SYSTEM ABBREVIATIONS BFF
BELOW FINISHED FLOOR
BFG
BELOW FINISHED GRADE
CFM
CUBIC FEET PER MINUTE
CI
CAST IRON
1.
THE CONTRACTOR SHALL SCHEDULE ALL WORK IN A MANNER TO MAINTAIN THE OWNER'S CONTINUOUS USE OF THE BUILDING.
2.
THE CONTRACTOR SHALL COORDINATE ALL NECESSARY INTERRUPTION OF BUILDING SERVICES WITH OWNER, GENERAL CONTRACTOR, UTILITY COMPANIES, AND ALL AFFECTED PARTIES.
3. CO
CLEANOUT
CW
COLD WATER DRAINAGE FIXTURE UNITS
DN
DOWN
EA
EACH
ELECT
ELECTRICAL
FC
FINAL CONNECT
FD
FLOOR DRAIN
FE
FIRE EXTINGUISHER
FEC
FIRE EXTINGUISHER CABINET
FF
FINISHED FLOOR
FLR MTD
FLOOR MOUNTED
FT
FEET
5.
6. 7.
8.
FT HD
FEET OF HEAD
FV
FLUSH VALVE
GN
GOOSENECK
GPH
GALLONS PER HOUR
GPM
GALLONS PER MINUTE
HP
HORSE POWER
HW
HOT WATER
HWR
HOT WATER RETURN
IE
INVERT ELEVATION
IN
INCHES
LPA
LINE PRESSURE ALARM
MECH
MECHANICAL
MSA
MULTI-SIGNAL ALARM
MU
MAKE-UP
NCA
NON-CLINCAL AIR
NCV
NON-CLINCAL VACUUM
OFE
OWNER FURNISHED EQUIPMENT
PRV
PRESSURE REDUCING VALVE
RI
ROUGH-IN
SAN
SANITARY WASTE
SCFM
STANDARD CUBIC FEET PER MINUTE
SS
STAINLESS STEEL
TOC
TOP OF COVER
TOS
TOP OF STEEL
VB
VACUUM BREAKER
VTR
VENT THRU ROOF
WB
WRIST BLADE
WCO
WALL CLEANOUT
WH
WALL HUNG
SCHEMATIC SYMBOL
DOMESTIC COLD WATER PIPING
HW
DOMESTIC HOT WATER PIPING
HWR
THE DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER TRADES AND WITH THE NEW CONSTRUCTION PLANS FOR THE EXACT SCOPE OF WORK AND ALL PHASING REQUIREMENTS.
G S & P
SYMBOL DESCRIPTION
CW
R
Design Services For The Built Environment
DOMESTIC HOT WATER RETURN PIPING SANITARY VENT PIPING
SAN 4.
DFU
PLUMBING SYMBOL LEGEND
GENERAL DEMOLITION NOTES
EXISTING PLUMBING FIXTURES INDICATED SHALL REMAIN AS IS UNLESS OTHERWISE NOTED ON THE CONTRACT DOCUMENTS.
SANITARY WASTE PIPING EXISTING PIPING TO BE REMOVED EXISTING PIPING TO REMAIN
REMOVE ALL EXISTING PLUMBING FIXTURES AS INDICATED ON THE CONTRACT DOCUMENTS. REMOVAL OF PLUMBING FIXTURES SHALL INCLUDE AT A MINIMUM THE REMOVAL OF CONNECTED PIPING TO BEHIND NEW ARCHITECTURAL FINISHES.
BALL VALVE SOLENOID VALVE
THE REMOVAL OF EXISTING FIXTURES, EQUIPMENT, AND PIPING SHALL ALSO INCLUDE THE REMOVAL OF ALL ASSOCIATED HANGERS, ANCHORS, PADS, ETC.
#
PLUMBING FIXTURES REMOVED MAY BE REUSED PROVIDED THEY ARE CLEANED, RECONDITIONED, AND CONFORM EXACTLY TO THAT SPECIFIED. THE OWNER'S REPRESENTATIVE TO MAKE FINAL DECISION AS TO THE FIXTURE'S ACCEPTANCE.
REFER TO DRAWING KEYNOTE POINT OF NEW CONNECTION
EXISTING FIXTURES AND MATERIALS REMOVED BUT NOT REINSTALLED SHALL BE OFFERED TO THE OWNER FOR RETAINMENT OR DISPOSAL UPON THEIR DISCRETION.
NCA
NON-CLINICAL AIR PIPING
NCV
NON-CLINICAL VACUUM PIPING
Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS
GRESHAM SMITH AND PARTNERS
NON-CLINICAL ZONE VALVE BOX 9.
EXISTING VERTICAL PIPING DISCOVERED IN WALLS OR CHASES DURING DEMOLITION SHALL BE REWORKED TO OFFSET INTO NEW WALLS, CHASES, ETC. AND RECONNECTED TO MAINTAIN SERVICES AS REQUIRED IN THE FLOORS ABOVE AND BELOW.
10.
PLUMBING SERVICES FOR EXISTING EQUIPMENT SCHEDULED FOR REMOVAL SHALL BE DISCONNECTED AND CAPPED BEHIND NEW FINISHES. FLOOR DRAINS SERVING EQUIPMENT SHALL BE REMOVED AND THE FLOOR PATCHED TO MATCH EXISTING SURFACES.
Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL
225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699 FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381
GENERAL PLUMBING NOTES 1.
THE CONTRACTOR SHALL SCHEDULE ALL WORK IN A MANNER TO MAINTAIN THE OWNER'S CONTINUOUS USE OF THE BUILDING.
2.
THE CONTRACTOR SHALL COORDINATE ALL NECESSARY INTERRUPTION OF BUILDING SERVICES WITH OWNER, GENERAL CONTRACTOR, UTILITY COMPANIES, AND ALL AFFECTED PARTIES.
3.
ALL WORK SHALL BE COORDINATED WITH ALL OTHER TRADES.
