D6600

Computer Interface Manual

EN

Receiver/Gateway

D6600 | Computer Interface Manual | Trademarks

Trademarks Microsoft®, Windows®, Windows NT® are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries. Modem IIIa2 is a trademark of Bosch Security Systems, Inc.

2

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Contents .

Contents 1.0 2.0 2.1 2.2 3.0 3.1 3.2 4.0 4.1 4.1.1 4.1.2 4.1.3 4.1.4 4.1.5 4.1.6 4.1.7 4.1.8 4.1.9 4.1.10 4.1.11 4.1.12 4.1.13 4.1.14 4.1.15 4.1.16 4.1.17 4.1.18 4.1.19 4.1.20 4.1.21 4.1.22 4.1.23 4.1.24 4.1.25 4.1.26 4.1.27 4.1.28 4.1.29 4.1.30 4.2 4.2.1

Documentation Conventions.........................7 System Connection ..........................................7 D6680 Network Adapter Connection ..............7 Direct Connection – RS-232 .............................8 Making the Right Connection.......................8 COM3 DB9 Connector .....................................8 Selecting Program Options in the D6600 ........9 Computer Communication Protocols........10 D6500 Mode Messages ....................................10 Acron Super Fast (Message Type 9)...............10 Ademco 4-1 Express (Message Type b).........11 Ademco 4-2 Express (Message Type c) .........11 Ademco Contact-ID (Message ♦Type a) .......12 Ademco High Speed, 4-8-1 (Message Type f)...............................................12 ADT SIA (Message Type S) ............................13 Caller ID (Message Type e).............................13 CFSK (Message Type i) ...................................14 Common Formats (Message Type 1) .............14 DNIS/ANI (Message Type N) ........................15 DSC 4-3 (Message Type d)..............................15 FBI Super Fast (Message Type F) ...................16 ITI (Message Type I)........................................16 Link Test (Message Type 1) ............................16 Robofon (Message Type j)...............................17 Sescoa Super Speed (Message Type 7) ..........18 Scancom 4-16-1, 5-16-1, 6-16-1 - Available Upon Request (Message Type g) ....................19 Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h)....................20 Seriee FSK (Message Type k)..........................21 Seriee DTMF (Message Type l) ......................21 SIA (Message Type S) ......................................22 Silent Knight FSK0 (Message Type 1) ...........22 Silent Knight FSK2 (Message Type m) ..........25 Silent Knight FSK80 D6500 mode (Message Type E) .............................................25 Telim (Message Type n) ..................................26 Text Message (Message Type 3) .....................26 Varitech FSK 4-1 (Message Type 1)...............27 Varitech FSK 4-2 (Message Type 1)...............27 VONK (Message Type V)...............................28 X-SIA Text (Message Type S).........................28 SIA Mode Messages.........................................29 Acron Super Fast (Message Type 9)...............29

Bosch Security Systems | 1/05 | 4998122703D

4.2.2 4.2.3 4.2.4 4.2.5

Ademco Contact-ID (Message Type a) ......... 30 Ademco 4-1 Express (Message Type b) ........ 31 Ademco 4-2 Express (Message Type c)......... 32 Ademco High Speed 4-8-1, SCANCOM 4-8-1 (Message Type f) .............................................. 33 4.2.6 ADT SIA (Message Type ) ................ 34 4.2.7 Caller ID (Message Type ) ................ 34 4.2.8 CFSK (Message Type I) .................................. 35 4.2.9 Common Formats (Message Type )................................................... 35 4.2.10 DNIS/ANI (Message Type N)........................ 36 4.2.11 DSC 4-3 (Message Type d) ............................. 37 4.2.12 FBI Super Fast (Message Type F) .................. 38 4.2.13 ITI (Message Type I) ....................................... 39 4.2.14 Link Test (Message Type ) ................ 39 4.2.15 RB2000 (Message Type R) Description ........ 40 4.2.16 Robofon (Message Type j) .............................. 41 4.2.17 Scancom 4-16-1, 5-16-1, 6-16-1 - Available Upon Request (Message Type g) ................... 41 4.2.18 Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) ................... 42 4.2.19 Seriee DTMF (Message Type l)...................... 43 4.2.20 Seriee FSK (Message Type k) ......................... 43 4.2.21 Sescoa Super Speed (Message Type 7).......... 44 4.2.22 Silent Knight FSK() (Message Type )................................................... 45 4.2.23 Silent Knight FSK1 (Message Type m).......... 45 4.2.24 Silent Knight FSK2 (Message Type m).......... 47 4.2.25 Silent Knight FSK80 (Message Type E) ........ 48 4.2.26 Telim (Message Type n).................................. 49 4.2.27 Varitech FSK 4-1 (Message Type )................................................... 49 4.2.28 Varitech FSK 4-2 (Message Type )... 50 4.2.29 VONK (Message Type V) .............................. 50 4.2.30 X-SIA text (Message Type ) .............. 51 4.3 Input Command Processing ........................... 52 4.3 Input Command Processing ........................... 52 Appendix A: Contact ID Event Code Classifications ................................................. 53 Appendix B: Internal Messages................................ 58 Appendix C: Radionics Modem IIIa2 Messages.... 61 C.1 Bosch Security Systems Zonex and COMEX Translation ..................................... 140 Appendix D: NetCom Messages............................. 141 Appendix E: Pulse Output ....................................... 144 Appendix F: Format ID (Identified by Message Type)............................................................... 149 Appendix G: ADT SIA Report Codes................... 152

3

D6600 | Computer Interface Manual | Contents Appendix H: D6600 RB2000 Messages ..................154 Appendix I: D6600 SafeCom Messages.................161

Table 9: Table 10:

Figures Figure 1: Figure 2: Figure 3: Figure 4: Figure 5: Figure 6: Figure 7: Figure 8: Figure 9: Figure 10: Figure 11: Figure 12: Figure 13: Figure 14: Figure 15: Figure 16: Figure 17: Figure 18: Figure 19: Figure 20: Figure 21: Figure 22: Figure 23:

Table 11: D6600 System – Standard/Network Automation ..................................................7 D6600 System – Direct Connect ...............8 Null Modem Cable Configuration ............8 Straight-through Modem Cable Configuration ...............................................8 Modem Cable Pin Definitions ...................9 Message sent to printer .............................29 Message sent to printer .............................30 Message sent to printer .............................31 Message sent to printer .............................32 Message sent to printer .............................33 Message sent to printer .............................36 Message sent to printer .............................37 Message sent to printer .............................38 Single message sent to Printer..................40 Multiple messages sent to printer ............40 Message sent to printer .............................42 Message sent to printer .............................42 Message sent to printer .............................44 Message sent to printer .............................48 Message sent to printer .............................51 Contact ID format .....................................53 D6200 Receiver Software Line Card Configuration ...........................................144 SafeCom message characters .................161

Tables Table 1: Table 2: Table 3: Table 4: Table 5: Table 6: Table 7: Table 8:

4

Recommended Programming Selections..9 D6600 Line Number/Group Number Conversion Table ......................................10 Message Type 9 (Acron Super Fast) Byte Description .................................................10 Message Type b (Ademco 4-1 Express) Byte Description ........................................11 Message Type c (Ademco 4-2 Express) Byte Description ........................................11 Message Type a (Ademco Contact ID) Byte Description ........................................12 Message Type f (Ademco High Speed, 4-81) Byte Description....................................12 ADT SIA (Message Type S) Byte Description .................................................13

Table 12: Table 13: Table 14: Table 15: Table 16: Table 17: Table 18: Table 19:

Table 20:

Table 21: Table 22: Table 23: Table 24: Table 25: Table 26: Table 27: Table 28: Table 29: Table 30: Table 31: Table 32: Table 33: Table 34:

Caller ID (Message Type e) Byte Description ................................................ 13 CFSK (Message Type i) Byte Description ................................................ 14 Common Formats (Message Type 1) Byte Description ................................................ 14 DNIS/ANI (Message Type N) Byte Description ................................................ 15 DSC-4-3 (Message Type d) Byte Description ................................................ 15 FBI Super Fast (Message Type F) Byte Description ................................................ 16 ITI (Message Type I) Byte Description.. 16 Link Test (Message Type 1) Byte Description ................................................ 17 Robofon (Message Type j) Byte Description ................................................ 17 Sescoa Super Speed (Message Type 7) Byte Description........................................ 18 Scancom 4-16-1, 5-16-1, 6-16-1 - Available Upon Request (Message Type g) Byte Description ................................................ 19 Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) Byte Description ................................................ 20 Seriee FSK (Message Type k) Byte Description ................................................ 21 Seriee DTMF (Message Type l) Byte Description ................................................ 21 SIA (Message Type S) Byte Description 22 Silent Knight FSK1 (Message Type m) Byte Description........................................ 22 Optional Silent Knight SK1 (Message Type m) Byte Description........................ 23 Silent Knight Automation Format .......... 24 Silent Knight FSK2 (Message Type m) Byte Description........................................ 25 Silent Knight FSK80 (Message Type E) Byte Description........................................ 25 Telim (Message Type n) Byte Description .................................................................... 26 Text Message (Message Type 3) Byte Description ................................................ 26 Varitech FSK 4-1 (Message Type 1) Byte Description ................................................ 27 Varitech FSK 4-2 (Message Type 1) Byte Description ................................................ 27 VONK (Message Type V) Byte Description ................................................ 28 X-SIA Text (Message Type S) Byte Description ................................................ 28 Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Contents . Table 35: Table 36: Table 37: Table 38: Table 39: Table 40: Table 41: Table 42: Table 43: Table 44: Table 45: Table 46: Table 47: Table 48: Table 49: Table 50: Table 51: Table 52: Table 53: Table 54: Table 55: Table 56: Table 57: Table 58: Table 59: Table 60: Table 61:

Acron Super Fast (Message Type 9) Byte Description .................................................29 Acron Super Fast (Message Type 9) Printer Output............................................29 Ademco Contact-ID (Message Type a) Byte Description ........................................30 Ademco Contact-ID (Message Type a) Printer Output............................................30 Ademco 4-1 Express (Message Type b) Byte Description ........................................31 Ademco 4-1 Express (Message Type b) Printer Output............................................31 Ademco 4-2 Express (Message Type c) Byte Description ........................................32 Ademco 4-2 Express (Message Type c) Printer Output............................................32 Ademco High Speed 4-8-1, SCANCOM 48-1 (Message Type F) Byte Description ..33 Ademco High Speed, 4-8-1 (Message Type f) Printer Output ........................................33 ADT SIA (Message Type ) Byte Description .................................................34 Caller ID (Message Type ) Byte Description .................................................34 CFSK (Message Type I) Byte Description .................................................35 Common Formats (Message Type ) Byte Description ........................35 DNIS/ANI (Message Type N) Byte Description .................................................36 DSC 4-3 (Message Type d) Byte Description .................................................37 DSC 4-3 (Message Type d) Printer Output.........................................................37 Event Code Table .....................................37 Printer Output Codes................................37 FBI Super Fast (Message Type F) Byte Description .................................................38 FBI Super Fast (Message Type F) Printer Output.........................................................38 Event Code Table .....................................38 Printer Output Codes................................38 ITI (Message Type I) Byte Description ..39 Link Test (Message Type ) Description .................................................39 RB2000 (Message Type R) Byte Description .................................................40 RB2000 (Message Type R) Printer Output .....................................................................40

Bosch Security Systems | 1/05 | 4998122703D

Table 62: Table 63:

Table 64:

Table 65:

Table 66:

Table 67: Table 68: Table 69: Table 70: Table 71: Table 72: Table 73: Table 74: Table 75: Table 76: Table 77: Table 78: Table 79: Table 80: Table 81: Table 82: Table 83: Table 84: Table 85: Table 86:

Robofon (Message Type j) Byte Description ................................................ 41 Scancom 4-16-1, 5-16-1, 6-16-1 - Available Upon Request (Message Type g) Byte Description ................................................ 41 Scancom 4-16-1, 5-16-1, 6-16-1 - Available Upon Request (Message Type g) Printer Output ........................................................ 42 Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) Byte Description ................................................ 42 Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) Printer Output ........................................................ 42 Seriee DTMF (Message Type l) Byte Description ................................................ 43 Seriee FSK (Message Type k) Byte Description ................................................ 43 Sescoa Super Speed (Message Type 7) Byte Description........................................ 44 Sescoa Super Speed (Message Type 7) Printer Output ........................................... 44 Silent Knight FSK0 (Message Type ) Byte Description........................ 45 Silent Knight FSK1 (Message Type m) Byte Description........................................ 45 Optional Silent Knight FSK1 (Message Type m) Byte Description........................ 46 Silent Knight FSK1 Optional Outputs.... 46 Silent Knight FSK2 (Message Type m) Byte Description........................................ 47 Silent Knight FSK80 (Message Type E) Byte Description........................................ 48 Silent Knight FSK80 Printer/LCD output ......................................................... 48 Telim (Message Type n) Byte Description ................................................ 49 Varitech FSK 4-1 (Message Type ) Byte Description........................................ 49 Varitech FSK 4-2 (Message Type ) Byte Description........................................ 50 VONK (Message Type V) Byte Description ................................................ 50 X-SIA text (Message Type ) Byte Description ................................................ 51 X-SIA Printer/LCD output ...................... 51 ASCII Text Message to Automation Port ............................................................. 52 Input Command Output Messages......... 52 Event Codes .............................................. 53

5

D6600 | Computer Interface Manual | Contents Table 87: Table 88: Table 89: Table 90: Table 91: Table 92: Table 93: Table 94: Table 95: Table 96: Table 97: Table 98: Table 99: Table 100: Table 101: Table 102: Table 103: Table 104: Table 105: Table 106: Table 107: Table 108: Table 109: Table 110: Table 111: Table 112:

6

Internal Messages ......................................58 Radionics Modem IIIa2 Messages ...........61 Point to ZONEX Translation.................140 User ID to COMEX Translation...........140 Reported Zone/ID to Actual Point/ID .140 NetCom Messages...................................141 Pulse 3/1 Format .....................................144 Pulse 3/1E Menu 3.1.3.12 3-1 Extended Format = 1 ...............................................145 Pulse 3/1E Menu 3.1.3.12 3-1 Extended Format = 2 ...............................................145 Pulse 3/2 ...................................................146 Pulse 4/1 ...................................................146 Pulse 4/1E Menu 3.1.3.3 4/1 Extended = 1 ...........................................147 Pulse 4/1E Menu 3.1.3.3 4/1 Extended = 2 ...........................................147 Pulse 4/2 ...................................................148 Pulse 4/3 ...................................................148 Generic Byte Description .......................149 Generic SIA Byte Description ...............149 Message Examples ..................................150 ADT SIA Report Codes .........................152 D6600 RB2000 Messages .......................154 D6600 Virtual Line Conversion Table .161 D6600 SafeCom Messages - Line Card or Account Signals .......................................162 D6600 SafeCom Messages - Intercepted Control Panel Signals..............................165 Explanation of Automation Output Items (within Message Body only) ...................167 Explanation of Printer Output Items ....168 Supported Event Codes..........................169

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Contents .

1.0 Documentation Conventions Important Notes - Information for successful operation and programming. Also tips and shortcuts can be included here. Caution - These caution the operator that physical damage to the program or equipment might occur.

2.0 System Connection 2.1

D6680 Network Adapter Connection

Use the D6680 Network Adapter to connect a manufacturer’s automation software package to the D6600 when the software cannot receive network data (Figure 1). Refer to Special Bosch Security Systems D6600 NetCom Applications in the D6600 NetCom System Guide (P/N: 4998122712). Figure 1:

D6600 System – Standard/Network Automation

Warning - These warn of the possibility of physical damage to the operator.

1 2

3 4

5 6 7 8 12345678*

Bosch Security Systems | 1/05 | 4998122703D

Automation PC Connection - PC COM1 to D6680 D6680 Connection - D6680 to hub Hub Second D6680 Connection - D6680 to D6600 COM4 D6600 Receiver For automation packages with network capabilities: The packet format received from the D6600 is the same as for RS-232 reporting, execpt an internet protocol (IP) and user datagram protocol (UDP) header is stamped on the packet as the data transmitted by either standard IP or UDP structure over the network. Automation software can support the network communication easily by calling Socket functions, both provided in Windows and Unix. by using the built-in IP connections (or sockets) available in Windows and Unix.

7

D6600 | Computer Interface Manual | 3.0

2.2

Making the Right Connection

Direct Connection – RS-232

Figure 2 show a D6600-System using any manufacturer’s automation software package directly connected to a D6600 Receiver.

3.0 Making the Right Connection 3.1

Figure 2:

D6600 System – Direct Connect

COM3 DB9 Connector

The COM3 Port uses a standard DB9 female connector. The suggested connection to the computer is shown in Figure 3 to Figure 5. When connecting data terminal equipment (DTE) together (such as a COM1 port to PC serial port), a null-modem cable must be used. One possible configuration for a null modem cable is shown in Figure 3.

1

2

Figure 3:

3

1 - Automation PC 2 - Connection - Automation PC COM1 to D6600 Receiver COM3 3 - D6600 Receiver

Null Modem Cable Configuration DTE DB-9 Pin

DTE DB-9 Pin

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

When connecting data terminal equipment to data communication equipment (DCE) (such as the D6600 COM port to a modem), a modem cable should be used (such as a straight-through cable shown in Figure 4). Figure 4:

8

Straight-through Modem Cable Configuration DTE

DCE

1

8

2

3

3

2

4

20

5

7

6

6

7

4

8

5

9

22

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Contents . Each pin of the modem cable is defined in Figure 5. Figure 5:

Modem Cable Pin Definitions 1

2 6

1 - Data carrier detect (DCD) 2 - Receive (RX) 3 - Transmit (TX) 4 - Data terminal ready (DTR) 5 - Signal-ground (SIG-GND)

3.2

3 7

4 8

5 9

6 - Data set ready (DSR) 7 - Ready to send (RTS) 8 - Clear to send (CTS) 9 - Ring indicator (RI)

Selecting Program Options in the D6600

Use the D6600 Keypad or the D6200 Programming Software to program the receivers. Below are the recommended selections for programming when connecting the receivers to an automation system. Additional selections can be found in the D6600 Program Entry Guide (P/N: 4998122702). Table 1:

ReceiverGateway Number Output Format

Baud Rate Link Test

Recommended Programming Selections Selects a number (01 to 99) that is included in every message to the computer in both D6500 and SIA modes Enable computer output messages in the selected format: SIA computer interface standard format, recommended (expanded reporting capabilities) D6500 21-character format output Use maximum speed supported by PC Tests if a supervision signal can be sent and received from the central station by the receiver

Bosch Security Systems | 1/05 | 4998122703D

9

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.0 Computer Communication Protocols 4.1

D6500 Mode Messages

In D6500 Mode, the line number/group number sent to the computer is only one digit. Refer to Table 2. Table 2:

D6600 Line Number/Group Number Conversion Table

Line# /Group # L01/G01 L02/G02 L03/G03 L04/G04 L05/G05 L06/G06 L07/G07 L08/G08

Converted to 1 2 3 4 5 6 7 8

Line# /Group # L09/G09 L10/G10 L11/G11 L12/G12 L13/G13 L14/G14 L15/G15 L16/G16

Converted to 9 A B C D E F G

Line # /Group # L17/G17 L18/G18 L19/G19 L20/G20 L21/G21 L22/G22 L23/G23 L24/G24

Converted to H I J K L M N O

Line # /Group # L25/G25 L26/G26 L27/G27 L28/G28 L29/G29 L30/G30 L31/G31 L32/G32

Converted to P Q R S T U V W

In D6500 mode, any group that equals 33 is converted to an “X.” Any group greater than or equal to 34 is converted to a “Y.” For lines that are grouped, Gxx appears instead of Lxx. For networked accounts, Nxx appears instead of Lxx and the line number is identified. 4.1.1

Acron Super Fast (Message Type 9)

Acron Super Fast Example

Table 3: # 1 2 3-4 5 6-9 10-13 14-21 22

10

D6500 Byte Description 1 h

2 9

3 r

4 r

5 l

6 s

7 s

8 s

9 s

10 a

11 a

12 a

13 a

14 C

15 C

16 C

17 C

18 C

19 C

20 C

21 C

22 t

Message Type 9 (Acron Super Fast) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number Channels Trailer Character

Description Optional. Check with the computer automation software for compatibility. 9 Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Six spaces Account number, four digits Channels 1 to 8 Typically, this is HEX 14.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0 . 4.1.2

Ademco 4-1 Express (Message Type b)

4-1 Express Example

Table 4: # 1 2 3-4 5 6-11 12-15 16 17 18-20 21 22

4.1.3

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

h

b

r

r

l

s

s

s

s

s

s

a

a

a

a

s

E

s

s

s

X

t

Message Type b (Ademco 4-1 Express) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number Space E Spaces X Trailer Character

Description Optional. Check with the computer automation software for compatibility. b Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message. Six spaces Account number, four digits One space Event Code, “A” as the default. Three spaces Zone number Typically, this is HEX 14.

Ademco 4-2 Express (Message Type c)

4-2 Express Example

Table 5: # 1 2 3-4 5 6-11 12-15 16 17 18-19 20-21 22

Computer Communication Protocols

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

h

c

r

r

l

s

s

s

s

s

s

a

a

a

a

s

E

s

s

X

Y

t

Message Type c (Ademco 4-2 Express) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number Space E Spaces XY Trailer Character

Description Optional. Check with the computer automation software for compatibility. c Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Six spaces Account number, four digits One space Event Code, “A” as the default. Two spaces Event code and zone number Typically, this is HEX 14.

Bosch Security Systems | 1/05 | 4998122703D

11

D6600 | Computer Interface Manual | 4.0 4.1.4

Ademco Contact-ID (Message •Type a)

Contact ID Example

Table 6:

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

h

a

r

r

l

s

a

a

a

a

1

8

Q

X

Y

Z

G

G

C

C

C

t

Message Type a (Ademco Contact ID) Byte Description

# 1 2 3-4 5 6 7-10 11-12 13 14-16 17-18 19-21 22

4.1.5

Computer Communication Protocols

Title Header Character (h) Message Type Receiver Number Line/Group Number Space Account Number 18 Qualifier XYZ GG CCC Trailer Character

Description Optional. Check with the computer automation software for compatibility. a Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message One space Account number, four digits Ademco Contact-ID format number Qualifier, 1=New event or opening, 3=New restore or closing, 6=Previous event Class code and event code (see Appendix A) Group number Zone codes or user ID Typically, this is HEX 14.

Ademco High Speed, 4-8-1 (Message Type f) SCANCOM 4-8-1, 5-8-1, 6-8-1 - Available Upon Request

High Speed Example

Table 7:

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

h

f

r

r

l

a

a

a

a

a

s

C

C

C

C

s

C

C

C

C

s

C

t

Message Type f (Ademco High Speed, 4-8-1) Byte Description

# 1 2 3-4 5 6-11

Title Header Character (h) Message Type Receiver Number Line/Group Number Account Number

12 13-16 17 18-21 22 23 24

Space CCCC Space CCCC Space C Trailer Character

12

a

Description Optional. Check with the computer automation software for compatibility. f Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Account number, up to six digits Account number less than six characters is right aligned with leading ASCII spaces. One space Channels 1 to 4 One space Channels 5 to 8 One space Supervisory channel Typically, this is HEX 14.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0 . 4.1.6

ADT SIA (Message Type S)

ADT SIA Example

Table 8: # 1 2 3-4 5 6 7 8-11 12 13-32 33 34-35 36-39 40 41 42

4.1.7

Computer Communication Protocols

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

h

S

r

r

l

[

#

a

a

a

a

|

d

a

m

m

-

d

d

-

y

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

y

t

I

h

h

:

m

m

:

s

s

E

M

M

Z

Z

Z

Z

/

** *

t

ADT SIA (Message Type S) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number space # Account Number | Date and Time E Event Code Zone / *** Trailer Character

Description Optional. Check with the computer automation software for compatibility. S Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message. One space # Up to sixteen digits in the account number. Separator. Indicates more data positions after account number. Date and time SIA block code SIA event code (refer to Appendix G ADT SIA Report Codes on page 152) Zone number Separator Next block of data Typically, this is HEX 14.

Caller ID (Message Type e)

Caller ID Example

Table 9:

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

e

r

r

1

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

t

Caller ID (Message Type e) Byte Description

# 1 2 3-4 5 6-21

Title Header Character (h) Message Type Receiver Number Line/Group Number Caller ID

22

Trailer Character

Description Optional. Check with the computer automation software for compatibility. e Receiver gateway Number from 01 to 99 Line number in the receiver gateway that sent the message Up to sixteen digits, Caller ID with less than sixteen characters is right aligned with leading ASCII spaces. Typically, this is HEX 14.

Bosch Security Systems | 1/05 | 4998122703D

13

D6600 | Computer Interface Manual | 4.0 4.1.8

CFSK (Message Type i)

CFSK Example

Table 10: # 1 2 3-4 5 6-9 10-15 16-17 18-19 20-21 22

4.1.9

Computer Communication Protocols

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

i

r

r

l

s

s

s

s

a

a

a

a

a

a

T

T

E

E

s

s

t

CFSK (Message Type i) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number TT EE Spaces Trailer Character

Description Optional. Check with the computer automation software for compatibility. i Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message. Four spaces Six digit account number Event Code Zone/User ID Two spaces Typically, this is HEX 14.

Common Formats (Message Type 1)

Type 1 Example

Table 11:

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

l

r

r

l

a

a

a

a

a

a

a

a

a

a

E

E

y

y

y

y

t

Common Formats (Message Type 1) Byte Description

# 1 2 3-4 5 6-15

Title Header Character (h) Message Type Receiver Number Line Number Account Number

16-17

Event Code

18-21

Zone Number

22

Trailer Character

Description Optional. Check with the computer automation software for compatibility. 1 Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Account number, up to ten digits. Account numbers less than ten characters are right aligned with leading ASCII spaces. Event codes define the type of signal received and interpreted by the D6500 receiver gateway. Zone or ID number sent by the communicator. Zone numbers less than four digits are right aligned with leading ASCII spaces. Typically, this is HEX 14.

The receiver gateway will sends the 3-1, 4-1, 4-2, single round, double round, extended pulse formats, Radionics BFSK, Radionics Modem II or Modem IId messages in either D6500 Mode or SIA Mode, depending on the programmable option selected. The receiver gateway also sends internal and Radionics Modem IIIa² messages in either D6500 mode or SIA mode, depending on the option selected. Refer to Appendix B: Internal Messages on page 58 and Appendix C: Radionics Modem IIIa2 Messages on page 61 for a list of the messages and their descriptions.

14

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.1.10 DNIS/ANI (Message Type N) DNIS/ANI Example

Table 12: # 1 2 3-4 5 6 7 8-18 19 20-30 31

D6500 Byte Description

1 H

2 N

3 r

4 r

5 l

6 s

7 D

8 d

9 d

10 d

11 d

12 d

13 d

14 d

15 d

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

d

d

&

a

a

a

a

a

a

a

a

a

16

DNIS/ANI (Message Type N) Byte Description Title Header Character (H) Message Type Receiver Number Line/Group Number Space DNIS Identifier DNIS Number ANI Identifier (&) ANI Number Trailer Character

Description Optional. Check with the computer automation software for compatibility. N (Capital n) Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message One space DNIS identifier DNIS number, up to 11 digits ANI identifier ANI number, up to 11 digits Typically, this is HEX 14.

4.1.11 DSC 4-3 (Message Type d) DSC 4-3 Example

Table 13: # 1 2 3-4 5 6-11 12-15 16 17 18 19 20-21 22

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

h

d

r

r

l

s

s

s

s

s

s

a

a

a

a

s

E

s

X

Y

Y

t

DSC-4-3 (Message Type d) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number Space E Space X YY Trailer Character

Description Optional. Check with the computer automation software for compatibility. d Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Six spaces Account number, four digits One space Event Code, “A” as the default One space Event code number Zone number Typically, this is HEX 14.

Bosch Security Systems | 1/05 | 4998122703D

15

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.1.12 FBI Super Fast (Message Type F) FBI Super Fast Example

Table 14: # 1 2 3-4 5 6-11 12-15 16 17-18 19 20-21 22

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

h

F

r

r

l

s

s

s

s

s

s

a

a

a

a

T

Z

Z

E

s

s

t

FBI Super Fast (Message Type F) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number T ZZ E Spaces Trailer Character

Description Optional. Check with the computer automation software for compatibility. F (Capital f) Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Six spaces Account number, four digits Zone type Zone number Event type Two spaces Typically, this is HEX 14.

4.1.13 ITI (Message Type I) ITI Example

Table 15: # 1 2 3-4 5 6-8 9 10 11-14 15 16 17-18 19 20 21 22

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

I

r

r

l

s

s

s

a

T

a

a

a

a

G

I

Z

Z

E

W

N

t

ITI (Message Type I) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number Panel Type Account Number G I ZZ E W N Trailer Character

Description Optional. Check with the computer automation software for compatibility. I (Capital i) Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message. Three spaces First digit account number Control panel Type Next four digit account number Group number Open/close (O/C) User ID Zone number Condition code Protection level was Protection level is Typically, this is HEX 14.

4.1.14 Link Test (Message Type 1) Link Test Example

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

1

r

r

0

s

s

s

s

s

s

s

s

s

s

s

@

s

s

s

s

t

The D6600 can automatically generate this message at the programmed intervals.

16

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. Table 16: # 1 2 3-4 5 6-15 16-17 18-21 22

Link Test (Message Type 1) Byte Description Title Header Character (h) Message Type Receiver Number Line Number Spaces Event Code Spaces Trailer Character

Description Optional. Check with the computer automation software for compatibility. 1 Receiver gateway number from 01 to 99 Line number as zero for link test Eleven spaces Event code is @ for link test Four spaces Typically, this is HEX 14.

4.1.15 Robofon (Message Type j) Robofon Example

Table 17: # 1 2 3-4 5 6-9 10-15 16-17 18-21 22

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

j

r

r

l

s

s

s

s

a

a

a

a

a

a

E

E

s

s

s

s

t

Robofon (Message Type j) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number EE Spaces Trailer Character

Description Optional. Check with the computer automation software for compatibility. j Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Four spaces Six digit account number Event code Four spaces Typically, this is HEX 14.

Bosch Security Systems | 1/05 | 4998122703D

17

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.1.16 Sescoa Super Speed (Message Type 7) Sescoa Super Speed Example

Table 18: # 1 2 3-4 5 6-11 12-15 16 17 18-19 20 21 22

18

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

7

r

r

l

s

s

s

s

s

s

a

a

a

a

s

I

A

A

C

s

t

Sescoa Super Speed (Message Type 7) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number Space I AA C s Trailer Character

Description Optional. Check with the computer automation software for compatibility. 7 Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Six spaces Account number, four digits One space Event code Two digit zone code or the first two digits user code Space if zone report, or the last digit user code One space Typically, this is HEX 14.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.1.17 Scancom 4-16-1, 5-16-1, 6-16-1 - Available Upon Request (Message Type g) Scancom 4-16-1, 5-16-1, 6-16-1 Example

Table 19:

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

h

g

r

r

l

a

a

a

a

a

a

s

C

C

C

C

s

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

C

C

C

C

s

C

C

C

C

s

C

C

C

C

s

C

t

Scancom 4-16-1, 5-16-1, 6-16-1 - Available Upon Request (Message Type g) Byte Description

# 1 2 3-4 5 6-11

Title Header Character (h) Message Type Receiver Number Line/Group Number Account Number

12 13-16 17 18-21 22 23-26 27 28-31 32 33 34

Space CCCC Space CCCC Space CCCC Space CCCC Space C Trailer Character

Description Optional. Check with the computer automation software for compatibility g Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Account number, up to six digits Account numbers less than six characters are right aligned with leading ASCII spaces One space Channels 1 to 4 One space Channels 5 to 8 One space Channels 9 to 12 One space Channels 13 to 16 One space Supervisory channel Typically, this is HEX 14.

Bosch Security Systems | 1/05 | 4998122703D

19

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.1.18 Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) Scancom 4-24-1 Example

Table 20:

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

h

r

r

l

a

a

a

a

a

a

s

C

C

C

C

s

C

C

C

C

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43 44

C

C

C

C

s

C

C

C

C

s

C

C

C

C

s

C

C

C

C

s

C

t

Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) Byte Description

# 1 2 3-4 5 6-11

Title Header Character (h) Message Type Receiver Number Line/Group Number Account Number

12 13-16 17 18-21 22 23-26 27 28-31 32 33-36 37 38-41 42 43 44

Space CCCC Space CCCC Space CCCC Space CCCC Space CCCC Space CCCC Space C Trailer Character

20

s

Description Optional. Check with the computer automation software for compatibility. h Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Account number, up to six digits. Account numbers less than six characters are right aligned with leading ASCII spaces One space Channels 1 to 4 One space Channels 5 to 8 One space Channels 9 to 12 One space Channels 13 to 16 One space Channels 17 to 20 One space Channels 21 to 24 One space Supervisory channel Typically, this is HEX 14.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.1.19 Seriee FSK (Message Type k) Seriee FSK Example

D6500 Byte Description

Table 21: # 1 2 3-4 5 6-11 12-16 17 18 19 20 -21 22

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

h

k

r

r

l

s

s

s

s

s

s

a

a

a

a

a

s

E

s

Z

Z

t

20

21 22

Seriee FSK (Message Type k) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number Space E Space ZZ Trailer Character

Description Optional. Check with the computer automation software for compatibility. k Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message. Six spaces Five digit account number One space Event code One space Zone number Typically, HEX 14

4.1.20 Seriee DTMF (Message Type l) Seriee DTMF Example

Table 22: # 1 2 3-4 5 6-7 8 9-14 15 16-21 22

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

h

l

r

r

l

L

L

*

a

a

a

a

a

a

*

16

17

18

19

. . .

t

Seriee DTMF (Message Type l) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number LL * Account number * *** Trailer Character

Description Optional. Check with the computer automation software for compatibility. 1 (lowercase L) Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Data length Data separator Four, five or six account numbers Data separator DTMF Seriee Data Typically, HEX 14

Bosch Security Systems | 1/05 | 4998122703D

21

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.1.21 SIA (Message Type S) SIA Example

D6500 Byte Description 1

h Table 23: # 1 2 3-4 5 6 7 8-11 12 13 14-15 16-19 20 21 22

2

S

3

r

4

r

5

l

6

[

7

#

8

a

9

a

10

a

11

a

12

|

13

E

14

M

15

16

M

Z

17

Z

18

Z

19

20

21

Z

/

** t *

22

SIA (Message Type S) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number [ # Account Number | E Event Code Zone / *** Trailer Character

Description Optional Check with the computer automation software for compatibility S Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Open bracket # Up to sixteen digits may be used in the account number Separator, indicates more data positions after account number. SIA block code SIA Event code Zone number Separator Next block of data Typically, HEX 14

4.1.22 Silent Knight FSK0 (Message Type 1) Silent Knight FSK0 Example

Table 24: # 1 2 3-4 5 6-11 12-15 16 17 18-20 21 22

22

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

1

r

r

l

s

s

s

s

s

s

a

a

a

a

s

E

s

s

s

Z

t

Silent Knight FSK1 (Message Type m) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number Spaces E Space Zone number Trailer Character

Description Optional Check with the computer automation software for compatibility 1 Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Six spaces Four digit account number One space Event code Three spaces Zone number Typically, HEX 14

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. Optional Silent Knight SK1 (Message Type m): If menu item 2.5.16 in the D6600 Receiver is equal to 1, the following output is used. Silent Knight FSK1 Example

D6500 Byte Description 1 h

Table 25: # 1

2 m

3 r

r

5 l

6 s

7 a

8 a

9 a

10

11

12

13

14

15

16

17

18

a

a

a

a

a



Z

Z



19

20

21 22

. . .

t

Optional Silent Knight SK1 (Message Type m) Byte Description

6 7-14

Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number

15 16-17 18 19 21

“ ZZ “ *** Trailer Character

2 3-4 5

4

Description Optional Check with the computer automation software for compatibility m Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message One space Maximum eight-digit account code. If the account code is less than eight digits, enter the actual number of digits without a leading space. Separator First zone number, up to eight reports, one report has two digits Separator More data Typically, HEX 14

Bosch Security Systems | 1/05 | 4998122703D

23

D6600 | Computer Interface Manual | 4.0

Table 26:

Silent Knight Automation Format

Report Code

Description

00: 01 to 08: 09: 10 to 19: 20 to 29: 30: 31: 32: 33: 34: 35: 36: 37: 38: 39: 40: 41 to 49: 50 to 59: 60: 61 to 68: 69: 70: 71 to 78: 79: 80: 81 to 89: 90: 91 to 99:

Alarm Panic Alarm 01 to 08 Holdup Alarm 10 to 19 Alarm Restore 10 to 19 Test Code Trouble Line 1 Trouble Line 2 Expand Trouble Forced Access Restore Line 1 Restore Line 2 Expand Restore Cancel Code Data Lost Closing Closing 01 to 09 Bypass 10 to 19 Trouble AC Trouble 01 to 08 Trouble BAT Restore AC Restore 01 to 08 Restore BAT Access Access 01 to 09 Opening Opening 01 to 09

24

Computer Communication Protocols

To Automation 2 5 16=0(EEZZ) PAss sA0x Hass sA1x sH1x sXss LT01 LT02 ETss DFss LR01 LR02 ERss OCss RTss CL00 CL0x sB1x ATss sT0x YTss ARss sRss YRss DS00 DG0x OP00 OP0x

2 5 16=1(ZZ) 00 01 to 08 09 10 to 19 20 to 29 30 31 32 33 34 35 36 37 38 39 40 41 to 49 50 to 59 60 61 to 68 69 70 71 to 78 79 80 80 to 89 90 91 to 99

Note

x=1 to 8 x=0 to 9 x=0 to 9

x=1 to 9 x=0 to 9 x=1 to 8

x=1 to 9

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.1.23 Silent Knight FSK2 (Message Type m) Silent Knight FSK2 Example

Table 27: # 1

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

m

r

r

l

s

a

a

a

a

a

a

a

a



E

E

Z

Z



* * *

Silent Knight FSK2 (Message Type m) Byte Description

6 7-14

Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number

15 16-19

“ EEZZ

20 21 22

“ *** Trailer Character

2 3-4 5

t

Description Optional Check with the computer automation software for compatibility m Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message One space Maximum eight-digit account code If the account code is less than eight digits, enter the actual number of digits without a leading space Separator First event and zone number If this is the only event, it will be ended with the terminator Up to eight reports One report has four digits: one-digit event code, one-digit condition code, two-digit zone code Separator Next data Typically, HEX 14

4.1.24 Silent Knight FSK80 D6500 mode (Message Type E) Silent Knight FSK80 Example

Table 28: # 1 2 3-4 5 6-11 12-15 16 17 18-19 20-21 24

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

E

r

r

l

s

s

s

s

s

s

A

A

A

A

s

A

s

s

X

Y

t

Silent Knight FSK80 (Message Type E) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number Space Filler character A Spaces XY Trailer Character

Description Optional Check with the computer automation software for compatibility E Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message

Four-digit account number Always char “A” Two-digit alarm zone code Typically, HEX 14

Bosch Security Systems | 1/05 | 4998122703D

25

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.1.25 Telim (Message Type n) Telim Example

Table 29: # 1 2 3-4 5 6 7-12 13 14 15-32 33

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

h

n

R

R

L

s

A

A

A

A

A

A

s

E

T

T

Z

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

Z

Z

Z

Z

Z

Z

Z

Z

Z

Z

Z

Z

Z

Z

Z

t

Z

Telim (Message Type n) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Space Account Number Space E TTZZZZZZZZZZZZ Trailer Character

Description Optional Check with the computer automation software for compatibility n Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message One space Six digit account number One space Event code Input line number Typically, HEX 14

4.1.26 Text Message (Message Type 3) Type 3 Example

Table 30: # 1 2 3-4 5 6-21 22

26

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

h

3

r

r

l

P

R

I

N

T

E

R

13

14

15

16

17

18

19

20

21 22

v

v

.

v

v

t

Text Message (Message Type 3) Byte Description Title Header Character (h) Message Type Receiver Number Line Number Message Text Trailer Character

Description Optional Check with the computer automation software for compatibility 3 Receiver gateway number from 01 to 99 Line number fixed at 1. Sixteen characters in length Typically, HEX 14

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.1.27 Varitech FSK 4-1 (Message Type 1) Varitech FSK 4-1 D6500 Byte Description Example 1 2 3 4 5 6

h Table 31: # 1 2 3-4 5 6-11 12-15 16 17 18-20 21 22

1

r

r

l

s

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

s

s

s

s

s

a

a

a

a

s

E

s

s

s

X

t

Varitech FSK 4-1 (Message Type 1) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number Space E Spaces X Trailer Character

Description Optional, check with the computer automation software for compatibility 1 Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Six spaces Four digit account number One space Event code Three spaces Zone number Typically, HEX 14

4.1.28 Varitech FSK 4-2 (Message Type 1) Varitech FSK 4-2 D6500 Byte Description Example 1 2 3 4 5 6

h Table 32: # 1 2 3-4 5 6-11 12-15 16 17 18-19 20-21 22

1

r

r

l

s

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

s

s

s

s

s

a

a

a

a

s

E

s

s

X

Y

t

Varitech FSK 4-2 (Message Type 1) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number Spaces Account Number Space E Spaces XY Trailer Character

Description Optional Check with the computer automation software for compatibility 1 Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Six spaces Four digit account number One space Event code Two spaces Zone number Typically, HEX 14

Bosch Security Systems | 1/05 | 4998122703D

27

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.1.29 VONK (Message Type V) D6500 Byte Description VONK Example

Table 33: # 1

1 h

2 V

3 r

4 r

6 A

7 A

8 1

9 2

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 3 4 5 6 7 8 9 A B C D E F G t

VONK (Message Type V) Byte Description

6-7 8-23

Title Header Character (h) Message Type Receiver Number Line/Group Number Account Number Zone status

24

Trailer Character

2 3-4 5

5 l

Description Optional Check with the computer automation software for compatibility V Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Two digit account number Status of zones 1 to 16. If the zone is Closed, a “.”(Period) is in this position. If the zone is Open, 1 to G appears in this position. Typically, HEX 14

4.1.30 X-SIA Text (Message Type S) X-SIA Example

Table 34: # 1 2 3-4 5 6 7 8-11 12 13 14-15 16-19 20 21 22-34 35 36-37 38 39-41 42

28

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

S

r

r

l

[

#

a

a

a

a

|

E

M

M

Z

Z

Z

Z

*

`

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

T

T

T

T

T

T

T

T

T

T

T

T



N

M

/

*

*

*

t

T

X-SIA Text (Message Type S) Byte Description Title Header Character (h) Message Type Receiver Number Line/Group Number [ # Account Number | E MM ZZZZ * ‘ TT…T ‘ NM / *** Trailer Character

Description Optional, check with the computer automation software for compatibility S Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Open bracket # Up to sixteen digits can be used in the account number Separator, indicates more data positions after account number SIA block code SIA event code Zone number Text identifier Quotation mark (single) 13 character text string Qutotation mark (single) Unit field characters Separator Next block of data Typically, HEX 14

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

.

4.2

SIA Mode Messages

Use the SIA mode for central station monitoring. 4.2.1 Acron Super Fast (Message Type 9) Acron Super Fast Example

Table 35:

Acron Super Fast (Message Type 9) Byte Description

Title L CRC Message Type sequence# receiver# line# (Line/Group #) account#

Figure 6:

SIA Mode Description [#aaaa|CCCCCCCC]

Description Standard line feed character Cyclical redundancy check number 9 The message sequence number, the valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits.

Message sent to printer

mm/ddshh:mmsLxxsACNsACCTsaaaa+++sACCsa aaasCCCCsCCCC For lines that are grouped, Gxx appears instead of Lxx. Table 36:

Characters ACN Lxx Gxx

Acron Super Fast (Message Type 9) Printer Output Description Acron Super Fast format Line number Grouped line numbers

Bosch Security Systems | 1/05 | 4998122703D

29

D6600 | Computer Interface Manual | 4.0 4.2.2

Computer Communication Protocols

Ademco Contact-ID (Message Type a)

Contact-ID Example

Table 37:

SIA Mode Description [#aaaa|18QXYZGGCCC]

Ademco Contact-ID (Message Type a) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# 18 Q XYZ GG CCC

Figure 7:

Description Standard line feed character Cyclical redundancy check number a The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. Ademco Contact-ID format number Qualifier, 1 = New event or opening, 3 = New restore or closing, 6 = Previous event Class code and event code (refer to Appendix A: Contact ID Event Code Classifications on page 53) Group number Zone codes or User ID

Message sent to printer

Table 38:

Ademco Contact-ID (Message Type a) Printer Output

mm/ddshh:mmsLxxsCIDsACCTsaaaa+++sACCsa aaasNNNsEVENT=XYZsG=GGsC=CCC For lines that are grouped, Gxx appears instead of Lxx.

