RP-L7/B7 Twin/Triple/ Double Twin Application
Split Sky Air
air conditioning systems
technical data
Split - Sky Air
ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment
Daikin units comply with the European regulations that guarantee the safety of the product.
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.
Zandvoordestraat 300 B - 8400 Ostend Belgium Internet: http://www.daikineurope.com
EEDE05-1/2 • 05/2005 Prepared in Belgium by Goekint Graphics
Specifications are subject to change without prior notice.
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
TABLE OF CONTENTS RP-L7/B7 1
Features
2
Specifications
.................................................................................
.......................................................................
2 3
Technical specifications Electrical specifications
3
Combination table
.............................................................
6
4
Capacity tables
...................................................................
8
5
Dimensional drawings
6
.....................................................
10
Operation range
.................................................................
10
7
Piping diagrams
..................................................................
11
8
Wiring diagrams
.................................................................
14
9
Sound level
..........................................................................
14
Sound level data Sound pressure spectrum
10
Accessories
..........................................................................
14
Standard accessories Optional accessories
11
Center of gravity
12
Safety device settings
13
Installation
• Split - Sky Air • Outdoor Units
................................................................
14
......................................................
14
............................................................................
15
1
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
1
1 1
2
Features
Outdoor units for twin/triple/double twin application. + It is possible to connect 2, 3 or 4 indoor units to one single outdoor unit. The indoor units may be of different types (e.g. ceiling mounted cassette, wall mounted,...) and even different capacities (e.g. 45 and 60 class). All indoor units are operated together within the same mode (cooling or heating) from one remote control. This allows an equal air distribution in larger rooms, even if they are irregularly shaped. + Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall. + They are fitted with a scroll compressor, renowned for low noise and high energy efficiency.
• Split - Sky Air • Outdoor Units
+ The piping connections can be accessed from underneath, front, side or rear. + The service valves are hidden inside the casing. + A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions.
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
2
Specifications
1 2
TECHNICAL SPECIFICATIONS OUTDOOR UNITS DIMENSIONS
WEIGHT MATERIAL COLOUR SOUND LEVEL FAN
HEAT EXCHANGER
REFRIGERANT CIRCUIT
COMPRESSOR
PIPING CONNECTIONS
INSULATION MATERIAL
Unit
Unit Unit Sound pressure (1) Sound power (2) Air flow rate Speed Qty x model Qty x motor output Type
mm mm mm kg
high high high steps high
dB(A) dB(A) m3/min
50 63 48
rpm
-
W mm m2
1 x 65 Hi-XSS cooling tube, non sym. waffle fin 2 x 34 x 2.0 0.634
1 x 80 Non symm. waffle louvre, Hi-XA U-cooling tube 2 x 38 x 2.0 0.719
kg m
2.8 5 / 70
3.1 - / 70
m
30 Expansion valve (electronic type)
30 -
Type Qty x model
Heat insulation Safety devices
RP71B7/T1 RP100L7V1/W1 860 1,170 880 900 320 320 88/85/85 100/99 Painted galvanised steel plate Ivory white 50 53 63 66 51 55 3 steps -
H W D
Rows x stages x fin pitch Face area Refrigerant type Refrigerant charge Minimum/maximum allowable distance between indoor and outdoor Maximum allowable level difference Refrigerant control
Motor output x no Oil type Oil charge volume
RP71L7V1/W1 770 900 320 79/78
W
liquid gas drain
! mm mm mm
1xP47L11S
RP100B7V1/T1 1,215 880 320 103/98/98
