SECTION LIGHTING FIXTURES

SECTION 265010 LIGHTING FIXTURES PART 1 - GENERAL 1.01 DESCRIPTION A. Description of System 1. Light fixtures furnished under this Division shall be ...
Author: Earl Brown
10 downloads 2 Views 16MB Size
SECTION 265010 LIGHTING FIXTURES PART 1 - GENERAL 1.01

DESCRIPTION A. Description of System 1. Light fixtures furnished under this Division shall be furnished complete with lamps and all necessary trim and mounting hardware, and installed as shown on the drawings. 2. Light fixtures shall be neatly and firmly mounted, using standard supports for outlets and fixtures. See special mounting requirements as detailed on the drawings. 3. Lamps shall be included in the system guarantee for a period of ninety (90) days after final acceptance of the building.

1.02

CODES A. The WORK of this Section shall comply with the current editions of the following codes 1. National Electrical Code (NEC), NFPA 70 2. Florida Building Code (FBC)

1.03

SPECIFICATIONS AND STANDARDS A. Except as otherwise indicated, the current editions of the following apply to the WORK of this Section 1. UL Underwriters Laboratories 2. CBM Certified Ballast Manufacturer's Association

1.04

SUBMITTALS A. Shop Drawings 1. Shop Drawings and manufacturers data shall be submitted for the following items a. Luminaire data shall show full-size cross sections. Indicate finished dimensions, metal thickness, U.L. Label, finish, lens/louver thickness and materials. b. Show mounting details, including hung ceiling construction. c. Indicate type of ballast and manufacturers and ballast quantity and location. Include information as to power factor, input watts and ballast factor. d. Indicate lamps to be utilized and quantity. e. Include a complete listing of all luminaries on a single sheet. This listing shall contain the luminaire type, manufacturer’s catalog number, applied voltage, lamps, ballast type and luminaire quantities. f. The Engineer reserves the right to require submittal of a complete sample fixture for any fixture type. g. For exterior post/pole mounted light fixtures, clearly indicate hand hole and lightning protection ground lug mounted to post/pole at hand hole inside post/pole. h. Signed and sealed shop drawings and calculations shall be submitted for all exterior pole mounted fixtures. The seal must be of a registered professional engineer certifying that the foundation and pole/fixture assembly meets or exceeds the wind load criteria of the Florida Building Code 2008. The foundation details shown on the

LIGHTING FIXTURES 60060986 - March 24, 2010

265010-1

i.

plans are for bidding purposes only; the contractor shall provide the foundation and pole assembly necessary for compliance as submitted at no additional cost to owner. Product data shall be submitted showing manufacturer’s written recommendations for storage and protection, and installation instructions.

PART 2 – PRODUCTS 2.01

2.02

APPROVED MANUFACTURERS A. Luminaires 1. Acceptable manufacturers are listed in the lighting fixture schedule shown on the Drawings. 2. The designations indicated on the lighting fixture schedule are a design series reference (not necessarily a complete catalog number) and do not necessarily represent the number, size, voltage, wattage, type of lamp, ballast, finish trim, ceiling type, mounting hardware of special requirements as specified hereinafter on as required by the particular installation(s) and code. Contractor shall verify these requirements and order fixtures as required to give proper installation per the contract documents and per codes. B. Ballasts 1. It is preferred that all ballasts shall be of the same manufacturer. Every effort shall be made to eliminate ballasts from multiple manufacturers. Ballasts within luminaires of a given type must however be of the same manufacturer. Multiple manufacturers will not be permitted. 2. Approved Manufacturers: a) Motorola b) Advance Transformer Co. c) Magnetek d) General Electric C. Lamps 1. All lamps shall be of the same manufacturer. Multiple manufacturers are not permitted. 2. Approved Manufacturers: a) General Electric b) Philips c) Osram Sylvania MATERIALS A. All lighting fixtures mounted outdoors subject to dampness and insects shall have gasketing material between lens door and frame to completely seal interior of fixture. Knockouts and holes in fixtures housing shall be closed and sealed. All fixtures shall be complete with lamps, shielding brackets, concrete bases, anchor bolts, and all necessary fittings and accessories for a complete installation. B. Plastic Lenses and diffusers: 1. Virgin acrylic unless otherwise noted. De-staticize after cleaning. Install and leave with no finger prints or dirt marks on the lens or diffuser. Lenses shall be provided on all recessed metal halide luminaires. 2. Minimum unpenetrated thickness for Parabolic or conical element diffuser: 0.085 inch. 3. Minimum nominal thickness: 0.125 inch. C. Parabolic Luminaire Care: Parabolic luminaires to be installed with mylar cover over louvers. Cover shall be U.L. listed for temporary lighting. Upon completion of work, remove mylar cover with white gloves and blow clean reflectors. D. Finish: Porcelain or baked enamel finish matte white on interiors with minimum

LIGHTING FIXTURES 60060986 - March 24, 2010

265010-2

E.

F.

G.

H.

I. J.

tested reflectance of 90 percent matte white finish or as specified in visible exterior. Thoroughly clean base metal and bonderize after fabrication. Sockets: Incandescent lamp sockets - porcelain housings over copper screw shells, with medium base sockets rated at 660 watts and 250 volts. Insulating joint in pull chains. Fluorescent lampholder - white, heat-resistant plastic rated 660 watts and 600 volts. Fluorescent industrial sockets - heavy-duty, multisocket, metal-clad, spring-loaded. Provide heavy-duty sockets for H.I.D. luminaires where mounted less than 8'-0" AFF. Luminaire Wiring: Minimum individual luminaire wiring - number 18 gauge with insulation at rated operating temperature of 105 degrees Centigrade or higher. Terminate wiring for recessed luminaires, except fluorescent units, in an external splice box. Ballasts 1. Ballasts for F32T8 lamps shall be: a) High frequency solid state electronic. b) Instant start, parallel operation. c) 50 F minimum starting temperature unless otherwise noted d) Minimum 0.87 ballast factor e) aximum total harmonic distortion (THD) 10% f) High power factor, minimum 95 % g) Sound rated A 2. High-power factor (over 90 percent). Certified Ballast Manufacturers' Certification, ballast case temperature not to exceed 90 degrees Centigrade during normal operation in 30 degrees Centigrade ambient temperature. Ballast voltage: 120 or 277 volts, as required by circuiting. Ballast shall be provided with the best sound rating available. 3. Built-in self-resetting thermal actuated device will remove ballast from line when excessive ballast temperature is reached. U.L. Class P, CBM certified 100% output. 4. The conductors between ballasts and lampholders shall have an approved insulation for 1,000 volts. This includes conductors to and from remote ballasts. 5. High-intensity discharge ballasts shall be constant wattage autotransformer type with built-in thermal protection, minimum power factor of 80%. 12" min. leads. 6. Provide ballasts with voltage characteristics to match that of all related circuitry indicated on the Drawings. No extra compensation will be allowed for failure to properly coordinate ballast voltage with circuitry. 7. Ballasts for control of lamps in one housing or fixture unit shall not control lamps of an adjoining unit, except as otherwise noted. 8. Guarantee ballast for one full year and one year prorated as per standard manufacturer's warranty against defects for a period of 2 years. Guarantee to include replacing defective ballast with new ballast. 9. Provide dimming ballasts as required for fixtures controlled by individual dimming or dimming systems. Lamps 1. Provide a complete set of new lamps in each fixture. 2. Unless noted otherwise lamps must conform to the following: a) Fluorescent: T-8, 35k color. b) Incandescent: "A" lamps to be inside frosted rated at 130 volts. c) Compact Fluorescent: triple Twin tube, 4-pin d) HID: Metal Halide, clear, universal base Luminaires installed recessed in a metal pan ceiling shall have a flange type trim to overlap abutment of adjacent pans. Where utilized as raceways, luminaires shall be suitable for use as raceways.

LIGHTING FIXTURES 60060986 - March 24, 2010

265010-3

K.

L.

M.

N.

Provide feed through splice boxes where necessary. Where ceiling mounted fixtures are called for in the Light Fixture Schedule and on the drawings, this contractor shall provide fixture trims and supports as required to match type of ceiling system which will be furnished. No ceiling fixtures shall be ordered until the Ceiling System Installer has given written approval of the method and location of fixture hanging and fixture type. Fixtures supported by suspended ceiling systems shall be securely fastened to the ceiling framing member by mechanical means, such as bolts, screws, or rivets. Clips identified for use with the type of ceiling frame member(s) and fixture(s) shall also be permitted. Where fixtures are supported by the suspended ceiling system; the ceiling system shall have a minimum (2) opposite corners tied to structure at each fixture location; this contractor shall be responsible for doing this work or for having the ceiling contractor perform it. All exterior post/pole mounted light fixtures shall have a hand hole at the base, lightning protection in hand hole and ground conductor connected to ground rod at base. Hand hole shall provide easy access to light fixture fusing and lightning protection ground lug. Lightning protection ground lug shall be provided inside post/pole, electrically in contact with pole, for connection to ground rod. Provide and install ground wire from ground lug to ground rod, concealing ground wire through post/pole base. Anchor bolts to be galvanized. All interior and exterior light fixtures shall not have any labels exposed to normal viewing angles. This includes manufacturer labels and U.L. labels. All labels shall be concealed within the body of the fixture and/or luminaire. No manufacturers name or logo shall appear on the exterior of any light fixtures unless approved in writing by engineer. All light fixtures shall adhere to U.L. Test Standard #1571 and Section #410-65C of the National Electric Code. All manufacturers shall provide the required thermal protection as required.

PART 3 – EXECUTION 3.01

INSTALLATION A. Install luminaires in mechanical and unfinished areas after ductwork and piping installation. Adjust fixture locations to provide the best lighting for equipment access and service locations. Locate fixtures 8 feet 6 inches above floor, or at suitable locations within space on walls but not lower than 7'-0" AFF. B. The Contractor shall protect luminaires from damage during installation of same and up to time of final acceptance. Any broken luminaires, glassware, plastics, lamps, etc., must be replaced by the Contractor with new parts, without any additional expense to the Owner. C. The contractor shall verify prior to ordering fixtures that each fixture scheduled has correct type trim and support arrangement for the proposed ceiling construction. D. Install all fixtures in accordance with manufacturer’s written instructions and the NEC. E. Pendant mounted units shall comply with the following: 1. Each stem shall have a brass or steel swivel or other self-aligning device of type approved by the Engineer. The entire luminaire mounting (hickey, aligner, swivel, stem, etc.) shall be submitted to and approved by the Engineer before installation. 2. An insulated malleable iron bushing shall be placed at luminaire end of stem through which wire passes. 3. A pendant support using an approved sliding clevis bracket which firmly grips an indentation in rigid sides of the wiring channel will be acceptable. 4. Connections between outlet boxes and luminaires shall be by means of

LIGHTING FIXTURES 60060986 - March 24, 2010

265010-4

F.

G.

H. I. J.

3.02

3.03

approved flexible raceways. The application of raceways directly between luminaires is unacceptable. Where luminaires are mounted upon surface-mounted outlet boxes in surface mounted conduit runs, this Contractor shall furnish and install a luminaire canopy sufficiently deep to permit exposed conduits to pass through. Canopy shall have proper openings cut by luminaire manufacturer through which conduits may pass. Submit sample of canopy for approval before installation. Ceiling surface mounted fluorescent fixtures installed in exposed ceiling areas are to be suspended from ceiling structure with all-thread rods and 1-1/2”x1-1/2” Kindorf channels, full length of fixture/row. Mount outlet box at structure with flexible connection to fixture. Ducseal shall be installed to seal all conduits entering exterior light fixtures from underground. Install exit light as indicated on the drawings but not higher than 10'0" AFF. Size and color of lettering shall comply with local codes. Outdoor lighting shall be aimed in periods of darkness in front of the owner/engineer.

COORDINATION WITH AMBIENT CONDITIONS A. The Contractor is responsible for coordinating the characteristics and the U.L. labeling of the luminaires and their components with the ambient conditions which will exist when the luminaires are installed. No extra compensation will be permitted for failure to coordinate the luminaires with their ambient conditions. These areas of coordination include but are not limited to the following: 1. Wet location labels 2. Damp location labels 3. Low temperature ballasts 4. Dimming ballasts 5. Very low heat rise ballasts 6. Explosion proof 7. Plenums and air handling spaces 8. Fire rated ceilings 9. Low density ceilings 10. Insulated ceilings CLEAN-UP A. Luminaires: 1. Clean free from dust and dirt. Wash lens and glassware using cleaner such as “Windex” and dry with absorbent paper. Clean plastic per manufacturer’s recommendations; do not wipe. Lenses which are kept in original containers until immediately prior to final inspection may not require cleaning. Clean “Alzak” aluminum surfaces (reflectors, fixture cones and the like) per mfr’s recommendations being careful to remove finger prints and smudges. 2. It is the contractor’s responsibility to remove any U.L. labels or manufacturers labels from areas of fixture exposed to view and relocate label to non-obtrusive area on fixture.

END OF SECTION

LIGHTING FIXTURES 60060986 - March 24, 2010

265010-5

SECTION 266100 LIGHTNING PROTECTION SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. Description of Systems: 1. A Lightning Protection System shall be placed on the structures by experienced installers in compliance with provisions of Code for Lightning Protection Systems as adopted by the National Fire Protection Association and Underwriters' Laboratories. Intent of the lightning protection systems shall be to protect the structures against damage by lightning. All equipment to that result shall be included whether or not specifically called for herein. Installers shall be Underwriters Laboratories certified as Master Label installers or of equal qualifications as approved by Engineer. 2. Provide lightning protection system for the telemetry antenna system as noted on the drawings. Provide complete bonding and grounding systems as shown on the drawings and as specified. All systems shall be in conformance to NFPA-780, UL-96, UL96-A and as shown on the contract drawings. 3. Materials shall comply in weight, size and composition with the requirements of Underwriters' Laboratories and the National Fire Protection Code relating to this type of installation, and shall be U.L. labeled. 4. All installations shall be performed to meet Underwriters Laboratories Master Label standards. 1.02

SUBMITTALS A. Shop Drawings and Product Data: 1. Shop Drawings: Shop drawings shall be submitted before work is started. Drawings shall include full layout of cabling and points, and connections. The drawing shall show the type, size and location of all equipment, grounds and cable routing. The drawing shall show all grounds and air terminals that are shown on the contract drawings. See additional requirements for shop drawings in section 16050. 2. Product Data: Product Data shall be submitted on all equipment to show compliance with this section of the specifications and shall include manufacturer's written recommendations for installation. Provide a sample of the air terminal to be used with the shop drawing submittal.

1.03

SYSTEM DESIGN A. The system shall be an effective, aesthetically acceptable streamer-delaying lightning protection system to the standards of Underwriters Laboratories UL 96 & UL96A. The purpose of the system shall be to reduce the likelihood of a direct strike to the protected structure by delaying the formation of streamers from that structure. Secondarily the system shall be designed in such a manner that it affords protection to the structure upon which it is installed in the event a direct lightning strike to the structure does occur. B. The system components shall not require mounting in a specific configuration or impose any other mounting limitations which may interfere with utility use of structure space or otherwise preclude or limit the intended use of the structure.

LIGHTNING PROTECTION SYSTEM 60060986 - March 24, 2010

266100-1

C.

D.

E.

F.

All components shall be attached to the structure in such a manner as to reduce the possibility of corrosion between dissimilar metals. If installed on a metallic or otherwise electrically conductive structure, the system shall be electrically bonded to the structure upon which it is installed through mounting clamps and brackets, with additional bonding to grounded objects and to the structure, as required or as indicated on the drawings. The system shall be composed of components that meet the requirements of Underwriters Laboratories UL 96. Aluminum and Stainless Steel components shall be employed on structures and portions of structures subject to corrosive elements, where the use of copper components could be rendered ineffective, due to the surrounding environment. No dissimilar metals shall be allowed to be in contact. Air Terminals shall be mounted on all outside corners of each structure, around the perimeter of each structure at intervals not to exceed twenty (20) feet, and on the interior of each structure in such a manner that no two Air Terminals are separated by a distance of more than fifty (50) feet. In the event this is not practical, such as on a large open tank, Air Terminal spacing around the perimeter shall be decreased to not more than fifteen (15) feet, with a total number around the perimeter not less than the total of the normally required perimeter Air Terminals, plus the additional number of Air Terminals if Air Terminals had been installed on the interior at intervals not greater than fifty (50) feet. Each Air Terminal shall be provided with two (2) contiguous paths to ground. On structures with handrails, exposed structural members, or other conductors, provide a bond to structural conductors from the lightning protection system. Handrails shall not be used as a main lightning protection conductor. Provide a continuous lightning protection conductor parallel with handrails and bond from it to each handrail section and a minimum of 10’ on center. In the case of a structure or a portion of the structure where the structure itself is electrically conductive, such as a light pole, tower, etc, that structure or portion of the structure itself may be employed as part of the lightning protection system, provided it meets the minimum requirements of UL 96 or UL 96A, and down conductors are specifically not required on such structures.

PART 2 - PRODUCTS AND INSTALLATION 2.01 AIR TERMINALS A. Air Terminals shall be of the streamer delaying type. Each air terminal shall have a minimum of five hundred dissipater electrode wires, none of which exceed ten thousands of an inch diameter. Electrode material shall be high quality 316 series stainless steel and shall have proper base support for surface on which they are attached, and shall be securely anchored to this surface. Terminals shall project a minimum of 18" above top of object to which attached. B. Streamer-delaying Air Terminals shall be manufactured by Lightning Master Corporation. 2.02

CONDUCTORS A. Roof conductors shall consist of rope lay tinned copper conductor complying with the weight and construction requirements for Class II lightning protection systems (115,000 CM). Conductors shall be coursed to interconnect with air terminals, and in general, provide a two-way minimum path to ground. The angle of any turn shall not exceed 90 degrees, and shall provide an approximately horizontal or downward course. Down conductors shall be copper, and shall be installed in PVC conduit and hidden within the structure. Approved bi-metal transitions from

LIGHTNING PROTECTION SYSTEM 60060986 - March 24, 2010

266100-2

B.

C.

aluminum conductors for bonding of aluminum roof structures (exhaust fans, etc.) to copper down conductors shall be provided. Only in the case where aluminum building flashing, aluminum handrails, aluminum catwalks is specified, will aluminum roof conductors be acceptable; otherwise provide copper system throughout. All down conductors shall be copper. Radius of bends shall not be less than 8 inches. Counterpoise loop ground conductors shall be tinned copper and be a minimum size equal to the main roof conductor size (115,000cm) or 2/0.

2.03

FASTENER A. Conductor fasteners shall be of the same material as the conductor, having ample strength to support conductor. Where fasteners are to be mounted in masonry or structural work, they shall be furnished to the Masonry or Structural Contractor so they may be installed during construction of the project. B. All fasteners shall be of a heavy-duty bolted type typically used for Class II lightning protection systems. Conductor to conductor connections shall be through heavy-duty pressure type bolted fasteners. Splice and bimetal connections shall be through four bolt pressure type heavy-duty connectors. Crimp fasteners shall not be used. C. Dissimilar metals shall not be allowed to be in contact. Aluminum fittings shall be mounted on aluminum where necessary, and bonded to the main system using bi-metal connectors. Lead coating shall not be acceptable as a bi-metal transition. D. All mechanical termination points and lugs shall have an anti-corrosive coating applied. In areas subject to chemical corrosion (odor control, degasifiers, chem. Rooms, etc.) apply Glyptal 1201 red enamel coating after termination is made. In other less corrosive areas apply Permatex battery protector sealer (SA-9) or Glyptal 1201 or equal. E. Lugs for copper cable shall be high copper alloy terminals or stainless steel equal to Burndy type QDA Qiklug. Lugs of aluminum alloy are not acceptable.

2.04

GROUND CONNECTIONS A. Ground rods shall be installed in the quantities as indicated on the drawings and as required by NFPA-780. Ground rods shall be placed a minimum of two (2) feet from building foundations. In addition to above artificial grounds, one down conductor of each two-path system shall be connected to water piping system with approved water pipe type strap connector. All ground rods shall be 5/8" X 20' copperweld type. All connections made below grade shall be exothermically welded (cadweld) connection and placed in a ground rod inspection well as detailed. B. Soil type in the area is primarily sand with rock layer below. The rock layers on site will require drilling of ground rod holes. All ground rods shall be installed vertically. After drilling and installation of rod, back fill with sand and hydro compact around rod to provide low resistance to ground.

2.05 A.

GROUND ROD & GROUND SYSTEM TESTING The contractor shall utilize a clamp on ground loop tester during construction to check the system for high resistance connections. The resistance at any point below the air terminal shall be less than 5 ohms. The resistance at grade level on the down conductors should be less than 2 ohms. The contractor shall investigate and correct high resistance readings within the system. Demonstrate

LIGHTNING PROTECTION SYSTEM 60060986 - March 24, 2010

266100-3

B.

to the engineer’s satisfaction with witness testing, provision of a low resistance installation meeting this specification. Provide three point fall of potential ground testing on a minimum of one ground rod on each facility prior to connection to the counterpoise system. As an alternate provide ground rod selective method testing with appropriate ground testers. The complete ground system shall be three point fall of potential tested after completion of work. The system shall be tested at a minimum of three points spaced around the site using the “Tagg Slope” technique. Total grid system grounds should be less than one ohm.

2.06 INSTALLATION A. Installation shall be made in an inconspicuous manner with conductors coursed to conceal equipment as much as possible. Down conductors shall be concealed within structure, and shall be run in 1" PVC conduit. Surface mount down conductors to existing structures in a neat and workmanlike manner. All metallic equipment within 6 feet of any lightning conductor shall be bonded to conductor. System shall also be tied to the main service electrical ground and other ground systems in the area. 2.07

COORDINATION A. The installer shall coordinate the lightning protection work to insure a correct, neat, and unobtrusive installation. B. Any electrical service grounding system and metallic water service piping to the structure shall be electrically bonded to the lightning protection system. C. The contractor shall coordinate his work in such a manner as to not interfere with the normal operation of the structure upon which the installation is performed.

2.08

Material Manufacturers A. Equipment shall be as manufactured by Thompson Lightning Protection, Inc. Independent Protection Company, Inc., Heary Brothers Lightning Protection, Harger Lightning Protection, Robbins Lightning Protection or Lightning Master Corporation.

END OF SECTION

LIGHTNING PROTECTION SYSTEM 60060986 - March 24, 2010

266100-4

SECTION 267090 SURGE SUPPRESSION, BONDING & GROUNDING PART 1 - GENERAL 1.

2.

APPLICABILITY A.

Surge suppression, grounding and bonding requirements outlined herein shall be fully applicable to all electrical and electronic systems which are provided as part of this contract under this division. It is intended that surge suppressors, grounding and bonding provisions as described herein be provided for each system or device by the contractor installing the system or device. Under certain circumstances, Surge suppression devices, bonding and special grounding may be required as provision for owner provided systems or equipment. Specific requirements for such additional surge suppression, bonding, and grounding will be indicated on the contract drawings or described elsewhere in this specification.

B.

Surge suppression, bonding and grounding shall be required on electrical and electronic systems apparatus residing outside the confines of a protected building. Tower mounted lighting, RF transmitters and active repeaters are examples of these types of devices. Devices mounted on the exterior wall of a protected building below the roof line shall be considered as being within the protected building.

C.

Requirements of this section shall be fully applicable to systems furnished under other divisions when reference is made to this section. References shall be by section number, name, or both.

REFERENCE STANDARDS AND PUBLICATIONS A.

The following standards and publications are referenced in various parts of this section and shall apply to this work: 1.

ANSI/IEEE C62.41-1980 (IEEE 587) Guide for Surge Voltages in LowVoltage AC Power Circuits. For purposes of this specification, category A and B exposures shall be as described. Category C exposure shall be assumed to be similar to category B in terms of surge waveforms, however, maximum voltage amplitude shall be assumed to be ten kilovolts and maximum current amplitude shall be assumed to be ten kiloamperes.

2.

ANSI/IEEE C62.31-1977 (IEEE 465.1-1977) Standard Test Specifications for Gas Tube Surge Protective Devices.

3.

ANSI/IEEE C62.1-1984 Standard for Surge Arresters for AC Power Circuits.

4.

ANSI/IEEE C62.32-1981 Standard Test Specifications for Low-Voltage Air Gap Surge-Protective Devices.

5.

ANSI/IEEE C62.33-1982 Standard Test Specifications for Varistor SurgeProtection Devices.

6.

ANSI/IEEE Standard 81-1983 Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System.

SURGE SUPPRESSION BONDING AND GROUNDING 60060986 - March 24, 2010

267090-1

3.

7.

Lightning and 60 Hz Disturbances at the Bell Operating Company Network Interface. Bell Communications Research Technical Reference TR-EOP000001, Issue 1, June 1984

8.

UL-1449 Standard for Transient Voltage Surge Suppressors

B.

ANSI/IEEE standards may be obtained from the Institute of Electrical and Electronics Engineers, Inc. 345 East 47th Street, New York, NY, 10017.

C.

Qualified surge suppression and equipment manufacturers may obtain a copy of the Bell Communications Research Standard through a Bell Operating Company representative. This document is also on file at the Engineer's office for review by interested parties. Permission to copy this document has not been granted.

SYSTEM PERFORMANCE CRITERIA A.

Surge suppression, grounding and bonding required by this specification for protection of electronic systems shall effectively protect the systems to which it is applied against lightning and other surge transients throughout the useful life of the system. Surge suppression devices and related grounding and bonding systems shall be designed and installed in such a manner that normal operation of the system is not impaired due to installation of such devices.

B.

Calculations for suppressor pulse-lifetime ratings shall assume the devices are installed in areas of medium exposure when such devices are installed in ANSI/IEEE 62.41-1980 category A or B locations. Devices in category C locations shall be considered to be in an area of high exposure. Frequency of surge occurrence and surge amplitudes shall be as outlined in this standard with a required minimum suppressor lifetime of fifteen years.

C.

Electronic system equipment shall be protected by dealing with each group of related devices as a "cluster" of equipment and protecting all metallic circuits which enter and leave the cluster. The cluster may be as large as a computer room, control room or equipment room or as small as an individual equipment cabinet. For purposes of establishing maximum size, all equipment within a protected cluster shall fall within a circular area of not greater than twenty-five feet in radius around a common point. All metallic circuits entering and leaving the equipment cluster shall be grouped together at a common point or "window" not larger than four by eight feet in dimension and protected with one exception. Circuitry which is supported by equipment within the cluster and extending beyond the cluster to serve devices within the building shall not require protection provided all of the following conditions are met: 1.

Circuitry is enclosed within ferrous metal conduit.

2.

No wiring within the raceways containing such circuits extends beyond the confines of the building.

3.

No connection is made between this wiring and conduit ground outside of the protected perimeter established for the equipment cluster.

4.

All devices connecting to such circuits shall have no connections to conduit, other grounds or other power sources outside the perimeter established for

SURGE SUPPRESSION BONDING AND GROUNDING 60060986 - March 24, 2010

267090-2

the equipment cluster. 5.

D.

4.

5.

All wiring to devices (and circuitry within devices) must be insulated from conduit and other grounds to a minimum impulse breakdown level of 5000 (five-thousand) volts or greater.

All equipment chassis within a protected equipment cluster shall be effectively isolated from stray grounds and bonded only to a ground bar at the "window" location for the cluster. The ground terminals of the suppressors protecting the equipment cluster shall also connect to this bar using a short direct route. The ground bar for each equipment cluster shall interconnect with each of the following external grounding systems: 1.

Electrical "Green-Wire" grounds serving equipment within the cluster.

2.

The building metallic structure at the closest point.

3.

The nearest point of attachment to the building cold water piping system (if metallic).

SPECIAL CABLING REQUIREMENTS A.

Cabling extended beyond the protected confines of a building, either direct burial or enclosed in non-ferrous conduit shall be designed for direct burial in a high lightning environment.

B.

Cables shall be expected to carry significant potentials associated with the direct or induced effects of lightning and protection from pinhole sheath damage and subsequent electrolytic action shall be provided.

C.

Cable design shall include a metallic shield and high density polyethylene outer jacket. Flooding compound shall be provided between the jacket and shield to heal pinhole jacket penetrations resulting from lightning. Standard direct burial telephone cables and CATV cables are acceptable for this application.

EXEMPTION FROM EXTERNAL SURGE SUPPRESSION REQUIREMENTS A.

It is recognized that equipment and system manufacturers are beginning to address surge suppression as an inherent part of their equipment design and it is the intent of this specification to permit the use of such equipment without requiring supplementary external surge suppression.

B.

Specific exemption will be granted for such systems and equipment upon receipt of documented tests from the manufacturer certifying the ability of the equipment or system to withstand common and differential mode surges on all metallic circuits using levels and waveforms described in ANSI/IEEE C62.41-1980 and as extended in the standards paragraph of this section. Pulse lifetime and withstand ratings for equipment shall be certified based on the appropriate category of exposure for a medium or high exposure location as appropriate to the location in which the equipment will be installed.

C.

Exposure for circuits which connect to telephone company lines shall be determined from the Bell Communications Research Standard listed herein. Frequency of surge occurrence shall also be determined from this standard.

SURGE SUPPRESSION BONDING AND GROUNDING 60060986 - March 24, 2010

267090-3

6.

7.

8.

D.

Surge suppression furnished as an integral part of the equipment or system shall be designed for a useful lifetime of fifteen years under conditions of exposure as outlined in the appropriate standard.

E.

Grounding and bonding provisions described herein shall apply to all equipment which is internally protected by the equipment manufacturer.

F.

In absence of a more relative standard, ANSI/IEEE C62.41-1980 exposure categories and waveforms shall be utilized in determining protective requirements for both power and signal wiring. The branch circuit wiring systems providing power to various electronic systems are quite similar to signal wiring in terms of topography and electrical characteristics which determine their ability to propagate surge energy.

MANUFACTURER QUALIFICATIONS A.

All surge suppression devices shall be manufactured by a company normally engaged in the design, development, and manufacture of such devices for electrical and electronic systems equipment.

B.

The surge suppressor manufacturer shall offer factory repair service for all nonencapsulated assemblies and replacement for all encapsulated units.

WARRANTY A.

All surge suppression devices and supporting components shall be guaranteed by the installing contractor to be free of defects in materials and workmanship for a period of one year from the date of substantial completion for the system to which the suppressor is attached.

B.

Any suppressor which shows evidence of failure or incorrect operation during the warranty period shall be repaired or replaced at no expense to the Owner. Since "Acts of Nature" or similar statements include the lightning threat to which these suppression devices will be exposed, any such clause limiting warranty responsibility in the general conditions of this specification shall not apply to this section.

SUBMITTAL A.

Surge suppression devices shall be submitted as an integral part of the equipment submittal for the system or equipment which they protect. Surge suppressors and their wiring, bonding, and grounding connections shall be indicated on the wiring diagrams for each system. Equipment grouped in clusters for the purposes of protection shall be indicated on the drawings by cluster and all bonding and grounding connections for the cluster shall be shown.

B.

The surge suppression submittal shall also include, but shall not be limited to, the following additional data: 1.

Complete schematic data for each suppressor type indicating component values, part numbers, conductor sizes, etc.

2.

Dimensions for each suppressor type indicating mounting arrangement and

SURGE SUPPRESSION BONDING AND GROUNDING 60060986 - March 24, 2010

267090-4

required accessory hardware. 3.

Manufacturers certified test data indicating the ability of the product to meet or exceed requirements of this specification.

4.

If requested, a non-encapsulated sample of each suppressor type to be used for testing and evaluation. If requested by the manufacturer, sample will be held confidential unless cause is found to suspect that actual devices furnished do not match sample. Samples will not be returned.

5.

It is recognized that certain manufacturers do not wish to divulge the contents of their products. Under these conditions, and in lieu of the required sample, the suppressor manufacturer may submit certified test data from a recognized independent testing laboratory indicating compliance with each element of this specification.

PART 2 - PRODUCTS 1.

POWER SUPPRESSORS FOR ELECTRONIC EQUIPMENT A.

Each item of electronic equipment provided under this contract and connected by line cord or direct wired to the building electrical system shall be provided with a three-stage single or multi-phase hybrid suppressor. Fusing shall be provided which removes the protective elements from the circuit upon failure. Visual indication or loss of output power shall be used to notify the user of device failure.

B.

Suppressors shall be rated for a minimum of 125% of their continuous electrical load. Suppressors for cord connected equipment shall be equipped with standard NEMA cordsets one of which includes a molded grounding receptacle and the other, a molded grounding plug. Suppressor shall be installed in series with the power cord for the protected equipment. Where several items of equipment are grouped within the same cluster of equipment, one suppressor may be used in conjunction with properly sized grounding plugstrip to serve the equipment.

C.

Suppressors for direct wired equipment shall be identical in internal design to the unit described for cord connected applications, however, protected screw terminals suitable for termination of solid copper wire shall be used for wiring terminations. One suppressor may be used to support several equipment cabinets provided all cabinets are located within the same equipment cluster and the maximum connected load shall not exceed eighty percent of the rated suppressor capacity.

D.

Suppressors shall be constructed with a phenolic non-flammable exterior housing with provisions for mounting to the interior of equipment racks, cabinets, or to the exterior of free-standing equipment. Suppressors shall be constructed as threestage devices. The first stage shall include a high-energy varistor clamp between line and neutral and from neutral to ground. The second stage shall consist of series air-core inductor installed in the line conductor(s) to properly coordinate the action of the first and third stages. The third, fast acting, hard clamping stage shall consist of a network of silicon avalanche bipolar surge suppression diodes between the neutral and line conductor(s).

E.

Minimum suppressor performance characteristics shall be as follows: 1.

Maximum single impulse line-to-neutral current withstand: 15,000 Amperes

SURGE SUPPRESSION BONDING AND GROUNDING 60060986 - March 24, 2010

267090-5

(8 x 20 us waveform)

2.

2.

Maximum single impulse neutral-to-ground current withstand: 10,000 Amperes (8 x 20 us waveform)

3.

Pulse lifetime rating Category B worst case current waveform (8 x 20 us @ 3000 Amperes): 1200 occurrences

4.

Pulse lifetime rating for 200 Ampere (8 x 20 us waveform): 10,000 occurrences

5.

Worst case response time: Five Nanoseconds

6.

Worst case (Maximum Single Impulse Current Conditions) clamping voltage: 400% of nominal phase-to-ground RMS voltage.

7.

Initial breakdown voltage: 200% of nominal phase-to-ground RMS voltage.

SUPPRESSORS FOR SINGLE CONDUCTOR PROTECTION A.

Suppression devices for single conductor protection shall be provided in multicircuit pluggable packages suitable for the circuitry to be protected. Units for protection of data circuits which utilize standard connector configurations shall be equipped with connectors which install in series with the data cable to the protected equipment. Units intended for use with individual wiring conductors shall be equipped with accessory terminal blocks or strips suitable for the type of wiring being used. Suppressors installed outside of terminal or equipment cabinets (except at designated terminal boards) shall be provided with a housing approved for the location.

B.

Suppression for each circuit shall consist of a two-element gas tube first stage, a series isolating element, and a silicon avalanche second stage. Resistive limiting elements may be used where the voltage drop across the series resistance has no effect on circuit operation. Inductive series elements may be used on other circuits to effectively pass direct or low frequency alternating currents while limiting passage of fast risetime surge waveforms. Silicon avalanche devices shall be designed for surge suppressor applications and shall be polarized or bipolar as appropriate for each circuit.

C.

Minimum performance criteria (each circuit) shall be as follows: 1.

Maximum single impulse conductor-to-ground current withstand: 12,000 Amperes (8 x 20 us waveform)

2.

Pulse lifetime rating Category B worst case current waveform (8 x 20 us @ 3000 Amperes): 1200 occurrences

3.

Pulse lifetime rating for 100 Ampere (10 x 1000 us waveform): 1,000 occurrences

4.

Worst case response time: Five Nanoseconds

5.

Worst case (Maximum Single Impulse Current) clamping voltage: 200% of normal operating voltage amplitude and polarized or bipolar as appropriate

SURGE SUPPRESSION BONDING AND GROUNDING 60060986 - March 24, 2010

267090-6

for each circuit type.

3.

6.

Initial breakdown voltage: 150 percent of normal operating voltage peak amplitude plus or minus five percent.

7.

Capacitance: Capacitance for DC or low frequency lines shall not exceed 2000 picofarads measured line to ground at the rated diode breakdown voltage. Suppressors intended for use on high frequency or high baud rate circuits shall be designed for use on such lines. Capacitance of such units shall be equated to equivalent cable feet based on the type of cabling used for the particular circuit. The sum of equivalent cable feet for suppressors and actual cable footage shall not exceed manufacturers recommended maximum values for the system on which these devices are installed.

8.

Circuit compensation: Any additional circuit compensation (gain or equalization) required to compensate for the insertion of surge suppression devices shall be provided as part of this contract.

SUPPRESSORS FOR CONDUCTOR PAIR PROTECTION A.

Suppression devices for conductor pair protection shall be provided in multi-circuit pluggable packages suitable for the circuitry to be protected. Units for protection of data circuits which utilize standard connector configurations shall be equipped with connectors which install in series with the data cable to the protected equipment. Units intended for use with multiple wiring pairs shall be equipped with an accessory terminal blocks or strips suitable for the type of wiring being used. Single pair units shall be configured as encapsulated units with wire leads or screwterminal wiring terminations. Suppressors installed outside of terminal or equipment cabinets (except at designated terminal boards) shall be provided with a housing to afford physical protection for the surge suppression modules.

B.

Suppression for each pair shall consist of a three-element gas tube first stage, an isolating element in series with each conductor of the pair, and a silicon avalanche second stage. Second stage clamping shall be provided across the pair for differential mode protection and from each side of the pair to ground for common mode protection. Resistive limiting elements may be used on low current circuits where the effect of voltage drop across the series resistance has no effect on circuit operation. Inductive series elements shall be used on higher current circuits to effectively pass direct or low frequency alternating currents while limiting passage of fast risetime surge waveforms. Silicon avalanche devices shall be designed for surge suppressor applications and shall be polarized or bipolar as appropriate for each circuit.

C.

Minimum performance criteria (each circuit) shall be as follows: 1.

Maximum single impulse conductor-to-ground or conductor to conductor current withstand: 10,000 Amperes (8 x 20 us waveform)

2.

Pulse lifetime rating Category B worst case current waveform (8 x 20 us @ 3000 Amperes): 10 occurrences

3.

Pulse lifetime rating for 100 Ampere (10 x 1000 us waveform): 1,000 occurrences

SURGE SUPPRESSION BONDING AND GROUNDING 60060986 - March 24, 2010

267090-7

4.

4.

Worst case response time: Five Nanoseconds

5.

Worst case (Maximum Single Impulse Current) clamping voltage: 200% of normal operating voltage amplitude and polarized or bipolar as appropriate for each circuit type.

6.

Initial breakdown voltage: 150 percent of normal operating voltage peak amplitude plus or minus five percent.

7.

Capacitance: Capacitance for DC or low frequency lines shall not exceed 2000 picofarads measured line to line or line to ground at the rated diode breakdown voltage. Suppressors intended for use on high frequency or high baud rate circuits shall be designed for use on such lines. Capacitance of such units shall be equated to equivalent cable feet based on the type of cabling used for the particular circuit. The sum of equivalent cable feet for suppressors and actual cable footage shall not exceed manufacturers recommended maximum values for the system on which these devices are installed.

8.

Circuit compensation: Any additional circuit compensation (gain or equalization) required to compensate for the insertion of surge suppression devices shall be provided as part of this contract.

BONDING AND GROUNDING CONDUCTORS AND MATERIALS A.

Conductors utilized for surge suppressor bonding shall be a minimum of #6 AWG solid insulated copper unless otherwise specified.

B.

Ground bus or strip material shall be copper, a minimum of 26 gauge in thickness and three inches wide unless otherwise specified. Bus materials may be secured to surfaces with an appropriate mastic material or mechanical fasteners. Bus connections shall be bolted or brazed and reinforced as necessary on thin bus material to provide a permanent and secure connection.

C.

Unless otherwise specified, all surge suppression grounding electrodes shall be 5/8" diameter copperweld rods, twenty feet in length.

D.

Connectors, splices, and other fittings used to interconnect grounding conductors, bond to equipment or ground bars, shall comply with requirements of the National Electric Code and be approved by Underwriters Laboratories for the purpose.

E.

Connectors and fittings for grounding and bonding conductors shall be of the compression or set-screw type in above grade locations. Connections below grade shall be exothermically welded or brazed.

F.

Bonding connections between electrically dissimilar metals shall be made using exothermic welds or using bi-metal connectors designed to prevent galvanic corrosion.

PART 3 - EXECUTION 1.

SEGREGATION OF WIRING A.

All system wiring shall be classified into protected and non-protected categories.

SURGE SUPPRESSION BONDING AND GROUNDING 60060986 - March 24, 2010

267090-8

Wiring on the exposed side of suppression devices shall be considered unprotected. Surge suppressor grounding and bonding conductors shall also fall into this category.

2.

B.

All wiring between surge suppressors and protected equipment shall be considered protected. Isolated circuitry exempted from surge suppression requirements in part one of this section shall also be considered protected.

