Installation Instructions
GuardMaster MSR57P Speed Monitoring Safety Relay Catalog Number 440R-S845AER-NNL
Dimensions S32 S42 S52 S62 S11 S21 S12 S22
13 14 34 44
P
Encoder 1
99 mm (3.9 in.)
24 A1 51 52
67.5 mm (2.66 in.)
Config Lock Stop
Inputs
DPI
Limited Speed Standstill
Status
Safe Speed Motion Power Door
Encoder 2 S72 S82 X32 X42 Y31 Y32 Y33 Y30
Y1 Y2 S34 Y37 68 78 Y35 A2
114.5 mm (4.51 in.)
PWR/Fault
Additional Resources Resource
Description
GuardMaster MSR57P Speed Monitoring Safety Relay User Manual, publication 440R-UM004
Detailed information on wiring, configuring, and operating an MSR57P relay, including safety requirements.
You can view or download publications at http://literature.rockwellautomation.com. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
Publication 440R-IN016B-EN-P - November 2008
2
GuardMaster MSR57P Speed Monitoring Safety Relay
Installation Instructions in Other Languages English
This instruction sheet is available in multiple languages at http://rockwellautomation.com/literature. Select publication language and type “MSR57P” in the search field.
Deutsch
Dieses Instruktionsblatt kann in mehreren Sprachen unter http://rockwellautomation.com/literature gelesen werden. Bitte Ihre Sprache anwählen und “MSR57P” im Suchfeld eintippen.
Français
Ces instructions sont disponibles dans différentes langues à l’adresse suivante: http://rockwellautomation.com/literature. Sélectionner la langue puis taper > dans le champ de recherche.
Italiano
La presente scheda d’istruzione è disponibile in varie lingue sul sito http://rockwellautomation.com/literature. Selezionare la lingua desiderata e digitare “MSR57P” nel campo di ricerca.
Español
Puede encontrar esta hoja de instrucciones en varios idiomas en http://rockwellautomation.com/literature. Seleccione el idioma de publicación y escriba “MSR57P” en el campo de búsqueda.
Português
Esta folha de instruções está disponível em várias línguas em http://rockwellautomation.com/literature. Seleccione a língua de publicação e entre com “MSR57P” no espaço de busca.
Polish
Ta kartka z instrukcjami jest dostepna w wielu jezykach na stronie: http://rockwellautomation.com/literature. Wybierz jezyk publikacji i wpisz w polu poszukiwania “MSR57P”.
Czech
Tyto pokyny jsou k dispozici v nekolika jazycích na http://rockwellautomation.com/literature. Zvolte si jazyk publikace a do vyhledávacího polícka vepište “MSR57P”.
Swedish
Detta instruktionsblad finns på olika språk på http://rockwellautomation.com/literature. Välj önskat språk och skriv “MSR57P” i sökrutan.
Dutch
Dit instructieblad is beschikbaar in diverse talen op: http://rockwellautomation.com/literature. Kies taal van publicatie en tik “MSR57P” in het zoekveld.
Chinese (complex)
從以下網頁可以獲得本說明書的多種語言的版本 :http://rockwellautomation.com/literature 。 請選擇出版物的語言 , 並在搜索欄輸入 “MSR57P”。
Chinese (simplified)
从以下网页可以获得本说明书的多种语言的版本 :http://rockwellautomation.com/literature 。 请选择出版物的语言 , 并在搜索栏输入 “MSR57P 印ٛ
Japanese
本説明書シートの多言語版は Web サイト http://rockwellautomation.com/literature にて入手できます。出版言語を選択し、検索フィールドに 「MSR57P」とタイプしてください。
Publication 440R-IN016B-EN-P - November 2008
GuardMaster MSR57P Speed Monitoring Safety Relay
3
General Safety Information Retain these instructions for future reference. Rockwell Automation cannot accept responsibility or liability for a failure of this device if the product is used outside the recommended specifications in this document.
ATTENTION This device is intended to be part of the safety-related control system of a machine. Before
installation, a risk assessment should be performed to determine whether the specifications of this device are suitable for all foreseeable operational and environmental characteristics for the machine to which it is to be fitted. At regular intervals during the life of the machine, check whether the characteristics foreseen remain valid.
ATTENTION Safety Programmable Electronic Systems (PES) Personnel responsible for the installation and application of safety-related programmable electronic systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system.
