RP-L7/B7 Twin/Triple/ Double Twin Application

Split Sky Air

air conditioning systems

technical data

Split - Sky Air

ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment

Daikin units comply with the European regulations that guarantee the safety of the product.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.

Zandvoordestraat 300 B - 8400 Ostend Belgium Internet: http://www.daikineurope.com

EEDE05-1/2 • 05/2005 Prepared in Belgium by Goekint Graphics

Specifications are subject to change without prior notice.

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

TABLE OF CONTENTS RP-L7/B7 1

Features

2

Specifications

.................................................................................

.......................................................................

2 3

Technical specifications Electrical specifications

3

Combination table

.............................................................

6

4

Capacity tables

...................................................................

8

5

Dimensional drawings

6

.....................................................

10

Operation range

.................................................................

10

7

Piping diagrams

..................................................................

11

8

Wiring diagrams

.................................................................

14

9

Sound level

..........................................................................

14

Sound level data Sound pressure spectrum

10

Accessories

..........................................................................

14

Standard accessories Optional accessories

11

Center of gravity

12

Safety device settings

13

Installation

• Split - Sky Air • Outdoor Units

................................................................

14

......................................................

14

............................................................................

15

1

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

1

1 1

2

Features

Outdoor units for twin/triple/double twin application. + It is possible to connect 2, 3 or 4 indoor units to one single outdoor unit. The indoor units may be of different types (e.g. ceiling mounted cassette, wall mounted,...) and even different capacities (e.g. 45 and 60 class). All indoor units are operated together within the same mode (cooling or heating) from one remote control. This allows an equal air distribution in larger rooms, even if they are irregularly shaped. + Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall. + They are fitted with a scroll compressor, renowned for low noise and high energy efficiency.

• Split - Sky Air • Outdoor Units

+ The piping connections can be accessed from underneath, front, side or rear. + The service valves are hidden inside the casing. + A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions.

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

2

Specifications

1 2

TECHNICAL SPECIFICATIONS OUTDOOR UNITS DIMENSIONS

WEIGHT MATERIAL COLOUR SOUND LEVEL FAN

HEAT EXCHANGER

REFRIGERANT CIRCUIT

COMPRESSOR

PIPING CONNECTIONS

INSULATION MATERIAL

Unit

Unit Unit Sound pressure (1) Sound power (2) Air flow rate Speed Qty x model Qty x motor output Type

mm mm mm kg

high high high steps high

dB(A) dB(A) m3/min

50 63 48

rpm

-

W mm m2

1 x 65 Hi-XSS cooling tube, non sym. waffle fin 2 x 34 x 2.0 0.634

1 x 80 Non symm. waffle louvre, Hi-XA U-cooling tube 2 x 38 x 2.0 0.719

kg m

2.8 5 / 70

3.1 - / 70

m

30 Expansion valve (electronic type)

30 -

Type Qty x model

Heat insulation Safety devices

RP71B7/T1 RP100L7V1/W1 860 1,170 880 900 320 320 88/85/85 100/99 Painted galvanised steel plate Ivory white 50 53 63 66 51 55 3 steps -

H W D

Rows x stages x fin pitch Face area Refrigerant type Refrigerant charge Minimum/maximum allowable distance between indoor and outdoor Maximum allowable level difference Refrigerant control

Motor output x no Oil type Oil charge volume

RP71L7V1/W1 770 900 320 79/78

W

liquid gas drain

! mm mm mm

1xP47L11S

RP100B7V1/T1 1,215 880 320 103/98/98

53 66 94

2xP47L11S

1 x 55 Hi-XSS cooling tube, non sym. waffle fin 2 x 52 x 2.0 0.983 R-407C 3.7 5 / 70

-

1 x (80 + 85) Non symm. waffle louvre, Hi-XA U-cooling tube 2 x 54 x 2.0 1.022 3.6 - / 70

