Floor Standing (50Hz, R410A)
5CSP0-02A(Replaces:5CSP0-01A)
5CSP0-02A
General Description Thank you very much for your special patronage of LG air conditioners. Keeping pace with developments in global environment policies, the company has developed a new refrigerant (R-410a) to replace Freon gas (R22), ahead of it being banned due to its environmentally - damaging greenhouse effects. This is our environment-friendly policy protecting the environment for the future. LG’s "Floor Standing" is the indoor unit which is used as luxury domestic or commercial appliance and is used in the places like restaurant, store or meeting room. This unit has good design and is equipped with many special features. It comes in different color to suits the interior design and maintains the harmony of the room.Installation of floor standing unit is easy and it has very low operating noise.Apart from that it has very special features such as child lock, neuro fuzzy control logic, dual plasma filter. In installation field we can use this unit as the duct system also which makes it more dynamic and diversified than other units. It has wide capacity range from 28~72kBtu/h. A lot of information regarding the design and installation of this system is provided in this publication. This new products series contains data on the same pattern. Please utilize all the information for conducting your business efficiently. Make sure the specification, dimension or others technical data are same as provided in enginering data book before you start the project. We look forward to your continuing support.
LG Electronics Inc. Air-Conditioning Company
Floor Standing
1
2
Floor Standing
Floor Standing(50Hz, R410A) Contens 1. Models List ................................................................................4 2. Model Number Nomenclature .................................................5 3. Feature and Benefits ................................................................6 4. List of Functions .......................................................................9 5. Specifications .........................................................................10 6. Dimensional Drawings ..........................................................11 7. Wiring Diagrams .....................................................................15 8. Refrigerant Cycle Diagrams .................................................17 9. Selection Procedure ..............................................................18 10. Performance Data ..................................................................19 11. The Coefficient of Capacity Change ..................................23 12. Operation Range ...................................................................24 13. Sound Levels.......................................................................25 14. Installation ..............................................................................26 15. Function of Remote Control ................................................34
Floor Standing
3
Models List
5CSP0-02A
1. Models List 1.1 Heat Pump Nominal Capacity
4
kW
Btu/h
8.2
28k
14.1
48k
21.1
72k
Model Refrigerant
Power Supply Model Name AP-Z286RC0[P03AH SR0]
R410A
AP-Z488TC0[P05AH ST0] AP-Z728FA1[P08AH SF1]
Floor Standing
V-PH-Hz 220-240V, 1Ø, 50Hz 380-415V, 3Ø, 50Hz
5CSP0-02A
Model Number Nomenclature
2. Model Number Nomenclature • Global Model Number A P
- Z 2 8 6 R C 0
Development Sequence
Function A : Basic
C : Plasma Air Purifier
Chassis Type Electric Standard (Volts / Freq. / Phase) 6 : 220V-240V, 50Hz, 1Ø 8 : 380V-415V, 50Hz, 3Ø
Nominal Cooling Capacity Ex) 28 → 27,800 Btu/h 72 → 72,000 Btu/h
48 → 46,000 Btu/h
Model Type Z : Heat Pump+Electric Heater
Type of Air Conditioner AP : R410A Floor Standing Type Air Conditioner
Floor Standing
5
Features and Benefits
5CSP0-02A
3. Features and Benefits Plasma Air Purifying System : Dust Reduction Respirable particles from 5 cigarettes in a sealed room removed by LG Plasma Air Purifying System (%) 100
Natural
80
The PLASMA Air Purifying System within the air conditioner removes microscopic contaminants and dust to eliminate offensive odors and prevent allergic reactions.It can also be used as an air-purifying unit even though the air-cooling function is off.
60 40
Plasma
20 0
15
30
45
60(Min)
Deodorization LG's Plasma unit effectively removes high concentration tobacco odors confirmed in Sensory tests of odor index carried out in Korea and Japan. (%) 100
Natural
80 60 40
Plasma
20 0
10
20
30(Min)
Anti-Allergy In clinical tests,the plasma unit has earned a satisfaction ratio of 82%. Air Purifying Filter captures particles as small as 0.1 micron 0.1 Visible with an electron microscope
1
Visible with an optical microscope
10
100 (micron) Visible with the naked eye
Soot Cigarette smoke particles Insecticide particles Mould Viruses spores Bacteria Pollen Dust harmful to lungs
Dust electrode discharge Dust particles
Ionizer
Dust particles in the air
Photo-Catalyst Coated Mesh
+4.8KV discharge
Evaluated by CSIRO Australia (DBCE Doc 98/204) Tested by Korean Food Research Institute and Japanese Environmental Centre and Yonsei Univ.College of Medicine.(Allergy Research Lab.)
Polluted Air
+ +
+
Purified fresh Air
+
Generating plasma
Odour Odour molecule
Jet Cool : - In this mode quick and fast Cooling is done. Cold and high velocity air is supplied to the room till the indoor temperature reaches 18°C.
6
Floor Standing
5CSP0-02A
Features and Benefits
Child Lock Function: - This function prevents children or others from tampering with the control buttons on the unit. It is then controlled by the remote controller. - All the buttons on indoor display panel will be locked. - The unit will be controlled only by remote controller.
Cooling Heating and Fan Operation(for heat pump): - LG Floor Standing type air conditioners can provide cooling, heating and fan operation. In the cooling mode, it cools the air with an operation range of 16~30°C. In the heating mode, it heats the air with an operation range of 16~30°C. In the fan operation mode, only indoor fan at the selected speed will run, outdoor fan and compressor will be off.
Electric Heater: - Electric Heater can be used to provide heat in addition to refrigerant cycle heat. It also provide and quick heating. It can also work as a stand alone heater with only fan operation.
Auto Swing: - Hot or cold air can be evenly distributed throughout the room as the auto swing function blows air in 2 or 4 directions.
7-Hour On/Off Timer: - This function allows you to set the timer for one or up to seven hours.
Duct Operation(72k Btu/h Model): - Depending on the room size and shape, if the unit is installed in a Duct-type manner you are able to cool more air at the same time to save energy.
Floor Standing
7
Features and Benefits
5CSP0-02A
Auto Restart Operation : - Whenever there is an electricity failure to the unit, and after resumption of the power, unit will start in the same mode prior to the power failure. Memorized condition are on/off condition, operting mode (cooling/heating), set temperature and fan speed. The unit will memorize the above conditions and start with same memorized condition.
Hot Start Function : - During starting of the unit in the heating mode it prevents cold air blown from the unit. It starts the indoor fan only after indoor unit pipe temperature reaches a preset value(28°C). When indoor unit pipe temperature has reached 28°C, then for initial 1 minute the indoor fan runs at low speed and after that at the set fan speed.
Defrost / Deicing : - In the heating mode, it prevents the ice formation on the outdoor unit. The heating cycle is reversed to the cooling cycle to defrost the evaporator pipe of the outdoor unit. While defrost cycle, the compressor is on and indoor fan, outdoor fan and 4-way valve are off.
Soft Dry Operation : - During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 2°C, the compressor OFF temperature is the setting temperature minus 1°C. When the room temperature rises over the compressor ON temperature, the operation mode is switched to the Cooling mode. When the room temperature falls between the compressor ON temperature and OFF temperature, the operation mode is switched to the Soft Dry Operation.
Intake Air Temp.
Operation Cooling
Cooling operation
Dry operation
Setting Temp. +2°C (Compressor ON)
Setting Temp. -1°C (Compressor OFF)
Indoor Fan Speed Compressor
Selecting fan speed ON
maximum 7 min.
3 min.
10 min.
LOW
LOW
LOW
OFF
ON
OFF
3 min.
Selecting fan speed ON
maximum 10 min.
LOW
LOW
LOW
OFF
ON
OFF
Time Delay Safety Function: -It delays restarting of the compressor by three minutes, thereby preventing damage to the compressor.