4.
THE CONTRACTOR SHALL COORDINATE WITH ALL EQUIPMENT MANUFACTURERS AND OWNER TO DETERMINE EXACT SCOPE OF WORK AND MATERIALS NECESSARY FOR PROPER INSTALLATION AND OPERATION.
5.
THE CONTRACTOR SHALL MAINTAIN PROPER CLEARANCE ABOVE AND 42" IN FRONT OF ALL ELECTRICAL/ELECTRONIC EQUIPMENT INCLUDING BUT NOT LIMITED TO PANELS, STARTERS, TRANSFORMER, ETC.
6.
IF PIPING ENCROACHES UPON PROPER CLEARANCES AND 42 INCHES IN FRONT OF ELECTRICAL/ELECTRONIC EQUIPMENT, WHETHER NEW OR EXISTING CONDITIONS, THE PIPING SHALL BE REWORKED TO RUN OUTSIDE RESTRICTED AREA.
7.
COORDINATE ALL SLAB PENETRATIONS AND SLAB RECESSES WITH STRUCTURAL.
8.
COORDINATE ALL UTILITY BUILDING EXIT/ENTRANCE POINTS WITH SITE UTILITY CONTRACTOR. COORDINATION SHALL INCLUDE EXACT POINTS OF EXIT/ENTRANCE, INVERT ELEVATIONS, PIPE SIZES, ETC.
9.
ALL PIPE ROUTING (DOMESTIC WATER, SANITARY WASTE AND VENT, MEDICAL GASES, ETC.) SHALL BE COORDINATED WITH MECHANICAL DUCTWORK AND PIPING, ELECTRICAL LIGHTING LAYOUTS, ARCHITECTURAL CEILING HEIGHTS, ETC.
10.
11.
12.
13.
ALL SANITARY WASTE AND RAIN WATER LEADER PIPING LINE SIZE 3" AND LARGER SHALL BE SLOPED AT 1/8 INCH FALL PER FOOT AND LINE SIZES 2-1/2" AND SMALLER SHALL BE SLOPED AT 1/4 INCH FALL PER FOOT. ALL VENTS THRU ROOF WILL BE OFF-SET AS REQUIRED TO MAINTAIN THE FOLLOWING DISTANCES: MECHANICAL FRESH AIR INTAKE 25 FEET ADJACENT VERTICAL WALLS WITH WINDOWS 25 FEET ADJACENT VERTICAL WALLS WITHOUT WINDOWS 10 FEET EDGE OF BUILDING 5 FEET ALL PLUMBING FIXTURES, GROUPS OF PLUMBING FIXTURES, AND EQUIPMENT WITH FLUSH VALVES AND/OR QUICK CLOSING VALVES SHALL BE PIPE WITH SEALED SHOCK ABSORBERS. SIZE AND PLACEMENT SHALL BE PER PLUMBING DRAINAGE INSTITUTE RECOMMENDATIONS AND REQUIREMENTS. ALL PLUMBING FIXTURES AND/OR EQUIPMENT CONNECTIONS THAT HAVE THE POTENTIAL FOR BACK SIPHONAGE INTO THE DOMESTIC WATER SYSTEM SHALL BE PROTECTED WITH A BACKFLOW PREVENTION DEVICE AS REQUIRED BY LOCAL CODE REQUIREMENTS.
14.
COORDINATE EXACT LOCATION OF ALL FLOOR DRAINS WITH OWNER FURNISHED EQUIPMENT BEING SERVED, HVAC EQUIPMENT, AND LOCATIONS INDICATED ON ARCHITECTURAL FLOOR PLANS FOR SLOPING REQUIREMENTS.
15.
SAWCUT EXISTING FLOOR SLABS AS REQUIRED FOR NEW PIPING INSTALLATION. REPAIR FLOOR SLAB TO MATCH EXISTING CONDITIONS AFTER INSTALLATION OF NEW PIPING.
1
PLUMBING ADD ALTERNATES GENERAL: THE PLUMBING ADD ALTERNATES EFFECT MULTIPLE SHEETS. REFER TO ARCHITECTURAL DRAWINGS FOR ADD ALTERNATE DRAWINGS. PLUMBING ADD ALTERNATE 1: PROVIDE WALL HUNG 10 LBS. ABC FIRE EXTINGUISHER IN RECEPTION AREA. PROVIDE JUST NUMBER SLADA-1921-A-GR, SINGLE COMPARTMENT 18 GAGE STAINLESS STEEL SINK, 19 INCHES O.D. BY 21 INCHES O.D. BY 5-1/2 INCHES I.D. DEEP COMPARTMENT. CHICAGO FAUCET NUMBER 786-GN2AFCCP, GOOSENECK FAUCET WITH 4 INCH WRIST CONTROL HANDLES, 1.5 GPM LAMINAR FLOW IN BASE OF SPOUT AND PLAIN END TRIM. MCGUIRE NUMBER 1149WC, BRASS FLAT GRID SINK STRAINER WITH 1-1/2 INCH TAILPIECE OFFSET FOR ACCESSIBLE USE. MCGUIRE NUMBER 8912, 1-1/2 INCH SEMICAST BRASS P-TRAP WITH CLEANOUT PLUG, PIPED PARALLEL TO WALL. MCGUIRE NUMBER BV175, SUPPLIES WITH WHEEL HANDLE STOP. CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM SINK TO EXISTING MAINS ABOVE THE CEILING AND PROVIDE BALL VALVES ON NEW BRANCH PIPING. CONNECT NEW 2" SANITARY WASTE FROM SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING. PLUMBING ADD ALTERNATE 2: PROVIDE WALL HUNG 10 LBS. ABC FIRE EXTINGUISHER IN STORAGE ROOM AND IN LIVING/KITCHEN AREA. PROVIDE JUST NUMBER DL-1829-A-GR, DOUBLE COMPARTMENT 18 GAGE STAINLESS STEEL SINK, 12 INCHES I.D. BY 