Failure Modes, Effects and Diagnostic Analysis Project: Transmitter supply unit with limit values type 9162/13–11–*4

Customer: R. STAHL Schaltgeräte GmbH Waldenburg Germany

Contract No.: STAHL 08/04-21 Report No.: STAHL 08/04-21-R020 Version V1, Revision R2, November 2009 Stephan Aschenbrenner, Alexander Dimov

The document was prepared using best effort. The authors make no warranty of any kind and shall not be liable in any event for incidental or consequential damages in connection with the application of the document. © All rights on the format of this technical report reserved.

Management summary This report summarizes the results of the hardware assessment carried out on the transmitter supply unit with limit values type 9162/13–11–*4 in hardware revision B and software version V01-04. Table 1 gives an overview of the different configurations that belong to the considered transmitter supply unit with limit values type 9162/13–11–*4. The hardware assessment consists of a Failure Modes, (FMEDA). A FMEDA is one of the steps taken to achieve device per IEC 61508. From the FMEDA, failure rates are Safe Failure Fraction (SFF) is calculated for the device. requirements of IEC 61508 must be considered.

Effects and Diagnostics Analysis functional safety assessment of a determined and consequently the For full assessment purposes all

Table 1: Configuration overview

Type

Channel

Outputs

Variants

9162/13–11–14

1

4..20 mA current output (HART) and Ex i 2 active closed contacts

9162/13–11–64

1

4..20 mA current output (HART) and non Ex i Output signals active 2 active closed contacts

Output signals active

For safety applications only the described versions are considered. All other possible output variants or electronics are not covered by this report. The failure rates used in this analysis are from the exida Electrical & Mechanical Component Reliability Handbook (see [N2]) for Profile 1. The limit value outputs can be connected in series. Therefore transmitter supply unit with limit values type 9162/13–11–*4 could be split into two separate subsystems; one representing the input and logic part having a hardware fault tolerance of 0 and one representing the output part having a hardware fault tolerance of 1. For simplicity reasons the analysis was done by considering one of the outputs to be the "diagnostics" for the “primary” output. A diagnostic coverage (DC) of 90% was considered to account for possible common cause failures (this is equivalent to a beta factor of 10%). The transmitter supply unit with limit values type 9162/13–11–*4 is considered to be a Type B1 subsystem with a hardware fault tolerance of 0. For Type B subsystems with a hardware fault tolerance of 0 the SFF has to be ≥ 90% for SIL 2 subsystems according to table 2 of IEC 61508-2. It is important to realize that the “no effect” failures and the “annunciation” failures are included in the “safe” failure category according to IEC 61508:2000. Note that these failures on its own will not affect system reliability or safety, and should not be included in spurious trip calculations. It is assumed that the connected safety logic solver is configured as per the NAMUR NE43 signal ranges, i.e. the transmitter supply unit with limit values type 9162/13–11–*4 using the current output communicates detected faults by an alarm output current ≤ 3,6mA or ≥ 21mA. Assuming that the application program in the safety logic solver does not automatically trip on these failures, these failures have been classified as dangerous detected failures. The following tables show how the above stated requirements are fulfilled. 1

Type B subsystem:

“Complex” subsystem (using micro controllers or programmable logic); for details see 7.4.3.1.3 of IEC 61508-2.

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 2 of 5

Table 2: 9162/13–11–*4 with current output

exida Profile 1 2 Failure category

Failure rates (in FIT) 0

Fail Safe Detected (λSD) Fail safe detected

0 259

Fail Safe Undetected (λSU) Fail safe undetected

0

No effect

234

Annunciation undetected (95%)

25 355

Fail Dangerous Detected (λDD) Fail detected (detected by internal diagnostics)

186

Fail low (detected by safety logic solver)

148

Fail high (detected by safety logic solver)

21

Annunciation detected

0 59

Fail Dangerous Undetected (λDU) Fail dangerous undetected

58

Annunciation undetected (5%)

1

No part

180

Total failure rate (safety function)