30 30 Expansion valve (electronic type) Hermetically sealed scroll type 1 x JT90FA-V1N 1 x JT90FA-V1N/ 1 x JT125FA-V1N 1 x JT125FA-V1N/ 1 x JT90FA-YE/ 1 x JT125FA-YE/ 1 x JT90FA-T1 1 x JT125FA-T1 2,200 x 1 3,750 x 1 DAPHNE FVC68D 1.2 1.2 1.5 1.5 φ9.5 φ15.9 φ19.1 φ26 x 3 Both liquid and gas pipes High and low pressure switch, thermal protector for indoor and outdoor fan motor, overcurrent relay (compressor), reverse phase protector, fuse 3TW25161-1B 3TW25211-1B 3TW25171-1A 3TW25221-1A 3TW25231-1A

• Split - Sky Air • Outdoor Units

3

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

2

Specifications

1 2

TECHNICAL SPECIFICATIONS OUTDOOR UNITS DIMENSIONS

WEIGHT MATERIAL COLOUR SOUND LEVEL FAN

HEAT EXCHANGER

REFRIGERANT CIRCUIT

COMPRESSOR

PIPING CONNECTIONS

INSULATION MATERIAL SAFETY DEVICE SETTINGS

Unit

Unit Unit Sound pressure (1) Sound power (2) Air flow rate Speed Qty x model Qty x motor output Type

H W D

mm mm mm kg

high

dB(A) dB(A) m3/min

high steps

W

Rows x stages x fin pitch Face area Refrigerant type Refrigerant charge Minimum/maximum allowable distance between indoor and outdoor Maximum allowable level difference Additional refrigerant charge

mm m2

m g/m

Heat insulation

rpm

liquid gas drain

53 67 89

3 steps 2 x P47L11S 85 + 65 Hi-XSS cooling tube, non sym. waffle fin 2 x 52 x 2.0 0.983

kg m

Type Qty x model Speed Oil type Oil charge volume Crankcase heater

RP125L7W1 1,170 900 320 104

! W mm mm mm

3.7 5 / 70

RP125B7T1 RP200B7W1 1,215 1,220 880 1,290 320 700 100 194 Painted galvanised steel plate Ivory white 53 56 67 77 94 170 2 x P47L11S 1 x (80+85) 2 x 54 x 2.0 1.022 3.9 - / 70

RP250B7W1 1,440 1,290 700 206

56 77 175

1 step 1 x P55J11F 1 x P55J11F 1 x (230+190) 1 x (230+140) Non symm. waffle louvre, Hi-XA U-cooling tube

R-407C

2 x 40 x 2 1.57

2 x 50 x 2 1.97

7.5 - / 50

9.2 - / 50

30 30 Please refer to item 13 ’Installation’ of this chapter

30 30 60 g/m for total piping length 90 g/m for total piping length >30m >30m Hermetically sealed scroll type 1xJT160FA-YE/ 1xJT236DA-YE@2 1xJT300DA-YE@2 1 x JT160FA-YE 1xJT160FA-T1 3,750 x 1 − 2900 2900 DAPHNE FVC68D 1.5 1.5 4 4 50 72 φ9.5 φ12.7 x 0.90 φ15.9 x 0.45 φ19.1 φ28.6 x 1.15 φ28.6 x 1.15 φ26 x 3 φ26 x 6 φ26 x 6 Both liquid and gas pipes High and low pressure switch, thermal protection for indoor and outdoor fan motor, fuse, overcurrent relay (compressor), reserve phase protection, compr. Thermal protection 3TW23281-1 3TW23291-1 3TW23301-1 3TW23331-1 3TW23341-1 3TW23351-1 3TW23381-1 3TW23391-1 3TW23611-1A 3TW23621-1A

4

• Split - Sky Air • Outdoor Units

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

2

Specifications

1 2

ELECTRICAL SPECIFICATIONS OUTDOOR UNITS CURRENT

POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM VOLTAGE

Nominal running current Maximum running current Starting current Phase Frequency Voltage

cooling/heating A cooling/heating A cooling/heating A

RP71L7V1/W1

Hz V

ELECTRICAL SPECIFICATIONS OUTDOOR UNITS CURRENT

POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM VOLTAGE

Nominal running current Max. running current Starting current Phase Frequency Voltage

cooling/heating A cooling/heating A cooling/heating A

Hz V

V1/W1 1∼/3N∼ 50 230 / 400

RP71B7T1 RP100L7V1/W1 Please refer to electrical data Please refer to electrical data Please refer to electrical data T1 V1/W1 3∼ 1∼/3N∼ 50 50 230 230 / 400