53 66 94
2xP47L11S
1 x 55 Hi-XSS cooling tube, non sym. waffle fin 2 x 52 x 2.0 0.983 R-407C 3.7 5 / 70
-
1 x (80 + 85) Non symm. waffle louvre, Hi-XA U-cooling tube 2 x 54 x 2.0 1.022 3.6 - / 70
30 30 Expansion valve (electronic type) Hermetically sealed scroll type 1 x JT90FA-V1N 1 x JT90FA-V1N/ 1 x JT125FA-V1N 1 x JT125FA-V1N/ 1 x JT90FA-YE/ 1 x JT125FA-YE/ 1 x JT90FA-T1 1 x JT125FA-T1 2,200 x 1 3,750 x 1 DAPHNE FVC68D 1.2 1.2 1.5 1.5 φ9.5 φ15.9 φ19.1 φ26 x 3 Both liquid and gas pipes High and low pressure switch, thermal protector for indoor and outdoor fan motor, overcurrent relay (compressor), reverse phase protector, fuse 3TW25161-1B 3TW25211-1B 3TW25171-1A 3TW25221-1A 3TW25231-1A
• Split - Sky Air • Outdoor Units
3
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
2
Specifications
1 2
TECHNICAL SPECIFICATIONS OUTDOOR UNITS DIMENSIONS
WEIGHT MATERIAL COLOUR SOUND LEVEL FAN
HEAT EXCHANGER
REFRIGERANT CIRCUIT
COMPRESSOR
PIPING CONNECTIONS
INSULATION MATERIAL SAFETY DEVICE SETTINGS
Unit
Unit Unit Sound pressure (1) Sound power (2) Air flow rate Speed Qty x model Qty x motor output Type
H W D
mm mm mm kg
high
dB(A) dB(A) m3/min
high steps
W
Rows x stages x fin pitch Face area Refrigerant type Refrigerant charge Minimum/maximum allowable distance between indoor and outdoor Maximum allowable level difference Additional refrigerant charge
mm m2
m g/m
Heat insulation
rpm
liquid gas drain
53 67 89
3 steps 2 x P47L11S 85 + 65 Hi-XSS cooling tube, non sym. waffle fin 2 x 52 x 2.0 0.983
kg m
Type Qty x model Speed Oil type Oil charge volume Crankcase heater
RP125L7W1 1,170 900 320 104
! W mm mm mm
3.7 5 / 70
RP125B7T1 RP200B7W1 1,215 1,220 880 1,290 320 700 100 194 Painted galvanised steel plate Ivory white 53 56 67 77 94 170 2 x P47L11S 1 x (80+85) 2 x 54 x 2.0 1.022 3.9 - / 70
RP250B7W1 1,440 1,290 700 206
56 77 175
1 step 1 x P55J11F 1 x P55J11F 1 x (230+190) 1 x (230+140) Non symm. waffle louvre, Hi-XA U-cooling tube
R-407C
2 x 40 x 2 1.57
2 x 50 x 2 1.97
7.5 - / 50
9.2 - / 50
30 30 Please refer to item 13 ’Installation’ of this chapter
30 30 60 g/m for total piping length 90 g/m for total piping length >30m >30m Hermetically sealed scroll type 1xJT160FA-YE/ 1xJT236DA-YE@2 1xJT300DA-YE@2 1 x JT160FA-YE 1xJT160FA-T1 3,750 x 1 − 2900 2900 DAPHNE FVC68D 1.5 1.5 4 4 50 72 φ9.5 φ12.7 x 0.90 φ15.9 x 0.45 φ19.1 φ28.6 x 1.15 φ28.6 x 1.15 φ26 x 3 φ26 x 6 φ26 x 6 Both liquid and gas pipes High and low pressure switch, thermal protection for indoor and outdoor fan motor, fuse, overcurrent relay (compressor), reserve phase protection, compr. Thermal protection 3TW23281-1 3TW23291-1 3TW23301-1 3TW23331-1 3TW23341-1 3TW23351-1 3TW23381-1 3TW23391-1 3TW23611-1A 3TW23621-1A
4
• Split - Sky Air • Outdoor Units
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
2
Specifications
1 2
ELECTRICAL SPECIFICATIONS OUTDOOR UNITS CURRENT
POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM VOLTAGE
Nominal running current Maximum running current Starting current Phase Frequency Voltage
cooling/heating A cooling/heating A cooling/heating A
RP71L7V1/W1
Hz V
ELECTRICAL SPECIFICATIONS OUTDOOR UNITS CURRENT
POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM VOLTAGE
Nominal running current Max. running current Starting current Phase Frequency Voltage
cooling/heating A cooling/heating A cooling/heating A
Hz V
V1/W1 1∼/3N∼ 50 230 / 400
RP71B7T1 RP100L7V1/W1 Please refer to electrical data Please refer to electrical data Please refer to electrical data T1 V1/W1 3∼ 1∼/3N∼ 50 50 230 230 / 400
RP125L7W1 RP125B7T1 RP200B7W1 Please refer to electrical data 14.4 Please refer to electrical data 17.9 Please refer to electrical data W1 T1 W1 3N∼ 3∼ 3N∼ 50 50 50 400 230 400
RP100B7T1
T1 3∼ 50 230
RP250B7W1 17.2 27.5 W1 3N∼ 50 400
NOTES 1
The sound pressure level is measured via a microphone at 1m distance from the unit. It is a relative value, depending on the distance and acoustic environment. For measuring conditions: please refer to item 9 of this chapter.
