Ethernet RTU Controller & Data Logger

PRO Series Battery & Solar Powered Cellular/WiFi/Ethernet RTU Controller & Data Logger Pressure, Differential Pressure, Flow, Level, Water Quality, ...
Author: Darleen Andrews
0 downloads 0 Views 2MB Size
PRO Series

Battery & Solar Powered

Cellular/WiFi/Ethernet RTU Controller & Data Logger Pressure, Differential Pressure, Flow, Level, Water Quality, Valve, Weather, Structure, Analog and Digital I/OAuto Data Collection, Cloud Storage, Operation and Monitoring Anytime and Anywhere ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Battery Powered, 5 Year Continuous Operation for 8 Times Data Upload per Day IP68 Continuous Submersible to 5 m of Water, Solution without Cabinet -30~85°C Operating Temperature, 0~100% RH Operating Humidity Cellular, WiFi, Ethernet Communication Redundant Simultaneous Acquisition of Multiple Process Signals including 2 Pressures Sensors, 8 Digital Analyzers and Transmitters, and I/O Module with 2DI, 2DO, 2AI, 2AO 1 Million Log, 3 Year Storage Capacity at Every 30 min Logging 0.01 sec Transient Pressure Auto Detection and Data Logging Smart Control Algorithms of PRV and Valve for Pressure, Flow, Chlorine and Level Optimization Peer to Peer Communication for I/O Exchange Standard Modbus RTU Protocol Seamless SCADA Software and Database Connectivity via OPC Server Web Configuration, Operation, Monitoring, Alarm, Control and Data Analysis Software

RoHS

Outstanding Award

RTU Controller, Data Logger, Device Gateway, Wireless Transmitter, Smart Meter Reader, Digital Transmitter I/O Signal Processing, Data Acquisition, Data Logging, Cellular/ Wireless Communication, Data Monitoring, Alarming, Analysis and Control © 2013 AQUAS. All rights reserved. Specification and product information contained herein are subject to change with notice. Performance varies depending on hardware, software and overall system configuration. Warrenty and RMA policy varies depending on countries, please check with your local distributors or visit www.aquas.com.tw/en GPRS

LOG

IF THEN ELSE

CONTROL MULTIPLE MULTIPLE GPRS IP68 SMS WIRELESS GPS SENSORS I/O PROTECT NETWORK MESSAGE NETWORK POSITION RULES

+75°C -25°C

DATA LOG

Alarm Profile

ALARM

SURGE BATTERY SOLAR PRESSURE OPERATION POWER

OPC SECURITY ULTRA LOW WIDE LOCK POWER TEMPERATURE SERVER

144.9 144.9 145

8.11

GOOGLE DATA EARTH QA/QC

100%

STATISTICS UV ANALYSIS RESISTANT

PRO Series

Battery & Solar Powered Cellular/WiFi/Ethernet RTU Controller and Data Logger The PRO series is a highly reliable and cost-effective remote terminal unit and data logger for data collection, communication, logging, alarming, control and analysis applications. Built-in pressure, differential pressure, level and water quality transmitters, I/Os, cellular, WiFi, Ethernet, RS485, barometer and GPS module. Housing in a robust IP68 water submersible, aluminum alloy enclosure, the products are ideally used in frequently flooded underground chambers and extreme temperature and humidity, outdoor locations such as hydrants, manholes, meter vaults, pump and PRV stations, bunkers, etc. Ultra low power consumption to ensure battery or solar powered for 5 years continuous operation. The RS485 port is able to connect up to 8 digital analyzers and transmitters including pressure, differential pressure, level, free chlorine, PH, ORP,temperature, conductivity, resistivity, dissolved oxygen, turbidity, salinity, suspended solid, ammonium, COD humidity and barometer, analog input, digital input, digital output, vibration wire input, valve position, inclinometer, vibration...etc. It is also able to connect 2 Modbus RTU devices, such as flow meters or PLC.

