K Appendix. Section K Appendix Electrical MONASH DESIGN & CONSTRUCTION STANDARDS. Page 1 of 7. Monash University Buildings and Property Division

Page 1 of 7 Section K – Appendix – Electrical Monash University Buildings and Property Division MONASH DESIGN & CONSTRUCTION STANDARDS K Appendix...
Author: Annice Murphy
8 downloads 0 Views 869KB Size
Page 1 of 7

Section K – Appendix – Electrical

Monash University Buildings and Property Division

MONASH DESIGN & CONSTRUCTION STANDARDS

K

Appendix ELECTRICAL

Monash Design & Construction Standards

REVISION

DEPT

REVIEWER/S

1/ April 2016

PLANNING

JL, SB, RB

SERVICES

AF, CM

Monash University 

Revision 01, 2016

Page 2 of 7

Section K – Appendix – Electrical TABLE OF CONTENTS K1 METER NETWORK DIAGRAM ...................................................................................................................... 3 K2 PRE-APPROVED EXTERNAL LIGHT FITTINGS ................................................................................................ 3 K3 LIGHTING CONTROL STRATEGY BY SPACE TYPE ........................................................................................... 3

Monash Design & Construction Standards

Monash University 

Revision 01, 2016

Page 3 of 7

Section K – Appendix – Electrical K1

METER NETWORK DIAGRAM

K2

PRE-APPROVED EXTERNAL LIGHT FITTINGS Versalux – STARLED

Iguzzini – Wow

Weef – RFL500_LED

K3

LIGHTING CONTROL STRATEGY BY SPACE TYPE The purpose of developing a lighting control strategy is to establish consistent a design and performance standard relevant to lighting controls within different space types. To develop a lighting control framework for different space types at Monash University, the following strategies listed in Table 1 were employed. These strategies provide the premise for appropriate lighting control within each space type – defined in Table 2. As a standard, lighting control is to be achieved via local smart sensors that are adjustable by any qualified electrician. Programmable control systems are acceptable subject to Monash approval for space types that require complex functions, e.g. multiple scene settings. Monash Design & Construction Standards Monash University 

Revision 01, 2016

Page 4 of 7

Section K – Appendix – Electrical Daylight harvesting is to be implemented where good day lighting is available, provided space size and other attributes justify its use. In spaces where operable walls are in located, lighting control will need to be reviewed on a case-by-case basis. For all implementation strategies, the position of control devices must enable ease of access for initial installation, wiring and testing, maintenance, removal and replacement of equipment and wiring during the life of the installation. Table 1 Description of the different types of lighting control strategies that are employed in the Monash University lighting control matrix in Table 2. Strategy Control Description Manual On/off switch Local switches to allow occupant on/off control of lights. Manual dimming Local stepped or continuous dimming with the DALI dimming protocol (e.g. for audio visual presentations) Multi-zone switch Local switches to allow occupant on/off control for multiple zones of lights. Override switch Central override of automatic controls Scheduling Time clock on Turn lighting on at pre-set daily time schedule Time clock off Turn lighting off at pre-set daily time schedule Occupancy Presence on/dim/off Detects presence to determine lights on (with motion), off (no motion) or dim then off (no motion) Acoustic on/dim/off Detects sound to determine lights on (with sound), off (no sound) or dim then off (no sound) Absence off Detects the absence of people to switch lighting off Auto-dim/off timer Field adjustable setting that determines how much (mins) time will pass before lights are either dimmed or turned off after last motion is detected Dimmed time (mins) Field adjustable setting that determines how much time lights are dimmed before turning off (where occupancy controlled dimming is utilised) Daylighting On/off Turn lighting off when daylight is detected, or turn lighting on when there is not enough daylight detected in a photocell in applicable zones Continuous dimming Detects using a photocell if the daylight level is too high or low to dim or increase lumen output as required with the DALI dimming protocol. AV AV system Low level or High level interfacing with lighting integration control - TBA regarding the AV functions HVAC HVAC integration Low level or High level interfacing with lighting control - depends on the HVAC system. HVAC integration to be a dedicated output/channel from the lighting control.

Monash Design & Construction Standards Monash University 

Revision 01, 2016

Page 5 of 7

Section K – Appendix – Electrical Table 2 The Monash University lighting control matrix for common University space types, with description of operation and a suggested strategy for implementation.

Computer laboratory

Conference/ Meeting



Conference room



Meeting





30



15





15

External Feature Lighting



Fitness & rec.