30

Characters CID Gxx Lxx NNN

Description Contact-ID format Grouped Line numbers Line number If Q = 1, print E/O for new event or opening If Q = 3, print R/C for restore or closing If Q = 6, print “OLD” for old messages and events.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0 . 4.2.3

Computer Communication Protocols

Ademco 4-1 Express (Message Type b)

4-1 Express Example

Table 39:

SIA Mode Description [#aaaa|X]

Ademco 4-1 Express (Message Type b) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# X

Figure 8:

Description Standard line feed character Cyclical redundancy check number b The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. Zone number

Message sent to printer

mm/ddshh:mmsLxxsE41sACCTsaaaasEVENT=X For lines that are grouped, Gxx appears instead of Lxx. Table 40:

Characters E41 Lxx: Gxx

Ademco 4-1 Express (Message Type b) Printer Output Description Ademco 4-1 Express format Line number Grouped line numbers

Bosch Security Systems | 1/05 | 4998122703D

31

D6600 | Computer Interface Manual | 4.0 4.2.4

Computer Communication Protocols

Ademco 4-2 Express (Message Type c)

4-2 Express Example

Table 41:

SIA Mode Description [#aaaa|XY]

Ademco 4-2 Express (Message Type c) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# XY

Figure 9:

Description Standard line feed character Cyclical redundancy check number c The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. Event code and Zone number

Message sent to printer

mm/ddshh:mmsLxxsE42sACCTsaaaasEVENT=XY For lines that are grouped, Gxx appears instead of Lxx. Table 42:

Characters E42 Lxx: Gxx

32

Ademco 4-2 Express (Message Type c) Printer Output Description Ademco 4-2 Express format Line number Grouped line numbers

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0 . 4.2.5

Computer Communication Protocols

Ademco High Speed 4-8-1, SCANCOM 4-8-1 (Message Type f) SCANCOM 5-8-1, 6-8-1 - available upon request

High Speed Example

Table 43:

SIA Mode Description [#aaaaaa|CC CCsCCCCsC]

Ademco High Speed 4-8-1, SCANCOM 4-8-1 (Message Type F) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# CCCC s CCCC s C

Description Standard line feed character Cyclical redundancy check number f The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has up to six digits. Channels 1 to 4 One space Channels 5 to 8 One space Supervisory channel

Figure 10: Message sent to printer

Table 44:

Ademco High Speed, 4-8-1 (Message Type f) Printer Output

mm/ddshh:mmsLxxsHGHsACCTsaaaaaa+++sACC saaaaaasCCCCsCCCCsC For lines that are grouped, Gxx appears instead of Lxx.

Bosch Security Systems | 1/05 | 4998122703D

Characters HGH Lxx: Gxx

Description Ademco High Speed format Line number Grouped line numbers

33

D6600 | Computer Interface Manual | 4.0 4.2.6

ADT SIA (Message Type )

ADT SIA Example

Table 45:

SIA Mode Description [#aaaa|data]

ADT SIA (Message Type ) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# E damm-dd-yytihh:mm:ss Data

4.2.7

Description Standard line feed character Cyclical redundancy check number 09 hex The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number up to sixteen digits. Event Code (refer to Appendix G ADT SIA Report Codes on page 152) Date and time This field contains message data codes such as event type, area number, point number, identification number.

Caller ID (Message Type )

SIA Example

Table 46:

SIA Mode Description [&TTTTTTTTTTTTTTTT]

Caller ID (Message Type ) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) & T

34

Computer Communication Protocols

Description Standard line feed character Cyclical Redundancy Check number The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. Origin ID Block Up to 16-digit Caller ID

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0 . 4.2.8

CFSK (Message Type I)

CFSK Example

Table 47:

SIA Mode Description [#aaaaaa|TTEE]

CFSK (Message Type I) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account # TT EE

4.2.9

Computer Communication Protocols

Description Standard line feed character Cyclical redundancy check number I (Capital I) The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number, up to six digits. Event code Zone/User ID

Common Formats (Message Type )

SIA Example

Table 48:

SIA Mode Description [#aaaaaaaaaaaaaaaa|data]

Common Formats (Message Type ) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# Data

Description Standard line feed character Cyclical Redundancy Check number 09 hex The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number up to sixteen digits. This field contains message data codes such as event type, area number, point number, identification number, etc

The receiver gateway sends the 3-1, 4-1, 4-2, single round, double round, extended pulse formats, BFSK, Modem II or Modem IId messages in either D6500 Mode or SIA Mode, depending on the program option selected. The receiver gateway also sends internal and Modem IIIa² messages in either D6500 mode or SIA mode, depending on the programmable option selected. Refer to Appendix B: Internal Messages on page 58 and Appendix C: Radionics Modem IIIa2 Messages on page 61 for a list of the messages and their descriptions.

Bosch Security Systems | 1/05 | 4998122703D

35

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.2.10 DNIS/ANI (Message Type N) SIA Example

Table 49:

SIA Mode Description [#0000|Dddddddddddd&aaaaaaaaaa]

DNIS/ANI (Message Type N) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# D DNIS number (d) ANI identifier (&) ANI number (a)

Description Standard line feed character Cyclical redundancy check number N The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. Fixed at 0000 DNIS identifier DNIS number, up to 11 digits ANI identifier ANI number, up to 11 digits

Figure 11: Message sent to printer MM/DDsHH:MMsLxxsDNISsddddddddddd+++sAN Isaaaaaaaaaaa

36

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.2.11 DSC 4-3 (Message Type d) DSC4-3 Example

Table 50:

SIA Mode Description [#aaaa|XYY]

DSC 4-3 (Message Type d) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# X YY

Description Standard line feed character Cyclical redundancy check number d The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. Event code number Zone number

Figure 12: Message sent to printer

Table 51:

DSC 4-3 (Message Type d) Printer Output

mm/ddshh:mmsLxxsDSGsACCTsaaaasEVENT=XY Y+++sACCsaaaaseeeeeeeesiisnnn For lines that are grouped, Gxx appears instead of Lxx.

Table 52:

Event Code Table

Code Number

Message

1 2 3 4 5 6 7 8 9 0 B C D E F

Alarm

Close Open Alarm

Restore Trouble CloseGrp OpenGrp Bypass UnBypass Cancel

Characters DSG Lxx: Gxx

Table 53: Event Characters A A A C O A A A R T C O B H O

Bosch Security Systems | 1/05 | 4998122703D

Characters ii nnn eeeeeeee

Description DSC/Sur-Gard 4-3 format Line number Grouped line numbers

Printer Output Codes Description ZN=Zone number - ID=User ID Zone/User number Up to eight-character event type, right justified - ALARM, RESTORE, TROUBLE, OPEN, OPENGRP, CLOSE, CLOSEGRP, BYPASS, UN BYPASS, CANCEL

37

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.2.12 FBI Super Fast (Message Type F) FBI Super Fast Example

Table 54:

SIA Mode Description [#aaaa|TZZE]

FBI Super Fast (Message Type F) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# T ZZ E

Description Standard line feed character Cyclical redundancy check number F The message sequence number. The valid sequence number range is 0001 to 9999 The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600 The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages The communicator's account number has four digits. Zone type Zone number Event type

Figure 13: Message sent to printer

Table 55:

mm/ddshh:mmsLxxsFBIsACCTsaaaasTZZE+++s ACCsaaaastttttttttseeeeeeeesiisnnn For lines that are grouped, Gxx appears instead of Lxx.

Table 56: Code 1 2 3 4 5 6 7 8 9 0 B C D E F

38

Event Code Table Zone/Event Type Fire Panic Burglary Medical Auxiliary Bypass Inactive Eight Nine Zero Opening Closing Abort Restore Trouble

FBI Super Fast (Message Type F) Printer Output

Characters FBI Lxx: Gxx

Description FBI Super Fast format Line number Grouped line numbers

Table 57:

Printer Output Codes

Characters ii nnn ttttttttt

eeeeeeee

Description ZN=Zone number - ID=User ID Zone/User number Up to nine-character zone type, right justified FIRE, PANIC, BURGLARY, MEDICAL, AUXILIARY Up to eight-character event type, left justified ALARM, RESTORE, TROUBLE, OPEN, OPENGRP, CLOSE, CLOSEGRP, BYPASS, UN BYPASS, CANCEL

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.2.13 ITI (Message Type I) ITI Example

Table 58:

SIA Mode Description [#aaaaa|GIZZEWN]

ITI (Message Type I) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# G I ZZ E W N

Description Standard line feed character Cyclical redundancy check number I (Captial I) The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has up to six digits. Group number O/C User ID Zone number Condition code Protection level was Protection level now

4.2.14 Link Test (Message Type ) Link Test Example

SIA Mode Description []

The D6600 can automatically generate this message at the preprogrammed intervals. Table 59:

Link Test (Message Type ) Description

Title LF CRC Message Type sequence# receiver#

Description Standard line feed character Cyclical redundancy check number The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600.

Bosch Security Systems | 1/05 | 4998122703D

39

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.2.15 RB2000 (Message Type R) Description RB2000 Example

Table 60:

SIA Mode Description []

RB2000 (Message Type R) Byte Description

Title LF CRC R sequence# Receiver# line# CR

Description Standard line feed character, hex 0A Cyclical redundancy check number ASCII R, Message Type R for RB2000 format The message sequence number. The valid sequence number range: 0001 to 9999. The receiver gateway that sent the message. Valid digits: 01 to 99 for the D6600. The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages. VDS message sent as a hex string, the receiver extracts the alarm type Hex 0D

Figure 14: Single message sent to Printer

Table 61:

RB2000 (Message Type R) Printer Output

MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ RB2000_EVENT_RAW_DATA Figure 15: Multiple messages sent to printer MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ RB2000_EVENT_RAW_DATA 1 +++ RB2000_EVENT_RAW_DATA 2 ... +++ RB2000_EVENT_RAW_DATA n

40

Characters

Description

MM/DDsHH:MM RB2 Lxx ACCT xxxxxxxxxxxx

Date and time RB2000 format Line number Subscriber number, up to 12 characters(hex) The raw data of RB2000 event

RB2000_EVENT_RAW _DATA RB2000_EVENT_RAW _DATA1 RB2000_EVENT_RAW _DATA 2 RB2000_EVENT_RAW _DATA n

The raw data of RB2000 event 1 The raw data of RB2000 event 2 The raw data of RB2000 event n

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.2.16 Robofon (Message Type j) Robofon Example

Table 62:

SIA Mode Description [#aaaaaa|EE]

Robofon (Message Type j) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account # EE

Description Standard line feed character Cyclical redundancy check number j The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has up to six digits. Event code

4.2.17 Scancom 4-16-1, 5-16-1, 6-16-1 - Available Upon Request (Message Type g) 4-16-1 Example

Table 63:

SIA Mode Description [#aaaaaa|CCCCsCCCCsCCCCsCCCCsC]

Scancom 4-16-1, 5-16-1, 6-16-1 - Available Upon Request (Message Type g) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) Account# CCCC s CCCC s CCCC s CCCC s C

Description Standard line feed character Cyclical redundancy check number g The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has up to six digits. Channels 1 to 4 One space Channels 5 to 8 One space Channels 9 to 12 One space Channels 13 to 16 One space Supervisory channel

Bosch Security Systems | 1/05 | 4998122703D

41

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

Figure 16: Message sent to printer

Table 64:

mm/ddshh:mmsLxxsSCNsACCTsaaaaaa+++sACC saaaaaasCCCCsCCCCsCCCCsCCCCsC For lines that are grouped, Gxx appears instead of Lxx.

Scancom 4-16-1, 5-16-1, 6-16-1 Available Upon Request (Message Type g) Printer Output

Characters SCN Lxx: Gxx

Description Scancom Line number Grouped line numbers

4.2.18 Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) 4-24-1 Example

Table 65:

SIA Mode Description [#aaaaaa|CCCCsCCCCs CCCCs CCCCsCCCCsCCCCsC]

Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# CCCC s CCCC s CCCC s CCCC s CCCC s CCCC s C

Description Standard line feed character Cyclical redundancy check number h The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number, up to six digits Channels 1 to 4 One space Channels 5 to 8 One space Channels 9 to 12 One space Channels 13 to 16 One space Channels 17 to 20 One space Channels 21 to 24 One space Supervisory channel

Figure 17: Message sent to printer

Table 66:

mm/ddshh:mmsLxxsSCNsACCTsaaaaaa +++sACCsaaaasCCCCsCCCCsCCCCsCCCC ++++++++++++++CCCCsCCCCsC For lines that are grouped, Gxx appears instead of Lxx.

42

Characters SCN Lxx: Gxx

Scancom 4-24-1, 5-24-1, 6-24-1 Available Upon Request (Message Type h) Printer Output Description Scancom Line number Grouped line numbers

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.2.19 Seriee DTMF (Message Type l) Seriee DTMF Example

Table 67:

SIA Mode Description [#aaaa|*data]

Seriee DTMF (Message Type l) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account # * Data

Description Standard line feed character Cyclical redundancy check number l (lowercase L) The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. Data separator DTMF Seriee Data

4.2.20 Seriee FSK (Message Type k) Seriee FSK Example

Table 68:

SIA Mode Description [#aaaaa|EZZ]

Seriee FSK (Message Type k) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) Account # E ZZ

Description Standard line feed character Cyclical redundancy check number k The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has up to six digits. Event code Zone number

Bosch Security Systems | 1/05 | 4998122703D

43

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.2.21 Sescoa Super Speed (Message Type 7) Sescoa Super Speed Example

Table 69:

SIA Mode Description

Sescoa Super Speed (Message Type 7) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# I AA C

Description Standard line feed character Cyclical redundancy check number 7 The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits are 01 to 99 for D6600. The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. Event code Two- digit zone code or the first two digits user code. Space if zone report, or the last digit user code

Figure 18: Message sent to printer

Table 70:

Sescoa Super Speed (Message Type 7) Printer Output

mm/ddshh:mmsLxxSESsACCTsaaaa +++sACCsaaaasEEEseeeeeeeeeeeeee For lines that are grouped, Gxx appears instead of Lxx.

44

Characters SES Lxx Gxx aaaa EEE eeeeeeeeeeeeee

Description SESCOA Super Speed format Line number Grouped line numbers Account code SESCOA Super Speed format event Up to 14-characters of event description

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.2.22 Silent Knight FSK() (Message Type ) Silent Knight FSK0 Example

Table 71:

SIA Mode Description [#aaaa|data]

Silent Knight FSK0 (Message Type ) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account # Data

Description Standard line feed character Cyclical redundancy check number The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600. The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. Data

4.2.23 Silent Knight FSK1 (Message Type m) Silent Knight FSK1 Example

Table 72:

SIA Mode Description [#aaaa| EEZZ”ECZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ]

Silent Knight FSK1 (Message Type m) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account # EEZZ”EEZZ”EEZZ”EEZZ” EEZZ”EEZZ”EEZZ”EEZZ

Description Standard line feed character Cyclical redundancy check number m The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600. The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. Up to eight reports. One report has four digits: one-digit event code, one-digit condition code, and two-digit zone code. The quote (“) is the separation character.

Bosch Security Systems | 1/05 | 4998122703D

45

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

Optional Silent Knight FSK1 (Message Type m) If Menu Item 2.5.16 in the D6600 Receiver is equal to 1, the following output is used. Silent Knight FSK1 Example

Table 73:

SIA Mode Description [#aaaa|ZZ”ZZ”ZZ”ZZ”ZZ”ZZ”ZZ”ZZ]< CR>

Optional Silent Knight FSK1 (Message Type m) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account # ZZ”ZZ”ZZ”ZZ”ZZ”ZZ”ZZ”Z Z

Table 74:

Description Standard line feed character Cyclical redundancy check number m The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600. The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. Up to eight reports. One report has two digits. The quote (“) is the separate character.

Silent Knight FSK1 Optional Outputs

Report Code

Description

To Automation 2 5 16 = 0(EEZZ)

2 5 16 = 1(ZZ)

00 01 to 08 09 10 to 19 20 to 29 30 31 32 33 34 35 36 37 38 39 40 41 to 49 50 to 59 60 61 to 68 69 70 71 to 78 79 80 81 to 89

Alarm Panic Alarm 01 to 08 Holdup Alarm 10 to 19 Alarm Restore 10 to 19 Test Code Trouble Line 1 Trouble Line 2 Expand Trouble Forced Access Restore Line 1 Restore Line 2 Expand Restore Cancel Code Data Lost Closing Closing 01 to 09 Bypass 10 to 19 Trouble AC Trouble 01 to 08 Trouble BAT Restore AC Restore 01 to 08 Restore BAT Access Access 01 to 09

PAss sA0x Hass sA1x sH1x sXss LT01 LT02 ETss DFss LR01 LR02 ERss OCss RTss CL00 CL0x sB1x ATss sT0x YTss ARss sRss YRss DS00 DG0x

00 01 to 08 09 10 to 19 20 to 29 30 31 32 33 34 35 36 37 38 39 40 41 to 49 50 to 59 60 61 to 68 69 70 71 to 78 79 80 80 to 89

46

Note

x = 1 to 8 x = 0 to 9 x = 0 to 9

x = 1 to 9 x = 0 to 9 x = 1 to 8

x = 1 to 9

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. Table 74:

Silent Knight FSK1 Optional Outputs (continued)

Report Code

Description

To Automation

90 91 to 99

Opening Opening 01 to 09

OP00 OP0x

Note 90 91 to 99

4.2.24 Silent Knight FSK2 (Message Type m) Silent Knight FSK2 Example

Table 75:

SIA Mode Description [#aaaaaa| EEZZ”ECZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ]

Silent Knight FSK2 (Message Type m) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account # EEZZ”EEZZ”EEZZ”EEZZ” EEZZ”EEZZ”EEZZ”EEZZ

Description Standard line feed character Cyclical redundancy check number m The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600 The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has up to six digits. Up to eight reports. One report has four digits: one-digit event code, one-digit condition code, and two-digit zone code. The quote (“) is the separation character.

Bosch Security Systems | 1/05 | 4998122703D

47

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.2.25 Silent Knight FSK80 (Message Type E) Silent Knight FSK80 Example

Table 76:

SIA Mode Description [#AAAA|NBAXY]

Silent Knight FSK80 (Message Type E) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account # NBA

Description Standard line feed character Cyclical redundancy check number E The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600 The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. Alarm event

Figure 19: Message sent to printer MM/DDsHH:MMsLxxsSFKsACCTsAAAA +++ACCTsAAAAsALARM_ZNs1 +++ACCTsAAAAsALARM_ZNs2 +++ACCTsAAAAsALARM_ZNs3 +++ACCTsAAAAsALARM_ZNs4 +++ACCTsAAAAsALARM_ZNs5 +++ACCTsAAAAsALARM_ZNs7 +++ACCTsAAAAsALARM_ZNs8 +++ACCTsAAAAsALARM_ZNs9

Table 77:

Characters MM/DDsHH:MM SFK Lxx AAAA s

48

Silent Knight FSK80 Printer/LCD output Description Date and time SFSK80 format Line number The communicator's account number has four digits. Space

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.2.26 Telim (Message Type n) Telim Example

Table 78:

SIA Mode Description [#aaaaaa|EETTZZZZZZZZZZZZZZZZZZ]

Telim (Message Type n) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account # EETTZZZZZZZZZZZZZZZZ ZZ

Description Standard line feed character Cyclical redundancy check number n The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600 The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has up to six digits. The event type and input line number

4.2.27 Varitech FSK 4-1 (Message Type ) Varitech FSK 4-1 Example

Table 79:

SIA Mode Description [#aaaa|data]

Varitech FSK 4-1 (Message Type ) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account# data

Description Standard line feed character Cyclical redundancy check number The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600 The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 99 The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. The event type and 1-digit zone number

Bosch Security Systems | 1/05 | 4998122703D

49

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

4.2.28 Varitech FSK 4-2 (Message Type ) Varitech FSK 4-2 Example

Table 80:

SIA Mode Description [#aaaa|data]

Varitech FSK 4-2 (Message Type ) Byte Description

Title LF CRC Message sequence# receiver# line# (Line/Group #) account # data

Description Standard line feed character Cyclical redundancy check number The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600 The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has four digits. The event type and two-digit zone number.

4.2.29 VONK (Message Type V) VONK Example

Table 81:

VONK (Message Type V) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account # Data

50

SIA Mode Description [#aa|123456789ABCDEFG]

Description Standard line feed character Cyclical redundancy check number V The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600 The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has two digits. Status of zones 1 to 16. If the zone is closed, a “.” (Period) appears in this position. If the zone is open, any digit from 1 to G appears in this position.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | 4.0

Computer Communication Protocols

. 4.2.30 X-SIA text (Message Type ) X-SIA Example

Table 82:

SIA Mode Description [#aaaa|EMMZZZZ*'TTTTTTTTTTTTT' NM/***]

X-SIA text (Message Type ) Byte Description

Title LF CRC Message Type sequence# receiver# line# (Line/Group #) account # E MM ZZZZ * ` TT…TTT ‘ NM / ***

Description Standard line feed character Cyclical redundancy check number The message sequence number. The valid sequence number range is 0001 to 9999. The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600 The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number has up to 16 digits. SIA block code SIA event code Zone number Text identifier Single quote 13 character text string Single quote Unit field characters Separator Next data

Figure 20: Message sent to printer MM/DDsHH:MMsLxxsSIAsACCTsAAAA+++sEMMZZ ZZ*'TTTTTTTTTTTTT'NM+++sEMMZZZZ*'TTTTT TTTTTTTT'NM

Bosch Security Systems | 1/05 | 4998122703D

Table 83:

X-SIA Printer/LCD output

Characters MM/DDsHH:MM Lxx SIA AAAA E MM ZZZZ * ‘ TTT…T ‘ NM

Description Date and time Line number SIA format Account code SIA block code SIA event code Zone number Text identifier Single quote 13 character text string Single quote Unit field characters

51

D6600 | Computer Interface Manual | 4.0

4.3

Computer Communication Protocols

Input Command Processing

Input devices, such as automation systems, send the commands described in Table 84 to the receiver. If the receiver does not recognize a command, it generates a REJECT COMMAND message, prints at connected printers, and sends an ASCII text message to the automation port. The CPU programming in Menu Item 2.2.4 of the D6600 Receiver must be set to 1 to use input commands. Table 84:

ASCII Text Message to Automation Port

Set Time

The automation system, or other device, sends the command shown below to set the time at the D6600 provided that the D6600 is programmed to synchronize the time and date with the automation system !Thhmm D6650 Mode: [CSThhm SIA m] Mode: hh - hours (24 hour format) mm - minutes The automation system, or other device, sends the command shown below to set the date at the D6600 provided that the D6600 is programmed to synchronize the time and date with the automation system !Dmmddyy D6650 Mode: [CSDmmd SIA dyy] Mode: mm - month, dd - day, yy – year The automation system, or other device, sends the command shown below to stop a two way audio session on the line specified !Kn D6650 Mode: [CLKnn] SIA Mode: nn - line card number, 01-32 h3rrlsREJECTsCOMMANDsst D6650 Mode: [RE Mode: JECT COMMAND]

Set Date

Stop Two Way Audio

Reject Command

52

Table 85 shows the D6500 and SIA automation output formats for these input commands. Table 85:

Set Time Set Date Stop Two Way Audio

Input Command Output Messages

D6500 Mode h1rrssssss ssssssXss2 t h1rrssssss ssssssXss5 1t h1rrssssss ssssssXss5 2t

SIA Mode [NJT]

Printer Output TIME SET

[NJD]

DATE SET

[CLK]

TWO WAY AUDIO STOP STOP

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications .

Appendix A: Contact ID Event Code Classifications Figure 21: Contact ID format 1

2

3

4

5

1234 E 123 01 123 1234-

Customer (Subscriber Account Number) Event Qualifier - E = New Event, R = Restore Event Code - refer to Section A.1 Event Codes Partition Number, 00 to 08 (always 00 for nonpartitioned panels) 5 - Zone ID number* - reporting the alarm (001 to 999) or user number for open or close reports. * System status messages, such as AC Loss and Low Battery, are Zone ID 000. Table 86: #

Event Codes

Event Type

Medical: 100 Medical 101 Pendant Transmitter 102 Fail to report in Fire Alarms: 110 Fire 111 Smoke w/Verification 112 Combustion 113 Waterflow 114 Heat 115 Pull Station 116 Duct 117 Flame 118 Near Alarm Panic Alarms: 120 Panic Alarm 121 Duress 122 Silent 123 Audible 124 Duress-Access Granted 125 Duress-Egress Granted

Zone Emerg-Personal Emergency-# Emerg-Personal Emergency-# Emerg-Fail to check in-# Fire-Fire Alarm-# Fire-Fire Alarm-# Fire-Combustion-# Fire-Water Flow-# Fire-Heat Sensor-# Fire-Pull Station-# Fire-Duct Sensor-# Fire-Flame Sensor-# Fire-Near Alarm-# Panic-Panic-# Panic-Duress-User # Panic-Silent Panic-# Panic-Audible Panic-# Panic-Duress Access Grant-# Panic-Duress Egress Grant-#

Bosch Security Systems | 1/05 | 4998122703D

Table 86:

#

Event Codes (continued)

Event Type

Burglar Alarms: 130 Burglary 131 Perimeter 132 Interior 133 24 HR Burg (Aux) 134 Entry/Exit 135 Day/Night 136 Outdoor 137 Tamper 138 Near Alarm 139 Intrusion Verifier General Alarms: 14 General Alarm 0 14 Polling Loop 1 Open 14 Polling Loop 2 Short (AL) 14 Expansion Mod 3 Failure 14 Sensor Tamper 4 14 Expansion Module 5 Tamper 14 Silent Burg 6

Zone Burg-Burglary-# Burg-Perimeter-# Burg-Interior-# Burg-24 Hour-# Burg-Entry/Exit-# Burg-Day/Night-# Burg-Outdoor-# Burg-Tamper-# Burg-Near Alarm-# Burg-Intrusion Verifier-# Alarm-General Alarm-# Alarm-Polling Loop Open Alarm-Polling Loop Short Alarm-Exp. Module Tamper-# Alarm-Sensor Tamper-# Alarm-Exp. Module Tamper-# Alarm-Silent Burglary-#

53

D6600 | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications

Table 86:

#

Event Codes (continued)

Event Type

24 Hour Non-Burglary: 150 24 Hour (Auxiliary 151 Gas Detected 152 Refrigeration 153 Loss of Heat 154 Water Leakage 155 Foil Break 156 Day Trouble Low Bottled Gas 157 Level 158 High Temp 159 Low Temp 161 Loss of Air Flow Carbon Monoxide 162 Detected 163 Tank Level Fire Supervisory: 200 Fire Supervisory Low Water 201 Pressure 202 Low CO2 Gate Valve 203 Sensor 204 Low Water Level 205 Pump Activated 206 Pump Failure System Troubles: 300 System Trouble 301 AC Loss 302 Low System Batt RAM Checksum 303 Bad ROM Checksum 304 Bad 305 System Reset 306 307 308 309 310 311 312 313

54

Panel Prog Change Self-Test Failure System Shutdown Battery Test Fail Ground Fault Battery Missing Power Supply Overcurrent Engineer Reset

Zone Alarm-24 Hr. Non-Burg-# Alarm-Gas Detected-# Alarm-Refrigeration-# Alarm-Heating System-# Alarm-Water Leakage-# Trouble-Foil Break-# Trouble-Day Zone-# Alarm-Low Gas Level-# Alarm-High Temperature-# Alarm-Low Temperature-# Alarm-Air Flow-# Alarm-Carbon Monoxide-# Trouble-Tank Level-# Super.-Fire Supervisory-# Super.-Low Water Pressure-# Super.-Low CO2-# Super.-Gate Valve-# Super.-Low Water Level-# Super.-Pump Activation-# Super.-Pump Failure-# Trouble-System Trouble Trouble-AC Power Trouble-Low Battery Trouble-Bad RAM Checksum (Restore not applicable) Trouble-Bad ROM Checksum (Restore not applicable) Trouble-System Reset (Restore not applicable) Trouble-Programming Changed (Restore not applicable) Trouble-Self Test Failure Trouble-System Shutdown Trouble-Battery Test Failure Trouble-Ground Fault-# Trouble-Battery Missing Trouble-Pwr. Supp. Overcur.-#

Table 86:

#

Event Codes (continued)

Event Type

Sounder/Relay Troubles: 320 Sounder/Relay 321 BELL 1 322 BELL 2 323 Alarm Relay 324 Trouble Relay 325 Reversing Relay Notification 326 Appliance CKT. #3 Notification 327 Appliance CKT. #4 System Peripheral Troubles: 330 System Peripheral 331 Polling Loop Open 332 Polling Loop Short 333 Exp. Module Failure 334 Repeater Failure Local Printer Paper 335 Out 336 Local Printer Failure 337 Exp. Mod. DC Loss 338 Exp. Mod. Low bat 339 Exp. Mod. Reset 341 Exp. Mod. Tamper Exp. Module AC 342 Loss Exp. Module Self 343 Test Fail RF Rcvr Jam Detect 344 # Communication Troubles: 350 Communication 351 352 353 354 355 356 357

Telco 1 Fault Telco 2 Fault LR Radio Xmitter Fault Failure To Communicate Loss of Radion Super. Loss of Central Polling LRR XMTR. VSWR

Zone Trouble-Sounder/Relay-# Trouble-Bell/Siren #1 Trouble-Bell/Siren #2 Trouble-Alarm Relay Trouble-Trouble Relay Trouble-Reversing Relay Trouble-Notification Appl. Ckt#3 Trouble-Notification Appl. Ckt#4 Trouble-Sys. Peripheral-# Trouble-Polling Loop Open Trouble-Polling Loop Short Trouble-Exp. Module Fail-# Trouble-Repeater Failure-# Trouble-Printer Paper Out Trouble-Local Printer Trouble-Exp. Mod. DC Loss-# Trouble-Exp. Mod. Low Batt-# Trouble-Exp. Mod. Reset-# Trouble-Exp. Mod. Tamper-# Trouble-Exp. Module AC Loss-# Trouble-Exp. Self-Test Fail-# Trouble-RF Rcvr Jam Detect# Trouble-Communication Failure Trouble-Phone line #1 Trouble-Phone line #2 Trouble-Radio Transmitter Trouble-Fail to Communicate Trouble-Radio Supervision Trouble-Central Radion Polling Trouble-Radio Xmitter. VSWR-#

Status-Engineer Reset-User # (Restore not applicable)

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications . Table 86:

#

Event Codes (continued)

Event Type

Protection Loop: 370 Protection Loop Protection Loop 371 Open Protection Loop 372 Short 373 Fire Trouble 374 Exit Error (By User) 375 Panic Zone Trouble Hold-Up Zone 376 Trouble Sensor: Sensor TRBL380 Global Loss Of 381 Supervision 382 Loss Of Supervisn 383 384 385 386 387 388 389 391 392 393

Sensor Tamper RF Low Battery Smoke Hi Sens. Smoke lo sens. Intrusion hi sens. Intrusion lo sens. Det. Self test fail Sensor Watch Failure Drift Comp. Error Maintenance Alert

Zone Trouble-Protection Loop-# Trouble-Prot. Loop Open-# Trouble-Prot. Loop Short-# Trouble-Fire Loop-# Alarm-Exit Error-# Trouble-PA Trouble-# Trouble-Hold-Up Trouble-#

Table 86:

#

Event Codes (continued)

Event Type

Open/Close: 400 Open/Close Open/Close By 401 User 402 Group O/C Automatic 403 Open/Close 404 Late to O/C 405 Deferred O/C 406 407

Trouble-Sensor Trouble-# 408

Cancel (By User) Remote Arm/Disarm Quick Arm

Trouble-RF Sensor Super.-# 409 Trouble-RPM Sensor Super.# Trouble-Sensor Tamper-# Trouble-RF Sensor Battery-# Trouble-Smoke Hi Sens.-# Trouble-Smoke Lo Sens.-# Trouble-Intrusion Hi Sens.-# Trouble-Intrusion Lo Sens.-# Trouble-Sensor Test Fail-# Trouble-Sensor Watch Fail-# Trouble-Drift Comp. Error-# Trouble-Maintenance Alert-#

Bosch Security Systems | 1/05 | 4998122703D

441

Keyswitch Open/Close Armed Stay

442

Keyswitch Armed Stay

450

Exception O/C

451

Early O/C

452

Late O/C

153

Failed to Open

454

Failed to Close

455

Auto-Arm Failed

456 457 458

Partial Arm Exit Error (User) User on Premises

459

Recent Close

461

Wrong Code Entry

462

Legal Code Entry

463

Re-arm after Alarm

Zone Opening/Closing Opening-User #/Closing-User # Closing-Group User # Opening-Automatic/ClosingAutomatic Opening-Late/Closing-Late Event & Restore Not Applicable Opening-Cancel Opening-Remote/ClosingRemote Event not applicable for opening/closing-Quick Arm Opening-Keyswitch/ClosingKeyswitch Opening-Armed Stay/ClosingArmed Stay Opening-Keysw. Arm Stay/Opening-Keysw. Arm Stay Opening-Exception/ClosingException Opening-Early/Closing-EarlyUse r# Opening-Late/Closing-LateUser # Trouble-Fail to open (Restore not applicable) Trouble-Fail to Close (Restore not applicable) Trouble-Auto Arm Failed (Restore not applicable) Closing-Partial arm-User # Closing-Exit Error-User # Opening-User on Prem. –User # Trouble-Recent Close-User # (Restore not applicable) Access-Wrong Code entry (Restore not applicable) Access-Legal Code entry-user # (Restore not applicable) Status-Re Arm After AlarmUser # (restore not applicable)

55

D6600 | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications

Table 86:

#

Event Codes (continued)

Event Type

Open/Close: Auto Arm Time 464 Extended 465

Panic Alarm Reset

Remote Access: Callback 411 Requested Success412 Download/access Unsuccessful 413 Access 414 System Shutdown 415 Dialer Shutdown 416 Successful Upload Access Control: 421 Access Denied

423 424

Access Report by User Forced Access Egress Denied

425

Egress Granted

422

Access Door Propped Open Access Point DSM 427 Trouble Access Point RTE 428 Trouble Access Program 429 Mode Entry Access Program 430 Mode Exit Access Threat 431 Level Change Access 432 Relay/Trigger Fail 433 Access RTE Shunt 434 Access DSM Shunt System Disables: Access Reader 501 Disable 426

56

Zone Status-Auto Arm Time Ext.User # (Restore not applicable) Status-PA Reset (Restore not applicable) Remote-Callback Requested (Restore not applicable) Remote-Successful Access (Restore not applicable) Remote-Unsuccessful Access (Restore not applicable) Remote-System Shutdown Remote-Dialer Shutdown Remote-Successful Upload (Restore not applicable) Access-Access Denied-User # (Restore not applicable) Access-Access Gained-User # (Restore not applicable) Panic-Forced Access-# Access-Egress Denied (Restore not applicable) Access-Egress Granted (Restore not applicable) Access-Door Propped Open# Access-ACS Point DSM Trbl.# Access-ACS Point RTE Trbl.# Access-ACS Prog. Entry-User # (Restore not applicable) Access-ACS Prog. Exit-User # (Restore not applicable) Access-ACS Threat Level Chg. Access-ACS Relay/Trig. Fail# Access-ACS RTE Shunt-# Access-ACS DSM Shunt-#

Table 86:

#

Event Codes (continued)

Event Type

Sounder/Relay Disables: Sounder/Relay 520 Disable 521 Bell 1 Disable 522 Bell 2 Disable Alarm Relay 523 Disable Trouble Relay 524 Disable Reversing Relay 525 Disable Notification 526 Appliance Ckt #3 Notification 527 Appliance Ckt #4 System Peripheral Disables: 531 Module Added 532

Module Removed

Communication Disables: 551 Dialer Disabled Radio Xmitter 552 Disabled Remote 553 Upload/Download Bypasses: Zone/Sensor 570 Bypass 571 Fire Bypass 24 Hour Zone 572 Bypass 573 Burg. Bypass 574 Group Bypass 575 Swinger Bypass 576 Access Zone Shunt Access Point 577 Bypass

Zone Disable-Sounder/Relay-# Disable-Bell/Siren #1 Disable-Bell/Siren #2 Disable-Alarm Relay Disable-Trouble Relay Disable-Reversing Relay Disable-Notification Appl. Ckt #3 Disable-Notification Appl. Ckt #4 Super.-Module Added (Restore not applicable) Super.-Module Removed (Restore not applicable) Disable-Dialer Disable Disable-Radio Disable Disable-Rem. Up/Download Disable Bypass-Zone Bypass-# Bypass-Fire Bypass-# Bypass-24 Hour Bypass-# Bypass-Burg. Bypass-# Bypass-Group Bypass-User # Bypass-Swinger Bypass-# Access-ACS Zone Shunt-# Access-ACS Point Bypass-#

Disable-Access Rdr. Disable#

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications . Table 86:

#

Event Codes (continued)

Event Type

Test/Misc.: 601 Manual Test 602

Periodic Test

603

Periodic RF Xmission Fire Test Status Report To Follow Listen-In To Follow

604 605 606 607 608 609

Walk-Test Mode System Trouble Present Video XMTR Active

611

Point Tested OK

612

Point Not Tested

Intrusion Zone Walk Tested Fire Zone Walk 614 Tested Panic Zone Walk 615 Tested 616 Service Request Event Log: 621 Event Log Reset 613

622

Event Log 50% Full

623

Event Log 90% Full

624

Event Log Overflow

625

Time/Date Reset

626

Time/Date Inaccurate Program Mode Entry Program Mode Exit

627 628

Zone Test-Manually Triggered (Restore not applicable) Test-Periodic (Restore not applicable) Test-Periodic Radio (Restore not applicable) Test-Fire Walk Test-User # Test-Fire Walk-User # Listen-Listen-In Active (Restore not applicable) Test-Walk Test Mode-User # Test-System Trouble Present (Restore not applicable) Listen-Video Xmitter Active (Restore not applicable) Test-Point Tested OK-# (Restore not applicable) Test-Point Not Tested-# (Restore not applicable) Test-Intrn Zone Walk Test-# (Restore not applicable) Test-Fire Zone Walk Test-# (Restore not applicable) Test-PA Zone Walk Test (Restore not applicable) Trouble-Service Request

Table 86:

#

Event Codes (continued)

Event Type

Scheduling: 630 Schedule Change 631 632

Exception Sched. Change Access Schedule Changes

Zone Trouble-Schedule Changed (Restore not applicable) Trouble-Esc. Sched. Changed (Restore not applicable) Trouble-Access Sched. Changed (Restore not applicable)

Personnel Monitoring: Senior Watch 641 Trouble-Senior Watch Trouble Trouble Latch-key Status-Latch-key Super-User 642 Supervision # (Restore not applicable) Special Codes: 750These codes are used by Protection ONLY & can be 789 assigned any unique non-standard Event code, which Pro 1 will be tracking.

Trouble-Event Log Reset (Restore not applicable) Trouble-Event Log 50% Full (Restore not applicable) Trouble-Event Log 90% Full (Restore not applicable) Trouble-Event Log Overflow (Restore not applicable) Trouble-Time/Date Reset-User # (Restore not applicable) Trouble-Time/Date Invalid Trouble-Program Mode Entry (Restore not applicable) Trouble-Program Mode Exit (Restore not applicable)

Bosch Security Systems | 1/05 | 4998122703D

57

D6600 | Computer Interface Manual | Appendix B: Internal Messages

Appendix B: Internal Messages Table 87:

Internal Messages

#

Internal Messages

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14.

Acknowledge † Keypad Operation † Service Required Set Time Battery Missing † Battery Present Battery Bad Battery Restore AC Fail AC Restore † Paper In † Paper Out † Local Parameter Program In Local Parameter Program † Successful † Local Software Program In Local Software Program † Successful † Local Program Failure † Local Program Denied Remote Parameter Program In Remote Parameter Program Successful Remote Software Program In Remote Software Program Successful Remote Program Failure † Remote Program Denied † Printer On Line † Printer Off Line External PRT Error External PRT Restore † Internal PRT Error † Internal PRT Restore Busy Seconds COM3 Error COM3 Trouble COM3 Restore UPS AC Fail UPS AC Restore UPS Battery Low UPS Battery Restore

15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. 38.

D6500 Output††

SIA †† Output

X X X X X X X X X X X X X

0 1 2 9 10 11 12 13 14 15 16 17 18

[NYZ] [NYX] [NJT] [NYM] [NYR] [NYT] [NYR] [NAT] [NAR] [NVI] [NVO] [NLB] [NLS]

Acknowledge OPERATOR KEYPAD OPERATION SERVICE REQUIRED TIME SET BATTERY MISSING BATTERY PRESENT BATTERY BAD BATTERY RESTORE AC FAIL AC RESTORE PAPER IN PAPER OUT LOCAL PARM PROGRAM IN LOCAL PARM PROGRAM SUCCESSFUL

X 41 X 42

[NLB] [NLS]

LOCAL SOFTWARE PROGRAM IN LOCAL SOFTWARE PROGRAM SUCCESS

X X X X

43 44 45 46

[NLU] [NLD] [NRB] [NRS]

LOCAL PROGRAM FAILURE LOCAL PROGRAM DENIED REMOTE PARM PROGRAM IN REMOTE PARM PROGRAM OK

X 47 X 48

[NRB] [NRS]

REMOTE SOFTWARE PROGRAM IN REMOTE SOFTWARE PROGRAM SUCCESS

X 49 X 50 X 19 X 20 X 21 X 22 X 21 X 22 bbb B X 30 X 31 X 32 X 33 X 34 X 35 X 36

[NRU] [NRD] [NVY] [NVZ] [NVT] [NVR] [NVT] [NVR] [NYBbbb] [NYC] [NYS] [NYK] [NUA01] [NUR01] [NUA02] [NUR02]

REMOTE PROGRAM FAILURE REMOTE PROGRAM DENIED PRINTER ON LINE PRINTER OFF LINE EXTERNAL PRINTER ERROR EXTERNAL PRINTER RESTORE INTERNAL PRINTER ERROR INTERNAL PRINTER RESTORE BUSY SECONDS bbb% COMPUTER ERROR COMPUTER TROUBLE COMPUTER RESTORE UPS AC FAIL UPS AC RESTORE UPS BATTERY LOW UPS BATTERY RESTORE



Internal message is not currently implemented.

††

Output messages are abbreviated for clarity

58

Printer Output

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix B: Internal Messages . Table 87:

Internal Messages (continued)

#

Internal Messages

D6500 Output††

SIA Output††

Printer Output

39. 40. 41. 42. 43. 44. 45.

System Reset † System Default System Temperature High System Temperature Restore Slotx/Linex (Lxx) Line Fault Slotx/Linex (Lxx) Line Restore Slotx/Linex (Lxx) Line Card Trouble Slotx/Linex (Lxx) Line Card Restore Slotx/Linex (Lxx) Audio In Slotx/Linex (Lxx) Audio Done Slotx/Linex (Lxx) † Communication Error Slotx/Linex (Lxx) † Communication Restr Slotx/Linex (Lxx) Data Error Slotx/Linex (Lxx) No Data Received Slotx/Linex (Lxx) Reset † Slotx/Linex (Lxx) Codec Error Slotx/Linex (Lxx) Private Call Slotx/Linex (Lxx) No Call Number Slotx/Linex (Lxx) Caller Unknown Set Date Stop Two Way Audio † CPU Data Error † Network Error † Network Restore Account Status Failure Account Status Restore Supervision Rate Changed Switch To Intercept Mode Switch to Fallback Mode Diable Intercept Mode Activate Output Deactivate Output C900 Reboot C900 Battery Low C900 Battery Restore C900 Switched to Intercept C900 Switched to Fallback C900 Output Activated

X X X X X X X

[NYW01] [NYG] [NKA] [NKR] [NLT] [NLR] [NYD]

SYSTEM RESET SYSTEM DEFAULT SYSTEM TEMPERATURE HIGH SYSTEM TEMPERATURE RESTORE PHONE LINE FAULT PHONE LINE RESTORE LINE CARD TROUBLE

X 8

[NYE]

LINE CARD RESTORE

* L X 60

[NLF] [NLE] [NUA03]

AUDIO IN AUDIO DONE COMMUNICATION ERROR

X 61

[NUR03]

COMMUNICATION RESTR

X 62 X 63

[NYN] [NUT04]

DATA ERROR NO DATA RECEIVED

X 64 X 65 P N

[NYW02] [NUT05] [NUT06] [NUT07]

RESET CODEC ERROR PRIVATE CALL NO CALL NUMBER

U

[NUT08]

CALLER UNKNOWN

X 51 X 52 X 53 X 54 X 55 T B02 N B02 X 66 X 88 X 81 X 83 X 84 X 86 X 59 X 58 X 68 X 87 X 82 X 85

[NJD] [CLK] [NYN01] [NNT] [NNR] [NYC] [NYK] [NCO0001] [NCO0002] [NCO0003] [NCO0004] [NCO0005] [NCO0006] [NSC0001] [NSC0002] [NSC0003] [NSC0004] [NSC0005] [NSC0006]

DATE SET TWO WAY AUDIO STOP CPU DATA ERROR NETWORK TROUBLE NETWORK RESTORE COMMUNICATIONS FAILURE COMMUNICATIONS RESTORED SUPERVISION RATE CHANGED SWITCH TO INTERCEPT MODE SWITCH TO FALLBACK MODE DISABLE INTERCEPT MODE ACTIVATE OUTPUT DEACTIVATE OUTPUT C900 REBOOT C900 BATTERY LOW C900 BATTERY RESTORE C900 SWITCHED TO INTERCEPT C900 SWITCHED TO FALLBACK C900 OUTPUT ACTIVATED

46. 47. 48. 49. 50. 51. 52. 53. 54. 55. 56. 57. 58. 59. 60. 61. 62. 63. 64. 65. 66. 67. 68. 69. 70. 71. 72. 73. 74. 75. 76.

