Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Air cooled water packaged chiller Series EKE-R290 Refrigerant: R290 (Propane) Release: uk 1.0

Installation, Operation and Maintenance Manual Manuale_EKE-R290_uk_r0 1

Tel: 01823 665660

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

The technical data, information and illustrations contained in this manual were believed to be correct at the time of print. Euroklimat Spa reserve the right to change specifications and other information contained in this manual as part of our continual improvement process. No part of this manual may be reproduced, stored in a retrieval system or transmitted in any form, electronic or otherwise, without the prior permission of Euroklimat Spa. No liability can be accepted for any inaccuracies or omissions in this manual.

Contents

Tel: 01823 665660

[2]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Contents Contents.............................................................................................................................................................................................. 2 Name, address and contacts of the manufacturer................................................................................................................................. 5 WARRANTY CONDITIONS ..................................................................................................................................................................... 5 General warnings................................................................................................................................................................................. 6 Under no circumstances may parts be inserted that do not guarantee safety. ....................................................................................... 6 Basic safety rules ................................................................................................................................................................................. 7 Qualified operators .............................................................................................................................................................................. 8

Specialised maintenance electrician .............................................................................................................................. 8 Specialised maintenance mechanic ............................................................................................................................... 8 Refrigeration technician ................................................................................................................................................ 8 Transport operator ....................................................................................................................................................... 8 Person assigned to switching on and off ........................................................................................................................ 8 Safety officer ................................................................................................................................................................ 8 Storage................................................................................................................................................................................................ 9 Machine identification ....................................................................................................................................................................... 10 Transportation and handling .............................................................................................................................................................. 11

Example of lifting with a lift truck: ............................................................................................................................... 11 Example of lifting with ropes ....................................................................................................................................... 12 Dimensions and weights of the unit............................................................................................................................. 12 Unit positioning ................................................................................................................................................................................. 13

Example of placement under a roof............................................................................................................................. 14 Description of operation of the machine ............................................................................................................................................ 15

Description of cycle process ........................................................................................................................................ 15 Safety measures taken on the units EKE-R290 .................................................................................................................................... 16

Semihermetic compressor ATEX Certified.................................................................................................................... 16 Main components in the refrigerant circuit ATEX certified ........................................................................................... 17 Device for detecting leaks of refrigerant R290 (GAS LEAK DETECTOR) .......................................................................... 18 Other safety precautions............................................................................................................................................. 18 Water connections ............................................................................................................................................................................ 19

Water drain ................................................................................................................................................................ 19 Air purge..................................................................................................................................................................... 19 Water outlet ............................................................................................................................................................... 19 Water inlet.................................................................................................................................................................. 19 Condensate drain........................................................................................................................................................ 20 Water connections dimensions ................................................................................................................................... 20 Safety valves installation ............................................................................................................................................. 20 Electrical wiring ................................................................................................................................................................................. 21

Power supply .............................................................................................................................................................. 21 Check of protective devices and unit operations before switching on .......................................................................... 22 Start-up procedure ............................................................................................................................................................................ 23

Filling the water circuit................................................................................................................................................ 23 Filling with antifreeze mixture ..................................................................................................................................... 23 STARTING AND USE ..................................................................................................................................................... 24 Check of cooling.......................................................................................................................................................... 26 Checking the safety devices......................................................................................................................................... 26 Compressor START/STOP ............................................................................................................................................ 26

Tel: 01823 665660

[3]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Standby ...................................................................................................................................................................... 27 Switching off ............................................................................................................................................................... 27 Control panel..................................................................................................................................................................................... 28

Main functions ............................................................................................................................................................ 28 Controlled devices ...................................................................................................................................................... 29 Display ........................................................................................................................................................................ 29 Remote control panel (available on request) ............................................................................................................... 29 Set point modification (outlet water temperature) in COOLING mode ......................................................................... 31 TROUBLESHOOTING........................................................................................................................................................................... 32

List of main ALARMS µchiller2 SE ................................................................................................................................... 33 List of WARNING µchiller2 ........................................................................................................................................... 33 Periodical checks and servicing........................................................................................................................................................... 39

Semi-hermetic compressor maintenance .................................................................................................................... 39 Oil Type ...................................................................................................................................................................... 40 Checking the condensing coil ...................................................................................................................................... 40 Checking the electrical equipment .............................................................................................................................. 41 Seasonal stop.............................................................................................................................................................. 41 Seasonal start ............................................................................................................................................................. 41 R290 (Propane) Safety Data Sheet ...................................................................................................................................................... 42

1.

IDENTIFICATION OF THE SUBSTANCE .................................................................................................................. 42

2.

COMPOSITION/INFORMATION ON INGREDIENTS................................................................................................ 42

3.

HAZARDS IDENTIFICATION.................................................................................................................................. 42

4.

FIRST AID MEASURES.......................................................................................................................................... 42

5.

FIRE FIGHTING MEASURES.................................................................................................................................. 43

6.

ACCIDENTAL RELEASE MEASURES ....................................................................................................................... 43

7.

HANDLING AND STORAGE .................................................................................................................................. 43

8.

EXPOSURE CONTROLS/PERSONAL PROTECTION.................................................................................................. 43

9.

PHYSICAL AND CHEMICAL PROPERTIES ............................................................................................................... 44

10.

STABILITY AND REACTIVITY............................................................................................................................. 44

11.

TOXICOLOGICAL INFORMATION ..................................................................................................................... 44

12.

ECOLOGICAL INFORMATION........................................................................................................................... 44

13.

DISPOSAL CONSIDERATIONS........................................................................................................................... 44

14.

TRANSPORT INFORMATION............................................................................................................................ 44

15.

REGULATORY INFORMATION.......................................................................................................................... 45

16.

OTHER INFORMATION.................................................................................................................................... 45

Tel: 01823 665660

[4]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Name, address and contacts of the manufacturer Name: Address: Phone number.: E.mail:

Euroklimat S.p.A. Via Liguria, 8 27010 Siziano (PV) Italy +39(0)0382610282 [email protected]

