GRUNDFOS DATABOOKLET

Control 2000, Delta Control 2000 Controllers for pumps connected in parallel

Contents

General data Application Control 2000 Delta Control 2000

Page Page Page

3 3 3

Page

4

Page Page Page Page

5 6 8 10

Page Page

13 18

General data, Control 2000 System configuration

Functions, Control 2000 Functions Type key Examples of functioning Control parameters

Technical data, Control 2000 Dimensions and weight Product numbers

General data, Delta Control 2000 System configuration

Page

24

Page Page Page Page Page

25 26 28 30 31

Functions, Delta Control 2000 Functions Type key Examples of functioning Control parameters Systems with PMU 2000

Technical data, Delta Control 2000 Dimensions and weights Product numbers

Page Page

34 38

Page Page Page Page Page Page Page Page Page Page Page Page

42 42 42 43 43 43 43 43 43 43 43 43

Page Page

44 44

Optional equipment PMU 2000 Switching off of neutral lead Emergency operation switch Phase-failure protection Lightning protection Voltmeter Ammeter Operating light Fault light Panel light Extra documentation Enclosure class

Accessories PMU 2000 PCU 2000

2

General data

Control 2000 Delta Control 2000

Application Control 2000

Delta Control 2000

The Control 2000 controller is used for pumps connected in parallel in systems which should supply a geometric head.

The Delta Control 2000 controller is used for pumps connected in parallel in closed systems with the purpose of circulating a pumped liquid.

Typical systems are water supply systems, pressure boosting systems or other systems characterized by a varying water consumption and in which a constant pressure should be maintained.

Typical systems are heating or air-conditioning systems characterized by a variable need for pumping and in which a constant differential pressure should be maintained. The control of pumps according to temperature or flow is also possible using the Delta Control 2000.

The Control 2000 controller features all the necessary components to control and monitor 2 - 6 pumps connected in parallel.

The Delta Control 2000 controller features all the necessary components to control and monitor 1 - 4 pumps connected in parallel.

Delta Control 2000 Control 2000

Pumps

Boiler or refrigeration unit

Heating or air-conditioning system

TM01 2858 2598

TM01 2856 2598

Pumps

TM01 2857 2598

Geometric head

TM01 2855 2598

System characteristics

General data, Control 2000

3

General data

Control 2000

System configuration The Control 2000 consists of three main groups: 3.

Control 2000 E is used when the system comprises E-pumps (Grundfos pumps equipped with Grundfos MGE motors). Each main group consists of subgroups, see the table below:

1. Control 2000 S is used for mains operation (on/off operation) of standard pumps with standard motors. 2. Control 2000 F features a standard frequency converter and can be used together with pumps with standard motors.

Description of pumps

Control 2000 S (on/off)

Main group

Subgroup

Size

Number

MS

Full-size

All

Mains operation (on/off).

Half-size

1

Mains operation (on/off).

Full-size

All other pumps

Mains operation (on/off).

Number of controlled pumps

MF Control 2000 F (Variable speed)

Comments

MSH

1

1

Speed control via frequency converter mounted in control cabinet.

Full-size All other pumps

Frequency-converter control rotates among all pumps in the system.

Mains operation (on/off).

1

Speed control via frequency converter mounted in control cabinet.

Frequency-converter control alternates between the two pumps. The uncontrolled pump is mains operated (on/off).

Half-size

2

Full-size

All other pumps

Full-size

All

All

Speed control via frequency converter integrated in the motor.

All pumps in operation run at the same speed (cascade control).

Half-size

2

2

Speed control via frequency converter integrated in the motor.

The two pumps run at the same speed when both are in operation.

Full-size

All other pumps

Full-size

1

Full-size

All other pumps

MFH

ME

Control 2000 E (Variable speed)

Mode of operation

Mains operation (on/off).

MEH Mains operation (on/off).

1

Speed control via frequency converter integrated in the motor.

MES

Abbreviations: M: The Control 2000 features a microprocessor for the control of all functions.

4

S:

Some or all of the pumps in the system are on/offoperated.

F:

The Control 2000 features a frequency converter for the speed control of some of the pumps in the system. One pump only is speed-controlled at a time.

E:

Some or all of the pumps in the system are E-pumps (pumps with integrated frequency converter).

Mains operation (on/off).

H: The system has one or two half-size pumps (one half-size pump provides approximately the same head as one full-size pump, but only approxi mately half the flow).

Functions

Functions Control 2000 A standard Control 2000 always includes the electronics unit PFU 2000 (Pump Functional Unit 2000) built into the control cabinet. The PFU 2000 front cover with reset button and indicator lights is mounted in the front door of the control cabinet. Alternatively, the Control 2000 can be supplied with the PMU 2000 (Pump Management Unit 2000) mounted in the front door of the control cabinet. The PMU 2000 enables the read-out of operating data and the optimisation of operation according to system conditions. The Control 2000 without PMU 2000 offers the following functions:

Control 2000

• Possibility of digital remote-control functions: –system on/off, –reduced operation, –setpoint control with two-point switch, –setpoint control with three-point switch, –alternative setpoint. • Pump and system monitoring functions: –minimum and maximum limits of actual value, –inlet pressure, –motor protection. • Display and indication functions: –2 x 24 character LCD display, –green indicator light for operating indications and red indicator light for fault indications, –potential-free changeover contacts for operation and fault. • Clock functions.

• Constant pressure control of the system.

• GRUNDFOS BUS communication.

• On/off operation at low flow.

PCU 2000

• Automatic changeover to mains operation in case of defective frequency converter (Control 2000 F only). • Automatic cascade control of pumps. • Possibility of setpoint influence: –proportional influence (proportional pressure), –external setpoint influence. • Possibility of remote control: –system on/off. • Pump and system monitoring functions: –inlet pressure –motor protection.

A PCU 2000 (Pump Communication Unit 2000) can be connected to the Control 2000 via the BUS input. The PCU 2000 enables remote operating and fault indication for each individual pump. The PCU 2000 also enables external setpoint influence and system on/off. Functions, Control 2000 Functions

• Display and indication functions: –green indicator light for operating indications and red indicator light for fault indications, –potential-free changeover contacts for operation and fault. • GRUNDFOS BUS communication. The Control 2000 with PMU 2000 offers the following functions: • Constant pressure control of the system. • On/Off operation at low flow. • Automatic changeover to mains operation in case of defective frequency converter (Control 2000 F only). • Automatic cascade control of pumps. • Selection of switching sequences, automatic pump changeover and pump priority. • Manual operation. • Possibility of setpoint influence: –proportional influence (proportional pressure), –external setpoint influence.

5

Functions

Control 2000

Type key Example Type range Supgroup: MS - MSH - MF - MFH - ME - MEH - MES Number of full-size pumps 1 - 4 Power, full-size pumps [kW] Starting method of full size pumps: DOL: Direct-on-line starting SD: Star-delta starting E: Electronic soft start (MGE motor) Number of half-size pumps 1 - 2 Power, half-size pumps [kW] Starting method of half-size pumps: DOL: Direct-on-line starting SD: Star-delta starting E: Electronic soft start (MGE motor) Control panel: PMU: PMU 2000 PFU: PFU 2000 Supply voltage/frequency Enclosure class: IP 54 IP 00

6

Control 2000

MEH

2

x 5.5

SD

+

2

x 3.0

E

PMU

3 x 400/230 V, 50 Hz

IP 54

7

Functions

Control 2000

Examples of functioning The following table shows examples of Control 2000 systems using constant pressure control.

On/off

Variable speed GRUNDFOS Control 2000 MSH

PFU 2000

GRUNDFOS Control 2000 MF

PFU 2000

PFU 2000

TM002680 0294

TM00 2674 0294

TM00 2678 0294

PFU 2000

The half-size pump in opera- One pump in operation via One half-size pump in operation. frequency converter. tion via frequency converter.

Q

H

TM00 2751 0294

Q

H stop H set

Q

TM00 2775 0294

H

H set

Q

H set

Q

One full-size pump and the One pump in operation via One half-size pump in operahalf-size pump in operation. frequency converter and two tion via frequency converter pumps on mains operation. and one full-size pump on mains operation

H

H stop

H set

H

H set

Q

H set

Q

TM00 2783 0294

Three pumps in operation.

H set

TM00 2759 0294

Q

Hstop

TM00 2773 0294

H set

TM00 2749 0294

Hstop

H

H

H

TM00 2781 0294

H

TM00 2757 0294

One pump in operation.

GRUNDFOS Control 2000 MFH

TM002677 0294

GRUNDFOS Control 2000 MS

• Maintains an almost con- • Maintains an almost con- • Maintains a constant • Maintains a constant stant pressure through stant pressure through pressure through continupressure through continucutting in/out the halfcutting in/out the reously variable adjustously variable adjustsize pump and the fullquired number of pumps. ment of the speed of one ment of the speed of one size pumps. pump. The other pumps half-size pump. The rest • Changeover among the are mains-operated (on/ of the pumps are mainspumps is automatic and • The half-size pump will aloff) according to the deoperated. ways start first, and will depends on load, time mand. be cut out again when a and fault. • The half-size pump confull-size pump is cut in. • The frequency-converter trolled by the frequency • The cut-out pressure controlled pump will alconverter will always start (Hstop) cannot be set but is • Changeover among the ways start first. first. calculated automatically. full-size pumps is automatic and depends on load, time and fault.

• Pump changeover is auto- • Pump changeover is automatic and depends on matic and depends on load, time and fault. load, time and fault.

• The cut-out pressure (Hstop) cannot be set but is • Besides, all pumps will be calculated automatically. controlled by the frequency converter in rotation.

8

Functions

Control 2000

Examples of functioning, cont. The following table shows examples of Control 2000 systems using constant pressure control.

Variable speed GRUNDFOS Control 2000 MEH

PFU 2000

MGE

MGE

The half-size pump in opera- One half-size pump in operation. tion via frequency converter. H

Three pumps in operation.

H set

Q

H

TM00 7996 2296

Q

Q

One full-size pump and the One half-size pump in operahalf-size pump in operation. tion via frequency converter and one full-size pump on mains operation

H

H set

H set

H

H set

Q

H set

Q

TM00 7998 2296

Q

TM00 7995 2296

H set

TM00 7994 2296

H

H

TM00 7993 2296

One pump in operation.

MGE

TM00 7984 2296

MGE

PFU 2000

TM00 7997 2296

MGE

TM00 7983 2296

PFU 2000

MGE

GRUNDFOS Control MES

TM00 7985 2296

GRUNDFOS Control 2000 ME

• Maintains a constant • Maintains a constant • Maintains a constant pressure through continupressure through continupressure through continuously variable adjustously variable adjustously variable adjustment of the speed of the ment of the speed of the ment of the speed of one pumps connected. two half-size pumps with pump. The other pumps MGE motors, while the are cut in/out on mains • The system performance full-size pump is mainsoperation according to deis adjusted to the demand operated. (on/off). mand thus achieving a through cutting in/out performance correspondthe required number of • The half-size pumps aling to the consumption. pumps and through paralways start first. lel control of the pumps in • Pump changeover is auto- • The pump with MGE mooperation. tor will always start first. matic and depends on • Pump changeover is autoload, time and fault. • Pump changeover is automatic and depends on matic and depends on load, time and fault. load, time and fault.

9

Functions

Control 2000

Control parameters

Remote setpoint setting:

Systems without PMU 2000

A 0 - 10 V or 0 - 20 mA signal can be connected for remote setpoint setting.

Controllers without the PMU 2000 can be used in systems having small time constants and are preset to the control parameter "pressure".

Setpoint via external signals Actual setpoint Current setpoint

Locally Locallyset set setpoint setpoint TM00 7048 0296

TM01 2504 1898

PFU 2000

P

100% 100%

Transmitterrange Transmitter range

Pressure

10 V 10V

0

20 mA

The locally set setpoint is set by means of the function selector in the PFU 2000. Sensor input:

Cascade control: Cascade control ensures automatic adjustment of performance to the system demand by cutting in/out the required number of pumps. The controller will operate the system with as few pumps as possible.

Sensors giving the following analog signals can be connected: – 0 - 10 V, – 0 - 20 mA, – 4 - 20 mA. Input for external start/stop:

Automatic pump changeover:

A potential-free contact for external start/stop of all pumps can be connected.

