Author

Checker

Approver

Drawn By:

Checked By:

Approved By:

SYSTEM ABBREVIATIONS BFF

BELOW FINISHED FLOOR

BFG

BELOW FINISHED GRADE

CFM

CUBIC FEET PER MINUTE

CI

CAST IRON

1.

THE CONTRACTOR SHALL SCHEDULE ALL WORK IN A MANNER TO MAINTAIN THE OWNER'S CONTINUOUS USE OF THE BUILDING.

2.

THE CONTRACTOR SHALL COORDINATE ALL NECESSARY INTERRUPTION OF BUILDING SERVICES WITH OWNER, GENERAL CONTRACTOR, UTILITY COMPANIES, AND ALL AFFECTED PARTIES.

3. CO

CLEANOUT

CW

COLD WATER DRAINAGE FIXTURE UNITS

DN

DOWN

EA

EACH

ELECT

ELECTRICAL

FC

FINAL CONNECT

FD

FLOOR DRAIN

FE

FIRE EXTINGUISHER

FEC

FIRE EXTINGUISHER CABINET

FF

FINISHED FLOOR

FLR MTD

FLOOR MOUNTED

FT

FEET

5.

6. 7.

8.

FT HD

FEET OF HEAD

FV

FLUSH VALVE

GN

GOOSENECK

GPH

GALLONS PER HOUR

GPM

GALLONS PER MINUTE

HP

HORSE POWER

HW

HOT WATER

HWR

HOT WATER RETURN

IE

INVERT ELEVATION

IN

INCHES

LPA

LINE PRESSURE ALARM

MECH

MECHANICAL

MSA

MULTI-SIGNAL ALARM

MU

MAKE-UP

NCA

NON-CLINCAL AIR

NCV

NON-CLINCAL VACUUM

OFE

OWNER FURNISHED EQUIPMENT

PRV

PRESSURE REDUCING VALVE

RI

ROUGH-IN

SAN

SANITARY WASTE

SCFM

STANDARD CUBIC FEET PER MINUTE

SS

STAINLESS STEEL

TOC

TOP OF COVER

TOS

TOP OF STEEL

VB

VACUUM BREAKER

VTR

VENT THRU ROOF

WB

WRIST BLADE

WCO

WALL CLEANOUT

WH

WALL HUNG

SCHEMATIC SYMBOL

DOMESTIC COLD WATER PIPING

HW

DOMESTIC HOT WATER PIPING

HWR

THE DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER TRADES AND WITH THE NEW CONSTRUCTION PLANS FOR THE EXACT SCOPE OF WORK AND ALL PHASING REQUIREMENTS.

G S & P

SYMBOL DESCRIPTION

CW

R

Design Services For The Built Environment

DOMESTIC HOT WATER RETURN PIPING SANITARY VENT PIPING

SAN 4.

DFU

PLUMBING SYMBOL LEGEND

GENERAL DEMOLITION NOTES

EXISTING PLUMBING FIXTURES INDICATED SHALL REMAIN AS IS UNLESS OTHERWISE NOTED ON THE CONTRACT DOCUMENTS.

SANITARY WASTE PIPING EXISTING PIPING TO BE REMOVED EXISTING PIPING TO REMAIN

REMOVE ALL EXISTING PLUMBING FIXTURES AS INDICATED ON THE CONTRACT DOCUMENTS. REMOVAL OF PLUMBING FIXTURES SHALL INCLUDE AT A MINIMUM THE REMOVAL OF CONNECTED PIPING TO BEHIND NEW ARCHITECTURAL FINISHES.

BALL VALVE SOLENOID VALVE

THE REMOVAL OF EXISTING FIXTURES, EQUIPMENT, AND PIPING SHALL ALSO INCLUDE THE REMOVAL OF ALL ASSOCIATED HANGERS, ANCHORS, PADS, ETC.

#

PLUMBING FIXTURES REMOVED MAY BE REUSED PROVIDED THEY ARE CLEANED, RECONDITIONED, AND CONFORM EXACTLY TO THAT SPECIFIED. THE OWNER'S REPRESENTATIVE TO MAKE FINAL DECISION AS TO THE FIXTURE'S ACCEPTANCE.

REFER TO DRAWING KEYNOTE POINT OF NEW CONNECTION

EXISTING FIXTURES AND MATERIALS REMOVED BUT NOT REINSTALLED SHALL BE OFFERED TO THE OWNER FOR RETAINMENT OR DISPOSAL UPON THEIR DISCRETION.

NCA

NON-CLINICAL AIR PIPING

NCV

NON-CLINICAL VACUUM PIPING

Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS

GRESHAM SMITH AND PARTNERS

NON-CLINICAL ZONE VALVE BOX 9.

EXISTING VERTICAL PIPING DISCOVERED IN WALLS OR CHASES DURING DEMOLITION SHALL BE REWORKED TO OFFSET INTO NEW WALLS, CHASES, ETC. AND RECONNECTED TO MAINTAIN SERVICES AS REQUIRED IN THE FLOORS ABOVE AND BELOW.

10.

PLUMBING SERVICES FOR EXISTING EQUIPMENT SCHEDULED FOR REMOVAL SHALL BE DISCONNECTED AND CAPPED BEHIND NEW FINISHES. FLOOR DRAINS SERVING EQUIPMENT SHALL BE REMOVED AND THE FLOOR PATCHED TO MATCH EXISTING SURFACES.

Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL

225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699 FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381

GENERAL PLUMBING NOTES 1.

THE CONTRACTOR SHALL SCHEDULE ALL WORK IN A MANNER TO MAINTAIN THE OWNER'S CONTINUOUS USE OF THE BUILDING.

2.

THE CONTRACTOR SHALL COORDINATE ALL NECESSARY INTERRUPTION OF BUILDING SERVICES WITH OWNER, GENERAL CONTRACTOR, UTILITY COMPANIES, AND ALL AFFECTED PARTIES.