WARRANTY CONDITIONS The warranty, with regards to the quality of the materials used and the good manufacture of the Products, is valid for 12 months from the set-up, provided the latter is certified by the relevant report drawn up by the specialised personnel duly authorised by EUROKLIMAT. The warranty, however, shall be valid for a maximum period of 18 months from invoice date, reduced in proportion to the working hours in excess of what is considered normal for the specific technology of the machine, i.e. 18 hours per week for domestic use and 40 hours per week for industrial use, over a total of 52 weeks per year. During the warranty period, parts being recognised as faulty due to poor quality materials or defect in manufacture shall either be replaced, repaired or put back in operation, provided the faults are not due to the user’s negligence or carelessness, or to an insufficient servicing of the equipment, damages caused by third parties, accidental damages, galvanic or chemical actions, technological processes used by the DISTRIBUTOR or to any other cause not due to defects in the manufacturing quality. When necessary, replacing spare parts will be arranged as soon as possible in EUROKLIMAT premises (27010 SizianoItaly). EUROKLIMAT keeps the right to ask the DISTRIBUTOR for sending back the faulty parts for analysis. If the inspection’s result shows the defect has been caused by not proper installation or use or the defects do not depend on any reason beyond EUROKLIMAT’s control, the DISTRIBUTROR will be charged for the relevant costs. The expenses (fees, travel, reimbursements) for the personnel that needs to be sent on the spot to discover the problems, or to repair or replace faulty parts, shall be borne by the DISTRIBUTOR, with no exception. Parts subject to normal wear are not covered by the warranty, as are all electrical materials if they are subject, even for a short period, to: overload, unbalanced feeding, frequency different from the one resulting from the plate, wrong voltage. Furthermore, the warranty does not cover damages caused to engines by overload, even for short periods, or by other problems due to not tightening the terminals. The warranty automatically expires if the equipment is repaired or modified by the DISTRIBUTOR or by third parties without a written consent of EUROKLIMAT, or if non original spare parts have been used. Equipment shall be repaired by specialised personnel appointed by EUROKLIMAT who, by filing in a specific form, shall validate the warranty. The above terms are subject to the DISTRIBUTOR fulfilling all obligations arising from the Contract, specifically those with regards to payments.

Tel: 01823 665660

[5]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

General warnings Before starting to use the units, the contents of this manual must have been fully read and understood. This operating and maintenance manual describes the construction, operation and directions for use and maintenance of the units made by Euroklimat S.p.A. Euroklimat S.p.A. is relieved of all and any liability for damage or injury due to failure to comply with the instructions in this manual. If in doubt of any kind whatsoever or in need of explanations, Euroklimat S.p.A. is ready with its own qualified technical personnel to provide all the necessary indications. To make it easier to identify and recognise the units it is important that the technical data printed on the label applied to the exterior of the units and in particular the serial number are always quoted. The unit must not be made to operate other than under design conditions, even for a short time. Under no circumstances may parts be inserted that do not guarantee safety.

Tel: 01823 665660

[6]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Basic safety rules The unit must be fitted with an emergency stop by the installer. The user must check that this has been done before starting the unit. The unit is fitted with fixed guards to protect its components. A canopy must be provided to protect the unit from snow, which could create risks during operation if it freezes on the fan blades. Respect the indication of the Chapter “Installation”. Replace any damaged or missing supply lines of the various energy sources. The lubricating oil in the compressor is not dangerous. Gloves must be worn, however, when handling it and it should not be swallowed. For all work concerned with installation, commissioning, equipping, use, alterations to the conditions of use and working methods, routine maintenance, inspection and periodic maintenance, comply with the procedures given in the relative sections of this manual. The manual must be kept to hand for ready reference The unit must be used in the conditions envisaged in this operating and maintenance manual. Some recommendations are given below for the USER, who should avoid abnormal conditions of use. Any condition of use other than those expressly described in this manual must be avoided.

Do not climb onto the unit; Operate with the unit correctly installed in the recommended position; Operate with the unit correctly installed in the recommended position; Do not start the unit without the fixed guards correctly mounted; Do not remove the guards when the unit is in operation; Do not remove the guards when the unit is powered; Do not clean the unit when it is in operation. Do not install the unit in corrosive or explosive environments; Do not disconnect or remove safety parts or devices; The unit may not be used other than in the conditions described in this manual.

Tel: 01823 665660

[7]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Euroklimat S.p.A. declines every responsibility for eventual damages that can directly or indirectly derive to persons or things in consequence to the lacked observance the present instructions.

Any assembly/disassembly carried out by the USER that is not contemplated in this manual or authorised by “Euroklimat”, will be considered as tampering, thereby jeopardising the safety functions and invalidating the warranty of the unit.

Qualified operators Only the following professionals may operate the unit after having received all the necessary instructions contained in this manual:

Specialised maintenance electrician The electrician must have general experience with switchboards and specific experience with the control panel and electrical components of chillers or similar appliances in the air-conditioning sector. The electrician may only carry out the specific operations indicated in this manual, scrupulously following the relative instructions.

Specialised maintenance mechanic The mechanic must have general experience with mechanics in general and specific experience with chillers or similar appliances in the air-conditioning sector. The mechanic may only carry out the specific operations indicated in this manual, scrupulously following the relative instructions.

Refrigeration technician The refrigeration technician must have specific qualifications from a suitable school for similar appliances or work under the supervision of instructed personnel. The refrigeration technician may only carry out the specific operations indicated in this manual, scrupulously following the relative instructions.

Transport operator The transport operator may only carry out the specific operations indicated in this manual, scrupulously following the relative instructions.

Person assigned to switching on and off (Ordinary and mechanical operator) After having read the information in this manual the ordinary operator may manually operate the unit with regard to the following functions: switching on, switching off, display of alarms. In any case this operator may only carry out the specific operations indicated in this manual, scrupulously following the relative instructions.

Safety officer The safety officer is responsible for protection and the prevention of occupational risks as set forth in European Directive 89/391/EEC (Safety in the workplace). The safety officer shall make certain that all the persons who operate the unit have received all applicable instructions which are contained in this manual, including the initial installation and commissioning operations.

Tel: 01823 665660

[8]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

WARNING: The refrigerant R290 (Propane) is flammable and it must be handled only by competent and responsible operators, under the conditions specified in the safety regulations in force.

Storage

WARNING: The gas content into the unit is flammable. The refrigerator should be stored OUTSIDE only. Max. storage Temp. = +45,0°C

-

Keep the unit away from: sunlight, rain, sand and wind Temperature: 45°C maximum / minimum -10°C Maximum Humidity: 90%rH Avoid, in any way other objects to overlay unit DO NOT SMOKE

Tel: 01823 665660

[9]

www.heronhill.co.uk

NO NAKED FLAMES

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Machine identification The machines can be identified through the EC DATA LABEL (machine identification). One label is positioned on the panel behind the water connections of the machine. A copy of the label is fixed inside the electrical switchboard.

EC DATA LABEL example EUROKLIMAT S.p.A. Via Liguria, 8 27010 SIZIANO (PV) ITALY Phone: +39 0382.610282 Fax: +39 0382 617782 E-mail: [email protected] Web: www.euroklimat.it

Chiller model EKE 201 R290 Serial number: EKEMT0201FA001K Year of construction: 2011 Refrigerant type: R290 Refrigerant charge: 3.900gr. Max. Pressure: 24,0bar Power supply: 400V/3ph/50Hz Max Power / Max. Curr.:

Made in Italy

It is recommended to take note of the serial number of the unit and keep it with care. The serial number is essential to any request for spare parts or technical assistance. In case of damage you can request a copy to Technical Service Euroklimat SpA.