2
The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.
ELECTRICAL DATA
See chapter RP-L7/B7 for the electrical data of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1
• Split - Sky Air • Outdoor Units
5
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
3
1 3
Combination table
Possible combinations for twin and triple application RP71-125L7 Possible indoor combination Simultaneous operation Twin
Triple Out
Out
Outdoor models In
In
RP71L7V1/W1 RP71B7T1
35-35 (KHRQ22M20T7)
RP100L7V1/W1 RP100B7T1
45-45 (KHRQ22M20T7)
45-60 (KHRQ22M20T7)
RP125L7W1 RP125B7T1
60-60 (KHRQ22M20T7)
45-71 (KHRQ22M20T7)
In
35-71 (KHRQ22M20T7)
In
In
35-35-35 (KHRP127HB7) 45-45-45 (KHRP127HB7) 3TW25149-3A
NOTES
6
1
Possible indoor units: FHYCP35-71, FUYP71, FHYKP35-71, FAYP71, FHYP35-71, FHYBP35-71, FDYMP71
2
Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).
3
When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. In note 1 are the indoor units mentioned in order of the possible function (most functions are on FHYCP, less functions are on FDYMP).
4
Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.
5
For unit specification of the outdoor units and the indoor units refer to the unit specifications mentioned for pair systems.
6
Nominal cooling capacities are based on the following conditions: Indoor air temperature: 27°CDB, 19.0°CWB, outdoor temperature 35°CDB. Nominal heating capacities are based on the following conditions: Indoor air temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB.
• Split - Sky Air • Outdoor Units
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
3
Combination table
1
Possible combinations and standard capacity for twin, triple and double twin application
3
RP200-250B7 Possible indoor combination Simultaneous operation Capacity [kW] Outdoor models
Cooling In
RP200B7W1
20.0
RP250B7W1
25.0
Twin
Triple
Double twin
Out
Out
Out
In
In
In
In
In
100-100 71-125 71-71-71 60-60-60 45-71-71 45-45-100 35-71-100 35-35-125 45-60-100 71-60-60 (KHRQ22M64T7) (KHRQ22M64T7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7)
125-125 (KHRQ22M64T7)
45-100-100 (KHRP127HB7)
60-60-125 (KHRP127HB7)
125-45-71 (KHRP127HB7)
100-71-71 (KHRP127HB7)
In
In
In
45-45-45-45 (2 x KHRQ22M20T7 + KHRQ22M64T7) 60-60-60-60 (2 x KHRQ22M20T7 + KHRQ22M64T7) 3TW23619-1A
NOTES 1
Possible indoor units: FHYCP35-125, FUYP71-125, FHYKP35-71, FAYP71-100, FHYP35-60, FHYP71-125, FHYBP35-125, FDYP125.
2
Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).
3
When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. Note 1 mentions the indoor units in order of the possible function (most functions are on FHYCP, less functions are on FDYP).
4
Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.
5
For unit specification of the outdoor units and the indoor units refer to the unit specifications mentioned for pair systems.
6
Nominal cooling capacities are based on the following conditions:Indoor air temperature: 27°CDB, 19.0°CWB, outdoor temperature 35°CDB. Nominal heating capacities are based on the following conditions:Indoor air temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB.