Benifits ■ Borderless deployment without standard cabin, signal transmitter, communication module, power supply,surge isolation and lighting arrester ■ Eliminate power/networking/sensor/IO cabling, software configuration, engineering and infrastructure cost

■ Seamless connection to public or private network and software solutions ■ Easy to install without calibration and quick connect within seconds, Ideal for mobile operation ■ Low maintenance and trouble shooting, minimizing running and operating cost

Application ■ Minimum night flow leakage analysis ■ District metering and water loss measurement ■ Water distribution network pressure management ■ Water distribution network modeling and calibration ■ Automatic user meter reading ■ Realtime pipeline break detection ■ High speed surge pressure tracking and statistics ■ Reservoir and water tank capacity monitoring and analysis ■ Groundwater level and water quality monitoring and data logging

■ Storm drainage network monitoring ■ Sewer overflow and wastewater quality monitoring ■ River and flood monitoring ■ Water and waste water treatment process monitoring and data logging ■ Water distribution network water quality monitoring ■ Reservoir and river water quality monitoring ■ Water pump optimal control management ■ Rainfall monitoring and alarming

1

PRO Series Features ►Completely Self Contained

►Easy Setup

■ 3G/GPRS/CDMA five band 800/850/1700/1900/2100 MHz global coverage cellular communication ■ License-free 2.4 GHz WiFi network ■ Integral 10 years long life Lithium battery to sustain 5 years continuous operation for hourly data upload per day ■ Optimized solar power module, solar panel and rechargeable Lithium battery for 3 years continuous operation at every 5 minutes data upload per day

■ Cellular/WiFi over the air remote configuration download ■ Setup operation parameters, monitor system, I/O, battery capacity, cellular/WiFi/GPS signal and calibrate sensor via AQCFG software ■ 2.4” LCD display of sensor value, I/O Status, system status, units.

►Robust Outdoor, Compact Construction ■ IP68 continuous submersible to 5 meters of water ■ Operating temperature: -30 to 85 °C; operating humidity: 0~100% RH

►High Capacity and Flexibility ■ 3 signal inputs: I/O module, pressure module, RS485 ■ 4 communication: cellular, WiFi, RS485, Ethernet ■ Built-in I/O modules: 4 digital inputs, 2 relay outputs, 4 analog inputs, 2 analog outputs ■ Connect SMR I/O modules up to 16 digital/analog inputs or relay outputs ■ 4 types of power supply: external power, inernal battery, solar power and external battery box ■ RS485 communication module for data collection, up to 8 SMR digital analyzers and transmitters and 2 serial devices such as flow meters or PLCs ■ Up to 2 internal pressure modules ■ 1,000,000 data values of log

►High Accuracy and Reliability ■ Accuracy of pressure sensor: up to ± 0.1% FS ■ Accuracy of analog inputs: ± 0.025% FS ■ Pressure module with temperature compensation ■ Barometer for level compensation ■ Superior communication performance in underground chamber environment

►Transient Pressure Detection and Logging ■ 0.01 sec transient pressure auto detection and alarming for water hammer, pipeline rupture, leakage, sudden change in demand, negative pressure, pump and valve malfunction, faulty operation, etc. ■ 0.01 sec high speed transient pressure wave logging

►Smart Function ■ Scheduled and alarm communication: data collection, SMS, alarm notification, data upload, setting download, store and forward; upload data more frequently while alarming ■ Log: periodical, event, alarm, transient pressure ■ Configurable alarm (HH, H, L, LL) and actions including, SMS, alarm log and control outputs ■ Programmable control functions: IF_THEN_ELSE, PID, Set Point, time table, alarm, manual ON/OFF ■ Peer to peer communication for I/O and data exchange

►Auto Data Collection, Cloud Storage, WEB Operation and Monitoring ■ Automatic registration and synchronization of device ID, serial number, alias, location and operation settings ■ Automatic GPS locating, time synchronization and coordinates logging with process data ■ Web configuration ,operation, monitoring, alarm, control, Google Map display, statistical analysis, transient pressure analysis, trend, bar graph and tabular report functions ■ Central communication server and application programming library for field device data collection and central communication integration ■ SQL and mySQL database connection for development of application software ■ Seamless SCADA software and database connectivity via OPC server ■ Anytime and anywhere internet operation and monitoring

►Security ■ Login password access protection ■ 128 bits cellular and WiFi encryption to prevent unauthorized access ■ Security cable and lock ■ GPS location deviation anti-theft alarm ■ CE, FCC safety certification

►Quick Installation ■ Quick fit SS316 pressure coupler ■ IP68 quick fit connector for system communication, remote I/O module and RS485 port

2

PRO Series Block Diagram

WiFi

Cellular GPS

● Power

High gain anti theft, anti sabotage antenna

►Internal Battery:

►External Power :

16MB solid state,rotating memory, data will not loss after power failure

● 9~18 V DC ±10%, 1.5 A ►Solar Power:

IP68 continuous water submersible to 5 m water

● PAN01: 3 W 6 V DC Solar Panel, BAT02: 3.6 V DC 10 AH Rechargeable Battery

2.4” LCD display Operating temperature: -30~85 °C Operating humidity: 0~100% RH

● BAT01 3.6 V DC 28 AH Non-rechargeable Battery ● BAT02 3.6 V DC 10 AH Rechargeable Battery ►External Battery Box: ● BAT03 3.6 V DC 60 AH Rechargeable Battery Box

Barometer module(for level compensation)

● Port0: System Configuration Port ►RS232: ● System configuration and data upload/ download ● PLC/DCS/HMI Communication

● Port1: Device Communication Port or Pressure Module 2 ►RS485 Port Connecting up to 8 SMR digital analyzers and transmitters and 2 Modbus RTU serial devices ● SMR Digital Analyzers and Transmitters: Pressure, differential pressure, hydrostatic level, free chlorine, PH, ORP, temperature, conductivity, resistivity, dissolved oxygen, turbidity, salinity, suspended solid, ammonium, COD, humidity and analog input, counter and digital input, digital output, vibration wire input, valve position, inclinometer, vibration

● Modbus RTU Devices: flow meters, PLC, I/O Modules ● PLC/DCS/HMI: drivers for different communication protocols

● Port2: I/O Module

● Port3: Pressure Module

►IO Module A: 4DI, 2DO, 2AI ►IO Module B: 2DI, 4AI ►IO Module C: 4DI ►IO Module D: 2DI,2DO,2AI,2AO ►IO Module E: 2DI, 1DO, 2AI ►IO Module F: 4DI, 2DO, 2AI

►Pressure Module1 ●1/8" SS316 quick fit connection ● ± 0.25% FS or ± 0.1% FS high accuracy ● 0.01 sec transient pressure detection for water hammer, pipeline rupture. negative pressure, sudden change in demand, etc. ● 0.01 sec transient pressure log

● Port2&3: Differential Pressure Module ►Differential Pressure Module: ● 1/8” SS316 quick fit connection ● ± 0.1% FS high accuracy

►Pressure Module 2 ● 1/8” SS316 quick connection ● ±0.25% FS or ±0.1 % FS high accuracy

3

PRO Series Block Diagram

GPS Cellular

WiFi LED light

High gain antenna 16MB solid state,rotating memory, data will not loss after power failure

● Solar Power ● 9W 6 V DC Solar Panel ● 10 AH rechargeable Lithum Battery

IP68 continuous water submersible to 5 m water Operating temperature: -30~85 °C Operating humidity: 0~100% RH Barometer module(for level compensation)

● Port0: System Configuration Port ►RS232: ● System configuration and data upload/ download ● PLC/DCS/HMI Communication

● Port1: Device Communication Port ►RS485 Port Connecting up to 8 SMR digital transmitters and 2 Modbus RTU serial devices ● SMR Digital Analyzers and Transmitters:

● Port2: I/O Module

►IO Module A: 4DI, 2DO, 2AI ►IO Module B: 2DI, 4AI ►IO Module C: 4DI ►IO Module D: 2DI,2DO,2AI,2AO

hydrostatic level, free chlorine, PH, ORP, temperature, conductivity, resistivity, dissolved oxygen, turbidity, salinity, suspended solid, ammonium, COD, analog input, counter and digital input, digital output

● Modbus RTU Devices: flow meters, PLC, I/O Modules

4

PRO Series System Architecture The PRO Series is fully integrated with cellular, WiFi, RS485 and Ethernet communication, providing seamless connections from sensors and I/O to public or private network.

AQWEB/AQOPC Station

System Architecture

■ Notebook with AQCFG software for configuration ■ AQWEB WEB Server software for configuration, Sensor I/O Device

automatic data acquisition and storage, remote monitoring, N

Node

tabular report functions

3G/GPRS/CDMA Cellular Network

.N ..... ...... ... AP Node ....... . . . . . . . WiFi AP .EN

S

WiFi AP

Sensor I/O Device

Sensor I/O Device N

N

Node

Node

Sensor I/O Device

Sewage Treatment Plant

AP

.. ..

.....

N

N

Node

N

Node

Sensor I/O Device

.N ...... AP.......N ... . ... ... .N .N .. WiFi AP

Sensor I/O Device

N

Node

N

Wastewater Treatment Plant

.......