8
Floor Standing
5CSP0-02A
List of Functions
4. List of Functions Floor Standing Function Air Discharge outlet Airflow Direction control (left & right) Airflow Direction control (up & down) Airflow Steps(Fan / Cool /Heat) Auto Changeover Auto Operation Auto Restart Operation Auto Swing Central Control Child Lock Function Cooling & Fan Operation(Cooling Only) Coolling, Heating & Fan Operation(Heat Pump) Defrost / Deicing Deodorizing Filter Drain Pump E.S.P. Control Electric Heater Energy Saving Gold Fin Energy Saving Cool Operation Environment Friendly Refrigerant Fire Alarm Function Forced Operation Group Control High Ceiling Operation Hot Start Jet Cool Low Ambient Control Plasma Air Purifier Prefilter(Washable / Anti-fungus) Restart Delay (3-minutes) Self Diagnosis Sleep Mode Soft Dry Operation Swirl Swing Space Control Tele Control Temperature Control Test Function Time Delay Safety Function Timer (weekly) Timer (24 hr On/Off) Two Thermistor Control Wired LCD Remote Controller Wireless Remote Controller Zero Standby Power Zone Control
AP-Z286RC0 [P03AH SR0] 3 Auto Auto 3/3/2 O O O O O O O O O O O O O O O O O Optional O O(7Hr Off Setting) O O -
AP-Z488TC0 [P05AH ST0] 1 Auto Manual 3/3/2 O O O O O O O O O O O O O O O O O O(7Hr Off Setting) O O -
AP-Z728FA1 [P08AH SF1] 1 Manual Manual 2/2/2 O O O O O O O O O O O O O O O O O(7Hr Off Setting) O O -
Notes : • O : Basic • Optional : Factory-Installed • Accessory : Field-Installed • - : Not available on this system
Floor Standing
9
Specifications
5CSP0-02A
5. Specifications Item
Unit
Cooling Capacity
Other
Outdoor
Indoor
General
Heating Capacity Input Running Current Starting Current Power Supply Power Factor Electric Heater
Cooling/Heating Cooling/Heating Cooling/Heating
E.E.R
Cooling
C.O.P
Heating
kcal/h(W) Btu/h kcal/h(W) Btu/h W A A ø,V,Hz % kW kcal/h W(W/W) Btu/h W W/W(kcal/h W) Btu/h W °C
Setting temperature range(cool/heat) Operational Temperature Cool Range(Outdoor) Heat Dehumidification Rate l/h Refrigerant Control Refrigerant charge g(oz), type Output W Model No. of Poles Indoor fan motor Input W Running Current A Capacitor µF/Vac Type Indoor Fan No. Used / Diameter EA/inch(mm) Cooling(H/M/L) rpm Indoor Fan RPM Heating(H/M/L) rpm Air Circulation Indoor (H/M/L) CMM(CFM) Noise Level(Sound Press,1m) Indoor(H/M/L) dB(A)±3 Temperature controller Tube Size (OD) inch(mm) Indoor Coil Fins per inch No. of Rows and Column Dimensions (W*H*D) Indoor inch(mm) Net Weight indoor kg(lbs) Locked Rotor Amp. A Type Quantity No. Model Maker Compressor Capacity kcal/h(Btu/h) Motor Type Motor Input W Oil Type Oil Charge cc O.L.P Type(model name) Tube Size (OD) inch(mm) Outdoor Coil Fins per inch No. of Rows and Column/No. Output W Model No. of Poles Outdoor fan motor Input W Running Current A Capacitor µF/Vac Type No. Used / Diameter EA/inch(mm) Outdoor Fan Discharge Side / Top Speed rpm Air Circulation Outdoor CMM(CFM) Noise Level(Sound Press,1m) Outdoor dB(A)±3 Liquid inch (mm) SVC Valve Gas inch(mm) Dimensions (W*H*D) Outdoor inch(mm) Net Weight Outdoor kg(lbs) Power Supply Cable No.* mm2 Connecting Cable No.* mm2 Liquid Side inch(mm) Connecting Tube Gas Side inch(mm) (Ø Socket Flare) Length, std m Max length/elevation m Drain hose Indoor Unit mm (ID Ø) Outdoor Unit mm Packing Dimension Indoor inch(mm) (W*H*D) Outdoor inch(mm) Stuffing Quantity With(Without) S/Parts 20/40ft
Notes: 1. Capacities are based on the following conditions:
Cooling: -
AP-Z286RC0 [P03AH SR0]
AP-Z488TC0 [P05AH ST0]
AP-Z728FA1 [P08AH SF1]
7,000(8,140) 27,800 7,000(8140) 27,800 2,800/2,800 13.0/13.0 68 1, 220-240, 50 92 2 2.50(2.91) 9.93 2.91(2.50) 9.93 16~30/-5 ~ +48 -10 ~ +24 3.3 Capillary Tube 2,200(77.6),R410A 50.9 IC-9440LG124A 4 170 0.75 4.0/440 TURBO FAN 1/12.6(320) 935/860/580/445 860/580/445 17(600) 48/46/40 Themistor 3/8(9.52) 18FPI 2R 30C 22.4*71.7*12.5(570*1,820*317) 33(73) 64/68 Rotary 1 5JS330DAB21 Matsushita 7,003(27,792) Permanent Split Capacitor 2,850 FVC50S 1,130 UP14TE5115-C 0.28(7) 21 1R(2R) 36C 85 OBM-4710P2 6 151 0.62 6/370 PROPELLER 2/18.11(460) Side discharge 880 58(2048) 58 3/8(9.52) 5/8(15.88) 34.25*25.79*12.6(870*655*320) 63(139) 3*4.0 4*0.75 9.52 15.88 7.5 30/20 21.5 25.0*74.6*15.6(635*1,895*395) 40.2*28.1*17.3(1,020*715*440) 30/60(30/65)
11,590(13,480) 46,000 12,095(14,060) 48,000 5,300/5,000 9.5/9.0 3, 380-415, 50 84 4 2.19(2.54) 8.68 2.81(2.42) 9.60 16~30/16~30 -5 ~ +48 -10 ~ +24 6 Capillary Tube 2,900(102.3),R410A 194 IC-13670LGSJ 6 457 1.41 10/370 SIRROCO FAN 1/13.4(340) 590/520/490 520/490 30/28/26(1,060/989/918) 53/51/48 Themistor 3/8(9.52) 18FPI 3R 28C 23.2*72.8*17.3(590*1,850*440) 60(132) 63(at 420V) Scroll 1 AR061YAB LG 12,626(50,100) Three Phase Induction Motor 5,330 FVC68D(PVE) 1,800 UP18TA057 0.28(7) 18 1R(2R) 26C 85 OBM-4710P2 6 151 0.63 6/370 PROPELLER 2/18.11(460) Side discharge 880 104(3673) 58 3/8(9.52) 3/4(19.05) 35.43*45.87*14.57(900*1,165*370) 90(198) 3*3.5 4*1.25 9.52 19.05 7.5 40/25 40 27.1*74.8*21.1(688*1,900*536) 41.7*48.0*18.3(1,060*1,220*465) 15/30(15/30)
17,200(20,000) 68,200 18,140(21,100) 72,000 7,000/6,000 11.1/10.0 3, 380-415, 50 92 10 2.40(2.79) 9.52 3.5(3.01) 11.94 16~30/16~30 -5 ~ +48 -10 ~ +24 8.5 Capillary Tube 3,500(123.5),R410A 385 IC-16660LGG 6 590 3.18 40/400 BLOWER WHEEL 2/9.53(242) 830/730/680 730/680 57/-/48(2,013/-/1695) 60/58/56 Themistor 3/8(9.52) 17 3R 33C 41.3*74.0*19.5(1,050*1,880*495) 132(291) 63/47(at 420V) Scroll 1 AR081YAB LG 12,626(50,100)/8,735(34,900) Three Phase Induction Motor 5,330/3,579 FVC68D(PVE) 1,800/1,200 UP18OA057 3/8(9.52) 17 1R(2R) 18C*2 130 AMR-240E1 6 230 0.96 6/370 PROPELLER 2/20.71(526) Side discharge 820 135(4767) 63 3/8(9.52) 3/4(19.05) 37.4*54.3*12.99(950*1,380*330) 113(249.1) 5*5.5 4*1.25 9.52 19.05 7.5 40/25 25 45.1*79.3*23.2(1,145*2,015*590) 45.2*57.6*18.1(1,147*1,463*461) 11/23(11/23)
Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB Interconnecting Piping Length 7.5m Level Difference of Zero.
2. Capacities are Net Capacities. 3. Due to our policy of innovation some specifications may be changed without notification.
10
Floor Standing
Heating:
-
Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB Interconnecting Piping Length 7.5 m Level Difference of Zero.