12 INCHES I.D. BY 7-1/2 INCHES I.D. DEEP COMPARTMENTS. KOHLER NUMBER K-15173-PT, SINGLE LEVER FAUCET, 10" SPOUT REACH, HOSE SPRAY MOUNTED IN ESCUTCHEON. MCGUIRE NUMBER 151, BASKET STRAINERS WITH 1-1/2 INCH TAILPIECE. MCGUIRE NUMBER 8912, 1-1/2 INCH SEMI-CAST BRASS P-TRAP WITH CLEANOUT PLUG. MCGUIRE NUMBER 111C16G17, 1-1/2 INCH CONTINUOUS WASTE WITH REQUIRED END OUTLET LENGTH. MCGUIRE NUMBER BV175, SUPPLIES WITH WHEEL HANDLE STOP. PROVIDE KOHLER NUMBER K-3889-T(TR), 1.28 GALLON VITREOUS CHINA SIPHON JET, FLOOR MOUNTED FLUSH TANK, WATER CLOSET WITH TWO BOLT CAPS AND TANK COVER LOCKS. KOHLER NUMBER K-4670-C, ELONGATED PLASTIC, OPEN FRONT SEAT WITH CHECK HINGE. TANK HANDLE TO BE MOUNTED ON "MOST OPEN" SIDE OF WATER CLOSET. ONE (1) MCGUIRE MANUFACTURING COMPANY, INC., NUMBER BV172, SUPPLY WITH QUARTER TURN WITH CONVERTIBLE LOOSE KEY HANDLE. PROVIDE KOHLER NUMBER K-505 LEFT OUTLET, OR K-506 RIGHT OUTLET, ENAMELED CAST IRON BATHTUB, AS SHOWN ON CONTRACT DRAWINGS. SYMMONS TEMPTROL NUMBER S-96-600-B30-LR-X-CHKS, PRESSURE BALANCING VALVE WITH INTEGRAL DIVERTER, 2.5 GPM, FIXED SHOWER HEAD, TUB SPOUT, HAND SHOWER, LEVER HANDLE, 30 INCH SLIDE BAR, AND INTEGRAL CHECK STOPS. EBC, INC. NUMBER WB150T, 1-1/2 INCH TUB DRAIN AND OVERFLOW. FURNISH AND INSTALL REQUIRED 1-1/2 INCH P-TRAP (2 INCHES WHEN BATHTUB ON GRADE). PROVIDE P321 IN MILLWORK IN RESTROOM. CONNECT NEW 3/4" COLD WATER AND HOT WATER FROM EXISTING MAINS ABOVE THE CEILING AND CONNECT TO NEW FIXTURES. PROVIDE BALL VALVES ON NEW BRANCH PIPING. CONNECT NEW 2" SANITARY WASTE FROM SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING.
1
NORTH CAMPUS SIMULATION LAB
PLUMBING ADD ALTERNATE 3: PROVIDE WALL HUNG 10 LBS. ABC FIRE EXTINGUISHER LOCATED IN A CABINET IN THE CORRIDOR.
FLORIDA STATE COLLEGE AT JACKSONVILLE
PROVIDE P321 IN MILLWORK IN SIMULATION 5. CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM EXISTING MAINS ABOVE THE CEILING AND CONNECT TO NEW FIXTURE. PROVIDE BALL VALVES ON NEW BRANCH PIPING. PROVIDE ISIMET SOLENOID ENCLOSURE MODEL S-1311-2-1/2-S ABOVE CEILING FOR DOMESTIC WATER TO P321 . CONNECTSOLENOID VALVES TO ISIMET CONTROL PANELS IN CONTROL ROOM. CONNECT NEW 2" SANITARY WASTE FROM SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING. CONNECT 1" NON-CLINICAL VACUUM AND 3/4" NON-CLINICAL AIR TO VALVED AND CAPPED STUB-OUTS PROVIDED IN BASE BID. ROUTE NEW PIPING THROUGH NEW ZONE VALVE BOX OUTSIDE SIMULATION 5 AND ROUTE TO OUTLETS/INLETS LOCATIONS AS SHOWN ON ARCHITECTURAL ELEVATIONS. PROVIDE ISIMET SOLENOID ENCLOSURE MODEL S-1311-3-3/4-1-S ABOVE CEILING FOR NON-CLINICAL GASES. CONNECT SOLENOID VALVES TO ISIMET CONTROL PANELS IN CONTROL ROOM.
4501 Capper Rd. Jacksonville, FL 32218
PLUMBING ADD ALTERNATE 4: PROVIDE WALL HUNG 10 LBS. ABC FIRE EXTINGUISHER LOCATED IN A CABINET IN THE WORKROOM. PROVIDE JUST NUMBER SLADA-1921-A-GR, SINGLE COMPARTMENT 18 GAGE STAINLESS STEEL SINK, 19 INCHES O.D. BY 21 INCHES O.D. BY 5-1/2 INCHES I.D. DEEP COMPARTMENT. CHICAGO FAUCET NUMBER 786-GN2AFCCP, GOOSENECK FAUCET WITH 4 INCH WRIST CONTROL HANDLES, 1.5 GPM LAMINAR FLOW IN BASE OF SPOUT AND PLAIN END TRIM. MCGUIRE NUMBER 1149WC, BRASS FLAT GRID SINK STRAINER WITH 1-1/2 INCH TAILPIECE OFFSET FOR ACCESSIBLE USE. MCGUIRE NUMBER 8912, 1-1/2 INCH SEMICAST BRASS P-TRAP WITH CLEANOUT PLUG, PIPED PARALLEL TO WALL. MCGUIRE NUMBER BV175, SUPPLIES WITH WHEEL HANDLE STOP.
BID REVIEW
CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM SINK TO EXISTING MAINS ABOVE THE CEILING AND PROVIDE BALL VALVES ON NEW BRANCH PIPING.