Sensor I/O Device

AP

WiFi AP

WiFi AP

N

Factory & Buildings

Sensor I/O

■ Standard Modbus RTU protocol

N

Water Treatment Plant

■ Peer to peer communication

■ RS485 serial communication

Sensor I/O Device

N

..... ..... .....

AQCFG

...

. ....

AP

■ Borderless cellular and WiFi communication

SMR Digital Analyzer and Transmitter

WiFi Network

... .

devices, logged with time stamp

Node

.......

devices, logged with time stamp ■ Borderless cellular and WiFi communication

■ Periodically sample digital transmitters, I/Os and serial

Sensor I/O Device

Wireless Configuration Module

■ Periodically sample digital transmitters, I/Os and serial

ECO Wireless Transmitter & Data Logger

................. . ... . . .... .... ....

WiFi AP

N

... ... .

AP

Ethernet

AQWEB

AQWEB

Node

PRO RTU Controller & Data Logger

■ Peer to peer communication

Control Room S

S

Device SMR

N

AP

PRO/ECO

WiFi AP

3G/GPRS/GSM

Ethernet

S AQWEB/AQOPC

WiFi

......

Sensor I/O Device

......

software

Tank

Node Pipe Network Flow Meter Chamber Fire Hydrant

WiFi AP GATE

.........

■ Application interface library for developing user customized

AP

Node

Sensor I/O Device

N

Reservoir

■ Seamless SCADA software and database connectivity via AQOPC OPC server

Node

Pumping Station

.....

transient pressure analysis, time series trend graph and

Sensor I/O Device

.....

alarming, control, Google Earth fusion display, data analysis,

Sensor I/O Device

E

N

RS232/485

■ Up to 1.2 Km transmission distance

5

PRO Series Specifications General ■ CPU: 32 bits ■ Memory: type: solid state, non-volatile flash; Size: 16 MB;

rotating, no log or setting data loss after power failure ■ Real-time Clock: type: crystal controlled calendar clock with leap year adjustment; accuracy: 10 seconds per month; GPS and NTP server auto time synchronization, accuracy: 1 ms (GPS), 1~3 sec (NTP) ■ Environment: protection: IP68, continuous submersible to 5 meters of water; operating temperature: -30~85 °C; operating humidity: 0~100% RH ■ Safety: CE, FCC

■ Surge protection: 1500 V DC ■ Protocol: Modbus TCP

GPS Module ■ ■ ■ ■

Frequency: 1575.42 MHz Position accuracy: 2.5 m Time accuracy: 300 nsec Antenna: 28±3 dBi

Barometer Module

■ Data Collection: SMR digital transmitters, flow meters or

Pressure ■ Range: 10~ 1300 mbar ■ Operating temperature: -30 ~ 85 °C ■ Accuracy:± 0.0015 Kgf/cm² ■ Resolution: 24 bits

■ Communication: data transmission; SMS alarm

LCD Display Module

Function Modbus RTU devices

notification; data upload/download; store and forward; FTP ■ Log: 1,000,000 data values, rotating store; periodical, event, alarm, transient pressure ■ Alarm: HH, H, L, LL; alarm action:relay output, SMS, alarm log ■ Control: IF_THEN_ELSE, PID, set points, time table, alarm output, manual ON/OFF

GSM/GPRS Module ■ Standard: GSM/GPRS ■ Frquency: 850/900/1800/1900 MHz ■ Antenna: 3 dBi

3G Module ■ Standard: UMTS/HSPA+/AWS ■ Frequency: 800/850/1700/1900/2100 MHz ■ Antenna: 3 dBi

CDMA

■ 2.4” with back light ■ Display: sensor and transmitter values, I/O status, system and communication status, unit

■ 3 numbers: 9 digits,4½ digits,1½ digits ■ Dimensions: 60(W) x 34(H) Housing ►Standard ■ Material: Aluminum alloy ■ Dimensions: 220(W)×230(H)×85(D) mm ■ Weight: approx. 3 Kg ►Buoys System ■ Material: Polypropylene ■ Dimension: Φ460 x 335 mm ■ Weight: approx. 14 Kg Power ►External Power

■ Standard: CDMA/CDMA 2000 ■ Frequency: 800/1900 MHz ■ Antenna: 3 dBi

■ Voltage: 9-18 V DC ±10%, 1.5 A ■ Surge protection: 4000 V DC ■ Isolation: 1000 V DC ■ ESD line rotection:15 KV DC

