DUCTILE IRON PIPE BEDDING DETAIL

SPECIAL EARTHEN MATERIALS AND COMPACTION 12" #57 STONE INITIAL BACKFILL SPRING LINE OF PIPE 4" MIN. STONE OR SPECIAL COMPACTION HAUNCHING BEDDI...
Author: Darcy Carpenter
2 downloads 0 Views 1MB Size
SPECIAL EARTHEN MATERIALS AND COMPACTION

12"

#57 STONE

INITIAL BACKFILL

SPRING LINE OF PIPE

4" MIN.

STONE OR SPECIAL COMPACTION

HAUNCHING BEDDING 6" MAX.

EMBEDMENT MATERIAL

FOUNDATION (MAY NOT BE REQUIRED)

NOTE: 1. SEE SPECIFICATIONS FOR PIPE INSTALLATION REQUIREMENTS 2. CLASS "B" BEDDING OR BETTER REQUIRED FOR ALL SEWERS

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE DRAWING NO.

DUCTILE IRON PIPE BEDDING DETAIL

A

H

W

S

W

Y

C A TE R

&

S E WE GE A R

T I R HO UT A

S01

SPECIAL EARTHEN MATERIALS AND COMPACTION

12"

#57 STONE

SPRING LINE

INITIAL BACKFILL

HAUNCHING

OF PIPE

4" MIN.

STONE OR SPECIAL COMPACTION

BEDDING 6" MAX.

EMBEDMENT MATERIAL

FOUNDATION (MAY NOT BE REQUIRED)

NOTE: 1. SEE SPECIFICATIONS FOR PIPE INSTALLATION REQUIREMENTS 2. CLASS "A" BEDDING REQUIRED FOR SDR-35 PVC PIPE

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE DRAWING NO.

SDR-35 PVC BEDDING DETAIL

A

H

W

S

W

Y

C A TE R

&

S E WE GE A R

T I R HO UT A

S02

10’-0" MIN.

2’-0" MIN.

TYPICAL

TYPICAL

VARI ES

TOP OF BANK

SLOPE VARIES

DEPTH

1’-0" (TYP.) STONE RIPRAP

A

1’-0"

1’-0"

CLASS "B" CONCRETE ENCASEMENT

MIN.

A

UNDISTURBED EARTH

C L

MIN.

ELEVATION * INSTALL RIP-RAP APPROXIMATELY 5’ UPSTREAM AND 5’ DOWNSTREAM FROM CENTERLINE OF PIPE ALONG CREEKBED

CLASS "B" CONCRETE

L

H

(ft.) (c.y.)

CONCRETE ENCASEMENT

(ft.)

VOL. CONC. (c.y./ft.)

H

8

2.25 2.00 2.06

0.30

1.81

0.13

10

2.50 2.00 2.27

0.36

2.00

0.15

12

2.75 2.00 2.50

0.47

2.14

0.18

15

3.00 2.00 2.83

0.50

2.50

0.21

H

H

6" ESVCP,DI P,PVC

Bd

(ft.) (ft.)

MI N.

D (in.)

6"

CONCRETE COLLAR

DIMENSIONS

MI N.

CONCRETE QUANTITIES

Bd

SECTION B-B

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE DRAWING NO.

CREEK CROSSING DETAIL

A

H

W

S

W

Y

C A TE R

&

S E WE GE A R

T I R HO UT A

S03

CASING PIPE 3 MIN.

3’ MIN.

3’ MIN.

VARIES PLUG ENDS OF PIPE WITH 8" THICK BRICK BULKHEAD CARRIER PIPE

PUSH-ON JOINT

CASING SPACERS

TYPICAL HIGHWAY CROSSING NOTE: CASING PIPE SHALL HAVE A PROTECTIVE COATING, CONSISTING OF A COAL-TAR PRIMER COAT AND AN APPLICATION OF HOT COAL - TAR ENAMEL" (+1/32") THICK.

CARRIER PIPE

CASING PIPE

CASING PIPE FOR

8" WIDE EPOXY COATED

HIGHWAY CROSSINGS

STEEL CASING CHOCKS,

INSIDE DIA. NOMINAL DIA. THICKNESS IN INCHES 8 10

IN INCHES 16 18

MODEL 4810 BY POWER

IN INCHES

SEAL OR EQUAL

0.250

(2 - PER JOINT)

0.250

12

20

0.313

14

24

0.344

16

26

0.375

20

30

0.438

24

36

0.500

30

42

0.500

36

48

0.500

CARRIER PIPE INVERT AS NOTED ON PLANS

TYPICAL ENCASEMENT SECTION FOR JACK & BORE INSTALLATION NOTE: CASING TO BE SEALED AROUND THE CARRIER PIPE WITH 8" BRICK. BULKHEAD AT EACH END SHALL BE CONSTRUCTED USING CEMENT MORTAR.