RP125L7W1 RP125B7T1 RP200B7W1 Please refer to electrical data 14.4 Please refer to electrical data 17.9 Please refer to electrical data W1 T1 W1 3N∼ 3∼ 3N∼ 50 50 50 400 230 400

RP100B7T1

T1 3∼ 50 230

RP250B7W1 17.2 27.5 W1 3N∼ 50 400

NOTES 1

The sound pressure level is measured via a microphone at 1m distance from the unit. It is a relative value, depending on the distance and acoustic environment. For measuring conditions: please refer to item 9 of this chapter.

2

The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.

ELECTRICAL DATA

See chapter RP-L7/B7 for the electrical data of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1

• Split - Sky Air • Outdoor Units

5

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

3

1 3

Combination table

Possible combinations for twin and triple application RP71-125L7 Possible indoor combination Simultaneous operation Twin

Triple Out

Out

Outdoor models In

In

RP71L7V1/W1 RP71B7T1

35-35 (KHRQ22M20T7)

RP100L7V1/W1 RP100B7T1

45-45 (KHRQ22M20T7)

45-60 (KHRQ22M20T7)

RP125L7W1 RP125B7T1

60-60 (KHRQ22M20T7)

45-71 (KHRQ22M20T7)

In

35-71 (KHRQ22M20T7)

In

In

35-35-35 (KHRP127HB7) 45-45-45 (KHRP127HB7) 3TW25149-3A

NOTES

6

1

Possible indoor units: FHYCP35-71, FUYP71, FHYKP35-71, FAYP71, FHYP35-71, FHYBP35-71, FDYMP71

2

Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).

3

When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. In note 1 are the indoor units mentioned in order of the possible function (most functions are on FHYCP, less functions are on FDYMP).

4

Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.

5

For unit specification of the outdoor units and the indoor units refer to the unit specifications mentioned for pair systems.

6

Nominal cooling capacities are based on the following conditions: Indoor air temperature: 27°CDB, 19.0°CWB, outdoor temperature 35°CDB. Nominal heating capacities are based on the following conditions: Indoor air temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB.

• Split - Sky Air • Outdoor Units

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

3

Combination table

1

Possible combinations and standard capacity for twin, triple and double twin application

3

RP200-250B7 Possible indoor combination Simultaneous operation Capacity [kW] Outdoor models

Cooling In

RP200B7W1

20.0

RP250B7W1

25.0

Twin

Triple

Double twin

Out

Out

Out

In

In

In

In

In

100-100 71-125 71-71-71 60-60-60 45-71-71 45-45-100 35-71-100 35-35-125 45-60-100 71-60-60 (KHRQ22M64T7) (KHRQ22M64T7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7)

125-125 (KHRQ22M64T7)

45-100-100 (KHRP127HB7)

60-60-125 (KHRP127HB7)

125-45-71 (KHRP127HB7)

100-71-71 (KHRP127HB7)

In

In

In

45-45-45-45 (2 x KHRQ22M20T7 + KHRQ22M64T7) 60-60-60-60 (2 x KHRQ22M20T7 + KHRQ22M64T7) 3TW23619-1A

NOTES 1

Possible indoor units: FHYCP35-125, FUYP71-125, FHYKP35-71, FAYP71-100, FHYP35-60, FHYP71-125, FHYBP35-125, FDYP125.

2

Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).

3

When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. Note 1 mentions the indoor units in order of the possible function (most functions are on FHYCP, less functions are on FDYP).

4

Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.

5

For unit specification of the outdoor units and the indoor units refer to the unit specifications mentioned for pair systems.

6

Nominal cooling capacities are based on the following conditions:Indoor air temperature: 27°CDB, 19.0°CWB, outdoor temperature 35°CDB. Nominal heating capacities are based on the following conditions:Indoor air temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB.