37 38 39 40 5 6 7



Internal message is not currently implemented.

††

Output messages are abbreviated for clarity

Bosch Security Systems | 1/05 | 4998122703D

59

D6600 | Computer Interface Manual | Appendix B: Internal Messages

Table 87:

Internal Messages (continued)

#

Internal Messages

D6500 Output††

SIA Output††

Printer Output

77. 78. 79. 80. 81. 82. 83.

C900 Output Deactivated C900 Input Shorted C900 Input Open C900 Input Restored C900 Intercept Enabled C900 Intercept Disabled No Acknowledgement Received Not Dialing Dialing Error No Response to Handshake No Response to Acknowledgement Message Unknown Invalid Message 30 Minutes Since Fallback Command

X X X X X X X

94 89 90 91 92 93 71

[NSC0007] [NSC0008] [NSC0009] [NSC0010] [NSC0011] [NSC0012] [NYU0001]

C900 OUTPUT DEACTIVATED C900 INPUT SHORTED C900 INPUT OPEN C900 INPUT RESTORED C900 INTERCEPT ENABLED C900 INTERCEPT DISABLED NO ACKNOWLEDGEMENT RECEIVED

X X X X

72 73 74 75

[NYU0002] [NYU0003] [NYU0004] [NYU0005]

NOT DIALING DIALING ERROR NO RESPONSE TO HANDSHAKE NO RESPONSE TO ACK

X 76 X 77 X 95

[NYU0006] [NYU0007] [NMI0001]

MESSAGE UNKNOWN INVALID MESSAGE 30 MIN SINCE FALLBACK CMD

84. 85. 86. 87. 88. 89. 90. †

Internal message is not currently implemented.

††

Output messages are abbreviated for clarity

60

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages .

Appendix C: Radionics Modem IIIa2 Messages For lines that are grouped, Gxx appears instead of Lxx

Table 88:

1.

2.

3.

4.

Radionics Modem IIIa2 Messages

Event

Device/Mode

Display

Abort (User not identified)

Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa ABORT BY USER +++ACC aaaa AREA=a h1rrlssssssaaaasIsD41t [#aaaa|NriaAB] dd/dd tt:tt Lxx ACC aaaa ABORT BY USER +++ACC aaaa AREA=a ID=iii h1rrlssssssaaaasIsiiit [#aaaa|Nria/idiiiAB] dd/dd tt:tt Lxx ACC aaaa ABORT BY USER +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasIiiiit [#aaaa|Nriaa/idiiiiAB] dd/dd tt:tt Lxx ACC aaaa ACCESS GRANTED +++ ACC aaaa AREA=a CRD=iii-x POINT=ppp h1rrlssssssaaaaAGspppt [#aaaa|Nria/idiiiDGppp] or [#aaaa|Nria/idiii/ssxDGppp] dd/dd tt:tt Lxx ACC aaaa ACCESS GRANTED +++ACC aaaa AREA=aa CRD=iiii POINT=ppp h1rrlssssssaaaaAGspppt [#aaaa|Nria/idiiiiDGppp] dd/dd tt:tt Lxx ACC aaaa ACCESS GRANTED +++ACC aaaa AREA=aa CRD=iii-x POINT=pppp h1rrlssssssaaaaAGppppt [#aaaa|Nriaa/idiiiDGpppp] or [#aaaa|Nriaa/idiii/ssxDGpppp] dd/dd tt:tt Lxx ACC aaaa ACCESS GRANTED +++ACC aaaa AREA=aa CRD=iiii POINT=pppp h1rrlssssssaaaaAGppppt [#aaaa|Nriaa/idiiiiDGpppp] dd/dd tt:tt Lxx ACC aaaa AC FAILURE +++ACC aaaa AREA=aa h1rrlssssssaaaasPsssst [#aaaa|NriaaAT] dd/dd tt:tt Lxx ACC aaaa AC FAILURE h1rrlssssssaaaasPsssst [#aaaa|NAT]

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasTssszt [#aaaa|NATO]

Abort (users < 255)

Abort (users > 254)

Access Granted

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

5.

6.

7.

8.

Access Granted (point < 255, user > 254) Access Granted (point > 254, user < 255) Access Granted (point > 254, user > 255) AC Fail (Area reported)

9.

AC Fail

10.

AC Fail

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

Bosch Security Systems | 1/05 | 4998122703D

Explanation

TROUBLE

ZN z

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

No AC power. Control panel is running on battery power only. You can program the control panel to defer this report. 2, z=0

61

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

11.

AC Fail (as a rider)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasPsssst [#aaaa|NAT]

12.

AC Fail Since Last Call

Printer: D6500 Mode: SIA Mode:

+++ ACC aaaa h1rrlssssssaaaaSPsssst [#aaaa|OAT]

13.

AC Restoral (Area reported)

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa AC RESTORAL +++ACC aaaa AREA=aa h1rrlssssssaaaasRsss0t [#aaaa|NriaaAR] dd/dd tt:tt Lxx ACC aaaa AC RESTORAL h1rrlssssssaaaasRsss0t [#aaaa|NAR] dd/dd tt:tt Lxx ACC aaa RESTORAL ZN z h1rrlssssssaaaasRssszt [#aaaa|NURO] dd/dd tt:tt AC RESTORED RCVR rr h1rrssssssssssssXss14t [NAR] dd/dd tt:tt AC TROUBLED RCVR rr h1rrssssssssssssXss13t [NAT] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT h1rrlssssssaaaasAsssst [#aaaa|NBA]

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasAssszzt [#aaaa|NBAz] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasAszyyt [#aaaa|NBAzyy] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasAssxxt [#aaaa|NBAxx] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasAss16t [#aaaa|NBA16]

Printer:

dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|NriaaBApppp]

14.

AC Restoral

15.

AC Restoral

16.

AC Restored

17.

AC Troubled

18.

Alarm

19.

Alarm

20.

Alarm

21.

Alarm

22.

Alarm

23.

Alarm (points > 254)

D6500 Mode: SIA Mode:

62

AC FAILED

AC FAILURE

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

No AC power. Control anel is running on battery power only. This report is sent along with the next report transmitted - it is not transmitted independently.

2, D9112

No AC power. Control panel is running on battery power only. You can program the control panel to defer this report.

5.

AC power restored.

D7112

2, z=0

Unexpanded alarm report. Alarm report from the POINT in the AREA specified in the second line of the report.

ALARM ZN z

1,10

2,9

ALARM ZN zyy

ALARM ZN zxx

ALARM ZN 16

Alarm condition on the zone number shown.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

24.

25.

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Alarm (with Ground Fault) (points > 254)

Printer:

dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa GROUND FAULT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|NriaaBApppp] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ ACC aaaa POINT=ppp +++ ACC aaaa ID=iii POINT=ppp h1rrlssssssaaaasAspppt [#aaaa|NBAppp]

Alarm (Area Not Reported)

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: 26.

27.

28.

29.

30.

31.

32.

Alarm (points < 255)

Alarm with Recent Closing Created due to alarm within 2 min of close (points < 255)

Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

Alarm with Recent Closing Created due to alarm within 2 min of close (points > 254, user < 255) Alarm with Recent Closing Created due to alarm within 2 min of close (points > 254, user > 254)

Printer:

Alarm with Recent Closing Created due to alarm within 5 min of close (with Ground Fault) (points > 254, user < 255) Alarm with Recent Closing Created due to alarm within 5 min of close (with Ground Fault) (points > 254, user > 254) Alarm Cross Point (points < 255)

Printer:

D6500 Mode: SIA Mode:

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

Printer:

D6500 Mode: SIA Mode:

Printer:

D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Unexpanded alarm report. Alarm report from the POINT in the AREA specified in the second line of the report.

dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasAspppt [#aaaa|NriaBAppp] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa RECENT CLOSING +++ACC aaaa AREA=a ID=iii POINT=ppp h1rrlssssssaaaasAspppt [#aaaa|Nria/idiiiCRppp] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa RECENT CLOSING +++ACC aaaa AREA=aa ID=iii POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|Nriaa/idiiiCRpppp]

dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa RECENT CLOSING +++ACC aaaa AREA=aa ID=iiii POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|Nriaa/idiiiiCRpppp] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa RECENT CLOSING +++ACC aaaa GROUND FAULT +++ACC aaaa AREA=aa ID=iii POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|Nriaa/idiiiCRpppp]

dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa RECENT CLOSING +++ACC aaaa GROUND FAULT +++ACC aaaa AREA=aa ID=iiii POINT=pppp h1rrlssssssaaaasAsppppt [#aaaa|Nriaa/idiiiiCRpppp]

dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa CROSS POINT +++ACC aaaa AREA=a CG=gg POINT=ppp h1rrlssssssaaaasAspppt [#aaaa|NriaBMppp]

Bosch Security Systems | 1/05 | 4998122703D

63

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

33.

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Explanation

Alarm Cross Point

Printer:

dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ ACC aaaa CROSS POINT +++ ACC aaaa POINT=ppp h1rrlssssssaaaasAspppt [#aaaa|NBMppp] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa CROSS POINT +++ACC aaaa AREA=aa CG=gg POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|NriaaBMpppp] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa CROSS POINT, GROUND FAULT +++ACC aaaa AREA=aa CG=gg POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|NriaaBMpppp] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa DOOR FORCED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|NriaaDFpppp] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ ACC aaaa EXIT ERROR h1rrlssssssaaaasAspppt [#aaaa|NidiiiEAppp]

Unexpanded alarm report. Alarm report from the POINT in the AREA specified in the second line of the report.

(Area Not Reported) 34.

35.

36.

37.

38.

39.

40.

41.

42.

43.

64

Alarm Cross Point (points > 254)

Alarm Cross Point (with Ground Fault) (points > 254) Alarm Door Forced (points > 254)

Alarm Exit Error (Area Not Reported)

Alarm Exit Error (points < 255)

Alarm Exit Error (points > 254, user < 255)) Alarm Exit Error (points > 254, user > 254) Alarm Exit Error (with Ground Fault) (points > 254, user < 255)

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Unexpanded alarm report. Alarm report from the POINT in the AREA specified in the second line of the report.

dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa EXIT ERROR +++ACC aaaa AREA=a ID=iii POINT=ppp h1rrlssssssaaaasAspppt [#aaaa|Nria/idiiiEAppp] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa EXIT ERROR +++ACC aaaa AREA=aa ID=iii POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|Nriaa/idiiiEApppp] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa EXIT ERROR +++ACC aaaa AREA=aa ID=iiii POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|Nriaa/idiiiiEApppp] dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa EXIT ERROR, GROUND FAULT +++ACC aaaa AREA=aa ID=iii POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|Nriaa/idiiiEApppp]

Alarm Exit Error (with Ground Fault) (points > 254, user > 254)

Printer:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa ALARM REPORT +++ACC aaaa EXIT ERROR, GROUND FAULT +++ACC aaaa AREA=aa ID=iiii POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|Nriaa/idiiiiEApppp]

Alarm Fire

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasFssszt [#aaaa|NFAz]

FIRE FR z

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

44.

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Alarm Silenced

Printer:

dd/dd tt:tt Lxx ACC aaaa ALARM SILENCED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaFSppppt [#aaaa|NriaaFLpppp] dd/dd tt:tt Lxx ACC aaaa ALL PTS TESTED h1rrlssssssaaaasRsssFt [#aaaa|NTC] dd/dd tt:tt Lxx ACC aaaa ANALOG RESTORE +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasRspppt [#aaaa|NriaANppp] dd/dd tt:tt Lxx ACC aaaa ANALOG RESTORE +++ACC aaaa SENSOR DIRTY +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasRspppt [#aaaa|NriaANppp] dd/dd tt:tt Lxx ACC aaaa ANALOG RESTORE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasRsppppt [#aaaa|NriaaANpppp] dd/dd tt:tt Lxx ACC aaaa ANALOG RESTORE +++ACC aaaa SENSOR DIRTY +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasRsppppt [#aaaa|NriaaANpppp] dd/dd tt:tt Lxx ACC aaaa ANALOG SERVICE +++ACC aaaa SENSOR DIRTY +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasTspppt [#aaaa|NriaASppp] dd/dd tt:tt Lxx ACC aaaa ANALOG SERVICE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasTsppppt [#aaaa|NriaaASpppp] dd/dd tt:tt Lxx ACC aaaa ANALOG SERVICE +++ACC aaaa SENSOR DIRTY +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasTsppppt [#aaaa|NriaaASpppp] dd/dd tt:tt Lxx ACC aaaa ANALOG SERVICE +++ACC aaaa AREA=aa POINT=pppp +++ACC aaaa LEVEL=lll VALUE=vvv h1rrlssssssaaaasTsppppt [#aaaa|Nriaa/lvlll/vavvvASpppp] dd/dd tt:tt Lxx ACC aaaa AREA WATCH +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasNsD51t [#aaaa|Nria/idiiiTW] dd/dd tt:tt Lxx ACC aaaa WATCH MODE END +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasNsD52t [#aaaa|Nriaa/idiiiiTZ] dd/dd tt:tt Lxx ACC aaaa WATCH START +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasNsD51t [#aaaa|Nriaa/idiiiiTW]

45.

All Points Tested

46.

Analog Restoral (points < 255)

47.

48.

49.

50.

51.

52.

53.

54.

55.

56.

Analog Restoral (points < 255)

Analog Restoral (points > 254) Analog Restoral (points > 254)

Analog Service (points < 255)

Analog Service (points > 254)

Analog Service (points > 254)

Analog Service (points > 254) (Level and Value Reported) Area Watch

Area Watch (Watch mode ended) (users > 254) Area Watch (Watch mode started) (users > 254)

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Bosch Security Systems | 1/05 | 4998122703D

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

65

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

57.

Audio Done

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx AUDIO DONE h1rrlsssssssssssLsssst [NLE]

58.

Audio In

59.

Battery Low

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx AUDIO IN h1rrlsssssssssss*sssst [NLF] dd/dd tt:tt Lxx ACC aaaa BATTERY LOW h1rrlssssssaaaasTsss9t [#aaaa|NYT]

60.

Battery Low

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z h1rrlssssssaaaasTssszt [#aaaa|NBT9] dd/dd tt:tt Lxx ACC aaaa BATTERY LOW +++ACC aaaa AREA=aa h1rrlssssssaaaasTsss9t [#aaaa|NriaaYT] +++ ACC aaaa BATTERY LOW h1rrlssssssaaaaSTsssst [#aaaa|OYT]

61.

Battery Low (Area reported)

Explanation

63.

Battery Low Since Last Call

64.

Battery Missing Since Last Call

Printer: D6500 Mode: SIA Mode:

+++ ACC aaaa h1rrlssssssaaaaSTsssst [#aaaa|OYM]

65.

Battery Restoral (Area reported)

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa BATTERY RESTORE +++ACC aaaa AREA=aa h1rrlssssssaaaasRsss9t [#aaaa|NriaaYR] dd/dd tt:tt Lxx ACC aaaa BATTERY MISSING h1rrlssssssaaaasTsss9t [#aaaa|NYM]

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z h1rrlssssssaaaasTssszt [#aaaa|NBT9] dd/dd tt:tt BATTERY MISSING RCVR rr h1rrssssssssssssXsss9t [NYM] dd/dd tt:tt BATTERY PRESENT RCVR rr h1rrssssssssssssXss10t [NYR] dd/dd tt:tt Lxx ACC aaaa BATTERY RESTORE h1rrlssssssaaaasRsss9t [#aaaa|NYR]

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasRssszt [#aaaa|NUR9]

66.

Battery Missing

67.

Battery Missing

68.

Battery Missing

69.

Battery Present

70.

Battery Restoral

71.

Battery Restoral

66

BATTERY MISSING

RESTORAL ZN z

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The control panel battery discharged to 11.8 VDC or less. 2, z=9

The control panel battery discharged to 11.8 VDC or less.

5.

The control panel battery is connected incorrectly, disconnected, or completely discharged.

5.

The control panel battery is connected incorrectly, disconnected, or completely discharged. 2, z=9

The control panel battery charged to 13.2 VDC after a BATTERY LOW was reported (the battery is fully charged at 13.8 VDC). 2, z=9

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

72.

Battery Restoral

73.

Blank Line

dd/dd tt:tt BATTERY RESTORED RCVR rr h1rrssssssssssssXss12t [NYR] print blank line (CR and LF)

74.

Busy Seconds

75.

Bypass, Command

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

76.

Bypass, Programmer

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

77.

78.

79.

80.

81.

82.

Bypass, Remote (Call back)

Printer:

Bypass, Remote (No Call back)

Printer:

Bypass Restore

Printer:

Bypass Restore (points < 255)

Bypass Restore (point < 255) (Fire point)

Bypass Restore (points < 255) (Supervisory point)

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx BUSY SECONDS bbb% RCVR rr h1rrlsssssssbbbsBsssst [NYBbbb] dd/dd tt:tt Lxx ACC aaaa COMMAND BYPASS +++ ACC aaaa AREA=a ID=iii POINT=ppp h1rrlssssssaaaasNspppt [#aaaa|Nria/idiiiUBppp] dd/dd tt:tt Lxx ACC aaaa PROGRAMR BYPASS +++ ACC aaaa AREA=a POINT=ppp SDI=ddd h1rrlssssssaaaasNspppt [#aaaa|Nria/pidddUBppp]

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The POINT in the AREA in the second line of the report is faulted, and was bypassed by a programmer with the specified serial device number when the system was armed.

dd/dd tt:tt Lxx ACC aaaa RAM BYPASS +++ ACC aaaa AREA=a POINT=ppp PH#=h h1rrlssssssaaaasNspppt [#aaaa|Nria/phhUBppp]

The POINT in the AREA specified in the second line of the report is faulted, and was bypassed by a RAM through the specified phone line.

dd/dd tt:tt Lxx ACC aaaa RAM BYPASS +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasNspppt [#aaaa|NriaUBppp]

The POINT in the AREA specified in the second line of the report is faulted, and was bypassed by a RAM through the specified phone line.

dd/dd tt:tt Lxx ACC aaaa BYPASS RESTORE +++ACC aaaa POINT=ppp h1rrlssssssaaaaRBspppt [#aaaa|NUUppp] dd/dd tt:tt Lxx ACC aaaa BYPASS RESTORE +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaRBspppt [#aaaa|NriaUUppp] dd/dd tt:tt Lxx ACC aaaa BYPASS RESTORE +++ACC aaaa FIRE POINT +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaRBspppt [#aaaa|NriaFUppp] dd/dd tt:tt Lxx ACC aaaa BYPASS RESTORE +++ACC aaaa SUPERVISORY POINT +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaRBspppt [#aaaa|NriaSUppp]

Bosch Security Systems | 1/05 | 4998122703D

67

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

83.

84.

85.

86.

87.

88.

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Bypass Restore (points < 255) (Waterflow point))

Printer:

dd/dd tt:tt Lxx ACC aaaa BYPASS RESTORE +++ACC aaaa WATERFLOW POINT +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaRBspppt [#aaaa|NriaWUppp] dd/dd tt:tt Lxx ACC aaaa BYPASS RESTORE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaRBppppt [#aaaa|NriaaUUpppp] dd/dd tt:tt Lxx ACC aaaa BYPASS RESTORE +++ACC aaaa FIRE POINT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaRBppppt [#aaaa|NriaaFUpppp] dd/dd tt:tt Lxx ACC aaaa BYPASS RESTORE +++ACC aaaa SUPERVISORY POINT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaRBppppt [#aaaa|NriaaSUpppp] dd/dd tt:tt Lxx ACC aaaa BYPASS RESTORE +++ACC aaaa WATERFLOW POINT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaRBppppt [#aaaa|NriaaWUpppp]

Bypass Restore (point > 254)

Bypass Restore (point > 254) (Fire point)

Bypass Restore (point > 254) (Supervisory point) Bypass Restore (point > 254) (Waterflow point)

Bypass, Sked

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

dd/dd tt:tt Lxx ACC aaaa SKED BYPASS +++ ACC aaaa AREA=a POINT=ppp SKED=kk h1rrlssssssaaaasNspppt [#aaaa|Nria/aikkUBppp]

The POINT in the AREA in the second line of the report is faulted, and was bypassed when the system was armed by the specified Sked.

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa SWINGER BYPASS +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasNspppt [#aaaa|NriaUBppp]

The POINT in the AREA in the second line of the report (that was programmed for swinger bypass) is faulted, and was bypassed while the system was armed. If the point restores while the system is armed, it returns to the system, and is ready to detect faults. A system in alarm was disarmed before the bell time expired. The specified point sends a Cancel Report for the alarmed area.

D6500 Mode: SIA Mode:

89.

Bypass, Swinger

Explanation

Printer:

90.

Cancel

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaas\sssst [#aaaa|NOC]

CANCEL REPORT

91.

Cancel

Cancel

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaas\sssit [#aaaa|NOCi] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaas\siyyt [#aaaa|NOCiyy]

CANCEL ID i

92.

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

68

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

CANCEL ID iyy

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

93.

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Cancel Alarm

Printer:

dd/dd tt:tt Lxx ACC aaaa CANCEL ALARM +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaas\sssst [#aaaa|Nria/idiiiBC]

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

1.

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaas\sssst [#aaaa|NidiiiBC]

CANCEL ALARM ID=iii

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

dd/dd tt:tt Lxx ACC aaaa CANCEL ALARM +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaas\siiit [#aaaa|Nria/idiiiBC]

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

D6500 Mode: SIA Mode: 94.

95.

Cancel Alarm (Area Not Reported)

Printer:

Cancel Alarm (Non-Fire)

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: 96.

97.

Cancel Alarm (Non-Fire)

Cancel Alarm (Non-Fire) (users > 254)

98.

Cancel Alarm by Area

99.

Cancel, Fire Alarm

100. Card Assigned (By Programmer)

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: 101. Card Assigned (By Programmer) (users > 254) 102. Card Assigned (By Remote)

Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: 103. Card Assigned (By Remote) (users > 254)

Printer:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa CANCEL ALARM +++ACC aaaa AREA=a h1rrlssssssaaaas\sssst [#aaaa|NriaBC] dd/dd tt:tt Lxx ACC aaaa CANCEL ALARM +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaas\iiiit [#aaaa|Nriaa/idiiiiBC] dd/dd tt:tt Lxx ACC aaa CANCEL REPORT h1rrlssssssaaaas\sssst [#aaaa|NOC]

A system in alarm was disarmed before the bell time expired. The specified point sends a Cancel Report for the alarmed area.

2, 9

dd/dd tt:tt Lxx ACC aaaa FIRE CANCEL +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaas\siiit [#aaaa|Nria/idiiiFC] dd/dd tt:tt Lxx ACC aaaa CARD ASSIGNED +++ ACC aaaa BY PROGRAMMER +++ ACC aaaa CRD=iii-x SDI=ddd h1rrlssssssaaaasNsD30t [#aaaa|NpidddDAiii] or [#aaaa|Npiddd/ssxDAiii] dd/dd tt:tt Lxx ACC aaaa CARD ASSIGNED +++ACC aaaa BY PROGRAMMER +++ACC aaaa CRD=iiii SDI=ddd h1rrlssssssaaaasNsD30t [#aaaa|Npiddd/DAiiii] dd/dd tt:tt Lxx ACC aaaa CARD ASSIGNED +++ ACC aaaa BY REMOTE +++ ACC aaaa CRD=iii-x h1rrlssssssaaaasNsD30t [#aaaa|NDAiii] or [#aaaa|NssxDAiii] dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa +++ACC aaaa h1rrlssssssaaaasNsD30t [#aaaa|NDAiiii]

Bosch Security Systems | 1/05 | 4998122703D

CARD ASSIGNED BY REMOTE CRD=iiii

69

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

104. Card Assigned (By User)

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa CARD ASSIGNED +++ ACC aaaa BY USER +++ ACC aaaa CRD=iii-x ID=iii h1rrlssssssaaaasNsD30t [#aaaa|NidiiiDAiii] or [#aaaa|Nidiii/ssxDAiii] dd/dd tt:tt Lxx ACC aaaa CARD ASSIGNED +++ACC aaaa BY USER h1rrlssssssaaaasNsD30t [#aaaa|NDA] dd/dd tt:tt Lxx ACC aaaa CARD ASSIGNED +++ACC aaaa BY USER +++ACC aaaa CRD=iiii ID=iiii h1rrlssssssaaaasNsD30t [#aaaa|NidiiiiDAiiii] dd/dd tt:tt Lxx ACC aaaa CARD DELETED +++ACC aaaa BY USER h1rrlssssssaaaasNsD31t [#aaaa|NDB] dd/dd tt:tt Lxx ACC aaaa CARD DELETED +++ACC aaaa BY USER +++ACC aaaa CRD=iiii ID=iiii h1rrlssssssaaaasNsD31t [#aaaa|NidiiiiDBiiii] dd/dd tt:tt Lxx ACC aaaa CARD DELETED +++ACC aaaa BY PROGRAMMER +++ACC aaaa CRD=iiii SDI=ddd h1rrlssssssaaaasNsD31t [#aaaa|NpidddDBiiii] dd/dd tt:tt Lxx ACC aaaa CARD DELETED +++ACC aaaa BY REMOTE +++ACC aaaa CRD=iiii h1rrlssssssaaaasNsD31t [#aaaa|NDBiiii] dd/dd tt:tt Lxx CARD RESTORED RCVR rr h1rrlsssssssssssXsss8t [NYE] dd/dd tt:tt Lxx CARD TROUBLED RCVR rr h1rrlsssssssssssXsss7t [NYD] dd/dd tt:tt Nll ACC aaaa STATUS CHANGED +++ aaaa C900 BATTERY LOW h1rrlssssssaaaasXss58t [#aaaa|NSC0002] dd/dd tt:tt Lxx ACC aaaa CHECKSUM FAIL h1rrlssssssaaaasAsD12t [#aaaa|NYX]

D6500 Mode: SIA Mode: 105. Card Assigned (By User, User not identified) 106. Card Assigned (By User) (users > 254)

107. Card Deleted (By User, User not identified) 108. Card Deleted (By User) (users > 254)

109. Card Deleted (By Programmer) (users > 254) 110. Card Deleted (By Remote) (users > 254)

111. Card Restored

112. Card Troubled

113. Change Of Status (C900 Battery Low) 114. Checksum Fail

115. Checksum Fail (SDI Device and Point reported)

70

Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Explanation

dd/dd tt:tt Lxx ACC aaaa CHECKSUM FAIL +++ ACC aaaa POINT=ppp SDI=ddd h1rrlssssssaaaasAspppt [#aaaa|NpidddYXppp]

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The program in the control panel is corrupt. Send service immediately. The program in the control panel is corrupt. Send service immediately.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

116. Closing

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NCL]

CLOSING REPORT

117. Closing

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

CLOSING ZN i

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsssit [#aaaa|NCLi] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsssit [#aaaa|NCLi] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsiyyt [#aaaa|NCLiyy] dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasCsiiit [#aaaa|NidiiiCL]

121. Closing by Account (area not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasCsssit [#aaaa|NCLi]

122. Closing by Account

Printer:

CLOSING REPORT ID=iii

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasCsiiit [#aaaa|NidiiiCL]

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

123. Closing by Account (ID not reported) (area not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NCL]

CLOSING REPORT

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

1,

124. Closing by Account (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasCsssst [#aaaa|NCL]

CLOSING REPORT

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

2,

125. Closing by Area

Printer:

dd/dd tt:tt Lxx ACC aaaa CLOSING REPORT +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiCL]

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

1.

118. Closing

119. Closing

120. Closing by Account

D6500 Mode: SIA Mode: 126. Closing by Area 127. Closing by Area

128. Closing by Area (users > 254)

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Explanation

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

CLOSING ID i

CLOSING ID iyy

CLOSING REPORT ID=iii

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

CLOSING ZN i

2, i = user id.

dd/dd tt:tt Lxx ACC aaa CLOSING ZN z h1rrlssssssaaaasCssszt [#aaaa|NCLz] dd/dd tt:tt Lxx ACC aaaa CLOSING REPORT +++ACC aaaa AREA=a h1rrlssssssaaaasCsssst [#aaaa|NriaCL] dd/dd tt:tt Lxx ACC aaaa CLOSING REPORT +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiCL]

Bosch Security Systems | 1/05 | 4998122703D

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

D7112

D7112

2, z = area number

71

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

129. Closing by Area (ID not reported)

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NriaCL]

CLOSING REPORT AREA=a

130. Closing Early By Account

Printer:

CLOSING EARLY ID=iii

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasCsiiit [#aaaa|NidiiiCK]

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasCsssit [#aaaa|NCLi] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NCK]

CLOSING ZN i

133. Closing Early by Account (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasCsssst [#aaaa|NCL]

134. Closing Early By Area

Printer:

dd/dd tt:tt Lxx ACC aaaa CLOSING EARLY +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiCK]

131. Closing Early by Account 132. Closing Early By Account (ID not reported)

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

135. Closing Early By Area

136. Closing Early by Area 137. Closing Early By Area (ID not reported)

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

138. Closing Early By Area (users > 254) 139. Closing Late by Account (area not reported)

72

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NriaCK] dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasCssszt [#aaaa|NCLz] dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NriaCK]

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

1,

A user with the ID in the second line of the report armed the AREA before the programmed closing time window.

1,

D7112

D7112

2, i = user id.

CLOSING EARLY

CLOSING REPORT

A user with the ID in the second line of the report armed the AREA before the programmed closing time window.

1,

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

2,

A user with the ID in the second line of the report has armed the AREA before the programmed closing time window.

1.

D7112

D7112

CLOSING EARLY AREA=a

CLOSING ZN z

2, z = area number

CLOSING EARLY AREA=a

dd/dd tt:tt Lxx ACC aaaa CLOSING EARLY +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiCK] dd/dd tt:tt Lxx ACC aaaa CLOSING LATE +++ ACC aaaa ID=iii h1rrlssssssaaaasCsiiit [#aaaa|NidiiiCJ]

A user with the ID in the second line of the report armed the AREA before the programmed closing time window.

1,

A user with the ID in the second line of the report armed the AREA after the programmed closing time window.

1,

D7112

D7112

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasCsssit [#aaaa|NCLi]

CLOSING ZN i

141. Closing Late by Account (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NCJ]

CLOSING LATE

142. Closing Late by Account (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasCsssst [#aaaa|NCL]

143. Closing Late by Area

Printer:

dd/dd tt:tt Lxx ACC aaaa CLOSING LATE +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiCJ]

140. Closing Late by Account

D6500 Mode: SIA Mode:

144. Closing Late by Area 145. Closing Late by Area

146. Closing Late by Area (users > 254) 147. Closing Late by Area (ID not reported)

148. Command Bypass

149. Command Bypass

150. Command Bypass (point < 255, user > 254) 151. Command Bypass (point > 254, user < 255)

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140 2, i = user id

CLOSING REPORT

dd/dd tt:tt Lxx ACC aaa CLOSING ZN z h1rrlssssssaaaasCssszt [#aaaa|NCLz] dd/dd tt:tt Lxx ACC aaaa CLOSING LATE +++ACC aaaa AREA=a h1rrlssssssaaaasCsssst [#aaaa|NriaCJ] dd/dd tt:tt Lxx ACC aaaa CLOSING LATE +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiCJ] dd/dd tt:tt Lxx ACC aaaa CLOSING LATE +++ ACC aaaa AREA=a h1rrlssssssaaaasCsssst [#aaaa|NriaCJ]

dd/dd tt:tt Lxx ACC aaaa COMMAND BYPASS +++ ACC aaaa AREA=a POINT=ppp ID=iii h1rrlssssssaaaasNspppt [#aaaa|Nria/idiiiUBppp] dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z h1rrlssssssaaaasTssszt [#aaaa|NBTz]

A user with the ID in the second line of the report armed the AREA after the programmed closing time window.

1,

The system armed or disarmed with a passcode or COMMAND 1 reporting no User ID.

2,

A user with the ID in the second line of the report armed the AREA after the programmed closing time window.

1.

D7112

D7112

2, z = area number

A user with the ID in the second line of the report armed the AREA after the programmed closing time window.

1, D7112

1.

9, D9112

dd/dd tt:tt Lxx ACC aaaa COMMAND BYPASS +++ACC aaaa AREA=a ID=iiii POINT=ppp h1rrlssssssaaaasNspppt [#aaaa|Nria/idiiiiUBppp] dd/dd tt:tt Lxx ACC aaaa COMMAND BYPASS +++ACC aaaa AREA=aa ID=iii POINT=pppp h1rrlssssssaaaasNppppt [#aaaa|Nriaa/idiiiUBpppp]

Bosch Security Systems | 1/05 | 4998122703D

73

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

152. Comm Fail

153. Comm Fail (SDI Device not reported)

154. Comm Restoral

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasTsB01t [#aaaa|NphhYC] dd/dd tt:tt Lxx ACC aaaa

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

155. Comm Restoral (SDI Device not reported)

Printer:

156. Communicatio ns Fail (2212/9112)

Printer:

158. Communicatio ns Trouble (Route Group and SDI Device# reported) 159. Communicatio ns Trouble Restoral

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

COMM FAIL

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasNsB01t [#aaaa|NrggYK]

RG=g

COMM RESTORAL PHONE#=h

The PHONE# specified in the second line of the report was restored.

COMM RESTORAL RG=g

The PHONE# specified in the second line of the report was restored.

dd/dd tt:tt Lxx ACC aaaa COMM FAIL +++ACC aaaa PH#=hh h1rrlssssssaaaasTsB01t [#aaaa|NphhhYC] dd/dd tt:tt Lxx ACC aaaa COMM TROUBLE +++ACC aaaa PH#=hh h1rrlssssssaaaasTsB01t [#aaaa|NphhhYS] dd/dd tt:tt Lxx ACC aaaa COMM TROUBLE +++ACC aaaa RG=g SDI=ddd h1rrlssssssaaaasTsB01t [#aaaa|Nrgg/pidddYS]

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa COMM TRBL RESTR +++ACC aaaa PH#=hh h1rrlssssssaaaasNsB01t [#aaaa|NphhhYK] dd/dd tt:tt Lxx ACC aaaa COMM TRBL RESTR +++ACC aaaa RG=g SDI=ddd h1rrlssssssaaaasNsB01t [#aaaa|Nrgg/pidddYK]

161. Computer Error

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx COMPUTER ERROR h1rr0sssssssssssXss30t [NYC]

Indicates a complete loss of communication between receiver and automation system.

162. Computer Restore

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx COMPUTER RESTORE h1rr0sssssssssssXss32t [NYK]

Indicates that communication between the receiver and the automation system was restored.

163. Computer Trouble

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx COMPUTER TROUBLE h1rr0sssssssssssXss31t [NYS]

Indicates that an automation message was rejected by the automation software.

160. Communicatio ns Trouble Restoral (Route Group and SDI Device# reported)

74

Printer:

h1rrlssssssaaaasTsB01t [#aaaa|NrggYC] dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasNsB01t [#aaaa|NphhYK]

D6500 Mode: SIA Mode: Printer:

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

COMM FAIL PHONE#=h

+++ ACC aaaa

D6500 Mode: SIA Mode:

157. Communicatio ns Trouble

Explanation

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

164. Create Status Report

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasSsssst [#aaaa|NYY]

165. Custom Function (Custom Function Initiated)

Printer:

dd/dd tt:tt Lxx ACC aaaa CUSTOM FUNCTION +++ACC aaaa BY CUSTOM FUNCTION +++ACC aaaa CUST.FX=fff AREA=aa ICF=fff h1rrlssssssaaaasNsD39t [#aaaa|Nriaa/cffffCXfff] dd/dd tt:tt Lxx ACC aaaa CUSTOM FUNCTION +++ACC aaaa BY SKED +++ACC aaaa CUST.FX=fff AREA=aa SKED=kkk h1rrlssssssaaaasNsD39t [#aaaa|Nriaa/aikkkCXfff] dd/dd tt:tt Lxx ACC aaaa CUSTOM FUNCTION +++ACC aaaa BY USER +++ACC aaaa CUST.FX=fff AREA=aa ID=iii h1rrlssssssaaaasNsD39t [#aaaa|Nriaa/idiiiCXfff] dd/dd tt:tt Lxx ACC aaaa CUSTOM FUNCTION +++ACC aaaa BY USER +++ACC aaaa CUST.FX=fff AREA=aa ID=iiii h1rrlssssssaaaasNsD39t [#aaaa|Nriaa/idiiiiCXfff] dd/dd tt:tt Lxx ACC aaaa CUSTOM FUNCTION +++ACC aaaa BY USER +++ACC aaaa CUST.FX=fff AREA=aa h1rrlssssssaaaasNsD39t [#aaaa|NriaaCXfff] dd/dd tt:tt Lxx ACC aaaa DATE CHANGED +++ ACC aaaa ID= iii h1rrlssssssaaaasNsD07t [#aaaa|NidiiiJD]

166. Custom Function (Sked Initiated) 167. Custom Function (users < 255) (User Initiated) 168. Custom Function (users > 254) User Initiated) 169. Custom Function (User Initiated, User not identified) 170. Date Changed

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

171. Date Changed

Printer: D6500 Mode: SIA Mode:

172. Date Changed

173. Date Changed (users > 254)

174. Diagnostic

175. Diagnostic

Printer: D6500 Mode: SIA Mode: Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasNsD07t [#aaaa|NidiiiJD]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasNsD07t [#aaaa|NJD] dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasNsD07t [#aaaa|NidiiiiJD] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasYsssst [#aaaa|NYX]

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasYssszt [#aaaa|NYXz]

Bosch Security Systems | 1/05 | 4998122703D

Explanation

STATUS REPORT

DATE CHANGED ID=iii

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Indicates that the next report is an Account Status Report.

The user changed the control panel date or time with the ID specified in the second line of the report.

D9112

The user changed the control panel date or time with the ID specified in the second line of the report.

DATE CHANGED

DATE CHANGED ID=iiii

DIAG REPORT

A Command 42 was entered at a keypad to send a diagnostic report. No service conditions in trouble memory to report.

