EZ Meter-Pak® Meter Centers

Class 4100 Catalog 4100CT0701

2008

EZMH114125

EZM32000CB

CONTENTS Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page Application Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Dimensions and Knockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

EZ Meter-Pak® Meter Centers Table of Contents

Table of Contents EZ METER-PAK METER CENTERS UL Listed Meter Center Short Circuit Current Ratings . . . . . . . . . . . . . . . . .4 EZM Typical Equipment Lineups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 EZ Meter-Pak (EZM) Meter Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Utility Company Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Equipment Short Circuit Current Ratings . . . . . . . . . . . . . . . . . . . . . . . . .6 Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Main Device Ampere Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Main Circuit Breaker Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Main Fusible Switch Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Terminal Box Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Branch Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 125 A Maximum Residential Branch Units . . . . . . . . . . . . . . . . . . . . . . . .9 225 A Maximum Residential Branch Units . . . . . . . . . . . . . . . . . . . . . . . .9 225 A Maximum Commercial Branch Units . . . . . . . . . . . . . . . . . . . . . .10 400 A Maximum Commercial Branch Units . . . . . . . . . . . . . . . . . . . . . .10 Bussed Extension Sections (NEMA Type 3R) . . . . . . . . . . . . . . . . . . . . . .11 Bussed Corner Sections for Indoor (NEMA Type 1) Construction Only . . .11 Mounting Channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Rotating Mounting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Main Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Single-Phase Branch Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Three-Phase Branch Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Closing Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 Closing Plates—Main Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 Closing Plates—Branch Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 Closing Plates—Main Devices and Branch Units . . . . . . . . . . . . . . . . . .17 Horizontal Cross Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 Equipment Grounding Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Visi-Tite® Nut Horizontal Cross Bus Connectors . . . . . . . . . . . . . . . . . .19 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Sealing Rings for Ring-Type Meter Sockets . . . . . . . . . . . . . . . . . . . . . .20 Circuit Breaker Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Individual Meter Socket Closing Plates. . . . . . . . . . . . . . . . . . . . . . . . . .20 Branch Unit Outer Covers for Tenant Circuit Breaker and Individual Meter Socket Compartments . . . . . . . . . . . . . . . . . . . . . . . . .21 Branch Unit Load Neutral Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 Branch Unit Load Equipment Grounding Terminals . . . . . . . . . . . . . . . .22 Meter Sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 Branch Unit Tenant Circuit Breaker Types and Meter Socket Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 Ring-Type Residential Meter Socket Compartment Standard Features .23 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 125 A Tenant Circuit Breaker Compartment . . . . . . . . . . . . . . . . . . . . . .26 225 A Tenant Circuit Breaker Compartment . . . . . . . . . . . . . . . . . . . . . .26 Optional Ringless Residential Meter Socket Features . . . . . . . . . . . . . .26 400 A Tenant Circuit Breaker Compartment . . . . . . . . . . . . . . . . . . . . . .28 Optional Ringless Commercial Meter Socket Features . . . . . . . . . . . . .30 Factory Phase Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Phase Balancing Flexibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 EZM Main Device Types and Configurations . . . . . . . . . . . . . . . . . . . . . . .33 Dimensions and Knockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61 2 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers

NEMA 3R Construction 240 Vac Maximum, for use on AC systems, suitable for use as Service Equipment. Utility Company Requirements: Review local utility requirements to ensure that metering equipment meets their standards. EZ Meter-Pak meter center enclosures meet NEC wire bending requirements, and are designed for wall mounting only (not suitable for floor mounting). All unmetered conductor compartments may be sealed by the utility company. EZ Meter-Pak meter centers have UL Listed short circuit current ratings up to 100 kA at 240 Vac when properly applied. For three-tier series ratings, refer to Data Bulletin 4100DB0301 and Instruction Bulletin 80043-303-19. Suitable incoming services for an EZM main device and available outgoing feeder(s) to downstream panelboards from EZM branch section(s)— Incoming Service to Main Device 120/240 Vac, 1Ø3W Available outgoing feeder(s) to downstream panelboards:







120/208 Vac, 1Ø3W (five-jaw meter sockets, two-pole circuit breakers) 208Y/120 Vac, 3Ø4W (seven-jaw meter sockets, three-pole circuit breakers)



• • • •

Note: QO, QO-VH and QO-H tenant circuit breakers used in 225 A branch units require the use of adapter EZM125QOA (purchased separately). • 400 A branch units are available in ringless type

mounted.



2000 A main disconnect or terminal box must be center mounted and requires use of branch units having 1200 A continuous horizontal cross bus. 400, 800 and 1200 A Type EZM-TBU tap boxes supplied with lug landings to meet EUSERC requirements.



Main Circuit Breaker, ratings: 400, 600, 800, 1000, 1200, 1600 and 2000 A Main Fusible Switch, ratings: 400, 600, 800, and 1200 A (1Ø3W only) Main Lugs Terminal Box, ratings: 225, 400, 600, 800, 1200, 1600 and 2000 A

Tenant circuit breakers must be ordered separately for these branch units. 125 A max. units make use of Type QO, QO-VH or QO-H two-pole tenant circuit breakers (40–125 A). 225 A max. units make use of Type QDP-TM, QBP-TM, QGP-TM and QJP-TM two-pole tenant circuit breakers (70–225 A), and may also make use of two-pole Type QO (40–125 A at 10 kA max.), two-pole Type QO-VH (40–60 A at 100 kA max.), or two-pole Type QO-H (40–60 A at 100 kA max.) tenant circuit breakers. 225 A commercial branch units are available in ring type or ringless type construction and are supplied with 1200 A copper horizontal cross bus with aluminum vertical connectors as standard (Example: EZML314225). For optional 1200 A continuous all-copper bussing, add suffix “CU” to catalog number (Example: EZML314225CU). Plug-in style commercial meter sockets are available as ring type EZMT with test block bypass (meets EUSERC requirements), ringless type EZMR without bypass, and ringless type EZML with lever bypass. 225 A max. units make use of type QDP-TM, QBP-TM, QGPTM and QJP-TM two-pole or three-pole tenant circuit breakers (70– 225 A), and may also make use of two-pole type QO (40–125 A at 10 kA max.), two-pole type QO-VH (40–60 A at 100 kA max.), or two-pole type QO-H (40–60 A at 100 kA max.) tenant circuit breakers.

Main Devices: • 400, 600 and 800 A main disconnects may be end mounted with branch units having 800 A or 1200 A continuous horizontal cross bus. 1000 and 1200 A main disconnect or terminal box must be center mounted when used with branch devices with main bus rated 800 A continuous. 1600 A main disconnect or terminal box must be center

125 A and 225 A residential branch units are available in ring type or ringless type construction and are supplied with 800 A continuous aluminum horizontal cross bus as standard (Example: EZM314125). For optional 1200 A continuous copper horizontal cross bus with aluminum vertical connectors, add suffix “X” to catalog number (Example: EZM314125X). For optional 1200 A continuous all-copper bussing, add suffix “CUX” to catalog number (Example: EZM314125CUX). NOTE: Five-gang 225 A EZM, EZMR and EZMH residential branch units are supplied with 1200 A continuous cross bus as standard, do not add suffix “X” or “CUX” to these units (Examples: EZMR315225 or EZMR315225CU). Plug-in style residential meter sockets are available as ring type EZM without bypass, ringless type EZMR without bypass, and ringless type EZMH with horn bypass.

120/240 Vac, 1Ø3W (Fed from transformer’s “A-Phase” and “C-Phase” only.) NOTE: Connection to High-Leg “B-Phase” not permitted for this service. (four-jaw ring type meter sockets, two-pole circuit breakers) (five-jaw ringless meter sockets, two-pole circuit breakers) Standard 3Ø IN/1Ø OUT branch units are not suitable for use on this Delta System. Special branch units are available for this System by adding suffix: “CA” to catalog number (Typical Examples: EZM313125CA, EZM313125XCA, EZM313125CUXCA, EZM314225CA, EZM314225XCA, EZM314225CUXCA, EZM315225CA, EZM314225CUCA, etc.). 240/120 Vac, 3Ø4W Delta (seven-jaw meter sockets, threepole circuit breakers)

Incoming Service to Main Device 208Y/120 Vac, 3Ø4W Available outgoing feeder(s) to downstream panelboards:





120/240 Vac, 1Ø3W (four-jaw ring type meter sockets, two-pole circuit breakers) (five-jaw ringless meter sockets, two-pole circuit breakers)

Incoming Service to Main Device 240/120 Vac, 3Ø4W Delta Available outgoing feeder(s) to downstream panelboards:



Branch Units:

construction only, and are supplied with 1200 A continuous all-copper bussing as standard (Example: EZML332400). These branch units are supplied with factory-installed type DJM tenant circuit breakers that have a field adjustable ampere rating trip setting from 160 A min. to 400 A max. A tamper-evident seal kit is available where needed, order seal kit 29375 (refer to NEC 240-6 [c]). 400 A branch units are available as Type EZML with plug-in style lever bypass type meter sockets, or Type EZMK with bolt-on style with manual bypass type meter sockets. Units having 800 A continuous horizontal cross bus WILL CONNECT with units having 1200 A continuous horizontal cross bus. Single phase units (three bus bars in horizontal cross bus) WILL NOT CONNECT with three phase units (four bus bars in horizontal cross bus).

For Load Center Three-Tiered Series Ratings used downstream from Metering Equipment, refer to Data Bulletins 4100DB0301 and 2700DB9901.

3 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers • •

Review local utility requirements to ensure that metering equipment meets their standards. Check local utility to determine available fault current at the meter center.



Using the SCCR table: —

— — —

Select meter center configuration, main lugs only (Six Disconnect Rule), or remote main, main circuit breaker, or main fusible switch. Read down to select SCCR equal to, or greater than desired rating. Read across to select branch unit tenant circuit breaker type. Continue reading across to select EZM main device type.

UL Listed Meter Center Short Circuit Current Ratings (SCCR) Tenant circuit breakers of same frame size having higher AIR values may replace tenant circuit breakers as listed in tables below and maintain the series rating. EZM Meter Center Overcurrent Protection Devices Short Circuit EZM Branch Unit Tenant Circuit Breaker Current Rating EZM Main Device with Integral Mounted Main, Types Available (Branch Unit Amperes max., (240 Vac Remote Mounted Main or without an Upstream Mounted Main Number of Poles, Tenant Circuit Breaker Maximum) a b (Six Disconnect Rule) Amperes Rating Range)

Figures

EZ Meter-Pak (Six Disconnect Rule Applications)—See Figure 1

EZM Branch Units

Load Centers (Main Lugs)

Service Disconnects (6 Max.)

10 kA 22 kA

T ransformer

EZM Main Lugs Terminal Box

Figure 1

25 kA 42 kA 65 kA 100 kA

EZM Main Lugs Terminal Box EZM Branch Units

Transformer

Tenant Circuit Breakers

65 kA

Figure 2

QG (225 A 2P or 3P, 70–225 A) DJM (400 A, 2P or 3P, 160–400 A) e QO-VH (125 A, 2P, 40–125 A) QO-VH (225 A, 2P, 40–60 A) d QD (225 A 2P or 3P, 70–225 A) QD (225 A 2P or 3P, 70–225 A)

100 kA

QJ (225 A 2P or 3P, 70–225 A ) c DJM (400 A 2P or 3P, 160–400 A) c e QO-VH (125 A, 2P, 40–125 A) QO-VH (225 A, 2P, 40–60 A) d QD (225 A 2P only, 70–225 A) QD (225 A 3P only, 70–225 A) c

EZM Circuit Breaker Main or EZM Main Fusible Switch EZM Branch Units

Transformer Tenant Circuit Breakers

Figure 3

Load Centers (Main Lugs)

400–2000 A Main Lugs Terminal Box (Tenant Circuit Breakers used as Service Disconnects—6 maximum)

EZ Meter-Pak 225–2000 A Main Lugs Terminal Box Applications Protected By Remote Main—See Figure 2 QO (125 A, 2P, 40–125 A) QO (225 A, 2P, 40–125 A) d 10 kA Must be protected by an upstream disconnecting means rated 10 k AIR minimum QB (225 A 2P or 3P, 70–225 A) DJM (400 A, 2P or 3P 160–400 A) e QO-VH (125 A, 2P, 40–125 A) 22 kA QO-VH (225 A, 2P, 40–60 A) d Must be protected by an upstream disconnecting means rated 22 k AIR minimum DJM (400 A, 2P or 3P, 160–400 A) e QD (225 A 2P or 3P, 70–225 A) 25 kA Must be protected by an upstream disconnecting means rated 25 k AIR minimum DJM (400 A, 2P or 3P, 160–400 A)e QOH (125 A, 2P, 40–125 A) d QOH (225 A, 2P, 40–60 A) Must be protected by an upstream disconnecting means rated 42 k AIR minimum DJM (400 A, 2P or 3P, 160–400 A) e 42 kA QO-VH (125 A, 2P, 40–125 A) Must be protected by a Square D circuit breaker QO-VH (225 A, 2P, 40–60 A) d Type LA (400 A max.) or MA (1000 A max.) Rated 42 k AIR minimum QD (225 A 2P or 3P, 70–225 A)

Load Centers (Main Lugs)

Upstream Disconnection Means and Overcurrent Protection as required

QO (125 A, 2P, 40–125 A) QO (225 A, 2P, 40–125 A) d QB (225 A, 2P or 3P, 70–225 A) QO-VH (125 A, 2P, 40–125 A ) QO-VH (225 A, 2P, 40–60 A) d QD (225 A, 2P or 3P, 70–225 A) QOH (125 A, 2P, 40–125 A) QOH (225 A, 2P, 40–60 A) d QG (225 A, 2P or 3P, 70–225 A) QJ (225 A, 2P or 3P, 70–225 A) c DJM (400 A, 2P or 3P, 160–400 A) c e

Must be protected by an upstream disconnecting means rated 65 k AIR minimum Must be protected by a Square D circuit breaker Type LH (400 A max.), MH (1000 A max.) or PA (1600 A max.) rated 65 k AIR minimum Must be protected by a Square D circuit breaker Type MG (800 A max.), PG (1200 A max.) or RG (2000 A max.) rated 65 k AIR minimum Must be protected by an upstream disconnecting means rated 100 k AIR minimum Must be protected by an upstream disconnection means with Class R (600 A max.), or Class T (300 Vac, 800 A maximum) fuses. Must be protected by an upstream disconnection means with Class J (600 A max.), Class L (1200 A max.), Class R (600 A max.), Class T (300 Vac, 1200 A max.) or Class T (600 Vac, 800 A maximum) fuses; or protected by a Square D circuit breaker Type MJ (800 A max.), PJ (1200 A max.), PH (1600 A max.) or RJ (2000 A max.) rated 100 k AIR minimum.

EZ Meter-Pak—Main Circuit Breaker Applications—See Figure 3 QO (125 A, 2P, 40–125 A) 10 kA QO (225 A, 2P, 40–125 A) d QB (225 A 2P or 3P, 70–225 A) 400–1600 A EZM Main Device with Type LH (400 A Max.), MH (1000 A max.) or PA (1600 A QO-VH (125 A, 2P, 40–125 A) max.) circuit breaker. d QO-VH (225 A, 2P , 40–60 A) 65 kA QD (225 A 2P or 3P, 70–225 A) e DJM (400 A, 2P or 3P, 160–400 A) 65 kA QD (225 A, 3P, 70–225 A) QO-VH (125 A, 2P, 40–125 A) 1000–1200 A Main Device with catalog number suffix "CBU" supplied with QO-VH (225 A, 2P, 40–60 A) d Type MHF circuit breaker. QD (225 A 2P only, 70–225 A) QD (225 A 3P only, 70–225 A) c 100 kA DJM (400 A, 2P or 3P, 160–400 A) c e QD (225 A 2P only, 70–225 A) QD (225 A 3P only, 70–225 A) c 2000 A EZM Main Device with Type RJ (2000 A) circuit breaker DJM (400 A 2P or 3P, 160–400 A) c e EZ Meter-Pak—Main Fusible Switch Applications—See Figure 3 QO (125 A, 2P, 40–125 A) 400–800 A EZM Main Device (1Ø or 3Ø) with Class T (300 Vac) fuses installed. 1200 A EZM 10 kA QO (225 A, 2P, 40–125 A) d Main Device (1Ø only) with Class T (300 Vac) fuses installed. QB (225 A 2P or 3P, 70–225 A)

QO-VH (125 A, 2P, 40–125 A) QO-VH (225 A, 2P, 40–60 A) d 1200 A EZM Main Device (1Ø only) with Class T (300 Vac) fuses installed. DJM (400 A, 2P, 160–400 A) e 100 kA QD (225 A 2P, 70–225 A) QO-VH (125 A, 2P, 40–125 A) QO-VH (225 A, 2P, 40–60 A) d QD (225 A 2P, only, 70–225 A) 100 kA 400–800 A EZM Main Device (1Ø or 3Ø) with Class T (300 Vac) fuses installed. QD (225 A 3P only, 70–225 A) c DJM (400 A, 2P or 3P, 160–400 A) c e Meter center short circuit current rating is equal to the lowest short circuit current rating given in table for any circuit breaker installed in any meter panelboard in the meter center. Short circuit current rating is measured at the LINE SIDE terminals of the integral mounted or remote mounted main providing overcurrent protection for the EZM metering equipment lineup. Three-pole only tenant circuit breaker(s) are limited to 208Y/120 Vac maximum. Requires use of EZM125QOA adapter (order separately). Supplied with factory installed circuit breaker(s), with an adjustable trip range of 160–400 A. 42 kA

a b c d e

For three-tier series ratings refer to Data Bulletin 4100DB0301 and Instruction Bulletin 80043-303-19. 4 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers

EZM Typical Equipment Lineups

Typical Tenant Circuit Breakers

QO2100 Two-Pole, Plug-On QO Circuit Breaker

EZM114125 EZM1800TB

QDP22200TM Two-Pole Circuit Breaker (shown) NOTE: The Q-Frame circuit breaker used with EZM devices comes without line side lugs.

EZM114225 EZM1800CB

DJM32400E20 Circuit Breaker

EZML334225

EZML311400 EZM31600CB

NOTE: 1600 A main circuit breaker must be center mounted with branch units mounted on both sides.

5 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Application Data

Application Data EZ Meter-Pak (EZM) Meter Centers

EZM1800CB



Enclosures are indoor/rainproof NEMA Type 3R meter centers for use on ac systems.



Finish: ANSI gray, baked powder-coat epoxy electrodeposited over cleaned phosphatized steel.

• •

240 Vac maximum.

• • •

Enclosures meet NEC® wire bending space requirements.



EZ Meter-Pak meter centers are UL Listed under File E-10582 and File E-131840.

Suitable for use as service equipment and suitable for use on the line side of service equipment. Designed to be wall mounted only (not suitable for floor mounting). All unmetered conductor compartments may be sealed by the utility company.

Utility Company Requirements Review local utility requirements to ensure that the metering equipment selected meets local standards. EZ Meter-Pak meter centers, to be complete, must include:

• • •

EZM main device, or terminal box; EZM branch section(s), and Square D® brand branch circuit breakers (tenant mains).

Equipment Short Circuit Current Ratings EZM3800FS

Available up to 100,000 RMS symmetrical amperes. Refer to pages 3 and 4.

Systems Utility systems suitable for use as an incoming service to an EZM main device:



System: 120/240 Vac, 1Ø3W

Available incoming service to main device: 120/240 Vac, 1Ø3W



System: 240/120 Vac, 3Ø4W delta

Available incoming services to main device: 240/120 Vac, 3Ø4W delta 120/240 Vac, 1Ø3W (fed from transformer’s AØ and CØ only). EZM1800TB

NOTE: Connection to High-Leg BØ not permitted for this service. Standard 3-phase IN/1-phase OUT branch units are NOT suitable for use on this DELTA System. Special branch units are available for this system by adding suffix "CA" to catalog number (examples: EZM313125CA, EZM314225CA etc.)



System: 208Y/120 Vac, 3Ø4W

Available incoming services to main device: 120/208 Vac, 1Ø3W or 208Y/120 Vac, 3Ø4W

6 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Application Data Services The following are incoming services for an EZM main device and available outgoing feeder(s) to downstream panelboards from EZM branch section(s):



120/240 Vac, 1Ø3W to main device. Available outgoing feeder(s) to downstream panelboards 120/240 Vac, 1Ø3W.



120/208 Vac, 1Ø3W to main device (derived from a 208Y/120 Vac, 3Ø4W network). Available outgoing feeder(s) to downstream panelboards 120/208 Vac, 1Ø3W.



240/120 Vac, 3Ø4W delta to main device. Available outgoing feeder(s) to downstream panelboards: — 120/240 Vac, 1Ø3W (fed from transformer’s AØ and CØ only). Special branch units are available for this system by adding suffix “CA” to catalog number, for example: EZM313125CA.

EZM314125

NOTE: Connection to High-Leg BØ not permitted for this service. Standard 3Ø IN/1Ø OUT branch units are not suitable for use on this delta system. — 240/120 Vac, 3Ø4W delta



208Y/120 Vac, 3Ø4W to main device. Available outgoing feeder(s) to downstream panelboards: — 120/208 Vac, 1Ø3W (Fifth jaw required) — 208Y/120 Vac, 3Ø4W

EZM114225

EZML311400

EZMR332225

7 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Main Device Ampere Ratings

Main Device Ampere Ratings Main Circuit Breaker Ratings •

400, 600, 800,1000, 1200,1600, and 2000 A combination overhead/underground



400, 600, 800, 1000, and 1200 A underground only (meets EUSERC standards)



1600 and 2000 A underground only (does not meet EUSERC standards).

Main Fusible Switch Ratings

EZM31600CB



400, 600, and 800 A (1Ø3W and 3Ø4W) and 1200 A (1Ø3W only) combination overhead/underground



400, 600, and 800 A (1Ø3W and 3Ø4W) and 1200 A (1Ø3W only) underground only (meets EUSERC standards).

Terminal Box Ratings 225, 400, 600, 800, 1600, and 2000 A combination overhead/underground. 400, 800, and 1200 A underground only (meets EUSERC standards). Mounting Restrictions for Main Devices:

EZM1800CBU

EZM32000CB



400, 600, and 800 A main disconnects may be end mounted with branch units having 800 or 1200 A continuous horizontal cross bus.



1000 and 1200 A main disconnect or terminal box must be center mounted when used with branch devices with main bus rated 800 A continuous.

• •

1600 A main disconnect or terminal box must be center mounted.



400, 800, and 1200 A type EZM-TBU tap boxes supplied with lug landings to meet EUSERC standards.

2000 A main disconnect or terminal box must be center mounted and requires use of branch units having 1200 A continuous horizontal cross bus.

EZM3800FS

EZM1800TB

8 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Branch Units

Branch Units UL Listed meter center short circuit current ratings (RMS symmetrical amperes) are listed on pages 3 and 4.

