Instruction Leaflet IL01301032E

effective January 2011 supersedes IL01301032H01

Series NRX

Instructions for Series NRX Neutral Current Sensor – Type NF Instructions apply to:

Series NRX, Type NF Frame ANSI, UL1066, UL489 / IEC, IZMX16, IZM91

1600 NRX SUB-TITLE IMAGE (12/15/2010)

• Warning (1) Only qualified electrical personnel should be permitted to work on the equipment. (2) Always de-energize primary and secondary circuits if a circuit breaker cannot be removed to a safe work location. (3) Drawout circuit breakers should be levered (racked) out to the Disconnect position. (4) All circuit breakers should be switched to the off position and mechanism springs discharged. Failure to follow these steps for all procedures described in this instruction leaflet could result in death, bodily injury, or property damage.

• Warning The instructions contained in this IL and on product labels have to be followed. Observe the Five Safety Rules: – Disconnecting – Ensure that devices cannot be accidentally restarted – Verify isolation from the supply – Earthing and short-circuiting – Covering or providing barriers to adjacent live parts Disconnect the equipment from the supply. Use only authorized spare parts in the repair of the equipment. The specified maintenance intervals as well as the instructions for repair and exchange must be strictly adhered to prevent injury to personnel and damage to the switchboard.

Instruction Leaflet IL01301032E

Instructions for Series NRX Neutral  Current Sensor – Type NF 

effective January 2011

Section 1: Neutral Current Sensor Installation Ground Fault Trip Units detect ground fault currents through Residual Sensing. A different, round, torroidal sensor is required for source ground or zero sequence sensing. All further information is for residual ground fault sensing method only. If the system neutral is grounded and residual ground fault is desired, but no phase to neutral loads are used, a neutral current sensor is not necessary. In that case, no additional connections are required to circuit breaker secondary contacts. If the system neutral is grounded and phase to neutral loads are used, then the neutral current sensor (see Figure 2 and 3) must be used to account for this load in the residual ground fault sensing. It has the same turns ratio as the phase current sensors in the Series NRX circuit breaker. The neutral sensor is an air core design and can be used with all Type NF rating plugs (Figure 1).

Section 2: Performance Testing For Ground Fault Circuit Breakers Code Requirements In the United States of America and certain other countries it is required that any ground fault protection system be performance tested when first installed (National Electric Code under Article 23095-C). Conduct tests in accordance with the approved instructions provided with the equipment. Make a written record of this test and make the results available to the authority having inspection jurisdiction.

Standards Requirements In addition to the basic performance requirements stated above, UL Standard No. 1053 requires that certain minimum instructions accompany each ground fault protection system.

General Test Instructions

• IMPORTANT The polarity of the sensor connections is critical. Always observe the polarity markings on the installation drawings. The polarity markings are identified as white dots on the transformers. To insure correct ground fault equipment performance, conduct field tests to comply with National Electric Code requirements under Article 230-95-C. See Performance Testing instructions on following pages.

5.440” 138,9 mm

The interconnect system shall be evaluated in accordance with the equipment assembler’s detailed instruction by qualified personnel. The polarity of the neutral sensor connection (if used) must agree with equipment assembler’s detailed instructions to avoid improper operations following apparently correct simulated test operations. Where a question exists, consult the specifying engineer and/or equipment assembler.

+

1.062” 27,0 mm

2.000” 50,8 mm

.469” 11,9 mm

1.230” 30,5 mm

3.344” 85,0 mm

2.750” 69,9 mm

1.250” 31.8 mm 4.37” 111,2 mm 6.000” at Base 152,4 mm

Figure 1. Sensor Installation Information - Type NF

2

2.750” at top 69,9 mm 2.250” at top 57,2 mm 2.188” 55,6 mm

Torque to 20 lb in ±2 27,1 Nm ±2,7 T/Conductor

5.860” 148,9 mm 1.440” 36,6 mm

T/Potting

Torque to 50 lb ft ±3 67,8 Nm ± 4,1

Polarity Markings

eaton corporation www.eaton.com

2.330” at base 59,9 mm 3.040” at base 77,2 mm

Instructions for Series NRX Neutral Current Sensor – Type NF The grounding points of the system shall be verified to determine that ground paths do not exist that would bypass the sensors. High-voltage testers and resistance bridges may be used. Source L C R