• Fault-dependent pump changeover. If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on. • Time-dependent pump changeover. This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function. Test run: To eliminate the risk of pump seizure caused by long periods of standstill, a test run lasting 1 sec. is carried out once every 24 hours.

Systems with PMU 2000 The PMU 2000 is designed for the control of various pumps or pump systems. As an example, the PMU 2000 can be used for the control of GRUNDFOS circulator pumps of the UPE type and pumping systems and controllers based on the PFU 2000, such as the Control 2000. Using the Control 2000 it is possible to control the pumps according to a constant pressure (fig. 1) or a constant pressure with pre-pressure measuring (fig. 2). Pressure

Setpoint: The setpoint is set by means of the function selector in the PFU 2000. It is also possible to stop all pumps, or to set all pumps to operate at maximum performance.

PFU 2000

P

Function selector in the PFU 2000 Setpoint

100% MAX

Fig. 1. Pressure with pre-pressure measuring PFU 2000

P

Fig. 2

10

P

TM01 2505 1898

STOP

TM00 5217 2796

0%

TM01 2504 1898

Automatic pump changeover is made as follows:

Functions

Control 2000

Cascade control:

Friction loss compensation:

Cascade control ensures automatic adjustment of performance to the system demand by cutting in/out the required number of pumps.

The control unit is capable of compensating for friction loss. The setpoint increases from an adjustable percentage at zero flow to 100% at max. flow. The actual flow is estimated based on internal operating data without the flow being measured directly.

The controller will operate the system with as few pumps as possible.

Friction loss compensation

The on/off rate is limited by setting the switching sequences.

HH

Automatic pump changeover:

Setpoint Setpoint max max.

60% 60 %

• Fault-dependent pump changeover. If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on. • Time-dependent pump changeover. This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function. Test run: To eliminate the risk of pump seizure caused by long periods of standstill, a test run lasting 1 sec. is carried out once every 24 hours. Clock functions: If the system demand varies during the day and/or during the week, the pump performance required will also vary. In this case, a clock program can be set in order to achieve optimum performance of the pumps. It is possible to set a total of 10 switching times, all having individual setpoints. Clock program with three switching times Setpoint Setpoint

Q Q

TM00 4991 4894

100 % 100%

Automatic pump changeover is made as follows:

Remote setpoint setting: In view of optimizing system operation, it is often best for the system to operate according to a variable setpoint instead of a constant setpoint. The selected settings influencing the setpoint will reduce "setpoint max". The following possibilities are available: • "extern" (%) An external analog signal or potential-free contact influences the setpoint in accordance with a table. • "timer" (minutes) An internal timer program in the PMU 2000 controls the setpoint in accordance with a table. • "level" (m, cm, ft, in) The level signal controls the setpoint in accordance with a table. • "flow" (m3/h, l/h, l/s, gpm) The flow signal controls the setpoint in accordance with a table.

C

1

2

3

Time Time

TM00 4989 4894

B A

• "flow/I" (%), (applies only to Delta Control 2000 F) An internal flow signal controls the setpoint in accordance with a table.

Sensor input:

Standby pumps:

Sensors giving the following analog signals can be connected:

In systems with more than one pump, standby pumps can be selected. A standby pump is started only if one of the duty pumps is faulty.

– 0 - 10 V, – 0 - 20 mA, – 4 - 20 mA.

Example: In a system with four pumps of which one pump has been selected as standby-pump, the maximum number of pumps in operation at the same time will be three. The standby pump is started only if one of the duty pumps is faulty.

Setpoint: The max. setpoint is set in the PMU 2000 menu Set A Setpoint max.

5.0 bar

11

Technical data

Control 2000

Dimensions and weights All motors must be three-phase.

H

Delta

H

The starting methods of the motors are:

TM00 9394 2402- TM01 0473 2402

Dimensions and weights are for control cabinets with a PFU 2000 control panel. l 2000 Contro

2000 Control Delta

• DOL (Direct-on-line starting) • SD (Star-delta starting) • E (Electronic soft start via frequency converter).

D

B

B

D

Mounting Motor of control [kW] cabinet

Starting full-size

Control 2000 MS Control 2000 MS for 2 pumps Dimensions [mm] H

B

D

Weight [kg]

Dimensions [mm] H

B

D

Weight [kg]

Control 2000 MS for 4 pumps Dimensions [mm] H

B

D

Weight [kg]

Control 2000 MS for 5 pumps Dimensions [mm] H

B

D

Weight [kg]

Control 2000 MS for 6 pumps Dimensions [mm] H

B

D

Weight [kg]

0.37 Wall mount. DOL 600

380 210

20

600

380 210

21

600

600 210

31

600

600 210

31

600

600 210

32

0.55 Wall mount. DOL 600

380 210

20

600

380 210

21

600

600 210

31

600

600 210

31

600

600 210

32

0.75 Wall mount. DOL 600

32

380 210

20

600

380 210

21

600

600 210

31

600

600 210

31

600

600 210

1.1

Wall mount. DOL 600

380 210

20

600

380 210

21

600

600 210

31

600

600 210

31

600

600 210

32

1.5

Wall mount. DOL 600

380 210

20

600

380 210

21

600

600 210

31

600

600 210

31

600

600 210

32

2.2

Wall mount. DOL 600

380 210

20

600

380 210

21

600

600 210

31

600

600 210

31

600

600 210

32

3

Wall mount. DOL 600

380 210

20

600

380 210

21

600

600 210

31

600

600 210

31

600

600 210

32

4

Wall mount.

SD

600

600 210

31

600

600 210

32

1000 800 300

66

1000 800 300

68

1000 800 300

69

5.5

Wall mount.

SD

600

600 210

31

600

600 210

32

1000 800 300

66

1000 800 300

68

1800 1000 400 163!

7.5

Wall mount.

SD

600

600 210

31

600

600 210

33

1000 800 300

66

1800 1000 400 161! 1800 1000 400 164!

11

Wall mount.

SD

600

600 210

31

1000 800 300

65

1000 800 300

67

1800 1000 400 162! 1800 1000 400 165!

15

Wall mount.

SD

600

600 210

32

1000 800 300

67

1000 800 300

69

1800 1000 400 164! 1800 1000 400 168!

18.5 Wall mount.

SD

1000 800 300

65

1000 800 300

68

1000 800 300

70

1800 1200 400 202! 1800 1200 400 204!

22

Wall mount.

SD

1000 800 300

66

1000 800 300

69

1000 800 300

71

1800 1200 400 203! 1800 1200 400 206!

30

Wall mount.

SD

1200 1000 300

97

1200 1000 300

101

1200 1000 300

105

1900 1200 400 218! 1900 1200 400 222!

! The control cabinet is prepared for floor mounting.

12

Control 2000 MS for 3 pumps

Technical data, Control 2000

Technical data

Control 2000

Control 2000 MSH Control 2000 MSH for 2 pumps (1 full-size and 1 half-size)

Motor

Full-size [kW]

Half-size [kW]

Mounting of control cabinet

Starting full-size

Starting half-size

Dimensions [mm] H

B

D

Weight [kg]

Control 2000 MSH for 3 pumps (2 full-size and 1 half-size) Dimensions [mm] H

B

D

Weight [kg]

Control 2000 MSH for 4 pumps (3 full-size and 1 half-size) Dimensions [mm] H

B

D

Weight [kg]

1.1

0.75

Wall mounting

DOL

DOL

600

380

210

20

600

380

210

21

600

600

210

32

1.5

1.1

Wall mounting

DOL

DOL

600

380

210

20

600

380

210

21

600

600

210

32

2.2

1.1

Wall mounting

DOL

DOL

600

380

210

20

600

380

210

21

600

600

210

32

3

1.5

Wall mounting

DOL

DOL

600

380

210

20

600

380

210

21

600

600

210

32

3

2.2

Wall mounting

DOL

DOL

600

380

210

20

600

380

210

21

600

600

210

32

4

2.2

Wall mounting

SD

DOL

600

600

210

31

600

600

210

32

1000

800

300

66

4

3.0

Wall mounting

SD

DOL

600

600

210

31

600

600

210

32

1000

800

300

66

5.5

3.0

Wall mounting

SD

DOL

600

600

210

31

600

600

210

32

1000

800

300

66

5.5

4.0

Wall mounting

SD

SD

600

600

210

31

600

600

210

32

1000

800

300

66

7.5

4.0

Wall mounting

SD

SD

600

600

210

32

600

600

210

34

1000

800

300

67

7.5

5.5

Wall mounting

SD

SD

600

600

210

32

600

600

210

34

1000

800

300

67

11

5.5

Wall mounting

SD

SD

600

600

210

32

600

600

210

34

1000

800

300

68

11

7.5

Wall mounting

SD

SD

600

600

210

32

600

600

210

34

1000

800

300

68

11

11

Wall mounting

SD

SD

600

600

210

32

600

600

210

34

1000

800

300

68

15

7.5

Wall mounting

SD

SD

600

600

210

33

1000

800

300

67

1000

800

300

69

15

11

Wall mounting

SD

SD

600

600

210

33

1000

800

300

67

1000

800

300

69

18.5

11

Wall mounting

SD

SD

600

600

210

33

1000

800

300

67

1000

800

300

69

22

11

Wall mounting

SD

SD

1000

800

300

65

1000

800

300

68

1000

800

300

71

22

15

Wall mounting

SD

SD

1000

800

300

66

1000

800

300

69

1000

800

300

71

30

15

Wall mounting

SD

SD

1200

1000 300

97

1200

1000 300

101

1200

1000 300

104

30

18.5

Wall mounting

SD

SD

1200

1000 300

97

1200

1000 300

101

1200

1000 300

104

Dimensions and weight

13

Technical data

Control 2000

Dimensions and weights Dimensions and weights are for control cabinets with a PFU 2000 control panel. All motors must be three-phase.

Delta

H

l 2000 Contro

The starting methods of the motors are: TM01 0473 2402

• DOL (Direct-on-line starting) • SD (Star-delta starting) B

D

Control 2000 MF Control 2000 MF for 2 pumps

Control 2000 MF for 3 pumps

Control 2000 MF for 4 pumps

Control 2000 MF for 5 pumps

Control 2000 MF for 6 pumps

Starting full-size

Mounting of control cabinet

Dimensions [mm]

0.37 Floor mount.

DOL

1400 600 300

77

1400 800 300

93

1400 800 300

94

1400 1000 300

111

1400 1000 300

112

0.55 Floor mount.

DOL

1400 600 300

77

1400 800 300

93

1400 800 300

94

1400 1000 300

111

1400 1000 300

112

0.75 Floor mount.

DOL

1400 600 300

77

1400 800 300

93

1400 800 300

94

1400 1000 300

111

1400 1000 300

112 112

Motor [kW]

H

B

D

Weight [kg]

Dimensions [mm] H

B

D

Dimensions [mm]

Weight [kg]

H

B

Dimensions [mm]

Weight [kg]

D

H

B

D

Weight [kg]

Dimensions [mm] H

B

Weight [kg]

D

1.1

Floor mount.

DOL

1400 600 300

77

1400 800 300

93

1400 800 300

94

1400 1000 300

111

1400 1000 300

1.5

Floor mount.

DOL

1400 600 300

77

1400 800 300

93

1400 800 300

94

1400 1000 300

111

1400 1000 300

112

2.2

Floor mount.

DOL

1400 600 300

77

1400 800 300

93

1400 800 300

94

1400 1000 300

111

1400 1000 300

112

3

Floor mount.

DOL

1400 600 300

77

1400 800 300

93

1400 800 300

94

1400 1000 300

111

1400 1000 300

112

4

Floor mount.

SD

1400 800 300

102

1400 1000 300

120

1400 1000 300

122

1400 1000 300

124

1900 1000 400

190

5.5

Floor mount.

SD

1400 800 300

102

1400 1000 300

120

1400 1000 300

122

1900 1000 400

188

1900 1000 400

190

7.5

Floor mount.

SD

1400 800 300

94

1400 1000 300

120

1400 1000 300

178

1900 1000 400

181

1900 1000 400

182

11

Floor mount.

SD

1900 1000 400

185

1900 1200 400

221

1900 1200 400

224

1900 1200 400

226

1900 1200 400

228

15

Floor mount.

SD

1900 1000 400

188

1900 1200 400

226

1900 1200 400

228

1900 1600 400

274

1900 1600 400

276

18.5 Floor mount.

SD

1900 1000 400

197

1900 1600 400

279

1900 1600 400

283

1900 1800 400

392

1900 1800 400

396

22

Floor mount.

