FC721 Fire control panel

FC721 Cerberus™ PRO Fire control panel Series FS720 (IP5)  Compact, prefabricated, microprocessor-controlled fire control panel for the connection...
15 downloads 0 Views 2MB Size
FC721

Cerberus™ PRO

Fire control panel Series FS720 (IP5)  Compact, prefabricated, microprocessor-controlled fire control panel for the

connection of up to 126 addresses

 Fire control panel can be used as stand-alone version  Integrated emergency operation function

 Fast Ethernet interface for remote control service  Integrated user-friendly operating unit  Optional key switch

 Slot for a RS232 or a RS485 serial port

 Emergency power supply for up to 72 h emergency power time

 Detection and automatic read-in (auto configuration) of all C-NET devices,

providing immediate simple operation

 Processes signals from the Cerberus PRO FD720 detector series

 Floor repeater displays, operating panels and alarm devices in the detector

loop (C-NET)  Flexible programming of complex applications and controls  Stored data can be uploaded via remote access  Firmware download of all processor controlled control panel components

Building Technologies CPS Fire Safety

System overview Remote access Engineering Tool, Operating Tool

FC721

Fire control panel

FDM233-Ex Explosionhazard area OOH740-A9-Ex

Detection line collective Siemens, TM Synova SynoLINE300 or SynoLINE600

RT- Alarm RT-Fault

24VDC ext. FDS221/ FDS229

Fire controls

FDCI222

FDCL221-Ex

FDCIO223

2 in-/outputs optionally

FT2010/FT2011

Floor repeater terminal/ Floor repeater display

4 inputs DBS721 / DBS729

C-NET

HI720

OH720

1 loop max. 126 addresses

DBS720 HI722 24VDC ext. possible

stub line

Mimic display FT2001-A1

OP720 OP720

FDA221/ FDA241

1 output

FDCW241 4 outputs

FDM22x

Conventional horn line via FCI2009-A1

FDCIO221

OH720

FDCI723

FDCL221

FDCI221

FDM221 FDCIO222 4 inputs

1 input

1 input

FDOOT271 FDM273 Radio detectors

Characteristics – The FC721 is a compact fire control panel with an integrated operating unit that can process signals from FD720 devices. – The control panel can be programmed with the user-friendly Cerberus-EngineeringTool. – All detector lines are monitored for ground faults. – Adaptation of the user text directly on the terminal or with the software engineering tool. – Up to 2000 events can be stored according to various criteria. – Automatic summer/winter time change.

2 Building Technologies Fire Safety & Security Products

Functional elements Operating unit The following are located on the operating unit: – CPU module and the electronics for the operating unit – Ethernet connection – Slots for RS232, RS485 modules – Space for 'Kaba' or 'Nordic' key switch Periphery board The following are located on the periphery board: – Connection terminals for C-NET loops, remote transmission (alarm, fault), horn output, programmable control inputs/outputs, monitored alarm and fault output, degrade supply, power supply Power supply 70 W, emergency power supply The power supply supplies the hardware and charges the batteries – The batteries supply the emergency power in case of power failure Configuration The FXS7212 Cerberus-Engineering-Tool permits the system to be adapted to specific customers' requirements. Application ranges The FC721 is ideally suited for smaller applications, e. g. in workshops, hotels, etc.

3 Building Technologies CPS Fire Safety

Display and operating elements  Each control panel has an integrated operating unit.

1

2 3 4 5 6 7 8 9 10 11 12 13 14

4 Building Technologies Fire Safety & Security Products

Large-format, backlit plain text display (LCD 256 x 112 dots) with detailed plain text information for all events that occur – Event type, event location, reaction texts, operating status, etc. – Operator guidance texts are displayed directly in alarm situations – Convenient operation via soft keys and navigation key Alarm indicator lights red when an alarm even is received 4 programmable LEDs and div. display fields Soft keys for direct menu operation 2 operation keys with LEDs, individually programmable Keys –> 'Buzzer off', 'Acknowledge' message and 'Reset' message Key for scrolling through the alarm messages Navigation and menu key for the display Keypad for numerical and alphanumeric entries such as password, customer text, etc. Function keys for alarm organization Display and key field for alarming equipment Optional key switch for operating access (Kaba or Nordic) Label strips inserts. With 24 indicator groups with each one red + yellow LED

Overview of FC721 fire control panels Housing (Eco) FC721-ZZ

FC721-YZ

With 24 indicator groups with each one red + yellow LED

1 Loop With power supply (70 W) Battery capacity max. 7 Ah

1 Loop With power supply (70 W) Battery capacity max. 7 Ah

Expansion FH7201-Z3

FH7202-Z3

Housing (Eco) 430 x 398 x 80 mm

Housing (Standard) 430 x 398 x 160 mm

Empty housing For various applications e. g. for event printer

Empty housing For various applications e. g. for additional power supply Space for batteries 2 x FA2004-A1 (12 Ah) or 2 x FA2006-A1 (26 Ah) + Power supply kit (150 W)