125 A Maximum Residential Branch Units •

Available in two cross bus configurations: 1Ø IN/1Ø OUT (includes three horizontal cross bus bars), and 3Ø IN/1Ø OUT (includes four horizontal cross bus bars).



Accepts 40–125 A, two-pole, plug-on type QO, QO-VH, or QOH circuit breakers (order circuit breakers separately).



Ring-type EZM branch units supplied with four-jaw (1Ø IN units), and with five-jaw (3Ø IN units), 100 A continuous duty rated meter sockets, without bypass (manual slider type bypass kit MM200MB can be ordered separately and field-installed).



Ringless-type EZMR branch units supplied with five-jaw, 100 A continuous duty rated meter sockets, without bypass (horn type bypass kit MMHB can be ordered separately and field-installed).



Ringless-type EZMH branch units supplied with five-jaw, 100 A continuous duty rated meter sockets and horn type bypass.

• •

Supplied with 800 A horizontal main cross bus.



2000 A main device must be center located when used with 125 A branch units with 1200 A main horizontal cross bus.

EZM115125 EZM316125

1000, 1200, or 1600 A main devices must be center located when used with 125 A branch units with 800 A main cross bus.

225 A Maximum Residential Branch Units EZMH114125

EZM113125

EZM114225



Available in two cross bus configurations: 1Ø IN/1Ø OUT (includes three horizontal cross bus bars), and 3Ø IN/1Ø OUT (includes four horizontal cross bus bars).



Accepts 70–225 A, 2-pole, bolt-on type QB, QD, QG or QJ circuit breakers, or with the use of plug-on adapter catalog number EZM125QOA, these units will accept 40–125 A, two-pole plug-on type QO, 40-60 A two-pole plug-on type circuit breakers QO-VH or QOH (order circuit breakers and adapters separately).



Ring-type EZM branch units supplied with four-jaw (1Ø IN units), and with five-jaw (3Ø IN units), 200 A continuous duty rated meter sockets, without bypass (manual slider type bypass kit MM200MB can be ordered separately and field-installed).



Ringless-type EZMR branch units supplied with five-jaw, 200 A continuous duty rated meter sockets without bypass (horn type bypass kit MMHB can be ordered separately and field-installed).



Ringless-type EZMH branch units supplied with five-jaw, 200 A continuous duty rated meter sockets and horn type bypass.



Two- through four-position units supplied with 800 A horizontal main cross bus and five-position supplied with 1200 A horizontal cross bus.



1000, 1200, and 1600 A main device must be center located when used with 225 A branch units with 800 A main horizontal cross bus.



2000 A main device must be center located when used with 225 A branch units with 1200 A main horizontal cross bus.

9 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Branch Units

225 A Maximum Commercial Branch Units

EZMR333225



Available in two cross bus configurations: 1Ø IN/1Ø OUT (includes three horizontal cross bus bars), 3Ø IN/1Ø OUT, and 3Ø IN/3Ø OUT (includes four horizontal cross bus bars).



1Ø OUT branch units accept 70–225 A type QB, QD, QG, and QJ, two-pole, bolt-on circuit breakers (order circuit breakers separately).



3Ø OUT branch units accept 70–225 A type QB, QD, QG, and QJ, three-pole, bolt-on circuit breakers (order circuit breakers separately).



1Ø OUT ringless-type EZML branch units are supplied with five-jaw, 200 A continuous duty 1Ø meter sockets with lever type bypass.



1Ø OUT ring-type EZMT branch units are supplied with five-jaw, 200 A continuous duty 1Ø meter sockets with test block bypass (meets EUSERC standards).



3Ø OUT ringless-type EZML branch units are supplied with seven-jaw, 200 A continuous duty 3Ø meter sockets with lever bypass.



3Ø OUT ringless-type EZMR branch units are supplied with seven-jaw, 200 A continuous duty 3Ø meter sockets without bypass.



3Ø OUT Ring-type EZMT branch units are supplied with seven-jaw, 200 A continuous duty 3Ø meter sockets with test block bypass (meets EUSERC standards).

• •

Supplied with 1200 A horizontal main cross bus. 1600 and 2000 A main devices must be center located when used with 225 A commercial branch units.

400 A Maximum Commercial Branch Units •

Available in two cross bus configurations: 1Ø IN/1Ø OUT (includes three horizontal cross bus bars), and 3Ø IN/1Ø OUT (includes four horizontal cross bus bars).



1Ø OUT branch units are supplied with factory-installed 400 A Type DJM two-pole circuit breaker(s). DJM circuit breaker has adjustable trip settings from 160–400 A (seal kit catalog number 29375 available separately).



3Ø OUT branch units are supplied with factory-installed 400 A Type DJM three-pole circuit breaker(s). DJM circuit breaker has adjustable trip settings from 160–400 A (seal kit catalog number 29375 available separately).

• •

Supplied with 1200 A horizontal main cross bus.

EZML334225

EZMT

1600 and 2000 A main devices must be center located when used with 400 A commercial branch units.

EZML331400

10 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Bussed Extension Sections (NEMA Type 3R)

Bussed Extension Sections (NEMA Type 3R) Bussed extensions provide separation between enclosures where needed to avoid building obstructions. The bussed extension occupies an area 19.25 in. (489 mm) H x 12.0 in. (304 mm) or 6.0 in. (152 mm) W positioned vertically in line with the horizontal cross bus of main and branch unit enclosures. Extensions provide additional space between the main device and the branch unit where needed to meet local utility requirements. In this case the main device is deeper than the branch unit, and the dimension between the side of the main device and the centerline of the branch unit meter socket is too close to meet minimum “clear space” requirements.

EZM3EXT



Bussed extensions are also used with bussed corner sections to provide additional working space in inside corner areas.

• • • •

Use EZM1EXT6 (6.0 in.) or EZM1EXT (12.0 in.) wide. Use EZM3EXT6 (6.0 in.) or EZM3EXT (12.0 in.) wide. Supplied with 1200 A horizontal main cross bus. Provisions for padlocking or sealing by the utility.

Bussed Corner Sections for Indoor (NEMA Type 1) Construction Only • • • • • • • • •

Enables mounting of metering enclosures on two adjacent walls. NEMA Type 1 construction for use indoors only. Designed for “inside and outside corners”. Use EZM1CORNER (inside corner) with 1Ø cross bus equipment. Use EZM1ELBOW (outside corner) with 1Ø cross bus equipment. Use EZM3CORNER (inside corner) with 3Ø cross bus equipment. Use EZM3ELBOW (outside corner) with 3Ø cross bus equipment. Supplied with 1200 A horizontal main cross bus. Provisions for padlocking or sealing by the utility.

Mounting Channel (see page 12)

EZM3CORNER



EZM main and branch units are each supplied with a wall mounting channel.



Mounting channel is packed externally to each device on top surface of front cover inside each carton for easy access. Covers do not need to be removed from device to access mounting channel.

Rotating Mounting Brackets (see page 12) •

EZM sections are equipped with permanently attached swinging mounting brackets that are easily rotated out of the way after marking wall for drilling mounting holes. The rotating feature of the mounting brackets will accommodate slight mounting hole misalignment.



Rotate mounting brackets to extended position before lifting device onto mounting channel for ease of installation.



Rotating mounting brackets are provided at top and bottom of each unit to secure device to the wall. 21.79 [553]

15.41 [391]

7.09 [180]

8.02 [204]

Common Corner Application to Meet Utility Clearance Requirements

14.88 [378]

8.50 [216]

Common Wall Application to Meet Utility Clearance Requirements

in. Dimensions: [mm]

EZM3ELBOW

11 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Bussed Extension Sections (NEMA Type 3R) Determine Mounting Channel Height for Metering Equipment Lineup

• Chalk Line

Contact your local utility to determine the following branch unit meter socket mounting height restrictions: — Maximum dimension, centerline of top meter socket to floor or finished grade level — Minimum dimension, centerline of bottom meter socket to floor or finished grade level

56.51 [14.35]

— Total branch unit meter socket height window (maximum dimension less minimum dimension). 125 A and 225 A Residential Branch Units (Typical)

in. Dimensions: [mm] Chalk line on wall at proper height and secure mounting channel to wall. Mounting channel is secured to wall and device is hung on channel by bracket attached to rear of unit.

Main Circuit Breaker Device (Typical)

225 A Commercial Branch Units (Typical)

9.00 [229] Typical 14.00 [356] Typical

Maximum Meter Socket Total Height Meter Requirement Socket

Mounting Channel

C C See note below.

Window Height

Top of Mounting Channel

Maximum Meter Socket Height Total Meter Requirement Socket Window Height

Minimum Meter Socket Height Requirement

Minimum Meter Socket Height Requirement

Minimum Height Requirement to Bottom of Main Floor or Finished Grade Level

Mounting Channel

Mounting Channel Height Requirements Detail

in. Dimensions: [mm]

NOTE: See pages 14–16 for dimension “C” for each catalog number.



Contact your local utility to determine minimum dimension from bottom of main device to floor or finished grade level.



Refer to drawings of main devices and branch units starting on page 40 and determine proper height to install mounting channels. Ensure branch unit meter sockets are positioned within total branch unit meter socket height window, and main device bottom is positioned far enough above floor or finished grade level to comply with local requirements.



Once the mounting channel height is determined, chalk a level line on wall at proper height.



Align top edge of mounting channels for each unit to wall in the order that they will be installed.



Some EZM branch sections (five-position and six-position branch units) may not fit within utility’s meter height window for outdoor applications, although could be acceptable for use in indoor installations.

Rotating Mounting Brackets

12 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Main Devices

Main Devices Width

T Mounting Channel Height 56.51 [1435] Mounting Channel

B

in. Dimensions: [mm] Main Device (Typical) NOTE: Mounting channel height of 56.51 in. (1435 mm) is for reference only. Consult local utility for minimum and maximum meter socket height requirements to properly position mounting channel above grade level.

Height

Width

Depth

B

M1

T

Catalog Number

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

EZM11000CB EZM11000CBU EZM11200CB EZM11200CBU EZM11200FS

53.97 70.05 61.19 70.05 61.19

1371 1779 1554 1779 1554

18.66 34.19 30.19 34.19 30.19

474 868 767 868 767

11.50 18.33 18.33 18.33 18.33

292 466 466 466 466

EZM11200FSU EZM11600CBU EZM11200TBU EZM11600CB

70.05 71.19 44.71 61.19

1779 1808 1136 1554

34.19 30.19 33.16 30.19

868 767 842 767

18.33 18.33 11.12 18.33

466 466 282 466

34.30 46.99 38.13 46.99 38.13 46.99 48.12 31.17 38.13

EZM11600TB EZM12000CB EZM12000CBU EZM12000TB EZM1225TB EZM1400CB EZM1400CBU EZM1400FS EZM1400FSU EZM1400TB EZM1400TBU EZM1600CB EZM1600CBU EZM1600FS EZM1600FSU EZM1600TB EZM1800CB EZM1800CBU EZM1800FS EZM1800FSU EZM1800TB EZM1800TBCU EZM1800TBU EZM1EXT EZM1EXT6

51.58 68.91 68.91 71.13 21.81 53.97 69.03 53.97 69.03 30.46 35.71 53.97 69.03 53.97 69.03 28.43 53.97 69.03 53.97 69.03 53.97 51.76 39.96 19.34 19.34

1310 1750 1750 1807 554 1371 1753 1371 1753 774 907 1371 1753 1371 1753 722 1371 1753 1371 1753 1371 1315 1015 491 491

22.33 30.19 30.19 30.19 11.50 18.66 20.46 18.66 20.46 17.00 17.16 18.66 20.46 18.66 20.46 17.00 18.66 20.46 18.66 20.46 18.66 23.93 25.06 11.66 6.00

567 767 767 767 292 474 520 474 520 432 436 474 520 474 520 432 474 520 474 520 474 608 637 296 152

13.00 18.33 18.33 21.46 5.81 11.50 11.50 11.50 11.50 6.53 8.00 11.50 11.50 11.50 11.50 6.53 11.50 11.50 11.50 11.50 11.50 6.41 11.12 6.37 6.37

330 466 466 545 148 292 292 292 292 166 203 292 292 292 292 166 292 292 292 292 292 163 282 162 162

27.92 44.25 44.25 37.62 13.002 34.30 49.37 34.30 49.37 16.29 27.17 34.30 49.37 34.30 49.37 16.29 34.30 49.37 34.30 49.37 34.30 28.01 31.17 11.852 11.852

871 1194 969 1194 969 1193 1222 792 969 709 1124 1124 956 330 871

19.67 23.06 23.06 23.06 23.06 23.07 23.07 13.54 23.06 23.66 24.66 24.66 33.51 8.81 19.67

500 586 586 586 586 586 586 344 586 601 626 626 851 224 500

22.21 9.52 18.38 9.52 18.38 9.53 8.39 25.34 18.38 28.59 12.26 12.26 18.89 43.51 22.21

1254 871 1254 414 690 871 1254 871 1254 414 871 1254 871 1254 871

19.66 19.67 19.66 14.17 8.54 19.67 19.66 19.67 19.66 12.14

499 500 499 360 217 500 499 500 499 308

7.14 22.21 7.14 40.22 29.34 22.21 7.14 22.21 7.14 40.22

564 242 467 242 467 242 213 644 467 725 311 311 480 1105 564 181 564 181 1022 745 564 181 564 181 1022

19.67 19.66 19.67 19.66 19.67

500 499 500 499 500

22.21 7.14 22.21 7.14 22.21

564 181 564 181 564

711 792 301 301

23.75 8.79 — —

603 223 — —

28.50 25.34 — —

724 644 — —

EZM1CORNER (indoor only) 3

19.50

495

14.40

366

8.02

204

11.852

301









EZM1ELBOW (indoor only) 4 EZM31000CB EZM31000CBU EZM31200CB EZM31200CBU EZM31200TBU EZM31600CB EZM31600CBU EZM31600TB EZM32000CB EZM32000CBU EZM32000TB EZM3225TB EZM3400CB EZM3400CBU EZM3400FS EZM3400FSU EZM3400TB EZM3400TBU EZM3600CB EZM3600CBU EZM3600FS EZM3600FSU EZM3600TB EZM3800CB EZM3800CBU EZM3800FS EZM3800FSU EZM3800TB EZM3800TBCU EZM3800TBU EZM3EXT EZM3EXT6 EZM3CORNER (indoor only)3 EZM3ELBOW (indoor only)4 1 2 3 4

19.50

495

14.52

369

8.01

204

11.852

301









53.97 70.05 61.19 70.05 44.71 61.19 68.69 55.12 68.91 68.91 71.13 21.81 53.97 69.03 53.97 69.03 30.46 35.71 53.97 69.03

1371 1779 1554 1779 1136 1554 1745 1400 1750 1750 1807 554 1371 1753 1371 1753 774 907 1371 1753

18.66 34.19 30.19 34.19 33.16 30.19 27.69 22.40 30.19 30.19 30.19 11.50 18.66 20.46 18.66 20.46 17.15 17.16 18.66 26.19

474 868 767 868 842 767 707 569 767 767 767 292 474 520 474 520 436 436 474 665

11.50 18.33 18.33 18.33 11.12 18.33 18.45 12.94 18.33 18.33 21.46 5.81 11.50 11.50 11.50 11.50 7.09 8.00 11.50 11.65

292 466 466 466 282 466 471 329 466 466 545 148 292 292 292 292 180 203 292 296

34.30 46.99 38.13 46.99 31.17 38.13 49.12 29.67 44.25 44.25 37.62 13.002 34.30 49.37 34.30 49.37 16.29 27.17 34.30 49.37

871 1194 969 1194 792 969 1255 754 1124 1124 956 330 871 1254 871 1254 414 690 871 1254

19.67 23.06 23.06 23.06 13.54 23.06 19.57 25.45 24.66 24.66 33.51 8.81 19.67 19.66 19.67 19.66 14.17 8.54 19.67 19.66

500 586 586 586 344 586 525 646 626 626 851 224 500 499 500 499 360 217 500 499

22.21 9.52 18.38 9.52 25.34 18.38 7.39 26.84 12.26 12.26 18.89 43.51 22.21 7.14 22.21 7.14 40.22 29.34 22.21 7.14

564 242 467 242 644 467 189 682 311 311 480 1105 564 181 564 181 1022 745 564 181

53.97 69.03 30.46 53.97 69.03 53.97 69.03 53.97 51.76 39.96 19.34 19.34

1371 1753 774 1371 1753 1371 1753 1371 1315 1015 491 491

18.66 26.19 17.15 18.66 26.19 18.66 26.19 18.66 23.93 25.06 11.66 6.00

474 665 436 474 665 474 665 474 608 637 296 152

11.50 11.65 7.09 11.50 11.65 11.50 11.65 11.50 6.41 11.12 6.37 6.37

292 296 180 292 296 292 296 292 163 282 162 162

34.30 49.37 16.29 34.30 49.37

871 1254 414 871 1254

19.67 19.66 14.17 19.67 19.66

500 499 360 500 499

22.21 7.14 40.22 22.21 7.14

564 181 1022 564 181

34.30 49.37 34.30 28.01 31.17 11.852 11.852

871 1254 871 711 792 301 301

19.67 19.66 19.67 23.75 8.79

500 499 500 603 223

22.21 7.14 22.21 28.50 25.34

564 181 564 724 644









19.50

495

14.40

366

8.02

204

11.852

301









19.50

495

14.52

369

8.01

204

11.852

301









If channel height is 56.51 in. (1435 mm) then M = Device supplied without mounting channel, secure to wall by use of rotating mounting feet. Each leg of this corner section measures 14.72 in. (373.89 mm) from wall to start of next enclosure. Each leg of elbow section measures 6.17 in. (156.72 mm) corner of wall to start of next enclosure.

13 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Main Devices 125 A and 225 A Residential Branch Units (Typical)

225 A Commercial Branch Units (Typical) Main Device (Typical) U

U

T

A

T

A

T

R

R C

S Max.

C

S Max.

B

B B L

L

S Min. Mounting Channel

S Min. Mounting Channel

M

Floor or Finished Grade Level

Determine Height for Mounting Channel NOTE: S Max., S Min., and M dimensions are based on local utility requirements and will determine proper height for mounting channel.

Single-Phase Branch Devices

Catalog Number (available suffix)

EZM112225 (X, CUX) EZM113125 (X, CUX) EZM113225 (X, CUX) EZM114125 (X, CUX) EZM114225 (X, CUX) EZM115125 (X, CUX) EZM115225 (CU) EZM116125 (X, CUX) EZMH112225 (X, CUX) EZMH113125 (X, CUX) EZMH113225 (X, CUX) EZMH114125 (X, CUX) EZMH114225 (X, CUX) EZMH115125 (X, CUX) EZMH115225 (CU) EZMH116125 (X, CUX) EZMK111400 EZMK112400 EZML111225 (CU) EZML11225D EZML111400 EZML112225 (CU) EZML11225D EZML112400 EZML113225 (CU) EZML113225D EZML114225 (CU) EZML114225D EZMR112225 (X, CUX) EZMR113125 (X, CUX) EZMR113225 (X, CUX) EZMR114125 (X, CUX) EZMR114225 (X, CUX) EZMR115125 (X, CUX) EZMR115225 (X, CUX) EZMR116125 (X, CUX) EZMT111225 EZMT112225 EZMT113225

Height

Width

Depth

Mtg. Channel (B)

A

C

Top Meter (U)

T

if “S Min.” for Bottom Meter = 30 then...

Bottom Meter (L)

(R) Top Meter is...

