Energy Conservation Case Study for Mini Office Retrofitting Multiple Split Air Conditioners With Digital Scroll VRF at ICPCI, Powai, Mumba...
Energy Conservation Case Study for Mini Office Retrofitting Multiple Split Air Conditioners With Digital Scroll VRF at ICPCI, Powai, Mumbai Manas Kundu, ICPCI on 18 Dec 2009
Executive Summary • Retrofitted 7 nos. Split ACs with latest technology Digital Scroll VRF at a Small Office in Mumbai – To Improve Comfort Conditions & To Reduce Energy Bill
• TERI assigned with Pre & Post Audit for Verification of Energy & Comfort conditions before and after VRF Installation • Project Timelines – Baseline Energy Audit In April 2008 – Digital Scroll VRF Commissioned In May 2008 – Post Installation Audit In August 2009
• Energy Consumption Reduced In kWHr By 31% On Annual Basis –
38% Energy Cost Saving Realized
1
12/21/2009
Agenda • • • • •
Challenges Faced Pre Audit Findings Digital Scroll VRF Technology Post Audit Findings Results
Agenda • • • • •
Challenges Faced Pre Audit Findings Digital Scroll VRF Technology Post Audit Findings Results
2
12/21/2009
Back Ground • International Copper Promotion Council India (ICPCI) Office Is At Hiranandani Gardens, Omega Complex, Powai, Mumbai-76 • 2,000 Sq Ft And 11 Employees • Leased Property Since June 2000; Promoters Hiranandani Builders • Six + Basement Storey Building; ICPCI Office Is At 6th Floor • Original Property Came With 7 Split Air Conditioners Fitted At Different Places In The Offices
Details Of Air Conditioners Used
3
12/21/2009
Challenges Faced
• Existing Split ACs Could Not Maintain Comfort Conditions – Situation Persisted Even Under AMC With A Reputed Dealer • Increasing Trend Of Annual AC Energy Consumption – ICPCI Power Supply Under LT2 Tariff From Reliance Power • Intangible Challenges – Ashthetic Looks, Pigeon Menace – Floor Space Utilization For Outdoor Units – High Sound Level Of Outdoor Units • ICPCI Felt A Strong Need To Improve The Conditions – ICPCI Discussed The Issue With Emerson Climate Technologies – Evaluating Alternate Option (5 star Vs VRF Vs Inverter) – Decided To Switch Over To Digital Scroll VRF AC System
Agenda • • • • •
Challenges Faced Pre Audit Findings Digital Scroll VRF Technology Post Audit Findings Results
4
12/21/2009
Energy Audit • TERI ---Industrial Energy Efficiency Division, Bangalore • Instruments Used – – – – – –
Krykard ALM-32 Power & Harmonics Analyser Fluke- 41B Power & Harmonics Analyser Anemometer Digital Indicators & Thermocouples Lux Meter Multi Function Kit
Pre Audit Methodology • Parameters Measured By TERI –
–
– –
Temperature & Relative Humidity Of Inlet & Outlet Air , User Area Velocity & Flow Rate Of Air Across The Condensers KW, KVA, Power Factor, Amperage & Voltage Lux Level
5
12/21/2009
Pre Audit Findings
Monthwise Electrical Consumption & Cost
Performance Evaluation Of AC Units
Comparison With BEE Guidelines Area
Actual Floor Capacity Area TR Sq.M
Specific TR/Sq.M
Reception
0.46
12.54
0.036
Server Room
0.74
5.02
0.147
Main Hall
0.95
23.65
0.040
Director Chember
0.71
11.78
0.060
CEO Chember
0.99
12.47
0.080
Main Hall
0.89
38.87
0.023
Conference Room
1.52
20.8
0.073
Specific TR/Sqm Of Facility
Particulars
Specific TR/Sq.M
Small Office Cabins
0.1
Medium Size Cabins and Centralized AC
0.06
Large Office With Centralized AC
0.04
BEE Guidelines Of TR/ Sq m For Different Complexes
6
12/21/2009
Electrical Load Facility
Loading Parameters ICPCI Incomer
Power Consumption With Time