Tel: 01823 665660

[10]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Transportation and handling The courier is always liable for any damage during transit to the goods that have been entrusted to the same. Before preparing the unit for installation and commissioning, a thorough visual inspection must therefore be carried out to check that the packaging is intact and that the unit presents no visible damage nor oil or refrigerant leak. Also ensure that the units correspond to the order that was placed. Any damage or complaints should be reported to Euroklimat and to the carrier by recorded delivery letter within 8 days from receiving the goods. Should one or more components be damaged, do not proceed with starting up the unit and inform Euroklimat of the problem, agreeing with the latter the actions to be taken. Preferably remove the packaging at the actual place of installation. Internal handling must be carried out with the utmost care, without using unit components as handholds. To avoid damage it is essential when moving the units that they always remain in the position envisaged for their operation. Do not leave packaged units in places exposed to strong sunlight, since the internal temperature could reach safety device tripping values. The water circuit must be fully drained before handling the unit in any way whatsoever. Lifting should preferably be carried out with a lift truck. Use a spreader beam if belts or ropes are used for slinging, making sure that there is no pressure on the upper edges of the units or the packaging.

Example of lifting with a lift truck: Insert protection for the outer structure of the unit, for example a sheet of cardboard or polystyrene (A). Make sure that the forks of the lift truck project at least 100 mm (B) from the other side of the unit.

Tel: 01823 665660

[11]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Example of lifting with ropes -

Place the lifting pipes like the figure.

-

Place rigid structures on the upper edges of the unit so as to ensure it is not damaged (only in the case of one point at which the force acts).

-

Tighten the hoisting straps gradually, ensuring that they are correctly positioned.

-

Begin hoisting the unit.

Dimensions and weights of the unit

EKE R290 Propane

Model

151 201 251 301 351 401 502 602

Lenght (L)

[mm]

1.280

1.930

1.930

2.580

2.580

2.580

3.520

3.520

Deptht(P)

[mm]

990

990

990

990

990

990

990

990

Height (H)

[mm]

2.075

2.155

2.155

2.155

2.155

2.175

2.235

2.235

Shipping weight

[Kg]

630

760

940

1.110

1.230

1.250

1.980

2.100

Tel: 01823 665660

[12]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Unit positioning The customer should check that the strength of the supporting surface is suitable for the weight of the unit. It is unnecessary to fix the unit to the floor for correct operation. If the floor is rough, to ensure a level surface and prevent even the smallest of vibrations, it is advisable to insert a continuous rubber sheet the same size as the base supports. It is also advisable to make sure the unit is level. Should this be impossible or difficult to accomplish, the unit must not tilt more than 0.5°.

For a correct operation and for maintenance interventions respect the free space around the unit (see figure).

WARNING: The gas content into the R290 is flammable. The chiller should be installed only outside and away from any heat source and sunlight protected. Max Temp = +45.0 ° C (storage) Max Temp = +40.0 ° C (operating)

Tel: 01823 665660

[13]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Example of placement under a roof

The units must be installed without obstructing the air intakes. When installing under a canopy roof, this roof must be at least 3 meters above the top of the unit.

Tel: 01823 665660

[14]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Description of operation of the machine Liquid chillers of the series "EKE-R290" are designed to meet the needs of air conditioning systems or industrial processes, requiring the production of chilled water. The variety of models and power, can cover a wide range of applications. The production of cold water occurs through the refrigerant cycle, as shown in the following diagram:

The refrigeration system consists of a compressor, a condenser, an expansion valve, and an evaporator. The use of the suction gas heat exchanger (SGHX) is a special feature of EKE-R290 EUROKLIMAT range.

Description of cycle process The suction gas (1) is compressed and discharged into the discharge line (2). The discharge line leads the refrigerant to the inlet of the condenser (3). The condensed and subcooled refrigerant in the condenser outlet (4) is either lead to the liquid inlet of the suction gas heat exchanger (SGHX). The exit condition (5) will be different from condition (4). From the expansion valve outlet (6) the refrigerant is lead to the evaporator. The evaporated and superheated refrigerant in the evaporator outlet (7) is lead through the suction line, either to the gas side inlet of the SGHX, if this has been selected, or to the compressor inlet (1). Thanks to SGHX the exit condition (8) will be different from condition (1). In the suction line the gas may experience both a pressure drop and a temperature increase. In the discharge line the gas may experience a pressure drop only.

Tel: 01823 665660

[15]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Safety measures taken on the units EKE-R290 In order to avoid the possibility of fire or explosion due to a possible leak of refrigerant, the following measures have been adopted in the design, construction and assembly of the unit:

Semihermetic compressor ATEX Certified The compressors of the units EKE R290 EUROKLIMAT are designed in accordance to the safety requirements necessary for the installation in ambient classified, for presence of flammable gas (Zone 2, Gas group IIB) according to Directive ATEX 94/9/CE, these compressors are equipped with electrical components conform to this Directive.

The main characteristics that distinguish these compressors from standard types are: • Mechanically optimized for use with HC • Special oil charge • Equipotential connection of all electrical components • Electrical connection box • Crankcase heater • PTC sensor for discharge temperature control • Electronic oil differential pressure switch • Capacity control head

Electronic control module INT69/INT69TM for remote Installation (installed in the electrical switchboard of the unit).

Tel: 01823 665660

[16]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Main components in the refrigerant circuit ATEX certified

Tel: 01823 665660

[17]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Device for detecting leaks of refrigerant R290 (GAS LEAK DETECTOR) The refrigerant leak-detection device installed inside the unit disconnects the power supply to compressors contactors if presence of R290 it is detected inside the unit frame.

Setting = 20% of LEL (Low Explosion Limit)

Other safety precautions - Water flow switch IP55 positioned outside the machine; - Anterior and posterior panels with ventilation grills. - Security Alerts:

Tel: 01823 665660

[18]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Water connections Authorised personnel: Maintenance mechanic Before carrying out the water connections to the user positions on the water circuit, the installed piping must be flushed through to eliminate machining residues and in any case to reveal any leaks.

Water drain This outlet is fitted with a hose connecting tap suitable for attaching, and securing with a hose clamp, a plastic hose with an inside diameter of 13 mm. It allows the filling of the tank connetting it to the water net. During the unfilling of the inside tank (if present), it allows to drain the water to the extern.

Air purge This outlet is fitted with a hose connecting tap suitable for attaching, and securing with a hose clamp, a plastic hose with an inside diameter of 13 mm. During the unfilling of the inside tank (if present), it allows to drain the water to the extern.

