LARGE Drives & Controls Intelligent solutions for pumping applications
Contents Starters Intelligent Pump Starter (IPS) Standard Pump Starter (SPS) Economy Pump Starter (EPS) Advanced Duplex Pump Controller (APX) Duplex Alternating Pump Controller (DPX)
4 11 15 19 23
Reduced Voltage Digital Soft Starter (MS6) Analog Soft Starter (RVS)
27 31
Variable Speed P-Series P-Series Enclosed P- Series Stand Alone
35 40
Intelligent Pump Starter (IPS)
IPS
Intelligent Pump Starter
50/60 Hz, 1Ø & 3Ø, 120~600 VAC, 1/3 - 300 hp Integrated electronic pump protection overload Power metering and data logging options
More Protection, Less Nuisance Trips Integrated Tru-power™ electronic motor and pump protection • Eliminates need for costly pump protection relays • Dry pump detection using power (nuisance trip-free); automatic restart for well recovery mode • Wide range class 5-30 electronic overload eliminates call backs due to mid-sized heaters • Advanced protective features include over/under voltage, phase loss, phase unbalance, stalled/locked rotor, cycle fault, and UL 1053 ground fault • Tru-power™ sensing protects pumps from dry pump, dead head, runout, and jammed impeller conditions - keeping you online and preventing costly premature pump failure. Along with superior protection, measuring underload using power allows for a more flexible trip range, as opposed to measuring by current, which requires a more precise set point. The end result is the elimination of nuisance trips. Adjustable over/under voltage is included. Plus you get phase unbalance, loss, anti-cycling, phase sequence, and warm start protection. Our overload is wide range - so you never have the wrong sized heaters.
Built-in power monitoring and fault logging for easy troubleshooting • View voltage, current, power factor, and more through an intuitive display • Last 5 fault types are recorded (all power condition values are stored) • Quickly identify common power problems such as phase imbalance, voltage drop, and over/undercurrent conditions to ensure proper pump operation
NEMA
Optional Ethernet card provides time-stamped data logging, ending utility power disputes • Download and display up to 100 faults and alarms, including operational mode and values of operation at the time • All power condition values are stored by phase for voltage, current, and power factor per fault • Data is easily displayed and saved on any web browser using an Ethernet connection. Starter incorporates internal web-server. No programming required
Power
Current
• Time and date stamped for utility documentation
No Load
Full Load
No Load
Full Load
Power is linear for superior load monitoring
4
Get up to100 faults - even utility power quality - on any web-browser!
IPS
Intelligent Pump Starter (IPS)
Easy to setup and use • Inside, the display shows an easy to use menu for setting
a wealth of parameters. Adjust any protective or control setting in seconds. For example, choose how long to allow for dry well recovery, set run time periods and On/Off delays. All this with just a few intuitive keystrokes. The IPS ships with factory default settings pre-programmed for optimal submersible pump protection.
Internal keypad menu for easy operation • All control and protective functions are easily programmable • LEDs indicate Hand/Off/Auto modes, run and fault conditions
Industrial grade construction for long life • Door mounted pilot devices include HOA switch • UL/NEMA 3R outdoor rating • Multi-tap transformer accommodates common voltages; no fuse(s) required • 120 V control power for field devices • Magnetic contactors feature 2.5 million contactor electrical cycles at full rated current
Advanced programmable pump control options • Auto-restart with well recovery timer • Backspin delay prevents start-ups into draining system • On delay and off delay settings • Minimum run time based on last input • 12-120 V auto run terminal for remote start/stop
UL/NEMA Type 3R enclosure
• Dry contact terminal for remote start/stop • Analog input for transducer for use with pressurized tanks (under development - consult factory for availability)
Main circuit breaker disconnect rated for service entrance • UL 489 circuit breaker provides branch and short circuit protection • No fuses required – saves time and money • Lockable handle for safety
5
Intelligent Pump Starter (IPS)
IPS Ordering & Sizing Information Intelligent Pump Starter (Combination) UL/NEMA 3R Enclosure (Electronic Overload)
HP
NEMA Size
Wt. (lbs)
Description
IPS3R-S1-J-G15-8 1/3 1 2 2 5 8A IPS3R-S1-J-G20-11 1/2 1.5 3 3 7.5 11A IPS3R-S1-6J-G20-11 10 IPS3R-S1-J-G30-17 1 3 5 10 17A 1 IPS3R-S1-6J-G30-17 15 IPS3R-S1-J-G40-22 7.5 15 22A IPS3R-S1-6J-G40-22 20 IPS3R-S1-J-G50-28 2 5 7.5 10 20 28A IPS3R-S1-6J-G50-28 25 IPS3R-S2-6J-G30-17 15 17A IPS3R-S2-J-G40-22 7.5 15 22A IPS3R-S2-6J-G40-22 20 IPS3R-S2-J-G50-28 2 5 7.5 10 20 28A IPS3R-S2-6J-G50-28 25 2 IPS3R-S2-J-G60-34 3 5 10 10 25 34A IPS3R-S2-6J-G60-34 30 IPS3R-S2-J-G80-42 7.5 15 30 42A IPS3R-S2-6J-G80-42 40 IPS3R-S3-6J-G60-34 30 34A IPS3R-S3-J-G80-42 7.5 15 30 42A IPS3R-S3-6J-G80-42 40 IPS3R-S3-J-G100-56 5 10 15 20 40 56A IPS3R-S3-6J-G100-56 50 3 IPS3R-S3-J-G125-68 5 15 20 25 50 68A IPS3R-S3-6J-G125-68 60 IPS3R-S3-J-G150-80 7.5 15 25 30 60 80A IPS3R-S3-6J-G150-80 75 IPS3R-S4-6J-G125-68 60 68A IPS3R-S4-J-G150-80 7.5 15 25 30 60 80A IPS3R-S4-6J-G150-80 75 4 IPS3R-S4-J-G200-104 10 25 30 40 75 104Asize rating. * Note: The shaded figures represent the minimum horsepower for corresponding NEMA IPS3R-S4-6J-G200-104 100 IPS3R-S4-J-G250-136 15 30 40 50 100 136A IPS3R-S5-6J-G250-125 125 125A IPS3R-S5-J-G300-156 50 60 125 156A IPS3R-S5-6J-G300-150 150 150A 5 IPS3R-S5-J-G400-221 50 75 75 150 221A IPS3R-S5-6J-G400-200 200 200A IPS3R-S5-J-G500-248 75 100 200 248A IPS3R-S5P-6J-G500-250 250 250A IPS3R-S5P-J-G600-312 100 125 250 312A 5+ IPS3R-S5P-6J-G600-300 300 300A IPS3R-S5P-J-G800-361 150 150 300 361A
46 46 46 46 46 46 46 46 46 50 50 50 50 50 50 50 50 50 66 66 66 66 66 66 66 66 66 85 85 85 85 85 85 240 240 240 240 240 240 382 382 382 382
N3R IPS, S1, 8A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 11A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 11A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 17A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 17A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 22A w/ SCM, MCCB Disc, HOA, 50VA CPT N3R IPS, S1, 22A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 28A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 28A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 17A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 22A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 22A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 28A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 28A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 34A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 34A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 42A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 42A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S3, 34A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 42A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 42A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 56A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 56A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 68A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 68A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S3, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 68A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S4, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 104A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S4, 104A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 136A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S5, 125A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 156A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5, 150A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 221A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5, 200A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 248A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5P, 250A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5P, 312A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5P, 300A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5P, 361A w/ SCM, MCCB Disc, HOA, 200 VA CPT
Model No.
Single-Phase 120 V
230 V
Three-Phase 200 V
230 V
460 V
575 V
Max. Amps
* Note: The shaded figures represent the maximum horsepower for corresponding NEMA size rating.
6
Intelligent Pump Starter (IPS)
IPS Ordering & Sizing Information Intelligent Pump Starter (Combination) with Ethernet Card UL/NEMA 3R Enclosure (Electronic Overload)
HP Model No. IPS3R-S1-J-G15-8E IPS3R-S1-J-G20-11E IPS3R-S1-6J-G20-11E IPS3R-S1-J-G30-17E IPS3R-S1-6J-G30-17E IPS3R-S1-J-G40-22E IPS3R-S1-6J-G40-22E IPS3R-S1-J-G50-28E IPS3R-S1-6J-G50-28E IPS3R-S2-6J-G30-17E IPS3R-S2-J-G40-22E IPS3R-S2-6J-G40-22E IPS3R-S2-J-G50-28E IPS3R-S2-6J-G50-28E IPS3R-S2-J-G60-34E IPS3R-S2-6J-G60-34E IPS3R-S2-J-G80-42E IPS3R-S2-6J-G80-42E IPS3R-S3-6J-G60-34E IPS3R-S3-J-G80-42E IPS3R-S3-6J-G80-42E IPS3R-S3-J-G100-56E IPS3R-S3-6J-G100-56E IPS3R-S3-J-G125-68E IPS3R-S3-6J-G125-68E IPS3R-S3-J-G150-80E IPS3R-S3-6J-G150-80E IPS3R-S4-6J-G125-68E IPS3R-S4-J-G150-80E IPS3R-S4-6J-G150-80E IPS3R-S4-J-G200-104E IPS3R-S4-6J-G200-104E IPS3R-S4-J-G250-136E IPS3R-S5-6J-G250-125E IPS3R-S5-J-G300-156E IPS3R-S5-6J-G300-150E IPS3R-S5-J-G400-221E IPS3R-S5-6J-G400-200E IPS3R-S5-J-G500-248E IPS3R-S5P-6J-G500-250 IPS3R-S5P-J-G600-312E IPS3R-S5P-6J-G600-300E IPS3R-S5P-J-G800-361E
Single-Phase
Three-Phase
120 V
230 V
200 V
230 V
460 V
575 V
1/3 1/2 1 2 2 3 5 5 7.5 7.5 10 15 -
1 1.5 3 5 5 5 7.5 7.5 10 15 15 15 25 30 50 -
2 3 7.5 7.5 10 15 20 25 25 30 40 50 75 75 100 150
2 3 5 7.5 10 7.5 10 10 15 15 20 25 30 30 40 50 60 75 100 125 150
5 7.5 10 15 20 15 20 25 30 30 40 50 60 60 75 100 125 150 200 250 300
10 15 20 25 15 20 25 30 40 30 40 50 60 75 60 75 100 125 150 200 250 300 -
Max. Amps
NEMA Size
8A 11A 17A
1
22A 28A 17A 22A 28A
2
34A 42A 34A 42A 56A
3
68A 80A 68A 80A 4 104A 136A 125A 156A 150A 221A 200A 248A 250A 312A 300A 361A
5
5+
Wt. (lbs)
Description
46 46 46 46 46 46 46 46 46 50 50 50 50 50 50 50 50 50 66 66 66 66 66 66 66 66 66 85 85 85 85 85 85 240 240 240 240 240 240 382 382 382 382
N3R IPS, S1, 8A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 11A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 11A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 17A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 17A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 22A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 22A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S1, 28A w/ SCM, MCCB Disc, HOA, 50 VA CPT N3R IPS, S1, 28A w/ SCM, MCCB Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 17A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 22A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 22A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 28A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 28A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 34A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 34A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S2, 42A w/ SCM, MCCS Disc, HOA, 50 VA CPT N3R IPS, S2, 42A w/ SCM, MCCS Disc, HOA, 50 VA CPT, 600V N3R IPS, S3, 34A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 42A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 42A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 56A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 56A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 68A w/ SCM, MCCS Disc, HOA, 100 VA CPT N3R IPS, S3, 68A w/ SCM, MCCS Disc, HOA, 100 VA CPT, 600V N3R IPS, S3, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S3, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 68A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S4, 80A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 104A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S4, 104A w/ SCM, MCCB Disc, HOA, 100 VA CPT, 600V N3R IPS, S4, 136A w/ SCM, MCCB Disc, HOA, 100 VA CPT N3R IPS, S5, 125A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 156A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5, 150A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 221A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5, 200A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5, 248A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5, 250A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5P, 312A w/ SCM, MCCB Disc, HOA, 200 VA CPT N3R IPS, S5P, 300A w/ SCM, MCCB Disc, HOA, 200 VA CPT, 600V N3R IPS, S5P, 361A w/ SCM, MCCB Disc, HOA, 200 VA CPT
* Note: The shaded figures represent the maximum horsepower for corresponding NEMA size rating.
