INSTALLATION AND USER GUIDE

Contents 04 Introduction 05 Technical Specifications 06 System Elements 07 Device Settlement and Installation Guidelines 08 General Recommendations 10 Before Activating 10 Activating 11 KBS - Single Serpentine Water Heater Flow Diagram 12 KBD - Double Serpentine Water Heater Flow Diagram 13 KXS - KXD - Maxi Water Heater Flow Diagram 14 KCB - Combi Water Heater Flow Diagram 15 KEB - Electric Water Heater Flow Diagram 16 KAT - Hot Water Storage Tank Flow Diagram 17 KSS - Single Serpentine Horizontal Water Heater Flow Diagram 17 KSC - Closed Loop Double Wall Water Heater Flow Diagram 18 KSO - Open Loop Horizontal Water Heater Flow Diagram 19 KCS - Single Copper Coil Water Heater Flow Diagram 20 Periodic Maintenance and Cleaning 21 Check List Before Calling Authorized Services 22 Potable and Domestic Water Standards

3

Introduction

• In order to guarantee a safe and efficient usage of your device, we recommend that you follow the instructions provided in this guide. • Your device installation, usage and maintenance should be performed as described in this guide otherwise it will not be covered by the guarantee. • For more detailed information about your device, you can contact KODSAN Co. • Please keep this manual for future reference • To continuously improve the quality of our products and provide better service to our users, the features mentioned in this document may be upgraded without prior notice.

Note: The safety valve that will be used on the product varies according to the system pressure. (Max. 9 bar - Min. 6 bar)

4

Technical Specifications

• Our water heaters are manufactured in accordance with EN 12897 and TS 736 standard. • The inner surface of the water heater is enameled in accordance with DIN 4753 standards. Protection against corrosion is provided by a magnesium anode located in the device. • In order to control the water temperature inside the device, there is a thermostat sensor that can be connected through the thermowell. • Our water heaters have connection sleeves for electric heaters and thermostat. Both elements are removable.

5

System Elements

Safety Valve : In case of high pressure in the boiler it discharges the water. Expansion Tank : It adjusts pressure fluctuations that can occur within the system. Check Valve : It allows fluid moving within the system in the desired direction and blocks the fluid flow to the opposite direction. Filter : It is used to remove impurities from the water circulating in the system. Valve : It is used as an installation element that allows or stops the flow of water into system. Pump : It enables the circulation of fluid used in the system. Manometer : It is used to measure the pressure inside the system. Thermometer : It is used to measure the temperature of the liquid in the system. Pressure Reducer : In case the water pressure in the system exceeds the optimal allowable pressure of the device a pressure reducer must be installed on the connection line to automatically discharge water in the system until pressure is normalized.

6

Device Settlement and Installation Guide

• Products will be delivered with wooden pallet. Before the installation the wooden should be removed. • The installation should be performed according to the Flow Diagrams in this document. • The device should be placed on a suitable base with smooth and strong surfaces to support the weight of the boiler. • The user should choose the area of installation according to maintenance requirements. • The device should be placed indoors or in an area where there is no danger of freezing. • In order to make the device work effectively, the system to which the water heater is connected should be according to schemes. Heating resources should be chosen according to hot water supply needs. • If the installation guidelines are not followed or if damages occur during the installation process the product will be out of warranty. • If the automatic safety valve is not assembled or if it is is incorrectly installed then the product will be out of warranty. • The place of installation should be protected against fires and floods. The warranty does not cover any product failure caused by external system elements.

7

General Recommendations

8

1. SCENARIO

2. SCENARIO Shower

3. SCENARIO Shower

9 Shower

THE MOST IMPORTANT POINT WHEN INSTALLING A WATER HEATER IS NOT TO FORGET TO INSTALL THE SAFETY VALVE Water expands when heated. The expansion rate with temperature is illustrated at the table and plot below. For example, water expands 1.19% at 50 oC. This extra volume of water should be removed from the water heater. Water is an incompressible liquid. If the expanded water is not removed from the water heater then there will increased pressure on the product body which can cause damages on the weakest point of the water heater. d (kg/lt) 0.9998 0.9996 0.9982 0.9956 0.9922 0.9880 0.9832 0.9777 0.9718 0.9635 0.9583 0.9519 0.9431

V (kg/lt) 1.0002 1.0004 1.0018 1.0044 1.0079 1.021 1.071 1.0228 1.0290 1.0359 1.0435 1.0515 1.0603

%

e

0 0.02 0.16 0.42 0.77 1.19 1.67 2.26 2.88 3.57 4.33 5.13 6.01

0.0002 0.0004 0.0018 0.0044 0.079 0.0121 0.0171 0.0228 0.0290 0.0390 0.0435 0.0515 0.0608

Heat source started working and the flowing hot water inside the serpentine starts heating the domestic water.

