Handbook – products, design and installation Version 2016.06
1.0.0.1 LOGSTOR FlexPipe handbook General Introduction
This section describes LOGSTOR’s solutions for heating and domestic water systems primarily for community heating projects.
Contents
1.1 System description 1.2 Fields of application 1.3 Component solutions Design 1.4
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
1.1.0.1 LOGSTOR FlexPipe handbook General - system description System description
This LOGSTOR handbook is primarily directed at the community heating/low temperature (up to 95°C) market with the products: • PexFlex and AluFlex for heating • PEX DW for domestic water Community heating as a concept does not differ essentially from district heating as regards the technical solutions, but primarily as regards the facts that: • the system is connected to a local energy source either by utilising: - existing systems or - new community heating systems • the ownership is rooted locally • the system, by its nature, has a limited size • the pipe dimensions are small, making flexible pipe systems an obvious choice • the temperatures are low, enabling optimisation of the product choice and thus reducing the construction costs. LOGSTOR FlexPipe systems contribute to this with: • good insulating properties. Certified thermal conductivity, lambda = 0.022 W/mK • few buried joints • no welding or soldering. Only mechanical joints. • narrow trenches = minimise the excavation and restoration costs also due to: -- the possibility to use TwinPipe -- the small bending radii -- self-compensating systems. No expansion components
LOGSTOR FlexPipe handbook
This handbook is based on excerpts from LOGSTOR´s Product Catalogue, Design, and Handling & Installation manual. Refer to these, if additional documentation and instructions are required. All rights reserved. The English version on www.logstor.com is the original. All other language versions are made according to the best knowledge of the translators.
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
1.2.0.1 LOGSTOR FlexPipe handbook General - fields of application Typical fields of application for community heating projects
System types:
Distribution:
Consumers:
Biogas
Horticultural farms
Landfill gas
Terraced and cluster houses
Biomass (Wood chips/straw) Heat pump (Air/ground)
Detached houses LOGSTOR FlexPipes
Schools
Industry
Sports centres
Geothermal energy
Small- and medium-sized enterprises
Solar system
Villages
BIO
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
1.3.0.1 LOGSTOR FlexPipe handbook General - component solutions Component solutions
In addition to choosing the pipe system there are only a few other choices to make. The primary choices are: A. Branching components B. Connection to the consumer C. Straight joint of two lengths of FlexPipe
A
Solution A
C
A. Branching components: - Preinsulated T-pieces and straight casing joints - T-press couplings and T-casing joints Illustration
FlexPipe · 2013.06
B
Components
Component No.
T-piece straight with couplings fitted onto it
3400
FXJoint (single pipe)
5057
SXJoint (TwinPipe) for foaming
5012
T-coupling, press T-coupling, compression
6062 Pex/Alu 6160 PEX DW
T-straight (single pipe)
5140
T-straight (TwinPipe) for foaming
5140
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
1.3.0.2 LOGSTOR FlexPipe handbook General - component solutions Solution B
B. Connection to the consumer: - In the cellar - Tilted bore - Embedded inlet pipe Illustration
Solution C
Components
Component No.
Wall entry sleeve
5800
End cap
5600
End cap
5600
or protective cap
1230
Inlet pipe
1236
End cap
5600
Protective cap
1230
C. Straight joint between two lengths of FlexPipe: - Jointing single pipes - J ointing TwinPipe/DoublePipe (PEX DW) Illustration
LOGSTOR A/S · Tel. +45 99 66 10 00
Components
Component No.
Press coupling
6000 PexFlex 6001 AluFlex
Compression coupling
6100 PEX DW and PexFlex
FXJoint (insulated)
5057
Press coupling
6000 PexFlex 6001 AluFlex
Compression coupling
6100 PEX DW and PexFlex
SXJoint (foamed)
5012
FlexPipe · 2013.06
1.4.1.1 Design with FlexPipes General Introduction
This section describes general and product specific rules for designing and dimensioning with PexFlex, AluFlex, and PEX DW.
Design and piping
The design of the pipeline is very simple, because the pipes are self-compensating. That means that expansion movements in the soil shall not be taken into account. in the design phase the following shall be decided upon: -- The design of the trench, see page 3.2.0.1 -- Bending radius of the relevant dimensions, see page 3.2.0.3 -- Introduction in buildings, see section2.6.1. (If FlexPipes are to be connected to existing systems with steel service pipes special rules apply! (see www.logstor.com/Design, section 11.3 and 13.1-2).
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
1.4.2.1 Design with FlexPipes Heat loss Conditions
The tables in this section are based on the following and are consequently only guiding: -- Flow temperature 80°C -- Return temperature 40°C -- Soil temperature 10°C -- Soil cover 0.6 m -- Distance between pipes (in connection with single pipes) 0.15 m -- Lambda value of the soil 1.6 W/mK If exact calculations with other condistions are required, please refer to LOGSTOR Calculator at www.logstor.com (use the quick link).
PexFlex
The heat loss is the total heat loss of flow and return pipe. Pipe pair: Series 1
Series 2
Service pipe ø mm
Outer casing ø mm
Heat loss W/m
Service pipe ø mm
Outer casing ø mm
Heat loss W/m
16
77
10.72
16
90
9.15
20
77
12.55
20
90
10.50
25
77
15.17
25
90
12.35
32
77
19.73
28
90
13.57
40
90
19.77
40
110
15.15
50
110
19.61
50
125
16.17
63
125
21.74
63
140
18.16
75
140
23.28
75
160
18.81
90
160
24.77
110
160
38.30
TwinPipes: Series 2
Series 1
LOGSTOR A/S · Tel. +45 99 66 10 00
Service pipe ø mm
Outer casing ø mm
Heat loss W/m
Service pipe ø mm
Outer casing ø mm
Heat loss W/m
2x16
90
7.59
2x16
110
6.14
2x20
90
9.33
2x20
110
7.24
2x25
110
8.91
2x25
125
7.46
2x32
110
12.29
2x32
125
9.64
2x40
125
13.51
2x40
140
10.73
2x50
160
11.92
FlexPipe · 2013.06
1.4.2.2 Design with FlexPipes Heat loss AluFlex
The heat loss is the total heat loss of flow and return pipe. Pipe pair: Series 1
Series 2
Service pipe ø mm
Outer casing ø mm
Heat loss W/m
Service pipe ø mm
Outer casing ø mm
Heat loss W/m
16
77
8.64
16
90
7.76
20
77
10.03
20
90
8.87
26
77
12.40
26
90
10.67
32
90
12.70
TwinPipes: Series 2
Series 1
FlexPipe · 2013.06
Service pipe ø mm
Outer casing ø mm
Heat loss W/m
Service pipe ø mm
Outer casing ø mm
Heat loss W/m
2x16
90
6.38
2x16
110
5.40
2x20
90
7.76
2x20
110
6.33
2x26
110
8.06
2x26
125
6.90
2x32
110
10.49
2x32
125
8.54
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
1.4.3.1 Design with FlexPipes Pressure loss charts General
In order to establish the correct pipe dimension it is necessary to know the water flow and the maximum allowable pressure loss. Small pipelines are often dimensioned after the available pressure difference, thereby minimising the dimension and the heat loss as much as possible as well as assuring the consumer the highest possible flow temperature. In addition, it must be ensured that the water speed will not be too high. For flexible pipelines it is recommended that the speed does not exceed 2 m/s in couplings and that the speed in house connections does not exceed 1 m/s to minimise the risk of noise. It is recommended that the system is dimensioned after the available pressure difference. In case it is not known, a value corresponding to 150 Pa/m is often used. As a dimensioning tool LOGSTOR Calculator can be used. It is available on: www.logstor.com/calculator. As an alternative to a hand calculation the graphs in the following can be used. Inter-related values between output (kW) and cooling as well as water flow (kg/h) appear from the graphs. The required output is found with the inter-related cooling, or the water flow can be found after the formula: q ≅ Q ∙ 860 ∆T q = Mass flow [ kg/h] Q = Output [kW] DT = Cooling The following graphs are based on: Water temperature of 80°C for heat pipes and 60° for domestic water pipes. Absolute PEX roughness = 0.01 mm
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
1.4.3.2 Design with FlexPipes Pressure loss charts PexFlex
kg/h
kW
ø 110
100000
ø 90
0 2,
ø 75
/s
m
2000
3000 2000
ø 63
0 1, /s
m
1000
/s
m
500 500
ø 50
50 0,
1000
ø 40
10000 300
300
ø 32
200
200 100 75 50
100 75 50 40
40
30
30 20
20 10
10 5 5
ø 20
1000 ø 16
500 400 300 200 100 25
0,
3
3
ø 25
m /s
50 40 30
AluFlex
30°C
ΔT 40°C
20 10 10
20
30
100
40 50
200
300 400 500
1000
2000
Pa/m
kg/h
kW
ø 40
0
2,
300 10000
/s
m
200
0 /s
m
50 /s
1000
/s
m
10 10
ø 20
25
20
0,
20
m
75 50 40 30
ø 26
0,
100 100 75 50 40 30
ø 32
1,
300 200
ø 16
500 400 300 200
5 5 3
3
100 50 40 30
FlexPipe · 2013.06
30°C
ΔT 40°C
20 10 10
20
30
40 50
100
200
300 400 500
1000
2000
Pa/m
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
1.4.3.3 Design with FlexPipes Pressure loss charts PEX DW
kg/h
ø 63
0 2, /s
m ø 50
0 1,
10000
m /s
ø 40
50 0, /s
m
ø 32
25 0,
ø 28
/s
m ø 22
1000 ø 16
500 400 300 200 100 50 40 30 20 10 10
LOGSTOR A/S · Tel. +45 99 66 10 00
20
30
40 50
100
200
300 400 500
1000
2000
Pa/m
FlexPipe · 2013.06
2.0.0.1 FlexPipes Product Catalogue Introduction
This section contains a presentation of the LOGSTOR products: -- pipes -- fittings -- casing joints -- accessories -- tools available to the following systems: -- heating: PexFlex AluFlex -- domestic water: PEX DW
Contents
Technical description of FlexPipes
2.1
PexFlex 2.2 AluFlex 2.3 PEX DW
2.4
Casing joint types
2.5
2.6 Terminations with FlexPipes -- General 2.6.1 -- PexFlex 2.6.2 -- AluFlex 2.6.3 Tools for FlexPipes
FlexPipe · 2013.06
2.7
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.1.0.1 FlexPipes Technical description Overview
Materials, properties etc. for LOGSTOR FlexPipes
2 1
4
3
Service pipe (1)
PexFlex
AluFlex
PEX DW
PEXb ø 16-110 mm EVOH diffusion barrier 3.1 certificate is available
PEX/Alu/PE (out.) ø 16-32 mm
PEX ø 22-63 mm
Polyurethane foam, PU Blowing agent: Cyclopentane Certified thermal conductivity: l50 = 0.022 W/mK
Insulation (2) Diffusion barrier (3)
Multilayer polymer foil
Outer casing (4) Standards/approvals
Polyethylene PELD Service pipe: - EN 12318 - DVGW K 178 and 183
EN 15632-2
EN 15632-2
PN 6: ø 16 mm PN 10: ø 20-110 mm
PN 10
PN 10
Temperature, °C - Continuous max. - Max. at 100 h/year
85 95
95 105
85 95
Delivered lengths: Standard lengths Fixed lengths min. 10 - max. 90 m
50 and 100 mm Yes
50 and 100 mm Yes
50 and 100 mm
Pressure, Pbar
Measurements of FlexPipe coil Apply to series 1, 2, and TwinPipe
Di H De
LOGSTOR A/S · Tel. +45 99 66 10 00
-
Outer casing, ø out. mm
Measure approx.
77
90
110
125
140
160
Di
1600
1600
1800
1800
2000
2000
De
2200
2300
2200
2300
2300
2300
H50
300
350
500
650
1100
1300
H100
425
475
800
1150
2250
2400
FlexPipe · 2013.06
2.2.0.1 FlexPipes PexFlex - pipes in coils Single pipe
Component No. 2100. Lengths: 50 or 100 m PN 6, SDR 11. PEX service pipe
Series 1 Outer casing
Series 2 Outer casing
ø out. mm
Wall t. mm
ø out. mm
Wall t. mm
ø out. mm
Wall t. mm
16**
2.2
77
2.2
90
2.5
20
2.0
77
2.2
90
2.5
25
2.5
77
2.2
90
2.5
32
2.9
77
2.2
90
2.5
40
3.7
90
2.5
110
2.5
50
4.6
110
2.5
125
2.5
63
5.8
125
2.5
140
3.0
75
6.9
140
3.0
160
3.0
90
8.2
160
3.0
110
10.0
160*
3.0
* Series 0. Note! Preinsulated components have casing pipes ø 180 mm. ** PN 10.