• Split - Sky Air • Outdoor Units
7
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
4
1 4
Capacity tables
Simultaneous operation RP71-100-125L7V1/W1 Cooling capacity
Outdoor
RP71
RP100
RP125
EWB (°C) 12.0 14.0 16.0 18.0 19.0 19.5 22.0 24.0 12.0 14.0 16.0 18.0 19.0 19.5 22.0 24.0 12.0 14.0 16.0 18.0 19.0 19.5 22.0 24.0
V1: 230V [50Hz] W1: 400V [50Hz]
Indoor
EDB (°C) 18.0 20.0 22.0 25.0 27.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 27.0 30.0 32.0
TC 6.2 6.6 7.2 7.7 8.0 8.0 8.7 9.4 8.4 8.9 10.1 10.8 11.1 11.2 12.2 13.0 11.1 11.8 12.7 13.3 13.6 13.8 15.1 15.9
20
PI 1.75 1.83 1.83 1.92 1.92 1.92 2.00 2.00 2.61 2.71 2.71 2.71 2.71 2.71 2.81 2.90 3.24 3.33 3.33 3.43 3.52 3.52 3,62 3.62
TC 6.1 6.5 7.0 7.5 7.7 7.9 8.5 9.1 8.3 8.8 9.8 10.5 10.8 11.0 11.8 12.7 10.8 11.4 12.1 13.0 13.3 13.5 14.6 15.5
25
PI 2.00 2.08 2.08 2.08 2.08 2.08 2.17 2.17 2.81 2.81 2.90 2.90 3.00 3.00 3.00 3.10 3.52 3.52 3.62 3.62 3.71 3.71 3.71 3.81
TC 5.7 6.0 6.5 7.2 7.3 7.4 8.0 8.6 8.1 8.7 9.1 9.8 10.1 10.3 11.2 11.9 10.0 10.7 11.4 12.1 12.7 12.8 13.7 14.6
Outdoor temperature (°CDB) 32 35 PI TC 2.17 5.5 2.25 5.9 2.25 6.3 2.33 6.8 2.33 7.1 2.33 7.2 2.42 7.9 2.50 8.4 3.19 7.8 3.19 8.4 3.29 8.9 3.29 9.6 3.39 10.0 3.39 10.1 3.48 11.0 3.58 11.6 3.81 9.7 3.90 10.4 3.90 11.1 4.00 11.8 4.09 12.2 4.09 12.4 4.19 13.4 4.28 14.3
PI 2.33 2.33 2.42 2.50 2.50 2.50 2.58 2.58 3.39 3.39 3.48 3.48 3.58 3.58 3.68 3.77 4.09 4.19 4.28 4.38 4.38 4.38 4.48 4.57
TC 5.3 5.5 6.0 6.4 6.6 6.7 7.4 8.0 7.5 7.8 8.5 9.0 9.4 9.5 10.4 11.1 9.2 9.8 10.4 11.2 11.5 11.7 12.9 13.6
40
PI 2.58 2.58 2.67 2.67 2.75 2.75 2.75 2.83 3.77 3.77 3.87 3.87 3.97 3.97 4.06 4.16 4.48 4.57 4.67 4.76 4.86 4.86 4.95 5.05
46
TC 4.9 5.3 5.5 6.0 6.2 6.3 6.8 7.4 6.9 7.5 7.8 8.4 8.7 8.8 9.6 10.3 8.6 9.2 9.7 10.4 10.8 11.0 12.0 12.9
PI 2.83 2.83 2.92 3.00 3.00 3.00 3.08 3.17 4.16 4.16 4.26 4.35 4.45 4.45 4.45 4.55 5.14 5.14 5.24 5.24 5.33 5.33 5.52 5.62
3TW25142-15
SYMBOLS
NOTES
EWB: EDB: TC: PI o: PI corr1:
Entering wet bulb temp. (°CWB) Entering dry bulb temp. (°CDB) Total capacity cooling (kW) Power input of outdoor unit (kW) Correction factor for Pi depending on voltage of outdoor (kW) PI corr2: Correction factor for Pi depending used indoor units (kW) PI: Total power input (kW) PI = PI o + PI corr1 + ∑ PI corr2 e.g. RYP100L7V1 + FHYBP71B7V1 + FHYP35B7V1 PI = 3.5 + 0.23 + 0.21 + 0.14 = 4.08 kW
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal capacities 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0m 5. Add the following correction to the power input for the different outdoor units (PI corr1)
Outdoor model RP71 RP100
Caution: TC and SHC are shown by kW
V1 0.06 0.23
Power supply W1 0 0
T1 0 0
6. Add the following correction to the power input for each connected indoor unit (PI corr2)
Indoor model 35 45 60 71
FHYBP 0.12 0.16 0.21 0.21
FH(Y)P 0.14 0.14 0.14 0.14
FHYCP 0.14 0.14 0.16 0.16
Indoor types FHYKP 0.046 0.069 0.12 0.12
FAYP
FUYP
0.069
0.16
FDYMP 0.12 0.16 0.21 0.21
NOTE: The total capacity does not change with different combination of indoor units.