Mounting Channel Height

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

43.41 42.37 43.41 48.12 52.00 57.12 61.00 66.12 43.41 42.37 43.41 48.12 52.00 57.12 61.00 66.12 45.55 72.99 39.06 39.06 44.55 39.06 39.06 69.61 53.06 53.06 67.06 67.06 43.41 42.37 43.41 48.12 52.00 57.12 61.00 66.12 25.12 60.56 79.56

1103 1076 1103 1222 1321 1451 1549 1679 1103 1076 1103 1222 1321 1451 1549 1679 1157 1854 992 992 1132 992 992 1768 1348 1348 1703 1703 1103 1076 1103 1222 1321 1451 1549 1679 638 1538 2021

17.38 12.25 17.38 12.25 17.38 12.25 17.38 12.25 17.38 12.25 17.38 12.25 17.38 12.25 17.38 12.25 27.56 27.56 19.44 19.44 23.21 19.44 19.44 23.21 19.44 19.44 19.44 19.44 17.38 12.25 17.38 12.25 17.38 12.25 17.38 12.25 22.42 22.42 22.42

441 311 441 311 441 311 441 311 441 311 441 311 441 311 441 311 700 700 494 494 590 494 494 590 494 494 494 494 441 311 441 311 441 311 441 311 570 570 570

8.09 7.09 8.09 7.09 8.09 7.09 8.09 7.09 8.09 7.09 8.09 7.09 8.09 7.09 8.09 7.09 9.74 9.74 9.44 9.44 9.44 9.44 9.44 9.44 9.44 9.44 9.44 9.44 8.09 7.09 8.09 7.09 8.09 7.09 8.09 7.09 9.38 9.38 9.38

205 180 205 180 205 180 205 180 205 180 205 180 205 180 205 180 247 247 240 240 240 240 240 240 240 240 240 240 205 180 205 180 205 180 205 180 238 238 238

9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 — 29.69 — — — 14.00 14.00 27.44 14.00 14.00 14.00 14.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 — 19.00 19.00

229 229 229 229 229 229 229 229 229 229 229 229 229 229 229 229 — 754 — — — 356 356 697 356 356 356 356 229 229 229 229 229 229 229 229 — 483 483

32.34 31.30 32.34 31.30 32.34 31.30 32.35 40.30 32.34 31.30 32.34 31.30 32.34 31.30 32.35 40.30 37.81 37.81 25.51 25.51 37.81 25.51 25.51 37.81 39.50 39.50 39.50 39.50 32.34 31.30 32.34 31.30 32.34 31.30 32.35 40.30 16.19 43.63 48.25

821 795 821 795 821 795 821 1024 821 795 821 795 821 795 822 1024 960 960 648 648 960 648 648 960 1003 1003 1003 1003 821 795 821 795 821 795 822 1024 411 1108 1226

20.11 20.11 20.11 20.11 20.11 20.11 20.12 29.11 20.11 20.11 20.11 20.11 20.11 20.11 20.12 29.11 16.77 16.77 12.12 12.12 16.28 12.12 12.12 16.28 26.16 26.16 26.16 26.16 20.11 20.11 20.11 20.11 20.11 20.11 20.12 29.11 — 14.74 19.36

511 511 511 511 511 511 511 739 511 511 511 511 511 511 511 739 426 426 308 308 414 308 308 414 664 664 664 664 511 511 511 511 511 511 511 739 — 374 492

11.07 11.07 11.07 16.82 19.66 25.82 28.65 25.82 11.07 11.07 11.07 16.82 19.66 25.82 28.65 25.82 7.74 35.18 13.55 13.55 6.74 13.55 13.55 31.80 13.56 13.56 27.56 27.56 11.07 11.07 11.07 16.82 19.66 25.82 28.65 25.82 8.93 16.93 31.31

281 281 281 427 499 656 728 656 281 281 281 427 499 656 728 656 197 894 344 344 171 344 344 808 344 344 700 700 281 281 281 427 499 656 728 656 227 430 795

22.18 13.18 13.18 9.93 12.77 9.93 12.77 9.93 22.18 13.18 13.18 9.93 12.77 9.93 12.77 9.93 24.51 22.26 25.67 25.67 24.02 11.67 11.67 20.64 11.72 11.72 11.72 11.72 22.18 13.18 13.18 9.93 12.77 9.93 12.77 9.93 4.67 12.67 12.67

563 335 335 252 324 252 324 252 563 335 335 252 324 252 324 252 622 565 652 652 610 296 296 524 298 298 298 298 563 335 335 252 324 252 324 252 119 322 322

12.23 11.19 12.23 11.19 12.23 11.19 12.23 11.19 12.23 11.19 12.23 11.19 12.23 11.19 12.23 11.19 21.04 21.04 13.39 13.39 21.53 13.39 13.39 21.53 13.34 13.34 13.34 13.34 12.23 11.19 12.23 11.19 12.23 11.19 12.23 11.19 20.45 28.89 28.89

311 284 311 284 311 284 311 284 311 284 311 284 311 284 311 284 534 534 340 340 547 340 340 547 339 339 339 339 311 284 311 284 311 284 311 284 519 734 734

9.00 18.00 18.00 27.00 27.00 36.00 36.00 45.00 9.00 18.00 18.00 27.00 27.00 36.00 36.00 45.00 — 29.69 — — — 14.00 14.00 27.44 28.00 28.00 42.00 42.00 9.00 18.00 18.00 27.00 27.00 36.00 36.00 45.00 — 19.00 38.00

229 457 457 686 686 914 914 1143 229 457 457 686 686 914 914 1143 — 754 — — — 356 356 697 711 711 1067 1067 229 457 457 686 686 914 914 1143 — 483 965

39.00 48.00 48.00 57.00 57.00 66.00 66.00 75.00 39.00 48.00 48.00 57.00 57.00 66.00 66.00 75.00 30.00 59.69 30.00 30.00 30.00 44.00 44.00 57.44 58.00 58.00 72.00 72.00 39.00 48.00 48.00 57.00 57.00 66.00 66.00 75.00 30.00 49.00 68.00

991 1219 1219 1448 1448 1676 1676 1905 991 1219 1219 1448 1448 1676 1676 1905 762 1516 762 762 762 1118 1118 1459 1473 1473 1829 1829 991 1219 1219 1448 1448 1676 1676 1905 762 1245 1727

50.11 50.11 50.11 50.11 50.11 50.11 50.12 59.11 50.11 50.11 50.11 50.11 50.11 50.11 50.12 59.11 46.77 46.77 42.12 42.12 46.28 42.12 42.12 46.28 56.17 56.17 56.17 56.17 50.11 50.11 50.11 50.11 50.11 50.11 50.12 59.11 25.74 44.74 49.36

1273 1273 1273 1273 1273 1273 1273 1501 1273 1273 1273 1273 1273 1273 1273 1501 1188 1188 1070 1070 1176 1070 1070 1175 1427 1427 1427 1427 1273 1273 1273 1273 1273 1273 1273 1501 654 1136 1254

14 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Main Devices 125 A and 225 A Residential Branch Units (Typical)

225 A Commercial Branch Units (Typical) Main Device (Typical) U

U

T

A

T

T

A

R

R C

S Max.

C

S Max.

B

B B L

L

S Min.

S Min. Mounting Channel

Mounting Channel M Floor or Finished Grade Level

Determine Height for Mounting Channel NOTE: S Max., S Min., and M dimensions are based on local utility requirements and will determine proper height for mounting channel.

Three-Phase Branch Devices

Catalog Number (available suffix)

Height

in. EZM312225 (X, CUX, CA, XCA, CUXCA) EZM313125 (X, CUX, CA, XCA, CUXCA) EZM313125M10 EZM313225 (X, CUX, CA, XCA, CUXCA) EZM314125 (X, CUX, CA, XCA, CUXCA) EZM314125M10 EZM314225 (X, CUX, CA, XCA, CUXCA) EZM315125 (X, CUX, CA, XCA, CUXCA) EZM315125M10 EZM315225 (CU, CA, CUCA) EZM316125 (X, CUX, CA, XCA, CUXCA) EZMH312225 (X, CUX, CA, XCA, CUXCA) EZMH313125 (X, CUX, CA, XCA, CUXCA) EZMH313225 (X, CUX, CA, XCA, CUXCA) EZMH314125 (X, CUX, CA, XCA, CUXCA) EZMH314225 (X, CUX, CA, XCA, CUXCA) EZMH315125 (X, CUX, CA, XCA, CUXCA) EZMH315225 (CU, CA, CUCA) EZMH316125 (X, CUX, CA, XCA, CUXCA) EZMK311400 (CA)

Width

A

C

Top Meter (U)

T

if “S Min.” for Bottom Meter = 30 then...

Bottom Meter (L)

(R) Top Meter is...

Mounting Channel Height

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

22.18

563

12.23

311

9.00

229

39.00

991

42.37 1076 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

11.07

281

13.18

335

11.19

284

18.00

457

48.00 1219 50.11 1273

42.37 1076 12.25

311

7.09

180

10.00

254

24.29

617

12.10

307

18.08

459

10.18

259

12.19

310

20.00

508

50.00 1270 42.10 1069

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

13.18

335

12.23

311

18.00

457

48.00 1219 50.11 1273

48.12 1222 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

16.82

427

9.93

252

11.19

284

27.00

686

57.00 1448 50.11 1273

52.12 1324 12.25

311

7.09

180

10.00

254

34.29

871

22.10

561

17.83

453

9.93

252

12.19

310

30.00

762

60.00 1524 52.10 1323

52.00 1321 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

19.66

499

12.77

324

12.23

311

27.00

686

57.00 1448 50.11 1273

57.12 1451 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

25.82

656

9.93

252

11.19

284

36.00

914

66.00 1676 50.11 1273

62.12 1578 12.25

311

7.09

180

10.00

254

34.29

871

22.10

561

27.83

707

9.93

252

12.19

310

40.00 1016 70.00 1778 52.10 1323

822

[mm]

in.

Depth

Mtg. Channel (B)

[mm]

61.00 1549 17.38

441

8.09

205

9.00

229

32.35

20.12

511

28.65

728

12.77

324

12.23

311

36.00

66.12 1679 12.25

311

7.09

180

9.00

229

40.30 1024 29.11

739

25.82

656

9.93

252

11.19

284

45.00 1143 75.00 1905 59.11 1501

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

22.18

563

12.23

311

9.00

229

39.00

42.37 1076 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

11.07

281

13.18

335

11.19

284

18.00

457

48.00 1219 50.11 1273

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

13.18

335

12.23

311

18.00

457

48.00 1219 50.11 1273

48.12 1222 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

16.82

427

9.93

252

11.19

284

27.00

686

57.00 1448 50.12 1273

52.00 1321 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

19.66

499

12.77

324

12.23

311

27.00

686

57.00 1448 50.11 1273

57.12 1451 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

25.82

656

9.93

252

11.19

284

36.00

914

66.00 1676 50.11 1273

61.00 1549 17.38

441

8.09

205

9.00

229

32.35

822

20.12

511

28.65

728

12.77

324

12.23

311

36.00

914

66.00 1676 50.12 1273

66.12 1679 12.25

311

7.09

180

9.00

229

40.30 1024 29.11

739

25.82

656

9.93

252

11.19

284

45.00 1143 75.00 1905 59.11 1501

45.55 1157 27.56

700

9.74

247





30.60

426

7.74

197

24.51

623

21.04

534

777

16.77



914

in.

50.11 1273



66.00 1676 50.12 1273

30.00

991

762

50.11 1273

46.77 1188

15 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Main Devices Three-Phase Branch Devices

Catalog Number (available suffix)

EZMK312400 (CA) EZMK331400 EZMK332400 EZML311400 (CA) EZML312225 (CU, CA, CUCA) EZML31225D (CA) EZML312400 (CA) EZML313225 (CU, CA, CUCA) EZML313225D (CA) EZML314225 (CU, CA, CUCA) EZML314225D (CA) EZML331225 (CU) EZML331225D EZML331400 EZML332225 (CU) EZML332225D EZML332400 (CU) EZML333225 (CU) EZML333225D EZML334225 (CU) EZML334225D EZMR312225 (X, CUX, CA, XCA, CUXCA) EZMR313125 (X, CUX, CA, XCA, CUXCA) EZMR313225 (X, CUX, CA, XCA, CUXCA) EZMR314125 (X, CUX, CA, XCA, CUXCA) EZMR314225 (X, CUX, CA, XCA, CUXCA) EZMR315125 (X, CUX, CA, XCA, CUXCA) EZMR315225 (CU, CA, CUXCA) EZMR316125 (X, CUX, CA, XCA, CUXCA) EZMR332225 (CU) EZMR333225 (CU) EZMR334225 (CU) EZMT311225 (CA) EZMT312225 (CA) EZMT313225 (CA) EZMT331225 EZMT332225 EZMT333225

Height

Width

Depth

Mtg. Channel (B)

A

C

Top Meter (U)

T

if “S Min.” for Bottom Meter = 30 then...

Bottom Meter (L)

(R) Top Meter is... in.

Mounting Channel Height

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

72.99 45.55 72.99 45.55

1854 1157 1854 1157

27.56 27.56 27.56 23.21

700 700 700 589

9.74 9.74 9.74 9.44

247 247 247 240

29.69 — 29.69 —

754 — 754 —

37.81 30.60 37.81 37.81

960 777 960 960

16.77 16.77 16.77 16.28

426 426 426 414

35.18 7.74 35.18 7.74

894 197 894 197

22.26 24.51 22.26 24.02

565 623 565 610

21.04 21.04 21.04 21.53

534 534 534 547

29.69 — 29.69 —

754 — 754 —

59.69 1516 46.77 1188 30.00 762 46.77 1188 59.69 1516 46.77 1188 30.00 762 46.28 1175

39.06

992

[mm]

in.

[mm]

19.44

494

9.44

240

14.00

356

25.50

648

12.17

309

13.56

344

11.73

298

13.33

339

14.00

356

44.00 1118 42.17 1071

39.06 992 19.44 69.61 1768 23.21

494 589

9.44 9.44

240 240

14.00 27.44

356 697

25.50 37.81

648 960

12.17 16.28

309 414

13.56 31.80

344 808

11.73 20.64

298 524

13.33 21.53

339 547

14.00 27.44

356 697

44.00 1118 42.17 1071 57.44 1459 46.28 1176

53.06 1348 19.44

494

9.44

240

14.00

356

39.50 1003 26.17

665

13.56

344

11.72

298

13.34

339

28.00

711

58.00 1473 56.17 1427

53.06 1348 19.44

494

9.44

240

14.00

356

39.50 1003 26.17

665

13.56

344

11.72

298

13.34

339

28.00

711

58.00 1473 56.17 1427

67.06 1703 19.44

494

9.44

240

14.00

356

39.50 1003 26.17

665

27.56

700

11.73

298

13.34

339

42.00 1067 72.00 1829 56.17 1427

67.06 39.06 39.06 45.55 39.06 39.06 69.61 53.06 53.06 67.06 67.06

19.44 19.44 19.44 23.21 19.44 19.44 23.21 19.44 19.44 19.44 19.44

494 494 494 590 494 494 590 494 494 494 494

9.44 9.44 9.44 9.44 9.44 9.44 9.44 9.44 9.44 9.44 9.44

240 240 240 240 240 240 240 240 240 240 240

14.00 — — — 14.00 14.00 27.44 14.00 14.00 14.00 14.00

356 — — — 356 356 697 356 356 356 356

39.50 25.50 25.50 37.81 25.50 25.50 37.81 39.50 39.50 39.50 39.50

1003 648 648 960 648 648 960 1003 1003 1003 1003

26.17 12.17 12.17 16.28 12.17 12.17 16.28 26.16 26.16 26.16 26.16

665 309 309 414 309 309 414 664 664 664 664

27.56 13.56 13.56 7.74 13.56 13.56 31.80 13.56 13.56 27.56 27.56

700 344 344 197 344 344 808 344 344 700 700

11.73 25.73 25.73 24.02 11.74 11.74 20.64 11.72 11.72 11.72 11.72

298 654 654 610 298 298 524 298 298 298 298

13.34 13.33 13.33 21.53 13.33 13.33 21.53 13.34 13.34 13.34 13.34

339 339 339 547 339 339 547 339 339 339 339

42.00 1067 72.00 1829 56.17 1427 — — 30.00 762 42.17 1071 — — 30.00 762 42.17 1071 — — 30.00 762 46.28 1176 13.99 355 43.99 1117 42.17 1071 13.99 355 43.99 1117 42.17 1071 27.44 697 57.44 1459 46.28 1176 28.00 711 58.00 1473 56.17 1427 28.00 711 58.00 1473 56.17 1427 42.00 1067 72.00 1829 56.17 1427 42.00 1067 72.00 1829 56.17 1427

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

22.18

563

12.23

311

9.00

229

39.00

42.37 1076 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

11.07

281

13.18

335

11.19

284

18.00

457

48.00 1219 50.11 1273

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

13.18

335

12.23

311

18.00

457

48.00 1219 50.11 1273

48.12 1222 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

16.82

427

9.93

252

11.19

284

27.00

686

57.00 1448 50.11 1273

52.00 1321 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

19.66

499

12.77

324

12.23

311

27.00

686

57.00 1448 50.11 1273

57.12 1451 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

25.82

656

9.93

252

11.19

284

36.00

914

66.00 1676 50.11 1273

60.94 1548 17.37

441

8.09

205

9.00

229

32.35

822

20.14

512

28.59

726

12.73

323

12.21

310

36.00

914

66.00 1676 50.14 1274

66.12 1679 12.25

311

7.09

180

9.00

229

40.30 1024 29.11

739

25.82

656

9.93

252

11.19

284

45.00 1143 75.00 1905 59.11 1501

39.06 53.06 67.06 25.12 60.56 79.56 25.12 60.56 79.56

494 494 494 569 569 569 569 569 569

9.44 9.44 9.44 9.38 9.38 9.38 9.38 9.38 9.38

240 240 240 238 238 238 238 238 238

14.00 14.00 14.00 — 19.00 19.00 — 19.00 19.00

356 356 356 — 483 483 — 483 483

25.50 39.50 39.50 16.19 43.63 48.25 16.19 43.63 48.25

309 664 664 — 374 492 — 374 492

13.56 13.56 27.56 8.93 16.93 31.31 8.93 16.93 31.31

344 344 700 227 430 795 227 430 795

11.74 11.72 11.72 4.67 12.67 12.67 4.67 12.67 12.67

298 298 298 119 322 322 119 322 322

13.33 13.34 13.34 20.45 28.89 28.89 20.45 28.89 28.89

339 339 339 519 734 734 519 734 734

13.99 355 43.99 1117 42.17 1071 28.00 711 58.00 1473 56.16 1426 42.00 1067 72.00 1829 56.16 1426 — — 30.00 762 25.74 654 19.00 483 49.00 1245 44.74 1136 38.00 965 68.00 1727 49.36 1254 — — 30.00 762 25.74 654 19.00 483 49.00 1245 44.74 1136 38.00 965 68.00 1727 49.36 1254

1703 992 992 1157 992 992 1768 1348 1348 1703 1703

992 1348 1703 638 1538 2021 638 1538 2021

19.44 19.44 19.44 22.42 22.42 22.42 22.42 22.42 22.42

648 1003 1003 411 1108 1226 411 1108 1226

12.17 26.16 26.16 — 14.74 19.36 — 14.74 19.36

991

50.11 1273

16 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Closing Plates

Closing Plates Closing Plates—Main Devices

Closing Plates Provided with Main Device for use at Each End of Metering Line-Up



EZM main devices are supplied with two closing plates, one on each side of the enclosure, to cover and seal openings for horizontal cross bus.



Right-side closing plate is one inch deep and secured to the box side using three 1/4-20 captive screws and three 1/4-inch hex nuts. Two sealing wing nuts for this side are provided in the bag assembly packed with each main device. Holes in wing nuts and lanced ears in closing plates are provided to seal the closing plate to the box sides. Install one wing nut on screw extending through closing plate at bottom of center and the other wing nut on screw extending through the closing plate at the top front to seal.



Left-side closing plate is two inches deep and secured to box side using three 1/4-20 carriage head screws and three 1/4-inch hex nuts. Two sealing wing nuts for this side are provided in the bag assembly packed with each device. Holes in wing nuts and lanced ears in closing plates are provided to seal the closing plate to the box sides. Install one wing nut on screw extending through the closing plate at bottom center and the other wing nut on screw extending through closing plate at the top rear to seal. Where sealing is not required, install screws from outside to inside of unit and secure with hex nuts.

Closing Plates—Branch Units EZM branch units are shipped without closing plates, but are designed to receive one from a main device. To install, remove closing plate from side of main device before connecting branch unit to main device. After last branch unit is installed in lineup, follow closing plate installation instructions for main devices.

Closing Plates—Main Devices and Branch Units When adding on to an existing EZM metering equipment line up, repeat the above procedure by moving closing plate to end of lineup.

17 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Horizontal Cross Bus

Horizontal Cross Bus 800 A aluminum horizontal cross bus is standard for the following devices:

Right End of 3Ø Horizontal Cross Bus, Shown with Visi-Tite Nuts

Left End of 3Ø Horizontal Cross Bus, Shown with Slotted End Bus Bars

• • • • •

400, 600, 800, and 1000 A main circuit breaker devices

• •

Left end of each horizontal cross bus bar has a slotted end



1Ø main and branch units have 3 horizontal cross bus bars (Ø, Ø and neutral)



3Ø main and branch units have 4 horizontal cross bus bars (AØ, BØ, CØ, and neutral)



1Ø main or branch units will not interconnect with 3Ø main or branch units.

400, 600, and 800 A main fusible switches 225, 400, 600, and 800 A main lugs terminal boxes 125 and 225 A residential branch units Right end of each horizontal cross bus bar is supplied with 1/2-13 captive bolt and Visi-Tite® nut 800 A horizontal cross bussed units will connect with 1200 A horizontal cross bussed units

1200 A copper horizontal cross bus is standard in the following devices:

• •

1000 A “CBU” suffix main circuit breaker devices



1600 A “CB” and “CBU” suffix main circuit breaker devices (must always be center mounted)



1200 A “TBU” suffix main lug terminal devices (must be center mounted when used with branch devices with main bus rated 800 A)



1600 A “TB” suffix main lug terminal devices (must always be center mounted)



2000 A "TB" suffix main lug terminal devices (must always be center mounted and require the use of branch devices having 1200 A horizontal cross bus)

• • • •

125 A and 225 A “CUX” suffix residential branch devices

• •

Left end of each horizontal cross bus bar has a slotted end



1Ø main and branch units have 3 horizontal cross bus bars (Ø, Ø and neutral)



3Ø main and branch units have 4 horizontal cross bus bars (AØ, BØ, CØ, and neutral)



1Ø main or branch units will not interconnect with 3Ø main or branch units.

1200 A “CB” and “CBU” suffix main circuit breaker devices (must be center mounted when used with branch devices with main bus rated 800 A)

225 A commercial branch units 400 A commercial branch units Right end of each horizontal cross bus bar is supplied with 1/2-13 captive bolt and Visi-Tite nut 1200 A horizontal cross bussed units will connect with 800 A horizontal cross bussed units

18 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Equipment Grounding Procedure

Equipment Grounding Procedure 1. Install mounting channels to wall at proper height (refer to “Mounting Channel” on page 11). 2. Remove closing plates from sides of EZM main device next to where EZM branch sections are to be installed. 3. Position units on mounting channel next to each other, but do not secure rotating mounting brackets to wall at this time. 4. Remove outer covers EZM main device and exterior covers from EZM branch sections (refer to page 21 for outer covers on branch devices). 5. Remove individual meter socket cover from over horizontal cross bus area of EZM branch sections (refer to “Individual Meter Socket Covers” on page 21).

Captive Equipment Bonding Screws are Located on Right Side of Each EZM Main and Branch Device

Install Hex Nuts with Star Washers onto Captive Screws

6. Bond enclosures together by sliding three captive screws from the RIGHT side of unit through holes in box side (closing plate holes), and through LEFT side of adjacent enclosure. Install three 1/4-20 hex nuts with star washer provided onto 1/4-20 captive screws and torque to 50 lb-in. (5.6 N•m). Bonding for equipment ground path is complete, and enclosure gaskets are compressed to seal connection between units. 7. Replace closing plates at each end of metering equipment lineup (refer to “Closing Plates” on page 17). At this point, the enclosures are connected together and a bonded equipment ground path is established. The next installation step involves connection of the horizontal cross bus assemblies.

Tighten Until Outer Head Twists Off and RED Indicating Disc Falls Away

Shown with RED Indicating Disc in Place

Shown with Outer Head and RED Indicating Disc Falling Away

Visi-Tite® Nut Horizontal Cross Bus Connectors •

The Visi-Tite nut horizontal cross bus connector is a high-strength 1/2-13 UNC double-headed torque indicating nut. Installed as an integral part of the horizontal cross bus structure in every EZM main and branch device, this unique nut makes it possible to ensure proper torque at each connection without the need for a torque wrench.



The torque indicating Visi-Tite nut assembly also makes it possible to reduce equipment installation time over other designs requiring the use of a torque wrench.



When making EZM metering equipment cross bus connections, there is no need for a torque wrench. Use a socket wrench with a long handle to tighten the outer Visi-Tite nut head until it twists off and releases the RED plastic warning disc.



If the RED disc remains visible during inspection, the horizontal cross bus assembly has not yet been tightened.



Once the outer Visi-Tite nut head is twisted off, an inner hex-head nut remains for use with a torque wrench on maintenance checks or relocation of equipment (torque 50 lb-ft./600 lb-in. [68 N•m]).



All phase and neutral connections to the horizontal cross bus structure are now completed.



The final step is to secure the rotating mounting brackets to the wall at top and bottom of each EZM main and branch unit enclosure.