Water outlet This connection is male and has a diameter that changes by the size of the unit as for following table. Connect the outlet pipe of the chilled water to the plant. The diameter of the pipe must be equal or major of the diameter of the outlet connection.

Water inlet This connection is male and has a diameter that changes by the size of the unit as for following table. Connect the intlet pipe of the heated water from the plant. The diameter of the pipe must be equal or major of the diameter of the outlet connection.

Tel: 01823 665660

[19]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Condensate drain “EKE R290” chiller has got a special condesate water recipient positioned under the air condenser; Since the tray collects rainwater it is not compulsory for the outlet to be connected to a drain. In any case the water may be drained off with a plastic hose secured with a hose clamp, the value of the hose diameter being given in the table.

Water connections dimensions

Serie “EKE” Model

Dimension Water drain

151 201 – 251 301 – 351 – 401 502 – 602

13 mm

Air purge

13 mm

Water outlet

Water inlet

1”¼

1”¼

1”½

1”½

2”

2”

3”

3”

Condensate drain

28 mm

Safety valves installation All the units are fitted with a safety valve on the water side. The purpose of this valve is to drain to the outside through a pipe. It is therefore advisable to connect the valve to a pipe of at least the same diameter in order to convey any discharge from the valve to the outside. This pipe must be located so that the discharge can cause no damage to property or injury to persons. The pipe must also be suitably supported so that it does not weigh on the valve. The installation must be in conformity with current safety regulations. If units are not used during the winter, fully drain the water system of all units installed outdoors. If operation is envisaged also in this period or in any case with low ambient temperatures, antifreeze mixtures must be used. With indoor installations, drainage is in any case necessary when the room temperature falls to below 0°C. For installation diagrams, refer to the examples given in the section “Installation”. Always fit ball shutoff valves on the water inlet and outlet. If it is possible that the water may be dirty, also install a “Y” filter on the water inlet. For more information please contact the After Sales Department of Euroklimat S.p.A.. If the USER needs to disassemble some parts for which the procedure is not given in this manual, it is indispensable to request permission and the relevant procedure from “Euroklimat”. Any assembly/disassembly carried out by the USER that is not contemplated in this manual or authorised by “Euroklimat”, will be considered as tampering, thereby jeopardising the safety functions and invalidating the warranty of the unit. During construction of the unit all necessary measures are taken to ensure cleanliness in all the parts. After installation, clean the unit removing the protective substances. Use soft cloths and harmless detergent substances for cleaning, which do not damage the surfaces. The unit is always tested and inspected in the factory prior to delivery and requires no further controls.

Tel: 01823 665660

[20]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Electrical wiring Authorised personnel: Maintenance electrician The unit must be fitted with an emergency stop, which the installer must put in an easily accessible position. Should just one activation point be considered insufficient, several emergency stops in various points may be installed.

This device is available as an accessory from Euroklimat. There is just one version for all models

Power supply Carry out all the electrical connections, scrupulously observing the wiring diagrams supplied with the units. The components onboard the unit are protected by the equipment inside the switchboard. It is the end user’s responsibility to ensure the correct size and capacity of the power supply cable of the unit in relation to the total input indicated on the wiring diagram and the length of the same. This cable must also be protected by a safety device installed on the user’s electrical system

-

-

Connect the phase wires to the unit's circuit breaker, respecting the sequence of the phases L1 L2 L3. The neutral is not needed. The earth is connected to the special terminal inside the electrical panel. The picture to the side shows an example of connection of the cables. Power supply from below.

CAUTION USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. Failure to do so may cause damage to the equipment.

Tel: 01823 665660

[21]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Check of protective devices and unit operations before switching on Authorised personnel: Safety officer Should any abnormality be found when checking the unit, inform “Euroklimat” and do not operate the unit. Before switching on for the first time, the unit must be visually inspected, checking that: No electrical wires are loose, especially at connection points, and that there is no possibility of doubtful contacts. The fluid circuit connections have been carried out correctly and show no visible leaks or damage. The air intake and outlet sides have no obstructions of any kind whatsoever that could jeopardise efficient operation. The fluid circuit connections present no obstructions such as: clogged filters, closed manual or automatic shutoff valves, etc. Check that all the fixed guards are mounted and properly bolted in position and that the mobile protective elements are closed.

Tel: 01823 665660

[22]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Start-up procedure Filling the water circuit Authorised personnel: Maintenance mechanic

Before to start up the unit it’s necessary to fill the water circuit Water / mixture temperature for filling = MAX. 25°C Open the air valve (and connect it to a drainage well using a plastic hose) so that any air present in the circuit will be discharged during filling, which will consequently be quicker. Take care that any water that sprays out when the circuit has been filled does not create a hazardous situation. If there are any points in the system circuit higher than the unit air valve, another air valve, if possible automatic, must be inserted at the highest point to ensure complete filling of the circuit. - Connect the unit water outlet tap to the mains water system. - Open the mains water supply to fill the circuit. - When water comes out of the hose connected to the air valve, the circuit has been filled.

CAUTION Once the system has been filled and after having made the pump circulate for some time, check for residual air. If there is still air present, the circuit must be bled and filled up with the missing water. With the system inoperative, it is also necessary to ensure that the pressure in the circuit is only just above zero. This indication is visible through the pressure gauge mounted on the unit.

Warning: WHEN THE FILLING IS FINISHED YOU HAVE TO CLOSE THE WATER DRAIN TO AVOID THAT THE PRESSURE IN THE CIRCUIT INCREASES. (Not for versions with closed vessel, which is equipped with pressure reducing valve). Filling with antifreeze mixture If it is necessary to use antifreeze mixtures, filling must be carried out with a solution prepared according to the water temperature: Mixture / Outside % ethylene glycol temperature +20 °C +15 °C +10 °C 5% (suggested) +5 °C 10% 0 °C 15% -5 °C 25% -10°C 30% If a ready solution is unavailable, it must be prepared in a container to be connected to the unit water outlet, as described above. Closed or open tank filling kits are available on request by the customer.

For more information please contact the After Sales Department of Euroklimat S.p.A..

Tel: 01823 665660

[23]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

STARTING AND USE The professionals involved in this section are: The Operator, who must always operate with the fixed guards correctly mounted and check that under no circumstances have they been tampered with.

The Maintenance men, who must always operate with the unit at a standstill and after having carried out the required operations, check that all the protective devices are correctly remounted, closed and in proper working order.

The Safety officer, who must check that the Operator and the Maintenance men have received all the necessary information as per this manual. He will check in particular that all the fixed guards have been correctly mounted, are in proper working order and have not been tampered with.