TwinPipe
Component No. 2190. Lengths: 50 or 100 m PN 6, SDR 11. PEX service pipe
Series 1 Outer casing
Series 2 Outer casing
ø out. mm
Wall t. mm
ø out. mm
Wall t. mm
ø out. mm
Wall t. mm
16/16*
2.2
90
2.5
110
2.5
20/20
2.0
90
2.5
110
2.5
25/25
2.5
110
2.5
125
2.5
32/32
2.9
110
2.5
125
2.5
40/40
3.7
125
2.5
140
3.0
50/50
4.6
160
3.0
* PN 10.
Order example
FlexPipe · 2013.06
System
-
Component
-
Component No.
-
Dim. service/casing pipe -
Length:
PexFlex
-
pipe
-
2100
-
25/77
-
50 m
PexFlex Twin
-
pipe
-
2190
-
40x2/125
-
100 m
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.2.0.2 FlexPipes PexFlex - preinsulated bends Application
PexFlex 90° bends are used, when a sharper curvature than allowed by the minimum bending radius is required.
90° preinsulated bend
PexFlex bends have PEX service pipes. Do not shorten! Are available without free ends.
Component overview
Component No. 2500. TwinPipe
Single pipe Outer casing ø out. mm
PEX pipe ø out. mm
Series 1
20
77
Outer casing ø out. mm
Series 2
PEX pipe ø out. mm
Series 1
Series 2
90
20/20
90
110
25
77
90
25/25
110
125
32
77
90
32/32
110
125
40
90
110
40/40
125
140
50/50
160
50
110
125
63
125
140 160
75
140
90
160
110
*180
*P exFlex in coils is delivered as ø 110 mm in a ø 160 mm casing pipe.
Order example
System - Component - Component No. - Dimension: PexFlex - 90° bend
LOGSTOR A/S · Tel. +45 99 66 10 00
-
2500
-
32/90
FlexPipe · 2013.06
2.2.0.3 FlexPipes PexFlex - preinsulated branches Description
Preinsulated branches for PexFlex are straight branches with steel service pipes. They are delivered with press couplings already welded on to them. As an alternative they can be ordered with compression couplings.
Component No. 3400 605
40 0m m
Single pipes
PexFlex, main pipe, D1 Service pipe
Branch ø out. mm, D2 Dim. outer casing = main pipe
Outer casing, ø out. mm
ø out. mm
Series 1
Series 2
16
20
25
32
16
77
90
x
20
77
90
x
x
25
77
90
x
x
x
32
77
90
x
x
x
x
40
90
110
x
x
x
x
x
50
110
125
x
x
x
x
x
x
63
125
140
x
x
x
x
x
x
x
75
140
160
x
x
x
x
x
x
x
x
90
160
180
x
x
x
x
x
x
x
x
x
110
160
180
x
x
x
x
x
x
x
x
x
40 0 FlexPipe · 2013.06
40
50
63
75
90
110
x
Component No. 3490 m m
TwinPipes
mm
60 5
mm
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.2.0.4 FlexPipes PexFlex - preinsulated branches TwinPipes, continued
Order example
PexFlex, main pipe, D1 Service pipe
Branch, ø out. mm, D2 Dim. outer casing = main pipe
Outer casing, ø out. mm
ø out. mm
Series 1
Series 2
16/16
16/16
90
110
x
20/20
90
110
x
20/20
25/25
110
125
x
x
x
32/32
110
125
x
x
x
40/40
125
140
50/50
160
PexFlex - Straight branch -
32/32
40/40
x
x
x
x
x
x
x
x
x
x
x
3490
50/50
x
System - Component - Component No. -
LOGSTOR A/S · Tel. +45 99 66 10 00
25/25
-
x
D1 - D2: 32/32-125 -
25/25-125
FlexPipe · 2013.06
2.2.0.5 FlexPipes PexFlex - transition pipes, TwinPipe - single pipe Application
Preinsulated transition pipes are used in connection with straight transition from a single pipe system to a TwinPipe system. As a standard series 2 dimensions for single pipe ends and series 1 dimensons for TwinPipe ends are delivered for PexFlex. As the flow pipe is always placed at the bottom, the transition is available in a “type 1” as well as a “type 2” version.
Description
"Type 1" and "type 2" are defined by viewing the transition pipe from the single pipe end perspective. Type 1
Type 2 C/C = 245 mm
0m 1 70
Possible combinations
Order example
Component No. 3071 Single pipe ø out. mm
16/77
20/77
25/77
32/77
40/90
50/110
TwinPipe ø out. mm
16/90
20/90
25/110
32/110
40/125
50/160
System - Component - Component No. - Dim. single - Dim. Twin - Type: PexFlex - Overgangsrør -
FlexPipe · 2013.06
m
3071
-
25/77
-
25/110
-
1
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.2.0.6 FlexPipes PexFlex - press couplings Coupling types
For PexFlex-systems the three most commonly used coupling types are: -- Straight press coupling: Same dimension -- Reducing press coupling: 1-3 dimensional offsets dependent on the dimension -- Straight branch with press coupling Press couplings ensure a permanent sealing at all temperature variations. Alternative: Straight couplngs as well as T-couplings are also available as compression couplings, see page 2.2.0.8.
Straight and reducing couplings
Component No. 6000 ø1
ø1
Dimension = PEX ø out. mm
ø2
ø1
Coupling end ø1
16
20
x
x
22
25
x
x
28
32
40
50
63
75
90
110
Coupling end ø2 16 20 22
x
x
25 28
x x
x x
32
x
40
x x
63
x x
75
x x
90
x x
110
System - Coupling type - ø1
x x
50
Order example
x
x x
- ø2:
PexFlex - Press/reducing - 40 - 32
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
2.2.0.7 FlexPipes PexFlex - press couplings T-branch with press couplings
Component No. 6060
ø2 ø1 PEX main pipe ø1 = ø3 ø out. mm
ø3
PEX branch, ø2 ø out. mm 16
20
20
25
32
40
50
63
75
x
x
x
32
x
x
x
x
40
x
x
x
x
50
x
x
x
x
x
63
x
x
x
x
x
x
75
x
x
x
x
x
x
x
90
x
x
x
x
x
x
x
x
110
x
x
x
x
x
x
x
x
PEX main pipe with reduction ø1 - ø3 ø out. mm
20
25-20
x
25
32
40
50
x
x
63
x
75-50
x
75-63
x
90-63
x
x
90-75
x
Coupling type
PexFlex - T-branch PexFlex - T-branch with reduction
FlexPipe · 2013.06
75
x
63-50
Other coupling types
x
PEX branch, ø2 ø out. mm
63-40
System -
110
x
25
32-25
Order example
90
- - -
Comp. No. - 6060 6060
ø1
- 75 - 75
-
ø2
x
- ø3:
- 32 - 75 - 50 - 63
-- Transition coupling for steel service pipe. From steel/PEX: ø 26.9/16 mm to ø 114.3/110 mm.
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.2.0.8 FlexPipes PexFlex - compression couplings Coupling types
For PexFlex compression couplings can also be used. They are available as straight couplings and T-couplings. Please note that in some countries special rules apply to the use of not visible compression couplings.
Straight connections
Straight compression coupling:
ø20-32
Component No. 6100 PEX pipe diameter d, mm
20
25
32
ø40-110
Component No. 6100 PEX pipe diameter d, mm 40
50
63
75
90
110
Order example: System PexFlex
Branches
- Component - Component No. - Dim. service pipe: - Straight compression coupling - 6100 - 63
Compression-T-coupling, component No. 6160.
ø2
In principle ø2 and ø3 are optional, provided that they are ≤ ø1.
ø3
ø1
PEX-branch, ø2 ø out. mm
PEX main pipe ø1 = ø 3 ø out. mm
20
20
x
25
x
32 x
32
40
50
63
75
90
110
x x
40 50
25
x
x
x
x
x
x
x
x
63
x
x
x
x
x
x
75
x
x
x
x
x
x
x
90
x
x
110
x
x
x
x
x
x
x
x
x
x
x
x
Order example: System - Component - Component No. PexFlex - Compression-T-coupling - 6160
LOGSTOR A/S · Tel. +45 99 66 10 00
- Dimension from/to: - 50/28
FlexPipe · 2013.06
2.3.0.1 FlexPipes AluFlex - pipes in coils Single pipe
Component No. 2100 AluPEX Series 1 Series 2 Casing pipe Casing pipe ø out. Wall t. ø out. Wall t. ø out. Wall t. mm mm mm mm mm mm
TwinPipe
16 2.2 77 2.2 90 2.5 20 2.5 77 2.2 90 2.5 26 3.0 77 2.2 90 2.5 32 3.0 90 2.5
Component No. 2190 AluPEX Series 1 Series 2 Casing pipe Casing pipe ø out. Wall t. ø out. Wall t. ø out. Wall t. mm mm mm mm mm mm 16/16 2.0 90 2.5 110 2.5 20/20 2.5 90 2.5 110 2.5 26/26 3.0 110 2.5 125 2.5 32/32 3.0 110 2.5 125 2.5
Order example
System - Component - Component No. - Dim. service pipe/outer casing - Length: AluFlex - Single pipe - AluFlex - TwinPipe -
FlexPipe · 2013.06
2100 2190
- -
20/90 26-26/110
- 100 - 50
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.3.0.2 FlexPipes AluFlex - preinsulated branches Description
Preinsulated branches for AluFlex are straight branches with steel service pipes. They are delivered with press couplings already welded on to them.
Component No. 3400 605
40 0m m
Single pipe
AluFlex, main pipe, D1 Service pipe
Branch ø out. mm, D2 Dim. outer casing = main pipe
Outer casing, ø out. mm
ø out. mm
Series 1
Series 2
16
20
26
16
77
90
x
20
77
90
x
x
26
77
90
x
x
x
32
90
x
x
x
x
60 5
40 0 AluFlex, main pipe, D1 Service pipe
Order example
32
Component No. 3490 m m
TwinPipes
mm
ø out. mm
Series 1
Series 2
16/16
16/16
90
110
x
20/20
26/26
20/20
90
110
x
x
26/26
110
125
x
x
x
32/32
110
125
x
x
x
-
AluFlex - Straight branch -
LOGSTOR A/S · Tel. +45 99 66 10 00
Branch, ø out. mm, D2 Dim. outer casing = main pipe
Outer casing, ø out. mm
System - Component
mm
Component No. - 3490
32/32
x
D1 - D2:
- 32-32/125 - 26-26/125
FlexPipe · 2013.06
2.3.0.3 FlexPipes AluFlex - press couplings Coupling types
For AluFlex systems the three most commonly used coupling types are: -- Straight press coupling: Same dimension -- Reducing press coupling: 1-3 dimensional offsets dependent on the dimension -- Straight branch with press coupling Press couplings ensure a permanent sealing at all temperature variations. Please note that press couplings for AluFlex are equipped with O-rings and insulator rings. See "Installation of press couplings".
Straight and reducing couplings
Component No. 6001
Coupling end ø1
16
ø1
ø1
Dimension = PEX ø out. mm 20
26
32
Coupling end ø2 16
x
20
x x
26
x x
32
Order example
x
System - Coupling type - ø1
ø2
ø1
x
- ø2:
AluFlex - Press/reducing - 32 - 26
T-branch with press couplings
Component No. 6062 Main pipe Branch, ø 2 ø1 = ø3 AluFlex, ø mm AluFlex 16 20 26 32 16 20 26 32
Order example
Other coupling types
x x x x
x x x
ø2 x x
x
ø1
System - Coupling type - ø1
- ø2
-
ø3:
AluFlex
- 20
-
32
- T-press coupling - 32
ø3
-- Transition coupling for steel service pipe. From steel/PEX: ø 26.9/16 mm to ø 33.7/32 mm. -- End coupling, closed press coupling. Also see "Terminations with AluFlex", page 2.6.3.
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.4.0.1 FlexPipes PEX DW - pipes in coils Application
The FlexPipe system “PEX DW” for domestic water is a complete distribution and house entry system.
Single pipe, PN 10 SDR 7.4
Distribution pipe, component No. 2100
DoublePipe, PN 10 SDR 7.4
Order example
PEX service pipe
Outer casing (series 1)
ø out.