N 16

effective January 2011

Using a low voltage (0-24v) high current AC source, apply a test current of 125% of the ground fault pick-up setting through one phase of the circuit breaker as displayed in Figures 4 and 7. This should cause the breaker to trip in less than 1 second, and if an alarm indicator is supplied, it should operate. Reset the breaker and the alarm indicator. Repeat the test on the other two phases. If the system is a 4-wire system with a neutral current sensor, apply the same current as described above through one phase of the breaker, returning through the neutral sensor, as displayed in Figures 5 and 8. The breaker should not trip and the alarm indicator, if supplied, should not operate. Repeat the test on the other two phases.

X

15

IL01301032E

If the system is a 3-wire system with no neutral current sensor, apply the same current as described above through any two phases of the breaker with the connections as displayed in Figures 6 and 9. The breaker should not trip and the alarm indicator, if supplied, should not operate.

X

Neutral Sensor

Repeat the test using the other two combinations of breaker phases. Record the test results on the test form provided with the equipment.

Load

Figure 2. Neutral Current Sensor Application (NEMA) Source L C R

N 16

WARNING ELECTRICAL SHOCK OR BURN INJURY CAN OCCUR WHEN WORKING ON POWER SYSTEMS. ALWAYS TURN OFF POWER SUPPLYING CIRCUIT BREAKER BEFORE CONDUCTING TESTS. TEST OUT OF THE CELL, IF POSSIBLE.

X

15

CAUTION FIELD TESTING SHOULD BE USED FOR FUNCTIONAL TESTING, NOT FOR FIELD CALIBRATION. IF TEMPORARY CONNECTIONS WERE MADE FOR THE PURPOSE OF CONDUCTING TESTS, RESTORE TO PROPER OPERATING CONDITIONS BEFORE RETURNING THE BREAKER TO SERVICE.

X

Neutral Sensor

Load

Figure 3. Neutral Current Sensor Application (IEC) N ote: Since the ground fault circuit breakers derive their operating power from the phase current and not from the neutral current, passing current through the neutral sensor only will not properly test the ground fault feature.

EATON CORPORATION www.eaton.com

3

Instruction Leaflet IL01301032E

Instructions for Series NRX Neutral  Current Sensor – Type NF 

effective January 2011

Low Voltage Source

Low Voltage Source

Low Voltage Source Source

Source

Source

Load

Load Current Limiting Resistor (if required)

Figure 4. Connections for Ground Fault Trip Test (NEMA)

Load Current Limiting Resistor (if required)

Figure 5. Connections for Ground Fault No-Trip Test with a 4 Wire System (NEMA)

Low Voltage Source

Current Limiting Resistor (if required)

Figure 6. Connections for Ground Fault No-Trip Test with a 3 Wire System (NEMA)

Low Voltage Source

Low Voltage Source Source

Source

Source

Load

Load Current Limiting Resistor (if required)

Figure 7. Connections for Ground Fault Trip Test (IEC)

4

Load Current Limiting Resistor (if required)

Figure 8. Connections for Ground Fault No-Trip Test with a 4 Wire System (IEC)

eaton corporation www.eaton.com

Current Limiting Resistor (if required)

Figure 9. Connections for Ground Fault No-Trip Test with a 3 Wire System (IEC)

Instructions for Series NRX Neutral  Current Sensor – Type NF 

Instruction Leaflet IL01301032E effective January 2011

eaton corporation www.eaton.com

5

Instruction Leaflet IL01301032E

Instructions for Series NRX Neutral  Current Sensor – Type NF 

effective January 2011

Disclaimer of warranties and limitation of liability The information, recommendations, descriptions, and safety notations in this document are based on Eaton Corporation’s (“Eaton”) experience and judgment, and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.