• Split - Sky Air • Outdoor Units

7

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

4

1 4

Capacity tables

Simultaneous operation RP71-100-125L7V1/W1 Cooling capacity

Outdoor

RP71

RP100

RP125

EWB (°C) 12.0 14.0 16.0 18.0 19.0 19.5 22.0 24.0 12.0 14.0 16.0 18.0 19.0 19.5 22.0 24.0 12.0 14.0 16.0 18.0 19.0 19.5 22.0 24.0

V1: 230V [50Hz] W1: 400V [50Hz]

Indoor

EDB (°C) 18.0 20.0 22.0 25.0 27.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 27.0 30.0 32.0

TC 6.2 6.6 7.2 7.7 8.0 8.0 8.7 9.4 8.4 8.9 10.1 10.8 11.1 11.2 12.2 13.0 11.1 11.8 12.7 13.3 13.6 13.8 15.1 15.9

20

PI 1.75 1.83 1.83 1.92 1.92 1.92 2.00 2.00 2.61 2.71 2.71 2.71 2.71 2.71 2.81 2.90 3.24 3.33 3.33 3.43 3.52 3.52 3,62 3.62

TC 6.1 6.5 7.0 7.5 7.7 7.9 8.5 9.1 8.3 8.8 9.8 10.5 10.8 11.0 11.8 12.7 10.8 11.4 12.1 13.0 13.3 13.5 14.6 15.5

25

PI 2.00 2.08 2.08 2.08 2.08 2.08 2.17 2.17 2.81 2.81 2.90 2.90 3.00 3.00 3.00 3.10 3.52 3.52 3.62 3.62 3.71 3.71 3.71 3.81

TC 5.7 6.0 6.5 7.2 7.3 7.4 8.0 8.6 8.1 8.7 9.1 9.8 10.1 10.3 11.2 11.9 10.0 10.7 11.4 12.1 12.7 12.8 13.7 14.6

Outdoor temperature (°CDB) 32 35 PI TC 2.17 5.5 2.25 5.9 2.25 6.3 2.33 6.8 2.33 7.1 2.33 7.2 2.42 7.9 2.50 8.4 3.19 7.8 3.19 8.4 3.29 8.9 3.29 9.6 3.39 10.0 3.39 10.1 3.48 11.0 3.58 11.6 3.81 9.7 3.90 10.4 3.90 11.1 4.00 11.8 4.09 12.2 4.09 12.4 4.19 13.4 4.28 14.3

PI 2.33 2.33 2.42 2.50 2.50 2.50 2.58 2.58 3.39 3.39 3.48 3.48 3.58 3.58 3.68 3.77 4.09 4.19 4.28 4.38 4.38 4.38 4.48 4.57

TC 5.3 5.5 6.0 6.4 6.6 6.7 7.4 8.0 7.5 7.8 8.5 9.0 9.4 9.5 10.4 11.1 9.2 9.8 10.4 11.2 11.5 11.7 12.9 13.6

40

PI 2.58 2.58 2.67 2.67 2.75 2.75 2.75 2.83 3.77 3.77 3.87 3.87 3.97 3.97 4.06 4.16 4.48 4.57 4.67 4.76 4.86 4.86 4.95 5.05

46

TC 4.9 5.3 5.5 6.0 6.2 6.3 6.8 7.4 6.9 7.5 7.8 8.4 8.7 8.8 9.6 10.3 8.6 9.2 9.7 10.4 10.8 11.0 12.0 12.9

PI 2.83 2.83 2.92 3.00 3.00 3.00 3.08 3.17 4.16 4.16 4.26 4.35 4.45 4.45 4.45 4.55 5.14 5.14 5.24 5.24 5.33 5.33 5.52 5.62

3TW25142-15

SYMBOLS

NOTES

EWB: EDB: TC: PI o: PI corr1:

Entering wet bulb temp. (°CWB) Entering dry bulb temp. (°CDB) Total capacity cooling (kW) Power input of outdoor unit (kW) Correction factor for Pi depending on voltage of outdoor (kW) PI corr2: Correction factor for Pi depending used indoor units (kW) PI: Total power input (kW) PI = PI o + PI corr1 + ∑ PI corr2 e.g. RYP100L7V1 + FHYBP71B7V1 + FHYP35B7V1 PI = 3.5 + 0.23 + 0.21 + 0.14 = 4.08 kW

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal capacities 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0m 5. Add the following correction to the power input for the different outdoor units (PI corr1)

