The OPAL plastic pipe collar is a powder coated mild steel or stainless steel casing containing OPAL graphite intumescent layers for Polypropylene, P...
Author: Roderick Weaver
3 downloads 0 Views 8MB Size
The OPAL plastic pipe collar is a powder coated mild steel or stainless steel casing containing OPAL graphite intumescent layers for Polypropylene, Polyethylene and ABS plastic pipes. OPAL intumescent is also suitable for uPVC pressure and non-pressure pipes. These layers expand at approximately 150oC to crush the softening plastic pipe and thereby close the penetrations through fire rated walls and floors.

and floors, OPAL fire collars have been tested at Warrington Fire Research Centre and Building Research Establishment Ltd. (BRE) to BS476 Part 20 1987 and Station d’essais CTICM 98-E-275 for wall collars and 98-H-276 for floor collars. OPAL fire collars meet both integrity and insulation requirements to this standard for both two and four hours, when surface mounted and cast in a concrete floor or in a masonry or blockwork wall.

The OPAL fire collars can be surface mounted and they can be cast in when fixing space is not available. Fixing is with non-combustible metal screws, anchor or cavity fixings.

Surface mounted to wall

The OPAL fire collar is fully tested for uPVC, Polypropylene, Polyethylene and ABS plastic pipes for both wall and floor penetrations.

Surface mounted to floor

The OPAL fire collar can be used through plasterboard, concrete, blockwork and brickwork constructions. The OPAL fire collar has achieved performance from 2 to 4 hours in tests to relevant British standards at approved laboratories. OPAL fire collars are available in all pipe sizes up to 315mm dia. (Remark: Size not mention may be Specially offered by the Manufacturer.)

BUILDING REGULATIONS To satisfy building regulation requirements on all penetrating fire rated compartment walls

Installation OPAL fire collars must be fitted on each side of a wall where both sides are at risk from fire. Penetrations through floors require an OPAL fire collar fitted to the underside only of each penetration. Non-flammable screws, anchor or cavity fixings must be used to secure OPAL fire collars to walls and floors.

Full Cast In Type

Surface Mounted Type

Surface Mounted Type

Surface Mounted Type

Availability of Fire Collars Nominal Dia. 15 mm 20 mm 25 mm 30 mm 32 mm 40 mm 50 mm 55 mm 63 mm 65 mm 75 mm 80 mm 82 mm 90 mm 100 mm 110 mm 125 mm 140 mm 150 mm 160 mm 175 mm 200 mm 225 mm 300 mm

BS 5255 2 hr 4 hr

* * *

uPVC BS 4514 2 hr 4 hr

* * *

*

*

*

*

*

*

Polyprop Polyeth BS 3505 (JIS K6741/2)

2 hr * * *

4 hr * * *

* * *

* * *

*

*

*

*

*

*

*

*

* * * * * *

* * * * * *

ABS Surface

Cast In

*

*

*

*

*

*

*

* *

* *

* *

* *

* *

*

*

*

*

*

* *

* *

* *

* *

* *

* * *

* * *

* * *

* * *

* * *

*

*

*

*

*

2 hr

2 hr

2 hr

*

*

*

2 Hours Fire Collars Height

Fixing Lug

Details for fixing uPVC Pipes to BS5255/BS4514 Nominal Diameter of Pipe

Actual Outside Diameter of Pipe

32 40 *50 *80 *100 *150

36.5 43 56 83 110 160

Minimum Total Number of Thickness of Intumescent Intumescent Layer (2 Hours) 2 4 2 4 3 6 5 10 5 10 8 16

Collar Height (2 Hours)

Total Available Recommended Number of Min. No. Min. Sizing of Fixing Lugs of Fixing Mild Steel Anchor Lugs for Mounting

60 60 45 45 45 45

2 2 3 3 4 6

2 2 2 2 2 4

M3 x 25mm M3 x 25mm M5 x 25mm M5 x 25mm M5 x 25mm M5 x 25mm

Remark: All Dimension in (mm) * 60mm Collar Height is available upon request.

Details for fixing uPVC Pipes to BS3505 Nominal Diameter of Pipe

Actual Outside Diameter of Pipe

20 25 32 40 50 65 80 100 150

26.8 33.6 42.3 48.3 60.3 75.3 88.9 114.3 160.25

Remark:

Minimum Total Number of Thickness of Intumescent Intumescent Layer (2 Hours) 2 4 2 4 3 6 3 6 3 6 4 8 4 8 4 8 6 15

All Dimension in (mm)

Collar Height (2 Hours)

60 60 60 60 60 60 60 60 60

Total Available Recommended Number of Min. No. Min. Sizing of Fixing Lugs of Fixing Mild Steel Anchor Lugs for Mounting 2 2 2 2 3 3 3 4 6

2 2 2 2 2 2 2 2 4

M3 x 25mm M3 x 25mm M3 x 25mm M3 x 25mm M5 x 25mm M5 x 25mm M5 x 25mm M5 x 25mm M5 x 25mm

2 Hours Opal Stainless Steel Fire Collars Height

Fixing Lug

Details for fixing uPVC Pipes to BS5255/BS4514 Nominal Diameter of Pipe

32 40 *50 *80 *100 *150

Actual Minimum Total Outside Number of Thickness of Diameter Intumescent Intumescent of Pipe Layer (2 Hours) 36.5 2 4 43 2 4 56 3 6 83 5 10 110 5 10 160 8 16

Collar Height (2 Hours)

Total Number of Fixing Lugs

Available Min. No. of Fixing Lugs

Recommended Min. Sizing of Mild Steel Anchor for Mounting

60 60 45 45 45 45

2 2 3 3 4 6

2 2 2 2 2 4

M3 x 25mm M3 x 25mm M5 x 25mm M5 x 25mm M5 x 25mm M5 x 25mm

Collar Height (2 Hours)

Total Number of Fixing Lugs

Available Min. No. of Fixing Lugs

Recommended Min. Sizing of Mild Steel Anchor for Mounting

60 60 60 60 60 60 60 60 60

2 2 2 2 3 3 3 4 6

2 2 2 2 2 2 2 2 4

M3 x 25mm M3 x 25mm M3 x 25mm M3 x 25mm M5 x 25mm M5 x 25mm M5 x 25mm M5 x 25mm M5 x 25mm

Remark: All Dimension in (mm) * 60mm Collar Height is available upon request.