DIAG ZN z

75

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

176. Door Closed, Restoral

177. Door Cycled

178. Door Cycled (By User)

179. Door Cycled (By Programmer) (points > 254) 180. Door Cycled (By Remote) (points > 254)

181. Door Cycled (By User) (points < 255, users > 254) 182. Door Cycled (By User) (points > 254, users < 255) 183. Door Cycled (By User) (points > 254, users > 254) 184. Door Cycled (By User, User not identified) (points < 255) 185. Door Cycled (By User, User not identified) (points > 254) 186. Door Cycled (points > 254)

187. Door Left Open

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa REST-DR CLOSED +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasRspppt [#aaaa|NriaDHppp] dd/dd tt:tt Lxx ACC aaaa DOOR CYCLED +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaAGspppt [#aaaa|NriaDGppp] dd/dd tt:tt Lxx ACC aaaa DOOR CYCLED +++ ACC aaaa BY USER +++ ACC aaaa AREA=a ID=iii POINT=ppp h1rrlssssssaaaaAGspppt [#aaaa|Nria/idiiiDGppp] dd/dd tt:tt Lxx ACC aaaa DOOR CYCLED +++ACC aaaa BY PROGRAMMER +++ACC aaaa AREA=aa POINT=pppp SDI=ddd h1rrlssssssaaaaAGppppt [#aaaa|Nriaa/pidddDGpppp] dd/dd tt:tt Lxx ACC aaaa DOOR CYCLED +++ACC aaaa BY REMOTE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaAGppppt [#aaaa|NriaaDGpppp] dd/dd tt:tt Lxx ACC aaaa DOOR CYCLED +++ACC aaaa BY USER +++ACC aaaa AREA=a ID=iiii POINT=ppp h1rrlssssssaaaaAGspppt [#aaaa|Nria/idiiiiDGppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

76

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The Modifier “/ssx” refers to the Data Type Address, not the Modifiers “idiii,” or “piddd”

dd/dd tt:tt Lxx ACC aaaa DOOR CYCLED +++ACC aaaa BY USER +++ACC aaaa AREA=aa ID=iii POINT=pppp h1rrlssssssaaaaAGppppt [#aaaa|Nriaa/idiiiDGpppp] dd/dd tt:tt Lxx ACC aaaa DOOR CYCLED +++ACC aaaa BY USER +++ACC aaaa AREA=aa ID=iiii POINT=pppp h1rrlssssssaaaaAGpppptv [#aaaa|Nriaa/idiiiiDGpppp] dd/dd tt:tt Lxx ACC aaaa DOOR CYCLED +++ACC aaaa BY USER +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaAGspppt [#aaaa|NriaDGppp] dd/dd tt:tt Lxx ACC aaaa DOOR CYCLED +++ACC aaaa BY USER +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaAGppppt [#aaaa|NriaaDGpppp] dd/dd tt:tt Lxx ACC aaaa DOOR CYCLED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaAGppppt [#aaaa|NriaaDGpppp] dd/dd tt:tt Lxx ACC aaaa DOOR LFT OPN +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaAOspppt [#aaaa|NriaDNppp]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

188. Door Left Open (points > 254) 189. Door Left Open (Point text reported)

190. Door Left Open, Alarm

191. Door Left Open, Alarm (points > 254) 192. Door Left Open, Alarm (Text reported)

193. Door Left Open, Alarm (Point text and User Name reported) 194. Door Left Open, Trouble

195. Door Left Open, Trouble (Text reported)

196. Door Left Open, Trouble (Point text and User name reported) 197. Door Locked

198. Door Locked (Automatic)

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa DOOR LEFT OPEN +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaAOppppt [#aaaa|NriaaDNpppp] dd/dd tt:tt Lxx ACC aaaa DOOR LFT OPN +++ ACC aaaa AREA=a POINT=ppp +++ ACC aaaa (ptext) h1rrlssssssaaaaAOspppt [#aaaa|NriaDNppp] dd/dd tt:tt Lxx ACC aaaa ALRM-DR LFT OPN +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasAspppt [#aaaa|NriaDLppp] dd/dd tt:tt Lxx ACC aaaa ALRM-DR LFT OPN +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|NriaaDLpppp] dd/dd tt:tt Lxx ACC aaaa ALRM-DR LFT OPN +++ ACC aaaa AREA=a POINT=ppp +++ ACC aaaa (text) h1rrlssssssaaaasAspppt [#aaaa|NriaDLppp] dd/dd tt:tt Lxx ACC aaaa ALRM-DR LFT OPN +++ ACC aaaa AREA=a POINT=ppp +++ ACC aaaa (ptext) +++ ACC aaaa (uname) h1rrlssssssaaaasAspppt [#aaaa|NriaDLppp] dd/dd tt:tt Lxx ACC aaaa TRBL-DR LFT OPN +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasTspppt [#aaaa|NriaDLppp] dd/dd tt:tt Lxx ACC aaaa TRBL-DR LFT OPN +++ ACC aaaa AREA=a POINT=ppp +++ ACC aaaa (text) h1rrlssssssaaaasTspppt [#aaaa|NriaDMppp] dd/dd tt:tt Lxx ACC aaaa TRBL-DR LFT OPN +++ ACC aaaa AREA=a POINT=ppp +++ ACC aaaa (text) +++ ACC aaaa (uname) h1rrlssssssaaaasTspppt [#aaaa|NriaDMppp] dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaALspppt [#aaaa|NriaDYLpp] dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ ACC aaaa AUTOMATIC +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaALspppt [#aaaa|NriaDYppp]

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

Bosch Security Systems | 1/05 | 4998122703D

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

77

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

199. Door Locked (Automatic) (points > 254)

200. Door Locked (By Programmer) (points > 254) 201. Door Locked (By Remote) (points > 254)

202. Door Locked (By Sked) (points > 254)

203. Door Locked (By User)

204. Door Locked (By User) (points > 254, users < 255) 205. Door Locked (By User) (points > 254, users > 254) 206. Door Locked (By User, User not identified) (points < 255) 207. Door Locked (By User, User not identified) (points > 254) 208. Door Locked (points > 254)

209. Door Request (Request to Enter) (points > 254) 210. Door Request (Request to Exit) (points > 254)

78

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ACC aaaa AUTOMATIC +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaALppppt [#aaaa|NriaaDYpppp] dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ACC aaaa BY PROGRAMMER +++ACC aaaa AREA=aa POINT=pppp SDI=ddd h1rrlssssssaaaaALppppt [#aaaa|Nriaa/pidddDYpppp] dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ACC aaaa BY REMOTE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaALppppt [#aaaa|NriaaDYpppp] dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ACC aaaa BY SKED +++ACC aaaa AREA=aa POINT=pppp SKED=kkk h1rrlssssssaaaaALppppt [#aaaa|Nriaa/aikkkDYpppp] dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ ACC aaaa BY USER +++ ACC aaaa AREA=a ID=iii POINT=ppp h1rrlssssssaaaaALspppt [#aaaa|Nria/idiiiDYppp] dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ACC aaaa BY USER +++ACC aaaa AREA=aa ID=iii POINT=pppp h1rrlssssssaaaaALppppt [#aaaa|Nriaa/idiiiDYpppp] dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ACC aaaa BY USER +++ACC aaaa AREA=aa ID=iiii POINT=pppp h1rrlssssssaaaaALppppt [#aaaa|Nriaa/idiiiiDYpppp] dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ACC aaaa BY USER +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaALspppt [#aaaa|NriaDYppp] dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ACC aaaa BY USER +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaALppppt [#aaaa|NriaaDYpppp] dd/dd tt:tt Lxx ACC aaaa DOOR LOCKED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaALppppt [#aaaa|NriaaDYpppp] dd/dd tt:tt Lxx ACC aaaa REQUEST TO ENTR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaAGppppt [#aaaa|NriaaDEpppp] dd/dd tt:tt Lxx ACC aaaa REQUEST TO EXIT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaAGppppt [#aaaa|NriaaDXpppp]

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

211. Door Request (REX)

212. Door Request (REX, Denied) (Interlock Deny) 213. Door Request (REX, Denied) (Door Secured) 214. Door Request (RTE)

215. Door Request (RTE, Denied) (Door Secured) (points > 254) 216. Door Request (RTE, Denied) (Interlock Deny) (points > 254) 217. Door Request (RTX, Denied) (Door Secured) (points > 254) 218. Door Request (RTX, Denied) (Interlock Deny) (points > 254) 219. Door Secured

220. Door Secured (Automatic)

221. Door Secured (Automatic) (points > 254)

222. Door Secured (By Programmer) (points > 254)

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa REQUEST TO EXIT +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaAGspppt [#aaaa|NriaDXppp] dd/dd tt:tt Lxx ACC aaaa REQUEST TO EXIT +++ ACC aaaa DENIED-INTERLOCK +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaADspppt [#aaaa|NriaDKppp] dd/dd tt:tt Lxx ACC aaaa REQUEST TO EXIT +++ ACC aaaa DENIED-DOOR SECURED +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaADspppt [#aaaa|NriaDKppp]

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa REQUEST TO ENTR +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaAGspppt [#aaaa|NriaDEppp] dd/dd tt:tt Lxx ACC aaaa REQUEST TO ENTR +++ACC aaaa DENIED-DOOR SECURED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|NriaaDKpppp] dd/dd tt:tt Lxx ACC aaaa REQUEST TO ENTR +++ACC aaaa DENIED-INTERLOCK +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|NriaaDKpppp] dd/dd tt:tt Lxx ACC aaaa REQUEST TO EXIT +++ACC aaaa DENIED-DOOR SECURED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|NriaaDKpppp] dd/dd tt:tt Lxx ACC aaaa REQUEST TO EXIT +++ACC aaaa DENIED-INTERLOCK +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|NriaaDKpppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaASspppt [#aaaa|NriaDCppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ ACC aaaa AUTOMATIC +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaASspppt [#aaaa|NriaDCppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ACC aaaa AUTOMATIC +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaASppppt [#aaaa|NriaaDCpppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ACC aaaa BY PROGRAMMER +++ACC aaaa AREA=aa POINT=pppp SDI=ddd h1rrlssssssaaaaASppppt [#aaaa|Nriaa/pidddDCpppp]

Bosch Security Systems | 1/05 | 4998122703D

79

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

223. Door Secured (By Remote) (points > 254)

224. Door Secured (By Sked) (points > 254)

225. Door Secured (By User)

226. Door Secured (By User) (points 254) 227. Door Secured (By User) (points > 254, users < 255) 228. Door Secured (By User) (points > 254, users > 254) 229. Door Secured (By User, User not identified) (points < 255) 230. Door Secured (By User, User not identified) (points > 254) 231. Door Secured (points > 254)

232. Door Unlocked

233. Door Unlocked (Automatic)

234. Door Unlocked (By User)

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ACC aaaa BY REMOTE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaASppppt [#aaaa|NriaaDCpppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ACC aaaa BY SKED +++ACC aaaa AREA=aa POINT=pppp SKED=kkk h1rrlssssssaaaaASppppt [#aaaa|Nriaa/aikkkDCpppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ ACC aaaa BY USER +++ ACC aaaa AREA=a ID-iii POINT=ppp h1rrlssssssaaaaASspppt [#aaaa|Nria/idiiiDCppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ACC aaaa BY USER +++ACC aaaa AREA=a ID=iiii POINT=ppp h1rrlssssssaaaaASspppt [#aaaa|Nria/idiiiiDCppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ACC aaaa BY USER +++ACC aaaa AREA=a ID=iii POINT=pppp h1rrlssssssaaaaASppppt [#aaaa|Nriaa/idiiiDCpppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ACC aaaa BY USER +++ACC aaaa AREA=a ID=iiii POINT=pppp h1rrlssssssaaaaASppppt [#aaaa|Nriaa/idiiiiDCpppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ACC aaaa BY USER +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaASspppt [#aaaa|NriaDCppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ACC aaaa BY USER +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaASppppt [#aaaa|NriaaDCpppp] dd/dd tt:tt Lxx ACC aaaa DOOR SECURED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaASppppt [#aaaa|NriaaDCpppp] dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaAUspppt [#aaaa|NriaDOppp] dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ ACC aaaa AUTOMATIC +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaAUspppt [#aaaa|NriaDOppp] dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ ACC aaaa BY USER +++ ACC aaaa AREA=a ID=iii POINT=ppp h1rrlssssssaaaaAUspppt [#aaaa|Nria/idiiiDOppp]

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

80

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

235. Door Unlocked (Automatic) (points > 254) 236. Door Unlocked (By Programmer) (points > 254) 237. Door Unlocked (By Remote) (points > 254) 238. Door Unlocked (By Sked) (points > 254) 239. Door Unlocked (By User) (points < 255, users > 254) 240. Door Unlocked (By User) (points > 254, users < 255) 241. Door Unlocked (By User) (points >254, users > 254) 242. Door Unlocked (By User, User not identified) (points > 254) 243. Door Unlocked (By User) (points > 254) 244. Duress

245. Duress

Device/Mode

Display

Printer:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ACC aaaa AUTOMATIC +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaAUppppt [#aaaa|NriaaDOpppp] dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ACC aaaa BY PROGRAMMER +++ACC aaaa AREA=aa POINT=pppp SDI=ddd h1rrlssssssaaaaAUppppt [#aaaa|Nriaa/pidddDOpppp] dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ACC aaaa BY REMOTE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaAUppppt [#aaaa|NriaaDOpppp] dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ACC aaaa BY SKED +++ACC aaaa AREA=aa POINT=pppp SKED=kkk h1rrlssssssaaaaAUppppt [#aaaa|Nriaa/aikkkDOpppp] dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ACC aaaa BY USER +++ACC aaaa AREA=a ID=iiii POINT=ppp h1rrlssssssaaaaAUspppt [#aaaa|Nria/idiiiiDOppp] dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ACC aaaa BY USER +++ACC aaaa AREA=aa ID=iii POINT=pppp h1rrlssssssaaaaAUppppt [#aaaa|Nriaa/idiiiDOpppp] dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ACC aaaa BY USER +++ACC aaaa AREA=aa ID=iiii POINT=pppp h1rrlssssssaaaaAUppppt [#aaaa|Nriaa/idiiiiDOpppp] dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ACC aaaa BY USER +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaAUppppt [#aaaa|NriaaDOpppp] dd/dd tt:tt Lxx ACC aaaa DOOR UNLOCKED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaAUppppt [#aaaa|NriaaDOpppp] dd/dd tt:tt Lxx ACC aaaa DURESS +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasDsiiit [#aaaa|Nria/idiiiHA]

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasAssszt [#aaaa|NBAz]

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

ALARM ZN z

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

A user with the ID in the second line of the report initiated a duress from a keypad located in the AREA in the second line of the report.

1.

2, D7112: z=0. D9112: z= as programmed in BFSK Duress Code

Bosch Security Systems | 1/05 | 4998122703D

81

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

246. Duress

247. Duress (Area Not Reported)

248. Duress

Device/Mode

Display

Printer: D6500 Mode: SIA Mode: Printer:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasDssszt [#aaaa|NHAz]

DURESS ID z

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasDsiiit [#aaaa|NidiiiHA]

DURESS ID=iii

A user with the ID in the second line of the report initiated a duress from a keypad located in the AREA in the second line of the report.

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasDsiiit [#aaaa|Nria/idiiiHA]

DURESS ID=iii

A user with the ID in the second line of the report initiated a duress from a keypad located in the AREA in the second line of the report.

D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode:

249. Duress (user > 254)

250. Early Open By Account

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Explanation

dd/dd tt:tt Lxx ACC aaaa DURESS +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasDiiiit [#aaaa|Nriaa/idiiiiHA] dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasOsiiit [#aaaa|NidiiiOK]

EARLY TO OPEN ID=iii

251. Early Open By Account (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasOsssst [#aaaa|NOK]

EARLY TO OPEN

252. Early Open By Account

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasOsssit [#aaaa|NOPi]

OPENING Zn I

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasOsssst [#aaaa|NOP]

OPENING REPORT

253. Early Open By Account (ID not reported) 254. Early Open By Area (ID not reported)

Printer:

255. Early Open By Area

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

256. Early Open By Area

82

Printer: D6500 Mode: SIA Mode:

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasOsssst [#aaaa|NriaOK]

1,

A user with the ID in the second line of the report disarmed the AREA before the programmed opening time window.

1,

D7112

D7112

2, 9.

EARLY TO OPEN AREA=a

dd/dd tt:tt Lxx ACC aaaa EARLY TO OPEN +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasOsiiit [#aaaa|Nria/idiiiOK]

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasOssszt [#aaaa|NOPz]

A user with the ID in the second line of the report disarmed the AREA before the programmed opening time window.

OPENING ZN z

System disarmed. A user with the ID in the second line of the report disarmed the AREA.

2,

A user with the ID in the second line of the report disarmed the AREA before the programmed opening time window.

1,

A user with the ID in the second line of the report disarmed the AREA before the programmed opening time window.

1.

9. D7112

D7112

2, z = area number

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

257. Early To Close (7112 Only) 258. Early To Open (7112 Only) 259. Equipment Fail (Report from UPLINK router indicating ”Transceiver Trouble Condition”) 260. Error

261. Error

262. Error

263. Error

264. Extend Close Time by Area

265. Extend Close Time by Area

266. Extend Close Time by Area (ID not reported) 267. Extend Close Time by Area (users < 255) 268. Extend Close Time by Area (users > 254) 269. Extra Point

Device/Mode

Display

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NCK] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasOsssst [#aaaa|NOK]

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

A user with the ID in the second line of the report extended the closing time of the AREA to the TIME printed.

1.

A user with the ID in the second line of the report extended the closing time of the AREA to the TIME printed.

1,

CLOSING EARLY

EARLY TO OPEN

EQUIPMENT FAIL

+++ ACC aaaa

SDI=255 COND=001

+++ ACC aaaa

UPLINK.

h1rrlssssssaaaasTsD29t [#aaaa|Npi255IA001]

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa [ERROR] ZN h1rrlssssssaaaas[sssst [#aaaa|NRT] dd/dd tt:tt Lxx ACC aaaa [ERROR] ZN z h1rrlssssssaaaas[ssszt [#aaaa|NRTz] dd/dd tt:tt Lxx ACC aaaa [ERROR] ZN zz h1rrlssssssaaaas[sszzt [#aaaa|NRTzz] dd/dd tt:tt Lxx ACC aaaa [ERROR] ZN zzz h1rrlssssssaaaas[szzzt [#aaaa|NRTzzz] dd/dd tt:tt Lxx ACC aaaa EXTN CLOSE TIME +++ ACC aaaa AREA=a ID=iii TIME=hh:mm h1rrlssssssaaaasTsD26t [#aaaa|Nria/idiii/tihhmmCE]

dd/dd tt:tt Lxx ACC aaaa EXTN CLOSE TIME +++ACC aaaa AREA=a TIME=hh:mm h1rrlssssssaaaasTsD26t [#aaaa|Nria/tihhmmCE] dd/dd tt:tt Lxx ACC aaaa EXTN CLOSE TIME +++ ACC aaaa AREA=a TIME=hh:mm h1rrlssssssaaaasTsD26t [#aaaa|Nria/tihhmmCE]

D7112

dd/dd tt:tt Lxx ACC aaaa EXTN CLOSE TIME +++ACC aaaa AREA=a ID=iiii TIME=hh:mm h1rrlssssssaaaasTsD26t [#aaaa|Nriaa/idiiii/tihhmmCE] dd/dd tt:tt Lxx ACC aaaa EXTN CLOSE TIME +++ACC aaaa AREA=aa ID=iiii TIME=hh:mm h1rrlssssssaaaasTsD26t [#aaaa|Nriaa/idiiii/tihhmmCE] dd/dd tt:tt Lxx ACC aaaa EXTRA POINT +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasTspppt [#aaaa|NriaXEppp]

Bosch Security Systems | 1/05 | 4998122703D

83

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

270. Extra Point (points > 254)

271. Extra RF Point

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa EXTRA POINT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasTppppt [#aaaa|NriaaXEpppp]

D6500 Mode: SIA Mode: Printer:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

An extra RF POINT in the AREA in the second line of the report was detected.

1,

Abnormal RAM session termination or beginning of the Command 58 Fire Test.

2.

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasTsD16t [#aaaa|NpidddXF] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasTsD16t [#aaaa|NriaXF]

273. Fail To Call RAM

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasTsssFt [#aaaa|NBTF]

274. Fail To Call RAM

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa BAD CALL TO RAM h1rrlssssssaaaasTsF02t [#aaaa|NRA]

Control panel attempted to call RAM and was unsuccessful.

275. Fail To Close by Area

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasTsssEt [#aaaa|NriaCI]

The AREA in the second line of the report was not armed before the programmed closing time.

272. Extra RF Point Detected

D6500 Mode: SIA Mode:

276. Fail To Close by Area

Printer: D6500 Mode: SIA Mode:

277. Fail To Close, Delinquent

278. Fail To Execute (Door UnlockedInterlock) 279. Fail to Execute (Door UnlockedInterlock) (points > 254) 280. Fail To Execute (Door UnlockedDoor Secured)

84

Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasTsssEt [#aaaa|NriaCI]

EXTRA RF POINT SDI=ddd

EXTRA RF POINT

TROUBLE ZN F

FAIL TO CLOSE AREA=a

FAIL TO CLOSE AREA=a

D7112

The AREA in the second line of the report was not armed before the programmed closing time.

dd/dd tt:tt Lxx ACC aaaa DELNQNT CLOSING +++ACC aaaa AREA=a h1rrlssssssaaaasTsssEt [#aaaa|NriaCD] dd/dd tt:tt Lxx ACC aaaa FAIL TO EXECUTE +++ ACC aaaa DOOR UNLOCKED-INTERLOCK +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasNsD35t [#aaaa|NriaDKppp] dd/dd tt:tt Lxx ACC aaaa FAIL TO EXECUTE +++ACC aaaa DOOR UNLOCKED-INTERLOCK +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasNsD35t [#aaaa|NriaaDKpppp] dd/dd tt:tt Lxx ACC aaaa FAIL TO EXECUTE +++ ACC aaaa DOOR UNLOCKED-DOOR SECURED +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasNsD35t [#aaaa|NriaDKppp]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

281. Fail To Execute (Door UnlockedDoor Secured) (points > 254)

Printer:

dd/dd tt:tt Lxx ACC aaaa FAIL TO EXECUTE +++ACC aaaa DOOR UNLOCKED-DOOR SECURE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasNsD35t [#aaaa|NriaaDKpppp]

282. Fail To Execute (Door UnlockedDoor Secured) (points > 254)

Printer:

283. Fail To Execute (Door UnlockedDoor Secured) (points < 255)

Printer:

284. Fail To Execute (Door CycledInterlock)

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

Explanation

dd/dd tt:tt Lxx ACC aaaa FAIL TO EXECUTE +++ACC aaaa DOOR CYCLED-DOOR SECURED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|NriaaDKpppp] dd/dd tt:tt Lxx ACC aaaa FAIL TO EXECUTE +++ACC aaaa DOOR CYCLED-DOOR SECURE +++ACC aaaa AREA=aa POINT=ppp h1rrlssssssaaaasNsD35t [#aaaa|NriaDKppp]

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa FAIL TO EXECUTE +++ ACC aaaa DOOR CYCLED-INTERLOCK +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaADspppt [#aaaa|NriaDKppp] dd/dd tt:tt Lxx ACC aaaa FAIL TO EXECUTE +++ACC aaaa DOOR CYCLED-INTERLOCK +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|NriaaDKpppp] dd/dd tt:tt Lxx ACC aaaa FAIL TO EXECUTE +++ ACC aaaa DOOR CYCLED-DOOR SECURED +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaADspppt [#aaaa|NriaDKppp] dd/dd tt:tt Lxx ACC aaaa FAIL TO EXECUTE +++ ACC aaaa INCORRECT RESPONSE +++ ACC aaaa SDI=ddd h1rrlssssssaaaasNsD34t [#aaaa|NpidddYX] dd/dd tt:tt Lxx ACC aaaa FAIL TO EXECUTE +++ ACC aaaa NO RESPONSE +++ ACC aaaa SDI=ddd h1rrlssssssaaaasNsD34t [#aaaa|NpidddYX] dd/dd tt:tt Lxx ACC aaaa FAIL TO OPEN +++ ACC aaaa AREA=a h1rrlssssssaaaasTsssEt [#aaaa|NriaOI]

290. Fail To Call RAM

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa BAD CALL TO RAM h1rrlssssssaaaasTsF02t [#aaaa|NRA]

Control panel attempted to call RAM and was unsuccessful.

291. Fire Alarm

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa FIRE ALARM +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasFspppt [#aaaa|NriaFAppp]

Alarm signal from the POINT (programmed with a Fire Point code) and the AREA in the second line of the report.

285. Fail To Execute (Door CycledInterlock) (points > 254) 286. Fail To Execute (Door CycledDoor Secured) 287. Fail To Execute (SDI Device, Incorrect Response) 288. Fail To Execute (SDI Device, No Response) 289. Fail To Open by Area

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Bosch Security Systems | 1/05 | 4998122703D

The AREA in the second line of the report was not disarmed during the programmed opening time window.

1, 10.

85

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasFssszt [#aaaa|NFAz]

293. Fire Alarm (Area Not Reported)

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasFspppt [#aaaa|NFAppp]

294. Fire Alarm (point < 255)

Printer:

292. Fire Alarm

Explanation

FIRE FR z

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140 2, 3, 9.

295. Fire Alarm (point < 255)

296. Fire Alarm (point < 255)

297. Fire Alarm (point < 255)

298. Fire Alarm (point < 255)

299. Fire Alarm Cross point (point > 254)

300. Fire Alarm Crossed Point (Area Not Reported)

301. Fire Alarm Smoke (point > 254)

302. Fire Alarm (point > 254)

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

86

FIRE ALARM POINT=ppp

dd/dd tt:tt Lxx ACC aaaa FIRE ALARM +++ACC aaaa CROSS POINT +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasFspppt [#aaaa|NriaFMppp] dd/dd tt:tt Lxx ACC aaaa FIRE ALARM +++ACC aaaa SMOKE DETECTED +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasFspppt [#aaaa|NriaFAppp] dd/dd tt:tt Lxx ACC aaaa FIRE ALARM +++ACC aaaa HIGH TEMPERATURE DETECTED +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasFspppt [#aaaa|NriaKAppp] dd/dd tt:tt Lxx ACC aaaa FIRE ALARM +++ACC aaaa WATER FLOW DETECTED +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasFspppt [#aaaa|NriaSAppp] dd/dd tt:tt Lxx ACC aaaa FIRE ALARM +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasFppppt [#aaaa|NriaaFApppp] dd/dd tt:tt Lxx ACC aaaa FIRE ALARM +++ACC aaaa CROSS POINT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasFppppt [#aaaa|NriaaFMpppp] dd/dd tt:tt Lxx ACC aaaa FIRE ALARM +++ ACC aaaa CROSS POINT +++ ACC aaaa POINT=ppp h1rrlssssssaaaasFspppt [#aaaa|NFMppp]

Alarm signal from the POINT (programmed with a Fire Point code) and the AREA in the second line of the report.

Alarm signal from the POINT (programmed with a Fire Point code) and the AREA in the second line of the report.

dd/dd tt:tt Lxx ACC aaaa FIRE ALARM +++ACC aaaa SMOKE DETECTED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasFppppt [#aaaa|NriaaFApppp] dd/dd tt:tt Lxx ACC aaaa FIRE ALARM +++ACC aaaa HIGH TEMPERATURE DETECTED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasFppppt [#aaaa|NriaaKApppp]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

303. Fire Alarm (point > 254)

304. Fire Cancel (users > 254)

305. Fire Missing

306. Fire Missing

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa FIRE ALARM +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa WATER FLOW DETECTED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasFppppt [#aaaa|NriaaSApppp] dd/dd tt:tt Lxx ACC aaaa FIRE CANCEL +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaas\iiiit [#aaaa|Nriaa/idiiiiFC]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa MISSING FIRE +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasMspppt [#aaaa|NriaFYppp]

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaaGsssszt [#aaaa|NFTz]

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The POINT (programmed with a Fire Point code) in the AREA in the second line of the report is missing.

1,

TROUBL FR z

10.

2, 3, 9.

307. Fire Missing (points > 254)

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa MISSING FIRE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasMppppt [#aaaa|NriaaFYpppp] dd/dd tt:tt Lxx ACC aaaa FIRE ALM RESTOR +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaHsspppt [#aaaa|NriaFHppp] dd/dd tt:tt Lxx ACC aaaa FIRE ALM RESTOR +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaHsspppt [#aaaa|NriaFJppp]

310. Fire Restoral after Alarm

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaaHsssszt [#aaaa|NFRz]

311. Fire Restoral after Alarm

Printer:

dd/dd tt:tt Lxx ACC aaaa FIRE RESTORAL +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaHsspppt [#aaaa|NriaFRppp]

The POINT (programmed with a Fire Point code) in the AREA specified in the second line of the report was restored after an alarm, trouble, or missing condition.

1,

dd/dd tt:tt Lxx ACC aaaa FIRE RESTORAL +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaHsspppt [#aaaa|NriaFRppp]

The POINT (programmed with a Fire Point code) in the AREA specified in the second line of the report was restored after an alarm, trouble, or missing condition.

1,

308. Fire Restoral (from Fire Alarm) 309. Fire Restoral(from Trouble/Missi ng/Supervision )

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

RESTORAL FR z

2, 3, 9.

D6500 Mode: SIA Mode:

312. Fire Restore after Trouble/Missi ng

Printer: D6500 Mode: SIA Mode:

Bosch Security Systems | 1/05 | 4998122703D

10.

10.

87

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

313. Fire Restore after Trouble/Missi ng

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaaHsssszt [#aaaa|NFRz]

314. Fire Restoral From Fire Alarm (no area)

Printer:

dd/dd tt:tt Lxx ACC aaaa FIRE ALM RESTOR +++ACC aaaa POINT=ppp h1rrlssssssaaaaHsspppt [#aaaa|NFHppp] dd/dd tt:tt Lxx ACC aaaa FIRE ALM RESTOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaHsppppt [#aaaa|NriaaFHpppp] dd/dd tt:tt Lxx ACC aaaa FIRE TBL RESTOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaHsppppt [#aaaa|NriaaFJpppp] dd/dd tt:tt Lxx ACC aaaa FIRE SUPRVISION +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasEspppt [#aaaa|NriaFSppp] dd/dd tt:tt Lxx ACC aaaa FIRE SUPRVISION +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasEppppt [#aaaa|NriaaFSpppp] dd/dd tt:tt Lxx ACC aaaa FIRE SUPRVISION +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasEppppt [#aaaa|NriaaFSpppp] dd/dd tt:tt Lxx ACC aaaa FIRE SUPRVISION +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasEspppt [#aaaa|NriaFSppp] dd/dd tt:tt Lxx ACC aaaa FIRE SUPRV TRBL +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaGsspppt [#aaaa|NriaFWppp]

315. Fire Restoral From Fire Alarm (points > 254) 316. Fire Restoral From Trouble/Missi ng/Supervision 317. Fire Supervision

318. Fire Supervision (points < 255) 319. Fire Supervision (points > 254)

320. Fire Supervision (Water Flow) (points < 255) 321. Fire Supervision (Water Flow) (points > 254) 322. Fire Supervision Restore (points < 255) 323. Fire Supervision Restore (points > 254) 324. Fire Supervision Restore (Water Flow) (points < 255) 325. Fire Supervision Restore (Water Flow) (points > 254)

88

Explanation

RESTORALFR z

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140 2, 3, 9.

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa FIRE SUPRV REST +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasEspppt [#aaaa|NriaFVppp] dd/dd tt:tt Lxx ACC aaaa FIRE SUPRV REST +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasEppppt [#aaaa|NriaaFVpppp] dd/dd tt:tt Lxx ACC aaaa FIRE SUPRV REST +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasEspppt [#aaaa|NriaFVppp] dd/dd tt:tt Lxx ACC aaaa FIRE SUPRV REST +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasEppppt [#aaaa|NriaaFVpppp]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

326. Fire Supervision Trouble (points < 255) 327. Fire Supervision Trouble (points > 254) 328. Fire Supervision Trouble (Water Flow) (points < 255) 329. Fire Supervision Trouble (Water Flow) (points > 254) 330. Fire Supervision Trouble Restore (points < 255)

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa FIRE SUPRV TRBL +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaGsspppt [#aaaa|NriaFWppp] dd/dd tt:tt Lxx ACC aaaa FIRE SUPRV TRBL +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaGsppppt [#aaaa|NriaaFWpppp] dd/dd tt:tt Lxx ACC aaaa FIRE SUPRV TRBL +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaGsppppt [#aaaa|NriaaFWpppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

331. Fire Supervision Trouble Restore (points > 254)

Printer:

332. Fire Supervision Trouble Restore (Water Flow) (points < 255)

Printer:

333. Fire Supervision Trouble Restore (Water Flow) (points > 254)

Printer:

334. Fire Trouble

Printer:

335. Fire Restoral

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Trouble condition from the POINT (programmed with a Fire Point code) in the AREA in the second line of the report.

1,

dd/dd tt:tt Lxx ACC aaaa FIRE SUPRV TRBL +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaGsppppt [#aaaa|NriaaFWpppp] dd/dd tt:tt Lxx ACC aaaa FIR SUPR TR RES +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaHsspppt [#aaaa|NriaFQppp] dd/dd tt:tt Lxx ACC aaaa FIR SUPR TR RES +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaHsppppt [#aaaa|NriaFQpppp] dd/dd tt:tt Lxx ACC aaaa FIR SUPR TR RES +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaHsspppt [#aaaa|NriaFQppp] dd/dd tt:tt Lxx ACC aaaa FIR SUPR TR RES +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaHsppppt [#aaaa|NriaFQpppp]

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa FIRE TROUBLE +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaGsspppt [#aaaa|NriaFTppp]

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaaHsssszt [#aaaa|NFRz]

Printer:

dd/dd tt:tt Lxx ACC aaaa FIRE TROUBLE +++ACC aaaa SMOKE DETECTOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaGsspppt [#aaaa|NriaFTppp]

RESTORAL FR z

10.

2, 3, 9.

336. Fire Trouble (point < 255)

D6500 Mode: SIA Mode:

Bosch Security Systems | 1/05 | 4998122703D

89

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

337. Fire Trouble (point < 255)

338. Fire Trouble (point < 255)

339. Fire Trouble (point < 254)

340. Fire Trouble (with Ground Fault) (point > 254) 341. Fire Trouble (point > 254)

342. Fire Trouble (point > 254)

343. Fire Trouble (point > 254)

344. Fire Walk End

345. Fire Walk End

346. Fire Walk Start

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa FIRE TROUBLE +++ACC aaaa HIGH TEMPERATURE DETECTOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaGsspppt [#aaaa|NriaKTppp] dd/dd tt:tt Lxx ACC aaaa FIRE TROUBLE +++ACC aaaa WATER FLOW DETECTOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaGsspppt [#aaaa|NriaSTppp] dd/dd tt:tt Lxx ACC aaaa FIRE TROUBLE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaGsppppt [#aaaa|NriaaFTpppp] dd/dd tt:tt Lxx ACC aaaa FIRE TROUBLE +++ACC aaaa GROUND FAULT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaGsppppt [#aaaa|NriaaFTpppp] dd/dd tt:tt Lxx ACC aaaa FIRE TROUBLE +++ACC aaaa SMOKE DETECTOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaGsppppt [#aaaa|NriaaFTpppp] dd/dd tt:tt Lxx ACC aaaa FIRE TROUBLE +++ACC aaaa HIGH TEMPERATURE DETECTOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaGsppppt [#aaaa|NriaaKTpppp] dd/dd tt:tt Lxx ACC aaaa FIRE TROUBLE +++ACC aaaa WATER FLOW DETECTOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaGsppppt [#aaaa|NriaaSTpppp] dd/dd tt:tt Lxx ACC aaaa FIRE WALK END +++ ACC aaaa AREA=a h1rrlssssssaaaasRsssFt [#aaaa|NriaFK] dd/dd tt:tt Lxx ACC aaa RESTORAL ZN F h1rrlssssssaaaasRsssFt [#aaaa|NURF] dd/dd tt:tt Lxx ACC aaaa FIRE WALK START +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasTsssFt [#aaaa|Nria/idiiiFI] dd/dd tt:tt Lxx ACC aaa TROUBLE ZN F h1rrlssssssaaaasTsssFt [#aaaa|NBTF]

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

347. Fire Walk Start

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

348. Fire Walk Start

Printer: D6500 Mode: SIA Mode:

90

Explanation

dd/dd tt:tt Lxx ACC aaaa FIRE WALK START +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasTsssFt [#aaaa|Nria/idiiiFI]

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Fire Walk Test ended.

D9112

Fire Walk Test begun.

D9112

Abnormal RAM session termination or beginning of the Command 58 Fire Test.

D9112

Fire Walk Test begun.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

349. Fire Walk Start (no user)

350. Fire Walk Start (users > 254)

351. Fire Walk End (no users)

352. Fire Walk End (users > 254)

353. Force Armed

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa FIRE WALK START +++ACC aaaa AREA=a h1rrlssssssaaaasTsssFt [#aaaa|NriaFI]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa FIRE WALK START +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasTsssFt [#aaaa|Nriaa/idiiiiFI] dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasRsssFt [#aaaa|NriaFK]

FIRE WALK END AREA=a

dd/dd tt:tt Lxx ACC aaaa FIRE WALK END +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasRsssFt [#aaaa|Nriaa/idiiiiFK] dd/dd tt:tt Lxx ACC aaaa WAS FORCE ARMED h1rrlssssssaaaasWsssst [#aaaa|NCW]

Account armed with zones or points faulted. The faulted zones or POPITs were not armed. Zones, areas, or points that were not armed are indicated by a TROUBLE or SHUNTED report.

FORCED CLOSE ID=iii

A user with the ID in the second line of the report armed the AREA while points in the AREA were faulted. Faulted points were not armed.

1,

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasCsiiit [#aaaa|NidiiiCF]

355. Force Close by Account (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NCF]

FORCED CLOSE

A user with the ID in the second line of the report armed the AREA while points in the AREA were faulted. Faulted points were not armed.

1,

356. Force Close by Area

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa FORCED CLOSE h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiCF]

A user with the ID in the second line of the report armed the AREA while points in the AREA were faulted. Faulted points were not armed.

1.

357. Force Close Early by Account

Printer:

dd/dd tt:tt Lxx ACC aaa dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasCsssit h1rrlssssssaaaasWsssst [#aaaa|NCLi] [#aaaa|NCW]

Account armed with zones or points faulted. The faulted zones or POPITs were not armed. Zones, areas, or points which were not armed are indicated by a TROUBLE or SHUNTED report.

2,

354. Force Close by Account

Printer:

D6500 Mode: SIA Mode:

Bosch Security Systems | 1/05 | 4998122703D

CLOSING ZN I WAS FORCE ARMED

D7112

D7112

I = user id.

91

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

358. Force Close Early by Account

Printer:

dd/dd tt:tt Lxx ACC aaaa F CLOSE EARLY +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiCF]

A user with the ID in the second line of the report armed the AREA in the second line of the report after the programmed closing time while points in the AREA were faulted. Faulted points were not armed.

1.

359. Force Close Early by Account (ID not reported)

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NriaCF]

F CLOSE EARLY AREA=a

A user with the ID in the second line of the report armed the AREA in the second line of the report after the programmed closing time while points in the AREA were faulted. Faulted points were not armed.

1,

360. Force Close Early by Account

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasCsiiit [#aaaa|NidiiiCF]

F CLOSE EARLY ID=iii

A user with the ID in the second line of the report armed the AREA in the second line of the report after the programmed closing time while points in the AREA were faulted. Faulted points were not armed.

1,

361. Force Close Early by Account (ID not reported)

Printer:

The system armed/disarmed with a passcode or COMMAND 1 reporting no User ID (D8112G2 excluded). AREA armed by user with the ID in the second line of the report

2,

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasCsssst h1rrlssssssaaaasWsssst [#aaaa|NCL] [#aaaa|NCW]

CLOSING REPORT WAS FORCE ARMED

D7112

D7112 by Account

D7112

Account armed with zones or points faulted. The faulted zones or POPITs were not armed. Zones, areas, or points that were not armed are indicated by a TROUBLE or SHUNTED report. 362. Force Close Early by Account (ID not reported)

92

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NCF]

F CLOSE EARLY

A user with the ID in the second line of the report armed the AREA in the second line of the report after the programmed closing time while points in the AREA were faulted. Faulted points were not armed.

1, D7112

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

363. Forced Close Early by Area

Device/Mode

Display

Explanation

Printer:

dd/dd tt:tt Lxx ACC aaaa F CLOSE LATE +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiCF]

A user with the ID in the second line of the report armed the AREA in the second line of the report after the programmed closing time while points in the AREA were faulted. Faulted points were not armed. A user with the ID in the second line of the report armed the AREA before the programmed closing time while points in the AREA were faulted. Faulted points were not armed. A user with the ID in the second line of the report armed the AREA before the programmed closing time while points in the AREA were faulted. Faulted points were not armed. Account armed with zones or points faulted. The faulted zones or POPITs were not armed. Zones, areas, or points that were not armed are indicated by a TROUBLE or SHUNTED report. A user with the ID in the second line of the report armed the AREA in the second line of the report after the programmed closing time while points in the AREA were faulted. Faulted points were not armed. A user with the ID in the second line of the report armed the AREA in the second line of the report after the programmed closing time while points in the AREA were faulted. Faulted points were not armed. Unexpanded reporting, system armed by arm/disarm passcode or COMMAND 1 (D8112G2 excluded). Unexpanded reporting, system armed by arm/disarm passcode or CMD 1. AREA armed by user with the ID in the second line of the report Account armed with zones or points faulted. The faulted zones or POPITs were not armed. Zones, areas, or points that were not armed are indicated by a TROUBLE or SHUNTED report.

D6500 Mode: SIA Mode:

364. Forced Close Early by Area(ID not reported)

Printer:

365. Forced Close Early by Area

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

366. Force Close Late by Account

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NriaCF]

F CLOSE EARLY AREA=a

dd/dd tt:tt Lxx ACC aaaa FRC CLOSE EARLY +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiCF]

dd/dd tt:tt Lxx ACC aaa CLOSING ZN I dd/dd tt:tt Lxx ACC aaa WAS FORCE ARMED h1rrlssssssaaaasCsssit h1rrlssssssaaaasWsssst [#aaaa|NCLi] [#aaaa|NCW]

367. Force Close Late by Account (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NCF]

F CLOSE LATE

368. Force Close Late by Account

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasCsiiit [#aaaa|NidiiiCF]

F CLOSE LATE ID=iii

369. Force Close Late by Account (ID not reported)

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa CLOSING REPORT dd/dd tt:tt Lxx ACC aaa WAS FORCE ARMED h1rrlssssssaaaasCsssst h1rrlssssssaaaasWsssst [#aaaa|NCL] [#aaaa|NCW]

Bosch Security Systems | 1/05 | 4998122703D

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140 1,

1, D7112

2, i = user id.

1, D7112

1, D7112

2, D7112

93

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

370. Forced Close Early by Area (users > 254) 371. Force Close Early (7112 Only) 372. Force Close Late (7112 Only) 373. Forced Close Late by Area

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa FRC CLOSE EARLY +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiCF] dd/dd tt:tt Lxx ACC aaaa FRC CLOSE EARLY h1rrlssssssaaaasCsssst [#aaaa|NCF] dd/dd tt:tt Lxx ACC aaaa FORC CLOSE LATE h1rrlssssssaaaasCsssst [#aaaa|NCF] dd/dd tt:tt Lxx ACC aaaa FORC CLOSE LATE +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiCF]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

374. Forced Close Late by Area (users > 254) 375. Forced Close Perimeter Delay by Area (ID not reported)

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Explanation

dd/dd tt:tt Lxx ACC aaaa FORC CLOSE LATE +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiCF] dd/dd tt:tt Lxx ACC aaaa F CLOSE PR DLAY +++ ACC aaaa AREA=a h1rrlssssssaaaasCsssst [#aaaa|NriaNF]

376. Forced Close Perimeter Delay by Area (ID not reported)

Printer:

377. Forced Close Perimeter Delay by Area (User ID# > 254 reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa F CLOSE PR DLAY +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiNF]

378. Forced Close Perimeter instant by Area

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa F CLOSE PR INST h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiNF]

94

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa F CLOSE PR DLAY +++ ACC aaaa AREA=a h1rrlssssssaaaasCsssst [#aaaa|NriaNF]

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

A user with the ID in the second line of the report armed the AREA in the second line of the report after the programmed closing time while points in the AREA were faulted. Faulted points were not armed.

A user with the ID in the second line of the report has delay armed the perimeter of the AREA while points in the AREA were faulted. Faulted points were not armed.

1, D7112

A user with the ID in the second line of the report armed the perimeter of the AREA while points in the AREA were faulted. Faulted points were not armed.

A user with the ID in the second line of the report armed the perimeter of the AREA while points in the AREA were faulted. Faulted points were not armed.

1, D7112

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

379. Forced Close Perimeter instant by Area(ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa F CLOSE PR INST h1rrlssssssaaaasCsssst [#aaaa|NriaNF]

A user with the ID in the second line of the report armed the perimeter of the AREA while points in the AREA were faulted. Faulted points were not armed.

1.

380. Forced Close Perimeter Instant by Area (User ID# > 254 reported)

Printer:

dd/dd tt:tt Lxx ACC aaaa F CLOSE PR INST +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiNF]

381. Force Closing by Account

Printer:

Account armed with zones or points faulted. The faulted zones or POPITs were not armed. Zones, areas, or points that were not armed are indicated by a TROUBLE or SHUNTED report.

2,

The system armed/disarmed with a passcode or COMMAND 1 reporting no User ID (D8112G2 excluded). AREA armed by user with the ID in the second line of the report

2,

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

382. Force Closing by Account (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasCsssit h1rrlssssssaaaasWsssst [#aaaa|NCLi] [#aaaa|NCW]

CLOSING ZN I WAS FORCE ARMED

dd/dd tt:tt Lxx ACC aaa dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasCsssst h1rrlssssssaaaasWsssst [#aaaa|NCL] [#aaaa|NCW]

CLOSING REPORT WAS FORCE ARMED

I = user id.

D7112

Account armed with zones or points faulted. The faulted zones or POPITs were not armed. Zones, areas, or points that were not armed are indicated by a TROUBLE or SHUNTED report. 383. Forced Closing by Area

Printer: D6500 Mode: SIA Mode:

384. Forced Closing by Area

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa FORCED CLOSE +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiNF]

A user with the ID in the second line of the report armed the AREA while points in the AREA were faulted. Faulted points were not armed.

dd/dd tt:tt Lxx ACC aaa CLOSING ZN z dd/dd tt:tt Lxx ACC aaa WAS FORCE ARMED h1rrlssssssaaaasCssszt h1rrlssssssaaaasWsssst [#aaaa|NCLz] [#aaaa|NCW]

Account armed with zones or points faulted. The faulted zones or POPITs were not armed. Zones, areas, or points that were not armed are indicated by a TROUBLE or SHUNTED report.

Bosch Security Systems | 1/05 | 4998122703D

2, z = area number

95

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

385. Forced Closing by Area (no area) (users 254) 387. Forced Point

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa FORCED CLOSE +++ACC aaaa ID=iii h1rrlssssssaaaasCsiiit [#aaaa|NidiiiCF] dd/dd tt:tt Lxx ACC aaaa FORCED CLOSE +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiCF] dd/dd tt:tt Lxx ACC aaaa FORCED POINT +++ ACC aaaa AREA=a POINT=ppp ID=iii h1rrlssssssaaaasTspppt [#aaaa|Nria/idiiiXWppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

388. Forced Point

Printer: D6500 Mode: SIA Mode:

389. Forced Point (ID not reported)

390. Forced Point

Printer: D6500 Mode: SIA Mode:

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The POINT in the AREA in the second line of the report was faulted and bypassed when the system was armed.

10,

dd/dd tt:tt Lxx ACC aaaa FORCED POINT +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasTspppt [#aaaa|NriaXWppp]

The POINT in the AREA in the second line of the report was faulted and bypassed when the system was armed.

1,

dd/dd tt:tt Lxx ACC aaaa FORCED POINT +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasTspppt [#aaaa|NriaXWppp]

The POINT in the AREA in the second line of the report was faulted and bypassed when the system was armed.

1,

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z h1rrlssssssaaaasTssszt [#aaaa|NBTz] dd/dd tt:tt Lxx ACC aaaa FORCED POINT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasTppppt [#aaaa|NriaaXWpppp] dd/dd tt:tt Lxx ACC aaaa PROG ACCESS BAD +++ ACC aaaa SDI=ddd h1rrlssssssaaaasTsF01t [#aaaa|NpidddLU]

393. Invalid Remote Access

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasTsssFt [#aaaa|NBTF]

394. Invalid Remote Access (phone not reported)

Printer:

dd/dd tt:tt Lxx ACC aaaa RAM ACCESS FAIL +++ ACC aaaa PHONE#=5 h1rrlssssssaaaasTsssFt [#aaaa|Nph5RU]

395. Invalid Remote Access (from Call Back)

Printer:

391. Forced Point (point > 254)

392. Invalid Local Access

96

Printer: D6500 Mode: SIA Mode: Printer:

Explanation

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

TROUBLE ZN

F

D7112

6, D9112

6, D7112

9.

An unsuccessful attempt was made to locally access the account through the supervised keypad or other serial device specified in the second line of the report. Abnormal RAM session termination or beginning of the Command 58 Fire Test. An unsuccessful attempt was made by a RAM to contact the account on the PHONE# specified in the second line of the report.

D9112

2.

