Temperature Controller Plug-In

Description / Documentation

Temperature Controller Plug-In Description / Documentation

www.belimo.com

Temperature Controller Plug-In • en • v2.1 • 04.2015 • Subject to changes

1 / 10

Temperature Controller Plug-In

Description / Documentation

Table of Content

1

General ........................................................................................................................................................ 3

2

Application ................................................................................................................................................... 3

3

Accessing Thermostat Object #8060 .......................................................................................................... 4

4

Installation ................................................................................................................................................... 5 4.1

System requirements .......................................................................................................................... 5

4.2

Installation........................................................................................................................................... 5

5

Remote capability ........................................................................................................................................ 5

6

Opening the Plug-In .................................................................................................................................... 5

7

Functions ..................................................................................................................................................... 6 7.1 Heating ............................................................................................................................................... 7 7.1.1 Set point (SpH) ............................................................................................................................... 7 7.1.2 Parameters ..................................................................................................................................... 7 7.2 Cooling................................................................................................................................................ 8 7.2.1 Set point (SpC) ............................................................................................................................... 8 7.2.2 Parameters ..................................................................................................................................... 8 7.3 General controller settings .................................................................................................................. 9 7.3.1 Controller mode .............................................................................................................................. 9 7.3.2 Bypass Time (switch-back delay Comfort mode) ........................................................................... 9 7.3.3 Sensitivity........................................................................................................................................ 9 7.4

CO2 control settings (with corresponding LON application only) .....................................................10

www.belimo.com

Temperature Controller Plug-In • en • v2.1 • 04.2015 • Subject to changes

2 / 10

Temperature Controller Plug-In

1

Description / Documentation

General

The Belimo Temperature Controller Plug-In is an LNS-capable Plug-In, run-capable on a Standard LNSBinding Tool (LonMaker, NL220, Alex etc.). It is used for configuring the Controller Object (LonMark Thermostat Object #8060) of the Belimo LON actuators.

2

Application

The Temperature Controller Plug-In is available with the following Belimo LON actuators:

Please contact your local Belimo representative if you require other actuators in LON versions. Overview: www.belimo.eu

www.belimo.com

Temperature Controller Plug-In • en • v2.1 • 04.2015 • Subject to changes

3 / 10

Temperature Controller Plug-In

3

Description / Documentation

Accessing Thermostat Object #8060

Das Temperature Controller Plug-In accesses the controller function via Thermostat Object #8060. Thermostat Object #8060

nviSetPoint SNVT_temp_p

nvoHeatOutput SNVT_lev_percent

nvoCoolOutput SNVT_lev_percent

nvoSpaceTemp SNVT_temp_p nvoUnitStatus SNVT_HVAC_Status

nviSpaceTemp SNVT_temp_p

nvoHeatCoolOutput SNVT_lev_percent

nviOccCmd SNVT_occupancy

nvoEffectSetpt SNVT_temp_p

nviEnergyHoldOff SNVT_switch nviSetptOffset SNVT_temp_p

nviDewpointAlarm SNVT_switch nviSenOccCmd SNVT_occupancy nviSpaceCO2 SNVT_ppm

Configuration Properties SCPTobjMajVer (167) SCPTobjMinVer (168) SCPTmaxRcvTime (48) SCPTmaxSendTime (49) SCPTbypassTime (34) SCPTsetPnts (60) UCPTpiConfig (5) UCPTsensitivity (4) UCPTspaceCO2Low (6) UCPTspaceCO2High (7)

Remark: The variable nviSpaceCO2 is only available with corresponding LON application.

www.belimo.com

Temperature Controller Plug-In • en • v2.1 • 04.2015 • Subject to changes

4 / 10

Temperature Controller Plug-In

4 4.1 -

4.2

Description / Documentation

Installation System requirements Minimum requirement LNS 3.x Remote capability (with LNS Turbo Edition)

Installation

Belimo provides the Temperature Controller Plug-In as setup file. The setup file contains all Belimo Plug-In (Actuator, Sensor, Controller), that is why only one setup procedure is required. Download address: : www.belimo.eu Bus- & System-Integration ¦ LonWorks ¦ Download Section

1. Download the Plug-In and save to a temporary directory 2. Start installation by double-clicking on the file BelimoPlugIn - xxxx.exe. 3. Follow the instructions in the Setup program

5

Remote capability

The Plug-In is remote-capable. This means that remote-controlled access to the database of a project is possible at any time.

Picture: Remote Lightweight Client. e.g.: Remote access via an IP connection to a LonWorks project.