673 FIT

SFF 3

91.2%

DCD

86%

MTBF SIL AC 4

134 years SIL2

2

For details see Appendix 3. The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 4 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled. 3

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 3 of 5

Table 3: 9162/13–11–*4 with limit value output

exida Profile 1 5 Failure category

Failure rates (in FIT) 0

Fail Safe Detected (λSD) Fail safe detected

0 427

Fail Safe Undetected (λSU) Fail safe undetected

174

No effect

226

Annunciation undetected (95%)

28 184

Fail Dangerous Detected (λDD) Fail detected (detected by internal diagnostics)

184

Fail low (detected by safety logic solver)

0

Fail high (detected by safety logic solver)

0

Annunciation detected

0

6

66

Fail Dangerous Undetected (λDU) Fail dangerous undetected

65

Annunciation undetected (5%)

1

No part

254

Total failure rate (safety function)

678 FIT

SFF 7

90.2%

DCD

74%

MTBF SIL AC 8

123 years SIL2

5

For details see Appendix 3. These failures could also be classified as safe failures as they will immediately lead to a safe state. 7 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 8 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled. 6

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 4 of 5

Table 4: 9162/13–11–*4 with two limit value outputs in series

exida Profile 19 Failure category

Failure rates (in FIT) 0

Fail Safe Detected (λSD) Fail safe detected

0 438

Fail Safe Undetected (λSU) Fail safe undetected

174

No effect

226

Annunciation undetected (95%)

38 196

Fail Dangerous Detected (λDD) Fail detected (detected by internal diagnostics)

196

Fail low (detected by safety logic solver)

0

Fail high (detected by safety logic solver)

0

Annunciation detected

0

10

44

Fail Dangerous Undetected (λDU) Fail dangerous undetected

43

Annunciation undetected (5%)

1

No part

254

Total failure rate (safety function)

678 FIT

SFF 11

93.4%

DCD

81%

MTBF SIL AC 12

123 years SIL2

9

For details see Appendix 3. These failures could also be classified as safe failures as they will immediately lead to a safe state. 11 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 12 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled. 10

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 5 of 5

Table of Contents Management summary....................................................................................................2 1

Purpose and Scope ...................................................................................................7

2

Project management..................................................................................................8 2.1 2.2 2.3 2.4

3

exida...............................................................................................................................8 Roles and Parties............................................................................................................8 Standards / Literature used.............................................................................................8 Reference documents.....................................................................................................8 2.4.1 Documentation provided by the customer............................................................8 2.4.2 Documentation generated by exida.....................................................................9

Description of the analyzed subsystem.................................................................... 10 3.1 Transmitter supply unit with limit values type 9162/13–11–*4 ......................................10

4

Failure Modes, Effects, and Diagnostic Analysis ..................................................... 11 4.1 Description of the failure categories..............................................................................11 4.2 Methodology – FMEDA, Failure rates...........................................................................12 4.2.1 FMEDA...............................................................................................................12 4.2.2 Failure rates .......................................................................................................12 4.2.3 Assumptions.......................................................................................................13 4.3 Results ..........................................................................................................................13 4.3.1 9162/13–11–*4 with current output ....................................................................14 4.3.2 9162/13–11–*4 with limit value output ...............................................................15 4.3.3 9162/13–11–*4 with two limit value outputs in series.........................................16

5

Using the FMEDA results......................................................................................... 17 5.1 Example PFDAVG calculation .........................................................................................17

6

Terms and Definitions .............................................................................................. 18

7

Status of the document ............................................................................................ 19 7.1 Liability ..........................................................................................................................19 7.2 Releases .......................................................................................................................19

Appendix 1: Possibilities to reveal dangerous undetected faults during the proof test .. 20 Appendix 1.1: Possible proof tests to detect dangerous undetected faults..........................22

Appendix 2: Impact of lifetime of critical components on the failure rate ....................... 23 Appendix 3: Description of the considered profiles........................................................ 24 Appendix 3.1: exida electronic database ............................................................................24

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 6 of 24

1 Purpose and Scope This document shall describe the results of the FMEDA carried out on the transmitter supply unit with limit values type 9162/13–11–*4 in hardware revision B and software version V01-04. The FMEDA is one part of the complete functional safety assessment according to IEC 61508. The information in this report can be used to evaluate whether a sensor subsystem, including the transmitter supply unit with limit values type 9162/13–11–*4 meets the average Probability of Failure on Demand (PFDAVG) requirements and the architectural constraints / minimum hardware fault tolerance requirements per IEC 61508. It does not consider any calculations necessary for proving intrinsic safety.