7
Intelligent Pump Starter (IPS)
IPS IPS Accessories Model No.
Wt. (lbs)
Description
0.5
Data and Fault Logging with Date/Time Stamp, Ethernet Output
IPS-LTA
1
Lightning/Surge Arrestor
IPS-SPB
1
Start Push button Control (Door Mounted)
IPS-STSP
1
Start/Stop Push button Control (Door Mounted)
IPS-TMR
0
Programmable Timer Functions: Backspin, On Delay
IPS-ENET
IPS Dimensions Starter Size
H
W
D
Size 1, Size 2
22
15
10
Size 3, Size 4
32
15
10
Size 5
42
30
12
Size 5+
48
36
16
Description
UL/NEMA 3R Enclosure
*All measurements in inches
W
H
D
8
D
Intelligent Pump Starter (IPS)
IPS Wiring Diagram
SCM PCB Common
DRY INPUTS
See Table 1
Hand Auto Status
RELAY OUTPUTS
Common Fault Auto Run
Auto Run CAT 5 Input
VOLTAGE INPUTS Shut Down Motor
ACTUATOR CONTROL
A1
M
12-120VAC/DC Input
Limit Switch
120VAC, 0.25A Output
Normally Open Input
Common
A2
To Auto Run
N
X2 X1 120V
CPT
208V 240V 480V
TRANSFORMER PRIMARY CIRCUIT BREAKER SIZING V 208/230
VA 50VA 100VA
480
N/A 2A
N/A 1A
TABLE 1 H1
H4
L1
L2
HOA SWITCH
L3
Common
OFF H
Hand
MCCB
A
X X
Auto
A
B
C
X
HOA SWITCH / START OFF
OL
CAT 5 Output H4
H1
H
Common
X
START / STOP
14 22
T3
START
Auto
M
T2
X
Hand 13 21
T1
A
STOP
Common
Hand
M
START
Auto
3PH
SCHM-IPS3R/C-V2
9
Intelligent Pump Starter (IPS)
IPS IPS Specifications Starter Type Intelligent Pump Starter Combination, Service Rated UL Type 3R
User Interface Hand-Off-Auto Keypad with LEDs
Internal
Hand-Off-Auto Switch
Door mounted
Standard Control Operations Inputs Voltage Auto Run Shutdown
Apply 10 - 130 VAC/DC to energize Apply 10 - 130 VAC/DC to energize
Actuator position switch
N.O. dry contact closure
Dry Auto
N.O. dry contact closure
Outputs Run Status
N.O., 0.3 A@125 VAC; 1 A@24 VAC
Fault relay
N.O., 0.3 A@125 VAC; 1 A@24 VAC
Actuator motor control
120VAC, 0.25A max
Operational Overload Type Electronic; I2t Thermal Trip Curve Power fail mode
Restart last mode, no delay (default) Restart with delay Restart Off - LED flashes last mode
On/Off Time Delay
Programmable, selectable from 0.1 to 99 seconds
Environmental Ambient Operating Temp
-5 to 140 °F (-20 to 60 °C)
Ambient Storage Temp
-5 to 185 °F (-20 to 85 °C)
Relative Humidity
5% to 95% non-condensing
Protective Functions Current Setting: 1-95 A Trip Class: 5-30 (10 default) Reset: Automatic/Manual (manual default)
Overload
Warm Start Provision Delays restart based on calculated motor temperature when enabled Locked Rotor / Stall Trip within 0.5s Ground Fault (UL1053) Current Setting: 1.0-9.9A (1.0A default) Current Phase Unbalance Setting: 1-50% (20% default) Over/Under Voltage Setting: +/- 5-25% (5% default) Voltage Phase Unbalance Setting: 1-20% (3% default) Voltage Phase Loss Setting: 1-50% (5% default) Phase Sequence Trip in 0.1s when enabled Under Power
10
Setting: 0-99% of nominal hp (20% Default)
Over Power
Setting: 101-200% of nominal hp (125% Default)
Cycle Fault
Trip if cycle rate exceeds 1200 starts per hour
STANDARD PUMP STARTER (SPS)
SPS
STANDARD PUMP STARTER
50/60 Hz, 1Ø & 3Ø, 120~600 VAC, 1–250 hp Service rated circuit breaker disconnect Adjustable overload with phase loss protection
SUPERIOR PROTECTION, PROVEN RELIABILITY Rugged construction provides dependable operation • Simple and functional control with heavy duty HOA switch • Powder coated metal Type 3R enclosure available with optional pole mounting straps • Ample space for adding additional controls Main circuit breaker disconnect rated for service entrance • UL 489 circuit breaker provides branch and short circuit protection • No fuses required – save time and money • Lockable handle for safety • UL listed for use as service equipment Reliable components ensure long life • 2.5 million contactor electrical cycles at full rated current • Contactor includes standard 1 N.O. and 1 N.C. auxiliary contacts • NEMA size rated, available in NEMA sizes 1-5
Thermal overload motor protection • Differential phase failure protection • Ambient temperature compensated: 41 ºF - 104 ºF (5 ºC to 40 ºC) • Reset push button on door eliminates the need to access panel interior
NEMA Standard control transformer (CPT) offers flexibility • Multi-tap CPT input accepts all common motor voltages • Integrated secondary protection – no fuses required • 120 V control power available for additional field installed devices
11
STANDARD PUMP STARTER (SPS)
SPS Standard Pump Starter (Combination) UL/NEMA 3R Enclosures (Thermal Overload)
HP Model No.
Single-Phase
NEMA Size
Three-Phase
120 V
230 V
200 V
230 V
SPS3R-S1-K-G15-9
-
1
2
2
5
SPS3R-S1-K-G20-13
1/2
2
3
3
7.5
SPS3R-S1-K-G30-18
1
3
5
5
SPS3R-S2-K-G40-25
1.5
-
-
7.5
SPS3R-S2-K-G50-36
2
-
7.5
10
20
SPS3R-S2-K-G60-40
3
5
10
-
25
SPS3R-S2-K-G80-50
-
7.5
15
15
SPS3R-S3-K-G100-65
5
10
-
20
SPS3R-S3-K-G125-75
-
15
20
25
50
SPS3R-S3P-K-G150-85
7.5
-
25
30
60
SPS3R-S4-K-G200-125
10
-
40
40
75
SPS3R-S4-K-G250-150
-
-
40
50
100
SPS3R-S5-K-G300-180
-
-
60
60
125
SPS3R-S5-K-G400-240
-
-
75
75
150
SPS3R-S5P-K-G500-400
-
-
100
100
200
SPS3R-S5P-K-G600-400
-
-
125
125
250
Wt. (lbs)
Description
460 V 44
N3R SPS, S1, 9A w/ HOA, CB, TOL & CPT
44
N3R SPS, S1, 13A w/ HOA, CB, TOL & CPT
10
44
N3R SPS, S1, 18A w/ HOA, CB, TOL & CPT
15
48
N3R SPS, S2, 25A w/ HOA, CB, TOL & CPT
48
N3R SPS, S2, 36A w/ HOA, CB, TOL & CPT
48
N3R SPS, S2, 40A w/ HOA, CB, TOL & CPT
30
48
N3R SPS, S2, 50A w/ HOA, CB, TOL & CPT
40
64
N3R SPS, S3, 65A w/ HOA, CB, TOL & CPT
1
2
3 3+ 4 5 5+
64
N3R SPS, S3, 75A w/ HOA, CB, TOL & CPT
64
N3R SPS, S3P, 85A w/ HOA, CB, TOL & CPT
68
N3R SPS, S4, 125A w/ HOA, CB, TOL & CPT
68
N3R SPS, S4, 150A w/ HOA, CB, TOL & CPT
240
N3R SPS, S5, 180A w/ HOA, CB, TOL & CPT
240
N3R SPS, S5, 240A w/ HOA, CB, TOL & CPT
382
N3R SPS, S5P, 400A w/ HOA, CB, TOL & CPT
382
N3R SPS, S5P, 400A w/ HOA, CB, TOL & CPT
SPS Accessories Model No.