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

A

SEWER LINE JACK & BORE W

S

W

Y

C A TE R

&

DRAWING NO.

T I R HO UT S E WE GE A A R

INSTALLATION DETAIL

S04

MACHINED SURFACE 4" LETTERS (RECESSED FLUSH)

1 1/2"

(2) CLOSED PICKHOLES

(4) 1" DIA

BOTTOM VIEW OF COVER

HOLES ON 29 1/4" DIA BOLT CIRCLE.

MACHINED SURFACE

2 1/4"

1 1/2" 23 1/2" DIA

7/16"

21 1/8" DIA

1"

PICKHOLE DETAIL COVER SECTION 2 15/16"

EST. WT. COVER: 130 LBS FRAME: 190 LBS UNIT: 320 LBS 25 3/16" DIA

1 1/2"

6"

23 3/4" DIA

MAT’L SPEC. COVER - GRAY IRON 6 3/4"

ASTM A48 CL35 FRAME - GRAY IRON ASTM A48 CL35

22" DIA

5/8"

LOAD RATING

HEAVY DUTY

24 1/2" DIA

25 7/8" DIA

3/4" MUD RING 32 1/4" DIA

DOMESTIC MADE ONLY NO IMPORTS

FRAME SECTION

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

A

STANDARD MANHOLE W

S

W

Y

C A TE R

&

DRAWING NO.

T I R HO UT S E WE GE A A R

FRAME & COVER DETAIL

S05

MACHINED SURFACE

4" LETTERS (RECESSED FLUSH)

(4) 1/2-13 X 2" HEX HD SS CAP SCREWS & WASHERS

EST. WT. COVER: 130 LBS FRAME: 187 LBS

SEWER

UNIT: 318 LBS 1 1/2"

(2) CLOSED MAT’L SPEC.

PICKHOLES

BOTTOM VIEW

(4) 1" X 1 1/2"

COVER - GRAY IRON

SLOTTED HOLES

MACHINED SURFACE

ASTM A48 CL35 FRAME - GRAY IRON

PLAN VIEW

ASTM A48 CL35 5/8" -11 X 2" S.S HE HEAD BOLT W/S.S WASHERS

23 1/2" DIA

LOAD RATING

1 3/8"

HEAVY DUTY DOMESTIC MADE ONLY NO IMPORTS

2 15/16"

COVER SECTION 1/8" THICK U.S. FOUNDRY MODEL # 362-CKBWT

NEOPRENE FLAT GASKET

VULCAN FOUNDRY MODEL # V-2480-1

25 3/16" DIA.

WT DETAIL

OR EQUAL

1 1/2" 23 3/4" DIA. 6 3/4"

6" 2 1/4"

3/4" 3/4" DIA

20 1/2" DIA. 1 3/8" 24 7/16" DIA.

1 1/4"

25 7/8" DIA. 1/2" 7/16" 32 1/4" DIA.

PICKHOLE DETAIL FRAME SECTION

BOLTHOLE DETAIL

1"

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

A

BOLT DOWN MANHOLE W

S

W

Y

C A TE R

&

DRAWING NO.

T I R HO UT S E WE GE A A R

FRAME & COVER DETAIL

S06

ALL MANHOLES LOCATED OUTSIDE * NOTE: OF PAVEMENT TO HAVE BOLT-DOWN CAST-IN FRAME AND COVER

CAST IRON MANHOLE

PAVEMENT OR SHOULDER BRICK FOR GRADE ADJUSTMENT. ONLY WHEN REQ’D (1’ MAX.) (HALF BOND HEADER)

1 /2"

ECCENTRIC CONE

1.95 1 /8"

GRADE

OUTSI DE

FRAME AND COVER

2

24"

5"

GASKET

5"

MANHOLE DIA.

5"

4’-0" I.D.

TYPICAL 48" DIA. RISER SECTION, 1’-0", 1’-6", 2’-0", 2’-6", 3’-0", 3’-6" & 4’-0" HEIGHTS

MANHOLE STEPS

1.63

FOR PAYMENT

JOINTS

DEPTH OF MANHOLE

ALL

.64

1.5

1.03

JOINT DETAIL NTS

48"x5" WALL ONE PIECE 3’-0" HEIGHTS.