Unit control devices Door interlock

Microprocessor for unit start and control

Compressor ON/OFF switch

1. Check the compressor ON/OFF switch is off (position “0”). 2. Turn the door interlock in position “1” (ON).

Warning When switching on for the first time, the oil must be preheated in the models indicated in the table. This requirement is also identified on the unit by the following plate. The procedure is carried out when starting the unit for the first time and whenever the unit has been switched off by means of the power on/off switch for longer than 4 hours. Do not proceed with other operations until this procedure has been completed, otherwise the compressors could be damaged.

Euroklimat S.p.A. declines every responsibility for eventual damages that can directly or indirectly derive to persons or things in consequence to the lacked observance the present instructions.

Tel: 01823 665660

[24]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Put to ON. On the microprocessor, press the button

for 5 seconds.

The water pump (if present) starts.

When starting for the first time, check the correct direction of rotation of the pump. To do this, close the ball valve fitted at the unit water inlet and outlet, as described in the paragraph “water connections”. Fully open the by-pass. Using the pressure gauge on the unit check that the circuit is pressurised. If it is not, switch off the unit using the power on/off switch and invert the connection phases at the on/off switch input, paying attention to the possible presence of current. Then check the working pressure with the pressure gauge on the unit. Make sure that there are no automatic valves, which could reduce the flow, and that the circuit shutoff valves are fully open. Use the handle of the by-pass valve to adjust the pressure until the liquid pressure gauge indicator is in the appropriate sector. This sector is specific for each type of pump (standard or uprated) and for each model. The table below indicates the operating range for each combination.

Standard Pump [bar]

Uprated pump [bar]

“EKE” pump operating range 81 – 101 – 121 – 151 201 251 – 301 – 351 401 – 502 – 602

min

max

min

max

2,3 3,1 3,3 2,5

3,1 3,7 3,6 3,2

4,5 5,4 5,3 4,3

5,0 5,9 5,8 5,2

Enable the compressors by putting the relative switch to position 1 (ON).

Tel: 01823 665660

[25]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

COOLING mode If the temperature of the water (see value of the display) is lower than r01 (Summer/cooling set point) value (default is 7.0°C), the compressor is OFF. The water pump (if present) runs. If the temperature of the water (see value of the display) is higher than r01 + r02 (differential) value (default is 3.0°C), the compressor is ON and the cooling starts and runs valore di set point r01.

FOR SET POINT MODIFICATION (r01 and/or r03) SEE CHAPTER “CONTROL PANEL”

Check of cooling The chiller normally works with a difference of approx. 5° between the evaporator water inlet and outlet (with by-pass valve closed), which may be checked with contact thermometers. Check for any alarm warnings.

Checking the safety devices The unit, connected as described in the section “Commissioning” under the paragraph “Connection of Safety Devices”, must guarantee safety functions in an emergency. The emergency stop button must therefore be pressed to check that all the motors stop. If operation is correct, reset the emergency button and continue with the switching on procedure as described previously.

Compressor START/STOP This switch is used to cut out compressor operation and allow the unit to work with the pump only whenever working conditions so require. Under normal working conditions compressor starting and stopping is automatic and is controlled entirely by the microprocessor. Position “0”: Compressor off Position “1”: Compressor on

The unit is equipped with a safety that doesn’t permit more than 1 (one) START/STOP every 3 minutes from the first.

Tel: 01823 665660

[26]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Standby Press button

for 5 seconds.

Since the compressor and the pump are timed and work together, before stopping they finish the cycle in progress. A certain interval may therefore be necessary before the unit comes to a total stop. In this condition the unit is in stand-by and may be restarted by just pressing the button for 5 seconds.

During stand-by preheating of the oil is unnecessary.

Switching off This operation should always be carried out after having put the unit in stand-by and after all the components have come to a stop. Put the door interlock switch to OFF.

If the unit has been at a standstill for more than 4 hours, before restarting the oil must be preheated.

Tel: 01823 665660

[27]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Control panel “EKE R290” water chillers are fitted with a compact electronic control (µchiller2 SE), having the size of a normal thermostat, for complete control of the unit.

CONTROLPANEL Reference refrigerant circuit

Meaning

Symbol

Colour

1;2 3;4

with LED on

with LED flashing

Amber

Compressor 1 and/or 2 ON

Start up request

1

Amber

Compressor 3 and/or 4 ON

Start up request

2

Amber

At least one compressor ON

-

1/2

Amber

Pump ON (if present)

Start up request

1/2

Amber

Not used

-

1/2

Amber

Defrost ON (only “heat pump”)

Defrost request (only “heat pump”)

1/2

Amber

Heater ON (if present)

-

1/2

Red

Alarm active

-

1/2

Amber

Heating mode (only “heat pump”)

Heating mode request (only “heat pump”)

1/2

Amber

Cooling mode (chiller)

Cooling mode request (chiller)

1/2

Main functions -

water temperature control complete alarm management set-up for serial line for supervision/remote servicing a connectable external terminal (optional) self-diagnosis

Tel: 01823 665660

[28]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Controlled devices -

compressor condensing fans water circulating pump safety and timing devices, alarms

Display The 3-digit display automatically shows the decimal point between -19.9 and +19.9 °C. Outside this range the value is automatically displayed without the decimal point (although the unit always operates inside considering the decimal part). In the normal operating mode the displayed value corresponds to the temperature read by the sensor. In the event of alarm, the sensor value is displayed alternately with the codes of the active alarms. During programming the parameter codes and their value appear on the display. The visualization and the configuration of the unit is possible also using a remote control panel (available on request).

Remote control panel (available on request) The remote control panel (available on request) is an electronic device that allows the remote control of the unit. The functions allowed are the same as those available on the display and the local keypad of the µChiller2 installed on the unit. The connection between the remote control panel and the unit is possible using a pin-to-pin phone cable (max. length = 40 meters). For more longer applications please contact the Euroklimat S.p.A. Customer Service.

There are 2 versions of the remote control panel (available on request): - version for panel installation - version for wall-mounting installation Panel installation This version has been designed for panel installation, with the drilling template measuring 127 x 69 mm with 2 circular holes, diameter 4 mm, as shown in figure. For installation proceed as follows: -

connect the telephone cable; insert the terminal, without the front frame, in the opening, and use the countersunk screws to fasten the device to the panel; finally, apply the click-on frame.

Tel: 01823 665660

[29]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Version for wall-mounting installation The version of the terminal for wall-mounting requires the rear of the case A to be fastened (see figure) using a standard 3-module switch box.

-

fasten the rear of the case to the box using the round-head screws; connect the telephone cable; rest the front panel on the rear of the case and fasten the assembly using the countersunk screws, as shown in figure; finally, apply the click-on frame.

To install the remote terminal, no configuration is required on the µChiller2. When first switched on the display will show the firmware version of the µChiller2. After around 4 s the main screen will be displayed, with the symbols that represent the status of the µChiller2. Now it’s possible to obtain all the functions managed by the control installed on board of the chiller unit.