Shown After Installation of Cross Bus Structure is Complete

19 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Accessories

Accessories Sealing Rings for Ring-Type Meter Sockets

Snap-Type Sealing Ring

Screw-Type Sealing Ring

Standard Snap-Type Aluminum Sealing Ring, catalog number 29209-100-01, is the standard sealing ring for all ring-type EZM branch sections. Replacement sealing rings may be ordered separately. Snap-Type Stainless Steel Sealing Ring, catalog number ARP00026, is a non-standard sealing ring. Order separately and install when required by the local utility. Screw-Type Aluminum Sealing Ring, catalog number 29008W, is a non-standard sealing ring. Order separately and install when required by the local utility.

Circuit Breaker Doors BCV Circuit Breaker Door Shown with Door Closed

125, 225, and 400 A EZM branch sections are supplied with factor-installed circuit breaker doors constructed of durable impact-resistant material. The following replacement kits are available:



BCV replacement door for vertically operated circuit breaker handles: — 125 A ring and ringless residential branch sections — 225 A ring and ringless residential branch sections — 225 A ringless commercial branch sections — Supplied with built-in latch with padlock provisions.



BCM replacement door for vertically operated circuit breaker handles: — 400 A ringless commercial branch sections

BCM Circuit Breaker Cover Shown with Door Open

— 400–800 A standard and EUSERC fusible switch main devices — 400–1000 A standard circuit breaker main devices — 400–1200 A EUSERC circuit breaker main devices — Supplied with built-in latch with padlock provisions.

Individual Meter Socket Closing Plates LEXAN® Meter Socket Closing Plate for Residential Branch Units:

LEXAN Closing Plate

• • • •

Order separately (catalog number 29007)



Closing plates have four LEXAN blades as a part of the molding used to engage meter socket jaws.

For use with 125 and 200 A residential branch units Molded of LEXAN #141-112 polycarbonate resin LEXAN offers high-impact and tensile strength characteristics and contains an ultra-violet inhibitor to ensure years of clear visibility

Metal Meter Socket Closing Plate for Ringless-Type Branch Units:

Ringless-Type Metal Closing Plate

• • •

Order separately (catalog number RSG4)



Closing plate cannot be removed from individual meter socket cover with meter socket cover installed on branch unit.

For use with ringless-type branch units Metal closing plate attaches to individual meter socket cover from the backside with four hold-down screws

20 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Accessories Branch Unit Outer Covers for Tenant Circuit Breaker and Individual Meter Socket Compartments 125 and 225 A Ring-Type Residential Branch Unit Outer Covers for Tenant Circuit Breaker Compartments and Individual Meter Socket Covers:

EZM113200 (Ring-Type) EZM113125 (Ring-Type) Outer Tenant Circuit Breaker Outer Tenant Circuit Breaker Cover and Individual Cover and Individual Meter Socket Covers Meter Socket Covers



Outer tenant circuit breaker covers can be removed without disturbing sealed utility meters mounted to the individual meter socket cover.



All unmetered conductor compartments remain sealed and isolated when outer tenant circuit breaker covers are removed.



Outer tenant circuit breaker covers are supplied with individual tenant circuit breaker doors that may be locked with a padlock.



An individual meter socket cover is supplied for each meter socket position.



Each ring-type meter socket cover has a rim formed into the cover to support the base of the utility meter.



Aluminum snap-type sealing rings are standard and are used to attach the base of the utility meter to the rim. A slot is provided in the tab of the sealing ring for the local utility to install their seal to lock the meter into place.

125, 225, and 400 A Ringless-Type Branch Unit Outer Covers for Tenant Circuit Breaker Compartments and Individual Meter Socket Covers:

EZML113200 (Ringless-Type) Outer Tenant Circuit Breaker Cover and Individual Meter Socket Covers

EZML332200 (Ringless-Type) Outer Tenant Circuit Breaker Cover and Individual Meter Socket Covers



Outer tenant circuit breaker covers can be removed without disturbing sealed utility meters secured under individual meter socket covers.



All unmetered conductor compartments remain sealed and isolated when outer tenant circuit breaker covers are removed.



Outer tenant circuit breaker covers are supplied with individual tenant circuit breaker doors that may be locked with a padlock.



Individual ringless-type meter socket covers are supplied with stainless steel hasps that extend through cover and stainless steel latches for sealing covers to branch unit while utility meter or closing plate is mounted in meter socket.



Ringless meter socket covers have provisions to accept utility seals including plastic padlocks, lead and wire seals, padlocks, and barrel locks, to prevent unauthorized access to meter socket compartment.

21 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Accessories Branch Unit Load Neutral Terminals 125 A branch unit load neutral terminals accept one 14-2/0 AWG copper or one 12-2/0 AWG aluminum conductor per meter socket position. 225 A branch unit load neutral terminals accept one 6 AWG-300 kcmil aluminum or copper conductor per meter socket position. 400 A branch unit load neutral terminals will accept one 1/0 AWG-600 kcmil or two 1/0 AWG-250 kcmil aluminum or copper conductor(s) per meter socket position.

Branch Unit Load Equipment Grounding Terminals Branch units are supplied with load equipment grounding terminals for feeds to downstream panelboards.

225 A Branch Unit Load Neutral Terminals

Grounding terminals on 125 and 225 A branch devices have provisions to accept one 14-2/0 AWG copper, or one 12-2/0 AWG aluminum conductor per meter socket position. Grounding terminals on 400 A branch devices have provisions to accept one 4 AWG-300 kcmil copper or aluminum conductor per meter socket position. Grounding terminals are factory-installed at the bottom of the wiring gutter compartment, but may be relocated to the top of the wiring gutter compartment when exiting out the top of the device.

225 A Branch Unit Load Neutral Terminals

400 A Branch Unit Load Neutral Terminals

Branch Unit Load Equipment Grounding Terminals

22 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Accessories

Meter Sockets Branch Unit Tenant Circuit Breaker Types and Meter Socket Configurations EZM branch units are supplied with meter sockets and provisions for mounting tenant circuit breakers to feed downstream type QO or HOM load centers or type NQOD panelboards. The following table includes standard and optional branch unit features along with tenant circuit breaker types and meter socket configurations. 125 A and 225 A Ring-Type EZM Residential Branch Units (1Ø OUT) Meter Socket Ring-Type (Quantity)

Four-Jaw Meter Socket 1Ø IN

Five-Jaw Meter Socket 3Ø IN

Catalog Number

Catalog Number

Circuit Breaker Type (Two-Pole Only)

125 A Ring-Type Residential without Bypass Three-Position

EZM113125 — EZM113125CUX

EZM313125 EZM313125M10 EZM313125CUX

QO, QO-VH, QOH

Four-Position

EZM114125 — EZM114125CUX

EZM314125 EZM314125M10 EZM314125CUX

QO, QO-VH, QOH

Five-Position

EZM115125 — EZM115125CUX

EZM315125 EZM315125M10 EZM315125CUX

QO, QO-VH, QOH

Six-Position

EZM116125 EZM116125CUX

EZM316125 EZM316125CUX

QO, QO-VH, QOH

225 A Ring-Type Residential without Bypass

EZM115125

EZM113225

Two-Position

EZM112225 EZM112225CUX

EZM312225 EZM312225CUX

QB, QD, QG, QJ

Three-Position

EZM113225 EZM113225CUX

EZM313225 EZM313225CUX

QB, QD, QG, QJ

Four-Position

EZM114225 EZM114225CUX

EZM314225 EZM314225CUX

QB, QD, QG, QJ

Five-Position

EZM115225 EZM115225CU

EZM315225 EZM315225CU

QB, QD, QG, QJ

Ring-Type Residential Meter Socket Compartment Standard Features •

1Ø IN, 1Ø OUT branch sections include three horizontal cross bus bars and a four-jaw meter socket.



3Ø IN, 1Ø OUT branch sections include four horizontal cross bus bars and a five-jaw meter socket. — 120/208 Vac, 1Ø3W (derived from a 208Y/120 Vac, 3Ø4W network). Standard 3Ø IN/1Ø OUT branch units are suitable for use on this system.

125 A and 225 A Ring-Type 125 A and 225 A Ring-Type Meter Socket, Four-Jaw Individual Meter Socket Cover Shown without Sealing Ring without Bypass

— 120/240 Vac, delta, 1Ø3W (fed from transformer’s AØ and CØ only). Connection to high-leg BØ not permitted for use on this system. Standard 3Ø IN/1Ø OUT branch units are not suitable for use on this system. Special branch units are available for this system by adding suffix “CA” to catalog number; for example: EZM313125CA.

• •

Meter socket jaws are front removable and spring reinforced.

• •

200 A continuous duty rated meter socket jaws supplied without bypass.

Meter blade guides are supplied as standard on both line and load side meter socket jaws. Aluminum snap-type sealing ring supplied with each meter socket as standard. 23

07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Accessories 125 A Tenant Circuit Breaker Compartment •

125 A maximum branch units will accept 40–125 A two-pole plug-on type QO, QO-VH, or QOH circuit breakers (order circuit breakers separately).



Refer to pages 3 and 4 for meter center available short circuit current ratings with the above tenant circuit breakers installed.

225 A Tenant Circuit Breaker Compartment

125 A Tenant Circuit Breaker Base (Two-Pole)



225 A maximum branch units listed in this section will accept 100–225 A two-pole bolt-on type QB, QD, QG, or QJ circuit breakers.



With the use of plug-on adapter catalog number EZM125QOA, these units will accept 40–125 A two-pole plug-on type QO, and 40–60 A two-pole plug-on type QO-VH and QOH circuit breakers. (Order circuit breakers and adapters separately.)



Refer to pages 3 and 4 for meter center available short circuit current ratings with the above tenant circuit breakers installed.

QO2100 Tenant Circuit Breaker Installed

Optional Ring-Type Residential Meter Socket Features

225 A Q2M Tenant Circuit Breaker Base (Two-Pole)



Five-jaw kit catalog number 5J (one kit required per meter socket) is available for field installation and can be mounted on the meter socket base assembly at three, six, or nine o’clock positions. Used to convert a four-jaw 125 A or 225 A ring-type branch unit meter socket to a five-jaw meter socket.



Five-jaw meter sockets are required for a 120/208 Vac, 1Ø3W service derived from a 208Y/120 Vac, 3Ø4W system.



Manual slider type bypass kit catalog number MM200MB is available for field installation. It includes manual slider-type bypass and replacement individual meter socket cover (cover is notched to allow handle of slider bypass to pass through rim with meter installed). Slider-type bypass is intended for temporary use only (not continuous duty rated). Available short circuit current rating of metering equipment is limited to 10,000 RMS symmetrical amperes with slider-type bypass kits installed.



Plug-on adapter kit catalog number EZM125QOA available for use in 225 A branch units that use bolt-on type QB, QD, QG, or QJ two-pole tenant circuit breakers. Kit will accept 40–125 A two-pole plug-on type QO, and 40–60 A two-pole plug-on type QO-VH and QOH circuit breakers. (Order circuit breakers and adapters separately.)

Five-Jaw Kit (5J) Installed at the 9 O’Clock Position

Manual Slider-Type Bypass Shown in Closed Position with Handle Extending through Notch in Rim of Meter Socket Cover

Manual Slider-Type Bypass Shown in Open Position with Handle Secured by Notch Meter Socket Sealing Ring

EZM125QOA Two-Pole Plug-On Adapter Kit for use in QB, QD, QG, or QJ Bolt-On Tenant Circuit Breaker Compartments

24 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Accessories 125 A and 225 A Ringless-Type EZMR and EZMH Residential Branch Units (1Ø OUT)

Meter Socket Ringless-Type (Qty.)

Five-Jaw Meter Socket 1Ø IN

Five-Jaw Meter Socket 3Ø IN

Catalog Number

Catalog Number

Circuit Breaker Type (Two-Pole Only)

125 A Ringless without Bypass Three-Position

EZMR113125 EZMR113125CUX

EZMR313125 EZMR313125CUX

QO, QO-VH or QOH

Four-Position

EZMR114125 EZMR114125CUX

EZMR314125 EZMR314125CUX

QO, QO-VH or QOH

Five-Position

EZMR115125 EZMR115125CUX

EZMR315125 EZMR315125CUX

QO, QO-VH or QOH

Six-Position

EZMR116125 EZMR116125CUX

EZMR316125 EZMR316125CUX

QO, QO-VH or QOH

225 A Ringless without Bypass

EZMH114125

Two-Position

EZMR112225 EZMR112225CUX

EZMR312225 EZMR312225CUX

QB, QD, QG or QJ

Three-Position

EZMR113225 EZMR113225CUX

EZMR313225 EZMR313225CUX

QB, QD, QG or QJ

Four-Position

EZMR114225 EZMR114225CUX

EZMR314225 EZMR314225CUX

QB, QD, QG or QJ

Five-Position

EZMR115225 EZMR115225CU

EZMR315225 EZMR315225CU

QB, QD, QG or QJ

125 A Ringless with Horn Bypass Three-Position

EZMH113125 EZMH113125CUX

EZMH313125 EZMH313125CUX

QO, QO-VH or QOH

Four-Position

EZMH114125 EZMH114125CUX

EZMH314125 EZMH314125CUX

QO, QO-VH or QOH

Five-Position

EZMH115125 EZMH115125CUX

EZMH315125 EZMH315125CUX

QO, QO-VH or QOH

Six-Position

EZMH116125 EZMH116125CUX

EZMH316125 EZMH316125CUX

QO, QO-VH or QOH

225 A Ringless with Horn Bypass 125 A and 225 A 125 A and 225 A Ringless-Type Ringless Meter Socket Individual Meter Socket Cover with Horn Bypass Shown with Stainless Steel Hasp and Latch for use with Utility Seals

Two-Position

EZMH112225 EZMH112225CUX

EZMH312225 EZMH312225CUX

QB, QD, QG or QJ

Three-Position

EZMH113225 EZMH113225CUX

EZMH313225 EZMH313225CUX

QB, QD, QG or QJ

Four-Position

EZMH114225 EZMH114225CUX

EZMH314225 EZMH314225CUX

QB, QD, QG or QJ

Five-Position

EZMH115225 EZMH115225CU

EZMH315225 EZMH315225CU

QB, QD, QG or QJ

Ringless Residential Meter Socket Compartment Standard Features



1Ø IN, 1Ø OUT branch sections (includes three horizontal cross bus bars). Five-jaw meter sockets supplied as standard.



3Ø IN, 1Ø OUT branch sections (includes four horizontal cross bus bars). Five-jaw meter sockets supplied as standard. — 120/208 Vac, 1Ø3W (derived from a 208Y/120 Vac, 3Ø4W service). Standard 3Ø IN/1Ø OUT branch units are suitable for use on this system. — 120/240 Vac, 1Ø3W (fed from transformer’s AØ and CØ only). Connection to high-leg BØ not permitted for use on this system. Standard 3Ø IN/1Ø OUT branch units are available for this system by adding suffix “CA” to catalog number (Examples: EZMR313125CA, EZMH314125CA, EZMR313225CA and EZMH312225CA).

25 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers

General Information:

125 A QO Tenant Circuit Breaker Base (Two-Pole)

QO2100 Tenant Circuit Breaker Installed

• •

Meter socket jaws are removable from the front and spring-reinforced.

• •

200 A continuous duty rated meter socket jaws supplied with fifth jaw.



Ringless meter socket covers have provisions to accept utility seals including plastic padlocks, lead and wire seals, and barrel locks to prevent unauthorized access to meter socket compartment.

Meter blade guides supplied as standard on both line and load side meter socket jaws. Individual ringless-type meter socket covers are provided with stainless steel hasps that extend through cover, and stainless steel latches for sealing covers to branch unit. The utility meter or closing plate is mounted in meter socket.

125 A Tenant Circuit Breaker Compartment •

125 A maximum residential branch units will accept 40–125 A, two-pole, plug-on type QO, QO-VH, or QOH circuit breakers (order circuit breakers separately).



Refer to pages 3 and 4 for meter center available short circuit current ratings with the above tenant.

225 A Tenant Circuit Breaker Compartment

225 A Q-Frame Tenant Circuit Breaker Base (Three-Pole)



225 A maximum branch units listed in this section will accept 100–225 A, two-pole, bolt-on type QB, QD, QG, or QJ circuit breakers.



Or with the use of plug-on adapter catalog number EZM125QOA, these units will accept 40–125 A, two-pole plug-on type QO, and 40–60 A two-pole plug-on type QO-VH and QOH circuit breakers. (Order circuit breakers and adapters separately.)



Refer to pages 3 and 4 for meter center available short circuit current ratings with the above tenant circuit breakers installed.

Optional Ringless Residential Meter Socket Features •

Ringless-Type Individual Meter Socket Cover Ringless-Type Individual Shown with Barrel Lock Meter Socket Cover Shown with Barrel Lock Installed through Cover and Lock Bracket Head Protector (Reverse View) (Catalog Number MMBLC)

Barrel lock head protector kit, catalog number MMBLC (one kit covers six meter sockets) is available for field-installation. — Knockout in individual meter socket cover is provided for barrel lock head protector kit. — Secure head protector kit to cover with lock nut supplied. — Barrel lock not supplied.



Horn bypass kit catalog number MMHB (one kit required per meter socket) is available for field-installation. — To install horn bypass kit remove one of four 1/4-inch hex nuts from meter socket jaw assemblies and position horn bypass bus bar connector on top of meter jaw. Secure with hex nut and torque to 75 lb-in. (8.5 N•m). Repeat this process for remaining three jaw positions. — Horn bypass bus bars are of different shapes, and must be installed as shown (refer to instructions provided with each kit). — Horn bypass factory-installed on EZMH device.

Residential Horn Type Bypass Kit Available for Use on EZMR Ringless Branch Units, and Standard on EZMH Ringless Branch Units

26 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers 225 A Ring-Type EZMT Commercial Branch Units (1Ø OUT) Meter Socket Ringless-Type (Qty)

Five-Jaw Meter Socket 1Ø IN

Five-Jaw Meter Socket 3Ø IN

Catalog Number

Catalog Number

Circuit Breaker Type (Two-Pole Only)

225 A Ring-Type with Test Block Bypass One-Position

EZMT111225

EZMT311225

QB, QD, QG, or QJ

Two-Position

EZMT112225

EZMT312225

QB, QD, QG, or QJ

Three-Position

EZMT113225

EZMT313225

QB, QD, QG, or QJ

NOTE: EZMT devices are supplied with Test Block Bypass, which meets EUSERC requirements.

225 A and 400 A Ringless-Type EZML and EZMK Commercial Branch Units (1Ø OUT) Meter Socket Ringless-Type (Qty)

EZMT311225

Five-Jaw Meter Socket 1Ø IN

Five-Jaw Meter Socket 3Ø IN

Catalog Number

Catalog Number

Circuit Breaker Type (Two-Pole Only)

225 A Ringless with Lever Type Bypass and Jaw Release One-Position

EZML111225 EZML111225CU EZML111225D



QB, QD, QG, or QJ

Two-Position

EZML112225 EZML112225CU EZML112225D

EZML312225 EZML312225CU EZML312225D

QB, QD, QG, or QJ

Three-Position

EZML113225 EZML113225CU EZML113225D

EZML313225 EZML313225CU EZML313225D

QB, QD, QG, or QJ

Four-Position

EZML114225 EZML114225CU EZML114225D

EZML314225 EZML314225CU EZML314225D

QB, QD, QG, or QJ

400 A Ringless with Lever Type Bypass and Jaw Release One-Position

EZML111400

EZML311400

DJM36400E201

Two-Position

EZML112400

EZML312400

DJM36400E201

400 A Ringless Type K Bolt-On with Manual Bypass

EZML113225

One-Position

EZMK1114002

EZMK311400

DJM36400E201

Two-Position

EZMK1124002

EZMK312400

DJM36400E201

1

Factory-installed.

2

Contains one four-jaw meter socket.

Ringless Commercial Meter Socket Compartment Standard Features



1Ø IN, 1Ø OUT branch units (include three horizontal cross bus bars). Fivejaw meter sockets supplied as standard. Not available in 400 A branch unit.



3Ø IN, 1Ø OUT branch units (include four horizontal cross bus bars). Fivejaw meter sockets supplied as standard. — 120/208 Vac, 1Ø3W (derived from a 208Y/120 Vac, 3Ø4W service). Standard 3Ø IN/1Ø OUT branch units are suitable for use on this system.

225 A Ringless-Type Meter Socket, Seven-Jaw with Lever Type Bypass Shown with Lexan Shield over Line and Load Meter Jaws

— 120/240 Vac, 1Ø3W (fed from transformer’s AØ and CØ only). Connection to high-leg BØ not permitted for use on this system. Standard 3Ø IN/1Ø OUT branch units are not suitable for use on this Delta system. Special branch units are available for this system by adding suffix: “CA” to catalog number (Examples: EZML313125CA and EZML312400CA).

400 A Ringless-Type Meter Socket, Five-Jaw with Lever Type Bypass Shown with Lexan Shield over Line and Load Meter Jaws

• •

320 A continuous duty rated meter sockets supplied with lever bypass. Lever bypass meter sockets are supplied with jaw release. 27

07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers •

Lever bypass meter sockets are supplied with a Lexan shield as an integral part of the meter socket assembly and used as a guide to assist mounting of utility meter.



Ringless type K bolt-on meter sockets have a four-jaw socket and only accept a bolt-on watt-hour meter.

• •

Type K bolt-on meter sockets are supplied with a manual bypass.



Ringless meter socket covers have provisions to accept utility seals including plastic padlocks, lead and wire seals, padlocks, and barrel locks to prevent unauthorized access to meter socket compartment.

Individual ringless-type meter socket covers are supplied with a stainless steel hasp that extends through cover and stainless steel latches for sealing covers to branch unit while utility meter or closing plate is mounted in meter socket.

400 A EZMK Bolt-On Meter Socket

225 A Tenant Circuit Breaker Compartment 225 A maximum commercial branch units accept 70–225 A, two-pole, bolt-on type QB, QD, QG, or QJ circuit breakers (order circuit breakers separately). Refer to pages 3 and 4 for meter center available short circuit current ratings.

400 A Tenant Circuit Breaker Compartment •

DJM36400E20 circuit breakers are factory-installed into 400 A maximum commercial branch units. Refer to pages 3 and 4 for meter center available short circuit current ratings.



DJM circuit breaker has adjustable trip settings from 160–400 A for field adjustment.

Optional Ringless Commercial Meter Socket Features Barrel lock head protector kit, catalog number MMBLC (one kit covers six meter sockets) is available for field-installation.



DJM circuit breaker seal kit, catalog number 29375, is available for field-installation.



Knockout in individual meter socket cover is provided for barrel lock head protector kit.

• •

Secure head protector kit to cover with lock nut provided. Barrel lock not provided.

Ringless-Type Individual Meter Socket Cover Shown with Barrel Lock Head Protector (Catalog Number MMBLC)

Ringless-Type Individual Meter Socket Cover Shown with Barrel Lock Installed through Cover and Lock Bracket (Reverse View)

28 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Ring-Type Commercial Meter Socket Compartment Standard Features

• • •

3Ø IN, 3Ø OUT branch units (include four horizontal cross bus bars). Seven-jaw meter sockets supplied as standard. EZMT meter sockets are supplied with Test Block Bypass. EZMT branch devices are bondable to meet EUSERC specifications.