A DEPTH OF 0.8 x H.

5"

D .S .

CONCRETE SHALL HAVE

H

BASE UNIT, 2’-0" AND

PIPE INV.

PROVIDE CLAMP AND RUBBER BOOT AT ALL INFLUENT/EFFLUENT OPENINGS

BOTTOM OF BASE

INVERT TO BE PRECAST OR SOLID CONCRETE 12" MIN. STONE OR GRAVEL BEDDING.

STEP DETAIL NTS

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE DRAWING NO.

MANHOLE STANDARD ASSEMBLY DETAIL

A

H

W

S

W

Y

C A TE R

T I R HO & UT S E WE GE A A R

S07

MANHOLE DIA. 4’-0" I.D.

TYPICAL PRECAST M.H.

MINIMUM 6’ X 6’ X 6" THICK SLAB FOOTING TO BE POURED IN PLACE WHERE MANHOLE IS TO BE CONSTRUCTED WITHIN FILL MATERIAL

MIN. 12" #57 STONE

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

A

MANHOLE STANDARD W

S

W

Y

C A TE R

&

DRAWING NO.

T I R HO UT S E WE GE A A R

ASSEMBLY IN FILL DIRT DETAIL

S08

NO. 5 BARS AT 6" O.C. " 4 2

TOP SLAB DETAIL

NO. 4 BAR

CAST IRON MANHOLE FRAME AND COVER

BRICK COURSES FOR ADJUSTING TO GRADE.

1/2" CEMENT PLASTER PAVEMENT

FINISHED

4’ -6" OR LESS

UNI T W /TOP SLAB (LESS FRAME & COVER) TO BE PAI D PER EACH

STANDARD

BASE SECTI ON

12

1 / 4"

GRADE

NOTE: MANHOLE STEPS AND INVERT CONCRETE/GROUTING REQUIRED PER HENRY CO. WATER & SEWERAGE AUTHORITY STANDARDS.

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

W

S

W

Y

C A TE R

&

DRAWING NO.

A

MANHOLE SHALLOW T I R HO UT S E WE GE A A R

ASSEMBLY DETAIL

S09

STEEL PIPE W/4 ROWS 3/8" DIA. HOLES AT 2" O.C. WATER-TIGHT

FLOOD LEVEL

MANHOLE COVER 1’ -0"

BRICK COURSES FOR ADJUSTING TO GRADE. PLASTER INSIDE EXPOSED SURFACES.

1’ -0"

(VARIES)

3’-6" MIN.

4’ -3"

GRADE

1’ -0"

FINISHED

"H"

ELEVATION 50 YR.

2500 PSI CONC. ENCASEMENT FOR SUPPORT, WIDTH 2’-0"

24" 5"

NO. 5 OPEN 5" 1’ -0"

LOOPED TIES DOWELED IN MH

5"

STEEL PIPE SCHEDULE 80 3" DIA. FOR "H" LESS THAN 6’-0" 4" DIA. FOR "H" LESS THAN 10’-0" 5" DIA. FOR "H" LESS THAN 15’-0" 6" DIA. FOR "H" LESS THAN 15’-0" PIPE TO BE ENAMELED WITH 2

9"

GROUT INTO MANHOLE

COATS OF BITUMINOUS ENAMEL. 2’-0" SQ. FOR PIPE 4" DIA. & SMALLEER 3’-0" SQ. FOR PIPE 5" DIA. & LARGER

NOTE: VENTED CONNECTION TO MANHOLE TO CONSIST OF STEEL PIPE AND CLASS "D" CONCRETE COMPLETE.

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

W

S10

S

Y

W

&

ASSEMBLY DETAIL

A

H

C A TE R

MANHOLE VENTED

DRAWING NO.

T I R HO UT S E WE GE A A R

*

NOTE: ALL MANHOLES LOCATED OUTSIDE OF PAVEMENT TO HAVE BOLT-DOWN CAST-IN FRAME AND COVER CAST IRON MANHOLE

PAVEMENT OR SHOULDER

FRAME AND COVER

BRICK FOR GRADE ADJUSTMENT. ONLY

GRADE

WHEN REQ’D (1’ MAX.) (HALF BOND HEADER)

ECCENTRIC CONE 24"

TEE BRANCH-SIZE SMALLER THAN SEWER 8" MAIN

GASKET OF MANHOLE

#4 DOWEL AT 12" O.C. GROUTED INTO PRECAST

5"

MANHOLE DIA.