Internal printer FTO2001-A1

External printer DL3750+

Event printer

installable in empty housings RS232 module must be ordered separately

Matrix printer (Extern) RS232 interface

RS232 module must be ordered separately

5 Building Technologies CPS Fire Safety

Configuration FC721

11

4

7 1

2

12 5

9

3

6 10

Basic equipment 1 Rear (Eco) 2 Periphery board (1-Loop) 3 Power supply (70 W) Power supply (70 W) 4 Mains terminals on DIN mounting rail TS35 5 Operating unit 6 Space for batteries Expansion 7 Relay module Key switch (Kaba) 8 Key switch (Nordic) RS485 module (isolated) or 9 RS232 module(isolated) 10 Battery (12V, 7Ah, VDS) 11 19" mounting kit 12 Cable kit (communication)

6 Building Technologies Fire Safety & Security Products

8

Designation FHA2001-A1 FCI2010-A1 FP2001-A1 FP2015-A1 – FCM7xx-xx –

Notes

Z3B171 FTO2005-C1 FTO2006-B1 FCA2002-A1 FCA2001-A1 FA2003-A1 FHA2016-A1 FCA2014-A1

Relay for fire controls

Pos. 1-5 –> Basic equipment for each FC721 (Eco) Space for 2 relay modules Combined system operating panel and CPU, incl. cover 2 x 12 V / 7 Ah

For operating access rights For peripheral devices with RS485 port For stations with RS232 port For emergency power supply For the installation in 3rd party housings For flexible cable connections to the modules on the operating unit

Technical data Mains voltage Power supply Operating voltage Operating current Battery capacity Battery monitoring Mains monitoring Connectable detector series Number of lines – Loop or – Stub lines Number of addresses Integrated inputs/outputs – Relay output – RT alarm – RT fault – Monitored outputs – Alarm – Fault – Horn – Free programmable inputs/outputs Operating unit Plug-in position for serial interfaces RS232, RS485 Mounting place for cable kit (communication) Ethernet connection RJ45 Operating temperature Storage temperature Humidity (no condensation permitted) Dimensions (W x H x D) – Without cover cap – With cover cap Color – Housing – Cover Protection category (IEC 60529) Standards Approvals – LPCB – FM

AC 97…127 V / AC 196…253 V 70 W DC 21…28.6 V max. 2.5 A 2 x 12 V, 7 Ah yes yes Cerberus PRO FD720 (C-NET) 1 2 max. 126

1 1 1 1 1 4 integrated 1 1 1 -8…+42 °C -20…+60 °C ≤95 % rel. 430 x 398 x 80 mm 430 x 398 x 108 mm grey, ~RAL 7035 grey, ~RAL-Design 000 50 00 IP30 EN 54-2, EN 54-4 126bn/05 approved

7 Building Technologies CPS Fire Safety

Details for ordering Type FC721-ZZ FC721-YZ Expansion Z3B171 FTO2001-A1 – FTO2005-C1 FTO2006-B1 FCA2002-A1 FCA2001-A1 FCA2014-A1 FH7201-Z3 FH7202-Z3 FHA2016-A1 FN2006-A1 FN2007-A1 Additional power supply FP2003-A1 FP2015-A1 FP2004-A1

Part no S54400-C32-A2 S54400-C32-A3 BPZ:4843830001 A5Q00010126 A5Q00017619 A5Q00010113 A5Q00010129 A5Q00009923 A5Q00005327 A5Q00023027 S54400-B72-A101 S54400-B70-A101 A5Q00020179 S54400-A109-A1 S54400-A110-A1 A5Q00016005 S54400-B121-A1 A5Q00020825

Batteries

A5Q00019353 A5Q00019354 A5Q00019356 A5Q00023962 A5Q00023963

Fire control panels

External printer Spare part

FA2003-A1 FA2004-A1 FA2006-A1 DL3750+ –

Siemens Switzerland Ltd Infrastructure & Cities Sector Building Technologies Division International Headquarters CPS Fire Safety Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724 24 24 www.siemens.com/buildingtechnologies Document no.

A6V10203220_g_en_--

Edition

06.2014

Designation Fire control panel (1L) Fire control panel (1L, 1LED) Relay module 250 VAC / 10 A (1 relay) Event printer Replacement printer rolls (10 rolls) Key switch (Kaba) Key switch (Nordic) RS485 module (isolated) RS232 module (isolated) Cable kit (communication) Housing (Eco) Housing (Standard) 19" mounting kit Fiber network module (SM) Fiber network module (MM) Power supply kit (70 W) Power supply (70 W) Power supply kit (150 W) for installation in empty housing Battery (12 V, 7 Ah, VDS) Battery (12 V, 12 Ah, VDS) Battery (12 V, 26 Ah, VDS) Matrix printer (Extern) Black typewriter ribbon for matrix printer DL3750+

Weight 8.900 kg 9.000 kg 0.042 kg 0.250 kg 0.090 kg 0.013 kg 0.050 kg 0.067 kg 0.068 kg 0.224 kg 5.700 kg 7.500 kg 3.000 kg 0.770 kg 0.770 kg 0.650 kg 1,300 kg 1.366 kg 2.450 kg 3.930 kg 7.572 kg 7.300 kg 0.078 kg

© 2014 Copyright by Siemens Switzerland Ltd Data and design subject to change without notice. Supply subject to availability. Manual FS720 Section 1