225 A Ring-Type EZMT Commercial Branch Units (3Ø OUT) Meter Socket Ringless-Type (Qty)

Seven-Jaw Meter Socket 3Ø IN Catalog Number

Circuit Breaker Type (Three-Pole Only)

225 A Ring Type with Test Block Bypass EZMT311225

One-Position

EZMT331225

QB, QD, QG, or QJ

Two-Position

EZMT332225

QB, QD, QG, or QJ

Three-Position

EZMT333225

QB, QD, QG, or QJ

225 A and 400 A Ringless-Type Commercial Branch Units (3Ø OUT) Meter Socket Ringless-Type (Qty)

Seven-Jaw Meter Socket 3Ø IN Catalog Number

Circuit Breaker Type (Three-Pole Only)

225 A Ringless without Bypass Two-Position

EZMR332225 EZMR332225CU

QB, QD, QG, or QJ

Three-Position

EZMR333225 EZMR333225CU

QB, QD, QG, or QJ

Four-Position

EZMR334225 EZMR334225CU

QB, QD, QG, or QJ

225 A Ringless with Lever Type Bypass and Jaw Release

EZML334225

EZML311400

One-Position

EZML331225 EZML331225CU EZML331225D

QB, QD, QG, or QJ

Two-Position

EZML332325 EZML332225CU EZML332225D

QB, QD, QG, or QJ

Three-Position

EZML333225 EZML333225CU EZML333225D

QB, QD, QG, or QJ

Four-Position

EZML334225 EZML334225CU EZML334225D

QB, QD, QG, or QJ

400 A Ringless with Lever Type Bypass and Jaw Release One-Position

EZML331400

DJM36400E20 1

Two-Position

EZML332400

DJM36400E20 1

400 A Ringless Type K with Manual Bypass Provision 225 A Ringless-Type Meter Socket, Seven-Jaw without Bypass Shown with Line and Load Side Blade Guides

225 A Ringless-Type Individual Meter Socket Cover Shown with Stainless Steel Hasp and Latch for Use with Utility Seals

1

• • • • • 400 A Ringless-Type Individual Meter Socket Cover

EZMK331400

DJM36400E20 1

Two-Position

EZMK332400

DJM36400E20 1

Factory-installed.

Ringless Commercial Meter Socket Compartment Standard Features



400 A Ringless-Type Meter Socket, Five-Jaw with Lever Type Bypass Shown with Lexan Shield over Line and Load Meter Jaws

One-Position

• •

3Ø IN, 3Ø OUT branch units (include four horizontal cross bus bars). Seven-jaw meter sockets supplied as standard. 320 A continuous duty rated meter sockets are supplied with lever-type bypass. Lever-type bypass meter socket is supplied with jaw release. Lexan shield supplied as an integral part of meter socket assembly and used as a guide to assist mounting of utility meter. Individual ringless-type meter socket covers are supplied with stainless steel hasps that extend through cover and stainless steel latches for sealing covers to branch unit while utility meter or closing plate is mounted in meter socket. Ringless meter socket covers have provisions to accept utility seals including plastic padlocks, lead and wire seals, and barrel locks to prevent unauthorized access to meter socket compartment. 400 A continuous duty rated meter sockets are supplied with a K-base bolt-on. 400 A K-base bolt-on are supplied with manual bypass provision. 29

07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers 225 A Tenant Circuit Breaker Compartment 225 A maximum commercial branch units will accept 70–225 A three-pole bolt-on type QB, QD, QG, or QJ circuit breakers. (Order circuit breakers separately.) Refer to pages 3 and 4 for meter center available short circuit current ratings.

400 A Tenant Circuit Breaker Compartment

Q-Frame Circuit Breaker Installed



DJM36400E20 circuit breakers are factory-installed into 400 A maximum commercial branch units. Refer to pages 3 and 4 for meter center available short circuit current ratings.



DJM circuit breaker has adjustable trip settings from 160–400 A.

Optional Ringless Commercial Meter Socket Features Barrel lock head protector kit, catalog number MMBLC, (one kit covers six meter sockets), is available for field-installation.



Knockout in individual meter socket cover is provided for barrel lock head protector kit.

• •

Secure head protector kit to cover with lock nut, provided. Barrel lock not provided.

DJM Circuit Breaker Installed

Ringless-Type Individual Meter Socket Cover Ringless-Type Individual Shown with Barrel Lock Meter Socket Cover Shown with Barrel Lock Installed through Cover and Lock Bracket Head Protector (Reverse View) (Catalog Number MMBLC)

30 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Factory Phase Balancing

Factory Phase Balancing Branch unit meter sockets are phase balanced at the factory according to the following table: Meter Socket (Quantity)

Catalog Number

AØ—BØ (Quantity)

AØ—CØ (Quantity)

BØ—CØ (Quantity)

125 A Branch Units (used on 120/208 Vac, 1Ø3W service derived from a 208Y/120 Vac, 3Ø4W system)

Three-Position

EZM313125

1

1

1

Four-Position

EZM314125

1

2

1

Five-Position

EZM315125

2

1

2

Six-Position

EZM316125

2

2

2

Three-Position

EZMR313125

1

1

1

Four-Position

EZMR314125

1

2

1

Five-Position

EZMR315125

2

1

2

Six-Position

EZMR316125

2

2

2

Three-Position

EZMH313125

1

1

1

Four-Position

EZMH314125

1

2

1

Five-Position

EZMH315125

2

1

2

Six-Position

EZMH316125

2

2

2

225 A Branch Units (used on 120/208 Vac, 1Ø3W service derived from a 208Y/120 Vac, 3Ø4W system)

EZM314125

Two-Position

EZM312225

1

0

Three-Position

EZM313225

1

1

1 1

Four-Position

EZM314225

1

2

1

Two-Position

EZMR312225

1

0

1

Three-Position

EZMR313225

1

1

1

Four-Position

EZMR314225

1

2

1

Two-Position

EZMH312225

1

0

1

Three-Position

EZMH313225

1

1

1

Four-Position

EZMH314225

1

2

1

Two-Position

EZML312225

1

0

1

Three-Position

EZML313225

1

1

1

Four-Position

EZML314225

1

2

1

400 A Branch Units (used on 120/208 Vac, 1Ø3W service derived from a 208Y/120 Vac, 3Ø4W system)

One-Position

EZML311400

0

1

0

Two-Position

EZML312400

1

0

1

NOTE: Refer to page 27 for branch units in the field.

31 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Factory Phase Balancing Phase Balancing Flexibility The major benefit of factory phase balancing is that most jobs will not require field phase balancing. To see if meter socket phase balancing in the field is required (refer to wiring diagram for complete instructions): A. Determine if the load in amperes on each phase of the transformer using handle rating of tenant circuit breakers installed at each number of meter sockets. Use Phase Balancing Chart to determine total number of connections each meter socket makes on each phase of transformer. B. If phase balancing is required, determine which meter sockets should be changed to properly phase balance metering equipment lineup. C. Once meter socket(s) is selected to be phase balanced, remove individual meter socket cover from each meter socket to be phase balanced. The vertical bus bars running top to bottom in the branch unit behind each meter socket are phased: AØ, BØ, CØ, left to right. D. By moving only the line side meter socket “Z” shaped connectors per meter socket to be changed, phase balancing can easily be accomplished on-site: Possible Ending Position (by moving only one “Z” connector)

Starting Position AØ and BØ

can be changed to

AØ and CØ

AØ and CØ

can be changed to

AØ and BØ or BØ and CØ

BØ and CØ

can be changed to

AØ and CØ

To change an AØ and CØ meter socket to a BØ and CØ meter socket:

32 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers EZM Main Device Types and Configurations

EZM Main Device Types and Configurations EZM main devices are available as main circuit breakers, main fusible switches, or main lug terminal boxes; for use in single-phase or three-phase applications. An EZM main device is required upstream from EZM branch units even in the case of the NEC six Disconnect rule. EZM main devices ending in “-CB”, “-FS”, or “-TB” are configured for overhead (top feed) or underground (bottom feed) service, and are supplied with lugs. EZM main devices ending in “-CBU”, “-FSU”, or “-TBU” are configured for underground (bottom feed) service only, and are equipped with lug landing pads (lugs must be ordered separately). Circuit Breaker Main Devices (Fed from Overhead or Underground Service)

Service Type

Ampere Rating

Catalog Number

Circuit Breaker1

Service Line Phase Line Neutral Grounding Terminal Terminal Terminal Wire Range Wire Range Wire Range (AWG-kcmil, (AWG-kcmil, (AWG-kcmil, Al/Cu) Al/Cu) Al/Cu)

1Ø IN Circuit Breaker Main Devices (Fed from Overhead or Underground Service) EZM1400CB

LHP264002

600

EZM1600CB

MHP266002 (3) 3/0–5003

(4) 3/0–5005

(1) 6–300

800

EZM1800CB

MHP268002 (3) 3/0–5003

(4) 3/0–5005

(1) 6–300

1000

EZM11000CB MHP2610002 (3) 3/0–5003

(4) 3/0–5005

(1) 6–300

1200

PAF2026 with (4) 1/0–750 or (4) 1/0–750 or EZM11200CB (1) 6–300 PA21200RC (8) 1/0–250 (8) 1/0–250

1600

EZM11600CB

2000

EZM12000CB

EZM1800CB

1Ø3W, 120/240 Vac

(1) 1/0–600 or (1) 1/0–600 or (1) 6–300 (2) 1/0–2503 (2) 1/0–2504

400

PAF2026 with (6) 1/0–750 or (6) 1/0–750 or (1) 6–300 PA21600RC (12) 1/0–250 (12) 1/0–250 RJF26200

(6) 1/0–750 or (6) 1/0–750 or (1) 6–300 (12) 1/0–250 (12) 1/0–250

3Ø IN Circuit Breaker Main Devices (Fed from Overhead or Underground Service)

3Ø4W, 208Y/120 Vac or 240/120 Vac Delta EZM31600CB

(1) 1/0–600 or (1) 1/0–600 or (1) 6–300 (2) 1/0–2503 (2) 1/0–2504

400

EZM3400CB

LHP364002

600

EZM3600CB

MHP366002 (3) 3/0–5003

(4) 3/0–5005

(1) 6–300

800

EZM3800CB

MHP368002 (3) 3/0–5003

(4) 3/0–5005

(1) 6–300

1000

EZM31000CB MHP3610002 (3) 3/0–5003

(4) 3/0–5005

(1) 6–300

1200

PAF2036 with (4) 1/0–750 or (4) 1/0–750 or (1) 6–300 EZM31200CB PA31200RC (8) 1/0–250 (8) 1/0–250

1600

EZM31600CB

2000

EZM32000CB

PAF2036 with (6) 1/0–750 or (6) 1/0–750 or (1) 6–300 PA31600RC (12) 1/0–250 (12) 1/0–250 RJF36200

(6) 1/0–750 or (6) 1/0–750 or (1) 6–300 (12) 1/0–250 (12) 1/0–250

1

Supplied factory-installed.

2

Handle extension available, order kit AHEXLI. Handle is hinged, allowing it to be tucked under door on cover.

3

Alternate lug kits are available for use on line side of circuit breaker (refer to most current Digest).

4

Alternate neutral lug available, order one MMLK500 for use of two 3/0 AWG–500 kcmil Al/Cu (includes three two-barrel lugs). Neutral will accommodate one two-barrel lug only.

5

Alternate neutral lugs available, order one MMLK250 for use of one 1/0 AWG–600 kcmil Al/Cu or two 1/0 AWG–250 kcmil Al/Cu (includes three two-barrel lugs). Neutral will accommodate two two-barrel lugs only.

EZM32000CB

33 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers EZM Main Device Types and Configurations Circuit Breaker Main Devices (Fed from Underground Service Only)

Service Type

Ampere Catalog Number Rating

Service Line Phase and Grounding Neutral Lug Landing Terminal Pads provided for use Wire with Crimp-Type Lugs Range (Two-Hole Mounting) (AWGQuantity of Lugs kcmil, permitted per Pad Al/Cu)

Circuit Breaker 1

1Ø IN Circuit Breaker Main Devices (Fed from Underground Service Only)

1Ø3W, 120/240 Vac

EZM1800CBU

400

EZM1400CBU 2

LHF26400 3

14

(1) 6–300

600

EZM1600CBU

2

3

24

(1) 6–300

800

EZM1800CBU 2

MHF26800 3

24

(1) 6–300

1000

EZM11000CBU 2 MHF2210003

34

(1) 6–300

1200

EZM11200CBU 2 MHF2212003

34

(1) 6–300

4

(1) 6–300

MHF26600

5

PA2026 with PA21600RC

1600

EZM11600CBU

2000

EZM12000CBU 5 RJF26200

6

(6) 1/0–750 or (12) 1/0–250

(1) 6–300

3Ø IN Circuit Breaker Main Devices (Fed from Underground Service Only)

3Ø4W, 208Y/120 Vac or 240/120 Vac Delta

400

EZM3400CBU 2

600

EZM3600CBU

2

800

EZM3800CBU 2

LHF36400 3

14

(1) 6–300

3

24

(1) 6–300

MHF36800 3

24

(1) 6–300

1000

EZM31000CBU 2 MHF3210003

34

(1) 6–300

1200

EZM31200CBU 2 MHF3212003

34

(1) 6–300

PAF2036 with PA31600RC

4

(1) 6–300

MHF36600

5

1600

EZM31600CBU

2000

EZM32000CBU 5 RJF36200

6

(6) 1/0–750 or (12) 1/0–250

(1) 6–300

1

Supplied factory-installed.

2

Meets Electrical Utility Service Equipment Requirements Committee (EUSERC) Standards for West Coast based utilities.

3

Handle extension available, order kit AHEXLI. Handle is hinged, allowing it to be tucked under door on cover.

4

Order lugs separately.

5

Does not meet EUSERC Standards.

Grounding Provisions Service Grounding EZM1800CBU



Each main device is equipped with a service grounding lug and provisions to bond the neutral to the enclosure when required.



EZM main devices are suitable for use as service equipment.

Grounding Lug and Isolated Main Neutral Bus as Installed at Factory on Main Devices EZM32000CBU

Service Grounding Lug, Bonding Strap, and Bonded Main Neutral Bus as installed on Main Devices at Job Site as Required for use as Service Equipment

34 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers EZM Main Device Types and Configurations Fusible Switch Main Devices (Fed from Overhead or Underground Service)

Service Ampere Type Rating

Catalog Numbers 1

Line Phase Terminal Wire Range (AWG-kcmil, Al/Cu)

Molded Case Switch 2

Service Line Neutral Grounding Terminal Terminal Wire Range Wire Range (AWG-kcmil, (AWG-kcmil, Al/Cu) Al/Cu)

1Ø IN Fusible Switch Main Devices (Fed from Overhead or Underground Service)

1Ø3W, 120/240 Vac

(1) 1/0–600 or (1) 1/0–600 or (1) 6–300 (2) 1/0–250 4 (2) 1/0–250 5

400

EZM1400FS

LHP26000M 3

600

EZM1600FS

MHP260006M 3 (3) 3/0–500 4

(4) 3/0–500 6

(1) 6–300

800

EZM1800FS

MHP260008M 3 (3) 3/0–500 4

(4) 3/0–500 6

(1) 6–300

1200

EZM11200FS PHF260000M

(4) 1/0–750 or (4) 1/0–750 or (1) 6–300 (8) 1/0–250 (8) 1/0–250

3Ø IN Fusible Switch Main Devices (Fed from Overhead or Underground Service) 3Ø4W, 208Y/120 Vac or 240/120 Vac Delta EZM3800FS

(1) 1/0–600 or (1) 1/0–600 or (1) 6–300 (2) 1/0–250 4 (2) 1/0–250 5

400

EZM3400FS

LHP36000M 3

600

EZM3600FS

MHP360006M 3 (3) 3/0–500 4

(4) 3/0–500 6

(1) 6–300

800

EZM3800FS

MHP360008M 3 (3) 3/0–500 4

(4) 3/0–500 6

(1) 6–300

1

Fuses not included. Order 300 V Class T fuses.

2

Supplied factory-installed.

3

Handle extension available, order kit AHEXLI. Handle is hinged, allowing it to be tucked under door on cover.

4

Alternate lug kits are available for use on line side of molded case switch (refer to most current Digest).

5

Alternate neutral lug available, order one MMLK500 for use of two 3/0 AWG-500 kcmil Al/Cu (includes three two-barrel lugs). Neutral will accommodate one two-barrel lug only.

6

Alternate neutral lugs available, order one MMLK250 for use on 1/0 AWG-600 kcmil Al/Cu or two 1/0 AWG-250 kcmil Al/Cu (includes three two-barrel lugs). Neutral will accommodate two two-barrel lugs only.

Fusible Switch Main Devices (Fed from Underground Service Only)

Service Ampere Type Rating

Catalog Numbers 1

Molded Case Switch 2

Line Phase and Neutral Lug Landing Pads provided for use with Crimp-Type Lugs (Two-Hole Mounting) Quantity of Lugs Permitted per Pad

Service Grounding Terminal Wire Range (AWGkcmil, Al/Cu)

1Ø IN Fusible Switch Main Devices (Fed from Underground Service Only) 1Ø3W, 120/240 Vac

EZM3800FS

400

EZM1400FSU 3

LHF26000M 4

15

(1) 6–300

600

EZM1600FSU 3

MHF260006M 4

25

(1) 6–300

800

EZM1800FSU 3

MHF260008M 4

25

(1) 6–300

1200

EZM11200FSU 3 PHF260000M

35

(1) 6–300

3Ø IN Fusible Switch Main Devices (Fed from Underground Service Only) 3Ø4W, 208Y/120 Vac or 240/120 Vac Delta

400

EZM3400FSU 3 LHF36000M 4

15

(1) 6–300

600

EZM3600FSU 3 MHF360006M 4

25

(1) 6–300

800

EZM3800FSU 3 MHF360008M 4

25

(1) 6–300

1

Fuses not included. Order 300 V Class T fuses.

2

Supplied factory-installed.

3

Meets Electrical Utility Service Equipment Requirements Committee (EUSERC) Standards for West Coast based utilities.

4

Handle extension available, order kit AHEXLI. Handle is hinged, allowing it to be tucked under door on cover.

5

Order lugs separately.

35 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers EZM Main Device Types and Configurations Main Lugs Terminal Boxes (Fed from Overhead or Underground Service) Service Ampere Type Rating

Line Phase Neutral Service Ground Terminal Wire Range Terminal Wire Range (AWG-kcmil, Al/Cu) (AWG-kcmil, Al/Cu)

Catalog Number

1Ø IN Main Lugs Terminal Boxes (Fed from Overhead or Underground Service)

1Ø3W, 120/240 Vac

225

EZM1225TB

(1) 4–300

(1) 6–300

400

EZM1400TB

(2) 3/0–500 1

(1) 6–300

600

EZM1600TB

(2) 1/0–750 or (4) 1/0–300

(1) 6–300

800

EZM1800TB and EZM1800TBCU

(4) 3/0–500 2

(1) 6–300

1600

EZM11600TB

(6) 1/0–600 or (12) 1/0–300

(1) 6–300

2000

EZM12000TB

(6)

3

(1) 6–300

3Ø IN Main Lugs Terminal Boxes (Fed from Overhead or Underground Service)

EZM1800TB

3Ø4W, 208Y/120 Vac or 240/120 Vac Delta

225

EZM3225TB

(1) 4–300

(1) 6–2/0

400

EZM3400TB

(2) 3/0–500 1

(1) 6–300

600

EZM3600TB

(2) 1/0–750 or (4) 1/0–300

(1) 6–300

(4) 3/0–500

2

800

EZM3800TB

1600

EZM31600TB

(6) 2–600

(1) 6–300

2000

EZM32000TB

(6) 3

(1) 6–300

(1) 6–300

1

Alternate lug kits available with the use of lug landing kit EZMSK2.

2

Alternate lug kit available, order MMLK250 kits for two 1/0 AWG–600 kcmil or four 1/0 AWG–250 kcmil Al/Cu (each kit includes three two-barrel lugs) each bus bar will accept two two-barrel lugs. For 1Ø applications, order two kits. For 3Ø applications, order three kits.

3

Order lugs separately. Device provided with 6 lug landing pads per phase and neutral for use with mechanical or crimp type lugs.

Main Lugs Terminal Boxes (Fed from Underground Service)

Service Ampere Type Rating

EZM1800TB

Line Phase and Neutral Lug Landing Pads provided for use Service Ground with Crimp-type Lugs Terminal Wire Range (Two-hole Mounting) (AWG-kcmil, Al/Cu) Quantity of Lugs Permitted per Pad

Catalog Number1 2 3

1Ø IN Main Lugs Terminal Boxes (Fed from Underground Service Only) 1Ø3W, 120/240 Vac

400

EZM1400TBU

1 (order lugs separately)

800

EZM1800TBU

2 (order lugs separately)

(1) 6–300 (1) 6–300

1200

EZM11200TBU 4

3 (order lugs separately)

(1) 6–300

3Ø IN Main Lugs Terminal Boxes (Fed from Underground Service Only) 3Ø4W, 208Y/120 Vac or 240/120 Vac Delta

400

EZM3400TBU

1 (order lugs separately)

(1) 6–300

800

EZM3800TBU

2 (order lugs separately)

(1) 6–300

3 (order lugs separately

(1) 6–300

1200

EZM31200TBU

4

1

For mechanical lugs (3/0 AWG–600 kcmil) order kit CMELK4, kit includes four lugs only; multiple kits may be required.

2

Meets Electrical Utility Service Equipment Requirements Committee (EUSERC) Standards for West-coast based utilities.

3

Tap box is suitable for use on Line or Load side of service equipment. Supplied with isolated neutral and provided with neutral bonding kit for use as required.

4

Supplied with copper horizontal bus bars and aluminum vertical bus bars.