SD

1900 1000 400

198

1900 1600 400

280

1900 1600 400

285

1900 1800 400

394

1900 1800 400

399

30

Floor mount.

SD

1900 1200 400

262

1900 1800 400

380

1900 2200 400

461

1900 2200 400

466

1900 2000 400

471

Control 2000 MFH Control 2000 MFH for 3 pumps (1 full-size and 2 half-size)

Motor

14

Mounting of control cabinet

Starting full-size

Starting half-size

Dimensions [mm]

Control 2000 MFH for 4 pumps (2 full-size and 2 half-size)

Weight [kg]

Dimensions [mm]

Weight [kg]

Full-size [kW]

Half-size [kW]

H

B

D

H

B

D

3

2.2

Floor mounting

DOL

DOL

1500

800

300

93

1500

800

300

94

4

3

Floor mounting

SD

DOL

1500

800

300

94

1500

800

300

95

5.5

3

Floor mounting

SD

DOL

1500

800

300

94

1500

800

300

95

5.5

4

Floor mounting

SD

SD

1500

1000

300

120

1500

1000

300

121

7.5

4

Floor mounting

SD

SD

1500

1000

300

120

1500

1000

300

121

7.5

5.5

Floor mounting

SD

SD

1500

1000

300

120

1500

1000

300

121

11

5.5

Floor mounting

SD

SD

1500

1000

300

120

1900

1000

400

178

11

7.5

Floor mounting

SD

SD

1500

1000

300

112

1900

1000

400

185

15

7.5

Floor mounting

SD

SD

1500

1000

300

112

1900

1000

400

179

15

11

Floor mounting

SD

SD

1900

1000

400

187

1900

1000

400

189

18.5

11

Floor mounting

SD

SD

1900

1000

400

187

1900

1000

400

180

22

11

Floor mounting

SD

SD

1900

1000

400

190

1900

1000

400

193

22

15

Floor mounting

SD

E/SD

1900

1000

400

190

1900

1000

400

193

30

15

Floor mounting

SD

E/SD

1900

1200

400

227

1900

1600

400

273

30

18.5

Floor mounting

SD

E/SD

1900

1600

400

282

1900

1600

400

283

Technical data

Control 2000

Dimensions and weights Dimensions and weights are for control cabinets with a PFU 2000 control panel. All motors must be three-phase.

H

The starting methods of the motors are:

2000 Control Delta

Note: E-pumps marked with """ must be with singlephase mains connection.

D

TM00 9394 2402

• E (Electronic soft start via frequency converter).

B

Control 2000 ME Control 2000 ME for 2 pumps

Motor [kW]

Mounting of control cabinet

Starting full-size

1.1 "

Wall mounting

E

Dimensions [mm] H

B

D

400

400

210

Control 2000 ME for 3 pumps Weight [kg] 14

Dimensions [mm] H

B

D

600

400

210

Control 2000 ME for 4 pumps Weight kg]

Dimensions [mm] H

B

D

Weight [kg]

20

1.1

Wall mounting

E

400

400

210

14

600

400

210

20

600

400

210

20

1.5

Wall mounting

E

600

400

210

20

600

400

210

20

600

400

210

20

2.2

Wall mounting

E

600

400

210

20

600

400

210

20

600

400

210

20

3

Wall mounting

E

600

400

210

20

600

400

210

20

600

400

210

20

4

Wall mounting

E

600

400

210

20

600

400

210

20

600

400

210

20

5.5

Wall mounting

E

600

400

210

20

600

400

210

20

600

400

210

20

7.5

Wall mounting

E

600

400

210

24

600

400

210

26

600

400

210

37

11

Wall mounting

E

600

380

210

25

600

380

210

26

600

600

210

37

15

Wall mounting

E

600

380

210

25

600

600

210

37

760

760

210

56

18.5

Wall mounting

E

600

380

210

26

760

760

210

55

760

760

210

57

22

Wall mounting

E

600

600

210

37

760

760

210

56

760

760

210

58

15

Technical data

Control 2000

The starting methods of the motors are: • DOL (Direct-on-line starting) • SD (Star-delta starting) • E (Electronic soft start via frequency converter)

Control 2000 MEH Motor

16

Full-size [kW]

Half-size [kW]

Mounting of control cabinet

Starting full-size

Starting half-size

Control 2000 MEH for 3 pumps (1 full-size and 2 half-size) Dimensions [mm] H

B

D

Weight [kg]

Control 2000 MEH for 4 pumps (2 full-size and 2 half-size) Dimensions [mm] H

B

D

Weight [kg]

1.1

0.75 "

Wall mounting

DOL

E

600

400

210

20

600

400

210

21

1.5

1.1 "

Wall mounting

DOL

E

600

400

210

20

600

400

210

21

2.2

1.1 "

Wall mounting

DOL

E

600

400

210

20

600

400

210

21

2.2

1.5

Wall mounting

DOL

E

600

400

210

20

600

400

210

21

3

1.5

Wall mounting

DOL

E

600

400

210

20

600

400

210

21

3

2.2

Wall mounting

DOL

E

600

400

210

20

600

400

210

21

4

2.2

Wall mounting

SD

E

600

600

210

31

600

600

210

33 33

4

3

Wall mounting

SD

E

600

600

210

31

600

600

210

5.5

3

Wall mounting

SD

E

600

600

210

31

600

600

210

33

5.5

4

Wall mounting

SD

E

600

600

210

32

600

600

210

33

7.5

4

Wall mounting

SD

E

600

600

210

32

600

600

210

65

7.5

5.5

Wall mounting

SD

E

600

600

210

32

600

600

210

65

11

5.5

Wall mounting

SD

E

600

600

210

32

600

600

210

65

11

7.5

Wall mounting

SD

E

600

600

210

32

600

600

210

65

15

7.5

Wall mounting

SD

E

1000

600

300

63

1000

800

300

66

15

11

Wall mounting

DOL

E

600

600

210

37

760

760

210

57

15

11

Wall mounting

SD

E

600

600

210

37

760

760

210

58

18.5

11

Wall mounting

DOL

E

600

600

210

38

760

760

210

58

18.5

11

Wall mounting

SD

E

600

600

210

38

760

760

210

59

18.5

15

Wall mounting

DOL

E

600

600

210

38

760

760

210

59

18.5

15

Wall mounting

SD

E

600

600

210

38

760

760

210

59

22

11

Wall mounting

DOL

E

600

600

210

40

1000

800

300

81

22

11

Wall mounting

SD

E

600

600

210

39

760

760

210

60

22

15

Wall mounting

DOL

E

1000

800

300

76

1000

800

300

81

22

15

Wall mounting

SD

E

760

760

210

57

760

760

210

60

22

18.5

Wall mounting

DOL

E

1000

800

300

76

1000

800

300

81

22

18.5

Wall mounting

SD

E

760

760

210

57

760

760

210

60 83

30

15

Wall mounting

DOL

E

1000

800

300

77

1000

800

300

30

15

Wall mounting

SD

E

100

800

300

76

1000

800

300

81

30

18.5

Wall mounting

DOL

E

1000

800

300

77

1000

800

300

83

30

18.5

Wall mounting

SD

E

1000

800

300

77

1000

800

300

81

30

22

Wall mounting

DOL

E

1000

800

300

78

1200

800

300

122

30

22

Wall mounting

SD

E

1000

800

300

77

1200

800

300

121

37

18.5

Wall mounting

DOL

E

1000

800

300

80

1200

800

300

129

37

18.5

Wall mounting

SD

E

1000

800

300

77

1200

800

300

124

37

22

Wall mounting

DOL

E

1000

800

300

81

1200

800

300

130

37

22

Wall mounting

SD

E

1000

800

300

78

1200

800

300

125

45

22

Wall mounting

DOL

E

1200

800

300

116

1200

800

300

130

45

22

Wall mounting

SD

E

1200

800

300

114

1200

800

300

125

Technical data

Control 2000

Control 2000 MES Motor [kW]

Mounting of control cabinet

Control 2000 MES for 2 pumps Starting full-size

Dimensions [mm] H

B

D

Control 2000 MES for 3 pumps

Weight [kg]

Dimensions [mm] H

B

D

Control 2000 MES for 4 pumps

Weight [kg]

Dimensions [mm] H

B

D

Weight [kg]

1.1

Wall mounting

E/DOL

600

400

210

20

600

400

210

20

600

600

210

1.1

Wall mounting

E/DOL

600

400

210

20

600

400

210

20

600

600

210

31 31

1.5

Wall mounting

E/DOL

600

400

210

20

600

400

210

21

600

600

210

31

2.2

Wall mounting

E/DOL

600

400

210

20

600

400

210

21

600

600

210

31

3

Wall mounting

E/DOL

600

400

210

20

600

400

210

21

600

600

210

31 34

4

Wall mounting

E/SD

600

600

210

31

600

600

210

33

600

600

210

5.5

Wall mounting

E/SD

600

600

210

31

600

600

210

33

600

600

210

34

7.5

Wall mounting

E/SD

600

600

210

31

600

600

210

33

1000

800

300

66

11

Wall mounting

E/DOL

600

400

210

25

600

600

210

37

600

600

210

38

11

Wall mounting

E/SD

600

600

210

36

600

600

210

38

600

600

210

41

15

Wall mounting

E/DOL

600

600

210

36

600

600

210

38

760

760

210

57

15

Wall mounting

E/SD

600

600

210

36

600

600

210

39

760

760

210

60

18.5

Wall mounting

E/DOL

600

600

210

37

760

760

210

57

760

760

210

60

18.5

Wall mounting

E/SD

600

600

210

37

760

760

210

58

760

760

210

62

22

Wall mounting

E/DOL

600

600

210

39

1000

800

300

80

1000

800

300

84

22

Wall mounting

E/SD

600

600

210

38

760

760

210

59

760

760

210

63

17

Technical data

Control 2000

Product numbers Product numbers for control cabinets with a PFU 2000 control panel.

The starting methods of the motors are:

Supply voltage: 3 x 400 V +6%/–10%, 50 Hz, N, PE.

• SD (Star-delta starting)

• DOL (Direct-on-line starting)

All motors must be three-phase. Enclosure class: IP 54.

Product numbers

Motor output [kW]

Mounting of control cabinet

0.37

Wall mount.

DOL

96 01 11 97

96 01 12 11

0.55

Wall mount.

DOL

96 01 11 98

96 01 12 12

0.75

Wall mount.

DOL

96 01 11 99

96 01 12 13

1.1

Wall mount.

DOL

96 01 12 00

96 01 12 14

!

18

Starting full-size

Control 2000 MS Control 2000 MS for 2 pumps

Control 2000 MS for 3 pumps

Control 2000 MS for 4 pumps

Control 2000 MS for 5 pumps

Control 2000 MS for 6 pumps

96 01 12 25

96 01 12 39

96 01 12 50

96 01 12 26

96 01 12 40

96 01 12 51

96 01 12 27

96 01 12 41

96 01 12 52

96 01 12 28

96 01 12 42

96 01 12 53 96 01 12 54

1.5

Wall mount.

DOL

96 01 12 01

96 01 12 15

96 01 12 29

96 01 12 43

2.2

Wall mount.

DOL

96 01 12 02

96 01 12 16

96 01 12 30

96 01 12 44

96 01 12 55

3

Wall mount.

DOL

96 01 12 03

96 01 12 17

96 01 12 31

96 01 12 45

96 01 12 56

4

Wall mount.

SD

96 01 12 04

96 01 12 18

96 01 12 32

96 01 12 46

96 01 12 57

5.5

Wall mount.

SD

96 01 12 05

96 01 12 19

96 01 12 33

96 01 12 47

96 01 12 58 !

7.5

Wall mount.

SD

96 01 12 06

96 01 12 20

96 01 12 34

96 01 12 48 !

96 01 12 59 !

11

Wall mount.

SD

96 01 12 07

96 01 12 21

96 01 12 35

96 01 12 49 !

96 01 13 58 !

15

Wall mount.

SD

96 01 12 08

96 01 12 22

96 01 12 36

96 01 14 09 !

96 01 14 12 !

18.5

Wall mount.

SD

96 01 12 09

96 01 12 23

96 01 12 37

96 01 14 10 !

96 01 14 13 !

22

Wall mount.

SD

96 01 12 10

96 01 12 24

96 01 12 38

96 01 14 11 !

96 01 14 14 !

