LARGE Drives. Intelligent solutions for pumping applications

LARGE Drives & Controls Intelligent solutions for pumping applications Contents Starters Intelligent Pump Starter (IPS) Standard Pump Starter (SPS) ...
0 downloads 2 Views 4MB Size
LARGE Drives & Controls Intelligent solutions for pumping applications

Contents Starters Intelligent Pump Starter (IPS) Standard Pump Starter (SPS) Economy Pump Starter (EPS) Advanced Duplex Pump Controller (APX) Duplex Alternating Pump Controller (DPX)

4 11 15 19 23

Reduced Voltage Digital Soft Starter (MS6) Analog Soft Starter (RVS)

27 31

Variable Speed P-Series P-Series Enclosed P- Series Stand Alone

35 40

Intelligent Pump Starter (IPS)

IPS

Intelligent Pump Starter

50/60 Hz, 1Ø & 3Ø, 120~600 VAC, 1/3 - 300 hp Integrated electronic pump protection overload Power metering and data logging options

More Protection, Less Nuisance Trips Integrated Tru-power™ electronic motor and pump protection • Eliminates need for costly pump protection relays • Dry pump detection using power (nuisance trip-free); automatic restart for well recovery mode • Wide range class 5-30 electronic overload eliminates call backs due to mid-sized heaters • Advanced protective features include over/under voltage, phase loss, phase unbalance, stalled/locked rotor, cycle fault, and UL 1053 ground fault • Tru-power™ sensing protects pumps from dry pump, dead head, runout, and jammed impeller conditions - keeping you online and preventing costly premature pump failure. Along with superior protection, measuring underload using power allows for a more flexible trip range, as opposed to measuring by current, which requires a more precise set point. The end result is the elimination of nuisance trips. Adjustable over/under voltage is included. Plus you get phase unbalance, loss, anti-cycling, phase sequence, and warm start protection. Our overload is wide range - so you never have the wrong sized heaters.

Built-in power monitoring and fault logging for easy troubleshooting • View voltage, current, power factor, and more through an intuitive display • Last 5 fault types are recorded (all power condition values are stored) • Quickly identify common power problems such as phase imbalance, voltage drop, and over/undercurrent conditions to ensure proper pump operation

NEMA

Optional Ethernet card provides time-stamped data logging, ending utility power disputes • Download and display up to 100 faults and alarms, including operational mode and values of operation at the time • All power condition values are stored by phase for voltage, current, and power factor per fault • Data is easily displayed and saved on any web browser using an Ethernet connection. Starter incorporates internal web-server. No programming required

Power

Current

• Time and date stamped for utility documentation

No Load

Full Load

No Load

Full Load

Power is linear for superior load monitoring

4

Get up to100 faults - even utility power quality - on any web-browser!

IPS

Intelligent Pump Starter (IPS)

Easy to setup and use • Inside, the display shows an easy to use menu for setting



a wealth of parameters. Adjust any protective or control setting in seconds. For example, choose how long to allow for dry well recovery, set run time periods and On/Off delays. All this with just a few intuitive keystrokes. The IPS ships with factory default settings pre-programmed for optimal submersible pump protection.

Internal keypad menu for easy operation • All control and protective functions are easily programmable • LEDs indicate Hand/Off/Auto modes, run and fault conditions

Industrial grade construction for long life • Door mounted pilot devices include HOA switch • UL/NEMA 3R outdoor rating • Multi-tap transformer accommodates common voltages; no fuse(s) required • 120 V control power for field devices • Magnetic contactors feature 2.5 million contactor electrical cycles at full rated current

Advanced programmable pump control options • Auto-restart with well recovery timer • Backspin delay prevents start-ups into draining system • On delay and off delay settings • Minimum run time based on last input • 12-120 V auto run terminal for remote start/stop

UL/NEMA Type 3R enclosure

• Dry contact terminal for remote start/stop • Analog input for transducer for use with pressurized tanks (under development - consult factory for availability)

Main circuit breaker disconnect rated for service entrance • UL 489 circuit breaker provides branch and short circuit protection • No fuses required – saves time and money • Lockable handle for safety

5

Intelligent Pump Starter (IPS)

IPS Ordering & Sizing Information Intelligent Pump Starter (Combination) UL/NEMA 3R Enclosure (Electronic Overload)

HP

NEMA Size

Wt. (lbs)

Description

IPS3R-S1-J-G15-8 1/3 1 2 2 5 8A IPS3R-S1-J-G20-11 1/2 1.5 3 3 7.5 11A IPS3R-S1-6J-G20-11 10 IPS3R-S1-J-G30-17 1 3 5 10 17A 1 IPS3R-S1-6J-G30-17 15 IPS3R-S1-J-G40-22 7.5 15 22A IPS3R-S1-6J-G40-22 20 IPS3R-S1-J-G50-28 2 5 7.5 10 20 28A IPS3R-S1-6J-G50-28 25 IPS3R-S2-6J-G30-17 15 17A IPS3R-S2-J-G40-22 7.5 15 22A IPS3R-S2-6J-G40-22 20 IPS3R-S2-J-G50-28 2 5 7.5 10 20 28A IPS3R-S2-6J-G50-28 25 2 IPS3R-S2-J-G60-34 3 5 10 10 25 34A IPS3R-S2-6J-G60-34 30 IPS3R-S2-J-G80-42 7.5 15 30 42A IPS3R-S2-6J-G80-42 40 IPS3R-S3-6J-G60-34 30 34A IPS3R-S3-J-G80-42 7.5 15 30 42A IPS3R-S3-6J-G80-42 40 IPS3R-S3-J-G100-56 5 10 15 20 40 56A IPS3R-S3-6J-G100-56 50 3 IPS3R-S3-J-G125-68 5 15 20 25 50 68A IPS3R-S3-6J-G125-68 60 IPS3R-S3-J-G150-80 7.5 15 25 30 60 80A IPS3R-S3-6J-G150-80 75 IPS3R-S4-6J-G125-68 60 68A IPS3R-S4-J-G150-80 7.5 15 25 30 60 80A IPS3R-S4-6J-G150-80 75 4 IPS3R-S4-J-G200-104 10 25 30 40 75 104Asize rating. * Note: The shaded figures represent the minimum horsepower for corresponding NEMA IPS3R-S4-6J-G200-104 100 IPS3R-S4-J-G250-136 15 30 40 50 100 136A IPS3R-S5-6J-G250-125 125 125A IPS3R-S5-J-G300-156 50 60 125 156A IPS3R-S5-6J-G300-150 150 150A 5 IPS3R-S5-J-G400-221 50 75 75 150 221A IPS3R-S5-6J-G400-200 200 200A IPS3R-S5-J-G500-248 75 100 200 248A IPS3R-S5P-6J-G500-250 250 250A IPS3R-S5P-J-G600-312 100 125 250 312A 5+ IPS3R-S5P-6J-G600-300 300 300A IPS3R-S5P-J-G800-361 150 150 300 361A

46 46 46 46 46 46 46 46 46 50 50 50 50 50 50 50 50 50 66 66 66 66 66 66 66 66 66 85 85 85 85 85 85 240 240 240 240 240 240 382 382 382 382

N3R IPS, S1, 8A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 11A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 11A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 17A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 17A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 22A w/ SCM, MCCB Disc, HOA, 50VA CPT N3R IPS, S1, 22A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 28A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 28A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 17A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 22A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 22A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 28A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 28A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 34A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 34A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 42A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 42A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S3, 34A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 42A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 42A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 56A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 56A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 68A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 68A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S3, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 68A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S4, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 104A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S4, 104A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 136A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S5, 125A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 156A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5, 150A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 221A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5, 200A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 248A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5P, 250A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5P, 312A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5P, 300A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5P, 361A w/ SCM, MCCB Disc, HOA, 200 VA CPT

Model No.

Single-Phase 120 V

230 V

Three-Phase 200 V

230 V

460 V

575 V

Max. Amps

* Note: The shaded figures represent the maximum horsepower for corresponding NEMA size rating.

6

Intelligent Pump Starter (IPS)

IPS Ordering & Sizing Information Intelligent Pump Starter (Combination) with Ethernet Card UL/NEMA 3R Enclosure (Electronic Overload)

HP Model No. IPS3R-S1-J-G15-8E IPS3R-S1-J-G20-11E IPS3R-S1-6J-G20-11E IPS3R-S1-J-G30-17E IPS3R-S1-6J-G30-17E IPS3R-S1-J-G40-22E IPS3R-S1-6J-G40-22E IPS3R-S1-J-G50-28E IPS3R-S1-6J-G50-28E IPS3R-S2-6J-G30-17E IPS3R-S2-J-G40-22E IPS3R-S2-6J-G40-22E IPS3R-S2-J-G50-28E IPS3R-S2-6J-G50-28E IPS3R-S2-J-G60-34E IPS3R-S2-6J-G60-34E IPS3R-S2-J-G80-42E IPS3R-S2-6J-G80-42E IPS3R-S3-6J-G60-34E IPS3R-S3-J-G80-42E IPS3R-S3-6J-G80-42E IPS3R-S3-J-G100-56E IPS3R-S3-6J-G100-56E IPS3R-S3-J-G125-68E IPS3R-S3-6J-G125-68E IPS3R-S3-J-G150-80E IPS3R-S3-6J-G150-80E IPS3R-S4-6J-G125-68E IPS3R-S4-J-G150-80E IPS3R-S4-6J-G150-80E IPS3R-S4-J-G200-104E IPS3R-S4-6J-G200-104E IPS3R-S4-J-G250-136E IPS3R-S5-6J-G250-125E IPS3R-S5-J-G300-156E IPS3R-S5-6J-G300-150E IPS3R-S5-J-G400-221E IPS3R-S5-6J-G400-200E IPS3R-S5-J-G500-248E IPS3R-S5P-6J-G500-250 IPS3R-S5P-J-G600-312E IPS3R-S5P-6J-G600-300E IPS3R-S5P-J-G800-361E

Single-Phase

Three-Phase

120 V

230 V

200 V

230 V

460 V

575 V

1/3 1/2 1 2 2 3 5 5 7.5 7.5 10 15 -

1 1.5 3 5 5 5 7.5 7.5 10 15 15 15 25 30 50 -

2 3 7.5 7.5 10 15 20 25 25 30 40 50 75 75 100 150

2 3 5 7.5 10 7.5 10 10 15 15 20 25 30 30 40 50 60 75 100 125 150

5 7.5 10 15 20 15 20 25 30 30 40 50 60 60 75 100 125 150 200 250 300

10 15 20 25 15 20 25 30 40 30 40 50 60 75 60 75 100 125 150 200 250 300 -

Max. Amps

NEMA Size

8A 11A 17A

1

22A 28A 17A 22A 28A

2

34A 42A 34A 42A 56A

3

68A 80A 68A 80A 4 104A 136A 125A 156A 150A 221A 200A 248A 250A 312A 300A 361A

5

5+

Wt. (lbs)

Description

46 46 46 46 46 46 46 46 46 50 50 50 50 50 50 50 50 50 66 66 66 66 66 66 66 66 66 85 85 85 85 85 85 240 240 240 240 240 240 382 382 382 382

N3R IPS, S1, 8A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 11A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 11A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 17A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 17A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 22A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 22A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 28A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 28A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 17A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 22A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 22A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 28A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 28A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 34A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 34A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 42A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 42A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S3, 34A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 42A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 42A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 56A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 56A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 68A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 68A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S3, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 68A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S4, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 104A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S4, 104A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 136A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S5, 125A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 156A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5, 150A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 221A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5, 200A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 248A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5, 250A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5P, 312A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5P, 300A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5P, 361A w/ SCM, MCCB Disc, HOA, 200 VA CPT

* Note: The shaded figures represent the maximum horsepower for corresponding NEMA size rating.