C.

A minimum of three inches of separation shall be provided between parallel runs of protected and unprotected wiring in control panels, terminal cabinets, terminal boards and other locations. In no case shall protected and unprotected wiring be bundled together or routed through the same conduit. Where bundles of protected and unprotected wiring cross, such crossings shall be made at right angles.

INSTALLATION OF SUPPRESSORS A.

Suppressors shall be installed as close as practical to the equipment to be protected consistent with available space. Where space permits and no code restrictions apply, suppressors may be installed within the same cabinet as the protected equipment. Suppressors installed in this manner shall utilize the equipment chassis as a medium for bonding of their ground terminals. Bonding jumpers not exceeding two inches in length shall be installed between the chassis and suppressor ground terminals. Bolted connections with star washers shall be used to insure electrical and mechanical integrity of connections to the equipment chassis.

B.

Suppressors shall be installed in a neat, workmanlike manner. Lead dress shall be consistent with recommended industry practices for the system on which these devices are installed.

C.

Bonding between ground terminals for power and signal line suppressors serving a particular item or cluster of equipment shall be kept as short as possible. Where practical, suppressors shall be installed in a common location for the cluster with their ground terminals bonded closely together. For installations requiring separation between the various suppressor grounds and equipment chassis within an equipment cluster, the following table shall be used to determine bonding conductor requirements (distances are measured between most distant suppressor or chassis grounds): BONDING DISTANCE MATERIAL ------------------------------------------0 - 10 feet #6 AWG Bare Copper (Solid) 10- 25 feet 1-1/2" Copper Strip 26ga. Min. 25- 50 feet 3" Copper Strip 26ga. Min. Over 50 feet 6" Copper Strip 26ga. Min. Care shall be exercised to avoid connection of incidental grounds to the bonding bus system.

D.

Where terminal cabinets are used to house surge suppressors, painted steel backboards shall be used to serve as a low impedance ground plane for bonding surge suppressor leads together. Terminal boards used for the same purpose shall be laminated with a single sheet of 14 ga. galvanized steel to serve as a ground plane for suppressors. Suppressors with ground

SURGE SUPPRESSION BONDING AND GROUNDING 60060986 - March 24, 2010

267090-9

terminals not inherently bonded to the ground plane through their mounting shall be bonded to this plane using a two-inch maximum length of #12AWG copper wire and suitable lug. Ground planes and backboards shall be drilled to accept self tapping screws, any paint in the area of the bond shall be removed and star washers shall be used. E.

Supplementary grounding and bonding connections required between the bonding bus or ground plane for each equipment cluster and other locations as indicated herein shall be accomplished using #6 AWG bare copper conductor and approved connections unless otherwise noted.

END OF SECTION

SURGE SUPPRESSION BONDING AND GROUNDING 60060986 - March 24, 2010

267090-10

SECTION 268500 INSTRUMENTATION AND CONTROL SYSTEM PART 1 GENERAL 1.1 SCOPE A.

Furnish and install, complete with all accessories, a programmable logic control based monitoring and control system with its associated instrumentation as described herein and shown on the contract drawings. The system shall serve as a self-contained monitoring and control system for all aspects of pumping station operation. It shall also be capable of integration with the existing City of Sarasota central telemetry site.

B.

This Specification has been developed to establish minimum requirements for a pump controller. This system shall be designed, constructed, tested and documented in strict accordance with the guidelines of this document. All system construction and programming will be the responsibility of the instrumentation and control (I&C) system supplier. All materials and labor shall be provided for a fully functional system including any items which are required for system operation but are not specifically addressed in this document or on the contract drawings.

C.

This specification is intended to be used in conjunction with all drawings supplied and is not intended to be complete without reference diagrams on system configurations, etc. All bidders must conform to all areas of the documentation. It is the intent of this specification that the monitoring and control system contractor have single source responsibility for the complete control and instrumentation package for the project; including but not limited to flow, pressure, level instrumentation and control, Variable Frequency Drives, and interconnecting conduit and control wiring for total system responsibility.

1.2 CONTRACTOR QUALIFICATIONS AND ADDITIONAL RESPONSIBILITY A.

The contractor providing this system shall be an instrumentation and control systems contractor who is experienced in and regularly engaged in engineering, installation and service of systems of similar size and complexity within the water treatment industry.

B.

The contractor shall assume total systems responsibility for all aspects of this system including installation, commissioning and start-up of the system, training of operating personnel and coordinating interfaces between this system and equipment provided by others. This responsibility shall include mounting and wiring of relays, transformers, disconnecting means, and other control devices as required forming a complete system.

C.

The installing contractor shall maintain an office with full time sales and service staff within a one hundred and fifty-mile radius of the site. Emergency warranty service response shall be guaranteed to be a maximum of four-hours between the time of emergency notification and arrival of service personnel on site. An emergency service condition shall be considered to exist when any failed system hardware or software prevents or threatens to prevent the pumping station from fulfilling it's intended purpose as determined by the owner or engineer.

D.

Non-emergency service requests shall be responded to within 2 business days. Telephone support for operating procedures and non-hardware problems shall be provided on an unlimited basis during the warranty period.

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-1

1.3

E.

An unconditional warranty shall be provided for all equipment supplied for Two years from date of final acceptance of system by the owner. THIS WARRANTY SHALL INCLUDE ANY DAMAGES CAUSED BY LIGHTNING INDUCED ELECTRICAL SURGES; ONLY DAMAGES CAUSED BY DIRECT LIGHTNING STRIKES TO THE BUILDING STRUCTURE (AS DETERMINED BY THE ENGINEER) SHALL BE EXCLUDED FROM THE WARRANTY. Theft, fire, vandalism and floods shall be excluded from the warranty except for fire damage which originates at equipment which is provided as part of this work.

F.

Provide the services of a qualified system integrator that has demonstrated competence in providing controls system integration on this type of facility. Submittal qualifications with submittal of bid. Submit 10 example projects of installed history of the type and complexity of this project. Submit project data, and reference contacts.

SUBMITTALS A.

B.

Shop Drawings shall be submitted in accordance with Section 16050, Shop Drawings, Product Data and Samples. These drawings shall include: 1.

A cover sheet consisting of a Bill of Material, purchase order number, manufacturer's job number, Owner's name, location, application and shipping address.

2.

Mechanical layouts detailing the overall external dimensions of all enclosures. Include all pertinent information such as location of door handles, windows, lifting lugs and enclosure mounted items such as pump controller chassis and I/O modules (show cable connections on modules), relays, cooling fans, etc.

3.

Details for mounting of the processor, I/O racks, relays, motor starters, disconnect switch, fuse blocks, wireways, etc. All materials shall be labeled to provide easy cross-reference to the Bill of Material listing.

5.

Electrical drawings detailing all hardwiring, done by the supplier, to devices such as relays, pump controller modules, disconnect switches, fuse blocks, etc. Provide individual wire numbers and relay contact cross-reference designations.

6.

A description of all input and output modules by name, rack, module and terminal location.

7.

The last sheet(s) in the set shall describe all terminal block designations and individual terminal numbers.

Shop Drawings: 1.

Complete master wiring diagrams, elementary schematics and control schematics shall be submitted for approval before proceeding with manufacture. Suitable outline drawings shall be furnished as part of this submittal. Standard or typical pre-printed sheets or drawings simply marked to indicate applicability to this contract will not be acceptable. Shop drawings shall be on standard 24" X 36" or 11" X 17" media; drawn with a computer aided design package. The computer aided design package shall be AUTOCAD version 2004 or converted to Autocad version 2004. Engineering plan backgrounds of the facility shown on the contract documents will be available to the contractor on request.

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-2

Submittals shall include reproducible plots of the drawings on paper translucent bond and CD-ROM electronic copies. 2.

A complete drawing indicating each point of interface with the process control system and the type of signal provided or accepted at each point. This drawing shall depict the actual interface terminal block including all circuit designations.

3.

A complete sequence of operation describing the control strategy in response to external signals and the signals which will be provided to the process control system during operation of the plant. All interlocks and limits which are internal to the operation of the controls shall be included in this description.

4.

A drawing showing the layout of the control panels indicating every device with complete identification.

PART 2 PRODUCTS 2.1 PUMPING SYSTEM CONTROLLER OPERATION A.

The pump control panel (PCP) system shall perform all logic operations necessary to sequence and alternate the pumps to accomplish proportional level control and to ensure equal run times on all pumps. The pump controller shall also automatically select one or multiple backup units in the event of a single or multiple pump failure. The pump controller shall interface with the VFD's through an analog module interface. The pump controller coordinates the operation of the pump drive system; monitors status of the complete plant operation and provides the telemetry interface. In normal operation the controller shall schedule the pumps on and off to maintain wetwell level. The level control parameters will be based on values set by the operator from the PCP graphic screen. The initial wetwell proportional values are as indicated on the drawings. The control levels set by the operator are to be checked by the PCP to be within the minimum and maximum limits established. Minimum low level limits will be 3.4 feet above wetwell floor to protect pumps from running dry which is also the low alarm point. Maximum high level control limit will be 10.4 feet above wetwell floor which is also the high level float. The high high level float is initially set for 11.4 feet above the wetwell bottom and will activate the backup pump controller. Also provide virtual high level alarms from the level transmitter signal at 3” below the “start diesel pump1 start” level and 3” below the “start diesel pump2 start” level.

B.

The following operating modes shall be required for the pump controller: 1.

Maintain the wetwell level established by the proportional level control system, automatically and without regard to system flow within a 0.2 feet level deviation. The turn on and turn off level values for each pump (lead, lag and lag-2 and lag-3) will be operator configurable with the initial values as indicated on the drawings. The pump controller shall insure speed matching of all pumps. 2. Allow or disallow automatic operation of each pump via telemetry or locally from the operator interface. 3.

Provide for sensing of VFD current.

4. Provide for pump shutdown on fault indication from pump control and status module (Fairbanks Morse SubGard). INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-3

C.

For each Drive in the system, the controller program shall control the RUN command and specify the operating mode (LEAD, LAG, LAG-2, LAG-3) of the Drives. The software internal to the controller shall coordinate the Drives to allow a lower priority pump to move up in the priority string in the event of the next higher pump drive has faulted.

D.

As the level in the wetwell increases and the lead pump is running at full speed, the level reaches the “start lag pump” setpoint, a signal shall activate and latch to call on the lag pump. The lag pump will come on line and quickly ramp up and match the speed of the lead pump. The pumps will operate as a speed matched pair. As the level continues to rise and the Lead and Lag pumps are running at full speed, the level reaches the “start lag-2 pump” level, a signal shall activate and latch to call on the Lag-2 pump. Same for the Lag-3 pump.

E.

As demand increases and decreases, the Pump controller shall stage on and off the lag and lag-2 &3 pumps based on “lag pump stop” elevation, lag-2 & lag-3 pump stop elevation. As flow decreased further the lead pump ramps down based on level to minimum speed. The minimum speed is maintained until the level drops further to a “stop lead pump” wetwell level setpoint. The lead VFD pump shall be alternated on each operation based on the pump with the least hours. The PCP monitors the flow rate of the pump station through the magnetic flowmeter, and totalizes the pulsed volume. If the flow rate drops below a setpoint initially set for 50gpm after a time delay (initial setting of 30sec) with the pump running, an alarm is initiated and the lead pump is shutdown. The VFD minimum speed programmed into the VFD shall be set to maintain a flowrate with an initial setpoint of 50gpm for all head conditions.

F.

The pump controller shall monitor the signals of two (2) redundant level transmitters using either as a backup or check of the other. Each transmitter shall be totally independent of each other with independent power supplies. The pump controller will generate an alarm if the transmitter signals are more than a predetermined (operator) configurable percent deviation from each other. The operator shall be able to select either level or an average of both level transmitters to control from. The selection shall be locally at the pump controller. Normally the average of the level transmitters shall be used for control. In the event the levels are more than 10% apart the higher of the two shall be used for control and an alarm shall be indicated to the operator. Signals less than 4ma or greater than 20ma shall be ignored and the other used for control. A backup pump controller shall override the control to the VFDs on initiation of a high-high level switch operation. The VFDs shall be programmed to start and run at a predetermined speed until a second low level float activates.

G.

The control signals to and from the PCP controller shall be as shown in the I/O PCP appendix.

2.2 PUMP CONTROLLER ENCLOSURE A. The pump system controller shall be housed in a free standing NEMA type 12 enclosure of approximately 36" wide, 24” depth and 72” height. The enclosure shall accommodate all associated new equipment and instrumentation for the plant. The enclosure shall be ventilated as required by the application. A matching adjacent 36”x24”x72” termination/surge suppression cabinet shall be provided for all field cable terminations. B.

Fused terminal blocks shall be provided for all inputs and outputs. Blocks shall be permanently marked to indicate the appropriate I/O address of each circuit on the pump controller. Surge suppressors shall be provided for all analog inputs

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-4

and outputs. Surge suppressors shall be provided for all digital inputs and outputs that leave or enter the pump building. C.

The assembled system shall include circuit breakers, fuse blocks and other electrical components as required by the application and in accordance with the standard requirements of the National Electric Code as well as all State and Local electrical code requirements.

D.

All I/O racks, processor racks and power supplies shall be grounded in accordance with the manufacturer's specifications.

E.

All push-buttons, switches and other operator devices shall be UL listed and/or CSA approved and sufficiently large and durable to provide dependable, long life operation.

F.

All cables, plugs, connectors and receptacles requiring user field installation shall be designed to withstand an industrial environment.

2.3 PUMP CONTROLLER: SYSTEM A.

Provide Multitrode Multismart Pump Controller with an intuitive user-interface. The product shall come with pre-built configuration parameters which are selectable via the user interface and a PC configuration program, including: Setpoint adjustment for pump activation/deactivation and level alarms; Level device from 4-20mA; Redundant level device handling; Selectable between fill / empty; Functionality for advanced pump control of up to 9 pumps including grouping and alternation; Station optimization including, Max off time (odour reduction). Maximum starts per hour (pump protection), Inter-pump start and stop delays. Maximum run time (turn off inefficient or partially blocked pumps), Blocked pump detection, Well clean out (periodic pump down to snore point), Multiple profiles of setpoints for spill management, off peak pumping, Datalogger of 50,000 events, 3-phase supply monitoring and supply protection, Undervoltage, Over-voltage, Phase fail, Phase rotation, Monitoring of dc supply, battery voltage, and internal temperature. Provide for optional VFD control algorithms.

B.

The I/O shall be expandable to many hundreds of I/O points per unit. Available I/O types shall include: Digital inputs (voltage free input), also configurable as counters. Digital outputs (240V, 5A resistive); Analog inputs (10bit); Analog outputs (10bit). The product shall include: Ethernet 10Mbit/s; Multiple RS232 ports to 115kBit/s. The system shall support a variety of communications networks including: Private radio over RS232; PSTN; Wireless LAN; Cellular voice and cellular data. The communications protocol will be an open protocol such as DNP3 which includes: Change of state reporting; Native date/time and quality stamps for each data point; Event buffering for different classes of data; Modbus master/slave protocol will also be provided

C.

The field hardware shall include a user interface for operations and configuration. The display shall provide status of most aspects of the pump station, control of pumps, resetting of faults, and configuration of parameters. The following parameters shall be displayed on the main screen: Level, Setpoints for alarms and pump start/stop, Pump running/stopped, Pump available, Pump fault. The screen will also have buttons to allow the user to access Faults, History, Information and Settings. The following parameters shall be available via a user key press from the main screen: Hours Run accumulators for each pump & the station with the following comparisons, last minutes run, this hour, last hour, today, yesterday, this week, last week, total hours run; Starts accumulators for each pump & the station with the following comparisons Flow values, either derived from calculations or via a flowmeter, including inflow, pump flow rate,

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-5

total volume. Any overflow information, including start time, duration, estimated volume; Insulation resistance value for each motor; Status of all I/O D.

The following aspects of the system, as a minimum, shall be controlled intuitively through the user-interface: Pump mode, for each pump, between Auto/ Manual (Hand)/ Off; Pump fault reset; Level alarm reset.

E.

The main screen shall include a Fault button which takes the user to a Fault screen and allows them to check all current and unacknowledged alarms. The fault screen will detail the fault (e.g. contactor fail, seal fault, motor overtemp, over-current, etc) along with date/time each fault occurred and cleared. A reset option for a fault will be presented to the user when faults can be acknowledged/reset.

F.

The main screen shall include a History button which takes the user to a History screen and allows them to check all faults and events along with date/time. The History screen shall include the ability to filter to view only faults, only events, or narrow down to events relating to specific types of data.

G.

The user interface should allow intuitive configuration of the system, including as a minimum: 1. Set-points, including alarm and pump setpoints. 2. Enable/disable level alarms (so that for example, the low level alarm can be easily activated or deactivated) 3. Start, stop and alarm delays 4. Alternation/ fixed sequence and grouping of pumps where necessary 5. Assign primary/backup level to any input, e.g. 4-20mA or conductive probe 6. Assign pre-defined (or user-defined) faults, e.g. thermal overload, contactor fail, to any digital input 7. Zero and span analog inputs 8. Set Digital outputs to change state with any digital tag in the system 9. Set Analog outputs to follow any analog value, including primary level 10. Set each fault as either: display only; manual/SCADA restart; auto restart with configurable restart time 11. Pump station optimisation parameters such as: 12. Max off time (odor reduction) 13. Maximum pumps to run (overload protection) 14. Maximum starts per hour (pump protection) 15. Inter-pump start and stop delays 16. Maximum run time (turn off inefficient or partially blocked pumps) 17. Well washer controls 18. Well clean out (periodic pump down to snore point) 19. Supply protection 20. Under- and over-voltage alarm points 21. DC-supply alarm point 22. Motor protection parameters, including under- and over-current, ground/earth fault, phase fail.

J.

Lightning and transient surge protection shall be provided for all analog circuits and all digital circuitry entering or leaving the pumping unit controller room. AC line noise filtering shall be provided. K. Provide six spare digital inputs and five spare digital outputs; two spare analog inputs and analog outputs for future designation.

2.4

Radio Based Telemetry System

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-6

2.5

A.

Provide a radio telemetry system for this project to match the existing City of Sarasota telemetry systems. The telemetry system shall include a Dataflow model RTU 204 with Modbus Communications link PLC033. The integrator shall include the VTSCADA software integration at the existing City of Sarasota Central Telemetry System.

B.

Provide for communications with the pump station PCP through a Modbus communications module. Telemetry Control/Monitoring/Alarm Signals communicated through the Modbus link with the pump station PCP shall include but not be limited to the signals shown in the PCP I/O appendix and shall be provided to the RTU for transmission to the Master Telemetry Unit.

C.

Provide 30’ to 50’ concrete pole antenna structure where shown on the drawings. Provide a field propagation study demonstrating fade margins obtained at the project site from 20-60 feet in 5 foot increments with the exact proposed telemetry radio and antenna equipment. The height of the structure shall be no less than 30 feet and have a minimum of a 20db fade margin to and from the Central Telemetry site. Provide all required hardware. Provide structure certified for 140mph wind loading per FBC2007. Provide drilled pier type structural foundation. Provide design by a registered structural engineer in the state of Florida. Provide lightning protection, grounding and surge suppression as detailed on the drawings.

D.

Provide a Dataflow radio modem for the owners existing frequency 217.925mhz). DFS will provide a Remote Terminal Unit (RTU) as required to interface with the Multismart PCP. The RTU will interface with the automation PLC using Modbus TCP over a network cable, cable and connectors to be provided by others (RJ45connector). Standard 5 digit registers must be used and formatted with 0XXXX for digital outputs, 1XXXX for digital inputs, 3XXXX for analog inputs, and 4XXXX for analog outputs. Packing Modbus digital input, digital output, and analog input registers into the 4XXXX range is not permitted. All analog points over the Modbus link must be provided as the raw value (0-4095, 12 bit) number with 0 representing 0ma (-25% of full scale) and 4095 representing 20ma (100% of full scale); with the exception of integers in which the value will not exceed 4095 in this case the transmission can be direct. The translation of the Multismart to Modbus protocol is the responsibility of the integrator or Multitrode provider. The integrator shall supply to DFS the Modbus addressing I/O map (including the type of digital outputs from telemetry, momentary or maintained) and P&ID drawing for the site must.

E.

The antenna system shall be yagi type of heavy wall black anodized construction rated for 140MPH minimum equal to Sinclair SY307 series with a peak gain of not less than 10dB. The RTU antenna coaxial cable shall be equal to or better than RG-8U 0.405"OD closed cell foam filled with an attenuation of 2.7db/100 feet at 400Mhz or less and equal to Belden #9913.

Master Telemetry Computer Software Integration A. At the existing master telemetry computer for the City of Sarasota, provide graphic screen programming utilizing the existing VTSCADA software. Construct and link graphic screens depicting each element. Screen presentation shall be constructed with full use of dynamic colors, levels and numeric values and tied to real time data. All pumps etc, shall be controllable from the computer operator interface pointing device with on and off indications on the video terminal. B.

Provide a color graphic screen depicting all pumps, flows, levels, alarms, etc. All pumps shall be red when running, green when off and flash amber when in alarm. Valves shall be red when open and green when closed. All analog values

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-7

shall be displayed in engineering units. Graphic levels shall be animated in blue with levels that raise or lower in proportion to their signal values. Critical analog and digital values shall flash amber when outside normal limits or when in an alarm state. C.

The operator work station shall scan the database as necessary to retrieve and send analog and digital information for displays, control, logging and related operator work station functions. Create internal registers and signals as required to link real signals to graphics for monitoring and keyboard for control. Each signal shall be individually defined and assigned to a new device file. Incorporate all required signals into the database and set limits and alarm values based on owner requests and operational testing.

D.

Individual RTU and global system screens will be configured for each system. The graphic screens shall have a graphic control switch indicating "on", and "auto" position for each pump. The "on" position shall symbolize the operator manual on (call) condition. The pumps shall be animated when the running indication is detected. The normal "auto" position shall allow start and stop from the computer control logic.

E.

Provide Historical logging of all data received by CTU. Provide historical trending screens for operator selected parameters from the historical files; hourly, daily, weekly, monthly and yearly averages and peak values. Elapsed running time values shall be maintained in the distributed database for all pumps. This data shall be expressed in hours and tenths of hours and shall be updated every sixty seconds using the last scanned value for each associated discrete input. For reporting purposes, the database shall perform averaging and integration on a point basis over one of the following time periods: one minute, five minutes, hourly, shift, or daily, weekly, monthly with the following averages provided. 1. 2. 3. 4. 5. 6. 7.

One minute - derived from readings accumulated at scan rates. Five minutes - derived from above one minute values. Hourly - derived from above five minute values. Shift - derived from above one hour values. Daily - derived from above shift values. Weekly - derived from above daily values. Monthly - derived from above daily values.

2.6 UNINTERRUPTABLE POWER SUPPLY SYSTEM A. A UPS system shall be provided for support of electronic equipment through the normal-to-emergency power transfer interval. The UPS shall operate in an on line mode and supply power continuously with no interruption in CPU operation when normal power fails. The UPS shall be based on a constant voltage transformer technology. The UPS shall support all I/O, transmitters power supplies, pump controller and associated controls and operator interface for a minimum of 45 minutes (but in no case less than standard battery pack run time) upon interruption of normal power. B. Lightning and surge protection shall be provided at the input to the UPS. C. Batteries shall be a sealed lead acid or gelled electrolyte type which require no special ventilation provisions. D. Transfer time shall be 5 ms or less. E. The UPS back up system shall be contained within a NEMA-1 enclosure. F. The UPS shall be Best Power Technologies Microferrups. 2.7

Ball Float Switches A. Units shall be direct-acting float type level sensing device with a 5-1/2" diameter, 316 stainless steel float. The switch shall be mercury free. The switch shall be

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-8

SPDT, rated 1 Amps at 150 VAC/VDC non-inductive with a mechanical life of 10 million operations. The float cable shall be rated "continuous service" for high flexibility. The float switch(es) shall be cable/pipe mounted. All mounting hardware shall be 316 SS. All float fittings shall be flared and incorporate strain relief jacketing.

2.8

B.

Cable shall be rugged and flexible with heavy neoprene or PVC jacket. The actuation/deactuation differential shall not exceed 4 inches. Units shall be pipe mounted or suspended type as noted, and provided with 40 feet of cable unless otherwise noted. Each pipe mounted type shall be provided with a clamp to secure the cable to 1-inch support pipe.

C.

Each suspended type shall be provided with necessary brackets and clamps to suspend the unit from the top of a tank or vessel. The suspended type shall include an integral or attached weight assembly for stabilization and positive operation of the unit. All mounting clamps shall be PVC or neoprene.

D.

Provide Contegra model FS90 mercury free switch with suspended cable kit or approved equal.

TRANSMITTER POWER SUPPLIES A. Provide dc power supplies as required to power instruments requiring external dc power. Provide individual power supplies for each instrument or provide redundant monitored power supplies for multiple instruments. Each redundant power supply shall automatically backup the other in case of failure of one supply. B.

Power supplies shall convert 120V ac, 60-Hz power to dc power of the appropriate voltage(s) with sufficient voltage regulation and ripple control to assure that the instruments being supplied can operate within their required tolerances.

C.

Output overvoltage and overcurrent protective devices shall be provided with the power supply to protect the instruments from damage due to power supply failure and to protect the power supply from damage due to external failure. Provide NEMA 1 enclosure for all power supplies. Power supplies shall be mounted such that dissipated heat does not adversely affect other components.

2.9

PROCESS METERS A. Process Meters: Provide digital programmable process meters designed for a 420MA current loop display and isolated retransmission of displayed output. Provide minimum 0.5" high, 4-1/2 digit LED display to indicate amplitude of current in the current loop and calibrated to engineering process units. In general, a loop current of 4ma corresponds to a display indication of 0 percent and a loop current of 20ma corresponds to a display indication of 100 percent. The meter shall be provided with programmable internal scaling adjustment. Provide units with NEMA-4X faceplate rating constructed of silicone coated Lexan and gasketed for NEMA 4 requirements; circuit boards coated for moisture resistance. Provide Yokogawa Model UM330; no equal.

2.10

Isolating transmitters: Current-To-Current Isolating Transmitter A. Unit shall receive 4 to 20 mA dc input signal and shall produce a isolated, proportional 4 to 20 mA dc output signal into loads in the range of 0 to 1200 ohms minimum without load adjustments for a 24V dc supply. Input impedance

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-9

B.

C.

shall be less than or equal to 50 ohms. Unit accuracy shall be plus or minus 0.25 percent of span, minimum. Unit shall be provided with multi-turn span and zero adjustments. Unit shall be housed in a NEMA 1 rated enclosure and shall be furnished with an integral bracket for rear-of-panel mounting, unless otherwise noted. Unit shall have input/output and power isolation. Unit shall operate on 120-volt, 50/60-Hz power. Unit shall be Moore Industries SCT/ECT/MIX or equal.

2.11

Control Panel Operating Controls and Instruments: A. All operating controls and instruments shall be securely mounted on the control compartment door or backplane. All controls and instruments shall be clearly labeled to indicate function. B. Indicator lamps shall be LED full voltage type and mounted in NEMA 4X (800H) modules, as manufactured by Allen Bradley or SKPI as manufactured by Square D. Lamp modules shall be equipped to operate at 24 or 120 volt input. Lamps shall be easily replaceable from the front of the control compartment door without removing lamp module from its mounted position. Units shall be heavyduty, oiltight, industrial type with screwed on prismatic glass lenses in colors as shown, and shall have factory engraved legend plates. LED's shall be high illumination type (5ma at 130V ac). C. Selector switches shall be heavy-duty, oiltight, industrial type selector switches with contacts rated for 120V ac service at 10 amperes continuous. Units shall have standard size, black field, legend plates with white markings, as indicated. Operators shall be black knob type. Units shall have the number of positions and contact arrangements and spring return function (if any) as shown. Units shall be single-hole mounting, accommodating panel thicknesses from 1/16-inch minimum to 1/4-inch maximum. Units with up to four selection positions shall be Allen Bradley 800H, Square D Type K, Cutler-Hammer Type T, or equal. Units with up to 12 selection positions shall be Rundel-Idec Standard Cam Switch, Electroswitch 31, or equal.

2.12

RELAYS A. Control circuit switching shall be accomplished with relays. These relays, for interfacing and control applications, shall be the compact general purpose plugin type having low coil inrush and holding current characteristics. A neon statusindicating light shall be provided with each relay. Contact arrangements shall be as noted or shown, and shall be rated for not less than 10 amperes at 120V ac or 28V dc. Coil voltage shall be as noted or shown. Non-latching relays shall have a single coil. Latching relays shall have two coils, unlatching being accomplished by energizing one coil, and latching being accomplished by energizing the other coil. Relays shall have plain plastic dust covers, test buttons, and mounting sockets with screw terminals and holddown springs. Relays shall be UL recognized. Relays shall be Potter and Brumfield, StruthersDunn, or equal. B. Time delay functions shall be accomplished with time delay relays. Units shall be adjustable time delay relays with the number of contacts and contact arrangements as shown. A neon status-indicating light shall be provided with each relay. Contacts shall be rated for 10 amperes at 120V ac. Integral knob with calibrated scale shall be provided for adjustment of time delay. Initial setting shall be as shown with time delay range approximately three times the initial setting. Time delay rangeability shall be at least 10:1. Operating voltage shall be 120V ac, plus 10 percent, -15 percent at 60-Hz. Operating temperature shall be -20 degrees F to 165 degrees F. Repeat timing accuracy shall be plus or minus 10 percent over the operating range. Units shall be Amerace Corp., Control Products Division, Agastat Series 7000, Cutler-Hammer Series D87, or equal.

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-10

C.

2.13

2.14

All relays shall have a screw terminal interface with the wiring. Terminals shall have a permanent, legible identification. Relays shall be mounted such that the terminal identifications are clearly visible and the terminals are readily accessible.

ELECTROMAGNETIC FLOWMETER A. Provide a dual excitation electromagnetic flow meter suitable for measurement of flow in a full pipe. The flow meter shall consist of a flow tube and a converter, which shall indicate, totalize and transmit flow. The flow tube shall use a spool piece configuration with sensor coils and electrodes. The nominal diameter of the flow tube shall be as shown on the piping drawings. Provide flow tube with standard PFA lining unless otherwise indicated. B.

The spool piece flow tube shall be made of carbon steel and shall be epoxy enamel painted. O ring seals shall be made of Viton, and standpipe gaskets shall be made of nitrile rubber. The flow tube shall be supplied with raised face carbon steel flanges. The flow sensors shall contain a coil, a pair of sensing electrodes, and an integral grounding electrode. The sensors shall use solid state design, with the coils, electrodes, and other sensor components encapsulated in polyurethane. The electrodes shall be made of Type 316 stainless steel. The flow tube shall be rated for continuous submergence (NEMA 6).

C.

The wiring from the converter to the sensors shall be 2 separate 2-conductor cables, 18 gauge, twisted and shielded The converter shall contain a 3-1/2 digit liquid crystal display (LCD). The LCD shall display flow rate based on discharge units or flow rate percentage. The converter shall have the capability to dampen the flow rate display to provide an average value of readings over a selectable time interval from 0 to 60 seconds. The converter shall include a 6 digit, non-resettable LCD totalizer. The converter shall include an isolated 4 to 20 mA output based on flow and a pulsed volume output. The converter shall operate on 120 VAC, 50/60 Hz line power. The converter shall be housed in a rugged, lockable, watertight, dust-tight, corrosion resistant (NEMA 4X) polyester fiberglass enclosure suitable for conduit connections. The enclosure shall include a clear polycarbonate window for viewing the LCD and totalizer without opening the enclosure. Provide an EDCO model SLAC TVSS unit and 316 stainless steel ground rings with the flow meter. Provide factory built in surge protector power option.

D.

The flowmeter transmitter shall be calibrated for 0-100%flow range; 4-20ma and be rated for 0.35% of reading accuracy. Provide HART communication interface superimposed on the 4 to 20 mA DC signal. Flow Meters shall be factory calibrated to NIST traceable standards. Provide certified factory calibration records. Flow meters shall be ANSI/NSF 61 approved.

E.

Provide Yokogawa Magnetic Flow Meters series AXF for sizes as shown on the mechanical process drawings.

PRESSURE SWITCHES A. Pressure, vacuum, and differential pressure switches shall be single or dual action with an adjustable setpoint for the process requirement and/or as specified herein. Switches shall be bourdon tube, diaphragm or piston operated and activate D.P.D.T. snap action switches on increasing or decreasing pressure. Minimum differential shall be less than 10 percent of the range. Deadband shall be adjustable. Allowable surge pressure shall be a minimum 1.5 times the range. Each pressure switch shall have visible scale. B. Pressure switches shall have a contact rating of 10 amperes at 120 volts AC. Pressure switches shall be in NEMA 4X enclosures. Switches shall have a

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-11

repeatable accuracy of 1 percent of range. Pressure switches shall be isolated from the process fluid by a diaphragm seal or an isolation ring except for clean water applications. Wetted parts materials shall be compatible with the process fluid for corrosion resistance. Pressure switches shall be manufactured by Ashcroft, Mercoid or equal. 2.15

SUBMERSIBLE LEVEL TRANSDUCER (intrinsically safe) A. Provide submersible level transmitters to sense the liquid level of the wetwell. The unit shall consist of a submersible sensor and encapsulated transmitter to provide a continuous monitoring of the wetwell level. Provide transducer housing fabricated of 316 stainless steel with a 3”” diameter oil filled diaphragm. Provide transducer with 1/2” NPT male thread for pipe mounting and stainless steel standoff to protect the diaphragm. B. Provide transmitter with 4-20madc output, loop powered type, with output signal directly proportional to the measured level. Excitation range 9-36vdc. C. Provide a NEMA-4X lockable weatherproof enclosure for the wiring termination. The enclosure shall house a sealed breather system that relieves the internal air pressure of the sensor assembly to atmospheric pressure and the Permanent Desiccant Filter. D. Provide unit with 30+ foot 1” 316 stainless steel pipe and mounting provisions as detailed. E. Provide intrinsically safe FM approved Wilkerson Instrument LS1000 Series with 0-15psi (0-34’) range. Provide total of four; two instruments for each half wetwell; one for the PCP system and one for the Standby Diesel Pump control.

2.16

Temperature Indicating Transmitters; Differential A.

Temperature indicating transmitters shall be microprocessor based with "smart" electronics, capable of accepting direct inputs from 2-, 3-, or 4-wire, platinum, copper, or nickel resistance temperature detectors (RTD) from 10 to 1000 ohms, thermocouple inputs, direct millivolt sources, and resistance potentiometer devices. The indicating transmitter shall be a true 2-wire device capable of operating on voltages up to 45 VDC.

B.

The accuracy of the transmitter's Digital-to-Analog converter shall be within 0.03 percent of span. An LCD digital display shall be provided, capable of displaying ma, degrees in any units, ohms, or mV. The indicator transmitter shall contain an analog-to-digital converter which shall convert the RTD input to a digital signal and send it to the transmitter's electronics for further processing. Factory set correction coefficients shall be stored in the sensor's non-volatile memory for correction and linearization of the sensor output in the electronics section. The electronics section shall correct the digital signal from the sensor and convert it into a 4-20 mA analog signal for transmission to receiving devices. The electronics section shall contain configuration parameters and diagnostic data in non-volatile EEPROM memory and shall be capable of communicating, via a digital signal superimposed on the 4-20 mA output signal, with a remote interface device. Output signal damping shall be provided, with an adjustable time constant of 0-36 seconds.

C.

The transmitter assembly shall be furnished with all necessary hardware for proper mounting as recommended by the manufacturer. Indicating transmitter shall be housed in a watertight enclosure meeting NEMA 4X requirements. Enclosure shall be suitable for wall or 2-inch pipe stand mounting.

D.

The transmitter shall provide a linear isolated 4-20 mADC output proportional to

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-12

temperature.

2.17

E.

The temperature Indicating Transmitters shall be furnished complete with temperature sensor RTDs, 100 ohms platinum type for pump room and outside air temperature. Calibrate for 4-20 degrees differential temperature to 4-20ma out.

F.

Temperature measurement system shall be Model 3144P as manufactured by Rosemount Engineering Co., or equal.

Electrical Surge And Transient Protection A. General: All instrument and control equipment mounted outside of protective structures (field-mounted equipment) shall be equipped with suitable surgearresting devices to protect the equipment from damage due to electrical transients induced in the interconnecting lines from lightning discharges and nearby electrical devices. Surge suppression equipment shall meet or exceed the requirements as specified herein. Surge suppressors shall be as manufactured by EDCO, Inc., of Ocala, Florida. B.

Suppressor Locations: Surge suppression equipment described herein and indicated on the contract drawings shall be installed in the following locations: At the point of connection between each equipment item and its power supply conductors (direct wired equipment). In other locations where equipment sensitivity to surges and transients requires additional protection beyond that inherent to the design of the equipment.

C.

Power Supply Suppressor Assemblies: Provide suppressors suitable for connection to 120-volt, single-phase power supply. Suppressors shall be EDCO "HSP-121 SERIES", or equal, and shall meet or exceed the following requirements: 1.

2.

3.

4.

Suppressors for direct wired equipment shall be provided with two 3terminal barrier terminal strips capable of accepting no. 12 AWG solid or stranded copper wire. One terminal strip shall be located on each end of the suppressor unit. Suppressors shall be epoxy encapsulated within a phenolic nonflammable enclosure with provision for mounting to interior of equipment racks, cabinets or to the exterior of free standing equipment. Epoxy encapsulation shall be flame retardant. Suppressors shall be constructed as multistage devices. The first stage shall be a high energy metal oxide varistor element. The second stage shall consist of fast acting high power bipolar silicon avalanche devices. First and second stages shall be interconnected through a series air core inductor of sufficient current carrying capacity to permit a continuous operating current of 15 amperes. Suppressors shall meet or exceed the following performance criteria based on a test surge waveshape of 8 times 20 microseconds. Maximum Operating Voltage: 130V ac Minimum Breakdown Voltage: 150V ac Maximum Operating Current: 15 amps Response Time: 5 nanoseconds Peak First Stage Clamping Voltage: 20,000 amps Maximum First Stage Clamping Voltage: 350 Volts Maximum Second Stage clamping Voltage: 210 Volts Pulse Life Before Failure: 2,000 occurrences

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-13

D.

Analog Signal Cable Suppressor Assemblies: Suppressors shall be EDCO SRA or DRS Series, or equal. Provide EDCO type SS64 surge suppressors at all loop powered instrument locations. Suppressors shall be epoxy encapsulated within a phenolic enclosure and stainless steel for SS64 units. Suppressor Assembly shall be flame retardant. Suppressor assemblies shall be four lead devices and shall include a threaded mounting/grounding stud. Suppressors shall meet or exceed the following performance criteria based on a test surge waveshape of 8 times 20 microseconds: 1.

2. 3. 4. 5. 6. 7. 8. 9. 10. 11.

2.18

Components: Hybird circuit consisting of a 3 electrode gas tube and silicone avalanche devices to clamp each line to ground. High energy gas tube and silicone avalanche devices shall be separated by a series impedance. Recovery: Automatic Peak Surge Current: 10,000 amps Pulse Life Before Failure: 100 occurrences Response Time: 5 nanoseconds Minimum Voltage Clamp Rating: 40 volts Series Impedance: 24 ohms total Temperature Range: -40 degrees C to +85 degrees C Operating Voltage: Less than 30V dc Operating Current: 4 to 20 Ma dc Resistance Line to Ground: Greater than 1 megohm

E.

Hybrid power and analog signal suppressor assemblies. Suppressors shall be EDCO SLAC units or approved equal.

F.

Surge suppressor input (unprotected) and output (protected) wiring shall be kept segregated at the point of connection to the surge unit and external to the unit. Do not route unprotected cable adjacent to protected cable.

SPARE PARTS A.

B.

Provide as part of this contract a complete compliment of replacement spare parts for all component parts of this system. It shall be the supplier's responsibility to prepare a detailed suggested replacement parts list for review and approval by the owner. As a minimum, the controls system supplier shall furnish one plug-in module for each type of control module used in the system; CPU module, one analog input module; one analog output module; two digital input modules; two digital output modules; two each relay; one each type power supply; 2 each type signal surge suppressor; two sets complete of each type fuse.

PART 3 - EXECUTION 3.1 INSTALLATION A.

The work included in this section consists of furnishing, installing and placing in operation the instruments and appurtenances, including all conduit, wiring and circuitry, necessary to provide the Owner with a fully operable system properly calibrated and installed.

B.

Include the services of a factory trained, qualified service engineer of the equipment manufacturer to inspect the complete equipment installation to assure that it is installed in accordance with the manufacturer's

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-14

recommendations, make all adjustments necessary to place the system in trouble-free operation and instruct the operating personnel in the proper care and operation of the equipment furnished. C.

All workmanship utilized in the manufacture and installation of this system shall be of the highest quality and performed in a manner which is consistent with all accepted practices for industrial controls.

3.2 START UP SUPERVISION

3.3

3.4

A.

