MW400S
400 Watts Output Power ACTIVE POWER FACTOR CORRECTION & ISOLATED DC OUTPUT MODULE
HOW TO ORDER
FEATURES
400 - S
MW
M / 28 - I
Series
I - M3 inserts
Total Output Power(W) Single Output Unscreened (I) or Screened(M) Output Voltage
INPUT CHARACTERISTICS Min. 90 Input Voltage (Single Phase) 47 Input Frequency Range 120 Input Voltage DC Inrush Current @115 Vrms @240 Vrms Input Filter Capacitance Power factor @ 400W Output Power 0.98 115Vin / 60Hz 0.94 115Vin / 400Hz 0.95 230Vin / 50Hz Efficiency at Full Load 28Vout, 115Vin / 60Hz 28Vout, 115Vin / 400Hz 28Vout, 230Vin / 50Hz 5Vout, 115Vin / 60Hz 5Vout, 115Vin / 400Hz 5Vout, 230Vin / 50Hz No Load Input Current No Load Input Power Input Power, Output Disabled Input Undervoltage Shutdown Input Undervoltage Hystersis
Typ.
Max. Units 265 Vac 440 Hz 380 Vdc 20 28
3.1
A A μF
0.99 0.95 0.97 81 80 82 78 77 80 .55 60 13 89 6
% % % % % % Arms W W Vac Vac
• Meets Harmonic Requirements of MIL - STD - 1399 • Meets CE101 and CE102 of MIL - STD - 461 (No external filter required) • Meets MIL standards: MIL - STD - 704E and MIL - STD - 810 • Non-latching Over Temperature Protection • Latching Output Overvoltage Protection • Isolated Input AC Good TTL Signal • Isolated Output DC Good TTL Signal • Isolated 13 VDC Standby Output • Fully rated 400 Watts of output power from 90 VAC to 265 VAC and up to 100°C baseplate temperature • Utilizes non isolated boost topology followed by isolated DC-DC converter • Environmental Screening available • Fixed frequency PFC and DC-DC converters synchronized at 240/480 kHz or to a 500 - 550 kHz external clock • 385 VDC PFC High Voltage Bus is accessible at the input connector
SELECTION CHART Nominal Output Voltage (Volts) 2 3.3 5 12 15 24 28
Output Current (Amps) 100 100 80 33.3 26.7 16.7 14.3
Model Number (Unscreened) MW400SI/2 MW400SI/3.3 MW400SI/5 MW400SI/12 MW400SI/15 MW400SI/24 MW400SI/28
Model Number (Screened) MW400SM/2 MW400SM/3.3 MW400SM/5 MW400SM/12 MW400SM/15 MW400SM/24 MW400SM/28
All specifications are typical @+25°C with nominal input voltage under full output load conditions, unless otherwise noted. Specifications subject to change without notice.
>> 2
1111 Knox Street
Torrance
CA 90502
USA
Tel: +1 310 202 8820
[email protected]
www.martekpower.com MW400S Active Power Factor Correction & Isolated Output Module OUTPUT CHARACTERISTICS
PFC HIGH VOLTAGE BUS CHARACTERISTICS Nominal / Voltage Internal Holdup Capacitance External Holdup Capacitance (customer supplied) Min. Output Holdup Voltage Output Holdup Time
Min. 375
Typ. 385 200
0 190 24
20
Max. Units 390 Vdc μF 600 μF 200
Vdc mS
CONTROLS INTERFACE CHARACTERISTICS Referenced to floating Signal Ground
Min. TTL Logic Disable Current TTL Logic Disable Voltage Sync Input Voltage Sync Input Frequency Sync Input Duty (High) Sync Output Voltage Status “OK” Status “Bad” @ 2mA AC OK Threshold AC “Bad” Response Time Output OK Threshold Turn-on Overshoot Standby 13V Standby 13V Load 1
Typ. 135
0 4.5 500 15 4 4.4 0 88
90 8 ±7
±5 12 0
Max. Units 150 μA 0.8 V 5.1 Vp-p 550 kHz 55 % 5 Vp-p 5 V 0.8 Vdc 95 Vac 10 mS ±9 %Vout 1501 mV V 15 mA 15
150mV or 3% Vout, whichever is greater.