Wall thick.
ø out.
Wall thick.
mm
mm
mm
mm
22
3.0
77
2.2
28
4.0
77
2.2
32
4.4
77
2.2
40
5.5
90
2.5
50
6.9
110
2.5
63
8.7
125
2.5
Circulation pipe, component No. 2190 PEX service pipe
Outer casing (series 1)
ø out.
Wall thick.
ø out.
Wall thick.
mm
mm
mm
mm
28/22
4.0/3.0
90
2.5
32/22
4.4/3.0
110
2.5
40/28
5.5/4.0
125
2.5
50/32
6.9/4.4
125
2.5
System - Component - Component No. - Dim. service/casing pipe - PEX DW - DoublePipe -
LOGSTOR A/S · Tel. +45 99 66 10 00
2190
-
32/22-90
-
Length: 50
FlexPipe · 2013.06
2.4.0.2 FlexPipes PEX DW - preinsulated bends Preinsulated 90° bend
PEX DW bends have PEX service pipes. Do not shorten them! They are delivered without free ends.
Component overview
Order example
FlexPipe · 2013.06
Component No. 3500.
PEX pipe ø out. mm
Outer casing ø out. mm
22
77
28
77
32
77
40
90
50
110
63
125
System - Component
- Component No. - Dimension:
PEX DW - 90° bend
-
3500
-
50/110
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.4.0.3 FlexPipes PEX DW - compression couplings Connection types
PEX DW pipes are connected by means of compression couplings. When ordering, please state 10 bar.
Straight connections
Straight compression coupling:
ø22-32
Component No. 6100 PEX pipe diameter d, mm
22
28
32
ø40-63 Component No. 6100 PEX pipe diameter d, mm
40
50
63
Order example: Component - Component No. - Dim. service pipe: System - PEX DW - Straight compression coupling, 10 bar - 6100 - 63 Compression coupling with male thread, component No. 6100. PEX pipe ø out. mm
Male thread /4”
1”
22
x
x
28
x
x
3
11/4”
32
x
x
40
x
x
50
x
1½”
2”
x
63
x
Compression coupling with female thread, component No. 6100. PEX pipe ø out. mm
Female thread /4”
1”
22
x
x
28
x
x
3
11/4”
32
x
x
40
x
x
50 63
x
1½”
2”
x x
Order example: System - Component - Component No. - Dimension (mm/"): PEX DW - Compression coupling, male, 10 bar - 6100 - 32/11/4
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
2.4.0.4 FlexPipes PEX DW - compression couplings Bends
Compression coupling. Union elbow with male thread, component No. 6100. PEX pipe
Male thread
ø out. mm
/4 ”
1”
22
x
x
28
x
x
3
11/4”
32
x
40
x
1½”
50
2”
x
63
x
Compression coupling. Union elbow with female thread, component No. 6100. PEX pipe
Female thread /4”
1”
22
x
x
28
x
x
ø out. mm
3
11/4”
32
x
40
x
50
1½”
2”
x
63
x
Order example: Component - Comp. No. - Dimension (mm/"): System - PEX DW - Compression coupling, 90° male, 10 bar - 6100 - 50/11/4
Branches
Compression-T-coupling, component No. 6160. Branch ø out. mm
Main pipe ø out. mm
22
28
32
40
50
22
x
28
x
x
x
32
x
x
x
40
x
x
x
x
50
x
x
x
x
x
63
x
x
x
x
x
63
x
Order example: System - Component - PEX DW - Compression-T-coupling, 10 bar -
FlexPipe · 2013.06
Component No. - Dimension from/to: 6160 - 50/28
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.5.0.1 FlexPipes Casing joint types Casing joint types
From LOGSTOR’s casing joint assortment 4 types have been selected which ensure simple and efficient connections of FlexPipes. For single pipes shrink joints with insulation shells are used. Alternatively, casing joints for foaming may be used. For TwinPipe shrink joints for foaming with foam packs are used.
Overview
LOGSTOR A/S · Tel. +45 99 66 10 00
Pipe type
Straight connections
Branches
Insulation
Single pipe
FXJoint
T-joint, straight F
Insulation shells
TwinPipe
SXJoint
T-joint, straight
Foam packs
FlexPipe · 2013.06
2.5.1.1 FlexPipes Casing joints for FlexPipes - FXJoint Application
The shrink joint FXJoint with insulation shells is used for connections on single pipe FlexPipes ø 77-160 mm. The sleeve is pre-installed on the pipes, before they are connected. FXJoints are installed by means of a soft gas flame. (See installation instructions section 3.5).
Description
The FXJoint set consists of: 1. Insulation shells with flexible core for couplings 2. Shrink sleeve with integrated mastic 3. Cleaning tissue
2 1 3
Materials
Sleeve
Cross-linked PE (PEX) with mastic, embedded in the ends
Insulation shells
Hard PU, polyurethane, furnished with soft PU
Component overview
Component No. 5057
Order example
Casing joint type
- Component No.
FXJoint
- 5057 -
FXJoint is available in 2 dimensions, covering the following two intervals: - Dimension ø 77-125 mm - Dimension ø 125-160 mm
-
Outer casing dimension: 125
(No distinction is made between series 1 and 2).
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.5.2.1 FlexPipes Casing joints for FlexPipes - T-joint, straight F Application
The shrink joint “T-joint, straight F” with insulation shells is used for straight connections on single pipe FlexPipes ø 77-160 mm. Collar, shrink wrap and T-shoe are pre-installed on the branch prior to connection to the main pipe.
Description
A complete set consists of: 1. Closure patch 2. Shrink wrap 3. Insulation shells with marking for branch 4. T-shoe 5. Insulation shells 6. Collar 7. Cleaning tissue
Materials
-
Component overview
Component No. 5140
Order example
T-shoe Shrink wrap and collar Closure patch Insulation shells
6 5 4 2
1
3
7
PE with hotmelt in the branch PE with mastic Cross-linked polyolefin with fibreglass reinforcement Hard PU, polyurethane with soft PU embedded
Branch, outer casing ø mm
Main pipe, outer casing ø mm
77
77
x
90
x
x
110
x
x
x
125
x
x
x
x
140
x
x
x
x
x
160
x
x
x
x
x
90
110
125
Casing joint type - Component No.
- From dimension
- To dimension:
T-joint, straight F -
-
-
5140
160
140
160
x
125
No distinction is made between series 1 and 2.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
2.5.3.1 FlexPipes Casing joints for FlexPipes - SXJoint Application
The shrink joint SXJoint for foaming is used for straight connections of Twin FlexPipes ø 77-160 mm. The sleeve is pre-installed on the pipes prior to their connection. The SXJoint is installed by means of a soft gas flame, see installation instructions section 3.7. The joint is for foaming and consequently shrinkable at the ends and not in the middle.
Description
The SXJoint set consists of: 1. Shrink sleeve (The joint ends contain mastic) 2. Venting plugs 3. Expansion plugs 4. Wedge plugs 5. Patches 6. Collars (to be ordered separately)
4 3 2
Shrink sleeve: Venting plugs: Expansion plugs: Wedge plugs: Patches:
Component overview/data
Component No. 5012
L
1
The joint set is wrapped in white PE foil on delivery. Store the shrink sleeve vertically. Max. temperature during transportation and storage: 80°C.
Materials
6
5
Crosslinked PE (PEX) LDPE PEX with a butyl mastic ring PEX PEX with water-resistant hotmelt
Outer casing dim. ø mm
Shrinkable to ø mm
L mm
90 77 650 110 90 650 125 110 650 140 125 650 160 140 650 180 160 650
For outer casing dimension ø 77 mm a ø 90 mm sleeve is used.
Order example
Accessories
Casing joint type - For outer casing dmension - Foam pack
- Series:
SXJoint
-
-
ø 125 mm
-
incl.
2
Foam packs are used for foaming. When ordering, simply state the insulation series and that the casing joint must be delivered including foam packs, then the correct dosage will be delivered automatically. The foam pack size appears from the table on page 3.12.0.1.
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.5.4.1 FlexPipes Casing joints for FlexPipes - T-joint, straight branch Application
The shrink joint T-joint for foaming is used for branching single pipe FlexPipes ø 77-160 mm. Collar, shrink wrap and T-shoe are pre-installed on the branch prior to connection to the main pipe.
Description
A complete set consists of: 1. Closure patch 2. Shrink wrap 3. T-shoe 4. Collar 5. Venting, expansion, and wedge plugs
Materials
T-shoe: Shrink wrap and collar: Closure patch: Venting plugs: Expansion plugs: Wedge plugs:
Component overview
Component No. 5140
Order example
Accessories
2 1
L1 L2
Branch, outer casing ø mm
Main pipe, outer casing ø mm
90
125
140
90
x x
x
125
x
x
x
140
x
x
x
x
160
x
x
x
x
T-joint, straight
ø 160 mm - ø 125 mm -
-
110
110
From dim. - To dim.
5140
5
PE with hotmelt in the branch PE with mastic Cross-linked polyolefin with fibreglass reinforcement LDPE PEX with mastic PEX
Casing joint type - Comp. No. - -
4
3
- Foam pack incl.
160
x
-
Series:
-
1
Foam packs are used for foaming. When ordering, simply state the insulation series and that the casing joint must be delivered including foam packs, then the correct dosage will be delivered automatically. The foam pack size appears from the table on page 3.12.0.1.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
2.6.1.1 Terminations with FlexPipes General Possible terminations. Description
In principle there are 4 methods to introduce FlexPipes through a wall: - Straight lead-in through the base - Tilted bore in the base - 90° lead-in through the base with embedded inlet pipe - External lead-in through the wall, covered by a cabinet For internal use a number of possible mountings and valves, adjusted to the pipe type and expansion stress (see under the different FlexPipe types) are offered. Consequently, it is possible to find a solution which fits the specific task precisely.
Straight lead-in throug the base. Wall entry sleeve
Is used by direct introduction into e.g. service space, cellar etc. Component No. 5800. Dependent on whether bore or core has been used a wall entry sleeve may be required.
Outer casing ø out. mm
Sealing ring
77 90 110 125 140 160
Order example
System - Component -
Tilted bore in the base
x x x x x x
- Component No. - Dim. service/casing pipe - Length:
- Wall entry pipe -
5800
-
32/22-90
-
50
Is used in connection with existing buildings, where boring is preferred to cutting a hole.
A projected FlexPipe end may be covered by a tight-fitting protective cap. Component No. 1230. As for TwinPipes the conical connecting pieces are adjusted to the service pipe end.
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.6.1.2 Terminations with FlexPipes General Tilted bore in the base, component overview for protective cap
Order example
Lead in through base by means of embedded inlet pipe
Component No. of protective cap for single pipe: 1230. General for all FlexPipe types. Dimension internal/external mm
System
20/77
25/77
PexFlex
x
x
AluFlex
x
System -
Component
AluFlex -
Protective cap
26/77
32/77
22/90
26/90
32/90
x x
x
x
- Component No. - -
1230
-
x
40/90
50/110
x
x
x
Dimension: 26/77
Is used in connection with new buildings to facilitate later introduction of FlexPipe without drawbacks for the building.
2/3
1. Inlet pipe 2. Sealing reduction or
1
3. End-cap Use a special pulling tool to pull the pipe through the inlet pipe, see page 2.7.1.1.
Inlet pipe (1)
Component No. 1236.
ø
FlexPipe R H L ø ø out. mm mm mm mm mm
R
800 1050 900 125 800 1050 900 125 800 1050 900 140
H
77 90 110
L
Order example
System -
Component
FlexPipe -
Inlet pipe
LOGSTOR A/S · Tel. +45 99 66 10 00
- Component No. - -
1236
-
Dimension: 110/140
FlexPipe · 2013.06
2.6.1.3 Terminations with FlexPipes General Protective cap (2)
The introduction may be terminated with a protective cap (see section about tilted introduction) or an end-cap.
End-cap (3)
Shrinkable end-cap for single pipe. Component No. 5600
Service pipe ø out. mm
Outer casing ø out. mm
16-32 35-40 42-50 54-63 70-75 90
DHEC No.
77 90 110 125 140 160
2000 2100 2200 2300 2400 2500
Shrinkable end-cap for Twin FlexPipe. Component No. 5600
Service ppe ø out. mm
Outer casing ø out. mm
16/16-20/20 22/22-25/25 28/28 35/35
Order example
System
90 110 125 140
- Component
Twin FlexPipe -
DHEC No.