The system supplier shall provide a qualified service technician to inspect all final connections and check the system prior to start-up of the system. The service technician shall coordinate with the owner's representative for functional check-out of the complete system.

B.

A system software engineer shall be provided on site during start up of the plant to make adjustments to the Control Computer/ Operator Interface and tune the system as deemed necessary by the engineer.

C.

System verification marking end of suppliers on-site start-up obligations will be issued after system functionality can be demonstrated for a period of 168 continuous hours without interruptions due to engineering error on the part of the supplier.

MOUNTING OF EQUIPMENT AND ACCESSORIES A.

Install and mount equipment in accordance with the Contract Documents, manufacturer's instructions and installation detailed shop drawings. Mount equipment so that they are rigidly supported, level and plumb, and in such a manner as to provide accessibility; protection from damage; isolation from heat, shock and vibration ; and freedom from interference with other equipment, piping, and electrical work. Do not install field enclosures, cabinets, and panels until heavy construction work adjacent to the equipment has been completed to the extent that there shall be no damage to the equipment.

B.

Locate devices, including accessories, where they shall be accessible from grade, except as shown otherwise.

C.

Coordinate the installation of the electrical service to components related to the system to assure a compatible and functionally correct system. All accessories shall be coordinated and installation supervised by the Contractor.

E.

Test the completed system after installation to assure that all components are operating with the specified range and all interlocks are functioning properly.

CALIBRATION A.

Calibrate each instrument in the factory before shipping and furnish with the calibration data and the certification of calibration.

B.

Calibrate all instruments and components of the instrumentation system with field adjustable ranges and/or settings after installation in conformance with the manufacturer's instructions, the Contract Documents and the reviewed shop drawings. Set each instrument and components for the specific conditions and intended application as specified for this installation. Replace defective instruments and components which cannot achieve correct calibration of stated accuracy, either individually or collectively within the system.

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-15

C.

Certify in writing to the Owner that all calibrations have been completed and the instrumentation system is ready to be operated. Provide instrumentation calibration sheets in the O&M manuals for future reference for both factory and field calibration tests. Calibration certification documents shall be available on site at the time of substantial completion.

3.5

FIELD TESTING A. Conduct a field test of all the instrumentation equipment in the presence of the Engineer, Owner, or their designated representative(s). B. Verify that each instrument has been properly installed, connected, grounded and calibrated. C. Verify that the inputs/outputs functions of each instrument conform to the requirements of the application. D. Provide continuous protection of the installed instrumentation equipment from the elements, moisture, construction damage, dust, debris, paint spatter or other conditions which will adversely affect the unit operation until such time as the equipment scheduled for start up testing. E. Exercise each system as defined by each loop description through operational tests to demonstrate that it performs as intended on a continuing basis and to demonstrate the integrity of the system. F. Make all necessary replacements, repairs, correction and/or adjustments including but not limited to labor, parts and freight at no additional cost to the owner to demonstrate a fully operational system. G. The service technician shall calibrate all gauges and instruments. A documented calibration and settings report shall be included in the O&M manuals.

3.6

START UP TESTING A. After the field testing has been successfully demonstrated, a date for system start up involving the Owner's operating personnel will be scheduled as agreed to by the Owner. B. Start up and test the instrumentation equipment with the entire system operational. C. Provide manufacturer's representative as directed by the Engineer for instruction of Owner's operating personnel.

3.7 WARRANTY AND TRAINING A. All products mentioned herein must be warranted by the supplier for a period of Two (2) years from the date of system turnover; final acceptance. B. The system supplier shall also provide four (4) days of training instruction to the owner’s personnel to include; two days operator training; and two days PCP and Controls system maintenance training including software maintenance training. END OF SECTION

INSTRUMENTATION AND CONTROL SYSTEM 60060986 - March 24, 2010

268500-16

City of Sarasota Utilities; Master Pump Station 87 Pump Controller/SCADA-I/O LIST DESCRIPTION

TYPE

STATUS

Elec Elec Elec Elec Elec Elec Elec Elec Elec Elec

Effluent Pump#1 VFD Effluent Pump#1 VFD Effluent Pump#1 VFD Effluent Pump#1 VFD Effluent Pump#1 VFD Effluent Pump#1 VFD Effluent Pump#1 Seal leak Effluent Pump#1 High Winding Temp Effluent Pump#1 High Bearing Temp Effluent Pump#1 VFD

DI DI DI DO AI AO DI DI DI AI

RUN REMOTE FAULT START/STOP PUMP SPEED SPEED/DMD Alarm Alarm Alarm Pump Current

Elec Elec Elec Elec Elec Elec Elec Elec Elec Elec

Effluent Pump#2 VFD Effluent Pump#2 VFD Effluent Pump#2 VFD Effluent Pump#2 VFD Effluent Pump#2 VFD Effluent Pump#2 VFD Effluent Pump#2 Seal leak Effluent Pump#2 High Winding Temp Effluent Pump#2 High Bearing Temp Effluent Pump#2 VFD

DI DI DI DO AI AO DI DI DI AI

RUN REMOTE FAULT START/STOP PUMP SPEED SPEED/DMD Alarm Alarm Alarm Pump Current

Elec Elec Elec Elec Elec Elec Elec Elec Elec Elec

Effluent Pump#3 VFD Effluent Pump#3 VFD Effluent Pump#3 VFD Effluent Pump#3 VFD Effluent Pump#3 VFD Effluent Pump#3 VFD Effluent Pump#3 Seal leak Effluent Pump#3 High Winding Temp Effluent Pump#3 High Bearing Temp Effluent Pump#3 VFD

DI DI DI DO AI AO DI DI DI AI

RUN REMOTE FAULT START/STOP PUMP SPEED SPEED/DMD Alarm Alarm Alarm Pump Current

Elec Elec Elec Elec Elec Elec Elec Elec Elec Elec

Effluent Pump#4 VFD Effluent Pump#4 VFD Effluent Pump#4 VFD Effluent Pump#4 VFD Effluent Pump#4 VFD Effluent Pump#4 VFD Effluent Pump#4 Seal leak Effluent Pump#4 High Winding Temp Effluent Pump#4 High Bearing Temp Effluent Pump#4 VFD

DI DI DI DO AI AO DI DI DI AI

RUN REMOTE FAULT START/STOP PUMP SPEED SPEED/DMD Alarm Alarm Alarm Pump Current

Elec Elec

Wetwell Basin 1 Level LIT#1 Wetwell Basin 2 Level LIT#2

AI AI

Level Level

Facility

PUMP CONTROLLER/SCADA – I/O LIST 60060986 - March 24, 2010

268500-A-1

City of Sarasota Utilities; Master Pump Station 87 Pump Controller/SCADA-I/O LIST Elec Elec

Wetwell Basin#1 High Level Switch Wetwell Basin#2 High Level Switch

DI DI

alarm alarm

Elec Elec Elec

Wetwell Basin#1 High-High Level Switch Wetwell Basin#2 High-High Level Switch Backup pump controller fault

DI DI DI

Backup Pmp Ctrl Backup Pmp Ctrl alarm

Elec Elec Elec Elec Elec

North Discharge H2S AIT from OCCP South Discharge H2S AIT from OCCP Odor Control, Control Panel (OCCP) Odor Control, Control Panel (OCCP) Odor Control, Control Panel (OCCP)

AI AI DI DI DI

PPM PPM RUN REMOTE FAULT

Elec Elec

Sump Pumps Pit#1 Sump Pumps Pit#2

DI DI

High Level High Level

Elec Elec

Effluent Flow Rate FIT Effluent Flow Total FIT

AI DI

Flow Rate Flow Total pulse

Elec Elec Elec Elec Elec Elec Elec

Generator Test (start & transfer) ATS Cmd Utility Supplying load Genset supplying load Emergency Source Available Utility Source Available ATS Not in Auto Common Alarm (trouble)

DO DI DI DI DI DI DI

Gen Test Closed Closed Status Status Alarm Alarm

Elec Elec Elec

Pump Room Exhaust Fan VFD Pump Room Exhaust Fan VFD Pump Room Exhaust Fan VFD

DI DI DI

RUN FAULT Auto

Elec Elec Elec

Pump Room Supply Fan VFD Pump Room Supply Fan VFD Pump Room Supply Fan VFD

DI DI DI

RUN FAULT Auto

Elec Elec Elec Elec Elec

Pump Room Temp Alarm Pump Room HVAC Alarm Pump Controller power failure Pump Controller UPS battery/low voltage Entrance Hatch Intrusion Alarm limit switch

DI DI DI DI DI

High Temp Fault alarm alarm alarm

PUMP CONTROLLER/SCADA – I/O LIST 60060986 - March 24, 2010

268500-A-2

City of Sarasota Utilities; Master Pump Station 87 Pump Controller/SCADA-I/O LIST Pmp Pmp Pmp Pmp Pmp

Genset Alarm Shutdown Genset WARNING Genset Battery Charger alarm Genset not in auto GenSet Running (Ready to Load)

DI DI DI DI DI

Shutdown Trip Warning Alarm Alarm status

Pmp Pmp Pmp

Diesel Tank level Diesel Tank Rupture Diesel Fuel Line Leak

AI DI DI

0-100% fuel alarm alarm

Pmp Pmp

Diesel Pump#1 Day Tank Alarm Diesel Pump#1 Day Tank Rupture

DI DI

Alarm alarm

Pmp Pmp

Diesel Pump#2 Day Tank Alarm Diesel Pump# 2 Day Tank Rupture

DI DI

Alarm alarm

Pmp Pmp

Genset Day Tank Alarm Genset Day Tank Rupture

DI DI

Alarm alarm

Pmp Pmp

Sump Pumps Pit#1 Sump Pumps Pit#2

DI DI

High Level High Level

Pmp Pmp

Cooling Water Pressure Alarm (PSL) Entrance Hatch Intrusion Alarm limit switch

DI DI

alarm alarm

Pmp Pmp Pmp

Diesel Pump#1 Alarm Diesel Pump#1 not in auto Diesel Pump#1 Running

DI DI DI

Alarm Alarm status

Pmp Pmp Pmp

Diesel Pump#2 Alarm Diesel Pump#2 not in auto Diesel Pump#2 Running

DI DI DI

Alarm Alarm status

Pmp Pmp

Diesel Pump#1 Running Diesel Pump#2 Running

DO DO

Pilot light Pilot light

PUMP CONTROLLER/SCADA – I/O LIST 60060986 - March 24, 2010

268500-A-3

City of Sarasota LS87 Instrument List TAG

DESCRIPTION

TYPE

RANGE

COMMENT 16” meter (verify)

10FIT-1

Effluent Flowmeter

Magnetic

0-7,500 GPM

10LIT-1

Diesel Tank level

Intrinsically safe resistive

0-5000gal

By tank vendor

20LIT-1A

Wetwell Level

Submersible, Diaphragm actuated, silicon filled

0-30 Ft H20

0-30’ SCADA

20LIT-1B

Wetwell Level

Submersible, Diaphragm actuated, silicon filled

0-30 Ft H20

0-30’ Diesel pmp1

20LIT-2A

Wetwell Level

Submersible, Diaphragm actuated, silicon filled

0-30 Ft H20

0-30’ SCADA

20LIT-2B

Wetwell Level

Submersible, Diaphragm actuated, silicon filled

0-30 Ft H20

0-30’ Diesel pmp2

INSTRUMENTATION LIST 60060986 - March 24, 2010

268500-B-1

SECTION 269100 CONTROL PANELS PART 1 - GENERAL 1.

2.

WORK INCLUDED A.

Furnish all labor, equipment, and materials for control panels as indicated on the drawings and specified herein. The panel supplier shall be a UL listed panel shop and all panels shall be UL-508 certified and labeled.

B.

Control panel equipment shall be coordinated to provide all the specified control as indicate in the elementary diagrams or specified herein.

C.

The Contractor shall be responsible for coordinating and interfacing with equipment and instrumentation supplied under other sections of the Contract Documents that are an integral part of the plant control systems. This interfacing shall be incorporated in the detailed systems drawings and data sections to be submitted by the contractor prior to rough-in work.

SUBMITTALS A.

The contractor shall submit to the Engineer for approval complete shop drawings, wiring diagrams, data, and operation and maintenance manuals of all equipment to be furnished under this section.

B.

Coordination and Shop Drawings: Prepare and submit coordination drawings for installation of products and materials fabricated. Coordination and shop drawings shall be prepared using a computer aided drafting system compatible with Autodesk Autocad version 2004 or greater. Coordination and shop drawings shall be submitted on hard copy and electronic CD-Rom (dwg) format. 1.

Submit component interconnect drawings showing the interconnecting wiring between each component including equipment supplied under other sections requiring interfacing with the control system. Diagrams shall show all component and panel terminal board identification numbers, and external wire and cable numbers. Note, this diagram shall include all intermediate terminations between field elements and panels (e.g., terminal junction boxes, pull boxes, etc.). Diagrams' devise designations, and symbols shall be in accordance with NEMA ICS 1-101.

2.

Panel Wiring Diagrams: Elementary diagrams shall be similar to those diagrams shown in the drawings, but with the addition of all auxiliary devices such as additional relays, alarms, fuses, lights, fans, heaters, etc.

3.

Panel wiring diagrams shall identify wire numbers and types, terminal numbers, tag numbers and PMP CP I/O identification (address) numbers. Wiring diagrams shall show all circuits individually; no common diagrams shall be allowed.

4.

Submit arrangement and construction drawings for consoles, control panels, and for other special enclosed assemblies for field installation. Include dimensions, identification of all components, preparation and finish data, nameplates, enough other details to define the style and

CONTROL PANELS 60060986 - March 24, 2010

269100-1

overall appearance of the assembly and a finish treatment. Drawings shall show the location of all front panel mounted devices to scale, and shall include a panel legend and a bill of materials. The panel legend shall list and identify all front of panel devices by their assigned tag numbers, all nameplate inscriptions, service legends and annunciator inscriptions. The bill of materials shall list all devices mounted within the panel that are not listed in the panel legend, and shall include the tag number, description, manufacturer and complete model number for each service. 5. C.

Operation, Maintenance and Repair Manuals 1.

3.

Submit installation, mounting, and anchoring details for all components.

Submit operation and maintenance manuals.

CODES AND STANDARDS: A.

Equipment, materials, and workmanship shall comply with the latest revisions of the following codes and standards 1. 2. 3. 4. 5. 6.

Instrumentation: Instrument Society of America (ISA). National Electrical Code (NEC) 2005, Wiring: ISA S5.3 and S5.4, latest issue. Control Panels and equipment: NEMA, UL and ANSI. Control Logic: Joint Industrial Council (JIC). UL508A and UL508A-SB

PART 2 – PRODUCTS 2.01

GENERAL A. Unless otherwise specified, instruments shall be solid state, electronic, using enclosures to suit specified environmental conditions. All instruments shall be provided with mounting hardware and floor stands, wall brackets, or instrument racks as shown on the Drawings, or as required. Equipment installed in a hazardous area shall meet Class, Group, and Division as shown on the Drawings, to comply with the National Electrical Code. Provide heavy-duty type devices throughout that are designed for continuous industrial service. Equipment used shall be U.L. approved. B.

All field instrumentation for outdoor service shall be furnished in and subsequently installed in Field Panels or Sun Shade. Unless otherwise specified, provide field instrument enclosures of stainless steel or copper free cast aluminum and powder coated white with NEMA 4X rated construction; provide sunshades for all exposed exterior panels.

C.

Unless otherwise shown or specified, local indicators shall be provided for all instruments. Where instruments are located in inaccessible locations, local indicators shall be provided and shall be mounted remotely. All indicator readouts shall be linear in process units. Readouts of 0-100% shall not be acceptable (except for valve position). Floating outputs shall be provided for all transmitters.

D.

Electronic equipment shall utilize printed circuitry and shall be coated (tropicalized) to prevent contamination by dust, moisture and fungus. Solid-state

CONTROL PANELS 60060986 - March 24, 2010

269100-2

components shall be conservatively rated for long-term performance and dependability over ambient atmosphere fluctuations. Ambient conditions shall be -15 to 50 degrees C and 20 to 100 percent relative humidity, unless otherwise specified. Field mounted equipment and system components shall be designed for installation in dusty, humid, and corrosive service conditions. E.

2.02

All analog transmitter and controller outputs shall be isolated, 4-20 milliamps into a load of 0-750 ohms, unless specifically noted otherwise. All switches shall have double-pole, double-throw contacts rated at a minimum of 600 VA, unless specified otherwise.

Control Panels A.

Control panels shall be UL508A/SB compliant. Control panels shall be marked with a short circuit current rating (SCCR). The SCCR shall be equal to or more than the short circuit current available at the panel line terminals.

B.

The electrical control equipment shall be mounted within a pad-lockable NEMA Type 4X dead-front enclosure constructed of not less than 304 stainless steel and shall be quipped with a 3-point latch with all hardware and exterior components construction of 300 series stainless steel (except control panels in air conditioned spaces and electrical room may be NEMA 1 painted steel). The enclosure shall be equipped with an inner dead front door and shall incorporate a removable, aluminum or stainless steel back panel on which control components shall be mounted. Back panel shall be secured to enclosure with collar studs. All hardware shall be stainless steel. Provide safety hardware to hold the door in an open position. Provide a folding shelf on the door for convenient temporary support of a laptop computer.

C.

Components: All motor branch circuit breakers; motor starters and control relays shall be of highest industrial quality, securely fastened to the removable back panels with screws and lock washers. Back panels shall be tapped to accept all mounting screws. Self-tapping screws shall not be used to mount any component.

D.

A circuit breaker shall be provided on each control panel as a means of disconnecting power to the control panel. The disconnect operating handle shall be installed on the right side of the cabinet not in the door.

E.

Control transformers shall be installed where shown to provide 120VAC and 24VAC for control circuits. Transformers shall be fused on the primary and secondary circuits. The transformer secondary shall be grounded on one leg.

F.

All control panel wiring shall be identified at both ends with type written heat shrinkable wire markers with the numbering system shown on the control submittal drawings. 1.

G.

Control wiring shall be stranded copper, minimum size #14 AWG (except for shielded instrumentation cable may be #16 AWG), with 600 volt, 90 degree C, flame retardant, Type MTW thermoplastic insulation.

The control panel shall be provided with nameplates identifying each component, selector switches, pilot lights, etc. Nameplates shall be permanently affixed using an epoxy process. Nameplates shall be laminated plastic, engraved white letters with a black background.

CONTROL PANELS 60060986 - March 24, 2010

269100-3

H.

Corrosion Inhibitor Emitter: Provide an industrial corrosion inhibitor emitter on all exterior mounted control panels that will protect internal components of the control panel from corrosion one year. Provide one spare emitter for each control panel.

I.

Terminal strips shall be provided for all signals as indicated on the drawings plus all spare conductors as specified. Terminal strips shall be switch type with integral fuses equal to Allen Bradley 1492-H6. Wiring from the control panel to the terminal strips shall be factory installed. All spare conductors shall be terminated and identified. All terminals over 200V phase to phase shall be covered with approved plastic shields.

J.

RELAYS

K.

1.

Control circuit switching shall be accomplished with relays. These relays, for interfacing and control applications, shall be the compact general purpose plug-in type having low coil inrush and holding current characteristics. A neon status-indicating light shall be provided with each relay. Contact arrangements shall be as noted or shown, and shall be rated for not less than 10 amperes at 120V ac or 28V dc. Coil voltage shall be as noted or shown. Non-latching relays shall have a single coil. Latching relays shall have two coils, unlatching being accomplished by energizing one coil, and latching being accomplished by energizing the other coil. Relays shall have plain plastic dust covers, test buttons, and mounting sockets with screw terminals and holddown springs. Relays shall be UL recognized. Relays shall be Potter and Brumfield, StruthersDunn, or equal.

2.

Time delay functions shall be accomplished with time delay relays. Units shall be adjustable time delay relays with the number of contacts and contact arrangements as shown. A neon status-indicating light shall be provided with each relay. Contacts shall be rated for 10 amperes at 120V ac. Integral knob with calibrated scale shall be provided for adjustment of time delay. Initial setting shall be as shown with time delay range approximately three times the initial setting. Time delay rangeability shall be at least 10:1. Operating voltage shall be 120V ac, plus 10 percent, -15 percent at 60-Hz. Operating temperature shall be -20 degrees F to 165 degrees F. Repeat timing accuracy shall be plus or minus 10 percent over the operating range. Units shall be Amerace Corp., Control Products Division, Agastat Series 7000, Cutler-Hammer Series D87, or equal.

3.

All relays shall have a screw terminal interface with the wiring. Terminals shall have a permanent, legible identification. Relays shall be mounted such that the terminal identifications are clearly visible and the terminals are readily accessible.

Front Panel Operating Controls and Instruments 1.

All operating controls and instruments shall be securely mounted on the control compartment door. All controls and instruments shall be clearly labeled to indicate function.

2.

Indicator lamps shall be LED full voltage push to test type and mounted in

CONTROL PANELS 60060986 - March 24, 2010

269100-4

NEMA 4X (800H) modules, as manufactured by Allen Bradley or SKPI as manufactured by Square D. Lamp modules shall be equipped to operate at 24 or 120 volt input. Lamps shall be easily replaceable from the front of the control compartment door without removing lamp module from its mounted position. Units shall be heavy-duty, oiltight, push to test industrial type with screwed on prismatic glass lenses in colors as shown, and shall have factory engraved legend plates. LED's shall be high illumination type (5ma at 130V ac). 3.

L.

2.03

Selector switches shall be heavy-duty, oiltight, industrial type selector switches with contacts rated for 120V ac service at 10 amperes continuous. Units shall have standard size, black field, legend plates with white markings, as indicated. Operators shall be black knob type. Units shall have the number of positions and contact arrangements and spring return function (if any) as shown. Units shall be single-hole mounting, accommodating panel thickness from 1/16-inch minimum to 1/4-inch maximum. Units with up to four selection positions shall be Allen Bradley 800H, Square D Type K, Cutler-Hammer Type T, or equal. Units with up to 12 selection positions shall be Rundel-Idec Standard Cam Switch, Electroswitch 31, or equal.

Process Meters: Provide digital programmable process meters with a loop powered display designed for a 4-20MA current loop. Provide minimum 0.5" high, 4-1/2 digit LED display to indicate amplitude of current in the current loop. In general, a loop current of 4ma corresponds to a display indication of 0 percent and a loop current of 20ma corresponds to a display indication of 100 percent. The meter shall be provided with programmable internal scaling adjustment. Provide units with NEMA-4X faceplate rating constructed of silicone coated Lexan and gasketed for NEMA 4 requirements; circuit boards coated for moisture resistance. Provide panel meters for each analog process variables; Pressure, level and flow as indicated equal to Precision Digital, or ABB or equal.

Electrical Surge And Transient Protection A. General: All instrument and control equipment, field-mounted shall be equipped with suitable surge-arresting devices to protect the equipment from damage due to electrical transients induced in the interconnecting lines from lightning discharges and nearby electrical devices. Surge suppression equipment shall meet or exceed the requirements as specified herein. Surge suppressors shall be as manufactured by EDCO, Inc., of Ocala, Florida. B.

Suppressor Locations: Surge suppression equipment described herein and indicated on the contract drawings shall be installed in the following locations: At the point of connection between each equipment item and its power supply conductors (direct wired equipment). In other locations where equipment sensitivity to surges and transients requires additional protection beyond that inherent to the design of the equipment.

C.

Power Supply Suppressor Assemblies: Provide suppressors suitable for connection to 120-volt, single-phase power supply. Suppressors shall be EDCO "HSP-121 SERIES", or equal, and shall meet or exceed the following requirements: 1.

Suppressors for direct wired equipment shall be provided with two 3terminal barrier terminal strips capable of accepting no. 12 AWG solid or stranded copper wire. One terminal strip shall be located on each end of

CONTROL PANELS 60060986 - March 24, 2010

269100-5

the suppressor unit.

D.

2.

Suppressors shall be epoxy encapsulated within a phenolic nonflammable enclosure with provision for mounting to interior of equipment racks, cabinets or to the exterior of free standing equipment. Epoxy encapsulation shall be flame retardant.

3.

Suppressors shall be constructed as multistage devices. The first stage shall be a high energy metal oxide varistor element. The second stage shall consist of fast acting high power bipolar silicon avalanche devices. First and second stages shall be interconnected through a series air core inductor of sufficient current carrying capacity to permit a continuous operating current of 15 amperes.

4.

Suppressors shall meet or exceed the following performance criteria based on a test surge waveshape of 8 times 20 microseconds. a. Maximum Operating Voltage: 130V ac b. Minimum Breakdown Voltage: 150V ac c. Maximum Operating Current: 15 amps d. Response Time: 5 nanoseconds e. Peak First Stage Clamping Voltage: 20,000 amps f. Maximum First Stage Clamping Voltage: 350 Volts g. Maximum Second Stage clamping Voltage: 210 Volts h. Pulse Life Before Failure: 2,000 occurrences

Analog Signal Cable Suppressor Assemblies: Suppressors shall be EDCO SRA or DRS Series, or equal. Provide EDCO type SS64 surge suppressors at all loop powered instrument locations. Suppressors shall be epoxy encapsulated within a phenolic enclosure and stainless steel for SS64 units. Suppressor Assembly shall be flame retardant. Suppressor assemblies shall be four lead devices and shall include a threaded mounting/grounding stud. Suppressors shall meet or exceed the following performance criteria based on a test surge waveshape of 8 times 20 microseconds: 1.

2. 3. 4. 5. 6. 7. 8. 9. 10. 11.

Components: Hybird circuit consisting of a 3 electrode gas tube and silicone avalanche devices to clamp each line to ground. High energy gas tube and silicone avalanche devices shall be separated by a series impedance. Recovery: Automatic Peak Surge Current: 10,000 amps Pulse Life Before Failure: 100 occurrences Response Time: 5 nanoseconds Minimum Voltage Clamp Rating: 40 volts Series Impedance: 24 ohms total Temperature Range: -40 degrees C to +85 degrees C Operating Voltage: Less than 30V dc Operating Current: 4 to 20 Ma dc Resistance Line to Ground: Greater than 1 megohm

E.

Hybrid power and analog signal suppressor assemblies. Suppressors shall be EDCO SLAC units or approved equal.

F.

Surge suppressor input (unprotected) and output (protected) wiring shall be kept segregated at the point of connection to the surge unit and external to the unit. Do not route unprotected cable adjacent to protected cable.

CONTROL PANELS 60060986 - March 24, 2010

269100-6

PART 3 - EXECUTION 1.

MOUNTING OF EQUIPMENT AND ACCESSORIES A.

B.

C.

Install and mount equipment in accordance with the Contract Documents, and installation detailed shop drawings. Mount equipment so that they are rigidly supported, level and plumb, and in such a manner as to provide accessibility; protection from damage; isolation from heat, shock and vibration; and freedom from interference with other equipment, piping, and electrical work. Mount local equipment in cabinets or existing panels as specified. Mount associated terminals on a common panel or rack; all terminals over 200V phase to phase shall be covered with plastic shields. Provide services of panel manufacturer to test the completed system after installation to assure that all components are operating with the specified range and all interlocks are functioning properly. Panel manufacturer shall certify functional operation and calibration in written startup report. Perform field tests on all completed control assemblies to demonstrate conformance to specifications and functional compatibility. END OF SECTION

CONTROL PANELS 60060986 - March 24, 2010

269100-7

PART 3 - EXECUTION 3.1

INSTALLATION A.

Comply with manufacturer's written instructions for installing access doors and frames.

B.

Set frames accurately in position and attach securely to supports with plane of face panels aligned with adjacent finish surfaces.

C.

Install doors and hatches flush with adjacent finish surfaces or recessed to receive finish material.

3.2

ADJUSTING AND CLEANING A.

Adjust doors and hatches hardware after installation for proper operation.

B.

Remove and replace doors, hatches and frames that are warped, bowed, or otherwise damaged. END OF SECTION

STAIR ACCESS DOORS, HATCHES AND FRAMES 60060986 - March 23, 2010

083113 - 3

DIVISION 28 – ELECTRONIC SAFETY AND SECURITY 283336

HYDROGEN SULFIDE GAS DETECTION SYSTEM

SECTION 283336 PART 1 A.

HYDROGEN SULFIDE GAS DETECTION SYSTEM

- GENERAL

Description This section includes materials, installation, and testing of calibrated field-mounted hydrogen sulfide gas detectors, monitors, alarms, and calibration kits.

B.

Related Work Specified Elsewhere Biofilter Odor Control System: 444628.

C.

D.

Submittals 1.

Submit shop drawings in accordance with the General Provisions, Section 013300 and the following:

2.

Submit certified dimensional drawings and catalog cuts for each size and type of instrument, cabinet, and alarm beacon. Catalog cuts are to be highlighted to define specific materials of construction and specified features.

3.

Submit installation, operation, and maintenance manuals and wiring diagrams.

Manufacturer’s Services Provide equipment manufacturer’s services at the jobsite for the minimum labor days listed below, travel time excluded: 1.

One-half labor day to check the installation and advise during start-up, testing, and adjustment of the equipment.

2.

One-half labor day to instruct the Owner’s personnel in the operation and maintenance of the equipment.

PART 2 - MATERIALS A.

Hydrogen Sulfide Gas Detector 1.

The hydrogen sulfide gas detector shall be the electrochemical type designed to measure concentrations of hydrogen sulfide. The detector shall have an adjustable range of 0- to 50-ppm hydrogen sulfide, a maximum zero drift of ±5% of span per year, a maximum span drift of ±10% per year, and a repeatability of ±1% of full scale. The detector shall be UL and FM listed.

2.

Calibration of the hydrogen sulfide gas detector shall not require opening the transmitter enclosure or declassification of the area.

3.

House the detector and its electronics in a Type 316 stainless steel NEMA 4 enclosure, UL approved for Class 1, Division 1, Group B hazardous locations.

HYDROGEN SULFIDE GAS DETECTION SYSTEM 60060986 - March 24, 2010

283336-1

4.

B.

The detector head, with the electrochemical bead cell, shall be removable and replaceable without replacement of electronics, without the need to open the sensor housing, and without the need to declassify the area. The detector head shall be “smart” and shall store all calibration data and sensor identification data, such as type of gas monitored and range. Upon installation into the housing, this data shall be recognized and uploaded into the transmitter electronics. This shall allow sensors to be bench calibrated then taken to the field and installed. Detector life shall be guaranteed for one year of continuous operation, minimum.

Hydrogen Sulfide Gas Transmitters 1.

The gas concentration shall be continuously displayed in engineering units at the integrally mounted local display.

2.

The transmitter shall be capable of storing and displaying average, minimum, and maximum gas concentrations over selected periods of time.

3.

The transmitter shall give an indication of when sensor is nearing the end of its useful life by means of the front panel LCD. Indication that the sensor is nearing its useful life shall be based on the sensor output, not on the time the sensor has been in service.

4.

The transmitter shall have the following internal relays for remote alarm annunciation: a.

Gas concentration medium.

b.

Gas concentration high.

c.

Gas concentration high-high.

d.

Fault relay.

5.

The three gas concentration alarm relays shall have normally open and normally closed contacts. The relays shall be energized as long as the gas concentration exceeds the set points adjustable with a hand-held controller.

6.

Normally open contact of the fault relay shall be open (relay energized) during normal operation. The relay shall operate in steady mode and in pulsed mode. a.

b.

Steady Mode: Relay shall be de-energized when any of the following occurs: (1)

Gas sensor is disconnected.

(2)

Transmitter internal problem.

(3)

Power off.

Pulsed Mode: Relay shall be de-energized for five seconds every minute when any of the following occurs: (1)

Under-range reading on the display.

HYDROGEN SULFIDE GAS DETECTION SYSTEM 60060986 - March 24, 2010

283336-2

(2)

C.

D.

Improper calibration.

7.

The transmitter shall be housed in a NEMA 4X enclosure.

8.

Provide a d-c power supply to power the required transmitters.

Hydrogen Sulfide Gas Calibration Kit 1.

The gas calibration kit shall provide flow-type calibration for 40-ppm hydrogen sulfide in nitrogen. Flow rate shall be preset, not to exceed 0.25 liter per minute.

2.

Provide a gas cylinder capable of providing 57 liters of calibration gas.

3.

The kit shall include a carrying case, gas cylinder regulator, hose, adapter for gas detectors, and infrared nonintrusive controller.

Hydrogen Sulfide Gas Detection System Manufacturers The hydrogen sulfide gas detection systems shall be the UltimaX Gas Monitor as manufactured by Mine Safety Appliances or equal.

E.

Spare Parts 1.

Provide to the Owner necessary spare parts of components required to maintain the system. Prior to final acceptance of work, provide a spare parts listing of necessary spare parts and quantities for review by the Owner's Representative. The spare parts shall include the following minimum requirements: MINIMUM SPARE PARTS LIST Part Description

2.

Quantity

Transmitter

1 each

Sensor

1 each

Deliver to the Owner the required spare parts upon final acceptance of the work. The spare parts shall not be used as replacement parts during the guarantee period.

PART 3 - EXECUTION A.

Installation Install components per manufacturer's recommendations.

B.

Field Testing After units have been energized and functions completely checked, set hydrogen sulfide alarm set points at 10 and 20 ppm. END OF SECTION

HYDROGEN SULFIDE GAS DETECTION SYSTEM 60060986 - March 24, 2010

283336-3

DIVISION 31 – EATHWORK 311100

CLEARING, STRIPPING, AND GRUBBING

312300

EARTHWORK

312316

TRENCHING, BACKFILLING, AND COMPACTING

312323

GRAVEL AND CRUSHED ROCK BASE FOR STRUCTURES

312500

EROSION AND SEDIMENTATION CONTROL

313219

FILTER FABRIC

317216

CASING PIPE – BORING AND JACKING

SECTION 311100

PART 1 A.

CLEARING, STRIPPING, AND GRUBBING

- GENERAL

Description This section describes the work included in clearing, stripping, grubbing, and preparing the project site for construction operations.

B.

C.

Related Work Specified Elsewhere 1.

Existing Conditions: General Provisions.

2.

Protecting Existing Underground Utilities: 020120.

3.

Earthwork: 312300.

4.

Trenching, Backfilling, and Compacting: 312316.

5.

Landscape Planting: 329010.

Clearing Remove and dispose of trees, snags, stumps, shrubs, brush, limbs, sticks, branches, and other vegetative growth. Remove rocks, tiles, and lumps of concrete. Remove all evidence of their presence from the surface. Remove and dispose of trash piles, and rubbish, and fencing. Protect structures and piping above and below ground, trees, shrubs, and vegetative growth and fencing which are not designated for removal.

D.

E.

Stripping 1.

Remove and dispose of organic sod, topsoil to a depth of 3 inches, grass and grass roots, and other objectionable material remaining after clearing from the areas designated to be stripped.

2.

Retain topsoil material onsite for dressing backfill areas before planting.

Grubbing After clearing and stripping, remove and dispose of wood or root matter, including stumps, logs, trunks, roots, or root systems greater than 1 inch in diameter or thickness to a depth of 12 inches below the ground surface.

CLEARING, STRIPPING, AND GRUBBING 60060986 - March 24, 2010

311100-1

PART 2 A.

- MATERIALS

Trees and Shrubbery Existing trees, shrubbery, and other vegetative material may not be shown in the drawings. Inspect the site as to the nature, location, size, and extent of vegetative material to be removed or preserved, as specified herein. Preserve in place trees that are specifically shown in the drawings and designated to be preserved.

B.

Preservation of Trees, Shrubs, and Other Plant Material 1.

Save and protect plant materials (trees, shrubbery, and plants) beyond the limits of clearing and grubbing from damage resulting from the work. No filling, excavating, trenching, or stockpiling of materials will be permitted within the drip line of these plant materials. The drip line is defined as a circle drawn by extending a line vertically to the ground from the outermost branches of a plant or group of plants. To prevent soil compaction within the drip line area, no equipment will be permitted within this area.

2.

When trees are close together, restrict entry to area within drip line by fencing. In areas where no fence is erected, protect the trunks of trees 2 inches or greater in diameter by encircling the trunk entirely with boards held securely by 12-gauge wire and staples. This protection shall extend from ground level to a height of 6 feet.

3.

Cut and remove tree branches where necessary for construction. Remove branches other than those required for a balanced appearance of any tree. Treat cuts with a tree sealant.

PART 3 A.

- EXECUTION

Clearing, Stripping, and Grubbing Areas and Limits 1.

Clear, strip, and grub excavation and embankment areas associated with new structures, slabs, walks, and roadways.

2.

Clear and strip stockpile areas.

CLEARING, STRIPPING, AND GRUBBING 60060986 - March 24, 2010

311100-2

3.

B.

Limits of clearing, stripping, and grubbing: a.

Excavation, Excluding Trenches: 5 feet beyond tops of cut slopes.

b.

Trench excavation for piping and electrical conduits: 3 feet from edge of trench.

c.

Earth Fill: 5 feet beyond toe of permanent fill as indicated in the drawings.

d.

Structures: 15 feet beyond footings.

e.

Streets, Roadways, and Parking Areas: 10 feet from toe of fill or top of cut.

f.

Sidewalks: 2 feet beyond edges.

g.

Landscaped Areas: 2 feet beyond areas designated to receive landscaping.

Disposal of Clearing and Grubbing Debris Do not burn combustible materials. Remove cleared and grubbed material from the worksite and dispose.

C.

Disposal of Strippings Remove stripped material and dispose offsite, except topsoil. END OF SECTION

CLEARING, STRIPPING, AND GRUBBING 60060986 - March 24, 2010

311100-3

SECTION 312300

PART 1 A.

EARTHWORK

- GENERAL

Description This section includes materials, testing, and installation of earthwork for excavations, fills, and embankments for roadways, structures, and sites and accessory items such as vapor barrier.

B.

C.

Related Work Specified Elsewhere 1.

Existing Conditions: General Provisions.

2.

Protecting Existing Underground Utilities: 020120.

3.

Leakage Testing of Hydraulic Structures: 030510.

4.

Concrete: 033000.

5.

Concrete Finishing and Curing: 033500.

6.

Cold Fluid Applied Waterproofing: 071416.

7.

Bentonite Geotextile Waterproofing: 071700.

8.

Clearing, Stripping, and Grubbing: 311100.

9.

Trenching, Backfilling, and Compacting: 312316.

10.

Gravel and Crushed Rock Base for Structures: 312323.

11.

Plumbing Systems: 220010

Submittals 1.

Submit excavation and shoring drawings for worker protection in accordance with the General Provisions.

2.

Submit six copies of a report from a testing laboratory verifying that the material conforms to the gradation specified.

3.

Submit dewatering plan including disposition of groundwater.

EARTHWORK 6006986 - April 6, 2010

312300-1

D.

E.

Testing for Compaction 1.

The Owner will test for compaction and relative density as described below.

2.

Determine the density of soil in place by the drive cylinder method, ASTM D2937 or by nuclear methods, ASTM D6938. Compaction tests will be performed for each lift or layer. If nuclear methods are used for in-place density determination, verify the accuracy with one drive cylinder test for every five nuclear tests taken.

3.

Determine the moisture-density relations of soils per ASTM D1557. This will be required for determination of percent compaction and moisture variation from optimum.

4.

Sample materials per ASTM D75.

5.

“Percent compaction” is the ration, expressed as a percentage, of the in-place dry density to the maximum dry density as determined by the Modified Proctor, ASTM D1557.

6.

Contractor shall pay the cost of any retesting of work not conforming to the specifications.

Disposal of Excess Materials Excess site excavated or wasted material shall be disposed of offsite by the Contractor at his expense. No prearranged disposal site or related permits have been determined or secured by the Owner.

F.

Measurement and Payment for Authorized Overexcavation Measurement of the volume of material for payment of authorized overexcavation will be made by taking cross sections after excavation and calculating the volume using the average end area method. The Owner will measure and calculate the volume. The volume for payment will be the gross volume, up to the elevation of the finished earthwork subgrade. A change order will be made as described in the General Provisions based upon a unit price according to actual time and material volume of earthwork. No payment will be made for unauthorized excavated and fill material exceeding the contract lines and grades.

PART 2 A.

- MATERIALS

Structural Fill 1.

Structural fill is material that is to be placed beneath structures to the limits indicated in the drawings. Material shall be free from organic matter, roots, debris, and rocks larger than 3 inches in the greatest dimension.

EARTHWORK 6006986 - April 6, 2010

312300-2

2.

B.

Sieve Size

Percent Passing By Weight

¾ inch

90-100

No. 200

0-5

Structural Backfill 1.

Structural backfill is material that is to be placed adjacent to and around piping and structures. Material shall be free from deleterious materials.

2.

Material shall have the following gradation:

3. C.

Material shall have the following gradation:

Sieve Size

Percent Passing By Weight

¾ inch

90-100

No. 200

0-10

Excavated onsite material may be used for structural backfill provided it conforms to the above specifications for structural backfill material.

Fill Fill material is material that is to be placed in locations that are not to be constructed as structural fill or structural backfill. Fill material shall be native material.

D.

Sand, Including Imported Sand for Pipe Zone and Pipe Base in Pipe Trenches 1.