5CSP0-02A
Dimensional Drawings
6. Dimensional Drawings Model No. : AP-Z286RC0[P03AH SR0] 1) Indoor Unit 3
4
1,820
1
2
570
(Unit:mm)
317
No. 1 2 3 4
Items Control Display Air outlet vent Air inlet vent Sliding Clean Door
2) Outdoor Unit
360
340
95
546
870
320
3
800
5
1
No. 1 2 3 4 5
180
101
2 4
(Unit:mm)
Items Gas side service valve (Ø 15.88) Liquid side service valve (Ø 9.52) Fan cover Earth screw Connecting cable hole
Floor Standing
11
Dimensional Drawings
5CSP0-02A
Model No. : AP-Z488TC0[P05AH ST0] 1) Indoor Unit
486
439
260
1
1540
1850
525
3
2
139
134
79
562
950
40
590
338
No. 1 2 3
41
Items Air Outlet Vent Air Inlet Vent Control display 546
360
340
125
2) Outdoor Unit
1165
370
No. 1 2 3 4 5
12
230
150
505
Items Air Outlet Vent Liquid Side SVC Valve(Ø 9.52) Gas Side SVC Valve(Ø 19.05) Control Box Earth Screw
Floor Standing
5CSP0-02A
Dimensional Drawings
Model No. : AP-Z728FA1[P08AH SF1] 496
75
268
1
1051 951
75 130
193
1) Indoor Unit
121
1890
568
3
990
Knock out for piping
2 36
75 93.8
60
109.5
145.8
36 345
93.8
131
36
58.5
525
(Unit:mm) No. 1 2 3
Items Air outlet vent Air inlet vent Control Display
2) Outdoor Unit
(Unit:mm) No. 1 2 3 4 5
Items Gas side service valve (Ø19.05) Liquid side service valve (Ø9.52) Fan cover Control panel Connecting cable hole
Floor Standing
13
Wiring Diagrams
5CSP0-02A
7. Wiring Diagrams Model No.: AP-Z286RC0[P03AH SR0] 1) Indoor
GN/YL
DOOR S/W1
HVB ASM
A/CL UNIT
BL WH RD BK
BL
MAIN (AC) PCB ASM CNAIRC
CNHEATER
RY-COMP VARISTOR
CNHEATER
RY-LOW RY-MID RY-HIGH RY-S/H
RY-HEATER
RY-HEATER CNHEATER
BR CN-FAN/M
CN-AC/M RY-OPEN RY-CLOSE
CN-EVA TH
MAIN (DC) PCB ASM
CNLE/RI CNUP/DOWN
PTC2 T/S FUSE
STEP M
CNCNDOOR1 DOOR2
STEP M
E-HEATER
PTC1
CNHEATER
L/DOOR L/DOOR MOTOR MOTOR
BL
FUSE(250V,3.15A)
CN-TOP SENSOR
CN-ROOM TH
DOOR SENSOR (OPTION SENSOR)
RD BL BK WH OR
BK
4
C TH Deice PCB TNS
RD
3
GN/YL
2
BR
CAPACITOR BR
L2 1
BK
YL T/B1
WH 6
2
STEP LE/RI M MOTOR
L3
0
1 CN/YL
BL YL SYNC DOOR OR M UPPER
L4
WH L1
YL
FMi
BL
BL
FUSE (250V,5A)
CN4WAY
RD
T/B2
BL
BK BK
REVERSING VALVE
1 2 3 4 5
DOOR S/W1
1 2
GN/YL
2
8
OR
BK
BK Cr
4
POWER RELAY
WH R
BR S
FAN MOTOR
WH
STEP UP/DOWN M MOTOR
WH
1
POWER SUPPLY
CN-KEY
O.L.P
C COMP BK
GN/YL
OR
YL
CAPACITOR
KEY PCB ASM
3854A20144Z
2) Outdoor
TO THE INDOOR UNIT
BL
BL BK
4
C TH Deice PCB TNS
RD
3
L4
WH L1 GN/YL
2
BR
L2 1
BK
L3
0
YL
1
T/B1
WH
FUSE (250V,5A)
E-HEATER POWER SUPPLY (TO THE INDOOR UNIT)
T/B2
BL
BK BK
REVERSING VALVE
2
6
8
2
4
OR
POWER RELAY
Cr WH R
BR S
WH POWER SUPPLY
O.L.P
WH
1
BK
BK
C COMP BK
GN/YL
FAN MOTOR OR
YL
CAPACITOR
3854A20179Y
Notes: RY BK OR GN/YL
14
RELAY BLACK ORANGE GREEN/YELLOW
COMP
COMPRESSOR
BL
BLUE
BR
BROWN
RD
RED
WH
WHITE
YL
OPTIONAL PARTS
Floor Standing
YELLOW FIELD WIRING
5CSP0-02A
Wiring Diagrams
Model No.: AP-Z488TC0[P05AH ST0] 1) Indoor
ELECTRIC HEATER DIAGRAM
YL DOOR S/W
OR
BK RD WH
FUSE
DOOR S/W
AIR CLEANER (AIR CLEANER MODEL ONLY)
250V 3.15A
RY-COMP CN-AIRC
RY-4WAY
BK RD
H.V ASSY
CN-OUTUNIT CN-FAN
GN/YL RD
BL BR
CN-HEAT
PIPE SENSOR
CNEVA TH
4
TF
TS
PTC HEATER
TF
BL BL
1 2 3 4 5 6 SYN. MOTOR
CNSYNC
CN-CABLE
TS PTC HEATER
RY-2
RY-HIGH RY-MID RY-LOW RY-SYNC
HEAT PCB ASM CNHEAT
RY-1
BK BK
YL
INDOOR MOTOR
RD
1(L) 2(N) 3
CAPACITOR
BL
AC PCB ASM
OR BK BL RD
TERMINAL BLOCK
BR
BR
TO OUTDOOR UNIT
5
GN/YL
POWER SUPPLY (CONNECT CONTACT "R","N" OF OUTDOOR TERMINAL BLOCK "TM")
KEY PCB ASM CN-CABLE
CNROOM TH
ROOM SENSOR
DC PCB ASM
P/NO; 3854A20410A
P/NO. : 3854A20411A
2) Outdoor F1
BK BK
D.P BK
BK
WH
F1
WH OR
1
52C
POWER SUPPLY 3Ø,380-415V~,50Hz TERMINAL(4P)
WH
WH
BK
TM R S T N
C TH NO NC NO NC
TNS
WH RD
3
5
BK A1 T/B1
CRANK-CASE HEATER
2
OR
3
4
WH
5
6
7
8
A2 2
4
6
52F1 1
21
22
OR
T/B2
BK RD
BL RD
BK
WH
BK
BK
Co BK
RD
1(L) WH
WH YL BK OR
FMo 49FMo
2(N) 3 4 5
RD
YL BK OR
FMo 49FMo
(T1) W
(T2) (T3) V U
BK
BL
BK
BL
20SV
CM
TMo
To the indoor unit
BK
Co
GN/YL
NOTE
BL : BLUE RD : RED WH : WHITE BK : BLACK YL : YELLOW OR : ORANGE GN/YL : GREEN/YELLOW 63H2
HIGH PRESSURE SWITCH FOR COOLING
52C
MAGNECTIC CONTACTOR
FMo
OUTDOOR FAN MOTOR
C TH
THERMISTOR FOR PIPE TEMP.
