance with IRC Figure R602.10.4.1.1.
CONTINUOUSLY SHEATHED BRACED WALL WITH OPENINGS R602.10.4.2 OPENINGS IN BRACED WALL LINE
EXAMPLE PROBLEM
Example 1 – Upper Level
EXAMPLE PROBLEM 1 !
Single Family
!
Two Story
!
SDC = C
!
Wind =100 MPH, Exposure C
!
Roof Eave-to-Ridge = 8 ft
!
Roof/Ceiling Dead Load = 20 psf
!
Wall Dead Load = 8 psf
!
Wall Heights: 10 ft
2012 IRC - WIND
TABLE R602.10.3(2) WIND ADJUSTMENT FACTORS TO THE REQUIRED LENGTH OF WALL BRACING
!
BASIC WIND SPEED 5
1.00 1.30 1.45 1.60
Additional 800-Pound Hold-Down Device
Top Story Only
Fastened to the end studs of each braced wall panel and to the foundation or framing below.
0.80
DWB, WSP, SFB, PBS, PCP, HPS
Interior Gypsum Board Finish (or Equivalent)
Any Story
Omitted from inside face of braced wall panels
1.40
DWB, WSP, SFB, PBS, PCP, HPS, CS-WSP, CS-G, CS-SFB
Gypsum Board Fastening
Any Story
4 inches o.c. at panel edges, including top and bottom plates, and all horizontal joints blocked
0.70
GB
APPLICABLE METHODS
All Methods
For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 pound = 4.48 N. a. Linear interpolation shall be permitted. b. The total adjustment factor is the product of all applicable adjustment factors. c. The adjust factor is permitted to be 1.0 when determining bracing amounts for intermediate braced wall lines provided the bracing amounts on adjacent braced wall lines are based on a spacing and number that neglects the intermediate braced wall line.
2012 IRC - WIND
TABLE R602.10.3(2) WIND ADJUSTMENT FACTORS TO THE REQUIRED LENGTH OF WALL BRACING
!
BASIC WIND SPEED 5
1.00 1.30 1.45 1.60
Additional 800-Pound Hold-Down Device
Top Story Only
Fastened to the end studs of each braced wall panel and to the foundation or framing below.
0.80
DWB, WSP, SFB, PBS, PCP, HPS
ABW
Interior Gypsum Board Finish (or Equivalent)
Omitted from inside face of braced wall panels
1.40
DWB, WSP, SFB, PBS, PCP, HPS, CS-WSP, CS-G, CS-SFB
PFH
Any Story
Gypsum Board Fastening
Any Story
4 inches o.c. at panel edges, including top and bottom plates, and all horizontal joints blocked
APPLICABLE METHODS MINIMUM LENGTH a
METHOD (See Table R602.10.4)
All Methods
CONTRIBUTING LENGTH (inches)
9 Feet
10 Feet
11 Feet
12 Feet
DWB, WSP, SFB, PBS, PCP, HPS, BV-WSP
48
48
48
53
58
Actual b
GB
48
48
48
53
58
Double Sided = Actual Single Sided + 0.5 x Actual Actual b
LIB
0.70
Wall Height 8 Feet
55
62
69
NP
NP
SDC A, B, and C wind speed = < 110 mph
28
32
34
38
42
SDC D0, D1, and D2 Wind speed < 110 mph
28
32
34
NP
NP
Supporting Roof Only
16
16
16
18c
20c
Supporting One Story & Roof
24
24
24
27c
29c
48
PFG
24
27
30
33d
36d
1.5 x Actual b
CS-G
24
27
30
33
36
Actual b
CS-PF
16
18
20
22e
24e
Actual b
48
48
GB
For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 pound = 4.48 N. a. Linear interpolation shall be permitted. b. The total adjustment factor is the product of all applicable adjustment factors. c. The adjust factor is permitted to be 1.0 when determining bracing amounts for intermediate braced wall lines provided the bracing amounts on adjacent braced wall lines are based on a spacing and number that neglects the intermediate braced wall line.
This concludes The American Institute of Architects Continuing Education Systems Course!
Todd Grevious! (952)898-8651!
[email protected]!
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.45 N, 1 mile per hour = 0.447 m/s. NP = Not Permitted a. Linear interpolation shall be permitted. b. Use the actual length when it is greater than or equal to the minimum length. c. Maximum header height for PFH is 10 feet in accordance with Figure R602.10.6.2 but wall height may be increased to 12 feet with pony wall. d. Maximum opening height for PFG is 10 feet in accordance with Figure R602.10.6.3 but wall height may be increased to 12 feet with pony wall. e. Maximum opening height for CS-PF is 10 feet in accordance with Figure R602.10.6.4 but wall height may be increased to 12 feet with pony wall.