6

Opening the Plug-In

Procedure: (Example: LonMaker Binding Tool)

1

1. Selecting the Controller Object 2. Select "Configure“ in the context menu

2

www.belimo.com

Temperature Controller Plug-In • en • v2.1 • 04.2015 • Subject to changes

5 / 10

Temperature Controller Plug-In

7

Description / Documentation

Functions

The controller settings can be adjusted through the Plug-In in accordance with the application.

Initial sequences for heating, cooling Two initial sequences area available for controlling the heating and/or cooling units. The two identically constructed sequences can be adjusted independently of one another. The setpoint values are tested for plausibility at the time of input in order to prevent unnecessary energy consumption. As a result, no overlapping of the heating and cooling setpoint values is possible, for example.

Plug-In Dialog

Remark: The CO2-Limits are only adjustable with corresponding LON application. www.belimo.com

Temperature Controller Plug-In • en • v2.1 • 04.2015 • Subject to changes

6 / 10

Temperature Controller Plug-In

7.1 7.1.1

Description / Documentation

Heating Set point (SpH)

The heating sequence is equipped with the following three Set point (SpH) adjustment parameters

Mode

Description

 Comfort  Pre-comfort  Building protection

Room occupied Stand-by, lowering mode Building protection - Window open -> Energy hold off

7.1.2

Range

12…35°C 11…34°C 10…30°C

Default

21°C 18°C 14°C

Parameters

Function

Description

Range

Default

P-Band (PB) Integral time

Proportional band P-Controller (in Kelvin) Reset time PI Controllers (in seconds)

0.0...100.0 K 0…6000 sec

4.0 K 600 sec

www.belimo.com

Temperature Controller Plug-In • en • v2.1 • 04.2015 • Subject to changes

7 / 10

Temperature Controller Plug-In

7.2 7.2.1

Description / Documentation

Cooling Set point (SpC)

The cooling sequence is equipped with the following three Set point (SpC) adjustment parameters

Mode

Description

 Comfort  Pre-comfort  Building protection

Room occupied Stand-by, lowering mode Building protection - Window open -> Energy hold off - Dew point not reached

7.2.2

Range

11…34°C 12…35°C 30…35°C

Default

23°C 26°C 35°C

Parameters

Function

Description

Range

Default

P-Band (PB) Integral time

Proportional band P-Controller (in Kelvin) Reset time PI Controllers (in seconds)

0.0...100.0 K 0…6000 sec

2.0 K 600 sec

www.belimo.com

Temperature Controller Plug-In • en • v2.1 • 04.2015 • Subject to changes

8 / 10

Temperature Controller Plug-In

7.3

7.3.1

Description / Documentation

General controller settings

Controller mode

The control mode can be specified by means of the Mode parameter as: - P-Controller or - PI-Controller (default).

7.3.2

Bypass Time (switch-back delay Comfort mode)

Bypass Time

Range

Default

0…120 min

60 min

Switching back and forth between the Comfort and Pre-Comfort modes is accomplished by means of the local occupancy input (nviSenOccCmd). The Bypass Time (switch-back delay) parameter makes it possible to have a time delay when switching back from Comfort to Pre-Comfort. Benefit: The Comfort mode stays active during short absence (e. g. breaks)

7.3.3

Sensitivity

The sensitivity of the variable nviSpaceTemp can be adjusted with the parameter Sensitivity: - Low: prevent or reduce short-term interferences which affect the sensor. - High: Deactivate filter function, for system testing, etc.

Sensitivity

www.belimo.com

Range

Default

Low/high

low

Temperature Controller Plug-In • en • v2.1 • 04.2015 • Subject to changes

9 / 10

Temperature Controller Plug-In

7.4

Description / Documentation

CO2 control settings (with corresponding LON application only)

The Thermostat object #8060 provides an additional input for a CO2 signal in ppm (nviSpaceCO2). The resulting air demand 0…100% is calculated based on the CO2 pollution and the control limits nciSpaceCO2Low and nciSpaceCO2High. The air demand is provided on the cooling sequence (nvoCoolOutput). Combination with temperature control: In the case that both control loops are active, that is that the temperature value as well as the CO2 value are bound, the value of the output variable nvoCoolOutput is the maximum of the cooling sequence (temperature controller) and the air demand (CO2 controller).

Low Limit High Limit

www.belimo.com

Range

Default

1…5000 ppm 1…5000 ppm

400 ppm 800 ppm

Temperature Controller Plug-In • en • v2.1 • 04.2015 • Subject to changes