D9112

dd/dd tt:tt Lxx ACC aaaa RAM ACCESS FAIL +++ACC aaaa PH#=hh h1rrlssssssaaaasTsssFt [#aaaa|NphhhRU]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Explanation

396. Invalid Remote Access (no call back)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RAM ACCESS FAIL h1rrlssssssaaaasTsssFt [#aaaa|NpRU]

397. Invalid Remote Access

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RAM ACCESS FAIL h1rrlssssssaaaasTsssFt [#aaaa|NphhRU]

398. Invalid Remote Access

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RAM ACCESS FAIL h1rrlssssssaaaasTsssFt [#aaaa|NRU]

An unsuccessful attempt was made by a RAM to contact the account on the PHONE# specified in the second line of the report. An unsuccessful attempt was made by a RAM to contact the account on the PHONE# specified in the second line of the report. An unsuccessful attempt was made by a RAM to contact the account on the PHONE# specified in the second line of the report.

399. Invalid Report

Printer: D6500 Mode: SIA Mode: Printer:

INVALID REPORT

LATE TO OPEN ID=iii

A user with the ID in the second line of the report disarmed the AREA after the programmed opening time window.

1.

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlsssssssssssXss26t [#aaaa|NYN] dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasOsiiit [#aaaa|NidiiiOJ]

401. Late Opening By Account (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasOsssst [#aaaa|NOJ]

LATE TO OPEN

A user with the ID in the second line of the report disarmed the AREA after the programmed opening time window.

1,

402. Late Opening By Area

Printer:

dd/dd tt:tt Lxx ACC aaaa LATE TO OPEN +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasOsiiit [#aaaa|Nria/idiiiOJ]

A user with the ID in the second line of the report disarmed the AREA after the programmed opening time window.

1,

LATE TO OPEN AREA=a

A user with the ID in the second line of the report disarmed the AREA after the programmed opening time window.

1,

CLOSING LATE

400. Late Opening By Account

D6500 Mode: SIA Mode:

403. Late Opening By Area (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasOsssst [#aaaa|NriaOJ]

404. Late To Close (7112 Only)

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasCsssst [#aaaa|NCJ] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasOsssst [#aaaa|NOJ] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaas*sssst [#aaaa|NLF] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaas*sssst [#aaaa|NLF]

405. Late To Open (7112 Only) 406. Listen In

407. Listen In

Bosch Security Systems | 1/05 | 4998122703D

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140 D9112

D7112

D7112

D7112

D7112

LATE TO OPEN

LISTEN IN

LISTEN jj

97

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

408. Log Threshold

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasTsD01t [#aaaa|NJL]

409. Log Overflow

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa LOG OVERFLOW h1rrlssssssaaaasAsD01t [#aaaa|NJO] +++ ACC aaaa LOG OVERFLOW h1rrlssssssaaaaSLsssst [#aaaa|OJO]

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

+++ ACC aaaa LOG THRESHOLD h1rrlssssssaaaaSBsssst [#aaaa|OJL] dd/dd tt:tt LOW BATTERY RCVR rr h1rrssssssssssssXss11t [NYT] dd/dd tt:tt Lxx ACC aaaa LOW TEMPERATURE +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasLspppt [#aaaa|NriaZAppp] dd/dd tt:tt Lxx ACC aaaa LOW TEMPERATURE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasLppppt [#aaaa|NriaaZApppp] dd/dd tt:tt Lxx ACC aaaa LOW TEMP RESTOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaRLspppt [#aaaa|NriaZRppp] dd/dd tt:tt Lxx ACC aaaa LOW TEMP RESTOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaRLppppt [#aaaa|NriaaZRpppp] dd/dd tt:tt Lxx ACC aaaa MISSING ALARM +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasMspppt [#aaaa|NriaUZppp]

410. Log Overflow Since Last Call

411. Log Threshold Since Last Call 412. Low Battery

413. Low Temperature (points < 255) 414. Low Temperature (points > 254) 415. Low Temperature Restore (points < 255) 416. Low Temperature Restore (points > 254) 417. Missing Alarm

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

418. Missing Alarm

419. Missing Alarm (Area Not Reported) 420. Missing Alarm

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

98

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasAssszt [#aaaa|NBAz] dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasMspppt [#aaaa|NUZppp]

Explanation

LOG THRESHOLD

ALARM

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The log in the control panel reached the programmed percent full point programmed in item Log % Full (default Log Full = 85%).

The log in the control panel reached the programmed percent full point programmed in item Log % Full (default Log Full = 85%).

5.

5.

The POINT in the AREA specified in the second line of the report is missing.

ZN z

1, 10.

2, 9.

MISSING ALARM POINT=ppp

The POINT in the AREA specified in the second line of the report is missing.

dd/dd tt:tt Lxx ACC aaaa MISSING ALARM +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasMspppt [#aaaa|NriaUZppp]

The POINT in the AREA specified in the second line of the report is missing.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

421. Missing Alarm (points > 254)

422. Missing Alarm - Cross Point (points < 255)

423. Missing Alarm - Cross Point (points > 254)

424. Missing Alarm with Recent Closing Created due to alarm within 5 min of close (points > 254, users 254, users >254)

Printer:

426. Missing Alarm - Exit Error (points > 254, users < 255)

Printer:

427. Missing Alarm - Exit Error (points > 254, users > 254) 428. Missing Fire Supervision

429. Missing Fire Supervision (points < 255)

430. Missing Fire Supervision (points > 254) 431. Missing Fire Supervision (points > 254)

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa MISSING ALARM +++ACC aaaa CROSS POINT +++ACC aaaa AREA=a CG=gg POINT=ppp h1rrlssssssaaaasMspppt [#aaaa|NriaXMppp] dd/dd tt:tt Lxx ACC aaaa MISSING ALARM +++ACC aaaa CROSS POINT +++ACC aaaa AREA=aa CG=gg POINT=pppp h1rrlssssssaaaasMppppt [#aaaa|NriaaXMpppp] dd/dd tt:tt Lxx ACC aaaa MISSING ALARM +++ACC aaaa RECENT CLOSING +++ACC aaaa AREA=aa ID=iii POINT=pppp h1rrlssssssaaaasMppppt [#aaaa|Nriaa/idiiiCMpppp]

dd/dd tt:tt Lxx ACC aaaa MISSING ALARM +++ACC aaaa RECENT CLOSING +++ACC aaaa AREA=aa ID=iiii POINT=pppp h1rrlssssssaaaasMppppt [#aaaa|Nriaa/idiiiiCMpppp]

dd/dd tt:tt Lxx ACC aaaa MISSING ALARM +++ACC aaaa EXIT ERROR +++ACC aaaa AREA=aa ID=iii POINT=pppp h1rrlssssssaaaasMppppt [#aaaa|Nriaa/idiiiEZpppp] dd/dd tt:tt Lxx ACC aaaa MISSING ALARM +++ACC aaaa EXIT ERROR +++ACC aaaa AREA=aa ID=iiii POINT=pppp h1rrlssssssaaaasMppppt [#aaaa|Nriaa/idiiiiEZpppp] dd/dd tt:tt Lxx ACC aaaa MISS FIR SUPRVN +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaGMspppt [#aaaa|NriaFZppp] dd/dd tt:tt Lxx ACC aaaa MISS FIR SUPRVN +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaGMspppt [#aaaa|NriaFZppp] dd/dd tt:tt Lxx ACC aaaa MISS FIR SUPRVN +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaGMppppt [#aaaa|NriaaFZpppp] dd/dd tt:tt Lxx ACC aaaa MISS FIR SUPRVN +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaGMppppt [#aaaa|NriaaFZpppp]

Bosch Security Systems | 1/05 | 4998122703D

99

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

432. Missing Supervision

433. Missing Supervision (points > 254) 434. Missing Tbl

435. Missing Trouble 436. Missing Trouble

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa MISSING SUPRVSN +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaMTspppt [#aaaa|NriaBZppp] dd/dd tt:tt Lxx ACC aaaa MISSING SUPRVSN +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaMTppppt [#aaaa|NriaaBZpppp] dd/dd tt:tt Lxx ACC aaaa TROUBLE* ZN zyy h1rrlssssssaaaasVszyyt [#aaaa|NUYzyy] dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z h1rrlssssssaaaasTssszt [#aaaa|NBTz] dd/dd tt:tt Lxx ACC aaaa MISSING TROUBLE +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasVspppt [#aaaa|NriaUYppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

437. Missing Trouble (Area Not Reported)

Printer:

438. Missing Trouble (for use with Keyfob device) (points < 255)

Printer:

439. Missing Trouble (points < 255) 440. Missing Trouble (for use with Keyfob device) (points > 254) 441. Missing Trouble (points > 254) 442. MPU Version

443. No Entry (Door Secured)

100

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Explanation

dd/dd tt:tt Lxx ACC aaaa MISSING TROUBLE +++ ACC aaaa POINT=ppp h1rrlssssssaaaasVspppt [#aaaa|NUYppp]

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

2.

Trouble condition received from the POINT (programmed with a Fire Point code) in the AREA in the second line of the report.

1, 10.

Trouble condition received from the POINT (programmed with a Fire Point code) in the AREA in the second line of the report.

dd/dd tt:tt Lxx ACC aaaa MISSING TROUBLE +++ACC aaaa KEYFOB +++ACC aaaa ID=iii h1rrlssssssaaaasVsD10t [#aaaa|NidiiiUY] dd/dd tt:tt Lxx ACC aaaa MISSING TROUBLE +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasVspppt [#aaaa|NriaUYppp] dd/dd tt:tt Lxx ACC aaaa MISSING TROUBLE +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasVspppt [#aaaa|NriaUYppp] dd/dd tt:tt Lxx ACC aaaa MISSING TROUBLE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasVppppt [#aaaa|NriaaUYpppp] dd/dd tt:tt 6500 MPU vv.vv RCVR rr h3rrs 6500 MPU vv.vvt [A6500 MPU vv.vv] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-SECURE +++ ACC aaaa AREA=a CRD=iii-x POINT=ppp h1rrlssssssaaaaADspppt [#aaaa|Nria/idiiiDZppp] or [#aaaa|Nria/idiii/ssxDZppp]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

444. No Entry (Interlock Deny)

Printer:

445. No Entry (points < 255, user < 255) (AntiPassback)

Printer:

446. No Entry (points > 254, users < 254) (Wrong Arming State)

Printer:

dd/dd tt:tt Lxx ACC aaaa NO ENTRY-INTRLK +++ ACC aaaa AREA=a CRD=iii-x POINT=ppp h1rrlssssssaaaaADspppt [#aaaa|Nria/idiiiDWppp] or [#aaaa|Nria/idiii/ssxDWppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-PASSBK +++ACC aaaa AREA=a CRD=iii-x POINT=ppp h1rrlssssssaaaaADspppt [#aaaa|Nria/idiiiDIppp] or [#aaaa|Nria/idii/ssxDIpppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-ARMED +++ACC aaaa AREA=aa CRD=iiii POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiiDQpppp]

447. No Entry (point > 254, users < 255) (AntiPassback)

Printer:

448. No Entry (points > 254, users < 255) (Door Secured)

Printer:

449. No Entry (points > 254, users < 255) (Interlock Deny)

Printer:

450. No Entry (points > 254, users < 255) (No Rights in Area)

Printer:

451. No Entry (points > 254, users < 255) (Outside Time Window)

Printer:

452. No Entry (points > 254, users > 254) (AntiPassback)

Printer:

453. No Entry (points > 254, users > 254) (Door Secured)

Printer:

454. No Entry (points > 254, users > 254) (Interlock Deny)

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa NO ENTRY-PASSBK +++ACC aaaa AREA=aa CRD=iii-x POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiiDIppp] or [#aaaa|Nriaa/idiii/ssxDIpppp]

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The Modifier “/ssx” refers to the Data Type Address, not the Modifiers “idiii,” or “piddd”

dd/dd tt:tt Lxx ACC aaaa NO ENTRY-SECURE +++ACC aaaa AREA=aa CRD=iii-x POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiDZpppp] or [#aaaa|Nriaa/idiii/ssxDZpppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-INTRLK +++ACC aaaa AREA=aa CRD=iii-x POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiDWpppp] or [#aaaa|Nriaa/idiii/ssxDWpppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-LEVEL +++ACC aaaa AREA=aa CRD=iiii POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiiDVpppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-TIME +++ACC aaaa AREA=aa CRD=iii-x POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiDPpppp] or [#aaaa|Nriaa/idiii/ssxDPpppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-PASSBK +++ACC aaaa AREA=aa CRD=iii-x POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiiDIppp] or [#aaaa|Nriaa/idiii/ssxDIpppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-SECURE +++ACC aaaa AREA=aa CRD=iiii POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiiDZpppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-INTRLK +++ACC aaaa AREA=aa CRD=iiii POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiiDWpppp]

Bosch Security Systems | 1/05 | 4998122703D

101

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

455. No Entry (points > 254, users > 254) (No Rights in Area)

Printer:

dd/dd tt:tt Lxx ACC aaaa NO ENTRY-LEVEL +++ACC aaaa AREA=aa CRD=iiii POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiiDVpppp]

456. No Entry (points > 254, users > 254) (Wrong Arming State)

Printer:

457. No Entry (points > 254, users > 254) (Outside Time Window)

Printer:

458. No Entry (No Rights in Area)

Printer:

459. No Entry (Outside Time Window)

Printer:

460. No Entry (Unknown ID)

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

Explanation

dd/dd tt:tt Lxx ACC aaaa NO ENTRY-ARMED +++ACC aaaa AREA=aa CRD=iii-x POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiDQpppp] or [#aaaa|Nriaa/idiii/ssxDQpppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-TIME +++ACC aaaa AREA=aa CRD=iiii POINT=pppp h1rrlssssssaaaaADppppt [#aaaa|Nriaa/idiiiiDPpppp]

461. No Entry (Wrong Arming State)

Printer:

462. Opening

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa NO ENTRY-LEVEL +++ ACC aaaa AREA=a CRD=iii-x POINT=ppp h1rrlssssssaaaaADspppt [#aaaa|Nria/idiiiDVppp] or [#aaaa|Nria/idiii/ssxDVppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-TIME +++ ACC aaaa AREA=a CRD=iii-x POINT=ppp h1rrlssssssaaaaADspppt [#aaaa|Nria/idiiiDPppp] or [#aaaa|Nria/idiii/ssxDPppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-UNK ID +++ ACC aaaa AREA=a CRD=iii-x POINT=ppp h1rrlssssssaaaaADspppt [#aaaa|Nria/idiiiDDppp] or [#aaaa|Nria/idiii/ssxDDppp] dd/dd tt:tt Lxx ACC aaaa NO ENTRY-ARMED +++ ACC aaaa AREA=a CRD=iii-x POINT=ppp h1rrlssssssaaaaADspppt [#aaaa|Nria/idiiiDQppp] or [#aaaa|Nria/idiii/ssxDQppp] dd/dd tt:tt Lxx ACC aaaa OPENING REPORT h1rrlssssssaaaasOsssst [#aaaa|NOP]

463. Opening

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa OPENING ZN I h1rrlssssssaaaasOsssit [#aaaa|NOPi] dd/dd tt:tt Lxx ACC aaaa OPENING ID I h1rrlssssssaaaasOsssit [#aaaa|NOPi] dd/dd tt:tt Lxx ACC aaaa OPENING ID iyy h1rrlssssssaaaasOsiyyt [#aaaa|NOPiyy] dd/dd tt:tt Lxx ACC aaaa OPENING REPORT h1rrlssssssaaaasOsiiit [#aaaa|NidiiiOP]

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

464. Opening

465. Opening

466. Opening By Account

102

D6500 Mode: SIA Mode:

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

System disarmed. A user with the ID in the second line of the report disarmed the AREA.

System disarmed. A user with the ID in the second line of the report disarmed the AREA.

1.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasOsssst [#aaaa|NOP]

OPENING REPORT

468. Opening By Account (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasOsssst [#aaaa|NOP]

OPENING REPORT

469. Opening By Account

Printer: D6500 Mode: SIA Mode: Printer:

467. Opening By Account

470. Opening By Account

D6500 Mode: SIA Mode: 471. Opening by Account from Alarm 472. Opening By Area

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

473. Opening By Area

Printer: D6500 Mode: SIA Mode:

474. Opening by Area

475. Opening By Area (ID not reported) 476. Opening by Area (users > 254) 477. Opening by Area (users < 255) 478. Opening by Area from Alarm

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasOsssit [#aaaa|NOPi] dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasOsiiit [#aaaa|NidiiiOP]

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

System disarmed. A user with the ID in the second line of the report disarmed the AREA.

1,

System disarmed. A user with the ID in the second line of the report disarmed the AREA.

2,

OPENING ZN I

D7112

9, D7112 2, 9.

OPENING REPORT ID=iii

dd/dd tt:tt Lxx ACC aaaa OPEN FROM ALARM +++ ACC aaaa ID=iii h1rrlssssssaaaasOsiiit [#aaaa|NidiiiOR] dd/dd tt:tt Lxx ACC aaaa OPENING REPORT +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasOsiiit [#aaaa|Nria/idiiiOP] dd/dd tt:tt Lxx ACC aaaa OPENING REPORT +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasOsiiit [#aaaa|Nria/idiiiOP] dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasOsssst [#aaaa| NriaOP] dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasOsssst [#aaaa|NriaOP]

Explanation

System disarmed. A user with the ID in the second line of the report disarmed the AREA.

System disarmed. A user with the ID in the second line of the report disarmed the AREA. System disarmed. A user with the ID in the second line of the report disarmed the AREA.

1.

System disarmed. A user with the ID in the second line of the report disarmed the AREA.

1,

OPENING REPORT AREA=a

OPENING REPORT AREA=a

D7112.

dd/dd tt:tt Lxx ACC aaaa OPENING REPORT +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasOiiiit [#aaaa|Nriaa/idiiiiOP] dd/dd tt:tt Lxx ACC aaaa OPENING REPORT +++ACC aaaa AREA=aa ID=iii h1rrlssssssaaaasOiiit [#aaaa|Nriaa/idiiiOP] dd/dd tt:tt Lxx ACC aaaa OPEN FROM ALARM +++ACC aaaa AREA=a h1rrlssssssaaaasOsssst [#aaaa|NriaOR]

Bosch Security Systems | 1/05 | 4998122703D

103

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

479. Opening by Area from Alarm (users > 254) 480. Opening Early by Area

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa OPEN FROM ALARM +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasOiiiit [#aaaa|Nriaa/idiiiiOR] dd/dd tt:tt Lxx ACC aaaa EARLY TO OPEN +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasOsiiit [#aaaa|Nria/idiiiOK]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

481. Opening Early by Area

482. Opening Early by Area (users > 254) 483. Opening Early by Area from Alarm 484. Opening Early by Area from Alarm (users > 254) 485. Opening Late by Area

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

486. Opening Late by Area

487. Opening Late by Area (users > 254) 488. Opening Late by Area from Alarm 489. Opening Late by Area from Alarm (users > 254) 490. Output State (outputs < 255)

491. Output State (outputs > 254)

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

104

dd/dd tt:tt Lxx ACC aaaa EARLY +++ACC aaaa h1rrlssssssaaaasOsssst [#aaaa|NriaOK] dd/dd tt:tt Lxx ACC aaaa EARLY +++ACC aaaa AREA=aa h1rrlssssssaaaasOiiiit [#aaaa|Nriaa/idiiiiOK] dd/dd tt:tt Lxx ACC aaaa OP ERLY +++ACC aaaa h1rrlssssssaaaasOsssst [#aaaa|NriaOH] dd/dd tt:tt Lxx ACC aaaa OP ERLY +++ACC aaaa AREA=aa h1rrlssssssaaaasOiiiit [#aaaa|Nriaa/idiiiiOH] dd/dd tt:tt Lxx ACC aaaa LATE +++ ACC aaaa AREA=a h1rrlssssssaaaasOsiiit [#aaaa|Nria/idiiiOJ]

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

A user with the ID in the second line of the report disarmed the AREA before the programmed opening time window.

TO OPEN AREA=a

TO OPEN ID=iiii

FRM-ALM AREA=a

FRM-ALM ID=iiii

TO OPEN ID=iii

A user with the ID in the second line of the report disarmed the AREA after the programmed opening time window.

dd/dd tt:tt Lxx ACC aaaa LATE TO OPEN +++ACC aaaa AREA=a h1rrlssssssaaaasOsssst [#aaaa|NriaOJ] dd/dd tt:tt Lxx ACC aaaa LATE TO OPEN +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasOiiiit [#aaaa|Nriaa/idiiiiOJ] dd/dd tt:tt Lxx ACC aaaa OP LATE FRM-ALM +++ACC aaaa AREA=a h1rrlssssssaaaasOsssst [#aaaa|NriaOL] dd/dd tt:tt Lxx ACC aaaa OP LATE FRM-ALM +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasOiiiit [#aaaa|Nriaa/idiiiiOL] dd/dd tt:tt Lxx ACC aaaa OUTPUT-TROUBLE +++ACC aaaa OUTPUT=uuu h1rrlssssssaaaasTsD47t [#aaaa|NOUuuu] dd/dd tt:tt Lxx ACC aaaa OUTPUT-TROUBLE +++ACC aaaa OUTPUT=uuuu h1rrlssssssaaaasTsD47t [#aaaa|NOUuuuu]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

492. Output State Restore (outputs < 255) 493. Output State Restore (outputs > 254) 494. Paper In

495. Paper Out

496. Parameters Changed 497. Parameter Checksum Fail

498. Parameter Checksum Fail 499. Parameter Checksum Fail (SDI Device and Point reported) 500. Parameters Checksum Fail Since Last Call 501. Perimeter Delay (Area Not Reported) 502. Perimeter Delay by Area

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa OUTPUT-TRBL RST +++ACC aaaa OUTPUT=uuu h1rrlssssssaaaasRsD47t [#aaaa|NOVuuu] dd/dd tt:tt Lxx ACC aaaa OUTPUT-TRBL RST +++ACC aaaa OUTPUT=uuuu h1rrlssssssaaaasRsD47t [#aaaa|NOVuuuu] dd/dd tt:tt PAPER IN RCVR rr h1rrssssssssssssXss15t [NVI] dd/dd tt:tt PAPER OUT RCVR rr h1rrssssssssssssXss16t [NVO] dd/dd tt:tt Lxx ACC aaaa PARAMS CHANGED h1rrlssssssaaaasNsD02t [#aaaa|NYG] dd/dd tt:tt Lxx ACC aaaa PARM CKSUM FAIL h1rrlssssssaaaasTsD15t [#aaaa|NYF]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

503. Perimeter Delay by Area (ID not reported)

Printer:

504. Perimeter Delay by Area (User ID# > 254 reported)

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The program in the control panel parameters is corrupt. Send service immediately.

D9112

dd/dd tt:tt Lxx ACC aaaa PARMS BAD CKSUM h1rrlssssssaaaasTsD15t [#aaaa|NYF] dd/dd tt:tt Lxx ACC aaaa PARMS BAD CKSUM +++ ACC aaaa POINT=ppp SDI=ddd h1rrlssssssaaaasTspppt [#aaaa|NpidddYFppp] +++ ACC aaaa PARAMS BAD CKSM h1rrlssssssaaaaSMsssst [#aaaa|OYF] dd/dd tt:tt Lxx ACC aaaa PERM DLAY ARMED +++ ACC aaaa ID=iii h1rrlssssssaaaasCsiiit [#aaaa|NidiiiNL]

5.

A user with the ID in the second line of the report delay armed the perimeter of the AREA.

dd/dd tt:tt Lxx ACC aaaa PERM DLAY ARMED +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiNL]

A user with the ID in the second line of the report delay armed the perimeter of the AREA.

1.

dd/dd tt:tt Lxx ACC aaaa PERM DLAY ARMED +++ ACC aaaa AREA=a h1rrlssssssaaaasCsssst [#aaaa|NriaNL]

A user with the ID in the second line of the report delay armed the perimeter of the AREA.

1, D7112

dd/dd tt:tt Lxx ACC aaaa PERM DLAY ARMED +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiNL]

Bosch Security Systems | 1/05 | 4998122703D

105

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

505. Perimeter Delay by Area, User Defined (User Defined ID# > 254 reported)

Printer:

dd/dd tt:tt Lxx ACC aaaa PERM DLAY ARMED +++ACC aaaa USER DEFINED +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiNM]

506. Perimeter Instant (Area Not Reported)

Printer:

507. Perimeter Instant by Area

Printer:

508. Perimeter Instant by Area (ID not reported)

Printer:

509. Perimeter Instant by Area (ID not reported)

Printer:

510. Perimeter Instant by Area (User ID# > 254 reported)

Printer:

511. Perimeter Instant by Area, User Defined (User ID# > 254 reported)

Printer:

512. Phone Line Fail (Line 1)

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa PERM INST ARMED +++ ACC aaaa ID=iii h1rrlssssssaaaasCsiiit [#aaaa|NidiiiNL]

A user with the ID in the second line of the report armed the perimeter of the AREA.

dd/dd tt:tt Lxx ACC aaaa PERM INST ARMED +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasCsiiit [#aaaa|Nria/idiiiNL]

A user with the ID in the second line of the report armed the perimeter of the AREA.

1.

dd/dd tt:tt Lxx ACC aaaa PERM INST ARMED +++ ACC aaaa ID=ii h1rrlssssssaaaasCsssst [#aaaa|NriaNL]

A user with the ID in the second line of the report armed the perimeter of the AREA.

1,

dd/dd tt:tt Lxx ACC aaaa PERM INST ARMED +++ ACC aaaa AREA=a h1rrlssssssaaaasCsssst [#aaaa|NriaNL]

A user with the ID in the second line of the report armed the perimeter of the AREA.

D7112

dd/dd tt:tt Lxx ACC aaaa PERM INST ARMED +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiNL] dd/dd tt:tt Lxx ACC aaaa PERM INST ARMED +++ACC aaaa USER DEFINED +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasCiiiit [#aaaa|Nriaa/idiiiiNM] PHONE LINE FAIL PHONE LINE=1

The premises phone line in the second line of the report does not operate.

D7112

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasTsssBt [#aaaa|NLT1]

513. Phone Line 1 Fail

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasTsssBt [#aaaa|NBTB]

TROUBLE

ZN

B

Primary Phone Line failure (two-line system).

2.

514. Phone Line 2 Fail

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasTsssCt [#aaaa|NBTC]

TROUBLE

ZN

C

Secondary Phone Line failure (two-line system).

2.

515. Phone Line Fail (Line 2)

Printer:

PHONE LINE FAIL PHONE LINE=2

The premises phone line in the second line of the report does not operate.

D7112

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasTsssCt [#aaaa|NLT2]

516. Phone Line 1 Restoral

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasRsssBt [#aaaa|NURB]

RESTORAL ZN

Primary Phone Line is restored (two line system).

2.

106

B

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

517. Phone Line Restoral (Line 1)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasRsssBt [#aaaa|NLR1]

The premises line in the second line of the report is restored.

D7112

518. Phone Line 2 Restoral

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasRsssCt [#aaaa|NURC]

Secondary Phone Line is restored (two line system).

2.

519. Phone Line 2 Restoral (Line2)

Printer:

The premises line in the second line of the report is restored.

D7112

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa PHONE RESTORAL +++ ACC aaaa PHONE LINE=2 h1rrlssssssaaaasRsssCt [#aaaa|NLR2] dd/dd tt:tt Lxx PHONE RESTORED RCVR rr h1rrlsssssssssssXsss6t [NLR dd/dd tt:tt Lxx PHONE TROUBLED RCVR rr h1rrlsssssssssssXsss5t [NLT] dd/dd tt:tt Lxx ACC aaaa PT BUS TROUBLE h1rrlssssssaaaasTsssDt [#aaaa|NET]

523. Point Bus Fail

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasTsssDt [#aaaa|NBTD]

Zonex service required message: indicates a trouble condition on the data lines wiring from the POPEX Module to the POPITs. Trouble on wiring connecting control panel and keypads. Point bus, supervised keypad, printer, or other serial device trouble.

2.

524. Point Bus Fail (area reported)

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa PT BUS TROUBLE +++ACC aaaa AREA=aa h1rrlssssssaaaasTsssDt [#aaaa|NriaaET] +++ ACC aaaa PT BUS TROUBLE h1rrlssssssaaaaSTsssst [#aaaa|OET]

Trouble on the data line for the points or keypads.

5.

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa PT BUS RESTORAL h1rrlssssssaaaasRsssDt [#aaaa|NER] dd/dd tt:tt Lxx ACC aaa RESTORAL ZN D h1rrlssssssaaaasRsssDt [#aaaa|NURD]

520. Phone Restored 521. Phone Troubled 522. Point Bus Fail

525. Point Bus Fail Since Last Call 526. Point Bus Restoral 527. Point Bus Restoral

Bosch Security Systems | 1/05 | 4998122703D

PHONE RESTORAL PHONE LINE=1

RESTORAL

TROUBLE

ZN

ZN

C

D

Trouble on the data line for the points or keypads.

Data line for the points or keypads restored. Zonex restoral message: indicates a trouble condition on the wiring from the POPEX Module to the POPITs was cleared. Wiring connecting the control panel and keypads restored. Point bus, supervised keypad, printer, or other serial device was restored.

2.

107

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

528. Point Bus Restoral (area reported) 529. Point Bypass

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa PT BUS RESTORAL +++ACC aaaa AREA=aa h1rrlssssssaaaasRsssDt [#aaaa|NriaaER] dd/dd tt:tt Lxx ACC aaaa POINT BYPASS +++ ACC aaaa AREA=a POINT=ppp ID=iii h1rrlssssssaaaasNspppt [#aaaa|Nria/idiiiUBppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

530. Point Bypass

531. Point Bypass (Area and ID Not Reported)

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

532. Point Bypass (ID not reported)

Printer:

533. Point Bypass (point < 255)

Printer:

534. Point Bypass (point < 255) (fire point)

535. Point Bypass (point > 254) (fire point)

536. Point Bypass (point < 255) (supervisory point) 537. Point Bypass (point > 254) (supervisory point) 538. Point Bypass (point < 255) (waterflow point)

108

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z h1rrlssssssaaaasTssszt [#aaaa|NBTz] dd/dd tt:tt Lxx ACC aaaa POINT BYPASS +++ ACC aaaa POINT=ppp h1rrlssssssaaaasNspppt [#aaaa|NUBppp]

dd/dd tt:tt Lxx ACC aaaa POINT BYPASS +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasNspppt [#aaaa|NriaUBppp]

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The POINT in the AREA specified in the second line of the report is faulted, and was bypassed by the user with the specified ID.

1, D7112

9, D7112 The POINT in the AREA specified in the second line of the report is faulted, and was bypassed by the user with the specified ID. The POINT in the AREA specified in the second line of the report is faulted, and was bypassed by the user with the specified ID.

1, D7112

dd/dd tt:tt Lxx ACC aaaa POINT BYPASS +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasNspppt [#aaaa|NriaUBppp] dd/dd tt:tt Lxx ACC aaaa POINT BYPASS +++ACC aaaa FIRE POINT +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasNspppt [#aaaa|NriaFBppp] dd/dd tt:tt Lxx ACC aaaa POINT BYPASS +++ACC aaaa FIRE POINT +++ACC aaaa AREA=a POINT=pppp h1rrlssssssaaaasNppppt [#aaaa|NriaaFBpppp] dd/dd tt:tt Lxx ACC aaaa POINT BYPASS +++ACC aaaa SUPERVISORY POINT +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasNspppt [#aaaa|NriaSBppp] dd/dd tt:tt Lxx ACC aaaa POINT BYPASS +++ACC aaaa SUPERVISORY POINT +++ACC aaaa AREA=a POINT=pppp h1rrlssssssaaaasNppppt [#aaaa|NriaaSBpppp] dd/dd tt:tt Lxx ACC aaaa POINT BYPASS +++ACC aaaa WATERFLOW POINT +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasNspppt [#aaaa|NriaWBppp]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

539. Point Bypass (point > 254) (waterflow point) 540. Point Bypass (point > 254)

541. Point Closing

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa POINT BYPASS +++ACC aaaa WATERFLOW POINT +++ACC aaaa AREA=a POINT=pppp h1rrlssssssaaaasNppppt [#aaaa|NriaaWBpppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

542. Point Closing (points > 254)

543. Point Opening

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

544. Point Opening (points > 254)

545. Point Text

546. Power Fail

547. Programmer Bypass

548. Programmer Bypass 549. Printer Off Line 550. Printer On Line

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Printer:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The POINT in the AREA in the second line of the report was armed.

1,

The POINT in the AREA in the second line of the report was armed.

1,

dd/dd tt:tt Lxx ACC aaaa POINT BYPASS +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasNppppt [#aaaa|NriaaUBpppp] dd/dd tt:tt Lxx ACC aaaa POINT CLOSING +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasCspppt [#aaaa|NriaCZppp]

10.

dd/dd tt:tt Lxx ACC aaaa POINT CLOSING +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasCppppt [#aaaa|NriaaCZpppp] dd/dd tt:tt Lxx ACC aaaa POINT OPENING +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasOspppt [#aaaa|NriaOZppp]

10.

dd/dd tt:tt Lxx ACC aaaa POINT OPENING +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasOppppt [#aaaa|NriaaOZpppp] +++ ACC aaaa (point text) no message no message dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasPsssst [#aaaa|NAT]

D9112

AC FAILED

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa PROGRAMR BYPASS +++ ACC aaaa AREA=a POINT=ppp SDI=ddd h1rrlssssssaaaasNspppt [#aaaa|Nria/pidddUBppp]

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z h1rrlssssssaaaasTssszt [#aaaa|NBTz] dd/dd tt:tt PRINTER OFFLINE RCVR rr h1rrssssssssssssXss20t [NVZ] dd/dd tt:tt PRINTER ONLINE RCVR rr h1rrssssssssssssXss19t [NVY]

Bosch Security Systems | 1/05 | 4998122703D

No AC power. Control panel is running on battery power only. This report is sent along with the next report transmitted. It is not transmitted independently. The POINT in the AREA in the second line of the report is faulted, and was bypassed by a programmer with the specified serial device number when the system was armed.

1, D9112

9, D9112

109

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

551. Printer Restoral 552. Printer Status – Off Line

553. Printer Status – On Line

554. Printer – Paper In

555. Printer – Paper Out

556. Printer Trouble 557. Printer Version 558. Programmer Bypass (point > 254) 559. Programmer In 560. Programmer Out 561. Pulse Error

562. RAM Access Fail (Call Back)

563. RAM Access Fail (No Call Back)

110

Device/Mode

Display

Printer: D6500 Mode: SIA Mode: Printer:

dd/dd tt:tt PRINTER RESTORAL RCVR rr h1rrssssssssssssXss22t [NVR] dd/dd tt:tt Lxx ACC aaaa PRINTR-OFF LINE +++ACC aaaa SDI=ddd h1rrlssssssaaaaSTsssst [#aaaa|NpidddVZ] dd/dd tt:tt Lxx ACC aaaa PRINTER-ON LINE +++ACC aaaa SDI=ddd h1rrlssssssaaaaSTsssst [#aaaa|NpidddVY] dd/dd tt:tt Lxx ACC aaaa PRINTR-PAPER IN +++ACC aaaa SDI=ddd h1rrlssssssaaaaSTsssst [#aaaa|NpidddVI] dd/dd tt:tt Lxx ACC aaaa PRNTR-PAPER OUT +++ACC aaaa SDI=ddd h1rrlssssssaaaaSTsssst [#aaaa|NpidddVO] dd/dd tt:tt PRINTER TROUBLE RCVR rr h1rrssssssssssssXss21t [NVT] dd/dd tt:tt PRINTER vv.vv RCVR rr h3rrs PRINTER vv.vvt [APRINTER vv.vv] dd/dd tt:tt Lxx ACC aaaa PROGRAMR BYPASS +++ACC aaaa AREA=aa POINT=pppp SDI=ddd h1rrlssssssaaaasNppppt [#aaaa|Nriaa/pidddUBpppp] dd/dd tt:tt PROGRAM MODE IN RCVR rr h1rrssssssssssssXss17t [NLB] dd/dd tt:tt PROGRAM MODE OUT RCVR rr h1rrssssssssssssXss18t [NLD] dd/dd tt:tt Lxx PULSE ERROR # ## RCVR rr h3rrlPULSE ERROR # ##t [APULSE ERROR # ##] dd/dd tt:tt Lxx ACC aaaa RAM ACCESS FAIL h1rrlssssssaaaasTsssFt [#aaaa|NRU]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode:

Explanation

dd/dd tt:tt Lxx ACC aaaa RAM ACCESS FAIL +++ ACC aaaa PHONE#=h h1rrlssssssaaaasTsssFt [#aaaa|NphhRU]

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

An unsuccessful attempt was made by a RAM to contact the account on the PHONE# specified in the second line of the report. An unsuccessful attempt was made by a RAM to contact the account on the PHONE# specified in the second line of the report.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

564. RAM Access OK (from Call Back)

Printer:

RAM ACCESS OK PHONE#=h

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasRsssFt [#aaaa|NphhRS]

The account was contacted by a RAM on the PHONE# specified in the second line of the report.

565. RAM Access OK (via Phone Line)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasRsssFt [#aaaa|NRS]

RAM ACCESS OK

The account was contacted by a RAM on the PHONE# specified in the second line of the report.

566. Re-Boot

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RE-BOOT h1rrlssssssaaaasNsD14t [#aaaa|NRR] dd/dd tt:tt Lxx ACC aaa RESTORAL ZN 9 h1rrlssssssaaaasRsss9t [#aaaa|NUR9]

The control panel was reset.

567. Re-Boot

Explanation

Battery restoral report, control panel reboot, watchdog reset, power reset, or ResetBye with RAM.

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

2, D9112

Control panel reboot, watchdog reset, power reset, or ResetBye with RAM (can also be Battery Restoral Report for D7112). 568. Re-Boot (SDI Device and Point reported)

Printer:

569. Reject Command

Printer: D6500 Mode: SIA Mode:

570. Relay Reset (by Programmer)

Printer:

571. Relay Reset (by RAM)

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: 572. Relay Reset (by SKED)

573. Relay Reset (by USER)

Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RE-BOOT +++ ACC aaaa POINT=ppp SDI=ddd h1rrlssssssaaaasNspppt [#aaaa|NpidddRRppp] dd/dd tt:tt REJECT COMMAND RCVR rr h3rrsREJECT COMMANDsst [REJECT COMMAND] dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ ACC aaaa BY PROGRAMMER +++ ACC aaaa RELAY#=rrr SDI=ddd h1rrlssssssaaaasNsD22t [#aaaa|NpidddROrrr] dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ ACC aaaa BY REMOTE +++ ACC aaaa RELAY#=rrr h1rrlssssssaaaasNsD24t [#aaaa|NROrrr]

The control panel was reset.

The RELAY specified in the second line of the report was reset.

The RELAY specified in the second line of the report was reset.

dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ ACC aaaa BY SKED +++ ACC aaaa RELAY#=rrr SKED=kk h1rrlssssssaaaasNsD20t [#aaaa|NaikkROrrr]

The RELAY specified in the second line of the report was reset.

dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ ACC aaaa BY USER +++ ACC aaaa ID=iii RELAY#=rrr h1rrlssssssaaaasNsD18t [#aaaa|NidiiiROrrr]

The RELAY specified in the second line of the report was reset.

Bosch Security Systems | 1/05 | 4998122703D

111

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

574. Relay Reset (relay 254) (by USER) 575. Relay Reset (relay > 254) (by SKED)

576. Relay Reset (relay > 254) (by Programmer) 577. Relay Reset (relay > 254) (by RAM)

578. Relay Reset (relay >254, user < 255) (by USER) 579. Relay Reset (relay >254, user > 254) (by USER) 580. Relay Reset by Sked

581. Relay Reset by User

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ACC aaaa BY USER +++ACC aaaa ID=iiii RELAY#=rrr h1rrlssssssaaaasNsD18t [#aaaa|NidiiiiROrrr] dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ACC aaaa BY SKED +++ACC aaaa RELAY#=rrrr SKED=kkk h1rrlssssssaaaasNsD20t [#aaaa|NaikkkROrrrr] dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ACC aaaa BY PROGRAMMER +++ACC aaaa RELAY#=rrrr SDI=ddd h1rrlssssssaaaasNsD22t [#aaaa|NpidddROrrrr] dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ACC aaaa BY REMOTE +++ACC aaaa RELAY#=rrrr h1rrlssssssaaaasNsD24t [#aaaa|NROrrrr] dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ACC aaaa BY USER +++ACC aaaa ID=iii RELAY#=rrrr h1rrlssssssaaaasNsD18t [#aaaa|NidiiiROrrrr] dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ACC aaaa BY USER +++ACC aaaa ID=iiii RELAY#=rrrr h1rrlssssssaaaasNsD18t [#aaaa|NidiiiiROrrrr] dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ ACC aaaa RELAY#=rrr SKED=kk h1rrlssssssaaaasNsD20t [#aaaa|NaikkROrrr]

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

582. Relay Set (by Programmer)

583. Relay Set (by RAM)

584. Relay Set (by SKED)

Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

112

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The RELAY specified in the second line of the report was reset.

7,

dd/dd tt:tt Lxx ACC aaaa RELAY RESET +++ ACC aaaa ID=iii RELAY#=rrr h1rrlssssssaaaasNsD18t [#aaaa|NidiiiROrrr]

The RELAY specified in the second line of the report was reset.

1,

dd/dd tt:tt Lxx ACC aaaa RELAY SET +++ ACC aaaa BY PROGRAMMER +++ ACC aaaa RELAY#=rrr SDI=ddd h1rrlssssssaaaasNsD21t [#aaaa|NpidddRCrrr]

The RELAY specified in the second line of the report was set.

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa +++ ACC aaaa h1rrlssssssaaaasNsD23t [#aaaa|NRCrrr]

RELAY SET BY REMOTE RELAY#=rrr

The RELAY specified in the second line of the report was set.

dd/dd tt:tt Lxx ACC aaaa RELAY SET +++ ACC aaaa BY SKED +++ ACC aaaa RELAY#=rrr SKED=kk h1rrlssssssaaaasNsD19t [#aaaa|NaikkRCrrr]

The RELAY specified in the second line of the report was set.

D9112

7, D9112

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

585. Relay Set (by USER)

586. Relay Set (relay 254) (by USER) 587. Relay Set (relay > 254) (by Programmer) 588. Relay Set (relay > 254) (by RAM)

589. Relay Set (relay > 254) (by SKED)

590. Relay Set (relay >254, user < 255) (by USER) 591. Relay Set (relay >254, user > 254) (by USER) 592. Relay Set by Sked

593. Relay Set by User

Device/Mode

Display

Explanation

Printer:

dd/dd tt:tt Lxx ACC aaaa RELAY SET +++ ACC aaaa BY USER +++ ACC aaaa ID=iii RELAY#=rrr h1rrlssssssaaaasNsD28t [#aaaa|NidiiiRCrrr]

The RELAY specified in the second line of the report was set.

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

594. Remote Bypass

Printer: D6500 Mode: SIA Mode:

595. Remote Bypass

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RELAY SET +++ACC aaaa BY USER +++ACC aaaa ID=iiii RELAY#=rrr h1rrlssssssaaaasNsD28t [#aaaa|NidiiiiRCrrr] dd/dd tt:tt Lxx ACC aaaa RELAY SET +++ACC aaaa BY PROGRAMMER +++ACC aaaa RELAY#=rrrr SDI=ddd h1rrlssssssaaaasNsD21t [#aaaa|NpidddRCrrrr] dd/dd tt:tt Lxx ACC aaaa RELAY SET +++ACC aaaa BY REMOTE +++ACC aaaa RELAY#=rrrr h1rrlssssssaaaasNsD23t [#aaaa|NRCrrrr] dd/dd tt:tt Lxx ACC aaaa RELAY SET +++ACC aaaa BY SKED +++ACC aaaa RELAY#=rrrr SKED=kkk h1rrlssssssaaaasNsD19t [#aaaa|NaikkkRCrrrr] dd/dd tt:tt Lxx ACC aaaa RELAY SET +++ACC aaaa BY USER +++ACC aaaa ID=iii RELAY#=rrrr h1rrlssssssaaaasNsD28t [#aaaa|NidiiiRCrrrr] dd/dd tt:tt Lxx ACC aaaa RELAY SET +++ACC aaaa BY USER +++ACC aaaa ID=iii RELAY#=rrrr h1rrlssssssaaaasNsD28t [#aaaa|NidiiiRCrrrr] dd/dd tt:tt Lxx ACC aaaa RELAY SET +++ ACC aaaa RELAY#=rrr SKED=kk h1rrlssssssaaaasNsD19t [#aaaa|NaikkRCrrr]

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The RELAY specified in the second line of the report was set.