Spacing Requirements Adequate air space must be provided around the system (module cluster). Minimum recommended clearances:
• 15 mm (0.6 in.) above • 15 mm (0.6 in.) below • 2…3 mm (0.08…0.12 in.) between modules at ambient temperatures higher than 40 °C (104 °F).
Mount the MSR57P Relay Follow these steps to mount the MSR57P relay to an EN50022 -35 x 7.5 DIN rail. 1. Hook the top slot over the DIN rail. 2. Snap the bottom of the device into position while pressing the device down against the top of the rail.
Slot DIN Rail
3. Attach end plates on each end of the DIN rail. To remove the device from the DIN rail, use a flathead screwdriver to pull down the latch and lift the device from the rail.
Latch
Publication 440R-IN016B-EN-P - November 2008
4
GuardMaster MSR57P Speed Monitoring Safety Relay
S72 S82
S32 S42
X32 X42
Pulse Test Outputs
Safe Stop (SS_In)
Safe Limited Speed (SLS_In)
Enabling Switch (ESM_In)
Door Monitor (DM_In)
Lock Monitor (LM_In)
SLS_Status
Fault_Status
Y31
Y32
Y33
Y30 Y35
Y37
Door Lock Control SS_Out SLS_Out (DC_Out) (Cascade) (Cascade) bipolar 2 OSSD 2 OSSD
34
44
68
78
Lo
GND
Y2
SLS_Command
S34
Stop_Command
Y1
Diag. Out
24V dc
Reset_In Feedback (RL_In)
DPI
24V dc
Isolated Outputs
13
A1
51
52
Motion Power (MP_Out) 2 OSSD
A2
14
24
Door Lock Control (DC_Out) Cascade Hi
S52 S62
Hi
S12 S22
Hi
RJ45-1
Mini-DIN
HIM
Monitor Encoder PS
S11 S21
RJ45-2
Encoder 2
Encoder 1
Circuit Diagram
51
52
Terminal Connections Terminal A1 A2 S11, S21 S12, S22 S72, S82 S52, S62 S32, S42 X32, X42 Y1 S34 Y2 Y35 Y37 13 14, 24 68, 78 51
Function +24V dc, user supply Common, user supply Test_Out_0, Test_Out_1, pulse test outputs for safety functions SS_In_Ch0, SS_In_Ch1, Safe Stop (SS) dual-channel input ESM_In_Ch0, ESM_In_Ch1, Enabling Switch Monitor (ESM) dual-channel input SLS_In_Ch0, SLS_In_Ch1, Safe Limited Speed (SLS) dual-channel input DM_In_Ch0, DM_In_Ch1, Door Monitor (DM) dual-channel input LM_In_Ch0, LM_In_Ch1, Lock Monitor (LM) dual-channel input, solenoid position 24V dc output for reset (S34) and for feedback (Y2) Reset_In RL_In, feedback input SLS_Status output Fault_Status output Supply power for Motion Power (MP) safety outputs 14 and 24 MP_Out_Ch0, MP_Out_Ch1, Motion Power (MP) outputs SLS_Out_Ch0, SLS_Out_Ch1, Safe Limited Speed (SLS) outputs
52
DC_Out_Ch1 (Low Side), Door Control output [door switch solenoid, bipolar or cascading(1)]
34, 44
SS_Out_Ch0, SS_Out_Ch1, cascading Safe Stop outputs
Y31
24V dc power for isolated outputs
Y32
Stop_Command, isolated output
DC_Out_Ch0 (High Side), Door Control output [door switch solenoid, bipolar or cascading(1)]
Y33
SLS_Command, isolated output
Y30
GND for isolated outputs
(1)
The DC_Out output may also be configured as cascading (2 Channel Source). For information on using this configuration in limited applications, refer to the GuardMaster Speed Monitoring Safety Relay User Manual, publication 440R-UM004.
Publication 440R-IN016B-EN-P - November 2008
GuardMaster MSR57P Speed Monitoring Safety Relay
5
Status Indicators Indicator PWR/Fault
(1)
Status
Description
Green/On
The device is operating normally and is in Run mode.
Red/Flashing
A recoverable fault has occurred.
Red/On
A nonrecoverable fault has occurred.
Red/Green Flashing
The configuration is being downloaded or a firmware upgrade is in progress.
Config Lock(1) Yellow/On Yellow/Flashing
The device’s configuration is unlocked.
