ADCP-61-498 Issue 2, April 1997

HDSL Remote Network Interface Installation and Operation Manual Content

Page

INTRODUCTION ........................................................................... 1 Revision History ....................................................................... 2 List of Changes ....................................................................... 2 Trademark Information .................................................................. 2 Related Publications ................................................................... 2 Admonishments ....................................................................... 2 Safety Information ..................................................................... 3 FCC Compliance Statement .............................................................. 3 Certification: UL Listed.................................................................. 3 1. INSTALL HDSL NID..................................................................... 4 A. B.

Unpack HDSL NID Unit ............................................................... 4 Mounting a HDSL NID Enclosure ...................................................... 4 Surface Mounting ................................................................... 4 Conduit Mounting .................................................................. 6

C. D.

Install New Cover with HDSL Module .................................................... 6 Telephone Company Wiring........................................................... 8 Earth Ground Wiring ............................................................... 10

E.

Subscriber/Customer Wiring ......................................................... 11 DS1 Wiring ....................................................................... 13 POTS Wiring...................................................................... 13

2. OPERATION ......................................................................... 15 A.

Front Panel Indicators and Controls ................................................... 15

B.

Network Loopback Functions ........................................................ 17

C.

Customer Loopback Functions ....................................................... 19

D.

Loopback Functions with the HDSL Repeater Unit ........................................ 19

3. SYSTEM INTEGRATION SERVICES ....................................................... 20 4. CUSTOMER SUPPORT SERVICES ........................................................ 20

INTRODUCTION The ADC Soneplex® HDSL Remote Network Interface Enclosure is an outdoor demarcation point between telephone company equipment/wiring and subscriber or customer equipment/ wiring. The enclosure is designed to support delivery of two POTS lines and one DS1 signal to the subscriber. The enclosure contains a test point that is used to determine if faults are in the subscriber or telephone wiring. The enclosure also contains protectors and the HDSL remote module. HDSL service may either be added to an existing SIECOR® CAC® 7600 Network Interface Demarcation (NID) or installed as a complete preassembled unit.

2-70000-1544

Page 1 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

Revision History ISSUE

DATE

REASON FOR CHANGE

1

3/96

Original

2

4/97

Add new label, cable tie down, and update format.

List of Changes PAGE

IDENTIFIER

All

DESCRIPTION OF CHANGE Format changes

Trademark Information Soneplex is a registered trademark of ADC Telecommunications, Inc. T-TERM is a registered trademark of ADC Telecommunications, Inc. SIECOR and CAC are registered trademarks of Siecor Corporation

Related Publications This manual is one of several manuals for the Soneplex System. Listed below are all of the related manuals and their publication numbers. Copies of these publications can be ordered by contacting the ADC Technical Assistance Center at 1-800-366-3891 (in U.S.A. or Canada) or 612-946-3000, extension 3223 (outside U.S.A. and Canada). Title

ADCP Number

T-Term Version B HLX220 HDSL Module User Manual B1 HLX 319 HDSL Operation and Maintenance Manual HDSL Repeater (HRX) Installation Instructions Soneplex Broadband System Operation and Maintenance Manual (Version 5) Soneplex Broadband System Operation and Maintenance Manual (Version 5) HLX Plus HDSL Operation and Maintenance Manual Soneplex Broadband System Operation and Maintenance Manual (Version 6)

ADCP-61-062 ADCP-61-063 ADCP-61-315 ADCP-61-467 ADCP-61-471 ADCP-61-480 ADCP-61-494

Admonishments Important safety admonishments are used throughout this manual to warn of possible hazards to persons or equipment. An admonishment identifies a possible hazard and then explains what may happen if the hazard is not avoided. The admonishments — in the form of Dangers, Warnings, and Cautions — must be followed at all times. These warnings are flagged by use of the triangular alert icon (seen below), and are listed in descending order of severity of injury or damage and likelihood of occurrence. Danger: Danger is used to indicate the presence of a hazard that will cause severe personal injury, death, or substantial property damage if the hazard is not avoided.