End-cap
3200 3200 3200 3280
- Component No. -
Dimension:
-
28/28-125 or DHEC 3200
5600
-
Description. Internal fixing. Connection to house installation
There are a lot of suitable individual solutions, but LOGSTOR offers a number of possibilities which make allowance for the material properties of the individual pipe type and the pure pipestatic influences.
Mounting type A
Applicable for all types of introduction in connection with screw couplings. Used for: - PexFlex - AluFlex Product No. 0005 0000 802 011.
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.6.1.5 Terminations with FlexPipes General Accessories for mounting type A
For installation on this mounting an adapter coupling with ex- and internal thread respectively is available for threaded couplings, screw couplings and loose ball valves.
Thread 3/4” 1”
Product No. 0005 0000 202 021 0005 0000 202 022
In connection with mounting type A (or for individual solutions) a 3/4” ball valve with internal thread is available. Component No. 4261
Mounting type C
Design
Flow (red)
Return (blue)
All-welded steel
x
x
Nickeled brass
x
x
If expansion movements occur in the FlexPipes through the wall, the pipe bending must be ensured by means of a matrix (especially in connection with cooling of the pipes). Primarily used for: - PexFlex (max. ø 28 mm) - AluFlex
Order example
Service pipe ø out. mm 18 - 20 22 - 26 28 - 32
Product No. 0005 0000 202 023 8-41631 8-41632
System -
Component
-
FlexPipe -
Mounting type C
-
LOGSTOR A/S · Tel. +45 99 66 10 00
Component No.
-
0005 0000 202 023 -
Dimension: 18-20
FlexPipe · 2013.06
2.6.2.1 Terminations with FlexPipes PexFlex Internal wall installation (with relief)
Mounting type A is used for all introductions where there is some kind of expansion absorption. Product No. 0005 0000 202 011. See ”Terminations, general”.
Termination in cabinet (relieved)
Press coupling with male thread. Material: Brass Component No. 6000. To be used relieved (in cabinet or indoors). PEX pipe ø out. mm 16 20 22 25 28 32 40 50 63 75 90 110
Order example
System -
/2” x
1
3
/4” x x x x
Male thread 1” 11/4” 11/2”
2”
3”
x x
x x x x x x x
Component
- Component No.
PexFlex - Press coupling with male thread -
Internal installation
6000
- Dimension: -
32/11/4”
Compression coupling with male thread can be used for internal installation. Component No. 6100. The coupling is made of brass.
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.6.2.2 Terminations with FlexPipes PexFlex Internal installation, continued
PEX pipe
Male thread
ø out. mm
3/4”
20
x
22
x
x
25
x
x
28
x
x
32
1”
1 1/4”
x
40
1 1/2”
x x
63
x
75
x
90
x
110
x
System -
Component
- Component No. - Dimension:
PexFlex - compression coupling with male thread -
Internal wall installation (without relief) ø 22 and 28 mm
3”
x
50
Order example
2”
Mounting type A combined with mounting type C is used, when the PexFlex pipe is installed directly through the wall without any absorption of the expansion movement.
6100
50/11/2”
-
A
See page 2.6.1.4.
C
Internal wall installation (without relief), ø 32 and 40 mm
In connection with PexFlex ≥ ø 32 mm mounting type C cannot be used, as the radius will be too large. Instead a 90° bend coupling is used. Component Nos. 6100, see page 2.4.0.4. (Naturally, this solution can also be used in cellars).
LOGSTOR A/S · Tel. +45 99 66 10 00
A
FlexPipe · 2013.06
2.6.2.3 Terminations with FlexPipes PexFlex Inlet pipe
Order example
End fitting
Component No. 1236. For casing øD, mm
77
90
110
125
Pipe K, mm
110
125
140
160
R = 6 × øD
System - Component
- Component No. -
PexFlex -
-
Inlet pipe
1236
-
Dimension: 90/125
Component No. 5700. The outmost 100 mm of the end fitting is shrinkable.
500
100
1. End fitting 2. Shrink sleeve
Order example
FlexPipe · 2013.06
PEX pipe ø out. mm
Outer casing ø out. mm
20
77
22
77
25
77
28
77
32
77
40
90
50
110
63
125
75
140
90
160
System -
Component
PexFlex -
End fitting
1 2
- Component No. - -
5700
-
Dimension: 32/77
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.6.3.1 Terminations with FlexPipes AluFlex Internal wall installation (partial relief)
In connection with introduction with partial absorption of the expansion movement - Tilted bore - Embedded inlet pipe mounting type A is used.
Internal wall installation (with relief)
If the AluFlex pipe is installed through the wall after the expansion movement has been absorbed, mounting type A can be used. Product No. 0005 0000 202 011. See ”Terminations, general”.
Straight screw couplings (with relief)
Order example
Internal wall installation (without relief)
When the lead-in has been relieved, straight couplings can be used to connect to internal installations. Dimension ø out. mm
Product No.
20
6001 0020 043 000 (3/4”)
26
6001 0026 043 000 (3/4”)
32
6001 0032 043 000 (1”)
System -
Component
-
AluFlex -
Screw coupling
-
1
2
Component No.
-
6001 0032 043 000 -
Mounting type A combined with mounting type C is used, when the AluFlex pipe is installed directly through the wall without any absorption of the expansion movement.
Dimension: 32/1”
A min. 300 mm C
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
2.7.1.1 FlexPipes Tools for FlexPipes, general Introduction
This section describes the tools which can be used generally for: - PexFlex - AluFlex
Pulling tool
If concrete cast pipes or tilted bore in the base is used, then pulling tool and pulling sleeve are used. LOGSTOR Service Department can refer to a supplier.
Transport and uncoiling
To transport or uncoil FlexPipes it is possible to hire or buy special FlexPipe trailers from various suppliers. Especially for major dimensions of AluFlex and major numbers of house entries, the FlexPipe wagon with motorized straightener and remote control are recommended. Please contact our Service Department.
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.7.2.1 FlexPipes Tools for PexFlex Introduction
This section describes the tools which are used especially in connection with Pexflex pipes.
Installation equipment Joints
When installing compression couplings for PexFlex pipes a tool set, containing compression tool and accessories for PEXservice pipe dimensions ø 16, 22, 25, 28, 32, 40 and 50 mm, is used. Available in a sturdy carrying case, product No. 0500 0000 002 006. 1. 2. 3. 4. 5. 6. 7. 8.
Compression tool Exchangeable compression inserts Saw Plastic pipe cutter for ≤ ø 40 mm Plastic pipe cutter for ≤ ø 63 mm Stripping knife Deburring tool Special lubricating grease
3
8
1 2
4 5
6
7
For the installation a hydraulic pump must also be used. Product No. 0520 0000 008 100.
Stripping tools
Stripping tools Type
Product No.
A
20-25
9000 0000 006 001
32-40
9000 0000 006 011
B
LOGSTOR A/S · Tel. +45 99 66 10 00
A
PEX dimension ø mm
40-50
9000 0000 006 003
63
9000 0000 006 004
75
9000 0000 006 005
90
9000 0000 006 006
110
9000 0000 006 007
B
FlexPipe · 2013.06
2.7.3.1 FlexPipes Tools for AluFlex Introduction
This section describes the tools which are used in connection with AluFlex pipes.
Hydraulic pump
Carrying case for hydraulic pump, product No. 0520 0000 008 100. Contents: 1. Hydraulic pump, complete 2. Bottle with reserve oil
1 2
Compression tool for service pipe dimensions ø 20-32 mm
Sturdy carrying case for compression tool and accessories for service pipe dimensions ø 20, ø 26 and ø 32 mm. Available in sturdy carrying case, product No. 0500 0000 002 005. Contents: 1. Compression tool 2. Exchangeable compression inserts 3. Hacksaw 4. Pipe cutter 5. Stripping knife 6. Deburring tool, internal 7. Deburring tool, external 8. Special lubricating agent
Alternative stripping tool
FlexPipe · 2013.06
3
Alu-PEX ø mm
Product No.
16-20
9000 0000 006 020
26-32
9000 0000 006 021
7
2
4 5
8
1 6
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
2.7.3.2 FlexPipes Tools for AluFlex Alternatively compression tool for service pipe dim. ø 20 - 32 mm
Complete tool set in carrying case with all necessary tools and accessories for service pipe dimensions ø 20, ø 26 and ø 32 mm. Part no. 18266.
REMS REMS
LOGSTOR Service Department sells this tool set or can refer to suppliers of it.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
2.7.4.1 FlexPipes Tools for shrink joints Introduction
This section describes the tools and accessories to use, when installing shrink joints and other shrink materials: end-caps, shrink sleeves, and shrink wrap for repairs.
Burner set for shrinking
Burner set for propane gas with 10 m hose and 50 mm burner head and union for regulator: Product No. 9000 0000 001 943. Burner set for propane gas with 10 m hose and hose union with ½” thread: Product No. 9000 0000 001 944. Also used to dry joint locations and preheat joints.
Roller
Used to compress overlap etc. on shrink joints and shrink sleeves. Component No. 9000.
Heat protection
LOGSTOR Heat Shield is wrapped around the outer casings, when shrinking joints. Product No. 9050 0150 031 000. Dimension: L x W = 120 x 15 cm
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.0.0.1 FlexPipes Handling & Installation Introduction
This section describes the most important requirements to and instructions for handling, adapting and installing the FlexPipe system.
Contents
Storage and transport Installation, general Installing press couplings Installing compression couplings
3.1 3.2 3.3 3.4
Installing casing joints: -- FXJoint 3.5 3.6 - T-joint, straight F 3.7 - SXJoint 3.8 - T-joint, straight Insulating joints with foam packs: -- Foam packs, general - Storage and handling -- Foam packs for shrink joints -- Foam pack numbers
LOGSTOR A/S · Tel. +45 99 66 10 00
3.9 3.10 3.11 3.12
FlexPipe · 2013.06
3.1.0.1 General Storage and transport Delivery takes place in accordance with the sales and delivery terms of the supplier, see www.logstor.com/District Heating/Sales & Delivery.
Storage
• Stock pipes in such a way that they are not damaged. Stack the pipes on a level surface of stoneless sand with cushions of sand as it appears from the illustration. Stack the FlexPipe coils so the maximum height is 2 m.
max. 2 m
Delivery
• Store pallets with foam liquids indoors at 16-22°. • Likewise store shrink materials indoors or under cover. • All casing joints of plastic materials must be stored vertically, resting on one end in order to avoid ovalization.
Unloading
Do not throw or roll pipes and other components directly on to the ground. They must be lifted into place and NOT dragged - neither on the truck bed nor on the ground.
Handling, FlexPipes
Only use lifting straps with a width of min. 100 mm.
100 mm
When using a truck protect the forks with casing pipe, rubber pads etc.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
3.2.0.1 FlexPipes Installation, general Installation methods
FlexPipes are installed in trenches either horizontally or vertically in accordance with the minimum trench dimensions in the illustration below.
Trench installation
This sectional view of the trench shows the minimum dimensions for: - The sand layer The pipes must be surrounded by min. 50 mm sand or other stonefree backfill material. - The distance between outer casing pipes, 50 mm - The cover H1 = In areas with heavy traffic min. 400 mm from the top of the pipe to the bottom of the asphalt or concrete layer H2 = In areas with no or only light traffic min. 300 mm ! = Warning tape or net The cross section of the trench must allow sufficient space for proper installation of pipes and casing joints and compacting of backfilling. Note! The minimum cover also applies to branching, if any, from the illustrated cross section.
Shortening
FlexPipes are delivered in coils. The required length is cut perpendicularly, using a suitable saw. The casing of the FlexPipe has a metre indication, facilitating the cutting of exact lengths. Example of marking: LOGSTOR PEXFLEX :: VARME - HEAT - HEIZUNG :: EN 15632 :: 20x20/77 MM :: MAX 95°C :: 6 BAR :: PELD :: MADE IN DK :: 198 m
FlexPipe · 2013.06
H2
H1 !
50 mm
!
!
D
50 mm D
50 mm
50 mm
50 mm D 50 mm D 50 mm
50 D 50 D 50 mm
50 D 50 mm 50 D 50 mm
LOGSTOR PEXFLEX :: VARME-HEAT-HEIZUNG :: EN 15632 :: 20x20/77 MM :: MAX 95°C :: 6 BAR :: PELD :: MADE IN DK :: 198 m
0198
0199 LOGSTOR PEXFLEX :: VARME-HEAT-HEIZUNG :: EN 15632 :: 20x20/77 MM :: MAX 95°C :: 6 BAR :: PELD :: MADE IN DK :: 199 m
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.2.0.2 FlexPipes Installation, general Unwinding
Do not cut all fixation strings at the same time. Place the coil at the start of the trench. Cut the first string. Unwind the pipe till the next string and then cut that etc.