7

Intelligent Pump Starter (IPS)

IPS IPS Accessories Model No.

Wt. (lbs)

Description

0.5

Data and Fault Logging with Date/Time Stamp, Ethernet Output

IPS-LTA

1

Lightning/Surge Arrestor

IPS-SPB

1

Start Push button Control (Door Mounted)

IPS-STSP

1

Start/Stop Push button Control (Door Mounted)

IPS-TMR

0

Programmable Timer Functions: Backspin, On Delay

IPS-ENET

IPS Dimensions Starter Size

H

W

D

Size 1, Size 2

22

15

10

Size 3, Size 4

32

15

10

Size 5

42

30

12

Size 5+

48

36

16

Description

UL/NEMA 3R Enclosure

*All measurements in inches

W

H

D

8

D

Intelligent Pump Starter (IPS)

IPS Wiring Diagram

SCM PCB Common

DRY INPUTS

See Table 1

Hand Auto Status

RELAY OUTPUTS

Common Fault Auto Run

Auto Run CAT 5 Input

VOLTAGE INPUTS Shut Down Motor

ACTUATOR CONTROL

A1

M

12-120VAC/DC Input

Limit Switch

120VAC, 0.25A Output

Normally Open Input

Common

A2

To Auto Run

N

X2 X1 120V

CPT

208V 240V 480V

TRANSFORMER PRIMARY CIRCUIT BREAKER SIZING V 208/230

VA 50VA 100VA

480

N/A 2A

N/A 1A

TABLE 1 H1

H4

L1

L2

HOA SWITCH

L3

Common

OFF H

Hand

MCCB

A

X X

Auto

A

B

C

X

HOA SWITCH / START OFF

OL

CAT 5 Output H4

H1

H

Common

X

START / STOP

14 22

T3

START

Auto

M

T2

X

Hand 13 21

T1

A

STOP

Common

Hand

M

START

Auto

3PH

SCHM-IPS3R/C-V2

9

Intelligent Pump Starter (IPS)

IPS IPS Specifications Starter Type Intelligent Pump Starter Combination, Service Rated UL Type 3R

User Interface Hand-Off-Auto Keypad with LEDs

Internal

Hand-Off-Auto Switch

Door mounted

Standard Control Operations Inputs Voltage Auto Run Shutdown

Apply 10 - 130 VAC/DC to energize Apply 10 - 130 VAC/DC to energize

Actuator position switch

N.O. dry contact closure

Dry Auto

N.O. dry contact closure

Outputs Run Status

N.O., 0.3 A@125 VAC; 1 A@24 VAC

Fault relay

N.O., 0.3 A@125 VAC; 1 A@24 VAC

Actuator motor control

120VAC, 0.25A max

Operational Overload Type Electronic; I2t Thermal Trip Curve Power fail mode

Restart last mode, no delay (default) Restart with delay Restart Off - LED flashes last mode

On/Off Time Delay

Programmable, selectable from 0.1 to 99 seconds

Environmental Ambient Operating Temp

-5 to 140 °F (-20 to 60 °C)

Ambient Storage Temp

-5 to 185 °F (-20 to 85 °C)

Relative Humidity

5% to 95% non-condensing

Protective Functions Current Setting: 1-95 A Trip Class: 5-30 (10 default) Reset: Automatic/Manual (manual default)

Overload

Warm Start Provision Delays restart based on calculated motor temperature when enabled Locked Rotor / Stall Trip within 0.5s Ground Fault (UL1053) Current Setting: 1.0-9.9A (1.0A default) Current Phase Unbalance Setting: 1-50% (20% default) Over/Under Voltage Setting: +/- 5-25% (5% default) Voltage Phase Unbalance Setting: 1-20% (3% default) Voltage Phase Loss Setting: 1-50% (5% default) Phase Sequence Trip in 0.1s when enabled Under Power

10

Setting: 0-99% of nominal hp (20% Default)

Over Power

Setting: 101-200% of nominal hp (125% Default)

Cycle Fault

Trip if cycle rate exceeds 1200 starts per hour

STANDARD PUMP STARTER (SPS)

SPS

STANDARD PUMP STARTER

50/60 Hz, 1Ø & 3Ø, 120~600 VAC, 1–250 hp Service rated circuit breaker disconnect Adjustable overload with phase loss protection

SUPERIOR PROTECTION, PROVEN RELIABILITY Rugged construction provides dependable operation • Simple and functional control with heavy duty HOA switch • Powder coated metal Type 3R enclosure available with optional pole mounting straps • Ample space for adding additional controls Main circuit breaker disconnect rated for service entrance • UL 489 circuit breaker provides branch and short circuit protection • No fuses required – save time and money • Lockable handle for safety • UL listed for use as service equipment Reliable components ensure long life • 2.5 million contactor electrical cycles at full rated current • Contactor includes standard 1 N.O. and 1 N.C. auxiliary contacts • NEMA size rated, available in NEMA sizes 1-5

Thermal overload motor protection • Differential phase failure protection • Ambient temperature compensated: 41 ºF - 104 ºF (5 ºC to 40 ºC) • Reset push button on door eliminates the need to access panel interior

NEMA Standard control transformer (CPT) offers flexibility • Multi-tap CPT input accepts all common motor voltages • Integrated secondary protection – no fuses required • 120 V control power available for additional field installed devices

11

STANDARD PUMP STARTER (SPS)

SPS Standard Pump Starter (Combination) UL/NEMA 3R Enclosures (Thermal Overload)

HP Model No.

Single-Phase

NEMA Size

Three-Phase

120 V

230 V

200 V

230 V

SPS3R-S1-K-G15-9

-

1

2

2

5

SPS3R-S1-K-G20-13

1/2

2

3

3

7.5

SPS3R-S1-K-G30-18

1

3

5

5

SPS3R-S2-K-G40-25

1.5

-

-

7.5

SPS3R-S2-K-G50-36

2

-

7.5

10

20

SPS3R-S2-K-G60-40

3

5

10

-

25

SPS3R-S2-K-G80-50

-

7.5

15

15

SPS3R-S3-K-G100-65

5

10

-

20

SPS3R-S3-K-G125-75

-

15

20

25

50

SPS3R-S3P-K-G150-85

7.5

-

25

30

60

SPS3R-S4-K-G200-125

10

-

40

40

75

SPS3R-S4-K-G250-150

-

-

40

50

100

SPS3R-S5-K-G300-180

-

-

60

60

125

SPS3R-S5-K-G400-240

-

-

75

75

150

SPS3R-S5P-K-G500-400

-

-

100

100

200

SPS3R-S5P-K-G600-400

-

-

125

125

250

Wt. (lbs)

Description

460 V 44

N3R SPS, S1, 9A w/ HOA, CB, TOL & CPT

44

N3R SPS, S1, 13A w/ HOA, CB, TOL & CPT

10

44

N3R SPS, S1, 18A w/ HOA, CB, TOL & CPT

15

48

N3R SPS, S2, 25A w/ HOA, CB, TOL & CPT

48

N3R SPS, S2, 36A w/ HOA, CB, TOL & CPT

48

N3R SPS, S2, 40A w/ HOA, CB, TOL & CPT

30

48

N3R SPS, S2, 50A w/ HOA, CB, TOL & CPT

40

64

N3R SPS, S3, 65A w/ HOA, CB, TOL & CPT

1

2

3 3+ 4 5 5+

64

N3R SPS, S3, 75A w/ HOA, CB, TOL & CPT

64

N3R SPS, S3P, 85A w/ HOA, CB, TOL & CPT

68

N3R SPS, S4, 125A w/ HOA, CB, TOL & CPT

68

N3R SPS, S4, 150A w/ HOA, CB, TOL & CPT

240

N3R SPS, S5, 180A w/ HOA, CB, TOL & CPT

240

N3R SPS, S5, 240A w/ HOA, CB, TOL & CPT

382

N3R SPS, S5P, 400A w/ HOA, CB, TOL & CPT

382

N3R SPS, S5P, 400A w/ HOA, CB, TOL & CPT

SPS Accessories Model No.