If the safety valve was not installed there would be damages to the water heater.

Water Expansion rate with Temperature Expansion %

T (oC) 0 10 20 30 40 50 60 70 80 90 100 110 120

Both the water from the heat source and the domestic water are cold.

10.00 5.00 4.00 3.00

The heated and expanded domestic water cannot exit the water heater because the shower is closed and the check valve is stopping reverse flowing. The water is released at the safety valve.

2.00 1.00

Expansion Tank Application The expansion tank used in the system should have at least 10% of the volume of the water heater, capable of work under 10 bar pressure and initial pressure should be set to 10 bar. The most important feature in the system is to use safety valve and expansion tank. Always install the expansion tank and the safety valve between the water heater and the valve.

0.50 0.40 0.30 0.20 0.15 0.10 0

20

40

60

80

100

120

140 °C Water Temperature

Before Activating

• The domestic hot water circulating in the system should be according to the quality standards defined in the last page of this document. The warranty does not cover the cases where the domestic hot water does not meet these standards. • Verify the mechanical and electrical connections of the product. • Check for leakages in all connections and pipes. • The electric resistances should be grounded. When you are working on the connections of the system please turn off electricity. Activating • Please do not start to operate your water heater before you make sure that it is filled with water and that the cold water inlet is available. • After completely filling the water heater, in order to release remaining air in the product please open the hot water tap. • Electric connections of the device must be done by a qualified electrician. • Check the cable section, voltage and grounding line and then set the safety thermostat in the control panel. • Do not turn on the electric resistance before completely filling the water heaters.

10

KBS - Single Serpentine Water Heater Flow Diagram

CIRCULATION PUMP

STRAINER

ON/OFF VALVE

SAFETY VALVE

CHECK VALVE MANOMETER

11

HOT WATER OUTLET

CLOSED EXPANSION TANK BOILER INLET

The flow diagram is for information purposes. It can be changed according the application.

CIRCULATION BOILER OUTLET

COLD WATER INLET

KBD - Double Serpentine Water Heater Flow Diagram

CIRCULATION PUMP ON/OFF VALVE CHECK VALVE MANOMETER

STRAINER

HOT WATER OUTLET BOILER INLET

SAFETY VALVE CLOSED EXPANSION TANK

12

KXS - KXD - Maxi Water Heater Flow Diagram

CIRCULATION PUMP

STRAINER

ON/OFF VALVE

SAFETY VALVE

CHECK VALVE

HOT WATER CIRCULATION

MANOMETER

13

SICAK SU ÇIKIŞ

CLOSED EXPANSION TANK KAZAN GİRİŞ

BOILER OUTLET

The flow diagram is for information purposes. It can be changed according the application.

The flow diagram is for information purposes. It can be changed according the application.

SOLAR COLECTOR INLET

SİRKÜLASYON SOLAR COLECTOR OUTLET

KAZAN DÖNÜŞ

COLD WATER INLET

SOĞUK SU GİRİŞ

KCB - Combi Water Heater Flow Diagram

14

KEB - Electric Water Heater Flow Diagram

15

HOT WATER OUTLET

CIRCULATION PUMP

STRAINER

ON/OFF VALVE

SAFETY VALVE

CHECK VALVE MANOMETER

COLD WATER INLET

RADIATOR OUTLET

STRAINER

ON/OFF VALVE

SAFETY VALVE

CHECK VALVE

CLOSED EXPANSION TANK

The flow diagram is for information purposes. It can be changed according the application.

CIRCULATION PUMP

MANOMETER

RADIATOR RETURN

BOILER INLET

BOILER OUTLET

SOLAR COLECTOR INLET

SOLAR COLECTOR OUTLET

Before activating Combi Water Heaters, first the inner tank should be filled and pressurized then the outter tank should be filled. When the water is going to be flushed please do it first from the outter tank and secondly from the inner tank.

HOT WATER OUTLET

CLOSED EXPANSION TANK

The flow diagram is for information purposes. It can be changed according the application.

CIRCULATION

COLD WATER INLET

KAT - Hot Water Storage Tank Flow Diagram

CIRCULATION PUMP

STRAINER

ON/OFF VALVE

SAFETY VALVE

CHECK VALVE MANOMETER

16

HOT WATER OUTLET

KSS - Single Serpentine Horizontal Water Heater Flow Diagram KSC - Closed Loop Double Wall Water Heater Flow Diagram ON/OFF VALVE

SAFETY VALVE

CHECK VALVE

CLOSED EXPANSION TANK

AIR RELEASE VALVE

HOSE

HOT WATER OUTLET

HOT WATER OUTLET

PRESSURE RELEASE VALVE

CLOSED EXPANSION TANK

17

PLATE HEAT EXCHANGER

COLD WATER INLET

COLD WATER INLET

BOILER INLET

BOILER OUTLET

HOT WATER CIRCULATION

The flow diagram is for information purposes. It can be changed according the application.