5"

SECTION AND EXTENDING INTO DROP CONNECTION

8" CONC. OUTSIDE

4’-0" I.D.

BRICK MANHOLE

OF PIPE BELL

STEPS

DEPTH

JOINTS

CONTRACTOR TO FURNISH

FOR PAYMENT

ALL

5"

1-90 OR CONCRETE SHALL HAVE

2-45

A DEPTH OF 0.8 x H.

5"

D .S

.

BENDS

PIPE INV. VARIABLE-MATCH CROWN W/MAIN SEWER BOTTOM OF BASE

INVERT TO BE PRECAST OR SOLID CONCRETE 12" MIN. STONE OR GRAVEL BEDDING.

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

A

MANHOLE DROP W

S

W

Y

C A TE R

&

DRAWING NO.

T I R HO UT S E WE GE A A R

ASSEMBLY DETAIL

S11

ALL MANHOLES LOCATED OUTSIDE * NOTE: OF PAVEMENT TO HAVE BOLT-DOWN CAST-IN FRAME AND COVER

BRICK FOR GRADE

CAST IRON MANHOLE

PAVEMENT OR SHOULDER

FRAME AND COVER

ADJUSTMENT. ONLY WHEN REQ’D (1’ MAX.) (HALF-BOND HEADER)

GRADE

STANDARD ECCENTRIC CONE

24"

NOTE: ALL JOINTS AROUND EXISTING AND PROPOSED SEWERLINE SHALL BE PROPERLY GROUTED AND SEALED. MANHOLE DIA.

ONCE MANHOLE INSTALLATION IS COMPLETE, TOP HALF OF EXISTING

4’-0" I.D.

TYPICAL 48" DIA. RISER SECTION, 1’-0", 1’-6",

PIPE SHALL BE CUT OUT USING A

2’-0", 2’-6", 3’-0",

CIRCULAR SAW.

3’-6" & 4’-0" HEIGHTS (RISER TO BE SET IN SHAPE BOTTOM OF RISER TO ALLOW

CONCRETE BASE)

FOR SEWER PIPES

A R

I E S

PROPOSED SEWERLINE

5"

V

EXISTING SEWERLINE

BASE TO BE SOLID CONCRETE POURED UP TO MID-POINT OF PIPE & SLOPED TO CENTER AT 1:4

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 12/02/10 SCALE: NONE

H

W

S

W

Y

C A TE R

&

DRAWING NO.

A

DOGHOUSE MANHOLE T I R HO UT S E WE GE A A R

ASSEMBLY DETAIL

S12

NOTES: CONCRETE USED FOR INVERTS MUST NOT EXCEED 3 PARTS SAND TO 1 PART PORTLAND CEMENT. ( MORTAR IS NOT ALLOWED ) USE SMOOTH RED COMMON BRICK ONLY. SMOOTHEST SIDE OUT.

MINIMUM OF 2 INCH CONCRETE WATER CAP. ( MUST HAVE SLOPE )

DRY MIXTURE OF SAND AND CONCRETE CAN BE USED WHERE

D .S .

INVERT = RADIUS OF PIPE

TABLE BUILT WITH LOOSE

FILL IS LESS THAN 1/2 BRICK.

BRICK STACKED CLOSELY

( 3:1 RATIO )

TOGETHER.

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

A

MANHOLE BRICK ROLL-LOCK W

S

W

Y

C A TE R

&

DRAWING NO.

T I R HO UT S E WE GE A A R

INVERT ASSEMBLY DETAIL

S13

NOTE: PLUMBING CONTRACTOR FOR BUILDER TO TIE ON AT THIS LOCATION WITH CLEAN-OUT UTILIZING STANDARDPVC FITTINGS OR "DONUT" CONNECTION

NOTE:

*

SERVICE LINES SHALL BE STUBBED OUT TO 22ft BOC AND BE NO MORE THAN 10ft DEEP. A WATERTIGHT CAP OR PLUG MUST BE USED

R/W

AT END OF LINE.