Granular material free from clay balls, organic matter, and other deleterious substances and conforming to the following gradations:

EARTHWORK 6006986 - April 6, 2010

Sieve Size

Percent Passing By Weight

3/8 inch

100

No. 4

75 to 100

312300-3

E.

Sand-Cement Slurry Backfill Sand-cement slurry backfill shall consist of one sack (94 pounds) of Type I or II portland cement added per cubic yard of imported sand and sufficient water for workability.

F.

Water for Compaction Water shall be free of organic materials and shall have a pH of 7.0 to 9.0, a maximum chloride concentration of 500 mg/L, and a maximum sulfate concentration of 500 mg/L. Provide all water needed for earthwork. Provide temporary piping and valves to convey water from the source to the point of use. Provide any meters if the water is taken from a city, water district, or agency pipeline.

G.

Aggregate Base for Hydraulic Structures Aggregate base shall be No. 57 stone in accordance with the requirements of Section 901 of the Florida Department of Transportation Standard Specifications for Road and Bridge Construction, latest edition.

H.

Drain Rock Drain rock, or crushed rock, shall consist of hard, durable particles of stone, crushed to the required gradation below per AASHTO T-27 or ASTM C136, and shall be free from vegetable matter, lumps of clay, and other deleterious matter size:

I.

Percent Passing by Weight

1 inch

100

3/4 inch

90 to 100

1/2 inch

30 to 60

3/8 inch

0 to 20

No. 4

0 to 5

Filter Fabric 1.

2. J.

Sieve Size

Filter fabric shall be manufactured from polyester, nylon, or polypropylene material; shall be of nonwoven construction; and shall meet the following requirements: a.

Grab tensile strength (ASTM D1682): 100 lbs minimum for a 1-inch grip.

b.

Equivalent open sizes (UFGS-02373).

Filter fabric shall be MIRAFI, manufactured by Mirafi Inc., Charlotte, North Carolina; Horchst Fibers; or equal.

Vapor Barrier Underslab vapor barrier shall be polyethylene sheeting, minimum 6 mils, conforming to ASTM D4397

EARTHWORK 6006986 - April 6, 2010

312300-4

K.

Waterproofing As shown on the drawings, refer to Section 099750 Cold Fluid-Applied Waterproofing and Section 099755 Bentonite Geotextile Waterproofing.

PART 3 A.

- EXECUTION

Dewatering Provide and operate equipment adequate to keep excavations and trenches free of water. Dewater subgrade to a minimum of 3 feet below bottom of excavation. Remove water during period when concrete is being deposited, when pipe is being laid, and during the placing of backfill. Avoid settlement or damage to adjacent property. Dispose of water in a manner that will not damage adjacent property. When dewatering open excavations, dewater from outside the structural limits and from a point below the bottom of the excavation. Obtain and comply with discharge permit from Southwest Florida Water Management District (SWFWMD).

B.

C.

Excavation 1.

Excavations shall have sloping, sheeting, shoring, and bracing conforming with 29CFR1926 Subpart P-Excavations, OSHA requirements, and the General Provisions.

2.

Excavation is unclassified. Perform excavation regardless of the type, nature, or condition of the material encountered to accomplish the construction. Do not operate excavation equipment within 5 feet of existing structures or newly completed construction. Excavate with hand tools in these areas.

3.

After the required excavation has been completed, the Owner will observe the exposed subgrade to determine the need for any additional excavation. It is the intent that additional excavation is to be conducted in all areas within the influence of the structure where unacceptable subgrade materials exist at the exposed subgrade. Overexcavation shall include the removal of all such unacceptable material that exists directly beneath the structure or within a zone outside and below the structure defined by a line sloping at 1-horizontal to 1-vertical from 1 foot outside the edge of the footing. Refill the overexcavated areas with structural backfill material.

4.

The Contractor will not receive any additional payment for refill material used for his convenience.

Limits of Foundation Excavation Excavate to the depths and widths needed to accomplish the construction. Allow for forms, working space, structural backfill, and site grading. Do not excavate for footings, slabs, or conduits below elevations indicated. Unless unacceptable material is encountered and overexcavation is authorized by the Owner, backfill overexcavations with compacted structural backfill material. Correct cuts below grade by trimming

EARTHWORK 6006986 - April 6, 2010

312300-5

adjoining areas and creating a smooth transition. The Contractor shall bear all costs for correcting unauthorized overexcavated areas. D.

E.

F.

G.

Preparation of Foundation Subgrade 1.

The finished subgrade shall be within a tolerance of ±0.08 of a foot of the grade and cross section indicated, shall be smooth and free from irregularities, and shall be at the specified relative compaction. The subgrade shall extend over the full width and extend 1 foot beyond the edge of the foundations.

2.

Compact the top 12 inches of the subgrade to 98% relative compaction. Recompaction will not be required if rock is exposed at final subgrade.

3.

Remove soft material encountered and replace with structural backfill. Fill holes and depressions to the required line, grade, and cross sections with structural backfill.

4.

If rock is encountered at final grade, overexcavate to a depth of 6 inches and place structural backfill to establish final grade.

Preparation for Placing Fill or Backfill 1.

After excavation of existing material or removal of unacceptable material at the exposed subgrade, scarify the final subgrade surface to a depth of 12 inches and compact to a minimum of 98% compaction of the maximum density as determined by the modified proctor, ASTM D1557.

2.

Remove foreign materials and trash from the excavation before placing any fill material. Obtain the specified compressive strength and finish of concrete work per Sections 033000 and 033500 before backfilling.

Placing and Compacting Fill and Structural Fill 1.

Use structural backfill material for all fill and structural fill.

2.

Place in maximum 12-inch lifts and compact each lift to 98% compaction.

3.

Where fill is to be constructed on slopes steeper than 3:1, bench the fill into competent undisturbed materials as the fill progresses up the slope. Benches shall be sloped at least 2% into the slope and shall be of a width at least equal to the height of fill lift.

Placing and Compacting Structural Backfill 1.

Place structural backfill material around piping, structures, channels, and other areas, including authorized overexcavation areas, to the lines and grades shown or specified. Do not exceed loose lifts of 12 inches.

2.

Limits of Structural Backfill: Limits of structural backfill shall be 1.0 feet from edge of footing and shall extend at a 1:1 slope to the finish grade.

EARTHWORK 6006986 - April 6, 2010

312300-6

H.

3.

Compact each lift to 98% compaction, unless otherwise shown in the drawings. Stop structural backfill at least 6 inches below finished grade in all areas where topsoil is to be placed.

4.

Backfill around concrete structures as specified in Section 033000.

5.

Do not operate earthmoving equipment within 5 feet of walls of concrete structures. Place and compact backfill adjacent to concrete walls with hand-operated tampers or other equipment that will not damage the structure.

6.

Backfill adjacent to water-holding basins and channels only after leakage tests have been conducted as specified in Section 030510.

Moisture Control During the compacting operations, maintain optimum practicable moisture content required for compaction purposes in each lift of the material. Maintain uniform moisture content throughout the lift. Insofar as practicable, add water to the material at the site of excavation. Supplement by sprinkling the material. At the time of compaction, the water content of the material shall be at optimum water content or within 2 percentage points above optimum. Aerate material containing excessive moisture by blading, discing, or harrowing to hasten the drying process.

I.

Site Grading Perform earthwork to the lines and grades shown in the drawings. Shape, trim, and finish slopes of channels to conform to the lines, grades, and cross sections as shown. Remove exposed roots and loose rocks exceeding 3 inches in diameter. Round tops of banks to circular curves of not less than a 6-foot radius. Neatly and smoothly trim rounded surfaces. Do not overexcavate and backfill to achieve the proper grade.

EARTHWORK 6006986 - April 6, 2010

312300-7

J.

Vapor Barrier Installation 1.

Place vapor barrier with adjacent sheets bonded per manufacturer's requirements as follows.

2.

Lay vapor barrier sheets directly over the compacted subgrade just before sand cushion is placed and concrete is poured. Carefully install to avoid puncture or tear. Patch punctures and tears occurring during subsequent operations. Lap edges at least 4 inches and lap end joints at least 6 inches, with laps continuously sealed with tape. Carry barrier over any pipes laid on the fill and seal in waterproof manner to any pipes or conduits which penetrate the fill. Turn up membrane a minimum of 2 inches at the edges and secure to exterior wall foundations or footings with adhesive. Apply vapor barrier to walls with the same adhesive. Do not place stakes through vapor barrier membranes for screeding of concrete slabs. END OF SECTION

EARTHWORK 6006986 - April 6, 2010

312300-8

SECTION 312316

PART 1 A.

TRENCHING, BACKFILLING, AND COMPACTING

- GENERAL

Description This section includes materials, testing, and installation for pipeline and ductbank trench excavation, backfilling, and compacting.

B.

C.

D.

Related Work Specified Elsewhere 1.

Existing Conditions: General Provisions.

2.

Protecting Existing Underground Utilities: 020120.

3.

Concrete: 033000.

4.

Clearing, Stripping, and Grubbing: 311100.

5.

Earthwork: 312300.

6.

Gravel and Crushed Rock Base for Structures: 312323.

7.

Concrete Curbs, Gutters, and Sidewalks: 321613.

8.

Pressure Testing of Piping: 400515.

9.

Equipment, Piping Duct, and Valve Identification: 400775.

Submittals 1.

Submit six copies of a report from a testing laboratory verifying that material conforms to the specified gradations or characteristics for pea gravel, granular material, imported sand, rock refill for foundation stabilization, and water.

2.

Submit method(s) of compaction including removal sequence of shoring where used.

3.

Submit mix design for controlled low-strength material (CLSM).

Testing for Compaction 1.

E.

The Owner will test for compaction as described in Section 312300.

Pavement Zone The pavement zone includes the asphalt concrete and aggregate base pavement section placed over the trench backfill.

TRENCHING, BACKFILLING, AND COMPACTING 60060986 - April 6, 2010

312316-1

F.

Street Zone The street zone is the top 30 inches of the trench immediately below the pavement zone in paved areas. Where the depth of cover over the pipe does not permit the full specified thickness of the street zone, construct a thinner street zone, extending from the top of the pipe zone to the bottom of the pavement zone.

G.

Trench Zone The trench zone includes the portion of the trench from the top of the pipe zone to the bottom of the street zone in paved areas or to the existing surface in unpaved areas. If the resulting trench zone is less than 24 inches thick, the street zone shall extend to the top of the pipe zone and there shall be no separate trench zone.

H.

Pipe Zone The pipe zone shall include the full width of trench from the bottom of the pipe or conduit to a horizontal level above the top of the pipe, as specified below. Where multiple pipes or conduits are placed in the same trench, the pipe zone shall extend from the bottom of the lowest pipe to a horizontal level above the top of the highest or topmost pipe. Thickness of pipe zone above the highest top of pipe shall be as follows unless otherwise shown in the drawings or otherwise described in the specifications for the particular type of pipe installed.

I.

Pipe Diameter

Thickness of Pipe Zone Above Top of Pipe

6 inches or smaller

6 inches

8 inches and larger

10 inches

Pipe Base or Bedding The pipe base or bedding shall be defined as a layer of material immediately below the bottom of the pipe or conduit and extending over the full trench width in which the pipe is bedded. Thickness of pipe base shall be as follows unless otherwise shown in the drawings or otherwise described in the specifications for the particular type of pipe installed. Pipe Diameter Thickness of Pipe Base

PART 2 A.

Smaller than 4 inches

3 inches

4 inches through 16 inches

4 inches

18 inches and larger

6 inches

- MATERIALS

Pea Gravel Pea gravel shall be rounded gravel graded with less than 10% passing a No. 200 sieve, less than 50% passing a No. 4 sieve, and having a maximum particle size as follows:

TRENCHING, BACKFILLING, AND COMPACTING 60060986 - April 6, 2010

312316-2

Maximum Particle Size (inches)

Type of Pipe

B.

Ductile iron

3/4

Fiberglass

3/4

VCP

3/4

Granular Material for Imported Fill--Street and Trench Zones Granular material or granular soil for backfill used above the pipe zone shall be lean bank-run or pit-run gravel, or native soil. The maximum particle size shall be 2 inches. A maximum of 10% shall pass a No. 200 sieve.

C.

D.

Native Earth Backfill--Street and Trench Zones 1.

Native earth backfill used above the pipe zone shall be excavated fine-grained materials free from roots, debris, rocks larger than 3 inches, asbestos, organic matter, clods, clay balls, broken pavement, and other deleterious materials. Less than 10% shall pass a No. 200 sieve. At least 40% shall pass a No. 4 sieve. The coarser materials shall be well distributed throughout the finer material.

2.

Backfill materials that are obtained from trench excavated materials to the extent such material is available may be either screened directly into the trench or screened during the trenching operation if needed to meet specifications. If screened during trenching, the material shall be maintained free of unscreened material during the handling and backfilling process. Backfill shall be moisture conditioned to within approximately 2% of the optimum moisture content prior to being placed in trench. When excavating rock it shall be separated out and not used for backfill.

Imported Sand--Pipe Zone and Pipe Base 1.

Imported sand used in the pipe zone or for the pipe base shall have the following gradation: Sieve Size

Percent Passing By Weight

3/8 inch

2. E.

100

No. 4

75

to

100

No. 200

0

to

10

Imported sand shall have a saturated resistivity greater than 1,000 ohm-cm, a neutral pH, and chlorides less than 100 ppm.

Gravel and Crushed Rock--Pipe Zone and Pipe Base 1.

Gravel or crushed rock material shall conform to the Florida DOT Section 901, "Coarse Aggregate," Grade 357 and shall meet the following gradation:

TRENCHING, BACKFILLING, AND COMPACTING 60060986 - April 6, 2010

312316-3

Designated Gravel Size 1-1/2-Inch

1-Inch

3/4-Inch

3/8-Inch

Percent Passing

Percent Passing

Percent Passing

Percent Passing

-

-

-

-

-

Sieve Sizes 2 inches 1-1/2 inches

90 to 100

1 inch

20 to

55

90 to 100

3/4 inch

0 to

15

30 to

60

1/2 inch

-

0 to

20

3/8 inch

0 to

100

5

-

No. 4

-

0 to

No. 8

-

-

2. F.

100

5

100

-

90

to 100

-

30

to

60

100

0

to

20

90 to 100

0

to

5

-

30 to

60

0 to

10

Use 3/4 -inch size unless indicated otherwise in the drawings.

Sand-Cement Slurry Backfill--Pipe Zone Sand-cement slurry backfill shall consist of one sack (94 pounds) of Type I or II portland cement added per cubic yard of imported sand and sufficient water for workability.

G.

Rock Refill for Foundation Stabilization Rock refill shall be crushed or natural rock, having the following gradation: Sieve Size 3 inches

H.

Percent Passing By Weight 100

1-1/2 inches

70 to 100

3/4 inch

60 to 100

No. 4

25 to 55

No. 30

10 to 30

No. 200

0 to 10

Concrete for Pipe Encasement and Thrust Blocks 1.

Concrete for pipe encasement and thrust blocks shall be Class C per Section 033000, unless otherwise shown in the drawings.

2.

Provide thrust blocks at fittings in pipe having rubber gasket bell-and-spigot or unrestrained mechanical joints. Provide thrust blocks at fittings for FRP pipe, regardless of the type of joint utilized. Do not provide thrust blocks for steel pipe having welded, flanged, or butt-strap joints unless detailed in the drawings or required in the detailed piping specification.

TRENCHING, BACKFILLING, AND COMPACTING 60060986 - April 6, 2010

312316-4

3.

See the details in the drawings for thrust block sizes. Install thrust blocks based on the test pressures given in the Piping Schedule. Size thrust blocks in accordance with the following table: Pipe Test Pressure (psi)

4.

I.

Use Thrust Block Sizing for

0

to

25

25 psi

26

to

50

50 psi

51

to

100

100 psi

101

to

150

150 psi

151

to 200

200 psi

Dimensions of thrust blocks for pipes smaller than 6 inches shall be the same as the dimensions shown for 6-inch pipe, unless specific dimensions are shown in the drawings.

Water for Compaction See Section 312300. Water shall be free of organic materials injurious to the pipe coatings.

J.

Underground Plastic Warning Tape for Metal Pipe See Section 400775.

K.

Underground Detectable Metallic Pipe Warning Tape See Section 400775.

PART 3 A.

- EXECUTION

Sloping, Sheeting, Shoring, and Bracing of Trenches Trenches shall have sloping, sheeting, shoring, and bracing conforming with 29CFR1926, Subpart P--Excavations, OSHA requirements, and the General Provisions

B.

Sidewalk, Pavement, and Curb Removal Cut bituminous and concrete pavements regardless of the thickness and curbs and sidewalks prior to excavation of the trenches with a pavement saw or pavement cutter. Width of the pavement cut shall be at least equal to the required width of the trench at ground surface. Haul pavement and concrete materials from the site. Do not use for trench backfill.

C.

Trench Excavation 1.

Excavate the trench to the lines and grades shown in the drawings with allowance for pipe thickness, sheeting and shoring if used, and for pipe base or special

TRENCHING, BACKFILLING, AND COMPACTING 60060986 - April 6, 2010

312316-5

bedding. If the trench is excavated below the required grade, refill any part of the trench excavated below the grade at no additional cost to the Owner with pea gravel of the type specified for the type of pipe, granular material, or imported sand. Place the refilling material over the full width of trench in compacted layers not exceeding 6 inches deep to the established grade with allowance for the pipe base or special bedding. 2.

D.

E.

F.

Trench widths in the pipe zone shall be as shown in the drawings. If no details are shown, maximum width shall be 18 inches greater than the pipe outside diameter. Comply with 29CFR Part 1926 Subpart P--Excavations. Trench width at the top of the trench will not be limited except where width of excavation would undercut adjacent structures and footings. In such case, width of trench shall be such that there is at least 2 feet between the top edge of the trench and the structure or footing.

Trench Excavation in Backfill and Embankment Areas 1.

Construct and compact the embankment to an elevation of 1 foot minimum over the top of the largest pipe or conduit to be installed.

2.

Excavate trench in the compacted backfill or embankment.

Location of Excavated Material 1.

During trench excavation, place the excavated material only within the working area. Do not obstruct any roadways or streets. Do not place trench spoil over pipe, buried utilities, manholes, or vaults. Conform to federal, state, and local codes governing the safe loading of trenches with excavated material.

2.

Remove and store excavated topsoil separately. Replace topsoil in the top 12 inches of the trench zone.

3.

Locate trench spoil piles at least 15 feet from the tops of the slopes of trenches. Do not operate cranes and other equipment on the same side of the trench as the spoil piles.

Length of Open Trench Limit the length of open trench to 750 feet in advance of pipelaying or amount of pipe installed in one working day. Complete backfilling and temporary or first layer paving not more than 250 feet in the rear of pipelaying.

G.

Dewatering Provide and maintain means and devices to remove and dispose of water entering the trench excavation during the time the trench is being prepared for the pipelaying, during the laying of the pipe, and until the backfill at the pipe zone has been completed. These provisions shall apply during both working and nonworking hours, including lunch time, evenings, weekends, and holidays. Dispose of the water in a manner to prevent damage to adjacent property and in accordance with regulatory agency requirements. Do not drain trench water through the pipeline under construction.

TRENCHING, BACKFILLING, AND COMPACTING 60060986 - April 6, 2010

312316-6

H.

I.

Foundation Stabilization 1.

After the required excavation has been completed, the Owner or Owner’s representative will inspect the exposed subgrade to determine the need for any additional excavation. It is the intent that additional excavation be conducted in all areas where unacceptable materials exist at the exposed subgrade. Overexcavation shall include the removal of all such unacceptable material that exist directly beneath the pipeline to a width 24 inches greater than the pipe outside diameter and to the depth required.

2.

Place filter fabric on the bottom of the trench and up the sides a sufficient height to retain refill material. Backfill the trench to subgrade of base with refill material for foundation stabilization. Place the foundation stabilization material over the full width of the excavation and compact in layers not exceeding 6 inches deep to the required grade.

3.

Refill used by the Contractor for his convenience will not be cause for any additional payment.

Installing Buried Piping 1.

Grade the bottom of the trench to the line and grade to which the pipe is to be laid, with allowance for pipe thickness. Remove hard spots that would prevent a uniform thickness of bedding. Place the specified thickness of pipe base material over the full width of trench. Grade the top of the pipe base ahead of the pipelaying to provide firm, continuous, uniform support along the full length of pipe, and compact to the relative compaction specified herein. Before laying each section of the pipe, check the grade and correct any irregularities.

2.

Excavate bell holes at each joint to permit proper assembly and inspection of the entire joint. Fill the area excavated for the joints with the bedding material specified or indicated in the drawings for use in the pipe zone. If no bedding material is specified or indicated, use imported sand.

3.

Inspect each pipe and fitting before lowering the buried pipe or fitting into the trench. Inspect the interior and exterior protective coatings. Patch damaged areas in the field with material recommended by the protective coating manufacturer. Clean ends of pipe thoroughly. Remove foreign matter and dirt from inside of pipe and keep clean during and after installation.

4.

Handle pipe in such a manner as to avoid damage to the pipe. Do not drop or dump pipe into trenches under any circumstances.

5.

When installing pipe, do not deviate more than 1 inch from line or 1/4 inch from grade. Measure elevation at the pipe invert.

6.

After pipe has been bedded, place pipe zone material simultaneously on both sides of the pipe, in maximum 6-inch lifts, keeping the level of backfill the same on each side. If no pipe zone material is specified or indicated, use imported sand. Carefully place the material around the pipe so that the pipe barrel is completely supported and no voids or uncompacted areas are left beneath the pipe. Use particular care in

TRENCHING, BACKFILLING, AND COMPACTING 60060986 - April 6, 2010

312316-7

placing material on the underside of the pipe to prevent lateral movement during subsequent backfilling.

J.

7.

Compact each lift to the relative compaction specified herein.

8.

Push the backfill material carefully onto the backfill previously placed in the pipe zone. If no backfill material is otherwise specified or indicated, use granular material for backfill. Do not permit free-fall of the material until at least 2 feet of cover is provided over the top of the pipe. Do not drop sharp, heavy pieces of material directly onto the pipe or the tamped material around the pipe. Do not operate heavy equipment or a sheepsfoot wheel mounted on a backhoe over the pipe until at least 3 feet or one-half of the internal diameter, whichever is greater, of backfill has been placed and compacted over the pipe.

9.

When the pipelaying is not in progress, including the noon hours, close the open ends of pipe. Do not allow trench water, animals, or foreign material to enter the pipe.

10.

Keep the trench dry until the pipelaying and jointing are completed.

Backfill Compaction 1.

Unless otherwise shown in the drawings or otherwise described in the specifications for the particular type of pipe installed, percent compaction in pipe trenches shall be as follows: a.

Pipe Zone: 95% of modified proctor.

b.

Backfill in Trench Zone Not Beneath Paving: 90% of modified proctor. Compact backfill within embankment above the pipe zone to the same relative compaction as the adjacent embankment as specified in Section 312300.

c.

Backfill in Trench Zone to Street Zone in Paved Areas: 95% of modified proctor.

d.

Backfill in Street Zone in Paved Areas: 98% of modified proctor.

e.

Rock Refill for Foundation Stabilization: 95% of modified proctor.

f.

Refill for Overexcavation: 95% of modified proctor.

2.

Compact trench backfill to the specified relative compaction. Compact by using mechanical compaction or hand tamping. Do not use high-impact hammer-type equipment except where the pipe manufacturer warrants in writing that such use will not damage the pipe.

3.

Compact material placed within 12 inches of the outer surface of the pipe by hand tamping only.

TRENCHING, BACKFILLING, AND COMPACTING 60060986 - April 6, 2010

312316-8

4. K.

Do not use any axle-driven or tractor-drawn compaction equipment within 5 feet of building walls, foundations, and other structures.

Material Replacement Remove and replace any trenching and backfilling material that does not meet the specifications, at the Contractor's expense.

L.

Placing Sand-Cement Slurry Backfill Place sand-cement slurry backfill in a uniform manner that will prevent voids in or segregation of the material. Remove foreign material that falls into the excavation or trench. Do not commence backfilling over or place any material over the slurry cement backfill until at least four hours after placing the sand-cement slurry. END OF SECTION

TRENCHING, BACKFILLING, AND COMPACTING 60060986 - April 6, 2010

312316-9

SECTION 312323 GRAVEL AND CRUSHED ROCK BASE FOR STRUCTURES

PART 1 A.

- GENERAL

Description This includes materials, testing, and installation of gravel and crushed rock bases for structures such as manholes and vaults. See plans for details on over excavation and rock fill under major structures.

B.

C.

Related Work Specified Elsewhere 1.

Concrete: 033000.

2.

Earthwork: 312300.

Submittals Submit six copies of a report from a testing laboratory verifying that material conforms to the specified gradations or characteristics.

D.

Testing for Compaction 1.

PART 2 A.

The Owner will test for compaction as described in Sections 312300 and 312316. - MATERIALS

Crushed Rock Crushed rock base shall be No. 89 stone conforming to Section 901, "Coarse Aggregate" of the Florida Department of Transportation Standard Specifications for Road and Bridge Construction.

PART 3 A.

- EXECUTION

Placement of Crushed Rock or Gravel 1.

Place crushed rock or gravel base beneath structures where shown in the drawings, 12 inches thick unless otherwise indicated. Excavate below the required grade for the bottom of the structure and refill with crushed rock or gravel as specified above. The rock base shall extend a minimum of 12 inches beyond the structure base, floor slab, or footing.

GRAVEL AND CRUSHED ROCK BASE FOR STRUCTURES 60060986 - April 6, 2010

312323-1

2.

Compact the gravel with heavy vibratory place compactor or walk-behind roller. Make a minimum of 3 passes over the material with each pass overlapping the previous pass by 30 percent. After compaction, each lift should be inspected to ensure that it is firm and unyielding.

3.

Place base material in maximum lifts of 6 inches. END OF SECTION

GRAVEL AND CRUSHED ROCK BASE FOR STRUCTURES 60060986 - April 6, 2010

312323-2

SECTION 312500 EROSION AND SEDIMENTATION CONTROL PART 1 – GENERAL A.

Description The work specified in this Section consists of measures required to control erosion on the project and in areas outside the project area where work is accomplished in conjunction with the project, so as to prevent pollution of water, detrimental effects of public or private property adjacent to the project area and damage to work on the project. These measures will consist of construction and maintenance of temporary erosion control features or, where practical, the construction and maintenance of permanent erosion control features. Effective May 1 2003, construction sites that will result in a disturbance of one acre or more are required to seek coverage from FDEP under the Generic Permit for Stormwater Discharge from Large and Small Construction Activities (DEP Document 62-621.300(4)(a) Accordingly, the Contractor shall be required to submit a Notice of Intent (NOI) along with the application fee to the FDEP Stormwater Notices Center to use the Generic Construction NPDES permit. This will also require the Contractor to develop and implement a Stormwater Pollution Prevention Plan (SWPPP) for this project; the requirements of which shall be followed by the Contractor for the duration of the project. Note that the project will be subject to inspection by the FDEP or their subcontractors and daily and weekly reports shall be maintained by the Contractor as required by the regulations.

B.

Control of Contractor's Operations Which May Result in Water Pollution 1.

Take sufficient precautions to prevent pollution of streams, canals, lakes, reservoirs, and other water impoundments, with fuels, oils, bitumens, calcium chloride, or other harmful materials. Conduct and schedule operations so as to avoid or otherwise minimize pollution or siltation of such streams, etc. and to avoid interference with movement of migratory fish. Do not dump the residue from dust collectors or washers into any water body.

2.

Construction operations in rivers, streams, lakes, tidal waters, reservoirs, canals, and other impoundments shall be restricted to those areas where it is necessary to perform filling or excavation to accomplish the work shown in the Contract Documents and to those areas which must be entered to construct temporary or permanent structures. As soon as conditions permit, promptly clear rivers, streams, and impoundments of all obstructions placed therein or caused by construction operations.

3.

Except as necessary for construction, do not deposit excavated material in rivers, streams, canals, or impoundments, or in a position close enough thereto, to be washed away by high water or runoff.

EROSION AND SEDIMENTATION CONTROL 60060986 - March 24, 2010

312500-1

C.

4.

Where pumps are used to remove highly turbid waters from enclosed construction areas such as cofferdams or forms, treat the water prior to discharge into State waters. Pump the water into grassed swales, appropriate vegetated areas, or sediment basins, or confine it by an appropriate enclosure such as siltation curtains when other methods are not considered appropriate. Do not contaminate state waters.

5.

Do not disturb lands or waters outside the limits of construction, except as may be found necessary to complete the work with written permission of the City.

Start of Work Do not start work until erosion control measures are in place.

PART 2 - PRODUCTS A.

General 1.

No testing of materials used in construction of temporary erosion control features will be required.

2.

Materials used for the construction of the temporary erosion and sedimentation control measures not to be incorporated into the completed project may be new or used.

PART 3 - EXECUTION A.

B.

General 1.

Temporary erosion control features shall consist of, but not be limited to, temporary grassing, temporary sodding, temporary mulching, sandbagging, slope drains, sediment basins, artificial coverings, berms, baled hay or straw, floating silt barriers, staked silt barriers and staked silt fences. Design details for some of these items may be found in the Water Quality Section of the applicable edition of the FDOT Roadway and Traffic Design Standards.

2.

Incorporate permanent erosion control features into the project at the earliest practical time. Correct conditions, using temporary measures, that develop during construction to control erosion prior to the time it is practical to construct permanent control features.

3.

Construct temporary and permanent erosion and sediment control measures to prevent the pollution of adjacent water ways in conformance with the laws, rules and regulations of Federal, State and local agencies.

Installation 1.

Temporary Grassing: This work shall consist of furnishing and placing grass seed in accordance with Section 329210 -- Hydro Seeding.

EROSION AND SEDIMENTATION CONTROL 60060986 - March 24, 2010

312500-2

2.

Temporary Mulching: This work shall consist of furnishing and applying a two-inch to four-inch thick blanket of straw or hay mulch and then mixing or forcing the mulch into the top two inches of the soil in order to temporarily control erosion. Only undecayed straw or hay, which can readily be cut into the soil, shall be used. Other measures for temporary erosion control such as hydro-mulching, chemical adhesive soil stabilizers, etc., may be substituted for mulching with straw or hay. When permanent grassing operations begin, temporary mulch materials shall be plowed under in conjunction with preparation of the ground.

3.

Sandbagging: This work shall consist of furnishing and placing sandbags in configurations, so as to control erosion and siltation.

4.

Slope Drains: This work shall consist of constructing slope drains, utilizing pipe, fiber mats, rubble, cement concrete, asphaltic concrete plastic sheeting, or other acceptable materials, in accordance with the details shown in FDOT's Roadway and Traffic Design Standards or as may be approved as suitable to adequately perform the intended function.

5.

Sediment Basins: Sediment basins shall be constructed in accordance with the details shown in FDOT's Roadway and Traffic Design Standards or as suitable to adequately perform the intended function. Sediment basins shall be cleaned out as necessary.

6.

Artificial Coverings: This work shall consist of furnishing and applying fiber mats, netting, plastic sheeting, or other approved covering to the earth surfaces.

7.

Berms: This work shall consist of construction of temporary earth berms to divert the flow of water from an erodible surface.

8.

Baled Hay or Straw: a.

This work shall consist of construction of baled hay or straw dams to protect against downstream accumulations of silt. The baled hay or straw dams shall be constructed in accordance with the details shown in FDOT's Roadway and Traffic Design Standards.

b.

The dam shall be placed so as to effectively control silt dispersion under conditions present on this project. Alternate solutions and usage of materials may be used if approved.

9.

Temporary Silt Fences and Staked Silt Barriers: This work shall consist of furnishing, installing, maintaining and removing staked turbidity barriers in accordance with the manufacturer's directions, these specifications and the details as shown in FDOT's Roadway and Traffic Design Standards, latest edition.

10.

Floating Silt Barriers: This work shall consist of installing, maintaining, and removal of floating silt barriers to contain turbidity that may occur as the result of dredging, filling, or other construction activities in waters of the State. The type barrier used, the deployment and maintenance of the barrier will be such as to minimize dispersion of turbid waters from the construction site. Alternate methods or materials may be used provided that compliance with applicable permit conditions and State water quality standards are maintained.

EROSION AND SEDIMENTATION CONTROL 60060986 - March 24, 2010

312500-3

C.

Removal of Temporary Erosion Control Features In general, remove or incorporate into the soil any temporary erosion control features existing at the time of construction of the permanent erosion control features in such a manner that there will be no detrimental effect.

D.

Maintenance of Erosion Control Features General: Provide routine maintenance of permanent and temporary erosion control features until the project is completed and accepted.

E.

Protection During Suspension of Contract Time In the event that it is necessary that the construction operations be suspended for any appreciable length of time, shape the top of the earthwork in such a manner as to permit runoff of rainwater and construct earth berms along the top edges of embankments to intercept runoff water. Provide temporary slope drains to carry runoff from cuts and embankments which are located in the vicinity of rivers, streams, canals, lakes, and impoundments. Should such preventive measures fail, immediately take such other action as necessary to effectively prevent erosion and siltation. END OF SECTION

EROSION AND SEDIMENTATION CONTROL 60060986 - March 24, 2010

312500-4

SECTION 313219

PART 1 A.

FILTER FABRIC

- GENERAL

Description This section includes materials and installation of filter fabric and its maintenance until the filter material, bedding material, crushed rock or rip rap cover is completed.

B.

C.

Related Work Specified Elsewhere 1.

Clearing, Stripping, and Grubbing: 311100.

2.

Earthwork: 312300.

3.

Trenching, Backfilling, and Compacting: 312316.

4.

Drainage and Plumbing Piping: Div. 22.

Submittals 1.

Submit shop drawings in accordance with the General Provisions, Section 013300 and the following.

2.

Submit manufacturer's catalog data and a sample of the filter fabric.

3.

Submit manufacturer's recommended installation instructions and details.

4.

Submit mill certificate or affidavit signed by a legally authorized official from the company manufacturing the fabric. The mill certificate or affidavit shall attest that the fabric meets the chemical, physical, and manufacturing requirements stated in this specification.

PART 2 A.

- MATERIALS

Manufacturers

FILTER FABRIC 60060986 - March 24, 2010

313219-1

Products - Underdrains (AOS) Product

Catalog No.

AOS

Woven/ Non

Hoechst Fibers Ind. P.O. Box 5887 Spartanburg, SC

Trevira Spunbond

1115

70+

Non

Hoechst Fibers Ind.

Trevira Spunbond

1120

50-70

Non

Hoechst Fibers Ind.

Trevira Spunbond

1127

70-100

Non

Hoechst Fibers Ind.

Trevira Spunbond

1135

70-100

Non

Hoechst Fibers Ind.

Trevira Spunbond

1145

100-120

Non

Hoechst Fibers Ind.

Trevira Spunbond

1155

120+

Non

Mirafi

140N

100+

Non

Bradley Materials Co., Inc. P.O. Box 254 Valparaiso, FL 32580

Terram

1000

120

Non

Bradley Materials

Terram

1500

200

Non

Bradley Materials

Terram

2000

230

Non

Bradley Materials

Terram

3000

270

Non

Bradley Materials

Terram

4000

400

Non

Manufacturer/Supplier

Celanese Fibers Marketing Co. P.O. Box 1414 Charlotte, NC 28232

Products - Underdrains (AOS) Manufacturer/Supplier Hoechst Fibers Ind. P.O. Box 5887 Spartanburg, SC Nicholon/Mirafi Group Suite 500 3500 Parkway Lane Norcross, GA

Product

Catalog No.

AOS

Woven/ Non

Trevira Spunbond

1114

70-100

Non

Mirafi

140N

70-100

Non

Catalog No.

AOS

Woven/ Non

70

Woven

Products – Riprap Manufacturer/Supplier Carthage Mills 1821 Summit Road Cincinnati, OH 45327

FILTER FABRIC 60060986 - March 24, 2010

Product Poly-Filter X

313219-2

Bradley Materials

Filterweave

70-100

70/100

Woven

Bradley Materials

Filterweave

40-80

40-80

Woven

Bradley Materials

Filterweave

40

40

Woven

Bradley Materials

Filterweave

50

50

Woven

Bradley Materials

Filterweave

50

50

Woven

B.

Filter Fabric 1.

Filter fabric shall be a pervious sheet of woven or nonwoven plastic yarn. The filter fabric shall provide an apparent opening size (AOS) per ASTM D4751 no finer than the U.S. Standard Sieve No. 200 and no coarser than the U.S. Standard Sieve No. 40.

2.

The plastic yarn shall meet the physical requirements specified in AASHTO M288.

3.

Geotextiles shall meet the properties specified in AASHTO M288 as follows: Service

C.

Requirements

Stabilization

Table 4

Permanent erosion control

Table 5

Temporary silt fence

Table 6

Paving fabric

Table 7

4.

Manufacture the fabric into a width not less than 10 feet.

5.

Filter fabric shall not act as a wicking agent.

Securing Pins Securing pins shall be 3/16-inch-diameter steel, pointed at one end, and fabricated with a head to retain a steel washer having an outside diameter of no less than 1.5 inches. The lengths of the pins shall be no less than 12 inches.

PART 3 A.

- EXECUTION

Shipment, Storage, and Handling 1.

Store and handle geotextiles in accordance with ASTM A4753 and the following.

2.

Protect the fabric from direct sunlight, ultraviolet rays, temperatures greater than 140°F, mud, dirt, dust, and debris at all times during shipment and storage. To the extent possible, wrap the fabric in a heavy-duty protective covering.

3.

Store fabric on clean, dry surfaces, free of foreign substances such as grease, oil, paint, epoxy, cement, or any other substances which would have a deleterious effect on the fabric. When stored in outside areas, keep fabric 1 foot minimum above ground level. Keep the fabric in its protective covering until it is ready for

FILTER FABRIC 60060986 - March 24, 2010

313219-3

installation. Cover opened rolls by a waterproof cover. Do not use hooks, tongs, or other sharp tools or instruments when handling fabric. Fabric may be unloaded or handled in one of the following ways:

B.

a.

By placing slings under the rolls.

b.

By using a pole inserted through a hollow core, provided the pole extends 1 foot minimum beyond each end of the core and lifting and handling devices are attached to only that portion of the pole located outside the ends of the core.

c.

By hand.

Protection During Installation Protect the geotextile during installation from clogging, tears, and other damage. Provide ballast (e.g., sand bags) to prevent uplift by wind. Do not leave the geotextile uncovered for more than 14 days after installation.

C.

Subgrade Preparation Prepare the surface to receive fabric to a smooth condition free of sharp objects, obstructions, depressions, debris, and soft or low-density pockets of material.

D.

E.

Placement of Geotextile in Channels, Shorelines, and Trenches 1.

Install in accordance with AASHTO M288, Appendices A1 and A3 except as modified below.

2.

Place filter fabric in the manner and at the locations shown in the drawings. Do not use fabric with defects, rips, holes, flaws, deterioration, or damage of any nature.

3.

Handle and place filter fabric in accordance with the manufacturer's recommendations. Stretch, align, and place the fabric in a wrinkle-free manner.

4.

Place fabric with the long dimension perpendicular to the centerline of the channel and lay smooth and free of tension, stress, folds, wrinkles, or creases. Place the strips to provide a minimum width of 12 inches of overlap for each joint.

5.

Insert securing pins with washers through both strips of overlapped fabric at not greater than 3-foot intervals along a line through the midpoint of the overlap.

6.

Install additional pins regardless of location to prevent any slippage of the filter fabric. Place the fabric so that the upstream strip of fabric will overlap the downstream strip. Each securing pin shall be pushed through the fabric until the washer bears against the fabric and secures it firmly to the foundation.

Covering With Filter Rock 1.

Schedule the work so that the covering of the fabric with the planned thickness of the specified material is accomplished within 30 days after placement of the fabric. Failure to comply shall require replacement of fabric.

FILTER FABRIC 60060986 - March 24, 2010

313219-4

2.

F.

Protect the filter fabric from damage due to the placement of riprap or other materials by limiting the height of drop of the material or by placing a 6 inch cushioning layer of sand on top of the fabric before dumping the material. Before placement of riprap, the Contractor shall demonstrate that the placement technique will prevent damage to the fabric.

Covering With Soil or Sand Do not cover geotextile prior to inspection by the Owner’s Representative. Place cover soil or sand in a manner that prevents soil or sand from entering the geotextile overlap zone, prevents tensile stress from being mobilized in the geotextile, and prevents wrinkles from folding over onto themselves. On side slopes, place soil or sand backfill from the bottom of the slope upward. Do not drop cover soil or sand onto the geotextile from a height greater than 3 feet. Do not operate equipment directly on top of the geotextile. Use equipment with ground pressures less than 7 psi to place the first lift over the geotextile. Maintain a minimum of 12 inches of soil between full-scale construction equipment and the geotextile. Cover soil or sand material type, compaction, and testing requirements are described in Section 312316. Equipment placing cover soil shall not stop abruptly, make sharp turns, spin their wheels, or travel at speeds exceeding 5 mph.

G.

H.

Placement of Geotextile Around Underdrain Piping 1.

Install in accordance with AASHTO M288, Appendices A1 and A2, except as modified below.