Page 2 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

Warning: Warning is used to indicate the presence of a hazard that can cause severe personal injury, death, or substantial property damage if the hazard is not avoided. Caution: Caution is used to indicate the presence of a hazard that will or can cause minor personal injury or property damage if the hazard is not avoided. Safety Information Danger: To avoid electric shock, be careful when working near HDSL Loop connections or Telecommunication circuits. A electrical potential of ± 130 volts (relative to Earth ground) exists on the HDSL Loop connections or Telecommunication circuits. Coming in contact with this high electrical potential will result in death or severe personal injury. To avoid electric shock be certain the HDSL loop is not powered at the CO. Warning: To prevent electrical shock, never install telephone equipment in a wet location or during a lightning storm. When installing or modifying telephone lines, disconnect lines on the network side before working with uninsulated lines or terminals. Caution: Electronic modules can be damaged by static electrical discharge. Before handling electronic modules, wear an anti-static discharge wrist strap to prevent damage to electronic components. Place electronic modules in anti-static packing material when transporting or storing. When working on electronic modules, always place them on an approved anti-static mat that is electrically grounded. FCC Compliance Statement Class B The HDSL NID complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions; (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Warning: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with limits for a Class B digital device pursuant to Subpart B of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a residential environment. If interference to TV and radio reception does occur relocate or reorient the antenna of the affected radio or TV. This equipment does not exceed Class B limits for radio emission for digital apparatus, set out in the radio interference regulation of the authorization methods of Industry Canada. Certification: UL Listed The HDSL NID has been tested and found to comply with the requirements of UL 1459.

Page 3 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

1. INSTALL HDSL NID Caution: Electronic modules can be damaged by static electrical discharge. Before handling electronic modules, wear an anti-static discharge wrist strap to prevent damage to electronic components. Place electronic modules in anti-static packing material when transporting or storing. When working on electronic modules, always place them on an approved anti-static mat that is electrically grounded.

A. Unpack HDSL NID Unit At the Central Office (CO) verify that the CO equipment is not connected to the HDSL 1.01 NID unit (telephone company wiring). Danger: To avoid electric shock, be careful when working near HDSL Loop connections or Telecommunication circuits. A electrical potential of ± 130 volts (relative to Earth ground) exists on the HDSL Loop connections or Telecommunication circuits. Coming in contact with this high electrical potential will result in death or severe personal injury. To avoid electric shock be certain the HDSL loop is not powered at the CO. Open the shipping carton and carefully unpack the equipment from the protective 1.02 packing material. Check each component for broken or missing parts. If there are any damages, file a claim with the commercial carrier. Warning: To prevent electrical shock, never install telephone equipment in a wet location or during a lightning storm. When installing or modifying telephone lines, disconnect lines on the network side before working with uninsulated lines or terminals. 1.03

Are you installing a HDSL NID Enclosure? If YES, go to Step B, Mounting a HDSL NID Enclosure. If NO, and you are converting an existing CAC 7600 Enclosure to provide HDSL service go to Step C, Install New Cover with HDSL Module.

B. Mounting a HDSL NID Enclosure Choose a suitable location to mount the enclosure. Select a vertical surface near an 1.04 approved ground. The location should be away from gutter down spouts, permanent water sprinklers, or other water sources. Always allow easy access to the enclosure for testing by either the customer or telephone company. The enclosure can either be mounted directly on a flat vertical surface or secured to a vertical conduit. Surface Mounting Use a standard screwdriver to open the enclosure outside door. Open the inside protector 1.05 compartment door using a standard telephone company KS, 216B or Robertson tool.

Page 4 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

Make certain the enclosure sits flat on the mounting surface to prevent warping. Use 1.06 washers or other shims to square the enclosure on uneven surfaces. Use the knockouts provided in the back plate to secure the enclosure. There are four 1.07 knockouts located behind the top protector, four knockouts located below the bottom protector location, and one behind the bottom subscriber bridge. Use a screw driver to punch out the knockouts that you are going to use. Knockout locations and mounting ear locations are shown in Figure 1.