The flow diagram is for information purposes. It can be changed according the application. COLD WATER INLET

KSS

KSC

KSO - Open Loop Horizontal Water Heater Flow Diagram

18

COLD WATER OUTLET

KCS - Single Copper Coil Water Heater Flow Diagram

CIRCULATION PUMP

STRAINER

CIRCULATION PUMP

STRAINER

ON/OFF VALVE

SAFETY VALVE

ON/OFF VALVE

SAFETY VALVE

MANOMETER

CHECK VALVE

CLOSED EXPANSION TANK

The flow diagram is for information purposes. It can be changed according the application.

MANOMETER

COLD WATER INLET

CHECK VALVE

19

HOT WATER OUTLET

CLOSED EXPANSION TANK

The flow diagram is for information purposes. It can be changed according the application.

CIRCULATION

BOILER INLET BOILER OUTLET

COLD WATER INLET

Periodic Maintenance and Cleaning

• It is suggested to clean inside the water heater through the cleaning flange in order to remove dirt particles that may exist in the water system. • If the product is with electrical instruments please disable the electrical connections. • The gaskets used on the products are only suitable for one usage. In case they are removed for any reason they should be replaced and you should contact the seller. • Please be sure that the elements like valve, check valve, strainer, security valve, expansion tank and thermometer are in good condition. • Please remove and clean the filter of the strainer periodically • The magnesium anode rod should be checked every year. The substitution frequency can be determined after the first control. The quality of the water is important for the life of the anode. • If the magnesium anode rod diameter is less than 12mm it should be changed. (Original diameter is 26mm) • The magnesium anode rod is out of the warranty. • When the water heater is deactivated please be sure that the tank is empty to prevent possible freezing problems. • When cleaning the interior of the product please be sure that you do not damage the enamel inside. • After cleaning the interior of the product please be sure that cleaning flange, thermowell (sensor) and thermostat are safe and there is no leakage.

20

Checklist Before Calling Authorized Service

A. If the electrical heater (optional) is not working; • Electricity might be off, • The switch might be off, • The building’s main fuse might be off. B. If hot water is not coming from the tap; • Water Works might be off, • The hot-cold water valve might be closed. • The strainer might be full and out of order. C. If water is coming from the tap but it is not hot; • Heating system or solar collector might be out of order, • Even if the heating system is working the circulation pump might be off. D. If there is not enough hot water coming from the water heater; • The product capacity might not be adequate, • The hot water might return to the system if a check valve is not being used, • There might be a problem with automation system. E. If the safety valve on water heater is leaking; • The water work’s pressure might be 7 bars or more, • There might be dirt in the safety valve gasket.

21

Potable and Domestic Water Standards

STANDARDS Microbiology Coliform Escherichia Coli(E.Coli) C.perfringens Enterococcus Parameter mg/L pH(pH) Colour(Co-Pt unit) Odor(NTU unit) Conductivity 20 (uS/cm) Odor Iron(Fe) Manganese(Mn) Aluminium(Al) Amonium(NH4) Sodium(Na) Chlorine(Cl) Sulfate(SO4) Hardness (CaA03)

22

TSE 266 Turkish Standard Institute

EC European Comunity

WHO World Health Organization

0

0

0

0

0

0

0 0

0 0

0 0

6,5-9,5

6,5-9,5

6,5-8,5

20

20

15

5,0

4,0

5,0

2500

2500

2500

0,2 0,05 0,20 0,5 200 250 250

Without smell 0,2 0,05 0,20 0,5 200 250 250

0,3 0,10 0,20 1,5 200 250 250 500

STANDARDS Chemical mg/L Nitrate(NO3) Nitrite(NO2) Borium(B) Nickel(Ni) Arsenic(As) Cadmium(Cd) Chromium(Cr) Fluorine(F) Lead(Pb) Cyanide(CN) Bromium(Br) Benzene(C6H6) Selenium(Se) Antimony(Sb) Copper(Cu)

TSE 266 Turkish Standard Institute

EC European Comunity

WHO World Health Organization

50 0,5 1 0,02 0,01 0,005 0,05 1,5 0,01 0,05 0,01 0,001 0,01 0,005 2,0

50 0,5 2 0,02 0,01 0,005 0,05 1,5 0,01 0,05 0,01 0,001 0,01 0,005 2,0

50 0,5 2 0,02 0,01 0,003 0,05 1,5 0,01 0,05 0,025 0,01 0,01 0,005 2,0