12
Wt. (lbs)
Description
SPS-24
0
24 VAC Control Circuit
SPS-3FC
1
Three Float Switch Input Terminals for Simplex Operation
SPS-BCN
1
Optional Top Mount Alarm Beacon Light, 120 VAC
SPS-BZR
1
Optional Door Mounted Buzzer, 120 VAC w/ Silence Push button
SPS-CLK-120V
1
Optional 7 Day, 24 Hr. Programmable Clock
SPS-CLK-24V
1
Optional 7 Day, 24 Hr. Programmable Clock
SPS-ENCL
1
Upgrade for S1 & S2 Panels to Larger 3R Enclosure, 32x15x8"
SPS-LTA
1
Lightning/Surge Arrestor
SPS-RLY-120VAC
1
Factory Installed 120 VAC Finder Interposing Run Relay
SPS-RLY-24VAC-DC
1
Factory Installed 24 VAC/VDC Finder Interposing Run Relay
SPS-RPL
1
Run Pilot Light
SPS-SPB
1
Start Push button
STANDARD PUMP STARTER (SPS)
SPS SPS Dimensions Starter Size
H
W
D
Size 1, Size 2
22
15
10
Size 3, Size 3+, Size 4
32
15
10
Size 5, Size 5+
42
30
12
W
Description
D
UL/NEMA 3R Enclosure
*All measurements in inches H
Wiring Diagram H1
H4 L2
480V
240V
208V
L1
CPT
L1
L2
MCCB H1
H2
MCCB H1
H2
M
N
120V
AUX CONT
OL T1
H
O
A
M AUX CONT
OL T1
T2
T3
OL A2
X00
95
START 00X
T3
L3
1
2
96
M
A1
MTR
MTR
SINGLE PHASE
THREE PHASE
13
STANDARD PUMP STARTER (SPS)
SPS SPS Specifications Starter Type Standard Pump Starter 3R Combination, Service Rated UL Type 3R Enclosure
User Interface HOA Selector Switch Reset Push Button
Standard Control Operations Auto Run Input
N.O. dry contact closure to energize starter
Environmental Ambient Operating Temp
-5 to 140 °F (-20 to 60 °C)
Ambient Storage Temp
-5 to 185 °F (-20 to 85 °C)
Relative Humidity
5% to 95% non-condensing
Protective Functions
14
Overload Type
Thermal bi-metallic
Trip Class
Class 10
Reset
Manual
Phase Loss
Differential overload protection
ECONOMY PUMP STARTER (EPS)
EPS
ECONOMY PUMP STARTER
50/60 Hz, 1Ø & 3Ø, 120~600VAC, 1-50 hp Wide range class 1-30 electronic overload HOA switch with run pilot light
DEPENDABLE PERFORMANCE COMES STANDARD Rugged construction provides dependable operation • Industrial HOA switch and LED run pilot light • NEMA rated contactor with 1N.O. & 1N.C. auxiliary contacts • Ample space for adding additional controls Reliable components ensure long life • 2.5 Million contactor electrical cycles at full rated current • Contactor includes standard 1 N.O. and 1 N.C. auxiliary contacts • NEMA Size rated, available in NEMA sizes 1-3 Adjustable electronic overload • Class 1-30 overload • Advanced protective features include phase loss, imbalance, stall protection and manual reset Standard control transformer (CPT) offers flexibility • Multi-tap CPT input accepts all common motor voltages • Integrated secondary protection – no fuses required • 120 V control power available for additional field installed devices
NEMA
15
ECONOMY PUMP STARTER (EPS)
EPS Economy Pump Starters (Non-Combination) UL/NEMA Type 1, 3R, 4, and 4X Fiberglass Enclosures (Electronic Overload) HP Enclosure Type
Model #
UL/NEMA Type 1 UL/NEMA Type 3R UL/NEMA Type 4 UL/NEMA Type 4X Fiberglass
Three Phase
NEMA SIZE
WT (lbs)
Description
120V
230V
200V
230V
460V
1/6
1/2
1
1.5
3
00
14
N1 EPS, S00, 5A w/ RPL, HOA, EOL & CPT
EPS1-18-J-22
1
3
3
5
10
0
14
N1 EPS, S0, 22A w/ RPL, HOA, EOL & CPT
EPS1-32-J-22
1
3
5
7.5
15
1
14
N1 EPS, S1, 22A w/ RPL, HOA, EOL & CPT
EPS1-32-J-40
2
5
7.5
10
20
1
14
N1 EPS, S1, 40A w/ RPL, HOA, EOL & CPT
EPS1-50-J-40
3
7.5
10
10
30
2
15
N1 EPS, S2, 40A w/ RPL, HOA, EOL & CPT
EPS1-50-J-80
3
10
15
15
30
2
15
N1 EPS, S2, 80A w/ RPL, HOA, EOL & CPT
EPS1-85-J-80
7.5
15
20
25
50
3
27
N1 EPS, S3, 80A w/ RPL, HOA, EOL & CPT
EPS3R-9-J-5
EPS1-9-J-5
16
Single Phase
1/6
1/2
1
1.5
3
00
27
N3R EPS, S00, 5A w/ RPL, HOA, EOL & CPT
EPS3R-18-J-22
1
3
3
5
10
0
27
N3R EPS, S0, 22A w/ RPL, HOA, EOL & CPT
EPS3R-32-J-22
1
3
5
7.5
15
1
27
N3R EPS, S1, 22A w/ RPL, HOA, EOL & CPT
EPS3R-32-J-40
2
5
7.5
10
20
1
27
N3R EPS, S1, 40A w/ RPL, HOA, EOL & CPT
EPS3R-50-J-40
3
7.5
10
10
30
2
29
N3R EPS, S2, 40A w/ RPL, HOA, EOL & CPT
EPS3R-50-J-80
3
10
15
15
30
2
29
N3R EPS, S2, 80A w/ RPL, HOA, EOL & CPT
EPS3R-85-J-80
7.5
15
20
25
50
3
33
N3R EPS, S3, 80A w/ RPL, HOA, EOL & CPT
EPS4-9-J-5
1/6
1/2
1
1.5
3
00
15
N4 EPS, S00, 5A w/ RPL, HOA, EOL & CPT
EPS4-18-J-22
1
3
3
5
10
0
15
N4 EPS, S0, 22A w/ RPL, HOA, EOL & CPT
EPS4-32-J-22
1
3
5
7.5
15
1
15
N4 EPS, S1, 22A w/ RPL, HOA, EOL & CPT
EPS4-32-J-40
2
5
7.5
10
20
1
15
N4 EPS, S1, 40A w/ RPL, HOA, EOL & CPT
EPS4-50-J-40
3
7.5
10
10
30
2
19
N4 EPS, S2, 40A w/ RPL, HOA, EOL & CPT
EPS4-50-J-80
3
10
15
15
30
2
19
N4 EPS, S2, 80A w/ RPL, HOA, EOL & CPT
EPS4-85-J-80
7.5
15
20
25
50
3
26
N4 EPS, S3, 80A w/ RPL, HOA, EOL & CPT
EPS4XF-9-J-5
1/6
1/2
1
1.5
3
00
14
N4XF, EPS, S00, 5A w/ RPL, HOA, EOL, CPT
EPS4XF-18-J-22
1
3
3
5
10
0
14
N4XF, EPS, S0, 22A w/ RPL, HOA, EOL, CPT
EPS4XF-32-J-40
2
5
7.5
10
20
1
14
N4XF, EPS, S1, 40A w/ RPL, HOA, EOL, CPT
EPS4XF-50-J-80
3
10
15
15
30
2
16
N4XF, EPS, S2, 80A w/ RPL, HOA, EOL, CPT
EPS4XF-85-J-90
7.5
15
20
25
50
3
23
N4XF, EPS, S3, 90A w/ RPL, HOA, EOL, CPT
16
ECONOMY PUMP STARTER (EPS)
EPS EPS Dimensions D
15.7 7.5 6.1
EPS3R-9 to EPS3R-85
16
12
8
EPS4-9 to EPS4-32
10
8
6.2
EPS4-50
12
10
6
EPS4-85
14
12
6.5
EPS4XF-9 to EPS4XF-18
12
10
6
EPS4XF-32 to EPS4XF-85 14
12
6.2
Description
H1
H4
UL/NEMA 1 Enclosure UL/NEMA 3R Enclosure
TRANSFORMER PRIMARY CIRCUIT BREAKER SIZING V 208/230
VA
50VA 100VA
UL/NEMA 4 Enclosure
N/A 2A
480 N/A 1A
3
4
5 480V
EPS1-9 to EPS1-32
W
240V
H
208V
Starter Size
Wiring Diagram
CPT UL/NEMA 4X Fiberglass Enclosure
H2 *
120V
N EOL
*All measurements in inches
A2
A1
G H
O
A
EOL
X00
W
95
D
A2
M
96
A1
START 00X L1
2
1
L1
L2
H H1
H1
H4
L2
L3
H4 M
M AUX CONT
AUX CONT
EOL
EOL T1
T3
MTR NON COMB. 1-PHASE
*H2 Terminal does not apply for Type 1 enclosed configurations
T1
T2
T3
MTR NON COMB. 3-PHASE SCHM-EPS-V1
17
ECONOMY PUMP STARTER (EPS)
EPS EPS Specifications Starter Type Economy Pump Starter UL/NEMA Type 1, 3R, 4, and 4X Enclosure
User Interface HOA Selector switch with Run pilot light
Standard Control Operations Inputs Dry Auto Run
N.O. dry contact closure to energize starter
Mechanical Enclosure types
UL/NEMA Type 1, 3R, 4, or 4X
Environmental Ambient Operating Temp
-5° to 140° F (-20° to 60° C)
Ambient Storage Temp
-5° to 185° F (-20° to 85° C)
Relative Humidity
5% to 95% non-condensing
Protective Functions
18
Overload Type
Electronic; l²t Thermal Trip Curve
Current Setting Range
Class 1-30
Trip Class
Manual
Reset
Differential overload protection
Phase Unbalance
Trip within 3 seconds @ 70% unbalance
Phase Loss
Trip within 3 seconds
Stall Condition
Trip within 3 seconds @ 170% FLA
ADVANCED DUPLEX PUMP CONTROLLER (APX)
AP
ADVANCED DUPLEX PUMP CONTROLLER
50/60 Hz, 1Ø & 3Ø, 115~600 VAC, 1–200 hp HOA switches for independent local or remote operation Wide range electronic class 1-30 overload Advanced Lead/Lag & Alternating Operation • HOA switches for independent local or remote operation
• Automatic alternating control
• Wide range electronic class 1-30 overload with advanced protective features including phase loss, imbalance, stall protection, and manual reset
• Combination versions include a Circuit Breaker service disconnect which provides short circuit protection • Dual run pilot lights indicate motor operation
• Flexible control for 3-5 float switches
• Door-mounted alarm pilot light indicates high level alarm and float switch failure (identifies specific float number)
• Adjustable lag start delay and alternation settings
NEMA
19
AP Advanced Duplex Pump Controllers (Non-Combination) UL/NEMA 4 and 4X Fiberglass Enclosures (HOA & Electronic Overload) HP
UL/NEMA Type 4X Fiberglass
UL/NEMA Type 4
Enclosure Type
Model No.