EXTERNAL MOUNTING EAR

8397-B

UNIVERSAL KNOCKOUT

EXTERNAL MOUNTING EAR

#6 SCREW

ENTRANCE GROMMETS

CABLE TIE MOUNT

Figure 1. Knockout Locations and Mounting Ears

Page 5 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

Conduit Mounting Enclosures can be secured to a vertical conduit with metal straps wrapped around the 1.08 mounting ears located on the top and bottom of the enclosure. Mount enclosure only in a vertical position to prevent water from entering. 1.09

Proceed to Step D.

C. Install New Cover with HDSL Module The enclosures outside door is secured with a snap lock and slotted screw. Customer 1.10 locks can be defeated using a standard telephone company KS, 216B or Robertson tool. The same tool is used to open the inside protector compartment door. 1.11

Open outside enclosure and inside protector compartment doors.

a)

Snap the old cover off the enclosure base.

b)

Snap the new cover, with the HDSL NID unit installed in it, on to the enclosure base.

c)

When adding a HDSL NID unit to an existing enclosure make certain that there are two empty adjoining protector blocks available. If there are not two adjoining spaces available, install new protector blocks and move the POTS connections and associated subscriber bridges to create two empty adjoining protector blocks.

d)

Install a new HDSL NID subscriber bridge in the proper position for the two protector blocks installed or selected in step above. Note: The top protector block installed in Step C above is used to make the DS1 connections, this is not the place to make subscriber/customer connections. The lower protector block is used to make the HDSL loop connections. Caution: Do not connect subscriber wiring to the DS1 protector block screws. All subscriber/customer connections must be made at the subscriber bridge located on the right side of the enclosure.

e)

Position tie mount in the back plate at approximately a 45° degree angle relative to the bottom of the back plate. See Figure 1. Secure tie mount to the back plate using the #6 (8-32 × ¼ inch) thread forming Philips head screw provided.

f)

Locate cable coming from the HDSL NID unit. Route cable around the inside cover and through the opening at the lower left corner of the inside cover. When cable is located properly the protective sleeve provided, is adequate to protect the cable pairs from being pinched or damaged by closing the cover. Use cable tie provided to secure cable to one side of the tie mount installed in Step f as shown in Figure 2.

g)

Observing the wire color codes make the connections to the protector blocks as shown in Figure 2. Wires should be secured under the lower nut and washer. Wire color code and signal name are listed in Table 1.

Page 6 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

Table 1. Cable Color Code and Signal COLOR

SIGNAL

White/Blue

Loop 1 TIP

Blue

Loop 1 RING

White/Orange

Loop 2 TIP

Orange

Loop 2 RING

Not used

No connection

White/Green

DS1 RCV T

Green

DS1 RCV R

White/Brown

DS1 XMT T1

Brown

DS1 XMT R1

Green (18 gauge)

Chassis Ground

PROTECTOR BLOCKS

DS1 CONNECTIONS WHITE/ BROWN

WHITE/ GREEN

TIP

TIP

RING

RING

BROWN

GREEN

XMT (OUT)

RCV (IN)

HDSL LOOP CONNECTIONS WHITE/ BLUE

WHITE/ ORANGE

TIP

TIP

RING

RING

BLUE

ORANGE

LOOP 1

LOOP 2

8398-D

Figure 2. Connect HDSL NID Unit to Protector Blocks

Page 7 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

h)

Connect HDSL NID subscriber bridge to DS1 connections/protector blocks. See Figure 3. Connect TIP XMT to T1, RING XMT to R1, TIP RCV to T, and RING RCV to R. The subscriber bridge RJ48C and screw terminals are wired in parallel. Place both wires of the same color under the upper nut and washer on the corresponding protector block screw. Connect green wire #10 to the ground stud in the enclosure base.

i)

Record all terminations at the network interface. SUBSCRIBER BRIDGES

CUSTOMER DS1 CONNECTIONS BINDING POSTS

RJ48C T1

R1

XMT (OUT)

T

R

RCV (IN))

8399-D

Figure 3. Connect Subscriber Bridge to DS1 Connections/Protector Blocks

D. Telephone Company Wiring Obtain the materials and tools listed below:

1.12 •

Wire crimping tool



Wire cutters

Page 8 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

1.13



22 AWG shielded twisted pair cable (4-wire) with drain.



No. 10 Ring Tongue Terminal(s). Remove the left-hand grommet and punch a small hole in the center of it using a pencil point. Caution: Do not use a knife to punch a hole or cut the grommet. Doing so creates too large of an opening in the grommet allowing moisture into the enclosure. Do not cut or break through the edge of the grommet, doing so may compromise grommets holding ability.