TM
MAIN TERMINAL BLOCK
F1
FUSE (250V 5A)
49FMo INTERNAL T.P FOR FMo
52F1
RELAY FOR FMo
TMo
TERMINAL BLOCK
20SV
REVERSING COIL
D.P
DEICER PCB
CM
COMPRESSOR
Co
RUN CAPACITOR FOR FMo
P/NO : 3854A20119V
Floor Standing
15
Wiring Diagrams
5CSP0-02A
Model No.: AP-Z728FA1[P08AH SF1] 1) Indoor
2) Outdoor
16
Floor Standing
5CSP0-02A
Refrigerant Cycle Diagrams
8. Refrigerant Cycle Diagrams Heat Pump INDOOR UNIT
OUTDOOR UNIT LIQUID SIDE
CHECK VALVE
3-WAY VALVE
CAPILLARY TUBE
CAPILLARY TUBE HEAT EXCHANGER HEAT EXCHANGER 4-WAY VALVE GAS SIDE 3-WAY VALVE
ACCUMULATOR
MUFFLER COOLING HEATING DE-ICE COMPRESSOR
Floor Standing
17
Selection Procedure
5CSP0-02A
9. Selection Procedure Step 1. Determine cooling load requirements at design conditions. Required load conditions: Required cooling capacity (TC) .......................26,000 Btu/h Sensible capacity (SHC) .................................18,500 Btu/h Temperature air entering outdoor unit ............95°F Temperature air entering indoor unit ...............80°F DB/67°F WB DB — dry bulb temperature WB — wet bulb temperature Step 2. Select unit based on required cooling capacity. Based on Total Cooling Capacity, choose suitable model from the specification table. The model with a net capacity of 27,800 Btu/h cooling is selected. The system consists of a AP-Z286RC0[P03AH SR0]. Verify the unit performance at the given conditions in accordance with step 3. Step 3. Determine if system selected satisfies cooling requirements. Enter cooling capacities table on page 21 at high speed and 95 F outdoor entering air temperature with 80 F DB/67 F WB indoor entering air temperature. Total cooling capacity = 27,800 Btu/h, Sensible capacity=20,300 Btu/h To find capacity at intermediate conditions not in the table ; Interpolation should be used when design conditions are between two numbers that are in the capacity table. Extra-polation is not recommended. If the interconnecting piping length is more than 7.5m ; Find the capacity(%) at that particular interconnecting piping length from the coefficient of capacity change graph, on page 23. Multiply cofficient factor with Total Cooling Capacity and Sensible Capacity. Ex: At 15m interconnecting piping length, from coefficient of capacity change graph, cofficient factor is 0.96.
Total Cooling Capacity = Capacity(%) x Total Cooling Capacity = 96x27800 = 26,688Btu/h 100 100 Sensible Capacity = Capacity(%) x Sensible Capacity = 96x20,300 = 19,488Btu/h 100 100
18
Floor Standing
5CSP0-02A
Performance Data
10. Performance Data 10.1 Cooling Capacity(SI Units) Model No.: AP-Z286RC0[P03AH SR0] Outdoor DB (°C)
29.4
Indoor WB (°C) Indoor DB (°C) 23.9 26.7 29.4 32.2
16.1 TC 7.6 7.9 8.2 8.5
SHC 6.2 7.2 7.9 8.3
Outdoor DB (°C)
40.6
Indoor WB (°C)
22.8
Indoor DB (°C) 23.9 26.7 29.4 32.2
TC 8.1 8.1 8.1 8.0
SHC 2.0 3.7 5.1 6.2
35.0
19.4 PI 2.45 2.46 2.46 2.47
TC 8.4 8.6 8.7 8.8
SHC 4.7 5.9 7.1 7.9
22.8 PI 2.53 2.53 2.54 2.55
TC 9.1 9.1 9.0 9.0
SHC 2.1 3.9 5.4 6.5
16.1 PI 2.57 2.58 2.59 2.60
TC 7.2 7.6 7.8 8.1
SHC 6.3 7.2 7.8 8.1
40.6
19.4 PI 2.71 2.71 2.72 2.73
TC 8.0 8.1 8.3 8.4
SHC 4.7 5.9 7.2 8.0
22.8 PI 2.79 2.80 2.81 2.82
16.1
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
8.6 8.6 8.6 8.5
2.1 3.9 5.4 6.6
2.84 2.85 2.86 2.87
6.8 7.1 7.4 7.6
6.0 6.8 7.4 7.6
2.90 2.91 2.91 2.92
7.5 7.7 7.8 7.9
4.5 5.7 6.8 7.6
2.99 3.00 3.01 3.02
46.1 16.1 PI 3.04 3.05 3.06 3.07
TC 6.3 6.6 6.9 7.1
SHC 5.7 6.6 6.9 7.1
51.7
19.4 PI 3.06 3.07 3.08 3.09
TC 7.0 7.1 7.2 7.3
SHC 4.3 5.4 6.5 7.3
19.4
22.8 PI 3.16 3.17 3.18 3.19
TC 7.5 7.5 7.5 7.5
SHC 1.9 3.6 4.9 6.0
16.1 PI 3.22 3.23 3.24 3.25
TC 5.6 5.8 6.0 6.2
SHC 5.2 5.8 6.0 6.2
19.4 PI 3.20 3.21 3.22 3.23
TC 6.2 6.3 6.4 6.4
SHC 3.9 4.9 5.9 6.4
22.8 PI 3.30 3.31 3.32 3.33
TC SHC PI 6.6 1.7 3.36 6.6 3.2 3.37 6.6 4.5 3.38 6.6 5.4 3.39
Model No.: AP-Z488TC0[P05AH ST0] Outdoor DB (°C)
29.4
Indoor WB (°C) Indoor DB (°C) 23.9 26.7 29.4 32.2
16.1 TC 12.6 13.1 13.6 14.1
SHC 9.9 11.4 12.5 13.1
Outdoor DB (°C)
19.4 PI 4.63 4.65 4.66 4.68
TC 13.9 14.2 14.4 14.5
SHC 7.5 9.4 11.3 12.6
22.8 PI 4.78 4.79 4.81 4.82
TC 15.0 15.0 14.9 14.9
SHC 3.3 6.2 8.5 10.4
40.6
Indoor WB (°C) Indoor DB (°C) 23.9 26.7 29.4 32.2
35.0
SHC 3.2 5.9 8.1 9.9
PI 4.87 4.88 4.90 4.91
TC 12.0 12.5 13.0 13.4
SHC 9.9 11.4 12.5 13.2
19.4 PI 5.12 5.14 5.15 5.17
TC 13.2 13.5 13.7 13.8
SHC 7.5 9.4 11.4 12.6
22.8 PI 5.28 5.30 5.32 5.33
TC
SHC
14.2 3.3 14.2 6.2 14.2 8.5 14.1 10.4
16.1 PI
16.1 PI 5.76 5.78 5.80 5.81
19.4
TC
SHC
PI
TC
SHC
PI
5.38 11.3 5.40 11.8 5.41 12.2 5.43 12.6
9.5 10.9 11.9 12.5
5.48 5.50 5.52 5.53
12.5 12.7 12.9 13.0
7.2 9.0 10.8 12.0
5.66 5.67 5.69 5.71
46.1
22.8 TC 13.4 13.4 13.4 13.3
16.1
40.6
51.7
19.4
22.8
TC SHC PI TC SHC PI 10.5 9.1 5.80 11.6 6.9 5.98 10.9 10.4 5.81 11.8 8.6 6.00 11.4 11.4 5.83 12.0 10.4 6.02 11.7 11.7 5.85 12.1 11.5 6.03
TC 12.5 12.5 12.4 12.4
SHC 3.0 5.6 7.8 9.5
16.1 PI 6.09 6.11 6.13 6.15
TC 9.2 9.6 10.0 10.3
SHC 8.2 9.4 10.0 10.3
19.4 PI 6.06 6.08 6.10 6.12
TC 10.2 10.4 10.5 10.6
SHC 6.2 7.8 9.4 10.4
22.8 PI 6.25 6.27 6.29 6.31
TC 11.0 11.0 10.9 10.9
SHC 2.7 5.1 7.1 8.6
PI 6.37 6.39 6.41 6.43
Model No.: AP-Z728FA1[P08AH SF1] Outdoor DB (°C)
29.4