NOT FOR CONSTRUCTION
CONNECT NEW 2" SANITARY WASTE FROM SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING. PLUMBING ADD ALTERNATE 5: PROVIDE P321 IN MILLWORK IN EXAM 1 AND EXAM 2. CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM EXISTING MAINS ABOVE THE CEILING AND CONNECT TO NEW FIXTURE IN EXAM 1. PROVIDE BALL VALVES ON NEW BRANCH PIPING. PROVIDE ISIMET SOLENOID ENCLOSURE MODEL S-1311-2-1/2-S ABOVE CEILING FOR DOMESTIC WATER TO P321 . CONNECT SOLENOID VALVES TO ISIMET CONTROL PANELS IN CONTROL ROOM. CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM EXISTING MAINS ABOVE THE CEILING AND CONNECT TO NEW FIXTURE IN EXAM 2. PROVIDE BALL VALVES ON NEW BRANCH PIPING. PROVIDE ISIMET SOLENOID ENCLOSURE MODEL S-1311-2-1/2-S ABOVE CEILING FOR DOMESTIC WATER TO P321 . CONNECT SOLENOID VALVES TO ISIMET CONTROL PANELS IN CONTROL ROOM.
1/3/2017 2:23:12 PM
C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt
CONNECT NEW 2" SANITARY WASTE FROM EACH SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING. PLUMBING ADD ALTERNATE 6:
Revision No. 1
Date 01/04/17
Description Addendum 2
PROVIDE P321 IN MILLWORK IN TEAM STATION 1. CONNECT NEW 1/2" COLD WATER AND HOT WATER FROM SINK TO EXISTING MAINS ABOVE THE CEILING AND PROVIDE BALL VALVES ON NEW BRANCH PIPING. CONNECT NEW 2" SANITARY WASTE FROM SINK TO EXISTING 4" SANITARY SEWER UNDER SLAB AND CONNECT 2" SANITARY VENT TO EXISTING 3" VENT UP ABOVE CEILING.
PLUMBING & MEDICAL GENERAL NOTES & LEGENDS
P001 PROJECT: 42390.00 DATE: November 21, 2016
PLUMBING FIXTURE SPECIFICATIONS
Approver
Checker
Author
GAS WATER HEATER SCHEDULE Approved By:
1
WH-1
LAVATORY (INTEGRAL , GN, ACCESSIBLE, COUNTERTOP FURNISHED BY OTHERS) INTEGRAL COUNTERTOP TOP AND LAVATORY BOWL FURNISHED BY INTERIORS AND INSTALLED BY CONTRACTOR. CONTRACTOR SHALL FURNISH AND INSTALL THE FOLLOWING: CHICAGO FAUCET NUMBER 895-317GN2FCCP, 4-INCH CENTER GOOSENECK FAUCET WITH 4 INCH WRIST CONTROL HANDLES AND 1.5 GPM LAMINAR FLOW CONTROL DEVICE AT BASE OF SPOUT. MCGUIRE MANUFACTURING, INC., NUMBER 155WC, 1-1/4 INCH GRID DRAIN WITH TAILPIECE, OFFSET FOR ACCESSIBLE USE. MCGUIRE MANUFACTURING, INC., NUMBER 8872, 1-1/4 INCH CAST BRASS P-TRAP WITH CLEANOUT PLUG. P-TRAP PIPED PARALLEL TO WALL. MCGUIRE MANUFACTURING, INC., NUMBER BV175, SUPPLIES WITH QUARTER-TURN BRASS BALL VALVE STOPS.
INPUT RATING
VOLTAGE / PHASE
GALLONS STORAGE
E.W.T.
L.W.T.
FLOW RECOVERY IN GPH
LOCATION
199,999 BTUH/7"-14" WC
120/1
90
40°
120°
233
JANITOR
MANUFACTURER / MODEL NUMBER LOCHINVAR / SNA201-100
G S & P R
Design Services For The Built Environment
REMARKS:
Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS
1
Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL
GRESHAM SMITH AND PARTNERS 225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699 FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381
PUMP SCHEDULE PUMP DATA MARK
MANUFACTURER
MOTOR DATA
PUMP MODEL PUMP DISCHARGE
FLOW RATE
FLUID PUMPED
RECEIVER GALLONS
HORSEPOWER
VOLT/PHASE
R.P.M.
NCVP-1
BEACON MEDAES
VDV05D-080V-D
19" HG
21 CFM
AIR
80
5 H.P.
460/3
----
NCAP-1
BEACON MEDAES
SAS10D-120V-D
50 PSI
34.8 CFM
AIR
120
10 H.P.
460/3
----
REMARKS:
FIXTURE CONNECTION SCHEDULE CONNECTION SIZES TAG P321
DESCRIPTION LAVATORY (INTEGRAL, GN, ACCESSIBLE, COUNTERTOP FURNISHED BY OTHERS)
WASTE
CW
HW
1 1/2"
1/2"
1/2"
1
NORTH CAMPUS SIMULATION LAB FLORIDA STATE COLLEGE AT JACKSONVILLE 4501 Capper Rd. Jacksonville, FL 32218
BID REVIEW NOT FOR CONSTRUCTION
Revision C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt
No.