30

Wall mount.

SD

96 01 24 46

96 01 24 47

96 01 24 48

96 01 24 49 !

96 01 24 50!

The control cabinet is prepared for floor mounting.

Technical data

Control 2000

Control 2000 MSH Motor output

Product numbers Mounting of control cabinet

Starting full-size

Starting half-size

Control 2000 MSH for 2 pumps (1 full-size and 1 half-size)

Control 2000 MSH for 3 pumps (2 full-size and 1 half-size)

Control 2000 MSH for 4 pumps (3 full-size and 1 half-size)

Full-size [kW]

Half-size [kW]

1.1

0.75

Wall mounting

DOL

DOL

96 01 12 60

96 01 12 72

96 01 12 83

1.5

1.1

Wall mounting

DOL

DOL

96 01 12 61

96 01 12 73

96 01 12 84

2.2

1.1

Wall mounting

DOL

DOL

96 01 12 62

96 01 12 74

96 01 12 85

3

1.5

Wall mounting

DOL

DOL

96 01 12 63

96 01 12 75

96 01 12 86

3

2.2

Wall mounting

DOL

DOL

96 01 20 43

96 01 20 48

96 01 20 53

4

2.2

Wall mounting

SD

DOL

96 01 12 64

96 01 12 76

96 01 12 87 96 01 20 56

4

3

Wall mounting

SD

DOL

96 01 20 46

96 01 20 51

5.5

3

Wall mounting

SD

DOL

96 01 20 21

96 01 12 77

96 01 12 88

5.5

4

Wall mounting

SD

SD

96 01 20 59

96 01 20 69

96 01 20 79

7.5

4

Wall mounting

SD

SD

96 01 12 67

96 01 12 78

96 01 12 89

7.5

5.5

Wall mounting

SD

SD

96 01 20 62

96 01 20 72

96 01 20 82

11

5.5

Wall mounting

SD

SD

96 01 12 68

96 01 12 79

96 01 12 90

11

7.5

Wall mounting

SD

SD

96 01 20 64

96 01 20 74

96 01 20 84

11

11

Wall mounting

SD

SD

96 01 20 66

96 01 20 76

96 01 20 86

15

7.5

Wall mounting

SD

SD

96 01 12 69

96 01 12 80

96 01 12 91

15

11

Wall mounting

SD

SD

96 01 20 16

96 01 20 18

96 01 20 20

18.5

11

Wall mounting

SD

SD

96 01 12 70

96 01 12 81

96 01 12 92

22

11

Wall mounting

SD

SD

96 01 12 71

96 01 12 82

96 01 12 93 96 01 24 70

22

15

Wall mounting

SD

SD

96 01 24 68

96 01 24 69

30

15

Wall mounting

SD

SD

96 01 24 71

96 01 24 72

96 01 24 73

30

18.5

Wall mounting

SD

SD

96 01 24 74

96 01 24 75

96 01 24 76

19

Technical data

Control 2000

Product numbers Product numbers for control cabinets with a PFU 2000 control panel.

The starting methods of the motors are:

Supply voltage: 3 x 400 V +6%/–10%, 50 Hz, N, PE.

• SD (Star-delta starting)

• DOL (Direct-on-line starting)

All motors must be three-phase. Enclosure class: IP 54.

Control 2000 MF Motor output [kW]

Mounting of control cabinet

0.37

Floor mount.

0.55

Floor mount.

Starting full-size

Product numbers Control 2000 MF for 2 pumps

Control 2000 MF for 3 pumps

Control 2000 MF for 4 pumps

Control 2000 MF for 5 pumps

Control 2000 MF for 6 pumps

DOL

96 01 13 74

96 01 13 82

96 01 13 90

96 01 13 99

96 01 14 08

DOL

96 01 13 67

96 01 13 75

96 01 13 83

96 01 13 91

96 01 14 00

0.75

Floor mount.

DOL

96 01 13 68

96 01 13 76

96 01 13 84

96 01 13 92

96 01 14 01

1.1

Floor mount.

DOL

96 01 13 69

96 01 13 77

96 01 13 85

96 01 13 93

96 01 14 02

1.5

Floor mount.

DOL

96 01 13 70

96 01 13 78

96 01 13 86

96 01 13 94

96 01 14 03

2.2

Floor mount.

DOL

96 01 13 71

96 01 13 79

96 01 13 87

96 01 13 95

96 01 14 04

3

Floor mount.

DOL

96 01 13 72

96 01 13 80

96 01 13 88

96 01 13 96

96 01 14 05

4

Floor mount.

SD

96 01 13 73

96 01 13 81

96 01 13 89

96 01 13 97

96 01 14 06

5.5

Floor mount.

SD

96 01 12 94

96 01 13 00

96 01 13 06

96 01 13 98

96 01 14 07

7.5

Floor mount.

SD

96 01 12 95

96 01 13 01

96 01 13 07

96 01 13 12

96 01 13 14

11

Floor mount.

SD

96 01 12 96

96 01 13 02

96 01 13 08

96 01 13 13

96 01 13 15

15

Floor mount.

SD

96 01 12 97

96 01 13 03

96 01 13 09

96 01 13 61

96 01 13 64

18.5

Floor mount.

SD

96 01 12 98

96 01 13 04

96 01 13 10

96 01 13 62

96 01 13 65

22

Floor mount.

SD

96 01 12 99

96 01 13 05

96 01 13 11

96 01 13 63

96 01 13 66

30

Floor mount.

SD

96 01 24 14

96 01 24 15

96 01 24 16

96 01 24 17

96 01 24 18

Control 2000 MFH Motor output

20

Product numbers

Full-size [kW]

Half-size [kW]

Mounting of control cabinet

Starting full-size

Starting half-size

Control 2000 MFH for 3 pumps (1 full-size and 2 half-size)

Control 2000 MFH for 4 pumps (2 full-size and 2 half-size)

3

2.2

Floor mounting

DOL

DOL

96 01 13 16

96 01 13 28

4

3

Floor mounting

SD

DOL

96 01 13 17

96 01 13 29

5.5

3

Floor mounting

SD

DOL

96 01 13 18

96 01 13 30

5.5

4

Floor mounting

SD

SD

96 01 13 19

96 01 13 31

7.5

4

Floor mounting

SD

SD

96 01 13 20

96 01 13 32

7.5

5.5

Floor mounting

SD

SD

96 01 13 21

96 01 13 33

11

5.5

Floor mounting

SD

SD

96 01 13 22

96 01 13 34

11

7.5

Floor mounting

SD

SD

96 01 13 23

96 01 13 35

15

7.5

Floor mounting

SD

SD

96 01 13 24

96 01 13 36

15

11

Floor mounting

SD

SD

96 01 13 25

96 01 13 37

18.5

11

Floor mounting

SD

SD

96 01 13 26

96 01 13 38

22

11

Floor mounting

SD

SD

96 01 20 33

96 01 20 35

22

15

Floor mounting

SD

E/SD

96 01 13 27

96 01 13 39

30

15

Floor mounting

SD

E/SD

96 01 24 30

96 01 24 31

30

18.5

Floor mounting

SD

E/SD

96 01 24 32

96 01 24 33

Technical data

Control 2000

Product numbers Product numbers for control cabinets with a PFU 2000 control panel.

The starting methods of the motors are:

Supply voltage: 3 x 400 V +6%/–10%, 50 Hz, N, PE.

• SD (Star-delta starting)

All motors must be three-phase.

• E (Electronic soft start via frequency converter).

• DOL (Direct-on-line starting)

Note: CRE-pumps marked with """ must be with singlephase mains connection. Enclosure class: IP 54.

Control 2000 ME Motor output [kW]

Mounting of control cabinet

Starting full-size

Product numbers Control 2000 ME for 2 pumps

Control 2000 ME for 3 pumps

Control 2000 ME for 4 pumps

1.1 "

Wall mounting

E

96 01 11 52

96 01 14 15

1.1

Wall mounting

E

96 01 20 89

96 01 20 90

96 01 23 15

1.5

Wall mounting

E

96 01 11 68

96 01 14 16

96 01 23 02

2.2

Wall mounting

E

96 01 11 69

96 01 14 17

96 01 23 03

3

Wall mounting

E

96 01 11 70

96 01 14 18

96 01 23 04

4

Wall mounting

E

96 01 11 71

96 01 14 19

96 01 23 05

5.5

Wall mounting

E

96 01 11 72

96 01 14 20

96 01 23 06

7.5

Wall mounting

E

96 01 23 87

96 01 23 88

96 01 23 89

11

Wall mounting

E

96 01 33 45

96 01 33 49

96 01 33 53

15

Wall mounting

E

96 01 33 46

96 01 33 50

96 01 33 54

18.5

Wall mounting

E

96 01 33 47

96 01 33 51

96 01 33 55

22

Wall mounting

E

96 01 33 48

96 01 33 52

96 01 33 56

21

Technical data

Control 2000

Control 2000 MEH Motor output

22

Full-size [kW]

Half-size [kW]

Product numbers

Mounting of control cabinet

Starting full-size

Starting half-size

Control 2000 MEH for 3 pumps (1 full-size and 2 half-size)

Control 2000 MEH for 4 pumps (2 full-size and 2 half-size)

1.1

0.75 "

Wall mounting

DOL

E

96 01 11 73

96 01 11 85

1.5

1.1 "

Wall mounting

DOL

E

96 01 11 74

96 01 11 86

2.2

1.1 "

Wall mounting

DOL

E

96 01 11 75

96 01 11 87

2.2

1.5

Wall mounting

DOL

E

96 01 11 76

96 01 11 88

3

1.5

Wall mounting

DOL

E

96 01 11 77

96 01 11 89

3

2.2

Wall mounting

DOL

E

96 01 11 78

96 01 11 90

4

2.2

Wall mounting

SD

E

96 01 11 79

96 01 11 91

4

3

Wall mounting

SD

E

96 01 11 80

96 01 11 92

5.5

3

Wall mounting

SD

E

96 01 11 81

96 01 11 93

5.5

4

Wall mounting

SD

E

96 01 11 82

96 01 11 94

7.5

4

Wall mounting

SD

E

96 01 11 83

96 01 11 95

7.5

5.5

Wall mounting

SD

E

96 01 13 59

96 01 13 60

11

5.5

Wall mounting

SD

E

96 01 11 84

96 01 11 96

11

7.5

Wall mounting

SD

E

96 01 23 91

96 01 23 95

15

7.5

Wall mounting

SD

E

96 01 23 93

96 01 23 97

15

11

Wall mounting

DOL

E

96 01 35 57

96 01 35 63

15

11

Wall mounting

SD

E

96 01 35 58

96 01 35 64

18.5

11

Wall mounting

DOL

E

96 01 35 59

96 01 35 65

18.5

11

Wall mounting

SD

E

96 01 35 60

96 01 35 66

18.5

15

Wall mounting

DOL

E

96 01 35 69

96 01 35 75

18.5

15

Wall mounting

SD

E

96 01 35 70

96 01 35 76

22

11

Wall mounting

DOL

E

96 01 35 61

96 01 35 67

22

11

Wall mounting

SD

E

96 01 35 62

96 01 35 68

22

15

Wall mounting

DOL

E

96 01 35 71

96 01 35 77

22

15

Wall mounting

SD

E

96 01 35 72

96 01 35 78

22

18.5

Wall mounting

DOL

E

96 01 35 81

96 01 35 87

22

18.5

Wall mounting

SD

E

96 01 35 82

96 01 35 88

30

15

Wall mounting

DOL

E

96 01 35 73

96 01 35 79

30

15

Wall mounting

SD

E

96 01 35 74

96 01 35 80

30

18.5

Wall mounting

DOL

E

96 01 35 83

96 01 35 89

30

18.5

Wall mounting

SD

E

96 01 35 84

96 01 35 90

30

22

Wall mounting

DOL

E

96 01 35 93

96 01 35 99

30

22

Wall mounting

SD

E

96 01 35 94

96 01 36 00

37

18.5

Wall mounting

DOL

E

96 01 35 85

96 01 35 91

37

18.5

Wall mounting

SD

E

96 01 35 86

96 01 35 92

37

22

Wall mounting

DOL

E

96 01 35 95

96 01 36 01

37

22

Wall mounting

SD

E

96 01 35 96

96 01 36 02

45

22

Wall mounting

DOL

E

96 01 35 97

96 01 36 03

45

22

Wall mounting

SD

E

96 01 35 98

96 01 36 04

Technical data

Control 2000

Product numbers for control cabinets with a PFU 2000 control panel.