WiFi Module

►Internal Battery

■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Standard: IEEE 802.11b Data rate: Up to 11 M bps Frequency: 2.412~2.497 GHz Modulation: direct sequence spread spectrum(DSSS) Supported topologies: Star Max. transmitter power output: 18 dbm Receive sensitivity: -83~-92 dBm Range: up to 1 Km Antenna: 3 dBi (external) Security: WPA/WPA2

■ Non-rechargeable 3.6 V DC 28 AH lithium cell ■ Life: 10 years

►Internal Battery

■ Rechargeable 3.6 V DC 10 AH lithium cell ■ Life: minimum 300 charge/discharge cycles

► Solar Power

■ Type: 6 V DC, 3 W solar panel ■ Rechargeable 3.6 V DC 10 AH lithium cell

Ethernet Module

■ Life: minimum 300 charge/discharge cycles

■ Data rate: 10/100 Mbps

6

PRO Series Specifications ►External Battery Box:

I/O Module B

■ Life:minimum 300 times charge/discharge cycles

►Digital inputs

■ Rechargeable 3.6 V DC 60 AH lithium cell ■ Number of channels: 2 counter or state inputs

System Configuration Port (Port0)

■ Type: 3.5-12 V DC or dry contact single ended

RS232 Module

■ Maximum operation frequency: 1 KHz

■ System configuration and data upload/ download

■ Minimum pulse width: 10 msec

■ 115,200bps, 8 bits, no parity, 1 stop bit

■ Surge protection: 4000 V DC

■ Surge protection: 4000 V DC

■ Isolation: 1000 V DC

input

■ Protocol: Modbus RTU or proprietary device drivers

Device Communication Port

►Analog inputs

■ Number of channels: 4

■ Resolution: 15 bits

RS485 Module

■ Accuracy: 0.025% FS

■ Device data collection, connecting up to 8 SMR digital

■ Signals: 0~1 V DC, 0~10 V DC, 4~20 mA

transmitters and 2 serial devices

■ Surge protection: 4000 V DC

■ 19200bps, 8 bits, no parity, 1 stop bit ■ Surge protection: 4000 V DC

I/O Module C

■ Isolation: 1000 V DC ■ Protocol: Modbus RTU or proprietary device drivers

►Digital inputs

■ Number of channels: 4 (2 counter or state inputs, 2

I/O Module A

state inputs) ■ Type: 3.5-12 V DC or dry contact single ended

►Digital inputs

■ Number of channels: 4 (2 counter or state inputs and 2

state inputs) ■ Type: 3.5-12 V DC or dry contact single ended

input ■ Maximum operating frequency: 1 KHz ■ Minimum pulse width: 10 msec ■ Surge protection: 4000 V DC

input ■ Maximum operating frequency: 1 KHz

I/O Module D

■ Minimum pulse width: 10 msec ■ Surge protection: 4000 V DC

►Digital inputs

■ Number of channels: 4 (2 counter or state inputs and 2

►Digital outputs

■ Number of channels: 2 ■ Type: relay, 2 poles

state inputs) ■ Type: 3.5-12 V DC or dry contact single ended

input

■ Load: 0.5 A 125 V AC; 1 A 30 V DC

■ Maximum operating frequency: 1 KHz

■ Maximum operating frequency: 20 Hz

■ Minimum pulse width: 10 msec

■ Surge protection: 4000 V DC

■ Surge protection: 4000 V DC

►Analog inputs

►Digital outputs

■ Resolution: 15 bits;

■ Type: relay, 2 poles

■ Accuracy: 0.025% FS

■ Load: 0.5 A 125 V AC; 1 A 30 V DC

■ Signals: 0~1 V DC, 0~10 V DC, 4~20 mA

■ Maximum operating frequency: 20 Hz

■ Surge protection: 4000 V DC

■ Surge protection: 4000 V DC

■ Number of channels: 2

■ Number of channels: 2

7

PRO Series Specifications ►Analog inputs

■ Number of channels: 2

■ Resolution: 15 bits;

►Digital outputs

■ Number of channels: 2

■ Accuracy: 0.025% FS

■ Type: relay, 2 poles

■ Signals: 0~1 V DC, 0~10 V DC, 4~20 mA

■ Load: 0.5 A 125 V AC; 1 A 30 V DC

■ Surge protection: 4000 V DC

■ Maximum operating frequency: 20 Hz

►Analog outputs

■ Number channels: 2 ■ Resolution:12 bits ■ Accuracy:0.1% FS ■ Signals: 4~20 mA ■ Surge protection: 4000 V DC ■ Load resistor: 50 or 500 ohms