8
• Split - Sky Air • Outdoor Units
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
4
Capacity tables
1
Simultaneous operation RP71-125B7T1 Cooling capacity
Outdoor
RP71
RP100
RP125
EWB (°C) 12.0 14.0 16.0 18.0 19.0 22.0 24.0 12.0 14.0 16.0 18.0 19.0 22.0 24.0 12.0 14.0 16.0 18.0 19.0 22.0 24.0
4
W1: 400V [50Hz]
Indoor
EDB (°C) 18.0 20.0 22.0 25.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 30.0 32.0
TC 6.2 6.6 7.2 7.7 7.9 8.7 9.4 8.4 8.9 10.1 10.8 11.1 12.2 13.0 11.0 11.8 12.7 13.4 13.7 15.1 15.9
20
PI o 1.7 1.8 1.8 1.8 1.8 1.9 1.9 2.3 2.4 2.4 2.5 2.5 2.6 2.7 3.3 3.3 3.3 3.4 3.5 3.6 3.7
TC 6.1 6.5 7.0 7.5 7.7 8.5 9.2 8.3 8.8 9.8 10.5 10.8 11.8 12.7 10.7 11.4 12.1 13.0 13.4 14.6 15.5
25
PI o 1.9 2.0 2.0 2.0 2.0 2.1 2.1 2.6 2.6 2.7 2.7 2.8 2.8 2.9 3.5 3.5 3.6 3.7 3.8 3.8 3.9
TC 5.7 6.0 6.5 7.2 7.3 8.0 8.6 8.1 8.7 9.1 9.8 10.1 11.2 11.9 10.0 10.7 11.4 12.1 12.7 13.8 14.6
Outdoor temperature (°CDB) 32 35 PI o TC 2.1 5.5 2.2 5.9 2.2 6.4 2.3 6.8 2.3 7.1 2.4 7.8 2.4 8.4 3.0 7.8 3.0 8.4 3.1 8.9 3.1 9.6 3.2 10.0 3.3 11.0 3.4 11.6 3.9 9.7 4.0 10.4 4.0 11.0 4.1 11.8 4.2 12.2 4.3 13.5 4.4 14.3
PI o 2.3 2.3 2.4 2.4 2.4 2.5 2.5 3.2 3.2 3.3 3.3 3.4 3.4 3.5 4.2 4.3 4.4 4.5 4.5 4.6 4.7
TC 5.2 5.5 6.0 6.4 6.6 7.4 7.9 7.5 7.8 8.5 9.0 9.4 3.7 11.1 9.2 9.8 10.4 11.1 11.5 12.9 13.7
40
PI o 2.5 2.5 2.6 2.6 2.7 2.7 2.8 3.5 3.5 3.6 3.6 3.6 9.6 3.8 4.6 4.7 4.8 4.9 5.0 5.1 5.2
46
TC 4.9 5.2 5.5 6.0 6.2 6.8 7.4 6.9 7.5 7.8 8.4 8.7 4.2 10.3 8.6 9.2 9.7 10.4 10.7 12.0 12.9
PI o 2.8 2.8 2.9 3.0 3.0 3.0 3.1 3.8 3.8 3.9 4.0 4.1 3.0 4.3 5.3 5.4 5.4 5.4 5.5 5.6 5.7
3TW23282-8A
SYMBOLS
NOTES
EWB: EDB: TC: PI o: PI corr1:
Entering wet bulb temp. (°CWB) Entering dry bulb temp. (°CDB) Total capacity cooling (kW) Power input of outdoor unit (kW) Correction factor for Pi depending on voltage of outdoor (kW) PI corr2: Correction factor for Pi depending used indoor units (kW) PI: Total power input (kW) PI = PI o + PI corr1 + ∑ PI corr2 e.g. RYP100L7V1 + FHYBP71B7V1 + FHYP35B7V1 PI = 3.5 + 0.23 + 0.21 + 0.14 = 4.08 kW
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal capacities 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0m 5. Add the following correction to the power input for the different outdoor units (PI corr1)
Outdoor model RP71 RP100
Caution: TC and SHC are shown by kW
Power supply W1 0 0
V1 0.2 0.3
T1 0 0
6. Add the following correction to the power input for each connected indoor unit (PI corr2)
Indoor model 35 45 60 71
FHYBP 0.12 0.16 0.21 0.21
FHYP 0.14 0.14 0.14 0.14
FHYCP 0.14 0.14 0.16 0.16
Indoor types FHYKP 0.046 0.069 0.12 0.12
FAYP
FUYP
0.069
0.16
FDYMP 0.12 0.16 0.21 0.21
7. For RP125 twin and triple combination, add the following correction to the total capacity for the following connected indoor units (TC corr 1).