12

Wt. (lbs)

Description

SPS-24

0

24 VAC Control Circuit

SPS-3FC

1

Three Float Switch Input Terminals for Simplex Operation

SPS-BCN

1

Optional Top Mount Alarm Beacon Light, 120 VAC

SPS-BZR

1

Optional Door Mounted Buzzer, 120 VAC w/ Silence Push button

SPS-CLK-120V

1

Optional 7 Day, 24 Hr. Programmable Clock

SPS-CLK-24V

1

Optional 7 Day, 24 Hr. Programmable Clock

SPS-ENCL

1

Upgrade for S1 & S2 Panels to Larger 3R Enclosure, 32x15x8"

SPS-LTA

1

Lightning/Surge Arrestor

SPS-RLY-120VAC

1

Factory Installed 120 VAC Finder Interposing Run Relay

SPS-RLY-24VAC-DC

1

Factory Installed 24 VAC/VDC Finder Interposing Run Relay

SPS-RPL

1

Run Pilot Light

SPS-SPB

1

Start Push button

STANDARD PUMP STARTER (SPS)

SPS SPS Dimensions Starter Size

H

W

D

Size 1, Size 2

22

15

10

Size 3, Size 3+, Size 4

32

15

10

Size 5, Size 5+

42

30

12

W

Description

D

UL/NEMA 3R Enclosure

*All measurements in inches H

Wiring Diagram H1

H4 L2

480V

240V

208V

L1

CPT

L1

L2

MCCB H1

H2

MCCB H1

H2

M

N

120V

AUX CONT

OL T1

H

O

A

M AUX CONT

OL T1

T2

T3

OL A2

X00

95

START 00X

T3

L3

1

2

96

M

A1

MTR

MTR

SINGLE PHASE

THREE PHASE

13

STANDARD PUMP STARTER (SPS)

SPS SPS Specifications Starter Type Standard Pump Starter 3R Combination, Service Rated UL Type 3R Enclosure

User Interface HOA Selector Switch Reset Push Button

Standard Control Operations Auto Run Input

N.O. dry contact closure to energize starter

Environmental Ambient Operating Temp

-5 to 140 °F (-20 to 60 °C)

Ambient Storage Temp

-5 to 185 °F (-20 to 85 °C)

Relative Humidity

5% to 95% non-condensing

Protective Functions

14

Overload Type

Thermal bi-metallic

Trip Class

Class 10

Reset

Manual

Phase Loss

Differential overload protection

ECONOMY PUMP STARTER (EPS)

EPS

ECONOMY PUMP STARTER

50/60 Hz, 1Ø & 3Ø, 120~600VAC, 1-50 hp Wide range class 1-30 electronic overload HOA switch with run pilot light

DEPENDABLE PERFORMANCE COMES STANDARD Rugged construction provides dependable operation • Industrial HOA switch and LED run pilot light • NEMA rated contactor with 1N.O. & 1N.C. auxiliary contacts • Ample space for adding additional controls Reliable components ensure long life • 2.5 Million contactor electrical cycles at full rated current • Contactor includes standard 1 N.O. and 1 N.C. auxiliary contacts • NEMA Size rated, available in NEMA sizes 1-3 Adjustable electronic overload • Class 1-30 overload • Advanced protective features include phase loss, imbalance, stall protection and manual reset Standard control transformer (CPT) offers flexibility • Multi-tap CPT input accepts all common motor voltages • Integrated secondary protection – no fuses required • 120 V control power available for additional field installed devices

NEMA

15

ECONOMY PUMP STARTER (EPS)

EPS Economy Pump Starters (Non-Combination) UL/NEMA Type 1, 3R, 4, and 4X Fiberglass Enclosures (Electronic Overload) HP Enclosure Type

Model #

UL/NEMA Type 1 UL/NEMA Type 3R UL/NEMA Type 4 UL/NEMA Type 4X Fiberglass

Three Phase

NEMA SIZE

WT (lbs)

Description

120V

230V

200V

230V

460V

1/6

1/2

1

1.5

3

00

14

N1 EPS, S00, 5A w/ RPL, HOA, EOL & CPT

EPS1-18-J-22

1

3

3

5

10

0

14

N1 EPS, S0, 22A w/ RPL, HOA, EOL & CPT

EPS1-32-J-22

1

3

5

7.5

15

1

14

N1 EPS, S1, 22A w/ RPL, HOA, EOL & CPT

EPS1-32-J-40

2

5

7.5

10

20

1

14

N1 EPS, S1, 40A w/ RPL, HOA, EOL & CPT

EPS1-50-J-40

3

7.5

10

10

30

2

15

N1 EPS, S2, 40A w/ RPL, HOA, EOL & CPT

EPS1-50-J-80

3

10

15

15

30

2

15

N1 EPS, S2, 80A w/ RPL, HOA, EOL & CPT

EPS1-85-J-80

7.5

15

20

25

50

3

27

N1 EPS, S3, 80A w/ RPL, HOA, EOL & CPT

EPS3R-9-J-5

EPS1-9-J-5

16

Single Phase

1/6

1/2

1

1.5

3

00

27

N3R EPS, S00, 5A w/ RPL, HOA, EOL & CPT

EPS3R-18-J-22

1

3

3

5

10

0

27

N3R EPS, S0, 22A w/ RPL, HOA, EOL & CPT

EPS3R-32-J-22

1

3

5

7.5

15

1

27

N3R EPS, S1, 22A w/ RPL, HOA, EOL & CPT

EPS3R-32-J-40

2

5

7.5

10

20

1

27

N3R EPS, S1, 40A w/ RPL, HOA, EOL & CPT

EPS3R-50-J-40

3

7.5

10

10

30

2

29

N3R EPS, S2, 40A w/ RPL, HOA, EOL & CPT

EPS3R-50-J-80

3

10

15

15

30

2

29

N3R EPS, S2, 80A w/ RPL, HOA, EOL & CPT

EPS3R-85-J-80

7.5

15

20

25

50

3

33

N3R EPS, S3, 80A w/ RPL, HOA, EOL & CPT

EPS4-9-J-5

1/6

1/2

1

1.5

3

00

15

N4 EPS, S00, 5A w/ RPL, HOA, EOL & CPT

EPS4-18-J-22

1

3

3

5

10

0

15

N4 EPS, S0, 22A w/ RPL, HOA, EOL & CPT

EPS4-32-J-22

1

3

5

7.5

15

1

15

N4 EPS, S1, 22A w/ RPL, HOA, EOL & CPT

EPS4-32-J-40

2

5

7.5

10

20

1

15

N4 EPS, S1, 40A w/ RPL, HOA, EOL & CPT

EPS4-50-J-40

3

7.5

10

10

30

2

19

N4 EPS, S2, 40A w/ RPL, HOA, EOL & CPT

EPS4-50-J-80

3

10

15

15

30

2

19

N4 EPS, S2, 80A w/ RPL, HOA, EOL & CPT

EPS4-85-J-80

7.5

15

20

25

50

3

26

N4 EPS, S3, 80A w/ RPL, HOA, EOL & CPT

EPS4XF-9-J-5

1/6

1/2

1

1.5

3

00

14

N4XF, EPS, S00, 5A w/ RPL, HOA, EOL, CPT

EPS4XF-18-J-22

1

3

3

5

10

0

14

N4XF, EPS, S0, 22A w/ RPL, HOA, EOL, CPT

EPS4XF-32-J-40

2

5

7.5

10

20

1

14

N4XF, EPS, S1, 40A w/ RPL, HOA, EOL, CPT

EPS4XF-50-J-80

3

10

15

15

30

2

16

N4XF, EPS, S2, 80A w/ RPL, HOA, EOL, CPT

EPS4XF-85-J-90

7.5

15

20

25

50

3

23

N4XF, EPS, S3, 90A w/ RPL, HOA, EOL, CPT

16

ECONOMY PUMP STARTER (EPS)

EPS EPS Dimensions D

15.7 7.5 6.1

EPS3R-9 to EPS3R-85

16

12

8

EPS4-9 to EPS4-32

10

8

6.2

EPS4-50

12

10

6

EPS4-85

14

12

6.5

EPS4XF-9 to EPS4XF-18

12

10

6

EPS4XF-32 to EPS4XF-85 14

12

6.2

Description

H1

H4

UL/NEMA 1 Enclosure UL/NEMA 3R Enclosure

TRANSFORMER PRIMARY CIRCUIT BREAKER SIZING V 208/230

VA

50VA 100VA

UL/NEMA 4 Enclosure

N/A 2A

480 N/A 1A

3

4

5 480V

EPS1-9 to EPS1-32

W

240V

H

208V

Starter Size

Wiring Diagram

CPT UL/NEMA 4X Fiberglass Enclosure

H2 *

120V

N EOL

*All measurements in inches

A2

A1

G H

O

A

EOL

X00

W

95

D

A2

M

96

A1

START 00X L1

2

1

L1

L2

H H1

H1

H4

L2

L3

H4 M

M AUX CONT

AUX CONT

EOL

EOL T1

T3

MTR NON COMB. 1-PHASE

*H2 Terminal does not apply for Type 1 enclosed configurations

T1

T2

T3

MTR NON COMB. 3-PHASE SCHM-EPS-V1

17

ECONOMY PUMP STARTER (EPS)

EPS EPS Specifications Starter Type Economy Pump Starter UL/NEMA Type 1, 3R, 4, and 4X Enclosure

User Interface HOA Selector switch with Run pilot light

Standard Control Operations Inputs Dry Auto Run

N.O. dry contact closure to energize starter

Mechanical Enclosure types

UL/NEMA Type 1, 3R, 4, or 4X

Environmental Ambient Operating Temp

-5° to 140° F (-20° to 60° C)

Ambient Storage Temp

-5° to 185° F (-20° to 85° C)

Relative Humidity

5% to 95% non-condensing

Protective Functions

18

Overload Type

Electronic; l²t Thermal Trip Curve

Current Setting Range

Class 1-30

Trip Class

Manual

Reset

Differential overload protection

Phase Unbalance

Trip within 3 seconds @ 70% unbalance

Phase Loss

Trip within 3 seconds

Stall Condition

Trip within 3 seconds @ 170% FLA

ADVANCED DUPLEX PUMP CONTROLLER (APX)

AP

ADVANCED DUPLEX PUMP CONTROLLER

50/60 Hz, 1Ø & 3Ø, 115~600 VAC, 1–200 hp HOA switches for independent local or remote operation Wide range electronic class 1-30 overload Advanced Lead/Lag & Alternating Operation • HOA switches for independent local or remote operation



• Automatic alternating control





• Wide range electronic class 1-30 overload with advanced protective features including phase loss, imbalance, stall protection, and manual reset









• Combination versions include a Circuit Breaker service disconnect which provides short circuit protection • Dual run pilot lights indicate motor operation



• Flexible control for 3-5 float switches









• Door-mounted alarm pilot light indicates high level alarm and float switch failure (identifies specific float number)



• Adjustable lag start delay and alternation settings

NEMA



19

AP Advanced Duplex Pump Controllers (Non-Combination) UL/NEMA 4 and 4X Fiberglass Enclosures (HOA & Electronic Overload) HP

UL/NEMA Type 4X Fiberglass

UL/NEMA Type 4

Enclosure Type

Model No.