Single-Phase 120 V
230 V
Three-Phase 200 V
230 V
460 V
575 V
SCIC KAIC @ 460 V
NEMA Size
Wt. (lbs)
Description
APX4-9-J-5
-
1/2
1
1.5
3
3
5
00
72
N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-18-J-22
1
3
5
5
10
15
5
0
72
N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-32-J-22
1.5
3
5
7.5
15
20
5
1
72
N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-32-J-40
2
5
7.5
10
20
25
5
1
72
N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-50-J-40
3
7.5
10
10
25
30
5
2
81
N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-50-J-80
3
10
20
20
40
50
5
2
81
N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-85-J-80
5
15
30
40
60
60
10
3
90
N4, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-9-J-5
-
1/2
1
1.5
3
3
5
00
53
N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-18-J-22
1
3
5
5
10
15
5
0
53
N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-32-J-22
1.5
3
5
7.5
15
20
5
1
53
N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-32-J-40
2
5
7.5
10
20
25
5
1
53
N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-50-J-40
3
7.5
10
10
25
30
5
2
41
N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-50-J-80
3
10
20
20
40
50
5
2
41
N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-85-J-80
5
15
30
40
60
60
10
3
61
N4X FG, Duplex Starters w/ No Disc Lead-Lag, Alt, 4FSw, PLC & CPT
Advanced Duplex Pump Controllers (Combination) UL/NEMA 4 and 4X Fiberglass Enclosures (HOA & Electronic Overload) HP
UL/NEMA Type 4
Enclosure Type
Model No.
120 V
230 V
APX4-9-J-G1.6-5
-
1/10
APX4-9-J-G2.5-5
-
1/6
UL/NEMA Type 4X Fiberglass
Three-Phase 200 V
NEMA Size
Wt. (lbs)
Description
230 V
460V
575 V
-
-
3/4
3/4
65
00
75
N4 Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT
1/2
1/2
1
1.5
65
00
75
N4 Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-9-J-G4-5
1/8
1/3
3/4
3/4
2
3
65
00
75
N4 Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-9-J-G6-5
1/4
1/2
1
1.5
3
3
65
00
75
N4 Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-18-J-G20-22
1/3
1
2
2
5
5
65
0
75
N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-18-J-G30-22
1/2
2
3
3
7.5
10
65
0
75
N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-18-J-G50-22
1
3
3
5
10
15
30
0
75
N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-32-J-G60-40
1.5
3
5
7.5
15
20
30
1
75
N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-32-J-G80-40
2
5
7.5
10
20
25
30
1
75
N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-50-J-G100-40
3
7.5
10
10
30
30
50
2
83
N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-50-J-G125-80
3
10
15
15
30
40
50
2
83
N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-85-J-G160-80
5
10
20
20
40
50
50
3
95
N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT
APX4-85-J-G200-80
5
15
20
25
50
60
50
3
95
N4 Duplex Starter w/ CB, Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-9-J-G1.6-5
-
1/10
-
-
3/4
3/4
65
00
56
N4 FG Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-9-J-G2.5-5
20
Single-Phase
SCIC KAIC @ 460 V
APXF-9-J-G4-5
-
1/6
1/2
1/2
1
1.5
65
00
56
N4 FG Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT
1/8
1/3
3/4
3/4
2
3
65
00
56
N4 FG Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-9-J-G6-5
1/4
1/2
1
1.5
3
3
65
00
56
N4 FG Duplex Starter w/ Mms, Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-18-J-G20-22
1/3
1
2
2
5
5
65
0
56
N4 FG Duplex Starter w/ CB Disc L ead-Lag, Alt, 4FSw, PLC & CPT
APXF-18-J-G30-22
1/2
2
3
3
7.5
10
65
0
56
N4 FG Duplex Starter w/ CB Disc L ead-Lag, Alt, 4FSw, PLC & CPT
APXF-18-J-G50-22
1
3
3
5
10
15
30
0
56
N4 FG Duplex Starter w/ CB Disc L ead-Lag, Alt, 4FSw, PLC & CPT
APXF-32-J-G60-40
1.5
3
5
7.5
15
20
30
1
56
N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-32-J-G80-40
2
5
7.5
10
20
25
30
1
56
N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-50-J-G100-40
3
7.5
10
10
30
30
50
2
64
N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-50-J-G125-80
3
10
15
15
30
40
50
2
64
N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-85-J-G160-80
5
10
20
20
40
50
50
3
66
N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT
APXF-85-J-G200-80
5
15
20
25
50
60
50
3
66
N4 FG Duplex Starter w/ CB Disc, Lead-Lag, Alt, 4FSw, PLC & CPT
ADVANCED DUPLEX PUMP CONTROLLER (APX)
AP APX Accessories Model No. APX-BCN
Wt. (lbs)
Description
1
Optional Top Mount Alarm Beacon Light, 120 VAC
APX-BZR
1
Optional Door Mounted Buzzer, 120 VAC w/ Silence Push button
APX-DHM
1
Optional Digital Hour Meters (2), 120 VAC
APX-FPL
1
Door Mounted Fault Pilot Lights
APX-GFCI
1
15A GFCI Option
APX-HRN
1
Optional Door Mounted Horn, 120 VAC w/ Silence Push button
APX-LSR
1
Optional Leak Seal Relays (2), 120 VAC
APX-RST
1
Door Mounted Overload Reset Push buttons
APX-STR
1
Optional Leak Seal Relays (2), High Temp, 120 VAC
APX Dimensions Starter Size
H
W
D
APX4-9 to APX4-32
24
20
8
APX4-40 to APX4-50
30
24
8
APX4-85
30
24
12
APX4-9-G to APX4-32-G
24
20
8
APX4-40-G to APX4-50-G
30
24
8
APX4-85-G
30
24
12
APXF-9 to APXF-50
24
20
8
APXF-85
30
24
10
APXF-9-G to APXF-32-G
24
20
8
APXF-50-G
30
24
10
APXF-85-G
30
24
10
Description UL/NEMA 4 Enclosure
W
D
UL/NEMA 4 Enclosure Combination UL/NEMA 4 Fiberglass Enclosure
H
UL/NEMA 4 Fiberglass Enclosure Combination
*All measurements in inches
21
AP Wiring Diagram
22
ADVANCED DUPLEX PUMP CONTROLLER (APX)
DUPLEX ALTERNATING PUMP CONTROLLER (DPX)
DUPLEX ALTERNATING PUMP CONTROLLER 50/60 Hz, 1Ø & 3Ø, 115~600 VAC, 1–200 hp Manual Pump Selection Switch Wide range electronic class 1-30 overload
ALTERNATING CONTROL TO EXTEND MOTOR LIFE • HOA switch and manual pump selection switch for flexible operation • Optional alternating control by relay, 24-hour timer, or 7-day clock • Wide range electronic class 1-30 overload with advanced protective features including phase loss, imbalance, stall protection, and manual reset • Combination versions include a MCP or MCCB disconnect which provides short circuit protection
NEMA
23
DUPLEX ALTERNATING PUMP CONTROLLER (DPX)
Duplex Alternating Pump Controllers (Non-Combination) UL/NEMA 4 and 4X Fiberglass Enclosures (HOA & Electronic Overload)
120 V
230 V
200 V
230 V
460 V
575 V
SCIC KAIC @ 460 V
UL/NEMA Type 4
DPX4-9-J-5 DPX4-18-J-22 DPX4-32-J-22 DPX4-32-J-40 DPX4-50-J-40 DPX4-50-J-80 DPX4-85-J-80
1 1.5 2 3 3 5
1/2 3 3 5 7.5 10 15
1 5 5 7.5 10 20 30
1.5 5 7.5 10 10 20 40
3 10 15 20 25 40 60
3 15 20 25 30 50 60
5 5 5 5 5 5 10
00 0 1 1 2 2 3
30 30 30 30 48 48 53
N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT
UL/NEMA Type 4X Fiberglass
HP
DPXF-9-J-5 DPXF-18-J-22 DPXF-32-J-22 DPXF-32-J-40 DPXF-50-J-40 DPXF-50-J-80 DPXF-85-J-80
1 1.5 2 3 3 5
1/2 3 3 5 7.5 10 15
1 5 5 7.5 10 20 30
1.5 5 7.5 10 10 20 40
3 10 15 20 25 40 60
3 15 20 25 30 50 60
5 5 5 5 5 5 10
00 0 1 1 2 2 3
26 26 26 43 43 43 50
N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT N4X FG Duplex Alternating Starter w/ EOL, HOA, M1/M2 Sw, CPT
NEMA Size
Wt. (lbs)
Description
Enclosure Type
Model No.
Single-Phase
Three-Phase
NEMA Size
Wt. (lbs)
Description
Duplex Alternating Pump Controllers (Combination) UL/NEMA 4 and 4X Fiberglass Enclosures (HOA & Electronic Overload)
24
Model No.
120 V
230 V
200 V
230 V
460 V
575 V
SCIC KAIC @ 460 V
UL/NEMA Type 4
DPX4-9-J-G1.6-5 DPX4-9-J-G2.5-5 DPX4-9-J-G4-5 DPX4-9-J-G6-5 DPX4-18-J-G8-22 DPX4-18-J-G10-22 DPX4-18-J-G13-22 DPX4-18-J-G17-22 DPX4-32-J-G22-40 DPX4-32-J-G26-40 DPX4-32-J-G32-40 DPX4-50-J-G40-40 DPX4-50-J-G50-80 DPX4-85-J-G63-80 DPX4-85-J-G75-80
1/8 1/4 1/3 1/2 1/2 1 1.5 2 2 3 3 5 5
1/10 1/6 1/3 1/2 1 1.5 2 3 3 3 5 7.5 10 10 15
1/2 3/4 1 2 2 3 3 5 7.5 7.5 10 15 20 20
1/2 3/4 1.5 2 3 3 5 7.5 7.5 10 10 15 20 25
3/4 1 2 3 5 5 7.5 10 15 15 20 30 30 40 50
3/4 1.5 3 3 5 7.5 10 15 20 20 25 30 40 50 60
65 65 65 65 65 65 65 30 30 30 30 50 50 50 50
00 00 00 00 0 0 0 0 1 1 1 2 2 3 3
36 36 36 36 36 36 36 36 36 36 36 50 50 58 58
N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT N4 Duplex Alternating Starter w/MMS, EOL, HOA, M1/M2 Sw, CPT
UL/NEMA Type 4X Fiberglass
HP Enclosure Type
DPXF-9-J-G1.6-5 DPXF-9-J-G2.5-5 DPXF-9-J-G4-5 DPXF-9-J-G6-5 DPXF-18-J-G8-22 DPXF-18-J-G10-22 DPXF-18-J-G13-22 DPXF-18-J-G17-22 DPXF-32-J-G22-40 DPXF-32-J-G26-40 DPXF-32-J-G32-40 DPXF-50-J-G40-40 DPXF-50-J-G50-80 DPXF-85-J-G63-80 DPXF-85-J-G75-80
1/8 1/4 1/3 1/2 1/2 1 1.5 2 2 3 3 5 5
1/10 1/6 1/3 1/2 1 1.5 2 3 3 3 5 7.5 10 10 15
1/2 3/4 1 2 2 3 3 5 7.5 7.5 10 15 20 20
1/2 3/4 1.5 2 3 3 5 7.5 7.5 10 10 15 20 25
3/4 1 2 3 5 5 7.5 10 15 15 20 30 30 40 50
3/4 1.5 3 3 5 7.5 10 15 20 20 25 30 40 50 60
65 65 65 65 65 65 65 30 30 30 30 50 50 50 50
00 00 00 00 0 0 0 0 1 1 1 2 2 3 3
28 28 28 28 28 28 28 28 28 28 28 40 40 46 46
N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT N4X FG Duplex Alternating Starter w/MMS Disc, EOL, HOA & CPT
Single-Phase
Three-Phase
DUPLEX ALTERNATING PUMP CONTROLLER (DPX)
DPX Accessories Model No.