R/W

SEWER MAIN

GLUE-IN OR PUSH-IN

TEE

2" P.V.C. RISER PIPE TO EXTEND

PERM. CAP

FITTING

5 FT ABOVE FINISH GRADE FOR LOCATING SERVICE LINE

W ARRANT

6" SERVICE

W ARRANT

EXTRA DEPTH

CONDI TI ONS

10’MAX 45 ELBOW

EXTRA DEPTH

5

(TYP.) CONDI TI ONS

UNLESS SI TE

10’ MAX

P L

UNLESS SI TE

P L

PLAN

4" MINIMUM #57 STONE

LINE

4" MINIMUM #57 STONE

*

NOTE: SERVICE LINES HAVING LESS THAN 4 FT.

PROFILE

COVER SHALL BE DUCTILE IRON.

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE DRAWING NO.

SEWER SERVICE LINE LATERAL

A

H

W

S

W

Y

C A TE R

&

S E WE GE A R

T I R HO UT A

S14

2" P.V.C. RISER PIPE TO EXTEND 5 FT ABOVE FINISH GRADE FOR

R/W W ARRANT

EXTRA DEPTH

(TYP.) CONDI TI ONS

10’ MAX

UNLESS SI TE

5

R/W

LOCATING SERVICE LINE

6" 45 MJ X MJ ELBOW 6" D.I. SERVICE LINE

P L 6" DI 45 BEND MJ X PLAIN END 4" MINIMUM #57 STONE

6" WATERTIGHT CAP OR PLUG MUM NI 4" MI 57 STONE #

6" 45 MJ X PE ELBOW

6" D.I. SERVICE LINE

ONE CONTINUOUS PIECE OF DIP. LENGTH WILL VARY

P L

6" 45 MJ X MJ ELBOW

6" D.I. SERVICE LINE 6" D.I. SERVICE LINE NOTE: LINES SHALL BE DUCTILE IRON PIPE *SERVICE STUBBED OUT TO 22ft BOC AND BE NO MORE

D.I. TEE

D.I. TEE D.I. MAIN

THAN 10ft DEEP. A WATERTIGHT CAP OR PLUG MUST BE USED AT END OF LINE.

PROFILE A

PROFILE B

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 12/02/10 SCALE: NONE

H

A

SERVICE LINE LATERAL DETAIL W

S

W

Y

C A TE R

&

DRAWING NO.

T I R HO UT S E WE GE A A R

FOR SEWER LINES 18 VF & DEEPER

S15

Brock Biles: 678-583-3847 Cell: 678-794-5282 Nextel: 154*21*32327 IF NO ANSWER CONTACT

R/W

SEWER TAP INSPECTIONS

CLEAN OUT BOX (CARSON IND. MODEL 910 OR EQUAL) WITH SEWER/HCWSA EMBOSSED ON LID.

P L

4" PVC CLEAN OUT

Engineering Dept. 770-914-3688

45 ELBOW

4" PVC SERVICE LINE

45 ELBOW

4" WYE 6" X 4" REDUCER (GLUE-ON OR INSERT)

6" SERVICE LINE

NOTE: PLUMBING CONTRACTOR FOR BUILDER TO TIE ON AT THIS LOCATION WITH CLEAN-OUT UTILIZING STANDARD PVC FITTINGS OR "DONUT" CONNECTION FOR DIP.

SEWER MAIN

SEWER TAP INSPECTION REQUIRED BY HCWSA.

PROFILE

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

W

S

W

Y

C A TE R

&

DRAWING NO.

A

SEWER SERVICE LINE T I R HO UT S E WE GE A A R

CLEANOUT CONNECTION DETAIL

S16

NOTE:

*

SERVICE LINES SHALL BE STUBBED OUT TO 22ft BOC AND BE NO MORE THAN 10ft DEEP. A WATERTIGHT CAP OR PLUG MUST BE USED

R/W

AT END OF LINE.

10"X18.5" CLEANOUT BOX WITH LID

P L

MFR STD SEWER

CONTRACTOR

AND SPIGOT "O" RING GASKET JOINTS OR APPROVED MFGRS STD SOLVENT

45 ELBOW

SI TE

W ARRANT

6" PVC SEWER PIPE WITH BELL 1/8th BEND

EXTRA DEPTH

DEVELOPER /

10’MAX

STUB BY

UNLESS

4" GRAVEL IN BOX 10’-0

CONDI TI ONS

CLEANOUT PLUG

TO STRUCTURE

6"X6"X6" 45 WYE

4" MINIMUM #57 STONE

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE DRAWING NO.