Single-Phase 120 V

230 V

Three-Phase 200 V

230 V

460 V

575 V

SCIC KAIC @ 460 V

NEMA Size

Wt. (lbs)

Description

APX4-9-J-5

-

1/2

1

1.5

3

3

5

00

72

N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-18-J-22

1

3

5

5

10

15

5

0

72

N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-32-J-22

1.5

3

5

7.5

15

20

5

1

72

N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-32-J-40

2

5

7.5

10

20

25

5

1

72

N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-50-J-40

3

7.5

10

10

25

30

5

2

81

N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-50-J-80

3

10

20

20

40

50

5

2

81

N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-85-J-80

5

15

30

40

60

60

10

3

90

N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-9-J-5

-

1/2

1

1.5

3

3

5

00

53

N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-18-J-22

1

3

5

5

10

15

5

0

53

N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-32-J-22

1.5

3

5

7.5

15

20

5

1

53

N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-32-J-40

2

5

7.5

10

20

25

5

1

53

N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-50-J-40

3

7.5

10

10

25

30

5

2

41

N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-50-J-80

3

10

20

20

40

50

5

2

41

N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-85-J-80

5

15

30

40

60

60

10

3

61

N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT

Advanced Duplex Pump Controllers (Combination) UL/NEMA 4 and 4X Fiberglass Enclosures (HOA & Electronic Overload) HP

UL/NEMA Type 4

Enclosure Type

Model No.

120 V

230 V

APX4-9-J-G1.6-5

-

1/10

APX4-9-J-G2.5-5

-

1/6

UL/NEMA Type 4X Fiberglass

Three-Phase 200 V

NEMA Size

Wt. (lbs)

Description

230 V

460V

575 V

-

-

3/4

3/4

65

00

75

N4 Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT

1/2

1/2

1

1.5

65

00

75

N4 Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-9-J-G4-5

1/8

1/3

3/4

3/4

2

3

65

00

75

N4 Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-9-J-G6-5

1/4

1/2

1

1.5

3

3

65

00

75

N4 Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-18-J-G20-22

1/3

1

2

2

5

5

65

0

75

N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-18-J-G30-22

1/2

2

3

3

7.5

10

65

0

75

N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-18-J-G50-22

1

3

3

5

10

15

30

0

75

N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-32-J-G60-40

1.5

3

5

7.5

15

20

30

1

75

N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-32-J-G80-40

2

5

7.5

10

20

25

30

1

75

N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-50-J-G100-40

3

7.5

10

10

30

30

50

2

83

N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-50-J-G125-80

3

10

15

15

30

40

50

2

83

N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-85-J-G160-80

5

10

20

20

40

50

50

3

95

N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT

APX4-85-J-G200-80

5

15

20

25

50

60

50

3

95

N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-9-J-G1.6-5

-

1/10

-

-

3/4

3/4

65

00

56

N4 FG Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-9-J-G2.5-5

20

Single-Phase

SCIC KAIC @ 460 V

APXF-9-J-G4-5

-

1/6

1/2

1/2

1

1.5

65

00

56

N4 FG Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT

1/8

1/3

3/4

3/4

2

3

65

00

56

N4 FG Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-9-J-G6-5

1/4

1/2

1

1.5

3

3

65

00

56

N4 FG Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-18-J-G20-22

1/3

1

2

2

5

5

65

0

56

N4 FG Duplex Starter w/ CB Disc L ead-Lag, Alt, 4FSw, PLC & CPT

APXF-18-J-G30-22

1/2

2

3

3

7.5

10

65

0

56

N4 FG Duplex Starter w/ CB Disc L ead-Lag, Alt, 4FSw, PLC & CPT

APXF-18-J-G50-22

1

3

3

5

10

15

30

0

56

N4 FG Duplex Starter w/ CB Disc L ead-Lag, Alt, 4FSw, PLC & CPT

APXF-32-J-G60-40

1.5

3

5

7.5

15

20

30

1

56

N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-32-J-G80-40

2

5

7.5

10

20

25

30

1

56

N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-50-J-G100-40

3

7.5

10

10

30

30

50

2

64

N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-50-J-G125-80

3

10

15

15

30

40

50

2

64

N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-85-J-G160-80

5

10

20

20

40

50

50

3

66

N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT

APXF-85-J-G200-80

5

15

20

25

50

60

50

3

66

N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT

ADVANCED DUPLEX PUMP CONTROLLER (APX)

AP APX Accessories Model No. APX-BCN

Wt. (lbs)

Description

1

Optional Top Mount Alarm Beacon Light, 120 VAC

APX-BZR

1

Optional Door Mounted Buzzer, 120 VAC w/ Silence Push button

APX-DHM

1

Optional Digital Hour Meters (2), 120 VAC

APX-FPL

1

Door Mounted Fault Pilot Lights

APX-GFCI

1

15A GFCI Option

APX-HRN

1

Optional Door Mounted Horn, 120 VAC w/ Silence Push button

APX-LSR

1

Optional Leak Seal Relays (2), 120 VAC

APX-RST

1

Door Mounted Overload Reset Push buttons

APX-STR

1

Optional Leak Seal Relays (2), High Temp, 120 VAC

APX Dimensions Starter Size

H

W

D

APX4-9 to APX4-32

24

20

8

APX4-40 to APX4-50

30

24

8

APX4-85

30

24

12

APX4-9-G to APX4-32-G

24

20

8

APX4-40-G to APX4-50-G

30

24

8

APX4-85-G

30

24

12

APXF-9 to APXF-50

24

20

8

APXF-85

30

24

10

APXF-9-G to APXF-32-G

24

20

8

APXF-50-G

30

24

10

APXF-85-G

30

24

10

Description UL/NEMA 4 Enclosure

W

D

UL/NEMA 4 Enclosure Combination UL/NEMA 4 Fiberglass Enclosure

H

UL/NEMA 4 Fiberglass Enclosure Combination

*All measurements in inches

21

AP Wiring Diagram

22

ADVANCED DUPLEX PUMP CONTROLLER (APX)

DUPLEX ALTERNATING PUMP CONTROLLER (DPX)

DUPLEX ALTERNATING PUMP CONTROLLER 50/60 Hz, 1Ø & 3Ø, 115~600 VAC, 1–200 hp Manual Pump Selection Switch Wide range electronic class 1-30 overload

ALTERNATING CONTROL TO EXTEND MOTOR LIFE • HOA switch and manual pump selection switch for flexible operation • Optional alternating control by relay, 24-hour timer, or 7-day clock • Wide range electronic class 1-30 overload with advanced protective features including phase loss, imbalance, stall protection, and manual reset • Combination versions include a MCP or MCCB disconnect which provides short circuit protection

NEMA

23

DUPLEX ALTERNATING PUMP CONTROLLER (DPX)

Duplex Alternating Pump Controllers (Non-Combination) UL/NEMA 4 and 4X Fiberglass Enclosures (HOA & Electronic Overload)

120 V

230 V

200 V

230 V

460 V

575 V

SCIC KAIC @ 460 V

UL/NEMA Type 4

DPX4-9-J-5 DPX4-18-J-22 DPX4-32-J-22 DPX4-32-J-40 DPX4-50-J-40 DPX4-50-J-80 DPX4-85-J-80

1 1.5 2 3 3 5

1/2 3 3 5 7.5 10 15

1 5 5 7.5 10 20 30

1.5 5 7.5 10 10 20 40

3 10 15 20 25 40 60

3 15 20 25 30 50 60

5 5 5 5 5 5 10

00 0 1 1 2 2 3

30 30 30 30 48 48 53

N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT

UL/NEMA Type 4X Fiberglass

HP

DPXF-9-J-5 DPXF-18-J-22 DPXF-32-J-22 DPXF-32-J-40 DPXF-50-J-40 DPXF-50-J-80 DPXF-85-J-80

1 1.5 2 3 3 5

1/2 3 3 5 7.5 10 15

1 5 5 7.5 10 20 30

1.5 5 7.5 10 10 20 40

3 10 15 20 25 40 60

3 15 20 25 30 50 60

5 5 5 5 5 5 10

00 0 1 1 2 2 3

26 26 26 43 43 43 50

N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT

NEMA Size

Wt. (lbs)

Description

Enclosure Type

Model No.

Single-Phase

Three-Phase

NEMA Size

Wt. (lbs)

Description

Duplex Alternating Pump Controllers (Combination) UL/NEMA 4 and 4X Fiberglass Enclosures (HOA & Electronic Overload)

24

Model No.

120 V

230 V

200 V

230 V

460 V

575 V

SCIC KAIC @ 460 V

UL/NEMA Type 4

DPX4-9-J-G1.6-5 DPX4-9-J-G2.5-5 DPX4-9-J-G4-5 DPX4-9-J-G6-5 DPX4-18-J-G8-22 DPX4-18-J-G10-22 DPX4-18-J-G13-22 DPX4-18-J-G17-22 DPX4-32-J-G22-40 DPX4-32-J-G26-40 DPX4-32-J-G32-40 DPX4-50-J-G40-40 DPX4-50-J-G50-80 DPX4-85-J-G63-80 DPX4-85-J-G75-80

1/8 1/4 1/3 1/2 1/2 1 1.5 2 2 3 3 5 5

1/10 1/6 1/3 1/2 1 1.5 2 3 3 3 5 7.5 10 10 15

1/2 3/4 1 2 2 3 3 5 7.5 7.5 10 15 20 20

1/2 3/4 1.5 2 3 3 5 7.5 7.5 10 10 15 20 25

3/4 1 2 3 5 5 7.5 10 15 15 20 30 30 40 50

3/4 1.5 3 3 5 7.5 10 15 20 20 25 30 40 50 60

65 65 65 65 65 65 65 30 30 30 30 50 50 50 50

00 00 00 00 0 0 0 0 1 1 1 2 2 3 3

36 36 36 36 36 36 36 36 36 36 36 50 50 58 58

N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT

UL/NEMA Type 4X Fiberglass

HP Enclosure Type

DPXF-9-J-G1.6-5 DPXF-9-J-G2.5-5 DPXF-9-J-G4-5 DPXF-9-J-G6-5 DPXF-18-J-G8-22 DPXF-18-J-G10-22 DPXF-18-J-G13-22 DPXF-18-J-G17-22 DPXF-32-J-G22-40 DPXF-32-J-G26-40 DPXF-32-J-G32-40 DPXF-50-J-G40-40 DPXF-50-J-G50-80 DPXF-85-J-G63-80 DPXF-85-J-G75-80

1/8 1/4 1/3 1/2 1/2 1 1.5 2 2 3 3 5 5

1/10 1/6 1/3 1/2 1 1.5 2 3 3 3 5 7.5 10 10 15

1/2 3/4 1 2 2 3 3 5 7.5 7.5 10 15 20 20

1/2 3/4 1.5 2 3 3 5 7.5 7.5 10 10 15 20 25

3/4 1 2 3 5 5 7.5 10 15 15 20 30 30 40 50

3/4 1.5 3 3 5 7.5 10 15 20 20 25 30 40 50 60

65 65 65 65 65 65 65 30 30 30 30 50 50 50 50

00 00 00 00 0 0 0 0 1 1 1 2 2 3 3

28 28 28 28 28 28 28 28 28 28 28 40 40 46 46

N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT

Single-Phase

Three-Phase

DUPLEX ALTERNATING PUMP CONTROLLER (DPX)

DPX Accessories Model No.