1/3/2017 2:23:13 PM
Checked By:
Drawn By:
P321
TAG
1
Date 01/04/17
Description Addendum 2
PLUMBING SCHEDULES & SPECIFICATIONS
P002 PROJECT: 42390.00 DATE: November 21, 2016
Author
Checker
Approver
Drawn By:
Checked By:
Approved By:
G S & P R
Design Services For The Built Environment
STOR/ LAUNDRY E102
FREEZER E107
LOADING DOCK E100A
IDF E102A
REF E108
SAN
133 SF
M E104
FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381
160 SF
3" G 2 1/2"
6"
2"
CW
69 SF
OFFICE E103A
OFFICE E103
CW
CORR 2 1/2" E100
STOR E110
CW HW
LAB SUPPORT E111
225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699
ELEVATOR E190
W E105
121 SF
GRESHAM SMITH AND PARTNERS
GARBAGE E101
8 SF
FREEZER E109
Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL
127 SF
STOR E106
81 SF
Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS
1 1/2"
1
3"
MECH E182
SAN
151 SF
4"
STOR E181 177 SF
SAN
402 SF
1 1/2"
1 1/2" 4"
1 4
4" HW CW
2
EXTERIOR CIRCULATION E183
SAN
CULINARY ARTS2 LAB 1 E114
N SA
CULINARY SERVICE E113
CATERING LAB E179
523 SF
515 SF
1 4"
MEN LOCKER E175
1651 SF
2 2 2
2" CW
1 4
RELATED INSTRUCTION E117
3
1
2
WOMEN LOCKER E176
1224 SF
CORR. E124A
1
M I( C D L K N IS lin 2 U , )T IY L
CULINARY ARTS LAB E116
SAN
254 SF
DISHWASHING 2 E118
6
1 4
3
2
JANITOR E177A
211 SF
225 amp PANEL
LAB SUPPORT E115
K
S
LAB SUPPORT E119 FOOD SERVICE E120
66 SF
608 SF
N SA
93 SF
WOMEN E177
DRAWING KEYNOTES:
EXTERIOR CIRCULATION E184 DINING E122A
376 SF
4"
3"
1
1.
DEMOLISH EXISTING FIXTURE AND ASSOCIATED PIPING BACK TO MAINS AND CAP.
2.
DEMOLISH EXISTING FLOOR DRAIN/FLOOR SINK AND ASSOCIATED PIPING BACK TO MAIN AND CAP.
3.
DEMOLISH EXISTING TRENCH DRAIN AND ASSOCIATED PIPING BACK TO MAIN AND CAP.
4.
DEMOLISH EXISTING VENT PIPING BACK TO RISER UP TO SECOND FLOOR AND CAP. RISER SHALLL REMAIN.
NORTH CAMPUS SIMULATION LAB FLORIDA STATE COLLEGE AT JACKSONVILLE
S
SK
S
SERVICE E123
4501 Capper Rd. Jacksonville, FL 32218
S
CULINARY LAB E121 1220 SF
DINING E122
SS a Sb
1054 SF 4"
4" SAN
SAN
BID REVIEW
D
SK
NOT FOR CONSTRUCTION
E187 LAB SERVICE E121A Revision
1/3/2017 2:23:13 PM
C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt
No. 1
1
FIRST FLOOR DEMOLITION 1/8" = 1'-0"
0'
4'
8'
16'
24'
Date 01/04/17
Description Addendum 2
FIRST FLOOR DEMOLITION
P121 PROJECT: 42390.00 DATE: November 21, 2016
Author
Checker
Approver
Drawn By:
Checked By:
Approved By:
G S & P R
Design Services For The Built Environment Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS
LOADING DOCK E100A LP
FREEZER E107
STOR E106
LP
REF E108
W E105
121 SF
STOR E110
69 SF
ELEVATOR E190
6"
225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699
OFFICE E103A
OFFICE E103 133 SF
M E104
GRESHAM SMITH AND PARTNERS
FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381
160 SF
SAN
FREEZER E109
GARBAGE E101
IDF 102
LP
Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL
1
1 CR
MECH E182
LAB SUPPORT E111
151 SF 4"
3"
STOR E181 177 SF
3" SAN
4"
SAN
402 SF
4" 4" 4"
SIMULATION 3 E112A
1 2"
N SA
EXTERIOR CIRCULATION E183
SAN
CR
CONTROL 2 E112 1
4"
MEN LOCKER E175
1651 SF
SIMLUATION 4 E112B N SA
SIMULATION 1 E113A
1
CATERING LAB E179
2"
CR
FCO
4"
WOMEN LOCKER E176
SAN 2" 1
CONTROL 1 E113
1
K
S
JANITOR E177A
CORRIDOR E114
TEAM STATION 1 E115
LAB SUPPORT E119
SAN
SIMULATION 2 E113B
1.
M I( C D L K N IS lin 2 U , )T IY L
4"
CR
CORRIDOR E114.1
DRAWING KEYNOTES:
FOOD SERVICE E120
1
NORTH CAMPUS SIMULATION LAB
EXTERIOR CIRCULATION E184 DINING E122A
376 SF 4"
WOMEN E177
608 SF
93 SF
CONNECT NEW 2" SANITARY TO EXISTING IN THIS APPROXIMATE LOCATION.
S
FLORIDA STATE COLLEGE AT JACKSONVILLE
SK
4" S
SERVICE E123
S
4501 Capper Rd. Jacksonville, FL 32218
CULINARY LAB E121 1220 SF
DINING E122
SS a Sb
1054 SF 4"
4" SAN
SK
BID REVIEW D
NOT FOR CONSTRUCTION
E187 LAB SERVICE E121A
Revision
1/3/2017 2:23:15 PM
C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt
No. 1
1
Date 01/04/17
Description Addendum 2
FIRST FLOOR UNDERGOUND PLAN 1/8" = 1'-0"
0'
4'
8'
16'
24'
FIRST FLOOR UNDERGOUND
P201 PROJECT: 42390.00 DATE: November 21, 2016
Author
Checker
Approver
Drawn By:
Checked By:
Approved By:
G S & P R
Design Services For The Built Environment Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS
LOADING DOCK E100A LP
FREEZER E107
STOR E106
LP
REF E108
69 SF
STOR E110
OFFICE E103 133 SF
M E104
160 SF
1
LAB SUPPORT E111
FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381
OFFICE E103A
MECH E182
CR
FREEZER E109
225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699
ELEVATOR E190
W E105
121 SF
GRESHAM SMITH AND PARTNERS
GARBAGE E101
IDF 102
LP
151 SF
402 SF
Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL
1
STOR E181 177 SF
2
SIMULATION 3 E112A
2"
EXTERIOR CIRCULATION E183
2"
CR
2"
CATERING LAB E179
CONTROL 2 E112 2"
MEN LOCKER E175
1651 SF 1
SIMLUATION 4 E112B
SIMULATION 1 E113A 1
DRAWING KEYNOTES: 2"
WOMEN LOCKER E176
CR
2"
CONTROL 1 E113
JANITOR E177A
LAB SUPPORT E119
WOMEN E177
NORTH CAMPUS SIMULATION LAB
EXTERIOR CIRCULATION E184 DINING E122A
376 SF
FOOD SERVICE E120 1
CONNECT NEW 2" VENT TO EXISTING 2" VENT UP IN THIS APPROXIMATE LOCATION.