I/O Module E (Solenoid Control) ►Digital inputs

■ Number of channels: 4 (2 counter or state inputs, 2

state inputs) ■ Type: 3.5-12 V DC or dry contact single ended

input ■ Maximum operating frequency: 1 KHz ■ Minimum pulse width: 10 msec ■ Surge protection: 4000 V DC

►Digital outputs

■ Number of channels: 1 ■ Type: ±12 V DC snap shot output (0.5 sec) for solenoid

control ■ Load: 1 A 12 V DC ■ Operating frequency: 10 Hz ■ Surge protection: 4000 V DC

►Analog inputs

■ Number of channels: 2

■ Resolution: 15 bits ■ Accuracy: 0.025% FS ■ Signals: 0~1 V DC, 0~10 V DC, 4~20 mA ■ Surge protection: 4000 V DC

I/O Module F (PRV Control) ►Digital inputs

■ Number of channels: 4 (1 counter input and 3 state

inputs) ■ Type: 3.5-12 V DC or dry contact single ended

input ■ Maximum operating frequency: 1 KHz ■ Minimum pulse width: 10 msec ■ Surge protection: 4000 V DC

■ Surge protection: 4000 V DC

►Analog inputs

■ Number of channels: 2

■ Resolution: 15 bits; ■ Accuracy: 0.025% FS ■ Signals: 0~12 V DC, 4~20 mA ■ Surge protection: 4000 V DC

Pressure Module ■ Measurement range: 0~1/5/10/15/20/35 Kgf/cm² ■ Operating temperature: -30 ~ 125 °C ■ Accuracy: ± 0.25% FS or ± 0.1% FS ■ Resolution: 0.05% FS ■ Repeatability: ±0.025% FS ■ Stability (annual): ±0.1 % FS ■ Overload: 3 X ■ Burst: 4 X ■ Connection: 1/8” quick fit coupler ■ Housing: SS316

Differential Pressure Module ■ Messurement range: 0~0.05/0.25/0.5/1/5/20 Kgf/cm ■ Operating temperature: -30-125 °C ■ Accuracy: ± 0.1% FS ■ Resolution: 0.05% FS ■ Repeatability: ±0.025% FS ■ Stability(annual): ±0.1 % FS ■ Overload: 3 X ■ Burst: 4 X ■ Connection: 1/8” quick fit coupler ■ Housing: SS316

Digital Analyzer and Transmitter ■ Pressure, differential pressure, level, free chlorine, PH, ORP, temperature, conductivity, resistivity, dissolved oxygen, turbidity, salinity, suspended solid, ammonium, COD, humidity, differential pressure, barometer, analog input, counter input, digital input, digital output, vibration wire input, valve position, inclinometer, vibration

8

PRO Series Applications Type

Order Selection PRO-XXXXXX

Port Assignment

Applications Port1

Port2

Port3

A

Multiple Water Quality, Flow and Level Monitoring for Source Water, Water Distribution, Waste Water, Process Water, Aquaculture and Fishery

RS485

I/O Module A/B/C/D None

B

PRV Control

Pressure 2

I/O Module F

Pressure 1

C

Pump Control, Pressure, Transient, V i b r a t i o n a n d T e m p e r a t u r e RS485 Monitoring

I/O Module A/D

D

Chlorine Control(Auto Flush), Pressure, Transient Monitoring

I/O Module E

E

Tank Differential Pressure, Level, Pressure 2 Presure, Multiple Water Quality or RS485 Monitoring

Differential Pressure

F

Valve & Gate Control

RS485

I/O Module A/D

G

Dosing Pump Control

RS485

I/O Module A/D

RS485

Main Unit

Port1

PRO-XXXXXX

Port2

Port3

21XXX 22XXX 23XXX 24XXX

300000

27000

3XXXXX

Pressure 1

11X Cellular Module WiFi Module GPS Module 12X Barometer Module LCD Display 11X Power