The starting methods of the motors are:

Supply voltage: 3 x 400 V +6%/–10%, 50 Hz, N, PE.

• SD (Star-delta starting)

All motors must be three-phase.

• E (Electronic soft start via frequency converter).

• DOL (Direct-on-line starting)

Note: CRE-pumps marked with """ must be with single-phase mains connection. Enclosure class: IP 54.

Control 2000 MES Product numbers

Motor output [kW]

Mounting of control cabinet

Starting full-size

1.1 "

Wall mounting

E/DOL

96 01 13 40

96 01 13 46

96 01 13 52

1.1

Wall mounting

E/DOL

96 01 20 92

96 01 20 93

96 01 20 94

Control 2000 MES for 2 pumps

Control 2000 MES for 3 pumps

Control 2000 MES for 4 pumps

1.5

Wall mounting

E/DOL

96 01 13 41

96 01 13 47

96 01 13 53

2.2

Wall mounting

E/DOL

96 01 13 42

96 01 13 48

96 01 13 54

3

Wall mounting

E/DOL

96 01 13 43

96 01 13 49

96 01 13 55

4

Wall mounting

E/SD

96 01 13 44

96 01 13 50

96 01 13 56

5.5

Wall mounting

E/SD

96 01 13 45

96 01 13 51

96 01 13 57

7.5

Wall mounting

E/SD

96 01 23 99

96 01 24 01

96 01 24 03

11

Wall mounting

E/DOL

96 01 34 37

96 01 34 39

96 01 34 41

11

Wall mounting

E/SD

96 01 34 38

96 01 34 40

96 01 34 42

15

Wall mounting

E/DOL

96 01 34 43

96 01 34 45

96 01 34 47

15

Wall mounting

E/SD

96 01 34 44

96 01 34 46

96 01 34 48

18.5

Wall mounting

E/DOL

96 01 34 49

96 01 34 51

96 01 34 53

18.5

Wall mounting

E/SD

96 01 34 50

96 01 34 52

96 01 34 54

22

Wall mounting

E/DOL

96 01 34 55

96 01 34 57

96 01 34 59

22

Wall mounting

E/SD

96 01 34 56

96 01 34 58

96 01 34 60

23

General data

Delta Control 2000

System configuration

Each main group consists of subgroups, see the table below:

Grundfos Delta Control 2000 features two main groups and one variant:

Abbreviations:

1. Delta Control 2000 F uses a standard frequency converter and can be used together with pumps with standard motors. Delta Control 2000 F is divided into subgroups.

M: The Delta Control 2000 features a microprocessor for the control of all functions.

2. Delta Control 2000 E is used when the system comprises E-pumps (Grundfos pumps equipped with Grundfos MGE motors). Delta Control 2000 E is also divided into subgroups. (See table below).

E: Some or all of the pumps in the system are E-pumps (pumps with integrated frequency converter).

F: Frequency-converter control rotates among all pumps in the system.

H: The system has one or two half-size pumps. (One half-size pump provides approximately the same head as one full-size pump, but only approximately half the flow).

3. Delta Control 2000 ME (PO) should be used when a controller must be designed especially according to the customer’s needs. Delta Control 2000 ME (PO) contains only a PFU 2000 set up for the control of Grundfos MGE motors. The Delta Control 2000 ME (PO) controller is supplied without control cabinet, fuses, main switch, etc.

General data, Delta Control 2000 System configuration

Description of pumps

Delta Control 2000 E (variable speed)

Delta Control 2000 F (variable speed)

Main group

24

Sub group

MF

Size

Full-size

Number

Number of controlled pumps

Mode of operation

1

Speed control via frequency converter mounted in control cabinet.

All other pumps

Mains operation (on/off).

1

Speed control via frequnecy converter mounted in control cabinet.

All

Frequency-converter control rotates among all pumps in the system

Frequency-converter control alternates between the two pumps. The uncontrolled pump is mains operated (on/off).

Half-size

2

Full-size

All other pumps

Full-size

All

All

Speed control via frequency converter integrated in the motor.

All pumps in operation run at the same speed (cascade control).

Half-size

2

2

Speed control via frequency converter integrated in the motor.

The two pumps run at the same speed when both are in operation.

Full-size

All other pumps

MFH

ME

Comments

MEH

Mains operation (on/off).

Mains operation (on/off).

Functions

Functions Delta Control 2000 A standard Delta Control 2000 always includes the electronics unit PFU 2000 (Pump Functional Unit 2000) built into the control cabinet. The PFU 2000 front cover with reset button and indicator lights is mounted in the front door of the control cabinet. Alternatively, the Delta Control 2000 can be supplied with the PMU 2000 (Pump Management Unit 2000) mounted in the front door of the control cabinet. The PMU 2000 enables the read-out of operating data and the optimisation of operation according to system conditions. The Delta Control 2000 without PMU 2000 offers the following functions: • Control according to a constant differential pressure or a constant flow. • Automatic changeover to mains operation in case of defective frequency converter (Delta Control 2000 F only). • Automatic cascade control of pumps.

Delta Control 2000

• Possibility of digital remote-control functions: –system on/off, –reduced operation, –setpoint control with two-point switch, –setpoint control with three-point switch, –alternative setpoint. • Pump and system monitoring functions: –minimum and maximum limits of actual value, –motor protection. • Display and indication functions: –2 x 24 character LCD display, –green indicator light for operating indications and red indicator light for fault indications, –potential-free changeover contacts for operation and fault. • Clock functions. • Grundfos BUS communication.

PCU 2000 A PCU 2000 (Pump Communication Unit 2000) can be connected to the Delta Control 2000 via the BUS input. The PCU 2000 enables remote operating and fault indication for each individual pump. The PCU 2000 also enables external setpoint influence and system on/off.

• Possibility of setpoint influence: –proportional influence (proportional pressure), –external setpoint influence. • Possibility of remote control: –system on/off. • Pump and system monitoring functions: –motor protection.

Functions, Delta Control 2000

Functions

• Display and indication functions: –green indicator light for operating indications and red indicator light for fault indications, –potential-free changeover contacts for operation and fault. • Grundfos BUS communication. The Delta Control 2000 with PMU 2000 offers the following functions: • Pump control based on differential pressure, differential temperature, temperature, flow or level. • Automatic changeover to mains operation in case of defective frequency converter (Delta Control 2000 F only). • Automatic cascade control of pumps. • Selection of switching sequences, automatic pump changeover and pump priority. • Manual operation. • Possibility of setpoint influence: –proportional influence (proportional pressure), –external setpoint influence.

25

Functions

Delta Control 2000

Type key Example Type range Supgroup: MF - MFH - ME - MEH Number of full-size pumps 1 - 4 Power, full-size pumps [kW] Starting method of full size pumps: DOL: Direct-on-line starting SD: Star-delta starting E: Electronic soft start (MGE motor) Number of half-size pumps 1 - 2 Power, half-size pumps [kW] Starting method of half-size pumps: DOL: Direct-on-line starting SD: Star-delta starting E: Electronic soft start (MGE motor) Control panel: PMU: PMU 2000 PFU: PFU 2000 Supply voltage/frequency Enclosure class: IP 54 IP 00

26

Control 2000

MEH

2

x 5.5

SD

+

2

x 3.0

E

PMU

3 x 400/230 V, 50 Hz

IP 54

27

Functions

Delta Control 2000

Examples of functioning The following table shows examples of Delta Control 2000 systems using constant differential pressure control.

Variable speed GRUNDFOS Delta Control 2000 MF

GRUNDFOS Delta Control 2000 MFH

PFU 2000

P

TM01 1025 3397

TM01 1024 3397

PFU 2000

P

One pump in operation via The half-size pump in operafrequency converter. tion via frequency converter.

Q

TM01 1086 3697

H set

One pump in operation via frequency converter. Two pumps are mains-operated (on/off).

H set

Q

TM01 1088 3697

H

H

One half-size pump in operation via frequency converter. One full-size pump is mainsoperated (on/off).

Q

TM01 1087 3697

H set

H set

Q

TM01 1089 3697

H

H

• Maintains a constant dif- • Maintains a constant differential pressure through ferential pressure through continuously variable adcontinuously variable adjustment of the speed of justment of the speed of one pump. The other one half-size pump. The mains-operated pumps orher pumps are mainsare cut in/out according operated. to the demand. • The half-size pump con• The pump controlled by trolled by the frequency the frequency converter converter always starts always starts first. first. • Pump changeover is auto- • Pump changeover is automatic and depends on matic and depends on load, time and fault. load, time and fault. • All pumps will be controlled by the frequency converter in rotation.

28

Functions

Delta Control 2000

Examples of functioning, cont. The following table shows examples of Delta Control 2000 systems using constant differential pressure control.

Variable speed GRUNDFOS Delta Control 2000 MEH

GRUNDFOS Delta Control 2000 ME

PFU 2000

GRUNDFOS Delta Control ME (PO)

PFU 2000

MGE

MGE

One pump in operation.

P

MGE

MGE

P

MGE

MGE

TM01 2701 2298

MGE

TM01 1027 3397

P

TM01 1026 3397

PFU 2000

MGE

The half-size pump with MGE One half-size pump with motor in operation. MGE motor in operation. H

H

Three pumps in operation.

Q

H set

Q

TM01 1093 3697

Q

H set

TM01 1093 3697

H set

TM01 1090 3697

H

One half-size pump with MGE One half-size pump with MGE motor and the full-size pump motor and the full-size pump in operation. in operation. H

H

Q

H set

Q

TM01 1093 3697

Q

H set

TM01 1093 3697

H set

TM01 1091 3697

H

• Maintains a constant • Maintains a constant • Maintains a constant pressure through continupressure through continupressure through continuously variable adjustously variable adjustously variable adjustment of the speed of the ment of the speed of the ment of the speed of the pumps connected. two half-size pumps with pumps connected. MGE motors, while the • The system performance • The system performance full-size pump is mainsis adjusted to the demand is adjusted to the demand operated. (on/off). through cutting in/out through cutting in/out the required number of • The half-size pumps althe required number of pumps and through paralways start first. pumps and through parallel control of the pumps in • Pump changeover is autolel control of the pumps in operation. operation. matic and depends on • Pump changeover is automatic and depends on load, time and fault.

load, time and fault.

• Pump changeover is automatic and depends on load, time and fault.

29

Functions

Delta Control 2000

Control parameters Systems without PMU 2000

Setpoint:

Controllers without the PMU 2000 can be used in systems having small time constants and are pre-set to the control parameter "differential pressure". However, they can also be used with other control parameters, such as "flow" etc.

The setpoint is set by means of the function selector in the PFU 2000. It is also possible to stop all pumps, or to set all pumps to operate at maximum performance. Function selector in the PFU 2000

Differential pressure

Setpoint

PFU 2000 0%

100% MAX

TM00 5217 2796

P

TM01 1124 3897

STOP

Remote setpoint setting: A 0 - 10 V or 0 - 20 mA signal can be connected for remote setpoint setting.

Flow Setpoint via external signals

PFU 2000

Cascade control: Cascade control ensures automatic adjustment of performance to the system demand by cutting in/out the required number of pumps. The controller will operate the system with as few pumps as possible.

0

10 V 10V10V 20mA

The locally set setpoint is set by means of the function selector in the PFU 2000.

Sensor input: Sensors giving the following analog signals can be connected:

Automatic pump changeover:

– 0 - 10 V,

Automatic pump changeover is made as follows:

– 0 - 20 mA,

• Fault-dependent pump changeover. If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on.

– 4 - 20 mA.

• Time-dependent pump changeover. This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function.

A potential-free contact for external start/stop of all pumps can be connected.

Test run: To eliminate the risk of pump seizure caused by long periods of standstill, a test run lasting 1 second is carried out once every 24 hours.