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 7 of 24

2 Project management 2.1 exida exida is one of the world’s leading knowledge companies specializing in automation system safety and availability with over 300 years of cumulative experience in functional safety. Founded by several of the world’s top reliability and safety experts from assessment organizations and manufacturers, exida is a partnership company with offices around the world. exida offers training, coaching, project oriented consulting services, internet based safety engineering tools, detail product assurance and certification analysis and a collection of on-line safety and reliability resources. exida maintains a comprehensive failure rate and failure mode database on process equipment.

2.2 Roles and Parties R. STAHL Schaltgeräte GmbH

Manufacturer of the transmitter supply unit with limit values type 9162/13–11–*4.

exida

Performed the FMEDA together with the customer.

R. STAHL Schaltgeräte GmbH contracted exida in July 2008 with the FMEDA review of the above mentioned device in the listed configurations.

2.3 Standards / Literature used The services delivered by exida were performed based on the following standards / literature. [N1] IEC 61508-2:2000

Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems

[N2] Electrical & Mechanical Component Reliability Handbook, 2nd Edition, 2008

exida L.L.C, Electrical & Mechanical

Component Reliability Handbook, Second Edition, 2008, ISBN 978-0-9727234-6-6

2.4 Reference documents 2.4.1 Documentation provided by the customer [D1] 9162 6 020 002 0_00.pdf of 02.10.09

Circuit diagram “Transmitter Supply Unit type 9162/13-11-**”, 9162 6 020 002 0 of 29.09.09

[D2] B9162_de_en_screen.pdf of 02.07.08

Operating Instructions ID-Nr. 9162 6 031 001 0 S-BA-9162-000-de/en-10/2006

[D3] SAP Stüli 17 09 2009.xlsx of 17.09.09

Parts List

[D4] Pflichtenheft 9162 Rev 2_3 SIL-2.docx of 02.10.09

Requirements specification

[D5] Fehlerversuche_9162_V0R1_Me 01.xls of 12.08.09 and Fehlerversuche an I102.docx of 18.11.09

Fault insertion tests: current output, relay output and 2 relays in series output

[D6] Anpassung der FMEDAS 9162.docx of 18.11.09

Descriptions of FMEDA updates

[D7] FMEDA V7 9162 current output V1R9.efm of 18.11.09 [D8] FMEDA V7 9162 relay output V1R11.efm of 18.11.09 [D9] FMEDA V7 9162 relay outputs in series V1R9.efm of 18.11.09 © exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 8 of 24

2.4.2 Documentation generated by exida [R1] FMEDA V7 9162 current output V1R10.efm of 23.11.09 [R2] FMEDA V7 9162 relay output V1R12.efm of 23.11.09 [R3] FMEDA V7 9162 relay outputs in series V1R10.efm of 23.11.09

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 9 of 24

3 Description of the analyzed subsystem 3.1 Transmitter supply unit with limit values type 9162/13–11–*4 The transmitter supply unit with limit values type 9162/13–11–*4 is used in the operation of 2wire and 3-wire transmitters or to connect to intrinsically safe mA current sources. The 2-wire and 3-wire transmitters are supplied with power by the transmitter power supply unit with limit values. The unit offers two user selectable limit values. If a limit value is exceeded, a potential free, semiconductor relay output is opened. The devices transfer a superimposed HART communications signal bidirectionally. The following Figure 1 shows the principle architecture of the transmitter supply unit with limit values type 9162/13–11–*4.