Wt. (lbs)

Description

DPX-ALT

1

Optional Automatic Alternating Relay

DPX-CLK

1

Optional 7 Day, 24 Hr. Programmable Clock

DPX-FPL

1

Door Mounted Fault Pilot Lights

DPX-TMR

1

Optional Alternating 24 Hr. Timer

DPX Dimensions Starter Size

H

W

D

DPX(4/F)-9

14

12

6

DPX(4/F)-18

14

12

6

DPX(4/F)-32

14

12

6

DPX(4/F)-50

16

14

8

DPX(4/F)-85

16

14

8

DPX(4/F)-9-G

16

14

8

DPX(4/F)-18-G

16

14

8

DPX(4/F)-32-G

16

14

8

DPX(4/F)4-50-G

20

16

10

DPX(4/F)-85-G

20

16

10

Description W

D

UL/NEMA 4 OR 4X Fiberglass Enclosure

H UL/NEMA 4 OR 4X Fiberglass Enclosure w/ Disconnect

*All measurements in inches

25

DUPLEX ALTERNATING PUMP CONTROLLER (DPX)

Wiring Diagram

26

DIGITAL SOFT STARTER (MS6)

DIGITAL SOFT STARTER 50/60 Hz, 50-1000 hp, 200~600 VAC Optional Bypass Versions

HEAVY-DUTY RATED SOFT STARTER FOR PUMP APPLICATIONS

Keypad and LCD display for easy starter setup, status and diagnostics • Soft stop, up-to-speed contact, shorted SCR detection and line/load lugs standard with each unit • Enclosed models include control power transformer • 120 VAC control inputs for: Start/Stop/Jog/Reverse/Reset/Enable • Two or three wire control allow for remote operation options • Dry contact relay outputs for: Fault/Bypass/Running/Reverse

Operation & features • Provides smooth current ramp output to motor, eliminating surges and equipment shock • Adjustable ramp setting ranges (Up/Down 0-60 seconds) • Dual operation modes to match application needs: Constant Current mode for light duty or limited power supplies and Current Ramp mode for high inertia or heavy loads • Jog speeds: Forward at 14% of full speed, Reverse at 20% of full speed • DC injection braking option for enhanced performance

NEMA

Protective functions • Class 10~30 adjustable electronic overload • 500% overload for 30 seconds guarantees heavy duty operation • Single-phase protection • Instantaneous over-current trip • Shorted SCR fault output

Integrated bypass rated for emergency starts • Reduces enclosure size and eliminates need for additional cooling • Ensures reliable operation with automatic transition to bypass contactor at full speed • Eliminates downtime in critical applications

27

DIGITAL SOFT STARTER (MS6)

Digital Soft Starters (Standard Chassis) Model No.

HP

Wt. (lbs)

Description

30

30

MS6 Standard Chassis Soft Start, 30 A

50

30

MS6 Standard Chassis Soft Start, 50 A

230 V

460 V

575 V

MS6-30-CH

10

20

MS6-50-CH

20

40

MS6-80-CH

30

60

75

30

MS6 Standard Chassis Soft Start, 80 A

MS6-125-CH

50

100

125

40

MS6 Standard Chassis Soft Start, 125 A

MS6-250-CH

100

200

250

40

MS6 Standard Chassis Soft Start, 250 A

MS6-420-CH

150

350

400

50

MS6 Standard Chassis Soft Start, 420 A MS6 Standard Chassis Soft Start, 500 A

MS6-500-CH

200

400

500

93

MS6-600-CH

250

500

600

93

MS6 Standard Chassis Soft Start, 600 A

MS6-800-CH

300

600

800

125

MS6 Standard Chassis Soft Start, 800 A

MS6-1000-CH

400

800

1000

125

MS6 Standard Chassis Soft Start, 1000 A

Digital Soft Starters (Standard Chassis with Bypass Contactor) Model No.

HP 230 V

460 V

575 V

Wt. (lbs)

Description

MS6B-30-CH

10

20

30

30

MS6 Standard Chassis Soft Start with Bypass, 30 A

MS6B-50-CH

20

40

50

30

MS6 Standard Chassis Soft Start with Bypass, 50 A

MS6B-80-CH

30

60

75

30

MS6 Standard Chassis Soft Start with Bypass, 80 A

MS6B-125-CH

50

100

125

60

MS6 Standard Chassis Soft Start with Bypass, 125 A

MS6B-250-CH

100

200

250

60

MS6 Standard Chassis Soft Start with Bypass, 250 A

MS6B-420-CH

150

350

400

75

MS6 Standard Chassis Soft Start with Bypass, 420 A

MS6B-500-CH

200

400

500

140

MS6 Standard Chassis Soft Start with Bypass, 500 A

MS6B-600-CH

250

500

600

140

MS6 Standard Chassis Soft Start with Bypass, 600 A

MS6B-800-CH

300

600

800

188

MS6 Standard Chassis Soft Start with Bypass, 800 A

MS6B-1000-CH

400

800

1000

188

MS6 Standard Chassis Soft Start with Bypass, 1000 A

Digital Soft Starters (Enclosed) UL/NEMA 4 Enclosures Model No.

28

HP

Wt. (lbs)

Description

20

82.5

N4 Soft Start, 20 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

40

82.5

N4 Soft Start, 40 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

25

50

201

N4 Soft Start, 50 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

30

60

201

N4 Soft Start, 60 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

40

75

315

N4 Soft Start, 75 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

50

100

362

N4 Soft Start, 100 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

C4-SFS125GXX-J-PMP

60

125

361

N4 Soft Start, 125 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

C4-SFS150GXX-J-PMP

75

150

361

N4 Soft Start, 150 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

C4-SFS200GXX-J-PMP

100

200

361

N4 Soft Start, 200 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

C4-SFS300GXX-J-PMP

125

300

535

N4 Soft Start, 300 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

C4-SFS350GXX-J-PMP

150

350

605

N4 Soft Start, 350 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

C4-SFS400GXX-J-PMP

200

400

655

N4 Soft Start, 400 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

C4-SFS500GXX-J-PMP

250

500

655

N4 Soft Start, 500 HP, 460/3/60 w/ CB Disc, HOA, Pump Version

230 V

460 V

C4-SFS020GXX-J-PMP

-

C4-SFS040GXX-J-PMP

20

C4-SFS050GXX-J-PMP C4-SFS060GXX-J-PMP C4-SFS075GXX-J-PMP C4-SFS100GXX-J-PMP

DIGITAL SOFT STARTER (MS6)

MS6 Dimensions Starter Size

H

W

D

MS6-30-CH to MS6-80-CH

17

12

10.5

MS6-125-CH to MS6-250-CH

15

15

11.5

MS6-420-CH

19.5

15

11.5

MS6-500-CH to MS6-600-CH

19.5

18

13

MS6-800-CH to MS6-1000-CH

27

24

15

MS6B-30-CH

17

12

10.5

MS6B-50-CH to MS6-80-CH

21

12

10.5

20.5

15

11.5

MS6B-420-CH

27

15

11.5

MS6B-500-CH to MS6B-600-CH

27

18

13

MS6B-800-CH

35

24

15

MS6B-1000-CH

35

24

16

C4/SFS040GXX-J-PMP

24

20

10

C4-SFS050GXX-J-PMP to C4-SFS060GXX-J-PMP

36

24

16

C4-SFS075GXX-J-PMP

36

30

16

C4-SFS100GXX-J-PMP to C4-SFS200GXX-J-PMP

48

36

16

C4/SFS300GXX-J-PMP to C4-SFS350GXX-J-PMP

60

36

16

C4-SFS400GXX-J-PMP to C4-SFS500GXX-J-PMP

72

36

16

MS6B-125-CH to MS6B-250-CH

Description

Standard Chassis

Standard Chassis w/ Bypass Contactor

UL/NEMA 4 Enclosure

*All measurements in inches

W

D

H

29

DIGITAL SOFT STARTER (MS6)

Wiring Diagram

30

ANALOG SOFT STARTER (RVS)

RVS

ANALOG SOFT STARTER

50/60 Hz, 2-125 hp, 200~600 VAC Integrated electronic overload Bypass standard

EXTEND EQUIPMENT LIFE & REDUCE PEAK CURRENT DEMAND Standard features • Compact, space saving soft start with integrated electronic overload • Standard, built-in bypass • Aluminum chassis design ensures cool and efficient operation • Powder coated metal type 3R enclosure available • Integrated LED display and control terminals • Rated for line or inside delta motor connections

Comprehensive motor protection • Current limiting and integrated phase loss • Starter over-temperature shut down with reset push button • Metal Oxide Varistors (MOV) protect SCRs from damaging surges

NEMA

Easy setup & operation • LED display modes include: On, ramp up/down, run, overload, phase loss, over-temp • Simple dial adjustments for: motor FLA, initial voltage, current limit, ramp up/down times • Adjustable ramp setting ranges (up/down 0-30 seconds) • End of acceleration relay (1 N.O. contact) • Fault output relay (1 N.O. contact) • Auxiliary relays

31

ANALOG SOFT STARTER (RVS)

RVS Analog Soft Starters (Standard Chassis) HP Model No.

Three-Phase

Wt. (lbs)

230 V

460 V

575 V

RVS-AX-8

2

5

7.5

RVS-AX-17

5

10

15

RVS-AX-31

10

20

30

RVS-AX-58

20

40

50

RVS-AX-72

25

50

60

RVS-AX-85

30

60

75

RVS-AX-105

40

75

100

RVS-AX-145

50

100

125

RVS-AX-170

60

125

150

Description RVS Standard Chassis Soft Start, 8A

5.74

RVS Standard Chassis Soft Start, 17A RVS Standard Chassis Soft Start, 31A

11 18.5 26

RVS Standard Chassis Soft Start, 58A RVS Standard Chassis Soft Start, 72A RVS Standard Chassis Soft Start, 85A RVS Standard Chassis Soft Start, 105A RVS Standard Chassis Soft Start, 145A RVS Standard Chassis Soft Start, 170A

Analog Soft Starters (Enclosed) UL/NEMA 3R Enclosures (HOA)

HP Model No.