3.

ALL WORK SHALL BE COORDINATED WITH ALL OTHER TRADES.

4.

THE CONTRACTOR SHALL COORDINATE WITH ALL EQUIPMENT MANUFACTURERS AND OWNER TO DETERMINE EXACT SCOPE OF WORK AND MATERIALS NECESSARY FOR PROPER INSTALLATION AND OPERATION.

5.

THE CONTRACTOR SHALL MAINTAIN PROPER CLEARANCE ABOVE AND 42" IN FRONT OF ALL ELECTRICAL/ELECTRONIC EQUIPMENT INCLUDING BUT NOT LIMITED TO PANELS, STARTERS, TRANSFORMER, ETC.

6.

IF PIPING ENCROACHES UPON PROPER CLEARANCES AND 42 INCHES IN FRONT OF ELECTRICAL/ELECTRONIC EQUIPMENT, WHETHER NEW OR EXISTING CONDITIONS, THE PIPING SHALL BE REWORKED TO RUN OUTSIDE RESTRICTED AREA.

7.

COORDINATE ALL SLAB PENETRATIONS AND SLAB RECESSES WITH STRUCTURAL.

8.

COORDINATE ALL UTILITY BUILDING EXIT/ENTRANCE POINTS WITH SITE UTILITY CONTRACTOR. COORDINATION SHALL INCLUDE EXACT POINTS OF EXIT/ENTRANCE, INVERT ELEVATIONS, PIPE SIZES, ETC.

9.

ALL PIPE ROUTING (DOMESTIC WATER, SANITARY WASTE AND VENT, MEDICAL GASES, ETC.) SHALL BE COORDINATED WITH MECHANICAL DUCTWORK AND PIPING, ELECTRICAL LIGHTING LAYOUTS, ARCHITECTURAL CEILING HEIGHTS, ETC.

10.

11.

12.

13.

ALL SANITARY WASTE AND RAIN WATER LEADER PIPING LINE SIZE 3" AND LARGER SHALL BE SLOPED AT 1/8 INCH FALL PER FOOT AND LINE SIZES 2-1/2" AND SMALLER SHALL BE SLOPED AT 1/4 INCH FALL PER FOOT. ALL VENTS THRU ROOF WILL BE OFF-SET AS REQUIRED TO MAINTAIN THE FOLLOWING DISTANCES: MECHANICAL FRESH AIR INTAKE 25 FEET ADJACENT VERTICAL WALLS WITH WINDOWS 25 FEET ADJACENT VERTICAL WALLS WITHOUT WINDOWS 10 FEET EDGE OF BUILDING 5 FEET ALL PLUMBING FIXTURES, GROUPS OF PLUMBING FIXTURES, AND EQUIPMENT WITH FLUSH VALVES AND/OR QUICK CLOSING VALVES SHALL BE PIPE WITH SEALED SHOCK ABSORBERS. SIZE AND PLACEMENT SHALL BE PER PLUMBING DRAINAGE INSTITUTE RECOMMENDATIONS AND REQUIREMENTS. ALL PLUMBING FIXTURES AND/OR EQUIPMENT CONNECTIONS THAT HAVE THE POTENTIAL FOR BACK SIPHONAGE INTO THE DOMESTIC WATER SYSTEM SHALL BE PROTECTED WITH A BACKFLOW PREVENTION DEVICE AS REQUIRED BY LOCAL CODE REQUIREMENTS.

14.

COORDINATE EXACT LOCATION OF ALL FLOOR DRAINS WITH OWNER FURNISHED EQUIPMENT BEING SERVED, HVAC EQUIPMENT, AND LOCATIONS INDICATED ON ARCHITECTURAL FLOOR PLANS FOR SLOPING REQUIREMENTS.

15.

SAWCUT EXISTING FLOOR SLABS AS REQUIRED FOR NEW PIPING INSTALLATION. REPAIR FLOOR SLAB TO MATCH EXISTING CONDITIONS AFTER INSTALLATION OF NEW PIPING.