Indoor model 35 45 60 71
• Split - Sky Air • Outdoor Units
FHYKP 0.08 0.11 0.14 0.17
Indoor types FAYP 0.08 0.11 0.14 0.17
FUYP 0.08 0.11 0.14 0.17
9
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
4
1 4
Capacity tables
Simultaneous operation RP200-250B7W1 Cooling capacity
Outdoor
RP200
RP250
EWB (°C) 12.0 14.0 16.0 18.0 19.0 22.0 24.0 12.0 14.0 16.0 18.0 19.0 22.0 24.0
W1: 400V [50Hz]
Indoor
EDB (°C) 18.0 20.0 22.0 25.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 30.0 32.0
TC 17.9 19.2 20.5 21.8 22.5 24.7 26.3 22.4 24.0 25.6 27.2 28.1 30.9 32.8
20
PI o 5.39 5.50 5.61 5.72 5.72 5.93 6.04 6.74 6.85 6.97 7.08 7.20 7.43 7.54
TC 17.2 18.4 19.7 20.9 21.6 23.8 25.2 21.5 23.0 24.6 26.2 27.0 29.7 31.6
25
PI o 5.82 5.93 6.04 6.15 6.26 6.47 6.58 7.43 7.54 7.66 7.77 7.89 8.12 8.23
TC 16.2 17.3 18.6 19.8 20.5 22.6 24.0 20.2 21.7 23.2 24.8 25.6 28.2 30.0
Outdoor temperature (°CDB) 32 35 PI o TC 6.69 15.8 6.80 16.9 6.90 18.2 7.01 19.4 7.12 20.0 7.33 22.1 8.46 23.5 8.46 19.7 8.58 21.2 8.69 22.7 8.92 24.2 8.92 25.0 9.27 27.6 9.38 29.4
PI o 7.12 7.23 7.33 7.44 7.56 7.77 7.98 8.92 9.04 9.27 9.38 9.50 9.85 9.96
TC 15.2 16.3 17.4 18.7 19.3 21.2 22.7 18.9 20.3 21.8 23.3 24.1 26.5 28.3
40
PI o 7.87 7.98 8.09 8.31 8.31 8.63 8.74 9.96 10.08 10.19 10.42 10.54 10.77 11.00
TC 14.5 15.5 16.6 17.8 18.4 20.3 21.6 18.0 19.4 20.8 22.3 23.0 25.4 27.1
46
PI o 8.95 9.06 9.17 9.38 9.49 9.71 9.92 11.23 11.46 11.57 11.80 11.92 12.26 12.49
3TW23612-2B
SYMBOLS EWB: EDB: TC: PI o: PI corr: PI:
NOTES
Entering wet bulb temp. Entering dry bulb temp. Total capacity cooling Power input of outdoor unit Correction factor for Pi depending used indoor units Total power input PI = PI o + ∑PI corr e.g. RYP200B7W1 + FHYP100 + FHYCP100 PI = 7.43 + 0.16 + 0.2 = 7.79 kW
(°CWB) (°CDB) (kW) (kW) (kW) (kW)
Indoor model
Caution: TC and SHC are shown by kW
5
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal capacities 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0m 5. Add the following correction to the power input for the different outdoor units (PI corr1)
35 45 60 71 100 125
FHYBP 0.13 0.14 0.17 0.18 0.22 0.29
FHYP 0.09 0.09 0.1 0.1 0.16 0.18
FHYCP 0.14 0.14 0.16 0.16 0.2 0.24
Indoor types FHYKP 0.08 0.08 0.105 0.105
FAYP
0.05 0.06
Dimensional drawings See chapter RP-L7/B7 for the dimensional drawings of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1
6
Operation range See chapter RP-L7/B7 for the operation range of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1
10
• Split - Sky Air • Outdoor Units
FDYP
FUYP
0.7
0.14 0.23 0.23
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
7
Piping diagrams See chapter RP-L7/B7 for the piping diagrams of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1
1 7