EZM32000TB

36 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers EZM Main Device Types and Configurations EZM Main Device Standard and Alternate Lugs Alternate Lugs by Manufacturer, Catalog Number, Wire Range AWG-kcmil, Crimping Tool, and Quantity Per Line Side Phase and Neutral (Order Lugs Separately)

TA-600-2N1

TA-800-2N

AU-600-2N (Two-Barrel)

750-1000 Al

2-600 Al/Cu

300-800 Al/Cu

250-600 Al/Cu

2-600 Al/Cu

300-800 Al/Cu

(2) 2-600 Al/Cu

Mechanical

IDT-12

Mechanical

Mechanical

L1D2-800

2ACL-600

500-750 Cu

L1D2-600

LID2-800

250-600 Cu

2AB2-600 (Two-Barrel

LID2-600

Line Side Neutral Terminals

VACL-1000-12BN

Line Side Phase Terminals

CMC

VHCL-750-12BN

Catalog Number

ILSCO

VHCL-600-12BN

ANDERSON

A1B2-600-2

Standard Lugs (FactoryInstalled)

(2) 2-600 2-600 (2) 2-600 300-800 Al/Cu Al/Cu Al/Cu Al/Cu

VC-6

VC-7

VC-8

EZM1400CB2 3

(1) AL400LA

(1) MMLK250



















Mechanical —





Mechanical

EZM1600CB2 4

(1) AL900MA

(2) MMLK500



























EZM1800CB2 4

(1) AL900MA

(2) MMLK500



























EZM11000CB2 4 (1) AL900MA

(2) MMLK500





























EZM11200CB5

(4) 40251-136-50 (4) 40251-136-50

4

4



4





4



2

4

2





EZM11600CB5

(6) 40251-136-50 (6) 40251-136-50

6

6



6





6



3

6

3





EZM12000CB5

(6) 40251-136-50 (6) 40251-136-50

6

6







6















EZM3400CB2 3

(1) AL400LA

(1) MMLK250



























EZM3600CB2 4

(1) AL900MA

(2) MMLK500



























EZM3800CB2 4

(1) AL900MA

(2) MMLK500



























EZM31000CB2 4 (1) AL900MA

(2) MMLK500



























EZM31200CB5

(4) 40251-136-50 (4) 40251-136-50

4

4



4





4



2

4

2





EZM31600CB5

(6) 40251-136-50 (6) 40251-136-50

6

6



6





6



3

6

3





EZM32000CB5

(6) 40251-136-50 (6) 40251-136-50

6

6







6















EZM1400CBU

Studs (1 lug)

Studs (1 lug)

1

1

1

1





1



1

1

1





EZM1600CBU

Studs (2 lugs)

Studs (2 lugs)

2

2



2





2



1

2

1





EZM1800CBU

Studs (2 lugs)

Studs (2 lugs)

2

2



2





2



1

2

1





EZM11000CBU

Studs (3 lugs)

Studs (3 lugs)

3

3



3





3



2

3

2





EZM11200CBU

Studs (3 lugs)

Studs (3 lugs)

3

3



3





3



2

3

2





EZM11600CBU

Studs (6 lugs)

Studs (6 lugs)

6

6



6



6

6

6

3

6

3

6

6

EZM12000CBU

Studs (6 lugs)

Studs (6 lugs)

6

6



6

66

6

6

66



6



6

66

EZM3400CBU

Studs (1 lug)

Studs (1 lug)

1

1

1

1





1



1

1

1





EZM3600CBU

Studs (2 lugs)

Studs (2 lugs)

2

2



2





2



1

2

1





EZM3800CBU

Studs (2 lugs)

Studs (2 lugs)

2

2



2





2



1

2

1





EZM31000CBU

Studs (3 lugs)

Studs (3 lugs)

3

3



3





3



2

3

2





EZM31200CBU

Studs (3 lugs)

Studs (3 lugs)

3

3



3





3



2

3

2





EZM31600CBU

Studs (6 lugs)

Studs (6 lugs)

6

6



6



6

6

6

3

6

3

6

6

EZM32000CBU

Studs (6 lugs)

Studs (6 lugs)

6

66



6

66

6

6

66



6



6

66

EZM1400FS2 3

(1) AL400LA

(1) MMLK250



























EZM1600FS2 4

(1) AL900MA

(2) MMLK500



























EZM1800FS2 4

(1) AL900MA

(2) MMLK500



























EZM11200FS5

(4) 40251-136-50 (4) 40251-136-50

4

4



4



4

4



2

4

2





EZM3400FS2 3

(1) AL400LA

(1) MMLK250



























EZM3600FS2 4

(1) AL900MA

(2) MMLK500



























EZM3800FS2 4

(1) AL900MA

(2) MMLK500



























EZM1400FSU

Studs (1 lug)

Studs (1 lug)

1

1

1

1





1



1

1

1





EZM1600FSU

Studs (2 lugs)

Studs (2 lugs)

2

2



2





2



1

2

1





EZM1800FSU

Studs (2 lugs)

Studs (2 lugs)

2

2



2





2



1

2

1





EZM11200FSU

Studs (3 lugs)

Studs (3 lugs)

3

3



3



3

3



2

3

2





EZM3400FSU

Studs (1 lug)

Studs (1 lug)

1

1

1

1





1



1

1

1





1

This lug is available from Schneider Electric. Order catalog number CMELK4; kit includes four lugs.

2

Alternate lug kits are available for use on line side terminals of molded case circuit breaker or molded case switch (refer to most current Digest). Alternate neutral lugs available, order one kit MMLK500 for two 3/0 AWG–500 kcmil Al/Cu (kit includes three two-barrel lugs). Neutral will accommodate one two-barrel lug only. Alternate neutral lugs available, order one kit MMLK250 for one 1/0 AWG–600 kcmil Al/Cu or two 1/0 AWG–250 kcmil (kit includes three two-barrel lugs). Neutral will accommodate two two-barrel lugs only.

3 4 5

Lugs are supplied factory-installed on the lug landing pads of this device. Alternate lugs are available.

6

Wire range is limited to 750 kcmil max. in this device to comply with wire bending space requirements.

37 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers EZM Main Device Types and Configurations Alternate Lugs by Manufacturer, Catalog Number, Wire Range AWG-kcmil, Crimping Tool, and Quantity Per Line Side Phase and Neutral (Order Lugs Separately)

AU-600-2N (Two-Barrel)

250-600 Al/Cu

2-600 Al/Cu

300-800

(2) 2-600 Al/Cu

Mechanical

IDT-12

Mechanical

Mechanical

L1D2-800

TA-800-2N

300-800

L1D2-600

TA-600-2N1

2-600 Al/Cu

2AB2-600 (Two-Barrel

2ACL-600

CMC

LID2-800

250-600 500-750 750-1000 Cu Cu Al

ILSCO

LID2-600

Line Side Neutral Terminals

VACL-1000-12BN

Line Side Phase Terminals

VHCL-750-12BN

Catalog Number

VHCL-600-12BN

ANDERSON

A1B2-600-2

Standard Lugs (FactoryInstalled)

(2) 2-600 2-600 (2) 2-600 300-800 Al/Cu Al/Cu Al/Cu Al/Cu

VC-6

VC-7

VC-8

EZM3600FSU

Studs (2 lugs)

Studs (2 lugs)

2

2



2





2



1

Mechanical 2

1



Mechanical

EZM3800FSU

Studs (2 lugs)

Studs (2 lugs)

2

2



2





2



1

2

1





EZM1225TB

(1) 40251-052-50

(1) 40251-052-50



























EZM1400TB2 3 4

(1) MMLK500

(1) MMLK500

1

1



1

1



1

1



1





1

EZM1600TB2 5

(2) 40251-136-50

(2) 40251-136-50



























EZM1800TB6

(2) MMLK500

(2) MMLK500



























EZM11600TB

(6) 40251-136-50 (6) 40251-136-50



























EZM3225TB

(1) 40251-052-50

(1) 40251-052-50



























EZM3400TB2 3 7

(1) MMLK500

(1) MMLK500

1

1



1

1



1

1



1





1

EZM3600TB2 5

(2) 40251-136-50

(2) 40251-136-50



























EZM3800TB8

(2) MMLK500

(2) MMLK500



























EZM12000TB

Studs (6 lugs)

Studs (6 lugs)

6

6

6

6

6



6

6

6

6

6

6

6

EZM31600TB

(6) 40251-136-50 (6) 40251-136-50





























EZM32000TB

Studs (6 lugs)

Studs (6 lugs)

6

6

6

6

6



6

6

6

6

6

6

6

EZM1400TBU5

Studs (1 lug)

Studs (1 lug)

1

1



1

1



1

1



1





1

EZM1800TBU5

Studs (2 lugs)

Studs (2 lugs)

2

2

2

2



2

2



2





2

EZM11200TBU5

Studs (3 lugs)

Studs (3 lugs)

3

3

3

3



3

3



3





3

EZM3400TBU/CU5

Studs (1 lug)

Studs (1 lug)

1

1

1

1



1

1



1





1

EZM3800TBU/CU5

Studs (2 lugs)

Studs (2 lugs)

2

2

2

2



2

2



2





2

EZM31200TBU/CU5 Studs (3 lugs)

Studs (3 lugs)

3

3

3

3



3

3



3





3

1 2 3 4 5 6 7 8

This lug kit is available from Schneider Electric. Order catalog number CMELK4; kit includes four lugs. Alternate lug requires the use of lug landing kit part number EZMSK2 (order separately). See pad drawing or wiring diagram for additional alternate lugs. Alternate lug kit available from Schneider Electric. Order one kit MMLK250 for one 1/0 AWG–600 kcmil or 2 1/0 AWG–250 kcmil Al/Cu (kit includes three two-barrel lugs) each bus bar will accept one two-barrel lug. See pad drawing for additional alternate lugs. Alternate lug kit available from Schneider Electric. Order two MMLK250 kits for two 1/0 AWG–600 kcmil or four 1/0 AWG–250 kcmil Al/Cu (each kit includes three two-barrel lugs) each bus bar will accept two two-barrel lugs. Alternate lug kit available. order two MMLK250 kits for one 1/0 AWG–250kcmil or two 1/0 AWG–250kcmil Al/Cu (each kit includes three two-barrel lugs) each bus bar will accept one two-barrel lug. Alternate lug kit available. Order three MMLK250 kits for two 1/0 AWG–600 kcmil or four 1/0 AWG–250 kcmil Al/Cu (each kit includes three two-barrel lugs) each bus bar will accept two two-barrel lugs.

38 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers EZM Main Device Types and Configurations

EZM Mains Devices Number Segment

Character

Device Name

Description

EZM

EZM

EZ Meter-Pak Meter Center

1

1Ø3W

1

1000

CB

U

CU

3

125

CU

Service Feed 3

3Ø4W 225 A 400 A 600 A 800 A

Mains Rating 1000 A 1200 A 1600 A 2000 A

Main Type

CB

Main Circuit Breaker

FS

Main Fusible Switch

TB

Terminal Box

Blank

Overhead/Underground

U

Underground Only, Meets EUSERC Standards up to 1200 A max.

Blank

Aluminum Horizontal Cross Bus Bar up to 1000 A max.

CU

Copper Horizontal Cross Bus Bar

Feed Direction

Special Construction

EZM Branch Units Number Segment Character Device Name

Description

EZM

EZM

EZ Meter-Pak Meter Center

Blank

Ring Type

R

Ringless Type with 5th Jaw

H

Ringless with Horn Bypass and 5th Jaw

L

Lever Bypass with 5th Jaw, 7th Jaw if Three-Phase

T

Ring Type Test-Block Bypass EUSERC

R

1

1

Socket/Bypass Type

K

K-Base Bolt-On Type

1

1Ø3W

3

3Ø4W

1

1Ø3W

3

3Ø4W

Meter Sockets Available

1, 2, 3, 4, 5, or 6

Service Feed

Load Feed Number of Meter Sockets Maximum Tenant Circuit Breaker Amperage

125 A 225 A 400 A Blank

Aluminum Horizontal Cross Bus Bar

CA

For 240/120 Vac Delta Systems

CU

Copper Horizontal Cross Bus Bar

D

Removable Drip Hood with Indoor Top Endwall with Knockouts

Special Construction M10

10-Inch Meter Centers

X

1200 A Copper Horizontal Cross Bus Bar

39 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Dimensions and Knockouts

Dimensions and Knockouts Box Side

18.66 [474] 14.50 [368]

11.50 [292] Nut

Captive Screw

Torque to 50 lb-in.

Omitted on 1Ø Units

Hanging Mounting Rail Hex Nut (2)

3.44 [87] Omitted on 1Ø Units

53.97 [1371]

Gasket Top View

2.00 [51]

Square Neck Bolt

(1) Sealing Wing Nut

Line Phase Lugs Line Neutral

(1) Sealing Wing Nut

Closing Cap

Box Side Right

(1) (1)

Closing Cap

(1)

(1) (1)

Gasket 14.50 [368] 18.48 [469]

E, F, G, H, I, J

9.13 [232] 11.06 [281]

5.09 [129]

3.00 [76]

Hex Nut (2)

Captive (2) Screw

Box Side Left

34.30 [871] 24.75 [629]

1.00 [25.5]

Gasket Right Side Closing Cap

Left Side Closing Cap 30.19 [767] 24.00 [610]

18.33 [466]

A, B 11.06 [281] Omitted on 1Ø Units

1.12 [28] 2.92 [74]

5.61 5.61 [142] [142]

0.91 [23]

Hanging Mounting Rail

3.44 [87]

EZM1400CB, EZM3400CB EZM1600CB, EZM3600CB EZM1800CB, EZM3800CB EZM11000CB, EZM31000CB

Omitted on 1Ø Units

61.19 [1554]

38.13 [969]

19.38 [492]

Knockouts Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

0.50

13

0.88

22

Line Phase Lugs

Line Neutral

21.91 [557]

Symbol A B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

24.00 [610] 30.00 [762]

17.83 [453]

E, F, G, H, I, J 3.07 [78]

17.83 A, B [453]

1.16 [29] 4.81 [122]

6.75 [171]

6.75 [171]

6.75 [171]

in. Dimensions: [mm]

0.92 [23]

EZM11200CB, EZM31200CB EZM11600CB, EZM31600CB

40 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Dimensions and Knockouts Box Side

30.19 [767] 24.00 [610]

18.31 [465]

0.31 [8]

Nut

Captive Screw

Omitted on 1Ø Units

Torque to 50 lb-in.

Hanging Mounting Rail

3.44 [87] Typ. Omitted on 1Ø Units

Gasket Top View 2.00 [51]

Hex Nut (2)

68.91 [1750]

Square Neck Bolt (2)

(1) Line Phase Lugs

44.50 [1130] Line Neutral

Sealing Wing Nut

Box Side Left

31.35 [796]

27.35 [695]

Closing Cap (1) Grounding Lug

24.00 [610]

17.89 [454]

(1)

(1) Gasket

30.00 [762]

Left Side Closing Cap 1.00 [25.5]

17.89 [454]

Hex Nut (2)

Captive Screw

(1)

EZM12000CB, EZM32000CB Sealing Wing Nut

NOTE: No knockouts provided. 30.19 [767] 24.00 [610]

21.46 [545]

0.20 [5]

Box Side Right

Closing Cap (1)

30.67 [779]

Omitted on 1Ø Units

0.34 [9] Top of Mounting Channel

3.44 [87]

(1) Gasket Right Side Closing Cap

71.09 [1806]

30.67 [779]

30.39 [772]

1/2-13 in. studs and keps nuts provided. 2.69 [68] Typical

37.62 [956] 1.75 [44]

Lug Landing Pad Detail 1.81 [46] See Detail B

20.73 [527]

EZM12000TB, EZM32000TB

NOTE: No knockouts provided.

in. Dimensions: [mm]

41 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Dimensions and Knockouts Box Side

18.66 [474] 14.50 [368]

11.50 [292] Nut Captive Screw

Torque to 50 lb-in.

17.72 [450] Omitted on 1Ø Units

Gasket Top View

Hanging Mounting Rail

3.44 [87] Omitted on 1Ø Units

2.00 [51]

Hex Nut (2)

53.97 [1371]

(1) Sealing 34.30 Wing Nut [871]

Line Neutral Lugs Line Phase Lugs

Square Neck Captive Screw Bolt (2)

Hex Nut (2) (1) Sealing Wing Nut

Box Side Left Box Side Right

Closing Cap

16.50 [419]

1.00 [25.5]

Closing Cap

(1)

14.50 [368] 18.48 [469]

E, F, G, H, I, J

(1) Gasket

11.06 [281]

5.09 [129]

3.01 [76]

(1)

(1)

(1)

Gasket Right Side Closing Cap

Left Side Closing Cap

30.19 [767] 24.00 [610]

A, B 11.06 [281]

18.33 [465]

1.12 [28] 2.92 [74]

5.61 5.61 [142] [142]

0.91 [23]

3.44 [87]

Hanging Mounting Rail

EZM1400FS, EZM3400FS EZM1600FS, EZM3600FS EZM1800FS, EZM3800FS 61.19 [1554]

38.13 [968]

Knockouts Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

Symbol

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

19.38 [492]

21.91 [556]

Line Neutral Lugs

Line Phase Lugs 24.00 [610] 30.00 [762]

17.83 [453]

E, F, G, H, I, J 3.07 [78]

4.81 [122]

17.83 A, B [453]

1.16 [29] 6.75 [171]

6.75 [171]

6.75 [171]

0.92 [23]

in. Dimensions: [mm]

EZM11200FS

42 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Dimensions and Knockouts Box Side

11.66 [296] 5.85 [149]

1.74 [44]

6.37 [162]

Nut Captive Screw

See detail C

3.44 [87]

21.81 [554]

Gasket Top View

2.00 [51]

Hex Nut (2)

Square Neck Bolt

(1) Sealing Wing Nut

Omitted on 1Ø Units

5.74 [146]

Torque to 50 lb-in.

0.34 [9]

(1) 5.81 [148]

1.80 [46]

0.27 [7]

Closing Cap (1)

(1) (1)

Gasket Gasket Right Side Closing Cap

Left Side Closing Cap A

See detail B

13.00 [330]

D, E, F, G

17.15 [436] 1.68 [43]

7.09 [180] 0.34 [9]

See detail C

1.21 [31] 0.75 [19]

4.45 [113]

Hex Nut (2) (1) Sealing Wing Nut

Box Side Right

(1) 11.50 [292]

Captive Screw (2)

Box Side Left

Closing Cap

See detail A

1.00 [25.5]

0.32 [8] Top of Mounting Channel

3.62 [92] 11.38 [289] 3.44 [87]

EZM1225TB, EZM3225TB

30.46 [774]

Omitted on 1Ø Units 16.29 [414]

1.00 [25] 0.25 [6]

R 0.19 [5]

9.03 [229] See detail A

1.08 [27] 0.78 [20]

1.50 [38]

Detail A Bottom Mounting Bracket R 0.13 [3] R 0.25 [6]

17.00 [432] Detail B Cover Sealing Latch

1.50 [38]

0.40 [10]

0.38 [10] Detail C Top Mounting Bracket

NOTE: For knockout dimensions, see table on opposite page.

A A, B

3.25 [83]

6.53 [166]

1.80 [46]

0.34 [9]

See detail B E, F, G, H, I, J

6.53 [166]

2.00 [51] 0.89 [23]

5.50 5.75 [140] [146] 17.00 [432]

2.84 [72]

2.86 [73]

EZM1400TB, EZM3400TB EZM1600TB, EZM3600TB

43 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Dimensions and Knockouts Box Side

18.66 [474] 14.50 [368]

11.50 [292] Nut Captive Screw

16.12 [409] Hanging Mounting Rail

3.44 [87] 53.97 [1371]

Omitted on 1Ø Units

2.00 [51]

Hex Nut (2)

Torque to 50 lb-in. Gasket Top View Square Neck Bolt

(1) Sealing Wing Nut

Hex Nut (2) (1)

Captive Screw (2)

Sealing Wing Nut

Box Side Left

34.30 [871]

26.59 [675]

Line Phase Lugs Line Neutral

1.00 [25.5]

Box Side Right

Closing Cap (1)

Closing Cap (1)

(1)

(1)

(1) Gasket 9.13 [232] 11.06 [281]

14.50 [368] 18.48 [469]

E, F, G, H, I, J 3.00 [76]

Left Side Closing Cap

A, B 11.06 [281]

19.93 [506]

1.12 [28] 2.92 [74]

5.61 5.61 [142] [142]

24.00 [610] 1.68 [43]

Gasket Right Side Closing Cap

7.09 [180]

See detail C on page 43

0.91 [23]

EZM1800TB EZM3800TB

0.33 [8] Top of Mounting Channel

3.44 [87] 51.76 [1315]

Omitted on 1Ø Units

20.71 [526]

Knockouts Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

28.01 [712] Line Neutral

See detail A on page 43

Symbol

E

Line Phase Lugs

0.34 [9]

23.93 [608]

1.81 [46]

6.53 [166]

See detail B on page 43 E, F, G, H, I, J

2.97 [75]

A, B

3.00 [76]

5.61 [143] Typ. EZM1800TBCU EZM3800TBCU

0.87 [22] 3.12 [79] in. Dimensions: [mm]

44 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Dimensions and Knockouts

22.48 [571]

Box Side

18.33 [466]

12.94 [329] Nut Captive Screw

See detail C on page 43

Torque to 50 lb-in.