1

PLUMBING ADD ALTERNATES GENERAL: THE PLUMBING ADD ALTERNATES EFFECT MULTIPLE SHEETS. REFER TO ARCHITECTURAL DRAWINGS FOR ADD ALTERNATE DRAWINGS. PLUMBING ADD ALTERNATE 1: PROVIDE WALL HUNG 10 LBS. ABC FIRE EXTINGUISHER IN RECEPTION AREA. PROVIDE JUST NUMBER SLADA-1921-A-GR, SINGLE COMPARTMENT 18 GAGE STAINLESS STEEL SINK, 19 INCHES O.D. BY 21 INCHES O.D. BY 5-1/2 INCHES I.D. DEEP COMPARTMENT. CHICAGO FAUCET NUMBER 786-GN2AFCCP, GOOSENECK FAUCET WITH 4 INCH WRIST CONTROL HANDLES, 1.5 GPM LAMINAR FLOW IN BASE OF SPOUT AND PLAIN END TRIM. MCGUIRE NUMBER 1149WC, BRASS FLAT GRID SINK STRAINER WITH 1-1/2 INCH TAILPIECE OFFSET FOR ACCESSIBLE USE. MCGUIRE NUMBER 8912, 1-1/2 INCH SEMICAST BRASS P-TRAP WITH CLEANOUT PLUG, PIPED PARALLEL TO WALL. MCGUIRE NUMBER BV175, SUPPLIES WITH WHEEL HANDLE STOP. CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM SINK TO EXISTING MAINS ABOVE THE CEILING AND PROVIDE BALL VALVES ON NEW BRANCH PIPING. CONNECT NEW 2" SANITARY WASTE FROM SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING. PLUMBING ADD ALTERNATE 2: PROVIDE WALL HUNG 10 LBS. ABC FIRE EXTINGUISHER IN STORAGE ROOM AND IN LIVING/KITCHEN AREA. PROVIDE JUST NUMBER DL-1829-A-GR, DOUBLE COMPARTMENT 18 GAGE STAINLESS STEEL SINK, 12 INCHES I.D. BY 12 INCHES I.D. BY 7-1/2 INCHES I.D. DEEP COMPARTMENTS. KOHLER NUMBER K-15173-PT, SINGLE LEVER FAUCET, 10" SPOUT REACH, HOSE SPRAY MOUNTED IN ESCUTCHEON. MCGUIRE NUMBER 151, BASKET STRAINERS WITH 1-1/2 INCH TAILPIECE. MCGUIRE NUMBER 8912, 1-1/2 INCH SEMI-CAST BRASS P-TRAP WITH CLEANOUT PLUG. MCGUIRE NUMBER 111C16G17, 1-1/2 INCH CONTINUOUS WASTE WITH REQUIRED END OUTLET LENGTH. MCGUIRE NUMBER BV175, SUPPLIES WITH WHEEL HANDLE STOP. PROVIDE KOHLER NUMBER K-3889-T(TR), 1.28 GALLON VITREOUS CHINA SIPHON JET, FLOOR MOUNTED FLUSH TANK, WATER CLOSET WITH TWO BOLT CAPS AND TANK COVER LOCKS. KOHLER NUMBER K-4670-C, ELONGATED PLASTIC, OPEN FRONT SEAT WITH CHECK HINGE. TANK HANDLE TO BE MOUNTED ON "MOST OPEN" SIDE OF WATER CLOSET. ONE (1) MCGUIRE MANUFACTURING COMPANY, INC., NUMBER BV172, SUPPLY WITH QUARTER TURN WITH CONVERTIBLE LOOSE KEY HANDLE. PROVIDE KOHLER NUMBER K-505 LEFT OUTLET, OR K-506 RIGHT OUTLET, ENAMELED CAST IRON BATHTUB, AS SHOWN ON CONTRACT DRAWINGS. SYMMONS TEMPTROL NUMBER S-96-600-B30-LR-X-CHKS, PRESSURE BALANCING VALVE WITH INTEGRAL DIVERTER, 2.5 GPM, FIXED SHOWER HEAD, TUB SPOUT, HAND SHOWER, LEVER HANDLE, 30 INCH SLIDE BAR, AND INTEGRAL CHECK STOPS. EBC, INC. NUMBER WB150T, 1-1/2 INCH TUB DRAIN AND OVERFLOW. FURNISH AND INSTALL REQUIRED 1-1/2 INCH P-TRAP (2 INCHES WHEN BATHTUB ON GRADE). PROVIDE P321 IN MILLWORK IN RESTROOM. CONNECT NEW 3/4" COLD WATER AND HOT WATER FROM EXISTING MAINS ABOVE THE CEILING AND CONNECT TO NEW FIXTURES. PROVIDE BALL VALVES ON NEW BRANCH PIPING. CONNECT NEW 2" SANITARY WASTE FROM SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING.

1

NORTH CAMPUS SIMULATION LAB

PLUMBING ADD ALTERNATE 3: PROVIDE WALL HUNG 10 LBS. ABC FIRE EXTINGUISHER LOCATED IN A CABINET IN THE CORRIDOR.

FLORIDA STATE COLLEGE AT JACKSONVILLE

PROVIDE P321 IN MILLWORK IN SIMULATION 5. CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM EXISTING MAINS ABOVE THE CEILING AND CONNECT TO NEW FIXTURE. PROVIDE BALL VALVES ON NEW BRANCH PIPING. PROVIDE ISIMET SOLENOID ENCLOSURE MODEL S-1311-2-1/2-S ABOVE CEILING FOR DOMESTIC WATER TO P321 . CONNECTSOLENOID VALVES TO ISIMET CONTROL PANELS IN CONTROL ROOM. CONNECT NEW 2" SANITARY WASTE FROM SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING. CONNECT 1" NON-CLINICAL VACUUM AND 3/4" NON-CLINICAL AIR TO VALVED AND CAPPED STUB-OUTS PROVIDED IN BASE BID. ROUTE NEW PIPING THROUGH NEW ZONE VALVE BOX OUTSIDE SIMULATION 5 AND ROUTE TO OUTLETS/INLETS LOCATIONS AS SHOWN ON ARCHITECTURAL ELEVATIONS. PROVIDE ISIMET SOLENOID ENCLOSURE MODEL S-1311-3-3/4-1-S ABOVE CEILING FOR NON-CLINICAL GASES. CONNECT SOLENOID VALVES TO ISIMET CONTROL PANELS IN CONTROL ROOM.

4501 Capper Rd. Jacksonville, FL 32218

PLUMBING ADD ALTERNATE 4: PROVIDE WALL HUNG 10 LBS. ABC FIRE EXTINGUISHER LOCATED IN A CABINET IN THE WORKROOM. PROVIDE JUST NUMBER SLADA-1921-A-GR, SINGLE COMPARTMENT 18 GAGE STAINLESS STEEL SINK, 19 INCHES O.D. BY 21 INCHES O.D. BY 5-1/2 INCHES I.D. DEEP COMPARTMENT. CHICAGO FAUCET NUMBER 786-GN2AFCCP, GOOSENECK FAUCET WITH 4 INCH WRIST CONTROL HANDLES, 1.5 GPM LAMINAR FLOW IN BASE OF SPOUT AND PLAIN END TRIM. MCGUIRE NUMBER 1149WC, BRASS FLAT GRID SINK STRAINER WITH 1-1/2 INCH TAILPIECE OFFSET FOR ACCESSIBLE USE. MCGUIRE NUMBER 8912, 1-1/2 INCH SEMICAST BRASS P-TRAP WITH CLEANOUT PLUG, PIPED PARALLEL TO WALL. MCGUIRE NUMBER BV175, SUPPLIES WITH WHEEL HANDLE STOP.