Stop
Green/On
The Safe Stop (SS) input is closed.
Red/On
The SS input is open or pressed.
Red/Flashing
The SS input has a fault.
Green/On
The Safe Limited Speed (SLS) input is closed for normal Run operation.
Green/Flashing
The SLS input is open for a safe speed request to allow access to the machine (Maintenance operation).
Limited Speed
Off
The SLS function is not configured.
Red/Flashing
The SLS input has a fault.
Motion Power Green/On
Door
Safe Speed
Standstill
(1)
The device’s configuration is locked.
The Motion Power (MP) output is ON.
Off
The MP output is OFF.
Red/Flashing
The MP output has a fault.
Green/On
The door is closed.
Red/On
The door is open.
Red/Flashing
Door Monitor or Lock Monitor input switch has a fault.
Off
Door monitoring is not configured.
Green/On
Safe Limited Speed is being actively monitored and is below the configured Safe Limited Speed value after an SLS request has been made.
Off
Safe Limited Speed is not being monitored.
Red/Flashing
An SLS Speed Fault has occurred.
Green/On
Standstill Speed has been detected.
Off
Speed is greater than the configured Standstill Speed.
Red/Flashing
Motion has been detected after stopped condition or a Stop Speed Fault has occurred.
PWR/Fault green indicator and Config Lock indicator flash in synch when the device is in Program mode.
When you apply power to the device, the red/green indicators flash alternate colors twice and the Config Lock indicator flashes on and off twice before all indicators except for the PWR/Fault indicator turn off. The PWR/Fault indicator remains flashing until the device enters Run or Program mode.
Publication 440R-IN016B-EN-P - November 2008
6
GuardMaster MSR57P Speed Monitoring Safety Relay
Specifications GuardMaster MSR57P Speed Monitoring Safety Relay – 440R-S845AER-NNL Attribute
Value
Standards
IEC/EN60204-1, ISO12100, IEC 61800-5-2
Safety category
Cat. 4 and PL e per EN ISO 13849-1; SIL CL1 to CL3 per IEC 61508/EN62061
Power supply
24V dc, 0.8…1.1 x rated voltage(3) PELV/SELV
Aggregate current of MSR57P
10.4 A max. @ terminal A1 + 13
Power consumption
5W
Outputs 14, 24, 68, 78 24V dc, 2 A, short-circuit protected Outputs 34, 44
24V dc, 100 mA, short-circuit protected
Outputs Y35, Y37
24V dc, 50 mA, short-circuit protected
Door switches 51, 52(1) 24V dc, short-circuit protected • 1.5 A, bipolar (Power to Release/Power to Lock) configuration • 20 mA, cascading (2 Channel Source) configuration Outputs Y32, Y33
24V dc, 100 mA, short-circuit protected
Output Y1
24V dc, 20 mA, short-circuit protected
Pulse outputs S11, S21 24V dc, 100 mA, short-circuit protected Pulse inputs S12, S22, 11 mA per input, max S32, S42, S52, S62, S72, S82, X32, X42 Inputs S34, Y2
11 mA per input, max
Power-on delay, max
3s
Response time
User-configurable.(4)
Pollution degree
2
Enclosure protection
IP40
Terminal protection
IP20
Wire Type
Use copper that will withstand 60/75 °C (140/167 °F)
Conductor size(2)
0.2…2.5 mm2 (12…24 AWG)
Terminal screw torque 0.6…0.8 Nm (5…7 lb-in) Case material
Polyamide PA 6.6
Mounting
35 mm DIN rail
Weight, approx.
350 g (0.77 lb)
(1) (2) (3) (4)
For information on using these outputs in bipolar or cascading configurations, refer to the GuardMaster Speed Monitoring Safety Relay, publication 440R-UM004. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. Safety outputs need additional fuse for reverse voltage protection of the control circuit. Install a 6 A slow-blow or 10 A fast-acting fuse. Refer to the GuardMaster MSR57P Speed Monitoring Safety Relay User Manual, publication 440R-UM004 for details.