Figure 1: Block diagram

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 10 of 24

4 Failure Modes, Effects, and Diagnostic Analysis The Failure Modes, Effects, and Diagnostic Analysis was done together with R. STAHL Schaltgeräte GmbH and is documented in [D7], [D8] and [D9]. When the effect of a certain component failure mode could not be analyzed theoretically, the failure modes were introduced on component level and the effects of these failure modes were examined on system level (see fault insertion test report [D5]). This resulted in failures that can be classified according to the following failure categories.

4.1 Description of the failure categories In order to judge the failure behavior of the transmitter supply unit with limit values type 9162/13–11–*4, the following definitions for the failure of the product were considered. Current output: Fail-Safe State Fail Dangerous

Fail High Fail Low No Effect

The fail-safe state is defined as the output exceeding the user defined threshold. Failure that does not respond to a demand from the process (i.e. being unable to go to the defined fail-safe state) or deviates the output current by more than 2% full span. Failure that causes the output signal to go to the maximum output current (> 21 mA) Failure that causes the output signal to go to the minimum output current (< 3.6 mA) Failure of a component that is part of the safety function but that has no effect on the safety function or deviates the output current by not more than 2% full span. For the calculation of the SFF it is treated like a safe undetected failure.

Limit value output: Fail-Safe State Fail Dangerous No Effect

The fail-safe state is defined as the output being de-energized. Failure that does not respond to a demand from the process (i.e. being unable to go to the defined fail-safe state). Failure of a component that is part of the safety function but that has no effect on the safety function. For the calculation of the SFF it is treated like a safe undetected failure.

General failure categories: Fail Safe

Failure that causes the subsystem to go to the defined fail-safe state without a demand from the process. Safe failures are divided into safe detected (SD) and safe undetected (SU) failures. Fail Dangerous Undetected Failure that is dangerous and that is not being diagnosed by internal diagnostics. Fail Dangerous Detected Failure that is dangerous but is detected by internal diagnostics (These failures may be converted to the selected fail-safe state). Annunciation Failure that does not directly impact safety but does impact the ability to detect a future fault (such as a fault in a diagnostic circuit). Annunciation failures are divided into annunciation detected (AD) and annunciation undetected (AU) failures. For the © exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 11 of 24

No Part

calculation of the SFF they are treated to 5% as a dangerous failure and to 95% as a “No Effect” failure. Component that plays no part in implementing the safety function but is part of the circuit diagram and is listed for completeness. When calculating the SFF this failure mode is not taken into account. It is also not part of the total failure rate.

The “No Effect” and “Annunciation Undetected” failures are provided for those who wish to do reliability modeling more detailed than required by IEC 61508. In IEC 61508.2000 the “No Effect” failures are defined as safe undetected failures even though they will not cause the safety function to go to a safe state. Therefore they need to be considered in the Safe Failure Fraction calculation.

4.2 Methodology – FMEDA, Failure rates 4.2.1 FMEDA A Failure Modes and Effects Analysis (FMEA) is a systematic way to identify and evaluate the effects of different component failure modes, to determine what could eliminate or reduce the chance of failure, and to document the system under consideration. An FMEDA (Failure Mode Effect and Diagnostic Analysis) is an FMEA extension. It combines standard FMEA techniques with extensions to identify online diagnostics techniques and the failure modes relevant to safety instrumented system design. It is a technique recommended to generate failure rates for each important category (safe detected, safe undetected, dangerous detected, dangerous undetected, fail high, fail low) in the safety models. The format for the FMEDA is an extension of the standard FMEA format from MIL STD 1629A, Failure Modes and Effects Analysis.