In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations, and descriptions contained herein.

The information contained in this manual is subject to change without notice.

Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN-CARE (877-386-2273) Eaton.com © 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL01301032EH02 January 2011

6

eaton corporation www.eaton.com

Power Chain Management is a registered Trademark of Eaton Corporation All other Trademarks are property of their respective owners.

Instruction Leaflet IL01301032E

gültig ab Januar 2011 ersetzt IL01301032H01

Series NRX

Montageanweisung für Series NRX Neutralwandler - Baugröße NF Die Montageanweisung ist für folgende Baugrößen gültig:

Series NRX, Type NF Frame ANSI, UL1066, UL489 / IEC, IZMX16, IZM91

1600 NRX SUB-TITLE IMAGE (12/15/2010)

• warnUng

(1) Die Instandhaltung darf nur durch entsprechend elektrontechnisch qualifiziertes Personal erfolgen. (2) Vor Beginn der Arbeiten muss der spannungsfreie Zustand der Schaltanlage hergestellt und während der Arbeiten sichergestellt sein. (3) Schalter in Ausfahrtechnik müssen in Trennstellung gefahren werden. (4) Die Schalter sind auf AUS zu stellen und der Federspeicher ist zu entspannen. Beim Betrieb elektrischer Geräte stehen zwangsläufig bestimmte Teile dieser Geräte unter gefährlicher Spannung. UnsachgemäSSer Umgang mit diesen Geräten kann deshalb zu Tod oder schweren Körperverletzungen sowie erheblichen Sachschäden führen.

• warnUng Beachten Sie bei InstandhaltungsmaSSnahmen an diesem Gerät alle in dieser AWA und auf dem Produkt selbst aufgeführten Hinweise. Die fünf Sicherheitsregeln sind einzuhalten – Freischalten – Gegen Wiedereinschalten sichern – Spannungsfreiheit feststellen – Erden und KurzschlieSSen – Benachbarte, unter Spannung stehende teile abdecken oder abschranken Das Gerät ist vom Netz zu trennen. Es dürfen nur vom Hersteller zugelassene Ersatzteile verwendet werden. Die vorgeschriebenen Wartungsintervalle sowie die Anweisungen für Reparatur und Austausch sind unbedingt einzuhalten, um Schäden an Personen und Anlagen zu vermeiden.

Instruction Leaflet IL01301032E

Montageanweisung für Series NRX  Neutralwandler - Baugröße NF 

gültig ab Januar 2011

Abschnitt 1: Installation des Neutralwandlers Die Fehlerstrommessung ist die Standardmethode für Erdschlussmessungen in NRX-Leistungsschaltern. Für die Fehlerstromquellenmessung oder die Nullmessung wird ein anderer Wandler-Typ benötigt. Die folgenden Informationen betreffen nur die Fehlerstrommessung. Wenn das Neutralsystem geerdet ist und als Messmethode die Fehlerstrommessung verwendet wird, aber keine Phase zu Neutrallasten verwendet wird, dann ist der Einsatz eines Neutralwandlers nicht erforderlich. In diesem Falle sind auch keine weiteren Verbindungen zu den Steuerleitungsanschlüssen nötig. Wenn das Neutralsystem geerdet ist und eine Phase zu Neutrallasten verwendet wird, dann ist der Einsatz des Neutralwandlers (siehe Abbildung 2 und 3) erforderlich. Dieser hat das gleiche Verhältnis wie die Stromwandler. Der Neutralwandler hat einen Luftkern und kann mit allen für die Baugröße NF kompatiblen Bemessungsstrommodulen verwendet werden (siehe Abbildung 1).