Outdoor model RP71 RP100

Caution: TC and SHC are shown by kW

V1 0.06 0.23

Power supply W1 0 0

T1 0 0

6. Add the following correction to the power input for each connected indoor unit (PI corr2)

Indoor model 35 45 60 71

FHYBP 0.12 0.16 0.21 0.21

FH(Y)P 0.14 0.14 0.14 0.14

FHYCP 0.14 0.14 0.16 0.16

Indoor types FHYKP 0.046 0.069 0.12 0.12

FAYP

FUYP

0.069

0.16

FDYMP 0.12 0.16 0.21 0.21

NOTE: The total capacity does not change with different combination of indoor units.

8

• Split - Sky Air • Outdoor Units

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

4

Capacity tables

1

Simultaneous operation RP71-125B7T1 Cooling capacity

Outdoor

RP71

RP100

RP125

EWB (°C) 12.0 14.0 16.0 18.0 19.0 22.0 24.0 12.0 14.0 16.0 18.0 19.0 22.0 24.0 12.0 14.0 16.0 18.0 19.0 22.0 24.0

4

W1: 400V [50Hz]

Indoor

EDB (°C) 18.0 20.0 22.0 25.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 30.0 32.0

TC 6.2 6.6 7.2 7.7 7.9 8.7 9.4 8.4 8.9 10.1 10.8 11.1 12.2 13.0 11.0 11.8 12.7 13.4 13.7 15.1 15.9

20

PI o 1.7 1.8 1.8 1.8 1.8 1.9 1.9 2.3 2.4 2.4 2.5 2.5 2.6 2.7 3.3 3.3 3.3 3.4 3.5 3.6 3.7

TC 6.1 6.5 7.0 7.5 7.7 8.5 9.2 8.3 8.8 9.8 10.5 10.8 11.8 12.7 10.7 11.4 12.1 13.0 13.4 14.6 15.5

25

PI o 1.9 2.0 2.0 2.0 2.0 2.1 2.1 2.6 2.6 2.7 2.7 2.8 2.8 2.9 3.5 3.5 3.6 3.7 3.8 3.8 3.9

TC 5.7 6.0 6.5 7.2 7.3 8.0 8.6 8.1 8.7 9.1 9.8 10.1 11.2 11.9 10.0 10.7 11.4 12.1 12.7 13.8 14.6

Outdoor temperature (°CDB) 32 35 PI o TC 2.1 5.5 2.2 5.9 2.2 6.4 2.3 6.8 2.3 7.1 2.4 7.8 2.4 8.4 3.0 7.8 3.0 8.4 3.1 8.9 3.1 9.6 3.2 10.0 3.3 11.0 3.4 11.6 3.9 9.7 4.0 10.4 4.0 11.0 4.1 11.8 4.2 12.2 4.3 13.5 4.4 14.3

PI o 2.3 2.3 2.4 2.4 2.4 2.5 2.5 3.2 3.2 3.3 3.3 3.4 3.4 3.5 4.2 4.3 4.4 4.5 4.5 4.6 4.7

TC 5.2 5.5 6.0 6.4 6.6 7.4 7.9 7.5 7.8 8.5 9.0 9.4 3.7 11.1 9.2 9.8 10.4 11.1 11.5 12.9 13.7

40

PI o 2.5 2.5 2.6 2.6 2.7 2.7 2.8 3.5 3.5 3.6 3.6 3.6 9.6 3.8 4.6 4.7 4.8 4.9 5.0 5.1 5.2

46

TC 4.9 5.2 5.5 6.0 6.2 6.8 7.4 6.9 7.5 7.8 8.4 8.7 4.2 10.3 8.6 9.2 9.7 10.4 10.7 12.0 12.9

PI o 2.8 2.8 2.9 3.0 3.0 3.0 3.1 3.8 3.8 3.9 4.0 4.1 3.0 4.3 5.3 5.4 5.4 5.4 5.5 5.6 5.7

3TW23282-8A

SYMBOLS

NOTES

EWB: EDB: TC: PI o: PI corr1:

Entering wet bulb temp. (°CWB) Entering dry bulb temp. (°CDB) Total capacity cooling (kW) Power input of outdoor unit (kW) Correction factor for Pi depending on voltage of outdoor (kW) PI corr2: Correction factor for Pi depending used indoor units (kW) PI: Total power input (kW) PI = PI o + PI corr1 + ∑ PI corr2 e.g. RYP100L7V1 + FHYBP71B7V1 + FHYP35B7V1 PI = 3.5 + 0.23 + 0.21 + 0.14 = 4.08 kW

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal capacities 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0m 5. Add the following correction to the power input for the different outdoor units (PI corr1)

Outdoor model RP71 RP100

Caution: TC and SHC are shown by kW

Power supply W1 0 0

V1 0.2 0.3

T1 0 0

6. Add the following correction to the power input for each connected indoor unit (PI corr2)

Indoor model 35 45 60 71

FHYBP 0.12 0.16 0.21 0.21

FHYP 0.14 0.14 0.14 0.14

FHYCP 0.14 0.14 0.16 0.16

Indoor types FHYKP 0.046 0.069 0.12 0.12

FAYP

FUYP

0.069

0.16

FDYMP 0.12 0.16 0.21 0.21

7. For RP125 twin and triple combination, add the following correction to the total capacity for the following connected indoor units (TC corr 1).

Indoor model 35 45 60 71

• Split - Sky Air • Outdoor Units

FHYKP 0.08 0.11 0.14 0.17

Indoor types FAYP 0.08 0.11 0.14 0.17

FUYP 0.08 0.11 0.14 0.17

9

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

4

1 4

Capacity tables

Simultaneous operation RP200-250B7W1 Cooling capacity

Outdoor

RP200

RP250

EWB (°C) 12.0 14.0 16.0 18.0 19.0 22.0 24.0 12.0 14.0 16.0 18.0 19.0 22.0 24.0

W1: 400V [50Hz]

Indoor

EDB (°C) 18.0 20.0 22.0 25.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 30.0 32.0

TC 17.9 19.2 20.5 21.8 22.5 24.7 26.3 22.4 24.0 25.6 27.2 28.1 30.9 32.8

20

PI o 5.39 5.50 5.61 5.72 5.72 5.93 6.04 6.74 6.85 6.97 7.08 7.20 7.43 7.54

TC 17.2 18.4 19.7 20.9 21.6 23.8 25.2 21.5 23.0 24.6 26.2 27.0 29.7 31.6

25

PI o 5.82 5.93 6.04 6.15 6.26 6.47 6.58 7.43 7.54 7.66 7.77 7.89 8.12 8.23

TC 16.2 17.3 18.6 19.8 20.5 22.6 24.0 20.2 21.7 23.2 24.8 25.6 28.2 30.0

Outdoor temperature (°CDB) 32 35 PI o TC 6.69 15.8 6.80 16.9 6.90 18.2 7.01 19.4 7.12 20.0 7.33 22.1 8.46 23.5 8.46 19.7 8.58 21.2 8.69 22.7 8.92 24.2 8.92 25.0 9.27 27.6 9.38 29.4

PI o 7.12 7.23 7.33 7.44 7.56 7.77 7.98 8.92 9.04 9.27 9.38 9.50 9.85 9.96

TC 15.2 16.3 17.4 18.7 19.3 21.2 22.7 18.9 20.3 21.8 23.3 24.1 26.5 28.3

40

PI o 7.87 7.98 8.09 8.31 8.31 8.63 8.74 9.96 10.08 10.19 10.42 10.54 10.77 11.00

TC 14.5 15.5 16.6 17.8 18.4 20.3 21.6 18.0 19.4 20.8 22.3 23.0 25.4 27.1

46

PI o 8.95 9.06 9.17 9.38 9.49 9.71 9.92 11.23 11.46 11.57 11.80 11.92 12.26 12.49

3TW23612-2B

SYMBOLS EWB: EDB: TC: PI o: PI corr: PI:

NOTES

Entering wet bulb temp. Entering dry bulb temp. Total capacity cooling Power input of outdoor unit Correction factor for Pi depending used indoor units Total power input PI = PI o + ∑PI corr e.g. RYP200B7W1 + FHYP100 + FHYCP100 PI = 7.43 + 0.16 + 0.2 = 7.79 kW