Connected Lighting Load Load Trend Of The Facility Measured Lux Levels
Agenda • • • • •
Challenges Faced Pre Audit Findings Digital Scroll VRF Technology Post Audit Findings Results
7
12/21/2009
VRF A/C Market Transition VRF A/C
Conventional Splits
Benefits Of VRF A/C Systems
± °C
• Precise Temperature Control 0.5 • Better Humidity Control • Individual Room Comfort Control • Superior Aesthetics & Prestige
Fixed Speed Systems Do Not Match Load Requirements Compressor Output
Compressor Cycling (Inefficient)
Inadequate Heating
-20
-10
0
10
20
Inadequate Cooling
30
40
Ambient Temperature (o C)
Heating
Cooling
8
12/21/2009
Modulated Compressor Matches Supply & Demand • Capacity Matches Load • Energy Savings • High Comfort Compressor Output
Inverter 40% - 100%
Digital Scroll 10% - 100%
-20
-10
0
10
20
Ambient Temperature (o C)
Heating
30
40 Cooling
Emerson Climate Technologies Powering The Leading Air Conditioning Systems
Digital Scroll Technology
Energy Saving Reliability Human Comfort Flexibility
India OEMs: (1) Blue Star, (2) Carrier, (3) Samsung, (4) Voltas and (5) York
9
12/21/2009
Digital Scroll Control System
+
+
Basic Package
Indoor Controller
Remote
Typical Modulated System Configuration Communication
Outdoor Unit
Multiple Indoor Units
10
12/21/2009
Modulation Mechanism
1.0 mm Scroll Separation
Loaded (1)
Unloaded (0)
Full Capacity
Zero Capacity
Ex: 20% Output
Ex: 50% Output Full Capacity
Full Capacity
Zero Capacity
Zero Capacity
2 Sec
5 Sec
8 Sec
5 Sec
Seamless Capacity Delivery Capacity = (Loaded Time x 100% + Unloaded Time x 0%) Total Time Example: Cycle Time = 10 Seconds Capacity
Loaded Time
10% 11% 12% … … 25% … 50% … 90%
1.0 Second 1.1 Second 1.2 Second
2.5 Second 5.0 Seconds 9.0 Seconds
11
12/21/2009
Part Load Function Of Digital VRF 12 HP Example Sequence Of Compressor Operation 6HP Digital
6HP Fixed
Part Load %
100% (12.0HP) 90% (10.8HP) 75% (9.0HP)
ON : No modulation ( 6HP ) ON 80% Modulation (4.8HP) ON 50% Modulation (3.0HP)
ON ( 6HP) ON ( 6HP) ON ( 6HP)
50% (6.0HP)
ON : No modulation (6HP)
OFF (0HP)
30% (3.6HP)
ON 60% Modulation (3.6HP)
OFF (0HP)
25% (3.0HP)
ON 50% Modulation (3.0HP)
OFF (0HP)
10% (1.2HP)
ON 20% Modulation (1.2HP)
OFF (0HP)
ON 10% Modulation (0.6HP)
OFF (0HP)
5% (0.6HP)
Details of Digital VRF System To Replace Existing Multiple Split ACs • Digital VRF Airconditioner –
–
Designed,Manufactured,Installed & Commissioned By Blue Star Copeland Digital Scroll Compressor Used In The VRF AC
• Switched From Seven Nos of R22 Gas 1.5 & 2 TR Split ACs To Single 12HP R410A Digital VRF AC Connected To Eight Indoor Units • All Digital VRF Systems Come With R410A Gas, Taking Care Of Future Need Of R22 Phase-out, To Protect Climate (Reducing Global Warming)
12
12/21/2009
Agenda • • • • •
Challenges Faced Pre Audit Findings Digital Scroll VRF Technology Post Audit Findings Results
Last Three Years Electrical Consumption
13
12/21/2009
Last Three Years Energy Bill Pattern
Note: Difference In Percentage Saving & Cost Saving is Due To Change In Tariff From Rs 8.5 To Rs. 9.4 Per kWHr
Results • 31% Annual Energy (kWh) Saving • Improved Human Comfort & Working Environment – – –
• • • •
Low Sound Performance Flexibility In Using Different Types & Capacities Of Indoor Units Allows Different Rooms To Be Set At Different Temperatures
38% Realized Annual Electricity Bill (Cost) Saving Transition To Environment Friendly R410A Refrigerant Improved Aesthetic Look (Internal and External) Outdoor Unit Floor Space Savings
14