2.

Wrap the perforated underslab drains with filter fabric. Do not use fabric with defects, rips, holes, flaws, deterioration, or damage of any nature.

3.

Handle and place filter fabric in accordance with the manufacturer's recommendations. Stretch, align, and place the fabric in a wrinkle-free manner.

4.

Spiral wrap the perforated underdrain pipes with filter fabric to provide a minimum width of 18 inches of overlap. Install perforated pipe per Section 402350 and the drawings.

5.

Cover filter fabric wrapped underdrain pipes with permeable underdrain material and compact per fabric manufacturer and Section 312316.

Repairing Damaged Fabric 1.

Protect the fabric at all times during construction from contamination by surface runoff. Remove and replace fabric so contaminated with uncontaminated fabric. Repair any damage to the fabric during its installation or during placement of filter materials, crushed rock and riprap by the Contractor at his expense.

2.

Repair fabric damaged during placing, in other than underdrain piping service, by placing a piece of fabric large enough to cover the torn or punctured area, meet the overlap requirement, and extend a minimum of 12 inches beyond the edge of the damaged area. Repair damaged sections of fabric used in underdrain piping by cutting out the damaged section over the full width of the spiral section and stitching a new fabric section in place for a minimum length of 18 inches.

FILTER FABRIC 60060986 - March 24, 2010

313219-5

3.

Damage to the fabric and underdrain piping system resulting from the Contractor's vehicles, equipment, or operations shall be repaired by the Contractor at his expense.

4.

Maintain a minimum of 6 inches of material between the fabric and Contractor's equipment, during spreading and compaction of the filter materials, crushed rock, and riprap. Where embankment material is to be placed on the filter fabric, maintain a minimum of 18 inches of embankment material between the fabric and the Contractor's equipment. Do not operate or drive equipment or vehicles directly on the filter fabric. END OF SECTION

FILTER FABRIC 60060986 - March 24, 2010

313219-6

SECTION 317216 CASING PIPE - BORING AND JACKING PART 1 - GENERAL A.

Description Furnish all material, equipment, transportation, tools and labor to install casing pipe by jacking and boring method, carrier pipe within casing, masonry plugs, and all related excavation, backfill, testing and other work for a complete job.

B.

Jurisdiction For casing pipe crossing under roadways, railroads, or other installations not within the jurisdiction of the Owner, the Contractor shall comply with regulations of said authority. State highway casing installations shall be as specified in the Florida Department of Transportation, "Utility Accommodation Guide", and for railroads, the American Railway Engineering Association, Part 5, Section 5.2, "Specifications for Pipelines Conveying NonFlammable Substances", shall be applicable.

C.

D.

Related Work Specified Elsewhere 1.

Submittals: 013300.

2.

Pressure Testing of Piping: 400515.

Submittals 1.

Submit shop drawings in accordance with Section 013300 and the following: a.

Site plan of jacking and receiving pits.

b.

List of materials and procedures.

PART 2 - PRODUCTS A.

Casing Casing shall be new prime steel pipe conforming to ASTM A139 Grade B. Pipe shall be seamless or not have more than one (1) longitudinal weld. Minimum casing pipe size and wall thickness shall be as indicated on the plans.

B.

Carrier Pipe Carrier pipe installed within casing shall be ductile iron pipe, Special Class 51 or class for other part of pipe, whichever is higher, unless otherwise noted on the plans, equipped with mechanical joint connections. Pipe and fittings shall comply with the applicable provisions of these specifications.

CASING PIPE – BORING AND JACKING 60060986 - March 24, 2010

317216-1

C.

Casing Spacers Casing spacers shall be stainless steel with vinyl runners as manufactured by Advance Products Series 55, Cascade series CCS/CCPS/AZ, PSI series 5-G-2, PowerSeal Model 48 series, or equal.

PART 3 - EXECUTION A.

B.

C.

Boring and Jacking 1.

The boring and jacking operations shall be done simultaneously with continuous installation until the casing pipe is in final position. Correct line and grade shall be carefully maintained. If desired, a pilot hole with a maximum diameter of 2 inches may be used for controlling line and grade. Add-on sections of casing pipe shall be full-ring welded to the proceeding length, developing watertight total pipe strength joints. The casing installation shall produce no upheaval, settlement, cracking, movement or distortion of the existing roadbed or other facilities. Following placement of the carrier pipe within the steel casing, masonry plugs shall be installed at each open end. Said plugs shall be suitable for restraining the external earth load, while allowing internal drainage. The pipe shall be jacked from the low or downstream end.

2.

The variation in the field position of the pipe from the line and grade as indicated on plans will be limited to 2 percent in lateral alignment and 1 percent vertical grade providing that the final grade of the flow line shall be in the direction as indicated on the plans.

Auger 1.

Casing pipe holes shall be mechanically bored through the soil by a cutting head on a continuous auger mounted inside the pipe. The auger shall extend a minimum distance beyond the end of the casing pipe to preclude formation of voids outside the pipe shell. Any voids, which develop during the installation operation, shall be pressure grouted with an approved mix.

2.

The use of water or other fluids shall be in connection with the boring operation to lubricate cuttings. Jetting will not be permitted.

Casing Protection/Damage 1.

The casing pipe shall be adequately protected to prevent crushing or other damage under jacking pressures. Backstops shall be provided for adequately distributing the jack thrust without causing deformation of the soil or other damage. Should the casing pipe be damaged, such damaged portion, if not in the hole, shall be replaced; however, if inserted, the encasement pipe shall be abandoned in place, suitably plugged, and an alternate installation made, after reviewed by the Engineer.

CASING PIPE – BORING AND JACKING 60060986 - March 24, 2010

317216-2

2.

D.

Coating: Coat the casing pipe inside and out with the following: a.

Type: High-build epoxy having a minimum volume solids of 60%, with an inorganic zinc prime coat.

b.

Surface Preparation: SSPC SP-10.

c.

Prime Coat: Self-curing, two-component inorganic zinc-rich coating recommended by the manufacturer for overcoating with a high-build epoxy finish coat. Minimum zinc content shall 15 pounds per gallon. Products: Tnemec 90E92 or Ameron (PPG Industries) Dimetcote 9, 3 mils; or equal.

d.

Finish Coat: Ameron (PPG Industries) 383HS, 5 mils; Tnemec 104, 5 mils; or equal.

Excavation Required boring and jacking pits or shafts shall be excavated and maintained to minimum dimensions. Said excavations shall be adequately barricaded, sheeted, braced and dewatered, as required, in accordance with the applicable portions of these specifications.

E.

Casing Spacers (Skids) Carrier pipe shall be braced with casing spacers (wood skids) securely strapped to the barrel pipe such that there is clearance between bells and casing pipe. A minimum of four spacers (skids) shall be used. Casing spacers (Skids) shall have a maximum spacing of 10 (15) feet.

F.

Tests Hydraulically test the carrier pipe with the other pipe on the project per Section 400515 and the Pipe Schedule (Flow Identification table) on the drawings. END OF SECTION

CASING PIPE – BORING AND JACKING 60060986 - March 24, 2010

317216-3

DIVISION 32 – EXTERIOR IMPROVEMENTS 320116

PAVING REMOVAL AND RESTORATION

321113

STABILIZED SUB BASE

321128

SHELL BASE COURSE

321129

CRUSHED CONCRETE BASE COURSE

321213

PRIME AND SEAL COAT

321215

ASPHALT PAVEMENT

321313

PORTLAND CEMENT CONCRETE PAVING

321613

CONCRETE CURBS, GUTTERS, AND SIDEWALKS

321723

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS

328420

LANDSCAPE IRRIGATION SYSTEM

329010

LANDSCAPE PLANTING

329210

SODDING

329211

VEGETATIVE ACCESS DRIVE

SECTION 320116 PAVEMENT REMOVAL AND RESTORATION PART 1 - GENERAL A.

Description The work specified in this section consists of removing and restoring pavement, pavement base, curb, curb and gutter, valley gutter, sidewalks and driveways disturbed by the work. Contractor shall provide all necessary labor, materials, equipment, tools, supplies, plant and equipment.

B.

Related Work Specified Elsewhere 1. 2. 3. 4. 5 6 7 8.

C.

Stabilized Sub-Base: 321113 Crushed Concrete Base Course: 321129 Prime and Tack Coat: 321213 Asphalt Pavement: 321215 Portland Cement Concrete Pavement: 321313 Concrete Curbs and Gutters and Sidewalks: 321613 Concrete Formwork: 031110 Concrete: 033000

Jurisdiction For removals and restorations or other installation in areas not within the jurisdiction of the City, the Contractor shall comply with regulations and conditions of permits issued by said authority.

A.

Submittals 1.

Submit shop drawings in accordance with the General Provisions, and Section 013300.

PART 2 - PRODUCTS A.

Stabilizers See Section 321113 – Stabilized Sub-base.

B.

Base 1.

See Section 321129 – Crushed Concrete Base Course.

PAVEMENT REMOVAL AND RESTORATION 60060986 - March 24, 2010

320116-1

C.

Prime and Tack Coat See Section 321213.

D.

Asphalt Concrete Surfaces See Section 321215.

E.

Concrete See Section 033300.

PART 3 - EXECUTION A.

B.

C.

Roadway and Pavement Restoration 1.

Replace pavement or roadway surfaces cut or damaged by the Contractor in equal or better condition than the original, including stabilization, base course, surface course, or other appurtenances.

2.

Concrete roadway surface shall be constructed as specified in Section 321313.

3.

Asphalt roadway surface shall be constructed as specified in Sections 321213 and 321215.

4.

Base course shall be constructed as specified in Section 321129.

5.

Sub-base shall be constructed as specified in Section 321113.

Concrete Curbs, Gutters and Valley Gutters 1.

Do not disturb curbs or gutters where practical to tunnel underneath. If tunneling is not possible, remove the curb to the existing joints or sawcut, leaving pieces not less than five feet long, and replace with identical sections.

2.

Concrete curbs, curb and gutter, and valley gutter shall be constructed as specified in Section 321613.

Saw-Cutting 1.

Where existing pavement is to be removed, saw-cut the surface leaving a uniform and straight edge, with minimum disturbance to the remaining adjacent surfacing.

2.

The width of all pavement surface cuts shall be not less than two feet greater than width of trench in order to provide a minimum of one-foot bearing width on each side.

PAVEMENT REMOVAL AND RESTORATION 60060986 - March 24, 2010

320116-2

D.

Temporary Surface 1.

2.

E.

a.

Compact the backfill as specified and bring to grade to match existing roadway surface. Within ten days after pavement removal, regrade the backfill and place, compact, and seal the subbase and base.

b.

Within sixty (60) days after pavement removal, place the finished surface course. Pavement repair shall at all times provide a smooth traffic surface so as not to create a bump or depression.

In areas where traffic is to be maintained, place a temporary asphalt mix immediately after backfilling and before opening the area to traffic. Lay the temporary pavement even with existing pavement to create a smooth pavement, and maintain the area until the permanent pavement is constructed.

Minimum Pavement Repair 1.

2.

F.

Where existing pavement is removed, provide a temporary surface according to the following:

Provide the following minimum pavement structure: a.

Subbase: 12 inches of compacted material with a Florida bearing value of 50. Compaction to minimum of 95 percent of maximum density, AASHTO T-180 modified.

b.

Base: 8 inches compacted crushed concrete compacted to 95 percent maximum density, AASHTO T-180 modified. Base shall extend beyond top of trench width at least 1 foot on both sides.

c.

Concrete Base: If the area to be repaired is small and it would not be practical to mix and compact a subbase, the base may be made 9 inches thick using either limerock or Portland cement concrete.

d.

Prime Coat: Prime the crushed concrete base with a minimum of 0.2 gallons per square yard and then sand as required.

e.

Surface: 1-1/2 inch compacted thickness of plant mix, Type II, unless otherwise specified or required to match existing pavement. Finish surface to proper grade and cross section to match original. Width of asphalt surface shall exceed width of top of trench by at least 1 foot on both sides.

If pavement removed is superior to the minimum specifications set forth above, make the patch equal to the pavement removed.

Settlement of Pavement All settlement of pavement repairs occurring within a period of one year after final acceptance of the project by the City shall be repaired or replaced by the Contractor as required by and at no cost to the City.

PAVEMENT REMOVAL AND RESTORATION 60060986 - March 24, 2010

320116-3

G.

Stabilized Roads On clay or other type stabilized roads, replace and compact the clay or stabilizing material to at least its original condition.

H.

Testing For testing procedures and requirements see referenced applicable sections as appear in this Project Manual.

I.

Disposal of Removed Materials The CONTRACTOR is responsible for properly disposing of all removed materials.

END OF SECTION

PAVEMENT REMOVAL AND RESTORATION 60060986 - March 24, 2010

320116-4

SECTION 321113 STABILIZED SUB-BASE PART 1 - GENERAL A.

Description This section includes materials, testing and construction of a firm and unyielding stabilized sub-base.

PART 2 - PRODUCTS A.

Materials Use local or hauled-in clean sand or sand and clay.

B.

Stabilizers Use high-bearing-value soil, sand-clay, ground limestone, crushed limestone, oyster shell, coquina shell, or rock screenings. Do not use muck, trash, hardpan, material having a plasticity index of more than 10 or a liquid limit greater than 40.

PART 3 - EXECUTION A.

Construction Methods Test local material for compliance with the required Florida Bearing Value. If the natural inplace soils do not meet the required stability, uniformly mix to depth shown in plans sufficient borrow material for stabilization with the in-place soils to produce the required bearing value. Compact the stabilized sub-base in both cuts and fills to a density of 98 percent of the maximum density as required by AASHTO T-180 (modified). Shape the sub-base to within 1/4 inch of the cross section grade shown in the plans prior to making the density tests. MAKE THE DENSITY TESTS BEFORE OTHER WORK PROCEEDS. Maintain the required density and cross section until the base or pavement has been laid or until the aggregate materials for the base or pavement course have been spread in place.

B.

Required Bearing Value Unless otherwise specified or shown in the plans, stabilized sub-base shall have a minimum Florida Bearing Value of 50.

C.

Tests Density and bearing value tests shall be made by an independent testing laboratory at intervals not more than 300 feet in roadways or 2,400 sq. ft. in area paving. If any test results are unsatisfactory, re-excavate and re-compact the sub-base until the desired compaction is obtained. Make additional tests on each side of an unsatisfactory test to determine the extent of re-excavation, re-mixing and re-compaction necessary. END OF SECTION

STABILIZED SUB-BASE 60060986 - March 24, 2010

321113-1

SECTION 321128 SHELL BASE COURSE PART 1 - GENERAL A.

Description The work specified in this section consists of the construction of a base course composed of shell constructed on a prepared subbase.

B.

Submittals 1.

Submit shop drawings in accordance with the General Provisions, Section 013300 and the following:

2.

Submit copies of a certification from a testing laboratory that the material used for the base meets the specified criteria.

PART 2 - PRODUCTS Shell material shall meet the requirements of Section 913 of the Florida Department of Transportation Standard Specifications for Road and Bridge Design, Latest Edition. PART 3 - EXECUTION The placement, compaction and finishing of the shell base shall meet the requirements of Section 250 of the Florida Department of Transportation Standard Specifications for Road and Bridge Design, Latest Edition. END OF SECTION

SHELL BASE COURSE 60060986 - March 24, 2010

321128-1

SECTION 321129 - CRUSHED CONCRETE BASE COURSE PART 1 - GENERAL 1.01

SCOPE This item shall consist of the construction of a base course composed of crushed concrete. It shall be constructed on the prepared subgrade in accordance with this specification and shall conform to the dimensions, lines, grades and cross sections shown on the plans.

1.02

REFERENCES Standards applicable to this Specification shall be:

1.03

A.

American Association of State Highway and Transportation Officials Standard Specifications (AASHTO). 1. AASHTO M81-75 (1982) - Standard Specification for Cut-Back Asphalt (Rapid-Curing Type).

B.

Florida Department of Transportation Standard Specifications (F.D.O.T.). 1. FDOT Section 300, Prime and Tack Latest Issue.

SUBMITTALS A.

Submit shop drawings in accordance with the General Provisions, Section 013300, and the following:

B.

Submit copies of a certification from a testing laboratory that the material used for the base meets the specified criteria and contains less than 1% by weight asbestos.

PART 2 2.01

MATERIALS

CRUSHED CONCRETE A.

Composition- Base material shall conform to the following gradation: SIEVE SIZE 2" 1 1/2" 3/4" 3/8" No. 4 No. 10 No. 50 No. 200

PERCENT BY WEIGHT PASSING 100 98 - 100 65 - 90 45 - 75 35 - 60 25 - 45 5 - 25 0 - 10

Material for Crushed Concrete Base shall consist only of crushed concrete and such additive materials as may be approved by the Engineer for the purpose of facilitating construction and achieving the desired characteristics of the finished in-place product. Material which shows a significant tendency toward adverse chemical or CRUSHED CONCRETE BASE COURSE 60060986 - March 24, 2010

321129-1

physical change on exposure to moisture will not be acceptable. The material shall be free of any Ferrous Metals. B.

Mechanical and Physical Properties- The material shall not contain lumps, balls, or pockets of sand or clay material in size or quantity sufficient to be detrimental to the proper bonding, finishing, or strength of the crushed concrete base. The specific mechanical and physical properties of crushed concrete aggregate and any additive materials permitted in the construction of Crushed Concrete Base under this contract shall be determined on the basis of test results as the work progresses. C. The Crushed Concrete material used in construction of crushed concrete base shall have an LBR value of not less than 100PART 3 - EXECUTION OF WORK

3.01

TRANSPORTING CRUSHED CONCRETE The material shall be transported to the point where it is to be used, over crushed concrete previously placed where possible, and dumped at the end of the preceding spread. Hauling over the subgrade, or dumping on the subgrade for further placement operations, will be permitted only when, in the opinion of the Engineer, such procedures will not adversely affect the integrity of the completed base and subgrade.

3.02

EQUIPMENT A.

Crushed Concrete Base - The rock shall be accomplished by mechanical spreader, equipped with a device which strikes off the rock uniformly to laying thickness, and capable of producing an even distribution of crushed concrete aggregate. For crossovers, intersections and ramp areas; for roadway widths of 20 feet or less; for the main roadway area when forms are used and for any other areas where the use of a mechanical spreader is not practicable; spreading may be done by bulldozers or blade graders.

B.

Pressure Distributor - The pressure distributor shall be equipped with pneumatic tires having a sufficient width of rubber in contact with the road surface to avoid breaking the bond or forming a rut in the surface. The distance between the centers of openings of the outside nozzles of the spray bar shall be equal to the width of the application required, within an allowable variation two (2) inches. The outside nozzle at each end of the spray bar shall have an area of opening not less than 25 percent nor more than 75 percent, in excess of the other nozzles. All other nozzles shall have uniform openings. When the application covers less than the full width, the normal opening of the end nozzle at the junction line may remain the same as those of the interior nozzles. less than the full width, the normal opening of the end nozzle at the junction line may remain the same as those of the interior nozzles.

3.03

SPREADING CRUSHED CONCRETE A.

Method of Spreading - The crushed concrete shall be spread uniformly with equipment as specified in 3.02 A. above. All segregated areas of fine or coarse rock shall be removed and replaced with properly graded rock.

CRUSHED CONCRETE BASE COURSE 60060986 - March 24, 2010

321129-2

B.

3.04

Number of Courses - When the specified compacted thickness of the base is greater than six inches, the base; shall be constructed in two courses. The thickness of the first course shall be approximately one-half the total thickness of the finished base, or enough additional to bear the weight of the construction equipment without disturbing the subgrade.

COMPACTING AND FINISHING BASE A.

Single-Course Base - For single-course base, after the spreading is completed the entire surface shall be scarified and then shaped so as to produce the required grade and cross section after compaction.

B.

Double-Course Base - For double-course base, the first course shall be cleaned of foreign material and bladed and brought to a surface cross section approximately parallel to that of the finished base. Prior to the spreading of any material for the upper course, the density tests for the lower course shall be made and the Engineer shall have determined that the required compaction has been obtained. After the spreading of the material for the final course is completed, its surface shall be finished and shaped so as to produce the required grade and cross section after compaction, and free of scabs and laminations.

C. Moisture Content - When the material does not have the proper moisture content to insure the required density, wetting or drying will be required. When water is added it shall be uniformly mixed-in by disking to the full depth of the course which is being compacted. Wetting or drying operations shall involve manipulation, as a unit, of the entire width and depth of the course which is being compacted. D. Density Requirements - After spreading is completed the crushed concrete shall be uniformly compacted, with water being added as required, to a density of not less than ninety eight percent (98%) of the maximum density as determined by AASHTO T-180. during final compaction operations, if the blading of any areas is necessary to obtain the true grade and cross section, the compacting operations for such areas shall be completed prior to the performance of density tests on the finished base. Crushed concrete base for shoulder pavement shall be compacted to a density not less than ninety eight percent (98%) of the maximum density as determined under AASHTO T 180. E.

Density Test - At least three density determinations shall be made on each day's final compaction operations on each course, and the density determinations shall be made at more frequent intervals if deemed necessary by the Engineer. During final compacting operations, if blading of any areas is necessary to obtain the true grade and cross section, the compacting operations for such areas shall be completed prior to making the density tests on the finished base.

F.

Correction of Defects 1. Contamination of Base Material - If, at any time, the subgrade material should become mixed with the base course material, the Contractor shall, without additional compensation, dig out and remove the mixture, reshape and compact

CRUSHED CONCRETE BASE COURSE 60060986 - March 24, 2010

321129-3

the subgrade and replace the materials removed with clean base material, which shall be shaped and compacted as specified above. 2. Cracks and Checks - If cracks or checks appear in the base, either before or after priming, which, in the opinion of the Engineer, would impair the structural efficiency of the base, the Contractor shall remove the cracks or checks by rescarifying, reshaping, adding base material where necessary, and recompacting. G. Compaction and Finishing Base - Dynamic Compactor with vibratory rollers shall not be used on this project and shall not be permitted at the job site. The contractor is responsible for all damages caused by compaction operations.

3.05

QUALITY CONTROL A.

Testing Surface - The finished surface of the base course shall be checked with a templet cut to the required grade and with a 15-foot straightedge laid parallel to the centerline of the road. All irregularities greater than 1/4 inch shall be corrected by scarifying and removing or adding rock as required, after which the entire area shall be recompacted as specified hereinbefore. In the testing of the surface, the measurements will not be taken in small holes caused by individual pieces of rock having been pulled out by the grader.

B.

Thickness Requirements: 1. Measurements - Thickness of base shall be measured at intervals of not more than 200 feet. Measurements shall be taken at various points on the cross section, through holes not less than three inches in diameter. 2. Areas Requiring Correction - Where the compacted base is deficient by more than 1/2 inch from the thickness called for in the plans, the Contractor shall correct such areas by scarifying and adding rock. The base shall be scarified and rock added for a distance of 100 feet in each direction from the edge of the deficient area. The affected areas shall then be brought to the required state of compaction and to the required thickness and cross section. 3. Deficient Areas Left in Place - As an exception to the requirement for correcting areas of base which show a thickness deficiency exceeding the allowable 1/2 inch, if so approved in writing by the Engineer. Any of such areas in which the extent of the deficiency might be considered as not sufficient to seriously impair the required strength of the base may be left in place. No payment, however, will be made for such deficient areas left in place and not corrected. 4. Density Testing - After the base is completed, the density shall be checked at intervals of not more than 300 feet of roadway or 2,400 sq. ft. of area paving. If any field density tests are below the specified density, rework and recompact the area until the minimum density is achieved. MAKE AT LEAST THREE DENSITY DETERMINATIONS ON EACH DAY'S FINAL COMPACTION OPERATIONS ON EACH COURSE. The density determinations shall be made at more frequent intervals if deemed necessary by

CRUSHED CONCRETE BASE COURSE 60060986 - March 24, 2010

321129-4

the Engineer. 3.07

MAINTENANCE The Contractor will be responsible for assuring that the true crown and templet are maintained, with no rutting or other distortion, and that the base meets all the requirements, at the time the surface course is applied.

END OF SECTION

CRUSHED CONCRETE BASE COURSE 60060986 - March 24, 2010

321129-5

SECTION 321213 PRIME AND TACK COATS PART 1 - GENERAL A.

Description This section includes materials, testing and application of bituminous material on a previously prepared base and on an existing pavement surface.

B.

Submittals Submit shop drawings in accordance with the General Provisions and Section 013300 showing the materials to be used and manufacturer's certificates showing compliance with the specifications.

PART 2 - PRODUCTS A.

Prime Coat The material used for prime coat shall be: 1.

Cut-back Asphalt Grade RC-70 or RC-250 meeting the requirements of AASHTO M81 except that the penetration range shall be from 60-120 instead of 80120. For Grade RC-3000, in addition to the requirements shown in Table I of AASHTO M81 the following values shall be added to the requirements for Distillation Test:

Distillate, percentage by volume of total distillate to 680 deg. F.

Grade RC-3000 Max.

to 320 deg. F to 374 deg. F to 437 deg. F

0 10 40

All other requirements for the distillation test (and for other properties included in the table) shall be as shown in Table I of AASHTO M81. 2.

Emulsified Asphalt Grades SS-1 or CCS-1, SS-1H or CCS-1H diluted in equal proportion with water; asphalt emulsified asphalt grade AE-60, AE-90, AE-150 or AE200 diluted at the ratio of 6 parts emulsified asphalt to 4 parts water; special MSEmulsion diluted at the ratio of 6 parts emulsified asphalt to 4 parts water; Asphalt Emulsion Prime (AEP) meeting the following: a.

Anionic Emulsified Asphalt shall meet the requirements of AASHTO M140 with the exception that the cement mix test will be waived when the asphalt is used in non-mix application, such as tack coats and primes.

b.

Cationic Emulsified Asphalt shall meet the requirements of AASHTO M208.

PRIME AND TACK COATS 60060986 - March 24, 2010

321213-1

c.

Emulsified Asphalt Grades AE-60, AE-90, AE-150 and AE-200 shall meet the following requirements:

HIGH FLOAT EMULSIONS Asphalt Emulsion Grade AE-60 AE-90 Min Max Min Max Tests on Emulsion: Saybolt Furol Viscosity at 122°F, sec. Settlement 5 days, % Storage Stability 24 Hr., % Sieve Test, % Demulsibility, 50 ml CaC12 0.10N, % Residue by Distillation, % Oil Portion, % by Volume (500°F Dist) Tests on Residue: Penetration 77°F 100 g 5 sec Absolute Viscosity, poise 140°F Ductility 77°F 5 cm/min, cm Float Test 140°F, sec Solubility in Trichloroethylene, %

PRIME AND TACK COATS 60060986 - March 24, 2010

75

75 65

40 3200 40 1200 97.5

400 5 1 0.10 1

75

75 65

400 5 1 0.10 2

70 1600 40 1200 97.5

321213-2

Tests on Emulsion: Saybolt Furol Viscosity at 122°F, sec. Settlement 5 days, % Storage Stability 24 Hr., % Sieve Test, % Demulsibility, 50 ml CaC12 0.10N, % Residue by Distillation, % Oil Portion, % by Volume (500°F Dist) Tests on Residue: Penetration 77°F 100 g 5 sec Absolute Viscosity, poise 140°F Ductility 77°F 5 cm/min, cm Float Test 140°F, sec Solubility in Trichloroethylene, %

d.

AE-150 Min Max

AE-200 Min Max

75

75

75 65

125 800 40 1200 97.5

400 5 1 0.10 3

62

5 1 0.10 8

150 400 1200 97.5

Special MS-Emulsion shall meet the following requirements with a minimum application temperature of 170°F:

SPECIAL MS-EMULSION

Tests on Emulsion: Saybolt Furol Viscosity at 77°F, sec. Storage Stability 24 Hr., % Sieve Test, % Demulsibility, 50 ml CaC12 0.10N, % Residue by Distillation, % Oil Portion, % by Volume (500°F Dist) Tests on Residue: Penetration 77°F 100 g 5 sec Ductility 77°F 5 cm/min, cm Absolute Viscosity, poise 140°F Solubility in Trichloroethylene, %

PRIME AND TACK COATS 60060986 - March 24, 2010

Min

Max

45 --65 62 --

-1 0.10 --8

60 40 800 97.5

----

321213-3

e.

Emulsified Asphalt Grade CRS-2H shall meet the following requirements:

EMULSIFIED ASPHALT GRADE CRS-2H

Tests on Emulsion: Saybolt Furol Viscosity at 122°F, sec. Settlement 5 days, % Storage Stability 24 Hr., % Demulsibility, 35 ml 0.8% Sodium dioctyl Sulfosaccinate, % Particle Charge Sieve Test, % Residue, % Tests on Residue: Penetration 77°F 100 g 5 sec Ductility 77°F 5 cm/min, cm Solubility in Trichloroethylene, %

f.

Min

Max

100 ---

400 5 1

40 Positive -65 80 40 97.5

0.1 -140 ---

Asphalt Emulsion Prime shall meet the following requirements:

ASPHALT EMULSION PRIME (AEP)

Tests on Emulsion: Saybolt Furol Viscosity at 77°F, sec. Settlement 5 days, % Storage Stability 24 Hr., % Sieve Test, % Demulsibility, 50 ml CaC12 0.10N, % Residue, % Oil Portion, % by Volume (500°F Dist) Tests on Residue: Penetration 77°F 100 g 5 sec Ductility 77°F 5 cm/min, cm Solubility in Trichloroethylene, %

PRIME AND TACK COATS 60060986 - March 24, 2010

Min

Max

20 ---65 55 --

150 5 1 0.1 --12

40 40 97.5

200 ---

321213-4

Where Emulsified Asphalt is deficient from the minimum percentage of residue required in the applicable specifications, payment for such material will be made at reduced rates as shown in the following table:

Deficiency from Minimum Percent Residue 1 4 7 *More

Percentage of Original Contract Price

- 3 - 6 - 9 than 9

95 85 75 50

*At the discretion of the Engineer, the asphaltic mixture, the base material, the surface treatment, or the mineral seal coat containing this material may be left in place with 50 percent payment made therefore, or be removed to the extent required by the Engineer and acceptably replaced. The viscosity requirements for all Grades of Emulsified Asphalt used as tack coat or prime coat may be waived by the Engineer if satisfactory results are being obtained. B.

C.

Cover Material for Prime Coat 1.

If an emulsified asphalt is used for prime coat, the cover material shall be hot-asphalt coated (mix to contain from two to four percent asphalt-cement) to achieve a prime coat which will remain reasonably intact until the surface course is placed.

2.

If material other than emulsified asphalt is used for the prime coat, the cover material shall be either sand (bare or hot-asphalt coated) or screenings. The sand shall be nonplastic and free from any appreciable amount of silt, clay balls and root particles, and from any noticeable sticks, trash, vegetation or other organic matter. Screenings shall be Miami Oolitic rock screenings as specified in FDOT Specification Section 902-5.2.3.

Tack Coat 1.

Unless a specific type or grade of material is called for in the plans or specifications, the material used for tack coat may be any of the following: Emulsified Asphalt, Grades RS-1, RS-2, CRS-2, SS-1, CSS-1, SS-1H, CSS-1H, AE-60, AE-90, AE-150, or CRS-2H, Special MS Emulsion, or Asphalt Emulsion Prime (AEP). The materials specified above shall not be diluted prior to use.

2.

Emulsified asphalt (RS Type) shall meet the following requirements:

Tests on Emulsion: Saybolt furol viscosity at 77°F, sec. Storage stability 24 Hr., % Sieve test, % Naptha content, % by volume Residue, %

PRIME AND TACK COATS 60060986 - March 24, 2010

Min.

Max.

75 --5 55

-1.0 0.1 15 --

321213-5

Tests on Residue:* Penetration at 77°F, 100g, 5 sec. Viscosity at 140°F (poises) Solubility in trichloroethylene, %

50 800 97.5

----

* Residue by distillation shall be in accordance with AASHTO T-59 except that the maximum temperature shall be 329° + 10°F (165° + 5°C) and the sample shall be maintained at this temperature for 20 minutes. PART 3 - EXECUTION A.

Equipment Pressure Distributor: The pressure distributor shall be equipped with pneumatic tires having a sufficient width of rubber in contact with the road surface to avoid breaking the bond or forming a rut in the surface. The distance between the centers of openings of the outside nozzles of the spray bar shall be equal to the width of the application required, within an allowable variation of two inches. The outside nozzle at each end of the spray bar shall have an area of opening not less than 25 percent nor more than 75 percent, in excess of the other nozzles. All other nozzles shall have uniform openings. When the application covers less than the full width, the normal opening of the end nozzle at the junction line may remain the same as those of the interior nozzles.

B.

C.

Cleaning Base and Protection of Adjacent Work 1.

Before any bituminous material is applied, all loose material, dust, dirt, caked clay and other foreign materials which might prevent proper bond with the existing surface shall be removed for the full width of the application. Particular care shall be taken in cleaning the outer edges of the strip to be treated, to insure that the prime or tack coat will adhere.

2.

When the prime or tack coat is applied adjacent to curb and gutter, valley gutter or any other concrete surfaces, such concrete surfaces (except where they are to be covered with a bituminous wearing course) shall be covered with heavy paper, or otherwise protected while the prime or tack coat is being applied. Any bituminous material deposited on such concrete surfaces shall be removed.

Weather Limitations Prime and tack coats shall be applied when the air temperature, in the shade, is above 40°F, and when all other weather conditions and the condition of the surface are suitable.

D.

Application of Prime Coat 1.

General: The surface to be primed shall be clean and the moisture content of the base shall not exceed 90 percent of the optimum moisture. The temperature of the prime material shall be between 100°F and 180°F. The actual temperature shall be that which will insure uniform distribution. The material shall be applied by means of a pressure distributor. The amount to be applied will be dependent on the character of the surface and shall be sufficient to coat the surface thoroughly and uniformly, with no excess. A prime coat is required on newly constructed limerock, shell, and sand clay bases.

PRIME AND TACK COATS 60060986 - March 24, 2010

321213-6

2.

E.

Rate of Application a.

Limerock, Limerock Stabilized, and Local Rock Bases: For these bases, the rate of application shall be not less than 0.10 gallon per square yard.

b.

Sandy-Clay, Shell and Shell Stabilized Bases: The rate of application for these bases shall be not less than 0.15 gallon per square yard.

3.

Partial Width of Application: If warranted by traffic conditions, the application may be made on only one-half of the width of the base at one time, in which case positive means shall be used to secure the correct amount of bituminous material at the joint.

4.

Sanding a.

If an emulsified asphalt is used to prime coat, the primed base shall be uniformly covered by an application of sand-bituminous hot mix or screenings at an approximate rate of ten pounds per square yard. The entire surface of the sand-bituminous hot mix or screenings cover material shall be rolled with a traffic roller as required to produce a reasonable dense mat.

b.

If material other than emulsified asphalt is used for prime coat, the primed base shall be covered by a light uniform application of cover material. If considered necessary for proper distribution of spread, the cover material shall be lightly dragged with a drag broom, after which it shall be rolled with a traffic roller, for at least ten passes over the entire area.

Application of Tack Coat 1.

General: Where a bituminous surface is to be laid and a tack coat is required, the tack coat shall be applied as specified herein below.

2.

Use a tack coat on existing pavement to be resurfaced, primed bases in areas which have become excessively dirty and cannot be cleaned, or in areas where the prime has cured and lost its bonding effect.

3.

Method of Application: The tack coat shall be applied with a pressure distributor except that, on small jobs if approved by the Engineer, application may be by other mechanical devices or by hand methods. The bituminous material shall be heated to a suitable temperature and shall be applied in a thin, uniform layer.

4.

Rate of Application: The rate of application shall be between 0.02 and 0.08 gallon per square yard. For tack coat applied on concrete pavement which is to be surfaced, the rate of application may exceed the upper limit.

5.

Curing and Time of Application: The tack coat shall be applied sufficiently in advance of the laying of the bituminous mix to permit drying but shall not be applied so far in advance that it might lose its adhesiveness as a result of being covered with dust or other foreign material.

6.

Protection: The tack coat surface shall be kept free from traffic until the subsequent layer of bituminous hot mix has been laid. END OF SECTION

PRIME AND TACK COATS 60060986 - March 24, 2010

321213-7

SECTION 321215 ASPHALT PAVEMENT PART 1 - GENERAL A.

Description This section specifies requirements for material, testing and installation of plant mix asphalt pavement.

B.

Related Work Specified Elsewhere 1.

C.

D.

Submittals: 013300.

Rights-of-Way 1.

County: Roadway and pavement within county rights-of-way shall be in accordance with applicable county standards and "Right-of-Way Utilization Regulations".

2.

City: Roadway, pavement and right-of-way utilization within city limits shall be in accordance with applicable city standards and regulations.

3.

FDOT: Roadway, pavement and right-of-way utilization within FDOT rights-of-way shall be in accordance with applicable FDOT standards and right-of-way utilization permit(s).

Submittals 1.

Submit shop drawings in accordance with the General Provisions, Section 013300, and the following:

2.

A design mix for the asphalt including gradation of all materials, content of mix, Marshall stability, and laboratory density.

3.

Certifications showing that the materials comply with the specifications and contain less than 1% by weight asbestos.

PART 2 - PRODUCTS A.

Asphaltic Concrete 1.

Composition, design mix and physical properties shall meet the requirements of the following:

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-1

Bituminous Concrete Mixtures (Gradation Design Range) Type

Percent by Weight Total Aggregate Passing Sieves ______________________________________________________ 3/4 1/2 3/8 No.4 No.10 No.40 No.80 No.200

S-I 100 88-100 75-93 47-75 31-53 19-35 7-21 2-6 S-II(1) 83-98 71-87 62-78 47-63 33-49 19-35 9-18 2-6 S-III 100 88-100 60-90 40-70 20-45 10-30 2-6 Type II 100 90-100 80-100 55-90 2-12 Type III 100 80-100 65-100 40-75 20-45 10-30 2-10 ABC-2 100 55-90 0-12 ABC-3(2) 70-100 30-70 20-60 10-40 2-10 FC-1 100 55-85 2-8 FC-2 100 85-100 10-40 4-12 2-5 FC-4 100 75-90 2-6 _________________________________________________________________ (1) 100% passing sieve.

1-1/4-inch

sieve

and

94-100%

passing

1-inch

(2) 100% passing 1-1/2-inch sieve. Marshall Design Properties for Bituminous Concrete Mixes

Mix Type

Minimum Marshall Stability (lbs.)

Minimum Air VMA Voids (%) (%)

Flow(1) (0.01 in.)

Minimum Effective Asphalt Content (%)

S-I 1500 8-14 14 3-5 5.0 S-II 1500 8-14 13 3-5 5.0 S-III 1500 8-14 15 3-7 5.5 Type II 500-750 8-16 18 5-16 6.0 Type III 750-1000 8-16 15 5-12 5.5 ABC-2 250 8-20 15 5-14 5.5 ABC-3 1000 8-20 14 3-7 5.0 FC-1 500 8-16 15 8-14 5.5 FC-2 -----------FC-4 500 8-16 15 12-16 5.0 _________________________________________________________ (1) The maximum flow for the mix design shall be one point less than shown. The maximum flow values shown apply only during production.

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-2

B.

Asphaltic Concrete Type S-I, S-II and S-III 1.

Type S-I, S-II and S-III shall meet the above requirements and the requirements in the following paragraphs.

2.

The Asphalt Cement, Viscosity Grade AC-20 or AC-30, shall meet the following except that no spot test is required:

Test Viscosity, 140°F (60°C), poises 600) Viscosity, 275°F (135°C), Cs Penetration, 77°F (25°C), 100 gm, 5 Sec. Flash Point, COC, °F (°C) Solubility in Trichloroethylene, percent Tests on Residue from Thin Film Oven Test: Viscosity Ratio= Visc. 140°F after TFOT Visc. 140°F before TFOT Ductility 77°F (25°C) 5 cm per min, cm. Loss on Heating, %

3.

AC-20 Min. Max.

AC-30 Min. Max.

(2000 + 400)

(3000

300 60 450 99.0

350 50 (232) 99.0

-----

+ -----

--

4

--

4

80 --

-0.5

50 --

-0.5

Mineral filler shall consist of limerock dust, portland cement, slag dust or hydrated lime. It shall be thoroughly dry and free from lumps, consisting of aggregations of fine particles. The filler shall meet the following gradation requirements:

Sieve Number 30 80 200

Total % Passing 100 95 (min) 65 (min)

Mineral filler may be provided from process screenings from stone or slag provided that the loss in processing under the Los Angeles Abrasion Test does not exceed 45%. The gradation of this filler shall be such that all of it shall pass the No. 10 sieve, and not more than 35% shall pass the No. 200 sieve. The material passing the No. 200 sieve shall be free of organic impurities and clay minerals shall not exceed 4.0%. The plasticity index of the material passing the No. 200 sieve shall not exceed 4. 4.

Coarse Aggregate: a.

Coarse Aggregate shall consist of gravel, rock or slag and contain less than 1% by weight asbestos. All coarse aggregate shall be washed and shall be free from disintegrated pieces, clay lumps, soft and friable particles, salt, alkali, organic matter and adherent coatings. The weight of deleterious substances shall not exceed the following percentages:

Coal and lignite . . . . . . . . . . . . . Clay lumps . . . . . . . . . . . . . . . .