4.2.2 Failure rates The failure rate data used by exida in this FMEDA are from the exida Electrical & Mechanical Component Reliability Handbook for Profile 1. The rates were chosen in a way that is appropriate for safety integrity level verification calculations. The rates were chosen to match operating stress conditions typical of an industrial field environment similar to exida Profile 1. It is expected that the actual number of field failures due to random events will be less than the number predicted by these failure rates. For hardware assessment according to IEC 61508 only random equipment failures are of interest. It is assumed that the equipment has been properly selected for the application and is adequately commissioned such that early life failures (infant mortality) may be excluded from the analysis. Failures caused by external events however should be considered as random failures. Examples of such failures are loss of power or physical abuse. The assumption is also made that the equipment is maintained per the requirements of IEC 61508 or IEC 61511 and therefore a preventative maintenance program is in place to replace equipment before the end of its “useful life”. The user of these numbers is responsible for determining their applicability to any particular environment. Accurate plant specific data may be used for this purpose. If a user has data collected from a good proof test reporting system that indicates higher failure rates, the higher numbers shall be used. Some industrial plant sites have high levels of stress. Under those conditions the failure rate data is adjusted to a higher value to account for the specific conditions of the plant. © exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 12 of 24

4.2.3 Assumptions The following assumptions have been made during the Failure Modes, Effects, and Diagnostic Analysis of the transmitter supply unit with limit values type 9162/13–11–*4. •

Failure rates are constant, wear out mechanisms are not included.



Propagation of failures is not relevant.



The HART protocol is only used for setup, calibration, and diagnostics purposes, not during normal operation.



The device is installed per manufacturer’s instructions.



Failures during parameterization are not considered.



Sufficient tests are performed prior to shipment to verify the absence of vendor and/or manufacturing defects that prevent proper operation of specified functionality to product specifications or cause operation different from the design analyzed.



The Mean Time To Restoration (MTTR) after a safe failure is 24 hours.



The device is locked against unintended operation / modification.



The worst-case internal fault detection time is 20 minutes.



All modules are operated in the low demand mode of operation.



External power supply failure rates are not included.



The time of a connected safety PLC to react on a dangerous detected failure and to bring the process to the safe state is identical to MTTR.



The output signals are either fed to a SIL 2 compliant input board of a safety PLC or are directly used in a SIL 2 safety function.



Only the described versions are used for safety applications.



The application program in the safety logic solver is configured according to NAMUR NE43 to detect under-range and over-range failures and does not automatically trip on these failures; therefore these failures have been classified as dangerous detected failures.



Short circuit and lead breakage detection are activated.

4.3 Results For the calculation of the Safe Failure Fraction (SFF) and λtotal the following has to be noted: λtotal = λSD + λSU + λDD + λDU SFF = 1 – λDU / λtotal DCD = λDD / (λDD + λDU) MTBF = MTTF + MTTR = (1 / (λtotal + λno part)) + 24 h

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 13 of 24

4.3.1 9162/13–11–*4 with current output The FMEDA carried out on the transmitter supply unit with limit values type 9162/13–11–*4 using the 4..20mA current output in a safety function leads under the assumptions described in section 4.2.3 to the following failure rates.

exida Profile 1 13 Failure category

Failure rates (in FIT) 0

Fail Safe Detected (λSD) Fail safe detected

0 259

Fail Safe Undetected (λSU) Fail safe undetected

0

No effect

234

Annunciation undetected (95%)

25 355

Fail Dangerous Detected (λDD) Fail detected (detected by internal diagnostics)

186

Fail low (detected by safety logic solver)

148

Fail high (detected by safety logic solver)

21

Annunciation detected

0 59

Fail Dangerous Undetected (λDU) Fail dangerous undetected

58

Annunciation undetected (5%)

1

No part

180

Total failure rate (safety function)

673 FIT

SFF 14

91.2%

DCD

86%

MTBF SIL AC 15

134 years SIL2

13

For details see Appendix 3. The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 15 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled. 14

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 14 of 24

4.3.2 9162/13–11–*4 with limit value output The FMEDA carried out on the transmitter supply unit with limit values type 9162/13–11–*4 using the limit value output in a safety function leads under the assumptions described in section 4.2.3 to the following failure rates.

exida Profile 1 16 Failure category

Failure rates (in FIT) 0

Fail Safe Detected (λSD) Fail safe detected

0 427

Fail Safe Undetected (λSU) Fail safe undetected

174

No effect

226

Annunciation undetected (95%)