Route the HDSL and POTS twisted pair cables to the left opening on the bottom of the 1.14 enclosure. Make POTS connections following local practices. Thread telephone company wiring (HDSL) through the grommet. See Figure 4. Strip 1.15 back each cable jacket 10 to 12 inches to expose the two wire pairs, the metallic sheath, and drain wire (if present). Danger: To avoid electric shock, be careful when working near HDSL Loop connections or Telecommunication circuits. A electrical potential of ± 130 volts (relative to Earth ground) exists on the HDSL Loop connections or Telecommunication circuits. Coming in contact with this high electrical potential will result in death or severe personal injury. To avoid electric shock be certain the HDSL loop is not powered at the CO.

HDSL LOOP CONNECTIONS WHITE/ BLUE

WHITE/ ORANGE

TIP

TIP

LOOP 1

LOOP 2 RING

RING

BLUE

ORANGE

DRAIN WIRE

TELEPHONE COMPANY WIRING

8400-A

Figure 4. Telephone Company Wiring

Page 9 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

Cut off metallic sheath (if present) so that it is even with the outer jacket of the cables. 1.16 Cut drain wire (if present) so that it reaches the ground stud. The length of the drain wire should be as short as possible. Attach a No. 10 ring tongue terminal to each drain wire then attach the terminals to the ground stud. See Figure 5. Following local practice label protector block posts LOOP 1 TIP, LOOP 1 RING, 1.17 LOOP 2 TIP, and LOOP 2 RING. Secure HDSL Loop wiring using the top nut and washer on each protector block post. GROUND STUD GROUND WIRE GROUND LUG

HDSL LOOP CONNECTIONS WHITE/ BLUE

WHITE/ ORANGE

TIP

TIP

LOOP 1

LOOP 2 RING

RING

BLUE

ORANGE

DRAIN WIRE TELEPHONE COMPANY WIRING

TO EARTH GROUND

8401-B

Figure 5. Ground Stud

Earth Ground Wiring This procedure provides instructions for connecting a earth ground wire to the Enclosure. 1.18 The earth ground wire is installed between the enclosure and an earth ground source. a)

Obtain the supply materials listed below: • •

8 AWG solid copper wire (uninsulated) Wire cutters

b)

Locate ground wire with lug in the enclosure as shown in Figure 5. Secure ground wire to the ground lug by tightening the screw.

c)

Position the ground wire and lug in the lower portion of the enclosure away from the HDSL connections.

d)

Route the ground wire to an earth ground reference point.

Page 10 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

e)

At the earth ground reference point, cut the wire to the required length.

f)

Connect ground wire to earth ground reference point as specified by local practice.

E. Subscriber/Customer Wiring There is a subscriber entrance grommet located on the lower right bottom corner of the 1.19 enclosure base. See Figure 6. EXTERNAL MOUNTING EAR

8397-A

UNIVERSAL KNOCKOUT

EXTERNAL MOUNTING EAR

ENTRANCE GROMMETS

Figure 6. Subscriber Entrance Grommet Location

Remove the right-hand grommet and punch a small hole in the center of it using a pencil 1.20 point. Caution: Do not use a knife to punch a hole or cut the grommet. Doing so creates too large of an opening in the grommet allowing moisture into the enclosure. Do not cut or break through the edge of the grommet, doing so may compromise grommets holding ability.

Page 11 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

Obtain the materials and tools listed below:

1.21

1.22



Wire crimping tool



Wire cutters



22 AWG shielded twisted pair cable (4-wire) with drain.



No. 10 Ring Tongue Terminal(s). Thread subscriber wiring through the entrance grommet. See Figure 7.