30

100% 100% Locally set set setpoint Locally setpoint TM00 7048 0296

TM01 1125 3897

FT

Transmitter Transmitterrange range

Current setpoint Actual setpoint

Input for external start/stop:

Functions

Delta Control 2000

Systems with PMU 2000 The PMU 2000 is designed for the control of various pumps or pumping systems. As an example, the PMU 2000 can be used for the control of GRUNDFOS circulator pumps of the UPE type and pumping systems and controllers based on the PFU 2000, such as the Delta Control 2000. The control parameters offered by the Delta Control 2000 are shown in the table below:

PMU 2000 BUS

T

Possible with controller

Control parameters

without PMU

with PMU





1

Differential pressure

2

Differential temperature



3

Flow-pipe temperature with one sensor



4

Return-pipe temperature with one sensor



5

Differential temperature with one sensor signal



TM00 2719 3897

PFU 2000

Fig. 4 Differential temperature PMU 2000



BUS BUS PFU 2000

TM01 1257 4097

Fig.

Return-pipe temperature



6

Flow

7

Level



8

Open loop (uncontrolled)



T

Fig. 5 Differential pressure

Flow

PMU 2000

PMU 2000

BUS BUS

BUS BUS

PFU 2000

Fig. 1

TM00 2715 3897

P

TM00 4985 4894

PFU 2000

FT

Fig. 6 Differential temperature

Level PMU 2000

PMU 2000 BUS BUS

BUS BUS

PFU 2000

TM00 4998 3897

T

Fig. 2

h

Fig. 7 Flow-pipe temperature

Open loop

PMU 2000

PMU 2000

BUS BUS

TM00 2718 3897

T

PFU 2000

TM00 4986 4894

BUS BUS

PFU 2000

Fig. 3

TM01 1123 3897

LT

PFU 2000

Fig. 8

31

Functions

Delta Control 2000

Cascade control ensures automatic adjustment of performance to the system demand by cutting in/out the required number of pumps. The controller will operate the system with as few pumps as possible. The on/off rate is limited by setting the switching sequences.

The actual flow is estimated based on internal operating data without the flow being measured directly. Friction loss compensation H H

Setpoint Setpoint max max . 100 100 %%

6060 %%

Automatic pump changeover: Automatic pump changeover is made as follows: • Fault-dependent pump changeover. If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on. • Time-dependent pump changeover. This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function. Test run: To eliminate the risk of pump seizure caused by long periods of standstill, a test run lasting 1 second is carried out once every 24 hours. Clock functions: If the system demand varies during the day and/or during the week, the pump performance required will also vary. In this case, a clock program can be set in order to achieve optimum performance of the pumps. It is possible to set a total of 10 switching times, all having individual setpoints. Clock program with three switching times Setpoint Setpoint

Remote setpoint setting: In view of optimizing system operation, it is often best for the system to operate according to a variable setpoint instead of a constant setpoint. The selected settings influencing the setpoint will reduce "setpoint max". The following possibilities are available: • "extern" (%) An external analog signal or potential-free contact influences the setpoint in accordance with a table. • "timer" (minutes) An internal timer program in the PMU 2000 controls the setpoint in accordance with a table. • "Temp Tf" (°C, °F) The flow-pipe temperature controls the setpoint in accordance with a table. • "Temp Tr" (°C, °F) The return-pipe temperature controls the setpoint in accordance with a table. • "Temp To" (°C, °F) The ambient temperature controls the setpoint in accordance with a table.

C

1

2

3

Time Time

TM00 4989 4894

B A

Standby pumps:

• "level" (m, cm, ft, in) The level signal controls the setpoint in accordance with a table. • "flow" (m3/h, l/h, l/s, gpm) The flow signal controls the setpoint in accordance with a table. Example of application: Differential pressure drop compensation in circulation system if a flow meter signal is available.

In systems with more than one pump, standby pumps can be selected. A standby pump is started only if one of the duty pumps is faulty. Example: In a system with four pumps, of which one pump has been selected as standby-pump, the maximum number of pumps in operation at the same time will be three. The standby pump is started only if one of the duty pumps is faulty.

• "flow/I" (%), (applies only to Delta Control 2000 F) An internal flow signal controls the setpoint in accordance with a table. Example of application: Differential pressure drop compensation in circulation system if no flow meter signal is available.

Setpoint:

Sensor input:

The max. setpoint is set in the PMU 2000 menu

Sensors giving the following analog signals can be connected:

Set A Setpoint max.

32

Q Q

TM00 4991 4894

Cascade control:

12.5 bar

– 0 - 10 V,

Friction loss compensation:

– 0 - 20 mA,

The control unit is capable of compensating for friction loss. The setpoint increases from an adjustable percentage at zero flow to 100% at max. flow.

– 4 - 20 mA.

Technical data

Delta Control 2000

Dimensions and weights Dimensions and weights are for control cabinets with a PFU 2000 control panel. All motors must be three-phase.

Delta

H

l 2000 Contro

The starting methods of the motors are: TM01 0473 2402

• DOL (Direct-on-line starting) • SD (Star-delta starting) • E (Electronic soft start via frequency converter).

B

D

Delta Control 2000 MF Motor [kW]

Mounting of control Starting cabinet full-size

Delta Control 2000 MF for 1 pump Dimensions [mm]

Weight [kg]

Delta Control 2000 MF for 2 pumps Dimensions [mm]

Weight [kg]

Delta Control 2000 MF for 3 pumps Dimensions [mm]

Weight [kg]

Delta Control 2000 MF for 4 pumps Dimensions [mm]

Weight [kg]

H

B

D

H

B

D

H

B

D

H

B

D

0.75

Floor mount.

DOL

1000

800

300

78

1000

800

300

79

1000

800

300

80

1000

800

300

81

1.1

Floor mount.

DOL

1000

800

300

78

1000

800

300

79

1000

800

300

80

1000

800

300

81

1.5

Floor mount.

DOL

1000

800

300

78

1000

800

300

79

1000

800

300

80

1000

800

300

81

2.2

Floor mount.

DOL

1000

800

300

78

1000

800

300

79

1000

800

300

80

1000

800

300

81

DOL

1000

800

300

78

1000

800

300

79

1000

800

300

80

1000

800

300

81

SD

1000

800

300

78

1000

800

300

80

1200

800

300

95

1200

1000

300

113 103

3

Floor mount.

4

Floor mount.

5.5

Floor mount.

7.5

Floor mount.

11

Floor mount.

15

Floor mount.

18.5

Floor mount.

22

Floor mount.

30

Floor mount.

37

Floor mount.

45 55 75

Floor mount. Floor mount. Floor mount.

DOL

1200

800

300

100

1200

800

300

101

1200

800

300

102

1200

800

300

SD

1200

800

300

100

1200

800

300

102

1200

800

300

104

1200

1000

300

122

DOL

1200

800

300

100

1200

800

300

101

1200

800

300

103

1200

800

300

104 122

SD

1200

800

300

100

1200

800

300

103

1200

800

300

105

1200

1000

300

DOL

1200

800

300

92

1200

800

300

93

1200

800

300

94

1200

800

300

96

SD

1200

800

300

92

1200

800

300

94

1200

800

300

96

1200

1000

300

114

DOL

1900

800

400

168

1900

800

400

172

1900

1000

400

202

1900

1000

400

205

SD

1900

800

400

171

1900

800

400

174

1900

1000

400

204

1900

1000

400

208

DOL

1900

800

400

174

1900

800

400

179

1900

1000

400

206

1900

1000

400

209

SD

1900

1000

400

200

1900

1000

400

204

1900

1200

400

244

1900

1200

400

247

DOL

1900

1000

400

207

1900

1000

400

212

1900

1200

400

253

1900

1200

400

258 306

SD

1900

1000

400

208

1900

1000

400

213

1900

1600

400

301

1900

1600

400

DOL

1900

1000

400

208

1900

1000

400

213

1900

1200

400

253

1900

1200

400

258

SD

1900

1000

400

208

1900

1000

400

214

1900

1600

400

303

1900

1600

400

310

DOL

1900

1200

400

262

1900

1200

400

260

1900

1800

400

409

1900

2000

400

441

SD

1900

1200

400

264

1900

1200

400

264

1900

1800

400

414

1900

2200

400

499 449

DOL

1900

1200

400

269

1900

1200

400

266

1900

1800

400

416

1900

2000

400

SD

1900

1200

400

271

1900

1200

400

271

1900

1800

400

424

1900

2200

400

510

DOL

1900

1200

400

269

1900

1800

400

403

1900

1800

400

416

1900

2000

400

449

SD

1900

1200

400

271

1900

1800

400

408

1900

1800

400

424

1900

2200

400

510

DOL

1900

2000

500

552

1900

2200

500

612

1900

2600

500

690

1900

3000

500

794

SD

1900

2000

500

553

1900

2200

500

614

1900

2600

500

693

1900

3000

500

794

DOL

1900

2000

500

554

1900

2200

500

616

1900

2600

500

697

1900

3000

500

802

SD

1900

2000

500

556

1900

2200

500

618

1900

2600

500

700

1900

3000

500

804

Technical data, Delta Control 2000

33

Technical data

Delta Control 2000

Dimensions and weights Dimensions and weights are for control cabinets with a PFU 2000 control panel. Delta

H

l 2000 Contro

D

TM01 0473 2402

All motors must be three-phase.

B

Delta Control 2000 MFH Delta Control 2000 MFH for 3 pumps (1 full-size and 2 half-size)

Motor

34

Full-size [kW]

Mounting of control cabinet

11

Floor mounting

15

Floor mounting

15

Floor mounting

18.5

Floor mounting

11

22

Floor mounting

11

22

Floor mounting

15

30

Floor mounting

15

30

Floor mounting

18.5

37

Floor mounting

18.5

37

Floor mounting

45

Floor mounting

55

Floor mounting

75

Floor mounting

75

Floor mounting

Half-size [kW] 7.5 7.5 11

22 30 30 37 45

Delta Control 2000 MFH for 4 pumps (2 full-size and 2 half-size)

Starting full-size

Starting half-size H

B

D

H

B

D

DOL

DOL

1200

800

300

95

1200

800

300

SD

SD

1200

1000

300

97

1200

1000

300

123

DOL

DOL

1200

1000

300

115

1200

1000

300

118

Dimensions [mm]

Weight [kg]

Dimensions [mm]

Weight [kg] 100

SD

SD

1200

1000

300

118

1200

1000

300

125

DOL

DOL

1900

1000

400

202

1900

1000

400

205 208

SD

SD

1900

1000

400

205

1900

1000

400

DOL

DOL

1900

1000

400

204

1900

1000

400

207

SD

SD

1900

1000

400

205

1900

1000

400

209

DOL

DOL

1900

1000

400

204

1900

1000

400

207

SD

SD

1900

1000

400

206

1900

1000

400

210

DOL

DOL

1900

1200

400

207

1900

1000

400

210

SD

SD

1900

1200

400

244

1900

1200

400

248

DOL

DOL

1900

1600

400

208

1900

1400

400

320

SD

SD

1900

1200

400

247

1900

1600

400

299

DOL

DOL

1900

1600

400

218

1900

1400

400

330

SD

SD

1900

1600

400

304

1900

1600

400

308

DOL

DOL

1900

1000

400

218

1900

1400

400

330

SD

SD

1900

1600

400

305

1900

1600

400

310

DOL

DOL

1900

1000

400

254

1900

1400

400

330

SD

SD

1900

1600

400

305

1900

1600

400

310

DOL

DOL

1900

1600

400

319

1900

1600

400

323

SD

SD

1900

1600

400

325

1900

1600

400

331

DOL

DOL

1900

1600

400

323

1900

1600

400

330

SD

SD

1900

1600

400

325

1900

1600

400

333

DOL

DOL

1900

1600

400

330

1900

1600

400

339

SD

SD

1900

1800

400

424

1900

1800

400

431

DOL

DOL

1900

1600

400

330

1900

1600

400

339

SD

SD

1900

1800

400

424

1900

1800

400

431

Technical data

Delta Control 2000

Dimensions and weights Dimensions and weights are for control cabinets with a PFU 2000 control panel. All motors must be three-phase.

H

Note: E-pumps marked with """ must be with singlephase mains connection.