BID REVIEW

CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM SINK TO EXISTING MAINS ABOVE THE CEILING AND PROVIDE BALL VALVES ON NEW BRANCH PIPING.

NOT FOR CONSTRUCTION

CONNECT NEW 2" SANITARY WASTE FROM SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING. PLUMBING ADD ALTERNATE 5: PROVIDE P321 IN MILLWORK IN EXAM 1 AND EXAM 2. CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM EXISTING MAINS ABOVE THE CEILING AND CONNECT TO NEW FIXTURE IN EXAM 1. PROVIDE BALL VALVES ON NEW BRANCH PIPING. PROVIDE ISIMET SOLENOID ENCLOSURE MODEL S-1311-2-1/2-S ABOVE CEILING FOR DOMESTIC WATER TO P321 . CONNECT SOLENOID VALVES TO ISIMET CONTROL PANELS IN CONTROL ROOM. CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM EXISTING MAINS ABOVE THE CEILING AND CONNECT TO NEW FIXTURE IN EXAM 2. PROVIDE BALL VALVES ON NEW BRANCH PIPING. PROVIDE ISIMET SOLENOID ENCLOSURE MODEL S-1311-2-1/2-S ABOVE CEILING FOR DOMESTIC WATER TO P321 . CONNECT SOLENOID VALVES TO ISIMET CONTROL PANELS IN CONTROL ROOM.

1/3/2017 2:23:12 PM

C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt

CONNECT NEW 2" SANITARY WASTE FROM EACH SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING. PLUMBING ADD ALTERNATE 6:

Revision No. 1

Date 01/04/17

Description Addendum 2

PROVIDE P321 IN MILLWORK IN TEAM STATION 1. CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM SINK TO EXISTING MAINS ABOVE THE CEILING AND PROVIDE BALL VALVES ON NEW BRANCH PIPING. CONNECT NEW 2" SANITARY WASTE FROM SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING.

PLUMBING & MEDICAL GENERAL NOTES & LEGENDS

P001 PROJECT: 42390.00 DATE: November 21, 2016

PLUMBING FIXTURE SPECIFICATIONS

Approver

Checker

Author

GAS WATER HEATER SCHEDULE Approved By:

1

WH-1

LAVATORY (INTEGRAL , GN, ACCESSIBLE, COUNTERTOP FURNISHED BY OTHERS) INTEGRAL COUNTERTOP TOP AND LAVATORY BOWL FURNISHED BY INTERIORS AND INSTALLED BY CONTRACTOR. CONTRACTOR SHALL FURNISH AND INSTALL THE FOLLOWING: CHICAGO FAUCET NUMBER 895-317GN2FCCP, 4-INCH CENTER GOOSENECK FAUCET WITH 4 INCH WRIST CONTROL HANDLES AND 1.5 GPM LAMINAR FLOW CONTROL DEVICE AT BASE OF SPOUT. MCGUIRE MANUFACTURING, INC., NUMBER 155WC, 1-1/4 INCH GRID DRAIN WITH TAILPIECE, OFFSET FOR ACCESSIBLE USE. MCGUIRE MANUFACTURING, INC., NUMBER 8872, 1-1/4 INCH CAST BRASS P-TRAP WITH CLEANOUT PLUG. P-TRAP PIPED PARALLEL TO WALL. MCGUIRE MANUFACTURING, INC., NUMBER BV175, SUPPLIES WITH QUARTER-TURN BRASS BALL VALVE STOPS.

INPUT RATING

VOLTAGE / PHASE

GALLONS STORAGE

E.W.T.

L.W.T.

FLOW RECOVERY IN GPH

LOCATION

199,999 BTUH/7"-14" WC

120/1

90

40°

120°

233

JANITOR

MANUFACTURER / MODEL NUMBER LOCHINVAR / SNA201-100

G S & P R

Design Services For The Built Environment

REMARKS:

Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS

1

Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL

GRESHAM SMITH AND PARTNERS 225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699 FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381

PUMP SCHEDULE PUMP DATA MARK

MANUFACTURER

MOTOR DATA

PUMP MODEL PUMP DISCHARGE

FLOW RATE

FLUID PUMPED

RECEIVER GALLONS

HORSEPOWER

VOLT/PHASE

R.P.M.

NCVP-1

BEACON MEDAES

VDV05D-080V-D

19" HG

21 CFM

AIR

80

5 H.P.

460/3

----

NCAP-1

BEACON MEDAES

SAS10D-120V-D

50 PSI

34.8 CFM

AIR

120

10 H.P.

460/3

----

REMARKS:

FIXTURE CONNECTION SCHEDULE CONNECTION SIZES TAG P321

DESCRIPTION LAVATORY (INTEGRAL, GN, ACCESSIBLE, COUNTERTOP FURNISHED BY OTHERS)

WASTE

CW

HW

1 1/2"

1/2"

1/2"

1

NORTH CAMPUS SIMULATION LAB FLORIDA STATE COLLEGE AT JACKSONVILLE 4501 Capper Rd. Jacksonville, FL 32218

BID REVIEW NOT FOR CONSTRUCTION

Revision C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt

No.