(°CWB) (°CDB) (kW) (kW) (kW) (kW)

Indoor model

Caution: TC and SHC are shown by kW

5

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal capacities 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0m 5. Add the following correction to the power input for the different outdoor units (PI corr1)

35 45 60 71 100 125

FHYBP 0.13 0.14 0.17 0.18 0.22 0.29

FHYP 0.09 0.09 0.1 0.1 0.16 0.18

FHYCP 0.14 0.14 0.16 0.16 0.2 0.24

Indoor types FHYKP 0.08 0.08 0.105 0.105

FAYP

0.05 0.06

Dimensional drawings See chapter RP-L7/B7 for the dimensional drawings of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1

6

Operation range See chapter RP-L7/B7 for the operation range of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1

10

• Split - Sky Air • Outdoor Units

FDYP

FUYP

0.7

0.14 0.23 0.23

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

7

Piping diagrams See chapter RP-L7/B7 for the piping diagrams of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1

1 7

Twin application RP71-125L7 Indoor heat exchanger

Solenoid valve

Electronic expansion valve

Strainer

Filter

Receiver

Heat exchanger

Fan

Field piping Field piping Indoor unit Indoor heat exchanger

Filter

Low pressure switch

High pressure switch

Field piping JA C12207-0

Service port 1/4″

branch pipe (option)

Field piping JB Compressor

C1220T-0 Fan

Outdoor unit Field piping Field piping

A 9.5 9.5

Stop valve (with service port 1/4’’ flare)

Indoor unit

B 15.9 19.1

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

Model RP71 RP100,125

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

3TW25175-2

Triple application RP100-125L7 Indoor heat exchanger

Indoor unit

Solenoid valve

Fan

Strainer

Electronic expansion valve

Field piping

Filter

Receiver

Heat exchanger

Field piping

Indoor heat exchanger

Indoor unit

Field piping J9.5

Filter

C12207-0

Fan

Low pressure switch

High pressure switch

Field piping Field piping

Indoor heat exchanger

Indoor unit

Service port 1/4″

Field piping J19.1 C1220T-0

branch pipe

Compressor

(option) Stop valve (with service port 1/4’’ flare)

Fan

Field piping

Outdoor unit

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

Field piping

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

• Split - Sky Air • Outdoor Units

3TW25175-3

11

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

7

1 7

Piping diagrams See chapter RP-L7/B7 for the piping diagrams of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1

Twin application RP200-250B7W1 Indoor heat exchanger

Outdoor heat exchanger Solenoid valve Receiver

Propeller fan Electronic expansion valve

Filter

Fan

Field piping Field piping

Indoor unit

Service port 1/4’’ flare

Field piping JA Filter

Indoor heat exchanger branch pipe (option)

Low pressure switch

Field piping JB

High pressure switch

Stop valve (with service port 1/4’’ flare)

Compressor

Fan

Outdoor unit

A 12.7 15.9

Field piping Field piping

B 28.6 28.6

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

Model RP200 RP250

Indoor unit

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

Triple application RP200-250B7W1 Indoor heat exchanger

3TW23615-2

Indoor unit Outdoor heat exchanger Solenoid valve Receiver

Fan

Field piping

Propeller fan Electronic expansion valve

Field piping

Indoor heat exchanger

Indoor unit

Service port 1/4’’ flare

Field piping JA Fan

Filter Low pressure switch

Field piping Field piping

Indoor heat exchanger

Filter

High pressure switch

Field piping JB

Indoor unit branch pipe (option)

Compressor

Outdoor unit

Stop valve (with service port 1/4’’ flare) Fan

Field piping Field piping

A 12.7 15.9

B 28.6 28.6

Model RP200 RP250

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

12

• Split - Sky Air • Outdoor Units

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

3TW23615-3

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

7

Piping diagrams See chapter RP-L7/B7 for the piping diagrams of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1