D

TM00 9394 2402

2000 Control Delta

B

Delta Control 2000 ME Motor [kW]

Starting full-size [kW]

Delta Control 2000 ME for 1 pump

Delta Control 2000 ME for 2 pumps

Delta Control 2000 ME for 3 pumps

Delta Control 2000 ME for 4 pumps

Dimensions [mm]

Dimensions [mm]

Dimensions [mm]

Dimensions [mm]

H

B

D

Weight [kg]

H

B

D

Weight [kg]

H

B

D

Weight [kg]

H

B

D

Weight [kg]

1.1 "

E

380

380

210

15.0

380

380

210

14.2

600

380

210

19.8

600

380

210

1.1

E

380

380

210

15.0

380

380

210

14.2

600

380

210

19.8

600

380

210

20.1

1.5

E

600

380

210

23.0

600

380

210

19.8

600

380

210

20.2

600

380

210

20.6

20.1

2.2

E

600

380

210

23.0

600

380

210

19.8

600

380

210

20.2

600

380

210

20.6

3

E

600

380

210

23.0

600

380

210

19.8

600

380

210

20.2

600

380

210

20.6

4

E

600

380

210

23.0

600

380

210

19.8

600

380

210

20.2

600

380

210

20.6

5.5

E

600

380

210

24.0

600

380

210

19.8

600

380

210

20.2

600

380

210

20.9

7.5

E

600

380

210

24.0

600

380

210

35.0

600

380

210

36.0

600

600

210

47.0

11

E

600

380

210

24.0

600

380

210

35.0

600

380

210

37.0

600

600

210

48.0 67.0

15

E

600

380

210

24.0

600

380

210

36.0

600

600

210

47.0

760

760

210

18.5

E

600

380

210

24.0

600

380

210

36.0

760

760

210

66.0

760

760

210

67.0

22

E

600

380

210

25.0

600

600

210

47.0

760

760

210

67.0

760

760

210

68.0

35

Technical data

Delta Control 2000

Delta Control 2000 MEH Delta Control 2000 MEH for 3 pumps (1 full-size and 2 half-size)

Motor Fullsize [kW]

Mounting of control cabinet

Halfsize [kW]

Starting full-size

Starting half-size

Dimensions [mm] H

B

D

Weight [kg]

Delta Control 2000 MEH for 4 pumps (2 full-size and 2 half-size) Dimensions [mm] H

B

D

Weight [kg]

1.1

Wall mount.

0.75 "

DOL

E

600

380

210

20.1

600

380

210

20.6

1.5

Wall mount.

1.1 "

DOL

E

600

380

210

20.1

600

380

210

20.6

2.2

Wall mount.

1.1 "

DOL

E

600

380

210

20.1

600

380

210

20.6

2.2

Wall mount.

1.5

DOL

E

600

380

210

20.3

600

380

210

20.9

3

Wall mount.

1.5

DOL

E

600

380

210

20.3

600

380

210

20.9

SD

E

600

380

210

20.3

600

380

210

22.3

DOL

E

600

380

210

20.3

600

380

210

20.9 22.3

3

Wall mount.

2.2

4

Wall mount.

2.2

4

Wall mount.

3

5.5

Wall mount.

3

5.5

Wall mount.

4

7.5

Wall mount.

4

11

Wall mount.

5.5

15

Wall mount.

11

18.5

Wall mount.

11

22

Wall mount.

11

18.5 22 22

Wall mount. Wall mount. Wall mount.

15 15 18.5

SD

E

600

380

210

20.3

600

380

210

DOL

E

600

380

210

31.1

600

380

210

31.1

SD

E

600

600

210

31.1

600

600

210

32.5

DOL

E

600

380

210

31.1

600

380

210

31.1

SD

E

600

600

210

31.1

600

600

210

32.5

DOL

E

600

600

210

31.1

600

600

210

31.1

SD

E

600

600

210

31.1

600

600

210

32.9

DOL

E

600

600

210

31.5

600

600

210

31.5

SD

E

600

600

210

31.5

600

600

210

32.9

DOL

E

600

600

210

31.5

1000

800

300

31.5

SD

E

600

600

210

31.5

1000

800

300

65.0

DOL

E

600

600

210

31.5

1000

800

300

31.5

SD

E

600

600

210

31.5

1000

800

300

65.0

DOL

E

600

600

210

47.0

760

760

210

67.0

SD

E

600

600

210

48.0

760

760

210

68.0

DOL

E

600

600

210

48.0

760

760

210

69.0

SD

E

600

600

210

48.0

760

760

210

69.0 91.0

DOL

E

600

600

210

50.0

1000

800

300

SD

E

600

600

210

49.0

760

760

210

70.0

DOL

E

600

600

210

49.0

760

760

210

69.0

SD

E

600

600

210

49.0

760

760

210

70.0

DOL

E

1000

800

300

86.0

1000

800

300

91.0

SD

E

760

760

210

67.0

760

760

210

71.0

DOL

E

1000

800

300

86.0

1000

800

300

91.0

SD

E

760

760

210

67.0

1000

800

300

71.0

Delta Control 2000 MES

36

Delta Control 2000 MES for 2 pumps

Delta Control 2000 MES for 3 pumps

Delta Control 2000 MES for 4 pumps

Motor [kW]

Mounting of control cabinet

Starting full-size H

B

D

H

B

D

H

B

D

11

Wall mount.

E/DOL

600

380

210

36.0

600

600

210

47.0

600

600

210

11

Wall mount.

E/SD

600

600

210

46.0

600

600

210

48.0

600

600

210

51.0

15

Wall mount.

E/DOL

600

600

210

46.0

600

600

210

48.0

760

760

210

67.0 70.0

Dimensions [mm]

Weight [kg]

Dimensions [mm]

Weight [kg]

Dimensions [mm]

Weight [kg] 49.0

15

Wall mount.

E/SD

600

600

210

47.0

600

600

210

49.0

760

760

210

18.5

Wall mount.

E/DOL

600

600

210

47.0

760

760

210

68.0

760

760

210

71.0

18.5

Wall mount.

E/SD

600

600

210

48.0

760

760

210

68.0

760

760

210

72.0

22

Wall mount.

E/DOL

600

600

210

50.0

1000

800

300

90.0

1000

800

300

94.0

22

Wall mount.

E/SD

600

600

210

49.0

760

760

210

70.0

760

760

210

73.0

Technical data

Delta Control 2000

Dimensions and weights The Delta Control 2000 ME (PO) is prepared for DIN-rail mounting.

Delta Control 2000 ME (PO) Weight [kg]

Version

Net weight

Gross Weight

1.4

1.7

Delta Control 2000 ME (PO)

200

150 200 80

98

60

ø5

TM00 2734 2402

140

37

Technical data

Delta Control 2000

Product numbers

Enclosure class: IP 54.

Product numbers for control cabinets with a PFU 2000 control panel.

The starting methods of the motors are: • DOL (Direct-on-line starting) • SD (Star-delta starting).

All motors must be three-phase. Supply voltage: 3 x 400 V +6%/–10%, N, 50 Hz, PE.

Delta Control 2000 MF Mounting of Control Cabinet

Starting full-size

0.75

Floor mounting

DOL

96 01 15 15

96 01 15 45

96 01 15 75

96 01 16 05

1.1

Floor mounting

DOL

96 01 15 16

96 01 15 46

96 01 15 76

96 01 16 06

Delta Control 2000 MF for 1 pump

Delta Control 2000 MF for 2 pumps

Delta Control 2000 MF for 3 pumps

Delta Control 2000 MF for 4 pumps

1.5

Floor mounting

DOL

96 01 15 17

96 01 15 47

96 01 15 77

96 01 16 07

2.2

Floor mounting

DOL

96 01 15 18

96 01 15 48

96 01 15 78

96 01 16 08

3

Floor mounting

DOL

96 01 15 19

96 01 15 49

96 01 15 79

96 01 16 09

SD

96 01 15 32

96 01 15 62

96 01 15 92

96 01 16 22

DOL

96 01 15 20

96 01 15 50

96 01 15 80

96 01 16 10 96 01 16 23

4

Floor mounting

5.5

Floor mounting

7.5

Floor mounting

11 15

Floor mounting Floor mounting

18.5

Floor mounting

22

Floor mounting

30

Floor mounting

37

Floor mounting

45 55 75

38

Product numbers

Motor [kW]

Floor mounting Floor mounting Floor mounting

SD

96 01 15 33

96 01 15 63

96 01 15 93

DOL

96 01 15 21

96 01 15 51

96 01 15 81

96 01 16 11

SD

96 01 15 34

96 01 15 64

96 01 15 94

96 01 16 24

DOL

96 01 15 22

96 01 15 52

96 01 15 82

96 01 16 12

SD

96 01 15 35

96 01 15 65

96 01 15 95

96 01 16 25

DOL

96 01 15 23

96 01 15 53

96 01 15 83

96 01 16 13

SD

96 01 15 36

96 01 15 66

96 01 15 96

96 01 16 26

DOL

96 01 15 24

96 01 15 54

96 01 15 84

96 01 16 14

SD

96 01 15 37

96 01 15 67

96 01 15 97

96 01 16 27

DOL

96 01 15 25

96 01 15 55

96 01 15 85

96 01 16 15

SD

96 01 15 38

96 01 15 68

96 01 15 98

96 01 16 28

DOL

96 01 15 26

96 01 15 56

96 01 15 86

96 01 16 16

SD

96 01 15 39

96 01 15 69

96 01 15 99

96 01 16 29

DOL

96 01 15 27

96 01 15 57

96 01 15 87

96 01 16 17

SD

96 01 15 40

96 01 15 70

96 01 16 00

96 01 16 30

DOL

96 01 15 28

96 01 15 58

96 01 15 88

96 01 16 18

SD

96 01 15 41

96 01 15 71

96 01 16 01

96 01 16 31

DOL

96 01 15 29

96 01 15 59

96 01 15 89

96 01 16 19

SD

96 01 15 42

96 01 15 72

96 01 16 02

96 01 16 32

DOL

96 01 15 30

96 01 15 60

96 01 15 90

96 01 16 20 96 01 16 33

SD

96 01 15 43

96 01 15 73

96 01 16 03

DOL

96 01 15 31

96 01 15 61

96 01 15 91

96 01 16 21

SD

96 01 15 44

96 01 15 74

96 01 16 04

96 01 16 34

Technical data

Delta Control 2000

Product numbers

Enclosure class: IP 54. The starting methods of the motors are:

Product numbers for control cabinets with a PFU 2000 control panel.

• DOL (Direct-on-line starting) • SD (Star-delta starting).

All motors must be three-phase. Supply voltage: 3 x 400 V +6%/–10%, N, 50 Hz, PE.

Delta Control 2000 MFH Motor Full-size [kW]

Half-size [kW]

Mounting of Control Cabinet

11

7.5

Floor mounting

15 15 18.5 22 22 30 30

7.5 11 11 11 15 15 18.5

Floor mounting Floor mounting Floor mounting Floor mounting Floor mounting Floor mounting Floor mounting

37

18.5

Floor mounting

37

22

Floor mounting

45

22

Floor mounting

55

30

Floor mounting

75

37

Floor mounting

75

45

Floor mounting

Product numbers Starting full-size

Starting half-size

DOL SD DOL

Delta Control 2000 MFH for 3 pumps (1 full-size and 2 half-size)

Delta Control 2000 MFH for 4 pumps (2 full-size and 2 half-size)

DOL

96 01 16 35

96 01 16 63

SD

96 01 16 49

96 01 16 77

DOL

96 01 16 36

96 01 16 64

SD

SD

96 01 16 50

96 01 16 78

DOL

DOL

96 01 16 37

96 01 16 65

SD

SD

96 01 16 51

96 01 16 79

DOL

DOL

96 01 16 38

96 01 16 66

SD

SD

96 01 16 52

96 01 16 80

DOL

DOL

96 01 16 39

96 01 16 67

SD

SD

96 01 16 53

96 01 16 81

DOL

DOL

96 01 16 40

96 01 16 68

SD

SD

96 01 16 54

96 01 16 82

DOL

DOL

96 01 16 41

96 01 16 69

SD

SD

96 01 16 55

96 01 16 83

DOL

DOL

96 01 16 42

96 01 16 70 96 01 16 84

SD

SD

96 01 16 56

DOL

DOL

96 01 16 43

96 01 16 71

SD

SD

96 01 16 57

96 01 16 85

DOL

DOL

96 01 16 44

96 01 16 72

SD

SD

96 01 16 58

96 01 16 86

DOL

DOL

96 01 16 45

96 01 16 73

SD

SD

96 01 16 59

96 01 16 88

DOL

DOL

96 01 16 46

96 01 16 74

SD

SD

96 01 16 60

96 01 16 88

DOL

DOL

96 01 16 47

96 01 16 75

SD

SD

96 01 16 61

96 01 16 89

DOL

DOL

96 01 16 48

96 01 16 76

SD

SD

96 01 16 62

96 01 16 90

39

Technical data

Delta Control 2000

Product numbers

Enclosure class: IP 54.