ASPHALT PAVEMENT 60060986 - March 24, 2010

1.00 2.00

321215-3

Soft and friable particles . Cinders and clinkers . . . . Free Shell . . . . . . . . . Organic matter (wet) . . . . Material passing the No. 200 Chert . . . . . . . . . . .

. . . . . . . . . . . . Sieve . . .

. . . . . .

. . . . . .

. . . . . .

. . . . . .

2.00 0.50 1.00 0.03 1.75 3.00

In addition, the sum of the percentages of all substances listed above shall not exceed ten. b.

Coarse aggregate shall have a maximum loss of 45% when subjected to the Los Angeles Abrasion Test, a maximum loss of 12% when subjected to the Soundness (Sodium Sulfate) Test and contain a maximum of 10% flat or elongated pieces.

c.

Natural Stones: Coarse aggregate may be processed from gravels, granites, limestones, dolomites, sandstones, or other naturally occurring hard, sound, durable materials meeting the requirements of this paragraph. 1)

Gravel shall be composed of naturally occurring quartz. The loss when the material is subjected to the Los Angeles Abrasion Test (AASHTO T96), shall be no more than 45%. The dry-rodded weight per cubic foot of the gravel, tested according to AASHTO T19, shall be not less than 95 pounds. Crushed gravel shall consist of 85%, by weight, of the material retained on the No. 4 sieve, having three crushed faces.

2)

Granites: Coarse aggregate produced from the crushing of granites shall be sound and durable. For granites to be used in bituminous mixtures and surface treatments, the Los Angeles Abrasion requirement is modified to permit a maximum loss up to 50 (Manual of Florida Sampling and Testing Methods FM 1-T 096). Maximum amount of mica schist permitted is 5% (AASHTO T-189).

3)

Limestones, Dolomites and Sandstone: Coarse aggregates may be produced from limestone, dolomites, sandstones, and other naturally occurring hard, durable materials meeting the requirements of this paragraph. Pre-Cenozoic limestones and dolomites shall not be used as crushedstone aggregates, either coarse or fine, for wearing courses of asphaltic concrete surface courses. This specifically includes materials from the Ketona Dolomite (Cambrian), Newala Limestone (Lower Ordovician), Bangor Limestone (Mississippian), and other formations of similar composition and origin occurring in central and northern Alabama and Georgia.

d.

Slag shall be clean, tough and durable. It may be either air-cooled blastfurnace slag or phosphate slag. It shall be reasonably uniform in density and quality, and free from deleterious substances. It shall contain not more than 1.5% of sulphur. The dry-rodded weight shall be not less than 70 pounds per cubic foot. The loss, when the slag is subjected to the Los Angeles Abrasion Test, shall not exceed 45%. It shall contain not more than 10% glassy particles.

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-4

5.

e.

Unless written permission from the Owner is obtained, coarse aggregates of different types shall not be mixed, nor be used alternately in sections of less than one mile.

f.

Grading shall be in accordance with FDOT Specification Section 901-1.4 Table 1.

g.

Lightweight expanded aggregate shall be clean and durable material produced by firing shale, clay, or slate in a rotary kiln. It shall be reasonably uniform in quality and density and free from deleterious substances, except that the term cinders and clinkers shall only apply to those particles clearly foreign to the expanded aggregate in question and the maximum percentage of material passing the No. 200 sieve shall be 3.00. The dry-loose unit weight of the material, determined in accordance with AASHTO T19, shall not be less than 33 or more than 55 pounds per cubic foot. The burning process shall be carefully controlled. As an indication of the control of burning, the producer shall obtain and test samples of material at frequent intervals. Control shall be considered adequate if the dry-loose unit weight of such samples does not differ by more than +6% from the average weight established from the producer's quality control testing records. When subjected to the Los Angeles Abrasion Test, the loss shall not exceed 35%.

Fine Aggregate: a.

Fine aggregate shall consist of natural silica sand, screenings, or a combination thereof, composed of clean, tough, angular grains, free from clay, soft or flaky particles, salt, alkali, organic matter, loam and other foreign matter. As delivered to the mixer it shall be free from clayey lumps of loosely bonded aggregations and the individual particles shall be free from adhering dust. Stone of slag screenings shall be produced from material complying with the abrasion requirements specified for coarse aggregate. The weight of deleterious substances (shale, coal and lignite, cinders and clinkers, clay lumps) shall not exceed 1.0, 1.0, 0.5 and 1.0% respectively.

b.

The following additional limitation shall apply for stone used as aggregate in all asphaltic concrete used as a wearing coarse. Pre-Cenozoic limestones and dolomites shall not be used as crushed-stone aggregates, either coarse or fine, for wearing courses of asphaltic concrete surface courses. This specifically includes materials from the Ketona Dolomite (Cambrian), Newala Limestone (Lower Ordovician), Bangor Limestone (Mississippian), and other formations of similar composition and origin in central and northern Alabama and Georgia.

c.

Any screenings used in the combination of aggregate shall contain not more than 15% of material passing the No. 200 sieve and, if necessary to meet this requirement, they shall be washed.

d.

Any natural sand portion of the fine aggregate other than screenings shall be siliceous and shall contain not more than 10% of material passing the No. 200 sieve.

e.

Silica sand, when tested by means of laboratory sieves, shall meet the following requirements:

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-5

Passing Sieve

Percent by Weight

No. 4 . No. 8 . No. 16 . No. 30 . No. 50 . No. 100 . No. 200 . f.

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

. . . . . . .

95-100 85-100 65- 97 25- 70 5- 35 0- 7 Max. 4

Screenings: Screenings shall be composed of hard, durable particles, either naturally occurring, such as gravel screenings, or resulting from the crushing or processing of the parent rock, to include natural rock, slags, expanded clays or shales (lightweight aggregates), or other approved inert materials with similar characteristics. Aggregates classified as screenings shall conform to the following gradation requirements:

C.

Passing Percent

3/8" No. 4 No. 200

100 85 to 100 Maximum 15

Asphaltic Concrete Type II 1.

D.

Sieve Size

Type II shall meet the requirements of paragraphs 2A and 2B as modified by the following: a.

The aggregate shall contain no appreciable amount of phosphate and shall consist of either crushed slag, crushed stone, crushed gravel, coquina shell or oyster shell. Any combination of these aggregates with sand that meets the gradation and Marshall properties requirements specified may be used except that shell will not be permitted in the surface course.

b.

When tested at the cold elevator in the combination to be used, the aggregate shall contain not more than 12%, by weight, of material passing the No. 200 sieve. Any screenings used in the combination of aggregate shall not contain more than 15% of material passing the No. 200 sieve. When two screenings are blended to produce the screenings component of the aggregate, any component of such screenings may contain up to 18% of material passing the No. 200 sieve. Screenings may be washed to meet the requirements and shall be free from lumps and foreign matter.

c.

Not more than 40%, by weight, of the total aggregate used shall be sand.

Asphaltic Concrete Type III 1.

Type III shall meet the requirements of paragraphs 2A and 2B as modified by the following:

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-6

E.

a.

Not more than 25% by weight of the total aggregate used shall be local sand. In addition to the local sand, a portion not to exceed 15% by weight of the total aggregate may be commercial washed sand. The commercial washed sand must be in conformance with the requirements of fine aggregates for Asphaltic Concrete Type S-1.

b.

When tested at the cold elevator in the combination to be used, the aggregate shall contain not more than 10%, by weight, of material passing the No. 200 sieve. Any screenings used in the combination of aggregate shall not contain more than 15% of material passing the No. 200 sieve. When two screenings are blended to produce the screenings component of the aggregate, any component of such screenings may contain up to 18% of material passing the No. 200 sieve. Screenings may be washed to meet these requirements and shall be free from lumps and foreign matter.

Asphalt Base Course Asphalt base courses shall met the requirements of paragraphs 2A and 2B.

PART 3 - EXECUTION A.

Hot Bituminous Mixtures 1.

Plant operations shall not begin unless all weather conditions are suitable for the laying operations.

2.

The mixture shall be spread only when the surface upon which it is to be laid has been previously prepared, is intact, firm and properly cured, and is dry. No mixture shall be spread that cannot be finished and compacted during daylight hours. The mixture shall be spread only when the air temperature (the temperature in the shade away from artificial heat) is above 40°F for layers greater than one inch (100 lbs per square yard) in thickness and 45°F and above for layers one inch (100 lbs per square yard) or less in thickness (this includes leveling courses). No mixture shall be placed when there is evidence of a frozen base. The mixture shall not be spread when the wind is blowing to such an extent that proper and adequate compaction cannot be maintained or when sand, dust, etc., are being deposited on the surface being paved, to the extent that the bond between layers will be diminished.

3.

Mixing at the asphalt plant shall be sufficient to produce a thoroughly and uniformly coated mixture. The ingredients of the mix shall be heated and combined in such a manner as to produce a mixture, which shall be at a temperature, when discharged from the pugmill or surge bin, within the range of 230°F to 310°F and within the tolerance shown in the following table:

Temperature Tolerance From Job Mix Formula _________________________________________________________ Any Single Measurement . . . . . . . . . . . . . Average of Any Five Consecutive Measurements . .

+25°F +15°F

_________________________________________________________

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-7

However, the temperature of the mixture, in all cases, shall be such that will yield an asphalt Kinematic viscosity within the range of 280 and 150 centistokes. The mix temperature will be taken at the plant on the first five loads each day and on an average of once every five loads thereafter. Take corrective action if the temperature fails to fall within the specified tolerance. 4.

The maximum time that any mix may be kept in a hot storage or surge bin is 72 hours. Produce a homogeneous mixture, free from moisture and with no segregated materials, that meets all requirements of the specifications for the mixture, including compliance with the design limits. These requirements shall apply also to all mixes produced by the drum mixer process and all mixes processed through a hot storage or surge bin, both before and after storage.

5.

The mixture shall be transported in tight vehicles previously cleaned of all foreign material and each load shall be covered. The inside surface of the truck bodies shall be thinly coated with soapy water or an emulsion containing not over 5% of oil. Kerosene, gasoline or similar products shall not be used. After the truck bodies are coated and before any mixture is placed therein, they shall be raised so that all excess liquids will be drained out.

6.

Prior to the laying of the mixture, the surface of the base or pavements to be covered shall be cleaned of all loose and deleterious material by the use of power brooms or blowers, supplemented by hand brooming where necessary.

7.

All asphaltic concrete mixtures (including leveling courses), other than adjacent to curb and gutter or other true edges, shall be laid by the string-line method, to assure the obtaining of an accurate, uniform alignment of the pavement edge. The temperature of the mix at the time of spreading shall be within +25°F of the actual mix temperature. The minimum frequency for taking mix temperatures on the road will be an average of one per five trucks. Take corrective action if the temperature range fails to fall within the specified tolerance range. Any mixture caught in transit by a sudden rain may be laid at risk. Should such mixture prove unsatisfactory, it shall be removed and replaced with satisfactory mixture at no additional expense to the Owner. In no case shall the mixture be laid while rain is falling or when there is water on the surface to be covered. The forward speed of the spreader shall be as established by the manufacturer of the equipment and sufficient for an even application. For each paving machine being operated, a separate crew will be required; each crew operating as a full unit. The depth of each layer shall be checked at frequent intervals of approximately 25 feet. Any deviation below the design thickness as shown on the drawings shall be immediately corrected. In limited areas where the use of the spreader is impossible or impracticable, the mixture may be spread and finished by hand. Straight-edging and back-patching shall be done after initial compaction has been obtained and while the material is still hot.

8.

For courses other than leveling, upon arrival, the mixture shall be dumped into a mechanical spreader and immediately spread and struck-off to the full width required and to such loose depth for each course that, when the work is completed, the required weight of mixture per square yard, or the specified thickness, will be secured. An excess amount of mixture shall be carried ahead of the screed at all times. Hand raking shall be done behind the machine as required. If necessary due to the traffic requirements, the mixture shall be laid in trips in such manner as to

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-8

provide for the passage of traffic. Where the road is closed to traffic, the mixture may be laid to the full width, by machines traveling in echelon. Before any rolling is started the surface shall be checked, any irregularities adjusted, and all drippings, fat sandy accumulations from the screed, and fat spots from any source shall be removed and replaced with satisfactory material. No skin patching shall be done. When a depression is to be corrected while the mixture is hot, the surface shall be well scarified before the addition of fresh mixture. 9.

For leveling courses, all depressions in the existing surface more than one inch deep shall be filled by spot patching with leveling course mixture and then thoroughly compacted prior to spreading any leveling course. All leveling courses shall be placed by the use of two motor graders (one of which is equipped with a spreader box) unless otherwise shown in the plans. When the total asphalt mix provided for leveling exceeds 50 pounds per square yard, the mix shall be placed in two or more layers, with the average spread of any layer not to exceed 50 pounds per square yard. When Type S-III Asphaltic Concrete is used for leveling, the average spread of a layer shall not be less than 50 lbs per square yard nor more than 75 pounds per square yard. The quantity of mix for leveling shown in the plans represents the average for the entire project; however, the rate of application may vary throughout the project. When leveling in connection with base widening, all the leveling mix must be placed prior to the widening operation. When a leveling course is specified to be placed over cracked concrete pavement (including existing concrete pavement covered with an asphaltic surface), the first layer of leveling shall be placed as soon as possible but no later than 48 hours after cracking the concrete. The remainder of the leveling course shall be placed in the normal sequence of operations. Where a leveling course is to be placed over existing concrete pavement or bridge decks, the excess joint filler in the cracks and joints shall be trimmed flush with the surface prior to placing the first layer of the leveling course.

10.

For each paving or leveling train in operation, furnish a separate set of rollers, with their operators. The following equipment, sequence and coverage are only suggested for use based on past successful performance. Utilizing whatever equipment selected, the sequence and coverage of rolling shall meet the minimum density requirements specified:

11.

a.

Seal rolling by using tandem steel rollers weighing 5 to 12 tons, following as close behind the spreaders as is possible without pick-up, undue displacement or blistering of the material.

b.

Rolling with self-propelled pneumatic-tired rollers, following as close behind the seal rolling as the mix will permit. The roller shall cover every portion of the surface with at least five passes.

c.

Final rolling with the 8- to 12-ton tandem steel rollers, to be done after the seal rolling and pneumatic-tired rolling have been completed, but before the internal pavement temperature has dropped below 175°F.

The initial rolling shall be longitudinal. Where the lane being placed is adjacent to a previously placed lane, the center joint shall be pinched or rolled, prior to the rolling of the rest of the lane. After the rolling or pinching of the center joint, the rolling shall continue across the mat by overlapping each previous roller path by at least one-half the width of the roller wheel. The motion of the roller shall be slow enough to avoid displacement of the mixture, and any displacement shall be corrected at once by the use of rakes, and the addition of fresh mixture if required. Final rolling shall be

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-9

continued until all roller marks are eliminated. Rolling with the self-propelled, pneumatic-tired rollers shall proceed at a speed of 6 to 10 miles per hour, and the area covered by each roller shall not be more than 4,000 square yards per hour, except that for Type S Asphaltic Concrete, this maximum rate of coverage shall be 3,000 square yards per hour. a.

A sufficient number of self-propelled pneumatic-tired rollers shall be used such that the rolling of the surface for the required number of passes will not delay any other phase of the laying operation nor result in excessive cooling of the mixture before the rolling is complete. In the event that the rolling falls behind, the laying operation shall be discontinued until the rolling operations are sufficiently caught up.

b.

Areas which are inaccessible to a roller (such as areas adjacent to curbs, headers, gutters, bridges, manholes, etc.) shall be compacted by the use of hand tamps or other satisfactory means.

c.

Self-propelled pneumatic-tired rollers shall be used for the rolling of all patching and leveling courses. Where the initial leveling course is placed over broken concrete pavement, the pneumatic-tired roller shall weigh at least 15 tons. For Type S-III Asphaltic Concrete leveling courses, the use of a steelwheel roller, to supplement the traffic rollers, will be required. On other leveling courses, the use of a steel-wheeled roller will be required on all passes after the first.

d.

The rollers shall not be allowed to deposit gasoline, oil or grease onto the pavement, and any areas damaged by such deposits shall be removed and replaced. While rolling is in progress, the surface shall be tested continuously and all discrepancies corrected to comply with the surface requirements. All drippings, fat or lean areas and defective construction of any description shall be removed and replaced. Depressions which develop before the completion of the rolling shall be remedied by loosening the mixture and adding new mixture to bring the depressions to a true surface. Should any depression remain after the final compaction has been obtained, the full depth of the mixture shall be removed and replaced with sufficient new mixture to form a true and even surface. All high spots, high joints and honeycomb shall be corrected. Any mixture remaining unbonded after rolling shall be removed and replaced. Any mixture which becomes loose or broken, mixed or coated with dirt or in any way defective, prior to laying the wearing course shall be removed and replaced with fresh mixture which shall be immediately be compacted to conform with the surrounding area. Areas of defective surface may be repaired by the use of indirect heat. No method of repair involving open-flame heaters shall be used.

12.

Shoulder pavements wider than 5-1/2 feet shall be compacted by the use of equipment of the type required for other asphaltic concrete pavements. Compaction of asphaltic concrete 5-1/2 feet or less in width, shall be done by the use of tandem steel rollers not exceeding 12 tons in weight. Other compaction in such restricted widths shall be by the use of rubber-tired equipment.

14.

The density of a completed course shall be at least 94% of the laboratory density.

15.

Placing of the mixture shall be as continuous as possible and the roller shall not pass over the unprotected end of the freshly laid mixture except when the laying operation

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-10

is to be discontinued long enough to permit the mixture to become chilled. When the laying operation is thus interrupted, a transverse joint shall be constructed by cutting back on the previous run to expose the full depth of the mat. 16.

Where only a portion of the width of pavement is to be laid and opened to traffic, longitudinal joints shall be formed by rolling the exposed edge of the strip first laid. When the adjacent strip is constructed, the Engineer may require the edge of the mixture in place to be trimmed back to expose an unsealed or granular vertical surface. Where the strip first laid is closed to traffic, the edge shall not be sealed but shall be left vertical and the adjacent strip placed against it without trimming.

17.

When fresh mixture is laid against the exposed edges of joints (trimmed or formed as provided above), it shall be placed in close contact with the exposed edge so that an even, well-compacted joint will be produced after rolling.

18.

The finished surface shall be of uniform texture and compaction and shall be smooth. The surface shall have no pulled, torn, or loosened portions and shall be free of segregation, sand streaks, sand spots, or ripples. Any area of the surface which does not meet the foregoing requirements shall be corrected.

19.

All pavements (both intermediate and final courses), intersections, acceleration lanes, deceleration lanes, tapers, crossovers, transitions at beginning and end of project, and similar areas shall be tested with a straightedge for surface tolerance. Any individual surface irregularity in these areas in excess of 3/16-inch as determined by a 15-foot straightedge shall be corrected and retested. Provide a 15foot manual straightedge at the job site at all times during the paving operation for checking joints and surface irregularities.

20.

If the Owner elects to waive corrections, the appropriate pay quantity for Asphaltic Concrete shall be reduced by the equivalent quantity of materials which would have been removed and replaced if the correction had been made.

21.

a.

Where the pay quantity is in square yards, the reduction is based on the area which would have been removed multiplied by the ratio of the layer thickness to the total thickness of the type of mix specified.

b.

Where the pay quantity is in tons, the reduction is based on the volume which would have been removed (length x lane width x layer thickness) multiplied by the laboratory density for the mix.

c.

Where the project is a lump sum pay quantity based on amount completed, the appropriate reduction in percent complete shall be calculated based on the total amount of paving.

Select one of the following correction methods unless overlaying is prohibited. a.

Removing and Replacing: If correction is made by removing and replacing the pavement, the removal must be for the full depth of the course and extend at least 50 feet on either side of the defective area, for the full width of the paving lane.

b.

Overlaying: If correction is made by overlaying, the overlaying shall cover the length of the defective area and taper uniformly to a featheredge thickness at a minimum distance of 50 feet on either side of the defective area. The overlay

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-11

shall extend full width of the roadway. Care shall be taken to maintain the specified cross and lengthwise slopes. 22.

All corrective work, either by removing and replacing or by overlaying, including the bituminous material, shall be provided at no additional cost to the Owner.

23.

Sections of newly compacted asphaltic concrete which are to be covered by additional courses shall be kept clean until the successive course is laid.

24.

Blade graders operating adjacent to the pavement during shoulder construction shall have a 2-inch by 8-inch (or larger) board (or other attachment providing essentially the same results) attached to their blades in such manner that it extends below the blade edge, in order to protect the pavement surface from damage by the grader blade.

25.

Vehicular traffic shall not be permitted on any pavement which has not hardened sufficiently to prevent rutting or other distortion. The specified thickness and density is the minimum to be supplied and any deficiency(s) shall be corrected either by replacing the full thickness for a length extending at least 50 feet from each end of the deficient area, or (when permitted by the Owner) by overlaying with a minimum thickness of 75% of the specified thickness.

26.

B.

C.

Asphalt Base Courses 1.

General: The construction requirements for asphalt base course construction shall be as specified in this section with the following modifications and specific requirements.

2.

Tacking Between Layers: A tack coat shall be placed between each successive layer of base material.

3.

Placing the Mixture: a.

Spreading and Finishing: The base course material shall be placed with a mechanical spreading and finishing machine meeting the requirements of this section.

b.

Automatic Screed Control: For all machine-laid courses, the paver shall be equipped with automatic screed control of the ski or traveling string line type. The automatic joint matcher shall be used on the top course of the base after the first pass with the paving machine.

c.

Thickness of Layers: Unless otherwise shown, the maximum compacted thickness of any layer of asphalt base course shall be 3 inches.]

Saw-Cutting Where existing pavement is to be removed, except brick, saw-cut the surface leaving a uniform and straight edge with minimum disturbance to the remaining adjacent surface.

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-12

D.

Settlement of Pavement All settlement of pavement repairs occurring within a period of one year after final acceptance of the project by the Owner shall be repaired or replaced as required by and at no cost to the Owner.

E.

Testing 1.

F.

Unless otherwise stipulated on the plans, the following tests will be made by an independent testing laboratory. a.

Extraction of the asphaltic concrete and sieve analysis of the aggregate.

b.

Determination of bitumen content of the asphaltic concrete.

c.

Core borings (approximately every 200 feet) to determine thickness and density.

d.

Marshall stability.

Repairs Repair holes made to test the finished asphalt. END OF SECTION

ASPHALT PAVEMENT 60060986 - March 24, 2010

321215-13

SECTION 321313 PART 1 A.

PORTLAND CEMENT CONCRETE PAVING

- GENERAL

Description This section includes materials, testing, and installation of unreinforced portland cement concrete pavement, aggregate base course, and herbicide.

B.

C.

Related Work Specified Elsewhere 1.

Concrete Joints, Water Stops, and Sealants: 031510.

2.

Concrete: 033000.

3.

Earthwork: 312300.

4.

Concrete Curbs, Gutters, and Sidewalks: 321613.

Submittals Submit six copies of a report from a testing laboratory verifying that aggregate material contains less than 1% asbestos by weight or volume and conforms to the specified gradations or characteristics.

D.

Testing for Compaction 1.

The OWNERS representative will test for compaction as described in Section 312300.

2.

Compaction tests will be performed for each lift or layer.

3.

Determine laboratory moisture-density relations of soils by ASTM D698.

4.

Determine the relative density of cohesionless soils by ASTM D4253 and D4254.

5.

Sample backfill materials by ASTM D75.

6.

"Relative compaction" is the ratio, expressed as a percentage, of the inplace dry density to the laboratory maximum dry density.

7.

Compaction shall be deemed to comply with the specifications when no test falls below the specified relative compaction. The Contractor shall pay the costs of any retesting of work not conforming to the specifications.

PART 2 A.

- MATERIALS

Concrete Concrete shall be Class B per Section 033000.

PORTLAND CEMENT CONCRETE PAVING 60060986 - March 24, 2010

321313-1

B.

Joint Sealant See Section 031510.

C.

Aggregate Base Course Aggregate base shall be FDOT No. 57 coarse aggregate.

PART 3 A.

B.

- EXECUTION

Preparation of Subgrade 1.

Excavate and shape subgrade to line, grade, and cross section shown in the drawings. The subgrade shall be considered to extend over the full width of the base course.

2.

Remove soft material disclosed by the subgrade preparation, replace with structural backfill material per Section 312300 and recompact.

3.

Compact the top 12 inches of subgrade to 90% relative compaction.

4.

The finished subgrade shall be within a tolerance of ±0.08 of a foot of the grade and cross-section shown and shall be smooth and free from irregularities and at the specified relative compaction.

Installing Wood Headers Provide wood header at edges of paving except where paving is adjacent to concrete slabs, gutters, walks, existing paving, or structures.

C.

Placing Aggregate Base Course Place aggregate base course of No. 57 mixed into structural material and placed at a thickness of 6 inches, unless shown otherwise in the drawings. Compact to 95% relative compaction.

D.

Compaction of Aggregate Base and Leveling Courses Compaction and rolling shall begin at the outer edges of the surfacing and continue toward the center. Apply water uniformly throughout the material to provide moisture for obtaining the specified compaction. Compact each layer to the specified relative compaction before placing the next layer.

E.

Placing and Installing Concrete Paving 1.

Producing, hauling, placing and installing, compacting, curing, and finishing of concrete paving shall conform to FDOT Specifications.

2.

Place concrete paving to a minimum thickness of 8 inches, unless otherwise shown in the drawings.

PORTLAND CEMENT CONCRETE PAVING 60060986 - March 24, 2010

321313-2

F.

3.

Construct to line and grade shown. Finished pavement shall present a uniform appearance for both grade and alignment. Remove any section of pavement showing abrupt changes in alignment or grade.

4.

Place, process, finish, and cure concrete in conformance with Section 033000.

5.

Place preformed asphaltic expansion joints at pavement perimeters, curbs, and around posts, poles, or other objects protruding through the pavement.

6.

Provide contraction joints at 12 foot spacing in both directions. These joints shall be weakened plane joints 3/16 inch wide by 1/4 of the slab thickness deep with a minimum depth of 1-1/2 inches. They shall be straight, at right angles to the pavement surface, and to each other where possible. Joint lines shall terminate only at pavement edges or expansion joints. Panels defined by contraction joints shall not exceed a length-to-width ratio of 1.5 to 1.

7.

Broom the surface with a fine-hair broom or machine equivalent.

8.

Remove and replace defective concrete.

Surface Tolerance 1.

Finished grade shall not deviate more than 0.02 foot in elevation from the grade indicated in the drawings. Slopes shall not vary more than 1/4 inch in 10 feet from the slopes shown in the drawings.

2.

After paving has been installed and compacted, spray water over the entire paved area. Correct any areas where water collects and does not drain away.

END OF SECTION

PORTLAND CEMENT CONCRETE PAVING 60060986 - March 24, 2010

321313-3

SECTION 321613 PART 1 A.

CONCRETE CURBS, GUTTERS, AND SIDEWALKS

- GENERAL

Description This section includes materials and installation of concrete curbs, gutters, and sidewalks.

B.

C.

D.

Related Work Specified Elsewhere 1.

Concrete Formwork: 031110.

2.

Concrete Joints, Water Stops, and Sealants: 031510.

3.

Concrete Reinforcement: 032100.

4.

Concrete: 033000.

5.

Concrete Finishing and Curing: 033500.

6.

Earthwork: 312300.

Submittals 1.

Submit shop drawings in accordance with the General Provisions, Section 013300, and the following:

2.

Submit six copies of a report from a testing laboratory verifying that crushed rock and aggregate material contains less than 1% asbestos by weight or volume and conforms to the specified gradations or characteristics.

Testing for Compaction 1.

The City will test for compaction as described below.

2.

Determine the density of soil in place by the sand cone method, ASTM D 1556 or by nuclear methods, ASTM D 2922 or D 3017. Compaction tests will be performed for each lift or layer.

3.

Determine laboratory moisture-density relations of soils by ASTM D 1557.

4.

Determine the relative density of cohesionless soils by ASTM D 4253 and D 4254.

5.

Sample backfill materials by ASTM D 75.

6.

"Relative compaction" is the ratio, expressed as a percentage, of the inplace dry density to the laboratory maximum dry density.

7.

The Contractor shall pay the costs of any retesting of work not conforming to the specifications.

CONCRETE CURBS, GUTTERS, AND SIDEWALKS 60060986 - March 24, 2010

321613-1

E.

Standard Specifications Wherever reference is made in this section to the State Specifications, such reference shall be understood to mean the Florida Department of Transportation Standard Specifications for Road and Bridge Construction, latest edition.

PART 2 A.

B.

- MATERIALS

Forms 1.

Forms shall conform to the requirements of Section 031110. Provide stakes and bracing materials to hold forms securely in place.

2.

Materials for sidewalk forms shall be 2-inch dressed lumber straight and free from defects, or standard metal forms. Where short-radius forms are required, 1-inch dressed lumber or plywood may be used. Provide stakes and bracing materials to hold forms securely in place.

Expansion Joint Filler Expansion joint filler shall be 1/2 inch thick for curbs and 1/4 inch thick for sidewalks and shall conform to premolded joint filler in Section 031510.

C.

Concrete Concrete shall be per Section 033000, Class I per Section 345 in the Florida State Specifications.

D.

Reinforcing Steel Conform to Section 032100 415 in the Florida State Specifications.

E.

Curing Compound Curing compound shall be as specified in Section 033500.

F.

Excavation and Backfill Conform to Section 312300.

PART 3 A.

- EXECUTION

Preparation of Subgrade Excavate and shape subgrade to line, grade, and cross-section. Compact subgrade until the top 12 inches are compacted to 95% relative compaction. Remove all soft material disclosed by compacting and replace with crushed rock base. The finished subgrade shall be within a tolerance of ±0.08 of a foot of the grade and cross-section shown and shall be smooth and free from irregularities at the specified relative compaction. The subgrade shall be considered to extend over the full width of the base course.

CONCRETE CURBS, GUTTERS, AND SIDEWALKS 60060986 - March 24, 2010

321613-2

B.

C.

Setting Forms 1.

Conform to Section 031110.

2.

Forms on the face of the curb shall not have any horizontal joints within 7 inches of the top of the curb. Brace forms to prevent change of shape of movement in any direction resulting from the weight of the concrete during placement. Construct short-radius curved forms to exact radius. Tops of forms shall not depart from gradeline more than 1/8 inch when checked with a 10-foot straightedge. Alignment of straight sections shall not vary more than 1/8 inch in 10 feet.

Curb Construction 1.

D.

Construct curbs to line and grade shown. Curbs shall conform to the details shown.

Sidewalk Construction 1.

Sidewalks shall be 4 inches thick in walk areas and 6 inches thick in driveway areas, unless otherwise shown in the drawings. Walks shall slope 1/4 inch per foot away from structures, unless otherwise shown in the drawings.

2.

At locations where the new sidewalk is to abut existing concrete, saw concrete for a depth of 2 inches, chip the old concrete down to sound material and a plane surface, clean the surface, and apply a neat cement paste just prior to pouring the new sidewalk.

3.

Place preformed asphalt expansion joints at intervals not exceeding 45 feet or less than 15 feet, where the sidewalk ends at a curb, and around posts, poles, or other objects protruding through the sidewalk. Place expansion joints between sidewalks and buildings or other structures.

4.

Place preformed asphalt expansion joint material between back of curbs and sidewalks.

5.

Provide contraction joints transversely to the walks at locations opposite the contraction joints in the curb and at intervals along the sidewalk such that the distance between contraction joints does not exceed 1.5 times the sidewalk width. These joints shall be 3/16 inch by one-fourth of the slab thickness weakened plane joints. They shall be straight and at right angles to the surface of the walk.

6.

Place, process, finish, and cure concrete in conformance with Section 033000.

7.

Broom the surface with a fine-hair broom at right angles to the length of the walk and tool at all edges, joints, and markings. Mark the walks transversely at 5-foot intervals with a jointing tool. Upon completion of the finishing, apply a curing compound to exposed surfaces. Protect the sidewalk from damage.

8.

Finished sidewalk shall present a uniform appearance for both grade and alignment. Remove any section of sidewalk showing abrupt changes in alignment or grade or that is more than 2 inches away from its location as shown in the drawings and construct new sidewalk in its place at no additional cost to the Owner. END OF SECTION

CONCRETE CURBS, GUTTERS, AND SIDEWALKS 60060986 - March 24, 2010

321613-3

SECTION 321723 THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS PART 1 - GENERAL A.

Description 1.

This section includes materials, testing and installation of traffic stripes and markings including reflective materials and markers, edge stripes and traffic guides.

2.

The thermoplastic compound shall be extruded or sprayed onto the pavement surface in a molten state by mechanical means, with surface application of glass spheres, when required, and upon cooling to ambient pavement temperature shall produce an adherent pavement marking of specified thickness and width and capable of resisting deformation. Preformed materials which are directly applied to the pavement will be permitted as an alternate to the extruded or sprayed application technique for pavement messages and transverse markings only.

B.

3.

The color of the compound shall be black, white or yellow, as specified in the plans.

4.

Also included in this section are reflective pavement markers (RPM).

Submittals Submit certificates to the Owner, from the manufacturer or a testing laboratory (acceptable to the Owner) showing that the materials, gradation and testing conforms with the requirements of these specifications.

C.

Standards These specifications generally conform to the FDOT Roadway and Traffic Design Standards, Federal Standards as modified herein.

PART 2 - PRODUCTS A.

Thermoplastic Compound 1.

2.

Composition: a.

The compound shall consist of a mixture of appropriate organic binders (20 percent by weight minimum), titanium dioxide (8 percent by weight minimum), black pigment, or yellow pigment, reflective glass spheres (20 percent by weight minimum), and calcium carbonate or other suitable filler.

b.

Upon application, the pigment, spheres and filler shall be well dispersed in the resin. The material shall be free from skins, dirt, and foreign objects and shall be of such composition that it will not bleed, stain, or discolor when applied to bituminous pavements.

Physical Requirements:

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010

321723-1

a.

Color: The white compound shall be pure white and free from dirt or tint. As demonstrated by a standard color difference meter, such as the Gardner Color Difference Meter, manufactured by Gardner Laboratories, Inc., Bethesda, Maryland, the material shall not show percent deviations from a magnesium oxide standard that are greater than the following:

Scale Definition

Magnesium Oxide Standard

Rd Reflectance Redness-Greeness Yellowness-Blueness 1)

100 0 0

Sample 70 min. minus 5 to plus 5 minus 10 to plus 10

The color of the yellow compound shall visually match that of color chips prepared from Code T-2, FDOT Standard yellow traffic paint, using a pigment composition of : medium chrome yellow 25% calcium carbonate 50% magnesium silicate 25% The visual comparison shall be made under natural daytime light, north facing. In the event of questionable visual matches the color of the material shall be determined by Federal Test Method Standard 141, Method 4252 and shall fall within these limits: Reflectance 49% to 66% Chromaticity coordinates, x, y shall fall in an area bounded by these coordinates: x 0.476 0.493 0.516 0.498 y 0.455 0.467 0.444 0.433

2)

The color of the black compound shall visually match that of color chips prepared from Code T-3, FDOT Standard black traffic paint.

b.

Color Retention: Retention of the initial color shall be determined by the following procedure: Specimens shall be prepared and tested from samples submitted in accordance with ASTM D 795-65T. The ultraviolet light source shall be as specified in the test procedure, or may be a General Electric 275watt sun lamp Type RS, with a built-in reflector. After 100 hours of exposure the test specimens shall show no perceptible color change (as indicated by comparison with an unexposed specimen).

c.

Water Absorption: The compound shall have no more than 0.5 percent, by weight, of retained water, when tested in accordance with ASTM D 570.

d.

Softening Point: The compound shall have a softening point of not less than 90°C, as determined by ASTM E 28.

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010 (SA321723 - THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS.docx)

321723-2

e.

f.

Low Temperature Stress Resistance: Test block samples shall not crack or fail to adhere to the substrate when tested as follows: 1)

A sample coated with not less than 32 square inches of the compound shall be immersed in cold water for one hour, then immediately placed in a freezer chest or other insulated cold compartment and maintained at a temperature of minus 10°C for 24 hours. After 24 hours the sample shall be removed from the cold compartment and allowed to come to normal room temperature. The compound shall shown no cracking or flaking off when examined following the exposure cycle.

2)

Test block samples shall show no evidence of fracture when subjected to an impact of 64 inch pounds at -10°C.

Reheating: The compound shall not break down or deteriorate if held at the plastic temperature for a period of four hours, or by reason of four reheatings to the plastic temperature. 1)

The temperature vs. viscosity characteristics of the plastic compound shall remain constant through up to four reheatings, and shall be the same from batch to batch.

g.

Safety: In the plastic state, the material shall not give off fumes which are toxic or otherwise injurious to persons or property.

h.

Specific Gravity: The specific gravity of the compound as determined by the water-displacement method, at 25°C, shall be between 1.9 and 2.5 (referred to water at 25°C).

i.

Drying Time: When at 70°F (21°C) in a thickness of between 0.125 inch (3.2 mm) and 0.188 inch (4.8 mm), the compound shall be completely solid and show no effect of tracking after 15 minutes.

j.

Indentation Resistance: Hardness shall be measured by a Shore Durometer, Type A2, as described in ASTM D 2240, except that the durometer and the panel shall be at least 25°C, and a two kilogram load applied. After 15 seconds, the reading shall be not less than 65.

k.

Abrasion Resistance: The material shall not show a loss greater than 0.5 grams when subjected to 200 revolutions on a Taber Abraser at 25°C, using H22 calibrase wheels, weighted to 500 grams. The wearing surface should be kept wet with distilled water throughout the test. The panel for this test shall be prepared by forming a representative lot of material at a thickness of 0.125 inches on a 4-inch square monel panel (thickness 0.050 + 0.0001 inch) on which a suitable primer has been previously applied. 1)

Infrared Spectra: a)

The color of the black compound shall visually match that of color chips prepared from Code T-3, FDOT Standard black traffic paint.

b)

Infrared spectra of the extracted-binder shall be a "fingerprint" match of the standard curves to be found on file at the FDOT Central laboratory.

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010

321723-3

B.

Sealing Primer The particular type and the proportions used shall be as recommended by the manufacturer of the thermoplastic compound.

C.

Glass Spheres 1.

2.

General: a.

Glass spheres shall provide a reflective surface that creates night visibility of the painted stripes and markings without altering day visibility of the stripes and markings.

b.

The reflective glass spheres premixed in the compound and used for surface application shall be of a composition designed to be highly resistant to traffic wear and to the effects of weathering.

Moisture Resistance: a.

The spheres shall pass the following moisture-resistance test: 1)

3.

Place a 300-gram portion of the air-dry sample in a 250-ml. Erlenmeyer flask; add 5 drops of water from a pipette calibrated to produce 20 drops per ml. (+ 1 drop); stopper the flask immediately and shake the flask and its contents vigorously for at least one minute. Remove the stopper and connect the flask mouth-to-mouth to another air-dry flask of the same size in hour-glass fashion, by means of stoppers joined by a short glass tube having an inside diameter of 1/4-inch; invert the assembly and observe the flow qualities of the beads. The beads shall then flow continuously into the lower flask until the upper flask is emptied. The flask may be gently tapped to initially start the flow of beads, after which the beads shall flow continuously without further agitation. If, after three trials, the beads fail to flow continuously, the sample shall be reported as failing the moisture-resistance test. A small quantity of beads sticking to the sides of the flask shall not be cause for rejection.

Physical Requirements: a.

The spheres shall contain not less than 75 percent spherical particles overall, and not less than 70 percent spherical particles on any sieve, when tested in accordance with ASTM D 1155. The quantity of sharp angular particles shall not exceed one percent. Particles showing milkiness, scoring or scratching shall not exceed two percent, and foreign matter shall not exceed one percent.

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010 (SA321723 - THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS.docx)

321723-4

4.

Gradation: a.

Type I (Drop-on Type): Type I spheres shall meet the following gradation requirements, when tested in accordance with ASTM D 1214 "Method of Test for Sieve Analysis of Glass Spheres". U.S. Standard SievePercent Passing No. 40 No. 50 No. 80 No. 100

b.

90-100 25-50 0-5 0-2

Type II (Premixed with Pigmented Binder): Type II spheres shall meet the following requirements for gradation (U.S. Standard Sieve):

5.

D.

E.

Passing

Retained

Percent

No. 60 No. 80 No. 200

No. 60 No. 80 No. 200

0-1 10-15 0-10

Index of Refraction (Both Types): The spheres, when tested by the liquid immersion method, at 25°C shall show an index of refraction within the range of 1.50 to 1.65. The spheres shall not show any tendency toward decomposition, including surface etching, when exposed to atmospheric condition, moisture, dilute acids, alkalies or paint film constituents. The spheres shall be crystal in color, and free from all surface film. They shall be corrected to prevent their imparting any noticeable daytime hue to the paint film.

Properties of Finished Stripping and Marking Installation 1.