Tel: 01823 665660

[30]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Set point modification (outlet water temperature) in COOLING mode The manufacturer set point setting is 7.0°C; the range of possible values is +5 / +20°C for standard version. Normal condition: When starting or during the operation, the display shows the water temperature (es.: 14,0°C).

Press SEL button for 5 seconds The display shows - / Press button

for 3 times

The display shows –r– Press SEL button The display shows r01 Press SEL button The display shows the actual value of set point (7.0°C)

Press Press

button the increase the value; button to decrease the value.

The display shows the new value (es.: 12.5°C) Press SEL button Press PRG button for 3 times to save the new value and to come back to the standard visualization (water outlet temperature)

Tel: 01823 665660

[31]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

TROUBLESHOOTING Authorised personnel: maintenance mechanic, electrician and refrigeration technician. In the event of unit malfunction, the display starts to blink and the buzzer activates.

The alarm identification code appears on the display for a few seconds, while the buzzer continues. Press the PRG key to mute the buzzer. The display continues to blink and the alarms are not reset.

Remove the causes that have generated the alarm. Press the keys

and

simultaneously for a few seconds to reset.

The display stops blinking and the normal screen display returns.

Tel: 01823 665660

[32]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

List of main ALARMS µchiller2 SE “EKE R290” ALARM code

Action

Description

Reset Size

Compress.

Fan

Pump

manual

OFF

OFF

-

manual

OFF

OFF

-

OFF

OFF

-

OFF

OFF

-

HP1 HP2

High pressure alarm (circuit 1)

all

High pressure alarm (circuit 2)

502

802

LP1

Low pressure alarm (circuit 1)

M2

401

LP2

Low pressure alarm (circuit 2)

502

802

General overload alarm

M2

401

manual

OFF

OFF

OFF

Circuit 1 overload alarm

502

802

manual

OFF

OFF

OFF

Circuit 2 overload alarm

502

802

manual

OFF

OFF

OFF

Water flow alarm

all

manual

OFF

OFF

OFF

E1÷ E8 probe alarm

all

automat.

OFF

OFF

OFF

EEPROM error during operation

all

automat.

-

-

-

EEPROM error at the start-up

all

automat.

OFF

OFF

OFF

Expansion error

502

automat.

OFF

OFF

OFF

Antifreeze alarm

all

manual

OFF

OFF

-

tP tC1 tC2 FL E1 E8 EPr EPb ESP A1

manual M2-M4: auto manual M2-M4: auto

802

List of WARNING µchiller2 WARNING code

Ht Lt AHt ALt ELS ELH

“EKE R290” Description

Action Reset

Size

Compress. Fan

Pump

High temperature plant warning

tutte

manual

-

-

-

Low temperature plant warning

tutte

manual

-

-

-

High temp. plant at the start-up

tutte

manual

-

-

-

Low temp. plant at the start-up

tutte

manual

-

-

-

Low supply voltage

tutte

automat.

-

-

-

High supply voltage

tutte

automat.

-

-

-

-

-

-

-

-

-

-

-

D1

Defrost circuit 1

D2

Defrost circuit 2

Tel: 01823 665660

M2 401 “heat pump” 502 802 “heat pump”

[33]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

High pressure alarm HP1 (circuit 1) HP2 (circuit 2)

Description: The alarm leads to the immediate stopping of the compressor and the fan, activation of the buzzer and the alarm relay, and blinking of the display.

CAUSE

CHECK

AUTHORIZED PERSONNEL

Airflow rate too low.

Check for obstructions near or on the air intake and outlet. Maintenance mechanic. Check the condensing coil for fouling.

Air inlet temperature too high.

Measure the inlet air temperature and compare it with design values. Refrigeration technician. (ver. ST= standard  max. +40°C) Eliminate any recirculation of expelled air. Check that the condensation control systems are in proper working order. Check the fan motor and the electrical circuit for breaks or faults. Replace the defective piece. Maintenance mechanic. Maintenance electrician. Check if the fan thermal cutout has tripped and if necessary check its absorption.

Condensing fans do not start.

Check the direction of rotation of the fans. Check and bring it to within the recommended Refrigeration technician. limits.

Refrigerant circuit too full. Faulty high operation.

pressure

switch

Compressor delivery partially closed.

valve

Check correct operation of its contact; check the connecting capillary for obstruction or crushing Refrigeration technician. and if necessary replace. Check its state and if necessary open the valve.

Refrigeration technician.

Check the motor winding and the charge level. Replace if necessary.

Check that the winding resistance is correct and there is no short circuit. Replace the compressor if necessary. The compressor is mechanically jammed or has gripped. Replace the compressor. Compressor thermal cutout trips Maintenance mechanic. due to motor overheating. Absorption is too high. Check operating Maintenance electrician. conditions (water and expansion tank temperatures, condensation, overheating, supercooling, etc.). The motor is operating with single-phase instead of three-phase power supply. Check the power supply voltage and correct electrical connection. Check continuity of the single windings.

Tel: 01823 665660

[34]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Low pressure alarm LP1 (circuit 1) LP2 (circuit 2)

Description: The alarm is detected with the compressor on or off and leads to the immediate stopping of the compressor or its non-start. The buzzer and the alarm relay activate and the display blinks.

CAUSE

CHECK

AUTHORIZED PERSONNEL

Check the water circuit for closed valves, obstructed filters or obstructions of any kind. No water.

Refrigeration technician. Check the pump for the direction of rotation and correct operation. Check the sensitive bulb and its capillary for leaks and if it is therefore empty. Check the external equaliser for obstruction or crushing Refrigeration technician. and that overheating is within correct values. Replace if necessary.

Faulty thermostatic valve.

Thermostat calibration.

valve

out

of Check the overheating values and re-calibrate if Refrigeration technician. necessary.

Condensation pressure too low.

Check operation of the condensation control Refrigeration technician. systems.

No gas in refrigerant circuit.

Search for any gas leaks. Repair and restore Refrigeration technician. correct gas load.

Obstructed filter on liquid line.

Replace the filter.

Faulty low operation.

Check correct operation of its contact; check the connecting capillary for obstruction or crushing Refrigeration technician. and if necessary replace.

pressure

switch

Refrigeration technician.

Overload alarm tP (general) tC1 – tC2 (circuit 1-2)

The alarm leads to the immediate stopping of the compressor and the fan, activation of the buzzer and the alarm relay, and blinking of the display.

CAUSE

CHECK

Description:

AUTHORIZED PERSONNEL

Test the winding resistance of the motor and if abnormal replace the compressor.