28 184

Fail Dangerous Detected (λDD) Fail detected (detected by internal diagnostics)

184 17

Fail low (detected by safety logic solver)

0

Fail high (detected by safety logic solver)

0

Annunciation detected

0 66

Fail Dangerous Undetected (λDU) Fail dangerous undetected

65

Annunciation undetected (5%)

1

No part

254

Total failure rate (safety function)

678 FIT

SFF 18

90.2%

DCD

74%

MTBF SIL AC 19

123 years SIL2

16

For details see Appendix 3. These failures could also be classified as safe failures as they will immediately lead to a safe state. 18 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 19 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled. 17

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 15 of 24

4.3.3 9162/13–11–*4 with two limit value outputs in series The FMEDA carried out on the transmitter supply unit with limit values type 9162/13–11–*4 using the two limit value outputs in series in a safety function leads under the assumptions described in section 4.2.3 to the following failure rates.

exida Profile 120 Failure category

Failure rates (in FIT) 0

Fail Safe Detected (λSD) Fail safe detected

0 438

Fail Safe Undetected (λSU) Fail safe undetected

174

No effect

226

Annunciation undetected (95%)

38 196

Fail Dangerous Detected (λDD) Fail detected (detected by internal diagnostics)

196 21

Fail low (detected by safety logic solver)

0

Fail high (detected by safety logic solver)

0

Annunciation detected

0 44

Fail Dangerous Undetected (λDU) Fail dangerous undetected

43

Annunciation undetected (5%)

1

No part

254

Total failure rate (safety function)

678 FIT

SFF 22

93.4%

DCD

81%

MTBF SIL AC 23

123 years SIL2

20

For details see Appendix 3. These failures could also be classified as safe failures as they will immediately lead to a safe state. 22 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 23 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled. 21

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 16 of 24

5 Using the FMEDA results The following section describes how to apply the results of the FMEDA. It is the responsibility of the Safety Instrumented Function designer to do calculations for the entire SIF. exida recommends the accurate Markov based exSILentia tool for this purpose. The following results must be considered in combination with PFDAVG values of other devices of a Safety Instrumented Function (SIF) in order to determine suitability for a specific Safety Integrity Level (SIL).

5.1

Example PFDAVG calculation

An average Probability of Failure on Demand (PFDAVG) calculation is performed for a single (1oo1) transmitter supply unit with limit values type 9162/13–11–*4 considering a proof test coverage of 99% (see Appendix 1.1) and a mission time of 10 years. The failure rate data used in this calculation are displayed in sections 4.3.1 to 4.3.3. The resulting PFDAVG values for a variety of proof test intervals are displayed in Table 5. For SIL2 applications, the PFDAVG value needs to be < 1.00E-02. Table 5: PFDAVG values

Configuration

T[Proof] = 1 year

T[Proof] = 2 years

T[Proof] = 5 years

4..20mA current output

PFDAVG = 2,90E-04

PFDAVG = 5,46E-04

PFDAVG =1,31E-03

Limit value output

PFDAVG = 3,20E-04

PFDAVG = 6,06E-04

PFDAVG = 1,46E-03

Limit value outputs in series

PFDAVG = 2,15E-04

PFDAVG = 4,06E-04

PFDAVG = 9,78E-04

This means that for a SIL2 application, the PFDAVG for a 1-year Proof Test Interval considering profile 1 data is approximately equal to 3% of the allowed range. Figure 2 shows the time dependent curve of PFDAVG. PFDAVG vs. Proof Test Interval current output

limit value output

2 limit value outputs in series

3,50E-03 3,00E-03

PFDAVG

2,50E-03 2,00E-03 1,50E-03 1,00E-03 5,00E-04 0,00E+00 1

2

3

4

5

6

7

8

9

10

Years

Figure 2: PFDAVG(t)

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 17 of 24

6 Terms and Definitions DCD

Diagnostic Coverage of dangerous failures (DCD = λdd / (λdd + λdu))

FIT

Failure In Time (1x10-9 failures per hour)

FMEDA

Failure Modes, Effects, and Diagnostic Analysis

HFT

Hardware Fault Tolerance

Low demand mode

Mode, where the frequency of demands for operation made on a safetyrelated system is no greater than one per year and no greater than twice the proof test frequency.