K
CORRIDOR E114
TEAM STATION 1 E115
2.
S
2
SIMULATION 2 E113B
CAP EXISTING VENT PIPING ABOVE CEILING IN THIS APPROXIMATE LOCATION.
1
M I( C D L K N IS lin 2 U , )T IY L
CR
CORRIDOR E114.1
2"
1.
608 SF
93 SF
FLORIDA STATE COLLEGE AT JACKSONVILLE
S
SK
S
SERVICE E123
4501 Capper Rd. Jacksonville, FL 32218 S
CULINARY LAB E121
DINING E122
SS a Sb
BID REVIEW
1054 SF
1220 SF
D
SK
NOT FOR CONSTRUCTION
E187 LAB SERVICE E121A
Revision
1/3/2017 2:23:16 PM
C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt
No. 1
1
FIRST FLOOR GRAVITY PLAN 1/8" = 1'-0"
0'
4'
8'
16'
Date 01/04/17
Description Addendum 2
FIRST FLOOR GRAVITY
24'
P301 PROJECT: 42390.00 DATE: November 21, 2016
Author
Checker
Approver
Drawn By:
Checked By:
Approved By:
G S & P R
Design Services For The Built Environment Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS
LOADING DOCK E100A LP
FREEZER E107
STOR E106
LP
REF E108 121 SF 2 1/2"
FREEZER E109 69 SF
225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699
ELEVATOR E190
W E105
OFFICE E103
M E104
FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381
OFFICE E103A
133 SF
CW
STOR E110
GRESHAM SMITH AND PARTNERS
GARBAGE E101
IDF 102
LP
Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL
160 SF
3" G
CW
2 1/2"
LAB SUPPORT E111
MECH E182
CR
2" CW HW
1
1 1/2"
2 1/2"
177 SF
1 1/4"
HW CW
402 SF
151 SF
STOR E181
1 1/2"
1 1/2"
SIMULATION 3 E112A
1
EXTERIOR CIRCULATION E183
2 1/2" P321 1
1/2" CR
2
1/2"
1
CATERING LAB E179
CONTROL 2 E112
MEN LOCKER E175
1651 SF
1/2" P321
2
1 1/2"
P321
2"
1 1/2"
CR
1/2"
SIMLUATION 4 E112B
CW
SIMULATION 1 E113A
WOMEN LOCKER E176
1/2" 2
CONTROL 1 E113
P321 M I( C D L K N IS lin 2 U , )T IY L
CR
CORRIDOR E114.1
JANITOR E177A
LAB SUPPORT E119
TEAM STATION 1 E115
1.
CONNECT NEW 1/2" CW AND 1/2" HW TO EXISTING MAINS. FEILD VERIFY EXACT CONNECTION POINT.
2.
PROVIDE ISIMET SOLENIOD ENCLOSURE MODEL S-1311-2-1/2-S FOR DOMESTIC WATER. CONNECT SOLENIOD VALVES TO ISIMET CONTROL PANELS. REFER TO ELECTRICAL SHEET E212 FOR PANEL LOCATIONS AND SHEET E601 FOR DETAILS.
K
S
CORRIDOR E114
SIMULATION 2 E113B
DRAWING KEYNOTES:
1
WOMEN E177
EXTERIOR CIRCULATION E184 DINING E122A
376 SF
FOOD SERVICE E120
608 SF
93 SF
NORTH CAMPUS SIMULATION LAB FLORIDA STATE COLLEGE AT JACKSONVILLE
S
SK
S
SERVICE E123 4501 Capper Rd. Jacksonville, FL 32218 S
CULINARY LAB E121
DINING E122
SS a Sb
1054 SF
BID REVIEW
1220 SF
D
SK
NOT FOR CONSTRUCTION
E187 LAB SERVICE E121A Revision
1/3/2017 2:23:17 PM
C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt
No. 1
1
FIRST FLOOR PLUMBING PLAN 1/8" = 1'-0"
0'
4'
8'
16'
Date 01/04/17
Description Addendum 2
FIRST FLOOR PLUMBING
24'
P401 PROJECT: 42390.00 DATE: November 21, 2016
Author
Checker
Approver
Drawn By:
Checked By:
Approved By:
G S & P Design Services For The Built Environment
BOILER ROOM E201
ELEC. E203
MECHANICAL (HVAC) E202
1252 SF
1012 SF WH-1
DEMOLISH EXISTING NATURAL GAS WATER HEATER AND REPLACE WITH WH-1. RECONNECT EXISTING PIPING TO NEW WATER HEATER AND SET DISCHARGE TEMPERATURE TO MATCH EXISTING SETTING
WORK RM E211
177 SF
ELEVATOR EQUIPMENT E204
WORK AREA E210 123 SF
COVERED WALKWAY E206
OFFICE E207B
OFFICE E207A
102 SF
106 SF
MONITOR CHECK-IN E209
130 SF
75 SF
ELEV E249
Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL
GRESHAM SMITH AND PARTNERS 225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699 FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381
108 SF
OFFICE E213
Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS
R
E207
123 SF
OPEN LAB E214 83 SF
OPEN LAB E215
CORR E212 WAITING/ REC E216
WALK-IN TESTING E217
84 SF
ROOF BELOW
90 SF
OFFICE E216 130 SF
E224
GROUP TESTING E218 90 SF
CORR. E220
MECH E225A 90 SF
E226 OPEN TO BELOW
CULINARY LAB E225
EXTERNAL CIRCULATION COVERED WALKWAY E248
1116 SF
OPEN BELOW (MALLARD ROOM)
NORTH CAMPUS SIMULATION LAB FLORIDA STATE COLLEGE AT JACKSONVILLE 4501 Capper Rd. Jacksonville, FL 32218
OPEN BELOW (CAFETERIA) E244 BID REVIEW
OPEN TO BELOW
NOT FOR CONSTRUCTION
Revision
1/3/2017 2:23:18 PM
C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt
No.
