Electric Wiring. Outdoor unit CCM. Indoor unit. (1) Address code setting

Content Electric Wiring Electric Wiring Electric Wiring (1) Address code setting CCM Outdoor unit Indoor unit Address code setting for out...
Author: Katherine Henry
3 downloads 0 Views 11MB Size
Content

Electric Wiring

Electric Wiring

Electric Wiring

(1) Address code setting

CCM

Outdoor unit

Indoor unit

Address code setting for outdoor unit Address setting switch (network)

Address setting switch (outdoor communication)

Address code setting for outdoor unit Address setting switch for communication among outdoor unit Each outdoor unit need a independent address code Address setting 0

Master unit

1

Salve unit

2

Salve unit

3

Salve unit

≥4

Invalid address, cause system error

Caution:  The address can be not beyond 0~3;  The address of each outdoor unit must be different.

Address code setting for outdoor unit Address setting switch for communication of network (CCM02) Because the CCM02 can be connected with 8 groups of outdoor units, each outdoor unit need two switches to label the address

For the address of different group

For the address of different outdoor unit in one group

Caution:  Only when outdoor units are connected with CCM02, the above two switch need to be changed.

Address code setting for indoor unit Address setting switch ( for communication with outdoor unit)

Address setting switch (network)

Address code setting for indoor unit Indoor unit Address code for communication between indoor units and outdoor units: Switch

Address Code

00 ~ 15

Eg: 33

16 ~ 31 32 ~ 47 48 ~ 63

Caution:  The address of each indoor unit must be different.

Address code setting for indoor unit Indoor unit Address code for network

Switch

(between indoor units and CCM):

Address Code

00 ~ 15 16 ~ 31 32 ~ 47 48 ~ 63

Caution:  The address of each indoor unit must be different.

Electric Wiring

Electric Wiring All wires, parts and material must conform to local standards All wiring work must be done by qualified person

Voltage range: rated voltage ±10%;

(2) Power supply

Basic requirement

Independe nt power supply;

Capacity of power device is bigger enough;

Well and reliable PE line

Electric Wiring

(2) Power supply

Power supply for outdoor unit

Creepage breaker Manual switch

3-phase 380/400/415V

earth

Electric Wiring

(2) Power supply

Power supply for outdoor unit •

The power supply of outdoor units are in series connection

earth

3-phase 380/400/415V

Creepage breaker Manual switch

We don’t suggest power wiring like this, because the power wire of the first outdoor unit is too big to be fixed in the terminal of outdoor unit.

Electric Wiring

(2) Power supply

Power supply for indoor unit

(1)

(2)

6.860 kW MDV-D71T2/N1-A3 IU-1 6.860 kW MDV-D71Q4/N1 IU-2

(3)

5.411 kW MDV-D56G/N1Y-C IU-3 8.696 kW MDV-D90T2/N1-A3 IU-4

Electric Wiring

(2) Power supply

Power supply for indoor unit (1)

Wiring branch box

Wiring (2) branch box

6.860 kW MDV-D71T2/N1-A3 IU-1 6.860 kW MDV-D71Q4/N1 IU-2

Manual switch Creepage switch (3)

5.411 kW

Wiring branch box 230v 50Hz 1N Power supply

MDV-D56G/N1Y-C IU-3 8.696 kW MDV-D90T2/N1-A3 IU-4

Strongly recommend: all the indoor units are connected with the same power supply •95

Electric Wiring

(2) Power supply

Power supply for indoor unit (1)

230v 50Hz 1N

Creepage switch

Manual switch

Wiring (2) branch box

6.860 kW MDV-D71T2/N1-A3 IU-1 6.860 kW MDV-D71Q4/N1 IU-2

230v 50Hz 1N

Creepage switch

Manual switch

(3)

5.411 kW

Wiring branch box

MDV-D56G/N1Y-C IU-3 8.696 kW MDV-D90T2/N1-A3 IU-4

If not possible, please guarantee that the power supply for all the indoor units are switched on when the system is running

Electric Wiring

L1 L2 L3N

(2) Power supply The spec of the outdoor power supply wire is selected according to the max. total current of outdoor units

L N

The spec of the wire is selected according to the max. total current of indoor units

Indoor unit

Controller

2

Electric Wiring

(3) Signal wire

Signal wire: The signal wire should use •

Between outdoor units in one combination;



Between outdoor unit and indoor unit; Master unit

P,Q, E

H1,H2, E

P,Q, E

Slave unit

H1,H2, E

P,Q, E

3-core shielding wire

Slave unit

H1,H2, E

P,Q, E

P,Q, E

2

Electric Wiring

(3) Signal wire

Signal wire: The signal wire should use •

Between outdoor units and CCM02;

Master unit

K1,K2, E

Slave unit

K1,K2, E

3-core shielding wire

Slave unit

K1,K2, E K1,K2, E

•Max. 32 outdoor units in 8 combination can be connected with CCM02; •All the outdoor units are in series connection.

2

Electric Wiring Signal wire: •

Between outdoor units and digital ammeter;

(3) Signal wire

2

Electric Wiring

(3) Signal wire

Signal wire: •

Wring terminals of ammeter

Between outdoor units and digital ammeter; Terminals of signal wire

Terminals of power supply

400v 50Hz 3N

2

Electric Wiring

(3) Signal wire

Signal wire: •

Back

Wring terminals of ammeter;

To power supply

Supply power to outdoor unit

2

Electric Wiring

(3) Signal wire

Signal wire: • •

The signal wire should use

Between indoor unit and CCM;

3-core shielding wire

Between CCM and computer.

X,Y, E

F1,F2, E

X,Y, E

F1,F2, E

X,Y, E

F1,F2, E

X,Y, E

X,Y, E

Electric Wiring

(3) Signal wire

Key point: 1.Signal wire should be 3-core shielding wire 2.The shielding skin is connected with PE 3. Keep away from the strong wire 4. Correct polarity; (P-P, Q-Q, X-X…………..) 5. Series connection