Min. Typ. Max. Units Set Point Accuracy 501 mV Load Regulation 25/0.52 mV/% Line Regulation 5/0.1 20/0.23 mV/% Ripple P-P (10 MHz) 60 100/14 mV/% Overvoltage Protection 2 - 5 Vout 125/0.75 %/Vout 12 - 28 Vout 125 %/Vout Transient Response Time - Overshoot 20 - 80% Load (@Nom.Line) 200/100 500/2506 μS/mV 115 - 180Vac per MIL-STD-704A 500/2506 μS/mV 102 - 124Vac per MIL-STD-704A 500/2506 μS/mV 92 - 138Vac per MIL-STD-1299 500/2506 μS/mV 163 - 281Vac, 50 Hz 500/2506 μS/mV 240 - 350Vdc per MIL-STD-704E 500/2506 μS/mV 50 - 100% Load (@Nom.Line) 200/100 500/2506 μS/mV Temperature Drift 0.02 0.05 %/oC Long Term Drift 0.02 0.05 %/1KHrs Current Limit 110 125 140 %/Iout Short Circuit Current 25 50 75 %/Iout Load Capacitance 2007 μF Remote Sense Compensation 0.5/108 Vdc/% Trim Range 90 110 %/Vout Turn On Time 260 300 mS Logic Turn On Time 8 10 mS 1 2 3 4 5 6 7 8
ISOLATION CHARACTERISTICS
TEMPERATURE CHARACTERISTICS Operating1 Storage - Ambient Over Temperature Shutdown2 1
2
Min. -40 -55
Typ. +106
or 1% maximum, whichever is greater whichever is greater from No Load to Full Load with line constant whichever is greater from Low Line to High Line at Full Load whichever is greater measured at 10 MHz Bandwidth or 0.7V maximum, whichever is greater or 5% maximum, whichever is greater or 3X Co, whichever is greater lesser of 10% of Vout or 0.5V
Max. Units o +100 C o +125 C o +115 C
Start-up guaranteed to -55oC Measured at baseplate (center line of output connector x center line of baseplate)
Isolation Input to Case Input to Output Input to Signal Ground Output to Case Signal Ground to Output to Case Insulation Resistance @ 50Vdc
Min.
Units
1000 1000 1000 250 250 50
Vdc Vdc Vdc Vdc Vdc Mohm
All specifications are typical @+25°C with nominal input voltage under full output load conditions, unless otherwise noted. Specifications subject to change without notice.
>> 3
1111 Knox Street
Torrance
CA 90502
USA
Tel: +1 310 202 8820
[email protected]
www.martekpower.com MECHANICAL CHARACTERISTICS
M-GRADE - ENVIRONMENTAL SCREENING Stabilization Bake Temperature Cycling Burn in Final Testing MTBF @ 50oC, GB
Weight
+105oC for 24 hours similar to MIL-STD883, M1008.2, Condition B 10 cycles at -55oC to +105oC (transition period 5oC/ min) similar to MIL-STD-883, M1010, Condition B 150 Hours at 85oC min. Full ATP 144,830 Hours
Size Volume Material Case Baseplate Finish Case Baseplate Mounting Standard Option - I
I-GRADE - ENVIRONMENTAL SCREENING Burn in Final Testing MTBF @ 50oC, GB
43.3 1230 6.5 x 8.0 x 1.00 165 x 203 x 25.4 52.0 852
16 Hours @ 50oC min. Full ATP 71,330 Hours
oz. grams inch mm inch3 cm3
Steel, 0.024” Aluminum Alloy Nickel Plated None 6-32 THD Inserts Metric M3 X 0.5
CASE DRAWING TOP VIEW
MOUNTING HOLE 6-32 UNC X .30/7.6 DEEP 9 places
BOTTOM VIEW
6.000/ 152.4 6.50/ 165.1
3.000 /76.2
.25/ 6.3
.25/6.3 MAX 2.40/ 60.9
7.500/190.50
3.40/86.3
Socket A1
.550/ 13.97
Output Connector J2 FUNCTION PIN No. - Output A1, A2, A3 + Output A5, A6, A7 Not Used A4 Out OK 5 13V STBY15mA 1 Signal Gnd 14, 15 + Sense 10 - Sense 9 TTL 3 Sync 17 Trim 7 AC OK 12 2, 4, 6, 8, 11, 13, 16 Not Used
PIN 1 1.00/25.4
Socket 1
J1 INPUT CONNECTOR DAMME15PF - A101
.25/6.3
3.750/95.25
8.00/203.2
J2 OUTPUT CONNECTOR DDME24H7SJ .040/ 1.03
Input Connector J1 PIN No. FUNCTION 1, 9 AC1 3, 10 AC2 8, 15 Chas Gnd 6 Ext. Cap (+) 5 Ext. Cap (-) 2, 4, 7, 11, 12, 13,14 Not Used Tolerances: inches
-
x.xx x.xxx
= ±0.03 = ±0.015
mm
- x.x x.xx
= ±0.8 = ±0.40
All specifications are typical @+25°C with nominal input voltage under full output load conditions, unless otherwise noted. Specifications subject to change without notice.