Straightening
Adapt the FlexPipe end, so that min. 500 mm of it is straight and plane-parallel with the welded branch pipe piece or the adjoining pipe end. This adaptation is important and necessary to ensure that subsequent installation of the casing joint can be carried out according to instructions.
1 2 3
500 L
Please keep the bounce effect of the free pipe ends in mind when cutting.
Auxiliary tools
In case of major tasks and very large dimensions it is advantageous to use a waggon with motorized straightener (not obligatory). The LOGSTOR Service Department can refer to relevant suppliers of the FlexPipe-waggon. NOTE! 1. At temperatures below +5°C the outer casing must be preheated to lukewarm, immediately before it is inserted in the straightener head (soft gas flame during the entire straightening process). 2. It is recommended to store the coil in a heated room at least 24 hours before use - this does not however exclude item 1, if the coil becomes cold again.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2015.04
3.2.0.3 FlexPipes Installation, general Bending radius
The minimum radius of the curve is determined by the dimension (see table below). Do not bend the pipes over a sharp edge. Outer casing ø out. mm 77 90 110 125 140 160 180
R min.
Bending radius R min. m 0.6 0.8 1.1 1.2 1.4 1.6 1.8
The rigidity of PexFlex pipes depends on the temperature of the pipe. On installation it may be necessary to ensure the pipe position e.g. by partial backfilling. Prior to bending/installation in the pipe trench it is advantageous to preheat the casing pipe in order to reduce the stresses.
Bending Winter measures
Unrolling and straightening do not normally require preheating, only common caution. Preheating is however recommended, if the material (FlexPipe) has a temperature below 5°C, see page 3.2.0.2 “Auxiliary tools”. Ordinarily bending of the outer casing at temperatures below 5°C, requires preheating of the section which is influenced by the bending to lukewarm, The preheating rule also applies to tilted bores in the base or inlet pipes. Bend the pipe slowly and smoothly, not jerkily. Avoid to bend the utmost 25-30 cm of the pipe because of the bounce effect.
FlexPipe · 2015.04
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.3.1.1 FlexPipes Installing press couplings, type JT Preskoblinger, PexFlex(tra) and SaniFlextra
The service pipe of PexFlex(tra) and SaniFlextra are joined by means of press couplings, ensuring a permanent tightness of all joints made at all temperature viariations.
2
1
1. Coupling nipple 2. Compression ring Note! For PexFlex(tra) and SaniFlextra compression couplings can be used as an alternative. For AluFlex(tra) press couplings, type MP, are used. LOGSTOR recommends press couplings for Flex(tra) systems in the ground.
Tools
Press couplings are installed by means of compressing tools, which typically are activated mechanically or electrohydraulically. Prior to installation of the coupling nipple the service pipe must be expanded by means of an expander pliers. Typical tools for compression of press couplings, type JT are: 1. Compression tool, incl. inserts* 2. Expander pliers, incl. expanders* 3. Saw 4. Plastic pipe cutter for ≤ ø 32 mm Product No. 9000 0000 005 002 Plastic pipe cutter for ≤ ø 63 mm Product No. 9000 0000 005 003 5. Pipe cutter > ø 63 mm 6. Stripping tool See p. 2.7.2.1 for product Nos. 7. Deburring tool Product No. 9050 0000 043 001
1
4
2
5
6
3
7
* Not supplied by LOGSTOR
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2016.06
3.3.1.2 FlexPipes Installing press couplings, type JT Foam removal
Remove L + 30 mm of the insulation from the FlexPipe end, using the stripping tool. The 30 mm is a general addition, ensuring that the service pipe end can be shortened in a clean and perpendicular cut to the L length. The L length appears from below table.
L + 30
After shortening check that the pipe end is not damaged.
L
L-measurements
30
Service pipe, ø mm
L mm
Straight and reducing*
16-110
140
90°
16-110
140
With transition to thread and weld end
16-110
200
Main pipe
16-110
140
Branch
16-110
200
Coupling types
T-coupling:
* In case of more than 1 dimensional offset on the service ppe, two successive casing joints (FXJoint) must be installed. This is not necessary, when using SXJoint.
Preparing pipe ends
Deburr the inside and outside of the perpendicularly cut service pipe end, using the deburring tool. Remove foam remnants on the service pipe with emery cloth, grain size 150. If closed shrink joints/collars are used, install them on the pipe end.
FlexPipe · 2016.06
L
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.3.1.3 FlexPipes Installing press couplings, type JT Expanding the pipe end
Push the compression ring on to one of the pipe ends. Place the compression ring minimum 2 x compression ring length from the pipe end.
Expand the pipe ends with the expander pliers as described in the user instructions of the tool supplier. Note! The pipe end is typically expanded twice in a row, rotating the expander pliers 30°.
Immediately after using the expander pliers the coupling nipple is inserted as far as possible into the pipe. Check that all the ribs of the coupling nipple as a minimum are covered by the pipe. If this is not the case, repeat the expansion process. Before compressing the coupling check again that none of the ribs of the coupling nipple pipe end are visible.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2016.06
3.3.1.4 FlexPipes Installing press couplings, type JT Preparing compression tool
Place the compression tool so the jaws presses against the nipple flange and the compression ring as described in the user instructions from the tool supplier. Check that the tool is correctly placed, before compressing.
Compressing the coupling
Activate the compressing tool, until the compression ring is flush with the nipple flange. Avoid excessive compression. Make sure the compression is even around the flanges of the coupling (perpendicular to the pipe).
Compressing the 2nd pipe end
The other pipe end is prepared and compressed according to the same guidelines and method.
Check
Ensure that the compression ring on the finished joint is flush with the nipple flange and that the joint is evenly compressed all around. (A minimal gap may occur). Note! A press coupling cannot be disassembled after installation is complete.
Weld coupling and transition to thread
FlexPipe · 2016.06
On transition from steel to PexFlex(tra) the coupling must first be installed on the steel part. The compression part of the coupling is then installted after the instructions in the precedings.
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.3.2.1 FlexPipes Installing press couplings, type MP Press couplings PexFlex(tra) og AluFlex(tra)
The service pipe of PexFlex(tra) and AluFlex(tra) are joined by means of press couplings, ensuring a permanent tightness of all joints made at all temperature variations.
2
3
1
1. Coupling nipple 2. Compression ring 3. Squeezing ring
5
4
AluFlex(tra) only: 4. O-ring 5. Insulating ring
Note! For the domestic water system SaniFlextra press couplings, type JT, are used or alternatively, 10 bar compression couplings. LOGSTOR recommends the use of press couplings in buried Flex(tra) systems.
Tools
Press couplings are installed with compression tools which are typically hydraulically activated. All tools can be rented from LOGSTOR Service department. Typical tools for press couplings, type MP, are: PexFlex(tra): Service pipe dimensions ø 16, ø 20, ø 22, ø 25, ø 28, ø 32, ø 40, ø 50 and 63 mm. 1. 2. 3. 4. 5.
Compression tool Exchangeable compression inserts Hydraulic pump Saw Plastic pipe cutter for ≤ ø 32 mm Product No. 9000 0000 005 002 Plastic pipe cutter ≤ ø 63 mm Product No. 9000 0000 005 003 6. Pipe cutter for > ø 63 mm 7. Stripping tool See p. 2.7.2.1 for product Nos 8. Deburring tool Product No. 9050 0000 043 001
2
1 3
4 6
5
7 8
For PexFlex(tra) service pipe dimensions ø 75, ø 90 and ø 110 mm a special tool set with a compression tool which is universal for all three dimensions is available. Contact LOGSTOR Service department for further information.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2016.06
3.3.2.2 FlexPipes Installing press couplings, type MP Tools continued
AluFlex(tra): Service pipe dimensions ø 16, ø 20, ø 26, and ø 32 mm. 1. Compression tool 2. Exchangeable compression inserts 3. Hydraulic pump 4. Hacksaw 5. Stripping tool See p. 2.7.2.1 for product Nos. 6. Deburring tool, internal Product No. 9050 0000 043 001 7. Deburring tool, external
FlexPipe · 2016.06
2
1 3 4
5
7 6
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.3.2.3 FlexPipes Installing press couplings, type MP Foam removal
Remove L + 30 mm of the insulation from the FlexPipe end. The 30 mm is a general addition, ensuring that the service pipe end can be shortened in a clean and perpendicular cut to the L length. The L length appears from below table.
L + 30
Cut the pipe perpendicularly, using: a. PexFlex(tra) plastic cutter b. AluFlex(tra) hacksaw
a
b
After shortening check that the pipe end is not damaged. Place shrink joint and collar on one of the pipe ends.
L-measurements
Preparing pipe ends
L
30
Service pipe, ø mm
L mm
16-40
90
50
105
63-110
125
Deburr the inside and outside of the perpendicularly cut service pipe end, using the deburring tool. Remove foam remnants on the service pipe with emery cloth, grain size 150. If closed shrink joints/collars are used, place them on the pipe end.
LOGSTOR A/S · Tel. +45 99 66 10 00
L
FlexPipe · 2016.06
3.3.2.4 FlexPipes Installing press couplings, type MP Preparing first pipe end
Push the compression ring and the squeezing ring on to one of the pipe ends.
Thrust the nipple into the pipe, until the pipe end is flush with the nipple flange. Use a rubber hammer, if necessary.
1
AluFlex(tra) only: Make sure that the insulating ring (1) and the O-ring (2) are placed correctly.
Preparing second pipe end
2
Push the compression ring and the squeezing ring on to the other pipe end.
Push the other pipe end on to the coupling nipple, so it is flush with the nipple flange.
1
AluFlex only: Make sure that the insulating ring (1) and the O-ring (2) are placed correctly.
2
FlexPipe · 2016.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.3.2.5 FlexPipes Installing press couplings, type MP Preparing compression tool
General: Follow the instructions in the tool box. Fit compression inserts, corresponding to the service pipe dimension, on to the compression tool.
Place the pipe joint in the compression tool. Prior to compression make sure that the joint is placed correctly.
Connecting hydraulic pump
General: Follow the instructions in the tool box. Connect the hydraulic pump to the compression tool.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2016.06
3.3.2.6 FlexPipes Installing press couplings, type MP Compressing coupling
Activate the compression tool, until the compression ring is flush with the nipple flange. Avoid excessive compression.
Compress the other end of the coupling by following the same directions and method.
Check
Ensure that both compression rings on the finished joint are compressed, so they are flush with the nipple flanges. (A minimal gap may occur).
FlexPipe · 2016.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.4.1.1 FlexPipes Installing compression couplings ø 16-32 mm Compression couplings ø 16-32 mm PexFlex(tra) and SaniFlextra
The service pipes of PexFlex(tra) and SaniFlextra can be joined by means of compression couplings, cf. local regulations. 1. Clutch casing 2. Supporting bush 3. Squeeze ring 4. Union nut
1
2
3
4
Please note! LOGSTOR recommends press coupling for systems in the ground.
Preparing pipe ends
emove 75 mm insulation from the FlexPipe R end with a stripping tool.
75 mm
ut the PEX pipe at right angles, using a pair C of PEX scissors or a pipe cutter. Free end: 45 mm. Remove any external burrs and foam remnants. If closed shrink joints/collars are used, install them on the pipe end.
Installing coupling
45 mm
Disassemble the coupling: Place the union nut and the squeeze ring on the pipe. Push the supporting bush into the pipe to full stop. Use a rubber hammer, if necessary. The pipe end must be in the dish-shaped part.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2016.06
3.4.1.2 FlexPipes Installing compression couplings ø 16-32 mm Installing coupling, continued
ush the supporting bush into the body of P the coupling - to the bottom. Tighten the union nut hard. The body must not turn. By correct installation of the union nut the squeeze ring must be visible between the union nut and the PEX pipe. Use a ring spanner or an adjustable spanner, NOT a PIPE WRENCH. If the union nut can be tightened to its bottom, the coupling must be dismantled. Then shorten the PEX pipe at least 100 mm and install a new coupling.
FlexPipe · 2016.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.4.2.1 FlexPipes Installing compression couplings ø 40-110 mm Compression couplings ø 40-110 mm PexFlex(tra) and SaniFlextra
The service pipes of PexFlex(tra) and SaniFlextra can be joined by means of compression couplings, cf. local regulations. 1. Clutch casing 2. Supporting bush 3. Clamp 4. Allen screw
4 1
2
3
Please note! LOGSTOR recommends press couplings for systems in the ground.