0.33 [8]

Gasket Top of Mounting Channel

3.44 [87]

2.00 [51]

Hex Nut (2)

55.12 [1400]

Square Neck Bolt (2)

(1)

Omitted on 1Ø Units

Sealing Wing Nut Line Phase Lugs

22.37 [568]

Line Neutral

21.06 [535]

29.67 Closing Cap[754] (1) (1)

1.81 [46] A, B 3.80 [97]

Box Side Left

0.34 [9]

See detail A on page 43

2.97 [75]

Top View

12.38 [314]

(1) Gasket Left Side Closing Cap 1.00 [25.5]

See detail B on page 43 E, F, G, H, I, J

Hex Nut (2) (1)

Captive Screw 5.53 [140]

1.06 [27]

1.56 [40]

6.61 6.61 [168] [168] 22.33 [567]

5.06 [129]

Sealing Wing Nut

3.90 [99]

Box Side Right

Closing Cap (1)

EZM11600TB EZM31600TB

(1) Gasket Right Side Closing Cap

Knockouts Conduit Size

Hole Diameter

Symbol in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

in. Dimensions: [mm]

45 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Dimensions and Knockouts Box Side

20.46 [520] 16.30 [414]

11.50 [292]

Nut

Captive Screw

Omitted on 1Ø Units

Hanging Mounting Rail Hex Nut (2)

3.44 [87]

Torque to 50 lb-in. Gasket Top View

2.00 [51]

Square Neck Bolt

(1) Omitted on 1Ø Units

Sealing Wing Nut

Sealing Wing Nut

Box Side Right

Closing Cap

30.25 [768]

Line Phase Pads

49.37 [1254]

Line Neutral Pad

(1)

Closing Cap (1)

(1)

(1)

(1) Gasket Gasket Right Side Closing Cap

Left Side Closing Cap 20.46 [520] 16.30 [414]

16.30 [414] 20.28 [515]

11.06 [281]

E, F, G, H, I, J 3.03 [77]

Hex Nut (2) (1)

Captive Screw (2)

Box Side Left

69.03 [1753]

4.00 [102]

1.00 [25.5]

11.50 [292]

3.44 [87]

Hanging Mounting Rail

A, B 11.06 [281] 69.03 [1753]

1.12 [28] 4.34 [110]

5.80 5.80 [147] [147]

0.91 [23] 4.00 [102]

EZM1400CBU EZM3400CBU

49.36 [1254]

Line Neutral Pad

Line Phase Pads 31.16 [791]

Knockouts Conduit Size

Hole Diameter

Symbol in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

46 © 2008 Schneider Electric All Rights Reserved

11.06 [281]

16.30 [414] 20.28 [515] E, F, G, H, I, J 3.03 [77]

A, B 11.06 [281] 1.12 [28]

4.34 [110]

5.80 5.80 [147] [147]

0.91 [23] EZM1600CBU EZM1800CBU

in. Dimensions: [mm]

07/2008

EZ Meter-Pak® Meter Centers Dimensions and Knockouts Box Side

26.19 [665] 20.00 [508]

11.65 [296]

Nut

Captive Screw

Torque to 50 lb-in. Gasket Top View

2.00 [51]

Hex Hanging Nut (2) Mounting Rail (1)

3.44 [87]

Square Neck Bolt

Sealing Wing Nut

69.03 [1753]

Line Phase Pads

Gasket Right Side Closing Cap

Left Side Closing Cap 34.19 [868] 24.00 [610]

18.33 [466]

Omitted on 1Ø Units

E, F, G, H, I, J

Hanging Mounting Rail

3.44 [87]

A, B 11.10 [282]

Omitted on 1Ø Units

1.13 [29] 8.25 [209]

(1)

(1)

Gasket

11.10 [282]

3.04 [77]

4.75 [121]

Closing Cap

(1)

31.16 [791]

20.00 [508] 26.00 [660]

Box Side Right (1)

Line Neutral Pad

8.25 [209]

Hex Nut (2) (1) Sealing Wing Nut

(1) 49.36 [1254]

Captive Screw (2)

Box Side Left

Closing Cap

4.00 [102]

1.00 [25.5]

70.07 [1780]

0.92 [23]

EZM3600CBU EZM3800CBU

4.28 [109] 26.08 [662]

Line Phase Pads

46.99 [1193]

Line Neutral Pad

Knockouts Conduit Size

Hole Diameter

Symbol in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

17.83 [453]

24.00 [610] 34.00 [864] E, F, G, H, I, J 3.06 [78]

17.83 A, B [453]

1.16 [29] 5.37 [136]

7.75 [197]

7.75 [197]

7.75 [197]

0.92 [23]

in. Dimensions: [mm]

EZM11000CBU, EZM31000CBU, EZM11200CBU, EZM31200CBU

47 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Dimensions and Knockouts 30.19 [767]

1.88 [48]

Box Side

0.86 [22]

18.34 [466]

Nut Captive Screw

17.61 [447]

Torque to 50 lb-in.

37.08 [942]

Gasket Top View 0.62 [16]

71.16 [1807]

29.04 [738]

2.00 [51]

6.75 [171]

1.75 [44] 5.32 [135]

0.97 [25] 6.40 [163]

33.16 [842]

Square Neck Bolt

1.75 [51]

Sealing Wing Nut

1.75 [44]

4.73 [120]

[16]

(1)

1.75 [44]

2.00 [51]

Hex 0.62 Nut (2)

Hex Nut (2) (1) Sealing Wing Nut

Box Side Right

Cap

1.00 [25]

Captive Screw (2)

Box Side Left

2.00 2.00 [51] [51] 0.69 0.69 [18] Closing [18]

2.00 [51]

1.00 [25.5]

(1)

Closing Cap (1)

(1)

(1)

(1) Gasket Left Side Closing Cap

NOTE: No knockouts provided.

Gasket Right Side Closing Cap

30.19 [767]

30.00 [762]

18.31 [465]

24.00 [610]

0.31 [8]

17.89 [454] Hanging Mounting Rail

Omitted on 1Ø Units EZM11600CBU EZM31600CBU

3.44 [87] Typ.

Omitted on 1Ø Units

68.91 [1750]

Line Lug Pads

44.50 [1130]

Line Neutral

26.13 [664]

24.00 [610]

31.35 [796]

Grounding Lug

17.89 [454]

30.00 [762]

17.89 [454]

NOTE: No knockouts provided. EZM12000CBU, EZM32000CBU

in. Dimensions: [mm]

48 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Dimensions and Knockouts Box Side 20.46 [520] 16.30 [414]

11.50 [292]

Nut Captive Screw

Omitted on 1Ø Units

Hanging Mounting Hex Rail 0.62 Nut (2)

3.44 [87]

[16]

(1)

Omitted on 1Ø Units

Gasket Top View

2.00 [51]

Square Neck Bolt

1.75 [51]

Sealing Wing Nut

49.37 [1254] Line Phase Pads

5.00 [127]

Line Neutral Pad

11.06 [281]

16.31 [414] 20.29 [515] E, F, G, H, I, J 3.03 [77]

1.00 [25.5]

Captive Screw (2)

Box Side Right

Cap

(1)

Hex Nut (2) Sealing Wing Nut

Box Side Left

2.00 [51] 0.69 Closing [18]

69.03 [1753]

22.00 [559]

Torque to 50 lb-in.

Closing Cap (1)

(1)

(1) 20.46 [520]

(1)

Gasket Left Side Closing Cap 16.30 [414]

Gasket Right Side Closing Cap 11.50 [292]

3.44 [87]

Hanging Mounting Rail

A, B 11.06 [281] 1.12 [28]

4.34 [110]

5.80 5.80 [147] [147]

0.91 [23]

69.03 [1753]

EZM1400FSU EZM3400FSU Line Phase Pads

Line Neutral Pad

26.06 [662]

Knockouts Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

49.36 [1254]

4.75 [121]

Symbol

E, F, G, H, I, J

11.06 [281]

16.30 [414] 20.28 [515]

3.03 [77]

A, B 11.06 [281] 1.12 [28]

4.34 [110]

5.80 5.80 [147] [147]

0.91 [23] EZM1600FSU EZM1800FSU

Dimensions:

in. [mm]

49 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Dimensions and Knockouts \

Box Side

26.19 [665] 20.00 [508]

11.65 [296]

Nut

Captive Screw

Gasket Top View

Hanging Mounting Hex Rail Nut (2)

3.44 [87]

Torque to 50 lb-in.

2.00 [51]

1.00 [25.5] (2)

(1) Sealing Wing Nut 1.75

Square Neck Bolt

[51]

69.03 [1753] 49.36 [1254]

26.06 [662]

Line Phase Pads

Box Side Right

(1)

Closing Cap (1)

Gasket Right Side Closing Cap

Left Side Closing Cap 34.26 [870] 24.00 [610]

18.32 [465]

11.10 [282] E, F, G, H, I, J

3.04 [77]

3.44 [87]

Hanging Mounting Rail

A, B 11.10 [282] 1.13 [29]

4.75 [121]

Hex Nut (2) (1) Sealing Wing Nut

(1) Gasket

4.75 [121]

Line Neutral Pad

20.00 [508] 26.00 [660]

Box Side Left

Closing Cap 2.00 [51] (1) 0.69 [18]

Captive Screw

8.25 [209]

8.25 [209]

70.05 [1779]

0.92 [23]

EZM3600FSU EZM3800FSU

26.08 [662]

Line Neutral Pad

Line Phase Pads

46.99 [1193]

6.25 [159]

Knockouts Conduit Size

Hole Diameter

Symbol in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

24.00 [610] 34.00 [864]

E, F, G, H, I, J

17.83 [453]

3.09 [78]

17.83 A, B [453]

1.16 [29] 5.37 [136]

7.75 [197]

7.75 [197]

7.75 [197]

0.92 [23]

EZM11200FSU

Dimensions:

in. [mm]

50 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Dimensions and Knockouts Box Side 17.16 [436] 13.00 [330]

2.08 [53]

8.00 [203]

0.34 [9] Nut Captive Screw

Top of Mounting Channel

Omitted on 1Ø Units 3.44 [87]

Gasket Top View

0.33 [8]

Omitted on 1Ø Units

35.72 [907]

1.75 [44] 19.88 [505]

27.17 [690]

22.36 [568]

2.00 [51]

Hex 0.62 Nut (2) [16]

(1)

Square Neck Bolt

1.75 [51]

Sealing Wing Nut

2.00 [51]

7.44 [189]

13.00 [330]

Captive Screw (2)

(1)

Closing Cap (1)

(1)

(1)

(1) Gasket Gasket Right Side Closing Cap

Left Side Closing Cap

A, B

8.00 8.72 [203] [221]

5.88 [149]

Hex Nut (2)

Sealing Wing Nut Box Side Right

Cap

E, F, G, H, I, J

1.18 [30] 1.14 [29]

1.00 [25.5]

Box Side Left

2.00 [51] 0.69 Closing [18]

17.00 [432]

3.09 [78]

Torque to 50 lb-in.

25.16 [639] 21.00 [533]

5.40 [137]

11.68 [297] Top of Mounting Channel

Omitted on 1Ø Units

EZM1400TBU, EZM3400TBU

3.44 [87]

0.33 [8]

Omitted on 1Ø Units 2.00 [51]

1.75 [44]

2.00 [51]

Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

21.00 [533]

11.12 [283]

25.00 [635]

Symbol

H

31.17 [792]

26.44 [672]

23.88 [607]

Knockouts

39.97 [1015]

E, F, G, H, I, J 11.68 [297]

A, B 3.09 [79]

1.19 [30]

12.05 [306]

1.19 [30] 9.92 [252]

5.40 [137] EZM1800TBU, EZM3800TBU in. Dimensions: [mm]

51 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Dimensions and Knockouts Box Side

Nut

Captive Screw

Gasket Top View

2.00 [51]

Hex Nut (2)

Torque to 50 lb-in.

Square Neck Bolt

(1) Sealing Wing Nut

1.00 [25.5]

Captive Screw (2)

Sealing Wing Nut

Box Side Left Box Side Right

Closing Cap (1)

Hex Nut (2) (1)

Closing Cap

(1)

(1)

(1) Gasket Left Side Closing Cap

Gasket Right Side Closing Cap

33.16 [842] 29.00 [737]

11.68 [297]

Omitted on 1Ø Units

Top of Mounting Channel

3.44 [87] Omitted on 1Ø Units

44.71 [1136]

1.75 [44]

2.00 [51]

4.00 [102]

23.88 [607]

31.17 [792]

26.74 [679]

Knockouts Conduit Size

Hole Diameter

2.00 [51]

Symbol in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

29.00 [737]

11.12 [283]

33.00 [838] E, F, G, H, I, J A, B

3.09 [79]

1.19 [30]

5.40 [137]

1.19 [30] 11.22 [285]

5.40 [137] EZM11200TBU, EZM31200TBU

in. Dimensions: [mm]

52 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Dimensions and Knockouts 12.25 [311]

2.21 [56]

1.56 [40] Typ.

7.09 [180]

3.75 [95]

Hanging Mounting Rail

3.44 [87] Typ.

Omitted on 1Ø Units 42.37 [1076]

5.20 [132] Typ.

9.00 [229] Typ. 11.19 [284]

7.10 [180] 4.79 [122]

C, D, E 1.65 [42]

2.48 [63]4.59 [117]

1.78 [45]

3.00 [76]

31.30 [795]

6.59 [167] 2.21 [56]

7.54 [192] 10.48 [266] 12.12 [308] 8.50 [216] 5.75 [146]

A, B

3.75 [95]

1.56 [40] Typ.

7.09 [180]

Hanging Mounting Rail

3.44 [87] Typ.

2.44 [62]

Omitted on 1Ø Units 48.12 [1222]

6.59 [167] 1.62 [41] 1.67

12.25 [311]

5.20 [132] Typ.

9.00 [229] Typ.

C, D, E

[42] 2.72 [69] EZM113125 / X / CUX, EZM313125 / X / CUX EZMR113125 / X / CUX, EZMR313125 / X / CUX EZMH113125 / X / CUX, EZMH313125 / X / CUX

11.19 [284]

7.10 [180] 4.79 [122]

Knockouts Hole Diameter

in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

Symbol

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

C, D, E 1.65 [42]

2.48 [63]

4.59 [117]

Conduit Size

1.78 [45]

31.30 [795]

3.00 [76]

7.54 [192] 10.48 [266] 12.12 [308] 8.50 [216] 5.75 [146]

6.59 [167]

A, B 2.44 [62] 6.59 [167]

1.62 [41] 1.67

C, D, E

[42] 2.72 [69] EZM114125 / X / CUX, EZM314125 / X / CUX EZMR114125 / X / CUX, EZMR314125 / X / CUX EZMH114125 / X / CUX, EZMH314125 / X / CUX

in. Dimensions: [mm]

53 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Dimensions and Knockouts 12.25 [311]

2.21 [56]

7.09 [180]

3.75 [95]

3.44 [87] Typ.

Hanging Mounting Rail

57.12 [1451] Omitted on 1Ø Units

2.21 [56]

5.20 [132] Typ.

9.00 [229] Typ.

12.25 [311]

7.09 [180]

3.75 [95]

1.56 [40] Typ.

31.30 [795]

11.19 [284]

7.10 [180] 4.79 [122]

C, D, E 1.65 [42]

2.48 [63] 4.59 [117]

1.78 [45]

1.56 [40] Typ.

7.54 [192] 10.48 [266] 12.12 [308] 8.50 [216] 5.75 [146]

3.00 [76]

3.44 [87] Typ.

6.59 [167]

Hanging Mounting Rail

Omitted on 1Ø Units 66.12 [1679]

A, B

5.20 [132] Typ.

2.44 [62] 6.59 [167]

1.62 [41] 1.67

11.19 [284]

7.10 [180] 4.79 [122]

C, D, E

[42] 2.72 [69]

EZM115125 / X / CUX, EZM315125 / X / CUX EZMR115125 / X / CUX, EZMR315125 / X / CUX EZMH115125 / X / CUX, EZMH315125 / X / CUX

2.48 [63] 4.59 [117]

Knockouts Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

Symbol

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

1.78 [45]

40.30 [1024]

9.00 [229] Typ.

3.00 [76]

C, D, E 1.65 [42] 7.54 [192] 10.48 [266] 12.12 [308] 8.50 [216] 5.75 [146]

6.59 [167]

A, B 2.44 [62] 6.59 [167]

1.62 [41] 1.67 [42] 2.72 [69]

C, D, E

EZM116125 / X / CUX, EZM316125 / X / CUX EZMR116125 / X / CUX, EZMR316125 / X / CUX EZMH116125 / X / CUX, EZMH316125 / X / CUX in. Dimensions: [mm]

54 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Dimensions and Knockouts

17.38 [441]

3.75 [95] Top Meter Position Omitted on 2-Position Devices Omitted on 1Ø Units

3.44 [87] Typ.

1.56 [40] Typ.

8.09 [205]

Hanging Mounting Rail

43.41 [1103] 9.00 [229] Typ.

2.12 [54]

17.38 [442]

12.23 [311]

6.00 [152]

2.25 [57]

32.34 [821]

8.30 [211]

2.18 [55] C, D, E, F

5.75 [146] 6.75 [171] 10.50 [267] 15.00 [381] 17.25 [438] 6.59 [167] A, B

3.75 [95]

1.56 [40] Typ.

8.09 [205]

7.50 [190]

3.44 [87] Typ.

Hanging Mounting Rail Omitted on 1Ø Units 52.00 [1321]

C, D, E, F 7.50 [190]

4.12 [105]

9.00 [229] Typ.

2.12 [54]

1.93 [49]

1.61 [41] 3.34 [85]

12.23 [311]

6.00 [152]

EZM112225 / X / CUX, EZM312225 / X / CUX EZM113225 / X / CUX, EZM313225 / X / CUX EZMR112225 / X / CUX, EZMR312225 / X / CUX EZMR113225 / X / CUX, EZMR313225 / X / CUX| EZMH112225 / X / CUX, EZMH312225 / X / CUX EZMH113225 / X / CUX, EZMH313225 / X / CUX

2.25 [57]

Knockouts Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

Symbol

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

32.34 [821]

5.30 [211] 5.75 [146] 6.75 [171] 10.50 [267] 15.00 [381] 17.25 [438] 6.59 A, B [167]

2.18 [55] C, D, E, F

7.50 [190]

C, D, E, F 7.50 [190]

4.18 [106] 1.61 [41] 3.34 [85]

1.93 [49]

EZM114225 / X / CUX, EZM314225 / X / CUX EZMR114225 / X / CUX, EZMR314225 / X / CUX EZMH114225 / X / CUX, EZMH314225 / X / CUX in. Dimensions: [mm]

55 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Dimensions and Knockouts

8.69 [221]

17.37 [441]

8.09 [208]

1.74 [44]

12.73 [323] 28.59 [728]

3.44 [87] Typ.

Omitted on 1Ø Units 60.94 [1548]

9.00 [229] Typ.

25.09 [837] C, D, E, F Knockouts in Rear of Box

32.35 [822]

12.21 [310]

7.53 [191]

17.25 [438]

NOTE: Shown with covers removed.

A, B 2.18 [55]

Top of Mounting Channel

2.27 [58]

C, D, E, F

2.35 [60]

1.72 3.32 [44] [84] 1.66 [42]

1.67 [42]

3.32 [84]

3.33 [85]

EZM115225 / CU, EZM315225 / CU EZMR115225 / CU, EZMR315225 / CU EZMH115225 / CU, EZMH315225 / CU

Knockouts Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

Symbol

in. Dimensions: [mm]

56 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Dimensions and Knockouts 19.44 [494] 12.09 [307]

5.50 [140]

9.44 [240]

Top Meter Position Omitted on Single Position Device

3.44 [87] 6.00 Typ. [152]

3.44 [87] Typ.

12.09 [307]

67.06 [1703]

D, E, F, G

8.83 [224]

14.00 [356] Typ.

EZML111225 / CU / D, EZML312225 / CU / D EZML112225 / CU / D, EZML331225 / CU / D EZMR332225 / CU / D, EZML332225 / CU / D

5.86 [149] 9.65 [245] 13.45 [342] 17.24 [438]

3.44 [87] Typ.

3.20 [81]

2.07 [53] 3.97 [101] 9.44 [240]

5.50 [140]

Top of Mounting Channel

Omitted on 1Ø Units

3.91 [99]

53.06 [1348]

D, E, F, G

12.09 [307]

5.86 [149] 9.65 [245] 13.45 [342] 17.24 [438] 19.31 [490]

3.20 [81]

39.50 [1003]

2.00 [51] 3.79 [96]

D, E, F, G

A, B 8.83 [224] 2.24 [57]

12.09 [307]

D, E, F, G

Knockouts Conduit Size 8.83 [224]

5.86 [149] 9.65 [245] 13.45 [342] 17.24 [438] EZML113225 / CU / D, EZML313225 / CU / D EZMR333225 / CU, EZML333225 / CU / D (See Typical Bottom View)

in. Dimensions: [mm]

Typical Bottom View

13.34 [339]

6.62 [168]

8.83 [224]

EZML114225 / CU / D, EZML314225 / CU / D EZMR334225 / CU, EZML334225 / CU / D

4.60 [117] 14.00 [356] Typ.

39.50 [1003]

13.34 [339]

6.62 [168]

(See Typical Bottom View) 19.44 [494] 12.09 [307]

Top of Mounting Channel

Omitted on 1Ø Units

13.34 [339]

6.62 [168]

2.07 [53] 3.97 [101]

9.44 [240]

39.06 [992] 25.50 [648]

3.20 [81]

5.50 [140]

Top of Mounting Channel

Omitted on 1Ø Units 13.99 [355]

2.07 [53] 3.97 [101]

19.44 [494] 12.09 [307]

Hole Diameter

Symbol in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

H

3.00

76

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

57 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Dimensions and Knockouts 22.42 [570]

22.42 [570]

18.31 [465] 9.16 [233]

C, D, E, F,G, H Knockouts in Rear of Box

2.06 [52]

9.38 [238] 1.68 [43]

3.44 [87] Typ.

25.12 [638]

Omitted on 1Ø Units

18.31 [465] 9.16 [233]

0.38 [10] Top of Mounting Channel

2.06 [52]

1.68 [43]

9.38 [238]

8.80 [224]

3.44 [87] 16.19 Typ. [411]

20.45 [519]

0.38 [10]

Top of Mounting Channel

8.97 [228]

19.00 [483]

2.77 [70]

5.15 [131]

7.25 [184]

22.31 [567]

1.81 [46]

C, D, E, F, G, H

A, B

8.94 [227]

C, D, E, F,G, H Knockouts in Rear of Box

60.56 [570] 43.63 [1108]

28.89 [734]

2.30 [58] 1.00 [25]

36.40 [925]

3.09 [79]

5.78 [147]

4.27 [108] 8.44 [214]

EZMT111225, EZMT311225, EZMT331225 4.31 [110] C, D, E, F, G, H

A, B

2.36 [60] 2.41 [61]

2.41 [61]

4.27 [108]

22.42 [570]

18.31 [465] 9.16 [233]

2.47 [63]

8.94 [227]

2.06 [52]

9.38 [238]

0.38 [10]

8.80 [224]

Typical endwall for 2 and 3 positions.

19.00 [483]

3.44 [87] Typ.

79.56 [2021]

Omitted on 1Ø Units

19.00 [483]

Knockouts Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

A

0.50

13

0.88

22

Symbol

B

0.75

19

1.25

32

C

1.00

25

1.38

35

D

1.25

32

1.75

44

E

1.50

38

2.00

51

F

2.00

51

2.50

64

G

2.50

64

3.00

76

76

1.80 [46]

EZMT112225, EZMT312225, EZMT332225 1.40 [36]

4.27 [108]

22.31 [567]

H

3.00

3.63

92

I

3.50

89

4.13

105

J

4.00

102

4.63

118

41.03 [1042] C, D, E, F,G, H Knockouts in Rear of Box 4.31 [110] 2.41 [61]

4.27 [108] Typ.

48.25 [1226] 28.89 [734] 8.44 [214] 1.81 [46]

8.94 [227] 22.31 [567] EZMT113225, EZMT313225, EZMT333225 in. Dimensions: [mm] 7.25 [184]

58 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Dimensions and Knockouts 23.21 [590] 12.09 [307]

3.44 [87] (Typ.)

5.50 [140]

23.21 [590] 12.09 [307]

9.44 [590] Top of Mounting Channel

Omitted on 1Ø Units

5.50 [140]

9.44 [240]

14.58 [370]

45.55 [1157] 37.81 [960]

Top of Mounting Channel

3.44 [87] (Typ.) 27.44 69.61 [697] [1768]

21.53 [547]

16.60 [422]

Omitted on 1Ø Units

37.81 [960]

10.11 [257] EZML111400, EZML311400, EZML331400 27.56 [700]

15.68 [398] 11.12 [282]

21.53 [547]

16.60 [422]

5.82 [148] 1.68 [43]

9.74 [247]

0.34 [9] Top of Mounting Channel

Omitted on 1Ø Units 3.44 [87] Typ.