7,

dd/dd tt:tt Lxx ACC aaaa RELAY SET +++ ACC aaaa ID=iii RELAY#=rrr h1rrlssssssaaaasNsD28t [#aaaa|NidiiiRCrrr]

The RELAY specified in the second line of the report was set.

1,

dd/dd tt:tt Lxx ACC aaaa RAM BYPASS +++ ACC aaaa AREA=a POINT=ppp PHONE#=h h1rrlssssssaaaasNspppt [#aaaa|Nria/phhUBppp]

The POINT in the AREA specified in the second line of the report is faulted, and was bypassed by a RAM through through the specified phone line.

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasTssszt [#aaaa|NBTz]

Bosch Security Systems | 1/05 | 4998122703D

TROUBLE

D9112

7, D9112

ZN

z

1, D9112

9, D9112

113

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Printer:

598. Remote Reset

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RAM BYPASS +++ACC aaaa AREA=aa POINT=pppp PH#=hh h1rrlssssssaaaasNppppt [#aaaa|Nriaa/phhhUBpppp] dd/dd tt:tt Lxx ACC aaaa RAM BYPASS +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasNppppt [#aaaa|NriaaUBpppp] dd/dd tt:tt Lxx ACC aaaa REMOTE RESET h1rrlssssssaaaasNsD11t [#aaaa|NRN]

The control panel power was reset using RAM.

D9112

599. Remote Reset

Printer:

dd/dd tt:tt Lxx ACC aaa RESTORAL

D9112

D6500 Mode: SIA Mode:

h1rrlssssssaaaasRsss9t [#aaaa|NUR9]

Battery restoral report, control panel reboot, watchdog reset, power reset, or ResetBye with RAM, control panel reboot, watchdog reset, power reset, or ResetBye with RAM (can also be battery restoral report for D7112).

600. Restoral

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RESTORAL REPORT h1rrlssssssaaaasRsssst [#aaaa|NUR]

601. Restoral

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasRssszt [#aaaa|NURz] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasRszyyt [#aaaa|NURzyy] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasRssxxt [#aaaa|NURxx] dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasRss16t [#aaaa|NUR16] dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasRspppt [#aaaa|NBRppp]

596. Remote Bypass (Call back) (point > 254) 597. Remote Bypass (No Call back) (point > 254)

602. Restoral

603. Restoral

604. Restoral

605. Restoral (Area Not Reported)

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

ZN

9

RESTORAL ZN

z

2, 9.

RESTORAL ZN zyy

RESTORAL ZN

xx

RESTORAL ZN

16

RESTORAL REPORT POINT=ppp

Unexpanded restoral report. Command 41. The POINT in the AREA in the second line of the report was restored. Unexpanded restoral report. Command 41. The POINT in the AREA in the second line of the report was restored.

606. Restoral (From Trouble, Missing, NonFire Supervision)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RESTORAL REPORT +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasRspppt [#aaaa|NriaBRppp]

607. Restoral Fire

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaaHsssszt [#aaaa|NFRz]

114

Unexpanded restoral report. Command 41. The POINT in the AREA in the second line of the report was restored.

RESTORAL FR z

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

608. Restoral from Alarm

609. Restoral from Alarm (no area) 610. Restoral from Alarm (points > 254) 611. Restoral (user < 255) (for use with Keyfob device) (from trouble, missing, nonfire supervision)

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa RESTORE FRM ALM +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasRspppt [#aaaa|NriaBHppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

612. Restoral (points > 254) (from trouble, missing, nonfire supervision)

Printer:

613. RF Battery Restore (Area Not Reported)

Printer:

D6500 Mode: SIA Mode:

Explanation

dd/dd tt:tt Lxx ACC aaaa RESTORE FRM ALM +++ACC aaaa POINT=ppp h1rrlssssssaaaasRspppt [#aaaa|NBHppp] dd/dd tt:tt Lxx ACC aaaa RESTORE FRM ALM +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasRppppt [#aaaa|NriaaBHpppp] dd/dd tt:tt Lxx ACC aaaa RESTORAL REPORT +++ACC aaaa KEYFOB +++ACC aaaa ID=iii h1rrlssssssaaaasRsD10t [#aaaa|NidiiiUR]

dd/dd tt:tt Lxx ACC aaaa RESTORAL REPORT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasRppppt [#aaaa|NriaaBRpppp]

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RF BATT RESTORE +++ ACC aaaa POINT=ppp h1rrlssssssaaaasRspppt [#aaaa|NXRppp]

The RF POINT transmitter in the AREA in the second line of the report was restored from a low battery

614. RF Interference

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RF INTERFERENCE h1rrlssssssaaaasTsD08t [#aaaa|NET]

RF interference was detected in premises RF system.

615. RF Low Battery (Area Not Reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasTspppt [#aaaa|NXTppp]

The RF POINT transmitter in the AREA in the second line of the report has a low battery.

616. RF Receiver Restoral

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RF RCVR RESTORE h1rrlssssssaaaasRsD17t [#aaaa|NER]

617. RF Receiver Restoral from Trouble

Printer:

dd/dd tt:tt Lxx ACC aaaa RCVR TBL RESTOR +++ ACC aaaa SDI=ddd h1rrlssssssaaaasRsD17t [#aaaa|NpidddER] dd/dd tt:tt Lxx ACC aaaa RCVR TAMPER +++ ACC aaaa SDI=ddd h1rrlssssssaaaasXss35t [#aaaa|NpidddXS] dd/dd tt:tt Lxx ACC aaaa RCVR TAMPR REST +++ ACC aaaa SDI=ddd h1rrlssssssaaaasXss36t [#aaaa|NpidddXJ]

618. RF Receiver Tamper

619. RF Receiver Tamper Restore

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Bosch Security Systems | 1/05 | 4998122703D

RF BATTERY LOW POINT=ppp

The premises RF receiver was restored from a trouble condition.

D7112

D7112

115

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

620. RF Receiver Trouble

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RF RCVR TROUBLE h1rrlssssssaaaasTsD17t [#aaaa|NET]

The premises RF receiver is in a trouble condition.

D7112

621. RF Receiver Trouble

Printer:

dd/dd tt:tt Lxx ACC aaaa RCVR TROUBLE +++ ACC aaaa SDI=ddd h1rrlssssssaaaasTsD17t [#aaaa|NpidddET] +++ ACC aaaa RF RCVR TROUBLE h1rrlssssssaaaaSTsssst [#aaaa|OET]

The premises RF receiver is in a trouble condition

5.

622. RF Receiver Trouble Since Last Call 623. RF Tamper Trouble (Area Not Reported) 624. RF Transmitter Battery Restore 625. RF Transmitter Battery Restore (for use with Keyfob device) (user < 255)

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

626. RF Transmitter Battery Restore (for use with Keyfob device) (user > 254)

Printer:

627. RF Transmitter Battery Restore (points > 254)

Printer:

628. RF Transmitter Low Battery

Printer:

629. RF Transmitter Low Battery (points > 254) 630. RF Transmitter Low Battery (for use with Keyfob device) (user < 255) 631. RF Transmitter Low Battery (for use with Keyfob device) (user > 254)

116

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RF TMPR TROUBLE +++ ACC aaaa POINT=ppp h1rrlssssssaaaasTspppt [#aaaa|NTTppp] dd/dd tt:tt Lxx ACC aaaa RF BATT RESTORE +++ACC aaaa SDI=ddd h1rrlssssssaaaasRsD10t [#aaaa|NpidddXR] dd/dd tt:tt Lxx ACC aaaa RF BATT RESTORE +++ACC aaaa KEYFOB +++ACC aaaa ID=iii h1rrlssssssaaaasRsD10t [#aaaa|NpidddXR]

dd/dd tt:tt Lxx ACC aaaa RF BATT RESTORE +++ACC aaaa KEYFOB +++ACC aaaa ID=iiii h1rrlssssssaaaasRsD10t [#aaaa|NidiiiiXR]

dd/dd tt:tt Lxx ACC aaaa RF BATT RESTORE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasRppppt [#aaaa|NriaaXRpppp] dd/dd tt:tt Lxx ACC aaaa RF BATTERY LOW +++ACC aaaa SDI=ddd h1rrlssssssaaaasTsD10t [#aaaa|NpidddXT] dd/dd tt:tt Lxx ACC aaaa RF BATTERY LOW +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasTppppt [#aaaa|NriaaXTpppp] dd/dd tt:tt Lxx ACC aaaa RF BATTERY LOW +++ACC aaaa KEYFOB +++ACC aaaa ID=iii h1rrlssssssaaaasTsD10t [#aaaa|NidiiiXT] dd/dd tt:tt Lxx ACC aaaa RF BATTERY LOW +++ACC aaaa KEYFOB +++ACC aaaa ID=iiii h1rrlssssssaaaasTsD10t [#aaaa|NidiiiiXT]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

632. RF Transmitter Tamper Alarm (points > 254) 633. RF Transmitter Tamper Restoral (Area Not Reported)

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa RF TAMPER ALARM +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasAppppt [#aaaa|NriaaTApppp] dd/dd tt:tt Lxx ACC aaaa RF TMPR RSTORAL +++ ACC aaaa POINT=ppp h1rrlssssssaaaasRspppt [#aaaa|NTRppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

634. RF Transmitter Tamper Restoral (points > 254)

Printer:

635. RF Transmitter Tamper Trouble (points > 254)

Printer:

636. SDI Bus Restore (Ground Fault)

Printer:

637. SDI Bus Restore (used by preOMNI panels) 638. SDI Device AC Failure (used by postOMNI panels) 639. SDI Device AC Restore (used by postOMNI panels) 640. SDI Device Battery Trouble (used by postOMNI panels)

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

641. SDI Device Missing (used by postOMNI panels)

Printer:

642. SDI Device Low Battery (used by postOMNI panels)

Printer:

643. SDI Device Missing Restore (used by postOMNI panels) 644. SDI Device Overcurrent (used by postOMNI panels)

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa RF TMPR RSTORAL +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasRppppt [#aaaa|NriaaTRpppp] dd/dd tt:tt Lxx ACC aaaa RF TMPR TROUBLE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasTppppt [#aaaa|NriaaTTpppp] dd/dd tt:tt Lxx ACC aaaa SDI RESTORAL +++ACC aaaa GROUND FAULT +++ACC aaaa SDI=ddd h1rrlssssssaaaasRsssDt [#aaaa|NpidddER] dd/dd tt:tt Lxx ACC aaaa SDI RESTORAL +++ACC aaaa SDI=ddd h1rrlssssssaaaasRsssDt [#aaaa|NpidddER] dd/dd tt:tt Lxx ACC aaaa DEVICE AC FAIL +++ACC aaaa SDI=ddd h1rrlssssssaaaasTsssDt [#aaaa|NpidddEP] dd/dd tt:tt Lxx ACC aaaa DEV AC RESTORE +++ACC aaaa SDI=ddd h1rrlssssssaaaasRsssDt [#aaaa|NpidddEQ] dd/dd tt:tt Lxx ACC aaaa DEVICE BAT TRBL +++ACC aaaa SDI=ddd h1rrlssssssaaaasTsssDt [#aaaa|NpidddEB] dd/dd tt:tt Lxx ACC aaaa DEVICE MISSING +++ACC aaaa SDI=ddd h1rrlssssssaaaasTsssDt [#aaaa|NpidddEM] dd/dd tt:tt Lxx ACC aaaa DEV BAT RESTORE +++ACC aaaa SDI=ddd h1rrlssssssaaaasRsssDt [#aaaa|NpidddEV] dd/dd tt:tt Lxx ACC aaaa DEV MISSING RST +++ACC aaaa SDI=ddd h1rrlssssssaaaasRsssDt [#aaaa|NpidddEN] dd/dd tt:tt Lxx ACC aaaa DEV OVERCURRENT +++ACC aaaa SDI=ddd h1rrlssssssaaaasTsssDt [#aaaa|NpidddYI]

Bosch Security Systems | 1/05 | 4998122703D

117

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

645. SDI Device Overcurrent Restore (used by postOMNI panels)

Printer:

dd/dd tt:tt Lxx ACC aaaa DEV OVERCUR RST +++ACC aaaa SDI=ddd h1rrlssssssaaaasRsssDt [#aaaa|NpidddYJ]

646. SDI Device Tamper (used by postOMNI panels)

Printer:

647. SDI Device Tamper Restore (used by postOMNI panels) 648. SDI Device Trouble (used by postOMNI panels) 649. SDI Device Trouble Restore (used by postOMNI panels) 650. SDI Fail

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa DEVICE TROUBLE +++ACC aaaa SDI=ddd h1rrlssssssaaaasTsssDt [#aaaa|NpidddET] dd/dd tt:tt Lxx ACC aaaa DEV TROUBLE RST +++ACC aaaa SDI=ddd h1rrlssssssaaaasRsssDt [#aaaa|NpidddER]

D6500 Mode: SIA Mode:

651. SDI Fail

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasTsssDt [#aaaa|NBTD]

652. SDI Fail (Point reported)

Printer:

dd/dd tt:tt Lxx ACC aaaa SDI FAILURE +++ ACC aaaa POINT=ppp SDI=ddd h1rrlssssssaaaasTspppt [#aaaa|NpidddETppp]

653. SDI Fail Since Last Call

Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

118

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa DEVICE TAMPER +++ACC aaaa SDI=ddd h1rrlssssssaaaasTsssDt [#aaaa|NpidddES] dd/dd tt:tt Lxx ACC aaaa DEV TAMPER REST +++ACC aaaa SDI=ddd h1rrlssssssaaaasRsssDt [#aaaa|NpidddEJ]

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasTsssDt [#aaaa|NpidddET]

654. SDI Restoral

Printer:

Explanation

SDI FAILURE SDI=ddd

TROUBLE

ZN

D

+++ ACC aaaa SDI FAILURE h1rrlssssssaaaaSDsssst [#aaaa|OET] dd/dd tt:tt Lxx ACC aaaa SDI RESTORAL +++ ACC aaaa SDI=ddd h1rrlssssssaaaasRsssDt [#aaaa|NpidddER]

A supervised keypad, printer, or other serial device listed in the second line of the report does not operate. Zonex service required message: indicates a trouble condition on the data lines wiring from the POPEX Module to the POPITs. Trouble on wiring connecting control panel and keypads. Point bus, supervised keypad, printer, or other serial device trouble.

2.

A supervised keypad, printer, or other serial device listed in the second line of the report does not operate. 5.

The supervised keypad, printer, or other serial device listed in the second line of the report was restored.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

655. SDI Restoral

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa RESTORAL h1rrlssssssaaaasRsssDt [#aaaa|NURD]

656. SDI Restoral

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasRsssDt [#aaaa|NpidddER]

D6500 Mode: SIA Mode:

657. SDI Restoral (Point reported)

Printer:

658. Sensor Reset

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

659. Sensor Reset (ID not reported)

660. Sensor Reset (ID/relay not reported)

661. Sensor Reset (relay > 254, user < 255) 662. Sensor Reset (relay > 254, user >254)

Printer: D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

ZN

D

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Zonex restoral message: indicates a trouble condition on the wiring from the POPEX Module to the POPITs was cleared. Wiring connecting the control panel and keypads restored. Point bus, supervised keypad, printer, or other serial device was restored.

2.

SDI RESTORAL SDI=ddd

The supervised keypad, printer, or other serial device listed in the second line of the report was restored.

dd/dd tt:tt Lxx ACC aaaa SDI RESTORAL +++ ACC aaaa POINT=ppp SDI=ddd h1rrlssssssaaaasRspppt [#aaaa|NpidddERppp]

The supervised keypad, printer, or other serial device listed in the second line of the report was restored.

dd/dd tt:tt Lxx ACC aaaa SENSOR RESET +++ ACC aaaa AREA=a ID=iii RELAY#=rrr h1rrlssssssaaaasNsD27t [#aaaa|Nria/idiiiXIrrr]

The sensor specified in the second line of the report (labeled “RELAY”) located in the specified AREA was reset by a user with the ID shown.

1,

dd/dd tt:tt Lxx ACC aaaa SENSOR RESET +++ ACC aaaa AREA=a RELAY#=rrr h1rrlssssssaaaasNsD27t [#aaaa|NriaXIrrr]

The sensor specified in the second line of the report (labeled “RELAY”) located in the specified AREA was reset by a user with the ID shown.

1,

The sensor specified in the second line of the report (labeled “RELAY”) located in the specified AREA was reset by a user with the ID shown.

1,

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasNsD27t [#aaaa|NriaXI]

SENSOR RESET AREA=a

7, 8.

7, 8, D7112

7, 8, D7112

dd/dd tt:tt Lxx ACC aaaa SENSOR RESET +++ACC aaaa AREA=aa ID=iii RELAY#=rrrr h1rrlssssssaaaasNsD27t [#aaaa|Nriaa/idiiiXIrrrr] dd/dd tt:tt Lxx ACC aaaa SENSOR RESET +++ACC aaaa AREA=a ID=iiii RELAY#=rrrr h1rrlssssssaaaasNsD27t [#aaaa|Nria/idiiiiXIrrrr]

Bosch Security Systems | 1/05 | 4998122703D

119

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

663. Sensor Reset (relay < 255, user < 255) (OMNI)

Printer:

dd/dd tt:tt Lxx ACC aaaa SENSOR RESET +++ACC aaaa AREA=aa ID=iii RELAY#=rrr h1rrlssssssaaaasNsD27t [#aaaa|Nria/idiiiXIrrr]

664. Sensor Reset (relay < 255, user > 254) (OMNI)

Printer:

665. Sensor Reset

Printer:

(relay not reported)

666. Sensor Restore (points < 255)

667. Sensor Restore (points > 254)

668. Sensor Trouble (points < 255) 669. Sensor Trouble (points > 254)

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

671. Service End

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

672. Service End

D6500 Mode: SIA Mode: Printer:

670. Service End

673. Service Req’d

674. Service Request 675. Service Start

676. Service Start

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

120

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The sensor specified in the second line of the report (labeled “RELAY”) located in the specified AREA was reset by a user with the ID shown.

1,

dd/dd tt:tt Lxx ACC aaaa SENSOR RESET +++ACC aaaa AREA=a ID=iiii RELAY#=rrr h1rrlssssssaaaasNsD27t [#aaaa|Nria/idiiiiXIrrr] dd/dd tt:tt Lxx ACC aaaa SENSOR RESET +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasNsD27t [#aaaa|Nria/idiiiXI]

7, 8, D7112

dd/dd tt:tt Lxx ACC aaaa SENSOR RESTORE +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaRQspppt [#aaaa|OriaXNppp] dd/dd tt:tt Lxx ACC aaaa SENSOR RESTORE +++ACC aaaa AREA=a POINT=pppp h1rrlssssssaaaaRQspppt [#aaaa|OriaXNppp] dd/dd tt:tt Lxx ACC aaaa SENSOR TROUBLE +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasQspppt [#aaaa|OriaXKppp] dd/dd tt:tt Lxx ACC aaaa SENSOR TROUBLE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasQppppt [#aaaa|OriaaXKpppp] dd/dd tt:tt Lxx ACC aaaa SERVICE END h1rrlssssssaaaasRsssFt [#aaaa|NTE] dd/dd tt:tt Lxx ACC aaaa SERVICE END +++ ACC aaaa AREA=a h1rrlssssssaaaasRsssFt [#aaaa|NriaTE] dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasRsssFt [#aaaa|NidiiiTE]

SERVICE END ID=iii

dd/dd tt:tt Lxx SERVICE REQUIRED RCVR rr h1rrlsssssssssssXsss1t [NYX] dd/dd tt:tt Lxx ACC aaaa SERVICE REQUEST h1rrlssssssaaaasNsD45t [#aaaa|NYX] dd/dd tt:tt Lxx ACC aaaa SERVICE START h1rrlssssssaaaasTsssFt [#aaaa|NTS] dd/dd tt:tt Lxx ACC aaaa SERVICE START +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasTsssFt [#aaaa|Nria/idiiiTS]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

677. Service Start

678. Service Start (no area)

679. Service Start (users > 254)

680. Set Time

681. Shunted

682. Shunted

683. Sked Bypass

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasTsssFt [#aaaa|NriaTS]

SERVICE START AREA=a

dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasTsssFt [#aaaa|NidiiiTS]

SERVICE START ID=iii

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

684. Sked Bypass

685. Sked Bypass (point > 254)

686. Sked Changed

687. Sked Changed (users > 254)

688. Skeds Changed

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

689. Sked Changed

Printer: D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The POINT in the AREA in the second line of the report is faulted, and was bypassed when the system was armed by the specified Sked.

1,

dd/dd tt:tt Lxx ACC aaaa SERVICE START +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasTsssFt [#aaaa|Nriaa/idiiiiTS] dd/dd tt:tt TIME SET RCVR rr h1rrssssssssssssXsss2t [NJT] dd/dd tt:tt Lxx ACC aaaa SHUNTED ZN z h1rrlssssssaaaasNssszt [#aaaa|NXWz] dd/dd tt:tt Lxx ACC aaaa SHUNTED ZN zyy h1rrlssssssaaaasNszyyt [#aaaa|NXWzyy] dd/dd tt:tt Lxx ACC aaaa SKED BYPASS +++ ACC aaaa AREA=a POINT=ppp SKED=kk h1rrlssssssaaaasNspppt [#aaaa|Nria/aikkUBppp]

dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z h1rrlssssssaaaasTssszt [#aaaa|NBTz] dd/dd tt:tt Lxx ACC aaaa SKED BYPASS +++ACC aaaa AREA=aa POINT=pppp SKED=kkk h1rrlssssssaaaasNppppt [#aaaa|Nriaa/aikkkUBpppp] dd/dd tt:tt Lxx ACC aaaa SKED CHANGED +++ACC aaaa SKED=kkk h1rrlssssssaaaasNsD06t [#aaaa|NaikkkJS] dd/dd tt:tt Lxx ACC aaaa SKED CHANGED +++ACC aaaa ID=iiii SKED=kkk h1rrlssssssaaaasNsD06t [#aaaa|Nidiiii/aikkkJS] dd/dd tt:tt Lxx ACC aaaa SKED CHANGED +++ ACC aaaa ID= iii SKED=kk h1rrlssssssaaaasNsD06t [#aaaa|Nidiii/aikkJS] dd/dd tt:tt Lxx ACC aaaa SKED CHANGED +++ ACC aaaa ID=iii SKED=kk h1rrlssssssaaaasNsD06t [#aaaa|Nidiii/aikkJS]

Bosch Security Systems | 1/05 | 4998122703D

D9112

9, D9112

The Sked in the second line of the report was changed by the user with the specified ID.

D9112

The Sked in the second line of the report was changed by the user with the specified ID.

121

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

690. Sked Executed

Printer: D6500 Mode: SIA Mode:

691. Status: Alarm

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa SKED EXECUTED h1rrlssssssaaaasNsD25 [#aaaa|NJR] dd/dd tt:tt Lxx ACC aaaa S: ALARM +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSAspppt [#aaaa|OriaBAppp]

692. Status: Alarm

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasSsssst [#aaaa|NYY]

693. Status: Alarm

Printer: D6500 Mode: SIA Mode: Printer:

dd/dd tt:tt Lxx ACC aaa ALARM ZN z h1rrlssssssaaaaSAssszt [#aaaa|OBAz] dd/dd tt:tt Lxx ACC aaaa S:ALARM +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSAppppt [#aaaa|OriaaBApppp] dd/dd tt:tt Lxx ACC aaaa S:ANALOG SERVCE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSTppppt [#aaaa|OriaaASpppp] dd/dd tt:tt Lxx ACC aaaa S:ANALOG SERVCE +++ACC aaaa AREA=aa POINT=pppp +++ACC aaaa LEVEL=lll VALUE=vvv h1rrlssssssaaaaSTppppt [#aaaa|Oriaa/lvlll/vavvvASpppp]

694. Status: Alarm (point > 254)

695. Status: Analog Service (points > 254) 696. Status: Analog Service (points > 254) (Level and Value reported) 697. Status: Close by Area

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode:

698. Status: Close by Area 699. Status: Close by Area 700. Status: Close by Area

SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

701. Status: Door Forced (points > 254) 702. Status: Door Left Open

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

122

STATUS REPORT

dd/dd tt:tt Lxx ACC aaaa S: CLOSING +++ ACC aaaa AREA=a h1rrlssssssaaaaSCsssst [#aaaa|OriaCL] dd/dd tt:tt Lxx ACC aaa STATUS REPORT h1rrlssssssaaaasSsssst [#aaaa|NYY] dd/dd tt:tt Lxx ACC aaa CLOSING ZN z h1rrlssssssaaaaSCssszt [#aaaa|OCLz] dd/dd tt:tt Lxx ACC aaaa S:CLOSING +++ ACC aaaa AREA=a h1rrlssssssaaaaSCsssst [#aaaa|OriaCL]

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Status report initiated by Skeds or by a user. The POINT in the AREA in the second line of the report is in alarm.

1.

Indicates that the next report is an account status report. 9, D9112

Status report initiated by Skeds or by a user. The AREA in the second line of the report is armed. Indicates that the next report is an account status report. z = area number

Status report initiated by Skeds or by a user. The AREA in the second line of the report is armed.

dd/dd tt:tt Lxx ACC aaaa S:DOOR FORCED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSAppppt [#aaaa|OriaaDFpppp] dd/dd tt:tt Lxx ACC aaaa S:DR LEFT OPEN +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSIspppt [#aaaa|OriaDNppp]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

703. Status: Door Left Open (points > 254) 704. Status: Fire Alarm

705. Status: Fire Alarm (points < 255)

706. Status: Fire Alarm (points < 255)

707. Status: Fire Alarm (points < 255)

708. Status: Fire Alarm (points < 255)

709. Status: Fire Alarm (points > 254) 710. Status: Fire Alarm (points > 254)

711. Status: Fire Alarm (points > 254)

712. Status: Fire Alarm (points > 254)

713. Status: Fire Alarm (points > 254)

714. Status: Fire Missing

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa S:DR LEFT OPEN +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSIppppt [#aaaa|OriaaDNpppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE ALARM +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSFspppt [#aaaa|OriaFAppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa S:FIRE ALARM +++ACC aaaa CROSS POINT +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSFspppt [#aaaa|OriaFAppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE ALARM +++ACC aaaa SMOKE DETECTOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSFspppt [#aaaa|OriaFAppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE ALARM +++ACC aaaa HIGH TEMPERATURE SENSOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSFspppt [#aaaa|OriaFAppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE ALARM +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSFspppt [#aaaa|OriaFAppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE ALARM +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSFppppt [#aaaa|OriaaFApppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE ALARM +++ACC aaaa CROSS POINT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSFppppt [#aaaa|OriaaFApppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE ALARM +++ACC aaaa SMOKE DETECTOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSFppppt [#aaaa|OriaaFApppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE ALARM +++ACC aaaa HIGH TEMPERATURE SENSOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSFppppt [#aaaa|OriaaFApppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE ALARM +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSFppppt [#aaaa|OriaaFApppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE MISSING +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSZspppt [#aaaa|OriaFYppp]

Bosch Security Systems | 1/05 | 4998122703D

123

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

715. Status: Fire Missing (points > 254) 716. Status: Fire Supervision

717. Status: Fire Supervision (points < 255) 718. Status: Fire Supervision (Water Flow) (point < 255) 719. Status Fire Supervision (Water Flow) (point > 254) 720. Status: Fire Trouble

721. Status: Fire Trouble (points < 255)

722. Status: Fire Trouble (points < 255)

723. Status: Fire Trouble (points < 255)

724. Status: Fire Trouble (points > 254) 725. Status: Fire Trouble (points > 254)

726. Status: Fire Trouble (points > 254)

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa S:FIRE MISSING +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSZppppt [#aaaa|OriaaFYpppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE SUPRVISN +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSEspppt [#aaaa|OriaFSppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

124

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa S:FIRE SUPRVISN +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSEppppt [#aaaa|OriaaFSpppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE SUPRVISN +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSEspppt [#aaaa|OriaFSppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE SUPRVISN +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSEppppt [#aaaa|OriaaFSpppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE TROUBLE +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSGspppt [#aaaa|OriaFTppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE TROUBLE +++ACC aaaa SMOKE DETECTOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSGspppt [#aaaa|OriaFTppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE TROUBLE +++ACC aaaa HIGH TEMPERATURE SENSOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSGspppt [#aaaa|OriaFTppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE TROUBLE +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSGspppt [#aaaa|OriaFTppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE TROUBLE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSGppppt [#aaaa|OriaaFTpppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE TROUBLE +++ACC aaaa SMOKE DETECTOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSGppppt [#aaaa|OriaaFTpppp] dd/dd tt:tt Lxx ACC aaaa S:FIRE TROUBLE +++ACC aaaa HIGH TEMPERATURE SENSOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSGppppt [#aaaa|OriaaFTpppp]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

727. Status: Fire Trouble (points > 254)

728. Status: Missing Alarm

729. Status: Missing Alarm (points > 254) 730. Status: Missing Fire Supervision 731. Status: Missing Fire Supervision (points < 255) 732. Status: Missing Fire Supervision (points > 254) 733. Status: Missing Fire Supervision (points > 254) 734. Status: Missing Supervision

735. Status: Missing Supervision (points > 254) 736. Status: Missing Trouble

737. Status: Missing Trouble (points > 254) 738. Status: Open by Area

739. Status: Open by Area

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa S:FIRE TROUBLE +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSGppppt [#aaaa|OriaaFTpppp] dd/dd tt:tt Lxx ACC aaaa S:MISSING ALARM +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSZspppt [#aaaa|OriaUZppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

Explanation

dd/dd tt:tt Lxx ACC aaaa S:MISSING ALARM +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSZppppt [#aaaa|OriaaUZpppp] dd/dd tt:tt Lxx ACC aaaa S:MIS FIR SUPRV +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSYspppt [#aaaa|OriaFZppp] dd/dd tt:tt Lxx ACC aaaa S:MIS FIR SUPRV +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSYspppt [#aaaa|OriaFZppp] dd/dd tt:tt Lxx ACC aaaa S:MIS FIR SUPRV +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSYppppt [#aaaa|OriaaFZpppp] dd/dd tt:tt Lxx ACC aaaa S:MIS FIR SUPRV +++ACC aaaa WATER FLOW SENSOR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSYppppt [#aaaa|OriaaFZpppp] dd/dd tt:tt Lxx ACC aaaa S:MIS SUPRVISN +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSYspppt [#aaaa|OriaBZppp] dd/dd tt:tt Lxx ACC aaaa S:MISS SUPRVISN +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSYppppt [#aaaa|OriaaBZpppp] dd/dd tt:tt Lxx ACC aaaa S:MISSING TRBL +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSVspppt [#aaaa|OriaUYppp]

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa S:MISSING TRBL +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSVppppt [#aaaa|OriaaUYpppp] dd/dd tt:tt Lxx ACC aaaa S: OPENING +++ ACC aaaa AREA=a h1rrlssssssaaaaSOsssst [#aaaa|OriaOP]

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasSsssst [#aaaa|NYY]

D6500 Mode: SIA Mode: Printer:

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Bosch Security Systems | 1/05 | 4998122703D

STATUS REPORT

Status report initiated by Skeds or by a user from a keypad: the AREA specified in the second line of the report is disarmed. Indicates that the next report is an Account Status Report.

125

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

740. Status: Open by Area 741. Status:Perimet er Delay by Area 742. Status:Perimet er Delay by Area 743. Status:Perimet er Delay by Area

Device/Mode

Display

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaaSOssszt [#aaaa|OOPz] dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasSsssst [#aaaa|NYY]

Printer: D6500 Mode: SIA Mode: Printer:

dd/dd tt:tt Lxx ACC aaa OPENING ZN z h1rrlssssssaaaaSOssszt [#aaaa|OOPz] dd/dd tt:tt Lxx ACC aaaa S:PERIM DELAY +++ ACC aaaa AREA=a h1rrlssssssaaaaSCsssst [#aaaa|OriaNL]

D6500 Mode: SIA Mode:

744. Status:Perimet er Instant by Area

Printer:

Explanation

OPENING

ZN

z

STATUS REPORT

z = area number

Indicates that the next report is an Account Status Report. z = area number

Status report initiated by Skeds or by a user. The perimeter of the AREA in the second line of the report was delay armed.

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa S:PERIM INSTANT +++ ACC aaaa AREA=a h1rrlssssssaaaaSCsssst [#aaaa|OriaNL]

Status report initiated by Skeds or by a user. The perimeter of the AREA in the second line of the report is armed.

745. Status:Perimet er Instant by Area

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasSsssst [#aaaa|NYY]

Indicates that the next report is an Account Status Report.

746. Status:Perimet er Instant by Area

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa OPENING ZN z h1rrlssssssaaaaSOssszt [#aaaa|OOPz] dd/dd tt:tt Lxx ACC aaaa S:PERIM INSTANT +++ ACC aaaa AREA=a h1rrlssssssaaaaSCsssst [#aaaa|OriaNL]

748. Status Report

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasSssszt [#aaaa|NYY]

749. Status: RF Transmitter Low Battery (points > 254)

Printer:

dd/dd tt:tt Lxx ACC aaaa S:RF BATTRY LOW +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSTppppt [#aaaa|OriaaXTpppp] dd/dd tt:tt Lxx ACC aaaa S:RF TMPR-ALARM +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSAppppt [#aaaa|OriaaTApppp] dd/dd tt:tt Lxx ACC aaaa S:RF TMPR-TRBL +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSTppppt [#aaaa|OriaaTApppp] dd/dd tt:tt Lxx ACC aaaa ALARM ZN z h1rrlssssssaaaaSAssszt [#aaaa|OBAz]

747. Status:Perimet er Instant by Area

750. Status: RF Transmitter Tamper Alarm (points > 254) 751. Status: RF Transmitter Tamper Alarm (points > 254) 752. Status Rpt/Alarm

126

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

STATUS REPORT

STATUS REPORT

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

z = area number

Status report initiated by Skeds or by a user. The perimeter of the AREA in the second line of the report is armed. Indicates that the next report is an Account Status Report.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

753. Status Rpt/Closing

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa CLOSING h1rrlssssssaaaaSCsssst [#aaaa|OCL]

REPORT

754. Status Rpt/Closing

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa CLOSING h1rrlssssssaaaaSCsssit [#aaaa|OCLi] dd/dd tt:tt Lxx ACC aaaa OPENING h1rrlssssssaaaaSOsssit [#aaaa|OOPi] dd/dd tt:tt Lxx ACC aaaa OPENING h1rrlssssssaaaaSOsssst [#aaaa|OOP]

ID

I

ID

I

757. Status Rpt/Power Fail

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaaSPsssst [#aaaa|OAT]

758. Status Rpt/Restoral

759. Status Rpt/Restoral

755. Status Rpt/Opening 756. Status Rpt/Opening

760. Status Rpt/Trouble 761. Status: Supervision

762. Status: Supervision (points > 254) 763. Status:Transmi tter Low Battery

Explanation

Unexpanded reporting, system armed by arm/disarm passcode or COMMAND 1 (D8112G2 excluded). Unexpanded reporting, system armed by arm/disarm passcode or CMD 1. AREA armed by user with the ID in the second line of the report.

REPORT

System disarmed. A user with the ID in the second line of the report disarmed the AREA.

AC FAILED

No AC power. Control panel is running on battery power only. This report is sent along with the next report transmitted. It is not transmitted independently.

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RESTORAL REPORT h1rrlssssssaaaaSRsssst [#aaaa|OUR]

Unexpanded Restoral Report. Command 41. The POINT in the AREA in the second line of the report was restored.

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

dd/dd tt:tt Lxx ACC aaaa RESTORAL ZN z h1rrlssssssaaaaSRssszt [#aaaa|OURz] dd/dd tt:tt Lxx ACC aaaa TROUBLE ZN z h1rrlssssssaaaaSTssszt [#aaaa|OBTz] dd/dd tt:tt Lxx ACC aaaa S:SUPERVISION +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSTspppt [#aaaa|OriaBSppp]

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa S:SUPERVISION +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSTppppt [#aaaa|OriaaBSpppp] dd/dd tt:tt Lxx ACC aaaa S:RF BATT LOW +++ ACC aaaa AREA=a RF POINT =ppp h1rrlssssssaaaaSVspppt [#aaaa|OriaXTppp]

Bosch Security Systems | 1/05 | 4998122703D

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Status report. The transmitter at the POINT in the AREA in the second line of the report has a low battery.

127

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

764. Status: Trouble

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasSsssst [#aaaa|NYY]

765. Status: Trouble

Printer:

dd/dd tt:tt Lxx ACC aaaa S: TROUBLE +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSTspppt [#aaaa|OriaBTppp]

D6500 Mode: SIA Mode:

766. Status: Trouble

767. Status: Trouble

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

768. Status: Trouble (point > 254)

769. Supervision (Non-Fire)

770. Supervision (Non-Fire) (points > 254) 771. Supervision (Non-Fire) (points > 254) (Ground Fault) 772. Swinger Bypass

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

128

Explanation

STATUS REPORT

dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z h1rrlssssssaaaaSTssszt [#aaaa|OBTz] dd/dd tt:tt Lxx ACC aaaa S:TROUBLE +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaaSTspppt [#aaaa|OriaBTppp]

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Indicates that the next report is an Account Status Report. Status report initiated by Skeds or by a user. The POINT in the AREA in the second line of the report is in a trouble condition.

1.

9, D9112 Status report initiated by Skeds or by a user. The POINT in the AREA in the second line of the report is in a trouble condition.

dd/dd tt:tt Lxx ACC aaaa S:TROUBLE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaaSTppppt [#aaaa|OriaaBTpppp] dd/dd tt:tt Lxx ACC aaaa SUPERVISION +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasJspppt [#aaaa|NriaBSppp] dd/dd tt:tt Lxx ACC aaaa SUPERVISION +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasJppppt [#aaaa|NriaaBSpppp] dd/dd tt:tt Lxx ACC aaaa SUPERVISION +++ACC aaaa GROUND FAULT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasJppppt [#aaaa|NriaaBSpppp] dd/dd tt:tt Lxx ACC aaaa SWINGER BYPASS +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasNspppt [#aaaa|NriaUBppp]

The POINT in the AREA in the second line of the report (that was programmed for swinger bypass) is faulted, and was bypassed while the system was armed. If the point is restored while the system is armed, it returns to the system and is ready to detect faults.

1.

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

773. Swinger Bypass (Area and ID Not Reported)

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasNspppt [#aaaa|NUBppp]

774. Swinger Bypass

Printer: D6500 Mode: SIA Mode: Printer:

775. Swinger Bypass (point > 254) 776. Swinger Bypass (7112 Only) 777. Test Failed (Report from UPLINK router indicating “Transceiver Test Failure”)

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode:

Explanation

SWINGER BYPASS POINT=ppp

dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z h1rrlssssssaaaasTssszt [#aaaa|NBTz] dd/dd tt:tt Lxx ACC aaaa SWINGER BYPASS +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasNppppt [#aaaa|NriaaUBpppp] dd/dd tt:tt Lxx ACC aaaa SWINGER BYPASS h1rrlssssssaaaasNsssst [#aaaa|NUB] dd/dd tt:tt Lxx ACC aaaa TEST FAILED +++ ACC aaaa PATH=001 COND=001 +++ ACC aaaa UPLINK. h1rrlssssssaaaasTsD49t [#aaaa|Npt001XX001

Bosch Security Systems | 1/05 | 4998122703D

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The POINT in the AREA in the second line of the report (that was programmed for swinger bypass) is faulted, and was bypassed while the system was armed. If the point is restored while the system is armed, it returns to the system, and is ready to detect faults. 2, 9.

129

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88: Event

778. Test-Off Normal Expaned

Radionics Modem IIIa2 Messages (continued) Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa TEST-OFF NORMAL +++ACC aaaa LOG THRESHOLD +++ACC aaaa LOG OVERFLOW +++ACC aaaa PT BUS TROUBLE +++ACC aaaa PROG ACCESS OK +++ACC aaaa RF RCVR TROUBLE +++ACC aaaa BAD CALL TO RAM +++ACC aaaa USER TAMPER +++ACC aaaa SDI FAILURE +++ACC aaaa COMM FAILURE +++ACC aaaa EQUIPMENT FAIL +++ACC aaaa AC FAILURE +++ACC aaaa BATTERY MISSING +++ACC aaaa BATTERY LOW +++ACC aaaa PARMS BAD CKSUM +++ACC aaaa PHONE FAIL +++ACC aaaa EXTRA RF POINT +++ACC aaaa RF INTERFERENCE +++ACC aaaa FIRE SUPERVISION +++ACC aaaa ANALOG SERVICE +++ACC aaaa FIRE FAULT +++ACC aaaa CTRL POINT FAULT +++ACC aaaa CHK DEVICE FAULT +++ACC aaaa NETWORK FAILURE

D6500 Mode:

h1rrlssssssaaaasRsssEt h1rrlssssssaaaaSBsssst h1rrlssssssaaaaSLsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSRsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSUsssst h1rrlssssssaaaaSDsssst h1rrlssssssaaaaSPsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSPsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSMsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSEsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSGsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSTsssst h1rrlssssssaaaaSTsssst

+++ACC aaaa

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

RF RCVR TAMPER

h1rrlssssssaaaaSXss35t

130

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

Explanation

Test-Off Normal Expaned

SIA Mode:

[#aaaa|NRY] [#aaaa|OJL] [#aaaa|OJO] [#aaaa|OET] [#aaaa|OLS] [#aaaa|OET] [#aaaa|ORA] [#aaaa|OJA] [#aaaa|OET] [#aaaa|OYC] [#aaaa|OIA] [#aaaa|OAT] [#aaaa|OYM] [#aaaa|OYT] [#aaaa|OYF] [#aaaa|OLT] [#aaaa|OXF] [#aaaa|OXQ] [#aaaa|OFS] [#aaaa|OAS] [#aaaa|OFT] [#aaaa|OBT] [#aaaa|OBT] [#aaaa|ONT]

779. Test Report NonExpanded

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasRsssEt [#aaaa|NRP]

TEST REPORT

780. Time Changed

Printer:

TIME CHANGED

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa ID= iii h1rrlssssssaaaasNsD07t [#aaaa|NidiiiJT]

781. Time Changed

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasNsD07t [#aaaa|NJT]

TIME CHANGED

782. Time Changed (users > 254)

Printer:

TIME CHANGED ID=iiii

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasNsD07t [#aaaa|NidiiiiJT]

783. Transmitter Battery Restoral

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa RESTORAL h1rrlssssssaaaasRssszt [#aaaa|NURz]

784. Transmitter Battery Restoral

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RF BATT RESTORE +++ ACC aaaa AREA=a RF POINT=ppp h1rrlssssssaaaasRspppt [#aaaa|NriaXRppp]

785. Transmitter Low Battery

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasTssszt [#aaaa|NBTz]

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

[#aaaa|OXS]

Bosch Security Systems | 1/05 | 4998122703D

TROUBLE

ZN

ZN

Test Report

D9112

z

z

D7112

The RF POINT transmitter in the AREA in the second line of the report was restored from a low battery.

1, D7112

D7112

131

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

786. Transmitter Low Battery

Device/Mode

Display

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Printer:

dd/dd tt:tt Lxx ACC aaaa RF BATTERY LOW +++ ACC aaaa AREA=a RF POINT=ppp h1rrlssssssaaaasTspppt [#aaaa|NriaXTppp]

The RF POINT transmitter in the AREA in the second line of the report has a low battery.

1,

Tamper alarm at the RF POINT in the AREA in the second line of the report.

1,

D6500 Mode: SIA Mode:

D7112

787. Transmitter Tamper Alarm

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa TAMPER ALARM +++ ACC aaaa AREA=a RF POINT=ppp h1rrlssssssaaaasAspppt [#aaaa|NriaTAppp]

788. Transmitter Tamper Alarm

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasAssszt [#aaaa|NBAz]

789. Transmitter Tamper Restoral

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasRssszt [#aaaa|NURZ]

790. Transmitter Tamper Restoral

Printer:

dd/dd tt:tt Lxx ACC aaaa TAMPER RESTORAL +++ ACC aaaa AREA=a RF POINT=ppp h1rrlssssssaaaasRspppt [#aaaa|NriaTRppp]

The tamper alarm at the RF POINT in the AREA in the second line of the report was restored.

1,

791. Transmitter Tamper Trouble

Printer:

Tamper trouble at the RF POINT in the AREA in the second line of the report.

1,

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa TAMPER TROUBLE +++ ACC aaaa AREA=a RF POINT=ppp h1rrlssssssaaaasTspppt [#aaaa|NriaTTppp]

792. Transmitter Tamper Trouble

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa TROUBLE h1rrlssssssaaaasTssszt [#aaaa|NBTz]

793. Trouble

Printer:

Unexpanded trouble report. The POINT in the AREA in the second line of the report is in a trouble condition. Unexpanded trouble report. The POINT in the AREA in the second line of the report is in a trouble condition.