RJ48C PLUG

8402-D

TO CUSTOMER EQUIPMENT

Figure 7. Subscriber Wiring with RJ48C Plug

Page 12 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

DS1 Wiring Strip back each cable jacket 10 to 12 inches to expose the two wire pairs, the metallic 1.23 sheath, and drain wire (if present). Cut off metallic sheath and drain wire (if present) so that it is even with the outer jacket of the cables. Interface point for subscriber wiring is the subscriber bridge (per ANSI T1.403). 1.24 Subscriber DS1 connections may be made to either the RJ48C jack or to the screw terminals. The subscriber bridge RJ48C jack and screw terminals are wired in parallel. If installation requires a RJ48C plug follow instructions given in the next step. If 1.25 installation does not require a RJ48C, connect subscriber wiring directly to the screw terminals on the subscriber bridge (See Figure 3). Install a RJ48C plug on to the subscriber wiring. See Figure 8 for RJ48C jack wiring 1.26 diagram and pin numbers. Plug RJ48C plug into RJ48C jack on subscriber bridge.

PIN 1

PIN 8 RJ-48

6927-A

RJ48C JACK (8) (7) (6) RJ48C JACK AND PLUG

(5)

T RECEIVE FROM CUSTOMER

(4)

R

(3) (2)

T1

(1)

R1

TRANSMIT TO CUSTOMER 8618-B

Figure 8. Wiring Diagram for RJ48C Jack

POTS Wiring 1.27

Strip subscriber inside wire insulation (POTS line wiring).

Page 13 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

Terminate subscriber POTS line(s), tip to green and ring to red, on the appropriate 1.28 subscriber bridge(s). Plug the RJ11 connector into the appropriate subscriber bridge RJ11 receptacle. Route DS1 line and POTS line(s) along the right side of the enclosure base. When 1.29 installing subscriber wiring, route wires under individual locking door support. Placing wires in this location allows installation of optional individual locking doors if required. Close inside protector compartment door and secure screw using a standard telephone 1.30 company KS, 216B or Robertson tool. If converting an existing CAC 7600 Enclosure to provide HDSL service, place high 1.31 voltage Danger label on the inside protector compartment door as shown in Figure 9.

WARNING: To avoid shock, remove the plug from test jack before wiring.

Telephone Company Access Only.

DANGER RISK OF ELECTRICAL SHOCK. VOLTAGES UP TO 260 VOLTS MAY BE PRESENT ON TELECOMMUNICATIONS CIRCUITS.

8624-A

Figure 9. Install Danger Label

Page 14 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

Use appropriate cable wire ties to secure telephone company and customer wiring to 1.32 enclosure using the slots provided. Carefully close enclosure outside door. Make certain HDSL cable is not pinched in the 1.33 door. Secure door with screw provided.

2. OPERATION Figure 10 provides a basic configuration diagram of a telco HDSL transmission facility 2.01 and a Soneplex HDSL NID unit. The HDSL unit in the Central Office receives the DS1 signal from the network equipment. The network DS1 signal is converted into two full duplex HDSL signals which are transmitted over the HDSL loops to the HDSL NID unit. The HDSL NID unit converts the HDSL signals back into a DS1 signal which is passed to the CPE per ANSI T1.403. The Soneplex HDSL NID unit also receives the DS1 signal coming from the CPE. The 2.02 DS1 signal from the CPE is converted into two full duplex HDSL signals which are transmitted over the HDSL loops to the HDSL unit in the telco facility. The telco facility HDSL unit converts the HDSL signals back into a DS1 signal which is passed to the network equipment per TR-TSY-000499.