1/3/2017 2:23:13 PM

Checked By:

Drawn By:

P321

TAG

1

Date 01/04/17

Description Addendum 2

PLUMBING SCHEDULES & SPECIFICATIONS

P002 PROJECT: 42390.00 DATE: November 21, 2016

Author

Checker

Approver

Drawn By:

Checked By:

Approved By:

G S & P R

Design Services For The Built Environment

STOR/ LAUNDRY E102

FREEZER E107

LOADING DOCK E100A

IDF E102A

REF E108

SAN

133 SF

M E104

FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381

160 SF

3" G 2 1/2"

6"

2"

CW

69 SF

OFFICE E103A

OFFICE E103

CW

CORR 2 1/2" E100

STOR E110

CW HW

LAB SUPPORT E111

225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699

ELEVATOR E190

W E105

121 SF

GRESHAM SMITH AND PARTNERS

GARBAGE E101

8 SF

FREEZER E109

Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL

127 SF

STOR E106

81 SF

Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS

1 1/2"

1

3"

MECH E182

SAN

151 SF

4"

STOR E181 177 SF

SAN

402 SF

1 1/2"

1 1/2" 4"

1 4

4" HW CW

2

EXTERIOR CIRCULATION E183

SAN

CULINARY ARTS2 LAB 1 E114

N SA

CULINARY SERVICE E113

CATERING LAB E179

523 SF

515 SF

1 4"

MEN LOCKER E175

1651 SF

2 2 2

2" CW

1 4

RELATED INSTRUCTION E117

3

1

2

WOMEN LOCKER E176

1224 SF

CORR. E124A

1

M I( C D L K N IS lin 2 U , )T IY L

CULINARY ARTS LAB E116

SAN

254 SF

DISHWASHING 2 E118

6

1 4

3

2

JANITOR E177A

211 SF

225 amp PANEL

LAB SUPPORT E115

K

S

LAB SUPPORT E119 FOOD SERVICE E120

66 SF

608 SF

N SA

93 SF

WOMEN E177

DRAWING KEYNOTES:

EXTERIOR CIRCULATION E184 DINING E122A

376 SF

4"

3"

1

1.

DEMOLISH EXISTING FIXTURE AND ASSOCIATED PIPING BACK TO MAINS AND CAP.

2.

DEMOLISH EXISTING FLOOR DRAIN/FLOOR SINK AND ASSOCIATED PIPING BACK TO MAIN AND CAP.

3.

DEMOLISH EXISTING TRENCH DRAIN AND ASSOCIATED PIPING BACK TO MAIN AND CAP.

4.

DEMOLISH EXISTING VENT PIPING BACK TO RISER UP TO SECOND FLOOR AND CAP. RISER SHALLL REMAIN.

NORTH CAMPUS SIMULATION LAB FLORIDA STATE COLLEGE AT JACKSONVILLE

S

SK

S

SERVICE E123

4501 Capper Rd. Jacksonville, FL 32218

S

CULINARY LAB E121 1220 SF

DINING E122

SS a Sb

1054 SF 4"

4" SAN

SAN

BID REVIEW

D

SK

NOT FOR CONSTRUCTION

E187 LAB SERVICE E121A Revision

1/3/2017 2:23:13 PM

C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt

No. 1

1

FIRST FLOOR DEMOLITION 1/8" = 1'-0"

0'

4'

8'

16'

24'

Date 01/04/17

Description Addendum 2

FIRST FLOOR DEMOLITION

P121 PROJECT: 42390.00 DATE: November 21, 2016

Author

Checker

Approver

Drawn By:

Checked By:

Approved By:

G S & P R

Design Services For The Built Environment Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS

LOADING DOCK E100A LP

FREEZER E107

STOR E106

LP

REF E108

W E105

121 SF

STOR E110

69 SF

ELEVATOR E190

6"

225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699

OFFICE E103A

OFFICE E103 133 SF

M E104

GRESHAM SMITH AND PARTNERS

FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381

160 SF

SAN

FREEZER E109

GARBAGE E101

IDF 102

LP

Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL

1

1 CR

MECH E182

LAB SUPPORT E111

151 SF 4"

3"

STOR E181 177 SF

3" SAN

4"

SAN

402 SF

4" 4" 4"

SIMULATION 3 E112A

1 2"

N SA

EXTERIOR CIRCULATION E183

SAN

CR

CONTROL 2 E112 1

4"

MEN LOCKER E175

1651 SF

SIMLUATION 4 E112B N SA

SIMULATION 1 E113A

1

CATERING LAB E179

2"

CR

FCO

4"

WOMEN LOCKER E176

SAN 2" 1

CONTROL 1 E113

1

K

S

JANITOR E177A

CORRIDOR E114

TEAM STATION 1 E115

LAB SUPPORT E119

SAN

SIMULATION 2 E113B

1.

M I( C D L K N IS lin 2 U , )T IY L

4"

CR

CORRIDOR E114.1

DRAWING KEYNOTES:

FOOD SERVICE E120

1

NORTH CAMPUS SIMULATION LAB

EXTERIOR CIRCULATION E184 DINING E122A

376 SF 4"

WOMEN E177

608 SF

93 SF

CONNECT NEW 2" SANITARY TO EXISTING IN THIS APPROXIMATE LOCATION.

S

FLORIDA STATE COLLEGE AT JACKSONVILLE

SK

4" S

SERVICE E123

S

4501 Capper Rd. Jacksonville, FL 32218

CULINARY LAB E121 1220 SF

DINING E122

SS a Sb

1054 SF 4"

4" SAN

SK

BID REVIEW D

NOT FOR CONSTRUCTION

E187 LAB SERVICE E121A

Revision

1/3/2017 2:23:15 PM

C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt

No. 1

1

Date 01/04/17

Description Addendum 2

FIRST FLOOR UNDERGOUND PLAN 1/8" = 1'-0"

0'

4'

8'

16'

24'

FIRST FLOOR UNDERGOUND

P201 PROJECT: 42390.00 DATE: November 21, 2016

Author

Checker

Approver

Drawn By:

Checked By:

Approved By:

G S & P R

Design Services For The Built Environment Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS

LOADING DOCK E100A LP

FREEZER E107

STOR E106

LP

REF E108

69 SF

STOR E110

OFFICE E103 133 SF

M E104

160 SF

1

LAB SUPPORT E111

FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381

OFFICE E103A

MECH E182

CR

FREEZER E109

225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699

ELEVATOR E190

W E105

121 SF

GRESHAM SMITH AND PARTNERS

GARBAGE E101

IDF 102

LP

151 SF

402 SF

Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL

1

STOR E181 177 SF

2

SIMULATION 3 E112A

2"

EXTERIOR CIRCULATION E183

2"

CR

2"

CATERING LAB E179

CONTROL 2 E112 2"

MEN LOCKER E175

1651 SF 1

SIMLUATION 4 E112B

SIMULATION 1 E113A 1

DRAWING KEYNOTES: 2"

WOMEN LOCKER E176

CR

2"

CONTROL 1 E113

JANITOR E177A

LAB SUPPORT E119

WOMEN E177

NORTH CAMPUS SIMULATION LAB

EXTERIOR CIRCULATION E184 DINING E122A

376 SF

FOOD SERVICE E120 1

CONNECT NEW 2" VENT TO EXISTING 2" VENT UP IN THIS APPROXIMATE LOCATION.

K

CORRIDOR E114

TEAM STATION 1 E115

2.

S

2

SIMULATION 2 E113B

CAP EXISTING VENT PIPING ABOVE CEILING IN THIS APPROXIMATE LOCATION.

1

M I( C D L K N IS lin 2 U , )T IY L

CR

CORRIDOR E114.1

2"

1.

608 SF

93 SF

FLORIDA STATE COLLEGE AT JACKSONVILLE

S

SK

S

SERVICE E123

4501 Capper Rd. Jacksonville, FL 32218 S

CULINARY LAB E121

DINING E122

SS a Sb

BID REVIEW

1054 SF

1220 SF

D

SK

NOT FOR CONSTRUCTION

E187 LAB SERVICE E121A

Revision

1/3/2017 2:23:16 PM

C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt

No. 1

1

FIRST FLOOR GRAVITY PLAN 1/8" = 1'-0"

0'

4'

8'

16'

Date 01/04/17

Description Addendum 2

FIRST FLOOR GRAVITY

24'

P301 PROJECT: 42390.00 DATE: November 21, 2016

Author

Checker

Approver

Drawn By:

Checked By:

Approved By:

G S & P R

Design Services For The Built Environment Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS

LOADING DOCK E100A LP

FREEZER E107

STOR E106

LP

REF E108 121 SF 2 1/2"

FREEZER E109 69 SF

225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699

ELEVATOR E190

W E105

OFFICE E103

M E104

FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381

OFFICE E103A

133 SF

CW

STOR E110

GRESHAM SMITH AND PARTNERS

GARBAGE E101

IDF 102

LP

Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL

160 SF

3" G

CW

2 1/2"

LAB SUPPORT E111

MECH E182

CR

2" CW HW

1

1 1/2"

2 1/2"

177 SF

1 1/4"

HW CW

402 SF

151 SF

STOR E181

1 1/2"

1 1/2"

SIMULATION 3 E112A

1

EXTERIOR CIRCULATION E183

2 1/2" P321 1

1/2" CR

2

1/2"

1

CATERING LAB E179

CONTROL 2 E112

MEN LOCKER E175

1651 SF

1/2" P321

2

1 1/2"

P321

2"

1 1/2"

CR

1/2"

SIMLUATION 4 E112B

CW

SIMULATION 1 E113A

WOMEN LOCKER E176

1/2" 2

CONTROL 1 E113

P321 M I( C D L K N IS lin 2 U , )T IY L

CR

CORRIDOR E114.1

JANITOR E177A

LAB SUPPORT E119

TEAM STATION 1 E115

1.

CONNECT NEW 1/2" CW AND 1/2" HW TO EXISTING MAINS. FEILD VERIFY EXACT CONNECTION POINT.

2.

PROVIDE ISIMET SOLENIOD ENCLOSURE MODEL S-1311-2-1/2-S FOR DOMESTIC WATER. CONNECT SOLENIOD VALVES TO ISIMET CONTROL PANELS. REFER TO ELECTRICAL SHEET E212 FOR PANEL LOCATIONS AND SHEET E601 FOR DETAILS.

K

S

CORRIDOR E114

SIMULATION 2 E113B

DRAWING KEYNOTES:

1

WOMEN E177

EXTERIOR CIRCULATION E184 DINING E122A

376 SF

FOOD SERVICE E120

608 SF

93 SF

NORTH CAMPUS SIMULATION LAB FLORIDA STATE COLLEGE AT JACKSONVILLE

S

SK

S

SERVICE E123 4501 Capper Rd. Jacksonville, FL 32218 S

CULINARY LAB E121

DINING E122

SS a Sb

1054 SF

BID REVIEW

1220 SF

D

SK

NOT FOR CONSTRUCTION

E187 LAB SERVICE E121A Revision

1/3/2017 2:23:17 PM

C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt

No. 1

1

FIRST FLOOR PLUMBING PLAN 1/8" = 1'-0"

0'

4'

8'

16'

Date 01/04/17

Description Addendum 2

FIRST FLOOR PLUMBING

24'

P401 PROJECT: 42390.00 DATE: November 21, 2016

Author

Checker

Approver

Drawn By:

Checked By:

Approved By:

G S & P Design Services For The Built Environment

BOILER ROOM E201

ELEC. E203

MECHANICAL (HVAC) E202

1252 SF

1012 SF WH-1

DEMOLISH EXISTING NATURAL GAS WATER HEATER AND REPLACE WITH WH-1. RECONNECT EXISTING PIPING TO NEW WATER HEATER AND SET DISCHARGE TEMPERATURE TO MATCH EXISTING SETTING

WORK RM E211

177 SF

ELEVATOR EQUIPMENT E204

WORK AREA E210 123 SF

COVERED WALKWAY E206

OFFICE E207B

OFFICE E207A

102 SF

106 SF

MONITOR CHECK-IN E209

130 SF

75 SF

ELEV E249

Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL

GRESHAM SMITH AND PARTNERS 225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699 FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381