1
Date
Description
SECOND FLOOR PLUMBING PLAN 1/8" = 1'-0"
0'
4'
8'
16'
24'
SECOND FLOOR PLUMBING
P402 PROJECT: 42390.00 DATE: November 21, 2016
Author
Checker
Approver
Drawn By:
Checked By:
Approved By:
G S & P R
Design Services For The Built Environment Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS
LOADING DOCK E100A LP
FREEZER E107
STOR E106
LP
REF E108
69 SF
STOR E110
OFFICE E103 133 SF
M E104 NCA
1
160 SF
3
MECH E182
1 1/4" 5
LAB SUPPORT E111
FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381
OFFICE E103A
CR
FREEZER E109
225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699
ELEVATOR E190
W E105
121 SF
GRESHAM SMITH AND PARTNERS
GARBAGE E101
IDF 102
LP
Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL
1 1/4" NCV
151 SF
STOR E181 1 1/4"
NCVP-1 NCV
177 SF 1"
1
4
402 SF
NCV
NCA
1 1/4"
SIMULATION 3 E112A
3/4"
EXTERIOR CIRCULATION E183
ZVB 2
3
2
1" 3
3/4"
3/4" CR
ZVB
1/2"
CATERING LAB E179
CONTROL 2 E112
1"
MEN LOCKER E175
1651 SF A NC V NC
SIMULATION 1 E113A
SIMLUATION 4 E112B
ZVB CR
3/4"
3/4"
1" 3/4"
CONTROL 1 E113
3 2
CORRIDOR E114.1
CR
2
3/4" M I( C D L K N IS lin 2 U , )T IY L
ZVB 1/2"
WOMEN LOCKER E176
1/2"
K
S
JANITOR E177A
1"
CORRIDOR E114
3/4"
SIMULATION 2 E113B
LAB SUPPORT E119
A V NC NCCA N
3
TEAM STATION 1 E115
WOMEN E177
FOOD SERVICE E120
608 SF
93 SF
1.
1-1/4" NON-CLINICAL AIR UP TO SECOND FLOOR.
2.
PROVIDE ISIMET SOLENIOD ENCLOSURE MODEL S-1311-3-3/4-1-S FOR NON-CLINICAL GASES. CONNECT SOLENIOD VALVES TO ISIMET CONTROL PANELS. REFER TO ELECTRICAL SHEET E212 FOR PANEL LOCATIONS AND SHEET E601 FOR DETAILS.
3.
ONE (1) 3/4" NON-CLINICAL VACUUM AND TWO (2) 1/2" NON-CLINICAL AIR DOWN TO EACH SIDE OF SIMULATION BED TO SUPPLY NON-CLINICAL OUTLETS/INLET. REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR OUTLETS/INLET TYPES AND ORIENTATION.
4.
VALVE AND CAP 1" NON-CLINICAL VACUUM FOR FUTURE CONNECTION.
5.
VALVE AND CAP 3/4" NON-CLINICAL AIR FOR FUTURE CONNECTION.
1
EXTERIOR CIRCULATION E184 DINING E122A
376 SF
3
DRAWING KEYNOTES:
1
S
NORTH CAMPUS SIMULATION LAB FLORIDA STATE COLLEGE AT JACKSONVILLE
SK
S
SERVICE E123
4501 Capper Rd. Jacksonville, FL 32218 S
CULINARY LAB E121
DINING E122
SS a Sb
1054 SF
1220 SF
BID REVIEW
D
SK
NOT FOR CONSTRUCTION
E187 LAB SERVICE E121A Revision
1/3/2017 2:23:20 PM
C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt
No. 1
1
FIRST FLOOR SIMULATION GAS PLAN 1/8" = 1'-0"
0'
4'
8'
16'
24'
Date 01/04/17
Description Addendum 2
FIRST FLOOR SIMULATION GAS PLANS
P501 PROJECT: 42390.00 DATE: November 21, 2016
Author
Checker
Approver
Drawn By:
Checked By:
Approved By:
G S & P Design Services For The Built Environment Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS
R
Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL
GRESHAM SMITH AND PARTNERS
BOILER ROOM E201
ELEC. E203
MECHANICAL (HVAC) E202
1252 SF
1012 SF
177 SF
ELEVATOR EQUIPMENT E204
225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699
75 SF
COVERED WALKWAY E206
NCA-1
FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381
ELEV E249
1-1/4" NCA DOWN TO FIRST FLOOR
1 1/4" NCA
WORK RM E211
WORK AREA E210 123 SF
108 SF
OFFICE E207B
OFFICE E207A
102 SF
106 SF
MONITOR CHECK-IN E209
OFFICE E213 130 SF
E207
123 SF
CORR E212 WAITING/ REC E216
OPEN LAB E214 83 SF
OPEN LAB E215
WALK-IN TESTING E217
84 SF
ROOF BELOW
90 SF
OFFICE E216 130 SF
NORTH CAMPUS SIMULATION LAB
E224
GROUP TESTING E218 90 SF
CORR. E220
MECH E225A 90 SF
E226 OPEN TO BELOW
CULINARY LAB E225
FLORIDA STATE COLLEGE AT JACKSONVILLE 4501 Capper Rd. Jacksonville, FL 32218
EXTERNAL CIRCULATION COVERED WALKWAY E248
1116 SF
OPEN BELOW (MALLARD ROOM) BID REVIEW NOT FOR CONSTRUCTION
OPEN BELOW (CAFETERIA) E244 OPEN TO BELOW
Revision
1/3/2017 2:23:20 PM
C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt
No.