Preparing pipe ends
emove 110 mm insulation from the FlexPipe R end with a stripping tool.
110 mm
ut the PEX pipe at right angles, using a pair C of PEX scissors or a pipe cutter. Free end: 80 mm. Remove any external burrs and foam remnants. If closed shrink joint/collars are used, place them onto the pipe end.
Installing coupling
80 mm
Disassemble the coupling: Push the supporting bush into the pipe, using a drift and a hammer The PEX end must reach the lock ring of the union nut.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2016.06
3.4.2.2 FlexPipes Installing compression couplings ø 40-110 mm Installing coupling, continued
Install the two clamps so the union nut flange fits the track in the clamps.
Tighten the two clamps with the screws. Allen wrench, width = 6 for dimension 40 mm and width = 10 for dimensions 50 and 63 mm. Tighten the screws so that there is no gap between the two clamps. Check that the union nut can be turned.
Install the union nut to the body. Use a ring spanner or an adjustable spanner, NOT a PIPE WRENCH.
FlexPipe · 2016.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.5.0.1 FlexPipes Installing FXJoints Application
FXJoints are used to join FlexPipes with outer casing dimensions ø 77-200 mm. 1. Insulation shells with flexible core for couplings 2. Shrink sleeve with integrated mastic 3. Cleaning tissue
2 1 3
Tools
Use the following tools when installing FXJoints: Type: Application: 1. Saw Adjusting insulation shells 2. Alcohol, min. 94% Cleaning the surface Surface activation 3. Emery cloth, grain size 80 4. Gas burner, Surface activation, Shrinking sleeve ø 50 mm 5. Heat shield Heat protecing the outer casing
Removing insulation from pipe ends
Preinstalling casing joint
1
2
3
5
4
1. Coupling Cut off the insulation with a suitable stripping tool. L depends on the type of coupling: - press couplings, see page 3.3.0.3 - compression couplings, see pages 3.4.0.1 and 3.4.0.3 Install the coupling as shown in the relevant instructions.
L
2. Place the shrink sleeve with packing on one of the pipes, before the service pipes are joined by means of a press or compression coupling. The total free pipe length must not exceed 300 mm regardless of the couplings length. m
0m
44
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
3.5.0.2 FlexPipes Installing FXJoints Cleaning
3. A ll surfaces in the mounting area must be CLEAN and DRY. Clean the outer casing at least 150 mm from both casing ends with alcohol.
Adjusting insulation shells
4. Shorten the insulation shells to size, so that they fit tightly between the casing pipes. As for couplings, it is normally not necessary to cut away insulation foam to make room for the coupling, when insulation shells with flexible core are used.
5. Fit the insulation shells tightly between the casing pipes, using adhesive tape if necessary. All surfaces must be CLEAN and DRY at least 150 mm from both casing ends. Reduction: See at the end of this instruction.
Activation
6. Activate the casing pipe with emery cloth grain size 80 at least 150 mm from both casing ends.
0
15
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.5.0.3 FlexPipes Installing FXJoints Activation, continued
7. Activate the casing pipes with a soft gas flame at least 150 mm from both casing ends, until the surface has a matt, silky look. Surface temperature: Approx. 65°C.
Installing shrink sleeve
8. Remove the packing from the shrink sleeve. Check that the sleeve is CLEAN and DRY inside and out and that the internal mastic has not been damaged. Centre the shrink sleeve over the joint.
Shrinkage
9. First, shrink from the middle towards one end, then from the middle towards the other end. Hold the burner head at an angle of approx. 30° against the sleeve to avoid unintended heating of the casings. NB! Avoid heating directly on the casing.
If necessary, use a LOGSTOR heat shield as illustrated. 10. The joint is complete.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
3.5.0.4 FlexPipes Installing FXJoints, reduction Reduction
When applied as a reduction, the sleeve may shrink up to 2 dimensions more than the minimum diameter listed. (Example: FX dimension 125-200 mm is able to shrink to dimension 90 mm). Max. covering length is 300 mm. 11. 1 offset. Use an insulation shell, which fits the largest pipe end. Bevel the insulation shell so that the insulation obtains a plane shape, see figure. D1
77
90
110
125
D2
90
110
125
140
160
77-125
77-125
125-200
125-200
125-200
Joint
140
12. 2-3 offsets. Use 2 different insulation shells, which fit the pipe ends in question. Bevel the inside of the smaller insulation shell, so that it is placed planely against the reduction and the service pipe. Bevel the outside of the larger insulation shell to obtain a plane shape of the insulation, see figure. Fasten the insulation shells with canvas tape. D1 D2 Joint
FlexPipe · 2013.06
77
max. 300 mm
90
110
110
125-140
140-160
77-125
125-200
125-200
max. 300 mm
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.6.0.1 FlexPipes T-joint straight F Application
Straight T-joints are used to branch with FlexPipes from outer casing dimensions ø 77-180 mm, using couplings.
6 5 4
Max. branch dimension: ø 160 mm. 1. Closure patch 2. Shrink wrap 3. Insulation shells with marking for branch 4. T-shoe 5. Insulation shells 6. Collar 7. Cleaning tissue
Tools
Use the following tools to install T-joint straight F: Type Application 1. Saw Adjusting insulation shells 2. Alcohol, min. 94% Cleaning the surface 3. Emery cloth, Surface activation grain size 80 4. Gas burner, Surface activation ø 50 mm Shrinking T-shoe, clo- sure patch, wrap and collar 5. Roller Securing mastic in overlap
Removing insulation from pipe ends
1. Cut off the insulation with suitable stripping tool. L depends on the type of coupling: - press couplings, see page 3.3.0.3 - compression couplings, see pages 3.4.0.1 and 3.4.0.3
Preinstalling joint parts
2. Place the collar, wrap and T-shoe on the branch pipe. Install the coupling according to the rele vant instructions. The total free pipe length must not exceed 300 mm regardless of couplings.
LOGSTOR A/S · Tel. +45 99 66 10 00
1
2
3
7
1
2
4
3
5
L
m
0m
30
FlexPipe · 2013.06
3.6.0.2 FlexPipes T-joint straight F Cleaning
3. Clean all surfaces in the mounting area. Clean min. 200 mm of the 3 outer casing ends with alcohol.
Adjusting insulation shells
4. S horten the insulation shells to make them fit tightly between the casing pipes. It can be necessary to remove insulation foam around the coupling. Use the marking for the position of the branch, when removing insulation for the branch pipe.
5. Fit the insulation shells tightly between the casing pipes, using adhesive tape if required. All surfaces must be CLEAN and DRY.
Preinstalling T-shoe
FlexPipe · 2013.06
6. H eat the T-shoe to 50-60°C. Pull the T-shoe over the main pipe and fasten it with tape.
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.6.0.3 FlexPipes T-joint straight F Activation
7. Activate the outer casings with emery cloth, grain size 80, at least 150 mm from the casing ends. m
0m
15
8. Activate the casing pipes with a soft gas flame at least 150 mm from the casing ends, until the surface has a matt, silky look. Surface temperature: Approx. 65°C.
Installing shrink wrap
9. Remove the paper, while pulling the wrap into position. Turn the wrap so that the text goes around the pipe and closes at the top.
10. Centre the closure patch on the wrap joint with the hotmelt facing down. The side with the hotmelt has visible reinforcement. Heat the closure patch until the structure of reinforcement becomes visible on the topside. Press down the closure patch.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
3.6.0.4 FlexPipes T-joint straight F Installing shrink wrap, continued
11. Shrink the wrap from the centre towards both ends ensuring that the mastic becomes visible at both ends and the full shrinking effect has been utilised. NB! Avoid heating directly on the casing.
oll along the overlapping edge, ensuring 12. R that any tunnel at the edge is sealed with mastic.
Shrinking and activating branch
13. S hrink the outermost 200 mm on the branch of the T-shoe. Activate the casing 150 mm onto the branch. Surface temperature: Approx. 65°C. 20
0 15
0
Shrinking collar
14. R emove the packing and paper from the collar. Check that the paper has been removed. Shrink while centering the collar on the end of the T-shoe. NB! Avoid heating directly on the casing. 15. The joint is complete.
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.7.0.1 Installing straight joints SXJoints Application
SXJoints are used for joints on FlexPipes with outer casing dimensions ø 90-200 mm. They are primarily used in connection with flexible TwinPipes.
2
1
1. Shrink sleeve with plugs and patches 2. Collars (to be ordered separately)
Tools
Use the following tools when installing SXJoints: Type: Application: 1. 2. 3.
Emery cloth, Surface activation grain size 80 Alcohol, min. 94% Cleaning the surface Gas burner, Surface activation ø 50 mm Shrinking joint Heating patch 4. Leakage test Leakage test equipment prior to foaming 5. Hammer Installing wedge plugs 6. Foam pads Insulating joint 7. Screw driver Dismounting venting plugs 8. Patch-spoon Heating and placing patch 9. Patch-press Securing patch 10. Heat shield Heat protecting the outer casing
Preinstallation of casing joint
1
6
2
4
3
7
5
8 10
9
1. Place the shrink sleeve with packing on one of the pipes before the service pipes are joined by means of a press or compression coupling. The total free pipe length must not exceed 440 mm regardless of the coupling length. m
0m
44
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
3.7.0.2 Installing straight joints SXJoints Cleaning
2. Clean all surfaces in the mounting area. Use alcohol on at least 150 mm of the two casing ends.
Activation
3. A ctivate the casing pipes with emery cloth, grain size 80, at least 150 mm from both casing ends. 0
15
4. A ctivate the casing pipes with a soft gas flame at least 150 mm from both casing ends, until the surface has a matt, silky look. Surface temperature: Approx. 65°C. 0
15
Positioning shrink sleeve
5. Remove the packing from the shrink sleeve, but leave the packing on the pipe as it may be useful later. 6. D o not use cutting tools with sharp edges. Make sure that the sleeve is CLEAN and DRY inside and out. 7 Centre the sleeve on the joint. Remove the mastic covering. Make sure that all the foil has been removed.
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.7.0.3 Installing straight joints SXJoints Shrinkage
8. Shrink the ends of the sleeve. NB! Avoid heating directly on the casing. Use a heat shield for heat protection of the casing. Shrink the sleeve starting at the top to ensure centering. Hold the flame perpendicular to the joint. 9. Shrink until all expansion marks have vanished and the end of the sleeve forms an almost straight encircling edge. 10. Shrink the collars over the casing joint end and the outer casing. Follow previous instructions.
Leakage test
11. Wait until the sleeve has cooled off. Leakage test at 0.2 bar.
Venting and foaming
Test the ends with a soap solution.
0,2 bar
12. Install a venting plug in one of the holes and foam the sleeve through the other hole. Install the other venting plug. 13. Wait min. 30 min. for degassing to complete. Remove the venting plugs by turning and lifting them. Remove excess foam or spillage, if any.
30 min.
2
1
14. Activate the whole surface of the recessed area around the holes with emery cloth, grain size 80, and clean the area with alcohol.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
3.7.0.4 Installing straight joints SXJoints Expansion plugs
15. Remove the protective foil from the expansion plugs and check the mastic.
1
2
16. Activate briefly the recessed area with a hard flame. 1-2 sec.
17. Mount the expansion plugs in the holes and press until the mastic is spread smoothly under the collar of the plug.
Wedge plugs
18. Centre the wedge plugs in the leading edge of the expansion plugs and drive them completely into the plugs with a hammer.
Patch installation
19. Activate the area where the patch must be placed by grinding it with emery cloth, grain size 80, and remove grind dust, if any and clean with alcohol. 20. Place the patch on a patch-spoon, the hotmelt side facing up. Heat the hotmelt side, until the mastic begins to bubble.
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.7.0.5 Installing straight joints SXJoints Patch installation, continued
21. A ctivate briefly, 1-2 sec., the recessed area with a hard flame. Place the patch over the plug in the recessed area, the hotmelt side facing down. 22. P ress it at once hard with the patchpress for approx. 20 sec. The patch must fit tightly to the joint in the recessed area. If the patch does not fit tightly or the colored spots, if any, of the patch do not turn black, it must be heated again for a short while with a hard flame and pressed with the patch-press for approx. 10 sec. Repeat the process at the other patch.
20 sec.