SEWER SERVICE LINE CLEANOUT DETAIL

A

H

W

S

W

Y

C A TE R

T I R HO & UT S E WE GE A A R

S17

NOTES FOR 2" AIR / RELEASE VALVE (ARV): 1. VALVES SHALL BE EQUIPPED WITH AN ELONGATED BODY, A 2" N.P.T. INLET CONNECTION,AND A 1/2" N.P.T. OUTLET CONNECTION AND SHALL BE PROVIDED WITH A 2" INLET SHUT-OFF VALVE, 1" BLOW-OFF VALVE, AND A 1/2 " BACK-FLUSH VALVE WITH QUICK- DISCONNECT COUPLING AND FLUSHING HOSE WITH QUICK-DISCONNECT CONNECTS.

2. MANUFACTURERS INCLUDE H-TEC OR HCWSA APPROVED EQUAL.

NOTES FOR 2" COMBINATION AIR VALVE (CAV): 1. VALVE REQUIRES A 1" N.P.T. OUTLET CONNECTION.

2. VALVES SHALL BE EQUIPPED WITH APPURTENANCES SPECIFIED IN NOTE 1 ABOVE.

3. MANUFACTURERS INCLUDE H-TEC OR HCWSA APPROVED EQUAL.

30" CLEAR OPENING FRAME AND VENTED COVER NEENAH R-6078 OR EQUAL (575 lbs.)

SET COVER FLUSH WITH ROADWAY WHERE IT OCCURS.

6" (TYP.)

1" MIN. (GROUT)

4’ (TYP.) MANHOLE STEPS (FOR DEPTHS GREATER THAN 4.0’)

TAPPING TEE OR SLEEVE

12" (TYP.)

1’- 6" (MIN.) #57 CRUSHED STONE SPRING LINE

COMPACT BACK FILL

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 12/02/10 SCALE: NONE

H

A

SEWER FORCE MAIN W

S

W

Y

C A TE R

&

DRAWING NO.

T I R HO UT S E WE GE A A R

AIR-RELEASE VALVE DETAIL

S18

DUMPSTER AREA DRAIN W/WIRE MESH

REQ.’D CLEAN-OUT

SLOPE AT

" PER FT.

OIL-WATER SEPERATOR (APPROVED BY HCWSA)

SANITARY SEWER SERVICE LATERAL

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

W

S

W

Y

C A TE R

&

DRAWING NO.

A

SEWER DUMPSTER PAD W/O T I R HO UT S E WE GE A A R

CANOPY CONNECTION DETAIL

S19

CANOPY (APPROVED BY HENRY CO. BLDG. DEPT.)

AREA DRAIN W/WIRE MESH

DUMPSTER

REQ.’D CLEAN-OUT

SLOPE AT

" PER FT.

OIL-WATER SEPERATOR (APPROVED BY HCWSA)

SANITARY SEWER SERVICE LATERAL

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

A

SEWER DUMPSTER PAD WITH W

S

W

Y

C A TE R

&

DRAWING NO.

T I R HO UT S E WE GE A A R

CANOPY CONNECTION DETAIL

S20

FLOOR OF DUMPSTER PAD

4-SIDED DIKE 8"X8" MIN. CONCRETE FOR WATER DIVERSION WIRE MESH

TOP VIEW SECTION A-A

CANOPY (MUST BE APPROVED BY HENRY CO. BLDG. DEPT.)

A

A

FLOOR OF DUMPSTER PAD

DUMPSTER

4-SIDED DIKE 8"X8" MIN. CONCRETE FOR WATER

REQ.’D CLEAN-OUT WIRE MESH

DIVERSION

8" MIN.

TERAL CE LA SERVI SEWER Y R A T SANI

FRONT VIEW NOTE: SEWER SERVICE CONNECTION MUST BE INSPECTED AND APPROVED BY HCWSA.

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

A

SS DUMPSTER PAD W/ CANOPY W

S

W

Y

C A TE R

&

DRAWING NO.

T I R HO UT S E WE GE A A R

SECTION CONNECTION DETAIL S21

STANDARD GREASE INTERCEPTOR DESIGN

2

2

4

4

5

5

2’

2’

3

3

FLOW FLOW WATER LEVEL

6

1’

1’

6"

1. PRECAST TANK, 1500 GALLONS.

2. MANHOLE TOP AND RING, ONE OVER EACH SECTION.

3. PIPE AND FITTINGS OF APPROVED MATERIALS.

4. BRICK UP TO GRADE. INSTALL MANHOLE STEPS 2’.0" ON CENTER IF THE HEIGHT OF THE BRICK WORK IS GREATER THAN 4’.0".

5. PROVIDE TOP SECTION WITH 24" DIAMETER OPENING AT EACH END OF TANK.

6. INSTALL CONCRETE BAFFLE IN TANK.

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

W

S

W

Y

C A TE R

&

DRAWING NO.