Details for fixing uPVC Pipes to BS3505 Nominal Diameter of Pipe

20 25 32 40 50 65 80 100 150 Remark:

Actual Minimum Total Outside Number of Thickness of Diameter Intumescent Intumescent of Pipe Layer (2 Hours) 26.8 2 4 33.6 2 4 42.3 3 6 48.3 3 6 60.3 3 6 75.3 4 8 88.9 4 8 114.3 4 8 160.25 6 15 All Dimension in (mm)

2 Hours Pipe Wraps Intumescent

Height

Length

Details for fixing uPVC Pipes to BS5255/BS4514 Nominal Diameter of Pipe 32 40 50 80 100 150

Actual Outside Diameter of Pipe 36.5 43 56 83 110 160

Number of Total Height of Minimum Intumescent Thickness of Intumescent Length of Layer Intumescent (2 Hours) Intumescent (2 Hours) 3 6 60 122 3 6 60 142 3 6 60 184 4 8 60 268 4 8 60 354 6 12 60 520

Remark: All Dimension in (mm)

Details for fixing uPVC Pipes to BS3505 Nominal Diameter of Pipe 20 25 32 40 50 65 80 100 150

Actual Outside Diameter of Pipe 26.8 33.6 42.3 48.3 60.3 75.3 88.9 114.3 160.25

Number of Total Height of Minimum Intumescent Thickness of Intumescent Length of Layer Intumescent (2 Hours) Intumescent (2 Hours) 2 4 60 90 2 4 60 112 3 6 60 140 3 6 60 160 3 6 60 194 4 8 60 246 4 8 60 288 4 8 60 372 6 12 60 520

Remark: All Dimension in (mm) Note:

The plastic bag with self adhesive tape is our original design for ease of installation. It can be removed away subject to project requirement. But our above required number of intumescent layers must be strictly followed and used to ensure the fire resistance performance.

INTUMESCENT TECHNICAL DATA COLOUR

ANTHRACITE GREY

CONSISTANCY

SOLID, FLEXIBLE

DENSITY

1 +/- 0.2 g/cm3

WEIGHT

2.5 mm THICKNESS: 2.5 +/- 0.3kg/M

FIRE PERFORMANCE

CLASSIFICATION B1 (DIN 4102)

EXPANSION TEMPERATURE

START AT APPROX. 150 C

EXPANSION RATE

MINIMUM 7:1 (15 min./300 C)

EXPANSION PRESSURE

MINIMUM 0.6N/mm

THORN FLEXIBILITY

MINI. 7:1 (15 min./300 C)

RESISTANCE TO UV RADIATION

EXCELLENT

HEAT CONDUCTIVITY

1.2 W/mK (UNEXPANDED)

HUMIDITY CHARACTERISTICS

INSOLUBLE IN WATER

2

O

O

2 O

彬記(國際)有限公司 BUN KEE (INTERNATIONAL) LIMITED OFF. ADD. :12/F., PHASE 1, AUSTIN TOWER, 22-26 AUSTIN AVENUE,TSIM SHA TSUI, KOWLOON, HONG KONG. TEL. : (852) 2728 7237 (16 LINES) FAX: (852) 2387 2999 SHOP : 1) G/F., 618 SHANGHAI STREET, KOWLOON. 2) G/F., 30 HOP YICK ROAD, YUEN LONG. 3) SHOP A, G/F., 7-11 TAI WONG ST., EAST, WAN CHAI. GODOWN : LOT 3719 IN DD 104, YUEN LONG, N.T. E-MAIL : [email protected]

Installation Manual For OPAL Fire Collars

METAL PIPE SLEEVE

AL SE

AN

T

STEP 1. BACK FILL THE GAP WITH MASTIC / MORTAR OR MINERAL WOOL BETWEEN uPVC PIPE AND METAL PIPE SLEEVE. ADD SEALANT / JOINT FILLER FOR FINISHING

STEP 2. STICK THE FIRE COLLAR TO THE CEILING OR WALL AND TEMPORARY LOCK IT ON THE PIPE

STEP 3. MARK AND DRILL THE HOLES ON CEILING OR WALL MATCHING WITH FIXING LUGS ACCORDINGLY

STEP 4. LOCK THE FIRE COLLAR AND FASTEN

Installation Manual For OPAL Pipe Wraps

METAL PIPE SLEEVE

STEP 1. CLEAN UP THE UPVC PIPE AND STICK THE PIPE WRAP AROUND THE PIPE

STEP 2. GLIDE THE PIPE WRAP INTO THE OPENING OF CEILING / FLOOR SLAB OR WALL

SE

STEP 3. BACK FILL THE OPENING WITH THE MASTIC / MORTAR OR MINERAL WOOL POINTING SURROUND THE UPVC PIPE

AL A

NT

STEP 4. CLEAN UP THE UPVC PIPE AND ADD SEALANT / JOINT FILLER FOR FINISHING