21XXX 24XXX

3XXXXX

Pressure 1

11X

26000

3XXXXX

10X 12X

25XXX

300000

Pressure 1

11X

21XXX 24XXX

3XXXXX

None

11X

21XXX 24XXX

300000

Example Battery Life GSM/GPRS Module

WIFi Module

Battery Power I/O, Log, Alarm Data Upload Interval Interval 10-AH(IR) 28-AH (INR) 60-AH(ER) 3W Solar Panel (w 10-AH(IR))

Approximate Battery Life

Battery Power I/O, Log, Alarm Data Upload Interval Interval

1 hour 2 minutes 15 minutes 1 minute 2 minutes 1 minute

12 hours 2 hours 3 hours 1 hour 2 hours 15 minutes

5+ Years 1+ Year 5+ Years 1+ Year 5+ Year 1+ Year

28-AH (INR)

5 minutes

5 minutes

5+ Years

3W Solar Panel (w 10-AH(IR))

10-AH(IR)

60-AH(ER)

Approximate Battery Life

15 minutes 2 minutes 3 minutes 2 minutes 1 minute 1 minute

8 hours 1 hour 2 hours 15 minutes 1 hour 10 minutes

5+ Years 1+ Year 5+ Years 1+ Year 5+ Year 1+ Year

5 minutes

5 minutes

5+ Years

IR=Internal Rechargeable Battery INR=Internal Non-rechargeable Battery ER=External Rechargeable Battery Pack

Optionals Hub, Cable and Accessories

Buoy, Battery and Solar Panel

BAT01

BAT02

PAN01

BAT03

Order No.

BUO01

Description

BOX01

BOX02

QFC02

Order No.

CAB02

CAB12

RFC01

Description

BAT01

3.6 V DC 28 AH, non-rechargeable lithium battery

BOX01

IP68 4 port RS485 hub

BAT02

3.6 V DC 10 AH, rechargeable lithium battery

BOX02

IP68 8 port RS485 hub

BAT03

3.6 V DC 60 AH, IP68 rechargeable lithium battery box

QFC02

1/8” quick coupler cable for pressure sensor(1.5 m hose)

PAN01

IP67 6 V DC, 3.0 W solar panel

CAB02

Configuration cable (1.5 m, USB interface)

CAB12

IP68 2 port RS485 cable (20 cm)

PRV Actuator

Order No. PRV01

Description IP68 PRV actuator

Email:[email protected]. Phone: +886-2-8797-5358 Fax: +886-2-2657-8926 Address: AQUAS INC.11F-3, No.408,Ruiguang Rd.,Taipei 11492,Taiwan

9

PRO Series Optionals RS485 Digital Analyzers and Transmitters

Order No. SMR01-1 SMR01-2 SMR01-3 SMR01-4 SMR01-5 SMR01-6 SMR01-7 SMR02-1 SMR02-2 SMR02-3 SMR02-4 SMR02-5 SMR02-6 SMR03-1 SMR03-2 SMR04-1 SMR05-1 SMR06-1 SMR06-2 SMR07-1 SMR07-2 SMR08-1 SMR09-1

Description Digital pressure transmitter (0~1 Kgf/cm²) Digital pressure transmitter (0~5 Kgf/cm²) Digital pressure transmitter (0~10 Kgf/cm²) Digital pressure transmitter (0~15 Kgf/cm²) Digital pressure transmitter (0~20 Kgf/cm²) Digital pressure transmitter (0~35 Kgf/cm²) Digital pressure transmitter (0~60 Kgf/cm²) Digital hydrostatic level transmitter (0~10 m) Digital hydrostatic level transmitter (0~50 m) Digital hydrostatic level transmitter (0~100 m) Digital hydrostatic level transmitter (0~200 m) Digital hydrostatic level transmitter (0~350 m) Digital hydrostatic level transmitter (0~600 m) Digital free chlorine analyzer (0~10 ppm) Digital free chlorine and pH analyzer (0~5 ppm) Digital pH and temperature analyzer (0~14 pH) Digital ORP(Redox) and temperature analyzer (-1000~1000 mV) Digital temperature transmitter (pt100)(-40~85 °C) Digital temperature transmitter (pt100)(-40~350 °C) Digital conductivity and temperature analyzer (0 ~ 5 ms/cm) Digital conductivity and temperature analyzer (0 ~ 50 ms/cm) Digital resistivity and temperature analyzer (0~20 MΩ) Digital dissolved oxygen and temperature analyzer (electrochemical)(0~20 ppm)

SMR09-2

Digital dissolved oxygen analyzer (optical)(0.00~20.00 ppm)