MTTR

Mean Time To Restoration

PFDAVG

Average Probability of Failure on Demand

SFF

Safe Failure Fraction summarizes the fraction of failures, which lead to a safe state and the fraction of failures which will be detected by diagnostic measures and lead to a defined safety action.

SIF

Safety Instrumented Function

SIL

Safety Integrity Level

Type B subsystem

“Complex” subsystem (using micro controllers or programmable logic); for details see 7.4.3.1.3 of IEC 61508-2

T[Proof]

Proof Test Interval

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 18 of 24

7 Status of the document 7.1 Liability exida prepares FMEDA reports based on methods advocated in International standards. Failure rates are obtained from a collection of industrial databases. exida accepts no liability whatsoever for the use of these numbers or for the correctness of the standards on which the general calculation methods are based. Due to future potential changes in the standards, best available information and best practices, the current FMEDA results presented in this report may not be fully consistent with results that would be presented for the identical product at some future time. As a leader in the functional safety market place, exida is actively involved in evolving best practices prior to official release of updated standards so that our reports effectively anticipate any known changes. In addition, most changes are anticipated to be incremental in nature and results reported within the previous three year period should be sufficient for current usage without significant question. Most products also tend to undergo incremental changes over time. If an exida FMEDA has not been updated within the last three years and the exact results are critical to the SIL verification you may wish to contact the product vendor to verify the current validity of the results.

7.2 Releases Version History: V1R2: Software version updated; November 25, 2009 V1R1: Numbers corrected after FMEDA updates; November 23, 2009 V1R0: Review comments incorporated; October 2, 2009 V0R1: Initial version; September 28, 2009 Authors: Stephan Aschenbrenner Review: V0R1: Andreas Bagusch (R. STAHL Schaltgeräte GmbH); October 1, 2009 V0R1: Rachel Amkreutz (exida); September 29, 2009 Release status: Released to R. STAHL Schaltgeräte GmbH as part of a complete functional safety assessment according to IEC 61508.

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 19 of 24

Appendix 1: Possibilities to reveal dangerous undetected faults during the proof test According to section 7.4.3.2.2 f) of IEC 61508-2 proof tests shall be undertaken to reveal dangerous faults which are undetected by diagnostic tests. This means that it is necessary to specify how dangerous undetected faults which have been noted during the FMEDA can be detected during proof testing. Table 6 to Table 8 show an importance analysis of the dangerous undetected faults and indicate how these faults can be detected during proof testing. Appendix 1 shall be considered when writing the safety manual as it contains important safety related information. Table 6: 9162/13–11–*4 with current output Component

% of total λdu

I003, I004

13,19%

I202, I203

13,10%

T003

6,96%

I102

5,85%

W001

3,64%

R031, R032

3,12%

R033, R034

3,12%

R223, R224

3,12%

I001-A

2,56%

I001-B

2,56%

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

Detection through 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 20 of 24

Table 7: 9162/13–11–*4 with limit value output Component

% of total λdu

O201

15,67%

O202

15,67%

I003, I004

11,75%

T003

6,20%

I006

5,90%

I102

5,21%

W001

3,24%

R031, R032

2,78%

R033, R034

2,78%

I001-A

2,28%

Detection through 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal

Table 8: 9162/13–11–*4 with two limit value outputs in series Component

% of total λdu

I003, I004

17,83%

T003

9,41%

I102

7,91%

W001

4,92%

R031, R032

4,22%

R033, R034

4,22%

I001-A

3,46%

I001-B

3,46%

I001-C

3,46%

I001-D

3,46%

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

Detection through 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal 100% functional test with monitoring of the correct output signal

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 21 of 24

Appendix 1.1: Possible proof tests to detect dangerous undetected faults Suggested proof tests consist of the following steps, as described in Table 9 and Table 10. Table 9: Suggested proof test for current output Step 1

Action Bypass the safety function and take appropriate action to avoid a false trip

2

Use HART communications to retrieve any diagnostics and take appropriate action.

