Sheet No. Component /Detail

Description

1

Draw ing Guide

2-4

Solution

5-7

UPS

MGE Galaxy 3500 10-15kVA 208V, Narrow Tow er

8

SBP

MGE Galaxy 3500, Parallel Maintenance Bypass up to 3 units, 10-15kVA 208V, Floormount

9-10 11

MGE Galaxy 3500 Narrow 10 to 15 kVA 2 Mod w ith Floor mount SBP draw ing guide MGE Galaxy 3500 Narrow Tow er 10-15kVA 2 MOD, SBP, 208V.

System One Line Diagram MGE Galaxy 3500 10-15kVA 208V 2MOD Narrow w ith Floor mount SBP System One Line Diagram System Wiring Diagram MGE Galaxy 3500 10-15kVA 208V 2MOD Narrow w ith Floor mount SBP System Control Wiring Diagram

2xG35T15KF2B2S with SBP

2xG35T10KF2B2S with SBP

15kVA

2xG35T10KF1B2S with SBP

Total number of battery modules (SYBT4) in UPS

10kVA

Net Net Net Weight in Runtime Weight in Runtime Weight in Runtime lbs [kg] in Min lbs [kg] in Min lbs [kg] in Min

1

1610 [732]

6

n.a

n.a

n.a

n.a

2

2014 [916]

18

2014 [916]

18

2014 [916]

10

FLOOR LOADING DATA - BATTERY CABINET No. of Dimensions H x W SKU Number Battery x D Inch [mm] Modules G35TBXR2B6

2

58.66x20.61x32.87 [1490x523x835]

3

58.66x20.61x32.87 [1490x523x835] 1066 [484]

227 [1110]

4

58.66x20.61x32.87 [1490x523x835] 1278 [580]

272 [1330]

5

58.66x20.61x32.87 [1490x523x835] 1489 [676]

317 [1550]

6

G35TBXR6B6

G35TSBPAR10K15F

10kVA

855 [388]

58.66x20.61x32.87 [1490x523x835] 1700 [772]

FLOOR LOADING DATA - SBP CABINET Dimensions H x W SKU Number x D Inch [mm]

Rating

Floor Weight in Loading Data lbs [kg] in lbs/sq.ft

SKU Number

58.7x13.8x32.9 [1490x352x835]

182 [890]

361 [1770]

Weight in Floor lbs [kg] Loading Data 268 [122]

85 [415]

COG Details in Inches [mm] X-Distance Y-Distance Z-Distance

G35T10KF1B2S 6.93 [176] 25.79 [655] 15.75 [400]

G35T10KF2B2S 6.93 [176] 25.59 [650] 15.67 [398] 15kVA G35T15KF2B2S 6.93 [176] 25.59 [650] 15.67 [398] No. of Batter G35TBXR2B6 2 3 4 5 G35TBXR6B6 6 SKU Number

SKU Number G35TSBPAR10K15F

COG Details in Inches [mm] X-Distance Y-Distance Z-Distance 10.28 [261] 19.68 [500] 15.87 [403] 10.28 [261] 19.53 [496] 15.79 [401] 10.28 [261] 20.47 [520] 15.71 [399] 10.28 [261] 22.05 [560] 15.67 [398] 10.28 [261] 24.02 [610] 15.63 [397] COG Details for SBP in Inches(mm) X-Distance Y-Distance Z-Distance 6.92 (176) 30 (762) 12.71 (323)

DEVICE

RATED SHORT CIRCUIT CURRENT

UPS

30kAIC SYMMETRICAL

SBP

20kAIC SYMMETRICAL

DEVICE RATING FOR G35TSBPAR10K15F

MODEL

ACCESSORIES

Q2a, Q2b, Q2c

60A

CB 4POLE 600V ABB

T1N060TL-4A AUX-C 3Q 1SY 24VDC

1-Aux. Sw itch

Q3, Q4

175A

CB 4POLE 600V ABB

T3N175TW-4A3, KT3AS3

1-Aux. Sw itch

DEVICE ID

RATING TYPE

MAKE

Galaxy 3500® 10K and 15K UPS Frame (2 Module) with SBP Site Planning Data Battery - Nominal Voltage : +/-192V DC Input Voltage : 208V AC, Output Voltage : 208V AC System Mains Input

UPS Rating

15KVA/12KW

G35T10KF1B2S G35T10KF2B2S G35T15KF2B2S

Recom m ended Over current Protection Device Ratings

System Output

SKU Number Nominal Current(A)

10KVA/8KW

System Bypass Input

Maximum Nominal System output Nominal Current(A) Current(A) Power Current(A)

Battery Current(A) (in UPS Cabinet)

Individual UPS Mains Input (A)

Individual UPS Bypass Input (A)

UPS System Input (A)

UPS System Output (A)

48.6

53.4

48.6

20KVA/16KW

55.6

27.5

35

35

70

70

73

80.4

73

30KVA/24KW

83.2

41.2

60

60

120

120

UPS Mechanical Data

58.7x14x33 [1491x356x838]

873 [397]

Floor Loading Heat Loss data in BTU/hr See Lbs/ft 2 Note 23 [kg/m2] 209 [1023] 1938 272 [1330]

58.7x14x33 [1491x356x838]

873 [397]

272 [1330]

Weight in Typical Dimensions H x W x D lbs [kg] see in inches [mm] see note 15 Note 15 58.7x14x33 [1491x356x838]

671 [305]

Notes. 1. Input current based on full rated output load.. 2. Maximum (Max.) current is for duration of battery recharge. 3. Input and bypass cables must be run in separate conduits from output cables. Not more than three conductors in raceway assumed; ambient temperature of 30°C (86°F) assumed. 4. If initial load is less than UPS' rated output, it is recommended that AC input, battery, and AC output wiring and over current protection be sized to UPS’ full load rating to accommodate possible future expansion. 5. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2. 6. DC cables should be sized for a total maximum of less than 1% of CB rating. 7. OCPD = Over current Protection Device. Recommended represents 125% of nominal full load current (continuous) per NEC 215. 8. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Neutral conductors to be sized for full capacity per NEC 310-15(b)(4). 9. Wiring requirements: - AC Input/Output: 3Ø, 3 or 4 wire + ground, depending on UPS configuration. See Installation Manual and submittal drawings for specific instructions. - DC Input: 2 wire (positive and negative) + ground 10. All wiring to be in accordance with all applicable national and/or local electrical codes. 11. DC cabling should be sized to give < 1% voltage drop at the nominal battery discharge current using three-wire separate conductors in positive, centre-tap and negative poles 12. Minimum access Clearance on all drawings. 13. Bottom cable entry through removable access plates. Punch plates to suit conduit size,then replace. 14. Control wiring and power wiring must be run in separate conduit. 15. Weights and dimensions shown do not include battery cabinet(s), distribution cabinet(s), or other options. 16. Backup emergency generator must be properly sized for UPS application and equipped with an isochronous governor for frequency regulation, and a UPS-compatible voltage regulator for voltage stability. 17. Input : THDI < 5% at full load. 18.Output : THDU