Indoor WB (°C) Indoor DB (°C) 23.9 26.7 29.4 32.2
Outdoor DB (°C) Indoor WB (°C) Indoor DB (°C) 23.9 26.7 29.4 32.2
16.1 TC 18.4 19.2 19.9 20.6
SHC 14.9 17.1 18.7 19.7
35.0
19.4 PI 6.12 6.14 6.16 6.18
TC 20.3 20.7 21.0 21.2
SHC 11.3 14.1 17.0 18.9
22.8 PI 6.31 6.33 6.35 6.37
TC 21.9 21.9 21.8 21.7
SHC 5.0 9.2 12.8 15.6
40.6
PI 6.43 6.45 6.47 6.49
TC 17.8 18.5 19.2 19.9
SHC 15.2 17.4 19.1 19.9
19.4 PI 6.77 6.79 6.81 6.83
TC 19.6 20.0 20.3 20.5
SHC 11.5 14.4 17.3 19.3
22.8 PI 6.98 7.00 7.02 7.04
16.1 PI 7.61 7.63 7.65 7.68
TC 16.2 16.9 17.5 18.1
SHC 14.4 16.5 17.5 18.1
TC 17.9 18.2 18.5 18.7
SHC 10.9 13.6 16.4 18.3
Notes: 1. All capacites are net, evaporator fan motor heat is deducted. 3. TC=Total cooling capacity(Unit:kW) 5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)
19.4
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
5.1 9.4 13.0 15.9
7.11 7.13 7.15 7.17
17.1 17.9 18.6 19.2
14.8 17.0 18.6 19.2
7.24 7.26 7.29 7.31
18.9 19.3 19.6 19.8
11.2 14.0 16.9 18.8
7.47 7.49 7.52 7.54
51.7
19.4 PI 7.66 7.68 7.70 7.73
16.1
21.1 21.1 21.1 20.9
46.1
22.8 TC SHC 20.4 4.9 20.4 9.2 20.3 12.7 20.2 15.5
16.1
40.6
22.8 PI 7.90 7.92 7.95 7.97
TC SHC PI 19.2 4.8 8.04 19.2 8.9 8.07 19.2 12.4 8.09 19.1 15.1 8.12
16.1 TC 15.0 15.6 16.2 16.7
SHC 13.7 15.6 16.2 16.7
19.4 PI 8.00 8.03 8.05 8.08
TC SHC 16.6 10.4 16.9 13.0 17.1 15.7 17.3 17.3
22.8 PI 8.26 8.28 8.31 8.33
TC SHC 17.8 4.6 17.8 8.5 17.8 11.8 17.7 14.4
PI 8.41 8.44 8.46 8.49
2. DB=Dry Bulb Temperature(°C), WB=Wet Bulb Temperature(°C) 4. SHC=Sensible heat capacity(Unit: kW)
Floor Standing
19
Performance Data
5CSP0-02A
10.2 Heating Capacity(SI Units) Model No.: AP-Z286RC0[P03AH SR0] Outdoor WB (°C) Indoor DB(°C) 16 18 20 22 24
-10
-5
0
2
4
6
10
15
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
5.5 5.3 5.2 5.0 4.8
2.0 2.1 2.2 2.2 2.3
6.5 6.3 6.1 5.9 5.7
2.2 2.3 2.4 2.5 2.5
7.5 7.3 7.0 6.8 6.6
2.4 2.5 2.6 2.7 2.8
7.9 7.6 7.4 7.1 6.9
2.5 2.6 2.7 2.8 2.8
8.3 8.0 7.8 7.5 7.2
2.6 2.7 2.8 2.8 2.9
8.7 8.4 8.1 7.9 7.6
2.6 2.7 2.8 2.9 3.0
9.4 9.1 8.9 8.5 8.3
2.8 2.9 3.0 3.0 3.1
10.4 10.1 9.8 9.4 9.1
3.0 3.1 3.2 3.3 3.4
Model No.: AP-Z488TC0[P05AH ST0] Outdoor WB (°C) Indoor DB(°C) 16 18 20 22 24
-10
-5
0
2
4
6
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
9.5 9.2 8.9 8.6 8.3
3.6 3.8 3.9 4.0 4.1
11.2 10.8 10.5 10.1 9.8
4.0 4.1 4.3 4.4 4.5
12.9 12.5 12.2 11.7 11.3
4.3 4.5 4.6 4.8 4.9
13.6 13.2 12.8 12.3 11.9
4.5 4.6 4.8 4.9 5.1
14.2 13.8 13.4 12.9 12.5
4.6 4.8 4.9 5.1 5.2
10
15
TC
PI
TC
PI
TC
PI
15.1 14.6 14.1 13.6 13.2
4.7 4.8 5.0 5.2 5.3
16.3 15.8 15.3 14.8 14.2
4.9 5.1 5.3 5.4 5.6
18.0 17.4 16.9 16.3 15.7
5.3 5.5 5.6 5.8 6.0
Model No.: AP-Z728FA1[P08AH SF1] Outdoor WB (°C) Indoor DB(°C) 16 18 20 22 24
-10
-5
0
2
4
6
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
14.2 13.8 13.4 12.9 12.5
4.4 4.5 4.7 4.8 5.0
16.8 16.3 15.8 15.2 14.7
4.8 4.9 5.1 5.3 5.4
19.4 18.8 18.2 17.6 17.0
5.2 5.4 5.6 5.7 5.9
20.4 19.7 19.2 18.5 17.8
5.4 5.5 5.7 5.9 6.1
21.4 20.7 20.1 19.4 18.7
5.5 5.7 5.9 6.1 6.3
10
15
TC
PI
TC
PI
TC
PI
22.6 21.9 21.1 20.4 19.7
5.6 5.8 6.0 6.2 6.4
24.4 23.7 23.0 22.1 21.4
5.9 6.1 6.3 6.5 6.7
27.0 26.1 25.3 24.4 23.6
6.3 6.6 6.8 7.0 7.2
Notes : 1. All capacities are net, indoor fan motor heat is deducted. 2. Capacities are based on the following conditions. Outdoor air : 85%RH. However, the condition on nominal capacity is 7°CDB/6°CWB. 3. TC=Total heating capacity(Unit:kW) 4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW) 5. All data above only consist of heat pump capacity and does not include electric heater capacity.
Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation. The heating capacity in the "Heating Capacity" Table above indicates the actual heating capacity excluding the effect of frost on the heat exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity reduction by frost on the exchanger and defrosting operation. Correction Factor
20
Outdoor Air Temperature (°CWB, RH=85%)
-10
-6
-4
-2
0
2
4
6
Correction Factor
0.95
0.95
0.89
0.87
0.87
0.89
0.91
1
Floor Standing
5CSP0-02A
Performance Data
10.3 Cooling Capacity(English Units) Model No.: AP-Z286RC0[P03AH SR0] Outdoor DB (°F)
85
Indoor WB (°F) Indoor DB (°F) 75 80 85 90
61 TC 26.0 27.1 28.1 29.1
SHC 21.3 24.5 26.8 28.2
Outdoor DB (°F)
105
Indoor WB (°F)
73
Indoor DB (°F) 75 80 85 90
TC 27.6 27.7 27.6 27.4
95
67 PI 2.45 2.46 2.46 2.47
TC 28.7 29.2 29.7 30.0
73
SHC 16.1 20.2 24.3 27.0
PI 2.53 2.53 2.54 2.55
TC 30.9 30.9 30.8 30.6
SHC 7.1 13.2 18.3 22.3
61 PI 2.57 2.58 2.59 2.60
TC 24.7 25.8 26.7 27.6
SHC 21.4 24.6 26.7 27.6
105
67 PI 2.71 2.71 2.72 2.73
TC 27.3 27.8 28.2 28.5
SHC 16.2 20.3 24.4 27.2
73 PI 2.79 2.80 2.81 2.82
TC
SHC
29.4 7.2 29.4 13.3 29.3 18.4 29.1 22.4
61 PI
SHC
PI
TC
SHC
PI
2.84 23.3 2.85 24.3 2.86 25.2 2.87 26.0
20.3 23.4 25.2 26.0
2.90 2.91 2.91 2.92
25.7 26.2 26.5 26.8
15.4 19.3 23.2 25.8
2.99 3.00 3.01 3.02
115 61
SHC 6.8 12.6 17.5 21.3
PI 3.04 3.05 3.06 3.07
TC 21.6 22.6 23.4 24.2
SHC 19.5 22.4 23.4 24.2
125
67 PI 3.06 3.07 3.08 3.09
TC 23.9 24.3 24.7 25.0
SHC 14.8 18.5 22.3 24.8
67
TC
73 PI 3.16 3.17 3.18 3.19
TC 25.7 25.7 25.6 25.5
SHC 6.5 12.1 16.8 20.4
61 PI 3.22 3.23 3.24 3.25