D6500 Mode: SIA Mode:

ALARM

ZN

RESTORAL ZN

ZN

z

D7112

z

D7112

z

SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasTsssst [#aaaa|NBT]

TROUBLE REPORT

795. Trouble

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasTssszt [#aaaa|NBTz]

TROUBLE

796. Trouble

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa TROUBLE h1rrlssssssaaaasTszyyt [#aaaa|NBTzyy]

ZN zyy

797. Trouble

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa TROUBLE h1rrlssssssaaaasTssxxt [#aaaa|NBTxx

ZN

xx

798. Trouble

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasTss16t [#aaaa|NBT16]

TROUBLE ZN

16

The zone number shown (1 to 8) reports a trouble condition.

799. Trouble

Printer:

dd/dd tt:tt Lxx ACC aaaa TROUBLE REPORT +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasTspppt [#aaaa|NriaBTppp]

Unexpanded trouble report. The POINT in the AREA in the second line of the report is in a trouble condition.

132

D7112

9.

794. Trouble

D6500 Mode: SIA Mode:

D7112

2,

dd/dd tt:tt Lxx ACC aaaa TROUBLE REPORT +++ ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasTspppt [#aaaa|NriaBTppp]

D6500 Mode:

D7112

ZN

1, 10.

z

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

800.

Trouble (Area Not Reported)

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasTspppt [#aaaa|NBTppp]

D6500 Mode: SIA Mode:

801. Trouble (with Ground Fault) (point > 254)

Printer:

802. Trouble Door Forced (point > 254)

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: 803. Trouble (point > 254)

Printer:

Explanation

TROUBLE REPORT POINT=ppp

dd/dd tt:tt Lxx ACC aaaa TROUBLE REPORT +++ACC aaaa DOOR FORCED +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasTppppt [#aaaa|NriaaDJpppp]

D6500 Mode: SIA Mode: 804. Trouble Fire

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa TROUBLE h1rrlssssssaaaaGsssszt [#aaaa|NFTz]

FR

805. Unknown Message

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx UNKNOWN h1rrlsssssssssssXss25t [NYO]

RCVR rr

806. Unverfied Events (points < 255)

Printer:

dd/dd tt:tt Lxx ACC aaaa UNVRFD EVT-BURG +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasKspppt [#aaaa|NriaBGppp]

807. Unverfied Events (points < 255)

Printer:

808. Unverfied Events (points < 255)

Printer:

809. Unverfied Events (points < 255)

Printer:

810. Unverfied Events (points < 255)

Printer:

811. Unverfied Events (points > 254)

Printer:

812. Unverfied Events (points > 254)

Printer:

813. Unverfied Events (points > 254)

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

Unexpanded trouble report. The POINT in the AREA in the second line of the report is in a trouble condition.

dd/dd tt:tt Lxx ACC aaaa TROUBLE REPORT +++ACC aaaa GROUND FAULT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasTppppt [#aaaa|NriaaBTpppp]

dd/dd tt:tt Lxx ACC aaaa TROUBLE REPORT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasTppppt [#aaaa|NriaaBTpppp]

D6500 Mode: SIA Mode:

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

z

dd/dd tt:tt Lxx ACC aaaa UNVRFD EVT-FIRE +++ACC aaaa AREA=a POINT=ppp h1rrlssssssaaaasKspppt [#aaaa|NriaFGppp] dd/dd tt:tt Lxx ACC aaaa UNVRFD EVT-BURG +++ACC aaaa AREA=a CG=gg POINT=ppp h1rrlssssssaaaasKspppt [#aaaa|NriaBGppp] dd/dd tt:tt Lxx ACC aaaa UNVRFD EVT-FIRE +++ACC aaaa AREA=a CG=gg POINT=ppp h1rrlssssssaaaasKspppt [#aaaa|NriaFGppp] dd/dd tt:tt Lxx ACC aaaa UNVERFIED EVENT +++ACC aaaa AREA=a CG=gg POINT=ppp h1rrlssssssaaaasKspppt [#aaaa|NriaUGppp] dd/dd tt:tt Lxx ACC aaaa UNVRFD EVT-BURG +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasKppppt [#aaaa|NriaaBGpppp] dd/dd tt:tt Lxx ACC aaaa UNVRFD EVT-FIRE +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasKppppt [#aaaa|NriaaFGpppp] dd/dd tt:tt Lxx ACC aaaa UNVRFD EVT-BURG +++ACC aaaa AREA=aa CG=gg POINT=pppp h1rrlssssssaaaasKppppt [#aaaa|NriaaBGpppp]

Bosch Security Systems | 1/05 | 4998122703D

133

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

814. Unverfied Events (points > 254)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa UNVRFD EVT-FIRE +++ACC aaaa AREA=aa CG=gg POINT=pppp h1rrlssssssaaaasKppppt [#aaaa|NriaaFGpppp]

815. User Alarm

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa USR ALRM ZN h1rrlssssssaaaasUssszt [#aaaa|NPAz]

816. User Alarm 7

Printer: D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa USER ALARM CMD7 +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasUsss7t [#aaaa|Nria/idiiiUA]

A user with the ID in the second line of the report initiated a CMD 7 in the AREA.

1.

A user with the ID in the second line of the report initiated a CMD 7 in the AREA.

1,

z

817. User Alarm 7 (ID not reported)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa USER ALARM CMD7 +++ ACC aaaa AREA=a h1rrlssssssaaaasUsss7t [#aaaa|NriaUA]

818. User Alarm 7

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasAssszt [#aaaa|NBAz]

Printer:

dd/dd tt:tt Lxx ACC aaaa USER ALARM CMD7 +++ACC aaaa AREA=a h1rrlssssssaaaasUsss7t [#aaaa|NriaUA]

819. User Alarm 7 (area only)

D6500 Mode: SIA Mode: 820. User Alarm 7 (user > 254)

821. User Alarm 9

822. User Alarm 9

(ID not reported) 824. User Alarm 9 (area only)

2, D7112: z=7 D9112: z= as programmed for point (Point Code Digit One =4)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasAssszt [#aaaa|NBAz]

Printer:

dd/dd tt:tt Lxx ACC aaaa USER ALARM CMD9 +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasUsss9t [#aaaa|Nria/idiiiPA]

A user with the ID in the second line of the report initiated a CMD 9 in the specified AREA.

1.

dd/dd tt:tt Lxx ACC aaaa USER ALARM CMD9 +++ ACC aaaa AREA=a h1rrlssssssaaaasUsss9t [#aaaa|NriaPA]

A user with the ID in the second line of the report initiated a CMD 9 in the specified AREA.

1,

Printer: D6500 Mode: SIA Mode: Printer:

Printer: D6500 Mode: SIA Mode:

134

z

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: 825. User Alarm 9 (user > 254)

ZN

dd/dd tt:tt Lxx ACC aaaa USER ALARM CMD7 +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasUsss7t [#aaaa|Nriaa/idiiiiUA]

Printer:

D6500 Mode: SIA Mode: 823. User Alarm 9

ALARM

D7112

ALARM ZN

z

2, D7112: z=9 D9112: z= as programmed for point (Point Code Digit One =5)

D7112

dd/dd tt:tt Lxx ACC aaaa USER ALARM CMD9 +++ACC aaaa AREA=a h1rrlssssssaaaasUsss9t [#aaaa|NriaPA] dd/dd tt:tt Lxx ACC aaaa USER ALARM CMD9 +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasUsss9t [#aaaa|Nriaa/idiiiiPA]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

826. User Code Added

Device/Mode

Display

Printer:

dd/dd tt:tt Lxx ACC aaaa USER CODE ADDED +++ ACC aaaa CODE ID=ccc ID=iii h1rrlssssssaaaasNsD38t [#aaaa|NidiiiJYccc]

D6500 Mode: SIA Mode: 827. User Code Added (users > 254, code > 254)

Printer:

828. User Code Changed

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

829. User Code Changed

Printer: D6500 Mode: SIA Mode:

830. User Code Changed (operator ID not reported)

Printer: D6500 Mode: SIA Mode:

831. User Code Changed (users > 254)

Printer:

832. User Code Deleted

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: 833. User Code Deleted

Printer: D6500 Mode: SIA Mode:

834. User Code Deleted

Printer: D6500 Mode: SIA Mode:

835. User Code Deleted (operator ID not reported)

836. User Code Deleted (User ID# > 254 reported)

Printer: D6500 Mode: SIA Mode:

Printer: D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa USER CODE ADDED +++ACC aaaa CODE ID=cccc ID=iiii h1rrlssssssaaaasNsD38t [#aaaa|NidiiiiJYcccc] dd/dd tt:tt Lxx ACC aaaa USR CODE CHANGE +++ ACC aaaa CODE ID=ccc ID=iii h1rrlssssssaaaasNsD04t [#aaaa|NidiiiJVccc]

The passcode user ID in the second line of the report was changed by the operator with the specified OPER ID.

dd/dd tt:tt Lxx ACC aaaa USR CODE CHANGE +++ ACC aaaa AREA=a CODE ID=ccc ID=iii h1rrlssssssaaaasNsD04t [#aaaa|Nria/idiiiJVccc]

The passcode user ID in the second line of the report was changed by the operator with the specified OPER ID.

D7112

dd/dd tt:tt Lxx ACC aaaa USR CODE CHANGE +++ ACC aaaa AREA=a CODE ID=ccc h1rrlssssssaaaasNsD04t [#aaaa|NriaJVccc]

The passcode user ID in the second line of the report was changed by the operator with the specified OPER ID.

D7112

dd/dd tt:tt Lxx ACC aaaa USR CODE DELETE +++ ACC aaaa CODE ID=ccc ID=iii h1rrlssssssaaaasNsD05t [#aaaa|NidiiiJXccc]

The user ID specified in the second line of the report was deleted by the operator with the OPER ID shown.

D9112

dd/dd tt:tt Lxx ACC aaaa USR CODE DELETE +++ ACC aaaa AREA= a CODE ID=ccc ID=iii h1rrlssssssaaaasNsD05t [#aaaa|Nria/idiiiJXccc]

The user ID specified in the second line of the report was deleted by the operator with the OPER ID shown.

D7112

The user ID specified in the second line of the report was deleted by the operator with the OPER ID shown.

D7112

dd/dd tt:tt Lxx ACC aaaa USR CODE CHANGE +++ACC aaaa CODE ID=cccc ID=iiii h1rrlssssssaaaasNsD04t [#aaaa|NidiiiiJVcccc]

dd/dd tt:tt Lxx ACC aaaa USR CODE DELETE +++ACC aaaa CODE ID=cccc h1rrlssssssaaaasNsD05t [#aaaa|NJXcccc] dd/dd tt:tt Lxx ACC aaaa USR CODE DELETE +++ ACC aaaa AREA= a CODE ID=ccc h1rrlssssssaaaasNsD05t [#aaaa|NriaJXccc]

dd/dd tt:tt Lxx ACC aaaa USR CODE DELETE +++ACC aaaa CODE ID=cccc ID=iiii h1rrlssssssaaaasNsD05t [#aaaa|NidiiiiJXcccc]

Bosch Security Systems | 1/05 | 4998122703D

135

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

837. User Code Tamper

Device/Mode

Display

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

Printer:

dd/dd tt:tt Lxx ACC aaaa USR CODE TAMPE +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasNsD03t [#aaaa|Nria/idiiiJA]

Five attempts were made in 5 min to access the AREA in the second line of the report with the invalid user ID shown.

1,

Five attempts were made in 5 min to access the AREA in the second line of the report with the invalid user ID shown.

1,

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa USR CODE TAMPER +++ ACC aaaa AREA=a h1rrlssssssaaaasNsD03t [#aaaa|NriaJA]

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa USR CODE TAMPER h1rrlssssssaaaasNsD03t [#aaaa|NJA]

Five attempts were made in 5 min to access the AREA in the second line of the report with the invalid user ID shown.

Printer:

dd/dd tt:tt Lxx ACC aaaa USER LEVEL SET +++ ACC aaaa CODE ID=ccc ID=iii h1rrlssssssaaaasNsD40t [#aaaa|NidiiiJZccc]

D6500 Mode: SIA Mode:

838. User Code Tamper

839. User Code Tamper (Area and ID Not Reported) 840. User Level Set

Printer:

D6500 Mode: SIA Mode: 841. User Level Set (modified user only)

Printer:

842. User Level Set (users > 254)

Printer:

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasNsD40t [#aaaa|NJZcccc]

D7112

USER LEVEL SET CODE ID=cccc

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa USER LEVEL SET +++ACC aaaa CODE ID=cccc ID=iiii h1rrlssssssaaaasNsD40t [#aaaa|NidiiiiJZcccc]

843. User Tamper Since Last Call

Printer: D6500 Mode: SIA Mode:

+++ ACC aaaa h1rrlssssssaaaaSUsssst [#aaaa|OJA]

844. [User Text]

Printer: D6500 Mode: SIA Mode:

+++ ACC aaaa (user text) no message no message

845. Valid Access

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa PROG ACCESS h1rrlssssssaaaasRsF01t [#aaaa|NLS]

846. Valid Access (via SDI Device or D5360)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa PROG ACCESS OK +++ACC aaaa SDI=ddd h1rrlssssssaaaasRsF01t [#aaaa|NpidddLS]

847. Valid Local Access

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasRsF01t [#aaaa|NpidddLS]

136

D9112

USER TAMPER

A supervised keypad, printer, or other serial device listed in the second line of the report does not operate.

5.

The account was locally accessed through the supervised keypad or other serial device specified in the second line of the report.

D7112

OK

PROG ACCESS OK

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

848. Valid Local Access Since Last Call

Printer: D6500 Mode: SIA Mode:

+++ ACC aaaa h1rrlssssssaaaaSRsssst [#aaaa|OLS]

849. Valid Remote Access

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasRsssFt [#aaaa|Nph5RS]

850. Valid Remote Access

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasRsssFt [#aaaa|NphhRS]

851. Valid Remote Access

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa h1rrlssssssaaaasRsssFt [#aaaa|NURF]

852. Valid Remote Access (2112, 9112)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa RAM ACCESS h1rrlssssssaaaasRsssFt [#aaaa|NRS]

853. Valid Remote Access (from Call Back)

Printer:

RAM ACCESS OK PH#=hh

D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasRsssFt [#aaaa|NphhhRS]

854. Valid Remote Access

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasRsssFt [#aaaa|NRS]

RAM ACCESS OK

855. Variable Text

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx text as received h3rrltext as receivedt [Atext as rcvd]

856. Walk Test End

Printer:

dd/dd tt:tt Lxx ACC aaaa +++ ACC aaaa h1rrlssssssaaaasRsssFt [#aaaa|NriaTE]

(phone not reported)

(no call back)

D6500 Mode: SIA Mode: 857. Walk Test End (Invisible Points) (users < 255)

Printer:

858. Walk Test End (Invisible Points) (users > 254)

Printer:

859. Walk Test End (no user)

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

The account was locally accessed through the supervised keypad or other serial device specified in the second line of the report.

5.

RAM ACCESS OK PHONE#=5

The account was contacted by a RAM on the PHONE# specified in the second line of the report.

D9112

RAM ACCESS OK

The account was contacted by a RAM on the PHONE# specified in the second line of the report.

D7112

PROG ACCESS OK

RESTORAL

ZN

F

2.

OK

The account was contacted by a RAM on the PHONE# specified in the second line of the report.

D9112

RCVR rr

WALK TEST END AREA=a

dd/dd tt:tt Lxx ACC aaaa WALK TEST END +++ACC aaaa INVISIBLE POINTS +++ACC aaaa AREA=a ID=iii h1rrlssssssaaaasRsssFt [#aaaa|Nria/idiiiTE] dd/dd tt:tt Lxx ACC aaaa WALK TEST END +++ACC aaaa INVISIBLE POINTS +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasRsssFt [#aaaa|Nriaa/idiiiiTE] dd/dd tt:tt Lxx ACC aaaa +++ACC aaaa h1rrlssssssaaaasRsssFt [#aaaa|NriaTE]

Bosch Security Systems | 1/05 | 4998122703D

WALK TEST END AREA=a

137

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

860. Walk Test End (users > 254)

Printer:

dd/dd tt:tt Lxx ACC aaaa WALK TEST END +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasRsssFt [#aaaa|Nriaa/idiiiiTE]

861. Walk Test Point (points > 254)

Printer:

862. Walk Test Point – Fire (points > 254)

Printer:

863. Walk Test Start

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

Explanation

dd/dd tt:tt Lxx ACC aaaa WALK TEST PT +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasZppppt [#aaaa|NriaaBXpppp] dd/dd tt:tt Lxx ACC aaaa WALK TST PT-FIR +++ACC aaaa AREA=aa POINT=pppp h1rrlssssssaaaasZppppt [#aaaa|NriaaFXpppp] dd/dd tt:tt Lxx ACC aaaa WALK TEST START +++ ACC aaaa AREA=a ID=iii h1rrlssssssaaaasTsssFt [#aaaa|Nria/idiiiTS]

864. Walk Test Start (Invisible Points) (users < 255)

Printer:

865. Walk Test Start (Invisible Points) (users > 254)

Printer:

866. Walk Test Start (no user)

Printer:

867. Walk Test Start (users > 254)

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa WALK TEST START +++ACC aaaa AREA=a ID=iiii h1rrlssssssaaaasTsssFt [#aaaa|Nria/idiiiiTS]

868. Was Force Armed

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa WAS FORCE ARMED h1rrlssssssaaaasWsssst [#aaaa|NCW]

Account armed with zones or points faulted. The faulted zones or POPITs were not armed. Zones, areas, or points that were not armed are indicated by a TROUBLE or SHUNTED report.

869. Watchdog Reset

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaa RESTORAL h1rrlssssssaaaasRsss9t [#aaaa|NUR9]

Battery restoral report, control panel reboot, watchdog reset, power reset, or ResetBye with RAM.

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

dd/dd tt:tt Lxx ACC aaaa WALK TEST START +++ACC aaaa INVISIBLE POINTS +++ACC aaaa AREA=a ID=iii h1rrlssssssaaaasTsssFt [#aaaa|Nria/idiiiTS] dd/dd tt:tt Lxx ACC aaaa WALK TEST START +++ACC aaaa INVISIBLE POINTS +++ACC aaaa AREA=aa ID=iiii h1rrlssssssaaaasTsssFt [#aaaa|Nriaa/idiiiiTS] dd/dd tt:tt Lxx ACC aaaa WALK TEST START +++ACC aaaa AREA=a h1rrlssssssaaaasTsssFt [#aaaa|NriaTS]

ZN

9

Control panel reboot, watchdog reset, power reset, or ResetBye with RAM (can also be battery restoral report for D7112).

138

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages . Table 88:

Radionics Modem IIIa2 Messages (continued)

Event

Device/Mode

Display

870. Watchdog Reset

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa h1rrlssssssaaaasNsD09t [#aaaa|NYW]

WATCHDOG RESET

The control panel’s watchdog reset. This is a non-emergency troubleshooting message. If it is followed by SDI ##, call Bosch Security Systems Technical Support during normal business hours for help in interpreting the message.

871. Watchdog Reset

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Lxx ACC aaaa WATCHDOG RESET +++ ACC aaaa POINT=ppp SDI=ddd h1rrlssssssaaaasNspppt [#aaaa|NpidddYWppp]

The control panel's watchdog reset. This is a non-emergency troubleshooting message. If it is followed by SDI ##, call Bosch Security Systems Technical Support during normal business hours for help in interpreting the message.

872. +5V Restored

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt +5 RESTORED h1rrssssssssssssXsss4t [NYQ]

RCVR rr

873. +5V Troubled

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt +5 TROUBLED h1rrssssssssssssXsss3t [NYP]

RCVR rr

874. +12V Restoral

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt +12 RESTORED h1rrssssssssssssXsss4t [NYQ]

RCVR rr

875. +12V Trouble

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt +12 TROUBLED h1rrssssssssssssXsss3t [NYP]

RCVR rr

876. -12V Restoral

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt -12 RESTORED h1rrssssssssssssXsss4t [NYQ]

RCVR rr

877. -12V Trouble

Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt -12 TROUBLED h1rrssssssssssssXsss3t [NYP]

RCVR rr

(SDI Device and Point reported)

Bosch Security Systems | 1/05 | 4998122703D

Explanation

Refer to Section C.1 Bosch Security Systems Zonex and COMEX Translation on page 140

139

D6600 | Computer Interface Manual | Appendix C: Radionics Modem IIIa2 Messages

C.1

Bosch Security Systems Zonex and COMEX Translation

These numbered items correspond to the number in the last column in Table 88 starting on page 61. 1. The D7112/D9112 verifies the user identification and point data formats and sends them to the automation system. If the control panel requests a translation, the D6600 converts point data to Zonex format and user IDs to COMEX format. If there is no request for translation, points and IDs are sent to the automation PC and print on the connected printer with no conversion. Table 90 shows the translation of User IDs and Table 89 shows the translation of point data. Table 89: Point 001-008 009-024 025-040 041-056 057-072 073-088 089-104 105-120 121-136 137-152 153-168 169-184 185-200 201-216 217-232 233-247

Table 90: ID 0 1-5 0-13 14-21 22-29 30-37 38-45 46-53 54-61 62-69 70-249

2. 3. 140

Point to ZONEX Translation ZONEX 100-800 101-116 201-216 301-316 401-416 501-516 601-616 701-716 801-816 117-132 217-232 317-332 417-432 517-532 617-632 717-731

User ID to COMEX Translation COMEX 0 001-005 601-608 701-708 801-808 B01-B08 C01-C08 D01-D08 E01-E08 F01-F08 000

4.

When the D7112 is transmitting a test report in Modem II format, the area number is sent to the automation system if the output format is in SIA communications mode.

Example 1: Log Threshold Since Last Call [#aaaa|OriaJL] 5.

6.

7.

8.

9.

When transmitted by a D7112, the identification number, if any, also prints. Refer to Forced Point in the D9112B Program Entry Guide (P/N: 74-06145-000-D). Not entering a phone number turns off these messages for the event class. All messages in this class exist in a unique event class. For these events, the area denotes the location of the keypad used to initiate the event (see Sensor Reset). BFSK Format: For the D9112, unless otherwise specified, the zone digit "z" uses the "BFSK Zone Code" as a base for a given point. This code is programmed in the control panel by point. The zone digit "i" indicates the most significant digit of the user ID. For the D7112, unless otherwise specified, Table 91 is the basis for the zone digit "z” and ID translation; however, actual IDs only go up to 25.

Table 91:

Reported Zone/ID to Actual Point/ID

Reported Zone/ID Actual Point/ID

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 17 25 33 41

10 18 26 34 42

11 19 27 35 43

12 20 28 36 44

13 21 29 37 45

14 22 30 38 46

15 23 31 39 47

16 24 32 40 48

10. This message reports from a D7112 RF point. The internal or external printer prints the label “RF POINT=” instead of “POINT=” in the second line (Example 2). Example 2: Label RF Point dd/dd tt:tt ql ACC aaaa FIRE ALARM +++ ACC aaaa AREA=a RF POINT=ppp

A D7112 using the Modem II format can transmit these messages. Not used. Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix D: NetCom Messages .

Appendix D: NetCom Messages For networked accounts, Nxx appears instead of Lxx in the line number.

Table 92:

1

2

3

4

5

6

7

8

9

10

NetCom Messages

Event

Device/Mode

Display

Explanation

Alarm-Panel Substitution

Printer:

dd/dd tt:tt Nxx ACC aaaa ALARM-PNL SUBST +++ ACC aaaa PATH=003 COND=007 h1rrlssssssaaaaAsD53t [#aaaa|Npt003AA007] dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 VOLTAGE LOW h1rrlssssssaaaasXss58t [#aaaa|NSC0002] dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 VOLTAGE RESTORE h1rrlssssssaaaasXss68t [#aaaa|NSC0003]

Condition 007 = Substitution/ Replay

Change Of Status (C900 Voltage Low) Change Of Status (C900 Voltage Restore) Change Of Status (C900 Input Restored) Change Of Status (C900 Input Shorted) Change Of Status (C900 Intercept Disabled)

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Change Of Status (C900 Intercept Enabled)

Printer:

Change Of Status (C900 Output Activated)

Printer:

Change Of Status (C900 Output Deactivated)

Printer:

Change Of Status (C900 Input Open)

Printer:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode:

dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 INPUT RESTORED h1rrlssssssaaaasXss91t [#aaaa|NSC0010] dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 INPUT SHORTED h1rrlssssssaaaasXss89t [#aaaa|NSC0008] dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 INTERCEPT DISABLED h1rrlssssssaaaasXss93t [#aaaa|NSC0012] dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 INTERCEPT ENABLED h1rrlssssssaaaasXss92t [#aaaa|NSC0011] dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 OUTPUT ACTIVATED h1rrlssssssaaaasXss85t [#aaaa|NSC0006] dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 OUTPUT DEACTIVATED h1rrlssssssaaaasXss94t [#aaaa|NSC0007] dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 INPUT OPEN H1rrlssssssaaaasXss90t [#aaaa|NSC0009]

Bosch Security Systems | 1/05 | 4998122703D

141

D6600 | Computer Interface Manual | Appendix D: NetCom Messages

Table 92:

11

12

13

14

15

16

17

18

19

20

21

NetCom Messages (continued)

Event

Device/Mode

Display

Change Of Status (C900 Reboot)

Printer:

dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 REBOOT h1rrlssssssaaaasXss59t [#aaaa|NSC0001] dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 SWITCHED TO FALLBACK h1rrlssssssaaaasXss82t [#aaaa|NSC0005]

Change Of Status (C900 Switched to Fallback)

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

Change Of Status (C900 Switched To Intercept)

Printer:

Command Sent (Activate Output)

Printer:

Command Sent (Deactivate Output) Command Sent (Disable Intercept Mode) Command Sent (Switch To Fallback Mode) Command Sent (Switch To Intercept Mode) Command Sent (Supervision Rate Changed) Communications Fail (Account Disabled By Attack) Communications Fail (Polling Lost)

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

142

Explanation

dd/dd tt:tt Nxx ACC aaaa STATUS CHANGED +++ aaaa C900 SWITCHED TO INTERCPT h1rrlssssssaaaasXss87t [#aaaa|NSC0004] dd/dd tt:tt Nxx ACC aaaa COMMAND SENT +++ aaaa ACTIVATE OUTPUT h1rrlssssssaaaasXss84t [#aaaa|NCO0005] dd/dd tt:tt Nxx ACC aaaa COMMAND SENT +++ aaaa DEACTIVATE OUTPUT h1rrlssssssaaaasXss86t [#aaaa|NCO0006] dd/dd tt:tt Nxx ACC aaaa COMMAND SENT +++ aaaa DISABLE INTERCEPT MODE h1rrlssssssaaaasXss83t [#aaaa|NCO0004] dd/dd tt:tt Nxx ACC aaaa COMMAND SENT +++ aaaa SWITCH TO FALLBACK MODE h1rrlssssssaaaasXss81t [#aaaa|NCO0003] dd/dd tt:tt Nxx ACC aaaa COMMAND SENT +++ aaaa SWITCH TO INTERCEPT MODE h1rrlssssssaaaasXss88t [#aaaa|NCO0002] dd/dd tt:tt Nxx ACC aaaa COMMAND SENT +++ aaaa SUPERVISION RATE CHANGED h1rrlssssssaaaasXss66t [#aaaa|NCO0001] dd/dd tt:tt Nxx ACC aaaa COMM FAIL +++ ACC aaaa ACCOUNT DISABLED BY ATTACK +++ ACC aaaa PATH=003 COND=008 h1rrlssssssaaaasTsB03t [#aaaa|Npt003YC008] dd/dd tt:tt Nxx ACC aaaa COMM FAIL +++ ACC aaaa PATH=003 COND=009 h1rrlssssssaaaasTsB02t [#aaaa|Npt003YC009]

Condition 008 = Attack

Condition 009 = Polling Monitor

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix D: NetCom Messages . Table 92:

22

23

24

25

26

27

28

29

30

NetCom Messages (continued)

Event

Device/Mode

Display

Explanation

Communications Fail Restore (Poll Restore)

Printer:

Condition 009 = Polling Monitor

Dialer Error (Dialing Error)

Printer:

dd/dd tt:tt Nxx ACC aaaa COMM FAIL RESTR +++ ACC aaaa PATH=003 COND=009 h1rrlssssssaaaasNsB02t [#aaaa|Npt003YK009] dd/dd tt:tt Nxx ACC aaaa DIALER ERROR +++ aaaa DIALING ERROR h1rrlssssssaaaasXss73t [#aaaa|NYU0003] dd/dd tt:tt Nxx ACC aaaa DIALER ERROR +++ aaaa INVALID MESSAGE h1rrlssssssaaaasXss77t [#aaaa|NYU0007] dd/dd tt:tt Nxx ACC aaaa DIALER ERROR +++ aaaa MESSAGE UNKNOWN h1rrlssssssaaaasXss76t [#aaaa|NYU0006] dd/dd tt:tt Nxx ACC aaaa DIALER ERROR +++ aaaa NO ACKNOWLEDGMNT RECEIVED h1rrlssssssaaaasXss71t [#aaaa|NYU0001]

Dialer Error (Invalid Message)

Dialer Error (Message Unknown) Dialer Error (No Acknowledgement Received) Dialer Error (Not Dialing)

Dialer Error (No Response to Acknowledgement) Dialer Error (No Response to Handshake) Miscellaneous Message (30 Minutes Since Fallback Command)

D6500 Mode: SIA Mode:

D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

dd/dd tt:tt Nxx ACC aaaa DIALER ERROR +++ aaaa NOT DIALING h1rrlssssssaaaasXss72t [#aaaa|NYU0002] dd/dd tt:tt Nxx ACC aaaa DIALER ERROR +++ aaaa NO RESPONSE TO ACK h1rrlssssssaaaasXss75t [#aaaa|NYU0005] dd/dd tt:tt Nxx ACC aaaa DIALER ERROR +++ aaaa NO RESPONSE TO HANDSHAKE h1rrlssssssaaaasXss74t [#aaaa|NYU0004] dd/dd tt:tt Nxx ACC aaaa MESSAGE +++ aaaa 30 MIN SINCE FALLBACK CMD h1rrlssssssaaaasXss95t [#aaaa|NMI0001]

Bosch Security Systems | 1/05 | 4998122703D

143

D6600 | Computer Interface Manual | Appendix E: Pulse Output

Appendix E: Pulse Output Table 93 to Table 101 (on page 148) vary depending on the account number specified and the digit parameter programmed using the drop-down menus in Menu Item 3.1.7 Event 3/1 or 4/1 (Figure 22).

Figure 22: D6200 Receiver Software Line Card Configuration

The output of the receiver depends on the reporting digit. Use the settings in Figure 22 that can be changed by the user: • Reporting digits 0 to 9 and A are alarms • Reporting digit B is an opening • Reporting digit C is a closing • Reporting digit D is a cancel • Reporting digit E is a restore Table 93: #

Event

1.

Pulse 3/1 Format

ALARM

Account Number 123

Reporting Digit 4

2.

OPENING

123

B

3.

CLOSING

123

C

4.

CANCEL

123

D

5.

RESTORE

123

E

6.

TROUBLE

123

F

144

Device/Mode

Displays

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

DD/DD TT:TT L01 ACCT 123 ALARM_ZN 4 [10]1011sssssss123sAsss4[13] [10]602415[9]00030101[#s123|NBA4][13] DD/DD TT:TT L01 ACCT 123 OPENING [10]1011sssssss123sOssss[13] [10]AA4214[9]00040101[#s123|NOP][13] DD/DD TT:TT L01 ACCT 123 CLOSING [10]1011sssssss123sCssss[13] [10]F94B14[9]00050101[#s123|NCL][13] DD/DD TT:TT L01 ACCT 123 CANCEL [10]1011sssssss123s\ssss[13] [10]FBCE14[9]00060101[#s123|NOC][13] DD/DD TT:TT L01 ACCT 123 RESTORE [10]1011sssssss123sRssss[13] [10]FC2214[9]00070101[#s123|NUR][13] DD/DD TT:TT L01 ACCT 123 TROUBLE [10]1011sssssss123sTssss[13] [10]ACD414[9]00080101[#s123|NBT][13]

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix E: Pulse Output . Table 94: #

Event

7.

Pulse 3/1E Menu 3.1.3.12 3-1 Extended Format = 1

ALARM

Account Number 123

Reporting Digit 45

8.

OPENING

123

B5

9.

CLOSING

123

C5

10.

CANCEL

123

D5

11.

RESTORE

123

E5

12.

TROUBLE

123

F5

Table 95: #

Event

13.

Device/Mode

Displays

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

DD/DD TT:TT L01 ACCT 123 ALARM_ZN 45 [10]1011sssssss123sAss45[13] [10]720816[9]00090101[#s123|NBA45][13] DD/DD TT:TT L01 ACCT 123 OPENING ZN 5 [10]1011sssssss123sOsss5[13] [10]B0B115[9]00100101[#s123|NOP5][13] DD/DD TT:TT L01 ACCT 123 CLOSING ZN 5 [10]1011sssssss123sCsss5[13] [10]B62215[9]00110101[#s123|NCL5][13] DD/DD TT:TT L01 ACCT 123 CANCEL ZN 5 [10]1011sssssss123s\sss5[13] [10]15E115[9]00120101[#s123|NOC5][13] DD/DD TT:TT L01 ACCT 123 RESTORE ZN 5 [10]1011sssssss123sRsss5[13] [10]98E715[9]00130101[#s123|NUR5][13] DD/DD TT:TT L01 ACCT 123 TROUBLE ZN 5 [10]1011sssssss123sTsss5[13] [10]1CB015[9]00140101[#s123|NBT5][13]

Pulse 3/1E Menu 3.1.3.12 3-1 Extended Format = 2

ALARM

Account Number 123

Reporting Digit 45

14.

OPENING

123

B5

15.

CLOSING

123

C5

16.

CANCEL

123

D5

17.

RESTORE

123

E5

18.

TROUBLE

123

F5

Device/Mode

Displays

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

DD/DD TT:TT L01 ACCT 123 ALARM_ZN 45 [10]1011sssssss123sAss45[13] [10]210D16[9]00450102[#s123|NBA45][13] DD/DD TT:TT L01 ACCT 123 OPENING ZN B5 [10]1011sssssss123sOssB5[13] [10]829516[9]00460102[#s123|NOPB5][13] DD/DD TT:TT L01 ACCT 123 CLOSING ZN C5 [10]1011sssssss123sCssC5[13] [10]2F8216[9]00470102[#s123|NCLC5][13] DD/DD TT:TT L01 ACCT 123 CANCEL ZN D5 [10]1011sssssss123s\ssD5[13] [10]EC1316[9]00480102[#s123|NOCD5][13] DD/DD TT:TT L01 ACCT 123 RESTORE ZN E5 [10]1011sssssss123sRssE5[13] [10]2E4F16[9]00490102[#s123|NURE5][13] DD/DD TT:TT L01 ACCT 123 TROUBLE ZN F5 [10]1011sssssss123sTssF5[13] [10]C72516[9]00500102[#s123|NBTF5][13]

Bosch Security Systems | 1/05 | 4998122703D

145

D6600 | Computer Interface Manual | Appendix E: Pulse Output

Table 96: #

Event

19.

Pulse 3/2

ALARM

Account Number 123

Reporting Digit 45

20.

OPENING

123

B5

21.

CLOSING

123

C5

22.

CANCEL

123

D5

23.

RESTORE

123

E5

24.

TROUBLE

123

F5

Table 97: #

Event

25.

Displays

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

DD/DD TT:TT L01 ACCT 123 ALARM_ZN 45 [10]1011sssssss123sAss45[13] [10]446B16[9]00150101[#s123|NBA45][13] DD/DD TT:TT L01 ACCT 123 OPENING B5 [10]1011sssssss123sOssB5[13] [10]17F616[9]00160101[#s123|NOPB5][13] DD/DD TT:TT L01 ACCT 123 CLOSING B5 [10]1011sssssss123sCssC5[13] [10]BAE116[9]00170101[#s123|NCLC5][13] DD/DD TT:TT L01 ACCT 123 CANCEL B5 [10]1011sssssss123s\ssD5[13] [10]797016[9]00180101[#s123|NOCD5][13] DD/DD TT:TT L01 ACCT 123 RESTORE B5 [10]1011sssssss123sRssE5[13] [10]BB2C16[9]00190101[#s123|NURE5][13] DD/DD TT:TT L01 ACCT 123 TROUBLE B5 [10]1011sssssss123sTssF5[13] [10]EA3F16[9]00200101[#s123|NBTF5][13]

Device/Mode

Displays

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

DD/DD TT:TT L01 ACCT 1234 ALARM_ZN 5 [10]1011ssssss1234sAsss5[13] [10]97CE15[9]00210101[#1234|NBA5][13] DD/DD TT:TT L01 ACCT 1234 OPENING [10]1011ssssss1234sOssss[13] [10]020A14[9]00220101[#1234|NOP][13] DD/DD TT:TT L01 ACCT 1234 CLOSING [10]1011ssssss1234sCssss[13] [10]510314[9]00230101[#1234|NCL][13] DD/DD TT:TT L01 ACCT 1234 CANCEL [10]1011ssssss1234s\ssss[13] [10]908414[9]00240101[#1234|NOC][13] DD/DD TT:TT L01 ACCT 1234 RESTORE [10]1011ssssss1234sRssss[13] [10]976814[9]00250101[#1234|NUR][13] DD/DD TT:TT L01 ACCT 1234 TROUBLE [10]1011ssssss1234sTssss[13] [10]C29B14[9]00260101[#1234|NBT][13]

Pulse 4/1

ALARM

Account Number 1234

Reporting Digit 5

26.

OPENING

1234

B

27.

CLOSING

1234

C

28.

CANCEL

1234

D

29.

RESTORE

1234

E

30.

TROUBLE

1234

F

146

Device/Mode

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix E: Pulse Output . Table 98: #

Event

31.

Pulse 4/1E Menu 3.1.3.3 4/1 Extended = 1

ALARM

Account Number 1234

Reporting Digit 45

32.

OPENING

1234

B5

33.

CLOSING

1234

C5

34.

CANCEL

1234

D5

35.

RESTORE

1234

E5

36.

TROUBLE

1234

F5

Table 99: #

Event

37.

Device/Mode

Displays

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

DD/DD TT:TT L01 ACCT 1234 ALARM_ZN 45 [10]1011ssssss1234sAss45[13] [10]418416[9]00270101[#1234|NBA45][13] DD/DD TT:TT L01 ACCT 1234 OPENING ZN 5 [10]1011ssssss1234sOsss5[13] [10]C5C215[9]00280101[#1234|NOP5][13] DD/DD TT:TT L01 ACCT 1234 CLOSING ZN 5 [10]1011ssssss1234sCsss5[13] [10]C35115[9]00290101[#1234|NCL5][13] DD/DD TT:TT L01 ACCT 1234 CANCEL ZN 5 [10]1011ssssss1234s\sss5[13] [10]3EE515[9]00300101[#1234|NOC5][13] DD/DD TT:TT L01 ACCT 1234 RESTORE ZN 5 [10]1011ssssss1234sRsss5[13] [10]B3E315[9]00310101[#1234|NUR5][13] DD/DD TT:TT L01 ACCT 1234 TROUBLE ZN 5 [10]1011ssssss1234sTsss5[13] [10]F6F615[9]00320101[#1234|NBT5][13]

Pulse 4/1E Menu 3.1.3.3 4/1 Extended = 2

ALARM

Account Number 1234

Reporting Digit 45

38.

OPENING

1234

B5

39.

CLOSING

1234

C5

40.

CANCEL

1234

D5

41.

RESTORE

1234

E5

42.

TROUBLE

1234

F5

Device/Mode

Displays

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

DD/DD TT:TT L01 ACCT 1234 ALARM_ZN 45 [10]1011ssssss1234sAss45[13] [10]599816[9]00510102[#1234|NBA45][13] DD/DD TT:TT L01 ACCT 1234 OPENING ZN B5 [10]1011ssssss1234sOssB5[13] [10]FA0016[9]00520102[#1234|NOPB5][13] DD/DD TT:TT L01 ACCT 1234 CLOSING ZN C5 [10]1011ssssss1234sCssC5[13] [10]571716[9]00530102[#1234|NCLC5][13] DD/DD TT:TT L01 ACCT 1234 CANCEL ZN D5 [10]1011ssssss1234s\ssD5[13] [10]F60416[9]00540102[#1234|NOCD5][13] DD/DD TT:TT L01 ACCT 1234 RESTORE ZN E5 [10]1011ssssss1234sRssE5[13] [10]345816[9]00550102[#1234|NURE5][13] DD/DD TT:TT L01 ACCT 1234 TROUBLE ZN F5 [10]1011ssssss1234sTssF5[13] [10]FB2C16[9]00560102[#1234|NBTF5][13]

Bosch Security Systems | 1/05 | 4998122703D

147

D6600 | Computer Interface Manual | Appendix E: Pulse Output

Table 100: Pulse 4/2 #

Event ALARM

Account Number 1234

Reporting Digit 45

43.

44.

OPENING

1234

B5

45.

CLOSING

1234

C5

46.

CANCEL

1234

D5

47.

RESTORE

1234

E5

48.

TROUBLE

1234

F5

Device/Mode

Displays

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

DD/DD TT:TT L01 ACCT 1234 ALARM_ZN 45 [10]1011ssssss1234sAss45[13] [10]220516[9]00330101[#1234|NBA45][13] DD/DD TT:TT L01 ACCT 1234 OPENING B5 [10]1011ssssss1234sOssB5[13] [10]708D16[9]00340101[#1234|NOPB5][13] DD/DD TT:TT L01 ACCT 1234 CLOSING C5 [10]1011ssssss1234sCssC5[13] [10]DD9A16[9]00350101[#1234|NCLC5][13] DD/DD TT:TT L01 ACCT 1234 CANCEL D5 [10]1011ssssss1234s\ssD5[13] [10]4DC816[9]00360101[#1234|NOCD5][13] DD/DD TT:TT L01 ACCT 1234 RESTORE E5 [10]1011ssssss1234sRssE5[13] [10]8F9416[9]00370101[#1234|NURE5][13] DD/DD TT:TT L01 ACCT 1234 TROUBLE F5 [10]1011ssssss1234sTssF5[13] [10]132316[9]00380101[#1234|NBTF5][13]

Device/Mode

Displays

Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode: Printer: D6500 Mode: SIA Mode:

DD/DD TT:TT L01 ACCT 1234 ALARM_ZN 456 [10]1011ssssss1234sAs456[13] [10]D5C017[9]00390101[#1234|NBA456][13] DD/DD TT:TT L01 ACCT 1234 OPENING B45 [10]1011ssssss1234sOsB45[13] [10]114C17[9]00400101[#1234|NOPB45][13] DD/DD TT:TT L01 ACCT 1234 CLOSING C45 [10]1011ssssss1234sCsC45[13] [10]1FA117[9]00410101[#1234|NCLC45][13] DD/DD TT:TT L01 ACCT 1234 CANCEL D45 [10]1011ssssss1234s\sD45[13] [10]E2B017[9]00420101[#1234|NOCD45][13] DD/DD TT:TT L01 ACCT 1234 RESTORE E45 [10]1011ssssss1234sRsE45[13] [10]DB7217[9]00430101[#1234|NURE45][13] DD/DD TT:TT L01 ACCT 1234 TROUBLE F45 [10]1011ssssss1234sTsF45[13] [10]CC4C17[9]00440101[#1234|NBTF45][13]

Table 101: Pulse 4/3 #

Event ALARM

Account Number 1234

Reporting Digit 456

49.

50.

OPENING

1234

B45

51.

CLOSING

1234

C45

52.

CANCEL

1234

D45

53.

RESTORE

1234

E45

54.

TROUBLE

1234

F45

148

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix F: Format ID (Identified by Message Type) .