The compressor is mechanically jammed or has gripped. Replace the compressor. Intervention of the The absorption is too high. Check operating magnetothermal protection of the conditions (water temperature, evaporating Maintenance electrician. compressor. pressure, condensing pressure, superheating, subcooling, etc…). Check the power supply voltage and correct electrical connection. Check the continuity of the single windings.

Tel: 01823 665660

[35]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Flow switch alarm Pump thermal cut-out FL

Description: The alarm is detected irrespective of the pump and compressor status. The compressor, pump and fan stop, while the buzzer and alarm relay activate and the display blinks.

CAUSE

CHECK

AUTHORIZED PERSONNEL

Check the water circuit for any closed valves, obstructed filters or obstructions of any kind. No water.

Refrigeration technician. Check the pump for the direction of rotation and correct operation. Test the winding resistance and if abnormal replace the pump.

Pump winding short-circuited.

Maintenance electrician. The pump is mechanically jammed or has gripped. Replace the pump.

Check operating conditions in terms of flow rate Pump current absorption too and delivery pressure. If necessary re-calibrate Maintenance electrician. high. pump operation using the by-pass valve. Pump motor operating with Check the power supply voltage and correct single-phase instead of three- electrical connection. Maintenance electrician. phase power supply. (ver. MICRO2 – MICRO4 excluded) Check the continuity of the single windings. Incorrect calibration of flow Check instrument calibration and operation and Refrigeration technician. switch or mechanical failure. replace if necessary.

Description:

Probe alarm E1 …. E8

CAUSE

Probe damaged or fault.

Tel: 01823 665660

These alarms are also detected with the unit in stand-by. The values read by a sensor are outside normal values. The presence of a sensor alarm leads to deactivation of the compressor, the condensing fans and the pump. The buzzer and alarm relay activate and the display blinks.

CHECK

AUTHORIZED PERSONNEL

Check the wiring between the sensor and the Maintenance electrician. microprocessor for breaks or faults.

[36]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Description:

EEPROM error during operation EPr

The microprocessor continues to perform the control of the unit with the data present in the random memory (RAM). After the first power supply failure the configuration will be lost.

CAUSE

Microprocessor error.

EEPROM error at the start-up EPb

CHECK

Turn OFF the unit. Wait for some seconds. Turn ON the unit. If after the autocontrol the Maintenance electrician. alarm will be shows again, replace the regulator.

Description: At the start-up of the µchiller2 it blocks and the diciture appears on the display.

CAUSE

Microprocessor error.

Communication error with expansion card ESP

(mod. 502 – 602) CAUSE

Communication data error.

Tel: 01823 665660

AUTHORIZED PERSONNEL

CHECK

AUTHORIZED PERSONNEL

Turn OFF the unit. Wait for some seconds. Turn ON the unit. If the alarm will be shows Maintenance electrician. again, replace the regulator.

Description: If the control µchiller2 loses communication with the expansion card, the entire system will be stopped to avoid affecting the unit. The alarm leads to the immediate stopping of the compressor and the fan, activation of the buzzer and the alarm relay, and blinking of the display.

CHECK

AUTHORIZED PERSONNEL

Turn OFF the unit. Wait for some seconds. Turn ON the unit. If the alarm will be shows Maintenance electrician. again, contact Euroklimat SpA.

[37]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Descrption:

Antifreeze alarm A1

CAUSE

The alarm is detected through the water sensor in the tank when the evaporator outlet water temperature is below the set antifreeze threshold. The compressor and the condensing fans stop immediately, the buzzer and the alarm relay activate and the display blinks.

CHECK

AUTHORIZED PERSONNEL

Check the water circuit for closed valves, obstructed filters or obstructions of any kind. No water.

Refrigeration technician. Check the pump for the direction of rotation and correct operation.

Water temperature too low.

Tel: 01823 665660

Check operating set point calibration.

[38]

www.heronhill.co.uk

Refrigeration technician.

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Periodical checks and servicing

WARNING: The refrigerant R290 (Propane) is flammable and it must be handled only by competent and responsible operators, under the conditions specified in the safety regulations in force.

Semi-hermetic compressor maintenance The periodical working pressure and lubricant level check are sufficient warranty for a long compressor operative life and for the reliability of the declared performances. The requested maintenance interventions are:

-

lubricant replacement after approx. 100 working hours from the initial compressor start to remove impurities remained in the system and collected in the crankcase from refrigerant and lubricant flow.

-

lubricant charge replacement each 10000 working hours to grant the original viscosity characteristics.

All lubricant replacement operations have to be executed when the compressor is at standstill. For lubricant replacement are required instruments that are part of the normal equipment of each refrigerator technician; the necessary instruments to execute the ordinary maintenance operations are: - vacuum pump - lubricant hand pump - flexible hoses with swivel connections and valve opener - ratchet wrench for square stems  With working compressor, close the suction valve; when the suction pressure reduces at 0.1÷0.2 bar, switch off the compressor.

CAUTION: Do not loose any compressor bolt or closing plug  close the discharge valve  remove, slowly, discharge valve plug  remove the oil discharge plug (ref.6, see drawings on catalogue) and let flow all the lubricant in a suitable package.

Do not pollute the environment with lubricant; it is a special waste and it has therefore to be carried off as per the regulations in force.

Tel: 01823 665660

[39]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

          

screw and close well the oil discharge plug and discharge valve plug remove the oil charge plug (ref.3, see drawings on catalogue), applying at its place a Schrader service valve remove the protection cap from the service valve and connect the lubricant hand pump discharge connect the hand pump suction to the lubricant package by acting the hand pump, introduce the right oil quantity in the compressor crankcase remove the hand pump from the service valve connect the vacuum pump suction line to the Schrader service valve start the vacuum pump and evacuate the compressor for at least 15 minutes disconnect the pump from the service valve and switch off screw the protection cap to the service valve open the compressor discharge and suction valves

CAUTION Failure to open the valve before starting, will cause many damages both to compressor and possibly to operator.  start the compressor  after 15 ÷ 20 working minutes, check the lubricant level The level at which the lubricant settles during compressor working is highly influenced by the discharge ratio and therefore by the working temperatures. Considering that the acceptable minimum level is 1/4 of oil sight glass, the maximum level has not to be higher than 3/4 of the sight glass, as illustrated in figure behind.

Oil Type

Mineral oil SFR68S Checking the condensing coil Authorised personnel: maintenance mechanic Frequency: once a month Checks: visually check from outside the unit if there is any dirt, such as paper, dry leaves or simply dust, on the coil. The presence of such deposits causes a reduction in the air flow with a consequent reduction of efficiency and the possibility that the high pressure switch could trip resulting in the unit stopping.