TELCO FACILITY

CARRIER SERVING AREA

UP TO 12 KFT FOR 24 AWG CABLE UP TO 9 KFT FOR 26 AWG CABLE

HLX PLUS, HLX 220, HLX 319, OR HLXC

HDSL LOOPS

NETWORK INTERFACE

CUSTOMER PREMISES

SONEPLEX REMOTE HDSL SYSTEM

HDSL NID

DS1 SIGNAL

CPE

DS1 SIGNAL

HDSL SIGNALS

8619-A

Figure 10. HDSL Transmission System

The HDSL NID unit provides two DS1 loopbacks: one toward the network and one 2.03 toward the CPE. These loopbacks are facilitated in the DS1 line interface of the HDSL NID unit. The only source for HDSL NID unit provisioning is the HLXC. All provisioning values 2.04 which can be altered by the Craft Interface remain in the state that was last set at the HLXC. A. Front Panel Indicators and Controls The primary function of the indicators provided on the HDSL NID unit front panel are 2.05 described in Table 2. Refer to Figure 11 for the location of each indicator described.

Page 15 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

When the HDSL NID unit is in a circuit with an HRX, the front panel HDSL related 2.06 indicators provide information about the loops between the HDSL NID unit and the HRX. Table 2. HDSL NID Unit Front Panel Indicators INDICATOR

COLOR

DESCRIPTION

STATUS

Green

Unit operating normally.

Yellow

Unit initializing or performing self test diagnostics. During selftest diagnostics, all other LEDs on front panel stay off.

Red

Fault detected during diagnostics.

Off

No power to the unit or blown fuse.

Yellow

Flashes yellow momentarily when intermittent BPV errors are detected. Steady yellow if DS1 signal has reached error rate (BPV) threshold value. (Default is 10–7.)

Red

DS1 Loss of Signal.

Off

DS1 signal normal.

Yellow

Signal to noise ratio on either of the HDSL loops is below the threshold value. (Default is 3 dB equivalent noise margin.)

Off

Signal to noise ratio is above threshold value in both HDSL loops.

Green

Loop 1 is active and HDSL signal is normal.

Yellow

Flashes yellow momentarily when intermittent HDSL CRC errors are detected on either end of loop 1. Steady yellow if bit error rate on HDSL loop 1 exceeds threshold value. (Default is 10 –7.)

Red

Loop 1 transceiver has lost frame synchronization.

Green

Loop 2 is active and HDSL signal is normal.

Yellow

Flashes yellow momentarily when intermittent HDSL CRC errors are detected on either end of loop 2. Steady yellow if bit error rate on HDSL loop 2 exceeds threshold value. (Default is 10–7.)

Red

Loop 2 transceiver has lost frame synchronization.

Off

Loop 2 inactive because CO HDSL unit is provisioned for single loop operation.

Yellow

Loopback condition is active at HDSL NID unit.

Off

Loopback at the HDSL NID unit is inactive.

Yellow

Alarm condition exists at the HLXC or the HRX.

Off

Remote alarms and customer loopback inactive.

DS1 LOS BER

SNR

L1 LOSW / BER

L2 LOSW / BER

LPBK CO ALM

Page 16 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

CUSTOMER DS1 CONNECTIONS RJ-48C 1 8

BINDING POSTS T1

R1

1

R

XMT (OUT) RCV (IN)

CABLE CODE COLOR CODE WHITE/BLUE BLUE WHITE/ORANGE ORANGE WHITE/GREEN GREEN WHITE/BROWN BROWN GREEN (18 GAUGE)

SIGNAL NAME LOOP 1 TIP LOOP 1 RING LOOP 2 TIP LOOP 2 RING DS1 RCV TIP (IN) DS1 RCV RING (IN) DS1 XMT TIP1 (OUT) DS1 XMT RING1 (OUT) EARTH GROUND

DANGER

RISK OF ELECTRICAL SHOCK. VOLTAGES UP TO 260 VOLTS MAY BE PRESENT ON TELECOMMUNICATIONS CIRCUITS.

WARNING WIRE 10 OF THE CABLE MUST BE CONNECTED TO EARTH GROUND. FAILURE TO DO SO MAY RESULT IN DAMAGE TO THE UNIT AND RISK OF ELECTRICAL SHOCK.

Tested To Comply With FCC Standards FOR HOME OR OFFICE USE

MODEL NO. PART NO. SERIAL NO.