108 SF

OFFICE E213

Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS

R

E207

123 SF

OPEN LAB E214 83 SF

OPEN LAB E215

CORR E212 WAITING/ REC E216

WALK-IN TESTING E217

84 SF

ROOF BELOW

90 SF

OFFICE E216 130 SF

E224

GROUP TESTING E218 90 SF

CORR. E220

MECH E225A 90 SF

E226 OPEN TO BELOW

CULINARY LAB E225

EXTERNAL CIRCULATION COVERED WALKWAY E248

1116 SF

OPEN BELOW (MALLARD ROOM)

NORTH CAMPUS SIMULATION LAB FLORIDA STATE COLLEGE AT JACKSONVILLE 4501 Capper Rd. Jacksonville, FL 32218

OPEN BELOW (CAFETERIA) E244 BID REVIEW

OPEN TO BELOW

NOT FOR CONSTRUCTION

Revision

1/3/2017 2:23:18 PM

C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt

No.

1

Date

Description

SECOND FLOOR PLUMBING PLAN 1/8" = 1'-0"

0'

4'

8'

16'

24'

SECOND FLOOR PLUMBING

P402 PROJECT: 42390.00 DATE: November 21, 2016

Author

Checker

Approver

Drawn By:

Checked By:

Approved By:

G S & P R

Design Services For The Built Environment Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS

LOADING DOCK E100A LP

FREEZER E107

STOR E106

LP

REF E108

69 SF

STOR E110

OFFICE E103 133 SF

M E104 NCA

1

160 SF

3

MECH E182

1 1/4" 5

LAB SUPPORT E111

FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381

OFFICE E103A

CR

FREEZER E109

225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699

ELEVATOR E190

W E105

121 SF

GRESHAM SMITH AND PARTNERS

GARBAGE E101

IDF 102

LP

Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL

1 1/4" NCV

151 SF

STOR E181 1 1/4"

NCVP-1 NCV

177 SF 1"

1

4

402 SF

NCV

NCA

1 1/4"

SIMULATION 3 E112A

3/4"

EXTERIOR CIRCULATION E183

ZVB 2

3

2

1" 3

3/4"

3/4" CR

ZVB

1/2"

CATERING LAB E179

CONTROL 2 E112

1"

MEN LOCKER E175

1651 SF A NC V NC

SIMULATION 1 E113A

SIMLUATION 4 E112B

ZVB CR

3/4"

3/4"

1" 3/4"

CONTROL 1 E113

3 2

CORRIDOR E114.1

CR

2

3/4" M I( C D L K N IS lin 2 U , )T IY L

ZVB 1/2"

WOMEN LOCKER E176

1/2"

K

S

JANITOR E177A

1"

CORRIDOR E114

3/4"

SIMULATION 2 E113B

LAB SUPPORT E119

A V NC NCCA N

3

TEAM STATION 1 E115

WOMEN E177

FOOD SERVICE E120

608 SF

93 SF

1.

1-1/4" NON-CLINICAL AIR UP TO SECOND FLOOR.

2.

PROVIDE ISIMET SOLENIOD ENCLOSURE MODEL S-1311-3-3/4-1-S FOR NON-CLINICAL GASES. CONNECT SOLENIOD VALVES TO ISIMET CONTROL PANELS. REFER TO ELECTRICAL SHEET E212 FOR PANEL LOCATIONS AND SHEET E601 FOR DETAILS.

3.

ONE (1) 3/4" NON-CLINICAL VACUUM AND TWO (2) 1/2" NON-CLINICAL AIR DOWN TO EACH SIDE OF SIMULATION BED TO SUPPLY NON-CLINICAL OUTLETS/INLET. REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR OUTLETS/INLET TYPES AND ORIENTATION.

4.

VALVE AND CAP 1" NON-CLINICAL VACUUM FOR FUTURE CONNECTION.

5.

VALVE AND CAP 3/4" NON-CLINICAL AIR FOR FUTURE CONNECTION.

1

EXTERIOR CIRCULATION E184 DINING E122A

376 SF

3

DRAWING KEYNOTES:

1

S

NORTH CAMPUS SIMULATION LAB FLORIDA STATE COLLEGE AT JACKSONVILLE

SK

S

SERVICE E123

4501 Capper Rd. Jacksonville, FL 32218 S

CULINARY LAB E121

DINING E122

SS a Sb

1054 SF

1220 SF

BID REVIEW

D

SK

NOT FOR CONSTRUCTION

E187 LAB SERVICE E121A Revision

1/3/2017 2:23:20 PM

C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt

No. 1

1

FIRST FLOOR SIMULATION GAS PLAN 1/8" = 1'-0"

0'

4'

8'

16'

24'

Date 01/04/17

Description Addendum 2

FIRST FLOOR SIMULATION GAS PLANS

P501 PROJECT: 42390.00 DATE: November 21, 2016

Author

Checker

Approver

Drawn By:

Checked By:

Approved By:

G S & P Design Services For The Built Environment Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS

R

Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL

GRESHAM SMITH AND PARTNERS

BOILER ROOM E201

ELEC. E203

MECHANICAL (HVAC) E202

1252 SF

1012 SF

177 SF

ELEVATOR EQUIPMENT E204

225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699

75 SF

COVERED WALKWAY E206

NCA-1

FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381

ELEV E249

1-1/4" NCA DOWN TO FIRST FLOOR

1 1/4" NCA

WORK RM E211

WORK AREA E210 123 SF

108 SF

OFFICE E207B

OFFICE E207A

102 SF

106 SF

MONITOR CHECK-IN E209

OFFICE E213 130 SF

E207

123 SF

CORR E212 WAITING/ REC E216

OPEN LAB E214 83 SF

OPEN LAB E215

WALK-IN TESTING E217

84 SF

ROOF BELOW

90 SF

OFFICE E216 130 SF

NORTH CAMPUS SIMULATION LAB

E224

GROUP TESTING E218 90 SF

CORR. E220

MECH E225A 90 SF

E226 OPEN TO BELOW

CULINARY LAB E225

FLORIDA STATE COLLEGE AT JACKSONVILLE 4501 Capper Rd. Jacksonville, FL 32218

EXTERNAL CIRCULATION COVERED WALKWAY E248

1116 SF

OPEN BELOW (MALLARD ROOM) BID REVIEW NOT FOR CONSTRUCTION

OPEN BELOW (CAFETERIA) E244 OPEN TO BELOW

Revision

1/3/2017 2:23:20 PM

C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt

No.