A

1,500 GALLON GREASE T I R HO UT S E WE GE A A R

INTERCEPTOR DETAIL

S22

4"

4"

4"

4"

4"

4"

4"

AUTOMATIC CAR WASHER

EQUIPMENT AND/OR MECHANICAL ROOM

GRATE DRAIN

4" C/O

4" C/O

4" 4"

6"

6"

6"

6"

4"

4" C/O

T N E V

4" C/O

" 3

4"

4" C/O

T O

S 6" A N .

G A L

L

1 5 0 0 4"

4"

4"

4"

1 5 0 0

1 5 0 0

G A

G A L

G A L 1 5 0 0

5 1 4"

4"

4" C/O

0

1 5 0

0

0

G A

G A L

L

S E W E R

4" C/O 4"

4"

6"

6"

6"

4"

1 5

0 0

G A

L

6"

4"

4" C/O

5 0 0

1 5 0 0

VE NT

G A L

2"

4" RECOVERY

3"

G A L

4"

4" C/O

4" C/O

6"

4"

TO N. SA R WE SE

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

W

S

W

Y

C A TE R

&

DRAWING NO.

A

CAR WASH PIPELINE T I R HO UT S E WE GE A A R

LAYOUT DETAIL

S23

SHARPEN FOR

2.0’

LIGHTNING ROD BIRD CAP

LEAVE 5’ SLACK CABLE FOR UTILITY CO. CONN. SET W.H. AT APPROX. 15’ ABOVE GROUND

NOTE: POWER CO. TO PROVIDE 120/240/480

3 n

SERVICE TO WEATHER HEAD

3- PHASE LIGHTNING ARRESTOR

24’ CLASS 5 PENTA 2 #8,1 #8(N),1"C

TREATED WOOD POLE 5’ IN EARTH

MOUNT METER BASE FURNISHED BY UTILITY CO.

60 A 2PSN FUSED SAFETY SWITCH IN NEMA 3R ENCLOSURE W/ FUSES. #6 CU BARE GROUND WIRE STAPLE TO POLE WITH COVER TO 8’-0

CONDUIT TO CP (24" MIN. COVER)

10’ X" COPPER CLAD GROUND ROD. DRIVE FULL DEPTH INTO EARTH

PUMP STATION "A" ELECTRICAL SERVICE POLE DETAIL

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

W

S24

S

Y

W

&

CONNECTION DETAIL

A

H

C A TE R

PUMP STATION ELECTRICAL

DRAWING NO.

T I R HO UT S E WE GE A A R

3 STRANDS BARBED WIRE

12"

x x x

x x x

x x x

x x x

x x x

x x x

x x x

" 0 TRUSS RODS 6’ -0

AT CORNERS

GATE FIN. GRADE

3’ -0

TENSION WIRE CONC.

CORNER POST

2" ABOVE GRADE

GATE POST

9"

LINE POST

12" (MIN)

ELEVATION " 0 TRUSS RODS AT CORNERS

SECTION

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE DRAWING NO.

SECURITY FENCE INSTALLATION & DETAIL

A

H

W

S

W

Y

C A TE R

&

S E WE GE A R

T I R HO UT A

S25

6"-8" DIA.TREATED PINE POST 6"-8" DIA. TREATED PINE POST

SINGLE STRAND, BARBED WIRE

3"-4" DIA. TREATED PINE (notched into pull post)

3"-4" DIA. TREATED PINE (notched into pull post)

SINGLE STRAND, BARBED WIRE 10" DIA. UTILITY POST

8" BRACE PIN

"SURE LATCH" GATE LATCH

8" BRACE PIN

16’X5’,2"DIA. TUBULAR STEEL GATE (HOY DIP GALVANIZED)

6’

ANCHOR SCREWS

6’

3"

3"

54"

54"

3’

3’ 3.6’

3.6’

GATE WHEEL

EX.GROUND

10"

CLASS "B" CONCRETE

12"

12"

10"

USE 1.25"GALVANIZED STAPLES TO ATTACH WOVEN WIRE TO POSTS RED BRAND47" WOVEN WIRE FIELD FENCE

RED BRAND47" WOVEN WIRE FIELD FENCE

ACCESS GATE AND FENCE DETAIL

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE

H

A

SEWER EASEMENT ACCESS GATE & W

S

W

Y

C A TE R

&

DRAWING NO.