Wt. (lbs)
Description
DPX-ALT
1
Optional Automatic Alternating Relay
DPX-CLK
1
Optional 7 Day, 24 Hr. Programmable Clock
DPX-FPL
1
Door Mounted Fault Pilot Lights
DPX-TMR
1
Optional Alternating 24 Hr. Timer
DPX Dimensions Starter Size
H
W
D
DPX(4/F)-9
14
12
6
DPX(4/F)-18
14
12
6
DPX(4/F)-32
14
12
6
DPX(4/F)-50
16
14
8
DPX(4/F)-85
16
14
8
DPX(4/F)-9-G
16
14
8
DPX(4/F)-18-G
16
14
8
DPX(4/F)-32-G
16
14
8
DPX(4/F)4-50-G
20
16
10
DPX(4/F)-85-G
20
16
10
Description W
D
UL/NEMA 4 OR 4X Fiberglass Enclosure
H UL/NEMA 4 OR 4X Fiberglass Enclosure w/ Disconnect
*All measurements in inches
25
DUPLEX ALTERNATING PUMP CONTROLLER (DPX)
Wiring Diagram
26
DIGITAL SOFT STARTER (MS6)
DIGITAL SOFT STARTER 50/60 Hz, 50-1000 hp, 200~600 VAC Optional Bypass Versions
HEAVY-DUTY RATED SOFT STARTER FOR PUMP APPLICATIONS
Keypad and LCD display for easy starter setup, status and diagnostics • Soft stop, up-to-speed contact, shorted SCR detection and line/load lugs standard with each unit • Enclosed models include control power transformer • 120 VAC control inputs for: Start/Stop/Jog/Reverse/Reset/Enable • Two or three wire control allow for remote operation options • Dry contact relay outputs for: Fault/Bypass/Running/Reverse
Operation & features • Provides smooth current ramp output to motor, eliminating surges and equipment shock • Adjustable ramp setting ranges (Up/Down 0-60 seconds) • Dual operation modes to match application needs: Constant Current mode for light duty or limited power supplies and Current Ramp mode for high inertia or heavy loads • Jog speeds: Forward at 14% of full speed, Reverse at 20% of full speed • DC injection braking option for enhanced performance
NEMA
Protective functions • Class 10~30 adjustable electronic overload • 500% overload for 30 seconds guarantees heavy duty operation • Single-phase protection • Instantaneous over-current trip • Shorted SCR fault output
Integrated bypass rated for emergency starts • Reduces enclosure size and eliminates need for additional cooling • Ensures reliable operation with automatic transition to bypass contactor at full speed • Eliminates downtime in critical applications
27
DIGITAL SOFT STARTER (MS6)
Digital Soft Starters (Standard Chassis) Model No.
HP
Wt. (lbs)
Description
30
30
MS6 Standard Chassis Soft Start, 30 A
50
30
MS6 Standard Chassis Soft Start, 50 A
230 V
460 V
575 V
MS6-30-CH
10
20
MS6-50-CH
20
40
MS6-80-CH
30
60
75
30
MS6 Standard Chassis Soft Start, 80 A
MS6-125-CH
50
100
125
40
MS6 Standard Chassis Soft Start, 125 A
MS6-250-CH
100
200
250
40
MS6 Standard Chassis Soft Start, 250 A
MS6-420-CH
150
350
400
50
MS6 Standard Chassis Soft Start, 420 A MS6 Standard Chassis Soft Start, 500 A
MS6-500-CH
200
400
500
93
MS6-600-CH
250
500
600
93
MS6 Standard Chassis Soft Start, 600 A
MS6-800-CH
300
600
800
125
MS6 Standard Chassis Soft Start, 800 A
MS6-1000-CH
400
800
1000
125
MS6 Standard Chassis Soft Start, 1000 A
Digital Soft Starters (Standard Chassis with Bypass Contactor) Model No.
HP 230 V
460 V
575 V
Wt. (lbs)
Description
MS6B-30-CH
10
20
30
30
MS6 Standard Chassis Soft Start with Bypass, 30 A
MS6B-50-CH
20
40
50
30
MS6 Standard Chassis Soft Start with Bypass, 50 A
MS6B-80-CH
30
60
75
30
MS6 Standard Chassis Soft Start with Bypass, 80 A
MS6B-125-CH
50
100
125
60
MS6 Standard Chassis Soft Start with Bypass, 125 A
MS6B-250-CH
100
200
250
60
MS6 Standard Chassis Soft Start with Bypass, 250 A
MS6B-420-CH
150
350
400
75
MS6 Standard Chassis Soft Start with Bypass, 420 A
MS6B-500-CH
200
400
500
140
MS6 Standard Chassis Soft Start with Bypass, 500 A
MS6B-600-CH
250
500
600
140
MS6 Standard Chassis Soft Start with Bypass, 600 A
MS6B-800-CH
300
600
800
188
MS6 Standard Chassis Soft Start with Bypass, 800 A
MS6B-1000-CH
400
800
1000
188
MS6 Standard Chassis Soft Start with Bypass, 1000 A
Digital Soft Starters (Enclosed) UL/NEMA 4 Enclosures Model No.
28
HP
Wt. (lbs)
Description
20
82.5
N4 Soft Start, 20 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
40
82.5
N4 Soft Start, 40 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
25
50
201
N4 Soft Start, 50 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
30
60
201
N4 Soft Start, 60 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
40
75
315
N4 Soft Start, 75 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
50
100
362
N4 Soft Start, 100 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
C4-SFS125GXX-J-PMP
60
125
361
N4 Soft Start, 125 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
C4-SFS150GXX-J-PMP
75
150
361
N4 Soft Start, 150 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
C4-SFS200GXX-J-PMP
100
200
361
N4 Soft Start, 200 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
C4-SFS300GXX-J-PMP
125
300
535
N4 Soft Start, 300 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
C4-SFS350GXX-J-PMP
150
350
605
N4 Soft Start, 350 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
C4-SFS400GXX-J-PMP
200
400
655
N4 Soft Start, 400 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
C4-SFS500GXX-J-PMP
250
500
655
N4 Soft Start, 500 HP, 460/3/60 w/ CB Disc, HOA, Pump Version
230 V
460 V
C4-SFS020GXX-J-PMP
-
C4-SFS040GXX-J-PMP
20
C4-SFS050GXX-J-PMP C4-SFS060GXX-J-PMP C4-SFS075GXX-J-PMP C4-SFS100GXX-J-PMP
DIGITAL SOFT STARTER (MS6)
MS6 Dimensions Starter Size
H
W
D
MS6-30-CH to MS6-80-CH
17
12
10.5
MS6-125-CH to MS6-250-CH
15
15
11.5
MS6-420-CH
19.5
15
11.5
MS6-500-CH to MS6-600-CH
19.5
18
13
MS6-800-CH to MS6-1000-CH
27
24
15
MS6B-30-CH
17
12
10.5
MS6B-50-CH to MS6-80-CH
21
12
10.5
20.5
15
11.5
MS6B-420-CH
27
15
11.5
MS6B-500-CH to MS6B-600-CH
27
18
13
MS6B-800-CH
35
24
15
MS6B-1000-CH
35
24
16
C4/SFS040GXX-J-PMP
24
20
10
C4-SFS050GXX-J-PMP to C4-SFS060GXX-J-PMP
36
24
16
C4-SFS075GXX-J-PMP
36
30
16
C4-SFS100GXX-J-PMP to C4-SFS200GXX-J-PMP
48
36
16
C4/SFS300GXX-J-PMP to C4-SFS350GXX-J-PMP
60
36
16
C4-SFS400GXX-J-PMP to C4-SFS500GXX-J-PMP
72
36
16
MS6B-125-CH to MS6B-250-CH
Description
Standard Chassis
Standard Chassis w/ Bypass Contactor
UL/NEMA 4 Enclosure
*All measurements in inches
W
D
H
29
DIGITAL SOFT STARTER (MS6)
Wiring Diagram
30
ANALOG SOFT STARTER (RVS)
RVS
ANALOG SOFT STARTER
50/60 Hz, 2-125 hp, 200~600 VAC Integrated electronic overload Bypass standard
EXTEND EQUIPMENT LIFE & REDUCE PEAK CURRENT DEMAND Standard features • Compact, space saving soft start with integrated electronic overload • Standard, built-in bypass • Aluminum chassis design ensures cool and efficient operation • Powder coated metal type 3R enclosure available • Integrated LED display and control terminals • Rated for line or inside delta motor connections
Comprehensive motor protection • Current limiting and integrated phase loss • Starter over-temperature shut down with reset push button • Metal Oxide Varistors (MOV) protect SCRs from damaging surges
NEMA
Easy setup & operation • LED display modes include: On, ramp up/down, run, overload, phase loss, over-temp • Simple dial adjustments for: motor FLA, initial voltage, current limit, ramp up/down times • Adjustable ramp setting ranges (up/down 0-30 seconds) • End of acceleration relay (1 N.O. contact) • Fault output relay (1 N.O. contact) • Auxiliary relays
31
ANALOG SOFT STARTER (RVS)
RVS Analog Soft Starters (Standard Chassis) HP Model No.
Three-Phase
Wt. (lbs)
230 V
460 V
575 V
RVS-AX-8
2
5
7.5
RVS-AX-17
5
10
15
RVS-AX-31
10
20
30
RVS-AX-58
20
40
50
RVS-AX-72
25
50
60
RVS-AX-85
30
60
75
RVS-AX-105
40
75
100
RVS-AX-145
50
100
125
RVS-AX-170
60
125
150
Description RVS Standard Chassis Soft Start, 8A
5.74
RVS Standard Chassis Soft Start, 17A RVS Standard Chassis Soft Start, 31A
11 18.5 26
RVS Standard Chassis Soft Start, 58A RVS Standard Chassis Soft Start, 72A RVS Standard Chassis Soft Start, 85A RVS Standard Chassis Soft Start, 105A RVS Standard Chassis Soft Start, 145A RVS Standard Chassis Soft Start, 170A
Analog Soft Starters (Enclosed) UL/NEMA 3R Enclosures (HOA)
HP Model No.