Gallery/Museum



Kitchen



Legend ● Required ○ Where appropriate HVAC integration

AV system integration

Continuous dimming

On/off

HVAC























1

15



External

AV

20





Daylighting

Dimmed time (mins)

Auto-dim/off timer (mins)



Absence off





Corridor/ circulation

General facility

Acoustic on/dim/off

Amenities

Occupancy

Presence on/dim/off

Time clock off

Time clock on

Scheduling

Override switch

Multi-zone switch

Space Type

Manual dimming

On/off switch

Manual

15







Monash Design & Construction Standards Monash University 



15



Revision 01, 2016



Operational Description Lights ON via presence detection or sound. Lights stay ON with movement or sound. After no movement or sound for 20 mins, lights turn OFF. Lights ON via switch or presence detection. Lights stay ON with movement. After no movement for 30 mins, lights DIM to minimum level for 1 min, then turn OFF. Lights also OFF via switch. Daylight harvesting active where appropriate. Sensors to be integrated into the HVAC control strategy. Lights ON via switch only. Lights stay ON with movement. After no movement for 15 mins, lights turn OFF via absence detection. Sensors to be integrated into the HVAC control strategy. Depending on the room size and equipment, provide separately zoned lighting that can be dimmed/switched OFF in front of visual displays or provide AV integration if applicable. Entry and junction points: 24 hour lighting utilised where appropriate Remaining lights: Lights ON via presence detection. Lights connected in master/slave configurations for defined spaces. Lights stay ON with movement. After no movement for 15 mins, lights turn off. Lights ON/OFF via presence detection only. Daylight harvesting active where appropriate Lights ON via lux detection or override switch. Lights stay ON when lux is lower than minimum lux threshold. When enough lux is provided by sunlight, lights turn OFF. Lights also OFF via override switch. Lights ON via lux detection or override switch. Lights stay ON when lux is lower than minimum lux threshold. When enough lux is provided by sunlight, lights turn OFF. Lights also OFF via override switch or timeclock. Lights ON via switch or presence detection. Lights stay ON with movement. After no movement for 15 mins, lights turn OFF. Lights also OFF via switch. Daylight harvesting active where appropriate. Sensors to be integrated into the HVAC control strategy. Lights ON via switch. Lights able to be switched ON/OFF in zones, with dimming capabilities. Lights OFF via switch. Lights ON via switch or presence detection. Lights stay ON with movement. After no movement for 15 mins, lights turn OFF. Lights also OFF via switch. Daylight harvesting active where appropriate. Sensors to be integrated into the HVAC control strategy where appropriate.

Suggested Implementation Strategy Easy to set ceiling mounted motion detector with integrated acoustic sensor. Easy to set ceiling mounted motion detector with lighting control and HVAC integration. In areas with daylight harvesting, an easy to set ceiling mounted motion detector with PE cell for continuous dimming. Easy to set ceiling mounted motion detector with lighting control and HVAC integration. Where AV integration is required a programmable lighting control system may be used.

Entry and junction points: 24 hour lighting Remaining lights: Easy to set ceiling mounted long range motion detector with lighting control. In areas with daylight harvesting, an easy to set ceiling mounted motion detector with PE cell for continuous dimming.

Either by easy to set surface mounted PE cell sensor with lighting control, or interface with BAS PE cell sensors if applicable. Easy to set surface mounted photocell sensor with lighting control and interfacing BAS timeclock functionality Easy to set ceiling mounted motion detector with lighting control and HVAC integration. In areas with daylight harvesting, an easy to set ceiling mounted motion detector with PE cell for continuous dimming. Labelled manual wall switches with multi-zones and/or manual dimmers if required. Easy to set ceiling mounted motion detector with lighting control and HVAC integration (if applicable). In areas with daylight harvesting, an easy to set ceiling mounted motion detector with PE cell for continuous dimming.

Page 6 of 7

Section K – Appendix – Electrical

Staff room

Laboratory/ Studio



Laboratory



Studio

● ●

Non-UFA

15





● ●

Store room







● ●

Operational Description Lights ON via switch or presence detection. Lights stay ON with movement. After no movement for 15 mins, lights DIM to minimum level for 1 min, then turn OFF. Lights also OFF via switch. Daylight harvesting active where appropriate. Sensors to be integrated into the HVAC control strategy. Lights ON via switch or presence detection. Lights stay ON with movement. After no movement for 15 mins, lights turn OFF. Lights also OFF via switch. Daylight harvesting active where appropriate. Sensors to be integrated into the HVAC control strategy where appropriate. Lights ON/OFF via switch. Daylight harvesting active where appropriate.

Lights ON/OFF via switch only. Lights ON/OFF via switch only.

● ●



Plant room Roof access

Legend ● Required ○ Where appropriate









15









30



Lift

Foyer/lobby

HVAC

HVAC integration

1

AV

AV system integration

15

Continuous dimming

Daylighting

On/off

Absence off

Acoustic on/dim/off





Airlock

Presence on/dim/off

Time clock off

Time clock on





Workshop

Library

Override switch



Occupancy

Dimmed time (mins)

Lounge

Scheduling

Auto-dim/off timer (mins)

General facility (cont'd)

Multi-zone switch

Space Type

Manual dimming

On/off switch

Manual





Monash Design & Construction Standards Monash University 



15







Lighting operation within library spaces subject to user approval of the lighting design. Lighting control within library spaces to be confirmed at a later date. Lights ON via presence detection. Lights stay ON during operating hours. During after hours, after no movement for 30 mins, lights turn OFF. Lights also OFF via timeclock, provided there is no movement. Daylight harvesting active where appropriate. Dependent on ability for lift to activate sleep mode, where car has lights, ventilation, music and/or video screens off. Lights ON via presence detection. Lights stay ON during operating hours. During after hours, after no movement for 15 mins, lights turn OFF. Lights also OFF via timeclock, provided there is no movement. Daylight harvesting active where appropriate. Lights ON/OFF via switch. Lights ON/OFF via switch. Lights ON via switch only. Lights stay ON with movement. After no movement for 15 mins, lights turn OFF via absence detection.