The joint is complete. NOTE! Do not touch the patch, before it has cooled.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
3.8.0.1 TwinPipes T-joint straight Application
T-joints straight are used to branch from TwinPipes to TwinPipes, primarily FlexPipes. TwinPipe outer casing: ø 90-200 mm. 1. Closure patch 2. Shrink wrap 3. T-shoe 4. Collar 5. Venting, expansion and wedge plugs
4
3
2 1
5
Use extra closure patches, filament tape or straps for the T-shoe.
Tools
Use the following tools when installing T-joint straight: Type: Application: 1 1. Emery cloth, Surface activation grain size 80 2. Alcohol, min. 94% Cleaning the surface 3. Gas burner, Surface activation ø 50 mm Shrinking T-shoe, 5 shrink wrap, closure patch and collars 4. Drill Venting and filling holes 5. Hammer Installing wedge plugs 6. Roller Securing mastic overlap
Removing insulation from pipe ends
1. C ut off the insulation with a suitable stripping tool. L depends on the type of coupling, press or compression coupling
Preinstalling shrink wrap and T-shoe
2. Cut the T-shoe open in the middle of the bevelled area.
FlexPipe · 2013.06
3
2 4
6
L
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.8.0.2 TwinPipes T-joint straight Preinstalling shrink wrap and T-shoe, continued
3. Place the collar, wrap and T-shoe on the branch pipe.
Connecting service pipes
4. Join the main pipes with the couplings according to the relevant instructions.
m
0m
44
440 mm
5. Mount the branch pipes in the couplings on the main pipes.
250 mm
6. The total free pipe length must not exceed 440 and 250 mm, respectively, regardless of coupling lengths.
Cleaning
7. Clean all surfaces in the mounting area. Use alcohol to clean at least 150 mm of the casing pipe ends.
Installing T-shoe
8. Pull the T-shoe over the main pipes. Fasten the T- shoe tightly around the pipe with tape, max 60 mm from the edge. m
0m
.6 ax
M
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
3.8.0.3 TwinPipes T-joint straight Shrinking branch Drilling holes
9. Shrink the outer 200 mm of the branch pipe. 10. D rill a hole ø25 mm in the branch pipe.
20
0
Venting and foaming
11. Foam the T-shoe and install a venting plug in the hole. Wait min. 30 min. for degassing. Remove the venting plug by turning and lifting it. Remove excess foam, if any. Activate the area around the hole with emery cloth, grain size 80.
Expansion plug
12. Remove the protective foil from the expansion plug and check the mastic. 13. Activate briefly the area around the hole with a hard flame.
1 1-2 sec.
2
14. Mount the expansion plug in the hole and press until the mastic is spread smoothly under the collar of the plug.
FlexPipe · 2013.06
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.8.0.4 TwinPipes T-joint straight Wedge plug
15. Centre the wedge plug in the expansion plug and drive it completely into the plug with a hammer.
Activation, main pipe
16. Activate the casing on the main pipe with emery cloth grain size 80 at least 150 mm from both pipe ends.
m
0m
15
17. Activate the casing on the main pipe with gas burner at least 150 mm from both pipe ends, until the surface has a matt, silky look. Surface temperature: Approx. 65°C. m
0m
15
Installing shrink wrap
18. Place the shrink wrap around the main pipe. Remove the protective paper as the wrap is pulled into place. Make sure that the text on the wrap goes around the pipe and that the wrap is joined on the upper side.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
3.8.0.5 TwinPipes T-joint straight Installing shrink wrap, continued
19. Centre the closure patch over the ends of the shrink wrap with the glue side facing down. The glue side has a visible net. Heat closure patch with a strong flame, until the net structure is faintly visible on the upper side. Press the closure patch in place.
20. Shrink the wrap from the centre towards both ends ensuring that the mastic becomes visible at both ends and the full shrinking effect has been utilised.
21. Roll along the overlapping edge, ensuring that any tunnel at the edge is sealed with mastic.
Activation, branch
22. Activate the branch pipe and casing with emery cloth grain 80 starting at least 150 mm from both pipe ends.
150
FlexPipe · 2013.06
mm
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.8.0.6 TwinPipes T-joint straight Activation, branch, continued
23. Activate the shoe and the casing with the gas burner starting at least 150 mm from the end of the branch pipe. Surface temperature: Approx. 65°C.
150
Shrinking the collar
mm
24. Remove wrapping and paper from the collar. Check that all paper is removed. Shrink the collar so that it is centred over the end of the shoe.
25. The joint is complete.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
3.9.0.1 Insulating joints General and foam packs Application
There are two ways of insulating joints on FlexPipes: -- F XJoints and T-joints straight F for single pipes are insulated with insulation shells, see the relevant installation instructions. -- SXJoints and T-joints straight for TwinPipes are insulated with foam packs as described in this section.
Foam packs
It is an easy-to-apply method according to which a two-component foam liquid, after mixing and filling, forms an effective insulation with the same properties as in the rest of the pipe system. Foam packs which are stored in accordance with stated rules have a time limit for use of 12 months counting from the stated production week. Foam packs comply with the requirements to materials in EN 253. Foam packs are supplied in insulation boxes with information about contents and storage.
8113 2x13 23.96
5
Cartons
The cartons in the insulation box contain predosed packings with a number corresponding to the table in this section and the foam pack folder in the box. The key is the information on the label on the casing joint. Each carton is marked with installation instructions, information about contents and storage as well as safety data.
FlexPipe · 2013.06
SX
5 5 00 0000 0700
815
4809
SX m 02 51 60 m ø1
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.9.0.2 Insulating joints General and foam packs The multi-ply plastic bag
The carton contains a multi-ply plastic bag, divided into two sections which are separated by a clip bairrier. The brown liquid (A) (isocyanate) is in a completely diffusion-tight section, in which aluminium foil forms part of the construction of the bag.
B A
The clear liquid (B) (polyole) is in a trans parent section which makes it possible visually to control that the mixing of the liquids has been carried out correctly. Also see the safety instructions on the carton.
Safety regulations
Note! Each country poses its specific requirements to education/training and use of personal protective equipment for working with polyurethane foam. The customer or his representative is responsible for the compliance with these requirements.
Material safety data sheet
It is a requirement in all EU countries that material safety data sheets are issued when using hazard classified products. Consequently, a material safety data sheet is an integrated part of the product “foam pack”. It must always be at the user's disposal and may follow material deliveries or be forwarded separately by mail, fax and via data network. The material safety data sheet contains 16 items of information
SAFETY DATA SHEET SAFETY DATA SHEET
Product name FOAM PACK Version no.: 1 Created: 10-01-2008 Date of revision: 10-01-2008 Product name FOAM PACK Version no.: 1 Created: 10-01-2008 Date of revision: 10-01-2008
Page 2/5
name FOAM PACK Version no.: Page 5/5 Wear Product self-contained breathing apparatus and1full protective gear when extinguishing fire. Isocyanate (component A) Polyol (component B) Created: 10-01-2008 Date of printing: 10-01-2008 Product Name: FOAM PACK Date of revision: 10-01-2008 Accumulation: General information: Form: Liquid Liquid Known. If it is Not without risk containers should be removed from the area where there is a riskEmergency of fire. telephone number : Supplier: Uses and Restrictions: Colour: Brown Clear, yellowing LOGSTOR A/S information: Dial 999 in case of a emergency, or General Individuals wit more susceptibility to dermatitis should not be selected to work isocyanates. 6. Odour: ACCIDENTAL RELEASE MEASURES: Prevent material from entering drains,the streams, lakes etc. NHS DirectWeak for advice 0845 4647 (GB). Not to be handled by persons under age ofWeak 18 years. Danmarksvej 11 Personal precautions: Both services available 24 hours. Density: 1,23 g/cm³ 1,04are g/cm³ DK-9670 DISPOSAL Loegstoer Special Education: CONSIDERATIONS: all ignition sources and ensure sufficient -ventilation. Avoid inhalation of vapours/aerosols and with skin and 13.Remove Explosion limits: 1,1-8,7 %contact (Cyclo pentane) Telephone no.:user of0045 99 66 10 the product must be thoroughly instructed in working with the product,- the eyes. The Unauthorized persons are00forbidden to enter. Regarding personal protection seedangerous section 8. properties of the product and the necessary safety Disposal considerations: Responsible for the Saftymeasurements. Data Sheet Boiling point: > 48°C (Cyclo pentane) Environmental Delivered toprecautions: disposable centre according to the local regulations. E- mail:
[email protected] Flash point: > 200°C 8°C Prevent material from entering drains, streams, lakes etc. 16. Waste code: 02 13 waste plastic OTHER INFORMATION: Melting point 07 < 0°C 400°C 380° C disposable (Cyclo pentane) R phrases: (section The container should not be closed caused by the developing of CO2 from the waste. The container should be General information: R11 Highly flammable. Insulation for13). district heating joints Vapour pressure 1 hPa (20°C) 345 hPa (20°C) (Cyclo underEAK observation. Keep itbe in use the open container outside. Thewaste total from time tiding of reaction: 7-14 days. Dispose according to pentane) section 07 02 13 should it is in a mixture or the up in section 6. R20 Harmful bywhen inhalation. Viscosity: 200 mPa (20°C) 690 mPa (23°C) Harmful to aquatic organisms. 13. R52 2. HAZARDS IDENTIFICATION: R53 May cause long-term adverse effects in the aquatic environment. TRANSPORT INFORMATION: 14. Water solubility: No No Toxicological Ecological R36/37/38 Irritating to hazards: eyes, respiratory system and skin. 7. Main HANDLING ANDand STORAGE: no.to eyes, R42/43 cause byUN inhalation and skin contact.system and skin. 1866 Isocyanate (component A): May Harmful bysensitisation inhalation. Irritating respiratory May cause sensitisation by ADR/RID Handling: inhalation and skin contact. Class: 10. 3 STABILITY AND REACTIVITY: Final remarks: Avoid inhalation of Highly and contact with product. Eating, drinking,group: smoking or storage of food, drinks and tobacco must not take Polyol (component B): flammable. Packaging II afterwith safety data is compiled on theofbasis of information the before supplierany andbreaks in accordance EU legislation. The users place This where there is asheet risk of contamination the product. Washfrom hands and working hours. Ensure Stability: Hazard Identification: 33 the working conditions is outside our knowledge and control, draw to your attention that to it'sprevent always users responsibility to take the adequate ventilation. Local mechanical exhaustion could be we necessary. Take measures static electricity. Ensure 3. COMPOSITION/INFORMATION ON INGREDIENTS: Isocyanate (component A): Polymerisation occurs by 200°C. The polymerisation will develop CO2. precautions and follow the given legislation. Proper Shipping Name: accessnecessary in the(component working area "rinse the eye" facility. to ample water,toshower changing-room. RESINand SOLUTION Polyol B): to The product is s table if it isEnsure handledaccess and stored according section facility 7. Isocyanate (component A) CAS no: Refer 9016-879 UN no. Personal protective equipment: to section 8. 1866 IMDG-CODE References: Polyol (Component B)to contains CAS no: 287-92-3 Class: Conditions avoid: 3 Storage: CHIP3: Chemicals (Hazard Information and Packaging for Supply), Regulations 2002 (SI 2002/1689) and accompanying Temperature above 40°C. Occupational Exposure Packaging group: Limits.foodstuffs, COSHH : medicaments The Control of or Substances Hazardous to Health Regulations 2992 II Stored Contains: Store documentation. securely, awayEH40/2005 from children, away from food, animal the like. in temperatures and10 subsequent amendments. EC Chemical Regulation no.ignition 1907/2006. REACH. and 40°C. Keep away from sources, oxidizing agents and strong CASbetween number: %: the product Name: Classification: Note:substances. EmS: F-E,acidic S-E and basic EC-no.: Substances to avoid: 10/03 C650 of (Working with liquids 2-pack isocyanate paints). Proper Shipping Name: FollowHSE the INDG388 HSG51 "The storage flammable in containers." acids. Bases. Alcohols. Amines. Isocyanate (component A): Isocyanates reactsSOLUTION strongly with water under a diphenylmethane-4,4'-diR20, RESIN R36/37/38, 9016-87-9Oxidizing agents and100% Xn, Xi no. heatingup development. 1866 IATA isocyanate,UN isomers and R42/43 Drawn by: pbb trotters aps homologueClass: 3 QA ah 01-2008 Hazardous Decomposition Products: 8. EXPOSURE CONTROLS/PERSONAL PROTECTION: Packaging group: Updated by: pbb 287-92-3 When 206-016-6 cyclo F liberate toxic gases/vapours R11, IIR52, R53 10% heated to high 480 min.warm Follow theblankets glove patient breathing. the of unconscious lay person recovery position and keep the IsocyanateIf(component A): Mayperson irritateisrespiratory tract and mayincause coughing, breathing with and difficulty inorbreathing. Contains: Isocyanate (component A):asthmatic Diphenylmethane-4,4´-diisocyanate, isomers and onmay userespiration. and replacement. like.manufacturer's If breathing hasrecommendations stopped,B):apply artificial Seekhomologue medical attention. Polyol (component Vapours cause bluntness and dizziness. Polyol (component B): Polyol with contains of cyclopentane Eye protection: Contact with eyes: Contact with skin: face shield. Use protective goggles Open your eye wide. Make or sure to remove any contact lenses. Immediately flush eyes with water for at least 10 minutes. Seek Irritating to skin. Labelling: Isocyanat (component A): Diphenylmethane-4,4´-diisocyanate, isomers and homologue medical Skinattention. Protection: Contact with skin: Contact with eyes: Harmful by inhalation. Xn Use special working clothes.R20 Irritating to eyes. R36/37/38 and wash skin thoroughly Irritating towith eyes, respiratory system and skin. Remove contaminated clothes immediately, soap and water. Always end cleansing with General information: R42/43 May cause sensitisation by inhalation and skin contact. applying moisturising cream to degreased skin. Obtain medical attention if irritation continues. Ingestion: vapour/spray. The employer has a duty to S23 ensure that pregnant women Do arenot notbreathe exposed to any influences, which may be a risqué to the Ingestion:Ingestion may cause nausea and queasy. unborn child. Rinse mouth with water. Drink afterwards plenty of water. Seek medical attention. S45 In case of accident or if you feel unwell, seek medical advice immediately (show Occupational Exposure Limits: Chronic effects: the label where possible). Burns: Isocyanate (component cause sensitisation by inhalation and skin contact. exposure limits. Harmful The(component general exposure limits ofA): allMay isocyanates are pain 0,02ceases. mg/m³. EH40/2005 Workplace Polyol B): Flush with plenty of until Whilst flushing with water, remove all loose clothing Polyol (component B) Inhalation ofwater vapours may cause drowsiness, dizziness and can cause damage to the central from nervous system by S36/37 Wear suitable protective clothing and gloves. area of burns. If medical treatment is necessary, continue flushing until medical trained staff takes over treatment. prolounged exposure. 5.