Twin application RP71-125L7 Indoor heat exchanger
Solenoid valve
Electronic expansion valve
Strainer
Filter
Receiver
Heat exchanger
Fan
Field piping Field piping Indoor unit Indoor heat exchanger
Filter
Low pressure switch
High pressure switch
Field piping JA C12207-0
Service port 1/4″
branch pipe (option)
Field piping JB Compressor
C1220T-0 Fan
Outdoor unit Field piping Field piping
A 9.5 9.5
Stop valve (with service port 1/4’’ flare)
Indoor unit
B 15.9 19.1
Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.
Model RP71 RP100,125
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
3TW25175-2
Triple application RP100-125L7 Indoor heat exchanger
Indoor unit
Solenoid valve
Fan
Strainer
Electronic expansion valve
Field piping
Filter
Receiver
Heat exchanger
Field piping
Indoor heat exchanger
Indoor unit
Field piping J9.5
Filter
C12207-0
Fan
Low pressure switch
High pressure switch
Field piping Field piping
Indoor heat exchanger
Indoor unit
Service port 1/4″
Field piping J19.1 C1220T-0
branch pipe
Compressor
(option) Stop valve (with service port 1/4’’ flare)
Fan
Field piping
Outdoor unit
Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.
Field piping
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
• Split - Sky Air • Outdoor Units
3TW25175-3
11
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
7
1 7
Piping diagrams See chapter RP-L7/B7 for the piping diagrams of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1
Twin application RP200-250B7W1 Indoor heat exchanger
Outdoor heat exchanger Solenoid valve Receiver
Propeller fan Electronic expansion valve
Filter
Fan
Field piping Field piping
Indoor unit
Service port 1/4’’ flare
Field piping JA Filter
Indoor heat exchanger branch pipe (option)
Low pressure switch
Field piping JB
High pressure switch
Stop valve (with service port 1/4’’ flare)
Compressor
Fan
Outdoor unit
A 12.7 15.9
Field piping Field piping
B 28.6 28.6
Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.
Model RP200 RP250
Indoor unit
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
Triple application RP200-250B7W1 Indoor heat exchanger
3TW23615-2
Indoor unit Outdoor heat exchanger Solenoid valve Receiver
Fan
Field piping
Propeller fan Electronic expansion valve
Field piping
Indoor heat exchanger
Indoor unit
Service port 1/4’’ flare
Field piping JA Fan
Filter Low pressure switch
Field piping Field piping
Indoor heat exchanger
Filter
High pressure switch
Field piping JB
Indoor unit branch pipe (option)
Compressor
Outdoor unit
Stop valve (with service port 1/4’’ flare) Fan
Field piping Field piping
A 12.7 15.9
B 28.6 28.6
Model RP200 RP250
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
12
• Split - Sky Air • Outdoor Units
Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.