Publication 440R-IN016B-EN-P - November 2008
GuardMaster MSR57P Speed Monitoring Safety Relay
7
Environmental Specifications Attribute
Value
Temperature, operating -5…55 °C (23…131 °F) Relative humidity
90% RH noncondensing
Vibration
10…55 Hz, 0.35 mm displacement
Shock, operating
10 g, 16 ms, 100 shocks
ESD immunity
4 kV contact discharges; 8 kV air discharges
Radiated RF immunity
10 V/m from 80…1000 MHz; 3 V/m from 1.4…2.0 GHz; 1V/m from 2.0…2.7GHz
EFT/B immunity
Power, dc: ±2 kV I/O signal lines: ±1 kV
Surge transient immunity Power, dc: ±0.5 kV line-line and ±0.5 kV line-earth I/O signal lines: ±1 kV line-earth Conducted RF immunity 10V rms from 150 kHz…80 MHz
Certifications Certification(1)
Value
c-UL-us
UL Listed, certified for US and Canada.
CE
European Union 2004/108/EC EMC Directive, compliant with: • EN 61000-6-4; Industrial Emissions. • EN 61131-2 Programmable Controllers (Clause 8, Zone A & B). • EN 61326-3-1; Meas./Control/Lab., Industrial Requirements. • EN 61000-6-2; Industrial Immunity.
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions.
TÜV
TÜV Certified for Functional Safety: SIL CL1 to CL3, according to IEC 61508/EN62061; Category 1 to 4 and Performance Level e, according to EN ISO 13849-1, when used as described in the GuardMaster MSR57P Speed Monitoring Safety Relay User Manual, publication 440R-UM004.
(1)
When product is marked. See the Product Certification link at http://ab.com for Declarations of Conformity, Certificates, and other certifications details.
Publication 440R-IN016B-EN-P - November 2008
8
GuardMaster MSR57P Speed Monitoring Safety Relay
Application Example 1 This example is configured for Safe Stop 1. The control cabinet contains an MSR57P relay, a PowerFlex 70 AC Drive with Safe-Off function, as well as a PanelView terminal. The MSR57P relay monitors speed via a TTL encoder connected to the PowerFlex 70 drive.
E-Stop Reset Maintenance
Run Stopped Safe Speed Running
Mode
The control panel lets the operator select Run or Maintenance speeds. The door has an interlock switch with guardlocking to limit access to the machine when the machine is operating at normal Run speed. A towerlight indicates machine status.
Example 1: System Layout PowerFlex 70 Drive With Safe-Off Safe Stop SLS Request
Encoder Cable 1585J-M8RB-2M5
Configuration Tools
20-HIM-A3
S32 S42 S52 S62 S11 S21 S12 S22
13 14 34 44
P
Encoder 1
20-HIM-H10
24 A1 51 52 Config Lock
PC
PWR/Fault Stop
Inputs
DPI
Encoder Input 1
Limited Speed
-OR-
Standstill Status
Safe Speed
1203-USB or 1203-SSS(B)
Motion Power Door Encoder 2 S72 S82 X32 X42 Y31 Y32 Y33 Y30
Motor Power Cable Encoder Feedback Cable
M
Start/Stop Command and Motion Power Outputs
Y1 Y2 S34 Y37 68 78 Y35 A2
MSR57P Relay
Primary Encoder (Example, Catalog Number: 845T-HZ42EEN)
Publication 440R-IN016B-EN-P - November 2008
Guardlocking Switch TLS3-GD2
(1)
S22
Y35
Y37 34
44
SLS Fault Status Status SS Output
RJ45 Encoder Input 2
SS Input
S12
S82 51
52
Door Lock Control
S34
Y33
Y32
Reset 800FM-F6MX10
Y2
Aux. Signals to PLC
Y1
Y30
X42
Y31
24V dc
14
24
A1
A2
A1
S42 13
68
42 52
41 51
78
SLS Output
Door Monitor
S32
Power to Release
Motion Power Out
Lock Monitor
X32
Isolated Diagnostics and Power
MSR57P Relay
ESM Input
S72
RL Reset Feed- SLS Stop GND back Cmd Cmd Feed
DPI
S62
SLS Input
S52
SLS Request 800FM-KM23 800F-MX02V
Digital input 4. Proper configuration is required for inputs 1, 2, 4, and 6 on the PowerFlex 70 Drive.