>> 4
1111 Knox Street
Torrance
CA 90502
USA
Tel: +1 310 202 8820
[email protected]
www.martekpower.com MW400S Active Power Factor Correction & Isolated Output Module PERFORMANCE CHARACTERISTICS 1. Power Factor vs. Input Voltage
2. Power Factor vs. Output Power
1.0
85%
50 Hz
60Hz 115Vac
Power Factor
60 Hz
.96 .94
At 400 W Load
.92
50Hz 230Vac
5V 80%
400Hz 115Vac
0.90 0.85
24V
12V 3.3V
75%
Full Load
0.80
400 Hz
70%
.90
2V
0.75
.88
0.70 90
115
136
180
230
265
65% 100
200
4. Efficiency vs. Output Power 85%
300
400
90
115
136
180
Output Power (watts)
Input Voltage (rms)
230
265
Input Voltage (rms) 6. Output Ripple (5Vout)
5. AC Input Voltage & Current
28V 24V
Input Current 12V
100 mV/div
5V
3.3V
5A/div
15V
80%
75%
Vin = 115 Vac/60Hz
70%
50 V/div
Efficiency
15V
28V
0.95
Efficiency
.98
Power Factor
3. Efficiency vs. Input Voltage
1.00
2V
Vin = 115 Vac/60Hz, Full Load
Vin = 115 Vac/60Hz, Full Load
Input Voltage
65% 100
150
200
250
300
350
400
Time: 5 mS/div
Output Power (watts)
7. Load Transient Response (5Vout)
Time: 5μS/div
8. Line Transient (60 Hz), no response at output
9. Line Transient (400 Hz), no response at output Low Line to High Line 115 V - 180 Vac, 400Hz, Full Load 200 V/div 50 V/div
Input Voltage
50 V/div
100 mV/div
100 V/div
Low Line to High Line 92 V - 138 Vac, 60Hz, Full Load
Vin = 115 Vac/60Hz, 20% to 80% of Full Load
380V Bus Voltage
380V Bus Voltage Time: 100 mS/div
Time: 100μS/div
10. Line Transient (50 Hz), no response at output
200 V/div
100 V/div
Vin = 115 Vac/60Hz, Full Load
Time: 100 mS/div
10 A/div
Input Current
5V/div
10 A/div
200 V/div
Input Voltage
Input Current
380V Bus Voltage 50 V/div
12. Turn-on Input Voltage & Input Current vs. Output Voltage
11. Inrush Current vs. Intermediate Bus
Low Line to High Line 163 V281 Vac, 50Hz, Full Load
380V Bus Voltage
Time: 100 mS/div
Output Voltage
Time: 100 mS/div
Vin = 115 Vac/60Hz, Full Load Time: 50 mS/div
>> 5
1111 Knox Street
Torrance
CA 90502
USA
Tel: +1 310 202 8820
[email protected]
www.martekpower.com MW400S Active Power Factor Correction & Isolated Output Module PERFORMANCE CHARACTERISTICS 13. Turn-on Input Voltage & Input Current vs. Output Voltage
15. TTL Turn-Off
14. TTL Turn-On
Output Voltage
5 V/div
5 V/div
Output OK
5 V/div
Vin = 230 Vac/50Hz, Full Load
Output Voltage
Output Voltage
Vin = 115 Vac/60Hz, Full Load
Time: 50 mS/div
Output OK
5 V/div
10 A/div 5 V/div
Input Current
TTL
5 V/div
TTL
5 V/div
400 V/div
Input Voltage
Vin = 115 Vac/60Hz, Full Load Time: 500 μS/div