Three-Phase 230 V

Wt. (lbs)

575 V

C3R-SFS020GXX-J-PMP

10

20

C3R-SFS030GXX-J-PMP

15

30

C3R-SFS040GXX-J-PMP

20

40

C3R-SFS050GXX-J-PMP

25

50

C3R-SFS060GXX-J-PMP

30

60

C3R-SFS075GXX-J-PMP

40

75

C3R-SFS100GXX-J-PMP

50

100

C3R-SFS125GXX-J-PMP

60

125

32

Description

47

N3R Soft Start, 20 HP, 460/3/60 w/ CB Disc, HOA N3R Soft Start, 30 HP, 460/3/60 w/ CB Disc, HOA

52.1

N3R Soft Start, 40 HP, 460/3/60 w/ CB Disc, HOA N3R Soft Start, 50 HP, 460/3/60 w/ CB Disc, HOA

72 144

N3R Soft Start, 60 HP, 460/3/60 w/ CB Disc, HOA N3R Soft Start, 75 HP, 460/3/60 w/ CB Disc, HOA N3R Soft Start, 100 HP, 460/3/60 w/ CB Disc, HOA N3R Soft Start, 125 HP, 460/3/60 w/ CB Disc, HOA

ANALOG SOFT STARTER (RVS)

RVS RVS Dimensions Starter Size

H

W

D

RVS-AX-8 to RVS-AX-31

9.5

4.75

4.25

RVS-AX-58 to RVS-AX-72

11

5

7.5

RVS-AX-85 to RVS-AX-105

15

5

7.5

RVS-AX-145 to RVS-AX-170

15

7

8

C3R-SFS020GXX-J-PMP to C3R-SFS050GXX-J-PMP

22

15

8

C3R-SFS060GXX-J-PMP to C3R-SFS070GXX-J-PMP

32

15

8

C3R-SFS100GXX-J-PMP to C3R-SFS170GXX-J-PMP

30

24

12

Description

Standard Chassis

UL/NEMA 3R Enclosure

*All measurements in inches

W

D

H

33

RVS Wiring Diagram

34

ANALOG SOFT STARTER (RVS)

 Large Drive Variable Speed Control is Just the Beginning Franklin FastApp™ Firmware • Pre-configured for easy operation and optimal performance • PSI unit display • Sleep and wake up • Lubrication output with timer - Provides a relay to control a lubrication solenoid for hollow shaft pump • Broken pipe detection - Monitors pump speed and system pressure. If minimum pressure isn’t met while pumping at full speed, system will trip after adjustable delay time • Dry-well/Underload detection with cycling timer • Pipe fill (Pre-PID) - VFD ramps up to Pre-PID frequency and fills pipes without pressurizing system • VFD auto-de-rating phase conversion • Pre-heat for motor windings in damp environments

Variable Speed Control • Space vector control for efficiency and long motor life. Cleaner sine wave as compared to typical V/Hz control. Motors run cooler and last longer • Automatic energy savings mode • Adaptive flux control for varying loads (e.g. damper loading)

NEMA

• Flying start protection prevents trips, rough starts, and drive damage from regenerative power due to heavy fan inertia rotation • Flux braking algorithm reduces deceleration time for enhanced system efficiency • Pre-heater function protects motor and inverter from damage when installed in damp location (e.g. green house)

Standard Features (Enclosed Drives) • Automatic carrier frequency change (adjusts based on temperature for optimal operation) • Selectable V/F, sensorless vector control • For outdoor and/or wash down applications • Rainproof 3R enclosure reduces thermal absorbtion with white, solar reflective finish and filtered cooling fans • Standard enclosed VFD package is rated for 110º ambient temperature, non-direct sunlight. • Additional application-specific protective devices included (i.e. lightning surge arrestor, line reactors, load reactors, and dV/dT filter)

Internal keypad menu for easy operation • All control and protective functions are easily programmable • The 32-character backlit LCD screen displays operational status and parameter settings

35

P-SERIES LARGE DRIVE

P-SERIES 3R ENCLOSED

 Large Drive

Designed to withstand harsh environments

1

• 32 character keypad and pre-configured parameters for all common pump applications

2

3 4

1

5

7 6

Part Number Anatomy Part Family (Cerus Industrial Enclosed) Enclosure Rating (NEMA 3R) Pump Type (Centrifugal) Voltage Input Phase (1ø)

CIE3R-CENP050-P4/1 FE Reference Number Only VFD Model (P-Series) VFD Voltage Rating (460 V)

36

P-Series Pump Optimized VFD

2

Rugged outdoor 3R enclosure with cooling fans and filtration

3

Circuit breaker disconnect eliminates call backs due to fuse issues

4

Lightning arrestor protects VFD from large voltage spikes

5

Line reactor enhances protection from transient surges and provides a degree of harmonic mitigation

6

Control power transformer with breaker protection

7

Output filter for long motor leads

P-SERIES LARGE DRIVE

P-SERIES Ordering & Sizing Information P-Series (Enclosed) - Centrifugals Single-Phase & Three-Phase (200-230 V, 480 V) UL/NEMA 3R Enclosures Voltage

200-230 V

480 V

Model No.

HP

FLA

Wt. (lbs)

Description

CIE3R-CENP003-P2-1

3

12

179

N3R, 3 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP010-P2-1

10

32

202

N3R, 10 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP015-P2-1 (230V Only)

15

46

243

N3R, 15 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP020-P2-1 (230V Only)

20

60

268

N3R, 20 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP015-P2-3

15

60

202

N3R, 15 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP020-P2-3

20

74

207

N3R, 20 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP025-P2-3

25

88

243

N3R, 25 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP030-P2-3

30

115

268

N3R, 30 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP010-P4-1

10

16

197

N3R, 10 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP015-P4-1

15

24

219

N3R, 15 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP020-P4-1

20

30

245

N3R, 20 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP025-P4-1

25

39

279

N3R, 25 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP030-P4-1

30

45

279

N3R, 30 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP040-P4-1

40

55

289

N3R, 40 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP050-P4-1

50

75

366

N3R, 50 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP060-P4-1

60

91

368

N3R, 60 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP075-P4-1

75

110

1025

N3R, 75 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP100-P4-1

100

152

1060

N3R, 100 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP125-P4-1

125

183

1091

N3R, 125 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP150-P4-1

150

223

1746

N3R, 150 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP200-P4-1

200

264

1752

N3R, 200 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP015-P4-3

15

30

197

N3R, 15 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP020-P4-3

20

39

200

N3R, 20 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP025-P4-3

25

45

219

N3R, 25 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP030-P4-3

30

61

245

N3R, 30 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP040-P4-3

40

75

279

N3R, 40 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP050-P4-3

50

91

279

N3R, 50 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP060-P4-3

60

110

289

N3R, 60 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP075-P4-3

75

152

366

N3R, 75 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP100-P4-3

100

183

368

N3R, 100 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP125-P4-3

125

223

1007

N3R, 125 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP150-P4-3

150

264

1060

N3R, 150 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

CIE3R-CENP200-P4/3

200

325

1091

N3R, 200 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR

* Phase refers to incoming power, not motor.

Description Key

NOTE: The drive MUST BE sized according to the motor manufacturer’s maximum amperage draw. Upsize VFD for ambient temperature compensation (see VFD specs for temperature rating). (See Stand Alone drive section)

N3R

NEMA 3R Enclosure

1-Ph

Single-Phase

3-Ph

Three-Phase

† 600 V available upon request. Contact manufacturer for more details.

MCCB

Molded Case Circuit Breaker

LR

Line Reactor

OR

Output (Load) Reactor

OF

Output Filter

37

P-SERIES LARGE DRIVE

P-SERIES Ordering & Sizing Information P-Series (Enclosed) - Submersibles Single-Phase & Three-Phase (200-230 V, 480 V) UL/NEMA 3R Enclosures Voltage

Model No.

HP

FLA

Wt. (lbs)

Description

200-230 V

CIE3R-SUBP010-P2-1 (230 V Only) CIE3R-SUBP015-P2-1 (230 V Only) CIE3R-SUBP020-P2-1 (230 V Only) CIE3R-SUBP015-P2-3 CIE3R-SUBP020-P2-3 CIE3R-SUBP025-P2-3 CIE3R-SUBP030-P2-3

10 15 20 15 20 25 30

32 46 60 60 75 88 115

215 275 300 215 223 275 300

N3R, 10 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR, OR N3R, 15 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR, OR N3R, 20 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR, OR N3R, 15 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR, OR N3R, 20 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR, OR N3R, 25 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR, OR N3R, 30 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR, OR

CIE3R-SUBP010-P4-1 CIE3R-SUBP015-P4-1 CIE3R-SUBP020-P4-1 CIE3R-SUBP025-P4-1 CIE3R-SUBP030-P4-1 CIE3R-SUBP040-P4-1 CIE3R-SUBP050-P4-1 CIE3R-SUBP060-P4-1 CIE3R-SUBP075-P4-1 CIE3R-SUBP100-P4-1 CIE3R-SUBP125-P4-1 CIE3R-SUBP150-P4-1 CIE3R-SUBP200-P4-1 CIE3R-SUBP015-P4-3 CIE3R-SUBP020-P4-3 CIE3R-SUBP025-P4-3 CIE3R-SUBP030-P4-3 CIE3R-SUBP040-P4-3 CIE3R-SUBP050-P4-3 CIE3R-SUBP060-P4-3 CIE3R-SUBP075-P4-3 CIE3R-SUBP100-P4-3 CIE3R-SUBP125-P4-3 CIE3R-SUBP150-P4-3 CIE3R-SUBP200-P4-3

10 15 20 25 30 40 50 60 75 100 125 150 200 15 20 25 30 40 50 60 75 100 125 150 200

16 24 30 39 45 75 75 91 110 152 223 223 306 30 39 45 61 75 91 110 152 183 223 264 325

210 234 260 297 297 338 391 411 1068 1119 1156 1130 1476 212 215 238 263 297 304 332 409 427 1071 1130 1177

N3R, 10 hp, 460 V, 1-Ph Enclosed VFD, MCCB,LR,OF N3R, 15 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 20 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 25 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 30 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 40 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 50 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 60 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 75 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 100 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 125 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 150 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 200 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 15 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 20 hp, 460 V, 3-Ph Enclosed VFD, MCCB,LR,OF N3R, 25 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 30 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 40 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 50 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 60 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR N3R, 75 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 100 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 125 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 150 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 200 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF

480 V

* Phase refers to incoming power, not motor. NOTE: The drive MUST BE sized according to the motor manufacturer’s maximum amperage draw. Upsize VFD for ambient temperature compensation (see VFD specs for temperature rating). (See Stand Alone drive section) † 600 V available upon request. Contact manufacturer for more details.