Three-Phase 230 V
Wt. (lbs)
575 V
C3R-SFS020GXX-J-PMP
10
20
C3R-SFS030GXX-J-PMP
15
30
C3R-SFS040GXX-J-PMP
20
40
C3R-SFS050GXX-J-PMP
25
50
C3R-SFS060GXX-J-PMP
30
60
C3R-SFS075GXX-J-PMP
40
75
C3R-SFS100GXX-J-PMP
50
100
C3R-SFS125GXX-J-PMP
60
125
32
Description
47
N3R Soft Start, 20 HP, 460/3/60 w/ CB Disc, HOA N3R Soft Start, 30 HP, 460/3/60 w/ CB Disc, HOA
52.1
N3R Soft Start, 40 HP, 460/3/60 w/ CB Disc, HOA N3R Soft Start, 50 HP, 460/3/60 w/ CB Disc, HOA
72 144
N3R Soft Start, 60 HP, 460/3/60 w/ CB Disc, HOA N3R Soft Start, 75 HP, 460/3/60 w/ CB Disc, HOA N3R Soft Start, 100 HP, 460/3/60 w/ CB Disc, HOA N3R Soft Start, 125 HP, 460/3/60 w/ CB Disc, HOA
ANALOG SOFT STARTER (RVS)
RVS RVS Dimensions Starter Size
H
W
D
RVS-AX-8 to RVS-AX-31
9.5
4.75
4.25
RVS-AX-58 to RVS-AX-72
11
5
7.5
RVS-AX-85 to RVS-AX-105
15
5
7.5
RVS-AX-145 to RVS-AX-170
15
7
8
C3R-SFS020GXX-J-PMP to C3R-SFS050GXX-J-PMP
22
15
8
C3R-SFS060GXX-J-PMP to C3R-SFS070GXX-J-PMP
32
15
8
C3R-SFS100GXX-J-PMP to C3R-SFS170GXX-J-PMP
30
24
12
Description
Standard Chassis
UL/NEMA 3R Enclosure
*All measurements in inches
W
D
H
33
RVS Wiring Diagram
34
ANALOG SOFT STARTER (RVS)
Large Drive Variable Speed Control is Just the Beginning Franklin FastApp™ Firmware • Pre-configured for easy operation and optimal performance • PSI unit display • Sleep and wake up • Lubrication output with timer - Provides a relay to control a lubrication solenoid for hollow shaft pump • Broken pipe detection - Monitors pump speed and system pressure. If minimum pressure isn’t met while pumping at full speed, system will trip after adjustable delay time • Dry-well/Underload detection with cycling timer • Pipe fill (Pre-PID) - VFD ramps up to Pre-PID frequency and fills pipes without pressurizing system • VFD auto-de-rating phase conversion • Pre-heat for motor windings in damp environments
Variable Speed Control • Space vector control for efficiency and long motor life. Cleaner sine wave as compared to typical V/Hz control. Motors run cooler and last longer • Automatic energy savings mode • Adaptive flux control for varying loads (e.g. damper loading)
NEMA
• Flying start protection prevents trips, rough starts, and drive damage from regenerative power due to heavy fan inertia rotation • Flux braking algorithm reduces deceleration time for enhanced system efficiency • Pre-heater function protects motor and inverter from damage when installed in damp location (e.g. green house)
Standard Features (Enclosed Drives) • Automatic carrier frequency change (adjusts based on temperature for optimal operation) • Selectable V/F, sensorless vector control • For outdoor and/or wash down applications • Rainproof 3R enclosure reduces thermal absorbtion with white, solar reflective finish and filtered cooling fans • Standard enclosed VFD package is rated for 110º ambient temperature, non-direct sunlight. • Additional application-specific protective devices included (i.e. lightning surge arrestor, line reactors, load reactors, and dV/dT filter)
Internal keypad menu for easy operation • All control and protective functions are easily programmable • The 32-character backlit LCD screen displays operational status and parameter settings
35
P-SERIES LARGE DRIVE
P-SERIES 3R ENCLOSED
Large Drive
Designed to withstand harsh environments
1
• 32 character keypad and pre-configured parameters for all common pump applications
2
3 4
1
5
7 6
Part Number Anatomy Part Family (Cerus Industrial Enclosed) Enclosure Rating (NEMA 3R) Pump Type (Centrifugal) Voltage Input Phase (1ø)
CIE3R-CENP050-P4/1 FE Reference Number Only VFD Model (P-Series) VFD Voltage Rating (460 V)
36
P-Series Pump Optimized VFD
2
Rugged outdoor 3R enclosure with cooling fans and filtration
3
Circuit breaker disconnect eliminates call backs due to fuse issues
4
Lightning arrestor protects VFD from large voltage spikes
5
Line reactor enhances protection from transient surges and provides a degree of harmonic mitigation
6
Control power transformer with breaker protection
7
Output filter for long motor leads
P-SERIES LARGE DRIVE
P-SERIES Ordering & Sizing Information P-Series (Enclosed) - Centrifugals Single-Phase & Three-Phase (200-230 V, 480 V) UL/NEMA 3R Enclosures Voltage
200-230 V
480 V
Model No.
HP
FLA
Wt. (lbs)
Description
CIE3R-CENP003-P2-1
3
12
179
N3R, 3 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP010-P2-1
10
32
202
N3R, 10 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP015-P2-1 (230V Only)
15
46
243
N3R, 15 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP020-P2-1 (230V Only)
20
60
268
N3R, 20 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP015-P2-3
15
60
202
N3R, 15 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP020-P2-3
20
74
207
N3R, 20 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP025-P2-3
25
88
243
N3R, 25 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP030-P2-3
30
115
268
N3R, 30 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP010-P4-1
10
16
197
N3R, 10 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP015-P4-1
15
24
219
N3R, 15 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP020-P4-1
20
30
245
N3R, 20 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP025-P4-1
25
39
279
N3R, 25 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP030-P4-1
30
45
279
N3R, 30 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP040-P4-1
40
55
289
N3R, 40 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP050-P4-1
50
75
366
N3R, 50 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP060-P4-1
60
91
368
N3R, 60 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP075-P4-1
75
110
1025
N3R, 75 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP100-P4-1
100
152
1060
N3R, 100 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP125-P4-1
125
183
1091
N3R, 125 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP150-P4-1
150
223
1746
N3R, 150 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP200-P4-1
200
264
1752
N3R, 200 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP015-P4-3
15
30
197
N3R, 15 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP020-P4-3
20
39
200
N3R, 20 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP025-P4-3
25
45
219
N3R, 25 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP030-P4-3
30
61
245
N3R, 30 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP040-P4-3
40
75
279
N3R, 40 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP050-P4-3
50
91
279
N3R, 50 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP060-P4-3
60
110
289
N3R, 60 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP075-P4-3
75
152
366
N3R, 75 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP100-P4-3
100
183
368
N3R, 100 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP125-P4-3
125
223
1007
N3R, 125 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP150-P4-3
150
264
1060
N3R, 150 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
CIE3R-CENP200-P4/3
200
325
1091
N3R, 200 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR
* Phase refers to incoming power, not motor.
Description Key
NOTE: The drive MUST BE sized according to the motor manufacturer’s maximum amperage draw. Upsize VFD for ambient temperature compensation (see VFD specs for temperature rating). (See Stand Alone drive section)
N3R
NEMA 3R Enclosure
1-Ph
Single-Phase
3-Ph
Three-Phase
† 600 V available upon request. Contact manufacturer for more details.
MCCB
Molded Case Circuit Breaker
LR
Line Reactor
OR
Output (Load) Reactor
OF
Output Filter
37
P-SERIES LARGE DRIVE
P-SERIES Ordering & Sizing Information P-Series (Enclosed) - Submersibles Single-Phase & Three-Phase (200-230 V, 480 V) UL/NEMA 3R Enclosures Voltage
Model No.
HP
FLA
Wt. (lbs)
Description
200-230 V
CIE3R-SUBP010-P2-1 (230 V Only) CIE3R-SUBP015-P2-1 (230 V Only) CIE3R-SUBP020-P2-1 (230 V Only) CIE3R-SUBP015-P2-3 CIE3R-SUBP020-P2-3 CIE3R-SUBP025-P2-3 CIE3R-SUBP030-P2-3
10 15 20 15 20 25 30
32 46 60 60 75 88 115
215 275 300 215 223 275 300
N3R, 10 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR, OR N3R, 15 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR, OR N3R, 20 hp, 230 V, 1-Ph Enclosed VFD, MCCB, LR, OR N3R, 15 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR, OR N3R, 20 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR, OR N3R, 25 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR, OR N3R, 30 hp, 230 V, 3-Ph Enclosed VFD, MCCB, LR, OR
CIE3R-SUBP010-P4-1 CIE3R-SUBP015-P4-1 CIE3R-SUBP020-P4-1 CIE3R-SUBP025-P4-1 CIE3R-SUBP030-P4-1 CIE3R-SUBP040-P4-1 CIE3R-SUBP050-P4-1 CIE3R-SUBP060-P4-1 CIE3R-SUBP075-P4-1 CIE3R-SUBP100-P4-1 CIE3R-SUBP125-P4-1 CIE3R-SUBP150-P4-1 CIE3R-SUBP200-P4-1 CIE3R-SUBP015-P4-3 CIE3R-SUBP020-P4-3 CIE3R-SUBP025-P4-3 CIE3R-SUBP030-P4-3 CIE3R-SUBP040-P4-3 CIE3R-SUBP050-P4-3 CIE3R-SUBP060-P4-3 CIE3R-SUBP075-P4-3 CIE3R-SUBP100-P4-3 CIE3R-SUBP125-P4-3 CIE3R-SUBP150-P4-3 CIE3R-SUBP200-P4-3
10 15 20 25 30 40 50 60 75 100 125 150 200 15 20 25 30 40 50 60 75 100 125 150 200
16 24 30 39 45 75 75 91 110 152 223 223 306 30 39 45 61 75 91 110 152 183 223 264 325
210 234 260 297 297 338 391 411 1068 1119 1156 1130 1476 212 215 238 263 297 304 332 409 427 1071 1130 1177
N3R, 10 hp, 460 V, 1-Ph Enclosed VFD, MCCB,LR,OF N3R, 15 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 20 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 25 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 30 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 40 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 50 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 60 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 75 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 100 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 125 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 150 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 200 hp, 460 V, 1-Ph Enclosed VFD, MCCB, LR, OF N3R, 15 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 20 hp, 460 V, 3-Ph Enclosed VFD, MCCB,LR,OF N3R, 25 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 30 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 40 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 50 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 60 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR N3R, 75 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 100 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 125 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 150 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF N3R, 200 hp, 460 V, 3-Ph Enclosed VFD, MCCB, LR, OF
480 V
* Phase refers to incoming power, not motor. NOTE: The drive MUST BE sized according to the motor manufacturer’s maximum amperage draw. Upsize VFD for ambient temperature compensation (see VFD specs for temperature rating). (See Stand Alone drive section) † 600 V available upon request. Contact manufacturer for more details.