UL



LISTED 21x5 TELEPHONE EQUIPMENT

VOLTS

AMPS

HERTZ

PH

L2 L1 LOSW LOSW CO ALM LPBK

BER

CAT # S/N  INMADE USA

BER

DS1 LOS SNR

BER STATUS

DATE CODE

9523-A

Figure 11. HDSL NID Unit Front Panel

B. Network Loopback Functions The HDSL NID unit supports network loopback shown in Figure 12. The network 2.07 loopback may be activated or deactivated by standard smart-jack loopback codes, by programmable inband loopback codes, through the craft interface, or by TL1 command. Note: To activate the network loopback with TL1 commands, the HDSL NID unit must be used with the Soneplex Broadband or Loop Extender System.

Page 17 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

B1 HLX 220, B1 HLX 319, HLX PLUS, OR HLXC

HDSL NID

LOOPED DS1 SIGNAL

DS1 SIGNAL FROM CPE DS1

HDSL

HDSL

DS1

HDSL LOOPS DS1 SIGNAL FROM NETWORK (LOOPBACK SIGNAL)

AIS TO CPE

NETWORK LOOPBACK

8620-A

Figure 12. Network Loopback at HDSL NID Unit

By default, the HDSL NID unit is provisioned to function as a NID. As a NID, the HDSL 2.08 NID unit supports the standard smart-jack loopback codes defined in TR-TSY-000312. Transmitting the inband (SF format) or out of band (ESF format) smart-jack loopup code at the network DS1 input activates the network loopback. Transmitting the smart-jack loopdown code deactivates the network loopback. If required, the NID function may be disabled through the craft interface. When the programmable loopback function is enabled, the HDSL NID unit will arm for 2.09 a network loopback when the smart-jack loopup code is sent. Once in the armed state, the network loopback is activated by transmitting a unique 16 bit activation code for at least three seconds. The network loopback is deactivated by transmitting a unique 16 bit deactivation code for three seconds. The various HDSL NID unit loopback codes are shown in Table 3. Table 3. Loopback Codes Applicable to the HDSL NID Unit CODE FUNCTION

BINARY CODE

In-Band Loopup or Arming Code

11000 (SF)

In-Band Loopdown or Disarming Code

11100 (SF)

Out-of-Band Loopup or Arming Code

0001001011111111 (ESF)

Out-of-Band Loopdown or Disarming Code

0010010011111111 (ESF)

Programmable Loopback Activate Code

1100 0111 0100 0010 (default)

Programmable Loopback Deactivate Code

1001 0011 1001 0011 (default)

Programmable Loopup Timeout Disable Code

1101 0101 1101 0011 (default)

When a programmable loopback is activated, the HDSL NID unit will send a loopback 2.10 signature consisting of 20 logic errors in the looped signal. This signature is sent approximately five seconds after the loopback is established. During loopback, the DS1 signal is looped back towards the network and an Alarm 2.11 Indication Signal (AIS) is sent to the CPE. A yellow LED on the HDSL NID unit front panel indicates when the loopback is activated.

Page 18 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

C. Customer Loopback Functions The HDSL NID unit supports the customer loopback function shown in Figure 13. When 2.12 the customer loopback is activated, the network signal is returned to the network at the HDSL NID unit DS1 interface as a keep-alive signal. When the HDSL NID unit Remote System is used in conjunction with the Soneplex Broadband or Soneplex Loop Extender System, the customer and network loopbacks can be activated by an MPU Craft Interface menu command or TL1 command. The standard inband (SF format) and out of band (ESF format) loopback codes will not activate or deactivate the customer loopback. T-TERM 220, HLX319, HLX PLUS OR D1 HLXC

HDSL NID

LOOPED DS1 SIGNAL FROM NETWORK

DS1

DS1

DS1 SIGNAL FROM CPE

HDSL

HDSL

HDSL LOOPS LOOPED DS1 SIGNAL

DS1 SIGNAL FROM NETWORK

8621-A

LOOPBACKS

Figure 13. Customer Loopback at Remote HDSL Unit

D. Loopback Functions with the HDSL Repeater Unit In a system with a Soneplex Version D HLXC, B HLX 220, B HLX 319 module, and 2.13 HDSL repeater, several loopback scenarios can be initiated through the Craft Interface, TL1, or by programmable loopback commands for installation and trouble analysis of the circuit. Figure 14 provides a summary of the loopback capabilities of the system. Note: TL1 activation method only applies to the Soneplex System CO installation.