10.11 [257] EZML112400, EZML312400, EZML332400 27.56 [700]

45.55 [1157]

37.81 [960]

30.58 [777]

15.68 [398] 11.12 [282]

21.04 [534]

27.48 [698]

1.80 [46]

EZMK111400, EZMK311400, EZMK331400

5.82 [148]

1.68 [43]

9.74 [247]

0.34 [9]

7.59 [193]

72.99 [1854]

9.23 [235] 3.44 [87] Typ.

Top of Mounting Channel

29.69 [754] Omitted on 1Ø Units

37.81 [960]

30.58 [777]

21.04 [534]

27.44 [697]

1.80 [46]

9.23 [235]

EZMK112400, EZMK312400, EZMK332400 NOTE: No knockouts provided on EZMK and 400 A EZML devices.

in. Dimensions: [mm]

59 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Dimensions and Knockouts

1.71 [43]

14.40 [366] 8.02 [204]

1.80 [46]

14.40 [366]

11.66 [296]

Omitted on 1Ø Units

6.37 [162]

19.34 [491]

1.74 [44]

7.20 [183]

5.87 [149]

11.50 [292] 19.50 [495]

Omitted on 1Ø Units

EZM1EXT EZM3EXT

1.69 [43]

EZM1CORNER EZM3CORNER NEMA Type 1 (Indoor Only)

1.71 [43]

8.07 [205]

6.00 [152]

Omitted on 1Ø Units

6.37 [162]

19.34 [491]

1.74 [44]

6.51 [165]

8.06 [205]

6.48 [165]

11.50 [292]

5.87 [149] EZM1EXT6 EZM3EXT6

1.80 [46]

Omitted on 1Ø Units

1.67 [42]

0.34 [9] EZM1ELBOW EZM3ELBOW

in. Dimensions: [mm]

60 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Wiring Diagrams

Wiring Diagrams

Load

Load N

Circuit Breaker

Omitted on 400 A Device Main Bonding Jumper (when required)

N

A

Load

B

Load

C N

Ground (when required)

Line

Main Bonding Strap (when required)

EZM1400CB, EZM1600CB, EZM1800CB, EZM11000CB

Circuit Breaker

N

Ground (when required) Line EZM12000CB

A Load B C N

Load Omitted on 400 A Device Main Bonding Jumper (when required)

Circuit Breaker N A

Load

Ground (when required)

C

B

Line

A B

Load

C N

Main Bonding Strap (when required)

EZM3400CB, EZM3600CB, EZM3800CB, EZM31000CB Circuit Breaker

N

Ground (when required) A

B

C

Line Load

Load

EZM32000CB

N

Omitted on 1200 A Device Main Bonding Jumper (when required)

Circuit Breaker

N

Omitted on 1200 A Device

Ground (when required)

Line

Load

Load N

Use 300 V Class T Fuses (order separately)

EZM11200CB, EZM11600CB,

N

Molded Case Switch A

Line

Load B

Omitted on 400 A Device Main Bonding Jumper (when required)

Ground (when required)

Load

C N

EZM1400FS, EZM1600FS, EZM1800FS Omitted on 1200 A Device Main Bonding Jumper (when required)

Circuit Breaker N

Omitted on 1200 A Device

A

B

C

Ground (when required)

Line

EZM31200CB, EZM31600CB

61 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Wiring Diagrams

A

Load B

Load

C N

Use 300 V Class T Fuses (order separately)

Omitted on 400 A Device Main Bonding Jumper (when required)

N

Molded Case Switch A

B

Ground (when required)

C

Line

EZM3400FS, EZM3600FS, EZM3800FS

N

Omitted on 400 A and 600 A Devices

Main Bonding Jumper (when required)

N

Ground (when required) Load

Load N

Use 300 V Class T Fuses (order separately)

N

Molded Case Switch

EZM1400TB, EZM1600TB, EZM1800TB, EZM1800TBCU

Main Bonding Jumper (when required)

Ground (when required) A

Line

B C N

EZM11200FS

Main Bonding Jumper (when required)

Omitted on 400 A and 600 A Devices A

B

C

N

Ground (when required) N

EZM3400TB, EZM3600TB, EZM3800TB N

Ground (when required) EZM1225TB N

Main Bonding Jumper (when required) N

A B C N

Ground (when required) EZM11600TB A

B

C

N

Ground (when required) EZM3225TB

62 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Wiring Diagrams

A B C N

A

C

B

Main Bonding Jumper (when required)

N

Ground (when required)

Load

Load N

EZM31600TB

Circuit Breaker

Load

Load

Line

N

Neutral Disconnect Link Box Bonding (when required) Ground (when required)

Circuit Breaker

Line

Service Grounding Lugs (when required)

A B Load C N

Load

A

Load B

Load

Circuit Breaker

A

B

Line

C

N

EZM1600CBU, EZM1800CBU

Circuit Breaker

Neutral Disconnect Link Box Bonding (when required) Ground (when required)

Service Grounding Lugs (when required)

N

EZM1400CBU

C N

Neutral Disconnect Link Box Bonding (when required) Ground (when required)

Service Grounding Lugs (when required)

A

B

Line

C

Neutral Disconnect Link Box Bonding (when required) Ground (when required)

Service Grounding Lugs (when required)

N

EZM3600CBU, EZM3800CBU

N

EZM3400CBU

63 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Wiring Diagrams

Load

Load N

Circuit Breaker

Line

Load

Load A B

Neutral Disconnect Link Box Bonding (when required) Ground (when required)

C

Service Grounding Lugs (when required)

N

N

N A

B

C

Line

EZM11000CBU, EZM11200CBU

A B Load C N

Main Bonding Strap (when required)

Circuit Breaker

Ground (when required)

EZM31600CBU, EZM32000CBU

Load Load

Circuit Breaker

A

B

Line

Neutral Disconnect Link Box Bonding (when required) Ground (when C required)

Service Grounding Lugs (when required)

Load N

Neutral Disconnect Link Box Bonding (when required) Ground (when required)

Use 300 V Class T Fuses (order separately) Molded Case Switch

N

Service Grounding Lugs (when required)

N

Line EZM31000CBU, EZM31200CBU

EZM1400FSU

A B C Load N

Load

Load

N

Main Bonding Strap (when required)

Circuit Breaker N

Ground (when required)

Load Neutral Disconnect Link Box Bonding (when required) Ground (when required)

Use 300 V Class T Fuses (order separately) Molded Case Switch

A

B

Service Grounding Lugs (when required)

N

C

Line EZM11600CBU, EZM12000CBU

EZM3400FSU

64 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Wiring Diagrams

Load

Load N

Neutral Disconnect Link Box Bonding (when required) Ground (when required)

Use 300 V Class T Fuses (order separately) Molded Case Switch

Service Grounding Lugs (when required)

N

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Line N

Line EZM1600FSU, EZM1800FSU A B Load C N

Load Neutral Disconnect Link Box Bonding (when required) Ground (when required)

Use 300 V Class T Fuses (order separately) Molded Case Switch

A

B

Tenant Circuit Breaker 125 A Max.

Service Grounding Lugs (when required)

Neutral and Service Ground N

Equipment Grounding

EZM113125 / X / CUX EZMR113125 / X / CUX EZMH113125 / X / CUX

N

C

Line EZM3600FSU, EZM3800FSU

A

Load

B

C

Load N

Use 300 V Class T Fuses (order separately) Molded Case Switch

Line

Neutral Disconnect Link Box Bonding (when required) Ground (when required)

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A B C N

Service Grounding Lugs (when required)

A

B C

N

EZM11200FSU Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Tenant Circuit Breaker 125 A Max.

N

Box Bonding (when required) Equipment Grounding N Terminal

Neutral and Service Ground N

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, and AC, top to bottom.

Equipment Grounding EZM313125 / X / CUX EZMR313125 / X / CUX EZMH313125 / X / CUX

EZM1400TBU, EZM1800TBU, EZM11200TBU, EZM12000TB A B C N

Torque to 50 lb-ft. (600 lb-in. or 68 N•m) Box Bonding (when required) A

B

C

N

Equipment Grounding Terminal

EZM3400TBU, EZM3800TBU, EZM31200TBU, EZM32000TB

65 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Wiring Diagrams

A

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Line N

Tenant Circuit Breaker 125 A Max.

B

C

A B C Line N

Torque to 50 lb-ft. (600 lb-in. or 68 N•m) A B

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, AC, and AC, top to bottom.

Tenant Circuit Breaker 125 A Max. Equipment Grounding

Neutral

Neutral

N

C

Equipment Grounding

N

EZM314125 / X / CUX EZMR314125 / X / CUX EZMH314125 / X / CUX

EZM114125 / X / CUX EZMR114125 / X / CUX EZMH114125 / X / CUX

A

B C

Tenant Circuit Breaker 125 A Max.

A

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Line N

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Line B

C N

A B C

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, AC, AB and BC, top to bottom.

Tenant Circuit Breaker 125 A Max.

Neutral

N

Equipment Grounding

EZM115125 / X / CUX EZMR115125 / X / CUX EZMH115125 / X / CUX

Neutral N

Equipment Grounding

EZM315125 / X / CUX EZMR315125 / X / CUX EZMH315125 / X / CUX

66 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Wiring Diagrams

A

B C

Tenant Circuit Breaker 125 A Max.

Tenant Circuit Breaker 125 A Max.

Line

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

N

Tenant Circuit Breaker 225 A Max.

Line

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

N

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A B C N

Neutral N

Equipment Grounding

EZM112225 / X / CUX EZMR112225 / X / CUX EZMH112225 / X / CUX

A B C

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, AC, AB, BC and AC, top to bottom.

Equipment Grounding

Neutral N

Neutral N

Equipment Grounding

EZM316125 / X / CUX EZMR316125 / X / CUX EZMH316125 / X / CUX

EZM116125 / X / CUX EZMR116125 / X / CUX EZMH116125 / X / CUX

A

Line

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

N

Tenant Circuit Breaker 225 A Max.

B

C

Torque to 50 lb-ft. (600 lb-in. A B C or 68 N•m)

A B C N

Tenant Circuit Breaker 225 A Max.

Equipment Grounding

Neutral

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB and BC, top to bottom.

N

Neutral N

Equipment Grounding

EZM312225 / X / CUX EZMR312225 / X / CUX EZMH312225 / X / CUX

EZM113225 / X / CUX EZMR113225 / X / CUX EZMH113225 / X / CUX

67 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Wiring Diagrams A

A B

C

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A B Line C N

B C

A B

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A B C Line N

C

Tenant Circuit Breaker 225 A Max.

Tenant Circuit Breaker 225 A Max.

A B C

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, and AC, top to bottom.

Neutral N

Equipment Grounding Neutral

EZM313225 / X / CUX EZMR313225 / X / CUX EZMH313225 / X / CUX

Equipment Grounding EZM314225 / X / CUX EZMR314225 / X / CUX EZMH314225 / X / CUX

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, AC and AC, top to bottom.

N

A B C

A

Tenant Circuit Breaker 225 A Max.

Line

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

N

Tenant Circuit Breaker 225 A Max.

B

C

Tenant Circuit Breaker 225 A Max.

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leavesthe factory phased AB, BC, AC, AB and BC, top to bottom.

N A

Line

B C N

Neutral

Equipment Grounding

EZM114225 / X / CUX EZMR114225 / X / CUX EZMH114225 / X / CUX

Neutral

Equipment Grounding

EZM115225 / CU EZMR115225 / CU EZMH115225 / CU Neutral

Equipment Grounding

EZM315225 / CU EZMR315225 / CU EZMH315225 / CU

68 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Wiring Diagrams A B

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Line

N Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Line N

A

Tenant Circuit Breaker 225 A Max.

Tenant Circuit Breaker 225 A Max.

Line

A B

C

Neutral

EZML112225 / CU / D A

Equipment Grounding EZML312225 / CU / D

C B

High Leg (Power Leg) for 3φ4W Delta System Torque to 50 lb-ft. Line (600 lb-in. or 68 N•m)

A

Line B C N

Tenant Circuit Breaker 225 A Max. High Leg (Power Leg) for 3φ4W Delta System

Equipment Grounding Neutral

A B C N

C

A

A BC

B C N

High Leg (Power Leg) for 3φ4W Delta System

Tenant

B

Neutral

High Leg (Power Leg) for 3φ4W Delta System (All Tenant Circuit Breaker Positions)

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

C

Line

B

High Leg (Power Leg) for 3φ4W Delta System

High Leg (Power Leg) Torque to for 3φ4W Delta System 50 lb-ft. (All Tenant Circuit (600 lb-in. Breaker Positions) or 68 N•m)

Tenant Circuit Breaker 225 A Max.

EZML331225 / CU / D A

C

A

A B

A BC

C

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB and BC,top to bottom.

EZML111225 / CU / D Equipment Grounding

B

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A B C N

Tenant Equipment Circuit Breaker 225 A Max. Grounding

Neutral

Neutral

High Leg (Power Leg) for 3φ4W Delta System

Each socket line Circuit Breaker 225 A Max. connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, and Equipment AC, top to bottom.

Grounding EZML313225 / CU / D

A BC

Equipment Grounding Neutral

EZML33225 / CU / D EZML33225 / CU Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A BC

A

Line

C

B C N

High Leg (Power Leg) for 3φ4W Delta System

Line

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

N

Tenant Circuit Breaker 225 A Max. A BC

Tenant Circuit Breaker 225 A Max. A BC

Neutral

Equipment Grounding

EZML333225 / CU / D EZMR333225 / CU

Neutral Equipment Grounding EZML113225 / CU / D

69 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Wiring Diagrams A B C

Tenant Circuit Breaker 225 A Max. Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Line N

A

Line B

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

C N

A

B C

Tenant Circuit Breaker 225 A Max. Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, and AC, top to bottom.

Neutral Equipment Grounding

Neutral

Equipment Grounding

EZML314225 / CU / D

EZML114225 / CU / D A

C

B

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Line N

High Leg (Power Leg) for 3φ4W Delta System (All Tenant Circuit Breaker Positions)

A Line B C N

Equipment Grounding Terminal

High Leg (Power Leg) for 3φ4W Delta System

A BC

N

Tenant Circuit Breaker 225 A Max. Service Grounding Lugs when Required Neutral Terminals

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A BC

Box Bonding (when required) EZMT111225

High Leg (Power Leg) for 3φ4W Delta System

A

Line

B

C

A B C N

A

Tenant Circuit Breaker 225 A Max.

A BC

Service Grounding Lugs when Required A BC

Equipment Grounding Neutral

C

NOTE: This device is shipped with line side meter socket bus connectors phased Aφ and Cφ. These connectors may be moved to balance loading for Bφ and Cφ, or for Aφ and Bφ phasing in the field.

Equipment Grounding Terminal

Tenant Circuit Breaker 225 A Max.

B

A

B

C

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AC.

Neutral Terminals Box Bonding (when required)

EZML334225 / CU / D EZMR334225 / CU

EZMT311225

70 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Wiring Diagrams

A C

Line

High Leg (Power Leg) for 3φ4W Delta System

C

A B

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A B C N

A B

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A B Line C N

C

High Leg (Power Leg) for 3φ4W Delta System

A BC

Tenant Circuit Breaker 400 A Max.

Tenant Circuit Breaker 400 A Max.

Neutral

Equipment Grounding

N

B

High Leg (Power Leg) for 3φ4W Delta System

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AC.

EZML311400

Equipment Grounding

Neutral N EZML331400

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Line High Leg (Power Leg) for 3φ4W Delta System

N A

Line

B

C

A B C N

Torque to 50 lb-ft. (600 lb-in. or 68 N•m) Line High Leg (Power Leg) for 3φ4W Delta System

Equipment Grounding Terminal

L I N E

High Leg (Power Leg) for 3φ4W Delta System

L O A D

A

Service Ground Lugs A B C (when required)

L I N E

L O A D

C

L I N E

L O A D

B

High Leg (Power Leg) for 3φ4W Delta System

N

Tenant Circuit Breaker 225 A Max.

L I N E

L O A D

L I N E

L O A D

L I N E

L O A D

Box Bonding (when required) Service Ground Lugs (when required) Neutral Disconnect Link

N

Neutral Terminals

Neutral Terminal Box Bonding (when required)

L I N E

EZMT331225

L O A D

Equipment Grounding Terminal EZMT112225

71 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Wiring Diagrams

A

B C

Line

C

B

A

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A B C N B

A N

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB and BC top to bottom.

L I N E

Tenant Circuit Breaker 225 A Max.

L O A D

L I N E

L O A D

Box Bonding (when required) Service Ground Lugs (when required)

C

B N

Neutral Disconnect Link Neutral Terminals L I N E

L O A D

L I N E

C

B

A

L O A D

Equipment Grounding Terminal EZMT312225

High Leg (Power Leg) for 3φ4W Delta System

Line

B

C

A

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A B C N

High Leg (Power Leg) for 3φ4W Delta System (All Meter Positions)

B

A C

N

High Leg (Power Leg) for 3φ4W Delta System (All Tenant Circuit Breaker Positions)

L I N E

L O A D

L I N E

L O A D

L O A D

L I N E

High Leg (Power Leg) for 3φ4W Delta System

A B C

Box Bonding (when required) Service Ground Lugs (when required)

B

A C

Neutral Disconnect Link Neutral Terminals

N L I N E

Tenant Circuit Breaker 225 A Max.

L O A D

A

L I N E

C

L O A D

L I N E

L O A D

B

A B C

Equipment Grounding Terminal EZMT332225

72 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Wiring Diagrams N B

A

L I N E

L I N E

L O A D

B

A N

C

L O A D

L I N E

L O A D

L I N E

L O A D

A B

Line

Line Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Tenant Circuit Breaker 225 A Max. Box Bonding (when required)

L I N E

L I N E

L O A D

L I N E

L O A D

L I N E

Line Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

L O A D

Box Bonding B C (when required)

Service Grounding Lugs (when required) Neutral Disconnect Link

C

C

B N

Tenant Circuit Breaker 225 A Max.

L O A D

B

B C N

Each socket line connector may be moved to balance loading. Phase AC, BC or AB. This device leaves the factory phased AB, BC and AC top to bottom.

N N

A

Line A

Service Grounding Lugs (when required) Neutral Disconnect Link

N

Neutral Terminals

A N

C

Neutral Terminals

L I N E

L I N E

L O A D

L O A D

B

A C

Equipment Grounding Terminal

L I N E

High Leg (Power Leg) for 3φ4W Delta System (All Meter Positions)

EZMT113225 High Leg (Power Leg) for 3φ4W Delta System (All Tenant Circuit Breaker Positions)

L O A D

L I N E

L O A D

A

L I N E

L O A D

L I N E

L O A D

A C

N L I N E

L O A D

B

C

Equipment Grounding Terminal EZMT313225

Tenant Circuit Breaker 225 A Max. High Leg (Power Leg) for 3φ4W Delta System

A B C A B Line C N

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

Line N

C

N L I N E

Box Bonding (when required)

B

A

Line Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

L O A D

L I N E

L O A D

L I N E

L O A D

Equipment Grounding

Tenant Circuit Breaker 400 A Max.

High Leg (Power Leg) for 3φ4W Delta System

A B C A

Service Grounding Lugs (when required)

C

Neutral Disconnect Link

Neutral

B

EZML111400 N

Neutral Terminals

L I N E

L O A D

Tenant Circuit Breaker 225 A Max.

L I N E

L O A D

L I N E

L O A D

Equipment Grounding Terminal A B C

EZMT333225

73 07/2008

© 2008 Schneider Electric All Rights Reserved

EZ Meter-Pak® Meter Centers Wiring Diagrams High Leg (Power Leg) for 3φ4W Delta System

A B C N

Neutral

Line

Line

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

C

Torque to 50 lb-ft. (600 lb-in. or 68 N•m) Line

High Leg (Power Leg) for 3φ4W Delta System

B A

Tenant Circuit Breaker 400 A Max.

Equipment Grounding Terminal

C

K-7 Bolt-On Meter Socket

Line

N

High Leg (Power Leg) for 3φ4W Delta System

B

A

Tenant Circuit Breaker 400 A Max.

EZMK331400 Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

A B Line C N Neutral

Tenant Circuit Breaker 400 A Max. Neutral

Line C

A

Equipment Grounding Terminal

Each socket line connector may be moved to balance loading. Phase AC, BC, or AB. (B phase line connector is provided). This device leaves the factory phased AC.

N

EZML112400

Tenant Circuit Breaker 400 A Max. K-5 Bolt-On Meter Socket

Line

Line

N

Neutral

Torque to 50 lb-ft. (600 lb-in. or 68 N•m)

EZMK311400 A

B

C

Equipment Grounding Terminal Tenant Circuit Breaker 400 A Max.

Tenant Circuit Breaker 400 A Max.

K-4 Bolt-On Meter Socket

Torque to 50 lb-ft. (600 lb-in. or 68 N•m) Line

A B

EZMK111400

Line C N B A

C

Neutral

Each meter socket line connector may be moved to balance loading. Phasing may be connected AC, BC, or AB. This device leaves the factory phased AB and BC top to bottom.

Equipment Grounding Terminal Tenant Circuit Breaker 400 A Max. Tenant Circuit Breaker 400 A Max.

Torque to 50 lb-ft. (600 lb-in. or 68 N•m) Line

Line N

K-5 Bolt-On Meter Socket

EZMK312400 A

High Leg (Power Leg) for 3φ4W Delta System (Both Tenant Circuit Breaker Positions)

C

B

High Leg (Power Leg) for 3φ4W Delta System (Both Tenant Circuit Breaker Positions)

A B C

Neutral

Tenant Circuit Breaker 400 A Max.

Equipment Grounding Terminal Tenant Circuit Breaker 400 A Max.

High Leg (Power Leg) for 3φ4W Delta System K-4 Bolt-On Meter Socket

EZMK112400

Torque to 50 lb-ft. (600 lb-in. or 68 N•m) Line

A B C Line N C A

Neutral

B

Equipment Grounding Terminal A B C Tenant Circuit Breaker 400 A Max. K-7 Bolt-On Meter Socket EZMK332400

74 © 2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak® Meter Centers Wiring Diagrams

75 07/2008

© 2008 Schneider Electric All Rights Reserved

Schneider Electric USA 1601 Mercer Road Lexington, KY 40511 USA 1-888-Square D 1-888-778-2733 www.us.SquareD.com

Square D, EZ Meter-Pak, Visi-Tite, and QO are trademarks or registered trademarks of Schneider Electric and/or its affiliates in the United States and/or other countries. Other marks used herein are the property of their respective owners. 4100CT0701 © 2008 Schneider Electric All Rights Reserved Replaces 4100CT9801 dated May 1999. 07/2008