38

Description Key N3R

NEMA 3R Enclosure

1-Ph

Single-Phase

3-Ph

Three-Phase

MCCB

Molded Case Circuit Breaker

LR

Line Reactor

OR

Output (Load) Reactor

OF

Output Filter

P-SERIES LARGE DRIVE

P-SERIES 3R Enclosed Dimension P-Series Model No. CIE3R-CENP003-P2-1 CIE3R-CENP010-P2-1 CIE3R-CENP015-P2-1 CIE3R-CENP020-P2-1

H

W

D

P-Series Model No. CIE3R-SUBP010-P2-1

H

W

D

35

24

12

35

24

12

41

24

12

CIE3R-SUBP020-P2-1

41

24

12

CIE3R-SUBP015-P2-3

47

24

14

35

24

12

CIE3R-SUBP015-P2-1

47

24

14

35

24

12

CIE3R-CENP025-P2-3

41

24

12

CIE3R-SUBP030-P2-3

41

24

12

CIE3R-CENP030-P2-3

47

24

14

CIE3R-SUBP010-P4-1

47

24

14

35

24

12

41

24

12

47

24

14

56

36

16

60

60

24

72

72

24

35

24

12

41

24

12

47

24

14

56

36

16

60

60

24

CIE3R-CENP015-P2-3 CIE3R-CENP020-P2-3

CIE3R-SUBP020-P2-3 CIE3R-SUBP025-P2-3

CIE3R-CENP010-P4-1

35

24

12

CIE3R-SUBP015-P4-1

CIE3R-CENP015-P4-1

41

24

12

CIE3R-SUBP020-P4-1 CIE3R-SUBP025-P4-1

CIE3R-CENP020-P4-1 CIE3R-CENP025-P4-1 CIE3R-CENP030-P4-1

47

24

14

CIE3R-CENP060-P4-1

56

36

16

60

60

24

CIE3R-CENP200-P4-1 CIE3R-CENP015-P4-3 CIE3R-CENP020-P4-3 CIE3R-CENP025-P4-3

72

72

24

35

24

12

41

24

12

CIE3R-CENP050-P4-3

47

24

14

CIE3R-CENP100-P4-3

56

36

16

60

60

24

CIE3R-SUBP200-P4-1 CIE3R-SUBP015-P4-3 CIE3R-SUBP020-P4-3 CIE3R-SUBP025-P4-3 CIE3R-SUBP030-P4-3 CIE3R-SUBP050-P4-3 CIE3R-SUBP060-P4-3 CIE3R-SUBP100-P4-3 CIE3R-SUBP125-P4-3 CIE3R-SUBP150-P4-3

CIE3R-CENP125-P4-3 CIE3R-CENP150-P4-3

CIE3R-SUBP125-P4-1

H

CIE3R-SUBP075-P4-3

CIE3R-CENP060-P4-3 CIE3R-CENP075-P4-3

D

CIE3R-SUBP040-P4-3

CIE3R-CENP030-P4-3 CIE3R-CENP040-P4-3

CIE3R-SUBP075-P4-1

W

CIE3R-SUBP150-P4-1

CIE3R-CENP125-P4-1 CIE3R-CENP150-P4-1

CIE3R-SUBP060-P4-1 CIE3R-SUBP100-P4-1

CIE3R-CENP075-P4-1 CIE3R-CENP100-P4-1

CIE3R-SUBP040-P4-1 CIE3R-SUBP050-P4-1

CIE3R-CENP040-P4-1 CIE3R-CENP050-P4-1

CIE3R-SUBP030-P4-1

CIE3R-SUBP200-P4-3

CIE3R-CENP200-P4-3 *All measurements in inches * Contact Franklin or visit www.franklin-electric.com for larger enclosed VFD dimensions

39

P-SERIES LARGE DRIVE

P-SERIES Ordering & Sizing Information P-Series (Stand Alone Large Drive) Single-Phase & Three-Phase (200-230 V)

Model No.

Output Full Load Amps 1Ø



Wt. (lbs)

3% Line Reactor Model No.

Wt. (lbs)

CI-007-P2

12

24

11

KDRULB23LE01

18.5

CI-010-P2

16

32

13.2

KDRULD25LE01

22.5

CI-015-P2

23

46

13.2

KDRULD24LE01

22.5

CI-020-P2

30

60

29

KDRULD26LE01

22.5

CI-025-P2

37

74

30

KDRULC22LE01

25.5

CI-030-P2

44

88

44.1

KDRULF24LE01

67

CI-040-P2

57

115

44.1

KDRULF25LE01

67

* Phase refers to incoming power, not motor. NOTE: The drive MUST BE sized according to the motor manufacturer’s maximum amperage draw. Upsize VFD for ambient temperature compensation (see VFD specs for temperature rating).

P-Series (Stand Alone Large Drive) Single-Phase & Three-Phase (480 V)

Model No.

Output Full Load Amps

3% Line Reactor

Wt. (lbs)

Model No.

Wt. (lbs)





CI-007-P4

6

12

11

KDRULA4LE01

14.5

CI-010-P4

8

16

13.2

KDRULA5LE01

14.5

CI-015-P4

12

24

13.2

KDRULB2LE01

18.5

CI-020-P4

15

30

28

KDRULB1LE01

18.5

CI-025-P4

19

39

29

KDRULD1LE01

20.5

CI-030-P4

22

45

44.1

KDRULD2LE01

20.5

CI-040-P4

30

61

44.1

KDRULC1LE01

20.5

CI-050-P4

32

75

60

KDRULF2LE01

67

CI-060-P4

45

91

60

KDRULF4LE01

25.5

CI-075-P4

55

110

64

KDRULF3LE01

67

CI-100-P4

76

152

93

KDRULH3LE01

78

CI-125-P4

94

183

95

KDRULH2LE01

78

CI-150-P4

111

223

223

KDRULH1LE01

108

CI-200-P4

132

264

223

KDRULG3LE01

78

CI-250-P4

162

325

252

KDRULG1LE01

108

CI-350-P4

216

432

442

KDRULJ2LE01

78

CI-400-P4

273

547

442

KDRULJ1LE01

131

* Phase refers to incoming power, not motor. NOTE: The drive MUST BE sized according to the motor manufacturer’s maximum amperage draw. Upsize VFD for ambient temperature compensation (see VFD specs for temperature rating). † 600 V available upon request. Contact manufacturer for more details.

40

P-SERIES LARGE DRIVE

P-SERIES P-Series Large Drive Dimension

P-Series Drive

H

W

D

11.19

5.91

6.17

11.18

7.87

7.16

11.18

7.87

7.16

15.16

9.84

7.94

15.16

9.84

7.94

18.11

11.97

9.22

18.11

11.97

9.22

CI-050-P4

20.28

11.81

10.46

CI-007-P2 CI-007-P4 CI-010-P2 CI-010-P4 CI-015-P2 CI-015-P4 CI-020-P2 CI-020-P4 CI-025-P2

D

CI-025-P4 CI-030-P2 CI-030-P4 H

W

CI-040-P2 CI-040-P4 CI-060-P4

20.28

11.81

10.46

* Line Reactors housed in separate UL/NEMA 1 Type Enclosure

CI-075-P4

20.28

11.81

11.52

5.91”

CI-100-P4

23.09

14.57

13.29

CI-125-P4

23.09

14.57

13.29

CI-150-P4

30.26

20.80

16.64

CI-200-P4

30.26

20.80

16.64

CI-250-P4

33.23

20.80

16.64

41.85

21.17

17.70

43.7

30.8

17.4

51.3

36.3

19.5

6.17”

CI-350-P4 CI-400-P4 CI-500-P4 CI-600-P4 CI-700-P4

P-Series Large Drive Accessories Model No.

VFD-FPL VFD-GXX VFD-HOA VFD-KPD/4X VFD-KPD/4X VFD-KPS VFD-LTA VFD-RPL VFD-SPD P51-100G-A-I240-20MA P51-200G-A-I240-20MA P51-300G-A-I240-20MA

*All measurements in inches

Wt. (lbs)

Description

1 1 1 1 1 1 1 1 1 1 1 1

Fault Pilot Light (Red Standard) Circuit Breaker Disconnect Hand/Off/Auto Switch Door Mounted Keypad with Type 4X Cover NEMA 4X Waterproof Keypad Door Mounted Keypad Lightning Arrestor Run Pilot Light (Green Standard) Door Mounted Speed Potentiometer Transducer (Gauge pressure), 100 PSIG 4-20 mA, +/-0.5% accy Transducer (Gauge pressure), 200 PSIG 4-20 mA, +/-0.5% accy Transducer (Gauge pressure), 300 PSIG 4-20 mA, +/-0.5% accy

41

P-SERIES LARGE DRIVE

P-SERIES P-Series Accessories Line Reactors (for Stand Alone Drives ONLY) UL/NEMA 1 Enclosure Model No.

42

Wt. (lbs)

Voltage

Description

KDRULA54LE01

14.5

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 0.5 hp

KDRULA53LE01

14.5

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 0.75 hp

KDRULA25LE01

14.5

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 1 hp

KDRULA26LE01

14.5

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 1.5 hp

KDRULA27LE01

14.5

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 2 hp

KDRULA28LE01

14.5

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 3 hp

KDRULB22LE01

18.5

KDRULB23LE01

18.5

208/240 V

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 5 hp 3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 7.5 hp

KDRULD25LE01

22.5

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 10 hp

KDRULD24LE01

22.5

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 15 hp 3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 20 hp

KDRULD26LE01

22.5

KDRULC22LE01

25.5

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 25 hp

KDRULF24LE01

67

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 30 hp

KDRULF25LE01

67

3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 40 hp

KDRULA54HE01

14.5

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 0.5 hp

KDRULA53HE01

14.5

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 0.75 hp

KDRULA25HE01

14.5

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 1 hp

KDRULA27HE01

14.5

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 1.5 hp

KDRULA26HE01

14.5

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 2 hp

KDRULA28HE01

14.5

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 3 hp

KDRULB25HE01

18.5

208/240 V

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 5 hp

KDRULB26HE01

18.5

KDRULD21HE01

22.5

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 7.5 hp 5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 10 hp

KDRULD22HE01

22.5

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 15 hp

KDRULC22HE01

25.5

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 20 hp

KDRULF28HE01

67

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 25 hp

KDRULF25HE01

67

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 30 hp

KDRULF26HE01

67

5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 40 hp

KDRULA6LE01

14.5

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, .5 hp

KDRULA7LE01

14.5

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, .75 hp

KDRULA8LE01

14.5

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 1 hp 3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 1.5 hp

KDRULA9LE01

14.5

KDRULA1LE01

14.5

KDRULA2LE01

14.5

KDRULA3LE01

14.5

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 5 hp

KDRULA4LE01

14.5

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 7.5 hp

KDRULA5LE01

14.5

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 10 hp

KDRULB2LE01

18.5

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 15 hp

KDRULB1LE01

18.5

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 20 hp

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 2 hp 480 V

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 3 hp

P-SERIES LARGE DRIVE

P-SERIES P-Series Accessories - Continued Line Reactors (for Stand Alone Drives ONLY) UL/NEMA 1 Enclosure Model No.