Abschnitt 2: Funktionsprüfung für Leistungsschalter mit Erdschlussschutz Prüfanforderungen für Nordamerika und andere Länder In Nordamerika und bestimmten anderen Ländern ist es vorgeschrieben, dass jedes Erdschlussgerät vor der ersten Inbetriebnahme einer Funktionsprüfung unterzogen wird (siehe National Electric Code Artikel 230-95-C). Führen Sie die Prüfung gemäß der genehmigten und mit der Ausrüstung gelieferten Anleitung durch und fertigen Sie einen schriftlichen Bericht über die Durchführung des Tests an.

Normen Als Zusatz zu den grundlegenden von der NEC vorgeschriebenen Leistungsanforderungen wird durch UL -Norm 1053 gefordert, dass jedem Erdschlussschutzsystem eine Anleitung mit einem bestimmten Mindestumfang beigelegt werden muss.

• ACHTUNG Fehlerhaftes AnschlieSSen der Stromwandler kann zu Fehlauslösungen führen . Beachten Sie immer die Polmarkierungen der Montagepläne. DIe Polmarkierungen sind als weiSSe Punkte auf den Wandlern markiert. Führen Sie zur Sicherstellung des ordnungsgemäSSen Betriebs der Erdschlussausrüstung Vor-Ort-Tests gemäSS National Elecetric Code (NEC) 230-95-C durch.

5.440” 138,9 mm

+

1.062” 27,0 mm

2.000” 50,8 mm

0.469” 11,9 mm

1.230” 30,5 mm

3.344” 85,0 mm

2.750” 69,9 mm

1.250” 31.8 mm 4.37” 111,2 mm 6.000” Unterseite 152,4 mm

Abbildung 1. Abmessungen Neutralwandler - Baugröße NF

2

2.750” Oberseite 69,9 mm 2.250” Oberseite 57,2 mm 2.188” 55,6 mm

Anziehen auf 20 lb in ±2 27,1 Nm ±2,7 T/Conductor

5.860” 148,8 mm 1.440” 36,6 mm

T/Potting

Anziehen auf 50 lb ft ±3 67,8 Nm ± 4,1

Polmarkierungen

eaton corporation www.eaton.com

2.330” Unterseite 59,9 mm 3.040” Unterseite 77,2 mm

Montageanweisung für Series NRX  Neutralwandler - Baugröße NF  Allgemeine Prüfhinweise Das vernetzte System muss von qualifizierten Fachleuten gemäß den detaillierten Anweisungen des Geräteherstellers beurteilt werden. Um einen nicht ordnungsgemäßen Betrieb nach offensichtlich korrekt simulierten Prüfoperationen zu vermeiden, muss die Polarität der Neutralwandlerkontakte (falls verwendet) mit den detaillierten Anweisungen des Geräteherstellers übereinstimmen. Wenden Sie sich bei Fragen an den zuständigen Ingenieur und/oder den Gerätehersteller. Prüfen Sie die Erdungspunkte des Systems mithilfe von Hochspannungsprüfern und Widerstandsbrücken, um sicherzustellen, dass keine an den Wandlern vorbeiführenden Erdleitungen existieren. N

L C R 15

16

Instruction Leaflet IL01301032E gültig ab Januar 2011

Verwenden Sie eine Niederspannungs- (0 bis 24 V), Hochstrom-ACQuelle, um einen Prüfstrom von 125 Prozent des Ansprechwertes des Erdschlussauslösers an eine Phase des Leistungsschalters anzulegen (siehe Abbildung 4 und 7). Dies sollte zu einer Auslösung des Schalters innerhalb einer Sekunde führen und die Alarmanzeige (falls vorhanden) aktivieren. Setzen Sie Schalter und Alarmanzeige in den Ausgangszustand zurück. Wiederholen Sie diese Prüfung für die anderen beiden Phasen. Um ein 4-Poliges System mit einem Neutralwandler zu prüfen, legen Sie denselben Strom (s.o.) an eine Phase des Schalters mit Rückführung durch den Neutralwandler an (siehe Abbildung 5 und 8). Der Schalter sollte nicht ausgelöst werden und die Alarmanzeige (falls vorhanden) sollte nicht in Betrieb sein. Um ein 3-Poliges System ohne Neutralwandler zu prüfen, legen Sie denselben Strom (s.o.) an zwei beliebige Phasen des Schalters an (siehe Abbildung 6 und 9). Der Schalter sollte nicht ausgelöst werden und die Alarmanzeige (falls vorhanden) sollte nicht in Betrieb sein. Wiederholen Sie diese Prüfung für die anderen beiden möglichen Phasenkombinationen

X

Halten Sie die Prüfergebnisse auf den Prüfformular fest.