1
Date
Description
SECOND FLOOR MEDICAL GAS PLAN 1/8" = 1'-0"
0'
4'
8'
16'
24'
SECOND FLOOR SIMULATION GAS PLANS
P502 PROJECT: 42390.00 DATE: November 21, 2016
Author
Checker
Approver
Drawn By:
Checked By:
Approved By:
1
G S & P CLEANOUT RATED FOR EXPECTED WHEEL LOADING REFER TO SPECIFICATIONS AND PLANS FOR TYPE AND LOCATIONS
Design Services For The Built Environment
TOP FLUSH WITH FINISHED FLOOR NOTE: REFER TO SPECIFICATIONS FOR PIPE MATERIALS AND JOINTS.
FINISHED FLOOR LEVEL
Atlanta GA Birmingham AL Charlotte NC Cincinnati OH Columbus OH Dallas TX Ft Lauderdale FL Houston TX Jackson MS
CL
VERTICAL PIPING REFER TO PLANS FOR SIZE AND LOCATION.
C L
FULL PIPE SIZE EXTENSION UP TO 6", LENGTH AS REQUIRED. PROVIDE SAME SIZE AS LINE SERVED UP TO 6" REFER TO SPECIFICATIONS AND FLOOR PLANS FOR SIZE AND TYPE OF MATERIAL
SLOTTED FLUSH TYPE BRASS CLOSURE PLUG TAPPED SANITARY "TEE" FITTING. PROVIDE EXTENSION WHERE REQUIRED. FINISHED FLOOR LEVEL
FINISHED WALL FACE. REFER TO ARCHITECTURAL DRAWINGS FOR CONSTRUCTION DETAIL CLEANOUT ACCESS COVER PLATE. REFER TO SPECIFICATIONS.
12" ABOVE FINISHED FLOOR LEVEL OR AS OTHERWISE SPECIFIED AND REQUIRED BY CODE.
LONG SWEEP 1/4 BEND 225 Water Street Suite 2200 Jacksonville, FL 32202 904.332.6699 FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381
REFER TO PLANS FOR THE FITTING REQUIRED FOR EACH INSTALLATION AND DIRECTION OF FLOW.
FLOW
1
SP01 INTERIOR CLEANOUT DETAIL NOT TO SCALE
Jacksonville FL Knoxville TN Louisville KY Memphis TN Miami FL Nashville TN Richmond VA Tallahassee FL Tampa FL
GRESHAM SMITH AND PARTNERS
COMBINATION WYE AND 1/8 BEND OR AS CODE REQUIRED
C L
R
C L
FLOW
FLOW
2
C L
SP04 WALL CLEANOUT DETAIL NOT TO SCALE
STRUT MOUNTED IPS PIPE STRAP ALL-THREAD CONTINUOUS, ONE PIECE HANGER ROD. COUPLING OF RODS IS NOT PERMITTED
PIPING INSULATION. DO NOT CRUSH
TYPICAL 10 GAUGE GALVANIZED SHEET METAL SADDLE. REFER TO SPECIFICATIONS 12 GAUGE CHANNEL STRUT WITH SLOTS
PIPING. ( 3 OR MORE PIPES )
LOCKING NUT WITH SINGLE WASHER. TYPICAL TOP AND BOTTOM OF STRUT
4
LENGTH AS REQUIRED BY QUANTITY AND SIZE OF PIPES
NORTH CAMPUS SIMULATION LAB
SP44 TRAPEZE PIPE HANGER DETAIL
FLORIDA STATE COLLEGE AT JACKSONVILLE
NOT TO SCALE
4501 Capper Rd. Jacksonville, FL 32218
2" x 2" x 3/16", ANGLE (MINIMUM), TACK WELD TO TOP CHORD OF BAR JOIST
TOP CHORD OF BAR JOIST - REFER TO STRUCTURE DRAWINGS BEAM CLAMP C-TYPE BEAM CLAMP
ATTACHED METHOD "A"
BID REVIEW LOCKING SCREW
NOT FOR CONSTRUCTION
LOCKING NUT WITH SINGLE WASHER
ALL THREAD HANGER ROD
BAR JOIST ATTACHMENT METHOD "A" ( AT BAR JOISTS )
ATTACHMENT METHOD "B" ( BETWEEN BAR JOISTS ) ALL THREAD HANGER ROD LOCKING NUT
WASHER ON BOTH SIDES
LOCKING NUT
No.
CLEVIS HANGER
1
C:\tmp\RevitLocal\4239000_Central_Plumb_2016_karaszd.rvt 1/3/2017 2:23:21 PM
Revision Date 01/04/17
Description Addendum 2
PIPE RIGID INSULATION 10 GAUGE GALVANIZED SHEET METAL SADDLE REFER TO SPECIFICATIONS FOR REQUIREMENTS
CLEVIS HANGER SINGLE HORIZONTAL RUNS WITH INSULATION CLEVIS HANGER SINGLE HORIZONTAL RUNS WITH NO INSULATION
HANGER ROD SCHEDULE PIPE SIZE
ROD SIZE
PIPE SIZE
ROD SIZE
UP TO 2"
3/8" DIA.
4" THRU 5"
5/8" DIA.
2 1/2" THRU 3"
1/2" DIA.
6" THRU 12"
7/8" DIA.
PLUMBING DETAILS COUPLING OF RODS IS NOT PERMITTED
5
SP43 CLEVIS PIPE HANGER DETAIL NOT TO SCALE
P801 PROJECT: 42390.00 DATE: November 21, 2016