T I R HO UT S E WE GE A A R

FENCE INSTALLATION DETAIL

S26

50’ R/W - RESIDENTIAL UTILITY PLACEMENT

2" PVC RISER PIPE TO EXTEND

2" PVC RISER PIPE TO EXTEND

5 FT. ABOVE FINISH GRADE FOR

5 FT. ABOVE FINISH GRADE FOR

LOCATING SERVICE LINE.

LOCATING SERVICE LINE

25’

5’

6’

4’

2’

25’

2’

11’

11’

2’

2’

4’

5’

6’

UTILITY EASEMENT

UTILITY EASEMENT

1 2:

8’ GAS

10’ TEL

4’ 1’

3’

2’

2’

3’

3’

1’

VARI ES

1 2:

CATV

2’

SIDEWALK

SIDEWALK

CATV 8’ WATER 10’ TEL 12’ POWER

12’ POWER SEWER STUB OUT 35’

SEWER STUB OUT 35’

1. NO TREES OR FENCES ALLOWED WITHIN THE ROAD R/W OR UTILITY EASEMENT EXCEPT

7. UTILITY EASEMENT SHALL BE SHOWN & RECORDED WITH THE FINAL PLAT.

WHERE REQUIRED BY CITY, COUNTY, OR OTHER GOVERNMENT ORDINANCE. 8. WATER METER BOXES SHALL BE LOCATED AT 6’ BACK OF R/W. 2. ALL TREES SHALL BE CLEARED & SHOULDERS GRADED WITHIN 6" OF FINAL GRADE (INCLUDING SEWER SERVICES SHALL BE STUBBED OUT AT 10’ BACK OF R/W. UTILITY EASEMENT) PRIOR TO THE INSTALLATION OF ANY UTILITIES. 9. WATER LATERALS SHALL BE MARKED WITH A BLUE "W" ON CURB AS SOON AS 3. UTILITY PLACEMENT SHALL REMAIN CONSISTENT FROM BACK OF CURB THROUGHOUT THE PROJECT REGARDLESS OF ANY INCONSISTENCIES IN ROAD CONSTRUCTION. EXAMPLES: STORM SEWERS, CULVERTS, CULDESACS, ETC... (EXCEPT CATV).

POSSIBLE AFTER CURB HAS BEEN INSTALLED. SEWER LATERALS SHALL BE MARKED WITH GREEN "X" ON CURB. 10. DEPTH REQUIREMENTS INDICATE MINIMUM DEPTH AT TIME OF INSTALLATION BELOW CURB LINE.

4. AFTER VERIFICATION OF FINAL GRADE, UTILITIES SHOULD BE INSTALLED AS FOLLOWS:

11. THIS STANDARD MAY BE COMBINED WITH JOINT USE STANDARD.

WATER, ELECTRIC, GAS, TELEPHONE, & CATV. 12. CATV PEDESTAL, TELEPHONE PEDESTALS, TRANSFORMERS, AND WATER METERS SHALL 5. TOTAL CLEARED AND GRADED WIDTH TO BE 60’ MINIMUM.

BE PLACED IN THE 5’ UTILITY EASEMENT.

6. PROPERTY CORNER REFERENCE SHALL BE PLACED ON CURB & GUTTER AND ON 10’ OFFSET

13. UTILITIES SHALL BE LOCATED WITHIN PLUS OR MINUS 6" OF PLAN LOCATION.

STAKE.

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: 1" = 10’

H

W

S

W

Y

C A TE R

&

DRAWING NO.

A

RESIDENTIAL UTILITY PLACEMENT DETAIL T I R HO UT S E WE GE A A R

FOR A ROAD WITH A 50’ RIGHT-OF-WAY

S27

12’ 3’

3’

3’ SHOULDERS

DRAINAGE DITCH

SLOPE " / FT

3 8’ TYP.

1

4’ TYP.

6" GRADED AGGREGATE BASE COURSE (GABC) ON COMPACTED SUBGRADE

HENRY COUNTY WATER & SEWERAGE AUTHORITY

COUN T NRY Y HE

REVISED: 11/23/10 SCALE: NONE DRAWING NO.

ACCESS ROAD CROSS SECTION DETAIL

A

H

W

S

W

Y

C A TE R

&

S E WE GE A R

T I R HO UT A

S28