A2
S21
Pulse Test Outputs
S11
RJ45 Encoder Input 1
A1
E-Stop 800FM-MT44 800F-MX02V
SS Request
24V dc Com
Remove jumpers
6 Enable
4 2
1 3
Gate Control Circuit
Gate Control Power Supply
PowerFlex 70 AC Drive with DriveGuard
Remove two internal jumpers
4 SLS Input (1) Safe-Off Option
2 Start
1 Stop
9 24V dc 8 DC Comm 7 Dig Comm
TLS3-GD2 440G-T27260
12 22 34
11 21 33
Motor
L1 L2 L3
+24V dc
GuardMaster MSR57P Speed Monitoring Safety Relay 9
Example 1: System Wiring
Publication 440R-IN016B-EN-P - November 2008
10
GuardMaster MSR57P Speed Monitoring Safety Relay
Application Example 2 This example is configured for Safe Stop 1. The control cabinet contains an MSR57P relay, a Kinetix 6000 drive with Safe-Off function, as well as a PanelView terminal. The MSR57P relay monitors speed via a Sin/Cos encoder connected to the Kinetix 6000 drive.
E-Stop Reset Run Maintenance Stopped Safe Speed Running
Mode
The control panel lets the operator select Run or Maintenance speeds. The door has an interlock switch with guardlocking to limit access to the machine when the machine is operating at normal Run speed. In addition, an enabling switch is required to be held in the middle position while operators are within the machine environment to keep the machine running at safe speed. A towerlight indicates machine status.
Example 2 System Layout Kinetix 6000 or Kinetix 7000 With Safe-Off Safe Stop Low Profile Connector 2090-K6CK-D15M
Enabling Switch SLS Request
Motion Power Outputs and Feedback Monitoring From the MSR57P Relay to Kinetix Safe-Off Interface Configuration Tools
Encoder Cable 1585J-M8RB-2M5
20-HIM-A3
S32 S42 S52 S62 S11 S21 S12 S22
20-HIM-H10
13 14 24 A1 34 44 51 52
P
Encoder 1
Config Lock
PWR/Fault Stop
Inputs
DPI
Encoder Input 1
Limited Speed
PC
-OR-
Standstill Status
Safe Speed
Encoder Feedback Cable
Motion Power Door Encoder 2 S72 S82 X32 X42 Y31 Y32 Y33 Y30
Motor Power Cable
Y1 Y2 S34 Y37 68 78 Y35 A2
1203-USB or 1203-SSS(B)
MSR57P Relay
Start/Stop Command to Logix Controller MP-Series Bulletin MPL Servo Motors
Publication 440R-IN016B-EN-P - November 2008
Guardlocking Switch TLS3-GD2
A2
Y35
Y37
SLS Fault Status Status
S22
SS Input
S12
Y2
Aux. Signals to Logix Controller
Reset 800FM-F6MX10
S34
Y33
Y1
44
34
MSR57P Relay
Door Lock Control
51
52
3
1
Y32
Stop Cmd
Y30
GND
Y31
24V dc
14
24
Motion Power Out
A1
A2
A1
13
68
42 52
41 51
FDBK2
FDBK1 FDBK2
FDBK1
R1
R2
R1 Safety Monitor
24V dc Com
R2
SAFETY EN2+
SAFETY EN-
SAFETY EN1+
Gate Control Enable
R1
Gate Control Circuit
R2
Motor
L1 L2 L3
+24V dc
Gate Control Power Supply
Remove two internal jumpers
Kinetix 6000 and 7000 AC Drive with GuardMotion
TLS3-GD2 440G-T27260
12 22 34
11 21 33
Aux.Signals to Logix Controller
78
SLS Output
S42
Door Monitor
S32
Power to Release
X42
Lock Monitor
X32
Isolated Diagnostics and Power
S82
ESM Input
S72
RL Reset Feed- SLS back Cmd Feed
DPI
S62
SLS Input
S52
4
2
440J-N21TNPM Enabling Switch
SS Output
RJ45 Encoder Input 2
S21
Pulse Test Outputs
S11
RJ45 Encoder Input 1
A1
E-Stop 800FM-MT44 800F-MX02V
SS Request
SLS Request 800FM-KM23 800F-MX02V
GuardMaster MSR57P Speed Monitoring Safety Relay 11
Example 2: System Wiring
Publication 440R-IN016B-EN-P - November 2008
Rockwell Automation, Allen-Bradley, GuardMaster, PowerFlex, Kinetix, PanelView, DriveExplorer, DriveGuard, GuardMotion, and MP-Series are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 440R-IN016B-EN-P - November 2008
PN 95302398 Copyright © 2008 Rockwell Automation, Inc. All rights reserved. Printed in Germany.