The stripe shall not be slippery when wet.

2.

The compound shall not lift from the pavement in freezing weather.

3.

The compound shall not deteriorate by contact with sodium chloride, calcium chloride or oil drippings from traffic.

4.

After application and proper drying time the stripe shall show no appreciable deformation or discoloration under traffic and under road temperatures up to 140°F, (60°C).

5.

The stripe or marking shall maintain its original dimensions and placement. The exposed surface shall be free from tack. Cold ductility of the material shall be such as to permit normal movement with the road surface without chipping or cracking.

Reflective Pavement Markers 1.

Description:

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010

321723-5

a.

b.

2.

Types: 1)

Type 1 Markers shall have amber bi-directional reflective faces.

2)

Type 2 Markers shall have bi-directional reflective faces. One face shall be colorless and the other face shall be colored red.

3)

Type 3 Markers shall have bi-directional reflective faces. One face shall be colored red and the other face shall be colored amber.

4)

Type 4 Markers shall have an amber mono-directional reflective face.

5)

Type 5 Markers shall have a colorless mono-directional reflective face.

Class: 1)

Class A Markers shall meet the specific intensity requirements as herein specified, except that the reflective face treatment is not required.

2)

Class B Markers shall meet the specific intensity requirements as herein specified including reflective face treatment.

Materials: a.

b.

General: 1)

The marker shall consist of a molded methyl methacrylate or an acrylonitrile butadine styrene (ABS) shell filled with a mixture of an inert thermostating compound and filler material.

2)

Methyl methacrylate shall conform to the requirements of Federal Specification L-P380C, Type 1, Class 3.

3)

The marker shall have a maximum width of 5 inches and a maximum height of 0.75 inch. The minimum area of each reflective face shall be 3.25 square inches. The outer surface shall be smooth and all corners and edges exposed to traffic shall be rounded. The base shall be substantially free of glass or substances that may reduce their bond to adhesive.

Strength Requirements: 1)

Marker Strength: a)

The marker shall support a load of 2,000 pounds when centered over the open end of a vertically positioned hollow metal cylinder. The cylinder shall be 1-inch high, with an internal diameter of 3 inches and a wall thickness of 0.25 inch. The load shall be slowly applied to the top of the marker through a 1-inch diameter by 1inch high metal plug centered on top of the marker.

b)

Failure shall constitute either breakage or significant deformation of the marker at any load less than or equal to 2,000 pounds. Should

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010 (SA321723 - THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS.docx)

321723-6

the marker fail the strength test, four additional markers shall be tested and the failure of anyone of the four markers shall be cause for the rejection of the entire lot or shipment. 2)

c.

Reflective Face Strength: a)

The Reflective Face Strength Tests shall only be applied to Class B Markers. The red reflective face of Type 2 and Type 3, Class B Marker shall not be subjected to this test.

b)

The marker shall be placed in a convection oven at 130°F for one hour. While at the elevated temperature, the face shall be impacted by a 0.2 pound dart fitted with a 0.25-inch radius spherical head falling perpendicularly onto the surface from a height of 6 inches.

c)

The impact area shall exhibit only concentric cracks. Failure shall constitute any radial cracks along the area. Should the marker fail, four additional markers shall be tested. The failure of any one of the four markers shall be cause for rejection of the entire lot.

Optical Requirements: 1)

2)

Definitions: a)

Horizontal entrance angle: The angle in the horizontal plane between the direction of incident light and the normal to the leading edge of the marker.

b)

Observation angle: The angle at the reflector between the observer's line of sight and the direction of the light incident on the reflector.

c)

Specific intensity: Candlepower of the returned light at the chosen observation and entrance angles for each foot-candle of illumination at the reflector on a plane perpendicular to the incident light.

Specific Intensity: a)

The specific intensity of each colorless reflective face of the marker at 0.2 degree observation angle shall not be less than the following when (1) the incident light is parallel to the base of the marker, (2) the reflective face has been subjected to the optical testing procedure specified in herein.

Horizontal Entrance Angle 0 Degree 20 Degree b)

Specific Intensity

3.0 1.2 The specific intensity of amber reflective faces shall be equal to or greater than 60 percent of the value for colorless faces.

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010

321723-7

c) 3)

The specific intensity of red reflective faces shall be equal to or greater than 20 percent of the value for colorless faces.

Optical Testing Procedure: a)

The markers to be tested shall be located with the center of the reflecting face at a distance of five feet from a uniformly bright source having an effective diameter of 0.2 inch.

b)

The photocell width shall be 0.5 inch. It shall be shielded to eliminate stray light. The distance from light source center to the photocell center shall be 0.21 inch. It a test distance other than five feet is used, the source and receiver dimensions and the distance between source and receiver shall be modified in the same proportion as the test distance.

c)

A random sample of five markers will constitute a representative sample for a lot. If more than one marker fails the initial test, a new sample (five markers) may be tested. Failure of more than one marker in the retest shall be cause for rejection of the entire lot.

d)

Reflective Face Treatment for Class B Markers: The reflective face of Class B Markers shall be prepared in accordance with the following procedure prior to measuring the specific intensity: (1)

d.

A pad 1-inch in diameter shall be formed from No. 3 coarse steel wool which conforms to Federal Specification FF-W1825. Place the steel wool on the reflective face. The entire reflective face shall be rubbed 100 times with an applied load of 50 pounds.

Adhesive: Thermoplastic or epoxy may be used for bonding the markers to the pavement. The thermoplastic adhesive shall be the same compound which is used for thermoplastic pavement markings. Epoxy adhesive for pavement markers shall be certified by the manufacturer that testing of the adhesive has demonstrated that not more than two percent of markers installed with the adhesive will fail within one year of installation due only to the failure of the adhesive.

PART 3 - EXECUTION A.

Equipment 1.

The material shall be applied to the pavement utilizing either extrusions or spray application equipment.

2.

The application equipment shall be so constructed as to provide continuous mixing and agitation of the material. Conveying parts of the equipment between the main material reservoir and the shaping die or gun shall be so constructed as to prevent accumulation and clogging. All parts of the equipment which come in contact with the material shall be so constructed as to be easily accessible and exposable for cleaning and maintenance. The equipment shall be constructed so that all mixing and conveying parts up to and including the shaping die or gun, maintain the material

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010 (SA321723 - THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS.docx)

321723-8

at the plastic temperature with heat transfer oil or electrical element controlled heat. Direct fire heat transfer will not be allowed.

B.

3.

The application equipment shall be so constructed as to insure continuous uniformity in the dimensions of the stripe. The applicator shall provide a means for cleanly cutting off square stripe ends and shall provide a method of applying "skip" lines. The use of pans, aprons, or similar appliances which the die overruns will not be permitted under this specification. The equipment will be so constructed as to provide for varying widths to produce varying widths of traffic markings.

4.

Glass spheres applied to the surface of the completed stripe shall be applied by an automatic bead dispenser attached to the striping machine in such a manner that the beads are dispensed almost instantaneously upon the installed line. The glass sphere dispenser cut-off shall be synchronized with the automatic cut-off of the thermoplastic material.

5.

Special kettle(s) shall be provided for melting and heating the thermoplastic material. The kettle(s) shall be equipped with automatic thermostatic control devices in order to provide uniform temperature control and prevent overheating of the material. The applicator and kettle(s) must be so equipped and arranged as to satisfy the requirements of the National Fire Underwriters, the State of Florida, and local authorities.

6.

Applications shall be mobile and maneuverable to the extent that straight lines can be followed and normal curves can be made in a true arc.

7.

The application equipment to be used on roadway installations shall consist of either hand equipment or truck mounted units depending on the type of marking required.

8.

The hand applicator equipment shall be insulated and shall have sufficient capacity to hold 150 pounds of molten material and shall be sufficiently maneuverable to install crosswalks, lane, edge, and center lines; arrows and legends. The truck mounted unit for lane, edge, and center lines shall consist of a mobile self contained unit carrying its own material capable of operating at a minimum speed of five miles per hour while installing striping.

Application 1.

Alignment: a.

2.

Establish tack points at appropriate intervals for use in aligning stripes and set a stringline from such points.

Tolerances in Dimensions and in Alignment: a.

Dimensions: 1)

Longitudinal Lines: a)

No stripe shall be less than the specified width. No stripe shall exceed the specified width by more than 1/2 inch.

b)

The length of the 10-foot painted segment for skip stripe, and the 30-foot gap between segments, may each vary plus or minus one

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010

321723-9

foot, except that over-tolerance and under-tolerance lengths shall approximately compensate. 2)

3.

Transverse markings, gore markings, arrows, and messages: When the specified width of the markings cannot be made with a single pass and multiple passes are required, the width of the line may vary by plus or minus 1 inch.

b.

Alignment: On tangents, and on curves up to one degree, the alignment of the painted stripe shall not deviate from the stringline by more than 1 inch. On curves exceeding one degree the maximum permissible deviation will be 2 inches. In addition, the outer edge of the edge stripe shall fall uniformly at not less than two nor more than 4 inches from the edge of the pavement, and shall have no noticeable breaks or deviations in alignment or width.

c.

Correction Rates: Any corrections of variations in the width or in the alignment of the stripes shall not be made abruptly but the stripes shall be returned to the design width at the rate of at least ten feet for each 1/2-inch of correction, and returned to the stringline at the rate of at least 25 lineal feet per inch of correction.

Time of Application: a.

Painting shall be done only during daylight hours and shall be terminated in time to permit sufficient drying by sunset.

b.

Placing of permanent pavement markings on newly constructed Friction Course 2 (FC-2) shall not be accomplished prior to 30 calendar days after placement of the friction course. Temporary pavement striping shall be required during the interim period if the road is open to traffic.

4.

Weather Limitations: No paint shall be applied when any moisture is present on the surface to be painted or when the air temperature is below 40°F. Painting shall not be done when winds are sufficient to cause spray dust.

5.

Preparation of Application Surface: The surface shall be cleaned, by compressed air or other effective means, immediately before the placement of thermoplastic compound, and shall be clean and dry when the thermoplastic compound is applied. Any vegetation or loose soil shall be removed from the pavement before edge striping is begun.

6.

Renewability: The material, when formed into traffic stripes or other markings must be readily renewable by placing an overlay of new material directly over an old line or marking of compatible material. Such new material shall bond itself to the old material in such a manner that no splitting or separation takes place.

7.

Sealing Primer: Sealing primer shall be sprayed on the road surface in a continuous film prior to application of the compound. Spraying shall be done by use of conventional mobile spray equipment in accordance with the manufacturer's recommendations.

8.

Application Temperature: This temperature shall be within the range specified by the manufacturer of the thermoplastic compound being used.

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010 (SA321723 - THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS.docx)

321723-10

9. 10.

Weather Limitations: No marking shall be applied when any moisture is present on the surface or when the air temperature is below 40°F. Thickness: a.

All pavement edge lines, gore, island and diagonal strip markings, bike lane symbols and messages, wherever located, shall have a minimum thickness of 0.060 inch at the edges and a maximum thickness of 0.120 inch at the center. A minimum average film thickness of 0.060 inch shall be maintained.

b.

All lane lines, center lines, transverse markings (except shoulder markings) and pavement markings within traffic wearing areas (such as dotted turning guide lines) shall have a minimum thickness of 0.90 inch at the edges and a maximum thickness of 0.188 inch at the center. A minimum average film thickness of 0.090 inch shall be maintained.

c.

All thickness measurements shall be an average in any three foot length.

d.

The glass sphere top coating shall be applied by a type of glass sphere dispenser or gun which will embed the spheres into the line surface to at least one-half their diameter. The glass sphere top coating shall not incur more than a 10 percent loss during the first 30 days of traffic exposure.

e.

Longitudinal lines shall be offset at least 2 inches from construction joints of Portland Cement Concrete Pavements.

11.

Application Over Existing Skip Traffic Stripe: When being applied over existing stripes, each stripe shall end with a clean cut-off free of tapers and drips. A longitudinal tolerance of plus or minus 2 inches at the beginning and end of each stripe and a horizontal tolerance of plus or minus 1/2 inch will be allowed. Skip traffic stripes not applied in accordance with these requirements shall be corrected at no expense to the Owner.

12.

Application of Spheres: a.

Reflective glass spheres shall be applied immediately behind the striping mechanism, at the rate of one pound of spheres for each 10 square feet of compound.

b.

Reflective glass spheres shall be applied to all white and yellow stripes or markings.

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010

321723-11

c.

To all thermoplastic bike lane symbols and longitudinal lines adjacent to or in a proposed bike lane, a mixture consisting of 50 percent glass spheres and 50 percent sharp silica sand shall be thoroughly pre-mixed and applied at a rate of two pounds for each ten square feet of thermoplastic surface. 1)

The sharp silica sand shall meet the following gradation requirements: U.S. Sieve Number 20 100 50 0-10

C.

D.

Percent Passing

Protection of Newly Marked Pavement 1.

Protection of Stripes: All new stripes, including edge stripes, shall be protected until the marking is sufficiently dry to permit vehicles to cross the stripe without damage from the tires.

2.

Protection of Traffic: Warning signs shall be set up before the beginning of each operation and extra signs shall be kept well ahead of the marking equipment. Warning signs are to be placed only where operations are in progress and are to be relocated as often as is necessary.

3.

Protective Devices: Erect adequate warning signs, provide a sufficient number or flagmen, and take all necessary precautions for the protection of the wet paint and the safety of the public. Cones, rubber "Z" guards or similar protective devices shall be placed along the newly painted stripe to prevent traffic from crossing the wet paint. Any such devices used shall be of a type that will not cause damage to vehicular traffic in the event that these objects are accidentally passed over. All protective devices shall be removed not later than sunset to allow free movement of traffic at night if roadway is open to traffic.

4.

Repair of Damaged Areas: Any portions of the stripes damaged by passing traffic or from any other cause shall be remarked at no expense to the Owner.

Corrective Measures 1.

All pavement markings which fail to meet the specifications, including the permissible tolerances and the appearance requirements, or are marred or damaged by traffic or from other causes, shall be corrected at no expense to the Owner.

2.

Reflective Pavement Markers: a.

General: Placement of the markers shall be in accordance with the FDOT's Roadway and Traffic Design Standards unless otherwise specified or indicated in the plans.

b.

Surface Preparation: The portion of the pavement surface or thermoplastic marking to which the marker is attached by the adhesive shall be cleaned of dirt, curing compound, grease, oil, moisture, loose or unsound pavement and any other material which would adversely affect the adhesive.

c.

The adhesive shall be spread on the bonding surface (not the marker) so that 100 percent of the bonding area of the marker will be covered. The adhesive application shall be of sufficient thickness so that when the marker is pressed

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010 (SA321723 - THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS.docx)

321723-12

into the adhesive, excess adhesive shall be forced out around the entire perimeter of the marker. All excessive adhesive shall be removed from in front of the reflective faces. If any adhesive or foreign matter adheres to the reflective face of the marker, the marker shall be replaced. d.

3.

Replacement Requirements: In the event that more than two percent of the markers fail in adhesion within the first 45 days under traffic, the Contractor shall replace all failed markers at his expense. If more than five percent of the markers fail in adhesion during the initial 45 day period, the replacement period shall be extended an additional 45 days from the date that all replacement markers have been installed. If, at the end of the additional 45 day period, more than two percent of all markers (initial installation and 45 day replacements combined) fail in adhesion, the Contractor shall replace all failed markers at his expense.

Whenever it is necessary to remove material it shall be done by means which will not damage the underlying surface of the pavement. END OF SECTION

THERMOPLASTIC TRAFFIC STRIPES AND PAVEMENT MARKINGS 60060986 - March 24, 2010

321723-13

SECTION 328420 PART 1 A.

LANDSCAPE IRRIGATION SYSTEM

- GENERAL

Description Under this item the Contractor shall furnish and install all materials and equipment for an automatic irrigation system in accordance with these plans and specifications. The Contractor shall provide all labor, material, construction equipment and technical supervision which may be required to produce an operational system. The automatic irrigation system shall consist of underground piping and sprinkler equipment to insure complete coverage of the areas as shown on the irrigation plan. Gate valves shall be incorporated in the system as shown on the plans to shut off certain portions of the system while allowing operation of the remaining sprinkler outlets.

B.

C.

D.

Related Work Specified Elsewhere 1.

Tree and Plant Protection: 020101.

2.

Trenching, Backfilling, and Compacting: 312316.

3.

Landscape Planting: 329010.

4.

Pressure Testing of Piping: 400515.

Description of the System 1.

Drawings are essentially diagrammatic. Size and location of equipment and fixtures are drawn to scale wherever possible.

2.

Provide offsets in piping and changes in equipment locations to conform with structures and to avoid obstructions or conflicts with other work.

3.

Do not exceed irrigation head spacing as shown in the drawings.

4.

Electrical work shall comply with the NEC.

Staking and Layout 1.

It is to be recognized, due to the artistic nature of landscape planting design and construction that the landscape planting as constructed may differ slightly from the plans drawn for construction of the irrigation system. The Contractor shall be prepared to adjust installation of the irrigation system so that it will properly irrigate planted features constructed in accordance with the evident intent of the irrigation plans, as interpreted by the Landscape Architect.

2.

The Contractor shall stake the location on the ground of all irrigation equipment to be installed. In staking the locations of the sprinkler outlets, he shall adjust the staking as required to best irrigate the area being developed and shall strive to maintain a uniform spacing between the various outlets. This spacing may vary

LANDSCAPE IRRIGATION SYSTEM 60060986 - March 24, 2010

328420-1

according to manufactures recommendations where adjustment of spacing is required to fit the landscape development as constructed. Routing of the pipe shall be in accordance with the irrigation piping plan except that the Landscape Architect reserves the right to change the routing of pipe from that shown on the plan and to change the depth of trench and cover over the top of pipe in case of rock or other obstacle. In no event shall field changes of this nature affect the overall cost of the project except where these changes may alter the quantity of materials to be provided according to the plan. The Contractor may adjust the location of any pipeline to avoid ledge rock, stumps or other obstacles, provided that such adjustment does not increase the quantity of pipe required and is not in conflict with the evident intent of the plan.

E.

3.

See irrigation plan for connections to water source, pipe sizes and location, heads and valves. Time clock(s)/ controller(s) shall be located at the direction of the Landscape Architect.

4.

The Irrigation Contractor shall carefully review bed and paving cut-out locations, walks, roads, property lines and other site features and install his work according to the intent of the irrigation plan. Should heads and/or lines or other system components be improperly located they shall be properly relocated at the contractors expense.

Submittals 1.

Submit shop drawings in accordance with the General Provisions, Section 013300 and the following:

2.

Submit schedule including coordination of electrical and water connections and the placement of materials and equipment.

3.

Submit material list using the following format (double spaced between each item): Item No.

Manufacturer

Model No.

1.

Pressure supply lines

Lasco

Schedule 40

2.

Lawn head

Rain-bird

#171-D-HP

Etc.

Etc.

Etc.

Etc. 4.

Description

Submit shop drawings of fabricated components and installations.

LANDSCAPE IRRIGATION SYSTEM 60060986 - March 24, 2010

328420-2

F.

G.

Definitions 1.

The following definitions are in addition to, supplement, and/or complement these set forth elsewhere in these specifications, wherever the following terms, or pronouns in place of them, are used in these specifications, their intent and meanings shall be interpreted as follows: SW: Solvent weld PVC pipe and/or fittings. RG: Rubber gasketed or O-ring PVC pipe and/or fittings. QCV: Quick coupler valve, as specified. HB: Hose bibb, as specified.

2.

SLEEVE: A conduit for encompassing other pipes, wires, cables, etc. with the purpose of presenting ease of access and/or replacement of such pipes, wires, cables, etc. within otherwise difficult to access areas.

Operation and Maintenance Manuals Provide installation, operation, and maintenance manuals from manufacturers and suppliers. See Section 019310.

H.

Record Drawings 1.

The Contractor shall maintain at all times an up-to-date record plan of the irrigation system as built. The plan shall indicate the location and measurements, to the nearest foot, of all mainline pipe installed, including all automatic and gate valves; splice boxes; main line tees, elbows and fittings; pulse and common control wire routings; equipment locations; sleeve locations; and, the contractor shall make such modifications to any notes and/or details as appropriate to show the final installed condition of the overall system. The record plan shall be drawn on a copy of an original plan, drawn in black ink at the scale of the original plan as bid. A copy shall be available on the site for inspection at all times.

2.

The Contractor shall submit one (1) print of the record plan to the Landscape Architect for his review simultaneously with each draw request as the project progresses. Such submissions shall be complete through the current work for which payment is requested.

3.

At least ten days prior to scheduled date of the final inspection of the completed irrigation system the Contractor shall submit to the Landscape Architect, for his approval, a complete and correct copy of the record plan and three (3) copies of manufacturer's maintenance and operating instructions for all valves, sprinklers and other equipment installed.

LANDSCAPE IRRIGATION SYSTEM 60060986 - March 24, 2010

328420-3

4.

5. I.

Dimension from two permanent points of reference (buildings, monuments, sidewalks, curbs, pavements, etc.) the items listed below. Locations shown on record drawings shall be kept day to day as the project is being installed. Dimensions noted in drawings shall be at least 1/8 inch in height. a.

Point of connection.

b.

Routing of irrigation pressure lines (dimension maximum 100 feet along routing).

c.

Gate valves.

d.

Irrigation control valves.

e.

Quick coupling valves.

f.

Routing of control wires.

g.

Other related equipment.

Maintain record drawings onsite at all times.

Controller Charts 1.

Record drawings will be evaluated by the Owner's Representative before charts are prepared.

2.

Provide one controller chart for each controller of the maximum size controller door will allow. Show the area covered by the automatic controller.

3.

The chart shall be a reduced drawing of the actual record drawing. In the event the controller sequence is not legible when the drawing is reduced, enlarge it to a readable size.

4.

Chart shall be a blackline print with a different color used to show area of coverage for each station.

5.

When completed and reviewed by the Owner's Representative, laminate the chart.

6.

Mount the chart inside controller enclosure/cabinet using Velcro or equal tape.

7.

These charts must be completed and reviewed prior to final observation of the irrigation system.

LANDSCAPE IRRIGATION SYSTEM 60060986 - March 24, 2010

328420-4

PART 2

- MATERIALS

A.

GENERAL: All materials and equipment shall be supplied by the Contractor and no substitutions shall be allowed without the prior written approval of the Landscape Architect. The Contractor shall inspect all materials and equipment prior to installation and any defective materials and equipment shall be replaced with the proper materials and equipment. Those items used in the installation that are found to be defective or improperly installed shall be removed and the proper materials and equipment installed in the proper manner.

B.

PVC PIPE AND FITTINGS: 1.

All pipe shall be class 160 unplasticized polyvinyl chloride pipe, type 1120 or 1220, or better. Pipe from 2" size up operating in excess of 90 PSI shall be gasketed pipe. Solvent weld pipe may be used in all other instances. Outside diameter to wall thickness ratios specified in CS 246 63 for standard dimension ration (SDR-PR) pipe shall be maintained in the barrel of the pipe. Minimum wall thickness at the bell joint shall be as follows: CLASS 160 (SDR 26) 2"

3"

4"

6"

8"

10"

0.132"

0.159" 0.205" 0.298" 0.386" 0.480"

2.

Pipe and fittings shall be made from clean, virgin, NSF approved Type I, Grade I (PVC 1120) PVC, conforming to ASTM resin specification D 1784 60T.

3.

All pipe shall be pressure rated at hydrostatic working pressures of 160 PSI 73.4 degrees F. and shall meet requirements as set forth in Commercial Standard CS 256 63 with standard dimension ratio SDR 26.

C.

RISERS AND SWING JOINT NIPPLES: All risers in excess of 12" above grade and/or swing joint nipples shall be unplasticized polyvinyl chloride, schedule 80, threaded pipe. Fittings on swing joints shall be Marlex, schedule 80, threaded elbows or street elbows. Assemble with teflon tape only. For systems operating at less than 90 PSI, swing joints may be constructed of flexible PVC and insert fittings as per plan detail.

D.

110-120 VOLT ELECTRIC WIRING: 120v electric will not be required on this job.

LANDSCAPE IRRIGATION SYSTEM 60060986 - March 24, 2010

328420-5

E.

VALVE CONTROL LINES: 1.

Smart Valve Controllers by Hunter Industries Inc. shall be located in the underground control valve box. Electric control lines from controller to automatic valves shall be wired direct leaving approximately three feet of spare wire to allow for ease of maintenance and programming of the controller. Splicing shall be in valve boxes only.

F.

SPRINKLER HEADS, CONTROLLERS, AUTOMATIC VALVES: called for on the irrigation plan or approved equal.

Shall be as

G.

QUICK COUPLING VALVES AND/OR HOSE BIBBS: Quick coupling valves and keys or hose bibbs shall be as specified on the plans. Locate as shown on the irrigation plan. If the plan specifies hose bibbs rather than quick coupling valves, provide and install hose bibbs within valve boxes as noted on plans.

H.

GATE VALVES: 1.

Gate valves shall be as specified on the plans, or approved equal. Each valve shall be afforded access through a PVC or fiberglass box equipped with cover.

2.

Provide two (2) gate valve keys.

3.

Gate valves at line size shall be located as shown on the contract drawings.

I.

MISCELLANEOUS SYSTEM COMPONENTS: All miscellaneous system components shall be of the type and size as indicated on the irrigation design plan and detail drawings.

J.

VALVE BOXES: all valves, splices within valve control lines, hose bibbs and/or quick coupler valves shall be located within an NDS, or equal, valve box as follows: Section valves, quick couplers and/or hose bibs, Gate valves and splices, Filters or other installations requiring more space - 12"x17" standard rectangular valve box and cover model no. NDS #113PBCR for reuse purple and NDS #114BC for green. All boxes and pits shall be fitted with NDS, or equal, extensions as necessary to provide a minimum of 2" clear space below the bottom of the valve, filter or fitting contained within the box.

LANDSCAPE IRRIGATION SYSTEM 60060986 - March 24, 2010

328420-6

PART 3 A.

Progress of the Work 1.

B.

C.

- EXECUTION

Begin work when ordered to do so by the Landscape Architect. This work must proceed in an orderly manner and in accordance with whatever job schedule may be set up to avoid delay or interference with other construction work. The irrigation work shall proceed in conjunction with the general construction work of the project. The Contractor must provide means of access to all site features at all times so as not to impede the general construction work in areas under construction, and leave the area of irrigation work in a finely graded condition with all stone or rock removed and smoothly blended to adjacent areas.

Product Handling 1.

Delivery: Deliver materials in manufacturer's original unopened containers, with each container identified with manufacturer's name, brand, or type.

2.

Protection: a.

Protect work and materials under this section from damage during construction and storage. Protect PVC pipe and fittings from sunlight.

b.

Beds on which pipe materials are stored shall be the full length of pipe. Do not use pipe that has been damaged or dented.

c.

Assume responsibility for damage to existing construction, and restore property to its original condition should damage occur.

Field Measurements Obtain field measurements required for proper and adequate fabrication and installation of the work. Exact measurements are the Contractor's responsibility.

D.

Utilities Services Make connections to water and electrical services at locations indicated in the drawings.

E.

Flushing System 1.

After irrigation pipelines and risers are in place and connected and prior to installation of irrigation heads, open the control valves and use a full head of water to flush out system.

2.

Install irrigation heads only after flushing of the system has been accomplished.

LANDSCAPE IRRIGATION SYSTEM 60060986 - March 24, 2010

328420-7

F.

System Maintenance The irrigation contractor shall maintain the system for a period of 60 days after initial acceptance. The system shall operate on a daily basis during that time period.

G.

General 1.

H.

I.

Trench Excavation 1.

All trenches shall be excavated to sufficient depths to provide a minimum of 10" cover on laterals and 18" cover on mains. (For those lines operating less than 90 PSI.) Lines operating in excess of 90 PSI shall have 24" of cover.

2.

Trench bottom shall be clean and smooth with all rock, soil and organic debris removed. All trenches shall be only as wide as necessary to permit easy handling and installation of pipe in them.

3.

Pipe shall be placed so that barrel of pipe and coupling are a minimum of 2" above high points of the trench bottom.

Rock Excavation 1.

J.

In the event large rock, boulders, stumps, or other obstruction is encountered in excavation of the trenches, which cannot be removed by the equipment in use or tractor mounted backhoe, the Contractor shall adjust the line or the trench to circumvent it, as part of his work. If the obstruction cannot be avoided, the Contractor shall remove the obstruction.

Bedding Material 1.

K.

The Contractor shall diligently follow the manufacturer's recommendations for installing pipe, valves, sprinklers and all other items. The pipe shall be laid in true, smooth alignment with sufficient cover and thrust blocking to prevent excessive movement.

Excavated material, except in the case of excavated rock, is usually satisfactory for bedding of pipe.

Thrust Blocks: 1.

Thrust blocks shall be constructed behind all mainline fittings, tees, bends, reducers, line valves, plugs, caps, etc., in accordance with pipe manufacturer's recommendations and plan details.

2.

Thrust block shall bear against undisturbed earth, and, in case this is not possible, they shall be made correspondingly larger.

3.

Thrust blocks shall be so placed as not to interfere with repair to joints and couplings and shall be a concrete mix consisting of one part cement, two parts sand and five parts gravel, mixed and placed fairly dry so they may be shaped easily. No precast units shall be used.

LANDSCAPE IRRIGATION SYSTEM 60060986 - March 24, 2010

328420-8

L.

M.

N.

Gate Valves 1.

All valves shall be closed at time of installation and shall be set plumb. Reach wells shall be installed so that lid is set 2" below finished grade. Gate valves shall be located as shown on the plans and of a size equal to the pipeline on which it is installed.

2.

Gate valves shall be installed so the lower end rests firmly on the ground and shall be designed to withstand 2,000 lbs. without failing.

Backfill 1.

After proper bedding of pipe is achieved, the balance of backfill shall be placed and suitably compacted by tamping mechanically or hydraulically to the satisfaction of the Landscape Architect. Backfill within areas to be paved over shall be compacted to 98% modified proctor maximum density. Testing, if required, will be at the owner's expense for all passed tests; all charges for failed tests will be the responsibility of the contractor.

2.

No lines shall be covered until they have been passed by inspection hereinafter described, except that lines may be covered with all joints left open for inspection.

3.

In the case of cutting of paved roads or drives, all back fill shall be compacted and the top 6" of back fill shall be poured in 3,000 PSI concrete. The final patch shall be made to match the grade and material of the adjacent finish road or drive.

Turf Area Heads 1.

O.

Heads in lawn areas shall be set flush with sod. All other heads shall be adjusted to sod height after installation of sod or seeding operations.

Planting and Groundcover Area Heads 1.

P.

Piping 1.

Q.

All heads to be set to the top of mulch.

Piping shall run as straight as possible. Pipe shall be cut square, properly reamed to remove constrictions or burrs before making up joints. All mains and laterals shall be thoroughly flushed before valves or heads are installed.

Existing Installations 1.

When the contractor is required to cut into any existing irrigation installation for the purpose of repair and/or connection, the contractor shall be responsible for the flushing and testing of all lines and cleaning of all heads, nozzles, and components which may be affected by such cut. It shall be the contractor’s responsibility to immediately report any damage subsequent to such cuts or repairs to the Landscape Architect so that proper resolution of the damage may be determined. When interfacing with existing irrigation systems it shall be the contractor’s responsibility to schedule his work in such a manner that the existing system will

LANDSCAPE IRRIGATION SYSTEM 60060986 - March 24, 2010

328420-9

remain operational for the greatest length of time possible. The contractor shall keep the owner and Landscape Architect appraised of his schedule in this matter. R.

Restoration 1.

S.

Any areas that have been disturbed must be fully restored. Contractor to rake out and sod areas disturbed by trenches and irrigation installation.

Hydrostatic Testing 1.

After the pipe has been laid and backfilled, it shall be hydrostatically tested for leakage. The Contractor shall furnish the pump, pipe connection, blow off valves and any other necessary apparatus including gauges and meters and all personnel necessary for conducting the test. Before applying the test pressure, all air shall be expelled from the pipe. If necessary, threaded taps shall be made at the points of higher elevations and then closed with plugs. When practical, tests shall be made on sections between valves, or sections not exceeding 2,000 feet in length. Dead ends, bends or other fittings shall have a firm foundation and be securely blocked against the trench walls before testing or completing the backfill as specified.

2.

The full test pressure of 65 pounds per square inch (psi) shall be held for no less than two hours or longer as necessary to permit thorough examination of all exposed joints in the section of main being tested. Test pressure shall be maintained at 65 psi by pumping water into the pipe in accordance with the requirements of AWWA C600.

3.

Leakage shall be measured by the quantity of water pumped into the pipe to maintain test pressure during test period. Maximum permissible leakage shall be less than the number of gallons per hour determined by the following formula: L= S x D x (P).5 L = Allowable leakage in gph 133200 S= Length of section tested, in feet D= Nominal diameter of the pipe in inches P= Average pressure maintained during the leakage test in psi. pressure shall be sixty five (65) psi.

The test

4.

Water for testing shall be obtained from an approved water source. The Contractor shall provide all water required at his own expense and shall make all necessary arrangements with the authority which controls the source of water system and shall be governed in his use of water by all rules and regulations imposed thereon by said authority. The Contractor shall provide and remove temporary connections between the source water system and the mains constructed under this contract. All temporary connections shall meet the approval of the Landscape Architect, the authority controlling the source water system and Public Health authorities having jurisdiction.

5.

All leaks shall be located and repaired until the test meets the above requirements. Any faulty fittings, valves or other accessories which leak during testing shall be repeated as specified above. Any replacement of faulty material or retesting shall be at the expense of the Contractor. END OF SECTION

LANDSCAPE IRRIGATION SYSTEM 60060986 - March 24, 2010

328420-10

SECTION 329010

PART 1 A.

LANDSCAPE PLANTING

- GENERAL

Description This section includes soil preparation, fine grading, weed control, erosion control, planting, watering, and plant establishment and maintenance. Landscape contractors shall be responsible for securing all necessary licenses and permits and shall comply in all way with Federal, State and local codes. All Landscape and Irrigation Contractors wishing to bid the project shall have experience specializing in this type of work in this location.

B.

Related Work Specified Elsewhere 1.

C.

Drawings and general provisions of the Contract, including General and Supplementary Provisions, Section 013300 and other Specification Sections, apply to this Section: a.

Landscape Irrigation System: 328420

b.

Landscaping Planting: 329010.

Investigation of Site 1.

All bidders shall examine the site and fully acquaint themselves with all existing conditions in order that no misunderstanding may arise as to the character or as to the extent of the work to be done; and likewise, in order to advise and acquaint themselves with all precautions to be taken in order to avoid injury to persons and property.

2.

Rough grades to be furnished shall be ascertained by site inspection prior to bidding

3.

The Contractor shall determine by site investigation any necessary work not specifically called for, but, necessary to satisfactorily complete the work. No additional compensation will be granted because of any difficulties which may be encountered on the site in the execution or maintenance of any portion of the work.

4.

Any damages to underground or above ground utilities or to any property of the Owner or other Contractor shall be repaired or replaced immediately at the responsible Contractor's expense.

5.

Any damage caused to underground installations of another Contractor shall be back charged to that Contractor if such installations are not located in accordance with plans.

LANDSCAPE PLANTING 60060986 - March 24, 2010

329010-1

D.

Submittals 1.

Submit shop drawings and other items in accordance with the General Provision, Section 013300 and the following:

2.

Work schedule.

1.

Agronomic soils test report. After completion of grading and prior to weed control or soil preparation, the Contractor shall obtain agronomic soils tests for all planting areas. Tests shall be performed by an agronomic soils testing laboratory and shall include a fertility and suitability analysis with written recommendations for soil amendment, fertilizer and chemical conditioner application rates for soil preparation, planting backfill mix, auger hole requirements, hydrospraying, and postmaintenance fertilization program. The soils report recommendations shall take precedence over the minimum amendment and fertilizer application rates specified herein only when they exceed specified minimums. The pH of all topsoil shall be between 6.0 and 7.0. A soil analysis shall be provided to the Landscape Architect by the Project Manager indicating soil pH.

2.

Percolation test and report. The Contractor is responsible for performing percolation tests to determine percolation rates for areas of the site to receive landscaping, ie., lawns, beds, hedge rows and all tree locations. In areas where drainage is less than 6" per hour the contractor shall install sumps to provide drainage at 6" per hour. Sumps shall be a minimum of 8" in diameter, shall be a minimum of 36" deep or sufficient depth to break through to sandy soils capable of providing the required drainage, whichever is greater and backfilled with clean builders sand.

3.

Materials list noting product (generic) name and supplier. All plant material furnished by the Contractor, unless otherwise specified, shall be Florida #1 or better in accordance with Grades and Standards for Nursery Plants, State Plant Board of Florida. The Landscape Architect reserves all rights to determine acceptability of plant material submitted for planting.

4.

Submit plant materials list and supplier's name, address, and phone number to Owner's Representative within 30 days of award of contract, giving evidence that Contractor has source for specified plant materials.

5.

Laboratory analysis of each soil amendment material. Submit samples of the import soil to the laboratory for analysis prior to and following placement on the site.

6.

Guarantees/written certifications.

7.

Substitutions will be permitted only upon submission of sufficient proof that any plant is not obtainable and upon authorization of the Landscape Architect. Under no circumstances shall unauthorized substitutions be included in the Bid Proposal and Breakdown.

LANDSCAPE PLANTING 60060986 - March 24, 2010

329010-2

E.

F.

Guarantee 1.

Immediately remove plant material that does not meet the specifications from the site. Replace these and any other plants that are missing with the same variety and size as originally designated in the plant list.

2.

See General Provisions for one-year guarantee.

Performance Standards 1.

All work shall be performed by competent and skilled craftsmen. Labor crews shall be under the direct control of a single foreman designated at the beginning of the work and skilled in reading blueprints and coordination between office and job. While labor crews may change, the same foreman will be in charge throughout the job. Contractor shall review plans throughout the job. Contractor shall review plans and specifications with the job foreman to insure complete understanding of the project.

2.

Tools shall not be left on the job site in an unsafe or unprotected condition.

3.

All open excavations shall be properly barricaded and lighted at night.

4.

The Contractor shall at all times keep the premises free from accumulation of waste material, soil, and/or rubbish caused by his employees or work. The Contractor shall clean behind his work immediately and shall take necessary precautions to keep concrete, brick and other paving material clean of soil. This shall include the use of drop-cloths, etc. Damage to grades or lawns shall be repaired immediately and all debris and excess soil removed by raking.

5.

All staking and layout of physical features shall be approved by the Landscape Architect before construction or planting is started. The same shall apply to the establishment of proper grades and levels. All planting beds shall be accurately staked in accordance with the plans. Changes necessitated by building changes, etc., shall be in keeping with the overall concepts of the design. Any beds developed without the approval of the Landscape Architect shall, if they do not accurately represent the plan and/or the design concept, be redeveloped without additional expense to the Owner.

6.

Material such as ground covers, mulch or gravel shall be spread in the specified quantity to cover the area designed. No additional materials shall be used in such areas without the approval of the Landscape Architect and/or Owner.

7.

The Contractor shall in good workmanlike manner, do and perform all work and furnish all supplies and materials, machinery, equipment, facilities and means, except as otherwise expressly specified herein, necessary or proper to perform and complete all the work required by this contract, within the time specified herein, in accordance with the provisions of this contract and said specifications and in accordance with the plans, and in accordance with the directions of the Landscape Architect as given from time to time during the progress of the work.

LANDSCAPE PLANTING 60060986 - March 24, 2010

329010-3

G.

H.

Observations 1.

Request observation by the Owner's Representative at least 48 hours in advance of the time observation is required.

2.

Observation will be required for the following parts of the work: a.

Prior to completion of grading and soil preparation.

b.

Plant material when delivered to the project site.

c.

When shrubs and trees are spotted for planting but before planting pits are excavated.

d.

When planting and all other indicated or specified work has been completed.

e.

Upon completion of maintenance and plant establishment.

Abbreviations for Landscape Planting c.w. clear wood c.t. clear trunk cl. (s) clump (s) dbl. double o.a. over all (height & width the same) o.a.h over all height spr. spread stms. stems stg. hts. staggered heights hd. (s) head (s) std. standard f.o.w. fan on wall * f.o.f. fan on fence * tks. trunks esp. espalier r.c. rooted cuttings u.r.c. un-rooted cuttings o.c. on center * NOTE: (f.o.w. & f.o.f) Fan on Wall and Fan on Fence shall mean providing all necessary hooks, masonry plugs, and tying as required to begin espalier of plants specified.

LANDSCAPE PLANTING 60060986 - March 24, 2010

329010-4

PART 2 A.

- MATERIALS

Topsoil Topsoil is defined as 90% sand with not more than 2% clay or silt and the balance as loam material. Organic material shall not exceed 5%. Sand is defined below as material which passes through number 270 and number 10 sieve. Topsoil shall be free from hard clods, stiff clay, hardpan, sods, stones over 1", lime, cement, bricks, coal ashes, cinders, slag, concrete, tar or its residue, tarred paper, boards, weeds or weed seed, sticks or other objectionable material as determined by the Landscape Architect.