SMR10-1 SMR10-2 SMR10-3 SMR10-4 SMR11-1 SMR12-1 SMR12-2 SMR13-1 SMR14-1 SMR14-2 SMR14-3 SMR14-4 SMR14-5 SMR14-6 SMR15-1 SMR16-1 SMR16-2 SMR16-3 SMR17-1 SMR17-2 SMR17-3 SMR17-4 SMR17-5 SMR17-6 SMR18-1 SMR18-2 SMR18-3 SMR19-1 SMR19-2 SMR19-3 SMR20-1 SMR21-1 SMR21-2 SMR22-1 SMR23-1 SMR24-1

Digital turbidity analyzer (0~10 NTU) Digital turbidity analyzer (0~100 NTU) Digital turbidity analyzer (0~1000 NTU) Digital turbidity analyzer (0~4000 NTU) Digital salinity and temperature analyzer (0~100 ppt) Digital suspended solid analyzer (0~100 ppm) Digital suspended solid analyzer (0~1000 ppm) Digital humidity transmitter (0 ~ 100% RH; -40~85 °C) Digital differential pressure transmitter (0~0.05 Kgf/cm²) Digital differential pressure transmitter (0~0.25 Kgf/cm²) Digital differential pressure transmitter (0~0.5 Kgf/cm²) Digital differential pressure transmitter (0~1 Kgf/cm²) Digital differential pressure transmitter (0~5 Kgf/cm²) Digital differential pressure transmitter (0~20 Kgf/cm²) Digital barometer transmitter (-40~85 °C; 10~1300 mbar) Analog input transmitter (4-20 mA, 2 channels) Analog input transmitter (4-20 mA, 4 channels) Analog input transmitter (4-20 mA, 8 channels) Counter input transmitter (2 channels) Counter input transmitter (4 channels) Counter input transmitter (8 channels) Digital input transmitter (2 channels) Digital input transmitter (4 channels) Digital input transmitter (8 channels) Digital output transmitter (2 channels) Digital output transmitter (4 channels) Digital output transmitter (8 channels) Vibration wire input transmitter(1 channel) Vibration wire input transmitter(2 channels) Vibration wire input transmitter(4 channels) Digital gate position transmitter (0~100%) Digital inclinometer analyzer (±15 °)(vertical) Digital inclinometer analyzer (±15 °)(horizontal) Digital vibration and temperature analyzer (±25 mm/s) Digital ammonium and temperature analyzer (0.1~1,000 ppm) Digital wind direction transmitter (0~360°)

SMR25-1

Digital COD and temperature analyzer (0~100 ppm)

Ordering Model No:

PRO-

Cellular or Ethernet Module 0 None 1 GSM/GPRS 2 3G 3 CDMA 4 Ethernet Wireless Module None 0 WiFi 1 GPS Module 0 None 1 Add-on Barometer Module 0 None 1 Add-on LCD Display Module None 0 Metric Unit 1 British Unit 2 Power External Power (No battery) Internal Battery (3.6 V DC 28 AH, Non-rechargeable) Internal Battery (3.6 V DC 10 AH, Rechargeable) Solar Panel (3 W 6 V DC 10 AH, Rechargeable) External Battery Box (3.6 V DC 60 AH, Rechargeable) Port1 (Device Communication Module or Pressure 2) None RS485 Pressure Module 2 (Range same as pressure module 1) Driver None Customer Specify Port2 (I/O Module or Differential Pressure Module *Note1) None I/O Module A I/O Module B I/O Module C I/O Module D Differential Pressure Module I/O Module E I/O Module F Range(Kgf/cm²) None 0.05 0.25 0.5 1 5 20 Type None Absolute Accuracy None 0.1% FS Port3 (Pressure Module 1 *Note1) None Add-on Range(Kgf/cm²) None 0~1 0~10 0~20 0~5 0~15 0~35 Type None Absolute Gauge Accuracy None 0.25% FS 0.1% FS Transient Pressure Detection Module None Add-on Housing None Aluminum alloy Buoys System

-1

-2

-

-3

0 1 2 3 4 0 1 2 0 1 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 0 1 0 1 0 1 0 1 2 3 4 5 6 0 1 2 0 1 2 0 1 0 1 2

Note: 1. Choose 5 of port 2 for differential pressure, the pressure module1 is mounted on port1 if selected. 2. The product is customizable designed with different kinds of sensors, I/O modules and devices protocols upon request.

10