Appendix F: Format ID (Identified by Message Type) If Menu Item 2.5.17 equals 1, the following outputs apply. Generic Example

D6500 Byte Description 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21 22

h

9

r

r

l

s

s

s

s

a

a

a

a

C

C

C

C

C

C

C

C

t

Table 102: Generic Byte Description # 1

Title Header Character (h)

Description Optional, check with the computer automation software for compatibility

2

Message Type

9

3-4 5 6-9 10-13 14-21 22

Receiver Number Line/Group Number Spaces Account Number Channels Trailer Character

Receiver gateway number from 01 to 99 Line number in the receiver gateway that sent the message Six spaces Account number, four digits Channels 1 to 8 Typically, this is HEX 14

Generic Example

SIA Mode Description [#aaaa|CCCCCCCC]

Table 103: Generic SIA Byte Description Title L CRC

Description Standard line feed character Cyclical redundancy check number

Message Type

9

sequence#

The message sequence number, the valid sequence number range is 0001 to 9999 The receiver gateway that sent the message, valid digits are 01 to 99 The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal messages. The communicator's account number, four digits. Channel 1 to 8

receiver# line# (Line/Group #) account# CCCCCCCC

The heavier outlined row in Table 102 and Table 103 indicate the meaning of the shaded digit in the D6500 Byte Description, SIA Mode Description Generic Examples, and Table 104 on page 150. Table 104 show examples for each format that the receiver supports. If Menu Item 2.5.17 = 1, the following message type follows a specific format ID. If Menu Item 2.5.17 = 0, the output to automation follows the standard message type ID.

Bosch Security Systems | 1/05 | 4998122703D

149

D6600 | Computer Interface Manual | Appendix F: Format ID (Identified by Message Type)

Table 104: Message Examples #

Communication Format

Mode

Message

1.

Acron Super Fast

2.

Ademco Contact-ID

3.

Ademco 4-1 Express

4.

Ademco 4-2 Express

5.

Ademco High Speed/ Scancom

SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500:

[10]146D18900120101[#123|45678912][13] [10]9011sssss12345678912[14] [10]6A721Ca00140101[#7401|18113003003][13] [10]a011s740118113003003[14] [10]1FDC12b00150101[#1234|7][13] [10]b011ssssss1234sAsss7[14] [10]9D2F13c00160101[#1234|55][13] [10]c011ssssss1234sAss55[14] [10]C3651Cf00180101[#1234|5678s9123s4][13] [10]f011ss1234s5678s9123s4[14]

5-8-1

SIA: D6500:

[10]69311Df00190101[#12345|6789s1234s5][13] [10]f011s12345s6789s1234s5[14]

6-8-1

SIA: D6500:

[10]42CD1Ef00200101[#123456|7891s2345s6][13] [10]f011123456s7891s2345s6[14]

SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D500: SIA: D6500: SIA: D6500: SIA: D6500:

[10]0BB619G00480101[#0308|Nid39OP2][13] [10]G011[#0308|Nid39OP2][14] [10]257B1Ce00570101[#0000|&9569688558][13] [10]e011ssssss9569688558[14] [10]BDAE17i00270101[#123ABC|0108][13] [10]i011ssss123ABC0108ss[14] [10]99EA17d00170101[#1234|NBA567][13] [10]d011ssssss1234sAs567[14] [10]02A215t00400101[#1234|NBA5][13] [10]t011ssssss1234sAsss5[14] [10]40EC16u00410101[#1234|NBA56][13] [10]u011ssssss1234sAss56[14] [10]921C15F00470101[#1234|5678][13] [10]F011ssssss12345678ss[14] [10]5FB90EZ00090124[NLT][13] [10]Z010sssssssssssXss51[14] [10]ABFB19I00490101[#MMTST|g090A31][13] [10]I011sssMvMTSTg090A31[14] [10]2D270B[9]00920100[][13] [10]1010sssssssssss@ssss[14] [10]827316p00340101[#s123|NBA12][13] [10]p011sssssss123sAss12[14]

SIA: D6500: SIA: D6500: SIA: D6500:

[10]16A815p00330101[#s706|NBA1][13] [10]p011sssssss706sAsss1[14] [10]C37A16q00350101[#s706|NBA61][13] [10]q011sssssss706sAss61[14] [10]608F15r00360101[#7066|NBA0][13] [10]r011ssssss7066sAsss0[14]

SIA: D6500: SIA: D6500:

[10]5ACC16r00370101[#1234|NBA12][13] [10]r011ssssss1234sAss12[14] [10]8A7F16s00380101[#7066|NBA02][13] [10]s011ssssss7066sAss02[14]

SIA: D6500: SIA: D6500:

[10]185317s00390101[#1234|NBA566][13] [10]s011ssssss1234sAs566[14] [10]8B9C1AA00440101[#1234|Nti1158LF][13] [10]A011ssssss1234s*ssss[14]

SIA: D6500: SIA: D6500:

[10]942B15B00450101[#1481|NUR2][13] [10]B011ssssss1481sRsss2[14] [10]FFF115C00460101[#s2B2|NBA3][13] [10]C011sssssss2B2sAsss3[14]

4-8-1

6.

ADT SIA

7.

Caller ID

8.

CFSK

9.

DSC/Sur-Gard 4-3

10.

DTMF 4-1

11.

DTMF 4-2

12.

FBI Super Fast

13.

Internal Message

14.

ITI

15.

Link Test

16.

Pulse

3-1 3-1E

17.

Pulse 3-2

18.

Pulse

4-1 4-1E

19.

Pulse

4-2 4-2E

20.

Radionics Modem IIIa2 or Modem IId

21.

Radionics Modem II

22.

Radionics BFSK

150

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix F: Format ID (Identified by Message Type) . Table 104: Message Examples (continued) #

Communication Format

Mode

Message

23.

Robofon

24.

Scancom

SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500: SIA: D6500:

[10]2D3B15j00280101[#123ABC|12][13] [10]j011ssss123ABC12ssss[14] [10]D47C26g00210101[#1234|2222s2222s2222s2222s2][13] [10]g011ss1234s2222s2222s2222s2222s2[14] [10]91FC27g00220101[#12345|2222s2222s2222s2222s2][13] [10]g011s12345s2222s2222s2222s2222s2[14] [10]13EA28g00230101[#123456|2222s2222s2222s2222s2][13] [10]g011123456s2222s2222s2222s2222s2[14] [10]091930h00240101[#1234|2222s2222s2222s2222s2222s2222s2][13] [10]h011ss1234s2222s2222s2222s2222s2222s2222s2[14] [10]D4ED31h00250101[#12345|2222s2222s2222s2222s2222s2222s2][13] [10]h011s12345s2222s2222s2222s2222s2222s2222s2[14] [10]B51132h00260101[#123452|2222s2222s2222s2222s2222s2222s2][13] [10]h011123452s2222s2222s2222s2222s2222s2222s2[14] [10]61F619K00900101[#7080|*#000***][13] [10]K01113*7080*#000***[14] [10]352815k00290101[#123AB|101][13] [10]k011ssssss123ABs1s01[14] [10]787215700110101[#0258|A56s][13] [10]7011ssssss0258sA56ss[14] [10]86E416[9]00500101[#7080|NBA01][13] [10]S011[#7080|NBA01][14] [10]3E6714E01040101[#4444|NOP][13] [10]E011ssssss4444sOssss[13] [10]3E6714E01040101[#4444|NBA13][13] [10]E011ssssss4444sAss08[14] [10]DC7115m00300101[#7654|sA01][13] [10]m011s7654"sA01[14]

SIA: D6500:

[10]8AAC17m00310101[#123456|HA00][13] [10]m011s123456"HA00[14]

SIA: D6500: SIA: D6500:

[10]C2EB26n00320101[#000257|1090000000110000000][13] [10]n011s000257s1s090000000110000000[14] [10]8EFA16v00430101[#1234|NBA98][13] [10]v011ssssss1234sAss98[14]

SIA: D6500: SIA: D6500: SIA: D6500:

[10]802515v00420101[#1234|NBA9][13] [10]v011ssssss1234sAsss9[14] [10]802515V00450101[#55|123456789ABCDEFG][13] [10]V01155123456789ABCDEFG [14] [10]86E416[9]01430101[#1234|6011100*’THISISATEST’12][13] [10]S011[#1234|6011100*’THISISATEST’12][14]

4-16-1 5-16-1 6-16-1

25.

Scancom

4-24-1 5-24-1 6-24-1

26.

Seriee DTMF

27.

Seriee FSK

28.

Sescoa Super Speed

29.

SIA

30.

Silent Knight

FSK 0 FSK80

31.

Silent Knight

FSK1 FSK2

32.

Telim

33.

Varitech FSK 4-1,Varitech FSK 4-2

34.

VONK

35.

X-SIA

VFSK 4-2 VFSK 4-1

Bosch Security Systems | 1/05 | 4998122703D

151

D6600 | Computer Interface Manual | Appendix G: ADT SIA Report Codes

Appendix G: ADT SIA Report Codes Table 105: ADT SIA Report Codes

Description ADT SIA System Event System Reset Reset Memory AC Fail AA AC Restore AH AC Fail 4 hour AT AC Fail 4 hour Restore AJ TELCO Line Trouble LT (Line 1 or Line 2) TELCO Line Trouble LR Restore (Line 1 or Line 2) Low Battery System YT Low Battery Restore YR Change Date Description ADT SIA Expansion Module Interactive Keypad IA Tamper Interactive Keypad IT Trouble – Supervision Interactive Keypad IR Restore Cardreader Alarm DA Cardreader Trouble DT Cardreader Restore DR Point Gateway Tamper EA Alarm Point Gateway Tamper ET – Supervision Point Gateway Restore ER Printer Tamper Alarm PA Printer Trouble – PT Supervision Printer Restore PR Description ADT SIA Downloading DLL Aborted RA Start DLL RB DLL Interrupted RI End DLL Altered RS DLL Comm Fail RT End DLL Not Altered RG

152

Description

ADT SIA

Burglary BA Burg Alarm BA PT Bypass BA Restore BA Trouble BA PT Unbypass

Description

ADT SIA Panic

BA BB BR BT BU

Description Open/Close BA Auto Close BA Auto Close with Bypass – within Group BA Trouble Closing (closed with burg during exit) BA Bypass Closing – within Group BA Closing BA Auto Open BA Irregular Opening BA Opening BA No Close – Sched close time expire BA Exit Fail, exit error (user)

ADT SIA

Description

ADT SIA

CA CB CF

Hold-Up Alarm Hold-Up Point Trouble (sensor trouble) Hold-Up Restore Hold-Up Point Bypass Hold-Up Point Unbypass Hostage Alarm (Duress) Hostage Restore Medical Alarm Medical Restore Description

CG CL OA OI OP OT

HA HT HR HB HU HH HR MA MR ADT SIA

Scheduling BA Change Close Time Change Auto On Level Change Close Time Print Only

EF

Fire Fire Alarm Fire Trouble Fire Restore Fire Alarm Silence Fire Point Bypass Fire Alarm Point Unbypass Supervisory Alarm Supervisory Trouble Supervisory Restore Supervisory Point Bypass Supervisory Unbypass

FA FT FR FB FU SS ST SR SB SU

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix G: ADT SIA Report Codes . Table 105: ADT SIA Report Codes (Continued)

Description Other Supervised Bell Alarm Supervised Bell Trouble Supervised Bell Restore Remote Power Supply Alarm Remote Power Supply Trouble Remote Power Supply Restore Keyswitch Alarm Keyswitch Trouble Keyswitch Restore Janitor Keyswitch Alarm Janitor Keyswitch Trouble Janitor Keyswitch Restore Janitor On Premises (user on premises) Janitor Off Premises (user on premises restore) ADT On Premises ADT Off Premises Tamper Alarm Tamper Restore VVS Bypass VVS Unbypass Keypad Active Audible Walk Test Change Code Change Early Open Change Holiday Change Latest Close (sent to CMC only if Closing sched is altered) Change Open Time, schedule change Change Time, time/date reset

ADT SIA UA UT UR UA UT UR UA UT UR UA UT UR JI JO

SI SO TA TR VB VU AC AT

CL

Description System Test alk Test, walk test mode Bell Test Hold-Up Test Alarm (sent to printer) Hold-Up Test Restore (sent to printer) Start FA Test, fire test End FA Test, fire test restore Start BA Test End BA Test Start Supervision Test End Supervision Test Start Hold-Up Test End Hold-Up Test Long Print Short Print Supervisory Test Print, manual trigger test report Supervisory Test Restore Fire Test Alarm Print, fire test Fire Test Restore Print, fire test restore BA Point Test Print BA Point Test Restore Print Hold-Up Suspicion Print Keypad No Access Untyped Bypass Untyped Unbypass Tamper Bypass Tamper Unbypass BA Diagnostics FA Diagnostics Output Trouble Output Restore Point Trouble Point Alarm, general alarm

Bosch Security Systems | 1/05 | 4998122703D

ADT SIA WT BT

FM FK BN BK SM SK HM HK

ST

ST FA FR BT BT

Description Point Restore, general alarm restore Untyped Diagnostics BA Weak Battery FA Weak Battery HA Weak Battery SA Weak Battery UA Weak Battery

ADT SIA UR

Description

ADT SIA

Access 2 Man 2nd Person Keypad Lockout Cardreader Irregular Access Manual PB Access, remote arm/disarm opening Access Denied Code Known, access denied Access Denied Code Unknown, access denied

UW BL FL HL SL UL

DI MP

DK DD

Description ADT SIA Dialer Test Report Dialer Test Report RP1 Dialer Test Report with RP5 System Trouble

HS NA UB UU TB TU BW FW UT UR UT UA

153

D6600 | Computer Interface Manual | Appendix H: D6600 RB2000 Messages

Appendix H: D6600 RB2000 Messages For lines that are grouped, Gxx appears instead of Lxx.

Table 106: D6600 RB2000 Messages #

Event

1.

Mains Power Failure

2.

3.

Device/ Mode SIA Printer SIA Printer

Mains Power Return

4.

SIA Printer SIA Printer

5.

Battery Broken

SIA Printer

6.

RF Y Battery Empty

SIA Printer

7.

RF Y Battery Full

SIA Printer

8.

HTS Battery Empty

SIA Printer

9.

HTS Battery Full

SIA Printer

10.

Sensor Battery

SIA Printer

11.

SIA Printer

12.

Technical Alarm

SIA Printer

13.

Technical Alarm Confirmed

SIA Printer

154

Display [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 32 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 34 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 B2 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 B4 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 33 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY 33 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 B7 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 37 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 B7 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 38 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 B8 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 41 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 C1

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix H: D6600 RB2000 Messages . Table 106: D6600 RB2000 Messages (continued) #

Event

14.

PRO 100 Transmitter

15.

16.

SIA Printer PRO 100 Pull Cord

17.

18.

PRO 100 Situation Alarm

Pull Switch

Confirmation at Local Unit

Hand Transmitter/Button

29.

SIA Printer SIA Printer

Emergency Button

27.

28.

SIA Printer SIA Printer

25.

26.

SIA Printer SIA Printer

23.

24.

SIA Printer SIA Printer

21.

22.

SIA Printer SIA Printer

19.

20.

Device/ Mode SIA Printer

SIA Printer SIA Printer

External Input X

SIA Printer SIA Printer

Display [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 42 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 C2 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 43 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 C3 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 44 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 C4 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 46 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 C6 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 47 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 C7 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 48 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 C8 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 49 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 C9 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 01 XX 49 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 01 XX C9

Bosch Security Systems | 1/05 | 4998122703D

155

D6600 | Computer Interface Manual | Appendix H: D6600 RB2000 Messages

Table 106: D6600 RB2000 Messages (continued) #

Event

30.

RF Y - Alarm

31.

32.

SIA Printer Activity Monitor

33.

34.

Device/ Mode SIA Printer

SIA Printer SIA Printer

Fire Alarm

35.

SIA Printer SIA Printer

36.

Fire Alarm from Ext Input X

SIA Printer

37.

Intrusion

SIA Printer

38.

SIA Printer

39.

Intrusion from Ext Input X

SIA Printer

40.

Intrusion from RF X

SIA Printer

41.

External Alarm Button

SIA Printer

42.

43.

SIA Printer Protocol Error

44.

45.

46.

156

SIA Printer SIA Printer

RF Y Error

SIA Printer SIA Printer

Display [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY 49 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY C9 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 4A [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 CA [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 4B [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 CB [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 01 XX 4B [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 4C [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 CC [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 01 XX 4C [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 01 XX 4C [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 4D [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 CD [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 4E [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 CE [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY 51 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY D1

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix H: D6600 RB2000 Messages . Table 106: D6600 RB2000 Messages (continued) #

Event

47.

RF Y Maintenance

48.

49.

SIA Printer RF Y Start

50.

51.

RF Y Disassembly

RF Y Test OK

RF Y Test NOK

SIA Printer SIA Printer

RF Y Plug

58.

59.

SIA Printer SIA Printer

56.

57.

SIA Printer SIA Printer

54.

55.

SIA Printer SIA Printer

52.

53.

Device/ Mode SIA Printer

SIA Printer SIA Printer

RF Y Test

60.

SIA Printer SIA Printer

61.

Outgoing Call HNZ

SIA Printer

62.

Resetting

SIA Printer

63.

Personal Sign In

SIA Printer

Display [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY 52 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY D2 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY 53 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY D3 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY 54 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY D4 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY 55 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY D5 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY 56 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY D6 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY 57 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY D7 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY 58 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY D8 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 60 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 61 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx+++ 0E 00 00 00 62

Bosch Security Systems | 1/05 | 4998122703D

157

D6600 | Computer Interface Manual | Appendix H: D6600 RB2000 Messages

Table 106: D6600 RB2000 Messages (continued) #

Event

64.

Personal Sign Out

65.

Door Alarm

SIA Printer

66.

Bed Alarm

SIA Printer

67.

Medical Remind

SIA Printer

68.

Message 1

SIA Printer

69.

Message 2

SIA Printer

70.

Message 3

SIA Printer

71.

Sign Out

SIA Printer

72.

73.

SIA Printer Sign In

74.

75.

Device/ Mode SIA Printer

SIA Printer SIA Printer

Service Call

76.

SIA Printer SIA Printer

77.

Repeated Call

SIA Printer

78.

Confirmation Call

SIA Printer

79.

Pager Call Activated

SIA Printer

80.

Full Duplex Communication

SIA Printer

158

Display [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 63 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 64 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 65 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 66 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 67 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 68 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 69 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 71 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 78 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 F1 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 F8 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 72 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 F2 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 73 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 F3 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 74 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 75

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix H: D6600 RB2000 Messages . Table 106: D6600 RB2000 Messages (continued) #

Event

81.

Test Call

82.

83.

SIA Printer RF Jamming

84.

85.

RF Y No Alive

Call for Assistance

SIA Printer SIA Printer

Registration Call

90.

91.

SIA Printer SIA Printer

88.

89.

SIA Printer SIA Printer

86.

87.

Device/ Mode SIA Printer

SIA Printer SIA Printer

Manual Test Call

92.

SIA Printer SIA Printer

93.

Release Code XX XX

SIA Printer

94.

Error Message HNZ2001

SIA Printer

95.

Error Ended HNZ2001

SIA Printer

96.

Status: Mains Power Failure

SIA Printer

97.

Status: Battery Broken

SIA Printer

Display [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 79 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 F9 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 7A [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 FA [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY 7B [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 02 XY FB [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 7C [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 FC [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 7D [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 FD [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 7E [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 00 00 FE [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 00 XX XX FF [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 01 YY XX 42 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 0E 01 YY XX C2 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ A2 00 00 00 32 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ A2 00 00 00 33

Bosch Security Systems | 1/05 | 4998122703D

159

D6600 | Computer Interface Manual | Appendix H: D6600 RB2000 Messages

Table 106: D6600 RB2000 Messages (continued) #

Event

98.

Status: Battery Empty

99.

Status: Signed Out

100. Remote Programming Request

160

Device/ Mode SIA Printer SIA Printer SIA Printer

Display [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ A2 00 00 00 37 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ A2 00 00 00 71 [] MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx +++ 10 00 xx yy 70

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix I: D6600 SafeCom Messages .

Appendix I: D6600 SafeCom Messages For lines that are grouped, Gxx appears instead of Lxx. In D6500 Mode, the line number or group number sent to the computer is only one digit. Refer to Table 107. Figure 23: SafeCom message characters

2 1

4 3

5

6

7

hprr100000100t 1 - Header 2 - SafeCom

3 - D6600 receiver number (01 to 99) 4 - Line card number or virtual line

5 - Account or virtual account 6 - SafeCom signal 7 - Trailer

If Virtual Line is 00, it is disabled. The D6600 reports the actual D6600 line card number. Table 107: D6600 Virtual Line Conversion Table Line# 01 02 03 04 05 06 07 08 09

Converted to 1 2 3 4 5 6 7 8 9

Line# 0A 0B 0C 0D OE 0F 10 11 12

Converted to A B C D E F G H I

Line # 13 14 15 16 17 18 19 1A 1B

Converted to J K L M N O P Q R

Line # 1C 1D 1E 1F 20 21 22 23 FF

Converted to S T U V W X Y Y Y

Any group greater than or equal to 22 is converted to a “Y.” For lines that are grouped, Gxx appears instead of Lxx. For networked accounts, Nxx appears instead of Lxx and the line number is identified.

Bosch Security Systems | 1/05 | 4998122703D

161

D6600 | Computer Interface Manual | Appendix I: D6600 SafeCom Messages

Table 108: D6600 SafeCom Messages - Line Card or Account Signals

#

Event

Device/ Mode

Display

1.

System Startup

6500/SIA

1

2

Printer 2.

3.

4.

5.

Radio Restart

Battery Trouble

Battery Restoral

Aux. Fault

6500/SIA

hprrl0aaa0100t [#0aaa|0100]

Printer2

dd/dd tt:tt Sxx aaa>restart 1

6500/SIA

hprrl0aaa0103t [#0aaa|0103]

Printer2

dd/dd tt:tt Sxx aaa>BATTERY TROUBLE 1

6500/SIA

hprrl0aaa0104t [#0aaa|0104]

Printer2

dd/dd tt:tt Sxx aaa battery restore

6500/SIA1

hprrl0aaa0103t [#0aaa|0103]

2

7.

Aux. Restoral

AC Trouble

6500/SIA

hprrl0aaa0104t [#0aaa|0104]

Printer2

dd/dd tt:tt Sxx aaa aux restore 1

6500/SIA 2

9.

10.

11.

12.

AC Restoral

External Power Fail

External Power Restoral

Remote Com Restore

RF Trouble

Only valid for DP1000, PID-FE10

dd/dd tt:tt Sxx aaa>AUX FAULT 1

Printer 8.

hprrl00000100t [#0000|0100] dd/dd tt:tt Sxx SYSTEM STARTUP

1

Printer 6.

Notes on Auto Output

Only valid for DP1000, PID-FE10

hprrl0aaa0105t [#0aaa|0105] dd/dd tt:tt Sxx aaa>AC TROUBLE

1

6500/SIA

hprrl0aaa0106t [#0aaa|0106]

Printer2

dd/dd tt:tt Sxx aaa ac restore

6500/SIA1

hprrl0aaa0105t [#0aaa|0105]

Printer2

dd/dd tt:tt Sxx aaa>POWER TROUBLE

6500/SIA1

hprrl0aaa0106t [#0aaa|0106]

Printer2

dd/dd tt:tt Sxx aaa power restore 1

6500/SIA

hprrl0aaa0110t [#0aaa|0110]

Printer2

dd/dd tt:tt Sxx aaa>REMOTE COM RESTORE

6500/SIA1

hprrl0aaa0111t [#0aaa|0111]

Printer2

dd/dd tt:tt Sxx aaa>RF TROUBLE

SC3100 PID-0330 or 0340, SC2104 PID-0430 or 0440 SC3100 PID-0330 or 0340, SC2104 PID-0430 or 0440 This indicates that the radio could not report a previous message (until just now).

1 - Refer to Table 110: Explanation of Automation Output Items (within Message Body only) on page 167 2 - Refer to Table 111: Explanation of Printer Output Items on page 168

162

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix I: D6600 SafeCom Messages . Table 108: D6600 SafeCom Messages - Line Card or Account Signals (continued)

#

Event

Device/ Mode

Display

13.

RF Restore

6500/SIA1

hprrl0aaa0112t [#0aaa|0112]

Printer2

dd/dd tt:tt Sxx aaa rf restore

14.

System RF Channel Busy

1

6500/SIA 2

Printer 15.

16.

System RF Channel Clear Channel Busy

Channel Clear

6500/SIA

hprrl00000112t [#0000|0112]

Printer2

dd/dd tt:tt Sxx CHn channel clear 1

6500/SIA

dd/dd tt:tt Sxx aaa>CHANNEL BUSY

6500/SIA1

hprrl0aaa0122t [#0aaa|0122]

2

Dialer Error

hprrl0aaa0121t [#0aaa|0121]

Printer

Printer 18.

hprrl00000111t [#0000|0111] dd/dd tt:tt Sxx CHn>CHANNEL BUSY

1

2

17.

Notes on Auto Output

dd/dd tt:tt Sxx aaa channel clear 1

6500/SIA

hprrl0aaa022000t [#0aaa|022000]

Printer2

dd/dd tt:tt Sxx aaa>DIALER ERROR e

“e” is error code. See below for details: 0 - unknown error 1 - dialing error 2 - handshake error 3 - noise error 19.

20.

Tamper Fault

Tamper Restore

1

6500/SIA

hprrl0aaa03200301t [#0aaa|03200301]

Printer2

dd/dd tt:tt Sxx aaa>TAMPER FAULT 1

6500/SIA 2

Printer 21.

22.

23.

24.

25.

Phone Line Fail

Phone Line Restore

Aux. Power Fail

Aux. Power Restore

Fire Panic

4 - unexpected disconnect 5 - validation error 6 - priority error

Dialer error is reported to automation in a format similar to 3-1 event.

hprrl0aaa03200101t [#0aaa|03200101] dd/dd tt:tt Sxx aaa tamper restore

1

6500/SIA

hprrl0aaa03200301t [#0aaa|03200301]

Printer2

dd/dd tt:tt Sxx aaa>TELCO TROUBLE

6500/SIA1

hprrl0aaa03200101t [#0aaa|03200101]

Printer2

dd/dd tt:tt Sxx aaa telco restore 1

6500/SIA

hprrl0aaa03200301t [#0aaa|03200301]

Printer2

dd/dd tt:tt Sxx aaa>AUX POWER TROUBLE 1

6500/SIA

hprrl0aaa03200101t [#0aaa|03200101]

Printer2

dd/dd tt:tt Sxx aaa aux power restore 1

6500/SIA

hprrl0aaa03200302t [#0aaa|03200302]

Printer2

dd/dd tt:tt Sxx aaa>FIRE PANIC

Only valid for SC2104 Only valid for SC2104 Only valid for SC5000 Only valid for SC5000 Only valid for SC5000

1 - Refer to Table 110: Explanation of Automation Output Items (within Message Body only) on page 167 2 - Refer to Table 111: Explanation of Printer Output Items on page 168

Bosch Security Systems | 1/05 | 4998122703D

163

D6600 | Computer Interface Manual | Appendix I: D6600 SafeCom Messages

Table 108: D6600 SafeCom Messages - Line Card or Account Signals (continued)

#

Event

Device/ Mode

26.

Burglary Panic

6500/SIA

1

2

27.

28.

29.

30.

Silent/Medical Panic

Operator Evacuation Bell Input Normal

Input Open

Input Bypass

hprrl0aaa03200304t [#0aaa|03200304]

Printer2

dd/dd tt:tt Sxx aaa>SILENT/MEDICAL PANIC 1

6500/SIA

hprrl0aaa03200305t [#0aaa|03200305]

Printer2

dd/dd tt:tt Sxx aaa>OPERATOR EVACUATION 1

6500/SIA

hprrl0aaa0320011it [#0aaa|0320011i]

Printer2

dd/dd tt:tt Sxx aaa normal: input i 1

6500/SIA

6500/SIA

34.

Zone Restore

dd/dd tt:tt Sxx aaa>SHORTED: input i hprrl0aaa0320041it [#0aaa|0320041i] dd/dd tt:tt Sxx aaa bypass: input i 1

6500/SIA

hprrl0aaa0320051it [#0aaa|0320051i]

Printer2

dd/dd tt:tt Sxx aaa unbypass: input i 1

6500/SIA 2

36.

37.

38.

39.

Zone Trouble

Fire Alarm

Silent Alarm

Burglary Alarm

Zone Bypass

hprrl0aaa0320031it [#0aaa|0320031i]

6500/SIA1

Printer 35.

Only valid for SC5000

hprrl0aaa0320021it [#0aaa|0320021i]

Printer

2

Input Unbypass

Only valid for SC5000

dd/dd tt:tt Sxx aaa>OPENED: input i 1

Printer 33.

Only valid for SC5000

dd/dd tt:tt Sxx aaa>BURGLARY PANIC

2

32.

hprrl0aaa03200303t [#0aaa|03200303]

6500/SIA1

2

Input Short

Notes on Auto Output

Printer

Printer 31.

Display

hprrl0aaa0320011zt [#0aaa|0320011z]

Only valid for SC5000

dd/dd tt:tt Sxx aaa restore: zone z 1

6500/SIA

hprrl0aaa0320021zt [#0aaa|0320021z]

Printer2

dd/dd tt:tt Sxx aaa>TROUBLE: zone z

6500/SIA1

hprrl0aaa0320031zt [#0aaa|0320031z]

Printer2

dd/dd tt:tt Sxx aaa>FIRE: zone z

6500/SIA1

hprrl0aaa0320031zt [#0aaa|0320031z]

Printer2

dd/dd tt:tt Sxx aaa>SILENT: zone z

6500/SIA1

hprrl0aaa0320031zt [#0aaa|0320031z]

Printer2

dd/dd tt:tt Sxx aaa>BURGLARY: zone z

6500/SIA1

hprrl0aaa0320041zt [#0aaa|0320041z]

Printer2

dd/dd tt:tt Sxx aaa BYPASS: zone z

Only valid for SC5000 Only valid for SC5000, depending on the zone type Only valid for SC5000, depending on the zone type Only valid for SC5000, depending on the zone type Only valid for SC5000

1 - Refer to Table 110: Explanation of Automation Output Items (within Message Body only) on page 167 2 - Refer to Table 111: Explanation of Printer Output Items on page 168

164

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix I: D6600 SafeCom Messages . Table 108: D6600 SafeCom Messages - Line Card or Account Signals (continued)

#

Event

Device/ Mode

40.

Zone Unbypass

6500/SIA

1

2

41.

42.

Operator Armed

User Armed

44.

45.

User Disarmed

User Duress

hprrl0aaa03200600t [#0aaa|03200600]

Printer2

dd/dd tt:tt Sxx aaa OPERATOR ARMED 1

hprrl0aaa0320060ut [#0aaa|0320060u]

6500/SIA

47.

User Cancel

Only valid for SC5000 Only valid for SC5000

dd/dd tt:tt Sxx aaa ARMED: user u 1

6500/SIA

hprrl0aaa03200700t [#0aaa|03200700]

Printer2

dd/dd tt:tt Sxx aaa>OPERATOR DISARMED 1

6500/SIA

hprrl0aaa0320070ut [#0aaa|0320070u]

Printer2

dd/dd tt:tt Sxx aaa>DISARMED: user u 1

hprrl0aaa0320080ut [#0aaa|0320080u]

6500/SIA 2

Operator Cancel

Only valid for SC5000

dd/dd tt:tt Sxx aaa unbypass: zone z

Printer 46.

hprrl0aaa0320051zt [#0aaa|0320051z]

6500/SIA1

2

Operator Disarmed

Notes on Auto Output

Printer

Printer 43.

Display

Only valid for SC5000 Only valid for SC5000 Only valid for SC5000

dd/dd tt:tt Sxx aaa>DURESS: user u 1

6500/SIA

hprrl0aaa03200900t [#0aaa|03200900]

Printer2

dd/dd tt:tt Sxx aaa OPERATOR CANCEL 1

hprrl0aaa0320090ut [#0aaa|0320090u]

6500/SIA 2

Printer

Only valid for SC5000 Only valid for SC5000

dd/dd tt:tt Sxx aaa CANCEL: user u

1 - Refer to Table 110: Explanation of Automation Output Items (within Message Body only) on page 167 2 - Refer to Table 111: Explanation of Printer Output Items on page 168 Table 109: D6600 SafeCom Messages - Intercepted Control Panel Signals

#

Event

Device/ Mode

Display

48.

3-1 Unexpanded

6500/SIA1

hprrlaaaa0220e0t [#aaaa|0220e0]

Printer2

dd/dd tt:tt Sxx aaa>(aaaa) e XXXXXXXX

49.

50.

51.

3-1 Expanded, 4-2, BFSK, or Ademco 42 Express FBI SuperFast

Ademco 4-9 High Speed

1

6500/SIA

hprrlaaaa0220ezt [#aaaa|0220ez]

Printer2

dd/dd tt:tt Sxx aaa>(aaaa) ez XXXXXXXX 1

6500/SIA

hprrlaaaa0321ezzet [#aaaa|0321ezze]

Printer2

dd/dd tt:tt Sxx aaa>(aaaa) ee zzz >>>>>>>>>>>>>>> aaa>XXXXXXXX

6500/SIA1

hprrlaaaa0620eeeeeeeet0t [#aaaa|0620eeeeeeeet0]

2

Printer

Notes on Auto Output

dd/dd tt:tt Sxx aaa>(aaaa) eeee eeee t

1 - Refer to Table 110: Explanation of Automation Output Items (within Message Body only) on page 167 2 - Refer to Table 111: Explanation of Printer Output Items on page 168

Bosch Security Systems | 1/05 | 4998122703D

165

D6600 | Computer Interface Manual | Appendix I: D6600 SafeCom Messages

Table 109: D6600 SafeCom Messages - Intercepted Control Panel Signals (continued) #

Event

52.

Ademco Contact ID

Device/ Mode 1 6500/SIA Printer2

53.

54.

1

SIA DCS

6500/SIA

Modem II - PID 0x50

Printer2 1 6500/SIA Printer2

55.

56.

57.

58.

59.

Modem II - PID 0x72, Unexpanded, without Status Report

6500/SIA1

Modem II - PID 0x72, Unexpanded, with Status Report

6500/SIA1

Modem II - PID 0x72, Expanded, without Status Report

6500/SIA

Modem II - PID 0x72, Expanded, with Status Report

6500/SIA1

Modem II - PID 0xBB

6500/SIA1, 3

Printer2

2

Printer

1

Printer2

Printer2

2

Printer 60.

Modem IIe/IIIa2

6500/SIA1, 3 Printer2

61.

Modem IIe/IIIa2 with 4-Digit Zone

6500/SIA1, 3 2

Printer

Display

Notes on Auto Output

hprrlaaaa072018qeeeggccc0t [#aaaa|072018qeeeggccc0] dd/dd tt:tt Sxx aaa>(aaaa) qeee gg czzz >>>>>>>>>>>>>>> aaa>qeeeTTTTTTTTXXXXXXXX hprrlaaaa0f20ffeeeezzzzzz0000000000000000t [#aaaa|0f20ffeeeezzzzzz0000000000000000] dd/dd tt:tt Sxx aaa>(aaaa) feezzz hprrlaaaa03231ezzt [#aaaa|03231ezz] dd/dd tt:tt Sxx aaa>(aaaa) ezz >>>>>>>>>>>>>>> aaa>XXXXXXXX hprrlaaaa0322ez00t [#aaaa|0322ez00] dd/dd tt:tt Sxx aaa>(aaaa) e z00 >>>>>>>>>>>>>>> aaa>XXXXXXXX hprrlaaaa0322ez00t [#aaaa|0322ez00] dd/dd tt:tt Sxx aaa>(aaaa) e z00 >>>>>>>>>>>>>>> aaa>STATUS:XXXXXXXX hprrlaaaa0322ezzzt [#aaaa|0322ezxx] dd/dd tt:tt Sxx aaa>(aaaa) e zzz >>>>>>>>>>>>>>> aaa>XXXXXXXX hprrlaaaa0322ezzzt [#aaaa|0322ezzz] dd/dd tt:tt Sxx aaa>(aaaa) e zxx >>>>>>>>>>>>>>> aaa>STATUS:XXXXXXXX hprrlaaaa0621aaeezzz000t [#aaaa|0621aaeezzz000] dd/dd tt:tt Sxx aaa>(aaaa) aa ee zzz >>>>>>>>>>>>>>> aaa>XXXXXXXX hprrlaaaa0621aaeezzz000t [#aaaa|0621aaeezzz000] dd/dd tt:tt Sxx aaa>(aaaa) aa ee zzz >>>>>>>>>>>>>>> aaa>XXXXXXXX hprrlaaaa0622aaeezzzz00t [#aaaa|0622aaeezzzz00] dd/dd tt:tt Sxx aaa>(aaaa) aa ee zzzz >>>>>>>>>>>>>>> aaa>XXXXXXXX

1 - Refer to Table 110: Explanation of Automation Output Items (within Message Body only) on page 167 2 - Refer to Table 111: Explanation of Printer Output Items on page 168 3 - Refer to Table 112: Supported Event Codes on page 169

166

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix I: D6600 SafeCom Messages . Table 110: Explanation of Automation Output Items (within Message Body only) Character aaa i z u aaaa e ee eee eeee eeeeeeee t z zz zzz zzzz zzzzzz gg ff aa q ccc

Meaning Radio account number (in hex), range: 001 to 9C4 Input number, range: 1 to 8 Zone number, range: 1 to 8 User number, range: 1 to 8 Control panel account number Event code Event codes for Zone 1 thru 8 (Ademco 4-9 High Speed only) Type code

Zone (or contact) code

Group number Function code Area code Event qualifier (1: new event or opening, 3: restoral or closing, 6: previous message) (Ademco Contact ID only) Hex contact or user code

Bosch Security Systems | 1/05 | 4998122703D

167

D6600 | Computer Interface Manual | Appendix I: D6600 SafeCom Messages

Table 111: Explanation of Printer Output Items Character dd/dd tt:tt S xx n aaa > e i z u (aaaa) e ee eee eeee eeee t z zz zzz gg f aa XXXXXXXX TTTTTTTT q

168

Meaning Month and day (MM/DD) Time of message receipt (HH:MM) SafeCom Line card number, range: 01 to 08 Radio channel number, range: 1 to 8 Radio account number (in hex), range: 001 to 9C4 If exists, the signal is in high priority Error code (for dialer error signals only), range: 0 to 6 Input number, range: 1 to 8 Zone number, range: 1 to 8 User number, range: 1 to 8 Control panel account number Event code Event codes for Zone 1 thru 8 (Ademco 4-9 High Speed only) Type code Zone (or contact) code Group number Function code Area code Translation text embedded (only when valid digital XLAT is selected for the radio account) Event type can be NEW, RESTORE, or PRIOR (Ademco Contact ID only) Event qualifier (1: new event or opening, 3: restoral or closing, 6: previous message) (Ademco Contact ID only)

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix I: D6600 SafeCom Messages . Modem IIe Format DD/MM HH:MM:SS NNN > (DDDD) AA EE ZZZ Modem IIe messages are reported as AA EE ZZZ where AA is the area code, EE is the event code from Table 112, and ZZZ is the zone or user code. For example: 01 EF 009 = area 1, alarm zone 9. Table 112: Supported Event Codes Code FE FD FC FB FA F9 F8 F7 F6 F5 F4 F3 F2 F1 F0 EF EE ED EC EB EA E9 E8 E7 E6 E5 E4 E3 E2 E1 E0 DF DE DD DC DB DA D9 D8 D7 D6 D5

Meaning Listen in Fail to call RAM Access granted Duress user ZZZ User ZZZ alarm 7 User ZZZ alarm 9 Point ZZZ bypass Point ZZZ forced bypass Status = alarm ZZZ Status = trouble ZZZ Fire alarm ZZZ Fire trouble ZZZ Missing fire ZZZ Fire restore ZZZ Fire trouble restore ZZZ Alarm ZZZ Trouble ZZZ Restore ZZZ Missing alarm ZZZ Missing trouble ZZZ Point ZZZ open Point ZZZ close Extra point ZZZ Point bus trouble All points tested Restoral from alarm Fire cancel User code added Service start Service end Sensor ZZZ reset Relay ZZZ set Relay ZZZ reset Panel was forced armed Cerate status report Fire walk start by user ZZZ Fire walk end Walk test start by user ZZZ Walk test end Fail to open Fail to close Area watch by user ZZZ

Bosch Security Systems | 1/05 | 4998122703D

Code D4 D3 D2 D1 D0 CF CE CD CC CB CA C9 C8 C7 C6 C5 C4 C3 C2 C1 C0 BF BE BD BC BB BA B9 B8 B7 B6 B5 B4 B3 B2 B1 B0 AF AE AD AC AB

Meaning Walk test point Extend close time by user ZZZ Cancel by user ZZZ Status = open Open by user ZZZ Force close by user ZZZ Status = closed Close by user ZZZ Test report Log at threshold Log overflow Parameter change User code tamper by user ZZZ User code for user ZZZ added or changed Sked ZZZ execute Sked ZZZ changed Date changed by user ZZZ Time changed by user ZZZ User level set by user ZZZ Valid programmer access by SDI device ZZZ Invalid programmer access by SDI device ZZZ Valid RAM access on phone ZZZ Invalid RAM access on phone ZZZ Comm fail phone ZZZ Comm restore phone ZZZ Phone line ZZZ fail Phone line ZZZ restore SDI device ZZZ trouble SDI device ZZZ restore Panel AC fail Panel AC restore Panel battery missing Panel battery low Panel battery restore Panel watchdog activated Supervision (non-fire) ZZZ Remote reset ROM checksum failure Memory failure Reboot Parameter checksum failure Force perimeter instant by user ZZZ

169

D6600 | Computer Interface Manual | Appendix I: D6600 SafeCom Messages

Table 112: Supported Event Codes Code AA A9 A8 A7 A6 A5 A4 A2 A1 A0 9F 9A 99 98 95 94 92 91 90 8F 8E 8D 8C 8B 8A 89 88 87 86 85 84 83 82 81 7F 7E 7D 7C

170

Meaning Force perimeter delay by user ZZZ Status = perimeter instant Status = perimeter delayed Perimeter instant by user ZZZ Perimeter delayed by user ZZZ Passcode for user ZZZ deleted Point bus restore Transmitter point ZZZ battery low Transmitter point ZZZ battery restore Transmitter point ZZZ tamper restore RF receiver trouble by SDI device ZZZ Extra RF point ZZZ RF receiver restore by SDI device ZZZ RF interference by SDI device ZZZ Transmitter point ZZZ tamper alarm Transmitter point ZZZ tamper trouble Equipment restoral by SDI device ZZZ Card assigned by user ZZZ Card deleted by user ZZZ Door cycled point ZZZ Door unlocked point ZZZ Door locked point ZZZ No entry point ZZZ Door left open point ZZZ Door request point ZZZ Network failure path ZZZ Network restoral path ZZZ Network condition path ZZZ Equipment fail by SDI device ZZZ Status supervision point ZZZ Fire Supervision Restoral point ZZZ Fire supervision point ZZZ Fire Supervision Trouble point ZZZ Fire Supervision Trouble Restoral point ZZZ Status fire supervision point ZZZ Extra account path ZZZ Low signal strength path ZZZ RF receiver tamper by SDI device ZZZ

Code 7B 7A 79 78 77 76 75 74 73 72 71 70 6F 6E 6D 6C 6B 6A 69 68 5F 5E 5D 5C 5B 5A 59 58 56 55 54 53 52 51 50 4F 4E

Meaning RF receiver tamper restoral by SDI device ZZZ Status fire alarm point ZZZ Status fire trouble point ZZZ RF interference restoral by SDI device ZZZ Status RF trans low battery point ZZZ Status RF trans tamper alarm point ZZZ Status RF trans tamper trouble point ZZZ Sensor Trouble point ZZZ Sensor Trouble Restoral point ZZZ Status fire missing point ZZZ Status missing alarm point ZZZ Status missing trouble point ZZZ Status door forced point ZZZ Door locked point ZZZ Missing fire supervision point ZZZ Missing supervision point ZZZ Status missing fire supervision point ZZZ Status missing supervision point ZZZ Status door left open point ZZZ Failed to execute point ZZZ Analog service point ZZZ Analog restoral point ZZZ Status analog service point ZZZ Test Failed path ZZZ External device ZZZ Custom Function ZZZ Executed Low Temperature point ZZZ Low Temperature Restoral point ZZZ Unverified Event point ZZZ Printer Status by SDI device ZZZ Abort by user ZZZ Service Request Output ZZZ State Output ZZZ State Restoral Bypass Restoral point ZZZ Alarm Silenced point ZZZ Alarm-Panel Substitution path ZZZ

Bosch Security Systems | 1/05 | 4998122703D

D6600 | Computer Interface Manual | Appendix I: D6600 SafeCom Messages .

Bosch Security Systems | 1/05 | 4998122703D

171

Bosch Security Systems 130 Perinton Parkway Fairport, NY 14450-9199 Customer Service: (800) 289-0096 Technical Support: (888) 886-6189

© 2005 Bosch Security Systems 4998122703D