B.

Peat Moss - Peat moss shall consist of coarse, partially decomposed vegetable matter of natural occurrence. It shall be medium brown in color, clean, low in content of mineral and woody material, and mildly acid, and shall be shredded and free from all stones and twigs.

C.

Sand - Clean, coarse, ungraded, meeting ASTM C33-55 requirement for concrete sand.

D.

Bonemeal - Commercial bonemeal shall be finely ground and have a minimum analysis of 4% nitrogen and 20% phosphoric acid.

E.

Natural Organic Fertilizer - Shall be a commercially natural organic fertilizer 6-3-0 (active sludge), such as Milorganite, produced by the Sewerage Commission, Milwaukee, Wisconsin.

F.

Fertilizer and Lime Materials 1.

Deliver amendments and fertilizers in sacks with manufacturer's label showing weight and analysis attached to each sack.

2.

Fertilizers: All fertilizers shall be uniform in composition free flowing and suitable for application by mechanical spreader equipment. Fertilizers shall be delivered to the site fully labeled according to applicable State Fertilizer laws. The following information shall be shown on the fertilizer bag or package or on a tag:

3.

a.

Name and address of manufacturer.

b.

Name, brand or trade mark.

c.

Number of net pounds of ready mixed material in the package.

d.

Chemical composition or analysis.

e.

Guarantee of analysis.

If a brand or grade of fertilizer is delivered in the bulk, a written statement having the above listed information must accompany each load.

LANDSCAPE PLANTING 60060986 - March 24, 2010

329010-5

4.

5.

Custom Mixed Fertilizers shall have a written statement containing the following information with each load: a.

Weight of each commercial fertilizer used in the custom mixing.

b.

The guaranteed analysis of each commercial fertilizer used in the custom mixing.

c.

Total weight of fertilizer delivered in each load.

d.

The manufacturer of each of the commercial fertilizers.

e.

Guaranteed analysis of each load to be stated as follows: (1)

% of total Nitrogen.

(2)

% of total available Phosphoric Acid.

(3)

% of total Soluble Potash.

Name and address of the person selling the fertilizer.

G.

Fertilizer Application Rates shall be determined by soil test (Under unusual circumstances where there is insufficient time for a complete soil test, 3 pounds Milorganite Fertilizer per 1000 sq. ft. can be applied.) shall be distributed evenly over the area to be sodded.

H.

Lime: Lime material shall be ground limestone (Hydrated or burnt lime may be substituted) which contains at least 50% total oxides (calcium oxide plus magnesium oxide). Ground limestone shall be ground to such fineness that at least 50% will pass through a 100-mesh sieve and 98% to 100% will pass through a mesh sieve. 1.

Application rates for liming materials shall be determined by soil tests. (Under unusual circumstances where there is insufficient time for a complete soil test, the Landscape Architect shall be consulted for rates off application to be used if any. When used lime shall be applied at a minimum rate of 50 pounds of ground limestone of its equivalent per 1000 sq. ft.) unless otherwise directed by the Landscape Architect. Lime shall be distributed uniformly over the entire area to be sodded or planted.

LANDSCAPE PLANTING 60060986 - March 24, 2010

329010-6

PART 3

- EXECUTION

A.

Topsoil: Topsoil shall be placed in all planting pits 6" below and to the side of Plant Root System.

B.

Fertilizers and soil amendments: All fertilizers and soil amendments shall be spread prior to beginning work under paragraph 3 below.

C.

Lawn Areas - in those instances that topsoil is called for in lawn areas it shall be placed four inches (4") deep and diced or roto-tilled an additional four inches (4") into the existing grade. A smooth tractor blade finish plus one inch (1") below sod finish grade shall then be established.

D.

Staking and Layout: All staking and layout of physical features shall be approved by the Landscape Architect before construction of planting is started. The same shall apply to the establishment of proper grades and levels. All planting beds shall be accurately staked in accordance with the plans. Changes necessitated by building changes, etc., shall be in keeping with the overall concepts of the design. Any beds developed without the approval of the Landscape Architect shall, if they do not accurately represent the plan and/or the design concept, be re-developed without additional expense to the Owner.

E.

Commencement of work: Work under this contract shall commence not less than ten (10) days after notice to proceed and shall be complete in an orderly business like fashion. Once work is begun it shall continue on consecutive working days until work is completed. Sundays, Saturdays, holidays and stoppages due to foul weather or delays caused by the Owner or building contractor shall be excluded. Unnecessary delays in work may result in forfeiture of Performance Bond when required.

F.

Maintenance: The Contractor is entirely responsible for the work until final acceptance. Once material is planted, it shall receive water each day from time of planting until final inspection - not to include Sundays. Watering shall be done in accordance with sound nursery practice. Water source shall be provided by the Owner, hoses, etc. by the Contractor, unless otherwise specified for specific job conditions. The contractor is responsible for all plant material maintenance until acceptance by the owner. This shall include all watering pruning, cultivating, fertilizing, and weeding as required for healthy growth and establishment. Maintenance shall also include restoration of planting saucers, adjusting or repairing staking, resetting plant material to proper grade or vertical position as required, spraying material for insects and disease control and replacement of dead stolen or unacceptable materials.

G.

Coordination of work: The Contractor shall be responsible for complete coordination of planting operations with the other Contractors on the job. Repair of damage to plants, grades, lawns, etc., during installation shall not be considered as an extra, and not chargeable to the Owner. Damage caused by other Contractors will be the responsibility of said Contractors.

H.

Right to reject: The Owner shall have the right, at any stage of the work, to reject any and all work and materials which, in his opinion, may not meet the requirements of these specifications. Rejected material shall be immediately removed from the site and acceptable material substituted in its place.

LANDSCAPE PLANTING 60060986 - March 24, 2010

329010-7

I.

Underground debris: Should any objectionable material such as concrete, bricks, roots or other debris be encountered during landscape installation, they shall be removed from the site by the Contractor. All open excavations shall be properly barricaded, and lighted at night.

J.

Clean-up: The Contractor shall at all times keep the premises free from accumulation of waste material, soil, and/or rubbish caused by his employees or work. Contractor shall clean behind his work immediately and shall take necessary precautions to keep concrete, brick and other paving material clean of soil. This shall include the use of dropcloths, etc. Damage to grades or lawns shall be repaired immediately and all debris and excess soil removed. Should the Contractor fail to keep the premises in a clean satisfactory condition, the owner reserves the right to hire appropriate personnel to perform clean-up work and back charge the Contractor for all costs incurred.

K.

Completion and acceptance:

L.

1.

Completion of the work shall mean the full and exact compliance and conformity with the provisions expressed or implied in the drawings and specifications, and associated change order as approved by the Landscape Architect.

2.

Final inspection shall be made by the Landscape Architect at the request of the Contractor, and shall be prior to final request for payment. All requirements of the specifications shall apply until final acceptance of the work by the Owner or his representative.

3.

The acceptability of all material, workmanship, labor and compliance with the specifications, grades and standards shall be solely determined by the Landscape Architect.

Guarantee and replacement: 1.

All plant materials shall be guaranteed to be alive and in satisfactory growth, Florida #1 Grade or better, as to their species, at the end of the guarantee period.

2.

Guarantee periods for plant materials shall be as follows: Ground covers & vines Shrubs Palms Trees (including Myrica spp.)

3.

- 12 months - 12 months - 12 months - 12 months

Upon acceptance of the landscape installation the Landscape Contractor shall supply the Owner with a complete and adequate maintenance program to be followed during and after the guarantee period. The Landscape Contractor shall make frequent inspections of the job during the guarantee period to determine if proper maintenance is being given. It shall be understood that in accordance with the terms of the guarantee that the Landscape Contractor must promptly inform the Owner if proper maintenance is not being given to the installation. Such notice shall be in writing outlining corrective measures to be taken with a copy to the Landscape Architect.

LANDSCAPE PLANTING 60060986 - March 24, 2010

329010-8

4.

At any time during the guarantee period the Landscape Contractor shall be required to replace all plants that are dead or in an unsatisfactory condition of growth. All replacements included within the guarantee shall be at the Contractor's expense, shall be of like size and kind of the plants removed, and, shall be guaranteed for an additional period of time. END OF SECTION

LANDSCAPE PLANTING 60060986 - March 24, 2010

329010-9

SECTION 329210 SODDING

PART 1 - GENERAL A.

Description Provide all materials, water, equipment, transportation, tools, and labor, to establish grass plus all items called for or that can be reasonably inferred from the drawings, including sodding, grading, fertilizing, watering, mowing, replacing and maintaining the area for a complete job.

B.

Related Work Specified Elsewhere 1. 2.

D.

Earthwork: 312300. Trenching, Backfilling and Compacting: 312316.

Applicable Publications Portions of the publications listed below form a part of this specification only to the extent referenced.

E.

1.

Florida Department of Transportation, "Standard Specifications for Road and Bridge Construction" (Fla. DOT SPEC), latest edition.

2.

Florida Department of Transportation, "Utility Accommodation Guide".

3.

Turfgrass Producers Association of Florida, "Standards of Sod Quality".

Records Submit written weekly records to the Owner of all grassed areas for use in determining the beginning and ending of the maintenance period for each area. The records shall indicate the date of grassing, fertilizing and mowing, the type (seed or sod), quantity (sq. ft., sq. yds, or acres) and location of grassing.

F.

Submittals 1.

2.

Submit Shop Drawings in accordance with the General Provisions and Section 013300. Submit certificates stating that the materials conform to the requirements of this specification as follows: a.

Certificate from sod producer stating that sod meets the requirements for "Florida Standard Grade" as defined by the Turfgrass Producers Association of Florida, and set forth in paragraph "SOD" of this specification.

c.

Fertilizer manufacturer's certificate of analysis including Nitrogen, Phosphorus Potash and complete micro-nutrients in accordance with paragraph "Fertilizer" of this specification.

Submit a copy of the certificate(s) with each delivery.

SODDING 60060986 - March 24, 2010

329210-1

PART 2 - PRODUCTS A.

B.

Sod 1.

Argentine Bahia with well matted roots. The sod shall be taken up in commercialsize rectangles, preferably 12-inch by 24-inch or larger, except where 6-inch strip sodding is called for.

2.

The sod shall have no visible broadleaf weeds when viewed from a standing position and the turf shall be visibly consistent with no obvious patches of foreign grasses. In no case may the total amount of foreign grasses or weeds exceed 2% of the total canopy. Florida Standard Grade sod shall be neatly mowed and mature enough that when grasped at one end it can be picked up and handled without damage. The sod shall be sufficiently thick to secure a dense stand of live grass. The sod shall be live, fresh and uninjured, at the time of planting. It shall have a soil mat of sufficient thickness adhering firmly to the roots to withstand all necessary handling.

Fertilizer Commercial grade, controlled release, granular fertilizer consisting of blend of coated prilled urea with iron included in a slowly soluble form, free flowing and uniform in composition conforming to Florida DOT Specification 982-1, and bearing the manufacturer's guaranteed statement of analysis by weight of 12 parts nitrogen, 8 parts phosphoric acid and 8 parts potash, plus complete micronutrient including magnesium, sulfur, zinc, manganese, copper and boron.

D.

Mulch Dry mulch: The mulch material used shall normally be dry mulch. Dry mulch shall be straw or hay, consisting of oat, rye, or wheat straw, or of pangola, peanut, coastal bermuda or Bahia grass hay. Only undeteriorated mulch which can readily be cut into the soil shall be used. Mulch shall be free of weeds, weed seed and other deleterious material.

E.

Source Requirements for Sod and Mulch Comply with all current restrictions for transporting sod and mulch material from or through quarantine areas for the white fringed beetle, witchweed, and West Indian sugar cane borer weevil, as issued by the Division of Plant Industry, Florida Department of Agriculture and the Animal and Plant Health Inspection Service, U.S. Department of Agriculture.

F.

Water Provide permanent or temporary piping and valves, and temporary trucks to convey water from the source to the point of use.

SODDING 60060986 - March 24, 2010

329210-2

PART 3 - EXECUTION A.

Coordination of Work Coordinate all work activities to provide for establishment of grass cover at the earliest possible time in the construction schedule to minimize erosion of topsoil.

B.

C.

D.

Construction Methods - General 1.

Provide and establish grass in all areas designated on the drawings and that are disturbed during construction (except areas to be paved, landscaped or covered with structures).

2.

Do not fertilize when wind velocities exceed 15 miles per hour. Sod only when the soil is in proper condition to induce growth.

3.

When a length of roadway slopes or adjacent areas have been graded and made ready, commence grassing in accordance with these specifications. Incorporate grass covering into the project at the earliest practical time in the life of the contract to reduce potential erosion.

4.

Store fertilizer in dry locations away from contaminants. Sprinkle sod with water and protect from exposure to wind and direct sunlight until planted. Provide covering that will allow air to circulate so that heating will not develop.

Preparation of Area to be Grassed 1.

Prepare the areas to be grassed by disc-harrowing and thoroughly pulverizing them to a depth of at least 6 inches.

2.

Bring all areas to be grassed to finished grades, remove weeds, surplus dirt and rock debris over 1 inch in diameter, and rough grade the area.

3.

Test the soil for pH. If the soil is below a pH level of 5.5, spread lime to raise the pH level to at least 5.5.

4.

Uniformly apply fertilizer at the rate of 400 to 500 pounds per acre. Immediately after the fertilizer and/or lime is spread over the area, mix them into the soil to a depth of approximately 4 inches.

5.

Float the area to a smooth uniform grade. Slope all areas to drain. Establish flow lines as shown on the drawings. Finish areas to be grassed approximately 1 inch below top of adjoining curb or pathway.

Sodding 1.

Incorporate sodding into the project at the earliest practical time in the life of the contract. Do not use sod which has been cut for more than 3 days. Stack any sod which is not planted within 24 hours after cutting and maintain properly moistened.

SODDING 60060986 - March 24, 2010

329210-3

E.

F.

G.

2.

Place the sod on a prepared surface, with abutting joints. Fill any gaps or cracks between sod blocks with sod. Roll with a minimum one-ton roller to obtain an even surface. Bring the sod edge in a neat, clean manner to the edge of all paving and shrub areas and project limits.

3.

Where sodding is used in drainage ditches, stagger the setting of the pieces to avoid a continuous seam along the line of flow.

4.

On areas where the sod may slide due to height and slope, peg the sod with pegs driven through the sod blocks into firm earth at suitable intervals. Replace any pieces of sod which, after placing, show an appearance of extreme dryness.

Mowing 1.

Mow first when the grass reaches a height of 3 to 4 inches. Mow a second time when the grass reaches a height of 6 inches and before a seedhead occurs. Subsequent mowings should establish a uniform grass surface of 2-1/2 inches and be made before seedhead occurs. All mowings should be made with a cut height as low as possible to stop shading of the Bahia grass.

2.

Mow sod to establish a uniform grass surface of 2-1/2 inches.

3.

Provide equipment for mowing that does not rut the soil surface. Fill any ruts that are in excess of two (2) inches deep with native soil free from twigs and rocks larger than 1 inch in diameter. Temporarily suspend mowing operations when the soil is too wet to provide adequate support and traction for equipment.

Watering 1.

Maintain a balanced watering program until the acceptance of work.

2.

Apply water in sufficient quantities and as often as seasonal conditions require to keep the grassed areas moist.

3.

Provide supplemental water and irrigate seed areas when the rainfall is not adequate to maintain soil moisture necessary for germination and growth of the grass. It is Contractor's responsibility to determine the quantities of water required and when to irrigate. This obligation shall remain in full force and effect until final acceptance of the work by Owner and shall be provided at no additional cost to Owner.

4.

Owner, at his discretion, may relieve Contractor of this obligation at such time as Owner is able to provide irrigation. This action, however, does not relieve Contractor of the provisions and guarantees set forth in the Contract Documents.

Maintenance 1.

Maintain all grassed areas for a period of 90 days after the date of substantial completion and guarantee against all defects and faults of material and workmanship.

2.

Maintain grass areas by watering, fertilizing, and mowing to establish an even and uniform grass surface of 2-1/2 inches, as specified above.

SODDING 60060986 - March 24, 2010

329210-4

3. H.

I.

Guarantee 1.

Guarantee all grasses areas to be alive and in satisfactory growth at the end of the maintenance period (90 days).

2.

Replace any grass that is dead or not in satisfactory growth, as determined by the Owner or Owner's representative. Guarantee new sod or seed for an additional 90 days.

3.

The term "Satisfactory Growth" as used in this section is defined as even plant growth in healthy conditions without bare spots larger than one square foot in seeded areas and without bare spots in sodded areas. Bare spots larger than one square foot in seeded areas shall be reseeded and bare spots in sodded areas resodded. All grassed and sodded areas shall be maintained until satisfactory growth has been demonstrated. In the event that the subsequent stand of grass is found to be contaminated with weeds or other obnoxious or undesirable growth, effectively eliminate such undesirable growth, at the Contractor's expense.

4.

Replace sod or seed with the same variety as initially specified.

Resoding 1.

J.

In the event that the grass exhibits iron chlorosis symptoms during the establishment period, apply liquid iron at manufacturer's recommended rates.

Resod any grass that has not achieved healthy and vigorous growth where this occurs in areas in excess of one square foot.

Inspection 1.

Request inspection from the Owner and his representative at least 72 hours in advance of the time inspection is required.

2.

Provide an authorized representative to be on-site during inspection. END OF SECTION

SODDING 60060986 - March 24, 2010

329210-5

SECTION 329211 VEGETATIVE ACCESS DRIVE

PART 1 - GENERAL A.

Description Provide all materials, water, equipment, transportation, tools, and labor, to establish a vegetative access drive/grass plus all items called for or that can be reasonably inferred from the drawings, including sodding, grading, fertilizing, watering, mowing, replacing and maintaining the area for a complete job. Material and system used shall be Grasspave2.

B.

D.

Related Work Specified Elsewhere 1.

Earthwork: 312300.

2.

Stabilized Subbase: 321113.

3.

Shell Base Course: 321128.

4.

Crushed Concrete Base Course: 321129.

Applicable Publications Portions of the publications listed below form a part of this specification only to the extent referenced.

E.

1.

Florida Department of Transportation, "Standard Specifications for Road and Bridge Construction" (Fla. DOT SPEC), latest edition.

2.

Florida Department of Transportation, "Utility Accommodation Guide".

3.

Turfgrass Producers Association of Florida, "Standards of Sod Quality".

Records Submit written weekly records to the Engineer of all vegetative access drive areas for use in determining the beginning and ending of the maintenance period for each area. The records shall indicate the date of grassing, fertilizing and mowing, the type (seed or sod), quantity (sq. ft., or sq. yds) and location of grassing.

VEGETATIVE ACCESS DRIVE 60060986 - March 24, 2010

329211-1

F.

Submittals 1.

2.

Submit Shop Drawings in accordance with the General Provisions and Section 013300. Submit certificates stating that the materials conform to the requirements of this specification as follows: a.

Submit manufacturer’s product data and installation instructions.

b.

Submit a 10” by 10” section of Grasspave2 material for review.

c.

Certificate from sod producer stating that sod meets the requirements for "Florida Standard Grade" as defined by the Turfgrass Producers Association of Florida, and set forth in paragraph "SOD" of this specification.

d.

Fertilizer manufacturer's certificate of analysis including Nitrogen, Phosphorus Potash and complete micro-nutrients in accordance with paragraph "Fertilizer" of this specification.

Submit a copy of the certificate(s) with each delivery.

PART 2 - PRODUCTS A.

Grasspave2 1.

Manufacturer (Grasspave2, Hydrogrow) Invisible Structures, Inc. 20100 East 35th Drive, Aurora CO 80611. 1-800-233-1510; fax 303-373-1223.

2.

GrassPave2 Grass Paving Units shall be lightweight injection –molded plastic units (20”x20”x1”high with hollow rings rising from a strong open grid. The open grid shall be designed to allow grass root penetration and development. The plastic shall be 100% post-co0nsumer recycled plastic resins, predominately HDPE with minimum 3% carbon black concentrate added for UV protection. Loading capability shall be equal to 5700 psi when filled with sand. Units shall have the following features. Unit weight: 18 oz Volume: 8% solid Color: black

3. B.

Units may be shipped in pre-assembled into rolls from 108 sf to 1345 sf.

Hydrogrow Mix 1.

Manufacturer (Grasspave2, Hydrogrow) Invisible Structures, Inc. 20100 East 35th Drive, Aurora CO 80611. 1-800-233-1510; fax 303-373-1223.

VEGETATIVE ACCESS DRIVE 60060986 - March 24, 2010

329211-2

2.

Mix shall be a mixture made from cross-linked polyacrylimide nm.nllli and ~Mal.rlal. Conl,,'Ivnl"",1ra'f"'flne sand-

a

pale briiNil fine sand wIth

a

flne sand wlth--

,phosphoUL

gray silty sand wIth

llilHH "She/I'", ,. dark brown sllfy---f!rnr-" sond

··dark'"",,,,,,,,·'lne sond-

'H"'g~ay

sHt'-Wltlt'BOnd ,","

JJBlY Qf!IJ1J!I)teA~;Hmi)emsti'

sz

& Associates, Inc.

GeotechnTcal. Environmental and Consultants

Soil Boring Profiles

GROUNOWAlER lEVEl

Osprey Avenue 0 Hudson Bayou Slit

Sarasota DRI\WN B'f:

Matted OrganIcs

KGS

FI.£ NO..

09-7020

County~

CtIECICED 8Y:

APPROYEO B'f:

Florida

""" 6 11 09

Pajer, Craig Dean, Scott [[email protected]] Thursday, September 03, 2009 11:53 AM Pajer, Craig Graph, Don GFY Project submittals 0913010000 TestHoleSummaryReport0913010000.pdf; 01014-03-11.pdf; AbbrvLegend-Page2of2.pdf

From: Sent: To: Cc: Subject: Attachments:

George F. Young, Inc. Turning Vision Into Reality – Since 1919 ARCHITECTURE  ENGINEERING  ENVIRONMENTAL  LANDSCAPE ARCHITECTURE  PLANNING  SURVEYING  UTILITIES

Craig Pajer, P.E. AECOM 5971 Cattleridge Blvd. Sarasota, FL 34232 Re: Subsurface Utility Engineering (SUE) Services GFY Project Number: 0913010000 Project Name: Pomelo Avenue Sanitary Sewer Improvements Craig,

Please find attached, electronic copies of our submittals for the above referenced project.

Having 90 years of experience, George F. Young, Inc. is a multi-faceted, professional consulting firm with seven offices around the state offering Civil Engineering, Environmental Engineering, Ecological Services, Architecture, Landscape Architecture, Planning, Surveying & Mapping, Hydrographic Surveying, GPS/GIS and Subsurface Utility Engineering (SUE). Contact us regarding resumes and project lists needed for partnering opportunities.

 Please consider the environment before printing this email. Sincerely, Scott Dean Project Manager, Utility and SUE Services

George F. Young, Inc. 299 Dr. Martin Luther King Jr. St. N. St. Petersburg, FL 33701 Phone: (727) 822-4317 ext 291 Fax: (727) 551-9395 www.georgefyoung.com

1

PRIVACY/CONFIDENTIALITY NOTICE: This message contains private, confidential, or legally privileged information and is intended for the recipient ONLY. If you are not the intended recipient or have received this e-mail in error, please notify [email protected] immediately by return e-mail or phone and delete all copies of this e-mail, including all attachments without reading them or saving to any storage device. If you are the intended recipient(s) you will need to secure the contents conforming to all applicable state and/or federal requirements relating to the privacy and confidentiality of such information. E-mail transmission cannot be guaranteed to be secure or error-free as information could be intercepted, corrupted, lost, destroyed, arrive late or incomplete, or contain viruses. The sender and George F. Young, Inc. therefore do not accept liability for any errors or omissions in the contents of this message, which arise as a result of e-mail transmission. If verification is required please request a hard-copy version.

2

George F. Young, Inc.

299 Dr. Martin Luther King Jr. Street North Saint Petersburg, Florida 33701 (727) 822-4317 Fax (727) 551-9395

Turning Vision Into Reality Since 1919

ARCHITECTURE

ENGINEERING

ENVIRONMENTAL

LANDSCAPE ARCHITECTURE

PLANNING

SURVEYING

UTILITIES

ABBREVIATION LEGEND # A A/C ACP APPROX ASPH BCATV BE BIP BLDG BOB BOC BT C CALC CATV CDS CFP CIP CL CLF COMM CONC CORS CSH CSL DBC DIA DIP DIR DIST DWY EDO ELEC ELEV EOP ESMT EXP FBK FCM FCP FDOT FIP FIR FM FND FOC FOP FPC FPID FPL FPP FRD FS GALV GAS GPR GPS GSP GSS

Number Arc, Area or Amperes Air Conditioner Asbestos Cement Pipe (Transite) Approximate Asphalt Buried Cable Television Buried Electric Black Iron Pipe Building Bottom Of Bank Back of Curb Buried Telephone Cable Chord Calculated Television Cable Continuous Deflective Separation Unit Corrugated Flex Pipe Cast Iron Pipe Center Line Chain Link Fence Communication or Committee Concrete Continously Operating Reference Station Core Sample Hole Concrete Slab Direct Buried Cable Diameter Ductile Iron Pipe Direction Distance or District Drive Way Electronic Depth Only Electric Elevation Edge Of Pavement Easement Exposed Field Book Found Concrete Monument Fiber Conduit Pipe Florida Department of Transportation Found Iron Pin Found Iron Rod Force Main Found, Found Nail & Disk Fiber Optic Cable Found Open Iron Pipe Florida Power Corporation Financial Project Identification Florida Power and Light Inc. Found Pinched Iron Pipe Found Rivet & Disk Foresight, Farside or Florida Statute Galvanized Gas Line Ground Penetrating Radar Global Positioning System Galvanized Steel Pipe Gravity Sanitary Sewer

SERVING FLORIDA AND THE CARIBBEAN BASIN

GYA HCAA HDPE ID INV IRR LB LP LS LT M MD MEAS MH MHWL MISC MOT MULTI MW N/A NAD NAVD NFV NGS NGVD No. NTS NUF O/S OCC OHL P PAVMT PC PCC PCP PED PET PG PI PID PK PK&D PLS POLY POSS PP PRC PRM PSM PVC R R/W RAD RCP RCW RNG ROW RT SAN

Guy Anchor Hillsborough County Aviation Authority High Density Poly-Ethylene Inside Diameter or Identification Invert Elevation Irrigation System Licenced Business Light Pole Land Surveyor Left Meters Measure Down Measured Manhole Cover Mean High Water Line Miscellaneous Maintenance of Traffic Multiple Water Meter Not Available North American Datum North American Vertical Datum Of 1988 Not Field Verified National Geodetic Survey National Geodetic Vertical Datum Number Not To Scale No Utility Found Offset Occupation Overhead Line Point or Platted Data Pavement Point Of Curvature Point Of Compound Curvature Permanent Control Point Pedestrian or Pedestal Petrolium Pipeline Page Point of Intersection Permanent Identifier Parker-Kalon Nail PK Nail and Disk Professional Land Surveyor Polyethylene Possible Power Pole Point Of Reverse Curvature Permanent Reference Monument Professional Surveyor and Mapper Polyvinyl Chloride Record or Radius Right of Way Radius or Radian Reinforced Concrete Pipe Reclaimed Water Main Range Right of Way Right Sanitary

SARA SCM SEC SEW SHP SIR SND SOP SR SRD ST STA STMD STORM SUE SWK TBM TECO TEL TEMP TOB TOP TP TRAFF TRNF TV TWP UAO UNK VCP VCW VRZ VVH WDL WF WL WM WPP

SARASOTA COUNTY Set Concrete Monument Section Sewer Shared Pole Set Iron Rod Set Nail Disk Shot On Pipe State Road Set Rivet and Disk Street Station Stamped Disk Storm Drainage Subsurface Utility Engineering Sidewalk Temporary Bench Mark Tampa Electric Company Telephone Temporary Top Of Bank Top of Utility Elevation Traverse Point or Turning Point Traffic Signalization Line Transformer Television Township Utility Agency Owner Unknown Vitrified Clay Pipe Valve Cover Water Verizon Telephone Verified Vertical and Horizontal Location Woods Line Wood Fence Water Line Water Main Wooden Power Pole

Page 2 of 2

299 Dr. Martin Luther King Jr. Street North Saint Petersburg, Florida 33701 (727) 822-4317 Fax (727) 551-9395

George F. Young, Inc. Turning Vision Into Reality Since 1919

g ENGINEERING g ENVIRONMENTAL g LANDSCAPE ARCHITECTURE g PLANNING g SURVEYING g UTILITIES

TEST HOLE SUMMARY REPORT AECOM Client: Address: City / State: Requested By: Email:

AECOM 5971 Cattleridge Blvd. Sarasota, FL 34232 Craig Pajer, P.E. [email protected]

GFY Project No.: Project Name: Project Location: Project Type: Field Book Number:

SIZE MATERIAL

OWNER

0913010000 Pomelo Avenue Sanitary Sewer Improvements Conflict locations specified by client Subsurface Utility Excavation and Location SUE# 1014

TEST HOLE

MD

TYPE

OTHER DESCRIPTION

VVH101

6.30'

SANITARY SEWER

10"

ACP

SARASOTA

SOIL

4

VVH102 VVH103

2.18' 3.61'

WATER LINE FORCE MAIN

6" 14"

PVC ACP

SARASOTA SARASOTA

SOIL SOIL

4 4

VVH104

3.85'

FORCE MAIN

14"

ACP

SARASOTA

SOIL

4

VVH105

2.14'

FORCE MAIN

NFV

CONC CAP

SARASOTA NFV DUE TO CONCRETE CAP

SOIL

5

VVH106

5.54'

RECLAIMED WATER

16"

PVC

SARASOTA

ASPHALT

6

VVH107

3.79'

RECLAIMED WATER

NFV

CONC CAP

SARASOTA NFV DUE TO CONCRETE CAP

ASPHALT

7

VVH108

4.38'

RECLAIMED WATER

16"

PVC

SARASOTA

ASPHALT

8

VVH109 VVH110

5.98' 4.47'

FORCE MAIN FORCE MAIN

18" 18"

ACP ACP

SARASOTA SARASOTA

SOIL SOIL

9 9

VVH111

4.96'

FORCE MAIN

20"

DIP

SARASOTA

ASPHALT

11

VVH112

4.88'

FORCE MAIN

22"

DIP

SARASOTA

ASPHALT

11

VVH113

3.33'

WATER LINE

6"

PVC

SARASOTA

ASPHALT

11

VVH114

2.73'

WATER LINE

6"

PVC

SARASOTA

ASPHALT

11

BRADENTON g GAINESVILLE g PALM BEACH GARDENS g SARASOTA g ST. PETERSBURG g TAMPA g ORLANDO

GROUND FBK COVER PAGE

Page 3 of 3

2

I

4

3

I

6

5

8

7

BEGIN CONSTRUCTION

I

'I

II ~

MH- 5 STA 20+52.49, 2.44' Rr. RIM El 11.95

l'

o

20+00

I

~,,::,

II LF SAN24 II 020%

A

I I I E'" a ~I 'I; AlF I~MH-6 ~ . ~ I STA 20+57.99, 7.06' LT. I I ' RIM EL 11.82 ~~.

1

INY EL (NW) -6.20 (24' ) INY EL (E) - 6.33 (24' ) INY EL (NE) -3.81 (8") INY EL (5) 7.85 (8" ) EXIST NY EL (NE) -623 (8") OROP INY EL (5) - 650 (8") OROP

STA 10+00.00 II IN01087572.15 482126.92

'

o.

I 1;\

I



'h

I

STA EOUATlON---,. STA 30+1 :3.70 POMELO PLACE POMELO AVENUE STA 22+75.80 N ::: 1087828.24 E ::: 482187.38

0

I

A a'

INY EL (w) -6.00 (2c,A.f.et

c ~'1-'~ ' -,

""

I'\D.. 0............ "" . \

.,.•,," W.:fI

1 "~N INV. :1.11'

If~~ s hN. 5.41' '1M' ""'-

II ' I

20,----.-----,----.-----.----.-----r-----r----,-----r----.-----r----._----.---~----_.----_r----._----.___.

20

16~--~r_----t------t-----+-----+-----+-----~----_+----~----~----~----4------f__----+_----+_-M~94_----~-----4---~ 16 RIM El. 10.65

B

EXlST- iASRA,OE OVER

~

12

§ ~ ~

,

• g

ELINE

B

MH-8

r-----f------t------~----+_--~,-t------~----f_----_+------~-----1-----_+------~----4-----_1·--~R~IM~E~'~0.~91i--I~----_4r-----+----4 - f- r--- -I- - --I-

Br---_+----+----4----_I_----~--_+----_I_----~--_+----~----~---+----+

12

8

1------t----~----+----1__--_eo.. No. EfI-JII

Cl NUll

7/09

BOYlE

3

CITY OF SARASOTA LIFT STATI ON NO. 87

! AECOM

.30554

"'~ .0K0m.

4

50+00

~9+00

48+00

PIIW(,l INGIN((R

"n:~. ~ ~~..,.""OH"E~-_\_,=...-,,,,~'""'60~0~6,,0,,98,,6'---------1 I

B

C-105 X II»" OOOSH£ns I ~'"

OSPREY AVENU E SANITARY SEWER PLAN AND PROFILE

.......

5

6

7

8

A

2

4

3

5

1

6

8

7

Ol e:==-20

0

20

W'........

D

I

D

SCALE: 1" - 20

41:04

E)t,c;r' (I. "

14-" F M

c

c

SEE DRAWING C-l07 16

r-----,------r-----,------~----_r----_.------r_----_r----_,------r_----_r----_,------r_----_.----_,------~----,------,------,------,

12

r_----t---t---+_--4_--~---+--_+--_4--~r_--t_---+_--4_-~~~~~--_+--_4--~r_--t_+_-+_--~ r EX I~T CRADE MH 14

~~-r~---+_~_+--~4_-+--r_~-~--~~_+--~+_M~,p,-~~-1

16

RIM El.

,

B

~

r--~r_-_4--_+--_+--~--~---4_--4_--4_--+_--+_---+_~~~ ~R~~ ~El~IN~Er_--r--~r_~-~~IMM4

o

J'l"

!

~

,_

I-

' ,5T

_

-

--IL ' -l20-t:B-:'N-O

Is•

-

-

-e-- -- -

5TRM '

GAS

7. ..-3~~~ P1i ~t ~~~~~~~~j!;j~~~~~~~~~~~~~~~~~~~~~~~~~~~~'f~:!~~--W;M~Rl'~US!,: ~'l=~W"~'~°=t::~~tt=:=::t=====l==::~!:~' , 8'", / l ql-

!

M I

B

GRA~":)_

1.-1- -- -+- - -- I -----+----+------f-----+----!\ 1----+-----+- ---"!----·-f-----+------!-----k'X"'IST . ---,--I=-...,,--,,'JeXIS '"'T----I----EXIST-lolorr----1-----+-----k XISTI- -+-----+--.3' 16" " 4"

r-- -- --. _

-- -I-

j

~

XlST

EXIST B

_

I

O.f'\lC _EM

,-

-.-

V~ --t.....

45+---1--+--+--+-...J+---j~--+--

18'

",N

8



,~

'--__-t____-+-____-!-____I-__--I-iE(TO" XlSTB,RE FMl ' OVED) --+-----+-----1------1-----+-----+----+'-....:::::" ...• --'. I-.......---I

if::d - -.

,././

I

4 1-· '7'

EXlf'O l8 -

1-

4

"/7' ~/[XiS TE' ..J L 2~,'8" TEE /

o

-4

~ A

A

~, ~

-8

-8

I~

g,

~ ~ ~

_12L----L----L--~L----L--L-L----L--~L----L----L----L----L----L----L----L----~---L----1----1----1----1____1-__~_

!

63+00

~

I,: ~

VERIFY SCALES 1005IGH(o OHBI-'I ~~

ir>; 1

~~

lIT

I'RO.(tl

t~UM

,'"

5~ 7'

I

3

C.W.1lid9' BouIno,d.

50'0'010. no.r\do 3'232

~'sm~.~ "~".. ,r°"-H,,~-/0-9-f"=.,.""'-~ ..60"'Or60' ' ' 9' ':' -:y-LE-------------I 2

CITY OF SARASOTA LI FT STATION NO, 87

, AECOM IolCOJ.l IIS/>, ......

T 9'U17.88\08

n..

I

C-112

OSPREY AV ENUE FORCEMAIN PLAN AND PROFILE

SI>,. 200

9'l.llU~6!1

••rir.t e.. .....

~ .......... 00 ..... 6IfI

4

r

12

67+00

66+00

~~O~FG~--~ w~CRA~'G~J~.~P~~~'R~,~P~'"'"'"'----R(; _OCR IXP twt

~r." l ~-4~~30~5~54 tr.r----------------~ ... , - - - " Ie [K ~P~ lIT [C NWR[l1

~o

!~ "0

65+00

64+00

No. EB-18

5

I

6

7

Of

8

x

000 SHE

15

2

4

3

MATCH LINE STA. SEE DRAWING

82+35,00 C-107

5

8

7

6

20

20

0

'I........

D

!

D

SCALE: 1~ = 20

C

•~ ~

C

20

1----i----4----+----r---+---~---+----~----r_--~--_+----r_--+---~--,_4 16 ~----~----~----4_-----r----_r----_+----_+-----4~----~----+_----4_----~-----_+----_+-----

S B ~ ~

r-----, -----,-----,-----,------,-----r----- ,-----,------r-----.-----,-----,------r-----.-----, 20

16

B

1----j----~--+__--+_--~--~--~---t---_+----+--_4----r_--r---+__----

12

EXiS GRADE, AIR RELEA E VALVE, 1-----+-----r----+-----~~~~~RR~FM~~ \ ----4-----i---~~---+-----+----4-~~f~~~----~ 12

-r- _

~

_

8

r-- - f - - - - -

:_~~~~M-~---+I---------~~----------+r----~~~'~,

I------+-----!-----+--,-

------

eXIS i-exISf-- fLEXIST B1

-j::;::;::::;3.*'N~~""~W~8T~=~I~\4~-~W!AY~ I,~

6-WAY EXIS T B_____

4

r- - r -

+____~~~ -+____ ---~~~~I~F=4.J~20#~=C==FM==F===~ - - - - ---

I-----~----+_---_+------ 1- --,, -./" "-' t - - - - - t - - ---+-,,""olc-- - - - + - - -+ - ----+----=-1'7C"-

(

RH:'::-=--=-=1'TI=-=-=-=-:j:-=-=-: -:::-~~:\:=;20: ~C FM -=-=-=-'If=-::-u=:\:===i==!:t-+----~_____26~ +I -::::::::~,-I-----I-0 E 1ST BT~ - --I -11- t " I t -BEND 45 ..J - - ~~STSA -N-9' -WAY- - -

o _,_

---L--~ 20 BEND 45

___~~IJ :

I

-~_\_I F

.J

____ --.L

- 20-BEND S_ _

~O~BEN:=_"-+-

8

4

o ___I_____

-4I--_-+__~J~""~~~EEL -L~--_t--+--~,2~U~~·EL-- -_+---I----t---_+---t--~----1-4 ASING PIPii

- 4 !1- ___

- 8 - - - ' - - t - - - j - - - - - --,---..- , - - -,-----I-----+----,,---,--,-,- ,--,---,,----------------!------I------

61+00

A

-8

62+00

CITY OF SARASOTA LIFT STATION NO, 87

AECOM

.."

C-113

OSPREY AVENUE FORCEMAIN PLAN AN PROFILE 4

I

5

6

I

7

ry

8

X

000 SH( [lS

~(;)j,19~ ~OO\I...- 10\'1

cA1301CO"OO f>(VtM,LD

~ ~{E.'-'''\I. ~\~\'41::.

i\u

cl,..

6"-

\o\,

S.SY

~ lOb

\°1

\0'3

"'~.3~ .'1'1

16\ \10

S.'l'O 4."1

1\1

II,

\\~

11'\

'1.~b

C,.~9

,."" ~\'1~

10-\ loS

\01 ~'IGe 6'< IcR ~\ "

COR

1\0

~,~

11\

'"'f "

11::>-113

,,~

t

,

SYbr~9\i, ld' 0rA...{ s.!> LC.;";\/ QI'

101

".go, \1...\

10'1

+

\-)e\\\'1\1.\':>

II"

\,"

cc f f

~ .... "

I.::IV~

+ +

+

+

"'l! ~

SN>."1'"

" ) 'II,i.u"," W':>">, ...

;:01,.\"'\-"

cl>(~

,

8J~o9

\{ •. . " ....

~oOk-

,I.lL

loll.[

~....,;v-\·,:c . \,',0\ \..ocA\'''"G .-4, \-l.£OI\'>lo \~~fl.\~ \:,

,

Q----r-~\_:ee..

51",

if> fIoa ,,,,,-,,,,,,-

,O~o



Co~'0-

\1



'JfJ-'7

t· H

-

W\\- \\~- N~V \::::"••.~\

0

'5'~(,..

~~



,

~\~ 'tt'~

~H

~~ I

Suggest Documents