LOGSTOR A/S · Tel. +45 99 66 10 00
Page 1/5 Date of printing: 10-01-2008
Date of printing: 10-01-2008 SAFETY DATA SHEET Product name FOAM PACK Version no.: 1 Page 3/5 SAFETY DATA SHEET Created: 10-01-2008 Date of revision: 10-01-2008 Date of printing: 10-01-2008 FOAM PACK en Page 4/5 Product name FOAM PACK Version no.: 1 SAFETY DATA SHEET 9. Special protective equipment: Created: 10-01-2008 Date of revision: 10-01-2008 Date of printing: 10-01-2008 1. PHYSICAL AND CHEMICAL PROPERTIES: IDENTIFICATION OF THE SUBSTANCE/PREPARATION AND OF THE COMPANY/UNDERTAKING:
F Polyol (component B): 12. FIGHTING FIREMEASURES: ECOLOGICAL INFORMATION: R11
Highly flammable. Suitable extinguishing media: Eco toxicity: S9 Keep container in a well-ventilated place. Fire is extinguished with water fog, foam, powder or carbon dioxide. None known. S16 Keep away from sources of ignition - No smoking. Extinguishing media that must not be used: S33 Take precautionary measures against static discharges. Do not useMobility: full jet of water. The fire will spread. Isocyanate (componenet A), Polyol (componenet B) and the mixture are not soluble in water. Therefore there is no mobility in water. Special hazards: Highly flammable If heated or in case of fire toxic fumes are formed. Degradability: Isocyanate (component A): Bio-degradation: Difficult. Polyol (component Special labelling: B): Bio-degradation: Difficult. Contains isocyanates.
FlexPipe · 2013.06
3.10.0.1 Insulating joints Storing and handling foam packs Overview
Besides the correct dosing of foam liquids which is ensured through the filling in the factory and through the numbering of foam pack sizes on joints and cartons, there are 4 factors which are important for a correct foaming process: · Liquid temperature · Job-site temperature · Dry joints · Mixing
Liquid temperature/Storage
It is very important to keep the temperature of the foam liquids within certain limits to obtain a homogeneous foam quality.
1
As the reaction time of the foam liquids depends on the storage temperature (1), the mixing (2) and filling times (3) vary.
2
When the carton is removed from the insulation box a correct temperature of application can be kept for approx. two hours. Symbol key to the shown figures: tree = job-site temperature house = storage temperature The shown figures are found on every insulation box and carton.
FlexPipe · 2013.06
30 25
20
20 15
70 60
50
45 40
30
5
Liquid temperature in carton
25
95
On condition that the cover of the insulation box is always replaced immediately after taking a carton from it, the insulation box can keep the foam liquids hot or cold throughout an ordinary working day, i.e. eight hours.
20
sec.
3
It is best to keep foam liquids in storage rooms at a temperature of 16-22°C.
Liquid temperature in insulation box
10 15
34
They appear from the foam pack carton.
°C t°C
˚C
°C
sec.
˚C
8113 2x13 23.96
5
°C
5 00 0000 0700
815
4809
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.10.0.2 Insulating joints Storing and handling foam packs Job-site temperature
If the job-site temperature is down to +10° C, then insulation is carried out as described on the carton, the label of the fitting or in this handbook. If the temperature is below +10° C, then the fitting/joint parts - particularly the lower halves - must be preheated with a soft gas flame to 30-40° C. If hot water is circulating in the pipeline, it suffices that the fitting parts have reached a temperature of approx. +20° C.
Dry joints
Moisture in a joint gives a poor foam quality. Therefore, always see to it that - the joint area is dry, before the joint is installed - avoid foaming during rainy weather. If necessary use a tent. - foam the joint the same day it has been installed.
Mixing
Careful mixing ensures a homogeneous foam quality and therefore a correctly filled joint.
2
10 15
20
25
30 25
20
20 15
70 60
50
45 40
30
5
LOGSTOR A/S · Tel. +45 99 66 10 00
°C t°C
95
The insulation process is described as a strip on the carton and on the label of the fitting.
1
34
Dependent on the liquid temperature (the lower the liquid temperature, the longer the mixing time) the two liquids are carefully shaken and mixed togehter for 15-30 seconds until the mixture has a homogeneous light brown colour.
10°C
10°C
sec.
3 sec.
FlexPipe · 2013.06
3.11.0.1 Insulating joints Using foam packs for shrink joints Application
In FlexPipe systems foam packs are used to insulate joints on Twin FlexPipes.
Tools
The required tools appear from the relevant installation instructions.
Venting holes/ plugs
It is important that the filling holes always face upwards (12 o'clock position).
12
The foam liquid should always be filled into the lower filling hole of the joint to ensure an optimum venting.
The holes in the venting plug ensure that the air in the joint can escape quickly and easily during the foaming process.
a
b
a. SXJoint predrilled hole b. T -joint straight ø 25 mm holes must be drilled prior to foaming
Correct foam pack number
1. F ind the relevant foam pack number in the folder in the insulation box, on the label of the casing joint or page 3.12.0.1 of this handbook. The cartons must be marked with the corresponding foam pack number. NB! Please differentiate between series 1 and series 2.
FlexPipe · 2013.06
15.2.6.1 Foam pack Foam pack numbers for band joint, medium Series 1 pipes ø 225-800 mm Straight joints
The list below details which foam pack numbers to use for the different Series 1 pipes.
Joint type Band joint Band joint, long Band joint, E Band joint, E long
225
250
315
400
7 8 9 10
8 9 10 10
9 10 11 2x9
11 12 10+11 13
Dimension outer casing, ø mm 450 500 520 2x9 12 13 10+12
12 13 10+12
2x9 10+11 13
560
630
780
800
12 10+11 10+12
10+11 10+12 10+13
12+13 2x13 2x12+13
10+13 12+13 2x13
Series 1 pipes ø 225-315 mm Band joint branch
This list details which foam pack numbers to use for the different Series 1 pipes.
Series 2 pipes ø 225-800 mm Straight joints
The list below details which foam pack numbers to use for the different Series 2 pipes.
Joint type Band joint Band joint, long Band joint, E Band joint, E long
LOGSTOR A/S · Tel. +45 99 66 10 00
225
250
280
355
8 9 10 11
9 10 11 11
9 10 11 2x9
11 2x9 12 10+11
Length of main pipe casing L mm/ø branch mm 590/77 590/90 590/110 590/125 590/140 Repair joint: 720/77 720/90 720/110 720/125 720/140
Dimension outer casing, ø mm 450 500 520 12 13 10+13 10+13
10+11 10+12 10+13
10+11 10+12 10+13
Dimension, main pipe outer casing ø mm 225 250 315 8 9 10 9 9 10 9 9 10 10 10 11 10 10 11 9 10 10 10 11
560
630
10+11 10+12 10+13
10+12 12+13 12+13
10 10 10 11 11
710
5
0700000000815
4809
5
11 11 11 2x9 2x9
800
12+13 12+13 2x13 2x12+13 2x12+13 2x12+13
Product Catalogue · 2009.05
SX m 02 51 60 m ø1
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.11.0.2 Insulating joints Using foam packs for shrink joints Opening carton
The cartons with foam packs must be stored in the insulating box until use. Remember to replace the cover of the box to maintain the correct liquid temperature. 2. Open the carton by pulling the perforated flap in the direction of the arrow. 3. O pen up the carton by pulling in the two holes.
Mixing foam liquids
4. P ull at both sides of the bag and remove the clip barrier, so the two liquids mix.
5. M ix the liquids by shaking the bag vigorously and stirring the two liquids with the built-in mixing stick at the same time. Mix the foam liquids carefully for the number of seconds, appearing from the table on the carton, until the liquid mixture is homogeneous light brown. Hold the mixing stick, not the nozzle.
Filling in foam liquid
6. N ow place the nozzle in the open filling hole - the lower hole of the joint. 7. Press the mixing stick into the nozzle, which is supported by one hand.
2 1
8. T wist the mixing stick back and forth several times, until the plastic membrane breaks. It is important that the penetration is thorough, so that the liquids can run down into the joint.
LOGSTOR A/S · Tel. +45 99 66 10 00
FlexPipe · 2013.06
3.11.0.3 Insulating joints Using foam packs for shrink joints Filling in foam liquid, continued
9. S queeze the foam liquid into the joint and flatten/wring the bag during filling, so that no air pockets appear behind the liquid in the bag.
Venting and hardening
10. F it the venting plugs into the filling holes after filling is complete. Proceed with the next joint. The foam liquid expands in the joint, forcing air through the venting plug. When the ventilation is complete, a little foam will be forced through the venting holes. The insulation of the joint is complete, when the foam, appearing at the holes is hard.
Removing venting plug
11. Wait min. 30 min. for degassing to complete. Remove the venting plugs by turning and lifting them. Remove excess foam or spillage, if any.
30 min.
2
1
Installing expansion/wedge plugs and patches
12. Install expansion/wedge plugs and patch as described under the individual joints.
1
The joint is now complete.
1-2 sec.
FlexPipe · 2013.06
2
20 sec.
LOGSTOR Fredericia A/S · Tel. +45 76 23 30 00
3.12.0.1 Foam pack Foam pack numbers SXJoint
Dimension, main pipe, outer casing ø mm Joint type Straight joint Reduction joint*)
Series 1
Series 2
90
110
125
140
160
110
125
140
160
180
1
3
3
4
5
3
4
5
6
7
←
1
2
3
4
←
3
4
5
6
*) From stated dimension to the next smaller dimension.
T-joint straight
Dimension, main pipe, outer casing ø mm Branch, ø mm
Series 2
90
110
125
160
3
4
5
6
5
5
7
125
6
7
140
6
7
90 110
160
LOGSTOR A/S · Tel. +45 99 66 10 00
Series 1 110
125
140
5
5
6
6
7
8
FlexPipe · 2013.06
1985 Mediegruppen 7/13
LOGSTOR A/S Danmarksvej 11 · DK-9670 Løgstør Tel. +45 9966 1000 · Fax +45 9966 1180
[email protected] · www.logstor.com