Double twin application RP200-250B7W1

Indoor heat exchanger

1 7

Indoor unit

Outdoor heat exchanger Solenoid valve Field piping JC Fan

Receiver

Field piping JA Indoor heat exchanger

Propeller fan

Indoor unit

Electronic expansion valve

Field piping J9.5

Filter

Field piping J19.1 Field piping JC Fan

Field piping JA Indoor heat exchanger

Indoor unit

Field piping JA

Service port 1/4’’ flare

Filter

branch pipe (option)

Low pressure switch

Field piping JB

High pressure switch

Field piping JC Fan

Stop valve (with service port 1/4’’ flare)

Field piping JA

Indoor heat exchanger

Indoor unit Field piping J9.5

Field piping J19.1

Compressor

Outdoor unit

A 12.7 15.9

B 28.6 28.6

C 6.4 9.5

Model RP200 RP250

Field piping JC Fan

Field piping JA

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

• Split - Sky Air • Outdoor Units

3TW23615-4

13

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

8

1 8

Wiring diagrams See chapter RP-L7/B7 for the wiring diagrams of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1

9

Sound level See chapter RP-L7/B7 for the sound levels ofRP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1

10

Accessories See chapter RP-L7/B7 for the accessories of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1

11

Center of gravity See chapter RP-L7/B7 for the centre of gravity of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1

12

Safety device settings See chapter RP-L7/B7 for the safety device setting of RP71-100-125L7V1/W1∼RP71-100-125B7T1∼RP200-250B7W1

14

• Split - Sky Air • Outdoor Units

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

13

Installation

RP71-125L7/B7

1

(B) In case obstacles exist only in front of outlet side

The numerical figures used here represent the dimensions for the models RP71 to 125. The figures inside ( ) indicate the dimensions for the models RP100 and 125. (Unit:mm) The figures inside < > indicate the dimension of discharge grille when it is installed facing downward When installing multiple units in lateral connection, discharge grille cannot be set to discharge air in Left/Right direction

(A) In case obstacles exist in front of the air inlet

13

+ Where there are no obstacles above the unit. 1

Installation of single unit + In case obstacles exist only in front of outlet side.

2

Installation of multiple units in lateral connection (2 units or more).

150 or more 20 mm or more 20 mm or more

+ Where there are no obstacles above the unit 1

Installation of single unit + In case obstacles exist only in front of the air inlet. + In case obstacles exist in front of the air inlet and on both sides of the unit.

50 or more (100)

1000 mm or more

+ Where there are obstacles above the unit.

100 or more

2 Installation of multiple units in lateral connection (2 units or more).

1

Installation of single unit + In case obstacles exist only in front of outlet side.

2

Installation of multiple units in lateral connection (2 units or more).

100 or more

100 or more

100 or more

500 or less

20 mm or more 20 mm or more

+ In case obstacles exist in front of the air inlet and on both sides of the unit.

1000 mm or more

500 mm or more

500 or less 200 or more (300)

20 mm or more

1000 mm or more

20 mm or more

+ Where there are obstacles above the unit.

+ In case obstacles exist only in front of outlet side.

1000 mm or more

1

500 or less

Installation of single unit + In case obstacles exist only in front of the air inlet.

20 mm or more

100 or more 500 or less 1000 mm or more

+ In case obstacles exist in front of the air inlet and on both sides of the unit.

1000 mm or more

(C) In case obstacles exist in front of both the air inlet and outlet sides.

Pattern 1 150 or more

150 or more

150 or more

+ Where there are no obstacles above the unit.

500 or less 20 mm or more

1000 mm or more

2 Installation of multiple units in lateral connection (2 units or more).

1

2

1000 mm or more

+ In case obstacles exist in front of the air inlet and on both sides of the unit.

20 mm or more 200 or more (300) 200 mm or more

Where obstacle in front of the air outlet is higher than the unit.

Installation of single unit. Installation of multiple units in lateral connection (2 units or more).

50 or more (100) 500 or more (1000)

20 mm or more 20 mm or more

200 or more (300) 1000 or more (1500)

DU427-826

• Split - Sky Air • Outdoor Units

15

• Twin/triple/double twin application • R-407C • RP71-125L7V1/W1∼RP71-125B7T1∼RP200-250B7W1

13

1

13

Installation

RP71-125L7/B7

2 500 or less

Installation of single unit.

Relation of dimensions of H, A, and L are shown in the table below. L≤H H