TC 19.0 19.9 20.6 21.3
SHC 17.7 19.9 20.6 21.3
67 PI 3.20 3.21 3.22 3.23
TC 21.0 21.4 21.7 22.0
SHC 13.4 16.8 20.2 22.0
73 PI 3.30 3.31 3.32 3.33
TC 22.6 22.6 22.6 22.4
SHC 5.9 11.0 15.2 18.5
PI 3.36 3.37 3.38 3.39
Model No.: AP-Z488TC0[P05AH ST0] Outdoor DB (°F)
85
Indoor WB (°F) Indoor DB (°F) 75 80 85 90
61 TC 43.0 44.9 46.6 48.1
SHC 33.8 38.8 42.6 44.8
Outdoor DB (°F)
105
Indoor WB (°F)
73
Indoor DB (°F) 75 80 85 90
TC 45.7 45.8 45.6 45.4
95
67 PI 4.63 4.65 4.66 4.68
TC 47.5 48.4 49.1 49.6
SHC 25.6 32.1 38.6 42.9
73 PI 4.78 4.79 4.81 4.82
TC 51.1 51.1 51.0 50.7
SHC 11.3 21.0 29.1 35.4
61 PI 4.87 4.88 4.90 4.91
TC 40.9 42.6 44.3 45.7
SHC 34.0 39.0 42.7 45.0
105
67 PI 5.12 5.14 5.15 5.17
TC 45.2 46.0 46.7 47.2
SHC 25.7 32.2 38.8 43.1
73 PI 5.28 5.30 5.32 5.33
TC
SHC
48.6 11.3 48.6 21.1 48.5 29.2 48.2 35.5
61 PI
SHC
PI
TC
SHC
PI
5.38 38.5 5.40 40.1 5.41 41.7 5.43 43.0
32.3 37.1 40.6 42.8
5.48 5.50 5.52 5.53
42.5 43.3 43.9 44.4
24.4 30.6 36.9 41.0
5.66 5.67 5.69 5.71
115 61
SHC 10.8 20.0 27.7 33.8
PI 5.76 5.78 5.80 5.81
TC 35.8 37.3 38.7 40.0
SHC 31.0 35.5 38.7 40.0
125
67 PI 5.80 5.81 5.83 5.85
TC 39.6 40.3 40.8 41.3
SHC 23.4 29.4 35.4 39.3
67
TC
73 PI 5.98 6.00 6.02 6.03
TC 42.5 42.5 42.4 42.2
SHC 10.3 19.2 26.6 32.4
61 PI 6.09 6.11 6.13 6.15
TC 31.5 32.9 34.1 35.2
SHC 28.1 32.2 34.1 35.2
67 PI 6.06 6.08 6.10 6.12
TC 34.8 35.4 36.0 36.3
SHC 21.3 26.6 32.1 35.6
73 PI 6.25 6.27 6.29 6.31
TC 37.4 37.5 37.3 37.1
SHC 9.4 17.4 24.1 29.4
PI 6.37 6.39 6.41 6.43
Model No.: AP-Z728FA1[P08AH SF1] Outdoor DB (°F)
85
Indoor WB (°F) Indoor DB (°F) 75 80 85 90
61 TC 62.8 65.5 68.0 70.2
Outdoor DB (°F)
67 PI 6.12 6.14 6.16 6.18
TC 69.4 70.7 71.7 72.5
SHC 38.5 48.2 58.0 64.5
73 PI 6.31 6.33 6.35 6.37
TC 74.7 74.7 74.5 74.0
SHC 17.0 31.6 43.6 53.2
105
Indoor WB (°F) Indoor DB (°F) 75 80 85 90
SHC 50.8 58.3 63.9 67.3
95
SHC 16.9 31.3 43.3 52.8
TC 60.6 63.2 65.6 67.8
SHC 51.8 59.5 65.2 67.8
67 PI 6.77 6.79 6.81 6.83
TC 67.0 68.2 69.2 69.9
SHC 39.2 49.1 59.1 65.7
73 PI 6.98 7.00 7.02 7.04
61 PI 7.61 7.63 7.65 7.68
TC 55.2 57.6 59.8 61.7
SHC 49.1 56.4 59.8 61.7
TC 61.0 62.1 63.0 63.7
SHC 37.2 46.6 56.1 62.3
Notes: 1. All capacites are net, evaporator fan motor heat is deducted. 3. TC=Total cooling capacity(Unit:1,000Btu/h) 5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)
67
SHC
PI
TC
SHC
PI
TC
SHC
PI
72.0 72.1 71.9 71.4
17.3 32.2 44.5 54.2
7.11 7.13 7.15 7.17
58.5 61.0 63.3 65.4
50.5 57.9 63.3 65.4
7.24 7.26 7.29 7.31
64.7 65.8 66.8 67.5
38.2 47.9 57.6 64.0
7.47 7.49 7.52 7.54
125
67 PI 7.66 7.68 7.70 7.73
61
TC
115
73 TC 69.5 69.5 69.3 68.9
61 PI 6.43 6.45 6.47 6.49
105
73 PI 7.90 7.92 7.95 7.97
TC 65.6 65.6 65.4 65.0
SHC 16.4 30.5 42.2 51.4
61 PI 8.04 8.07 8.09 8.12
TC 51.1 53.3 55.3 57.2
SHC 46.9 53.3 55.3 57.2
67 PI 8.00 8.03 8.05 8.08
TC SHC 56.5 35.5 57.5 44.4 58.4 53.5 59.0 59.0
73 PI 8.26 8.28 8.31 8.33
TC 60.8 60.8 60.6 60.2
SHC 15.7 29.1 40.3 49.0
PI 8.41 8.44 8.46 8.49
2. DB=Dry Bulb Temperature(°F), WB=Wet Bulb Temperature(°F) 4. SHC=Sensible heat capacity(Unit:1,000Btu/h)
Floor Standing
21
Performance Data
5CSP0-02A
10.4 Heating Capacity(English Units) Model No.: AP-Z286RC0[P03AH SR0] Outdoor WB (°F) Indoor DB(°F) 60.8 64.4 68 71.6 75.2
14.0
23.0
32
35.6
39.2
42.8
50
59.0
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
18.8 18.2 17.6 17.0 16.4
2.0 2.1 2.2 2.2 2.3
22.1 21.4 20.8 20.0 19.3
2.2 2.3 2.4 2.5 2.5
25.6 24.8 24.0 23.2 22.4
2.4 2.5 2.6 2.7 2.8
26.9 26.0 25.3 24.3 23.5
2.5 2.6 2.7 2.8 2.8
28.2 27.3 26.5 25.5 24.6
2.6 2.7 2.8 2.8 2.9
29.8 28.8 27.8 27.0 26.0
2.6 2.7 2.8 2.9 3.0
32.2 31.2 30.3 29.2 28.2
2.8 2.9 3.0 3.0 3.1
35.6 34.4 33.4 32.2 31.1
3.0 3.1 3.2 3.3 3.4
Model No.: AP-Z488TC0[P05AH ST0] Outdoor WB (°F) Indoor DB(°F) 60.8 64.4 68 71.6 75.2
14.0
23.0
32
35.6
39.2
42.8
50
59.0
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
32.4 31.4 30.5 29.4 28.4
3.6 3.8 3.9 4.0 4.1
38.2 37.0 35.9 34.6 33.4
4.0 4.1 4.3 4.4 4.5
44.2 42.8 41.5 40.0 38.6
4.3 4.5 4.6 4.8 4.9
46.4 44.9 43.6 42.0 40.6
4.5 4.6 4.8 4.9 5.1
48.6 47.1 45.7 44.0 42.5
4.6 4.8 4.9 5.1 5.2
51.4 49.8 48.0 46.5 44.9
4.7 4.8 5.0 5.2 5.3
55.6 53.9 52.3 50.4 48.6
4.9 5.1 5.3 5.4 5.6
61.4 59.5 57.7 55.6 53.7
5.3 5.5 5.6 5.8 6.0
Model No.: AP-Z728FA1[P08AH SF1] Outdoor WB (°F) Indoor DB(°F) 60.8 64.4 68 71.6 75.2
14.0
23.0
32
35.6
39.2
42.8
50
59.0
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
48.6 47.1 45.7 44.0 42.5
4.4 4.5 4.7 4.8 5.0
57.3 55.5 53.8 51.9 50.1
4.8 4.9 5.1 5.3 5.4
66.3 64.2 62.3 60.0 58.0
5.2 5.4 5.6 5.7 5.9
69.6 67.4 65.4 63.0 60.9
5.4 5.5 5.7 5.9 6.1
73.0 70.6 68.5 66.1 63.8
5.5 5.7 5.9 6.1 6.3
77.1 74.6 72.0 69.8 67.4
5.6 5.8 6.0 6.2 6.4
83.4 80.8 78.4 75.6 73.0
5.9 6.1 6.3 6.5 6.7
92.1 89.2 86.5 83.4 80.5
6.3 6.6 6.8 7.0 7.2
Notes : 1. All capacities are net, indoor fan motor heat is deducted. 2. Capacities are based on the following conditions. Outdoor air : 85%RH. However, the condition on nominal capacity is 44.6°FDB/42.8°FWB. 3. TC=Total heating capacity(Unit:1,000 Btu/h) 4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW) 5. All data above only consist of heat pump capacity and does not include electric heater capacity.
Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation. The heating capacity in the "Heating Capacity" Table above indicates the actual heating capacity excluding the effect of frost on the heat exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity reduction by frost on the exchanger and defrosting operation. Correction Factor
22
Outdoor Air Temperature (°FWB, RH=85%)
14
21.2
24.8
28.4
32
35.6
39.2
42.8
Correction Factor
0.95
0.95
0.89
0.87
0.87
0.89
0.91
1.00
Floor Standing
5CSP0-02A
The Coefficient of Capacity Change
11. The Coefficient of Capacity Change
Capacity(%)
100
Heating
90
Cooling 80
70 7.5
10
20
30
40
50
Total Pipe Length(m) Max. Pipe Length(m)
Max. Elevation (m)
Additional Refrigerant
AP-Z286RC0[P03AH SR0]
30
20
30g/m
AP-Z488TC0[P05AH ST0]
40
25
40g/m
AP-Z728FA1[P08AH SF1]
40
25
60g/m
Model No.
Notes ❈ Equivalent pipe length = actual pipe length + number of band x 0.3 ❈ Additional Refrigerant Charge Example: For Model No. AP-Z286RC0[P03AH SR0] having 20m pipe length, additional refrigerant to be charged is (20-7.5) x 30 = 375g
Floor Standing
23
Operation Range
5CSP0-02A
12. Operation Range
Inlet air temperature (Cooling)
Standard operation
Range
Outdoor air temperature °C D.B.(°F)
Item
43(109.4)
21(69.8)
15(59)
24(75.2)
Indoor air temperature °C W.B.(°F)
Outdoor air temperature °C W.B.(°F)
Inlet air temperature (Heating)
18(64.4)
Standard operation
-10(14) 10(50)
24(75.2)
Indoor air temperature °C D.B.(°F)
24
Power source voltage
Rating ±10%
Voltage at starting
Min. 85% of rating
Floor Standing
5CSP0-02A
Sound Levels
13. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operation condition - Reference accoustic pressure OdB = 20µPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard(KS conditions)
1m
1m
Sound Levels(dBA)
Model
H 48 53 60
AP-Z286RC0[P03AH SR0] AP-Z488TC0[P05AH ST0] AP-Z728FA1[P08AH SF1]
M 46 51 58
L 40 48 56
Sound Pressure Level
80
NC-70 NC-65
60 NC-60 NC-55 50 NC-50 NC-45
40
NC-40 NC-35
30
Sound Pressure Level (dB re 20µPa )
80
70
Sound Pressure Level (dB re 20µPa )
AP-Z488TC0[P05AH ST0] 90
80
70 NC-70 NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35 30
NC-25
NC-25
20
NC-15 63
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
NC-70 NC-65
60
NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35 30 NC-30 NC-25
20
NC-20
NC-20 10
70
NC-30
NC-30 20
AP-Z728FA1[P08AH SF1] 90
Sound Pressure Level (dB re 20µPa )
AP-Z286RC0[P03AH SR0] 90
NC-20
NC-15
10
NC-15
10 63
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
Floor Standing
8000
63
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
25
Installation
5CSP0-02A
14. Installation 14.1 Select the best location 14.1.1 Indoor Unit • There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • There should be easy provision of condensate drain. • Taking into account the noise prevention criteria, spot the installation. • Keep proper distance of the unit from ceiling, fence, walls and other obstacles as shown figure. • The indoor unit must have the maintenance space around.
14.1.2 Outdoor Unit • If an roof is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted. • Do not place animals and plants in the path of the warm air. • Take the air conditioner weight into account and select a place where noise and vibration are minimum. • Select a place so that the warm air and noise from the air conditioner do not disturb neighbors. • Rooftop Installations : If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
Model No.: AP-Z286RC0[P03AH SR0] OUTDOOR UNIT
INDOOR UNIT
5cm m 00c
5cm
20c
m
40cm
m
50c
1
0cm
10
26
Floor Standing
50c
m
5CSP0-02A
Installation
Model No.: AP-Z488TC0[P05AH ST0] INDOOR
OUTDOOR
30c
m m
5cm
30c
5cm 40cm
0cm
50c
m
m 70c
10
Model No.: AP-Z728FA1[P08AH SF1] INDOOR UNIT
OUTDOOR UNIT
50cm 100cm
5cm
50cm
5cm 40cm
100cm
Floor Standing
50cm
27
Installation
5CSP0-02A
14.2 Installation of Indoor unit and outdoor unit
The Indoor Unit Installation Wall
Core Drill
200mm 90mm
70mm
70mm
1. The mounting floor should be strong and solid enough to prevent it from vibration.
INSIDE
2. Drill the piping hole with 70mm diameter holecore drill at either the right or the left of indoor unit. The hole should be sightly slant to the outdoor side.
Plastic tube (Bushing)
3. Insert the plastic tube through the hole.
OUTSIDE Wall
Tilt
4. Cut the extruded outside part of the plastic tube, if necessary.
Cut if necessary More than 15mm
Outdoor unit Installation 1. Install the outdoor unit on the concrete or any solid base securely and horizontally by securing it with bolts (Ø12mm) and nuts. 2. If there is any vibration transmitted to the building, mount the rubber underneath the outdoor unit.
Refrigerant amount Before shipment, this air conditioner is filled with the rated amount of refrigerant including additional amount required for air-purging, subject to 5m piping length. (The rated amount of refrigerant is indicated on the name plate.) But when the piping length exceeds 5 meters, additional charge is required according to the following table.
MODEL
REFRIGERANT CHARGE
28k (Btu/h)
30 per 1m
48k (Btu/h)
40 per 1m
72k (Btu/h)
60 per 1m
Example) 28K/30K In case of 10m long pipe(one-way), the amount of refrigerant to be replenished is: (10 - 5) x 30 = 150g 28
Floor Standing
5CSP0-02A
Installation
14.3 Wiring Connection 14.3.1 Connecting the Cable to Indoor Unit • In order to protect cable, it should be inserted “Bushing Rubber”. • The inside and outside connecting cable can be connected after opening the inlet grille. 1. Open the inlet grille manually.
2. Open the control cover with Driver( ).
3. Connect the supplied cables to the connector in the control box. (Method "A") AP-Z286RC0[P03AH SR0], AP-Z488TC0[P05AH ST0])
Method
5. Connect the cables (LG doesn't supply) to the connector in the control box(Method "C"). (AP-Z286RC0[P03AH SR0], AP-Z488TC0[P05AH ST0])
6. Secure the control cover to the original position with the screw.
"C"
4 5
"B"
INDOOR UNIT MOTOR (1PHASE 220V) TO OUTDOOR UNIT TO OUTDOOR UNIT
1 2 3 4 5 6
4. Connector the cables (LG doesn't supply) to the connector in the control box[Method "B"). (AP-Z728FA1[P08AH SF1])
1 2 3
"A"
To outdoor unit AP-Z286RC0[P03AH SR0] AP-Z488TC0[P05AH ST0]
7. Close the inlet grille.
Bushing rubber Knock-out holes
Floor Standing
29
Installation
5CSP0-02A
14.3.2 Connection cable to outdoor unit The unit is completely wired internally at the factory according to general rule of electrical technology, but local rules, if they are required, should be complied with.
1. Power supply Power source must fulfill the following conditions: • The working voltage should be higher than 90% and lower than 110% of the rated voltage marked on the name plate.
Voltage Power source voltage working voltage Starting voltage Starting point Time
• The starting voltage should be higher than 85% of the rated voltage marked on the name plate.
2. Wiring After the confirmation of the above conditions, prepare the wiring as follows: • Use the power supply cord(Rubber insulation, type Ho7RNF approved by HAR or SAA) suitable for the product's electriccal capacity.