D1 HLXC

1

HDSL

HDSL

DS1

DS1 SIGNAL FROM CPE

HDSL REPEATER

2

HDSL LOOPS

DS1

4

HDSL NID

HDSL

3

HDSL HDSL LOOPS

DS1

5

DS1 SIGNAL FROM CPE

6 LOOPED DS1 SIGNAL

DS1 SIGNAL FROM NETWORK

LOOPBACK TYPE

ACTIVATE/DEACTIVATE BY

REVERSE DIRECTION SIGNAL

1.) 2.) 3.) 4.) 5.) 6.)

CRAFT/TL1/HLXR FRONT PANEL SWITCH CRAFT/TL1/16 BIT CODE CRAFT/TL1 CRAFT/TL1/16 BIT CODE CRAFT/TL1 CRAFT/TL1/16 BIT CODE/NID CODE

CPE RCV → CPE XMT AIS → CPE NETWORK RCV → NETWORK XMT AIS → CPE NETWORK RCV → NETWORK XMT AIS → CPE

HLXC CUSTOMER HLXC NETWORK REPEATER CUSTOMER REPEATER NETWORK HLXR CUSTOMER HLXR NETWORK

8622-A

Figure 14. Network and Customer Loopbacks with the HRX

Page 19 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

3. SYSTEM INTEGRATION SERVICES ADC offers the following system integration services. For calls originating in the U.S.A. 3.01 or Canada, dial 1-800-366-3891, extension 3000. For calls originating outside the U.S.A. or Canada, dial 612-946-3000. Technical Assistance Center

• • • • •

Product Management Project Engineering Project Administration System Turn-Up and Test Support Service/Maintenance Agreements

Technical Training

• Product Technology • Custom Designed Training

Technical Operations

• Detail Engineering • End-to-End Installation • Drafting Services

4. CUSTOMER SUPPORT SERVICES ADC offers the following customer support services. For calls originating in the U.S.A. 4.01 or Canada, dial 1-800-366-3891, then request the extension listed. For calls originating outside the U.S.A. or Canada, dial 612-946-3000 or 612-946-3223. NSD Technical Assistance Center Extension 3223

• • • • • • • • •

Technical Information System/Network Configuration Product Specification Product Application Proposals Training Installation and Operation Assistance Troubleshooting and Repair Field Assistance

Sales Administration Extension 3000

• • • •

Quotation Ordering Delivery General Product Information

Product Return Department Extension 3000

• ADC Return Authorization number and instructions must be obtained before returning products.

Product information and service can also be obtained by writing ADC Telecommunications, 4.02 Inc., 4900 West 78th Street, Minneapolis, Minnesota 55435, U.S.A.

Page 20 © 1997, ADC Telecommunications, Inc.

ADCP-61-498 Issue 2, April 1997

Contents herein are current as of the date of publication. ADC reserves the right to change the contents without prior notice. In no event shall ADC be liable for any damages resulting from loss of data, loss of use, or loss of profits and ADC further disclaims any and all liability for indirect, incidental, special, consequential or other similar damages. This disclaimer of liability applies to all products, publications and services during and after the warranty period. This publication may be verified at any time by contacting ADC’s Technical Assistance Center at 1-800-366-3891, extension 3223 (in U.S.A. or Canada) or 612-946-3223 (outside U.S.A. and Canada), or by writing to ADC Telecommunications, Inc., Attn: Technical Assistance Center, Mail Station #77, 4900 West 78th Street, Minneapolis, MN 55435, U.S.A.

© 1997, ADC Telecommunications, Inc. All Rights Reserved Printed in U.S.A.

Page 21