Product numbers for control cabinets with a PFU 2000 control panel.

The starting methods of the motors are: • DOL (Direct-on-line starting) • SD (Star-delta starting).

All motors must be three-phase Note: E-pumps marked with """ must be with singlephase mains connection. Supply voltage: 3 x 400 V +6%/–10%, N, 50 Hz, PE.

Delta Control 2000 ME

40

Product numbers

Motor [kW]

Mounting of control cabinet

1.1 "

Wall mounting

E

96 01 14 88

96 01 14 95

96 01 15 02

96 01 15 09

1.1

Wall mounting

E

96 01 90 70

96 01 90 78

96 01 90 86

96 01 90 94 96 01 15 10

Starting full-size

Delta Control 2000 ME for 1 pump

Delta Control 2000 ME for 2 pumps

Delta Control 2000 ME for 3 pumps

Delta Control 2000 ME for 4 pumps

1.5

Wall mounting

E

96 01 14 89

96 01 14 96

96 01 15 03

2.2

Wall mounting

E

96 01 14 90

96 01 14 97

96 01 15 04

96 01 15 11

3

Wall mounting

E

96 01 14 91

96 01 14 98

96 01 15 05

96 01 15 12

4

Wall mounting

E

96 01 14 92

96 01 14 99

96 01 15 06

96 01 15 13

5.5

Wall mounting

E

96 01 14 93

96 01 15 00

96 01 15 07

96 01 15 14

7.5

Wall mounting

E

96 01 52 97

96 01 25 91

96 01 25 93

96 01 25 94

11

Wall mounting

E

96 01 33 57

96 01 33 61

96 01 33 65

96 01 33 69 96 01 33 70

15

Wall mounting

E

96 01 33 58

96 01 33 62

96 01 33 66

18.5

Wall mounting

E

96 01 33 59

96 01 33 63

96 01 33 67

96 01 33 71

22

Wall mounting

E

96 01 33 60

96 01 33 64

96 01 33 68

96 01 33 72

Technical data

Delta Control 2000

Delta Control 2000 MEH Motor

Product numbers

Full-size [kW]

Half-size [kW]

Mounting of control cabinet

Starting full-size

Starting half-size

Delta Control 2000 MEH for 3 pumps (1 full-size and 2 half-size)

Delta Control 2000 MEH for 4 pumps (2 full-size and 2 half-size)

1.1

0.75 "

Wall mounting

DOL

E

96 01 16 91

96 01 17 11

1.5

1.1 "

Wall mounting

DOL

E

96 01 16 92

96 01 17 12

2.2

1.1 "

Wall mounting

DOL

E

96 01 16 93

96 01 17 13

2.2

1.5

Wall mounting

DOL

E

96 01 16 94

96 01 17 14

3

1.5

Wall mounting

DOL

E

96 01 16 95

96 01 17 15

SD

E

96 01 17 03

96 01 17 23

3

2.2

Wall mounting

DOL

E

96 01 16 96

96 01 17 16

SD

E

96 01 17 04

96 01 17 24

4

2.2

Wall mounting

DOL

E

96 01 16 97

96 01 17 17

SD

E

96 01 17 05

96 01 17 25

4

3

Wall mounting

DOL

E

96 01 16 98

96 01 17 18

SD

E

96 01 17 06

96 01 17 26

5.5

3

Wall mounting

DOL

E

96 01 16 99

96 01 17 19

SD

E

96 01 17 07

96 01 17 27

DOL

E

96 01 17 00

96 01 17 20 96 01 17 28

5.5

4

Wall mounting

7.5

4

Wall mounting

11

5.5

Wall mounting

15

11

Wall mounting

18,5

11

Wall mounting

22

11

Wall mounting

18.5

15

Wall mounting

22

15

Wall mounting

22

18.5

Wall mounting

SD

E

96 01 17 08

DOL

E

96 01 17 01

96 01 17 21

SD

E

96 01 17 09

96 01 17 29

DOL

E

96 01 17 02

96 01 17 22

SD

E

96 01 17 10

96 01 17 30

DOL

E

96 01 36 05

96 01 36 11

SD

E

96 01 36 06

96 01 36 12

DOL

E

96 01 36 07

96 01 36 13

SD

E

96 01 36 08

96 01 36 14

DOL

E

96 01 36 09

96 01 36 15

SD

E

96 01 36 10

96 01 36 16

DOL

E

96 01 36 17

96 01 36 23

SD

E

96 01 36 18

96 01 36 24

DOL

E

96 01 36 19

96 01 36 25

SD

E

96 01 36 20

96 01 36 26

DOL

E

96 01 36 29

96 01 36 35

SD

E

96 01 36 30

96 01 36 36

Delta Control MES Product numbers

Motor [kW]

Mounting of control cabinet

Starting full-size

11

Wall mounting

E/DOL

96 01 3461

96 01 34 63

96 01 34 65

11

Wall mounting

E/SD

96 01 34 62

96 01 34 64

96 01 34 66

15

Wall mounting

E/DOL

96 01 34 67

96 01 34 69

96 01 34 71

15

Wall mounting

E/SD

96 01 34 68

96 01 34 70

96 01 34 72

18,5

Wall mounting

E/DOL

96 01 34 73

96 01 34 75

96 01 34 77

18,5

Wall mounting

E/SD

96 01 34 74

96 01 34 76

96 01 34 78

22

Wall mounting

E/DOL

96 01 34 79

96 01 34 81

96 01 34 83

22

Wall mounting

E/SD

96 01 34 80

96 01 34 82

96 01 34 84

Delta Control 2000 MES for 2 pumps

Delta Control 2000 MES for 3 pumps

Delta Control 2000 MES for 4 pumps

Delta Control 2000 ME (PO) Description Delta Control 2000 ME (PO)

Product number 96 01 20 91

Supply voltage: 1 x 230 V +6%/–10%, N, 50 Hz, PE. Enclosure class: IP 42.

41

Optional equipment

Optional equipment is fitted from factory prior to delivery. Therefore, it is necessary to order the required optional equipment at the same time as ordering the Control 2000 or Delta Control 2000.

PMU 2000 The PMU 2000 is fitted in the front door of the control cabinet instead of the PFU 2000 control panel. The PMU 2000 enables regular optimization of operation and read-out of operating data. Description (language)

Mounting

Reference number

Danish

In front door

96 02 00 52

English

In front door

96 02 00 53

French

In front door

96 02 00 54

Dutch

In front door

96 02 00 55

Italian

In front door

96 02 00 56

Swedish

In front door

96 02 00 57

German

In front door

96 02 00 58

Portuguese

In front door

96 02 00 59

Spanish

In front door

96 02 00 60

Finnish

In front door

96 02 00 62

Control 2000 Delta Control 2000

Switching off of neutral lead As standard, the Control 2000 and Delta Control 2000 are supplied with a main switch switching off all three phases. If required, the controller 2000 can be supplied with a main switch switching off the three phases and the neutral lead. Description

Mounting

Reference number

Main switch incorporating the switching off of the neutral lead (40 A)

In front door

96 02 00 23

Main switch incorporating the switching off of the neutral lead (100 A)

In front door

96 02 00 22

Main switch incorporating the switching off of the neutral lead (175 A)

In front door

96 02 00 21

Main switch incorporating the switching off of the neutral lead (250 A)

In front door

96 02 00 20

Main switch incorporating the switching off of the neutral lead (400 A)

In front door

96 02 00 19

Main switch incorporating the switching off of the neutral lead (630 A)

In front door

96 02 00 18

Main switch incorporating the switching off of the neutral lead (800 A)

In front door

96 02 00 17

Main switch incorporating the switching off of the neutral lead (1250 A)

In front door

96 02 00 16

Main switch incorporating the switching off of the neutral lead (1750 A)

In front door

96 02 00 15

Main switch incorporating the switching off of the neutral lead (2000 A)

In front door

96 02 00 14

Main switch incorporating the switching off of the neutral lead (2500 A)

In front door

96 02 00 13

Emergency operation switch The emergency operation switch enables emergency operation if fault occurs in the control cabinet. Order one emergency operation switch for each pump. Mounting

Reference number

Pump for mains operation

Inside control cabinet

96 02 00 98

Pump with external frequency converter

Inside control cabinet

96 02 00 99

Pump with MGE-motor

Inside control cabinet

96 02 01 00

Description

Example: If emergency operation switches are required for Delta Control 2000 MFH with four pumps, order the following: • two 96 02 00 98 (for mains-operated pumps) and • two 96 02 00 99 (for half-size pumps).

42

Optional equipment

Control 2000 Delta Control 2000

Phase-failure protection

Panel light

If required, protection against phase failure (i.e. failure of one or two phases) is available. In case of phase failure the system is cut out.

The panel light is lit whenever the door of the control cabinet is opened. Description

Description Phase-failure protection

Mounting Inside control cabinet

Reference number

Mounting

Reference number

Inside control cabinet

96 02 01 25

A voltmeter indicates the mains voltage between the individual phases. Mounting

Reference number

Voltmeter

In front door

96 02 01 18

Voltmeter (with changeover switch)

In front door

96 02 01 19

Ammeter An ammeter indicates the power consumption for a single phase. Mounting

Reference number

Ammeter (6 A)

In front door

96 02 01 20

Ammeter (15 A)

In front door

96 02 01 21

Ammeter (40 A)

In front door

96 02 01 22

Description

96 02 01 26

To supplement the documentation supplied with the system, an extra set may be supplied, consisting of: • Installation and Operating Instructions, • Wiring Diagram, • List of Default Values. This extra set may be ordered under the following numbers:

Voltmeter

Description

Inside control cabinet

Extra documentation

If required, the system can be protected against stroke of lightning.

Lightning protection

Reference number

96 02 01 17

Lightning protection

Description

Panel light

Mounting

Ammeter (100 A)

In front door

96 02 01 23

Ammeter (150 A)

In front door

96 02 01 24

Description (language)

Reference number

English

96 02 00 37

Danish

96 02 00 38

French

96 02 00 39

Dutch

96 02 00 40

Italian

96 02 00 41

Swedish

96 02 00 42

German

96 02 00 43

Spanish

96 02 00 45

Enclosure class As standard, the system is supplied in enclosure class IP 54. The Control 2000 and Delta Control 2000 are also available without control cabinet in enclosure class IP 00 with all components mounted on one back plate prepared for mounting in a control cabinet or panel. Reference number

Description

Operating light

Built-in version

IP 00

96 02 00 50

The operating light for a pump is lit when the pump is in operation. Order one light for each pump. Description Operating light

Mounting

Reference number

In front door

96 02 01 39

Fault light The fault light for a pump is lit if a fault occurs in the pump. Order one light for each pump. Description Fault light

Mounting

Reference number

In front door

96 02 01 40

43

Accessories

Control 2000 Delta Control 2000

The following accessories can be ordered separately and fitted/replaced at any time. Contrary to optional equipment, accessories will not be fitted from factory.

PMU 2000 As an accessory to all controllers, the PMU 2000 can be ordered in enclosure class IP 42. The unit can be located outside the control cabinet, if required. The PMU 2000 enables regular optimization of operation and read-out of operating data. Description (language)

Reference number

Danish

62 57 28 41

English

62 57 28 47

French

62 57 28 45

Dutch

62 57 28 43

Italian

62 57 28 46

Swedish

62 57 28 40

German

62 57 28 44

Portuguese

62 57 28 49

Spanish

62 57 28 48

Finnish

62 57 28 42

PCU 2000 The PCU 2000 enables control and monitoring of the system via an external SCADA system. The PCU 2000 in enclosure class IP 42 is supplied separately for mounting outside the Control 2000 or Delta Control 2000 control cabinet. The PCU 2000 offers remote fault indication of operation, fault and local operation via potential-free changeover contacts. The PCU 2000 also offers the possibility of external setpoint influence and on/off operation of the system. Description

Max. number of pumps

Reference number

PCU 2000

2

62 55 22 41

PCU 2000

4

62 55 24 41

If the system consists of more than four pumps, two PCU 2000 units must be connected.

44

45

46

47

Back.fm Page 48 Friday, January 9, 2004 8:51 AM

Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence

V7 14 63 70 01 04 Repl. V7 14 63 70 03 00

GB

GRUNDFOS A/S . DK-8850 Bjerringbro . Denmark Telephone: +45 87 50 14 00. www.grundfos.com

Subject to alterations.