H/P
450/750V
Conductor cross-sectional area 2.5mm2
C/O
450/750V
2.5mm2
H/P
450/750V
4.0mm2
C/O
450/750V
4.0mm2
H/P
450/750V
5.5mm2
C/O
450/750V
5.5mm2
UNIT 28k 48k 72k
VOLTS
• See to it that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
• Provide a recognized circuit breaker as below between power source and unit. A disconnection device to adequately disconnect all supply lines must be fitted. (for service operations) UNIT 28k 48k 72k
30
• The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
• The following troubles would be caused by voltage drop-down. Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
Circuit breaker capacity H/P
30A
C/O
30A
H/P
30A
C/O
30A
H/P
30A
C/O
30A
Floor Standing
5CSP0-02A
Installation
14.4 Checking the Drainage and Form the Piping 14.4.1 Checking the Drainage 1. Remove the inlet grille with your hands as shown (right and left) and pull in the direction indicated by the arrow.
2. Check the drainage • Pour a glass of water into the drain pan. • Ensure if water flows drain hose of indoor unit.
Floor Standing
31
Installation
5CSP0-02A
14.4.2 Form the Piping 1. Wrap the connecting portion of indoor unit with the insulation material and secure it with two Plastic Bands. (for the right piping) • If you connect an additional drain hose, the end of the drain-outlet should be kept distance from the ground. (Do not dip it into water, and fix it on the wall to avoid swinging in the wind.)
Gas side piping Main cable
In case of the outdoor unit is installed below position of the indoor unit. 2. Tape the Piping, and Connecting Cable from down to up.
Tube PE Foam Connecting Cable Connecting Cable (For heater)
3. Form the piping gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent.
Trap is required to prevent the electrical parts from entering the water.
In case of the outdoor unit is installed upper position of the indoor unit.
Seal a small opening around the piping with gum type sealer.
1. Tape the piping and connecting cable from down to up.
Trap
2. In order to prevent water from entering the room, form a trap and tape the piping. 3. Fix the piping onto the wall with saddle or bracket.
Trap
Drain water treatment of outdoor unit(Heat Pump Only) 1. When using the drain elbow hose, use a mount of 3cm of higher. 2. In the cold district (0°c continued for 2~3 day), the drain water is frozen and the fan fail to function, do not use the drain elbow.
Drain elbow Hose(inner diameter ø20) Arrange the hose downward slope without waving.
32
Floor Standing
5CSP0-02A
Installation
14.5 The Method of duct Installation(Only 72k Btu/h model) The Method of Duct Installation (Only 72k Model) Heater Switch
1. First of all, turn ON Duct switch of Main PCB. Duct Switch
ON
2. After removing upper side chamber, connect the duct to the barrier blower directly.
OFF
ON
OFF
(MICOM)
FUSE(250V 3A)
Main PCB
CORRECT INSTALLATION
Outlet Air Duct Barrier Blower
Blower Intake Air
Floor Standing
33
Function of Remote Control
5CSP0-02A
15. Function of Remote Control Model No.: AP-Z286RC0[P03AH SR0]
2 4
1
1. Signal Transmitter • Transmits the signals to the Floor Standing Type air conditioner
15
2. Operation Display of the Remote Control
9
3. Timer Set Button • Each time the button is pressed, the mode is changed in the following process. Timer set (1, 2, 3, 4, 5, 6, 7 hours) If you select “0:00” the off Timer function will be canceled.
A/CL
3
10
5
11 6
TURBO-Z
4. Plasma Airfurifying Button
7
12
8
13 14
(Heat pump Model)
5. Auto Airflow Direction Control Button • The holizontal louvers swing up and down. 6. Auto Airflow Direction Control Button • The vertical louvers swings left and right. 7. Turbo-Z Cooling Operation Button
1
8. Indoor Fan Speed Selection Button • To select the desired fan speed in two steps [Low, Mid, High]
9
9. Cooling ON Button
3
10
10. Heating Button (Heat Pump Model Only) Auto Operation Button (Cooling Model Only)
5
11
2 4
A/CL
TURBO-Z
6
7
12
8
13 14
11. Soft Dry Operation Button 12. Energy Saving Operation Button(Cooling Model Only) 13. Power ON/OFF Button • Operation will start when this button is pressed, and stop when the button is pressed again. 14. Temperature Setting Buttons
(Cooling Model)
15. Electric Heater ON/OFF Button(Heat Pump & Electric Heater Product Only)
Wireless Remote Control Puts all functions at your fingertips Handling the remote control • Aim at the signal receptor on the floor standing type air conditioner when operating. • The remote control signal can be received at a distance of up to about 7meters. • Be sure that there are no obstructions between the remote control and the signal receptor. • Do not drop or throw the remote control. • Do not place the remote control in a location exposed to direct sunlight, or next to a heating unit, or other heat source.
34
Floor Standing
5CSP0-02A
Function of Remote Control
Model No.: AP-Z488TC0[P05AH ST0] 1 16
2
4
11 A/CL
12
10
7
13
1. Signal Transmitter • Transmits the signals to the floor standing type air conditioner 2. Operation Display of the Remote Control 3. Indoor Fan Speed Selection Button • To select the desired fan speed in two steps [Low, Mid] 4. Cooling ON Button
8 14
17
3
6
11
6. Power ON/OFF Button • Operation will start when this button is pressed, and stop when the button is pressed again.
5
7. Auto Airfloor Direction Control Button (No application) • The horizontal louvers swing up and down.
1
8. Auto Airflow Direction Control Button • The vertical louvers swing left and right.
16
9. Auto Mode Operation Button (Cooling Model Only)
(Heat pump Model)
2
5. Temperature Setting Buttons
4
10. Heating Button (Heat Pump Model) 11. Plasma Air purifying Button
A/CL
12
9
10
13
14
15
12. Timer Set Button • Each time the button is pressed, the mode is changed in the following process. Time set (1, 2, 3, 4, 5, 6, 7 hours) If you select "0" the off Timer function will be cancelled.
3
6
13. Soft Dry Operation Button
5
14. JET Cool Operation Button
8
15. Auto Air Flow Operation Button 16. Electric heater On/OFF Button(Heat pump & Electric heater product only) 17. ENERGY Saving Operation Button(No application)
(Cooling Model)
Wireless Remote Control Puts all functions at your fingertips Handling the remote control • Aim at the signal receptor on the floor standing type air conditioner when operating. • The remote control signal can be received at a distance of up to about 7meters. • Be sure that there are no obstructions between the remote control and the signal receptor. • Do not drop or throw the remote control. • Do not place the remote control in a location exposed to direct sunlight, or next to a heating unit, or other heat source.
Floor Standing
35
Function of Remote Control
5CSP0-02A
Model No.: AP-Z728FA1[P08AH SF1] 1 16
2 11
4
12
10
7
13
1. Signal Transmitter • Transmits the signals to the floor standing type air conditioner 2. Operation Display of the Remote Control 3. Indoor Fan Speed Selection Button • To select the desired fan speed in two steps [Low, High] 4. Cooling ON Button
8 14
15
3
6
5. Temperature Setting Buttons 6. Power ON/OFF Button • Operation will start when this button is pressed, and stop when the button is pressed again.
5
7. Auto Airfloor Direction Control Button (No application) • The horizontal louvers swing up and down.
1
8. Auto Airflow Direction Control Button(No application) • The vertical louvers swing left and right.
(Heat pump Model)
9. Auto Mode Operation Button (Cooling Model Only) 2 11
16
10
10. Heating Button (Heat Pump Model) 11. Indoor Fan Operation Button
A/CL
17
12
4
12. Timer Set Button • Each time the button is pressed, the mode is changed in the following process. Time set (1, 2, 3, 4, 5, 6, 7 hours) If you select "0:00" the off Timer function will be cancelled.
3
6
13. Soft Dry Operation Button
5
14. Duct Operation Button
8
9 13
15. ENERGY Saving Operation Button(No application) 16. Electric heater On/OFF Button(Heat pump & Electric heater product only) 17. Plasma Air purifying Button(No application)
(Cooling Model)
Wireless Remote Control Puts all functions at your fingertips Handling the remote control • Aim at the signal receptor on the floor standing type air conditioner when operating. • The remote control signal can be received at a distance of up to about 7meters. • Be sure that there are no obstructions between the remote control and the signal receptor. • Do not drop or throw the remote control. • Do not place the remote control in a location exposed to direct sunlight, or next to a heating unit, or other heat source.
36
Floor Standing
P/No.: 3828A20428C
Air Conditioner 20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com
All rights reserved Printed in Korea April/2009 The specifications, designs, and information in this brochure are subject to change without notice.
File No. : A8974 Volume:1
Certificate No. : E00626/1
The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.