3TW23615-3
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
7
Piping diagrams See chapter RP-L7/B7 for the piping diagrams of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1
Double twin application RP200-250B7W1
Indoor heat exchanger
1 7
Indoor unit
Outdoor heat exchanger Solenoid valve Field piping JC Fan
Receiver
Field piping JA Indoor heat exchanger
Propeller fan
Indoor unit
Electronic expansion valve
Field piping J9.5
Filter
Field piping J19.1 Field piping JC Fan
Field piping JA Indoor heat exchanger
Indoor unit
Field piping JA
Service port 1/4’’ flare
Filter
branch pipe (option)
Low pressure switch
Field piping JB
High pressure switch
Field piping JC Fan
Stop valve (with service port 1/4’’ flare)
Field piping JA
Indoor heat exchanger
Indoor unit Field piping J9.5
Field piping J19.1
Compressor
Outdoor unit
A 12.7 15.9
B 28.6 28.6
C 6.4 9.5
Model RP200 RP250
Field piping JC Fan
Field piping JA
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
• Split - Sky Air • Outdoor Units
3TW23615-4
13
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
8
1 8
Wiring diagrams See chapter RP-L7/B7 for the wiring diagrams of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1
9
Sound level See chapter RP-L7/B7 for the sound levels ofRP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1
10
Accessories See chapter RP-L7/B7 for the accessories of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1
11
Center of gravity See chapter RP-L7/B7 for the centre of gravity of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1
12
Safety device settings See chapter RP-L7/B7 for the safety device setting of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1
14
• Split - Sky Air • Outdoor Units
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
13
Installation
RP71-125L7/B7
1
(B) In case obstacles exist only in front of outlet side
The numerical figures used here represent the dimensions for the models RP71 to 125. The figures inside ( ) indicate the dimensions for the models RP100 and 125. (Unit:mm) The figures inside < > indicate the dimension of discharge grille when it is installed facing downward When installing multiple units in lateral connection, discharge grille cannot be set to discharge air in Left/Right direction
(A) In case obstacles exist in front of the air inlet
13
+ Where there are no obstacles above the unit. 1
Installation of single unit + In case obstacles exist only in front of outlet side.
2
Installation of multiple units in lateral connection (2 units or more).
150 or more 20 mm or more 20 mm or more
+ Where there are no obstacles above the unit 1
Installation of single unit + In case obstacles exist only in front of the air inlet. + In case obstacles exist in front of the air inlet and on both sides of the unit.
50 or more (100)
1000 mm or more
+ Where there are obstacles above the unit.
100 or more
2 Installation of multiple units in lateral connection (2 units or more).
1
Installation of single unit + In case obstacles exist only in front of outlet side.
2
Installation of multiple units in lateral connection (2 units or more).
100 or more
100 or more
100 or more
500 or less
20 mm or more 20 mm or more
+ In case obstacles exist in front of the air inlet and on both sides of the unit.
1000 mm or more
500 mm or more
500 or less 200 or more (300)
20 mm or more
1000 mm or more
20 mm or more
+ Where there are obstacles above the unit.
+ In case obstacles exist only in front of outlet side.
1000 mm or more
1
500 or less
Installation of single unit + In case obstacles exist only in front of the air inlet.
20 mm or more
100 or more 500 or less 1000 mm or more
+ In case obstacles exist in front of the air inlet and on both sides of the unit.
1000 mm or more
(C) In case obstacles exist in front of both the air inlet and outlet sides.
Pattern 1 150 or more
150 or more
150 or more
+ Where there are no obstacles above the unit.
500 or less 20 mm or more
1000 mm or more
2 Installation of multiple units in lateral connection (2 units or more).
1
2
1000 mm or more
+ In case obstacles exist in front of the air inlet and on both sides of the unit.
20 mm or more 200 or more (300) 200 mm or more
Where obstacle in front of the air outlet is higher than the unit.
Installation of single unit. Installation of multiple units in lateral connection (2 units or more).
50 or more (100) 500 or more (1000)
20 mm or more 20 mm or more
200 or more (300) 1000 or more (1500)
DU427-826
• Split - Sky Air • Outdoor Units
15
• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1
13
1
13
Installation
RP71-125L7/B7
2 500 or less
Installation of single unit.
Relation of dimensions of H, A, and L are shown in the table below. L≤H H