15

Revision 01, 2016

Suggested Implementation Strategy Easy to set ceiling mounted motion detector with lighting control and HVAC integration. In areas with daylight harvesting, an easy to set ceiling mounted motion detector with PE cell for continuous dimming. Easy to set ceiling mounted motion detector with lighting control and HVAC integration (if applicable). In areas with daylight harvesting, an easy to set ceiling mounted motion detector with PE cell for continuous dimming. Manual wall switches with multi-zones and/or manual dimmers if required. In areas with daylight harvesting, an easy to set ceiling mounted PE cell detector for continuous dimming. Manual wall switches with multi-zone switching Manual wall switches with multi-zones and/or manual dimmers as required. Decentralised local smart control preferred. A controllable network system may be justified upon Monash BPD approval. Easy to set ceiling mounted motion detector with lighting control and interface with BAS timeclock. In areas with daylight harvesting, an easy to set ceiling mounted PE cell detector for continuous dimming. A controllable network system may be justified upon Monash BPD approval. N/A Easy to set ceiling mounted motion detector with lighting control and interface with BAS timeclock. In areas with daylight harvesting, an easy to set ceiling mounted PE cell detector for continuous dimming. A controllable network system may be justified upon Monash BPD approval. Manual wall switches Manual wall switches Easy to set ceiling mounted motion detector with lighting control.

Page 7 of 7

Section K – Appendix – Electrical





HVAC

Legend ● Required ○ Where appropriate HVAC integration

1

AV

AV system integration

15

Continuous dimming

Daylighting

On/off

Absence off

Acoustic on/dim/off

Presence on/dim/off

Time clock off

Time clock on

Override switch



Occupancy

Dimmed time (mins)



Scheduling

Auto-dim/off timer (mins)

Office (open)

Multi-zone switch

Space Type

Manual dimming

On/off switch

Manual



Office Office (private)

Reception









Stairs (enclosed)

Teaching



Lecture Theatre

Tutorial Rooms











Monash Design & Construction Standards Monash University 



15



30



15



15



15



1



Revision 01, 2016





Operational Description Lights ON via switch or presence detection. Lights stay ON with movement. After no movement for 15 mins, lights DIM to minimum level for 1 min, then turn OFF. Lights also OFF via switch. Daylight harvesting active where appropriate. Sensors to be integrated into the HVAC control strategy. Lights ON via switch only. Lights stay ON with movement. After no movement for 15 mins, lights turn OFF via absence detection. Sensors to be integrated into the HVAC control strategy if appropriate. Lights ON via switch only. Lights stay ON with movement. After no movement for 30 mins, lights turn OFF. Daylight harvesting active where appropriate. Sensors to be integrated into the HVAC control strategy. Lights ON via presence detection. Lights connected in master/slave configurations for entire stairwell. Lights stay ON with movement. After no movement for 15 mins, lights turn OFF. Lights ON/OFF via presence detection only. Aisle lights ON via presence detection. All other lights ON via switches. All lights stay ON with movement. After no movement for 15 mins, lights DIM to minimum level for 1 min and then turn OFF. Lights also OFF via switch. Lighting also integrated with AV system and controlled at the lectern with multiple pre-set configurations and designed with Monash University AV design guidelines as supported by eSolutions. Sensors to be integrated into the HVAC control strategy. Lights ON via switch or presence detection. Lights stay ON with movement. After no movement for 15 mins, lights turn OFF. Lights also OFF via switch. Daylight harvesting active where appropriate. Sensors to be integrated into the HVAC control strategy.

Suggested Implementation Strategy Easy to set ceiling mounted motion detector with lighting control and HVAC integration. In areas with daylight harvesting, an easy to set ceiling mounted motion detector with PE cell for continuous dimming. Easy to set ceiling mounted motion detector with lighting control and HVAC integration (if applicable).

Easy to set ceiling mounted motion detector with lighting control and HVAC integration. In areas with daylight harvesting, an easy to set ceiling mounted motion detector with PE cell for continuous dimming. Easy to set ceiling mounted motion detector with lighting control.

A controllable network system may be justified upon Monash BPD approval.

Easy to set ceiling mounted motion detector with lighting control and HVAC integration. In areas with daylight harvesting, an easy to set ceiling mounted motion detector with PE cell for continuous dimming.