38
Description Key N3R
NEMA 3R Enclosure
1-Ph
Single-Phase
3-Ph
Three-Phase
MCCB
Molded Case Circuit Breaker
LR
Line Reactor
OR
Output (Load) Reactor
OF
Output Filter
P-SERIES LARGE DRIVE
P-SERIES 3R Enclosed Dimension P-Series Model No. CIE3R-CENP003-P2-1 CIE3R-CENP010-P2-1 CIE3R-CENP015-P2-1 CIE3R-CENP020-P2-1
H
W
D
P-Series Model No. CIE3R-SUBP010-P2-1
H
W
D
35
24
12
35
24
12
41
24
12
CIE3R-SUBP020-P2-1
41
24
12
CIE3R-SUBP015-P2-3
47
24
14
35
24
12
CIE3R-SUBP015-P2-1
47
24
14
35
24
12
CIE3R-CENP025-P2-3
41
24
12
CIE3R-SUBP030-P2-3
41
24
12
CIE3R-CENP030-P2-3
47
24
14
CIE3R-SUBP010-P4-1
47
24
14
35
24
12
41
24
12
47
24
14
56
36
16
60
60
24
72
72
24
35
24
12
41
24
12
47
24
14
56
36
16
60
60
24
CIE3R-CENP015-P2-3 CIE3R-CENP020-P2-3
CIE3R-SUBP020-P2-3 CIE3R-SUBP025-P2-3
CIE3R-CENP010-P4-1
35
24
12
CIE3R-SUBP015-P4-1
CIE3R-CENP015-P4-1
41
24
12
CIE3R-SUBP020-P4-1 CIE3R-SUBP025-P4-1
CIE3R-CENP020-P4-1 CIE3R-CENP025-P4-1 CIE3R-CENP030-P4-1
47
24
14
CIE3R-CENP060-P4-1
56
36
16
60
60
24
CIE3R-CENP200-P4-1 CIE3R-CENP015-P4-3 CIE3R-CENP020-P4-3 CIE3R-CENP025-P4-3
72
72
24
35
24
12
41
24
12
CIE3R-CENP050-P4-3
47
24
14
CIE3R-CENP100-P4-3
56
36
16
60
60
24
CIE3R-SUBP200-P4-1 CIE3R-SUBP015-P4-3 CIE3R-SUBP020-P4-3 CIE3R-SUBP025-P4-3 CIE3R-SUBP030-P4-3 CIE3R-SUBP050-P4-3 CIE3R-SUBP060-P4-3 CIE3R-SUBP100-P4-3 CIE3R-SUBP125-P4-3 CIE3R-SUBP150-P4-3
CIE3R-CENP125-P4-3 CIE3R-CENP150-P4-3
CIE3R-SUBP125-P4-1
H
CIE3R-SUBP075-P4-3
CIE3R-CENP060-P4-3 CIE3R-CENP075-P4-3
D
CIE3R-SUBP040-P4-3
CIE3R-CENP030-P4-3 CIE3R-CENP040-P4-3
CIE3R-SUBP075-P4-1
W
CIE3R-SUBP150-P4-1
CIE3R-CENP125-P4-1 CIE3R-CENP150-P4-1
CIE3R-SUBP060-P4-1 CIE3R-SUBP100-P4-1
CIE3R-CENP075-P4-1 CIE3R-CENP100-P4-1
CIE3R-SUBP040-P4-1 CIE3R-SUBP050-P4-1
CIE3R-CENP040-P4-1 CIE3R-CENP050-P4-1
CIE3R-SUBP030-P4-1
CIE3R-SUBP200-P4-3
CIE3R-CENP200-P4-3 *All measurements in inches * Contact Franklin or visit www.franklin-electric.com for larger enclosed VFD dimensions
39
P-SERIES LARGE DRIVE
P-SERIES Ordering & Sizing Information P-Series (Stand Alone Large Drive) Single-Phase & Three-Phase (200-230 V)
Model No.
Output Full Load Amps 1Ø
3Ø
Wt. (lbs)
3% Line Reactor Model No.
Wt. (lbs)
CI-007-P2
12
24
11
KDRULB23LE01
18.5
CI-010-P2
16
32
13.2
KDRULD25LE01
22.5
CI-015-P2
23
46
13.2
KDRULD24LE01
22.5
CI-020-P2
30
60
29
KDRULD26LE01
22.5
CI-025-P2
37
74
30
KDRULC22LE01
25.5
CI-030-P2
44
88
44.1
KDRULF24LE01
67
CI-040-P2
57
115
44.1
KDRULF25LE01
67
* Phase refers to incoming power, not motor. NOTE: The drive MUST BE sized according to the motor manufacturer’s maximum amperage draw. Upsize VFD for ambient temperature compensation (see VFD specs for temperature rating).
P-Series (Stand Alone Large Drive) Single-Phase & Three-Phase (480 V)
Model No.
Output Full Load Amps
3% Line Reactor
Wt. (lbs)
Model No.
Wt. (lbs)
1Ø
3Ø
CI-007-P4
6
12
11
KDRULA4LE01
14.5
CI-010-P4
8
16
13.2
KDRULA5LE01
14.5
CI-015-P4
12
24
13.2
KDRULB2LE01
18.5
CI-020-P4
15
30
28
KDRULB1LE01
18.5
CI-025-P4
19
39
29
KDRULD1LE01
20.5
CI-030-P4
22
45
44.1
KDRULD2LE01
20.5
CI-040-P4
30
61
44.1
KDRULC1LE01
20.5
CI-050-P4
32
75
60
KDRULF2LE01
67
CI-060-P4
45
91
60
KDRULF4LE01
25.5
CI-075-P4
55
110
64
KDRULF3LE01
67
CI-100-P4
76
152
93
KDRULH3LE01
78
CI-125-P4
94
183
95
KDRULH2LE01
78
CI-150-P4
111
223
223
KDRULH1LE01
108
CI-200-P4
132
264
223
KDRULG3LE01
78
CI-250-P4
162
325
252
KDRULG1LE01
108
CI-350-P4
216
432
442
KDRULJ2LE01
78
CI-400-P4
273
547
442
KDRULJ1LE01
131
* Phase refers to incoming power, not motor. NOTE: The drive MUST BE sized according to the motor manufacturer’s maximum amperage draw. Upsize VFD for ambient temperature compensation (see VFD specs for temperature rating). † 600 V available upon request. Contact manufacturer for more details.
40
P-SERIES LARGE DRIVE
P-SERIES P-Series Large Drive Dimension
P-Series Drive
H
W
D
11.19
5.91
6.17
11.18
7.87
7.16
11.18
7.87
7.16
15.16
9.84
7.94
15.16
9.84
7.94
18.11
11.97
9.22
18.11
11.97
9.22
CI-050-P4
20.28
11.81
10.46
CI-007-P2 CI-007-P4 CI-010-P2 CI-010-P4 CI-015-P2 CI-015-P4 CI-020-P2 CI-020-P4 CI-025-P2
D
CI-025-P4 CI-030-P2 CI-030-P4 H
W
CI-040-P2 CI-040-P4 CI-060-P4
20.28
11.81
10.46
* Line Reactors housed in separate UL/NEMA 1 Type Enclosure
CI-075-P4
20.28
11.81
11.52
5.91”
CI-100-P4
23.09
14.57
13.29
CI-125-P4
23.09
14.57
13.29
CI-150-P4
30.26
20.80
16.64
CI-200-P4
30.26
20.80
16.64
CI-250-P4
33.23
20.80
16.64
41.85
21.17
17.70
43.7
30.8
17.4
51.3
36.3
19.5
6.17”
CI-350-P4 CI-400-P4 CI-500-P4 CI-600-P4 CI-700-P4
P-Series Large Drive Accessories Model No.
VFD-FPL VFD-GXX VFD-HOA VFD-KPD/4X VFD-KPD/4X VFD-KPS VFD-LTA VFD-RPL VFD-SPD P51-100G-A-I240-20MA P51-200G-A-I240-20MA P51-300G-A-I240-20MA
*All measurements in inches
Wt. (lbs)
Description
1 1 1 1 1 1 1 1 1 1 1 1
Fault Pilot Light (Red Standard) Circuit Breaker Disconnect Hand/Off/Auto Switch Door Mounted Keypad with Type 4X Cover NEMA 4X Waterproof Keypad Door Mounted Keypad Lightning Arrestor Run Pilot Light (Green Standard) Door Mounted Speed Potentiometer Transducer (Gauge pressure), 100 PSIG 4-20 mA, +/-0.5% accy Transducer (Gauge pressure), 200 PSIG 4-20 mA, +/-0.5% accy Transducer (Gauge pressure), 300 PSIG 4-20 mA, +/-0.5% accy
41
P-SERIES LARGE DRIVE
P-SERIES P-Series Accessories Line Reactors (for Stand Alone Drives ONLY) UL/NEMA 1 Enclosure Model No.
42
Wt. (lbs)
Voltage
Description
KDRULA54LE01
14.5
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 0.5 hp
KDRULA53LE01
14.5
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 0.75 hp
KDRULA25LE01
14.5
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 1 hp
KDRULA26LE01
14.5
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 1.5 hp
KDRULA27LE01
14.5
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 2 hp
KDRULA28LE01
14.5
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 3 hp
KDRULB22LE01
18.5
KDRULB23LE01
18.5
208/240 V
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 5 hp 3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 7.5 hp
KDRULD25LE01
22.5
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 10 hp
KDRULD24LE01
22.5
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 15 hp 3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 20 hp
KDRULD26LE01
22.5
KDRULC22LE01
25.5
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 25 hp
KDRULF24LE01
67
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 30 hp
KDRULF25LE01
67
3%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 40 hp
KDRULA54HE01
14.5
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 0.5 hp
KDRULA53HE01
14.5
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 0.75 hp
KDRULA25HE01
14.5
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 1 hp
KDRULA27HE01
14.5
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 1.5 hp
KDRULA26HE01
14.5
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 2 hp
KDRULA28HE01
14.5
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 3 hp
KDRULB25HE01
18.5
208/240 V
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 5 hp
KDRULB26HE01
18.5
KDRULD21HE01
22.5
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 7.5 hp 5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 10 hp
KDRULD22HE01
22.5
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 15 hp
KDRULC22HE01
25.5
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 20 hp
KDRULF28HE01
67
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 25 hp
KDRULF25HE01
67
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 30 hp
KDRULF26HE01
67
5%, 208/240 V, Enclosed Type 1 Line Reactor, UL Listed, 40 hp
KDRULA6LE01
14.5
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, .5 hp
KDRULA7LE01
14.5
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, .75 hp
KDRULA8LE01
14.5
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 1 hp 3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 1.5 hp
KDRULA9LE01
14.5
KDRULA1LE01
14.5
KDRULA2LE01
14.5
KDRULA3LE01
14.5
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 5 hp
KDRULA4LE01
14.5
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 7.5 hp
KDRULA5LE01
14.5
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 10 hp
KDRULB2LE01
18.5
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 15 hp
KDRULB1LE01
18.5
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 20 hp
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 2 hp 480 V
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 3 hp
P-SERIES LARGE DRIVE
P-SERIES P-Series Accessories - Continued Line Reactors (for Stand Alone Drives ONLY) UL/NEMA 1 Enclosure Model No.