Tel: 01823 665660

[40]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

Checking the electrical equipment Authorised personnel: maintenance electrician Frequency: once a month Checks: check the wiring to ensure that there are no loose wires at connection points and no possibility of doubtful contacts. For the check, proceed as follows: - switch off the unit by putting the switch to ‘0’; - check that there are no moving parts; - once the unit has stopped, open the electrical panel; - gently tug the wires of the contacts to check that the wiring up is secure; if necessary tighten the screws using a screwdriver. -

Seasonal stop Authorised personnel: maintenance mechanic and electrician. Frequency: once a year. Procedure: -

close the water circuit water supply valve; if the system risks being exposed to freezing temperatures during the period of inactivity, fully drain the water circuit; disconnect from the electricity supply by means of the power on/off switch, ensuring that the switch cannot be put to “on” again during the period of inactivity of the system.

Seasonal start Authorised personnel: maintenance mechanic and electrician. Frequency: once a year. Procedure: -

open the water supply tap; if the system has been drained, refill the water circuit; Carry out all checks and procedures as with the first time of starting.

Tel: 01823 665660

[41]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

R290 (Propane) Safety Data Sheet

1.

IDENTIFICATION OF THE SUBSTANCE

Product name Chemical formula

2.

Propane C3H8

COMPOSITION/INFORMATION ON INGREDIENTS

Substance/Preparation Substance. Components/Impurities Contains no other components or impurities which will influence the classification of the product. CAS Nr 74-98-6 EC Nr (from EINECS) 200-827-9

3.

HAZARDS IDENTIFICATION

Hazards identification

4.

Liquefied gas Extremely flammable

FIRST AID MEASURES

Inhalation

In low concentrations may cause narcotic effects. Symptoms may include dizziness, headache, nausea and loss of co-ordination. In high concentrations may cause asphyxiation. Symptoms may include loss of mobility/consciousness. Victim may not be aware of asphyxiation. Remove victim to uncontaminated area wearing self contained breathing apparatus. Keep victim warm and rested. Call a doctor. Apply artificial respiration if breathing stopped.

Skin/eye contact

In case of frostbite spray with water for at least 15 minutes. Apply a sterile dressing. Immediately flush eyes thoroughly with water for at least 15 minutes. Obtain medical assistance

Ingestion

Ingestion is not considered a potential route of exposure.

Tel: 01823 665660

[42]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

5.

FIRE FIGHTING MEASURES

Specific hazards

Exposure to fire may cause containers to rupture/explode.

Hazardous combustion products Incomplete combustion may form carbon monoxide. Suitable extinguishing media

All known extinguishants can be used.

Specific methods

If possible, stop flow of product. Do not extinguish a leaking gas flame unless absolutely Spontaneous/explosive re-ignition may occur. Extinguish any other fire.

necessary.

Special protective equipment for fire fighters Use self-contained breathing apparatus

6.

ACCIDENTAL RELEASE MEASURES

Personal precautions

Evacuate area. Wear self-contained breathing apparatus when entering area unless atmosphere is proved to be safe. Ensure adequate air ventilation. Eliminate ignition sources.

Environmental precautions

Try to stop release. Prevent from entering sewers, basements and workpits, or any place where its accumulation can be dangerous.

Clean up methods

Ventilate area

7.

HANDLING AND STORAGE

Handling and storage

8.

Ensure equipment is adequately earthed. Suck back of water into the container must be prevented. Purge air from system before introducing gas. Do not allow backfeed into the container. Use only properly specified equipment which is suitable for this product, its supply pressure and temperature. Contact your gas supplier if in doubt. Keep away from ignition sources (including static discharges). Segregate from oxidant gases and other oxidants in store. Refer to supplier's container handling instructions. Keep container below 50°C in a well ventilated place.

EXPOSURE CONTROLS/PERSONAL PROTECTION

Personal protection

Ensure adequate ventilation. Do not smoke while handling product

Tel: 01823 665660

[43]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

9.

PHYSICAL AND CHEMICAL PROPERTIES

Molecular weight Melting point Boiling point Critical temperature Relative density, gas Relative density, liquid Vapour Pressure 20°C Solubility mg/l water Appearance/Colour Odour

Flammability range Autoignition temperature Other data

10.

STABILITY AND REACTIVITY

Stability and reactivity

11.

No known toxicological effects from this product.

ECOLOGICAL INFORMATION

General

13.

No known ecological damage caused by this product.

DISPOSAL CONSIDERATIONS

General

14.

Can form explosive mixture with air. May react violently with oxidants.

TOXICOLOGICAL INFORMATION

General

12.

44 -188°C -42.1°C 97°C 1.5 (air=1) 0.51 (water=1) 8.3 bar 75 mg/l Colourless gas Sweetish Poor warning properties at low concentrations. Stenchant often added 2.1 - 9.5 vol% in air. 450°C Gas/vapour heavier than air. May accumulate in confined spaces, particularly at or below ground level.

Do not discharge into areas where there is a risk of forming an explosive mixture with air. Waste gas should be flared through a suitable burner with flash back arrestor. Do not discharge into any place where its accumulation could be dangerous. Contact supplier if guidance is required.

TRANSPORT INFORMATION

Proper shipping name UN Nr Class ADR/RID Classification code ADR/RID Hazard Nr Labelling ADR Other transport information

Tel: 01823 665660

PROPANE 1978 2 2F 23 Label 2.1: flammable gas Avoid transport on vehicles where the load space is not separated from the driver's compartment. Ensure vehicle driver is aware of the potential hazards of the load and knows what to do in the event of an accident or an emergency. Before transporting product containers ensure that they are firmly secured and: - cylinder valve is closed and not leaking. - valve outlet cap nut or plug (where provided) is correctly fitted. - valve protection device (where provided) is correctly fitted. - there is adequate ventilation. - compliance with applicable regulations.

[44]

www.heronhill.co.uk

Fax: 01823665807

Heronhill - for all your Euroklimat requirements Air cooled water packaged chiller | Serie: EKE-R290 (Propane) File name: Manuale_EKE-R290_uk_r0

15.

REGULATORY INFORMATION

Number in Annex I of Dir 67/548 EC Classification -Symbols F+: Labelling of cylinders -Symbols -Risk phrases -Safety phrases

16.

601-003-00-5. F+;R12 Extremely flammable Label 2.1: flammable gas R12 Extremely flammable. S9 Keep container in well ventilated place. S16 Keep away from ignition sources - No smoking. S33 Take precautionary measures against static discharges.

OTHER INFORMATION -

Ensure all national/local regulations are observed. Ensure operators understand the flammability hazard. Contact with liquid may cause cold burns/frost bite. The hazard of asphyxiation is often overlooked and must be stressed during operator training. Users of breathing apparatus must be trained.

This Safety Data Sheet has been established in accordance with the applicable European Directives and applies to all countries that have translated the Directives in their national laws.