Time: 5 mS/div
16. Input Voltage Turn-Off vs. Output Voltage
18. Input Voltage Turn-On vs. AC OK
17. Input Voltage Turn-Off vs. AC OK
Input Voltage
100 V/div
Output Voltage
100 V/div
100 V/div
Input Voltage
5 V/div
Vin = 115 Vac/60Hz, Full Load Input Voltage
AC OK
Vin = 115 Vac/60Hz, Full Load
AC OK
5 V/div
5 V/div
Vin = 115 Vac/60Hz, Full Load
Time: 10mS/div
Time: 5 mS/div
Time: 10 mS/div
19. Free-running Sync Output
20. Output Converter Voltage Loop Gain & Phase (5Vout)
21. Output Converter Voltage Loop Gain & Phase (28Vout)
db
db
50
150o
PHASE
150o
50
1 V/div
PHASE
0
0
Vin = 115 Vac/60Hz, No Load
GAIN
-150o
-50
100Hz
Time: 500 nS/div
1kHz
10kHz
100kHz
22. MIL-STD-461D CE101-4
dBμV
100
dBμA
-150o
-50
100Hz
1kHz
80 60
0.00001
Vin = 115 Vac/60Hz, Full Load
80 70 60 50
0.001
0.01
0.01
0.1
Torrance
1 MHz
MHz
1111 Knox Street
100kHz
40 30 20 10 0
Vin = 115 Vac/60Hz, Full Load 0.00003
10kHz
23. MIL-STD-461D CE102-1
120
20
GAIN
110 100 90
140
40
0
0
CA 90502
USA
Tel: +1 310 202 8820
10
>> 6
[email protected]
www.martekpower.com MW400S Active Power Factor Correction & Isolated Output Module
18 V
PFC BOOST CONTROLS
+380 VDC
ISOLATED HOUSEKEEPING SUPPLY
INPUT 18 V UNDERVOLTAGE LOCKOUT & AC OK INDICATION 14 V 18 V
SYNC 2
ENA POWER UP TIME DELAY
OPTO
SYNC 2 SYNC 1
BOOST OVERVOLTAGE DISABLE
VCC 1
C113 -
- OUT - SENSE TRIM
OPTO
18 V
XMFR
BIDIRECTIONAL SYNC VCC3 CIRCUIT SIGNAL GND XMFR
SYNC
BOOST RTN SDN
+380 VDC
VCC 2
380V PFC HIGH VOLTAGE BUS DC OK CIRCUIT
OPTO
DC OK RTN 2 VCC 2
14 V LIMITER
RTN 2 VCC 3
}
S+ S-
PHASE SHIFT CONTROLS
SYNC 1
POST FILTER
OUTPUT CONNECTOR
GATE DRIVE
FILTER
+SENSE +OUT
VCC 2A 13 V
OUTPUT SHUTDOWN LOGIC FOR: DC OK, TTL, OUTPUT OVER VOLTAGE, OVER TEMPERATURE, & OUTPUT OK INDICATION OUTPUT OK
OPTO
14 V
TTL
OPTO
SYNC AC OK
SIGNAL GND
}
13V STANDBY OVERCURRENT PROTECTION CIRCUIT
OUPUT CONNECTOR
14 V
VDC RTN
SOFT START
RTN 2
BOOST RTN
-
CS 2
RS
AC B
ISOLATED FULL BRIDGE
BOOST CONVERTER
GATE DRIVE
EMI FILTER
AVERAGE CURRENT
+380 VDC
+
VCC 2A
AC 2
AC A
}
-
CS 1
AC 1
+
EXT. CAP. + INPUT CONNECTOR EXT. CAP. -
C113 +
BRIDGE RECTIFIER
FOR OUTPUTS >= 12V ACTIVE PRELOAD
VCC 2A
COMMON MODE BEAD
SDN
}
CHASSIS
SCR GATE
INPUT CONNECTOR
BLOCK DIAGRAM OF MW400S
SIGNAL GND
All specifications are typical @+25°C with nominal input voltage under full output load conditions, unless otherwise noted. Specifications subject to change without notice.
>> 7
1111 Knox Street
Torrance
CA 90502
USA
Tel: +1 310 202 8820
[email protected]