Wt. (lbs)
Voltage
Description
KDRULD1LE01
20.5
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 25 hp
KDRULD2LE01
20.5
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 30 hp
KDRULC1LE01
25.5
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 40 hp
KDRULF2LE01
67
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 50 hp
KDRULF4LE01
67
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 60 hp
KDRULF3LE01
67
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 75 hp
KDRULH3LE01
78
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 100 hp
KDRULH2LE01
78
KDRULH1LE01
108
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 150 hp
KDRULG3LE01
131
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 200 hp
KDRULG1LE01
132
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 250 hp
KDRULG2LE01
132
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 300 hp
KDRULJ2LE01
150
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 350 hp
KDRULJ1LE01
150
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 400 hp
KDRULA6HE01
14.5
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, .5 hp
KDRULA7HE01
14.5
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, .75 hp
KDRULA8HE01
14.5
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 1 hp
KDRULA9HE01
14.5
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 1.5 hp
KDRULA1HE01
14.5
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 2 hp
KDRULA2HE01
14.5
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 3 hp
KDRULA3HE01
14.5
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 5 hp
KDRULA4HE01
15.5
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 7.5 hp
KDRULA5HE01
15.5
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 10 hp
KDRULB2HE01
17.5
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 15 hp
KDRULC3HE01
25.5
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 20 hp
KDRULC1HE01
25.5
KDRULE2HE01
26.5
KDRULF4HE01
67
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 40 hp
KDRULF1HE01
67
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 50 hp
KDRULF2HE01
67
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 60 hp
KDRULH2HE01
82
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 75 hp
KDRULI2HE01
82
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 100 hp
KDRULG3HE01
122
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 125 hp
KDRULG1HE01
127
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 150 hp
KDRULJ1HE01
136
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 200 hp
KDRULL1HE01
162
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 250 hp
KDRULL2HE01
162
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 300 hp
KDRULL3HE01
166
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 350 hp
KDRULL4HE01
176
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 400 hp
480 V
3%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 125 hp
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 25 hp 480 V
5%, 480 V, Enclosed Type 1 Line Reactor, UL Listed, 30 hp
43
P-SERIES LARGE DRIVE
P-SERIES P-Series Accessories - Continued Load Reactors (for Stand Alone Drives ONLY) UL/NEMA 1 Enclosure Model No.
44
Wt. (lbs)
Voltage
Description
KDRULA1PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 2 hp
KDRULA2PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 3 hp
KDRULA3PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 5 hp
KDRULA4PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 7.5 hp
KDRULB1PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 10 hp
KDRULD1PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 15 hp
KDRULD2PE01
18.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 20 hp
KDRULD3PE01
18.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 25 hp
KDRULD4PE01
22.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 30 hp
KDRULC1PE01
22.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 40 hp
KDRULF1PE01
22.5
KDRULF2PE01
25.5
KDRULF3PE01
67
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 75 hp
KDRULH1PE01
67
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 100 hp
KDRULI1PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 125 hp
KDRULI2PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 150 hp
KDRULG1PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 200 hp
KDRULJ1PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 250 hp
KDRULJ2PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 300 hp
KDRULL1PE01
14.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 350 hp
KDRULL2PE01
18.5
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 400 hp
480 V
3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 50 hp 3%, 480 V, Enclosed Type 1 Load Reactor, UL Listed, 60 hp
P-SERIES LARGE DRIVE
P-SERIES P-Series Accessories - Continued Output Filters (for Stand Alone Drives ONLY) UL/NEMA 1 Enclosure Model No.
Wt. (lbs)
Voltage
Description
V1K2A01
11
V1K, KLC Series Output Filter, N1 Enclosed, .75 hp @460 V
V1K3A01
11
V1K, KLC Series Output Filter, N1 Enclosed, 1-1.5 hp @460 V
V1K4A01
11
V1K, KLC Series Output Filter, N1 Enclosed, 2 hp @460 V
V1K6A01
11
V1K, KLC Series Output Filter, N1 Enclosed, 3 hp @460 V
V1K8A01
11
V1K, KLC Series Output Filter, N1 Enclosed, 5 hp @460 V
V1K12A01
11
V1K, KLC Series Output Filter, N1 Enclosed, 7.5 hp @460 V
V1K18A01
15
V1K, KLC Series Output Filter, N1 Enclosed, 10 hp @460 V
V1K21A01
15
V1K, KLC Series Output Filter, N1 Enclosed, 15 hp @460 V
V1K25A01
15
V1K, KLC Series Output Filter, N1 Enclosed, 15 hp @460 V
V1K27A01
15
V1K, KLC Series Output Filter, N1 Enclosed, 20 hp @460 V
V1K35A01
23
V1K, KLC Series Output Filter, N1 Enclosed, 25 hp @460 V
V1K45A01
23
V1K, KLC Series Output Filter, N1 Enclosed, 30 hp @460 V
V1K55A01
23
V1K80A01
29
V1K, KLC Series Output Filter, N1 Enclosed, 50/60 hp @460 V
V1K110A01
68
V1K, KLC Series Output Filter N1 Enclosed, 75 hp @460 V
V1K130A01
83
V1K, KLC Series Output Filter N1 Enclosed, 100 hp @460 V
V1K160A01
83
V1K, KLC Series Output Filter, N1 Enclosed, 125 hp @460 V
V1K200A01
93
V1K, KLC Series Output Filter, N1 Enclosed, 150 hp @460 V
V1K250A01
93
V1K, KLC Series Output Filter, N1 Enclosed, 200 hp @460 V
V1K305A01
117
V1K, KLC Series Output Filter, N1 Enclosed, 250 hp @460 V
V1K362A01
117
V1K, KLC Series Output Filter, N1 Enclosed, 300 hp @460 V
V1K420A01
132
V1K, KLC Series Output Filter, N1 Enclosed, 350 hp @460 V
V1K480A01
138
V1K, KLC Series Output Filter, N1 Enclosed, 400 hp @460 V
V1K600A01
168
V1K, KLC Series Output Filter, N1 Enclosed, 500 hp @460 V
V1K750A01
180
V1K, KLC Series Output Filter, N1 Enclosed, 600 hp @460 V
480 V
V1K, KLC Series Output Filter, N1 Enclosed, 40 hp @460 V
45
P-SERIES Wiring Diagram
*For general reference only, not field wiring. Consult installation instructions.
46
P-SERIES LARGE DRIVE
P-SERIES
P-SERIES LARGE DRIVE
Specifications Output Ratings
Input Ratings
Operation
Voltage (V)
Three -phase, 200~230 V, Three -phase, 380~480 V
Frequency (Hz)
0~120 Hz
Voltage (V)
Single/Three -phase, 200~230 V (-15%, +10%), Three -phase, 380~480 V (-15%, +10%)
Frequency (Hz)
50~60 Hz (±5%)
Input Power Factor
96%
Control Method
V/F control, sensorless vector control
Frequency Setting Resolution
Digital reference: 0.01 Hz (below 99 Hz) & 0.1 Hz (100 Hz and over); Analog reference: 0.06 Hz at 60 Hz
Frequency Setting Accuracy
Digital: 0.01% of maximum output frequency; Analog: 0.1% of maximum output frequency
V/F Ratio
Linear, Square, User V/F
Overload Capacity
1 minute at 120%, 10 seconds at 150% (with inverse characteristic proportional to time)
Torque Boost
Auto, manual (0~15%)
Multi-Function Input Terminals Total 8 inputs (programmable)
Input Signal
Output Signal
Protective Functions
Operating Environment
Analog Output
0~10 V linear
Operator Control
32-character LCD keypad, Terminals, ModBus-RTU communication Optional, ProfiBus-DP, DeviceNet, F-Net, BACnet, LonWorks
Frequency Setting
Analog: 0~10 V, 4~20mA, additional port for Sub-Board (0~10 V); Digital: Keypad, Communication
Start Signal
Forward, reverse
Multi-Step Operation
Setting up to 17 speeds (using multi-function terminal)
Multi-Step Accel/Decel Time
0.1~6000 seconds. Maximum 8 pre-defined steps using multi-function terminals
Operational Functions
DC braking, frequency limit, frequency jump, second motor function, slip compensation, reverse rotation prevention, auto restart, inverter bypass, auto-tuning, dual PID control
Emergency Stop
Stops output from inverter
Auto Operation
Operates from internal sequence by setting multi-function terminal (5 way x 8 step)
Jog
Jog operation
Fault Reset
Resets fault signal when protective function is active
Operational Status
Frequency detection, overload alarm, stall, overvoltage, undervoltage, inverter overheat, run, stop, constant speed, speed search, fault output, inverter bypass, auto-operation sequence
Indicator
Output frequency, output current, output voltage, DC voltage, output torque (output voltage: 0~10 V)
Trip
Overvoltage, undervoltage, overcurrent, inverter overheat, motor overheat, i/o -phase loss, fuse open, ground fault, external fault 1, 2, option fault, overload, speed command loss, hardware fault, communication error, etc.
Alarm
Stall, overload temperature sensor fault
Ambient Temperature
-10~40 °C (50 °C when derated 20%) or 14~104 °F (122 °F when derated 20%)
Storage Temperature
-20 ~65 °C or -4~149.5 °F
Humidity
Less than 95% relative humidity maximum (non-condensing)
Vibration
Below 5.9m²/sec (=0.6g)
Altitude
Below 1,000 m (3,300 ft): derate VFD by 10% for every additional 1,000 m
Application Site
Pollution degree 2. no corrosive gas, combustible gas, oil mist or dust
47
Notes:
48
Notes:
49
Notes:
50