1

Date

Description

SECOND FLOOR MEDICAL GAS PLAN 1/8" = 1'-0"

0'

4'

8'

16'

24'

SECOND FLOOR SIMULATION GAS PLANS

P502 PROJECT: 42390.00 DATE: November 21, 2016

Author

Checker

Approver

Drawn By:

Checked By:

Approved By:

1

G S & P CLEANOUT RATED FOR EXPECTED WHEEL LOADING REFER TO SPECIFICATIONS AND PLANS FOR TYPE AND LOCATIONS

Design Services For The Built Environment

TOP FLUSH WITH FINISHED FLOOR NOTE: REFER TO SPECIFICATIONS FOR PIPE MATERIALS AND JOINTS.

FINISHED FLOOR LEVEL

Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS

CL

VERTICAL PIPING REFER TO PLANS FOR SIZE AND LOCATION.

C L

FULL PIPE SIZE EXTENSION UP TO 6", LENGTH AS REQUIRED. PROVIDE SAME SIZE AS LINE SERVED UP TO 6" REFER TO SPECIFICATIONS AND FLOOR PLANS FOR SIZE AND TYPE OF MATERIAL

SLOTTED FLUSH TYPE BRASS CLOSURE PLUG TAPPED SANITARY "TEE" FITTING. PROVIDE EXTENSION WHERE REQUIRED. FINISHED FLOOR LEVEL

FINISHED WALL FACE. REFER TO ARCHITECTURAL DRAWINGS FOR CONSTRUCTION DETAIL CLEANOUT ACCESS COVER PLATE. REFER TO SPECIFICATIONS.

12" ABOVE FINISHED FLOOR LEVEL OR AS OTHERWISE SPECIFIED AND REQUIRED BY CODE.

LONG SWEEP 1/4 BEND 225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699 FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381

REFER TO PLANS FOR THE FITTING REQUIRED FOR EACH INSTALLATION AND DIRECTION OF FLOW.

FLOW

1

SP01 INTERIOR CLEANOUT DETAIL NOT TO SCALE

Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL

GRESHAM SMITH AND PARTNERS

COMBINATION WYE AND 1/8 BEND OR AS CODE REQUIRED

C L

R

C L

FLOW

FLOW

2

C L

SP04 WALL CLEANOUT DETAIL NOT TO SCALE

STRUT MOUNTED IPS PIPE STRAP ALL-THREAD CONTINUOUS, ONE PIECE HANGER ROD. COUPLING OF RODS IS NOT PERMITTED

PIPING INSULATION. DO NOT CRUSH

TYPICAL 10 GAUGE GALVANIZED SHEET METAL SADDLE. REFER TO SPECIFICATIONS 12 GAUGE CHANNEL STRUT WITH SLOTS

PIPING. ( 3 OR MORE PIPES )

LOCKING NUT WITH SINGLE WASHER. TYPICAL TOP AND BOTTOM OF STRUT

4

LENGTH AS REQUIRED BY QUANTITY AND SIZE OF PIPES

NORTH CAMPUS SIMULATION LAB

SP44 TRAPEZE PIPE HANGER DETAIL

FLORIDA STATE COLLEGE AT JACKSONVILLE

NOT TO SCALE

4501 Capper Rd. Jacksonville, FL 32218

2" x 2" x 3/16", ANGLE (MINIMUM), TACK WELD TO TOP CHORD OF BAR JOIST

TOP CHORD OF BAR JOIST - REFER TO STRUCTURE DRAWINGS BEAM CLAMP C-TYPE BEAM CLAMP

ATTACHED METHOD "A"

BID REVIEW LOCKING SCREW

NOT FOR CONSTRUCTION

LOCKING NUT WITH SINGLE WASHER

ALL THREAD HANGER ROD

BAR JOIST ATTACHMENT METHOD "A" ( AT BAR JOISTS )

ATTACHMENT METHOD "B" ( BETWEEN BAR JOISTS ) ALL THREAD HANGER ROD LOCKING NUT

WASHER ON BOTH SIDES

LOCKING NUT

No.

CLEVIS HANGER

1

C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt 1/3/2017 2:23:21 PM

Revision Date 01/04/17

Description Addendum 2

PIPE RIGID INSULATION 10 GAUGE GALVANIZED SHEET METAL SADDLE REFER TO SPECIFICATIONS FOR REQUIREMENTS

CLEVIS HANGER SINGLE HORIZONTAL RUNS WITH INSULATION CLEVIS HANGER SINGLE HORIZONTAL RUNS WITH NO INSULATION

HANGER ROD SCHEDULE PIPE SIZE

ROD SIZE

PIPE SIZE

ROD SIZE

UP TO 2"

3/8" DIA.

4" THRU 5"

5/8" DIA.

2 1/2" THRU 3"

1/2" DIA.

6" THRU 12"

7/8" DIA.

PLUMBING DETAILS COUPLING OF RODS IS NOT PERMITTED

5

SP43 CLEVIS PIPE HANGER DETAIL NOT TO SCALE

P801 PROJECT: 42390.00 DATE: November 21, 2016