Wt. (lbs)

Voltage

Description

KDRULD1LE01

20.5

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 25 hp

KDRULD2LE01

20.5

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 30 hp

KDRULC1LE01

25.5

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 40 hp

KDRULF2LE01

67

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 50 hp

KDRULF4LE01

67

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 60 hp

KDRULF3LE01

67

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 75 hp

KDRULH3LE01

78

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 100 hp

KDRULH2LE01

78

KDRULH1LE01

108

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 150 hp

KDRULG3LE01

131

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 200 hp

KDRULG1LE01

132

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 250 hp

KDRULG2LE01

132

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 300 hp

KDRULJ2LE01

150

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 350 hp

KDRULJ1LE01

150

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 400 hp

KDRULA6HE01

14.5

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, .5 hp

KDRULA7HE01

14.5

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, .75 hp

KDRULA8HE01

14.5

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 1 hp

KDRULA9HE01

14.5

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 1.5 hp

KDRULA1HE01

14.5

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 2 hp

KDRULA2HE01

14.5

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 3 hp

KDRULA3HE01

14.5

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 5 hp

KDRULA4HE01

15.5

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 7.5 hp

KDRULA5HE01

15.5

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 10 hp

KDRULB2HE01

17.5

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 15 hp

KDRULC3HE01

25.5

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 20 hp

KDRULC1HE01

25.5

KDRULE2HE01

26.5

KDRULF4HE01

67

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 40 hp

KDRULF1HE01

67

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 50 hp

KDRULF2HE01

67

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 60 hp

KDRULH2HE01

82

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 75 hp

KDRULI2HE01

82

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 100 hp

KDRULG3HE01

122

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 125 hp

KDRULG1HE01

127

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 150 hp

KDRULJ1HE01

136

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 200 hp

KDRULL1HE01

162

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 250 hp

KDRULL2HE01

162

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 300 hp

KDRULL3HE01

166

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 350 hp

KDRULL4HE01

176

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 400 hp

480 V

3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 125 hp

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 25 hp 480 V

5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 30 hp

43

P-SERIES LARGE DRIVE

P-SERIES P-Series Accessories - Continued Load Reactors (for Stand Alone Drives ONLY) UL/NEMA 1 Enclosure Model No.

44

Wt. (lbs)

Voltage

Description

KDRULA1PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 2 hp

KDRULA2PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 3 hp

KDRULA3PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 5 hp

KDRULA4PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 7.5 hp

KDRULB1PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 10 hp

KDRULD1PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 15 hp

KDRULD2PE01

18.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 20 hp

KDRULD3PE01

18.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 25 hp

KDRULD4PE01

22.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 30 hp

KDRULC1PE01

22.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 40 hp

KDRULF1PE01

22.5

KDRULF2PE01

25.5

KDRULF3PE01

67

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 75 hp

KDRULH1PE01

67

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 100 hp

KDRULI1PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 125 hp

KDRULI2PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 150 hp

KDRULG1PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 200 hp

KDRULJ1PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 250 hp

KDRULJ2PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 300 hp

KDRULL1PE01

14.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 350 hp

KDRULL2PE01

18.5

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 400 hp

480 V

3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 50 hp 3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 60 hp

P-SERIES LARGE DRIVE

P-SERIES P-Series Accessories - Continued Output Filters (for Stand Alone Drives ONLY) UL/NEMA 1 Enclosure Model No.

Wt. (lbs)

Voltage

Description

V1K2A01

11

V1K, KLC Series Output Filter, N1 Enclosed, .75 hp @460 V

V1K3A01

11

V1K, KLC Series Output Filter, N1 Enclosed, 1-1.5 hp @460 V

V1K4A01

11

V1K, KLC Series Output Filter, N1 Enclosed, 2 hp @460 V

V1K6A01

11

V1K, KLC Series Output Filter, N1 Enclosed, 3 hp @460 V

V1K8A01

11

V1K, KLC Series Output Filter, N1 Enclosed, 5 hp @460 V

V1K12A01

11

V1K, KLC Series Output Filter, N1 Enclosed, 7.5 hp @460 V

V1K18A01

15

V1K, KLC Series Output Filter, N1 Enclosed, 10 hp @460 V

V1K21A01

15

V1K, KLC Series Output Filter, N1 Enclosed, 15 hp @460 V

V1K25A01

15

V1K, KLC Series Output Filter, N1 Enclosed, 15 hp @460 V

V1K27A01

15

V1K, KLC Series Output Filter, N1 Enclosed, 20 hp @460 V

V1K35A01

23

V1K, KLC Series Output Filter, N1 Enclosed, 25 hp @460 V

V1K45A01

23

V1K, KLC Series Output Filter, N1 Enclosed, 30 hp @460 V

V1K55A01

23

V1K80A01

29

V1K, KLC Series Output Filter, N1 Enclosed, 50/60 hp @460 V

V1K110A01

68

V1K, KLC Series Output Filter N1 Enclosed, 75 hp @460 V

V1K130A01

83

V1K, KLC Series Output Filter N1 Enclosed, 100 hp @460 V

V1K160A01

83

V1K, KLC Series Output Filter, N1 Enclosed, 125 hp @460 V

V1K200A01

93

V1K, KLC Series Output Filter, N1 Enclosed, 150 hp @460 V

V1K250A01

93

V1K, KLC Series Output Filter, N1 Enclosed, 200 hp @460 V

V1K305A01

117

V1K, KLC Series Output Filter, N1 Enclosed, 250 hp @460 V

V1K362A01

117

V1K, KLC Series Output Filter, N1 Enclosed, 300 hp @460 V

V1K420A01

132

V1K, KLC Series Output Filter, N1 Enclosed, 350 hp @460 V

V1K480A01

138

V1K, KLC Series Output Filter, N1 Enclosed, 400 hp @460 V

V1K600A01

168

V1K, KLC Series Output Filter, N1 Enclosed, 500 hp @460 V

V1K750A01

180

V1K, KLC Series Output Filter, N1 Enclosed, 600 hp @460 V

480 V

V1K, KLC Series Output Filter, N1 Enclosed, 40 hp @460 V

45

P-SERIES Wiring Diagram

*For general reference only, not field wiring. Consult installation instructions.

46

P-SERIES LARGE DRIVE

P-SERIES

P-SERIES LARGE DRIVE

Specifications Output Ratings

Input Ratings

Operation

Voltage (V)

Three -phase, 200~230 V, Three -phase, 380~480 V

Frequency (Hz)

0~120 Hz

Voltage (V)

Single/Three -phase, 200~230 V (-15%, +10%), Three -phase, 380~480 V (-15%, +10%)

Frequency (Hz)

50~60 Hz (±5%)

Input Power Factor

96%

Control Method

V/F control, sensorless vector control

Frequency Setting Resolution

Digital reference: 0.01 Hz (below 99 Hz) & 0.1 Hz (100 Hz and over); Analog reference: 0.06 Hz at 60 Hz

Frequency Setting Accuracy

Digital: 0.01% of maximum output frequency; Analog: 0.1% of maximum output frequency

V/F Ratio

Linear, Square, User V/F

Overload Capacity

1 minute at 120%, 10 seconds at 150% (with inverse characteristic proportional to time)

Torque Boost

Auto, manual (0~15%)

Multi-Function Input Terminals Total 8 inputs (programmable)

Input Signal

Output Signal

Protective Functions

Operating Environment

Analog Output

0~10 V linear

Operator Control

32-character LCD keypad, Terminals, ModBus-RTU communication Optional, ProfiBus-DP, DeviceNet, F-Net, BACnet, LonWorks

Frequency Setting

Analog: 0~10 V, 4~20mA, additional port for Sub-Board (0~10 V); Digital: Keypad, Communication

Start Signal

Forward, reverse

Multi-Step Operation

Setting up to 17 speeds (using multi-function terminal)

Multi-Step Accel/Decel Time

0.1~6000 seconds. Maximum 8 pre-defined steps using multi-function terminals

Operational Functions

DC braking, frequency limit, frequency jump, second motor function, slip compensation, reverse rotation prevention, auto restart, inverter bypass, auto-tuning, dual PID control

Emergency Stop

Stops output from inverter

Auto Operation

Operates from internal sequence by setting multi-function terminal (5 way x 8 step)

Jog

Jog operation

Fault Reset

Resets fault signal when protective function is active

Operational Status

Frequency detection, overload alarm, stall, overvoltage, undervoltage, inverter overheat, run, stop, constant speed, speed search, fault output, inverter bypass, auto-operation sequence

Indicator

Output frequency, output current, output voltage, DC voltage, output torque (output voltage: 0~10 V)

Trip

Overvoltage, undervoltage, overcurrent, inverter overheat, motor overheat, i/o -phase loss, fuse open, ground fault, external fault 1, 2, option fault, overload, speed command loss, hardware fault, communication error, etc.

Alarm

Stall, overload temperature sensor fault

Ambient Temperature

-10~40 °C (50 °C when derated 20%) or 14~104 °F (122 °F when derated 20%)

Storage Temperature

-20 ~65 °C or -4~149.5 °F

Humidity

Less than 95% relative humidity maximum (non-condensing)

Vibration

Below 5.9m²/sec (=0.6g)

Altitude

Below 1,000 m (3,300 ft): derate VFD by 10% for every additional 1,000 m

Application Site

Pollution degree 2. no corrosive gas, combustible gas, oil mist or dust

47

Notes:

48

Notes:

49