• Warnung

X

BEI DER ARBEIT AN STROMVERSORGUNGSSYSTEMEN BESTEHT IMMER DIE GEFAHR EINES ELEKTRISCHEN SCHLAGS ODER EINES ELEKTROBRANDS. SCHALTEN SIE VOR DURCHFÜHRUNG DER Prüfungen IMMER DEN SCHALTER FÜR DIE STROMVERSORGUNG AB. Entfernen SIe den Schalter wenn möglich immer aus der Kassette.

Neutralwandler

• Warnung Abbildung 2. Neutralwandler Anwendung (NEMA) N

L C R 16

X

15

Funktionsprüfungen sollten nur zur Sicherstellung der Funktionalität des Leistungsschalters vorgenommen werden, Nicht zur Kalibrierung des Schalters. Stellen Sie nach der Funktionsrpüfung alle EInstellungen des Leistungsschalters in ihren Ausgangszustand zurück und entfernen Sie alle für die Prüfung vorgenommenen Verbindungen zu den Prüfgeräten bevor der Schalter wieder in Betrieb genommen wird.

X

Neutralwandler

Abbildung 3. Neutralwandler Anwendung (IEC) AAnmerkung: Da Leistungsschalter mit Erdschlussschutz ihren Betriebsstrom aus den Stromwandlern und nicht aus dem Neutralwandler beziehen, reicht es bei einer Funktionsprüfung nicht aus nur Strom durch den Neutralwandler zu leiten, um den Erdschlussschutz zu prüfen.

eaton corporation www.eaton.com

3

Instruction Leaflet IL01301032E

Montageanweisung für Series NRX  Neutralwandler - Baugröße NF 

gültig ab Januar 2011

NiederspannungsQuelle

NiederspannungsQuelle

StrombegrenzungsWiderstand (falls nötig)

Abbildung 4. Verbindungen für Erdschlussauslöseprüfungen (NEMA)

NiederspannungsQuelle

StrombegrenzungsWiderstand (falls nötig)

Abbildung 5. Verbindungen für Erdschlussprüfung ohne Auslösung bei 4-poligen System (NEMA)

NiederspannungsQuelle

StrombegrenzungsWiderstand (falls nötig)

Abbildung 7. Verbindungen für Erdschlussauslöseprüfungen (IEC)

4

StrombegrenzungsWiderstand (falls nötig)

Abbildung 8. Verbindungen für Erdschlussprüfung ohne Auslösung bei 4-poligen System (IEC)

eaton corporation www.eaton.com

NiederspannungsQuelle

StrombegrenzungsWiderstand (falls nötig)

Abbildung 6. Verbindungen für Erdschlussprüfung ohne Auslösung bei 3-poligen System (NEMA) NiederspannungsQuelle

StrombegrenzungsWiderstand (falls nötig)

Abbildung 9. Verbindungen für Erdschlussprüfung ohne Auslösung bei 3-poligen System (IEC)

Montageanweisung für Series NRX  Neutralwandler - Baugröße NF 

Instruction Leaflet IL01301032E gültig ab Januar 2011

eaton corporation www.eaton.com

5

Instruction Leaflet IL01301032E gültig ab Januar 2011

Montageanweisung für Series NRX  Neutralwandler - Baugröße NF 

Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN-CARE (877-386-2273) Eaton.com © 2011 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL01301032EH02 Januar 2011

6

eaton corporation www.eaton.com

Power Chain Management is a registered Trademark of Eaton Corporation All other Trademarks are property of their respective owners.

Suggest Documents