3

Send a HART command to the transmitter to go to the high alarm current output and verify that the analog current of the transmitter supply unit reaches that value24.

4

Send a HART command to the transmitter to go to the low alarm current output and verify that the analog current of the transmitter supply unit reaches that value25.

5

Perform a two-point calibration26 of the transmitter and the transmitter supply unit over the full working range.

6

Remove the bypass and otherwise restore normal operation

This test will detect more than 99% of possible “du” failures of the transmitter supply unit with limit values type 9162/13–11–*4. Table 10: Suggested proof test for limit value output Step 1

Action Bypass the safety PLC or take other appropriate action to avoid a false trip.

2

Force the transmitter supply unit with limit values type 9162/13–11–*4 to go to the safe state and verify that the safe state is reached.

3

Restore the loop to full operation.

4

Remove the bypass from the safety PLC or otherwise restore normal operation.

This test will detect more than 99% of possible “du” failures of the transmitter supply unit with limit values type 9162/13–11–*4.

24

This tests for compliance voltage problems such as a low loop power supply voltage or increased wiring resistance. This also tests for other possible failures. 25 This tests for possible quiescent current related failures. 26 If the two-point calibration is performed with electrical instrumentation, this proof test will not detect any failures of the sensor. © exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 22 of 24

Appendix 2: Impact of lifetime of critical components on the failure rate According to section 7.4.7.4 of IEC 61508-2, a useful lifetime, based on experience, should be assumed. Although a constant failure rate is assumed by the probabilistic estimation method (see section 4.2.3) this only applies provided that the useful lifetime27 of components is not exceeded. Beyond their useful lifetime the result of the probabilistic calculation method is therefore meaningless, as the probability of failure significantly increases with time. The useful lifetime is highly dependent on the component itself and its operating conditions – temperature in particular (for example, electrolytic capacitors can be very sensitive). This assumption of a constant failure rate is based on the bathtub curve, which shows the typical behavior for electronic components. Therefore it is obvious that the PFDAVG calculation is only valid for components which have this constant domain and that the validity of the calculation is limited to the useful lifetime of each component. It is assumed that early failures are detected to a huge percentage during the installation period and therefore the assumption of a constant failure rate during the useful lifetime is valid. Table 11 shows which components with reduced useful lifetime are contributing to the dangerous undetected failure rate and therefore to the PFDAVG calculation and what their estimated useful lifetime is. Table 11: Useful lifetime of components with reduced useful lifetime contributing to λdu

Type Opto-coupler - With bipolar output

Name O201, O202

Useful lifetime More than 10 years

When plant experience indicates a shorter useful lifetime than indicated in this appendix, the number based on plant experience should be used.

27 Useful lifetime is a reliability engineering term that describes the operational time interval where the failure rate of a device is relatively constant. It is not a term which covers product obsolescence, warranty, or other commercial issues.

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov

STAHL 9162 08-04-21 R020 V1R2.doc, November 25, 2009 Page 23 of 24

Appendix 3: Description of the considered profiles Appendix 3.1: exida electronic database Profile

Profile according to IEC60654-1

1 2 3

B2 C3 C3

Ambient Temperature [°C] Average Mean (external) (inside box) 30 25 25

60 30 45

Temperature Cycle [°C / 365 days]

5 25 25

PROFILE 1: Cabinet mounted equipment typically has significant temperature rise due to power dissipation but is subjected to only minimal daily temperature swings. PROFILE 2: Low power electrical (two-wire) field products have minimal self heating and are subjected to daily temperature swings. PROFILE 3: General (four-wire) field products may have moderate self heating and are subjected to daily temperature swings.

© exida.com GmbH Stephan Aschenbrenner, Alexander Dimov